Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2024-07-03 12:19:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2401.86 | 10337.57 | 10337.57 |
Net Site Energy | 2401.86 | 10337.57 | 10337.57 |
Total Source Energy | 3727.53 | 16043.20 | 16043.20 |
Net Source Energy | 3727.53 | 16043.20 | 16043.20 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1142.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 272.03 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 137.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 242.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 35.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 539.56 | 1862.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1142.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 8.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 40.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 15.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 137.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 242.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 10.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 17.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1142.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 8.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 40.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 272.03 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 137.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 242.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 35.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 369.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 628.52 | 5961.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1324.59 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2322.26 | 8015.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 369.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 628.52 | 5961.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1324.59 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2322.26 | 8015.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 539.562 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 539.562 | 100.00 |
Total On-Site and Utility Electric Sources | 539.562 | 100.00 |
Total Electricity End Uses | 539.562 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 21.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4757.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 63.19 | 0.00 | 15.80 | 31.59 | 15.80 |
Gross Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Above Ground Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 63.19 | 0.00 | 15.80 | 31.59 | 15.80 |
Gross Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Above Ground Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 63.19 | 63.19 | 9.2637 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 11.9458 | 18.52 | 1072.7618 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 63.19 | 63.19 | 10.6047 | 2.48 | 594.7744 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 63.19 | 63.19 | 10.6047 | 2.48 | 594.7744 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.2637 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.9458 | 18.52 | 1072.7618 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 10.6047 | 1.24 | 594.7744 | |||||||
Conditioned Total | 232.34 | 10.6047 | 1.24 | 594.7744 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 10.6047 | 2.48 | 594.7744 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-10:20 | 12-JAN-11:09 | - | - | - | - | - | - | - | - | - | - | 02-MAY-12:50 |
Heating | 0.00 | 154950.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6076.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1971.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14269.29 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20201.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 3907.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31347.88 | 201812.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 154950.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 6076.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1971.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 13046.29 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 20201.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 3284.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 622.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1238.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 26.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 141.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 129.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 861.52 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 436.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 262.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 113.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1708.79 | 2018.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5330.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 112.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 558.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3707.96 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1878.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1131.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 487.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7354.61 | 8688.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5330.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 112.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 558.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3707.96 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1878.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1131.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 487.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7354.61 | 8688.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.74 |
KITCHEN DIRECT AIR | 1.34 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.74 | 1.74 | 1.74 | 1.74 | 1.74 | 1.74 | 1.00 | 1.00 | 1.74 |
PSZ-AC_2:2 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.00 | 1.34 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.74 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.34 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.74 | 2895.98 |
PSZ-AC_2:2_ADDAQ FAN | 1.34 | 2227.96 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.74 | 1.74 | 1.74 | 1.74 | 31640.99 | 54416.36 | 32.22 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 1.34 | 22190.52 | 100578.81 | 30.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.74 | 0.871234 | 1.16 | 31640.99 | 15820.50 | 0.800160 | 0.800160 |
PSZ-AC_2:2 COOLING COIL | 1.34 | 0.670265 | 0.893687 | 22190.52 | 11095.26 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 54416.36 |
PSZ-AC_2:2 HEATING COIL | 100578.81 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 29.76 | 63.19 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 9.264 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 126.051 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 11.946 | 281.409 | 791.353 | 0.000 | 0.000 | 0.000 | 1084.708 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 1076.175 | 9.264 | 12.293 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1076.175 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1387.759 | 11.946 | 221.217 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1387.759 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 493.000 | 4.244 | 78.587 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 493.000 | 493.000 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 730.000 | 6.284 | 116.366 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 730.000 | 730.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 4.938 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.2873 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.2873 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2550 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2550 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2025 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.381 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.381 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.845 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.845 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 4.9377744 | 4.9377744 | 4.9377744 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | -0.15938491E-16 | 0.22577064E-15 | 0.55609747E-14 | 0.92450259E-16 |
24 | 3 | -0.63183477E-08 | 0.20513873E-06 | -0.57859220E-04 | 0.15773779E-12 |
25 | 2 | 0.82781278E-04 | 0.44202424E-02 | 1.1641569 | -0.76298128E-04 |
26 | 1 | -0.10190401 | 0.11348462 | -17.249072 | 0.33938703 |
27 | 0 | 0.29164587 | 0.71919559E-01 | 16.274798 | |
28 | 4 | 0.55609747E-14 | 0.22577064E-15 | -0.15938491E-16 | 0.92450259E-16 |
29 | 3 | -0.57859220E-04 | 0.20513873E-06 | -0.63183477E-08 | 0.15773779E-12 |
30 | 2 | 1.1641569 | 0.44202424E-02 | 0.82781278E-04 | -0.76298128E-04 |
31 | 1 | -17.249072 | 0.11348462 | -0.10190401 | 0.33938703 |
32 | 0 | 16.274798 | 0.71919559E-01 | 0.29164587 | |
33 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
34 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
35 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
36 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
37 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
38 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
39 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
40 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
41 | 7 | -0.16459679E-08 | -0.32692664E-15 | 0.10422529E-13 | -0.14706702E-15 |
42 | 6 | 0.71279470E-05 | 0.48919389E-08 | 0.31855004E-02 | -0.26722647E-04 |
43 | 5 | -0.51387372E-03 | 0.28990711E-05 | -0.22347621 | 0.19539581E-02 |
44 | 4 | 0.11828338E-01 | 0.13198320E-03 | 4.8254089 | -0.45225216E-01 |
45 | 3 | -0.10389352 | 0.10497736E-02 | -37.998046 | 0.39839544 |
46 | 2 | 0.36893606 | 0.17465704E-02 | 116.43846 | -1.4173309 |
47 | 1 | -0.53252332 | 0.53234446E-03 | -143.88053 | 2.0485998 |
48 | 0 | 0.25963561 | 0.12843692E-04 | 60.838472 | |
49 | 7 | -0.16459679E-08 | -0.32692664E-15 | 0.10422529E-13 | -0.14706702E-15 |
50 | 6 | 0.71279470E-05 | 0.48919389E-08 | 0.31855004E-02 | -0.26722647E-04 |
51 | 5 | -0.51387372E-03 | 0.28990711E-05 | -0.22347621 | 0.19539581E-02 |
52 | 4 | 0.11828338E-01 | 0.13198320E-03 | 4.8254089 | -0.45225216E-01 |
53 | 3 | -0.10389352 | 0.10497736E-02 | -37.998046 | 0.39839544 |
54 | 2 | 0.36893606 | 0.17465704E-02 | 116.43846 | -1.4173309 |
55 | 1 | -0.53252332 | 0.53234446E-03 | -143.88053 | 2.0485998 |
56 | 0 | 0.25963561 | 0.12843692E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.46_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.46_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.46_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.46_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 21.722 | 0.5184 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 4 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 5 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 4 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 5 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 4 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 5 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone DINING | 1.2500 |
3 | Zone KITCHEN | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone DINING | 1.1500 |
3 | Zone KITCHEN | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 20296.73546 | 23341.24577 | 1.51519 | 1.74247 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 27.19600 | 7.00683E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 13551.19621 | 16938.99527 | 0.99448 | 1.24310 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -41.90000 | 6.45023E-005 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 15613.19336 | 17955.17236 | 1.16568 | 1.34053 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.48200 | 7.00575E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 3385.32232 | 4231.65290 | 0.24771 | 1.14133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -41.90000 | 6.45023E-005 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 24745.59 | 1.74247 | 1.74247 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 47759.46 | 1.24310 | 1.24310 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 18236.66 | 1.34053 | 1.34053 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 97752.02 | 1.14133 | 1.14133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.74247 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.34053 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.74247 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.74247 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.74247 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.74247 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.74247 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.74247 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.34053 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34053 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.34053 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34053 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.34053 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.34053 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.74247 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.34053 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.74247 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.74247 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2895.97755 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.74247 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.74247 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.74247 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.74247 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.74247 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.87123 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.16165 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31640.99000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15820.49500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80016 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80016 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31640.99000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54416.36323 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 54416.36323 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.34053 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.34053 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2227.95603 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.34053 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.34053 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.34053 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.34053 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.34053 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67026 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.89369 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22190.52000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11095.26000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22190.52000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100578.81134 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 30.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 100578.81134 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 30373.2 | 10.49 | 10.44 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 21209.8 | 10.31 | 10.26 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 7.44 | 23.24 | 7.44 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_EAST_0.4 | N/A | 2.615 | No | 15.80 | 15.80 | 15.80 | 90.00 | 90.00 | 7.11 | 2.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 14.88 | 46.47 | 14.88 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 31.59 | 31.59 | 31.59 | 180.00 | 90.00 | 14.23 | 2.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 7.44 | 23.24 | 7.44 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_WEST_0.4 | N/A | 2.615 | No | 15.80 | 15.80 | 15.80 | 270.00 | 90.00 | 7.11 | 2.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.255 | 0.240 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.287 | 0.273 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.255 | 0.240 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.287 | 0.273 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.287 | 0.269 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.287 | 0.269 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.2276683053 | 0.8498206105 | Pass | Pass | 0.4895391952 | 2.0844378841 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1035938993 | 0.4930583034 | Pass | Pass | 7.0208626549E-002 | 0.3344146986 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 5.6847111583E-002 | 4.7803016616E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 292.88 | 227.87 | 1590.27 | 24.60 | 449.07 | 2584.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 23.24 | 7.44 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 46.47 | 14.88 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 23.24 | 7.44 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.245 | 0.255 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.245 | 0.255 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.267 | 0.287 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.267 | 0.287 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.267 | 0.287 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.267 | 0.287 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.46_SHGC_EAST_0.4 | 15.80 | 0.00 | 0.00 | 15.80 | 15.80 | 2.615 | 0.401 | 0.442 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.46_SHGC_SOUTH_0.4 | 31.59 | 0.00 | 0.00 | 31.59 | 31.59 | 2.615 | 0.401 | 0.442 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.46_SHGC_WEST_0.4 | 15.80 | 0.00 | 0.00 | 15.80 | 15.80 | 2.615 | 0.401 | 0.442 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 63.19 | 2.615 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 63.19 | 2.615 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.2637 | 116.17 | 1076.18 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 19.58 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.9458 | 116.17 | 1387.76 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 25.25 |
Interior Lighting Total | 10.6047 | 232.34 | 2463.93 | 44.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 2625.88 | AstronomicalClock | - | 83.06 | 83.06 | 40.94 | |
Exterior Lighting Total | 2625.88 | 40.94 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31640.99 | 25317.85 | 6323.14 | 0.80 | 3.50 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22190.52 | 17767.06 | 4423.46 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 30373.2 | 10.49 | 10.44 | ||||
PSZ-AC_2:2 COOLING COIL | 21209.8 | 10.31 | 10.26 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 54416.36 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 100578.81 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 1.56 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 966.87 | 1.74 | 2895.98 | 1662.00 | 1.00 | 1.24 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 966.87 | 1.34 | 2227.96 | 1662.00 | 1.00 | 1.28 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 21.72 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 20296.74 | 23341.25 | 200.92 | 1.515 | 1.742 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 23.89 | 23.88 | 0.00785 | 27.20 | 0.00701 | 0.416 | 0.00 |
KITCHEN | 15613.19 | 17955.17 | 154.56 | 1.166 | 1.341 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00847 | 26.48 | 0.00701 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 13551.20 | 16939.00 | 145.81 | 0.994 | 1.243 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00799 | -41.90 | 0.00006 | 0.416 | 0.00 |
KITCHEN | 3385.32 | 4231.65 | 36.43 | 0.248 | 1.141 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.89 | 18.89 | 0.00766 | -41.90 | 0.00006 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.74 | 1.74 | 1.24 | 1.24 | 1.7425 | 1.7425 | 1.7425 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.34 | 1.34 | 1.14 | 1.14 | 1.3405 | 1.3405 | 1.3405 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 31640.990 | 25317.855 | 1.742470 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 15820.50 | 14380.24 | 1.161647 | 24.72 | 15.75 | 0.00764929 | 11.40 | 9.81 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 35.8161 | 23.88 | 0.00785119 | 41.9488 | 20259.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 54416.363 | 54416.363 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 54416.36 | 54416.36 | 1.742468 | 6.00 | 6.00 | 0.00609845 | 32.22 | 18.60 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 23.8774 | 21.11 | 0.00799111 | 50.5149 | 13551.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 22190.520 | 17767.062 | 1.340530 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 11095.26 | 10758.26 | 0.893687 | 26.42 | 15.99 | 0.00722404 | 13.62 | 10.78 | 0.00700000 | 26.48 | 0.00700575 | 15.82 | 127.7107 | 26.10 | 0.00847479 | 39.6308 | 15613.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 100578.811 | 100578.811 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100578.81 | 100578.81 | 1.340529 | -32.99 | -32.99 | 0.00118691 | 30.00 | 17.87 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 85.1405 | 18.03 | 0.00761797 | 58.3507 | 1055.27 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31640.990 | 25317.855 | 1.742470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.0596 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.742468 | 2.06559020 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 15820.50 | 14380.24 | 1.0000 | 1.37706160 | 1.161647 | 24.72 | 15.75 | 0.00764929 | 44324.2 | 11.40 | 9.81 | 0.00700000 | 29113.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15820.50 | 27.40 | 0.00700714 | 16.15 | 0.41605618 | 35.8161 | 23.88 | 0.00785119 | 23.88 | 0.00785119 | 41.9488 | 20259.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54416.363 | 54416.363 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.742468 | 2.06559020 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 54416.36 | 54416.36 | 1.0000 | 2.06559020 | 1.742468 | 6.00 | 6.00 | 0.00609845 | 21352.1 | 32.22 | 18.60 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54416.36 | -41.90 | 0.00006450 | -41.90 | 0.41605618 | 23.8774 | 21.03 | 0.00799111 | 21.11 | 0.00799111 | 50.5149 | 13551.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22190.520 | 17767.062 | 1.340530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2691 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.340529 | 1.58911596 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 11095.26 | 10758.26 | 1.0000 | 1.05941129 | 0.893687 | 26.42 | 15.99 | 0.00722404 | 44968.9 | 13.62 | 10.78 | 0.00700000 | 31371.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11095.26 | 26.48 | 0.00700575 | 15.82 | 1.14133354 | 127.7107 | 26.06 | 0.00847479 | 26.10 | 0.00847479 | 39.6308 | 15613.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 100578.811 | 100578.811 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.340529 | 1.58911596 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100578.81 | 100578.81 | 1.0000 | 1.58911596 | 1.340529 | -32.99 | -32.99 | 0.00118691 | -30250.3 | 30.00 | 17.87 | 0.00800000 | 50598.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100578.81 | -41.90 | 0.00006450 | -41.90 | 1.14133354 | 85.1405 | 18.09 | 0.00761797 | 18.03 | 0.00761797 | 58.3507 | 1055.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | FixedDryBulb | 0.42 | 1.74 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | FixedDryBulb | 1.14 | 1.34 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4994.00 | 5432.67 | 3559.67 |
KITCHEN | 5354.50 | 6298.00 | 4673.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5537.17 | 6400.83 | 4757.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 338.83 | 9.67 | 21.17 | 0.00 |
KITCHEN | 0.00 | 64.33 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 338.83 | 72.67 | 21.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.403 | 2.853 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.889 | 0.019 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.080 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.223 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 14028762.64 | 0.00 | 14028762.64 | 7180182.88 | 21208945.51 | 13120747.55 | 1330.67 | 6087.35 | 1341.98 | 525.17 |
KITCHEN | 30507707.80 | 0.00 | 30507707.80 | 85214.71 | 30592922.51 | 35993094.65 | 1456.88 | 6730.25 | 572.87 | 307.36 |
Total Facility | 44536470.44 | 0.00 | 44536470.44 | 7265397.59 | 51801868.02 | 49113842.20 | 1459.26 | 6856.52 | 1344.31 | 673.72 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5224 | 0.0000 | 0.5224 | 0.2761 | 0.7985 | 0.4161 | 0.00 | 5851.33 | 1335.67 |
KITCHEN | 1.1554 | 0.0000 | 1.1554 | 0.0019 | 1.1573 | 1.1413 | 0.00 | 6617.17 | 569.83 |
Total Facility | 1.6778 | 0.0000 | 1.6778 | 0.2780 | 1.9558 | 1.5574 | 0.00 | 6617.23 | 1335.73 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 19714117.95 | 0.00 | 19714117.95 | 13120747.55 | 1305.29 | 2.09 | 7452.62 | 525.09 |
PSZ-AC_2:2 | 42871454.25 | 0.00 | 42871454.25 | 35993094.65 | 1454.70 | 0.20 | 7305.10 | 307.36 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.7341 | 0.0000 | 0.7341 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6237 | 0.0000 | 1.6237 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 836.45 | 793.14 | 6082.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 603.74 | 6890.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.8376 | 1.0726 | 0.5848 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.8509 | 1.6041 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 365 |
Defaulted Fields | 263 |
Fields with Defaults | 866 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 539.56 | 3517.19 | 30-MAY-03:00 | 31347.88 | 22-JUL-10:20 |
Electricity:Building | 324.80 | 2625.15 | 01-JAN-01:10 | 19780.88 | 02-JAN-11:10 |
Electricity:Zone:DINING | 89.91 | 431.44 | 01-JAN-01:10 | 4898.81 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 316.86 | 2488.87 | 01-JAN-01:10 | 16486.83 | 02-JAN-11:10 |
InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 234.89 | 2193.72 | 01-JAN-01:10 | 14882.07 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 272.03 | 2119.28 | 01-JAN-01:10 | 14269.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 272.03 | 2119.28 | 01-JAN-01:10 | 14269.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 201.70 | 1849.27 | 01-JAN-01:10 | 10339.04 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 35.73 | 594.45 | 06-APR-22:30 | 3919.35 | 30-JUN-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 27.79 | 508.67 | 07-DEC-23:10 | 1617.92 | 25-JUL-03:40 |
LowTempRefrigeration:Refrigeration:Electricity | 10.45 | 0.00 | 01-JAN-11:10 | 980.83 | 25-JUL-03:40 |
MedTempRefrigeration:Refrigeration:Electricity | 17.34 | 475.34 | 17-JAN-01:10 | 637.09 | 22-JUN-02:20 |
ElectricityPurchased:Facility | 539.56 | 3517.19 | 30-MAY-03:00 | 31347.88 | 22-JUL-10:20 |
ElectricityPurchased:Plant | 539.56 | 3517.19 | 30-MAY-03:00 | 31347.88 | 22-JUL-10:20 |
Cogeneration:ElectricityPurchased | 539.56 | 3517.19 | 30-MAY-03:00 | 31347.88 | 22-JUL-10:20 |
General:Cogeneration:ElectricityPurchased | 539.56 | 3517.19 | 30-MAY-03:00 | 31347.88 | 22-JUL-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 539.56 | 3517.19 | 30-MAY-03:00 | 31347.88 | 22-JUL-10:20 |
ElectricityNet:Plant | 539.56 | 3517.19 | 30-MAY-03:00 | 31347.88 | 22-JUL-10:20 |
Cogeneration:ElectricityNet | 539.56 | 3517.19 | 30-MAY-03:00 | 31347.88 | 22-JUL-10:20 |
General:Cogeneration:ElectricityNet | 539.56 | 3517.19 | 30-MAY-03:00 | 31347.88 | 22-JUL-10:20 |
Electricity:HVAC | 146.03 | 0.00 | 01-JAN-01:40 | 15314.20 | 29-JUL-17:10 |
Fans:Electricity | 137.81 | 0.00 | 01-JAN-01:40 | 5123.93 | 30-JAN-05:10 |
General:Fans:Electricity | 137.81 | 0.00 | 01-JAN-01:40 | 5123.93 | 30-JAN-05:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 8.22 | 0.00 | 01-JAN-00:10 | 10190.27 | 29-JUL-17:10 |
General:Cooling:Electricity | 8.22 | 0.00 | 01-JAN-00:10 | 10190.27 | 29-JUL-17:10 |
ExteriorLights:Electricity | 40.94 | 0.00 | 01-JAN-11:20 | 2625.88 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 40.94 | 0.00 | 01-JAN-11:20 | 2625.88 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1862.30 | 1838.65 | 15-MAY-02:40 | 201812.54 | 12-JAN-11:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 1142.60 | 0.00 | 01-JAN-01:40 | 158791.97 | 12-JAN-07:10 |
Heating:NaturalGas | 1142.60 | 0.00 | 01-JAN-01:40 | 158791.97 | 12-JAN-07:10 |
General:Heating:NaturalGas | 1142.60 | 0.00 | 01-JAN-01:40 | 158791.97 | 12-JAN-07:10 |
NaturalGas:Plant | 242.54 | 0.00 | 18-APR-03:50 | 29767.03 | 02-APR-12:20 |
WaterSystems:NaturalGas | 242.54 | 0.00 | 18-APR-03:50 | 29767.03 | 02-APR-12:20 |
Water Heater:WaterSystems:NaturalGas | 242.54 | 0.00 | 18-APR-03:50 | 29767.03 | 02-APR-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-MAY-12:50 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-MAY-12:50 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-MAY-12:50 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-MAY-12:50 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-MAY-12:50 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-MAY-12:50 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-MAY-12:50 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-MAY-12:50 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1712.59 | 2415.08 | 04-MAR-01:10 | 185258.96 | 12-JAN-14:00 |
EnergyTransfer:Building | 524.02 | 1207.54 | 04-MAR-01:10 | 46571.03 | 13-JAN-12:10 |
EnergyTransfer:Zone:KITCHEN | 298.12 | 1207.39 | 12-JAN-01:10 | 22912.08 | 22-AUG-04:10 |
Refrigeration:EnergyTransfer | 126.59 | 2414.78 | 12-JAN-01:10 | 7834.84 | 30-JUN-03:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 63.30 | 1207.39 | 12-JAN-01:10 | 3917.42 | 30-JUN-03:40 |
General:Refrigeration:EnergyTransfer | 63.30 | 1207.39 | 12-JAN-01:10 | 3917.42 | 30-JUN-03:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 63.30 | 1207.39 | 12-JAN-01:10 | 3917.42 | 30-JUN-03:40 |
EnergyTransfer:Plant | 249.74 | 1207.39 | 12-JAN-01:10 | 26011.07 | 11-MAY-12:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.78 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 50.52 | 1059.55 | 17-JAN-01:10 | 2238.70 | 22-JUN-02:20 |
EnergyTransfer:Zone:DINING | 225.90 | 0.00 | 01-JAN-01:40 | 34621.82 | 06-DEC-04:00 |
Heating:EnergyTransfer | 174.77 | 0.00 | 01-JAN-00:30 | 33307.35 | 15-DEC-18:10 |
Heating:EnergyTransfer:Zone:DINING | 174.60 | 0.00 | 01-JAN-00:10 | 33307.35 | 15-DEC-18:10 |
General:Heating:EnergyTransfer | 174.77 | 0.00 | 01-JAN-00:30 | 33307.35 | 15-DEC-18:10 |
General:Heating:EnergyTransfer:Zone:DINING | 174.60 | 0.00 | 01-JAN-00:10 | 33307.35 | 15-DEC-18:10 |
Cooling:EnergyTransfer | 285.95 | 0.00 | 01-JAN-01:40 | 25845.19 | 11-JUL-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 51.29 | 0.00 | 01-JAN-01:00 | 16701.05 | 13-JAN-04:50 |
General:Cooling:EnergyTransfer | 285.95 | 0.00 | 01-JAN-01:40 | 25845.19 | 11-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 51.29 | 0.00 | 01-JAN-01:00 | 16701.05 | 13-JAN-04:50 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.16 | 0.00 | 01-JAN-00:20 | 2335.14 | 15-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.16 | 0.00 | 01-JAN-00:20 | 2335.14 | 15-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 234.66 | 0.00 | 01-JAN-01:10 | 19072.16 | 02-JUN-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 234.66 | 0.00 | 01-JAN-01:10 | 19072.16 | 02-JUN-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 186.44 | 0.00 | 01-JAN-00:10 | 23590.35 | 04-APR-12:10 |
PlantLoopHeatingDemand:Plant | 186.44 | 0.00 | 01-JAN-00:10 | 23590.35 | 04-APR-12:10 |
WaterSystems:PlantLoopHeatingDemand | 186.44 | 0.00 | 01-JAN-00:10 | 23590.35 | 04-APR-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 186.44 | 0.00 | 01-JAN-00:10 | 23590.35 | 04-APR-12:10 |
EnergyTransfer:HVAC | 938.83 | 0.00 | 01-JAN-01:40 | 126352.79 | 12-JAN-07:10 |
HeatingCoils:EnergyTransfer | 909.46 | 0.00 | 01-JAN-01:40 | 126352.79 | 12-JAN-07:10 |
CoolingCoils:EnergyTransfer | 29.37 | 0.00 | 01-JAN-00:10 | 39401.72 | 29-JUL-17:10 |
WaterSystems:EnergyTransfer | 186.44 | 0.00 | 01-JAN-00:10 | 23590.35 | 04-APR-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 186.44 | 0.00 | 01-JAN-00:10 | 23590.35 | 04-APR-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 174.605 | -51.291 | 0.000 | 0.000 | 73.051 | 19.580 | 52.748 | 44.921 | 0.000 | 0.222 | 0.001 | 0.000 | -68.538 | 0.000 | -197.342 | -47.956 |
KITCHEN | 0.000 | 0.000 | 0.163 | -234.657 | 0.000 | 0.000 | 5.519 | 25.249 | 207.409 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | -2.124 | -1.558 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.379 | 7.596 | 0.000 | 0.000 | 0.000 | -9.975 | -0.000 |
Total Facility | 0.000 | 0.000 | 174.767 | -285.948 | 0.000 | 0.000 | 78.570 | 44.830 | 260.157 | 44.921 | 0.000 | 2.600 | 7.599 | 0.000 | -68.538 | 0.000 | -209.442 | -49.514 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-JAN-04:33 | 0.00 | 0.00 | 0.00 | -56028.07 | 0.00 | 0.00 | 0.00 | 161.43 | 506.27 | 0.00 | 0.00 | 0.00 | 62048.18 | 0.00 | -6524.79 | 0.00 | -163.02 | 0.00 |
KITCHEN | 22-DEC-05:01 | 0.00 | 0.00 | 0.00 | -62629.57 | 0.00 | 0.00 | 21.42 | 277.55 | 5126.85 | 0.00 | 0.00 | 0.00 | 57216.06 | 0.00 | -0.00 | 0.00 | -12.31 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-AUG-02:61 | 0.00 | 0.00 | 0.00 | -80923.65 | 0.00 | 0.00 | 0.00 | 369.59 | 2075.06 | 0.00 | 0.00 | 252.46 | 80841.26 | 0.00 | -2155.28 | 0.00 | -459.44 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 09-FEB-03:01 | 0.00 | 0.00 | 43489.03 | 0.00 | 0.00 | 0.00 | 0.00 | 161.43 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1985.46 | 0.00 | -102.89 | -41764.61 |
KITCHEN | 15-DEC-05:02 | 0.00 | 0.00 | 23326.71 | 0.00 | 0.00 | 0.00 | 22.33 | 277.55 | 5126.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28753.44 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-DEC-05:02 | 0.00 | 0.00 | 49581.95 | 0.00 | 0.00 | 0.00 | 474.41 | 492.79 | 6346.59 | 0.00 | 0.00 | 202.32 | 0.00 | 0.00 | -6016.46 | 0.00 | 0.00 | -51081.60 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7425 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.7425 | 0.2388 | 1.0000 | Not calculated | 0.4161 | 0.2388 | ||
PSZ-AC_2:2 | 1.3405 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3405 | 0.1128 | 1.0000 | Not calculated | 0.1513 | 0.1128 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7425 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.7425 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2388 | ||
PSZ-AC_2:2 | 1.3405 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3405 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1128 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7425 | 1.7425 | 1.7425 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3405 | 1.3405 | 1.3405 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7425 | 1.7425 | 1.7425 | 1.7425 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3405 | 1.3405 | 1.3405 | 1.3405 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7425 | 1.7425 | 1.7425 | No | 0.4161 | 0.3347 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3405 | 1.3405 | 1.3405 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7425 | 1.7425 | 1.7425 | 1.7425 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3405 | 1.3405 | 1.3405 | 1.3405 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 21.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 21.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1142.60 | 158791.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 8.22 | 10190.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 44.83 | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 40.94 | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 15.55 | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 23.02 | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 137.81 | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 242.54 | 29767.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 10.45 | 980.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 17.34 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 307.76 | 539.56 |
Natural Gas | 477.16 | 1862.30 |
Additional | 0.00 | 0.00 |
Total | 784.92 | 2401.86 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 192.95 |
Space Heating | 0.00 |
Space Cooling | 35.39 |
Fans (All) | 593.13 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1170.81 |
Miscellaneous (All) | 2322.26 |
Subtotal | 2322.26 |
Natural Gas [MJ/m2] | |
Space Heating | 4917.73 |
Service Water Heating | 1043.90 |
Miscellaneous (All) | 8015.31 |
Subtotal | 8015.31 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.87 |
Space Heating | 47.57 |
Space Cooling | 0.34 |
Fans (All) | 5.74 |
Service Water Heating | 10.10 |
Receptacle Equipment | 31.19 |
Miscellaneous | 3.19 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8561.33 | 198.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 7875.83 | 492.83 | 329.00 | 62.33 | 0.00 |
Min | 7875.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 492.83 | 329.00 | 62.33 | 0.00 |
Average | 8399.06 | 230.50 | 109.67 | 20.78 | 0.00 |
Sum | 25197.17 | 691.50 | 329.00 | 62.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8369.83 | 390.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 8012.17 | 627.00 | 98.33 | 22.50 | 0.00 |
Min | 8012.17 | 4.67 | 0.00 | 0.00 | 0.00 |
Max | 8755.33 | 627.00 | 98.33 | 22.50 | 0.00 |
Average | 8379.11 | 340.61 | 32.78 | 7.50 | 0.00 |
Sum | 25137.33 | 1021.83 | 98.33 | 22.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 254690.00 | 35.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15603.00 | 655.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254690.00 | 655.00 | 0.00 | 0.00 | 0.00 |
Average | 90097.67 | 230.00 | 0.00 | 0.00 | 0.00 |
Sum | 270293.00 | 690.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141593E+10 | 56028.82 | 12-JAN-04:33 | -37.6 | -37.7 | 0.440168E+10 | 3722.80 | 14-JAN-19:10 | -21.8 | -22.0 |
February | 0.129088E+10 | 52333.13 | 27-FEB-04:43 | -35.8 | -35.9 | 0.402379E+10 | 3722.80 | 18-FEB-19:10 | -35.8 | -35.9 |
March | 0.112168E+10 | 39024.85 | 01-MAR-04:45 | -28.2 | -28.6 | 0.449065E+10 | 3722.83 | 18-MAR-18:30 | 1.95 | 0.04 |
April | 0.250251E+10 | 26234.39 | 03-APR-03:43 | -21.1 | -21.6 | 0.442880E+10 | 4680.85 | 22-APR-18:10 | 12.62 | 5.42 |
May | 0.613049E+10 | 9862.50 | 31-MAY-16:05 | 22.12 | 10.79 | 0.504489E+10 | 4681.01 | 13-MAY-18:19 | 22.12 | 10.79 |
June | 0.103987E+11 | 33954.79 | 04-JUN-02:61 | 15.82 | 10.16 | 0.517998E+10 | 4681.01 | 03-JUN-18:19 | 15.82 | 10.16 |
July | 0.119819E+11 | 35692.92 | 13-JUL-02:61 | 14.82 | 9.29 | 0.530848E+10 | 4681.45 | 08-JUL-18:10 | 14.82 | 9.29 |
August | 0.936855E+10 | 40526.27 | 11-AUG-02:61 | 12.02 | 7.35 | 0.525117E+10 | 4681.10 | 26-AUG-18:30 | 20.60 | 13.96 |
September | 0.297859E+10 | 6728.33 | 28-SEP-23:01 | -1.2 | -2.4 | 0.453598E+10 | 4680.90 | 16-SEP-18:19 | -1.2 | -2.4 |
October | 0.925038E+09 | 20718.92 | 22-OCT-03:47 | -18.0 | -18.3 | 0.445413E+10 | 3722.81 | 14-OCT-18:40 | -18.0 | -18.3 |
November | 0.146946E+10 | 40437.62 | 29-NOV-04:09 | -28.9 | -29.1 | 0.429978E+10 | 3722.81 | 04-NOV-18:19 | -28.9 | -29.1 |
December | 0.170832E+10 | 47638.84 | 15-DEC-04:47 | -33.1 | -33.2 | 0.443909E+10 | 3722.80 | 02-DEC-19:19 | -33.1 | -33.2 |
Annual Sum or Average | 0.512920E+11 | 0.558584E+11 | ||||||||
Minimum of Months | 0.925038E+09 | 6728.33 | -37.6 | -37.7 | 0.402379E+10 | 3722.80 | -35.8 | -35.9 | ||
Maximum of Months | 0.119819E+11 | 56028.82 | 22.12 | 10.79 | 0.530848E+10 | 4681.45 | 22.12 | 13.96 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163278E+11 | 53715.40 | 03-JAN-05:01 | -20.8 | -20.9 | 0.768043E+10 | 5036.86 | 18-JAN-11:00 | -10.6 | -10.8 |
February | 0.146413E+11 | 53487.48 | 17-FEB-05:01 | -21.0 | -21.2 | 0.693764E+10 | 5036.86 | 21-FEB-11:00 | -19.4 | -19.7 |
March | 0.175631E+11 | 57324.68 | 31-MAR-04:01 | -24.5 | -25.0 | 0.768291E+10 | 5036.86 | 08-MAR-11:00 | -24.5 | -25.0 |
April | 0.195028E+11 | 42806.18 | 09-APR-04:01 | -13.4 | -14.5 | 0.744109E+10 | 5061.17 | 22-APR-10:00 | 12.80 | 6.00 |
May | 0.214800E+11 | 43974.63 | 14-MAY-02:61 | 8.72 | 4.17 | 0.775390E+10 | 5135.91 | 31-MAY-10:00 | 18.90 | 10.59 |
June | 0.214322E+11 | 41558.61 | 17-JUN-02:61 | 8.80 | 7.19 | 0.757230E+10 | 5135.94 | 30-JUN-10:39 | 21.67 | 16.64 |
July | 0.228841E+11 | 40787.01 | 31-JUL-02:61 | 8.12 | 7.57 | 0.782656E+10 | 5135.95 | 27-JUL-10:00 | 8.12 | 7.57 |
August | 0.234747E+11 | 40979.15 | 29-AUG-02:61 | 7.70 | 6.84 | 0.780549E+10 | 5135.93 | 04-AUG-10:00 | 7.70 | 6.84 |
September | 0.224200E+11 | 35086.65 | 29-SEP-04:01 | -3.9 | -4.5 | 0.746146E+10 | 5073.35 | 19-SEP-10:00 | -3.9 | -4.5 |
October | 0.210162E+11 | 50682.69 | 31-OCT-04:01 | -17.9 | -18.4 | 0.768239E+10 | 5057.12 | 04-OCT-10:00 | -17.9 | -18.4 |
November | 0.172490E+11 | 61792.22 | 28-NOV-05:01 | -27.7 | -27.9 | 0.743255E+10 | 5036.86 | 10-NOV-11:00 | -27.7 | -27.9 |
December | 0.166715E+11 | 62447.62 | 22-DEC-05:01 | -28.2 | -28.4 | 0.768032E+10 | 5036.86 | 18-DEC-11:09 | -28.2 | -28.4 |
Annual Sum or Average | 0.234663E+12 | 0.909570E+11 | ||||||||
Minimum of Months | 0.146413E+11 | 35086.65 | -28.2 | -28.4 | 0.693764E+10 | 5036.86 | -28.2 | -28.4 | ||
Maximum of Months | 0.234747E+11 | 62447.62 | 8.80 | 7.57 | 0.782656E+10 | 5135.95 | 21.67 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 | -29.2 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 | -13.3 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 | 2.18 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 | 8.14 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 | 11.83 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 | 0.12 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.00 | 0.00 | -28.9 | -29.2 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350208E+11 | 41479.13 | 19-JAN-03:01 | -4.2 |
February | 0.275936E+11 | 43489.84 | 09-FEB-03:01 | 1.93 |
March | 0.206453E+11 | 42161.10 | 22-MAR-02:61 | -0.7 |
April | 0.610216E+10 | 39533.54 | 16-APR-02:61 | -6.1 |
May | 0.428892E+09 | 27646.09 | 28-MAY-02:61 | 0.10 |
June | 2899865.33 | 9978.48 | 24-JUN-02:03 | 16.52 |
July | 2290506.94 | 8183.91 | 13-JUL-02:03 | 14.82 |
August | 90935960.16 | 5353.66 | 31-AUG-06:10 | -1.5 |
September | 0.226322E+10 | 30142.54 | 28-SEP-02:61 | -1.1 |
October | 0.130525E+11 | 40213.29 | 19-OCT-02:61 | -3.3 |
November | 0.319689E+11 | 39958.98 | 18-NOV-03:11 | -7.6 |
December | 0.374326E+11 | 42230.10 | 24-DEC-03:01 | -1.0 |
Annual Sum or Average | 0.174604E+12 | |||
Minimum of Months | 2290506.94 | 5353.66 | -7.6 | |
Maximum of Months | 0.374326E+11 | 43489.84 | 16.52 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30111690.91 | 19276.85 | 31-JAN-05:02 | -26.0 |
February | 27106806.69 | 18098.45 | 21-FEB-05:02 | -22.9 |
March | 24937317.83 | 17758.01 | 31-MAR-04:02 | -24.5 |
April | 8216426.28 | 13321.15 | 02-APR-04:02 | -14.3 |
May | 184884.03 | 1501.05 | 06-MAY-04:04 | 1.88 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 702347.09 | 6926.19 | 30-SEP-04:03 | -4.0 |
October | 4466748.40 | 10142.99 | 13-OCT-04:03 | -9.0 |
November | 28527037.17 | 18533.43 | 25-NOV-05:02 | -22.7 |
December | 38473009.33 | 23351.41 | 15-DEC-05:02 | -33.2 |
Annual Sum or Average | 0.162726E+09 | |||
Minimum of Months | 0.00 | 0.00 | -33.2 | |
Maximum of Months | 38473009.33 | 23351.41 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165449E+10 | 968.56 | 02-JAN-10:09 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.149855E+10 | 968.56 | 01-FEB-10:09 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.168084E+10 | 968.56 | 01-MAR-10:09 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.160761E+10 | 968.56 | 01-APR-16:10 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.166766E+10 | 968.56 | 01-MAY-09:09 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.162466E+10 | 968.56 | 01-JUN-09:09 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.165081E+10 | 968.56 | 01-JUL-16:10 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.168084E+10 | 968.56 | 01-AUG-09:09 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.160800E+10 | 968.56 | 01-SEP-09:09 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.165430E+10 | 968.56 | 02-OCT-09:09 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.160161E+10 | 968.56 | 01-NOV-09:09 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.165100E+10 | 968.56 | 01-DEC-10:09 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.195804E+11 | 0.703313E+11 | ||||
Minimum of Months | 0.149855E+10 | 968.56 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.168084E+10 | 968.56 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.213351E+10 | 1248.98 | 02-JAN-10:09 | 0.171305E+11 | 10339.04 | 01-JAN-11:09 |
February | 0.193243E+10 | 1248.98 | 01-FEB-10:09 | 0.154728E+11 | 10339.04 | 01-FEB-11:09 |
March | 0.216749E+10 | 1248.98 | 01-MAR-10:09 | 0.171306E+11 | 10339.04 | 01-MAR-11:09 |
April | 0.207306E+10 | 1248.98 | 01-APR-16:10 | 0.165779E+11 | 10339.04 | 01-APR-10:09 |
May | 0.215050E+10 | 1248.98 | 01-MAY-09:09 | 0.171306E+11 | 10339.04 | 01-MAY-10:09 |
June | 0.209504E+10 | 1248.98 | 01-JUN-09:09 | 0.165780E+11 | 10339.04 | 01-JUN-10:09 |
July | 0.212877E+10 | 1248.98 | 01-JUL-16:10 | 0.171305E+11 | 10339.04 | 01-JUL-10:09 |
August | 0.216749E+10 | 1248.98 | 01-AUG-09:09 | 0.171306E+11 | 10339.04 | 01-AUG-10:09 |
September | 0.207356E+10 | 1248.98 | 01-SEP-09:09 | 0.165779E+11 | 10339.04 | 01-SEP-10:09 |
October | 0.213326E+10 | 1248.98 | 02-OCT-09:09 | 0.171305E+11 | 10339.04 | 01-OCT-10:09 |
November | 0.206532E+10 | 1248.98 | 01-NOV-09:09 | 0.165780E+11 | 10339.04 | 01-NOV-10:09 |
December | 0.212902E+10 | 1248.98 | 01-DEC-10:09 | 0.171305E+11 | 10339.04 | 01-DEC-11:09 |
Annual Sum or Average | 0.252494E+11 | 0.201699E+12 | ||||
Minimum of Months | 0.193243E+10 | 1248.98 | 0.154728E+11 | 10339.04 | ||
Maximum of Months | 0.216749E+10 | 1248.98 | 0.171306E+11 | 10339.04 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.165449E+10 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297960E+11 |
February | 0.852256E+10 | 0.149855E+10 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247774E+11 |
March | 0.954557E+10 | 0.168084E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228730E+11 |
April | 0.915225E+10 | 0.160761E+10 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131477E+11 |
May | 0.947560E+10 | 0.166766E+10 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712741E+10 |
June | 0.922788E+10 | 0.162466E+10 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64728824.01 | 0.402104E+10 |
July | 0.939996E+10 | 0.165081E+10 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138303E+09 | 0.343855E+10 |
August | 0.954557E+10 | 0.168084E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18576766.29 | 0.523740E+10 |
September | 0.915225E+10 | 0.160800E+10 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951945E+10 |
October | 0.940563E+10 | 0.165430E+10 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175538E+11 |
November | 0.909363E+10 | 0.160161E+10 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285973E+11 |
December | 0.939996E+10 | 0.165100E+10 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312534E+11 |
Annual Sum or Average | 0.111326E+12 | 0.195804E+11 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221609E+09 | 0.197342E+12 |
Minimum of Months | 0.852256E+10 | 0.149855E+10 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343855E+10 |
Maximum of Months | 0.954557E+10 | 0.168084E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138303E+09 | 0.312534E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.213351E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227738E+09 |
February | 0.610713E+09 | 0.193243E+10 | 0.117185E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188014E+09 |
March | 0.684021E+09 | 0.216749E+10 | 0.129742E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294624E+09 |
April | 0.655836E+09 | 0.207306E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287567E+09 |
May | 0.679007E+09 | 0.215050E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184183E+09 |
June | 0.661256E+09 | 0.209504E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 55014.31 | 0.115693E+09 |
July | 0.673587E+09 | 0.212877E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 306441.85 | 86768123.36 |
August | 0.684021E+09 | 0.216749E+10 | 0.129742E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110414E+09 |
September | 0.655836E+09 | 0.207356E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111708E+09 |
October | 0.673993E+09 | 0.213326E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249763E+09 |
November | 0.651635E+09 | 0.206532E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91635954.98 |
December | 0.673587E+09 | 0.212902E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176350E+09 |
Annual Sum or Average | 0.797748E+10 | 0.252494E+11 | 0.152760E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 361456.16 | 0.212446E+10 |
Minimum of Months | 0.610713E+09 | 0.193243E+10 | 0.117185E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86768123.36 |
Maximum of Months | 0.684021E+09 | 0.216749E+10 | 0.129742E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 306441.85 | 0.294624E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315272E+09 | 64193809.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248752E+09 | 0.292703E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173910E+09 | 0.899479E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158319E+09 | 0.137821E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124013E+09 | 0.161116E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64938340.76 | 0.169460E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78057154.63 | 0.159483E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133314E+09 | 0.124896E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203725E+09 | 0.687240E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175178E+09 | 0.360244E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379652E+09 | 0.121139E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323398E+09 | 22230930.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237853E+10 | 0.997499E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64938340.76 | 22230930.18 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379652E+09 | 0.169460E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 968.56 | 02-JAN-10:09 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 40425.80 | 12-JAN-12:01 |
February | 9454.80 | 04-FEB-19:10 | 968.56 | 01-FEB-10:09 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 35554.10 | 27-FEB-12:05 |
March | 9454.80 | 04-MAR-19:10 | 968.56 | 01-MAR-10:09 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 29494.06 | 01-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 968.56 | 01-APR-16:10 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 19621.83 | 01-APR-19:00 |
May | 9454.80 | 06-MAY-18:10 | 968.56 | 01-MAY-09:09 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 10372.22 | 26-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 968.56 | 01-JUN-09:09 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.77 | 20-JUN-17:55 | 6688.88 | 24-JUN-19:00 |
July | 9454.80 | 01-JUL-18:10 | 968.56 | 01-JUL-16:10 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2794.89 | 29-JUL-17:03 | 6251.61 | 05-JUL-12:00 |
August | 9454.80 | 05-AUG-18:10 | 968.56 | 01-AUG-09:09 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 962.88 | 11-AUG-17:05 | 8809.83 | 30-AUG-19:53 |
September | 9454.80 | 02-SEP-18:10 | 968.56 | 01-SEP-09:09 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 14981.94 | 30-SEP-19:00 |
October | 9454.80 | 07-OCT-18:10 | 968.56 | 02-OCT-09:09 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 25585.07 | 30-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 968.56 | 01-NOV-09:09 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 33964.73 | 25-NOV-20:00 |
December | 9454.80 | 02-DEC-19:10 | 968.56 | 01-DEC-10:09 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 37618.22 | 15-DEC-12:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 968.56 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6251.61 | |||||
Maximum of Months | 9454.80 | 968.56 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2794.89 | 40425.80 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 1248.98 | 02-JAN-10:09 | 7604.23 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1482.30 | 29-JAN-01:10 |
February | 677.52 | 04-FEB-19:10 | 1248.98 | 01-FEB-10:09 | 7604.23 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 987.06 | 24-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 1248.98 | 01-MAR-10:09 | 7604.23 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 757.78 | 25-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 1248.98 | 01-APR-16:10 | 7604.23 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 830.06 | 07-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 1248.98 | 01-MAY-09:09 | 7604.23 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 557.62 | 26-MAY-02:00 |
June | 677.52 | 03-JUN-18:10 | 1248.98 | 01-JUN-09:09 | 7604.23 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 11.20 | 30-JUN-15:00 | 579.56 | 25-JUN-04:00 |
July | 677.52 | 01-JUL-18:10 | 1248.98 | 01-JUL-16:10 | 7604.23 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 33.20 | 21-JUL-16:00 | 360.84 | 30-JUL-01:20 |
August | 677.52 | 05-AUG-18:10 | 1248.98 | 01-AUG-09:09 | 7604.23 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 433.42 | 30-AUG-01:00 |
September | 677.52 | 02-SEP-18:10 | 1248.98 | 01-SEP-09:09 | 7604.23 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 307.22 | 30-SEP-02:00 |
October | 677.52 | 07-OCT-18:10 | 1248.98 | 02-OCT-09:09 | 7604.23 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 746.45 | 21-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 1248.98 | 01-NOV-09:09 | 7604.23 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 603.31 | 10-NOV-05:00 |
December | 677.52 | 02-DEC-19:10 | 1248.98 | 01-DEC-10:09 | 7604.23 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 608.74 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 1248.98 | 7604.23 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 307.22 | ||||||
Maximum of Months | 677.52 | 1248.98 | 7604.23 | 7998.14 | 0.00 | 0.00 | 0.00 | 33.20 | 1482.30 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.98 | 18-JAN-02:51 | 549.00 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.95 | 06-FEB-21:00 | 1161.07 | 27-FEB-13:30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.50 | 27-MAR-07:32 | 1896.34 | 26-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.24 | 21-APR-05:45 | 1834.52 | 27-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.71 | 22-MAY-03:30 | 1948.15 | 31-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.67 | 07-JUN-01:00 | 1991.45 | 08-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.48 | 11-JUL-24:00 | 2049.53 | 23-JUL-12:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.39 | 31-AUG-24:00 | 1866.08 | 09-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.72 | 19-SEP-01:55 | 1299.36 | 07-SEP-12:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.63 | 31-OCT-08:00 | 922.03 | 22-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.05 | 18-NOV-03:52 | 645.31 | 06-NOV-14:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 608.50 | 23-DEC-01:53 | 332.48 | 27-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.71 | 332.48 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.05 | 2049.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 56028.82 | 12-JAN-04:33 | 0.00 | 1614.26 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.02 |
February | 52333.13 | 27-FEB-04:43 | 0.00 | 1614.26 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39024.85 | 01-MAR-04:45 | 0.00 | 1614.26 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.73 |
April | 26234.39 | 03-APR-03:43 | 0.00 | 1614.26 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.12 |
May | 9862.50 | 31-MAY-16:05 | 10505.33 | 1937.12 | 7047.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.44 |
June | 33954.79 | 04-JUN-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.70 |
July | 35692.92 | 13-JUL-02:61 | 0.00 | 1129.98 | 1890.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.73 |
August | 40526.27 | 11-AUG-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.57 |
September | 6728.33 | 28-SEP-23:01 | 3676.87 | 1129.98 | 2846.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.14 |
October | 20718.92 | 22-OCT-03:47 | 0.00 | 1614.26 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.55 |
November | 40437.62 | 29-NOV-04:09 | 0.00 | 1614.26 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 47638.84 | 15-DEC-04:47 | 0.00 | 1614.26 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6728.33 | 0.00 | 1129.98 | 1890.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56028.82 | 10505.33 | 1937.12 | 7047.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 53715.40 | 03-JAN-05:01 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53487.48 | 17-FEB-05:01 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 |
March | 57324.68 | 31-MAR-04:01 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 107.61 |
April | 42806.18 | 09-APR-04:01 | 0.00 | 1873.47 | 34680.13 | 29786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 87.16 |
May | 43974.63 | 14-MAY-02:61 | 0.00 | 1873.47 | 14952.52 | 4964.36 | 0.00 | 0.00 | 0.00 | 0.00 | 152.46 |
June | 41558.61 | 17-JUN-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40787.01 | 31-JUL-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 176.22 |
August | 40979.15 | 29-AUG-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 188.32 |
September | 35086.65 | 29-SEP-04:01 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 37.58 |
October | 50682.69 | 31-OCT-04:01 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 139.44 |
November | 61792.22 | 28-NOV-05:01 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 62447.62 | 22-DEC-05:01 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35086.65 | 0.00 | 1873.47 | 14952.52 | 4964.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62447.62 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 188.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.16 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.99 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.20 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.44 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.82 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.99 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.11 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.61 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.19 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.474417E+11 | 28064.60 | 02-JAN-11:09 | 0.273271E+12 | 201812.54 | 12-JAN-11:09 |
February | 0.419751E+11 | 25446.94 | 09-FEB-11:20 | 0.229541E+12 | 186998.92 | 27-FEB-11:09 |
March | 0.454039E+11 | 25448.50 | 22-MAR-10:20 | 0.209684E+12 | 153921.57 | 01-MAR-08:09 |
April | 0.427285E+11 | 25449.40 | 28-APR-10:20 | 0.120871E+12 | 125916.22 | 03-APR-07:10 |
May | 0.433707E+11 | 25676.35 | 31-MAY-16:10 | 0.703262E+11 | 75236.85 | 27-MAY-10:09 |
June | 0.436288E+11 | 31028.64 | 30-JUN-11:00 | 0.592538E+11 | 51977.68 | 01-JUN-12:30 |
July | 0.470061E+11 | 31347.88 | 22-JUL-10:20 | 0.604400E+11 | 50845.04 | 01-JUL-12:00 |
August | 0.457656E+11 | 28829.54 | 11-AUG-16:10 | 0.622899E+11 | 58223.82 | 31-AUG-07:10 |
September | 0.432332E+11 | 25467.92 | 01-SEP-10:20 | 0.824559E+11 | 85533.04 | 29-SEP-10:09 |
October | 0.457103E+11 | 25456.31 | 02-OCT-10:20 | 0.154600E+12 | 130948.09 | 31-OCT-10:09 |
November | 0.454550E+11 | 25439.68 | 02-NOV-10:20 | 0.256662E+12 | 173362.43 | 30-NOV-11:09 |
December | 0.478426E+11 | 28065.03 | 26-DEC-11:20 | 0.282906E+12 | 194613.91 | 15-DEC-13:09 |
Annual Sum or Average | 0.539562E+12 | 0.186230E+13 | ||||
Minimum of Months | 0.419751E+11 | 25439.68 | 0.592538E+11 | 50845.04 | ||
Maximum of Months | 0.478426E+11 | 31347.88 | 0.282906E+12 | 201812.54 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.378800E+10 | 0.564984E+10 | 0.231039E+11 | 0.00 | 0.119906E+11 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343098E+10 | 0.422714E+10 | 0.208680E+11 | 0.00 | 0.108204E+11 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384832E+10 | 0.368831E+10 | 0.231040E+11 | 0.00 | 0.118453E+11 | 0.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368067E+10 | 0.259647E+10 | 0.223586E+11 | 0.00 | 0.112409E+11 | 0.77 | 0.00 | 152851.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.381816E+10 | 0.169684E+10 | 0.231040E+11 | 0.00 | 0.114597E+11 | 0.80 | 0.00 | 0.193600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371970E+10 | 0.945317E+09 | 0.223587E+11 | 0.00 | 0.111533E+11 | 0.77 | 0.00 | 0.228014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377958E+10 | 0.131399E+10 | 0.231038E+11 | 0.00 | 0.115428E+11 | 0.79 | 0.00 | 0.396728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.384832E+10 | 0.226718E+10 | 0.231040E+11 | 0.00 | 0.115227E+11 | 0.80 | 0.00 | 0.177973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.368156E+10 | 0.315263E+10 | 0.223586E+11 | 0.00 | 0.111036E+11 | 0.77 | 0.00 | 1711199.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378756E+10 | 0.425235E+10 | 0.231039E+11 | 0.00 | 0.116204E+11 | 0.79 | 0.00 | 209025.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366693E+10 | 0.509998E+10 | 0.223586E+11 | 0.00 | 0.115106E+11 | 0.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378002E+10 | 0.605003E+10 | 0.231038E+11 | 0.00 | 0.119983E+11 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448298E+11 | 0.409401E+11 | 0.272030E+12 | 0.00 | 0.137809E+12 | 9.37 | 0.00 | 0.822282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.343098E+10 | 0.945317E+09 | 0.208680E+11 | 0.00 | 0.108204E+11 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.384832E+10 | 0.605003E+10 | 0.231040E+11 | 0.00 | 0.119983E+11 | 0.80 | 0.00 | 0.396728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.211265E+12 | 0.00 | 0.214804E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.173534E+12 | 0.00 | 0.194027E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.147636E+12 | 0.00 | 0.215222E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.608848E+11 | 0.00 | 0.207681E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.851880E+10 | 0.00 | 0.212817E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.210535E+09 | 0.00 | 0.198248E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.213530E+09 | 0.00 | 0.197007E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.243769E+10 | 0.00 | 0.193265E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.245536E+11 | 0.00 | 0.186839E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.943802E+11 | 0.00 | 0.196942E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.197722E+12 | 0.00 | 0.197210E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.221243E+12 | 0.00 | 0.211374E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.114260E+13 | 0.00 | 0.242544E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.210535E+09 | 0.00 | 0.186839E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.221243E+12 | 0.00 | 0.215222E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2217.54 | 02-JAN-10:09 | 2625.88 | 01-JAN-00:10 | 14269.29 | 01-JAN-11:09 | 0.00 | 5123.93 | 30-JAN-05:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 2217.54 | 01-FEB-10:09 | 2625.88 | 01-FEB-00:10 | 14269.29 | 01-FEB-11:09 | 0.00 | 5123.93 | 01-FEB-10:09 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 2217.54 | 01-MAR-10:09 | 2625.88 | 01-MAR-00:10 | 14269.29 | 01-MAR-11:09 | 0.00 | 5123.93 | 06-MAR-08:39 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 2217.54 | 01-APR-16:10 | 2625.88 | 01-APR-00:10 | 14269.29 | 01-APR-10:09 | 0.00 | 5123.93 | 04-APR-12:00 | 0.00 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 2217.54 | 01-MAY-09:09 | 2625.88 | 01-MAY-00:10 | 14269.29 | 01-MAY-10:09 | 0.00 | 5123.93 | 02-MAY-08:20 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 2217.54 | 01-JUN-09:09 | 2625.88 | 01-JUN-00:10 | 14269.29 | 01-JUN-10:09 | 0.00 | 5123.93 | 01-JUN-05:49 | 0.00 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 2217.54 | 01-JUL-16:10 | 2625.88 | 01-JUL-00:10 | 14269.29 | 01-JUL-10:09 | 0.00 | 5123.93 | 05-JUL-07:00 | 0.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 2217.54 | 01-AUG-09:09 | 2625.88 | 01-AUG-00:10 | 14269.29 | 01-AUG-10:09 | 0.00 | 5123.93 | 05-AUG-18:19 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 2217.54 | 01-SEP-09:09 | 2625.88 | 01-SEP-00:10 | 14269.29 | 01-SEP-10:09 | 0.00 | 5123.93 | 23-SEP-10:30 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 2217.54 | 02-OCT-09:09 | 2625.88 | 01-OCT-00:10 | 14269.29 | 01-OCT-10:09 | 0.00 | 5123.93 | 12-OCT-23:19 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 2217.54 | 01-NOV-09:09 | 2625.88 | 01-NOV-00:10 | 14269.29 | 01-NOV-10:09 | 0.00 | 5123.93 | 01-NOV-09:00 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 2217.54 | 01-DEC-10:09 | 2625.88 | 01-DEC-00:10 | 14269.29 | 01-DEC-11:09 | 0.00 | 5123.93 | 23-DEC-10:00 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2217.54 | 2625.88 | 14269.29 | 0.00 | 5123.93 | 0.00 | 0.00 | ||||||
Maximum of Months | 2217.54 | 2625.88 | 14269.29 | 0.00 | 5123.93 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 133.55 | 21-APR-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4270.78 | 31-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9419.98 | 30-JUN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10190.27 | 29-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7641.64 | 11-AUG-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.52 | 12-SEP-03:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 125.03 | 06-OCT-03:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10190.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 28064.60 | 02-JAN-11:09 | 2217.54 | 14269.29 | 2625.88 | 0.00 | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25446.94 | 09-FEB-11:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25448.50 | 22-MAR-10:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25449.40 | 28-APR-10:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25676.35 | 31-MAY-16:10 | 2217.54 | 12919.68 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 4270.78 | 0.00 |
June | 31028.64 | 30-JUN-11:00 | 2217.54 | 13369.55 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 9131.28 | 0.00 |
July | 31347.88 | 22-JUL-10:20 | 1971.15 | 14269.29 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 6076.51 | 0.00 |
August | 28829.54 | 11-AUG-16:10 | 2217.54 | 12919.68 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 7415.88 | 0.00 |
September | 25467.92 | 01-SEP-10:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25456.31 | 02-OCT-10:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25439.68 | 02-NOV-10:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28065.03 | 26-DEC-11:20 | 2217.54 | 14269.29 | 2625.88 | 0.00 | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 25439.68 | 1971.15 | 12919.68 | 0.00 | 0.00 | 5123.93 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31347.88 | 2217.54 | 14269.29 | 2625.88 | 0.00 | 5123.93 | 0.00 | 0.00 | 9131.28 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 158791.97 | 12-JAN-07:10 | 0.00 | 29766.80 | 15-JAN-13:30 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 150096.53 | 27-FEB-07:10 | 0.00 | 29766.62 | 05-FEB-13:30 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 131270.75 | 01-MAR-07:10 | 0.00 | 29766.79 | 16-MAR-12:00 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 105432.51 | 03-APR-06:10 | 0.00 | 29767.03 | 02-APR-12:20 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 38314.81 | 27-MAY-06:00 | 0.00 | 29647.48 | 02-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 9688.40 | 02-JUN-05:10 | 0.00 | 28994.53 | 01-JUN-12:30 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 8474.70 | 05-JUL-06:10 | 0.00 | 27861.89 | 01-JUL-12:00 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 39776.59 | 31-AUG-06:10 | 0.00 | 26998.45 | 03-AUG-12:00 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 55103.36 | 30-SEP-06:10 | 0.00 | 26802.10 | 29-SEP-12:20 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 105714.70 | 22-OCT-06:10 | 0.00 | 27790.57 | 31-OCT-12:00 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 137114.59 | 30-NOV-20:10 | 0.00 | 28517.49 | 30-NOV-13:20 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 145081.15 | 15-DEC-07:00 | 0.00 | 29766.57 | 31-DEC-13:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 8474.70 | 0.00 | 26802.10 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 158791.97 | 0.00 | 29767.03 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.67 | 17.66 | 15.83 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
February | 57.50 | 17.47 | 1.00 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
March | 45.17 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
April | 16.33 | 19.62 | 0.17 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
May | 1.83 | 20.29 | 0.17 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.60 | 0.00 | 24.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.61 | 0.00 | 24.61 |
August | 0.33 | 20.53 | 0.00 | 20.53 | 2.00 | 24.11 | 0.00 | 24.11 |
September | 4.50 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
October | 16.67 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
November | 48.83 | 18.16 | 0.17 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
December | 70.00 | 17.53 | 3.83 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
Annual Sum or Average | 338.83 | 18.00 | 21.17 | 18.02 | 9.67 | 18.19 | 0.00 | 18.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 | 0.00 | 17.52 |
Maximum of Months | 77.67 | 20.53 | 15.83 | 20.53 | 4.83 | 24.61 | 0.00 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.74 | 0.00 | 26.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.33 | 0.00 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 28.46 | 0.00 | 28.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 28.83 | 0.00 | 28.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 28.46 | 0.00 | 28.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.07 | 0.00 | 27.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.82 | 0.00 | 26.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 64.33 | 28.32 | 0.00 | 28.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 28.83 | 0.00 | 28.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.75 | 610.00 | 20.75 | 610.00 | 20.75 |
February | 551.00 | 20.83 | 543.83 | 20.83 | 543.83 | 20.83 |
March | 612.00 | 20.84 | 491.33 | 20.81 | 491.33 | 20.80 |
April | 541.33 | 20.97 | 231.33 | 20.93 | 211.67 | 20.84 |
May | 351.33 | 21.46 | 177.50 | 22.06 | 28.67 | 21.96 |
June | 135.67 | 22.05 | 394.83 | 23.43 | 0.00 | 23.43 |
July | 106.17 | 21.88 | 469.83 | 23.53 | 1.00 | 23.53 |
August | 210.50 | 21.71 | 361.83 | 23.05 | 6.33 | 23.02 |
September | 505.83 | 21.16 | 117.17 | 21.26 | 70.50 | 21.16 |
October | 608.83 | 20.89 | 396.33 | 20.83 | 396.33 | 20.81 |
November | 591.00 | 20.83 | 591.00 | 20.83 | 591.00 | 20.83 |
December | 609.00 | 20.82 | 609.00 | 20.82 | 609.00 | 20.82 |
Annual Sum or Average | 5432.67 | 21.00 | 4994.00 | 21.32 | 3559.67 | 21.18 |
Minimum of Months | 106.17 | 20.75 | 117.17 | 20.75 | 0.00 | 20.75 |
Maximum of Months | 612.00 | 22.05 | 610.00 | 23.53 | 610.00 | 23.53 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.72 | 610.00 | 18.72 | 610.00 | 18.72 |
February | 551.00 | 18.72 | 548.17 | 18.72 | 548.17 | 18.72 |
March | 612.00 | 18.72 | 581.50 | 18.72 | 581.50 | 18.72 |
April | 585.83 | 18.99 | 365.17 | 18.85 | 365.17 | 18.79 |
May | 425.50 | 20.10 | 224.33 | 20.98 | 97.67 | 20.85 |
June | 365.33 | 24.25 | 431.83 | 24.80 | 246.17 | 25.09 |
July | 421.00 | 24.83 | 493.50 | 25.07 | 336.50 | 25.30 |
August | 407.50 | 23.22 | 401.00 | 24.01 | 230.33 | 24.37 |
September | 509.83 | 19.28 | 136.33 | 19.39 | 95.50 | 19.23 |
October | 610.00 | 18.81 | 363.00 | 18.74 | 363.00 | 18.71 |
November | 591.00 | 18.72 | 591.00 | 18.72 | 591.00 | 18.72 |
December | 609.00 | 18.72 | 608.67 | 18.72 | 608.67 | 18.72 |
Annual Sum or Average | 6298.00 | 19.91 | 5354.50 | 20.18 | 4673.67 | 20.12 |
Minimum of Months | 365.33 | 18.72 | 136.33 | 18.72 | 95.50 | 18.71 |
Maximum of Months | 612.00 | 24.83 | 610.00 | 25.07 | 610.00 | 25.30 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.74574 | 11.19047 | -1.0215 | 27.76973 |
February | 551.00000 | 20.83433 | 12.45728 | -0.9300 | 24.20589 |
March | 612.00000 | 20.83982 | 13.74728 | -0.7542 | 18.49593 |
April | 590.00000 | 21.18961 | 18.64793 | -0.4115 | 11.74596 |
May | 611.00000 | 22.45850 | 26.22430 | -0.9308 | 28.57797 |
June | 592.00000 | 23.45576 | 38.30056 | -0.4175 | 11.68589 |
July | 609.00000 | 23.52062 | 46.73675 | -0.3176 | 10.39537 |
August | 612.00000 | 23.10062 | 42.73373 | -0.5340 | 15.84510 |
September | 590.00000 | 21.53278 | 33.91494 | -1.3223 | 43.87657 |
October | 610.00000 | 20.89561 | 21.76739 | -0.6311 | 14.82489 |
November | 591.00000 | 20.83366 | 10.36502 | -0.9520 | 24.82053 |
December | 609.00000 | 20.82311 | 10.23016 | -1.0240 | 27.69338 |
Annual Sum or Average | 7187.00000 | 21.69259 | 23.94077 | -0.7691 | 21.62214 |
Minimum of Months | 551.00000 | 20.74574 | 10.23016 | -1.3223 | 10.39537 |
Maximum of Months | 612.00000 | 23.52062 | 46.73675 | -0.3176 | 43.87657 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.72247 | 15.66612 | -0.8875 | 22.19155 |
February | 551.00000 | 18.72280 | 17.43958 | -0.8817 | 22.07176 |
March | 612.00000 | 18.72393 | 19.21635 | -0.8289 | 20.21840 |
April | 590.00000 | 19.01992 | 25.02384 | -0.6534 | 15.68834 |
May | 611.00000 | 21.33512 | 31.51013 | -1.0592 | 37.44639 |
June | 592.00000 | 24.10019 | 40.29985 | -0.0542 | 14.25266 |
July | 609.00000 | 24.42168 | 47.19008 | 0.13105 | 14.65567 |
August | 612.00000 | 23.30993 | 44.86588 | -0.2453 | 19.66954 |
September | 590.00000 | 19.80910 | 39.82119 | -1.4678 | 51.09684 |
October | 610.00000 | 18.81464 | 27.29973 | -0.6708 | 15.41836 |
November | 591.00000 | 18.72290 | 14.92226 | -0.8489 | 20.77473 |
December | 609.00000 | 18.72183 | 14.46045 | -0.8850 | 22.07977 |
Annual Sum or Average | 7187.00000 | 20.38270 | 28.21340 | -0.6937 | 22.94216 |
Minimum of Months | 551.00000 | 18.72183 | 14.46045 | -1.4678 | 14.25266 |
Maximum of Months | 612.00000 | 24.42168 | 47.19008 | 0.13105 | 51.09684 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 |
May | 0.512285E+09 | 0.158107E+09 | 47.69 | 0.512251E+09 | 33976.83 | 0.00 | 0.69 | 31-MAY-16:05 | 0.00 | 01-MAY-00:01 | 9972.69 | 31-MAY-16:05 | 9972.69 | 31-MAY-16:05 | 225.89 | 31-MAY-03:30 | 2816.26 | 31-MAY-16:05 | 0.00 | 01-MAY-00:01 |
June | 0.498761E+10 | 0.141672E+10 | 217.08 | 0.485334E+10 | 0.134269E+09 | 0.00 | 1.00 | 04-JUN-02:61 | 0.00 | 01-JUN-00:01 | 31215.33 | 04-JUN-02:61 | 27752.34 | 04-JUN-02:61 | 11099.49 | 30-JUN-02:62 | 8122.82 | 04-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.839815E+10 | 0.231515E+10 | 261.56 | 0.799072E+10 | 0.407430E+09 | 0.00 | 1.00 | 07-JUL-02:61 | 0.00 | 01-JUL-00:01 | 31215.33 | 20-JUL-02:61 | 28846.49 | 13-JUL-02:61 | 13522.30 | 15-JUL-02:61 | 8122.82 | 07-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.385230E+10 | 0.109763E+10 | 154.47 | 0.370193E+10 | 0.150370E+09 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 31215.33 | 01-AUG-02:61 | 28328.43 | 11-AUG-02:61 | 11708.31 | 01-AUG-02:61 | 8122.82 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.177503E+11 | 0.498761E+10 | 680.81 | 0.170582E+11 | 0.692104E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.839815E+10 | 0.231515E+10 | 261.56 | 0.799072E+10 | 0.407430E+09 | 0.00 | 1.00 | 0.00 | 31215.33 | 28846.49 | 13522.30 | 8122.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 461484.12 | 152851.36 | 0.31 | 341721.42 | 119762.70 | 0.00 | 0.07 | 28-APR-03:40 | 0.00 | 01-APR-00:01 | 631.01 | 28-APR-03:40 | 463.70 | 28-APR-03:40 | 167.31 | 28-APR-03:40 | 208.16 | 28-APR-03:40 | 0.00 | 01-APR-00:01 |
May | 0.113993E+09 | 35493349.51 | 22.74 | 0.112625E+09 | 1367549.07 | 0.00 | 1.00 | 14-MAY-02:61 | 0.00 | 01-MAY-00:01 | 21891.99 | 14-MAY-02:61 | 19067.67 | 31-MAY-02:61 | 2864.39 | 14-MAY-02:61 | 5696.71 | 14-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.308096E+10 | 0.863422E+09 | 176.56 | 0.298576E+10 | 95195097.73 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 21891.99 | 20-JUN-04:01 | 18623.44 | 04-JUN-02:61 | 9856.23 | 28-JUN-02:61 | 5696.71 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.603713E+10 | 0.165213E+10 | 240.70 | 0.572649E+10 | 0.310632E+09 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 21891.99 | 28-JUL-02:61 | 18645.05 | 13-JUL-02:11 | 12102.46 | 16-JUL-02:61 | 5696.71 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.237986E+10 | 0.682098E+09 | 141.62 | 0.222887E+10 | 0.150991E+09 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 21891.99 | 02-AUG-02:61 | 18245.89 | 11-AUG-02:61 | 11733.18 | 13-AUG-02:11 | 5696.71 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 5240230.89 | 1711199.80 | 3.42 | 3412719.60 | 1827511.29 | 0.00 | 0.30 | 01-SEP-03:05 | 0.00 | 01-SEP-00:01 | 2745.51 | 01-SEP-03:05 | 1837.35 | 19-SEP-03:05 | 1193.47 | 01-SEP-03:05 | 857.77 | 01-SEP-03:05 | 0.00 | 01-SEP-00:01 |
October | 639373.34 | 209025.95 | 0.31 | 488865.15 | 150508.19 | 0.00 | 0.17 | 06-OCT-03:10 | 0.00 | 01-OCT-00:01 | 1553.02 | 06-OCT-03:10 | 1388.83 | 06-OCT-03:10 | 352.81 | 20-OCT-03:58 | 500.13 | 06-OCT-03:10 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.116183E+11 | 0.323521E+10 | 585.67 | 0.110580E+11 | 0.560284E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.603713E+10 | 0.165213E+10 | 240.70 | 0.572649E+10 | 0.310632E+09 | 0.00 | 1.00 | 0.00 | 21891.99 | 19067.67 | 12102.46 | 5696.71 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.65 | 8.02 | 17.63 | 0.34 | 1111.94 | 0.00 | 0.00 | 0.00 |
February | 141.98 | 67.65 | 74.33 | 46.54 | 943.67 | 0.00 | 0.00 | 0.00 |
March | 405.78 | 205.61 | 200.17 | 290.87 | 706.83 | 0.00 | 0.00 | 0.00 |
April | 557.97 | 282.54 | 275.43 | 454.10 | 395.74 | 0.00 | 0.00 | 0.00 |
May | 810.94 | 457.02 | 353.92 | 844.66 | 193.71 | 0.00 | 0.00 | 0.00 |
June | 745.61 | 347.67 | 397.94 | 803.03 | 103.72 | 0.00 | 0.00 | 0.00 |
July | 708.38 | 343.40 | 364.98 | 793.88 | 117.06 | 0.00 | 0.00 | 0.00 |
August | 561.21 | 273.28 | 287.93 | 583.55 | 179.58 | 0.00 | 0.00 | 0.00 |
September | 347.00 | 152.03 | 194.97 | 285.02 | 327.84 | 0.00 | 0.00 | 0.00 |
October | 183.10 | 73.43 | 109.66 | 102.41 | 615.86 | 0.00 | 0.00 | 0.00 |
November | 38.85 | 13.50 | 25.35 | 0.77 | 1094.28 | 0.00 | 0.00 | 0.00 |
December | 5.54 | 1.31 | 4.23 | 0.00 | 1188.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 379.11 | 186.28 | 192.84 | 352.54 | 579.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.54 | 1.31 | 4.23 | 0.00 | 103.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.94 | 457.02 | 397.94 | 844.66 | 1188.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.35 | 155.39 | 79.96 | 93.74 | 2062.36 | 0.00 | 0.00 | 0.00 |
February | 809.12 | 563.61 | 245.51 | 565.55 | 1650.31 | 0.00 | 0.00 | 0.00 |
March | 1387.14 | 940.91 | 446.23 | 1219.48 | 1269.93 | 0.00 | 0.00 | 0.00 |
April | 1689.46 | 1050.94 | 638.52 | 1763.73 | 826.48 | 0.00 | 0.00 | 0.00 |
May | 1391.29 | 719.95 | 671.34 | 1505.79 | 454.14 | 0.00 | 0.00 | 0.00 |
June | 1270.04 | 519.34 | 750.70 | 1406.40 | 268.15 | 0.00 | 0.00 | 0.00 |
July | 1223.93 | 532.06 | 691.87 | 1409.04 | 278.65 | 0.00 | 0.00 | 0.00 |
August | 1268.65 | 698.89 | 569.76 | 1432.74 | 396.56 | 0.00 | 0.00 | 0.00 |
September | 1026.58 | 618.57 | 408.01 | 1023.47 | 648.32 | 0.00 | 0.00 | 0.00 |
October | 740.32 | 470.35 | 269.97 | 585.25 | 1108.78 | 0.00 | 0.00 | 0.00 |
November | 397.59 | 278.10 | 119.49 | 187.12 | 1941.66 | 0.00 | 0.00 | 0.00 |
December | 70.63 | 49.88 | 20.75 | 4.81 | 2296.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 958.91 | 548.99 | 409.92 | 934.34 | 1097.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.63 | 49.88 | 20.75 | 4.81 | 268.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1689.46 | 1050.94 | 750.70 | 1763.73 | 2296.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.50 | 2.38 | 11.12 | 0.00 | 1125.80 | 0.00 | 0.00 | 0.00 |
February | 79.75 | 27.62 | 52.12 | 5.10 | 982.87 | 0.00 | 0.00 | 0.00 |
March | 239.72 | 102.98 | 136.74 | 100.33 | 742.55 | 0.00 | 0.00 | 0.00 |
April | 569.68 | 295.48 | 274.20 | 489.10 | 416.88 | 0.00 | 0.00 | 0.00 |
May | 553.88 | 252.51 | 301.37 | 510.61 | 208.59 | 0.00 | 0.00 | 0.00 |
June | 606.87 | 258.98 | 347.89 | 628.35 | 123.08 | 0.00 | 0.00 | 0.00 |
July | 507.72 | 192.23 | 315.49 | 530.76 | 131.21 | 0.00 | 0.00 | 0.00 |
August | 417.32 | 176.86 | 240.46 | 398.72 | 192.21 | 0.00 | 0.00 | 0.00 |
September | 252.44 | 105.73 | 146.71 | 171.75 | 342.56 | 0.00 | 0.00 | 0.00 |
October | 98.72 | 29.59 | 69.13 | 21.93 | 649.90 | 0.00 | 0.00 | 0.00 |
November | 39.44 | 14.26 | 25.18 | 1.14 | 1089.05 | 0.00 | 0.00 | 0.00 |
December | 3.54 | 0.37 | 3.18 | 0.00 | 1190.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 282.61 | 121.84 | 160.77 | 239.14 | 597.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.54 | 0.37 | 3.18 | 0.00 | 123.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 606.87 | 295.48 | 347.89 | 628.35 | 1190.24 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68706527.39 | 21474602.13 | 47231925.27 | 922122.18 | 0.297821E+10 |
February | 0.343487E+09 | 0.163659E+09 | 0.179828E+09 | 0.112585E+09 | 0.228293E+10 |
March | 0.108684E+10 | 0.550705E+09 | 0.536133E+09 | 0.779068E+09 | 0.189316E+10 |
April | 0.144625E+10 | 0.732334E+09 | 0.713917E+09 | 0.117704E+10 | 0.102576E+10 |
May | 0.217202E+10 | 0.122408E+10 | 0.947940E+09 | 0.226233E+10 | 0.518825E+09 |
June | 0.193261E+10 | 0.901158E+09 | 0.103146E+10 | 0.208146E+10 | 0.268851E+09 |
July | 0.189733E+10 | 0.919769E+09 | 0.977560E+09 | 0.212633E+10 | 0.313531E+09 |
August | 0.150313E+10 | 0.731941E+09 | 0.771192E+09 | 0.156298E+10 | 0.481000E+09 |
September | 0.899420E+09 | 0.394071E+09 | 0.505350E+09 | 0.738777E+09 | 0.849772E+09 |
October | 0.490404E+09 | 0.196679E+09 | 0.293725E+09 | 0.274291E+09 | 0.164953E+10 |
November | 0.100701E+09 | 35003801.74 | 65697248.24 | 2000491.36 | 0.283636E+10 |
December | 14851087.53 | 3511347.21 | 11339740.32 | 0.00 | 0.318284E+10 |
Annual Sum or Average | 0.119558E+11 | 0.587439E+10 | 0.608137E+10 | 0.111178E+11 | 0.182808E+11 |
Minimum of Months | 14851087.53 | 3511347.21 | 11339740.32 | 0.00 | 0.268851E+09 |
Maximum of Months | 0.217202E+10 | 0.122408E+10 | 0.103146E+10 | 0.226233E+10 | 0.318284E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.630370E+09 | 0.416192E+09 | 0.214178E+09 | 0.251082E+09 | 0.552382E+10 |
February | 0.195743E+10 | 0.136349E+10 | 0.593936E+09 | 0.136818E+10 | 0.399243E+10 |
March | 0.371532E+10 | 0.252013E+10 | 0.119519E+10 | 0.326626E+10 | 0.340137E+10 |
April | 0.437909E+10 | 0.272405E+10 | 0.165504E+10 | 0.457159E+10 | 0.214222E+10 |
May | 0.372643E+10 | 0.192831E+10 | 0.179811E+10 | 0.403310E+10 | 0.121638E+10 |
June | 0.329194E+10 | 0.134612E+10 | 0.194582E+10 | 0.364538E+10 | 0.695042E+09 |
July | 0.327818E+10 | 0.142507E+10 | 0.185311E+10 | 0.377398E+10 | 0.746326E+09 |
August | 0.339795E+10 | 0.187191E+10 | 0.152604E+10 | 0.383745E+10 | 0.106216E+10 |
September | 0.266091E+10 | 0.160334E+10 | 0.105757E+10 | 0.265282E+10 | 0.168045E+10 |
October | 0.198288E+10 | 0.125979E+10 | 0.723091E+09 | 0.156753E+10 | 0.296977E+10 |
November | 0.103054E+10 | 0.720827E+09 | 0.309718E+09 | 0.485007E+09 | 0.503279E+10 |
December | 0.189167E+09 | 0.133601E+09 | 55566744.02 | 12873300.24 | 0.615223E+10 |
Annual Sum or Average | 0.302402E+11 | 0.173128E+11 | 0.129274E+11 | 0.294653E+11 | 0.346150E+11 |
Minimum of Months | 0.189167E+09 | 0.133601E+09 | 55566744.02 | 12873300.24 | 0.695042E+09 |
Maximum of Months | 0.437909E+10 | 0.272405E+10 | 0.194582E+10 | 0.457159E+10 | 0.615223E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36167158.46 | 6381576.27 | 29785582.19 | 0.00 | 0.301534E+10 |
February | 0.192922E+09 | 66829737.35 | 0.126092E+09 | 12338679.43 | 0.237777E+10 |
March | 0.642069E+09 | 0.275831E+09 | 0.366238E+09 | 0.268727E+09 | 0.198886E+10 |
April | 0.147662E+10 | 0.765891E+09 | 0.710727E+09 | 0.126774E+10 | 0.108055E+10 |
May | 0.148351E+10 | 0.676320E+09 | 0.807191E+09 | 0.136761E+10 | 0.558676E+09 |
June | 0.157300E+10 | 0.671264E+09 | 0.901738E+09 | 0.162868E+10 | 0.319014E+09 |
July | 0.135989E+10 | 0.514869E+09 | 0.845018E+09 | 0.142160E+10 | 0.351433E+09 |
August | 0.111774E+10 | 0.473694E+09 | 0.644045E+09 | 0.106793E+10 | 0.514813E+09 |
September | 0.654325E+09 | 0.274054E+09 | 0.380271E+09 | 0.445188E+09 | 0.887906E+09 |
October | 0.264419E+09 | 79253670.74 | 0.185165E+09 | 58739198.19 | 0.174068E+10 |
November | 0.102238E+09 | 36970156.76 | 65267623.87 | 2960154.06 | 0.282283E+10 |
December | 9490633.07 | 980116.40 | 8510516.67 | 0.00 | 0.318793E+10 |
Annual Sum or Average | 0.891239E+10 | 0.384234E+10 | 0.507005E+10 | 0.754150E+10 | 0.188458E+11 |
Minimum of Months | 9490633.07 | 980116.40 | 8510516.67 | 0.00 | 0.319014E+09 |
Maximum of Months | 0.157300E+10 | 0.765891E+09 | 0.901738E+09 | 0.162868E+10 | 0.318793E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 32.10 | 4238.10 | 274.51 | 165.79 | 108.72 | 0.00 | 0.00 |
February | 425.33 | 3384.99 | 1030.85 | 658.89 | 371.96 | 0.00 | 0.00 |
March | 1403.38 | 2512.00 | 2032.64 | 1249.50 | 783.14 | 0.00 | 0.00 |
April | 2538.88 | 1471.04 | 2817.11 | 1628.96 | 1188.15 | 0.00 | 0.00 |
May | 2744.15 | 739.54 | 2756.11 | 1429.48 | 1326.63 | 0.00 | 0.00 |
June | 2767.08 | 424.25 | 2622.51 | 1125.98 | 1496.53 | 0.00 | 0.00 |
July | 2683.59 | 476.82 | 2440.04 | 1067.69 | 1372.34 | 0.00 | 0.00 |
August | 2348.96 | 702.31 | 2247.17 | 1149.02 | 1098.15 | 0.00 | 0.00 |
September | 1402.22 | 1240.70 | 1626.02 | 876.34 | 749.69 | 0.00 | 0.00 |
October | 601.90 | 2266.85 | 1022.14 | 573.37 | 448.77 | 0.00 | 0.00 |
November | 84.18 | 4020.14 | 475.88 | 305.86 | 170.02 | 0.00 | 0.00 |
December | 0.00 | 4670.74 | 79.72 | 51.56 | 28.16 | 0.00 | 0.00 |
Annual Sum or Average | 1424.43 | 2173.32 | 1620.64 | 857.10 | 763.53 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 424.25 | 79.72 | 51.56 | 28.16 | 0.00 | 0.00 |
Maximum of Months | 2767.08 | 4670.74 | 2817.11 | 1628.96 | 1496.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 85966433.33 | 0.113513E+11 | 0.735244E+09 | 0.444049E+09 | 0.291195E+09 | 0.00 | 0.00 |
February | 0.102895E+10 | 0.818896E+10 | 0.249383E+10 | 0.159398E+10 | 0.899857E+09 | 0.00 | 0.00 |
March | 0.375882E+10 | 0.672815E+10 | 0.544423E+10 | 0.334667E+10 | 0.209756E+10 | 0.00 | 0.00 |
April | 0.658077E+10 | 0.381294E+10 | 0.730196E+10 | 0.422227E+10 | 0.307969E+10 | 0.00 | 0.00 |
May | 0.734993E+10 | 0.198077E+10 | 0.738196E+10 | 0.382872E+10 | 0.355324E+10 | 0.00 | 0.00 |
June | 0.717226E+10 | 0.109965E+10 | 0.679756E+10 | 0.291854E+10 | 0.387902E+10 | 0.00 | 0.00 |
July | 0.718774E+10 | 0.127713E+10 | 0.653540E+10 | 0.285971E+10 | 0.367569E+10 | 0.00 | 0.00 |
August | 0.629145E+10 | 0.188106E+10 | 0.601882E+10 | 0.307754E+10 | 0.294128E+10 | 0.00 | 0.00 |
September | 0.363455E+10 | 0.321588E+10 | 0.421465E+10 | 0.227147E+10 | 0.194319E+10 | 0.00 | 0.00 |
October | 0.161212E+10 | 0.607153E+10 | 0.273770E+10 | 0.153572E+10 | 0.120198E+10 | 0.00 | 0.00 |
November | 0.218186E+09 | 0.104202E+11 | 0.123348E+10 | 0.792801E+09 | 0.440683E+09 | 0.00 | 0.00 |
December | 0.00 | 0.125101E+11 | 0.213509E+09 | 0.138092E+09 | 75417001.01 | 0.00 | 0.00 |
Annual Sum or Average | 0.449207E+11 | 0.685377E+11 | 0.511083E+11 | 0.270296E+11 | 0.240788E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.109965E+10 | 0.213509E+09 | 0.138092E+09 | 75417001.01 | 0.00 | 0.00 |
Maximum of Months | 0.734993E+10 | 0.125101E+11 | 0.738196E+10 | 0.422227E+10 | 0.387902E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.173572E+11 | -0.165296E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -827591357.0 | 60.05 | 0.00 | 0.00 |
February | 0.156781E+11 | -0.149301E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -747983348.3 | 60.05 | 0.00 | 0.00 |
March | 0.173908E+11 | -0.165639E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -826953828.4 | 60.05 | 0.00 | 0.00 |
April | 0.167814E+11 | -0.159900E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -791431680.8 | 60.05 | 0.00 | 0.00 |
May | 0.171965E+11 | -0.164254E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -771158251.1 | 60.05 | 0.00 | 0.00 |
June | 0.160192E+11 | -0.153253E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -693869889.9 | 60.05 | 0.00 | 0.00 |
July | 0.159190E+11 | -0.152081E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -710925335.4 | 60.05 | 0.00 | 0.00 |
August | 0.156164E+11 | -0.148858E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -730639581.4 | 60.05 | 0.00 | 0.00 |
September | 0.150974E+11 | -0.143257E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -771776110.7 | 60.05 | 0.00 | 0.00 |
October | 0.159136E+11 | -0.150939E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -819686555.1 | 60.05 | 0.00 | 0.00 |
November | 0.159353E+11 | -0.151363E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -799022948.9 | 60.05 | 0.00 | 0.00 |
December | 0.170800E+11 | -0.162529E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -827166467.9 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.195985E+12 | -0.186667E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.931821E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.150974E+11 | -0.165639E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -827591357.0 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.173908E+11 | -0.143257E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -693869889.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.787543E+11 | 54416.36 | 01-JAN-01:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.644218E+11 | 54416.36 | 01-FEB-01:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.536057E+11 | 54416.36 | 01-MAR-01:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213666E+11 | 54416.36 | 01-APR-02:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.300534E+10 | 38271.77 | 28-MAY-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97973121.58 | 11423.96 | 24-JUN-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117771E+09 | 10104.57 | 13-JUL-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.883034E+09 | 13723.76 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.929144E+10 | 41739.48 | 28-SEP-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.349372E+11 | 54416.36 | 11-OCT-02:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.726243E+11 | 54416.36 | 01-NOV-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.826605E+11 | 54416.36 | 01-DEC-01:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421766E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 97973121.58 | 10104.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.826605E+11 | 54416.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.894114E+11 | 83306.50 | 13-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737080E+11 | 75892.48 | 28-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638985E+11 | 75345.35 | 03-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.270850E+11 | 61066.33 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.377399E+10 | 22577.38 | 06-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 69794272.66 | 6366.10 | 02-JUN-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 52555570.34 | 6658.23 | 06-JUL-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105711E+10 | 22935.63 | 30-AUG-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102544E+11 | 35903.18 | 30-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.401867E+11 | 57816.08 | 22-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.847516E+11 | 77981.52 | 28-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.934493E+11 | 91830.52 | 15-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.487698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 52555570.34 | 6366.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.934493E+11 | 91830.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.512285E+09 | 0.512251E+09 | 9972.69 | 31-MAY-16:05 | 9972.69 | 0.00 |
June | 0.00 | 0.00 | 0.498761E+10 | 0.485334E+10 | 31215.33 | 04-JUN-02:61 | 27752.34 | 0.00 |
July | 0.00 | 0.00 | 0.839815E+10 | 0.799072E+10 | 31215.33 | 20-JUL-02:61 | 18849.31 | 0.00 |
August | 0.00 | 0.00 | 0.385230E+10 | 0.370193E+10 | 31215.33 | 01-AUG-02:61 | 19507.02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177503E+11 | 0.170582E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.839815E+10 | 0.799072E+10 | 31215.33 | 27752.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 461484.12 | 341721.42 | 631.01 | 28-APR-03:40 | 463.70 | 0.00 |
May | 0.00 | 0.00 | 0.113993E+09 | 0.112625E+09 | 21891.99 | 14-MAY-02:61 | 19027.61 | 0.00 |
June | 0.00 | 0.00 | 0.308096E+10 | 0.298576E+10 | 21891.99 | 20-JUN-04:01 | 15545.08 | 0.00 |
July | 0.00 | 0.00 | 0.603713E+10 | 0.572649E+10 | 21891.99 | 28-JUL-02:61 | 12155.45 | 0.00 |
August | 0.00 | 0.00 | 0.237986E+10 | 0.222887E+10 | 21891.99 | 02-AUG-02:61 | 12149.38 | 0.00 |
September | 0.00 | 0.00 | 5240230.89 | 3412719.60 | 2745.51 | 01-SEP-03:05 | 1552.03 | 0.00 |
October | 0.00 | 0.00 | 639373.34 | 488865.15 | 1553.02 | 06-OCT-03:10 | 1388.83 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116183E+11 | 0.110580E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.603713E+10 | 0.572649E+10 | 21891.99 | 19027.61 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 6161.65 | 23752.41 | 03-JAN-13:30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6161.77 | 23752.60 | 05-FEB-13:35 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 6174.41 | 23752.66 | 19-MAR-12:23 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6159.36 | 23752.75 | 04-APR-12:50 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6122.15 | 23752.63 | 05-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5899.47 | 23130.78 | 01-JUN-12:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5663.26 | 22178.48 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5542.02 | 21445.85 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5511.22 | 21311.80 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5620.29 | 21942.19 | 31-OCT-12:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5825.91 | 22849.37 | 30-NOV-13:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 6057.13 | 23752.34 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 5906.79 | ||||
Minimum of Months | 0.00 | 0.00 | 5511.22 | 21311.80 | ||
Maximum of Months | 0.00 | 0.00 | 6174.41 | 23752.75 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.701777E+10 | 1.27 | 2895.98 | 01-JAN-00:09 | 1.39 |
February | 0.632882E+10 | 1.27 | 2895.98 | 07-FEB-05:05 | 1.39 |
March | 0.687251E+10 | 1.24 | 2895.98 | 02-MAR-10:10 | 1.39 |
April | 0.642815E+10 | 1.22 | 2895.98 | 01-APR-04:03 | 1.39 |
May | 0.647240E+10 | 1.17 | 2895.98 | 14-MAY-14:40 | 1.38 |
June | 0.627174E+10 | 1.18 | 2895.98 | 02-JUN-07:03 | 1.38 |
July | 0.648583E+10 | 1.19 | 2895.98 | 06-JUL-05:50 | 1.38 |
August | 0.647947E+10 | 1.18 | 2895.98 | 05-AUG-18:20 | 1.38 |
September | 0.628068E+10 | 1.18 | 2895.98 | 02-SEP-09:17 | 1.38 |
October | 0.664692E+10 | 1.23 | 2895.98 | 04-OCT-11:10 | 1.39 |
November | 0.669817E+10 | 1.25 | 2895.98 | 27-NOV-05:04 | 1.39 |
December | 0.702553E+10 | 1.27 | 2895.98 | 23-DEC-11:00 | 1.39 |
Annual Sum or Average | 0.790080E+11 | 1.22 | |||
Minimum of Months | 0.627174E+10 | 1.17 | 2895.98 | 1.38 | |
Maximum of Months | 0.702553E+10 | 1.27 | 2895.98 | 1.39 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.497280E+10 | 1.16 | 2227.96 | 01-JAN-00:10 | 1.39 |
February | 0.449156E+10 | 1.16 | 2227.96 | 01-FEB-00:03 | 1.39 |
March | 0.497280E+10 | 1.16 | 2227.96 | 01-MAR-00:01 | 1.39 |
April | 0.481277E+10 | 1.16 | 2227.96 | 01-APR-04:03 | 1.39 |
May | 0.498728E+10 | 1.20 | 2227.96 | 01-MAY-04:15 | 1.39 |
June | 0.488155E+10 | 1.24 | 2227.96 | 01-JUN-04:19 | 1.38 |
July | 0.505693E+10 | 1.25 | 2227.96 | 03-JUL-04:01 | 1.38 |
August | 0.504318E+10 | 1.24 | 2227.96 | 01-AUG-14:45 | 1.37 |
September | 0.482297E+10 | 1.19 | 2227.96 | 01-SEP-04:08 | 1.38 |
October | 0.497353E+10 | 1.16 | 2227.96 | 01-OCT-05:00 | 1.39 |
November | 0.481239E+10 | 1.16 | 2227.96 | 01-NOV-04:04 | 1.39 |
December | 0.497280E+10 | 1.16 | 2227.96 | 01-DEC-00:06 | 1.39 |
Annual Sum or Average | 0.588005E+11 | 1.19 | |||
Minimum of Months | 0.449156E+10 | 1.16 | 2227.96 | 1.37 | |
Maximum of Months | 0.505693E+10 | 1.25 | 2227.96 | 1.39 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.37 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.05 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.05 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.05 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:03 | 0.00 | 0.00 | 46.19 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:05 | 0.00 | 0.00 | 51.27 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 51.62 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:05 | 0.00 | 0.00 | 51.89 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 52.00 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 50.42 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 51.70 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.36 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 46.19 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 52.00 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 34.25 | 34.25 | 6161.65 | 23752.41 | 03-JAN-13:30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.05 | 51.05 | 6161.77 | 23752.60 | 05-FEB-13:35 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.05 | 51.05 | 6174.41 | 23752.66 | 19-MAR-12:23 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.05 | 51.05 | 6159.36 | 23752.75 | 04-APR-12:50 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 34.25 | 34.25 | 6122.15 | 23752.63 | 05-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.26 | 51.26 | 5899.47 | 23130.78 | 01-JUN-12:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.61 | 51.61 | 5663.26 | 22178.48 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 51.88 | 51.88 | 5542.02 | 21445.85 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.00 | 52.00 | 5511.22 | 21311.80 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 36.80 | 36.80 | 5620.29 | 21942.19 | 31-OCT-12:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.71 | 51.71 | 5825.91 | 22849.37 | 30-NOV-13:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.37 | 51.37 | 6057.13 | 23752.34 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 5906.79 | ||||||
Minimum of Months | 0.00 | 0.00 | 34.25 | 34.25 | 5511.22 | 21311.80 | ||
Maximum of Months | 0.00 | 0.00 | 52.00 | 52.00 | 6174.41 | 23752.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.701777E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.632882E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.687251E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.642815E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.663051E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.768846E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.880098E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.757710E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.628068E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.664692E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.669817E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.702553E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.839956E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.628068E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.880098E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.497280E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.449156E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.497280E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.481292E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.502277E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.574497E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.670905E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.572528E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.482469E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.497374E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.481239E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.497280E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.620358E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.449156E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.670905E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.701777E+10 | 0.00 | 0.787543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.632882E+10 | 0.00 | 0.644218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687251E+10 | 0.00 | 0.536057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.642815E+10 | 0.00 | 0.213666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.647240E+10 | 0.512285E+09 | 0.300534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.627174E+10 | 0.498761E+10 | 97973121.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.648583E+10 | 0.839815E+10 | 0.117771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647947E+10 | 0.385230E+10 | 0.883034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.628068E+10 | 0.00 | 0.929144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.664692E+10 | 0.00 | 0.349372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669817E+10 | 0.00 | 0.726243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.702553E+10 | 0.00 | 0.826605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790080E+11 | 0.177503E+11 | 0.421766E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.627174E+10 | 0.00 | 97973121.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.702553E+10 | 0.839815E+10 | 0.826605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.497280E+10 | 0.00 | 0.894114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.449156E+10 | 0.00 | 0.737080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.497280E+10 | 0.00 | 0.638985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.481277E+10 | 461484.12 | 0.270850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.498728E+10 | 0.113993E+09 | 0.377399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.488155E+10 | 0.308096E+10 | 69794272.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.505693E+10 | 0.603713E+10 | 52555570.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.504318E+10 | 0.237986E+10 | 0.105711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482297E+10 | 5240230.89 | 0.102544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.497353E+10 | 639373.34 | 0.401867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.481239E+10 | 0.00 | 0.847516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.497280E+10 | 0.00 | 0.934493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.588005E+11 | 0.116183E+11 | 0.487698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.449156E+10 | 0.00 | 52555570.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.505693E+10 | 0.603713E+10 | 0.934493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.701777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.632882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.642815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.647240E+10 | 0.00 | 0.00 | 0.00 | 0.158107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.627174E+10 | 0.00 | 0.00 | 0.00 | 0.141672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.648583E+10 | 0.00 | 0.00 | 0.00 | 0.231515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647947E+10 | 0.00 | 0.00 | 0.00 | 0.109763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.628068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.664692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.702553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790080E+11 | 0.00 | 0.00 | 0.00 | 0.498761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.627174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.702553E+10 | 0.00 | 0.00 | 0.00 | 0.231515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.497280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.449156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.497280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.481277E+10 | 0.00 | 0.00 | 0.00 | 152851.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.498728E+10 | 0.00 | 0.00 | 0.00 | 35493349.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.488155E+10 | 0.00 | 0.00 | 0.00 | 0.863422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.505693E+10 | 0.00 | 0.00 | 0.00 | 0.165213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.504318E+10 | 0.00 | 0.00 | 0.00 | 0.682098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482297E+10 | 0.00 | 0.00 | 0.00 | 1711199.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.497353E+10 | 0.00 | 0.00 | 0.00 | 209025.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.481239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.497280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.588005E+11 | 0.00 | 0.00 | 0.00 | 0.323521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.449156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.505693E+10 | 0.00 | 0.00 | 0.00 | 0.165213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535088E+11 | 0.00 | 0.00 | 3.81 |
February | 0.111622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456273E+11 | 0.00 | 0.00 | 3.78 |
March | 0.193606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415974E+11 | 0.00 | 0.00 | 3.72 |
April | 0.621256E+10 | 0.00 | 0.00 | 1348462.08 | 0.00 | 0.192672E+11 | 0.133471E+10 | 0.00 | 3.73 |
May | 0.775826E+10 | 0.00 | 0.00 | 13006640.86 | 0.00 | 0.231001E+10 | 0.790663E+10 | 0.00 | 4.92 |
June | 0.362591E+10 | 5805810.62 | 0.00 | 31670914.77 | 0.00 | 712829.11 | 0.119344E+11 | 0.00 | 6.99 |
July | 0.335928E+10 | 42498720.72 | 0.00 | 37793782.85 | 0.00 | 34138699.15 | 0.107232E+11 | 0.00 | 6.91 |
August | 0.566063E+10 | 0.00 | 0.00 | 25792917.57 | 0.00 | 0.588431E+09 | 0.102770E+11 | 0.00 | 6.22 |
September | 0.785106E+10 | 0.00 | 0.00 | 2486443.71 | 0.00 | 0.898411E+10 | 0.224280E+10 | 0.00 | 3.81 |
October | 0.299429E+10 | 0.00 | 0.00 | 13369.12 | 0.00 | 0.290400E+11 | 35122007.61 | 0.00 | 3.67 |
November | 0.156472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497409E+11 | 0.00 | 0.00 | 3.75 |
December | 0.117551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553068E+11 | 0.00 | 0.00 | 3.81 |
Annual Sum or Average | 0.444333E+11 | 48304531.34 | 0.00 | 0.112113E+09 | 0.00 | 0.306006E+12 | 0.444538E+11 | 0.00 | 4.60 |
Minimum of Months | 0.111622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 712829.11 | 0.00 | 0.00 | 3.67 |
Maximum of Months | 0.785106E+10 | 42498720.72 | 0.00 | 37793782.85 | 0.00 | 0.553068E+11 | 0.119344E+11 | 0.00 | 6.99 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183450E+09 | 0.00 | 0.00 | 9.79 |
February | 0.101371E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190463E+09 | 0.00 | 0.00 | 9.68 |
March | 0.963271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163866E+09 | 0.00 | 0.00 | 9.68 |
April | 0.611674E+11 | 0.00 | 0.00 | 98227.52 | 0.00 | 61585939.49 | 0.389483E+09 | 0.00 | 9.75 |
May | 0.313981E+11 | 0.00 | 0.00 | 9425219.44 | 0.00 | 6177559.27 | 0.939028E+10 | 0.00 | 9.92 |
June | 0.122724E+11 | 0.00 | 0.00 | 39640653.27 | 0.00 | 0.00 | 0.210724E+11 | 0.00 | 10.55 |
July | 0.111633E+11 | 1167220.78 | 0.00 | 49676870.64 | 0.00 | 0.00 | 0.207192E+11 | 0.00 | 10.67 |
August | 0.177742E+11 | 0.00 | 0.00 | 33786072.45 | 0.00 | 0.00 | 0.193785E+11 | 0.00 | 10.38 |
September | 0.434561E+11 | 0.00 | 0.00 | 1327563.15 | 0.00 | 10642320.96 | 0.305639E+10 | 0.00 | 9.80 |
October | 0.752957E+11 | 0.00 | 0.00 | 96898.19 | 0.00 | 42995252.57 | 43654163.03 | 0.00 | 9.74 |
November | 0.115842E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169925E+09 | 0.00 | 0.00 | 9.72 |
December | 0.124018E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209323E+09 | 0.00 | 0.00 | 9.74 |
Annual Sum or Average | 0.809929E+12 | 1167220.78 | 0.00 | 0.134052E+09 | 0.00 | 0.103843E+10 | 0.740500E+11 | 0.00 | 9.95 |
Minimum of Months | 0.111633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 |
Maximum of Months | 0.124018E+12 | 1167220.78 | 0.00 | 49676870.64 | 0.00 | 0.209323E+09 | 0.210724E+11 | 0.00 | 10.67 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.304435E+10 | 0.316455E+11 | 0.214732E+12 | 0.00 | 0.567083E+11 |
February | 0.356294E+10 | 0.267274E+11 | 0.181948E+12 | 0.00 | 0.485530E+11 |
March | 0.225239E+11 | 0.258460E+11 | 0.172111E+12 | 0.00 | 0.454427E+11 |
April | 0.434352E+11 | 0.165398E+11 | 0.110489E+12 | 0.230166E+09 | 0.274833E+11 |
May | 0.567699E+11 | 0.106324E+11 | 0.753318E+11 | 0.346659E+10 | 0.186000E+11 |
June | 0.593812E+11 | 0.711420E+10 | 0.592296E+11 | 0.748167E+10 | 0.279956E+11 |
July | 0.535313E+11 | 0.628230E+10 | 0.574593E+11 | 0.673865E+10 | 0.372088E+11 |
August | 0.388125E+11 | 0.797954E+10 | 0.673139E+11 | 0.606160E+10 | 0.258501E+11 |
September | 0.166771E+11 | 0.119286E+11 | 0.869803E+11 | 0.619901E+09 | 0.174931E+11 |
October | 0.582717E+10 | 0.198814E+11 | 0.134933E+12 | 0.00 | 0.308547E+11 |
November | -482715171.1 | 0.302625E+11 | 0.207088E+12 | 0.00 | 0.539893E+11 |
December | -0.411100E+10 | 0.330316E+11 | 0.222655E+12 | 0.00 | 0.588868E+11 |
Annual Sum or Average | 0.292883E+12 | 0.227871E+12 | 0.159027E+13 | 0.245986E+11 | 0.449066E+12 |
Minimum of Months | -0.411100E+10 | 0.628230E+10 | 0.574593E+11 | 0.00 | 0.174931E+11 |
Maximum of Months | 0.593812E+11 | 0.330316E+11 | 0.222655E+12 | 0.748167E+10 | 0.588868E+11 |