Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2024-07-03 12:20:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1722.37 | 7413.06 | 7413.06 |
Net Site Energy | 1722.37 | 7413.06 | 7413.06 |
Total Source Energy | 3097.18 | 13330.22 | 13330.22 |
Net Source Energy | 3097.18 | 13330.22 | 13330.22 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 444.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 272.03 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 210.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 36.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 590.56 | 1131.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 444.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 15.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 167.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 210.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 10.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 17.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 444.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 28.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 44.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 272.03 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 167.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 210.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 36.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 370.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 843.87 | 2817.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1327.63 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2541.75 | 4871.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 370.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 843.87 | 2817.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1327.63 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2541.75 | 4871.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 590.557 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 590.557 | 100.00 |
Total On-Site and Utility Electric Sources | 590.557 | 100.00 |
Total Electricity End Uses | 590.557 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.67 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4101.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 63.19 | 0.00 | 15.80 | 31.59 | 15.80 |
Gross Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Above Ground Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 63.19 | 0.00 | 15.80 | 31.59 | 15.80 |
Gross Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Above Ground Window-Wall Ratio [%] | 33.99 | 0.00 | 33.99 | 67.98 | 33.99 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 63.19 | 63.19 | 9.2637 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 11.9458 | 18.52 | 1072.7618 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 63.19 | 63.19 | 10.6047 | 2.48 | 594.7744 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 63.19 | 63.19 | 10.6047 | 2.48 | 594.7744 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 9.2637 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.9458 | 18.52 | 1072.7618 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 10.6047 | 1.24 | 594.7744 | |||||||
Conditioned Total | 232.34 | 10.6047 | 1.24 | 594.7744 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 10.6047 | 2.48 | 594.7744 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-16:10 | 10-JAN-21:00 | - | - | - | - | - | - | - | - | - | - | 15-MAR-12:50 |
Heating | 0.00 | 128408.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16991.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 12919.68 | 16547.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6257.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 11561.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1151.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 39537.60 | 156517.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 128408.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16991.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 11696.68 | 16547.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6257.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 11561.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 363.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 593.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 481.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 89.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 141.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 130.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 861.52 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 531.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 115.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1870.29 | 1226.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2071.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 386.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 561.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3707.96 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 982.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 496.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8049.71 | 5280.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2071.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 386.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 611.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 561.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3707.96 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 982.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 496.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8049.71 | 5280.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.23 |
KITCHEN DIRECT AIR | 1.54 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.23 | 2.23 | 2.23 | 2.23 | 2.23 | 2.23 | 1.00 | 1.000000 | 2.23 |
PSZ-AC_2:2 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.00 | 1.000000 | 1.54 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.23 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.54 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.23 | 3699.33 |
PSZ-AC_2:2_ADDAQ FAN | 1.54 | 2558.01 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.23 | 2.23 | 2.23 | 2.23 | 37881.36 | 47772.88 | 32.22 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.54 | 1.54 | 1.54 | 1.54 | 30835.87 | 74496.17 | 30.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.23 | 1.11 | 1.48 | 37881.36 | 18940.68 | 0.800600 | 0.800600 |
PSZ-AC_2:2 COOLING COIL | 1.54 | 0.769559 | 1.03 | 30835.87 | 15417.93 | 0.775770 | 0.775770 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 47772.88 |
PSZ-AC_2:2 HEATING COIL | 74496.17 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 29.76 | 63.19 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 9.264 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 126.051 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 11.946 | 281.409 | 791.353 | 0.000 | 0.000 | 0.000 | 1084.708 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 1076.175 | 9.264 | 12.293 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1076.175 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1387.759 | 11.946 | 221.217 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1387.759 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 493.000 | 4.244 | 78.587 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 493.000 | 493.000 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 730.000 | 6.284 | 116.366 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 730.000 | 730.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.3836 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.3836 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.508 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.508 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | -0.36752283E-16 | 0.36650618E-15 | -0.17323971E-14 | 0.96945811E-16 |
24 | 3 | -0.69118654E-08 | 0.27160578E-06 | -0.56853996E-04 | 0.15386634E-12 |
25 | 2 | 0.11860501E-03 | 0.58949329E-02 | 1.1525899 | -0.75054507E-04 |
26 | 1 | -0.13685427 | 0.15202565 | -17.175506 | 0.33646671 |
27 | 0 | 0.39128804 | 0.96631513E-01 | 16.277526 | |
28 | 4 | -0.17323971E-14 | 0.36650618E-15 | -0.36752283E-16 | 0.96945811E-16 |
29 | 3 | -0.56853996E-04 | 0.27160578E-06 | -0.69118654E-08 | 0.15386634E-12 |
30 | 2 | 1.1525899 | 0.58949329E-02 | 0.11860501E-03 | -0.75054507E-04 |
31 | 1 | -17.175506 | 0.15202565 | -0.13685427 | 0.33646671 |
32 | 0 | 16.277526 | 0.96631513E-01 | 0.39128804 | |
33 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
34 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
35 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
36 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
37 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
38 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
39 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
40 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 | 39 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | NONRESWINDOW_U_0.57_SHGC_EAST_0.39 | 40 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 41 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 21.722 | 0.5184 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 4 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 5 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 4 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 5 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 4 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 5 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.68 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone DINING | 1.2500 |
3 | Zone KITCHEN | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone DINING | 1.1500 |
3 | Zone KITCHEN | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 23035.92521 | 26491.31399 | 1.93551 | 2.22583 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 13060.73731 | 16325.92163 | 1.07956 | 1.34945 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -27.60000 | 3.41898E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 15925.78162 | 18314.64886 | 1.33836 | 1.53912 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.96000 | 6.30459E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 3458.12117 | 4322.65146 | 0.28540 | 1.14133 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -27.60000 | 3.41898E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30336.53 | 2.22583 | 2.22583 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 37393.21 | 1.34945 | 1.34945 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 25415.07 | 1.53912 | 1.53912 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 69570.65 | 1.14133 | 1.14133 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.22583 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.53912 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.22583 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.22583 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.22583 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.22583 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.22583 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.22583 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.53912 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53912 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.53912 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53912 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.53912 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.53912 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.22583 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.53912 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.22583 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.22583 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3699.32792 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.22583 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.22583 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.22583 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.22583 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.22583 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.11292 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.48389 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37881.36000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18940.68000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80060 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80060 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37881.36000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 47772.88482 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 47772.88482 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.53912 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.53912 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2558.01046 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.53912 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53912 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53912 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.53912 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.53912 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76956 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02608 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30835.87000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15417.93500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77577 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77577 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30835.87000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 74496.16753 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 30.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 74496.16753 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 36255.5 | 10.36 | 10.32 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 29723.3 | 10.68 | 10.63 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 7.44 | 23.24 | 7.44 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 15.80 | 15.80 | 15.80 | 90.00 | 90.00 | 7.11 | 2.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 14.88 | 46.47 | 14.88 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 31.59 | 31.59 | 31.59 | 180.00 | 90.00 | 14.23 | 2.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 7.44 | 23.24 | 7.44 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 15.80 | 15.80 | 15.80 | 270.00 | 90.00 | 7.11 | 2.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.384 | 0.358 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.384 | 0.358 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.384 | 0.351 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.384 | 0.351 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1247364067 | 0.3983319682 | Pass | Pass | 0.2643083577 | 0.6561912610 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1424059268 | 0.5590239178 | Pass | Pass | 4.7508397713E-002 | 0.1848061179 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2860510766 | 0.3213945824 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 466.03 | 142.90 | 1005.83 | 39.74 | 426.54 | 2081.05 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 23.24 | 7.44 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 46.47 | 14.88 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 23.24 | 7.44 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.348 | 0.384 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.348 | 0.384 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.348 | 0.384 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.348 | 0.384 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.57_SHGC_EAST_0.39 | 15.80 | 0.00 | 0.00 | 15.80 | 15.80 | 3.241 | 0.391 | 0.431 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39 | 31.59 | 0.00 | 0.00 | 31.59 | 31.59 | 3.241 | 0.391 | 0.431 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 15.80 | 0.00 | 0.00 | 15.80 | 15.80 | 3.241 | 0.391 | 0.431 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 63.19 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 63.19 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 9.2637 | 116.17 | 1076.18 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 19.58 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.9458 | 116.17 | 1387.76 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 25.25 |
Interior Lighting Total | 10.6047 | 232.34 | 2463.93 | 44.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 2625.88 | AstronomicalClock | - | 83.57 | 83.57 | 41.19 | |
Exterior Lighting Total | 2625.88 | 41.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37881.36 | 30327.82 | 7553.54 | 0.80 | 3.50 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30835.87 | 23921.54 | 6914.33 | 0.78 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 36255.5 | 10.36 | 10.32 | ||||
PSZ-AC_2:2 COOLING COIL | 29723.3 | 10.68 | 10.63 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 47772.88 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 74496.17 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 1.56 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 966.87 | 2.23 | 3699.33 | 1662.00 | 1.00 | 1.21 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 966.87 | 1.54 | 2558.01 | 1662.00 | 1.00 | 1.26 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 21.72 | 0.52 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 23035.93 | 26491.31 | 228.04 | 1.936 | 2.226 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 23.89 | 23.88 | 0.00764 | 33.24 | 0.00631 | 0.416 | 0.00 |
KITCHEN | 15925.78 | 18314.65 | 157.65 | 1.338 | 1.539 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00844 | 31.96 | 0.00630 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 13060.74 | 16325.92 | 140.53 | 1.080 | 1.349 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00793 | -27.60 | 0.00034 | 0.416 | 0.00 |
KITCHEN | 3458.12 | 4322.65 | 37.21 | 0.285 | 1.141 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.89 | 18.89 | 0.00753 | -27.60 | 0.00034 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.23 | 2.23 | 1.35 | 1.35 | 2.2258 | 2.2258 | 2.2258 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.54 | 1.54 | 1.14 | 1.14 | 1.5391 | 1.5391 | 1.5391 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 37881.360 | 30327.817 | 2.225830 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 18940.68 | 18007.01 | 1.483887 | 25.66 | 14.66 | 0.00739123 | 11.23 | 8.74 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 28.0383 | 23.88 | 0.00764061 | 36.2765 | 23029.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 47772.885 | 47772.885 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 47772.88 | 47772.88 | 2.225833 | 11.94 | 8.54 | 0.00651447 | 32.22 | 17.31 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.6922 | 21.11 | 0.00793351 | 44.5591 | 13060.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 30835.870 | 23921.543 | 1.539120 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 15417.93 | 15417.93 | 1.026080 | 31.98 | 16.25 | 0.00674183 | 13.45 | 9.41 | 0.00674183 | 33.40 | 0.00630683 | 16.37 | 111.2324 | 26.10 | 0.00856250 | 35.5756 | 15925.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 74496.168 | 74496.168 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 74496.17 | 74496.17 | 1.539118 | -15.74 | -15.74 | 0.00216395 | 30.00 | 16.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 74.1550 | 17.91 | 0.00739184 | 50.6892 | 1156.37 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37881.360 | 30327.817 | 2.225830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5799 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.225833 | 2.34411300 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 18940.68 | 18007.01 | 1.0000 | 1.56274023 | 1.483887 | 25.66 | 14.66 | 0.00739123 | 44623.0 | 11.23 | 8.74 | 0.00700000 | 28936.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18940.68 | 33.40 | 0.00630683 | 16.37 | 0.41605618 | 28.0383 | 23.88 | 0.00764061 | 23.88 | 0.00764061 | 36.2765 | 23029.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 47772.885 | 47772.885 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.225833 | 2.34411300 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 47772.88 | 47772.88 | 1.0000 | 2.34411300 | 2.225833 | 11.94 | 8.54 | 0.00651447 | 28433.3 | 32.22 | 17.31 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47772.88 | -27.60 | 0.00034190 | -27.60 | 0.41605618 | 18.6922 | 21.03 | 0.00793351 | 21.11 | 0.00793351 | 44.5591 | 13060.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30835.870 | 23921.543 | 1.539120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.3727 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.539118 | 1.62090674 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 15417.93 | 15417.93 | 1.0000 | 1.08060577 | 1.026080 | 31.98 | 16.25 | 0.00674183 | 49399.6 | 13.45 | 9.41 | 0.00674183 | 30542.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15417.93 | 33.40 | 0.00630683 | 16.37 | 1.14133354 | 111.2324 | 26.05 | 0.00856250 | 26.10 | 0.00856250 | 35.5756 | 15925.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 74496.168 | 74496.168 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.539118 | 1.62090674 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 74496.17 | 74496.17 | 1.0000 | 1.62090674 | 1.539118 | -15.74 | -15.74 | 0.00216395 | -10464.9 | 30.00 | 16.60 | 0.00800000 | 50598.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 74496.17 | -27.60 | 0.00034190 | -27.60 | 1.14133354 | 74.1550 | 18.30 | 0.00739184 | 17.91 | 0.00739184 | 50.6892 | 1156.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | FixedDryBulb | 0.42 | 2.23 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | FixedDryBulb | 1.14 | 1.54 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4125.00 | 4693.67 | 2239.00 |
KITCHEN | 4832.67 | 6098.83 | 3953.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5015.33 | 6312.17 | 4101.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 219.00 | 15.67 | 1.67 | 0.17 |
KITCHEN | 0.00 | 91.17 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 219.00 | 104.00 | 1.67 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 6.196 | 2.785 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 12.126 | 0.041 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.066 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.150 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 16073619.62 | 0.00 | 16073619.62 | 7083434.06 | 23157053.68 | 13120747.55 | 1369.78 | 5599.79 | 1790.43 | 475.56 |
KITCHEN | 31330519.16 | 0.00 | 31330519.16 | 176597.47 | 31507116.63 | 35993094.65 | 1448.93 | 6422.72 | 888.35 | 386.01 |
Total Facility | 47404138.78 | 0.00 | 47404138.78 | 7260031.53 | 54664170.31 | 49113842.20 | 1457.15 | 6496.89 | 1798.88 | 696.46 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.6016 | 0.0000 | 0.6016 | 0.2709 | 0.8726 | 0.4161 | 0.00 | 5428.49 | 1758.51 |
KITCHEN | 1.1815 | 0.0000 | 1.1815 | 0.0040 | 1.1855 | 1.1413 | 0.00 | 6309.86 | 877.14 |
Total Facility | 1.7831 | 0.0000 | 1.7831 | 0.2749 | 2.0580 | 1.5574 | 0.00 | 6310.40 | 1759.06 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 17827293.65 | 0.00 | 17827293.65 | 13120747.55 | 1364.89 | 0.84 | 7394.27 | 475.56 |
PSZ-AC_2:2 | 34748791.81 | 0.00 | 34748791.81 | 35993094.65 | 1445.79 | 0.52 | 7313.69 | 386.01 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6673 | 0.0000 | 0.6673 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3104 | 0.0000 | 1.3104 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 956.21 | 1111.48 | 5594.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 957.95 | 6615.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.8523 | 0.9582 | 0.4615 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.6270 | 1.2661 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 365 |
Defaulted Fields | 263 |
Fields with Defaults | 866 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 590.56 | 5919.80 | 27-NOV-01:10 | 39537.60 | 17-JUL-16:10 |
Electricity:Building | 324.80 | 2625.15 | 01-JAN-01:10 | 19780.88 | 02-JAN-11:10 |
Electricity:Zone:DINING | 89.91 | 431.44 | 01-JAN-01:10 | 4898.81 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 316.86 | 2488.87 | 01-JAN-01:10 | 16486.83 | 02-JAN-11:10 |
InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 19.58 | 161.43 | 01-JAN-01:10 | 968.56 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 44.83 | 369.59 | 01-JAN-01:10 | 2217.54 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 234.89 | 2193.72 | 01-JAN-01:10 | 14882.07 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 25.25 | 208.16 | 01-JAN-01:10 | 1248.98 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 272.03 | 2119.28 | 01-JAN-01:10 | 14269.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 272.03 | 2119.28 | 01-JAN-01:10 | 14269.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 201.70 | 1849.27 | 01-JAN-01:10 | 10339.04 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 36.44 | 594.45 | 26-MAR-22:30 | 3920.08 | 07-SEP-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 28.50 | 508.67 | 20-JAN-23:10 | 1629.14 | 05-SEP-03:40 |
LowTempRefrigeration:Refrigeration:Electricity | 10.85 | 0.00 | 01-JAN-11:10 | 992.04 | 05-SEP-03:40 |
MedTempRefrigeration:Refrigeration:Electricity | 17.65 | 475.34 | 06-FEB-01:00 | 637.09 | 02-MAY-13:10 |
ElectricityPurchased:Facility | 590.56 | 5919.80 | 27-NOV-01:10 | 39537.60 | 17-JUL-16:10 |
ElectricityPurchased:Plant | 590.56 | 5919.80 | 27-NOV-01:10 | 39537.60 | 17-JUL-16:10 |
Cogeneration:ElectricityPurchased | 590.56 | 5919.80 | 27-NOV-01:10 | 39537.60 | 17-JUL-16:10 |
General:Cogeneration:ElectricityPurchased | 590.56 | 5919.80 | 27-NOV-01:10 | 39537.60 | 17-JUL-16:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 590.56 | 5919.80 | 27-NOV-01:10 | 39537.60 | 17-JUL-16:10 |
ElectricityNet:Plant | 590.56 | 5919.80 | 27-NOV-01:10 | 39537.60 | 17-JUL-16:10 |
Cogeneration:ElectricityNet | 590.56 | 5919.80 | 27-NOV-01:10 | 39537.60 | 17-JUL-16:10 |
General:Cogeneration:ElectricityNet | 590.56 | 5919.80 | 27-NOV-01:10 | 39537.60 | 17-JUL-16:10 |
Electricity:HVAC | 196.07 | 0.00 | 01-JAN-01:10 | 23287.06 | 17-JUL-13:00 |
Fans:Electricity | 167.69 | 0.00 | 01-JAN-01:10 | 6257.34 | 01-JAN-00:10 |
General:Fans:Electricity | 167.69 | 0.00 | 01-JAN-01:10 | 6257.34 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 28.38 | 0.00 | 01-JAN-00:10 | 17029.72 | 17-JUL-13:00 |
General:Cooling:Electricity | 28.38 | 0.00 | 01-JAN-00:10 | 17029.72 | 17-JUL-13:00 |
ExteriorLights:Electricity | 41.19 | 0.00 | 01-JAN-08:20 | 2625.88 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 41.19 | 0.00 | 01-JAN-08:20 | 2625.88 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-13:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-13:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1131.82 | 1838.65 | 08-APR-00:40 | 156517.20 | 10-JAN-22:00 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 444.10 | 0.00 | 01-JAN-01:10 | 128408.16 | 10-JAN-22:00 |
Heating:NaturalGas | 444.10 | 0.00 | 01-JAN-01:10 | 128408.16 | 10-JAN-22:00 |
General:Heating:NaturalGas | 444.10 | 0.00 | 01-JAN-01:10 | 128408.16 | 10-JAN-22:00 |
NaturalGas:Plant | 210.56 | 0.00 | 07-APR-04:00 | 27768.65 | 15-FEB-13:30 |
WaterSystems:NaturalGas | 210.56 | 0.00 | 07-APR-04:00 | 27768.65 | 15-FEB-13:30 |
Water Heater:WaterSystems:NaturalGas | 210.56 | 0.00 | 07-APR-04:00 | 27768.65 | 15-FEB-13:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-12:50 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-12:50 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-12:50 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-12:50 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-12:50 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-12:50 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-12:50 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-12:50 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1128.34 | 2416.13 | 27-NOV-01:10 | 147439.97 | 10-JAN-21:00 |
EnergyTransfer:Building | 445.73 | 1208.06 | 27-NOV-01:10 | 40651.86 | 09-JAN-12:10 |
EnergyTransfer:Zone:KITCHEN | 308.90 | 1207.44 | 11-JAN-01:10 | 24071.34 | 20-OCT-04:10 |
Refrigeration:EnergyTransfer | 131.34 | 2414.89 | 11-JAN-01:10 | 7834.84 | 13-JUN-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 65.67 | 1207.44 | 11-JAN-01:10 | 3917.42 | 13-JUN-03:20 |
General:Refrigeration:EnergyTransfer | 65.67 | 1207.44 | 11-JAN-01:10 | 3917.42 | 13-JUN-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 65.67 | 1207.44 | 11-JAN-01:10 | 3917.42 | 13-JUN-03:20 |
EnergyTransfer:Plant | 226.53 | 1207.44 | 11-JAN-01:10 | 24245.63 | 27-FEB-13:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.89 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 52.78 | 1059.55 | 06-FEB-01:00 | 2238.70 | 02-MAY-13:10 |
EnergyTransfer:Zone:DINING | 136.83 | 0.00 | 01-JAN-01:10 | 35257.08 | 07-JAN-03:20 |
Heating:EnergyTransfer | 67.35 | 0.00 | 01-JAN-00:10 | 30130.58 | 10-JAN-20:10 |
Heating:EnergyTransfer:Zone:DINING | 67.32 | 0.00 | 01-JAN-00:10 | 30130.58 | 10-JAN-20:10 |
General:Heating:EnergyTransfer | 67.35 | 0.00 | 01-JAN-00:10 | 30130.58 | 10-JAN-20:10 |
General:Heating:EnergyTransfer:Zone:DINING | 67.32 | 0.00 | 01-JAN-00:10 | 30130.58 | 10-JAN-20:10 |
Cooling:EnergyTransfer | 312.70 | 0.00 | 01-JAN-01:10 | 32891.94 | 17-JUL-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 69.51 | 0.00 | 01-JAN-01:10 | 20203.16 | 17-JUL-17:10 |
General:Cooling:EnergyTransfer | 312.70 | 0.00 | 01-JAN-01:10 | 32891.94 | 17-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 69.51 | 0.00 | 01-JAN-01:10 | 20203.16 | 17-JUL-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.03 | 0.00 | 01-JAN-00:10 | 1567.93 | 29-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.03 | 0.00 | 01-JAN-00:10 | 1567.93 | 29-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 243.20 | 0.00 | 01-JAN-01:10 | 20218.33 | 20-OCT-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 243.20 | 0.00 | 01-JAN-01:10 | 20218.33 | 20-OCT-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 160.86 | 0.00 | 01-JAN-00:10 | 21864.43 | 18-FEB-13:10 |
PlantLoopHeatingDemand:Plant | 160.86 | 0.00 | 01-JAN-00:10 | 21864.43 | 18-FEB-13:10 |
WaterSystems:PlantLoopHeatingDemand | 160.86 | 0.00 | 01-JAN-00:10 | 21864.43 | 18-FEB-13:10 |
General:WaterSystems:PlantLoopHeatingDemand | 160.86 | 0.00 | 01-JAN-00:10 | 21864.43 | 18-FEB-13:10 |
EnergyTransfer:HVAC | 456.08 | 0.00 | 01-JAN-01:10 | 102205.69 | 10-JAN-22:00 |
HeatingCoils:EnergyTransfer | 353.57 | 0.00 | 01-JAN-01:10 | 102205.69 | 10-JAN-22:00 |
CoolingCoils:EnergyTransfer | 102.51 | 0.00 | 01-JAN-00:10 | 56624.61 | 17-JUL-13:00 |
WaterSystems:EnergyTransfer | 160.86 | 0.00 | 01-JAN-00:10 | 21864.43 | 18-FEB-13:10 |
WaterUse:WaterSystems:EnergyTransfer | 160.86 | 0.00 | 01-JAN-00:10 | 21864.43 | 18-FEB-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 67.320 | -69.505 | 0.000 | 0.000 | 71.336 | 19.580 | 52.748 | 60.769 | 0.000 | 2.920 | 0.000 | 0.000 | -53.441 | 0.000 | -110.961 | -40.767 |
KITCHEN | 0.000 | 0.000 | 0.032 | -243.191 | 0.000 | 0.000 | 5.226 | 25.249 | 207.409 | 0.000 | 0.000 | 0.018 | 8.319 | 0.000 | 0.000 | 0.000 | -3.061 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.909 | 10.761 | 0.000 | 0.000 | 0.000 | -12.670 | -0.000 |
Total Facility | 0.000 | 0.000 | 67.352 | -312.696 | 0.000 | 0.000 | 76.562 | 44.830 | 260.157 | 60.769 | 0.000 | 4.848 | 19.080 | 0.000 | -53.441 | 0.000 | -126.692 | -40.767 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 29-JAN-04:08 | 0.00 | 0.00 | 0.00 | -59100.83 | 0.00 | 0.00 | 0.00 | 161.43 | 506.27 | 0.00 | 0.00 | 0.00 | 65805.98 | 0.00 | -6925.79 | 0.00 | -447.06 | 0.00 |
KITCHEN | 28-SEP-02:61 | 0.00 | 0.00 | 0.00 | -51624.87 | 0.00 | 0.00 | 0.00 | 208.16 | 1872.55 | 0.00 | 0.00 | 0.00 | 49823.14 | 0.00 | -0.00 | 0.00 | -278.98 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-SEP-02:61 | 0.00 | 0.00 | 0.00 | -85013.90 | 0.00 | 0.00 | 0.00 | 369.59 | 2075.06 | 0.00 | 0.00 | 197.98 | 84692.22 | 0.00 | -2291.18 | 0.00 | -29.76 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 01-APR-02:61 | 0.00 | 0.00 | 38827.89 | 0.00 | 0.00 | 0.00 | 0.00 | 161.43 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2276.94 | 0.00 | -343.41 | -36571.48 |
KITCHEN | 29-DEC-05:02 | 0.00 | 0.00 | 14094.46 | 0.00 | 0.00 | 0.00 | 22.87 | 277.55 | 5126.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19521.73 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-APR-02:61 | 0.00 | 0.00 | 38827.89 | 0.00 | 0.00 | 0.00 | 0.00 | 369.59 | 2075.06 | 0.00 | 0.00 | 316.33 | 0.00 | 0.00 | -2276.94 | 0.00 | -749.54 | -38562.40 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2258 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.2258 | 0.1869 | 1.0000 | Not calculated | 0.4161 | 0.1869 | ||
PSZ-AC_2:2 | 1.5391 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.5391 | 0.0983 | 1.0000 | Not calculated | 0.1513 | 0.0983 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2258 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.2258 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1869 | ||
PSZ-AC_2:2 | 1.5391 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.5391 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.0983 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2258 | 2.2258 | 2.2258 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5391 | 1.5391 | 1.5391 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2258 | 2.2258 | 2.2258 | 2.2258 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.5391 | 1.5391 | 1.5391 | 1.5391 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2258 | 2.2258 | 2.2258 | No | 0.4161 | 0.3083 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5391 | 1.5391 | 1.5391 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2258 | 2.2258 | 2.2258 | 2.2258 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.5391 | 1.5391 | 1.5391 | 1.5391 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 1.67 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 1.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 444.10 | 128408.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 28.38 | 17029.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 44.83 | 2217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.19 | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 15.55 | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 23.02 | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 167.69 | 6257.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 210.56 | 27768.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 10.85 | 992.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 17.65 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 308.47 | 590.56 |
Natural Gas | 477.16 | 1131.82 |
Additional | 0.00 | 0.00 |
Total | 785.62 | 1722.37 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 192.95 |
Space Heating | 0.00 |
Space Cooling | 122.13 |
Fans (All) | 721.74 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1170.81 |
Miscellaneous (All) | 2541.75 |
Subtotal | 2541.75 |
Natural Gas [MJ/m2] | |
Space Heating | 1911.40 |
Service Water Heating | 906.24 |
Miscellaneous (All) | 4871.32 |
Subtotal | 4871.32 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.60 |
Space Heating | 25.78 |
Space Cooling | 1.65 |
Fans (All) | 9.74 |
Service Water Heating | 12.22 |
Receptacle Equipment | 43.50 |
Miscellaneous | 4.51 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8487.33 | 272.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 7282.67 | 529.50 | 457.00 | 483.00 | 7.83 |
Min | 7282.67 | 12.17 | 0.00 | 0.00 | 0.00 |
Max | 8747.83 | 529.50 | 457.00 | 483.00 | 7.83 |
Average | 8172.61 | 271.44 | 152.33 | 161.00 | 2.61 |
Sum | 24517.83 | 814.33 | 457.00 | 483.00 | 7.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254689.00 | 36.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254689.00 | 36.00 | 0.00 | 0.00 | 0.00 |
Average | 90315.67 | 12.00 | 0.00 | 0.00 | 0.00 |
Sum | 270947.00 | 36.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8421.00 | 339.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7485.00 | 696.17 | 243.83 | 194.17 | 140.83 |
Min | 7485.00 | 14.67 | 0.00 | 0.00 | 0.00 |
Max | 8745.33 | 696.17 | 243.83 | 194.17 | 140.83 |
Average | 8217.11 | 349.94 | 81.28 | 64.72 | 46.94 |
Sum | 24651.33 | 1049.83 | 243.83 | 194.17 | 140.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 254524.83 | 200.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15826.33 | 431.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254524.83 | 431.67 | 0.00 | 0.00 | 0.00 |
Average | 90117.06 | 210.61 | 0.00 | 0.00 | 0.00 |
Sum | 270351.17 | 631.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149301E+10 | 59101.32 | 29-JAN-04:08 | -30.6 | -30.9 | 0.444957E+10 | 3722.82 | 28-JAN-19:30 | -30.6 | -30.9 |
February | 0.159421E+10 | 48089.46 | 01-FEB-04:50 | -25.0 | -25.2 | 0.409933E+10 | 4413.04 | 21-FEB-12:39 | 13.17 | 3.42 |
March | 0.165000E+10 | 40442.51 | 05-MAR-03:52 | -21.1 | -21.7 | 0.457133E+10 | 4413.07 | 14-MAR-11:50 | 14.13 | 6.25 |
April | 0.260466E+10 | 13792.07 | 29-APR-03:43 | -7.6 | -8.5 | 0.463460E+10 | 4680.95 | 22-APR-18:00 | -7.6 | -8.5 |
May | 0.507672E+10 | 12550.68 | 19-MAY-17:03 | 26.02 | 14.43 | 0.499968E+10 | 4681.04 | 20-MAY-18:19 | 23.87 | 13.86 |
June | 0.103184E+11 | 33294.94 | 26-JUN-02:61 | 15.60 | 11.93 | 0.517632E+10 | 4681.01 | 24-JUN-18:00 | 15.60 | 11.93 |
July | 0.157364E+11 | 38524.94 | 13-JUL-02:61 | 15.40 | 9.44 | 0.538958E+10 | 4681.32 | 01-JUL-18:00 | 15.40 | 9.44 |
August | 0.143717E+11 | 41528.03 | 30-AUG-02:61 | 12.98 | 8.24 | 0.540801E+10 | 4681.03 | 12-AUG-18:40 | 12.98 | 8.24 |
September | 0.938651E+10 | 42359.33 | 02-SEP-02:61 | 13.40 | 8.31 | 0.502151E+10 | 4681.03 | 02-SEP-18:40 | 28.13 | 14.29 |
October | 0.433362E+10 | 11853.75 | 18-OCT-13:00 | 24.40 | 10.82 | 0.488794E+10 | 4680.94 | 28-OCT-18:30 | 13.60 | 6.97 |
November | 0.174667E+10 | 30074.48 | 27-NOV-03:17 | -15.9 | -16.7 | 0.447581E+10 | 4680.88 | 04-NOV-18:30 | -15.9 | -16.7 |
December | 0.119418E+10 | 49290.94 | 29-DEC-03:04 | -25.8 | -26.1 | 0.445947E+10 | 4204.14 | 06-DEC-12:00 | -25.8 | -26.1 |
Annual Sum or Average | 0.695060E+11 | 0.575732E+11 | ||||||||
Minimum of Months | 0.119418E+10 | 11853.75 | -30.6 | -30.9 | 0.409933E+10 | 3722.82 | -30.6 | -30.9 | ||
Maximum of Months | 0.157364E+11 | 59101.32 | 26.02 | 14.43 | 0.540801E+10 | 4681.32 | 28.13 | 14.29 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174355E+11 | 42388.59 | 26-JAN-00:01 | -22.2 | -22.7 | 0.768108E+10 | 5048.87 | 14-JAN-11:00 | -22.2 | -22.7 |
February | 0.167854E+11 | 43424.78 | 10-FEB-05:01 | -19.5 | -19.9 | 0.694490E+10 | 5117.54 | 27-FEB-11:00 | 16.10 | 6.08 |
March | 0.191464E+11 | 41183.04 | 05-MAR-00:01 | -23.1 | -23.6 | 0.768873E+10 | 5078.83 | 14-MAR-10:00 | 12.80 | 5.58 |
April | 0.191217E+11 | 32376.49 | 28-APR-04:01 | -6.7 | -7.1 | 0.747502E+10 | 5135.89 | 07-APR-10:00 | -6.7 | -7.1 |
May | 0.205633E+11 | 49016.02 | 14-MAY-02:61 | 8.30 | 4.34 | 0.776336E+10 | 5135.94 | 19-MAY-10:50 | 21.83 | 13.58 |
June | 0.211086E+11 | 48165.43 | 20-JUN-02:61 | 9.13 | 5.67 | 0.757503E+10 | 5135.94 | 06-JUN-10:00 | 9.13 | 5.67 |
July | 0.227967E+11 | 49130.10 | 12-JUL-02:61 | 9.27 | 5.03 | 0.784681E+10 | 5135.95 | 19-JUL-10:00 | 27.20 | 17.90 |
August | 0.227170E+11 | 47457.28 | 28-AUG-02:61 | 10.00 | 6.08 | 0.784380E+10 | 5135.94 | 22-AUG-10:00 | 10.00 | 6.08 |
September | 0.219338E+11 | 51681.92 | 28-SEP-02:61 | 7.33 | 3.71 | 0.755001E+10 | 5135.95 | 06-SEP-10:50 | 7.33 | 3.71 |
October | 0.224081E+11 | 50146.46 | 20-OCT-04:01 | 4.13 | 1.44 | 0.774273E+10 | 5135.93 | 18-OCT-10:00 | 4.13 | 1.44 |
November | 0.201909E+11 | 36094.54 | 21-NOV-05:01 | -9.9 | -11.1 | 0.745511E+10 | 5110.45 | 17-NOV-11:00 | -9.9 | -11.1 |
December | 0.189908E+11 | 43681.06 | 29-DEC-05:01 | -25.0 | -25.3 | 0.768354E+10 | 5082.61 | 06-DEC-11:00 | -25.0 | -25.3 |
Annual Sum or Average | 0.243198E+12 | 0.912501E+11 | ||||||||
Minimum of Months | 0.167854E+11 | 32376.49 | -25.0 | -25.3 | 0.694490E+10 | 5048.87 | -25.0 | -25.3 | ||
Maximum of Months | 0.227967E+11 | 51681.92 | 10.00 | 6.08 | 0.784681E+10 | 5135.95 | 27.20 | 17.90 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.3 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.9 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 | -4.1 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 | 0.55 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 | -3.0 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -3.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 | 10.36 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.36 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 | 13.32 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.32 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 | 11.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.96 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 | 11.59 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.59 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 | 6.94 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.94 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 | 1.54 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.54 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.9 | 0.00 | 0.00 | -12.4 | -13.9 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.32 | 0.00 | 0.00 | 19.45 | 13.32 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206033E+11 | 37906.41 | 27-JAN-02:31 | -27.0 |
February | 0.109579E+11 | 38432.47 | 11-FEB-03:01 | 3.30 |
March | 0.842213E+10 | 37383.99 | 09-MAR-03:01 | 0.87 |
April | 0.327356E+10 | 38832.76 | 01-APR-02:61 | 4.78 |
May | 0.179552E+10 | 36846.24 | 01-MAY-02:61 | -0.8 |
June | 0.127594E+09 | 16089.49 | 17-JUN-02:62 | 2.12 |
July | 51670963.54 | 18575.34 | 26-JUL-02:43 | 19.68 |
August | 51081804.78 | 17283.07 | 11-AUG-02:43 | 18.40 |
September | 0.411367E+09 | 15728.75 | 10-SEP-03:07 | 19.72 |
October | 0.149407E+10 | 23554.25 | 05-OCT-04:01 | -1.7 |
November | 0.588723E+10 | 37401.72 | 30-NOV-03:01 | 1.10 |
December | 0.142449E+11 | 37728.15 | 30-DEC-03:21 | -20.3 |
Annual Sum or Average | 0.673202E+11 | |||
Minimum of Months | 51081804.78 | 15728.75 | -27.0 | |
Maximum of Months | 0.206033E+11 | 38832.76 | 19.72 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12344283.48 | 10801.66 | 09-JAN-00:02 | -27.2 |
February | 6098587.16 | 12422.54 | 10-FEB-05:02 | -19.5 |
March | 2418807.50 | 10593.47 | 05-MAR-00:02 | -23.1 |
April | 1272403.20 | 5878.76 | 28-APR-04:03 | -6.7 |
May | 284713.75 | 2820.70 | 01-MAY-04:03 | -0.6 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 2148828.50 | 6430.60 | 14-NOV-05:03 | -8.0 |
December | 6962038.40 | 14111.39 | 29-DEC-05:02 | -25.0 |
Annual Sum or Average | 31529661.97 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 12344283.48 | 14111.39 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.165449E+10 | 968.56 | 02-JAN-10:09 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.149855E+10 | 968.56 | 01-FEB-10:09 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.168084E+10 | 968.56 | 01-MAR-10:09 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.160761E+10 | 968.56 | 01-APR-16:10 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.166766E+10 | 968.56 | 01-MAY-09:09 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.162466E+10 | 968.56 | 01-JUN-09:09 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.165081E+10 | 968.56 | 01-JUL-16:10 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.168084E+10 | 968.56 | 01-AUG-09:09 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.160800E+10 | 968.56 | 01-SEP-09:09 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.165430E+10 | 968.56 | 02-OCT-09:09 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.160161E+10 | 968.56 | 01-NOV-09:09 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.165100E+10 | 968.56 | 01-DEC-10:09 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.195804E+11 | 0.703313E+11 | ||||
Minimum of Months | 0.149855E+10 | 968.56 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.168084E+10 | 968.56 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.213351E+10 | 1248.98 | 02-JAN-10:09 | 0.171305E+11 | 10339.04 | 01-JAN-11:09 |
February | 0.193243E+10 | 1248.98 | 01-FEB-10:09 | 0.154728E+11 | 10339.04 | 01-FEB-11:09 |
March | 0.216749E+10 | 1248.98 | 01-MAR-10:09 | 0.171306E+11 | 10339.04 | 01-MAR-11:09 |
April | 0.207306E+10 | 1248.98 | 01-APR-16:10 | 0.165779E+11 | 10339.04 | 01-APR-10:09 |
May | 0.215050E+10 | 1248.98 | 01-MAY-09:09 | 0.171306E+11 | 10339.04 | 01-MAY-10:09 |
June | 0.209504E+10 | 1248.98 | 01-JUN-09:09 | 0.165780E+11 | 10339.04 | 01-JUN-10:09 |
July | 0.212877E+10 | 1248.98 | 01-JUL-16:10 | 0.171305E+11 | 10339.04 | 01-JUL-10:09 |
August | 0.216749E+10 | 1248.98 | 01-AUG-09:09 | 0.171306E+11 | 10339.04 | 01-AUG-10:09 |
September | 0.207356E+10 | 1248.98 | 01-SEP-09:09 | 0.165779E+11 | 10339.04 | 01-SEP-10:09 |
October | 0.213326E+10 | 1248.98 | 02-OCT-09:09 | 0.171305E+11 | 10339.04 | 01-OCT-10:09 |
November | 0.206532E+10 | 1248.98 | 01-NOV-09:09 | 0.165780E+11 | 10339.04 | 01-NOV-10:09 |
December | 0.212902E+10 | 1248.98 | 01-DEC-10:09 | 0.171305E+11 | 10339.04 | 01-DEC-11:09 |
Annual Sum or Average | 0.252494E+11 | 0.201699E+12 | ||||
Minimum of Months | 0.193243E+10 | 1248.98 | 0.154728E+11 | 10339.04 | ||
Maximum of Months | 0.216749E+10 | 1248.98 | 0.171306E+11 | 10339.04 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.165449E+10 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202647E+11 |
February | 0.852256E+10 | 0.149855E+10 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139385E+11 |
March | 0.954557E+10 | 0.168084E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130848E+11 |
April | 0.915225E+10 | 0.160761E+10 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859601E+10 |
May | 0.947560E+10 | 0.166766E+10 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44403725.07 | 0.689648E+10 |
June | 0.922788E+10 | 0.162466E+10 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408461E+09 | 0.337032E+10 |
July | 0.939996E+10 | 0.165081E+10 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121643E+10 | 0.168880E+10 |
August | 0.954557E+10 | 0.168084E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912238E+09 | 0.243987E+10 |
September | 0.915225E+10 | 0.160800E+10 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336336E+09 | 0.471563E+10 |
October | 0.940563E+10 | 0.165430E+10 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2335896.94 | 0.807874E+10 |
November | 0.909363E+10 | 0.160161E+10 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113352E+11 |
December | 0.939996E+10 | 0.165100E+10 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165519E+11 |
Annual Sum or Average | 0.111326E+12 | 0.195804E+11 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292021E+10 | 0.110961E+12 |
Minimum of Months | 0.852256E+10 | 0.149855E+10 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168880E+10 |
Maximum of Months | 0.954557E+10 | 0.168084E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121643E+10 | 0.202647E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.213351E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470317E+09 |
February | 0.610713E+09 | 0.193243E+10 | 0.117185E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354259E+09 |
March | 0.684021E+09 | 0.216749E+10 | 0.129742E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316480E+09 |
April | 0.655836E+09 | 0.207306E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219848E+09 |
May | 0.679007E+09 | 0.215050E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 270057.13 | 0.231658E+09 |
June | 0.661256E+09 | 0.209504E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2285979.51 | 0.141215E+09 |
July | 0.673587E+09 | 0.212877E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6835563.72 | 96075320.90 |
August | 0.684021E+09 | 0.216749E+10 | 0.129742E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6191099.39 | 0.109285E+09 |
September | 0.655836E+09 | 0.207356E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2600213.42 | 0.181119E+09 |
October | 0.673993E+09 | 0.213326E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233576E+09 |
November | 0.651635E+09 | 0.206532E+10 | 0.125556E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323187E+09 |
December | 0.673587E+09 | 0.212902E+10 | 0.129741E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384381E+09 |
Annual Sum or Average | 0.797748E+10 | 0.252494E+11 | 0.152760E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 18182913.17 | 0.306140E+10 |
Minimum of Months | 0.610713E+09 | 0.193243E+10 | 0.117185E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96075320.90 |
Maximum of Months | 0.684021E+09 | 0.216749E+10 | 0.129742E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6835563.72 | 0.470317E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126053E+09 | 0.635977E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135011E+09 | 0.710776E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156487E+09 | 0.111897E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151410E+09 | 0.122722E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112261E+09 | 0.158847E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103190E+09 | 0.166962E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166233E+09 | 0.166324E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185314E+09 | 0.140786E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184458E+09 | 0.101948E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226434E+09 | 0.735696E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203173E+09 | 0.474238E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159444E+09 | 0.418603E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190947E+10 | 0.126701E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103190E+09 | 0.418603E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226434E+09 | 0.166962E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 968.56 | 02-JAN-10:09 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 30901.36 | 10-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 968.56 | 01-FEB-10:09 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 27085.14 | 04-FEB-20:00 |
March | 9454.80 | 04-MAR-19:10 | 968.56 | 01-MAR-10:09 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 26223.09 | 04-MAR-20:00 |
April | 9454.80 | 01-APR-18:10 | 968.56 | 01-APR-16:10 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 14648.74 | 28-APR-20:00 |
May | 9454.80 | 06-MAY-18:10 | 968.56 | 01-MAY-09:09 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1876.42 | 20-MAY-17:05 | 12076.82 | 22-MAY-19:00 |
June | 9454.80 | 03-JUN-18:10 | 968.56 | 01-JUN-09:09 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3653.57 | 29-JUN-13:00 | 8556.11 | 16-JUN-11:02 |
July | 9454.80 | 01-JUL-18:10 | 968.56 | 01-JUL-16:10 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5961.28 | 17-JUL-17:03 | 5236.15 | 07-JUL-19:57 |
August | 9454.80 | 05-AUG-18:10 | 968.56 | 01-AUG-09:09 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5569.74 | 05-AUG-18:03 | 6927.48 | 17-AUG-12:00 |
September | 9454.80 | 02-SEP-18:10 | 968.56 | 01-SEP-09:09 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4412.49 | 02-SEP-17:03 | 9993.88 | 18-SEP-20:00 |
October | 9454.80 | 07-OCT-18:10 | 968.56 | 02-OCT-09:09 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 307.33 | 18-OCT-14:00 | 12269.79 | 31-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 968.56 | 01-NOV-09:09 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 18450.93 | 26-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 968.56 | 01-DEC-10:09 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 26333.24 | 29-DEC-19:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 968.56 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5236.15 | |||||
Maximum of Months | 9454.80 | 968.56 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5961.28 | 30901.36 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 1248.98 | 02-JAN-10:09 | 7604.23 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 906.87 | 06-JAN-03:51 |
February | 677.52 | 04-FEB-19:10 | 1248.98 | 01-FEB-10:09 | 7604.23 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 849.83 | 17-FEB-04:10 |
March | 677.52 | 04-MAR-19:10 | 1248.98 | 01-MAR-10:09 | 7604.23 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 972.41 | 17-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 1248.98 | 01-APR-16:10 | 7604.23 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 690.00 | 27-APR-02:00 |
May | 677.52 | 06-MAY-18:10 | 1248.98 | 01-MAY-09:09 | 7604.23 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 18.98 | 20-MAY-16:00 | 1464.19 | 22-MAY-03:52 |
June | 677.52 | 03-JUN-18:10 | 1248.98 | 01-JUN-09:09 | 7604.23 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 45.49 | 29-JUN-15:00 | 679.05 | 14-JUN-02:00 |
July | 677.52 | 01-JUL-18:10 | 1248.98 | 01-JUL-16:10 | 7604.23 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 49.55 | 25-JUL-15:00 | 377.06 | 05-JUL-01:00 |
August | 677.52 | 05-AUG-18:10 | 1248.98 | 01-AUG-09:09 | 7604.23 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 45.31 | 11-AUG-14:00 | 501.70 | 23-AUG-03:20 |
September | 677.52 | 02-SEP-18:10 | 1248.98 | 01-SEP-09:09 | 7604.23 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 46.28 | 02-SEP-14:00 | 834.59 | 12-SEP-03:00 |
October | 677.52 | 07-OCT-18:10 | 1248.98 | 02-OCT-09:09 | 7604.23 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 594.39 | 31-OCT-03:50 |
November | 677.52 | 04-NOV-18:10 | 1248.98 | 01-NOV-09:09 | 7604.23 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 826.39 | 28-NOV-05:00 |
December | 677.52 | 02-DEC-19:10 | 1248.98 | 01-DEC-10:09 | 7604.23 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1368.94 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 1248.98 | 7604.23 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 377.06 | ||||||
Maximum of Months | 677.52 | 1248.98 | 7604.23 | 7998.14 | 0.00 | 0.00 | 0.00 | 49.55 | 1464.19 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.11 | 11-JAN-08:32 | 1671.33 | 28-JAN-14:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.95 | 05-FEB-23:53 | 1706.33 | 05-FEB-13:40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.22 | 01-MAR-07:00 | 2023.43 | 07-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.64 | 11-APR-06:53 | 2194.53 | 29-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.76 | 31-MAY-06:33 | 2483.14 | 09-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.07 | 20-JUN-04:55 | 2122.52 | 02-JUN-12:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.79 | 03-JUL-14:35 | 2335.50 | 05-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.95 | 07-AUG-02:52 | 2031.97 | 03-AUG-12:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.80 | 03-SEP-04:55 | 1988.02 | 17-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.14 | 16-OCT-05:00 | 1491.82 | 10-OCT-12:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.95 | 14-NOV-07:45 | 1230.18 | 12-NOV-13:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.19 | 03-DEC-24:00 | 1343.15 | 29-DEC-13:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.19 | 1230.18 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.11 | 2483.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 59101.32 | 29-JAN-04:08 | 0.00 | 1614.26 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.06 |
February | 48089.46 | 01-FEB-04:50 | 0.00 | 1614.26 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.41 |
March | 40442.51 | 05-MAR-03:52 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.29 |
April | 13792.07 | 29-APR-03:43 | 0.00 | 1614.26 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.68 |
May | 12550.68 | 19-MAY-17:03 | 25212.80 | 2905.67 | 9757.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.05 | 0.00 |
June | 33294.94 | 26-JUN-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.01 |
July | 38524.94 | 13-JUL-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.55 |
August | 41528.03 | 30-AUG-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42359.33 | 02-SEP-02:61 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 |
October | 11853.75 | 18-OCT-13:00 | 7353.73 | 968.56 | 3388.15 | 0.00 | 0.00 | 0.00 | 0.00 | 230.26 | 0.00 |
November | 30074.48 | 27-NOV-03:17 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.05 |
December | 49290.94 | 29-DEC-03:04 | 0.00 | 1614.26 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11853.75 | 0.00 | 968.56 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59101.32 | 25212.80 | 2905.67 | 9757.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.05 | 657.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 42388.59 | 26-JAN-00:01 | 376.40 | 2081.64 | 18831.27 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 125.83 |
February | 43424.78 | 10-FEB-05:01 | 338.76 | 2497.97 | 34771.56 | 29786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 |
March | 41183.04 | 05-MAR-00:01 | 376.40 | 2775.52 | 18831.27 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 125.67 |
April | 32376.49 | 28-APR-04:01 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49016.02 | 14-MAY-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 125.17 |
June | 48165.43 | 20-JUN-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 114.89 |
July | 49130.10 | 12-JUL-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 134.26 |
August | 47457.28 | 28-AUG-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 187.75 |
September | 51681.92 | 28-SEP-02:61 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 278.98 |
October | 50146.46 | 20-OCT-04:01 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 52.54 |
November | 36094.54 | 21-NOV-05:01 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 55.35 |
December | 43681.06 | 29-DEC-05:01 | 338.76 | 2497.97 | 34771.56 | 29786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 32376.49 | 0.00 | 2081.64 | 16613.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51681.92 | 376.40 | 2775.52 | 38635.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 278.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.27 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.09 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.19 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.15 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.42 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.40 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.83 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.93 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.43 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.82 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.82 | 223.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.488183E+11 | 26582.67 | 12-JAN-11:20 | 0.181815E+12 | 156517.20 | 10-JAN-21:00 |
February | 0.436404E+11 | 26606.72 | 27-FEB-11:20 | 0.124768E+12 | 125198.63 | 09-FEB-20:00 |
March | 0.478829E+11 | 26583.19 | 14-MAR-10:20 | 0.119841E+12 | 124439.80 | 04-MAR-21:00 |
April | 0.458243E+11 | 26635.50 | 07-APR-10:09 | 0.829641E+11 | 79925.39 | 28-APR-12:09 |
May | 0.481406E+11 | 31287.13 | 20-MAY-16:10 | 0.744646E+11 | 75660.28 | 08-MAY-10:09 |
June | 0.501086E+11 | 35392.10 | 23-JUN-10:20 | 0.570059E+11 | 56958.95 | 16-JUN-10:09 |
July | 0.568435E+11 | 39537.60 | 17-JUL-16:10 | 0.566987E+11 | 45821.59 | 02-JUL-12:39 |
August | 0.551554E+11 | 37616.26 | 10-AUG-10:20 | 0.565175E+11 | 45849.06 | 17-AUG-12:39 |
September | 0.500220E+11 | 36125.50 | 02-SEP-16:00 | 0.584757E+11 | 54187.43 | 18-SEP-10:09 |
October | 0.484307E+11 | 29412.31 | 18-OCT-12:00 | 0.719969E+11 | 68992.42 | 10-OCT-07:10 |
November | 0.468777E+11 | 26613.00 | 08-NOV-11:20 | 0.989978E+11 | 104895.99 | 26-NOV-11:09 |
December | 0.488122E+11 | 26592.01 | 06-DEC-11:20 | 0.148272E+12 | 138779.52 | 28-DEC-13:09 |
Annual Sum or Average | 0.590557E+12 | 0.113182E+13 | ||||
Minimum of Months | 0.436404E+11 | 26582.67 | 0.565175E+11 | 45821.59 | ||
Maximum of Months | 0.568435E+11 | 39537.60 | 0.181815E+12 | 156517.20 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.378800E+10 | 0.446820E+10 | 0.231039E+11 | 0.00 | 0.145429E+11 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343098E+10 | 0.369146E+10 | 0.208680E+11 | 0.00 | 0.129894E+11 | 0.72 | 0.00 | 2405094.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384832E+10 | 0.360481E+10 | 0.231040E+11 | 0.00 | 0.143811E+11 | 0.80 | 0.00 | 1771.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368067E+10 | 0.300138E+10 | 0.223586E+11 | 0.00 | 0.137371E+11 | 0.77 | 0.00 | 0.115041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.381816E+10 | 0.266894E+10 | 0.231040E+11 | 0.00 | 0.141519E+11 | 0.80 | 0.00 | 0.127466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371970E+10 | 0.235699E+10 | 0.223587E+11 | 0.00 | 0.136196E+11 | 0.77 | 0.00 | 0.488323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377958E+10 | 0.253975E+10 | 0.231038E+11 | 0.00 | 0.141847E+11 | 0.79 | 0.00 | 0.990132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.384832E+10 | 0.290685E+10 | 0.231040E+11 | 0.00 | 0.141690E+11 | 0.80 | 0.00 | 0.780861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.368156E+10 | 0.327552E+10 | 0.223586E+11 | 0.00 | 0.136549E+11 | 0.77 | 0.00 | 0.392356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378756E+10 | 0.388525E+10 | 0.231039E+11 | 0.00 | 0.140975E+11 | 0.79 | 0.00 | 0.466873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366693E+10 | 0.420036E+10 | 0.223586E+11 | 0.00 | 0.137589E+11 | 0.77 | 0.00 | 1139610.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378002E+10 | 0.459266E+10 | 0.231038E+11 | 0.00 | 0.144043E+11 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448298E+11 | 0.411922E+11 | 0.272030E+12 | 0.00 | 0.167691E+12 | 9.37 | 0.00 | 0.283768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.343098E+10 | 0.235699E+10 | 0.208680E+11 | 0.00 | 0.129894E+11 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.384832E+10 | 0.459266E+10 | 0.231040E+11 | 0.00 | 0.145429E+11 | 0.80 | 0.00 | 0.990132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.121652E+12 | 0.00 | 0.196367E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.701454E+11 | 0.00 | 0.180192E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.595184E+11 | 0.00 | 0.197967E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.253186E+11 | 0.00 | 0.184270E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.158931E+11 | 0.00 | 0.180458E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.136718E+10 | 0.00 | 0.164203E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 70721026.85 | 0.00 | 0.161023E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.182125E+09 | 0.00 | 0.158096E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.376204E+10 | 0.00 | 0.154953E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.147086E+11 | 0.00 | 0.167625E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.425519E+11 | 0.00 | 0.172275E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.889294E+11 | 0.00 | 0.188166E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.444099E+12 | 0.00 | 0.210560E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 70721026.85 | 0.00 | 0.154953E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.121652E+12 | 0.00 | 0.197967E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2217.54 | 02-JAN-10:09 | 2625.88 | 01-JAN-00:10 | 14269.29 | 01-JAN-11:09 | 0.00 | 6257.34 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 2217.54 | 01-FEB-10:09 | 2625.88 | 01-FEB-00:10 | 14269.29 | 01-FEB-11:09 | 0.00 | 6257.34 | 01-FEB-00:30 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 2217.54 | 01-MAR-10:09 | 2625.88 | 01-MAR-00:10 | 14269.29 | 01-MAR-11:09 | 0.00 | 6257.34 | 01-MAR-00:10 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 2217.54 | 01-APR-16:10 | 2625.88 | 01-APR-00:10 | 14269.29 | 01-APR-10:09 | 0.00 | 6257.34 | 01-APR-04:00 | 0.00 | 19-APR-13:39 | 0.00 | 01-APR-00:10 |
May | 2217.54 | 01-MAY-09:09 | 2625.88 | 01-MAY-00:10 | 14269.29 | 01-MAY-10:09 | 0.00 | 6257.34 | 01-MAY-04:19 | 0.00 | 26-MAY-12:39 | 0.00 | 01-MAY-00:10 |
June | 2217.54 | 01-JUN-09:09 | 2625.88 | 01-JUN-00:10 | 14269.29 | 01-JUN-10:09 | 0.00 | 6257.34 | 01-JUN-16:30 | 0.00 | 04-JUN-13:30 | 0.00 | 01-JUN-00:10 |
July | 2217.54 | 01-JUL-16:10 | 2625.88 | 01-JUL-00:10 | 14269.29 | 01-JUL-10:09 | 0.00 | 6257.34 | 01-JUL-04:10 | 0.00 | 06-JUL-14:39 | 0.00 | 01-JUL-00:10 |
August | 2217.54 | 01-AUG-09:09 | 2625.88 | 01-AUG-00:10 | 14269.29 | 01-AUG-10:09 | 0.00 | 6257.34 | 01-AUG-06:49 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 2217.54 | 01-SEP-09:09 | 2625.88 | 01-SEP-00:10 | 14269.29 | 01-SEP-10:09 | 0.00 | 6257.34 | 01-SEP-07:00 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 2217.54 | 02-OCT-09:09 | 2625.88 | 01-OCT-00:10 | 14269.29 | 01-OCT-10:09 | 0.00 | 6257.34 | 01-OCT-04:30 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 2217.54 | 01-NOV-09:09 | 2625.88 | 01-NOV-00:10 | 14269.29 | 01-NOV-10:09 | 0.00 | 6257.34 | 01-NOV-04:19 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 2217.54 | 01-DEC-10:09 | 2625.88 | 01-DEC-00:10 | 14269.29 | 01-DEC-11:09 | 0.00 | 6257.34 | 01-DEC-00:10 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2217.54 | 2625.88 | 14269.29 | 0.00 | 6257.34 | 0.00 | 0.00 | ||||||
Maximum of Months | 2217.54 | 2625.88 | 14269.29 | 0.00 | 6257.34 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 448.71 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.95 | 28-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4849.53 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8872.00 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12493.38 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17029.72 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14779.96 | 06-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14355.78 | 02-SEP-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7322.21 | 18-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 433.34 | 17-NOV-04:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17029.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 26582.67 | 12-JAN-11:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26606.72 | 27-FEB-11:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26583.19 | 14-MAR-10:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26635.50 | 07-APR-10:09 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31287.13 | 20-MAY-16:10 | 2217.54 | 12919.68 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 8740.25 | 0.00 |
June | 35392.10 | 23-JUN-10:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 8736.69 | 0.00 |
July | 39537.60 | 17-JUL-16:10 | 2217.54 | 12919.68 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 16991.51 | 0.00 |
August | 37616.26 | 10-AUG-10:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 10964.83 | 0.00 |
September | 36125.50 | 02-SEP-16:00 | 2217.54 | 12919.68 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 13579.37 | 0.00 |
October | 29412.31 | 18-OCT-12:00 | 2217.54 | 12469.80 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 7289.86 | 0.00 |
November | 26613.00 | 08-NOV-11:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26592.01 | 06-DEC-11:20 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 26582.67 | 2217.54 | 12469.80 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39537.60 | 2217.54 | 14269.29 | 0.00 | 0.00 | 6257.34 | 0.00 | 0.00 | 16991.51 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 128408.16 | 10-JAN-21:00 | 0.00 | 27317.08 | 31-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 102445.54 | 01-FEB-07:10 | 0.00 | 27768.65 | 15-FEB-13:30 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 98271.08 | 04-MAR-22:00 | 0.00 | 27656.45 | 01-MAR-13:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 59716.11 | 11-APR-02:30 | 0.00 | 26845.82 | 01-APR-12:20 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 59716.11 | 01-MAY-02:20 | 0.00 | 25697.20 | 02-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 29587.27 | 17-JUN-02:30 | 0.00 | 24098.76 | 01-JUN-12:30 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 5591.88 | 26-JUL-03:30 | 0.00 | 22838.44 | 02-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 7795.38 | 17-AUG-22:30 | 0.00 | 21796.89 | 01-AUG-12:39 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 26266.76 | 17-SEP-06:10 | 0.00 | 22480.71 | 30-SEP-12:20 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 59716.11 | 04-OCT-02:09 | 0.00 | 23891.54 | 31-OCT-12:39 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 79098.25 | 26-NOV-07:00 | 0.00 | 25130.03 | 30-NOV-13:20 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 117566.14 | 31-DEC-07:10 | 0.00 | 26590.26 | 31-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 5591.88 | 0.00 | 21796.89 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 128408.16 | 0.00 | 27768.65 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.67 | 17.17 | 1.67 | 17.25 | 0.00 | 17.25 | 0.00 | 17.25 |
February | 32.83 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
March | 32.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
April | 15.83 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
May | 11.67 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 |
June | 0.50 | 19.96 | 0.00 | 19.96 | 1.17 | 23.20 | 0.00 | 23.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.74 | 0.17 | 24.74 |
August | 0.17 | 20.53 | 0.00 | 20.53 | 5.67 | 24.64 | 0.00 | 24.64 |
September | 1.67 | 20.19 | 0.00 | 20.19 | 3.83 | 23.35 | 0.00 | 23.35 |
October | 8.33 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
November | 19.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
December | 36.67 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
Annual Sum or Average | 219.00 | 18.44 | 1.67 | 18.45 | 15.67 | 18.87 | 0.17 | 18.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.25 | 0.00 | 17.25 |
Maximum of Months | 59.67 | 20.53 | 1.67 | 20.53 | 5.67 | 24.74 | 0.17 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.34 | 0.00 | 27.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.69 | 0.00 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 28.51 | 0.00 | 28.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 29.28 | 0.00 | 29.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 29.33 | 0.00 | 29.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 28.91 | 0.00 | 28.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.61 | 0.00 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.19 | 0.00 | 27.19 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 91.17 | 28.74 | 0.00 | 28.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 29.33 | 0.00 | 29.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.88 | 488.50 | 20.85 | 488.50 | 20.84 |
February | 516.00 | 20.96 | 330.83 | 20.92 | 320.00 | 20.87 |
March | 583.50 | 21.01 | 320.33 | 20.91 | 319.50 | 20.86 |
April | 473.67 | 21.30 | 232.17 | 21.30 | 191.67 | 21.18 |
May | 374.67 | 21.48 | 248.17 | 21.90 | 104.83 | 21.73 |
June | 151.33 | 22.00 | 363.83 | 23.34 | 5.50 | 23.32 |
July | 70.17 | 23.20 | 501.50 | 23.89 | 17.83 | 23.92 |
August | 108.17 | 22.61 | 442.17 | 23.71 | 15.17 | 23.71 |
September | 224.33 | 21.77 | 330.83 | 22.99 | 31.50 | 22.96 |
October | 418.17 | 21.46 | 179.83 | 21.81 | 66.67 | 21.68 |
November | 556.67 | 21.28 | 249.00 | 21.15 | 240.00 | 21.05 |
December | 607.00 | 20.91 | 437.83 | 20.86 | 437.83 | 20.84 |
Annual Sum or Average | 4693.67 | 21.25 | 4125.00 | 21.72 | 2239.00 | 21.54 |
Minimum of Months | 70.17 | 20.88 | 179.83 | 20.85 | 5.50 | 20.84 |
Maximum of Months | 610.00 | 23.20 | 501.50 | 23.89 | 488.50 | 23.92 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.76 | 517.83 | 18.73 | 517.83 | 18.72 |
February | 536.33 | 18.94 | 378.00 | 18.88 | 369.33 | 18.81 |
March | 609.17 | 18.94 | 369.33 | 18.82 | 369.33 | 18.77 |
April | 484.83 | 19.36 | 300.67 | 19.77 | 220.00 | 19.54 |
May | 467.00 | 20.98 | 330.67 | 21.88 | 215.17 | 21.96 |
June | 415.83 | 24.32 | 450.67 | 24.89 | 302.00 | 25.15 |
July | 482.17 | 25.76 | 562.83 | 25.75 | 451.67 | 25.86 |
August | 466.33 | 25.32 | 528.67 | 25.51 | 401.83 | 25.67 |
September | 434.00 | 23.27 | 394.83 | 24.12 | 265.67 | 24.43 |
October | 448.83 | 20.07 | 247.83 | 20.99 | 123.00 | 20.94 |
November | 535.33 | 19.23 | 279.83 | 19.24 | 246.50 | 19.09 |
December | 609.00 | 18.86 | 471.50 | 18.78 | 471.50 | 18.75 |
Annual Sum or Average | 6098.83 | 20.91 | 4832.67 | 21.43 | 3953.83 | 21.46 |
Minimum of Months | 415.83 | 18.76 | 247.83 | 18.73 | 123.00 | 18.72 |
Maximum of Months | 610.00 | 25.76 | 562.83 | 25.75 | 517.83 | 25.86 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.88226 | 15.00537 | -0.8004 | 20.28452 |
February | 551.00000 | 21.14802 | 18.22563 | -0.5927 | 15.58128 |
March | 612.00000 | 21.13612 | 19.80863 | -0.5454 | 13.99994 |
April | 590.00000 | 21.80810 | 24.75264 | -0.2883 | 10.76854 |
May | 611.00000 | 22.41108 | 28.33690 | -1.0725 | 34.96031 |
June | 592.00000 | 23.42749 | 35.27883 | -0.5043 | 15.26246 |
July | 609.00000 | 23.86017 | 37.79278 | -0.2236 | 8.37790 |
August | 612.00000 | 23.72519 | 33.85191 | -0.3209 | 10.82484 |
September | 590.00000 | 23.10370 | 35.39778 | -0.6213 | 20.37006 |
October | 610.00000 | 22.20908 | 27.14312 | -0.0794 | 8.92008 |
November | 591.00000 | 21.42735 | 21.33704 | -0.4280 | 11.79699 |
December | 609.00000 | 20.92126 | 17.42938 | -0.7067 | 17.19297 |
Annual Sum or Average | 7187.00000 | 22.17741 | 26.23087 | -0.5153 | 15.70967 |
Minimum of Months | 551.00000 | 20.88226 | 15.00537 | -1.0725 | 8.37790 |
Maximum of Months | 612.00000 | 23.86017 | 37.79278 | -0.0794 | 34.96031 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.75664 | 20.45063 | -0.8209 | 20.15404 |
February | 551.00000 | 19.08049 | 24.11706 | -0.6898 | 17.32286 |
March | 612.00000 | 18.96220 | 26.06229 | -0.6901 | 16.48711 |
April | 590.00000 | 20.29787 | 30.70710 | -0.3359 | 13.70597 |
May | 611.00000 | 21.78821 | 33.04880 | -0.9323 | 38.89831 |
June | 592.00000 | 24.26371 | 36.90333 | -0.0288 | 17.89705 |
July | 609.00000 | 25.40723 | 37.66530 | 0.40045 | 13.78175 |
August | 612.00000 | 25.04067 | 34.35530 | 0.24818 | 14.20400 |
September | 590.00000 | 23.44472 | 37.42294 | -0.2718 | 24.09889 |
October | 610.00000 | 21.14211 | 31.90247 | -0.0575 | 12.56200 |
November | 591.00000 | 19.65701 | 26.59386 | -0.4773 | 13.60551 |
December | 609.00000 | 18.85574 | 22.80359 | -0.7383 | 17.58790 |
Annual Sum or Average | 7187.00000 | 21.40526 | 30.19038 | -0.3645 | 18.37991 |
Minimum of Months | 551.00000 | 18.75664 | 20.45063 | -0.9323 | 12.56200 |
Maximum of Months | 612.00000 | 25.40723 | 37.66530 | 0.40045 | 38.89831 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 7091058.19 | 2339708.00 | 2.59 | 7091058.19 | 0.00 | 0.00 | 0.09 | 27-FEB-15:00 | 0.00 | 01-FEB-00:01 | 1366.36 | 27-FEB-15:00 | 1366.36 | 27-FEB-15:00 | 0.00 | 27-FEB-14:45 | 448.74 | 27-FEB-15:00 | 0.00 | 01-FEB-00:01 |
March | 5282.17 | 1771.83 | 0.17 | 5282.17 | 0.00 | 0.00 | 0.00 | 28-MAR-16:57 | 0.00 | 01-MAR-00:01 | 9.13 | 28-MAR-16:57 | 9.13 | 28-MAR-16:57 | 0.00 | 28-MAR-16:53 | 3.06 | 28-MAR-16:57 | 0.00 | 01-MAR-00:01 |
April | 0.271899E+09 | 84090657.29 | 21.17 | 0.271899E+09 | 0.00 | 0.00 | 0.55 | 07-APR-13:53 | 0.00 | 01-APR-00:01 | 9231.27 | 07-APR-13:53 | 9231.27 | 07-APR-13:53 | 0.00 | 06-APR-17:17 | 2703.94 | 07-APR-13:53 | 0.00 | 01-APR-00:01 |
May | 0.255001E+10 | 0.733171E+09 | 98.76 | 0.253530E+10 | 14711235.72 | 0.00 | 0.93 | 19-MAY-17:20 | 0.00 | 01-MAY-00:01 | 17298.01 | 19-MAY-17:20 | 17190.42 | 19-MAY-17:03 | 779.90 | 19-MAY-12:30 | 4561.01 | 19-MAY-17:20 | 0.00 | 01-MAY-00:01 |
June | 0.974337E+10 | 0.268523E+10 | 245.04 | 0.925881E+10 | 0.484562E+09 | 0.00 | 1.00 | 20-JUN-11:55 | 0.00 | 01-JUN-00:01 | 37371.76 | 21-JUN-02:61 | 32668.14 | 21-JUN-02:61 | 11563.20 | 22-JUN-02:61 | 9724.84 | 21-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.190361E+11 | 0.526065E+10 | 397.11 | 0.184218E+11 | 0.614330E+09 | 0.00 | 1.00 | 01-JUL-02:62 | 0.00 | 01-JUL-00:01 | 37763.30 | 19-JUL-02:61 | 37371.76 | 26-JUL-02:61 | 16342.99 | 19-JUL-02:61 | 9753.59 | 19-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.151416E+11 | 0.419735E+10 | 335.78 | 0.150189E+11 | 0.122720E+09 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 37371.76 | 06-AUG-02:61 | 37371.76 | 07-AUG-03:09 | 11375.46 | 01-AUG-02:61 | 9724.84 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.769049E+10 | 0.212988E+10 | 197.23 | 0.732221E+10 | 0.368280E+09 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 37371.76 | 02-SEP-02:61 | 36380.17 | 10-SEP-02:61 | 9637.81 | 07-SEP-14:50 | 9724.84 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 0.103154E+10 | 0.305013E+09 | 49.55 | 0.103154E+10 | 2300.63 | 0.00 | 0.87 | 18-OCT-13:00 | 0.00 | 01-OCT-00:01 | 15773.81 | 18-OCT-13:00 | 15773.81 | 18-OCT-13:00 | 6.54 | 19-OCT-02:15 | 4239.07 | 18-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 35.63 | 11.95 | 0.33 | 35.63 | -0.0 | 0.00 | 0.00 | 07-NOV-17:35 | 0.00 | 01-NOV-00:01 | 0.11 | 07-NOV-17:35 | 0.11 | 07-NOV-17:35 | 0.00 | 17-NOV-11:45 | 0.04 | 07-NOV-17:35 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.554721E+11 | 0.153977E+11 | 1347.72 | 0.538675E+11 | 0.160461E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.190361E+11 | 0.526065E+10 | 397.11 | 0.184218E+11 | 0.614330E+09 | 0.00 | 1.00 | 0.00 | 37763.30 | 37371.76 | 16342.99 | 9753.59 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 197146.81 | 65386.76 | 0.11 | 140444.09 | 56702.72 | 0.00 | 0.06 | 28-FEB-04:30 | 0.00 | 01-FEB-00:01 | 718.02 | 28-FEB-04:30 | 510.74 | 28-FEB-04:30 | 207.28 | 28-FEB-04:30 | 237.58 | 28-FEB-04:30 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 99065893.26 | 30949891.81 | 12.13 | 98575616.56 | 490276.71 | 0.00 | 0.54 | 07-APR-13:53 | 0.00 | 01-APR-00:01 | 7300.30 | 07-APR-13:53 | 7300.30 | 07-APR-13:53 | 449.96 | 18-APR-03:10 | 2146.09 | 07-APR-13:53 | 0.00 | 01-APR-00:01 |
May | 0.188937E+10 | 0.541494E+09 | 88.66 | 0.187174E+10 | 17623444.66 | 0.00 | 1.00 | 14-MAY-02:61 | 0.00 | 01-MAY-00:01 | 30421.04 | 14-MAY-02:61 | 28244.80 | 29-MAY-02:61 | 11787.83 | 21-MAY-02:61 | 7916.13 | 14-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.803246E+10 | 0.219800E+10 | 228.25 | 0.767679E+10 | 0.355669E+09 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 30421.04 | 06-JUN-02:11 | 24803.16 | 25-JUN-02:11 | 16957.16 | 13-JUN-03:51 | 7916.13 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.169116E+11 | 0.464067E+10 | 383.68 | 0.165367E+11 | 0.374842E+09 | 0.00 | 1.00 | 01-JUL-02:11 | 0.00 | 01-JUL-00:01 | 30421.04 | 19-JUL-03:42 | 29127.49 | 26-JUL-03:42 | 16421.15 | 01-JUL-02:52 | 8844.51 | 17-JUL-14:00 | 0.00 | 01-JUL-00:01 |
August | 0.130382E+11 | 0.361127E+10 | 326.58 | 0.129361E+11 | 0.102139E+09 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 | 30421.04 | 07-AUG-02:52 | 30421.04 | 11-AUG-02:52 | 12349.76 | 14-AUG-02:61 | 7916.13 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 |
September | 0.652536E+10 | 0.179368E+10 | 181.08 | 0.614598E+10 | 0.379387E+09 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 30421.04 | 04-SEP-02:24 | 27990.47 | 04-SEP-03:53 | 17343.21 | 08-SEP-03:31 | 7916.13 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 0.539494E+09 | 0.161860E+09 | 37.62 | 0.535249E+09 | 4244386.54 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 30421.04 | 01-OCT-02:61 | 27603.46 | 19-OCT-02:61 | 13656.49 | 01-OCT-02:61 | 7916.13 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 3501156.84 | 1139598.11 | 1.19 | 2968874.66 | 532282.18 | 0.00 | 0.27 | 24-NOV-04:05 | 0.00 | 01-NOV-00:01 | 3378.20 | 24-NOV-04:05 | 3378.20 | 24-NOV-04:05 | 620.92 | 17-NOV-04:08 | 1063.82 | 24-NOV-04:05 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.470392E+11 | 0.129791E+11 | 1259.29 | 0.458043E+11 | 0.123499E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.169116E+11 | 0.464067E+10 | 383.68 | 0.165367E+11 | 0.379387E+09 | 0.00 | 1.00 | 0.00 | 30421.04 | 30421.04 | 17343.21 | 8844.51 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 182.44 | 83.64 | 98.80 | 73.09 | 903.56 | 0.00 | 0.00 | 0.00 |
February | 285.35 | 141.67 | 143.68 | 180.71 | 673.27 | 0.00 | 0.00 | 0.00 |
March | 383.68 | 158.76 | 224.92 | 270.88 | 536.43 | 0.00 | 0.00 | 0.00 |
April | 489.54 | 242.61 | 246.93 | 439.07 | 374.73 | 0.00 | 0.00 | 0.00 |
May | 540.76 | 240.60 | 300.16 | 527.73 | 299.30 | 0.00 | 0.00 | 0.00 |
June | 699.94 | 360.19 | 339.75 | 813.62 | 200.92 | 0.00 | 0.00 | 0.00 |
July | 734.61 | 415.30 | 319.32 | 937.16 | 167.01 | 0.00 | 0.00 | 0.00 |
August | 638.41 | 355.70 | 282.71 | 783.89 | 191.14 | 0.00 | 0.00 | 0.00 |
September | 451.61 | 233.12 | 218.49 | 484.74 | 273.88 | 0.00 | 0.00 | 0.00 |
October | 324.01 | 164.53 | 159.48 | 267.54 | 403.93 | 0.00 | 0.00 | 0.00 |
November | 205.35 | 95.87 | 109.48 | 113.72 | 566.83 | 0.00 | 0.00 | 0.00 |
December | 151.46 | 65.05 | 86.41 | 54.53 | 777.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 424.66 | 213.46 | 211.20 | 413.57 | 446.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.46 | 65.05 | 86.41 | 54.53 | 167.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 734.61 | 415.30 | 339.75 | 937.16 | 903.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1120.12 | 800.01 | 320.11 | 949.63 | 1640.86 | 0.00 | 0.00 | 0.00 |
February | 1426.45 | 1025.96 | 400.49 | 1369.83 | 1219.05 | 0.00 | 0.00 | 0.00 |
March | 1275.06 | 716.02 | 559.05 | 1219.92 | 1072.54 | 0.00 | 0.00 | 0.00 |
April | 1024.94 | 490.23 | 534.70 | 1026.32 | 791.87 | 0.00 | 0.00 | 0.00 |
May | 910.63 | 302.44 | 608.19 | 916.37 | 642.21 | 0.00 | 0.00 | 0.00 |
June | 904.80 | 263.88 | 640.92 | 1056.41 | 454.32 | 0.00 | 0.00 | 0.00 |
July | 975.47 | 360.33 | 615.13 | 1311.81 | 368.55 | 0.00 | 0.00 | 0.00 |
August | 1159.28 | 584.49 | 574.79 | 1520.34 | 418.14 | 0.00 | 0.00 | 0.00 |
September | 1285.78 | 787.84 | 497.94 | 1551.38 | 575.91 | 0.00 | 0.00 | 0.00 |
October | 1344.21 | 929.51 | 414.71 | 1460.58 | 796.25 | 0.00 | 0.00 | 0.00 |
November | 1225.52 | 887.72 | 337.80 | 1190.11 | 1028.80 | 0.00 | 0.00 | 0.00 |
December | 1065.17 | 769.16 | 296.01 | 932.50 | 1399.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1141.15 | 657.36 | 483.79 | 1207.47 | 866.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 904.80 | 263.88 | 296.01 | 916.37 | 368.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1426.45 | 1025.96 | 640.92 | 1551.38 | 1640.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.25 | 66.60 | 98.65 | 62.25 | 945.66 | 0.00 | 0.00 | 0.00 |
February | 282.06 | 138.65 | 143.41 | 176.44 | 687.40 | 0.00 | 0.00 | 0.00 |
March | 360.97 | 132.26 | 228.70 | 240.14 | 561.01 | 0.00 | 0.00 | 0.00 |
April | 471.25 | 208.78 | 262.46 | 418.63 | 390.26 | 0.00 | 0.00 | 0.00 |
May | 582.90 | 265.83 | 317.06 | 588.07 | 311.36 | 0.00 | 0.00 | 0.00 |
June | 634.17 | 291.30 | 342.87 | 729.96 | 216.55 | 0.00 | 0.00 | 0.00 |
July | 649.64 | 328.27 | 321.37 | 833.50 | 184.01 | 0.00 | 0.00 | 0.00 |
August | 551.63 | 270.73 | 280.90 | 675.41 | 204.85 | 0.00 | 0.00 | 0.00 |
September | 443.75 | 224.34 | 219.41 | 481.08 | 292.24 | 0.00 | 0.00 | 0.00 |
October | 317.16 | 157.58 | 159.58 | 263.62 | 422.55 | 0.00 | 0.00 | 0.00 |
November | 224.52 | 111.38 | 113.14 | 142.22 | 586.20 | 0.00 | 0.00 | 0.00 |
December | 150.92 | 63.70 | 87.22 | 58.21 | 802.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 403.40 | 188.47 | 214.93 | 390.29 | 466.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 150.92 | 63.70 | 87.22 | 58.21 | 184.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 649.64 | 328.27 | 342.87 | 833.50 | 945.66 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.488646E+09 | 0.224024E+09 | 0.264622E+09 | 0.195770E+09 | 0.242010E+10 |
February | 0.690323E+09 | 0.342729E+09 | 0.347594E+09 | 0.437178E+09 | 0.162878E+10 |
March | 0.102765E+10 | 0.425214E+09 | 0.602439E+09 | 0.725520E+09 | 0.143679E+10 |
April | 0.126889E+10 | 0.628851E+09 | 0.640036E+09 | 0.113807E+10 | 0.971298E+09 |
May | 0.144837E+10 | 0.644435E+09 | 0.803938E+09 | 0.141347E+10 | 0.801635E+09 |
June | 0.181426E+10 | 0.933614E+09 | 0.880642E+09 | 0.210890E+10 | 0.520797E+09 |
July | 0.196758E+10 | 0.111233E+10 | 0.855256E+09 | 0.251010E+10 | 0.447315E+09 |
August | 0.170992E+10 | 0.952712E+09 | 0.757205E+09 | 0.209958E+10 | 0.511947E+09 |
September | 0.117058E+10 | 0.604248E+09 | 0.566331E+09 | 0.125644E+10 | 0.709896E+09 |
October | 0.867824E+09 | 0.440667E+09 | 0.427157E+09 | 0.716580E+09 | 0.108189E+10 |
November | 0.532268E+09 | 0.248499E+09 | 0.283769E+09 | 0.294755E+09 | 0.146923E+10 |
December | 0.405664E+09 | 0.174234E+09 | 0.231431E+09 | 0.146049E+09 | 0.208117E+10 |
Annual Sum or Average | 0.133920E+11 | 0.673155E+10 | 0.666042E+10 | 0.130424E+11 | 0.140808E+11 |
Minimum of Months | 0.405664E+09 | 0.174234E+09 | 0.231431E+09 | 0.146049E+09 | 0.447315E+09 |
Maximum of Months | 0.196758E+10 | 0.111233E+10 | 0.880642E+09 | 0.251010E+10 | 0.242010E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300012E+10 | 0.214274E+10 | 0.857374E+09 | 0.254349E+10 | 0.439488E+10 |
February | 0.345087E+10 | 0.248199E+10 | 0.968876E+09 | 0.331390E+10 | 0.294911E+10 |
March | 0.341513E+10 | 0.191778E+10 | 0.149735E+10 | 0.326743E+10 | 0.287268E+10 |
April | 0.265663E+10 | 0.127068E+10 | 0.138595E+10 | 0.266022E+10 | 0.205254E+10 |
May | 0.243903E+10 | 0.810068E+09 | 0.162896E+10 | 0.245440E+10 | 0.172009E+10 |
June | 0.234525E+10 | 0.683985E+09 | 0.166126E+10 | 0.273822E+10 | 0.117760E+10 |
July | 0.261269E+10 | 0.965120E+09 | 0.164757E+10 | 0.351354E+10 | 0.987114E+09 |
August | 0.310501E+10 | 0.156549E+10 | 0.153952E+10 | 0.407207E+10 | 0.111995E+10 |
September | 0.333274E+10 | 0.204208E+10 | 0.129066E+10 | 0.402117E+10 | 0.149276E+10 |
October | 0.360034E+10 | 0.248959E+10 | 0.111075E+10 | 0.391203E+10 | 0.213267E+10 |
November | 0.317656E+10 | 0.230097E+10 | 0.875588E+09 | 0.308477E+10 | 0.266664E+10 |
December | 0.285294E+10 | 0.206011E+10 | 0.792831E+09 | 0.249761E+10 | 0.374969E+10 |
Annual Sum or Average | 0.359873E+11 | 0.207306E+11 | 0.152567E+11 | 0.380789E+11 | 0.273157E+11 |
Minimum of Months | 0.234525E+10 | 0.683985E+09 | 0.792831E+09 | 0.245440E+10 | 0.987114E+09 |
Maximum of Months | 0.360034E+10 | 0.248959E+10 | 0.166126E+10 | 0.407207E+10 | 0.439488E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442610E+09 | 0.178375E+09 | 0.264235E+09 | 0.166732E+09 | 0.253286E+10 |
February | 0.682358E+09 | 0.335414E+09 | 0.346945E+09 | 0.426847E+09 | 0.166296E+10 |
March | 0.966816E+09 | 0.354256E+09 | 0.612560E+09 | 0.643181E+09 | 0.150261E+10 |
April | 0.122147E+10 | 0.541166E+09 | 0.680301E+09 | 0.108510E+10 | 0.101157E+10 |
May | 0.156123E+10 | 0.712004E+09 | 0.849226E+09 | 0.157509E+10 | 0.833943E+09 |
June | 0.164377E+10 | 0.755043E+09 | 0.888724E+09 | 0.189205E+10 | 0.561308E+09 |
July | 0.173998E+10 | 0.879239E+09 | 0.860745E+09 | 0.223245E+10 | 0.492855E+09 |
August | 0.147748E+10 | 0.725116E+09 | 0.752365E+09 | 0.180902E+10 | 0.548662E+09 |
September | 0.115020E+10 | 0.581495E+09 | 0.568707E+09 | 0.124697E+10 | 0.757490E+09 |
October | 0.849480E+09 | 0.422061E+09 | 0.427420E+09 | 0.706072E+09 | 0.113176E+10 |
November | 0.581953E+09 | 0.288698E+09 | 0.293255E+09 | 0.368637E+09 | 0.151944E+10 |
December | 0.404218E+09 | 0.170609E+09 | 0.233609E+09 | 0.155904E+09 | 0.215008E+10 |
Annual Sum or Average | 0.127216E+11 | 0.594347E+10 | 0.677809E+10 | 0.123081E+11 | 0.147055E+11 |
Minimum of Months | 0.404218E+09 | 0.170609E+09 | 0.233609E+09 | 0.155904E+09 | 0.492855E+09 |
Maximum of Months | 0.173998E+10 | 0.879239E+09 | 0.888724E+09 | 0.223245E+10 | 0.253286E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 929.87 | 3334.98 | 1467.81 | 950.25 | 517.56 | 0.00 | 0.00 |
February | 1598.92 | 2451.65 | 1993.86 | 1306.27 | 687.59 | 0.00 | 0.00 |
March | 1664.99 | 2104.04 | 2019.71 | 1007.04 | 1012.67 | 0.00 | 0.00 |
April | 1798.82 | 1471.67 | 1985.72 | 941.63 | 1044.09 | 0.00 | 0.00 |
May | 1954.36 | 1175.05 | 2034.29 | 808.88 | 1225.41 | 0.00 | 0.00 |
June | 2536.45 | 808.26 | 2238.92 | 915.37 | 1323.54 | 0.00 | 0.00 |
July | 3040.82 | 677.91 | 2359.71 | 1103.90 | 1255.82 | 0.00 | 0.00 |
August | 2933.96 | 768.44 | 2349.32 | 1210.92 | 1138.40 | 0.00 | 0.00 |
September | 2472.15 | 1096.98 | 2181.14 | 1245.30 | 935.84 | 0.00 | 0.00 |
October | 1937.00 | 1567.99 | 1985.38 | 1251.61 | 733.77 | 0.00 | 0.00 |
November | 1331.51 | 2067.30 | 1655.39 | 1094.97 | 560.42 | 0.00 | 0.00 |
December | 906.82 | 2841.32 | 1367.54 | 897.91 | 469.63 | 0.00 | 0.00 |
Annual Sum or Average | 1926.96 | 1694.62 | 1969.21 | 1059.29 | 909.92 | 0.00 | 0.00 |
Minimum of Months | 906.82 | 677.91 | 1367.54 | 808.88 | 469.63 | 0.00 | 0.00 |
Maximum of Months | 3040.82 | 3334.98 | 2359.71 | 1306.27 | 1323.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249057E+10 | 0.893242E+10 | 0.393138E+10 | 0.254514E+10 | 0.138623E+10 | 0.00 | 0.00 |
February | 0.386810E+10 | 0.593104E+10 | 0.482355E+10 | 0.316014E+10 | 0.166342E+10 | 0.00 | 0.00 |
March | 0.445952E+10 | 0.563546E+10 | 0.540959E+10 | 0.269725E+10 | 0.271235E+10 | 0.00 | 0.00 |
April | 0.466255E+10 | 0.381457E+10 | 0.514699E+10 | 0.244070E+10 | 0.270629E+10 | 0.00 | 0.00 |
May | 0.523455E+10 | 0.314725E+10 | 0.544863E+10 | 0.216651E+10 | 0.328213E+10 | 0.00 | 0.00 |
June | 0.657448E+10 | 0.209501E+10 | 0.580327E+10 | 0.237264E+10 | 0.343063E+10 | 0.00 | 0.00 |
July | 0.814453E+10 | 0.181572E+10 | 0.632026E+10 | 0.295669E+10 | 0.336358E+10 | 0.00 | 0.00 |
August | 0.785832E+10 | 0.205820E+10 | 0.629241E+10 | 0.324332E+10 | 0.304909E+10 | 0.00 | 0.00 |
September | 0.640781E+10 | 0.284337E+10 | 0.565352E+10 | 0.322782E+10 | 0.242570E+10 | 0.00 | 0.00 |
October | 0.518807E+10 | 0.419971E+10 | 0.531765E+10 | 0.335232E+10 | 0.196533E+10 | 0.00 | 0.00 |
November | 0.345128E+10 | 0.535844E+10 | 0.429078E+10 | 0.283817E+10 | 0.145261E+10 | 0.00 | 0.00 |
December | 0.242883E+10 | 0.761020E+10 | 0.366283E+10 | 0.240496E+10 | 0.125787E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.607686E+11 | 0.534414E+11 | 0.621009E+11 | 0.334056E+11 | 0.286952E+11 | 0.00 | 0.00 |
Minimum of Months | 0.242883E+10 | 0.181572E+10 | 0.366283E+10 | 0.216651E+10 | 0.125787E+10 | 0.00 | 0.00 |
Maximum of Months | 0.814453E+10 | 0.893242E+10 | 0.632026E+10 | 0.335232E+10 | 0.343063E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.158674E+11 | -0.150402E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -827190266.1 | 60.05 | 0.00 | 0.00 |
February | 0.145602E+11 | -0.138203E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -739965281.2 | 60.05 | 0.00 | 0.00 |
March | 0.159964E+11 | -0.151760E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -820371758.0 | 60.05 | 0.00 | 0.00 |
April | 0.148899E+11 | -0.141224E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -767486476.3 | 60.05 | 0.00 | 0.00 |
May | 0.145817E+11 | -0.138179E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -763748597.9 | 60.05 | 0.00 | 0.00 |
June | 0.132683E+11 | -0.125759E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -692445683.4 | 60.05 | 0.00 | 0.00 |
July | 0.130113E+11 | -0.123176E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -693710495.8 | 60.05 | 0.00 | 0.00 |
August | 0.127747E+11 | -0.120751E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -699575302.3 | 60.05 | 0.00 | 0.00 |
September | 0.125208E+11 | -0.118144E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -706397882.1 | 60.05 | 0.00 | 0.00 |
October | 0.135448E+11 | -0.127710E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -773752140.8 | 60.05 | 0.00 | 0.00 |
November | 0.139204E+11 | -0.131422E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -778214823.6 | 60.05 | 0.00 | 0.00 |
December | 0.152046E+11 | -0.143822E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -822332225.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.170140E+12 | -0.161055E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.908519E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.125208E+11 | -0.151760E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -827190266.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.159964E+11 | -0.118144E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -692445683.4 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.462034E+11 | 47772.88 | 02-JAN-03:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268533E+11 | 47772.88 | 01-FEB-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232620E+11 | 47772.88 | 01-MAR-03:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106128E+11 | 47772.88 | 01-APR-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.679237E+10 | 47772.88 | 01-MAY-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.646262E+09 | 27673.21 | 17-JUN-02:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45875755.36 | 18047.43 | 26-JUL-02:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122428E+09 | 17131.04 | 11-AUG-02:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161585E+10 | 21085.94 | 13-SEP-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.617844E+10 | 47772.88 | 04-OCT-02:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164608E+11 | 47772.88 | 02-NOV-02:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.340651E+11 | 47772.88 | 01-DEC-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172859E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 45875755.36 | 17131.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.462034E+11 | 47772.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.506390E+11 | 64930.61 | 11-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289886E+11 | 57144.47 | 01-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.241244E+11 | 54722.24 | 05-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.955171E+10 | 34254.11 | 28-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.586657E+10 | 24487.58 | 08-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.443286E+09 | 18046.42 | 15-JUN-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10600743.63 | 3195.42 | 08-JUL-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23053626.65 | 3163.87 | 17-AUG-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138071E+10 | 14901.19 | 17-SEP-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.553608E+10 | 22308.44 | 10-OCT-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174158E+11 | 43394.27 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367308E+11 | 64432.86 | 29-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10600743.63 | 3163.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.506390E+11 | 64930.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7091058.19 | 7091058.19 | 1366.36 | 27-FEB-15:00 | 1366.36 | 0.00 |
March | 0.00 | 0.00 | 5282.17 | 5282.17 | 9.13 | 28-MAR-16:57 | 9.13 | 0.00 |
April | 0.00 | 0.00 | 0.271899E+09 | 0.271899E+09 | 9231.27 | 07-APR-13:53 | 9231.27 | 0.00 |
May | 0.00 | 0.00 | 0.255001E+10 | 0.253530E+10 | 17298.01 | 19-MAY-17:20 | 17105.31 | 0.00 |
June | 0.00 | 0.00 | 0.974337E+10 | 0.925881E+10 | 37371.76 | 21-JUN-02:61 | 32668.14 | 0.00 |
July | 0.00 | 0.00 | 0.190361E+11 | 0.184218E+11 | 37763.30 | 19-JUL-02:61 | 21420.31 | 0.00 |
August | 0.00 | 0.00 | 0.151416E+11 | 0.150189E+11 | 37371.76 | 06-AUG-02:61 | 34617.94 | 0.00 |
September | 0.00 | 0.00 | 0.769049E+10 | 0.732221E+10 | 37371.76 | 02-SEP-02:61 | 32094.66 | 0.00 |
October | 0.00 | 0.00 | 0.103154E+10 | 0.103154E+10 | 15773.81 | 18-OCT-13:00 | 15773.81 | 0.00 |
November | 0.00 | 0.00 | 35.63 | 35.63 | 0.11 | 07-NOV-17:35 | 0.11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.554721E+11 | 0.538675E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.190361E+11 | 0.184218E+11 | 37763.30 | 34617.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 197146.81 | 140444.09 | 718.02 | 28-FEB-04:30 | 510.74 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 99065893.26 | 98575616.56 | 7300.30 | 07-APR-13:53 | 7300.30 | 0.00 |
May | 0.00 | 0.00 | 0.188937E+10 | 0.187174E+10 | 30421.04 | 14-MAY-02:61 | 23444.60 | 0.00 |
June | 0.00 | 0.00 | 0.803246E+10 | 0.767679E+10 | 30421.04 | 06-JUN-02:11 | 24098.31 | 0.00 |
July | 0.00 | 0.00 | 0.169116E+11 | 0.165367E+11 | 30421.04 | 19-JUL-03:42 | 17894.76 | 0.00 |
August | 0.00 | 0.00 | 0.130382E+11 | 0.129361E+11 | 30421.04 | 07-AUG-02:52 | 29416.36 | 0.00 |
September | 0.00 | 0.00 | 0.652536E+10 | 0.614598E+10 | 30421.04 | 04-SEP-02:24 | 27273.12 | 0.00 |
October | 0.00 | 0.00 | 0.539494E+09 | 0.535249E+09 | 30421.04 | 01-OCT-02:61 | 16764.55 | 0.00 |
November | 0.00 | 0.00 | 3501156.84 | 2968874.66 | 3378.20 | 24-NOV-04:05 | 3378.20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.470392E+11 | 0.458043E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169116E+11 | 0.165367E+11 | 30421.04 | 29416.36 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5600.15 | 21815.89 | 31-JAN-13:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5698.03 | 21934.56 | 18-FEB-13:40 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5650.95 | 21894.24 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5432.44 | 21343.72 | 01-APR-12:47 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5141.67 | 20330.01 | 01-MAY-12:15 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4833.50 | 19073.34 | 01-JUN-12:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4580.32 | 17979.58 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4489.52 | 17281.90 | 01-AUG-12:25 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4539.41 | 17726.59 | 30-SEP-12:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4749.82 | 18764.67 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5052.64 | 19980.32 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5353.39 | 21116.37 | 31-DEC-13:40 |
Annual Sum or Average | 0.00 | 5089.93 | ||||
Minimum of Months | 0.00 | 0.00 | 4489.52 | 17281.90 | ||
Maximum of Months | 0.00 | 0.00 | 5698.03 | 21934.56 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.883346E+10 | 1.42 | 3699.33 | 01-JAN-11:27 | 1.56 |
February | 0.783237E+10 | 1.40 | 3699.33 | 02-FEB-00:08 | 1.57 |
March | 0.867160E+10 | 1.39 | 3699.33 | 11-MAR-09:18 | 1.56 |
April | 0.820641E+10 | 1.37 | 3699.33 | 01-APR-10:30 | 1.56 |
May | 0.841818E+10 | 1.35 | 3699.33 | 01-MAY-08:22 | 1.56 |
June | 0.801771E+10 | 1.32 | 3699.33 | 02-JUN-04:12 | 1.55 |
July | 0.833069E+10 | 1.34 | 3699.33 | 01-JUL-13:50 | 1.54 |
August | 0.832718E+10 | 1.34 | 3699.33 | 18-AUG-06:10 | 1.55 |
September | 0.804330E+10 | 1.34 | 3699.33 | 19-SEP-09:00 | 1.55 |
October | 0.836425E+10 | 1.33 | 3699.33 | 01-OCT-10:33 | 1.55 |
November | 0.822799E+10 | 1.37 | 3699.33 | 01-NOV-04:10 | 1.56 |
December | 0.869481E+10 | 1.39 | 3699.33 | 01-DEC-12:50 | 1.56 |
Annual Sum or Average | 0.999679E+11 | 1.36 | |||
Minimum of Months | 0.783237E+10 | 1.32 | 3699.33 | 1.54 | |
Maximum of Months | 0.883346E+10 | 1.42 | 3699.33 | 1.57 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.570948E+10 | 1.30 | 2558.01 | 01-JAN-00:06 | 1.56 |
February | 0.515704E+10 | 1.30 | 2558.01 | 01-FEB-10:02 | 1.57 |
March | 0.570948E+10 | 1.30 | 2558.01 | 01-MAR-00:03 | 1.56 |
April | 0.553074E+10 | 1.32 | 2558.01 | 01-APR-04:06 | 1.56 |
May | 0.573371E+10 | 1.34 | 2558.01 | 01-MAY-04:06 | 1.56 |
June | 0.560193E+10 | 1.39 | 2558.01 | 02-JUN-05:10 | 1.55 |
July | 0.585399E+10 | 1.43 | 2558.01 | 01-JUL-08:40 | 1.54 |
August | 0.584179E+10 | 1.42 | 2558.01 | 01-AUG-14:33 | 1.55 |
September | 0.561158E+10 | 1.39 | 2558.01 | 01-SEP-08:32 | 1.55 |
October | 0.573321E+10 | 1.35 | 2558.01 | 01-OCT-04:10 | 1.55 |
November | 0.553087E+10 | 1.32 | 2558.01 | 01-NOV-20:10 | 1.56 |
December | 0.570948E+10 | 1.30 | 2558.01 | 01-DEC-00:40 | 1.56 |
Annual Sum or Average | 0.677233E+11 | 1.35 | |||
Minimum of Months | 0.515704E+10 | 1.30 | 2558.01 | 1.54 | |
Maximum of Months | 0.585399E+10 | 1.43 | 2558.01 | 1.57 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 50.50 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.75 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.72 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.93 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 50.86 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 52.78 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 53.19 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 53.45 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.48 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 52.01 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 52.88 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 52.42 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 50.50 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.48 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 36.97 | 36.97 | 5600.15 | 21815.89 | 31-JAN-13:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.75 | 51.75 | 5698.03 | 21934.56 | 18-FEB-13:40 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.72 | 51.72 | 5650.95 | 21894.24 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.92 | 51.92 | 5432.44 | 21343.72 | 01-APR-12:47 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 37.81 | 37.81 | 5141.67 | 20330.01 | 01-MAY-12:15 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.76 | 52.76 | 4833.50 | 19073.34 | 01-JUN-12:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.18 | 53.18 | 4580.32 | 17979.58 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.45 | 53.45 | 4489.52 | 17281.90 | 01-AUG-12:25 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.48 | 53.48 | 4539.41 | 17726.59 | 30-SEP-12:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 40.66 | 40.66 | 4749.82 | 18764.67 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.89 | 52.89 | 5052.64 | 19980.32 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 52.44 | 52.44 | 5353.39 | 21116.37 | 31-DEC-13:40 |
Annual Sum or Average | 0.00 | 5089.93 | ||||||
Minimum of Months | 0.00 | 0.00 | 36.97 | 36.97 | 4489.52 | 17281.90 | ||
Maximum of Months | 0.00 | 0.00 | 53.48 | 53.48 | 5698.03 | 21934.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.883346E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.783471E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.867160E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.829050E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.915135E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.107029E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.135913E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.125245E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.101732E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.866926E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.822799E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.869481E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.115366E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.783471E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.135913E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.570948E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.515710E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.570948E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.556169E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.627520E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.779993E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.104947E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.945306E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.740525E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.589507E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.553201E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.570948E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.807024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.515710E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.104947E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.883346E+10 | 0.00 | 0.462034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.783237E+10 | 7091058.19 | 0.268533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.867160E+10 | 5282.17 | 0.232620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.820641E+10 | 0.271899E+09 | 0.106128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.841818E+10 | 0.255001E+10 | 0.679237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.801771E+10 | 0.974337E+10 | 0.646262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.833069E+10 | 0.190361E+11 | 45875755.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.832718E+10 | 0.151416E+11 | 0.122428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.804330E+10 | 0.769049E+10 | 0.161585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.836425E+10 | 0.103154E+10 | 0.617844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.822799E+10 | 35.63 | 0.164608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.869481E+10 | 0.00 | 0.340651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.999679E+11 | 0.554721E+11 | 0.172859E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.783237E+10 | 0.00 | 45875755.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.883346E+10 | 0.190361E+11 | 0.462034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.570948E+10 | 0.00 | 0.506390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.515704E+10 | 197146.81 | 0.289886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.570948E+10 | 0.00 | 0.241244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553074E+10 | 99065893.26 | 0.955171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.573371E+10 | 0.188937E+10 | 0.586657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.560193E+10 | 0.803246E+10 | 0.443286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.585399E+10 | 0.169116E+11 | 10600743.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.584179E+10 | 0.130382E+11 | 23053626.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.561158E+10 | 0.652536E+10 | 0.138071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.573321E+10 | 0.539494E+09 | 0.553608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.553087E+10 | 3501156.84 | 0.174158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.570948E+10 | 0.00 | 0.367308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.677233E+11 | 0.470392E+11 | 0.180711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.515704E+10 | 0.00 | 10600743.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.585399E+10 | 0.169116E+11 | 0.506390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.883346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.783237E+10 | 0.00 | 0.00 | 0.00 | 2339708.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.867160E+10 | 0.00 | 0.00 | 0.00 | 1771.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.820641E+10 | 0.00 | 0.00 | 0.00 | 84090657.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.841818E+10 | 0.00 | 0.00 | 0.00 | 0.733171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.801771E+10 | 0.00 | 0.00 | 0.00 | 0.268523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.833069E+10 | 0.00 | 0.00 | 0.00 | 0.526065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.832718E+10 | 0.00 | 0.00 | 0.00 | 0.419735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.804330E+10 | 0.00 | 0.00 | 0.00 | 0.212988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.836425E+10 | 0.00 | 0.00 | 0.00 | 0.305013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.822799E+10 | 0.00 | 0.00 | 0.00 | 11.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.869481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.999679E+11 | 0.00 | 0.00 | 0.00 | 0.153977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.783237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.883346E+10 | 0.00 | 0.00 | 0.00 | 0.526065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.570948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.515704E+10 | 0.00 | 0.00 | 0.00 | 65386.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.570948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553074E+10 | 0.00 | 0.00 | 0.00 | 30949891.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.573371E+10 | 0.00 | 0.00 | 0.00 | 0.541494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.560193E+10 | 0.00 | 0.00 | 0.00 | 0.219800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.585399E+10 | 0.00 | 0.00 | 0.00 | 0.464067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.584179E+10 | 0.00 | 0.00 | 0.00 | 0.361127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.561158E+10 | 0.00 | 0.00 | 0.00 | 0.179368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.573321E+10 | 0.00 | 0.00 | 0.00 | 0.161860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.553087E+10 | 0.00 | 0.00 | 0.00 | 1139598.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.570948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.677233E+11 | 0.00 | 0.00 | 0.00 | 0.129791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.515704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.585399E+10 | 0.00 | 0.00 | 0.00 | 0.464067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364422E+11 | 0.00 | 0.00 | 3.76 |
February | 0.310856E+10 | 0.00 | 0.00 | 1525315.81 | 0.00 | 0.234240E+11 | 0.121782E+10 | 0.00 | 3.87 |
March | 0.426112E+10 | 0.00 | 0.00 | 782607.48 | 0.00 | 0.227562E+11 | 0.823645E+09 | 0.00 | 3.73 |
April | 0.454861E+10 | 0.00 | 0.00 | 7164844.21 | 0.00 | 0.121881E+11 | 0.407895E+10 | 0.00 | 4.61 |
May | 0.502937E+10 | 8576049.65 | 0.00 | 19058445.04 | 0.00 | 0.766573E+10 | 0.661093E+10 | 0.00 | 5.82 |
June | 0.338953E+10 | 0.225854E+09 | 76593.78 | 35305223.27 | 0.00 | 0.705921E+09 | 0.907325E+10 | 15483.51 | 7.17 |
July | 0.153826E+10 | 0.757883E+09 | 492053.16 | 48941527.32 | 0.00 | 1065708.27 | 0.811697E+10 | 102743.35 | 7.20 |
August | 0.217008E+10 | 0.488471E+09 | 0.00 | 45871520.92 | 0.00 | 0.121084E+09 | 0.967289E+10 | 0.00 | 7.56 |
September | 0.388683E+10 | 0.268996E+09 | 177156.96 | 29213563.21 | 0.00 | 0.198799E+10 | 0.892938E+10 | 29017.12 | 6.69 |
October | 0.634964E+10 | 0.00 | 0.00 | 11417826.78 | 0.00 | 0.718308E+10 | 0.601587E+10 | 0.00 | 4.99 |
November | 0.541178E+10 | 0.00 | 0.00 | 1088579.25 | 0.00 | 0.162745E+11 | 0.153226E+10 | 0.00 | 3.76 |
December | 0.293416E+10 | 0.00 | 0.00 | 22023.69 | 0.00 | 0.293323E+11 | 52377899.66 | 0.00 | 3.71 |
Annual Sum or Average | 0.446901E+11 | 0.174978E+10 | 745803.90 | 0.200391E+09 | 0.00 | 0.158082E+12 | 0.561243E+11 | 147243.97 | 5.25 |
Minimum of Months | 0.153826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1065708.27 | 0.00 | 0.00 | 3.71 |
Maximum of Months | 0.634964E+10 | 0.757883E+09 | 492053.16 | 48941527.32 | 0.00 | 0.364422E+11 | 0.967289E+10 | 102743.35 | 7.56 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.837327E+11 | 0.00 | 0.00 | 6832.33 | 0.00 | 0.120979E+09 | 4739437.88 | 0.00 | 9.65 |
February | 0.593358E+11 | 0.00 | 0.00 | 474899.95 | 0.00 | 58096921.29 | 0.836107E+09 | 0.00 | 9.64 |
March | 0.590872E+11 | 0.00 | 0.00 | 62123.65 | 0.00 | 38438500.92 | 0.324440E+09 | 0.00 | 9.70 |
April | 0.393742E+11 | 0.00 | 0.00 | 5968700.12 | 0.00 | 12341628.94 | 0.524736E+10 | 0.00 | 9.82 |
May | 0.305944E+11 | 0.00 | 0.00 | 25708750.76 | 0.00 | 4419352.55 | 0.110664E+11 | 0.00 | 10.29 |
June | 0.122585E+11 | 33184124.88 | 0.00 | 56807684.12 | 0.00 | 0.00 | 0.179952E+11 | 0.00 | 10.87 |
July | 0.572880E+10 | 0.454665E+09 | 0.00 | 83124383.98 | 0.00 | 0.00 | 0.181210E+11 | 0.00 | 11.10 |
August | 0.748422E+10 | 0.285631E+09 | 0.00 | 73233758.20 | 0.00 | 0.00 | 0.198522E+11 | 0.00 | 11.15 |
September | 0.160986E+11 | 0.132338E+09 | 0.00 | 43998824.04 | 0.00 | 0.00 | 0.167735E+11 | 0.00 | 10.73 |
October | 0.334161E+11 | 0.00 | 0.00 | 12425602.47 | 0.00 | 0.00 | 0.101214E+11 | 0.00 | 10.02 |
November | 0.495598E+11 | 0.00 | 0.00 | 1614043.20 | 0.00 | 20642194.19 | 0.332029E+10 | 0.00 | 9.66 |
December | 0.710021E+11 | 0.00 | 0.00 | 40002.60 | 0.00 | 67488813.77 | 0.262827E+09 | 0.00 | 9.69 |
Annual Sum or Average | 0.467672E+12 | 0.905819E+09 | 0.00 | 0.303466E+09 | 0.00 | 0.322406E+09 | 0.103925E+12 | 0.00 | 10.20 |
Minimum of Months | 0.572880E+10 | 0.00 | 0.00 | 6832.33 | 0.00 | 0.00 | 4739437.88 | 0.00 | 9.64 |
Maximum of Months | 0.837327E+11 | 0.454665E+09 | 0.00 | 83124383.98 | 0.00 | 0.120979E+09 | 0.198522E+11 | 0.00 | 11.15 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.156396E+11 | 0.232251E+11 | 0.149531E+12 | 0.00 | 0.389363E+11 |
February | 0.227634E+11 | 0.166462E+11 | 0.107235E+12 | 0.443864E+09 | 0.275803E+11 |
March | 0.407734E+11 | 0.163605E+11 | 0.105979E+12 | 95410703.84 | 0.279427E+11 |
April | 0.455405E+11 | 0.116927E+11 | 0.796176E+11 | 0.218757E+10 | 0.220320E+11 |
May | 0.620603E+11 | 0.102836E+11 | 0.725292E+11 | 0.485364E+10 | 0.278517E+11 |
June | 0.685661E+11 | 0.607855E+10 | 0.513429E+11 | 0.713970E+10 | 0.439322E+11 |
July | 0.680481E+11 | 0.356537E+10 | 0.386703E+11 | 0.671669E+10 | 0.701998E+11 |
August | 0.557757E+11 | 0.445055E+10 | 0.448429E+11 | 0.800078E+10 | 0.581046E+11 |
September | 0.407480E+11 | 0.690413E+10 | 0.564375E+11 | 0.655821E+10 | 0.369850E+11 |
October | 0.248083E+11 | 0.106666E+11 | 0.778961E+11 | 0.336527E+10 | 0.201187E+11 |
November | 0.120614E+11 | 0.138665E+11 | 0.949013E+11 | 0.377249E+09 | 0.213768E+11 |
December | 0.924641E+10 | 0.191621E+11 | 0.126850E+12 | 0.00 | 0.314801E+11 |
Annual Sum or Average | 0.466031E+12 | 0.142902E+12 | 0.100583E+13 | 0.397384E+11 | 0.426540E+12 |
Minimum of Months | 0.924641E+10 | 0.356537E+10 | 0.386703E+11 | 0.00 | 0.201187E+11 |
Maximum of Months | 0.685661E+11 | 0.232251E+11 | 0.149531E+12 | 0.800078E+10 | 0.701998E+11 |