Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20

Tabular Output Report in Format: HTML

Building: RetailStandalone

Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820

Simulation Timestamp: 2024-07-03 12:20:03


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1204.24 524.95 524.95
Net Site Energy 1204.24 524.95 524.95
Total Source Energy 3813.81 1662.52 1662.52
Net Source Energy 3813.81 1662.52 1662.52


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 2293.99
Net Conditioned Building Area 2293.99
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 5.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 554.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 221.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 43.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 165.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 19.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1204.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 5.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 554.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 221.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 43.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 165.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 19.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 5.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 554.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 221.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 43.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 165.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 19.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 115.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 324.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06
Other 84.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 524.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 115.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 324.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06
Other 84.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 524.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1204.236 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1204.236 100.00
     
Total On-Site and Utility Electric Sources 1204.236 100.00
Total Electricity End Uses 1204.236 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 134.99 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 134.99 100.00
Total Water End Uses 134.99 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 50.33
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3505.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ZoneHeatingSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ZoneElectricSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

SpaceGainsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

PeakSpaceGainsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

SpaceGainComponentsAtCoolingPeakMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ComfortReportSimple55Monthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

OccupantComfortDataSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL |

WindowReportMonthly

| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |

WindowEnergyReportMonthly

| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |

WindowZoneSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

WindowEnergyZoneSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL |

FanReportMonthly

| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |

ZoneTemperatureOscillationReportMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

MechanicalVentilationLoadsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
RunPeriod RUNPERIOD 1
Weather File New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Latitude [deg] 28.58
Longitude [deg] 77.20
Elevation [m] 216.00
Time Zone 5.50
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Above Ground Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Window Opening Area [m2] 83.95 0.00 0.00 83.95 0.00
Gross Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00
Above Ground Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Above Ground Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Window Opening Area [m2] 83.95 0.00 0.00 83.95 0.00
Gross Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00
Above Ground Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 2293.99
Skylight Area [m2] 23.78
Skylight-Roof Ratio [%] 1.04


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BACK_SPACE 379.89 Yes Yes 2317.33 1.00 416.17 0.00 0.00 0.00 4.6739 46.45 8.0700
CORE_RETAIL 1600.48 Yes Yes 9762.95 1.00 356.86 0.00 0.00 0.00 11.3021 6.19 3.2300
POINT_OF_SALE 150.81 Yes Yes 919.94 1.00 189.80 0.00 38.06 38.06 11.3021 6.19 21.5200
FRONT_RETAIL 150.81 Yes Yes 919.94 1.00 189.80 0.00 38.06 38.06 11.3021 6.19 3.2300
FRONT_ENTRY 12.00 Yes Yes 73.20 1.00 24.38 0.00 7.83 7.83 7.5347 6.19 0.0000
Total 2293.99     13993.36   1177.02 0.00 83.95 83.95 10.1847 7.23 5.2170
Conditioned Total 2293.99     13993.36   1177.02 0.00 83.95 83.95 10.1847 7.23 5.2170
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BACK_SPACE 379.89 Yes Yes 1.00 BACK_SPACE GENERAL BACK_SPACE 4.6739 46.45 8.0700  
CORE_RETAIL 1600.48 Yes Yes 1.00 CORE_RETAIL GENERAL CORE_RETAIL 11.3021 6.19 3.2300  
POINT_OF_SALE 150.81 Yes Yes 1.00 POINT_OF_SALE GENERAL POINT_OF_SALE 11.3021 6.19 21.5200  
FRONT_RETAIL 150.81 Yes Yes 1.00 FRONT_RETAIL GENERAL FRONT_RETAIL 11.3021 6.19 3.2300  
FRONT_ENTRY 12.00 Yes Yes 1.00 FRONT_ENTRY GENERAL FRONT_ENTRY 7.5347 6.19 0.0000  
Total 2293.99             10.1847 3.62 5.2170  
Conditioned Total 2293.99             10.1847 3.62 5.2170  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 2293.99 2293.99 0.00 0.00 10.1847 7.23 5.2170
Total 2293.99 2293.99 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 10-JUN-15:00 - - - - - - - - - - - 01-MAY-11:09
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 80683.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 16846.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 10740.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 14626.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1022.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 123919.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 80683.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 16846.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 10740.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 14626.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 1022.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 17.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1757.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 701.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 138.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 615.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 522.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 60.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 3813.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 7.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 766.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 305.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 268.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 227.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 26.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1662.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 7.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 766.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 305.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 268.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 227.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 26.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1662.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BACK_SPACE DIRECT AIR 2.49
CORE_RETAIL DIRECT AIR 8.21
POINT_OF_SALE DIRECT AIR 1.50
FRONT_RETAIL DIRECT AIR 1.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:UnitHeater

Design Size Maximum Supply Air Flow Rate [m3/s]
FRONT_ENTRY UNIT HEATER 0.722408
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
FRONT_ENTRY UNIT HEATER FAN 0.722408
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
FRONT_ENTRY UNIT HEATER HEATING COIL 20769.08
PSZ-AC:1_SUPPHEATCOIL 49368.21
PSZ-AC:2_SUPPHEATCOIL 208665.51
PSZ-AC:3_SUPPHEATCOIL 31838.24
PSZ-AC:4_SUPPHEATCOIL 28736.74
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 2.49 2.49 2.49 2.49 2.49 2.49 1.00 1.000000 2.49
PSZ-AC:2 8.21 8.21 8.21 8.21 8.40 8.40 1.00 0.977539 8.40
PSZ-AC:3 1.50 1.50 1.50 1.50 1.50 1.50 1.00 1.00 1.50
PSZ-AC:4 1.31 1.31 1.31 1.31 1.31 1.31 1.00 1.00 1.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 2.49 0.231581
PSZ-AC:2_OA_CONTROLLER 8.40 1.89
PSZ-AC:3_OA_CONTROLLER 1.50 0.178122
PSZ-AC:4_OA_CONTROLLER 1.31 0.178122
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN 2.49 2661.43
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN 8.40 14156.59
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN 1.50 1608.29
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN 1.31 1450.45
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] User-Specified Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 2.49 2.49 2.49 1.64 50251.47 33076.70 40.00 49368.21 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 8.40 8.40 8.40 5.55 208665.51 139805.89 40.00 208665.51 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 1.50 1.50 1.50 0.991983 32360.80 21331.62 40.00 31838.24 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 1.31 1.31 1.31 0.864645 29141.94 19253.62 40.00 28736.74 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 2.49 1.24 1.66 50251.47 25125.74 0.772230 0.772230
PSZ-AC:2 HP COOLING COIL 8.40 4.20 5.60 208665.51 104332.76 0.701080 0.701080
PSZ-AC:3 HP COOLING COIL 1.50 0.751503 1.00 32360.80 16180.40 0.748670 0.748670
PSZ-AC:4 HP COOLING COIL 1.31 0.655034 0.873380 29141.94 14570.97 0.736590 0.736590
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:MultiSpeed

Design Size Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] Design Size Speed 2 Gross Rated Heating Capacity [W] Design Size Speed 1 Gross Rated Heating Capacity [W] Design Size Resistive Defrost Heater Capacity
PSZ-AC:1 HEATING COIL 2.49 1.24 49368.21 24684.11 0.000000
PSZ-AC:2 HEATING COIL 8.40 4.20 208665.51 104332.75 0.000000
PSZ-AC:3 HEATING COIL 1.50 0.751503 31838.24 15919.12 0.000000
PSZ-AC:4 HEATING COIL 1.31 0.655034 28736.74 14368.37 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
BACK_SPACE_WALL_EAST BACK_SPACE_WALL_EAST_ROLLDOOR |
BACK_SPACE_WALL_NORTH BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 |
BACK_SPACE_WALL_WEST BACK_SPACE_WALL_WEST_ROLLDOOR |
CORE_RETAIL_WALL_WEST_2 CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 |
CORE_RETAIL_WALL_EAST_2 CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 |
CORE_RETAIL_ROOF SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 |
POINT_OF_SALE_WALL_SOUTH POINT_OF_SALE_WALL_SOUTH_GLAZING |
FRONT_RETAIL_WALL_SOUTH FRONT_RETAIL_WALL_SOUTH_GLAZING |
FRONT_ENTRY_WALL_SOUTH FRONT_ENTRY_WALL_SOUTH_GLAZING |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 25.10 19.60 14.50 13.40 17.00 22.40 29.10 33.00 33.60 31.70 30.00 28.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 28.58 77.20 5.50 216.00 98757 1.1738


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 24.84 20.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 RetailStandalone 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 5 73 32


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BACK_SPACE 0.0 0.00 35.27 0.00 27.14 38.77 3.05 1 1 1 0.00 54.27 35.27 42.27 0.00 6.10 6.10 2317.33 TARP TARP 379.89 416.17 375.11 0.00 6 7 0 Yes
2 CORE_RETAIL 0.0 0.00 6.00 0.00 27.14 14.41 3.05 1 1 1 0.00 54.27 3.00 35.27 0.00 6.10 6.10 9762.95 TARP TARP 1600.48 356.86 345.15 23.78 10 22 0 Yes
3 POINT_OF_SALE 0.0 0.00 0.00 0.00 12.57 3.00 3.05 1 1 1 0.00 25.14 0.00 6.00 0.00 6.10 6.10 919.94 TARP TARP 150.81 189.80 151.74 38.06 7 1 0 Yes
4 FRONT_RETAIL 0.0 29.14 0.00 0.00 41.70 3.00 3.05 1 1 1 29.14 54.27 0.00 6.00 0.00 6.10 6.10 919.94 TARP TARP 150.81 189.80 151.74 38.06 7 1 0 Yes
5 FRONT_ENTRY 0.0 25.14 0.00 0.00 27.14 1.50 3.05 1 1 1 25.14 29.14 0.00 3.00 0.00 6.10 6.10 73.20 TARP TARP 12.00 24.38 16.55 7.83 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BACK_SPACE 379.89 8.2 46.452 2.153E-002 4.674 8.070 0.000 0.000 0.000 0.000 12.744 No
2 CORE_RETAIL 1600.48 258.4 6.193 0.161 11.302 3.230 0.000 0.000 0.000 0.000 14.532 No
3 POINT_OF_SALE 150.81 24.4 6.193 0.161 11.302 21.520 0.000 0.000 0.000 0.000 32.822 No
4 FRONT_RETAIL 150.81 24.4 6.193 0.161 11.302 3.230 0.000 0.000 0.000 0.000 14.532 No
5 FRONT_ENTRY 12.00 1.9 6.192 0.162 7.535 0.000 0.000 0.000 0.000 0.000 7.535 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BACK_SPACE BLDG_OCC_SCH BACK_SPACE 379.89 8.2 8.2 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_RETAIL BLDG_OCC_SCH CORE_RETAIL 1600.48 258.4 258.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 258 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 POINT_OF_SALE BLDG_OCC_SCH POINT_OF_SALE 150.81 24.4 24.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 24 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 FRONT_RETAIL BLDG_OCC_SCH FRONT_RETAIL 150.81 24.4 24.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 24 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 FRONT_ENTRY BLDG_OCC_SCH FRONT_ENTRY 12.00 1.9 1.9 0.162 6.192 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BACK_SPACE_LIGHTS LTG_SCH_BACK BACK_SPACE 379.89 8.2 1775.579 4.674 217.113 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1775.579
2 CORE_RETAIL_LIGHTS LTG_SCH_CORE CORE_RETAIL 1600.48 258.4 18088.802 11.302 69.994 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18088.802
3 POINT_OF_SALE_LIGHTS LTG_SCH_SALE POINT_OF_SALE 150.81 24.4 1704.468 11.302 69.994 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1704.468
4 FRONT_RETAIL_LIGHTS LTG_SCH_FRONT FRONT_RETAIL 150.81 24.4 1704.468 11.302 69.994 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1704.468
5 FRONT_ENTRY_LIGHTS LTG_SCH_ENTRY FRONT_ENTRY 12.00 1.9 90.417 7.535 46.655 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 90.417


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BACK_SPACE_MISCPLUG_EQUIP BLDG_EQUIP_SCH BACK_SPACE 379.89 8.2 3065.712 8.070 374.868 0.000 0.500 0.000 0.500 MiscPlug 0.000 3065.712
2 CORE_RETAIL_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_RETAIL 1600.48 258.4 5169.560 3.230 20.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 5169.560
3 POINT_OF_SALE_MISCPLUG_EQUIP BLDG_EQUIP_SCH POINT_OF_SALE 150.81 24.4 3245.431 21.520 133.273 0.000 0.500 0.000 0.500 MiscPlug 0.000 3245.431
4 FRONT_RETAIL_MISCPLUG_EQUIP BLDG_EQUIP_SCH FRONT_RETAIL 150.81 24.4 487.116 3.230 20.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 487.116


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 2.390 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
6 NONRES_EXT_WALL_GRD 21 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
7 BACK_SPACE_FLOOR_FFACTOR 38 2 7 0.167 0.2354 0.000 0.900 0.000 0.700 MediumRough
8 CORE_RETAIL_FLOOR_FFACTOR 39 2 7 0.167 0.4655E-01 0.000 0.900 0.000 0.700 MediumRough
9 POINT_OF_SALE_FLOOR_FFACTOR 40 2 7 0.167 0.2719 0.000 0.900 0.000 0.700 MediumRough
10 FRONT_RETAIL_FLOOR_FFACTOR 41 2 7 0.167 0.2719 0.000 0.900 0.000 0.700 MediumRough
11 FRONT_ENTRY_FLOOR_FFACTOR 42 2 7 0.167 0.4506 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.4184
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
10 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.2994E-01
11 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
12 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 4.172
13 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
14 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 21.40
15 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
16 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.601
17 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
18 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 3.601
19 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
20 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.142
21 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 2.3900722 2.3900722 2.3900722  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
21 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
22 1 -21.915918 0.11588205 -6.3286394 0.20197014
23 0 21.365777 0.10835518 5.5011278  
24 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
25 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
26 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
27 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
28 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
29 4 19.715055 0.51780401E-02 12.415669 -0.24584718
30 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
31 2 168.49726 0.99923307E-02 62.094262 -2.4465849
32 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
33 0 57.057407 0.91053392E-05 16.929182  
34 7 -0.17867606E-08 -0.41848128E-15 0.59564440E-14 -0.80268503E-16
35 6 0.65885627E-05 0.45121803E-08 0.31870471E-02 -0.26735622E-04
36 5 -0.47407468E-03 0.26731137E-05 -0.22356413 0.19547341E-02
37 4 0.10906669E-01 0.12168607E-03 4.8268734 -0.45239294E-01
38 3 -0.95781928E-01 0.96775432E-03 -38.006321 0.39848689
39 2 0.34010998 0.16100142E-02 116.45457 -1.4175463
40 1 -0.49090295 0.49061009E-03 -143.89001 2.0487556
41 0 0.23934032 0.11861159E-04 60.838472  
42 7 -0.92098544E-08 0.58605081E-15 -0.29904982E-14 0.25019681E-16
43 6 0.19387148E-05 0.91388609E-09 0.32017682E-02 -0.26859115E-04
44 5 -0.10799279E-03 0.53275402E-06 -0.22440051 0.19621166E-02
45 4 0.22736042E-02 0.24052495E-04 4.8407977 -0.45373149E-01
46 3 -0.19287081E-01 0.18995237E-03 -38.084949 0.39935605
47 2 0.67516478E-01 0.31394945E-03 116.60756 -1.4195928
48 1 -0.96817688E-01 0.94848058E-04 -143.98006 2.0502357
49 0 0.47046370E-01 0.22824214E-05 60.838472  
50 7 -0.15410587E-08 -0.27131508E-15 0.13739895E-13 -0.20869099E-15
51 6 0.75948721E-05 0.52202150E-08 0.31841660E-02 -0.26711453E-04
52 5 -0.54825752E-03 0.30939483E-05 -0.22340036 0.19532886E-02
53 4 0.12624073E-01 0.14086823E-03 4.8241453 -0.45213070E-01
54 3 -0.11089483 0.11205317E-02 -37.990908 0.39831653
55 2 0.39381345 0.18644394E-02 116.42457 -1.4171450
56 1 -0.56844024 0.56830838E-03 -143.87235 2.0484654
57 0 0.27714917 0.13715070E-04 60.838472  
58 7 -0.15410587E-08 -0.27131508E-15 0.13739895E-13 -0.20869099E-15
59 6 0.75948721E-05 0.52202150E-08 0.31841660E-02 -0.26711453E-04
60 5 -0.54825752E-03 0.30939483E-05 -0.22340036 0.19532886E-02
61 4 0.12624073E-01 0.14086823E-03 4.8241453 -0.45213070E-01
62 3 -0.11089483 0.11205317E-02 -37.990908 0.39831653
63 2 0.39381345 0.18644394E-02 116.42457 -1.4171450
64 1 -0.56844024 0.56830838E-03 -143.87235 2.0484654
65 0 0.27714917 0.13715070E-04 60.838472  
66 7 -0.91256693E-09 -0.65654920E-16 0.14763662E-14 0.25811017E-17
67 6 0.12659591E-04 0.87293215E-08 0.31698558E-02 -0.26591407E-04
68 5 -0.91895148E-03 0.51830142E-05 -0.22258679 0.19461077E-02
69 4 0.21183618E-01 0.23613386E-03 4.8105909 -0.45082779E-01
70 3 -0.18612912 0.18798277E-02 -37.914317 0.39746999
71 2 0.66101200 0.31293459E-02 116.27548 -1.4151508
72 1 -0.95411819 0.95507326E-03 -143.78458 2.0470226
73 0 0.46518638 0.22828278E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.503_SHGC_0.23 36 1 VerySmooth 2.860 2.860 1.000 0.231    
2 NONRESSKYLIGHT_U_0.7_SHGC_0.3 37 1 VerySmooth 3.979 3.979 1.000 0.303    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SpectralAverage   1.93472E-002 0.14129 0.63061 0.63061 0.25300 0.16079 0.23715 0.00000 0.84000 0.84000 0.10783 1.00000 No
2 NONRES SKYLIGHT GLAZING LAYER SpectralAverage   2.00000E-003 0.17728 0.47032 0.47032 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 2.40661E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CORE_RETAIL 16 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CORE_RETAIL 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 1.001 0.9283


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BACK_SPACE_WALL_EAST 0 257.68 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
2 BACK_SPACE_WALL_EAST_ROLLDOOR 0 257.68 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
3 BACK_SPACE_WALL_NORTH 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
4 BACK_SPACE_WALL_NORTH_DOOR1 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
5 BACK_SPACE_WALL_NORTH_DOOR2 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
6 BACK_SPACE_WALL_NORTH_ROLLDOOR1 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
7 BACK_SPACE_WALL_NORTH_ROLLDOOR2 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
8 BACK_SPACE_WALL_NORTH_ROLLDOOR3 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
9 BACK_SPACE_WALL_WEST 0 257.68 96.73 6.10 0 6.10 68.27 12.40 0.00 0 No No
10 BACK_SPACE_WALL_WEST_ROLLDOOR 0 257.68 96.73 6.10 0 6.10 68.27 12.40 0.00 0 No No
11 BACK_SPACE_WALL_SOUTH 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
12 BACK_SPACE_FLOOR 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
13 BACK_SPACE_ROOF 0 2293.99 205.08 0.00 0 6.10 68.27 12.40 0.00 0 No No
14 BACK_SPACE_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
15 CORE_RETAIL_WALL_SOUTH_3 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
16 CORE_RETAIL_WALL_SOUTH_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
17 CORE_RETAIL_WALL_EAST_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
18 CORE_RETAIL_WALL_SOUTH_2 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
19 CORE_RETAIL_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
20 CORE_RETAIL_WALL_WEST_2 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 4 No No
21 CORE_RETAIL_WALL_WEST_2_DOOR3 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
22 CORE_RETAIL_WALL_WEST_2_DOOR2 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
23 CORE_RETAIL_WALL_WEST_2_DOOR1 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
24 CORE_RETAIL_WALL_EAST_2 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 4 No No
25 CORE_RETAIL_WALL_EAST_2_DOOR1 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
26 CORE_RETAIL_WALL_EAST_2_DOOR2 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
27 CORE_RETAIL_WALL_EAST_2_DOOR3 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
28 CORE_RETAIL_WALL_WEST_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
29 CORE_RETAIL_FLOOR 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
30 CORE_RETAIL_ROOF 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
31 SKYLIGHTS_R4C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
32 SKYLIGHTS_R4C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
33 SKYLIGHTS_R4C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
34 SKYLIGHTS_R4C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
35 SKYLIGHTS_R1C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
36 SKYLIGHTS_R1C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
37 SKYLIGHTS_R1C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
38 SKYLIGHTS_R1C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
39 SKYLIGHTS_R2C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
40 SKYLIGHTS_R2C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
41 SKYLIGHTS_R2C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
42 SKYLIGHTS_R2C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
43 SKYLIGHTS_R3C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
44 SKYLIGHTS_R3C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
45 SKYLIGHTS_R3C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
46 SKYLIGHTS_R3C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
47 CORE_RETAIL_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
48 POINT_OF_SALE_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 4 No No
49 POINT_OF_SALE_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 1 No No
50 POINT_OF_SALE_WALL_EAST_2 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
51 POINT_OF_SALE_WALL_WEST 0 257.68 96.73 6.10 0 6.10 31.14 9.69 0.20 4 No No
52 POINT_OF_SALE_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
53 POINT_OF_SALE_WALL_EAST_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
54 POINT_OF_SALE_FLOOR 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
55 POINT_OF_SALE_ROOF 0 2293.99 205.08 0.00 0 6.10 31.14 9.69 0.20 0 No No
56 POINT_OF_SALE_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
57 FRONT_RETAIL_WALLL_EAST 0 257.68 149.77 6.10 0 6.10 31.14 9.69 0.20 4 No No
58 FRONT_RETAIL_WALL_WEST_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
59 FRONT_RETAIL_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
60 FRONT_RETAIL_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 4 No No
61 FRONT_RETAIL_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 1 No No
62 FRONT_RETAIL_WALL_WEST_2 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
63 FRONT_RETAIL_FLOOR 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
64 FRONT_RETAIL_ROOF 0 2293.99 205.08 0.00 0 6.10 31.14 9.69 0.20 0 No No
65 FRONT_RETAIL_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
66 FRONT_ENTRY_WALL_EAST 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
67 FRONT_ENTRY_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
68 FRONT_ENTRY_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 4.00 3.43 0.32 4 No No
69 FRONT_ENTRY_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 4.00 3.43 0.32 1 No No
70 FRONT_ENTRY_WALL_WEST 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
71 FRONT_ENTRY_FLOOR 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
72 FRONT_ENTRY_ROOF 0 2293.99 205.08 0.00 0 6.10 4.00 3.43 0.32 0 No No
73 FRONT_ENTRY_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No


FenestrationAssembly

Construction Name Frame and Divider Name NFRC Product Type Assembly U-Factor {W/m2-K} Assembly SHGC Assembly Visible Transmittance
1 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES CurtainWall 3.838 0.300 0.402


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 BACK_SPACE_INFILTRATION INFIL_SCH_PNNL BACK_SPACE 379.89 8.2 0.107 2.808E-004 1.274E-004 0.166 0.000 0.000 0.224 0.000
2 CORE_RETAIL_INFILTRATION INFIL_SCH_PNNL CORE_RETAIL 1600.48 258.4 9.147E-002 5.715E-005 4.645E-005 3.373E-002 0.000 0.000 0.224 0.000
3 POINT_OF_SALE_INFILTRATION INFIL_SCH_PNNL POINT_OF_SALE 150.81 24.4 4.865E-002 3.226E-004 1.428E-004 0.190 0.000 0.000 0.224 0.000
4 FRONT_RETAIL_INFILTRATION INFIL_SCH_PNNL FRONT_RETAIL 150.81 24.4 4.865E-002 3.226E-004 1.428E-004 0.190 0.000 0.000 0.224 0.000
5 FRONT_ENTRY_INFILTRATION INFIL_SCH_PNNL FRONT_ENTRY 12.00 1.9 6.250E-003 5.208E-004 1.718E-004 0.307 0.000 0.000 0.224 0.000
6 FRONT_ENTRY_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH FRONT_ENTRY 12.00 1.9 1.419 0.118 3.899E-002 69.771 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BACK_SPACE Mixing/Well-Stirred
2 CORE_RETAIL Mixing/Well-Stirred
3 POINT_OF_SALE Mixing/Well-Stirred
4 FRONT_RETAIL Mixing/Well-Stirred
5 FRONT_ENTRY Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone BACK_SPACE 1.2000
3 Zone CORE_RETAIL 1.2000
4 Zone POINT_OF_SALE 1.2000
5 Zone FRONT_RETAIL 1.2000
6 Zone FRONT_ENTRY 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone BACK_SPACE 1.2000
3 Zone CORE_RETAIL 1.2000
4 Zone POINT_OF_SALE 1.2000
5 Zone FRONT_RETAIL 1.2000
6 Zone FRONT_ENTRY 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 1.1015E-004
2 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 1.8574E-004
3 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 1.0071E-004
4 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 1.5871E-004
5 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 9.8223E-005
6 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 1.5709E-004
7 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 1.2140E-004
8 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 2.5134E-004
9 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 1.6791E-004
10 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 1.3641E-004
11 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 1.4467E-004
12 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 1.2176E-004
13 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 1.4008E-004
14 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 1.2503E-004
15 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 2.1606E-004
16 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 1.6361E-004
17 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 1.7662E-004
18 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 9.2170E-005
19 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 1.5208E-004
20 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 8.7617E-005
21 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 1.5280E-004
22 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 8.9803E-005
23 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 2.3470E-004
24 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 9.8097E-005
25 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.1873E-004
26 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 7.5580E-005
27 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.0820E-004
28 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 7.4577E-005
29 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.1131E-004
30 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 7.6287E-005
31 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.3538E-004
32 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 7.9371E-005
33 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 1.6135E-004
34 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 1.1074E-003
35 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 1.5789E-004
36 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 1.2897E-003
37 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 1.7163E-004
38 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 7.9746E-004
39 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 1.3163E-004
40 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 3.1688E-004
41 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 5.2691E-004
42 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 4.1274E-004
43 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 5.6757E-004
44 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 4.4919E-004
45 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 5.0285E-004
46 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 3.6154E-004
47 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 2.6373E-004
48 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 1.8840E-004
49 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 2.6960E-004
50 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 8.3767E-005
51 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 2.8369E-004
52 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 8.3554E-005
53 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 2.5107E-004
54 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 8.4740E-005
55 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 1.4999E-004
56 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 8.0054E-005
57 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 1.0346E-003
58 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 1.3422E-004
59 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 1.2053E-003
60 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 1.3496E-004
61 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 7.3328E-004
62 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 1.3230E-004
63 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 2.9158E-004
64 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 1.0222E-004
65 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 1.6110E-003
66 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 7.8755E-004
67 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 1.6033E-003
68 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 7.8477E-004
69 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 2.1530E-003
70 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 1.0021E-003
71 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 1.9958E-003
72 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 7.3619E-004
73 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 2.4062E-004
74 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 4.9337E-003
75 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 2.1983E-004
76 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 5.5196E-003
77 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 2.9328E-004
78 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 5.2265E-003
79 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 2.8004E-004
80 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 3.7367E-003
81 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 3.6004E-003
82 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 1.6038E-004
83 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 3.9664E-003
84 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 1.5302E-004
85 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 3.9726E-003
86 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 1.7792E-004
87 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 2.7826E-003
88 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 1.4729E-004
89 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 4.2373E-004
90 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 8.6702E-005
91 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 4.1005E-004
92 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 8.5132E-005
93 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 5.2635E-004
94 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 8.9222E-005
95 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 3.9533E-004
96 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 8.5415E-005
97 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 6.6269E-004
98 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 3.7741E-004
99 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 5.5389E-004
100 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 3.2701E-004
101 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 7.6657E-004
102 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 4.6770E-004
103 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 1.6019E-003
104 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 6.4168E-004
105 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 1.9024E-004
106 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 9.9900E-004
107 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 1.6687E-004
108 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 8.3997E-004
109 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 1.9710E-004
110 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 1.1841E-003
111 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 2.6013E-004
112 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 2.7993E-003
113 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 8.4986E-004
114 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 1.2913E-004
115 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 7.1954E-004
116 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 1.1955E-004
117 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 1.0483E-003
118 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 1.3780E-004
119 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 2.1576E-003
120 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 1.4225E-004
121 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 2.5303E-004
122 Clear Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 8.2354E-005
123 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 2.2308E-004
124 Clear Turbid Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 8.0517E-005
125 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 2.9934E-004
126 Intermediate Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 8.4107E-005
127 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 3.5932E-004
128 Overcast Sky 01/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 8.4939E-005


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BACK_SPACE Cooling 27461.41202 32953.69443 2.07267 2.48721 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:40:00 40.90067 9.15606E-003 379.89000 8.17812 0.23158 0.00000
2 BACK_SPACE Heating 23214.13934 27856.96721 1.00249 1.20299 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 379.89000 8.17812 0.23158 0.00000
3 CORE_RETAIL Cooling 94178.37711 113014.05253 6.84519 8.21422 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 1600.48290 258.43418 1.89033 0.00000
4 CORE_RETAIL Heating 50396.62113 60475.94536 2.13214 2.55857 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 1600.48290 258.43418 1.89033 0.00000
5 POINT_OF_SALE Cooling 16592.46919 19910.96302 1.25250 1.50301 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:10:00 41.28867 9.15671E-003 150.81000 24.35169 0.17812 0.00000
6 POINT_OF_SALE Heating 10470.21439 12564.25727 0.45325 0.54390 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 150.81000 24.35169 0.17812 0.00000
7 FRONT_RETAIL Cooling 14462.51794 17355.02152 1.09172 1.31007 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 41.61200 9.15725E-003 150.81000 24.35169 0.17812 0.00000
8 FRONT_RETAIL Heating 10462.32313 12554.78775 0.45290 0.54349 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 150.81000 24.35169 0.17812 0.00000
9 FRONT_ENTRY Cooling 0.00000 0.00000 0.00000 1.41732E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:10:00 41.90300 9.15774E-003 12.00000 1.93800 1.41732E-002 0.00000
10 FRONT_ENTRY Heating 17305.91083 20767.09299 0.60201 0.72241 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 13:00:00 6.30000 6.07234E-003 12.00000 1.93800 1.41732E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 37252.63 2.48721 2.48721 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
2 PSZ-AC:1 Heating Sensible 31078.97 1.20299 1.20299 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 PSZ-AC:2 Cooling Sensible 148440.99 8.40296 8.40296 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
4 PSZ-AC:2 Heating Sensible 90276.86 2.55857 2.55857 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00
5 PSZ-AC:3 Cooling Sensible 23345.17 1.50301 1.50301 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
6 PSZ-AC:3 Heating Sensible 15318.15 0.54390 0.54390 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00
7 PSZ-AC:4 Cooling Sensible 20900.68 1.31007 1.31007 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
8 PSZ-AC:4 Heating Sensible 15308.76 0.54349 0.54349 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BACK_SPACE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 2.48721
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_RETAIL DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 8.21422
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat POINT_OF_SALE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.50301
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat FRONT_RETAIL DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.31007
5 ZoneHVAC:UnitHeater FRONT_ENTRY UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 0.72241
6 Fan:ConstantVolume FRONT_ENTRY UNIT HEATER FAN Design Size Maximum Flow Rate [m3/s] 0.72241
7 Coil:Heating:Electric FRONT_ENTRY UNIT HEATER HEATING COIL Design Size Nominal Capacity [W] 20769.08053
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.48721
9 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.48721
10 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 2.48721
11 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 2.48721
12 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 2.48721
13 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 2.48721
14 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
15 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 8.21422
17 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 8.21422
18 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 8.21422
19 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 8.21422
20 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 8.40296
21 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 8.40296
22 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
23 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 0.97754
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.50301
25 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.50301
26 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.50301
27 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 1.50301
28 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 1.50301
29 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 1.50301
30 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
31 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.31007
33 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.31007
34 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.31007
35 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 1.31007
36 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 1.31007
37 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 1.31007
38 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
39 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
40 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 2.48721
41 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 8.40296
42 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 1.50301
43 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 1.31007
44 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.48721
45 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.23158
46 Fan:SystemModel PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 2.48721
47 Fan:SystemModel PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 2661.42971
48 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 2.48721
49 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 2.48721
50 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 2.48721
51 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.64156
52 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 2.48721
53 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 1.24360
54 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.65814
55 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 50251.47000
56 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 25125.73500
57 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.77223
58 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.77223
59 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 50251.47000
60 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 33076.70252
61 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
62 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 49368.21271
63 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
64 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 2.48721
65 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 1.24360
66 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 49368.21271
67 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 24684.10636
68 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
69 Coil:Heating:Electric PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 49368.21271
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.40296
71 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.89033
72 Fan:SystemModel PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 8.40296
73 Fan:SystemModel PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 14156.58979
74 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 8.40296
75 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 8.40296
76 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 8.40296
77 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 5.54595
78 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 8.40296
79 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 4.20148
80 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 5.60197
81 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 208665.51000
82 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 104332.75500
83 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.70108
84 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.70108
85 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 208665.51000
86 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 139805.89082
87 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
88 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 208665.50869
89 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
90 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 8.40296
91 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 4.20148
92 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 208665.50782
93 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 104332.75391
94 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
95 Coil:Heating:Electric PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 208665.50869
96 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.50301
97 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.17812
98 Fan:SystemModel PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.50301
99 Fan:SystemModel PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1608.28650
100 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.50301
101 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.50301
102 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.50301
103 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.99198
104 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.50301
105 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.75150
106 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.00201
107 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 32360.80000
108 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 16180.40000
109 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.74867
110 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.74867
111 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 32360.80000
112 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 21331.62225
113 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
114 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 31838.24217
115 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
116 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 1.50301
117 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.75150
118 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 31838.24217
119 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 15919.12109
120 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
121 Coil:Heating:Electric PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 31838.24217
122 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.31007
123 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.17812
124 Fan:SystemModel PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.31007
125 Fan:SystemModel PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1450.45290
126 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.31007
127 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.31007
128 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.31007
129 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.86464
130 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.31007
131 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.65503
132 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.87338
133 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 29141.94000
134 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 14570.97000
135 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.73659
136 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.73659
137 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 29141.94000
138 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 19253.61636
139 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
140 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 28736.74083
141 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
142 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 1.31007
143 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.65503
144 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 28736.74083
145 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 14368.37041
146 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
147 Coil:Heating:Electric PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 28736.74083


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL 48296.5     11.22 11.22  
2 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL 202036.3     10.63 10.63  
3 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL 31178.2     11.52 11.52  
4 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL 28110.5     11.58 11.58  


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL 51351.4 28430.0 7.90 2
2 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL 215416.5 118534.3 7.31 2
3 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL 33039.1 18256.8 8.03 2
4 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL 29784.7 16442.4 8.02 2


Zone Surfaces

Zone Name # Surfaces
1 BACK_SPACE 14
2 CORE_RETAIL 33
3 POINT_OF_SALE 9
4 FRONT_RETAIL 9
5 FRONT_ENTRY 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BACK_SPACE_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   35.24 42.67 35.24 90.00 90.00 7.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
2 BACK_SPACE_WALL_EAST_ROLLDOOR Door BACK_SPACE_WALL_EAST CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 90.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
3 BACK_SPACE_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   304.63 330.83 304.63 0.00 90.00 54.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
4 BACK_SPACE_WALL_NORTH_DOOR1 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 BACK_SPACE_WALL_NORTH_DOOR2 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
6 BACK_SPACE_WALL_NORTH_ROLLDOOR1 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
7 BACK_SPACE_WALL_NORTH_ROLLDOOR2 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
8 BACK_SPACE_WALL_NORTH_ROLLDOOR3 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 BACK_SPACE_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   35.24 42.67 35.24 270.00 90.00 7.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 BACK_SPACE_WALL_WEST_ROLLDOOR Door BACK_SPACE_WALL_WEST CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 270.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 BACK_SPACE_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   330.83 330.83 330.83 180.00 90.00 54.27 6.10 0.00 CORE_RETAIL_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
12 BACK_SPACE_FLOOR Floor   CTF - ConductionTransferFunction BACK_SPACE_FLOOR_FFACTOR 0.235 0.223   379.89 379.89 379.89 90.00 180.00 7.00 54.27 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 BACK_SPACE_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   379.89 379.89 379.89 90.00 0.00 7.00 54.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
14 BACK_SPACE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   759.78 759.78 759.78 0.00 90.00 759.78 1.00 0.00 BACK_SPACE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 CORE_RETAIL_WALL_SOUTH_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 180.00 90.00 25.14 6.10 0.00 FRONT_RETAIL_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
16 CORE_RETAIL_WALL_SOUTH_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 180.00 90.00 25.14 6.10 0.00 POINT_OF_SALE_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
17 CORE_RETAIL_WALL_EAST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_RETAIL_WALL_WEST_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
18 CORE_RETAIL_WALL_SOUTH_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.38 24.38 24.38 180.00 90.00 4.00 6.10 0.00 FRONT_ENTRY_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 CORE_RETAIL_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   330.83 330.83 330.83 0.00 90.00 54.27 6.10 0.00 BACK_SPACE_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 CORE_RETAIL_WALL_WEST_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   172.58 178.43 172.58 270.00 90.00 29.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 CORE_RETAIL_WALL_WEST_2_DOOR3 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 CORE_RETAIL_WALL_WEST_2_DOOR2 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
23 CORE_RETAIL_WALL_WEST_2_DOOR1 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 CORE_RETAIL_WALL_EAST_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   172.58 178.43 172.58 90.00 90.00 29.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 CORE_RETAIL_WALL_EAST_2_DOOR1 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
26 CORE_RETAIL_WALL_EAST_2_DOOR2 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
27 CORE_RETAIL_WALL_EAST_2_DOOR3 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
28 CORE_RETAIL_WALL_WEST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 POINT_OF_SALE_WALL_EAST_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_RETAIL_FLOOR Floor   CTF - ConductionTransferFunction CORE_RETAIL_FLOOR_FFACTOR 4.655E-002 4.603E-002   1600.48 1600.48 1600.48 0.00 180.00 40.01 40.01 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
30 CORE_RETAIL_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   1576.70 1600.48 1576.70 180.00 0.00 40.01 40.01 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
31 SKYLIGHTS_R4C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 1.11E-016 1.00 4
32 SKYLIGHTS_R4C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
33 SKYLIGHTS_R4C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
34 SKYLIGHTS_R4C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
35 SKYLIGHTS_R1C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
36 SKYLIGHTS_R1C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
37 SKYLIGHTS_R1C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
38 SKYLIGHTS_R1C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
39 SKYLIGHTS_R2C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
40 SKYLIGHTS_R2C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
41 SKYLIGHTS_R2C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
42 SKYLIGHTS_R2C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
43 SKYLIGHTS_R3C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
44 SKYLIGHTS_R3C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 1.11E-016 1.00 4
45 SKYLIGHTS_R3C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
46 SKYLIGHTS_R3C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
47 CORE_RETAIL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3200.97 3200.97 3200.97 0.00 90.00 3200.97 1.00 0.00 CORE_RETAIL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
48 POINT_OF_SALE_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   115.16 153.22 115.16 180.00 90.00 25.14 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 POINT_OF_SALE_WALL_SOUTH_GLAZING Window POINT_OF_SALE_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.503_SHGC_0.23 N/A 2.860 No 38.06 38.06 38.06 180.00 90.00 25.04 1.52 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
50 POINT_OF_SALE_WALL_EAST_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 CORE_RETAIL_WALL_WEST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 POINT_OF_SALE_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   36.58 36.58 36.58 270.00 90.00 6.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 POINT_OF_SALE_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 0.00 90.00 25.14 6.10 0.00 CORE_RETAIL_WALL_SOUTH_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
53 POINT_OF_SALE_WALL_EAST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_ENTRY_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 POINT_OF_SALE_FLOOR Floor   CTF - ConductionTransferFunction POINT_OF_SALE_FLOOR_FFACTOR 0.272 0.255   150.81 150.81 150.81 180.00 180.00 25.14 6.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
55 POINT_OF_SALE_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   150.81 150.81 150.81 180.00 0.00 25.14 6.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
56 POINT_OF_SALE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   301.62 301.62 301.62 0.00 90.00 301.62 1.00 0.00 POINT_OF_SALE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
57 FRONT_RETAIL_WALLL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   36.58 36.58 36.58 90.00 90.00 6.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 FRONT_RETAIL_WALL_WEST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 FRONT_ENTRY_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 FRONT_RETAIL_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 0.00 90.00 25.14 6.10 0.00 CORE_RETAIL_WALL_SOUTH_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 FRONT_RETAIL_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   115.16 153.22 115.16 180.00 90.00 25.14 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 FRONT_RETAIL_WALL_SOUTH_GLAZING Window FRONT_RETAIL_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.503_SHGC_0.23 N/A 2.860 No 38.06 38.06 38.06 180.00 90.00 25.04 1.52 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 FRONT_RETAIL_WALL_WEST_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 CORE_RETAIL_WALL_EAST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 FRONT_RETAIL_FLOOR Floor   CTF - ConductionTransferFunction FRONT_RETAIL_FLOOR_FFACTOR 0.272 0.255   150.81 150.81 150.81 90.00 180.00 6.00 25.14 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
64 FRONT_RETAIL_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   150.81 150.81 150.81 90.00 0.00 6.00 25.14 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
65 FRONT_RETAIL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   301.62 301.62 301.62 0.00 90.00 301.62 1.00 0.00 FRONT_RETAIL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
66 FRONT_ENTRY_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_RETAIL_WALL_WEST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
67 FRONT_ENTRY_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.38 24.38 24.38 0.00 90.00 4.00 6.10 0.00 CORE_RETAIL_WALL_SOUTH_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
68 FRONT_ENTRY_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   16.55 24.38 16.55 180.00 90.00 4.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 FRONT_ENTRY_WALL_SOUTH_GLAZING Window FRONT_ENTRY_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.503_SHGC_0.23 N/A 2.860 No 7.83 7.83 7.83 180.00 90.00 3.00 2.61 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 FRONT_ENTRY_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 POINT_OF_SALE_WALL_EAST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 FRONT_ENTRY_FLOOR Floor   CTF - ConductionTransferFunction FRONT_ENTRY_FLOOR_FFACTOR 0.451 0.406   12.00 12.00 12.00 180.00 180.00 4.00 3.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
72 FRONT_ENTRY_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   12.00 12.00 12.00 180.00 0.00 4.00 3.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
73 FRONT_ENTRY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   24.00 24.00 24.00 0.00 90.00 24.00 1.00 0.00 FRONT_ENTRY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BACK_SPACE RunPeriod: RUNPERIOD 1 7.8937087716E-002 0.3229491629 Pass Pass 5.0669045375E-002 0.2314142840 Pass Pass
2 CORE_RETAIL RunPeriod: RUNPERIOD 1 4.5620703306E-002 0.1889543166 Pass Pass 0.3396882578 1.6197673647 Pass Pass
3 POINT_OF_SALE RunPeriod: RUNPERIOD 1 7.8901181599E-002 0.2156077965 Pass Pass 0.1404213270 0.5339944555 Pass Pass
4 FRONT_RETAIL RunPeriod: RUNPERIOD 1 7.0329306919E-002 0.2644170366 Pass Pass 0.1334888805 0.3818698565 Pass Pass
5 FRONT_ENTRY RunPeriod: RUNPERIOD 1 0.1625881378 0.3880412850 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 2638.29 -1.6 0.00 -736.2 2498.43 4398.98



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 6.30 0.00 6.30 Wetbulb [C] 0.50 270.00
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 42.00 9.70 22.20 Wetbulb [C] 3.20 320.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.60 4      
Feb 21.40 43      
Mar 12.00 35      
Apr 29.10 12      
May 29.10 57      
Jun 197.10 59      
Jul 47.90 83      
Aug 0.00 0      
Sep 171.60 106      
Oct 4.80 31      
Nov 1.20 7      
Dec 33.00 13      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BACK_SPACE_WALL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 42.67 35.24 90.00 90.00 E
BACK_SPACE_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 330.83 304.63 0.00 90.00 N
BACK_SPACE_WALL_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 42.67 35.24 270.00 90.00 W
BACK_SPACE_FLOOR BACK_SPACE_FLOOR_FFACTOR 1.00 0.227 0.235 379.89 379.89 90.00 180.00  
BACK_SPACE_ROOF NONRES_ROOF 0.55 0.273 0.283 379.89 379.89 90.00 0.00  
CORE_RETAIL_WALL_WEST_2 NONRES_EXT_WALL_GRD 0.30 2.882 5.069 178.43 172.58 270.00 90.00 W
CORE_RETAIL_WALL_EAST_2 NONRES_EXT_WALL_GRD 0.30 2.882 5.069 178.43 172.58 90.00 90.00 E
CORE_RETAIL_FLOOR CORE_RETAIL_FLOOR_FFACTOR 1.00 0.046 0.047 1600.48 1600.48 0.00 180.00  
CORE_RETAIL_ROOF NONRES_ROOF 0.55 0.273 0.283 1600.48 1576.70 180.00 0.00  
POINT_OF_SALE_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 153.22 115.16 180.00 90.00 S
POINT_OF_SALE_WALL_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 36.58 36.58 270.00 90.00 W
POINT_OF_SALE_FLOOR POINT_OF_SALE_FLOOR_FFACTOR 1.00 0.260 0.272 150.81 150.81 180.00 180.00  
POINT_OF_SALE_ROOF NONRES_ROOF 0.55 0.273 0.283 150.81 150.81 180.00 0.00  
FRONT_RETAIL_WALLL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 36.58 36.58 90.00 90.00 E
FRONT_RETAIL_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 153.22 115.16 180.00 90.00 S
FRONT_RETAIL_FLOOR FRONT_RETAIL_FLOOR_FFACTOR 1.00 0.260 0.272 150.81 150.81 90.00 180.00  
FRONT_RETAIL_ROOF NONRES_ROOF 0.55 0.273 0.283 150.81 150.81 90.00 0.00  
FRONT_ENTRY_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 24.38 16.55 180.00 90.00 S
FRONT_ENTRY_FLOOR FRONT_ENTRY_FLOOR_FFACTOR 1.00 0.420 0.451 12.00 12.00 180.00 180.00  
FRONT_ENTRY_ROOF NONRES_ROOF 0.55 0.273 0.283 12.00 12.00 180.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BACK_SPACE_WALL_SOUTH INT_WALL 0.30 2.511 6.299 330.83 330.83 180.00 90.00 S
CORE_RETAIL_WALL_SOUTH_3 INT_WALL 0.30 2.511 6.299 153.22 153.22 180.00 90.00 S
CORE_RETAIL_WALL_SOUTH_1 INT_WALL 0.30 2.511 6.299 153.22 153.22 180.00 90.00 S
CORE_RETAIL_WALL_EAST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
CORE_RETAIL_WALL_SOUTH_2 INT_WALL 0.30 2.511 6.299 24.38 24.38 180.00 90.00 S
CORE_RETAIL_WALL_NORTH INT_WALL 0.30 2.511 6.299 330.83 330.83 0.00 90.00 N
CORE_RETAIL_WALL_WEST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
POINT_OF_SALE_WALL_EAST_2 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
POINT_OF_SALE_WALL_NORTH INT_WALL 0.30 2.511 6.299 153.22 153.22 0.00 90.00 N
POINT_OF_SALE_WALL_EAST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
FRONT_RETAIL_WALL_WEST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
FRONT_RETAIL_WALL_NORTH INT_WALL 0.30 2.511 6.299 153.22 153.22 0.00 90.00 N
FRONT_RETAIL_WALL_WEST_2 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
FRONT_ENTRY_WALL_EAST INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
FRONT_ENTRY_WALL_NORTH INT_WALL 0.30 2.511 6.299 24.38 24.38 0.00 90.00 N
FRONT_ENTRY_WALL_WEST INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
BACK_SPACE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 759.78   0.00 90.00 N
CORE_RETAIL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3200.97   0.00 90.00 N
POINT_OF_SALE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 301.62   0.00 90.00 N
FRONT_RETAIL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 301.62   0.00 90.00 N
FRONT_ENTRY_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 24.00   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
SKYLIGHTS_R4C1 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C2 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C3 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C4 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C1 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C2 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C4 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C3 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C2 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C1 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C3 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C4 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C2 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C1 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C3 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C4 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
POINT_OF_SALE_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.503_SHGC_0.23   38.06 0.00 0.00 38.06 38.06 2.860 0.231 0.254             No POINT_OF_SALE_WALL_SOUTH 180.00 90.00 S
FRONT_RETAIL_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.503_SHGC_0.23   38.06 0.00 0.00 38.06 38.06 2.860 0.231 0.254             No FRONT_RETAIL_WALL_SOUTH 180.00 90.00 S
FRONT_ENTRY_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.503_SHGC_0.23   7.83 0.00 0.00 7.83 7.83 2.860 0.231 0.254             No FRONT_ENTRY_WALL_SOUTH 180.00 90.00 S
Total or Average             107.73 3.107 0.247 0.286                      
North Total or Average             0.00 - - -                      
Non-North Total or Average             107.73 3.107 0.247 0.286                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
BACK_SPACE_WALL_EAST_ROLLDOOR OVERHEAD DOOR_CON 1.760 2.390 7.43 BACK_SPACE_WALL_EAST
BACK_SPACE_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR1 OVERHEAD DOOR_CON 1.760 2.390 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR2 OVERHEAD DOOR_CON 1.760 2.390 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR3 OVERHEAD DOOR_CON 1.760 2.390 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_WEST_ROLLDOOR OVERHEAD DOOR_CON 1.760 2.390 7.43 BACK_SPACE_WALL_WEST
CORE_RETAIL_WALL_WEST_2_DOOR3 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_WEST_2_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_WEST_2_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_EAST_2_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_EAST_2
CORE_RETAIL_WALL_EAST_2_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_EAST_2
CORE_RETAIL_WALL_EAST_2_DOOR3 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_EAST_2


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
SKYLIGHTS_R4C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
POINT_OF_SALE_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
FRONT_RETAIL_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
FRONT_ENTRY_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BACK_SPACE_LIGHTS BACK_SPACE BACK_SPACE GENERAL 4.6739 379.89 1775.58 LightsWired LTG_SCH_BACK 32.16 168.00 32.49 0.0000 Y 10.83
CORE_RETAIL_LIGHTS CORE_RETAIL CORE_RETAIL GENERAL 11.3021 1600.48 18088.80 LightsWired LTG_SCH_CORE 69.21 168.00 49.57 0.0000 Y 168.31
POINT_OF_SALE_LIGHTS POINT_OF_SALE POINT_OF_SALE GENERAL 11.3021 150.81 1704.47 LightsWired LTG_SCH_SALE 69.21 168.00 65.23 0.0000 Y 20.87
FRONT_RETAIL_LIGHTS FRONT_RETAIL FRONT_RETAIL GENERAL 11.3021 150.81 1704.47 LightsWired LTG_SCH_FRONT 69.21 168.00 65.23 0.0000 Y 20.87
FRONT_ENTRY_LIGHTS FRONT_ENTRY FRONT_ENTRY GENERAL 7.5347 12.00 90.42 LightsWired LTG_SCH_ENTRY 38.07 168.00 37.20 0.0000 Y 0.63
Interior Lighting Total       10.1847 2293.99 23363.73               221.51


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
CORE_RETAIL_DAYLREFPT1 CORE_RETAIL CORE_RETAIL_DAYLCTRL SplitFlux Continuous/Off 0.25 18088.80 4522.20
CORE_RETAIL_DAYLREFPT2 CORE_RETAIL CORE_RETAIL_DAYLCTRL SplitFlux Continuous/Off 0.25 18088.80 4522.20


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 358.54 AstronomicalClock -   41.75 41.75 2.81
EXTERIOR_LIGHTS_B 3462.32 AstronomicalClock -   83.75 62.75 40.79
Exterior Lighting Total 3820.86           43.60



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   50251.47 38805.69 11445.78 0.77 3.67    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   208665.51 146291.22 62374.29 0.70 3.32    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   32360.80 24227.56 8133.24 0.75 3.74    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   29141.94 21465.66 7676.28 0.74 3.74    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   48296.5     11.22 11.22  
PSZ-AC:2 HP COOLING COIL   202036.3     10.63 10.63  
PSZ-AC:3 HP COOLING COIL   31178.2     11.52 11.52  
PSZ-AC:4 HP COOLING COIL   28110.5     11.58 11.58  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed 51351.4 28430.0 7.90 2
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed 215416.5 118534.3 7.31 2
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed 33039.1 18256.8 8.03 2
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed 29784.7 16442.4 8.02 2
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
FRONT_ENTRY UNIT HEATER HEATING COIL Coil:Heating:Electric   20769.08 1.00
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed   49368.21 3.49
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Electric   49368.21 1.00
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed   208665.51 3.49
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Electric   208665.51 1.00
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed   31838.24 3.55
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Electric   31838.24 1.00
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed   28736.74 3.55
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Electric   28736.74 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
FRONT_ENTRY UNIT HEATER FAN Fan:ConstantVolume 0.54 49.80 0.72 67.12 92.91 1.00 4.54 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 13:00:00
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.58 622.50 2.49 2661.43 1070.05 1.00 1.29 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:40:00
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.60 1018.41 8.40 14156.59 1684.71 1.00 1.15 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:20:00
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.58 622.50 1.50 1608.29 1070.05 1.00 1.36 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 622.50 1.31 1450.45 1107.16 1.00 1.34 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
None                


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 1.00 0.93



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BACK_SPACE 27461.41 32953.69 86.75 2.073 2.487 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:40:00 23.89 23.89 0.00709 40.90 0.00916 0.232 0.00
CORE_RETAIL 94178.38 113014.05 70.61 6.845 8.214 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 23.89 23.89 0.00798 34.82 0.00915 1.890 0.00
POINT_OF_SALE 16592.47 19910.96 132.03 1.253 1.503 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:10:00 23.89 23.89 0.00734 41.29 0.00916 0.178 0.00
FRONT_RETAIL 14462.52 17355.02 115.08 1.092 1.310 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 23.89 23.89 0.00739 41.61 0.00916 0.178 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.000 0.014 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:10:00 0.00 41.11 0.00922 41.90 0.00916 0.014 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BACK_SPACE 23214.14 27856.97 73.33 1.002 1.203 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.11 21.11 0.00798 6.30 0.00607 0.232 0.00
CORE_RETAIL 50396.62 60475.95 37.79 2.132 2.559 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.11 21.11 0.00799 6.30 0.00607 1.890 0.00
POINT_OF_SALE 10470.21 12564.26 83.31 0.453 0.544 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.11 21.11 0.00798 6.30 0.00607 0.178 0.00
FRONT_RETAIL 10462.32 12554.79 83.25 0.453 0.543 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.11 21.11 0.00798 6.30 0.00607 0.178 0.00
FRONT_ENTRY 17305.91 20767.09 1730.59 0.602 0.722 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 13:00:00 16.00 15.98 0.00663 6.30 0.00607 0.014 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 2.49 2.49 1.20 1.20 2.4872 2.4872 2.4872 1.0000 1.0000
PSZ-AC:2 8.40 8.40 2.56 2.56 8.4030 8.2142 8.4030 0.9775 1.0000
PSZ-AC:3 1.50 1.50 0.54 0.54 1.5030 1.5030 1.5030 1.0000 1.0000
PSZ-AC:4 1.31 1.31 0.54 0.54 1.3101 1.3101 1.3101 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
FRONT_ENTRY UNIT HEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER FRONT_ENTRY UNIT HEATER 20769.081 20769.081 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 13:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 13:00:00 20769.08 20769.08 0.722408 15.98 11.31 0.00663124 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 15.98 0.00663124 57.3626 20767.09 0.00 -999.00 -999.00
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:1 50251.470 38805.693 2.487210 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:40:00 25125.74 24184.91 1.658140 26.42 15.94 0.00728050 12.80 10.34 0.00700000 41.42 0.00915693 22.10 13.9663 23.89 0.00708741 37.5210 27403.86 0.00 -999.00 -999.00
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:1 49368.213 49368.213 2.487208 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24684.11 24684.11 1.243604 19.55 13.87 0.00780388 40.00 20.89 0.00800000 6.30 0.00607234 6.30 18.6217 21.11 0.00798166 49.9598 23214.14 0.00 -999.00 -999.00
PSZ-AC:1_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:1 49368.213 49368.213 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 49368.21 49368.21 2.487208 19.55 13.87 0.00780388 40.00 20.89 0.00800000 6.30 0.00607234 6.30 9.3109 21.11 0.00798166 49.9598 23214.14 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:2 208665.510 146291.216 8.402960 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:20:00 104332.76 93422.28 5.601973 29.44 17.56 0.00798067 12.80 10.34 0.00700000 42.00 0.00915790 22.26 33.7440 23.89 0.00763144 40.3705 91212.67 0.00 -999.00 -999.00
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:2 208665.509 208665.509 8.402960 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 104332.75 104332.75 4.201480 17.53 12.86 0.00755676 40.00 20.89 0.00800000 6.30 0.00607234 6.30 44.9920 21.11 0.00798763 49.9966 50396.62 0.00 -999.00 -999.00
PSZ-AC:2_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:2 208665.509 208665.509 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 208665.51 208665.51 8.402960 17.53 12.86 0.00755676 40.00 20.89 0.00800000 6.30 0.00607234 6.30 22.4960 21.11 0.00798763 49.9966 50396.62 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:3 32360.800 24227.560 1.503010 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:10:00 16180.40 15050.20 1.002007 26.89 16.34 0.00755528 12.80 10.34 0.00700000 41.61 0.00915725 22.16 17.7765 23.89 0.00733947 38.8435 16562.71 0.00 -999.00 -999.00
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:3 31838.242 31838.242 1.503005 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 15919.12 15919.12 0.751503 19.17 13.69 0.00775750 40.00 20.89 0.00800000 6.30 0.00607234 6.30 23.7021 21.11 0.00798405 49.9746 10470.21 0.00 -999.00 -999.00
PSZ-AC:3_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:3 31838.242 31838.242 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 31838.24 31838.24 1.503005 19.17 13.69 0.00775750 40.00 20.89 0.00800000 6.30 0.00607234 6.30 11.8510 21.11 0.00798405 49.9746 10470.21 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:4 29141.940 21465.662 1.310070 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 14570.97 13448.09 0.873380 27.28 16.54 0.00763038 12.80 10.34 0.00700000 42.00 0.00915790 22.26 20.3945 23.89 0.00738939 39.1046 14430.48 0.00 -999.00 -999.00
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:4 28736.741 28736.741 1.310068 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 14368.37 14368.37 0.655034 18.92 13.56 0.00772409 40.00 20.89 0.00800000 6.30 0.00607234 6.30 27.1927 21.11 0.00798401 49.9743 10462.32 0.00 -999.00 -999.00
PSZ-AC:4_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:4 28736.741 28736.741 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 28736.74 28736.74 1.310068 18.92 13.56 0.00772409 40.00 20.89 0.00800000 6.30 0.00607234 6.30 13.5964 21.11 0.00798401 49.9743 10462.32 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
FRONT_ENTRY UNIT HEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER FRONT_ENTRY UNIT HEATER FRONT_ENTRY N/A N/A N/A Yes No unknown No 20769.081 20769.081 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 FRONT_ENTRY UNIT HEATER FAN Fan:ConstantVolume 0.722408 0.84795230   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 13:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 13:00:00 Sensible 20769.08 20769.08 1.0000 0.84795230 0.722408 15.98 11.31 0.00663124 32838.9 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 20769.08 6.30 0.00607234 6.30 0.00000000 0.0000 15.98 0.00663124 15.98 0.00663124 57.3626 20767.09 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident CoolingDesignCapacity N/A No No unknown No 50251.470 38805.693 2.487210 -999.0 -999.000 -999.0000 1.00000 1.00000 1018.3741 1004.8586 1.1738 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 2.487208 2.91944812   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:40:00 Sensible 25125.74 24184.91 1.0000 1.94630062 1.658140 26.42 15.94 0.00728050 45113.9 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 25125.74 41.42 0.00915693 22.10 0.23158056 13.9663 23.89 0.00708741 23.89 0.00708741 37.5210 27403.86 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident HeatingDesignCapacity N/A Yes Yes unknown No 49368.213 49368.213 2.487208 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 2.487208 2.91944812   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24684.11 24684.11 1.0000 1.45972406 1.243604 19.55 13.87 0.00780388 39444.0 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 24684.11 6.30 0.00607234 6.30 0.23158056 18.6217 20.91 0.00798166 21.11 0.00798166 49.9598 23214.14 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident HeatingDesignCapacity N/A Yes No unknown No 49368.213 49368.213 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 2.487208 2.91944812   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 49368.21 49368.21 1.0000 2.91944812 2.487208 19.55 13.87 0.00780388 39444.0 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 49368.21 6.30 0.00607234 6.30 0.23158056 9.3109 20.91 0.00798166 21.11 0.00798166 49.9598 23214.14 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident CoolingDesignCapacity N/A No No unknown No 208665.510 146291.216 8.402960 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.6757 1004.8586 1.1738 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 8.402960 9.86327231   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:20:00 Sensible 104332.76 93422.28 1.0000 6.57551485 5.601973 29.44 17.56 0.00798067 49977.6 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 104332.76 42.00 0.00915790 22.26 1.89032875 33.7440 23.89 0.00763144 23.89 0.00763144 40.3705 91212.67 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident HeatingDesignCapacity N/A Yes Yes unknown No 208665.509 208665.509 8.402960 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 8.402960 9.86327231   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 104332.75 104332.75 1.0000 4.93163616 4.201480 17.53 12.86 0.00755676 36762.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 104332.75 6.30 0.00607234 6.30 1.89032875 44.9920 20.79 0.00798763 21.11 0.00798763 49.9966 50396.62 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident HeatingDesignCapacity N/A Yes No unknown No 208665.509 208665.509 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 8.402960 9.86327231   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 208665.51 208665.51 1.0000 9.86327231 8.402960 17.53 12.86 0.00755676 36762.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 208665.51 6.30 0.00607234 6.30 1.89032875 22.4960 20.79 0.00798763 21.11 0.00798763 49.9966 50396.62 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident CoolingDesignCapacity N/A No No unknown No 32360.800 24227.560 1.503010 -999.0 -999.000 -999.0000 1.00000 1.00000 1018.8849 1004.8586 1.1738 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.503005 1.76420553   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:10:00 Sensible 16180.40 15050.20 1.0000 1.17614086 1.002007 26.89 16.34 0.00755528 46290.2 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 16180.40 41.61 0.00915725 22.16 0.17812154 17.7765 23.89 0.00733947 23.89 0.00733947 38.8435 16562.71 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident HeatingDesignCapacity N/A Yes Yes unknown No 31838.242 31838.242 1.503005 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.503005 1.76420553   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 15919.12 15919.12 1.0000 0.88210276 0.751503 19.17 13.69 0.00775750 38944.9 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 15919.12 6.30 0.00607234 6.30 0.17812154 23.7021 20.91 0.00798405 21.11 0.00798405 49.9746 10470.21 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident HeatingDesignCapacity N/A Yes No unknown No 31838.242 31838.242 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.503005 1.76420553   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 31838.24 31838.24 1.0000 1.76420553 1.503005 19.17 13.69 0.00775750 38944.9 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 31838.24 6.30 0.00607234 6.30 0.17812154 11.8510 20.91 0.00798405 21.11 0.00798405 49.9746 10470.21 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident CoolingDesignCapacity N/A No No unknown No 29141.940 21465.662 1.310070 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.0245 1004.8586 1.1738 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.310068 1.53773842   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 Sensible 14570.97 13448.09 1.0000 1.02516075 0.873380 27.28 16.54 0.00763038 46883.9 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 14570.97 42.00 0.00915790 22.26 0.17812154 20.3945 23.89 0.00738939 23.89 0.00738939 39.1046 14430.48 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident HeatingDesignCapacity N/A Yes Yes unknown No 28736.741 28736.741 1.310068 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.310068 1.53773842   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 14368.37 14368.37 1.0000 0.76886921 0.655034 18.92 13.56 0.00772409 38600.4 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 14368.37 6.30 0.00607234 6.30 0.17812154 27.1927 20.91 0.00798401 21.11 0.00798401 49.9743 10462.32 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident HeatingDesignCapacity N/A Yes No unknown No 28736.741 28736.741 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.310068 1.53773842   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 28736.74 28736.74 1.0000 1.53773842 1.310068 18.92 13.56 0.00772409 38600.4 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 28736.74 6.30 0.00607234 6.30 0.17812154 13.5964 20.91 0.00798401 21.11 0.00798401 49.9743 10462.32 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BACK_SPACE 2983.83 1617.50 234.17
CORE_RETAIL 3304.17 1863.33 830.83
POINT_OF_SALE 3968.17 474.33 61.00
FRONT_RETAIL 3834.17 750.67 205.50
FRONT_ENTRY 3990.50 4246.17 3464.67
Facility 4384.17 4678.00 3505.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BACK_SPACE 6.33 62.50 0.00 0.00
CORE_RETAIL 0.00 0.00 0.00 0.00
POINT_OF_SALE 0.33 83.00 0.00 0.00
FRONT_RETAIL 0.50 65.00 0.00 0.00
FRONT_ENTRY 55.33 0.00 50.33 0.00
Facility 61.67 96.33 50.33 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BACK_SPACE 4.06 8.18 2317.33 0.371 0.005 0.000 0.000
CORE_RETAIL 128.26 258.43 9762.95 0.720 0.001 0.000 0.000
POINT_OF_SALE 12.09 24.35 919.94 0.719 0.006 0.000 0.000
FRONT_RETAIL 12.09 24.35 919.94 0.719 0.006 0.000 0.000
FRONT_ENTRY 0.96 1.94 73.20 0.000 35.337 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BACK_SPACE 4.06 8.18 2317.33 0.339 0.000 0.000 0.000
CORE_RETAIL 128.26 258.43 9762.95 0.657 0.000 0.000 0.000
POINT_OF_SALE 12.09 24.35 919.94 0.658 0.000 0.000 0.000
FRONT_RETAIL 12.09 24.35 919.94 0.657 0.000 0.000 0.000
FRONT_ENTRY 0.96 1.94 73.20 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BACK_SPACE PSZ-AC:1 4.06 8.18 2317.33 379.89 0.2316 0.232
CORE_RETAIL PSZ-AC:2 128.26 258.43 9762.95 1600.48 1.8903 1.890
POINT_OF_SALE PSZ-AC:3 12.09 24.35 919.94 150.81 0.1781 0.178
FRONT_RETAIL PSZ-AC:4 12.09 24.35 919.94 150.81 0.1781 0.178
FRONT_ENTRY   0.96 1.94 73.20 12.00   0.014
Total Facility   157.45 317.25 13993.36 2293.99 2.4782 2.492


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BACK_SPACE 4489338.26 0.00 4489338.26 140360.86 4629699.12 7303124.67 3443.74 5316.26 0.00 613.11
CORE_RETAIL 35924905.77 0.00 35924905.77 120356.30 36045262.06 59613407.55 3481.57 5278.43 0.00 373.45
POINT_OF_SALE 3453066.61 0.00 3453066.61 64012.53 3517079.13 5617240.89 3457.97 5302.03 0.00 737.75
FRONT_RETAIL 3446000.82 0.00 3446000.82 64012.53 3510013.35 5617240.89 3457.02 5302.98 0.00 636.92
FRONT_ENTRY 0.00 0.00 0.00 12134837.51 12134837.51 446965.66 8760.00 0.00 0.00 0.00
Total Facility 47313311.45 0.00 47313311.45 12523579.72 59836891.17 78597979.65 8760.00 5319.75 0.00 827.32


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BACK_SPACE 0.2316 0.0000 0.2316 0.0033 0.2349 0.2316 0.00 4913.00 0.00
CORE_RETAIL 1.8903 0.0000 1.8903 0.0029 1.8932 1.8903 0.00 4913.00 0.00
POINT_OF_SALE 0.1781 0.0000 0.1781 0.0015 0.1796 0.1781 0.00 4913.00 0.00
FRONT_RETAIL 0.1781 0.0000 0.1781 0.0015 0.1796 0.1781 0.00 4913.00 0.00
FRONT_ENTRY 0.0000 0.0000 0.0000 0.6809 0.6809 0.0142 4913.00 0.00 0.00
Total Facility 2.4782 0.0000 2.4782 0.6901 3.1682 2.4923 4913.00 4913.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 6185277.07 0.00 6185277.07 7303124.67 3424.09 2.22 5333.68 612.78
PSZ-AC:2 49496273.82 0.00 49496273.82 59613407.55 3481.47 0.02 5278.51 373.43
PSZ-AC:3 4757528.15 0.00 4757528.15 5617240.89 3441.74 1.92 5316.34 730.94
PSZ-AC:4 4747798.86 0.00 4747798.86 5617240.89 3439.40 1.99 5318.61 633.84


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.3191 0.0000 0.3191 0.2316 0.00 0.00 4913.00
PSZ-AC:2 2.6044 0.0000 2.6044 1.8903 0.00 0.00 4913.00
PSZ-AC:3 0.2454 0.0000 0.2454 0.1781 0.00 0.00 4913.00
PSZ-AC:4 0.2454 0.0000 0.2454 0.1781 0.00 0.00 4913.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 5525.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 5286.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 5643.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 5546.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.3191 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 2.6050 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.2455 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.2455 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Surfaces by Class

Total Outdoors
Wall 26 10
Floor 5 5
Roof 5 5
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 19 19
Door 13 13
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 4
Conditioned Zones 5
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 507
Defaulted Fields 477
Fields with Defaults 1428
Autosized Fields 96
Autosizable Fields 234
Autocalculated Fields 78
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1204.24 2224.80 01-JAN-07:40 123919.44 10-JUN-16:00
Electricity:Building 415.81 2224.80 01-JAN-00:10 30876.16 02-JAN-17:40
Electricity:Zone:BACK_SPACE 60.60 495.06 01-JAN-00:10 3493.96 02-JAN-09:10
Electricity:SpaceType:GENERAL 415.81 2224.80 01-JAN-00:10 30876.16 02-JAN-17:40
InteriorLights:Electricity 221.51 453.21 01-JAN-00:10 20135.27 02-JAN-17:40
InteriorLights:Electricity:Zone:BACK_SPACE 10.83 41.25 01-JAN-00:10 742.55 02-JAN-09:10
InteriorLights:Electricity:SpaceType:GENERAL 221.51 453.21 01-JAN-00:10 20135.27 02-JAN-17:40
LightsWired:InteriorLights:Electricity 221.51 453.21 01-JAN-00:10 20135.27 02-JAN-17:40
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE 10.83 41.25 01-JAN-00:10 742.55 02-JAN-09:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 221.51 453.21 01-JAN-00:10 20135.27 02-JAN-17:40
Electricity:Zone:CORE_RETAIL 252.24 1109.80 01-JAN-00:10 20919.50 02-JAN-17:40
InteriorLights:Electricity:Zone:CORE_RETAIL 168.31 344.55 01-JAN-00:10 16279.92 02-JAN-17:40
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL 168.31 344.55 01-JAN-00:10 16279.92 02-JAN-17:40
Electricity:Zone:POINT_OF_SALE 73.56 512.89 01-JAN-00:10 4446.73 02-JAN-09:10
InteriorLights:Electricity:Zone:POINT_OF_SALE 20.87 32.47 01-JAN-00:10 1534.02 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE 20.87 32.47 01-JAN-00:10 1534.02 02-JAN-09:10
Electricity:Zone:FRONT_RETAIL 28.78 104.57 01-JAN-00:10 1971.20 02-JAN-09:10
InteriorLights:Electricity:Zone:FRONT_RETAIL 20.87 32.47 01-JAN-00:10 1534.02 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL 20.87 32.47 01-JAN-00:10 1534.02 02-JAN-09:10
Electricity:Zone:FRONT_ENTRY 0.63 2.49 01-JAN-00:10 44.76 02-JAN-09:10
InteriorLights:Electricity:Zone:FRONT_ENTRY 0.63 2.49 01-JAN-00:10 44.76 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY 0.63 2.49 01-JAN-00:10 44.76 02-JAN-09:10
InteriorEquipment:Electricity 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
InteriorEquipment:Electricity:Zone:BACK_SPACE 49.77 453.82 01-JAN-00:10 2751.42 02-JAN-09:10
InteriorEquipment:Electricity:SpaceType:GENERAL 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE 49.77 453.82 01-JAN-00:10 2751.42 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
InteriorEquipment:Electricity:Zone:CORE_RETAIL 83.93 765.25 01-JAN-00:10 4639.58 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL 83.93 765.25 01-JAN-00:10 4639.58 02-JAN-09:10
InteriorEquipment:Electricity:Zone:POINT_OF_SALE 52.69 480.42 01-JAN-00:10 2912.71 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE 52.69 480.42 01-JAN-00:10 2912.71 02-JAN-09:10
InteriorEquipment:Electricity:Zone:FRONT_RETAIL 7.91 72.11 01-JAN-00:10 437.18 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL 7.91 72.11 01-JAN-00:10 437.18 02-JAN-09:10
ElectricityPurchased:Facility 1204.24 2224.80 01-JAN-07:40 123919.44 10-JUN-16:00
ElectricityPurchased:Plant 1204.24 2224.80 01-JAN-07:40 123919.44 10-JUN-16:00
Cogeneration:ElectricityPurchased 1204.24 2224.80 01-JAN-07:40 123919.44 10-JUN-16:00
General:Cogeneration:ElectricityPurchased 1204.24 2224.80 01-JAN-07:40 123919.44 10-JUN-16:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1204.24 2224.80 01-JAN-07:40 123919.44 10-JUN-16:00
ElectricityNet:Plant 1204.24 2224.80 01-JAN-07:40 123919.44 10-JUN-16:00
Cogeneration:ElectricityNet 1204.24 2224.80 01-JAN-07:40 123919.44 10-JUN-16:00
General:Cogeneration:ElectricityNet 1204.24 2224.80 01-JAN-07:40 123919.44 10-JUN-16:00
Electricity:HVAC 725.63 0.00 01-JAN-00:10 95309.94 10-JUN-16:00
Fans:Electricity 165.05 0.00 01-JAN-00:10 15062.41 01-JUL-16:00
General:Fans:Electricity 165.05 0.00 01-JAN-00:10 15062.41 01-JUL-16:00
Heating:Electricity 5.65 0.00 01-JAN-00:10 31202.03 02-JAN-06:20
General:Heating:Electricity 5.65 0.00 01-JAN-00:10 31202.03 02-JAN-06:20
Cooling:Electricity 554.93 0.00 01-JAN-00:10 80683.26 10-JUN-16:00
General:Cooling:Electricity 554.93 0.00 01-JAN-00:10 80683.26 10-JUN-16:00
ExteriorLights:Electricity 43.60 0.00 01-JAN-07:20 3820.86 01-JAN-06:10
General:ExteriorLights:Electricity 43.60 0.00 01-JAN-07:20 3820.86 01-JAN-06:10
Electricity:Plant 19.20 0.00 01-JAN-00:10 1995.38 17-JAN-13:00
WaterSystems:Electricity 19.20 0.00 01-JAN-00:10 1995.38 17-JAN-13:00
Water Heater:WaterSystems:Electricity 19.20 0.00 01-JAN-00:10 1995.38 17-JAN-13:00


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 134.99 0.00 01-JAN-00:10 0.00 01-MAY-11:10
Water:Plant 134.99 0.00 01-JAN-00:10 0.00 01-MAY-11:10
WaterSystems:Water 134.99 0.00 01-JAN-00:10 0.00 01-MAY-11:10
Water Heater:WaterSystems:Water 134.99 0.00 01-JAN-00:10 0.00 01-MAY-11:10
MainsWater:Facility 134.99 0.00 01-JAN-00:10 0.00 01-MAY-11:10
MainsWater:Plant 134.99 0.00 01-JAN-00:10 0.00 01-MAY-11:10
WaterSystems:MainsWater 134.99 0.00 01-JAN-00:10 0.00 01-MAY-11:10
Water Heater:WaterSystems:MainsWater 134.99 0.00 01-JAN-00:10 0.00 01-MAY-11:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 3064.07 0.00 01-JAN-00:10 376255.81 01-JUL-16:00
EnergyTransfer:Building 1090.35 0.00 01-JAN-00:10 132900.27 12-JUN-14:40
EnergyTransfer:Zone:BACK_SPACE 182.10 0.00 01-JAN-00:10 36210.32 06-MAY-04:10
Heating:EnergyTransfer 11.22 0.00 01-JAN-00:10 80647.43 01-JAN-08:20
Heating:EnergyTransfer:Zone:BACK_SPACE 7.59 0.00 01-JAN-00:10 30268.33 01-JAN-07:10
General:Heating:EnergyTransfer 11.22 0.00 01-JAN-00:10 80647.43 01-JAN-08:20
General:Heating:EnergyTransfer:Zone:BACK_SPACE 7.59 0.00 01-JAN-00:10 30268.33 01-JAN-07:10
Cooling:EnergyTransfer 1079.13 0.00 01-JAN-00:10 132900.27 12-JUN-14:40
Cooling:EnergyTransfer:Zone:BACK_SPACE 174.51 0.00 01-JAN-00:10 36210.32 06-MAY-04:10
General:Cooling:EnergyTransfer 1079.13 0.00 01-JAN-00:10 132900.27 12-JUN-14:40
General:Cooling:EnergyTransfer:Zone:BACK_SPACE 174.51 0.00 01-JAN-00:10 36210.32 06-MAY-04:10
EnergyTransfer:Zone:CORE_RETAIL 625.28 0.00 01-JAN-00:10 86322.58 07-JUN-06:10
Heating:EnergyTransfer:Zone:CORE_RETAIL 3.20 0.00 01-JAN-00:10 59216.50 01-JAN-08:20
General:Heating:EnergyTransfer:Zone:CORE_RETAIL 3.20 0.00 01-JAN-00:10 59216.50 01-JAN-08:20
Cooling:EnergyTransfer:Zone:CORE_RETAIL 622.09 0.00 01-JAN-00:10 81781.47 12-JUN-06:10
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL 622.09 0.00 01-JAN-00:10 81781.47 12-JUN-06:10
EnergyTransfer:Zone:POINT_OF_SALE 157.06 0.00 01-JAN-00:10 16065.45 09-MAY-04:10
Heating:EnergyTransfer:Zone:POINT_OF_SALE 0.12 0.00 01-JAN-00:10 7591.43 01-JAN-07:10
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE 0.12 0.00 01-JAN-00:10 7591.43 01-JAN-07:10
Cooling:EnergyTransfer:Zone:POINT_OF_SALE 156.94 0.00 01-JAN-00:10 16065.45 09-MAY-04:10
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE 156.94 0.00 01-JAN-00:10 16065.45 09-MAY-04:10
EnergyTransfer:Zone:FRONT_RETAIL 125.88 0.00 01-JAN-00:10 15532.45 13-JUN-04:10
Heating:EnergyTransfer:Zone:FRONT_RETAIL 0.30 0.00 01-JAN-00:10 9744.52 01-JAN-07:10
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL 0.30 0.00 01-JAN-00:10 9744.52 01-JAN-07:10
Cooling:EnergyTransfer:Zone:FRONT_RETAIL 125.58 0.00 01-JAN-00:10 15532.45 13-JUN-04:10
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL 125.58 0.00 01-JAN-00:10 15532.45 13-JUN-04:10
EnergyTransfer:Zone:FRONT_ENTRY 0.02 0.00 01-JAN-00:10 2150.72 03-JAN-08:20
Heating:EnergyTransfer:Zone:FRONT_ENTRY 0.02 0.00 01-JAN-00:10 2150.72 03-JAN-08:20
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY 0.02 0.00 01-JAN-00:10 2150.72 03-JAN-08:20
Cooling:EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:HVAC 1973.72 0.00 01-JAN-00:10 265376.83 01-JUL-16:00
HeatingCoils:EnergyTransfer 17.93 0.00 01-JAN-00:10 101962.25 02-JAN-06:20
CoolingCoils:EnergyTransfer 1955.79 0.00 01-JAN-00:10 265376.83 01-JUL-16:00
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BACK_SPACE 0.000 0.000 7.590 -174.512 0.000 0.000 5.029 10.830 49.772 0.000 0.000 0.547 101.071 0.000 0.000 0.000 -0.326 -0.008
CORE_RETAIL 0.000 0.000 3.196 -622.079 0.000 0.000 155.918 168.308 83.928 43.586 0.000 0.488 179.078 0.000 -12.098 0.000 -0.325 -0.011
POINT_OF_SALE 0.000 0.000 0.119 -156.942 0.000 0.000 14.600 20.870 52.690 36.527 0.000 0.241 41.758 0.000 -9.656 0.000 -0.206 -0.001
FRONT_RETAIL 0.000 0.000 0.298 -125.581 0.000 0.000 14.648 20.870 7.908 36.449 0.000 0.246 54.624 0.000 -9.271 0.000 -0.189 -0.000
FRONT_ENTRY 0.021 0.000 0.000 0.000 0.000 0.000 0.739 0.631 0.000 6.600 0.000 3.426 0.000 0.000 -2.042 0.000 -5.380 -3.996
Total Facility 0.021 0.000 11.202 -1079.114 0.000 0.000 190.934 221.508 194.299 123.161 0.000 4.947 376.532 0.000 -33.067 0.000 -6.426 -4.016


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BACK_SPACE 03-MAY-04:01 0.00 0.00 0.00 -48419.34 0.00 0.00 0.00 81.78 605.09 0.00 0.00 0.00 47732.47 0.00 -0.00 0.00 0.00 0.00
CORE_RETAIL 28-APR-05:01 0.00 0.00 0.00 -186244.23 0.00 0.00 0.00 344.55 1020.33 0.00 0.00 0.03 185597.06 0.00 -717.74 0.00 0.00 0.00
POINT_OF_SALE 23-OCT-04:01 0.00 0.00 0.00 -31713.78 0.00 0.00 0.00 32.47 640.56 0.00 0.00 0.00 32068.36 0.00 -1016.79 0.00 -10.81 0.00
FRONT_RETAIL 23-OCT-04:01 0.00 0.00 0.00 -27836.38 0.00 0.00 0.00 32.47 96.14 0.00 0.00 0.00 28693.23 0.00 -975.39 0.00 -10.07 0.00
FRONT_ENTRY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 06-MAY-04:01 0.00 0.00 0.00 -285913.71 0.00 0.00 0.00 493.85 1771.59 0.00 0.00 49.33 284683.85 0.00 -1083.77 0.00 -1.13 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BACK_SPACE 25-DEC-07:01 0.00 0.00 53840.44 0.00 0.00 0.00 0.00 41.25 453.82 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -93.53 -54241.97
CORE_RETAIL 01-JAN-08:12 0.00 0.00 192871.89 0.00 0.00 0.00 0.00 344.55 765.25 0.00 0.00 0.00 0.00 0.00 -434.00 0.00 -1.36 -193546.33
POINT_OF_SALE 01-JAN-07:01 0.00 0.00 28662.16 0.00 0.00 0.00 0.00 32.47 480.42 0.00 0.00 0.00 0.00 0.00 -1109.46 0.00 0.00 -28065.59
FRONT_RETAIL 17-JAN-05:02 0.00 0.00 28747.39 0.00 0.00 0.00 0.00 32.47 96.14 0.00 0.00 0.00 0.00 0.00 -806.17 0.00 0.00 -28069.83
FRONT_ENTRY 03-JAN-08:05 3353.65 0.00 0.00 0.00 0.00 0.00 36.17 19.89 0.00 64.64 0.00 0.00 0.00 0.00 -0.00 0.00 -2468.32 -1006.03
Total Facility 01-JAN-08:12 0.00 0.00 214302.57 0.00 0.00 0.00 0.00 453.21 1771.59 293.28 0.00 0.00 0.00 0.00 -434.00 0.00 -1321.53 -215065.13



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 2.4872 0.0000 8.1781 1.0000 Calculated from schedules 0.2316 2.4872 0.0931 1.0000 Not calculated 0.2316 0.0931    
PSZ-AC:2 8.2142 0.0000 258.4342 1.0000 Calculated from schedules 1.8903 8.4030 0.2250 1.0000 Not calculated 1.8903 0.2250    
PSZ-AC:3 1.5030 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.5030 0.1185 1.0000 Not calculated 0.1781 0.1185    
PSZ-AC:4 1.3101 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.3101 0.1360 1.0000 Not calculated 0.1781 0.1360    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 2.4872 0.0000 8.1781 1.0000 Calculated from schedules 0.2316 2.4872 1.0000 1.0000 Not calculated 0.2316 0.0931    
PSZ-AC:2 8.2142 0.0000 258.4342 1.0000 Calculated from schedules 1.8903 8.2142 1.0000 1.0000 Not calculated 1.8903 0.2301    
PSZ-AC:3 1.5030 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.5030 1.0000 1.0000 Not calculated 0.1781 0.1185    
PSZ-AC:4 1.3101 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.3101 1.0000 1.0000 Not calculated 0.1781 0.1360    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BACK_SPACE PSZ-AC:1 0.000000 8.1781 0.000610 379.89 0.2316 1.0000 0.2316 1.000 0.2316
CORE_RETAIL PSZ-AC:2 0.000000 258.4342 0.001181 1600.48 1.8903 1.0000 1.8903 1.000 1.8903
POINT_OF_SALE PSZ-AC:3 0.000000 24.3517 0.001181 150.81 0.1781 1.0000 0.1781 1.000 0.1781
FRONT_RETAIL PSZ-AC:4 0.000000 24.3517 0.001181 150.81 0.1781 1.0000 0.1781 1.000 0.1781


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.18 0.000610 379.8900 0.2316 0.2316 0.2316
PSZ-AC:2 0.000000 258.43 0.001181 1600.4829 1.8903 1.8903 1.8903
PSZ-AC:3 0.000000 24.35 0.001181 150.8100 0.1781 0.1781 0.1781
PSZ-AC:4 0.000000 24.35 0.001181 150.8100 0.1781 0.1781 0.1781


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BACK_SPACE PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 2.4872 2.4872 2.4872 No 0.2316 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_RETAIL PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 8.2142 8.2142 8.2142 No 1.8903 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
POINT_OF_SALE PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.5030 1.5030 1.5030 No 0.1781 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FRONT_RETAIL PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3101 1.3101 1.3101 No 0.1781 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 2.4872 2.4872 2.4872 2.4872 0.2316 1.0000
PSZ-AC:2 8.2142 8.4030 8.2142 8.2142 1.8903 1.0000
PSZ-AC:3 1.5030 1.5030 1.5030 1.5030 0.1781 1.0000
PSZ-AC:4 1.3101 1.3101 1.3101 1.3101 0.1781 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BACK_SPACE PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 2.4872 2.4872 2.4872 No 0.2316 0.1925 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_RETAIL PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 8.2142 8.2142 8.2142 No 1.8903 0.7388 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
POINT_OF_SALE PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.5030 1.5030 1.5030 No 0.1781 0.3275 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FRONT_RETAIL PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3101 1.3101 1.3101 No 0.1781 0.3277 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 2.4872 2.4872 2.4872 2.4872 0.2316 1.0000
PSZ-AC:2 8.2142 8.2142 8.2142 8.2142 1.8903 1.0000
PSZ-AC:3 1.5030 1.5030 1.5030 1.5030 0.1781 1.0000
PSZ-AC:4 1.3101 1.3101 1.3101 1.3101 0.1781 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Total gross floor area [m2] 2293.99
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BACK_SPACE 379.89 379.89 0.00 94.22
CORE_RETAIL 1600.48 1600.48 0.00 94.22
POINT_OF_SALE 150.81 150.81 0.00 94.22
FRONT_RETAIL 150.81 150.81 0.00 94.22
FRONT_ENTRY 12.00 12.00 0.00 94.22
Totals 2293.99 2293.99 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 50.33
Number of hours cooling loads not met 0.00
Number of hours not met 50.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 5.65 31202.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 554.93 80683.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 221.51 20135.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 43.60 3820.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 194.30 10740.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 165.05 15062.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 19.20 1995.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 194.30 1204.24
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 194.30 1204.24


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 96.56
Space Heating 2.46
Space Cooling 241.91
Fans (All) 71.95
Service Water Heating 8.37
Receptacle Equipment 84.70
Miscellaneous (All) 524.95
Subtotal 524.95


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 18.39
Space Heating 0.47
Space Cooling 46.08
Fans (All) 13.71
Service Water Heating 1.59
Receptacle Equipment 16.13
Miscellaneous 3.62


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
FRONTENTRY_COILSCHED 8760. 8760.
FRONTENTRY_FANSCHED 8760. 8760.
LTG_SCH_ENTRY 1985. 8760.
LTG_SCH_CORE 3609. 8760.
LTG_SCH_BACK 1677. 8760.
LTG_SCH_SALE 3609. 8760.
LTG_SCH_FRONT 3609. 8760.
BLDG_OCC_SCH 2410. 4950.
BLDG_EQUIP_SCH 4552. 8760.
BLDG_ELEVATORS 2743. 4950.
INFIL_SCH 3551. 3551.
INFIL_HALF_ON_SCH 6156. 8760.
INFIL_DOOR_OPENING_SCH 2505. 4380.
BLDG_SWH_SCH 2009. 4950.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6543. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4950. 4950.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
INFIL_SCH_PNNL 4774. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4950. 4950.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
SZ_SYSTEM_OA_MAX_FRAC_SCH 6570. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_FRONTENTRY_STD2013 FRONT_ENTRY HEATING SP January 16.00 365 15.56 365
HTGSETP_SCH_NO_OPTIMUM BACK_SPACE DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM BACK_SPACE DUAL SP CONTROL July 23.89 365 29.44 365
HTGSETP_SCH_YES_OPTIMUM CORE_RETAIL DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM CORE_RETAIL DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BACK_SPACE 7439.17 1320.83 0.00 0.00 0.00
CORE_RETAIL 7505.67 1254.33 0.00 0.00 0.00
POINT_OF_SALE 6899.83 1860.17 0.00 0.00 0.00
FRONT_RETAIL 7090.33 1669.67 0.00 0.00 0.00
FRONT_ENTRY 3341.50 2304.33 2496.67 617.50 0.00
Min 3341.50 1254.33 0.00 0.00 0.00
Max 7505.67 2304.33 2496.67 617.50 0.00
Average 6455.30 1681.87 499.33 123.50 0.00
Sum 32276.50 8409.33 2496.67 617.50 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BACK_SPACE 16872.00 0.00 0.00 0.00 0.00
CORE_RETAIL 609599.00 0.00 0.00 0.00 0.00
POINT_OF_SALE 56000.00 0.00 0.00 0.00 0.00
FRONT_RETAIL 56000.00 0.00 0.00 0.00 0.00
FRONT_ENTRY 656.67 416.17 512.17 335.00 0.00
Min 656.67 0.00 0.00 0.00 0.00
Max 609599.00 416.17 512.17 335.00 0.00
Average 147825.53 83.23 102.43 67.00 0.00
Sum 739127.67 416.17 512.17 335.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BACK_SPACE 7302.50 1457.50 0.00 0.00 0.00
CORE_RETAIL 6511.17 2248.83 0.00 0.00 0.00
POINT_OF_SALE 6932.83 1827.17 0.00 0.00 0.00
FRONT_RETAIL 6953.50 1806.50 0.00 0.00 0.00
FRONT_ENTRY 3183.67 3060.33 2067.50 437.00 11.50
Min 3183.67 1457.50 0.00 0.00 0.00
Max 7302.50 3060.33 2067.50 437.00 11.50
Average 6176.73 2080.07 413.50 87.40 2.30
Sum 30883.67 10400.33 2067.50 437.00 11.50


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BACK_SPACE 16806.50 65.50 0.00 0.00 0.00
CORE_RETAIL 550847.00 58752.00 0.00 0.00 0.00
POINT_OF_SALE 55900.33 99.67 0.00 0.00 0.00
FRONT_RETAIL 55062.67 937.33 0.00 0.00 0.00
FRONT_ENTRY 655.67 560.83 461.00 234.33 8.17
Min 655.67 65.50 0.00 0.00 0.00
Max 550847.00 58752.00 461.00 234.33 8.17
Average 135854.43 12083.07 92.20 46.87 1.63
Sum 679272.17 60415.33 461.00 234.33 8.17


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:03

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BACK_SPACE 0.00 0.00 0.00 0.00
CORE_RETAIL 0.00 0.00 0.00 8760.00
POINT_OF_SALE 0.00 0.00 0.00 0.00
FRONT_RETAIL 0.00 0.00 0.00 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 8760.00
Average 0.00 0.00 0.00 1752.00
Sum 0.00 0.00 0.00 8760.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BACK_SPACE 0.00 0.00 0.00 0.00
CORE_RETAIL 0.00 0.00 0.00 609599.00
POINT_OF_SALE 0.00 0.00 0.00 0.00
FRONT_RETAIL 0.00 0.00 0.00 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 609599.00
Average 0.00 0.00 0.00 121919.80
Sum 0.00 0.00 0.00 609599.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.144109E+09 2129.80 13-JAN-06:10 9.98 9.13 0.230275E+09 320.03 14-JAN-16:00 20.70 14.72
February 0.795657E+09 3841.40 24-FEB-17:00 25.60 17.28 0.240565E+09 329.81 08-FEB-15:39 25.60 17.28
March 0.660071E+10 46215.91 27-MAR-04:01 20.78 13.92 0.302546E+09 326.82 10-MAR-15:00 20.78 13.92
April 0.185498E+11 47993.08 30-APR-06:01 23.07 14.85 0.287508E+09 326.82 01-APR-11:00 23.07 14.85
May 0.287741E+11 48418.21 03-MAY-04:01 25.78 20.40 0.297660E+09 326.85 06-MAY-13:39 41.43 19.96
June 0.291573E+11 46869.66 05-JUN-04:01 30.32 20.26 0.293539E+09 326.85 03-JUN-10:00 30.32 20.26
July 0.283957E+11 45051.77 01-JUL-04:01 29.80 24.06 0.291628E+09 326.84 20-JUL-14:30 34.40 26.59
August 0.257877E+11 43946.62 09-AUG-04:01 30.32 25.72 0.304131E+09 326.84 30-AUG-14:00 33.40 25.93
September 0.197468E+11 44580.43 27-SEP-04:01 23.75 21.11 0.287512E+09 326.84 02-SEP-15:00 23.75 21.11
October 0.131627E+11 47014.69 23-OCT-04:01 18.78 14.95 0.291184E+09 326.82 07-OCT-11:30 18.78 14.95
November 0.315310E+10 40295.61 01-NOV-04:01 15.75 12.60 0.275913E+09 326.81 07-NOV-15:00 28.10 18.13
December 0.245613E+09 2143.31 05-DEC-06:10 10.00 9.32 0.243863E+09 328.98 01-DEC-15:20 10.00 9.32
                     
Annual Sum or Average 0.174513E+12         0.334632E+10        
Minimum of Months 0.144109E+09 2129.80   9.98 9.13 0.230275E+09 320.03   10.00 9.32
Maximum of Months 0.291573E+11 48418.21   30.32 25.72 0.304131E+09 329.81   41.43 26.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.149028E+11 33114.04 05-JAN-07:05 4.93 4.82 0.844655E+10 10327.40 28-JAN-16:10 18.07 11.45
February 0.212292E+11 32444.24 23-FEB-16:00 24.80 14.35 0.818499E+10 10327.77 21-FEB-15:39 24.80 14.35
March 0.429645E+11 155301.22 30-MAR-06:02 21.25 16.72 0.959868E+10 10327.95 11-MAR-11:30 21.25 16.72
April 0.666570E+11 186238.15 28-APR-05:01 27.22 17.16 0.908891E+10 10328.36 27-APR-14:39 27.22 17.16
May 0.836194E+11 183814.37 06-MAY-04:01 30.18 17.72 0.941014E+10 10328.55 06-MAY-15:09 41.68 19.96
June 0.805832E+11 166335.13 07-JUN-04:01 33.27 20.24 0.927982E+10 10328.18 07-JUN-14:50 44.40 21.49
July 0.748454E+11 149089.24 05-JUL-04:01 32.58 25.33 0.921954E+10 10328.14 12-JUL-14:39 27.87 25.10
August 0.706055E+11 136671.80 07-AUG-05:01 29.53 24.79 0.961454E+10 10327.96 19-AUG-15:00 26.30 25.38
September 0.609816E+11 143571.05 26-SEP-05:02 25.12 20.63 0.908934E+10 10328.12 30-SEP-12:09 33.53 23.69
October 0.538603E+11 158858.76 16-OCT-06:03 21.32 15.13 0.920384E+10 10327.99 14-OCT-12:30 21.32 15.13
November 0.331894E+11 39451.02 09-NOV-15:20 28.93 17.66 0.881482E+10 10327.94 08-NOV-15:00 28.93 17.66
December 0.186488E+11 31880.79 21-DEC-07:05 5.68 4.75 0.878164E+10 10327.67 01-DEC-15:00 5.68 4.75
                     
Annual Sum or Average 0.622087E+12         0.108733E+12        
Minimum of Months 0.149028E+11 31880.79   4.93 4.75 0.818499E+10 10327.40   5.68 4.75
Maximum of Months 0.836194E+11 186238.15   33.27 25.33 0.961454E+10 10328.55   44.40 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.488512E+10 7965.33 12-JAN-15:50 23.35 14.44 0.842844E+09 973.21 14-JAN-13:00 21.60 15.18
February 0.659090E+10 28757.52 23-FEB-05:02 15.08 13.22 0.783296E+09 973.21 13-FEB-15:39 15.08 13.22
March 0.112918E+11 31023.30 29-MAR-04:01 21.45 17.80 0.905493E+09 973.25 29-MAR-14:00 33.10 19.05
April 0.154561E+11 31052.32 05-APR-04:01 20.68 15.17 0.856120E+09 973.33 20-APR-14:30 37.05 19.66
May 0.181141E+11 30642.07 09-MAY-04:01 27.65 19.17 0.886340E+09 973.29 06-MAY-11:50 27.65 19.17
June 0.174615E+11 29560.45 05-JUN-04:01 30.32 20.26 0.874065E+09 973.31 02-JUN-14:00 30.32 20.26
July 0.170796E+11 27072.49 01-JUL-04:01 29.80 24.06 0.868372E+09 973.26 26-JUL-14:00 30.70 25.75
August 0.165717E+11 26268.30 03-AUG-04:01 28.73 23.54 0.905595E+09 973.27 10-AUG-14:39 26.63 25.80
September 0.153125E+11 29263.27 27-SEP-04:01 23.75 21.11 0.856117E+09 973.29 30-SEP-10:39 31.77 23.65
October 0.159862E+11 31713.08 23-OCT-04:01 18.78 14.95 0.867087E+09 973.33 18-OCT-14:20 18.78 14.95
November 0.117915E+11 30605.34 02-NOV-04:01 16.58 13.43 0.833933E+09 973.20 18-NOV-11:30 25.00 17.42
December 0.640164E+10 12865.79 29-DEC-05:03 16.42 12.56 0.858331E+09 973.21 15-DEC-15:30 16.42 12.56
                     
Annual Sum or Average 0.156943E+12         0.103376E+11        
Minimum of Months 0.488512E+10 7965.33   15.08 12.56 0.783296E+09 973.20   15.08 12.56
Maximum of Months 0.181141E+11 31713.08   30.32 24.06 0.905595E+09 973.33   37.05 25.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288448E+10 5982.47 12-JAN-15:40 23.40 14.39 0.819660E+09 973.18 07-JAN-16:00 23.40 14.39
February 0.453565E+10 25067.25 23-FEB-05:02 15.08 13.22 0.772282E+09 973.19 08-FEB-15:00 15.08 13.22
March 0.862839E+10 26918.87 27-MAR-04:01 20.78 13.92 0.904670E+09 973.22 29-MAR-14:00 33.10 19.05
April 0.127875E+11 27717.78 29-APR-04:01 26.47 18.00 0.856117E+09 973.31 20-APR-14:00 26.47 18.00
May 0.152630E+11 27300.40 09-MAY-04:01 27.65 19.17 0.886333E+09 973.28 27-MAY-11:00 39.70 20.30
June 0.144697E+11 25700.17 05-JUN-04:01 30.32 20.26 0.874059E+09 973.27 02-JUN-14:00 30.32 20.26
July 0.142010E+11 23808.40 01-JUL-04:01 29.80 24.06 0.868365E+09 973.24 29-JUL-11:39 31.80 26.87
August 0.136618E+11 23030.71 09-AUG-04:01 30.32 25.72 0.905591E+09 973.25 21-AUG-14:20 28.90 27.60
September 0.125410E+11 25113.79 27-SEP-04:01 23.75 21.11 0.856109E+09 973.25 30-SEP-10:39 31.77 23.65
October 0.132512E+11 27836.25 23-OCT-04:01 18.78 14.95 0.867077E+09 973.31 18-OCT-14:30 18.78 14.95
November 0.921344E+10 26648.36 02-NOV-04:01 16.58 13.43 0.833166E+09 973.21 18-NOV-11:50 25.47 17.40
December 0.414520E+10 7585.76 01-DEC-15:30 22.85 13.56 0.846424E+09 973.20 18-DEC-15:00 21.10 14.78
                     
Annual Sum or Average 0.125582E+12         0.102899E+11        
Minimum of Months 0.288448E+10 5982.47   15.08 13.22 0.772282E+09 973.18   15.08 13.22
Maximum of Months 0.152630E+11 27836.25   30.32 25.72 0.905591E+09 973.31   39.70 27.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83 7.49 43336724.52 78.40 12-JAN-15:09 23.55 14.25
February 0.00 0.00 01-FEB-00:10 9.73 7.85 54867632.37 104.52 22-FEB-15:09 27.00 16.16
March 0.00 0.00 01-MAR-00:10 15.55 12.96 93454363.12 180.07 28-MAR-14:00 35.60 18.50
April 0.00 0.00 01-APR-00:10 23.70 16.77 0.130750E+09 186.05 13-APR-14:00 36.50 19.35
May 0.00 0.00 01-MAY-00:10 30.53 18.24 0.150992E+09 186.05 01-MAY-14:09 43.87 21.97
June 0.00 0.00 01-JUN-00:10 28.05 22.58 0.147022E+09 186.05 02-JUN-14:09 38.28 20.75
July 0.00 0.00 01-JUL-00:10 32.95 24.65 0.133668E+09 186.05 01-JUL-11:20 37.50 27.66
August 0.00 0.00 01-AUG-00:10 29.32 26.26 0.131763E+09 186.05 07-AUG-14:09 37.22 26.32
September 0.00 0.00 01-SEP-00:10 28.43 25.91 0.119997E+09 186.00 26-SEP-14:00 36.10 22.69
October 0.00 0.00 01-OCT-00:10 26.58 21.85 0.111252E+09 186.05 02-OCT-14:09 36.40 21.05
November 0.00 0.00 01-NOV-00:10 17.72 15.09 79113571.43 131.90 04-NOV-14:09 30.28 17.23
December 0.00 0.00 01-DEC-00:10 12.50 9.11 48985892.83 84.88 28-DEC-15:09 24.38 15.36
                     
Annual Sum or Average 0.00         0.124520E+10        
Minimum of Months 0.00 0.00   7.83 7.49 43336724.52 78.40   23.55 14.25
Maximum of Months 0.00 0.00   32.95 26.26 0.150992E+09 186.05   43.87 27.66



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.421289E+10 51066.70 17-JAN-05:02 10.95
February 0.108272E+10 51039.61 12-FEB-07:02 11.22
March 16422710.86 841.63 26-MAR-08:55 23.00
April 1758051.93 760.95 01-APR-05:10 23.02
May 0.00 0.00 01-MAY-00:10 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:10 32.95
August 0.00 0.00 01-AUG-00:10 29.32
September 0.00 0.00 01-SEP-00:10 28.43
October 0.00 0.00 01-OCT-00:10 26.58
November 0.107482E+09 17138.12 26-NOV-08:61 13.92
December 0.216863E+10 53840.76 25-DEC-07:01 12.18
         
Annual Sum or Average 0.758989E+10      
Minimum of Months 0.00 0.00   10.95
Maximum of Months 0.421289E+10 53840.76   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124063E+10 192875.05 01-JAN-08:12 8.33
February 0.172490E+09 145429.66 11-FEB-07:03 9.97
March 10868162.98 7423.33 11-MAR-07:06 23.87
April 0.148089E+09 22065.63 16-APR-08:06 30.70
May 0.262746E+09 26190.85 01-MAY-06:06 32.80
June 0.256252E+09 26518.66 07-JUN-06:06 33.87
July 0.257767E+09 21657.54 02-JUL-07:20 33.63
August 0.256934E+09 16852.90 09-AUG-05:06 29.90
September 0.198659E+09 12936.97 12-SEP-06:08 27.02
October 58814906.58 11204.47 04-OCT-06:06 25.52
November 1890378.73 1457.03 26-NOV-10:05 22.08
December 0.330601E+09 151311.25 23-DEC-07:03 6.25
         
Annual Sum or Average 0.319574E+10      
Minimum of Months 1890378.73 1457.03   6.25
Maximum of Months 0.124063E+10 192875.05   33.87



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 99527703.24 28662.90 01-JAN-07:01 7.25
February 16364018.99 21535.01 11-FEB-05:02 9.03
March 0.00 0.00 01-MAR-00:10 15.55
April 373804.89 473.60 23-APR-07:07 22.45
May 403566.83 1929.25 02-MAY-05:04 29.28
June 218824.96 1656.44 09-JUN-05:06 31.20
July 320492.90 1923.63 08-JUL-05:06 31.70
August 74997.93 874.98 09-AUG-05:06 29.90
September 0.00 0.00 01-SEP-00:10 28.43
October 0.00 0.00 01-OCT-00:10 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 1231254.45 2673.64 31-DEC-08:62 6.52
         
Annual Sum or Average 0.118515E+09      
Minimum of Months 0.00 0.00   6.52
Maximum of Months 99527703.24 28662.90   31.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234007E+09 28748.70 17-JAN-05:02 10.95
February 42299709.11 26814.03 11-FEB-05:02 9.03
March 0.00 0.00 01-MAR-00:10 15.55
April 26758.53 133.79 23-APR-07:03 22.45
May 0.00 0.00 01-MAY-00:10 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 38070.78 444.16 07-JUL-05:06 31.52
August 0.00 0.00 01-AUG-00:10 29.32
September 0.00 0.00 01-SEP-00:10 28.43
October 0.00 0.00 01-OCT-00:10 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 21175216.56 20349.58 31-DEC-07:01 5.53
         
Annual Sum or Average 0.297547E+09      
Minimum of Months 0.00 0.00   5.53
Maximum of Months 0.234007E+09 28748.70   31.52



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 12914153.33 3355.60 03-JAN-08:05 6.40
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:10 23.70
May 0.00 0.00 01-MAY-00:10 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:10 32.95
August 0.00 0.00 01-AUG-00:10 29.32
September 0.00 0.00 01-SEP-00:10 28.43
October 0.00 0.00 01-OCT-00:10 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 7798150.08 2744.63 21-DEC-08:04 6.25
         
Annual Sum or Average 20712303.41      
Minimum of Months 0.00 0.00   6.25
Maximum of Months 12914153.33 3355.60   32.95



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.906964E+09 742.55 02-JAN-09:09 0.419292E+10 2751.42 02-JAN-09:09
February 0.826011E+09 742.55 01-FEB-09:09 0.380401E+10 2751.42 01-FEB-09:09
March 0.943673E+09 742.55 01-MAR-09:09 0.429860E+10 2751.42 01-MAR-09:09
April 0.889382E+09 742.55 01-APR-09:09 0.408537E+10 2751.42 01-APR-09:09
May 0.924906E+09 742.55 01-MAY-08:09 0.424576E+10 2751.42 01-MAY-08:09
June 0.910287E+09 742.55 01-JUN-08:09 0.415080E+10 2751.42 01-JUN-08:09
July 0.904343E+09 742.55 01-JUL-09:09 0.417978E+10 2751.42 01-JUL-09:09
August 0.943527E+09 742.55 01-AUG-08:09 0.429860E+10 2751.42 01-AUG-08:09
September 0.889382E+09 742.55 01-SEP-08:09 0.408428E+10 2751.42 01-SEP-08:09
October 0.907110E+09 742.55 02-OCT-08:09 0.419346E+10 2751.42 02-OCT-08:09
November 0.879167E+09 742.55 01-NOV-08:09 0.405935E+10 2751.42 01-NOV-08:09
December 0.904973E+09 742.55 01-DEC-09:09 0.417924E+10 2751.42 01-DEC-09:09
             
Annual Sum or Average 0.108297E+11     0.497722E+11    
Minimum of Months 0.826011E+09 742.55   0.380401E+10 2751.42  
Maximum of Months 0.943673E+09 742.55   0.429860E+10 2751.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.155839E+11 16279.92 02-JAN-17:40 0.707031E+10 4639.58 02-JAN-09:09
February 0.134830E+11 16279.92 01-FEB-17:00 0.641452E+10 4639.58 01-FEB-09:09
March 0.140141E+11 15837.37 04-MAR-17:00 0.724851E+10 4639.58 01-MAR-09:09
April 0.135259E+11 14786.79 22-APR-16:00 0.688896E+10 4639.58 01-APR-09:09
May 0.140353E+11 15172.20 31-MAY-16:00 0.715941E+10 4639.58 01-MAY-08:09
June 0.134629E+11 14310.65 24-JUN-09:09 0.699930E+10 4639.58 01-JUN-08:09
July 0.126846E+11 15127.28 27-JUL-16:00 0.704816E+10 4639.58 01-JUL-09:09
August 0.133729E+11 15180.22 19-AUG-16:00 0.724851E+10 4639.58 01-AUG-08:09
September 0.128922E+11 15381.07 08-SEP-16:00 0.688712E+10 4639.58 01-SEP-08:09
October 0.144053E+11 15905.67 25-OCT-16:00 0.707123E+10 4639.58 02-OCT-08:09
November 0.151235E+11 16279.92 06-NOV-17:30 0.684509E+10 4639.58 01-NOV-08:09
December 0.157242E+11 16279.92 01-DEC-17:19 0.704724E+10 4639.58 01-DEC-09:09
             
Annual Sum or Average 0.168308E+12     0.839284E+11    
Minimum of Months 0.126846E+11 14310.65   0.641452E+10 4639.58  
Maximum of Months 0.157242E+11 16279.92   0.724851E+10 4639.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.174880E+10 1534.02 02-JAN-09:09 0.443872E+10 2912.71 02-JAN-09:09
February 0.159209E+10 1534.02 01-FEB-09:09 0.402701E+10 2912.71 01-FEB-09:09
March 0.181792E+10 1534.02 01-MAR-09:09 0.455059E+10 2912.71 01-MAR-09:09
April 0.171452E+10 1534.02 01-APR-09:09 0.432486E+10 2912.71 01-APR-09:09
May 0.178336E+10 1534.02 01-MAY-08:09 0.449465E+10 2912.71 01-MAY-08:09
June 0.175416E+10 1534.02 01-JUN-08:09 0.439413E+10 2912.71 01-JUN-08:09
July 0.174372E+10 1534.02 01-JUL-09:09 0.442481E+10 2912.71 01-JUL-09:09
August 0.181792E+10 1534.02 01-AUG-08:09 0.455059E+10 2912.71 01-AUG-08:09
September 0.171452E+10 1534.02 01-SEP-08:09 0.432371E+10 2912.71 01-SEP-08:09
October 0.174880E+10 1534.02 02-OCT-08:09 0.443929E+10 2912.71 02-OCT-08:09
November 0.169012E+10 1534.02 01-NOV-08:09 0.429732E+10 2912.71 01-NOV-08:09
December 0.174372E+10 1534.02 01-DEC-09:09 0.442423E+10 2912.71 01-DEC-09:09
             
Annual Sum or Average 0.208697E+11     0.526899E+11    
Minimum of Months 0.159209E+10 1534.02   0.402701E+10 2912.71  
Maximum of Months 0.181792E+10 1534.02   0.455059E+10 2912.71  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.174880E+10 1534.02 02-JAN-09:09 0.666220E+09 437.18 02-JAN-09:09
February 0.159209E+10 1534.02 01-FEB-09:09 0.604426E+09 437.18 01-FEB-09:09
March 0.181792E+10 1534.02 01-MAR-09:09 0.683011E+09 437.18 01-MAR-09:09
April 0.171452E+10 1534.02 01-APR-09:09 0.649132E+09 437.18 01-APR-09:09
May 0.178336E+10 1534.02 01-MAY-08:09 0.674616E+09 437.18 01-MAY-08:09
June 0.175416E+10 1534.02 01-JUN-08:09 0.659528E+09 437.18 01-JUN-08:09
July 0.174372E+10 1534.02 01-JUL-09:09 0.664132E+09 437.18 01-JUL-09:09
August 0.181792E+10 1534.02 01-AUG-08:09 0.683011E+09 437.18 01-AUG-08:09
September 0.171452E+10 1534.02 01-SEP-08:09 0.648959E+09 437.18 01-SEP-08:09
October 0.174880E+10 1534.02 02-OCT-08:09 0.666307E+09 437.18 02-OCT-08:09
November 0.169012E+10 1534.02 01-NOV-08:09 0.644998E+09 437.18 01-NOV-08:09
December 0.174372E+10 1534.02 01-DEC-09:09 0.664046E+09 437.18 01-DEC-09:09
             
Annual Sum or Average 0.208697E+11     0.790839E+10    
Minimum of Months 0.159209E+10 1534.02   0.604426E+09 437.18  
Maximum of Months 0.181792E+10 1534.02   0.683011E+09 437.18  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 52953287.74 44.76 02-JAN-09:09 0.00 0.00
February 48182266.45 44.76 01-FEB-09:09 0.00 0.00
March 54927912.53 44.76 01-MAR-09:09 0.00 0.00
April 51865380.39 44.76 01-APR-09:09 0.00 0.00
May 53941762.61 44.76 01-MAY-08:09 0.00 0.00
June 53008506.70 44.76 01-JUN-08:09 0.00 0.00
July 52802317.57 44.76 01-JUL-09:09 0.00 0.00
August 54927563.77 44.76 01-AUG-08:09 0.00 0.00
September 51865380.39 44.76 01-SEP-08:09 0.00 0.00
October 52953636.50 44.76 02-OCT-08:09 0.00 0.00
November 51191943.51 44.76 01-NOV-08:09 0.00 0.00
December 52796660.11 44.76 01-DEC-09:09 0.00 0.00
           
Annual Sum or Average 0.631417E+09     0.00 0.00
Minimum of Months 48182266.45 44.76   0.00 0.00
Maximum of Months 54927912.53 44.76   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.699524E+09 0.906964E+09 0.419292E+10 0.00 0.00 0.00 0.00 146320.99 63177166.83
February 0.638757E+09 0.826011E+09 0.380401E+10 0.00 0.00 0.00 0.00 1789605.45 81047203.56
March 0.730614E+09 0.943673E+09 0.429860E+10 0.00 0.00 0.00 0.00 17668236.73 66843906.57
April 0.690691E+09 0.889382E+09 0.408537E+10 0.00 0.00 0.00 0.00 67293064.62 6977901.55
May 0.715069E+09 0.924906E+09 0.424576E+10 0.00 0.00 0.00 0.00 0.124142E+09 6511894.48
June 0.705176E+09 0.910287E+09 0.415080E+10 0.00 0.00 0.00 0.00 95417762.45 1969164.26
July 0.700584E+09 0.904343E+09 0.417978E+10 0.00 0.00 0.00 0.00 0.108650E+09 2021116.11
August 0.730614E+09 0.943527E+09 0.429860E+10 0.00 0.00 0.00 0.00 64163463.12 3303508.30
September 0.690691E+09 0.889382E+09 0.408428E+10 0.00 0.00 0.00 0.00 41419500.65 3722207.92
October 0.699524E+09 0.907110E+09 0.419346E+10 0.00 0.00 0.00 0.00 20609624.54 6396739.73
November 0.673027E+09 0.879167E+09 0.405935E+10 0.00 0.00 0.00 0.00 4965920.33 19625005.79
December 0.700584E+09 0.904973E+09 0.417924E+10 0.00 0.00 0.00 0.00 341029.25 64520917.82
                   
Annual Sum or Average 0.837485E+10 0.108297E+11 0.497722E+11 0.00 0.00 0.00 0.00 0.546607E+09 0.326117E+09
Minimum of Months 0.638757E+09 0.826011E+09 0.380401E+10 0.00 0.00 0.00 0.00 146320.99 1969164.26
Maximum of Months 0.730614E+09 0.943673E+09 0.429860E+10 0.00 0.00 0.00 0.00 0.124142E+09 81047203.56



Table of Contents

Report: SpaceGainsMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.221054E+11 0.155839E+11 0.707031E+10 0.00 0.00 0.00 0.00 0.00 68889346.31
February 0.201852E+11 0.134830E+11 0.641452E+10 0.00 0.00 0.00 0.00 1191131.89 83496426.59
March 0.230879E+11 0.140141E+11 0.724851E+10 0.00 0.00 0.00 0.00 15184313.10 63876559.62
April 0.218263E+11 0.135259E+11 0.688896E+10 0.00 0.00 0.00 0.00 57842490.02 6306566.30
May 0.225967E+11 0.140353E+11 0.715941E+10 0.00 0.00 0.00 0.00 0.110468E+09 3630505.33
June 0.222841E+11 0.134629E+11 0.699930E+10 0.00 0.00 0.00 0.00 85562612.09 1486170.33
July 0.221389E+11 0.126846E+11 0.704816E+10 0.00 0.00 0.00 0.00 0.101321E+09 945204.35
August 0.230879E+11 0.133729E+11 0.724851E+10 0.00 0.00 0.00 0.00 58596917.62 1409614.08
September 0.218263E+11 0.128922E+11 0.688712E+10 0.00 0.00 0.00 0.00 35772296.74 2148894.13
October 0.221054E+11 0.144053E+11 0.707123E+10 0.00 0.00 0.00 0.00 17731018.90 5591020.99
November 0.212681E+11 0.151235E+11 0.684509E+10 0.00 0.00 0.00 0.00 4215897.39 19236977.80
December 0.221389E+11 0.157242E+11 0.704724E+10 0.00 0.00 0.00 0.00 40178.70 67982759.94
                   
Annual Sum or Average 0.264651E+12 0.168308E+12 0.839284E+11 0.00 0.00 0.00 0.00 0.487926E+09 0.325000E+09
Minimum of Months 0.201852E+11 0.126846E+11 0.641452E+10 0.00 0.00 0.00 0.00 0.00 945204.35
Maximum of Months 0.230879E+11 0.157242E+11 0.724851E+10 0.00 0.00 0.00 0.00 0.110468E+09 83496426.59



Table of Contents

Report: SpaceGainsMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.208295E+10 0.174880E+10 0.443872E+10 0.00 0.00 0.00 0.00 0.00 40720799.66
February 0.190200E+10 0.159209E+10 0.402701E+10 0.00 0.00 0.00 0.00 633364.65 48371466.04
March 0.217552E+10 0.181792E+10 0.455059E+10 0.00 0.00 0.00 0.00 7782867.67 42100586.71
April 0.205665E+10 0.171452E+10 0.432486E+10 0.00 0.00 0.00 0.00 29776368.03 5548463.12
May 0.212923E+10 0.178336E+10 0.449465E+10 0.00 0.00 0.00 0.00 55469162.82 4497770.08
June 0.209978E+10 0.175416E+10 0.439413E+10 0.00 0.00 0.00 0.00 42301329.66 1165349.47
July 0.208610E+10 0.174372E+10 0.442481E+10 0.00 0.00 0.00 0.00 47399381.08 1618952.73
August 0.217552E+10 0.181792E+10 0.455059E+10 0.00 0.00 0.00 0.00 27797195.66 2730330.95
September 0.205665E+10 0.171452E+10 0.432371E+10 0.00 0.00 0.00 0.00 18389179.56 3387389.02
October 0.208295E+10 0.174880E+10 0.443929E+10 0.00 0.00 0.00 0.00 9186704.49 4101162.69
November 0.200405E+10 0.169012E+10 0.429732E+10 0.00 0.00 0.00 0.00 2242253.95 11675011.40
December 0.208610E+10 0.174372E+10 0.442423E+10 0.00 0.00 0.00 0.00 21352.95 40073646.07
                   
Annual Sum or Average 0.249375E+11 0.208697E+11 0.526899E+11 0.00 0.00 0.00 0.00 0.240999E+09 0.205991E+09
Minimum of Months 0.190200E+10 0.159209E+10 0.402701E+10 0.00 0.00 0.00 0.00 0.00 1165349.47
Maximum of Months 0.217552E+10 0.181792E+10 0.455059E+10 0.00 0.00 0.00 0.00 55469162.82 48371466.04



Table of Contents

Report: SpaceGainsMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.208295E+10 0.174880E+10 0.666220E+09 0.00 0.00 0.00 0.00 0.00 38268501.04
February 0.190200E+10 0.159209E+10 0.604426E+09 0.00 0.00 0.00 0.00 633325.62 45585552.82
March 0.217552E+10 0.181792E+10 0.683011E+09 0.00 0.00 0.00 0.00 7806933.64 38647027.37
April 0.205665E+10 0.171452E+10 0.649132E+09 0.00 0.00 0.00 0.00 29950136.56 4557364.37
May 0.212923E+10 0.178336E+10 0.674616E+09 0.00 0.00 0.00 0.00 56069510.67 3277463.27
June 0.209978E+10 0.175416E+10 0.659528E+09 0.00 0.00 0.00 0.00 43336785.59 843573.11
July 0.208610E+10 0.174372E+10 0.664132E+09 0.00 0.00 0.00 0.00 49209054.60 904277.97
August 0.217552E+10 0.181792E+10 0.683011E+09 0.00 0.00 0.00 0.00 28573123.34 1756146.96
September 0.205665E+10 0.171452E+10 0.648959E+09 0.00 0.00 0.00 0.00 18546323.57 2358855.35
October 0.208295E+10 0.174880E+10 0.666307E+09 0.00 0.00 0.00 0.00 9213279.12 3714089.67
November 0.200405E+10 0.169012E+10 0.644998E+09 0.00 0.00 0.00 0.00 2242197.78 11201758.61
December 0.208610E+10 0.174372E+10 0.664046E+09 0.00 0.00 0.00 0.00 21348.04 38048782.48
                   
Annual Sum or Average 0.249375E+11 0.208697E+11 0.790839E+10 0.00 0.00 0.00 0.00 0.245602E+09 0.189163E+09
Minimum of Months 0.190200E+10 0.159209E+10 0.604426E+09 0.00 0.00 0.00 0.00 0.00 843573.11
Maximum of Months 0.217552E+10 0.181792E+10 0.683011E+09 0.00 0.00 0.00 0.00 56069510.67 45585552.82



Table of Contents

Report: SpaceGainsMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.165769E+09 52953287.74 0.00 0.00 0.00 0.00 0.00 0.00 0.133384E+10
February 0.151369E+09 48182266.45 0.00 0.00 0.00 0.00 0.00 0.00 0.853585E+09
March 0.173136E+09 54927912.53 0.00 0.00 0.00 0.00 0.00 30060796.08 0.433913E+09
April 0.163676E+09 51865380.39 0.00 0.00 0.00 0.00 0.00 0.472373E+09 56527358.93
May 0.169453E+09 53941762.61 0.00 0.00 0.00 0.00 0.00 0.101115E+10 13206575.16
June 0.167108E+09 53008506.70 0.00 0.00 0.00 0.00 0.00 0.941519E+09 19100085.82
July 0.166020E+09 52802317.57 0.00 0.00 0.00 0.00 0.00 0.491550E+09 20805693.44
August 0.173136E+09 54927563.77 0.00 0.00 0.00 0.00 0.00 0.289946E+09 45715920.66
September 0.163676E+09 51865380.39 0.00 0.00 0.00 0.00 0.00 0.161579E+09 53233423.71
October 0.165769E+09 52953636.50 0.00 0.00 0.00 0.00 0.00 28041456.10 0.324667E+09
November 0.159490E+09 51191943.51 0.00 0.00 0.00 0.00 0.00 0.00 0.852124E+09
December 0.166020E+09 52796660.11 0.00 0.00 0.00 0.00 0.00 0.00 0.137300E+10
                   
Annual Sum or Average 0.198462E+10 0.631417E+09 0.00 0.00 0.00 0.00 0.00 0.342622E+10 0.537972E+10
Minimum of Months 0.151369E+09 48182266.45 0.00 0.00 0.00 0.00 0.00 0.00 13206575.16
Maximum of Months 0.173136E+09 54927912.53 0.00 0.00 0.00 0.00 0.00 0.101115E+10 0.137300E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 785.10 02-JAN-15:09 742.55 02-JAN-09:09 2751.42 02-JAN-09:09 0.00 0.00 0.00 0.00 8.92 11-JAN-14:00 188.57 15-JAN-19:10
February 785.10 01-FEB-15:09 742.55 01-FEB-09:09 2751.42 01-FEB-09:09 0.00 0.00 0.00 0.00 18.02 19-FEB-15:00 358.35 09-FEB-21:10
March 785.10 01-MAR-15:09 742.55 01-MAR-09:09 2751.42 01-MAR-09:09 0.00 0.00 0.00 0.00 146.51 26-MAR-18:02 762.66 24-MAR-24:00
April 785.10 01-APR-10:09 742.55 01-APR-09:09 2751.42 01-APR-09:09 0.00 0.00 0.00 0.00 277.98 02-APR-18:02 82.34 04-APR-24:00
May 785.10 01-MAY-14:09 742.55 01-MAY-08:09 2751.42 01-MAY-08:09 0.00 0.00 0.00 0.00 476.93 28-MAY-18:01 114.42 15-MAY-03:00
June 785.10 01-JUN-14:09 742.55 01-JUN-08:09 2751.42 01-JUN-08:09 0.00 0.00 0.00 0.00 394.67 17-JUN-21:02 87.93 18-JUN-02:00
July 785.10 01-JUL-10:09 742.55 01-JUL-09:09 2751.42 01-JUL-09:09 0.00 0.00 0.00 0.00 296.62 03-JUL-04:40 62.03 19-JUL-03:00
August 785.10 01-AUG-14:09 742.55 01-AUG-08:09 2751.42 01-AUG-08:09 0.00 0.00 0.00 0.00 184.35 31-AUG-04:09 100.23 15-AUG-23:50
September 785.10 01-SEP-14:09 742.55 01-SEP-08:09 2751.42 01-SEP-08:09 0.00 0.00 0.00 0.00 114.16 02-SEP-21:02 30.11 08-SEP-21:30
October 785.10 02-OCT-14:09 742.55 02-OCT-08:09 2751.42 02-OCT-08:09 0.00 0.00 0.00 0.00 109.43 03-OCT-15:00 112.66 12-OCT-03:00
November 785.10 01-NOV-14:09 742.55 01-NOV-08:09 2751.42 01-NOV-08:09 0.00 0.00 0.00 0.00 40.26 13-NOV-14:00 147.98 29-NOV-24:00
December 785.10 01-DEC-15:09 742.55 01-DEC-09:09 2751.42 01-DEC-09:09 0.00 0.00 0.00 0.00 19.31 24-DEC-14:00 304.29 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 785.10   742.55   2751.42   0.00 0.00 0.00 0.00 8.92   30.11  
Maximum of Months 785.10   742.55   2751.42   0.00 0.00 0.00 0.00 476.93   762.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 24809.68 02-JAN-15:09 16279.92 02-JAN-17:40 4639.58 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 185.79 15-JAN-19:30
February 24809.68 01-FEB-15:09 16279.92 01-FEB-17:00 4639.58 01-FEB-09:09 0.00 0.00 0.00 0.00 15.45 19-FEB-15:00 365.53 09-FEB-21:10
March 24809.68 01-MAR-15:09 15837.37 04-MAR-17:00 4639.58 01-MAR-09:09 0.00 0.00 0.00 0.00 125.28 26-MAR-18:02 766.92 24-MAR-24:00
April 24809.68 01-APR-10:09 14786.79 22-APR-16:00 4639.58 01-APR-09:09 0.00 0.00 0.00 0.00 240.07 02-APR-18:02 70.87 10-APR-05:00
May 24809.68 01-MAY-14:09 15172.20 31-MAY-16:00 4639.58 01-MAY-08:09 0.00 0.00 0.00 0.00 412.43 28-MAY-18:01 76.39 15-MAY-03:00
June 24809.68 01-JUN-14:09 14310.65 24-JUN-09:09 4639.58 01-JUN-08:09 0.00 0.00 0.00 0.00 343.21 17-JUN-21:02 66.44 18-JUN-04:00
July 24809.68 01-JUL-10:09 15127.28 27-JUL-16:00 4639.58 01-JUL-09:09 0.00 0.00 0.00 0.00 231.27 20-JUL-20:02 48.67 19-JUL-03:00
August 24809.68 01-AUG-14:09 15180.22 19-AUG-16:00 4639.58 01-AUG-08:09 0.00 0.00 0.00 0.00 151.80 15-AUG-20:02 65.56 15-AUG-24:00
September 24809.68 01-SEP-14:09 15381.07 08-SEP-16:00 4639.58 01-SEP-08:09 0.00 0.00 0.00 0.00 100.25 02-SEP-21:02 37.17 19-SEP-05:00
October 24809.68 02-OCT-14:09 15905.67 25-OCT-16:00 4639.58 02-OCT-08:09 0.00 0.00 0.00 0.00 93.83 03-OCT-15:00 97.59 12-OCT-03:00
November 24809.68 01-NOV-14:09 16279.92 06-NOV-17:30 4639.58 01-NOV-08:09 0.00 0.00 0.00 0.00 34.52 13-NOV-14:00 153.43 28-NOV-05:02
December 24809.68 01-DEC-15:09 16279.92 01-DEC-17:19 4639.58 01-DEC-09:09 0.00 0.00 0.00 0.00 3.54 28-DEC-14:00 340.47 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 24809.68   14310.65   4639.58   0.00 0.00 0.00 0.00 0.00   37.17  
Maximum of Months 24809.68   16279.92   4639.58   0.00 0.00 0.00 0.00 412.43   766.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2337.76 02-JAN-15:09 1534.02 02-JAN-09:09 2912.71 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 104.56 12-JAN-04:00
February 2337.76 01-FEB-15:09 1534.02 01-FEB-09:09 2912.71 01-FEB-09:09 0.00 0.00 0.00 0.00 8.22 19-FEB-15:00 203.35 09-FEB-21:10
March 2337.76 01-MAR-15:09 1534.02 01-MAR-09:09 2912.71 01-MAR-09:09 0.00 0.00 0.00 0.00 61.54 26-MAR-18:02 501.96 24-MAR-23:00
April 2337.76 01-APR-10:09 1534.02 01-APR-09:09 2912.71 01-APR-09:09 0.00 0.00 0.00 0.00 123.99 30-APR-18:01 60.00 04-APR-24:00
May 2337.76 01-MAY-14:09 1534.02 01-MAY-08:09 2912.71 01-MAY-08:09 0.00 0.00 0.00 0.00 215.90 28-MAY-18:01 63.76 15-MAY-03:00
June 2337.76 01-JUN-14:09 1534.02 01-JUN-08:09 2912.71 01-JUN-08:09 0.00 0.00 0.00 0.00 178.71 17-JUN-21:02 45.01 18-JUN-01:50
July 2337.76 01-JUL-10:09 1534.02 01-JUL-09:09 2912.71 01-JUL-09:09 0.00 0.00 0.00 0.00 135.87 03-JUL-04:17 32.51 19-JUL-03:00
August 2337.76 01-AUG-14:09 1534.02 01-AUG-08:09 2912.71 01-AUG-08:09 0.00 0.00 0.00 0.00 84.75 31-AUG-04:07 53.07 15-AUG-23:10
September 2337.76 01-SEP-14:09 1534.02 01-SEP-08:09 2912.71 01-SEP-08:09 0.00 0.00 0.00 0.00 50.90 02-SEP-21:02 20.35 08-SEP-21:30
October 2337.76 02-OCT-14:09 1534.02 02-OCT-08:09 2912.71 02-OCT-08:09 0.00 0.00 0.00 0.00 49.91 03-OCT-15:00 61.35 12-OCT-03:00
November 2337.76 01-NOV-14:09 1534.02 01-NOV-08:09 2912.71 01-NOV-08:09 0.00 0.00 0.00 0.00 18.36 13-NOV-14:00 104.39 29-NOV-24:00
December 2337.76 01-DEC-15:09 1534.02 01-DEC-09:09 2912.71 01-DEC-09:09 0.00 0.00 0.00 0.00 1.88 28-DEC-14:00 178.87 29-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2337.76   1534.02   2912.71   0.00 0.00 0.00 0.00 0.00   20.35  
Maximum of Months 2337.76   1534.02   2912.71   0.00 0.00 0.00 0.00 215.90   501.96  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2337.76 02-JAN-15:09 1534.02 02-JAN-09:09 437.18 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 100.84 26-JAN-21:10
February 2337.76 01-FEB-15:09 1534.02 01-FEB-09:09 437.18 01-FEB-09:09 0.00 0.00 0.00 0.00 8.22 19-FEB-15:00 178.82 09-FEB-21:10
March 2337.76 01-MAR-15:09 1534.02 01-MAR-09:09 437.18 01-MAR-09:09 0.00 0.00 0.00 0.00 62.26 26-MAR-18:02 455.81 24-MAR-24:00
April 2337.76 01-APR-10:09 1534.02 01-APR-09:09 437.18 01-APR-09:09 0.00 0.00 0.00 0.00 124.61 02-APR-18:02 50.42 04-APR-24:00
May 2337.76 01-MAY-14:09 1534.02 01-MAY-08:09 437.18 01-MAY-08:09 0.00 0.00 0.00 0.00 216.36 28-MAY-18:01 52.76 15-MAY-03:00
June 2337.76 01-JUN-14:09 1534.02 01-JUN-08:09 437.18 01-JUN-08:09 0.00 0.00 0.00 0.00 179.50 17-JUN-21:02 37.22 18-JUN-02:00
July 2337.76 01-JUL-10:09 1534.02 01-JUL-09:09 437.18 01-JUL-09:09 0.00 0.00 0.00 0.00 135.87 03-JUL-04:16 26.69 19-JUL-03:00
August 2337.76 01-AUG-14:09 1534.02 01-AUG-08:09 437.18 01-AUG-08:09 0.00 0.00 0.00 0.00 85.69 31-AUG-04:07 47.63 15-AUG-23:30
September 2337.76 01-SEP-14:09 1534.02 01-SEP-08:09 437.18 01-SEP-08:09 0.00 0.00 0.00 0.00 51.35 02-SEP-21:02 16.56 19-SEP-04:00
October 2337.76 02-OCT-14:09 1534.02 02-OCT-08:09 437.18 02-OCT-08:09 0.00 0.00 0.00 0.00 49.91 03-OCT-15:00 54.49 12-OCT-03:00
November 2337.76 01-NOV-14:09 1534.02 01-NOV-08:09 437.18 01-NOV-08:09 0.00 0.00 0.00 0.00 18.36 13-NOV-14:00 97.01 29-NOV-24:00
December 2337.76 01-DEC-15:09 1534.02 01-DEC-09:09 437.18 01-DEC-09:09 0.00 0.00 0.00 0.00 1.88 28-DEC-14:00 167.01 29-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2337.76   1534.02   437.18   0.00 0.00 0.00 0.00 0.00   16.56  
Maximum of Months 2337.76   1534.02   437.18   0.00 0.00 0.00 0.00 216.36   455.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 186.05 02-JAN-15:09 44.76 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 3991.24 27-JAN-12:01
February 186.05 01-FEB-15:09 44.76 01-FEB-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3097.64 09-FEB-12:01
March 186.05 01-MAR-15:09 44.76 01-MAR-09:09 0.00 0.00 0.00 0.00 0.00 730.43 28-MAR-11:03 2007.70 16-MAR-07:01
April 186.05 01-APR-10:09 44.76 01-APR-09:09 0.00 0.00 0.00 0.00 0.00 2706.77 16-APR-11:01 1316.99 05-APR-07:01
May 186.05 01-MAY-14:09 44.76 01-MAY-08:09 0.00 0.00 0.00 0.00 0.00 4694.24 03-MAY-11:01 770.09 31-MAY-16:53
June 186.05 01-JUN-14:09 44.76 01-JUN-08:09 0.00 0.00 0.00 0.00 0.00 4647.77 05-JUN-11:01 1423.07 27-JUN-11:02
July 186.05 01-JUL-10:09 44.76 01-JUL-09:09 0.00 0.00 0.00 0.00 0.00 2861.86 01-JUL-11:01 1130.24 18-JUL-11:02
August 186.05 01-AUG-14:09 44.76 01-AUG-08:09 0.00 0.00 0.00 0.00 0.00 1361.09 05-AUG-11:02 749.90 16-AUG-07:02
September 186.05 01-SEP-14:09 44.76 01-SEP-08:09 0.00 0.00 0.00 0.00 0.00 1213.41 11-SEP-11:02 971.06 29-SEP-15:55
October 186.05 02-OCT-14:09 44.76 02-OCT-08:09 0.00 0.00 0.00 0.00 0.00 1015.78 02-OCT-11:02 2060.79 30-OCT-07:01
November 186.05 01-NOV-14:09 44.76 01-NOV-08:09 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2983.74 30-NOV-12:01
December 186.05 01-DEC-15:09 44.76 01-DEC-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5596.30 21-DEC-12:01
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 186.05   44.76   0.00 0.00 0.00 0.00 0.00 0.00   749.90  
Maximum of Months 186.05   44.76   0.00 0.00 0.00 0.00 0.00 4694.24   5596.30  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2129.80 13-JAN-06:10 0.00 163.56 1210.17 0.00 0.00 0.00 0.00 0.00 28.00
February 3841.40 24-FEB-17:00 686.96 742.55 2751.42 0.00 0.00 0.00 0.00 9.24 0.00
March 46215.91 27-MAR-04:01 0.00 371.22 5445.79 0.00 0.00 0.00 0.00 0.00 114.19
April 47993.08 30-APR-06:01 0.00 412.47 4538.16 0.00 0.00 0.00 0.00 0.00 8.02
May 48418.21 03-MAY-04:01 0.00 817.82 6050.87 0.00 0.00 0.00 0.00 0.00 0.00
June 46869.66 05-JUN-04:01 0.00 412.47 6050.87 0.00 0.00 0.00 0.00 0.00 0.00
July 45051.77 01-JUL-04:01 0.00 817.82 4538.16 0.00 0.00 0.00 0.00 14.74 0.00
August 43946.62 09-AUG-04:01 0.00 817.82 6050.87 0.00 0.00 0.00 0.00 9.01 0.00
September 44580.43 27-SEP-04:01 0.00 817.82 6050.87 0.00 0.00 0.00 0.00 0.00 0.00
October 47014.69 23-OCT-04:01 0.00 412.47 6050.87 0.00 0.00 0.00 0.00 0.00 18.05
November 40295.61 01-NOV-04:01 0.00 736.04 5445.79 0.00 0.00 0.00 0.00 0.00 22.45
December 2143.31 05-DEC-06:10 0.00 163.56 1210.17 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2129.80   0.00 163.56 1210.17 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 48418.21   686.96 817.82 6050.87 0.00 0.00 0.00 0.00 14.74 114.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33114.04 05-JAN-07:05 12404.84 1378.20 8248.14 0.00 0.00 0.00 0.00 0.00 0.00
February 32444.24 23-FEB-16:00 24809.68 13252.66 4639.58 0.00 0.00 0.00 0.00 3.24 0.00
March 155301.22 30-MAR-06:02 15506.05 1722.75 10310.18 0.00 0.00 0.00 0.00 0.00 0.82
April 186238.15 28-APR-05:01 0.00 2411.84 7142.30 0.00 0.00 0.00 0.00 0.03 0.00
May 183814.37 06-MAY-04:01 0.00 3445.49 7652.47 0.00 0.00 0.00 0.00 23.32 0.00
June 166335.13 07-JUN-04:01 0.00 3445.49 10203.29 0.00 0.00 0.00 0.00 63.28 0.00
July 149089.24 05-JUL-04:01 0.00 3445.49 10203.29 0.00 0.00 0.00 0.00 50.72 0.00
August 136671.80 07-AUG-05:01 0.00 2756.39 8162.63 0.00 0.00 0.00 0.00 4.49 0.00
September 143571.05 26-SEP-05:02 0.00 1722.75 5101.65 0.00 0.00 0.00 0.00 0.00 1.74
October 158858.76 16-OCT-06:03 12404.84 1378.20 8248.14 0.00 0.00 0.00 0.00 0.00 5.41
November 39451.02 09-NOV-15:20 24809.68 13609.99 4639.58 0.00 0.00 0.00 0.00 6.25 0.00
December 31880.79 21-DEC-07:05 12404.84 1378.20 8248.14 0.00 0.00 0.00 0.00 0.00 13.28
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 31880.79   0.00 1378.20 4639.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 186238.15   24809.68 13609.99 10310.18 0.00 0.00 0.00 0.00 63.28 13.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7965.33 12-JAN-15:50 2337.76 1534.02 2912.71 0.00 0.00 0.00 0.00 0.00 1.71
February 28757.52 23-FEB-05:02 0.00 194.80 3843.35 0.00 0.00 0.00 0.00 0.00 1.24
March 31023.30 29-MAR-04:01 0.00 324.66 6405.59 0.00 0.00 0.00 0.00 0.00 0.00
April 31052.32 05-APR-04:01 0.00 324.66 6405.59 0.00 0.00 0.00 0.00 0.00 0.00
May 30642.07 09-MAY-04:01 0.00 324.66 6405.59 0.00 0.00 0.00 0.00 0.00 0.00
June 29560.45 05-JUN-04:01 0.00 324.66 6405.59 0.00 0.00 0.00 0.00 0.00 0.00
July 27072.49 01-JUL-04:01 0.00 324.66 4804.19 0.00 0.00 0.00 0.00 5.88 0.00
August 26268.30 03-AUG-04:01 0.00 324.66 6405.59 0.00 0.00 0.00 0.00 0.00 2.10
September 29263.27 27-SEP-04:01 0.00 324.66 6405.59 0.00 0.00 0.00 0.00 0.00 0.00
October 31713.08 23-OCT-04:01 0.00 324.66 6405.59 0.00 0.00 0.00 0.00 0.00 10.81
November 30605.34 02-NOV-04:01 0.00 292.19 5765.03 0.00 0.00 0.00 0.00 0.00 20.16
December 12865.79 29-DEC-05:03 0.00 129.86 2562.24 0.00 0.00 0.00 0.00 0.00 156.95
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7965.33   0.00 129.86 2562.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31713.08   2337.76 1534.02 6405.59 0.00 0.00 0.00 0.00 5.88 156.95



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5982.47 12-JAN-15:40 2337.76 1534.02 437.18 0.00 0.00 0.00 0.00 0.00 1.61
February 25067.25 23-FEB-05:02 0.00 194.80 576.86 0.00 0.00 0.00 0.00 0.00 1.18
March 26918.87 27-MAR-04:01 0.00 292.19 865.29 0.00 0.00 0.00 0.00 0.00 73.26
April 27717.78 29-APR-04:01 0.00 324.66 721.08 0.00 0.00 0.00 0.00 0.00 0.00
May 27300.40 09-MAY-04:01 0.00 324.66 961.43 0.00 0.00 0.00 0.00 0.00 0.00
June 25700.17 05-JUN-04:01 0.00 324.66 961.43 0.00 0.00 0.00 0.00 0.00 0.00
July 23808.40 01-JUL-04:01 0.00 324.66 721.08 0.00 0.00 0.00 0.00 7.27 0.00
August 23030.71 09-AUG-04:01 0.00 324.66 961.43 0.00 0.00 0.00 0.00 3.75 0.00
September 25113.79 27-SEP-04:01 0.00 324.66 961.43 0.00 0.00 0.00 0.00 0.00 0.00
October 27836.25 23-OCT-04:01 0.00 324.66 961.43 0.00 0.00 0.00 0.00 0.00 10.07
November 26648.36 02-NOV-04:01 0.00 292.19 865.29 0.00 0.00 0.00 0.00 0.00 19.08
December 7585.76 01-DEC-15:30 2337.76 1534.02 437.18 0.00 0.00 0.00 0.00 0.00 1.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5982.47   0.00 194.80 437.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27836.25   2337.76 1534.02 961.43 0.00 0.00 0.00 0.00 7.27 73.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 2.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 01-FEB-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 01-MAR-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 01-APR-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 01-MAY-00:10 0.00 2.49 0.00 0.00 0.00 0.00 0.00 0.00 0.10
June 0.00 01-JUN-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 01-JUL-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 1.88 0.00
August 0.00 01-AUG-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 1.02
September 0.00 01-SEP-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 2.25
October 0.00 01-OCT-00:10 0.00 2.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 01-NOV-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 01-DEC-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 2.60
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 2.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00   0.00 2.58 0.00 0.00 0.00 0.00 0.00 1.88 2.60



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [] NATURALGAS:FACILITY []
January 0.619061E+11 52073.68 12-JAN-17:40 0.00 0.00
February 0.594145E+11 60640.66 24-FEB-16:00 0.00 0.00
March 0.830547E+11 78549.48 28-MAR-15:00 0.00 0.00
April 0.105367E+12 96587.51 28-APR-14:00 0.00 0.00
May 0.133949E+12 115194.13 03-MAY-14:00 0.00 0.00
June 0.138216E+12 123919.44 10-JUN-15:00 0.00 0.00
July 0.137485E+12 118831.25 01-JUL-15:00 0.00 0.00
August 0.133912E+12 108636.57 07-AUG-15:00 0.00 0.00
September 0.115822E+12 98786.19 14-SEP-15:00 0.00 0.00
October 0.984610E+11 88912.52 03-OCT-14:00 0.00 0.00
November 0.747183E+11 70298.67 08-NOV-17:30 0.00 0.00
December 0.619304E+11 54917.24 01-DEC-17:19 0.00 0.00
           
Annual Sum or Average 0.120424E+13     0.00 0.00
Minimum of Months 0.594145E+11 52073.68   0.00 0.00
Maximum of Months 0.138216E+12 123919.44   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.200414E+11 0.437329E+10 0.163682E+11 0.00 0.128040E+11 0.00 0.372290E+10 0.262971E+10 0.00 0.00 0.00 0.196658E+10 0.00
February 0.175413E+11 0.373154E+10 0.148500E+11 0.00 0.115776E+11 0.00 0.617073E+09 0.934602E+10 0.00 0.00 0.00 0.175089E+10 0.00
March 0.186485E+11 0.377724E+10 0.167807E+11 0.00 0.130137E+11 0.00 0.00 0.289775E+11 0.00 0.00 0.00 0.185704E+10 0.00
April 0.178962E+11 0.330885E+10 0.159483E+11 0.00 0.129164E+11 0.00 0.00 0.536986E+11 0.00 0.00 0.00 0.159850E+10 0.00
May 0.185809E+11 0.311470E+10 0.165744E+11 0.00 0.152009E+11 0.00 0.00 0.790017E+11 0.00 0.00 0.00 0.147635E+10 0.00
June 0.179345E+11 0.285035E+10 0.162038E+11 0.00 0.160587E+11 0.00 0.00 0.838548E+11 0.00 0.00 0.00 0.131380E+10 0.00
July 0.171292E+11 0.303446E+10 0.163169E+11 0.00 0.162341E+11 0.00 0.00 0.835037E+11 0.00 0.00 0.00 0.126642E+10 0.00
August 0.180072E+11 0.327976E+10 0.167807E+11 0.00 0.156608E+11 0.00 0.00 0.788392E+11 0.00 0.00 0.00 0.134483E+10 0.00
September 0.172625E+11 0.350601E+10 0.159441E+11 0.00 0.135245E+11 0.00 0.00 0.641826E+11 0.00 0.00 0.00 0.140188E+10 0.00
October 0.188630E+11 0.398356E+10 0.163703E+11 0.00 0.129764E+11 0.00 0.00 0.446678E+11 0.00 0.00 0.00 0.159997E+10 0.00
November 0.194341E+11 0.415479E+10 0.158468E+11 0.00 0.122989E+11 0.00 8552101.46 0.212638E+11 0.00 0.00 0.00 0.171150E+10 0.00
December 0.201694E+11 0.448104E+10 0.163148E+11 0.00 0.127886E+11 0.00 0.129846E+10 0.496380E+10 0.00 0.00 0.00 0.191438E+10 0.00
                           
Annual Sum or Average 0.221508E+12 0.435956E+11 0.194299E+12 0.00 0.165055E+12 0.00 0.564699E+10 0.554929E+12 0.00 0.00 0.00 0.192021E+11 0.00
Minimum of Months 0.171292E+11 0.285035E+10 0.148500E+11 0.00 0.115776E+11 0.00 0.00 0.262971E+10 0.00 0.00 0.00 0.126642E+10 0.00
Maximum of Months 0.201694E+11 0.448104E+10 0.167807E+11 0.00 0.162341E+11 0.00 0.372290E+10 0.838548E+11 0.00 0.00 0.00 0.196658E+10 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 20135.27 02-JAN-17:40 3820.86 01-JAN-06:10 10740.89 02-JAN-09:09 0.00 10074.19 03-JAN-06:19 0.00 31202.03 02-JAN-06:19
February 20135.27 01-FEB-17:00 3820.86 01-FEB-06:10 10740.89 01-FEB-09:09 0.00 9384.68 02-FEB-07:10 0.00 16807.77 02-FEB-07:10
March 19692.72 04-MAR-17:00 3820.86 01-MAR-06:10 10740.89 01-MAR-09:09 0.00 10074.19 12-MAR-08:09 0.00 0.00 01-MAR-00:10
April 18642.13 22-APR-16:00 3820.86 01-APR-05:10 10740.89 01-APR-09:09 0.00 11094.28 16-APR-08:09 0.00 0.00 01-APR-00:10
May 19027.54 31-MAY-16:00 3820.86 01-MAY-05:10 10740.89 01-MAY-08:09 0.00 13175.97 30-MAY-14:00 0.00 0.00 01-MAY-00:10
June 18165.99 24-JUN-09:09 3820.86 01-JUN-05:10 10740.89 01-JUN-08:09 0.00 14626.68 10-JUN-15:00 0.00 0.00 01-JUN-00:10
July 18982.63 27-JUL-16:00 3820.86 01-JUL-05:10 10740.89 01-JUL-09:09 0.00 15062.41 01-JUL-15:00 0.00 0.00 01-JUL-00:10
August 19035.57 19-AUG-16:00 3820.86 01-AUG-05:10 10740.89 01-AUG-08:09 0.00 13591.51 28-AUG-06:10 0.00 0.00 01-AUG-00:10
September 19236.42 08-SEP-16:00 3820.86 01-SEP-05:10 10740.89 01-SEP-08:09 0.00 11682.37 01-SEP-06:10 0.00 0.00 01-SEP-00:10
October 19761.02 25-OCT-16:00 3820.86 01-OCT-05:10 10740.89 02-OCT-08:09 0.00 11348.29 04-OCT-06:10 0.00 0.00 01-OCT-00:10
November 20135.27 06-NOV-17:30 3820.86 01-NOV-05:10 10740.89 01-NOV-08:09 0.00 7980.13 19-NOV-08:09 0.00 929.40 27-NOV-06:00
December 20135.27 01-DEC-17:19 3820.86 01-DEC-06:10 10740.89 01-DEC-09:09 0.00 9689.06 23-DEC-07:10 0.00 21463.33 23-DEC-07:10
                         
Annual Sum or Average             0.00     0.00    
Minimum of Months 18165.99   3820.86   10740.89   0.00 7980.13   0.00 0.00  
Maximum of Months 20135.27   3820.86   10740.89   0.00 15062.41   0.00 31202.03  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 11690.07 12-JAN-15:00 0.00 0.00 0.00 1995.38 17-JAN-12:00 0.00
February 23219.36 24-FEB-15:00 0.00 0.00 0.00 1993.02 01-FEB-12:20 0.00
March 41245.13 28-MAR-15:00 0.00 0.00 0.00 1890.45 03-MAR-12:50 0.00
April 58271.13 28-APR-14:00 0.00 0.00 0.00 1699.31 03-APR-11:20 0.00
May 73680.86 03-MAY-14:00 0.00 0.00 0.00 1551.34 01-MAY-11:09 0.00
June 80683.26 10-JUN-15:00 0.00 0.00 0.00 1408.78 01-JUN-11:50 0.00
July 77077.69 01-JUL-15:00 0.00 0.00 0.00 1278.80 03-JUL-11:50 0.00
August 69266.35 07-AUG-14:00 0.00 0.00 0.00 1406.00 31-AUG-11:20 0.00
September 59301.13 14-SEP-15:00 0.00 0.00 0.00 1545.31 29-SEP-11:30 0.00
October 51596.67 03-OCT-14:00 0.00 0.00 0.00 1696.58 31-OCT-11:09 0.00
November 30509.31 09-NOV-15:09 0.00 0.00 0.00 1847.82 30-NOV-12:20 0.00
December 14596.16 01-DEC-15:20 0.00 0.00 0.00 1990.90 29-DEC-12:30 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 11690.07   0.00 0.00 0.00 1278.80   0.00
Maximum of Months 80683.26   0.00 0.00 0.00 1995.38   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 52073.68 12-JAN-17:40 20135.27 10740.89 3820.86 0.00 7950.70 0.00 0.00 7997.86 0.00
February 60640.66 24-FEB-16:00 18548.93 10740.89 0.00 0.00 7950.70 0.00 0.00 21983.80 0.00
March 78549.48 28-MAR-15:00 17118.29 10740.89 0.00 0.00 8161.28 0.00 0.00 41245.13 0.00
April 96587.51 28-APR-14:00 16115.01 10740.89 0.00 0.00 10311.43 0.00 0.00 58271.13 0.00
May 115194.13 03-MAY-14:00 16619.28 10740.89 0.00 0.00 13006.41 0.00 0.00 73680.86 0.00
June 123919.44 10-JUN-15:00 16846.20 10740.89 0.00 0.00 14626.68 0.00 0.00 80683.26 0.00
July 118831.25 01-JUL-15:00 15044.15 10740.89 0.00 0.00 15062.41 0.00 0.00 77077.69 0.00
August 108636.57 07-AUG-15:00 15494.41 10740.89 0.00 0.00 12978.52 0.00 0.00 68432.88 0.00
September 98786.19 14-SEP-15:00 16364.94 10740.89 0.00 0.00 11352.88 0.00 0.00 59301.13 0.00
October 88912.52 03-OCT-14:00 16231.33 10740.89 0.00 0.00 9311.92 0.00 0.00 51596.67 0.00
November 70298.67 08-NOV-17:30 20135.27 10740.89 3820.86 0.00 7950.70 0.00 0.00 26364.09 0.00
December 54917.24 01-DEC-17:19 20135.27 10740.89 3820.86 0.00 7950.70 0.00 0.00 10853.29 0.00
                       
Annual Sum or Average           0.00   0.00     0.00
Minimum of Months 52073.68   15044.15 10740.89 0.00 0.00 7950.70 0.00 0.00 7997.86 0.00
Maximum of Months 123919.44   20135.27 10740.89 3820.86 0.00 15062.41 0.00 0.00 80683.26 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.67 20.34 0.00 20.34 0.00 20.34 0.00 20.34
February 0.17 20.46 0.00 20.46 0.00 20.46 0.00 20.46
March 0.00 0.00 0.00 0.00 0.17 24.45 0.00 24.45
April 0.00 0.00 0.00 0.00 5.67 24.82 0.00 24.82
May 0.00 0.00 0.00 0.00 10.83 25.56 0.00 25.56
June 0.00 0.00 0.00 0.00 12.17 25.60 0.00 25.60
July 0.00 0.00 0.00 0.00 12.83 25.64 0.00 25.64
August 0.00 0.00 0.00 0.00 10.83 25.12 0.00 25.12
September 0.00 0.00 0.00 0.00 8.50 24.84 0.00 24.84
October 0.00 0.00 0.00 0.00 1.50 24.64 0.00 24.64
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 2.50 20.46 0.00 20.46 0.00 20.46 0.00 20.46
                 
Annual Sum or Average 6.33 20.39 0.00 20.39 62.50 24.87 0.00 24.87
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.67 20.46 0.00 20.46 12.83 25.64 0.00 25.64



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.42 0.00 20.42 0.00 20.42 0.00 20.42
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 3.00 24.70 0.00 24.70
April 0.00 0.00 0.00 0.00 9.50 25.95 0.00 25.95
May 0.00 0.00 0.00 0.00 12.83 26.20 0.00 26.20
June 0.00 0.00 0.00 0.00 12.50 26.28 0.00 26.28
July 0.00 0.00 0.00 0.00 12.83 26.16 0.00 26.16
August 0.00 0.00 0.00 0.00 12.33 25.83 0.00 25.83
September 0.00 0.00 0.00 0.00 9.67 25.54 0.00 25.54
October 0.00 0.00 0.00 0.00 8.17 25.33 0.00 25.33
November 0.00 0.00 0.00 0.00 2.00 24.59 0.00 24.59
December 0.00 0.00 0.00 0.00 0.17 24.47 0.00 24.47
                 
Annual Sum or Average 0.33 20.42 0.00 20.42 83.00 25.84 0.00 25.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.42 0.00 20.42 12.83 26.28 0.00 26.28



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 20.31 0.00 20.31 0.00 20.31 0.00 20.31
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 2.00 24.65 0.00 24.65
April 0.00 0.00 0.00 0.00 6.83 25.08 0.00 25.08
May 0.00 0.00 0.00 0.00 10.83 25.61 0.00 25.61
June 0.00 0.00 0.00 0.00 9.83 25.48 0.00 25.48
July 0.00 0.00 0.00 0.00 10.83 25.45 0.00 25.45
August 0.00 0.00 0.00 0.00 10.00 25.41 0.00 25.41
September 0.00 0.00 0.00 0.00 7.83 25.05 0.00 25.05
October 0.00 0.00 0.00 0.00 6.17 24.99 0.00 24.99
November 0.00 0.00 0.00 0.00 0.67 24.53 0.00 24.53
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.50 20.31 0.00 20.31 65.00 25.27 0.00 25.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 20.31 0.00 20.31 10.83 25.61 0.00 25.61



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 36.00 14.59 31.50 14.62 0.00 14.62 0.00 14.62
February 3.33 15.07 3.33 15.07 0.00 15.07 0.00 15.07
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 16.00 14.58 15.50 14.59 0.00 14.59 0.00 14.59
                 
Annual Sum or Average 55.33 14.61 50.33 14.64 0.00 14.64 0.00 14.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36.00 15.07 31.50 15.07 0.00 15.07 0.00 15.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 414.00 21.45 116.33 21.37 116.33 21.33
February 357.17 22.63 15.83 22.57 15.83 22.51
March 153.00 23.61 84.33 23.71 0.00 23.71
April 1.00 23.89 334.50 23.89 0.00 23.89
May 0.17 23.89 418.00 23.89 0.17 23.89
June 4.33 23.89 408.00 23.89 4.33 23.89
July 2.33 23.89 415.00 23.89 2.33 23.89
August 1.50 23.89 422.00 23.89 1.50 23.89
September 42.67 23.89 405.00 23.89 42.67 23.89
October 3.50 23.84 313.83 23.89 0.00 23.89
November 222.83 23.40 0.00 23.40 0.00 23.40
December 415.00 21.90 51.00 21.82 51.00 21.75
             
Annual Sum or Average 1617.50 22.38 2983.83 23.25 234.17 23.18
Minimum of Months 0.17 21.45 0.00 21.37 0.00 21.33
Maximum of Months 415.00 23.89 422.00 23.89 116.33 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 400.67 22.60 5.83 22.58 5.83 22.56
February 194.83 22.97 30.50 23.10 0.00 23.10
March 26.00 23.29 249.17 23.83 0.00 23.83
April 0.00 0.00 388.83 23.89 0.00 23.89
May 9.00 23.91 418.00 23.89 9.00 23.89
June 93.00 23.90 408.00 23.89 93.00 23.90
July 247.67 23.90 415.00 23.90 247.67 23.90
August 280.33 23.90 422.00 23.90 280.33 23.90
September 186.83 23.90 405.00 23.89 186.83 23.90
October 8.17 23.88 399.00 23.89 8.17 23.89
November 56.33 23.07 162.83 23.68 0.00 23.68
December 360.50 22.93 0.00 22.93 0.00 22.93
             
Annual Sum or Average 1863.33 23.30 3304.17 23.68 830.83 23.70
Minimum of Months 0.00 0.00 0.00 22.58 0.00 22.56
Maximum of Months 400.67 23.91 422.00 23.90 280.33 23.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 187.17 22.66 51.50 22.89 2.67 22.87
February 81.17 22.83 191.67 23.57 0.00 23.57
March 13.67 23.74 356.83 23.88 0.00 23.88
April 0.00 0.00 399.33 23.89 0.00 23.89
May 0.67 23.89 418.00 23.89 0.67 23.89
June 7.00 23.89 408.00 23.89 7.00 23.89
July 6.33 23.89 415.00 23.89 6.33 23.89
August 6.67 23.89 422.00 23.89 6.67 23.89
September 37.67 23.89 405.00 23.89 37.67 23.89
October 0.00 0.00 414.00 23.89 0.00 23.89
November 10.67 23.43 343.83 23.88 0.00 23.88
December 123.33 22.94 143.00 23.45 0.00 23.45
             
Annual Sum or Average 474.33 22.96 3968.17 23.79 61.00 23.79
Minimum of Months 0.00 0.00 51.50 22.89 0.00 22.87
Maximum of Months 187.17 23.89 422.00 23.89 37.67 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 235.33 22.32 29.67 22.43 5.67 22.41
February 107.17 22.42 164.00 23.31 0.00 23.31
March 28.00 23.42 337.67 23.85 0.00 23.85
April 0.00 0.00 393.17 23.89 0.00 23.89
May 2.00 23.89 418.00 23.89 2.00 23.89
June 24.33 23.89 408.00 23.89 24.33 23.89
July 31.17 23.89 415.00 23.89 31.17 23.89
August 44.83 23.89 422.00 23.89 44.83 23.89
September 95.00 23.89 405.00 23.89 95.00 23.89
October 2.50 23.89 410.17 23.89 2.50 23.89
November 19.33 23.09 331.67 23.85 0.00 23.85
December 161.00 22.60 99.83 23.10 0.00 23.10
             
Annual Sum or Average 750.67 22.87 3834.17 23.72 205.50 23.72
Minimum of Months 0.00 0.00 29.67 22.43 0.00 22.41
Maximum of Months 235.33 23.89 422.00 23.89 95.00 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 404.17 18.96 197.67 18.41 194.67 18.11
February 233.17 20.61 161.67 21.40 58.67 21.01
March 232.33 27.24 327.00 27.35 163.67 27.84
April 361.67 32.29 402.00 31.95 360.50 32.07
May 418.00 34.36 418.00 34.36 418.00 34.36
June 408.00 34.04 408.00 34.04 408.00 34.04
July 415.00 32.06 415.00 32.06 415.00 32.06
August 422.00 30.97 422.00 30.97 422.00 30.97
September 405.00 30.33 405.00 30.33 405.00 30.33
October 372.33 29.57 407.50 29.38 369.67 29.46
November 216.33 25.93 304.67 26.16 153.17 26.52
December 358.17 19.72 122.00 19.41 96.33 19.00
             
Annual Sum or Average 4246.17 28.51 3990.50 29.00 3464.67 29.36
Minimum of Months 216.33 18.96 122.00 18.41 58.67 18.11
Maximum of Months 422.00 34.36 422.00 34.36 422.00 34.36



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 21.44797 43.51512 -0.4161 9.22599
February 376.00000 22.69403 44.16277 -0.0615 6.67867
March 422.00000 23.78721 42.21689 0.31702 7.46958
April 405.00000 23.89014 41.39352 0.50298 10.43493
May 418.00000 23.89031 47.05656 -0.1695 5.72620
June 408.00000 23.89021 50.96589 -0.1325 5.56931
July 415.00000 23.89022 53.75692 -0.1315 5.49308
August 422.00000 23.89032 54.57404 -0.1624 5.60848
September 405.00000 23.89028 54.71685 -0.2375 6.24089
October 414.00000 23.88978 46.30102 0.46855 9.67606
November 399.00000 23.61539 42.96371 0.22420 6.65164
December 415.00000 21.90382 42.07690 -0.2877 7.63981
           
Annual Sum or Average 4913.00000 23.39389 47.00526 -0.0078 7.20115
Minimum of Months 376.00000 21.44797 41.39352 -0.4161 5.49308
Maximum of Months 422.00000 23.89032 54.71685 0.50298 10.43493



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 22.64113 44.40869 -0.0369 6.37599
February 376.00000 23.41285 44.73925 0.22222 6.94934
March 422.00000 23.85058 43.63556 0.42711 8.98167
April 405.00000 23.89088 43.57360 0.54526 11.32794
May 418.00000 23.89298 51.21459 -0.1675 5.66961
June 408.00000 23.89387 56.75763 -0.1368 5.48849
July 415.00000 23.89484 62.31504 -0.1349 5.44149
August 422.00000 23.89460 63.84137 -0.1510 5.50492
September 405.00000 23.89395 62.08922 -0.1988 5.85805
October 414.00000 23.88842 49.24385 0.52773 10.89476
November 399.00000 23.77153 43.93084 0.37129 8.14896
December 415.00000 23.05840 42.60721 0.08640 6.34178
           
Annual Sum or Average 4913.00000 23.66664 50.75896 0.11108 7.24352
Minimum of Months 376.00000 22.64113 42.60721 -0.1988 5.44149
Maximum of Months 422.00000 23.89484 63.84137 0.54526 11.32794



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 23.33407 40.96421 0.19814 7.42591
February 376.00000 23.66119 41.57186 0.36587 8.76848
March 422.00000 23.88556 41.31798 0.53225 11.21041
April 405.00000 23.89036 42.21220 0.64971 14.08765
May 418.00000 23.89041 48.27726 -0.0413 5.26046
June 408.00000 23.89028 52.28149 -0.0241 5.27409
July 415.00000 23.89027 55.33227 -0.0222 5.18010
August 422.00000 23.89029 55.83451 -0.0361 5.16054
September 405.00000 23.89036 54.25691 -0.0654 5.35940
October 414.00000 23.89056 44.37009 0.67148 14.66724
November 399.00000 23.87803 40.00950 0.55286 11.68615
December 415.00000 23.60713 38.58117 0.30649 7.98989
           
Annual Sum or Average 4913.00000 23.80061 46.30091 0.25546 8.48914
Minimum of Months 376.00000 23.33407 38.58117 -0.0654 5.16054
Maximum of Months 422.00000 23.89056 55.83451 0.67148 14.66724



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 22.99631 42.69268 0.10887 7.19918
February 376.00000 23.47101 43.14561 0.30779 8.37190
March 422.00000 23.85853 42.10716 0.50450 10.66849
April 405.00000 23.89032 42.38091 0.62679 13.47683
May 418.00000 23.89033 48.83692 -0.0699 5.33712
June 408.00000 23.89020 53.35488 -0.0554 5.31780
July 415.00000 23.89019 56.87177 -0.0493 5.21912
August 422.00000 23.89024 57.58129 -0.0634 5.20901
September 405.00000 23.89024 56.14756 -0.0923 5.42500
October 414.00000 23.89044 45.01286 0.65014 14.06827
November 399.00000 23.85057 40.62964 0.52287 11.07216
December 415.00000 23.39043 40.07001 0.24066 7.64090
           
Annual Sum or Average 4913.00000 23.73469 47.45168 0.21755 8.23598
Minimum of Months 376.00000 22.99631 40.07001 -0.0923 5.20901
Maximum of Months 422.00000 23.89044 57.58129 0.65014 14.06827



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 19.07386 50.56974 -0.5751 16.46925
February 376.00000 22.08003 46.57382 0.06442 11.76399
March 422.00000 26.28593 39.12332 0.92098 29.32812
April 405.00000 31.58818 30.15416 1.93705 67.51328
May 418.00000 34.35642 37.82655 2.53986 79.03760
June 408.00000 34.04050 48.72623 2.56980 79.95937
July 415.00000 32.06318 65.95912 2.21117 74.75306
August 422.00000 30.96720 72.98203 1.96550 68.69717
September 405.00000 30.32639 67.01203 1.71152 59.23755
October 414.00000 29.09945 43.46664 1.63271 57.20734
November 399.00000 25.31880 40.49531 0.81321 24.06564
December 415.00000 20.25553 46.48140 -0.2993 11.96131
           
Annual Sum or Average 4913.00000 27.99634 49.17888 1.29979 48.62119
Minimum of Months 376.00000 19.07386 30.15416 -0.5751 11.76399
Maximum of Months 422.00000 34.35642 72.98203 2.56980 79.95937



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00
February 0.953066E+09 0.279988E+09 110.17 0.854047E+09 99019149.45 0.00 0.31 24-FEB-16:00 0.00 01-FEB-00:10 6182.93 24-FEB-16:00 5438.66 24-FEB-16:00 1394.72 25-FEB-17:00 1821.04 24-FEB-16:00 0.00
March 0.941505E+10 0.274832E+10 381.25 0.857400E+10 0.841048E+09 0.00 1.00 10-MAR-05:01 0.00 01-MAR-00:10 52244.82 11-MAR-05:01 49626.43 27-MAR-04:01 9073.04 11-MAR-05:02 11851.20 11-MAR-05:01 0.00
April 0.248544E+11 0.726407E+10 454.72 0.234524E+11 0.140197E+10 0.00 1.00 01-APR-04:01 0.00 01-APR-00:10 52587.49 17-APR-04:01 51438.40 29-APR-04:01 7499.39 17-APR-04:12 12662.55 27-APR-04:42 0.00
May 0.405512E+11 0.118026E+11 484.83 0.359354E+11 0.461574E+10 0.00 1.00 01-MAY-04:01 0.00 01-MAY-00:10 54220.53 24-MAY-04:01 51947.49 02-MAY-04:01 16435.06 23-MAY-04:04 13394.69 04-MAY-04:01 0.00
June 0.441512E+11 0.126488E+11 485.83 0.364326E+11 0.771858E+10 0.00 1.00 01-JUN-04:01 0.00 01-JUN-00:10 55525.37 26-JUN-04:01 51532.02 05-JUN-04:01 21220.01 26-JUN-04:07 13552.22 12-JUN-04:01 0.00
July 0.471208E+11 0.125434E+11 488.42 0.346508E+11 0.124700E+11 0.00 1.00 01-JUL-04:01 0.00 01-JUL-00:10 55572.60 20-JUL-04:01 49457.11 01-JUL-04:01 21175.60 20-JUL-04:07 13517.57 02-JUL-06:01 0.00
August 0.442765E+11 0.113890E+11 478.43 0.311558E+11 0.131207E+11 0.00 1.00 01-AUG-04:01 0.00 01-AUG-00:10 54868.20 19-AUG-04:01 48423.71 09-AUG-04:01 18823.55 17-AUG-04:13 12998.79 08-AUG-04:01 0.00
September 0.336089E+11 0.881113E+10 457.84 0.241996E+11 0.940923E+10 0.00 1.00 01-SEP-04:01 0.00 01-SEP-00:10 55530.27 10-SEP-06:02 47764.40 27-SEP-04:01 24199.29 10-SEP-06:03 12526.50 02-SEP-04:01 0.00
October 0.191719E+11 0.540359E+10 458.80 0.164219E+11 0.274996E+10 0.00 1.00 01-OCT-06:01 0.00 01-OCT-00:10 53278.00 12-OCT-04:01 49753.91 02-OCT-04:01 13874.56 12-OCT-04:02 12039.52 04-OCT-04:01 0.00
November 0.462896E+10 0.136779E+10 286.48 0.417765E+10 0.451311E+09 0.00 1.00 01-NOV-04:01 0.00 01-NOV-00:10 49406.94 01-NOV-04:01 41959.05 01-NOV-04:01 7447.89 01-NOV-04:01 10881.58 01-NOV-04:01 0.00
December 8504901.31 2526068.26 3.50 8490187.06 14714.26 0.00 0.10 01-DEC-15:20 0.00 01-DEC-00:10 1816.01 01-DEC-15:20 1816.01 01-DEC-15:20 6.37 01-DEC-17:20 538.03 01-DEC-15:20 0.00
                                       
Annual Sum or Average 0.268740E+12 0.742612E+11 4090.27 0.215863E+12 0.528776E+11 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.471208E+11 0.126488E+11 488.42 0.364326E+11 0.131207E+11 0.00 1.00   0.00   55572.60   51947.49   24199.29   13552.22   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.344922E+10 0.108166E+10 102.56 0.286954E+10 0.579683E+09 0.00 0.29 14-JAN-15:10 0.00 01-JAN-00:10 25058.74 14-JAN-15:10 20804.58 12-JAN-15:30 6382.69 14-JAN-15:10 7605.29 14-JAN-15:00 0.00
February 0.196772E+11 0.605949E+10 245.75 0.161925E+11 0.348471E+10 0.00 0.59 24-FEB-16:00 0.00 01-FEB-00:10 54197.25 24-FEB-16:00 43972.40 22-FEB-15:10 17522.28 25-FEB-17:00 16210.63 24-FEB-16:00 0.00
March 0.646631E+11 0.196837E+11 391.59 0.538674E+11 0.107957E+11 0.00 1.00 11-MAR-07:02 0.00 01-MAR-00:10 217176.57 11-MAR-07:02 168448.56 13-MAR-06:03 52339.80 11-MAR-07:02 54355.18 11-MAR-07:02 0.00
April 0.114355E+12 0.357932E+11 417.88 0.100858E+12 0.134974E+11 0.00 1.00 01-APR-06:02 0.00 01-APR-00:10 221169.52 26-APR-06:02 206833.64 28-APR-05:01 69194.27 24-APR-06:02 59262.03 27-APR-05:02 0.00
May 0.167815E+12 0.525675E+11 445.82 0.134168E+12 0.336470E+11 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 228521.39 24-MAY-06:02 207198.43 06-MAY-04:01 95869.64 24-MAY-06:04 61187.78 04-MAY-04:01 0.00
June 0.185043E+12 0.560305E+11 437.44 0.131041E+12 0.540021E+11 0.00 1.00 01-JUN-05:03 0.00 01-JUN-00:10 236586.48 25-JUN-08:62 195840.00 12-JUN-05:01 122588.32 25-JUN-08:04 62156.57 12-JUN-06:02 0.00
July 0.200189E+12 0.557157E+11 444.49 0.117177E+12 0.830121E+11 0.00 1.00 01-JUL-05:01 0.00 01-JUL-00:10 236274.94 19-JUL-06:02 175512.36 05-JUL-04:01 122090.16 19-JUL-06:04 62636.81 02-JUL-08:62 0.00
August 0.196767E+12 0.529118E+11 447.74 0.107414E+12 0.893525E+11 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 238271.93 20-AUG-08:62 158630.01 07-AUG-05:01 129013.34 20-AUG-08:04 59615.17 08-AUG-06:02 0.00
September 0.157024E+12 0.428752E+11 427.64 0.913235E+11 0.657005E+11 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 239374.37 10-SEP-08:62 160973.73 26-SEP-05:02 134266.59 10-SEP-08:04 58422.17 24-SEP-08:62 0.00
October 0.979742E+11 0.290933E+11 410.25 0.749931E+11 0.229810E+11 0.00 1.00 01-OCT-07:13 0.00 01-OCT-00:10 227909.65 12-OCT-06:03 176008.83 15-OCT-08:62 100586.85 12-OCT-06:03 56156.94 04-OCT-06:02 0.00
November 0.448632E+11 0.137147E+11 345.43 0.370273E+11 0.783583E+10 0.00 0.71 09-NOV-15:10 0.00 01-NOV-00:10 66721.19 09-NOV-15:10 57665.32 04-NOV-15:00 14887.14 08-NOV-18:00 20266.52 09-NOV-15:10 0.00
December 0.820009E+10 0.256114E+10 179.43 0.673008E+10 0.147001E+10 0.00 0.38 01-DEC-15:10 0.00 01-DEC-00:10 31325.56 01-DEC-15:10 28794.35 01-DEC-15:10 6543.90 16-DEC-16:00 9554.78 01-DEC-15:10 0.00
                                       
Annual Sum or Average 0.126002E+13 0.368088E+12 4296.01 0.873661E+12 0.386359E+12 0.00                         0.00
Minimum of Months 0.344922E+10 0.108166E+10 102.56 0.286954E+10 0.579683E+09 0.00 0.29   0.00   25058.74   20804.58   6382.69   7605.29   0.00
Maximum of Months 0.200189E+12 0.560305E+11 447.74 0.134168E+12 0.893525E+11 0.00 1.00   0.00   239374.37   207198.43   134266.59   62636.81   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.386998E+10 0.101667E+10 276.61 0.351964E+10 0.350339E+09 0.00 0.65 12-JAN-16:00 0.00 01-JAN-00:10 9134.96 12-JAN-16:00 8494.70 12-JAN-15:40 1228.51 13-JAN-15:30 2291.93 12-JAN-16:00 0.00
February 0.688776E+10 0.177326E+10 315.94 0.617162E+10 0.716139E+09 0.00 1.00 21-FEB-05:03 0.00 01-FEB-00:10 32310.41 23-FEB-05:02 30578.39 23-FEB-05:02 4447.18 25-FEB-05:02 6996.95 23-FEB-05:02 0.00
March 0.139410E+11 0.362819E+10 451.89 0.125036E+11 0.143744E+10 0.00 1.00 04-MAR-05:02 0.00 01-MAR-00:10 33798.51 11-MAR-05:01 32778.56 29-MAR-04:01 5759.00 11-MAR-05:03 7513.25 11-MAR-05:01 0.00
April 0.205908E+11 0.569715E+10 471.81 0.190034E+11 0.158742E+10 0.00 1.00 01-APR-04:01 0.00 01-APR-00:10 34114.02 17-APR-04:01 33339.07 29-APR-04:01 5726.70 17-APR-04:12 8022.15 27-APR-04:01 0.00
May 0.272531E+11 0.776112E+10 522.21 0.233145E+11 0.393861E+10 0.00 1.00 01-MAY-04:01 0.00 01-MAY-00:10 35242.70 24-MAY-04:01 33463.66 09-MAY-04:01 11301.61 24-MAY-04:12 8408.24 04-MAY-04:11 0.00
June 0.289052E+11 0.807033E+10 511.37 0.226623E+11 0.624286E+10 0.00 1.00 01-JUN-04:01 0.00 01-JUN-00:10 36152.22 26-JUN-04:01 32894.87 05-JUN-04:01 14787.89 26-JUN-04:05 8571.58 12-JUN-04:01 0.00
July 0.312028E+11 0.807105E+10 506.63 0.215085E+11 0.969434E+10 0.00 1.00 01-JUL-04:01 0.00 01-JUL-00:10 36235.80 20-JUL-04:01 30164.09 01-JUL-04:01 14856.15 20-JUL-04:05 8554.71 02-JUL-06:01 0.00
August 0.308022E+11 0.771103E+10 491.10 0.204436E+11 0.103586E+11 0.00 1.00 01-AUG-04:01 0.00 01-AUG-00:10 35775.02 19-AUG-04:01 29050.27 03-AUG-04:01 13430.10 17-AUG-04:13 8231.48 08-AUG-04:01 0.00
September 0.264426E+11 0.665700E+10 466.53 0.185719E+11 0.787070E+10 0.00 1.00 01-SEP-04:01 0.00 01-SEP-00:10 35991.19 10-SEP-06:02 31287.44 27-SEP-04:01 15896.35 10-SEP-06:02 7943.21 02-SEP-04:01 0.00
October 0.213686E+11 0.545018E+10 472.38 0.182600E+11 0.310863E+10 0.00 1.00 01-OCT-06:01 0.00 01-OCT-00:10 34517.29 12-OCT-04:01 32988.97 23-OCT-04:01 9544.13 12-OCT-04:02 7656.24 04-OCT-04:01 0.00
November 0.136196E+11 0.341840E+10 422.90 0.122758E+11 0.134381E+10 0.00 1.00 01-NOV-04:01 0.00 01-NOV-00:10 33186.13 09-NOV-05:01 31840.40 02-NOV-04:01 4335.84 18-NOV-05:02 7165.27 09-NOV-05:01 0.00
December 0.578508E+10 0.149839E+10 331.88 0.519220E+10 0.592875E+09 0.00 0.95 29-DEC-05:03 0.00 01-DEC-00:10 14896.17 29-DEC-05:03 13369.74 29-DEC-05:03 1526.43 29-DEC-05:03 3289.18 29-DEC-05:03 0.00
                                       
Annual Sum or Average 0.230669E+12 0.607528E+11 5241.25 0.183427E+12 0.472418E+11 0.00                         0.00
Minimum of Months 0.386998E+10 0.101667E+10 276.61 0.351964E+10 0.350339E+09 0.00 0.65   0.00   9134.96   8494.70   1228.51   2291.93   0.00
Maximum of Months 0.312028E+11 0.807105E+10 522.21 0.233145E+11 0.103586E+11 0.00 1.00   0.00   36235.80   33463.66   15896.35   8571.58   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.198089E+10 0.531377E+09 205.08 0.177805E+10 0.202844E+09 0.00 0.57 12-JAN-15:40 0.00 01-JAN-00:10 7051.64 12-JAN-15:50 6459.55 12-JAN-15:30 1072.15 13-JAN-15:30 1813.58 12-JAN-15:40 0.00
February 0.470480E+10 0.123329E+10 276.95 0.415444E+10 0.550361E+09 0.00 1.00 22-FEB-05:02 0.00 01-FEB-00:10 28989.22 23-FEB-05:02 26240.83 23-FEB-05:02 3989.77 25-FEB-05:02 6278.50 23-FEB-05:02 0.00
March 0.110566E+11 0.291725E+10 422.29 0.974406E+10 0.131258E+10 0.00 1.00 06-MAR-05:02 0.00 01-MAR-00:10 30413.57 11-MAR-05:01 28599.69 27-MAR-04:01 6052.35 11-MAR-05:03 6763.12 11-MAR-05:01 0.00
April 0.177667E+11 0.494423E+10 460.23 0.162117E+11 0.155506E+10 0.00 1.00 01-APR-04:01 0.00 01-APR-00:10 30628.19 17-APR-04:01 29850.42 29-APR-04:01 5533.27 17-APR-04:12 7209.54 27-APR-04:01 0.00
May 0.241422E+11 0.687046E+10 496.22 0.203102E+11 0.383198E+10 0.00 1.00 01-MAY-04:01 0.00 01-MAY-00:10 31746.76 24-MAY-04:01 29634.94 09-MAY-04:01 11791.64 23-MAY-04:02 7562.06 04-MAY-04:11 0.00
June 0.255344E+11 0.710510E+10 486.60 0.195000E+11 0.603432E+10 0.00 1.00 01-JUN-04:01 0.00 01-JUN-00:10 32585.75 26-JUN-04:01 29036.60 07-JUN-04:01 14160.50 26-JUN-04:05 7712.11 12-JUN-04:01 0.00
July 0.278735E+11 0.717363E+10 490.91 0.184726E+11 0.940091E+10 0.00 1.00 01-JUL-04:01 0.00 01-JUL-00:10 32705.72 20-JUL-04:01 26437.44 01-JUL-04:01 14852.89 19-JUL-04:02 7704.11 02-JUL-06:01 0.00
August 0.274224E+11 0.682738E+10 483.18 0.173770E+11 0.100453E+11 0.00 1.00 01-AUG-04:01 0.00 01-AUG-00:10 32314.25 19-AUG-04:01 25672.16 09-AUG-04:01 13416.23 17-AUG-04:04 7414.74 08-AUG-04:01 0.00
September 0.232087E+11 0.583927E+10 460.60 0.156647E+11 0.754407E+10 0.00 1.00 01-SEP-04:01 0.00 01-SEP-00:10 32632.48 10-SEP-06:02 26709.74 27-SEP-04:01 16124.47 10-SEP-06:02 7157.68 02-SEP-04:01 0.00
October 0.183994E+11 0.472073E+10 467.84 0.154053E+11 0.299405E+10 0.00 1.00 01-OCT-06:01 0.00 01-OCT-00:10 31169.15 12-OCT-04:01 28686.31 23-OCT-04:01 10153.38 12-OCT-04:02 6881.64 04-OCT-04:01 0.00
November 0.108609E+11 0.276285E+10 402.12 0.961098E+10 0.124988E+10 0.00 1.00 01-NOV-04:01 0.00 01-NOV-00:10 29865.48 09-NOV-05:01 27520.13 13-NOV-05:01 5299.32 18-NOV-05:02 6449.07 09-NOV-05:01 0.00
December 0.341138E+10 0.901741E+09 280.10 0.299139E+10 0.419990E+09 0.00 0.66 01-DEC-15:20 0.00 01-DEC-00:10 8341.80 01-DEC-15:30 8000.49 01-DEC-15:10 1174.23 16-DEC-15:50 2076.63 01-DEC-15:10 0.00
                                       
Annual Sum or Average 0.196362E+12 0.518273E+11 4932.12 0.151220E+12 0.451414E+11 0.00                         0.00
Minimum of Months 0.198089E+10 0.531377E+09 205.08 0.177805E+10 0.202844E+09 0.00 0.57   0.00   7051.64   6459.55   1072.15   1813.58   0.00
Maximum of Months 0.278735E+11 0.717363E+10 496.22 0.203102E+11 0.100453E+11 0.00 1.00   0.00   32705.72   29850.42   16124.47   7712.11   0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.16 15.97 14.20 42.10 47.16 5.33 0.00 0.00
February 38.69 21.68 17.02 59.80 40.00 0.00 0.00 0.00
March 51.47 30.70 20.78 88.08 29.48 0.00 0.00 0.00
April 67.22 47.22 19.99 126.48 18.63 0.00 0.00 0.00
May 71.00 49.19 21.81 139.81 10.15 0.00 0.00 0.00
June 66.53 42.50 24.04 134.00 6.22 0.00 0.00 0.00
July 46.39 16.72 29.67 96.44 3.93 0.00 0.00 0.00
August 39.94 11.37 28.57 82.42 5.75 0.00 0.00 0.00
September 41.51 17.83 23.68 79.29 11.20 0.00 0.00 0.00
October 45.99 29.16 16.83 83.30 27.07 0.00 0.00 0.00
November 38.36 25.24 13.12 62.55 40.59 0.00 0.00 0.00
December 29.30 15.65 13.65 41.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 47.22 26.91 20.31 86.38 23.98 5.33 0.00 0.00
Minimum of Months 29.30 11.37 13.12 41.57 3.93 0.00 0.00 0.00
Maximum of Months 71.00 49.19 29.67 139.81 48.48 5.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: POINT_OF_SALE_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 794.50 482.76 311.74 1191.20 673.49 0.00 0.00 0.00
February 755.45 419.60 335.85 1224.97 564.50 0.00 0.00 0.00
March 645.93 285.30 360.63 1211.69 385.53 0.00 0.00 0.00
April 453.70 128.05 325.65 1115.54 186.58 0.00 0.00 0.00
May 326.27 24.15 302.12 992.06 64.81 0.00 0.00 0.00
June 298.46 5.09 293.36 958.30 32.78 0.00 0.00 0.00
July 311.32 4.28 307.04 889.39 20.48 0.00 0.00 0.00
August 330.24 17.64 312.60 854.53 49.27 0.00 0.00 0.00
September 442.72 114.91 327.81 1002.25 113.71 0.00 0.00 0.00
October 761.65 425.30 336.35 1505.22 348.66 0.00 0.00 0.00
November 951.34 628.81 322.52 1651.03 561.54 0.00 0.00 0.00
December 849.04 532.03 317.01 1312.32 687.25 0.00 0.00 0.00
                 
Annual Sum or Average 575.69 254.71 320.98 1158.25 306.19 0.00 0.00 0.00
Minimum of Months 298.46 4.28 293.36 854.53 20.48 0.00 0.00 0.00
Maximum of Months 951.34 628.81 360.63 1651.03 687.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FRONT_RETAIL_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 794.50 482.76 311.74 1195.67 650.16 0.00 0.00 0.00
February 755.45 419.60 335.85 1225.53 546.19 0.00 0.00 0.00
March 645.93 285.30 360.63 1206.61 371.38 0.00 0.00 0.00
April 453.70 128.05 325.65 1109.15 174.58 0.00 0.00 0.00
May 326.27 24.15 302.12 987.56 57.69 0.00 0.00 0.00
June 298.46 5.09 293.36 957.68 27.19 0.00 0.00 0.00
July 311.32 4.28 307.04 887.87 15.84 0.00 0.00 0.00
August 330.24 17.64 312.60 850.19 41.62 0.00 0.00 0.00
September 442.72 114.91 327.81 997.68 102.78 0.00 0.00 0.00
October 761.65 425.30 336.35 1499.04 337.56 0.00 0.00 0.00
November 951.34 628.81 322.52 1646.95 548.37 0.00 0.00 0.00
December 849.04 532.03 317.01 1314.97 668.37 0.00 0.00 0.00
                 
Annual Sum or Average 575.69 254.71 320.98 1155.78 293.98 0.00 0.00 0.00
Minimum of Months 298.46 4.28 293.36 850.19 15.84 0.00 0.00 0.00
Maximum of Months 951.34 628.81 360.63 1646.95 668.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FRONT_ENTRY_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 163.46 99.32 64.14 257.14 119.14 0.00 0.00 0.00
February 155.42 86.33 69.10 253.49 106.23 0.00 0.00 0.00
March 132.89 58.70 74.19 233.57 81.19 0.00 0.00 0.00
April 93.34 26.34 67.00 185.06 48.31 0.00 0.00 0.00
May 67.13 4.97 62.16 139.06 23.66 0.00 0.00 0.00
June 61.40 1.05 60.36 130.69 14.13 0.00 0.00 0.00
July 64.05 0.88 63.17 129.18 9.69 9.83 0.00 0.00
August 67.94 3.63 64.31 132.79 18.25 8.67 0.00 0.00
September 91.08 23.64 67.44 169.01 33.93 15.00 0.00 0.00
October 156.70 87.50 69.20 280.00 83.91 0.00 0.00 0.00
November 195.73 129.37 66.35 326.67 116.41 0.00 0.00 0.00
December 174.68 109.46 65.22 278.05 124.58 0.00 0.00 0.00
                 
Annual Sum or Average 118.44 52.40 66.04 209.27 64.74 33.50 0.00 0.00
Minimum of Months 61.40 0.88 60.36 129.18 9.69 0.00 0.00 0.00
Maximum of Months 195.73 129.37 74.19 326.67 124.58 15.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80786854.40 42764382.15 38022472.25 0.112766E+09 0.126301E+09
February 93609573.47 52437180.53 41172392.95 0.144658E+09 96758549.85
March 0.137868E+09 82217233.48 55650662.70 0.235926E+09 78960835.25
April 0.174224E+09 0.122406E+09 51817491.76 0.327834E+09 48281194.19
May 0.190163E+09 0.131739E+09 58424633.56 0.374468E+09 27176898.76
June 0.172451E+09 0.110150E+09 62300803.33 0.347317E+09 16130211.05
July 0.124249E+09 44786699.94 79462329.90 0.258311E+09 10537233.49
August 0.106964E+09 30452766.57 76510912.97 0.220766E+09 15396489.38
September 0.107582E+09 46214974.01 61367348.56 0.205513E+09 29024569.45
October 0.123191E+09 78107934.66 45083162.34 0.223110E+09 72502475.45
November 99431062.38 65419366.81 34011695.57 0.162121E+09 0.105204E+09
December 78476202.70 41908053.33 36568149.36 0.111338E+09 0.129858E+09
           
Annual Sum or Average 0.148900E+10 0.848604E+09 0.640392E+09 0.272413E+10 0.756132E+09
Minimum of Months 78476202.70 30452766.57 34011695.57 0.111338E+09 10537233.49
Maximum of Months 0.190163E+09 0.131739E+09 79462329.90 0.374468E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: POINT_OF_SALE_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.212798E+10 0.129301E+10 0.834966E+09 0.319052E+10 0.180388E+10
February 0.182759E+10 0.101509E+10 0.812495E+09 0.296346E+10 0.136563E+10
March 0.173006E+10 0.764151E+09 0.965907E+09 0.324538E+10 0.103261E+10
April 0.117600E+10 0.331902E+09 0.844098E+09 0.289148E+10 0.483613E+09
May 0.873891E+09 64691319.57 0.809199E+09 0.265714E+10 0.173583E+09
June 0.773598E+09 13201173.10 0.760397E+09 0.248393E+10 84967604.73
July 0.833833E+09 11468652.81 0.822365E+09 0.238214E+10 54866553.28
August 0.884520E+09 47239897.32 0.837280E+09 0.228877E+10 0.131962E+09
September 0.114752E+10 0.297840E+09 0.849679E+09 0.259783E+10 0.294738E+09
October 0.203999E+10 0.113912E+10 0.900871E+09 0.403157E+10 0.933847E+09
November 0.246586E+10 0.162988E+10 0.835981E+09 0.427946E+10 0.145552E+10
December 0.227408E+10 0.142500E+10 0.849078E+09 0.351492E+10 0.184074E+10
           
Annual Sum or Average 0.181549E+11 0.803260E+10 0.101223E+11 0.365266E+11 0.965595E+10
Minimum of Months 0.773598E+09 11468652.81 0.760397E+09 0.228877E+10 54866553.28
Maximum of Months 0.246586E+10 0.162988E+10 0.965907E+09 0.427946E+10 0.184074E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: FRONT_RETAIL_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.212798E+10 0.129301E+10 0.834966E+09 0.320248E+10 0.174139E+10
February 0.182759E+10 0.101509E+10 0.812495E+09 0.296479E+10 0.132135E+10
March 0.173006E+10 0.764151E+09 0.965907E+09 0.323180E+10 0.994691E+09
April 0.117600E+10 0.331902E+09 0.844098E+09 0.287491E+10 0.452504E+09
May 0.873891E+09 64691319.57 0.809199E+09 0.264509E+10 0.154528E+09
June 0.773598E+09 13201173.10 0.760397E+09 0.248231E+10 70473047.76
July 0.833833E+09 11468652.81 0.822365E+09 0.237807E+10 42426684.87
August 0.884520E+09 47239897.32 0.837280E+09 0.227715E+10 0.111469E+09
September 0.114752E+10 0.297840E+09 0.849679E+09 0.258599E+10 0.266404E+09
October 0.203999E+10 0.113912E+10 0.900871E+09 0.401504E+10 0.904133E+09
November 0.246586E+10 0.162988E+10 0.835981E+09 0.426890E+10 0.142138E+10
December 0.227408E+10 0.142500E+10 0.849078E+09 0.352202E+10 0.179016E+10
           
Annual Sum or Average 0.181549E+11 0.803260E+10 0.101223E+11 0.364485E+11 0.927090E+10
Minimum of Months 0.773598E+09 11468652.81 0.760397E+09 0.227715E+10 42426684.87
Maximum of Months 0.246586E+10 0.162988E+10 0.965907E+09 0.426890E+10 0.179016E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: FRONT_ENTRY_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.437805E+09 0.266021E+09 0.171783E+09 0.688714E+09 0.319099E+09
February 0.376003E+09 0.208843E+09 0.167160E+09 0.613234E+09 0.257001E+09
March 0.355937E+09 0.157214E+09 0.198723E+09 0.625586E+09 0.217467E+09
April 0.241946E+09 68284734.83 0.173662E+09 0.479663E+09 0.125223E+09
May 0.179791E+09 13309429.74 0.166482E+09 0.372466E+09 63371150.99
June 0.159157E+09 2715976.22 0.156441E+09 0.338755E+09 36621800.38
July 0.171550E+09 2359531.85 0.169191E+09 0.346009E+09 25963913.70
August 0.181978E+09 9719017.93 0.172259E+09 0.355659E+09 48889399.23
September 0.236087E+09 61276922.44 0.174810E+09 0.438071E+09 87942443.41
October 0.419702E+09 0.234360E+09 0.185342E+09 0.749964E+09 0.224746E+09
November 0.507320E+09 0.335328E+09 0.171992E+09 0.846717E+09 0.301723E+09
December 0.467862E+09 0.293175E+09 0.174687E+09 0.744731E+09 0.333686E+09
           
Annual Sum or Average 0.373514E+10 0.165261E+10 0.208253E+10 0.659957E+10 0.204173E+10
Minimum of Months 0.159157E+09 2359531.85 0.156441E+09 0.338755E+09 25963913.70
Maximum of Months 0.507320E+09 0.335328E+09 0.198723E+09 0.846717E+09 0.333686E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 673.63 754.49 482.60 255.46 227.14 0.00 0.00
February 956.73 639.94 619.11 346.81 272.30 0.00 0.00
March 1409.35 471.69 823.58 491.14 332.44 0.00 0.00
April 2023.67 298.03 1075.46 755.59 319.86 0.00 0.00
May 2236.96 162.35 1135.98 786.97 349.01 0.00 0.00
June 2143.93 99.57 1064.51 679.94 384.57 0.00 0.00
July 1543.08 62.95 742.23 267.54 474.69 0.00 0.00
August 1318.79 91.97 638.97 181.92 457.05 0.00 0.00
September 1268.60 179.16 664.09 285.28 378.81 0.00 0.00
October 1332.79 433.11 735.91 466.59 269.31 0.00 0.00
November 1000.75 649.41 613.77 403.82 209.95 0.00 0.00
December 665.10 775.73 468.79 250.35 218.45 0.00 0.00
               
Annual Sum or Average 1382.10 383.63 755.45 430.54 324.91 0.00 0.00
Minimum of Months 665.10 62.95 468.79 181.92 209.95 0.00 0.00
Maximum of Months 2236.96 775.73 1135.98 786.97 474.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1191.20 673.49 794.50 482.76 311.74 0.00 0.00
February 1224.97 564.50 755.45 419.60 335.85 0.00 0.00
March 1211.69 385.53 645.93 285.30 360.63 0.00 0.00
April 1115.54 186.58 453.70 128.05 325.65 0.00 0.00
May 992.06 64.81 326.27 24.15 302.12 0.00 0.00
June 958.30 32.78 298.46 5.09 293.36 0.00 0.00
July 889.39 20.48 311.32 4.28 307.04 0.00 0.00
August 854.53 49.27 330.24 17.64 312.60 0.00 0.00
September 1002.25 113.71 442.72 114.91 327.81 0.00 0.00
October 1505.22 348.66 761.65 425.30 336.35 0.00 0.00
November 1651.03 561.54 951.34 628.81 322.52 0.00 0.00
December 1312.32 687.25 849.04 532.03 317.01 0.00 0.00
               
Annual Sum or Average 1158.25 306.19 575.69 254.71 320.98 0.00 0.00
Minimum of Months 854.53 20.48 298.46 4.28 293.36 0.00 0.00
Maximum of Months 1651.03 687.25 951.34 628.81 360.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1195.67 650.16 794.50 482.76 311.74 0.00 0.00
February 1225.53 546.19 755.45 419.60 335.85 0.00 0.00
March 1206.61 371.38 645.93 285.30 360.63 0.00 0.00
April 1109.15 174.58 453.70 128.05 325.65 0.00 0.00
May 987.56 57.69 326.27 24.15 302.12 0.00 0.00
June 957.68 27.19 298.46 5.09 293.36 0.00 0.00
July 887.87 15.84 311.32 4.28 307.04 0.00 0.00
August 850.19 41.62 330.24 17.64 312.60 0.00 0.00
September 997.68 102.78 442.72 114.91 327.81 0.00 0.00
October 1499.04 337.56 761.65 425.30 336.35 0.00 0.00
November 1646.95 548.37 951.34 628.81 322.52 0.00 0.00
December 1314.97 668.37 849.04 532.03 317.01 0.00 0.00
               
Annual Sum or Average 1155.78 293.98 575.69 254.71 320.98 0.00 0.00
Minimum of Months 850.19 15.84 298.46 4.28 293.36 0.00 0.00
Maximum of Months 1646.95 668.37 951.34 628.81 360.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 257.14 119.14 163.46 99.32 64.14 0.00 0.00
February 253.49 106.23 155.42 86.33 69.10 0.00 0.00
March 233.57 81.19 132.89 58.70 74.19 0.00 0.00
April 185.06 48.31 93.34 26.34 67.00 0.00 0.00
May 139.06 23.66 67.13 4.97 62.16 0.00 0.00
June 130.69 14.13 61.40 1.05 60.36 0.00 0.00
July 129.18 9.69 64.05 0.88 63.17 0.00 0.00
August 132.79 18.25 67.94 3.63 64.31 0.00 0.00
September 169.01 33.93 91.08 23.64 67.44 0.00 0.00
October 280.00 83.91 156.70 87.50 69.20 0.00 0.00
November 326.67 116.41 195.73 129.37 66.35 0.00 0.00
December 278.05 124.58 174.68 109.46 65.22 0.00 0.00
               
Annual Sum or Average 209.27 64.74 118.44 52.40 66.04 0.00 0.00
Minimum of Months 129.18 9.69 61.40 0.88 60.36 0.00 0.00
Maximum of Months 326.67 124.58 195.73 129.37 74.19 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.180425E+10 0.202082E+10 0.129259E+10 0.684230E+09 0.608360E+09 0.00 0.00
February 0.231453E+10 0.154814E+10 0.149775E+10 0.838995E+09 0.658758E+09 0.00 0.00
March 0.377481E+10 0.126337E+10 0.220589E+10 0.131548E+10 0.890411E+09 0.00 0.00
April 0.524535E+10 0.772499E+09 0.278758E+10 0.195850E+10 0.829080E+09 0.00 0.00
May 0.599148E+10 0.434830E+09 0.304262E+10 0.210782E+10 0.934794E+09 0.00 0.00
June 0.555707E+10 0.258083E+09 0.275922E+10 0.176241E+10 0.996813E+09 0.00 0.00
July 0.413298E+10 0.168596E+09 0.198798E+10 0.716587E+09 0.127140E+10 0.00 0.00
August 0.353226E+10 0.246344E+09 0.171142E+10 0.487244E+09 0.122417E+10 0.00 0.00
September 0.328821E+10 0.464393E+09 0.172132E+10 0.739440E+09 0.981878E+09 0.00 0.00
October 0.356976E+10 0.116004E+10 0.197106E+10 0.124973E+10 0.721331E+09 0.00 0.00
November 0.259394E+10 0.168326E+10 0.159090E+10 0.104671E+10 0.544187E+09 0.00 0.00
December 0.178140E+10 0.207773E+10 0.125562E+10 0.670529E+09 0.585090E+09 0.00 0.00
               
Annual Sum or Average 0.435861E+11 0.120981E+11 0.238239E+11 0.135777E+11 0.102463E+11 0.00 0.00
Minimum of Months 0.178140E+10 0.168596E+09 0.125562E+10 0.487244E+09 0.544187E+09 0.00 0.00
Maximum of Months 0.599148E+10 0.207773E+10 0.304262E+10 0.210782E+10 0.127140E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.319052E+10 0.180388E+10 0.212798E+10 0.129301E+10 0.834966E+09 0.00 0.00
February 0.296346E+10 0.136563E+10 0.182759E+10 0.101509E+10 0.812495E+09 0.00 0.00
March 0.324538E+10 0.103261E+10 0.173006E+10 0.764151E+09 0.965907E+09 0.00 0.00
April 0.289148E+10 0.483613E+09 0.117600E+10 0.331902E+09 0.844098E+09 0.00 0.00
May 0.265714E+10 0.173583E+09 0.873891E+09 64691319.57 0.809199E+09 0.00 0.00
June 0.248393E+10 84967604.73 0.773598E+09 13201173.10 0.760397E+09 0.00 0.00
July 0.238214E+10 54866553.28 0.833833E+09 11468652.81 0.822365E+09 0.00 0.00
August 0.228877E+10 0.131962E+09 0.884520E+09 47239897.32 0.837280E+09 0.00 0.00
September 0.259783E+10 0.294738E+09 0.114752E+10 0.297840E+09 0.849679E+09 0.00 0.00
October 0.403157E+10 0.933847E+09 0.203999E+10 0.113912E+10 0.900871E+09 0.00 0.00
November 0.427946E+10 0.145552E+10 0.246586E+10 0.162988E+10 0.835981E+09 0.00 0.00
December 0.351492E+10 0.184074E+10 0.227408E+10 0.142500E+10 0.849078E+09 0.00 0.00
               
Annual Sum or Average 0.365266E+11 0.965595E+10 0.181549E+11 0.803260E+10 0.101223E+11 0.00 0.00
Minimum of Months 0.228877E+10 54866553.28 0.773598E+09 11468652.81 0.760397E+09 0.00 0.00
Maximum of Months 0.427946E+10 0.184074E+10 0.246586E+10 0.162988E+10 0.965907E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.320248E+10 0.174139E+10 0.212798E+10 0.129301E+10 0.834966E+09 0.00 0.00
February 0.296479E+10 0.132135E+10 0.182759E+10 0.101509E+10 0.812495E+09 0.00 0.00
March 0.323180E+10 0.994691E+09 0.173006E+10 0.764151E+09 0.965907E+09 0.00 0.00
April 0.287491E+10 0.452504E+09 0.117600E+10 0.331902E+09 0.844098E+09 0.00 0.00
May 0.264509E+10 0.154528E+09 0.873891E+09 64691319.57 0.809199E+09 0.00 0.00
June 0.248231E+10 70473047.76 0.773598E+09 13201173.10 0.760397E+09 0.00 0.00
July 0.237807E+10 42426684.87 0.833833E+09 11468652.81 0.822365E+09 0.00 0.00
August 0.227715E+10 0.111469E+09 0.884520E+09 47239897.32 0.837280E+09 0.00 0.00
September 0.258599E+10 0.266404E+09 0.114752E+10 0.297840E+09 0.849679E+09 0.00 0.00
October 0.401504E+10 0.904133E+09 0.203999E+10 0.113912E+10 0.900871E+09 0.00 0.00
November 0.426890E+10 0.142138E+10 0.246586E+10 0.162988E+10 0.835981E+09 0.00 0.00
December 0.352202E+10 0.179016E+10 0.227408E+10 0.142500E+10 0.849078E+09 0.00 0.00
               
Annual Sum or Average 0.364485E+11 0.927090E+10 0.181549E+11 0.803260E+10 0.101223E+11 0.00 0.00
Minimum of Months 0.227715E+10 42426684.87 0.773598E+09 11468652.81 0.760397E+09 0.00 0.00
Maximum of Months 0.426890E+10 0.179016E+10 0.246586E+10 0.162988E+10 0.965907E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.688714E+09 0.319099E+09 0.437805E+09 0.266021E+09 0.171783E+09 0.00 0.00
February 0.613234E+09 0.257001E+09 0.376003E+09 0.208843E+09 0.167160E+09 0.00 0.00
March 0.625586E+09 0.217467E+09 0.355937E+09 0.157214E+09 0.198723E+09 0.00 0.00
April 0.479663E+09 0.125223E+09 0.241946E+09 68284734.83 0.173662E+09 0.00 0.00
May 0.372466E+09 63371150.99 0.179791E+09 13309429.74 0.166482E+09 0.00 0.00
June 0.338755E+09 36621800.38 0.159157E+09 2715976.22 0.156441E+09 0.00 0.00
July 0.346009E+09 25963913.70 0.171550E+09 2359531.85 0.169191E+09 0.00 0.00
August 0.355659E+09 48889399.23 0.181978E+09 9719017.93 0.172259E+09 0.00 0.00
September 0.438071E+09 87942443.41 0.236087E+09 61276922.44 0.174810E+09 0.00 0.00
October 0.749964E+09 0.224746E+09 0.419702E+09 0.234360E+09 0.185342E+09 0.00 0.00
November 0.846717E+09 0.301723E+09 0.507320E+09 0.335328E+09 0.171992E+09 0.00 0.00
December 0.744731E+09 0.333686E+09 0.467862E+09 0.293175E+09 0.174687E+09 0.00 0.00
               
Annual Sum or Average 0.659957E+10 0.204173E+10 0.373514E+10 0.165261E+10 0.208253E+10 0.00 0.00
Minimum of Months 0.338755E+09 25963913.70 0.159157E+09 2359531.85 0.156441E+09 0.00 0.00
Maximum of Months 0.846717E+09 0.333686E+09 0.507320E+09 0.335328E+09 0.198723E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.39 10.38 7.87 1.20 0.38 63.33 149.51 0.00
February 16.97 12.78 9.69 1.81 4.63 75.94 163.32 0.01
March 22.37 15.60 11.23 1.86 10.07 92.70 193.23 0.00
April 29.13 18.33 11.93 1.64 16.17 89.20 259.84 0.01
May 32.98 21.97 16.72 2.17 21.14 97.31 248.85 0.02
June 33.59 24.39 20.62 1.55 23.45 107.22 203.36 0.06
July 31.67 26.29 24.51 2.27 24.88 132.35 83.14 0.02
August 30.03 26.31 25.11 1.75 23.81 127.44 60.46 0.00
September 28.75 24.70 23.21 1.33 20.22 105.62 105.60 0.08
October 25.09 18.74 15.36 0.77 12.83 75.09 190.08 0.00
November 19.63 14.46 10.99 0.66 5.78 58.54 201.10 0.00
December 14.52 10.88 7.89 0.97 0.94 60.91 153.60 0.01
                 
Annual Sum or Average 24.88 18.77 15.46 1.50 13.74 90.59 167.44 0.02
Minimum of Months 13.39 10.38 7.87 0.66 0.38 58.54 60.46 0.00
Maximum of Months 33.59 26.31 25.11 2.27 24.88 132.35 259.84 0.08



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 23.60 12-JAN-14:00 14.20 7.40 3.80 8.15 163.00 476.00
February 27.10 22-FEB-14:00 16.20 9.10 1.50 15.39 225.00 451.00
March 35.60 28-MAR-14:00 18.50 7.70 0.00 19.52 182.00 699.00
April 40.30 15-APR-14:00 20.67 10.00 6.70 28.43 201.00 649.50
May 44.50 03-MAY-14:00 20.64 5.30 2.80 28.91 150.00 809.00
June 44.60 07-JUN-15:00 21.53 9.10 3.10 28.43 167.00 640.50
July 40.40 02-JUL-15:00 26.36 21.60 2.10 29.87 200.00 545.50
August 37.30 07-AUG-14:00 26.58 22.90 3.00 29.87 311.00 370.00
September 37.50 17-SEP-19:00 27.68 24.60 0.20 28.59 0.00 0.00
October 36.40 02-OCT-14:20 21.05 13.00 1.80 21.61 187.33 678.83
November 30.30 04-NOV-13:00 17.17 8.90 1.10 14.84 155.00 710.00
December 24.60 28-DEC-13:00 15.30 8.90 2.80 10.88 181.50 535.00
                 
Annual Sum or Average                
Minimum of Months 23.60   14.20 5.30 0.00 8.15 0.00 0.00
Maximum of Months 44.60   27.68 24.60 6.70 29.87 311.00 809.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 4.80 05-JAN-06:00 4.73 4.60 0.00 -10.2 0.00 0.00
February 6.90 02-FEB-05:00 6.67 6.50 0.00 -7.8 0.00 0.00
March 13.30 01-MAR-03:00 10.56 8.30 0.80 -1.4 0.00 0.00
April 17.40 11-APR-04:00 13.58 10.90 0.00 3.06 0.00 0.00
May 22.70 13-MAY-04:00 20.32 19.30 2.10 20.40 0.00 0.00
June 23.30 18-JUN-04:00 21.80 21.20 2.70 17.75 0.00 0.00
July 23.20 19-JUL-02:00 23.20 23.20 2.30 15.39 0.00 0.00
August 23.40 15-AUG-23:00 22.91 22.80 2.40 21.78 0.00 0.00
September 23.00 27-SEP-04:00 20.74 19.70 0.00 10.30 0.00 0.00
October 15.50 31-OCT-04:00 14.07 13.20 0.00 1.80 0.00 0.00
November 9.50 27-NOV-05:00 8.75 8.10 0.00 -5.0 0.00 0.00
December 5.00 21-DEC-04:00 4.08 3.00 0.00 -10.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 4.80   4.08 3.00 0.00 -10.5 0.00 0.00
Maximum of Months 23.40   23.20 23.20 2.70 21.78 0.00 0.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.62 17-JAN-14:00 18.20 14.10 1.00 11.07 198.00 56.50
February 18.14 25-FEB-16:00 21.20 16.60 5.90 10.88 107.50 156.50
March 21.38 10-MAR-18:49 29.25 17.73 2.10 21.44 0.00 0.00
April 23.42 18-APR-13:00 37.10 17.80 5.70 23.49 233.50 671.50
May 27.40 22-MAY-22:00 29.40 26.80 0.00 20.40 0.00 0.00
June 28.92 28-JUN-12:00 34.40 27.50 1.00 25.49 332.50 501.50
July 29.18 01-JUL-16:00 37.20 26.80 2.30 25.66 196.00 196.00
August 29.17 27-AUG-15:00 35.10 27.40 1.30 29.55 256.00 129.00
September 28.10 14-SEP-16:00 33.70 26.40 1.40 26.48 122.50 108.50
October 23.06 06-OCT-10:00 28.60 20.80 1.30 20.22 327.00 348.50
November 18.93 08-NOV-17:10 27.55 14.47 0.17 16.67 28.00 65.33
December 15.64 29-DEC-19:00 16.80 14.90 4.80 13.54 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 15.62   16.80 14.10 0.00 10.88 0.00 0.00
Maximum of Months 29.18   37.20 27.50 5.90 29.55 332.50 671.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.10 17-JAN-13:00 17.80 15.48 0.90 9.72 260.50 81.50
February 16.60 25-FEB-16:00 21.20 18.14 5.90 10.88 107.50 156.50
March 18.30 10-MAR-19:00 27.70 21.26 2.10 21.44 0.00 0.00
April 19.30 26-APR-23:10 28.53 22.04 0.00 15.61 0.00 0.00
May 26.80 22-MAY-22:00 29.40 27.40 0.00 20.40 0.00 0.00
June 27.50 28-JUN-12:00 34.40 28.92 1.00 25.49 332.50 501.50
July 27.30 18-JUL-06:19 29.10 27.70 1.17 26.48 20.00 0.00
August 28.80 12-AUG-07:00 29.10 28.83 2.90 26.81 113.00 6.50
September 26.50 12-SEP-14:00 30.50 27.38 0.90 25.99 260.00 20.00
October 21.10 06-OCT-08:00 25.50 22.41 0.30 17.21 239.00 159.00
November 16.30 08-NOV-21:19 20.10 17.59 0.00 10.95 0.00 0.00
December 14.90 29-DEC-20:10 16.72 15.59 4.73 13.13 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 14.10   16.72 15.48 0.00 9.72 0.00 0.00
Maximum of Months 28.80   34.40 28.92 5.90 26.81 332.50 501.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 20.92 27.26 0.00
February 18.00 13.00 16.00 21.74 33.91 0.00
March 18.00 13.00 16.00 24.21 44.04 0.00
April 18.00 13.00 16.00 27.79 55.91 0.00
May 18.00 13.00 16.00 31.48 58.43 0.00
June 18.00 13.00 16.00 34.27 54.82 0.00
July 18.00 13.00 16.00 35.42 39.75 0.00
August 18.00 13.00 16.00 34.60 34.68 0.00
September 18.00 13.00 16.00 32.04 35.55 0.00
October 18.00 13.00 16.00 28.44 39.44 0.00
November 18.00 13.00 16.00 24.77 33.85 0.00
December 18.00 13.00 16.00 22.02 26.79 0.00
             
Annual Sum or Average 18.00 13.00 16.00 28.18 40.37 0.00
Minimum of Months 18.00 13.00 16.00 20.92 26.79 0.00
Maximum of Months 18.00 13.00 16.00 35.42 58.43 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.196661E+10 -0.184941E+10 0.00 0.00 744.00 0.00 -117204098.9 59.95 0.00 0.00
February 0.175086E+10 -0.164903E+10 0.00 0.00 672.00 0.00 -101833814.5 59.95 0.00 0.00
March 0.185709E+10 -0.174955E+10 0.00 0.00 744.00 0.00 -107540558.2 59.95 0.00 0.00
April 0.159849E+10 -0.149724E+10 0.00 0.00 720.00 0.00 -101242229.1 59.95 0.00 0.00
May 0.147634E+10 -0.137329E+10 0.00 0.00 744.00 0.00 -103052871.1 59.95 0.00 0.00
June 0.131382E+10 -0.121391E+10 0.00 0.00 720.00 0.00 -99908171.5 59.95 0.00 0.00
July 0.126636E+10 -0.116326E+10 0.00 0.00 744.00 0.00 -103101165.7 59.95 0.00 0.00
August 0.134485E+10 -0.124124E+10 0.00 0.00 744.00 0.00 -103612456.9 59.95 0.00 0.00
September 0.140191E+10 -0.130083E+10 0.00 0.00 720.00 0.00 -101083627.4 59.95 0.00 0.00
October 0.159997E+10 -0.149427E+10 0.00 0.00 744.00 0.00 -105702444.7 59.95 0.00 0.00
November 0.171149E+10 -0.160595E+10 0.00 0.00 720.00 0.00 -105549586.8 59.95 0.00 0.00
December 0.191433E+10 -0.179877E+10 0.00 0.00 744.00 0.00 -115560467.1 59.95 0.00 0.00
                     
Annual Sum or Average 0.192021E+11 -0.179367E+11 0.00 0.00 8760.00 0.00 -0.126539E+10 59.95 0.00 0.00
Minimum of Months 0.126636E+10 -0.184941E+10 0.00 0.00 672.00 0.00 -117204098.9 59.95 0.00 0.00
Maximum of Months 0.196661E+10 -0.116326E+10 0.00 0.00 744.00 0.00 -99908171.5 59.95 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.82 0.63 27-JAN-12:30 212.91 5.50 0.00 0.00 175.63 4.11 0.00 0.00
February 303.83 0.78 0.50 12-FEB-11:00 254.41 6.34 0.00 0.00 210.86 4.85 0.00 0.00
March 364.50 0.73 0.50 02-MAR-11:09 1668.29 7.41 0.00 62.00 1798.63 5.84 0.00 55.17
April 379.83 0.76 0.50 01-APR-11:20 278.99 7.74 0.00 7.17 231.98 6.12 0.00 5.00
May 406.00 0.76 0.50 12-MAY-10:00 280.55 8.96 0.00 13.17 233.61 7.26 0.00 8.50
June 386.67 0.74 0.50 01-JUN-09:50 301.01 9.77 0.00 24.00 249.93 8.02 0.00 14.00
July 379.83 0.70 0.50 01-JUL-11:30 351.48 10.60 0.00 70.33 297.03 8.99 0.00 39.17
August 372.50 0.70 0.50 01-AUG-09:30 395.68 9.98 0.00 91.00 345.90 8.42 0.00 54.00
September 344.33 0.71 0.50 01-SEP-09:50 925.15 8.81 0.00 72.00 920.69 7.22 0.00 48.83
October 347.33 0.77 0.50 04-OCT-10:30 267.31 6.50 0.00 4.17 222.29 5.04 0.00 2.00
November 317.83 0.82 0.67 28-NOV-11:50 212.60 5.21 0.00 0.00 176.16 3.79 0.00 0.00
December 315.50 0.82 0.66 09-DEC-11:00 207.41 5.33 0.00 0.00 170.72 3.93 0.00 0.00
                         
Annual Sum or Average 4237.50 0.76     451.91 7.82 0.00 343.83 425.04 6.26 0.00 226.67
Minimum of Months 303.83 0.70 0.50   207.41 5.21 0.00 0.00 170.72 3.79 0.00 0.00
Maximum of Months 406.00 0.82 0.67   1668.29 10.60 0.00 91.00 1798.63 8.99 0.00 55.17



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FRONT_ENTRY UNIT HEATER HEATING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 11294456.08 3203.41 03-JAN-08:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 6918870.51 2177.50 21-DEC-08:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 18213326.58     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 11294456.08 3203.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.506875E+10 53653.14 17-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.104493E+10 54078.43 12-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 27002175.00 18393.47 26-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.249777E+10 55635.97 25-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.863845E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.506875E+10 55635.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.557578E+10 209541.29 01-JAN-08:12 0.00 0.00 0.00 0.00 0.00
February 0.721730E+09 170708.06 02-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.143383E+10 179430.02 23-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.773134E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.557578E+10 209541.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.371051E+09 30914.02 01-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 58370639.62 23818.60 11-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 55462821.01 5249.61 31-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.484885E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.371051E+09 30914.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.752401E+09 31230.95 17-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.153422E+09 29482.75 11-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.155489E+09 23142.24 31-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.106131E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.752401E+09 31230.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.953066E+09 0.854047E+09 6182.93 24-FEB-16:00 5438.66 0.00
March 0.00 0.00 0.941505E+10 0.857400E+10 52244.82 11-MAR-05:01 43735.10 0.00
April 0.00 0.00 0.248544E+11 0.234524E+11 52587.49 17-APR-04:01 49669.50 0.00
May 0.00 0.00 0.405512E+11 0.359354E+11 54220.53 24-MAY-04:01 42589.08 0.00
June 0.00 0.00 0.441512E+11 0.364326E+11 55525.37 26-JUN-04:01 37923.00 0.00
July 0.00 0.00 0.471208E+11 0.346508E+11 55572.60 20-JUL-04:01 38085.36 0.00
August 0.00 0.00 0.442765E+11 0.311558E+11 54868.20 19-AUG-04:01 41022.59 0.00
September 0.00 0.00 0.336089E+11 0.241996E+11 55530.27 10-SEP-06:02 31790.01 0.00
October 0.00 0.00 0.191719E+11 0.164219E+11 53278.00 12-OCT-04:01 40048.99 0.00
November 0.00 0.00 0.462896E+10 0.417765E+10 49406.94 01-NOV-04:01 41959.05 0.00
December 0.00 0.00 8504901.31 8490187.06 1816.01 01-DEC-15:20 1816.01 0.00
                 
Annual Sum or Average 0.00 0.00 0.268740E+12 0.215863E+12       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.471208E+11 0.364326E+11 55572.60   49669.50 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.344922E+10 0.286954E+10 25058.74 14-JAN-15:10 18676.04 0.00
February 0.00 0.00 0.196772E+11 0.161925E+11 54197.25 24-FEB-16:00 42798.51 0.00
March 0.00 0.00 0.646631E+11 0.538674E+11 217176.57 11-MAR-07:02 164836.77 0.00
April 0.00 0.00 0.114355E+12 0.100858E+12 221169.52 26-APR-06:02 154058.11 0.00
May 0.00 0.00 0.167815E+12 0.134168E+12 228521.39 24-MAY-06:02 133588.73 0.00
June 0.00 0.00 0.185043E+12 0.131041E+12 236586.48 25-JUN-08:62 114346.98 0.00
July 0.00 0.00 0.200189E+12 0.117177E+12 236274.94 19-JUL-06:02 114523.77 0.00
August 0.00 0.00 0.196767E+12 0.107414E+12 238271.93 20-AUG-08:62 109435.18 0.00
September 0.00 0.00 0.157024E+12 0.913235E+11 239374.37 10-SEP-08:62 105140.65 0.00
October 0.00 0.00 0.979742E+11 0.749931E+11 227909.65 12-OCT-06:03 127322.79 0.00
November 0.00 0.00 0.448632E+11 0.370273E+11 66721.19 09-NOV-15:10 56751.11 0.00
December 0.00 0.00 0.820009E+10 0.673008E+10 31325.56 01-DEC-15:10 28794.35 0.00
                 
Annual Sum or Average 0.00 0.00 0.126002E+13 0.873661E+12       0.00
Minimum of Months 0.00 0.00 0.344922E+10 0.286954E+10 25058.74   18676.04 0.00
Maximum of Months 0.00 0.00 0.200189E+12 0.134168E+12 239374.37   164836.77 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.386998E+10 0.351964E+10 9134.96 12-JAN-16:00 8476.51 0.00
February 0.00 0.00 0.688776E+10 0.617162E+10 32310.41 23-FEB-05:02 30578.39 0.00
March 0.00 0.00 0.139410E+11 0.125036E+11 33798.51 11-MAR-05:01 29498.79 0.00
April 0.00 0.00 0.205908E+11 0.190034E+11 34114.02 17-APR-04:01 31932.55 0.00
May 0.00 0.00 0.272531E+11 0.233145E+11 35242.70 24-MAY-04:01 26332.95 0.00
June 0.00 0.00 0.289052E+11 0.226623E+11 36152.22 26-JUN-04:01 23482.72 0.00
July 0.00 0.00 0.312028E+11 0.215085E+11 36235.80 20-JUL-04:01 23521.49 0.00
August 0.00 0.00 0.308022E+11 0.204436E+11 35775.02 19-AUG-04:01 25363.46 0.00
September 0.00 0.00 0.264426E+11 0.185719E+11 35991.19 10-SEP-06:02 20094.84 0.00
October 0.00 0.00 0.213686E+11 0.182600E+11 34517.29 12-OCT-04:01 25567.41 0.00
November 0.00 0.00 0.136196E+11 0.122758E+11 33186.13 09-NOV-05:01 29991.22 0.00
December 0.00 0.00 0.578508E+10 0.519220E+10 14896.17 29-DEC-05:03 13369.74 0.00
                 
Annual Sum or Average 0.00 0.00 0.230669E+12 0.183427E+12       0.00
Minimum of Months 0.00 0.00 0.386998E+10 0.351964E+10 9134.96   8476.51 0.00
Maximum of Months 0.00 0.00 0.312028E+11 0.233145E+11 36235.80   31932.55 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.198089E+10 0.177805E+10 7051.64 12-JAN-15:50 6437.87 0.00
February 0.00 0.00 0.470480E+10 0.415444E+10 28989.22 23-FEB-05:02 26240.83 0.00
March 0.00 0.00 0.110566E+11 0.974406E+10 30413.57 11-MAR-05:01 25360.06 0.00
April 0.00 0.00 0.177667E+11 0.162117E+11 30628.19 17-APR-04:01 27756.34 0.00
May 0.00 0.00 0.241422E+11 0.203102E+11 31746.76 24-MAY-04:01 22534.54 0.00
June 0.00 0.00 0.255344E+11 0.195000E+11 32585.75 26-JUN-04:01 19802.55 0.00
July 0.00 0.00 0.278735E+11 0.184726E+11 32705.72 20-JUL-04:01 19898.33 0.00
August 0.00 0.00 0.274224E+11 0.173770E+11 32314.25 19-AUG-04:01 21414.26 0.00
September 0.00 0.00 0.232087E+11 0.156647E+11 32632.48 10-SEP-06:02 16508.01 0.00
October 0.00 0.00 0.183994E+11 0.154053E+11 31169.15 12-OCT-04:01 21392.27 0.00
November 0.00 0.00 0.108609E+11 0.961098E+10 29865.48 09-NOV-05:01 25446.76 0.00
December 0.00 0.00 0.341138E+10 0.299139E+10 8341.80 01-DEC-15:30 7941.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.196362E+12 0.151220E+12       0.00
Minimum of Months 0.00 0.00 0.198089E+10 0.177805E+10 7051.64   6437.87 0.00
Maximum of Months 0.00 0.00 0.278735E+11 0.203102E+11 32705.72   27756.34 0.00



Table of Contents

Report: FanReportMonthly

For: FRONT_ENTRY UNIT HEATER FAN

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 521708.53 0.00 67.12 03-JAN-08:05 0.08
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 384497.55 0.00 67.12 21-DEC-08:04 0.08
           
Annual Sum or Average 906206.08 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 521708.53 0.00 67.12   0.08



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.174296E+10 0.34 2661.43 01-JAN-07:01 0.89
February 0.155565E+10 0.33 2661.43 01-FEB-05:02 0.90
March 0.174598E+10 0.33 2661.43 10-MAR-05:01 0.89
April 0.173325E+10 0.35 2661.43 01-APR-04:01 0.89
May 0.207135E+10 0.38 2661.43 01-MAY-04:01 0.90
June 0.222250E+10 0.42 2661.43 01-JUN-04:01 0.89
July 0.222119E+10 0.40 2661.43 01-JUL-04:01 0.89
August 0.202941E+10 0.37 2661.43 01-AUG-04:01 0.89
September 0.176709E+10 0.35 2661.43 01-SEP-04:01 0.89
October 0.174448E+10 0.34 2661.43 01-OCT-06:01 0.89
November 0.164445E+10 0.32 2562.15 01-NOV-04:01 0.88
December 0.172640E+10 0.33 2661.43 10-DEC-07:02 0.89
           
Annual Sum or Average 0.222047E+11 0.36      
Minimum of Months 0.155565E+10 0.32 2562.15   0.88
Maximum of Months 0.222250E+10 0.42 2661.43   0.90



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.909555E+10 0.51 14156.59 01-JAN-08:12 1.41
February 0.823933E+10 0.51 11398.53 02-FEB-07:03 1.28
March 0.924202E+10 0.52 14156.59 11-MAR-07:02 1.40
April 0.908030E+10 0.52 14156.59 01-APR-06:02 1.41
May 0.106768E+11 0.56 14156.59 01-MAY-05:01 1.41
June 0.113128E+11 0.60 14156.59 01-JUN-06:02 1.40
July 0.114595E+11 0.58 14156.59 01-JUL-05:01 1.40
August 0.111410E+11 0.57 14156.59 01-AUG-05:02 1.39
September 0.948818E+10 0.53 14156.59 01-SEP-05:02 1.39
October 0.911392E+10 0.51 14156.59 01-OCT-08:62 1.40
November 0.874537E+10 0.51 5662.64 04-NOV-14:40 0.85
December 0.909705E+10 0.51 12616.06 23-DEC-07:03 1.34
           
Annual Sum or Average 0.116692E+12 0.54      
Minimum of Months 0.823933E+10 0.51 5662.64   0.85
Maximum of Months 0.114595E+11 0.60 14156.59   1.41



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.103234E+10 0.33 1608.29 01-JAN-07:01 0.89
February 0.937636E+09 0.33 1608.29 23-FEB-05:02 0.89
March 0.106709E+10 0.34 1608.29 06-MAR-05:02 0.89
April 0.110929E+10 0.37 1608.29 01-APR-04:01 0.89
May 0.129560E+10 0.42 1608.29 01-MAY-04:01 0.90
June 0.133792E+10 0.44 1608.29 01-JUN-04:01 0.89
July 0.134833E+10 0.42 1608.29 01-JUL-04:01 0.89
August 0.131881E+10 0.40 1608.29 01-AUG-04:01 0.89
September 0.119862E+10 0.38 1608.29 01-SEP-04:01 0.89
October 0.111683E+10 0.36 1608.29 01-OCT-06:01 0.89
November 0.100536E+10 0.34 1608.29 01-NOV-04:01 0.89
December 0.103302E+10 0.33 643.31 02-DEC-12:08 0.54
           
Annual Sum or Average 0.138009E+11 0.37      
Minimum of Months 0.937636E+09 0.33 643.31   0.54
Maximum of Months 0.134833E+10 0.44 1608.29   0.90



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.932664E+09 0.34 1450.45 01-JAN-07:01 0.92
February 0.845002E+09 0.34 1450.45 11-FEB-05:02 0.92
March 0.958597E+09 0.35 1450.45 07-MAR-05:01 0.92
April 0.993606E+09 0.37 1450.45 01-APR-04:01 0.93
May 0.115717E+10 0.41 1450.45 01-MAY-04:01 0.93
June 0.118552E+10 0.43 1450.45 01-JUN-04:01 0.92
July 0.120503E+10 0.42 1450.45 01-JUL-04:01 0.92
August 0.117148E+10 0.40 1450.45 01-AUG-04:01 0.92
September 0.107062E+10 0.39 1450.45 01-SEP-04:01 0.92
October 0.100117E+10 0.36 1450.45 01-OCT-06:01 0.92
November 0.903683E+09 0.34 1450.45 01-NOV-04:01 0.92
December 0.931746E+09 0.34 1222.65 31-DEC-07:01 0.86
           
Annual Sum or Average 0.123563E+11 0.37      
Minimum of Months 0.845002E+09 0.34 1222.65   0.86
Maximum of Months 0.120503E+10 0.43 1450.45   0.93



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.331058E+10 0.00 0.00
February 0.00 0.00 0.00 0.215966E+10 0.00 0.00
March 0.00 0.00 0.00 0.449430E+10 0.00 0.00
April 0.00 0.00 0.00 0.899732E+10 0.00 0.00
May 0.00 0.00 0.00 0.138739E+11 0.00 0.00
June 0.00 0.00 0.00 0.148713E+11 0.00 0.00
July 0.00 0.00 0.00 0.147646E+11 0.00 0.00
August 0.00 0.00 0.00 0.134184E+11 0.00 0.00
September 0.00 0.00 0.00 0.105782E+11 0.00 0.00
October 0.00 0.00 0.00 0.714807E+10 0.00 0.00
November 0.00 0.00 0.00 0.302079E+10 0.00 0.00
December 0.00 0.00 0.00 0.249785E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.991350E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.215966E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.148713E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.119607E+11 0.00 0.00
February 0.00 0.00 0.00 0.145253E+11 0.00 0.00
March 0.00 0.00 0.00 0.289257E+11 0.00 0.00
April 0.00 0.00 0.00 0.448735E+11 0.00 0.00
May 0.00 0.00 0.00 0.632443E+11 0.00 0.00
June 0.00 0.00 0.00 0.673432E+11 0.00 0.00
July 0.00 0.00 0.00 0.671752E+11 0.00 0.00
August 0.00 0.00 0.00 0.640528E+11 0.00 0.00
September 0.00 0.00 0.00 0.523634E+11 0.00 0.00
October 0.00 0.00 0.00 0.382073E+11 0.00 0.00
November 0.00 0.00 0.00 0.224601E+11 0.00 0.00
December 0.00 0.00 0.00 0.121125E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.487244E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.119607E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.673432E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.216963E+10 0.00 0.00
February 0.00 0.00 0.00 0.272936E+10 0.00 0.00
March 0.00 0.00 0.00 0.469529E+10 0.00 0.00
April 0.00 0.00 0.00 0.680644E+10 0.00 0.00
May 0.00 0.00 0.00 0.905672E+10 0.00 0.00
June 0.00 0.00 0.00 0.940825E+10 0.00 0.00
July 0.00 0.00 0.00 0.941938E+10 0.00 0.00
August 0.00 0.00 0.00 0.902984E+10 0.00 0.00
September 0.00 0.00 0.00 0.785562E+10 0.00 0.00
October 0.00 0.00 0.00 0.656701E+10 0.00 0.00
November 0.00 0.00 0.00 0.442375E+10 0.00 0.00
December 0.00 0.00 0.00 0.254971E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.747110E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.216963E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.941938E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.170391E+10 0.00 0.00
February 0.00 0.00 0.00 0.212634E+10 0.00 0.00
March 0.00 0.00 0.00 0.387584E+10 0.00 0.00
April 0.00 0.00 0.00 0.593784E+10 0.00 0.00
May 0.00 0.00 0.00 0.802763E+10 0.00 0.00
June 0.00 0.00 0.00 0.829062E+10 0.00 0.00
July 0.00 0.00 0.00 0.837866E+10 0.00 0.00
August 0.00 0.00 0.00 0.799886E+10 0.00 0.00
September 0.00 0.00 0.00 0.690989E+10 0.00 0.00
October 0.00 0.00 0.00 0.572190E+10 0.00 0.00
November 0.00 0.00 0.00 0.366653E+10 0.00 0.00
December 0.00 0.00 0.00 0.188348E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.645215E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.170391E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.837866E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.174296E+10 0.00 0.506875E+10 0.00 0.00 0.00 0.00 0.00
February 0.155565E+10 0.953066E+09 0.104493E+10 0.00 0.00 0.00 0.00 0.00
March 0.174598E+10 0.941505E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.173325E+10 0.248544E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.207135E+10 0.405512E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.222250E+10 0.441512E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.222119E+10 0.471208E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.202941E+10 0.442765E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.176709E+10 0.336089E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174448E+10 0.191719E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.164445E+10 0.462896E+10 27002175.00 0.00 0.00 0.00 0.00 0.00
December 0.172640E+10 8504901.31 0.249777E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.222047E+11 0.268740E+12 0.863845E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.155565E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.222250E+10 0.471208E+11 0.506875E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.909555E+10 0.344922E+10 0.557578E+10 0.00 0.00 0.00 0.00 0.00
February 0.823933E+10 0.196772E+11 0.721730E+09 0.00 0.00 0.00 0.00 0.00
March 0.924202E+10 0.646631E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.908030E+10 0.114355E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.106768E+11 0.167815E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.113128E+11 0.185043E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.114595E+11 0.200189E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.111410E+11 0.196767E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.948818E+10 0.157024E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.911392E+10 0.979742E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.874537E+10 0.448632E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.909705E+10 0.820009E+10 0.143383E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116692E+12 0.126002E+13 0.773134E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.823933E+10 0.344922E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.114595E+11 0.200189E+12 0.557578E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.103234E+10 0.386998E+10 0.371051E+09 0.00 0.00 0.00 0.00 0.00
February 0.937636E+09 0.688776E+10 58370639.62 0.00 0.00 0.00 0.00 0.00
March 0.106709E+10 0.139410E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.110929E+10 0.205908E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.129560E+10 0.272531E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133792E+10 0.289052E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.134833E+10 0.312028E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.131881E+10 0.308022E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.119862E+10 0.264426E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.111683E+10 0.213686E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.100536E+10 0.136196E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.103302E+10 0.578508E+10 55462821.01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.138009E+11 0.230669E+12 0.484885E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.937636E+09 0.386998E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134833E+10 0.312028E+11 0.371051E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.932664E+09 0.198089E+10 0.752401E+09 0.00 0.00 0.00 0.00 0.00
February 0.845002E+09 0.470480E+10 0.153422E+09 0.00 0.00 0.00 0.00 0.00
March 0.958597E+09 0.110566E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.993606E+09 0.177667E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.115717E+10 0.241422E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.118552E+10 0.255344E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.120503E+10 0.278735E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.117148E+10 0.274224E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.107062E+10 0.232087E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.100117E+10 0.183994E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.903683E+09 0.108609E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.931746E+09 0.341138E+10 0.155489E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.123563E+11 0.196362E+12 0.106131E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.845002E+09 0.198089E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120503E+10 0.278735E+11 0.752401E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.174296E+10 0.00 0.00 0.156763E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.155565E+10 0.00 0.00 0.324023E+09 0.279988E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.174598E+10 0.00 0.00 0.00 0.274832E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.173325E+10 0.00 0.00 0.00 0.726407E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.207135E+10 0.00 0.00 0.00 0.118026E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.222250E+10 0.00 0.00 0.00 0.126488E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.222119E+10 0.00 0.00 0.00 0.125434E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.202941E+10 0.00 0.00 0.00 0.113890E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.176709E+10 0.00 0.00 0.00 0.881113E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174448E+10 0.00 0.00 0.00 0.540359E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.164445E+10 0.00 0.00 8552101.46 0.136779E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.172640E+10 0.00 0.00 0.768927E+09 2526068.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.222047E+11 0.00 0.00 0.266913E+10 0.742612E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.155565E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.222250E+10 0.00 0.00 0.156763E+10 0.126488E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.909555E+10 0.00 0.00 0.178349E+10 0.108166E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.823933E+10 0.00 0.00 0.226527E+09 0.605949E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.924202E+10 0.00 0.00 0.00 0.196837E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.908030E+10 0.00 0.00 0.00 0.357932E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.106768E+11 0.00 0.00 0.00 0.525675E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.113128E+11 0.00 0.00 0.00 0.560305E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.114595E+11 0.00 0.00 0.00 0.557157E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.111410E+11 0.00 0.00 0.00 0.529118E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.948818E+10 0.00 0.00 0.00 0.428752E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.911392E+10 0.00 0.00 0.00 0.290933E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.874537E+10 0.00 0.00 0.00 0.137147E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.909705E+10 0.00 0.00 0.454325E+09 0.256114E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.116692E+12 0.00 0.00 0.246434E+10 0.368088E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.823933E+10 0.00 0.00 0.00 0.108166E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.114595E+11 0.00 0.00 0.178349E+10 0.560305E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.103234E+10 0.00 0.00 0.120620E+09 0.101667E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.937636E+09 0.00 0.00 18467982.77 0.177326E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.106709E+10 0.00 0.00 0.00 0.362819E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.110929E+10 0.00 0.00 0.00 0.569715E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.129560E+10 0.00 0.00 0.00 0.776112E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133792E+10 0.00 0.00 0.00 0.807033E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.134833E+10 0.00 0.00 0.00 0.807105E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.131881E+10 0.00 0.00 0.00 0.771103E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.119862E+10 0.00 0.00 0.00 0.665700E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.111683E+10 0.00 0.00 0.00 0.545018E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.100536E+10 0.00 0.00 0.00 0.341840E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.103302E+10 0.00 0.00 18298869.72 0.149839E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.138009E+11 0.00 0.00 0.157386E+09 0.607528E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.937636E+09 0.00 0.00 0.00 0.101667E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134833E+10 0.00 0.00 0.120620E+09 0.807105E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.932664E+09 0.00 0.00 0.239869E+09 0.531377E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.845002E+09 0.00 0.00 48054866.77 0.123329E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.958597E+09 0.00 0.00 0.00 0.291725E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.993606E+09 0.00 0.00 0.00 0.494423E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.115717E+10 0.00 0.00 0.00 0.687046E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.118552E+10 0.00 0.00 0.00 0.710510E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.120503E+10 0.00 0.00 0.00 0.717363E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.117148E+10 0.00 0.00 0.00 0.682738E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.107062E+10 0.00 0.00 0.00 0.583927E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.100117E+10 0.00 0.00 0.00 0.472073E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.903683E+09 0.00 0.00 0.00 0.276285E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.931746E+09 0.00 0.00 49993104.06 0.901741E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.123563E+11 0.00 0.00 0.337917E+09 0.518273E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.845002E+09 0.00 0.00 0.00 0.531377E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120503E+10 0.00 0.00 0.239869E+09 0.717363E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.805291E+09 0.00 875302.25 0.00 6911823.16 0.217572E+10 0.00 5465.63 0.22
February 0.876939E+09 57101393.45 273532.14 545324.50 10532842.08 0.550415E+09 0.160015E+09 2893.54 0.22
March 0.346357E+09 0.130948E+10 0.00 3260639.61 4376993.06 0.00 0.208331E+09 0.00 0.23
April 0.00 0.423091E+10 0.00 1615652.11 3601194.56 0.00 16089896.39 0.00 0.23
May 0.00 0.911908E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.23
June 0.00 0.120403E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.24
July 0.00 0.153894E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.24
August 0.00 0.155728E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.24
September 0.00 0.115063E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.23
October 13707801.15 0.402574E+10 0.00 2006766.77 0.00 0.00 72041574.69 0.00 0.22
November 0.718099E+09 0.570772E+09 0.00 1061849.43 5192412.79 11105106.30 0.196398E+09 0.00 0.22
December 0.106858E+10 81325.09 1566720.21 3642.45 22270559.03 0.146180E+10 1210598.03 11343.37 0.22
                   
Annual Sum or Average 0.382898E+10 0.738220E+11 2715554.60 8493874.86 52885824.68 0.419903E+10 0.654087E+09 19702.54 0.23
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.22
Maximum of Months 0.106858E+10 0.155728E+11 1566720.21 3260639.61 22270559.03 0.217572E+10 0.208331E+09 11343.37 0.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.236716E+11 0.00 0.00 7693756.65 0.00 0.257255E+10 0.721386E+10 0.00 0.42
February 0.106176E+11 0.252656E+09 0.00 26347228.91 0.00 0.195026E+09 0.775860E+10 0.00 0.43
March 0.256040E+10 0.920755E+10 0.00 30845892.08 31774307.03 0.00 0.373842E+10 0.00 0.44
April 0.146551E+09 0.297569E+11 0.00 5423645.73 0.386643E+09 0.00 0.147296E+09 0.00 0.44
May 0.00 0.640564E+11 0.00 483750.07 0.626714E+09 0.00 0.00 0.00 0.44
June 0.00 0.833358E+11 0.00 0.00 0.837584E+09 0.00 0.00 0.00 0.44
July 0.00 0.103666E+12 0.00 0.00 0.125818E+10 0.00 0.00 0.00 0.44
August 0.00 0.104215E+12 0.00 0.00 0.147652E+10 0.00 0.00 0.00 0.44
September 0.00 0.765953E+11 0.00 0.00 0.131411E+10 0.00 0.00 0.00 0.44
October 0.581121E+09 0.269252E+11 0.00 7277550.11 0.488510E+09 0.00 0.729422E+09 0.00 0.43
November 0.504760E+10 0.402146E+10 0.00 28561931.19 0.00 0.00 0.482432E+10 0.00 0.43
December 0.193921E+11 0.00 0.00 16828557.43 0.00 0.365449E+09 0.976950E+10 0.00 0.42
                   
Annual Sum or Average 0.620169E+11 0.502032E+12 0.00 0.123462E+09 0.642004E+10 0.313303E+10 0.341814E+11 0.00 0.43
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42
Maximum of Months 0.236716E+11 0.104215E+12 0.00 30845892.08 0.147652E+10 0.257255E+10 0.976950E+10 0.00 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.125531E+10 0.00 0.00 9600371.30 0.00 0.168830E+09 0.171206E+10 0.00 0.43
February 0.597940E+09 82555916.21 0.00 10245905.97 0.00 29290057.11 0.895561E+09 0.00 0.43
March 64635066.32 0.111864E+10 0.00 8335818.30 243812.27 0.00 0.394037E+09 0.00 0.44
April 0.00 0.314537E+10 0.00 1851156.98 478324.21 0.00 15851739.27 0.00 0.44
May 0.00 0.681361E+10 0.00 2314.38 944827.42 0.00 0.00 0.00 0.45
June 0.00 0.903541E+10 0.00 0.00 1007137.94 0.00 0.00 0.00 0.46
July 0.00 0.115430E+11 0.00 0.00 1259730.03 0.00 0.00 0.00 0.46
August 0.00 0.117358E+11 0.00 0.00 525839.75 0.00 0.00 0.00 0.46
September 0.00 0.892623E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.45
October 0.00 0.339890E+10 0.00 3009639.54 0.00 0.00 31743123.35 0.00 0.44
November 99827643.17 0.658440E+09 0.00 11475422.41 0.00 0.00 0.562125E+09 0.00 0.43
December 0.948214E+09 779492.68 0.00 13144117.34 0.00 14556859.52 0.156831E+10 0.00 0.43
                   
Annual Sum or Average 0.296593E+10 0.564587E+11 0.00 57664746.22 4459671.63 0.212677E+09 0.517968E+10 0.00 0.44
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Maximum of Months 0.125531E+10 0.117358E+11 0.00 13144117.34 1259730.03 0.168830E+09 0.171206E+10 0.00 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.138134E+10 0.00 0.00 4626324.25 0.00 0.509298E+09 0.126486E+10 0.00 0.43
February 0.754739E+09 63173915.60 0.00 6544989.27 0.00 83292830.37 0.752527E+09 0.00 0.43
March 0.164210E+09 0.105797E+10 0.00 5777669.81 229199.44 0.00 0.341624E+09 0.00 0.44
April 0.00 0.311888E+10 0.00 1335588.98 52665.75 0.00 16449803.48 0.00 0.44
May 0.00 0.671248E+10 0.00 69.94 0.00 0.00 0.00 0.00 0.45
June 0.00 0.883099E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.46
July 0.00 0.112645E+11 0.00 0.00 592266.96 0.00 0.00 0.00 0.45
August 0.00 0.114355E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.46
September 0.00 0.861228E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.45
October 0.00 0.330143E+10 0.00 2433550.98 0.00 0.00 39420080.82 0.00 0.44
November 0.207128E+09 0.626517E+09 0.00 8260939.71 0.00 0.00 0.499285E+09 0.00 0.43
December 0.119643E+10 375911.64 0.00 7549780.29 0.00 94644247.07 0.132321E+10 0.00 0.43
                   
Annual Sum or Average 0.370385E+10 0.550241E+11 0.00 36528913.23 874132.15 0.687236E+09 0.423738E+10 0.00 0.44
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Maximum of Months 0.138134E+10 0.114355E+11 0.00 8260939.71 592266.96 0.509298E+09 0.132321E+10 0.00 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:03

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.151138E+12 0.161868E+10 0.00 0.859170E+11 0.387343E+10
February 0.180267E+12 0.118226E+10 0.00 0.509896E+11 0.402074E+11
March 0.254929E+12 0.572567E+09 0.00 0.472922E+10 0.128053E+12
April 0.290664E+12 -520021317.0 0.00 -0.535942E+11 0.231266E+12
May 0.320615E+12 -0.168313E+10 0.00 -0.122200E+12 0.338763E+12
June 0.300471E+12 -0.165658E+10 0.00 -0.169281E+12 0.367488E+12
July 0.236439E+12 -0.206572E+10 0.00 -0.218175E+12 0.389890E+12
August 0.195681E+12 -0.132641E+10 0.00 -0.216424E+12 0.378107E+12
September 0.210723E+12 -663540156.2 0.00 -0.163329E+12 0.304467E+12
October 0.197216E+12 0.284797E+09 0.00 -0.461802E+11 0.201582E+12
November 0.164080E+12 0.981577E+09 0.00 0.299687E+11 0.952180E+11
December 0.136062E+12 0.168673E+10 0.00 0.813972E+11 0.195178E+11
           
Annual Sum or Average 0.263829E+13 -0.158880E+10 0.00 -0.736182E+12 0.249843E+13
Minimum of Months 0.136062E+12 -0.206572E+10 0.00 -0.218175E+12 0.387343E+10
Maximum of Months 0.320615E+12 0.168673E+10 0.00 0.859170E+11 0.389890E+12