Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19

Tabular Output Report in Format: HTML

Building: RetailStandalone

Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000

Simulation Timestamp: 2024-07-03 12:19:52


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1389.84 605.86 605.86
Net Site Energy 1389.84 605.86 605.86
Total Source Energy 4401.63 1918.76 1918.76
Net Source Energy 4401.63 1918.76 1918.76


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 2293.99
Net Conditioned Building Area 2293.99
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 766.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 207.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 43.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 160.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 17.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1389.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99


End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 766.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 207.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 43.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 160.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 17.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 766.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 207.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 43.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 160.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 17.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 109.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 411.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06
Other 84.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 605.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 109.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 411.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06
Other 84.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 605.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1389.842 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1389.842 100.00
     
Total On-Site and Utility Electric Sources 1389.842 100.00
Total Electricity End Uses 1389.842 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 134.99 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 134.99 100.00
Total Water End Uses 134.99 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 4910.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ZoneHeatingSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ZoneElectricSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

SpaceGainsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

PeakSpaceGainsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

SpaceGainComponentsAtCoolingPeakMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ComfortReportSimple55Monthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

OccupantComfortDataSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL |

WindowReportMonthly

| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |

WindowEnergyReportMonthly

| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |

WindowZoneSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

WindowEnergyZoneSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL |

FanReportMonthly

| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |

ZoneTemperatureOscillationReportMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

MechanicalVentilationLoadsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
RunPeriod RUNPERIOD 1
Weather File Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Latitude [deg] 10.82
Longitude [deg] 106.67
Elevation [m] 5.00
Time Zone 7.00
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Above Ground Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Window Opening Area [m2] 83.95 0.00 0.00 83.95 0.00
Gross Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00
Above Ground Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Above Ground Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Window Opening Area [m2] 83.95 0.00 0.00 83.95 0.00
Gross Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00
Above Ground Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 2293.99
Skylight Area [m2] 23.78
Skylight-Roof Ratio [%] 1.04


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BACK_SPACE 379.89 Yes Yes 2317.33 1.00 416.17 0.00 0.00 0.00 4.6739 46.45 8.0700
CORE_RETAIL 1600.48 Yes Yes 9762.95 1.00 356.86 0.00 0.00 0.00 11.3021 6.19 3.2300
POINT_OF_SALE 150.81 Yes Yes 919.94 1.00 189.80 0.00 38.06 38.06 11.3021 6.19 21.5200
FRONT_RETAIL 150.81 Yes Yes 919.94 1.00 189.80 0.00 38.06 38.06 11.3021 6.19 3.2300
FRONT_ENTRY 12.00 Yes Yes 73.20 1.00 24.38 0.00 7.83 7.83 7.5347 6.19 0.0000
Total 2293.99     13993.36   1177.02 0.00 83.95 83.95 10.1847 7.23 5.2170
Conditioned Total 2293.99     13993.36   1177.02 0.00 83.95 83.95 10.1847 7.23 5.2170
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BACK_SPACE 379.89 Yes Yes 1.00 BACK_SPACE GENERAL BACK_SPACE 4.6739 46.45 8.0700  
CORE_RETAIL 1600.48 Yes Yes 1.00 CORE_RETAIL GENERAL CORE_RETAIL 11.3021 6.19 3.2300  
POINT_OF_SALE 150.81 Yes Yes 1.00 POINT_OF_SALE GENERAL POINT_OF_SALE 11.3021 6.19 21.5200  
FRONT_RETAIL 150.81 Yes Yes 1.00 FRONT_RETAIL GENERAL FRONT_RETAIL 11.3021 6.19 3.2300  
FRONT_ENTRY 12.00 Yes Yes 1.00 FRONT_ENTRY GENERAL FRONT_ENTRY 7.5347 6.19 0.0000  
Total 2293.99             10.1847 3.62 5.2170  
Conditioned Total 2293.99             10.1847 3.62 5.2170  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 2293.99 2293.99 0.00 0.00 10.1847 7.23 5.2170
Total 2293.99 2293.99 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 13-JUN-14:00 - - - - - - - - - - - 02-JAN-12:09
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 67283.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 15298.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 10740.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 13473.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1025.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 107820.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 67283.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 15298.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 10740.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 13473.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 1025.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2427.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 655.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 138.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 615.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 508.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 55.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 4401.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1058.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 285.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 268.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 221.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 24.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1918.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1058.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 285.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 268.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 221.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 24.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1918.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BACK_SPACE DIRECT AIR 1.83
CORE_RETAIL DIRECT AIR 7.29
POINT_OF_SALE DIRECT AIR 1.13
FRONT_RETAIL DIRECT AIR 0.957784
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:UnitHeater

Design Size Maximum Supply Air Flow Rate [m3/s]
FRONT_ENTRY UNIT HEATER 0.014173
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
FRONT_ENTRY UNIT HEATER FAN 0.014173
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
FRONT_ENTRY UNIT HEATER HEATING COIL 417.48
PSZ-AC:1_SUPPHEATCOIL 38461.19
PSZ-AC:2_SUPPHEATCOIL 187506.00
PSZ-AC:3_SUPPHEATCOIL 25247.89
PSZ-AC:4_SUPPHEATCOIL 22260.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 1.83 1.83 1.83 1.83 1.90 1.90 1.00 0.961336 1.90
PSZ-AC:2 7.29 7.29 7.29 7.29 7.55 7.55 1.00 0.965860 7.55
PSZ-AC:3 1.13 1.13 1.13 1.13 1.14 1.14 1.00 0.987435 1.14
PSZ-AC:4 0.957784 0.957784 0.957784 0.957784 0.957784 0.957784 1.00 1.000000 0.957784
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 1.90 0.231581
PSZ-AC:2_OA_CONTROLLER 7.55 1.89
PSZ-AC:3_OA_CONTROLLER 1.14 0.178122
PSZ-AC:4_OA_CONTROLLER 0.957784 0.178122
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN 1.90 2035.58
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN 7.55 12721.06
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN 1.14 1265.47
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN 0.957784 1060.42
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] User-Specified Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 1.90 1.90 1.90 1.26 39067.33 25769.00 40.00 38461.19 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 7.55 7.55 7.55 4.98 187506.00 125629.02 40.00 187506.00 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 1.14 1.14 1.14 0.754374 25566.69 16916.08 40.00 25247.89 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.957784 0.957784 0.957784 0.632137 22523.73 14914.59 40.00 22260.59 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 1.90 0.951164 1.27 39067.33 19533.67 0.766350 0.766350
PSZ-AC:2 HP COOLING COIL 7.55 3.78 5.03 187506.00 93753.00 0.701080 0.701080
PSZ-AC:3 HP COOLING COIL 1.14 0.571495 0.761993 25566.69 12783.34 0.735080 0.735080
PSZ-AC:4 HP COOLING COIL 0.957780 0.478892 0.638520 22523.73 11261.86 0.718800 0.718800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:MultiSpeed

Design Size Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] Design Size Speed 2 Gross Rated Heating Capacity [W] Design Size Speed 1 Gross Rated Heating Capacity [W] Design Size Resistive Defrost Heater Capacity
PSZ-AC:1 HEATING COIL 1.90 0.951164 38461.19 19230.60 0.000000
PSZ-AC:2 HEATING COIL 7.55 3.78 187506.00 93753.00 0.000000
PSZ-AC:3 HEATING COIL 1.14 0.571495 25247.89 12623.94 0.000000
PSZ-AC:4 HEATING COIL 0.957784 0.478892 22260.59 11130.29 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
BACK_SPACE_WALL_EAST BACK_SPACE_WALL_EAST_ROLLDOOR |
BACK_SPACE_WALL_NORTH BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 |
BACK_SPACE_WALL_WEST BACK_SPACE_WALL_WEST_ROLLDOOR |
CORE_RETAIL_WALL_WEST_2 CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 |
CORE_RETAIL_WALL_EAST_2 CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 |
CORE_RETAIL_ROOF SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 |
POINT_OF_SALE_WALL_SOUTH POINT_OF_SALE_WALL_SOUTH_GLAZING |
FRONT_RETAIL_WALL_SOUTH FRONT_RETAIL_WALL_SOUTH_GLAZING |
FRONT_ENTRY_WALL_SOUTH FRONT_ENTRY_WALL_SOUTH_GLAZING |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 26.90 26.70 26.00 26.40 27.50 28.30 29.20 29.00 28.90 27.20 27.50 27.60


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 10.82 106.67 7.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 27.60 3.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 RetailStandalone 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 5 73 32


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BACK_SPACE 0.0 0.00 35.27 0.00 27.14 38.77 3.05 1 1 1 0.00 54.27 35.27 42.27 0.00 6.10 6.10 2317.33 TARP TARP 379.89 416.17 375.11 0.00 6 7 0 Yes
2 CORE_RETAIL 0.0 0.00 6.00 0.00 27.14 14.41 3.05 1 1 1 0.00 54.27 3.00 35.27 0.00 6.10 6.10 9762.95 TARP TARP 1600.48 356.86 345.15 23.78 10 22 0 Yes
3 POINT_OF_SALE 0.0 0.00 0.00 0.00 12.57 3.00 3.05 1 1 1 0.00 25.14 0.00 6.00 0.00 6.10 6.10 919.94 TARP TARP 150.81 189.80 151.74 38.06 7 1 0 Yes
4 FRONT_RETAIL 0.0 29.14 0.00 0.00 41.70 3.00 3.05 1 1 1 29.14 54.27 0.00 6.00 0.00 6.10 6.10 919.94 TARP TARP 150.81 189.80 151.74 38.06 7 1 0 Yes
5 FRONT_ENTRY 0.0 25.14 0.00 0.00 27.14 1.50 3.05 1 1 1 25.14 29.14 0.00 3.00 0.00 6.10 6.10 73.20 TARP TARP 12.00 24.38 16.55 7.83 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BACK_SPACE 379.89 8.2 46.452 2.153E-002 4.674 8.070 0.000 0.000 0.000 0.000 12.744 No
2 CORE_RETAIL 1600.48 258.4 6.193 0.161 11.302 3.230 0.000 0.000 0.000 0.000 14.532 No
3 POINT_OF_SALE 150.81 24.4 6.193 0.161 11.302 21.520 0.000 0.000 0.000 0.000 32.822 No
4 FRONT_RETAIL 150.81 24.4 6.193 0.161 11.302 3.230 0.000 0.000 0.000 0.000 14.532 No
5 FRONT_ENTRY 12.00 1.9 6.192 0.162 7.535 0.000 0.000 0.000 0.000 0.000 7.535 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BACK_SPACE BLDG_OCC_SCH BACK_SPACE 379.89 8.2 8.2 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_RETAIL BLDG_OCC_SCH CORE_RETAIL 1600.48 258.4 258.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 258 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 POINT_OF_SALE BLDG_OCC_SCH POINT_OF_SALE 150.81 24.4 24.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 24 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 FRONT_RETAIL BLDG_OCC_SCH FRONT_RETAIL 150.81 24.4 24.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 24 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 FRONT_ENTRY BLDG_OCC_SCH FRONT_ENTRY 12.00 1.9 1.9 0.162 6.192 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BACK_SPACE_LIGHTS LTG_SCH_BACK BACK_SPACE 379.89 8.2 1775.579 4.674 217.113 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1775.579
2 CORE_RETAIL_LIGHTS LTG_SCH_CORE CORE_RETAIL 1600.48 258.4 18088.802 11.302 69.994 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18088.802
3 POINT_OF_SALE_LIGHTS LTG_SCH_SALE POINT_OF_SALE 150.81 24.4 1704.468 11.302 69.994 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1704.468
4 FRONT_RETAIL_LIGHTS LTG_SCH_FRONT FRONT_RETAIL 150.81 24.4 1704.468 11.302 69.994 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1704.468
5 FRONT_ENTRY_LIGHTS LTG_SCH_ENTRY FRONT_ENTRY 12.00 1.9 90.417 7.535 46.655 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 90.417


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BACK_SPACE_MISCPLUG_EQUIP BLDG_EQUIP_SCH BACK_SPACE 379.89 8.2 3065.712 8.070 374.868 0.000 0.500 0.000 0.500 MiscPlug 0.000 3065.712
2 CORE_RETAIL_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_RETAIL 1600.48 258.4 5169.560 3.230 20.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 5169.560
3 POINT_OF_SALE_MISCPLUG_EQUIP BLDG_EQUIP_SCH POINT_OF_SALE 150.81 24.4 3245.431 21.520 133.273 0.000 0.500 0.000 0.500 MiscPlug 0.000 3245.431
4 FRONT_RETAIL_MISCPLUG_EQUIP BLDG_EQUIP_SCH FRONT_RETAIL 150.81 24.4 487.116 3.230 20.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 487.116


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 2.390 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 NONRES_EXT_WALL_GRD 21 3 9 0.167 5.069 0.900 0.900 0.700 0.700 MediumRough
7 BACK_SPACE_FLOOR_FFACTOR 38 2 7 0.167 0.2354 0.000 0.900 0.000 0.700 MediumRough
8 CORE_RETAIL_FLOOR_FFACTOR 39 2 7 0.167 0.4655E-01 0.000 0.900 0.000 0.700 MediumRough
9 POINT_OF_SALE_FLOOR_FFACTOR 40 2 7 0.167 0.2719 0.000 0.900 0.000 0.700 MediumRough
10 FRONT_RETAIL_FLOOR_FFACTOR 41 2 7 0.167 0.2719 0.000 0.900 0.000 0.700 MediumRough
11 FRONT_ENTRY_FLOOR_FFACTOR 42 2 7 0.167 0.4506 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.4184
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
10 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.2994E-01
11 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
12 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 4.172
13 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
14 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 21.40
15 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
16 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.601
17 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
18 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 3.601
19 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
20 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.142
21 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 2.3900722 2.3900722 2.3900722  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 9 -0.34109306E-14 0.24909287E-15 -0.70234472E-12 0.65513238E-16
25 8 0.13119258E-09 0.66225198E-13 0.25869970E-04 -0.14916918E-11
26 7 -0.11009939E-02 0.13568249E-07 -0.65256785E-02 0.12518681E-04
27 6 0.10140049 0.81303169E-05 0.18905580 -0.11654411E-02
28 5 -2.2086417 0.46066432E-03 -2.1793248 0.26223950E-01
29 4 19.715055 0.51780401E-02 12.415669 -0.24584718
30 3 -82.671456 0.14472115E-01 -37.782151 1.1032137
31 2 168.49726 0.99923307E-02 62.094262 -2.4465849
32 1 -160.45852 0.12849016E-02 -51.628788 2.5579517
33 0 57.057407 0.91053392E-05 16.929182  
34 7 -0.17867606E-08 -0.41848128E-15 0.59564440E-14 -0.80268503E-16
35 6 0.65885627E-05 0.45121803E-08 0.31870471E-02 -0.26735622E-04
36 5 -0.47407468E-03 0.26731137E-05 -0.22356413 0.19547341E-02
37 4 0.10906669E-01 0.12168607E-03 4.8268734 -0.45239294E-01
38 3 -0.95781928E-01 0.96775432E-03 -38.006321 0.39848689
39 2 0.34010998 0.16100142E-02 116.45457 -1.4175463
40 1 -0.49090295 0.49061009E-03 -143.89001 2.0487556
41 0 0.23934032 0.11861159E-04 60.838472  
42 7 -0.92098544E-08 0.58605081E-15 -0.29904982E-14 0.25019681E-16
43 6 0.19387148E-05 0.91388609E-09 0.32017682E-02 -0.26859115E-04
44 5 -0.10799279E-03 0.53275402E-06 -0.22440051 0.19621166E-02
45 4 0.22736042E-02 0.24052495E-04 4.8407977 -0.45373149E-01
46 3 -0.19287081E-01 0.18995237E-03 -38.084949 0.39935605
47 2 0.67516478E-01 0.31394945E-03 116.60756 -1.4195928
48 1 -0.96817688E-01 0.94848058E-04 -143.98006 2.0502357
49 0 0.47046370E-01 0.22824214E-05 60.838472  
50 7 -0.15410587E-08 -0.27131508E-15 0.13739895E-13 -0.20869099E-15
51 6 0.75948721E-05 0.52202150E-08 0.31841660E-02 -0.26711453E-04
52 5 -0.54825752E-03 0.30939483E-05 -0.22340036 0.19532886E-02
53 4 0.12624073E-01 0.14086823E-03 4.8241453 -0.45213070E-01
54 3 -0.11089483 0.11205317E-02 -37.990908 0.39831653
55 2 0.39381345 0.18644394E-02 116.42457 -1.4171450
56 1 -0.56844024 0.56830838E-03 -143.87235 2.0484654
57 0 0.27714917 0.13715070E-04 60.838472  
58 7 -0.15410587E-08 -0.27131508E-15 0.13739895E-13 -0.20869099E-15
59 6 0.75948721E-05 0.52202150E-08 0.31841660E-02 -0.26711453E-04
60 5 -0.54825752E-03 0.30939483E-05 -0.22340036 0.19532886E-02
61 4 0.12624073E-01 0.14086823E-03 4.8241453 -0.45213070E-01
62 3 -0.11089483 0.11205317E-02 -37.990908 0.39831653
63 2 0.39381345 0.18644394E-02 116.42457 -1.4171450
64 1 -0.56844024 0.56830838E-03 -143.87235 2.0484654
65 0 0.27714917 0.13715070E-04 60.838472  
66 7 -0.91256693E-09 -0.65654920E-16 0.14763662E-14 0.25811017E-17
67 6 0.12659591E-04 0.87293215E-08 0.31698558E-02 -0.26591407E-04
68 5 -0.91895148E-03 0.51830142E-05 -0.22258679 0.19461077E-02
69 4 0.21183618E-01 0.23613386E-03 4.8105909 -0.45082779E-01
70 3 -0.18612912 0.18798277E-02 -37.914317 0.39746999
71 2 0.66101200 0.31293459E-02 116.27548 -1.4151508
72 1 -0.95411819 0.95507326E-03 -143.78458 2.0470226
73 0 0.46518638 0.22828278E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.503_SHGC_0.22 36 1 VerySmooth 2.860 2.860 1.000 0.221    
2 NONRESSKYLIGHT_U_0.7_SHGC_0.3 37 1 VerySmooth 3.979 3.979 1.000 0.303    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SpectralAverage   1.93472E-002 0.13126 0.64057 0.64057 0.24200 0.16318 0.24318 0.00000 0.84000 0.84000 0.10783 1.00000 No
2 NONRES SKYLIGHT GLAZING LAYER SpectralAverage   2.00000E-003 0.17728 0.47032 0.47032 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 2.40661E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CORE_RETAIL 16 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CORE_RETAIL 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 1.001 0.9283


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BACK_SPACE_WALL_EAST 0 257.68 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
2 BACK_SPACE_WALL_EAST_ROLLDOOR 0 257.68 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
3 BACK_SPACE_WALL_NORTH 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
4 BACK_SPACE_WALL_NORTH_DOOR1 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
5 BACK_SPACE_WALL_NORTH_DOOR2 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
6 BACK_SPACE_WALL_NORTH_ROLLDOOR1 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
7 BACK_SPACE_WALL_NORTH_ROLLDOOR2 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
8 BACK_SPACE_WALL_NORTH_ROLLDOOR3 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
9 BACK_SPACE_WALL_WEST 0 257.68 96.73 6.10 0 6.10 68.27 12.40 0.00 0 No No
10 BACK_SPACE_WALL_WEST_ROLLDOOR 0 257.68 96.73 6.10 0 6.10 68.27 12.40 0.00 0 No No
11 BACK_SPACE_WALL_SOUTH 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
12 BACK_SPACE_FLOOR 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
13 BACK_SPACE_ROOF 0 2293.99 205.08 0.00 0 6.10 68.27 12.40 0.00 0 No No
14 BACK_SPACE_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
15 CORE_RETAIL_WALL_SOUTH_3 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
16 CORE_RETAIL_WALL_SOUTH_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
17 CORE_RETAIL_WALL_EAST_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
18 CORE_RETAIL_WALL_SOUTH_2 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
19 CORE_RETAIL_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
20 CORE_RETAIL_WALL_WEST_2 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 4 No No
21 CORE_RETAIL_WALL_WEST_2_DOOR3 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
22 CORE_RETAIL_WALL_WEST_2_DOOR2 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
23 CORE_RETAIL_WALL_WEST_2_DOOR1 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
24 CORE_RETAIL_WALL_EAST_2 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 4 No No
25 CORE_RETAIL_WALL_EAST_2_DOOR1 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
26 CORE_RETAIL_WALL_EAST_2_DOOR2 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
27 CORE_RETAIL_WALL_EAST_2_DOOR3 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
28 CORE_RETAIL_WALL_WEST_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
29 CORE_RETAIL_FLOOR 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
30 CORE_RETAIL_ROOF 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
31 SKYLIGHTS_R4C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
32 SKYLIGHTS_R4C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
33 SKYLIGHTS_R4C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
34 SKYLIGHTS_R4C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
35 SKYLIGHTS_R1C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
36 SKYLIGHTS_R1C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
37 SKYLIGHTS_R1C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
38 SKYLIGHTS_R1C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
39 SKYLIGHTS_R2C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
40 SKYLIGHTS_R2C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
41 SKYLIGHTS_R2C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
42 SKYLIGHTS_R2C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
43 SKYLIGHTS_R3C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
44 SKYLIGHTS_R3C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
45 SKYLIGHTS_R3C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
46 SKYLIGHTS_R3C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
47 CORE_RETAIL_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
48 POINT_OF_SALE_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 4 No No
49 POINT_OF_SALE_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 1 No No
50 POINT_OF_SALE_WALL_EAST_2 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
51 POINT_OF_SALE_WALL_WEST 0 257.68 96.73 6.10 0 6.10 31.14 9.69 0.20 4 No No
52 POINT_OF_SALE_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
53 POINT_OF_SALE_WALL_EAST_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
54 POINT_OF_SALE_FLOOR 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
55 POINT_OF_SALE_ROOF 0 2293.99 205.08 0.00 0 6.10 31.14 9.69 0.20 0 No No
56 POINT_OF_SALE_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
57 FRONT_RETAIL_WALLL_EAST 0 257.68 149.77 6.10 0 6.10 31.14 9.69 0.20 4 No No
58 FRONT_RETAIL_WALL_WEST_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
59 FRONT_RETAIL_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
60 FRONT_RETAIL_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 4 No No
61 FRONT_RETAIL_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 1 No No
62 FRONT_RETAIL_WALL_WEST_2 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
63 FRONT_RETAIL_FLOOR 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
64 FRONT_RETAIL_ROOF 0 2293.99 205.08 0.00 0 6.10 31.14 9.69 0.20 0 No No
65 FRONT_RETAIL_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
66 FRONT_ENTRY_WALL_EAST 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
67 FRONT_ENTRY_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
68 FRONT_ENTRY_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 4.00 3.43 0.32 4 No No
69 FRONT_ENTRY_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 4.00 3.43 0.32 1 No No
70 FRONT_ENTRY_WALL_WEST 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
71 FRONT_ENTRY_FLOOR 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
72 FRONT_ENTRY_ROOF 0 2293.99 205.08 0.00 0 6.10 4.00 3.43 0.32 0 No No
73 FRONT_ENTRY_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No


FenestrationAssembly

Construction Name Frame and Divider Name NFRC Product Type Assembly U-Factor {W/m2-K} Assembly SHGC Assembly Visible Transmittance
1 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES CurtainWall 3.838 0.300 0.402


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 BACK_SPACE_INFILTRATION INFIL_SCH_PNNL BACK_SPACE 379.89 8.2 0.107 2.808E-004 1.274E-004 0.166 0.000 0.000 0.224 0.000
2 CORE_RETAIL_INFILTRATION INFIL_SCH_PNNL CORE_RETAIL 1600.48 258.4 9.147E-002 5.715E-005 4.645E-005 3.373E-002 0.000 0.000 0.224 0.000
3 POINT_OF_SALE_INFILTRATION INFIL_SCH_PNNL POINT_OF_SALE 150.81 24.4 4.865E-002 3.226E-004 1.428E-004 0.190 0.000 0.000 0.224 0.000
4 FRONT_RETAIL_INFILTRATION INFIL_SCH_PNNL FRONT_RETAIL 150.81 24.4 4.865E-002 3.226E-004 1.428E-004 0.190 0.000 0.000 0.224 0.000
5 FRONT_ENTRY_INFILTRATION INFIL_SCH_PNNL FRONT_ENTRY 12.00 1.9 6.250E-003 5.208E-004 1.718E-004 0.307 0.000 0.000 0.224 0.000
6 FRONT_ENTRY_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH FRONT_ENTRY 12.00 1.9 1.419 0.118 3.899E-002 69.771 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BACK_SPACE Mixing/Well-Stirred
2 CORE_RETAIL Mixing/Well-Stirred
3 POINT_OF_SALE Mixing/Well-Stirred
4 FRONT_RETAIL Mixing/Well-Stirred
5 FRONT_ENTRY Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone BACK_SPACE 1.2000
3 Zone CORE_RETAIL 1.2000
4 Zone POINT_OF_SALE 1.2000
5 Zone FRONT_RETAIL 1.2000
6 Zone FRONT_ENTRY 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone BACK_SPACE 1.2000
3 Zone CORE_RETAIL 1.2000
4 Zone POINT_OF_SALE 1.2000
5 Zone FRONT_RETAIL 1.2000
6 Zone FRONT_ENTRY 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 1.0946E-004
2 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 1.7975E-004
3 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 1.0202E-004
4 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 1.5702E-004
5 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 9.9035E-005
6 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 1.4859E-004
7 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 1.2140E-004
8 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 2.5134E-004
9 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 1.6272E-004
10 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 1.3464E-004
11 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 1.4383E-004
12 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 1.2154E-004
13 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 1.3725E-004
14 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 1.1536E-004
15 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 2.1606E-004
16 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 1.6361E-004
17 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 1.7170E-004
18 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 9.2899E-005
19 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 1.5065E-004
20 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 8.8789E-005
21 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 1.4232E-004
22 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 8.6491E-005
23 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 2.3470E-004
24 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 9.8097E-005
25 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.1804E-004
26 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 7.7145E-005
27 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.0852E-004
28 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 7.6410E-005
29 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.0365E-004
30 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 7.6377E-005
31 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.3538E-004
32 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 7.9371E-005
33 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 1.6954E-004
34 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 6.3267E-004
35 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 1.6745E-004
36 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 6.8203E-004
37 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 1.6428E-004
38 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 5.7382E-004
39 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 1.3163E-004
40 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 3.1688E-004
41 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 4.7804E-004
42 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 2.6279E-004
43 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 5.0500E-004
44 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 2.6295E-004
45 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 4.4312E-004
46 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 2.5753E-004
47 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 2.6373E-004
48 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 1.8840E-004
49 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 1.9081E-004
50 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 8.1181E-005
51 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 1.8754E-004
52 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 8.0664E-005
53 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 1.8755E-004
54 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 8.1421E-005
55 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 1.4999E-004
56 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 8.0054E-005
57 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 5.3126E-004
58 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 1.1389E-004
59 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 5.6309E-004
60 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 1.1108E-004
61 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 4.9550E-004
62 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 1.1189E-004
63 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 2.9158E-004
64 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 1.0222E-004
65 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 2.3842E-003
66 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 6.4929E-004
67 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 2.5469E-003
68 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 6.2130E-004
69 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 2.7347E-003
70 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 7.5763E-004
71 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 1.9958E-003
72 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 7.3619E-004
73 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 2.7679E-004
74 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 7.5268E-003
75 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 2.6042E-004
76 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 8.7750E-003
77 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 2.9506E-004
78 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 7.4016E-003
79 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 2.8004E-004
80 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 3.7367E-003
81 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 3.5230E-003
82 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 1.4473E-004
83 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 3.8538E-003
84 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 1.3585E-004
85 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 3.9890E-003
86 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 1.4436E-004
87 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 2.7826E-003
88 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 1.4729E-004
89 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 3.5505E-004
90 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 8.5305E-005
91 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 3.3123E-004
92 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 8.3742E-005
93 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 3.9143E-004
94 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 8.4657E-005
95 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 3.9533E-004
96 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 8.5415E-005
97 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 7.4922E-004
98 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 3.7381E-004
99 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 6.5147E-004
100 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 3.2453E-004
101 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 8.3575E-004
102 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 3.8337E-004
103 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 1.6019E-003
104 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 6.4168E-004
105 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 2.0150E-004
106 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 1.1159E-003
107 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 1.8065E-004
108 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 9.7012E-004
109 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 1.9856E-004
110 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 1.2512E-003
111 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 2.6013E-004
112 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 2.7993E-003
113 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 9.1092E-004
114 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 1.2664E-004
115 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 7.8850E-004
116 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 1.1721E-004
117 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 1.0099E-003
118 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 1.1965E-004
119 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 2.1576E-003
120 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 1.4225E-004
121 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 2.4708E-004
122 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 8.3003E-005
123 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 2.1756E-004
124 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 8.1364E-005
125 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 2.4257E-004
126 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 8.1579E-005
127 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 3.5932E-004
128 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 8.4939E-005


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BACK_SPACE Cooling 21608.67626 25930.41152 1.52398 1.82878 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:00:00 28.91000 1.71462E-002 379.89000 8.17812 0.23158 0.00000
2 BACK_SPACE Heating 5974.52422 7169.42906 0.25088 0.30106 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 379.89000 8.17812 0.23158 0.00000
3 CORE_RETAIL Cooling 86304.41348 103565.29617 6.07757 7.29308 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:00:00 28.91000 1.71462E-002 1600.48290 258.43418 1.89033 0.00000
4 CORE_RETAIL Heating 18078.47126 21694.16552 0.75770 1.89033 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 1600.48290 258.43418 1.89033 0.00000
5 POINT_OF_SALE Cooling 13162.36477 15794.83772 0.94052 1.12863 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:00:00 28.91000 1.71462E-002 150.81000 24.35169 0.17812 0.00000
6 POINT_OF_SALE Heating 2727.48639 3272.98367 0.11450 0.17812 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 150.81000 24.35169 0.17812 0.00000
7 FRONT_RETAIL Cooling 10871.29052 13045.54862 0.79815 0.95778 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:40:00 35.20000 1.71581E-002 150.81000 24.35169 0.17812 0.00000
8 FRONT_RETAIL Heating 2727.48639 3272.98367 0.11450 0.17812 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 150.81000 24.35169 0.17812 0.00000
9 FRONT_ENTRY Cooling 0.00000 0.00000 0.00000 1.41732E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 35.11500 1.71580E-002 12.00000 1.93800 1.41732E-002 0.00000
10 FRONT_ENTRY Heating 0.00000 0.00000 0.00000 1.41732E-002   00:10:00 20.10000 1.47983E-002 12.00000 1.93800 1.41732E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 28533.19 1.90233 1.90233 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 05:00:00
2 PSZ-AC:1 Heating Sensible 7177.90 0.30106 0.30106 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00
3 PSZ-AC:2 Cooling Sensible 123623.17 7.55087 7.55087 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 05:00:00
4 PSZ-AC:2 Heating Sensible 45496.26 1.89033 1.89033 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00
5 PSZ-AC:3 Cooling Sensible 17692.31 1.14299 1.14299 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 05:00:00
6 PSZ-AC:3 Heating Sensible 4287.01 0.17812 0.17812 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 15:20:00
7 PSZ-AC:4 Cooling Sensible 15280.81 0.95778 0.95778 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 05:00:00
8 PSZ-AC:4 Heating Sensible 4287.01 0.17812 0.17812 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 14:30:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BACK_SPACE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.82878
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_RETAIL DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 7.29308
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat POINT_OF_SALE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.12863
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat FRONT_RETAIL DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.95778
5 ZoneHVAC:UnitHeater FRONT_ENTRY UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 1.41732E-002
6 Fan:ConstantVolume FRONT_ENTRY UNIT HEATER FAN Design Size Maximum Flow Rate [m3/s] 1.41732E-002
7 Coil:Heating:Electric FRONT_ENTRY UNIT HEATER HEATING COIL Design Size Nominal Capacity [W] 417.48081
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.82878
9 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.82878
10 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.82878
11 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 1.82878
12 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 1.90233
13 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 1.90233
14 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
15 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 0.96134
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 7.29308
17 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 7.29308
18 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 7.29308
19 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 7.29308
20 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 7.55087
21 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 7.55087
22 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
23 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 0.96586
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.12863
25 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.12863
26 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.12863
27 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 1.12863
28 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 1.14299
29 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 1.14299
30 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
31 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 0.98743
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.95778
33 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.95778
34 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.95778
35 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.95778
36 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.95778
37 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.95778
38 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
39 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
40 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 1.90233
41 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 7.55087
42 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 1.14299
43 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.95778
44 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.90233
45 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.23158
46 Fan:SystemModel PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.90233
47 Fan:SystemModel PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 2035.58130
48 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.90233
49 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.90233
50 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.90233
51 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.25554
52 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.90233
53 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.95116
54 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.26822
55 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 39067.33000
56 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 19533.66500
57 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.76635
58 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.76635
59 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 39067.33000
60 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 25768.99897
61 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
62 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 38461.19250
63 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
64 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 1.90233
65 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.95116
66 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 38461.19250
67 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 19230.59625
68 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
69 Coil:Heating:Electric PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 38461.19250
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 7.55087
71 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.89033
72 Fan:SystemModel PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 7.55087
73 Fan:SystemModel PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 12721.05530
74 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 7.55087
75 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 7.55087
76 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 7.55087
77 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 4.98357
78 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 7.55087
79 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 3.77543
80 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 5.03391
81 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 187506.00000
82 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 93753.00000
83 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.70108
84 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.70108
85 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 187506.00000
86 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 125629.01766
87 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
88 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 187505.99651
89 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
90 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 7.55087
91 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 3.77543
92 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 187505.99651
93 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 93752.99826
94 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
95 Coil:Heating:Electric PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 187505.99651
96 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.14299
97 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.17812
98 Fan:SystemModel PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.14299
99 Fan:SystemModel PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1265.47237
100 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.14299
101 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.14299
102 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.14299
103 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.75437
104 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.14299
105 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.57150
106 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.76199
107 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 25566.69000
108 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 12783.34500
109 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.73508
110 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.73508
111 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 25566.69000
112 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 16916.08401
113 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
114 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 25247.88658
115 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
116 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 1.14299
117 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.57150
118 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 25247.88658
119 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 12623.94329
120 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
121 Coil:Heating:Electric PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 25247.88658
122 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.95778
123 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.17812
124 Fan:SystemModel PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.95778
125 Fan:SystemModel PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1060.41862
126 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.95778
127 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.95778
128 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.95778
129 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.63214
130 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.95778
131 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.47889
132 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.63852
133 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 22523.73000
134 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 11261.86500
135 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.71880
136 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.71880
137 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 22523.73000
138 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 14914.59441
139 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
140 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 22260.58867
141 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
142 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 0.95778
143 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.47889
144 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 22260.58867
145 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 11130.29433
146 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
147 Coil:Heating:Electric PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 22260.58867


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL 37571.7     11.42 11.42  
2 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL 181549.0     10.63 10.63  
3 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL 24666.7     11.59 11.59  
4 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL 21768.9     11.68 11.68  


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL 39978.9 22121.6 8.04 2
2 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL 193572.4 106514.4 7.34 2
3 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL 26162.4 14439.9 8.12 2
4 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL 23028.2 12692.8 8.11 2


Zone Surfaces

Zone Name # Surfaces
1 BACK_SPACE 14
2 CORE_RETAIL 33
3 POINT_OF_SALE 9
4 FRONT_RETAIL 9
5 FRONT_ENTRY 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BACK_SPACE_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   35.24 42.67 35.24 90.00 90.00 7.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
2 BACK_SPACE_WALL_EAST_ROLLDOOR Door BACK_SPACE_WALL_EAST CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 90.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
3 BACK_SPACE_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   304.63 330.83 304.63 0.00 90.00 54.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
4 BACK_SPACE_WALL_NORTH_DOOR1 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 BACK_SPACE_WALL_NORTH_DOOR2 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
6 BACK_SPACE_WALL_NORTH_ROLLDOOR1 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
7 BACK_SPACE_WALL_NORTH_ROLLDOOR2 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
8 BACK_SPACE_WALL_NORTH_ROLLDOOR3 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 BACK_SPACE_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   35.24 42.67 35.24 270.00 90.00 7.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 BACK_SPACE_WALL_WEST_ROLLDOOR Door BACK_SPACE_WALL_WEST CTF - ConductionTransferFunction OVERHEAD DOOR_CON 2.390 2.390   7.43 7.43 7.43 270.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 BACK_SPACE_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   330.83 330.83 330.83 180.00 90.00 54.27 6.10 0.00 CORE_RETAIL_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
12 BACK_SPACE_FLOOR Floor   CTF - ConductionTransferFunction BACK_SPACE_FLOOR_FFACTOR 0.235 0.223   379.89 379.89 379.89 90.00 180.00 7.00 54.27 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 BACK_SPACE_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   379.89 379.89 379.89 90.00 0.00 7.00 54.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
14 BACK_SPACE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   759.78 759.78 759.78 0.00 90.00 759.78 1.00 0.00 BACK_SPACE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 CORE_RETAIL_WALL_SOUTH_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 180.00 90.00 25.14 6.10 0.00 FRONT_RETAIL_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
16 CORE_RETAIL_WALL_SOUTH_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 180.00 90.00 25.14 6.10 0.00 POINT_OF_SALE_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
17 CORE_RETAIL_WALL_EAST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_RETAIL_WALL_WEST_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
18 CORE_RETAIL_WALL_SOUTH_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.38 24.38 24.38 180.00 90.00 4.00 6.10 0.00 FRONT_ENTRY_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 CORE_RETAIL_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   330.83 330.83 330.83 0.00 90.00 54.27 6.10 0.00 BACK_SPACE_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 CORE_RETAIL_WALL_WEST_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   172.58 178.43 172.58 270.00 90.00 29.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 CORE_RETAIL_WALL_WEST_2_DOOR3 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 CORE_RETAIL_WALL_WEST_2_DOOR2 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
23 CORE_RETAIL_WALL_WEST_2_DOOR1 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 CORE_RETAIL_WALL_EAST_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   172.58 178.43 172.58 90.00 90.00 29.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 CORE_RETAIL_WALL_EAST_2_DOOR1 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
26 CORE_RETAIL_WALL_EAST_2_DOOR2 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
27 CORE_RETAIL_WALL_EAST_2_DOOR3 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
28 CORE_RETAIL_WALL_WEST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 POINT_OF_SALE_WALL_EAST_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_RETAIL_FLOOR Floor   CTF - ConductionTransferFunction CORE_RETAIL_FLOOR_FFACTOR 4.655E-002 4.603E-002   1600.48 1600.48 1600.48 0.00 180.00 40.01 40.01 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
30 CORE_RETAIL_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   1576.70 1600.48 1576.70 180.00 0.00 40.01 40.01 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
31 SKYLIGHTS_R4C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 1.11E-016 1.00 4
32 SKYLIGHTS_R4C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
33 SKYLIGHTS_R4C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
34 SKYLIGHTS_R4C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
35 SKYLIGHTS_R1C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
36 SKYLIGHTS_R1C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
37 SKYLIGHTS_R1C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
38 SKYLIGHTS_R1C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
39 SKYLIGHTS_R2C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
40 SKYLIGHTS_R2C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
41 SKYLIGHTS_R2C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
42 SKYLIGHTS_R2C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
43 SKYLIGHTS_R3C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
44 SKYLIGHTS_R3C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 1.11E-016 1.00 4
45 SKYLIGHTS_R3C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
46 SKYLIGHTS_R3C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.7_SHGC_0.3 N/A 3.979 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
47 CORE_RETAIL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3200.97 3200.97 3200.97 0.00 90.00 3200.97 1.00 0.00 CORE_RETAIL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
48 POINT_OF_SALE_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   115.16 153.22 115.16 180.00 90.00 25.14 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 POINT_OF_SALE_WALL_SOUTH_GLAZING Window POINT_OF_SALE_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.503_SHGC_0.22 N/A 2.860 No 38.06 38.06 38.06 180.00 90.00 25.04 1.52 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
50 POINT_OF_SALE_WALL_EAST_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 CORE_RETAIL_WALL_WEST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 POINT_OF_SALE_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   36.58 36.58 36.58 270.00 90.00 6.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 POINT_OF_SALE_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 0.00 90.00 25.14 6.10 0.00 CORE_RETAIL_WALL_SOUTH_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
53 POINT_OF_SALE_WALL_EAST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_ENTRY_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 POINT_OF_SALE_FLOOR Floor   CTF - ConductionTransferFunction POINT_OF_SALE_FLOOR_FFACTOR 0.272 0.255   150.81 150.81 150.81 180.00 180.00 25.14 6.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
55 POINT_OF_SALE_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   150.81 150.81 150.81 180.00 0.00 25.14 6.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
56 POINT_OF_SALE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   301.62 301.62 301.62 0.00 90.00 301.62 1.00 0.00 POINT_OF_SALE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
57 FRONT_RETAIL_WALLL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   36.58 36.58 36.58 90.00 90.00 6.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 FRONT_RETAIL_WALL_WEST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 FRONT_ENTRY_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 FRONT_RETAIL_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 0.00 90.00 25.14 6.10 0.00 CORE_RETAIL_WALL_SOUTH_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 FRONT_RETAIL_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   115.16 153.22 115.16 180.00 90.00 25.14 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 FRONT_RETAIL_WALL_SOUTH_GLAZING Window FRONT_RETAIL_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.503_SHGC_0.22 N/A 2.860 No 38.06 38.06 38.06 180.00 90.00 25.04 1.52 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 FRONT_RETAIL_WALL_WEST_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 CORE_RETAIL_WALL_EAST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 FRONT_RETAIL_FLOOR Floor   CTF - ConductionTransferFunction FRONT_RETAIL_FLOOR_FFACTOR 0.272 0.255   150.81 150.81 150.81 90.00 180.00 6.00 25.14 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
64 FRONT_RETAIL_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   150.81 150.81 150.81 90.00 0.00 6.00 25.14 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
65 FRONT_RETAIL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   301.62 301.62 301.62 0.00 90.00 301.62 1.00 0.00 FRONT_RETAIL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
66 FRONT_ENTRY_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_RETAIL_WALL_WEST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
67 FRONT_ENTRY_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.38 24.38 24.38 0.00 90.00 4.00 6.10 0.00 CORE_RETAIL_WALL_SOUTH_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
68 FRONT_ENTRY_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 5.069 2.882   16.55 24.38 16.55 180.00 90.00 4.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 FRONT_ENTRY_WALL_SOUTH_GLAZING Window FRONT_ENTRY_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.503_SHGC_0.22 N/A 2.860 No 7.83 7.83 7.83 180.00 90.00 3.00 2.61 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 FRONT_ENTRY_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 POINT_OF_SALE_WALL_EAST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 FRONT_ENTRY_FLOOR Floor   CTF - ConductionTransferFunction FRONT_ENTRY_FLOOR_FFACTOR 0.451 0.406   12.00 12.00 12.00 180.00 180.00 4.00 3.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
72 FRONT_ENTRY_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   12.00 12.00 12.00 180.00 0.00 4.00 3.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
73 FRONT_ENTRY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   24.00 24.00 24.00 0.00 90.00 24.00 1.00 0.00 FRONT_ENTRY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BACK_SPACE RunPeriod: RUNPERIOD 1 0.1247128051 0.1924562966 Pass Pass 0.5748059053 1.7110008958 Pass Pass
2 CORE_RETAIL RunPeriod: RUNPERIOD 1 2.7453780490E-002 0.1264653242 Pass Pass 7.7897904579E-002 0.3694760256 Pass Pass
3 POINT_OF_SALE RunPeriod: RUNPERIOD 1 0.1682217816 0.2599824345 Pass Pass 0.3920736751 0.8254860791 Pass Pass
4 FRONT_RETAIL RunPeriod: RUNPERIOD 1 0.1440931710 0.2225781324 Pass Pass 0.4002666693 0.8529582980 Pass Pass
5 FRONT_ENTRY RunPeriod: RUNPERIOD 1 7.2207603747E-002 9.9629760144E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3484.65 -21.3 0.00 -1873.9 3747.31 5336.70



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 20.10 0.00 20.10 Wetbulb [C] 1.80 0.00
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 35.20 8.50 25.80 Wetbulb [C] 4.10 160.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 57.00 12      
Feb 0.00 0      
Mar 153.60 31      
Apr 87.00 59      
May 227.22 128      
Jun 144.58 109      
Jul 42.40 24      
Aug 164.90 163      
Sep 119.60 50      
Oct 365.70 188      
Nov 70.90 67      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BACK_SPACE_WALL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 42.67 35.24 90.00 90.00 E
BACK_SPACE_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 330.83 304.63 0.00 90.00 N
BACK_SPACE_WALL_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 42.67 35.24 270.00 90.00 W
BACK_SPACE_FLOOR BACK_SPACE_FLOOR_FFACTOR 1.00 0.227 0.235 379.89 379.89 90.00 180.00  
BACK_SPACE_ROOF NONRES_ROOF 0.55 0.221 0.228 379.89 379.89 90.00 0.00  
CORE_RETAIL_WALL_WEST_2 NONRES_EXT_WALL_GRD 0.30 2.882 5.069 178.43 172.58 270.00 90.00 W
CORE_RETAIL_WALL_EAST_2 NONRES_EXT_WALL_GRD 0.30 2.882 5.069 178.43 172.58 90.00 90.00 E
CORE_RETAIL_FLOOR CORE_RETAIL_FLOOR_FFACTOR 1.00 0.046 0.047 1600.48 1600.48 0.00 180.00  
CORE_RETAIL_ROOF NONRES_ROOF 0.55 0.221 0.228 1600.48 1576.70 180.00 0.00  
POINT_OF_SALE_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 153.22 115.16 180.00 90.00 S
POINT_OF_SALE_WALL_WEST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 36.58 36.58 270.00 90.00 W
POINT_OF_SALE_FLOOR POINT_OF_SALE_FLOOR_FFACTOR 1.00 0.260 0.272 150.81 150.81 180.00 180.00  
POINT_OF_SALE_ROOF NONRES_ROOF 0.55 0.221 0.228 150.81 150.81 180.00 0.00  
FRONT_RETAIL_WALLL_EAST NONRES_EXT_WALL_GRD 0.30 2.882 5.069 36.58 36.58 90.00 90.00 E
FRONT_RETAIL_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 153.22 115.16 180.00 90.00 S
FRONT_RETAIL_FLOOR FRONT_RETAIL_FLOOR_FFACTOR 1.00 0.260 0.272 150.81 150.81 90.00 180.00  
FRONT_RETAIL_ROOF NONRES_ROOF 0.55 0.221 0.228 150.81 150.81 90.00 0.00  
FRONT_ENTRY_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 2.882 5.069 24.38 16.55 180.00 90.00 S
FRONT_ENTRY_FLOOR FRONT_ENTRY_FLOOR_FFACTOR 1.00 0.420 0.451 12.00 12.00 180.00 180.00  
FRONT_ENTRY_ROOF NONRES_ROOF 0.55 0.221 0.228 12.00 12.00 180.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BACK_SPACE_WALL_SOUTH INT_WALL 0.30 2.511 6.299 330.83 330.83 180.00 90.00 S
CORE_RETAIL_WALL_SOUTH_3 INT_WALL 0.30 2.511 6.299 153.22 153.22 180.00 90.00 S
CORE_RETAIL_WALL_SOUTH_1 INT_WALL 0.30 2.511 6.299 153.22 153.22 180.00 90.00 S
CORE_RETAIL_WALL_EAST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
CORE_RETAIL_WALL_SOUTH_2 INT_WALL 0.30 2.511 6.299 24.38 24.38 180.00 90.00 S
CORE_RETAIL_WALL_NORTH INT_WALL 0.30 2.511 6.299 330.83 330.83 0.00 90.00 N
CORE_RETAIL_WALL_WEST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
POINT_OF_SALE_WALL_EAST_2 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
POINT_OF_SALE_WALL_NORTH INT_WALL 0.30 2.511 6.299 153.22 153.22 0.00 90.00 N
POINT_OF_SALE_WALL_EAST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
FRONT_RETAIL_WALL_WEST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
FRONT_RETAIL_WALL_NORTH INT_WALL 0.30 2.511 6.299 153.22 153.22 0.00 90.00 N
FRONT_RETAIL_WALL_WEST_2 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
FRONT_ENTRY_WALL_EAST INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
FRONT_ENTRY_WALL_NORTH INT_WALL 0.30 2.511 6.299 24.38 24.38 0.00 90.00 N
FRONT_ENTRY_WALL_WEST INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
BACK_SPACE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 759.78   0.00 90.00 N
CORE_RETAIL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3200.97   0.00 90.00 N
POINT_OF_SALE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 301.62   0.00 90.00 N
FRONT_RETAIL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 301.62   0.00 90.00 N
FRONT_ENTRY_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 24.00   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
SKYLIGHTS_R4C1 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C2 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C3 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C4 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C1 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C2 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C4 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C3 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C2 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C1 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C3 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C4 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C2 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C1 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C3 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C4 NONRESSKYLIGHT_U_0.7_SHGC_0.3 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.979 0.303 0.402 0.000 0.000 CurtainWall 3.838 0.300 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
POINT_OF_SALE_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.503_SHGC_0.22   38.06 0.00 0.00 38.06 38.06 2.860 0.221 0.243             No POINT_OF_SALE_WALL_SOUTH 180.00 90.00 S
FRONT_RETAIL_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.503_SHGC_0.22   38.06 0.00 0.00 38.06 38.06 2.860 0.221 0.243             No FRONT_RETAIL_WALL_SOUTH 180.00 90.00 S
FRONT_ENTRY_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.503_SHGC_0.22   7.83 0.00 0.00 7.83 7.83 2.860 0.221 0.243             No FRONT_ENTRY_WALL_SOUTH 180.00 90.00 S
Total or Average             107.73 3.107 0.239 0.278                      
North Total or Average             0.00 - - -                      
Non-North Total or Average             107.73 3.107 0.239 0.278                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
BACK_SPACE_WALL_EAST_ROLLDOOR OVERHEAD DOOR_CON 1.760 2.390 7.43 BACK_SPACE_WALL_EAST
BACK_SPACE_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR1 OVERHEAD DOOR_CON 1.760 2.390 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR2 OVERHEAD DOOR_CON 1.760 2.390 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR3 OVERHEAD DOOR_CON 1.760 2.390 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_WEST_ROLLDOOR OVERHEAD DOOR_CON 1.760 2.390 7.43 BACK_SPACE_WALL_WEST
CORE_RETAIL_WALL_WEST_2_DOOR3 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_WEST_2_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_WEST_2_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_EAST_2_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_EAST_2
CORE_RETAIL_WALL_EAST_2_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_EAST_2
CORE_RETAIL_WALL_EAST_2_DOOR3 SWINGING DOOR_CON 2.101 3.065 1.95 CORE_RETAIL_WALL_EAST_2


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
SKYLIGHTS_R4C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
POINT_OF_SALE_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
FRONT_RETAIL_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
FRONT_ENTRY_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BACK_SPACE_LIGHTS BACK_SPACE BACK_SPACE GENERAL 4.6739 379.89 1775.58 LightsWired LTG_SCH_BACK 32.16 168.00 32.49 0.0000 Y 10.83
CORE_RETAIL_LIGHTS CORE_RETAIL CORE_RETAIL GENERAL 11.3021 1600.48 18088.80 LightsWired LTG_SCH_CORE 69.21 168.00 45.32 0.0000 Y 153.88
POINT_OF_SALE_LIGHTS POINT_OF_SALE POINT_OF_SALE GENERAL 11.3021 150.81 1704.47 LightsWired LTG_SCH_SALE 69.21 168.00 65.23 0.0000 Y 20.87
FRONT_RETAIL_LIGHTS FRONT_RETAIL FRONT_RETAIL GENERAL 11.3021 150.81 1704.47 LightsWired LTG_SCH_FRONT 69.21 168.00 65.23 0.0000 Y 20.87
FRONT_ENTRY_LIGHTS FRONT_ENTRY FRONT_ENTRY GENERAL 7.5347 12.00 90.42 LightsWired LTG_SCH_ENTRY 38.07 168.00 37.20 0.0000 Y 0.63
Interior Lighting Total       10.1847 2293.99 23363.73               207.08


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
CORE_RETAIL_DAYLREFPT1 CORE_RETAIL CORE_RETAIL_DAYLCTRL SplitFlux Continuous/Off 0.25 18088.80 4522.20
CORE_RETAIL_DAYLREFPT2 CORE_RETAIL CORE_RETAIL_DAYLCTRL SplitFlux Continuous/Off 0.25 18088.80 4522.20


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 358.54 AstronomicalClock -   41.93 41.93 2.82
EXTERIOR_LIGHTS_B 3462.32 AstronomicalClock -   83.83 62.88 40.87
Exterior Lighting Total 3820.86           43.69



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   39067.33 29939.25 9128.08 0.77 3.74    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   187506.00 131456.71 56049.29 0.70 3.32    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   25566.69 18793.56 6773.13 0.74 3.74    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   22523.73 16190.06 6333.67 0.72 3.74    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   37571.7     11.42 11.42  
PSZ-AC:2 HP COOLING COIL   181549.0     10.63 10.63  
PSZ-AC:3 HP COOLING COIL   24666.7     11.59 11.59  
PSZ-AC:4 HP COOLING COIL   21768.9     11.68 11.68  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed 39978.9 22121.6 8.04 2
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed 193572.4 106514.4 7.34 2
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed 26162.4 14439.9 8.12 2
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed 23028.2 12692.8 8.11 2
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
FRONT_ENTRY UNIT HEATER HEATING COIL Coil:Heating:Electric   417.48 1.00
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed   38461.19 3.55
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Electric   38461.19 1.00
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed   187506.00 3.49
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Electric   187506.00 1.00
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed   25247.89 3.55
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Electric   25247.89 1.00
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed   22260.59 3.55
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Electric   22260.59 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
FRONT_ENTRY UNIT HEATER FAN Fan:ConstantVolume 0.54 49.80 0.01 1.32 92.91 1.00 66.35 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.58 622.50 1.90 2035.58 1070.05 1.00 1.32 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:20:00
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.60 1018.41 7.55 12721.06 1684.71 1.00 1.16 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:20:00
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 622.50 1.14 1265.47 1107.16 1.00 1.37 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:00:00
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 622.50 0.96 1060.42 1107.16 1.00 1.41 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:40:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
None                


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 1.00 0.93



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BACK_SPACE 21608.68 25930.41 68.26 1.524 1.829 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:00:00 23.89 23.89 0.00891 28.91 0.01715 0.232 0.00
CORE_RETAIL 86304.41 103565.30 64.71 6.078 7.293 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:00:00 23.89 23.89 0.00982 28.91 0.01715 1.890 0.00
POINT_OF_SALE 13162.36 15794.84 104.73 0.941 1.129 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:00:00 23.89 23.89 0.00908 28.91 0.01715 0.178 0.00
FRONT_RETAIL 10871.29 13045.55 86.50 0.798 0.958 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:40:00 23.89 23.89 0.00912 35.20 0.01716 0.178 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.000 0.014 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 0.00 34.78 0.01721 35.12 0.01716 0.014 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BACK_SPACE 5974.52 7169.43 18.87 0.251 0.301 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.11 21.11 0.00944 20.10 0.01480 0.232 0.00
CORE_RETAIL 18078.47 21694.17 13.55 0.758 1.890 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.11 21.11 0.00845 20.10 0.01480 1.890 0.00
POINT_OF_SALE 2727.49 3272.98 21.70 0.115 0.178 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.11 21.11 0.00948 20.10 0.01480 0.178 0.00
FRONT_RETAIL 2727.49 3272.98 21.70 0.115 0.178 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.11 21.11 0.00948 20.10 0.01480 0.178 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.000 0.014   00:10:00 15.56 19.52 0.01427 20.10 0.01480 0.014 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 1.90 1.90 0.30 0.30 1.9023 1.8288 1.9023 0.9613 1.0000
PSZ-AC:2 7.55 7.55 1.89 1.89 7.5509 7.2931 7.5509 0.9659 1.0000
PSZ-AC:3 1.14 1.14 0.18 0.18 1.1430 1.1286 1.1430 0.9874 1.0000
PSZ-AC:4 0.96 0.96 0.18 0.18 0.9578 0.9578 0.9578 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
FRONT_ENTRY UNIT HEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER FRONT_ENTRY UNIT HEATER 417.481 417.481 -999.0 -999.0 -999.000   12/21 00:10:00   12/21 00:10:00 417.48 417.48 0.014173 16.00 12.90 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 16.00 0.00800000 70.7169 0.00 0.00 -999.00 -999.00
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:1 39067.330 29939.248 1.902330 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:20:00 19533.67 16053.59 1.268220 26.10 18.15 0.00975884 12.80 12.09 0.00850000 34.86 0.01715750 25.74 18.2603 23.89 0.00873088 47.2730 21550.30 0.00 -999.00 -999.00
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:1 38461.192 38461.192 1.902328 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 19230.60 19230.60 0.951164 20.81 16.61 0.01008933 40.00 21.18 0.00800000 20.10 0.01479830 20.10 24.3471 21.11 0.00943662 60.4239 5974.52 0.00 -999.00 -999.00
PSZ-AC:1_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:1 38461.192 38461.192 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 38461.19 38461.19 1.902328 20.81 16.61 0.01008933 40.00 21.18 0.00800000 20.10 0.01479830 20.10 12.1735 21.11 0.00943662 60.4239 5974.52 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:2 187506.000 131456.706 7.550870 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 13:50:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:20:00 93753.00 66061.97 5.033913 28.16 19.99 0.01127660 12.80 12.09 0.00850000 35.13 0.01715801 25.81 37.5519 23.89 0.00922225 49.8990 83017.42 0.00 -999.00 -999.00
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:2 187505.997 187505.997 7.550866 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 93753.00 88701.26 3.775433 20.86 16.52 0.00995493 40.00 21.18 0.00800000 20.10 0.01479830 20.10 50.0692 20.02 0.00833750 57.1837 0.00 0.00 -999.00 -999.00
PSZ-AC:2_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:2 187505.997 187505.997 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 187506.00 177402.53 7.550866 20.86 16.52 0.00995493 40.00 21.18 0.00800000 20.10 0.01479830 20.10 25.0346 20.02 0.00833750 57.1837 0.00 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:3 25566.690 18793.562 1.142990 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:00:00 12783.34 9830.38 0.761993 26.54 18.72 0.01029734 12.80 12.09 0.00850000 35.12 0.01715799 25.81 23.3757 23.89 0.00902553 48.8502 12927.94 0.00 -999.00 -999.00
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:3 25247.887 25247.887 1.142991 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 15:20:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 15:20:00 12623.94 12623.94 0.571495 20.95 16.28 0.00963419 40.00 21.18 0.00800000 20.10 0.01479830 20.10 31.1676 21.11 0.00868086 55.6530 1417.88 0.00 -999.00 -999.00
PSZ-AC:3_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:3 25247.887 25247.887 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 15:20:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 15:20:00 25247.89 25247.89 1.142991 20.95 16.28 0.00963419 40.00 21.18 0.00800000 20.10 0.01479830 20.10 15.5838 21.11 0.00868086 55.6530 1417.88 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:4 22523.730 16190.057 0.957780 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:40:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:40:00 11261.86 8366.93 0.638520 26.89 19.09 0.01061779 12.80 12.09 0.00850000 35.20 0.01715815 25.83 27.8960 23.89 0.00912358 49.3733 10871.29 0.00 -999.00 -999.00
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:4 22260.589 22260.589 0.957784 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 14:30:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 14:30:00 11130.29 11130.29 0.478892 20.92 16.44 0.00983738 40.00 21.18 0.00800000 20.10 0.01479830 20.10 37.1945 21.11 0.00870401 55.7993 1434.71 0.00 -999.00 -999.00
PSZ-AC:4_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:4 22260.589 22260.589 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 14:30:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 14:30:00 22260.59 22260.59 0.957784 20.92 16.44 0.00983738 40.00 21.18 0.00800000 20.10 0.01479830 20.10 18.5973 21.11 0.00870401 55.7993 1434.71 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
FRONT_ENTRY UNIT HEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER FRONT_ENTRY UNIT HEATER FRONT_ENTRY N/A N/A N/A Yes No unknown No 417.481 417.481 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 FRONT_ENTRY UNIT HEATER FAN Fan:ConstantVolume 0.014173 0.01705878   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0   12/21 00:10:00 unknown unknown   12/21 00:10:00 Sensible 417.48 417.48 1.0000 0.01705878 0.014173 16.00 12.90 0.00800000 36322.9 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 417.48 20.10 0.01479830 20.10 0.00000000 0.0000 16.00 0.00800000 16.00 0.00800000 70.7169 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident CoolingDesignCapacity N/A No No unknown No 39067.330 29939.248 1.902330 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.9812 1004.8586 1.2036 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.902328 2.28963290   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:20:00 Sensible 19533.67 16053.59 1.0000 1.52642323 1.268220 26.10 18.15 0.00975884 51102.7 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 19533.67 34.86 0.01715750 25.74 0.23158056 18.2603 23.89 0.00873088 23.89 0.00873088 47.2730 21550.30 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident HeatingDesignCapacity N/A Yes Yes unknown No 38461.192 38461.192 1.902328 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.902328 2.28963290   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 19230.60 19230.60 1.0000 1.14481645 0.951164 20.81 16.61 0.01008933 46533.6 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 19230.60 20.10 0.01479830 20.10 0.23158056 24.3471 20.91 0.00943662 21.11 0.00943662 60.4239 5974.52 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident HeatingDesignCapacity N/A Yes No unknown No 38461.192 38461.192 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.902328 2.28963290   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 38461.19 38461.19 1.0000 2.28963290 1.902328 20.81 16.61 0.01008933 46533.6 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 38461.19 20.10 0.01479830 20.10 0.23158056 12.1735 20.91 0.00943662 21.11 0.00943662 60.4239 5974.52 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident CoolingDesignCapacity N/A No No unknown No 187506.000 131456.706 7.550870 -999.0 -999.000 -999.0000 1.00000 1.00000 1025.8026 1004.8586 1.2036 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 7.550866 9.08818500   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 13:50:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 13:40:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:20:00 Sensible 93753.00 66061.97 1.0000 6.05879283 5.033913 28.16 19.99 0.01127660 57091.2 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 93753.00 35.13 0.01715801 25.81 1.89032875 37.5519 23.89 0.00922225 23.89 0.00922225 49.8990 83017.42 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident HeatingDesignCapacity N/A Yes Yes unknown No 187505.997 187505.997 7.550866 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 7.550866 9.08818500   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 93753.00 88701.26 1.0000 4.54409250 3.775433 20.86 16.52 0.00995493 46240.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 93753.00 20.10 0.01479830 20.10 1.89032875 50.0692 21.11 0.00833750 20.02 0.00833750 57.1837 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident HeatingDesignCapacity N/A Yes No unknown No 187505.997 187505.997 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 7.550866 9.08818500   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 187506.00 177402.53 1.0000 9.08818500 7.550866 20.86 16.52 0.00995493 46240.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 187506.00 20.10 0.01479830 20.10 1.89032875 25.0346 21.11 0.00833750 20.02 0.00833750 57.1837 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident CoolingDesignCapacity N/A No No unknown No 25566.690 18793.562 1.142990 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.9822 1004.8586 1.2036 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.142991 1.37569812   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:00:00 Sensible 12783.34 9830.38 1.0000 0.91713135 0.761993 26.54 18.72 0.01029734 52931.4 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 12783.34 35.12 0.01715799 25.81 0.17812154 23.3757 23.89 0.00902553 23.89 0.00902553 48.8502 12927.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident HeatingDesignCapacity N/A Yes Yes unknown No 25247.887 25247.887 1.142991 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.142991 1.37569812   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 15:20:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 15:20:00 Sensible 12623.94 12623.94 1.0000 0.68784906 0.571495 20.95 16.28 0.00963419 45524.1 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12623.94 20.10 0.01479830 20.10 0.17812154 31.1676 21.11 0.00868086 21.11 0.00868086 55.6530 1417.88 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident HeatingDesignCapacity N/A Yes No unknown No 25247.887 25247.887 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.142991 1.37569812   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 15:20:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 15:20:00 Sensible 25247.89 25247.89 1.0000 1.37569812 1.142991 20.95 16.28 0.00963419 45524.1 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 25247.89 20.10 0.01479830 20.10 0.17812154 15.5838 21.11 0.00868086 21.11 0.00868086 55.6530 1417.88 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident CoolingDesignCapacity N/A No No unknown No 22523.730 16190.057 0.957780 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.5779 1004.8586 1.2036 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.957784 1.15278369   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:40:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:40:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:40:00 Sensible 11261.86 8366.93 1.0000 0.76851947 0.638520 26.89 19.09 0.01061779 54104.6 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 11261.86 35.20 0.01715815 25.83 0.17812154 27.8960 23.89 0.00912358 23.89 0.00912358 49.3733 10871.29 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident HeatingDesignCapacity N/A Yes Yes unknown No 22260.589 22260.589 0.957784 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.957784 1.15278369   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 14:30:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 14:30:00 Sensible 11130.29 11130.29 1.0000 0.57639184 0.478892 20.92 16.44 0.00983738 46009.1 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 11130.29 20.10 0.01479830 20.10 0.17812154 37.1945 21.11 0.00870401 21.11 0.00870401 55.7993 1434.71 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident HeatingDesignCapacity N/A Yes No unknown No 22260.589 22260.589 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.957784 1.15278369   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 14:30:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 14:30:00 Sensible 22260.59 22260.59 1.0000 1.15278369 0.957784 20.92 16.44 0.00983738 46009.1 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 22260.59 20.10 0.01479830 20.10 0.17812154 18.5973 21.11 0.00870401 21.11 0.00870401 55.7993 1434.71 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BACK_SPACE 4902.33 126.83 126.83
CORE_RETAIL 4913.00 2063.50 2063.50
POINT_OF_SALE 4913.00 176.17 176.17
FRONT_RETAIL 4913.00 500.50 500.50
FRONT_ENTRY 4913.00 4910.67 4910.67
Facility 4913.00 4910.67 4910.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BACK_SPACE 0.00 561.67 0.00 0.00
CORE_RETAIL 0.00 0.00 0.00 0.00
POINT_OF_SALE 0.00 784.00 0.00 0.00
FRONT_RETAIL 0.00 722.50 0.00 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.00
Facility 0.00 786.17 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BACK_SPACE 4.07 8.18 2317.33 0.372 0.008 0.000 0.000
CORE_RETAIL 128.48 258.43 9762.95 0.722 0.002 0.000 0.000
POINT_OF_SALE 12.11 24.35 919.94 0.720 0.010 0.000 0.000
FRONT_RETAIL 12.11 24.35 919.94 0.721 0.010 0.000 0.000
FRONT_ENTRY 0.96 1.94 73.20 0.000 35.295 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BACK_SPACE 4.07 8.18 2317.33 0.364 0.000 0.000 0.000
CORE_RETAIL 128.48 258.43 9762.95 0.706 0.000 0.000 0.000
POINT_OF_SALE 12.11 24.35 919.94 0.705 0.000 0.000 0.000
FRONT_RETAIL 12.11 24.35 919.94 0.705 0.000 0.000 0.000
FRONT_ENTRY 0.96 1.94 73.20 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BACK_SPACE PSZ-AC:1 4.07 8.18 2317.33 379.89 0.2316 0.232
CORE_RETAIL PSZ-AC:2 128.48 258.43 9762.95 1600.48 1.8903 1.890
POINT_OF_SALE PSZ-AC:3 12.11 24.35 919.94 150.81 0.1781 0.178
FRONT_RETAIL PSZ-AC:4 12.11 24.35 919.94 150.81 0.1781 0.178
FRONT_ENTRY   0.96 1.94 73.20 12.00   0.014
Total Facility   157.72 317.25 13993.36 2293.99 2.4782 2.492


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BACK_SPACE 5173616.98 0.00 5173616.98 274200.50 5447817.49 7303124.67 3380.83 5379.17 0.00 2798.14
CORE_RETAIL 35917929.34 0.00 35917929.34 235120.81 36153050.14 59613407.55 3482.00 5278.00 0.00 365.00
POINT_OF_SALE 3929241.34 0.00 3929241.34 125051.01 4054292.36 5617240.89 3426.15 5333.85 0.00 2821.04
FRONT_RETAIL 3932474.96 0.00 3932474.96 125051.01 4057525.97 5617240.89 3419.43 5340.58 0.00 2813.81
FRONT_ENTRY 0.00 0.00 0.00 11958831.05 11958831.05 446965.66 8760.00 0.00 0.00 0.00
Total Facility 48953262.62 0.00 48953262.62 12718254.39 61671517.01 78597979.65 8760.00 5391.25 0.00 2943.21


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BACK_SPACE 0.2316 0.0000 0.2316 0.0052 0.2368 0.2316 0.00 4913.00 0.00
CORE_RETAIL 1.8903 0.0000 1.8903 0.0045 1.8948 1.8903 0.00 4913.00 0.00
POINT_OF_SALE 0.1781 0.0000 0.1781 0.0024 0.1805 0.1781 0.00 4913.00 0.00
FRONT_RETAIL 0.1781 0.0000 0.1781 0.0024 0.1805 0.1781 0.00 4913.00 0.00
FRONT_ENTRY 0.0000 0.0000 0.0000 0.6707 0.6707 0.0142 4913.00 0.00 0.00
Total Facility 2.4782 0.0000 2.4782 0.6851 3.1633 2.4923 4913.00 4913.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 7494649.47 0.00 7494649.47 7303124.67 3146.08 24.80 5589.12 2789.07
PSZ-AC:2 52031933.36 0.00 52031933.36 59613407.55 3482.00 0.00 5278.00 365.00
PSZ-AC:3 5692084.39 0.00 5692084.39 5617240.89 3238.92 4.76 5516.31 2820.64
PSZ-AC:4 5696814.50 0.00 5696814.50 5617240.89 3236.11 5.21 5518.68 2813.23


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.3355 0.0000 0.3355 0.2316 0.00 0.00 4913.00
PSZ-AC:2 2.7384 0.0000 2.7384 1.8903 0.00 0.00 4913.00
PSZ-AC:3 0.2580 0.0000 0.2580 0.1781 0.00 0.00 4913.00
PSZ-AC:4 0.2580 0.0000 0.2580 0.1781 0.00 0.00 4913.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 7702.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 5278.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 7733.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 7726.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.3355 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 2.7384 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.2580 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.2580 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Surfaces by Class

Total Outdoors
Wall 26 10
Floor 5 5
Roof 5 5
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 19 19
Door 13 13
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 4
Conditioned Zones 5
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 507
Defaulted Fields 477
Fields with Defaults 1428
Autosized Fields 96
Autosizable Fields 234
Autocalculated Fields 78
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1389.84 2224.80 08-JAN-06:40 107820.45 13-JUN-15:00
Electricity:Building 401.38 2224.80 01-JAN-00:10 30876.16 02-JAN-17:40
Electricity:Zone:BACK_SPACE 60.60 495.06 01-JAN-00:10 3493.96 02-JAN-09:10
Electricity:SpaceType:GENERAL 401.38 2224.80 01-JAN-00:10 30876.16 02-JAN-17:40
InteriorLights:Electricity 207.08 453.21 01-JAN-00:10 20135.27 02-JAN-17:40
InteriorLights:Electricity:Zone:BACK_SPACE 10.83 41.25 01-JAN-00:10 742.55 02-JAN-09:10
InteriorLights:Electricity:SpaceType:GENERAL 207.08 453.21 01-JAN-00:10 20135.27 02-JAN-17:40
LightsWired:InteriorLights:Electricity 207.08 453.21 01-JAN-00:10 20135.27 02-JAN-17:40
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE 10.83 41.25 01-JAN-00:10 742.55 02-JAN-09:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 207.08 453.21 01-JAN-00:10 20135.27 02-JAN-17:40
Electricity:Zone:CORE_RETAIL 237.81 1109.80 01-JAN-00:10 20919.50 02-JAN-17:40
InteriorLights:Electricity:Zone:CORE_RETAIL 153.88 344.55 01-JAN-00:10 16279.92 02-JAN-17:40
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL 153.88 344.55 01-JAN-00:10 16279.92 02-JAN-17:40
Electricity:Zone:POINT_OF_SALE 73.56 512.89 01-JAN-00:10 4446.73 02-JAN-09:10
InteriorLights:Electricity:Zone:POINT_OF_SALE 20.87 32.47 01-JAN-00:10 1534.02 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE 20.87 32.47 01-JAN-00:10 1534.02 02-JAN-09:10
Electricity:Zone:FRONT_RETAIL 28.78 104.57 01-JAN-00:10 1971.20 02-JAN-09:10
InteriorLights:Electricity:Zone:FRONT_RETAIL 20.87 32.47 01-JAN-00:10 1534.02 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL 20.87 32.47 01-JAN-00:10 1534.02 02-JAN-09:10
Electricity:Zone:FRONT_ENTRY 0.63 2.49 01-JAN-00:10 44.76 02-JAN-09:10
InteriorLights:Electricity:Zone:FRONT_ENTRY 0.63 2.49 01-JAN-00:10 44.76 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY 0.63 2.49 01-JAN-00:10 44.76 02-JAN-09:10
InteriorEquipment:Electricity 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
InteriorEquipment:Electricity:Zone:BACK_SPACE 49.77 453.82 01-JAN-00:10 2751.42 02-JAN-09:10
InteriorEquipment:Electricity:SpaceType:GENERAL 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE 49.77 453.82 01-JAN-00:10 2751.42 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
InteriorEquipment:Electricity:Zone:CORE_RETAIL 83.93 765.25 01-JAN-00:10 4639.58 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL 83.93 765.25 01-JAN-00:10 4639.58 02-JAN-09:10
InteriorEquipment:Electricity:Zone:POINT_OF_SALE 52.69 480.42 01-JAN-00:10 2912.71 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE 52.69 480.42 01-JAN-00:10 2912.71 02-JAN-09:10
InteriorEquipment:Electricity:Zone:FRONT_RETAIL 7.91 72.11 01-JAN-00:10 437.18 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL 7.91 72.11 01-JAN-00:10 437.18 02-JAN-09:10
ElectricityPurchased:Facility 1389.84 2224.80 08-JAN-08:00 107820.45 13-JUN-15:00
ElectricityPurchased:Plant 1389.84 2224.80 08-JAN-08:00 107820.45 13-JUN-15:00
Cogeneration:ElectricityPurchased 1389.84 2224.80 08-JAN-08:00 107820.45 13-JUN-15:00
General:Cogeneration:ElectricityPurchased 1389.84 2224.80 08-JAN-08:00 107820.45 13-JUN-15:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1389.84 2224.80 08-JAN-08:00 107820.45 13-JUN-15:00
ElectricityNet:Plant 1389.84 2224.80 08-JAN-08:00 107820.45 13-JUN-15:00
Cogeneration:ElectricityNet 1389.84 2224.80 08-JAN-08:00 107820.45 13-JUN-15:00
General:Cogeneration:ElectricityNet 1389.84 2224.80 08-JAN-08:00 107820.45 13-JUN-15:00
Electricity:HVAC 927.11 0.00 01-JAN-19:40 80756.44 13-JUN-15:00
Fans:Electricity 160.62 0.00 01-JAN-19:40 13473.24 13-JUN-15:00
General:Fans:Electricity 160.62 0.00 01-JAN-19:40 13473.24 13-JUN-15:00
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 766.49 0.00 01-JAN-19:40 67283.20 13-JUN-15:00
General:Cooling:Electricity 766.49 0.00 01-JAN-19:40 67283.20 13-JUN-15:00
ExteriorLights:Electricity 43.69 0.00 01-JAN-06:20 3820.86 01-JAN-06:10
General:ExteriorLights:Electricity 43.69 0.00 01-JAN-06:20 3820.86 01-JAN-06:10
Electricity:Plant 17.66 0.00 01-JAN-00:10 1551.69 12-JAN-12:50
WaterSystems:Electricity 17.66 0.00 01-JAN-00:10 1551.69 12-JAN-12:50
Water Heater:WaterSystems:Electricity 17.66 0.00 01-JAN-00:10 1551.69 12-JAN-12:50


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 4298.73 0.00 01-JAN-19:40 339178.57 13-JUN-15:00
EnergyTransfer:Building 1317.92 0.00 01-JAN-19:40 101759.75 06-MAY-15:30
EnergyTransfer:Zone:BACK_SPACE 269.37 0.00 01-JAN-00:10 21464.21 13-JUN-17:00
Heating:EnergyTransfer 2.34 0.00 01-JAN-00:10 11119.25 06-MAY-05:20
Heating:EnergyTransfer:Zone:BACK_SPACE 0.02 0.00 01-JAN-00:10 1020.94 20-AUG-07:20
General:Heating:EnergyTransfer 2.34 0.00 01-JAN-00:10 11119.25 06-MAY-05:20
General:Heating:EnergyTransfer:Zone:BACK_SPACE 0.02 0.00 01-JAN-00:10 1020.94 20-AUG-07:20
Cooling:EnergyTransfer 1315.58 0.00 01-JAN-19:40 101759.75 06-MAY-15:30
Cooling:EnergyTransfer:Zone:BACK_SPACE 269.35 0.00 01-JAN-00:10 21464.21 13-JUN-17:00
General:Cooling:EnergyTransfer 1315.58 0.00 01-JAN-19:40 101759.75 06-MAY-15:30
General:Cooling:EnergyTransfer:Zone:BACK_SPACE 269.35 0.00 01-JAN-00:10 21464.21 13-JUN-17:00
EnergyTransfer:Zone:CORE_RETAIL 708.31 0.00 01-JAN-00:10 64440.47 06-MAY-06:10
Heating:EnergyTransfer:Zone:CORE_RETAIL 2.31 0.00 01-JAN-00:10 11119.25 06-MAY-05:20
General:Heating:EnergyTransfer:Zone:CORE_RETAIL 2.31 0.00 01-JAN-00:10 11119.25 06-MAY-05:20
Cooling:EnergyTransfer:Zone:CORE_RETAIL 706.00 0.00 01-JAN-00:10 61340.29 06-MAY-06:10
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL 706.00 0.00 01-JAN-00:10 61340.29 06-MAY-06:10
EnergyTransfer:Zone:POINT_OF_SALE 187.73 0.00 01-JAN-00:40 13602.63 07-DEC-15:30
Heating:EnergyTransfer:Zone:POINT_OF_SALE 0.01 0.00 01-JAN-00:10 520.19 05-AUG-05:10
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE 0.01 0.00 01-JAN-00:10 520.19 05-AUG-05:10
Cooling:EnergyTransfer:Zone:POINT_OF_SALE 187.72 0.00 01-JAN-00:40 13602.63 07-DEC-15:30
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE 187.72 0.00 01-JAN-00:40 13602.63 07-DEC-15:30
EnergyTransfer:Zone:FRONT_RETAIL 152.51 0.00 01-JAN-00:40 11781.01 07-DEC-15:20
Heating:EnergyTransfer:Zone:FRONT_RETAIL 0.01 0.00 01-JAN-00:10 463.55 13-AUG-07:10
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL 0.01 0.00 01-JAN-00:10 463.55 13-AUG-07:10
Cooling:EnergyTransfer:Zone:FRONT_RETAIL 152.51 0.00 01-JAN-00:40 11781.01 07-DEC-15:20
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL 152.51 0.00 01-JAN-00:40 11781.01 07-DEC-15:20
EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:HVAC 2980.82 0.00 01-JAN-19:40 240219.50 13-JUN-15:00
HeatingCoils:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
CoolingCoils:EnergyTransfer 2980.82 0.00 01-JAN-19:40 240219.50 13-JUN-15:00
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BACK_SPACE 0.000 0.000 0.016 -269.348 0.000 0.000 4.889 10.830 49.772 0.000 0.000 1.132 202.752 0.000 0.000 0.000 -0.043 -0.000
CORE_RETAIL 0.000 0.000 2.309 -705.978 0.000 0.000 154.442 153.883 83.928 47.993 0.000 0.682 268.174 0.000 -5.262 0.000 -0.172 -0.011
POINT_OF_SALE 0.000 0.000 0.008 -187.720 0.000 0.000 14.557 20.870 52.690 28.697 0.000 0.513 72.579 0.000 -2.172 0.000 -0.021 -0.000
FRONT_RETAIL 0.000 0.000 0.007 -152.505 0.000 0.000 14.557 20.870 7.908 28.506 0.000 0.515 82.243 0.000 -2.081 0.000 -0.020 -0.000
FRONT_ENTRY 0.000 0.000 0.000 0.000 0.000 0.000 0.612 0.631 0.000 4.834 0.000 2.414 0.000 0.000 -0.924 0.000 -1.386 -6.183
Total Facility 0.000 0.000 2.339 -1315.551 0.000 0.000 189.057 207.083 194.299 110.030 0.000 5.256 625.749 0.000 -10.439 0.000 -1.641 -6.194


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BACK_SPACE 20-DEC-21:10 0.00 0.00 0.00 -30686.60 0.00 0.00 0.00 165.00 605.09 0.00 0.00 0.00 29954.78 0.00 -0.00 0.00 -38.27 0.00
CORE_RETAIL 24-FEB-07:02 0.00 0.00 0.00 -126096.54 0.00 0.00 1606.13 344.55 2062.04 286.08 0.00 0.00 121804.26 0.00 -0.00 0.00 -6.51 0.00
POINT_OF_SALE 20-DEC-21:08 0.00 0.00 0.00 -20006.73 0.00 0.00 0.00 340.89 640.56 0.00 0.00 0.00 19498.94 0.00 -454.16 0.00 -19.51 0.00
FRONT_RETAIL 20-DEC-21:08 0.00 0.00 0.00 -17030.77 0.00 0.00 0.00 340.89 96.14 0.00 0.00 0.00 17051.51 0.00 -438.69 0.00 -19.08 0.00
FRONT_ENTRY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 07-MAY-07:02 0.00 0.00 0.00 -159969.01 0.00 0.00 0.00 453.21 1771.59 3454.20 0.00 308.64 153981.37 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BACK_SPACE 18-JUN-07:08 0.00 0.00 2181.80 0.00 0.00 0.00 0.00 41.25 453.82 0.00 0.00 20.67 0.00 0.00 -0.00 0.00 0.00 -2697.53
CORE_RETAIL 28-MAY-07:05 0.00 0.00 21848.81 0.00 0.00 0.00 0.00 344.55 765.25 1814.13 0.00 16.37 0.00 0.00 -0.00 0.00 0.00 -24789.11
POINT_OF_SALE 13-AUG-07:07 0.00 0.00 1561.09 0.00 0.00 0.00 0.00 32.47 480.42 635.98 0.00 15.11 0.00 0.00 -0.00 0.00 0.00 -2725.07
FRONT_RETAIL 13-AUG-07:07 0.00 0.00 1391.08 0.00 0.00 0.00 0.00 32.47 72.11 646.27 0.00 14.85 0.00 0.00 -0.00 0.00 0.00 -2156.78
FRONT_ENTRY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 28-MAY-07:05 -5843.81 5843.81 21848.81 -5843.81 0.00 0.00 0.00 453.21 1771.59 4185.91 0.00 684.89 0.00 0.00 0.00 0.00 0.00 -23100.59



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 1.8288 0.0000 8.1781 1.0000 Calculated from schedules 0.2316 1.9023 0.1217 1.0000 Not calculated 0.2316 0.1217    
PSZ-AC:2 7.2931 0.0000 258.4342 1.0000 Calculated from schedules 1.8903 7.5509 0.2503 1.0000 Not calculated 1.8903 0.2503    
PSZ-AC:3 1.1286 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.1430 0.1558 1.0000 Not calculated 0.1781 0.1558    
PSZ-AC:4 0.9578 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 0.9578 0.1860 1.0000 Not calculated 0.1781 0.1860    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 1.8288 0.0000 8.1781 1.0000 Calculated from schedules 0.2316 1.8288 1.0000 1.0000 Not calculated 0.2316 0.1266    
PSZ-AC:2 7.2931 0.0000 258.4342 1.0000 Calculated from schedules 1.8903 7.2931 1.0000 1.0000 Not calculated 1.8903 0.2592    
PSZ-AC:3 1.1286 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.1286 1.0000 1.0000 Not calculated 0.1781 0.1578    
PSZ-AC:4 0.9578 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 0.9578 1.0000 1.0000 Not calculated 0.1781 0.1860    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BACK_SPACE PSZ-AC:1 0.000000 8.1781 0.000610 379.89 0.2316 1.0000 0.2316 1.000 0.2316
CORE_RETAIL PSZ-AC:2 0.000000 258.4342 0.001181 1600.48 1.8903 1.0000 1.8903 1.000 1.8903
POINT_OF_SALE PSZ-AC:3 0.000000 24.3517 0.001181 150.81 0.1781 1.0000 0.1781 1.000 0.1781
FRONT_RETAIL PSZ-AC:4 0.000000 24.3517 0.001181 150.81 0.1781 1.0000 0.1781 1.000 0.1781


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.18 0.000610 379.8900 0.2316 0.2316 0.2316
PSZ-AC:2 0.000000 258.43 0.001181 1600.4829 1.8903 1.8903 1.8903
PSZ-AC:3 0.000000 24.35 0.001181 150.8100 0.1781 0.1781 0.1781
PSZ-AC:4 0.000000 24.35 0.001181 150.8100 0.1781 0.1781 0.1781


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BACK_SPACE PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.8288 1.8288 1.8288 No 0.2316 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_RETAIL PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 7.2931 7.2931 7.2931 No 1.8903 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
POINT_OF_SALE PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.1286 1.1286 1.1286 No 0.1781 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FRONT_RETAIL PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.9578 0.9578 0.9578 No 0.1781 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 1.8288 1.9023 1.8288 1.8288 0.2316 1.0000
PSZ-AC:2 7.2931 7.5509 7.2931 7.2931 1.8903 1.0000
PSZ-AC:3 1.1286 1.1430 1.1286 1.1286 0.1781 1.0000
PSZ-AC:4 0.9578 0.9578 0.9578 0.9578 0.1781 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BACK_SPACE PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.8288 1.8288 1.8288 No 0.2316 0.7692 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_RETAIL PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 7.2931 7.2931 7.2931 No 1.8903 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
POINT_OF_SALE PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.1286 1.1286 1.1286 No 0.1781 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FRONT_RETAIL PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.9578 0.9578 0.9578 No 0.1781 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 1.8288 1.8288 1.8288 1.8288 0.2316 1.0000
PSZ-AC:2 7.2931 7.2931 7.2931 7.2931 1.8903 1.0000
PSZ-AC:3 1.1286 1.1286 1.1286 1.1286 0.1781 1.0000
PSZ-AC:4 0.9578 0.9578 0.9578 0.9578 0.1781 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Total gross floor area [m2] 2293.99


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BACK_SPACE 379.89 379.89 0.00 94.22
CORE_RETAIL 1600.48 1600.48 0.00 94.22
POINT_OF_SALE 150.81 150.81 0.00 94.22
FRONT_RETAIL 150.81 150.81 0.00 94.22
FRONT_ENTRY 12.00 12.00 0.00 94.22
Totals 2293.99 2293.99 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 766.49 67283.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 207.08 20135.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 43.69 3820.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 194.30 10740.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 160.62 13473.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 17.66 1551.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 194.30 1389.84
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 194.30 1389.84


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 90.27
Space Heating 0.00
Space Cooling 334.13
Fans (All) 70.02
Service Water Heating 7.70
Receptacle Equipment 84.70
Miscellaneous (All) 605.86
Subtotal 605.86


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 14.90
Space Heating 0.00
Space Cooling 55.15
Fans (All) 11.56
Service Water Heating 1.27
Receptacle Equipment 13.98
Miscellaneous 3.14


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
FRONTENTRY_COILSCHED 8760. 8760.
FRONTENTRY_FANSCHED 8760. 8760.
LTG_SCH_ENTRY 1985. 8760.
LTG_SCH_CORE 3609. 8760.
LTG_SCH_BACK 1677. 8760.
LTG_SCH_SALE 3609. 8760.
LTG_SCH_FRONT 3609. 8760.
BLDG_OCC_SCH 2410. 4950.
BLDG_EQUIP_SCH 4552. 8760.
BLDG_ELEVATORS 2743. 4950.
INFIL_SCH 3551. 3551.
INFIL_HALF_ON_SCH 6156. 8760.
INFIL_DOOR_OPENING_SCH 2505. 4380.
BLDG_SWH_SCH 2009. 4950.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6543. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4950. 4950.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
INFIL_SCH_PNNL 4774. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4950. 4950.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
SZ_SYSTEM_OA_MAX_FRAC_SCH 6570. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_FRONTENTRY_STD2013 FRONT_ENTRY HEATING SP January 16.00 365 15.56 365
HTGSETP_SCH_NO_OPTIMUM BACK_SPACE DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_NO_SETBACK BACK_SPACE DUAL SP CONTROL July 23.89 365 23.89 365
HTGSETP_SCH_YES_OPTIMUM CORE_RETAIL DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM CORE_RETAIL DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BACK_SPACE 8760.00 0.00 0.00 0.00 0.00
CORE_RETAIL 7772.67 987.33 0.00 0.00 0.00
POINT_OF_SALE 8760.00 0.00 0.00 0.00 0.00
FRONT_RETAIL 8760.00 0.00 0.00 0.00 0.00
FRONT_ENTRY 293.17 3756.50 4222.50 487.83 0.00
Min 293.17 0.00 0.00 0.00 0.00
Max 8760.00 3756.50 4222.50 487.83 0.00
Average 6869.17 948.77 844.50 97.57 0.00
Sum 34345.83 4743.83 4222.50 487.83 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BACK_SPACE 16872.00 0.00 0.00 0.00 0.00
CORE_RETAIL 609599.00 0.00 0.00 0.00 0.00
POINT_OF_SALE 56000.00 0.00 0.00 0.00 0.00
FRONT_RETAIL 56000.00 0.00 0.00 0.00 0.00
FRONT_ENTRY 31.67 248.83 1279.33 360.17 0.00
Min 31.67 0.00 0.00 0.00 0.00
Max 609599.00 248.83 1279.33 360.17 0.00
Average 147700.53 49.77 255.87 72.03 0.00
Sum 738502.67 248.83 1279.33 360.17 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BACK_SPACE 8610.17 149.83 0.00 0.00 0.00
CORE_RETAIL 2855.33 5904.67 0.00 0.00 0.00
POINT_OF_SALE 8557.67 202.33 0.00 0.00 0.00
FRONT_RETAIL 8185.50 574.50 0.00 0.00 0.00
FRONT_ENTRY 1.83 4667.50 3690.33 400.33 0.00
Min 1.83 149.83 0.00 0.00 0.00
Max 8610.17 5904.67 3690.33 400.33 0.00
Average 5642.10 2299.77 738.07 80.07 0.00
Sum 28210.50 11498.83 3690.33 400.33 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BACK_SPACE 16478.00 394.00 0.00 0.00 0.00
CORE_RETAIL 384686.33 224912.67 0.00 0.00 0.00
POINT_OF_SALE 54977.67 1022.33 0.00 0.00 0.00
FRONT_RETAIL 51885.83 4114.17 0.00 0.00 0.00
FRONT_ENTRY 0.00 556.17 1067.50 296.33 0.00
Min 0.00 394.00 0.00 0.00 0.00
Max 384686.33 224912.67 1067.50 296.33 0.00
Average 101605.57 46199.87 213.50 59.27 0.00
Sum 508027.83 230999.33 1067.50 296.33 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:19:52

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BACK_SPACE 0.00 0.00 0.00 0.00
CORE_RETAIL 0.00 0.00 0.00 8760.00
POINT_OF_SALE 0.00 0.00 0.00 0.00
FRONT_RETAIL 0.00 0.00 0.00 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 8760.00
Average 0.00 0.00 0.00 1752.00
Sum 0.00 0.00 0.00 8760.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BACK_SPACE 0.00 0.00 0.00 0.00
CORE_RETAIL 0.00 0.00 0.00 609599.00
POINT_OF_SALE 0.00 0.00 0.00 0.00
FRONT_RETAIL 0.00 0.00 0.00 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 609599.00
Average 0.00 0.00 0.00 121919.80
Sum 0.00 0.00 0.00 609599.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.183252E+11 29428.92 15-JAN-19:08 26.75 20.93 0.291188E+09 326.82 07-JAN-12:09 26.75 20.93
February 0.190822E+11 30270.72 24-FEB-21:07 27.38 21.32 0.265893E+09 326.83 14-FEB-15:39 27.38 21.32
March 0.233457E+11 30502.32 03-MAR-02:23 24.00 20.62 0.304129E+09 326.84 20-MAR-14:09 35.00 23.49
April 0.250058E+11 29131.52 22-APR-00:43 24.17 23.00 0.287508E+09 326.83 22-APR-13:09 33.67 25.67
May 0.278267E+11 29466.54 11-MAY-01:23 24.10 24.04 0.297653E+09 326.83 22-MAY-14:09 27.17 26.37
June 0.307643E+11 29841.18 01-JUN-01:23 23.70 23.52 0.293536E+09 326.85 13-JUN-14:39 36.00 28.43
July 0.259808E+11 30565.53 19-JUL-22:43 23.48 22.50 0.291627E+09 326.83 08-JUL-15:20 23.48 22.50
August 0.231889E+11 29736.02 24-AUG-02:63 23.17 23.17 0.304126E+09 326.83 30-AUG-14:39 29.33 26.36
September 0.215937E+11 28952.19 09-SEP-04:03 24.00 23.47 0.287508E+09 326.83 23-SEP-13:00 31.00 26.41
October 0.186475E+11 28897.77 09-OCT-04:43 23.77 23.44 0.291186E+09 326.83 03-OCT-14:30 23.77 23.44
November 0.182006E+11 28460.67 02-NOV-01:23 24.25 22.67 0.280158E+09 326.83 04-NOV-15:09 30.47 25.45
December 0.173897E+11 30689.25 20-DEC-21:10 22.83 18.43 0.291629E+09 326.82 16-DEC-13:39 22.83 18.43
                     
Annual Sum or Average 0.269351E+12         0.348614E+10        
Minimum of Months 0.173897E+11 28460.67   22.83 18.43 0.265893E+09 326.82   22.83 18.43
Maximum of Months 0.307643E+11 30689.25   27.38 24.04 0.304129E+09 326.85   36.00 28.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.557240E+11 117982.49 28-JAN-07:03 20.42 18.64 0.920516E+10 10328.07 31-JAN-15:20 32.03 22.46
February 0.550081E+11 126127.82 24-FEB-07:02 21.42 18.05 0.840583E+10 10328.10 24-FEB-15:50 34.33 21.12
March 0.659066E+11 122022.09 21-MAR-05:03 24.83 22.06 0.961457E+10 10327.99 01-MAR-15:30 24.83 22.06
April 0.646465E+11 116288.46 27-APR-05:03 26.00 23.88 0.908925E+10 10327.91 22-APR-10:09 26.00 23.88
May 0.635716E+11 109142.33 31-MAY-05:03 24.17 24.17 0.941000E+10 10327.75 17-MAY-14:09 24.17 24.17
June 0.647131E+11 110302.87 01-JUN-05:03 24.00 24.00 0.927977E+10 10327.48 30-JUN-14:20 27.67 26.17
July 0.584758E+11 115013.81 31-JUL-05:03 24.15 23.23 0.921952E+10 10327.99 08-JUL-12:09 24.15 23.23
August 0.589599E+11 108590.72 16-AUG-05:03 24.00 24.00 0.961446E+10 10327.93 29-AUG-14:09 25.05 23.86
September 0.577809E+11 111212.61 13-SEP-05:03 24.17 24.04 0.908922E+10 10327.82 16-SEP-14:20 26.00 24.74
October 0.539131E+11 103975.68 05-OCT-05:03 26.08 25.24 0.920545E+10 10327.94 30-OCT-14:00 23.50 23.13
November 0.531803E+11 115287.87 25-NOV-07:03 21.17 18.84 0.885682E+10 10328.01 28-NOV-15:00 28.70 24.63
December 0.541185E+11 113560.88 27-DEC-07:03 20.50 19.41 0.921915E+10 10328.05 05-DEC-15:50 20.50 19.41
                     
Annual Sum or Average 0.705999E+12         0.110209E+12        
Minimum of Months 0.531803E+11 103975.68   20.42 18.05 0.840583E+10 10327.48   20.50 19.41
Maximum of Months 0.659066E+11 126127.82   26.08 25.24 0.961457E+10 10328.10   34.33 26.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.177528E+11 19314.31 16-JAN-19:05 26.33 21.46 0.867054E+09 973.27 23-JAN-15:09 30.50 21.05
February 0.164691E+11 19507.63 24-FEB-21:05 27.38 21.32 0.791730E+09 973.27 25-FEB-12:09 29.43 21.54
March 0.171395E+11 18377.51 02-MAR-21:06 26.83 21.46 0.905584E+09 973.25 04-MAR-12:00 33.30 22.16
April 0.151776E+11 17737.71 22-APR-00:03 24.03 23.21 0.856096E+09 973.21 15-APR-10:30 24.03 23.21
May 0.153328E+11 17663.59 11-MAY-02:63 24.00 24.00 0.886311E+09 973.17 17-MAY-14:00 29.00 26.74
June 0.152937E+11 17615.75 21-JUN-02:63 23.17 23.17 0.874048E+09 973.16 30-JUN-14:39 28.33 26.82
July 0.141433E+11 17995.00 19-JUL-23:23 23.60 22.55 0.868371E+09 973.24 12-JUL-14:09 23.60 22.55
August 0.139247E+11 17837.69 24-AUG-00:43 24.00 23.26 0.905585E+09 973.23 19-AUG-11:39 24.00 23.26
September 0.144322E+11 17709.29 29-SEP-02:63 24.42 23.35 0.856098E+09 973.23 16-SEP-12:09 24.42 23.35
October 0.147369E+11 17941.50 08-OCT-01:43 24.08 23.28 0.867047E+09 973.23 21-OCT-10:30 29.10 24.92
November 0.159475E+11 18799.37 25-NOV-00:23 23.80 20.43 0.834207E+09 973.25 25-NOV-14:50 25.95 22.31
December 0.173721E+11 20008.94 20-DEC-21:08 22.83 18.43 0.868368E+09 973.24 19-DEC-15:50 22.83 18.43
                     
Annual Sum or Average 0.187722E+12         0.103805E+11        
Minimum of Months 0.139247E+11 17615.75   22.83 18.43 0.791730E+09 973.16   22.83 18.43
Maximum of Months 0.177528E+11 20008.94   27.38 24.00 0.905585E+09 973.27   33.30 26.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.147396E+11 16493.34 07-JAN-03:03 22.45 21.41 0.867051E+09 973.25 23-JAN-15:50 30.50 21.05
February 0.137497E+11 16652.08 20-FEB-22:23 27.15 20.34 0.791727E+09 973.23 25-FEB-12:09 29.43 21.54
March 0.139755E+11 15535.55 02-MAR-01:43 24.05 22.65 0.905581E+09 973.24 04-MAR-12:00 33.30 22.16
April 0.122578E+11 14838.37 22-APR-00:03 24.03 23.21 0.856096E+09 973.21 14-APR-14:20 24.03 23.21
May 0.123927E+11 14880.95 11-MAY-02:63 24.00 24.00 0.886312E+09 973.15 25-MAY-14:00 25.00 25.00
June 0.124497E+11 14945.49 20-JUN-04:03 24.08 23.67 0.874053E+09 973.15 30-JUN-14:00 29.00 27.47
July 0.112343E+11 15414.26 02-JUL-23:23 25.90 22.58 0.868366E+09 973.21 08-JUL-13:30 30.80 24.14
August 0.109543E+11 15038.78 24-AUG-00:43 24.00 23.26 0.905586E+09 973.21 29-AUG-14:09 25.05 23.86
September 0.116002E+11 15045.95 29-SEP-02:63 24.42 23.35 0.856100E+09 973.18 16-SEP-14:09 24.42 23.35
October 0.117099E+11 15344.55 09-OCT-04:03 24.03 23.37 0.867046E+09 973.21 21-OCT-10:39 29.40 25.11
November 0.130667E+11 16451.16 25-NOV-00:23 23.80 20.43 0.834203E+09 973.22 25-NOV-14:50 25.95 22.31
December 0.143770E+11 17033.16 20-DEC-21:08 22.83 18.43 0.868364E+09 973.20 23-DEC-11:00 29.00 24.59
                     
Annual Sum or Average 0.152507E+12         0.103805E+11        
Minimum of Months 0.109543E+11 14838.37   22.45 18.43 0.791727E+09 973.15   24.03 21.05
Maximum of Months 0.147396E+11 17033.16   27.15 24.00 0.905586E+09 973.25   33.30 27.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 25.03 23.60 0.112990E+09 166.23 05-JAN-15:09 33.73 23.23
February 0.00 0.00 01-FEB-00:10 26.43 22.46 0.109214E+09 175.24 28-FEB-15:09 34.60 24.66
March 0.00 0.00 01-MAR-00:10 25.93 22.97 0.128196E+09 184.14 21-MAR-14:09 35.67 23.99
April 0.00 0.00 01-APR-00:03 27.53 25.10 0.122202E+09 177.84 01-APR-14:09 35.42 26.93
May 0.00 0.00 01-MAY-00:03 28.62 26.40 0.125320E+09 186.05 06-MAY-11:50 36.83 25.90
June 0.00 0.00 01-JUN-00:03 24.05 23.91 0.124403E+09 183.38 13-JUN-14:00 36.00 28.43
July 0.00 0.00 01-JUL-00:05 25.40 24.33 0.108307E+09 155.71 15-JUL-15:00 33.20 25.63
August 0.00 0.00 01-AUG-00:03 25.63 24.75 0.114227E+09 162.88 10-AUG-14:09 33.50 27.78
September 0.00 0.00 01-SEP-00:03 26.53 25.66 0.109288E+09 163.55 06-SEP-14:09 33.83 26.60
October 0.00 0.00 01-OCT-00:10 26.27 25.35 0.105524E+09 154.93 04-OCT-14:09 32.92 26.22
November 0.00 0.00 01-NOV-00:05 25.22 24.37 0.103214E+09 167.52 18-NOV-13:09 33.75 25.30
December 0.00 0.00 01-DEC-00:10 23.80 23.43 0.109335E+09 157.09 07-DEC-15:09 32.63 22.66
                     
Annual Sum or Average 0.00         0.137222E+10        
Minimum of Months 0.00 0.00   23.80 22.46 0.103214E+09 154.93   32.63 22.66
Maximum of Months 0.00 0.00   28.62 26.40 0.128196E+09 186.05   36.83 28.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 286505.92 992.32 29-JAN-08:04 24.17
February 1112483.31 1801.49 19-FEB-08:07 26.17
March 1627252.88 2035.88 26-MAR-07:07 27.17
April 2333932.12 2112.60 30-APR-07:05 28.10
May 832645.39 1397.55 18-MAY-05:05 24.00
June 801496.70 2181.46 18-JUN-07:08 28.00
July 1192434.79 1902.66 01-JUL-05:05 25.88
August 3321603.39 1949.13 18-AUG-05:05 25.83
September 1178481.21 1961.96 03-SEP-07:05 27.58
October 1700634.16 1900.34 29-OCT-07:07 26.50
November 859544.42 1577.04 19-NOV-08:07 25.50
December 785009.23 1125.92 18-DEC-06:05 23.07
         
Annual Sum or Average 16032023.52      
Minimum of Months 286505.92 992.32   23.07
Maximum of Months 3321603.39 2181.46   28.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 66154052.45 10005.49 16-JAN-09:06 25.32
February 0.104299E+09 9157.48 16-FEB-07:08 25.50
March 0.208021E+09 12755.35 28-MAR-06:08 27.03
April 0.250927E+09 17211.14 09-APR-08:08 28.98
May 0.240956E+09 21846.27 28-MAY-07:05 32.25
June 0.227074E+09 13926.78 25-JUN-08:08 27.33
July 0.220862E+09 13039.20 02-JUL-08:08 27.17
August 0.249302E+09 16006.30 06-AUG-08:08 28.33
September 0.247199E+09 15852.95 04-SEP-08:08 28.33
October 0.238300E+09 15937.68 29-OCT-08:08 28.33
November 0.171854E+09 15491.49 11-NOV-09:08 28.23
December 83401645.98 15615.62 10-DEC-09:08 28.20
         
Annual Sum or Average 0.230835E+10      
Minimum of Months 66154052.45 9157.48   25.32
Maximum of Months 0.250927E+09 21846.27   32.25



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 281081.82 703.79 29-JAN-08:04 24.17
February 765511.96 1303.08 19-FEB-08:07 26.17
March 570932.03 1497.16 26-MAR-07:07 27.17
April 980235.80 1392.07 16-APR-07:07 26.78
May 509512.54 1529.34 14-MAY-07:07 27.50
June 201509.92 671.70 25-JUN-07:10 25.75
July 434107.58 1184.73 30-JUL-07:07 25.83
August 1378744.38 1560.58 13-AUG-07:07 27.67
September 424307.03 1326.78 10-SEP-07:07 26.50
October 1533364.84 1308.57 29-OCT-07:07 26.50
November 360745.41 1167.90 19-NOV-08:07 25.50
December 312797.32 775.73 03-DEC-08:04 24.50
         
Annual Sum or Average 7752850.64      
Minimum of Months 201509.92 671.70   24.17
Maximum of Months 1533364.84 1560.58   27.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 223002.45 585.69 29-JAN-08:04 24.17
February 653061.52 1141.77 19-FEB-08:07 26.17
March 506558.59 1337.97 26-MAR-07:07 27.17
April 911868.70 1234.84 16-APR-07:07 26.78
May 435225.04 1389.26 14-MAY-07:07 27.50
June 245624.76 818.75 25-JUN-07:10 25.75
July 374318.38 1035.88 30-JUL-07:07 25.83
August 999147.40 1390.64 13-AUG-07:07 27.67
September 390879.20 1173.73 10-SEP-07:07 26.50
October 1459288.80 1081.44 29-OCT-07:07 26.50
November 301702.13 1005.61 19-NOV-08:07 25.50
December 257838.51 659.90 03-DEC-08:04 24.50
         
Annual Sum or Average 6758515.48      
Minimum of Months 223002.45 585.69   24.17
Maximum of Months 1459288.80 1390.64   27.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:03 27.53
May 0.00 0.00 01-MAY-00:03 28.62
June 0.00 0.00 01-JUN-00:03 24.05
July 0.00 0.00 01-JUL-00:05 25.40
August 0.00 0.00 01-AUG-00:03 25.63
September 0.00 0.00 01-SEP-00:03 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:05 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.906964E+09 742.55 02-JAN-09:09 0.419292E+10 2751.42 02-JAN-09:09
February 0.826011E+09 742.55 01-FEB-09:09 0.380401E+10 2751.42 01-FEB-09:09
March 0.943673E+09 742.55 01-MAR-09:09 0.429860E+10 2751.42 01-MAR-09:09
April 0.889382E+09 742.55 01-APR-09:09 0.408537E+10 2751.42 01-APR-09:09
May 0.924906E+09 742.55 01-MAY-08:09 0.424576E+10 2751.42 01-MAY-08:09
June 0.910287E+09 742.55 01-JUN-08:09 0.415080E+10 2751.42 01-JUN-08:09
July 0.904343E+09 742.55 01-JUL-09:09 0.417978E+10 2751.42 01-JUL-09:09
August 0.943527E+09 742.55 01-AUG-08:09 0.429860E+10 2751.42 01-AUG-08:09
September 0.889382E+09 742.55 01-SEP-08:09 0.408428E+10 2751.42 01-SEP-08:09
October 0.907110E+09 742.55 02-OCT-08:09 0.419346E+10 2751.42 02-OCT-08:09
November 0.879167E+09 742.55 01-NOV-08:09 0.405935E+10 2751.42 01-NOV-08:09
December 0.904973E+09 742.55 01-DEC-09:09 0.417924E+10 2751.42 01-DEC-09:09
             
Annual Sum or Average 0.108297E+11     0.497722E+11    
Minimum of Months 0.826011E+09 742.55   0.380401E+10 2751.42  
Maximum of Months 0.943673E+09 742.55   0.429860E+10 2751.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.134546E+11 16279.92 02-JAN-17:40 0.707031E+10 4639.58 02-JAN-09:09
February 0.118847E+11 16279.92 01-FEB-17:00 0.641452E+10 4639.58 01-FEB-09:09
March 0.134860E+11 16279.92 01-MAR-17:00 0.724851E+10 4639.58 01-MAR-09:09
April 0.125520E+11 14875.90 20-APR-16:00 0.688896E+10 4639.58 01-APR-09:09
May 0.129527E+11 15095.16 22-MAY-16:00 0.715941E+10 4639.58 01-MAY-08:09
June 0.122638E+11 15009.01 03-JUN-16:00 0.699930E+10 4639.58 01-JUN-08:09
July 0.124926E+11 15080.09 17-JUL-16:00 0.704816E+10 4639.58 01-JUL-09:09
August 0.130527E+11 15029.10 24-AUG-16:00 0.724851E+10 4639.58 01-AUG-08:09
September 0.124526E+11 15281.86 26-SEP-16:00 0.688712E+10 4639.58 01-SEP-08:09
October 0.126890E+11 15731.39 30-OCT-16:00 0.707123E+10 4639.58 02-OCT-08:09
November 0.129755E+11 16279.92 06-NOV-17:30 0.684509E+10 4639.58 01-NOV-08:09
December 0.136266E+11 16279.92 01-DEC-17:30 0.704724E+10 4639.58 01-DEC-09:09
             
Annual Sum or Average 0.153883E+12     0.839284E+11    
Minimum of Months 0.118847E+11 14875.90   0.641452E+10 4639.58  
Maximum of Months 0.136266E+11 16279.92   0.724851E+10 4639.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.174880E+10 1534.02 02-JAN-09:09 0.443872E+10 2912.71 02-JAN-09:09
February 0.159209E+10 1534.02 01-FEB-09:09 0.402701E+10 2912.71 01-FEB-09:09
March 0.181792E+10 1534.02 01-MAR-09:09 0.455059E+10 2912.71 01-MAR-09:09
April 0.171452E+10 1534.02 01-APR-09:09 0.432486E+10 2912.71 01-APR-09:09
May 0.178336E+10 1534.02 01-MAY-08:09 0.449465E+10 2912.71 01-MAY-08:09
June 0.175416E+10 1534.02 01-JUN-08:09 0.439413E+10 2912.71 01-JUN-08:09
July 0.174372E+10 1534.02 01-JUL-09:09 0.442481E+10 2912.71 01-JUL-09:09
August 0.181792E+10 1534.02 01-AUG-08:09 0.455059E+10 2912.71 01-AUG-08:09
September 0.171452E+10 1534.02 01-SEP-08:09 0.432371E+10 2912.71 01-SEP-08:09
October 0.174880E+10 1534.02 02-OCT-08:09 0.443929E+10 2912.71 02-OCT-08:09
November 0.169012E+10 1534.02 01-NOV-08:09 0.429732E+10 2912.71 01-NOV-08:09
December 0.174372E+10 1534.02 01-DEC-09:09 0.442423E+10 2912.71 01-DEC-09:09
             
Annual Sum or Average 0.208697E+11     0.526899E+11    
Minimum of Months 0.159209E+10 1534.02   0.402701E+10 2912.71  
Maximum of Months 0.181792E+10 1534.02   0.455059E+10 2912.71  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.174880E+10 1534.02 02-JAN-09:09 0.666220E+09 437.18 02-JAN-09:09
February 0.159209E+10 1534.02 01-FEB-09:09 0.604426E+09 437.18 01-FEB-09:09
March 0.181792E+10 1534.02 01-MAR-09:09 0.683011E+09 437.18 01-MAR-09:09
April 0.171452E+10 1534.02 01-APR-09:09 0.649132E+09 437.18 01-APR-09:09
May 0.178336E+10 1534.02 01-MAY-08:09 0.674616E+09 437.18 01-MAY-08:09
June 0.175416E+10 1534.02 01-JUN-08:09 0.659528E+09 437.18 01-JUN-08:09
July 0.174372E+10 1534.02 01-JUL-09:09 0.664132E+09 437.18 01-JUL-09:09
August 0.181792E+10 1534.02 01-AUG-08:09 0.683011E+09 437.18 01-AUG-08:09
September 0.171452E+10 1534.02 01-SEP-08:09 0.648959E+09 437.18 01-SEP-08:09
October 0.174880E+10 1534.02 02-OCT-08:09 0.666307E+09 437.18 02-OCT-08:09
November 0.169012E+10 1534.02 01-NOV-08:09 0.644998E+09 437.18 01-NOV-08:09
December 0.174372E+10 1534.02 01-DEC-09:09 0.664046E+09 437.18 01-DEC-09:09
             
Annual Sum or Average 0.208697E+11     0.790839E+10    
Minimum of Months 0.159209E+10 1534.02   0.604426E+09 437.18  
Maximum of Months 0.181792E+10 1534.02   0.683011E+09 437.18  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 52953287.74 44.76 02-JAN-09:09 0.00 0.00
February 48182266.45 44.76 01-FEB-09:09 0.00 0.00
March 54927912.53 44.76 01-MAR-09:09 0.00 0.00
April 51865380.39 44.76 01-APR-09:09 0.00 0.00
May 53941762.61 44.76 01-MAY-08:09 0.00 0.00
June 53008506.70 44.76 01-JUN-08:09 0.00 0.00
July 52802317.57 44.76 01-JUL-09:09 0.00 0.00
August 54927563.77 44.76 01-AUG-08:09 0.00 0.00
September 51865380.39 44.76 01-SEP-08:09 0.00 0.00
October 52953636.50 44.76 02-OCT-08:09 0.00 0.00
November 51191943.51 44.76 01-NOV-08:09 0.00 0.00
December 52796660.11 44.76 01-DEC-09:09 0.00 0.00
           
Annual Sum or Average 0.631417E+09     0.00 0.00
Minimum of Months 48182266.45 44.76   0.00 0.00
Maximum of Months 54927912.53 44.76   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.699524E+09 0.906964E+09 0.419292E+10 0.00 0.00 0.00 0.00 55406685.73 13199397.42
February 0.638757E+09 0.826011E+09 0.380401E+10 0.00 0.00 0.00 0.00 75016726.64 697332.28
March 0.730614E+09 0.943673E+09 0.429860E+10 0.00 0.00 0.00 0.00 0.146172E+09 1399758.80
April 0.690691E+09 0.889382E+09 0.408537E+10 0.00 0.00 0.00 0.00 0.147475E+09 54120.88
May 0.715069E+09 0.924906E+09 0.424576E+10 0.00 0.00 0.00 0.00 0.158882E+09 533437.04
June 0.705176E+09 0.910287E+09 0.415080E+10 0.00 0.00 0.00 0.00 0.144915E+09 1165781.75
July 0.700584E+09 0.904343E+09 0.417978E+10 0.00 0.00 0.00 0.00 79303152.87 614349.90
August 0.730614E+09 0.943527E+09 0.429860E+10 0.00 0.00 0.00 0.00 0.106361E+09 1131310.79
September 0.690691E+09 0.889382E+09 0.408428E+10 0.00 0.00 0.00 0.00 75049924.81 619905.34
October 0.699524E+09 0.907110E+09 0.419346E+10 0.00 0.00 0.00 0.00 58888168.32 919360.09
November 0.673027E+09 0.879167E+09 0.405935E+10 0.00 0.00 0.00 0.00 46394461.11 3781531.78
December 0.700584E+09 0.904973E+09 0.417924E+10 0.00 0.00 0.00 0.00 38206086.81 18476084.11
                   
Annual Sum or Average 0.837485E+10 0.108297E+11 0.497722E+11 0.00 0.00 0.00 0.00 0.113207E+10 42592370.18
Minimum of Months 0.638757E+09 0.826011E+09 0.380401E+10 0.00 0.00 0.00 0.00 38206086.81 54120.88
Maximum of Months 0.730614E+09 0.943673E+09 0.429860E+10 0.00 0.00 0.00 0.00 0.158882E+09 18476084.11



Table of Contents

Report: SpaceGainsMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.221054E+11 0.134546E+11 0.707031E+10 0.00 0.00 0.00 0.00 37091434.85 31060897.70
February 0.201852E+11 0.118847E+11 0.641452E+10 0.00 0.00 0.00 0.00 48826217.36 9780881.23
March 0.230879E+11 0.134860E+11 0.724851E+10 0.00 0.00 0.00 0.00 80456597.97 19164802.26
April 0.218263E+11 0.125520E+11 0.688896E+10 0.00 0.00 0.00 0.00 80973249.14 2813542.11
May 0.225967E+11 0.129527E+11 0.715941E+10 0.00 0.00 0.00 0.00 95097937.17 8013349.28
June 0.222841E+11 0.122638E+11 0.699930E+10 0.00 0.00 0.00 0.00 82941945.65 8500863.70
July 0.221389E+11 0.124926E+11 0.704816E+10 0.00 0.00 0.00 0.00 52227689.89 7994444.19
August 0.230879E+11 0.130527E+11 0.724851E+10 0.00 0.00 0.00 0.00 62841325.49 13016929.43
September 0.218263E+11 0.124526E+11 0.688712E+10 0.00 0.00 0.00 0.00 46030677.97 7725681.54
October 0.221054E+11 0.126890E+11 0.707123E+10 0.00 0.00 0.00 0.00 37528582.01 12202663.04
November 0.212681E+11 0.129755E+11 0.684509E+10 0.00 0.00 0.00 0.00 29872273.22 16093307.42
December 0.221389E+11 0.136266E+11 0.704724E+10 0.00 0.00 0.00 0.00 28503720.76 35216330.70
                   
Annual Sum or Average 0.264651E+12 0.153883E+12 0.839284E+11 0.00 0.00 0.00 0.00 0.682392E+09 0.171584E+09
Minimum of Months 0.201852E+11 0.118847E+11 0.641452E+10 0.00 0.00 0.00 0.00 28503720.76 2813542.11
Maximum of Months 0.230879E+11 0.136266E+11 0.724851E+10 0.00 0.00 0.00 0.00 95097937.17 35216330.70



Table of Contents

Report: SpaceGainsMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.208295E+10 0.174880E+10 0.443872E+10 0.00 0.00 0.00 0.00 24794891.85 6531022.50
February 0.190200E+10 0.159209E+10 0.402701E+10 0.00 0.00 0.00 0.00 33626453.33 479411.64
March 0.217552E+10 0.181792E+10 0.455059E+10 0.00 0.00 0.00 0.00 65638149.89 785499.60
April 0.205665E+10 0.171452E+10 0.432486E+10 0.00 0.00 0.00 0.00 66839678.60 31765.81
May 0.212923E+10 0.178336E+10 0.449465E+10 0.00 0.00 0.00 0.00 72389403.07 260019.30
June 0.209978E+10 0.175416E+10 0.439413E+10 0.00 0.00 0.00 0.00 66329968.32 515579.87
July 0.208610E+10 0.174372E+10 0.442481E+10 0.00 0.00 0.00 0.00 36226894.87 285312.18
August 0.217552E+10 0.181792E+10 0.455059E+10 0.00 0.00 0.00 0.00 48398987.99 538259.19
September 0.205665E+10 0.171452E+10 0.432371E+10 0.00 0.00 0.00 0.00 33962922.52 318120.11
October 0.208295E+10 0.174880E+10 0.443929E+10 0.00 0.00 0.00 0.00 26540515.39 526464.95
November 0.200405E+10 0.169012E+10 0.429732E+10 0.00 0.00 0.00 0.00 20842651.23 1945729.62
December 0.208610E+10 0.174372E+10 0.442423E+10 0.00 0.00 0.00 0.00 17200529.83 8970722.76
                   
Annual Sum or Average 0.249375E+11 0.208697E+11 0.526899E+11 0.00 0.00 0.00 0.00 0.512791E+09 21187907.54
Minimum of Months 0.190200E+10 0.159209E+10 0.402701E+10 0.00 0.00 0.00 0.00 17200529.83 31765.81
Maximum of Months 0.217552E+10 0.181792E+10 0.455059E+10 0.00 0.00 0.00 0.00 72389403.07 8970722.76



Table of Contents

Report: SpaceGainsMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.208295E+10 0.174880E+10 0.666220E+09 0.00 0.00 0.00 0.00 24910209.17 6359947.21
February 0.190200E+10 0.159209E+10 0.604426E+09 0.00 0.00 0.00 0.00 33782738.57 411711.75
March 0.217552E+10 0.181792E+10 0.683011E+09 0.00 0.00 0.00 0.00 66107505.91 709630.13
April 0.205665E+10 0.171452E+10 0.649132E+09 0.00 0.00 0.00 0.00 67237199.02 23824.10
May 0.212923E+10 0.178336E+10 0.674616E+09 0.00 0.00 0.00 0.00 72726452.71 225076.27
June 0.209978E+10 0.175416E+10 0.659528E+09 0.00 0.00 0.00 0.00 66665095.88 479145.87
July 0.208610E+10 0.174372E+10 0.664132E+09 0.00 0.00 0.00 0.00 36370393.96 247729.17
August 0.217552E+10 0.181792E+10 0.683011E+09 0.00 0.00 0.00 0.00 48666390.60 512994.21
September 0.205665E+10 0.171452E+10 0.648959E+09 0.00 0.00 0.00 0.00 34128035.99 291236.96
October 0.208295E+10 0.174880E+10 0.666307E+09 0.00 0.00 0.00 0.00 26659236.43 473642.94
November 0.200405E+10 0.169012E+10 0.644998E+09 0.00 0.00 0.00 0.00 20938048.75 1855422.28
December 0.208610E+10 0.174372E+10 0.664046E+09 0.00 0.00 0.00 0.00 17241311.59 8786398.72
                   
Annual Sum or Average 0.249375E+11 0.208697E+11 0.790839E+10 0.00 0.00 0.00 0.00 0.515433E+09 20376759.62
Minimum of Months 0.190200E+10 0.159209E+10 0.604426E+09 0.00 0.00 0.00 0.00 17241311.59 23824.10
Maximum of Months 0.217552E+10 0.181792E+10 0.683011E+09 0.00 0.00 0.00 0.00 72726452.71 8786398.72



Table of Contents

Report: SpaceGainsMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.165769E+09 52953287.74 0.00 0.00 0.00 0.00 0.00 34406796.98 0.231498E+09
February 0.151369E+09 48182266.45 0.00 0.00 0.00 0.00 0.00 98084730.50 0.122204E+09
March 0.173136E+09 54927912.53 0.00 0.00 0.00 0.00 0.00 0.285302E+09 64826946.24
April 0.163676E+09 51865380.39 0.00 0.00 0.00 0.00 0.00 0.396931E+09 20455676.55
May 0.169453E+09 53941762.61 0.00 0.00 0.00 0.00 0.00 0.441112E+09 49367157.72
June 0.167108E+09 53008506.70 0.00 0.00 0.00 0.00 0.00 0.402694E+09 40922817.67
July 0.166020E+09 52802317.57 0.00 0.00 0.00 0.00 0.00 0.198340E+09 88922477.50
August 0.173136E+09 54927563.77 0.00 0.00 0.00 0.00 0.00 0.252305E+09 82207238.89
September 0.163676E+09 51865380.39 0.00 0.00 0.00 0.00 0.00 0.184931E+09 88660499.31
October 0.165769E+09 52953636.50 0.00 0.00 0.00 0.00 0.00 76278548.04 0.127615E+09
November 0.159490E+09 51191943.51 0.00 0.00 0.00 0.00 0.00 29089389.07 0.207596E+09
December 0.166020E+09 52796660.11 0.00 0.00 0.00 0.00 0.00 14228097.72 0.261287E+09
                   
Annual Sum or Average 0.198462E+10 0.631417E+09 0.00 0.00 0.00 0.00 0.00 0.241370E+10 0.138556E+10
Minimum of Months 0.151369E+09 48182266.45 0.00 0.00 0.00 0.00 0.00 14228097.72 20455676.55
Maximum of Months 0.173136E+09 54927912.53 0.00 0.00 0.00 0.00 0.00 0.441112E+09 0.261287E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 785.10 02-JAN-15:09 742.55 02-JAN-09:09 2751.42 02-JAN-09:09 0.00 0.00 0.00 0.00 155.70 08-JAN-19:10 377.77 07-JAN-05:00
February 785.10 01-FEB-15:09 742.55 01-FEB-09:09 2751.42 01-FEB-09:09 0.00 0.00 0.00 0.00 200.35 20-FEB-19:10 24.81 26-FEB-06:40
March 785.10 01-MAR-15:09 742.55 01-MAR-09:09 2751.42 01-MAR-09:09 0.00 0.00 0.00 0.00 435.92 19-MAR-18:10 66.14 03-MAR-05:40
April 785.10 01-APR-10:09 742.55 01-APR-09:09 2751.42 01-APR-09:09 0.00 0.00 0.00 0.00 269.42 02-APR-19:00 16.83 22-APR-02:40
May 785.10 01-MAY-14:09 742.55 01-MAY-08:09 2751.42 01-MAY-08:09 0.00 0.00 0.00 0.00 343.66 07-MAY-18:10 129.17 08-MAY-22:00
June 785.10 01-JUN-14:09 742.55 01-JUN-08:09 2751.42 01-JUN-08:09 0.00 0.00 0.00 0.00 323.32 11-JUN-19:00 113.08 20-JUN-23:20
July 785.10 01-JUL-10:09 742.55 01-JUL-09:09 2751.42 01-JUL-09:09 0.00 0.00 0.00 0.00 177.82 25-JUL-21:00 72.01 19-JUL-20:40
August 785.10 01-AUG-14:09 742.55 01-AUG-08:09 2751.42 01-AUG-08:09 0.00 0.00 0.00 0.00 259.66 01-AUG-21:00 87.26 23-AUG-20:05
September 785.10 01-SEP-14:09 742.55 01-SEP-08:09 2751.42 01-SEP-08:09 0.00 0.00 0.00 0.00 153.32 10-SEP-15:00 58.36 15-SEP-22:15
October 785.10 02-OCT-14:09 742.55 02-OCT-08:09 2751.42 02-OCT-08:09 0.00 0.00 0.00 0.00 220.95 08-OCT-18:10 41.43 23-OCT-04:40
November 785.10 01-NOV-14:09 742.55 01-NOV-08:09 2751.42 01-NOV-08:09 0.00 0.00 0.00 0.00 93.19 02-NOV-21:52 78.21 25-NOV-05:00
December 785.10 01-DEC-15:09 742.55 01-DEC-09:09 2751.42 01-DEC-09:09 0.00 0.00 0.00 0.00 104.91 09-DEC-14:00 160.01 21-DEC-04:40
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 785.10   742.55   2751.42   0.00 0.00 0.00 0.00 93.19   16.83  
Maximum of Months 785.10   742.55   2751.42   0.00 0.00 0.00 0.00 435.92   377.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 24809.68 02-JAN-15:09 16279.92 02-JAN-17:40 4639.58 02-JAN-09:09 0.00 0.00 0.00 0.00 130.32 08-JAN-19:02 534.35 07-JAN-04:53
February 24809.68 01-FEB-15:09 16279.92 01-FEB-17:00 4639.58 01-FEB-09:09 0.00 0.00 0.00 0.00 167.17 20-FEB-19:02 52.31 20-FEB-07:00
March 24809.68 01-MAR-15:09 16279.92 01-MAR-17:00 4639.58 01-MAR-09:09 0.00 0.00 0.00 0.00 362.67 19-MAR-18:02 101.12 14-MAR-22:00
April 24809.68 01-APR-10:09 14875.90 20-APR-16:00 4639.58 01-APR-09:09 0.00 0.00 0.00 0.00 216.71 02-APR-18:02 45.03 13-APR-05:00
May 24809.68 01-MAY-14:09 15095.16 22-MAY-16:00 4639.58 01-MAY-08:09 0.00 0.00 0.00 0.00 288.92 07-MAY-18:02 183.48 08-MAY-22:00
June 24809.68 01-JUN-14:09 15009.01 03-JUN-16:00 4639.58 01-JUN-08:09 0.00 0.00 0.00 0.00 267.75 11-JUN-18:02 204.45 20-JUN-23:00
July 24809.68 01-JUL-10:09 15080.09 17-JUL-16:00 4639.58 01-JUL-09:09 0.00 0.00 0.00 0.00 146.77 25-JUL-20:03 61.07 19-JUL-21:20
August 24809.68 01-AUG-14:09 15029.10 24-AUG-16:00 4639.58 01-AUG-08:09 0.00 0.00 0.00 0.00 185.45 01-AUG-20:02 115.17 04-AUG-03:00
September 24809.68 01-SEP-14:09 15281.86 26-SEP-16:00 4639.58 01-SEP-08:09 0.00 0.00 0.00 0.00 131.47 10-SEP-15:00 110.22 15-SEP-22:00
October 24809.68 02-OCT-14:09 15731.39 30-OCT-16:00 4639.58 02-OCT-08:09 0.00 0.00 0.00 0.00 183.02 08-OCT-18:02 62.72 23-OCT-23:00
November 24809.68 01-NOV-14:09 16279.92 06-NOV-17:30 4639.58 01-NOV-08:09 0.00 0.00 0.00 0.00 77.18 10-NOV-13:00 89.58 25-NOV-04:53
December 24809.68 01-DEC-15:09 16279.92 01-DEC-17:30 4639.58 01-DEC-09:09 0.00 0.00 0.00 0.00 89.96 09-DEC-14:00 171.58 21-DEC-04:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 24809.68   14875.90   4639.58   0.00 0.00 0.00 0.00 77.18   45.03  
Maximum of Months 24809.68   16279.92   4639.58   0.00 0.00 0.00 0.00 362.67   534.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2337.76 02-JAN-15:09 1534.02 02-JAN-09:09 2912.71 02-JAN-09:09 0.00 0.00 0.00 0.00 71.20 08-JAN-19:10 211.19 07-JAN-05:00
February 2337.76 01-FEB-15:09 1534.02 01-FEB-09:09 2912.71 01-FEB-09:09 0.00 0.00 0.00 0.00 90.87 20-FEB-19:10 16.89 24-FEB-01:00
March 2337.76 01-MAR-15:09 1534.02 01-MAR-09:09 2912.71 01-MAR-09:09 0.00 0.00 0.00 0.00 198.81 19-MAR-18:10 38.72 14-MAR-22:00
April 2337.76 01-APR-10:09 1534.02 01-APR-09:09 2912.71 01-APR-09:09 0.00 0.00 0.00 0.00 122.87 02-APR-19:00 9.64 22-APR-02:40
May 2337.76 01-MAY-14:09 1534.02 01-MAY-08:09 2912.71 01-MAY-08:09 0.00 0.00 0.00 0.00 157.83 07-MAY-18:10 64.65 08-MAY-22:00
June 2337.76 01-JUN-14:09 1534.02 01-JUN-08:09 2912.71 01-JUN-08:09 0.00 0.00 0.00 0.00 147.49 11-JUN-19:00 53.87 20-JUN-23:20
July 2337.76 01-JUL-10:09 1534.02 01-JUL-09:09 2912.71 01-JUL-09:09 0.00 0.00 0.00 0.00 81.10 25-JUL-21:00 32.81 19-JUL-20:40
August 2337.76 01-AUG-14:09 1534.02 01-AUG-08:09 2912.71 01-AUG-08:09 0.00 0.00 0.00 0.00 118.40 01-AUG-21:00 43.38 23-AUG-20:05
September 2337.76 01-SEP-14:09 1534.02 01-SEP-08:09 2912.71 01-SEP-08:09 0.00 0.00 0.00 0.00 69.92 10-SEP-15:00 34.53 15-SEP-22:00
October 2337.76 02-OCT-14:09 1534.02 02-OCT-08:09 2912.71 02-OCT-08:09 0.00 0.00 0.00 0.00 100.73 08-OCT-18:10 22.35 23-OCT-04:55
November 2337.76 01-NOV-14:09 1534.02 01-NOV-08:09 2912.71 01-NOV-08:09 0.00 0.00 0.00 0.00 42.26 02-NOV-20:10 39.13 25-NOV-05:00
December 2337.76 01-DEC-15:09 1534.02 01-DEC-09:09 2912.71 01-DEC-09:09 0.00 0.00 0.00 0.00 47.91 10-DEC-19:10 80.70 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2337.76   1534.02   2912.71   0.00 0.00 0.00 0.00 42.26   9.64  
Maximum of Months 2337.76   1534.02   2912.71   0.00 0.00 0.00 0.00 198.81   211.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2337.76 02-JAN-15:09 1534.02 02-JAN-09:09 437.18 02-JAN-09:09 0.00 0.00 0.00 0.00 71.22 08-JAN-19:10 199.86 07-JAN-05:00
February 2337.76 01-FEB-15:09 1534.02 01-FEB-09:09 437.18 01-FEB-09:09 0.00 0.00 0.00 0.00 90.87 20-FEB-19:10 14.84 24-FEB-01:00
March 2337.76 01-MAR-15:09 1534.02 01-MAR-09:09 437.18 01-MAR-09:09 0.00 0.00 0.00 0.00 198.80 19-MAR-18:10 34.90 14-MAR-22:00
April 2337.76 01-APR-10:09 1534.02 01-APR-09:09 437.18 01-APR-09:09 0.00 0.00 0.00 0.00 122.87 02-APR-19:00 7.54 22-APR-02:40
May 2337.76 01-MAY-14:09 1534.02 01-MAY-08:09 437.18 01-MAY-08:09 0.00 0.00 0.00 0.00 157.83 07-MAY-18:10 58.14 08-MAY-22:00
June 2337.76 01-JUN-14:09 1534.02 01-JUN-08:09 437.18 01-JUN-08:09 0.00 0.00 0.00 0.00 147.50 11-JUN-19:00 47.76 20-JUN-23:20
July 2337.76 01-JUL-10:09 1534.02 01-JUL-09:09 437.18 01-JUL-09:09 0.00 0.00 0.00 0.00 81.10 25-JUL-20:30 27.93 19-JUL-20:40
August 2337.76 01-AUG-14:09 1534.02 01-AUG-08:09 437.18 01-AUG-08:09 0.00 0.00 0.00 0.00 118.40 01-AUG-21:00 39.58 23-AUG-20:05
September 2337.76 01-SEP-14:09 1534.02 01-SEP-08:09 437.18 01-SEP-08:09 0.00 0.00 0.00 0.00 69.92 10-SEP-15:00 30.54 15-SEP-22:00
October 2337.76 02-OCT-14:09 1534.02 02-OCT-08:09 437.18 02-OCT-08:09 0.00 0.00 0.00 0.00 100.76 08-OCT-18:10 17.87 23-OCT-04:30
November 2337.76 01-NOV-14:09 1534.02 01-NOV-08:09 437.18 01-NOV-08:09 0.00 0.00 0.00 0.00 42.26 02-NOV-20:10 37.94 25-NOV-05:00
December 2337.76 01-DEC-15:09 1534.02 01-DEC-09:09 437.18 01-DEC-09:09 0.00 0.00 0.00 0.00 47.92 10-DEC-19:10 78.59 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2337.76   1534.02   437.18   0.00 0.00 0.00 0.00 42.26   7.54  
Maximum of Months 2337.76   1534.02   437.18   0.00 0.00 0.00 0.00 198.80   199.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 186.05 02-JAN-15:09 44.76 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 658.27 04-JAN-12:03 1546.93 24-JAN-08:61
February 186.05 01-FEB-15:09 44.76 01-FEB-09:09 0.00 0.00 0.00 0.00 0.00 1045.74 26-FEB-12:02 1124.03 21-FEB-09:53
March 186.05 01-MAR-15:09 44.76 01-MAR-09:09 0.00 0.00 0.00 0.00 0.00 2260.82 19-MAR-11:02 1291.24 14-MAR-11:02
April 186.05 01-APR-10:09 44.76 01-APR-09:09 0.00 0.00 0.00 0.00 0.00 1866.14 09-APR-11:02 1269.06 14-APR-15:53
May 186.05 01-MAY-14:09 44.76 01-MAY-08:09 0.00 0.00 0.00 0.00 0.00 2986.40 05-MAY-11:01 1886.09 21-MAY-12:52
June 186.05 01-JUN-14:09 44.76 01-JUN-08:09 0.00 0.00 0.00 0.00 0.00 1855.88 16-JUN-11:02 1620.84 30-JUN-12:53
July 186.05 01-JUL-10:09 44.76 01-JUL-09:09 0.00 0.00 0.00 0.00 0.00 1296.01 01-JUL-11:02 1429.69 03-JUL-12:53
August 186.05 01-AUG-14:09 44.76 01-AUG-08:09 0.00 0.00 0.00 0.00 0.00 1902.17 16-AUG-11:02 1677.80 25-AUG-11:02
September 186.05 01-SEP-14:09 44.76 01-SEP-08:09 0.00 0.00 0.00 0.00 0.00 1173.58 12-SEP-11:02 1677.39 15-SEP-16:53
October 186.05 02-OCT-14:09 44.76 02-OCT-08:09 0.00 0.00 0.00 0.00 0.00 1087.15 27-OCT-11:02 1109.84 29-OCT-16:53
November 186.05 01-NOV-14:09 44.76 01-NOV-08:09 0.00 0.00 0.00 0.00 0.00 703.94 18-NOV-12:55 1101.58 09-NOV-15:55
December 186.05 01-DEC-15:09 44.76 01-DEC-09:09 0.00 0.00 0.00 0.00 0.00 430.35 11-DEC-12:05 1207.05 21-DEC-08:61
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 186.05   44.76   0.00 0.00 0.00 0.00 0.00 430.35   1101.58  
Maximum of Months 186.05   44.76   0.00 0.00 0.00 0.00 0.00 2986.40   1886.09  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 29428.92 15-JAN-19:08 0.00 206.23 2269.08 0.00 0.00 0.00 0.00 66.42 0.00
February 30270.72 24-FEB-21:07 0.00 990.03 3630.52 0.00 0.00 0.00 0.00 26.54 0.00
March 30502.32 03-MAR-02:23 0.00 245.35 1815.26 0.00 0.00 0.00 0.00 1.24 0.00
April 29131.52 22-APR-00:43 0.00 245.35 1361.45 0.00 0.00 0.00 0.00 0.00 0.68
May 29466.54 11-MAY-01:23 0.00 245.35 1815.26 0.00 0.00 0.00 0.00 0.00 3.04
June 29841.18 01-JUN-01:23 0.00 245.35 1815.26 0.00 0.00 0.00 0.00 0.00 15.32
July 30565.53 19-JUL-22:43 0.00 245.35 1815.26 0.00 0.00 0.00 0.00 0.00 17.52
August 29736.02 24-AUG-02:63 0.00 245.35 1815.26 0.00 0.00 0.00 0.00 0.00 1.55
September 28952.19 09-SEP-04:03 0.00 245.35 1361.45 0.00 0.00 0.00 0.00 0.00 0.87
October 28897.77 09-OCT-04:43 0.00 123.74 1361.45 0.00 0.00 0.00 0.00 0.00 0.96
November 28460.67 02-NOV-01:23 0.00 245.35 1815.26 0.00 0.00 0.00 0.00 3.80 0.00
December 30689.25 20-DEC-21:10 0.00 660.02 2420.35 0.00 0.00 0.00 0.00 0.00 38.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 28460.67   0.00 123.74 1361.45 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30689.25   0.00 990.03 3630.52 0.00 0.00 0.00 0.00 66.42 38.27



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 117982.49 28-JAN-07:03 12404.84 1378.20 6186.11 0.00 0.00 0.00 0.00 0.00 1.27
February 126127.82 24-FEB-07:02 15506.05 1722.75 10310.18 0.00 0.00 0.00 0.00 0.00 6.51
March 122022.09 21-MAR-05:03 0.00 1378.20 4081.32 0.00 0.00 0.00 0.00 0.00 6.07
April 116288.46 27-APR-05:03 0.00 1378.20 4081.32 0.00 0.00 0.00 0.00 0.00 0.30
May 109142.33 31-MAY-05:03 0.00 1378.20 4081.32 0.00 0.00 0.00 0.00 0.00 7.47
June 110302.87 01-JUN-05:03 0.00 1378.20 4081.32 0.00 0.00 0.00 0.00 0.00 10.64
July 115013.81 31-JUL-05:03 0.00 1378.20 4081.32 0.00 0.00 0.00 0.00 0.00 3.29
August 108590.72 16-AUG-05:03 0.00 1378.20 4081.32 0.00 0.00 0.00 0.00 0.00 6.47
September 111212.61 13-SEP-05:03 0.00 1378.20 4081.32 0.00 0.00 0.00 0.00 0.00 3.77
October 103975.68 05-OCT-05:03 0.00 1033.65 3060.99 0.00 0.00 0.00 0.00 1.66 0.00
November 115287.87 25-NOV-07:03 12404.84 1378.20 6186.11 0.00 0.00 0.00 0.00 0.00 13.45
December 113560.88 27-DEC-07:03 12404.84 1378.20 8248.14 0.00 0.00 0.00 0.00 0.00 9.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 103975.68   0.00 1033.65 3060.99 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 126127.82   15506.05 1722.75 10310.18 0.00 0.00 0.00 0.00 1.66 13.45



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19314.31 16-JAN-19:05 0.00 511.34 2882.52 0.00 0.00 0.00 0.00 29.34 0.00
February 19507.63 24-FEB-21:05 0.00 2045.36 3843.35 0.00 0.00 0.00 0.00 11.28 0.00
March 18377.51 02-MAR-21:06 0.00 1704.47 3202.80 0.00 0.00 0.00 0.00 40.61 0.00
April 17737.71 22-APR-00:03 0.00 97.40 1441.26 0.00 0.00 0.00 0.00 0.00 0.02
May 17663.59 11-MAY-02:63 0.00 97.40 1921.68 0.00 0.00 0.00 0.00 0.00 0.12
June 17615.75 21-JUN-02:63 0.00 97.40 1921.68 0.00 0.00 0.00 0.00 0.00 5.62
July 17995.00 19-JUL-23:23 0.00 97.40 1921.68 0.00 0.00 0.00 0.00 0.00 1.95
August 17837.69 24-AUG-00:43 0.00 97.40 1921.68 0.00 0.00 0.00 0.00 0.00 0.03
September 17709.29 29-SEP-02:63 0.00 97.40 1921.68 0.00 0.00 0.00 0.00 1.67 0.00
October 17941.50 08-OCT-01:43 0.00 97.40 1441.26 0.00 0.00 0.00 0.00 0.07 0.00
November 18799.37 25-NOV-00:23 0.00 97.40 1441.26 0.00 0.00 0.00 0.00 0.00 2.35
December 20008.94 20-DEC-21:08 0.00 1363.57 2562.24 0.00 0.00 0.00 0.00 0.00 19.51
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17615.75   0.00 97.40 1441.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20008.94   0.00 2045.36 3843.35 0.00 0.00 0.00 0.00 40.61 19.51



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16493.34 07-JAN-03:03 0.00 97.40 216.32 0.00 0.00 0.00 0.00 0.00 6.12
February 16652.08 20-FEB-22:23 0.00 129.86 288.43 0.00 0.00 0.00 0.00 25.53 0.00
March 15535.55 02-MAR-01:43 0.00 97.40 288.43 0.00 0.00 0.00 0.00 0.04 0.00
April 14838.37 22-APR-00:03 0.00 97.40 216.32 0.00 0.00 0.00 0.00 0.41 0.00
May 14880.95 11-MAY-02:63 0.00 97.40 288.43 0.00 0.00 0.00 0.00 0.06 0.00
June 14945.49 20-JUN-04:03 0.00 97.40 288.43 0.00 0.00 0.00 0.00 0.61 0.00
July 15414.26 02-JUL-23:23 0.00 97.40 288.43 0.00 0.00 0.00 0.00 14.23 0.00
August 15038.78 24-AUG-00:43 0.00 97.40 288.43 0.00 0.00 0.00 0.00 0.02 0.00
September 15045.95 29-SEP-02:63 0.00 97.40 288.43 0.00 0.00 0.00 0.00 1.69 0.00
October 15344.55 09-OCT-04:03 0.00 97.40 216.32 0.00 0.00 0.00 0.00 0.08 0.00
November 16451.16 25-NOV-00:23 0.00 97.40 216.32 0.00 0.00 0.00 0.00 0.00 2.26
December 17033.16 20-DEC-21:08 0.00 1363.57 384.57 0.00 0.00 0.00 0.00 0.00 19.08
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 14838.37   0.00 97.40 216.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17033.16   0.00 1363.57 384.57 0.00 0.00 0.00 0.00 25.53 19.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:03 0.00 7.46 0.00 0.00 0.00 0.00 0.00 0.00 1.35
February 0.00 01-FEB-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 3.37
March 0.00 01-MAR-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 4.95
April 0.00 01-APR-00:03 0.00 7.75 0.00 0.00 0.00 0.00 0.00 0.00 2.36
May 0.00 01-MAY-00:03 0.00 7.46 0.00 0.00 0.00 0.00 0.00 0.00 0.06
June 0.00 01-JUN-00:03 0.00 7.75 0.00 0.00 0.00 0.00 0.00 0.00 3.80
July 0.00 01-JUL-00:05 0.00 5.17 0.00 0.00 0.00 0.00 0.00 0.00 0.82
August 0.00 01-AUG-00:03 0.00 7.75 0.00 0.00 0.00 0.00 0.00 0.00 2.87
September 0.00 01-SEP-00:03 0.00 7.75 0.00 0.00 0.00 0.00 0.00 0.00 0.96
October 0.00 01-OCT-00:10 0.00 2.49 0.00 0.00 0.00 0.00 0.00 0.00 1.04
November 0.00 01-NOV-00:05 0.00 5.17 0.00 0.00 0.00 0.00 0.00 0.00 0.96
December 0.00 01-DEC-00:10 0.00 2.58 0.00 0.00 0.00 0.00 0.00 0.00 2.07
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 2.49 0.00 0.00 0.00 0.00 0.00 0.00 0.06
Maximum of Months 0.00   0.00 7.75 0.00 0.00 0.00 0.00 0.00 0.00 4.95



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [] NATURALGAS:FACILITY []
January 0.107132E+12 86184.29 04-JAN-15:00 0.00 0.00
February 0.102086E+12 89862.98 13-FEB-15:00 0.00 0.00
March 0.119482E+12 92872.38 28-MAR-14:00 0.00 0.00
April 0.121970E+12 97521.59 01-APR-15:39 0.00 0.00
May 0.130621E+12 106778.64 06-MAY-15:09 0.00 0.00
June 0.130677E+12 107820.45 13-JUN-14:00 0.00 0.00
July 0.112764E+12 90431.92 15-JUL-15:00 0.00 0.00
August 0.121888E+12 97224.36 14-AUG-16:00 0.00 0.00
September 0.116157E+12 94056.26 06-SEP-14:00 0.00 0.00
October 0.112208E+12 90604.15 16-OCT-14:00 0.00 0.00
November 0.107683E+12 88036.80 14-NOV-17:30 0.00 0.00
December 0.107174E+12 85725.23 30-DEC-15:00 0.00 0.00
           
Annual Sum or Average 0.138984E+13     0.00 0.00
Minimum of Months 0.102086E+12 85725.23   0.00 0.00
Maximum of Months 0.130677E+12 107820.45   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.179122E+11 0.395605E+10 0.163682E+11 0.00 0.122734E+11 0.00 0.00 0.550809E+11 0.00 0.00 0.00 0.154093E+10 0.00
February 0.159430E+11 0.349771E+10 0.148500E+11 0.00 0.116006E+11 0.00 0.00 0.548000E+11 0.00 0.00 0.00 0.139429E+10 0.00
March 0.181205E+11 0.371076E+10 0.167807E+11 0.00 0.134866E+11 0.00 0.00 0.658269E+11 0.00 0.00 0.00 0.155697E+10 0.00
April 0.169223E+11 0.347391E+10 0.159483E+11 0.00 0.140838E+11 0.00 0.00 0.700879E+11 0.00 0.00 0.00 0.145332E+10 0.00
May 0.174983E+11 0.350443E+10 0.165744E+11 0.00 0.153896E+11 0.00 0.00 0.761792E+11 0.00 0.00 0.00 0.147455E+10 0.00
June 0.167354E+11 0.333636E+10 0.162038E+11 0.00 0.157142E+11 0.00 0.00 0.772626E+11 0.00 0.00 0.00 0.142509E+10 0.00
July 0.169372E+11 0.348609E+10 0.163169E+11 0.00 0.128833E+11 0.00 0.00 0.617143E+11 0.00 0.00 0.00 0.142610E+10 0.00
August 0.176870E+11 0.354799E+10 0.167807E+11 0.00 0.142821E+11 0.00 0.00 0.681126E+11 0.00 0.00 0.00 0.147791E+10 0.00
September 0.168229E+11 0.355644E+10 0.159441E+11 0.00 0.135224E+11 0.00 0.00 0.648816E+11 0.00 0.00 0.00 0.142932E+10 0.00
October 0.171467E+11 0.380704E+10 0.163703E+11 0.00 0.128927E+11 0.00 0.00 0.605057E+11 0.00 0.00 0.00 0.148589E+10 0.00
November 0.172861E+11 0.382080E+10 0.158468E+11 0.00 0.122273E+11 0.00 0.00 0.570429E+11 0.00 0.00 0.00 0.145959E+10 0.00
December 0.180718E+11 0.399170E+10 0.163148E+11 0.00 0.122613E+11 0.00 0.00 0.549987E+11 0.00 0.00 0.00 0.153623E+10 0.00
                           
Annual Sum or Average 0.207083E+12 0.436893E+11 0.194299E+12 0.00 0.160617E+12 0.00 0.00 0.766493E+12 0.00 0.00 0.00 0.176602E+11 0.00
Minimum of Months 0.159430E+11 0.333636E+10 0.148500E+11 0.00 0.116006E+11 0.00 0.00 0.548000E+11 0.00 0.00 0.00 0.139429E+10 0.00
Maximum of Months 0.181205E+11 0.399170E+10 0.167807E+11 0.00 0.157142E+11 0.00 0.00 0.772626E+11 0.00 0.00 0.00 0.155697E+10 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 20135.27 02-JAN-17:40 3820.86 01-JAN-06:10 10740.89 02-JAN-09:09 0.00 9886.06 03-JAN-07:10 0.00 0.00 01-JAN-00:10
February 20135.27 01-FEB-17:00 3820.86 01-FEB-06:10 10740.89 01-FEB-09:09 0.00 10307.76 16-FEB-07:10 0.00 0.00 01-FEB-00:10
March 20135.27 01-MAR-17:00 3820.86 01-MAR-06:10 10740.89 01-MAR-09:09 0.00 11149.58 28-MAR-06:10 0.00 0.00 01-MAR-00:10
April 18731.25 20-APR-16:00 3820.86 01-APR-05:10 10740.89 01-APR-09:09 0.00 11541.12 09-APR-08:09 0.00 0.00 01-APR-00:10
May 18950.51 22-MAY-16:00 3820.86 01-MAY-05:10 10740.89 01-MAY-08:09 0.00 12991.00 06-MAY-14:00 0.00 0.00 01-MAY-00:10
June 18864.35 03-JUN-16:00 3820.86 01-JUN-05:10 10740.89 01-JUN-08:09 0.00 13473.24 13-JUN-14:00 0.00 0.00 01-JUN-00:10
July 18935.43 17-JUL-16:00 3820.86 01-JUL-05:10 10740.89 01-JUL-09:09 0.00 10583.34 02-JUL-08:09 0.00 0.00 01-JUL-00:10
August 18884.45 24-AUG-16:00 3820.86 01-AUG-05:10 10740.89 01-AUG-08:09 0.00 11849.80 11-AUG-14:09 0.00 0.00 01-AUG-00:10
September 19137.20 26-SEP-16:00 3820.86 01-SEP-05:10 10740.89 01-SEP-08:09 0.00 11776.66 30-SEP-10:00 0.00 0.00 01-SEP-00:10
October 19586.74 30-OCT-16:00 3820.86 01-OCT-05:10 10740.89 02-OCT-08:09 0.00 11394.15 15-OCT-08:09 0.00 0.00 01-OCT-00:10
November 20135.27 06-NOV-17:30 3820.86 01-NOV-05:10 10740.89 01-NOV-08:09 0.00 11130.05 12-NOV-09:09 0.00 0.00 01-NOV-00:10
December 20135.27 01-DEC-17:30 3820.86 01-DEC-17:30 10740.89 01-DEC-09:09 0.00 11074.21 10-DEC-09:09 0.00 0.00 01-DEC-00:10
                         
Annual Sum or Average             0.00     0.00    
Minimum of Months 18731.25   3820.86   10740.89   0.00 9886.06   0.00 0.00  
Maximum of Months 20135.27   3820.86   10740.89   0.00 13473.24   0.00 0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 47654.48 04-JAN-15:50 0.00 0.00 0.00 1551.69 12-JAN-12:50 0.00
February 51696.08 28-FEB-15:09 0.00 0.00 0.00 1551.15 01-FEB-12:39 0.00
March 55114.72 28-MAR-14:00 0.00 0.00 0.00 1548.75 01-MAR-12:50 0.00
April 58542.91 01-APR-13:00 0.00 0.00 0.00 1544.13 03-APR-11:39 0.00
May 66285.75 06-MAY-14:00 0.00 0.00 0.00 1539.48 03-MAY-11:20 0.00
June 67283.20 13-JUN-14:00 0.00 0.00 0.00 1417.56 01-JUN-11:00 0.00
July 51946.74 15-JUL-15:00 0.00 0.00 0.00 1415.77 31-JUL-11:09 0.00
August 58333.14 11-AUG-14:09 0.00 0.00 0.00 1439.09 29-AUG-11:39 0.00
September 57642.32 30-SEP-10:00 0.00 0.00 0.00 1540.11 28-SEP-11:30 0.00
October 52668.15 16-OCT-14:00 0.00 0.00 0.00 1545.25 31-OCT-11:50 0.00
November 49051.85 18-NOV-12:00 0.00 0.00 0.00 1549.21 30-NOV-12:09 0.00
December 47355.27 30-DEC-13:00 0.00 0.00 0.00 1551.40 29-DEC-12:00 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 47355.27   0.00 0.00 0.00 1415.77   0.00
Maximum of Months 67283.20   0.00 0.00 0.00 1551.69   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 86184.29 04-JAN-15:00 17483.02 10740.89 0.00 0.00 9175.38 0.00 0.00 47637.25 0.00
February 89862.98 13-FEB-15:00 16725.71 10740.89 0.00 0.00 9896.83 0.00 0.00 51467.17 0.00
March 92872.38 28-MAR-14:00 15273.21 10740.89 0.00 0.00 10599.18 0.00 0.00 55114.72 0.00
April 97521.59 01-APR-15:39 16251.49 10740.89 0.00 0.00 11438.44 0.00 0.00 57941.73 0.00
May 106778.64 06-MAY-15:09 15954.44 10740.89 0.00 0.00 12984.03 0.00 0.00 65953.15 0.00
June 107820.45 13-JUN-14:00 15298.05 10740.89 0.00 0.00 13473.24 0.00 0.00 67283.20 0.00
July 90431.92 15-JUL-15:00 16487.92 10740.89 0.00 0.00 10113.35 0.00 0.00 51946.74 0.00
August 97224.36 14-AUG-16:00 18153.47 10740.89 0.00 0.00 11373.28 0.00 0.00 55813.02 0.00
September 94056.26 06-SEP-14:00 15531.53 10740.89 0.00 0.00 11118.69 0.00 0.00 55616.10 0.00
October 90604.15 16-OCT-14:00 15572.05 10740.89 0.00 0.00 10594.12 0.00 0.00 52668.15 0.00
November 88036.80 14-NOV-17:30 20135.27 10740.89 3820.86 0.00 8547.70 0.00 0.00 43641.50 0.00
December 85725.23 30-DEC-15:00 17510.57 10740.89 0.00 0.00 9253.39 0.00 0.00 47064.90 0.00
                       
Annual Sum or Average           0.00   0.00     0.00
Minimum of Months 85725.23   15273.21 10740.89 0.00 0.00 8547.70 0.00 0.00 43641.50 0.00
Maximum of Months 107820.45   20135.27 10740.89 3820.86 0.00 13473.24 0.00 0.00 67283.20 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 26.67 24.52 0.00 24.52
February 0.00 0.00 0.00 0.00 42.00 24.56 0.00 24.56
March 0.00 0.00 0.00 0.00 58.17 24.62 0.00 24.62
April 0.00 0.00 0.00 0.00 59.33 24.71 0.00 24.71
May 0.00 0.00 0.00 0.00 58.83 24.79 0.00 24.79
June 0.00 0.00 0.00 0.00 64.00 24.87 0.00 24.87
July 0.00 0.00 0.00 0.00 67.00 24.69 0.00 24.69
August 0.00 0.00 0.00 0.00 50.67 24.68 0.00 24.68
September 0.00 0.00 0.00 0.00 50.67 24.62 0.00 24.62
October 0.00 0.00 0.00 0.00 37.17 24.56 0.00 24.56
November 0.00 0.00 0.00 0.00 29.17 24.53 0.00 24.53
December 0.00 0.00 0.00 0.00 18.00 24.51 0.00 24.51
                 
Annual Sum or Average 0.00   0.00   561.67 24.67 0.00 24.67
Minimum of Months 0.00 0.00 0.00 0.00 18.00 24.51 0.00 24.51
Maximum of Months 0.00 0.00 0.00 0.00 67.00 24.87 0.00 24.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 69.83 24.89 0.00 24.89
February 0.00 0.00 0.00 0.00 65.00 24.93 0.00 24.93
March 0.00 0.00 0.00 0.00 69.00 24.92 0.00 24.92
April 0.00 0.00 0.00 0.00 63.67 24.87 0.00 24.87
May 0.00 0.00 0.00 0.00 66.00 24.83 0.00 24.83
June 0.00 0.00 0.00 0.00 65.67 24.86 0.00 24.86
July 0.00 0.00 0.00 0.00 70.83 24.73 0.00 24.73
August 0.00 0.00 0.00 0.00 57.50 24.76 0.00 24.76
September 0.00 0.00 0.00 0.00 63.00 24.80 0.00 24.80
October 0.00 0.00 0.00 0.00 60.33 24.80 0.00 24.80
November 0.00 0.00 0.00 0.00 63.83 24.83 0.00 24.83
December 0.00 0.00 0.00 0.00 69.33 24.84 0.00 24.84
                 
Annual Sum or Average 0.00   0.00   784.00 24.84 0.00 24.84
Minimum of Months 0.00 0.00 0.00 0.00 57.50 24.73 0.00 24.73
Maximum of Months 0.00 0.00 0.00 0.00 70.83 24.93 0.00 24.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 65.50 24.77 0.00 24.77
February 0.00 0.00 0.00 0.00 64.00 24.80 0.00 24.80
March 0.00 0.00 0.00 0.00 67.00 24.78 0.00 24.78
April 0.00 0.00 0.00 0.00 60.33 24.74 0.00 24.74
May 0.00 0.00 0.00 0.00 59.17 24.73 0.00 24.73
June 0.00 0.00 0.00 0.00 61.33 24.75 0.00 24.75
July 0.00 0.00 0.00 0.00 63.17 24.63 0.00 24.63
August 0.00 0.00 0.00 0.00 50.50 24.66 0.00 24.66
September 0.00 0.00 0.00 0.00 56.83 24.70 0.00 24.70
October 0.00 0.00 0.00 0.00 55.33 24.70 0.00 24.70
November 0.00 0.00 0.00 0.00 57.00 24.73 0.00 24.73
December 0.00 0.00 0.00 0.00 62.33 24.75 0.00 24.75
                 
Annual Sum or Average 0.00   0.00   722.50 24.73 0.00 24.73
Minimum of Months 0.00 0.00 0.00 0.00 50.50 24.63 0.00 24.63
Maximum of Months 0.00 0.00 0.00 0.00 67.00 24.80 0.00 24.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 407.67 23.89 0.00 23.89
February 0.00 0.00 376.00 23.89 0.00 23.89
March 0.00 0.00 421.50 23.89 0.00 23.89
April 2.00 23.89 405.00 23.89 2.00 23.89
May 30.33 23.89 418.00 23.89 30.33 23.89
June 2.00 23.89 408.00 23.89 2.00 23.89
July 1.50 23.89 415.00 23.89 1.50 23.89
August 36.67 23.89 422.00 23.89 36.67 23.89
September 16.17 23.89 405.00 23.89 16.17 23.89
October 38.17 23.89 414.00 23.89 38.17 23.89
November 0.00 0.00 398.83 23.89 0.00 23.89
December 0.00 0.00 411.33 23.89 0.00 23.89
             
Annual Sum or Average 126.83 23.89 4902.33 23.89 126.83 23.89
Minimum of Months 0.00 0.00 376.00 23.89 0.00 23.89
Maximum of Months 38.17 23.89 422.00 23.89 38.17 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 45.83 23.91 414.00 23.89 45.83 23.90
February 22.00 23.93 376.00 23.90 22.00 23.90
March 28.50 23.94 422.00 23.90 28.50 23.90
April 104.00 23.91 405.00 23.90 104.00 23.90
May 276.67 23.90 418.00 23.90 276.67 23.90
June 269.50 23.90 408.00 23.90 269.50 23.90
July 122.33 23.90 415.00 23.90 122.33 23.90
August 339.50 23.90 422.00 23.90 339.50 23.90
September 283.83 23.90 405.00 23.90 283.83 23.90
October 317.33 23.90 414.00 23.89 317.33 23.90
November 167.17 23.90 399.00 23.90 167.17 23.90
December 86.83 23.90 415.00 23.89 86.83 23.90
             
Annual Sum or Average 2063.50 23.90 4913.00 23.90 2063.50 23.90
Minimum of Months 22.00 23.90 376.00 23.89 22.00 23.90
Maximum of Months 339.50 23.94 422.00 23.90 339.50 23.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 414.00 23.89 0.00 23.89
February 0.00 0.00 376.00 23.89 0.00 23.89
March 0.00 0.00 422.00 23.89 0.00 23.89
April 4.83 23.89 405.00 23.89 4.83 23.89
May 42.67 23.89 418.00 23.89 42.67 23.89
June 20.33 23.89 408.00 23.89 20.33 23.89
July 2.67 23.89 415.00 23.89 2.67 23.89
August 58.67 23.89 422.00 23.89 58.67 23.89
September 24.67 23.89 405.00 23.89 24.67 23.89
October 22.33 23.89 414.00 23.89 22.33 23.89
November 0.00 0.00 399.00 23.89 0.00 23.89
December 0.00 0.00 415.00 23.89 0.00 23.89
             
Annual Sum or Average 176.17 23.89 4913.00 23.89 176.17 23.89
Minimum of Months 0.00 0.00 376.00 23.89 0.00 23.89
Maximum of Months 58.67 23.89 422.00 23.89 58.67 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.00 23.89 414.00 23.89 2.00 23.89
February 0.00 0.00 376.00 23.89 0.00 23.89
March 0.00 0.00 422.00 23.89 0.00 23.89
April 18.17 23.89 405.00 23.89 18.17 23.89
May 99.50 23.89 418.00 23.89 99.50 23.89
June 74.83 23.89 408.00 23.89 74.83 23.89
July 25.33 23.89 415.00 23.89 25.33 23.89
August 139.00 23.89 422.00 23.89 139.00 23.89
September 63.33 23.89 405.00 23.89 63.33 23.89
October 69.83 23.89 414.00 23.89 69.83 23.89
November 6.33 23.89 399.00 23.89 6.33 23.89
December 2.17 23.89 415.00 23.89 2.17 23.89
             
Annual Sum or Average 500.50 23.89 4913.00 23.89 500.50 23.89
Minimum of Months 0.00 0.00 376.00 23.89 0.00 23.89
Maximum of Months 139.00 23.89 422.00 23.89 139.00 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 412.17 29.31 414.00 29.29 412.17 29.30
February 376.00 30.03 376.00 30.03 376.00 30.03
March 422.00 30.31 422.00 30.31 422.00 30.31
April 405.00 30.42 405.00 30.42 405.00 30.42
May 418.00 30.34 418.00 30.34 418.00 30.34
June 408.00 30.40 408.00 30.40 408.00 30.40
July 415.00 28.76 415.00 28.76 415.00 28.76
August 422.00 28.89 422.00 28.89 422.00 28.89
September 405.00 29.04 405.00 29.04 405.00 29.04
October 414.00 28.52 414.00 28.52 414.00 28.52
November 399.00 28.75 399.00 28.75 399.00 28.75
December 414.50 28.95 415.00 28.95 414.50 28.95
             
Annual Sum or Average 4910.67 29.47 4913.00 29.47 4910.67 29.47
Minimum of Months 376.00 28.52 376.00 28.52 376.00 28.52
Maximum of Months 422.00 30.42 422.00 30.42 422.00 30.42



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 23.89024 53.52168 0.53620 11.04854
February 376.00000 23.89024 52.95227 0.55718 11.53144
March 422.00000 23.89022 53.47903 0.57606 11.98782
April 405.00000 23.89016 55.51259 0.61074 12.84990
May 418.00000 23.89008 57.24343 -0.2012 5.94549
June 408.00000 23.89010 55.74631 -0.1685 5.71073
July 415.00000 23.89021 54.20359 -0.2448 6.31628
August 422.00000 23.89014 58.93137 -0.2455 6.34832
September 405.00000 23.89017 58.34457 -0.2562 6.42492
October 414.00000 23.89020 59.54488 0.57759 12.01321
November 399.00000 23.89023 56.88496 0.56453 11.69981
December 415.00000 23.89023 55.15196 0.53996 11.13074
           
Annual Sum or Average 4913.00000 23.89018 55.97819 0.23378 9.39374
Minimum of Months 376.00000 23.89008 52.95227 -0.2562 5.71073
Maximum of Months 422.00000 23.89024 59.54488 0.61074 12.84990



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 23.89244 59.34673 0.60688 12.74139
February 376.00000 23.89338 59.03465 0.62362 13.17716
March 422.00000 23.89422 59.40281 0.64021 13.62631
April 405.00000 23.89491 62.91289 0.67030 14.45524
May 418.00000 23.89573 66.41490 -0.1641 5.59252
June 408.00000 23.89556 66.03830 -0.1521 5.51619
July 415.00000 23.89450 63.26704 -0.2088 5.92329
August 422.00000 23.89494 67.47290 -0.1854 5.75753
September 405.00000 23.89480 66.40886 -0.1845 5.73898
October 414.00000 23.89435 66.86389 0.64982 13.87943
November 399.00000 23.89422 64.06616 0.63612 13.50742
December 415.00000 23.89307 61.32221 0.61328 12.90678
           
Annual Sum or Average 4913.00000 23.89435 63.57360 0.29196 10.20283
Minimum of Months 376.00000 23.89244 59.03465 -0.2088 5.51619
Maximum of Months 422.00000 23.89573 67.47290 0.67030 14.45524



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 23.89024 50.51324 0.68485 14.95272
February 376.00000 23.89020 50.90923 0.69436 15.22165
March 422.00000 23.89018 52.78737 0.67802 14.73254
April 405.00000 23.89012 56.68838 0.67705 14.67398
May 418.00000 23.89010 59.19752 -0.1345 5.47460
June 408.00000 23.89009 59.03074 -0.1254 5.42140
July 415.00000 23.89027 56.39394 -0.1835 5.77599
August 422.00000 23.89016 60.08259 -0.1692 5.70349
September 405.00000 23.89013 58.40352 -0.1489 5.57443
October 414.00000 23.89015 57.67903 0.66996 14.49314
November 399.00000 23.89018 54.13027 0.68522 14.94188
December 415.00000 23.89023 51.60706 0.68599 14.97826
           
Annual Sum or Average 4913.00000 23.89017 55.65323 0.33079 10.95332
Minimum of Months 376.00000 23.89009 50.51324 -0.1835 5.42140
Maximum of Months 422.00000 23.89027 60.08259 0.69436 15.22165



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 23.89019 51.45705 0.66805 14.46076
February 376.00000 23.89015 51.74719 0.67740 14.72301
March 422.00000 23.89014 54.08067 0.66255 14.28827
April 405.00000 23.89010 58.44942 0.66642 14.36700
May 418.00000 23.89010 61.32835 -0.1520 5.56723
June 408.00000 23.89012 60.95939 -0.1427 5.51052
July 415.00000 23.89020 58.58372 -0.2018 5.91383
August 422.00000 23.89016 62.75825 -0.1834 5.79433
September 405.00000 23.89013 60.62257 -0.1661 5.67353
October 414.00000 23.89011 60.03453 0.66170 14.24829
November 399.00000 23.89012 55.63190 0.67191 14.54834
December 415.00000 23.89018 52.71428 0.67014 14.51313
           
Annual Sum or Average 4913.00000 23.89014 57.40629 0.31563 10.76125
Minimum of Months 376.00000 23.89010 51.45705 -0.2018 5.51052
Maximum of Months 422.00000 23.89020 62.75825 0.67740 14.72301



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 29.28018 60.76768 1.81708 66.62587
February 376.00000 30.02701 59.71327 1.95822 72.43238
March 422.00000 30.30616 60.73894 1.97266 72.69471
April 405.00000 30.42030 69.73734 2.04682 76.10421
May 418.00000 30.34055 77.85273 1.72275 60.32282
June 408.00000 30.39805 78.23060 1.75488 61.60159
July 415.00000 28.76395 73.23995 1.20216 38.28831
August 422.00000 28.88990 83.33135 1.32106 43.91913
September 405.00000 29.04054 80.75344 1.37926 46.45369
October 414.00000 28.51505 80.72280 1.75539 63.71127
November 399.00000 28.74578 73.81268 1.79751 65.75706
December 415.00000 28.94962 65.71198 1.79231 65.46721
           
Annual Sum or Average 4913.00000 29.46982 72.12549 1.70747 60.99840
Minimum of Months 376.00000 28.51505 59.71327 1.20216 38.28831
Maximum of Months 422.00000 30.42030 83.33135 2.04682 76.10421



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.297392E+11 0.752789E+10 640.81 0.219428E+11 0.779637E+10 0.00 1.00 01-JAN-00:55 0.00 01-JAN-00:03 41185.74 09-JAN-21:08 33024.42 15-JAN-19:08 12082.79 09-JAN-21:08 9639.70 08-JAN-19:08 0.00
February 0.306462E+11 0.773233E+10 586.67 0.229066E+11 0.773956E+10 0.00 1.00 01-FEB-00:23 0.00 01-FEB-00:12 40962.01 15-FEB-21:42 33866.22 20-FEB-21:03 11459.97 14-FEB-21:06 9718.35 26-FEB-19:06 0.00
March 0.381341E+11 0.960668E+10 661.54 0.282173E+11 0.991675E+10 0.00 1.00 01-MAR-00:23 0.00 01-MAR-00:12 40970.93 14-MAR-20:08 33582.89 03-MAR-02:23 10640.72 14-MAR-20:08 9785.19 26-MAR-18:06 0.00
April 0.430965E+11 0.107362E+11 642.74 0.303428E+11 0.127537E+11 0.00 1.00 01-APR-00:03 0.00 01-APR-00:33 41652.40 20-APR-20:10 32611.84 26-APR-21:23 14602.14 20-APR-20:10 10249.58 30-APR-18:43 0.00
May 0.497475E+11 0.122723E+11 664.22 0.336028E+11 0.161446E+11 0.00 1.00 01-MAY-00:03 0.00 01-MAY-00:33 42206.43 21-MAY-18:10 32038.46 31-MAY-22:03 16901.93 21-MAY-18:10 10170.89 29-MAY-18:06 0.00
June 0.532246E+11 0.130635E+11 647.32 0.366102E+11 0.166144E+11 0.00 1.00 01-JUN-00:03 0.00 01-JUN-00:33 41814.73 28-JUN-20:10 32437.16 07-JUN-20:42 15063.61 28-JUN-20:10 10041.65 11-JUN-18:42 0.00
July 0.422746E+11 0.103114E+11 666.71 0.302705E+11 0.120041E+11 0.00 1.00 01-JUL-00:20 0.00 01-JUL-00:05 41284.04 07-JUL-20:08 33317.83 13-JUL-20:43 12218.99 07-JUL-20:08 9798.76 30-JUL-18:08 0.00
August 0.425805E+11 0.103226E+11 654.78 0.276997E+11 0.148808E+11 0.00 1.00 01-AUG-00:03 0.00 01-AUG-00:33 41729.79 21-AUG-20:10 32180.98 24-AUG-02:63 14192.85 21-AUG-20:10 9811.64 27-AUG-18:06 0.00
September 0.391483E+11 0.954075E+10 639.07 0.258307E+11 0.133177E+11 0.00 1.00 01-SEP-00:03 0.00 01-SEP-00:33 41754.13 17-SEP-18:10 31808.23 12-SEP-04:03 14415.12 17-SEP-18:10 9830.40 04-SEP-18:06 0.00
October 0.345823E+11 0.844069E+10 644.47 0.224147E+11 0.121676E+11 0.00 1.00 01-OCT-00:23 0.00 01-OCT-00:12 41773.24 25-OCT-20:10 31896.76 10-OCT-02:63 14179.59 25-OCT-20:10 9603.16 12-OCT-20:08 0.00
November 0.320454E+11 0.788996E+10 620.92 0.217368E+11 0.103086E+11 0.00 1.00 01-NOV-20:08 0.00 01-NOV-00:33 41662.62 11-NOV-19:10 31526.77 02-NOV-01:23 13772.73 11-NOV-19:10 9683.25 19-NOV-19:08 0.00
December 0.293284E+11 0.735916E+10 638.51 0.208210E+11 0.850734E+10 0.00 1.00 01-DEC-00:23 0.00 01-DEC-00:13 41730.08 09-DEC-22:10 33596.68 20-DEC-21:10 13731.06 09-DEC-22:10 9609.56 10-DEC-19:08 0.00
                                       
Annual Sum or Average 0.464547E+12 0.114803E+12 7707.76 0.322396E+12 0.142152E+12 0.00                         0.00
Minimum of Months 0.293284E+11 0.735916E+10 586.67 0.208210E+11 0.773956E+10 0.00 1.00   0.00   40962.01   31526.77   10640.72   9603.16   0.00
Maximum of Months 0.532246E+11 0.130635E+11 666.71 0.366102E+11 0.166144E+11 0.00 1.00   0.00   42206.43   33866.22   16901.93   10249.58   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.127762E+12 0.347697E+11 422.56 0.793349E+11 0.484274E+11 0.00 1.00 01-JAN-09:02 0.00 01-JAN-00:03 211194.25 02-JAN-07:02 134845.05 16-JAN-09:02 107297.10 02-JAN-07:04 50892.74 11-JAN-07:02 0.00
February 0.127727E+12 0.347955E+11 387.19 0.799845E+11 0.477422E+11 0.00 1.00 01-FEB-06:13 0.00 01-FEB-00:10 210954.27 16-FEB-07:02 136970.90 25-FEB-07:02 104324.44 16-FEB-07:04 52358.10 20-FEB-09:02 0.00
March 0.156510E+12 0.426879E+11 442.14 0.974697E+11 0.590405E+11 0.00 1.00 01-MAR-06:03 0.00 01-MAR-00:10 210743.16 28-MAR-06:02 137452.01 20-MAR-05:03 101786.66 28-MAR-06:04 53055.02 26-MAR-08:62 0.00
April 0.172045E+12 0.460017E+11 428.15 0.979542E+11 0.740909E+11 0.00 1.00 01-APR-05:03 0.00 01-APR-00:03 212481.07 15-APR-06:02 133989.57 27-APR-05:03 109464.85 15-APR-06:04 53140.23 30-APR-08:15 0.00
May 0.188386E+12 0.495497E+11 441.18 0.983053E+11 0.900805E+11 0.00 1.00 01-MAY-05:02 0.00 01-MAY-00:03 215805.92 19-MAY-06:02 128354.10 07-MAY-07:02 128486.30 22-MAY-06:06 54832.02 28-MAY-07:02 0.00
June 0.190216E+12 0.499448E+11 429.27 0.989206E+11 0.912955E+11 0.00 1.00 01-JUN-05:03 0.00 01-JUN-00:03 215807.14 29-JUN-06:02 123516.00 16-JUN-05:02 121736.00 29-JUN-06:06 53615.47 18-JUN-08:15 0.00
July 0.150892E+12 0.396910E+11 434.20 0.835906E+11 0.673016E+11 0.00 1.00 01-JUL-06:02 0.00 01-JUL-00:05 213059.57 01-JUL-06:02 129343.62 15-JUL-05:03 112427.17 01-JUL-06:04 52044.00 09-JUL-08:62 0.00
August 0.175096E+12 0.450872E+11 442.44 0.868934E+11 0.882025E+11 0.00 1.00 01-AUG-05:03 0.00 01-AUG-00:03 214887.45 05-AUG-06:02 121536.76 16-AUG-05:03 122619.53 21-AUG-06:02 53098.36 13-AUG-08:15 0.00
September 0.164911E+12 0.426793E+11 425.39 0.843696E+11 0.805417E+11 0.00 1.00 01-SEP-05:03 0.00 01-SEP-00:03 215305.02 17-SEP-08:62 125495.94 14-SEP-05:03 119007.42 17-SEP-08:04 52772.19 10-SEP-08:06 0.00
October 0.153760E+12 0.396449E+11 430.41 0.778052E+11 0.759552E+11 0.00 1.00 01-OCT-07:03 0.00 01-OCT-00:10 214635.36 12-OCT-06:02 123679.82 05-OCT-05:03 119469.41 12-OCT-06:04 52379.86 29-OCT-08:04 0.00
November 0.139852E+12 0.366149E+11 415.14 0.757873E+11 0.640647E+11 0.00 1.00 01-NOV-06:02 0.00 01-NOV-00:05 213685.91 12-NOV-09:02 124650.99 25-NOV-07:03 111642.75 12-NOV-09:04 52576.01 23-NOV-09:02 0.00
December 0.130225E+12 0.349174E+11 420.46 0.766952E+11 0.535294E+11 0.00 1.00 01-DEC-07:03 0.00 01-DEC-00:10 211839.35 10-DEC-09:02 126594.03 03-DEC-09:02 109561.29 18-DEC-07:04 52512.68 31-DEC-09:02 0.00
                                       
Annual Sum or Average 0.187738E+13 0.496384E+12 5118.53 0.103711E+13 0.840272E+12 0.00                         0.00
Minimum of Months 0.127727E+12 0.347697E+11 387.19 0.757873E+11 0.477422E+11 0.00 1.00   0.00   210743.16   121536.76   101786.66   50892.74   0.00
Maximum of Months 0.190216E+12 0.499448E+11 442.44 0.989206E+11 0.912955E+11 0.00 1.00   0.00   215807.14   137452.01   128486.30   54832.02   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.278856E+11 0.681602E+10 654.76 0.205810E+11 0.730460E+10 0.00 1.00 01-JAN-00:10 0.00 01-JAN-00:03 27046.74 09-JAN-21:08 22138.58 15-JAN-19:42 8348.63 09-JAN-21:08 6302.99 08-JAN-19:06 0.00
February 0.263783E+11 0.652436E+10 593.99 0.194533E+11 0.692497E+10 0.00 1.00 01-FEB-00:23 0.00 01-FEB-00:12 26871.39 14-FEB-21:06 22696.35 20-FEB-21:42 7874.44 14-FEB-21:06 6361.34 26-FEB-19:06 0.00
March 0.290279E+11 0.723318E+10 661.73 0.207842E+11 0.824377E+10 0.00 1.00 01-MAR-00:23 0.00 01-MAR-00:12 26970.24 14-MAR-20:08 21387.02 13-MAR-22:03 7909.50 14-MAR-20:08 6417.30 26-MAR-18:06 0.00
April 0.287490E+11 0.712738E+10 639.01 0.189650E+11 0.978403E+10 0.00 1.00 01-APR-00:03 0.00 01-APR-00:33 27463.42 20-APR-20:10 20085.57 27-APR-04:43 10502.38 20-APR-20:10 6540.99 30-APR-18:06 0.00
May 0.311690E+11 0.764294E+10 661.19 0.192710E+11 0.118980E+11 0.00 1.00 01-MAY-00:03 0.00 01-MAY-00:33 27798.41 28-MAY-18:10 19778.57 11-MAY-02:63 11788.31 28-MAY-18:10 6679.80 29-MAY-18:06 0.00
June 0.309742E+11 0.757340E+10 641.78 0.191316E+11 0.118427E+11 0.00 1.00 01-JUN-00:03 0.00 01-JUN-00:33 27723.76 03-JUN-21:08 19627.66 20-JUN-04:03 11281.53 03-JUN-21:08 6594.67 11-JUN-18:42 0.00
July 0.258945E+11 0.629174E+10 652.27 0.170176E+11 0.887697E+10 0.00 1.00 01-JUL-10:10 0.00 01-JUL-00:10 27309.40 07-JUL-20:08 20527.30 02-JUL-22:43 9605.27 07-JUL-20:08 6438.53 30-JUL-18:08 0.00
August 0.283924E+11 0.681839E+10 653.53 0.170588E+11 0.113335E+11 0.00 1.00 01-AUG-00:03 0.00 01-AUG-00:07 27556.61 06-AUG-18:10 19966.15 24-AUG-00:43 10553.67 05-AUG-21:10 6445.25 27-AUG-18:06 0.00
September 0.280592E+11 0.676394E+10 635.89 0.174984E+11 0.105609E+11 0.00 1.00 01-SEP-00:03 0.00 01-SEP-00:07 27409.00 19-SEP-20:08 19935.55 29-SEP-02:63 10109.18 18-SEP-20:10 6449.76 04-SEP-18:06 0.00
October 0.278597E+11 0.667162E+10 650.75 0.175581E+11 0.103016E+11 0.00 1.00 01-OCT-00:23 0.00 01-OCT-00:12 27403.71 14-OCT-21:08 20161.13 09-OCT-03:23 10009.49 14-OCT-21:08 6295.38 15-OCT-18:08 0.00
November 0.277841E+11 0.668636E+10 632.01 0.186848E+11 0.909938E+10 0.00 1.00 01-NOV-10:10 0.00 01-NOV-00:33 27269.62 12-NOV-19:08 20900.71 25-NOV-00:23 9450.52 12-NOV-19:08 6335.10 19-NOV-19:06 0.00
December 0.280545E+11 0.678266E+10 655.34 0.200555E+11 0.799898E+10 0.00 1.00 01-DEC-00:23 0.00 01-DEC-00:13 27384.65 09-DEC-22:08 21877.36 26-DEC-21:42 9805.69 09-DEC-22:08 6286.60 10-DEC-19:06 0.00
                                       
Annual Sum or Average 0.340228E+12 0.829320E+11 7732.24 0.226059E+12 0.114169E+12 0.00                         0.00
Minimum of Months 0.258945E+11 0.629174E+10 593.99 0.170176E+11 0.692497E+10 0.00 1.00   0.00   26871.39   19627.66   7874.44   6286.60   0.00
Maximum of Months 0.311690E+11 0.764294E+10 661.73 0.207842E+11 0.118980E+11 0.00 1.00   0.00   27798.41   22696.35   11788.31   6679.80   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.244849E+11 0.596729E+10 655.27 0.173373E+11 0.714756E+10 0.00 1.00 01-JAN-00:10 0.00 01-JAN-00:03 24041.87 09-JAN-21:08 18930.26 15-JAN-20:23 8571.51 09-JAN-21:08 5562.92 08-JAN-19:06 0.00
February 0.233267E+11 0.574778E+10 594.59 0.165226E+11 0.680408E+10 0.00 1.00 01-FEB-00:23 0.00 01-FEB-00:12 23863.57 14-FEB-21:06 19417.31 20-FEB-21:42 8004.66 14-FEB-21:06 5612.64 26-FEB-19:06 0.00
March 0.253763E+11 0.629914E+10 661.16 0.173780E+11 0.799834E+10 0.00 1.00 01-MAR-00:23 0.00 01-MAR-00:12 23925.38 14-MAR-20:08 18071.03 13-MAR-22:03 8123.52 24-MAR-20:06 5662.26 26-MAR-18:06 0.00
April 0.252848E+11 0.622261E+10 638.03 0.158130E+11 0.947179E+10 0.00 1.00 01-APR-00:03 0.00 01-APR-00:33 24521.84 20-APR-20:10 16920.29 27-APR-04:43 10609.34 20-APR-20:10 5932.23 30-APR-18:43 0.00
May 0.276372E+11 0.671420E+10 660.92 0.160969E+11 0.115403E+11 0.00 1.00 01-MAY-00:03 0.00 01-MAY-00:33 24716.14 28-MAY-18:10 16530.14 11-MAY-02:63 11682.59 21-MAY-18:10 5891.38 29-MAY-18:06 0.00
June 0.275861E+11 0.668089E+10 641.89 0.160566E+11 0.115296E+11 0.00 1.00 01-JUN-00:03 0.00 01-JUN-00:33 24721.42 28-JUN-20:10 16600.65 20-JUN-04:03 11317.53 28-JUN-20:10 5815.39 11-JUN-18:42 0.00
July 0.223928E+11 0.542016E+10 652.66 0.138908E+11 0.850197E+10 0.00 1.00 01-JUL-10:40 0.00 01-JUL-00:10 24325.94 07-JUL-20:08 17501.57 02-JUL-23:23 9925.11 07-JUL-20:08 5680.75 30-JUL-18:08 0.00
August 0.246891E+11 0.588440E+10 650.10 0.138566E+11 0.108325E+11 0.00 1.00 01-AUG-00:03 0.00 01-AUG-00:07 24510.37 03-AUG-20:08 16689.77 24-AUG-00:43 10731.93 03-AUG-20:08 5685.68 27-AUG-18:06 0.00
September 0.246392E+11 0.589759E+10 635.18 0.144452E+11 0.101940E+11 0.00 1.00 01-SEP-00:03 0.00 01-SEP-00:07 24514.72 18-SEP-20:10 16785.46 29-SEP-02:63 10515.37 18-SEP-20:10 5689.91 13-SEP-20:06 0.00
October 0.241544E+11 0.574848E+10 647.75 0.143002E+11 0.985422E+10 0.00 1.00 01-OCT-00:23 0.00 01-OCT-00:12 24395.79 25-OCT-20:08 17024.85 09-OCT-03:23 10148.14 25-OCT-20:08 5556.01 15-OCT-18:08 0.00
November 0.244380E+11 0.585169E+10 631.95 0.155821E+11 0.885589E+10 0.00 1.00 01-NOV-10:25 0.00 01-NOV-00:33 24235.84 30-NOV-21:08 18114.59 25-NOV-00:23 9516.91 08-NOV-21:10 5591.68 19-NOV-19:06 0.00
December 0.246478E+11 0.593943E+10 655.72 0.168332E+11 0.781467E+10 0.00 1.00 01-DEC-00:23 0.00 01-DEC-00:13 24289.31 09-DEC-22:08 18537.78 26-DEC-22:23 9646.34 09-DEC-22:08 5547.59 10-DEC-19:06 0.00
                                       
Annual Sum or Average 0.298657E+12 0.723737E+11 7725.22 0.188112E+12 0.110545E+12 0.00                         0.00
Minimum of Months 0.223928E+11 0.542016E+10 594.59 0.138566E+11 0.680408E+10 0.00 1.00   0.00   23863.57   16530.14   8004.66   5547.59   0.00
Maximum of Months 0.276372E+11 0.671420E+10 661.16 0.173780E+11 0.115403E+11 0.00 1.00   0.00   24721.42   19417.31   11682.59   5932.23   0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 44.68 21.40 23.28 85.02 14.47 0.00 0.00 0.00
February 51.78 26.99 24.79 99.21 14.97 0.00 0.00 0.00
March 60.10 35.37 24.73 115.23 12.39 0.00 0.00 0.00
April 60.84 34.24 26.61 117.56 8.62 0.00 0.00 0.00
May 50.82 22.19 28.63 100.71 7.07 0.00 0.00 0.00
June 54.96 27.30 27.66 108.09 7.02 0.00 0.00 0.00
July 46.18 15.38 30.80 90.02 9.21 0.00 0.00 0.00
August 51.06 22.02 29.04 95.93 8.64 0.00 0.00 0.00
September 47.14 18.38 28.76 91.78 8.23 0.00 0.00 0.00
October 43.05 15.30 27.75 81.14 8.71 0.00 0.00 0.00
November 41.14 15.66 25.49 78.61 11.00 0.00 0.00 0.00
December 41.45 18.63 22.82 78.99 15.01 0.00 0.00 0.00
                 
Annual Sum or Average 49.40 22.69 26.71 95.11 10.43 0.00 0.00 0.00
Minimum of Months 41.14 15.30 22.82 78.61 7.02 0.00 0.00 0.00
Maximum of Months 60.84 35.37 30.80 117.56 15.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: POINT_OF_SALE_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 620.86 259.03 361.83 1332.08 129.25 0.00 0.00 0.00
February 527.20 171.89 355.32 1213.89 102.06 0.00 0.00 0.00
March 359.79 48.32 311.47 909.19 67.87 0.00 0.00 0.00
April 268.24 0.12 268.12 709.06 20.85 0.00 0.00 0.00
May 268.42 0.00 268.42 737.11 27.37 0.00 0.00 0.00
June 267.46 0.00 267.46 724.01 29.70 0.00 0.00 0.00
July 275.52 0.00 275.52 659.87 59.32 0.00 0.00 0.00
August 268.22 0.41 267.81 637.48 44.42 0.00 0.00 0.00
September 296.94 9.70 287.24 722.96 47.20 0.00 0.00 0.00
October 388.48 61.94 326.54 875.85 63.62 0.00 0.00 0.00
November 505.16 154.12 351.04 1103.22 87.98 0.00 0.00 0.00
December 620.54 264.02 356.53 1312.12 147.34 0.00 0.00 0.00
                 
Annual Sum or Average 388.36 80.48 307.88 909.97 68.89 0.00 0.00 0.00
Minimum of Months 267.46 0.00 267.46 637.48 20.85 0.00 0.00 0.00
Maximum of Months 620.86 264.02 361.83 1332.08 147.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FRONT_RETAIL_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 620.86 259.03 361.83 1325.32 125.72 0.00 0.00 0.00
February 527.20 171.89 355.32 1206.90 98.39 0.00 0.00 0.00
March 359.79 48.32 311.47 902.69 63.13 0.00 0.00 0.00
April 268.24 0.12 268.12 703.91 18.11 0.00 0.00 0.00
May 268.42 0.00 268.42 732.31 25.75 0.00 0.00 0.00
June 267.46 0.00 267.46 718.20 27.87 0.00 0.00 0.00
July 275.52 0.00 275.52 653.60 56.66 0.00 0.00 0.00
August 268.22 0.41 267.81 631.51 41.57 0.00 0.00 0.00
September 296.94 9.70 287.24 716.63 44.74 0.00 0.00 0.00
October 388.48 61.94 326.54 870.54 60.55 0.00 0.00 0.00
November 505.16 154.12 351.04 1096.96 85.42 0.00 0.00 0.00
December 620.54 264.02 356.53 1305.65 144.34 0.00 0.00 0.00
                 
Annual Sum or Average 388.36 80.48 307.88 903.93 66.00 0.00 0.00 0.00
Minimum of Months 267.46 0.00 267.46 631.51 18.11 0.00 0.00 0.00
Maximum of Months 620.86 264.02 361.83 1325.32 144.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FRONT_ENTRY_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.73 53.29 74.44 240.85 45.66 0.00 0.00 0.00
February 108.47 35.36 73.10 213.04 41.41 0.00 0.00 0.00
March 74.02 9.94 64.08 149.92 32.41 0.00 0.00 0.00
April 55.19 0.02 55.16 106.76 17.67 11.83 0.00 0.00
May 55.22 0.00 55.22 110.17 17.75 130.17 0.00 0.00
June 55.03 0.00 55.03 108.49 19.47 51.83 0.00 0.00
July 56.68 0.00 56.68 106.99 24.19 5.33 0.00 0.00
August 55.18 0.09 55.10 101.82 21.10 22.33 0.00 0.00
September 61.09 2.00 59.10 117.94 22.82 13.33 0.00 0.00
October 79.93 12.74 67.18 151.54 26.75 22.17 0.00 0.00
November 103.93 31.71 72.22 196.67 34.17 5.33 0.00 0.00
December 127.67 54.32 73.35 238.46 48.48 10.83 0.00 0.00
                 
Annual Sum or Average 79.90 16.56 63.34 153.30 29.29 273.17 0.00 0.00
Minimum of Months 55.03 0.00 55.03 101.82 17.67 0.00 0.00 0.00
Maximum of Months 127.73 54.32 74.44 240.85 48.48 130.17 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.119668E+09 57316697.66 62350935.04 0.227710E+09 38763457.69
February 0.125275E+09 65301437.78 59973345.77 0.240016E+09 36215712.20
March 0.160966E+09 94733381.88 66232667.26 0.308627E+09 33189116.93
April 0.157707E+09 88741763.38 68965002.29 0.304707E+09 22355298.68
May 0.136122E+09 59444700.43 76677047.89 0.269737E+09 18945529.98
June 0.142444E+09 70754060.03 71690031.69 0.280161E+09 18201532.55
July 0.123689E+09 41203502.75 82485341.86 0.241097E+09 24667651.07
August 0.136747E+09 58970423.89 77776561.69 0.256946E+09 23147463.95
September 0.122192E+09 47643267.57 74548473.43 0.237895E+09 21327078.89
October 0.115306E+09 40987029.18 74318550.75 0.217315E+09 23329213.59
November 0.106641E+09 40583404.70 66057729.50 0.203748E+09 28518237.50
December 0.111032E+09 49898437.62 61133744.05 0.211577E+09 40197888.06
           
Annual Sum or Average 0.155779E+10 0.715578E+09 0.842209E+09 0.299954E+10 0.328858E+09
Minimum of Months 0.106641E+09 40583404.70 59973345.77 0.203748E+09 18201532.55
Maximum of Months 0.160966E+09 94733381.88 82485341.86 0.308627E+09 40197888.06



Table of Contents

Report: WindowEnergyReportMonthly

For: POINT_OF_SALE_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.166291E+10 0.693785E+09 0.969128E+09 0.356785E+10 0.346186E+09
February 0.127541E+10 0.415832E+09 0.859582E+09 0.293664E+10 0.246913E+09
March 0.963655E+09 0.129419E+09 0.834236E+09 0.243516E+10 0.181774E+09
April 0.695277E+09 312113.29 0.694965E+09 0.183787E+10 54043777.94
May 0.718942E+09 0.00 0.718942E+09 0.197426E+10 73318908.02
June 0.693246E+09 0.00 0.693246E+09 0.187662E+10 76990981.68
July 0.737953E+09 0.00 0.737953E+09 0.176740E+10 0.158871E+09
August 0.718403E+09 1110301.74 0.717293E+09 0.170744E+10 0.118970E+09
September 0.769667E+09 25137800.16 0.744529E+09 0.187390E+10 0.122332E+09
October 0.104051E+10 0.165901E+09 0.874612E+09 0.234588E+10 0.170410E+09
November 0.130936E+10 0.399468E+09 0.909895E+09 0.285954E+10 0.228036E+09
December 0.166206E+10 0.707138E+09 0.954924E+09 0.351437E+10 0.394640E+09
           
Annual Sum or Average 0.122474E+11 0.253810E+10 0.970930E+10 0.286969E+11 0.217249E+10
Minimum of Months 0.693246E+09 0.00 0.693246E+09 0.170744E+10 54043777.94
Maximum of Months 0.166291E+10 0.707138E+09 0.969128E+09 0.356785E+10 0.394640E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FRONT_RETAIL_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.166291E+10 0.693785E+09 0.969128E+09 0.354972E+10 0.336731E+09
February 0.127541E+10 0.415832E+09 0.859582E+09 0.291972E+10 0.238031E+09
March 0.963655E+09 0.129419E+09 0.834236E+09 0.241777E+10 0.169089E+09
April 0.695277E+09 312113.29 0.694965E+09 0.182455E+10 46936674.86
May 0.718942E+09 0.00 0.718942E+09 0.196141E+10 68966551.09
June 0.693246E+09 0.00 0.693246E+09 0.186158E+10 72240222.52
July 0.737953E+09 0.00 0.737953E+09 0.175060E+10 0.151762E+09
August 0.718403E+09 1110301.74 0.717293E+09 0.169144E+10 0.111337E+09
September 0.769667E+09 25137800.16 0.744529E+09 0.185751E+10 0.115970E+09
October 0.104051E+10 0.165901E+09 0.874612E+09 0.233166E+10 0.162166E+09
November 0.130936E+10 0.399468E+09 0.909895E+09 0.284331E+10 0.221413E+09
December 0.166206E+10 0.707138E+09 0.954924E+09 0.349704E+10 0.386590E+09
           
Annual Sum or Average 0.122474E+11 0.253810E+10 0.970930E+10 0.285063E+11 0.208123E+10
Minimum of Months 0.693246E+09 0.00 0.693246E+09 0.169144E+10 46936674.86
Maximum of Months 0.166291E+10 0.707138E+09 0.969128E+09 0.354972E+10 0.386590E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FRONT_ENTRY_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.342123E+09 0.142738E+09 0.199385E+09 0.645090E+09 0.122296E+09
February 0.262400E+09 85552196.45 0.176848E+09 0.515390E+09 0.100189E+09
March 0.198259E+09 26626363.47 0.171633E+09 0.401550E+09 86797071.07
April 0.143044E+09 64213.40 0.142980E+09 0.276714E+09 45800421.02
May 0.147913E+09 0.00 0.147913E+09 0.295092E+09 47542084.31
June 0.142626E+09 0.00 0.142626E+09 0.281215E+09 50460195.06
July 0.151824E+09 0.00 0.151824E+09 0.286574E+09 64790227.19
August 0.147802E+09 228430.69 0.147573E+09 0.272715E+09 56503540.21
September 0.158349E+09 5171787.92 0.153177E+09 0.305689E+09 59153426.98
October 0.214072E+09 34132090.32 0.179940E+09 0.405876E+09 71659697.49
November 0.269385E+09 82185629.58 0.187199E+09 0.509766E+09 88567306.25
December 0.341948E+09 0.145485E+09 0.196463E+09 0.638692E+09 0.129853E+09
           
Annual Sum or Average 0.251974E+10 0.522183E+09 0.199756E+10 0.483436E+10 0.923611E+09
Minimum of Months 0.142626E+09 0.00 0.142626E+09 0.272715E+09 45800421.02
Maximum of Months 0.342123E+09 0.145485E+09 0.199385E+09 0.645090E+09 0.129853E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1360.27 231.56 714.86 342.39 372.47 0.00 0.00
February 1587.41 239.52 828.54 431.89 396.65 0.00 0.00
March 1843.65 198.26 961.57 565.91 395.66 0.00 0.00
April 1880.91 138.00 973.50 547.79 425.71 0.00 0.00
May 1611.33 113.18 813.15 355.11 458.05 0.00 0.00
June 1729.39 112.36 879.28 436.75 442.53 0.00 0.00
July 1440.24 147.36 738.88 246.14 492.74 0.00 0.00
August 1534.92 138.28 816.89 352.27 464.62 0.00 0.00
September 1468.49 131.65 754.27 294.09 460.18 0.00 0.00
October 1298.18 139.36 688.80 244.84 443.96 0.00 0.00
November 1257.70 176.04 658.28 250.51 407.76 0.00 0.00
December 1263.90 240.13 663.27 298.08 365.20 0.00 0.00
               
Annual Sum or Average 1521.84 166.85 790.35 363.05 427.30 0.00 0.00
Minimum of Months 1257.70 112.36 658.28 244.84 365.20 0.00 0.00
Maximum of Months 1880.91 240.13 973.50 565.91 492.74 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1332.08 129.25 620.86 259.03 361.83 0.00 0.00
February 1213.89 102.06 527.20 171.89 355.32 0.00 0.00
March 909.19 67.87 359.79 48.32 311.47 0.00 0.00
April 709.06 20.85 268.24 0.12 268.12 0.00 0.00
May 737.11 27.37 268.42 0.00 268.42 0.00 0.00
June 724.01 29.70 267.46 0.00 267.46 0.00 0.00
July 659.87 59.32 275.52 0.00 275.52 0.00 0.00
August 637.48 44.42 268.22 0.41 267.81 0.00 0.00
September 722.96 47.20 296.94 9.70 287.24 0.00 0.00
October 875.85 63.62 388.48 61.94 326.54 0.00 0.00
November 1103.22 87.98 505.16 154.12 351.04 0.00 0.00
December 1312.12 147.34 620.54 264.02 356.53 0.00 0.00
               
Annual Sum or Average 909.97 68.89 388.36 80.48 307.88 0.00 0.00
Minimum of Months 637.48 20.85 267.46 0.00 267.46 0.00 0.00
Maximum of Months 1332.08 147.34 620.86 264.02 361.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1325.32 125.72 620.86 259.03 361.83 0.00 0.00
February 1206.90 98.39 527.20 171.89 355.32 0.00 0.00
March 902.69 63.13 359.79 48.32 311.47 0.00 0.00
April 703.91 18.11 268.24 0.12 268.12 0.00 0.00
May 732.31 25.75 268.42 0.00 268.42 0.00 0.00
June 718.20 27.87 267.46 0.00 267.46 0.00 0.00
July 653.60 56.66 275.52 0.00 275.52 0.00 0.00
August 631.51 41.57 268.22 0.41 267.81 0.00 0.00
September 716.63 44.74 296.94 9.70 287.24 0.00 0.00
October 870.54 60.55 388.48 61.94 326.54 0.00 0.00
November 1096.96 85.42 505.16 154.12 351.04 0.00 0.00
December 1305.65 144.34 620.54 264.02 356.53 0.00 0.00
               
Annual Sum or Average 903.93 66.00 388.36 80.48 307.88 0.00 0.00
Minimum of Months 631.51 18.11 267.46 0.00 267.46 0.00 0.00
Maximum of Months 1325.32 144.34 620.86 264.02 361.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 240.85 45.66 127.73 53.29 74.44 0.00 0.00
February 213.04 41.41 108.47 35.36 73.10 0.00 0.00
March 149.92 32.41 74.02 9.94 64.08 0.00 0.00
April 106.76 17.67 55.19 0.02 55.16 0.00 0.00
May 110.17 17.75 55.22 0.00 55.22 0.00 0.00
June 108.49 19.47 55.03 0.00 55.03 0.00 0.00
July 106.99 24.19 56.68 0.00 56.68 0.00 0.00
August 101.82 21.10 55.18 0.09 55.10 0.00 0.00
September 117.94 22.82 61.09 2.00 59.10 0.00 0.00
October 151.54 26.75 79.93 12.74 67.18 0.00 0.00
November 196.67 34.17 103.93 31.71 72.22 0.00 0.00
December 238.46 48.48 127.67 54.32 73.35 0.00 0.00
               
Annual Sum or Average 153.30 29.29 79.90 16.56 63.34 0.00 0.00
Minimum of Months 101.82 17.67 55.03 0.00 55.03 0.00 0.00
Maximum of Months 240.85 48.48 127.73 54.32 74.44 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.364336E+10 0.620215E+09 0.191468E+10 0.917067E+09 0.997615E+09 0.00 0.00
February 0.384026E+10 0.579451E+09 0.200440E+10 0.104482E+10 0.959574E+09 0.00 0.00
March 0.493804E+10 0.531026E+09 0.257546E+10 0.151573E+10 0.105972E+10 0.00 0.00
April 0.487531E+10 0.357685E+09 0.252331E+10 0.141987E+10 0.110344E+10 0.00 0.00
May 0.431579E+10 0.303128E+09 0.217795E+10 0.951115E+09 0.122683E+10 0.00 0.00
June 0.448258E+10 0.291225E+09 0.227911E+10 0.113206E+10 0.114704E+10 0.00 0.00
July 0.385755E+10 0.394682E+09 0.197902E+10 0.659256E+09 0.131977E+10 0.00 0.00
August 0.411114E+10 0.370359E+09 0.218795E+10 0.943527E+09 0.124442E+10 0.00 0.00
September 0.380632E+10 0.341233E+09 0.195507E+10 0.762292E+09 0.119278E+10 0.00 0.00
October 0.347704E+10 0.373267E+09 0.184489E+10 0.655792E+09 0.118910E+10 0.00 0.00
November 0.325997E+10 0.456292E+09 0.170626E+10 0.649334E+09 0.105692E+10 0.00 0.00
December 0.338523E+10 0.643166E+09 0.177651E+10 0.798375E+09 0.978140E+09 0.00 0.00
               
Annual Sum or Average 0.479926E+11 0.526173E+10 0.249246E+11 0.114492E+11 0.134754E+11 0.00 0.00
Minimum of Months 0.325997E+10 0.291225E+09 0.170626E+10 0.649334E+09 0.959574E+09 0.00 0.00
Maximum of Months 0.493804E+10 0.643166E+09 0.257546E+10 0.151573E+10 0.131977E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.356785E+10 0.346186E+09 0.166291E+10 0.693785E+09 0.969128E+09 0.00 0.00
February 0.293664E+10 0.246913E+09 0.127541E+10 0.415832E+09 0.859582E+09 0.00 0.00
March 0.243516E+10 0.181774E+09 0.963655E+09 0.129419E+09 0.834236E+09 0.00 0.00
April 0.183787E+10 54043777.94 0.695277E+09 312113.29 0.694965E+09 0.00 0.00
May 0.197426E+10 73318908.02 0.718942E+09 0.00 0.718942E+09 0.00 0.00
June 0.187662E+10 76990981.68 0.693246E+09 0.00 0.693246E+09 0.00 0.00
July 0.176740E+10 0.158871E+09 0.737953E+09 0.00 0.737953E+09 0.00 0.00
August 0.170744E+10 0.118970E+09 0.718403E+09 1110301.74 0.717293E+09 0.00 0.00
September 0.187390E+10 0.122332E+09 0.769667E+09 25137800.16 0.744529E+09 0.00 0.00
October 0.234588E+10 0.170410E+09 0.104051E+10 0.165901E+09 0.874612E+09 0.00 0.00
November 0.285954E+10 0.228036E+09 0.130936E+10 0.399468E+09 0.909895E+09 0.00 0.00
December 0.351437E+10 0.394640E+09 0.166206E+10 0.707138E+09 0.954924E+09 0.00 0.00
               
Annual Sum or Average 0.286969E+11 0.217249E+10 0.122474E+11 0.253810E+10 0.970930E+10 0.00 0.00
Minimum of Months 0.170744E+10 54043777.94 0.693246E+09 0.00 0.693246E+09 0.00 0.00
Maximum of Months 0.356785E+10 0.394640E+09 0.166291E+10 0.707138E+09 0.969128E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.354972E+10 0.336731E+09 0.166291E+10 0.693785E+09 0.969128E+09 0.00 0.00
February 0.291972E+10 0.238031E+09 0.127541E+10 0.415832E+09 0.859582E+09 0.00 0.00
March 0.241777E+10 0.169089E+09 0.963655E+09 0.129419E+09 0.834236E+09 0.00 0.00
April 0.182455E+10 46936674.86 0.695277E+09 312113.29 0.694965E+09 0.00 0.00
May 0.196141E+10 68966551.09 0.718942E+09 0.00 0.718942E+09 0.00 0.00
June 0.186158E+10 72240222.52 0.693246E+09 0.00 0.693246E+09 0.00 0.00
July 0.175060E+10 0.151762E+09 0.737953E+09 0.00 0.737953E+09 0.00 0.00
August 0.169144E+10 0.111337E+09 0.718403E+09 1110301.74 0.717293E+09 0.00 0.00
September 0.185751E+10 0.115970E+09 0.769667E+09 25137800.16 0.744529E+09 0.00 0.00
October 0.233166E+10 0.162166E+09 0.104051E+10 0.165901E+09 0.874612E+09 0.00 0.00
November 0.284331E+10 0.221413E+09 0.130936E+10 0.399468E+09 0.909895E+09 0.00 0.00
December 0.349704E+10 0.386590E+09 0.166206E+10 0.707138E+09 0.954924E+09 0.00 0.00
               
Annual Sum or Average 0.285063E+11 0.208123E+10 0.122474E+11 0.253810E+10 0.970930E+10 0.00 0.00
Minimum of Months 0.169144E+10 46936674.86 0.693246E+09 0.00 0.693246E+09 0.00 0.00
Maximum of Months 0.354972E+10 0.386590E+09 0.166291E+10 0.707138E+09 0.969128E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.645090E+09 0.122296E+09 0.342123E+09 0.142738E+09 0.199385E+09 0.00 0.00
February 0.515390E+09 0.100189E+09 0.262400E+09 85552196.45 0.176848E+09 0.00 0.00
March 0.401550E+09 86797071.07 0.198259E+09 26626363.47 0.171633E+09 0.00 0.00
April 0.276714E+09 45800421.02 0.143044E+09 64213.40 0.142980E+09 0.00 0.00
May 0.295092E+09 47542084.31 0.147913E+09 0.00 0.147913E+09 0.00 0.00
June 0.281215E+09 50460195.06 0.142626E+09 0.00 0.142626E+09 0.00 0.00
July 0.286574E+09 64790227.19 0.151824E+09 0.00 0.151824E+09 0.00 0.00
August 0.272715E+09 56503540.21 0.147802E+09 228430.69 0.147573E+09 0.00 0.00
September 0.305689E+09 59153426.98 0.158349E+09 5171787.92 0.153177E+09 0.00 0.00
October 0.405876E+09 71659697.49 0.214072E+09 34132090.32 0.179940E+09 0.00 0.00
November 0.509766E+09 88567306.25 0.269385E+09 82185629.58 0.187199E+09 0.00 0.00
December 0.638692E+09 0.129853E+09 0.341948E+09 0.145485E+09 0.196463E+09 0.00 0.00
               
Annual Sum or Average 0.483436E+10 0.923611E+09 0.251974E+10 0.522183E+09 0.199756E+10 0.00 0.00
Minimum of Months 0.272715E+09 45800421.02 0.142626E+09 0.00 0.142626E+09 0.00 0.00
Maximum of Months 0.645090E+09 0.129853E+09 0.342123E+09 0.145485E+09 0.199385E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 26.42 22.38 20.70 2.25 18.66 103.85 146.57 0.01
February 27.50 22.91 21.01 2.37 18.54 110.59 164.59 0.00
March 28.33 23.63 21.77 3.67 19.85 110.33 194.39 0.01
April 29.15 25.37 24.04 2.98 21.51 118.69 185.56 0.03
May 29.01 26.53 25.72 3.19 23.00 127.71 124.87 0.08
June 28.86 26.50 25.74 3.10 22.78 123.38 156.09 0.05
July 27.25 24.29 23.20 2.32 21.53 137.39 88.28 0.02
August 27.54 25.86 25.31 3.22 21.55 129.55 122.00 0.07
September 27.58 25.59 24.93 2.22 22.01 128.30 103.37 0.04
October 26.89 25.07 24.46 2.18 21.39 123.79 92.41 0.11
November 26.68 24.14 23.20 1.94 20.29 113.70 103.30 0.02
December 25.97 22.85 21.57 2.00 18.63 101.83 131.96 0.00
                 
Annual Sum or Average 27.59 24.60 23.48 2.62 20.82 119.14 134.17 0.04
Minimum of Months 25.97 22.38 20.70 1.94 18.54 101.83 88.28 0.00
Maximum of Months 29.15 26.53 25.74 3.67 23.00 137.39 194.39 0.11



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 34.10 04-JAN-12:00 23.67 19.40 5.00 24.66 266.50 576.50
February 35.00 21-FEB-13:00 22.02 16.00 2.10 24.16 230.00 672.50
March 36.40 21-MAR-12:00 23.01 17.00 5.00 26.97 269.50 658.50
April 35.50 01-APR-13:00 26.96 24.00 2.50 27.14 295.50 519.50
May 37.60 06-MAY-12:00 26.43 22.60 4.00 29.39 317.00 525.50
June 36.00 12-JUN-14:00 27.60 25.00 4.00 28.43 235.00 472.00
July 33.20 15-JUL-15:00 25.63 23.00 2.00 27.95 219.00 181.00
August 34.00 10-AUG-13:00 27.86 26.00 5.00 26.65 344.50 278.50
September 34.00 06-SEP-13:00 26.51 24.00 4.00 25.00 258.00 581.50
October 33.00 04-OCT-13:00 26.23 24.00 4.00 25.16 303.00 428.50
November 34.30 18-NOV-12:00 25.34 22.20 3.00 25.49 289.50 511.50
December 33.00 07-DEC-13:00 23.23 19.00 3.00 22.98 215.00 596.00
                 
Annual Sum or Average                
Minimum of Months 33.00   22.02 16.00 2.00 22.98 215.00 181.00
Maximum of Months 37.60   27.86 26.00 5.00 29.39 344.50 672.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 18.70 23-JAN-05:00 16.92 16.00 2.00 7.75 0.00 0.00
February 20.30 21-FEB-09:00 19.04 18.40 2.00 10.50 258.50 564.00
March 22.00 03-MAR-05:00 19.94 19.00 3.00 13.35 0.00 0.00
April 22.90 14-APR-15:00 22.90 22.90 3.00 14.65 199.50 264.50
May 22.00 10-MAY-19:00 22.00 22.00 2.00 18.28 0.00 0.00
June 23.00 20-JUN-23:00 23.00 23.00 2.00 19.35 0.00 0.00
July 23.00 13-JUL-04:00 22.27 22.00 0.00 13.91 0.00 0.00
August 22.00 20-AUG-10:00 22.00 22.00 5.00 18.28 430.50 41.50
September 22.90 19-SEP-03:00 22.78 22.78 0.00 21.27 0.00 0.00
October 22.50 23-OCT-04:00 22.50 22.50 2.80 18.82 0.00 0.00
November 20.00 25-NOV-04:00 18.63 18.00 2.00 10.69 0.00 0.00
December 18.00 21-DEC-04:00 17.36 17.00 3.00 9.13 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 18.00   16.92 16.00 0.00 7.75 0.00 0.00
Maximum of Months 23.00   23.00 23.00 5.00 21.27 430.50 564.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 25.53 12-JAN-12:00 32.40 23.10 2.00 25.00 353.00 347.00
February 26.17 14-FEB-15:00 32.30 24.20 2.00 25.16 200.00 199.00
March 26.28 27-MAR-12:00 34.20 23.60 4.00 26.32 326.00 535.00
April 27.93 10-APR-16:49 31.52 26.85 4.08 27.70 110.67 57.00
May 29.00 28-MAY-20:00 29.00 29.00 3.00 22.47 0.00 0.00
June 30.11 15-JUN-09:00 33.20 29.20 5.00 26.48 320.50 421.00
July 26.43 20-JUL-14:00 32.80 24.20 1.00 26.65 305.00 253.00
August 28.81 14-AUG-16:00 32.00 28.00 1.00 25.16 107.50 223.00
September 30.06 30-SEP-10:00 32.80 29.40 3.00 25.66 398.00 359.50
October 27.36 16-OCT-14:00 31.50 26.00 3.00 24.16 239.00 346.50
November 27.56 10-NOV-12:00 31.00 26.40 6.00 28.11 388.00 95.50
December 26.86 03-DEC-12:00 31.50 25.30 1.00 23.49 301.00 468.50
                 
Annual Sum or Average                
Minimum of Months 25.53   29.00 23.10 1.00 22.47 0.00 0.00
Maximum of Months 30.11   34.20 29.40 6.00 28.11 398.00 535.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 24.20 09-JAN-21:00 26.50 24.77 4.00 25.16 0.00 0.00
February 24.40 15-FEB-18:00 28.30 25.33 4.00 20.75 0.00 0.00
March 25.30 28-MAR-06:00 27.20 25.72 3.00 19.87 103.00 28.00
April 27.00 10-APR-17:00 30.50 27.87 4.50 25.00 20.00 20.50
May 29.00 28-MAY-20:00 29.00 29.00 3.00 22.47 0.00 0.00
June 29.20 15-JUN-09:00 33.20 30.11 5.00 26.48 320.50 421.00
July 26.00 10-JUL-14:00 26.50 26.11 2.30 23.49 286.00 36.50
August 28.00 02-AUG-10:00 31.00 28.65 4.00 24.16 419.00 195.50
September 29.40 30-SEP-10:00 32.80 30.06 3.00 25.66 398.00 359.50
October 26.50 16-OCT-08:00 29.00 27.04 2.50 21.78 300.00 326.00
November 26.40 10-NOV-12:00 31.00 27.56 6.00 28.11 388.00 95.50
December 26.00 10-DEC-17:00 29.00 26.74 3.00 21.78 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 24.20   26.50 24.77 2.30 19.87 0.00 0.00
Maximum of Months 29.40   33.20 30.11 6.00 28.11 419.00 421.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 29.71 38.82 0.00
February 18.00 13.00 16.00 29.90 44.34 0.00
March 18.00 13.00 16.00 30.35 50.49 0.00
April 18.00 13.00 16.00 30.97 51.18 0.00
May 18.00 13.00 16.00 31.58 43.47 0.00
June 18.00 13.00 16.00 32.02 46.77 0.00
July 18.00 13.00 16.00 32.16 39.95 0.00
August 18.00 13.00 16.00 31.97 43.65 0.00
September 18.00 13.00 16.00 31.50 40.53 0.00
October 18.00 13.00 16.00 30.87 37.35 0.00
November 18.00 13.00 16.00 30.27 35.77 0.00
December 18.00 13.00 16.00 29.84 36.19 0.00
             
Annual Sum or Average 18.00 13.00 16.00 30.93 42.35 0.00
Minimum of Months 18.00 13.00 16.00 29.71 35.77 0.00
Maximum of Months 18.00 13.00 16.00 32.16 51.18 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.154093E+10 -0.143296E+10 0.00 0.00 744.00 0.00 -107971198.3 59.95 0.00 0.00
February 0.139431E+10 -0.129680E+10 0.00 0.00 672.00 0.00 -97505538.4 59.95 0.00 0.00
March 0.155696E+10 -0.144904E+10 0.00 0.00 744.00 0.00 -107918383.5 59.95 0.00 0.00
April 0.145333E+10 -0.134893E+10 0.00 0.00 720.00 0.00 -104403250.6 59.95 0.00 0.00
May 0.147459E+10 -0.136673E+10 0.00 0.00 744.00 0.00 -107859212.2 59.95 0.00 0.00
June 0.142507E+10 -0.132073E+10 0.00 0.00 720.00 0.00 -104341470.9 59.95 0.00 0.00
July 0.142610E+10 -0.131822E+10 0.00 0.00 744.00 0.00 -107882864.4 59.95 0.00 0.00
August 0.147792E+10 -0.137002E+10 0.00 0.00 744.00 0.00 -107904966.1 59.95 0.00 0.00
September 0.142928E+10 -0.132484E+10 0.00 0.00 720.00 0.00 -104436536.7 59.95 0.00 0.00
October 0.148588E+10 -0.137794E+10 0.00 0.00 744.00 0.00 -107940151.6 59.95 0.00 0.00
November 0.145962E+10 -0.135515E+10 0.00 0.00 720.00 0.00 -104474756.9 59.95 0.00 0.00
December 0.153622E+10 -0.142825E+10 0.00 0.00 744.00 0.00 -107974952.0 59.95 0.00 0.00
                     
Annual Sum or Average 0.176602E+11 -0.163896E+11 0.00 0.00 8760.00 0.00 -0.127061E+10 59.95 0.00 0.00
Minimum of Months 0.139431E+10 -0.144904E+10 0.00 0.00 672.00 0.00 -107974952.0 59.95 0.00 0.00
Maximum of Months 0.155696E+10 -0.129680E+10 0.00 0.00 744.00 0.00 -97505538.4 59.95 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.70 0.50 01-JAN-11:20 450.03 8.11 0.00 84.00 379.02 6.60 0.00 55.33
February 321.17 0.67 0.50 01-FEB-09:39 2572.96 8.68 0.00 126.50 2229.28 7.14 0.00 116.67
March 361.17 0.69 0.50 01-MAR-09:20 377.96 9.58 0.00 44.00 312.76 7.90 0.00 34.17
April 358.33 0.69 0.50 01-APR-10:39 354.47 11.13 0.00 36.67 294.03 9.35 0.00 16.17
May 376.33 0.68 0.50 01-MAY-10:00 370.01 12.14 1.83 53.33 297.47 10.34 0.00 20.50
June 370.50 0.66 0.50 01-JUN-09:50 643.33 15.62 53.17 110.33 301.81 10.93 0.00 19.83
July 383.17 0.68 0.50 01-JUL-09:30 359.51 12.13 0.00 69.17 301.13 10.46 0.00 32.00
August 369.33 0.67 0.50 01-AUG-10:09 372.28 11.80 0.00 71.00 311.08 10.10 0.00 25.33
September 357.83 0.68 0.50 01-SEP-08:00 383.91 10.38 0.00 103.17 311.89 8.82 0.00 52.33
October 356.83 0.67 0.50 01-OCT-09:30 661.51 9.65 0.00 167.33 415.38 8.05 0.00 75.67
November 337.67 0.69 0.50 01-NOV-09:20 903.18 8.81 0.00 121.17 919.86 7.21 0.00 66.00
December 349.33 0.70 0.50 01-DEC-09:20 341.36 7.98 0.00 54.33 287.76 6.47 0.00 38.33
                         
Annual Sum or Average 4292.33 0.68     628.60 10.57 55.00 1041.00 510.72 8.67 0.00 552.33
Minimum of Months 321.17 0.66 0.50   341.36 7.98 0.00 36.67 287.76 6.47 0.00 16.17
Maximum of Months 383.17 0.70 0.50   2572.96 15.62 53.17 167.33 2229.28 10.93 0.00 116.67



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FRONT_ENTRY UNIT HEATER HEATING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.297392E+11 0.219428E+11 41185.74 09-JAN-21:08 29102.95 0.00
February 0.00 0.00 0.306462E+11 0.229066E+11 40962.01 15-FEB-21:42 30050.23 0.00
March 0.00 0.00 0.381341E+11 0.282173E+11 40970.93 14-MAR-20:08 30330.21 0.00
April 0.00 0.00 0.430965E+11 0.303428E+11 41652.40 20-APR-20:10 27050.26 0.00
May 0.00 0.00 0.497475E+11 0.336028E+11 42206.43 21-MAY-18:10 25304.49 0.00
June 0.00 0.00 0.532246E+11 0.366102E+11 41814.73 28-JUN-20:10 26751.13 0.00
July 0.00 0.00 0.422746E+11 0.302705E+11 41284.04 07-JUL-20:08 29065.06 0.00
August 0.00 0.00 0.425805E+11 0.276997E+11 41729.79 21-AUG-20:10 27536.95 0.00
September 0.00 0.00 0.391483E+11 0.258307E+11 41754.13 17-SEP-18:10 27339.01 0.00
October 0.00 0.00 0.345823E+11 0.224147E+11 41773.24 25-OCT-20:10 27593.65 0.00
November 0.00 0.00 0.320454E+11 0.217368E+11 41662.62 11-NOV-19:10 27889.89 0.00
December 0.00 0.00 0.293284E+11 0.208210E+11 41730.08 09-DEC-22:10 27999.03 0.00
                 
Annual Sum or Average 0.00 0.00 0.464547E+12 0.322396E+12       0.00
Minimum of Months 0.00 0.00 0.293284E+11 0.208210E+11 40962.01   25304.49 0.00
Maximum of Months 0.00 0.00 0.532246E+11 0.366102E+11 42206.43   30330.21 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.127762E+12 0.793349E+11 211194.25 02-JAN-07:02 104184.43 0.00
February 0.00 0.00 0.127727E+12 0.799845E+11 210954.27 16-FEB-07:02 106972.02 0.00
March 0.00 0.00 0.156510E+12 0.974697E+11 210743.16 28-MAR-06:02 109355.59 0.00
April 0.00 0.00 0.172045E+12 0.979542E+11 212481.07 15-APR-06:02 103262.96 0.00
May 0.00 0.00 0.188386E+12 0.983053E+11 215805.92 19-MAY-06:02 93313.27 0.00
June 0.00 0.00 0.190216E+12 0.989206E+11 215807.14 29-JUN-06:02 94441.14 0.00
July 0.00 0.00 0.150892E+12 0.835906E+11 213059.57 01-JUL-06:02 100830.76 0.00
August 0.00 0.00 0.175096E+12 0.868934E+11 214887.45 05-AUG-06:02 94877.79 0.00
September 0.00 0.00 0.164911E+12 0.843696E+11 215305.02 17-SEP-08:62 96334.95 0.00
October 0.00 0.00 0.153760E+12 0.778052E+11 214635.36 12-OCT-06:02 95171.49 0.00
November 0.00 0.00 0.139852E+12 0.757873E+11 213685.91 12-NOV-09:02 102248.15 0.00
December 0.00 0.00 0.130225E+12 0.766952E+11 211839.35 10-DEC-09:02 107836.03 0.00
                 
Annual Sum or Average 0.00 0.00 0.187738E+13 0.103711E+13       0.00
Minimum of Months 0.00 0.00 0.127727E+12 0.757873E+11 210743.16   93313.27 0.00
Maximum of Months 0.00 0.00 0.190216E+12 0.989206E+11 215807.14   109355.59 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.278856E+11 0.205810E+11 27046.74 09-JAN-21:08 18698.12 0.00
February 0.00 0.00 0.263783E+11 0.194533E+11 26871.39 14-FEB-21:06 18996.95 0.00
March 0.00 0.00 0.290279E+11 0.207842E+11 26970.24 14-MAR-20:08 19060.74 0.00
April 0.00 0.00 0.287490E+11 0.189650E+11 27463.42 20-APR-20:10 16961.04 0.00
May 0.00 0.00 0.311690E+11 0.192710E+11 27798.41 28-MAY-18:10 16010.10 0.00
June 0.00 0.00 0.309742E+11 0.191316E+11 27723.76 03-JUN-21:08 16442.22 0.00
July 0.00 0.00 0.258945E+11 0.170176E+11 27309.40 07-JUL-20:08 17704.13 0.00
August 0.00 0.00 0.283924E+11 0.170588E+11 27556.61 06-AUG-18:10 17007.37 0.00
September 0.00 0.00 0.280592E+11 0.174984E+11 27409.00 19-SEP-20:08 17445.35 0.00
October 0.00 0.00 0.278597E+11 0.175581E+11 27403.71 14-OCT-21:08 17394.23 0.00
November 0.00 0.00 0.277841E+11 0.186848E+11 27269.62 12-NOV-19:08 17819.10 0.00
December 0.00 0.00 0.280545E+11 0.200555E+11 27384.65 09-DEC-22:08 17578.96 0.00
                 
Annual Sum or Average 0.00 0.00 0.340228E+12 0.226059E+12       0.00
Minimum of Months 0.00 0.00 0.258945E+11 0.170176E+11 26871.39   16010.10 0.00
Maximum of Months 0.00 0.00 0.311690E+11 0.207842E+11 27798.41   19060.74 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.244849E+11 0.173373E+11 24041.87 09-JAN-21:08 15470.37 0.00
February 0.00 0.00 0.233267E+11 0.165226E+11 23863.57 14-FEB-21:06 15858.90 0.00
March 0.00 0.00 0.253763E+11 0.173780E+11 23925.38 14-MAR-20:08 15851.02 0.00
April 0.00 0.00 0.252848E+11 0.158130E+11 24521.84 20-APR-20:10 13912.50 0.00
May 0.00 0.00 0.276372E+11 0.160969E+11 24716.14 28-MAY-18:10 13363.56 0.00
June 0.00 0.00 0.275861E+11 0.160566E+11 24721.42 28-JUN-20:10 13403.89 0.00
July 0.00 0.00 0.223928E+11 0.138908E+11 24325.94 07-JUL-20:08 14400.83 0.00
August 0.00 0.00 0.246891E+11 0.138566E+11 24510.37 03-AUG-20:08 13778.44 0.00
September 0.00 0.00 0.246392E+11 0.144452E+11 24514.72 18-SEP-20:10 13999.34 0.00
October 0.00 0.00 0.241544E+11 0.143002E+11 24395.79 25-OCT-20:08 14247.64 0.00
November 0.00 0.00 0.244380E+11 0.155821E+11 24235.84 30-NOV-21:08 14755.01 0.00
December 0.00 0.00 0.246478E+11 0.168332E+11 24289.31 09-DEC-22:08 14642.97 0.00
                 
Annual Sum or Average 0.00 0.00 0.298657E+12 0.188112E+12       0.00
Minimum of Months 0.00 0.00 0.223928E+11 0.138566E+11 23863.57   13363.56 0.00
Maximum of Months 0.00 0.00 0.276372E+11 0.173780E+11 24721.42   15858.90 0.00



Table of Contents

Report: FanReportMonthly

For: FRONT_ENTRY UNIT HEATER FAN

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 01-APR-00:03 0.00
May 0.00 0.00 0.00 01-MAY-00:03 0.00
June 0.00 0.00 0.00 01-JUN-00:03 0.00
July 0.00 0.00 0.00 01-JUL-00:05 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00
September 0.00 0.00 0.00 01-SEP-00:03 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.159434E+10 0.46 2035.58 02-JAN-21:08 0.87
February 0.150486E+10 0.47 2035.58 01-FEB-21:08 0.87
March 0.179534E+10 0.49 2035.58 01-MAR-21:08 0.87
April 0.194462E+10 0.51 2035.58 01-APR-04:03 0.87
May 0.225552E+10 0.54 2035.58 01-MAY-00:03 0.87
June 0.242150E+10 0.56 2035.58 01-JUN-01:23 0.87
July 0.193307E+10 0.51 2035.58 01-JUL-21:08 0.87
August 0.195272E+10 0.50 2035.58 01-AUG-00:03 0.87
September 0.178896E+10 0.50 2035.58 01-SEP-00:03 0.87
October 0.166875E+10 0.47 2035.58 01-OCT-03:43 0.87
November 0.157370E+10 0.47 2035.58 01-NOV-20:08 0.87
December 0.157846E+10 0.46 2035.58 01-DEC-00:23 0.87
           
Annual Sum or Average 0.220118E+11 0.50      
Minimum of Months 0.150486E+10 0.46 2035.58   0.87
Maximum of Months 0.242150E+10 0.56 2035.58   0.87



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.837750E+10 0.50 12721.06 01-JAN-09:02 1.36
February 0.792444E+10 0.52 12721.06 01-FEB-07:02 1.36
March 0.934603E+10 0.54 12721.06 01-MAR-07:02 1.36
April 0.987601E+10 0.56 12721.06 01-APR-05:03 1.36
May 0.106996E+11 0.58 12721.06 01-MAY-05:02 1.36
June 0.108657E+11 0.60 12721.06 01-JUN-05:03 1.36
July 0.889698E+10 0.52 12721.06 01-JUL-06:02 1.35
August 0.101061E+11 0.56 12721.06 01-AUG-06:02 1.35
September 0.952170E+10 0.55 12721.06 01-SEP-06:02 1.35
October 0.901560E+10 0.52 12721.06 01-OCT-08:62 1.35
November 0.842226E+10 0.51 12721.06 01-NOV-06:02 1.35
December 0.839174E+10 0.50 12721.06 01-DEC-07:03 1.36
           
Annual Sum or Average 0.111444E+12 0.54      
Minimum of Months 0.792444E+10 0.50 12721.06   1.35
Maximum of Months 0.108657E+11 0.60 12721.06   1.36



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.125551E+10 0.55 1265.47 02-JAN-21:08 0.90
February 0.118175E+10 0.56 1265.47 01-FEB-21:06 0.90
March 0.128192E+10 0.55 1265.47 01-MAR-21:08 0.90
April 0.123723E+10 0.55 1265.47 01-APR-04:03 0.90
May 0.132664E+10 0.56 1265.47 01-MAY-20:06 0.90
June 0.132057E+10 0.57 1265.47 01-JUN-01:23 0.90
July 0.112580E+10 0.52 1265.47 01-JUL-21:08 0.90
August 0.121840E+10 0.54 1265.47 01-AUG-00:03 0.90
September 0.120783E+10 0.55 1265.47 01-SEP-00:03 0.90
October 0.121024E+10 0.54 1265.47 01-OCT-03:43 0.90
November 0.121727E+10 0.55 1265.47 01-NOV-20:08 0.90
December 0.124937E+10 0.55 1265.47 01-DEC-21:06 0.90
           
Annual Sum or Average 0.148325E+11 0.55      
Minimum of Months 0.112580E+10 0.52 1265.47   0.90
Maximum of Months 0.132664E+10 0.57 1265.47   0.90



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.104607E+10 0.54 1060.42 02-JAN-21:08 0.90
February 0.989566E+09 0.56 1060.42 01-FEB-21:06 0.90
March 0.106336E+10 0.55 1060.42 01-MAR-21:08 0.90
April 0.102597E+10 0.54 1060.42 01-APR-04:03 0.90
May 0.110786E+10 0.55 1060.42 01-MAY-20:06 0.89
June 0.110640E+10 0.56 1060.42 01-JUN-01:23 0.90
July 0.927477E+09 0.51 1060.42 01-JUL-21:08 0.90
August 0.100490E+10 0.53 1060.42 01-AUG-00:03 0.90
September 0.100389E+10 0.54 1060.42 01-SEP-00:03 0.90
October 0.998070E+09 0.53 1060.42 01-OCT-03:43 0.90
November 0.101403E+10 0.54 1060.42 01-NOV-20:08 0.90
December 0.104169E+10 0.54 1060.42 01-DEC-21:06 0.90
           
Annual Sum or Average 0.123293E+11 0.54      
Minimum of Months 0.927477E+09 0.51 1060.42   0.89
Maximum of Months 0.110786E+10 0.56 1060.42   0.90



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.912223E+10 0.00 0.00
February 0.00 0.00 0.00 0.923719E+10 0.00 0.00
March 0.00 0.00 0.00 0.114020E+11 0.00 0.00
April 0.00 0.00 0.00 0.126808E+11 0.00 0.00
May 0.00 0.00 0.00 0.145279E+11 0.00 0.00
June 0.00 0.00 0.00 0.154850E+11 0.00 0.00
July 0.00 0.00 0.00 0.122445E+11 0.00 0.00
August 0.00 0.00 0.00 0.122753E+11 0.00 0.00
September 0.00 0.00 0.00 0.113297E+11 0.00 0.00
October 0.00 0.00 0.00 0.101094E+11 0.00 0.00
November 0.00 0.00 0.00 0.946367E+10 0.00 0.00
December 0.00 0.00 0.00 0.893762E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.136815E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.893762E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.154850E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.431472E+11 0.00 0.00
February 0.00 0.00 0.00 0.427199E+11 0.00 0.00
March 0.00 0.00 0.00 0.520339E+11 0.00 0.00
April 0.00 0.00 0.00 0.558777E+11 0.00 0.00
May 0.00 0.00 0.00 0.602493E+11 0.00 0.00
June 0.00 0.00 0.00 0.608105E+11 0.00 0.00
July 0.00 0.00 0.00 0.485880E+11 0.00 0.00
August 0.00 0.00 0.00 0.551933E+11 0.00 0.00
September 0.00 0.00 0.00 0.522010E+11 0.00 0.00
October 0.00 0.00 0.00 0.486605E+11 0.00 0.00
November 0.00 0.00 0.00 0.450372E+11 0.00 0.00
December 0.00 0.00 0.00 0.433092E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.607828E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.427199E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.608105E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.807153E+10 0.00 0.00
February 0.00 0.00 0.00 0.770611E+10 0.00 0.00
March 0.00 0.00 0.00 0.851510E+10 0.00 0.00
April 0.00 0.00 0.00 0.836460E+10 0.00 0.00
May 0.00 0.00 0.00 0.896958E+10 0.00 0.00
June 0.00 0.00 0.00 0.889397E+10 0.00 0.00
July 0.00 0.00 0.00 0.741754E+10 0.00 0.00
August 0.00 0.00 0.00 0.803679E+10 0.00 0.00
September 0.00 0.00 0.00 0.797177E+10 0.00 0.00
October 0.00 0.00 0.00 0.788186E+10 0.00 0.00
November 0.00 0.00 0.00 0.790364E+10 0.00 0.00
December 0.00 0.00 0.00 0.803204E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.977645E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.741754E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.896958E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.701336E+10 0.00 0.00
February 0.00 0.00 0.00 0.673735E+10 0.00 0.00
March 0.00 0.00 0.00 0.736251E+10 0.00 0.00
April 0.00 0.00 0.00 0.724858E+10 0.00 0.00
May 0.00 0.00 0.00 0.782206E+10 0.00 0.00
June 0.00 0.00 0.00 0.778729E+10 0.00 0.00
July 0.00 0.00 0.00 0.634764E+10 0.00 0.00
August 0.00 0.00 0.00 0.688929E+10 0.00 0.00
September 0.00 0.00 0.00 0.690148E+10 0.00 0.00
October 0.00 0.00 0.00 0.674655E+10 0.00 0.00
November 0.00 0.00 0.00 0.686572E+10 0.00 0.00
December 0.00 0.00 0.00 0.698112E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.847029E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.634764E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.782206E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.159434E+10 0.297392E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.150486E+10 0.306462E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.179534E+10 0.381341E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.194462E+10 0.430965E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.225552E+10 0.497475E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.242150E+10 0.532246E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.193307E+10 0.422746E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.195272E+10 0.425805E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.178896E+10 0.391483E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.166875E+10 0.345823E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.157370E+10 0.320454E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.157846E+10 0.293284E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.220118E+11 0.464547E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.150486E+10 0.293284E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.242150E+10 0.532246E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.837750E+10 0.127762E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.792444E+10 0.127727E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.934603E+10 0.156510E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.987601E+10 0.172045E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.106996E+11 0.188386E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.108657E+11 0.190216E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.889698E+10 0.150892E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.101061E+11 0.175096E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.952170E+10 0.164911E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.901560E+10 0.153760E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.842226E+10 0.139852E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.839174E+10 0.130225E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.111444E+12 0.187738E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.792444E+10 0.127727E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.108657E+11 0.190216E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.125551E+10 0.278856E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.118175E+10 0.263783E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.128192E+10 0.290279E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.123723E+10 0.287490E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132664E+10 0.311690E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132057E+10 0.309742E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.112580E+10 0.258945E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.121840E+10 0.283924E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.120783E+10 0.280592E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.121024E+10 0.278597E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.121727E+10 0.277841E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.124937E+10 0.280545E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.148325E+11 0.340228E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.112580E+10 0.258945E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.132664E+10 0.311690E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.104607E+10 0.244849E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.989566E+09 0.233267E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.106336E+10 0.253763E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.102597E+10 0.252848E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.110786E+10 0.276372E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.110640E+10 0.275861E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.927477E+09 0.223928E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.100490E+10 0.246891E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.100389E+10 0.246392E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.998070E+09 0.241544E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.101403E+10 0.244380E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.104169E+10 0.246478E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.123293E+11 0.298657E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.927477E+09 0.223928E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.110786E+10 0.276372E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.159434E+10 0.00 0.00 0.00 0.752789E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.150486E+10 0.00 0.00 0.00 0.773233E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.179534E+10 0.00 0.00 0.00 0.960668E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.194462E+10 0.00 0.00 0.00 0.107362E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.225552E+10 0.00 0.00 0.00 0.122723E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.242150E+10 0.00 0.00 0.00 0.130635E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.193307E+10 0.00 0.00 0.00 0.103114E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.195272E+10 0.00 0.00 0.00 0.103226E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.178896E+10 0.00 0.00 0.00 0.954075E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.166875E+10 0.00 0.00 0.00 0.844069E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.157370E+10 0.00 0.00 0.00 0.788996E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.157846E+10 0.00 0.00 0.00 0.735916E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.220118E+11 0.00 0.00 0.00 0.114803E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.150486E+10 0.00 0.00 0.00 0.735916E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.242150E+10 0.00 0.00 0.00 0.130635E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.837750E+10 0.00 0.00 0.00 0.347697E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.792444E+10 0.00 0.00 0.00 0.347955E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.934603E+10 0.00 0.00 0.00 0.426879E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.987601E+10 0.00 0.00 0.00 0.460017E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.106996E+11 0.00 0.00 0.00 0.495497E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.108657E+11 0.00 0.00 0.00 0.499448E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.889698E+10 0.00 0.00 0.00 0.396910E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.101061E+11 0.00 0.00 0.00 0.450872E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.952170E+10 0.00 0.00 0.00 0.426793E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.901560E+10 0.00 0.00 0.00 0.396449E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.842226E+10 0.00 0.00 0.00 0.366149E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.839174E+10 0.00 0.00 0.00 0.349174E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.111444E+12 0.00 0.00 0.00 0.496384E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.792444E+10 0.00 0.00 0.00 0.347697E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.108657E+11 0.00 0.00 0.00 0.499448E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.125551E+10 0.00 0.00 0.00 0.681602E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.118175E+10 0.00 0.00 0.00 0.652436E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.128192E+10 0.00 0.00 0.00 0.723318E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.123723E+10 0.00 0.00 0.00 0.712738E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132664E+10 0.00 0.00 0.00 0.764294E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132057E+10 0.00 0.00 0.00 0.757340E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.112580E+10 0.00 0.00 0.00 0.629174E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.121840E+10 0.00 0.00 0.00 0.681839E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.120783E+10 0.00 0.00 0.00 0.676394E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.121024E+10 0.00 0.00 0.00 0.667162E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.121727E+10 0.00 0.00 0.00 0.668636E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.124937E+10 0.00 0.00 0.00 0.678266E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.148325E+11 0.00 0.00 0.00 0.829320E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.112580E+10 0.00 0.00 0.00 0.629174E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.132664E+10 0.00 0.00 0.00 0.764294E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.104607E+10 0.00 0.00 0.00 0.596729E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.989566E+09 0.00 0.00 0.00 0.574778E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.106336E+10 0.00 0.00 0.00 0.629914E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.102597E+10 0.00 0.00 0.00 0.622261E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.110786E+10 0.00 0.00 0.00 0.671420E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.110640E+10 0.00 0.00 0.00 0.668089E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.927477E+09 0.00 0.00 0.00 0.542016E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.100490E+10 0.00 0.00 0.00 0.588440E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.100389E+10 0.00 0.00 0.00 0.589759E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.998070E+09 0.00 0.00 0.00 0.574848E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.101403E+10 0.00 0.00 0.00 0.585169E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.104169E+10 0.00 0.00 0.00 0.593943E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.123293E+11 0.00 0.00 0.00 0.723737E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.927477E+09 0.00 0.00 0.00 0.542016E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.110786E+10 0.00 0.00 0.00 0.671420E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.916732E+10 0.00 0.00 2055156.79 0.00 0.00 0.00 0.25
February 0.00 0.946078E+10 0.00 0.00 8068764.51 0.00 0.00 0.00 0.26
March 0.00 0.119640E+11 0.00 0.00 5152034.95 0.00 0.00 0.00 0.26
April 0.00 0.151061E+11 0.00 0.00 9382502.13 0.00 0.00 0.00 0.27
May 0.00 0.184051E+11 0.00 0.00 3862462.00 0.00 0.00 0.00 0.28
June 0.00 0.188114E+11 0.00 0.00 3787513.76 0.00 0.00 0.00 0.28
July 0.00 0.135523E+11 0.00 0.00 4841664.36 0.00 0.00 0.00 0.27
August 0.00 0.163119E+11 0.00 0.00 15569220.06 0.00 0.00 0.00 0.27
September 0.00 0.149622E+11 0.00 0.00 5412259.30 0.00 0.00 0.00 0.26
October 0.00 0.135320E+11 0.00 0.00 9746786.77 0.00 0.00 0.00 0.25
November 0.00 0.116194E+11 0.00 0.00 4992062.01 0.00 0.00 0.00 0.25
December 0.00 0.975858E+10 0.00 0.00 10093637.98 0.00 0.00 0.00 0.25
                   
Annual Sum or Average 0.00 0.162651E+12 0.00 0.00 82964064.62 0.00 0.00 0.00 0.26
Minimum of Months 0.00 0.916732E+10 0.00 0.00 2055156.79 0.00 0.00 0.00 0.25
Maximum of Months 0.00 0.188114E+11 0.00 0.00 15569220.06 0.00 0.00 0.00 0.28



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.116430E+09 0.537790E+11 0.00 1522709.58 0.107668E+10 0.00 47772125.20 0.00 0.43
February 6730166.74 0.556903E+11 0.00 1289404.25 0.111415E+10 0.00 9022579.91 0.00 0.43
March 0.00 0.703405E+11 0.00 0.00 0.149073E+10 0.00 0.00 0.00 0.44
April 0.00 0.869814E+11 0.00 0.00 0.156880E+10 0.00 0.00 0.00 0.44
May 0.00 0.102791E+12 0.00 0.00 0.187280E+10 0.00 0.00 0.00 0.44
June 0.00 0.103633E+12 0.00 0.00 0.184821E+10 0.00 0.00 0.00 0.44
July 0.00 0.728915E+11 0.00 0.00 0.177714E+10 0.00 0.00 0.00 0.43
August 0.00 0.944408E+11 0.00 0.00 0.217014E+10 0.00 0.00 0.00 0.44
September 0.00 0.868979E+11 0.00 0.00 0.200255E+10 0.00 0.00 0.00 0.44
October 0.00 0.800357E+11 0.00 0.00 0.202363E+10 0.00 0.00 0.00 0.43
November 10753051.57 0.682794E+11 0.00 236965.30 0.139401E+10 0.00 2212230.96 0.00 0.43
December 23243796.35 0.574767E+11 0.00 229672.55 0.134265E+10 0.00 4545039.14 0.00 0.43
                   
Annual Sum or Average 0.157157E+09 0.933237E+12 0.00 3278751.68 0.196815E+11 0.00 63551975.22 0.00 0.44
Minimum of Months 0.00 0.537790E+11 0.00 0.00 0.107668E+10 0.00 0.00 0.00 0.43
Maximum of Months 0.116430E+09 0.103633E+12 0.00 1522709.58 0.217014E+10 0.00 47772125.20 0.00 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.777512E+10 0.00 0.00 2409734.52 0.00 0.00 0.00 0.50
February 0.00 0.773286E+10 0.00 0.00 3651777.94 0.00 0.00 0.00 0.50
March 0.00 0.932244E+10 0.00 0.00 2029184.27 0.00 0.00 0.00 0.51
April 0.00 0.111120E+11 0.00 0.00 5884702.10 0.00 0.00 0.00 0.51
May 0.00 0.131848E+11 0.00 0.00 3710698.52 0.00 0.00 0.00 0.51
June 0.00 0.130834E+11 0.00 0.00 1756243.87 0.00 0.00 0.00 0.52
July 0.00 0.954501E+10 0.00 0.00 2180762.45 0.00 0.00 0.00 0.49
August 0.00 0.119598E+11 0.00 0.00 7480523.31 0.00 0.00 0.00 0.50
September 0.00 0.113068E+11 0.00 0.00 2556471.78 0.00 0.00 0.00 0.50
October 0.00 0.107908E+11 0.00 0.00 9038972.54 0.00 0.00 0.00 0.50
November 0.00 0.956703E+10 0.00 0.00 2113113.68 0.00 0.00 0.00 0.50
December 0.00 0.836053E+10 0.00 0.00 2187787.07 0.00 0.00 0.00 0.50
                   
Annual Sum or Average 0.00 0.123741E+12 0.00 0.00 44999972.04 0.00 0.00 0.00 0.50
Minimum of Months 0.00 0.773286E+10 0.00 0.00 1756243.87 0.00 0.00 0.00 0.49
Maximum of Months 0.00 0.131848E+11 0.00 0.00 9038972.54 0.00 0.00 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.763631E+10 0.00 0.00 2427915.60 0.00 0.00 0.00 0.50
February 0.00 0.763066E+10 0.00 0.00 3672671.03 0.00 0.00 0.00 0.50
March 0.00 0.910182E+10 0.00 0.00 2028620.11 0.00 0.00 0.00 0.51
April 0.00 0.108220E+11 0.00 0.00 5827170.01 0.00 0.00 0.00 0.51
May 0.00 0.128605E+11 0.00 0.00 2760067.68 0.00 0.00 0.00 0.51
June 0.00 0.128000E+11 0.00 0.00 1715736.29 0.00 0.00 0.00 0.52
July 0.00 0.918944E+10 0.00 0.00 2180456.43 0.00 0.00 0.00 0.50
August 0.00 0.114909E+11 0.00 0.00 5841240.06 0.00 0.00 0.00 0.50
September 0.00 0.109638E+11 0.00 0.00 2550546.97 0.00 0.00 0.00 0.50
October 0.00 0.103689E+11 0.00 0.00 13027206.53 0.00 0.00 0.00 0.50
November 0.00 0.934161E+10 0.00 0.00 2116068.29 0.00 0.00 0.00 0.50
December 0.00 0.819435E+10 0.00 0.00 2188778.20 0.00 0.00 0.00 0.50
                   
Annual Sum or Average 0.00 0.120400E+12 0.00 0.00 46336477.19 0.00 0.00 0.00 0.50
Minimum of Months 0.00 0.763066E+10 0.00 0.00 1715736.29 0.00 0.00 0.00 0.50
Maximum of Months 0.00 0.128605E+11 0.00 0.00 13027206.53 0.00 0.00 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:19:52

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.241578E+12 -839063398.5 0.00 -0.106387E+12 0.264953E+12
February 0.241456E+12 -993947484.2 0.00 -0.110485E+12 0.262878E+12
March 0.328634E+12 -0.247075E+10 0.00 -0.141047E+12 0.314875E+12
April 0.336070E+12 -0.258892E+10 0.00 -0.176286E+12 0.339263E+12
May 0.329249E+12 -0.317815E+10 0.00 -0.210712E+12 0.373119E+12
June 0.338622E+12 -0.298170E+10 0.00 -0.206153E+12 0.379264E+12
July 0.275006E+12 -0.138555E+10 0.00 -0.149555E+12 0.303168E+12
August 0.354772E+12 -0.252385E+10 0.00 -0.186474E+12 0.338870E+12
September 0.276964E+12 -0.155858E+10 0.00 -0.174308E+12 0.321640E+12
October 0.299821E+12 -0.131819E+10 0.00 -0.162440E+12 0.300863E+12
November 0.236982E+12 -866305144.1 0.00 -0.137089E+12 0.281163E+12
December 0.225493E+12 -620099194.1 0.00 -0.112986E+12 0.267254E+12
           
Annual Sum or Average 0.348465E+13 -0.213251E+11 0.00 -0.187392E+13 0.374731E+13
Minimum of Months 0.225493E+12 -0.317815E+10 0.00 -0.210712E+12 0.262878E+12
Maximum of Months 0.354772E+12 -620099194.1 0.00 -0.106387E+12 0.379264E+12