Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19

Tabular Output Report in Format: HTML

Building: RetailStandalone

Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2024-07-03 12:20:00


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1695.42 739.07 739.07
Net Site Energy 1695.42 739.07 739.07
Total Source Energy 5369.41 2340.64 2340.64
Net Source Energy 5369.41 2340.64 2340.64


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 2293.99
Net Conditioned Building Area 2293.99
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 53.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 363.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 491.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 125.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 443.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 23.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1695.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 53.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 363.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 491.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 125.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 443.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 23.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 53.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 363.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 491.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 125.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 443.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 23.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 269.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 385.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06
Other 84.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 739.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 269.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 385.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06
Other 84.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 739.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1695.424 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1695.424 100.00
     
Total On-Site and Utility Electric Sources 1695.424 100.00
Total Electricity End Uses 1695.424 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 134.99 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 134.99 100.00
Total Water End Uses 134.99 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 353.50
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3585.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ZoneHeatingSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ZoneElectricSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

SpaceGainsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

PeakSpaceGainsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

SpaceGainComponentsAtCoolingPeakMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ComfortReportSimple55Monthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

OccupantComfortDataSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL |

WindowReportMonthly

| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |

WindowEnergyReportMonthly

| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |

WindowZoneSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

WindowEnergyZoneSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL |

FanReportMonthly

| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |

ZoneTemperatureOscillationReportMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

MechanicalVentilationLoadsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
RunPeriod RUNPERIOD 1
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Above Ground Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Window Opening Area [m2] 129.50 0.00 0.00 129.50 0.00
Gross Window-Wall Ratio [%] 11.00 0.00 0.00 39.14 0.00
Above Ground Window-Wall Ratio [%] 11.00 0.00 0.00 39.14 0.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Above Ground Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Window Opening Area [m2] 129.50 0.00 0.00 129.50 0.00
Gross Window-Wall Ratio [%] 11.00 0.00 0.00 39.14 0.00
Above Ground Window-Wall Ratio [%] 11.00 0.00 0.00 39.14 0.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 2293.99
Skylight Area [m2] 23.78
Skylight-Roof Ratio [%] 1.04


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BACK_SPACE 379.89 Yes Yes 2317.33 1.00 416.17 0.00 0.00 0.00 9.0271 46.45 8.0700
CORE_RETAIL 1600.48 Yes Yes 9762.95 1.00 356.86 0.00 0.00 0.00 18.2986 6.19 3.2300
POINT_OF_SALE 150.81 Yes Yes 919.94 1.00 189.80 0.00 60.84 60.84 18.2986 6.19 21.5200
FRONT_RETAIL 150.81 Yes Yes 919.94 1.00 189.80 0.00 60.84 60.84 18.2986 6.19 3.2300
FRONT_ENTRY 12.00 Yes Yes 73.20 1.00 24.38 0.00 7.83 7.83 10.9792 6.19 0.0000
Total 2293.99     13993.36   1177.02 0.00 129.50 129.50 16.7250 7.23 5.2170
Conditioned Total 2293.99     13993.36   1177.02 0.00 129.50 129.50 16.7250 7.23 5.2170
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BACK_SPACE 379.89 Yes Yes 1.00 BACK_SPACE GENERAL BACK_SPACE 9.0271 46.45 8.0700  
CORE_RETAIL 1600.48 Yes Yes 1.00 CORE_RETAIL GENERAL CORE_RETAIL 18.2986 6.19 3.2300  
POINT_OF_SALE 150.81 Yes Yes 1.00 POINT_OF_SALE GENERAL POINT_OF_SALE 18.2986 6.19 21.5200  
FRONT_RETAIL 150.81 Yes Yes 1.00 FRONT_RETAIL GENERAL FRONT_RETAIL 18.2986 6.19 3.2300  
FRONT_ENTRY 12.00 Yes Yes 1.00 FRONT_ENTRY GENERAL FRONT_ENTRY 10.9792 6.19 0.0000  
Total 2293.99             16.7250 3.62 5.2170  
Conditioned Total 2293.99             16.7250 3.62 5.2170  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 2293.99 2293.99 0.00 0.00 16.7250 7.23 5.2170
Total 2293.99 2293.99 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 12-FEB-07:30 - - - - - - - - - - - 02-JAN-12:09
Heating 148607.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1918.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 7996.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1771.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 23491.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 104.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 183889.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 148607.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1918.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 7996.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1771.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 23491.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 104.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 169.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1150.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1556.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 398.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 615.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1403.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 75.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 5369.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 73.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 501.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 678.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 173.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 268.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 611.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 33.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2340.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 73.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 501.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 678.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 173.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 268.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 611.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 33.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2340.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BACK_SPACE DIRECT AIR 2.80
CORE_RETAIL DIRECT AIR 8.55
POINT_OF_SALE DIRECT AIR 1.36
FRONT_RETAIL DIRECT AIR 1.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:UnitHeater

Design Size Maximum Supply Air Flow Rate [m3/s]
FRONT_ENTRY UNIT HEATER 2.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
FRONT_ENTRY UNIT HEATER FAN 2.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
FRONT_ENTRY UNIT HEATER HEATING COIL 34182.56
PSZ-AC:1_SUPPHEATCOIL 55191.94
PSZ-AC:2_SUPPHEATCOIL 193914.98
PSZ-AC:3_SUPPHEATCOIL 27716.05
PSZ-AC:4_SUPPHEATCOIL 27566.68
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 2.80 2.80 2.80 2.80 2.80 2.80 1.00 1.00 2.80
PSZ-AC:2 8.55 8.55 8.55 8.55 8.55 8.55 1.00 1.000000 8.55
PSZ-AC:3 1.36 1.36 1.36 1.36 1.36 1.36 1.00 1.00 1.36
PSZ-AC:4 1.31 1.31 1.31 1.31 1.31 1.31 1.00 1.00 1.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 2.80 0.231581
PSZ-AC:2_OA_CONTROLLER 8.55 1.89
PSZ-AC:3_OA_CONTROLLER 1.36 0.178122
PSZ-AC:4_OA_CONTROLLER 1.31 0.178122
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN 2.80 4549.83
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN 8.55 13673.59
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN 1.36 2268.01
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN 1.31 2178.67
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] User-Specified Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 2.80 2.80 2.80 2.80 54620.02 36978.60 32.22 55191.94 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 8.55 8.55 8.55 8.55 192415.35 129923.04 32.22 193914.98 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 1.36 1.36 1.36 1.36 27382.14 18569.75 32.22 27716.05 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 1.31 1.31 1.31 1.31 27247.90 18469.68 32.22 27566.68 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 2.80 1.40 1.87 54620.02 27310.01 0.786530 0.786530
PSZ-AC:2 HP COOLING COIL 8.55 4.27 5.70 192415.35 96207.68 0.732400 0.732400
PSZ-AC:3 HP COOLING COIL 1.36 0.682315 0.909753 27382.14 13691.07 0.775300 0.775300
PSZ-AC:4 HP COOLING COIL 1.31 0.655436 0.873913 27247.90 13623.95 0.761790 0.761790
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:MultiSpeed

Design Size Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] Design Size Speed 2 Gross Rated Heating Capacity [W] Design Size Speed 1 Gross Rated Heating Capacity [W] Design Size Resistive Defrost Heater Capacity
PSZ-AC:1 HEATING COIL 2.80 1.40 55191.94 27595.97 0.000000
PSZ-AC:2 HEATING COIL 8.55 4.27 193914.98 96957.49 0.000000
PSZ-AC:3 HEATING COIL 1.36 0.682315 27716.05 13858.02 0.000000
PSZ-AC:4 HEATING COIL 1.31 0.655436 27566.68 13783.34 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
BACK_SPACE_WALL_EAST BACK_SPACE_WALL_EAST_ROLLDOOR |
BACK_SPACE_WALL_NORTH BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 |
BACK_SPACE_WALL_WEST BACK_SPACE_WALL_WEST_ROLLDOOR |
CORE_RETAIL_WALL_WEST_2 CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 |
CORE_RETAIL_WALL_EAST_2 CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 |
CORE_RETAIL_ROOF SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 |
POINT_OF_SALE_WALL_SOUTH POINT_OF_SALE_WALL_SOUTH_GLAZING |
FRONT_RETAIL_WALL_SOUTH FRONT_RETAIL_WALL_SOUTH_GLAZING |
FRONT_ENTRY_WALL_SOUTH FRONT_ENTRY_WALL_SOUTH_GLAZING |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 11.90 7.70 4.00 7.90 13.80 17.20 20.80 24.80 26.10 26.50 22.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 33.63 -84.43 -5.00 308.00 97679 1.1610


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.60 22.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 RetailStandalone 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 5 73 32


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BACK_SPACE 0.0 0.00 35.27 0.00 27.14 38.77 3.05 1 1 1 0.00 54.27 35.27 42.27 0.00 6.10 6.10 2317.33 TARP TARP 379.89 416.17 375.11 0.00 6 7 0 Yes
2 CORE_RETAIL 0.0 0.00 6.00 0.00 27.14 14.41 3.05 1 1 1 0.00 54.27 3.00 35.27 0.00 6.10 6.10 9762.95 TARP TARP 1600.48 356.86 345.15 23.78 10 22 0 Yes
3 POINT_OF_SALE 0.0 0.00 0.00 0.00 12.57 3.00 3.05 1 1 1 0.00 25.14 0.00 6.00 0.00 6.10 6.10 919.94 TARP TARP 150.81 189.80 128.96 60.84 7 1 0 Yes
4 FRONT_RETAIL 0.0 29.14 0.00 0.00 41.70 3.00 3.05 1 1 1 29.14 54.27 0.00 6.00 0.00 6.10 6.10 919.94 TARP TARP 150.81 189.80 128.96 60.84 7 1 0 Yes
5 FRONT_ENTRY 0.0 25.14 0.00 0.00 27.14 1.50 3.05 1 1 1 25.14 29.14 0.00 3.00 0.00 6.10 6.10 73.20 TARP TARP 12.00 24.38 16.55 7.83 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BACK_SPACE 379.89 8.2 46.452 2.153E-002 9.027 8.070 0.000 0.000 0.000 0.000 17.097 No
2 CORE_RETAIL 1600.48 258.4 6.193 0.161 18.299 3.230 0.000 0.000 0.000 0.000 21.529 No
3 POINT_OF_SALE 150.81 24.4 6.193 0.161 18.299 21.520 0.000 0.000 0.000 0.000 39.819 No
4 FRONT_RETAIL 150.81 24.4 6.193 0.161 18.299 3.230 0.000 0.000 0.000 0.000 21.529 No
5 FRONT_ENTRY 12.00 1.9 6.192 0.162 10.979 0.000 0.000 0.000 0.000 0.000 10.979 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BACK_SPACE BLDG_OCC_SCH BACK_SPACE 379.89 8.2 8.2 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_RETAIL BLDG_OCC_SCH CORE_RETAIL 1600.48 258.4 258.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 258 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 POINT_OF_SALE BLDG_OCC_SCH POINT_OF_SALE 150.81 24.4 24.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 24 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 FRONT_RETAIL BLDG_OCC_SCH FRONT_RETAIL 150.81 24.4 24.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 24 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 FRONT_ENTRY BLDG_OCC_SCH FRONT_ENTRY 12.00 1.9 1.9 0.162 6.192 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BACK_SPACE_LIGHTS LTG_SCH_BACK BACK_SPACE 379.89 8.2 3429.297 9.027 419.326 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3429.297
2 CORE_RETAIL_LIGHTS LTG_SCH_CORE CORE_RETAIL 1600.48 258.4 29286.644 18.299 113.323 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 29286.644
3 POINT_OF_SALE_LIGHTS LTG_SCH_SALE POINT_OF_SALE 150.81 24.4 2759.616 18.299 113.323 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2759.616
4 FRONT_RETAIL_LIGHTS LTG_SCH_FRONT FRONT_RETAIL 150.81 24.4 2759.616 18.299 113.323 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2759.616
5 FRONT_ENTRY_LIGHTS LTG_SCH_ENTRY FRONT_ENTRY 12.00 1.9 131.750 10.979 67.983 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 131.750


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BACK_SPACE_MISCPLUG_EQUIP BLDG_EQUIP_SCH BACK_SPACE 379.89 8.2 3065.712 8.070 374.868 0.000 0.500 0.000 0.500 MiscPlug 0.000 3065.712
2 CORE_RETAIL_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_RETAIL 1600.48 258.4 5169.560 3.230 20.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 5169.560
3 POINT_OF_SALE_MISCPLUG_EQUIP BLDG_EQUIP_SCH POINT_OF_SALE 150.81 24.4 3245.431 21.520 133.273 0.000 0.500 0.000 0.500 MiscPlug 0.000 3245.431
4 FRONT_RETAIL_MISCPLUG_EQUIP BLDG_EQUIP_SCH FRONT_RETAIL 150.81 24.4 487.116 3.230 20.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 487.116


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 9.815 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 200.0 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.3762 0.900 0.900 0.700 0.700 Rough
6 NONRES_EXT_WALL_GRD 21 4 7 0.167 0.7871 0.900 0.900 0.700 0.700 Smooth
7 BACK_SPACE_FLOOR_FFACTOR 38 2 7 0.167 0.2354 0.000 0.900 0.000 0.700 MediumRough
8 CORE_RETAIL_FLOOR_FFACTOR 39 2 7 0.167 0.4655E-01 0.000 0.900 0.000 0.700 MediumRough
9 POINT_OF_SALE_FLOOR_FFACTOR 40 2 7 0.167 0.2719 0.000 0.900 0.000 0.700 MediumRough
10 FRONT_RETAIL_FLOOR_FFACTOR 41 2 7 0.167 0.2719 0.000 0.900 0.000 0.700 MediumRough
11 FRONT_ENTRY_FLOOR_FFACTOR 42 2 7 0.167 0.4506 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.1019
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5000E-02
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 2.599
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
10 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
11 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.037
12 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
13 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 4.172
14 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
15 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 21.40
16 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
17 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.601
18 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
19 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 3.601
20 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
21 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.142
22 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 9.8148919 9.8148919 9.8148919  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 200.00000 200.00000 200.00000  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.61039648E-06 0.16815647E-08 -0.37447326E-05 0.10149002E-16
21 2 0.76989337 0.22941655E-02 1.0458372 -0.71793422E-06
22 1 -21.843031 0.15409339 -6.3407615 0.20050303
23 0 21.373924 0.14439780 5.5957134  
24 7 -0.29735092E-12 0.24575595E-14 -0.94456721E-13 0.15324278E-15
25 6 0.28546880E-07 0.22114619E-09 0.65405332E-08 -0.13451374E-12
26 5 -0.18947583E-03 0.18937623E-05 -0.97466953E-04 0.64660656E-08
27 4 0.29140875 0.92215111E-03 0.99417931E-01 -0.33466744E-04
28 3 -7.2517161 0.28579858E-01 -2.3345767 0.28937395E-01
29 2 40.822959 0.10163225 15.247323 -0.33280368
30 1 -80.508872 0.45869584E-01 -29.125752 1.0778326
31 0 46.824339 0.92288667E-03 16.291614  
32 7 -0.17867606E-08 -0.41848128E-15 0.59564440E-14 -0.80268503E-16
33 6 0.65885627E-05 0.45121803E-08 0.31870471E-02 -0.26735622E-04
34 5 -0.47407468E-03 0.26731137E-05 -0.22356413 0.19547341E-02
35 4 0.10906669E-01 0.12168607E-03 4.8268734 -0.45239294E-01
36 3 -0.95781928E-01 0.96775432E-03 -38.006321 0.39848689
37 2 0.34010998 0.16100142E-02 116.45457 -1.4175463
38 1 -0.49090295 0.49061009E-03 -143.89001 2.0487556
39 0 0.23934032 0.11861159E-04 60.838472  
40 7 -0.92098544E-08 0.58605081E-15 -0.29904982E-14 0.25019681E-16
41 6 0.19387148E-05 0.91388609E-09 0.32017682E-02 -0.26859115E-04
42 5 -0.10799279E-03 0.53275402E-06 -0.22440051 0.19621166E-02
43 4 0.22736042E-02 0.24052495E-04 4.8407977 -0.45373149E-01
44 3 -0.19287081E-01 0.18995237E-03 -38.084949 0.39935605
45 2 0.67516478E-01 0.31394945E-03 116.60756 -1.4195928
46 1 -0.96817688E-01 0.94848058E-04 -143.98006 2.0502357
47 0 0.47046370E-01 0.22824214E-05 60.838472  
48 7 -0.15410587E-08 -0.27131508E-15 0.13739895E-13 -0.20869099E-15
49 6 0.75948721E-05 0.52202150E-08 0.31841660E-02 -0.26711453E-04
50 5 -0.54825752E-03 0.30939483E-05 -0.22340036 0.19532886E-02
51 4 0.12624073E-01 0.14086823E-03 4.8241453 -0.45213070E-01
52 3 -0.11089483 0.11205317E-02 -37.990908 0.39831653
53 2 0.39381345 0.18644394E-02 116.42457 -1.4171450
54 1 -0.56844024 0.56830838E-03 -143.87235 2.0484654
55 0 0.27714917 0.13715070E-04 60.838472  
56 7 -0.15410587E-08 -0.27131508E-15 0.13739895E-13 -0.20869099E-15
57 6 0.75948721E-05 0.52202150E-08 0.31841660E-02 -0.26711453E-04
58 5 -0.54825752E-03 0.30939483E-05 -0.22340036 0.19532886E-02
59 4 0.12624073E-01 0.14086823E-03 4.8241453 -0.45213070E-01
60 3 -0.11089483 0.11205317E-02 -37.990908 0.39831653
61 2 0.39381345 0.18644394E-02 116.42457 -1.4171450
62 1 -0.56844024 0.56830838E-03 -143.87235 2.0484654
63 0 0.27714917 0.13715070E-04 60.838472  
64 7 -0.91256693E-09 -0.65654920E-16 0.14763662E-14 0.25811017E-17
65 6 0.12659591E-04 0.87293215E-08 0.31698558E-02 -0.26591407E-04
66 5 -0.91895148E-03 0.51830142E-05 -0.22258679 0.19461077E-02
67 4 0.21183618E-01 0.23613386E-03 4.8105909 -0.45082779E-01
68 3 -0.18612912 0.18798277E-02 -37.914317 0.39746999
69 2 0.66101200 0.31293459E-02 116.27548 -1.4151508
70 1 -0.95411819 0.95507326E-03 -143.78458 2.0470226
71 0 0.46518638 0.22828278E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.57_SHGC_0.25 36 1 VerySmooth 3.241 3.241 1.000 0.251    
2 NONRESSKYLIGHT_U_0.69_SHGC_0.39 37 1 VerySmooth 3.922 3.922 1.000 0.393    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SpectralAverage   2.00000E-003 0.16139 0.60205 0.60205 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
2 NONRES SKYLIGHT GLAZING LAYER SpectralAverage   2.00000E-003 0.26553 0.37967 0.37967 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 2.30798E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 1.001 0.9283


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BACK_SPACE_WALL_EAST 0 257.68 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
2 BACK_SPACE_WALL_EAST_ROLLDOOR 0 257.68 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
3 BACK_SPACE_WALL_NORTH 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
4 BACK_SPACE_WALL_NORTH_DOOR1 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
5 BACK_SPACE_WALL_NORTH_DOOR2 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
6 BACK_SPACE_WALL_NORTH_ROLLDOOR1 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
7 BACK_SPACE_WALL_NORTH_ROLLDOOR2 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
8 BACK_SPACE_WALL_NORTH_ROLLDOOR3 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
9 BACK_SPACE_WALL_WEST 0 257.68 96.73 6.10 0 6.10 68.27 12.40 0.00 0 No No
10 BACK_SPACE_WALL_WEST_ROLLDOOR 0 257.68 96.73 6.10 0 6.10 68.27 12.40 0.00 0 No No
11 BACK_SPACE_WALL_SOUTH 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
12 BACK_SPACE_FLOOR 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
13 BACK_SPACE_ROOF 0 2293.99 205.08 0.00 0 6.10 68.27 12.40 0.00 0 No No
14 BACK_SPACE_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
15 CORE_RETAIL_WALL_SOUTH_3 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
16 CORE_RETAIL_WALL_SOUTH_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
17 CORE_RETAIL_WALL_EAST_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
18 CORE_RETAIL_WALL_SOUTH_2 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
19 CORE_RETAIL_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
20 CORE_RETAIL_WALL_WEST_2 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 4 No No
21 CORE_RETAIL_WALL_WEST_2_DOOR3 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
22 CORE_RETAIL_WALL_WEST_2_DOOR2 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
23 CORE_RETAIL_WALL_WEST_2_DOOR1 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
24 CORE_RETAIL_WALL_EAST_2 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 4 No No
25 CORE_RETAIL_WALL_EAST_2_DOOR1 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
26 CORE_RETAIL_WALL_EAST_2_DOOR2 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
27 CORE_RETAIL_WALL_EAST_2_DOOR3 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
28 CORE_RETAIL_WALL_WEST_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
29 CORE_RETAIL_FLOOR 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
30 CORE_RETAIL_ROOF 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
31 SKYLIGHTS_R4C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
32 SKYLIGHTS_R4C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
33 SKYLIGHTS_R4C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
34 SKYLIGHTS_R4C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
35 SKYLIGHTS_R1C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
36 SKYLIGHTS_R1C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
37 SKYLIGHTS_R1C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
38 SKYLIGHTS_R1C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
39 SKYLIGHTS_R2C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
40 SKYLIGHTS_R2C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
41 SKYLIGHTS_R2C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
42 SKYLIGHTS_R2C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
43 SKYLIGHTS_R3C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
44 SKYLIGHTS_R3C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
45 SKYLIGHTS_R3C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
46 SKYLIGHTS_R3C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
47 CORE_RETAIL_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
48 POINT_OF_SALE_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.32 4 No No
49 POINT_OF_SALE_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.32 1 No No
50 POINT_OF_SALE_WALL_EAST_2 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.32 0 No No
51 POINT_OF_SALE_WALL_WEST 0 257.68 96.73 6.10 0 6.10 31.14 9.69 0.32 4 No No
52 POINT_OF_SALE_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.32 0 No No
53 POINT_OF_SALE_WALL_EAST_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.32 0 No No
54 POINT_OF_SALE_FLOOR 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.32 0 No No
55 POINT_OF_SALE_ROOF 0 2293.99 205.08 0.00 0 6.10 31.14 9.69 0.32 0 No No
56 POINT_OF_SALE_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.32 0 No No
57 FRONT_RETAIL_WALLL_EAST 0 257.68 149.77 6.10 0 6.10 31.14 9.69 0.32 4 No No
58 FRONT_RETAIL_WALL_WEST_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.32 0 No No
59 FRONT_RETAIL_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.32 0 No No
60 FRONT_RETAIL_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.32 4 No No
61 FRONT_RETAIL_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.32 1 No No
62 FRONT_RETAIL_WALL_WEST_2 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.32 0 No No
63 FRONT_RETAIL_FLOOR 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.32 0 No No
64 FRONT_RETAIL_ROOF 0 2293.99 205.08 0.00 0 6.10 31.14 9.69 0.32 0 No No
65 FRONT_RETAIL_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.32 0 No No
66 FRONT_ENTRY_WALL_EAST 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
67 FRONT_ENTRY_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
68 FRONT_ENTRY_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 4.00 3.43 0.32 4 No No
69 FRONT_ENTRY_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 4.00 3.43 0.32 1 No No
70 FRONT_ENTRY_WALL_WEST 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
71 FRONT_ENTRY_FLOOR 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
72 FRONT_ENTRY_ROOF 0 2293.99 205.08 0.00 0 6.10 4.00 3.43 0.32 0 No No
73 FRONT_ENTRY_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No


FenestrationAssembly

Construction Name Frame and Divider Name NFRC Product Type Assembly U-Factor {W/m2-K} Assembly SHGC Assembly Visible Transmittance
1 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES CurtainWall 3.786 0.393 0.402


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 BACK_SPACE_INFILTRATION INFIL_SCH_PNNL BACK_SPACE 379.89 8.2 0.237 6.240E-004 2.832E-004 0.368 0.000 0.000 0.224 0.000
2 CORE_RETAIL_INFILTRATION INFIL_SCH_PNNL CORE_RETAIL 1600.48 258.4 0.203 1.270E-004 1.032E-004 7.495E-002 0.000 0.000 0.224 0.000
3 POINT_OF_SALE_INFILTRATION INFIL_SCH_PNNL POINT_OF_SALE 150.81 24.4 0.108 7.168E-004 3.174E-004 0.423 0.000 0.000 0.224 0.000
4 FRONT_RETAIL_INFILTRATION INFIL_SCH_PNNL FRONT_RETAIL 150.81 24.4 0.108 7.168E-004 3.174E-004 0.423 0.000 0.000 0.224 0.000
5 FRONT_ENTRY_INFILTRATION INFIL_SCH_PNNL FRONT_ENTRY 12.00 1.9 1.389E-002 1.157E-003 3.817E-004 0.683 0.000 0.000 0.224 0.000
6 FRONT_ENTRY_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH FRONT_ENTRY 12.00 1.9 0.937 7.811E-002 2.576E-002 46.096 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BACK_SPACE Mixing/Well-Stirred
2 CORE_RETAIL Mixing/Well-Stirred
3 POINT_OF_SALE Mixing/Well-Stirred
4 FRONT_RETAIL Mixing/Well-Stirred
5 FRONT_ENTRY Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2500
2 Zone BACK_SPACE 1.2500
3 Zone CORE_RETAIL 1.2500
4 Zone POINT_OF_SALE 1.2500
5 Zone FRONT_RETAIL 1.2500
6 Zone FRONT_ENTRY 1.2500


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.1500
2 Zone BACK_SPACE 1.1500
3 Zone CORE_RETAIL 1.1500
4 Zone POINT_OF_SALE 1.1500
5 Zone FRONT_RETAIL 1.1500
6 Zone FRONT_ENTRY 1.1500


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BACK_SPACE Cooling 21604.64459 24845.34127 1.64108 1.88724 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 34.21000 1.44729E-002 379.89000 8.17812 0.23158 0.00000
2 BACK_SPACE Heating 30399.49042 37999.36302 2.24389 2.80486 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 379.89000 8.17812 0.23158 0.00000
3 CORE_RETAIL Cooling 97854.55347 112532.73649 7.43386 8.54894 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 34.16250 1.44728E-002 1600.48290 258.43418 1.89033 0.00000
4 CORE_RETAIL Heating 68249.11852 85311.39815 4.92285 6.15357 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 1600.48290 258.43418 1.89033 0.00000
5 POINT_OF_SALE Cooling 15619.70539 17962.66120 1.18663 1.36463 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 34.40000 1.44733E-002 150.81000 24.35169 0.17812 0.00000
6 POINT_OF_SALE Heating 14157.15885 17696.44857 1.04845 1.31056 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 150.81000 24.35169 0.17812 0.00000
7 FRONT_RETAIL Cooling 13295.50066 15289.82576 1.01007 1.16158 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40000 1.44733E-002 150.81000 24.35169 0.17812 0.00000
8 FRONT_RETAIL Heating 14160.43513 17700.54392 1.04870 1.31087 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 150.81000 24.35169 0.17812 0.00000
9 FRONT_ENTRY Cooling 0.00000 0.00000 0.00000 1.41732E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 34.40000 1.44733E-002 12.00000 1.93800 1.41732E-002 0.00000
10 FRONT_ENTRY Heating 27328.28294 34160.35368 2.06845 2.58556 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:10:00 -6.30000 2.29779E-003 12.00000 1.93800 1.41732E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 27282.56 1.88724 1.88724 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 44270.43 2.80486 2.80486 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 PSZ-AC:2 Cooling Sensible 133820.53 8.54894 8.54894 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 141318.74 6.15357 6.15357 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
5 PSZ-AC:3 Cooling Sensible 19869.39 1.36463 1.36463 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 22825.95 1.31056 1.31056 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
7 PSZ-AC:4 Cooling Sensible 17237.89 1.16158 1.16158 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 22830.02 1.31087 1.31087 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BACK_SPACE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 2.80486
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_RETAIL DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 8.54894
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat POINT_OF_SALE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.36463
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat FRONT_RETAIL DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.31087
5 ZoneHVAC:UnitHeater FRONT_ENTRY UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 2.58556
6 Fan:ConstantVolume FRONT_ENTRY UNIT HEATER FAN Design Size Maximum Flow Rate [m3/s] 2.58556
7 Coil:Heating:Electric FRONT_ENTRY UNIT HEATER HEATING COIL Design Size Nominal Capacity [W] 34182.56042
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.80486
9 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.80486
10 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 2.80486
11 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 2.80486
12 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 2.80486
13 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 2.80486
14 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
15 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 8.54894
17 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 8.54894
18 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 8.54894
19 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 8.54894
20 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 8.54894
21 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 8.54894
22 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
23 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.36463
25 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.36463
26 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.36463
27 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 1.36463
28 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 1.36463
29 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 1.36463
30 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
31 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.31087
33 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.31087
34 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.31087
35 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 1.31087
36 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 1.31087
37 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 1.31087
38 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
39 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
40 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 2.80486
41 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 8.54894
42 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 1.36463
43 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 1.31087
44 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.80486
45 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.23158
46 Fan:SystemModel PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 2.80486
47 Fan:SystemModel PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 4549.82706
48 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 2.80486
49 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 2.80486
50 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 2.80486
51 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 2.80486
52 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 2.80486
53 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 1.40243
54 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.86991
55 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 54620.02000
56 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 27310.01000
57 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.78653
58 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.78653
59 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 54620.02000
60 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 36978.60121
61 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 32.22000
62 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 55191.94210
63 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
64 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 2.80486
65 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 1.40243
66 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 55191.94210
67 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 27595.97105
68 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
69 Coil:Heating:Electric PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 55191.94210
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.54894
71 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.89033
72 Fan:SystemModel PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 8.54894
73 Fan:SystemModel PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 13673.59245
74 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 8.54894
75 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 8.54894
76 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 8.54894
77 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 8.54894
78 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 8.54894
79 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 4.27447
80 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 5.69929
81 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 192415.35000
82 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 96207.67500
83 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.73240
84 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.73240
85 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 192415.35000
86 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 129923.03793
87 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 32.22000
88 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 193914.98198
89 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
90 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 8.54894
91 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 4.27447
92 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 193914.98198
93 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 96957.49099
94 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
95 Coil:Heating:Electric PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 193914.98198
96 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.36463
97 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.17812
98 Fan:SystemModel PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.36463
99 Fan:SystemModel PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 2268.01101
100 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.36463
101 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.36463
102 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.36463
103 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.36463
104 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.36463
105 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.68231
106 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.90975
107 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 27382.14000
108 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 13691.07000
109 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.77530
110 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.77530
111 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 27382.14000
112 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 18569.75232
113 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 32.22000
114 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 27716.04824
115 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
116 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 1.36463
117 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.68231
118 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 27716.04824
119 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 13858.02412
120 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
121 Coil:Heating:Electric PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 27716.04824
122 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.31087
123 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.17812
124 Fan:SystemModel PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.31087
125 Fan:SystemModel PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 2178.66687
126 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.31087
127 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.31087
128 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.31087
129 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.31087
130 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.31087
131 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.65544
132 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.87391
133 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 27247.90000
134 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 13623.95000
135 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.76179
136 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.76179
137 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 27247.90000
138 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 18469.67679
139 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 32.22000
140 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX User-Specified Supplemental Heating Coil Nominal Capacity [W] 27566.68178
141 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
142 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 2 Rated Air Flow Rate [m3/s] 1.31087
143 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.65544
144 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 2 Gross Rated Heating Capacity [W] 27566.68178
145 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Speed 1 Gross Rated Heating Capacity [W] 13783.34089
146 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL Design Size Resistive Defrost Heater Capacity 0.00000
147 Coil:Heating:Electric PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 27566.68178


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 HP COOLING COIL 52416.7     9.94 9.94  
2 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 HP COOLING COIL 185683.5     9.89 9.89  
3 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 HP COOLING COIL 26309.7     10.52 10.52  
4 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 HP COOLING COIL 26217.1     10.58 10.58  


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:MultiSpeed PSZ-AC:1 HEATING COIL 57427.9 31802.5 7.80 2
2 Coil:Heating:DX:MultiSpeed PSZ-AC:2 HEATING COIL 200761.0 110727.4 7.15 2
3 Coil:Heating:DX:MultiSpeed PSZ-AC:3 HEATING COIL 28804.9 15936.5 7.76 2
4 Coil:Heating:DX:MultiSpeed PSZ-AC:4 HEATING COIL 28613.8 15814.7 7.78 2


Zone Surfaces

Zone Name # Surfaces
1 BACK_SPACE 14
2 CORE_RETAIL 33
3 POINT_OF_SALE 9
4 FRONT_RETAIL 9
5 FRONT_ENTRY 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BACK_SPACE_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   35.24 42.67 35.24 90.00 90.00 7.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
2 BACK_SPACE_WALL_EAST_ROLLDOOR Door BACK_SPACE_WALL_EAST CTF - ConductionTransferFunction OVERHEAD DOOR_CON 200.000 200.000   7.43 7.43 7.43 90.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
3 BACK_SPACE_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   304.63 330.83 304.63 0.00 90.00 54.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
4 BACK_SPACE_WALL_NORTH_DOOR1 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 BACK_SPACE_WALL_NORTH_DOOR2 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
6 BACK_SPACE_WALL_NORTH_ROLLDOOR1 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 200.000 200.000   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
7 BACK_SPACE_WALL_NORTH_ROLLDOOR2 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 200.000 200.000   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
8 BACK_SPACE_WALL_NORTH_ROLLDOOR3 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 200.000 200.000   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 BACK_SPACE_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   35.24 42.67 35.24 270.00 90.00 7.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 BACK_SPACE_WALL_WEST_ROLLDOOR Door BACK_SPACE_WALL_WEST CTF - ConductionTransferFunction OVERHEAD DOOR_CON 200.000 200.000   7.43 7.43 7.43 270.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 BACK_SPACE_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   330.83 330.83 330.83 180.00 90.00 54.27 6.10 0.00 CORE_RETAIL_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
12 BACK_SPACE_FLOOR Floor   CTF - ConductionTransferFunction BACK_SPACE_FLOOR_FFACTOR 0.235 0.223   379.89 379.89 379.89 90.00 180.00 7.00 54.27 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 BACK_SPACE_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   379.89 379.89 379.89 90.00 0.00 7.00 54.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
14 BACK_SPACE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   759.78 759.78 759.78 0.00 90.00 759.78 1.00 0.00 BACK_SPACE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 CORE_RETAIL_WALL_SOUTH_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 180.00 90.00 25.14 6.10 0.00 FRONT_RETAIL_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
16 CORE_RETAIL_WALL_SOUTH_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 180.00 90.00 25.14 6.10 0.00 POINT_OF_SALE_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
17 CORE_RETAIL_WALL_EAST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_RETAIL_WALL_WEST_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
18 CORE_RETAIL_WALL_SOUTH_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.38 24.38 24.38 180.00 90.00 4.00 6.10 0.00 FRONT_ENTRY_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 CORE_RETAIL_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   330.83 330.83 330.83 0.00 90.00 54.27 6.10 0.00 BACK_SPACE_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 CORE_RETAIL_WALL_WEST_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   172.58 178.43 172.58 270.00 90.00 29.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 CORE_RETAIL_WALL_WEST_2_DOOR3 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 CORE_RETAIL_WALL_WEST_2_DOOR2 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
23 CORE_RETAIL_WALL_WEST_2_DOOR1 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 CORE_RETAIL_WALL_EAST_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   172.58 178.43 172.58 90.00 90.00 29.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 CORE_RETAIL_WALL_EAST_2_DOOR1 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
26 CORE_RETAIL_WALL_EAST_2_DOOR2 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
27 CORE_RETAIL_WALL_EAST_2_DOOR3 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
28 CORE_RETAIL_WALL_WEST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 POINT_OF_SALE_WALL_EAST_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_RETAIL_FLOOR Floor   CTF - ConductionTransferFunction CORE_RETAIL_FLOOR_FFACTOR 4.655E-002 4.603E-002   1600.48 1600.48 1600.48 0.00 180.00 40.01 40.01 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
30 CORE_RETAIL_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   1576.70 1600.48 1576.70 180.00 0.00 40.01 40.01 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
31 SKYLIGHTS_R4C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 1.11E-016 1.00 4
32 SKYLIGHTS_R4C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
33 SKYLIGHTS_R4C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
34 SKYLIGHTS_R4C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
35 SKYLIGHTS_R1C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
36 SKYLIGHTS_R1C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
37 SKYLIGHTS_R1C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
38 SKYLIGHTS_R1C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
39 SKYLIGHTS_R2C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
40 SKYLIGHTS_R2C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
41 SKYLIGHTS_R2C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
42 SKYLIGHTS_R2C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
43 SKYLIGHTS_R3C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
44 SKYLIGHTS_R3C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 1.11E-016 1.00 4
45 SKYLIGHTS_R3C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
46 SKYLIGHTS_R3C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.69_SHGC_0.39 N/A 3.922 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
47 CORE_RETAIL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3200.97 3200.97 3200.97 0.00 90.00 3200.97 1.00 0.00 CORE_RETAIL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
48 POINT_OF_SALE_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   92.39 153.22 92.39 180.00 90.00 25.14 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 POINT_OF_SALE_WALL_SOUTH_GLAZING Window POINT_OF_SALE_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 60.84 60.84 60.84 180.00 90.00 25.04 2.43 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
50 POINT_OF_SALE_WALL_EAST_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 CORE_RETAIL_WALL_WEST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 POINT_OF_SALE_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   36.58 36.58 36.58 270.00 90.00 6.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 POINT_OF_SALE_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 0.00 90.00 25.14 6.10 0.00 CORE_RETAIL_WALL_SOUTH_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
53 POINT_OF_SALE_WALL_EAST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_ENTRY_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 POINT_OF_SALE_FLOOR Floor   CTF - ConductionTransferFunction POINT_OF_SALE_FLOOR_FFACTOR 0.272 0.255   150.81 150.81 150.81 180.00 180.00 25.14 6.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
55 POINT_OF_SALE_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   150.81 150.81 150.81 180.00 0.00 25.14 6.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
56 POINT_OF_SALE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   301.62 301.62 301.62 0.00 90.00 301.62 1.00 0.00 POINT_OF_SALE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
57 FRONT_RETAIL_WALLL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   36.58 36.58 36.58 90.00 90.00 6.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 FRONT_RETAIL_WALL_WEST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 FRONT_ENTRY_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 FRONT_RETAIL_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 0.00 90.00 25.14 6.10 0.00 CORE_RETAIL_WALL_SOUTH_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 FRONT_RETAIL_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   92.39 153.22 92.39 180.00 90.00 25.14 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 FRONT_RETAIL_WALL_SOUTH_GLAZING Window FRONT_RETAIL_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 60.84 60.84 60.84 180.00 90.00 25.04 2.43 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 FRONT_RETAIL_WALL_WEST_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 CORE_RETAIL_WALL_EAST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 FRONT_RETAIL_FLOOR Floor   CTF - ConductionTransferFunction FRONT_RETAIL_FLOOR_FFACTOR 0.272 0.255   150.81 150.81 150.81 90.00 180.00 6.00 25.14 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
64 FRONT_RETAIL_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   150.81 150.81 150.81 90.00 0.00 6.00 25.14 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
65 FRONT_RETAIL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   301.62 301.62 301.62 0.00 90.00 301.62 1.00 0.00 FRONT_RETAIL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
66 FRONT_ENTRY_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_RETAIL_WALL_WEST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
67 FRONT_ENTRY_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.38 24.38 24.38 0.00 90.00 4.00 6.10 0.00 CORE_RETAIL_WALL_SOUTH_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
68 FRONT_ENTRY_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   16.55 24.38 16.55 180.00 90.00 4.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 FRONT_ENTRY_WALL_SOUTH_GLAZING Window FRONT_ENTRY_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.57_SHGC_0.25 N/A 3.241 No 7.83 7.83 7.83 180.00 90.00 3.00 2.61 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 FRONT_ENTRY_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 POINT_OF_SALE_WALL_EAST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 FRONT_ENTRY_FLOOR Floor   CTF - ConductionTransferFunction FRONT_ENTRY_FLOOR_FFACTOR 0.451 0.406   12.00 12.00 12.00 180.00 180.00 4.00 3.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
72 FRONT_ENTRY_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   12.00 12.00 12.00 180.00 0.00 4.00 3.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
73 FRONT_ENTRY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   24.00 24.00 24.00 0.00 90.00 24.00 1.00 0.00 FRONT_ENTRY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BACK_SPACE RunPeriod: RUNPERIOD 1 7.5028421469E-002 0.2838435791 Pass Pass 5.9159419900E-002 0.2154752680 Pass Pass
2 CORE_RETAIL RunPeriod: RUNPERIOD 1 4.6708040692E-002 0.1422153814 Pass Pass 0.1641494381 0.4560915252 Pass Pass
3 POINT_OF_SALE RunPeriod: RUNPERIOD 1 9.1956259673E-002 0.2711153341 Pass Pass 0.1382702935 0.3369328384 Pass Pass
4 FRONT_RETAIL RunPeriod: RUNPERIOD 1 8.3896171848E-002 0.3273661629 Pass Pass 0.2016982708 1.0981117543 Pass Pass
5 FRONT_ENTRY RunPeriod: RUNPERIOD 1 0.1483135270 0.5458356780 Pass Pass 5.9619779075E-002 0.5851232733 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4405.28 44.45 0.00 346.87 -953576.0 -948779.3



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 90.00 25      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BACK_SPACE_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 42.67 35.24 90.00 90.00 E
BACK_SPACE_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.704 0.787 330.83 304.63 0.00 90.00 N
BACK_SPACE_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 42.67 35.24 270.00 90.00 W
BACK_SPACE_FLOOR BACK_SPACE_FLOOR_FFACTOR 1.00 0.227 0.235 379.89 379.89 90.00 180.00  
BACK_SPACE_ROOF NONRES_ROOF 0.30 0.358 0.376 379.89 379.89 90.00 0.00  
CORE_RETAIL_WALL_WEST_2 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 178.43 172.58 270.00 90.00 W
CORE_RETAIL_WALL_EAST_2 NONRES_EXT_WALL_GRD 0.30 0.704 0.787 178.43 172.58 90.00 90.00 E
CORE_RETAIL_FLOOR CORE_RETAIL_FLOOR_FFACTOR 1.00 0.046 0.047 1600.48 1600.48 0.00 180.00  
CORE_RETAIL_ROOF NONRES_ROOF 0.30 0.358 0.376 1600.48 1576.70 180.00 0.00  
POINT_OF_SALE_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.704 0.787 153.22 92.39 180.00 90.00 S
POINT_OF_SALE_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 36.58 36.58 270.00 90.00 W
POINT_OF_SALE_FLOOR POINT_OF_SALE_FLOOR_FFACTOR 1.00 0.260 0.272 150.81 150.81 180.00 180.00  
POINT_OF_SALE_ROOF NONRES_ROOF 0.30 0.358 0.376 150.81 150.81 180.00 0.00  
FRONT_RETAIL_WALLL_EAST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 36.58 36.58 90.00 90.00 E
FRONT_RETAIL_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.704 0.787 153.22 92.39 180.00 90.00 S
FRONT_RETAIL_FLOOR FRONT_RETAIL_FLOOR_FFACTOR 1.00 0.260 0.272 150.81 150.81 90.00 180.00  
FRONT_RETAIL_ROOF NONRES_ROOF 0.30 0.358 0.376 150.81 150.81 90.00 0.00  
FRONT_ENTRY_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.704 0.787 24.38 16.55 180.00 90.00 S
FRONT_ENTRY_FLOOR FRONT_ENTRY_FLOOR_FFACTOR 1.00 0.420 0.451 12.00 12.00 180.00 180.00  
FRONT_ENTRY_ROOF NONRES_ROOF 0.30 0.358 0.376 12.00 12.00 180.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BACK_SPACE_WALL_SOUTH INT_WALL 0.30 2.511 6.299 330.83 330.83 180.00 90.00 S
CORE_RETAIL_WALL_SOUTH_3 INT_WALL 0.30 2.511 6.299 153.22 153.22 180.00 90.00 S
CORE_RETAIL_WALL_SOUTH_1 INT_WALL 0.30 2.511 6.299 153.22 153.22 180.00 90.00 S
CORE_RETAIL_WALL_EAST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
CORE_RETAIL_WALL_SOUTH_2 INT_WALL 0.30 2.511 6.299 24.38 24.38 180.00 90.00 S
CORE_RETAIL_WALL_NORTH INT_WALL 0.30 2.511 6.299 330.83 330.83 0.00 90.00 N
CORE_RETAIL_WALL_WEST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
POINT_OF_SALE_WALL_EAST_2 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
POINT_OF_SALE_WALL_NORTH INT_WALL 0.30 2.511 6.299 153.22 153.22 0.00 90.00 N
POINT_OF_SALE_WALL_EAST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
FRONT_RETAIL_WALL_WEST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
FRONT_RETAIL_WALL_NORTH INT_WALL 0.30 2.511 6.299 153.22 153.22 0.00 90.00 N
FRONT_RETAIL_WALL_WEST_2 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
FRONT_ENTRY_WALL_EAST INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
FRONT_ENTRY_WALL_NORTH INT_WALL 0.30 2.511 6.299 24.38 24.38 0.00 90.00 N
FRONT_ENTRY_WALL_WEST INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
BACK_SPACE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 759.78   0.00 90.00 N
CORE_RETAIL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3200.97   0.00 90.00 N
POINT_OF_SALE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 301.62   0.00 90.00 N
FRONT_RETAIL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 301.62   0.00 90.00 N
FRONT_ENTRY_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 24.00   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
SKYLIGHTS_R4C1 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C2 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C3 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C4 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C1 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C2 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C4 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C3 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C2 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C1 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C3 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C4 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C2 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C1 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C3 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C4 NONRESSKYLIGHT_U_0.69_SHGC_0.39 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 3.922 0.393 0.402 0.000 0.000 CurtainWall 3.786 0.393 0.402 No CORE_RETAIL_ROOF 180.00 0.00  
POINT_OF_SALE_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.57_SHGC_0.25   60.84 0.00 0.00 60.84 60.84 3.241 0.251 0.276             No POINT_OF_SALE_WALL_SOUTH 180.00 90.00 S
FRONT_RETAIL_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.57_SHGC_0.25   60.84 0.00 0.00 60.84 60.84 3.241 0.251 0.276             No FRONT_RETAIL_WALL_SOUTH 180.00 90.00 S
FRONT_ENTRY_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.57_SHGC_0.25   7.83 0.00 0.00 7.83 7.83 3.241 0.251 0.276             No FRONT_ENTRY_WALL_SOUTH 180.00 90.00 S
Total or Average             153.28 3.346 0.273 0.295                      
North Total or Average             0.00 - - -                      
Non-North Total or Average             153.28 3.346 0.273 0.295                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
BACK_SPACE_WALL_EAST_ROLLDOOR OVERHEAD DOOR_CON 6.464 200.000 7.43 BACK_SPACE_WALL_EAST
BACK_SPACE_WALL_NORTH_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR1 OVERHEAD DOOR_CON 6.464 200.000 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR2 OVERHEAD DOOR_CON 6.464 200.000 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR3 OVERHEAD DOOR_CON 6.464 200.000 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_WEST_ROLLDOOR OVERHEAD DOOR_CON 6.464 200.000 7.43 BACK_SPACE_WALL_WEST
CORE_RETAIL_WALL_WEST_2_DOOR3 SWINGING DOOR_CON 3.975 9.815 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_WEST_2_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_WEST_2_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_EAST_2_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 CORE_RETAIL_WALL_EAST_2
CORE_RETAIL_WALL_EAST_2_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 CORE_RETAIL_WALL_EAST_2
CORE_RETAIL_WALL_EAST_2_DOOR3 SWINGING DOOR_CON 3.975 9.815 1.95 CORE_RETAIL_WALL_EAST_2


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
SKYLIGHTS_R4C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
POINT_OF_SALE_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
FRONT_RETAIL_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
FRONT_ENTRY_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BACK_SPACE_LIGHTS BACK_SPACE BACK_SPACE GENERAL 9.0271 379.89 3429.30 LightsWired LTG_SCH_BACK 69.21 168.00 68.25 0.0000 Y 43.94
CORE_RETAIL_LIGHTS CORE_RETAIL CORE_RETAIL GENERAL 18.2986 1600.48 29286.64 LightsWired LTG_SCH_CORE 69.21 168.00 68.25 0.0000 Y 375.23
POINT_OF_SALE_LIGHTS POINT_OF_SALE POINT_OF_SALE GENERAL 18.2986 150.81 2759.62 LightsWired LTG_SCH_SALE 69.21 168.00 68.25 0.0000 Y 35.36
FRONT_RETAIL_LIGHTS FRONT_RETAIL FRONT_RETAIL GENERAL 18.2986 150.81 2759.62 LightsWired LTG_SCH_FRONT 69.21 168.00 68.25 0.0000 Y 35.36
FRONT_ENTRY_LIGHTS FRONT_ENTRY FRONT_ENTRY GENERAL 10.9792 12.00 131.75 LightsWired LTG_SCH_ENTRY 69.21 168.00 68.25 0.0000 Y 1.69
Interior Lighting Total       16.7250 2293.99 38366.92               491.56


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS 7996.55 AstronomicalClock -   83.77 83.77 125.74
Exterior Lighting Total 7996.55           125.74



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   54620.02 42960.28 11659.74 0.79 3.20    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   192415.35 140925.00 51490.35 0.73 3.10    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   27382.14 21229.37 6152.77 0.78 3.40    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed   27247.90 20757.18 6490.72 0.76 3.40    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   52416.7     9.94 9.94  
PSZ-AC:2 HP COOLING COIL   185683.5     9.89 9.89  
PSZ-AC:3 HP COOLING COIL   26309.7     10.52 10.52  
PSZ-AC:4 HP COOLING COIL   26217.1     10.58 10.58  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed 57427.9 31802.5 7.80 2
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed 200761.0 110727.4 7.15 2
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed 28804.9 15936.5 7.76 2
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed 28613.8 15814.7 7.78 2
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
FRONT_ENTRY UNIT HEATER HEATING COIL Coil:Heating:Electric   34182.56 1.00
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed   55191.94 3.40
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Electric   55191.94 1.00
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed   193914.98 3.40
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Electric   193914.98 1.00
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed   27716.05 3.40
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Electric   27716.05 1.00
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed   27566.68 3.40
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Electric   27566.68 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
FRONT_ENTRY UNIT HEATER FAN Fan:ConstantVolume 0.54 340.63 2.59 1643.14 635.51 1.00 1.34 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:10:00
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.60 966.87 2.80 4549.83 1622.12 1.00 1.21 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.60 966.87 8.55 13673.59 1599.45 1.00 1.16 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.58 966.87 1.36 2268.01 1662.00 1.00 1.28 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.58 966.87 1.31 2178.67 1662.00 1.00 1.28 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
None                


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 1.00 0.93



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BACK_SPACE 21604.64 24845.34 65.40 1.641 1.887 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 23.89 23.89 0.00879 34.21 0.01447 0.232 0.00
CORE_RETAIL 97854.55 112532.74 70.31 7.434 8.549 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 23.89 23.89 0.00912 34.16 0.01447 1.890 0.00
POINT_OF_SALE 15619.71 17962.66 119.11 1.187 1.365 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 23.89 23.89 0.00897 34.40 0.01447 0.178 0.00
FRONT_RETAIL 13295.50 15289.83 101.38 1.010 1.162 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 23.89 23.89 0.00905 34.40 0.01447 0.178 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.000 0.014 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 0.00 34.14 0.01455 34.40 0.01447 0.014 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BACK_SPACE 30399.49 37999.36 100.03 2.244 2.805 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.11 21.11 0.00776 -6.30 0.00230 0.232 0.00
CORE_RETAIL 68249.12 85311.40 53.30 4.923 6.154 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.11 21.11 0.00782 -6.30 0.00230 1.890 0.00
POINT_OF_SALE 14157.16 17696.45 117.34 1.048 1.311 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.11 21.11 0.00777 -6.30 0.00230 0.178 0.00
FRONT_RETAIL 14160.44 17700.54 117.37 1.049 1.311 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.11 21.11 0.00777 -6.30 0.00230 0.178 0.00
FRONT_ENTRY 27328.28 34160.35 2846.70 2.068 2.586 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:10:00 16.00 15.94 0.00610 -6.30 0.00230 0.014 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 1.89 1.89 2.80 2.80 2.8049 2.8049 2.8049 1.0000 1.0000
PSZ-AC:2 8.55 8.55 6.15 6.15 8.5489 8.5489 8.5489 1.0000 1.0000
PSZ-AC:3 1.36 1.36 1.31 1.31 1.3646 1.3646 1.3646 1.0000 1.0000
PSZ-AC:4 1.16 1.16 1.31 1.31 1.3109 1.3109 1.3109 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
FRONT_ENTRY UNIT HEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER FRONT_ENTRY UNIT HEATER 34182.560 34182.560 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:10:00 34182.56 34182.56 2.585560 15.94 10.65 0.00610278 27.11 16.67 0.00800000 -6.30 0.00229779 -6.30 0.0000 15.94 0.00610278 52.3811 34160.35 0.00 -999.00 -999.00
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:1 54620.020 42960.284 2.804860 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 27310.01 23245.79 1.869907 25.18 17.24 0.00948983 11.41 11.20 0.00850000 34.40 0.01447326 23.54 12.3846 23.89 0.00879220 45.9155 21588.50 0.00 -999.00 -999.00
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:1 55191.942 55191.942 2.804858 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 27595.97 22462.40 1.402429 18.69 12.98 0.00731151 32.22 18.37 0.00800000 -6.30 0.00229779 -6.30 16.5128 21.11 0.00776272 48.0784 30399.49 0.00 -999.00 -999.00
PSZ-AC:1_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:1 55191.942 55191.942 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 55191.94 44924.80 2.804858 18.69 12.98 0.00731151 32.22 18.37 0.00800000 -6.30 0.00229779 -6.30 8.2564 21.11 0.00776272 48.0784 30399.49 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:2 192415.350 140925.002 8.548940 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 96207.68 74119.47 5.699293 26.22 18.24 0.01030944 11.43 11.21 0.00850000 34.40 0.01447326 23.54 33.1678 23.89 0.00912524 47.6333 97718.03 0.00 -999.00 -999.00
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:2 193914.982 193914.982 8.548939 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 96957.49 87774.36 4.274469 14.87 10.71 0.00659568 32.22 18.37 0.00800000 -6.30 0.00229779 -6.30 44.2237 21.11 0.00781582 48.4019 68249.12 0.00 -999.00 -999.00
PSZ-AC:2_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:2 193914.982 193914.982 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 193914.98 175548.73 8.548939 14.87 10.71 0.00659568 32.22 18.37 0.00800000 -6.30 0.00229779 -6.30 22.1119 21.11 0.00781582 48.4019 68249.12 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:3 27382.140 21229.373 1.364630 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 13691.07 11322.28 0.909753 25.26 17.43 0.00969109 11.38 11.19 0.00850000 34.40 0.01447326 23.54 19.5791 23.89 0.00897318 46.8516 15619.71 0.00 -999.00 -999.00
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:3 27716.048 27716.048 1.364630 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13858.02 11940.73 0.682315 17.44 12.23 0.00705770 32.22 18.37 0.00800000 -6.30 0.00229779 -6.30 26.1055 21.11 0.00777227 48.1370 14157.16 0.00 -999.00 -999.00
PSZ-AC:3_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:3 27716.048 27716.048 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 27716.05 23881.45 1.364630 17.44 12.23 0.00705770 32.22 18.37 0.00800000 -6.30 0.00229779 -6.30 13.0527 21.11 0.00777227 48.1370 14157.16 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:4 27247.900 20757.178 1.310870 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 13623.95 10993.51 0.873913 25.50 17.67 0.00988496 11.38 11.19 0.00850000 34.40 0.01447326 23.54 20.3821 23.89 0.00905393 47.2672 13295.50 0.00 -999.00 -999.00
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoopHVAC PSZ-AC:4 27566.682 27566.682 1.310873 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13783.34 11583.74 0.655436 17.29 12.14 0.00702845 32.22 18.37 0.00800000 -6.30 0.00229779 -6.30 27.1760 21.11 0.00777233 48.1374 14160.44 0.00 -999.00 -999.00
PSZ-AC:4_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoopHVAC PSZ-AC:4 27566.682 27566.682 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 27566.68 23167.48 1.310873 17.29 12.14 0.00702845 32.22 18.37 0.00800000 -6.30 0.00229779 -6.30 13.5880 21.11 0.00777233 48.1374 14160.44 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
FRONT_ENTRY UNIT HEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER FRONT_ENTRY UNIT HEATER FRONT_ENTRY N/A N/A N/A Yes No unknown No 34182.560 34182.560 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 FRONT_ENTRY UNIT HEATER FAN Fan:ConstantVolume 2.585560 3.00177465   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:10:00 Sensible 34182.56 34182.56 1.0000 3.00177465 2.585560 15.94 10.65 0.00610278 31464.5 27.11 16.67 0.00800000 47653.0 -999.0 -999.00 -999.00 -999.00 0.000 34182.56 -6.30 0.00229779 -6.30 0.00000000 0.0000 15.95 0.00610278 15.94 0.00610278 52.3811 34160.35 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident CoolingDesignCapacity N/A No No unknown No 54620.020 42960.284 2.804860 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.4811 1004.8586 1.1610 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 2.804858 3.25637407   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 Sensible 27310.01 23245.79 1.0000 2.17091777 1.869907 25.18 17.24 0.00948983 49479.4 11.41 11.20 0.00850000 32906.0 -999.0 -999.00 -999.00 -999.00 0.000 27310.01 34.40 0.01447326 23.54 0.23158056 12.3846 23.89 0.00879220 23.89 0.00879220 45.9155 21588.50 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident HeatingDesignCapacity N/A Yes Yes unknown No 55191.942 55191.942 2.804858 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 2.804858 3.25637407   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 27595.97 22462.40 1.0000 1.62818704 1.402429 18.69 12.98 0.00731151 37320.9 32.22 18.37 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 27595.97 -6.30 0.00229779 -6.30 0.23158056 16.5128 20.94 0.00776272 21.11 0.00776272 48.0784 30399.49 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident HeatingDesignCapacity N/A Yes No unknown No 55191.942 55191.942 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 2.804858 3.25637407   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 55191.94 44924.80 1.0000 3.25637407 2.804858 18.69 12.98 0.00731151 37320.9 32.22 18.37 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 55191.94 -6.30 0.00229779 -6.30 0.23158056 8.2564 20.94 0.00776272 21.11 0.00776272 48.0784 30399.49 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident CoolingDesignCapacity N/A No No unknown No 192415.350 140925.002 8.548940 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.0047 1004.8586 1.1610 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 8.548939 9.92511718   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 Sensible 96207.68 74119.47 1.0000 6.61674586 5.699293 26.22 18.24 0.01030944 52628.1 11.43 11.21 0.00850000 32927.5 -999.0 -999.00 -999.00 -999.00 0.000 96207.68 34.40 0.01447326 23.54 1.89032875 33.1678 23.89 0.00912524 23.89 0.00912524 47.6333 97718.03 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident HeatingDesignCapacity N/A Yes Yes unknown No 193914.982 193914.982 8.548939 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 8.548939 9.92511718   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 96957.49 87774.36 1.0000 4.96255859 4.274469 14.87 10.71 0.00659568 31624.4 32.22 18.37 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 96957.49 -6.30 0.00229779 -6.30 1.89032875 44.2237 20.89 0.00781582 21.11 0.00781582 48.4019 68249.12 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident HeatingDesignCapacity N/A Yes No unknown No 193914.982 193914.982 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 8.548939 9.92511718   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 193914.98 175548.73 1.0000 9.92511718 8.548939 14.87 10.71 0.00659568 31624.4 32.22 18.37 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 193914.98 -6.30 0.00229779 -6.30 1.89032875 22.1119 20.89 0.00781582 21.11 0.00781582 48.4019 68249.12 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident CoolingDesignCapacity N/A No No unknown No 27382.140 21229.373 1.364630 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.8552 1004.8586 1.1610 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.364630 1.58430304   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 13691.07 11322.28 1.0000 1.05620228 0.909753 25.26 17.43 0.00969109 50073.8 11.38 11.19 0.00850000 32872.2 -999.0 -999.00 -999.00 -999.00 0.000 13691.07 34.40 0.01447326 23.54 0.17812154 19.5791 23.89 0.00897318 23.89 0.00897318 46.8516 15619.71 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident HeatingDesignCapacity N/A Yes Yes unknown No 27716.048 27716.048 1.364630 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.364630 1.58430304   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13858.02 11940.73 1.0000 0.79215152 0.682315 17.44 12.23 0.00705770 35401.7 32.22 18.37 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 13858.02 -6.30 0.00229779 -6.30 0.17812154 26.1055 21.00 0.00777227 21.11 0.00777227 48.1370 14157.16 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident HeatingDesignCapacity N/A Yes No unknown No 27716.048 27716.048 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.364630 1.58430304   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 27716.05 23881.45 1.0000 1.58430304 1.364630 17.44 12.23 0.00705770 35401.7 32.22 18.37 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 27716.05 -6.30 0.00229779 -6.30 0.17812154 13.0527 21.00 0.00777227 21.11 0.00777227 48.1370 14157.16 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident CoolingDesignCapacity N/A No No unknown No 27247.900 20757.178 1.310870 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.2156 1004.8586 1.1610 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.310873 1.52189233   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 Sensible 13623.95 10993.51 1.0000 1.01459288 0.873913 25.50 17.67 0.00988496 50813.2 11.38 11.19 0.00850000 32872.7 -999.0 -999.00 -999.00 -999.00 0.000 13623.95 34.40 0.01447326 23.54 0.17812154 20.3821 23.89 0.00905393 23.89 0.00905393 47.2672 13295.50 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HEATING COIL Coil:Heating:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident HeatingDesignCapacity N/A Yes Yes unknown No 27566.682 27566.682 1.310873 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.310873 1.52189233   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13783.34 11583.74 1.0000 0.76094617 0.655436 17.29 12.14 0.00702845 35178.8 32.22 18.37 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 13783.34 -6.30 0.00229779 -6.30 0.17812154 27.1760 21.00 0.00777233 21.11 0.00777233 48.1374 14160.44 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4_SUPPHEATCOIL COIL:HEATING:ELECTRIC AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident HeatingDesignCapacity N/A Yes No unknown No 27566.682 27566.682 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.310873 1.52189233   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 27566.68 23167.48 1.0000 1.52189233 1.310873 17.29 12.14 0.00702845 35178.8 32.22 18.37 0.00800000 52862.6 -999.0 -999.00 -999.00 -999.00 0.000 27566.68 -6.30 0.00229779 -6.30 0.17812154 13.5880 21.00 0.00777233 21.11 0.00777233 48.1374 14160.44 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BACK_SPACE 2680.50 2428.33 786.00
CORE_RETAIL 2876.17 1764.50 363.83
POINT_OF_SALE 3037.00 1521.83 295.17
FRONT_RETAIL 2981.50 1799.33 474.50
FRONT_ENTRY 3966.33 4425.17 3584.50
Facility 4516.33 4510.33 3585.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BACK_SPACE 29.17 19.17 0.00 0.00
CORE_RETAIL 0.00 0.00 0.00 0.00
POINT_OF_SALE 17.67 103.50 0.00 0.00
FRONT_RETAIL 24.67 41.50 0.00 0.00
FRONT_ENTRY 356.67 0.00 353.50 0.00
Facility 391.83 114.00 353.50 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BACK_SPACE 4.05 8.18 2317.33 0.366 0.028 0.000 0.000
CORE_RETAIL 128.05 258.43 9762.95 0.710 0.006 0.000 0.000
POINT_OF_SALE 12.07 24.35 919.94 0.710 0.032 0.000 0.000
FRONT_RETAIL 12.07 24.35 919.94 0.710 0.032 0.000 0.000
FRONT_ENTRY 0.96 1.94 73.20 0.000 23.306 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BACK_SPACE 4.05 8.18 2317.33 0.352 0.000 0.000 0.000
CORE_RETAIL 128.05 258.43 9762.95 0.680 0.000 0.000 0.000
POINT_OF_SALE 12.07 24.35 919.94 0.681 0.000 0.000 0.000
FRONT_RETAIL 12.07 24.35 919.94 0.681 0.000 0.000 0.000
FRONT_ENTRY 0.96 1.94 73.20 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BACK_SPACE PSZ-AC:1 4.05 8.18 2317.33 379.89 0.2316 0.232
CORE_RETAIL PSZ-AC:2 128.05 258.43 9762.95 1600.48 1.8903 1.890
POINT_OF_SALE PSZ-AC:3 12.07 24.35 919.94 150.81 0.1781 0.178
FRONT_RETAIL PSZ-AC:4 12.07 24.35 919.94 150.81 0.1781 0.178
FRONT_ENTRY   0.96 1.94 73.20 12.00   0.014
Total Facility   157.19 317.25 13993.36 2293.99 2.4782 2.492


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BACK_SPACE 4567776.63 0.00 4567776.63 1070283.32 5638059.95 7303124.67 3444.73 5315.27 0.00 985.65
CORE_RETAIL 35921589.38 0.00 35921589.38 917744.04 36839333.42 59613407.55 3481.57 5278.43 0.00 365.83
POINT_OF_SALE 3573233.99 0.00 3573233.99 488110.02 4061344.01 5617240.89 3445.32 5314.68 0.00 1214.83
FRONT_RETAIL 3526313.30 0.00 3526313.30 488110.02 4014423.32 5617240.89 3445.24 5314.76 0.00 1059.38
FRONT_ENTRY 0.00 0.00 0.00 8338595.86 8338595.86 446965.66 8760.00 0.00 0.00 0.00
Total Facility 47588913.30 0.00 47588913.30 11302843.27 58891756.56 78597979.65 8760.00 5330.71 0.00 1411.74


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BACK_SPACE 0.2316 0.0000 0.2316 0.0176 0.2492 0.2316 0.00 4913.00 0.00
CORE_RETAIL 1.8903 0.0000 1.8903 0.0151 1.9054 1.8903 0.00 4913.00 0.00
POINT_OF_SALE 0.1781 0.0000 0.1781 0.0080 0.1862 0.1781 0.00 4913.00 0.00
FRONT_RETAIL 0.1781 0.0000 0.1781 0.0080 0.1862 0.1781 0.00 4913.00 0.00
FRONT_ENTRY 0.0000 0.0000 0.0000 0.4658 0.4658 0.0142 4913.00 0.00 0.00
Total Facility 2.4782 0.0000 2.4782 0.5146 2.9928 2.4923 4913.00 4913.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 6156753.23 0.00 6156753.23 7303124.67 3405.51 5.01 5349.48 984.07
PSZ-AC:2 48417507.94 0.00 48417507.94 59613407.55 3481.57 0.00 5278.43 365.83
PSZ-AC:3 4816242.49 0.00 4816242.49 5617240.89 3390.91 4.40 5364.69 1211.84
PSZ-AC:4 4752999.66 0.00 4752999.66 5617240.89 3419.05 2.82 5338.13 1057.43


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.3121 0.0000 0.3121 0.2316 0.00 0.00 4913.00
PSZ-AC:2 2.5479 0.0000 2.5479 1.8903 0.00 0.00 4913.00
PSZ-AC:3 0.2401 0.0000 0.2401 0.1781 0.00 0.00 4913.00
PSZ-AC:4 0.2401 0.0000 0.2401 0.1781 0.00 0.00 4913.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 5897.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 5278.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 6124.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 5970.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.3122 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 2.5484 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.2401 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.2401 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Surfaces by Class

Total Outdoors
Wall 26 10
Floor 5 5
Roof 5 5
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 19 19
Door 13 13
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 4
Conditioned Zones 5
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 481
Defaulted Fields 485
Fields with Defaults 1429
Autosized Fields 96
Autosizable Fields 234
Autocalculated Fields 78
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1695.42 3689.94 19-FEB-07:40 183889.95 12-FEB-07:30
Electricity:Building 685.86 3689.94 01-JAN-00:10 45271.12 02-JAN-09:10
Electricity:Zone:BACK_SPACE 93.71 625.28 01-JAN-00:10 5837.79 02-JAN-09:10
Electricity:SpaceType:GENERAL 685.86 3689.94 01-JAN-00:10 45271.12 02-JAN-09:10
InteriorLights:Electricity 491.57 1918.35 01-JAN-00:10 34530.23 02-JAN-09:10
InteriorLights:Electricity:Zone:BACK_SPACE 43.94 171.46 01-JAN-00:10 3086.37 02-JAN-09:10
InteriorLights:Electricity:SpaceType:GENERAL 491.57 1918.35 01-JAN-00:10 34530.23 02-JAN-09:10
LightsWired:InteriorLights:Electricity 491.57 1918.35 01-JAN-00:10 34530.23 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE 43.94 171.46 01-JAN-00:10 3086.37 02-JAN-09:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 491.57 1918.35 01-JAN-00:10 34530.23 02-JAN-09:10
Electricity:Zone:CORE_RETAIL 459.16 2229.58 01-JAN-00:10 30997.56 02-JAN-09:10
InteriorLights:Electricity:Zone:CORE_RETAIL 375.23 1464.33 01-JAN-00:10 26357.98 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL 375.23 1464.33 01-JAN-00:10 26357.98 02-JAN-09:10
Electricity:Zone:POINT_OF_SALE 88.05 618.40 01-JAN-00:10 5396.37 02-JAN-09:10
InteriorLights:Electricity:Zone:POINT_OF_SALE 35.36 137.98 01-JAN-00:10 2483.65 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE 35.36 137.98 01-JAN-00:10 2483.65 02-JAN-09:10
Electricity:Zone:FRONT_RETAIL 43.27 210.09 01-JAN-00:10 2920.83 02-JAN-09:10
InteriorLights:Electricity:Zone:FRONT_RETAIL 35.36 137.98 01-JAN-00:10 2483.65 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL 35.36 137.98 01-JAN-00:10 2483.65 02-JAN-09:10
Electricity:Zone:FRONT_ENTRY 1.69 6.59 01-JAN-00:10 118.58 02-JAN-09:10
InteriorLights:Electricity:Zone:FRONT_ENTRY 1.69 6.59 01-JAN-00:10 118.58 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY 1.69 6.59 01-JAN-00:10 118.58 02-JAN-09:10
InteriorEquipment:Electricity 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
InteriorEquipment:Electricity:Zone:BACK_SPACE 49.77 453.82 01-JAN-00:10 2751.42 02-JAN-09:10
InteriorEquipment:Electricity:SpaceType:GENERAL 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE 49.77 453.82 01-JAN-00:10 2751.42 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
InteriorEquipment:Electricity:Zone:CORE_RETAIL 83.93 765.25 01-JAN-00:10 4639.58 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL 83.93 765.25 01-JAN-00:10 4639.58 02-JAN-09:10
InteriorEquipment:Electricity:Zone:POINT_OF_SALE 52.69 480.42 01-JAN-00:10 2912.71 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE 52.69 480.42 01-JAN-00:10 2912.71 02-JAN-09:10
InteriorEquipment:Electricity:Zone:FRONT_RETAIL 7.91 72.11 01-JAN-00:10 437.18 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL 7.91 72.11 01-JAN-00:10 437.18 02-JAN-09:10
ElectricityPurchased:Facility 1695.42 3689.94 19-FEB-07:40 183889.95 12-FEB-07:30
ElectricityPurchased:Plant 1695.42 3689.94 19-FEB-07:40 183889.95 12-FEB-07:30
Cogeneration:ElectricityPurchased 1695.42 3689.94 19-FEB-07:40 183889.95 12-FEB-07:30
General:Cogeneration:ElectricityPurchased 1695.42 3689.94 19-FEB-07:40 183889.95 12-FEB-07:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1695.42 3689.94 19-FEB-07:40 183889.95 12-FEB-07:30
ElectricityNet:Plant 1695.42 3689.94 19-FEB-07:40 183889.95 12-FEB-07:30
Cogeneration:ElectricityNet 1695.42 3689.94 19-FEB-07:40 183889.95 12-FEB-07:30
General:Cogeneration:ElectricityNet 1695.42 3689.94 19-FEB-07:40 183889.95 12-FEB-07:30
Electricity:HVAC 859.90 0.00 01-JAN-00:10 172099.20 12-FEB-07:30
Fans:Electricity 443.14 0.00 01-JAN-00:10 24313.24 06-FEB-13:00
General:Fans:Electricity 443.14 0.00 01-JAN-00:10 24313.24 06-FEB-13:00
Heating:Electricity 53.56 0.00 01-JAN-00:10 148607.53 12-FEB-07:30
General:Heating:Electricity 53.56 0.00 01-JAN-00:10 148607.53 12-FEB-07:30
Cooling:Electricity 363.21 0.00 01-JAN-00:10 70420.62 08-JUL-14:30
General:Cooling:Electricity 363.21 0.00 01-JAN-00:10 70420.62 08-JUL-14:30
ExteriorLights:Electricity 125.74 0.00 01-JAN-07:50 7996.55 01-JAN-00:10
General:ExteriorLights:Electricity 125.74 0.00 01-JAN-07:50 7996.55 01-JAN-00:10
Electricity:Plant 23.91 0.00 01-JAN-00:10 2331.54 01-FEB-12:10
WaterSystems:Electricity 23.91 0.00 01-JAN-00:10 2331.54 01-FEB-12:10
Water Heater:WaterSystems:Electricity 23.91 0.00 01-JAN-00:10 2331.54 01-FEB-12:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 134.99 0.00 01-JAN-00:10 0.00 02-JAN-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 2257.13 0.00 01-JAN-00:10 332101.50 08-JUL-14:00
EnergyTransfer:Building 854.98 0.00 01-JAN-00:10 128644.91 13-FEB-06:10
EnergyTransfer:Zone:BACK_SPACE 118.25 0.00 01-JAN-00:10 44089.37 12-FEB-07:10
Heating:EnergyTransfer 65.24 0.00 01-JAN-00:10 124016.06 12-FEB-08:10
Heating:EnergyTransfer:Zone:BACK_SPACE 29.92 0.00 01-JAN-00:10 44089.37 12-FEB-07:10
General:Heating:EnergyTransfer 65.24 0.00 01-JAN-00:10 124016.06 12-FEB-08:10
General:Heating:EnergyTransfer:Zone:BACK_SPACE 29.92 0.00 01-JAN-00:10 44089.37 12-FEB-07:10
Cooling:EnergyTransfer 789.74 0.00 01-JAN-00:10 112485.52 08-JUL-14:50
Cooling:EnergyTransfer:Zone:BACK_SPACE 88.33 0.00 01-JAN-00:10 17403.97 08-JUL-15:50
General:Cooling:EnergyTransfer 789.74 0.00 01-JAN-00:10 112485.52 08-JUL-14:50
General:Cooling:EnergyTransfer:Zone:BACK_SPACE 88.33 0.00 01-JAN-00:10 17403.97 08-JUL-15:50
EnergyTransfer:Zone:CORE_RETAIL 542.57 0.00 01-JAN-00:10 81400.02 13-FEB-06:10
Heating:EnergyTransfer:Zone:CORE_RETAIL 10.49 0.00 01-JAN-00:10 76497.40 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:CORE_RETAIL 10.49 0.00 01-JAN-00:10 76497.40 13-FEB-06:10
Cooling:EnergyTransfer:Zone:CORE_RETAIL 532.08 0.00 01-JAN-00:10 72855.67 07-JUL-14:50
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL 532.08 0.00 01-JAN-00:10 72855.67 07-JUL-14:50
EnergyTransfer:Zone:POINT_OF_SALE 103.96 0.00 01-JAN-00:10 21212.36 12-FEB-07:20
Heating:EnergyTransfer:Zone:POINT_OF_SALE 4.39 0.00 01-JAN-00:10 21212.36 12-FEB-07:20
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE 4.39 0.00 01-JAN-00:10 21212.36 12-FEB-07:20
Cooling:EnergyTransfer:Zone:POINT_OF_SALE 99.56 0.00 01-JAN-00:10 14001.97 10-OCT-14:10
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE 99.56 0.00 01-JAN-00:10 14001.97 10-OCT-14:10
EnergyTransfer:Zone:FRONT_RETAIL 76.88 0.00 01-JAN-00:10 20598.24 12-FEB-07:10
Heating:EnergyTransfer:Zone:FRONT_RETAIL 7.12 0.00 01-JAN-00:10 20598.24 12-FEB-07:10
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL 7.12 0.00 01-JAN-00:10 20598.24 12-FEB-07:10
Cooling:EnergyTransfer:Zone:FRONT_RETAIL 69.76 0.00 01-JAN-00:10 12033.75 10-OCT-14:10
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL 69.76 0.00 01-JAN-00:10 12033.75 10-OCT-14:10
EnergyTransfer:Zone:FRONT_ENTRY 13.32 0.00 01-JAN-00:10 25167.86 07-JAN-18:00
Heating:EnergyTransfer:Zone:FRONT_ENTRY 13.32 0.00 01-JAN-00:10 25167.86 07-JAN-18:00
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY 13.32 0.00 01-JAN-00:10 25167.86 07-JAN-18:00
Cooling:EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 68.94 16-JAN-20:10
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 68.94 16-JAN-20:10
EnergyTransfer:HVAC 1402.15 0.00 01-JAN-00:10 220365.63 08-JUL-14:00
HeatingCoils:EnergyTransfer 107.71 0.00 01-JAN-00:10 194032.47 12-FEB-08:10
CoolingCoils:EnergyTransfer 1294.44 0.00 01-JAN-00:10 220365.63 08-JUL-14:00
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BACK_SPACE 0.000 0.000 29.917 -88.331 0.000 0.000 5.066 43.937 49.772 0.000 0.000 0.613 0.000 0.000 0.000 0.000 -10.559 -30.415
CORE_RETAIL 0.000 0.000 10.489 -532.069 0.000 0.000 159.071 375.227 83.928 46.290 0.000 0.444 0.000 0.000 -18.618 0.000 -10.392 -114.370
POINT_OF_SALE 0.000 0.000 4.393 -99.563 0.000 0.000 14.767 35.357 52.690 47.479 0.000 0.278 0.000 0.000 -28.120 0.000 -5.153 -22.127
FRONT_RETAIL 0.000 0.000 7.123 -69.760 0.000 0.000 14.903 35.357 7.908 47.545 0.000 0.279 0.002 0.000 -27.208 0.000 -4.953 -11.194
FRONT_ENTRY 13.322 -0.000 0.000 0.000 0.000 0.000 1.212 1.688 0.000 6.121 0.000 0.412 3.751 0.000 -3.225 0.000 -23.281 0.000
Total Facility 13.322 -0.000 51.922 -789.723 0.000 0.000 195.018 491.565 194.299 147.435 0.000 2.027 3.753 0.000 -77.171 0.000 -54.338 -178.107


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BACK_SPACE 16-JUL-18:06 0.00 0.00 0.00 -37161.84 0.00 0.00 0.00 171.46 453.82 0.00 0.00 449.71 36086.85 0.00 -0.00 0.00 0.00 0.00
CORE_RETAIL 11-JUN-08:62 0.00 0.00 0.00 -169516.36 0.00 0.00 1599.50 2928.66 1546.53 3375.76 0.00 0.00 160121.43 0.00 -0.00 0.00 -55.52 0.00
POINT_OF_SALE 11-JUN-18:08 0.00 0.00 0.00 -18228.88 0.00 0.00 0.00 137.98 480.42 1440.73 0.00 227.18 15942.57 0.00 -0.00 0.00 0.00 0.00
FRONT_RETAIL 27-AUG-18:08 0.00 0.00 0.00 -17468.37 0.00 0.00 0.00 137.98 72.11 969.77 0.00 272.50 16016.01 0.00 -0.00 0.00 0.00 0.00
FRONT_ENTRY 16-JAN-20:07 0.00 -206.81 0.00 0.00 0.00 0.00 0.00 6.59 0.00 0.00 0.00 0.00 432.45 0.00 -203.87 0.00 -28.36 0.00
Total Facility 11-JUN-08:62 0.00 0.00 0.00 -173366.95 0.00 0.00 2012.63 3836.69 3580.30 4628.69 0.00 0.00 159558.52 0.00 0.00 0.00 -249.87 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BACK_SPACE 24-DEC-07:02 0.00 0.00 63117.55 0.00 0.00 0.00 0.00 171.46 453.82 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -992.36 -62750.48
CORE_RETAIL 18-JAN-06:12 0.00 0.00 152164.25 0.00 0.00 0.00 0.00 1464.33 1020.33 0.00 0.00 0.00 0.00 0.00 -1083.97 0.00 -167.59 -153397.35
POINT_OF_SALE 19-JAN-05:01 0.00 0.00 30225.69 0.00 0.00 0.00 0.00 137.98 640.56 0.00 0.00 0.00 0.00 0.00 -1143.14 0.00 -397.15 -29463.94
FRONT_RETAIL 24-DEC-07:02 0.00 0.00 30730.69 0.00 0.00 0.00 0.00 137.98 72.11 0.00 0.00 0.00 0.00 0.00 -1009.01 0.00 -460.34 -29471.43
FRONT_ENTRY 07-JAN-18:00 25166.98 0.00 0.00 0.00 0.00 0.00 116.56 118.58 0.00 0.00 0.00 0.00 394.34 0.00 -421.94 0.00 -25374.51 0.00
Total Facility 13-FEB-05:01 0.00 0.00 224539.25 0.00 0.00 0.00 0.00 1918.35 2362.12 0.00 0.00 0.00 0.00 0.00 -9200.79 0.00 -9237.68 -210381.24



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 2.8049 0.0000 8.1781 1.0000 Calculated from schedules 0.2316 2.8049 0.1227 1.0000 Not calculated 0.2316 0.0826    
PSZ-AC:2 8.5489 0.0000 258.4342 1.0000 Calculated from schedules 1.8903 8.5489 0.2211 1.0000 Not calculated 1.8903 0.2211    
PSZ-AC:3 1.3646 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.3646 0.1305 1.0000 Not calculated 0.1781 0.1305    
PSZ-AC:4 1.3109 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.3109 0.1533 1.0000 Not calculated 0.1781 0.1359    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 2.8049 0.0000 8.1781 1.0000 Calculated from schedules 0.2316 2.8049 1.0000 1.0000 Not calculated 0.2316 0.0826    
PSZ-AC:2 8.5489 0.0000 258.4342 1.0000 Calculated from schedules 1.8903 8.5489 1.0000 1.0000 Not calculated 1.8903 0.2211    
PSZ-AC:3 1.3646 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.3646 1.0000 1.0000 Not calculated 0.1781 0.1305    
PSZ-AC:4 1.3109 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.3109 1.0000 1.0000 Not calculated 0.1781 0.1359    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BACK_SPACE PSZ-AC:1 0.000000 8.1781 0.000610 379.89 0.2316 1.0000 0.2316 1.000 0.2316
CORE_RETAIL PSZ-AC:2 0.000000 258.4342 0.001181 1600.48 1.8903 1.0000 1.8903 1.000 1.8903
POINT_OF_SALE PSZ-AC:3 0.000000 24.3517 0.001181 150.81 0.1781 1.0000 0.1781 1.000 0.1781
FRONT_RETAIL PSZ-AC:4 0.000000 24.3517 0.001181 150.81 0.1781 1.0000 0.1781 1.000 0.1781


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.18 0.000610 379.8900 0.2316 0.2316 0.2316
PSZ-AC:2 0.000000 258.43 0.001181 1600.4829 1.8903 1.8903 1.8903
PSZ-AC:3 0.000000 24.35 0.001181 150.8100 0.1781 0.1781 0.1781
PSZ-AC:4 0.000000 24.35 0.001181 150.8100 0.1781 0.1781 0.1781


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BACK_SPACE PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 2.8049 2.8049 2.8049 No 0.2316 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_RETAIL PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 8.5489 8.5489 8.5489 No 1.8903 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
POINT_OF_SALE PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3646 1.3646 1.3646 No 0.1781 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FRONT_RETAIL PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3109 1.3109 1.3109 No 0.1781 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 2.8049 2.8049 2.8049 2.8049 0.2316 1.0000
PSZ-AC:2 8.5489 8.5489 8.5489 8.5489 1.8903 1.0000
PSZ-AC:3 1.3646 1.3646 1.3646 1.3646 0.1781 1.0000
PSZ-AC:4 1.3109 1.3109 1.3109 1.3109 0.1781 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BACK_SPACE PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 2.8049 2.8049 2.8049 No 0.2316 0.0826 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_RETAIL PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 8.5489 8.5489 8.5489 No 1.8903 0.3072 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
POINT_OF_SALE PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3646 1.3646 1.3646 No 0.1781 0.1359 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FRONT_RETAIL PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3109 1.3109 1.3109 No 0.1781 0.1359 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 2.8049 2.8049 2.8049 2.8049 0.2316 1.0000
PSZ-AC:2 8.5489 8.5489 8.5489 8.5489 1.8903 1.0000
PSZ-AC:3 1.3646 1.3646 1.3646 1.3646 0.1781 1.0000
PSZ-AC:4 1.3109 1.3109 1.3109 1.3109 0.1781 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Total gross floor area [m2] 2293.99
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BACK_SPACE 379.89 379.89 0.00 94.22
CORE_RETAIL 1600.48 1600.48 0.00 94.22
POINT_OF_SALE 150.81 150.81 0.00 94.22
FRONT_RETAIL 150.81 150.81 0.00 94.22
FRONT_ENTRY 12.00 12.00 0.00 94.22
Totals 2293.99 2293.99 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 353.50
Number of hours cooling loads not met 0.00
Number of hours not met 353.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 53.56 148607.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 363.21 70420.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 491.57 34530.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 125.74 7996.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 194.30 10740.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 443.14 24313.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 23.91 2331.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 194.30 1695.42
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 194.30 1695.42


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 214.28
Space Heating 23.35
Space Cooling 158.33
Fans (All) 193.18
Service Water Heating 10.42
Receptacle Equipment 84.70
Miscellaneous (All) 739.07
Subtotal 739.07


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 28.99
Space Heating 3.16
Space Cooling 21.42
Fans (All) 26.14
Service Water Heating 1.41
Receptacle Equipment 11.46
Miscellaneous 7.42


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
FRONTENTRY_COILSCHED 8760. 8760.
FRONTENTRY_FANSCHED 8760. 8760.
LTG_SCH_ENTRY 3609. 8760.
LTG_SCH_CORE 3609. 8760.
LTG_SCH_BACK 3609. 8760.
LTG_SCH_SALE 3609. 8760.
LTG_SCH_FRONT 3609. 8760.
BLDG_OCC_SCH 2410. 4950.
BLDG_EQUIP_SCH 4552. 8760.
BLDG_ELEVATORS 2743. 4950.
INFIL_SCH 3551. 3551.
INFIL_HALF_ON_SCH 6156. 8760.
INFIL_DOOR_OPENING_SCH 2477. 4380.
BLDG_SWH_SCH 2009. 4950.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6543. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4950. 4950.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
INFIL_SCH_PNNL 4774. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4950. 4950.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
SZ_SYSTEM_OA_MAX_FRAC_SCH 6570. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_FRONTENTRY_STD2013 FRONT_ENTRY HEATING SP January 16.00 365 15.56 365
HTGSETP_SCH_NO_OPTIMUM BACK_SPACE DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_NO_SETBACK BACK_SPACE DUAL SP CONTROL July 23.89 365 23.89 365
HTGSETP_SCH_YES_OPTIMUM CORE_RETAIL DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM CORE_RETAIL DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BACK_SPACE 8760.00 0.00 0.00 0.00 0.00
CORE_RETAIL 8752.17 7.83 0.00 0.00 0.00
POINT_OF_SALE 8760.00 0.00 0.00 0.00 0.00
FRONT_RETAIL 8760.00 0.00 0.00 0.00 0.00
FRONT_ENTRY 7085.67 1285.17 389.17 0.00 0.00
Min 7085.67 0.00 0.00 0.00 0.00
Max 8760.00 1285.17 389.17 0.00 0.00
Average 8423.57 258.60 77.83 0.00 0.00
Sum 42117.83 1293.00 389.17 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BACK_SPACE 16872.00 0.00 0.00 0.00 0.00
CORE_RETAIL 609599.00 0.00 0.00 0.00 0.00
POINT_OF_SALE 56000.00 0.00 0.00 0.00 0.00
FRONT_RETAIL 56000.00 0.00 0.00 0.00 0.00
FRONT_ENTRY 1319.83 349.67 250.50 0.00 0.00
Min 1319.83 0.00 0.00 0.00 0.00
Max 609599.00 349.67 250.50 0.00 0.00
Average 147958.17 69.93 50.10 0.00 0.00
Sum 739790.83 349.67 250.50 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BACK_SPACE 8735.17 24.83 0.00 0.00 0.00
CORE_RETAIL 7763.00 997.00 0.00 0.00 0.00
POINT_OF_SALE 8753.50 6.50 0.00 0.00 0.00
FRONT_RETAIL 8697.00 63.00 0.00 0.00 0.00
FRONT_ENTRY 5731.33 2923.17 105.50 0.00 0.00
Min 5731.33 6.50 0.00 0.00 0.00
Max 8753.50 2923.17 105.50 0.00 0.00
Average 7936.00 802.90 21.10 0.00 0.00
Sum 39680.00 4014.50 105.50 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BACK_SPACE 16871.17 0.83 0.00 0.00 0.00
CORE_RETAIL 608082.17 1516.83 0.00 0.00 0.00
POINT_OF_SALE 55995.33 4.67 0.00 0.00 0.00
FRONT_RETAIL 55881.33 118.67 0.00 0.00 0.00
FRONT_ENTRY 1190.50 645.83 83.67 0.00 0.00
Min 1190.50 0.83 0.00 0.00 0.00
Max 608082.17 1516.83 83.67 0.00 0.00
Average 147604.10 457.37 16.73 0.00 0.00
Sum 738020.50 2286.83 83.67 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:00

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 12998056.62 922.77 20-JAN-16:00 17.20 12.77 0.230638E+09 326.80 31-JAN-15:00 20.00 13.58
February 0.336075E+09 5096.62 28-FEB-15:50 23.58 12.73 0.228376E+09 326.81 18-FEB-12:50 23.58 12.73
March 0.203062E+10 11553.72 30-MAR-20:25 24.15 16.94 0.291334E+09 326.82 29-MAR-14:09 24.15 16.94
April 0.510072E+10 12511.82 17-APR-22:00 20.00 13.85 0.284464E+09 326.82 29-APR-15:20 23.90 18.06
May 0.101831E+11 27042.87 29-MAY-18:08 29.13 20.06 0.297375E+09 326.82 27-MAY-13:30 29.13 20.06
June 0.160679E+11 36555.74 25-JUN-18:08 30.40 22.72 0.293529E+09 326.82 17-JUN-10:30 30.40 22.72
July 0.182804E+11 37164.39 16-JUL-18:06 32.52 22.45 0.291629E+09 326.82 01-JUL-10:09 32.52 22.45
August 0.189471E+11 36665.33 13-AUG-18:08 30.92 21.87 0.304130E+09 326.83 31-AUG-14:09 23.90 20.77
September 0.114015E+11 31982.87 07-SEP-20:10 26.93 22.31 0.287480E+09 326.83 16-SEP-13:50 26.88 23.85
October 0.458001E+10 13449.58 10-OCT-20:33 21.47 18.94 0.286588E+09 326.82 17-OCT-14:00 26.10 21.16
November 0.123582E+10 5972.71 05-NOV-15:30 24.15 18.21 0.264249E+09 326.81 02-NOV-14:00 24.15 18.21
December 0.156777E+09 3070.73 13-DEC-13:15 19.83 17.21 0.249232E+09 326.80 13-DEC-15:00 17.20 16.88
                     
Annual Sum or Average 0.883330E+11         0.330903E+10        
Minimum of Months 12998056.62 922.77   17.20 12.73 0.228376E+09 326.80   17.20 12.73
Maximum of Months 0.189471E+11 37164.39   32.52 22.72 0.304130E+09 326.83   32.52 23.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.159291E+11 45800.55 14-JAN-06:06 -6.7 -7.8 0.745539E+10 10327.59 31-JAN-15:00 20.00 13.58
February 0.196665E+11 44373.19 04-FEB-06:06 -6.0 -7.9 0.737346E+10 10327.34 22-FEB-15:00 14.40 13.41
March 0.356486E+11 53944.74 30-MAR-14:30 27.80 17.47 0.934838E+10 10327.94 31-MAR-14:20 13.87 12.50
April 0.450024E+11 56655.66 19-APR-14:40 26.33 17.56 0.902573E+10 10327.99 22-APR-12:20 21.10 17.79
May 0.583155E+11 126675.70 07-MAY-08:62 21.47 18.03 0.940046E+10 10328.02 25-MAY-14:09 20.10 18.53
June 0.683273E+11 169514.39 11-JUN-08:62 21.97 12.99 0.927877E+10 10327.78 26-JUN-14:30 30.85 23.95
July 0.715275E+11 128017.57 25-JUL-06:02 21.10 18.18 0.921950E+10 10328.05 29-JUL-12:00 20.00 20.00
August 0.736230E+11 135107.63 26-AUG-06:02 21.78 17.46 0.961475E+10 10327.80 24-AUG-14:30 21.78 17.46
September 0.554721E+11 127893.07 25-SEP-06:03 19.40 16.66 0.908705E+10 10327.98 02-SEP-11:50 19.40 16.66
October 0.406501E+11 104778.93 18-OCT-06:03 19.90 19.90 0.909023E+10 10327.84 16-OCT-14:09 19.90 19.90
November 0.275289E+11 37856.00 06-NOV-15:10 20.60 10.48 0.846908E+10 10327.90 02-NOV-14:39 20.60 10.48
December 0.203875E+11 39537.40 03-DEC-08:07 -3.4 -5.8 0.821767E+10 10327.47 14-DEC-15:00 15.00 10.77
                     
Annual Sum or Average 0.532079E+12         0.105580E+12        
Minimum of Months 0.159291E+11 37856.00   -6.7 -7.9 0.737346E+10 10327.34   13.87 10.48
Maximum of Months 0.736230E+11 169514.39   27.80 19.90 0.961475E+10 10328.05   30.85 23.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.279323E+10 7600.29 28-JAN-15:10 12.20 4.56 0.784593E+09 973.16 20-JAN-15:09 12.20 4.56
February 0.368263E+10 11370.40 21-FEB-14:40 22.43 10.97 0.738579E+09 973.15 16-FEB-15:39 22.43 10.97
March 0.639484E+10 12486.46 30-MAR-20:10 24.32 16.97 0.890073E+09 973.18 31-MAR-14:09 13.58 12.42
April 0.717729E+10 12455.23 16-APR-18:10 25.03 16.28 0.850446E+09 973.20 22-APR-10:39 19.80 17.06
May 0.922479E+10 16116.98 29-MAY-18:08 29.13 20.06 0.885489E+09 973.20 27-MAY-10:39 29.13 20.06
June 0.117999E+11 18230.81 11-JUN-18:08 32.02 20.92 0.873983E+09 973.16 26-JUN-14:39 30.93 23.89
July 0.131781E+11 17757.60 02-JUL-18:08 30.22 21.76 0.868383E+09 973.20 29-JUL-11:09 19.50 19.50
August 0.147975E+11 18114.64 27-AUG-18:08 29.82 21.80 0.905609E+09 973.17 24-AUG-14:30 29.82 21.80
September 0.113911E+11 17513.02 08-SEP-20:08 27.43 21.82 0.856053E+09 973.20 16-SEP-10:39 23.53 22.28
October 0.890267E+10 16809.06 09-OCT-18:08 24.13 18.81 0.861092E+09 973.16 23-OCT-14:09 17.80 13.42
November 0.616477E+10 11817.44 06-NOV-14:30 20.60 10.97 0.821837E+09 973.20 04-NOV-13:00 20.60 10.97
December 0.405743E+10 10042.73 12-DEC-14:00 22.80 17.07 0.833906E+09 973.20 13-DEC-15:00 17.20 16.88
                     
Annual Sum or Average 0.995643E+11         0.101700E+11        
Minimum of Months 0.279323E+10 7600.29   12.20 4.56 0.738579E+09 973.15   12.20 4.56
Maximum of Months 0.147975E+11 18230.81   32.02 21.82 0.905609E+09 973.20   30.93 23.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.141310E+10 5446.60 28-JAN-15:00 12.20 4.56 0.752042E+09 973.17 20-JAN-15:00 12.20 4.56
February 0.212970E+10 9303.88 21-FEB-14:30 22.25 10.82 0.713305E+09 973.15 16-FEB-15:50 22.25 10.82
March 0.397113E+10 10219.90 30-MAR-14:10 27.80 17.74 0.875508E+09 973.19 28-MAR-14:50 27.80 17.74
April 0.470274E+10 9731.10 16-APR-18:10 25.03 16.28 0.845000E+09 973.20 04-APR-14:50 25.03 16.28
May 0.636601E+10 12921.46 29-MAY-18:08 29.13 20.06 0.884194E+09 973.20 01-MAY-14:50 29.13 20.06
June 0.876082E+10 16781.40 25-JUN-18:08 30.40 22.72 0.873784E+09 973.18 24-JUN-10:09 30.40 22.72
July 0.100513E+11 17132.23 16-JUL-18:06 32.52 22.45 0.868372E+09 973.17 01-JUL-10:09 32.52 22.45
August 0.114931E+11 17470.51 27-AUG-18:08 29.82 21.80 0.905600E+09 973.19 12-AUG-10:09 29.82 21.80
September 0.841246E+10 14775.48 07-SEP-20:08 26.93 22.31 0.855745E+09 973.20 16-SEP-14:00 25.00 22.90
October 0.625328E+10 13519.18 09-OCT-18:08 24.13 18.81 0.852482E+09 973.18 19-OCT-14:09 23.90 19.56
November 0.392238E+10 9691.21 06-NOV-14:10 20.60 11.29 0.805701E+09 973.19 03-NOV-14:30 20.60 11.29
December 0.228499E+10 7806.40 12-DEC-13:50 22.52 17.00 0.803199E+09 973.16 12-DEC-15:00 22.20 15.97
                     
Annual Sum or Average 0.697610E+11         0.100349E+11        
Minimum of Months 0.141310E+10 5446.60   12.20 4.56 0.713305E+09 973.15   12.20 4.56
Maximum of Months 0.114931E+11 17470.51   32.52 22.72 0.905600E+09 973.20   32.52 22.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 41362.56 206.81 16-JAN-20:07 7.12 1.69 27110688.42 61.83 31-JAN-15:09 20.92 13.08
February 0.00 0.00 01-FEB-00:10 9.92 7.50 31455723.79 88.94 28-FEB-15:09 24.72 13.51
March 0.00 0.00 01-MAR-00:10 15.32 8.51 45473398.29 111.30 30-MAR-14:00 27.80 17.08
April 0.00 0.00 01-APR-00:10 12.05 7.82 60464293.16 119.25 17-APR-14:00 28.90 16.41
May 0.00 0.00 01-MAY-00:10 16.68 16.68 79265339.86 132.80 30-MAY-14:00 30.60 21.44
June 0.00 0.00 01-JUN-00:10 20.93 18.59 0.103003E+09 164.91 06-JUN-14:00 34.40 22.39
July 0.00 0.00 01-JUL-00:05 22.28 21.38 0.107664E+09 186.05 08-JUL-14:39 36.50 24.10
August 0.00 0.00 01-AUG-00:05 25.13 21.87 0.113662E+09 171.67 01-AUG-14:00 35.00 23.84
September 0.00 0.00 01-SEP-00:05 21.40 18.46 82341355.52 143.82 07-SEP-14:00 31.70 22.92
October 0.00 0.00 01-OCT-00:10 16.85 15.92 54579426.81 125.25 10-OCT-14:09 29.32 20.98
November 0.00 0.00 01-NOV-00:10 9.70 6.60 39713593.38 77.42 02-NOV-14:09 23.22 16.95
December 15774.41 157.74 15-DEC-20:03 7.20 3.16 28183590.80 74.83 12-DEC-15:09 7.20 3.16
                     
Annual Sum or Average 57136.97         0.772916E+09        
Minimum of Months 0.00 0.00   7.12 1.69 27110688.42 61.83   7.20 3.16
Maximum of Months 41362.56 206.81   25.13 21.87 0.113662E+09 186.05   36.50 24.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.110818E+11 62078.19 19-JAN-05:01 12.20
February 0.686664E+10 61312.94 11-FEB-05:01 11.78
March 0.182396E+10 50696.41 20-MAR-04:01 6.42
April 0.856306E+09 47862.25 27-APR-04:02 5.50
May 0.246168E+09 3013.43 07-MAY-07:03 19.27
June 48531430.05 4229.62 25-JUN-07:07 21.97
July 12684529.41 3799.39 02-JUL-07:05 20.37
August 6385156.23 2415.32 13-AUG-07:10 23.07
September 0.108922E+09 2934.76 24-SEP-07:13 18.50
October 0.646643E+09 43009.48 26-OCT-04:02 2.70
November 0.219317E+10 55214.24 24-NOV-05:01 8.90
December 0.602605E+10 63116.99 24-DEC-07:02 13.30
         
Annual Sum or Average 0.299172E+11      
Minimum of Months 6385156.23 2415.32   2.70
Maximum of Months 0.110818E+11 63116.99   23.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.492532E+10 152164.36 18-JAN-06:12 5.60
February 0.239763E+10 149945.01 10-FEB-07:03 5.60
March 0.143941E+09 141628.91 20-MAR-06:03 5.00
April 37576391.58 87933.05 06-APR-06:03 1.20
May 72371299.97 10804.93 07-MAY-08:06 21.47
June 0.204205E+09 15952.83 25-JUN-08:06 23.87
July 0.262891E+09 17243.74 15-JUL-06:06 24.40
August 0.283898E+09 15241.22 14-AUG-06:06 23.40
September 0.239198E+09 15102.13 04-SEP-08:06 23.17
October 43085509.21 89124.47 26-OCT-06:03 2.20
November 0.303507E+09 146704.34 23-NOV-09:02 5.73
December 0.157567E+10 147063.16 23-DEC-07:03 8.22
         
Annual Sum or Average 0.104893E+11      
Minimum of Months 37576391.58 10804.93   1.20
Maximum of Months 0.492532E+10 152164.36   24.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.189780E+10 30225.53 19-JAN-05:01 12.20
February 0.111741E+10 29856.17 11-FEB-05:01 11.78
March 0.175749E+09 24066.02 22-MAR-04:02 6.60
April 0.110590E+09 21390.50 07-APR-04:02 3.80
May 25268525.26 1189.33 07-MAY-07:03 19.27
June 3896956.49 1609.83 04-JUN-07:05 20.37
July 1091822.41 1148.30 31-JUL-05:20 20.60
August 570983.14 1523.59 27-AUG-07:05 21.38
September 3848237.43 545.92 30-SEP-05:10 16.70
October 19876488.49 10986.33 26-OCT-04:02 2.70
November 0.190075E+09 21815.42 21-NOV-05:01 -2.3
December 0.846432E+09 25749.46 23-DEC-05:01 7.80
         
Annual Sum or Average 0.439261E+10      
Minimum of Months 570983.14 545.92   -2.3
Maximum of Months 0.189780E+10 30225.53   21.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.284958E+10 30251.18 19-JAN-05:01 12.20
February 0.172131E+10 29839.67 11-FEB-05:01 11.78
March 0.394597E+09 24069.91 22-MAR-04:02 6.60
April 0.245226E+09 22637.03 27-APR-04:02 5.50
May 86640298.56 1949.22 11-MAY-05:05 8.22
June 17288403.74 1529.18 18-JUN-07:05 20.10
July 5096949.39 1400.92 02-JUL-07:05 20.37
August 2190554.61 1770.35 27-AUG-07:05 21.38
September 26907363.04 1170.71 12-SEP-05:20 21.10
October 83064551.29 19987.46 26-OCT-04:02 2.70
November 0.357641E+09 26414.83 24-NOV-05:01 8.90
December 0.133320E+10 30730.26 24-DEC-07:02 13.30
         
Annual Sum or Average 0.712274E+10      
Minimum of Months 2190554.61 1170.71   2.70
Maximum of Months 0.284958E+10 30730.26   21.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.644808E+10 25167.86 07-JAN-18:00 -5.0
February 0.373774E+10 24975.88 11-FEB-18:00 -5.0
March 0.381499E+09 13623.94 22-MAR-11:05 4.40
April 22798371.95 2124.17 06-APR-07:10 2.25
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:05 22.28
August 0.00 0.00 01-AUG-00:05 25.13
September 0.00 0.00 01-SEP-00:05 21.40
October 9963626.38 2194.12 26-OCT-07:10 2.57
November 0.702407E+09 13482.21 20-NOV-12:03 3.98
December 0.201979E+10 16803.37 17-DEC-18:00 1.10
         
Annual Sum or Average 0.133223E+11      
Minimum of Months 0.00 0.00   -5.0
Maximum of Months 0.644808E+10 25167.86   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.368451E+10 3086.37 02-JAN-09:09 0.419292E+10 2751.42 02-JAN-09:09
February 0.335241E+10 3086.37 01-FEB-09:09 0.380401E+10 2751.42 01-FEB-09:09
March 0.382401E+10 3086.37 01-MAR-09:09 0.429860E+10 2751.42 01-MAR-09:09
April 0.360796E+10 3086.37 01-APR-09:09 0.408537E+10 2751.42 01-APR-09:09
May 0.375426E+10 3086.37 01-MAY-08:09 0.424576E+10 2751.42 01-MAY-08:09
June 0.369006E+10 3086.37 01-JUN-08:09 0.415080E+10 2751.42 01-JUN-08:09
July 0.367216E+10 3086.37 01-JUL-09:09 0.417978E+10 2751.42 01-JUL-09:09
August 0.382401E+10 3086.37 01-AUG-08:09 0.429860E+10 2751.42 01-AUG-08:09
September 0.360796E+10 3086.37 01-SEP-08:09 0.408428E+10 2751.42 01-SEP-08:09
October 0.368451E+10 3086.37 02-OCT-08:09 0.419346E+10 2751.42 02-OCT-08:09
November 0.356290E+10 3086.37 01-NOV-08:09 0.405935E+10 2751.42 01-NOV-08:09
December 0.367216E+10 3086.37 01-DEC-09:09 0.417924E+10 2751.42 01-DEC-09:09
             
Annual Sum or Average 0.439369E+11     0.497722E+11    
Minimum of Months 0.335241E+10 3086.37   0.380401E+10 2751.42  
Maximum of Months 0.382401E+10 3086.37   0.429860E+10 2751.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314662E+11 26357.98 02-JAN-09:09 0.707031E+10 4639.58 02-JAN-09:09
February 0.286300E+11 26357.98 01-FEB-09:09 0.641452E+10 4639.58 01-FEB-09:09
March 0.326575E+11 26357.98 01-MAR-09:09 0.724851E+10 4639.58 01-MAR-09:09
April 0.308125E+11 26357.98 01-APR-09:09 0.688896E+10 4639.58 01-APR-09:09
May 0.320618E+11 26357.98 01-MAY-08:09 0.715941E+10 4639.58 01-MAY-08:09
June 0.315136E+11 26357.98 01-JUN-08:09 0.699930E+10 4639.58 01-JUN-08:09
July 0.313607E+11 26357.98 01-JUL-09:09 0.704816E+10 4639.58 01-JUL-09:09
August 0.326575E+11 26357.98 01-AUG-08:09 0.724851E+10 4639.58 01-AUG-08:09
September 0.308125E+11 26357.98 01-SEP-08:09 0.688712E+10 4639.58 01-SEP-08:09
October 0.314662E+11 26357.98 02-OCT-08:09 0.707123E+10 4639.58 02-OCT-08:09
November 0.304277E+11 26357.98 01-NOV-08:09 0.684509E+10 4639.58 01-NOV-08:09
December 0.313607E+11 26357.98 01-DEC-09:09 0.704724E+10 4639.58 01-DEC-09:09
             
Annual Sum or Average 0.375227E+12     0.839284E+11    
Minimum of Months 0.286300E+11 26357.98   0.641452E+10 4639.58  
Maximum of Months 0.326575E+11 26357.98   0.724851E+10 4639.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.296499E+10 2483.65 02-JAN-09:09 0.443872E+10 2912.71 02-JAN-09:09
February 0.269775E+10 2483.65 01-FEB-09:09 0.402701E+10 2912.71 01-FEB-09:09
March 0.307725E+10 2483.65 01-MAR-09:09 0.455059E+10 2912.71 01-MAR-09:09
April 0.290339E+10 2483.65 01-APR-09:09 0.432486E+10 2912.71 01-APR-09:09
May 0.302112E+10 2483.65 01-MAY-08:09 0.449465E+10 2912.71 01-MAY-08:09
June 0.296946E+10 2483.65 01-JUN-08:09 0.439413E+10 2912.71 01-JUN-08:09
July 0.295505E+10 2483.65 01-JUL-09:09 0.442481E+10 2912.71 01-JUL-09:09
August 0.307725E+10 2483.65 01-AUG-08:09 0.455059E+10 2912.71 01-AUG-08:09
September 0.290339E+10 2483.65 01-SEP-08:09 0.432371E+10 2912.71 01-SEP-08:09
October 0.296499E+10 2483.65 02-OCT-08:09 0.443929E+10 2912.71 02-OCT-08:09
November 0.286713E+10 2483.65 01-NOV-08:09 0.429732E+10 2912.71 01-NOV-08:09
December 0.295505E+10 2483.65 01-DEC-09:09 0.442423E+10 2912.71 01-DEC-09:09
             
Annual Sum or Average 0.353568E+11     0.526899E+11    
Minimum of Months 0.269775E+10 2483.65   0.402701E+10 2912.71  
Maximum of Months 0.307725E+10 2483.65   0.455059E+10 2912.71  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.296499E+10 2483.65 02-JAN-09:09 0.666220E+09 437.18 02-JAN-09:09
February 0.269775E+10 2483.65 01-FEB-09:09 0.604426E+09 437.18 01-FEB-09:09
March 0.307725E+10 2483.65 01-MAR-09:09 0.683011E+09 437.18 01-MAR-09:09
April 0.290339E+10 2483.65 01-APR-09:09 0.649132E+09 437.18 01-APR-09:09
May 0.302112E+10 2483.65 01-MAY-08:09 0.674616E+09 437.18 01-MAY-08:09
June 0.296946E+10 2483.65 01-JUN-08:09 0.659528E+09 437.18 01-JUN-08:09
July 0.295505E+10 2483.65 01-JUL-09:09 0.664132E+09 437.18 01-JUL-09:09
August 0.307725E+10 2483.65 01-AUG-08:09 0.683011E+09 437.18 01-AUG-08:09
September 0.290339E+10 2483.65 01-SEP-08:09 0.648959E+09 437.18 01-SEP-08:09
October 0.296499E+10 2483.65 02-OCT-08:09 0.666307E+09 437.18 02-OCT-08:09
November 0.286713E+10 2483.65 01-NOV-08:09 0.644998E+09 437.18 01-NOV-08:09
December 0.295505E+10 2483.65 01-DEC-09:09 0.664046E+09 437.18 01-DEC-09:09
             
Annual Sum or Average 0.353568E+11     0.790839E+10    
Minimum of Months 0.269775E+10 2483.65   0.604426E+09 437.18  
Maximum of Months 0.307725E+10 2483.65   0.683011E+09 437.18  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.141555E+09 118.58 02-JAN-09:09 0.00 0.00
February 0.128796E+09 118.58 01-FEB-09:09 0.00 0.00
March 0.146915E+09 118.58 01-MAR-09:09 0.00 0.00
April 0.138614E+09 118.58 01-APR-09:09 0.00 0.00
May 0.144235E+09 118.58 01-MAY-08:09 0.00 0.00
June 0.141768E+09 118.58 01-JUN-08:09 0.00 0.00
July 0.141081E+09 118.58 01-JUL-09:09 0.00 0.00
August 0.146915E+09 118.58 01-AUG-08:09 0.00 0.00
September 0.138614E+09 118.58 01-SEP-08:09 0.00 0.00
October 0.141555E+09 118.58 02-OCT-08:09 0.00 0.00
November 0.136883E+09 118.58 01-NOV-08:09 0.00 0.00
December 0.141081E+09 118.58 01-DEC-09:09 0.00 0.00
           
Annual Sum or Average 0.168801E+10     0.00 0.00
Minimum of Months 0.128796E+09 118.58   0.00 0.00
Maximum of Months 0.146915E+09 118.58   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.699524E+09 0.368451E+10 0.419292E+10 0.00 0.00 0.00 0.00 0.00 0.203739E+10
February 0.638757E+09 0.335241E+10 0.380401E+10 0.00 0.00 0.00 0.00 462631.15 0.176812E+10
March 0.730614E+09 0.382401E+10 0.429860E+10 0.00 0.00 0.00 0.00 4604777.07 0.116117E+10
April 0.690691E+09 0.360796E+10 0.408537E+10 0.00 0.00 0.00 0.00 11838263.42 0.710729E+09
May 0.715069E+09 0.375426E+10 0.424576E+10 0.00 0.00 0.00 0.00 36655479.25 0.444822E+09
June 0.705176E+09 0.369006E+10 0.415080E+10 0.00 0.00 0.00 0.00 0.150550E+09 0.182011E+09
July 0.700584E+09 0.367216E+10 0.417978E+10 0.00 0.00 0.00 0.00 0.172241E+09 0.103810E+09
August 0.730614E+09 0.382401E+10 0.429860E+10 0.00 0.00 0.00 0.00 0.181183E+09 41948773.31
September 0.690691E+09 0.360796E+10 0.408428E+10 0.00 0.00 0.00 0.00 47089088.30 0.221718E+09
October 0.699524E+09 0.368451E+10 0.419346E+10 0.00 0.00 0.00 0.00 8077665.76 0.844651E+09
November 0.673027E+09 0.356290E+10 0.405935E+10 0.00 0.00 0.00 0.00 51197.77 0.120769E+10
December 0.700584E+09 0.367216E+10 0.417924E+10 0.00 0.00 0.00 0.00 0.00 0.183454E+10
                   
Annual Sum or Average 0.837485E+10 0.439369E+11 0.497722E+11 0.00 0.00 0.00 0.00 0.612754E+09 0.105586E+11
Minimum of Months 0.638757E+09 0.335241E+10 0.380401E+10 0.00 0.00 0.00 0.00 0.00 41948773.31
Maximum of Months 0.730614E+09 0.382401E+10 0.429860E+10 0.00 0.00 0.00 0.00 0.181183E+09 0.203739E+10



Table of Contents

Report: SpaceGainsMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.221054E+11 0.314662E+11 0.707031E+10 0.00 0.00 0.00 0.00 0.00 0.191324E+10
February 0.201852E+11 0.286300E+11 0.641452E+10 0.00 0.00 0.00 0.00 396695.72 0.168779E+10
March 0.230879E+11 0.326575E+11 0.724851E+10 0.00 0.00 0.00 0.00 3920333.58 0.115766E+10
April 0.218263E+11 0.308125E+11 0.688896E+10 0.00 0.00 0.00 0.00 10124236.16 0.712952E+09
May 0.225967E+11 0.320618E+11 0.715941E+10 0.00 0.00 0.00 0.00 30327551.89 0.463282E+09
June 0.222841E+11 0.315136E+11 0.699930E+10 0.00 0.00 0.00 0.00 0.114451E+09 0.233026E+09
July 0.221389E+11 0.313607E+11 0.704816E+10 0.00 0.00 0.00 0.00 0.118436E+09 0.149430E+09
August 0.230879E+11 0.326575E+11 0.724851E+10 0.00 0.00 0.00 0.00 0.124022E+09 0.101774E+09
September 0.218263E+11 0.308125E+11 0.688712E+10 0.00 0.00 0.00 0.00 35812374.45 0.241939E+09
October 0.221054E+11 0.314662E+11 0.707123E+10 0.00 0.00 0.00 0.00 6925809.25 0.819089E+09
November 0.212681E+11 0.304277E+11 0.684509E+10 0.00 0.00 0.00 0.00 43900.45 0.115812E+10
December 0.221389E+11 0.313607E+11 0.704724E+10 0.00 0.00 0.00 0.00 0.00 0.175373E+10
                   
Annual Sum or Average 0.264651E+12 0.375227E+12 0.839284E+11 0.00 0.00 0.00 0.00 0.444461E+09 0.103920E+11
Minimum of Months 0.201852E+11 0.286300E+11 0.641452E+10 0.00 0.00 0.00 0.00 0.00 0.101774E+09
Maximum of Months 0.230879E+11 0.326575E+11 0.724851E+10 0.00 0.00 0.00 0.00 0.124022E+09 0.191324E+10



Table of Contents

Report: SpaceGainsMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.208295E+10 0.296499E+10 0.443872E+10 0.00 0.00 0.00 0.00 0.00 0.997988E+09
February 0.190200E+10 0.269775E+10 0.402701E+10 0.00 0.00 0.00 0.00 210986.10 0.863169E+09
March 0.217552E+10 0.307725E+10 0.455059E+10 0.00 0.00 0.00 0.00 2100627.30 0.575532E+09
April 0.205665E+10 0.290339E+10 0.432486E+10 0.00 0.00 0.00 0.00 5394895.29 0.341335E+09
May 0.212923E+10 0.302112E+10 0.449465E+10 0.00 0.00 0.00 0.00 16690865.61 0.208593E+09
June 0.209978E+10 0.296946E+10 0.439413E+10 0.00 0.00 0.00 0.00 68417938.07 82879471.50
July 0.208610E+10 0.295505E+10 0.442481E+10 0.00 0.00 0.00 0.00 78043623.59 46995610.91
August 0.217552E+10 0.307725E+10 0.455059E+10 0.00 0.00 0.00 0.00 81948987.86 18879350.04
September 0.205665E+10 0.290339E+10 0.432371E+10 0.00 0.00 0.00 0.00 21367062.49 0.102517E+09
October 0.208295E+10 0.296499E+10 0.443929E+10 0.00 0.00 0.00 0.00 3684637.50 0.407912E+09
November 0.200405E+10 0.286713E+10 0.429732E+10 0.00 0.00 0.00 0.00 23296.26 0.600765E+09
December 0.208610E+10 0.295505E+10 0.442423E+10 0.00 0.00 0.00 0.00 0.00 0.906694E+09
                   
Annual Sum or Average 0.249375E+11 0.353568E+11 0.526899E+11 0.00 0.00 0.00 0.00 0.277883E+09 0.515326E+10
Minimum of Months 0.190200E+10 0.269775E+10 0.402701E+10 0.00 0.00 0.00 0.00 0.00 18879350.04
Maximum of Months 0.217552E+10 0.307725E+10 0.455059E+10 0.00 0.00 0.00 0.00 81948987.86 0.997988E+09



Table of Contents

Report: SpaceGainsMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.208295E+10 0.296499E+10 0.666220E+09 0.00 0.00 0.00 0.00 0.00 0.964293E+09
February 0.190200E+10 0.269775E+10 0.604426E+09 0.00 0.00 0.00 0.00 210986.10 0.831361E+09
March 0.217552E+10 0.307725E+10 0.683011E+09 0.00 0.00 0.00 0.00 2102135.75 0.548189E+09
April 0.205665E+10 0.290339E+10 0.649132E+09 0.00 0.00 0.00 0.00 5396972.16 0.324229E+09
May 0.212923E+10 0.302112E+10 0.674616E+09 0.00 0.00 0.00 0.00 16720904.85 0.199709E+09
June 0.209978E+10 0.296946E+10 0.659528E+09 0.00 0.00 0.00 0.00 68606336.52 81975317.03
July 0.208610E+10 0.295505E+10 0.664132E+09 0.00 0.00 0.00 0.00 78409956.69 47112823.59
August 0.217552E+10 0.307725E+10 0.683011E+09 0.00 0.00 0.00 0.00 82383215.81 18984037.30
September 0.205665E+10 0.290339E+10 0.648959E+09 0.00 0.00 0.00 0.00 21444301.14 0.100693E+09
October 0.208295E+10 0.296499E+10 0.666307E+09 0.00 0.00 0.00 0.00 3684434.13 0.393254E+09
November 0.200405E+10 0.286713E+10 0.644998E+09 0.00 0.00 0.00 0.00 23338.58 0.575520E+09
December 0.208610E+10 0.295505E+10 0.664046E+09 0.00 0.00 0.00 0.00 0.00 0.868048E+09
                   
Annual Sum or Average 0.249375E+11 0.353568E+11 0.790839E+10 0.00 0.00 0.00 0.00 0.278983E+09 0.495337E+10
Minimum of Months 0.190200E+10 0.269775E+10 0.604426E+09 0.00 0.00 0.00 0.00 0.00 18984037.30
Maximum of Months 0.217552E+10 0.307725E+10 0.683011E+09 0.00 0.00 0.00 0.00 82383215.81 0.964293E+09



Table of Contents

Report: SpaceGainsMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.165769E+09 0.141555E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.770836E+10
February 0.151369E+09 0.128796E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.481235E+10
March 0.173136E+09 0.146915E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.169878E+10
April 0.163676E+09 0.138614E+09 0.00 0.00 0.00 0.00 0.00 25186.30 0.765892E+09
May 0.169453E+09 0.144235E+09 0.00 0.00 0.00 0.00 0.00 8013582.11 0.419588E+09
June 0.167108E+09 0.141768E+09 0.00 0.00 0.00 0.00 0.00 0.134082E+09 0.133868E+09
July 0.166020E+09 0.141081E+09 0.00 0.00 0.00 0.00 0.00 0.173147E+09 0.134290E+09
August 0.173136E+09 0.146915E+09 0.00 0.00 0.00 0.00 0.00 95035466.63 0.126521E+09
September 0.163676E+09 0.138614E+09 0.00 0.00 0.00 0.00 0.00 2162762.18 0.447430E+09
October 0.165769E+09 0.141555E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.122273E+10
November 0.159490E+09 0.136883E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.212649E+10
December 0.166020E+09 0.141081E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.368479E+10
                   
Annual Sum or Average 0.198462E+10 0.168801E+10 0.00 0.00 0.00 0.00 0.00 0.412466E+09 0.232811E+11
Minimum of Months 0.151369E+09 0.128796E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.126521E+09
Maximum of Months 0.173136E+09 0.146915E+09 0.00 0.00 0.00 0.00 0.00 0.173147E+09 0.770836E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 785.10 02-JAN-15:09 3086.37 02-JAN-09:09 2751.42 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 4390.92 07-JAN-05:20
February 785.10 01-FEB-15:09 3086.37 01-FEB-09:09 2751.42 01-FEB-09:09 0.00 0.00 0.00 0.00 55.00 28-FEB-15:00 5075.79 12-FEB-01:00
March 785.10 01-MAR-15:09 3086.37 01-MAR-09:09 2751.42 01-MAR-09:09 0.00 0.00 0.00 0.00 128.62 30-MAR-16:00 3328.50 22-MAR-05:00
April 785.10 01-APR-10:09 3086.37 01-APR-09:09 2751.42 01-APR-09:09 0.00 0.00 0.00 0.00 99.95 04-APR-15:00 1568.40 05-APR-05:00
May 785.10 01-MAY-14:09 3086.37 01-MAY-08:09 2751.42 01-MAY-08:09 0.00 0.00 0.00 0.00 331.54 29-MAY-18:10 1284.54 10-MAY-04:00
June 785.10 01-JUN-14:09 3086.37 01-JUN-08:09 2751.42 01-JUN-08:09 0.00 0.00 0.00 0.00 508.96 11-JUN-18:10 931.47 07-JUN-03:00
July 785.10 01-JUL-10:09 3086.37 01-JUL-09:09 2751.42 01-JUL-09:09 0.00 0.00 0.00 0.00 553.81 09-JUL-19:30 694.74 28-JUL-22:00
August 785.10 01-AUG-14:09 3086.37 01-AUG-08:09 2751.42 01-AUG-08:09 0.00 0.00 0.00 0.00 707.69 18-AUG-20:10 419.99 25-AUG-05:00
September 785.10 01-SEP-14:09 3086.37 01-SEP-08:09 2751.42 01-SEP-08:09 0.00 0.00 0.00 0.00 277.99 03-SEP-18:10 900.27 29-SEP-05:00
October 785.10 02-OCT-14:09 3086.37 02-OCT-08:09 2751.42 02-OCT-08:09 0.00 0.00 0.00 0.00 101.73 11-OCT-14:00 1834.30 28-OCT-04:00
November 785.10 01-NOV-14:09 3086.37 01-NOV-08:09 2751.42 01-NOV-08:09 0.00 0.00 0.00 0.00 18.97 19-NOV-14:55 2976.38 30-NOV-21:05
December 785.10 01-DEC-15:09 3086.37 01-DEC-09:09 2751.42 01-DEC-09:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4559.96 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 785.10   3086.37   2751.42   0.00 0.00 0.00 0.00 0.00   419.99  
Maximum of Months 785.10   3086.37   2751.42   0.00 0.00 0.00 0.00 707.69   5075.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 24809.68 02-JAN-15:09 26357.98 02-JAN-09:09 4639.58 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 3521.32 26-JAN-01:55
February 24809.68 01-FEB-15:09 26357.98 01-FEB-09:09 4639.58 01-FEB-09:09 0.00 0.00 0.00 0.00 47.16 28-FEB-15:00 4899.85 12-FEB-00:55
March 24809.68 01-MAR-15:09 26357.98 01-MAR-09:09 4639.58 01-MAR-09:09 0.00 0.00 0.00 0.00 110.29 30-MAR-16:00 3154.26 22-MAR-03:00
April 24809.68 01-APR-10:09 26357.98 01-APR-09:09 4639.58 01-APR-09:09 0.00 0.00 0.00 0.00 85.67 04-APR-15:00 1649.10 05-APR-05:00
May 24809.68 01-MAY-14:09 26357.98 01-MAY-08:09 4639.58 01-MAY-08:09 0.00 0.00 0.00 0.00 271.16 29-MAY-18:03 1310.88 10-MAY-04:00
June 24809.68 01-JUN-14:09 26357.98 01-JUN-08:09 4639.58 01-JUN-08:09 0.00 0.00 0.00 0.00 421.01 11-JUN-18:03 954.61 07-JUN-03:00
July 24809.68 01-JUL-10:09 26357.98 01-JUL-09:09 4639.58 01-JUL-09:09 0.00 0.00 0.00 0.00 425.15 09-JUL-18:02 719.49 28-JUL-22:00
August 24809.68 01-AUG-14:09 26357.98 01-AUG-08:09 4639.58 01-AUG-08:09 0.00 0.00 0.00 0.00 582.63 18-AUG-20:03 452.22 25-AUG-05:00
September 24809.68 01-SEP-14:09 26357.98 01-SEP-08:09 4639.58 01-SEP-08:09 0.00 0.00 0.00 0.00 228.95 03-SEP-18:03 906.94 29-SEP-05:00
October 24809.68 02-OCT-14:09 26357.98 02-OCT-08:09 4639.58 02-OCT-08:09 0.00 0.00 0.00 0.00 87.24 11-OCT-14:00 1909.85 28-OCT-04:00
November 24809.68 01-NOV-14:09 26357.98 01-NOV-08:09 4639.58 01-NOV-08:09 0.00 0.00 0.00 0.00 16.27 19-NOV-15:00 2746.16 30-NOV-21:30
December 24809.68 01-DEC-15:09 26357.98 01-DEC-09:09 4639.58 01-DEC-09:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4724.05 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 24809.68   26357.98   4639.58   0.00 0.00 0.00 0.00 0.00   452.22  
Maximum of Months 24809.68   26357.98   4639.58   0.00 0.00 0.00 0.00 582.63   4899.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2337.76 02-JAN-15:09 2483.65 02-JAN-09:09 2912.71 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 2045.95 07-JAN-05:10
February 2337.76 01-FEB-15:09 2483.65 01-FEB-09:09 2912.71 01-FEB-09:09 0.00 0.00 0.00 0.00 25.08 28-FEB-15:00 2275.91 12-FEB-00:55
March 2337.76 01-MAR-15:09 2483.65 01-MAR-09:09 2912.71 01-MAR-09:09 0.00 0.00 0.00 0.00 58.66 30-MAR-16:00 1517.99 22-MAR-05:00
April 2337.76 01-APR-10:09 2483.65 01-APR-09:09 2912.71 01-APR-09:09 0.00 0.00 0.00 0.00 45.57 04-APR-15:00 744.05 05-APR-05:00
May 2337.76 01-MAY-14:09 2483.65 01-MAY-08:09 2912.71 01-MAY-08:09 0.00 0.00 0.00 0.00 151.40 29-MAY-18:10 597.75 10-MAY-04:00
June 2337.76 01-JUN-14:09 2483.65 01-JUN-08:09 2912.71 01-JUN-08:09 0.00 0.00 0.00 0.00 232.08 11-JUN-18:10 418.73 07-JUN-03:10
July 2337.76 01-JUL-10:09 2483.65 01-JUL-09:09 2912.71 01-JUL-09:09 0.00 0.00 0.00 0.00 252.56 09-JUL-19:30 322.04 28-JUL-20:10
August 2337.76 01-AUG-14:09 2483.65 01-AUG-08:09 2912.71 01-AUG-08:09 0.00 0.00 0.00 0.00 318.45 18-AUG-20:10 196.01 25-AUG-05:00
September 2337.76 01-SEP-14:09 2483.65 01-SEP-08:09 2912.71 01-SEP-08:09 0.00 0.00 0.00 0.00 124.83 03-SEP-18:10 420.67 29-SEP-05:00
October 2337.76 02-OCT-14:09 2483.65 02-OCT-08:09 2912.71 02-OCT-08:09 0.00 0.00 0.00 0.00 46.39 11-OCT-14:00 925.99 28-OCT-04:00
November 2337.76 01-NOV-14:09 2483.65 01-NOV-08:09 2912.71 01-NOV-08:09 0.00 0.00 0.00 0.00 8.64 19-NOV-15:00 1427.95 30-NOV-21:05
December 2337.76 01-DEC-15:09 2483.65 01-DEC-09:09 2912.71 01-DEC-09:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2156.20 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2337.76   2483.65   2912.71   0.00 0.00 0.00 0.00 0.00   196.01  
Maximum of Months 2337.76   2483.65   2912.71   0.00 0.00 0.00 0.00 318.45   2275.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2337.76 02-JAN-15:09 2483.65 02-JAN-09:09 437.18 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 2045.95 07-JAN-05:10
February 2337.76 01-FEB-15:09 2483.65 01-FEB-09:09 437.18 01-FEB-09:09 0.00 0.00 0.00 0.00 25.08 28-FEB-15:00 2290.19 12-FEB-00:55
March 2337.76 01-MAR-15:09 2483.65 01-MAR-09:09 437.18 01-MAR-09:09 0.00 0.00 0.00 0.00 58.66 30-MAR-16:00 1517.98 22-MAR-05:00
April 2337.76 01-APR-10:09 2483.65 01-APR-09:09 437.18 01-APR-09:09 0.00 0.00 0.00 0.00 45.55 04-APR-15:00 697.55 05-APR-05:00
May 2337.76 01-MAY-14:09 2483.65 01-MAY-08:09 437.18 01-MAY-08:09 0.00 0.00 0.00 0.00 151.10 29-MAY-18:10 569.59 10-MAY-04:00
June 2337.76 01-JUN-14:09 2483.65 01-JUN-08:09 437.18 01-JUN-08:09 0.00 0.00 0.00 0.00 231.82 11-JUN-18:10 417.81 07-JUN-03:00
July 2337.76 01-JUL-10:09 2483.65 01-JUL-09:09 437.18 01-JUL-09:09 0.00 0.00 0.00 0.00 252.57 09-JUL-19:30 318.19 28-JUL-22:00
August 2337.76 01-AUG-14:09 2483.65 01-AUG-08:09 437.18 01-AUG-08:09 0.00 0.00 0.00 0.00 320.14 18-AUG-20:10 188.70 25-AUG-05:00
September 2337.76 01-SEP-14:09 2483.65 01-SEP-08:09 437.18 01-SEP-08:09 0.00 0.00 0.00 0.00 125.64 03-SEP-18:10 396.90 29-SEP-05:00
October 2337.76 02-OCT-14:09 2483.65 02-OCT-08:09 437.18 02-OCT-08:09 0.00 0.00 0.00 0.00 46.39 11-OCT-14:00 880.19 28-OCT-04:00
November 2337.76 01-NOV-14:09 2483.65 01-NOV-08:09 437.18 01-NOV-08:09 0.00 0.00 0.00 0.00 8.65 19-NOV-15:00 1348.13 30-NOV-21:05
December 2337.76 01-DEC-15:09 2483.65 01-DEC-09:09 437.18 01-DEC-09:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2075.18 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2337.76   2483.65   437.18   0.00 0.00 0.00 0.00 0.00   188.70  
Maximum of Months 2337.76   2483.65   437.18   0.00 0.00 0.00 0.00 320.14   2290.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 186.05 02-JAN-15:09 118.58 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 25397.72 07-JAN-17:00
February 186.05 01-FEB-15:09 118.58 01-FEB-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 25582.27 11-FEB-18:00
March 186.05 01-MAR-15:09 118.58 01-MAR-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 14429.05 22-MAR-11:05
April 186.05 01-APR-10:09 118.58 01-APR-09:09 0.00 0.00 0.00 0.00 0.00 30.85 02-APR-17:00 7312.78 05-APR-11:01
May 186.05 01-MAY-14:09 118.58 01-MAY-08:09 0.00 0.00 0.00 0.00 0.00 268.67 30-MAY-11:05 2887.49 10-MAY-11:01
June 186.05 01-JUN-14:09 118.58 01-JUN-08:09 0.00 0.00 0.00 0.00 0.00 1268.43 06-JUN-11:02 1748.56 07-JUN-11:02
July 186.05 01-JUL-10:09 118.58 01-JUL-09:09 0.00 0.00 0.00 0.00 0.00 1803.80 08-JUL-11:02 2606.54 28-JUL-11:01
August 186.05 01-AUG-14:09 118.58 01-AUG-08:09 0.00 0.00 0.00 0.00 0.00 1230.66 01-AUG-11:02 1546.05 04-AUG-14:53
September 186.05 01-SEP-14:09 118.58 01-SEP-08:09 0.00 0.00 0.00 0.00 0.00 205.71 03-SEP-17:00 2638.31 30-SEP-11:01
October 186.05 02-OCT-14:09 118.58 02-OCT-08:09 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 6657.88 25-OCT-11:01
November 186.05 01-NOV-14:09 118.58 01-NOV-08:09 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 15139.43 20-NOV-12:03
December 186.05 01-DEC-15:09 118.58 01-DEC-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 17693.11 17-DEC-18:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 186.05   118.58   0.00 0.00 0.00 0.00 0.00 0.00   1546.05  
Maximum of Months 186.05   118.58   0.00 0.00 0.00 0.00 0.00 1803.80   25582.27  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 922.77 20-JAN-16:00 785.10 3086.37 2751.42 0.00 0.00 0.00 0.00 0.00 196.59
February 5096.62 28-FEB-15:50 785.10 3086.37 2751.42 0.00 0.00 0.00 0.00 0.00 11.48
March 11553.72 30-MAR-20:25 0.00 1371.72 1210.17 0.00 0.00 0.00 0.00 18.16 0.00
April 12511.82 17-APR-22:00 0.00 514.39 1815.26 0.00 0.00 0.00 0.00 0.00 0.00
May 27042.87 29-MAY-18:08 0.00 685.86 1815.26 0.00 0.00 0.00 0.00 324.33 0.00
June 36555.74 25-JUN-18:08 0.00 685.86 1815.26 0.00 0.00 0.00 0.00 488.06 0.00
July 37164.39 16-JUL-18:06 0.00 857.32 2269.08 0.00 0.00 0.00 0.00 449.71 0.00
August 36665.33 13-AUG-18:08 0.00 685.86 1815.26 0.00 0.00 0.00 0.00 414.49 0.00
September 31982.87 07-SEP-20:10 0.00 2743.44 2420.35 0.00 0.00 0.00 0.00 173.96 0.00
October 13449.58 10-OCT-20:33 0.00 2057.58 1815.26 0.00 0.00 0.00 0.00 0.00 159.49
November 5972.71 05-NOV-15:30 392.55 2057.58 2445.70 0.00 0.00 0.00 0.00 2.09 0.00
December 3070.73 13-DEC-13:15 1373.92 6172.74 5502.84 0.00 0.00 0.00 0.00 0.00 86.61
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 922.77   0.00 514.39 1210.17 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37164.39   1373.92 6172.74 5502.84 0.00 0.00 0.00 0.00 488.06 196.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 45800.55 14-JAN-06:06 0.00 7321.66 3826.23 0.00 0.00 0.00 0.00 0.00 594.82
February 44373.19 04-FEB-06:06 0.00 7321.66 3826.23 0.00 0.00 0.00 0.00 0.00 419.27
March 53944.74 30-MAR-14:30 24809.68 26357.98 4639.58 0.00 0.00 0.00 0.00 94.97 0.00
April 56655.66 19-APR-14:40 24809.68 26357.98 4639.58 0.00 0.00 0.00 0.00 58.27 0.00
May 126675.70 07-MAY-08:62 15506.05 14643.32 7732.63 0.00 0.00 0.00 0.00 0.00 59.86
June 169514.39 11-JUN-08:62 15506.05 14643.32 7732.63 0.00 0.00 0.00 0.00 0.00 55.52
July 128017.57 25-JUL-06:02 15506.05 29286.64 10310.18 0.00 0.00 0.00 0.00 0.00 56.65
August 135107.63 26-AUG-06:02 15506.05 14643.32 7732.63 0.00 0.00 0.00 0.00 0.00 43.18
September 127893.07 25-SEP-06:03 12404.84 23429.32 8248.14 0.00 0.00 0.00 0.00 0.00 0.00
October 104778.93 18-OCT-06:03 12404.84 23429.32 8248.14 0.00 0.00 0.00 0.00 0.00 67.89
November 37856.00 06-NOV-15:10 24809.68 26357.98 4639.58 0.00 0.00 0.00 0.00 0.00 108.65
December 39537.40 03-DEC-08:07 0.00 4393.00 2295.74 0.00 0.00 0.00 0.00 0.00 493.09
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 37856.00   0.00 4393.00 2295.74 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 169514.39   24809.68 29286.64 10310.18 0.00 0.00 0.00 0.00 94.97 594.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7600.29 28-JAN-15:10 2337.76 2483.65 2912.71 0.00 0.00 0.00 0.00 0.00 63.85
February 11370.40 21-FEB-14:40 2045.54 2483.65 2912.71 0.00 0.00 0.00 0.00 0.00 16.19
March 12486.46 30-MAR-20:10 0.00 1655.77 1921.68 0.00 0.00 0.00 0.00 11.51 0.00
April 12455.23 16-APR-18:10 0.00 413.94 1441.26 0.00 0.00 0.00 0.00 30.08 0.00
May 16116.98 29-MAY-18:08 0.00 551.92 1921.68 0.00 0.00 0.00 0.00 146.97 0.00
June 18230.81 11-JUN-18:08 0.00 551.92 1921.68 0.00 0.00 0.00 0.00 227.18 0.00
July 17757.60 02-JUL-18:08 0.00 551.92 1921.68 0.00 0.00 0.00 0.00 161.94 0.00
August 18114.64 27-AUG-18:08 0.00 551.92 1921.68 0.00 0.00 0.00 0.00 264.00 0.00
September 17513.02 08-SEP-20:08 0.00 2207.69 2562.24 0.00 0.00 0.00 0.00 62.38 0.00
October 16809.06 09-OCT-18:08 0.00 551.92 1921.68 0.00 0.00 0.00 0.00 2.62 0.00
November 11817.44 06-NOV-14:30 2045.54 2483.65 2912.71 0.00 0.00 0.00 0.00 0.00 63.44
December 10042.73 12-DEC-14:00 2045.54 2483.65 2912.71 0.00 0.00 0.00 0.00 0.00 12.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7600.29   0.00 413.94 1441.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18230.81   2337.76 2483.65 2912.71 0.00 0.00 0.00 0.00 264.00 63.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5446.60 28-JAN-15:00 2337.76 2483.65 437.18 0.00 0.00 0.00 0.00 0.00 55.10
February 9303.88 21-FEB-14:30 2045.54 2483.65 437.18 0.00 0.00 0.00 0.00 0.00 18.23
March 10219.90 30-MAR-14:10 2337.76 2483.65 437.18 0.00 0.00 0.00 0.00 47.80 0.00
April 9731.10 16-APR-18:10 0.00 413.94 216.32 0.00 0.00 0.00 0.00 31.00 0.00
May 12921.46 29-MAY-18:08 0.00 551.92 288.43 0.00 0.00 0.00 0.00 147.45 0.00
June 16781.40 25-JUN-18:08 0.00 551.92 288.43 0.00 0.00 0.00 0.00 221.67 0.00
July 17132.23 16-JUL-18:06 0.00 689.90 360.54 0.00 0.00 0.00 0.00 204.59 0.00
August 17470.51 27-AUG-18:08 0.00 551.92 288.43 0.00 0.00 0.00 0.00 272.50 0.00
September 14775.48 07-SEP-20:08 0.00 2207.69 384.57 0.00 0.00 0.00 0.00 79.19 0.00
October 13519.18 09-OCT-18:08 0.00 551.92 288.43 0.00 0.00 0.00 0.00 2.92 0.00
November 9691.21 06-NOV-14:10 2045.54 2483.65 437.18 0.00 0.00 0.00 0.00 0.00 67.21
December 7806.40 12-DEC-13:50 2045.54 2483.65 437.18 0.00 0.00 0.00 0.00 0.00 16.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5446.60   0.00 413.94 216.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17470.51   2337.76 2483.65 437.18 0.00 0.00 0.00 0.00 272.50 67.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 206.81 16-JAN-20:07 0.00 19.76 0.00 0.00 0.00 0.00 0.00 0.00 28.36
February 0.00 01-FEB-00:10 0.00 6.59 0.00 0.00 0.00 0.00 0.00 0.00 76.66
March 0.00 01-MAR-00:10 0.00 6.59 0.00 0.00 0.00 0.00 0.00 0.00 48.15
April 0.00 01-APR-00:10 0.00 6.59 0.00 0.00 0.00 0.00 0.00 0.00 41.20
May 0.00 01-MAY-00:10 0.00 6.59 0.00 0.00 0.00 0.00 0.00 0.00 21.49
June 0.00 01-JUN-00:10 0.00 6.59 0.00 0.00 0.00 0.00 0.00 0.00 13.71
July 0.00 01-JUL-00:05 0.00 13.18 0.00 0.00 0.00 0.00 0.00 0.00 10.90
August 0.00 01-AUG-00:05 0.00 13.18 0.00 0.00 0.00 0.00 0.00 0.00 3.30
September 0.00 01-SEP-00:05 0.00 13.18 0.00 0.00 0.00 0.00 0.00 0.00 13.89
October 0.00 01-OCT-00:10 0.00 6.59 0.00 0.00 0.00 0.00 0.00 0.00 32.65
November 0.00 01-NOV-00:10 0.00 6.59 0.00 0.00 0.00 0.00 0.00 0.00 66.66
December 157.74 15-DEC-20:03 418.61 395.25 0.00 0.00 0.00 0.00 0.00 0.00 16.04
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 6.59 0.00 0.00 0.00 0.00 0.00 0.00 3.30
Maximum of Months 206.81   418.61 395.25 0.00 0.00 0.00 0.00 0.00 0.00 76.66



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [] NATURALGAS:FACILITY []
January 0.138667E+12 135275.04 07-JAN-17:00 0.00 0.00
February 0.118624E+12 183889.95 12-FEB-07:30 0.00 0.00
March 0.125526E+12 107997.05 30-MAR-14:09 0.00 0.00
April 0.128842E+12 106846.74 17-APR-14:30 0.00 0.00
May 0.146781E+12 117767.72 30-MAY-14:50 0.00 0.00
June 0.162025E+12 129110.25 23-JUN-13:30 0.00 0.00
July 0.173179E+12 139759.32 08-JUL-14:39 0.00 0.00
August 0.181045E+12 134499.03 01-AUG-14:00 0.00 0.00
September 0.150436E+12 126877.42 06-SEP-13:00 0.00 0.00
October 0.130662E+12 113926.41 10-OCT-14:09 0.00 0.00
November 0.117730E+12 102417.22 22-NOV-07:10 0.00 0.00
December 0.121908E+12 109194.79 18-DEC-07:10 0.00 0.00
           
Annual Sum or Average 0.169542E+13     0.00 0.00
Minimum of Months 0.117730E+12 102417.22   0.00 0.00
Maximum of Months 0.181045E+12 183889.95   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.412222E+11 0.124458E+11 0.163682E+11 0.00 0.387623E+11 0.00 0.262885E+11 0.127074E+10 0.00 0.00 0.00 0.230929E+10 0.00
February 0.375067E+11 0.106226E+11 0.148500E+11 0.00 0.344944E+11 0.00 0.143334E+11 0.471357E+10 0.00 0.00 0.00 0.210324E+10 0.00
March 0.427830E+11 0.108625E+11 0.167807E+11 0.00 0.372409E+11 0.00 0.112570E+10 0.144286E+11 0.00 0.00 0.00 0.230447E+10 0.00
April 0.403658E+11 0.961505E+10 0.159483E+11 0.00 0.356234E+11 0.00 0.357438E+09 0.248715E+11 0.00 0.00 0.00 0.206061E+10 0.00
May 0.420026E+11 0.915445E+10 0.165744E+11 0.00 0.369640E+11 0.00 2536660.92 0.401122E+11 0.00 0.00 0.00 0.197103E+10 0.00
June 0.412843E+11 0.851633E+10 0.162038E+11 0.00 0.368850E+11 0.00 0.00 0.573449E+11 0.00 0.00 0.00 0.179084E+10 0.00
July 0.410841E+11 0.892895E+10 0.163169E+11 0.00 0.381432E+11 0.00 0.00 0.669912E+11 0.00 0.00 0.00 0.171449E+10 0.00
August 0.427830E+11 0.958147E+10 0.167807E+11 0.00 0.390945E+11 0.00 0.00 0.710448E+11 0.00 0.00 0.00 0.176039E+10 0.00
September 0.403658E+11 0.101236E+11 0.159441E+11 0.00 0.364383E+11 0.00 0.00 0.458139E+11 0.00 0.00 0.00 0.175003E+10 0.00
October 0.412222E+11 0.113903E+11 0.163703E+11 0.00 0.365456E+11 0.00 0.128514E+09 0.230853E+11 0.00 0.00 0.00 0.191958E+10 0.00
November 0.398617E+11 0.118365E+11 0.158468E+11 0.00 0.354199E+11 0.00 0.244202E+10 0.103187E+11 0.00 0.00 0.00 0.200397E+10 0.00
December 0.410841E+11 0.126665E+11 0.163148E+11 0.00 0.375310E+11 0.00 0.887703E+10 0.321025E+10 0.00 0.00 0.00 0.222442E+10 0.00
                           
Annual Sum or Average 0.491565E+12 0.125744E+12 0.194299E+12 0.00 0.443142E+12 0.00 0.535552E+11 0.363206E+12 0.00 0.00 0.00 0.239124E+11 0.00
Minimum of Months 0.375067E+11 0.851633E+10 0.148500E+11 0.00 0.344944E+11 0.00 0.00 0.127074E+10 0.00 0.00 0.00 0.171449E+10 0.00
Maximum of Months 0.427830E+11 0.126665E+11 0.167807E+11 0.00 0.390945E+11 0.00 0.262885E+11 0.710448E+11 0.00 0.00 0.00 0.230929E+10 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 34530.23 02-JAN-09:09 7996.55 01-JAN-00:10 10740.89 02-JAN-09:09 0.00 24313.24 01-JAN-17:30 0.00 103263.18 08-JAN-08:09
February 34530.23 01-FEB-09:09 7996.55 01-FEB-00:10 10740.89 01-FEB-09:09 0.00 24313.24 06-FEB-12:00 0.00 148607.53 12-FEB-07:30
March 34530.23 01-MAR-09:09 7996.55 01-MAR-00:10 10740.89 01-MAR-09:09 0.00 24313.24 06-MAR-08:09 0.00 18781.63 18-MAR-06:10
April 34530.23 01-APR-09:09 7996.55 01-APR-00:10 10740.89 01-APR-09:09 0.00 24313.24 06-APR-07:19 0.00 27874.97 06-APR-06:10
May 34530.23 01-MAY-08:09 7996.55 01-MAY-00:10 10740.89 01-MAY-08:09 0.00 22670.10 01-MAY-10:39 0.00 499.48 11-MAY-05:00
June 34530.23 01-JUN-08:09 7996.55 01-JUN-00:10 10740.89 01-JUN-08:09 0.00 22670.10 01-JUN-15:39 0.00 0.00 01-JUN-00:10
July 34530.23 01-JUL-09:09 7996.55 01-JUL-00:10 10740.89 01-JUL-09:09 0.00 22670.10 01-JUL-15:09 0.00 0.00 01-JUL-00:10
August 34530.23 01-AUG-08:09 7996.55 01-AUG-00:10 10740.89 01-AUG-08:09 0.00 22670.10 01-AUG-05:30 0.00 0.00 01-AUG-00:10
September 34530.23 01-SEP-08:09 7996.55 01-SEP-00:10 10740.89 01-SEP-08:09 0.00 22670.10 01-SEP-13:50 0.00 0.00 01-SEP-00:10
October 34530.23 02-OCT-08:09 7996.55 01-OCT-00:10 10740.89 02-OCT-08:09 0.00 24313.24 25-OCT-07:00 0.00 18245.99 26-OCT-06:10
November 34530.23 01-NOV-08:09 7996.55 01-NOV-00:10 10740.89 01-NOV-08:09 0.00 24313.24 13-NOV-08:20 0.00 58348.18 22-NOV-07:10
December 34530.23 01-DEC-09:09 7996.55 01-DEC-00:10 10740.89 01-DEC-09:09 0.00 24313.24 01-DEC-08:50 0.00 65100.86 18-DEC-06:10
                         
Annual Sum or Average             0.00     0.00    
Minimum of Months 34530.23   7996.55   10740.89   0.00 22670.10   0.00 0.00  
Maximum of Months 34530.23   7996.55   10740.89   0.00 24313.24   0.00 148607.53  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 13908.85 31-JAN-15:09 0.00 0.00 0.00 2331.28 27-JAN-12:39 0.00
February 23745.51 28-FEB-15:09 0.00 0.00 0.00 2331.54 01-FEB-12:09 0.00
March 38493.50 30-MAR-14:09 0.00 0.00 0.00 2322.02 01-MAR-12:09 0.00
April 37364.33 17-APR-14:39 0.00 0.00 0.00 2164.50 03-APR-11:30 0.00
May 48501.14 30-MAY-14:00 0.00 0.00 0.00 2060.30 01-MAY-11:30 0.00
June 59750.38 23-JUN-13:30 0.00 0.00 0.00 1849.82 01-JUN-11:00 0.00
July 70420.62 08-JUL-14:30 0.00 0.00 0.00 1826.69 03-JUL-11:00 0.00
August 65281.30 01-AUG-14:00 0.00 0.00 0.00 1815.24 31-AUG-11:20 0.00
September 57629.58 06-SEP-14:09 0.00 0.00 0.00 1845.10 29-SEP-11:09 0.00
October 44573.47 10-OCT-14:09 0.00 0.00 0.00 2001.64 31-OCT-11:09 0.00
November 27102.87 02-NOV-14:09 0.00 0.00 0.00 2162.46 30-NOV-12:20 0.00
December 23264.25 12-DEC-13:00 0.00 0.00 0.00 2318.04 29-DEC-12:09 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 13908.85   0.00 0.00 0.00 1815.24   0.00
Maximum of Months 70420.62   0.00 0.00 0.00 2331.54   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 135275.04 07-JAN-17:00 34530.23 10740.89 7996.55 0.00 24313.24 0.00 55991.35 0.00 0.00
February 183889.95 12-FEB-07:30 1918.35 1771.59 7996.55 0.00 23491.67 0.00 148607.53 0.00 0.00
March 107997.05 30-MAR-14:09 34530.23 10740.89 0.00 0.00 22670.10 0.00 0.00 38493.50 0.00
April 106846.74 17-APR-14:30 34530.23 10740.89 0.00 0.00 22670.10 0.00 0.00 37353.11 0.00
May 117767.72 30-MAY-14:50 34530.23 10740.89 0.00 0.00 22670.10 0.00 0.00 48416.59 0.00
June 129110.25 23-JUN-13:30 34530.23 10740.89 0.00 0.00 22670.10 0.00 0.00 59750.38 0.00
July 139759.32 08-JUL-14:39 34530.23 10740.89 0.00 0.00 22670.10 0.00 0.00 70411.71 0.00
August 134499.03 01-AUG-14:00 34530.23 10740.89 0.00 0.00 22670.10 0.00 0.00 65281.30 0.00
September 126877.42 06-SEP-13:00 34530.23 10740.89 0.00 0.00 22670.10 0.00 0.00 57519.87 0.00
October 113926.41 10-OCT-14:09 34530.23 10740.89 0.00 0.00 22670.10 0.00 0.00 44573.47 0.00
November 102417.22 22-NOV-07:10 7673.38 4773.73 7996.55 0.00 23080.88 0.00 58348.18 0.00 0.00
December 109194.79 18-DEC-07:10 7673.38 4773.73 7996.55 0.00 23080.88 0.00 65036.67 0.00 0.00
                       
Annual Sum or Average           0.00   0.00     0.00
Minimum of Months 102417.22   1918.35 1771.59 0.00 0.00 22670.10 0.00 0.00 0.00 0.00
Maximum of Months 183889.95   34530.23 10740.89 7996.55 0.00 24313.24 0.00 148607.53 70411.71 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 11.33 19.51 0.00 19.51 0.00 19.51 0.00 19.51
February 7.83 18.86 0.00 18.86 0.00 18.86 0.00 18.86
March 1.17 20.43 0.00 20.43 0.00 20.43 0.00 20.43
April 0.17 20.47 0.00 20.47 0.17 22.47 0.00 22.47
May 0.00 0.00 0.00 0.00 0.33 24.50 0.00 24.50
June 0.00 0.00 0.00 0.00 4.00 24.51 0.00 24.51
July 0.00 0.00 0.00 0.00 7.33 24.54 0.00 24.54
August 0.00 0.00 0.00 0.00 5.33 24.52 0.00 24.52
September 0.00 0.00 0.00 0.00 1.67 24.49 0.00 24.49
October 0.00 0.00 0.00 0.00 0.33 24.47 0.00 24.47
November 2.00 20.23 0.00 20.23 0.00 20.23 0.00 20.23
December 6.67 20.02 0.00 20.02 0.00 20.02 0.00 20.02
                 
Annual Sum or Average 29.17 19.54 0.00 19.54 19.17 21.52 0.00 21.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.86 0.00 18.86
Maximum of Months 11.33 20.47 0.00 20.47 7.33 24.54 0.00 24.54



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.33 19.88 0.00 19.88 0.00 19.88 0.00 19.88
February 5.00 18.98 0.00 18.98 0.17 19.16 0.00 19.16
March 0.83 20.52 0.00 20.52 1.50 23.07 0.00 23.07
April 0.17 20.50 0.00 20.50 2.17 24.19 0.00 24.19
May 0.00 0.00 0.00 0.00 6.33 24.50 0.00 24.50
June 0.00 0.00 0.00 0.00 16.00 24.56 0.00 24.56
July 0.00 0.00 0.00 0.00 26.67 24.61 0.00 24.61
August 0.00 0.00 0.00 0.00 30.17 24.61 0.00 24.61
September 0.00 0.00 0.00 0.00 15.00 24.54 0.00 24.54
October 0.00 0.00 0.00 0.00 4.67 24.50 0.00 24.50
November 0.83 20.31 0.00 20.31 0.67 22.18 0.00 22.18
December 3.50 20.16 0.00 20.16 0.17 20.36 0.00 20.36
                 
Annual Sum or Average 17.67 19.74 0.00 19.74 103.50 23.87 0.00 23.87
Minimum of Months 0.00 0.00 0.00 0.00 0.00 19.16 0.00 19.16
Maximum of Months 7.33 20.52 0.00 20.52 30.17 24.61 0.00 24.61



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 9.50 19.65 0.00 19.65 0.00 19.65 0.00 19.65
February 7.00 18.77 0.00 18.77 0.00 18.77 0.00 18.77
March 1.00 20.36 0.00 20.36 0.00 20.36 0.00 20.36
April 0.50 20.43 0.00 20.43 0.17 21.46 0.00 21.46
May 0.00 0.00 0.00 0.00 0.67 24.52 0.00 24.52
June 0.00 0.00 0.00 0.00 5.83 24.52 0.00 24.52
July 0.00 0.00 0.00 0.00 14.17 24.55 0.00 24.55
August 0.00 0.00 0.00 0.00 14.83 24.56 0.00 24.56
September 0.00 0.00 0.00 0.00 5.17 24.51 0.00 24.51
October 0.00 0.00 0.00 0.00 0.67 24.50 0.00 24.50
November 1.00 20.12 0.00 20.12 0.00 20.12 0.00 20.12
December 5.67 20.11 0.00 20.11 0.00 20.11 0.00 20.11
                 
Annual Sum or Average 24.67 19.57 0.00 19.57 41.50 22.69 0.00 22.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.77 0.00 18.77
Maximum of Months 9.50 20.43 0.00 20.43 14.83 24.56 0.00 24.56



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 67.33 12.34 65.33 12.31 0.00 12.31 0.00 12.31
February 38.67 13.50 38.67 13.50 0.00 13.50 0.00 13.50
March 46.67 14.00 46.33 14.00 0.00 14.00 0.00 14.00
April 11.83 13.61 11.83 13.61 0.00 13.61 0.00 13.61
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 30.67 14.06 30.67 14.06 0.00 14.06 0.00 14.06
November 38.33 14.07 38.33 14.07 0.00 14.07 0.00 14.07
December 123.17 13.54 122.33 13.54 0.00 13.54 0.00 13.54
                 
Annual Sum or Average 356.67 13.47 353.50 13.47 0.00 13.47 0.00 13.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 123.17 14.07 122.33 14.07 0.00 14.07 0.00 14.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 414.00 21.45 321.50 21.31 321.50 21.26
February 376.00 22.20 186.83 21.84 186.83 21.66
March 352.83 23.13 51.50 22.96 38.50 22.80
April 203.17 23.45 76.50 23.47 9.67 23.40
May 53.83 23.67 250.33 23.85 0.00 23.85
June 12.83 23.85 350.33 23.89 0.00 23.89
July 2.50 23.89 405.33 23.89 2.50 23.89
August 1.67 23.89 416.33 23.89 1.67 23.89
September 27.50 23.84 303.17 23.89 1.33 23.89
October 227.83 23.38 91.67 23.51 4.50 23.49
November 351.00 22.96 51.83 22.78 44.33 22.61
December 405.17 22.01 175.17 21.75 175.17 21.61
             
Annual Sum or Average 2428.33 22.56 2680.50 22.84 786.00 22.62
Minimum of Months 1.67 21.45 51.50 21.31 0.00 21.26
Maximum of Months 414.00 23.89 416.33 23.89 321.50 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 397.17 21.52 150.00 21.40 150.00 21.34
February 297.67 21.98 74.83 21.84 69.67 21.73
March 187.33 22.82 86.33 23.15 1.17 23.14
April 63.67 22.91 235.00 23.68 0.00 23.68
May 11.00 23.07 375.17 23.87 0.00 23.87
June 8.83 23.84 389.67 23.89 5.33 23.89
July 18.33 23.91 415.00 23.89 18.33 23.89
August 43.33 23.92 422.00 23.90 43.33 23.90
September 19.67 23.84 385.67 23.89 16.33 23.89
October 95.50 22.83 211.50 23.56 8.83 23.57
November 243.83 22.76 69.17 22.95 6.33 22.92
December 378.17 22.22 61.83 22.18 44.50 22.08
             
Annual Sum or Average 1764.50 22.31 2876.17 23.13 363.83 23.03
Minimum of Months 8.83 21.52 61.83 21.40 0.00 21.34
Maximum of Months 397.17 23.92 422.00 23.90 150.00 23.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 354.67 22.31 135.00 22.02 127.00 21.84
February 268.17 22.53 110.33 22.42 68.83 22.22
March 169.50 22.99 158.33 23.29 16.17 23.19
April 98.83 23.20 228.17 23.62 6.83 23.57
May 32.17 23.50 338.33 23.86 0.00 23.86
June 11.17 23.75 375.67 23.89 0.00 23.89
July 6.33 23.89 411.67 23.89 6.33 23.89
August 6.50 23.89 419.33 23.89 6.50 23.89
September 15.17 23.81 366.00 23.89 2.00 23.89
October 88.67 23.11 252.67 23.68 1.83 23.67
November 174.50 23.14 152.00 23.40 10.17 23.33
December 296.17 22.81 89.50 22.71 49.50 22.53
             
Annual Sum or Average 1521.83 22.78 3037.00 23.35 295.17 23.22
Minimum of Months 6.33 22.31 89.50 22.02 0.00 21.84
Maximum of Months 354.67 23.89 419.33 23.89 127.00 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 376.17 21.95 165.50 21.70 164.50 21.56
February 295.67 22.20 129.17 22.08 97.33 21.90
March 207.17 22.74 136.33 22.98 27.17 22.84
April 120.17 22.94 204.00 23.45 10.33 23.38
May 48.17 23.32 327.00 23.82 4.33 23.82
June 23.00 23.68 369.83 23.88 9.00 23.88
July 23.00 23.89 412.17 23.89 23.00 23.89
August 29.17 23.89 418.83 23.89 29.17 23.89
September 27.17 23.69 357.83 23.88 9.00 23.88
October 126.00 22.85 235.50 23.51 13.67 23.51
November 202.50 22.75 126.83 23.06 15.00 22.98
December 321.17 22.34 98.50 22.23 72.00 22.07
             
Annual Sum or Average 1799.33 22.51 2981.50 23.15 474.50 23.01
Minimum of Months 23.00 21.95 98.50 21.70 4.33 21.56
Maximum of Months 376.17 23.89 418.83 23.89 164.50 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 414.00 16.00 394.67 15.91 394.67 15.87
February 356.33 17.20 300.67 16.95 291.33 16.77
March 370.50 18.56 270.00 18.42 232.00 18.08
April 297.50 21.07 261.33 21.76 166.83 21.58
May 322.67 24.60 316.83 25.05 241.00 25.18
June 361.67 28.20 377.33 28.25 339.33 28.36
July 415.00 28.49 415.00 28.49 415.00 28.49
August 417.67 28.76 421.67 28.74 417.67 28.75
September 339.67 25.73 342.67 26.07 282.50 26.24
October 345.67 20.71 255.33 20.95 208.17 20.85
November 374.33 18.65 230.50 18.20 218.50 17.92
December 410.17 16.19 380.33 16.02 377.50 15.95
             
Annual Sum or Average 4425.17 22.01 3966.33 22.25 3584.50 22.24
Minimum of Months 297.50 16.00 230.50 15.91 166.83 15.87
Maximum of Months 417.67 28.76 421.67 28.74 417.67 28.75



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 21.45402 23.07706 -0.6030 14.21922
February 376.00000 22.19732 25.25458 -0.3704 10.98068
March 422.00000 23.25112 31.53702 0.00867 6.99189
April 405.00000 23.66906 38.92735 0.23105 7.23554
May 418.00000 23.86131 46.26880 -0.4832 10.46225
June 408.00000 23.88882 48.44878 -0.3550 7.94265
July 415.00000 23.89024 52.76344 -0.3034 7.11552
August 422.00000 23.89026 53.30252 -0.2979 7.01775
September 405.00000 23.88658 50.03343 -0.4274 9.12548
October 414.00000 23.61092 42.57746 0.23458 7.23336
November 399.00000 23.07265 31.52968 -0.0485 7.17238
December 415.00000 22.05890 27.06681 -0.3822 10.06481
           
Annual Sum or Average 4913.00000 23.23475 39.34978 -0.2329 8.78360
Minimum of Months 376.00000 21.45402 23.07706 -0.6030 6.99189
Maximum of Months 422.00000 23.89026 53.30252 0.23458 14.21922



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 21.61349 26.96421 -0.3976 9.98490
February 376.00000 22.37651 29.11297 -0.1546 8.48868
March 422.00000 23.41518 34.61750 0.21706 7.48702
April 405.00000 23.73364 41.03928 0.39425 9.01957
May 418.00000 23.86622 48.07600 -0.3267 7.66117
June 408.00000 23.89008 50.98845 -0.2309 6.37740
July 415.00000 23.89258 56.00520 -0.1833 5.84927
August 422.00000 23.89374 56.64809 -0.1774 5.78259
September 405.00000 23.88722 52.89888 -0.2959 7.06917
October 414.00000 23.64486 45.07251 0.37219 8.74004
November 399.00000 23.19885 34.98330 0.13033 7.10987
December 415.00000 22.37262 30.93291 -0.1523 7.57599
           
Annual Sum or Average 4913.00000 23.32200 42.39068 -0.0672 7.58646
Minimum of Months 376.00000 21.61349 26.96421 -0.3976 5.78259
Maximum of Months 422.00000 23.89374 56.64809 0.39425 9.98490



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 22.53448 25.33493 -0.1967 9.28813
February 376.00000 22.91706 27.73464 -0.0340 8.65999
March 422.00000 23.52980 33.63397 0.25016 8.45866
April 405.00000 23.72222 40.62939 0.37999 9.40914
May 418.00000 23.85995 47.26557 -0.3488 8.49310
June 408.00000 23.88645 49.74200 -0.2365 6.77335
July 415.00000 23.89033 53.80315 -0.1789 6.09619
August 422.00000 23.89037 53.69133 -0.1414 5.86980
September 405.00000 23.88747 50.14732 -0.2519 7.09054
October 414.00000 23.72393 43.21135 0.43632 10.36435
November 399.00000 23.56003 33.31311 0.26039 8.31572
December 415.00000 23.12146 28.90653 0.03213 7.76368
           
Annual Sum or Average 4913.00000 23.54784 40.72673 -0.0031 8.04086
Minimum of Months 376.00000 22.53448 25.33493 -0.3488 5.86980
Maximum of Months 422.00000 23.89037 53.80315 0.43632 10.36435



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 22.13128 26.02910 -0.3083 10.22774
February 376.00000 22.56183 28.57063 -0.1349 9.27036
March 422.00000 23.32690 34.35461 0.17591 8.24627
April 405.00000 23.60703 41.47290 0.32495 8.89451
May 418.00000 23.82460 48.55029 -0.3981 9.47404
June 408.00000 23.87841 50.87301 -0.2710 7.17921
July 415.00000 23.89023 55.39223 -0.2060 6.27784
August 422.00000 23.89029 55.24641 -0.1705 6.02861
September 405.00000 23.87689 51.60584 -0.2871 7.53960
October 414.00000 23.57247 44.40007 0.37864 9.84312
November 399.00000 23.31104 34.17788 0.17960 8.10890
December 415.00000 22.69275 29.91559 -0.0827 8.18562
           
Annual Sum or Average 4913.00000 23.38599 41.82754 -0.0670 8.26417
Minimum of Months 376.00000 22.13128 26.02910 -0.3981 6.02861
Maximum of Months 422.00000 23.89029 55.39223 0.37864 10.22774



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 16.00468 32.01401 -1.4154 47.34275
February 376.00000 17.57185 33.61345 -1.0482 34.91498
March 422.00000 19.28057 40.25046 -0.5874 22.73447
April 405.00000 22.16533 45.51588 0.03317 17.07158
May 418.00000 24.70030 53.44586 -0.2014 19.46856
June 408.00000 27.87157 52.83210 0.74345 30.19511
July 415.00000 28.48800 62.16785 1.02080 38.93018
August 422.00000 28.72039 63.34811 1.15175 39.69310
September 405.00000 25.62622 60.68970 0.20646 21.37206
October 414.00000 21.24833 53.69911 -0.0428 19.00995
November 399.00000 18.94247 40.91589 -0.6300 20.95752
December 415.00000 16.27003 39.08764 -1.2566 41.53574
           
Annual Sum or Average 4913.00000 22.28184 48.25933 -0.1613 29.45757
Minimum of Months 376.00000 16.00468 32.01401 -1.4154 17.07158
Maximum of Months 422.00000 28.72039 63.34811 1.15175 47.34275



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.185463E+09 57099757.98 20.50 0.167694E+09 17768436.57 0.00 0.18 31-JAN-15:10 0.00 01-JAN-00:10 4222.86 20-JAN-15:30 4160.71 31-JAN-15:10 649.27 19-JAN-16:00 1285.77 20-JAN-15:30 0.00
February 0.132898E+10 0.404166E+09 96.83 0.129615E+10 32831050.63 0.00 0.41 28-FEB-15:30 0.00 01-FEB-00:10 9657.81 28-FEB-15:30 9657.81 28-FEB-15:30 881.44 19-FEB-15:00 2912.35 28-FEB-15:30 0.00
March 0.509517E+10 0.152284E+10 256.16 0.474604E+10 0.349134E+09 0.00 0.64 30-MAR-14:40 0.00 01-MAR-00:10 16713.07 30-MAR-14:20 15649.38 30-MAR-16:00 2297.86 30-MAR-11:35 4990.45 30-MAR-14:20 0.00
April 0.104380E+11 0.310509E+10 337.79 0.965110E+10 0.786943E+09 0.00 0.66 23-APR-18:25 0.00 01-APR-00:10 18089.63 23-APR-18:25 16008.70 17-APR-15:50 3215.34 04-APR-13:50 4938.35 19-APR-14:50 0.00
May 0.195048E+11 0.568656E+10 446.64 0.168682E+11 0.263666E+10 0.00 1.00 17-MAY-20:13 0.00 01-MAY-00:10 39266.01 29-MAY-18:08 34406.14 29-MAY-18:08 5459.76 30-MAY-21:00 11003.80 29-MAY-18:08 0.00
June 0.300681E+11 0.880558E+10 534.44 0.250542E+11 0.501392E+10 0.00 1.00 04-JUN-18:08 0.00 01-JUN-00:15 54442.93 25-JUN-18:08 44682.18 25-JUN-18:08 10566.10 29-JUN-20:10 15889.86 25-JUN-18:08 0.00
July 0.356181E+11 0.103882E+11 589.46 0.282166E+11 0.740143E+10 0.00 1.00 02-JUL-18:08 0.00 01-JUL-00:05 55148.03 23-JUL-18:08 45393.45 16-JUL-18:06 12932.83 31-JUL-20:10 16362.99 09-JUL-18:06 0.00
August 0.377655E+11 0.109279E+11 617.27 0.292884E+11 0.847709E+10 0.00 1.00 01-AUG-20:08 0.00 01-AUG-00:10 56225.43 20-AUG-18:10 44972.56 13-AUG-18:08 15503.23 22-AUG-20:10 16250.34 06-AUG-18:06 0.00
September 0.231751E+11 0.670093E+10 496.89 0.187651E+11 0.441001E+10 0.00 1.00 03-SEP-18:10 0.00 01-SEP-00:05 50908.40 07-SEP-20:10 39327.83 07-SEP-20:10 11580.58 07-SEP-20:10 13801.40 07-SEP-20:10 0.00
October 0.999726E+10 0.291363E+10 330.33 0.858217E+10 0.141509E+10 0.00 0.89 18-OCT-21:00 0.00 01-OCT-00:10 27083.30 18-OCT-21:00 18746.42 18-OCT-21:00 8829.24 19-OCT-05:05 6800.65 18-OCT-21:00 0.00
November 0.362029E+10 0.107731E+10 202.13 0.326799E+10 0.352308E+09 0.00 0.49 05-NOV-15:30 0.00 01-NOV-00:10 12710.82 05-NOV-15:30 10592.98 05-NOV-15:30 2453.60 05-NOV-13:30 3701.70 05-NOV-15:30 0.00
December 0.638744E+09 0.191634E+09 41.18 0.533121E+09 0.105623E+09 0.00 0.34 13-DEC-13:00 0.00 01-DEC-00:10 8670.28 13-DEC-13:00 6923.53 12-DEC-14:40 1978.76 13-DEC-12:30 2517.79 13-DEC-13:00 0.00
                                       
Annual Sum or Average 0.177436E+12 0.517809E+11 3969.62 0.146437E+12 0.309988E+11 0.00                         0.00
Minimum of Months 0.185463E+09 57099757.98 20.50 0.167694E+09 17768436.57 0.00 0.18   0.00   4222.86   4160.71   649.27   1285.77   0.00
Maximum of Months 0.377655E+11 0.109279E+11 617.27 0.292884E+11 0.847709E+10 0.00 1.00   0.00   56225.43   45393.45   15503.23   16362.99   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.178227E+10 0.551496E+09 32.70 0.139083E+10 0.391444E+09 0.00 0.36 31-JAN-15:10 0.00 01-JAN-00:10 30947.94 31-JAN-15:10 27249.90 31-JAN-15:10 9545.88 19-JAN-16:00 9264.95 31-JAN-15:10 0.00
February 0.937139E+10 0.284711E+10 121.58 0.874239E+10 0.628997E+09 0.00 0.58 28-FEB-15:10 0.00 01-FEB-00:10 51297.22 28-FEB-15:10 51297.22 28-FEB-15:10 11035.72 18-FEB-17:00 15336.99 28-FEB-15:10 0.00
March 0.323694E+11 0.952228E+10 295.30 0.280370E+11 0.433238E+10 0.00 0.90 30-MAR-14:10 0.00 01-MAR-00:10 89890.27 30-MAR-14:10 76318.58 30-MAR-14:30 19974.84 30-MAR-11:25 25511.99 30-MAR-14:10 0.00
April 0.592654E+11 0.171567E+11 348.21 0.505319E+11 0.873349E+10 0.00 0.90 19-APR-14:50 0.00 01-APR-00:10 90545.99 19-APR-14:40 81046.01 17-APR-14:50 26460.93 04-APR-14:10 25334.18 17-APR-14:40 0.00
May 0.977945E+11 0.274937E+11 402.11 0.759326E+11 0.218620E+11 0.00 1.00 06-MAY-06:03 0.00 01-MAY-00:10 204969.68 31-MAY-06:03 138165.60 07-MAY-08:62 84931.76 31-MAY-06:03 52728.69 31-MAY-06:03 0.00
June 0.134832E+12 0.383994E+11 415.03 0.997162E+11 0.351155E+11 0.00 1.00 01-JUN-06:03 0.00 01-JUN-00:10 208471.32 23-JUN-06:02 184844.48 11-JUN-08:62 94063.91 23-JUN-06:04 54319.12 25-JUN-08:62 0.00
July 0.155976E+12 0.444207E+11 432.78 0.106580E+12 0.493955E+11 0.00 1.00 01-JUL-06:02 0.00 01-JUL-00:05 212796.42 30-JUL-08:62 138197.61 25-JUL-06:02 109586.27 30-JUL-08:04 55795.24 16-JUL-08:62 0.00
August 0.165146E+12 0.465414E+11 443.88 0.110193E+12 0.549527E+11 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:05 213086.14 20-AUG-08:62 147487.17 26-AUG-06:02 107934.59 20-AUG-08:04 55287.48 06-AUG-08:62 0.00
September 0.108064E+12 0.301211E+11 408.19 0.760946E+11 0.319699E+11 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:05 212345.32 17-SEP-08:62 139761.46 24-SEP-08:62 106307.93 17-SEP-08:04 54758.06 17-SEP-08:62 0.00
October 0.521093E+11 0.148479E+11 327.74 0.403328E+11 0.117764E+11 0.00 1.00 18-OCT-06:03 0.00 01-OCT-00:10 210092.71 19-OCT-06:02 112832.55 18-OCT-06:03 103973.60 19-OCT-06:04 53388.76 19-OCT-06:02 0.00
November 0.210594E+11 0.623105E+10 221.90 0.175743E+11 0.348505E+10 0.00 0.68 04-NOV-15:55 0.00 01-NOV-00:10 66632.24 04-NOV-15:55 49105.03 02-NOV-14:30 22182.88 04-NOV-15:55 18118.30 04-NOV-15:55 0.00
December 0.509893E+10 0.153548E+10 84.31 0.394907E+10 0.114986E+10 0.00 0.55 12-DEC-14:00 0.00 01-DEC-00:10 51449.98 13-DEC-13:00 38694.79 12-DEC-15:10 17160.27 13-DEC-12:30 14759.66 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.842868E+12 0.239668E+12 3533.74 0.619075E+12 0.223793E+12 0.00                         0.00
Minimum of Months 0.178227E+10 0.551496E+09 32.70 0.139083E+10 0.391444E+09 0.00 0.36   0.00   30947.94   27249.90   9545.88   9264.95   0.00
Maximum of Months 0.165146E+12 0.465414E+11 443.88 0.110193E+12 0.549527E+11 0.00 1.00   0.00   213086.14   184844.48   109586.27   55795.24   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.171251E+10 0.465585E+09 148.67 0.162921E+10 83294736.95 0.00 0.60 31-JAN-12:55 0.00 01-JAN-00:10 7857.99 31-JAN-12:55 7426.19 28-JAN-15:10 1524.56 19-JAN-15:30 2004.53 31-JAN-12:55 0.00
February 0.349051E+10 0.904056E+09 195.26 0.338018E+10 0.110324E+09 0.00 0.95 21-FEB-14:50 0.00 01-FEB-00:10 13329.50 21-FEB-14:40 13329.50 21-FEB-14:40 1348.23 18-FEB-16:10 3119.85 21-FEB-15:00 0.00
March 0.777568E+10 0.199892E+10 350.49 0.726619E+10 0.509487E+09 0.00 1.00 30-MAR-12:30 0.00 01-MAR-00:10 17476.04 30-MAR-20:10 15784.70 30-MAR-20:10 2378.67 30-MAR-11:25 4304.61 30-MAR-14:10 0.00
April 0.101740E+11 0.262817E+10 380.43 0.925640E+10 0.917618E+09 0.00 1.00 12-APR-14:00 0.00 01-APR-00:10 16242.91 16-APR-18:10 15904.81 16-APR-18:10 3034.11 04-APR-13:30 3938.55 16-APR-18:10 0.00
May 0.150041E+11 0.385561E+10 485.10 0.125887E+11 0.241539E+10 0.00 1.00 05-MAY-13:50 0.00 01-MAY-00:10 23966.97 29-MAY-18:08 20420.11 29-MAY-18:08 5509.64 30-MAY-20:10 6395.79 29-MAY-18:08 0.00
June 0.209320E+11 0.552137E+10 565.63 0.167755E+11 0.415656E+10 0.00 1.00 01-JUN-12:50 0.00 01-JUN-00:10 27743.90 13-JUN-20:08 23261.70 11-JUN-18:08 7039.85 22-JUN-20:10 7645.98 11-JUN-18:08 0.00
July 0.248537E+11 0.659272E+10 619.41 0.188077E+11 0.604596E+10 0.00 1.00 01-JUL-10:20 0.00 01-JUL-00:05 28230.97 06-JUL-20:08 22453.95 16-JUL-18:06 8841.66 26-JUL-20:10 7758.45 09-JUL-18:06 0.00
August 0.278201E+11 0.732193E+10 643.20 0.207425E+11 0.707757E+10 0.00 1.00 01-AUG-09:50 0.00 01-AUG-00:10 28739.70 22-AUG-20:08 22575.93 13-AUG-18:08 9235.50 08-AUG-20:10 7699.89 06-AUG-18:06 0.00
September 0.192840E+11 0.492692E+10 556.69 0.152833E+11 0.400068E+10 0.00 1.00 01-SEP-14:20 0.00 01-SEP-00:05 28271.03 06-SEP-20:08 21514.15 08-SEP-20:08 7497.01 06-SEP-20:08 7248.17 08-SEP-20:08 0.00
October 0.120453E+11 0.300820E+10 415.40 0.105038E+11 0.154144E+10 0.00 1.00 02-OCT-11:00 0.00 01-OCT-00:10 24019.60 09-OCT-18:08 20088.18 09-OCT-18:08 6919.82 18-OCT-20:10 5890.17 09-OCT-18:08 0.00
November 0.704482E+10 0.178342E+10 319.32 0.655639E+10 0.488431E+09 0.00 0.96 08-NOV-15:10 0.00 01-NOV-00:10 13808.72 05-NOV-13:50 13403.30 08-NOV-15:10 2672.92 05-NOV-12:20 3265.93 05-NOV-14:00 0.00
December 0.363032E+10 0.951354E+09 238.00 0.341843E+10 0.211885E+09 0.00 0.95 12-DEC-14:00 0.00 01-DEC-00:10 13912.32 12-DEC-14:00 12075.79 12-DEC-14:00 2210.19 13-DEC-11:10 3263.83 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.153767E+12 0.399583E+11 4917.60 0.126208E+12 0.275586E+11 0.00                         0.00
Minimum of Months 0.171251E+10 0.465585E+09 148.67 0.162921E+10 83294736.95 0.00 0.60   0.00   7857.99   7426.19   1348.23   2004.53   0.00
Maximum of Months 0.278201E+11 0.732193E+10 643.20 0.207425E+11 0.707757E+10 0.00 1.00   0.00   28739.70   23261.70   9235.50   7758.45   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.706669E+09 0.196559E+09 92.56 0.661486E+09 45182870.23 0.00 0.45 31-JAN-12:55 0.00 01-JAN-00:10 5687.80 31-JAN-12:55 5359.35 29-JAN-15:30 1023.17 19-JAN-15:40 1513.16 31-JAN-12:55 0.00
February 0.211611E+10 0.558235E+09 142.82 0.207320E+10 42914228.80 0.00 0.83 21-FEB-14:40 0.00 01-FEB-00:10 11164.35 21-FEB-14:40 11164.35 21-FEB-14:40 898.12 19-FEB-14:30 2709.32 26-FEB-15:00 0.00
March 0.523538E+10 0.138460E+10 299.05 0.480524E+10 0.430138E+09 0.00 1.00 30-MAR-13:50 0.00 01-MAR-00:10 14693.11 30-MAR-14:10 13218.20 30-MAR-14:10 2441.03 30-MAR-11:35 3690.65 30-MAR-14:10 0.00
April 0.742464E+10 0.198149E+10 335.30 0.662429E+10 0.800350E+09 0.00 0.91 17-APR-14:10 0.00 01-APR-00:10 12946.55 16-APR-18:10 12569.12 16-APR-18:10 2897.02 04-APR-13:30 3373.49 17-APR-14:10 0.00
May 0.116232E+11 0.307627E+10 431.70 0.947153E+10 0.215163E+10 0.00 1.00 21-MAY-18:10 0.00 01-MAY-00:10 20217.96 29-MAY-18:08 16920.43 29-MAY-18:08 4907.01 30-MAY-20:10 5322.07 29-MAY-18:08 0.00
June 0.172729E+11 0.461860E+10 528.95 0.134366E+11 0.383636E+10 0.00 1.00 04-JUN-18:08 0.00 01-JUN-00:10 27540.81 25-JUN-18:08 21223.27 25-JUN-18:08 6527.79 22-JUN-20:10 7503.54 25-JUN-18:08 0.00
July 0.209145E+11 0.558958E+10 594.28 0.153382E+11 0.557633E+10 0.00 1.00 01-JUL-11:03 0.00 01-JUL-00:05 27579.95 07-JUL-20:08 21786.81 16-JUL-18:06 8428.46 26-JUL-20:10 7723.46 09-JUL-18:06 0.00
August 0.236328E+11 0.625353E+10 628.52 0.170790E+11 0.655382E+10 0.00 1.00 01-AUG-10:20 0.00 01-AUG-00:10 28082.96 17-AUG-20:08 21845.55 27-AUG-18:08 8935.17 08-AUG-20:10 7666.19 06-AUG-18:06 0.00
September 0.156546E+11 0.406494E+10 515.28 0.120163E+11 0.363828E+10 0.00 1.00 03-SEP-18:10 0.00 01-SEP-00:30 25751.72 07-SEP-20:08 18393.85 07-SEP-20:08 7357.88 07-SEP-20:08 6533.12 07-SEP-20:08 0.00
October 0.908119E+10 0.231555E+10 361.05 0.772673E+10 0.135446E+10 0.00 1.00 02-OCT-13:10 0.00 01-OCT-00:10 20080.22 09-OCT-18:08 16488.76 09-OCT-18:08 4931.96 18-OCT-20:55 4853.17 09-OCT-18:08 0.00
November 0.471911E+10 0.122689E+10 265.94 0.432046E+10 0.398653E+09 0.00 0.83 06-NOV-13:50 0.00 01-NOV-00:10 11786.09 05-NOV-13:50 11173.71 06-NOV-14:10 2609.49 05-NOV-12:40 2878.87 05-NOV-14:00 0.00
December 0.198821E+10 0.531784E+09 157.58 0.184173E+10 0.146482E+09 0.00 0.82 12-DEC-14:00 0.00 01-DEC-00:10 11578.76 12-DEC-14:00 9745.73 12-DEC-14:00 2071.68 12-DEC-12:30 2825.83 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.120369E+12 0.317980E+11 4353.02 0.953947E+11 0.249746E+11 0.00                         0.00
Minimum of Months 0.706669E+09 0.196559E+09 92.56 0.661486E+09 42914228.80 0.00 0.45   0.00   5687.80   5359.35   898.12   1513.16   0.00
Maximum of Months 0.236328E+11 0.625353E+10 628.52 0.170790E+11 0.655382E+10 0.00 1.00   0.00   28082.96   21845.55   8935.17   7723.46   0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.76 19.53 16.23 32.83 64.87 0.00 0.00 0.00
February 45.11 27.84 17.27 50.17 57.23 0.00 0.00 0.00
March 66.04 40.42 25.63 84.36 41.91 0.00 0.00 0.00
April 83.46 51.70 31.77 117.09 34.76 0.00 0.00 0.00
May 92.57 53.48 39.08 136.45 24.74 0.00 0.00 0.00
June 98.82 58.24 40.58 153.51 18.88 0.00 0.00 0.00
July 91.94 51.99 39.95 145.88 14.74 0.00 0.00 0.00
August 84.54 46.19 38.35 135.35 14.08 0.00 0.00 0.00
September 63.07 35.18 27.89 93.52 23.52 0.00 0.00 0.00
October 53.83 36.17 17.66 71.83 39.68 0.00 0.00 0.00
November 39.69 22.30 17.39 45.95 50.66 0.00 0.00 0.00
December 32.22 17.29 14.93 31.30 59.06 4.83 0.00 0.00
                 
Annual Sum or Average 65.69 38.41 27.28 91.74 36.90 4.83 0.00 0.00
Minimum of Months 32.22 17.29 14.93 31.30 14.08 0.00 0.00 0.00
Maximum of Months 98.82 58.24 40.58 153.51 64.87 4.83 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: POINT_OF_SALE_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1389.06 968.45 420.61 1520.39 1742.65 0.00 0.00 0.00
February 1296.46 869.05 427.41 1570.39 1507.38 0.00 0.00 0.00
March 1165.95 607.63 558.33 1543.83 1048.37 0.00 0.00 0.00
April 873.22 284.25 588.97 1304.86 851.46 0.00 0.00 0.00
May 705.53 82.00 623.53 1124.47 555.36 0.00 0.00 0.00
June 652.34 36.30 616.04 1265.39 339.56 0.00 0.00 0.00
July 659.50 49.18 610.32 1361.18 225.45 0.00 0.00 0.00
August 787.39 147.09 640.31 1644.32 186.47 0.00 0.00 0.00
September 865.94 322.08 543.86 1507.11 471.16 0.00 0.00 0.00
October 1255.36 813.22 442.14 1851.80 991.98 0.00 0.00 0.00
November 1350.54 896.20 454.35 1764.85 1283.64 0.00 0.00 0.00
December 1369.23 963.26 405.97 1608.40 1536.21 0.00 0.00 0.00
                 
Annual Sum or Average 1029.74 501.52 528.22 1505.54 891.68 0.00 0.00 0.00
Minimum of Months 652.34 36.30 405.97 1124.47 186.47 0.00 0.00 0.00
Maximum of Months 1389.06 968.45 640.31 1851.80 1742.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FRONT_RETAIL_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1389.06 968.45 420.61 1531.79 1690.62 0.00 0.00 0.00
February 1296.46 869.05 427.41 1579.04 1458.41 0.00 0.00 0.00
March 1165.95 607.63 558.33 1550.48 1009.29 0.00 0.00 0.00
April 873.22 284.25 588.97 1307.62 818.81 0.00 0.00 0.00
May 705.53 82.00 623.53 1123.09 536.25 0.00 0.00 0.00
June 652.34 36.30 616.04 1259.71 331.35 0.00 0.00 0.00
July 659.50 49.18 610.32 1355.90 219.69 0.00 0.00 0.00
August 787.39 147.09 640.31 1638.75 180.32 0.00 0.00 0.00
September 865.94 322.08 543.86 1502.82 461.45 0.00 0.00 0.00
October 1255.36 813.22 442.14 1853.36 962.67 0.00 0.00 0.00
November 1350.54 896.20 454.35 1771.10 1242.38 0.00 0.00 0.00
December 1369.23 963.26 405.97 1619.02 1480.19 0.00 0.00 0.00
                 
Annual Sum or Average 1029.74 501.52 528.22 1507.66 862.75 0.00 0.00 0.00
Minimum of Months 652.34 36.30 405.97 1123.09 180.32 0.00 0.00 0.00
Maximum of Months 1389.06 968.45 640.31 1853.36 1690.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FRONT_ENTRY_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 178.78 124.65 54.14 216.46 187.91 0.00 0.00 0.00
February 166.87 111.85 55.01 217.72 163.13 0.00 0.00 0.00
March 150.07 78.21 71.86 217.30 113.92 0.00 0.00 0.00
April 112.39 36.59 75.81 173.80 98.53 0.00 0.00 0.00
May 90.81 10.55 80.25 139.33 69.31 0.00 0.00 0.00
June 83.96 4.67 79.29 139.00 50.57 0.00 0.00 0.00
July 84.88 6.33 78.55 146.48 37.95 0.33 0.00 0.00
August 101.34 18.93 82.41 180.51 35.50 0.00 0.00 0.00
September 111.45 41.45 70.00 181.60 64.58 0.00 0.00 0.00
October 161.58 104.67 56.91 245.13 113.06 0.00 0.00 0.00
November 173.83 115.35 58.48 243.38 139.00 0.00 0.00 0.00
December 176.23 123.98 52.25 229.58 157.84 0.00 0.00 0.00
                 
Annual Sum or Average 132.54 64.55 67.99 194.11 102.27 0.33 0.00 0.00
Minimum of Months 83.96 4.67 52.25 139.00 35.50 0.00 0.00 0.00
Maximum of Months 178.78 124.65 82.41 245.13 187.91 0.33 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 95779921.66 52302530.61 43477391.05 87929974.35 0.173754E+09
February 0.109130E+09 67357785.24 41772017.52 0.121372E+09 0.138439E+09
March 0.176892E+09 0.108250E+09 68641588.58 0.225958E+09 0.112248E+09
April 0.216340E+09 0.134004E+09 82335109.35 0.303499E+09 90106488.82
May 0.247928E+09 0.143244E+09 0.104684E+09 0.365469E+09 66253978.58
June 0.256146E+09 0.150968E+09 0.105178E+09 0.397904E+09 48943520.42
July 0.246251E+09 0.139260E+09 0.106991E+09 0.390737E+09 39468317.19
August 0.226423E+09 0.123719E+09 0.102704E+09 0.362514E+09 37708056.74
September 0.163480E+09 91180584.39 72299198.61 0.242395E+09 60956069.67
October 0.144168E+09 96874716.40 47293026.62 0.192391E+09 0.106280E+09
November 0.102874E+09 57801111.55 45073362.61 0.119115E+09 0.131300E+09
December 86290069.36 46308356.91 39981712.45 83836095.90 0.158185E+09
           
Annual Sum or Average 0.207170E+10 0.121127E+10 0.860430E+09 0.289312E+10 0.116364E+10
Minimum of Months 86290069.36 46308356.91 39981712.45 83836095.90 37708056.74
Maximum of Months 0.256146E+09 0.150968E+09 0.106991E+09 0.397904E+09 0.173754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: POINT_OF_SALE_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.372045E+10 0.259389E+10 0.112657E+10 0.407221E+10 0.466751E+10
February 0.313639E+10 0.210241E+10 0.103398E+10 0.379908E+10 0.364665E+10
March 0.312289E+10 0.162746E+10 0.149543E+10 0.413499E+10 0.280796E+10
April 0.226339E+10 0.736781E+09 0.152661E+10 0.338219E+10 0.220698E+10
May 0.188969E+10 0.219632E+09 0.167006E+10 0.301178E+10 0.148749E+10
June 0.169086E+10 94089014.43 0.159677E+10 0.327990E+10 0.880135E+09
July 0.176640E+10 0.131712E+09 0.163469E+10 0.364578E+10 0.603855E+09
August 0.210896E+10 0.393959E+09 0.171500E+10 0.440414E+10 0.499431E+09
September 0.224451E+10 0.834840E+09 0.140967E+10 0.390642E+10 0.122126E+10
October 0.336237E+10 0.217814E+10 0.118422E+10 0.495987E+10 0.265691E+10
November 0.350061E+10 0.232294E+10 0.117767E+10 0.457449E+10 0.332718E+10
December 0.366734E+10 0.258000E+10 0.108734E+10 0.430794E+10 0.411459E+10
           
Annual Sum or Average 0.324739E+11 0.158159E+11 0.166580E+11 0.474788E+11 0.281199E+11
Minimum of Months 0.169086E+10 94089014.43 0.103398E+10 0.301178E+10 0.499431E+09
Maximum of Months 0.372045E+10 0.259389E+10 0.171500E+10 0.495987E+10 0.466751E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: FRONT_RETAIL_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.372045E+10 0.259389E+10 0.112657E+10 0.410275E+10 0.452814E+10
February 0.313639E+10 0.210241E+10 0.103398E+10 0.382002E+10 0.352819E+10
March 0.312289E+10 0.162746E+10 0.149543E+10 0.415281E+10 0.270328E+10
April 0.226339E+10 0.736781E+09 0.152661E+10 0.338934E+10 0.212236E+10
May 0.188969E+10 0.219632E+09 0.167006E+10 0.300809E+10 0.143628E+10
June 0.169086E+10 94089014.43 0.159677E+10 0.326516E+10 0.858855E+09
July 0.176640E+10 0.131712E+09 0.163469E+10 0.363165E+10 0.588415E+09
August 0.210896E+10 0.393959E+09 0.171500E+10 0.438923E+10 0.482981E+09
September 0.224451E+10 0.834840E+09 0.140967E+10 0.389532E+10 0.119607E+10
October 0.336237E+10 0.217814E+10 0.118422E+10 0.496404E+10 0.257842E+10
November 0.350061E+10 0.232294E+10 0.117767E+10 0.459070E+10 0.322025E+10
December 0.366734E+10 0.258000E+10 0.108734E+10 0.433637E+10 0.396454E+10
           
Annual Sum or Average 0.324739E+11 0.158159E+11 0.166580E+11 0.475455E+11 0.272078E+11
Minimum of Months 0.169086E+10 94089014.43 0.103398E+10 0.300809E+10 0.482981E+09
Maximum of Months 0.372045E+10 0.259389E+10 0.171500E+10 0.496404E+10 0.452814E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: FRONT_ENTRY_WALL_SOUTH_GLAZING

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.478854E+09 0.333856E+09 0.144999E+09 0.579779E+09 0.503287E+09
February 0.403680E+09 0.270598E+09 0.133082E+09 0.526707E+09 0.394652E+09
March 0.401943E+09 0.209469E+09 0.192474E+09 0.582014E+09 0.305118E+09
April 0.291317E+09 94830083.72 0.196487E+09 0.450477E+09 0.255380E+09
May 0.243218E+09 28268572.45 0.214950E+09 0.373193E+09 0.185651E+09
June 0.217627E+09 12110074.42 0.205517E+09 0.360289E+09 0.131082E+09
July 0.227350E+09 16952538.31 0.210398E+09 0.392323E+09 0.101644E+09
August 0.271440E+09 50705972.89 0.220734E+09 0.483481E+09 95077850.60
September 0.288888E+09 0.107451E+09 0.181437E+09 0.470706E+09 0.167393E+09
October 0.432765E+09 0.280346E+09 0.152419E+09 0.656566E+09 0.302812E+09
November 0.450558E+09 0.298983E+09 0.151575E+09 0.630851E+09 0.360290E+09
December 0.472018E+09 0.332068E+09 0.139950E+09 0.614915E+09 0.422771E+09
           
Annual Sum or Average 0.417966E+10 0.203564E+10 0.214402E+10 0.612130E+10 0.322516E+10
Minimum of Months 0.217627E+09 12110074.42 0.133082E+09 0.360289E+09 95077850.60
Maximum of Months 0.478854E+09 0.333856E+09 0.220734E+09 0.656566E+09 0.503287E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 525.27 1037.96 572.16 312.44 259.72 0.00 0.00
February 802.72 915.60 721.76 445.49 276.27 0.00 0.00
March 1349.81 670.54 1056.70 646.65 410.05 0.00 0.00
April 1873.45 556.21 1335.43 827.19 508.24 0.00 0.00
May 2183.21 395.78 1481.05 855.70 625.35 0.00 0.00
June 2456.20 302.12 1581.15 931.90 649.25 0.00 0.00
July 2334.15 235.77 1471.03 831.90 639.13 0.00 0.00
August 2165.55 225.26 1352.58 739.06 613.52 0.00 0.00
September 1496.27 376.27 1009.13 562.84 446.29 0.00 0.00
October 1149.29 634.89 861.22 578.70 282.52 0.00 0.00
November 735.28 810.50 635.03 356.80 278.23 0.00 0.00
December 500.81 944.95 515.47 276.63 238.84 0.00 0.00
               
Annual Sum or Average 1467.84 590.38 1051.09 614.55 436.54 0.00 0.00
Minimum of Months 500.81 225.26 515.47 276.63 238.84 0.00 0.00
Maximum of Months 2456.20 1037.96 1581.15 931.90 649.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1520.39 1742.65 1389.06 968.45 420.61 0.00 0.00
February 1570.39 1507.38 1296.46 869.05 427.41 0.00 0.00
March 1543.83 1048.37 1165.95 607.63 558.33 0.00 0.00
April 1304.86 851.46 873.22 284.25 588.97 0.00 0.00
May 1124.47 555.36 705.53 82.00 623.53 0.00 0.00
June 1265.39 339.56 652.34 36.30 616.04 0.00 0.00
July 1361.18 225.45 659.50 49.18 610.32 0.00 0.00
August 1644.32 186.47 787.39 147.09 640.31 0.00 0.00
September 1507.11 471.16 865.94 322.08 543.86 0.00 0.00
October 1851.80 991.98 1255.36 813.22 442.14 0.00 0.00
November 1764.85 1283.64 1350.54 896.20 454.35 0.00 0.00
December 1608.40 1536.21 1369.23 963.26 405.97 0.00 0.00
               
Annual Sum or Average 1505.54 891.68 1029.74 501.52 528.22 0.00 0.00
Minimum of Months 1124.47 186.47 652.34 36.30 405.97 0.00 0.00
Maximum of Months 1851.80 1742.65 1389.06 968.45 640.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1531.79 1690.62 1389.06 968.45 420.61 0.00 0.00
February 1579.04 1458.41 1296.46 869.05 427.41 0.00 0.00
March 1550.48 1009.29 1165.95 607.63 558.33 0.00 0.00
April 1307.62 818.81 873.22 284.25 588.97 0.00 0.00
May 1123.09 536.25 705.53 82.00 623.53 0.00 0.00
June 1259.71 331.35 652.34 36.30 616.04 0.00 0.00
July 1355.90 219.69 659.50 49.18 610.32 0.00 0.00
August 1638.75 180.32 787.39 147.09 640.31 0.00 0.00
September 1502.82 461.45 865.94 322.08 543.86 0.00 0.00
October 1853.36 962.67 1255.36 813.22 442.14 0.00 0.00
November 1771.10 1242.38 1350.54 896.20 454.35 0.00 0.00
December 1619.02 1480.19 1369.23 963.26 405.97 0.00 0.00
               
Annual Sum or Average 1507.66 862.75 1029.74 501.52 528.22 0.00 0.00
Minimum of Months 1123.09 180.32 652.34 36.30 405.97 0.00 0.00
Maximum of Months 1853.36 1690.62 1389.06 968.45 640.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 216.46 187.91 178.78 124.65 54.14 0.00 0.00
February 217.72 163.13 166.87 111.85 55.01 0.00 0.00
March 217.30 113.92 150.07 78.21 71.86 0.00 0.00
April 173.80 98.53 112.39 36.59 75.81 0.00 0.00
May 139.33 69.31 90.81 10.55 80.25 0.00 0.00
June 139.00 50.57 83.96 4.67 79.29 0.00 0.00
July 146.48 37.95 84.88 6.33 78.55 0.00 0.00
August 180.51 35.50 101.34 18.93 82.41 0.00 0.00
September 181.60 64.58 111.45 41.45 70.00 0.00 0.00
October 245.13 113.06 161.58 104.67 56.91 0.00 0.00
November 243.38 139.00 173.83 115.35 58.48 0.00 0.00
December 229.58 157.84 176.23 123.98 52.25 0.00 0.00
               
Annual Sum or Average 194.11 102.27 132.54 64.55 67.99 0.00 0.00
Minimum of Months 139.00 35.50 83.96 4.67 52.25 0.00 0.00
Maximum of Months 245.13 187.91 178.78 124.65 82.41 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.140688E+10 0.278006E+10 0.153248E+10 0.836840E+09 0.695638E+09 0.00 0.00
February 0.194195E+10 0.221502E+10 0.174608E+10 0.107772E+10 0.668352E+09 0.00 0.00
March 0.361533E+10 0.179597E+10 0.283026E+10 0.173200E+10 0.109827E+10 0.00 0.00
April 0.485598E+10 0.144170E+10 0.346143E+10 0.214407E+10 0.131736E+10 0.00 0.00
May 0.584751E+10 0.106006E+10 0.396685E+10 0.229191E+10 0.167494E+10 0.00 0.00
June 0.636646E+10 0.783096E+09 0.409833E+10 0.241549E+10 0.168285E+10 0.00 0.00
July 0.625179E+10 0.631493E+09 0.394002E+10 0.222817E+10 0.171185E+10 0.00 0.00
August 0.580022E+10 0.603329E+09 0.362276E+10 0.197950E+10 0.164326E+10 0.00 0.00
September 0.387832E+10 0.975297E+09 0.261568E+10 0.145889E+10 0.115679E+10 0.00 0.00
October 0.307826E+10 0.170048E+10 0.230668E+10 0.155000E+10 0.756688E+09 0.00 0.00
November 0.190584E+10 0.210081E+10 0.164599E+10 0.924818E+09 0.721174E+09 0.00 0.00
December 0.134138E+10 0.253097E+10 0.138064E+10 0.740934E+09 0.639707E+09 0.00 0.00
               
Annual Sum or Average 0.462899E+11 0.186183E+11 0.331472E+11 0.193803E+11 0.137669E+11 0.00 0.00
Minimum of Months 0.134138E+10 0.603329E+09 0.138064E+10 0.740934E+09 0.639707E+09 0.00 0.00
Maximum of Months 0.636646E+10 0.278006E+10 0.409833E+10 0.241549E+10 0.171185E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.407221E+10 0.466751E+10 0.372045E+10 0.259389E+10 0.112657E+10 0.00 0.00
February 0.379908E+10 0.364665E+10 0.313639E+10 0.210241E+10 0.103398E+10 0.00 0.00
March 0.413499E+10 0.280796E+10 0.312289E+10 0.162746E+10 0.149543E+10 0.00 0.00
April 0.338219E+10 0.220698E+10 0.226339E+10 0.736781E+09 0.152661E+10 0.00 0.00
May 0.301178E+10 0.148749E+10 0.188969E+10 0.219632E+09 0.167006E+10 0.00 0.00
June 0.327990E+10 0.880135E+09 0.169086E+10 94089014.43 0.159677E+10 0.00 0.00
July 0.364578E+10 0.603855E+09 0.176640E+10 0.131712E+09 0.163469E+10 0.00 0.00
August 0.440414E+10 0.499431E+09 0.210896E+10 0.393959E+09 0.171500E+10 0.00 0.00
September 0.390642E+10 0.122126E+10 0.224451E+10 0.834840E+09 0.140967E+10 0.00 0.00
October 0.495987E+10 0.265691E+10 0.336237E+10 0.217814E+10 0.118422E+10 0.00 0.00
November 0.457449E+10 0.332718E+10 0.350061E+10 0.232294E+10 0.117767E+10 0.00 0.00
December 0.430794E+10 0.411459E+10 0.366734E+10 0.258000E+10 0.108734E+10 0.00 0.00
               
Annual Sum or Average 0.474788E+11 0.281199E+11 0.324739E+11 0.158159E+11 0.166580E+11 0.00 0.00
Minimum of Months 0.301178E+10 0.499431E+09 0.169086E+10 94089014.43 0.103398E+10 0.00 0.00
Maximum of Months 0.495987E+10 0.466751E+10 0.372045E+10 0.259389E+10 0.171500E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.410275E+10 0.452814E+10 0.372045E+10 0.259389E+10 0.112657E+10 0.00 0.00
February 0.382002E+10 0.352819E+10 0.313639E+10 0.210241E+10 0.103398E+10 0.00 0.00
March 0.415281E+10 0.270328E+10 0.312289E+10 0.162746E+10 0.149543E+10 0.00 0.00
April 0.338934E+10 0.212236E+10 0.226339E+10 0.736781E+09 0.152661E+10 0.00 0.00
May 0.300809E+10 0.143628E+10 0.188969E+10 0.219632E+09 0.167006E+10 0.00 0.00
June 0.326516E+10 0.858855E+09 0.169086E+10 94089014.43 0.159677E+10 0.00 0.00
July 0.363165E+10 0.588415E+09 0.176640E+10 0.131712E+09 0.163469E+10 0.00 0.00
August 0.438923E+10 0.482981E+09 0.210896E+10 0.393959E+09 0.171500E+10 0.00 0.00
September 0.389532E+10 0.119607E+10 0.224451E+10 0.834840E+09 0.140967E+10 0.00 0.00
October 0.496404E+10 0.257842E+10 0.336237E+10 0.217814E+10 0.118422E+10 0.00 0.00
November 0.459070E+10 0.322025E+10 0.350061E+10 0.232294E+10 0.117767E+10 0.00 0.00
December 0.433637E+10 0.396454E+10 0.366734E+10 0.258000E+10 0.108734E+10 0.00 0.00
               
Annual Sum or Average 0.475455E+11 0.272078E+11 0.324739E+11 0.158159E+11 0.166580E+11 0.00 0.00
Minimum of Months 0.300809E+10 0.482981E+09 0.169086E+10 94089014.43 0.103398E+10 0.00 0.00
Maximum of Months 0.496404E+10 0.452814E+10 0.372045E+10 0.259389E+10 0.171500E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.579779E+09 0.503287E+09 0.478854E+09 0.333856E+09 0.144999E+09 0.00 0.00
February 0.526707E+09 0.394652E+09 0.403680E+09 0.270598E+09 0.133082E+09 0.00 0.00
March 0.582014E+09 0.305118E+09 0.401943E+09 0.209469E+09 0.192474E+09 0.00 0.00
April 0.450477E+09 0.255380E+09 0.291317E+09 94830083.72 0.196487E+09 0.00 0.00
May 0.373193E+09 0.185651E+09 0.243218E+09 28268572.45 0.214950E+09 0.00 0.00
June 0.360289E+09 0.131082E+09 0.217627E+09 12110074.42 0.205517E+09 0.00 0.00
July 0.392323E+09 0.101644E+09 0.227350E+09 16952538.31 0.210398E+09 0.00 0.00
August 0.483481E+09 95077850.60 0.271440E+09 50705972.89 0.220734E+09 0.00 0.00
September 0.470706E+09 0.167393E+09 0.288888E+09 0.107451E+09 0.181437E+09 0.00 0.00
October 0.656566E+09 0.302812E+09 0.432765E+09 0.280346E+09 0.152419E+09 0.00 0.00
November 0.630851E+09 0.360290E+09 0.450558E+09 0.298983E+09 0.151575E+09 0.00 0.00
December 0.614915E+09 0.422771E+09 0.472018E+09 0.332068E+09 0.139950E+09 0.00 0.00
               
Annual Sum or Average 0.612130E+10 0.322516E+10 0.417966E+10 0.203564E+10 0.214402E+10 0.00 0.00
Minimum of Months 0.360289E+09 95077850.60 0.217627E+09 12110074.42 0.133082E+09 0.00 0.00
Maximum of Months 0.656566E+09 0.503287E+09 0.478854E+09 0.333856E+09 0.220734E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 3.96 1.39 -3.0 4.56 -7.8 48.74 150.20 0.00
February 7.94 4.18 -1.3 5.19 -4.0 51.84 169.20 0.00
March 13.76 8.97 3.80 4.89 2.25 76.95 193.22 0.00
April 17.21 12.54 8.82 3.95 6.45 95.37 211.82 0.00
May 20.84 16.44 13.69 3.50 11.46 117.34 200.00 0.00
June 24.80 19.35 16.45 3.85 15.08 121.81 213.08 0.00
July 26.06 21.68 19.85 3.24 17.64 119.92 194.46 0.00
August 26.55 22.42 20.72 3.39 18.21 115.12 179.15 0.00
September 22.53 18.74 16.82 3.06 13.44 83.74 156.58 0.02
October 16.03 13.02 10.77 4.05 5.85 53.01 190.38 0.00
November 11.94 8.22 4.17 4.16 0.30 52.20 150.38 0.00
December 7.70 4.64 0.26 4.69 -4.1 44.81 142.03 0.00
                 
Annual Sum or Average 16.65 12.68 9.31 4.04 6.29 81.91 179.25 0.00
Minimum of Months 3.96 1.39 -3.0 3.06 -7.8 44.81 142.03 0.00
Maximum of Months 26.55 22.42 20.72 5.19 18.21 121.81 213.08 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.10 31-JAN-14:00 12.97 6.70 5.70 12.22 200.50 90.50
February 25.00 26-FEB-14:00 12.75 1.70 4.10 8.15 91.50 816.00
March 27.80 30-MAR-13:00 17.87 12.20 5.70 16.30 231.50 710.50
April 28.90 17-APR-14:20 16.56 8.13 2.03 13.35 125.83 887.67
May 30.60 19-MAY-13:00 18.49 11.70 4.60 15.76 140.00 875.50
June 34.40 06-JUN-14:00 22.39 17.20 8.20 22.13 251.00 561.00
July 36.70 08-JUL-14:00 23.91 18.90 2.10 24.66 274.00 567.00
August 35.00 01-AUG-14:00 23.84 19.40 2.60 26.15 306.00 508.00
September 31.70 07-SEP-15:09 23.05 19.60 4.02 22.55 218.67 591.33
October 30.00 10-OCT-15:00 20.56 16.10 3.60 17.57 97.00 561.00
November 24.40 05-NOV-15:00 17.95 14.40 2.10 14.10 117.50 361.50
December 22.80 12-DEC-14:20 16.78 13.33 5.20 13.35 144.17 433.83
                 
Annual Sum or Average                
Minimum of Months 21.10   12.75 1.70 2.03 8.15 91.50 90.50
Maximum of Months 36.70   23.91 19.60 8.20 26.15 306.00 887.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.7 14-JAN-06:10 -7.8 -10.6 4.95 -24.7 0.00 0.00
February -12.8 12-FEB-06:00 -13.8 -18.3 7.20 -30.1 0.00 0.00
March 1.10 19-MAR-06:00 -1.5 -6.1 0.00 -16.2 17.00 290.50
April 0.00 06-APR-04:00 -1.1 -2.8 3.10 -16.5 0.00 0.00
May 7.80 11-MAY-05:00 5.45 2.80 4.10 -7.8 21.50 204.50
June 11.10 10-JUN-04:00 8.73 6.70 0.00 -2.5 0.00 0.00
July 17.20 28-JUL-22:00 16.88 16.70 4.10 14.28 0.00 0.00
August 18.30 25-AUG-05:00 17.20 16.70 3.60 5.13 0.00 0.00
September 11.70 29-SEP-03:00 11.07 10.60 2.60 -2.3 0.00 0.00
October 2.20 26-OCT-04:00 1.95 1.70 3.10 -13.4 0.00 0.00
November -3.3 22-NOV-05:00 -4.0 -5.6 5.20 -20.2 0.00 0.00
December -5.6 18-DEC-07:00 -7.3 -11.7 2.60 -22.7 17.00 320.50
                 
Annual Sum or Average                
Minimum of Months -12.8   -13.8 -18.3 0.00 -30.1 0.00 0.00
Maximum of Months 18.30   17.20 16.70 7.20 14.28 21.50 320.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.51 19-JAN-21:00 18.30 15.60 8.80 15.21 0.00 0.00
February 15.81 18-FEB-15:00 17.20 15.00 5.20 13.91 73.00 1.00
March 18.16 30-MAR-12:30 25.85 13.85 5.45 15.39 323.00 600.00
April 20.01 04-APR-13:00 25.00 17.80 9.30 18.64 307.00 197.50
May 22.34 30-MAY-17:00 27.80 20.00 4.10 21.96 97.50 79.50
June 24.32 23-JUN-11:39 31.13 21.87 4.83 22.98 338.17 565.17
July 25.06 07-JUL-11:00 33.30 22.20 3.60 20.75 116.50 900.00
August 25.13 19-AUG-16:00 30.00 23.30 3.10 23.66 197.00 136.50
September 24.10 09-SEP-10:00 30.60 21.70 2.60 21.27 236.00 482.00
October 23.20 18-OCT-15:00 25.60 22.20 5.70 23.82 159.00 2.00
November 18.88 19-NOV-14:00 24.40 16.10 8.20 13.91 143.00 384.50
December 17.57 13-DEC-10:00 19.40 16.70 4.60 14.47 227.50 77.00
                 
Annual Sum or Average                
Minimum of Months 15.81   17.20 13.85 2.60 13.91 0.00 0.00
Maximum of Months 25.13   33.30 23.30 9.30 23.82 338.17 900.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.60 19-JAN-17:00 17.20 16.13 6.70 14.10 0.00 0.00
February 15.00 18-FEB-16:19 17.20 15.81 5.53 13.91 50.33 1.00
March 16.10 31-MAR-10:00 21.70 18.06 13.90 18.64 268.00 8.00
April 17.80 04-APR-09:20 20.77 18.74 7.53 16.79 242.00 111.50
May 20.60 30-MAY-19:00 25.00 21.79 2.60 12.41 0.00 0.00
June 22.80 18-JUN-16:00 28.30 24.23 0.00 24.66 140.50 115.50
July 23.30 26-JUL-09:00 26.10 24.10 3.60 24.66 338.00 251.50
August 23.90 08-AUG-19:00 26.10 24.51 1.50 24.83 0.00 0.00
September 23.30 16-SEP-16:00 25.60 23.89 2.10 22.13 108.00 57.50
October 22.20 18-OCT-14:00 25.00 23.04 4.60 23.32 234.50 2.00
November 17.20 04-NOV-13:00 17.80 17.48 3.60 15.02 276.50 2.50
December 16.70 13-DEC-16:19 17.03 16.82 2.93 14.10 54.00 4.50
                 
Annual Sum or Average                
Minimum of Months 15.00   17.03 15.81 0.00 12.41 0.00 0.00
Maximum of Months 23.90   28.30 24.51 13.90 24.83 338.00 251.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 13.74 22.89 0.00
February 18.00 13.00 16.00 13.65 27.55 0.00
March 18.00 13.00 16.00 15.17 38.46 0.00
April 18.00 13.00 16.00 17.98 47.59 0.00
May 18.00 13.00 16.00 21.32 52.44 0.00
June 18.00 13.00 16.00 24.28 55.84 0.00
July 18.00 13.00 16.00 26.07 52.33 0.00
August 18.00 13.00 16.00 26.20 48.31 0.00
September 18.00 13.00 16.00 24.63 36.35 0.00
October 18.00 13.00 16.00 21.78 31.91 0.00
November 18.00 13.00 16.00 18.45 24.33 0.00
December 18.00 13.00 16.00 15.51 20.76 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.94 38.29 0.00
Minimum of Months 18.00 13.00 16.00 13.65 20.76 0.00
Maximum of Months 18.00 13.00 16.00 26.20 55.84 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.230930E+10 -0.218947E+10 0.00 0.00 744.00 0.00 -119829047.3 59.95 0.00 0.00
February 0.210326E+10 -0.199774E+10 0.00 0.00 672.00 0.00 -105516323.2 59.95 0.00 0.00
March 0.230447E+10 -0.219217E+10 0.00 0.00 744.00 0.00 -112306652.8 59.95 0.00 0.00
April 0.206058E+10 -0.195395E+10 0.00 0.00 720.00 0.00 -106633003.4 59.95 0.00 0.00
May 0.197108E+10 -0.186257E+10 0.00 0.00 744.00 0.00 -108510315.5 59.95 0.00 0.00
June 0.179079E+10 -0.168631E+10 0.00 0.00 720.00 0.00 -104481251.0 59.95 0.00 0.00
July 0.171453E+10 -0.160662E+10 0.00 0.00 744.00 0.00 -107913787.5 59.95 0.00 0.00
August 0.176035E+10 -0.165243E+10 0.00 0.00 744.00 0.00 -107924206.8 59.95 0.00 0.00
September 0.175005E+10 -0.164552E+10 0.00 0.00 720.00 0.00 -104536252.9 59.95 0.00 0.00
October 0.191957E+10 -0.180942E+10 0.00 0.00 744.00 0.00 -110146684.4 59.95 0.00 0.00
November 0.200401E+10 -0.189457E+10 0.00 0.00 720.00 0.00 -109436256.5 59.95 0.00 0.00
December 0.222436E+10 -0.210725E+10 0.00 0.00 744.00 0.00 -117107713.9 59.95 0.00 0.00
                     
Annual Sum or Average 0.239124E+11 -0.225980E+11 0.00 0.00 8760.00 0.00 -0.131434E+10 59.95 0.00 0.00
Minimum of Months 0.171453E+10 -0.219217E+10 0.00 0.00 672.00 0.00 -119829047.3 59.95 0.00 0.00
Maximum of Months 0.230930E+10 -0.160662E+10 0.00 0.00 744.00 0.00 -104481251.0 59.95 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 290.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 263.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 351.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 369.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 407.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 411.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 411.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 390.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 298.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 293.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 299.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 285.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 4071.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 263.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 411.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.281776E+09 29210.61 14-JAN-05:11 0.00 0.00 0.00 0.00 0.00
February 0.310707E+09 55191.94 12-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 1351365.25 8204.98 19-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 1315416.25 8673.83 06-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 23337408.09 20948.42 22-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 84295993.84 26442.33 18-DEC-05:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.702783E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.310707E+09 55191.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.325996E+09 84548.93 14-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.339021E+09 193914.98 12-FEB-07:11 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 248418.98 1242.09 06-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 20226361.74 53658.82 22-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 77407907.04 69211.17 18-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.762899E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.339021E+09 193914.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 80202397.85 14553.28 08-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.131257E+09 27716.05 12-FEB-07:11 0.00 0.00 0.00 0.00 0.00
March 394056.91 3115.14 19-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 392612.28 4580.48 06-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 4880632.12 9199.22 22-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 21193181.51 11736.08 18-DEC-05:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.238320E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.131257E+09 27716.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.104932E+09 13993.80 14-JAN-05:01 0.00 0.00 0.00 0.00 0.00
February 0.164378E+09 27566.68 12-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 435491.08 3373.56 19-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 762450.69 4975.58 06-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 8534541.74 9592.77 22-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 27436039.03 11903.41 18-DEC-05:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.306479E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.164378E+09 27566.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FRONT_ENTRY UNIT HEATER HEATING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.493296E+10 25889.10 02-JAN-17:51 0.00 0.00 0.00 0.00 0.00
February 0.286056E+10 23332.74 11-FEB-18:00 0.00 0.00 0.00 0.00 0.00
March 0.232753E+09 10954.77 22-MAR-11:40 0.00 0.00 0.00 0.00 0.00
April 35495.50 53.50 06-APR-07:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.460444E+09 20628.48 21-NOV-16:51 0.00 0.00 0.00 0.00 0.00
December 0.134339E+10 15160.28 17-DEC-18:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.983015E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.493296E+10 25889.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.110133E+11 62229.35 19-JAN-05:01 0.00 0.00 0.00 0.00 0.00
February 0.619475E+10 61475.14 11-FEB-05:01 0.00 0.00 0.00 0.00 0.00
March 0.873540E+09 52503.64 22-MAR-04:02 0.00 0.00 0.00 0.00 0.00
April 0.275096E+09 50688.58 27-APR-04:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 88735614.97 46189.64 26-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.125213E+10 56394.93 24-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.476356E+10 64246.24 24-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.244611E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.110133E+11 64246.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.270897E+11 178956.36 29-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.136189E+11 178668.23 10-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.787863E+09 171645.78 20-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.216084E+09 124766.85 06-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.115456E+09 125135.51 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.214432E+10 175119.09 23-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.101114E+11 175667.69 11-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.540838E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.270897E+11 178956.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.305864E+10 31250.06 19-JAN-05:01 0.00 0.00 0.00 0.00 0.00
February 0.168262E+10 30871.32 11-FEB-05:01 0.00 0.00 0.00 0.00 0.00
March 0.278734E+09 26366.05 22-MAR-04:02 0.00 0.00 0.00 0.00 0.00
April 0.132923E+09 24072.96 07-APR-04:02 0.00 0.00 0.00 0.00 0.00
May 140012.34 216.21 11-MAY-06:00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 35577448.97 13412.39 26-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.335594E+09 23340.74 26-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.132291E+10 27377.14 23-DEC-05:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.684713E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.305864E+10 31250.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.443427E+10 31081.65 19-JAN-05:01 0.00 0.00 0.00 0.00 0.00
February 0.254743E+10 30704.95 11-FEB-05:01 0.00 0.00 0.00 0.00 0.00
March 0.555065E+09 26223.96 22-MAR-04:02 0.00 0.00 0.00 0.00 0.00
April 0.237799E+09 25317.39 27-APR-04:02 0.00 0.00 0.00 0.00 0.00
May 7283512.26 2822.59 11-MAY-05:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.104096E+09 23070.31 26-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.574513E+09 28167.54 24-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.201247E+10 32089.03 24-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.104729E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.443427E+10 32089.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.185463E+09 0.167694E+09 4222.86 20-JAN-15:30 3676.06 0.00
February 0.00 0.00 0.132898E+10 0.129615E+10 9657.81 28-FEB-15:30 9657.81 0.00
March 0.00 0.00 0.509517E+10 0.474604E+10 16713.07 30-MAR-14:20 15322.64 0.00
April 0.00 0.00 0.104380E+11 0.965110E+10 18089.63 23-APR-18:25 15316.58 0.00
May 0.00 0.00 0.195048E+11 0.168682E+11 39266.01 29-MAY-18:08 34406.14 0.00
June 0.00 0.00 0.300681E+11 0.250542E+11 54442.93 25-JUN-18:08 44682.18 0.00
July 0.00 0.00 0.356181E+11 0.282166E+11 55148.03 23-JUL-18:08 43304.34 0.00
August 0.00 0.00 0.377655E+11 0.292884E+11 56225.43 20-AUG-18:10 40854.20 0.00
September 0.00 0.00 0.231751E+11 0.187651E+11 50908.40 07-SEP-20:10 39327.83 0.00
October 0.00 0.00 0.999726E+10 0.858217E+10 27083.30 18-OCT-21:00 18746.42 0.00
November 0.00 0.00 0.362029E+10 0.326799E+10 12710.82 05-NOV-15:30 10592.98 0.00
December 0.00 0.00 0.638744E+09 0.533121E+09 8670.28 13-DEC-13:00 6706.63 0.00
                 
Annual Sum or Average 0.00 0.00 0.177436E+12 0.146437E+12       0.00
Minimum of Months 0.00 0.00 0.185463E+09 0.167694E+09 4222.86   3676.06 0.00
Maximum of Months 0.00 0.00 0.377655E+11 0.292884E+11 56225.43   44682.18 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.178227E+10 0.139083E+10 30947.94 31-JAN-15:10 27249.90 0.00
February 0.00 0.00 0.937139E+10 0.874239E+10 51297.22 28-FEB-15:10 51297.22 0.00
March 0.00 0.00 0.323694E+11 0.280370E+11 89890.27 30-MAR-14:10 76208.93 0.00
April 0.00 0.00 0.592654E+11 0.505319E+11 90545.99 19-APR-14:40 75757.61 0.00
May 0.00 0.00 0.977945E+11 0.759326E+11 204969.68 31-MAY-06:03 120037.92 0.00
June 0.00 0.00 0.134832E+12 0.997162E+11 208471.32 23-JUN-06:02 115248.42 0.00
July 0.00 0.00 0.155976E+12 0.106580E+12 212796.42 30-JUL-08:62 103678.33 0.00
August 0.00 0.00 0.165146E+12 0.110193E+12 213086.14 20-AUG-08:62 105631.26 0.00
September 0.00 0.00 0.108064E+12 0.760946E+11 212345.32 17-SEP-08:62 106601.62 0.00
October 0.00 0.00 0.521093E+11 0.403328E+11 210092.71 19-OCT-06:02 106664.24 0.00
November 0.00 0.00 0.210594E+11 0.175743E+11 66632.24 04-NOV-15:55 44449.36 0.00
December 0.00 0.00 0.509893E+10 0.394907E+10 51449.98 13-DEC-13:00 34508.48 0.00
                 
Annual Sum or Average 0.00 0.00 0.842868E+12 0.619075E+12       0.00
Minimum of Months 0.00 0.00 0.178227E+10 0.139083E+10 30947.94   27249.90 0.00
Maximum of Months 0.00 0.00 0.165146E+12 0.110193E+12 213086.14   120037.92 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.171251E+10 0.162921E+10 7857.99 31-JAN-12:55 7143.15 0.00
February 0.00 0.00 0.349051E+10 0.338018E+10 13329.50 21-FEB-14:40 13329.50 0.00
March 0.00 0.00 0.777568E+10 0.726619E+10 17476.04 30-MAR-20:10 15784.70 0.00
April 0.00 0.00 0.101740E+11 0.925640E+10 16242.91 16-APR-18:10 15904.81 0.00
May 0.00 0.00 0.150041E+11 0.125887E+11 23966.97 29-MAY-18:08 20420.11 0.00
June 0.00 0.00 0.209320E+11 0.167755E+11 27743.90 13-JUN-20:08 21851.77 0.00
July 0.00 0.00 0.248537E+11 0.188077E+11 28230.97 06-JUL-20:08 20612.27 0.00
August 0.00 0.00 0.278201E+11 0.207425E+11 28739.70 22-AUG-20:08 19538.98 0.00
September 0.00 0.00 0.192840E+11 0.152833E+11 28271.03 06-SEP-20:08 20774.02 0.00
October 0.00 0.00 0.120453E+11 0.105038E+11 24019.60 09-OCT-18:08 20088.18 0.00
November 0.00 0.00 0.704482E+10 0.655639E+10 13808.72 05-NOV-13:50 11432.42 0.00
December 0.00 0.00 0.363032E+10 0.341843E+10 13912.32 12-DEC-14:00 12075.79 0.00
                 
Annual Sum or Average 0.00 0.00 0.153767E+12 0.126208E+12       0.00
Minimum of Months 0.00 0.00 0.171251E+10 0.162921E+10 7857.99   7143.15 0.00
Maximum of Months 0.00 0.00 0.278201E+11 0.207425E+11 28739.70   21851.77 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.706669E+09 0.661486E+09 5687.80 31-JAN-12:55 5024.61 0.00
February 0.00 0.00 0.211611E+10 0.207320E+10 11164.35 21-FEB-14:40 11164.35 0.00
March 0.00 0.00 0.523538E+10 0.480524E+10 14693.11 30-MAR-14:10 13218.20 0.00
April 0.00 0.00 0.742464E+10 0.662429E+10 12946.55 16-APR-18:10 12569.12 0.00
May 0.00 0.00 0.116232E+11 0.947153E+10 20217.96 29-MAY-18:08 16920.43 0.00
June 0.00 0.00 0.172729E+11 0.134366E+11 27540.81 25-JUN-18:08 21223.27 0.00
July 0.00 0.00 0.209145E+11 0.153382E+11 27579.95 07-JUL-20:08 20876.37 0.00
August 0.00 0.00 0.236328E+11 0.170790E+11 28082.96 17-AUG-20:08 19832.59 0.00
September 0.00 0.00 0.156546E+11 0.120163E+11 25751.72 07-SEP-20:08 18393.85 0.00
October 0.00 0.00 0.908119E+10 0.772673E+10 20080.22 09-OCT-18:08 16488.76 0.00
November 0.00 0.00 0.471911E+10 0.432046E+10 11786.09 05-NOV-13:50 9396.44 0.00
December 0.00 0.00 0.198821E+10 0.184173E+10 11578.76 12-DEC-14:00 9745.73 0.00
                 
Annual Sum or Average 0.00 0.00 0.120369E+12 0.953947E+11       0.00
Minimum of Months 0.00 0.00 0.706669E+09 0.661486E+09 5687.80   5024.61 0.00
Maximum of Months 0.00 0.00 0.236328E+11 0.170790E+11 28082.96   21223.27 0.00



Table of Contents

Report: FanReportMonthly

For: FRONT_ENTRY UNIT HEATER FAN

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.178278E+10 0.22 1643.14 01-JAN-16:51 0.54
February 0.997197E+09 0.14 1643.14 01-FEB-08:70 0.54
March 0.152714E+09 0.02 1643.14 06-MAR-08:70 0.54
April 22675369.99 0.00 1643.14 06-APR-07:10 0.54
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:05 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 10548976.47 0.00 1643.14 13-OCT-07:07 0.54
November 0.270519E+09 0.03 1643.14 07-NOV-08:06 0.54
December 0.757942E+09 0.09 1643.14 01-DEC-04:55 0.54
           
Annual Sum or Average 0.399438E+10 0.04      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.178278E+10 0.22 1643.14   0.54



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.763852E+10 0.89 4549.83 01-JAN-09:00 1.37
February 0.688764E+10 0.89 4549.83 04-FEB-11:10 1.39
March 0.747519E+10 0.86 4549.83 03-MAR-08:18 1.38
April 0.715417E+10 0.84 4549.83 05-APR-17:07 1.38
May 0.747556E+10 0.89 4549.83 10-MAY-11:08 1.38
June 0.768317E+10 1.07 4549.83 14-JUN-07:40 1.36
July 0.807990E+10 1.14 4549.83 06-JUL-17:15 1.37
August 0.832402E+10 1.20 4549.83 17-AUG-06:40 1.36
September 0.746876E+10 1.00 4549.83 01-SEP-08:30 1.36
October 0.733394E+10 0.84 4549.83 03-OCT-17:00 1.37
November 0.710114E+10 0.84 4549.83 08-NOV-11:45 1.38
December 0.751156E+10 0.87 4549.83 01-DEC-21:00 1.38
           
Annual Sum or Average 0.901336E+11 0.94      
Minimum of Months 0.688764E+10 0.84 4549.83   1.36
Maximum of Months 0.832402E+10 1.20 4549.83   1.39



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.219051E+11 0.81 13673.59 17-JAN-13:50 1.36
February 0.199153E+11 0.82 13673.59 01-FEB-10:20 1.36
March 0.222989E+11 0.83 13673.59 01-MAR-14:50 1.35
April 0.214128E+11 0.82 13673.59 01-APR-10:00 1.36
May 0.221020E+11 0.81 13673.59 01-MAY-10:40 1.35
June 0.215605E+11 0.82 13673.59 01-JUN-06:05 1.34
July 0.219543E+11 0.81 13673.59 01-JUL-11:30 1.34
August 0.222989E+11 0.82 13673.59 01-AUG-05:20 1.34
September 0.214128E+11 0.81 13673.59 01-SEP-06:30 1.34
October 0.219051E+11 0.81 13673.59 01-OCT-08:30 1.34
November 0.211175E+11 0.81 13673.59 01-NOV-11:07 1.35
December 0.219543E+11 0.81 13673.59 01-DEC-07:20 1.36
           
Annual Sum or Average 0.259838E+12 0.81      
Minimum of Months 0.199153E+11 0.81 13673.59   1.34
Maximum of Months 0.222989E+11 0.83 13673.59   1.36



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.378024E+10 0.90 2268.01 02-JAN-10:00 1.41
February 0.340597E+10 0.90 2268.01 01-FEB-10:50 1.42
March 0.373276E+10 0.89 2268.01 01-MAR-19:30 1.40
April 0.359874E+10 0.90 2268.01 01-APR-09:00 1.41
May 0.380291E+10 0.98 2268.01 01-MAY-08:00 1.40
June 0.396494E+10 1.17 2268.01 01-JUN-05:20 1.40
July 0.421514E+10 1.23 2268.01 01-JUL-06:02 1.40
August 0.440300E+10 1.27 2268.01 01-AUG-06:00 1.40
September 0.391558E+10 1.15 2268.01 03-SEP-11:30 1.40
October 0.374427E+10 0.95 2268.01 01-OCT-09:20 1.39
November 0.353524E+10 0.87 2268.01 02-NOV-07:02 1.40
December 0.371859E+10 0.89 2268.01 01-DEC-05:57 1.42
           
Annual Sum or Average 0.458174E+11 1.01      
Minimum of Months 0.340597E+10 0.87 2268.01   1.39
Maximum of Months 0.440300E+10 1.27 2268.01   1.42



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.365569E+10 0.91 2178.67 18-JAN-20:02 1.40
February 0.328827E+10 0.90 2178.67 01-FEB-06:05 1.42
March 0.358130E+10 0.89 2178.67 19-MAR-11:45 1.42
April 0.343493E+10 0.88 2178.67 01-APR-10:20 1.41
May 0.358357E+10 0.92 2178.67 01-MAY-08:70 1.39
June 0.367640E+10 1.10 2178.67 01-JUN-05:50 1.40
July 0.389381E+10 1.18 2178.67 12-JUL-12:20 1.40
August 0.406860E+10 1.25 2178.67 05-AUG-12:20 1.40
September 0.364109E+10 1.09 2178.67 08-SEP-17:00 1.40
October 0.355173E+10 0.91 2178.67 01-OCT-07:50 1.39
November 0.339556E+10 0.86 2178.67 04-NOV-06:30 1.40
December 0.358860E+10 0.89 2178.67 06-DEC-08:61 1.41
           
Annual Sum or Average 0.433595E+11 0.98      
Minimum of Months 0.328827E+10 0.86 2178.67   1.39
Maximum of Months 0.406860E+10 1.25 2178.67   1.42



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.128107E+11 0.00 0.00
February 0.00 0.00 0.00 0.102353E+11 0.00 0.00
March 0.00 0.00 0.00 0.930671E+10 0.00 0.00
April 0.00 0.00 0.00 0.103711E+11 0.00 0.00
May 0.00 0.00 0.00 0.131621E+11 0.00 0.00
June 0.00 0.00 0.00 0.164887E+11 0.00 0.00
July 0.00 0.00 0.00 0.184681E+11 0.00 0.00
August 0.00 0.00 0.00 0.192519E+11 0.00 0.00
September 0.00 0.00 0.00 0.141697E+11 0.00 0.00
October 0.00 0.00 0.00 0.102800E+11 0.00 0.00
November 0.00 0.00 0.00 0.873260E+10 0.00 0.00
December 0.00 0.00 0.00 0.965885E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.152936E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.873260E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.192519E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.349154E+11 0.00 0.00
February 0.00 0.00 0.00 0.290569E+11 0.00 0.00
March 0.00 0.00 0.00 0.321007E+11 0.00 0.00
April 0.00 0.00 0.00 0.386576E+11 0.00 0.00
May 0.00 0.00 0.00 0.495957E+11 0.00 0.00
June 0.00 0.00 0.00 0.599599E+11 0.00 0.00
July 0.00 0.00 0.00 0.663750E+11 0.00 0.00
August 0.00 0.00 0.00 0.688403E+11 0.00 0.00
September 0.00 0.00 0.00 0.515340E+11 0.00 0.00
October 0.00 0.00 0.00 0.367955E+11 0.00 0.00
November 0.00 0.00 0.00 0.283223E+11 0.00 0.00
December 0.00 0.00 0.00 0.275958E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.523749E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.275958E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.688403E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.577631E+10 0.00 0.00
February 0.00 0.00 0.00 0.520643E+10 0.00 0.00
March 0.00 0.00 0.00 0.583336E+10 0.00 0.00
April 0.00 0.00 0.00 0.628249E+10 0.00 0.00
May 0.00 0.00 0.00 0.765857E+10 0.00 0.00
June 0.00 0.00 0.00 0.948631E+10 0.00 0.00
July 0.00 0.00 0.00 0.108079E+11 0.00 0.00
August 0.00 0.00 0.00 0.117249E+11 0.00 0.00
September 0.00 0.00 0.00 0.884250E+10 0.00 0.00
October 0.00 0.00 0.00 0.676591E+10 0.00 0.00
November 0.00 0.00 0.00 0.548335E+10 0.00 0.00
December 0.00 0.00 0.00 0.524077E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.891088E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.520643E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.117249E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.597950E+10 0.00 0.00
February 0.00 0.00 0.00 0.512295E+10 0.00 0.00
March 0.00 0.00 0.00 0.516210E+10 0.00 0.00
April 0.00 0.00 0.00 0.550959E+10 0.00 0.00
May 0.00 0.00 0.00 0.666233E+10 0.00 0.00
June 0.00 0.00 0.00 0.829500E+10 0.00 0.00
July 0.00 0.00 0.00 0.948339E+10 0.00 0.00
August 0.00 0.00 0.00 0.103221E+11 0.00 0.00
September 0.00 0.00 0.00 0.770602E+10 0.00 0.00
October 0.00 0.00 0.00 0.590410E+10 0.00 0.00
November 0.00 0.00 0.00 0.488171E+10 0.00 0.00
December 0.00 0.00 0.00 0.495005E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.799789E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.488171E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.103221E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.763852E+10 0.185463E+09 0.112951E+11 0.00 0.00 0.00 0.00 0.00
February 0.688764E+10 0.132898E+10 0.650545E+10 0.00 0.00 0.00 0.00 0.00
March 0.747519E+10 0.509517E+10 0.874892E+09 0.00 0.00 0.00 0.00 0.00
April 0.715417E+10 0.104380E+11 0.276412E+09 0.00 0.00 0.00 0.00 0.00
May 0.747556E+10 0.195048E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.768317E+10 0.300681E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.807990E+10 0.356181E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.832402E+10 0.377655E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.746876E+10 0.231751E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.733394E+10 0.999726E+10 88735614.97 0.00 0.00 0.00 0.00 0.00
November 0.710114E+10 0.362029E+10 0.127547E+10 0.00 0.00 0.00 0.00 0.00
December 0.751156E+10 0.638744E+09 0.484786E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.901336E+11 0.177436E+12 0.251639E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.688764E+10 0.185463E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.832402E+10 0.377655E+11 0.112951E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.219051E+11 0.178227E+10 0.274157E+11 0.00 0.00 0.00 0.00 0.00
February 0.199153E+11 0.937139E+10 0.139580E+11 0.00 0.00 0.00 0.00 0.00
March 0.222989E+11 0.323694E+11 0.787863E+09 0.00 0.00 0.00 0.00 0.00
April 0.214128E+11 0.592654E+11 0.216332E+09 0.00 0.00 0.00 0.00 0.00
May 0.221020E+11 0.977945E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.215605E+11 0.134832E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.219543E+11 0.155976E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.222989E+11 0.165146E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.214128E+11 0.108064E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.219051E+11 0.521093E+11 0.115456E+09 0.00 0.00 0.00 0.00 0.00
November 0.211175E+11 0.210594E+11 0.216455E+10 0.00 0.00 0.00 0.00 0.00
December 0.219543E+11 0.509893E+10 0.101888E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.259838E+12 0.842868E+12 0.548467E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.199153E+11 0.178227E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.222989E+11 0.165146E+12 0.274157E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.378024E+10 0.171251E+10 0.313884E+10 0.00 0.00 0.00 0.00 0.00
February 0.340597E+10 0.349051E+10 0.181387E+10 0.00 0.00 0.00 0.00 0.00
March 0.373276E+10 0.777568E+10 0.279129E+09 0.00 0.00 0.00 0.00 0.00
April 0.359874E+10 0.101740E+11 0.133315E+09 0.00 0.00 0.00 0.00 0.00
May 0.380291E+10 0.150041E+11 140012.34 0.00 0.00 0.00 0.00 0.00
June 0.396494E+10 0.209320E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.421514E+10 0.248537E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.440300E+10 0.278201E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.391558E+10 0.192840E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.374427E+10 0.120453E+11 35577448.97 0.00 0.00 0.00 0.00 0.00
November 0.353524E+10 0.704482E+10 0.340475E+09 0.00 0.00 0.00 0.00 0.00
December 0.371859E+10 0.363032E+10 0.134410E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.458174E+11 0.153767E+12 0.708545E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.340597E+10 0.171251E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.440300E+10 0.278201E+11 0.313884E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.365569E+10 0.706669E+09 0.453921E+10 0.00 0.00 0.00 0.00 0.00
February 0.328827E+10 0.211611E+10 0.271181E+10 0.00 0.00 0.00 0.00 0.00
March 0.358130E+10 0.523538E+10 0.555500E+09 0.00 0.00 0.00 0.00 0.00
April 0.343493E+10 0.742464E+10 0.238562E+09 0.00 0.00 0.00 0.00 0.00
May 0.358357E+10 0.116232E+11 7283512.26 0.00 0.00 0.00 0.00 0.00
June 0.367640E+10 0.172729E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.389381E+10 0.209145E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.406860E+10 0.236328E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.364109E+10 0.156546E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.355173E+10 0.908119E+10 0.104096E+09 0.00 0.00 0.00 0.00 0.00
November 0.339556E+10 0.471911E+10 0.583048E+09 0.00 0.00 0.00 0.00 0.00
December 0.358860E+10 0.198821E+10 0.203990E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.433595E+11 0.120369E+12 0.107794E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.328827E+10 0.706669E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.406860E+10 0.236328E+11 0.453921E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.763852E+10 0.00 0.00 0.483330E+10 57099757.98 0.281776E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.688764E+10 0.00 0.00 0.263284E+10 0.404166E+09 0.310707E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.747519E+10 0.00 0.00 0.307326E+09 0.152284E+10 1351365.25 0.00 0.00 0.00 0.00 0.00 0.00
April 0.715417E+10 0.00 0.00 0.110540E+09 0.310509E+10 1315416.25 0.00 0.00 0.00 0.00 0.00 0.00
May 0.747556E+10 0.00 0.00 0.00 0.568656E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.768317E+10 0.00 0.00 0.00 0.880558E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.807990E+10 0.00 0.00 0.00 0.103882E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.832402E+10 0.00 0.00 0.00 0.109279E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.746876E+10 0.00 0.00 0.00 0.670093E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.733394E+10 0.00 0.00 32473795.23 0.291363E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.710114E+10 0.00 0.00 0.530819E+09 0.107731E+10 23337408.09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.751156E+10 0.00 0.00 0.187136E+10 0.191634E+09 84295993.84 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.901336E+11 0.00 0.00 0.103187E+11 0.517809E+11 0.702783E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.688764E+10 0.00 0.00 0.00 57099757.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.832402E+10 0.00 0.00 0.483330E+10 0.109279E+11 0.310707E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.219051E+11 0.00 0.00 0.121328E+11 0.551496E+09 0.325996E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.199153E+11 0.00 0.00 0.595548E+10 0.284711E+10 0.339021E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.222989E+11 0.00 0.00 0.279530E+09 0.952228E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.214128E+11 0.00 0.00 87745565.01 0.171567E+11 248418.98 0.00 0.00 0.00 0.00 0.00 0.00
May 0.221020E+11 0.00 0.00 0.00 0.274937E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.215605E+11 0.00 0.00 0.00 0.383994E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.219543E+11 0.00 0.00 0.00 0.444207E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.222989E+11 0.00 0.00 0.00 0.465414E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.214128E+11 0.00 0.00 0.00 0.301211E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.219051E+11 0.00 0.00 42444187.62 0.148479E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.211175E+11 0.00 0.00 0.953567E+09 0.623105E+10 20226361.74 0.00 0.00 0.00 0.00 0.00 0.00
December 0.219543E+11 0.00 0.00 0.402860E+10 0.153548E+10 77407907.04 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.259838E+12 0.00 0.00 0.234802E+11 0.239668E+12 0.762899E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.199153E+11 0.00 0.00 0.00 0.551496E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.222989E+11 0.00 0.00 0.121328E+11 0.465414E+11 0.339021E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.378024E+10 0.00 0.00 0.145028E+10 0.465585E+09 80202397.85 0.00 0.00 0.00 0.00 0.00 0.00
February 0.340597E+10 0.00 0.00 0.765151E+09 0.904056E+09 0.131257E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.373276E+10 0.00 0.00 0.101280E+09 0.199892E+10 394056.91 0.00 0.00 0.00 0.00 0.00 0.00
April 0.359874E+10 0.00 0.00 55193740.27 0.262817E+10 392612.28 0.00 0.00 0.00 0.00 0.00 0.00
May 0.380291E+10 0.00 0.00 48817.52 0.385561E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.396494E+10 0.00 0.00 0.00 0.552137E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.421514E+10 0.00 0.00 0.00 0.659272E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.440300E+10 0.00 0.00 0.00 0.732193E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.391558E+10 0.00 0.00 0.00 0.492692E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.374427E+10 0.00 0.00 13443998.22 0.300820E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.353524E+10 0.00 0.00 0.159812E+09 0.178342E+10 4880632.12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.371859E+10 0.00 0.00 0.549624E+09 0.951354E+09 21193181.51 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.458174E+11 0.00 0.00 0.309483E+10 0.399583E+11 0.238320E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.340597E+10 0.00 0.00 0.00 0.465585E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.440300E+10 0.00 0.00 0.145028E+10 0.732193E+10 0.131257E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.365569E+10 0.00 0.00 0.202231E+10 0.196559E+09 0.104932E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.328827E+10 0.00 0.00 0.111207E+10 0.558235E+09 0.164378E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.358130E+10 0.00 0.00 0.195763E+09 0.138460E+10 435491.08 0.00 0.00 0.00 0.00 0.00 0.00
April 0.343493E+10 0.00 0.00 92408167.38 0.198149E+10 762450.69 0.00 0.00 0.00 0.00 0.00 0.00
May 0.358357E+10 0.00 0.00 2487843.40 0.307627E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.367640E+10 0.00 0.00 0.00 0.461860E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.389381E+10 0.00 0.00 0.00 0.558958E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.406860E+10 0.00 0.00 0.00 0.625353E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.364109E+10 0.00 0.00 0.00 0.406494E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.355173E+10 0.00 0.00 36815533.75 0.231555E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.339556E+10 0.00 0.00 0.250732E+09 0.122689E+10 8534541.74 0.00 0.00 0.00 0.00 0.00 0.00
December 0.358860E+10 0.00 0.00 0.802233E+09 0.531784E+09 27436039.03 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.433595E+11 0.00 0.00 0.451482E+10 0.317980E+11 0.306479E+09 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.328827E+10 0.00 0.00 0.00 0.196559E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.406860E+10 0.00 0.00 0.202231E+10 0.625353E+10 0.164378E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BACK_SPACE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.927915E+09 0.00 0.00 21666.80 0.00 0.673623E+10 55353266.65 0.00 0.23
February 0.123995E+10 6254194.59 0.00 508842.35 2081510.26 0.410447E+10 0.222948E+09 0.00 0.23
March 0.184523E+10 0.166482E+09 0.00 2126886.33 526666.55 0.944229E+09 0.979260E+09 0.00 0.22
April 0.957223E+09 0.506813E+09 0.00 3119709.77 1067155.55 0.287541E+09 0.779248E+09 0.00 0.22
May 0.359917E+09 0.203536E+10 0.00 2811178.73 3909794.30 0.00 0.301228E+09 0.00 0.23
June 94345908.73 0.543497E+10 0.00 2079555.94 17178392.27 0.00 0.136584E+09 0.00 0.24
July 3232241.61 0.786948E+10 0.00 32166.74 23010974.21 0.00 4522182.42 0.00 0.24
August 559.12 0.886885E+10 0.00 39666.76 15289099.76 0.00 2249658.96 0.00 0.25
September 0.183905E+09 0.390299E+10 0.00 1856791.78 9290063.55 0.00 0.179915E+09 0.00 0.23
October 0.155144E+10 0.918258E+09 0.00 4432033.58 2319974.05 0.135575E+09 0.109754E+10 0.00 0.22
November 0.224642E+10 94011310.20 617768.01 1639763.76 20571336.11 0.110462E+10 0.701241E+09 17991.29 0.22
December 0.241495E+10 1350063.69 0.00 238487.77 3703304.11 0.339610E+10 89387032.83 0.00 0.22
                   
Annual Sum or Average 0.118245E+11 0.298048E+11 617768.01 18906750.31 98948270.72 0.167088E+11 0.454948E+10 17991.29 0.23
Minimum of Months 559.12 0.00 0.00 21666.80 0.00 0.00 2249658.96 0.00 0.22
Maximum of Months 0.241495E+10 0.886885E+10 617768.01 4432033.58 23010974.21 0.673623E+10 0.109754E+10 17991.29 0.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.470400E+11 0.00 0.00 3079455.46 0.00 0.158691E+11 0.276908E+10 0.00 0.42
February 0.322012E+11 0.00 0.00 18603678.75 0.00 0.802844E+10 0.858741E+10 0.00 0.42
March 0.161650E+11 0.747091E+09 0.00 51343207.59 0.00 0.129084E+09 0.197062E+11 0.00 0.43
April 0.758930E+10 0.287495E+10 0.00 48161312.34 0.00 40475874.47 0.114151E+11 0.00 0.43
May 0.244659E+10 0.140760E+11 0.00 27910196.74 26513607.21 0.00 0.381082E+10 0.00 0.43
June 0.806475E+09 0.374671E+11 0.00 14351856.92 0.400942E+09 0.00 0.136589E+10 0.00 0.44
July 71443869.63 0.526372E+11 0.00 1199176.78 0.779393E+09 0.00 54289465.98 0.00 0.43
August 37768520.46 0.585470E+11 0.00 937960.38 0.934319E+09 0.00 30841052.87 0.00 0.44
September 0.105651E+10 0.252930E+11 0.00 19010977.42 0.471259E+09 0.00 0.248055E+10 0.00 0.43
October 0.110196E+11 0.601445E+10 0.00 50538800.83 30041399.46 8490912.63 0.148587E+11 0.00 0.43
November 0.218875E+11 0.337113E+09 0.00 35491324.31 46697647.11 0.953987E+09 0.150945E+11 0.00 0.42
December 0.395638E+11 0.00 0.00 11167201.70 0.00 0.521866E+10 0.894780E+10 0.00 0.42
                   
Annual Sum or Average 0.179885E+12 0.197994E+12 0.00 0.281795E+09 0.268917E+10 0.302483E+11 0.891212E+11 0.00 0.43
Minimum of Months 37768520.46 0.00 0.00 937960.38 0.00 0.00 30841052.87 0.00 0.42
Maximum of Months 0.470400E+11 0.585470E+11 0.00 51343207.59 0.934319E+09 0.158691E+11 0.197062E+11 0.00 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: POINT_OF_SALE

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.255612E+10 0.00 0.00 4135894.86 0.00 0.211338E+10 0.206183E+10 0.00 0.44
February 0.182615E+10 0.00 0.00 6910179.40 0.00 0.129071E+10 0.174934E+10 0.00 0.44
March 0.838754E+09 99725454.56 0.00 10981297.32 0.00 0.341718E+09 0.215075E+10 0.00 0.43
April 0.516860E+09 0.318156E+09 0.00 7867380.55 0.00 0.161951E+09 0.108982E+10 0.00 0.43
May 0.197720E+09 0.150174E+10 0.00 3656427.88 5136.69 0.00 0.378820E+09 0.00 0.44
June 65200489.62 0.411932E+10 0.00 1946513.22 3257327.25 0.00 0.139320E+09 0.00 0.48
July 0.00 0.608596E+10 0.00 61530.58 3987789.72 0.00 6438542.15 0.00 0.49
August 0.00 0.708054E+10 0.00 30384.26 3222516.77 0.00 1330990.51 0.00 0.51
September 66203231.59 0.313065E+10 0.00 2969614.50 1352643.22 0.00 0.220033E+09 0.00 0.47
October 0.715187E+09 0.798856E+09 0.00 12199296.50 0.00 55241495.84 0.160830E+10 0.00 0.44
November 0.103051E+10 89550854.70 0.00 12294934.25 2058004.96 0.308974E+09 0.227170E+10 0.00 0.43
December 0.166157E+10 7010221.23 0.00 7732427.45 0.00 0.110854E+10 0.253829E+10 0.00 0.43
                   
Annual Sum or Average 0.947426E+10 0.232315E+11 0.00 70785880.77 13883418.61 0.538051E+10 0.142160E+11 0.00 0.45
Minimum of Months 0.00 0.00 0.00 30384.26 0.00 0.00 1330990.51 0.00 0.43
Maximum of Months 0.255612E+10 0.708054E+10 0.00 12294934.25 3987789.72 0.211338E+10 0.253829E+10 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONT_RETAIL

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.214531E+10 0.00 0.00 1607798.60 0.00 0.329329E+10 0.121361E+10 0.00 0.44
February 0.169435E+10 0.00 0.00 3768411.53 0.00 0.204129E+10 0.110022E+10 0.00 0.44
March 0.984786E+09 83258739.23 0.00 6458580.68 0.00 0.631992E+09 0.169424E+10 0.00 0.43
April 0.616327E+09 0.273122E+09 0.00 4611184.49 0.00 0.261631E+09 0.891854E+09 0.00 0.43
May 0.288950E+09 0.134173E+10 0.00 2301213.76 2047194.78 22097788.07 0.304007E+09 0.00 0.44
June 0.100232E+09 0.382638E+10 0.00 1232964.24 10922413.70 0.00 0.100879E+09 0.00 0.46
July 6225764.20 0.564734E+10 0.00 32302.17 11536602.96 0.00 6836896.68 0.00 0.47
August 25705.38 0.658877E+10 0.00 19399.17 10710166.12 0.00 3343279.85 0.00 0.49
September 0.144670E+09 0.285926E+10 0.00 1853287.74 6618996.13 0.00 0.183156E+09 0.00 0.46
October 0.952792E+09 0.708573E+09 0.00 7951302.61 1243047.80 0.145262E+09 0.128041E+10 0.00 0.43
November 0.135052E+10 62836327.17 0.00 7502062.42 2819555.97 0.520786E+09 0.170713E+10 0.00 0.43
December 0.207694E+10 2670538.69 0.00 3923652.04 0.00 0.160460E+10 0.155307E+10 0.00 0.43
                   
Annual Sum or Average 0.103611E+11 0.213939E+11 0.00 41262159.45 45897977.46 0.852095E+10 0.100388E+11 0.00 0.45
Minimum of Months 25705.38 0.00 0.00 19399.17 0.00 0.00 3343279.85 0.00 0.43
Maximum of Months 0.214531E+10 0.658877E+10 0.00 7951302.61 11536602.96 0.329329E+10 0.170713E+10 0.00 0.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONT_ENTRY

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:00

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.225040E+12 0.140939E+11 0.00 0.143160E+12 -0.890387E+14
February 0.244709E+12 0.104943E+11 0.00 0.109754E+12 -0.762196E+14
March 0.390722E+12 0.540604E+10 0.00 0.820700E+11 -0.778072E+14
April 0.466615E+12 0.269722E+10 0.00 0.477218E+11 -0.706594E+14
May 0.529268E+12 0.832772E+09 0.00 -489720280.8 -0.740579E+14
June 0.529542E+12 -0.168743E+10 0.00 -0.568325E+11 -0.777153E+14
July 0.508239E+12 -0.258651E+10 0.00 -0.959755E+11 -0.834824E+14
August 0.465645E+12 -0.335411E+10 0.00 -0.112582E+12 -0.848944E+14
September 0.348480E+12 -232556326.2 0.00 -0.348693E+11 -0.777506E+14
October 0.307801E+12 0.326698E+10 0.00 0.526558E+11 -0.797365E+14
November 0.207399E+12 0.589824E+10 0.00 0.898867E+11 -0.784967E+14
December 0.181819E+12 0.962285E+10 0.00 0.122343E+12 -0.837042E+14
           
Annual Sum or Average 0.440528E+13 0.444518E+11 0.00 0.346842E+12 -0.953563E+15
Minimum of Months 0.181819E+12 -0.335411E+10 0.00 -0.112582E+12 -0.890387E+14