Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:19:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1206.33 | 5192.01 | 5192.01 |
Net Site Energy | 1206.33 | 5192.01 | 5192.01 |
Total Source Energy | 2657.33 | 11437.12 | 11437.12 |
Net Source Energy | 2657.33 | 11437.12 | 11437.12 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 265.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 239.49 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 70.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 106.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 40.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 647.95 | 558.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 265.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 10.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 220.85 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 70.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 106.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 13.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 19.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 265.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 10.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 239.49 | 451.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 70.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 106.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 40.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 137.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1444.89 | 460.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1206.37 | 1942.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2788.76 | 2403.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 137.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1444.89 | 460.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1206.37 | 1942.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2788.76 | 2403.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 647.948 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 647.948 | 100.00 |
Total On-Site and Utility Electric Sources | 647.948 | 100.00 |
Total Electricity End Uses | 647.948 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 2128.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6861.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1_SUPPHEATCOIL | PSZ-AC_2:2_SUPPHEATCOIL | PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.0792 | 1.33 | 110.4804 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.6205 | 18.52 | 1009.9592 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.8498 | 2.48 | 560.2198 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.8498 | 2.48 | 560.2198 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.0792 | 1.33 | 110.4804 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6205 | 18.52 | 1009.9592 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 6.8498 | 1.24 | 560.2198 | |||||||
Conditioned Total | 232.34 | 6.8498 | 1.24 | 560.2198 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 6.8498 | 2.48 | 560.2198 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-11:00 | 12-JAN-13:20 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27019.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 989.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 12081.43 | 21742.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14957.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1268.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 45583.88 | 36699.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 27019.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 989.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 11490.63 | 21742.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 14957.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 437.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 839.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 67.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 33.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 758.45 | 489.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 223.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 115.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 129.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2052.05 | 605.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3613.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 289.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 145.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3264.36 | 2105.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 962.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 499.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 556.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8831.99 | 2605.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3613.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 289.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 145.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3264.36 | 2105.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 962.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 499.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 556.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8831.99 | 2605.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.47 |
KITCHEN DIRECT AIR | 1.14 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.47 | 2.47 | 2.47 | 2.47 | 2.47 | 2.47 | 1.00 | 1.00 | 2.47 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.47 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.14 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.47 | 2644.07 |
PSZ-AC_2:2_ADDAQ FAN | 1.14 | 1263.64 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.47 | 2.47 | 2.47 | 1.63 | 61360.31 | 41111.41 | 40.00 | 61360.31 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.753280 | 28342.03 | 18989.16 | 40.00 | 28342.03 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 HP COOLING COIL | 2.47 | 1.24 | 1.65 | 61360.31 | 30680.15 | 0.701080 | 0.701080 |
PSZ-AC_2:2 HP COOLING COIL | 1.14 | 0.570667 | 0.760887 | 28342.03 | 14171.01 | 0.701080 | 0.701080 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | Design Size Speed 2 Gross Rated Heating Capacity [W] | Design Size Speed 1 Gross Rated Heating Capacity [W] | Design Size Resistive Defrost Heater Capacity | |
PSZ-AC_1:1 HEATING COIL | 2.47 | 1.24 | 61360.31 | 30680.16 | 0.000000 |
PSZ-AC_2:2 HEATING COIL | 1.14 | 0.570667 | 28341.94 | 14170.97 | 0.000000 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_SUPPHEATCOIL | 61360.31 |
PSZ-AC_2:2_SUPPHEATCOIL | 28342.03 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.079 | 110.480 | 0.000 | 0.000 | 0.000 | 0.000 | 114.560 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.620 | 261.340 | 748.620 | 0.000 | 0.000 | 0.000 | 1019.580 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 473.883 | 4.079 | 5.413 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 473.883 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1117.624 | 9.620 | 178.156 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1117.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 12834.676 | 110.480 | 146.608 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3722.056 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 29769.412 | 256.254 | 4745.415 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 8633.129 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 86968.240 | 748.620 | 13863.236 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 25220.790 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.6929 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.33002231E-12 | 0.10712597E-14 | -0.10720425E-12 | 0.10137879E-15 |
34 | 6 | 0.29661659E-07 | 0.19687232E-09 | 0.67865745E-08 | -0.14052424E-12 |
35 | 5 | -0.19512200E-03 | 0.16741682E-05 | -0.10029371E-03 | 0.67057946E-08 |
36 | 4 | 0.29799499 | 0.81016957E-03 | 0.10178761 | -0.34398158E-04 |
37 | 3 | -7.3821031 | 0.24971312E-01 | -2.3732702 | 0.29576512E-01 |
38 | 2 | 41.252923 | 0.88368331E-01 | 15.405914 | -0.33759269 |
39 | 1 | -80.838295 | 0.39713828E-01 | -29.267905 | 1.0848528 |
40 | 0 | 46.824337 | 0.79570062E-03 | 16.288235 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.22 | 38 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.221 | ||
2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.22 | 39 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.221 | ||
3 | NONRESWINDOW_U_0.503_SHGC_EAST_0.22 | 40 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.221 | ||
4 | NONRESWINDOW_U_0.503_SHGC_WEST_0.22 | 41 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93472E-002 | 0.13126 | 0.64057 | 0.64057 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93472E-002 | 0.13126 | 0.64057 | 0.64057 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93472E-002 | 0.13126 | 0.64057 | 0.64057 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93472E-002 | 0.13126 | 0.64057 | 0.64057 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 25.539 | 0.6095 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 1.853E-002 | 1.595E-004 | 1.994E-004 | 0.188 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 1.853E-002 | 1.595E-004 | 1.953E-004 | 0.188 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4327E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1168E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3046E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.9918E-003 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1798E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1191E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.6447E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.5811E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.0238E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.9446E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.2657E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.1732E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.4415E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.3903E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0375E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0375E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.3011E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2382E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 7.8234E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0699E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.8061E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.7119E-004 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.5824E-003 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.6448E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 33506.67114 | 33506.67114 | 2.47098 | 2.47098 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 402.05560 | 402.05560 | 1.71854E-002 | 0.41606 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 12.70000 | 9.15345E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16017.69874 | 16017.69874 | 0.98309 | 1.14133 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 41.92700 | 1.07803E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 12.70000 | 9.15345E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 42605.08 | 2.47098 | 2.47098 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 13737.25 | 0.41606 | 0.41606 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 41411.33 | 1.14133 | 1.14133 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 37684.31 | 1.14133 | 1.14133 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.47098 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14133 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.47098 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.47098 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.47098 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.47098 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.47098 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.47098 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14133 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14133 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14133 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14133 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14133 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14133 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.47098 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.14133 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.47098 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.47098 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2644.06517 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.47098 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.47098 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.47098 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.63085 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.47098 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.23549 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.64732 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 61360.31000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30680.15500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 61360.31000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 41111.40923 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 61360.31229 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 2.47098 |
42 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.23549 |
43 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 61360.31229 |
44 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 30680.15614 |
45 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
46 | Coil:Heating:Electric | PSZ-AC_1:1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 61360.31229 |
47 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14133 |
48 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
49 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14133 |
50 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1263.63741 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14133 |
52 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14133 |
53 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14133 |
54 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75328 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14133 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57067 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76089 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28342.03000 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14171.01500 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28342.03000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18989.16004 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 28342.02991 |
66 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
67 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.14133 |
68 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57067 |
69 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 28341.94189 |
70 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 14170.97095 |
71 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
72 | Coil:Heating:Electric | PSZ-AC_2:2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 28342.02991 |
73 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
74 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
75 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
76 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
77 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | 59604.0 | 11.98 | 11.92 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | 27530.8 | 12.17 | 12.11 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | 63345.5 | 34856.3 | 8.05 | 2 |
2 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | 29258.9 | 16099.9 | 8.27 | 2 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_EAST_0.22 | N/A | 2.860 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.22 | N/A | 2.860 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_WEST_0.22 | N/A | 2.860 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.693 | 0.628 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 7.6074576531E-002 | 0.1791898583 | Pass | Pass | 5.7634462756E-002 | 0.1618916951 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2294363249 | 0.6451416277 | Pass | Pass | 0.1288020910 | 0.6172438442 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3905524347 | 0.3156341648 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 481.24 | -125.3 | -258.5 | 0.92 | 0.147077E+11 | 0.147077E+11 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.628 | 0.693 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.503_SHGC_EAST_0.22 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.860 | 0.221 | 0.243 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.22 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.860 | 0.221 | 0.243 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.503_SHGC_WEST_0.22 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.860 | 0.221 | 0.243 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.860 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.860 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.0792 | 116.17 | 473.88 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.54 | 0.0000 | Y | 3.87 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6205 | 116.17 | 1117.62 | LightsWired | LTG_SCH_KITCHEN | 86.84 | 168.00 | 82.89 | 0.0000 | Y | 17.39 |
Interior Lighting Total | 6.8498 | 232.34 | 1591.51 | 21.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 473.88 | 180.08 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 473.88 | 180.08 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 209.35 | AstronomicalClock | - | 48.85 | 48.85 | 1.92 | |
EXTERIOR_LIGHTS_B | 742.80 | AstronomicalClock | - | 83.85 | 62.85 | 8.76 | |
Exterior Lighting Total | 952.15 | 10.68 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 61360.31 | 43018.49 | 18341.82 | 0.70 | 3.85 | |||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28342.03 | 19870.03 | 8472.00 | 0.70 | 3.92 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 HP COOLING COIL | 59604.0 | 11.98 | 11.92 | ||||
PSZ-AC_2:2 HP COOLING COIL | 27530.8 | 12.17 | 12.11 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 63345.5 | 34856.3 | 8.05 | 2 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 29258.9 | 16099.9 | 8.27 | 2 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 61360.31 | 3.60 | |
PSZ-AC_1:1_SUPPHEATCOIL | Coil:Heating:Electric | 61360.31 | 1.00 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 28341.94 | 3.66 | |
PSZ-AC_2:2_SUPPHEATCOIL | Coil:Heating:Electric | 28342.03 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.47 | 2644.07 | 1070.05 | 1.00 | 1.29 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1263.64 | 1107.16 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.95 | 25.54 | 0.61 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 33506.67 | 33506.67 | 288.42 | 2.471 | 2.471 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 23.89 | 23.87 | 0.00847 | 42.80 | 0.01078 | 0.416 | 0.00 |
KITCHEN | 16017.70 | 16017.70 | 137.88 | 0.983 | 1.141 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.11 | 26.10 | 0.00866 | 41.93 | 0.01078 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 402.06 | 402.06 | 3.46 | 0.017 | 0.416 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00825 | 12.70 | 0.00915 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 28.65 | 0.00551 | 12.70 | 0.00915 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.47 | 2.47 | 0.42 | 0.42 | 2.4710 | 2.4710 | 2.4710 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.1413 | 1.1413 | 1.1413 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 61360.310 | 43018.486 | 2.470980 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 30680.15 | 24454.14 | 1.647320 | 27.06 | 17.75 | 0.00886198 | 11.93 | 10.17 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 25.2565 | 23.87 | 0.00847328 | 45.9454 | 33506.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 61360.312 | 61360.312 | 2.470980 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 30680.16 | 30680.16 | 1.235490 | 19.69 | 14.66 | 0.00833251 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 33.6754 | 21.11 | 0.00816630 | 52.3980 | 224.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_1:1 | 61360.312 | 61360.312 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 61360.31 | 61360.31 | 2.470980 | 19.69 | 14.66 | 0.00833251 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 16.8377 | 21.11 | 0.00816630 | 52.3980 | 224.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28342.030 | 19870.030 | 1.141330 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14171.01 | 11059.21 | 0.760887 | 42.80 | 23.86 | 0.01078182 | 11.90 | 10.16 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 150.0005 | 26.09 | 0.00882068 | 41.8747 | 14496.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28342.030 | 28342.030 | 1.141334 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14170.97 | 14170.97 | 0.570667 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 200.0000 | 28.65 | 0.00550560 | 22.6265 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_2:2 | 28342.030 | 28342.030 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 28342.03 | 28342.03 | 1.141334 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 100.0000 | 28.65 | 0.00550560 | 22.6265 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 61360.310 | 43018.486 | 2.470980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3140 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.470980 | 2.97405886 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 30680.15 | 24454.14 | 1.0000 | 1.98270609 | 1.647320 | 27.06 | 17.75 | 0.00886198 | 49796.3 | 11.93 | 10.17 | 0.00700000 | 29649.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30680.15 | 42.80 | 0.01078182 | 23.86 | 0.41605618 | 25.2565 | 23.87 | 0.00847328 | 23.87 | 0.00847328 | 45.9454 | 33506.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 61360.312 | 61360.312 | 2.470980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.470980 | 2.97405886 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 30680.16 | 30680.16 | 1.0000 | 1.48702943 | 1.235490 | 19.69 | 14.66 | 0.00833251 | 40933.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30680.16 | 12.70 | 0.00915345 | 12.70 | 0.41605618 | 33.6754 | 21.11 | 0.00816630 | 21.11 | 0.00816630 | 52.3980 | 224.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61360.312 | 61360.312 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.470980 | 2.97405886 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 61360.31 | 61360.31 | 1.0000 | 2.97405886 | 2.470980 | 19.69 | 14.66 | 0.00833251 | 40933.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61360.31 | 12.70 | 0.00915345 | 12.70 | 0.41605618 | 16.8377 | 21.11 | 0.00816630 | 21.11 | 0.00816630 | 52.3980 | 224.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28342.030 | 19870.030 | 1.141330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8829 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.37370333 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14171.01 | 11059.21 | 1.0000 | 0.91579937 | 0.760887 | 42.80 | 23.86 | 0.01078182 | 70829.7 | 11.90 | 10.16 | 0.00700000 | 29621.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14171.01 | 42.80 | 0.01078182 | 23.86 | 1.14133354 | 150.0005 | 26.04 | 0.00882068 | 26.09 | 0.00882068 | 41.8747 | 14496.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 28342.030 | 28342.030 | 1.141334 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.37370333 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14170.97 | 14170.97 | 1.0000 | 0.68685166 | 0.570667 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14170.97 | 12.70 | 0.00915345 | 12.70 | 1.14133354 | 200.0000 | 0.00 | 0.00550560 | 28.65 | 0.00550560 | 22.6265 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28342.030 | 28342.030 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.141334 | 1.37370333 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 28342.03 | 28342.03 | 1.0000 | 1.37370333 | 1.141334 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28342.03 | 12.70 | 0.00915345 | 12.70 | 1.14133354 | 100.0000 | 0.00 | 0.00550560 | 28.65 | 0.00550560 | 22.6265 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 6702.33 | 3072.50 | 2804.33 |
KITCHEN | 7181.50 | 6860.67 | 6860.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7181.50 | 7112.67 | 6861.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 171.67 | 0.00 | 11.67 |
KITCHEN | 0.00 | 2591.17 | 0.00 | 2121.50 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 2646.33 | 0.00 | 2128.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.366 | 4.069 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.905 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.219 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 7.694 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 11322649.11 | 0.00 | 11322649.11 | 10053500.89 | 21376150.00 | 13120747.55 | 1321.66 | 7435.40 | 2.94 | 591.72 |
KITCHEN | 26084300.89 | 0.00 | 26084300.89 | 33955.51 | 26118256.40 | 35993094.65 | 6148.56 | 2611.44 | 0.00 | 1096.99 |
Total Facility | 37406950.00 | 0.00 | 37406950.00 | 10087456.41 | 47494406.40 | 49113842.20 | 6197.42 | 7485.15 | 2.94 | 1155.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4161 | 0.0000 | 0.4161 | 0.3881 | 0.8042 | 0.4161 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 0.9301 | 0.0000 | 0.9301 | 0.0009 | 0.9310 | 1.1413 | 4751.91 | 2435.09 | 0.00 |
Total Facility | 1.3462 | 0.0000 | 1.3462 | 0.3890 | 1.7352 | 1.5574 | 4751.91 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 16402365.13 | 0.00 | 16402365.13 | 13120747.55 | 1269.75 | 3.42 | 7486.83 | 591.72 |
PSZ-AC_2:2 | 37786784.01 | 0.00 | 37786784.01 | 35993094.65 | 4228.24 | 136.67 | 4395.09 | 1096.99 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6028 | 0.0000 | 0.6028 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3474 | 0.0000 | 1.3474 | 1.1413 | 2954.47 | 128.55 | 4103.98 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 339.36 | 0.00 | 7439.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 2328.10 | 0.00 | 1713.99 | 4241.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 0.6028 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 1.6535 | 0.0000 | 1.1853 | 1.2035 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 389 |
Defaulted Fields | 292 |
Fields with Defaults | 936 |
Autosized Fields | 49 |
Autosizable Fields | 119 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 647.95 | 2893.25 | 26-APR-02:40 | 45583.88 | 16-AUG-12:00 |
Electricity:Building | 268.69 | 1624.98 | 01-JAN-01:20 | 17215.91 | 02-JAN-11:10 |
Electricity:Zone:DINING | 70.41 | 280.44 | 01-JAN-01:20 | 3811.41 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 260.75 | 1488.70 | 01-JAN-01:20 | 13921.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 21.26 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-17:40 |
InteriorLights:Electricity:Zone:DINING | 3.87 | 25.01 | 01-JAN-01:20 | 389.13 | 02-JAN-17:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 21.26 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity | 21.26 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 3.87 | 25.01 | 01-JAN-01:20 | 389.13 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 21.26 | 50.02 | 01-JAN-01:20 | 1285.01 | 02-JAN-17:40 |
Electricity:Zone:KITCHEN | 198.28 | 1344.54 | 01-JAN-01:20 | 13404.50 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.39 | 25.01 | 01-JAN-01:20 | 895.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.39 | 25.01 | 01-JAN-01:20 | 895.88 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 239.49 | 1438.68 | 01-JAN-01:10 | 12932.59 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 66.53 | 255.43 | 01-JAN-01:10 | 3718.02 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 239.49 | 1438.68 | 01-JAN-01:10 | 12932.59 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 220.85 | 847.88 | 01-JAN-01:10 | 12341.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 66.53 | 255.43 | 01-JAN-01:10 | 3718.02 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 220.85 | 847.88 | 01-JAN-01:10 | 12341.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 172.95 | 1183.25 | 01-JAN-01:10 | 9214.57 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 154.32 | 592.45 | 01-JAN-01:10 | 8623.77 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 40.81 | 658.82 | 15-JAN-23:30 | 3931.14 | 10-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 32.87 | 573.04 | 15-JAN-23:30 | 1685.63 | 22-AUG-04:10 |
LowTempRefrigeration:Refrigeration:Electricity | 13.04 | 0.00 | 01-JAN-11:10 | 1048.54 | 22-AUG-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 19.82 | 553.83 | 01-JAN-05:20 | 637.09 | 03-JAN-14:10 |
ElectricityPurchased:Facility | 647.95 | 2893.25 | 26-APR-02:40 | 45583.88 | 16-AUG-12:00 |
ElectricityPurchased:Plant | 647.95 | 2893.25 | 26-APR-02:40 | 45583.88 | 16-AUG-12:00 |
Cogeneration:ElectricityPurchased | 647.95 | 2893.25 | 26-APR-02:40 | 45583.88 | 16-AUG-12:00 |
General:Cogeneration:ElectricityPurchased | 647.95 | 2893.25 | 26-APR-02:40 | 45583.88 | 16-AUG-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 647.95 | 2893.25 | 26-APR-02:40 | 45583.88 | 16-AUG-12:00 |
ElectricityNet:Plant | 647.95 | 2893.25 | 26-APR-02:40 | 45583.88 | 16-AUG-12:00 |
Cogeneration:ElectricityNet | 647.95 | 2893.25 | 26-APR-02:40 | 45583.88 | 16-AUG-12:00 |
General:Cogeneration:ElectricityNet | 647.95 | 2893.25 | 26-APR-02:40 | 45583.88 | 16-AUG-12:00 |
Electricity:HVAC | 335.71 | 0.00 | 01-JAN-01:10 | 31244.24 | 16-AUG-12:00 |
Fans:Electricity | 70.59 | 0.00 | 01-JAN-01:10 | 4411.34 | 06-JUL-17:10 |
General:Fans:Electricity | 70.59 | 0.00 | 01-JAN-01:10 | 4411.34 | 06-JUL-17:10 |
Cooling:Electricity | 265.07 | 0.00 | 01-JAN-00:10 | 27019.53 | 16-AUG-12:00 |
General:Cooling:Electricity | 265.07 | 0.00 | 01-JAN-00:10 | 27019.53 | 16-AUG-12:00 |
Heating:Electricity | 0.04 | 0.00 | 01-JAN-00:10 | 818.81 | 09-JAN-08:00 |
General:Heating:Electricity | 0.04 | 0.00 | 01-JAN-00:10 | 818.81 | 09-JAN-08:00 |
ExteriorLights:Electricity | 10.68 | 0.00 | 01-JAN-07:10 | 952.15 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 10.68 | 0.00 | 01-JAN-07:10 | 952.15 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 31-MAR-09:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 31-MAR-09:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 558.38 | 1739.36 | 01-JAN-02:00 | 36699.37 | 12-JAN-13:20 |
NaturalGas:Building | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 451.39 | 1739.36 | 01-JAN-01:10 | 25220.79 | 01-JAN-11:10 |
NaturalGas:Plant | 106.99 | 0.00 | 01-JAN-02:00 | 14957.31 | 12-JAN-13:20 |
WaterSystems:NaturalGas | 106.99 | 0.00 | 01-JAN-02:00 | 14957.31 | 12-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 106.99 | 0.00 | 01-JAN-02:00 | 14957.31 | 12-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 24-MAR-12:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 24-MAR-12:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 24-MAR-12:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 24-MAR-12:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 24-MAR-12:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 24-MAR-12:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 24-MAR-12:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 24-MAR-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1814.20 | 3645.03 | 20-JAN-01:10 | 137745.35 | 10-AUG-13:00 |
EnergyTransfer:Building | 572.24 | 1822.51 | 20-JAN-01:10 | 41330.01 | 30-AUG-11:10 |
EnergyTransfer:Zone:KITCHEN | 339.84 | 1822.51 | 20-JAN-01:10 | 19471.10 | 09-OCT-10:50 |
Refrigeration:EnergyTransfer | 164.42 | 3543.57 | 15-JAN-23:30 | 7834.84 | 30-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 82.21 | 1771.78 | 15-JAN-23:30 | 3917.42 | 30-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 82.21 | 1771.78 | 15-JAN-23:30 | 3917.42 | 30-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 82.21 | 1771.78 | 15-JAN-23:30 | 3917.42 | 30-JAN-11:40 |
EnergyTransfer:Plant | 175.92 | 1771.78 | 15-JAN-23:30 | 16388.14 | 11-JAN-13:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.57 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.64 | 1631.71 | 01-JAN-05:20 | 2238.70 | 03-JAN-14:10 |
EnergyTransfer:Zone:DINING | 232.40 | 0.00 | 01-JAN-01:10 | 29311.37 | 16-AUG-12:00 |
Heating:EnergyTransfer | 1.27 | 0.00 | 01-JAN-00:10 | 6511.16 | 21-JUL-23:10 |
Heating:EnergyTransfer:Zone:DINING | 1.22 | 0.00 | 01-JAN-00:10 | 4841.43 | 20-JUL-23:10 |
General:Heating:EnergyTransfer | 1.27 | 0.00 | 01-JAN-00:10 | 6511.16 | 21-JUL-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 1.22 | 0.00 | 01-JAN-00:10 | 4841.43 | 20-JUL-23:10 |
Cooling:EnergyTransfer | 488.76 | 0.00 | 01-JAN-01:10 | 37412.59 | 30-AUG-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 231.18 | 0.00 | 01-JAN-01:10 | 29311.37 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer | 488.76 | 0.00 | 01-JAN-01:10 | 37412.59 | 30-AUG-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 231.18 | 0.00 | 01-JAN-01:10 | 29311.37 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.05 | 0.00 | 01-JAN-00:10 | 1722.36 | 21-JUL-23:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.05 | 0.00 | 01-JAN-00:10 | 1722.36 | 21-JUL-23:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 257.58 | 0.00 | 01-JAN-01:10 | 15553.68 | 09-OCT-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 257.58 | 0.00 | 01-JAN-01:10 | 15553.68 | 09-OCT-10:50 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 93.71 | 0.00 | 01-JAN-00:10 | 13836.39 | 12-JAN-13:50 |
PlantLoopHeatingDemand:Plant | 93.71 | 0.00 | 01-JAN-00:10 | 13836.39 | 12-JAN-13:50 |
WaterSystems:PlantLoopHeatingDemand | 93.71 | 0.00 | 01-JAN-00:10 | 13836.39 | 12-JAN-13:50 |
General:WaterSystems:PlantLoopHeatingDemand | 93.71 | 0.00 | 01-JAN-00:10 | 13836.39 | 12-JAN-13:50 |
EnergyTransfer:HVAC | 1066.04 | 0.00 | 01-JAN-00:10 | 96069.08 | 30-AUG-20:00 |
CoolingCoils:EnergyTransfer | 1065.90 | 0.00 | 01-JAN-00:10 | 96069.08 | 30-AUG-20:00 |
HeatingCoils:EnergyTransfer | 0.14 | 0.00 | 01-JAN-00:10 | 2694.51 | 09-JAN-08:00 |
WaterSystems:EnergyTransfer | 93.71 | 0.00 | 01-JAN-00:10 | 13836.39 | 12-JAN-13:50 |
WaterUse:WaterSystems:EnergyTransfer | 93.71 | 0.00 | 01-JAN-00:10 | 13836.39 | 12-JAN-13:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 1.225 | -231.177 | 0.000 | 0.000 | 65.131 | 3.873 | 49.900 | 23.188 | 0.000 | 74.436 | 26.752 | 0.000 | -3.390 | 0.000 | -9.937 | 0.000 |
KITCHEN | 0.000 | 0.000 | 0.049 | -257.578 | 0.000 | 0.000 | 3.576 | 17.389 | 178.354 | 0.000 | 0.000 | 0.120 | 58.190 | 0.000 | 0.000 | 0.000 | -0.101 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.171 | 9.208 | 0.000 | 0.000 | 0.000 | -14.379 | -0.000 |
Total Facility | 0.000 | 0.000 | 1.274 | -488.756 | 0.000 | 0.000 | 68.707 | 21.263 | 228.254 | 23.188 | 0.000 | 79.727 | 94.150 | 0.000 | -3.390 | 0.000 | -24.417 | -0.000 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 11-MAY-02:61 | 0.00 | 0.00 | 0.00 | -39854.47 | 0.00 | 0.00 | 0.00 | 25.01 | 191.57 | 3.25 | 0.00 | 4.20 | 39630.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 01-JAN-03:01 | 0.00 | 0.00 | 0.00 | -38995.00 | 0.00 | 0.00 | 0.00 | 25.01 | 1205.28 | 0.00 | 0.00 | 0.00 | 37790.02 | 0.00 | -0.00 | 0.00 | -25.30 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-MAY-02:61 | 0.00 | 0.00 | 0.00 | -65734.54 | 0.00 | 0.00 | 0.00 | 50.02 | 1396.85 | 3.25 | 0.00 | 418.49 | 63865.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 20-JUL-23:01 | 0.00 | 0.00 | 6578.94 | 0.00 | 0.00 | 0.00 | 306.62 | 64.86 | 288.47 | 555.19 | 0.00 | 10.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7804.47 |
KITCHEN | 21-JUL-23:01 | 0.00 | 0.00 | 9584.91 | 0.00 | 0.00 | 0.00 | 18.35 | 199.08 | 1514.06 | 0.00 | 0.00 | 4.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11321.21 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-JUL-23:01 | 0.00 | 0.00 | 16111.01 | 0.00 | 0.00 | 0.00 | 324.96 | 285.56 | 1802.53 | 565.64 | 0.00 | 369.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19459.58 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4710 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.4710 | 0.1684 | 1.0000 | Not calculated | 0.4161 | 0.1684 | ||
PSZ-AC_2:2 | 1.1413 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1413 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1325 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4710 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.4710 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1684 | ||
PSZ-AC_2:2 | 1.1413 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1413 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1325 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4710 | 2.4710 | 2.4710 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1413 | 1.1413 | 1.1413 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4710 | 2.4710 | 2.4710 | 2.4710 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1413 | 1.1413 | 1.1413 | 1.1413 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4710 | 2.4710 | 2.4710 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1413 | 1.1413 | 1.1413 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4710 | 2.4710 | 2.4710 | 2.4710 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1413 | 1.1413 | 1.1413 | 1.1413 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 2128.33 |
Number of hours not met | 2128.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.04 | 818.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 265.07 | 27019.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 21.26 | 1285.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 10.68 | 952.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 220.85 | 12341.79 | 451.39 | 25220.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 70.59 | 4411.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 106.99 | 14957.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 13.04 | 1048.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 19.82 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 280.29 | 647.95 |
Natural Gas | 451.39 | 558.38 |
Additional | 0.00 | 0.00 |
Total | 731.68 | 1206.33 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 91.51 |
Space Heating | 0.18 |
Space Cooling | 1140.87 |
Fans (All) | 303.83 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1030.74 |
Miscellaneous (All) | 2788.76 |
Subtotal | 2788.76 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 460.48 |
Miscellaneous (All) | 2403.26 |
Subtotal | 2403.26 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.76 |
Space Heating | 0.00 |
Space Cooling | 21.97 |
Fans (All) | 5.85 |
Service Water Heating | 8.87 |
Receptacle Equipment | 57.27 |
Miscellaneous | 4.27 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4528. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8139.50 | 391.67 | 226.50 | 2.33 | 0.00 |
KITCHEN | 5132.50 | 2174.00 | 1327.00 | 126.50 | 0.00 |
ATTIC | 3717.67 | 992.33 | 1336.00 | 1361.17 | 1352.83 |
Min | 3717.67 | 391.67 | 226.50 | 2.33 | 0.00 |
Max | 8139.50 | 2174.00 | 1336.00 | 1361.17 | 1352.83 |
Average | 5663.22 | 1186.00 | 963.17 | 496.67 | 450.94 |
Sum | 16989.67 | 3558.00 | 2889.50 | 1490.00 | 1352.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 253962.33 | 470.00 | 283.33 | 9.33 | 0.00 |
KITCHEN | 10408.83 | 3089.17 | 2420.83 | 339.17 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 253962.33 | 3089.17 | 2420.83 | 339.17 | 0.00 |
Average | 88123.72 | 1186.39 | 901.39 | 116.17 | 0.00 |
Sum | 264371.17 | 3559.17 | 2704.17 | 348.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 4978.00 | 3591.17 | 187.50 | 3.33 | 0.00 |
KITCHEN | 1245.50 | 6535.00 | 884.50 | 95.00 | 0.00 |
ATTIC | 2866.17 | 2232.33 | 1145.67 | 674.17 | 1841.67 |
Min | 1245.50 | 2232.33 | 187.50 | 3.33 | 0.00 |
Max | 4978.00 | 6535.00 | 1145.67 | 674.17 | 1841.67 |
Average | 3029.89 | 4119.50 | 739.22 | 257.50 | 613.89 |
Sum | 9089.67 | 12358.50 | 2217.67 | 772.50 | 1841.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 157058.17 | 97450.17 | 206.00 | 10.67 | 0.00 |
KITCHEN | 1777.33 | 12444.67 | 1767.33 | 268.67 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 157058.17 | 97450.17 | 1767.33 | 268.67 | 0.00 |
Average | 52945.17 | 36631.61 | 657.78 | 93.11 | 0.00 |
Sum | 158835.50 | 109894.83 | 1973.33 | 279.33 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:41
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.853542E+10 | 23945.54 | 25-JAN-03:01 | 19.97 | 14.60 | 0.522854E+10 | 4640.76 | 07-JAN-19:00 | 19.97 | 14.60 |
February | 0.907834E+10 | 21440.76 | 20-FEB-03:01 | 18.65 | 16.28 | 0.477000E+10 | 4640.77 | 25-FEB-19:00 | 20.00 | 14.61 |
March | 0.126957E+11 | 33743.40 | 28-MAR-02:61 | 25.17 | 14.39 | 0.535479E+10 | 4640.76 | 18-MAR-18:49 | 25.17 | 14.39 |
April | 0.164393E+11 | 36230.16 | 29-APR-02:61 | 27.00 | 16.79 | 0.517821E+10 | 4641.29 | 22-APR-18:00 | 27.00 | 16.79 |
May | 0.236983E+11 | 39874.68 | 11-MAY-02:61 | 30.00 | 17.64 | 0.536629E+10 | 4641.00 | 20-MAY-18:40 | 34.27 | 22.96 |
June | 0.252847E+11 | 31852.17 | 02-JUN-02:61 | 29.00 | 16.67 | 0.521927E+10 | 4640.85 | 10-JUN-18:00 | 35.00 | 25.46 |
July | 0.289869E+11 | 34366.91 | 04-JUL-02:61 | 31.67 | 17.57 | 0.534098E+10 | 4641.01 | 15-JUL-18:00 | 40.20 | 25.74 |
August | 0.302220E+11 | 32026.87 | 02-AUG-02:61 | 34.83 | 26.83 | 0.540589E+10 | 4641.00 | 05-AUG-18:40 | 39.67 | 25.55 |
September | 0.257704E+11 | 29375.70 | 02-SEP-02:61 | 31.83 | 23.29 | 0.518793E+10 | 4640.90 | 30-SEP-18:10 | 32.82 | 27.62 |
October | 0.226961E+11 | 36971.10 | 20-OCT-02:61 | 25.67 | 17.74 | 0.533647E+10 | 4641.34 | 21-OCT-18:00 | 29.90 | 20.19 |
November | 0.167517E+11 | 35317.40 | 05-NOV-02:61 | 22.00 | 16.35 | 0.515613E+10 | 4641.46 | 04-NOV-18:49 | 22.00 | 16.35 |
December | 0.110181E+11 | 26852.44 | 01-DEC-03:01 | 18.13 | 12.93 | 0.528475E+10 | 4640.77 | 23-DEC-19:00 | 22.00 | 19.30 |
Annual Sum or Average | 0.231177E+12 | 0.628292E+11 | ||||||||
Minimum of Months | 0.853542E+10 | 21440.76 | 18.13 | 12.93 | 0.477000E+10 | 4640.76 | 19.97 | 14.39 | ||
Maximum of Months | 0.302220E+11 | 39874.68 | 34.83 | 26.83 | 0.540589E+10 | 4641.46 | 40.20 | 27.62 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205854E+11 | 39031.63 | 01-JAN-03:01 | 13.98 | 9.38 | 0.744468E+10 | 4868.93 | 25-JAN-11:20 | 21.67 | 15.59 |
February | 0.186099E+11 | 35563.47 | 13-FEB-03:01 | 13.77 | 11.14 | 0.672828E+10 | 4868.92 | 28-FEB-11:20 | 23.00 | 17.50 |
March | 0.206925E+11 | 35477.86 | 22-MAR-02:11 | 22.00 | 11.54 | 0.745537E+10 | 4880.13 | 27-MAR-10:00 | 38.00 | 18.84 |
April | 0.205167E+11 | 33392.37 | 26-APR-02:61 | 23.02 | 13.04 | 0.721480E+10 | 4903.36 | 28-APR-10:00 | 40.00 | 18.54 |
May | 0.223156E+11 | 26829.48 | 10-MAY-02:61 | 29.17 | 16.95 | 0.746769E+10 | 4925.66 | 30-MAY-10:00 | 36.00 | 26.94 |
June | 0.216773E+11 | 27463.88 | 02-JUN-02:61 | 29.00 | 16.67 | 0.726900E+10 | 4942.54 | 09-JUN-10:50 | 38.63 | 27.06 |
July | 0.219552E+11 | 25415.15 | 03-JUL-02:61 | 30.83 | 17.80 | 0.755204E+10 | 4973.74 | 25-JUL-10:50 | 35.92 | 28.99 |
August | 0.223007E+11 | 17860.76 | 06-AUG-02:61 | 36.83 | 23.47 | 0.757228E+10 | 4975.69 | 08-AUG-10:00 | 35.80 | 29.24 |
September | 0.220131E+11 | 21120.24 | 26-SEP-04:01 | 26.97 | 19.72 | 0.728447E+10 | 4977.36 | 11-SEP-10:00 | 26.97 | 19.72 |
October | 0.233201E+11 | 27895.67 | 21-OCT-02:61 | 23.83 | 16.46 | 0.746919E+10 | 4935.45 | 07-OCT-10:50 | 23.83 | 16.46 |
November | 0.219524E+11 | 30148.86 | 26-NOV-03:11 | 17.90 | 14.94 | 0.721343E+10 | 4909.94 | 01-NOV-10:00 | 17.90 | 14.94 |
December | 0.216422E+11 | 36233.82 | 31-DEC-03:11 | 15.00 | 11.16 | 0.744940E+10 | 4868.95 | 15-DEC-11:39 | 15.00 | 11.16 |
Annual Sum or Average | 0.257581E+12 | 0.881206E+11 | ||||||||
Minimum of Months | 0.186099E+11 | 17860.76 | 13.77 | 9.38 | 0.672828E+10 | 4868.92 | 15.00 | 11.16 | ||
Maximum of Months | 0.233201E+11 | 39031.63 | 36.83 | 23.47 | 0.757228E+10 | 4977.36 | 40.00 | 29.24 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 22.85 | 18.46 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.05 | 20.11 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 | 23.56 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 | 23.24 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 | 27.02 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 | 28.28 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 | 25.04 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 28.98 | 26.77 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 | 21.17 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 21.12 | 15.63 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.00 | 0.00 | 15.70 | 12.84 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 155772.67 | 467.47 | 06-FEB-00:02 | 23.92 |
March | 7595127.75 | 2362.67 | 27-MAR-23:01 | 27.83 |
April | 30807528.50 | 2791.95 | 28-APR-23:01 | 28.83 |
May | 0.159897E+09 | 4625.33 | 11-MAY-23:01 | 33.00 |
June | 0.211080E+09 | 5196.17 | 08-JUN-23:01 | 34.83 |
July | 0.263447E+09 | 6577.84 | 20-JUL-23:01 | 37.67 |
August | 0.246812E+09 | 6309.79 | 05-AUG-23:01 | 37.00 |
September | 0.187940E+09 | 4461.68 | 01-SEP-23:01 | 33.00 |
October | 99998598.10 | 3464.48 | 05-OCT-23:01 | 30.67 |
November | 16294226.68 | 3058.52 | 01-NOV-23:01 | 29.50 |
December | 112547.77 | 482.81 | 12-DEC-00:01 | 23.90 |
Annual Sum or Average | 0.122414E+10 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.263447E+09 | 6577.84 | 37.67 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 174061.37 | 1484.74 | 27-MAR-23:01 | 27.83 |
April | 637896.53 | 2334.84 | 28-APR-23:01 | 28.83 |
May | 11399828.21 | 5958.86 | 11-MAY-23:01 | 33.00 |
June | 10677395.90 | 6059.52 | 08-JUN-23:01 | 34.83 |
July | 8597696.47 | 9582.75 | 21-JUL-23:01 | 37.50 |
August | 6574419.34 | 8321.34 | 05-AUG-23:01 | 37.00 |
September | 6690992.91 | 5418.77 | 01-SEP-23:01 | 33.00 |
October | 4167359.09 | 3550.75 | 05-OCT-23:01 | 30.67 |
November | 503944.76 | 2867.44 | 01-NOV-23:01 | 29.50 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 21.12 |
Annual Sum or Average | 49423594.58 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 11399828.21 | 9582.75 | 37.50 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365119E+09 | 389.13 | 02-JAN-17:40 | 0.565077E+10 | 3718.02 | 01-JAN-11:09 |
February | 0.316555E+09 | 389.13 | 01-FEB-17:00 | 0.510393E+10 | 3718.02 | 01-FEB-11:09 |
March | 0.332410E+09 | 389.13 | 01-MAR-18:19 | 0.565082E+10 | 3718.02 | 01-MAR-11:09 |
April | 0.303102E+09 | 389.13 | 01-APR-18:40 | 0.546849E+10 | 3718.02 | 01-APR-10:09 |
May | 0.301179E+09 | 389.13 | 01-MAY-18:49 | 0.565080E+10 | 3718.02 | 01-MAY-10:09 |
June | 0.284297E+09 | 389.13 | 01-JUN-19:10 | 0.546853E+10 | 3718.02 | 01-JUN-10:09 |
July | 0.296912E+09 | 389.13 | 01-JUL-19:10 | 0.565075E+10 | 3718.02 | 01-JUL-10:09 |
August | 0.310430E+09 | 389.13 | 01-AUG-18:00 | 0.565082E+10 | 3718.02 | 01-AUG-10:09 |
September | 0.308295E+09 | 389.13 | 01-SEP-18:40 | 0.546849E+10 | 3718.02 | 01-SEP-10:09 |
October | 0.338100E+09 | 389.13 | 02-OCT-17:00 | 0.565077E+10 | 3718.02 | 01-OCT-10:09 |
November | 0.347747E+09 | 389.13 | 01-NOV-17:40 | 0.546851E+10 | 3718.02 | 01-NOV-10:09 |
December | 0.369027E+09 | 389.13 | 01-DEC-17:30 | 0.565075E+10 | 3718.02 | 01-DEC-11:09 |
Annual Sum or Average | 0.387317E+10 | 0.665334E+11 | ||||
Minimum of Months | 0.284297E+09 | 389.13 | 0.510393E+10 | 3718.02 | ||
Maximum of Months | 0.369027E+09 | 389.13 | 0.565082E+10 | 3718.02 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146885E+10 | 895.88 | 02-JAN-10:09 | 0.146891E+11 | 9214.57 | 01-JAN-11:09 |
February | 0.133058E+10 | 895.88 | 01-FEB-10:09 | 0.132676E+11 | 9214.57 | 01-FEB-11:09 |
March | 0.149423E+10 | 895.88 | 01-MAR-10:09 | 0.146892E+11 | 9214.57 | 01-MAR-11:09 |
April | 0.142731E+10 | 895.88 | 01-APR-16:10 | 0.142152E+11 | 9214.57 | 01-APR-10:09 |
May | 0.148154E+10 | 895.88 | 01-MAY-09:09 | 0.146891E+11 | 9214.57 | 01-MAY-10:09 |
June | 0.144409E+10 | 895.88 | 01-JUN-09:09 | 0.142153E+11 | 9214.57 | 01-JUN-10:09 |
July | 0.146494E+10 | 895.88 | 01-JUL-16:10 | 0.146890E+11 | 9214.57 | 01-JUL-10:09 |
August | 0.149423E+10 | 895.88 | 01-AUG-09:09 | 0.146892E+11 | 9214.57 | 01-AUG-10:09 |
September | 0.142766E+10 | 895.88 | 01-SEP-09:09 | 0.142152E+11 | 9214.57 | 01-SEP-10:09 |
October | 0.146867E+10 | 895.88 | 02-OCT-09:09 | 0.146891E+11 | 9214.57 | 01-OCT-10:09 |
November | 0.142226E+10 | 895.88 | 01-NOV-09:09 | 0.142153E+11 | 9214.57 | 01-NOV-10:09 |
December | 0.146511E+10 | 895.88 | 01-DEC-10:09 | 0.146890E+11 | 9214.57 | 01-DEC-11:09 |
Annual Sum or Average | 0.173895E+11 | 0.172953E+12 | ||||
Minimum of Months | 0.133058E+10 | 895.88 | 0.132676E+11 | 9214.57 | ||
Maximum of Months | 0.149423E+10 | 895.88 | 0.146892E+11 | 9214.57 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.365119E+09 | 0.565077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97659549.20 | 0.346342E+10 |
February | 0.852256E+10 | 0.316555E+09 | 0.510393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609819E+09 | 0.233507E+10 |
March | 0.954557E+10 | 0.332410E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188071E+10 | 0.130461E+10 |
April | 0.915225E+10 | 0.303102E+09 | 0.546849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453213E+10 | 0.316617E+09 |
May | 0.947560E+10 | 0.301179E+09 | 0.565080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953373E+10 | 22212965.21 |
June | 0.922788E+10 | 0.284297E+09 | 0.546853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105893E+11 | 1821371.30 |
July | 0.939996E+10 | 0.296912E+09 | 0.565075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126592E+11 | 0.00 |
August | 0.954557E+10 | 0.310430E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130383E+11 | 0.00 |
September | 0.915225E+10 | 0.308295E+09 | 0.546849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997688E+10 | 1020095.60 |
October | 0.940563E+10 | 0.338100E+09 | 0.565077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740991E+10 | 30146170.44 |
November | 0.909363E+10 | 0.347747E+09 | 0.546851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351008E+10 | 0.341615E+09 |
December | 0.939996E+10 | 0.369027E+09 | 0.565075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597919E+09 | 0.212077E+10 |
Annual Sum or Average | 0.111326E+12 | 0.387317E+10 | 0.665334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744356E+11 | 0.993731E+10 |
Minimum of Months | 0.852256E+10 | 0.284297E+09 | 0.510393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97659549.20 | 0.00 |
Maximum of Months | 0.954557E+10 | 0.369027E+09 | 0.565082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130383E+11 | 0.346342E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.146885E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 27911.34 | 22812301.30 |
February | 0.610713E+09 | 0.133058E+10 | 0.971608E+10 | 0.103882E+11 | 0.00 | 0.00 | 0.00 | 733719.65 | 22623632.39 |
March | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 2852334.27 | 14538030.98 |
April | 0.655836E+09 | 0.142731E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 6758292.61 | 8017053.60 |
May | 0.679007E+09 | 0.148154E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 16728802.98 | 1768204.00 |
June | 0.661256E+09 | 0.144409E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 18986209.07 | 878459.44 |
July | 0.673587E+09 | 0.146494E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 22353519.31 | 148431.73 |
August | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 22107226.10 | 139823.92 |
September | 0.655836E+09 | 0.142766E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 15076325.62 | 928768.62 |
October | 0.673993E+09 | 0.146867E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 10370851.50 | 3108993.52 |
November | 0.651635E+09 | 0.142226E+10 | 0.104101E+11 | 0.111302E+11 | 0.00 | 0.00 | 0.00 | 3777579.30 | 8111759.57 |
December | 0.673587E+09 | 0.146511E+10 | 0.107571E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 277222.13 | 17996294.23 |
Annual Sum or Average | 0.797748E+10 | 0.173895E+11 | 0.126656E+12 | 0.135417E+12 | 0.00 | 0.00 | 0.00 | 0.120050E+09 | 0.101072E+09 |
Minimum of Months | 0.610713E+09 | 0.133058E+10 | 0.971608E+10 | 0.103882E+11 | 0.00 | 0.00 | 0.00 | 27911.34 | 139823.92 |
Maximum of Months | 0.684021E+09 | 0.149423E+10 | 0.107572E+11 | 0.115012E+11 | 0.00 | 0.00 | 0.00 | 22353519.31 | 22812301.30 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442079E+09 | 0.911983E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351151E+09 | 0.972121E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434120E+09 | 0.124392E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421129E+09 | 0.136013E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413291E+09 | 0.149944E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402993E+09 | 0.145160E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396900E+09 | 0.147967E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406341E+09 | 0.140033E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439237E+09 | 0.123786E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505789E+09 | 0.110384E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507248E+09 | 0.891301E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450651E+09 | 0.826394E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517093E+10 | 0.143786E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351151E+09 | 0.826394E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507248E+09 | 0.149944E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 389.13 | 02-JAN-17:40 | 3718.02 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3242.61 | 23-JAN-14:00 | 5307.47 | 16-JAN-07:10 |
February | 9454.80 | 04-FEB-19:10 | 389.13 | 01-FEB-17:00 | 3718.02 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6320.21 | 06-FEB-14:00 | 4990.72 | 20-FEB-21:00 |
March | 9454.80 | 04-MAR-19:10 | 389.13 | 01-MAR-18:19 | 3718.02 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11942.47 | 27-MAR-11:02 | 4979.80 | 05-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 389.13 | 01-APR-18:40 | 3718.02 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15223.51 | 28-APR-11:55 | 3524.55 | 01-APR-06:10 |
May | 9454.80 | 06-MAY-18:10 | 389.13 | 01-MAY-18:49 | 3718.02 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15216.14 | 31-MAY-19:00 | 1706.16 | 01-MAY-06:10 |
June | 9454.80 | 03-JUN-18:10 | 389.13 | 01-JUN-19:10 | 3718.02 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15871.54 | 12-JUN-12:00 | 1436.60 | 22-JUN-08:00 |
July | 9454.80 | 01-JUL-18:10 | 389.13 | 01-JUL-19:10 | 3718.02 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18097.28 | 21-JUL-11:55 | 0.00 | 01-JUL-00:02 |
August | 9454.80 | 05-AUG-18:10 | 389.13 | 01-AUG-18:00 | 3718.02 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18213.50 | 16-AUG-11:53 | 0.00 | 01-AUG-00:01 |
September | 9454.80 | 02-SEP-18:10 | 389.13 | 01-SEP-18:40 | 3718.02 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14439.35 | 26-SEP-12:00 | 327.54 | 25-SEP-06:10 |
October | 9454.80 | 07-OCT-18:10 | 389.13 | 02-OCT-17:00 | 3718.02 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12025.56 | 04-OCT-12:00 | 2010.93 | 29-OCT-07:00 |
November | 9454.80 | 04-NOV-18:10 | 389.13 | 01-NOV-17:40 | 3718.02 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7520.69 | 01-NOV-11:55 | 3501.36 | 26-NOV-07:10 |
December | 9454.80 | 02-DEC-19:10 | 389.13 | 01-DEC-17:30 | 3718.02 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3821.15 | 01-DEC-13:00 | 5324.14 | 15-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 389.13 | 3718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 3242.61 | 0.00 | |||||
Maximum of Months | 9454.80 | 389.13 | 3718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 18213.50 | 5324.14 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 895.88 | 02-JAN-10:09 | 6627.44 | 01-JAN-11:09 | 7566.24 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 2.57 | 23-JAN-13:50 | 117.69 | 18-JAN-03:10 |
February | 677.52 | 04-FEB-19:10 | 895.88 | 01-FEB-10:09 | 6627.44 | 01-FEB-11:09 | 7566.24 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 12.34 | 05-FEB-14:55 | 91.61 | 10-FEB-04:30 |
March | 677.52 | 04-MAR-19:10 | 895.88 | 01-MAR-10:09 | 6627.44 | 01-MAR-11:09 | 7566.24 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 34.18 | 02-MAR-04:00 | 66.69 | 15-MAR-02:10 |
April | 677.52 | 01-APR-18:10 | 895.88 | 01-APR-16:10 | 6627.44 | 01-APR-10:09 | 7566.24 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 30.85 | 28-APR-13:20 | 66.56 | 05-APR-01:00 |
May | 677.52 | 06-MAY-18:10 | 895.88 | 01-MAY-09:09 | 6627.44 | 01-MAY-10:09 | 7566.24 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 86.55 | 21-MAY-12:55 | 29.28 | 02-MAY-02:00 |
June | 677.52 | 03-JUN-18:10 | 895.88 | 01-JUN-09:09 | 6627.44 | 01-JUN-10:09 | 7566.24 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 63.40 | 09-JUN-02:50 | 35.78 | 06-JUN-04:00 |
July | 677.52 | 01-JUL-18:10 | 895.88 | 01-JUL-16:10 | 6627.44 | 01-JUL-10:09 | 7566.24 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 53.67 | 15-JUL-02:10 | 19.31 | 18-JUL-04:00 |
August | 677.52 | 05-AUG-18:10 | 895.88 | 01-AUG-09:09 | 6627.44 | 01-AUG-10:09 | 7566.24 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 47.65 | 02-AUG-02:10 | 20.66 | 08-AUG-04:00 |
September | 677.52 | 02-SEP-18:10 | 895.88 | 01-SEP-09:09 | 6627.44 | 01-SEP-10:09 | 7566.24 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 35.76 | 13-SEP-03:51 | 22.73 | 28-SEP-03:20 |
October | 677.52 | 07-OCT-18:10 | 895.88 | 02-OCT-09:09 | 6627.44 | 01-OCT-10:09 | 7566.24 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 29.27 | 19-OCT-14:53 | 43.00 | 20-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 895.88 | 01-NOV-09:09 | 6627.44 | 01-NOV-10:09 | 7566.24 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 12.47 | 19-NOV-13:55 | 43.86 | 29-NOV-03:10 |
December | 677.52 | 02-DEC-19:10 | 895.88 | 01-DEC-10:09 | 6627.44 | 01-DEC-11:09 | 7566.24 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 4.77 | 10-DEC-13:00 | 80.49 | 15-DEC-03:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 895.88 | 6627.44 | 7566.24 | 0.00 | 0.00 | 0.00 | 2.57 | 19.31 | ||||||
Maximum of Months | 677.52 | 895.88 | 6627.44 | 7566.24 | 0.00 | 0.00 | 0.00 | 86.55 | 117.69 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.57 | 03-JAN-07:10 | 1729.57 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.34 | 15-FEB-07:52 | 1838.13 | 22-FEB-13:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.95 | 27-MAR-06:53 | 2076.41 | 30-MAR-13:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.47 | 26-APR-06:00 | 2124.02 | 30-APR-13:23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.90 | 28-MAY-03:51 | 2082.92 | 03-MAY-12:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.96 | 29-JUN-02:55 | 2118.88 | 27-JUN-12:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.77 | 04-JUL-04:30 | 2146.62 | 20-JUL-14:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.39 | 05-AUG-01:51 | 2039.06 | 04-AUG-13:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.54 | 30-SEP-07:51 | 1880.13 | 17-SEP-13:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786.88 | 29-OCT-04:55 | 1725.92 | 04-OCT-13:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.45 | 17-NOV-01:00 | 1562.92 | 07-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.88 | 30-DEC-07:20 | 1646.74 | 25-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.39 | 1562.92 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.90 | 2146.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23945.54 | 25-JAN-03:01 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.68 |
February | 21440.76 | 20-FEB-03:01 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.68 |
March | 33743.40 | 28-MAR-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 | 0.00 |
April | 36230.16 | 29-APR-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 | 0.00 |
May | 39874.68 | 11-MAY-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 | 0.00 |
June | 31852.17 | 02-JUN-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 0.00 |
July | 34366.91 | 04-JUL-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 0.00 |
August | 32026.87 | 02-AUG-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 50.22 | 0.00 |
September | 29375.70 | 02-SEP-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
October | 36971.10 | 20-OCT-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
November | 35317.40 | 05-NOV-02:61 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 |
December | 26852.44 | 01-DEC-03:01 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 21440.76 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39874.68 | 0.00 | 250.09 | 2554.29 | 0.00 | 0.00 | 0.00 | 0.00 | 50.22 | 19.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39031.63 | 01-JAN-03:01 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.30 |
February | 35563.47 | 13-FEB-03:01 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 |
March | 35477.86 | 22-MAR-02:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.97 |
April | 33392.37 | 26-APR-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 |
May | 26829.48 | 10-MAY-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 27463.88 | 02-JUN-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 25415.15 | 03-JUL-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 5.02 | 0.00 |
August | 17860.76 | 06-AUG-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 14.58 | 0.00 |
September | 21120.24 | 26-SEP-04:01 | 263.48 | 175.06 | 21621.04 | 21916.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 27895.67 | 21-OCT-02:61 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
November | 30148.86 | 26-NOV-03:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.57 |
December | 36233.82 | 31-DEC-03:11 | 0.00 | 250.09 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 17860.76 | 0.00 | 175.06 | 10055.18 | 5218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39031.63 | 263.48 | 250.09 | 21621.04 | 21916.00 | 0.00 | 0.00 | 0.00 | 14.58 | 62.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.87 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.24 | 0.00 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.46 | 0.00 |
April | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.92 | 0.00 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.23 | 0.00 |
June | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.18 | 0.00 |
July | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.86 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.24 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.26 | 0.00 |
October | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.93 | 0.00 |
November | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.11 | 0.00 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.86 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.375212E+11 | 26967.99 | 30-JAN-11:20 | 0.492416E+11 | 36699.37 | 12-JAN-13:20 |
February | 0.357300E+11 | 29351.26 | 07-FEB-11:20 | 0.442180E+11 | 36535.44 | 01-FEB-13:20 |
March | 0.423998E+11 | 33923.17 | 27-MAR-11:20 | 0.483014E+11 | 35751.77 | 01-MAR-13:20 |
April | 0.468223E+11 | 37463.25 | 28-APR-11:00 | 0.458376E+11 | 34747.03 | 02-APR-12:00 |
May | 0.585723E+11 | 41283.15 | 31-MAY-11:00 | 0.464785E+11 | 33896.44 | 01-MAY-10:30 |
June | 0.645074E+11 | 42587.04 | 09-JUN-11:00 | 0.443475E+11 | 32909.84 | 01-JUN-10:20 |
July | 0.732983E+11 | 43665.84 | 18-JUL-11:00 | 0.455779E+11 | 32606.46 | 28-JUL-10:00 |
August | 0.752597E+11 | 45583.88 | 16-AUG-11:00 | 0.458798E+11 | 33177.88 | 31-AUG-10:00 |
September | 0.663210E+11 | 42559.13 | 07-SEP-11:00 | 0.450757E+11 | 33955.67 | 30-SEP-10:20 |
October | 0.588479E+11 | 38757.62 | 07-OCT-10:20 | 0.475223E+11 | 35093.69 | 31-OCT-10:20 |
November | 0.474955E+11 | 35853.47 | 01-NOV-11:20 | 0.468638E+11 | 35931.48 | 30-NOV-13:00 |
December | 0.411721E+11 | 29499.09 | 05-DEC-11:20 | 0.490354E+11 | 36638.43 | 31-DEC-13:30 |
Annual Sum or Average | 0.647948E+12 | 0.558379E+12 | ||||
Minimum of Months | 0.357300E+11 | 26967.99 | 0.442180E+11 | 32606.46 | ||
Maximum of Months | 0.752597E+11 | 45583.88 | 0.492416E+11 | 36699.37 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.183397E+10 | 0.105415E+10 | 0.203399E+11 | 0.00 | 0.479341E+10 | 0.79 | 35490669.47 | 0.609217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164713E+10 | 0.901566E+09 | 0.183715E+11 | 0.00 | 0.437546E+10 | 0.72 | 4468396.56 | 0.736846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182664E+10 | 0.924466E+09 | 0.203400E+11 | 0.00 | 0.494341E+10 | 0.80 | 0.00 | 0.109663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173041E+10 | 0.816286E+09 | 0.196837E+11 | 0.00 | 0.507733E+10 | 0.77 | 0.00 | 0.162113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178272E+10 | 0.780501E+09 | 0.203399E+11 | 0.00 | 0.603827E+10 | 0.80 | 0.00 | 0.261857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172839E+10 | 0.726022E+09 | 0.196839E+11 | 0.00 | 0.670007E+10 | 0.77 | 0.00 | 0.322672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176185E+10 | 0.761077E+09 | 0.203398E+11 | 0.00 | 0.764737E+10 | 0.79 | 0.00 | 0.392384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180466E+10 | 0.815350E+09 | 0.203400E+11 | 0.00 | 0.787540E+10 | 0.80 | 0.00 | 0.408550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173596E+10 | 0.860275E+09 | 0.196837E+11 | 0.00 | 0.695741E+10 | 0.77 | 0.00 | 0.336673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180677E+10 | 0.966742E+09 | 0.203399E+11 | 0.00 | 0.614797E+10 | 0.79 | 0.00 | 0.261047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177001E+10 | 0.100253E+10 | 0.196838E+11 | 0.00 | 0.512598E+10 | 0.77 | 0.00 | 0.165619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183414E+10 | 0.107414E+10 | 0.203398E+11 | 0.00 | 0.491145E+10 | 0.79 | 1777176.92 | 0.955580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212626E+11 | 0.106831E+11 | 0.239486E+12 | 0.00 | 0.705935E+11 | 9.37 | 41736242.94 | 0.265074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164713E+10 | 0.726022E+09 | 0.183715E+11 | 0.00 | 0.437546E+10 | 0.72 | 0.00 | 0.609217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183414E+10 | 0.107414E+10 | 0.203400E+11 | 0.00 | 0.787540E+10 | 0.80 | 35490669.47 | 0.408550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.109042E+11 | 0.00 | 0.00 |
February | 0.346273E+11 | 0.00 | 0.00 | 0.00 | 0.959071E+10 | 0.00 | 0.00 |
March | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.996410E+10 | 0.00 | 0.00 |
April | 0.371007E+11 | 0.00 | 0.00 | 0.00 | 0.873699E+10 | 0.00 | 0.00 |
May | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.814113E+10 | 0.00 | 0.00 |
June | 0.371007E+11 | 0.00 | 0.00 | 0.00 | 0.724684E+10 | 0.00 | 0.00 |
July | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.724051E+10 | 0.00 | 0.00 |
August | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.754243E+10 | 0.00 | 0.00 |
September | 0.371007E+11 | 0.00 | 0.00 | 0.00 | 0.797501E+10 | 0.00 | 0.00 |
October | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.918501E+10 | 0.00 | 0.00 |
November | 0.371007E+11 | 0.00 | 0.00 | 0.00 | 0.976316E+10 | 0.00 | 0.00 |
December | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.106981E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.451391E+12 | 0.00 | 0.00 | 0.00 | 0.106988E+12 | 0.00 | 0.00 |
Minimum of Months | 0.346273E+11 | 0.00 | 0.00 | 0.00 | 0.724051E+10 | 0.00 | 0.00 |
Maximum of Months | 0.383373E+11 | 0.00 | 0.00 | 0.00 | 0.109042E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1285.01 | 02-JAN-17:40 | 952.15 | 01-JAN-06:10 | 12932.59 | 01-JAN-11:09 | 0.00 | 2413.33 | 24-JAN-12:09 | 0.00 | 01-JAN-07:10 | 818.81 | 09-JAN-07:00 |
February | 1285.01 | 01-FEB-17:00 | 952.15 | 01-FEB-06:10 | 12932.59 | 01-FEB-11:09 | 0.00 | 2673.60 | 07-FEB-15:09 | 0.00 | 01-FEB-06:10 | 450.81 | 13-FEB-07:10 |
March | 1285.01 | 01-MAR-18:19 | 952.15 | 01-MAR-06:10 | 12932.59 | 01-MAR-11:09 | 0.00 | 2882.38 | 27-MAR-11:20 | 0.00 | 31-MAR-09:39 | 0.00 | 01-MAR-00:10 |
April | 1285.01 | 01-APR-18:40 | 952.15 | 01-APR-05:10 | 12932.59 | 01-APR-10:09 | 0.00 | 3274.57 | 28-APR-11:00 | 0.00 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 1285.01 | 01-MAY-18:49 | 952.15 | 01-MAY-05:10 | 12932.59 | 01-MAY-10:09 | 0.00 | 3993.25 | 31-MAY-11:00 | 0.00 | 04-MAY-07:49 | 0.00 | 01-MAY-00:10 |
June | 1285.01 | 01-JUN-19:10 | 952.15 | 01-JUN-05:10 | 12932.59 | 01-JUN-10:09 | 0.00 | 4199.28 | 09-JUN-11:00 | 0.00 | 22-JUN-09:09 | 0.00 | 01-JUN-00:10 |
July | 1285.01 | 01-JUL-19:10 | 952.15 | 01-JUL-05:10 | 12932.59 | 01-JUL-10:09 | 0.00 | 4411.34 | 06-JUL-17:10 | 0.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 1285.01 | 01-AUG-18:00 | 952.15 | 01-AUG-05:10 | 12932.59 | 01-AUG-10:09 | 0.00 | 4411.34 | 08-AUG-11:30 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1285.01 | 01-SEP-18:40 | 952.15 | 01-SEP-05:10 | 12932.59 | 01-SEP-10:09 | 0.00 | 4411.34 | 08-SEP-17:19 | 0.00 | 30-SEP-08:09 | 0.00 | 01-SEP-00:10 |
October | 1285.01 | 02-OCT-17:00 | 952.15 | 01-OCT-05:10 | 12932.59 | 01-OCT-10:09 | 0.00 | 4032.04 | 07-OCT-18:00 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1285.01 | 01-NOV-17:40 | 952.15 | 01-NOV-05:10 | 12932.59 | 01-NOV-10:09 | 0.00 | 3493.32 | 01-NOV-11:00 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1285.01 | 01-DEC-17:30 | 952.15 | 01-DEC-06:10 | 12932.59 | 01-DEC-11:09 | 0.00 | 2794.48 | 05-DEC-14:00 | 0.00 | 01-DEC-06:10 | 407.46 | 31-DEC-07:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1285.01 | 952.15 | 12932.59 | 0.00 | 2413.33 | 0.00 | 0.00 | ||||||
Maximum of Months | 1285.01 | 952.15 | 12932.59 | 0.00 | 4411.34 | 0.00 | 818.81 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 9065.56 | 24-JAN-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11751.79 | 07-FEB-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16247.29 | 27-MAR-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19898.45 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22989.84 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24071.44 | 09-JUN-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24916.71 | 18-JUL-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27019.53 | 16-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24083.36 | 07-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20412.91 | 07-OCT-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17945.56 | 01-NOV-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12130.23 | 05-DEC-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9065.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27019.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 26967.99 | 30-JAN-11:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2145.76 | 0.00 | 0.00 | 6969.23 | 0.00 |
February | 29351.26 | 07-FEB-11:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2274.35 | 0.00 | 0.00 | 9223.91 | 0.00 |
March | 33923.17 | 27-MAR-11:20 | 989.27 | 12081.43 | 0.00 | 0.00 | 2882.38 | 0.00 | 0.00 | 16247.29 | 0.00 |
April | 37463.25 | 28-APR-11:00 | 989.27 | 12081.43 | 0.00 | 0.00 | 3274.57 | 0.00 | 0.00 | 19898.45 | 0.00 |
May | 41283.15 | 31-MAY-11:00 | 989.27 | 12081.43 | 0.00 | 0.00 | 3993.25 | 0.00 | 0.00 | 22989.84 | 0.00 |
June | 42587.04 | 09-JUN-11:00 | 989.27 | 12081.43 | 0.00 | 0.00 | 4199.28 | 0.00 | 0.00 | 24071.44 | 0.00 |
July | 43665.84 | 18-JUL-11:00 | 989.27 | 12081.43 | 0.00 | 0.00 | 4411.34 | 0.00 | 0.00 | 24916.71 | 0.00 |
August | 45583.88 | 16-AUG-11:00 | 989.27 | 12081.43 | 0.00 | 0.00 | 4224.71 | 0.00 | 0.00 | 27019.53 | 0.00 |
September | 42559.13 | 07-SEP-11:00 | 989.27 | 12081.43 | 0.00 | 0.00 | 4246.67 | 0.00 | 0.00 | 23993.83 | 0.00 |
October | 38757.62 | 07-OCT-10:20 | 879.34 | 12932.59 | 0.00 | 0.00 | 3464.94 | 0.00 | 0.00 | 17559.03 | 0.00 |
November | 35853.47 | 01-NOV-11:20 | 989.27 | 12081.43 | 0.00 | 0.00 | 3434.62 | 0.00 | 0.00 | 17581.03 | 0.00 |
December | 29499.09 | 05-DEC-11:20 | 989.27 | 12932.59 | 0.00 | 0.00 | 2335.14 | 0.00 | 0.00 | 9310.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 26967.99 | 879.34 | 12081.43 | 0.00 | 0.00 | 2145.76 | 0.00 | 0.00 | 6969.23 | 0.00 | |
Maximum of Months | 45583.88 | 989.27 | 12932.59 | 0.00 | 0.00 | 4411.34 | 0.00 | 0.00 | 27019.53 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 25220.79 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 14957.31 | 12-JAN-13:20 | 0.00 |
February | 25220.79 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 14793.38 | 01-FEB-13:20 | 0.00 |
March | 25220.79 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 14009.71 | 01-MAR-13:20 | 0.00 |
April | 25220.79 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 13004.97 | 02-APR-12:00 | 0.00 |
May | 25220.79 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 11711.14 | 01-MAY-12:39 | 0.00 |
June | 25220.79 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 10374.62 | 01-JUN-12:00 | 0.00 |
July | 25220.79 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 9958.48 | 31-JUL-12:50 | 0.00 |
August | 25220.79 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 10650.20 | 31-AUG-12:39 | 0.00 |
September | 25220.79 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 11867.56 | 30-SEP-12:39 | 0.00 |
October | 25220.79 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 13260.58 | 31-OCT-12:30 | 0.00 |
November | 25220.79 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 14189.42 | 30-NOV-13:00 | 0.00 |
December | 25220.79 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 14896.37 | 31-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 25220.79 | 0.00 | 0.00 | 0.00 | 9958.48 | 0.00 | ||
Maximum of Months | 25220.79 | 0.00 | 0.00 | 0.00 | 14957.31 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.57 | 0.50 | 24.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.58 | 0.67 | 24.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 24.63 | 1.33 | 24.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 24.67 | 1.33 | 24.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.06 | 0.00 | 25.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 25.28 | 0.00 | 25.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 25.40 | 1.17 | 25.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 25.40 | 3.67 | 25.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 25.47 | 0.00 | 25.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.26 | 0.00 | 25.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 24.92 | 1.67 | 24.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 24.64 | 1.33 | 24.63 |
Annual Sum or Average | 0.00 | 0.00 | 171.67 | 25.07 | 11.67 | 25.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.57 | 0.00 | 24.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 25.47 | 3.67 | 25.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 29.06 | 0.00 | 29.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 29.35 | 0.00 | 29.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 29.53 | 0.67 | 29.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 29.13 | 10.50 | 28.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 157.67 | 28.04 | 123.33 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 422.67 | 28.51 | 373.83 | 28.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 584.50 | 29.46 | 512.00 | 29.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 599.83 | 29.75 | 526.33 | 29.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 480.67 | 28.88 | 425.33 | 28.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 176.50 | 28.46 | 133.00 | 28.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 29.10 | 16.50 | 28.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 29.82 | 0.00 | 29.82 |
Annual Sum or Average | 0.00 | 0.00 | 2591.17 | 29.10 | 2121.50 | 29.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 28.04 | 0.00 | 27.82 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 599.83 | 29.82 | 526.33 | 29.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 131.33 | 22.15 | 437.00 | 23.48 | 14.83 | 23.50 |
February | 122.17 | 22.95 | 453.33 | 23.69 | 60.00 | 23.71 |
March | 118.50 | 23.39 | 514.67 | 23.84 | 74.17 | 23.86 |
April | 136.67 | 24.12 | 555.83 | 24.02 | 135.17 | 24.04 |
May | 184.50 | 24.49 | 607.00 | 24.18 | 184.50 | 24.24 |
June | 399.67 | 24.24 | 592.00 | 24.17 | 399.67 | 24.19 |
July | 443.50 | 24.27 | 609.00 | 24.21 | 443.50 | 24.23 |
August | 489.17 | 24.25 | 612.00 | 24.21 | 489.17 | 24.22 |
September | 432.67 | 24.22 | 590.00 | 24.17 | 432.67 | 24.18 |
October | 301.83 | 24.22 | 610.00 | 24.12 | 301.83 | 24.15 |
November | 144.17 | 24.11 | 588.50 | 24.02 | 144.17 | 24.03 |
December | 168.33 | 23.48 | 533.00 | 23.80 | 124.67 | 23.82 |
Annual Sum or Average | 3072.50 | 24.03 | 6702.33 | 24.04 | 2804.33 | 24.08 |
Minimum of Months | 118.50 | 22.15 | 437.00 | 23.48 | 14.83 | 23.50 |
Maximum of Months | 489.17 | 24.49 | 612.00 | 24.21 | 489.17 | 24.24 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.17 | 26.09 | 604.50 | 25.86 | 479.17 | 25.93 |
February | 475.67 | 26.09 | 551.00 | 25.96 | 475.67 | 26.00 |
March | 556.00 | 26.15 | 612.00 | 26.09 | 556.00 | 26.11 |
April | 583.83 | 26.24 | 590.00 | 26.23 | 583.83 | 26.23 |
May | 611.00 | 26.62 | 611.00 | 26.62 | 611.00 | 26.62 |
June | 592.00 | 27.78 | 592.00 | 27.78 | 592.00 | 27.78 |
July | 609.00 | 29.10 | 609.00 | 29.10 | 609.00 | 29.10 |
August | 612.00 | 29.44 | 612.00 | 29.44 | 612.00 | 29.44 |
September | 590.00 | 28.26 | 590.00 | 28.26 | 590.00 | 28.26 |
October | 610.00 | 26.76 | 610.00 | 26.76 | 610.00 | 26.76 |
November | 589.67 | 26.25 | 591.00 | 26.25 | 589.67 | 26.25 |
December | 552.33 | 26.10 | 609.00 | 26.03 | 552.33 | 26.05 |
Annual Sum or Average | 6860.67 | 27.13 | 7181.50 | 27.07 | 6860.67 | 27.09 |
Minimum of Months | 475.67 | 26.09 | 551.00 | 25.86 | 475.67 | 25.93 |
Maximum of Months | 612.00 | 29.44 | 612.00 | 29.44 | 612.00 | 29.44 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.47251 | 51.06942 | 0.44604 | 10.14434 |
February | 551.00000 | 23.64565 | 54.73381 | 0.51679 | 11.25010 |
March | 612.00000 | 23.81259 | 51.39115 | 0.53872 | 11.55984 |
April | 590.00000 | 23.98583 | 55.02571 | 0.62360 | 13.45855 |
May | 611.00000 | 24.08577 | 57.03636 | -0.1052 | 6.16223 |
June | 592.00000 | 24.12837 | 65.89454 | 0.00571 | 6.29907 |
July | 609.00000 | 24.16941 | 68.36903 | 0.08078 | 6.84213 |
August | 612.00000 | 24.17465 | 69.96365 | 0.12276 | 6.90590 |
September | 590.00000 | 24.13020 | 69.28813 | 0.07533 | 6.46218 |
October | 610.00000 | 24.07094 | 62.23631 | 0.77065 | 17.94993 |
November | 591.00000 | 23.98945 | 58.00249 | 0.68721 | 15.15362 |
December | 609.00000 | 23.74370 | 56.10520 | 0.56832 | 12.28681 |
Annual Sum or Average | 7187.00000 | 23.95216 | 59.94604 | 0.35963 | 10.36456 |
Minimum of Months | 551.00000 | 23.47251 | 51.06942 | -0.1052 | 6.16223 |
Maximum of Months | 612.00000 | 24.17465 | 69.96365 | 0.77065 | 17.94993 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.65247 | 48.55833 | 1.14275 | 33.61484 |
February | 551.00000 | 25.84570 | 51.40741 | 1.21364 | 36.58202 |
March | 612.00000 | 26.02818 | 49.13387 | 1.24271 | 37.75957 |
April | 590.00000 | 26.22934 | 52.78577 | 1.33325 | 42.17027 |
May | 611.00000 | 26.61935 | 56.99572 | 0.98420 | 26.95864 |
June | 592.00000 | 27.78099 | 64.17768 | 1.45928 | 49.31396 |
July | 609.00000 | 29.10467 | 66.35469 | 1.95664 | 69.90288 |
August | 612.00000 | 29.43900 | 67.94511 | 2.10465 | 75.82106 |
September | 590.00000 | 28.26478 | 66.50439 | 1.66828 | 58.20882 |
October | 610.00000 | 26.75848 | 59.74046 | 1.56873 | 54.00111 |
November | 591.00000 | 26.24748 | 54.91617 | 1.38228 | 44.66586 |
December | 609.00000 | 25.96184 | 51.97630 | 1.26116 | 38.69440 |
Annual Sum or Average | 7187.00000 | 27.00259 | 57.57032 | 1.44483 | 47.38226 |
Minimum of Months | 551.00000 | 25.65247 | 48.55833 | 0.98420 | 26.95864 |
Maximum of Months | 612.00000 | 29.43900 | 67.94511 | 2.10465 | 75.82106 |
Report: DXReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.965771E+10 | 0.271913E+10 | 454.13 | 0.683159E+10 | 0.282612E+10 | 0.00 | 1.00 | 24-JAN-03:01 | 0.00 | 01-JAN-00:10 | 35707.53 | 30-JAN-03:01 | 25981.29 | 25-JAN-03:01 | 15964.14 | 30-JAN-03:01 | 8331.30 | 25-JAN-03:01 | 0.00 |
February | 0.126581E+11 | 0.346903E+10 | 451.02 | 0.878312E+10 | 0.387495E+10 | 0.00 | 1.00 | 06-FEB-03:01 | 0.00 | 01-FEB-00:10 | 44810.26 | 09-FEB-03:01 | 23502.77 | 09-FEB-03:01 | 21307.49 | 09-FEB-03:01 | 9921.89 | 09-FEB-03:01 | 0.00 |
March | 0.202170E+11 | 0.547112E+10 | 552.12 | 0.148388E+11 | 0.537816E+10 | 0.00 | 1.00 | 01-MAR-03:01 | 0.00 | 01-MAR-00:02 | 62249.45 | 02-MAR-03:01 | 42511.20 | 02-MAR-03:01 | 27312.70 | 24-MAR-02:61 | 14066.97 | 02-MAR-03:01 | 0.00 |
April | 0.317034E+11 | 0.829746E+10 | 592.73 | 0.222388E+11 | 0.946454E+10 | 0.00 | 1.00 | 02-APR-02:61 | 0.00 | 01-APR-00:02 | 67258.19 | 30-APR-02:61 | 45972.42 | 29-APR-02:61 | 41935.00 | 30-APR-02:61 | 14767.24 | 30-APR-02:61 | 0.00 |
May | 0.516221E+11 | 0.134981E+11 | 631.97 | 0.354285E+11 | 0.161936E+11 | 0.00 | 1.00 | 01-MAY-02:61 | 0.00 | 01-MAY-00:03 | 67258.19 | 01-MAY-02:61 | 52745.69 | 11-MAY-02:61 | 46409.71 | 30-MAY-02:61 | 15309.30 | 23-MAY-02:61 | 0.00 |
June | 0.665228E+11 | 0.170216E+11 | 614.43 | 0.390250E+11 | 0.274978E+11 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:02 | 67258.19 | 21-JUN-02:61 | 42248.32 | 02-JUN-02:61 | 46672.56 | 27-JUN-02:61 | 16200.63 | 09-JUN-12:00 | 0.00 |
July | 0.836812E+11 | 0.217418E+11 | 649.03 | 0.466157E+11 | 0.370656E+11 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:02 | 66887.31 | 06-JUL-02:02 | 46543.14 | 04-JUL-02:61 | 49021.97 | 18-JUL-02:61 | 17146.94 | 18-JUL-12:05 | 0.00 |
August | 0.888341E+11 | 0.230749E+11 | 650.75 | 0.483499E+11 | 0.404841E+11 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 66980.96 | 31-AUG-02:61 | 45116.35 | 02-AUG-02:61 | 49087.70 | 08-AUG-02:61 | 18360.25 | 10-AUG-13:00 | 0.00 |
September | 0.723172E+11 | 0.180607E+11 | 616.79 | 0.390909E+11 | 0.332263E+11 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 67258.19 | 12-SEP-02:02 | 40346.39 | 02-SEP-02:61 | 48310.91 | 03-SEP-02:57 | 16483.94 | 07-SEP-13:00 | 0.00 |
October | 0.532580E+11 | 0.132551E+11 | 631.41 | 0.322505E+11 | 0.210074E+11 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:02 | 67258.19 | 15-OCT-02:61 | 46952.35 | 20-OCT-02:61 | 46353.67 | 07-OCT-02:61 | 14767.24 | 01-OCT-02:61 | 0.00 |
November | 0.330723E+11 | 0.842410E+10 | 599.45 | 0.214175E+11 | 0.116548E+11 | 0.00 | 1.00 | 01-NOV-02:61 | 0.00 | 01-NOV-00:03 | 67258.19 | 02-NOV-02:61 | 43650.93 | 20-NOV-03:01 | 35065.91 | 08-NOV-03:01 | 14767.24 | 02-NOV-02:61 | 0.00 |
December | 0.167427E+11 | 0.450887E+10 | 521.40 | 0.109844E+11 | 0.575833E+10 | 0.00 | 1.00 | 01-DEC-03:01 | 0.00 | 01-DEC-00:02 | 55947.95 | 12-DEC-03:01 | 31348.13 | 12-DEC-03:01 | 24599.81 | 12-DEC-03:01 | 12404.19 | 12-DEC-03:01 | 0.00 |
Annual Sum or Average | 0.540286E+12 | 0.139542E+12 | 6965.24 | 0.325855E+12 | 0.214432E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.965771E+10 | 0.271913E+10 | 451.02 | 0.683159E+10 | 0.282612E+10 | 0.00 | 1.00 | 0.00 | 35707.53 | 23502.77 | 15964.14 | 8331.30 | 0.00 | ||||||
Maximum of Months | 0.888341E+11 | 0.230749E+11 | 650.75 | 0.483499E+11 | 0.404841E+11 | 0.00 | 1.00 | 0.00 | 67258.19 | 52745.69 | 49087.70 | 18360.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.135220E+11 | 0.337304E+10 | 500.82 | 0.919533E+10 | 0.432662E+10 | 0.00 | 1.00 | 01-JAN-03:01 | 0.00 | 01-JAN-00:10 | 28816.25 | 30-JAN-03:11 | 24736.95 | 29-JAN-03:01 | 15285.33 | 10-JAN-03:01 | 6548.88 | 30-JAN-03:11 | 0.00 |
February | 0.160740E+11 | 0.389943E+10 | 496.31 | 0.108038E+11 | 0.527018E+10 | 0.00 | 1.00 | 01-FEB-03:11 | 0.00 | 01-FEB-00:10 | 29654.64 | 09-FEB-03:11 | 21400.36 | 10-FEB-04:31 | 15940.82 | 03-FEB-03:11 | 6602.77 | 09-FEB-03:11 | 0.00 |
March | 0.229337E+11 | 0.549513E+10 | 601.70 | 0.168971E+11 | 0.603655E+10 | 0.00 | 1.00 | 01-MAR-03:11 | 0.00 | 01-MAR-00:02 | 31066.25 | 28-MAR-10:55 | 28911.55 | 27-MAR-12:15 | 17502.09 | 24-MAR-03:41 | 7817.31 | 27-MAR-10:52 | 0.00 |
April | 0.339831E+11 | 0.791388E+10 | 637.93 | 0.247415E+11 | 0.924159E+10 | 0.00 | 1.00 | 01-APR-02:11 | 0.00 | 01-APR-00:02 | 31066.25 | 29-APR-19:55 | 29447.43 | 28-APR-12:43 | 19954.31 | 30-APR-02:61 | 8554.63 | 28-APR-11:55 | 0.00 |
May | 0.530246E+11 | 0.126875E+11 | 698.81 | 0.406172E+11 | 0.124073E+11 | 0.00 | 1.00 | 01-MAY-02:61 | 0.00 | 01-MAY-00:03 | 31066.25 | 30-MAY-02:25 | 29619.32 | 08-MAY-12:30 | 20950.71 | 30-MAY-02:61 | 8370.85 | 31-MAY-18:55 | 0.00 |
June | 0.636090E+11 | 0.152456E+11 | 686.24 | 0.422929E+11 | 0.213161E+11 | 0.00 | 1.00 | 01-JUN-00:06 | 0.00 | 01-JUN-00:02 | 31066.25 | 25-JUN-06:45 | 29499.33 | 16-JUN-16:13 | 22905.67 | 25-JUN-06:00 | 8420.72 | 15-JUN-10:53 | 0.00 |
July | 0.708514E+11 | 0.174966E+11 | 710.89 | 0.466281E+11 | 0.242234E+11 | 0.00 | 1.00 | 01-JUL-00:06 | 0.00 | 01-JUL-00:02 | 31066.25 | 02-JUL-05:00 | 29428.93 | 03-JUL-19:33 | 21548.23 | 20-JUL-06:00 | 8854.09 | 21-JUL-11:55 | 0.00 |
August | 0.719507E+11 | 0.177801E+11 | 711.06 | 0.467683E+11 | 0.251824E+11 | 0.00 | 1.00 | 01-AUG-00:04 | 0.00 | 01-AUG-00:01 | 31066.25 | 31-AUG-03:10 | 29437.02 | 15-AUG-19:33 | 22678.59 | 08-AUG-05:00 | 8854.09 | 16-AUG-11:53 | 0.00 |
September | 0.662669E+11 | 0.156066E+11 | 686.72 | 0.397908E+11 | 0.264760E+11 | 0.00 | 1.00 | 01-SEP-00:04 | 0.00 | 01-SEP-00:01 | 31066.25 | 09-SEP-07:05 | 29454.54 | 30-SEP-10:53 | 22948.96 | 10-SEP-06:00 | 8143.12 | 26-SEP-11:53 | 0.00 |
October | 0.562035E+11 | 0.128497E+11 | 694.35 | 0.355945E+11 | 0.206090E+11 | 0.00 | 1.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:02 | 31066.25 | 09-OCT-04:02 | 29604.40 | 04-OCT-11:02 | 23661.90 | 07-OCT-09:12 | 7770.55 | 04-OCT-11:53 | 0.00 |
November | 0.358377E+11 | 0.813782E+10 | 645.11 | 0.236088E+11 | 0.122289E+11 | 0.00 | 1.00 | 01-NOV-02:61 | 0.00 | 01-NOV-00:03 | 31066.25 | 02-NOV-20:00 | 23518.23 | 07-NOV-11:53 | 18850.17 | 08-NOV-03:11 | 7048.57 | 01-NOV-14:00 | 0.00 |
December | 0.213568E+11 | 0.504692E+10 | 573.90 | 0.134678E+11 | 0.788907E+10 | 0.00 | 1.00 | 01-DEC-03:01 | 0.00 | 01-DEC-00:02 | 30445.90 | 05-DEC-14:55 | 20242.24 | 01-DEC-03:01 | 17238.59 | 05-DEC-14:55 | 6591.73 | 11-DEC-03:11 | 0.00 |
Annual Sum or Average | 0.525613E+12 | 0.125532E+12 | 7643.84 | 0.350406E+12 | 0.175207E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.135220E+11 | 0.337304E+10 | 496.31 | 0.919533E+10 | 0.432662E+10 | 0.00 | 1.00 | 0.00 | 28816.25 | 20242.24 | 15285.33 | 6548.88 | 0.00 | ||||||
Maximum of Months | 0.719507E+11 | 0.177801E+11 | 711.06 | 0.467683E+11 | 0.264760E+11 | 0.00 | 1.00 | 0.00 | 31066.25 | 29619.32 | 23661.90 | 8854.09 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 57.33 | 17.34 | 39.98 | 79.76 | 72.63 | 0.00 | 0.00 | 0.00 |
February | 62.47 | 16.93 | 45.54 | 97.04 | 60.29 | 0.00 | 0.00 | 0.00 |
March | 69.01 | 17.01 | 52.00 | 124.54 | 44.94 | 0.00 | 0.00 | 0.00 |
April | 84.02 | 24.48 | 59.54 | 180.25 | 27.02 | 0.00 | 0.00 | 0.00 |
May | 93.90 | 29.92 | 63.98 | 245.15 | 6.45 | 0.00 | 0.00 | 0.00 |
June | 91.96 | 28.12 | 63.84 | 256.73 | 1.56 | 0.00 | 0.00 | 0.00 |
July | 85.83 | 24.74 | 61.08 | 276.91 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87.89 | 26.97 | 60.91 | 281.88 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 82.62 | 25.54 | 57.09 | 230.17 | 3.04 | 0.00 | 0.00 | 0.00 |
October | 74.97 | 24.49 | 50.48 | 180.20 | 12.35 | 0.00 | 0.00 | 0.00 |
November | 62.83 | 19.90 | 42.93 | 123.37 | 33.94 | 0.00 | 0.00 | 0.00 |
December | 50.85 | 13.95 | 36.90 | 76.84 | 61.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.36 | 22.47 | 52.88 | 179.88 | 26.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.85 | 13.95 | 36.90 | 76.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 93.90 | 29.92 | 63.98 | 281.88 | 72.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.85 | 96.31 | 108.54 | 333.48 | 144.30 | 0.00 | 0.00 | 0.00 |
February | 192.36 | 78.69 | 113.68 | 332.56 | 122.19 | 0.00 | 0.00 | 0.00 |
March | 158.32 | 42.98 | 115.34 | 306.40 | 93.72 | 0.00 | 0.00 | 0.00 |
April | 124.45 | 13.19 | 111.26 | 288.10 | 57.27 | 0.00 | 0.00 | 0.00 |
May | 105.42 | 1.61 | 103.81 | 328.97 | 13.86 | 0.00 | 0.00 | 0.00 |
June | 99.29 | 0.12 | 99.16 | 344.71 | 2.94 | 0.00 | 0.00 | 0.00 |
July | 99.28 | 0.84 | 98.44 | 407.19 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 115.16 | 8.16 | 107.00 | 449.48 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 151.84 | 34.80 | 117.04 | 450.55 | 6.56 | 0.00 | 0.00 | 0.00 |
October | 198.79 | 79.03 | 119.76 | 470.26 | 25.50 | 0.00 | 0.00 | 0.00 |
November | 219.30 | 105.72 | 113.58 | 434.61 | 68.63 | 0.00 | 0.00 | 0.00 |
December | 203.58 | 100.56 | 103.02 | 351.32 | 122.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 155.84 | 46.67 | 109.17 | 375.10 | 54.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.28 | 0.12 | 98.44 | 288.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.30 | 105.72 | 119.76 | 470.26 | 144.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.22 | 16.15 | 40.07 | 80.41 | 76.20 | 0.00 | 0.00 | 0.00 |
February | 64.20 | 18.31 | 45.89 | 102.51 | 62.82 | 0.00 | 0.00 | 0.00 |
March | 76.05 | 22.51 | 53.53 | 139.24 | 46.88 | 0.00 | 0.00 | 0.00 |
April | 83.10 | 23.35 | 59.76 | 178.47 | 28.57 | 0.00 | 0.00 | 0.00 |
May | 90.46 | 27.08 | 63.38 | 239.09 | 7.14 | 0.00 | 0.00 | 0.00 |
June | 93.48 | 29.47 | 64.01 | 260.54 | 1.56 | 0.00 | 0.00 | 0.00 |
July | 85.76 | 24.53 | 61.23 | 276.29 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87.98 | 26.75 | 61.23 | 280.67 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 83.69 | 26.29 | 57.40 | 232.04 | 3.48 | 0.00 | 0.00 | 0.00 |
October | 74.38 | 24.03 | 50.35 | 179.64 | 13.62 | 0.00 | 0.00 | 0.00 |
November | 63.92 | 20.90 | 43.01 | 127.87 | 36.10 | 0.00 | 0.00 | 0.00 |
December | 53.51 | 16.17 | 37.33 | 84.99 | 64.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.10 | 22.98 | 53.13 | 182.27 | 28.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.51 | 16.15 | 37.33 | 80.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 93.48 | 29.47 | 64.01 | 280.67 | 76.20 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153549E+09 | 46455922.64 | 0.107093E+09 | 0.213623E+09 | 0.194528E+09 |
February | 0.151139E+09 | 40959436.79 | 0.110180E+09 | 0.234768E+09 | 0.145848E+09 |
March | 0.184836E+09 | 45555301.97 | 0.139281E+09 | 0.333563E+09 | 0.120375E+09 |
April | 0.217786E+09 | 63455643.77 | 0.154331E+09 | 0.467210E+09 | 70042660.37 |
May | 0.251495E+09 | 80127388.33 | 0.171367E+09 | 0.656603E+09 | 17274302.57 |
June | 0.238355E+09 | 72891560.38 | 0.165464E+09 | 0.665451E+09 | 4033921.09 |
July | 0.229883E+09 | 66274824.17 | 0.163609E+09 | 0.741681E+09 | 5492.56 |
August | 0.235397E+09 | 72246293.14 | 0.163150E+09 | 0.754982E+09 | 49592.80 |
September | 0.214162E+09 | 66194676.04 | 0.147967E+09 | 0.596592E+09 | 7873832.62 |
October | 0.200808E+09 | 65603937.50 | 0.135204E+09 | 0.482661E+09 | 33081289.01 |
November | 0.162849E+09 | 51582265.25 | 0.111267E+09 | 0.319769E+09 | 87971800.13 |
December | 0.136205E+09 | 37368954.22 | 98835584.76 | 0.205819E+09 | 0.164057E+09 |
Annual Sum or Average | 0.237646E+10 | 0.708716E+09 | 0.166775E+10 | 0.567272E+10 | 0.845141E+09 |
Minimum of Months | 0.136205E+09 | 37368954.22 | 98835584.76 | 0.205819E+09 | 5492.56 |
Maximum of Months | 0.251495E+09 | 80127388.33 | 0.171367E+09 | 0.754982E+09 | 0.194528E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.548673E+09 | 0.257956E+09 | 0.290717E+09 | 0.893189E+09 | 0.386482E+09 |
February | 0.465367E+09 | 0.190355E+09 | 0.275012E+09 | 0.804535E+09 | 0.295599E+09 |
March | 0.424056E+09 | 0.115129E+09 | 0.308927E+09 | 0.820650E+09 | 0.251023E+09 |
April | 0.322587E+09 | 34200235.23 | 0.288387E+09 | 0.746754E+09 | 0.148451E+09 |
May | 0.282368E+09 | 4324169.18 | 0.278044E+09 | 0.881120E+09 | 37116684.17 |
June | 0.257348E+09 | 318475.99 | 0.257029E+09 | 0.893500E+09 | 7610455.35 |
July | 0.265919E+09 | 2259487.92 | 0.263659E+09 | 0.109061E+10 | 2955.01 |
August | 0.308444E+09 | 21854446.88 | 0.286590E+09 | 0.120389E+10 | 119197.88 |
September | 0.393568E+09 | 90197388.00 | 0.303371E+09 | 0.116784E+10 | 17006419.56 |
October | 0.532432E+09 | 0.211672E+09 | 0.320761E+09 | 0.125953E+10 | 68287654.97 |
November | 0.568433E+09 | 0.274027E+09 | 0.294406E+09 | 0.112651E+10 | 0.177876E+09 |
December | 0.545267E+09 | 0.269345E+09 | 0.275922E+09 | 0.940979E+09 | 0.327271E+09 |
Annual Sum or Average | 0.491446E+10 | 0.147164E+10 | 0.344282E+10 | 0.118291E+11 | 0.171685E+10 |
Minimum of Months | 0.257348E+09 | 318475.99 | 0.257029E+09 | 0.746754E+09 | 2955.01 |
Maximum of Months | 0.568433E+09 | 0.274027E+09 | 0.320761E+09 | 0.125953E+10 | 0.386482E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150582E+09 | 43248464.55 | 0.107334E+09 | 0.215383E+09 | 0.204083E+09 |
February | 0.155309E+09 | 44287911.37 | 0.111022E+09 | 0.248002E+09 | 0.151964E+09 |
March | 0.203680E+09 | 60299735.34 | 0.143380E+09 | 0.372935E+09 | 0.125567E+09 |
April | 0.215407E+09 | 60517642.82 | 0.154889E+09 | 0.462602E+09 | 74046942.93 |
May | 0.242285E+09 | 72525433.08 | 0.169759E+09 | 0.640369E+09 | 19125786.35 |
June | 0.242304E+09 | 76380648.75 | 0.165924E+09 | 0.675319E+09 | 4049049.04 |
July | 0.229698E+09 | 65711851.54 | 0.163986E+09 | 0.740016E+09 | 9183.51 |
August | 0.235644E+09 | 71645819.86 | 0.163999E+09 | 0.751742E+09 | 83895.40 |
September | 0.216928E+09 | 68152278.65 | 0.148775E+09 | 0.601450E+09 | 9023280.16 |
October | 0.199211E+09 | 64350549.61 | 0.134860E+09 | 0.481155E+09 | 36485421.81 |
November | 0.165675E+09 | 54180882.86 | 0.111494E+09 | 0.331430E+09 | 93558825.02 |
December | 0.143319E+09 | 43322672.94 | 99996175.35 | 0.227631E+09 | 0.171581E+09 |
Annual Sum or Average | 0.240004E+10 | 0.724624E+09 | 0.167542E+10 | 0.574803E+10 | 0.889577E+09 |
Minimum of Months | 0.143319E+09 | 43248464.55 | 99996175.35 | 0.215383E+09 | 9183.51 |
Maximum of Months | 0.242304E+09 | 76380648.75 | 0.169759E+09 | 0.751742E+09 | 0.204083E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 487.87 | 287.33 | 318.40 | 129.80 | 188.60 | 0.00 | 0.00 |
February | 527.85 | 241.03 | 319.04 | 113.92 | 205.11 | 0.00 | 0.00 |
March | 566.79 | 182.17 | 303.38 | 82.51 | 220.87 | 0.00 | 0.00 |
April | 644.74 | 110.78 | 291.58 | 61.02 | 230.56 | 0.00 | 0.00 |
May | 812.24 | 26.48 | 289.78 | 58.61 | 231.17 | 0.00 | 0.00 |
June | 861.88 | 5.95 | 284.73 | 57.71 | 227.01 | 0.00 | 0.00 |
July | 960.39 | 0.00 | 270.87 | 50.12 | 220.75 | 0.00 | 0.00 |
August | 1012.02 | 0.09 | 291.03 | 61.88 | 229.14 | 0.00 | 0.00 |
September | 912.52 | 12.84 | 318.15 | 86.63 | 231.52 | 0.00 | 0.00 |
October | 829.31 | 50.68 | 348.14 | 127.55 | 220.59 | 0.00 | 0.00 |
November | 683.54 | 136.36 | 346.05 | 146.52 | 199.52 | 0.00 | 0.00 |
December | 509.37 | 243.72 | 307.94 | 130.69 | 177.25 | 0.00 | 0.00 |
Annual Sum or Average | 735.28 | 107.48 | 307.30 | 92.12 | 215.18 | 0.00 | 0.00 |
Minimum of Months | 487.87 | 0.00 | 270.87 | 50.12 | 177.25 | 0.00 | 0.00 |
Maximum of Months | 1012.02 | 287.33 | 348.14 | 146.52 | 231.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.130670E+10 | 0.769597E+09 | 0.852804E+09 | 0.347660E+09 | 0.505144E+09 | 0.00 | 0.00 |
February | 0.127699E+10 | 0.583093E+09 | 0.771816E+09 | 0.275603E+09 | 0.496213E+09 | 0.00 | 0.00 |
March | 0.151810E+10 | 0.487919E+09 | 0.812572E+09 | 0.220984E+09 | 0.591588E+09 | 0.00 | 0.00 |
April | 0.167116E+10 | 0.287139E+09 | 0.755780E+09 | 0.158174E+09 | 0.597607E+09 | 0.00 | 0.00 |
May | 0.217550E+10 | 70926770.14 | 0.776148E+09 | 0.156977E+09 | 0.619171E+09 | 0.00 | 0.00 |
June | 0.223399E+10 | 15412260.39 | 0.738007E+09 | 0.149591E+09 | 0.588417E+09 | 0.00 | 0.00 |
July | 0.257230E+10 | 12874.98 | 0.725500E+09 | 0.134246E+09 | 0.591254E+09 | 0.00 | 0.00 |
August | 0.271061E+10 | 248570.21 | 0.779485E+09 | 0.165747E+09 | 0.613739E+09 | 0.00 | 0.00 |
September | 0.236525E+10 | 33274046.09 | 0.824657E+09 | 0.224544E+09 | 0.600113E+09 | 0.00 | 0.00 |
October | 0.222123E+10 | 0.135739E+09 | 0.932451E+09 | 0.341626E+09 | 0.590825E+09 | 0.00 | 0.00 |
November | 0.177174E+10 | 0.353438E+09 | 0.896957E+09 | 0.379790E+09 | 0.517167E+09 | 0.00 | 0.00 |
December | 0.136429E+10 | 0.652773E+09 | 0.824791E+09 | 0.350037E+09 | 0.474754E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.231879E+11 | 0.338957E+10 | 0.969097E+10 | 0.290498E+10 | 0.678599E+10 | 0.00 | 0.00 |
Minimum of Months | 0.127699E+10 | 12874.98 | 0.725500E+09 | 0.134246E+09 | 0.474754E+09 | 0.00 | 0.00 |
Maximum of Months | 0.271061E+10 | 0.769597E+09 | 0.932451E+09 | 0.379790E+09 | 0.619171E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.103591E+11 | -0.967069E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688400947.7 | 60.05 | 0.00 | 0.00 |
February | 0.911125E+10 | -0.849283E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -618419461.9 | 60.05 | 0.00 | 0.00 |
March | 0.946582E+10 | -0.878449E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -681329557.5 | 60.05 | 0.00 | 0.00 |
April | 0.830011E+10 | -0.764449E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -655622164.7 | 60.05 | 0.00 | 0.00 |
May | 0.773403E+10 | -0.706363E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -670399366.7 | 60.05 | 0.00 | 0.00 |
June | 0.688461E+10 | -0.625575E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -628867053.8 | 60.05 | 0.00 | 0.00 |
July | 0.687836E+10 | -0.625271E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -625648493.9 | 60.05 | 0.00 | 0.00 |
August | 0.716534E+10 | -0.654602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -619322239.0 | 60.05 | 0.00 | 0.00 |
September | 0.757632E+10 | -0.695590E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -620424818.2 | 60.05 | 0.00 | 0.00 |
October | 0.872565E+10 | -0.805807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -667583736.9 | 60.05 | 0.00 | 0.00 |
November | 0.927504E+10 | -0.861996E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -655085491.4 | 60.05 | 0.00 | 0.00 |
December | 0.101632E+11 | -0.948081E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -682386460.2 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.101639E+12 | -0.938253E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.781349E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.687836E+10 | -0.967069E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -688400947.7 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.103591E+11 | -0.625271E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -618419461.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.28 | 0.24 | 01-JAN-07:49 | 1247.47 | 24.49 | 134.67 | 294.50 | 1237.01 | 24.18 | 130.50 | 293.83 |
February | 308.33 | 0.27 | 0.24 | 01-FEB-07:40 | 1165.73 | 22.40 | 93.67 | 278.67 | 1103.93 | 20.44 | 48.83 | 275.50 |
March | 357.50 | 0.27 | 0.24 | 01-MAR-07:49 | 1007.26 | 18.30 | 3.17 | 329.00 | 975.44 | 18.33 | 1.67 | 329.67 |
April | 375.00 | 0.29 | 0.24 | 01-APR-07:10 | 902.31 | 17.36 | 0.00 | 332.50 | 935.95 | 17.41 | 0.00 | 331.33 |
May | 405.33 | 0.28 | 0.24 | 01-MAY-06:19 | 872.28 | 17.32 | 0.00 | 371.17 | 1040.40 | 17.29 | 0.00 | 367.17 |
June | 403.50 | 0.28 | 0.24 | 01-JUN-06:19 | 889.59 | 17.26 | 0.00 | 357.33 | 989.26 | 17.27 | 0.00 | 360.33 |
July | 405.00 | 0.29 | 0.24 | 01-JUL-06:40 | 879.75 | 17.22 | 0.00 | 355.50 | 932.23 | 17.21 | 0.00 | 356.67 |
August | 395.83 | 0.29 | 0.24 | 01-AUG-06:40 | 969.83 | 17.64 | 0.00 | 350.67 | 974.88 | 17.64 | 0.00 | 352.33 |
September | 358.83 | 0.27 | 0.24 | 01-SEP-06:49 | 1208.10 | 18.51 | 5.50 | 328.67 | 1079.84 | 18.51 | 5.67 | 331.17 |
October | 351.17 | 0.28 | 0.24 | 01-OCT-06:00 | 1164.30 | 20.94 | 64.17 | 319.50 | 1127.49 | 20.62 | 56.67 | 319.67 |
November | 318.83 | 0.26 | 0.24 | 01-NOV-06:00 | 1226.25 | 23.76 | 113.17 | 297.00 | 1136.80 | 21.70 | 60.00 | 298.50 |
December | 319.00 | 0.27 | 0.24 | 01-DEC-07:10 | 1218.66 | 24.73 | 136.17 | 290.33 | 1173.13 | 23.31 | 110.33 | 289.17 |
Annual Sum or Average | 4323.33 | 0.28 | 1049.68 | 19.74 | 550.50 | 3904.83 | 1051.62 | 19.29 | 413.67 | 3905.33 | ||
Minimum of Months | 308.33 | 0.26 | 0.24 | 872.28 | 17.22 | 0.00 | 278.67 | 932.23 | 17.21 | 0.00 | 275.50 | |
Maximum of Months | 405.33 | 0.29 | 0.24 | 1247.47 | 24.73 | 136.17 | 371.17 | 1237.01 | 24.18 | 130.50 | 367.17 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117747E+09 | 2694.51 | 09-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14953077.35 | 1506.64 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5936858.51 | 1357.22 | 31-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117747E+09 | 2694.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.965771E+10 | 0.683159E+10 | 35707.53 | 30-JAN-03:01 | 19743.40 | 0.00 |
February | 0.00 | 0.00 | 0.126581E+11 | 0.878312E+10 | 44810.26 | 09-FEB-03:01 | 23502.77 | 0.00 |
March | 0.00 | 0.00 | 0.202170E+11 | 0.148388E+11 | 62249.45 | 02-MAR-03:01 | 42511.20 | 0.00 |
April | 0.00 | 0.00 | 0.317034E+11 | 0.222388E+11 | 67258.19 | 30-APR-02:61 | 25323.19 | 0.00 |
May | 0.00 | 0.00 | 0.516221E+11 | 0.354285E+11 | 67258.19 | 01-MAY-02:61 | 30409.78 | 0.00 |
June | 0.00 | 0.00 | 0.665228E+11 | 0.390250E+11 | 67258.19 | 21-JUN-02:61 | 25654.49 | 0.00 |
July | 0.00 | 0.00 | 0.836812E+11 | 0.466157E+11 | 66887.31 | 06-JUL-02:02 | 20982.41 | 0.00 |
August | 0.00 | 0.00 | 0.888341E+11 | 0.483499E+11 | 66980.96 | 31-AUG-02:61 | 21658.82 | 0.00 |
September | 0.00 | 0.00 | 0.723172E+11 | 0.390909E+11 | 67258.19 | 12-SEP-02:02 | 22108.58 | 0.00 |
October | 0.00 | 0.00 | 0.532580E+11 | 0.322505E+11 | 67258.19 | 15-OCT-02:61 | 37482.87 | 0.00 |
November | 0.00 | 0.00 | 0.330723E+11 | 0.214175E+11 | 67258.19 | 02-NOV-02:61 | 34082.91 | 0.00 |
December | 0.00 | 0.00 | 0.167427E+11 | 0.109844E+11 | 55947.95 | 12-DEC-03:01 | 31348.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.540286E+12 | 0.325855E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.965771E+10 | 0.683159E+10 | 35707.53 | 19743.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.888341E+11 | 0.483499E+11 | 67258.19 | 42511.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.135220E+11 | 0.919533E+10 | 28816.25 | 30-JAN-03:11 | 14551.51 | 0.00 |
February | 0.00 | 0.00 | 0.160740E+11 | 0.108038E+11 | 29654.64 | 09-FEB-03:11 | 15092.98 | 0.00 |
March | 0.00 | 0.00 | 0.229337E+11 | 0.168971E+11 | 31066.25 | 28-MAR-10:55 | 16423.53 | 0.00 |
April | 0.00 | 0.00 | 0.339831E+11 | 0.247415E+11 | 31066.25 | 29-APR-19:55 | 12689.18 | 0.00 |
May | 0.00 | 0.00 | 0.530246E+11 | 0.406172E+11 | 31066.25 | 30-MAY-02:25 | 10644.27 | 0.00 |
June | 0.00 | 0.00 | 0.636090E+11 | 0.422929E+11 | 31066.25 | 25-JUN-06:45 | 8741.22 | 0.00 |
July | 0.00 | 0.00 | 0.708514E+11 | 0.466281E+11 | 31066.25 | 02-JUL-05:00 | 12499.65 | 0.00 |
August | 0.00 | 0.00 | 0.719507E+11 | 0.467683E+11 | 31066.25 | 31-AUG-03:10 | 11337.61 | 0.00 |
September | 0.00 | 0.00 | 0.662669E+11 | 0.397908E+11 | 31066.25 | 09-SEP-07:05 | 11626.13 | 0.00 |
October | 0.00 | 0.00 | 0.562035E+11 | 0.355945E+11 | 31066.25 | 09-OCT-04:02 | 8536.94 | 0.00 |
November | 0.00 | 0.00 | 0.358377E+11 | 0.236088E+11 | 31066.25 | 02-NOV-20:00 | 15148.05 | 0.00 |
December | 0.00 | 0.00 | 0.213568E+11 | 0.134678E+11 | 30445.90 | 05-DEC-14:55 | 13207.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.525613E+12 | 0.350406E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.135220E+11 | 0.919533E+10 | 28816.25 | 8536.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.719507E+11 | 0.467683E+11 | 31066.25 | 16423.53 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 3592.23 | 13813.49 | 12-JAN-14:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 3492.39 | 13669.77 | 01-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 3261.85 | 13021.45 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:02 | 2931.94 | 11868.85 | 01-APR-12:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 2620.27 | 10610.51 | 01-MAY-13:00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 2396.74 | 9516.16 | 01-JUN-12:15 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 2317.99 | 8991.85 | 31-JUL-12:20 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 2427.21 | 9689.40 | 31-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 2666.62 | 10806.80 | 30-SEP-12:15 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 2991.12 | 12105.95 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 3307.69 | 13164.72 | 30-NOV-13:20 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 3521.52 | 13759.72 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 2957.74 | ||||
Minimum of Months | 0.00 | 0.00 | 2317.99 | 8991.85 | ||
Maximum of Months | 0.00 | 0.00 | 3592.23 | 13813.49 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125448E+10 | 0.24 | 503.64 | 01-JAN-00:10 | 0.26 |
February | 0.114127E+10 | 0.25 | 503.64 | 01-FEB-00:10 | 0.26 |
March | 0.127897E+10 | 0.25 | 503.64 | 01-MAR-00:02 | 0.26 |
April | 0.124652E+10 | 0.25 | 503.64 | 01-APR-00:17 | 0.26 |
May | 0.128826E+10 | 0.25 | 503.64 | 01-MAY-00:08 | 0.26 |
June | 0.124774E+10 | 0.25 | 503.64 | 01-JUN-00:06 | 0.26 |
July | 0.129005E+10 | 0.25 | 503.64 | 01-JUL-00:06 | 0.26 |
August | 0.129015E+10 | 0.25 | 503.64 | 01-AUG-00:04 | 0.26 |
September | 0.124801E+10 | 0.25 | 503.64 | 01-SEP-00:04 | 0.26 |
October | 0.128834E+10 | 0.25 | 503.64 | 01-OCT-00:05 | 0.26 |
November | 0.124668E+10 | 0.25 | 503.64 | 01-NOV-00:08 | 0.26 |
December | 0.127583E+10 | 0.25 | 503.64 | 01-DEC-00:02 | 0.26 |
Annual Sum or Average | 0.150963E+11 | 0.25 | |||
Minimum of Months | 0.114127E+10 | 0.24 | 503.64 | 0.26 | |
Maximum of Months | 0.129015E+10 | 0.25 | 503.64 | 0.26 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.236704E+10 | 0.46 | 1312.18 | 25-JAN-03:01 | 0.61 |
February | 0.214039E+10 | 0.46 | 1611.63 | 09-FEB-03:01 | 0.68 |
March | 0.237299E+10 | 0.47 | 2532.84 | 02-MAR-03:01 | 0.85 |
April | 0.230645E+10 | 0.47 | 2644.07 | 18-APR-02:61 | 0.87 |
May | 0.252717E+10 | 0.48 | 2644.07 | 01-MAY-02:61 | 0.87 |
June | 0.280345E+10 | 0.51 | 2644.07 | 01-JUN-02:61 | 0.87 |
July | 0.337789E+10 | 0.55 | 2644.07 | 01-JUL-02:61 | 0.86 |
August | 0.355980E+10 | 0.57 | 2644.07 | 01-AUG-02:61 | 0.86 |
September | 0.296476E+10 | 0.53 | 2644.07 | 01-SEP-02:61 | 0.86 |
October | 0.254195E+10 | 0.48 | 2644.07 | 01-OCT-02:61 | 0.86 |
November | 0.231973E+10 | 0.47 | 2644.07 | 01-NOV-02:61 | 0.87 |
December | 0.237302E+10 | 0.47 | 2148.73 | 12-DEC-03:01 | 0.79 |
Annual Sum or Average | 0.316546E+11 | 0.49 | |||
Minimum of Months | 0.214039E+10 | 0.46 | 1312.18 | 0.61 | |
Maximum of Months | 0.355980E+10 | 0.57 | 2644.07 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117189E+10 | 0.52 | 1263.64 | 01-JAN-03:01 | 0.91 |
February | 0.109380E+10 | 0.53 | 1263.64 | 01-FEB-03:11 | 0.91 |
March | 0.129145E+10 | 0.55 | 1263.64 | 01-MAR-03:11 | 0.90 |
April | 0.152437E+10 | 0.61 | 1263.64 | 01-APR-02:11 | 0.90 |
May | 0.222284E+10 | 0.71 | 1263.64 | 01-MAY-02:61 | 0.90 |
June | 0.264888E+10 | 0.78 | 1263.64 | 01-JUN-02:61 | 0.90 |
July | 0.297943E+10 | 0.81 | 1263.64 | 01-JUL-02:61 | 0.89 |
August | 0.302545E+10 | 0.82 | 1263.64 | 01-AUG-00:04 | 0.89 |
September | 0.274464E+10 | 0.80 | 1263.64 | 01-SEP-00:04 | 0.89 |
October | 0.231767E+10 | 0.73 | 1263.64 | 01-OCT-00:05 | 0.89 |
November | 0.155957E+10 | 0.61 | 1263.64 | 01-NOV-02:61 | 0.90 |
December | 0.126260E+10 | 0.54 | 1263.64 | 01-DEC-03:01 | 0.91 |
Annual Sum or Average | 0.238426E+11 | 0.67 | |||
Minimum of Months | 0.109380E+10 | 0.52 | 1263.64 | 0.89 | |
Maximum of Months | 0.302545E+10 | 0.82 | 1263.64 | 0.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 53.81 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:05 | 0.00 | 0.00 | 54.82 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 55.07 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 55.51 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 55.23 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 56.41 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 56.63 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 56.61 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 56.33 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 55.13 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 55.41 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 55.01 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 53.81 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 56.63 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 44.96 | 44.96 | 3592.23 | 13813.49 | 12-JAN-14:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 54.82 | 54.82 | 3492.39 | 13669.77 | 01-FEB-14:00 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 55.06 | 55.06 | 3261.85 | 13021.45 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:02 | 55.50 | 55.50 | 2931.94 | 11868.85 | 01-APR-12:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 48.38 | 48.38 | 2620.27 | 10610.51 | 01-MAY-13:00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 56.40 | 56.40 | 2396.74 | 9516.16 | 01-JUN-12:15 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 56.63 | 56.63 | 2317.99 | 8991.85 | 31-JUL-12:20 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 56.61 | 56.61 | 2427.21 | 9689.40 | 31-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 56.35 | 56.35 | 2666.62 | 10806.80 | 30-SEP-12:15 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 48.21 | 48.21 | 2991.12 | 12105.95 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 55.42 | 55.42 | 3307.69 | 13164.72 | 30-NOV-13:20 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 55.02 | 55.02 | 3521.52 | 13759.72 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 2957.74 | ||||||
Minimum of Months | 0.00 | 0.00 | 44.96 | 44.96 | 2317.99 | 8991.85 | ||
Maximum of Months | 0.00 | 0.00 | 56.63 | 56.63 | 3592.23 | 13813.49 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.512166E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.561390E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.784411E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.106039E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.160253E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.198251E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.251197E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.266347E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.210254E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157970E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.107438E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.688367E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.171238E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.512166E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.266347E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.454493E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.499322E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.678658E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.943825E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.149104E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.178945E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.204760E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.208055E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.183512E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151673E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.969739E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.630952E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.149375E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.454493E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.208055E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.236704E+10 | 0.965771E+10 | 0.117747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214039E+10 | 0.126581E+11 | 14953077.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237299E+10 | 0.202170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230645E+10 | 0.317034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252717E+10 | 0.516221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.280345E+10 | 0.665228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.337789E+10 | 0.836812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.355980E+10 | 0.888341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.296476E+10 | 0.723172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254195E+10 | 0.532580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231973E+10 | 0.330723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237302E+10 | 0.167427E+11 | 5936858.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316546E+11 | 0.540286E+12 | 0.138637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214039E+10 | 0.965771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.355980E+10 | 0.888341E+11 | 0.117747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117189E+10 | 0.135220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109380E+10 | 0.160740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129145E+10 | 0.229337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152437E+10 | 0.339831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222284E+10 | 0.530246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264888E+10 | 0.636090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.297943E+10 | 0.708514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.302545E+10 | 0.719507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274464E+10 | 0.662669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231767E+10 | 0.562035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155957E+10 | 0.358377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126260E+10 | 0.213568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238426E+11 | 0.525613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109380E+10 | 0.135220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.302545E+10 | 0.719507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.236704E+10 | 0.00 | 0.00 | 35490669.47 | 0.271913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214039E+10 | 0.00 | 0.00 | 4468396.56 | 0.346903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237299E+10 | 0.00 | 0.00 | 0.00 | 0.547112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230645E+10 | 0.00 | 0.00 | 0.00 | 0.829746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252717E+10 | 0.00 | 0.00 | 0.00 | 0.134981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.280345E+10 | 0.00 | 0.00 | 0.00 | 0.170216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.337789E+10 | 0.00 | 0.00 | 0.00 | 0.217418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.355980E+10 | 0.00 | 0.00 | 0.00 | 0.230749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.296476E+10 | 0.00 | 0.00 | 0.00 | 0.180607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254195E+10 | 0.00 | 0.00 | 0.00 | 0.132551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231973E+10 | 0.00 | 0.00 | 0.00 | 0.842410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237302E+10 | 0.00 | 0.00 | 1777176.92 | 0.450887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316546E+11 | 0.00 | 0.00 | 41736242.94 | 0.139542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214039E+10 | 0.00 | 0.00 | 0.00 | 0.271913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.355980E+10 | 0.00 | 0.00 | 35490669.47 | 0.230749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117189E+10 | 0.00 | 0.00 | 0.00 | 0.337304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109380E+10 | 0.00 | 0.00 | 0.00 | 0.389943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129145E+10 | 0.00 | 0.00 | 0.00 | 0.549513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152437E+10 | 0.00 | 0.00 | 0.00 | 0.791388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222284E+10 | 0.00 | 0.00 | 0.00 | 0.126875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264888E+10 | 0.00 | 0.00 | 0.00 | 0.152456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.297943E+10 | 0.00 | 0.00 | 0.00 | 0.174966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.302545E+10 | 0.00 | 0.00 | 0.00 | 0.177801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274464E+10 | 0.00 | 0.00 | 0.00 | 0.156066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231767E+10 | 0.00 | 0.00 | 0.00 | 0.128497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155957E+10 | 0.00 | 0.00 | 0.00 | 0.813782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126260E+10 | 0.00 | 0.00 | 0.00 | 0.504692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238426E+11 | 0.00 | 0.00 | 0.00 | 0.125532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109380E+10 | 0.00 | 0.00 | 0.00 | 0.337304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.302545E+10 | 0.00 | 0.00 | 0.00 | 0.177801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243802E+10 | 0.204950E+09 | 0.00 | 22396452.49 | 0.00 | 0.00 | 0.313644E+10 | 0.00 | 3.62 |
February | 0.148814E+10 | 0.903975E+09 | 0.00 | 18224320.82 | 1004902.21 | 0.00 | 0.226163E+10 | 0.00 | 3.64 |
March | 0.973631E+09 | 0.229215E+10 | 0.00 | 17238804.70 | 6146481.72 | 0.00 | 0.150258E+10 | 0.00 | 3.67 |
April | 0.153805E+09 | 0.646338E+10 | 0.00 | 5442864.14 | 43958031.89 | 0.00 | 0.556046E+09 | 0.00 | 3.70 |
May | 2797075.06 | 0.151069E+11 | 0.00 | 1325225.07 | 0.294378E+09 | 0.00 | 23253918.76 | 0.00 | 3.79 |
June | 0.00 | 0.231734E+11 | 0.00 | 651501.28 | 0.493457E+09 | 0.00 | 4602743.25 | 0.00 | 3.89 |
July | 0.00 | 0.320196E+11 | 0.00 | 354878.41 | 0.776458E+09 | 0.00 | 5637130.14 | 0.00 | 3.92 |
August | 0.00 | 0.339836E+11 | 0.00 | 74804.61 | 0.707982E+09 | 0.00 | 67714.80 | 0.00 | 3.93 |
September | 1797.05 | 0.255512E+11 | 0.00 | 491894.95 | 0.524468E+09 | 0.00 | 707980.60 | 0.00 | 3.89 |
October | 7802764.77 | 0.157642E+11 | 0.00 | 1456441.50 | 0.271041E+09 | 0.00 | 35092048.90 | 0.00 | 3.81 |
November | 0.111488E+09 | 0.642678E+10 | 0.00 | 5422666.23 | 39387547.29 | 0.00 | 0.459553E+09 | 0.00 | 3.71 |
December | 0.121337E+10 | 0.140861E+10 | 0.00 | 18194906.87 | 1192942.10 | 0.00 | 0.227810E+10 | 0.00 | 3.65 |
Annual Sum or Average | 0.638906E+10 | 0.163299E+12 | 0.00 | 91274761.08 | 0.315947E+10 | 0.00 | 0.102637E+11 | 0.00 | 3.77 |
Minimum of Months | 0.00 | 0.204950E+09 | 0.00 | 74804.61 | 0.00 | 0.00 | 67714.80 | 0.00 | 3.62 |
Maximum of Months | 0.243802E+10 | 0.339836E+11 | 0.00 | 22396452.49 | 0.776458E+09 | 0.00 | 0.313644E+10 | 0.00 | 3.93 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302556E+10 | 50475141.88 | 0.00 | 64983152.93 | 6440.72 | 0.00 | 0.154445E+11 | 0.00 | 6.73 |
February | 0.149775E+10 | 0.340763E+09 | 0.00 | 61691269.43 | 883391.99 | 0.00 | 0.115736E+11 | 0.00 | 6.85 |
March | 0.777002E+09 | 0.117469E+10 | 0.00 | 69016387.17 | 2705177.09 | 0.00 | 0.977783E+10 | 0.00 | 7.07 |
April | 0.279356E+09 | 0.562381E+10 | 0.00 | 40116415.79 | 18781931.39 | 0.00 | 0.331109E+10 | 0.00 | 7.70 |
May | 5408807.94 | 0.187655E+11 | 0.00 | 11274021.06 | 57955571.58 | 0.00 | 0.519881E+09 | 0.00 | 9.20 |
June | 0.00 | 0.295823E+11 | 0.00 | 1367206.87 | 46618641.32 | 0.00 | 20343493.62 | 0.00 | 10.54 |
July | 0.00 | 0.359228E+11 | 0.00 | 826711.74 | 23859324.39 | 0.00 | 18811456.45 | 0.00 | 11.25 |
August | 0.00 | 0.365744E+11 | 0.00 | 0.00 | 16878200.09 | 0.00 | 0.00 | 0.00 | 11.36 |
September | 0.00 | 0.319425E+11 | 0.00 | 565869.89 | 44678358.21 | 0.00 | 12694390.14 | 0.00 | 10.75 |
October | 28871693.18 | 0.211454E+11 | 0.00 | 9074372.74 | 54824919.96 | 0.00 | 0.480480E+09 | 0.00 | 9.40 |
November | 0.339585E+09 | 0.609849E+10 | 0.00 | 38881927.34 | 14290899.16 | 0.00 | 0.301022E+10 | 0.00 | 7.77 |
December | 0.100269E+10 | 0.871942E+09 | 0.00 | 63010294.06 | 1630345.30 | 0.00 | 0.113500E+11 | 0.00 | 6.97 |
Annual Sum or Average | 0.695622E+10 | 0.188093E+12 | 0.00 | 0.360808E+09 | 0.283113E+09 | 0.00 | 0.555194E+11 | 0.00 | 8.81 |
Minimum of Months | 0.00 | 50475141.88 | 0.00 | 0.00 | 6440.72 | 0.00 | 0.00 | 0.00 | 6.73 |
Maximum of Months | 0.302556E+10 | 0.365744E+11 | 0.00 | 69016387.17 | 57955571.58 | 0.00 | 0.154445E+11 | 0.00 | 11.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:41
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.276923E+11 | 0.500284E+10 | 0.499230E+11 | 0.169028E+10 | 0.111050E+19 |
February | 0.317041E+11 | 0.273380E+10 | 0.341078E+11 | 0.114185E+10 | 0.103670E+19 |
March | 0.414718E+11 | 0.148150E+09 | 0.248050E+11 | 0.935136E+09 | 0.119560E+19 |
April | 0.465947E+11 | -0.550794E+10 | -0.467686E+10 | 0.595084E+09 | 0.122740E+19 |
May | 0.520515E+11 | -0.135787E+11 | -0.418738E+11 | -213828977.5 | 0.133430E+19 |
June | 0.517045E+11 | -0.198061E+11 | -0.651457E+11 | -677885974.6 | 0.131000E+19 |
July | 0.515185E+11 | -0.255782E+11 | -0.806579E+11 | -0.141512E+10 | 0.136580E+19 |
August | 0.498773E+11 | -0.278081E+11 | -0.835195E+11 | -0.154734E+10 | 0.136300E+19 |
September | 0.425794E+11 | -0.222984E+11 | -0.706278E+11 | -792145103.0 | 0.130250E+19 |
October | 0.350125E+11 | -0.141141E+11 | -0.459287E+11 | -391518818.5 | 0.125620E+19 |
November | 0.267092E+11 | -0.603725E+10 | -0.621024E+10 | 0.447995E+09 | 0.111740E+19 |
December | 0.243230E+11 | 0.155021E+10 | 0.313317E+11 | 0.115169E+10 | 0.108820E+19 |
Annual Sum or Average | 0.481239E+12 | -0.125294E+12 | -0.258473E+12 | 0.924187E+09 | 0.147076E+20 |
Minimum of Months | 0.243230E+11 | -0.278081E+11 | -0.835195E+11 | -0.154734E+10 | 0.103670E+19 |
Maximum of Months | 0.520515E+11 | 0.500284E+10 | 0.499230E+11 | 0.169028E+10 | 0.136580E+19 |