Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20

Tabular Output Report in Format: HTML

Building: RestaurantFastFood

Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930

Simulation Timestamp: 2024-07-03 12:20:39


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1411.30 6074.22 6074.22
Net Site Energy 1411.30 6074.22 6074.22
Total Source Energy 2679.79 11533.78 11533.78
Net Source Energy 2679.79 11533.78 11533.78


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 232.34
Net Conditioned Building Area 232.34
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 188.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 15.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 41.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 272.03 477.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 141.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 193.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 775.38
Refrigeration 36.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 552.06 859.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 775.38
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 188.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 15.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 44.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 41.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment Cooking 233.46 477.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 15.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 23.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 141.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 775.38
  Water Heater 0.00 193.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 7.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 10.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 17.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 188.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 15.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 44.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 41.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 272.03 477.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 141.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 193.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 775.38
Refrigeration Unassigned 36.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 370.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 676.51 1644.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.34
Other 1329.36 2053.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 2376.05 3698.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.34


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 370.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 676.51 1644.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.34
Other 1329.36 2053.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 2376.05 3698.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.34


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 552.059 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 552.059 100.00
     
Total On-Site and Utility Electric Sources 552.059 100.00
Total Electricity End Uses 552.059 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 775.38 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 775.38 100.00
Total Water End Uses 775.38 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2683.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| DINING | KITCHEN | ATTIC |

ZoneHeatingSummaryMonthly

| DINING | KITCHEN | ATTIC |

ZoneElectricSummaryMonthly

| DINING | KITCHEN |

SpaceGainsMonthly

| DINING | KITCHEN | ATTIC |

PeakSpaceGainsMonthly

| DINING | KITCHEN | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| DINING | KITCHEN | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| DINING | KITCHEN | ATTIC |

ComfortReportSimple55Monthly

| DINING | KITCHEN | ATTIC |

OccupantComfortDataSummaryMonthly

| DINING | KITCHEN |

DXReportMonthly

| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |

WindowReportMonthly

| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| DINING | KITCHEN | ATTIC |

WindowEnergyZoneSummaryMonthly

| DINING | KITCHEN | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| DINING | KITCHEN | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC_1:1 | PSZ-AC_2:2 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC_1:1 | PSZ-AC_2:2 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC_1:1 | PSZ-AC_2:2 |

MechanicalVentilationLoadsMonthly

| DINING | KITCHEN |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
RunPeriod RUNPERIOD 1
Weather File Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Latitude [deg] 47.47
Longitude [deg] -122.3
Elevation [m] 122.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 185.89 46.47 46.47 46.47 46.47
Above Ground Wall Area [m2] 185.89 46.47 46.47 46.47 46.47
Window Opening Area [m2] 63.19 0.00 15.80 31.59 15.80
Gross Window-Wall Ratio [%] 33.99 0.00 33.99 67.98 33.99
Above Ground Window-Wall Ratio [%] 33.99 0.00 33.99 67.98 33.99


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 185.89 46.47 46.47 46.47 46.47
Above Ground Wall Area [m2] 185.89 46.47 46.47 46.47 46.47
Window Opening Area [m2] 63.19 0.00 15.80 31.59 15.80
Gross Window-Wall Ratio [%] 33.99 0.00 33.99 67.98 33.99
Above Ground Window-Wall Ratio [%] 33.99 0.00 33.99 67.98 33.99


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 258.86
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
DINING 116.17 Yes Yes 354.18 1.00 92.94 0.00 63.19 63.19 9.2637 1.33 116.7869
KITCHEN 116.17 Yes Yes 354.18 1.00 92.94 0.00 0.00 0.00 11.9458 18.52 1072.7618
ATTIC 232.34 No No 262.34 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 232.34     708.37   185.89 0.00 63.19 63.19 10.6047 2.48 594.7744
Conditioned Total 232.34     708.37   185.89 0.00 63.19 63.19 10.6047 2.48 594.7744
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 232.34     262.34   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
DINING 116.17 Yes Yes 1.00 DINING GENERAL DINING 9.2637 1.33 116.7869  
KITCHEN 116.17 Yes Yes 1.00 KITCHEN GENERAL KITCHEN 11.9458 18.52 1072.7618  
ATTIC 232.34 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 232.34             10.6047 1.24 594.7744  
Conditioned Total 232.34             10.6047 1.24 594.7744  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 232.34             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 232.34 232.34 0.00 232.34 10.6047 2.48 594.7744
Total 232.34 232.34 0.00 232.34      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-AUG-10:20 07-JAN-11:09 - - - - - - - - - - 01-JUL-12:39
Heating 0.00 37407.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 8550.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2217.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14269.29 26660.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5338.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 16223.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 3920.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 34296.71 80291.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 37407.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 8550.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2217.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment Cooking 13046.29 26660.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 493.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 730.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 5338.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 16223.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 3294.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 626.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 204.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 48.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 141.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 130.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 861.52 517.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 449.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 209.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 116.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1748.37 931.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 878.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 207.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 611.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 561.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3707.96 2226.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1935.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 903.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 502.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 7524.96 4008.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 878.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 207.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 611.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 561.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3707.96 2226.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1935.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 903.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 502.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 7524.96 4008.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
DINING DIRECT AIR 1.84
KITCHEN DIRECT AIR 1.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC_1:1 1.84 1.84 1.84 1.84 1.84 1.84 1.00 1.00 1.84
PSZ-AC_2:2 1.37 1.37 1.37 1.37 1.37 1.37 1.00 1.000000 1.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC_1:1_OA_CONTROLLER 1.84 0.416056
PSZ-AC_2:2_OA_CONTROLLER 1.37 1.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ-AC_1:1_ADDAQ FAN 1.84 3060.55
PSZ-AC_2:2_ADDAQ FAN 1.37 2277.58
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC_1:1_UNITARY_PACKAGE_DX 1.84 1.84 1.84 1.84 34822.17 37187.81 32.22 1.00
PSZ-AC_2:2_UNITARY_PACKAGE_DX 1.37 1.37 1.37 1.37 25267.42 49736.27 30.00 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ-AC_1:1 COOLING COIL 1.84 0.920745 1.23 34822.17 17411.08 0.798840 0.798840
PSZ-AC_2:2 COOLING COIL 1.37 0.685195 0.913593 25267.42 12633.71 0.800080 0.800080
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC_1:1 HEATING COIL 37187.81
PSZ-AC_2:2 HEATING COIL 49736.27
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000096 0.011518
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000096 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000096
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
DINING_WALL_EAST DINING_WALL_EAST_WINDOW |
DINING_WALL_SOUTH DINING_WALL_SOUTH_WINDOW |
DINING_WALL_WEST DINING_WALL_WEST_WINDOW |
KITCHEN_WALL_EAST KITCHEN_WALL_EAST_DOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 11.40 8.10 5.40 4.50 5.80 8.30 10.90 13.00 15.60 17.70 18.80 15.10


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 47.47 -122.32 -8.00 122.00 99868 1.1870


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 11.22 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 RestaurantFastFood 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 3 24 4


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 DINING 0.0 0.00 0.00 0.00 7.62 3.81 1.52 1 1 1 0.00 15.24 0.00 7.62 0.00 3.05 3.05 354.18 TARP TARP 116.17 92.94 29.76 63.19 6 3 0 Yes
2 KITCHEN 0.0 0.00 0.00 0.00 7.62 11.43 1.52 1 1 1 0.00 15.24 7.62 15.24 0.00 3.05 3.05 354.18 TARP TARP 116.17 92.94 90.99 0.00 6 1 0 Yes
3 ATTIC 0.0 0.00 0.00 3.05 7.62 7.62 3.64 1 1 1 0.00 15.24 0.00 15.24 3.05 5.59 1.27 262.34 TARP TARP 232.34 0.00 0.00 0.00 6 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 DINING 116.17 87.5 1.327 0.754 9.264 116.787 0.000 0.000 0.000 0.000 126.051 No
2 KITCHEN 116.17 6.3 18.518 5.400E-002 11.946 281.409 791.353 0.000 0.000 0.000 1084.708 No
3 ATTIC 232.34 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DINING BLDG_OCC_SCH DINING 116.17 87.5 87.5 0.754 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 88 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 KITCHEN BLDG_OCC_SCH KITCHEN 116.17 6.3 6.3 5.400E-002 18.518 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 DINING_LIGHTS LTG_SCH_DINING DINING 116.17 87.5 1076.175 9.264 12.293 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1076.175
2 KITCHEN_LIGHTS LTG_SCH_KITCHEN KITCHEN 116.17 6.3 1387.759 11.946 221.217 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1387.759


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 DINING_MISCELEC_EQUIP BLDG_EQUIP_SCH DINING 116.17 87.5 13567.311 116.787 154.976 0.250 0.300 0.000 0.450 Cooking 0.000 3934.520
2 KITCHEN_MISCELEC_EQUIP BLDG_EQUIP_SCH KITCHEN 116.17 6.3 31468.723 270.882 5016.295 0.250 0.300 0.300 0.150 Cooking 0.000 9125.930
3 KITCHEN_REACH-IN-FREEZER ALWAYS_ON KITCHEN 116.17 6.3 493.000 4.244 78.587 0.000 0.250 0.000 0.750 ReachInFreezer 493.000 493.000
4 KITCHEN_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN 116.17 6.3 730.000 6.284 116.366 0.000 0.250 0.000 0.750 ReachInRefrigerator 730.000 730.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 KITCHEN_MISCGAS_EQUIP FF_GAS_EQUIP_SCH KITCHEN 116.17 6.3 91932.601 791.353 14654.584 0.100 0.200 0.700 0.000 Cooking 0.000 26660.454


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 9.815 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 ATTICROOFDECK 6 2 4 0.167 4.706 0.900 0.900 0.700 0.700 VeryRough
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 17 2 4 0.167 0.3836 0.900 0.900 0.700 0.700 MediumSmooth
6 NONRES_ROOF_FLOOR 20 2 4 0.167 0.3836 0.900 0.900 0.700 0.700 MediumSmooth
7 NONRES_EXT_WALL_GRD 23 4 7 0.167 0.7871 0.900 0.900 0.700 0.700 Smooth
8 DINING_FLOOR_FFACTOR 42 2 7 0.167 0.3496 0.000 0.900 0.000 0.700 MediumRough
9 KITCHEN_FLOOR_FFACTOR 43 2 7 0.167 0.3496 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.1019
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 F12 ASPHALT SHINGLES 0.0032 0.040 1120.000 1260.000 0.8000E-01
4 G02 16MM PLYWOOD 0.0159 0.120 544.000 1210.000 0.1325
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 2.508
8 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
9 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
10 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 2.508
11 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
12 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.037
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.784
16 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
17 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.784
18 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 9.8148919 9.8148919 9.8148919  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 4 0.12552254E-09 0.24226224E-10 0.35972174E-10 -0.14154396E-16
14 3 -0.27173896E-03 0.71777257E-04 -0.16206070E-03 0.11981077E-09
15 2 0.48258702 0.15872105 0.47241503 -0.16497355E-03
16 1 -7.8004821 2.4804491 -9.1443147 0.17387321
17 0 11.206599 1.2491899 12.560494  
18 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
19 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
20 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
21 1 -12.650482 3.3590720 -12.650482 0.19281313
22 0 16.907513 1.4507143 16.907513  
23 4 -0.36752283E-16 0.36650618E-15 -0.17323971E-14 0.96945811E-16
24 3 -0.69118654E-08 0.27160578E-06 -0.56853996E-04 0.15386634E-12
25 2 0.11860501E-03 0.58949329E-02 1.1525899 -0.75054507E-04
26 1 -0.13685427 0.15202565 -17.175506 0.33646671
27 0 0.39128804 0.96631513E-01 16.277526  
28 4 -0.17323971E-14 0.36650618E-15 -0.36752283E-16 0.96945811E-16
29 3 -0.56853996E-04 0.27160578E-06 -0.69118654E-08 0.15386634E-12
30 2 1.1525899 0.58949329E-02 0.11860501E-03 -0.75054507E-04
31 1 -17.175506 0.15202565 -0.13685427 0.33646671
32 0 16.277526 0.96631513E-01 0.39128804  
33 7 -0.29735092E-12 0.24575595E-14 -0.94456721E-13 0.15324278E-15
34 6 0.28546880E-07 0.22114619E-09 0.65405332E-08 -0.13451374E-12
35 5 -0.18947583E-03 0.18937623E-05 -0.97466953E-04 0.64660656E-08
36 4 0.29140875 0.92215111E-03 0.99417931E-01 -0.33466744E-04
37 3 -7.2517161 0.28579858E-01 -2.3345767 0.28937395E-01
38 2 40.822959 0.10163225 15.247323 -0.33280368
39 1 -80.508872 0.45869584E-01 -29.125752 1.0778326
40 0 46.824339 0.92288667E-03 16.291614  
41 7 -0.11889135E-08 -0.13101661E-15 0.72805024E-14 -0.91252007E-16
42 6 0.97710136E-05 0.67347286E-08 0.31779875E-02 -0.26659623E-04
43 5 -0.70792317E-03 0.39963827E-05 -0.22304912 0.19501884E-02
44 4 0.16314426E-01 0.18199987E-03 4.8182940 -0.45156824E-01
45 3 -0.14334616 0.14483103E-02 -37.957847 0.39795111
46 2 0.50909124 0.24102133E-02 116.36021 -1.4162842
47 1 -0.73485211 0.73528917E-03 -143.83447 2.0478426
48 0 0.35828816 0.17591693E-04 60.838472  
49 7 -0.11889135E-08 -0.13101661E-15 0.72805024E-14 -0.91252007E-16
50 6 0.97710136E-05 0.67347286E-08 0.31779875E-02 -0.26659623E-04
51 5 -0.70792317E-03 0.39963827E-05 -0.22304912 0.19501884E-02
52 4 0.16314426E-01 0.18199987E-03 4.8182940 -0.45156824E-01
53 3 -0.14334616 0.14483103E-02 -37.957847 0.39795111
54 2 0.50909124 0.24102133E-02 116.36021 -1.4162842
55 1 -0.73485211 0.73528917E-03 -143.83447 2.0478426
56 0 0.35828816 0.17591693E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39 38 1 VerySmooth 3.241 3.241 1.000 0.391    
2 NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 39 1 VerySmooth 3.241 3.241 1.000 0.391    
3 NONRESWINDOW_U_0.57_SHGC_EAST_0.39 40 1 VerySmooth 3.241 3.241 1.000 0.391    
4 NONRESWINDOW_U_0.57_SHGC_WEST_0.39 41 1 VerySmooth 3.241 3.241 1.000 0.391    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SOUTH SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
2 NONRES WINDOW GLAZING LAYER NORTH SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
3 NONRES WINDOW GLAZING LAYER EAST SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
4 NONRES WINDOW GLAZING LAYER WEST SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.510
2 RACK2 1 0 Zone Air-Cooled 7.290


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 21.722 0.5184


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 DINING_WALL_EAST 0 73.85 54.29 5.59 0 3.05 30.49 10.16 0.68 4 No No
2 DINING_WALL_EAST_WINDOW 0 73.85 54.29 5.59 0 3.05 30.49 10.16 0.68 5 No No
3 DINING_WALL_SOUTH 0 46.47 36.58 3.05 0 3.05 30.49 10.16 0.68 4 No No
4 DINING_WALL_SOUTH_WINDOW 0 46.47 36.58 3.05 0 3.05 30.49 10.16 0.68 5 No No
5 DINING_WALL_WEST 0 73.85 42.08 5.59 0 3.05 30.49 10.16 0.68 4 No No
6 DINING_WALL_WEST_WINDOW 0 73.85 42.08 5.59 0 3.05 30.49 10.16 0.68 5 No No
7 DINING_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.68 0 No No
8 DINING_FLOOR 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.68 0 No No
9 DINING_CEILING 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.68 0 No No
10 DINING_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.68 0 No No
11 KITCHEN_WALL_NORTH 0 46.47 49.21 3.05 0 3.05 30.49 10.16 0.00 0 No No
12 KITCHEN_WALL_EAST 0 73.85 54.29 5.59 0 3.05 30.49 10.16 0.00 0 No No
13 KITCHEN_WALL_EAST_DOOR 0 73.85 54.29 5.59 0 3.05 30.49 10.16 0.00 0 No No
14 KITCHEN_WALL_WEST 0 73.85 42.08 5.59 0 3.05 30.49 10.16 0.00 0 No No
15 DINING_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.00 0 No No
16 KITCHEN_FLOOR 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.00 0 No No
17 KITCHEN_CEILING 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.00 0 No No
18 KITCHEN_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.00 0 No No
19 ATTIC-FLOOR-DINNING 0 0.00 0.00 0.00 0 1.27 0.00 15.24 -999.00 0 No No
20 ATTIC-FLOOR-KITCHEN 0 0.00 0.00 0.00 0 1.27 0.00 15.24 -999.00 0 No No
21 WEST-ROOF 0 73.85 42.08 5.59 0 1.27 0.00 15.24 -999.00 0 No No
22 EAST-ROOF 0 73.85 54.29 5.59 0 1.27 0.00 15.24 -999.00 0 No No
23 NORTH-ROOF 0 204.09 60.97 2.54 0 1.27 0.00 15.24 -999.00 0 No No
24 SOUTH-ROOF 0 204.09 60.97 2.54 0 1.27 0.00 15.24 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 DINING_INFILTRATION INFIL_SCH_PNNL DINING 116.17 87.5 5.294E-002 4.557E-004 5.696E-004 0.538 0.000 0.000 0.224 0.000
2 DINING_DOOR_INFILTRATION VESTIBULE_DOOR_INFIL_SCH DINING 116.17 87.5 0.584 5.025E-003 6.281E-003 5.934 1.000 0.000 0.000 0.000
3 KITCHEN_INFILTRATION INFIL_SCH_PNNL KITCHEN 116.17 6.3 5.294E-002 4.557E-004 5.579E-004 0.538 0.000 0.000 0.224 0.000
4 ATTIC_INFILTRATION ALWAYS_ON ATTIC 232.34 0.0 7.290E-002 3.138E-004 2.816E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 DINING Mixing/Well-Stirred
2 KITCHEN Mixing/Well-Stirred
3 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2500
2 Zone DINING 1.2500
3 Zone KITCHEN 1.2500


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.1500
2 Zone DINING 1.1500
3 Zone KITCHEN 1.1500


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 DINING Cooling 21536.94718 24767.48926 1.60130 1.84149 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 29.40000 8.82150E-003 116.17148 87.54444 0.41606 0.00000
2 DINING Heating 8154.93603 10193.67004 0.59458 0.74323 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 07:00:00 -4.20000 2.69032E-003 116.17148 87.54444 0.41606 0.00000
3 KITCHEN Cooling 16025.59548 18429.43481 1.19164 1.37039 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 28.46400 8.82000E-003 116.17148 6.27330 1.14133 0.00000
4 KITCHEN Heating 737.70737 922.13421 5.48461E-002 1.14133 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 -4.20000 2.69032E-003 116.17148 6.27330 1.14133 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC_1:1 Cooling Sensible 27123.49 1.84149 1.84149 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 PSZ-AC_1:1 Heating Sensible 22460.79 0.74323 0.74323 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 07:00:00
3 PSZ-AC_2:2 Cooling Sensible 21352.94 1.37039 1.37039 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 PSZ-AC_2:2 Heating Sensible 46557.64 1.14133 1.14133 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat DINING DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.84149
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat KITCHEN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.37039
3 AirLoopHVAC PSZ-AC_1:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.84149
4 AirLoopHVAC PSZ-AC_1:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.84149
5 AirLoopHVAC PSZ-AC_1:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.84149
6 AirLoopHVAC PSZ-AC_1:1 Adjusted Heating Design Air Flow Rate [m3/s] 1.84149
7 AirLoopHVAC PSZ-AC_1:1 Adjusted Cooling Design Air Flow Rate [m3/s] 1.84149
8 AirLoopHVAC PSZ-AC_1:1 Adjusted Main Design Air Flow Rate [m3/s] 1.84149
9 AirLoopHVAC PSZ-AC_1:1 User Heating Air Flow Ratio [] 1.00000
10 AirLoopHVAC PSZ-AC_1:1 Calculated Heating Air Flow Ratio [] 1.00000
11 AirLoopHVAC PSZ-AC_2:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.37039
12 AirLoopHVAC PSZ-AC_2:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.37039
13 AirLoopHVAC PSZ-AC_2:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.37039
14 AirLoopHVAC PSZ-AC_2:2 Adjusted Heating Design Air Flow Rate [m3/s] 1.37039
15 AirLoopHVAC PSZ-AC_2:2 Adjusted Cooling Design Air Flow Rate [m3/s] 1.37039
16 AirLoopHVAC PSZ-AC_2:2 Adjusted Main Design Air Flow Rate [m3/s] 1.37039
17 AirLoopHVAC PSZ-AC_2:2 User Heating Air Flow Ratio [] 1.00000
18 AirLoopHVAC PSZ-AC_2:2 Calculated Heating Air Flow Ratio [] 1.00000
19 AirLoopHVAC PSZ-AC_1:1 Design Supply Air Flow Rate [m3/s] 1.84149
20 AirLoopHVAC PSZ-AC_2:2 Design Supply Air Flow Rate [m3/s] 1.37039
21 Controller:OutdoorAir PSZ-AC_1:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.84149
22 Controller:OutdoorAir PSZ-AC_1:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.41606
23 Fan:SystemModel PSZ-AC_1:1_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.84149
24 Fan:SystemModel PSZ-AC_1:1_ADDAQ FAN Design Electric Power Consumption [W] 3060.55152
25 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.84149
26 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.84149
27 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.84149
28 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.84149
29 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.84149
30 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.92074
31 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.22766
32 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 34822.17000
33 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 17411.08500
34 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.79884
35 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.79884
36 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 34822.17000
37 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 37187.81428
38 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 32.22000
39 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
40 Coil:Heating:Fuel PSZ-AC_1:1 HEATING COIL Design Size Nominal Capacity [W] 37187.81428
41 Controller:OutdoorAir PSZ-AC_2:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.37039
42 Controller:OutdoorAir PSZ-AC_2:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.14133
43 Fan:SystemModel PSZ-AC_2:2_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.37039
44 Fan:SystemModel PSZ-AC_2:2_ADDAQ FAN Design Electric Power Consumption [W] 2277.58466
45 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.37039
46 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.37039
47 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.37039
48 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.37039
49 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.37039
50 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.68520
51 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.91359
52 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 25267.42000
53 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 12633.71000
54 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80008
55 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80008
56 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 25267.42000
57 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 49736.26594
58 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 30.00000
59 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
60 Coil:Heating:Fuel PSZ-AC_2:2 HEATING COIL Design Size Nominal Capacity [W] 49736.26594
61 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 9.59800E-005
62 PlantLoop SWHSYS1 Plant Loop Volume [m3] 1.15176E-002
63 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 9.59800E-005
64 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 4.10171E-007
65 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 9.59800E-005


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL 33485.8     10.57 10.52  
2 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL 24271.3     10.52 10.47  


Zone Surfaces

Zone Name # Surfaces
1 DINING 10
2 KITCHEN 8
3 ATTIC 6


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 DINING_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   7.44 23.24 7.44 90.00 90.00 7.62 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
2 DINING_WALL_EAST_WINDOW Window DINING_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_EAST_0.39 N/A 3.241 No 15.80 15.80 15.80 90.00 90.00 7.11 2.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
3 DINING_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   14.88 46.47 14.88 180.00 90.00 15.24 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
4 DINING_WALL_SOUTH_WINDOW Window DINING_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 31.59 31.59 31.59 180.00 90.00 14.23 2.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 DINING_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   7.44 23.24 7.44 270.00 90.00 7.62 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
6 DINING_WALL_WEST_WINDOW Window DINING_WALL_WEST Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_WEST_0.39 N/A 3.241 No 15.80 15.80 15.80 270.00 90.00 7.11 2.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
7 DINING_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.47 46.47 46.47 0.00 90.00 15.24 3.05 0.00 DINING_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
8 DINING_FLOOR Floor   CTF - ConductionTransferFunction DINING_FLOOR_FFACTOR 0.350 0.322   116.17 116.17 116.17 0.00 180.00 15.24 7.62 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
9 DINING_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.384 0.358   116.17 116.17 116.17 180.00 0.00 15.24 7.62 0.00 ATTIC-FLOOR-DINNING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 DINING_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   232.34 232.34 232.34 0.00 90.00 232.34 1.00 0.00 DINING_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 KITCHEN_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   46.47 46.47 46.47 0.00 90.00 15.24 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 KITCHEN_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   21.29 23.24 21.29 90.00 90.00 7.62 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
13 KITCHEN_WALL_EAST_DOOR Door KITCHEN_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
14 KITCHEN_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   23.24 23.24 23.24 270.00 90.00 7.62 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
15 DINING_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.47 46.47 46.47 180.00 90.00 15.24 3.05 0.00 DINING_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
16 KITCHEN_FLOOR Floor   CTF - ConductionTransferFunction KITCHEN_FLOOR_FFACTOR 0.350 0.322   116.17 116.17 116.17 0.00 180.00 15.24 7.62 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 KITCHEN_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.384 0.358   116.17 116.17 116.17 180.00 0.00 15.24 7.62 0.00 ATTIC-FLOOR-KITCHEN Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 KITCHEN_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   232.34 232.34 232.34 0.00 90.00 232.34 1.00 0.00 KITCHEN_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 ATTIC-FLOOR-DINNING Floor   CTF - ConductionTransferFunction NONRES_ROOF_FLOOR 0.384 0.351   116.17 116.17 116.17 180.00 180.00 15.24 7.62 0.00 DINING_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
20 ATTIC-FLOOR-KITCHEN Floor   CTF - ConductionTransferFunction NONRES_ROOF_FLOOR 0.384 0.351   116.17 116.17 116.17 0.00 180.00 15.24 7.62 0.00 KITCHEN_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 WEST-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   27.38 27.38 27.38 270.00 45.00 8.43 15.24 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.15 0.85 0.15 0.85 3
22 EAST-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   27.38 27.38 27.38 90.00 45.00 8.43 15.24 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.15 0.85 0.15 0.85 3
23 NORTH-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   102.05 102.05 102.05 0.00 18.44 8.43 15.24 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 2.57E-002 0.97 2.57E-002 0.97 4
24 SOUTH-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   102.05 102.05 102.05 180.00 18.44 8.43 15.24 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 2.57E-002 0.97 2.57E-002 0.97 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 DINING RunPeriod: RUNPERIOD 1 0.1210372397 0.4245020271 Pass Pass 0.1603756510 0.4090594419 Pass Pass
2 KITCHEN RunPeriod: RUNPERIOD 1 0.1367858752 0.5544396348 Pass Pass 3.3502479427E-002 9.4953062837E-002 Pass Pass
3 ATTIC RunPeriod: RUNPERIOD 1 0.1115681536 0.1111610845 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 401.61 117.49 845.55 33.81 292.84 1691.31



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB -4.20 0.00 -4.20 Wetbulb [C] 4.30 20.00
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 29.40 10.40 18.30 Wetbulb [C] 4.20 350.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 22.00 23      
Apr 0.00 0      
May 0.00 0      
Jun 16.00 20      
Jul 0.00 0      
Aug 24.00 18      
Sep 12.00 15      
Oct 61.00 41      
Nov 0.00 0      
Dec 45.00 41      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
DINING_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 23.24 7.44 90.00 90.00 E
DINING_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.704 0.787 46.47 14.88 180.00 90.00 S
DINING_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 23.24 7.44 270.00 90.00 W
DINING_FLOOR DINING_FLOOR_FFACTOR 1.00 0.331 0.350 116.17 116.17 0.00 180.00  
KITCHEN_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.704 0.787 46.47 46.47 0.00 90.00 N
KITCHEN_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 23.24 21.29 90.00 90.00 E
KITCHEN_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 23.24 23.24 270.00 90.00 W
KITCHEN_FLOOR KITCHEN_FLOOR_FFACTOR 1.00 0.331 0.350 116.17 116.17 0.00 180.00  
WEST-ROOF ATTICROOFDECK 0.30 2.858 4.706 27.38 27.38 270.00 45.00  
EAST-ROOF ATTICROOFDECK 0.30 2.858 4.706 27.38 27.38 90.00 45.00  
NORTH-ROOF ATTICROOFDECK 0.30 2.858 4.706 102.05 102.05 0.00 18.44  
SOUTH-ROOF ATTICROOFDECK 0.30 2.858 4.706 102.05 102.05 180.00 18.44  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
DINING_WALL_NORTH INT_WALL 0.30 2.511 6.299 46.47 46.47 0.00 90.00 N
DINING_CEILING NONRES_ROOF 0.30 0.348 0.384 116.17 116.17 180.00 0.00  
DINING_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 46.47 46.47 180.00 90.00 S
KITCHEN_CEILING NONRES_ROOF 0.30 0.348 0.384 116.17 116.17 180.00 0.00  
ATTIC-FLOOR-DINNING NONRES_ROOF_FLOOR 0.30 0.348 0.384 116.17 116.17 180.00 180.00  
ATTIC-FLOOR-KITCHEN NONRES_ROOF_FLOOR 0.30 0.348 0.384 116.17 116.17 0.00 180.00  
DINING_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 232.34   0.00 90.00 N
KITCHEN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 232.34   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
DINING_WALL_EAST_WINDOW NONRESWINDOW_U_0.57_SHGC_EAST_0.39   15.80 0.00 0.00 15.80 15.80 3.241 0.391 0.431             No DINING_WALL_EAST 90.00 90.00 E
DINING_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39   31.59 0.00 0.00 31.59 31.59 3.241 0.391 0.431             No DINING_WALL_SOUTH 180.00 90.00 S
DINING_WALL_WEST_WINDOW NONRESWINDOW_U_0.57_SHGC_WEST_0.39   15.80 0.00 0.00 15.80 15.80 3.241 0.391 0.431             No DINING_WALL_WEST 270.00 90.00 W
Total or Average             63.19 3.241 0.391 0.431                      
North Total or Average             0.00 - - -                      
Non-North Total or Average             63.19 3.241 0.391 0.431                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
KITCHEN_WALL_EAST_DOOR SWINGING DOOR_CON 3.975 9.815 1.95 KITCHEN_WALL_EAST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
DINING_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
DINING_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
DINING_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
DINING_LIGHTS DINING DINING GENERAL 9.2637 116.17 1076.18 LightsWired LTG_SCH_DINING 97.50 168.00 96.93 0.0000 Y 19.58
KITCHEN_LIGHTS KITCHEN KITCHEN GENERAL 11.9458 116.17 1387.76 LightsWired LTG_SCH_KITCHEN 97.50 168.00 96.93 0.0000 Y 25.25
Interior Lighting Total       10.6047 232.34 2463.93               44.83


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS 2625.88 AstronomicalClock -   83.55 83.55 41.18
Exterior Lighting Total 2625.88           41.18



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed   34822.17 27817.34 7004.83 0.80 3.50    
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed   25267.42 20215.96 5051.46 0.80 3.50    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC_1:1 COOLING COIL   33485.8     10.57 10.52  
PSZ-AC_2:2 COOLING COIL   24271.3     10.52 10.47  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC_1:1 HEATING COIL Coil:Heating:Fuel   37187.81 0.80
PSZ-AC_2:2 HEATING COIL Coil:Heating:Fuel   49736.27 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
DINING EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.42 0.00 0.00 1.00 0.00 General    
KITCHEN EXHAUST FAN Fan:ZoneExhaust 0.39 0.00 1.56 0.00 0.00 1.00 0.00 General    
PSZ-AC_1:1_ADDAQ FAN Fan:SystemModel 0.58 966.87 1.84 3060.55 1662.00 1.00 1.23 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 07:00:00
PSZ-AC_2:2_ADDAQ FAN Fan:SystemModel 0.58 966.87 1.37 2277.58 1662.00 1.00 1.28 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000096 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 0.81 21.72 0.52



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
DINING 21536.95 24767.49 213.20 1.601 1.841 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 23.89 23.88 0.00940 29.40 0.00882 0.416 0.00
KITCHEN 16025.60 18429.43 158.64 1.192 1.370 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 26.11 26.10 0.00991 28.46 0.00882 1.141 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
DINING 8154.94 10193.67 87.75 0.595 0.743 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 07:00:00 21.11 21.11 0.00788 -4.20 0.00269 0.416 0.00
KITCHEN 737.71 922.13 7.94 0.055 1.141 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 23:30:00 18.89 18.89 0.00574 -4.20 0.00269 1.141 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC_1:1 1.84 1.84 0.74 0.74 1.8415 1.8415 1.8415 1.0000 1.0000
PSZ-AC_2:2 1.37 1.37 1.14 1.14 1.3704 1.3704 1.3704 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC_1:1 34822.170 27817.342 1.841490 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 17411.08 15276.12 1.227660 25.13 17.28 0.00926965 11.41 11.39 0.00850000 29.40 0.00882150 18.34 33.8902 23.88 0.00940046 50.1638 21536.95 0.00 -999.00 -999.00
PSZ-AC_1:1 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC_1:1 37187.814 37187.814 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 07:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 07:00:00 37187.81 37187.81 1.841490 15.29 11.19 0.00670919 32.22 18.61 0.00800000 -4.20 0.00269032 -4.20 22.5935 21.11 0.00788222 49.9020 8154.94 0.00 -999.00 -999.00
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC_2:2 25267.420 20215.957 1.370390 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 12633.71 11748.85 0.913593 28.06 18.05 0.00900223 13.63 12.31 0.00850000 28.46 0.00882000 18.03 124.9280 26.10 0.00991028 46.2989 16025.60 0.00 -999.00 -999.00
PSZ-AC_2:2 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC_2:2 49736.266 49736.266 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 18:10:00 49736.27 49736.27 1.370390 -0.43 -1.13 0.00323240 30.00 17.88 0.00800000 -4.20 0.00269032 -4.20 83.2853 18.68 0.00593344 43.7938 305.83 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC_1:1 DINING Coincident CoolingDesignCapacity N/A No No unknown No 34822.170 27817.342 1.841490 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.0718 1004.8586 1.1870 PSZ-AC_1:1_ADDAQ FAN Fan:SystemModel 1.841490 2.18583158   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 Sensible 17411.08 15276.12 1.0000 1.45722111 1.227660 25.13 17.28 0.00926965 48865.1 11.41 11.39 0.00850000 32902.4 -999.0 -999.00 -999.00 -999.00 0.000 17411.08 29.40 0.00882150 18.34 0.41605618 33.8902 23.88 0.00940046 23.88 0.00940046 50.1638 21536.95 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_1:1 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC_1:1 DINING Coincident HeatingDesignCapacity N/A Yes No unknown No 37187.814 37187.814 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC_1:1_ADDAQ FAN Fan:SystemModel 1.841490 2.18583158   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 07:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 07:00:00 Sensible 37187.81 37187.81 1.0000 2.18583158 1.841490 15.29 11.19 0.00670919 32333.1 32.22 18.61 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 37187.81 -4.20 0.00269032 -4.20 0.41605618 22.5935 20.98 0.00788222 21.11 0.00788222 49.9020 8154.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC_2:2 KITCHEN Coincident CoolingDesignCapacity N/A No No unknown No 25267.420 20215.957 1.370390 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.5747 1004.8586 1.1870 PSZ-AC_2:2_ADDAQ FAN Fan:SystemModel 1.370390 1.62664031   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 Sensible 12633.71 11748.85 1.0000 1.08442687 0.913593 28.06 18.05 0.00900223 51181.9 13.63 12.31 0.00850000 35167.6 -999.0 -999.00 -999.00 -999.00 0.000 12633.71 28.46 0.00882000 18.03 1.14133354 124.9280 26.06 0.00991028 26.10 0.00991028 46.2989 16025.60 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_2:2 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC_2:2 KITCHEN Coincident HeatingDesignCapacity N/A Yes No unknown No 49736.266 49736.266 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PSZ-AC_2:2_ADDAQ FAN Fan:SystemModel 1.370390 1.62664031   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 18:10:00 Sensible 49736.27 49736.27 1.0000 1.62664031 1.370390 -0.43 -1.13 0.00323240 7651.2 30.00 17.88 0.00800000 50598.9 -999.0 -999.00 -999.00 -999.00 0.000 49736.27 -4.20 0.00269032 -4.20 1.14133354 83.2853 18.37 0.00593344 18.68 0.00593344 43.7938 305.83 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PSZ-AC_1:1_OA_CONTROLLER FixedDryBulb 0.42 1.84 -      
PSZ-AC_2:2_OA_CONTROLLER FixedDryBulb 1.14 1.37 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
DINING 3175.33 4733.50 1107.33
KITCHEN 3642.50 5714.83 2511.00
ATTIC 0.00 0.00 0.00
Facility 3867.67 6102.33 2683.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
DINING 108.83 7.50 0.00 0.00
KITCHEN 0.00 93.50 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 108.83 99.50 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
DINING 36.94 87.54 354.18 5.890 2.732 0.000 0.000
KITCHEN 2.65 6.27 354.18 11.995 0.029 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
DINING 36.94 87.54 354.18 4.106 0.000 0.000 0.000
KITCHEN 2.65 6.27 354.18 11.220 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
DINING PSZ-AC_1:1 36.94 87.54 354.18 116.17 0.4161 0.416
KITCHEN PSZ-AC_2:2 2.65 6.27 354.18 116.17 0.1513 0.092
Total Facility   39.58 93.82 708.37 232.34 0.5673 0.508


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
DINING 15103015.20 0.00 15103015.20 6905727.60 22008742.80 13120747.55 1440.72 5482.18 1837.09 397.66
KITCHEN 30852782.95 0.00 30852782.95 125536.84 30978319.79 35993094.65 1454.84 6453.94 851.22 389.27
Total Facility 45955798.15 0.00 45955798.15 7031264.44 52987062.59 49113842.20 1459.05 6470.17 1842.05 628.95


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
DINING 0.5704 0.0000 0.5704 0.2649 0.8353 0.4161 0.00 5355.40 1831.60
KITCHEN 1.1654 0.0000 1.1654 0.0028 1.1682 1.1413 0.00 6341.24 845.76
Total Facility 1.7358 0.0000 1.7358 0.2677 2.0034 1.5574 0.00 6341.84 1832.20


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC_1:1 21279345.71 0.00 21279345.71 13120747.55 1424.83 2.66 7332.51 397.66
PSZ-AC_2:2 43469939.67 0.00 43469939.67 35993094.65 1449.79 0.30 7309.91 389.27


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC_1:1 0.8037 0.0000 0.8037 0.4161 0.00 0.00 7187.00
PSZ-AC_2:2 1.6420 0.0000 1.6420 1.1413 0.00 0.00 7187.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC_1:1 0.00 1008.91 1100.49 5475.26 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC_2:2 0.00 0.00 906.90 6669.37 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC_1:1 0.0000 1.9461 1.0933 0.5863 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC_2:2 0.0000 0.0000 1.8940 1.6083 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Surfaces by Class

Total Outdoors
Wall 8 6
Floor 4 2
Roof 6 4
Internal Mass 2 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 3 3
Door 1 1
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 2
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 365
Defaulted Fields 263
Fields with Defaults 866
Autosized Fields 39
Autosizable Fields 93
Autocalculated Fields 30
Autocalculatable Fields 60



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 552.06 5920.10 25-MAR-00:10 34296.71 29-AUG-10:20
Electricity:Building 324.80 2625.15 01-JAN-01:10 19780.88 02-JAN-11:10
Electricity:Zone:DINING 89.91 431.44 01-JAN-01:10 4898.81 02-JAN-11:10
Electricity:SpaceType:GENERAL 316.86 2488.87 01-JAN-01:10 16486.83 02-JAN-11:10
InteriorLights:Electricity 44.83 369.59 01-JAN-01:10 2217.54 02-JAN-10:10
InteriorLights:Electricity:Zone:DINING 19.58 161.43 01-JAN-01:10 968.56 02-JAN-10:10
InteriorLights:Electricity:SpaceType:GENERAL 44.83 369.59 01-JAN-01:10 2217.54 02-JAN-10:10
LightsWired:InteriorLights:Electricity 44.83 369.59 01-JAN-01:10 2217.54 02-JAN-10:10
LightsWired:InteriorLights:Electricity:Zone:DINING 19.58 161.43 01-JAN-01:10 968.56 02-JAN-10:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 44.83 369.59 01-JAN-01:10 2217.54 02-JAN-10:10
Electricity:Zone:KITCHEN 234.89 2193.72 01-JAN-01:10 14882.07 02-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN 25.25 208.16 01-JAN-01:10 1248.98 02-JAN-10:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN 25.25 208.16 01-JAN-01:10 1248.98 02-JAN-10:10
InteriorEquipment:Electricity 272.03 2119.28 01-JAN-01:10 14269.29 01-JAN-11:10
InteriorEquipment:Electricity:Zone:DINING 70.33 270.01 01-JAN-01:10 3930.26 01-JAN-11:10
InteriorEquipment:Electricity:SpaceType:GENERAL 272.03 2119.28 01-JAN-01:10 14269.29 01-JAN-11:10
Cooking:InteriorEquipment:Electricity 233.46 896.28 01-JAN-01:10 13046.29 01-JAN-11:10
Cooking:InteriorEquipment:Electricity:Zone:DINING 70.33 270.01 01-JAN-01:10 3930.26 01-JAN-11:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 233.46 896.28 01-JAN-01:10 13046.29 01-JAN-11:10
InteriorEquipment:Electricity:Zone:KITCHEN 201.70 1849.27 01-JAN-01:10 10339.04 01-JAN-11:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN 163.13 626.27 01-JAN-01:10 9116.04 01-JAN-11:10
ReachInFreezer:InteriorEquipment:Electricity 15.55 493.00 01-JAN-00:10 493.00 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN 15.55 493.00 01-JAN-00:10 493.00 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 15.55 493.00 01-JAN-00:10 493.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 23.02 730.00 01-JAN-00:10 730.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN 23.02 730.00 01-JAN-00:10 730.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 23.02 730.00 01-JAN-00:10 730.00 01-JAN-00:10
Refrigeration:Electricity 36.84 594.45 08-JAN-23:30 3931.14 30-AUG-10:10
Refrigeration:Electricity:Zone:KITCHEN 7.94 85.78 01-JAN-23:30 3294.05 02-JAN-11:10
General:Refrigeration:Electricity 7.94 85.78 01-JAN-23:30 3294.05 02-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN 7.94 85.78 01-JAN-23:30 3294.05 02-JAN-11:10
Electricity:Plant 28.90 508.67 11-FEB-23:10 1619.81 25-AUG-03:40
LowTempRefrigeration:Refrigeration:Electricity 10.93 0.00 01-JAN-11:10 982.72 25-AUG-03:40
MedTempRefrigeration:Refrigeration:Electricity 17.96 475.34 12-FEB-01:10 637.09 27-APR-13:50
ElectricityPurchased:Facility 552.06 5920.10 25-MAR-00:10 34296.71 29-AUG-10:20
ElectricityPurchased:Plant 552.06 5920.10 25-MAR-00:10 34296.71 29-AUG-10:20
Cogeneration:ElectricityPurchased 552.06 5920.10 25-MAR-00:10 34296.71 29-AUG-10:20
General:Cogeneration:ElectricityPurchased 552.06 5920.10 25-MAR-00:10 34296.71 29-AUG-10:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 552.06 5920.10 25-MAR-00:10 34296.71 29-AUG-10:20
ElectricityNet:Plant 552.06 5920.10 25-MAR-00:10 34296.71 29-AUG-10:20
Cogeneration:ElectricityNet 552.06 5920.10 25-MAR-00:10 34296.71 29-AUG-10:20
General:Cogeneration:ElectricityNet 552.06 5920.10 25-MAR-00:10 34296.71 29-AUG-10:20
Electricity:HVAC 157.18 0.00 01-JAN-01:10 18262.74 10-AUG-17:10
Fans:Electricity 141.98 0.00 01-JAN-01:10 5338.14 01-JAN-06:30
General:Fans:Electricity 141.98 0.00 01-JAN-01:10 5338.14 01-JAN-06:30
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 15.20 0.00 01-JAN-00:10 12924.61 10-AUG-17:10
General:Cooling:Electricity 15.20 0.00 01-JAN-00:10 12924.61 10-AUG-17:10
ExteriorLights:Electricity 41.18 0.00 01-JAN-08:10 2625.88 01-JAN-00:10
General:ExteriorLights:Electricity 41.18 0.00 01-JAN-08:10 2625.88 01-JAN-00:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 19-MAY-08:40
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 19-MAY-08:40


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 859.24 1838.65 03-MAY-01:00 80291.17 07-JAN-11:10
NaturalGas:Building 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
NaturalGas:Zone:KITCHEN 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
NaturalGas:SpaceType:GENERAL 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
InteriorEquipment:NaturalGas 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
InteriorEquipment:NaturalGas:Zone:KITCHEN 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
Cooking:InteriorEquipment:NaturalGas 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
NaturalGas:HVAC 188.36 0.00 01-JAN-01:10 59042.44 19-FEB-07:10
Heating:NaturalGas 188.36 0.00 01-JAN-01:10 59042.44 19-FEB-07:10
General:Heating:NaturalGas 188.36 0.00 01-JAN-01:10 59042.44 19-FEB-07:10
NaturalGas:Plant 193.72 0.00 27-FEB-05:00 24235.00 10-FEB-14:00
WaterSystems:NaturalGas 193.72 0.00 27-FEB-05:00 24235.00 10-FEB-14:00
Water Heater:WaterSystems:NaturalGas 193.72 0.00 27-FEB-05:00 24235.00 10-FEB-14:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 775.38 0.00 01-JAN-00:10 0.00 01-JUL-12:40
Water:Plant 775.38 0.00 01-JAN-00:10 0.00 01-JUL-12:40
WaterSystems:Water 775.38 0.00 01-JAN-00:10 0.00 01-JUL-12:40
WaterUse:WaterSystems:Water 775.38 0.00 01-JAN-00:10 0.00 01-JUL-12:40
MainsWater:Facility 775.38 0.00 01-JAN-00:10 0.00 01-JUL-12:40
MainsWater:Plant 775.38 0.00 01-JAN-00:10 0.00 01-JUL-12:40
WaterSystems:MainsWater 775.38 0.00 01-JAN-00:10 0.00 01-JUL-12:40
WaterUse:WaterSystems:MainsWater 775.38 0.00 01-JAN-00:10 0.00 01-JUL-12:40
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 826.78 2418.03 25-MAR-00:10 98770.05 29-AUG-13:00
EnergyTransfer:Building 405.71 1209.01 25-MAR-00:10 32095.60 10-AUG-17:10
EnergyTransfer:Zone:KITCHEN 322.24 1209.01 25-MAR-00:10 19602.51 23-MAY-04:10
Refrigeration:EnergyTransfer 136.16 2418.03 25-MAR-00:10 7834.84 25-JUL-03:30
Refrigeration:EnergyTransfer:Zone:KITCHEN 68.08 1209.01 25-MAR-00:10 3917.42 25-JUL-03:30
General:Refrigeration:EnergyTransfer 68.08 1209.01 25-MAR-00:10 3917.42 25-JUL-03:30
General:Refrigeration:EnergyTransfer:Zone:KITCHEN 68.08 1209.01 25-MAR-00:10 3917.42 25-JUL-03:30
EnergyTransfer:Plant 215.38 1209.01 25-MAR-00:10 21622.69 27-FEB-14:00
LowTempRefrigeration:Refrigeration:EnergyTransfer 12.99 0.00 01-JAN-11:10 1678.72 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 55.09 1059.55 12-FEB-01:10 2238.70 27-APR-13:50
EnergyTransfer:Zone:DINING 83.47 0.00 01-JAN-01:10 17828.77 10-AUG-17:10
Heating:EnergyTransfer 23.44 0.00 01-JAN-00:10 11507.61 19-FEB-07:10
Heating:EnergyTransfer:Zone:DINING 23.44 0.00 01-JAN-00:10 11507.61 19-FEB-07:10
General:Heating:EnergyTransfer 23.44 0.00 01-JAN-00:10 11507.61 19-FEB-07:10
General:Heating:EnergyTransfer:Zone:DINING 23.44 0.00 01-JAN-00:10 11507.61 19-FEB-07:10
Cooling:EnergyTransfer 314.19 0.00 01-JAN-01:10 29800.63 10-AUG-17:10
Cooling:EnergyTransfer:Zone:DINING 60.03 0.00 01-JAN-01:10 17828.77 10-AUG-17:10
General:Cooling:EnergyTransfer 314.19 0.00 01-JAN-01:10 29800.63 10-AUG-17:10
General:Cooling:EnergyTransfer:Zone:DINING 60.03 0.00 01-JAN-01:10 17828.77 10-AUG-17:10
Heating:EnergyTransfer:Zone:KITCHEN 0.00 0.00 01-JAN-00:10 806.91 09-FEB-05:10
General:Heating:EnergyTransfer:Zone:KITCHEN 0.00 0.00 01-JAN-00:10 806.91 09-FEB-05:10
Cooling:EnergyTransfer:Zone:KITCHEN 254.15 0.00 01-JAN-01:10 15834.46 23-MAY-04:10
General:Cooling:EnergyTransfer:Zone:KITCHEN 254.15 0.00 01-JAN-01:10 15834.46 23-MAY-04:10
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 147.30 0.00 01-JAN-00:10 19224.40 11-FEB-13:10
PlantLoopHeatingDemand:Plant 147.30 0.00 01-JAN-00:10 19224.40 11-FEB-13:10
WaterSystems:PlantLoopHeatingDemand 147.30 0.00 01-JAN-00:10 19224.40 11-FEB-13:10
General:WaterSystems:PlantLoopHeatingDemand 147.30 0.00 01-JAN-00:10 19224.40 11-FEB-13:10
EnergyTransfer:HVAC 205.69 0.00 01-JAN-01:10 48661.48 29-AUG-13:00
HeatingCoils:EnergyTransfer 150.69 0.00 01-JAN-01:10 47233.95 19-FEB-07:10
CoolingCoils:EnergyTransfer 55.00 0.00 01-JAN-00:10 48661.48 29-AUG-13:00
WaterSystems:EnergyTransfer 147.30 0.00 01-JAN-00:10 19224.40 11-FEB-13:10
WaterUse:WaterSystems:EnergyTransfer 147.30 0.00 01-JAN-00:10 19224.40 11-FEB-13:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
DINING 0.000 0.000 23.440 -60.032 0.000 0.000 71.382 19.580 52.748 47.343 0.000 0.684 0.000 0.000 -38.312 0.000 -85.708 -31.125
KITCHEN 0.000 0.000 0.004 -254.146 0.000 0.000 5.217 25.249 207.409 0.000 0.000 0.002 18.143 0.000 0.000 0.000 -1.878 -0.002
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.825 10.745 0.000 0.000 0.000 -12.570 -0.000
Total Facility 0.000 0.000 23.445 -314.179 0.000 0.000 76.599 44.830 260.157 47.343 0.000 2.511 28.889 0.000 -38.312 0.000 -100.157 -31.127


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
DINING 20-JUL-02:61 0.00 0.00 0.00 -33082.37 0.00 0.00 0.00 161.43 202.51 0.00 0.00 0.00 34635.76 0.00 -1851.67 0.00 -65.65 0.00
KITCHEN 05-OCT-02:61 0.00 0.00 0.00 -41157.28 0.00 0.00 0.00 208.16 1872.55 0.00 0.00 0.00 39172.65 0.00 -0.00 0.00 -96.09 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 20-JUL-02:61 0.00 0.00 0.00 -67655.36 0.00 0.00 0.00 369.59 2075.06 0.00 0.00 322.01 66916.46 0.00 -1851.67 0.00 -176.10 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
DINING 02-JAN-03:01 0.00 0.00 29334.14 0.00 0.00 0.00 0.00 161.43 202.51 0.00 0.00 0.00 0.00 0.00 -1927.70 0.00 -335.78 -27434.59
KITCHEN 09-FEB-05:03 0.00 0.00 8061.86 0.00 0.00 0.00 21.85 277.55 5126.85 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -64.09 -13424.02
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-JAN-03:01 0.00 0.00 29334.14 0.00 0.00 0.00 0.00 369.59 2075.06 0.00 0.00 32.72 0.00 0.00 -1927.70 0.00 -751.29 -29132.52



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC_1:1 1.8415 0.0000 87.5444 1.0000 Calculated from schedules 0.4161 1.8415 0.2259 1.0000 Not calculated 0.4161 0.2259    
PSZ-AC_2:2 1.3704 0.0000 6.2733 1.0000 Calculated from schedules 0.1513 1.3704 0.1104 1.0000 Not calculated 0.1513 0.1104    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC_1:1 1.8415 0.0000 87.5444 1.0000 Calculated from schedules 0.4161 1.8415 1.0000 1.0000 Not calculated 0.4161 0.2259    
PSZ-AC_2:2 1.3704 0.0000 6.2733 1.0000 Calculated from schedules 0.1513 1.3704 0.1325 1.0000 Not calculated 0.1513 0.1104    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
DINING PSZ-AC_1:1 0.000000 87.5444 0.003581 116.17 0.4161 1.0000 0.4161 1.000 0.4161
KITCHEN PSZ-AC_2:2 0.009440 6.2733 0.000792 116.17 0.1513 1.0000 0.1513 1.000 0.1513


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC_1:1 0.000000 87.54 0.003581 116.1715 0.4161 0.4161 0.4161
PSZ-AC_2:2 0.009440 6.27 0.000792 116.1715 0.1513 0.1513 0.1513


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
DINING PSZ-AC_1:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.8415 1.8415 1.8415 No 0.4161 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN PSZ-AC_2:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3704 1.3704 1.3704 No 0.1513 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC_1:1 1.8415 1.8415 1.8415 1.8415 0.4161 1.0000
PSZ-AC_2:2 1.3704 1.3704 1.3704 1.3704 0.1513 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
DINING PSZ-AC_1:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.8415 1.8415 1.8415 No 0.4161 0.5598 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN PSZ-AC_2:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3704 1.3704 1.3704 No 0.1513 0.1325 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC_1:1 1.8415 1.8415 1.8415 1.8415 0.4161 1.0000
PSZ-AC_2:2 1.3704 1.3704 1.3704 1.3704 0.1513 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Total gross floor area [m2] 232.34
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
DINING 116.17 116.17 0.00 137.83
KITCHEN 116.17 116.17 0.00 137.83
ATTIC 232.34 0.00 232.34 0.00
Totals 232.34 232.34 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 188.36 59042.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 15.20 12924.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 44.83 2217.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 41.18 2625.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 233.46 13046.29 477.16 26660.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 15.55 493.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 23.02 730.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 141.98 5338.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 193.72 24235.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.94 3294.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 10.93 982.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 17.96 637.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 308.87 552.06
Natural Gas 477.16 859.24
Additional 0.00 0.00
Total 786.02 1411.30


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 192.95
Space Heating 0.00
Space Cooling 65.41
Fans (All) 611.10
Service Water Heating 0.00
Receptacle Equipment 1170.81
Miscellaneous (All) 2376.05
Subtotal 2376.05


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 810.71
Service Water Heating 833.78
Miscellaneous (All) 3698.17
Subtotal 3698.17


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 3.18
Space Heating 13.35
Space Cooling 1.08
Fans (All) 10.06
Service Water Heating 13.73
Receptacle Equipment 53.08
Miscellaneous 5.53


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_DINING 5084. 8760.
LTG_SCH_KITCHEN 5084. 8760.
BLDG_EQUIP_SCH 1440. 8760.
FF_GAS_EQUIP_SCH 1442. 8760.
BLDG_OCC_SCH 2960. 7195.
INFIL_SCH_PNNL 3285. 8760.
DOOR_INFIL_SCH 3274. 6570.
VESTIBULE_DOOR_INFIL_SCH 3177. 6570.
BLDG_SWH_SCH 2246. 6360.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 7300. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
MINOA_SCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 6935. 6935.
WORK_EFF_SCH 0. 0.
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
WALKIN_OCC_LGHT_SCH_2 2785. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6935. 6935.
EXTERIOR_LIGHTING_SCHEDULE_B 8213. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 6935. 6935.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 1950. 7300.
SZ_SYSTEM_OA_MAX_FRAC_SCH 6570. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_NO_OPTIMUM DINING DUAL SP CONTROL January 21.11 365 21.11 365
CLGSETP_SCH_NO_OPTIMUM DINING DUAL SP CONTROL July 23.89 365 23.89 365
HTGSETP_KITCHEN_SCH_NO_OPTIMUM KITCHEN DUAL SP CONTROL January 18.89 365 18.89 365
CLGSETP_KITCHEN_SCH_NO_OPTIMUM KITCHEN DUAL SP CONTROL July 26.11 365 26.11 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
DINING 8760.00 0.00 0.00 0.00 0.00
KITCHEN 8436.67 323.33 0.00 0.00 0.00
ATTIC 7376.33 548.33 428.00 404.50 2.83
Min 7376.33 0.00 0.00 0.00 0.00
Max 8760.00 548.33 428.00 404.50 2.83
Average 8191.00 290.56 142.67 134.83 0.94
Sum 24573.00 871.67 428.00 404.50 2.83


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
DINING 254725.00 0.00 0.00 0.00 0.00
KITCHEN 16258.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 254725.00 0.00 0.00 0.00 0.00
Average 90327.67 0.00 0.00 0.00 0.00
Sum 270983.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
DINING 8740.00 20.00 0.00 0.00 0.00
KITCHEN 7686.50 1073.50 0.00 0.00 0.00
ATTIC 7462.17 769.50 259.00 186.00 83.33
Min 7462.17 20.00 0.00 0.00 0.00
Max 8740.00 1073.50 259.00 186.00 83.33
Average 7962.89 621.00 86.33 62.00 27.78
Sum 23888.67 1863.00 259.00 186.00 83.33


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
DINING 254643.50 81.50 0.00 0.00 0.00
KITCHEN 14185.33 2072.67 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 254643.50 2072.67 0.00 0.00 0.00
Average 89609.61 718.06 0.00 0.00 0.00
Sum 268828.83 2154.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:39

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.558226E+09 11226.27 15-JAN-03:23 -3.0 -4.1 0.445132E+10 3722.80 21-JAN-19:40 1.87 1.04
February 0.118488E+10 15710.68 19-FEB-04:43 -5.5 -6.0 0.407385E+10 4413.02 27-FEB-12:09 16.88 10.88
March 0.212324E+10 8389.52 01-MAR-05:02 0.00 -1.6 0.463495E+10 4680.89 18-MAR-18:00 16.70 8.15
April 0.420920E+10 13098.46 27-APR-13:00 26.10 16.28 0.467917E+10 4681.01 01-APR-18:49 26.10 16.28
May 0.603357E+10 11111.10 15-MAY-13:00 22.80 13.81 0.506812E+10 4681.10 06-MAY-18:10 22.80 13.81
June 0.812227E+10 13317.26 28-JUN-17:03 26.52 16.73 0.513800E+10 4681.26 10-JUN-18:49 26.52 16.73
July 0.112707E+11 33101.13 20-JUL-02:61 15.60 12.07 0.535783E+10 4681.24 15-JUL-18:00 15.60 12.07
August 0.125543E+11 32451.06 09-AUG-02:61 16.53 12.31 0.542588E+10 4681.45 26-AUG-18:10 20.40 16.97
September 0.785575E+10 31168.92 13-SEP-02:61 15.55 13.01 0.505208E+10 4681.25 23-SEP-18:30 20.00 16.29
October 0.398393E+10 10448.51 04-OCT-13:00 20.60 11.21 0.480824E+10 4680.61 07-OCT-18:10 13.80 10.77
November 0.137007E+10 7897.22 13-NOV-05:02 1.20 1.16 0.438034E+10 4680.94 04-NOV-18:30 1.20 1.16
December 0.767003E+09 7773.15 06-DEC-05:02 0.82 0.82 0.445756E+10 3726.65 05-DEC-12:00 0.82 0.82
                     
Annual Sum or Average 0.600331E+11         0.575273E+11        
Minimum of Months 0.558226E+09 7773.15   -5.5 -6.0 0.407385E+10 3722.80   0.82 0.82
Maximum of Months 0.125543E+11 33101.13   26.52 16.73 0.542588E+10 4681.45   26.52 16.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.200258E+11 30876.98 06-JAN-05:01 -1.2 -1.2 0.768218E+10 5062.29 27-JAN-11:00 11.70 8.31
February 0.182477E+11 32446.95 19-FEB-05:01 -5.6 -6.1 0.694831E+10 5108.57 27-FEB-11:00 16.70 10.79
March 0.211037E+11 29796.71 01-MAR-05:01 0.00 -1.6 0.770393E+10 5115.66 09-MAR-11:00 17.20 12.45
April 0.207954E+11 38755.42 02-APR-02:61 13.48 8.26 0.748636E+10 5135.93 27-APR-10:50 20.73 13.65
May 0.219366E+11 41038.31 15-MAY-02:61 10.18 8.23 0.777151E+10 5135.93 04-MAY-10:00 10.18 8.23
June 0.214357E+11 38746.18 04-JUN-02:61 13.22 9.58 0.756414E+10 5135.94 21-JUN-10:00 18.90 14.05
July 0.224787E+11 39736.91 06-JUL-02:61 12.12 9.05 0.783447E+10 5135.94 27-JUL-10:50 20.40 15.65
August 0.226732E+11 36606.43 19-AUG-02:61 13.62 10.93 0.784409E+10 5135.95 30-AUG-10:50 20.58 16.52
September 0.217056E+11 38115.02 05-SEP-02:61 12.62 9.59 0.755248E+10 5135.94 14-SEP-10:00 20.00 16.81
October 0.222692E+11 41198.92 05-OCT-02:61 10.92 8.09 0.773758E+10 5135.91 04-OCT-10:00 10.92 8.09
November 0.208891E+11 32376.95 05-NOV-02:61 13.22 12.32 0.745104E+10 5113.09 04-NOV-10:00 13.22 12.32
December 0.205916E+11 30478.80 26-DEC-05:01 -0.6 -0.6 0.768307E+10 5074.91 14-DEC-11:00 -0.6 -0.6
                     
Annual Sum or Average 0.254152E+12         0.912592E+11        
Minimum of Months 0.182477E+11 29796.71   -5.6 -6.1 0.694831E+10 5062.29   -0.6 -0.6
Maximum of Months 0.226732E+11 41198.92   13.62 12.32 0.784409E+10 5135.95   20.73 16.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 5.92 4.99 0.00 0.00 01-JAN-00:10 5.92 4.99
February 0.00 0.00 01-FEB-00:02 7.00 6.66 0.00 0.00 01-FEB-00:10 7.00 6.66
March 0.00 0.00 01-MAR-00:02 5.92 4.69 0.00 0.00 01-MAR-00:10 5.92 4.69
April 0.00 0.00 01-APR-00:01 7.93 7.13 0.00 0.00 01-APR-00:10 7.93 7.13
May 0.00 0.00 01-MAY-00:01 10.38 9.30 0.00 0.00 01-MAY-00:10 10.38 9.30
June 0.00 0.00 01-JUN-00:01 12.83 10.29 0.00 0.00 01-JUN-00:10 12.83 10.29
July 0.00 0.00 01-JUL-00:01 15.43 12.22 0.00 0.00 01-JUL-00:10 15.43 12.22
August 0.00 0.00 01-AUG-00:01 17.17 13.75 0.00 0.00 01-AUG-00:10 17.17 13.75
September 0.00 0.00 01-SEP-00:01 16.38 13.40 0.00 0.00 01-SEP-00:10 16.38 13.40
October 0.00 0.00 01-OCT-00:01 14.35 12.42 0.00 0.00 01-OCT-00:10 14.35 12.42
November 0.00 0.00 01-NOV-00:01 9.22 8.04 0.00 0.00 01-NOV-00:10 9.22 8.04
December 0.00 0.00 01-DEC-00:01 4.40 3.48 0.00 0.00 01-DEC-00:10 4.40 3.48
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   4.40 3.48 0.00 0.00   4.40 3.48
Maximum of Months 0.00 0.00   17.17 13.75 0.00 0.00   17.17 13.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.687732E+10 29335.22 02-JAN-03:01 6.20
February 0.438351E+10 28435.90 16-FEB-03:01 4.32
March 0.208490E+10 28899.62 06-MAR-03:01 6.70
April 0.836263E+09 19734.83 18-APR-02:62 3.80
May 0.201869E+09 11371.21 18-MAY-02:62 6.20
June 1299811.84 471.87 14-JUN-06:10 10.10
July 47281.50 381.00 31-JUL-04:03 17.20
August 2613137.17 8741.45 15-AUG-02:03 16.57
September 15214636.96 4337.07 27-SEP-04:04 7.20
October 0.440918E+09 10427.56 31-OCT-02:62 7.20
November 0.290407E+10 27042.73 13-NOV-05:01 1.20
December 0.569239E+10 29273.46 27-DEC-03:01 4.60
         
Annual Sum or Average 0.234404E+11      
Minimum of Months 47281.50 381.00   1.20
Maximum of Months 0.687732E+10 29335.22   17.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2177436.95 7477.88 07-JAN-05:03 -2.2
February 1855785.12 8069.11 09-FEB-05:03 -0.8
March 33518.39 421.13 27-MAR-04:04 4.90
April 54758.73 912.65 12-APR-04:04 4.32
May 0.00 0.00 01-MAY-00:01 10.38
June 0.00 0.00 01-JUN-00:01 12.83
July 0.00 0.00 01-JUL-00:01 15.43
August 0.00 0.00 01-AUG-00:01 17.17
September 0.00 0.00 01-SEP-00:01 16.38
October 0.00 0.00 01-OCT-00:01 14.35
November 52988.74 497.17 22-NOV-05:04 3.80
December 42716.51 664.55 11-DEC-05:04 3.72
         
Annual Sum or Average 4217204.43      
Minimum of Months 0.00 0.00   -2.2
Maximum of Months 2177436.95 8069.11   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 5.92
February 0.00 0.00 01-FEB-00:02 7.00
March 0.00 0.00 01-MAR-00:02 5.92
April 0.00 0.00 01-APR-00:01 7.93
May 0.00 0.00 01-MAY-00:01 10.38
June 0.00 0.00 01-JUN-00:01 12.83
July 0.00 0.00 01-JUL-00:01 15.43
August 0.00 0.00 01-AUG-00:01 17.17
September 0.00 0.00 01-SEP-00:01 16.38
October 0.00 0.00 01-OCT-00:01 14.35
November 0.00 0.00 01-NOV-00:01 9.22
December 0.00 0.00 01-DEC-00:01 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.165449E+10 968.56 02-JAN-10:09 0.597334E+10 3930.26 01-JAN-11:09
February 0.149855E+10 968.56 01-FEB-10:09 0.539527E+10 3930.26 01-FEB-11:09
March 0.168084E+10 968.56 01-MAR-10:09 0.597338E+10 3930.26 01-MAR-11:09
April 0.160761E+10 968.56 01-APR-16:10 0.578064E+10 3930.26 01-APR-10:09
May 0.166766E+10 968.56 01-MAY-09:09 0.597336E+10 3930.26 01-MAY-10:09
June 0.162466E+10 968.56 01-JUN-09:09 0.578068E+10 3930.26 01-JUN-10:09
July 0.165081E+10 968.56 01-JUL-16:10 0.597331E+10 3930.26 01-JUL-10:09
August 0.168084E+10 968.56 01-AUG-09:09 0.597338E+10 3930.26 01-AUG-10:09
September 0.160800E+10 968.56 01-SEP-09:09 0.578064E+10 3930.26 01-SEP-10:09
October 0.165430E+10 968.56 02-OCT-09:09 0.597334E+10 3930.26 01-OCT-10:09
November 0.160161E+10 968.56 01-NOV-09:09 0.578066E+10 3930.26 01-NOV-10:09
December 0.165100E+10 968.56 01-DEC-10:09 0.597331E+10 3930.26 01-DEC-11:09
             
Annual Sum or Average 0.195804E+11     0.703313E+11    
Minimum of Months 0.149855E+10 968.56   0.539527E+10 3930.26  
Maximum of Months 0.168084E+10 968.56   0.597338E+10 3930.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.213351E+10 1248.98 02-JAN-10:09 0.171305E+11 10339.04 01-JAN-11:09
February 0.193243E+10 1248.98 01-FEB-10:09 0.154728E+11 10339.04 01-FEB-11:09
March 0.216749E+10 1248.98 01-MAR-10:09 0.171306E+11 10339.04 01-MAR-11:09
April 0.207306E+10 1248.98 01-APR-16:10 0.165779E+11 10339.04 01-APR-10:09
May 0.215050E+10 1248.98 01-MAY-09:09 0.171306E+11 10339.04 01-MAY-10:09
June 0.209504E+10 1248.98 01-JUN-09:09 0.165780E+11 10339.04 01-JUN-10:09
July 0.212877E+10 1248.98 01-JUL-16:10 0.171305E+11 10339.04 01-JUL-10:09
August 0.216749E+10 1248.98 01-AUG-09:09 0.171306E+11 10339.04 01-AUG-10:09
September 0.207356E+10 1248.98 01-SEP-09:09 0.165779E+11 10339.04 01-SEP-10:09
October 0.213326E+10 1248.98 02-OCT-09:09 0.171305E+11 10339.04 01-OCT-10:09
November 0.206532E+10 1248.98 01-NOV-09:09 0.165780E+11 10339.04 01-NOV-10:09
December 0.212902E+10 1248.98 01-DEC-10:09 0.171305E+11 10339.04 01-DEC-11:09
             
Annual Sum or Average 0.252494E+11     0.201699E+12    
Minimum of Months 0.193243E+10 1248.98   0.154728E+11 10339.04  
Maximum of Months 0.216749E+10 1248.98   0.171306E+11 10339.04  



Table of Contents

Report: SpaceGainsMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.940563E+10 0.165449E+10 0.597334E+10 0.00 0.00 0.00 0.00 0.00 0.117288E+11
February 0.852256E+10 0.149855E+10 0.539527E+10 0.00 0.00 0.00 0.00 0.00 0.961727E+10
March 0.954557E+10 0.168084E+10 0.597338E+10 0.00 0.00 0.00 0.00 0.00 0.884525E+10
April 0.915225E+10 0.160761E+10 0.578064E+10 0.00 0.00 0.00 0.00 32687660.19 0.702414E+10
May 0.947560E+10 0.166766E+10 0.597336E+10 0.00 0.00 0.00 0.00 2291226.51 0.602946E+10
June 0.922788E+10 0.162466E+10 0.578068E+10 0.00 0.00 0.00 0.00 21340498.48 0.445925E+10
July 0.939996E+10 0.165081E+10 0.597331E+10 0.00 0.00 0.00 0.00 0.186648E+09 0.332216E+10
August 0.954557E+10 0.168084E+10 0.597338E+10 0.00 0.00 0.00 0.00 0.437440E+09 0.281358E+10
September 0.915225E+10 0.160800E+10 0.578064E+10 0.00 0.00 0.00 0.00 3388123.19 0.482893E+10
October 0.940563E+10 0.165430E+10 0.597334E+10 0.00 0.00 0.00 0.00 0.00 0.704900E+10
November 0.909363E+10 0.160161E+10 0.578066E+10 0.00 0.00 0.00 0.00 0.00 0.899393E+10
December 0.939996E+10 0.165100E+10 0.597331E+10 0.00 0.00 0.00 0.00 0.00 0.109964E+11
                   
Annual Sum or Average 0.111326E+12 0.195804E+11 0.703313E+11 0.00 0.00 0.00 0.00 0.683795E+09 0.857082E+11
Minimum of Months 0.852256E+10 0.149855E+10 0.539527E+10 0.00 0.00 0.00 0.00 0.00 0.281358E+10
Maximum of Months 0.954557E+10 0.168084E+10 0.597338E+10 0.00 0.00 0.00 0.00 0.437440E+09 0.117288E+11



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.673993E+09 0.213351E+10 0.129741E+11 0.121577E+11 0.00 0.00 0.00 0.00 0.218336E+09
February 0.610713E+09 0.193243E+10 0.117185E+11 0.109812E+11 0.00 0.00 0.00 0.00 0.185400E+09
March 0.684021E+09 0.216749E+10 0.129742E+11 0.121577E+11 0.00 0.00 0.00 0.00 0.188445E+09
April 0.655836E+09 0.207306E+10 0.125556E+11 0.117655E+11 0.00 0.00 0.00 57237.22 0.174630E+09
May 0.679007E+09 0.215050E+10 0.129741E+11 0.121577E+11 0.00 0.00 0.00 0.00 0.148766E+09
June 0.661256E+09 0.209504E+10 0.125556E+11 0.117655E+11 0.00 0.00 0.00 4685.26 0.138181E+09
July 0.673587E+09 0.212877E+10 0.129741E+11 0.121577E+11 0.00 0.00 0.00 639690.19 0.116504E+09
August 0.684021E+09 0.216749E+10 0.129742E+11 0.121577E+11 0.00 0.00 0.00 1620588.21 0.107381E+09
September 0.655836E+09 0.207356E+10 0.125556E+11 0.117655E+11 0.00 0.00 0.00 0.00 76872852.01
October 0.673993E+09 0.213326E+10 0.129741E+11 0.121577E+11 0.00 0.00 0.00 0.00 0.161020E+09
November 0.651635E+09 0.206532E+10 0.125556E+11 0.117655E+11 0.00 0.00 0.00 0.00 0.180935E+09
December 0.673587E+09 0.212902E+10 0.129741E+11 0.121577E+11 0.00 0.00 0.00 0.00 0.181700E+09
                   
Annual Sum or Average 0.797748E+10 0.252494E+11 0.152760E+12 0.143147E+12 0.00 0.00 0.00 2322200.89 0.187817E+10
Minimum of Months 0.610713E+09 0.193243E+10 0.117185E+11 0.109812E+11 0.00 0.00 0.00 0.00 76872852.01
Maximum of Months 0.684021E+09 0.216749E+10 0.129742E+11 0.121577E+11 0.00 0.00 0.00 1620588.21 0.218336E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.133616E+09 0.372408E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.139231E+09 0.569080E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.147750E+09 0.915865E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.121931E+09 0.134113E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.121545E+09 0.174678E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118916E+09 0.175569E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.132299E+09 0.184565E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.166265E+09 0.144956E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.218913E+09 0.115708E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.185325E+09 0.698636E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.143658E+09 0.409780E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.195788E+09 0.308589E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.182524E+10 0.125702E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118916E+09 0.308589E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.218913E+09 0.184565E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 9454.80 07-JAN-19:10 968.56 02-JAN-10:09 3930.26 01-JAN-11:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 14597.23 07-JAN-20:00
February 9454.80 04-FEB-19:10 968.56 01-FEB-10:09 3930.26 01-FEB-11:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:02 15677.40 18-FEB-20:00
March 9454.80 04-MAR-19:10 968.56 01-MAR-10:09 3930.26 01-MAR-11:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:02 10695.71 04-MAR-20:00
April 9454.80 01-APR-18:10 968.56 01-APR-16:10 3930.26 01-APR-10:09 0.00 0.00 0.00 0.00 1320.31 01-APR-17:10 9335.75 17-APR-18:53
May 9454.80 06-MAY-18:10 968.56 01-MAY-09:09 3930.26 01-MAY-10:09 0.00 0.00 0.00 0.00 278.48 05-MAY-16:10 8387.22 17-MAY-20:00
June 9454.80 03-JUN-18:10 968.56 01-JUN-09:09 3930.26 01-JUN-10:09 0.00 0.00 0.00 0.00 1483.44 28-JUN-17:03 6789.11 06-JUN-17:52
July 9454.80 01-JUL-18:10 968.56 01-JUL-16:10 3930.26 01-JUL-10:09 0.00 0.00 0.00 0.00 2802.11 24-JUL-18:00 5517.17 12-JUL-11:03
August 9454.80 05-AUG-18:10 968.56 01-AUG-09:09 3930.26 01-AUG-10:09 0.00 0.00 0.00 0.00 4249.57 10-AUG-17:03 5964.81 01-AUG-11:10
September 9454.80 02-SEP-18:10 968.56 01-SEP-09:09 3930.26 01-SEP-10:09 0.00 0.00 0.00 0.00 416.92 14-SEP-17:00 6485.59 16-SEP-18:55
October 9454.80 07-OCT-18:10 968.56 02-OCT-09:09 3930.26 01-OCT-10:09 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 8366.68 31-OCT-20:00
November 9454.80 04-NOV-18:10 968.56 01-NOV-09:09 3930.26 01-NOV-10:09 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 11259.06 13-NOV-21:00
December 9454.80 02-DEC-19:10 968.56 01-DEC-10:09 3930.26 01-DEC-11:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 12999.18 26-DEC-12:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 9454.80   968.56   3930.26   0.00 0.00 0.00 0.00 0.00   5517.17  
Maximum of Months 9454.80   968.56   3930.26   0.00 0.00 0.00 0.00 4249.57   15677.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 677.52 07-JAN-19:10 1248.98 02-JAN-10:09 7604.23 01-JAN-11:09 7998.14 01-JAN-11:09 0.00 0.00 0.00 0.00 01-JAN-00:01 705.47 28-JAN-04:10
February 677.52 04-FEB-19:10 1248.98 01-FEB-10:09 7604.23 01-FEB-11:09 7998.14 01-FEB-11:09 0.00 0.00 0.00 0.00 01-FEB-00:02 636.19 16-FEB-03:55
March 677.52 04-MAR-19:10 1248.98 01-MAR-10:09 7604.23 01-MAR-11:09 7998.14 01-MAR-11:09 0.00 0.00 0.00 0.00 01-MAR-00:02 498.74 29-MAR-00:20
April 677.52 01-APR-18:10 1248.98 01-APR-16:10 7604.23 01-APR-10:09 7998.14 01-APR-10:09 0.00 0.00 0.00 6.52 01-APR-16:00 639.03 08-APR-04:00
May 677.52 06-MAY-18:10 1248.98 01-MAY-09:09 7604.23 01-MAY-10:09 7998.14 01-MAY-10:09 0.00 0.00 0.00 0.00 01-MAY-00:01 411.43 17-MAY-02:00
June 677.52 03-JUN-18:10 1248.98 01-JUN-09:09 7604.23 01-JUN-10:09 7998.14 01-JUN-10:09 0.00 0.00 0.00 1.53 28-JUN-16:53 688.94 13-JUN-03:20
July 677.52 01-JUL-18:10 1248.98 01-JUL-16:10 7604.23 01-JUL-10:09 7998.14 01-JUL-10:09 0.00 0.00 0.00 12.55 24-JUL-14:10 392.48 02-JUL-04:00
August 677.52 05-AUG-18:10 1248.98 01-AUG-09:09 7604.23 01-AUG-10:09 7998.14 01-AUG-10:09 0.00 0.00 0.00 20.52 08-AUG-17:00 551.18 11-AUG-03:50
September 677.52 02-SEP-18:10 1248.98 01-SEP-09:09 7604.23 01-SEP-10:09 7998.14 01-SEP-10:09 0.00 0.00 0.00 0.00 01-SEP-00:01 300.51 19-SEP-01:00
October 677.52 07-OCT-18:10 1248.98 02-OCT-09:09 7604.23 01-OCT-10:09 7998.14 01-OCT-10:09 0.00 0.00 0.00 0.00 01-OCT-00:01 504.17 28-OCT-04:00
November 677.52 04-NOV-18:10 1248.98 01-NOV-09:09 7604.23 01-NOV-10:09 7998.14 01-NOV-10:09 0.00 0.00 0.00 0.00 01-NOV-00:01 527.35 29-NOV-03:50
December 677.52 02-DEC-19:10 1248.98 01-DEC-10:09 7604.23 01-DEC-11:09 7998.14 01-DEC-11:09 0.00 0.00 0.00 0.00 01-DEC-00:01 499.98 17-DEC-03:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 677.52   1248.98   7604.23   7998.14   0.00 0.00 0.00 0.00   300.51  
Maximum of Months 677.52   1248.98   7604.23   7998.14   0.00 0.00 0.00 20.52   705.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 337.31 09-JAN-03:10 1094.94 20-JAN-13:30
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 500.99 27-FEB-03:55 1407.16 08-FEB-13:30
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 412.04 01-MAR-21:00 2014.73 14-MAR-13:20
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 374.74 27-APR-02:00 2285.84 18-APR-12:50
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 354.45 15-MAY-03:00 2665.99 31-MAY-13:20
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 371.54 10-JUN-02:00 2360.03 09-JUN-12:30
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 407.94 08-JUL-03:00 2404.45 04-JUL-12:20
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 401.65 09-AUG-05:35 2224.63 06-AUG-12:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 471.80 23-SEP-02:00 2070.01 07-SEP-13:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 397.55 04-OCT-22:00 1537.83 11-OCT-12:30
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 420.02 04-NOV-20:00 1145.74 15-NOV-12:30
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 508.07 06-DEC-03:55 932.91 06-DEC-12:10
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 337.31   932.91  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 508.07   2665.99  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11226.27 15-JAN-03:23 0.00 1614.26 2700.09 0.00 0.00 0.00 0.00 0.00 158.44
February 15710.68 19-FEB-04:43 0.00 1614.26 6750.23 0.00 0.00 0.00 0.00 0.00 346.86
March 8389.52 01-MAR-05:02 5252.67 2152.35 16263.12 0.00 0.00 0.00 0.00 0.00 47.51
April 13098.46 27-APR-13:00 7353.73 968.56 3388.15 0.00 0.00 0.00 0.00 1108.31 0.00
May 11111.10 15-MAY-13:00 7353.73 968.56 3388.15 0.00 0.00 0.00 0.00 0.00 553.69
June 13317.26 28-JUN-17:03 25212.80 2905.67 9757.87 0.00 0.00 0.00 0.00 1483.44 0.00
July 33101.13 20-JUL-02:61 0.00 1614.26 2700.09 0.00 0.00 0.00 0.00 0.00 65.65
August 32451.06 09-AUG-02:61 0.00 1129.98 1890.06 0.00 0.00 0.00 0.00 0.00 52.36
September 31168.92 13-SEP-02:61 0.00 1614.26 2700.09 0.00 0.00 0.00 0.00 0.00 57.76
October 10448.51 04-OCT-13:00 7353.73 968.56 3388.15 0.00 0.00 0.00 0.00 0.00 1677.85
November 7897.22 13-NOV-05:02 5252.67 2152.35 16263.12 0.00 0.00 0.00 0.00 0.00 48.20
December 7773.15 06-DEC-05:02 5252.67 2152.35 16263.12 0.00 0.00 0.00 0.00 0.00 36.94
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7773.15   0.00 968.56 1890.06 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33101.13   25212.80 2905.67 16263.12 0.00 0.00 0.00 0.00 1483.44 1677.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 30876.98 06-JAN-05:01 376.40 2775.52 38635.07 33095.74 0.00 0.00 0.00 0.00 38.14
February 32446.95 19-FEB-05:01 0.00 1665.31 30826.78 26476.59 0.00 0.00 0.00 0.00 90.22
March 29796.71 01-MAR-05:01 376.40 2775.52 38635.07 33095.74 0.00 0.00 0.00 0.00 53.03
April 38755.42 02-APR-02:61 0.00 1665.31 13291.13 4412.76 0.00 0.00 0.00 0.00 120.67
May 41038.31 15-MAY-02:61 0.00 2081.64 16613.91 5515.96 0.00 0.00 0.00 0.00 20.22
June 38746.18 04-JUN-02:61 0.00 2081.64 16613.91 5515.96 0.00 0.00 0.00 0.00 171.50
July 39736.91 06-JUL-02:61 0.00 2081.64 16613.91 5515.96 0.00 0.00 0.00 0.00 130.46
August 36606.43 19-AUG-02:61 0.00 2081.64 16613.91 5515.96 0.00 0.00 0.00 0.00 167.36
September 38115.02 05-SEP-02:61 0.00 2081.64 16613.91 5515.96 0.00 0.00 0.00 0.00 143.31
October 41198.92 05-OCT-02:61 0.00 2081.64 16613.91 5515.96 0.00 0.00 0.00 0.00 96.09
November 32376.95 05-NOV-02:61 0.00 1873.47 14952.52 4964.36 0.00 0.00 0.00 0.00 123.47
December 30478.80 26-DEC-05:01 376.40 2775.52 38635.07 33095.74 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 29796.71   0.00 1665.31 13291.13 4412.76 0.00 0.00 0.00 0.00 0.00
Maximum of Months 41198.92   376.40 2775.52 38635.07 33095.74 0.00 0.00 0.00 0.00 171.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.12 0.00
February 0.00 01-FEB-00:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.40 0.00
March 0.00 01-MAR-00:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 177.81 0.00
April 0.00 01-APR-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.27 0.00
May 0.00 01-MAY-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 130.50 0.00
June 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 223.26 0.00
July 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.45 0.00
August 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 188.41 0.00
September 0.00 01-SEP-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 180.12 0.00
October 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 337.55 0.00
November 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82.57 0.00
December 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 213.01 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.27 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 337.55 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.465098E+11 25676.25 11-JAN-11:20 0.106218E+12 80291.17 07-JAN-11:09
February 0.417147E+11 25700.43 24-FEB-11:09 0.882023E+11 78079.41 19-FEB-11:09
March 0.456718E+11 25701.55 09-MAR-11:20 0.785453E+11 64847.14 22-MAR-10:09
April 0.442131E+11 29517.88 27-APR-16:10 0.653234E+11 55957.32 18-APR-10:09
May 0.457257E+11 28692.58 06-MAY-10:20 0.602235E+11 47765.04 18-MAY-10:09
June 0.449555E+11 29611.53 28-JUN-16:00 0.547210E+11 44919.96 01-JUN-12:20
July 0.490010E+11 33532.37 31-JUL-10:00 0.558456E+11 44420.28 01-JUL-12:20
August 0.511285E+11 34296.71 29-AUG-10:20 0.557612E+11 44152.97 31-AUG-12:00
September 0.456555E+11 29488.19 12-SEP-10:20 0.545184E+11 44507.99 30-SEP-12:39
October 0.459370E+11 25718.80 04-OCT-10:20 0.615520E+11 48572.33 30-OCT-10:09
November 0.448793E+11 25696.59 01-NOV-10:20 0.788946E+11 65908.17 30-NOV-13:09
December 0.466674E+11 25677.37 28-DEC-11:20 0.994379E+11 80114.51 26-DEC-13:09
             
Annual Sum or Average 0.552059E+12     0.859243E+12    
Minimum of Months 0.417147E+11 25676.25   0.545184E+11 44152.97  
Maximum of Months 0.511285E+11 34296.71   0.106218E+12 80291.17  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.378800E+10 0.447765E+10 0.231039E+11 0.00 0.121787E+11 0.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.343098E+10 0.369146E+10 0.208680E+11 0.00 0.110204E+11 0.72 0.00 4940215.28 0.00 0.00 0.00 0.00 0.00
March 0.384832E+10 0.360323E+10 0.231040E+11 0.00 0.120878E+11 0.80 0.00 11209550.12 0.00 0.00 0.00 0.00 0.00
April 0.368067E+10 0.300138E+10 0.223586E+11 0.00 0.116167E+11 0.77 0.00 0.565189E+09 0.00 0.00 0.00 0.00 0.00
May 0.381816E+10 0.266579E+10 0.231040E+11 0.00 0.119541E+11 0.80 0.00 0.101112E+10 0.00 0.00 0.00 0.00 0.00
June 0.371970E+10 0.234596E+10 0.223587E+11 0.00 0.115888E+11 0.77 0.00 0.177811E+10 0.00 0.00 0.00 0.00 0.00
July 0.377958E+10 0.253187E+10 0.231038E+11 0.00 0.120163E+11 0.79 0.00 0.425167E+10 0.00 0.00 0.00 0.00 0.00
August 0.384832E+10 0.290685E+10 0.231040E+11 0.00 0.120646E+11 0.80 0.00 0.585893E+10 0.00 0.00 0.00 0.00 0.00
September 0.368156E+10 0.327552E+10 0.223586E+11 0.00 0.116013E+11 0.77 0.00 0.158091E+10 0.00 0.00 0.00 0.00 0.00
October 0.378756E+10 0.388683E+10 0.231039E+11 0.00 0.119494E+11 0.79 0.00 95033873.14 0.00 0.00 0.00 0.00 0.00
November 0.366693E+10 0.420193E+10 0.223586E+11 0.00 0.116866E+11 0.77 0.00 40101514.87 0.00 0.00 0.00 0.00 0.00
December 0.378002E+10 0.459266E+10 0.231038E+11 0.00 0.122202E+11 0.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Annual Sum or Average 0.448298E+11 0.411812E+11 0.272030E+12 0.00 0.141985E+12 9.37 0.00 0.151972E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.343098E+10 0.234596E+10 0.208680E+11 0.00 0.110204E+11 0.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.384832E+10 0.459266E+10 0.231040E+11 0.00 0.122202E+11 0.80 0.00 0.585893E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.405257E+11 0.00 0.481326E+11 0.00 0.175599E+11 0.00 0.00
February 0.366039E+11 0.00 0.356442E+11 0.00 0.159542E+11 0.00 0.00
March 0.405257E+11 0.00 0.205168E+11 0.00 0.175027E+11 0.00 0.00
April 0.392184E+11 0.00 0.966586E+10 0.00 0.164391E+11 0.00 0.00
May 0.405257E+11 0.00 0.330864E+10 0.00 0.163891E+11 0.00 0.00
June 0.392184E+11 0.00 0.226451E+09 0.00 0.152761E+11 0.00 0.00
July 0.405257E+11 0.00 2466892.08 0.00 0.153174E+11 0.00 0.00
August 0.405257E+11 0.00 2601510.71 0.00 0.152329E+11 0.00 0.00
September 0.392184E+11 0.00 0.373992E+09 0.00 0.149260E+11 0.00 0.00
October 0.405257E+11 0.00 0.508489E+10 0.00 0.159414E+11 0.00 0.00
November 0.392184E+11 0.00 0.236318E+11 0.00 0.160444E+11 0.00 0.00
December 0.405257E+11 0.00 0.417732E+11 0.00 0.171389E+11 0.00 0.00
               
Annual Sum or Average 0.477158E+12 0.00 0.188363E+12 0.00 0.193722E+12 0.00 0.00
Minimum of Months 0.366039E+11 0.00 2466892.08 0.00 0.149260E+11 0.00 0.00
Maximum of Months 0.405257E+11 0.00 0.481326E+11 0.00 0.175599E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2217.54 02-JAN-10:09 2625.88 01-JAN-00:10 14269.29 01-JAN-11:09 0.00 5338.14 01-JAN-06:30 0.00 01-JAN-07:10 0.00 01-JAN-00:10
February 2217.54 01-FEB-10:09 2625.88 01-FEB-00:10 14269.29 01-FEB-11:09 0.00 5338.14 01-FEB-06:10 0.00 01-FEB-06:10 0.00 01-FEB-00:10
March 2217.54 01-MAR-10:09 2625.88 01-MAR-00:10 14269.29 01-MAR-11:09 0.00 5338.14 01-MAR-23:10 0.00 01-MAR-06:10 0.00 01-MAR-00:10
April 2217.54 01-APR-16:10 2625.88 01-APR-00:10 14269.29 01-APR-10:09 0.00 5338.14 02-APR-05:19 0.00 01-APR-06:10 0.00 01-APR-00:10
May 2217.54 01-MAY-09:09 2625.88 01-MAY-00:10 14269.29 01-MAY-10:09 0.00 5338.14 01-MAY-05:10 0.00 19-MAY-08:39 0.00 01-MAY-00:10
June 2217.54 01-JUN-09:09 2625.88 01-JUN-00:10 14269.29 01-JUN-10:09 0.00 5338.14 01-JUN-04:00 0.00 11-JUN-09:39 0.00 01-JUN-00:10
July 2217.54 01-JUL-16:10 2625.88 01-JUL-00:10 14269.29 01-JUL-10:09 0.00 5338.14 05-JUL-11:50 0.00 01-JUL-12:39 0.00 01-JUL-00:10
August 2217.54 01-AUG-09:09 2625.88 01-AUG-00:10 14269.29 01-AUG-10:09 0.00 5338.14 01-AUG-15:30 0.00 02-AUG-10:20 0.00 01-AUG-00:10
September 2217.54 01-SEP-09:09 2625.88 01-SEP-00:10 14269.29 01-SEP-10:09 0.00 5338.14 01-SEP-15:09 0.00 01-SEP-05:10 0.00 01-SEP-00:10
October 2217.54 02-OCT-09:09 2625.88 01-OCT-00:10 14269.29 01-OCT-10:09 0.00 5338.14 02-OCT-04:00 0.00 01-OCT-06:10 0.00 01-OCT-00:10
November 2217.54 01-NOV-09:09 2625.88 01-NOV-00:10 14269.29 01-NOV-10:09 0.00 5338.14 01-NOV-05:19 0.00 01-NOV-05:10 0.00 01-NOV-00:10
December 2217.54 01-DEC-10:09 2625.88 01-DEC-00:10 14269.29 01-DEC-11:09 0.00 5338.14 01-DEC-07:19 0.00 01-DEC-06:10 0.00 01-DEC-00:10
                           
Annual Sum or Average             0.00            
Minimum of Months 2217.54   2625.88   14269.29   0.00 5338.14   0.00   0.00  
Maximum of Months 2217.54   2625.88   14269.29   0.00 5338.14   0.00   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 1072.54 27-FEB-14:00 0.00 0.00 0.00 0.00 0.00
March 1200.84 18-MAR-15:00 0.00 0.00 0.00 0.00 0.00
April 7954.89 27-APR-12:00 0.00 0.00 0.00 0.00 0.00
May 7270.42 06-MAY-12:00 0.00 0.00 0.00 0.00 0.00
June 8343.36 28-JUN-17:10 0.00 0.00 0.00 0.00 0.00
July 10724.22 24-JUL-12:00 0.00 0.00 0.00 0.00 0.00
August 12924.61 10-AUG-17:10 0.00 0.00 0.00 0.00 0.00
September 7682.48 14-SEP-13:00 0.00 0.00 0.00 0.00 0.00
October 3831.76 04-OCT-13:00 0.00 0.00 0.00 0.00 0.00
November 3521.69 04-NOV-14:09 0.00 0.00 0.00 0.00 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 12924.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 25676.25 11-JAN-11:20 2217.54 14269.29 0.00 0.00 5338.14 0.00 0.00 0.00 0.00
February 25700.43 24-FEB-11:09 2217.54 14269.29 0.00 0.00 5338.14 0.00 0.00 0.00 0.00
March 25701.55 09-MAR-11:20 2217.54 14269.29 0.00 0.00 5338.14 0.00 0.00 0.00 0.00
April 29517.88 27-APR-16:10 2217.54 12919.68 0.00 0.00 5338.14 0.00 0.00 7881.91 0.00
May 28692.58 06-MAY-10:20 1971.15 14269.29 0.00 0.00 5338.14 0.00 0.00 3205.30 0.00
June 29611.53 28-JUN-16:00 2217.54 12919.68 0.00 0.00 5338.14 0.00 0.00 7977.08 0.00
July 33532.37 31-JUL-10:00 2217.54 14269.29 0.00 0.00 5338.14 0.00 0.00 10002.20 0.00
August 34296.71 29-AUG-10:20 2217.54 14269.29 0.00 0.00 5338.14 0.00 0.00 8550.96 0.00
September 29488.19 12-SEP-10:20 2217.54 14269.29 0.00 0.00 5338.14 0.00 0.00 3746.30 0.00
October 25718.80 04-OCT-10:20 2217.54 14269.29 0.00 0.00 5338.14 0.00 0.00 0.00 0.00
November 25696.59 01-NOV-10:20 2217.54 14269.29 0.00 0.00 5338.14 0.00 0.00 0.00 0.00
December 25677.37 28-DEC-11:20 2217.54 14269.29 0.00 0.00 5338.14 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 25676.25   1971.15 12919.68 0.00 0.00 5338.14 0.00 0.00 0.00 0.00
Maximum of Months 34296.71   2217.54 14269.29 0.00 0.00 5338.14 0.00 0.00 10002.20 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 26660.45 01-JAN-11:09 0.00 53708.55 08-JAN-07:10 0.00 24220.48 31-JAN-13:20 0.00
February 26660.45 01-FEB-11:09 0.00 59042.44 19-FEB-07:10 0.00 24235.00 10-FEB-13:00 0.00
March 26660.45 01-MAR-11:09 0.00 46484.77 01-MAR-03:20 0.00 24187.11 01-MAR-13:20 0.00
April 26660.45 01-APR-10:09 0.00 46484.77 18-APR-02:30 0.00 23877.63 03-APR-12:39 0.00
May 26660.45 01-MAY-10:09 0.00 20402.29 18-MAY-06:10 0.00 23000.87 01-MAY-12:20 0.00
June 26660.45 01-JUN-10:09 0.00 6961.12 15-JUN-05:10 0.00 21936.81 01-JUN-12:20 0.00
July 26660.45 01-JUL-10:09 0.00 544.56 04-JUL-06:10 0.00 21437.13 01-JUL-12:20 0.00
August 26660.45 01-AUG-10:09 0.00 2100.34 15-AUG-02:09 0.00 21169.82 31-AUG-12:00 0.00
September 26660.45 01-SEP-10:09 0.00 10984.34 27-SEP-05:10 0.00 21524.84 30-SEP-12:39 0.00
October 26660.45 01-OCT-10:09 0.00 18299.60 16-OCT-06:00 0.00 22308.76 31-OCT-12:39 0.00
November 26660.45 01-NOV-10:09 0.00 46484.77 11-NOV-03:30 0.00 23124.93 30-NOV-13:00 0.00
December 26660.45 01-DEC-11:09 0.00 46484.77 01-DEC-03:30 0.00 24023.01 31-DEC-13:20 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 26660.45   0.00 544.56   0.00 21169.82   0.00
Maximum of Months 26660.45   0.00 59042.44   0.00 24235.00   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 22.83 19.84 0.00 19.84 0.00 19.84 0.00 19.84
February 24.67 19.65 0.00 19.65 0.00 19.65 0.00 19.65
March 16.00 20.09 0.00 20.09 0.00 20.09 0.00 20.09
April 5.33 20.19 0.00 20.19 0.00 20.19 0.00 20.19
May 0.67 20.40 0.00 20.40 0.00 20.40 0.00 20.40
June 0.00 0.00 0.00 0.00 0.33 24.47 0.00 24.47
July 0.00 0.00 0.00 0.00 1.33 24.55 0.00 24.55
August 0.00 0.00 0.00 0.00 5.33 24.60 0.00 24.60
September 0.00 0.00 0.00 0.00 0.50 24.46 0.00 24.46
October 2.00 20.49 0.00 20.49 0.00 20.49 0.00 20.49
November 13.00 19.91 0.00 19.91 0.00 19.91 0.00 19.91
December 24.33 19.88 0.00 19.88 0.00 19.88 0.00 19.88
                 
Annual Sum or Average 108.83 19.88 0.00 19.88 7.50 20.19 0.00 20.19
Minimum of Months 0.00 0.00 0.00 0.00 0.00 19.65 0.00 19.65
Maximum of Months 24.67 20.49 0.00 20.49 5.33 24.60 0.00 24.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.83 27.29 0.00 27.29
March 0.00 0.00 0.00 0.00 1.50 26.97 0.00 26.97
April 0.00 0.00 0.00 0.00 4.33 27.47 0.00 27.47
May 0.00 0.00 0.00 0.00 9.17 27.56 0.00 27.56
June 0.00 0.00 0.00 0.00 14.67 27.93 0.00 27.93
July 0.00 0.00 0.00 0.00 17.67 28.51 0.00 28.51
August 0.00 0.00 0.00 0.00 20.00 29.08 0.00 29.08
September 0.00 0.00 0.00 0.00 14.67 28.00 0.00 28.00
October 0.00 0.00 0.00 0.00 8.17 27.40 0.00 27.40
November 0.00 0.00 0.00 0.00 2.50 27.27 0.00 27.27
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   93.50 28.15 0.00 28.15
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 20.00 29.08 0.00 29.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 610.00 20.92 318.67 20.86 318.67 20.82
February 537.67 21.01 203.17 20.93 198.00 20.87
March 573.17 21.21 135.00 21.17 115.00 21.08
April 435.00 21.35 142.17 21.68 47.17 21.58
May 330.67 21.54 236.00 22.45 8.67 22.41
June 185.83 22.05 348.83 23.25 0.00 23.25
July 101.67 22.65 455.50 23.68 2.33 23.68
August 95.83 22.84 494.83 23.76 23.33 23.76
September 229.00 22.02 316.67 23.10 3.17 23.10
October 458.17 21.41 129.00 21.84 16.00 21.79
November 567.50 21.10 132.83 21.09 112.33 21.01
December 609.00 20.95 262.67 20.87 262.67 20.82
             
Annual Sum or Average 4733.50 21.29 3175.33 21.89 1107.33 21.75
Minimum of Months 95.83 20.92 129.00 20.86 0.00 20.82
Maximum of Months 610.00 22.84 494.83 23.76 318.67 23.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 610.00 18.80 291.33 18.72 291.33 18.68
February 525.17 19.00 239.67 18.97 224.83 18.88
March 572.83 19.26 204.00 19.25 176.83 19.10
April 474.50 20.08 189.67 20.67 111.00 20.66
May 397.00 21.35 274.67 22.56 113.33 22.89
June 363.50 24.03 414.00 24.55 234.17 24.87
July 389.67 25.50 525.83 25.37 347.50 25.55
August 425.17 25.69 557.17 25.51 394.67 25.66
September 342.50 23.58 389.33 24.23 191.67 24.57
October 456.67 20.17 158.50 20.97 51.17 21.04
November 548.83 19.27 159.33 19.32 135.50 19.23
December 609.00 18.85 239.00 18.75 239.00 18.69
             
Annual Sum or Average 5714.83 20.90 3642.50 21.67 2511.00 21.84
Minimum of Months 342.50 18.80 158.50 18.72 51.17 18.68
Maximum of Months 610.00 25.69 557.17 25.51 394.67 25.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 610.00000 20.92040 33.90306 -0.5647 12.56219
February 551.00000 21.07997 35.48140 -0.4468 10.94170
March 612.00000 21.36588 36.55078 -0.3046 8.92395
April 590.00000 21.98772 40.07306 -0.0561 8.48369
May 611.00000 22.58138 43.75383 -0.8272 25.27530
June 592.00000 23.28000 44.58735 -0.5221 14.55105
July 609.00000 23.67891 47.42338 -0.2965 9.37170
August 612.00000 23.74004 50.86276 -0.2398 8.70347
September 590.00000 23.12820 50.47059 -0.5398 16.16501
October 610.00000 21.99869 44.45033 -0.0333 7.82204
November 591.00000 21.20523 42.34144 -0.3535 9.29781
December 609.00000 20.95448 35.99509 -0.5207 11.66097
           
Annual Sum or Average 7187.00000 22.16668 42.18987 -0.3919 11.98766
Minimum of Months 551.00000 20.92040 33.90306 -0.8272 7.82204
Maximum of Months 612.00000 23.74004 50.86276 -0.0333 25.27530



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 610.00000 18.79978 40.69486 -0.6367 14.35796
February 551.00000 19.20866 41.81818 -0.5256 13.38208
March 612.00000 19.54598 43.15102 -0.4139 11.41361
April 590.00000 20.80384 45.70465 -0.0861 11.53962
May 611.00000 22.11327 47.78171 -0.6873 27.87157
June 592.00000 23.80642 46.23955 -0.1095 15.60281
July 609.00000 24.78123 47.55044 0.25068 13.25279
August 612.00000 25.03360 50.22261 0.35653 13.66529
September 590.00000 23.51310 51.76212 -0.1688 15.89768
October 610.00000 21.00275 49.20438 0.00253 10.10957
November 591.00000 19.53417 48.36780 -0.3773 11.35615
December 609.00000 18.84798 42.95811 -0.5999 13.42454
           
Annual Sum or Average 7187.00000 21.42935 46.30638 -0.2480 14.33969
Minimum of Months 551.00000 18.79978 40.69486 -0.6873 10.10957
Maximum of Months 612.00000 25.03360 51.76212 0.35653 27.87157



Table of Contents

Report: DXReportMonthly

For: PSZ-AC_1:1 COOLING COIL

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01
February 12662713.87 4098359.06 2.00 12662713.87 -0.0 0.00 0.22 27-FEB-15:00 0.00 01-FEB-00:02 3111.24 27-FEB-15:00 3111.24 27-FEB-15:00 0.00 27-FEB-15:53 990.96 27-FEB-15:00 0.00 01-FEB-00:02
March 33163414.70 10611067.62 4.17 33163281.76 132.94 0.00 0.27 18-MAR-16:00 0.00 01-MAR-00:02 3813.24 18-MAR-16:00 3813.24 18-MAR-16:00 0.22 08-MAR-16:10 1200.85 18-MAR-16:00 0.00 01-MAR-00:02
April 0.124488E+10 0.348017E+09 39.81 0.121751E+10 27368685.05 0.00 1.00 27-APR-13:00 0.00 01-APR-00:01 18044.54 27-APR-17:10 17262.70 27-APR-13:00 1068.44 27-APR-17:10 4669.56 27-APR-17:10 0.00 01-APR-00:01
May 0.211802E+10 0.612249E+09 79.12 0.194765E+10 0.170378E+09 0.00 0.87 06-MAY-13:00 0.00 01-MAY-00:01 14740.20 06-MAY-13:00 13956.87 15-MAY-17:10 2385.67 05-MAY-18:00 3921.39 06-MAY-13:00 0.00 01-MAY-00:01
June 0.359916E+10 0.103920E+10 153.52 0.347510E+10 0.124056E+09 0.00 1.00 28-JUN-17:03 0.00 01-JUN-00:01 18598.34 28-JUN-17:10 17689.45 28-JUN-17:03 1557.26 22-JUN-18:00 4814.55 28-JUN-17:10 0.00 01-JUN-00:01
July 0.868605E+10 0.240705E+10 261.13 0.773842E+10 0.947636E+09 0.00 1.00 20-JUL-02:61 0.00 01-JUL-00:01 34353.72 20-JUL-02:61 25646.63 20-JUL-02:61 14554.04 25-JUL-02:61 8939.49 20-JUL-02:61 0.00 01-JUL-00:01
August 0.120903E+11 0.327371E+10 301.21 0.106646E+11 0.142571E+10 0.00 1.00 07-AUG-02:61 0.00 01-AUG-00:01 34353.72 24-AUG-02:61 27979.57 15-AUG-02:62 14977.92 31-AUG-02:61 8939.49 07-AUG-02:61 0.00 01-AUG-00:01
September 0.347662E+10 0.980088E+09 122.70 0.297389E+10 0.502730E+09 0.00 1.00 12-SEP-02:61 0.00 01-SEP-00:01 34353.72 13-SEP-02:61 22647.32 13-SEP-02:61 14257.60 15-SEP-02:61 8939.49 12-SEP-02:61 0.00 01-SEP-00:01
October 0.227371E+09 68830318.60 16.27 0.225641E+09 1729950.93 0.00 0.60 04-OCT-15:05 0.00 01-OCT-00:01 9282.32 04-OCT-15:05 9282.32 04-OCT-15:05 401.99 08-OCT-13:55 2686.89 04-OCT-15:05 0.00 01-OCT-00:01
November 91587416.73 27786421.10 4.83 71502559.13 20084857.60 0.00 0.50 04-NOV-14:25 0.00 01-NOV-00:01 7475.64 04-NOV-14:25 6032.56 04-NOV-14:30 1520.85 04-NOV-13:00 2223.28 04-NOV-14:25 0.00 01-NOV-00:01
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01 0.00 01-DEC-00:01 0.00 01-DEC-00:01 0.00 01-DEC-00:01 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                                         
Annual Sum or Average 0.315799E+11 0.877164E+10 984.76 0.283602E+11 0.321969E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.120903E+11 0.327371E+10 301.21 0.106646E+11 0.142571E+10 0.00 1.00   0.00   34353.72   27979.57   14977.92   8939.49   0.00  



Table of Contents

Report: DXReportMonthly

For: PSZ-AC_2:2 COOLING COIL

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01 0.00 01-JAN-00:01
February 2653031.75 841856.22 0.88 1635389.07 1017642.68 0.00 0.66 28-FEB-05:01 0.00 01-FEB-00:02 7568.18 28-FEB-05:01 4827.74 28-FEB-05:01 2740.43 28-FEB-05:01 2154.17 28-FEB-05:01 0.00 01-FEB-00:02
March 1820104.37 598482.50 1.14 1105382.83 714721.54 0.00 0.19 10-MAR-04:58 0.00 01-MAR-00:02 1925.68 10-MAR-04:58 927.55 10-MAR-04:58 998.13 10-MAR-04:58 617.94 10-MAR-04:58 0.00 01-MAR-00:02
April 0.780672E+09 0.217172E+09 33.87 0.767954E+09 12718226.16 0.00 1.00 02-APR-02:61 0.00 01-APR-00:01 24927.50 27-APR-02:61 21686.11 02-APR-03:22 13014.09 30-APR-02:61 6486.61 02-APR-02:61 0.00 01-APR-00:01
May 0.138518E+10 0.398869E+09 76.44 0.124651E+10 0.138675E+09 0.00 1.00 04-MAY-02:61 0.00 01-MAY-00:01 24927.50 04-MAY-02:61 16628.31 05-MAY-03:22 12728.34 07-MAY-02:61 6486.61 04-MAY-02:61 0.00 01-MAY-00:01
June 0.258187E+10 0.738915E+09 141.74 0.245996E+10 0.121909E+09 0.00 1.00 01-JUN-02:61 0.00 01-JUN-00:01 24927.50 30-JUN-03:22 18545.80 10-JUN-02:61 12632.00 18-JUN-02:61 6486.61 01-JUN-02:61 0.00 01-JUN-00:01
July 0.673892E+10 0.184462E+10 250.30 0.607612E+10 0.662803E+09 0.00 1.00 01-JUL-02:61 0.00 01-JUL-00:01 24927.50 29-JUL-02:61 20033.03 24-JUL-14:05 12873.74 16-JUL-02:11 6486.61 01-JUL-02:61 0.00 01-JUL-00:01
August 0.968512E+10 0.258522E+10 295.85 0.882266E+10 0.862456E+09 0.00 1.00 01-AUG-02:11 0.00 01-AUG-00:01 24927.50 09-AUG-02:52 22096.14 10-AUG-16:53 13012.29 27-AUG-02:61 6486.61 01-AUG-02:11 0.00 01-AUG-00:01
September 0.211686E+10 0.600822E+09 103.69 0.176693E+10 0.349932E+09 0.00 1.00 01-SEP-02:61 0.00 01-SEP-00:01 24927.50 22-SEP-02:61 17228.08 05-SEP-02:61 14177.78 25-SEP-02:61 6486.61 01-SEP-02:61 0.00 01-SEP-00:01
October 84957996.20 26203554.54 10.54 77512680.02 7445316.18 0.00 1.00 01-OCT-02:61 0.00 01-OCT-00:01 24927.50 01-OCT-02:61 17563.18 05-OCT-02:61 10801.67 01-OCT-02:61 6486.61 01-OCT-02:61 0.00 01-OCT-00:01
November 39438172.36 12315093.77 5.66 28419083.77 11019088.59 0.00 1.00 05-NOV-02:61 0.00 01-NOV-00:01 24927.50 05-NOV-02:61 12680.54 05-NOV-02:61 12246.96 05-NOV-02:61 6486.61 05-NOV-02:61 0.00 01-NOV-00:01
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01 0.00 01-DEC-00:01 0.00 01-DEC-00:01 0.00 01-DEC-00:01 0.00 01-DEC-00:01 0.00 01-DEC-00:01
                                         
Annual Sum or Average 0.234175E+11 0.642558E+10 920.12 0.212488E+11 0.216869E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.968512E+10 0.258522E+10 295.85 0.882266E+10 0.862456E+09 0.00 1.00   0.00   24927.50   22096.14   14177.78   6486.61   0.00  



Table of Contents

Report: WindowReportMonthly

For: DINING_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.37 26.46 77.91 26.63 498.47 0.00 0.00 0.00
February 191.51 67.97 123.54 101.73 430.64 0.00 0.00 0.00
March 285.95 103.51 182.43 208.32 345.36 0.00 0.00 0.00
April 443.26 184.18 259.08 412.73 270.97 0.00 0.00 0.00
May 471.67 163.99 307.68 462.46 230.82 0.00 0.00 0.00
June 564.88 245.78 319.10 602.32 190.37 0.00 0.00 0.00
July 526.04 236.11 289.92 583.89 175.42 0.00 0.00 0.00
August 517.02 258.64 258.38 596.86 173.86 0.00 0.00 0.00
September 382.26 176.30 205.96 380.20 239.76 0.00 0.00 0.00
October 249.16 105.87 143.29 196.56 317.89 0.00 0.00 0.00
November 122.12 34.48 87.65 51.01 399.70 0.00 0.00 0.00
December 100.17 32.25 67.92 36.46 497.62 0.00 0.00 0.00
                 
Annual Sum or Average 330.48 136.60 193.88 305.98 313.71 0.00 0.00 0.00
Minimum of Months 100.17 26.46 67.92 26.63 173.86 0.00 0.00 0.00
Maximum of Months 564.88 258.64 319.10 602.32 498.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 574.00 340.84 233.16 462.41 920.49 0.00 0.00 0.00
February 882.72 546.42 336.31 833.42 805.08 0.00 0.00 0.00
March 949.55 506.39 443.17 949.43 692.45 0.00 0.00 0.00
April 1002.55 435.30 567.25 1055.30 583.53 0.00 0.00 0.00
May 916.70 273.09 643.61 961.49 492.86 0.00 0.00 0.00
June 838.69 225.18 613.51 881.38 412.48 0.00 0.00 0.00
July 914.63 334.99 579.65 1085.44 384.80 0.00 0.00 0.00
August 982.66 458.23 524.43 1223.04 379.73 0.00 0.00 0.00
September 1088.74 601.24 487.50 1276.21 493.79 0.00 0.00 0.00
October 986.22 608.92 377.30 1055.43 628.10 0.00 0.00 0.00
November 583.08 334.16 248.93 514.41 755.11 0.00 0.00 0.00
December 610.07 394.80 215.27 556.89 932.53 0.00 0.00 0.00
                 
Annual Sum or Average 860.43 420.85 439.58 904.86 622.60 0.00 0.00 0.00
Minimum of Months 574.00 225.18 215.27 462.41 379.73 0.00 0.00 0.00
Maximum of Months 1088.74 608.92 643.61 1276.21 932.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.09 32.46 77.63 34.98 500.09 0.00 0.00 0.00
February 197.38 74.18 123.20 114.47 432.27 0.00 0.00 0.00
March 276.58 93.35 183.23 199.37 348.97 0.00 0.00 0.00
April 420.79 160.88 259.90 382.40 283.54 0.00 0.00 0.00
May 541.45 219.96 321.49 553.62 236.27 0.00 0.00 0.00
June 520.73 202.18 318.55 537.59 196.79 0.00 0.00 0.00
July 643.29 338.15 305.14 749.76 183.35 0.00 0.00 0.00
August 532.16 271.73 260.42 625.32 185.03 0.00 0.00 0.00
September 433.36 207.94 225.42 458.69 245.12 0.00 0.00 0.00
October 246.71 100.52 146.19 193.41 322.06 0.00 0.00 0.00
November 122.86 34.65 88.21 53.03 397.65 0.00 0.00 0.00
December 103.29 35.39 67.89 44.75 497.74 0.00 0.00 0.00
                 
Annual Sum or Average 346.63 148.18 198.45 330.39 318.56 0.00 0.00 0.00
Minimum of Months 103.29 32.46 67.89 34.98 183.35 0.00 0.00 0.00
Maximum of Months 643.29 338.15 321.49 749.76 500.09 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.279554E+09 70876071.01 0.208678E+09 71317699.58 0.133510E+10
February 0.463313E+09 0.164439E+09 0.298873E+09 0.246096E+09 0.104181E+10
March 0.765876E+09 0.277253E+09 0.488622E+09 0.557964E+09 0.925018E+09
April 0.114894E+10 0.477401E+09 0.671539E+09 0.106981E+10 0.702353E+09
May 0.126333E+10 0.439230E+09 0.824098E+09 0.123866E+10 0.618230E+09
June 0.146417E+10 0.637071E+09 0.827101E+09 0.156120E+10 0.493447E+09
July 0.140893E+10 0.632410E+09 0.776523E+09 0.156389E+10 0.469845E+09
August 0.138478E+10 0.692748E+09 0.692036E+09 0.159862E+10 0.465677E+09
September 0.990818E+09 0.456973E+09 0.533844E+09 0.985479E+09 0.621460E+09
October 0.667341E+09 0.283557E+09 0.383784E+09 0.526464E+09 0.851433E+09
November 0.316542E+09 89362933.45 0.227179E+09 0.132223E+09 0.103602E+10
December 0.268290E+09 86370492.69 0.181920E+09 97660528.46 0.133283E+10
           
Annual Sum or Average 0.104219E+11 0.430769E+10 0.611420E+10 0.964939E+10 0.989323E+10
Minimum of Months 0.268290E+09 70876071.01 0.181920E+09 71317699.58 0.465677E+09
Maximum of Months 0.146417E+10 0.692748E+09 0.827101E+09 0.159862E+10 0.133510E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.153740E+10 0.912913E+09 0.624484E+09 0.123851E+10 0.246545E+10
February 0.213548E+10 0.132189E+10 0.813589E+09 0.201621E+10 0.194766E+10
March 0.254328E+10 0.135631E+10 0.118698E+10 0.254295E+10 0.185467E+10
April 0.259861E+10 0.112830E+10 0.147031E+10 0.273535E+10 0.151251E+10
May 0.245530E+10 0.731457E+09 0.172384E+10 0.257525E+10 0.132009E+10
June 0.217389E+10 0.583662E+09 0.159023E+10 0.228454E+10 0.106915E+10
July 0.244975E+10 0.897228E+09 0.155252E+10 0.290725E+10 0.103065E+10
August 0.263195E+10 0.122732E+10 0.140463E+10 0.327579E+10 0.101706E+10
September 0.282202E+10 0.155841E+10 0.126361E+10 0.330793E+10 0.127991E+10
October 0.264148E+10 0.163092E+10 0.101056E+10 0.282686E+10 0.168231E+10
November 0.151135E+10 0.866132E+09 0.645221E+09 0.133336E+10 0.195725E+10
December 0.163402E+10 0.105744E+10 0.576581E+09 0.149157E+10 0.249768E+10
           
Annual Sum or Average 0.271345E+11 0.132720E+11 0.138625E+11 0.285356E+11 0.196344E+11
Minimum of Months 0.151135E+10 0.583662E+09 0.576581E+09 0.123851E+10 0.101706E+10
Maximum of Months 0.282202E+10 0.163092E+10 0.172384E+10 0.330793E+10 0.249768E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294861E+09 86949057.02 0.207912E+09 93680025.05 0.133944E+10
February 0.477502E+09 0.179458E+09 0.298043E+09 0.276917E+09 0.104575E+10
March 0.740791E+09 0.250037E+09 0.490754E+09 0.533998E+09 0.934695E+09
April 0.109068E+10 0.417008E+09 0.673670E+09 0.991180E+09 0.734937E+09
May 0.145023E+10 0.589150E+09 0.861081E+09 0.148283E+10 0.632837E+09
June 0.134973E+10 0.524056E+09 0.825677E+09 0.139342E+10 0.510088E+09
July 0.172299E+10 0.905692E+09 0.817300E+09 0.200817E+10 0.491097E+09
August 0.142533E+10 0.727812E+09 0.697514E+09 0.167486E+10 0.495591E+09
September 0.112327E+10 0.538968E+09 0.584300E+09 0.118892E+10 0.635351E+09
October 0.660796E+09 0.269243E+09 0.391554E+09 0.518018E+09 0.862601E+09
November 0.318457E+09 89818143.59 0.228639E+09 0.137466E+09 0.103071E+10
December 0.276649E+09 94800556.64 0.181849E+09 0.119867E+09 0.133316E+10
           
Annual Sum or Average 0.109313E+11 0.467299E+10 0.625829E+10 0.104193E+11 0.100463E+11
Minimum of Months 0.276649E+09 86949057.02 0.181849E+09 93680025.05 0.491097E+09
Maximum of Months 0.172299E+10 0.905692E+09 0.861081E+09 0.200817E+10 0.133944E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 470.09 1865.13 788.46 399.77 388.69 0.00 0.00
February 996.32 1614.70 1271.62 688.57 583.05 0.00 0.00
March 1321.88 1351.55 1512.08 703.25 808.82 0.00 0.00
April 1803.36 1090.96 1866.60 780.37 1086.23 0.00 0.00
May 1941.26 923.64 1929.83 657.05 1272.78 0.00 0.00
June 1986.18 764.55 1924.30 673.14 1251.16 0.00 0.00
July 2380.07 704.55 2083.96 909.25 1174.71 0.00 0.00
August 2405.74 699.14 2031.83 988.61 1043.23 0.00 0.00
September 2084.27 947.85 1904.36 985.48 918.89 0.00 0.00
October 1418.82 1241.47 1482.09 815.31 666.78 0.00 0.00
November 585.76 1519.76 828.07 403.28 424.78 0.00 0.00
December 586.79 1876.58 813.53 462.44 351.09 0.00 0.00
               
Annual Sum or Average 1501.23 1214.87 1537.53 705.63 831.91 0.00 0.00
Minimum of Months 470.09 699.14 788.46 399.77 351.09 0.00 0.00
Maximum of Months 2405.74 1876.58 2083.96 988.61 1272.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.125909E+10 0.499557E+10 0.211181E+10 0.107074E+10 0.104107E+10 0.00 0.00
February 0.241029E+10 0.390629E+10 0.307629E+10 0.166579E+10 0.141051E+10 0.00 0.00
March 0.354051E+10 0.361998E+10 0.404995E+10 0.188360E+10 0.216636E+10 0.00 0.00
April 0.467431E+10 0.282778E+10 0.483822E+10 0.202271E+10 0.281552E+10 0.00 0.00
May 0.519947E+10 0.247389E+10 0.516885E+10 0.175984E+10 0.340902E+10 0.00 0.00
June 0.514818E+10 0.198170E+10 0.498780E+10 0.174479E+10 0.324301E+10 0.00 0.00
July 0.637478E+10 0.188707E+10 0.558167E+10 0.243533E+10 0.314634E+10 0.00 0.00
August 0.644354E+10 0.187259E+10 0.544206E+10 0.264788E+10 0.279418E+10 0.00 0.00
September 0.540244E+10 0.245682E+10 0.493611E+10 0.255435E+10 0.238175E+10 0.00 0.00
October 0.380016E+10 0.332516E+10 0.396962E+10 0.218372E+10 0.178590E+10 0.00 0.00
November 0.151830E+10 0.393923E+10 0.214635E+10 0.104531E+10 0.110104E+10 0.00 0.00
December 0.157165E+10 0.502622E+10 0.217896E+10 0.123861E+10 0.940349E+09 0.00 0.00
               
Annual Sum or Average 0.473427E+11 0.383123E+11 0.484877E+11 0.222527E+11 0.262350E+11 0.00 0.00
Minimum of Months 0.125909E+10 0.187259E+10 0.211181E+10 0.104531E+10 0.940349E+09 0.00 0.00
Maximum of Months 0.644354E+10 0.502622E+10 0.558167E+10 0.264788E+10 0.340902E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.50 3.10 1.22 3.91 -4.2 29.50 44.23 0.00
February 5.82 4.07 1.77 3.94 -3.8 43.80 82.64 0.00
March 8.33 5.86 2.94 3.85 -1.4 65.55 100.60 0.02
April 10.85 8.04 5.25 4.23 1.22 89.73 150.02 0.00
May 12.97 10.02 7.49 3.85 3.75 114.98 168.60 0.00
June 15.59 11.80 8.88 4.02 5.93 107.53 199.74 0.01
July 17.66 13.41 10.38 3.76 8.02 92.25 247.81 0.00
August 18.80 14.57 11.86 3.84 8.90 79.20 215.47 0.01
September 15.09 12.55 10.74 2.23 5.47 68.06 162.11 0.01
October 11.43 9.19 7.19 4.02 2.10 48.18 106.36 0.04
November 8.07 6.72 5.29 3.86 0.13 33.26 46.10 0.00
December 5.42 4.09 2.46 3.51 -3.8 24.03 50.49 0.04
                 
Annual Sum or Average 11.24 8.64 6.31 3.75 1.89 66.43 131.49 0.01
Minimum of Months 4.50 3.10 1.22 2.23 -4.2 24.03 44.23 0.00
Maximum of Months 18.80 14.57 11.86 4.23 8.90 114.98 247.81 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.40 11-JAN-14:20 10.49 7.20 8.40 3.89 99.17 130.33
February 20.00 27-FEB-14:00 12.17 5.60 2.60 5.54 87.00 691.00
March 20.60 18-MAR-15:00 10.43 0.00 6.20 6.55 111.50 465.50
April 27.20 27-APR-15:09 17.22 11.02 4.10 12.63 151.33 598.33
May 25.00 05-MAY-15:00 17.36 12.80 2.60 18.99 208.50 29.50
June 26.70 28-JUN-16:00 16.74 10.60 3.10 11.84 131.50 527.00
July 30.60 24-JUL-14:00 18.78 12.20 3.10 20.75 267.00 383.50
August 31.80 10-AUG-16:00 18.70 11.10 2.60 16.85 50.50 750.50
September 25.00 14-SEP-16:00 16.69 11.70 3.10 13.54 100.50 235.00
October 21.70 04-OCT-14:00 11.49 1.70 5.20 4.92 56.50 783.50
November 21.10 04-NOV-13:00 15.94 12.80 0.00 6.95 52.50 729.00
December 13.30 14-DEC-11:00 8.44 3.60 13.90 5.33 127.50 85.00
                 
Annual Sum or Average                
Minimum of Months 13.30   8.44 0.00 0.00 3.89 50.50 29.50
Maximum of Months 31.80   18.78 12.80 13.90 20.75 267.00 783.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -3.9 07-JAN-07:00 -3.9 -3.9 2.10 -14.4 0.00 0.00
February -5.6 19-FEB-05:10 -6.1 -7.3 3.77 -22.8 0.00 0.00
March -0.6 01-MAR-06:00 -2.0 -3.9 1.50 -17.3 16.50 102.00
April 1.70 19-APR-04:00 1.21 0.60 3.10 -11.9 0.00 0.00
May 4.40 11-MAY-02:00 3.92 3.30 3.10 -10.9 0.00 0.00
June 8.30 15-JUN-02:00 7.50 6.70 3.10 -3.2 0.00 0.00
July 11.10 03-JUL-03:00 8.19 5.00 2.60 5.54 0.00 0.00
August 11.00 06-AUG-04:00 10.57 10.20 2.60 -3.2 11.00 135.50
September 7.20 27-SEP-04:49 6.72 6.20 0.25 -4.0 0.00 0.00
October 5.60 13-OCT-04:00 4.51 3.30 2.10 -8.5 0.00 0.00
November 0.00 11-NOV-06:00 -0.2 -0.6 2.10 -16.0 0.00 0.00
December -1.7 26-DEC-06:00 -1.7 -1.7 2.10 -15.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -6.1 -7.3 0.25 -22.8 0.00 0.00
Maximum of Months 11.10   10.57 10.20 3.77 5.54 16.50 135.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.49 11-JAN-13:00 14.40 7.20 8.20 2.85 105.50 249.00
February 12.42 27-FEB-15:00 19.40 6.70 2.60 6.35 88.00 342.50
March 12.45 09-MAR-11:00 17.20 8.90 2.10 12.41 178.00 40.00
April 17.29 27-APR-14:00 27.20 11.10 4.10 12.41 147.50 646.00
May 17.58 06-MAY-12:00 23.90 13.90 5.20 15.57 365.50 282.50
June 16.74 28-JUN-16:00 26.70 10.60 3.10 11.84 131.50 527.00
July 19.18 31-JUL-15:00 28.90 13.90 4.10 14.65 45.00 848.50
August 20.13 29-AUG-12:00 28.90 15.70 2.60 17.39 136.50 655.00
September 17.97 23-SEP-13:00 23.30 15.00 2.10 9.72 148.00 670.50
October 15.15 01-OCT-11:00 17.20 13.90 4.60 13.73 236.50 63.50
November 16.05 04-NOV-12:00 20.60 13.30 0.00 7.95 62.00 746.50
December 10.71 16-DEC-11:00 11.70 10.00 6.70 7.35 89.50 0.00
                 
Annual Sum or Average                
Minimum of Months 10.49   11.70 6.70 0.00 2.85 45.00 0.00
Maximum of Months 20.13   28.90 15.70 8.20 17.39 365.50 848.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.00 11-JAN-21:00 11.10 10.49 4.60 6.75 0.00 0.00
February 11.70 24-FEB-00:00 12.80 12.15 4.10 8.74 0.00 0.00
March 11.70 09-MAR-16:00 12.80 12.15 2.10 8.74 37.50 0.00
April 12.80 28-APR-12:00 16.70 14.35 4.10 8.35 265.50 596.00
May 13.90 05-MAY-16:00 22.80 17.10 2.60 19.17 111.50 27.50
June 13.90 12-JUN-12:00 16.70 15.00 3.60 13.16 263.50 0.00
July 15.00 11-JUL-09:20 16.13 15.49 4.60 12.91 204.17 28.17
August 16.40 30-AUG-07:00 17.40 16.77 5.20 12.41 168.50 34.50
September 15.00 14-SEP-11:20 20.37 16.93 2.10 6.89 152.83 748.17
October 13.90 01-OCT-10:00 16.70 15.01 4.10 13.16 184.50 0.00
November 13.90 03-NOV-19:00 15.00 14.31 4.60 11.46 0.00 0.00
December 10.00 16-DEC-10:00 11.10 10.48 7.70 6.75 81.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.00   11.10 10.48 2.10 6.75 0.00 0.00
Maximum of Months 16.40   22.80 17.10 7.70 19.17 265.50 748.17



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.48 8.35 0.00
February 18.00 13.00 16.00 11.14 14.81 0.00
March 18.00 13.00 16.00 11.69 23.26 0.00
April 18.00 13.00 16.00 12.99 36.00 0.00
May 18.00 13.00 16.00 14.72 45.46 0.00
June 18.00 13.00 16.00 16.40 49.26 0.00
July 18.00 13.00 16.00 17.58 51.50 0.00
August 18.00 13.00 16.00 17.95 42.11 0.00
September 18.00 13.00 16.00 17.39 30.76 0.00
October 18.00 13.00 16.00 16.06 18.91 0.00
November 18.00 13.00 16.00 14.32 9.65 0.00
December 18.00 13.00 16.00 12.65 7.39 0.00
             
Annual Sum or Average 18.00 13.00 16.00 14.55 28.19 0.00
Minimum of Months 18.00 13.00 16.00 11.14 7.39 0.00
Maximum of Months 18.00 13.00 16.00 17.95 51.50 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.141892E+11 -0.133681E+11 0.00 0.00 744.00 0.00 -821101069.2 60.05 0.00 0.00
February 0.128915E+11 -0.121570E+11 0.00 0.00 672.00 0.00 -734549889.8 60.05 0.00 0.00
March 0.141430E+11 -0.133378E+11 0.00 0.00 744.00 0.00 -805203202.7 60.05 0.00 0.00
April 0.132834E+11 -0.125275E+11 0.00 0.00 720.00 0.00 -755830439.8 60.05 0.00 0.00
May 0.132431E+11 -0.124876E+11 0.00 0.00 744.00 0.00 -755434599.6 60.05 0.00 0.00
June 0.123436E+11 -0.116439E+11 0.00 0.00 720.00 0.00 -699708994.7 60.05 0.00 0.00
July 0.123772E+11 -0.116725E+11 0.00 0.00 744.00 0.00 -704666223.7 60.05 0.00 0.00
August 0.123087E+11 -0.116090E+11 0.00 0.00 744.00 0.00 -699647806.3 60.05 0.00 0.00
September 0.120609E+11 -0.113567E+11 0.00 0.00 720.00 0.00 -704248809.4 60.05 0.00 0.00
October 0.128812E+11 -0.121060E+11 0.00 0.00 744.00 0.00 -775119143.6 60.05 0.00 0.00
November 0.129645E+11 -0.121861E+11 0.00 0.00 720.00 0.00 -778429654.1 60.05 0.00 0.00
December 0.138489E+11 -0.130295E+11 0.00 0.00 744.00 0.00 -819388632.7 60.05 0.00 0.00
                     
Annual Sum or Average 0.156535E+12 -0.147482E+12 0.00 0.00 8760.00 0.00 -0.905333E+10 60.05 0.00 0.00
Minimum of Months 0.120609E+11 -0.133681E+11 0.00 0.00 672.00 0.00 -821101069.2 60.05 0.00 0.00
Maximum of Months 0.141892E+11 -0.113567E+11 0.00 0.00 744.00 0.00 -699647806.3 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 237.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 259.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 247.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 379.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 427.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 375.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 471.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 366.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 301.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 245.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 242.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 160.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 3714.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 160.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 471.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_1:1 HEATING COIL

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.202964E+11 37187.81 01-JAN-03:01 0.00 0.00 0.00 0.00 0.00
February 0.150044E+11 37187.81 06-FEB-03:08 0.00 0.00 0.00 0.00 0.00
March 0.931829E+10 37187.81 01-MAR-03:10 0.00 0.00 0.00 0.00 0.00
April 0.448887E+10 37187.81 18-APR-02:08 0.00 0.00 0.00 0.00 0.00
May 0.161792E+10 23664.94 11-MAY-02:63 0.00 0.00 0.00 0.00 0.00
June 0.151141E+09 3640.16 15-JUN-04:01 0.00 0.00 0.00 0.00 0.00
July 1973513.66 435.64 04-JUL-06:10 0.00 0.00 0.00 0.00 0.00
August 2081208.57 10081.65 15-AUG-02:03 0.00 0.00 0.00 0.00 0.00
September 0.219346E+09 8603.94 27-SEP-04:04 0.00 0.00 0.00 0.00 0.00
October 0.263605E+10 16641.84 31-OCT-02:62 0.00 0.00 0.00 0.00 0.00
November 0.108118E+11 37187.81 10-NOV-03:08 0.00 0.00 0.00 0.00 0.00
December 0.184937E+11 37187.81 01-DEC-03:08 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.830419E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1973513.66 435.64   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.202964E+11 37187.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_2:2 HEATING COIL

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.182097E+11 34060.85 07-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.135110E+11 32995.16 19-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.709516E+10 20883.54 01-MAR-05:04 0.00 0.00 0.00 0.00 0.00
April 0.324382E+10 18670.30 12-APR-04:04 0.00 0.00 0.00 0.00 0.00
May 0.102899E+10 14372.80 11-MAY-04:15 0.00 0.00 0.00 0.00 0.00
June 30019695.24 4419.36 15-JUN-04:07 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:01 0.00 0.00 0.00 0.00 0.00
September 79847041.57 5408.74 27-SEP-04:15 0.00 0.00 0.00 0.00 0.00
October 0.143186E+10 8782.27 30-OCT-04:15 0.00 0.00 0.00 0.00 0.00
November 0.809364E+10 19279.76 11-NOV-05:20 0.00 0.00 0.00 0.00 0.00
December 0.149249E+11 22140.33 12-DEC-05:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.676489E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.182097E+11 34060.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_1:1 COOLING COIL

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 0.00
February 0.00 0.00 12662713.87 12662713.87 3111.24 27-FEB-15:00 3111.24 0.00
March 0.00 0.00 33163414.70 33163281.76 3813.24 18-MAR-16:00 3813.24 0.00
April 0.00 0.00 0.124488E+10 0.121751E+10 18044.54 27-APR-17:10 16976.10 0.00
May 0.00 0.00 0.211802E+10 0.194765E+10 14740.20 06-MAY-13:00 12379.65 0.00
June 0.00 0.00 0.359916E+10 0.347510E+10 18598.34 28-JUN-17:10 17689.01 0.00
July 0.00 0.00 0.868605E+10 0.773842E+10 34353.72 20-JUL-02:61 25646.63 0.00
August 0.00 0.00 0.120903E+11 0.106646E+11 34353.72 24-AUG-02:61 22536.11 0.00
September 0.00 0.00 0.347662E+10 0.297389E+10 34353.72 13-SEP-02:61 22647.32 0.00
October 0.00 0.00 0.227371E+09 0.225641E+09 9282.32 04-OCT-15:05 9282.32 0.00
November 0.00 0.00 91587416.73 71502559.13 7475.64 04-NOV-14:25 6032.27 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.315799E+11 0.283602E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.120903E+11 0.106646E+11 34353.72   25646.63 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_2:2 COOLING COIL

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 0.00
February 0.00 0.00 2653031.75 1635389.07 7568.18 28-FEB-05:01 4827.74 0.00
March 0.00 0.00 1820104.37 1105382.83 1925.68 10-MAR-04:58 927.55 0.00
April 0.00 0.00 0.780672E+09 0.767954E+09 24927.50 27-APR-02:61 17451.37 0.00
May 0.00 0.00 0.138518E+10 0.124651E+10 24927.50 04-MAY-02:61 14452.54 0.00
June 0.00 0.00 0.258187E+10 0.245996E+10 24927.50 30-JUN-03:22 14964.40 0.00
July 0.00 0.00 0.673892E+10 0.607612E+10 24927.50 29-JUL-02:61 13390.51 0.00
August 0.00 0.00 0.968512E+10 0.882266E+10 24927.50 09-AUG-02:52 16391.85 0.00
September 0.00 0.00 0.211686E+10 0.176693E+10 24927.50 22-SEP-02:61 11768.59 0.00
October 0.00 0.00 84957996.20 77512680.02 24927.50 01-OCT-02:61 14125.83 0.00
November 0.00 0.00 39438172.36 28419083.77 24927.50 05-NOV-02:61 12680.54 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.234175E+11 0.212488E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.968512E+10 0.882266E+10 24927.50   17451.37 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 4973.22 19219.58 31-JAN-13:47
February 0.00 0.00 01-FEB-00:02 5007.42 19243.18 11-FEB-13:50
March 0.00 0.00 01-MAR-00:02 4961.73 19176.37 01-MAR-13:50
April 0.00 0.00 01-APR-00:01 4814.97 18779.17 01-APR-12:40
May 0.00 0.00 01-MAY-00:01 4643.77 18152.29 01-MAY-12:42
June 0.00 0.00 01-JUN-00:01 4473.44 17432.09 01-JUN-12:55
July 0.00 0.00 01-JUL-00:01 4339.30 16849.99 01-JUL-12:20
August 0.00 0.00 01-AUG-00:01 4315.41 16572.15 31-AUG-12:57
September 0.00 0.00 01-SEP-00:01 4362.68 16953.90 30-SEP-12:55
October 0.00 0.00 01-OCT-00:01 4501.20 17597.14 31-OCT-13:00
November 0.00 0.00 01-NOV-00:01 4682.91 18295.29 30-NOV-13:50
December 0.00 0.00 01-DEC-00:01 4846.57 18900.47 31-DEC-14:00
             
Annual Sum or Average 0.00     4658.20    
Minimum of Months 0.00 0.00   4315.41 16572.15  
Maximum of Months 0.00 0.00   5007.42 19243.18  



Table of Contents

Report: FanReportMonthly

For: DINING EXHAUST FAN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:01 0.00
February 0.00 -0.0 0.00 01-FEB-00:02 0.00
March 0.00 -0.0 0.00 01-MAR-00:02 -0.0
April 0.00 0.00 0.00 01-APR-00:01 0.00
May 0.00 0.00 0.00 01-MAY-00:01 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 -0.0 0.00 01-JUL-00:01 0.00
August 0.00 -0.0 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:01 0.00
October 0.00 -0.0 0.00 01-OCT-00:01 0.00
November 0.00 -0.0 0.00 01-NOV-00:01 0.00
December 0.00 -0.0 0.00 01-DEC-00:01 -0.0
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN EXHAUST FAN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:01 0.00
February 0.00 0.00 0.00 01-FEB-00:02 0.00
March 0.00 0.00 0.00 01-MAR-00:02 0.00
April 0.00 -0.0 0.00 01-APR-00:01 0.00
May 0.00 0.00 0.00 01-MAY-00:01 0.00
June 0.00 -0.0 0.00 01-JUN-00:01 0.00
July 0.00 0.00 0.00 01-JUL-00:01 0.00
August 0.00 0.00 0.00 01-AUG-00:01 0.00
September 0.00 0.00 0.00 01-SEP-00:01 0.00
October 0.00 0.00 0.00 01-OCT-00:01 0.00
November 0.00 0.00 0.00 01-NOV-00:01 0.00
December 0.00 0.00 0.00 01-DEC-00:01 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: PSZ-AC_1:1_ADDAQ FAN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.709509E+10 1.23 3060.55 01-JAN-05:10 1.38
February 0.642628E+10 1.22 3060.55 26-FEB-18:45 1.38
March 0.700119E+10 1.22 3060.55 27-MAR-11:40 1.38
April 0.668518E+10 1.19 3060.55 06-APR-18:30 1.38
May 0.684220E+10 1.16 3060.55 01-MAY-08:40 1.37
June 0.661307E+10 1.15 3060.55 14-JUN-07:50 1.37
July 0.684506E+10 1.18 3060.55 01-JUL-12:42 1.37
August 0.686538E+10 1.18 3060.55 01-AUG-15:00 1.37
September 0.661856E+10 1.17 3060.55 07-SEP-17:20 1.37
October 0.684450E+10 1.17 3060.55 22-OCT-12:35 1.38
November 0.675984E+10 1.21 3060.55 18-NOV-11:00 1.37
December 0.713636E+10 1.23 3060.55 01-DEC-06:20 1.38
           
Annual Sum or Average 0.817327E+11 1.19      
Minimum of Months 0.642628E+10 1.15 3060.55   1.37
Maximum of Months 0.713636E+10 1.23 3060.55   1.38



Table of Contents

Report: FanReportMonthly

For: PSZ-AC_2:2_ADDAQ FAN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.508357E+10 1.15 2277.58 01-JAN-00:18 1.38
February 0.459412E+10 1.16 2277.58 01-FEB-18:35 1.38
March 0.508665E+10 1.16 2277.58 01-MAR-05:30 1.39
April 0.493147E+10 1.17 2277.58 01-APR-16:55 1.38
May 0.511187E+10 1.20 2277.58 02-MAY-04:01 1.38
June 0.497574E+10 1.22 2277.58 02-JUN-14:28 1.38
July 0.517120E+10 1.24 2277.58 01-JUL-12:36 1.37
August 0.519917E+10 1.26 2277.58 01-AUG-15:20 1.37
September 0.498274E+10 1.23 2277.58 02-SEP-14:12 1.37
October 0.510494E+10 1.19 2277.58 02-OCT-06:00 1.38
November 0.492679E+10 1.17 2277.58 02-NOV-04:30 1.38
December 0.508380E+10 1.15 2277.58 01-DEC-00:10 1.38
           
Annual Sum or Average 0.602521E+11 1.19      
Minimum of Months 0.459412E+10 1.15 2277.58   1.37
Maximum of Months 0.519917E+10 1.26 2277.58   1.39



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.79 0.24 0.00 01-JAN-07:10 0.00 0.00 51.49 0.10
February 0.72 0.22 0.00 01-FEB-06:10 0.00 0.00 52.72 0.10
March 0.80 0.24 0.00 01-MAR-06:10 0.00 0.00 52.74 0.10
April 0.77 0.23 0.00 01-APR-06:10 0.00 0.00 52.89 0.10
May 0.80 0.24 0.00 01-MAY-05:10 0.00 0.00 51.83 0.10
June 0.77 0.23 0.00 01-JUN-05:10 0.00 0.00 53.40 0.10
July 0.79 0.24 0.00 01-JUL-06:03 0.00 0.00 53.61 0.10
August 0.80 0.24 0.00 01-AUG-05:10 0.00 0.00 53.74 0.10
September 0.77 0.23 0.00 01-SEP-05:10 0.00 0.00 53.72 0.10
October 0.79 0.24 0.00 01-OCT-06:10 0.00 0.00 52.36 0.10
November 0.77 0.23 0.00 01-NOV-05:10 0.00 0.00 53.33 0.10
December 0.79 0.24 0.00 01-DEC-06:10 0.00 0.00 53.06 0.10
                 
Annual Sum or Average 9.37 2.81            
Minimum of Months 0.72 0.22 0.00   0.00 0.00 51.49 0.10
Maximum of Months 0.80 0.24 0.00   0.00 0.00 53.74 0.10



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 39.37 39.37 4973.22 19219.58 31-JAN-13:47
February 0.00 0.00 01-FEB-00:02 52.72 52.72 5007.42 19243.18 11-FEB-13:50
March 0.00 0.00 01-MAR-00:02 52.74 52.74 4961.73 19176.37 01-MAR-13:50
April 0.00 0.00 01-APR-00:01 52.88 52.88 4814.97 18779.17 01-APR-12:40
May 0.00 0.00 01-MAY-00:01 40.17 40.17 4643.77 18152.29 01-MAY-12:42
June 0.00 0.00 01-JUN-00:01 53.39 53.39 4473.44 17432.09 01-JUN-12:55
July 0.00 0.00 01-JUL-00:01 53.61 53.61 4339.30 16849.99 01-JUL-12:20
August 0.00 0.00 01-AUG-00:01 53.74 53.74 4315.41 16572.15 31-AUG-12:57
September 0.00 0.00 01-SEP-00:01 53.72 53.72 4362.68 16953.90 30-SEP-12:55
October 0.00 0.00 01-OCT-00:01 41.50 41.50 4501.20 17597.14 31-OCT-13:00
November 0.00 0.00 01-NOV-00:01 53.33 53.33 4682.91 18295.29 30-NOV-13:50
December 0.00 0.00 01-DEC-00:01 53.07 53.07 4846.57 18900.47 31-DEC-14:00
                 
Annual Sum or Average 0.00         4658.20    
Minimum of Months 0.00 0.00   39.37 39.37 4315.41 16572.15  
Maximum of Months 0.00 0.00   53.74 53.74 5007.42 19243.18  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC_1:1

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.709509E+10 0.00 0.00
February 0.00 0.00 0.00 0.643038E+10 0.00 0.00
March 0.00 0.00 0.00 0.701180E+10 0.00 0.00
April 0.00 0.00 0.00 0.703320E+10 0.00 0.00
May 0.00 0.00 0.00 0.745444E+10 0.00 0.00
June 0.00 0.00 0.00 0.765226E+10 0.00 0.00
July 0.00 0.00 0.00 0.925212E+10 0.00 0.00
August 0.00 0.00 0.00 0.101391E+11 0.00 0.00
September 0.00 0.00 0.00 0.759865E+10 0.00 0.00
October 0.00 0.00 0.00 0.691333E+10 0.00 0.00
November 0.00 0.00 0.00 0.678763E+10 0.00 0.00
December 0.00 0.00 0.00 0.713636E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.905043E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.643038E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.101391E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC_2:2

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.508357E+10 0.00 0.00
February 0.00 0.00 0.00 0.459496E+10 0.00 0.00
March 0.00 0.00 0.00 0.508725E+10 0.00 0.00
April 0.00 0.00 0.00 0.514864E+10 0.00 0.00
May 0.00 0.00 0.00 0.551074E+10 0.00 0.00
June 0.00 0.00 0.00 0.571466E+10 0.00 0.00
July 0.00 0.00 0.00 0.701582E+10 0.00 0.00
August 0.00 0.00 0.00 0.778440E+10 0.00 0.00
September 0.00 0.00 0.00 0.558356E+10 0.00 0.00
October 0.00 0.00 0.00 0.513115E+10 0.00 0.00
November 0.00 0.00 0.00 0.493911E+10 0.00 0.00
December 0.00 0.00 0.00 0.508380E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.666777E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.459496E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.778440E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC_1:1

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.709509E+10 0.00 0.202964E+11 0.00 0.00 0.00 0.00 0.00
February 0.642628E+10 12662713.87 0.150044E+11 0.00 0.00 0.00 0.00 0.00
March 0.700119E+10 33163414.70 0.931829E+10 0.00 0.00 0.00 0.00 0.00
April 0.668518E+10 0.124488E+10 0.448887E+10 0.00 0.00 0.00 0.00 0.00
May 0.684220E+10 0.211802E+10 0.161792E+10 0.00 0.00 0.00 0.00 0.00
June 0.661307E+10 0.359916E+10 0.151141E+09 0.00 0.00 0.00 0.00 0.00
July 0.684506E+10 0.868605E+10 1973513.66 0.00 0.00 0.00 0.00 0.00
August 0.686538E+10 0.120903E+11 2081208.57 0.00 0.00 0.00 0.00 0.00
September 0.661856E+10 0.347662E+10 0.219346E+09 0.00 0.00 0.00 0.00 0.00
October 0.684450E+10 0.227371E+09 0.263605E+10 0.00 0.00 0.00 0.00 0.00
November 0.675984E+10 91587416.73 0.108118E+11 0.00 0.00 0.00 0.00 0.00
December 0.713636E+10 0.00 0.184937E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.817327E+11 0.315799E+11 0.830419E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.642628E+10 0.00 1973513.66 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.713636E+10 0.120903E+11 0.202964E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC_2:2

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.508357E+10 0.00 0.182097E+11 0.00 0.00 0.00 0.00 0.00
February 0.459412E+10 2653031.75 0.135110E+11 0.00 0.00 0.00 0.00 0.00
March 0.508665E+10 1820104.37 0.709516E+10 0.00 0.00 0.00 0.00 0.00
April 0.493147E+10 0.780672E+09 0.324382E+10 0.00 0.00 0.00 0.00 0.00
May 0.511187E+10 0.138518E+10 0.102899E+10 0.00 0.00 0.00 0.00 0.00
June 0.497574E+10 0.258187E+10 30019695.24 0.00 0.00 0.00 0.00 0.00
July 0.517120E+10 0.673892E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.519917E+10 0.968512E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.498274E+10 0.211686E+10 79847041.57 0.00 0.00 0.00 0.00 0.00
October 0.510494E+10 84957996.20 0.143186E+10 0.00 0.00 0.00 0.00 0.00
November 0.492679E+10 39438172.36 0.809364E+10 0.00 0.00 0.00 0.00 0.00
December 0.508380E+10 0.00 0.149249E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.602521E+11 0.234175E+11 0.676489E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.459412E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.519917E+10 0.968512E+10 0.182097E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC_1:1

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.709509E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.642628E+10 0.00 0.00 0.00 4098359.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.700119E+10 0.00 0.00 0.00 10611067.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.668518E+10 0.00 0.00 0.00 0.348017E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.684220E+10 0.00 0.00 0.00 0.612249E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.661307E+10 0.00 0.00 0.00 0.103920E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.684506E+10 0.00 0.00 0.00 0.240705E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.686538E+10 0.00 0.00 0.00 0.327371E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.661856E+10 0.00 0.00 0.00 0.980088E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.684450E+10 0.00 0.00 0.00 68830318.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.675984E+10 0.00 0.00 0.00 27786421.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.713636E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.817327E+11 0.00 0.00 0.00 0.877164E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.642628E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.713636E+10 0.00 0.00 0.00 0.327371E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC_2:2

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.508357E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.459412E+10 0.00 0.00 0.00 841856.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.508665E+10 0.00 0.00 0.00 598482.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.493147E+10 0.00 0.00 0.00 0.217172E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.511187E+10 0.00 0.00 0.00 0.398869E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.497574E+10 0.00 0.00 0.00 0.738915E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.517120E+10 0.00 0.00 0.00 0.184462E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.519917E+10 0.00 0.00 0.00 0.258522E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.498274E+10 0.00 0.00 0.00 0.600822E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.510494E+10 0.00 0.00 0.00 26203554.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.492679E+10 0.00 0.00 0.00 12315093.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.508380E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.602521E+11 0.00 0.00 0.00 0.642558E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.459412E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.519917E+10 0.00 0.00 0.00 0.258522E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.206380E+10 0.00 0.00 0.00 0.00 0.216341E+11 0.00 0.00 3.68
February 0.452257E+10 0.00 0.00 481338.84 0.00 0.157605E+11 0.371022E+09 0.00 3.76
March 0.681980E+10 0.00 0.00 1553636.20 0.00 0.111141E+11 0.117178E+10 0.00 3.76
April 0.751374E+10 4876511.60 0.00 9254117.69 0.00 0.511013E+10 0.362042E+10 0.00 4.32
May 0.719034E+10 623184.29 0.00 18971456.11 0.00 0.155128E+10 0.685570E+10 0.00 5.19
June 0.466661E+10 463937.70 0.00 28948665.37 0.00 35019959.95 0.102666E+11 0.00 6.47
July 0.273596E+10 0.150072E+09 0.00 42687186.71 0.00 0.00 0.109913E+11 0.00 7.24
August 0.209208E+10 0.439195E+09 0.00 36745915.05 0.00 603294.56 0.995245E+10 0.00 7.10
September 0.555805E+10 1884164.84 0.00 27084758.96 0.00 0.170010E+09 0.910241E+10 0.00 6.10
October 0.840497E+10 0.00 0.00 6953141.58 0.00 0.320967E+10 0.421918E+10 0.00 4.24
November 0.530889E+10 0.00 0.00 990721.22 0.00 0.126886E+11 0.575877E+09 0.00 3.74
December 0.293042E+10 0.00 0.00 0.00 0.00 0.204014E+11 0.00 0.00 3.66
                   
Annual Sum or Average 0.598072E+11 0.597115E+09 0.00 0.173671E+09 0.00 0.916754E+11 0.571267E+11 0.00 4.94
Minimum of Months 0.206380E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.66
Maximum of Months 0.840497E+10 0.439195E+09 0.00 42687186.71 0.00 0.216341E+11 0.109913E+11 0.00 7.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.519571E+11 0.00 0.00 33904.05 0.00 18209084.88 88135731.03 0.00 9.68
February 0.436238E+11 0.00 0.00 634296.37 0.00 12937207.67 0.896389E+09 0.00 9.75
March 0.411863E+11 0.00 0.00 982055.16 0.00 1542995.58 0.150196E+10 0.00 9.72
April 0.322598E+11 0.00 0.00 8620088.30 0.00 1637158.13 0.540035E+10 0.00 9.85
May 0.258290E+11 0.00 0.00 20129891.22 0.00 0.00 0.109850E+11 0.00 10.09
June 0.150793E+11 0.00 0.00 39436310.44 0.00 0.00 0.188157E+11 0.00 10.46
July 0.944523E+10 2316109.72 0.00 65473222.94 0.00 0.00 0.220039E+11 0.00 10.75
August 0.727879E+10 44290113.68 0.00 64170204.38 0.00 0.00 0.209774E+11 0.00 10.85
September 0.153682E+11 0.00 0.00 34443843.91 0.00 0.00 0.185377E+11 0.00 10.38
October 0.300279E+11 0.00 0.00 7094805.94 0.00 0.00 0.784919E+10 0.00 9.87
November 0.399819E+11 0.00 0.00 1787588.97 0.00 1714300.47 0.217750E+10 0.00 9.74
December 0.492499E+11 0.00 0.00 35579.90 0.00 1729511.49 20823421.25 0.00 9.66
                   
Annual Sum or Average 0.361287E+12 46606223.40 0.00 0.242842E+09 0.00 37770258.22 0.109254E+12 0.00 10.07
Minimum of Months 0.727879E+10 0.00 0.00 33904.05 0.00 0.00 20823421.25 0.00 9.66
Maximum of Months 0.519571E+11 44290113.68 0.00 65473222.94 0.00 18209084.88 0.220039E+11 0.00 10.85



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:39

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.698759E+10 0.140710E+11 0.938180E+11 0.00 0.211318E+11
February 0.147408E+11 0.119468E+11 0.804280E+11 0.147840E+09 0.183432E+11
March 0.275655E+11 0.117376E+11 0.777180E+11 0.324396E+09 0.177437E+11
April 0.451322E+11 0.102114E+11 0.682690E+11 0.159571E+10 0.199826E+11
May 0.604656E+11 0.954497E+10 0.669220E+11 0.360060E+10 0.236196E+11
June 0.619009E+11 0.773061E+10 0.593734E+11 0.641690E+10 0.271765E+11
July 0.656401E+11 0.615796E+10 0.537442E+11 0.763728E+10 0.412189E+11
August 0.509698E+11 0.488448E+10 0.483751E+11 0.677550E+10 0.480355E+11
September 0.345176E+11 0.721590E+10 0.607357E+11 0.536692E+10 0.251245E+11
October 0.206396E+11 0.959363E+10 0.702322E+11 0.170404E+10 0.152246E+11
November 0.809790E+10 0.112593E+11 0.769406E+11 0.239680E+09 0.157088E+11
December 0.495378E+10 0.131399E+11 0.889946E+11 0.00 0.195297E+11
           
Annual Sum or Average 0.401611E+12 0.117493E+12 0.845551E+12 0.338089E+11 0.292839E+12
Minimum of Months 0.495378E+10 0.488448E+10 0.483751E+11 0.00 0.152246E+11
Maximum of Months 0.656401E+11 0.140710E+11 0.938180E+11 0.763728E+10 0.480355E+11