Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2024-07-03 12:20:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2320.99 | 4540.69 | 4540.69 |
Net Site Energy | 2320.99 | 4540.69 | 4540.69 |
Total Source Energy | 5621.92 | 10998.50 | 10998.50 |
Net Source Energy | 5621.92 | 10998.50 | 10998.50 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 5.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 478.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 455.60 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 272.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 360.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 38.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1491.10 | 829.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 5.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 478.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 15.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 272.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 360.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 12.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 19.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 5.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 478.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 455.60 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 272.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 360.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 38.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 470.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1480.25 | 704.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 966.56 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2917.13 | 1623.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 470.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1480.25 | 704.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 966.56 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2917.13 | 1623.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1491.102 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1491.102 | 100.00 |
Total On-Site and Utility Electric Sources | 1491.102 | 100.00 |
Total Electricity End Uses | 1491.102 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 340.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5952.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1_SUPPHEATCOIL | PSZ-AC_2:2_SUPPHEATCOIL | PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 66.16 | 0.00 | 19.55 | 27.07 | 19.55 |
Gross Window-Wall Ratio [%] | 24.00 | 0.00 | 28.36 | 39.27 | 28.36 |
Above Ground Window-Wall Ratio [%] | 24.00 | 0.00 | 28.36 | 39.27 | 28.36 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 66.16 | 0.00 | 19.55 | 27.07 | 19.55 |
Gross Window-Wall Ratio [%] | 24.00 | 0.00 | 28.36 | 39.27 | 28.36 |
Above Ground Window-Wall Ratio [%] | 24.00 | 0.00 | 28.36 | 39.27 | 28.36 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 66.16 | 66.16 | 20.6319 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 11.3949 | 18.52 | 1062.0430 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 66.16 | 66.16 | 18.1127 | 1.78 | 336.8677 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 66.16 | 66.16 | 18.1127 | 1.78 | 336.8677 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 20.6319 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.3949 | 18.52 | 1062.0430 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 18.1127 | 0.89 | 336.8677 | |||||||
Conditioned Total | 511.15 | 18.1127 | 0.89 | 336.8677 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 18.1127 | 1.78 | 336.8677 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-SEP-18:40 | 22-JAN-11:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-19:30 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48516.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18903.61 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10164.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20359.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1340.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 91855.14 | 46608.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 48516.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 17680.61 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 10164.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 20359.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 509.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 17.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1515.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 533.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 227.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1442.89 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 861.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 390.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 121.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4722.32 | 899.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 34.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2964.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 445.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2822.81 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1685.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 763.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 238.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9238.56 | 1759.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 34.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2964.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 445.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2822.81 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1685.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 763.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 238.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9238.56 | 1759.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.39 |
KITCHEN DIRECT AIR | 1.83 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.39 | 4.39 | 4.39 | 4.39 | 4.39 | 4.39 | 1.00 | 1.00 | 4.39 |
PSZ-AC_2:2 | 1.83 | 1.83 | 1.83 | 1.83 | 1.83 | 1.83 | 1.00 | 1.00 | 1.83 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.39 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.83 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.39 | 7115.41 |
PSZ-AC_2:2_ADDAQ FAN | 1.83 | 3049.45 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.39 | 4.39 | 4.39 | 4.39 | 108926.65 | 72980.85 | 32.11 | 108926.65 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.83 | 1.83 | 1.83 | 1.83 | 45562.76 | 30527.05 | 30.11 | 45562.76 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 HP COOLING COIL | 4.39 | 2.19 | 2.92 | 108926.65 | 54463.32 | 0.701080 | 0.701080 |
PSZ-AC_2:2 HP COOLING COIL | 1.83 | 0.917406 | 1.22 | 45562.76 | 22781.38 | 0.701080 | 0.701080 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | Design Size Speed 2 Gross Rated Heating Capacity [W] | Design Size Speed 1 Gross Rated Heating Capacity [W] | Design Size Resistive Defrost Heater Capacity | |
PSZ-AC_1:1 HEATING COIL | 4.39 | 2.19 | 108926.65 | 54463.32 | 0.000000 |
PSZ-AC_2:2 HEATING COIL | 1.83 | 0.917406 | 45562.70 | 22781.35 | 0.000000 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_SUPPHEATCOIL | 108926.65 |
PSZ-AC_2:2_SUPPHEATCOIL | 45562.76 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 103.03 | 66.16 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 20.632 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 85.559 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 11.395 | 412.767 | 649.276 | 0.000 | 0.000 | 0.000 | 1073.438 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 7669.876 | 20.632 | 27.379 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7669.876 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1588.510 | 11.395 | 211.016 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1588.510 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 493.000 | 3.536 | 65.490 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 493.000 | 493.000 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 730.000 | 5.237 | 96.973 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 730.000 | 730.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.3836 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.3836 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.508 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.508 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | -0.36752283E-16 | 0.36650618E-15 | -0.17323971E-14 | 0.96945811E-16 |
24 | 3 | -0.69118654E-08 | 0.27160578E-06 | -0.56853996E-04 | 0.15386634E-12 |
25 | 2 | 0.11860501E-03 | 0.58949329E-02 | 1.1525899 | -0.75054507E-04 |
26 | 1 | -0.13685427 | 0.15202565 | -17.175506 | 0.33646671 |
27 | 0 | 0.39128804 | 0.96631513E-01 | 16.277526 | |
28 | 4 | -0.17323971E-14 | 0.36650618E-15 | -0.36752283E-16 | 0.96945811E-16 |
29 | 3 | -0.56853996E-04 | 0.27160578E-06 | -0.69118654E-08 | 0.15386634E-12 |
30 | 2 | 1.1525899 | 0.58949329E-02 | 0.11860501E-03 | -0.75054507E-04 |
31 | 1 | -17.175506 | 0.15202565 | -0.13685427 | 0.33646671 |
32 | 0 | 16.277526 | 0.96631513E-01 | 0.39128804 | |
33 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
34 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
35 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
36 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
37 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
38 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
39 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
40 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
2 | NONRESWINDOW_U_1.22_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
3 | NONRESWINDOW_U_1.22_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
4 | NONRESWINDOW_U_1.22_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 8000.0 | 0.975 | 0.8950 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 14.749 | 0.4701 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 4 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 1 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 4 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 1 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 4 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 1 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone DINING | 1.2500 |
3 | Zone KITCHEN | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone DINING | 1.1500 |
3 | Zone KITCHEN | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 51957.26532 | 59750.85511 | 3.81433 | 4.38648 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 33.74200 | 1.65361E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 7505.63761 | 9382.04701 | 0.55058 | 1.33138 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 4.60000 | 5.25715E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 21749.69402 | 25012.14812 | 1.59549 | 1.83481 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 33.18900 | 1.65350E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 4.60000 | 5.25715E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 74730.45 | 4.38648 | 4.38648 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 44281.53 | 1.33138 | 1.33138 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 35261.20 | 1.83481 | 1.83481 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 37534.67 | 1.21700 | 1.21700 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.38648 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.83481 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.38648 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.38648 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.38648 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.38648 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.38648 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.38648 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.83481 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.83481 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.83481 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.83481 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.83481 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.83481 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.38648 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.83481 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.38648 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.38648 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7115.40804 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.38648 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.38648 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.38648 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.38648 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.38648 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.19324 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.92432 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 108926.65000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 54463.32500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 108926.65000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 72980.85344 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 108926.64693 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 4.38648 |
42 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.19324 |
43 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 108926.64693 |
44 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 54463.32347 |
45 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
46 | Coil:Heating:Electric | PSZ-AC_1:1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 108926.64693 |
47 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.83481 |
48 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
49 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.83481 |
50 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 3049.45352 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.83481 |
52 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.83481 |
53 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.83481 |
54 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.83481 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.83481 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.91741 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22321 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 45562.76000 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22781.38000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45562.76000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30527.05049 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 30.11000 |
65 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 45562.76192 |
66 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
67 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.83481 |
68 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.91741 |
69 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 45562.70176 |
70 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 22781.35088 |
71 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
72 | Coil:Heating:Electric | PSZ-AC_2:2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 45562.76192 |
73 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
74 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
75 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
76 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
77 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | 105808.9 | 9.92 | 9.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | 44258.6 | 10.20 | 10.16 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | 112450.8 | 61876.7 | 7.41 | 2 |
2 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | 47036.8 | 25882.3 | 7.89 | 2 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 30.58 | 50.13 | 30.58 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 19.55 | 19.55 | 19.55 | 90.00 | 90.00 | 15.24 | 1.28 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 41.86 | 68.93 | 41.86 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 27.07 | 27.07 | 27.07 | 180.00 | 90.00 | 21.10 | 1.28 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 30.58 | 50.13 | 30.58 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 19.55 | 19.55 | 19.55 | 270.00 | 90.00 | 15.24 | 1.28 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.384 | 0.358 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.384 | 0.358 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.384 | 0.351 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.384 | 0.351 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 3.9660921766E-002 | 0.1680186441 | Pass | Pass | 6.9110236717E-002 | 0.2819147473 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1757103082 | 0.5321310603 | Pass | Pass | 0.1748128379 | 0.8478620028 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4332444764 | 0.4275723984 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1185.13 | 3.94 | -109.5 | 49.23 | 2401.08 | 3529.90 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 50.13 | 30.58 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 68.93 | 41.86 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 50.13 | 30.58 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.348 | 0.384 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.348 | 0.384 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.348 | 0.384 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.348 | 0.384 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_1.22_SHGC_EAST_0.25 | 19.55 | 0.00 | 0.00 | 19.55 | 19.55 | 6.926 | 0.251 | 0.277 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_SOUTH_0.25 | 27.07 | 0.00 | 0.00 | 27.07 | 27.07 | 6.926 | 0.251 | 0.277 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_1.22_SHGC_WEST_0.25 | 19.55 | 0.00 | 0.00 | 19.55 | 19.55 | 6.926 | 0.251 | 0.277 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 66.16 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 66.16 | 6.926 | 0.251 | 0.277 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 20.6319 | 371.75 | 7669.88 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 139.55 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.3949 | 139.41 | 1588.51 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 28.90 |
Interior Lighting Total | 18.1127 | 511.15 | 9258.39 | 168.45 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4578.48 | AstronomicalClock | - | 83.73 | 83.73 | 71.96 | |
Exterior Lighting Total | 4578.48 | 71.96 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 108926.65 | 76366.30 | 32560.35 | 0.70 | 3.10 | |||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 45562.76 | 31943.14 | 13619.62 | 0.70 | 3.20 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 HP COOLING COIL | 105808.9 | 9.92 | 9.88 | ||||
PSZ-AC_2:2 HP COOLING COIL | 44258.6 | 10.20 | 10.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 112450.8 | 61876.7 | 7.41 | 2 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 47036.8 | 25882.3 | 7.89 | 2 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 108926.65 | 3.40 | |
PSZ-AC_1:1_SUPPHEATCOIL | Coil:Heating:Electric | 108926.65 | 1.00 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 45562.70 | 3.40 | |
PSZ-AC_2:2_SUPPHEATCOIL | Coil:Heating:Electric | 45562.76 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 2.55 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 966.87 | 4.39 | 7115.41 | 1622.12 | 1.00 | 1.18 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 966.87 | 1.83 | 3049.45 | 1662.00 | 1.00 | 1.23 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 0.80 | 0.98 | 0.90 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 14.75 | 0.47 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 51957.27 | 59750.86 | 160.73 | 3.814 | 4.386 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 23.98 | 0.01075 | 33.74 | 0.01654 | 1.331 | 0.00 |
KITCHEN | 21749.69 | 25012.15 | 179.42 | 1.595 | 1.835 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.01003 | 33.19 | 0.01654 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7505.64 | 9382.05 | 25.24 | 0.551 | 1.331 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00793 | 4.60 | 0.00526 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 22.69 | 0.00414 | 4.60 | 0.00526 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.39 | 4.39 | 1.33 | 1.33 | 4.3865 | 4.3865 | 4.3865 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.83 | 1.83 | 1.22 | 1.22 | 1.8348 | 1.8348 | 1.8348 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 108926.650 | 76366.296 | 4.386480 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 54463.32 | 33010.12 | 2.924320 | 26.99 | 20.53 | 0.01250592 | 11.58 | 11.58 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 45.5278 | 23.98 | 0.01074724 | 57.6570 | 51898.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 108926.647 | 108926.647 | 4.386476 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 54463.32 | 43289.74 | 2.193238 | 16.02 | 12.04 | 0.00712130 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 60.7037 | 21.00 | 0.00793368 | 51.2518 | 7499.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_1:1 | 108926.647 | 108926.647 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 108926.65 | 86579.47 | 4.386476 | 16.02 | 12.04 | 0.00712130 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 30.3519 | 21.00 | 0.00793368 | 51.2518 | 7499.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 45562.760 | 31943.140 | 1.834810 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 22781.38 | 12937.12 | 1.223207 | 31.44 | 23.21 | 0.01452572 | 13.55 | 12.40 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 99.4927 | 25.99 | 0.01003387 | 47.8203 | 21749.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 45562.762 | 45562.762 | 1.834812 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 22781.35 | 22781.35 | 0.917406 | 3.05 | 3.05 | 0.00487995 | 30.11 | 18.06 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 132.6568 | 22.69 | 0.00413692 | 24.2497 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_2:2 | 45562.762 | 45562.762 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 45562.76 | 45562.76 | 1.834812 | 3.05 | 3.05 | 0.00487995 | 30.11 | 18.06 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 66.3284 | 22.69 | 0.00413692 | 24.2497 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 108926.650 | 76366.296 | 4.386480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.0879 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.386476 | 5.27766280 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 54463.32 | 33010.12 | 1.0000 | 3.51844502 | 2.924320 | 26.99 | 20.53 | 0.01250592 | 59027.5 | 11.58 | 11.58 | 0.00850000 | 33074.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54463.32 | 33.90 | 0.01653638 | 25.13 | 1.33137743 | 45.5278 | 23.98 | 0.01074724 | 23.98 | 0.01074724 | 57.6570 | 51898.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 108926.647 | 108926.647 | 4.386476 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.386476 | 5.27766280 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 54463.32 | 43289.74 | 1.0000 | 2.63883140 | 2.193238 | 16.02 | 12.04 | 0.00712130 | 34121.8 | 32.11 | 18.72 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54463.32 | 4.60 | 0.00525715 | 4.60 | 1.33137743 | 60.7037 | 21.00 | 0.00793368 | 21.00 | 0.00793368 | 51.2518 | 7499.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 108926.647 | 108926.647 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.386476 | 5.27766280 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 108926.65 | 86579.47 | 1.0000 | 5.27766280 | 4.386476 | 16.02 | 12.04 | 0.00712130 | 34121.8 | 32.11 | 18.72 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 108926.65 | 4.60 | 0.00525715 | 4.60 | 1.33137743 | 30.3519 | 21.00 | 0.00793368 | 21.00 | 0.00793368 | 51.2518 | 7499.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 45562.760 | 31943.140 | 1.834810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.8426 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.834812 | 2.20758557 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 22781.38 | 12937.12 | 1.0000 | 1.47172177 | 1.223207 | 31.44 | 23.21 | 0.01452572 | 68772.7 | 13.55 | 12.40 | 0.00850000 | 35087.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22781.38 | 33.90 | 0.01653638 | 25.13 | 1.21700195 | 99.4927 | 25.96 | 0.01003387 | 25.99 | 0.01003387 | 47.8203 | 21749.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 45562.762 | 45562.762 | 1.834812 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.834812 | 2.20758557 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 22781.35 | 22781.35 | 1.0000 | 1.10379278 | 0.917406 | 3.05 | 3.05 | 0.00487995 | 15298.0 | 30.11 | 18.06 | 0.00800000 | 50711.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22781.35 | 4.60 | 0.00525715 | 4.60 | 1.21700195 | 132.6568 | 0.00 | 0.00413692 | 22.69 | 0.00413692 | 24.2497 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45562.762 | 45562.762 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.834812 | 2.20758557 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 45562.76 | 45562.76 | 1.0000 | 2.20758557 | 1.834812 | 3.05 | 3.05 | 0.00487995 | 15298.0 | 30.11 | 18.06 | 0.00800000 | 50711.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45562.76 | 4.60 | 0.00525715 | 4.60 | 1.21700195 | 66.3284 | 0.00 | 0.00413692 | 22.69 | 0.00413692 | 24.2497 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 6102.67 | 4039.67 | 3214.50 |
KITCHEN | 6564.17 | 6445.33 | 5941.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6574.67 | 6768.17 | 5952.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 41.17 | 0.00 | 0.00 |
KITCHEN | 0.00 | 584.00 | 0.00 | 340.17 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 621.50 | 0.00 | 340.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.319 | 0.897 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.595 | 0.025 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.089 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.040 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 35660606.24 | 0.00 | 35660606.24 | 7230137.17 | 42890743.40 | 41986318.57 | 1372.14 | 7387.86 | 0.00 | 325.78 |
KITCHEN | 33424497.97 | 0.00 | 33424497.97 | 119514.91 | 33544012.89 | 38379373.44 | 1343.52 | 7302.87 | 113.61 | 924.84 |
Total Facility | 69085104.21 | 0.00 | 69085104.21 | 7349652.08 | 76434756.29 | 80365692.01 | 1403.35 | 7390.56 | 113.61 | 978.76 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3315 | 0.0000 | 1.3315 | 0.2767 | 1.6082 | 1.3314 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.2170 | 0.0000 | 1.2170 | 0.0029 | 1.2199 | 1.2170 | 0.00 | 7187.00 | 0.00 |
Total Facility | 2.5485 | 0.0000 | 2.5485 | 0.2795 | 2.8281 | 2.5484 | 0.00 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 51622552.64 | 0.00 | 51622552.64 | 41986318.57 | 1343.52 | 1.47 | 7415.01 | 325.78 |
PSZ-AC_2:2 | 48385656.93 | 0.00 | 48385656.93 | 38379373.44 | 1293.42 | 3.49 | 7463.09 | 924.84 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9275 | 0.0000 | 1.9275 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.7617 | 0.0000 | 1.7617 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 125.66 | 0.00 | 7387.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 8111.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.9275 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.7617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 382 |
Defaulted Fields | 306 |
Fields with Defaults | 939 |
Autosized Fields | 51 |
Autosizable Fields | 123 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1491.10 | 9668.30 | 09-MAR-01:10 | 91855.14 | 09-SEP-18:40 |
Electricity:Building | 630.98 | 4348.05 | 01-JAN-01:10 | 35004.91 | 02-JAN-11:10 |
Electricity:Zone:DINING | 264.66 | 1630.49 | 01-JAN-01:10 | 13894.77 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 624.05 | 4211.77 | 01-JAN-01:10 | 32861.81 | 02-JAN-11:10 |
InteriorLights:Electricity | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 139.55 | 1150.48 | 01-JAN-01:10 | 6902.89 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 139.55 | 1150.48 | 01-JAN-01:10 | 6902.89 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 366.33 | 2717.56 | 01-JAN-01:10 | 21110.14 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 28.90 | 238.28 | 01-JAN-01:10 | 1429.66 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 28.90 | 238.28 | 01-JAN-01:10 | 1429.66 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 455.60 | 2823.01 | 01-JAN-01:10 | 24529.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 455.60 | 2823.01 | 01-JAN-01:10 | 24529.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 330.49 | 2343.01 | 01-JAN-01:10 | 17537.38 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 38.46 | 595.55 | 04-FEB-23:30 | 2780.19 | 12-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 31.97 | 527.64 | 04-FEB-23:30 | 1663.09 | 07-APR-03:20 |
LowTempRefrigeration:Refrigeration:Electricity | 12.13 | 0.00 | 01-JAN-11:10 | 1026.00 | 07-APR-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 19.40 | 509.69 | 09-MAR-00:20 | 637.09 | 01-JAN-02:00 |
ElectricityPurchased:Facility | 1491.10 | 9668.30 | 09-MAR-01:10 | 91855.14 | 09-SEP-18:40 |
ElectricityPurchased:Plant | 1491.10 | 9668.30 | 09-MAR-01:10 | 91855.14 | 09-SEP-18:40 |
Cogeneration:ElectricityPurchased | 1491.10 | 9668.30 | 09-MAR-01:10 | 91855.14 | 09-SEP-18:40 |
General:Cogeneration:ElectricityPurchased | 1491.10 | 9668.30 | 09-MAR-01:10 | 91855.14 | 09-SEP-18:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1491.10 | 9668.30 | 09-MAR-01:10 | 91855.14 | 09-SEP-18:40 |
ElectricityNet:Plant | 1491.10 | 9668.30 | 09-MAR-01:10 | 91855.14 | 09-SEP-18:40 |
Cogeneration:ElectricityNet | 1491.10 | 9668.30 | 09-MAR-01:10 | 91855.14 | 09-SEP-18:40 |
General:Cogeneration:ElectricityNet | 1491.10 | 9668.30 | 09-MAR-01:10 | 91855.14 | 09-SEP-18:40 |
Electricity:HVAC | 756.19 | 0.00 | 01-JAN-01:10 | 73138.42 | 21-DEC-04:30 |
Fans:Electricity | 272.11 | 0.00 | 01-JAN-01:10 | 10164.86 | 01-JAN-08:40 |
General:Fans:Electricity | 272.11 | 0.00 | 01-JAN-01:10 | 10164.86 | 01-JAN-08:40 |
Cooling:Electricity | 478.54 | 0.00 | 01-JAN-00:10 | 48868.33 | 09-SEP-18:10 |
General:Cooling:Electricity | 478.54 | 0.00 | 01-JAN-00:10 | 48868.33 | 09-SEP-18:10 |
Heating:Electricity | 5.53 | 0.00 | 01-JAN-00:10 | 66023.01 | 21-DEC-04:30 |
General:Heating:Electricity | 5.53 | 0.00 | 01-JAN-00:10 | 66023.01 | 21-DEC-04:30 |
ExteriorLights:Electricity | 71.96 | 0.00 | 01-JAN-07:30 | 4578.48 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 71.96 | 0.00 | 01-JAN-07:30 | 4578.48 | 01-JAN-00:10 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 12-FEB-11:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 12-FEB-11:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 829.89 | 1868.52 | 07-OCT-02:40 | 46608.55 | 22-JAN-11:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Plant | 360.10 | 58.26 | 21-NOV-04:10 | 23860.52 | 23-JAN-08:00 |
WaterSystems:NaturalGas | 360.10 | 58.26 | 21-NOV-04:10 | 23860.52 | 23-JAN-08:00 |
Water Heater:WaterSystems:NaturalGas | 360.10 | 58.26 | 21-NOV-04:10 | 23860.52 | 23-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 13-MAR-18:20 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 13-MAR-18:20 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 03-JAN-20:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 03-JAN-20:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2910.65 | 2933.67 | 05-FEB-01:10 | 233064.24 | 09-SEP-18:10 |
EnergyTransfer:Building | 930.02 | 1466.84 | 05-FEB-01:10 | 61650.80 | 30-AUG-17:20 |
EnergyTransfer:Zone:KITCHEN | 459.47 | 1466.84 | 05-FEB-01:10 | 24077.94 | 13-JUN-11:00 |
Refrigeration:EnergyTransfer | 155.97 | 2621.06 | 04-FEB-23:30 | 7834.84 | 12-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 77.99 | 1310.53 | 04-FEB-23:30 | 3917.42 | 12-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 77.99 | 1310.53 | 04-FEB-23:30 | 3917.42 | 12-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 77.99 | 1310.53 | 04-FEB-23:30 | 3917.42 | 12-JAN-11:40 |
EnergyTransfer:Plant | 278.19 | 1466.84 | 05-FEB-01:10 | 16545.10 | 19-JAN-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.43 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 65.56 | 1309.93 | 09-MAR-00:20 | 2238.70 | 01-JAN-02:00 |
EnergyTransfer:Zone:DINING | 470.55 | 0.00 | 01-JAN-01:10 | 40639.00 | 30-AUG-17:10 |
Heating:EnergyTransfer | 1.70 | 0.00 | 01-JAN-00:10 | 13809.70 | 09-SEP-23:10 |
Heating:EnergyTransfer:Zone:DINING | 1.70 | 0.00 | 01-JAN-00:10 | 13809.70 | 09-SEP-23:10 |
General:Heating:EnergyTransfer | 1.70 | 0.00 | 01-JAN-00:10 | 13809.70 | 09-SEP-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 1.70 | 0.00 | 01-JAN-00:10 | 13809.70 | 09-SEP-23:10 |
Cooling:EnergyTransfer | 850.34 | 0.00 | 01-JAN-01:10 | 59307.79 | 30-AUG-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 468.86 | 0.00 | 01-JAN-01:10 | 40639.00 | 30-AUG-17:10 |
General:Cooling:EnergyTransfer | 850.34 | 0.00 | 01-JAN-01:10 | 59307.79 | 30-AUG-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 468.86 | 0.00 | 01-JAN-01:10 | 40639.00 | 30-AUG-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 381.48 | 0.00 | 01-JAN-01:10 | 20675.19 | 03-JAN-05:20 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 381.48 | 0.00 | 01-JAN-01:10 | 20675.19 | 03-JAN-05:20 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 200.20 | 0.00 | 01-JAN-01:10 | 13900.22 | 23-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 200.20 | 0.00 | 01-JAN-01:10 | 13900.22 | 23-JAN-07:20 |
WaterSystems:PlantLoopHeatingDemand | 200.20 | 0.00 | 01-JAN-01:10 | 13900.22 | 23-JAN-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 200.20 | 0.00 | 01-JAN-01:10 | 13900.22 | 23-JAN-07:20 |
EnergyTransfer:HVAC | 1702.44 | 0.00 | 01-JAN-00:10 | 164560.61 | 06-OCT-11:20 |
CoolingCoils:EnergyTransfer | 1687.87 | 0.00 | 01-JAN-00:10 | 164560.61 | 06-OCT-11:20 |
HeatingCoils:EnergyTransfer | 14.57 | 0.00 | 01-JAN-00:10 | 101384.02 | 21-DEC-04:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 200.20 | 0.00 | 01-JAN-01:10 | 13900.22 | 23-JAN-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 200.20 | 0.00 | 01-JAN-01:10 | 13900.22 | 23-JAN-07:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 1.696 | -468.852 | 0.000 | 0.000 | 209.157 | 139.549 | 93.832 | 64.135 | 0.000 | 18.798 | 2.893 | 0.000 | -32.800 | 0.000 | -28.409 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -381.478 | 0.000 | 0.000 | 4.922 | 28.902 | 293.083 | 0.000 | 0.000 | 0.083 | 55.416 | 0.000 | 0.000 | 0.000 | -0.928 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.312 | 40.977 | 0.000 | 0.000 | 0.000 | -48.289 | -0.000 |
Total Facility | 0.000 | 0.000 | 1.696 | -850.330 | 0.000 | 0.000 | 214.079 | 168.451 | 386.915 | 64.135 | 0.000 | 26.194 | 99.286 | 0.000 | -32.800 | 0.000 | -77.626 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 17-OCT-03:01 | 0.00 | 0.00 | 0.00 | -67495.39 | 0.00 | 0.00 | 0.00 | 1150.48 | 900.01 | 0.00 | 0.00 | 0.00 | 68212.82 | 0.00 | -2642.82 | 0.00 | -125.10 | 0.00 |
KITCHEN | 09-NOV-04:11 | 0.00 | 0.00 | 0.00 | -68209.17 | 0.00 | 0.00 | 0.00 | 238.28 | 3668.14 | 0.00 | 0.00 | 0.00 | 64615.70 | 0.00 | -0.00 | 0.00 | -312.94 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-OCT-03:01 | 0.00 | 0.00 | 0.00 | -121156.36 | 0.00 | 0.00 | 0.00 | 1388.76 | 4568.15 | 0.00 | 0.00 | 368.85 | 118895.48 | 0.00 | -3592.59 | 0.00 | -472.28 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 09-SEP-23:01 | 0.00 | 0.00 | 19581.09 | 0.00 | 0.00 | 0.00 | 973.97 | 1533.98 | 540.00 | 1725.27 | 0.00 | 280.04 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24634.36 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-SEP-23:01 | -12226.60 | 12226.60 | 19581.09 | -12226.60 | 0.00 | 0.00 | 996.08 | 1851.68 | 3230.09 | 1725.27 | 0.00 | 1033.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16190.84 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.3865 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.3865 | 0.3035 | 1.0000 | Not calculated | 1.3314 | 0.3035 | ||
PSZ-AC_2:2 | 1.8348 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8348 | 0.0995 | 1.0000 | Not calculated | 0.1826 | 0.0995 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.3865 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.3865 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3035 | ||
PSZ-AC_2:2 | 1.8348 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8348 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.0995 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3865 | 4.3865 | 4.3865 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8348 | 1.8348 | 1.8348 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.3865 | 4.3865 | 4.3865 | 4.3865 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8348 | 1.8348 | 1.8348 | 1.8348 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3865 | 4.3865 | 4.3865 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8348 | 1.8348 | 1.8348 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.3865 | 4.3865 | 4.3865 | 4.3865 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8348 | 1.8348 | 1.8348 | 1.8348 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 340.17 |
Number of hours not met | 340.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 5.53 | 66023.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 478.54 | 48868.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 168.45 | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.96 | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 15.55 | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 23.02 | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 272.11 | 10164.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 360.10 | 23860.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 12.13 | 1026.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 19.40 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 494.06 | 1491.10 |
Natural Gas | 469.79 | 829.89 |
Additional | 0.00 | 0.00 |
Total | 963.85 | 2320.99 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 329.55 |
Space Heating | 10.83 |
Space Cooling | 936.20 |
Fans (All) | 532.35 |
Service Water Heating | 0.00 |
Receptacle Equipment | 891.32 |
Miscellaneous (All) | 2917.13 |
Subtotal | 2917.13 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 704.49 |
Miscellaneous (All) | 1623.56 |
Subtotal | 1623.56 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.26 |
Space Heating | 0.24 |
Space Cooling | 20.62 |
Fans (All) | 11.72 |
Service Water Heating | 15.51 |
Receptacle Equipment | 39.87 |
Miscellaneous | 4.78 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8014.83 | 719.67 | 25.50 | 0.00 | 0.00 |
KITCHEN | 7175.83 | 1306.00 | 278.17 | 0.00 | 0.00 |
ATTIC | 5221.83 | 796.17 | 831.00 | 1025.33 | 885.67 |
Min | 5221.83 | 719.67 | 25.50 | 0.00 | 0.00 |
Max | 8014.83 | 1306.00 | 831.00 | 1025.33 | 885.67 |
Average | 6804.17 | 940.61 | 378.22 | 341.78 | 295.22 |
Sum | 20412.50 | 2821.83 | 1134.67 | 1025.33 | 885.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 822007.67 | 2030.00 | 184.33 | 0.00 | 0.00 |
KITCHEN | 17646.50 | 1581.50 | 5.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822007.67 | 2030.00 | 184.33 | 0.00 | 0.00 |
Average | 279884.72 | 1203.83 | 63.11 | 0.00 | 0.00 |
Sum | 839654.17 | 3611.50 | 189.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 4146.00 | 4608.17 | 5.83 | 0.00 | 0.00 |
KITCHEN | 1952.67 | 6783.67 | 23.67 | 0.00 | 0.00 |
ATTIC | 3413.00 | 2941.67 | 641.50 | 510.00 | 1253.83 |
Min | 1952.67 | 2941.67 | 5.83 | 0.00 | 0.00 |
Max | 4146.00 | 6783.67 | 641.50 | 510.00 | 1253.83 |
Average | 3170.56 | 4777.83 | 223.67 | 170.00 | 417.94 |
Sum | 9511.67 | 14333.50 | 671.00 | 510.00 | 1253.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 418030.67 | 406163.33 | 28.00 | 0.00 | 0.00 |
KITCHEN | 4266.33 | 14966.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 418030.67 | 406163.33 | 28.00 | 0.00 | 0.00 |
Average | 140765.67 | 140376.67 | 9.33 | 0.00 | 0.00 |
Sum | 422297.00 | 421130.00 | 28.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:58
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270412E+11 | 62670.80 | 02-JAN-04:01 | 17.00 | 16.27 | 0.143650E+11 | 14051.29 | 28-JAN-19:00 | 15.00 | 12.68 |
February | 0.262744E+11 | 59721.61 | 25-FEB-04:01 | 15.23 | 15.23 | 0.133039E+11 | 14051.18 | 25-FEB-19:30 | 19.65 | 17.83 |
March | 0.304773E+11 | 58586.27 | 01-MAR-04:01 | 15.52 | 13.89 | 0.150541E+11 | 14051.18 | 04-MAR-19:00 | 20.50 | 14.09 |
April | 0.360013E+11 | 60932.08 | 16-APR-03:01 | 18.62 | 16.92 | 0.148542E+11 | 14051.69 | 29-APR-18:49 | 26.70 | 22.81 |
May | 0.466612E+11 | 58621.65 | 12-MAY-03:01 | 23.22 | 20.24 | 0.154330E+11 | 14053.11 | 20-MAY-18:00 | 26.10 | 23.27 |
June | 0.476384E+11 | 61551.82 | 07-JUN-03:01 | 21.10 | 18.25 | 0.150153E+11 | 14051.97 | 03-JUN-18:30 | 21.10 | 18.25 |
July | 0.496188E+11 | 45161.56 | 18-JUL-03:01 | 24.40 | 22.88 | 0.153363E+11 | 14052.00 | 29-JUL-18:10 | 28.40 | 25.38 |
August | 0.501992E+11 | 62509.58 | 20-AUG-03:01 | 23.53 | 17.99 | 0.155306E+11 | 14052.00 | 12-AUG-18:00 | 23.53 | 17.99 |
September | 0.456737E+11 | 55788.27 | 22-SEP-03:01 | 21.62 | 20.07 | 0.149108E+11 | 14052.46 | 23-SEP-18:30 | 26.65 | 23.79 |
October | 0.448686E+11 | 67557.77 | 17-OCT-03:01 | 18.08 | 14.23 | 0.153101E+11 | 14052.93 | 21-OCT-18:00 | 25.00 | 24.24 |
November | 0.342046E+11 | 57383.61 | 07-NOV-04:01 | 20.95 | 19.73 | 0.146400E+11 | 14052.40 | 25-NOV-19:00 | 16.50 | 13.17 |
December | 0.301974E+11 | 53999.69 | 11-DEC-04:01 | 21.00 | 20.31 | 0.146113E+11 | 14052.34 | 23-DEC-19:30 | 18.00 | 13.92 |
Annual Sum or Average | 0.468856E+12 | 0.178365E+12 | ||||||||
Minimum of Months | 0.262744E+11 | 45161.56 | 15.23 | 13.89 | 0.133039E+11 | 14051.18 | 15.00 | 12.68 | ||
Maximum of Months | 0.501992E+11 | 67557.77 | 24.40 | 22.88 | 0.155306E+11 | 14053.11 | 28.40 | 25.38 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306501E+11 | 65616.02 | 03-JAN-04:01 | 5.67 | 3.05 | 0.105313E+11 | 6930.43 | 31-JAN-11:50 | 23.17 | 20.94 |
February | 0.273631E+11 | 63188.44 | 12-FEB-04:11 | 14.60 | 8.54 | 0.953372E+10 | 6930.43 | 01-FEB-11:39 | 14.60 | 8.54 |
March | 0.303666E+11 | 62438.01 | 20-MAR-03:01 | 12.55 | 8.37 | 0.105709E+11 | 6930.44 | 06-MAR-11:50 | 12.55 | 8.37 |
April | 0.302105E+11 | 62004.38 | 11-APR-03:01 | 11.55 | 8.65 | 0.102518E+11 | 6930.44 | 24-APR-10:00 | 23.80 | 23.06 |
May | 0.333170E+11 | 33173.25 | 17-MAY-03:01 | 22.20 | 19.73 | 0.105983E+11 | 6956.61 | 26-MAY-10:00 | 31.10 | 25.83 |
June | 0.329268E+11 | 38054.03 | 07-JUN-03:01 | 21.10 | 18.25 | 0.102622E+11 | 6964.39 | 19-JUN-10:00 | 31.70 | 26.19 |
July | 0.341499E+11 | 25772.54 | 18-JUL-03:01 | 24.40 | 22.88 | 0.106066E+11 | 6973.95 | 03-JUL-10:00 | 24.40 | 22.88 |
August | 0.346667E+11 | 37257.41 | 20-AUG-03:01 | 23.53 | 17.99 | 0.106088E+11 | 6973.36 | 14-AUG-10:00 | 23.53 | 17.99 |
September | 0.329679E+11 | 32189.03 | 22-SEP-03:01 | 21.62 | 20.07 | 0.102598E+11 | 6956.88 | 18-SEP-10:50 | 21.62 | 20.07 |
October | 0.333189E+11 | 61062.79 | 27-OCT-03:01 | 14.17 | 7.88 | 0.105972E+11 | 6987.73 | 06-OCT-10:00 | 14.17 | 7.88 |
November | 0.304966E+11 | 68286.98 | 09-NOV-04:11 | 11.23 | 6.44 | 0.102400E+11 | 6931.80 | 02-NOV-10:50 | 11.23 | 6.44 |
December | 0.310499E+11 | 60603.41 | 29-DEC-04:11 | 11.00 | 9.86 | 0.105498E+11 | 6930.44 | 28-DEC-11:09 | 11.00 | 9.86 |
Annual Sum or Average | 0.381484E+12 | 0.124610E+12 | ||||||||
Minimum of Months | 0.273631E+11 | 25772.54 | 5.67 | 3.05 | 0.953372E+10 | 6930.43 | 11.00 | 6.44 | ||
Maximum of Months | 0.346667E+11 | 68286.98 | 24.40 | 22.88 | 0.106088E+11 | 6987.73 | 31.70 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 | 18.20 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 | 17.16 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.00 | 0.00 | 01-APR-00:01 | 20.72 | 19.79 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 | 19.11 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.11 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.93 | 21.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.07 | 23.10 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 | 23.55 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.55 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 22.17 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 21.63 | 21.01 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 | 12.36 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5388126.46 | 13372.27 | 05-JAN-05:01 | 0.83 |
February | 65872874.40 | 14146.58 | 05-FEB-04:03 | -1.7 |
March | 681816.04 | 4045.01 | 10-MAR-05:02 | 5.83 |
April | 26255328.01 | 6105.10 | 29-APR-23:02 | 25.50 |
May | 0.258726E+09 | 8538.09 | 02-MAY-23:02 | 26.93 |
June | 0.286448E+09 | 10554.27 | 28-JUN-23:01 | 28.22 |
July | 0.387087E+09 | 10812.04 | 04-JUL-23:01 | 28.30 |
August | 0.314798E+09 | 10849.26 | 24-AUG-23:01 | 28.52 |
September | 0.192586E+09 | 19572.53 | 09-SEP-23:01 | 33.88 |
October | 0.127392E+09 | 8173.13 | 13-OCT-23:02 | 26.83 |
November | 13529399.70 | 5202.48 | 01-NOV-23:02 | 24.75 |
December | 16679908.99 | 9465.37 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.169545E+10 | |||
Minimum of Months | 681816.04 | 4045.01 | -1.7 | |
Maximum of Months | 0.387087E+09 | 19572.53 | 33.88 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:01 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:01 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117915E+11 | 6902.89 | 02-JAN-10:09 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
February | 0.106801E+11 | 6902.89 | 01-FEB-10:09 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
March | 0.119793E+11 | 6902.89 | 01-MAR-10:09 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
April | 0.114574E+11 | 6902.89 | 01-APR-16:10 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
May | 0.118854E+11 | 6902.89 | 01-MAY-09:09 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
June | 0.115789E+11 | 6902.89 | 01-JUN-09:09 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
July | 0.117653E+11 | 6902.89 | 01-JUL-16:10 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
August | 0.119793E+11 | 6902.89 | 01-AUG-09:09 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
September | 0.114602E+11 | 6902.89 | 01-SEP-09:09 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
October | 0.117901E+11 | 6902.89 | 02-OCT-09:09 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
November | 0.114146E+11 | 6902.89 | 01-NOV-09:09 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
December | 0.117667E+11 | 6902.89 | 01-DEC-10:09 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
Annual Sum or Average | 0.139549E+12 | 0.125110E+12 | ||||
Minimum of Months | 0.106801E+11 | 6902.89 | 0.959744E+10 | 6991.88 | ||
Maximum of Months | 0.119793E+11 | 6902.89 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.244214E+10 | 1429.66 | 02-JAN-10:09 | 0.280690E+11 | 17537.38 | 01-JAN-11:09 |
February | 0.221197E+10 | 1429.66 | 01-FEB-10:09 | 0.253527E+11 | 17537.38 | 01-FEB-11:09 |
March | 0.248103E+10 | 1429.66 | 01-MAR-10:09 | 0.280692E+11 | 17537.38 | 01-MAR-11:09 |
April | 0.237295E+10 | 1429.66 | 01-APR-16:10 | 0.271636E+11 | 17537.38 | 01-APR-10:09 |
May | 0.246159E+10 | 1429.66 | 01-MAY-09:09 | 0.280691E+11 | 17537.38 | 01-MAY-10:09 |
June | 0.239811E+10 | 1429.66 | 01-JUN-09:09 | 0.271637E+11 | 17537.38 | 01-JUN-10:09 |
July | 0.243671E+10 | 1429.66 | 01-JUL-16:10 | 0.280690E+11 | 17537.38 | 01-JUL-10:09 |
August | 0.248103E+10 | 1429.66 | 01-AUG-09:09 | 0.280692E+11 | 17537.38 | 01-AUG-10:09 |
September | 0.237352E+10 | 1429.66 | 01-SEP-09:09 | 0.271636E+11 | 17537.38 | 01-SEP-10:09 |
October | 0.244186E+10 | 1429.66 | 02-OCT-09:09 | 0.280690E+11 | 17537.38 | 01-OCT-10:09 |
November | 0.236408E+10 | 1429.66 | 01-NOV-09:09 | 0.271636E+11 | 17537.38 | 01-NOV-10:09 |
December | 0.243700E+10 | 1429.66 | 01-DEC-10:09 | 0.280690E+11 | 17537.38 | 01-DEC-11:09 |
Annual Sum or Average | 0.289020E+11 | 0.330491E+12 | ||||
Minimum of Months | 0.221197E+10 | 1429.66 | 0.253527E+11 | 17537.38 | ||
Maximum of Months | 0.248103E+10 | 1429.66 | 0.280692E+11 | 17537.38 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.117915E+11 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52511537.17 | 0.682727E+10 |
February | 0.272721E+11 | 0.106801E+11 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96822819.86 | 0.500142E+10 |
March | 0.305458E+11 | 0.119793E+11 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224695E+09 | 0.455390E+10 |
April | 0.292871E+11 | 0.114574E+11 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728446E+09 | 0.193705E+10 |
May | 0.303219E+11 | 0.118854E+11 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288330E+10 | 41694230.39 |
June | 0.295292E+11 | 0.115789E+11 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340957E+10 | 34906500.60 |
July | 0.300798E+11 | 0.117653E+11 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352604E+10 | 23926976.18 |
August | 0.305458E+11 | 0.119793E+11 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330827E+10 | 80496747.28 |
September | 0.292871E+11 | 0.114602E+11 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215345E+10 | 0.158210E+09 |
October | 0.300980E+11 | 0.117901E+11 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183105E+10 | 0.969463E+09 |
November | 0.290996E+11 | 0.114146E+11 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379616E+09 | 0.326229E+10 |
December | 0.300798E+11 | 0.117667E+11 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204587E+09 | 0.551812E+10 |
Annual Sum or Average | 0.356244E+12 | 0.139549E+12 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187983E+11 | 0.284088E+11 |
Minimum of Months | 0.272721E+11 | 0.106801E+11 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52511537.17 | 23926976.18 |
Maximum of Months | 0.305458E+11 | 0.119793E+11 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352604E+10 | 0.682727E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.244214E+10 | 0.231104E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 12662.68 | 0.163943E+09 |
February | 0.732850E+09 | 0.221197E+10 | 0.208739E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 150561.48 | 0.118596E+09 |
March | 0.820818E+09 | 0.248103E+10 | 0.231105E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 553948.38 | 0.143083E+09 |
April | 0.786997E+09 | 0.237295E+10 | 0.223649E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 2706954.60 | 64399572.04 |
May | 0.814802E+09 | 0.246159E+10 | 0.231104E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 12600083.05 | 24870083.39 |
June | 0.793501E+09 | 0.239811E+10 | 0.223650E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 13368909.43 | 18629819.33 |
July | 0.808298E+09 | 0.243671E+10 | 0.231104E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 14878437.00 | 15458773.51 |
August | 0.820818E+09 | 0.248103E+10 | 0.231105E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 16105994.50 | 26701717.11 |
September | 0.786997E+09 | 0.237352E+10 | 0.223649E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 11587244.28 | 33376616.80 |
October | 0.808786E+09 | 0.244186E+10 | 0.231104E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 9867051.44 | 73810190.72 |
November | 0.781956E+09 | 0.236408E+10 | 0.223648E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 917382.49 | 95321033.64 |
December | 0.808298E+09 | 0.243700E+10 | 0.231104E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 515910.64 | 0.149977E+09 |
Annual Sum or Average | 0.957291E+10 | 0.289020E+11 | 0.272106E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 83265139.99 | 0.928166E+09 |
Minimum of Months | 0.732850E+09 | 0.221197E+10 | 0.208739E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 12662.68 | 15458773.51 |
Maximum of Months | 0.820818E+09 | 0.248103E+10 | 0.231105E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 16105994.50 | 0.163943E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527982E+09 | 0.324864E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707369E+09 | 0.346453E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569251E+09 | 0.389042E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700401E+09 | 0.493879E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587573E+09 | 0.465905E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644929E+09 | 0.525751E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636005E+09 | 0.486129E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574311E+09 | 0.457534E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573304E+09 | 0.378490E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433906E+09 | 0.352609E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785653E+09 | 0.310748E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571811E+09 | 0.297540E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731249E+10 | 0.482894E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433906E+09 | 0.297540E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785653E+09 | 0.525751E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 6902.89 | 02-JAN-10:09 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.25 | 02-JAN-13:00 | 11947.33 | 04-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 6902.89 | 01-FEB-10:09 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2627.31 | 02-FEB-13:00 | 12814.51 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 6902.89 | 01-MAR-10:09 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.05 | 30-MAR-13:00 | 8972.82 | 09-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 6902.89 | 01-APR-16:10 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4409.99 | 28-APR-13:00 | 6838.71 | 10-APR-20:00 |
May | 30255.31 | 06-MAY-18:10 | 6902.89 | 01-MAY-09:09 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5150.73 | 25-MAY-17:08 | 745.78 | 19-MAY-18:52 |
June | 30255.31 | 03-JUN-18:10 | 6902.89 | 01-JUN-09:09 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5379.24 | 13-JUN-17:03 | 913.22 | 07-JUN-06:10 |
July | 30255.31 | 01-JUL-18:10 | 6902.89 | 01-JUL-16:10 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5926.59 | 20-JUL-12:00 | 1116.93 | 11-JUL-19:53 |
August | 30255.31 | 05-AUG-18:10 | 6902.89 | 01-AUG-09:09 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6335.44 | 02-AUG-17:10 | 1995.72 | 16-AUG-19:00 |
September | 30255.31 | 02-SEP-18:10 | 6902.89 | 01-SEP-09:09 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7283.77 | 09-SEP-18:03 | 3007.86 | 07-SEP-17:53 |
October | 30255.31 | 07-OCT-18:10 | 6902.89 | 02-OCT-09:09 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5274.17 | 05-OCT-17:03 | 6736.16 | 27-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 6902.89 | 01-NOV-09:09 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3271.68 | 02-NOV-12:00 | 8779.40 | 15-NOV-20:00 |
December | 30255.31 | 02-DEC-19:10 | 6902.89 | 01-DEC-10:09 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2732.13 | 13-DEC-14:00 | 11995.96 | 20-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 6902.89 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.25 | 745.78 | |||||
Maximum of Months | 30255.31 | 6902.89 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7283.77 | 12814.51 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1429.66 | 02-JAN-10:09 | 14274.50 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 2.53 | 16-JAN-15:00 | 540.24 | 09-JAN-03:00 |
February | 813.01 | 04-FEB-19:10 | 1429.66 | 01-FEB-10:09 | 14274.50 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 14.66 | 02-FEB-13:00 | 573.77 | 04-FEB-04:40 |
March | 813.01 | 04-MAR-19:10 | 1429.66 | 01-MAR-10:09 | 14274.50 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 13.60 | 27-MAR-15:00 | 571.97 | 21-MAR-03:40 |
April | 813.01 | 01-APR-18:10 | 1429.66 | 01-APR-16:10 | 14274.50 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 29.65 | 29-APR-15:53 | 416.86 | 02-APR-03:10 |
May | 813.01 | 06-MAY-18:10 | 1429.66 | 01-MAY-09:09 | 14274.50 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 40.21 | 25-MAY-14:00 | 180.72 | 09-MAY-02:10 |
June | 813.01 | 03-JUN-18:10 | 1429.66 | 01-JUN-09:09 | 14274.50 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 42.70 | 08-JUN-15:00 | 212.56 | 08-JUN-02:50 |
July | 813.01 | 01-JUL-18:10 | 1429.66 | 01-JUL-16:10 | 14274.50 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 73.28 | 19-JUL-12:53 | 169.94 | 31-JUL-02:10 |
August | 813.01 | 05-AUG-18:10 | 1429.66 | 01-AUG-09:09 | 14274.50 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 46.36 | 20-AUG-14:00 | 282.79 | 16-AUG-02:50 |
September | 813.01 | 02-SEP-18:10 | 1429.66 | 01-SEP-09:09 | 14274.50 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 151.80 | 09-SEP-23:10 | 276.65 | 13-SEP-02:50 |
October | 813.01 | 07-OCT-18:10 | 1429.66 | 02-OCT-09:09 | 14274.50 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 54.56 | 09-OCT-14:00 | 362.43 | 29-OCT-01:50 |
November | 813.01 | 04-NOV-18:10 | 1429.66 | 01-NOV-09:09 | 14274.50 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 11.84 | 02-NOV-14:53 | 401.29 | 09-NOV-04:10 |
December | 813.01 | 02-DEC-19:10 | 1429.66 | 01-DEC-10:09 | 14274.50 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 12.23 | 13-DEC-14:30 | 598.71 | 20-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1429.66 | 14274.50 | 7874.59 | 0.00 | 0.00 | 0.00 | 2.53 | 169.94 | ||||||
Maximum of Months | 813.01 | 1429.66 | 14274.50 | 7874.59 | 0.00 | 0.00 | 0.00 | 151.80 | 598.71 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.44 | 05-JAN-01:00 | 6890.93 | 21-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.07 | 10-FEB-07:53 | 7112.68 | 13-FEB-13:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1685.85 | 14-MAR-07:33 | 7794.72 | 13-MAR-13:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1588.56 | 11-APR-06:53 | 8237.15 | 21-APR-13:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1642.38 | 02-MAY-23:00 | 8043.74 | 10-MAY-14:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1428.18 | 28-JUN-02:00 | 8037.38 | 28-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1435.20 | 15-JUL-05:00 | 8047.33 | 20-JUL-14:02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.30 | 30-AUG-23:20 | 7765.37 | 10-AUG-14:13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.40 | 01-SEP-06:45 | 7512.88 | 02-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.22 | 23-OCT-23:55 | 6608.86 | 02-OCT-13:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1408.32 | 24-NOV-06:00 | 6313.98 | 23-NOV-13:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2383.73 | 19-DEC-07:42 | 6179.56 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.22 | 6179.56 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2383.73 | 8237.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 62670.80 | 02-JAN-04:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.90 |
February | 59721.61 | 25-FEB-04:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 |
March | 58586.27 | 01-MAR-04:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.14 |
April | 60932.08 | 16-APR-03:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.68 |
May | 58621.65 | 12-MAY-03:01 | 0.00 | 10354.33 | 10800.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.73 |
June | 61551.82 | 07-JUN-03:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.29 |
July | 45161.56 | 18-JUL-03:01 | 0.00 | 10354.33 | 10800.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.35 |
August | 62509.58 | 20-AUG-03:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 |
September | 55788.27 | 22-SEP-03:01 | 0.00 | 10354.33 | 10800.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.14 |
October | 67557.77 | 17-OCT-03:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.10 |
November | 57383.61 | 07-NOV-04:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.32 |
December | 53999.69 | 11-DEC-04:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 45161.56 | 0.00 | 10354.33 | 10800.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 | |
Maximum of Months | 67557.77 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 65616.02 | 03-JAN-04:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 124.46 |
February | 63188.44 | 12-FEB-04:11 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 257.75 |
March | 62438.01 | 20-MAR-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 256.50 |
April | 62004.38 | 11-APR-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 29.01 |
May | 33173.25 | 17-MAY-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 |
June | 38054.03 | 07-JUN-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 124.04 |
July | 25772.54 | 18-JUL-03:01 | 0.00 | 2144.49 | 31167.18 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 42.71 |
August | 37257.41 | 20-AUG-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 25.93 |
September | 32189.03 | 22-SEP-03:01 | 0.00 | 2144.49 | 31167.18 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 47.92 |
October | 61062.79 | 27-OCT-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 206.31 |
November | 68286.98 | 09-NOV-04:11 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 312.94 |
December | 60603.41 | 29-DEC-04:11 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 421.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25772.54 | 0.00 | 2144.49 | 31167.18 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | |
Maximum of Months | 68286.98 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 421.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.05 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.46 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.83 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.42 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.69 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.30 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.79 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1135.10 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.92 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.66 | 0.00 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1135.10 | 218.05 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.981994E+11 | 72265.87 | 19-JAN-11:00 | 0.733016E+11 | 46608.55 | 22-JAN-11:09 |
February | 0.927316E+11 | 71684.67 | 24-FEB-12:00 | 0.660682E+11 | 46529.62 | 05-FEB-11:00 |
March | 0.104488E+12 | 73967.59 | 28-MAR-11:00 | 0.725316E+11 | 45687.73 | 04-MAR-11:00 |
April | 0.112886E+12 | 80982.67 | 28-APR-16:10 | 0.685916E+11 | 45511.11 | 01-APR-10:50 |
May | 0.143481E+12 | 83905.59 | 24-MAY-11:00 | 0.694552E+11 | 44480.03 | 07-MAY-10:39 |
June | 0.143761E+12 | 86596.68 | 29-JUN-11:00 | 0.661633E+11 | 43560.60 | 03-JUN-10:30 |
July | 0.154741E+12 | 89114.09 | 20-JUL-11:00 | 0.674646E+11 | 42694.99 | 02-JUL-10:39 |
August | 0.152036E+12 | 87333.13 | 10-AUG-11:00 | 0.679913E+11 | 43231.08 | 27-AUG-10:50 |
September | 0.142124E+12 | 91855.14 | 09-SEP-18:40 | 0.664833E+11 | 43647.03 | 30-SEP-10:30 |
October | 0.135137E+12 | 89748.08 | 06-OCT-11:09 | 0.699851E+11 | 44615.90 | 29-OCT-10:00 |
November | 0.107744E+12 | 80863.97 | 07-NOV-12:00 | 0.691853E+11 | 45584.55 | 25-NOV-11:00 |
December | 0.103772E+12 | 85484.39 | 21-DEC-04:30 | 0.726671E+11 | 46302.35 | 30-DEC-11:00 |
Annual Sum or Average | 0.149110E+13 | 0.829888E+12 | ||||
Minimum of Months | 0.927316E+11 | 71684.67 | 0.660682E+11 | 42694.99 | ||
Maximum of Months | 0.154741E+12 | 91855.14 | 0.733016E+11 | 46608.55 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.142337E+11 | 0.691167E+10 | 0.386947E+11 | 0.00 | 0.227642E+11 | 37879553.69 | 0.192438E+10 | 0.104879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128921E+11 | 0.596942E+10 | 0.349501E+11 | 0.00 | 0.206235E+11 | 34213790.43 | 0.159912E+10 | 0.137787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144603E+11 | 0.619743E+10 | 0.386950E+11 | 0.00 | 0.228198E+11 | 37879553.69 | 0.707946E+09 | 0.183530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138304E+11 | 0.559857E+10 | 0.374466E+11 | 0.00 | 0.221872E+11 | 36657632.61 | 3688974.96 | 0.306046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143470E+11 | 0.542550E+10 | 0.386949E+11 | 0.00 | 0.232824E+11 | 37879553.69 | 0.00 | 0.583793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139770E+11 | 0.505464E+10 | 0.374467E+11 | 0.00 | 0.226354E+11 | 36657632.61 | 0.00 | 0.613960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142020E+11 | 0.532660E+10 | 0.386947E+11 | 0.00 | 0.235348E+11 | 37879553.69 | 0.00 | 0.696173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144603E+11 | 0.561779E+10 | 0.386950E+11 | 0.00 | 0.234510E+11 | 37879553.69 | 0.00 | 0.664465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138337E+11 | 0.582932E+10 | 0.374466E+11 | 0.00 | 0.226315E+11 | 36657632.61 | 0.00 | 0.591308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142320E+11 | 0.644192E+10 | 0.386947E+11 | 0.00 | 0.231896E+11 | 37879553.69 | 1297749.02 | 0.492361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137787E+11 | 0.658202E+10 | 0.374465E+11 | 0.00 | 0.221560E+11 | 36657632.61 | 60280876.46 | 0.245380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142037E+11 | 0.700233E+10 | 0.386947E+11 | 0.00 | 0.228394E+11 | 37879553.69 | 0.123674E+10 | 0.165709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168451E+12 | 0.719572E+11 | 0.455600E+12 | 0.00 | 0.272115E+12 | 0.446001E+09 | 0.553345E+10 | 0.478539E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128921E+11 | 0.505464E+10 | 0.349501E+11 | 0.00 | 0.206235E+11 | 34213790.43 | 0.00 | 0.104879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144603E+11 | 0.700233E+10 | 0.386950E+11 | 0.00 | 0.235348E+11 | 37879553.69 | 0.192438E+10 | 0.696173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.334019E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.300297E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.326319E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.299790E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.295555E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.275507E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.275649E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.280916E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.278707E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.300854E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.305727E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.327674E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.00 | 0.00 | 0.360102E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.275507E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.334019E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8332.55 | 02-JAN-10:09 | 4578.48 | 01-JAN-00:10 | 24529.26 | 01-JAN-11:09 | 0.00 | 10164.86 | 01-JAN-08:39 | 17.86 | 01-JAN-00:10 | 22868.42 | 05-JAN-06:10 |
February | 8332.55 | 01-FEB-10:09 | 4578.48 | 01-FEB-00:10 | 24529.26 | 01-FEB-11:09 | 0.00 | 10164.86 | 01-FEB-08:00 | 17.86 | 12-FEB-11:09 | 45667.42 | 05-FEB-04:19 |
March | 8332.55 | 01-MAR-10:09 | 4578.48 | 01-MAR-00:10 | 24529.26 | 01-MAR-11:09 | 0.00 | 10164.86 | 01-MAR-11:39 | 17.86 | 01-MAR-00:10 | 13517.50 | 09-MAR-06:10 |
April | 8332.55 | 01-APR-16:10 | 4578.48 | 01-APR-00:10 | 24529.26 | 01-APR-10:09 | 0.00 | 10164.86 | 01-APR-04:10 | 17.86 | 14-APR-10:30 | 1787.23 | 11-APR-05:00 |
May | 8332.55 | 01-MAY-09:09 | 4578.48 | 01-MAY-00:10 | 24529.26 | 01-MAY-10:09 | 0.00 | 10164.86 | 01-MAY-04:10 | 17.86 | 12-MAY-10:30 | 0.00 | 01-MAY-00:10 |
June | 8332.55 | 01-JUN-09:09 | 4578.48 | 01-JUN-00:10 | 24529.26 | 01-JUN-10:09 | 0.00 | 10164.86 | 01-JUN-04:19 | 17.86 | 01-JUN-14:09 | 0.00 | 01-JUN-00:10 |
July | 8332.55 | 01-JUL-16:10 | 4578.48 | 01-JUL-00:10 | 24529.26 | 01-JUL-10:09 | 0.00 | 10164.86 | 01-JUL-04:19 | 17.86 | 03-JUL-13:09 | 0.00 | 01-JUL-00:10 |
August | 8332.55 | 01-AUG-09:09 | 4578.48 | 01-AUG-00:10 | 24529.26 | 01-AUG-10:09 | 0.00 | 10164.86 | 01-AUG-04:19 | 17.86 | 05-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 8332.55 | 01-SEP-09:09 | 4578.48 | 01-SEP-00:10 | 24529.26 | 01-SEP-10:09 | 0.00 | 10164.86 | 01-SEP-04:40 | 17.86 | 18-SEP-12:39 | 0.00 | 01-SEP-00:10 |
October | 8332.55 | 02-OCT-09:09 | 4578.48 | 01-OCT-00:10 | 24529.26 | 01-OCT-10:09 | 0.00 | 10164.86 | 01-OCT-04:00 | 17.86 | 01-OCT-05:10 | 525.92 | 28-OCT-05:00 |
November | 8332.55 | 01-NOV-09:09 | 4578.48 | 01-NOV-00:10 | 24529.26 | 01-NOV-10:09 | 0.00 | 10164.86 | 01-NOV-04:10 | 17.86 | 01-NOV-05:10 | 2215.44 | 15-NOV-06:49 |
December | 8332.55 | 01-DEC-10:09 | 4578.48 | 01-DEC-00:10 | 24529.26 | 01-DEC-11:09 | 0.00 | 10164.86 | 01-DEC-10:09 | 17.86 | 01-DEC-00:10 | 66023.01 | 21-DEC-04:30 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 8332.55 | 4578.48 | 24529.26 | 0.00 | 10164.86 | 17.86 | 0.00 | ||||||
Maximum of Months | 8332.55 | 4578.48 | 24529.26 | 0.00 | 10164.86 | 17.86 | 66023.01 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 28946.33 | 19-JAN-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29060.45 | 24-FEB-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31340.08 | 28-MAR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39167.70 | 28-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42258.33 | 24-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44052.80 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 46869.18 | 22-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45231.71 | 24-AUG-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48868.33 | 09-SEP-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46934.20 | 06-OCT-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38237.09 | 07-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34701.38 | 14-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 28946.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48868.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 72265.87 | 19-JAN-11:00 | 8332.55 | 24529.26 | 0.00 | 0.00 | 10164.86 | 17.86 | 0.00 | 27508.27 | 0.00 |
February | 71684.67 | 24-FEB-12:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 10164.86 | 17.86 | 0.00 | 29060.45 | 0.00 |
March | 73967.59 | 28-MAR-11:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 10164.86 | 17.86 | 0.00 | 31340.08 | 0.00 |
April | 80982.67 | 28-APR-16:10 | 8332.55 | 22118.27 | 0.00 | 0.00 | 10164.86 | 17.86 | 0.00 | 39167.70 | 0.00 |
May | 83905.59 | 24-MAY-11:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 10164.86 | 17.86 | 0.00 | 41265.15 | 0.00 |
June | 86596.68 | 29-JUN-11:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 10164.86 | 17.86 | 0.00 | 43951.87 | 0.00 |
July | 89114.09 | 20-JUL-11:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 10164.86 | 17.86 | 0.00 | 46460.43 | 0.00 |
August | 87333.13 | 10-AUG-11:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 10164.86 | 17.86 | 0.00 | 44685.52 | 0.00 |
September | 91855.14 | 09-SEP-18:40 | 8332.55 | 18903.61 | 4578.48 | 0.00 | 10164.86 | 17.86 | 0.00 | 48516.82 | 0.00 |
October | 89748.08 | 06-OCT-11:09 | 8332.55 | 22921.93 | 0.00 | 0.00 | 10164.86 | 17.86 | 0.00 | 46874.73 | 0.00 |
November | 80863.97 | 07-NOV-12:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 10164.86 | 17.86 | 0.00 | 38237.09 | 0.00 |
December | 85484.39 | 21-DEC-04:30 | 1388.76 | 5223.04 | 4578.48 | 0.00 | 7115.41 | 0.00 | 66023.01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 71684.67 | 1388.76 | 5223.04 | 0.00 | 0.00 | 7115.41 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91855.14 | 8332.55 | 24529.26 | 4578.48 | 0.00 | 10164.86 | 17.86 | 66023.01 | 48516.82 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 23860.52 | 23-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 23839.72 | 06-FEB-07:49 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 23689.93 | 01-MAR-19:40 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 22578.17 | 03-APR-06:19 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 21458.08 | 01-MAY-06:49 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 20383.55 | 01-JUN-18:30 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 20051.50 | 03-JUL-18:40 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 20282.53 | 31-AUG-06:19 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 21172.08 | 28-SEP-06:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 22331.67 | 31-OCT-18:00 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 23060.94 | 30-NOV-07:19 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 23784.29 | 26-DEC-07:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 20051.50 | 0.00 | ||
Maximum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 23860.52 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.70 | 0.00 | 24.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.68 | 0.00 | 24.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.69 | 0.00 | 24.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.83 | 0.00 | 24.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.16 | 0.00 | 25.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 25.24 | 0.00 | 25.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.33 | 0.00 | 25.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.38 | 0.00 | 25.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.29 | 0.00 | 25.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.16 | 0.00 | 25.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.92 | 0.00 | 24.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.89 | 0.00 | 24.89 |
Annual Sum or Average | 0.00 | 0.00 | 41.17 | 25.15 | 0.00 | 25.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.68 | 0.00 | 24.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.38 | 0.00 | 25.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 29.29 | 0.00 | 29.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 29.89 | 0.00 | 29.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 29.91 | 0.00 | 29.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 30.43 | 0.00 | 30.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 30.32 | 3.33 | 29.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 62.67 | 28.48 | 37.67 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 152.83 | 27.77 | 125.00 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 107.17 | 28.00 | 79.83 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 71.67 | 28.57 | 45.67 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 75.17 | 28.39 | 48.67 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 30.28 | 0.00 | 30.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 29.88 | 0.00 | 29.88 |
Annual Sum or Average | 0.00 | 0.00 | 584.00 | 28.52 | 340.17 | 28.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.77 | 0.00 | 27.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 152.83 | 30.43 | 125.00 | 30.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 318.17 | 22.05 | 319.17 | 22.95 | 84.00 | 23.02 |
February | 231.33 | 22.37 | 368.00 | 23.30 | 89.67 | 23.34 |
March | 245.83 | 22.69 | 414.50 | 23.51 | 98.33 | 23.58 |
April | 163.50 | 23.92 | 547.83 | 24.03 | 136.83 | 24.06 |
May | 392.33 | 24.26 | 611.00 | 24.21 | 392.33 | 24.22 |
June | 393.00 | 24.27 | 592.00 | 24.22 | 393.00 | 24.24 |
July | 549.83 | 24.23 | 609.00 | 24.21 | 549.83 | 24.22 |
August | 470.67 | 24.25 | 612.00 | 24.22 | 470.67 | 24.23 |
September | 503.00 | 24.20 | 590.00 | 24.18 | 503.00 | 24.19 |
October | 285.00 | 24.20 | 585.17 | 24.16 | 274.50 | 24.18 |
November | 181.50 | 23.32 | 484.33 | 23.85 | 110.33 | 23.89 |
December | 305.50 | 22.48 | 369.67 | 23.29 | 112.00 | 23.38 |
Annual Sum or Average | 4039.67 | 23.68 | 6102.67 | 23.93 | 3214.50 | 23.99 |
Minimum of Months | 163.50 | 22.05 | 319.17 | 22.95 | 84.00 | 23.02 |
Maximum of Months | 549.83 | 24.27 | 612.00 | 24.22 | 549.83 | 24.24 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 448.83 | 23.57 | 408.17 | 24.34 | 277.50 | 24.68 |
February | 445.50 | 24.48 | 440.33 | 24.92 | 350.50 | 25.12 |
March | 468.00 | 24.92 | 503.33 | 25.27 | 383.17 | 25.46 |
April | 534.83 | 25.96 | 579.00 | 25.90 | 532.00 | 25.93 |
May | 611.00 | 26.01 | 611.00 | 26.01 | 611.00 | 26.01 |
June | 592.00 | 26.09 | 592.00 | 26.09 | 592.00 | 26.09 |
July | 609.00 | 26.27 | 609.00 | 26.27 | 609.00 | 26.27 |
August | 612.00 | 26.17 | 612.00 | 26.17 | 612.00 | 26.17 |
September | 590.00 | 26.12 | 590.00 | 26.12 | 590.00 | 26.12 |
October | 582.67 | 26.08 | 605.50 | 26.06 | 579.50 | 26.08 |
November | 493.50 | 25.62 | 543.50 | 25.67 | 459.33 | 25.76 |
December | 458.00 | 24.46 | 470.33 | 24.90 | 345.50 | 25.16 |
Annual Sum or Average | 6445.33 | 25.58 | 6564.17 | 25.72 | 5941.50 | 25.81 |
Minimum of Months | 445.50 | 23.57 | 408.17 | 24.34 | 277.50 | 24.68 |
Maximum of Months | 612.00 | 26.27 | 612.00 | 26.27 | 612.00 | 26.27 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.94114 | 46.96358 | 0.28733 | 10.24706 |
February | 551.00000 | 23.28670 | 50.01011 | 0.40418 | 11.92179 |
March | 612.00000 | 23.45167 | 49.40842 | 0.44341 | 11.88684 |
April | 590.00000 | 23.98123 | 56.43786 | 0.66625 | 15.08537 |
May | 611.00000 | 24.17049 | 65.51903 | 0.04968 | 5.66686 |
June | 592.00000 | 24.18411 | 65.71145 | 0.08127 | 5.87219 |
July | 609.00000 | 24.20373 | 68.78019 | 0.11490 | 6.14280 |
August | 612.00000 | 24.19101 | 67.46434 | 0.11018 | 6.04512 |
September | 590.00000 | 24.16719 | 67.71953 | 0.08180 | 5.83246 |
October | 610.00000 | 24.09869 | 60.51939 | 0.78017 | 18.57320 |
November | 591.00000 | 23.77025 | 51.74691 | 0.57890 | 13.60698 |
December | 609.00000 | 23.20341 | 49.62760 | 0.39023 | 11.53482 |
Annual Sum or Average | 7187.00000 | 23.80611 | 58.37279 | 0.33147 | 10.18663 |
Minimum of Months | 551.00000 | 22.94114 | 46.96358 | 0.04968 | 5.66686 |
Maximum of Months | 612.00000 | 24.20373 | 68.78019 | 0.78017 | 18.57320 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.61417 | 48.16769 | 0.65455 | 22.83070 |
February | 551.00000 | 24.39037 | 50.25282 | 0.85863 | 28.52955 |
March | 612.00000 | 24.73634 | 49.12847 | 0.93741 | 29.50392 |
April | 590.00000 | 25.78560 | 54.88506 | 1.25947 | 39.15349 |
May | 611.00000 | 26.01285 | 63.29275 | 0.87149 | 21.43639 |
June | 592.00000 | 26.08685 | 63.70813 | 0.92187 | 23.58135 |
July | 609.00000 | 26.27078 | 65.96464 | 1.01092 | 27.54588 |
August | 612.00000 | 26.16838 | 64.82795 | 0.97663 | 25.89006 |
September | 590.00000 | 26.11936 | 64.43271 | 0.93887 | 24.32413 |
October | 610.00000 | 26.01260 | 58.11250 | 1.38323 | 45.16906 |
November | 591.00000 | 25.35757 | 50.51171 | 1.12450 | 34.46264 |
December | 609.00000 | 24.24853 | 49.68031 | 0.83353 | 27.14840 |
Annual Sum or Average | 7187.00000 | 25.40405 | 56.95371 | 0.98103 | 29.12016 |
Minimum of Months | 551.00000 | 23.61417 | 48.16769 | 0.65455 | 21.43639 |
Maximum of Months | 612.00000 | 26.27078 | 65.96464 | 1.38323 | 45.16906 |
Report: DXReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.227098E+11 | 0.718994E+10 | 310.01 | 0.150458E+11 | 0.766399E+10 | 0.00 | 1.00 | 01-JAN-04:01 | 0.00 | 01-JAN-00:10 | 117174.81 | 20-JAN-04:01 | 63022.61 | 02-JAN-04:01 | 64916.05 | 20-JAN-04:01 | 32370.82 | 20-JAN-04:01 | 0.00 |
February | 0.301636E+11 | 0.944511E+10 | 351.86 | 0.195630E+11 | 0.106005E+11 | 0.00 | 1.00 | 01-FEB-04:02 | 0.00 | 01-FEB-00:05 | 117231.36 | 03-FEB-04:01 | 58927.99 | 28-FEB-04:01 | 62143.97 | 03-FEB-04:01 | 32375.66 | 03-FEB-04:01 | 0.00 |
March | 0.397597E+11 | 0.123003E+11 | 419.86 | 0.267573E+11 | 0.130024E+11 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-00:05 | 118505.73 | 07-MAR-04:01 | 60950.92 | 06-MAR-04:01 | 63077.76 | 07-MAR-04:01 | 32486.38 | 07-MAR-04:01 | 0.00 |
April | 0.662684E+11 | 0.200295E+11 | 548.39 | 0.433746E+11 | 0.228938E+11 | 0.00 | 1.00 | 01-APR-03:02 | 0.00 | 01-APR-00:01 | 119396.55 | 29-APR-03:01 | 64247.03 | 22-APR-03:01 | 68345.70 | 29-APR-03:01 | 32565.97 | 28-APR-03:01 | 0.00 |
May | 0.127874E+12 | 0.365620E+11 | 612.96 | 0.743486E+11 | 0.535255E+11 | 0.00 | 1.00 | 01-MAY-03:02 | 0.00 | 01-MAY-00:01 | 119396.55 | 20-MAY-03:02 | 67270.40 | 12-MAY-03:01 | 72671.38 | 24-MAY-03:02 | 32565.97 | 02-MAY-03:01 | 0.00 |
June | 0.134817E+12 | 0.384158E+11 | 593.61 | 0.771892E+11 | 0.576280E+11 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 119396.55 | 05-JUN-03:01 | 68341.53 | 10-JUN-03:01 | 73347.88 | 30-JUN-03:02 | 32565.97 | 02-JUN-03:01 | 0.00 |
July | 0.153421E+12 | 0.432934E+11 | 613.70 | 0.810056E+11 | 0.724156E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 119396.55 | 21-JUL-03:03 | 62731.33 | 18-JUL-13:00 | 74929.76 | 24-JUL-03:03 | 32770.06 | 22-JUL-17:10 | 0.00 |
August | 0.146354E+12 | 0.414940E+11 | 613.57 | 0.798039E+11 | 0.665503E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 119396.55 | 07-AUG-03:03 | 70734.17 | 20-AUG-03:01 | 74365.16 | 06-AUG-03:03 | 32565.97 | 01-AUG-03:01 | 0.00 |
September | 0.130361E+12 | 0.368942E+11 | 594.36 | 0.697463E+11 | 0.606148E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 119396.55 | 06-SEP-03:02 | 65777.31 | 09-SEP-18:03 | 74219.08 | 05-SEP-03:02 | 34619.71 | 09-SEP-18:10 | 0.00 |
October | 0.108658E+12 | 0.312768E+11 | 591.20 | 0.631365E+11 | 0.455216E+11 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 119396.55 | 04-OCT-03:01 | 76811.79 | 05-OCT-03:01 | 79395.61 | 07-OCT-03:03 | 33268.65 | 06-OCT-11:13 | 0.00 |
November | 0.531873E+11 | 0.161948E+11 | 483.61 | 0.344458E+11 | 0.187414E+11 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 119396.55 | 08-NOV-04:01 | 62112.97 | 07-NOV-04:01 | 69732.84 | 03-NOV-03:02 | 32565.97 | 01-NOV-03:01 | 0.00 |
December | 0.360233E+11 | 0.110539E+11 | 368.84 | 0.230160E+11 | 0.130073E+11 | 0.00 | 1.00 | 08-DEC-13:50 | 0.00 | 01-DEC-00:05 | 119396.55 | 17-DEC-04:01 | 58622.62 | 11-DEC-04:01 | 68329.49 | 17-DEC-04:01 | 32565.97 | 17-DEC-04:01 | 0.00 |
Annual Sum or Average | 0.104960E+13 | 0.304150E+12 | 6101.97 | 0.607433E+12 | 0.442165E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.227098E+11 | 0.718994E+10 | 310.01 | 0.150458E+11 | 0.766399E+10 | 0.00 | 1.00 | 0.00 | 117174.81 | 58622.62 | 62143.97 | 32370.82 | 0.00 | ||||||
Maximum of Months | 0.153421E+12 | 0.432934E+11 | 613.70 | 0.810056E+11 | 0.724156E+11 | 0.00 | 1.00 | 0.00 | 119396.55 | 76811.79 | 79395.61 | 34619.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.113550E+11 | 0.329797E+10 | 264.16 | 0.682422E+10 | 0.453075E+10 | 0.00 | 1.00 | 01-JAN-04:01 | 0.00 | 01-JAN-00:10 | 47062.25 | 19-JAN-04:01 | 24640.48 | 01-JAN-04:01 | 30033.01 | 19-JAN-04:01 | 12960.79 | 19-JAN-04:01 | 0.00 |
February | 0.150034E+11 | 0.433359E+10 | 317.16 | 0.893944E+10 | 0.606394E+10 | 0.00 | 1.00 | 01-FEB-04:11 | 0.00 | 01-FEB-00:05 | 47169.98 | 03-FEB-04:11 | 37725.78 | 12-FEB-04:11 | 29636.47 | 03-FEB-04:52 | 12969.27 | 03-FEB-04:11 | 0.00 |
March | 0.211444E+11 | 0.605268E+10 | 406.07 | 0.132196E+11 | 0.792480E+10 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-00:05 | 48737.24 | 07-MAR-04:52 | 34104.19 | 04-MAR-04:01 | 30769.40 | 07-MAR-04:52 | 13094.51 | 07-MAR-04:52 | 0.00 |
April | 0.375276E+11 | 0.105751E+11 | 582.17 | 0.230767E+11 | 0.144509E+11 | 0.00 | 1.00 | 01-APR-03:11 | 0.00 | 01-APR-00:01 | 49942.21 | 29-APR-03:01 | 32246.08 | 10-APR-03:01 | 31073.54 | 29-APR-03:01 | 13765.94 | 28-APR-15:43 | 0.00 |
May | 0.807781E+11 | 0.218173E+11 | 706.33 | 0.442623E+11 | 0.365159E+11 | 0.00 | 1.00 | 01-MAY-03:11 | 0.00 | 01-MAY-00:01 | 49942.21 | 23-MAY-15:27 | 31959.89 | 28-MAY-15:53 | 32490.40 | 16-MAY-03:01 | 13880.63 | 28-MAY-16:13 | 0.00 |
June | 0.849158E+11 | 0.229802E+11 | 685.27 | 0.458125E+11 | 0.391033E+11 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 49942.21 | 19-JUN-16:20 | 33598.40 | 14-JUN-14:00 | 33414.90 | 30-JUN-03:01 | 14181.76 | 29-JUN-13:53 | 0.00 |
July | 0.975773E+11 | 0.263239E+11 | 708.47 | 0.477097E+11 | 0.498676E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 49942.21 | 01-JUL-18:10 | 34629.91 | 07-JUL-15:03 | 33763.18 | 15-JUL-03:01 | 14572.93 | 21-JUL-15:53 | 0.00 |
August | 0.924148E+11 | 0.249525E+11 | 708.23 | 0.468477E+11 | 0.455671E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 49942.21 | 08-AUG-16:15 | 36411.79 | 30-AUG-15:55 | 35149.89 | 19-AUG-03:01 | 14430.80 | 03-AUG-15:53 | 0.00 |
September | 0.827630E+11 | 0.222366E+11 | 685.66 | 0.405920E+11 | 0.421710E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 49942.21 | 18-SEP-09:28 | 31460.03 | 09-SEP-16:53 | 34512.75 | 02-SEP-03:01 | 14645.61 | 09-SEP-16:53 | 0.00 |
October | 0.659637E+11 | 0.179593E+11 | 662.60 | 0.352540E+11 | 0.307097E+11 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 49942.21 | 22-OCT-10:40 | 36256.60 | 27-OCT-03:01 | 36488.51 | 07-OCT-03:45 | 13887.32 | 07-OCT-13:00 | 0.00 |
November | 0.294432E+11 | 0.834322E+10 | 489.29 | 0.173913E+11 | 0.120519E+11 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 49942.21 | 02-NOV-10:53 | 36420.43 | 09-NOV-04:11 | 33632.33 | 01-NOV-03:01 | 13196.28 | 01-NOV-03:01 | 0.00 |
December | 0.193832E+11 | 0.551702E+10 | 360.89 | 0.111955E+11 | 0.818773E+10 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-00:05 | 48863.38 | 15-DEC-04:42 | 29055.51 | 07-DEC-04:01 | 32345.53 | 15-DEC-04:42 | 13104.86 | 15-DEC-04:42 | 0.00 |
Annual Sum or Average | 0.638270E+12 | 0.174389E+12 | 6576.29 | 0.341125E+12 | 0.297145E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.113550E+11 | 0.329797E+10 | 264.16 | 0.682422E+10 | 0.453075E+10 | 0.00 | 1.00 | 0.00 | 47062.25 | 24640.48 | 29636.47 | 12960.79 | 0.00 | ||||||
Maximum of Months | 0.975773E+11 | 0.263239E+11 | 708.47 | 0.477097E+11 | 0.498676E+11 | 0.00 | 1.00 | 0.00 | 49942.21 | 37725.78 | 36488.51 | 14645.61 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 174.73 | 89.10 | 85.63 | 280.58 | 684.81 | 4.33 | 0.00 | 0.00 |
February | 195.07 | 94.40 | 100.67 | 338.33 | 591.15 | 5.33 | 0.00 | 0.00 |
March | 227.78 | 109.23 | 118.55 | 454.19 | 508.04 | 8.67 | 0.00 | 0.00 |
April | 250.46 | 112.79 | 137.67 | 610.61 | 313.04 | 0.00 | 0.00 | 0.00 |
May | 257.55 | 111.12 | 146.43 | 847.56 | 105.36 | 0.00 | 0.00 | 0.00 |
June | 261.51 | 103.34 | 158.17 | 909.74 | 95.65 | 0.00 | 0.00 | 0.00 |
July | 252.34 | 92.04 | 160.30 | 873.23 | 72.49 | 0.00 | 0.00 | 0.00 |
August | 232.68 | 79.76 | 152.92 | 787.15 | 94.89 | 0.00 | 0.00 | 0.00 |
September | 205.67 | 70.31 | 135.36 | 653.67 | 131.78 | 0.00 | 0.00 | 0.00 |
October | 204.01 | 86.11 | 117.91 | 588.21 | 212.33 | 0.00 | 0.00 | 0.00 |
November | 180.89 | 92.38 | 88.52 | 367.16 | 441.54 | 0.00 | 0.00 | 0.00 |
December | 143.56 | 65.83 | 77.73 | 241.94 | 607.40 | 3.00 | 0.00 | 0.00 |
Annual Sum or Average | 215.59 | 92.16 | 123.43 | 580.73 | 320.16 | 21.33 | 0.00 | 0.00 |
Minimum of Months | 143.56 | 65.83 | 77.73 | 241.94 | 72.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 261.51 | 112.79 | 160.30 | 909.74 | 684.81 | 8.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 535.16 | 379.49 | 155.68 | 1173.59 | 876.35 | 4.33 | 0.00 | 0.00 |
February | 490.76 | 317.09 | 173.68 | 1089.54 | 771.67 | 5.33 | 0.00 | 0.00 |
March | 332.34 | 159.94 | 172.40 | 736.06 | 721.05 | 9.50 | 0.00 | 0.00 |
April | 248.07 | 69.69 | 178.38 | 622.53 | 463.46 | 0.00 | 0.00 | 0.00 |
May | 184.21 | 13.75 | 170.47 | 655.28 | 151.04 | 0.00 | 0.00 | 0.00 |
June | 177.07 | 2.92 | 174.14 | 677.74 | 137.71 | 0.00 | 0.00 | 0.00 |
July | 185.91 | 5.25 | 180.66 | 693.28 | 102.88 | 0.00 | 0.00 | 0.00 |
August | 220.63 | 30.05 | 190.58 | 816.91 | 138.09 | 0.00 | 0.00 | 0.00 |
September | 271.76 | 80.45 | 191.32 | 898.30 | 186.60 | 0.00 | 0.00 | 0.00 |
October | 406.14 | 213.04 | 193.10 | 1224.15 | 299.68 | 0.00 | 0.00 | 0.00 |
November | 512.09 | 352.29 | 159.80 | 1278.65 | 591.99 | 0.00 | 0.00 | 0.00 |
December | 520.59 | 371.15 | 149.44 | 1229.64 | 792.16 | 3.00 | 0.00 | 0.00 |
Annual Sum or Average | 339.58 | 165.46 | 174.12 | 923.89 | 434.30 | 22.17 | 0.00 | 0.00 |
Minimum of Months | 177.07 | 2.92 | 149.44 | 622.53 | 102.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 535.16 | 379.49 | 193.10 | 1278.65 | 876.35 | 9.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 186.07 | 100.79 | 85.28 | 329.69 | 699.12 | 4.67 | 0.00 | 0.00 |
February | 210.82 | 106.93 | 103.89 | 402.56 | 603.99 | 5.50 | 0.00 | 0.00 |
March | 206.18 | 90.71 | 115.46 | 415.34 | 529.66 | 9.50 | 0.00 | 0.00 |
April | 255.68 | 116.84 | 138.84 | 648.97 | 324.64 | 0.00 | 0.00 | 0.00 |
May | 214.13 | 69.80 | 144.33 | 724.90 | 108.70 | 0.00 | 0.00 | 0.00 |
June | 237.54 | 83.27 | 154.28 | 838.13 | 98.00 | 0.00 | 0.00 | 0.00 |
July | 216.96 | 60.23 | 156.73 | 760.24 | 72.64 | 0.00 | 0.00 | 0.00 |
August | 218.77 | 66.40 | 152.37 | 763.19 | 98.75 | 0.00 | 0.00 | 0.00 |
September | 201.68 | 68.94 | 132.74 | 646.26 | 133.92 | 0.00 | 0.00 | 0.00 |
October | 207.03 | 89.52 | 117.51 | 613.74 | 222.88 | 0.00 | 0.00 | 0.00 |
November | 177.82 | 89.63 | 88.19 | 394.04 | 469.52 | 0.00 | 0.00 | 0.00 |
December | 170.67 | 90.85 | 79.82 | 339.31 | 618.91 | 3.00 | 0.00 | 0.00 |
Annual Sum or Average | 208.49 | 85.95 | 122.54 | 573.79 | 330.31 | 22.67 | 0.00 | 0.00 |
Minimum of Months | 170.67 | 60.23 | 79.82 | 329.69 | 72.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 255.68 | 116.84 | 156.73 | 838.13 | 699.12 | 9.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.468003E+09 | 0.238649E+09 | 0.229354E+09 | 0.751518E+09 | 0.183419E+10 |
February | 0.471914E+09 | 0.228363E+09 | 0.243552E+09 | 0.818480E+09 | 0.143011E+10 |
March | 0.610091E+09 | 0.292571E+09 | 0.317521E+09 | 0.121650E+10 | 0.136075E+10 |
April | 0.649184E+09 | 0.292344E+09 | 0.356840E+09 | 0.158269E+10 | 0.811388E+09 |
May | 0.689825E+09 | 0.297628E+09 | 0.392197E+09 | 0.227010E+10 | 0.282190E+09 |
June | 0.677836E+09 | 0.267863E+09 | 0.409974E+09 | 0.235804E+10 | 0.247915E+09 |
July | 0.675862E+09 | 0.246524E+09 | 0.429338E+09 | 0.233887E+10 | 0.194168E+09 |
August | 0.623199E+09 | 0.213620E+09 | 0.409579E+09 | 0.210831E+10 | 0.254145E+09 |
September | 0.533105E+09 | 0.182253E+09 | 0.350852E+09 | 0.169432E+10 | 0.341583E+09 |
October | 0.546430E+09 | 0.230626E+09 | 0.315804E+09 | 0.157546E+10 | 0.568695E+09 |
November | 0.468874E+09 | 0.239439E+09 | 0.229434E+09 | 0.951681E+09 | 0.114447E+10 |
December | 0.384513E+09 | 0.176332E+09 | 0.208181E+09 | 0.648025E+09 | 0.162686E+10 |
Annual Sum or Average | 0.679884E+10 | 0.290621E+10 | 0.389262E+10 | 0.183140E+11 | 0.100965E+11 |
Minimum of Months | 0.384513E+09 | 0.176332E+09 | 0.208181E+09 | 0.648025E+09 | 0.194168E+09 |
Maximum of Months | 0.689825E+09 | 0.297628E+09 | 0.429338E+09 | 0.235804E+10 | 0.183419E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143337E+10 | 0.101641E+10 | 0.416961E+09 | 0.314334E+10 | 0.234720E+10 |
February | 0.118726E+10 | 0.767102E+09 | 0.420155E+09 | 0.263582E+10 | 0.186682E+10 |
March | 0.890138E+09 | 0.428381E+09 | 0.461757E+09 | 0.197146E+10 | 0.193126E+10 |
April | 0.642987E+09 | 0.180634E+09 | 0.462353E+09 | 0.161360E+10 | 0.120128E+10 |
May | 0.493399E+09 | 36814829.22 | 0.456585E+09 | 0.175510E+10 | 0.404539E+09 |
June | 0.458953E+09 | 7575362.70 | 0.451378E+09 | 0.175670E+10 | 0.356932E+09 |
July | 0.497951E+09 | 14065222.27 | 0.483885E+09 | 0.185689E+10 | 0.275546E+09 |
August | 0.590937E+09 | 80487675.99 | 0.510449E+09 | 0.218802E+10 | 0.369851E+09 |
September | 0.704406E+09 | 0.208514E+09 | 0.495892E+09 | 0.232840E+10 | 0.483678E+09 |
October | 0.108781E+10 | 0.570602E+09 | 0.517212E+09 | 0.327875E+10 | 0.802674E+09 |
November | 0.132734E+10 | 0.913148E+09 | 0.414192E+09 | 0.331425E+10 | 0.153443E+10 |
December | 0.139435E+10 | 0.994085E+09 | 0.400265E+09 | 0.329348E+10 | 0.212173E+10 |
Annual Sum or Average | 0.107089E+11 | 0.521782E+10 | 0.549109E+10 | 0.291358E+11 | 0.136959E+11 |
Minimum of Months | 0.458953E+09 | 7575362.70 | 0.400265E+09 | 0.161360E+10 | 0.275546E+09 |
Maximum of Months | 0.143337E+10 | 0.101641E+10 | 0.517212E+09 | 0.331425E+10 | 0.234720E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.498381E+09 | 0.269960E+09 | 0.228421E+09 | 0.883042E+09 | 0.187252E+10 |
February | 0.510013E+09 | 0.258679E+09 | 0.251335E+09 | 0.973873E+09 | 0.146117E+10 |
March | 0.552221E+09 | 0.242961E+09 | 0.309259E+09 | 0.111245E+10 | 0.141865E+10 |
April | 0.662726E+09 | 0.302860E+09 | 0.359866E+09 | 0.168214E+10 | 0.841463E+09 |
May | 0.573524E+09 | 0.186942E+09 | 0.386582E+09 | 0.194158E+10 | 0.291147E+09 |
June | 0.615715E+09 | 0.215823E+09 | 0.399892E+09 | 0.217243E+10 | 0.254017E+09 |
July | 0.581109E+09 | 0.161319E+09 | 0.419790E+09 | 0.203621E+10 | 0.194556E+09 |
August | 0.585949E+09 | 0.177854E+09 | 0.408095E+09 | 0.204414E+10 | 0.264482E+09 |
September | 0.522759E+09 | 0.178687E+09 | 0.344072E+09 | 0.167511E+10 | 0.347115E+09 |
October | 0.554510E+09 | 0.239772E+09 | 0.314737E+09 | 0.164384E+10 | 0.596949E+09 |
November | 0.460909E+09 | 0.232323E+09 | 0.228586E+09 | 0.102135E+10 | 0.121700E+10 |
December | 0.457131E+09 | 0.243343E+09 | 0.213788E+09 | 0.908799E+09 | 0.165769E+10 |
Annual Sum or Average | 0.657495E+10 | 0.271052E+10 | 0.386442E+10 | 0.180950E+11 | 0.104168E+11 |
Minimum of Months | 0.457131E+09 | 0.161319E+09 | 0.213788E+09 | 0.883042E+09 | 0.194556E+09 |
Maximum of Months | 0.662726E+09 | 0.302860E+09 | 0.419790E+09 | 0.217243E+10 | 0.187252E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1656.40 | 2132.81 | 895.97 | 569.38 | 326.59 | 0.00 | 0.00 |
February | 1733.59 | 1869.97 | 896.65 | 518.41 | 378.24 | 0.00 | 0.00 |
March | 1535.29 | 1688.46 | 766.30 | 359.88 | 406.41 | 0.00 | 0.00 |
April | 1830.60 | 1049.62 | 754.20 | 299.32 | 454.88 | 0.00 | 0.00 |
May | 2219.78 | 357.13 | 655.89 | 194.66 | 461.23 | 0.00 | 0.00 |
June | 2420.46 | 326.20 | 676.12 | 189.53 | 486.59 | 0.00 | 0.00 |
July | 2324.32 | 245.57 | 655.21 | 157.52 | 497.69 | 0.00 | 0.00 |
August | 2360.72 | 325.17 | 672.07 | 176.21 | 495.86 | 0.00 | 0.00 |
September | 2192.07 | 446.14 | 679.12 | 219.70 | 459.42 | 0.00 | 0.00 |
October | 2411.68 | 720.47 | 817.19 | 388.67 | 428.52 | 0.00 | 0.00 |
November | 1972.71 | 1435.91 | 870.80 | 534.30 | 336.50 | 0.00 | 0.00 |
December | 1727.04 | 1934.62 | 834.82 | 527.84 | 306.99 | 0.00 | 0.00 |
Annual Sum or Average | 2033.72 | 1040.07 | 763.66 | 343.56 | 420.10 | 0.00 | 0.00 |
Minimum of Months | 1535.29 | 245.57 | 655.21 | 157.52 | 306.99 | 0.00 | 0.00 |
Maximum of Months | 2420.46 | 2132.81 | 896.65 | 569.38 | 497.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.443650E+10 | 0.571252E+10 | 0.239976E+10 | 0.152502E+10 | 0.874736E+09 | 0.00 | 0.00 |
February | 0.419390E+10 | 0.452384E+10 | 0.216918E+10 | 0.125414E+10 | 0.915041E+09 | 0.00 | 0.00 |
March | 0.411212E+10 | 0.452237E+10 | 0.205245E+10 | 0.963913E+09 | 0.108854E+10 | 0.00 | 0.00 |
April | 0.474492E+10 | 0.272062E+10 | 0.195490E+10 | 0.775838E+09 | 0.117906E+10 | 0.00 | 0.00 |
May | 0.594545E+10 | 0.956548E+09 | 0.175675E+10 | 0.521385E+09 | 0.123536E+10 | 0.00 | 0.00 |
June | 0.627383E+10 | 0.845517E+09 | 0.175250E+10 | 0.491261E+09 | 0.126124E+10 | 0.00 | 0.00 |
July | 0.622545E+10 | 0.657746E+09 | 0.175492E+10 | 0.421908E+09 | 0.133301E+10 | 0.00 | 0.00 |
August | 0.632294E+10 | 0.870948E+09 | 0.180009E+10 | 0.471961E+09 | 0.132812E+10 | 0.00 | 0.00 |
September | 0.568186E+10 | 0.115641E+10 | 0.176027E+10 | 0.569454E+09 | 0.119082E+10 | 0.00 | 0.00 |
October | 0.645944E+10 | 0.192970E+10 | 0.218875E+10 | 0.104100E+10 | 0.114775E+10 | 0.00 | 0.00 |
November | 0.511327E+10 | 0.372188E+10 | 0.225712E+10 | 0.138491E+10 | 0.872213E+09 | 0.00 | 0.00 |
December | 0.462570E+10 | 0.518168E+10 | 0.223599E+10 | 0.141376E+10 | 0.822234E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.641354E+11 | 0.327998E+11 | 0.240827E+11 | 0.108346E+11 | 0.132481E+11 | 0.00 | 0.00 |
Minimum of Months | 0.411212E+10 | 0.657746E+09 | 0.175250E+10 | 0.421908E+09 | 0.822234E+09 | 0.00 | 0.00 |
Maximum of Months | 0.645944E+10 | 0.571252E+10 | 0.239976E+10 | 0.152502E+10 | 0.133301E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.666929E+10 | -0.650583E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163452026.1 | 82.17 | 0.00 | 0.00 |
February | 0.603405E+10 | -0.588831E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145742692.3 | 82.17 | 0.00 | 0.00 |
March | 0.673789E+10 | -0.657757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160313400.3 | 82.17 | 0.00 | 0.00 |
April | 0.646832E+10 | -0.631593E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -152385685.2 | 82.17 | 0.00 | 0.00 |
May | 0.669927E+10 | -0.654241E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156858392.7 | 82.17 | 0.00 | 0.00 |
June | 0.651257E+10 | -0.636095E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151624195.8 | 82.17 | 0.00 | 0.00 |
July | 0.665359E+10 | -0.649739E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156200250.7 | 82.17 | 0.00 | 0.00 |
August | 0.673543E+10 | -0.657898E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156450024.8 | 82.17 | 0.00 | 0.00 |
September | 0.646888E+10 | -0.631734E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151536766.3 | 82.17 | 0.00 | 0.00 |
October | 0.666132E+10 | -0.650443E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156896266.9 | 82.17 | 0.00 | 0.00 |
November | 0.644975E+10 | -0.629624E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -153507296.7 | 82.17 | 0.00 | 0.00 |
December | 0.665901E+10 | -0.649739E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161616660.3 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.787494E+11 | -0.768828E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.186658E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.603405E+10 | -0.657898E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -163452026.1 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.673789E+10 | -0.588831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145742692.3 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.201808E+11 | -0.192555E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -925324737.5 | 60.05 | 0.00 | 0.00 |
February | 0.181052E+11 | -0.172868E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -818458614.5 | 60.05 | 0.00 | 0.00 |
March | 0.194916E+11 | -0.185950E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -896585262.4 | 60.05 | 0.00 | 0.00 |
April | 0.176272E+11 | -0.167848E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -842424853.2 | 60.05 | 0.00 | 0.00 |
May | 0.170537E+11 | -0.161888E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -864949929.3 | 60.05 | 0.00 | 0.00 |
June | 0.156274E+11 | -0.147919E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -835452898.3 | 60.05 | 0.00 | 0.00 |
July | 0.154972E+11 | -0.146383E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -858923493.9 | 60.05 | 0.00 | 0.00 |
August | 0.158385E+11 | -0.149773E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -861210587.8 | 60.05 | 0.00 | 0.00 |
September | 0.159293E+11 | -0.150946E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -834652320.3 | 60.05 | 0.00 | 0.00 |
October | 0.175185E+11 | -0.166532E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -865296504.2 | 60.05 | 0.00 | 0.00 |
November | 0.181239E+11 | -0.172712E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -852695620.9 | 60.05 | 0.00 | 0.00 |
December | 0.196803E+11 | -0.187717E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -908519223.7 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.210673E+12 | -0.200309E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.103645E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.154972E+11 | -0.192555E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -925324737.5 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.201808E+11 | -0.146383E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -818458614.5 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.389851E+10 | 40145.34 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.320598E+10 | 92564.96 | 06-FEB-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168918E+10 | 23049.96 | 09-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10877376.60 | 5239.72 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3869635.12 | 1569.96 | 28-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177127E+09 | 8596.24 | 16-NOV-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250144E+10 | 70254.96 | 21-DEC-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.389851E+10 | 92564.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113133E+10 | 18939.05 | 05-JAN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.995304E+09 | 27536.05 | 05-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.308256E+09 | 16249.94 | 09-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17518.44 | 29.20 | 16-NOV-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.573314E+09 | 20082.94 | 21-DEC-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113133E+10 | 27536.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23797038.14 | 47787.32 | 05-FEB-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51144194.70 | 32766.68 | 21-DEC-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 74941232.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51144194.70 | 47787.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.227098E+11 | 0.150458E+11 | 117174.81 | 20-JAN-04:01 | 52258.76 | 0.00 |
February | 0.00 | 0.00 | 0.301636E+11 | 0.195630E+11 | 117231.36 | 03-FEB-04:01 | 55087.39 | 0.00 |
March | 0.00 | 0.00 | 0.397597E+11 | 0.267573E+11 | 118505.73 | 07-MAR-04:01 | 55427.97 | 0.00 |
April | 0.00 | 0.00 | 0.662684E+11 | 0.433746E+11 | 119396.55 | 29-APR-03:01 | 51050.84 | 0.00 |
May | 0.00 | 0.00 | 0.127874E+12 | 0.743486E+11 | 119396.55 | 20-MAY-03:02 | 49481.61 | 0.00 |
June | 0.00 | 0.00 | 0.134817E+12 | 0.771892E+11 | 119396.55 | 05-JUN-03:01 | 50228.79 | 0.00 |
July | 0.00 | 0.00 | 0.153421E+12 | 0.810056E+11 | 119396.55 | 21-JUL-03:03 | 47016.12 | 0.00 |
August | 0.00 | 0.00 | 0.146354E+12 | 0.798039E+11 | 119396.55 | 07-AUG-03:03 | 50275.41 | 0.00 |
September | 0.00 | 0.00 | 0.130361E+12 | 0.697463E+11 | 119396.55 | 06-SEP-03:02 | 51999.26 | 0.00 |
October | 0.00 | 0.00 | 0.108658E+12 | 0.631365E+11 | 119396.55 | 04-OCT-03:01 | 61185.66 | 0.00 |
November | 0.00 | 0.00 | 0.531873E+11 | 0.344458E+11 | 119396.55 | 08-NOV-04:01 | 52429.36 | 0.00 |
December | 0.00 | 0.00 | 0.360233E+11 | 0.230160E+11 | 119396.55 | 17-DEC-04:01 | 51067.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104960E+13 | 0.607433E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.227098E+11 | 0.150458E+11 | 117174.81 | 47016.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.153421E+12 | 0.810056E+11 | 119396.55 | 61185.66 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.113550E+11 | 0.682422E+10 | 47062.25 | 19-JAN-04:01 | 17029.24 | 0.00 |
February | 0.00 | 0.00 | 0.150034E+11 | 0.893944E+10 | 47169.98 | 03-FEB-04:11 | 17538.65 | 0.00 |
March | 0.00 | 0.00 | 0.211444E+11 | 0.132196E+11 | 48737.24 | 07-MAR-04:52 | 17967.84 | 0.00 |
April | 0.00 | 0.00 | 0.375276E+11 | 0.230767E+11 | 49942.21 | 29-APR-03:01 | 18868.67 | 0.00 |
May | 0.00 | 0.00 | 0.807781E+11 | 0.442623E+11 | 49942.21 | 23-MAY-15:27 | 21891.41 | 0.00 |
June | 0.00 | 0.00 | 0.849158E+11 | 0.458125E+11 | 49942.21 | 19-JUN-16:20 | 23717.41 | 0.00 |
July | 0.00 | 0.00 | 0.975773E+11 | 0.477097E+11 | 49942.21 | 01-JUL-18:10 | 21270.60 | 0.00 |
August | 0.00 | 0.00 | 0.924148E+11 | 0.468477E+11 | 49942.21 | 08-AUG-16:15 | 22271.45 | 0.00 |
September | 0.00 | 0.00 | 0.827630E+11 | 0.405920E+11 | 49942.21 | 18-SEP-09:28 | 21300.53 | 0.00 |
October | 0.00 | 0.00 | 0.659637E+11 | 0.352540E+11 | 49942.21 | 22-OCT-10:40 | 23116.75 | 0.00 |
November | 0.00 | 0.00 | 0.294432E+11 | 0.173913E+11 | 49942.21 | 02-NOV-10:53 | 26384.46 | 0.00 |
December | 0.00 | 0.00 | 0.193832E+11 | 0.111955E+11 | 48863.38 | 15-DEC-04:42 | 16517.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.638270E+12 | 0.341125E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.113550E+11 | 0.682422E+10 | 47062.25 | 16517.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.975773E+11 | 0.477097E+11 | 49942.21 | 26384.46 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7157.87 | 13865.98 | 23-JAN-19:50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7114.39 | 13844.31 | 01-FEB-19:55 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 6911.56 | 13529.30 | 01-MAR-19:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6445.24 | 12773.17 | 03-APR-18:38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6014.44 | 11973.26 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5677.51 | 11149.09 | 01-JUN-06:47 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5436.40 | 10600.59 | 03-JUL-18:17 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5562.78 | 10833.56 | 31-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5794.12 | 11486.35 | 29-SEP-18:33 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6187.60 | 12394.77 | 31-OCT-18:27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6632.67 | 13192.69 | 30-NOV-20:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 6977.49 | 13714.68 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 6321.59 | ||||
Minimum of Months | 0.00 | 0.00 | 5436.40 | 10600.59 | ||
Maximum of Months | 0.00 | 0.00 | 7157.87 | 13865.98 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159014E+11 | 1.11 | 7115.41 | 01-JAN-07:30 | 1.32 |
February | 0.144089E+11 | 1.12 | 7115.41 | 01-FEB-09:50 | 1.31 |
March | 0.159292E+11 | 1.13 | 7115.41 | 01-MAR-11:25 | 1.32 |
April | 0.154589E+11 | 1.14 | 7115.41 | 01-APR-08:25 | 1.31 |
May | 0.161511E+11 | 1.14 | 7115.41 | 01-MAY-09:12 | 1.31 |
June | 0.156951E+11 | 1.14 | 7115.41 | 01-JUN-07:28 | 1.31 |
July | 0.163176E+11 | 1.14 | 7115.41 | 01-JUL-09:02 | 1.31 |
August | 0.162618E+11 | 1.14 | 7115.41 | 01-AUG-06:40 | 1.31 |
September | 0.156893E+11 | 1.14 | 7115.41 | 01-SEP-08:05 | 1.31 |
October | 0.161145E+11 | 1.14 | 7115.41 | 01-OCT-08:14 | 1.32 |
November | 0.154456E+11 | 1.13 | 7115.41 | 01-NOV-06:00 | 1.31 |
December | 0.159470E+11 | 1.12 | 7115.41 | 01-DEC-09:23 | 1.32 |
Annual Sum or Average | 0.189320E+12 | 1.13 | |||
Minimum of Months | 0.144089E+11 | 1.11 | 7115.41 | 1.31 | |
Maximum of Months | 0.163176E+11 | 1.14 | 7115.41 | 1.32 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.686277E+10 | 1.21 | 3049.45 | 01-JAN-08:45 | 1.35 |
February | 0.621465E+10 | 1.23 | 3049.45 | 01-FEB-11:05 | 1.35 |
March | 0.689063E+10 | 1.24 | 3049.45 | 01-MAR-12:05 | 1.35 |
April | 0.672827E+10 | 1.28 | 3049.45 | 01-APR-04:20 | 1.34 |
May | 0.713127E+10 | 1.31 | 3049.45 | 01-MAY-03:13 | 1.34 |
June | 0.694025E+10 | 1.31 | 3049.45 | 01-JUN-04:20 | 1.34 |
July | 0.721723E+10 | 1.30 | 3049.45 | 01-JUL-05:00 | 1.34 |
August | 0.718920E+10 | 1.31 | 3049.45 | 01-AUG-03:15 | 1.34 |
September | 0.694228E+10 | 1.31 | 3049.45 | 01-SEP-04:40 | 1.34 |
October | 0.707504E+10 | 1.30 | 3049.45 | 01-OCT-05:10 | 1.35 |
November | 0.671046E+10 | 1.27 | 3049.45 | 01-NOV-05:10 | 1.34 |
December | 0.689246E+10 | 1.23 | 3049.45 | 01-DEC-10:40 | 1.35 |
Annual Sum or Average | 0.827945E+11 | 1.27 | |||
Minimum of Months | 0.621465E+10 | 1.21 | 3049.45 | 1.34 | |
Maximum of Months | 0.721723E+10 | 1.31 | 3049.45 | 1.35 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:10 | 5.36 | 5.36 | 50.43 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:05 | 5.36 | 5.36 | 51.75 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:05 | 5.36 | 5.36 | 51.94 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 54.37 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 54.75 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 55.12 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 55.35 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 55.40 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 55.25 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 54.78 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 54.55 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:05 | 5.36 | 5.36 | 52.13 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 50.43 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 55.40 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.43 | 60.05 | 7157.87 | 13865.98 | 23-JAN-19:50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 51.75 | 60.05 | 7114.39 | 13844.31 | 01-FEB-19:55 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 51.94 | 60.05 | 6911.56 | 13529.30 | 01-MAR-19:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.71 | 52.71 | 6445.24 | 12773.17 | 03-APR-18:38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 53.20 | 53.20 | 6014.44 | 11973.26 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.67 | 53.67 | 5677.51 | 11149.09 | 01-JUN-06:47 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.98 | 53.98 | 5436.40 | 10600.59 | 03-JUL-18:17 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 54.05 | 54.05 | 5562.78 | 10833.56 | 31-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.86 | 53.86 | 5794.12 | 11486.35 | 29-SEP-18:33 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.83 | 51.83 | 6187.60 | 12394.77 | 31-OCT-18:27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.97 | 52.97 | 6632.67 | 13192.69 | 30-NOV-20:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 52.13 | 60.05 | 6977.49 | 13714.68 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 6321.59 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.43 | 51.83 | 5436.40 | 10600.59 | ||
Maximum of Months | 0.00 | 0.00 | 54.05 | 60.05 | 7157.87 | 13865.98 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.245630E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.250665E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.288230E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.354921E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.527131E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.541109E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.596110E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.577558E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.525835E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.473926E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.317006E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.280070E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.497819E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.245630E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.596110E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.106082E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.109313E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.130565E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.173034E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.289486E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.299205E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.335411E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.321417E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.291788E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.250344E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150537E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.126381E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.258356E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.106082E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.335411E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159014E+11 | 0.227098E+11 | 0.389851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144089E+11 | 0.301636E+11 | 0.322978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159292E+11 | 0.397597E+11 | 0.168918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154589E+11 | 0.662684E+11 | 10877376.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161511E+11 | 0.127874E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156951E+11 | 0.134817E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163176E+11 | 0.153421E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162618E+11 | 0.146354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156893E+11 | 0.130361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161145E+11 | 0.108658E+12 | 3869635.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154456E+11 | 0.531873E+11 | 0.177127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159470E+11 | 0.360233E+11 | 0.255259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189320E+12 | 0.104960E+13 | 0.115619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144089E+11 | 0.227098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163176E+11 | 0.153421E+12 | 0.389851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.686277E+10 | 0.113550E+11 | 0.113133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.621465E+10 | 0.150034E+11 | 0.995304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.689063E+10 | 0.211444E+11 | 0.308256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.672827E+10 | 0.375276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.713127E+10 | 0.807781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.694025E+10 | 0.849158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.721723E+10 | 0.975773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.718920E+10 | 0.924148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.694228E+10 | 0.827630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.707504E+10 | 0.659637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.671046E+10 | 0.294432E+11 | 17518.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.689246E+10 | 0.193832E+11 | 0.573314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.827945E+11 | 0.638270E+12 | 0.300822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.621465E+10 | 0.113550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.721723E+10 | 0.975773E+11 | 0.113133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159014E+11 | 0.00 | 0.00 | 0.147171E+10 | 0.718994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144089E+11 | 0.00 | 0.00 | 0.118873E+10 | 0.944511E+10 | 23797038.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159292E+11 | 0.00 | 0.00 | 0.593477E+09 | 0.123003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154589E+11 | 0.00 | 0.00 | 3688974.96 | 0.200295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161511E+11 | 0.00 | 0.00 | 0.00 | 0.365620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156951E+11 | 0.00 | 0.00 | 0.00 | 0.384158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163176E+11 | 0.00 | 0.00 | 0.00 | 0.432934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162618E+11 | 0.00 | 0.00 | 0.00 | 0.414940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156893E+11 | 0.00 | 0.00 | 0.00 | 0.368942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161145E+11 | 0.00 | 0.00 | 1297749.02 | 0.312768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154456E+11 | 0.00 | 0.00 | 60274881.94 | 0.161948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159470E+11 | 0.00 | 0.00 | 0.954961E+09 | 0.110539E+11 | 51144194.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189320E+12 | 0.00 | 0.00 | 0.427414E+10 | 0.304150E+12 | 74941232.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144089E+11 | 0.00 | 0.00 | 0.00 | 0.718994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163176E+11 | 0.00 | 0.00 | 0.147171E+10 | 0.432934E+11 | 51144194.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.686277E+10 | 0.00 | 0.00 | 0.447497E+09 | 0.329797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.621465E+10 | 0.00 | 0.00 | 0.383043E+09 | 0.433359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.689063E+10 | 0.00 | 0.00 | 0.113212E+09 | 0.605268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.672827E+10 | 0.00 | 0.00 | 0.00 | 0.105751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.713127E+10 | 0.00 | 0.00 | 0.00 | 0.218173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.694025E+10 | 0.00 | 0.00 | 0.00 | 0.229802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.721723E+10 | 0.00 | 0.00 | 0.00 | 0.263239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.718920E+10 | 0.00 | 0.00 | 0.00 | 0.249525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.694228E+10 | 0.00 | 0.00 | 0.00 | 0.222366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.707504E+10 | 0.00 | 0.00 | 0.00 | 0.179593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.671046E+10 | 0.00 | 0.00 | 5994.52 | 0.834322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.689246E+10 | 0.00 | 0.00 | 0.228609E+09 | 0.551702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.827945E+11 | 0.00 | 0.00 | 0.117237E+10 | 0.174389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.621465E+10 | 0.00 | 0.00 | 0.00 | 0.329797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.721723E+10 | 0.00 | 0.00 | 0.447497E+09 | 0.263239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223956E+11 | 0.164744E+10 | 0.00 | 46489974.47 | 1486315.96 | 0.228260E+09 | 0.162160E+11 | 0.00 | 3.58 |
February | 0.136635E+11 | 0.239686E+10 | 0.00 | 57860330.11 | 435595.24 | 0.117615E+10 | 0.139438E+11 | 0.00 | 3.60 |
March | 0.116879E+11 | 0.433749E+10 | 0.00 | 65576039.35 | 1468360.80 | 6494248.47 | 0.154932E+11 | 0.00 | 3.61 |
April | 0.244782E+10 | 0.103292E+11 | 0.00 | 67347593.96 | 43279266.55 | 0.00 | 0.900032E+10 | 0.00 | 3.64 |
May | 95482812.07 | 0.437865E+11 | 0.00 | 3688731.42 | 0.364042E+09 | 0.00 | 6861064.21 | 0.00 | 3.72 |
June | 72113381.43 | 0.496719E+11 | 0.00 | 2904924.56 | 0.455807E+09 | 0.00 | 6984456.07 | 0.00 | 3.74 |
July | 12813730.49 | 0.628337E+11 | 0.00 | 3017025.58 | 0.698889E+09 | 0.00 | 4514483.21 | 0.00 | 3.75 |
August | 83082628.63 | 0.560989E+11 | 0.00 | 3302726.46 | 0.549781E+09 | 0.00 | 16647704.72 | 0.00 | 3.74 |
September | 0.116945E+09 | 0.467851E+11 | 0.00 | 4577279.53 | 0.382711E+09 | 0.00 | 23397125.46 | 0.00 | 3.74 |
October | 0.106076E+10 | 0.335362E+11 | 0.00 | 28763549.97 | 0.244732E+09 | 0.00 | 0.489242E+10 | 0.00 | 3.69 |
November | 0.611862E+10 | 0.852441E+10 | 0.00 | 66451548.37 | 34457243.47 | 0.00 | 0.142167E+11 | 0.00 | 3.62 |
December | 0.164497E+11 | 0.472656E+10 | 0.00 | 49084147.80 | 6753110.28 | 0.620328E+09 | 0.144212E+11 | 0.00 | 3.60 |
Annual Sum or Average | 0.742043E+11 | 0.324674E+12 | 0.00 | 0.399064E+09 | 0.278384E+10 | 0.203123E+10 | 0.882419E+11 | 0.00 | 3.67 |
Minimum of Months | 12813730.49 | 0.164744E+10 | 0.00 | 2904924.56 | 435595.24 | 0.00 | 4514483.21 | 0.00 | 3.58 |
Maximum of Months | 0.223956E+11 | 0.628337E+11 | 0.00 | 67347593.96 | 0.698889E+09 | 0.117615E+10 | 0.162160E+11 | 0.00 | 3.75 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196282E+11 | 0.311267E+09 | 0.00 | 55254536.46 | 0.00 | 0.00 | 0.226090E+11 | 0.00 | 8.82 |
February | 0.118915E+11 | 0.353643E+09 | 0.00 | 73712392.79 | 0.00 | 0.00 | 0.214568E+11 | 0.00 | 8.89 |
March | 0.892321E+10 | 0.132841E+10 | 0.00 | 77340544.37 | 0.00 | 0.00 | 0.238717E+11 | 0.00 | 8.93 |
April | 0.101821E+10 | 0.389209E+10 | 0.00 | 90073298.73 | 0.00 | 0.00 | 0.170530E+11 | 0.00 | 9.09 |
May | 0.00 | 0.261088E+11 | 0.00 | 3854266.26 | 0.00 | 0.00 | 0.131555E+09 | 0.00 | 9.46 |
June | 0.00 | 0.312508E+11 | 0.00 | 3810132.33 | 0.00 | 0.00 | 0.211659E+09 | 0.00 | 9.55 |
July | 0.00 | 0.420821E+11 | 0.00 | 814855.42 | 0.00 | 0.00 | 13601208.53 | 0.00 | 9.64 |
August | 0.00 | 0.365899E+11 | 0.00 | 3205607.40 | 0.00 | 0.00 | 0.125064E+09 | 0.00 | 9.57 |
September | 0.00 | 0.297821E+11 | 0.00 | 4751839.78 | 0.00 | 0.00 | 0.242935E+09 | 0.00 | 9.56 |
October | 0.516679E+09 | 0.202187E+11 | 0.00 | 41786592.00 | 0.00 | 0.00 | 0.819985E+10 | 0.00 | 9.33 |
November | 0.445669E+10 | 0.437066E+10 | 0.00 | 76492819.23 | 0.00 | 0.00 | 0.219683E+11 | 0.00 | 9.02 |
December | 0.126266E+11 | 0.182834E+10 | 0.00 | 56953539.69 | 0.00 | 0.00 | 0.227987E+11 | 0.00 | 8.90 |
Annual Sum or Average | 0.590610E+11 | 0.198117E+12 | 0.00 | 0.488050E+09 | 0.00 | 0.00 | 0.138682E+12 | 0.00 | 9.23 |
Minimum of Months | 0.00 | 0.311267E+09 | 0.00 | 814855.42 | 0.00 | 0.00 | 13601208.53 | 0.00 | 8.82 |
Maximum of Months | 0.196282E+11 | 0.420821E+11 | 0.00 | 90073298.73 | 0.00 | 0.00 | 0.238717E+11 | 0.00 | 9.64 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:58
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.776581E+11 | 0.108304E+11 | 0.132388E+12 | 0.993401E+10 | 0.589523E+11 |
February | 0.854542E+11 | 0.779584E+10 | 0.102639E+12 | 0.756573E+10 | 0.740376E+11 |
March | 0.103823E+12 | 0.810402E+10 | 0.969017E+11 | 0.744668E+10 | 0.971910E+11 |
April | 0.117728E+12 | 0.389093E+10 | 0.379872E+11 | 0.477923E+10 | 0.156095E+12 |
May | 0.118593E+12 | -0.550289E+10 | -0.972057E+11 | 0.887395E+09 | 0.289829E+12 |
June | 0.117326E+12 | -0.632281E+10 | -0.114084E+12 | 0.436103E+09 | 0.303864E+12 |
July | 0.121090E+12 | -0.920250E+10 | -0.151331E+12 | -133160697.0 | 0.343740E+12 |
August | 0.113449E+12 | -0.831553E+10 | -0.132130E+12 | 0.568842E+09 | 0.327752E+12 |
September | 0.944123E+11 | -0.684699E+10 | -0.107735E+12 | 0.795470E+09 | 0.292543E+12 |
October | 0.981935E+11 | -0.308736E+10 | -0.474780E+11 | 0.252698E+10 | 0.243527E+12 |
November | 0.688068E+11 | 0.443970E+10 | 0.664672E+11 | 0.619241E+10 | 0.125614E+12 |
December | 0.685981E+11 | 0.815605E+10 | 0.104091E+12 | 0.823473E+10 | 0.879315E+11 |
Annual Sum or Average | 0.118513E+13 | 0.393886E+10 | -0.109490E+12 | 0.492344E+11 | 0.240108E+13 |
Minimum of Months | 0.685981E+11 | -0.920250E+10 | -0.151331E+12 | -133160697.0 | 0.589523E+11 |
Maximum of Months | 0.121090E+12 | 0.108304E+11 | 0.132388E+12 | 0.993401E+10 | 0.343740E+12 |