Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2024-07-03 12:19:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1395.38 | 6005.71 | 6005.71 |
Net Site Energy | 1395.38 | 6005.71 | 6005.71 |
Total Source Energy | 3068.07 | 13204.93 | 13204.93 |
Net Source Energy | 3068.07 | 13204.93 | 13204.93 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 48.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 135.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 272.03 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 165.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 171.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 38.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 746.75 | 648.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 48.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 135.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 15.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 165.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 171.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 11.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 18.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 48.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 135.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 272.03 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 165.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 171.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 38.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 370.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1507.34 | 738.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1335.99 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3213.99 | 2791.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 370.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1507.34 | 738.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1335.99 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3213.99 | 2791.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 746.749 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 746.749 | 100.00 |
Total On-Site and Utility Electric Sources | 746.749 | 100.00 |
Total Electricity End Uses | 746.749 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 8.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4649.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1_SUPPHEATCOIL | PSZ-AC_2:2_SUPPHEATCOIL | PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 63.19 | 0.00 | 15.80 | 31.59 | 15.80 |
Gross Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Above Ground Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 63.19 | 0.00 | 15.80 | 31.59 | 15.80 |
Gross Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Above Ground Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 63.19 | 63.19 | 9.2637 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 11.9458 | 18.52 | 1072.7618 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 63.19 | 63.19 | 10.6047 | 2.48 | 594.7744 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 63.19 | 63.19 | 10.6047 | 2.48 | 594.7744 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.2637 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.9458 | 18.52 | 1072.7618 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 10.6047 | 1.24 | 594.7744 | |||||||
Conditioned Total | 232.34 | 10.6047 | 1.24 | 594.7744 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 10.6047 | 2.48 | 594.7744 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 12-FEB-07:10 | 01-FEB-13:00 | - | - | - | - | - | - | - | - | - | - | 01-APR-12:20 |
Heating | 73161.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 739.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 7971.08 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6170.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23141.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 936.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 91604.90 | 46124.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 73161.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 739.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 6748.08 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6170.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 23141.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 137.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 261.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 538.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 153.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 430.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 141.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 130.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 861.52 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 525.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 185.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 121.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2364.95 | 703.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 661.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1852.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3707.96 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2259.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 800.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 523.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 10178.71 | 3026.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 661.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1852.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3707.96 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2259.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 800.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 523.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 10178.71 | 3026.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.30 |
KITCHEN DIRECT AIR | 1.47 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.30 | 2.30 | 2.30 | 2.30 | 2.30 | 2.30 | 1.00 | 1.00 | 2.30 |
PSZ-AC_2:2 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.00 | 1.000000 | 1.47 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.30 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.47 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.30 | 3724.60 |
PSZ-AC_2:2_ADDAQ FAN | 1.47 | 2445.71 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.30 | 2.30 | 2.30 | 2.30 | 57018.26 | 38202.23 | 32.22 | 57018.26 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.47 | 1.47 | 1.47 | 1.47 | 36542.05 | 24483.18 | 30.00 | 36542.05 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 HP COOLING COIL | 2.30 | 1.15 | 1.53 | 57018.26 | 28509.13 | 0.701080 | 0.701080 |
PSZ-AC_2:2 HP COOLING COIL | 1.47 | 0.735774 | 0.981033 | 36542.05 | 18271.03 | 0.701080 | 0.701080 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | Design Size Speed 2 Gross Rated Heating Capacity [W] | Design Size Speed 1 Gross Rated Heating Capacity [W] | Design Size Resistive Defrost Heater Capacity | |
PSZ-AC_1:1 HEATING COIL | 2.30 | 1.15 | 57018.26 | 28509.13 | 0.000000 |
PSZ-AC_2:2 HEATING COIL | 1.47 | 0.735774 | 36542.05 | 18271.03 | 0.000000 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_SUPPHEATCOIL | 57018.26 |
PSZ-AC_2:2_SUPPHEATCOIL | 36542.05 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 29.76 | 63.19 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 9.264 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 126.051 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 11.946 | 281.409 | 791.353 | 0.000 | 0.000 | 0.000 | 1084.708 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 1076.175 | 9.264 | 12.293 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1076.175 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1387.759 | 11.946 | 221.217 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1387.759 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 493.000 | 4.244 | 78.587 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 493.000 | 493.000 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 730.000 | 6.284 | 116.366 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 730.000 | 730.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.3836 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.3836 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.508 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.508 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | -0.36752283E-16 | 0.36650618E-15 | -0.17323971E-14 | 0.96945811E-16 |
24 | 3 | -0.69118654E-08 | 0.27160578E-06 | -0.56853996E-04 | 0.15386634E-12 |
25 | 2 | 0.11860501E-03 | 0.58949329E-02 | 1.1525899 | -0.75054507E-04 |
26 | 1 | -0.13685427 | 0.15202565 | -17.175506 | 0.33646671 |
27 | 0 | 0.39128804 | 0.96631513E-01 | 16.277526 | |
28 | 4 | -0.17323971E-14 | 0.36650618E-15 | -0.36752283E-16 | 0.96945811E-16 |
29 | 3 | -0.56853996E-04 | 0.27160578E-06 | -0.69118654E-08 | 0.15386634E-12 |
30 | 2 | 1.1525899 | 0.58949329E-02 | 0.11860501E-03 | -0.75054507E-04 |
31 | 1 | -17.175506 | 0.15202565 | -0.13685427 | 0.33646671 |
32 | 0 | 16.277526 | 0.96631513E-01 | 0.39128804 | |
33 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
34 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
35 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
36 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
37 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
38 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
39 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
40 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.57_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.57_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 21.722 | 0.5184 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 4 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 5 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 4 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 5 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 4 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 5 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone DINING | 1.2500 |
3 | Zone KITCHEN | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone DINING | 1.1500 |
3 | Zone KITCHEN | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 26219.31592 | 30152.21330 | 1.99663 | 2.29613 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 8711.76769 | 10889.70961 | 0.65013 | 0.81266 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -6.30000 | 2.29779E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16833.00421 | 19357.95485 | 1.27961 | 1.47155 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 1170.77529 | 1463.46912 | 8.67700E-002 | 1.14133 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -6.30000 | 2.29779E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 34793.72 | 2.29613 | 2.29613 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 23874.11 | 0.81266 | 0.81266 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 28956.96 | 1.47155 | 1.47155 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 48333.43 | 1.14133 | 1.14133 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.29613 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.47155 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.29613 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.29613 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.29613 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.29613 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.29613 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.29613 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.47155 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.47155 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.47155 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.47155 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.47155 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.47155 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.29613 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.47155 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.29613 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.29613 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3724.59993 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.29613 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.29613 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.29613 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.29613 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.29613 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.14806 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.53075 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 57018.26000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 28509.13000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 57018.26000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38202.23387 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 57018.25950 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 2.29613 |
42 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.14806 |
43 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 57018.25950 |
44 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 28509.12975 |
45 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
46 | Coil:Heating:Electric | PSZ-AC_1:1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 57018.25950 |
47 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.47155 |
48 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
49 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.47155 |
50 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2445.70983 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.47155 |
52 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.47155 |
53 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.47155 |
54 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.47155 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.47155 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73577 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98103 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36542.05000 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18271.02500 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36542.05000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24483.17610 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 30.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 36542.05388 |
66 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
67 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.47155 |
68 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73577 |
69 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 36542.05388 |
70 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 18271.02694 |
71 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
72 | Coil:Heating:Electric | PSZ-AC_2:2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 36542.05388 |
73 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
74 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
75 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
76 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
77 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | 55386.2 | 10.20 | 10.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | 35496.1 | 10.76 | 10.71 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | 58863.0 | 32389.7 | 7.92 | 2 |
2 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | 37724.3 | 20758.0 | 7.89 | 2 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 7.44 | 23.24 | 7.44 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 15.80 | 15.80 | 15.80 | 90.00 | 90.00 | 7.11 | 2.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 14.88 | 46.47 | 14.88 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 31.59 | 31.59 | 31.59 | 180.00 | 90.00 | 14.23 | 2.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 7.44 | 23.24 | 7.44 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 15.80 | 15.80 | 15.80 | 270.00 | 90.00 | 7.11 | 2.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.384 | 0.358 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.384 | 0.358 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.384 | 0.351 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.384 | 0.351 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 6.1265786547E-002 | 0.2000136775 | Pass | Pass | 0.4721403007 | 1.4560864068 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2060776156 | 0.5446456033 | Pass | Pass | 3.2084288385E-002 | 0.1005941501 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2393020763 | 0.2275855509 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 529.82 | 69.34 | 453.78 | 20.52 | 780.57 | 1854.03 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 23.24 | 7.44 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 46.47 | 14.88 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 23.24 | 7.44 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.348 | 0.384 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.348 | 0.384 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.348 | 0.384 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.348 | 0.384 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.57_SHGC_EAST_0.25 | 15.80 | 0.00 | 0.00 | 15.80 | 15.80 | 3.241 | 0.251 | 0.276 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.25 | 31.59 | 0.00 | 0.00 | 31.59 | 31.59 | 3.241 | 0.251 | 0.276 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.57_SHGC_WEST_0.25 | 15.80 | 0.00 | 0.00 | 15.80 | 15.80 | 3.241 | 0.251 | 0.276 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 63.19 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 63.19 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.2637 | 116.17 | 1076.18 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 19.58 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.9458 | 116.17 | 1387.76 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 25.25 |
Interior Lighting Total | 10.6047 | 232.34 | 2463.93 | 44.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 2625.88 | AstronomicalClock | - | 83.77 | 83.77 | 41.29 | |
Exterior Lighting Total | 2625.88 | 41.29 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 57018.26 | 39974.36 | 17043.90 | 0.70 | 3.20 | |||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36542.05 | 25618.90 | 10923.15 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 HP COOLING COIL | 55386.2 | 10.20 | 10.16 | ||||
PSZ-AC_2:2 HP COOLING COIL | 35496.1 | 10.76 | 10.71 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 58863.0 | 32389.7 | 7.92 | 2 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 37724.3 | 20758.0 | 7.89 | 2 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 57018.26 | 3.40 | |
PSZ-AC_1:1_SUPPHEATCOIL | Coil:Heating:Electric | 57018.26 | 1.00 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 36542.05 | 3.40 | |
PSZ-AC_2:2_SUPPHEATCOIL | Coil:Heating:Electric | 36542.05 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 1.56 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 966.87 | 2.30 | 3724.60 | 1622.12 | 1.00 | 1.23 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 966.87 | 1.47 | 2445.71 | 1662.00 | 1.00 | 1.26 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 21.72 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 26219.32 | 30152.21 | 259.55 | 1.997 | 2.296 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 23.89 | 23.87 | 0.01092 | 34.30 | 0.01447 | 0.416 | 0.00 |
KITCHEN | 16833.00 | 19357.95 | 166.63 | 1.280 | 1.472 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00991 | 33.55 | 0.01447 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 8711.77 | 10889.71 | 93.74 | 0.650 | 0.813 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00786 | -6.30 | 0.00230 | 0.416 | 0.00 |
KITCHEN | 1170.78 | 1463.47 | 12.60 | 0.087 | 1.141 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.89 | 18.89 | 0.00553 | -6.30 | 0.00230 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.30 | 2.30 | 0.81 | 0.81 | 2.2961 | 2.2961 | 2.2961 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.47 | 1.47 | 1.14 | 1.14 | 1.4715 | 1.4715 | 1.4715 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 57018.260 | 39974.362 | 2.296130 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 28509.13 | 18761.68 | 1.530753 | 25.77 | 19.06 | 0.01156288 | 11.42 | 11.20 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 27.1798 | 23.87 | 0.01091869 | 56.9108 | 26212.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 57018.260 | 57018.260 | 2.296125 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 28509.13 | 21939.24 | 1.148063 | 16.08 | 11.47 | 0.00684922 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 36.2398 | 21.11 | 0.00785644 | 48.6513 | 8711.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_1:1 | 57018.260 | 57018.260 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 57018.26 | 43878.49 | 2.296125 | 16.08 | 11.47 | 0.00684922 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 18.1199 | 21.11 | 0.00785644 | 48.6513 | 8711.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 36542.050 | 25618.900 | 1.471550 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 18271.03 | 11446.27 | 0.981033 | 31.87 | 22.19 | 0.01344861 | 13.61 | 12.10 | 0.00850000 | 33.55 | 0.01447170 | 23.31 | 116.3399 | 26.10 | 0.00991248 | 45.2949 | 16833.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 36542.054 | 36542.054 | 1.471549 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 18271.03 | 18271.03 | 0.735774 | -0.88 | -2.03 | 0.00289581 | 30.00 | 17.65 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 155.1201 | 18.89 | 0.00496275 | 35.4328 | 847.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_2:2 | 36542.054 | 36542.054 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 36542.05 | 36542.05 | 1.471549 | -0.88 | -2.03 | 0.00289581 | 30.00 | 17.65 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 77.5600 | 18.89 | 0.00496275 | 35.4328 | 847.46 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 57018.260 | 39974.362 | 2.296130 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3348 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.296125 | 2.66574762 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 28509.13 | 18761.68 | 1.0000 | 1.77716871 | 1.530753 | 25.77 | 19.06 | 0.01156288 | 55366.7 | 11.42 | 11.20 | 0.00850000 | 32911.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28509.13 | 34.40 | 0.01447326 | 23.54 | 0.41605618 | 27.1798 | 23.86 | 0.01091869 | 23.87 | 0.01091869 | 56.9108 | 26212.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 57018.260 | 57018.260 | 2.296125 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.296125 | 2.66574762 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 28509.13 | 21939.24 | 1.0000 | 1.33287381 | 1.148063 | 16.08 | 11.47 | 0.00684922 | 33490.1 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28509.13 | -6.30 | 0.00229779 | -6.30 | 0.41605618 | 36.2398 | 21.03 | 0.00785644 | 21.11 | 0.00785644 | 48.6513 | 8711.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57018.260 | 57018.260 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.296125 | 2.66574762 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 57018.26 | 43878.49 | 1.0000 | 2.66574762 | 2.296125 | 16.08 | 11.47 | 0.00684922 | 33490.1 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57018.26 | -6.30 | 0.00229779 | -6.30 | 0.41605618 | 18.1199 | 21.03 | 0.00785644 | 21.11 | 0.00785644 | 48.6513 | 8711.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36542.050 | 25618.900 | 1.471550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.8403 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.471549 | 1.70843330 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 18271.03 | 11446.27 | 1.0000 | 1.13895669 | 0.981033 | 31.87 | 22.19 | 0.01344861 | 66451.4 | 13.61 | 12.10 | 0.00850000 | 35147.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18271.03 | 33.55 | 0.01447170 | 23.31 | 1.14133354 | 116.3399 | 26.06 | 0.00991248 | 26.10 | 0.00991248 | 45.2949 | 16833.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 36542.054 | 36542.054 | 1.471549 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.471549 | 1.70843330 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | Sensible | 18271.03 | 18271.03 | 1.0000 | 0.85421665 | 0.735774 | -0.88 | -2.03 | 0.00289581 | 6349.5 | 30.00 | 17.65 | 0.00800000 | 50598.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18271.03 | -6.30 | 0.00229779 | -6.30 | 1.14133354 | 155.1201 | 17.84 | 0.00496275 | 18.89 | 0.00496275 | 35.4328 | 847.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36542.054 | 36542.054 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.471549 | 1.70843330 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | Sensible | 36542.05 | 36542.05 | 1.0000 | 1.70843330 | 1.471549 | -0.88 | -2.03 | 0.00289581 | 6349.5 | 30.00 | 17.65 | 0.00800000 | 50598.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36542.05 | -6.30 | 0.00229779 | -6.30 | 1.14133354 | 77.5600 | 17.84 | 0.00496275 | 18.89 | 0.00496275 | 35.4328 | 847.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4639.33 | 4365.00 | 2224.50 |
KITCHEN | 5409.00 | 6136.83 | 4574.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5477.50 | 6626.67 | 4649.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 54.00 | 61.33 | 0.00 | 3.33 |
KITCHEN | 0.00 | 205.50 | 0.00 | 5.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 54.00 | 231.33 | 0.00 | 8.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.297 | 4.251 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.827 | 0.031 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.067 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.142 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 11211134.35 | 0.00 | 11211134.35 | 10709627.02 | 21920761.37 | 13120747.55 | 1380.31 | 7379.50 | 0.18 | 451.90 |
KITCHEN | 30753831.18 | 0.00 | 30753831.18 | 132069.92 | 30885901.11 | 35993094.65 | 1427.01 | 7301.51 | 31.47 | 719.00 |
Total Facility | 41964965.53 | 0.00 | 41964965.53 | 10841696.94 | 52806662.48 | 49113842.20 | 1437.04 | 7380.05 | 31.51 | 871.39 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4161 | 0.0000 | 0.4161 | 0.4118 | 0.8279 | 0.4161 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.1413 | 0.0000 | 1.1413 | 0.0030 | 1.1443 | 1.1413 | 0.00 | 7187.00 | 0.00 |
Total Facility | 1.5574 | 0.0000 | 1.5574 | 0.4148 | 1.9722 | 1.5574 | 0.00 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 15111049.52 | 0.00 | 15111049.52 | 13120747.55 | 1343.51 | 2.00 | 7414.49 | 451.90 |
PSZ-AC_2:2 | 41452059.64 | 0.00 | 41452059.64 | 35993094.65 | 1393.93 | 2.38 | 7363.69 | 719.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5608 | 0.0000 | 0.5608 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.5384 | 0.0000 | 1.5384 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 260.30 | 0.00 | 7378.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 7906.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 0.5608 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.5384 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 373 |
Defaulted Fields | 292 |
Fields with Defaults | 921 |
Autosized Fields | 49 |
Autosizable Fields | 119 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 746.75 | 5921.04 | 17-JAN-01:10 | 91604.90 | 12-FEB-07:10 |
Electricity:Building | 324.80 | 2625.15 | 01-JAN-01:10 | 19780.88 | 02-JAN-11:10 |
Electricity:Zone:DINING | 89.91 | 431.44 | 01-JAN-01:10 | 4898.81 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 316.86 | 2488.87 | 01-JAN-01:10 | 16486.83 | 02-JAN-11:10 |
InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 234.89 | 2193.72 | 01-JAN-01:10 | 14882.07 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 272.03 | 2119.28 | 01-JAN-01:10 | 14269.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 272.03 | 2119.28 | 01-JAN-01:10 | 14269.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 201.70 | 1849.27 | 01-JAN-01:10 | 10339.04 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 38.38 | 594.45 | 27-JAN-23:30 | 3931.14 | 04-APR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 30.44 | 508.67 | 14-JAN-23:30 | 1634.31 | 04-AUG-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 11.78 | 0.00 | 01-JAN-11:10 | 997.22 | 04-AUG-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 18.66 | 475.34 | 27-JAN-01:10 | 637.09 | 19-JAN-13:50 |
ElectricityPurchased:Facility | 746.75 | 5921.04 | 17-JAN-01:10 | 91604.90 | 12-FEB-07:10 |
ElectricityPurchased:Plant | 746.75 | 5921.04 | 17-JAN-01:10 | 91604.90 | 12-FEB-07:10 |
Cogeneration:ElectricityPurchased | 746.75 | 5921.04 | 17-JAN-01:10 | 91604.90 | 12-FEB-07:10 |
General:Cogeneration:ElectricityPurchased | 746.75 | 5921.04 | 17-JAN-01:10 | 91604.90 | 12-FEB-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 746.75 | 5921.04 | 17-JAN-01:10 | 91604.90 | 12-FEB-07:10 |
ElectricityNet:Plant | 746.75 | 5921.04 | 17-JAN-01:10 | 91604.90 | 12-FEB-07:10 |
Cogeneration:ElectricityNet | 746.75 | 5921.04 | 17-JAN-01:10 | 91604.90 | 12-FEB-07:10 |
General:Cogeneration:ElectricityNet | 746.75 | 5921.04 | 17-JAN-01:10 | 91604.90 | 12-FEB-07:10 |
Electricity:HVAC | 350.22 | 0.00 | 01-JAN-01:10 | 79331.81 | 12-FEB-07:10 |
Fans:Electricity | 165.77 | 0.00 | 01-JAN-01:10 | 6170.31 | 01-JAN-22:10 |
General:Fans:Electricity | 165.77 | 0.00 | 01-JAN-01:10 | 6170.31 | 01-JAN-22:10 |
Cooling:Electricity | 135.89 | 0.00 | 01-JAN-00:10 | 24674.05 | 07-JUL-12:00 |
General:Cooling:Electricity | 135.89 | 0.00 | 01-JAN-00:10 | 24674.05 | 07-JUL-12:00 |
Heating:Electricity | 48.56 | 0.00 | 01-JAN-00:20 | 73161.50 | 12-FEB-07:10 |
General:Heating:Electricity | 48.56 | 0.00 | 01-JAN-00:20 | 73161.50 | 12-FEB-07:10 |
ExteriorLights:Electricity | 41.29 | 0.00 | 01-JAN-07:50 | 2625.88 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 41.29 | 0.00 | 01-JAN-07:50 | 2625.88 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-11:30 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-11:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 648.63 | 1838.65 | 20-JAN-01:40 | 46124.30 | 01-FEB-14:00 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Plant | 171.48 | 0.00 | 20-JAN-01:40 | 23141.15 | 01-FEB-14:00 |
WaterSystems:NaturalGas | 171.48 | 0.00 | 20-JAN-01:40 | 23141.15 | 01-FEB-14:00 |
Water Heater:WaterSystems:NaturalGas | 171.48 | 0.00 | 20-JAN-01:40 | 23141.15 | 01-FEB-14:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:20 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:20 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:20 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:20 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:20 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:20 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:20 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1285.94 | 2416.73 | 12-FEB-01:10 | 135435.94 | 02-AUG-13:00 |
EnergyTransfer:Building | 480.99 | 1208.36 | 12-FEB-01:10 | 38392.39 | 18-AUG-11:10 |
EnergyTransfer:Zone:KITCHEN | 340.09 | 1208.36 | 12-FEB-01:10 | 21907.08 | 13-OCT-04:10 |
Refrigeration:EnergyTransfer | 146.75 | 2416.73 | 12-FEB-01:10 | 7834.84 | 04-APR-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 73.38 | 1208.36 | 12-FEB-01:10 | 3917.42 | 04-APR-10:40 |
General:Refrigeration:EnergyTransfer | 73.38 | 1208.36 | 12-FEB-01:10 | 3917.42 | 04-APR-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 73.38 | 1208.36 | 12-FEB-01:10 | 3917.42 | 04-APR-10:40 |
EnergyTransfer:Plant | 203.23 | 1208.36 | 12-FEB-01:10 | 20828.77 | 31-JAN-13:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.21 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 60.17 | 1059.55 | 27-JAN-01:10 | 2238.70 | 19-JAN-13:50 |
EnergyTransfer:Zone:DINING | 140.90 | 0.00 | 01-JAN-01:10 | 25748.84 | 11-FEB-20:00 |
Heating:EnergyTransfer | 31.49 | 0.00 | 01-JAN-00:10 | 25748.84 | 11-FEB-20:00 |
Heating:EnergyTransfer:Zone:DINING | 31.48 | 0.00 | 01-JAN-00:10 | 25748.84 | 11-FEB-20:00 |
General:Heating:EnergyTransfer | 31.49 | 0.00 | 01-JAN-00:10 | 25748.84 | 11-FEB-20:00 |
General:Heating:EnergyTransfer:Zone:DINING | 31.48 | 0.00 | 01-JAN-00:10 | 25748.84 | 11-FEB-20:00 |
Cooling:EnergyTransfer | 376.13 | 0.00 | 01-JAN-01:10 | 35223.37 | 18-AUG-13:00 |
Cooling:EnergyTransfer:Zone:DINING | 109.42 | 0.00 | 01-JAN-01:10 | 21845.66 | 01-AUG-17:10 |
General:Cooling:EnergyTransfer | 376.13 | 0.00 | 01-JAN-01:10 | 35223.37 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:DINING | 109.42 | 0.00 | 01-JAN-01:10 | 21845.66 | 01-AUG-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 876.23 | 12-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 876.23 | 12-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 266.71 | 0.00 | 01-JAN-01:10 | 18086.16 | 13-OCT-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 266.71 | 0.00 | 01-JAN-01:10 | 18086.16 | 13-OCT-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 129.85 | 0.00 | 01-JAN-00:10 | 18313.25 | 01-FEB-13:20 |
PlantLoopHeatingDemand:Plant | 129.85 | 0.00 | 01-JAN-00:10 | 18313.25 | 01-FEB-13:20 |
WaterSystems:PlantLoopHeatingDemand | 129.85 | 0.00 | 01-JAN-00:10 | 18313.25 | 01-FEB-13:20 |
General:WaterSystems:PlantLoopHeatingDemand | 129.85 | 0.00 | 01-JAN-00:10 | 18313.25 | 01-FEB-13:20 |
EnergyTransfer:HVAC | 601.72 | 0.00 | 01-JAN-00:20 | 87438.12 | 07-JUL-12:00 |
CoolingCoils:EnergyTransfer | 483.34 | 0.00 | 01-JAN-00:10 | 87438.12 | 07-JUL-12:00 |
HeatingCoils:EnergyTransfer | 118.38 | 0.00 | 01-JAN-00:20 | 73061.50 | 12-FEB-07:10 |
WaterSystems:EnergyTransfer | 129.85 | 0.00 | 01-JAN-00:10 | 18313.25 | 01-FEB-13:20 |
WaterUse:WaterSystems:EnergyTransfer | 129.85 | 0.00 | 01-JAN-00:10 | 18313.25 | 01-FEB-13:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 31.477 | -109.419 | 0.000 | 0.000 | 68.594 | 19.580 | 52.748 | 43.937 | 0.000 | 15.739 | 0.000 | 0.000 | -29.237 | 0.000 | -81.508 | -11.912 |
KITCHEN | 0.000 | 0.000 | 0.010 | -266.701 | 0.000 | 0.000 | 4.590 | 25.249 | 207.409 | 0.000 | 0.000 | 0.048 | 31.042 | 0.000 | 0.000 | 0.000 | -1.646 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.388 | 12.934 | 0.000 | 0.000 | 0.000 | -15.322 | -0.000 |
Total Facility | 0.000 | 0.000 | 31.487 | -376.120 | 0.000 | 0.000 | 73.184 | 44.830 | 260.157 | 43.937 | 0.000 | 18.175 | 43.976 | 0.000 | -29.237 | 0.000 | -98.476 | -11.912 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 16-SEP-02:61 | 0.00 | 0.00 | 0.00 | -33223.10 | 0.00 | 0.00 | 0.00 | 161.43 | 202.51 | 0.00 | 0.00 | 0.00 | 33763.63 | 0.00 | -887.83 | 0.00 | -16.64 | 0.00 |
KITCHEN | 15-APR-02:61 | 0.00 | 0.00 | 0.00 | -47429.21 | 0.00 | 0.00 | 0.00 | 208.16 | 1872.55 | 0.00 | 0.00 | 0.00 | 45512.14 | 0.00 | -0.00 | 0.00 | -163.65 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-SEP-02:61 | 0.00 | 0.00 | 0.00 | -64384.01 | 0.00 | 0.00 | 0.00 | 369.59 | 2075.06 | 0.00 | 0.00 | 96.74 | 62809.62 | 0.00 | -887.83 | 0.00 | -79.17 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-FEB-03:01 | 0.00 | 0.00 | 38926.32 | 0.00 | 0.00 | 0.00 | 0.00 | 161.43 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4432.09 | 0.00 | -784.41 | -34073.76 |
KITCHEN | 22-NOV-05:03 | 0.00 | 0.00 | 8381.84 | 0.00 | 0.00 | 0.00 | 21.07 | 277.55 | 5126.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -84.93 | -13722.39 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-FEB-03:01 | 0.00 | 0.00 | 38926.32 | 0.00 | 0.00 | 0.00 | 0.00 | 369.59 | 2075.06 | 0.00 | 0.00 | 102.74 | 0.00 | 0.00 | -4432.09 | 0.00 | -1658.77 | -35382.85 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2961 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.2961 | 0.1812 | 1.0000 | Not calculated | 0.4161 | 0.1812 | ||
PSZ-AC_2:2 | 1.4715 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.4715 | 0.1028 | 1.0000 | Not calculated | 0.1513 | 0.1028 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2961 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.2961 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1812 | ||
PSZ-AC_2:2 | 1.4715 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.4715 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1028 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2961 | 2.2961 | 2.2961 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4715 | 1.4715 | 1.4715 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2961 | 2.2961 | 2.2961 | 2.2961 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.4715 | 1.4715 | 1.4715 | 1.4715 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2961 | 2.2961 | 2.2961 | No | 0.4161 | 0.5120 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4715 | 1.4715 | 1.4715 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2961 | 2.2961 | 2.2961 | 2.2961 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.4715 | 1.4715 | 1.4715 | 1.4715 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 8.33 |
Number of hours not met | 8.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 48.56 | 73161.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 135.89 | 24674.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 44.83 | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.29 | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 15.55 | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 23.02 | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 165.77 | 6170.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 171.48 | 23141.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 11.78 | 997.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 18.66 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 310.41 | 746.75 |
Natural Gas | 477.16 | 648.63 |
Additional | 0.00 | 0.00 |
Total | 787.57 | 1395.38 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 192.95 |
Space Heating | 208.98 |
Space Cooling | 584.87 |
Fans (All) | 713.48 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1170.81 |
Miscellaneous (All) | 3213.99 |
Subtotal | 3213.99 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 738.03 |
Miscellaneous (All) | 2791.71 |
Subtotal | 2791.71 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.21 |
Space Heating | 3.48 |
Space Cooling | 9.74 |
Fans (All) | 11.88 |
Service Water Heating | 12.29 |
Receptacle Equipment | 53.69 |
Miscellaneous | 5.71 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8492.83 | 266.50 | 0.67 | 0.00 | 0.00 |
KITCHEN | 8033.83 | 661.00 | 65.17 | 0.00 | 0.00 |
ATTIC | 6143.17 | 637.17 | 653.00 | 773.17 | 553.50 |
Min | 6143.17 | 266.50 | 0.67 | 0.00 | 0.00 |
Max | 8492.83 | 661.00 | 653.00 | 773.17 | 553.50 |
Average | 7556.61 | 521.56 | 239.61 | 257.72 | 184.50 |
Sum | 22669.83 | 1564.67 | 718.83 | 773.17 | 553.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254357.67 | 364.67 | 2.67 | 0.00 | 0.00 |
KITCHEN | 16171.33 | 86.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254357.67 | 364.67 | 2.67 | 0.00 | 0.00 |
Average | 90176.33 | 150.44 | 0.89 | 0.00 | 0.00 |
Sum | 270529.00 | 451.33 | 2.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 7024.00 | 1736.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 4696.33 | 4060.33 | 3.33 | 0.00 | 0.00 |
ATTIC | 5634.17 | 1523.00 | 404.17 | 346.50 | 852.17 |
Min | 4696.33 | 1523.00 | 0.00 | 0.00 | 0.00 |
Max | 7024.00 | 4060.33 | 404.17 | 346.50 | 852.17 |
Average | 5784.83 | 2439.78 | 135.83 | 115.50 | 284.06 |
Sum | 17354.50 | 7319.33 | 407.50 | 346.50 | 852.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 211969.50 | 42755.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8430.83 | 7827.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 211969.50 | 42755.50 | 0.00 | 0.00 | 0.00 |
Average | 73466.78 | 16860.89 | 0.00 | 0.00 | 0.00 |
Sum | 220400.33 | 50582.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.604477E+09 | 7299.53 | 08-JAN-00:01 | -6.1 | -6.4 | 0.454225E+10 | 4413.13 | 31-JAN-12:50 | 19.03 | 13.61 |
February | 0.159892E+10 | 9980.10 | 13-FEB-05:03 | -5.1 | -7.7 | 0.427422E+10 | 4681.01 | 25-FEB-19:10 | 16.65 | 7.80 |
March | 0.389531E+10 | 13262.77 | 30-MAR-17:03 | 26.60 | 17.75 | 0.506785E+10 | 4681.44 | 11-MAR-19:30 | 26.60 | 17.75 |
April | 0.709615E+10 | 14163.96 | 17-APR-17:03 | 28.03 | 16.54 | 0.508364E+10 | 4681.32 | 15-APR-18:00 | 28.03 | 16.54 |
May | 0.117571E+11 | 16796.81 | 19-MAY-17:03 | 30.40 | 19.11 | 0.541087E+10 | 4681.49 | 20-MAY-18:19 | 24.10 | 18.33 |
June | 0.177883E+11 | 30476.80 | 15-JUN-02:61 | 21.78 | 18.19 | 0.528746E+10 | 4681.59 | 24-JUN-18:19 | 31.67 | 21.95 |
July | 0.200112E+11 | 31127.16 | 25-JUL-02:61 | 22.12 | 18.45 | 0.541527E+10 | 4681.78 | 01-JUL-18:00 | 22.12 | 18.45 |
August | 0.211918E+11 | 30393.93 | 26-AUG-02:61 | 22.12 | 17.57 | 0.547684E+10 | 4681.68 | 19-AUG-18:19 | 22.12 | 17.57 |
September | 0.141489E+11 | 33249.24 | 16-SEP-02:61 | 22.80 | 17.72 | 0.525029E+10 | 4681.48 | 09-SEP-18:49 | 22.80 | 17.72 |
October | 0.706178E+10 | 18048.28 | 17-OCT-02:61 | 18.12 | 17.15 | 0.514402E+10 | 4681.24 | 14-OCT-18:40 | 18.12 | 17.15 |
November | 0.314798E+10 | 8157.53 | 05-NOV-16:03 | 24.03 | 17.90 | 0.475807E+10 | 4681.01 | 04-NOV-18:30 | 24.03 | 17.90 |
December | 0.111813E+10 | 8239.07 | 12-DEC-14:00 | 22.80 | 17.07 | 0.460408E+10 | 4413.13 | 13-DEC-12:50 | 20.50 | 17.35 |
Annual Sum or Average | 0.109420E+12 | 0.603149E+11 | ||||||||
Minimum of Months | 0.604477E+09 | 7299.53 | -6.1 | -7.7 | 0.427422E+10 | 4413.13 | 16.65 | 7.80 | ||
Maximum of Months | 0.211918E+11 | 33249.24 | 30.40 | 19.11 | 0.547684E+10 | 4681.78 | 31.67 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203144E+11 | 36788.38 | 20-JAN-03:01 | 13.72 | 12.80 | 0.769926E+10 | 5122.98 | 31-JAN-11:00 | 17.20 | 13.29 |
February | 0.184853E+11 | 37971.66 | 22-FEB-03:01 | 13.72 | 8.01 | 0.698796E+10 | 5135.93 | 28-FEB-11:50 | 21.93 | 12.25 |
March | 0.213238E+11 | 45101.27 | 01-MAR-03:01 | 10.32 | 6.32 | 0.779106E+10 | 5135.98 | 09-MAR-11:50 | 20.68 | 16.45 |
April | 0.208025E+11 | 47485.97 | 15-APR-02:61 | 13.07 | 9.14 | 0.757299E+10 | 5135.98 | 21-APR-10:00 | 20.00 | 17.41 |
May | 0.225541E+11 | 43630.13 | 12-MAY-02:61 | 14.72 | 10.87 | 0.785180E+10 | 5135.98 | 24-MAY-10:00 | 18.30 | 16.86 |
June | 0.234094E+11 | 47170.96 | 10-JUN-02:11 | 14.30 | 9.40 | 0.760786E+10 | 5141.48 | 28-JUN-10:00 | 30.60 | 24.10 |
July | 0.247986E+11 | 32157.00 | 03-JUL-02:11 | 18.87 | 17.06 | 0.785874E+10 | 5146.61 | 07-JUL-10:50 | 32.02 | 24.15 |
August | 0.252273E+11 | 31444.38 | 26-AUG-02:61 | 22.12 | 17.57 | 0.786419E+10 | 5149.30 | 10-AUG-10:50 | 22.12 | 17.57 |
September | 0.231728E+11 | 42322.65 | 29-SEP-02:61 | 12.20 | 11.28 | 0.760303E+10 | 5135.99 | 05-SEP-10:00 | 12.20 | 11.28 |
October | 0.231941E+11 | 45716.48 | 12-OCT-02:61 | 11.60 | 7.13 | 0.781094E+10 | 5135.98 | 18-OCT-10:09 | 22.07 | 21.06 |
November | 0.217095E+11 | 44459.03 | 20-NOV-03:01 | 12.93 | 10.29 | 0.752081E+10 | 5135.98 | 27-NOV-11:50 | 20.82 | 17.42 |
December | 0.217141E+11 | 37309.60 | 12-DEC-03:01 | 13.80 | 13.18 | 0.771753E+10 | 5135.98 | 13-DEC-11:00 | 20.00 | 17.41 |
Annual Sum or Average | 0.266706E+12 | 0.918862E+11 | ||||||||
Minimum of Months | 0.184853E+11 | 31444.38 | 10.32 | 6.32 | 0.698796E+10 | 5122.98 | 12.20 | 11.28 | ||
Maximum of Months | 0.252273E+11 | 47485.97 | 22.12 | 17.57 | 0.786419E+10 | 5149.30 | 32.02 | 24.15 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 | 4.97 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 | 7.50 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.51 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.51 |
April | 0.00 | 0.00 | 01-APR-00:01 | 12.05 | 7.82 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.82 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 16.68 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 20.93 | 18.59 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.28 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 25.13 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.40 | 18.46 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.46 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.85 | 15.92 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.70 | 6.60 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.60 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124280E+11 | 36940.93 | 08-JAN-03:01 | -5.6 |
February | 0.717190E+10 | 38927.89 | 12-FEB-03:01 | -11.2 |
March | 0.160162E+10 | 10887.53 | 19-MAR-06:50 | 1.20 |
April | 0.550923E+09 | 11297.02 | 06-APR-04:01 | 0.92 |
May | 57217296.45 | 2928.91 | 11-MAY-06:10 | 8.17 |
June | 95495614.67 | 3404.23 | 13-JUN-23:01 | 26.52 |
July | 0.149001E+09 | 4023.33 | 16-JUL-23:01 | 28.12 |
August | 0.161034E+09 | 4164.39 | 18-AUG-23:01 | 28.72 |
September | 69583412.49 | 3086.24 | 05-SEP-23:01 | 25.73 |
October | 0.600405E+09 | 8151.91 | 26-OCT-06:10 | 2.20 |
November | 0.232509E+10 | 15707.10 | 22-NOV-03:02 | -2.8 |
December | 0.626691E+10 | 23014.09 | 18-DEC-03:02 | -3.9 |
Annual Sum or Average | 0.314772E+11 | |||
Minimum of Months | 57217296.45 | 2928.91 | -11.2 | |
Maximum of Months | 0.124280E+11 | 38927.89 | 28.72 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3052368.92 | 8192.58 | 27-JAN-05:03 | -5.7 |
February | 1660744.06 | 5738.56 | 13-FEB-05:03 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 16.68 |
June | 170802.17 | 1345.22 | 13-JUN-23:01 | 26.52 |
July | 1747985.23 | 3271.66 | 16-JUL-23:01 | 28.12 |
August | 1318375.24 | 3875.34 | 18-AUG-23:01 | 28.72 |
September | 30440.65 | 405.88 | 05-SEP-23:01 | 25.73 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.85 |
November | 531397.98 | 8387.99 | 22-NOV-05:03 | -2.9 |
December | 1158887.27 | 7259.00 | 04-DEC-05:03 | -2.8 |
Annual Sum or Average | 9671001.52 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 3052368.92 | 8387.99 | 28.72 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165449E+10 | 968.56 | 02-JAN-10:09 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.149855E+10 | 968.56 | 01-FEB-10:09 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.168084E+10 | 968.56 | 01-MAR-10:09 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.160761E+10 | 968.56 | 01-APR-16:10 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.166766E+10 | 968.56 | 01-MAY-09:09 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.162466E+10 | 968.56 | 01-JUN-09:09 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.165081E+10 | 968.56 | 01-JUL-16:10 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.168084E+10 | 968.56 | 01-AUG-09:09 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.160800E+10 | 968.56 | 01-SEP-09:09 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.165430E+10 | 968.56 | 02-OCT-09:09 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.160161E+10 | 968.56 | 01-NOV-09:09 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.165100E+10 | 968.56 | 01-DEC-10:09 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.195804E+11 | 0.703313E+11 | ||||
Minimum of Months | 0.149855E+10 | 968.56 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.168084E+10 | 968.56 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.213351E+10 | 1248.98 | 02-JAN-10:09 | 0.171305E+11 | 10339.04 | 01-JAN-11:09 |
February | 0.193243E+10 | 1248.98 | 01-FEB-10:09 | 0.154728E+11 | 10339.04 | 01-FEB-11:09 |
March | 0.216749E+10 | 1248.98 | 01-MAR-10:09 | 0.171306E+11 | 10339.04 | 01-MAR-11:09 |
April | 0.207306E+10 | 1248.98 | 01-APR-16:10 | 0.165779E+11 | 10339.04 | 01-APR-10:09 |
May | 0.215050E+10 | 1248.98 | 01-MAY-09:09 | 0.171306E+11 | 10339.04 | 01-MAY-10:09 |
June | 0.209504E+10 | 1248.98 | 01-JUN-09:09 | 0.165780E+11 | 10339.04 | 01-JUN-10:09 |
July | 0.212877E+10 | 1248.98 | 01-JUL-16:10 | 0.171305E+11 | 10339.04 | 01-JUL-10:09 |
August | 0.216749E+10 | 1248.98 | 01-AUG-09:09 | 0.171306E+11 | 10339.04 | 01-AUG-10:09 |
September | 0.207356E+10 | 1248.98 | 01-SEP-09:09 | 0.165779E+11 | 10339.04 | 01-SEP-10:09 |
October | 0.213326E+10 | 1248.98 | 02-OCT-09:09 | 0.171305E+11 | 10339.04 | 01-OCT-10:09 |
November | 0.206532E+10 | 1248.98 | 01-NOV-09:09 | 0.165780E+11 | 10339.04 | 01-NOV-10:09 |
December | 0.212902E+10 | 1248.98 | 01-DEC-10:09 | 0.171305E+11 | 10339.04 | 01-DEC-11:09 |
Annual Sum or Average | 0.252494E+11 | 0.201699E+12 | ||||
Minimum of Months | 0.193243E+10 | 1248.98 | 0.154728E+11 | 10339.04 | ||
Maximum of Months | 0.216749E+10 | 1248.98 | 0.171306E+11 | 10339.04 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.165449E+10 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187617E+11 |
February | 0.852256E+10 | 0.149855E+10 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6372935.37 | 0.130603E+11 |
March | 0.954557E+10 | 0.168084E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85082978.41 | 0.848706E+10 |
April | 0.915225E+10 | 0.160761E+10 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407932E+09 | 0.495590E+10 |
May | 0.947560E+10 | 0.166766E+10 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119038E+10 | 0.251657E+10 |
June | 0.922788E+10 | 0.162466E+10 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357672E+10 | 0.724830E+09 |
July | 0.939996E+10 | 0.165081E+10 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441898E+10 | 0.637605E+09 |
August | 0.954557E+10 | 0.168084E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436166E+10 | 0.212421E+09 |
September | 0.915225E+10 | 0.160800E+10 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148507E+10 | 0.167382E+10 |
October | 0.940563E+10 | 0.165430E+10 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205568E+09 | 0.656591E+10 |
November | 0.909363E+10 | 0.160161E+10 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 802471.51 | 0.981853E+10 |
December | 0.939996E+10 | 0.165100E+10 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140937E+11 |
Annual Sum or Average | 0.111326E+12 | 0.195804E+11 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157386E+11 | 0.815083E+11 |
Minimum of Months | 0.852256E+10 | 0.149855E+10 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212421E+09 |
Maximum of Months | 0.954557E+10 | 0.168084E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441898E+10 | 0.187617E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.213351E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285678E+09 |
February | 0.610713E+09 | 0.193243E+10 | 0.117185E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254585E+09 |
March | 0.684021E+09 | 0.216749E+10 | 0.129742E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 121236.29 | 0.179211E+09 |
April | 0.655836E+09 | 0.207306E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 415248.99 | 0.118172E+09 |
May | 0.679007E+09 | 0.215050E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2313159.65 | 83198814.30 |
June | 0.661256E+09 | 0.209504E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 13835305.67 | 48453427.17 |
July | 0.673587E+09 | 0.212877E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 14103054.39 | 34668031.84 |
August | 0.684021E+09 | 0.216749E+10 | 0.129742E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 14196399.55 | 26896171.83 |
September | 0.655836E+09 | 0.207356E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 3125373.26 | 49151844.65 |
October | 0.673993E+09 | 0.213326E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 331856.82 | 0.134863E+09 |
November | 0.651635E+09 | 0.206532E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178454E+09 |
December | 0.673587E+09 | 0.212902E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252847E+09 |
Annual Sum or Average | 0.797748E+10 | 0.252494E+11 | 0.152760E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 48441634.61 | 0.164618E+10 |
Minimum of Months | 0.610713E+09 | 0.193243E+10 | 0.117185E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26896171.83 |
Maximum of Months | 0.684021E+09 | 0.216749E+10 | 0.129742E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 14196399.55 | 0.285678E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161232E+09 | 0.913725E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161839E+09 | 0.904704E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213871E+09 | 0.133219E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195621E+09 | 0.157187E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166668E+09 | 0.179032E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188927E+09 | 0.170386E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195048E+09 | 0.171270E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222291E+09 | 0.159279E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258967E+09 | 0.114651E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199441E+09 | 0.107932E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224307E+09 | 0.820739E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199588E+09 | 0.753003E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238780E+10 | 0.153217E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161232E+09 | 0.753003E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258967E+09 | 0.179032E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 968.56 | 02-JAN-10:09 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 28635.59 | 07-JAN-19:10 |
February | 9454.80 | 04-FEB-19:10 | 968.56 | 01-FEB-10:09 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 862.28 | 28-FEB-14:00 | 30159.86 | 11-FEB-20:00 |
March | 9454.80 | 04-MAR-19:10 | 968.56 | 01-MAR-10:09 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2331.01 | 30-MAR-17:10 | 15498.02 | 22-MAR-11:10 |
April | 9454.80 | 01-APR-18:10 | 968.56 | 01-APR-16:10 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3543.00 | 17-APR-17:03 | 14348.08 | 05-APR-19:53 |
May | 9454.80 | 06-MAY-18:10 | 968.56 | 01-MAY-09:09 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5538.24 | 19-MAY-17:03 | 7314.54 | 09-MAY-19:53 |
June | 9454.80 | 03-JUN-18:10 | 968.56 | 01-JUN-09:09 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8184.67 | 06-JUN-17:03 | 5602.27 | 10-JUN-06:05 |
July | 9454.80 | 01-JUL-18:10 | 968.56 | 01-JUL-16:10 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9322.59 | 08-JUL-18:02 | 4990.57 | 28-JUL-20:00 |
August | 9454.80 | 05-AUG-18:10 | 968.56 | 01-AUG-09:09 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9109.95 | 01-AUG-17:10 | 2708.54 | 25-AUG-06:10 |
September | 9454.80 | 02-SEP-18:10 | 968.56 | 01-SEP-09:09 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6104.92 | 07-SEP-12:00 | 7152.96 | 28-SEP-18:55 |
October | 9454.80 | 07-OCT-18:10 | 968.56 | 02-OCT-09:09 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3879.01 | 10-OCT-17:04 | 12794.11 | 25-OCT-19:55 |
November | 9454.80 | 04-NOV-18:10 | 968.56 | 01-NOV-09:09 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.67 | 19-NOV-15:00 | 17117.76 | 21-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 968.56 | 01-DEC-10:09 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 22327.46 | 02-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 968.56 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2708.54 | |||||
Maximum of Months | 9454.80 | 968.56 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9322.59 | 30159.86 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 1248.98 | 02-JAN-10:09 | 7604.23 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 891.29 | 07-JAN-05:00 |
February | 677.52 | 04-FEB-19:10 | 1248.98 | 01-FEB-10:09 | 7604.23 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 972.30 | 12-FEB-01:10 |
March | 677.52 | 04-MAR-19:10 | 1248.98 | 01-MAR-10:09 | 7604.23 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 9.90 | 30-MAR-15:55 | 802.52 | 22-MAR-03:20 |
April | 677.52 | 01-APR-18:10 | 1248.98 | 01-APR-16:10 | 7604.23 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 8.26 | 12-APR-14:00 | 367.03 | 05-APR-02:00 |
May | 677.52 | 06-MAY-18:10 | 1248.98 | 01-MAY-09:09 | 7604.23 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 19.60 | 19-MAY-13:00 | 358.32 | 10-MAY-04:00 |
June | 677.52 | 03-JUN-18:10 | 1248.98 | 01-JUN-09:09 | 7604.23 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 57.41 | 06-JUN-14:00 | 272.88 | 07-JUN-03:30 |
July | 677.52 | 01-JUL-18:10 | 1248.98 | 01-JUL-16:10 | 7604.23 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 41.96 | 22-JUL-13:53 | 226.10 | 28-JUL-01:30 |
August | 677.52 | 05-AUG-18:10 | 1248.98 | 01-AUG-09:09 | 7604.23 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 47.35 | 07-AUG-15:00 | 227.55 | 29-AUG-02:00 |
September | 677.52 | 02-SEP-18:10 | 1248.98 | 01-SEP-09:09 | 7604.23 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 22.46 | 06-SEP-11:53 | 258.90 | 30-SEP-00:55 |
October | 677.52 | 07-OCT-18:10 | 1248.98 | 02-OCT-09:09 | 7604.23 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 11.32 | 10-OCT-15:53 | 564.62 | 28-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 1248.98 | 01-NOV-09:09 | 7604.23 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 696.45 | 07-NOV-04:20 |
December | 677.52 | 02-DEC-19:10 | 1248.98 | 01-DEC-10:09 | 7604.23 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1126.34 | 17-DEC-04:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 1248.98 | 7604.23 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 226.10 | ||||||
Maximum of Months | 677.52 | 1248.98 | 7604.23 | 7998.14 | 0.00 | 0.00 | 0.00 | 57.41 | 1126.34 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.55 | 01-JAN-00:53 | 1980.08 | 10-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.44 | 26-FEB-07:45 | 2259.58 | 12-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.66 | 19-MAR-07:15 | 2375.58 | 19-MAR-13:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.68 | 10-APR-06:20 | 2607.75 | 09-APR-14:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.68 | 20-MAY-05:50 | 2559.96 | 10-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.71 | 11-JUN-06:03 | 2338.41 | 02-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.02 | 05-JUL-03:00 | 2393.08 | 12-JUL-14:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.38 | 10-AUG-05:10 | 2609.14 | 04-AUG-14:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.90 | 09-SEP-06:00 | 2276.25 | 15-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.12 | 14-OCT-07:23 | 1988.96 | 13-OCT-13:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.07 | 23-NOV-07:30 | 1730.16 | 21-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.38 | 10-DEC-06:00 | 1612.28 | 17-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.44 | 1612.28 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.71 | 2609.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7299.53 | 08-JAN-00:01 | 4727.40 | 1937.12 | 3659.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.27 |
February | 9980.10 | 13-FEB-05:03 | 3676.87 | 1506.65 | 11384.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.47 |
March | 13262.77 | 30-MAR-17:03 | 33617.07 | 3874.23 | 13010.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2330.94 | 0.00 |
April | 14163.96 | 17-APR-17:03 | 33617.07 | 3874.23 | 13010.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3543.00 | 0.00 |
May | 16796.81 | 19-MAY-17:03 | 25212.80 | 2905.67 | 9757.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5538.24 | 0.00 |
June | 30476.80 | 15-JUN-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 |
July | 31127.16 | 25-JUL-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 |
August | 30393.93 | 26-AUG-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 |
September | 33249.24 | 16-SEP-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 |
October | 18048.28 | 17-OCT-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.68 |
November | 8157.53 | 05-NOV-16:03 | 11030.60 | 1937.12 | 10571.03 | 0.00 | 0.00 | 0.00 | 0.00 | 69.23 | 0.00 |
December | 8239.07 | 12-DEC-14:00 | 7353.73 | 968.56 | 3388.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 856.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7299.53 | 0.00 | 968.56 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33249.24 | 33617.07 | 3874.23 | 13010.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5538.24 | 856.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36788.38 | 20-JAN-03:01 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 130.86 |
February | 37971.66 | 22-FEB-03:01 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 |
March | 45101.27 | 01-MAR-03:01 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 226.57 |
April | 47485.97 | 15-APR-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 163.65 |
May | 43630.13 | 12-MAY-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.52 |
June | 47170.96 | 10-JUN-02:11 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 76.42 |
July | 32157.00 | 03-JUL-02:11 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 23.62 |
August | 31444.38 | 26-AUG-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 |
September | 42322.65 | 29-SEP-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 122.73 |
October | 45716.48 | 12-OCT-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 272.10 |
November | 44459.03 | 20-NOV-03:01 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 324.77 |
December | 37309.60 | 12-DEC-03:01 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 117.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31444.38 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 | |
Maximum of Months | 47485.97 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 324.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.30 | 0.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.12 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.63 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.17 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.01 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.58 | 0.00 |
August | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.24 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.65 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.26 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.26 | 141.36 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.681924E+11 | 61123.52 | 27-JAN-03:20 | 0.572977E+11 | 46117.34 | 27-JAN-13:50 |
February | 0.558193E+11 | 91604.90 | 12-FEB-07:10 | 0.517492E+11 | 46124.30 | 01-FEB-13:00 |
March | 0.529164E+11 | 33943.29 | 30-MAR-12:00 | 0.567594E+11 | 45902.21 | 01-MAR-13:30 |
April | 0.537082E+11 | 45755.80 | 06-APR-03:09 | 0.539317E+11 | 44636.40 | 01-APR-12:39 |
May | 0.607795E+11 | 40302.61 | 30-MAY-10:20 | 0.545825E+11 | 42996.42 | 01-MAY-12:00 |
June | 0.688017E+11 | 45373.70 | 28-JUN-11:20 | 0.518383E+11 | 41460.69 | 01-JUN-12:39 |
July | 0.762334E+11 | 47633.62 | 07-JUL-11:00 | 0.529179E+11 | 40231.67 | 01-JUL-12:39 |
August | 0.792936E+11 | 46960.94 | 18-AUG-11:00 | 0.529105E+11 | 40099.05 | 31-AUG-12:00 |
September | 0.647903E+11 | 44515.37 | 07-SEP-11:09 | 0.517025E+11 | 41259.41 | 30-SEP-12:30 |
October | 0.554082E+11 | 38273.28 | 18-OCT-10:00 | 0.544472E+11 | 42737.16 | 31-OCT-12:20 |
November | 0.522125E+11 | 55862.24 | 22-NOV-03:20 | 0.538394E+11 | 44534.92 | 30-NOV-13:20 |
December | 0.585931E+11 | 56175.02 | 18-DEC-03:20 | 0.566584E+11 | 45847.74 | 31-DEC-13:00 |
Annual Sum or Average | 0.746749E+12 | 0.648635E+12 | ||||
Minimum of Months | 0.522125E+11 | 33943.29 | 0.517025E+11 | 40099.05 | ||
Maximum of Months | 0.792936E+11 | 91604.90 | 0.572977E+11 | 46124.30 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.378800E+10 | 0.408692E+10 | 0.231039E+11 | 0.00 | 0.142866E+11 | 0.79 | 0.198265E+11 | 0.114570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343098E+10 | 0.348822E+10 | 0.208680E+11 | 0.00 | 0.127663E+11 | 0.72 | 0.115967E+11 | 0.893119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384832E+10 | 0.356700E+10 | 0.231040E+11 | 0.00 | 0.139554E+11 | 0.80 | 0.218200E+10 | 0.306102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368067E+10 | 0.315736E+10 | 0.223586E+11 | 0.00 | 0.134526E+11 | 0.77 | 0.948476E+09 | 0.692562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.381816E+10 | 0.300611E+10 | 0.231040E+11 | 0.00 | 0.139173E+11 | 0.80 | 24175315.07 | 0.135330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371970E+10 | 0.279656E+10 | 0.223587E+11 | 0.00 | 0.136215E+11 | 0.77 | 0.00 | 0.230006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377958E+10 | 0.293206E+10 | 0.231038E+11 | 0.00 | 0.141996E+11 | 0.79 | 0.00 | 0.287908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.384832E+10 | 0.314633E+10 | 0.231040E+11 | 0.00 | 0.143168E+11 | 0.80 | 0.00 | 0.314380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.368156E+10 | 0.332436E+10 | 0.223586E+11 | 0.00 | 0.136104E+11 | 0.77 | 0.00 | 0.185171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378756E+10 | 0.374030E+10 | 0.231039E+11 | 0.00 | 0.138976E+11 | 0.79 | 0.674006E+09 | 0.692596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366693E+10 | 0.388683E+10 | 0.223586E+11 | 0.00 | 0.134727E+11 | 0.77 | 0.353152E+10 | 0.223109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378002E+10 | 0.415939E+10 | 0.231038E+11 | 0.00 | 0.142762E+11 | 0.79 | 0.977278E+10 | 0.458972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448298E+11 | 0.412914E+11 | 0.272030E+12 | 0.00 | 0.165773E+12 | 9.37 | 0.485562E+11 | 0.135890E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.343098E+10 | 0.279656E+10 | 0.208680E+11 | 0.00 | 0.127663E+11 | 0.72 | 0.00 | 0.114570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.384832E+10 | 0.415939E+10 | 0.231040E+11 | 0.00 | 0.143168E+11 | 0.80 | 0.198265E+11 | 0.314380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.167720E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.151453E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.162337E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.147132E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.140567E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.126198E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.123922E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.123848E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.124840E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.139215E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.146209E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.161327E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.00 | 0.00 | 0.171477E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.123848E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.167720E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2217.54 | 02-JAN-10:09 | 2625.88 | 01-JAN-00:10 | 14269.29 | 01-JAN-11:09 | 0.00 | 6170.31 | 01-JAN-05:49 | 0.00 | 01-JAN-07:10 | 51334.42 | 27-JAN-03:20 |
February | 2217.54 | 01-FEB-10:09 | 2625.88 | 01-FEB-00:10 | 14269.29 | 01-FEB-11:09 | 0.00 | 6170.31 | 01-FEB-06:19 | 0.00 | 01-FEB-06:10 | 73161.50 | 12-FEB-07:10 |
March | 2217.54 | 01-MAR-10:09 | 2625.88 | 01-MAR-00:10 | 14269.29 | 01-MAR-11:09 | 0.00 | 6170.31 | 01-MAR-07:30 | 0.00 | 01-MAR-06:10 | 17778.18 | 19-MAR-03:49 |
April | 2217.54 | 01-APR-16:10 | 2625.88 | 01-APR-00:10 | 14269.29 | 01-APR-10:09 | 0.00 | 6170.31 | 01-APR-06:19 | 0.00 | 01-APR-06:10 | 34452.32 | 06-APR-03:09 |
May | 2217.54 | 01-MAY-09:09 | 2625.88 | 01-MAY-00:10 | 14269.29 | 01-MAY-10:09 | 0.00 | 6170.31 | 01-MAY-04:49 | 0.00 | 01-MAY-05:10 | 2204.33 | 11-MAY-06:10 |
June | 2217.54 | 01-JUN-09:09 | 2625.88 | 01-JUN-00:10 | 14269.29 | 01-JUN-10:09 | 0.00 | 6170.31 | 01-JUN-04:10 | 0.00 | 26-JUN-11:30 | 0.00 | 01-JUN-00:10 |
July | 2217.54 | 01-JUL-16:10 | 2625.88 | 01-JUL-00:10 | 14269.29 | 01-JUL-10:09 | 0.00 | 6170.31 | 01-JUL-05:30 | 0.00 | 26-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 2217.54 | 01-AUG-09:09 | 2625.88 | 01-AUG-00:10 | 14269.29 | 01-AUG-10:09 | 0.00 | 6170.31 | 01-AUG-04:30 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 2217.54 | 01-SEP-09:09 | 2625.88 | 01-SEP-00:10 | 14269.29 | 01-SEP-10:09 | 0.00 | 6170.31 | 01-SEP-06:49 | 0.00 | 04-SEP-13:50 | 0.00 | 01-SEP-00:10 |
October | 2217.54 | 02-OCT-09:09 | 2625.88 | 01-OCT-00:10 | 14269.29 | 01-OCT-10:09 | 0.00 | 6170.31 | 01-OCT-04:10 | 0.00 | 01-OCT-06:10 | 15034.02 | 26-OCT-03:49 |
November | 2217.54 | 01-NOV-09:09 | 2625.88 | 01-NOV-00:10 | 14269.29 | 01-NOV-10:09 | 0.00 | 6170.31 | 01-NOV-04:00 | 0.00 | 01-NOV-05:10 | 46047.51 | 22-NOV-03:20 |
December | 2217.54 | 01-DEC-10:09 | 2625.88 | 01-DEC-00:10 | 14269.29 | 01-DEC-11:09 | 0.00 | 6170.31 | 01-DEC-05:19 | 0.00 | 01-DEC-06:10 | 46373.21 | 18-DEC-03:20 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2217.54 | 2625.88 | 14269.29 | 0.00 | 6170.31 | 0.00 | 0.00 | ||||||
Maximum of Months | 2217.54 | 2625.88 | 14269.29 | 0.00 | 6170.31 | 0.00 | 73161.50 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 3897.17 | 31-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7950.27 | 28-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11889.39 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11136.94 | 17-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16484.24 | 31-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22358.21 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24674.05 | 07-JUL-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24005.83 | 18-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21871.14 | 06-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15310.04 | 11-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9333.27 | 05-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8392.83 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3897.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24674.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 61123.52 | 27-JAN-03:20 | 369.59 | 2119.28 | 2625.88 | 0.00 | 3724.60 | 0.00 | 51334.42 | 0.00 | 0.00 |
February | 91604.90 | 12-FEB-07:10 | 739.18 | 7971.08 | 2625.88 | 0.00 | 6170.31 | 0.00 | 73161.50 | 0.00 | 0.00 |
March | 33943.29 | 30-MAR-12:00 | 2217.54 | 12469.80 | 0.00 | 0.00 | 6170.31 | 0.00 | 0.00 | 11889.39 | 0.00 |
April | 45755.80 | 06-APR-03:09 | 369.59 | 3463.71 | 2625.88 | 0.00 | 3724.60 | 0.00 | 34452.32 | 0.00 | 0.00 |
May | 40302.61 | 30-MAY-10:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6170.31 | 0.00 | 0.00 | 13715.52 | 0.00 |
June | 45373.70 | 28-JUN-11:20 | 2217.54 | 13369.55 | 0.00 | 0.00 | 6170.31 | 0.00 | 0.00 | 21893.35 | 0.00 |
July | 47633.62 | 07-JUL-11:00 | 2217.54 | 13369.55 | 0.00 | 0.00 | 6170.31 | 0.00 | 0.00 | 24674.05 | 0.00 |
August | 46960.94 | 18-AUG-11:00 | 2217.54 | 13369.55 | 0.00 | 0.00 | 6170.31 | 0.00 | 0.00 | 24005.83 | 0.00 |
September | 44515.37 | 07-SEP-11:09 | 2217.54 | 13369.55 | 0.00 | 0.00 | 6170.31 | 0.00 | 0.00 | 21042.77 | 0.00 |
October | 38273.28 | 18-OCT-10:00 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6170.31 | 0.00 | 0.00 | 13900.91 | 0.00 |
November | 55862.24 | 22-NOV-03:20 | 369.59 | 2119.28 | 2625.88 | 0.00 | 3724.60 | 0.00 | 46047.51 | 0.00 | 0.00 |
December | 56175.02 | 18-DEC-03:20 | 369.59 | 2119.28 | 2625.88 | 0.00 | 3724.60 | 0.00 | 46373.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 33943.29 | 369.59 | 2119.28 | 0.00 | 0.00 | 3724.60 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91604.90 | 2217.54 | 14269.29 | 2625.88 | 0.00 | 6170.31 | 0.00 | 73161.50 | 24674.05 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 23134.19 | 27-JAN-13:50 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 23141.15 | 01-FEB-13:00 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 22919.06 | 01-MAR-13:30 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 21653.25 | 01-APR-12:39 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 20013.27 | 01-MAY-12:00 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 18477.54 | 01-JUN-12:39 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 17248.52 | 01-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 17115.90 | 31-AUG-12:00 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 18276.26 | 30-SEP-12:30 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 19754.01 | 31-OCT-12:20 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 21551.77 | 30-NOV-13:20 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 22864.59 | 31-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 17115.90 | 0.00 | ||
Maximum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 23141.15 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
February | 11.00 | 19.64 | 0.00 | 19.64 | 0.00 | 19.64 | 0.00 | 19.64 |
March | 3.50 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
April | 1.50 | 20.27 | 0.00 | 20.27 | 0.17 | 20.69 | 0.00 | 20.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.55 | 0.17 | 24.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 24.75 | 1.17 | 24.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 24.93 | 0.33 | 24.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 25.10 | 0.33 | 25.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 24.83 | 1.00 | 24.82 |
October | 0.33 | 20.53 | 0.00 | 20.53 | 2.17 | 24.15 | 0.33 | 24.21 |
November | 3.00 | 20.08 | 0.00 | 20.08 | 0.00 | 20.08 | 0.00 | 20.08 |
December | 14.50 | 20.08 | 0.00 | 20.08 | 0.00 | 20.08 | 0.00 | 20.08 |
Annual Sum or Average | 54.00 | 19.88 | 0.00 | 19.88 | 61.33 | 22.55 | 3.33 | 22.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.64 | 0.00 | 19.64 |
Maximum of Months | 20.17 | 20.53 | 0.00 | 20.53 | 15.83 | 25.10 | 1.17 | 25.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.72 | 0.00 | 27.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.55 | 0.00 | 27.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.99 | 0.00 | 27.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 28.36 | 0.00 | 28.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 29.46 | 0.00 | 29.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 30.14 | 0.00 | 30.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 29.90 | 3.33 | 29.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 30.01 | 1.67 | 29.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 30.10 | 0.00 | 30.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 28.77 | 0.00 | 28.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.91 | 0.00 | 27.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.42 | 0.00 | 27.42 |
Annual Sum or Average | 0.00 | 0.00 | 205.50 | 29.39 | 5.00 | 29.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.42 | 0.00 | 27.42 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 30.14 | 3.33 | 30.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 581.00 | 21.04 | 281.17 | 21.00 | 271.17 | 20.96 |
February | 454.67 | 21.28 | 189.83 | 21.33 | 148.17 | 21.22 |
March | 345.67 | 21.58 | 209.67 | 22.28 | 34.50 | 22.19 |
April | 219.50 | 22.23 | 352.33 | 23.19 | 49.17 | 23.17 |
May | 172.83 | 23.57 | 537.50 | 23.87 | 131.50 | 23.89 |
June | 240.83 | 24.13 | 563.67 | 24.07 | 229.00 | 24.10 |
July | 373.33 | 24.19 | 609.00 | 24.12 | 373.33 | 24.14 |
August | 461.00 | 24.16 | 612.00 | 24.13 | 461.00 | 24.14 |
September | 263.67 | 24.05 | 562.33 | 24.03 | 249.33 | 24.05 |
October | 311.67 | 22.27 | 352.00 | 23.13 | 90.17 | 23.21 |
November | 390.33 | 21.60 | 202.83 | 22.21 | 54.83 | 22.18 |
December | 550.50 | 21.20 | 167.00 | 21.26 | 132.33 | 21.18 |
Annual Sum or Average | 4365.00 | 22.38 | 4639.33 | 22.99 | 2224.50 | 23.03 |
Minimum of Months | 172.83 | 21.04 | 167.00 | 21.00 | 34.50 | 20.96 |
Maximum of Months | 581.00 | 24.19 | 612.00 | 24.13 | 461.00 | 24.14 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 572.33 | 19.15 | 347.00 | 19.26 | 320.33 | 19.20 |
February | 441.67 | 20.07 | 312.67 | 20.66 | 223.83 | 20.59 |
March | 408.17 | 22.10 | 340.33 | 23.25 | 181.83 | 23.53 |
April | 429.67 | 24.47 | 465.17 | 24.87 | 333.00 | 25.09 |
May | 542.67 | 25.74 | 581.67 | 25.76 | 519.67 | 25.83 |
June | 565.50 | 26.15 | 585.50 | 26.13 | 561.83 | 26.15 |
July | 609.00 | 26.23 | 609.00 | 26.23 | 609.00 | 26.23 |
August | 612.00 | 26.26 | 612.00 | 26.26 | 612.00 | 26.26 |
September | 537.00 | 26.14 | 585.00 | 26.05 | 537.00 | 26.08 |
October | 457.83 | 24.03 | 432.00 | 24.64 | 314.33 | 24.96 |
November | 421.00 | 21.60 | 306.83 | 22.70 | 173.67 | 22.97 |
December | 540.00 | 19.77 | 231.83 | 19.98 | 188.00 | 19.93 |
Annual Sum or Average | 6136.83 | 23.62 | 5409.00 | 24.18 | 4574.50 | 24.39 |
Minimum of Months | 408.17 | 19.15 | 231.83 | 19.26 | 173.67 | 19.20 |
Maximum of Months | 612.00 | 26.26 | 612.00 | 26.26 | 612.00 | 26.26 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.17042 | 27.16031 | -0.4694 | 12.05065 |
February | 551.00000 | 21.73523 | 30.22228 | -0.2638 | 10.32746 |
March | 612.00000 | 22.59198 | 36.30327 | 0.07489 | 8.78037 |
April | 590.00000 | 23.27736 | 44.87936 | 0.33308 | 10.11188 |
May | 611.00000 | 23.84014 | 53.57595 | -0.2582 | 8.29032 |
June | 592.00000 | 24.02129 | 57.13125 | -0.0698 | 6.35909 |
July | 609.00000 | 24.08284 | 64.03357 | 0.03244 | 6.06369 |
August | 612.00000 | 24.09844 | 65.30976 | 0.07514 | 6.21260 |
September | 590.00000 | 23.98208 | 59.11479 | -0.1024 | 6.56643 |
October | 610.00000 | 23.05397 | 49.45850 | 0.34615 | 10.82234 |
November | 591.00000 | 22.37081 | 37.39390 | 0.03642 | 8.83186 |
December | 609.00000 | 21.45885 | 32.12438 | -0.2965 | 9.50177 |
Annual Sum or Average | 7187.00000 | 22.97949 | 46.49371 | -0.0461 | 8.65282 |
Minimum of Months | 551.00000 | 21.17042 | 27.16031 | -0.4694 | 6.06369 |
Maximum of Months | 612.00000 | 24.09844 | 65.30976 | 0.34615 | 12.05065 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.44163 | 33.90274 | -0.5032 | 15.00734 |
February | 551.00000 | 20.86811 | 35.10066 | -0.1489 | 15.00322 |
March | 612.00000 | 22.78637 | 39.23802 | 0.36198 | 17.06767 |
April | 590.00000 | 24.31484 | 45.65529 | 0.78463 | 24.91028 |
May | 611.00000 | 25.55510 | 52.50428 | 0.55393 | 16.12881 |
June | 592.00000 | 26.06702 | 55.75060 | 0.80921 | 20.57935 |
July | 609.00000 | 26.22951 | 62.03315 | 0.93299 | 23.98757 |
August | 612.00000 | 26.25653 | 62.81036 | 0.95917 | 24.93806 |
September | 590.00000 | 25.93472 | 56.69029 | 0.76066 | 19.20455 |
October | 610.00000 | 23.87560 | 50.26027 | 0.74609 | 24.63285 |
November | 591.00000 | 22.27328 | 40.56106 | 0.27302 | 16.58081 |
December | 609.00000 | 20.18359 | 38.05185 | -0.2658 | 12.79279 |
Annual Sum or Average | 7187.00000 | 23.66193 | 47.79814 | 0.44130 | 19.25960 |
Minimum of Months | 551.00000 | 19.44163 | 33.90274 | -0.5032 | 12.79279 |
Maximum of Months | 612.00000 | 26.25653 | 62.81036 | 0.95917 | 24.93806 |
Report: DXReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.259058E+09 | 91095082.23 | 30.67 | 0.209419E+09 | 49638972.29 | 0.00 | 0.30 | 31-JAN-13:55 | 0.00 | 01-JAN-00:01 | 7019.44 | 31-JAN-13:55 | 6019.26 | 31-JAN-15:00 | 1465.77 | 19-JAN-15:55 | 2399.49 | 31-JAN-13:55 | 0.00 |
February | 0.176490E+10 | 0.600073E+09 | 91.30 | 0.171721E+10 | 47692156.38 | 0.00 | 0.57 | 28-FEB-14:00 | 0.00 | 01-FEB-00:05 | 14219.06 | 28-FEB-14:00 | 13992.75 | 28-FEB-14:00 | 1369.02 | 19-FEB-14:55 | 4541.92 | 28-FEB-14:00 | 0.00 |
March | 0.589965E+10 | 0.194707E+10 | 249.19 | 0.484669E+10 | 0.105296E+10 | 0.00 | 0.84 | 30-MAR-17:10 | 0.00 | 01-MAR-00:10 | 22879.25 | 30-MAR-12:53 | 18311.42 | 30-MAR-17:03 | 6136.62 | 30-MAR-11:43 | 6760.28 | 30-MAR-17:10 | 0.00 |
April | 0.125216E+11 | 0.403013E+10 | 368.39 | 0.101664E+11 | 0.235515E+10 | 0.00 | 0.82 | 17-APR-17:10 | 0.00 | 01-APR-00:01 | 22121.78 | 17-APR-17:10 | 19914.82 | 17-APR-17:03 | 8345.13 | 03-APR-02:61 | 6591.89 | 17-APR-17:10 | 0.00 |
May | 0.244695E+11 | 0.755214E+10 | 554.59 | 0.175857E+11 | 0.688378E+10 | 0.00 | 1.00 | 19-MAY-17:03 | 0.00 | 01-MAY-00:01 | 34951.27 | 31-MAY-02:62 | 23713.06 | 19-MAY-17:03 | 17608.59 | 31-MAY-02:62 | 9255.92 | 31-MAY-02:62 | 0.00 |
June | 0.413047E+11 | 0.121587E+11 | 593.18 | 0.274258E+11 | 0.138790E+11 | 0.00 | 1.00 | 05-JUN-02:61 | 0.00 | 01-JUN-00:01 | 62498.78 | 26-JUN-02:61 | 37938.27 | 15-JUN-02:61 | 35006.25 | 27-JUN-02:61 | 16514.12 | 26-JUN-02:61 | 0.00 |
July | 0.512879E+11 | 0.148823E+11 | 633.48 | 0.311442E+11 | 0.201437E+11 | 0.00 | 1.00 | 01-JUL-02:62 | 0.00 | 01-JUL-00:01 | 62498.78 | 05-JUL-02:61 | 38947.70 | 25-JUL-02:61 | 36945.83 | 27-JUL-02:61 | 16514.12 | 05-JUL-02:61 | 0.00 |
August | 0.560975E+11 | 0.160432E+11 | 634.15 | 0.328020E+11 | 0.232956E+11 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:02 | 62498.78 | 08-AUG-02:61 | 38132.13 | 26-AUG-02:61 | 36465.44 | 24-AUG-02:61 | 16514.12 | 01-AUG-02:61 | 0.00 |
September | 0.332482E+11 | 0.986440E+10 | 576.86 | 0.211020E+11 | 0.121462E+11 | 0.00 | 1.00 | 02-SEP-02:61 | 0.00 | 01-SEP-00:01 | 62498.78 | 07-SEP-02:61 | 41781.85 | 16-SEP-02:61 | 35605.15 | 17-SEP-02:61 | 16514.12 | 07-SEP-02:61 | 0.00 |
October | 0.129090E+11 | 0.402278E+10 | 346.71 | 0.904147E+10 | 0.386749E+10 | 0.00 | 1.00 | 10-OCT-11:43 | 0.00 | 01-OCT-00:01 | 52418.57 | 19-OCT-02:62 | 22622.47 | 18-OCT-02:61 | 30546.96 | 19-OCT-02:62 | 13834.32 | 19-OCT-02:62 | 0.00 |
November | 0.431345E+10 | 0.144199E+10 | 197.29 | 0.339615E+10 | 0.917305E+09 | 0.00 | 0.63 | 05-NOV-15:25 | 0.00 | 01-NOV-00:01 | 16300.42 | 05-NOV-15:25 | 11946.58 | 05-NOV-16:03 | 5568.81 | 05-NOV-12:55 | 5072.66 | 05-NOV-15:25 | 0.00 |
December | 0.911012E+09 | 0.307319E+09 | 52.67 | 0.677849E+09 | 0.233163E+09 | 0.00 | 0.61 | 12-DEC-14:00 | 0.00 | 01-DEC-00:01 | 15744.06 | 12-DEC-14:00 | 11415.64 | 12-DEC-14:00 | 4328.43 | 12-DEC-14:00 | 4933.04 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.244986E+12 | 0.729412E+11 | 4328.47 | 0.160115E+12 | 0.848715E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.259058E+09 | 91095082.23 | 30.67 | 0.209419E+09 | 47692156.38 | 0.00 | 0.30 | 0.00 | 7019.44 | 6019.26 | 1369.02 | 2399.49 | 0.00 | ||||||
Maximum of Months | 0.560975E+11 | 0.160432E+11 | 634.15 | 0.328020E+11 | 0.232956E+11 | 0.00 | 1.00 | 0.00 | 62498.78 | 41781.85 | 36945.83 | 16514.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 72368896.48 | 23475297.96 | 10.05 | 54012070.65 | 18356825.83 | 0.00 | 1.00 | 20-JAN-03:01 | 0.00 | 01-JAN-00:01 | 33460.68 | 20-JAN-03:01 | 17684.09 | 20-JAN-05:01 | 16840.86 | 20-JAN-03:01 | 8958.95 | 20-JAN-03:01 | 0.00 |
February | 0.932198E+09 | 0.293046E+09 | 71.69 | 0.884937E+09 | 47260929.13 | 0.00 | 1.00 | 17-FEB-05:01 | 0.00 | 01-FEB-00:05 | 29086.76 | 17-FEB-05:01 | 18127.88 | 22-FEB-03:01 | 11174.49 | 17-FEB-05:01 | 7780.13 | 17-FEB-05:01 | 0.00 |
March | 0.377077E+10 | 0.111394E+10 | 174.78 | 0.293971E+10 | 0.831062E+09 | 0.00 | 1.00 | 01-MAR-03:01 | 0.00 | 01-MAR-00:10 | 36050.45 | 05-MAR-03:01 | 24204.51 | 14-MAR-04:01 | 17440.72 | 05-MAR-03:01 | 9656.92 | 05-MAR-03:01 | 0.00 |
April | 0.100513E+11 | 0.289549E+10 | 320.97 | 0.806989E+10 | 0.198144E+10 | 0.00 | 1.00 | 01-APR-02:61 | 0.00 | 01-APR-00:01 | 37348.88 | 03-APR-02:61 | 26298.89 | 14-APR-04:01 | 21544.37 | 23-APR-02:61 | 9754.02 | 03-APR-02:61 | 0.00 |
May | 0.220117E+11 | 0.598084E+10 | 502.42 | 0.155071E+11 | 0.650463E+10 | 0.00 | 1.00 | 01-MAY-02:61 | 0.00 | 01-MAY-00:01 | 38482.91 | 31-MAY-02:11 | 24387.51 | 12-MAY-02:61 | 23276.44 | 31-MAY-02:11 | 9838.27 | 31-MAY-02:11 | 0.00 |
June | 0.413353E+11 | 0.108419E+11 | 617.80 | 0.267916E+11 | 0.145437E+11 | 0.00 | 1.00 | 01-JUN-02:11 | 0.00 | 01-JUN-00:01 | 40054.43 | 27-JUN-10:32 | 29021.93 | 11-JUN-02:11 | 25591.86 | 23-JUN-02:11 | 10378.98 | 23-JUN-13:05 | 0.00 |
July | 0.535148E+11 | 0.139085E+11 | 670.33 | 0.312112E+11 | 0.223036E+11 | 0.00 | 1.00 | 01-JUL-02:11 | 0.00 | 01-JUL-00:01 | 40054.43 | 26-JUL-10:46 | 30149.28 | 08-JUL-15:53 | 27938.09 | 27-JUL-02:61 | 11018.40 | 08-JUL-14:10 | 0.00 |
August | 0.599897E+11 | 0.153948E+11 | 679.76 | 0.327458E+11 | 0.272439E+11 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:02 | 40054.43 | 05-AUG-03:22 | 28619.65 | 18-AUG-13:00 | 27222.17 | 12-AUG-02:61 | 10623.33 | 02-AUG-13:00 | 0.00 |
September | 0.329970E+11 | 0.865275E+10 | 573.51 | 0.193511E+11 | 0.136460E+11 | 0.00 | 1.00 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 | 39922.38 | 07-SEP-11:00 | 23725.03 | 06-SEP-13:00 | 25347.32 | 03-SEP-02:11 | 10148.70 | 09-SEP-10:53 | 0.00 |
October | 0.105868E+11 | 0.290317E+10 | 300.52 | 0.659188E+10 | 0.399488E+10 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 40054.43 | 19-OCT-02:11 | 22635.52 | 15-OCT-02:61 | 27600.86 | 19-OCT-02:11 | 9961.06 | 19-OCT-02:11 | 0.00 |
November | 0.260089E+10 | 0.789095E+09 | 156.85 | 0.177496E+10 | 0.825926E+09 | 0.00 | 1.00 | 02-NOV-02:61 | 0.00 | 01-NOV-00:01 | 36050.45 | 02-NOV-02:61 | 24458.65 | 10-NOV-05:01 | 19036.20 | 04-NOV-02:11 | 9656.92 | 02-NOV-02:61 | 0.00 |
December | 0.491946E+09 | 0.151653E+09 | 31.86 | 0.317109E+09 | 0.174837E+09 | 0.00 | 1.00 | 12-DEC-03:01 | 0.00 | 01-DEC-00:01 | 36050.45 | 12-DEC-03:01 | 20403.00 | 13-DEC-05:01 | 18724.50 | 12-DEC-03:01 | 9656.92 | 12-DEC-03:01 | 0.00 |
Annual Sum or Average | 0.238355E+12 | 0.629486E+11 | 4110.53 | 0.146239E+12 | 0.921155E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 72368896.48 | 23475297.96 | 10.05 | 54012070.65 | 18356825.83 | 0.00 | 1.00 | 0.00 | 29086.76 | 17684.09 | 11174.49 | 7780.13 | 0.00 | ||||||
Maximum of Months | 0.599897E+11 | 0.153948E+11 | 679.76 | 0.327458E+11 | 0.272439E+11 | 0.00 | 1.00 | 0.00 | 40054.43 | 30149.28 | 27938.09 | 11018.40 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 148.11 | 66.80 | 81.30 | 91.24 | 513.45 | 0.00 | 0.00 | 0.00 |
February | 186.72 | 100.32 | 86.40 | 168.62 | 418.25 | 0.00 | 0.00 | 0.00 |
March | 234.91 | 106.94 | 127.97 | 255.30 | 262.56 | 0.00 | 0.00 | 0.00 |
April | 284.07 | 129.53 | 154.54 | 389.70 | 206.97 | 0.00 | 0.00 | 0.00 |
May | 311.93 | 131.91 | 180.02 | 479.99 | 142.70 | 0.00 | 0.00 | 0.00 |
June | 322.95 | 135.36 | 187.60 | 575.28 | 93.74 | 0.00 | 0.00 | 0.00 |
July | 314.89 | 132.39 | 182.51 | 582.78 | 70.13 | 0.00 | 0.00 | 0.00 |
August | 288.02 | 114.27 | 173.75 | 537.39 | 62.09 | 0.00 | 0.00 | 0.00 |
September | 236.72 | 104.88 | 131.83 | 371.85 | 131.35 | 0.00 | 0.00 | 0.00 |
October | 201.94 | 105.07 | 96.86 | 245.19 | 255.58 | 0.00 | 0.00 | 0.00 |
November | 161.45 | 73.10 | 88.35 | 141.45 | 334.76 | 0.00 | 0.00 | 0.00 |
December | 139.85 | 63.75 | 76.10 | 91.55 | 422.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 236.20 | 105.34 | 130.86 | 328.37 | 241.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 139.85 | 63.75 | 76.10 | 91.24 | 62.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 322.95 | 135.36 | 187.60 | 582.78 | 513.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 721.39 | 502.95 | 218.44 | 800.76 | 918.37 | 0.00 | 0.00 | 0.00 |
February | 673.30 | 451.33 | 221.97 | 819.94 | 784.58 | 0.00 | 0.00 | 0.00 |
March | 605.52 | 315.56 | 289.96 | 803.42 | 533.20 | 0.00 | 0.00 | 0.00 |
April | 453.50 | 147.62 | 305.87 | 667.93 | 447.65 | 0.00 | 0.00 | 0.00 |
May | 366.41 | 42.59 | 323.82 | 565.28 | 307.62 | 0.00 | 0.00 | 0.00 |
June | 338.78 | 18.85 | 319.93 | 634.98 | 202.90 | 0.00 | 0.00 | 0.00 |
July | 342.50 | 25.54 | 316.96 | 682.77 | 147.54 | 0.00 | 0.00 | 0.00 |
August | 408.92 | 76.39 | 332.53 | 830.08 | 129.39 | 0.00 | 0.00 | 0.00 |
September | 449.71 | 167.27 | 282.44 | 763.70 | 272.24 | 0.00 | 0.00 | 0.00 |
October | 651.96 | 422.34 | 229.62 | 956.44 | 510.38 | 0.00 | 0.00 | 0.00 |
November | 701.39 | 465.43 | 235.96 | 921.34 | 646.34 | 0.00 | 0.00 | 0.00 |
December | 711.09 | 500.26 | 210.83 | 848.69 | 779.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 534.78 | 260.46 | 274.32 | 774.54 | 471.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 338.78 | 18.85 | 210.83 | 565.28 | 129.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 721.39 | 502.95 | 332.53 | 956.44 | 918.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.13 | 70.57 | 81.56 | 104.64 | 526.58 | 0.00 | 0.00 | 0.00 |
February | 174.64 | 81.66 | 92.99 | 163.36 | 436.05 | 0.00 | 0.00 | 0.00 |
March | 257.41 | 124.39 | 133.02 | 305.63 | 274.72 | 0.00 | 0.00 | 0.00 |
April | 289.58 | 132.51 | 157.07 | 406.86 | 218.50 | 0.00 | 0.00 | 0.00 |
May | 291.04 | 110.26 | 180.78 | 454.91 | 150.95 | 0.00 | 0.00 | 0.00 |
June | 306.07 | 117.74 | 188.32 | 549.58 | 100.55 | 0.00 | 0.00 | 0.00 |
July | 288.69 | 107.04 | 181.65 | 541.05 | 72.86 | 0.00 | 0.00 | 0.00 |
August | 282.88 | 105.78 | 177.09 | 532.23 | 64.18 | 0.00 | 0.00 | 0.00 |
September | 230.47 | 96.00 | 134.47 | 364.51 | 135.35 | 0.00 | 0.00 | 0.00 |
October | 205.32 | 106.58 | 98.74 | 264.82 | 270.79 | 0.00 | 0.00 | 0.00 |
November | 163.86 | 73.55 | 90.31 | 165.03 | 357.45 | 0.00 | 0.00 | 0.00 |
December | 135.18 | 59.13 | 76.05 | 100.31 | 445.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 231.73 | 98.84 | 132.89 | 330.31 | 253.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.18 | 59.13 | 76.05 | 100.31 | 64.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 306.07 | 132.51 | 188.32 | 549.58 | 526.58 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.396694E+09 | 0.178929E+09 | 0.217765E+09 | 0.244378E+09 | 0.137523E+10 |
February | 0.451709E+09 | 0.242699E+09 | 0.209009E+09 | 0.407928E+09 | 0.101184E+10 |
March | 0.629191E+09 | 0.286426E+09 | 0.342765E+09 | 0.683807E+09 | 0.703229E+09 |
April | 0.736311E+09 | 0.335738E+09 | 0.400573E+09 | 0.101010E+10 | 0.536456E+09 |
May | 0.835475E+09 | 0.353310E+09 | 0.482165E+09 | 0.128560E+10 | 0.382219E+09 |
June | 0.837095E+09 | 0.350847E+09 | 0.486248E+09 | 0.149112E+10 | 0.242977E+09 |
July | 0.843408E+09 | 0.354580E+09 | 0.488828E+09 | 0.156092E+10 | 0.187830E+09 |
August | 0.771440E+09 | 0.306057E+09 | 0.465382E+09 | 0.143935E+10 | 0.166311E+09 |
September | 0.613566E+09 | 0.271855E+09 | 0.341711E+09 | 0.963846E+09 | 0.340471E+09 |
October | 0.540871E+09 | 0.281428E+09 | 0.259443E+09 | 0.656722E+09 | 0.684552E+09 |
November | 0.418482E+09 | 0.189487E+09 | 0.228995E+09 | 0.366649E+09 | 0.867697E+09 |
December | 0.374569E+09 | 0.170743E+09 | 0.203826E+09 | 0.245208E+09 | 0.113234E+10 |
Annual Sum or Average | 0.744881E+10 | 0.332210E+10 | 0.412671E+10 | 0.103556E+11 | 0.763114E+10 |
Minimum of Months | 0.374569E+09 | 0.170743E+09 | 0.203826E+09 | 0.244378E+09 | 0.166311E+09 |
Maximum of Months | 0.843408E+09 | 0.354580E+09 | 0.488828E+09 | 0.156092E+10 | 0.137523E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193217E+10 | 0.134710E+10 | 0.585068E+09 | 0.214476E+10 | 0.245977E+10 |
February | 0.162884E+10 | 0.109186E+10 | 0.536985E+09 | 0.198361E+10 | 0.189806E+10 |
March | 0.162183E+10 | 0.845202E+09 | 0.776629E+09 | 0.215189E+10 | 0.142813E+10 |
April | 0.117546E+10 | 0.382638E+09 | 0.792824E+09 | 0.173129E+10 | 0.116030E+10 |
May | 0.981383E+09 | 0.114063E+09 | 0.867320E+09 | 0.151405E+10 | 0.823931E+09 |
June | 0.878121E+09 | 48863916.60 | 0.829257E+09 | 0.164586E+10 | 0.525919E+09 |
July | 0.917356E+09 | 68403164.95 | 0.848952E+09 | 0.182873E+10 | 0.395167E+09 |
August | 0.109526E+10 | 0.204598E+09 | 0.890659E+09 | 0.222329E+10 | 0.346559E+09 |
September | 0.116566E+10 | 0.433564E+09 | 0.732094E+09 | 0.197951E+10 | 0.705651E+09 |
October | 0.174620E+10 | 0.113119E+10 | 0.615010E+09 | 0.256174E+10 | 0.136700E+10 |
November | 0.181800E+10 | 0.120639E+10 | 0.611604E+09 | 0.238812E+10 | 0.167531E+10 |
December | 0.190458E+10 | 0.133989E+10 | 0.564695E+09 | 0.227312E+10 | 0.208767E+10 |
Annual Sum or Average | 0.168649E+11 | 0.821376E+10 | 0.865110E+10 | 0.244260E+11 | 0.148735E+11 |
Minimum of Months | 0.878121E+09 | 48863916.60 | 0.536985E+09 | 0.151405E+10 | 0.346559E+09 |
Maximum of Months | 0.193217E+10 | 0.134710E+10 | 0.890659E+09 | 0.256174E+10 | 0.245977E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407460E+09 | 0.189008E+09 | 0.218451E+09 | 0.280268E+09 | 0.141040E+10 |
February | 0.422494E+09 | 0.197541E+09 | 0.224952E+09 | 0.395210E+09 | 0.105490E+10 |
March | 0.689452E+09 | 0.333159E+09 | 0.356293E+09 | 0.818606E+09 | 0.735801E+09 |
April | 0.750601E+09 | 0.343472E+09 | 0.407129E+09 | 0.105457E+10 | 0.566352E+09 |
May | 0.779523E+09 | 0.295330E+09 | 0.484192E+09 | 0.121844E+10 | 0.404307E+09 |
June | 0.793326E+09 | 0.305188E+09 | 0.488137E+09 | 0.142451E+10 | 0.260638E+09 |
July | 0.773231E+09 | 0.286687E+09 | 0.486543E+09 | 0.144916E+10 | 0.195142E+09 |
August | 0.757656E+09 | 0.283333E+09 | 0.474323E+09 | 0.142552E+10 | 0.171909E+09 |
September | 0.597370E+09 | 0.248831E+09 | 0.348539E+09 | 0.944815E+09 | 0.350830E+09 |
October | 0.549925E+09 | 0.285471E+09 | 0.264454E+09 | 0.709286E+09 | 0.725297E+09 |
November | 0.424723E+09 | 0.190637E+09 | 0.234085E+09 | 0.427766E+09 | 0.926517E+09 |
December | 0.362073E+09 | 0.158371E+09 | 0.203702E+09 | 0.268657E+09 | 0.119217E+10 |
Annual Sum or Average | 0.730783E+10 | 0.311703E+10 | 0.419080E+10 | 0.104168E+11 | 0.799426E+10 |
Minimum of Months | 0.362073E+09 | 0.158371E+09 | 0.203702E+09 | 0.268657E+09 | 0.171909E+09 |
Maximum of Months | 0.793326E+09 | 0.343472E+09 | 0.488137E+09 | 0.144916E+10 | 0.141040E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 896.47 | 1858.24 | 1021.63 | 640.32 | 381.30 | 0.00 | 0.00 |
February | 1073.42 | 1560.38 | 1034.66 | 633.31 | 401.35 | 0.00 | 0.00 |
March | 1318.04 | 1024.15 | 1097.85 | 546.89 | 550.96 | 0.00 | 0.00 |
April | 1417.97 | 826.60 | 1027.15 | 409.66 | 617.49 | 0.00 | 0.00 |
May | 1477.07 | 578.16 | 969.38 | 284.76 | 684.62 | 0.00 | 0.00 |
June | 1745.15 | 382.52 | 967.80 | 271.95 | 695.85 | 0.00 | 0.00 |
July | 1799.21 | 283.13 | 946.09 | 264.96 | 681.12 | 0.00 | 0.00 |
August | 1894.87 | 250.84 | 979.82 | 296.44 | 683.38 | 0.00 | 0.00 |
September | 1487.23 | 526.11 | 916.90 | 368.15 | 548.74 | 0.00 | 0.00 |
October | 1434.80 | 1005.10 | 1059.21 | 633.99 | 425.22 | 0.00 | 0.00 |
November | 1184.82 | 1295.54 | 1026.70 | 612.08 | 414.62 | 0.00 | 0.00 |
December | 967.23 | 1574.01 | 986.12 | 623.13 | 362.99 | 0.00 | 0.00 |
Annual Sum or Average | 1393.23 | 927.11 | 1002.71 | 464.64 | 538.07 | 0.00 | 0.00 |
Minimum of Months | 896.47 | 250.84 | 916.90 | 264.96 | 362.99 | 0.00 | 0.00 |
Maximum of Months | 1894.87 | 1858.24 | 1097.85 | 640.32 | 695.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.240111E+10 | 0.497710E+10 | 0.273632E+10 | 0.171504E+10 | 0.102128E+10 | 0.00 | 0.00 |
February | 0.259681E+10 | 0.377486E+10 | 0.250304E+10 | 0.153210E+10 | 0.970946E+09 | 0.00 | 0.00 |
March | 0.353024E+10 | 0.274310E+10 | 0.294047E+10 | 0.146479E+10 | 0.147569E+10 | 0.00 | 0.00 |
April | 0.367539E+10 | 0.214254E+10 | 0.266237E+10 | 0.106185E+10 | 0.160053E+10 | 0.00 | 0.00 |
May | 0.395618E+10 | 0.154856E+10 | 0.259638E+10 | 0.762703E+09 | 0.183368E+10 | 0.00 | 0.00 |
June | 0.452344E+10 | 0.991487E+09 | 0.250854E+10 | 0.704899E+09 | 0.180364E+10 | 0.00 | 0.00 |
July | 0.481899E+10 | 0.758335E+09 | 0.253399E+10 | 0.709671E+09 | 0.182432E+10 | 0.00 | 0.00 |
August | 0.507522E+10 | 0.671844E+09 | 0.262435E+10 | 0.793988E+09 | 0.183036E+10 | 0.00 | 0.00 |
September | 0.385491E+10 | 0.136369E+10 | 0.237659E+10 | 0.954249E+09 | 0.142234E+10 | 0.00 | 0.00 |
October | 0.384296E+10 | 0.269207E+10 | 0.283700E+10 | 0.169809E+10 | 0.113891E+10 | 0.00 | 0.00 |
November | 0.307106E+10 | 0.335805E+10 | 0.266120E+10 | 0.158652E+10 | 0.107468E+10 | 0.00 | 0.00 |
December | 0.259063E+10 | 0.421582E+10 | 0.264123E+10 | 0.166900E+10 | 0.972223E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.439369E+11 | 0.292374E+11 | 0.316215E+11 | 0.146529E+11 | 0.169686E+11 | 0.00 | 0.00 |
Minimum of Months | 0.240111E+10 | 0.671844E+09 | 0.237659E+10 | 0.704899E+09 | 0.970946E+09 | 0.00 | 0.00 |
Maximum of Months | 0.507522E+10 | 0.497710E+10 | 0.294047E+10 | 0.171504E+10 | 0.183368E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.135525E+11 | -0.127430E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -809490852.7 | 60.05 | 0.00 | 0.00 |
February | 0.122381E+11 | -0.115324E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -705693793.0 | 60.05 | 0.00 | 0.00 |
March | 0.131175E+11 | -0.123751E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -742431837.2 | 60.05 | 0.00 | 0.00 |
April | 0.118888E+11 | -0.111980E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -690774953.2 | 60.05 | 0.00 | 0.00 |
May | 0.113584E+11 | -0.106685E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -689931284.4 | 60.05 | 0.00 | 0.00 |
June | 0.101972E+11 | -0.953902E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -658221581.9 | 60.05 | 0.00 | 0.00 |
July | 0.100134E+11 | -0.933650E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -676940688.1 | 60.05 | 0.00 | 0.00 |
August | 0.100074E+11 | -0.933114E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -676232322.8 | 60.05 | 0.00 | 0.00 |
September | 0.100876E+11 | -0.942729E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -660329316.8 | 60.05 | 0.00 | 0.00 |
October | 0.112492E+11 | -0.105284E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -720841910.6 | 60.05 | 0.00 | 0.00 |
November | 0.118141E+11 | -0.110864E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -727769530.3 | 60.05 | 0.00 | 0.00 |
December | 0.130359E+11 | -0.122430E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -792884965.9 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.138560E+12 | -0.130009E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.855154E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.100074E+11 | -0.127430E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -809490852.7 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.135525E+11 | -0.933114E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -658221581.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 407.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 411.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 293.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.258195E+11 | 46877.44 | 03-JAN-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150170E+11 | 46986.59 | 01-FEB-03:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.465652E+10 | 46959.58 | 19-MAR-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174557E+10 | 44179.71 | 07-APR-03:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67258212.99 | 5542.53 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160819E+10 | 45836.56 | 26-OCT-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.591200E+10 | 47580.71 | 25-NOV-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166472E+11 | 47582.30 | 21-DEC-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.714733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.258195E+11 | 47582.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187575E+11 | 23725.40 | 07-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.990107E+10 | 21834.71 | 12-FEB-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179652E+10 | 19268.24 | 19-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.707889E+09 | 20380.89 | 06-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4885309.88 | 1496.06 | 11-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.381730E+09 | 15921.65 | 26-OCT-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315310E+10 | 21086.85 | 21-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.891145E+10 | 21909.89 | 02-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187575E+11 | 23725.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.488347E+09 | 39014.23 | 08-JAN-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.491078E+09 | 37485.38 | 12-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1545248.41 | 2165.51 | 19-MAR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52018109.76 | 17536.09 | 06-APR-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94282134.20 | 30186.58 | 22-NOV-03:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308255E+09 | 32251.41 | 18-DEC-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.491078E+09 | 39014.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.657135E+09 | 19523.78 | 27-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112636E+10 | 35853.26 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7113075.60 | 14590.08 | 22-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 65002264.81 | 14861.56 | 18-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112636E+10 | 35853.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.259058E+09 | 0.209419E+09 | 7019.44 | 31-JAN-13:55 | 6015.44 | 0.00 |
February | 0.00 | 0.00 | 0.176490E+10 | 0.171721E+10 | 14219.06 | 28-FEB-14:00 | 13992.75 | 0.00 |
March | 0.00 | 0.00 | 0.589965E+10 | 0.484669E+10 | 22879.25 | 30-MAR-12:53 | 17666.62 | 0.00 |
April | 0.00 | 0.00 | 0.125216E+11 | 0.101664E+11 | 22121.78 | 17-APR-17:10 | 19912.78 | 0.00 |
May | 0.00 | 0.00 | 0.244695E+11 | 0.175857E+11 | 34951.27 | 31-MAY-02:62 | 17342.68 | 0.00 |
June | 0.00 | 0.00 | 0.413047E+11 | 0.274258E+11 | 62498.78 | 26-JUN-02:61 | 30772.45 | 0.00 |
July | 0.00 | 0.00 | 0.512879E+11 | 0.311442E+11 | 62498.78 | 05-JUL-02:61 | 31244.15 | 0.00 |
August | 0.00 | 0.00 | 0.560975E+11 | 0.328020E+11 | 62498.78 | 08-AUG-02:61 | 29343.29 | 0.00 |
September | 0.00 | 0.00 | 0.332482E+11 | 0.211020E+11 | 62498.78 | 07-SEP-02:61 | 30402.67 | 0.00 |
October | 0.00 | 0.00 | 0.129090E+11 | 0.904147E+10 | 52418.57 | 19-OCT-02:62 | 21871.61 | 0.00 |
November | 0.00 | 0.00 | 0.431345E+10 | 0.339615E+10 | 16300.42 | 05-NOV-15:25 | 11833.57 | 0.00 |
December | 0.00 | 0.00 | 0.911012E+09 | 0.677849E+09 | 15744.06 | 12-DEC-14:00 | 11415.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.244986E+12 | 0.160115E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.259058E+09 | 0.209419E+09 | 7019.44 | 6015.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.560975E+11 | 0.328020E+11 | 62498.78 | 31244.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 72368896.48 | 54012070.65 | 33460.68 | 20-JAN-03:01 | 16619.83 | 0.00 |
February | 0.00 | 0.00 | 0.932198E+09 | 0.884937E+09 | 29086.76 | 17-FEB-05:01 | 17912.28 | 0.00 |
March | 0.00 | 0.00 | 0.377077E+10 | 0.293971E+10 | 36050.45 | 05-MAR-03:01 | 18609.73 | 0.00 |
April | 0.00 | 0.00 | 0.100513E+11 | 0.806989E+10 | 37348.88 | 03-APR-02:61 | 17826.38 | 0.00 |
May | 0.00 | 0.00 | 0.220117E+11 | 0.155071E+11 | 38482.91 | 31-MAY-02:11 | 15206.47 | 0.00 |
June | 0.00 | 0.00 | 0.413353E+11 | 0.267916E+11 | 40054.43 | 27-JUN-10:32 | 20253.82 | 0.00 |
July | 0.00 | 0.00 | 0.535148E+11 | 0.312112E+11 | 40054.43 | 26-JUL-10:46 | 17447.05 | 0.00 |
August | 0.00 | 0.00 | 0.599897E+11 | 0.327458E+11 | 40054.43 | 05-AUG-03:22 | 14702.59 | 0.00 |
September | 0.00 | 0.00 | 0.329970E+11 | 0.193511E+11 | 39922.38 | 07-SEP-11:00 | 22379.76 | 0.00 |
October | 0.00 | 0.00 | 0.105868E+11 | 0.659188E+10 | 40054.43 | 19-OCT-02:11 | 12453.57 | 0.00 |
November | 0.00 | 0.00 | 0.260089E+10 | 0.177496E+10 | 36050.45 | 02-NOV-02:61 | 17520.43 | 0.00 |
December | 0.00 | 0.00 | 0.491946E+09 | 0.317109E+09 | 36050.45 | 12-DEC-03:01 | 17325.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.238355E+12 | 0.146239E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 72368896.48 | 54012070.65 | 29086.76 | 12453.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.599897E+11 | 0.327458E+11 | 40054.43 | 22379.76 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4739.31 | 18317.94 | 31-JAN-13:43 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 4748.68 | 18318.43 | 01-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 4601.64 | 18025.42 | 01-MAR-13:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4301.46 | 17100.37 | 01-APR-12:43 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 3964.33 | 15841.90 | 01-MAY-12:57 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 3661.60 | 14521.49 | 01-JUN-12:13 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 3467.74 | 13564.83 | 01-JUL-12:13 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 3465.60 | 13468.83 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 3618.66 | 14355.50 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3912.08 | 15649.41 | 31-OCT-12:17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4258.29 | 16932.47 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4552.44 | 17929.59 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 4104.00 | ||||
Minimum of Months | 0.00 | 0.00 | 3465.60 | 13468.83 | ||
Maximum of Months | 0.00 | 0.00 | 4748.68 | 18318.43 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.882427E+10 | 1.22 | 3724.60 | 04-JAN-15:30 | 1.38 |
February | 0.782241E+10 | 1.20 | 3724.60 | 05-FEB-14:27 | 1.39 |
March | 0.845677E+10 | 1.17 | 3724.60 | 02-MAR-05:14 | 1.37 |
April | 0.810786E+10 | 1.16 | 3724.60 | 05-APR-18:27 | 1.38 |
May | 0.833522E+10 | 1.19 | 3724.60 | 08-MAY-07:57 | 1.36 |
June | 0.812593E+10 | 1.23 | 3724.60 | 07-JUN-08:46 | 1.37 |
July | 0.844567E+10 | 1.23 | 3724.60 | 03-JUL-18:36 | 1.37 |
August | 0.849799E+10 | 1.23 | 3724.60 | 01-AUG-19:38 | 1.36 |
September | 0.812539E+10 | 1.23 | 3724.60 | 12-SEP-16:17 | 1.36 |
October | 0.835298E+10 | 1.17 | 3724.60 | 05-OCT-11:23 | 1.37 |
November | 0.815563E+10 | 1.17 | 3724.60 | 07-NOV-12:00 | 1.38 |
December | 0.880831E+10 | 1.22 | 3724.60 | 07-DEC-09:56 | 1.38 |
Annual Sum or Average | 0.100058E+12 | 1.20 | |||
Minimum of Months | 0.782241E+10 | 1.16 | 3724.60 | 1.36 | |
Maximum of Months | 0.882427E+10 | 1.23 | 3724.60 | 1.39 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.546235E+10 | 1.19 | 2445.71 | 12-JAN-24:00 | 1.42 |
February | 0.494386E+10 | 1.22 | 2445.71 | 01-FEB-05:10 | 1.42 |
March | 0.549858E+10 | 1.26 | 2445.71 | 29-MAR-09:17 | 1.39 |
April | 0.534476E+10 | 1.28 | 2445.71 | 02-APR-10:50 | 1.39 |
May | 0.558207E+10 | 1.33 | 2445.71 | 01-MAY-10:50 | 1.40 |
June | 0.549555E+10 | 1.36 | 2445.71 | 01-JUN-06:35 | 1.39 |
July | 0.575389E+10 | 1.35 | 2445.71 | 01-JUL-04:10 | 1.39 |
August | 0.581876E+10 | 1.35 | 2445.71 | 01-AUG-04:30 | 1.39 |
September | 0.548505E+10 | 1.35 | 2445.71 | 01-SEP-05:20 | 1.39 |
October | 0.554460E+10 | 1.29 | 2445.71 | 01-OCT-08:15 | 1.39 |
November | 0.531705E+10 | 1.26 | 2445.71 | 01-NOV-06:20 | 1.41 |
December | 0.546787E+10 | 1.20 | 2445.71 | 01-DEC-00:04 | 1.41 |
Annual Sum or Average | 0.657144E+11 | 1.29 | |||
Minimum of Months | 0.494386E+10 | 1.19 | 2445.71 | 1.39 | |
Maximum of Months | 0.581876E+10 | 1.36 | 2445.71 | 1.42 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 51.92 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 53.06 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 53.17 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 53.52 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 52.87 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 54.50 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:05 | 0.00 | 0.00 | 54.86 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 55.02 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 54.90 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 53.53 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 54.06 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 53.57 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 51.92 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 55.02 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 40.41 | 40.41 | 4739.31 | 18317.94 | 31-JAN-13:43 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 53.06 | 53.06 | 4748.68 | 18318.43 | 01-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 53.17 | 53.17 | 4601.64 | 18025.42 | 01-MAR-13:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 53.51 | 53.51 | 4301.46 | 17100.37 | 01-APR-12:43 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 42.66 | 42.66 | 3964.33 | 15841.90 | 01-MAY-12:57 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 54.49 | 54.49 | 3661.60 | 14521.49 | 01-JUN-12:13 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 54.86 | 54.86 | 3467.74 | 13564.83 | 01-JUL-12:13 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 55.02 | 55.02 | 3465.60 | 13468.83 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 54.90 | 54.90 | 3618.66 | 14355.50 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 44.32 | 44.32 | 3912.08 | 15649.41 | 31-OCT-12:17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 54.07 | 54.07 | 4258.29 | 16932.47 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 53.59 | 53.59 | 4552.44 | 17929.59 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 4104.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 40.41 | 40.41 | 3465.60 | 13468.83 | ||
Maximum of Months | 0.00 | 0.00 | 55.02 | 55.02 | 4748.68 | 18318.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.201047E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.148495E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.119626E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.128205E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159099E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.202846E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.233280E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.245412E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.179898E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.129165E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118857E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154556E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.202048E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.118857E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.245412E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.140988E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103940E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.723436E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.850425E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.115646E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.163374E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.196624E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.212135E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.141378E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.857991E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.734461E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.903675E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.148108E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.723436E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.212135E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.882427E+10 | 0.259058E+09 | 0.263079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.782241E+10 | 0.176490E+10 | 0.155081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.845677E+10 | 0.589965E+10 | 0.465806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.810786E+10 | 0.125216E+11 | 0.179758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.833522E+10 | 0.244695E+11 | 67258212.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.812593E+10 | 0.413047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.844567E+10 | 0.512879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.849799E+10 | 0.560975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.812539E+10 | 0.332482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.835298E+10 | 0.129090E+11 | 0.160819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.815563E+10 | 0.431345E+10 | 0.600628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880831E+10 | 0.911012E+09 | 0.169555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100058E+12 | 0.244986E+12 | 0.729088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.782241E+10 | 0.259058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.882427E+10 | 0.560975E+11 | 0.263079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.546235E+10 | 72368896.48 | 0.194146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.494386E+10 | 0.932198E+09 | 0.110274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.549858E+10 | 0.377077E+10 | 0.179652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.534476E+10 | 0.100513E+11 | 0.707889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.558207E+10 | 0.220117E+11 | 4885309.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.549555E+10 | 0.413353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.575389E+10 | 0.535148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.581876E+10 | 0.599897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.548505E+10 | 0.329970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.554460E+10 | 0.105868E+11 | 0.381730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.531705E+10 | 0.260089E+10 | 0.316021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.546787E+10 | 0.491946E+09 | 0.897645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.657144E+11 | 0.238355E+12 | 0.454698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.494386E+10 | 72368896.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.581876E+10 | 0.599897E+11 | 0.194146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.882427E+10 | 0.00 | 0.00 | 0.107010E+11 | 91095082.23 | 0.488347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.782241E+10 | 0.00 | 0.00 | 0.593593E+10 | 0.600073E+09 | 0.491078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.845677E+10 | 0.00 | 0.00 | 0.155721E+10 | 0.194707E+10 | 1545248.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.810786E+10 | 0.00 | 0.00 | 0.630452E+09 | 0.403013E+10 | 52018109.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.833522E+10 | 0.00 | 0.00 | 22490492.57 | 0.755214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.812593E+10 | 0.00 | 0.00 | 0.00 | 0.121587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.844567E+10 | 0.00 | 0.00 | 0.00 | 0.148823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.849799E+10 | 0.00 | 0.00 | 0.00 | 0.160432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.812539E+10 | 0.00 | 0.00 | 0.00 | 0.986440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.835298E+10 | 0.00 | 0.00 | 0.540707E+09 | 0.402278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.815563E+10 | 0.00 | 0.00 | 0.219377E+10 | 0.144199E+10 | 94282134.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880831E+10 | 0.00 | 0.00 | 0.603170E+10 | 0.307319E+09 | 0.308255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100058E+12 | 0.00 | 0.00 | 0.276133E+11 | 0.729412E+11 | 0.143553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.782241E+10 | 0.00 | 0.00 | 0.00 | 91095082.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.882427E+10 | 0.00 | 0.00 | 0.107010E+11 | 0.160432E+11 | 0.491078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.546235E+10 | 0.00 | 0.00 | 0.795582E+10 | 23475297.96 | 0.657135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.494386E+10 | 0.00 | 0.00 | 0.403072E+10 | 0.293046E+09 | 0.112636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.549858E+10 | 0.00 | 0.00 | 0.621834E+09 | 0.111394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.534476E+10 | 0.00 | 0.00 | 0.263993E+09 | 0.289549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.558207E+10 | 0.00 | 0.00 | 1684822.50 | 0.598084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.549555E+10 | 0.00 | 0.00 | 0.00 | 0.108419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.575389E+10 | 0.00 | 0.00 | 0.00 | 0.139085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.581876E+10 | 0.00 | 0.00 | 0.00 | 0.153948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.548505E+10 | 0.00 | 0.00 | 0.00 | 0.865275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.554460E+10 | 0.00 | 0.00 | 0.132129E+09 | 0.290317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.531705E+10 | 0.00 | 0.00 | 0.123136E+10 | 0.789095E+09 | 7113075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.546787E+10 | 0.00 | 0.00 | 0.335222E+10 | 0.151653E+09 | 65002264.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.657144E+11 | 0.00 | 0.00 | 0.175898E+11 | 0.629486E+11 | 0.185561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.494386E+10 | 0.00 | 0.00 | 0.00 | 23475297.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.581876E+10 | 0.00 | 0.00 | 0.795582E+10 | 0.153948E+11 | 0.112636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.249422E+10 | 0.00 | 0.00 | 417248.42 | 0.00 | 0.222684E+11 | 0.391009E+09 | 0.00 | 3.69 |
February | 0.326071E+10 | 0.00 | 0.00 | 5205934.13 | 0.00 | 0.136749E+11 | 0.110017E+10 | 0.00 | 3.65 |
March | 0.444225E+10 | 92168129.27 | 0.00 | 11105556.98 | 0.00 | 0.559564E+10 | 0.253805E+10 | 0.00 | 3.59 |
April | 0.338950E+10 | 0.345393E+09 | 0.00 | 19907981.28 | 0.00 | 0.217937E+10 | 0.238867E+10 | 0.00 | 3.59 |
May | 0.134610E+10 | 0.200892E+10 | 0.00 | 17321839.27 | 649219.45 | 0.124514E+09 | 0.221645E+10 | 0.00 | 3.63 |
June | 0.421596E+09 | 0.726100E+10 | 0.00 | 9186475.23 | 21289674.55 | 0.00 | 0.664721E+09 | 0.00 | 3.72 |
July | 87262051.76 | 0.110289E+11 | 0.00 | 2597923.11 | 62487416.80 | 0.00 | 0.230485E+09 | 0.00 | 3.77 |
August | 46897735.20 | 0.128687E+11 | 0.00 | 1582130.47 | 0.100268E+09 | 0.00 | 30236104.57 | 0.00 | 3.83 |
September | 0.787875E+09 | 0.474580E+10 | 0.00 | 12421122.93 | 16259807.26 | 0.00 | 0.127921E+10 | 0.00 | 3.72 |
October | 0.406805E+10 | 0.899614E+09 | 0.00 | 15114258.09 | 1863338.43 | 0.227835E+10 | 0.252820E+10 | 0.00 | 3.61 |
November | 0.466524E+10 | 27388825.57 | 0.00 | 8747242.25 | 0.00 | 0.663236E+10 | 0.219908E+10 | 0.00 | 3.60 |
December | 0.377611E+10 | 0.00 | 0.00 | 1840698.92 | 0.00 | 0.175068E+11 | 0.709282E+09 | 0.00 | 3.65 |
Annual Sum or Average | 0.287858E+11 | 0.392778E+11 | 0.00 | 0.105448E+09 | 0.202818E+09 | 0.702603E+11 | 0.162756E+11 | 0.00 | 3.67 |
Minimum of Months | 46897735.20 | 0.00 | 0.00 | 417248.42 | 0.00 | 0.00 | 30236104.57 | 0.00 | 3.59 |
Maximum of Months | 0.466524E+10 | 0.128687E+11 | 0.00 | 19907981.28 | 0.100268E+09 | 0.222684E+11 | 0.253805E+10 | 0.00 | 3.83 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.522541E+11 | 0.00 | 0.00 | 2264864.95 | 0.00 | 31855872.17 | 0.269836E+10 | 0.00 | 9.63 |
February | 0.354152E+11 | 0.00 | 0.00 | 11384378.61 | 0.00 | 14506957.23 | 0.730071E+10 | 0.00 | 9.73 |
March | 0.216081E+11 | 0.00 | 0.00 | 29642013.22 | 0.00 | 0.00 | 0.138203E+11 | 0.00 | 9.87 |
April | 0.121684E+11 | 726663.35 | 0.00 | 58760912.55 | 0.00 | 0.00 | 0.150759E+11 | 0.00 | 9.98 |
May | 0.365273E+10 | 0.102070E+10 | 0.00 | 74857506.62 | 150331.25 | 0.00 | 0.138567E+11 | 0.00 | 10.19 |
June | 0.146084E+10 | 0.954556E+10 | 0.00 | 39282962.67 | 7805978.88 | 0.00 | 0.558878E+10 | 0.00 | 10.44 |
July | 0.403899E+09 | 0.164961E+11 | 0.00 | 20231650.04 | 26043418.76 | 0.00 | 0.289307E+10 | 0.00 | 10.61 |
August | 0.314804E+09 | 0.206809E+11 | 0.00 | 12099814.65 | 46098539.63 | 0.00 | 0.113188E+10 | 0.00 | 10.79 |
September | 0.149046E+10 | 0.568167E+10 | 0.00 | 48814972.31 | 6523204.46 | 0.00 | 0.928471E+10 | 0.00 | 10.44 |
October | 0.140259E+11 | 0.739901E+09 | 0.00 | 44771623.00 | 1034258.81 | 0.00 | 0.151900E+11 | 0.00 | 10.05 |
November | 0.240458E+11 | 0.00 | 0.00 | 22768760.40 | 0.00 | 4315591.78 | 0.133558E+11 | 0.00 | 9.86 |
December | 0.414008E+11 | 0.00 | 0.00 | 4694624.73 | 0.00 | 7314091.47 | 0.408535E+10 | 0.00 | 9.69 |
Annual Sum or Average | 0.208241E+12 | 0.541656E+11 | 0.00 | 0.369574E+09 | 87655731.79 | 57992512.66 | 0.104281E+12 | 0.00 | 10.11 |
Minimum of Months | 0.314804E+09 | 0.00 | 0.00 | 2264864.95 | 0.00 | 0.00 | 0.113188E+10 | 0.00 | 9.63 |
Maximum of Months | 0.522541E+11 | 0.206809E+11 | 0.00 | 74857506.62 | 46098539.63 | 31855872.17 | 0.151900E+11 | 0.00 | 10.79 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.276823E+11 | 0.222324E+11 | 0.978302E+11 | 0.256296E+10 | -0.116393E+11 |
February | 0.296626E+11 | 0.163337E+11 | 0.767808E+11 | 0.235429E+10 | 0.277274E+10 |
March | 0.470327E+11 | 0.118684E+11 | 0.643341E+11 | 0.235852E+10 | 0.266162E+11 |
April | 0.557479E+11 | 0.745629E+10 | 0.487720E+11 | 0.232228E+10 | 0.490911E+11 |
May | 0.633335E+11 | 0.227771E+10 | 0.288017E+11 | 0.152570E+10 | 0.826950E+11 |
June | 0.637714E+11 | -0.556280E+10 | -0.651109E+10 | 0.693519E+09 | 0.128829E+12 |
July | 0.609218E+11 | -0.946238E+10 | -0.273441E+11 | 0.217572E+09 | 0.157582E+12 |
August | 0.557240E+11 | -0.114843E+11 | -0.380597E+11 | 73036376.38 | 0.171660E+12 |
September | 0.416993E+11 | -0.226437E+10 | 0.752184E+10 | 0.811772E+09 | 0.105818E+12 |
October | 0.368428E+11 | 0.807109E+10 | 0.514097E+11 | 0.236434E+10 | 0.484086E+11 |
November | 0.250305E+11 | 0.126322E+11 | 0.686098E+11 | 0.287940E+10 | 0.192354E+11 |
December | 0.223710E+11 | 0.172402E+11 | 0.816326E+11 | 0.236043E+10 | -503318986.9 |
Annual Sum or Average | 0.529820E+12 | 0.693382E+11 | 0.453778E+12 | 0.205238E+11 | 0.780566E+12 |
Minimum of Months | 0.223710E+11 | -0.114843E+11 | -0.380597E+11 | 73036376.38 | -0.116393E+11 |
Maximum of Months | 0.637714E+11 | 0.222324E+11 | 0.978302E+11 | 0.287940E+10 | 0.171660E+12 |