Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2024-07-03 12:20:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 843.84 | 367.85 | 367.85 |
Net Site Energy | 768.97 | 335.21 | 335.21 |
Total Source Energy | 2672.43 | 1164.97 | 1164.97 |
Net Source Energy | 2435.32 | 1061.61 | 1061.61 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 3.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 310.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 29.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 117.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 20.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 843.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 3.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 310.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 167.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 29.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 117.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 20.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 3.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 310.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 167.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 29.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 117.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 20.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 197.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 367.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 86.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 197.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 367.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 78.153 | 9.26 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -3.29 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 74.867 | 8.87 |
Electricity Coming From Utility | 768.969 | 91.13 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 768.969 | 91.13 |
Total On-Site and Utility Electric Sources | 843.836 | 100.00 |
Total Electricity End Uses | 843.836 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 219.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3922.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 4.2421 | 46.45 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 8.6918 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 8.6918 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 8.6918 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 6.8308 | 6.19 | 0.0000 |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 7.9452 | 7.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 7.9452 | 7.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BACK_SPACE | 379.89 | Yes | Yes | 1.00 | BACK_SPACE | GENERAL | BACK_SPACE | 4.2421 | 46.45 | 8.0700 | |
CORE_RETAIL | 1600.48 | Yes | Yes | 1.00 | CORE_RETAIL | GENERAL | CORE_RETAIL | 8.6918 | 6.19 | 3.2300 | |
POINT_OF_SALE | 150.81 | Yes | Yes | 1.00 | POINT_OF_SALE | GENERAL | POINT_OF_SALE | 8.6918 | 6.19 | 21.5200 | |
FRONT_RETAIL | 150.81 | Yes | Yes | 1.00 | FRONT_RETAIL | GENERAL | FRONT_RETAIL | 8.6918 | 6.19 | 3.2300 | |
FRONT_ENTRY | 12.00 | Yes | Yes | 1.00 | FRONT_ENTRY | GENERAL | FRONT_ENTRY | 6.8308 | 6.19 | 0.0000 | |
Total | 2293.99 | 7.9452 | 3.62 | 5.2170 | |||||||
Conditioned Total | 2293.99 | 7.9452 | 3.62 | 5.2170 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2293.99 | 2293.99 | 0.00 | 0.00 | 7.9452 | 7.23 | 5.2170 |
Total | 2293.99 | 2293.99 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-15:00 | - | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45404.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11427.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9073.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1151.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 77797.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 45404.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 11427.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9073.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1151.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 10.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 983.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 531.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 93.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 615.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 372.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 66.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2672.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 428.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 162.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1164.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 428.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 162.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1164.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.47 |
CORE_RETAIL DIRECT AIR | 6.29 |
POINT_OF_SALE DIRECT AIR | 1.05 |
FRONT_RETAIL DIRECT AIR | 0.797672 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.841554 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER FAN | 0.841554 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | 24811.90 |
PSZ-AC:1_SUPPHEATCOIL | 29657.60 |
PSZ-AC:2_SUPPHEATCOIL | 163550.40 |
PSZ-AC:3_SUPPHEATCOIL | 23037.15 |
PSZ-AC:4_SUPPHEATCOIL | 19309.68 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.47 | 1.47 | 1.47 | 1.47 | 1.50 | 1.50 | 1.00 | 0.979925 | 1.50 |
PSZ-AC:2 | 6.29 | 6.29 | 6.29 | 6.29 | 6.59 | 6.59 | 1.00 | 0.955586 | 6.59 |
PSZ-AC:3 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC:4 | 0.797672 | 0.797672 | 0.797672 | 0.797672 | 0.824173 | 0.824173 | 1.00 | 0.967845 | 0.824173 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.50 | 0.231581 |
PSZ-AC:2_OA_CONTROLLER | 6.59 | |
PSZ-AC:3_OA_CONTROLLER | 1.05 | |
PSZ-AC:4_OA_CONTROLLER | 0.824173 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.50 | 1603.30 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 6.59 | 11095.82 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1162.73 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.824173 | 912.49 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.50 | 1.50 | 1.50 | 0.988908 | 30123.44 | 19870.59 | 40.00 | 29657.60 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 6.59 | 6.59 | 6.59 | 4.35 | 163550.40 | 109578.77 | 40.00 | 163550.40 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.693127 | 23328.52 | 15434.89 | 40.00 | 23037.15 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.824173 | 0.824173 | 0.824173 | 0.543954 | 19533.91 | 12937.49 | 40.00 | 19309.68 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC:1 HP COOLING COIL | 1.50 | 0.749173 | 0.998900 | 30123.44 | 15061.72 | 0.773720 | 0.773720 |
PSZ-AC:2 HP COOLING COIL | 6.59 | 3.29 | 4.39 | 163550.40 | 81775.20 | 0.701080 | 0.701080 |
PSZ-AC:3 HP COOLING COIL | 1.05 | 0.525096 | 0.700127 | 23328.52 | 11664.26 | 0.736980 | 0.736980 |
PSZ-AC:4 HP COOLING COIL | 0.824170 | 0.412087 | 0.549447 | 19533.91 | 9766.95 | 0.715780 | 0.715780 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | Design Size Speed 2 Gross Rated Heating Capacity [W] | Design Size Speed 1 Gross Rated Heating Capacity [W] | Design Size Resistive Defrost Heater Capacity | |
PSZ-AC:1 HEATING COIL | 1.50 | 0.749173 | 29657.60 | 14828.80 | 0.000000 |
PSZ-AC:2 HEATING COIL | 6.59 | 3.29 | 163550.29 | 81775.14 | 0.000000 |
PSZ-AC:3 HEATING COIL | 1.05 | 0.525096 | 23037.15 | 11518.57 | 0.000000 |
PSZ-AC:4 HEATING COIL | 0.824173 | 0.412087 | 19309.68 | 9654.84 | 0.000000 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 8.2 | 46.452 | 2.153E-002 | 4.242 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 12.312 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 8.692 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 11.922 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 8.692 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 30.212 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 8.692 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 11.922 | No |
5 | FRONT_ENTRY | 12.00 | 1.9 | 6.192 | 0.162 | 6.831 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.831 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 8.2 | 8.2 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.9 | 0.162 | 6.192 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | LTG_SCH_BACK | BACK_SPACE | 379.89 | 8.2 | 1611.543 | 4.242 | 197.055 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1611.543 |
2 | CORE_RETAIL_LIGHTS | LTG_SCH_CORE | CORE_RETAIL | 1600.48 | 258.4 | 13911.148 | 8.692 | 53.829 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13911.148 |
3 | POINT_OF_SALE_LIGHTS | LTG_SCH_SALE | POINT_OF_SALE | 150.81 | 24.4 | 1310.817 | 8.692 | 53.829 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1310.817 |
4 | FRONT_RETAIL_LIGHTS | LTG_SCH_FRONT | FRONT_RETAIL | 150.81 | 24.4 | 1310.817 | 8.692 | 53.829 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1310.817 |
5 | FRONT_ENTRY_LIGHTS | LTG_SCH_ENTRY | FRONT_ENTRY | 12.00 | 1.9 | 81.969 | 6.831 | 42.296 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 81.969 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 8.2 | 3065.712 | 8.070 | 374.868 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.145 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7063 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | 0.13978774E-14 | 0.42164564E-16 | -0.13958057E-09 | -0.65958802E-17 |
25 | 8 | 0.20446671E-07 | 0.15230601E-12 | 0.36262477E-03 | -0.23248569E-09 |
26 | 7 | -0.11788397E-01 | 0.80341688E-08 | -0.22433167E-01 | 0.13403836E-03 |
27 | 6 | 0.39303643 | 0.28173995E-05 | 0.46159007 | -0.46026110E-02 |
28 | 5 | -5.0703848 | 0.10592308E-03 | -4.3605482 | 0.61693694E-01 |
29 | 4 | 32.471215 | 0.87187145E-03 | 21.124720 | -0.41506426 |
30 | 3 | -110.09494 | 0.19107012E-02 | -54.999982 | 1.4988508 |
31 | 2 | 196.00982 | 0.10800696E-02 | 77.302744 | -2.8829103 |
32 | 1 | -170.75027 | 0.11582670E-03 | -55.088792 | 2.7383272 |
33 | 0 | 57.057407 | 0.66266081E-06 | 15.586427 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.248_SHGC_0.21 | 36 | 1 | VerySmooth | 1.408 | 1.408 | 1.000 | 0.210 | ||
2 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | 37 | 1 | VerySmooth | 3.695 | 3.695 | 1.000 | 0.302 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.57814E-002 | 0.12126 | 0.67915 | 0.67915 | 0.29000 | 0.15345 | 0.21878 | 0.00000 | 0.84000 | 0.84000 | 8.56546E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19440 | 0.51093 | 0.51093 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CORE_RETAIL | 16 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.1514 | 11722.8 | 1.001 | 0.9283 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.575 | 0.301 | 0.402 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 8.2 | 0.107 | 2.808E-004 | 1.274E-004 | 0.166 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 9.147E-002 | 5.715E-005 | 4.645E-005 | 3.373E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 4.865E-002 | 3.226E-004 | 1.428E-004 | 0.190 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 4.865E-002 | 3.226E-004 | 1.428E-004 | 0.190 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 1.9 | 6.250E-003 | 5.208E-004 | 1.718E-004 | 0.307 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.0638E-004 |
2 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 1.7992E-004 |
3 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 9.7387E-005 |
4 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 1.5404E-004 |
5 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 9.4824E-005 |
6 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 1.5361E-004 |
7 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.1773E-004 |
8 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.4462E-004 |
9 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 1.6263E-004 |
10 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 1.3170E-004 |
11 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 1.4026E-004 |
12 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 1.1796E-004 |
13 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 1.3582E-004 |
14 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 1.2259E-004 |
15 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.0997E-004 |
16 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 1.5868E-004 |
17 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 1.7092E-004 |
18 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 8.9037E-005 |
19 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 1.4756E-004 |
20 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 8.4926E-005 |
21 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 1.4978E-004 |
22 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 8.7779E-005 |
23 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.2827E-004 |
24 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 9.5366E-005 |
25 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.1456E-004 |
26 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 7.3333E-005 |
27 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.0479E-004 |
28 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 7.2523E-005 |
29 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.0901E-004 |
30 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 7.4629E-005 |
31 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.3124E-004 |
32 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 7.7678E-005 |
33 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 1.5020E-004 |
34 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 1.0125E-003 |
35 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 1.4615E-004 |
36 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 1.1710E-003 |
37 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 1.6125E-004 |
38 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 7.5598E-004 |
39 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 1.2762E-004 |
40 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 3.0923E-004 |
41 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 4.7751E-004 |
42 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 4.1866E-004 |
43 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 5.0829E-004 |
44 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 4.5914E-004 |
45 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 4.7081E-004 |
46 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 3.5744E-004 |
47 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 2.5682E-004 |
48 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 1.8288E-004 |
49 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 2.7105E-004 |
50 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 8.1549E-005 |
51 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 2.8751E-004 |
52 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 8.1552E-005 |
53 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 2.4709E-004 |
54 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 8.2617E-005 |
55 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 1.4542E-004 |
56 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 7.8315E-005 |
57 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 1.0080E-003 |
58 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 1.3213E-004 |
59 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 1.1742E-003 |
60 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 1.3362E-004 |
61 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 7.1426E-004 |
62 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 1.2906E-004 |
63 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 2.8427E-004 |
64 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 9.9302E-005 |
65 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 1.5271E-003 |
66 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 8.2024E-004 |
67 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 1.5053E-003 |
68 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 8.2671E-004 |
69 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 2.0606E-003 |
70 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.0246E-003 |
71 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 1.9793E-003 |
72 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 7.2541E-004 |
73 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 2.2841E-004 |
74 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 4.9383E-003 |
75 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 2.0774E-004 |
76 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 5.5292E-003 |
77 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 2.7668E-004 |
78 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 5.2206E-003 |
79 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 2.7288E-004 |
80 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 3.7112E-003 |
81 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 3.7847E-003 |
82 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 1.5874E-004 |
83 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 4.2031E-003 |
84 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 1.5232E-004 |
85 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 4.0814E-003 |
86 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 1.7542E-004 |
87 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 2.7617E-003 |
88 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 1.4280E-004 |
89 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 4.3373E-004 |
90 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 8.4369E-005 |
91 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 4.2390E-004 |
92 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 8.3061E-005 |
93 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 5.3188E-004 |
94 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 8.7070E-005 |
95 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 3.8681E-004 |
96 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 8.3339E-005 |
97 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 6.5283E-004 |
98 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 3.7642E-004 |
99 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 5.4464E-004 |
100 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 3.2740E-004 |
101 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 7.4704E-004 |
102 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 4.7202E-004 |
103 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 1.5875E-003 |
104 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 6.3139E-004 |
105 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 1.8407E-004 |
106 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 9.9469E-004 |
107 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 1.6121E-004 |
108 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 8.3744E-004 |
109 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 1.8789E-004 |
110 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.1842E-003 |
111 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 2.5328E-004 |
112 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 2.7783E-003 |
113 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 8.5021E-004 |
114 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 1.2593E-004 |
115 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 7.2180E-004 |
116 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 1.1696E-004 |
117 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.0584E-003 |
118 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 1.3550E-004 |
119 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 2.1403E-003 |
120 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 1.3791E-004 |
121 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 2.5049E-004 |
122 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 7.9937E-005 |
123 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 2.2165E-004 |
124 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 7.8342E-005 |
125 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 2.9963E-004 |
126 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 8.2167E-005 |
127 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 3.5117E-004 |
128 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 8.2891E-005 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 17497.86526 | 20997.43832 | 1.22356 | 1.46827 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
2 | BACK_SPACE | Heating | 19373.19094 | 23247.82912 | 0.81376 | 0.97651 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
3 | CORE_RETAIL | Cooling | 74914.92938 | 89897.91526 | 5.24471 | 6.29365 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 1600.48290 | 258.43418 | 1.89041 | 0.00000 |
4 | CORE_RETAIL | Heating | 49802.67851 | 59763.21421 | 2.05767 | 2.46920 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 1600.48290 | 258.43418 | 1.89041 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 12264.21721 | 14717.06065 | 0.87516 | 1.05019 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 150.81000 | 24.35169 | 0.17813 | 0.00000 |
6 | POINT_OF_SALE | Heating | 8547.69454 | 10257.23345 | 0.35988 | 0.43186 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 150.81000 | 24.35169 | 0.17813 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 9389.22736 | 11267.07283 | 0.66473 | 0.79767 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 150.81000 | 24.35169 | 0.17813 | 0.00000 |
8 | FRONT_RETAIL | Heating | 8540.83773 | 10249.00528 | 0.35959 | 0.43151 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 150.81000 | 24.35169 | 0.17813 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41732E-002 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
10 | FRONT_ENTRY | Heating | 20673.31665 | 24807.97998 | 0.70129 | 0.84155 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 21393.08 | 1.49835 | 1.49835 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 27127.23 | 0.97651 | 0.97651 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 105804.31 | 6.58617 | 6.58617 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 94409.24 | 2.46920 | 2.46920 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 15999.90 | 1.05019 | 1.05019 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 13490.06 | 0.43186 | 0.43186 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 13204.51 | 0.82417 | 0.82417 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 13481.88 | 0.43151 | 0.43151 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.46827 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.29365 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05019 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.79767 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.84155 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATER FAN | Design Size Maximum Flow Rate [m3/s] | 0.84155 |
7 | Coil:Heating:Electric | FRONT_ENTRY UNIT HEATER HEATING COIL | Design Size Nominal Capacity [W] | 24811.90049 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.46827 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46827 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.46827 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46827 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.49835 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.49835 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.97992 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.29365 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.29365 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.29365 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 6.29365 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.58617 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 6.58617 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.95559 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05019 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05019 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05019 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05019 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05019 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05019 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.79767 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.79767 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.79767 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.79767 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.82417 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.82417 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 0.96784 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.49835 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 6.58617 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.05019 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.82417 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.49835 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23158 |
46 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.49835 |
47 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1603.30049 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.49835 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.49835 |
50 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.49835 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98891 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.49835 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74917 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99890 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30123.44000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15061.72000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77372 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77372 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30123.44000 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19870.59474 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 29657.60408 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:DX:MultiSpeed | PSZ-AC:1 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.49835 |
65 | Coil:Heating:DX:MultiSpeed | PSZ-AC:1 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74917 |
66 | Coil:Heating:DX:MultiSpeed | PSZ-AC:1 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 29657.60408 |
67 | Coil:Heating:DX:MultiSpeed | PSZ-AC:1 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 14828.80204 |
68 | Coil:Heating:DX:MultiSpeed | PSZ-AC:1 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
69 | Coil:Heating:Electric | PSZ-AC:1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 29657.60408 |
70 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.58617 |
71 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.58617 |
72 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 11095.82464 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.58617 |
74 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.58617 |
75 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.58617 |
76 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.34688 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.58617 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.29309 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.39078 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 163550.40000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 81775.20000 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
84 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 163550.40000 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 109578.76661 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 163550.39793 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Coil:Heating:DX:MultiSpeed | PSZ-AC:2 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 6.58617 |
90 | Coil:Heating:DX:MultiSpeed | PSZ-AC:2 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.29309 |
91 | Coil:Heating:DX:MultiSpeed | PSZ-AC:2 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 163550.28557 |
92 | Coil:Heating:DX:MultiSpeed | PSZ-AC:2 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 81775.14279 |
93 | Coil:Heating:DX:MultiSpeed | PSZ-AC:2 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
94 | Coil:Heating:Electric | PSZ-AC:2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 163550.39793 |
95 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05019 |
96 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05019 |
97 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1162.72979 |
98 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05019 |
99 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05019 |
100 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05019 |
101 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69313 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05019 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52510 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70013 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23328.52000 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11664.26000 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73698 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73698 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23328.52000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 15434.88955 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 23037.14858 |
113 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
114 | Coil:Heating:DX:MultiSpeed | PSZ-AC:3 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.05019 |
115 | Coil:Heating:DX:MultiSpeed | PSZ-AC:3 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52510 |
116 | Coil:Heating:DX:MultiSpeed | PSZ-AC:3 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 23037.14858 |
117 | Coil:Heating:DX:MultiSpeed | PSZ-AC:3 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 11518.57429 |
118 | Coil:Heating:DX:MultiSpeed | PSZ-AC:3 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
119 | Coil:Heating:Electric | PSZ-AC:3_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 23037.14858 |
120 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.82417 |
121 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.82417 |
122 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 912.49061 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.82417 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.82417 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.82417 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.54395 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.82417 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.41209 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.54945 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19533.91000 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9766.95500 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71578 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71578 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19533.91000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 12937.48853 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 19309.68438 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
139 | Coil:Heating:DX:MultiSpeed | PSZ-AC:4 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 0.82417 |
140 | Coil:Heating:DX:MultiSpeed | PSZ-AC:4 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.41209 |
141 | Coil:Heating:DX:MultiSpeed | PSZ-AC:4 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 19309.68438 |
142 | Coil:Heating:DX:MultiSpeed | PSZ-AC:4 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 9654.84219 |
143 | Coil:Heating:DX:MultiSpeed | PSZ-AC:4 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
144 | Coil:Heating:Electric | PSZ-AC:4_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 19309.68438 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 HP COOLING COIL | 28945.8 | 11.85 | 11.85 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 HP COOLING COIL | 158354.5 | 11.09 | 11.09 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 HP COOLING COIL | 22501.7 | 12.06 | 12.06 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 HP COOLING COIL | 18884.3 | 12.19 | 12.19 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:MultiSpeed | PSZ-AC:1 HEATING COIL | 30852.2 | 17082.4 | 8.20 | 2 |
2 | Coil:Heating:DX:MultiSpeed | PSZ-AC:2 HEATING COIL | 168841.7 | 92906.2 | 7.42 | 2 |
3 | Coil:Heating:DX:MultiSpeed | PSZ-AC:3 HEATING COIL | 23877.2 | 13181.2 | 8.21 | 2 |
4 | Coil:Heating:DX:MultiSpeed | PSZ-AC:4 HEATING COIL | 19970.4 | 11005.1 | 8.22 | 2 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.145 | 0.977 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.145 | 0.977 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.145 | 0.977 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.390 | 2.390 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.145 | 0.977 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.145 | 0.977 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.145 | 0.977 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.145 | 0.977 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.145 | 0.977 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.145 | 0.977 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.145 | 0.977 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.248_SHGC_0.21 | N/A | 1.408 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 1.0026306380E-002 | 1.5484901415E-002 | Pass | Pass | 0.1098058791 | 0.8269624522 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 2.2930091660E-002 | 0.1048515934 | Pass | Pass | 5.7802671990E-002 | 0.2708863325 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.2345293130 | 0.3705266791 | Pass | Pass | 0.3296767147 | 1.4251856783 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1453388622 | 0.2338064061 | Pass | Pass | 5.0085112140 | 30.3168449244 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1612029502 | 0.3738421894 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3374.74 | 1.25 | 0.00 | -272.2 | 0.772590E+10 | 0.772590E+10 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.977 | 1.145 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.977 | 1.145 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.977 | 1.145 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.227 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.977 | 1.145 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.977 | 1.145 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.046 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.977 | 1.145 | 153.22 | 115.16 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.977 | 1.145 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.260 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.977 | 1.145 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.977 | 1.145 | 153.22 | 115.16 | 180.00 | 90.00 | S |
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.260 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.977 | 1.145 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.420 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 | |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 12.00 | 12.00 | 180.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
CORE_RETAIL_WALL_SOUTH_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 0.00 | 90.00 | N |
CORE_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
POINT_OF_SALE_WALL_EAST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
POINT_OF_SALE_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
POINT_OF_SALE_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
FRONT_RETAIL_WALL_WEST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_ENTRY_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_ENTRY_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 0.00 | 90.00 | N |
FRONT_ENTRY_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
BACK_SPACE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 759.78 | 0.00 | 90.00 | N | ||
CORE_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3200.97 | 0.00 | 90.00 | N | ||
POINT_OF_SALE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_ENTRY_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 24.00 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.248_SHGC_0.21 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 1.408 | 0.210 | 0.290 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.248_SHGC_0.21 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 1.408 | 0.210 | 0.290 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.248_SHGC_0.21 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 1.408 | 0.210 | 0.290 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 107.73 | 1.913 | 0.231 | 0.315 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 107.73 | 1.913 | 0.231 | 0.315 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | BACK_SPACE | GENERAL | 4.2421 | 379.89 | 1611.54 | LightsWired | LTG_SCH_BACK | 36.46 | 168.00 | 36.76 | 0.0000 | Y | 11.12 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | CORE_RETAIL | GENERAL | 8.6918 | 1600.48 | 13911.15 | LightsWired | LTG_SCH_CORE | 65.32 | 168.00 | 48.06 | 0.0000 | Y | 125.50 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | POINT_OF_SALE | GENERAL | 8.6918 | 150.81 | 1310.82 | LightsWired | LTG_SCH_SALE | 65.32 | 168.00 | 62.06 | 0.0000 | Y | 15.27 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | FRONT_RETAIL | GENERAL | 8.6918 | 150.81 | 1310.82 | LightsWired | LTG_SCH_FRONT | 65.32 | 168.00 | 62.06 | 0.0000 | Y | 15.27 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | FRONT_ENTRY | GENERAL | 6.8308 | 12.00 | 81.97 | LightsWired | LTG_SCH_ENTRY | 35.92 | 168.00 | 35.33 | 0.0000 | Y | 0.54 |
Interior Lighting Total | 7.9452 | 2293.99 | 18226.29 | 167.70 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 13911.15 | 3477.79 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 13911.15 | 3477.79 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 345.82 | AstronomicalClock | - | 41.73 | 41.73 | 2.71 | |
EXTERIOR_LIGHTS_B | 2284.89 | AstronomicalClock | - | 83.73 | 62.73 | 26.90 | |
Exterior Lighting Total | 2630.71 | 29.61 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30123.44 | 23307.11 | 6816.33 | 0.77 | 3.92 | |||
PSZ-AC:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 163550.40 | 114661.91 | 48888.49 | 0.70 | 3.48 | |||
PSZ-AC:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23328.52 | 17192.65 | 6135.87 | 0.74 | 3.92 | |||
PSZ-AC:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19533.91 | 13981.98 | 5551.93 | 0.72 | 3.92 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1 HP COOLING COIL | 28945.8 | 11.85 | 11.85 | ||||
PSZ-AC:2 HP COOLING COIL | 158354.5 | 11.09 | 11.09 | ||||
PSZ-AC:3 HP COOLING COIL | 22501.7 | 12.06 | 12.06 | ||||
PSZ-AC:4 HP COOLING COIL | 18884.3 | 12.19 | 12.19 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
PSZ-AC:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 30852.2 | 17082.4 | 8.20 | 2 |
PSZ-AC:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 168841.7 | 92906.2 | 7.42 | 2 |
PSZ-AC:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | 23877.2 | 13181.2 | 8.21 | 2 |
PSZ-AC:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | 19970.4 | 11005.1 | 8.22 | 2 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | Coil:Heating:Electric | 24811.90 | 1.00 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 29657.60 | 3.66 | |
PSZ-AC:1_SUPPHEATCOIL | Coil:Heating:Electric | 29657.60 | 1.00 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 163550.29 | 3.51 | |
PSZ-AC:2_SUPPHEATCOIL | Coil:Heating:Electric | 163550.40 | 1.00 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | 23037.15 | 3.66 | |
PSZ-AC:3_SUPPHEATCOIL | Coil:Heating:Electric | 23037.15 | 1.00 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | 19309.68 | 3.66 | |
PSZ-AC:4_SUPPHEATCOIL | Coil:Heating:Electric | 19309.68 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.84 | 78.19 | 92.91 | 1.00 | 4.35 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.50 | 1603.30 | 1070.05 | 1.00 | 1.36 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 6.59 | 11095.82 | 1684.71 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1162.73 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.82 | 912.49 | 1107.16 | 1.00 | 1.45 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.93 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 17497.87 | 20997.44 | 55.27 | 1.224 | 1.468 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00914 | 28.05 | 0.01653 | 0.232 | 0.00 |
CORE_RETAIL | 74914.93 | 89897.92 | 56.17 | 5.245 | 6.294 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.88 | 0.01054 | 28.05 | 0.01653 | 1.890 | 0.00 |
POINT_OF_SALE | 12264.22 | 14717.06 | 97.59 | 0.875 | 1.050 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00911 | 28.05 | 0.01653 | 0.178 | 0.00 |
FRONT_RETAIL | 9389.23 | 11267.07 | 74.71 | 0.665 | 0.798 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00973 | 28.05 | 0.01653 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 0.00 | 33.64 | 0.01659 | 33.90 | 0.01654 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 19373.19 | 23247.83 | 61.20 | 0.814 | 0.977 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00773 | 4.60 | 0.00526 | 0.232 | 0.00 |
CORE_RETAIL | 49802.68 | 59763.21 | 37.34 | 2.058 | 2.469 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00789 | 4.60 | 0.00526 | 1.890 | 0.00 |
POINT_OF_SALE | 8547.69 | 10257.23 | 68.01 | 0.360 | 0.432 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00774 | 4.60 | 0.00526 | 0.178 | 0.00 |
FRONT_RETAIL | 8540.84 | 10249.01 | 67.96 | 0.360 | 0.432 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00774 | 4.60 | 0.00526 | 0.178 | 0.00 |
FRONT_ENTRY | 20673.32 | 24807.98 | 2067.33 | 0.701 | 0.842 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 16.00 | 15.97 | 0.00614 | 4.60 | 0.00526 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.50 | 1.50 | 0.98 | 0.98 | 1.4983 | 1.4683 | 1.4983 | 0.9799 | 1.0000 |
PSZ-AC:2 | 6.59 | 6.59 | 2.47 | 2.47 | 6.5862 | 6.2937 | 6.5862 | 0.9556 | 1.0000 |
PSZ-AC:3 | 1.05 | 1.05 | 0.43 | 0.43 | 1.0502 | 1.0502 | 1.0502 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.82 | 0.82 | 0.43 | 0.43 | 0.8242 | 0.7977 | 0.8242 | 0.9678 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 24811.900 | 24811.900 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24811.90 | 24811.90 | 0.841554 | 15.97 | 11.01 | 0.00613647 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 15.97 | 0.00613647 | 54.4941 | 24807.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 30123.440 | 23307.108 | 1.498350 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 15061.72 | 11583.92 | 0.998900 | 25.48 | 18.27 | 0.01017050 | 12.80 | 12.09 | 0.00850000 | 28.55 | 0.01652632 | 23.72 | 23.1836 | 23.89 | 0.00900857 | 48.7374 | 17001.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 29657.604 | 29657.604 | 1.498345 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14828.80 | 14828.80 | 0.749173 | 18.37 | 13.22 | 0.00734929 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 30.9115 | 21.11 | 0.00773176 | 49.6285 | 19373.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC:1 | 29657.604 | 29657.604 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29657.60 | 29657.60 | 1.498345 | 18.37 | 13.22 | 0.00734929 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 15.4558 | 21.11 | 0.00773176 | 49.6285 | 19373.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 163550.400 | 114661.914 | 6.586170 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 81775.20 | 56210.63 | 4.390780 | 28.31 | 20.23 | 0.01154047 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 43.0540 | 23.89 | 0.00934170 | 50.5178 | 74708.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 163550.398 | 163550.398 | 6.586175 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 81775.14 | 81775.14 | 3.293087 | 16.08 | 12.07 | 0.00713084 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 57.4053 | 21.11 | 0.00788515 | 50.5992 | 49802.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC:2 | 163550.398 | 163550.398 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 163550.40 | 163550.40 | 6.586175 | 16.08 | 12.07 | 0.00713084 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 28.7027 | 21.11 | 0.00788515 | 50.5992 | 49802.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 23328.520 | 17192.653 | 1.050190 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 11664.26 | 8921.56 | 0.700127 | 26.51 | 18.74 | 0.01033661 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 25.4424 | 23.89 | 0.00904432 | 48.9327 | 11717.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 23037.149 | 23037.149 | 1.050192 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11518.57 | 11518.57 | 0.525096 | 18.12 | 13.09 | 0.00731794 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 33.9231 | 21.11 | 0.00773888 | 49.6738 | 8547.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC:3 | 23037.149 | 23037.149 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23037.15 | 23037.15 | 1.050192 | 18.12 | 13.09 | 0.00731794 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 16.9616 | 21.11 | 0.00773888 | 49.6738 | 8547.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 19533.910 | 13981.982 | 0.824170 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 9766.95 | 7132.49 | 0.549447 | 26.95 | 19.22 | 0.01077040 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 32.4197 | 23.89 | 0.00918059 | 49.6593 | 9351.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 19309.684 | 19309.684 | 0.824173 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9654.84 | 9654.84 | 0.412087 | 17.36 | 12.67 | 0.00720221 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 43.2261 | 21.11 | 0.00773851 | 49.6715 | 8540.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC:4 | 19309.684 | 19309.684 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19309.68 | 19309.68 | 0.824173 | 17.36 | 12.67 | 0.00720221 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 21.6131 | 21.11 | 0.00773851 | 49.6715 | 8540.84 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 24811.900 | 24811.900 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.841554 | 1.01252985 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 24811.90 | 24811.90 | 1.0000 | 1.01252985 | 0.841554 | 15.97 | 11.01 | 0.00613647 | 31575.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24811.90 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 15.97 | 0.00613647 | 15.97 | 0.00613647 | 54.4941 | 24807.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30123.440 | 23307.108 | 1.498350 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7464 | 1004.8586 | 1.2032 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.498345 | 1.80275967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | Sensible | 15061.72 | 11583.92 | 1.0000 | 1.20184341 | 0.998900 | 25.48 | 18.27 | 0.01017050 | 51519.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15061.72 | 28.55 | 0.01652632 | 23.72 | 0.23158056 | 23.1836 | 23.89 | 0.00900857 | 23.89 | 0.00900857 | 48.7374 | 17001.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 29657.604 | 29657.604 | 1.498345 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.498345 | 1.80275967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14828.80 | 14828.80 | 1.0000 | 0.90137984 | 0.749173 | 18.37 | 13.22 | 0.00734929 | 37087.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14828.80 | 4.60 | 0.00525715 | 4.60 | 0.23158056 | 30.9115 | 20.88 | 0.00773176 | 21.11 | 0.00773176 | 49.6285 | 19373.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29657.604 | 29657.604 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.498345 | 1.80275967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29657.60 | 29657.60 | 1.0000 | 1.80275967 | 1.498345 | 18.37 | 13.22 | 0.00734929 | 37087.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29657.60 | 4.60 | 0.00525715 | 4.60 | 0.23158056 | 15.4558 | 20.88 | 0.00773176 | 21.11 | 0.00773176 | 49.6285 | 19373.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 163550.400 | 114661.914 | 6.586170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2932 | 1004.8586 | 1.2032 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.586175 | 7.92426716 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | Sensible | 81775.20 | 56210.63 | 1.0000 | 5.28284115 | 4.390780 | 28.31 | 20.23 | 0.01154047 | 57918.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81775.20 | 33.90 | 0.01653638 | 25.13 | 1.89040796 | 43.0540 | 23.89 | 0.00934170 | 23.89 | 0.00934170 | 50.5178 | 74708.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 163550.398 | 163550.398 | 6.586175 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.586175 | 7.92426716 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 81775.14 | 81775.14 | 1.0000 | 3.96213358 | 3.293087 | 16.08 | 12.07 | 0.00713084 | 34207.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81775.14 | 4.60 | 0.00525715 | 4.60 | 1.89040796 | 57.4053 | 20.71 | 0.00788515 | 21.11 | 0.00788515 | 50.5992 | 49802.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 163550.398 | 163550.398 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.586175 | 7.92426716 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 163550.40 | 163550.40 | 1.0000 | 7.92426716 | 6.586175 | 16.08 | 12.07 | 0.00713084 | 34207.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 163550.40 | 4.60 | 0.00525715 | 4.60 | 1.89040796 | 28.7027 | 20.71 | 0.00788515 | 21.11 | 0.00788515 | 50.5992 | 49802.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23328.520 | 17192.653 | 1.050190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0553 | 1004.8586 | 1.2032 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.050192 | 1.26355684 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 11664.26 | 8921.56 | 1.0000 | 0.84236923 | 0.700127 | 26.51 | 18.74 | 0.01033661 | 53002.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11664.26 | 33.90 | 0.01653638 | 25.13 | 0.17812900 | 25.4424 | 23.89 | 0.00904432 | 23.89 | 0.00904432 | 48.9327 | 11717.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 23037.149 | 23037.149 | 1.050192 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.050192 | 1.26355684 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11518.57 | 11518.57 | 1.0000 | 0.63177842 | 0.525096 | 18.12 | 13.09 | 0.00731794 | 36751.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11518.57 | 4.60 | 0.00525715 | 4.60 | 0.17812900 | 33.9231 | 20.88 | 0.00773888 | 21.11 | 0.00773888 | 49.6738 | 8547.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23037.149 | 23037.149 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.050192 | 1.26355684 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23037.15 | 23037.15 | 1.0000 | 1.26355684 | 1.050192 | 18.12 | 13.09 | 0.00731794 | 36751.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23037.15 | 4.60 | 0.00525715 | 4.60 | 0.17812900 | 16.9616 | 20.88 | 0.00773888 | 21.11 | 0.00773888 | 49.6738 | 8547.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19533.910 | 13981.982 | 0.824170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8616 | 1004.8586 | 1.2032 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.824173 | 0.99161797 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 9766.95 | 7132.49 | 1.0000 | 0.66107604 | 0.549447 | 26.95 | 19.22 | 0.01077040 | 54555.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9766.95 | 33.90 | 0.01653638 | 25.13 | 0.17812900 | 32.4197 | 23.89 | 0.00918059 | 23.89 | 0.00918059 | 49.6593 | 9351.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 19309.684 | 19309.684 | 0.824173 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.824173 | 0.99161797 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9654.84 | 9654.84 | 1.0000 | 0.49580898 | 0.412087 | 17.36 | 12.67 | 0.00720221 | 35687.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9654.84 | 4.60 | 0.00525715 | 4.60 | 0.17812900 | 43.2261 | 20.88 | 0.00773851 | 21.11 | 0.00773851 | 49.6715 | 8540.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19309.684 | 19309.684 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.824173 | 0.99161797 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19309.68 | 19309.68 | 1.0000 | 0.99161797 | 0.824173 | 17.36 | 12.67 | 0.00720221 | 35687.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19309.68 | 4.60 | 0.00525715 | 4.60 | 0.17812900 | 21.6131 | 20.88 | 0.00773851 | 21.11 | 0.00773851 | 49.6715 | 8540.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialEnthalpy | 0.23 | 1.50 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 6.59 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 1.05 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 0.82 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_RETAIL | CORE_RETAIL_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
POINT_OF_SALE | POINT_OF_SALE_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
FRONT_RETAIL | FRONT_RETAIL_DCV | 0.003540 | 0.000610 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3140.00 | 1736.67 | 432.00 |
CORE_RETAIL | 3473.17 | 1608.17 | 629.50 |
POINT_OF_SALE | 3582.67 | 545.17 | 34.83 |
FRONT_RETAIL | 3432.00 | 833.50 | 120.33 |
FRONT_ENTRY | 4115.83 | 4604.50 | 3893.50 |
Facility | 4490.00 | 4775.17 | 3922.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 1.50 | 10.33 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 215.33 | 0.00 | 0.00 |
FRONT_RETAIL | 0.17 | 62.67 | 0.00 | 0.00 |
FRONT_ENTRY | 223.00 | 0.00 | 219.83 | 0.00 |
Facility | 224.50 | 234.50 | 219.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.07 | 8.18 | 2317.33 | 0.404 | 0.010 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.626 | 0.002 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.803 | 0.011 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.683 | 0.011 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 35.359 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.07 | 8.18 | 2317.33 | 0.353 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.387 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.386 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.386 | 0.000 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 4.07 | 8.18 | 2317.33 | 379.89 | 0.2316 | 0.232 |
CORE_RETAIL | PSZ-AC:2 | 128.48 | 258.43 | 9762.95 | 1600.48 | 1.8904 | 0.976 |
POINT_OF_SALE | PSZ-AC:3 | 12.11 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.092 |
FRONT_RETAIL | PSZ-AC:4 | 12.11 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.092 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 12.00 | 0.014 | ||
Total Facility | 157.72 | 317.25 | 13993.36 | 2293.99 | 2.4782 | 1.405 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BACK_SPACE | 4535353.47 | 0.00 | 4535353.47 | 350430.17 | 4885783.64 | 7303124.67 | 3838.24 | 4556.61 | 365.14 | 29.78 |
CORE_RETAIL | 29397142.64 | 0.00 | 29397142.64 | 300486.04 | 29697628.69 | 38574523.74 | 3846.50 | 3998.51 | 914.99 | 1.67 |
POINT_OF_SALE | 3662154.40 | 0.00 | 3662154.40 | 159816.07 | 3821970.47 | 3634792.93 | 3752.30 | 3676.28 | 1331.43 | 150.93 |
FRONT_RETAIL | 3074410.89 | 0.00 | 3074410.89 | 159816.07 | 3234226.96 | 3634792.93 | 3801.39 | 3955.94 | 1002.67 | 93.25 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 12420813.89 | 12420813.89 | 446965.66 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 40669061.39 | 0.00 | 40669061.39 | 13391362.25 | 54060423.65 | 53594199.92 | 8760.00 | 4679.94 | 1596.85 | 207.10 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BACK_SPACE | 0.2550 | 0.0000 | 0.2550 | 0.0061 | 0.2611 | 0.2316 | 0.00 | 4556.45 | 356.55 |
CORE_RETAIL | 1.6618 | 0.0000 | 1.6618 | 0.0052 | 1.6670 | 1.4170 | 0.00 | 3998.51 | 914.49 |
POINT_OF_SALE | 0.2013 | 0.0000 | 0.2013 | 0.0028 | 0.2041 | 0.1335 | 0.00 | 3674.41 | 1238.59 |
FRONT_RETAIL | 0.1711 | 0.0000 | 0.1711 | 0.0028 | 0.1738 | 0.1335 | 0.00 | 3955.29 | 957.71 |
FRONT_ENTRY | 0.0000 | 0.0000 | 0.0000 | 0.6964 | 0.6964 | 0.0142 | 4913.00 | 0.00 | 0.00 |
Total Facility | 2.2892 | 0.0000 | 2.2892 | 0.7132 | 3.0024 | 1.9298 | 4913.00 | 4677.26 | 1470.03 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC:1 | 6565419.33 | 0.00 | 6565419.33 | 7303124.67 | 3834.73 | 0.00 | 4925.27 | 29.78 |
PSZ-AC:2 | 42555675.19 | 0.00 | 42555675.19 | 38574523.74 | 3846.00 | 0.00 | 4914.00 | 1.67 |
PSZ-AC:3 | 5301376.90 | 0.00 | 5301376.90 | 3634792.93 | 3741.53 | 0.00 | 5018.47 | 150.93 |
PSZ-AC:4 | 4450558.55 | 0.00 | 4450558.55 | 3634792.93 | 3787.13 | 0.60 | 4972.26 | 92.91 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC:1 | 0.3691 | 0.0000 | 0.3691 | 0.2316 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:2 | 2.4057 | 0.0000 | 2.4057 | 1.4170 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:3 | 0.2914 | 0.0000 | 0.2914 | 0.1335 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:4 | 0.2477 | 0.0000 | 0.2477 | 0.1335 | 0.00 | 0.00 | 4913.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC:1 | 0.00 | 4692.60 | 250.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:2 | 0.00 | 478.54 | 487.78 | 0.00 | 0.00 | 0.00 | 3948.35 | 0.00 | 0.00 | 0.00 |
PSZ-AC:3 | 0.00 | 629.93 | 783.73 | 0.00 | 0.00 | 0.00 | 3650.27 | 0.00 | 0.00 | 0.00 |
PSZ-AC:4 | 0.00 | 504.82 | 592.27 | 0.00 | 0.00 | 0.00 | 3908.82 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC:1 | 0.0000 | 0.3561 | 0.6426 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:2 | 0.0000 | 4.7347 | 3.0727 | 0.0000 | 0.0000 | 0.0000 | 2.0422 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:3 | 0.0000 | 0.7528 | 0.4312 | 0.0000 | 0.0000 | 0.0000 | 0.1927 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:4 | 0.0000 | 0.5908 | 0.3472 | 0.0000 | 0.0000 | 0.0000 | 0.1922 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 512 |
Defaulted Fields | 478 |
Fields with Defaults | 1439 |
Autosized Fields | 93 |
Autosizable Fields | 234 |
Autocalculated Fields | 78 |
Autocalculatable Fields | 156 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 843.84 | 2225.65 | 01-JAN-07:30 | 77797.91 | 22-JUL-16:00 |
Electricity:Building | 362.00 | 2225.65 | 01-JAN-00:10 | 25585.72 | 02-JAN-17:50 |
Electricity:Zone:BACK_SPACE | 60.89 | 496.26 | 01-JAN-00:10 | 3515.42 | 02-JAN-09:10 |
Electricity:SpaceType:GENERAL | 362.00 | 2225.65 | 01-JAN-00:10 | 25585.72 | 02-JAN-17:50 |
InteriorLights:Electricity | 167.70 | 454.06 | 01-JAN-00:10 | 14844.83 | 02-JAN-17:50 |
InteriorLights:Electricity:Zone:BACK_SPACE | 11.12 | 42.45 | 01-JAN-00:10 | 764.01 | 02-JAN-09:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 167.70 | 454.06 | 01-JAN-00:10 | 14844.83 | 02-JAN-17:50 |
LightsWired:InteriorLights:Electricity | 167.70 | 454.06 | 01-JAN-00:10 | 14844.83 | 02-JAN-17:50 |
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE | 11.12 | 42.45 | 01-JAN-00:10 | 764.01 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 167.70 | 454.06 | 01-JAN-00:10 | 14844.83 | 02-JAN-17:50 |
Electricity:Zone:CORE_RETAIL | 209.43 | 1109.80 | 01-JAN-00:10 | 16455.36 | 02-JAN-17:50 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 125.50 | 344.55 | 01-JAN-00:10 | 11815.78 | 02-JAN-17:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL | 125.50 | 344.55 | 01-JAN-00:10 | 11815.78 | 02-JAN-17:50 |
Electricity:Zone:POINT_OF_SALE | 67.96 | 512.89 | 01-JAN-00:10 | 4026.09 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 15.27 | 32.47 | 01-JAN-00:10 | 1113.38 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE | 15.27 | 32.47 | 01-JAN-00:10 | 1113.38 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 23.18 | 104.57 | 01-JAN-00:10 | 1550.55 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 15.27 | 32.47 | 01-JAN-00:10 | 1113.38 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL | 15.27 | 32.47 | 01-JAN-00:10 | 1113.38 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 0.54 | 2.13 | 01-JAN-00:10 | 38.29 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 0.54 | 2.13 | 01-JAN-00:10 | 38.29 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY | 0.54 | 2.13 | 01-JAN-00:10 | 38.29 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
ElectricityProduced:Facility | 74.87 | -0.00 | 30-JAN-07:30 | 11909.46 | 10-APR-12:30 |
ElectricityProduced:Plant | 74.87 | -0.00 | 30-JAN-07:30 | 11909.46 | 10-APR-12:30 |
Photovoltaic:ElectricityProduced | 78.15 | 0.00 | 01-JAN-00:10 | 12401.05 | 10-APR-12:30 |
PowerConversion:ElectricityProduced | -3.29 | -491.59 | 10-APR-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 20.92 | 0.00 | 01-JAN-00:10 | 2000.02 | 23-JAN-13:00 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 768.97 | 562.38 | 05-MAR-08:00 | 71566.14 | 22-JUL-16:00 |
ElectricityPurchased:Plant | 768.97 | 562.38 | 05-MAR-08:00 | 71566.14 | 22-JUL-16:00 |
Cogeneration:ElectricityPurchased | 768.97 | 562.38 | 05-MAR-08:00 | 71566.14 | 22-JUL-16:00 |
General:Cogeneration:ElectricityPurchased | 768.97 | 562.38 | 05-MAR-08:00 | 71566.14 | 22-JUL-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 768.97 | 562.38 | 05-MAR-08:00 | 71566.14 | 22-JUL-16:00 |
ElectricityNet:Plant | 768.97 | 562.38 | 05-MAR-08:00 | 71566.14 | 22-JUL-16:00 |
Cogeneration:ElectricityNet | 768.97 | 562.38 | 05-MAR-08:00 | 71566.14 | 22-JUL-16:00 |
General:Cogeneration:ElectricityNet | 768.97 | 562.38 | 05-MAR-08:00 | 71566.14 | 22-JUL-16:00 |
Electricity:HVAC | 431.30 | 0.00 | 01-JAN-00:10 | 54477.57 | 22-JUL-16:00 |
Fans:Electricity | 117.53 | 0.00 | 01-JAN-00:10 | 9073.06 | 22-JUL-16:00 |
General:Fans:Electricity | 117.53 | 0.00 | 01-JAN-00:10 | 9073.06 | 22-JUL-16:00 |
Heating:Electricity | 3.18 | 0.00 | 01-JAN-00:10 | 22917.29 | 20-DEC-18:00 |
General:Heating:Electricity | 3.18 | 0.00 | 01-JAN-00:10 | 22917.29 | 20-DEC-18:00 |
Cooling:Electricity | 310.59 | 0.00 | 01-JAN-00:10 | 45404.50 | 22-JUL-16:00 |
General:Cooling:Electricity | 310.59 | 0.00 | 01-JAN-00:10 | 45404.50 | 22-JUL-16:00 |
ExteriorLights:Electricity | 29.61 | 0.00 | 01-JAN-07:30 | 2630.71 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 29.61 | 0.00 | 01-JAN-07:30 | 2630.71 | 01-JAN-06:10 |
WaterSystems:Electricity | 20.92 | 0.00 | 01-JAN-00:10 | 2000.02 | 23-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 20.92 | 0.00 | 01-JAN-00:10 | 2000.02 | 23-JAN-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1932.89 | 0.00 | 01-JAN-00:10 | 239969.59 | 07-OCT-13:00 |
EnergyTransfer:Building | 700.73 | 0.00 | 01-JAN-00:10 | 69736.30 | 07-JUL-14:50 |
EnergyTransfer:Zone:BACK_SPACE | 96.83 | 0.00 | 01-JAN-00:10 | 19481.13 | 06-FEB-05:10 |
Heating:EnergyTransfer | 7.88 | 0.00 | 01-JAN-00:10 | 27492.37 | 12-MAR-06:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 2.50 | 0.00 | 01-JAN-00:10 | 19481.13 | 06-FEB-05:10 |
General:Heating:EnergyTransfer | 7.88 | 0.00 | 01-JAN-00:10 | 27492.37 | 12-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:BACK_SPACE | 2.50 | 0.00 | 01-JAN-00:10 | 19481.13 | 06-FEB-05:10 |
Cooling:EnergyTransfer | 692.84 | 0.00 | 01-JAN-00:10 | 69736.30 | 07-JUL-14:50 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 94.33 | 0.00 | 01-JAN-00:10 | 11305.99 | 26-OCT-23:00 |
General:Cooling:EnergyTransfer | 692.84 | 0.00 | 01-JAN-00:10 | 69736.30 | 07-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:BACK_SPACE | 94.33 | 0.00 | 01-JAN-00:10 | 11305.99 | 26-OCT-23:00 |
EnergyTransfer:Zone:CORE_RETAIL | 420.79 | 0.00 | 01-JAN-00:10 | 52430.11 | 10-SEP-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 4.13 | 0.00 | 01-JAN-00:10 | 13664.83 | 21-DEC-07:40 |
General:Heating:EnergyTransfer:Zone:CORE_RETAIL | 4.13 | 0.00 | 01-JAN-00:10 | 13664.83 | 21-DEC-07:40 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 416.67 | 0.00 | 01-JAN-00:10 | 49237.88 | 10-SEP-08:10 |
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL | 416.67 | 0.00 | 01-JAN-00:10 | 49237.88 | 10-SEP-08:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 108.73 | 0.00 | 01-JAN-00:10 | 9840.97 | 07-OCT-14:30 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.12 | 0.00 | 01-JAN-00:10 | 4207.66 | 12-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.12 | 0.00 | 01-JAN-00:10 | 4207.66 | 12-MAR-06:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 108.61 | 0.00 | 01-JAN-00:10 | 9840.97 | 07-OCT-14:30 |
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 108.61 | 0.00 | 01-JAN-00:10 | 9840.97 | 07-OCT-14:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 73.47 | 0.00 | 01-JAN-00:10 | 7946.13 | 07-OCT-14:30 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.23 | 0.00 | 01-JAN-00:10 | 6826.61 | 12-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.23 | 0.00 | 01-JAN-00:10 | 6826.61 | 12-MAR-06:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 73.24 | 0.00 | 01-JAN-00:10 | 7946.13 | 07-OCT-14:30 |
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 73.24 | 0.00 | 01-JAN-00:10 | 7946.13 | 07-OCT-14:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.90 | 0.00 | 01-JAN-00:10 | 21280.38 | 20-DEC-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.90 | 0.00 | 01-JAN-00:10 | 21280.38 | 20-DEC-18:00 |
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.90 | 0.00 | 01-JAN-00:10 | 21280.38 | 20-DEC-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1232.17 | 0.00 | 01-JAN-00:10 | 171864.54 | 07-OCT-13:00 |
HeatingCoils:EnergyTransfer | 7.58 | 0.00 | 01-JAN-00:10 | 42627.92 | 05-FEB-09:20 |
CoolingCoils:EnergyTransfer | 1224.58 | 0.00 | 01-JAN-00:10 | 171864.54 | 07-OCT-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 2.500 | -94.325 | 0.000 | 0.000 | 5.018 | 11.121 | 49.772 | 0.000 | 0.000 | 0.512 | 27.071 | 0.000 | 0.000 | 0.000 | -1.669 | -0.001 |
CORE_RETAIL | 0.000 | 0.000 | 4.128 | -416.663 | 0.000 | 0.000 | 156.020 | 125.499 | 83.928 | 40.383 | 0.000 | 0.334 | 19.732 | 0.000 | -11.656 | 0.000 | -1.706 | -0.004 |
POINT_OF_SALE | 0.000 | 0.000 | 0.124 | -108.609 | 0.000 | 0.000 | 14.584 | 15.270 | 52.690 | 29.404 | 0.000 | 0.233 | 2.389 | 0.000 | -5.213 | 0.000 | -0.871 | -0.001 |
FRONT_RETAIL | 0.000 | 0.000 | 0.227 | -73.240 | 0.000 | 0.000 | 14.658 | 15.270 | 7.908 | 29.112 | 0.000 | 0.233 | 11.830 | 0.000 | -5.158 | 0.000 | -0.842 | -0.001 |
FRONT_ENTRY | 0.905 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.007 | 0.544 | 0.000 | 5.755 | 0.000 | 1.652 | 0.001 | 0.000 | -1.079 | 0.000 | -7.956 | -0.826 |
Total Facility | 0.905 | 0.000 | 6.979 | -692.837 | 0.000 | 0.000 | 191.287 | 167.704 | 194.299 | 104.654 | 0.000 | 2.964 | 61.022 | 0.000 | -23.106 | 0.000 | -13.044 | -0.833 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 26-OCT-20:19 | 0.00 | 0.00 | 0.00 | -27437.67 | 0.00 | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 26845.68 | 0.00 | -0.00 | 0.00 | -94.88 | 0.00 |
CORE_RETAIL | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | -193084.58 | 0.00 | 0.00 | 1635.97 | 344.55 | 2062.04 | 0.00 | 0.00 | 0.00 | 190203.39 | 0.00 | -1066.77 | 0.00 | -94.59 | 0.00 |
POINT_OF_SALE | 26-FEB-08:61 | 0.00 | 0.00 | 0.00 | -18992.29 | 0.00 | 0.00 | 0.00 | 32.47 | 480.42 | 319.95 | 0.00 | 0.00 | 18159.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 17-DEC-20:07 | 0.00 | 0.00 | 0.00 | -17659.95 | 0.00 | 0.00 | 0.00 | 32.47 | 72.11 | 0.00 | 0.00 | 0.00 | 18556.24 | 0.00 | -825.44 | 0.00 | -175.42 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | -197496.47 | 0.00 | 0.00 | 2047.26 | 493.85 | 4773.73 | 0.00 | 0.00 | 0.00 | 192737.18 | 0.00 | -2251.24 | 0.00 | -304.31 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 06-FEB-05:01 | 0.00 | 0.00 | 38466.13 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 | 605.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -237.92 | -38875.75 |
CORE_RETAIL | 21-DEC-07:40 | 0.00 | 0.00 | 27329.43 | 0.00 | 0.00 | 0.00 | 2124.61 | 2590.37 | 2062.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1522.18 | 0.00 | -100.60 | -32483.67 |
POINT_OF_SALE | 12-MAR-06:01 | 0.00 | 0.00 | 22292.40 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 480.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -729.84 | 0.00 | -152.72 | -21922.72 |
FRONT_RETAIL | 05-FEB-07:01 | 0.00 | 0.00 | 19885.98 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 72.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1193.88 | 0.00 | -490.23 | -18306.45 |
FRONT_ENTRY | 20-DEC-18:00 | 21281.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.13 | 38.29 | 0.00 | 0.00 | 0.00 | 0.00 | 755.52 | 0.00 | -153.22 | 0.00 | -22019.19 | 0.00 |
Total Facility | 05-FEB-07:01 | 0.00 | 0.00 | 78453.41 | 0.00 | 0.00 | 0.00 | 0.00 | 454.06 | 1771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4822.18 | 0.00 | -3053.36 | -72803.51 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.4683 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 1.4983 | 0.1546 | 1.0000 | Not calculated | 0.2316 | 0.1546 | ||
PSZ-AC:2 | 6.2937 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8904 | 6.5862 | 0.2870 | 1.0000 | Not calculated | 1.8904 | 0.2870 | ||
PSZ-AC:3 | 1.0502 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.0502 | 0.1696 | 1.0000 | Not calculated | 0.1781 | 0.1696 | ||
PSZ-AC:4 | 0.7977 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 0.8242 | 0.2161 | 1.0000 | Not calculated | 0.1781 | 0.2161 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.4683 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 1.4683 | 1.0000 | 1.0000 | Not calculated | 0.2316 | 0.1577 | ||
PSZ-AC:2 | 6.2937 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8904 | 6.2937 | 1.0000 | 1.0000 | Not calculated | 1.8904 | 0.3004 | ||
PSZ-AC:3 | 1.0502 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.0502 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1696 | ||
PSZ-AC:4 | 0.7977 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 0.7977 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.2233 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 8.1781 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.003540 | 258.4342 | 0.000610 | 1600.48 | 1.8904 | 1.0000 | 1.8904 | 1.000 | 1.8904 |
POINT_OF_SALE | PSZ-AC:3 | 0.003540 | 24.3517 | 0.000610 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.003540 | 24.3517 | 0.000610 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 8.18 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.003540 | 258.43 | 0.000610 | 1600.4829 | 1.8904 | 1.8904 | 1.8904 |
PSZ-AC:3 | 0.003540 | 24.35 | 0.000610 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.003540 | 24.35 | 0.000610 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4683 | 1.4683 | 1.4683 | No | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.2937 | 6.2937 | 6.2937 | No | 1.8904 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0502 | 1.0502 | 1.0502 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7977 | 0.7977 | 0.7977 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.4683 | 1.4983 | 1.4683 | 1.4683 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.2937 | 6.5862 | 6.2937 | 6.2937 | 1.8904 | 1.0000 |
PSZ-AC:3 | 1.0502 | 1.0502 | 1.0502 | 1.0502 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.7977 | 0.8242 | 0.7977 | 0.7977 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4683 | 1.4683 | 1.4683 | No | 0.2316 | 0.2372 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.2937 | 6.2937 | 6.2937 | No | 1.8904 | 0.7656 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0502 | 1.0502 | 1.0502 | No | 0.1781 | 0.4125 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7977 | 0.7977 | 0.7977 | No | 0.1781 | 0.4128 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.4683 | 1.4683 | 1.4683 | 1.4683 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.2937 | 6.2937 | 6.2937 | 6.2937 | 1.8904 | 1.0000 |
PSZ-AC:3 | 1.0502 | 1.0502 | 1.0502 | 1.0502 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.7977 | 0.7977 | 0.7977 | 0.7977 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 94.22 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 219.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 219.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 3.18 | 22917.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 310.59 | 45404.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 167.70 | 14844.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 29.61 | 2630.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.30 | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 117.53 | 9073.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 20.92 | 2000.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.30 | 843.84 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 194.30 | 843.84 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 78.15 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 73.11 |
Space Heating | 1.39 |
Space Cooling | 135.39 |
Fans (All) | 51.23 |
Service Water Heating | 9.12 |
Receptacle Equipment | 84.70 |
Miscellaneous (All) | 367.85 |
Subtotal | 367.85 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.87 |
Space Heating | 0.38 |
Space Cooling | 36.81 |
Fans (All) | 13.93 |
Service Water Heating | 2.48 |
Receptacle Equipment | 23.03 |
Miscellaneous | 3.51 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
LTG_SCH_ENTRY | 1873. | 8760. |
LTG_SCH_CORE | 3406. | 8760. |
LTG_SCH_BACK | 1901. | 8760. |
LTG_SCH_SALE | 3406. | 8760. |
LTG_SCH_FRONT | 3406. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4552. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY HEATING SP | January | 16.00 | 365 | 15.56 | 365 |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 4998.17 | 2719.33 | 1025.17 | 17.33 | 0.00 |
Min | 4998.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2719.33 | 1025.17 | 17.33 | 0.00 |
Average | 8007.63 | 543.87 | 205.03 | 3.47 | 0.00 |
Sum | 40038.17 | 2719.33 | 1025.17 | 17.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 16872.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 609599.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 877.33 | 442.50 | 590.83 | 9.33 | 0.00 |
Min | 877.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 609599.00 | 442.50 | 590.83 | 9.33 | 0.00 |
Average | 147869.67 | 88.50 | 118.17 | 1.87 | 0.00 |
Sum | 739348.33 | 442.50 | 590.83 | 9.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 8284.83 | 475.17 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 5779.50 | 2980.50 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8715.50 | 44.50 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 8601.83 | 158.17 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 3014.83 | 5090.50 | 643.67 | 11.00 | 0.00 |
Min | 3014.83 | 44.50 | 0.00 | 0.00 | 0.00 |
Max | 8715.50 | 5090.50 | 643.67 | 11.00 | 0.00 |
Average | 6879.30 | 1749.77 | 128.73 | 2.20 | 0.00 |
Sum | 34396.50 | 8748.83 | 643.67 | 11.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 15750.83 | 1121.17 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 503795.17 | 105803.83 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 55556.17 | 443.83 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 54116.83 | 1883.17 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 618.33 | 938.50 | 358.50 | 4.67 | 0.00 |
Min | 618.33 | 443.83 | 0.00 | 0.00 | 0.00 |
Max | 503795.17 | 105803.83 | 358.50 | 4.67 | 0.00 |
Average | 125967.47 | 22038.10 | 71.70 | 0.93 | 0.00 |
Sum | 629837.33 | 110190.50 | 358.50 | 4.67 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 8760.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 8760.00 |
Average | 0.00 | 0.00 | 0.00 | 1752.00 |
Sum | 0.00 | 0.00 | 0.00 | 8760.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 609599.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 609599.00 |
Average | 0.00 | 0.00 | 0.00 | 121919.80 |
Sum | 0.00 | 0.00 | 0.00 | 609599.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160428E+10 | 8661.21 | 19-JAN-23:05 | 21.00 | 21.00 | 0.247923E+09 | 326.80 | 30-JAN-15:09 | 22.33 | 19.53 |
February | 0.180056E+10 | 8671.63 | 28-FEB-22:40 | 18.47 | 18.18 | 0.238714E+09 | 326.81 | 25-FEB-12:39 | 18.47 | 18.18 |
March | 0.253632E+10 | 13686.67 | 30-MAR-21:25 | 18.80 | 18.47 | 0.282540E+09 | 326.81 | 24-MAR-14:00 | 18.80 | 18.47 |
April | 0.523384E+10 | 20077.03 | 23-APR-07:02 | 21.28 | 18.91 | 0.286221E+09 | 326.82 | 27-APR-14:09 | 29.08 | 22.47 |
May | 0.117603E+11 | 22281.93 | 07-MAY-18:53 | 26.10 | 24.12 | 0.297656E+09 | 326.82 | 13-MAY-10:30 | 29.45 | 23.08 |
June | 0.133339E+11 | 23253.44 | 13-JUN-20:10 | 30.03 | 21.76 | 0.293539E+09 | 326.82 | 14-JUN-14:09 | 34.72 | 24.33 |
July | 0.143390E+11 | 22683.66 | 07-JUL-21:23 | 28.85 | 25.02 | 0.291626E+09 | 326.82 | 10-JUL-14:00 | 31.70 | 25.48 |
August | 0.144848E+11 | 24463.45 | 03-AUG-21:23 | 24.45 | 19.23 | 0.304128E+09 | 326.82 | 04-AUG-14:20 | 31.80 | 24.90 |
September | 0.121086E+11 | 24875.72 | 11-SEP-02:63 | 25.32 | 23.70 | 0.287508E+09 | 326.82 | 09-SEP-14:39 | 25.32 | 23.70 |
October | 0.104348E+11 | 27437.68 | 26-OCT-20:19 | 19.67 | 11.98 | 0.290730E+09 | 326.82 | 07-OCT-10:50 | 19.67 | 11.98 |
November | 0.392595E+10 | 17975.00 | 02-NOV-22:03 | 24.07 | 22.97 | 0.274878E+09 | 326.82 | 03-NOV-14:00 | 27.70 | 23.72 |
December | 0.276339E+10 | 24976.80 | 17-DEC-08:61 | 19.83 | 15.88 | 0.261480E+09 | 326.81 | 01-DEC-15:50 | 19.83 | 15.88 |
Annual Sum or Average | 0.943258E+11 | 0.335694E+10 | ||||||||
Minimum of Months | 0.160428E+10 | 8661.21 | 18.47 | 11.98 | 0.238714E+09 | 326.80 | 18.47 | 11.98 | ||
Maximum of Months | 0.144848E+11 | 27437.68 | 30.03 | 25.02 | 0.304128E+09 | 326.82 | 34.72 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202405E+11 | 130110.88 | 02-JAN-07:03 | 15.83 | 15.23 | 0.863672E+10 | 10327.53 | 28-JAN-16:30 | 22.50 | 14.24 |
February | 0.200848E+11 | 128951.79 | 25-FEB-07:03 | 14.77 | 14.77 | 0.809974E+10 | 10327.48 | 08-FEB-15:30 | 14.77 | 14.77 |
March | 0.254623E+11 | 134404.44 | 01-MAR-07:03 | 15.30 | 14.01 | 0.935799E+10 | 10327.58 | 04-MAR-11:50 | 24.22 | 14.80 |
April | 0.331498E+11 | 127478.26 | 19-APR-06:03 | 16.88 | 15.73 | 0.908182E+10 | 10327.98 | 28-APR-14:00 | 33.30 | 23.06 |
May | 0.439893E+11 | 113443.77 | 12-MAY-06:02 | 23.40 | 20.68 | 0.940985E+10 | 10327.96 | 06-MAY-12:39 | 23.40 | 20.68 |
June | 0.460668E+11 | 116346.41 | 12-JUN-06:02 | 23.58 | 21.07 | 0.927963E+10 | 10327.93 | 13-JUN-14:50 | 33.90 | 21.48 |
July | 0.469490E+11 | 102457.49 | 08-JUL-06:02 | 24.87 | 23.59 | 0.921934E+10 | 10327.93 | 12-JUL-14:50 | 22.98 | 20.68 |
August | 0.473047E+11 | 110574.89 | 04-AUG-06:02 | 25.68 | 23.49 | 0.961442E+10 | 10327.92 | 30-AUG-14:09 | 32.28 | 22.78 |
September | 0.419986E+11 | 112613.99 | 23-SEP-06:02 | 22.28 | 20.36 | 0.908903E+10 | 10327.86 | 09-SEP-12:30 | 22.28 | 20.36 |
October | 0.404151E+11 | 193115.66 | 27-OCT-06:02 | 14.83 | 7.57 | 0.920139E+10 | 10327.91 | 19-OCT-14:50 | 14.83 | 7.57 |
November | 0.272906E+11 | 128869.07 | 05-NOV-08:62 | 18.17 | 15.31 | 0.882797E+10 | 10327.73 | 30-NOV-15:20 | 21.63 | 14.09 |
December | 0.237150E+11 | 137292.26 | 17-DEC-09:02 | 19.00 | 14.29 | 0.881345E+10 | 10327.85 | 16-DEC-13:50 | 19.00 | 14.29 |
Annual Sum or Average | 0.416666E+12 | 0.108631E+12 | ||||||||
Minimum of Months | 0.200848E+11 | 102457.49 | 14.77 | 7.57 | 0.809974E+10 | 10327.48 | 14.77 | 7.57 | ||
Maximum of Months | 0.473047E+11 | 193115.66 | 25.68 | 23.59 | 0.961442E+10 | 10327.98 | 33.90 | 23.06 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.635887E+10 | 14851.15 | 02-JAN-21:15 | 16.00 | 12.08 | 0.861547E+09 | 973.23 | 19-JAN-15:30 | 25.00 | 21.18 |
February | 0.601157E+10 | 18994.55 | 26-FEB-08:61 | 15.97 | 15.97 | 0.786473E+09 | 973.20 | 11-FEB-11:30 | 15.97 | 15.97 |
March | 0.617373E+10 | 15243.30 | 19-MAR-07:01 | 16.60 | 12.98 | 0.894839E+09 | 973.21 | 15-MAR-14:30 | 16.60 | 12.98 |
April | 0.723271E+10 | 15046.63 | 16-APR-19:02 | 16.42 | 12.73 | 0.855952E+09 | 973.22 | 28-APR-14:00 | 33.30 | 23.06 |
May | 0.992155E+10 | 13377.04 | 07-MAY-18:43 | 27.22 | 24.16 | 0.886335E+09 | 973.21 | 17-MAY-14:00 | 31.70 | 24.18 |
June | 0.102604E+11 | 13541.10 | 28-JUN-20:10 | 29.22 | 24.17 | 0.874072E+09 | 973.23 | 24-JUN-11:50 | 29.22 | 24.17 |
July | 0.109004E+11 | 16577.71 | 07-JUL-20:43 | 29.40 | 24.91 | 0.868377E+09 | 973.23 | 17-JUL-14:09 | 33.72 | 24.78 |
August | 0.118270E+11 | 18058.52 | 30-AUG-21:23 | 28.90 | 22.61 | 0.905599E+09 | 973.23 | 26-AUG-15:39 | 28.90 | 22.61 |
September | 0.111919E+11 | 18452.50 | 10-SEP-21:23 | 28.10 | 24.32 | 0.856117E+09 | 973.23 | 23-SEP-15:20 | 28.63 | 24.26 |
October | 0.120289E+11 | 18616.02 | 05-OCT-22:43 | 27.17 | 24.40 | 0.867023E+09 | 973.25 | 16-OCT-14:00 | 28.10 | 23.31 |
November | 0.909896E+10 | 17479.53 | 22-NOV-21:15 | 15.93 | 9.23 | 0.834170E+09 | 973.25 | 06-NOV-15:20 | 15.93 | 9.23 |
December | 0.760277E+10 | 16679.77 | 25-DEC-20:01 | 11.73 | 7.04 | 0.863234E+09 | 973.25 | 15-DEC-15:20 | 11.73 | 7.04 |
Annual Sum or Average | 0.108609E+12 | 0.103537E+11 | ||||||||
Minimum of Months | 0.601157E+10 | 13377.04 | 11.73 | 7.04 | 0.786473E+09 | 973.20 | 11.73 | 7.04 | ||
Maximum of Months | 0.120289E+11 | 18994.55 | 29.40 | 24.91 | 0.905599E+09 | 973.25 | 33.72 | 24.78 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380608E+10 | 10573.25 | 29-JAN-19:22 | 19.00 | 15.30 | 0.843589E+09 | 973.20 | 19-JAN-15:20 | 19.00 | 15.30 |
February | 0.362638E+10 | 10554.91 | 09-FEB-21:33 | 15.93 | 14.71 | 0.772041E+09 | 973.19 | 10-FEB-15:30 | 22.15 | 17.36 |
March | 0.355184E+10 | 11733.36 | 26-MAR-07:01 | 17.67 | 16.76 | 0.874887E+09 | 973.19 | 17-MAR-14:09 | 17.67 | 16.76 |
April | 0.434213E+10 | 11814.74 | 07-APR-20:33 | 15.50 | 12.59 | 0.854319E+09 | 973.18 | 05-APR-14:00 | 15.50 | 12.59 |
May | 0.667844E+10 | 11457.65 | 07-MAY-18:43 | 27.22 | 24.16 | 0.886321E+09 | 973.18 | 13-MAY-11:20 | 28.37 | 22.62 |
June | 0.707286E+10 | 10617.92 | 28-JUN-20:10 | 29.22 | 24.17 | 0.874063E+09 | 973.19 | 22-JUN-14:39 | 29.22 | 24.17 |
July | 0.775275E+10 | 13435.84 | 19-JUL-20:43 | 28.40 | 24.96 | 0.868365E+09 | 973.19 | 08-JUL-12:09 | 28.40 | 24.96 |
August | 0.856148E+10 | 14864.08 | 30-AUG-21:23 | 28.90 | 22.61 | 0.905589E+09 | 973.20 | 26-AUG-12:39 | 28.90 | 22.61 |
September | 0.802920E+10 | 15527.10 | 10-SEP-22:03 | 27.97 | 24.30 | 0.856105E+09 | 973.20 | 23-SEP-12:09 | 30.60 | 24.33 |
October | 0.880550E+10 | 15329.19 | 09-OCT-19:23 | 25.50 | 20.69 | 0.866773E+09 | 973.21 | 12-OCT-14:00 | 30.00 | 22.38 |
November | 0.613032E+10 | 16019.26 | 12-NOV-20:01 | 11.03 | 7.34 | 0.833481E+09 | 973.22 | 06-NOV-15:20 | 11.03 | 7.34 |
December | 0.488332E+10 | 17659.97 | 17-DEC-20:07 | 10.00 | 6.99 | 0.843880E+09 | 973.22 | 16-DEC-15:39 | 10.00 | 6.99 |
Annual Sum or Average | 0.732403E+11 | 0.102794E+11 | ||||||||
Minimum of Months | 0.355184E+10 | 10554.91 | 10.00 | 6.99 | 0.772041E+09 | 973.18 | 10.00 | 6.99 | ||
Maximum of Months | 0.880550E+10 | 17659.97 | 29.22 | 24.96 | 0.905589E+09 | 973.22 | 30.60 | 24.96 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 | 16.69 | 42487126.51 | 101.43 | 02-JAN-15:09 | 26.83 | 18.62 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 | 18.20 | 46728368.84 | 102.87 | 25-FEB-16:00 | 27.20 | 18.83 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 | 17.16 | 58137505.49 | 110.54 | 27-MAR-14:00 | 28.30 | 21.49 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 | 75656011.81 | 154.91 | 28-APR-14:00 | 33.30 | 23.06 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 | 19.11 | 0.108446E+09 | 155.61 | 18-MAY-14:00 | 33.30 | 23.27 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 22.93 | 21.40 | 0.112671E+09 | 171.16 | 14-JUN-14:09 | 34.72 | 24.33 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 | 23.10 | 0.110377E+09 | 180.91 | 22-JUL-15:00 | 36.10 | 27.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 | 23.55 | 0.114930E+09 | 170.46 | 03-AUG-14:00 | 35.00 | 24.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 | 24.22 | 97130664.08 | 174.89 | 09-SEP-15:00 | 35.60 | 26.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 22.17 | 20.64 | 93999064.93 | 162.81 | 05-OCT-14:00 | 34.00 | 24.05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21.63 | 21.01 | 64237155.47 | 125.99 | 01-NOV-14:09 | 29.80 | 24.92 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 | 52457479.18 | 127.10 | 13-DEC-15:09 | 29.83 | 21.67 |
Annual Sum or Average | 0.00 | 0.977258E+09 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 42487126.51 | 101.43 | 26.83 | 18.62 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.114930E+09 | 180.91 | 36.10 | 27.07 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.837232E+09 | 37490.50 | 10-JAN-05:01 | 1.33 |
February | 0.646742E+09 | 38466.13 | 06-FEB-05:01 | 3.03 |
March | 0.416615E+09 | 30180.26 | 14-MAR-04:03 | 8.65 |
April | 34562794.93 | 918.13 | 23-APR-07:04 | 21.28 |
May | 6942934.16 | 1169.78 | 26-MAY-05:05 | 25.00 |
June | 5469597.93 | 1242.41 | 15-JUN-05:05 | 25.50 |
July | 5089293.98 | 1248.56 | 06-JUL-05:05 | 25.10 |
August | 3917476.06 | 1230.47 | 02-AUG-05:05 | 26.00 |
September | 6655791.57 | 1229.65 | 04-SEP-07:05 | 26.83 |
October | 11406741.18 | 1178.18 | 12-OCT-05:05 | 22.00 |
November | 48611367.97 | 890.31 | 01-NOV-05:10 | 22.62 |
December | 0.476774E+09 | 37724.91 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.250002E+10 | |||
Minimum of Months | 3917476.06 | 890.31 | 0.17 | |
Maximum of Months | 0.837232E+09 | 38466.13 | 26.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.459506E+09 | 8328.73 | 10-JAN-07:10 | 3.17 |
February | 0.426961E+09 | 6870.35 | 06-FEB-07:10 | 3.90 |
March | 0.460272E+09 | 4412.97 | 12-MAR-07:11 | 7.33 |
April | 0.428494E+09 | 5157.32 | 28-APR-06:06 | 23.22 |
May | 0.276591E+09 | 10105.06 | 28-MAY-08:20 | 27.77 |
June | 0.213079E+09 | 10016.51 | 04-JUN-08:20 | 27.80 |
July | 0.196182E+09 | 10979.38 | 04-JUL-08:20 | 28.67 |
August | 0.176699E+09 | 10653.72 | 06-AUG-08:20 | 28.33 |
September | 0.251168E+09 | 15961.13 | 10-SEP-08:08 | 32.40 |
October | 0.304754E+09 | 8409.94 | 07-OCT-06:08 | 26.67 |
November | 0.445957E+09 | 6696.12 | 11-NOV-09:06 | 24.40 |
December | 0.488716E+09 | 27329.65 | 21-DEC-07:40 | 2.00 |
Annual Sum or Average | 0.412838E+10 | |||
Minimum of Months | 0.176699E+09 | 4412.97 | 2.00 | |
Maximum of Months | 0.488716E+09 | 27329.65 | 32.40 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 29164577.96 | 569.54 | 30-JAN-06:10 | 17.83 |
February | 25289003.24 | 20883.62 | 05-FEB-07:01 | -3.4 |
March | 34799523.17 | 22292.40 | 12-MAR-06:01 | 7.10 |
April | 7525119.78 | 817.13 | 27-APR-05:05 | 20.92 |
May | 1834347.16 | 846.85 | 22-MAY-05:05 | 26.10 |
June | 1057708.42 | 837.87 | 08-JUN-05:05 | 22.20 |
July | 803157.14 | 828.58 | 14-JUL-05:05 | 23.98 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 876448.96 | 823.45 | 16-SEP-05:05 | 23.80 |
October | 560158.67 | 649.59 | 29-OCT-07:02 | 14.17 |
November | 2847537.84 | 828.89 | 29-NOV-06:05 | 21.60 |
December | 18823988.40 | 803.63 | 12-DEC-06:05 | 20.17 |
Annual Sum or Average | 0.123582E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.4 | |
Maximum of Months | 34799523.17 | 22292.40 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30252907.17 | 3510.86 | 10-JAN-06:05 | 3.00 |
February | 51653490.21 | 19885.98 | 05-FEB-07:01 | -3.4 |
March | 76404401.11 | 18825.77 | 12-MAR-06:01 | 7.10 |
April | 14221324.48 | 535.78 | 23-APR-07:04 | 21.28 |
May | 2303304.39 | 608.32 | 22-MAY-05:05 | 26.10 |
June | 1347412.79 | 618.02 | 08-JUN-05:05 | 22.20 |
July | 641003.72 | 616.26 | 13-JUL-05:05 | 26.93 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 498995.10 | 449.58 | 10-SEP-07:04 | 31.43 |
October | 2373789.04 | 439.80 | 31-OCT-05:10 | 18.00 |
November | 9564798.75 | 612.44 | 01-NOV-05:05 | 22.62 |
December | 38079749.69 | 19056.07 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.227341E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.4 | |
Maximum of Months | 76404401.11 | 19885.98 | 31.43 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170259E+09 | 20778.07 | 04-JAN-17:21 | 7.00 |
February | 0.384691E+09 | 20750.85 | 04-FEB-14:51 | 7.20 |
March | 0.105482E+09 | 16996.77 | 11-MAR-12:10 | 6.28 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21.63 |
December | 0.244190E+09 | 21280.38 | 20-DEC-18:00 | 4.00 |
Annual Sum or Average | 0.904622E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.00 | |
Maximum of Months | 0.384691E+09 | 21280.38 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.931449E+09 | 764.01 | 02-JAN-09:09 | 0.419292E+10 | 2751.42 | 02-JAN-09:09 |
February | 0.848265E+09 | 764.01 | 01-FEB-09:09 | 0.380401E+10 | 2751.42 | 01-FEB-09:09 |
March | 0.968978E+09 | 764.01 | 01-MAR-09:09 | 0.429860E+10 | 2751.42 | 01-MAR-09:09 |
April | 0.913331E+09 | 764.01 | 01-APR-09:09 | 0.408537E+10 | 2751.42 | 01-APR-09:09 |
May | 0.949815E+09 | 764.01 | 01-MAY-08:09 | 0.424576E+10 | 2751.42 | 01-MAY-08:09 |
June | 0.934721E+09 | 764.01 | 01-JUN-08:09 | 0.415080E+10 | 2751.42 | 01-JUN-08:09 |
July | 0.928759E+09 | 764.01 | 01-JUL-09:09 | 0.417978E+10 | 2751.42 | 01-JUL-09:09 |
August | 0.968836E+09 | 764.01 | 01-AUG-08:09 | 0.429860E+10 | 2751.42 | 01-AUG-08:09 |
September | 0.913331E+09 | 764.01 | 01-SEP-08:09 | 0.408428E+10 | 2751.42 | 01-SEP-08:09 |
October | 0.931591E+09 | 764.01 | 02-OCT-08:09 | 0.419346E+10 | 2751.42 | 02-OCT-08:09 |
November | 0.902761E+09 | 764.01 | 01-NOV-08:09 | 0.405935E+10 | 2751.42 | 01-NOV-08:09 |
December | 0.929364E+09 | 764.01 | 01-DEC-09:09 | 0.417924E+10 | 2751.42 | 01-DEC-09:09 |
Annual Sum or Average | 0.111212E+11 | 0.497722E+11 | ||||
Minimum of Months | 0.848265E+09 | 764.01 | 0.380401E+10 | 2751.42 | ||
Maximum of Months | 0.968978E+09 | 764.01 | 0.429860E+10 | 2751.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118115E+11 | 11815.78 | 02-JAN-17:49 | 0.707031E+10 | 4639.58 | 02-JAN-09:09 |
February | 0.102841E+11 | 11633.30 | 04-FEB-17:00 | 0.641452E+10 | 4639.58 | 01-FEB-09:09 |
March | 0.110540E+11 | 11596.13 | 02-MAR-17:00 | 0.724851E+10 | 4639.58 | 01-MAR-09:09 |
April | 0.993118E+10 | 10749.83 | 14-APR-08:09 | 0.688896E+10 | 4639.58 | 01-APR-09:09 |
May | 0.101436E+11 | 10541.16 | 11-MAY-16:00 | 0.715941E+10 | 4639.58 | 01-MAY-08:09 |
June | 0.979229E+10 | 10551.48 | 20-JUN-16:30 | 0.699930E+10 | 4639.58 | 01-JUN-08:09 |
July | 0.946292E+10 | 10395.87 | 27-JUL-16:00 | 0.704816E+10 | 4639.58 | 01-JUL-09:09 |
August | 0.982729E+10 | 10647.48 | 30-AUG-16:00 | 0.724851E+10 | 4639.58 | 01-AUG-08:09 |
September | 0.952089E+10 | 11150.51 | 30-SEP-16:00 | 0.688712E+10 | 4639.58 | 01-SEP-08:09 |
October | 0.104621E+11 | 11433.31 | 21-OCT-16:00 | 0.707123E+10 | 4639.58 | 02-OCT-08:09 |
November | 0.112934E+11 | 11815.78 | 06-NOV-17:40 | 0.684509E+10 | 4639.58 | 01-NOV-08:09 |
December | 0.119155E+11 | 11815.78 | 01-DEC-17:40 | 0.704724E+10 | 4639.58 | 01-DEC-09:09 |
Annual Sum or Average | 0.125499E+12 | 0.839284E+11 | ||||
Minimum of Months | 0.946292E+10 | 10395.87 | 0.641452E+10 | 4639.58 | ||
Maximum of Months | 0.119155E+11 | 11815.78 | 0.724851E+10 | 4639.58 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.127983E+10 | 1113.38 | 02-JAN-09:09 | 0.443872E+10 | 2912.71 | 02-JAN-09:09 |
February | 0.116501E+10 | 1113.38 | 01-FEB-09:09 | 0.402701E+10 | 2912.71 | 01-FEB-09:09 |
March | 0.132974E+10 | 1113.38 | 01-MAR-09:09 | 0.455059E+10 | 2912.71 | 01-MAR-09:09 |
April | 0.125448E+10 | 1113.38 | 01-APR-09:09 | 0.432486E+10 | 2912.71 | 01-APR-09:09 |
May | 0.130479E+10 | 1113.38 | 01-MAY-08:09 | 0.449465E+10 | 2912.71 | 01-MAY-08:09 |
June | 0.128315E+10 | 1113.38 | 01-JUN-08:09 | 0.439413E+10 | 2912.71 | 01-JUN-08:09 |
July | 0.127612E+10 | 1113.38 | 01-JUL-09:09 | 0.442481E+10 | 2912.71 | 01-JUL-09:09 |
August | 0.132974E+10 | 1113.38 | 01-AUG-08:09 | 0.455059E+10 | 2912.71 | 01-AUG-08:09 |
September | 0.125448E+10 | 1113.38 | 01-SEP-08:09 | 0.432371E+10 | 2912.71 | 01-SEP-08:09 |
October | 0.127983E+10 | 1113.38 | 02-OCT-08:09 | 0.443929E+10 | 2912.71 | 02-OCT-08:09 |
November | 0.123696E+10 | 1113.38 | 01-NOV-08:09 | 0.429732E+10 | 2912.71 | 01-NOV-08:09 |
December | 0.127612E+10 | 1113.38 | 01-DEC-09:09 | 0.442423E+10 | 2912.71 | 01-DEC-09:09 |
Annual Sum or Average | 0.152702E+11 | 0.526899E+11 | ||||
Minimum of Months | 0.116501E+10 | 1113.38 | 0.402701E+10 | 2912.71 | ||
Maximum of Months | 0.132974E+10 | 1113.38 | 0.455059E+10 | 2912.71 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.127983E+10 | 1113.38 | 02-JAN-09:09 | 0.666220E+09 | 437.18 | 02-JAN-09:09 |
February | 0.116501E+10 | 1113.38 | 01-FEB-09:09 | 0.604426E+09 | 437.18 | 01-FEB-09:09 |
March | 0.132974E+10 | 1113.38 | 01-MAR-09:09 | 0.683011E+09 | 437.18 | 01-MAR-09:09 |
April | 0.125448E+10 | 1113.38 | 01-APR-09:09 | 0.649132E+09 | 437.18 | 01-APR-09:09 |
May | 0.130479E+10 | 1113.38 | 01-MAY-08:09 | 0.674616E+09 | 437.18 | 01-MAY-08:09 |
June | 0.128315E+10 | 1113.38 | 01-JUN-08:09 | 0.659528E+09 | 437.18 | 01-JUN-08:09 |
July | 0.127612E+10 | 1113.38 | 01-JUL-09:09 | 0.664132E+09 | 437.18 | 01-JUL-09:09 |
August | 0.132974E+10 | 1113.38 | 01-AUG-08:09 | 0.683011E+09 | 437.18 | 01-AUG-08:09 |
September | 0.125448E+10 | 1113.38 | 01-SEP-08:09 | 0.648959E+09 | 437.18 | 01-SEP-08:09 |
October | 0.127983E+10 | 1113.38 | 02-OCT-08:09 | 0.666307E+09 | 437.18 | 02-OCT-08:09 |
November | 0.123696E+10 | 1113.38 | 01-NOV-08:09 | 0.644998E+09 | 437.18 | 01-NOV-08:09 |
December | 0.127612E+10 | 1113.38 | 01-DEC-09:09 | 0.664046E+09 | 437.18 | 01-DEC-09:09 |
Annual Sum or Average | 0.152702E+11 | 0.790839E+10 | ||||
Minimum of Months | 0.116501E+10 | 1113.38 | 0.604426E+09 | 437.18 | ||
Maximum of Months | 0.132974E+10 | 1113.38 | 0.683011E+09 | 437.18 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 45578066.16 | 38.29 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 41478851.50 | 38.29 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 47305342.00 | 38.29 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 44651754.38 | 38.29 | 01-APR-09:09 | 0.00 | 0.00 |
May | 46438557.34 | 38.29 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 45648367.37 | 38.29 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 45447780.23 | 38.29 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 47303700.48 | 38.29 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 44651754.38 | 38.29 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 45579707.68 | 38.29 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 44084755.11 | 38.29 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 45449879.35 | 38.29 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.543619E+09 | 0.00 | 0.00 | ||
Minimum of Months | 41478851.50 | 38.29 | 0.00 | 0.00 | |
Maximum of Months | 47305342.00 | 38.29 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.699524E+09 | 0.931449E+09 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1176199.07 | 0.359976E+09 |
February | 0.638757E+09 | 0.848265E+09 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2345709.21 | 0.260227E+09 |
March | 0.730614E+09 | 0.968978E+09 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6316207.31 | 0.300594E+09 |
April | 0.690691E+09 | 0.913331E+09 | 0.408537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14715357.39 | 0.113699E+09 |
May | 0.715069E+09 | 0.949815E+09 | 0.424576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76169671.08 | 3030288.29 |
June | 0.705176E+09 | 0.934721E+09 | 0.415080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69890806.30 | 5273476.05 |
July | 0.700584E+09 | 0.928759E+09 | 0.417978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97415961.49 | 323038.76 |
August | 0.730614E+09 | 0.968836E+09 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97756033.26 | 6330951.44 |
September | 0.690691E+09 | 0.913331E+09 | 0.408428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75675237.32 | 11187396.32 |
October | 0.699524E+09 | 0.931591E+09 | 0.419346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60799172.64 | 96691181.95 |
November | 0.673027E+09 | 0.902761E+09 | 0.405935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6316823.28 | 0.193512E+09 |
December | 0.700584E+09 | 0.929364E+09 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3747201.64 | 0.318606E+09 |
Annual Sum or Average | 0.837485E+10 | 0.111212E+11 | 0.497722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512324E+09 | 0.166945E+10 |
Minimum of Months | 0.638757E+09 | 0.848265E+09 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1176199.07 | 323038.76 |
Maximum of Months | 0.730614E+09 | 0.968978E+09 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97756033.26 | 0.359976E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.118115E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 951164.95 | 0.350512E+09 |
February | 0.201852E+11 | 0.102841E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1920403.64 | 0.256136E+09 |
March | 0.230879E+11 | 0.110540E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5375159.72 | 0.291192E+09 |
April | 0.218263E+11 | 0.993118E+10 | 0.688896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11860689.86 | 0.112611E+09 |
May | 0.225967E+11 | 0.101436E+11 | 0.715941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48702715.77 | 16124406.59 |
June | 0.222841E+11 | 0.979229E+10 | 0.699930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46222898.61 | 15191550.38 |
July | 0.221389E+11 | 0.946292E+10 | 0.704816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58936443.92 | 4796485.47 |
August | 0.230879E+11 | 0.982729E+10 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61689149.85 | 20537108.62 |
September | 0.218263E+11 | 0.952089E+10 | 0.688712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49059128.34 | 30527518.83 |
October | 0.221054E+11 | 0.104621E+11 | 0.707123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40719113.37 | 0.110671E+09 |
November | 0.212681E+11 | 0.112934E+11 | 0.684509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5094147.18 | 0.185300E+09 |
December | 0.221389E+11 | 0.119155E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3140208.04 | 0.312065E+09 |
Annual Sum or Average | 0.264651E+12 | 0.125499E+12 | 0.839284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333671E+09 | 0.170567E+10 |
Minimum of Months | 0.201852E+11 | 0.946292E+10 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 951164.95 | 4796485.47 |
Maximum of Months | 0.230879E+11 | 0.119155E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61689149.85 | 0.350512E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.127983E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 505589.60 | 0.199380E+09 |
February | 0.190200E+10 | 0.116501E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1021105.13 | 0.141727E+09 |
March | 0.217552E+10 | 0.132974E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2858118.91 | 0.152105E+09 |
April | 0.205665E+10 | 0.125448E+10 | 0.432486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6719118.93 | 54044476.65 |
May | 0.212923E+10 | 0.130479E+10 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34872168.91 | 1287036.76 |
June | 0.209978E+10 | 0.128315E+10 | 0.439413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31841359.88 | 2326132.24 |
July | 0.208610E+10 | 0.127612E+10 | 0.442481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44383928.90 | 134945.77 |
August | 0.217552E+10 | 0.132974E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44289832.14 | 2863233.43 |
September | 0.205665E+10 | 0.125448E+10 | 0.432371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34334619.03 | 5051676.81 |
October | 0.208295E+10 | 0.127983E+10 | 0.443929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27464598.87 | 45032374.33 |
November | 0.200405E+10 | 0.123696E+10 | 0.429732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2886834.92 | 95212230.08 |
December | 0.208610E+10 | 0.127612E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1669838.97 | 0.171679E+09 |
Annual Sum or Average | 0.249375E+11 | 0.152702E+11 | 0.526899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232847E+09 | 0.870843E+09 |
Minimum of Months | 0.190200E+10 | 0.116501E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 505589.60 | 134945.77 |
Maximum of Months | 0.217552E+10 | 0.132974E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44383928.90 | 0.199380E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.127983E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 505715.83 | 0.191114E+09 |
February | 0.190200E+10 | 0.116501E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1021107.50 | 0.134880E+09 |
March | 0.217552E+10 | 0.132974E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2858500.59 | 0.145449E+09 |
April | 0.205665E+10 | 0.125448E+10 | 0.649132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6726472.00 | 53153970.52 |
May | 0.212923E+10 | 0.130479E+10 | 0.674616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34787472.67 | 1365501.14 |
June | 0.209978E+10 | 0.128315E+10 | 0.659528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31872504.71 | 2392219.83 |
July | 0.208610E+10 | 0.127612E+10 | 0.664132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44477586.62 | 146285.09 |
August | 0.217552E+10 | 0.132974E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44538597.11 | 2849015.04 |
September | 0.205665E+10 | 0.125448E+10 | 0.648959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34470230.36 | 5011676.08 |
October | 0.208295E+10 | 0.127983E+10 | 0.666307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27592236.54 | 45077165.38 |
November | 0.200405E+10 | 0.123696E+10 | 0.644998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2890477.14 | 95327946.74 |
December | 0.208610E+10 | 0.127612E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1669912.56 | 0.165079E+09 |
Annual Sum or Average | 0.249375E+11 | 0.152702E+11 | 0.790839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233411E+09 | 0.841845E+09 |
Minimum of Months | 0.190200E+10 | 0.116501E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 505715.83 | 146285.09 |
Maximum of Months | 0.217552E+10 | 0.132974E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44538597.11 | 0.191114E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.165769E+09 | 45578066.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8190.20 | 0.172930E+10 |
February | 0.151369E+09 | 41478851.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30606.87 | 0.150217E+10 |
March | 0.173136E+09 | 47305342.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6592287.48 | 0.100397E+10 |
April | 0.163676E+09 | 44651754.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46525639.46 | 0.406241E+09 |
May | 0.169453E+09 | 46438557.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344937E+09 | 50774349.06 |
June | 0.167108E+09 | 45648367.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392700E+09 | 25105775.41 |
July | 0.166020E+09 | 45447780.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376011E+09 | 58764389.55 |
August | 0.173136E+09 | 47303700.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308232E+09 | 73650596.90 |
September | 0.163676E+09 | 44651754.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131835E+09 | 0.158388E+09 |
October | 0.165769E+09 | 45579707.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39869113.57 | 0.358323E+09 |
November | 0.159490E+09 | 44084755.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3784436.05 | 0.989294E+09 |
December | 0.166020E+09 | 45449879.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1138524.88 | 0.160046E+10 |
Annual Sum or Average | 0.198462E+10 | 0.543619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165166E+10 | 0.795643E+10 |
Minimum of Months | 0.151369E+09 | 41478851.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8190.20 | 25105775.41 |
Maximum of Months | 0.173136E+09 | 47305342.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392700E+09 | 0.172930E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 785.10 | 02-JAN-15:09 | 764.01 | 02-JAN-09:09 | 2751.42 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 | 19-JAN-12:10 | 800.29 | 21-JAN-06:00 |
February | 785.10 | 01-FEB-15:09 | 764.01 | 01-FEB-09:09 | 2751.42 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.02 | 02-FEB-13:00 | 1219.02 | 05-FEB-08:00 |
March | 785.10 | 01-MAR-15:09 | 764.01 | 01-MAR-09:09 | 2751.42 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.80 | 28-MAR-14:00 | 956.90 | 20-MAR-22:00 |
April | 785.10 | 01-APR-10:09 | 764.01 | 01-APR-09:09 | 2751.42 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.93 | 29-APR-16:00 | 527.14 | 01-APR-21:10 |
May | 785.10 | 01-MAY-14:09 | 764.01 | 01-MAY-08:09 | 2751.42 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 211.15 | 07-MAY-18:03 | 50.92 | 13-MAY-04:55 |
June | 785.10 | 01-JUN-14:09 | 764.01 | 01-JUN-08:09 | 2751.42 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 208.47 | 09-JUN-20:03 | 129.99 | 06-JUN-20:55 |
July | 785.10 | 01-JUL-10:09 | 764.01 | 01-JUL-09:09 | 2751.42 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 239.35 | 02-JUL-21:00 | 34.20 | 11-JUL-20:10 |
August | 785.10 | 01-AUG-14:09 | 764.01 | 01-AUG-08:09 | 2751.42 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 335.16 | 22-AUG-20:03 | 173.10 | 25-AUG-24:00 |
September | 785.10 | 01-SEP-14:09 | 764.01 | 01-SEP-08:09 | 2751.42 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 453.97 | 09-SEP-22:53 | 125.58 | 05-SEP-02:55 |
October | 785.10 | 02-OCT-14:09 | 764.01 | 02-OCT-08:09 | 2751.42 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 205.34 | 08-OCT-18:20 | 470.91 | 29-OCT-02:00 |
November | 785.10 | 01-NOV-14:09 | 764.01 | 01-NOV-08:09 | 2751.42 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.59 | 07-NOV-21:30 | 683.49 | 12-NOV-07:00 |
December | 785.10 | 01-DEC-15:09 | 764.01 | 01-DEC-09:09 | 2751.42 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 | 13-DEC-14:00 | 938.64 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 785.10 | 764.01 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 | 34.20 | |||||
Maximum of Months | 785.10 | 764.01 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 453.97 | 1219.02 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 11815.78 | 02-JAN-17:49 | 4639.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 19-JAN-12:10 | 737.65 | 21-JAN-06:00 |
February | 24809.68 | 01-FEB-15:09 | 11633.30 | 04-FEB-17:00 | 4639.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.18 | 02-FEB-13:00 | 1042.51 | 05-FEB-08:00 |
March | 24809.68 | 01-MAR-15:09 | 11596.13 | 02-MAR-17:00 | 4639.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 28-MAR-14:00 | 909.19 | 20-MAR-22:00 |
April | 24809.68 | 01-APR-10:09 | 10749.83 | 14-APR-08:09 | 4639.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.69 | 29-APR-16:00 | 483.69 | 01-APR-21:10 |
May | 24809.68 | 01-MAY-14:09 | 10541.16 | 11-MAY-16:00 | 4639.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.63 | 07-MAY-18:03 | 79.01 | 05-MAY-03:55 |
June | 24809.68 | 01-JUN-14:09 | 10551.48 | 20-JUN-16:30 | 4639.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.01 | 09-JUN-20:03 | 153.03 | 06-JUN-21:10 |
July | 24809.68 | 01-JUL-10:09 | 10395.87 | 27-JUL-16:00 | 4639.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.40 | 04-JUL-18:03 | 59.94 | 31-JUL-02:55 |
August | 24809.68 | 01-AUG-14:09 | 10647.48 | 30-AUG-16:00 | 4639.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.51 | 22-AUG-20:03 | 216.01 | 25-AUG-23:55 |
September | 24809.68 | 01-SEP-14:09 | 11150.51 | 30-SEP-16:00 | 4639.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 322.69 | 09-SEP-22:53 | 171.97 | 05-SEP-02:55 |
October | 24809.68 | 02-OCT-14:09 | 11433.31 | 21-OCT-16:00 | 4639.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 175.13 | 08-OCT-18:03 | 445.66 | 29-OCT-02:00 |
November | 24809.68 | 01-NOV-14:09 | 11815.78 | 06-NOV-17:40 | 4639.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.26 | 07-NOV-13:00 | 616.43 | 12-NOV-07:00 |
December | 24809.68 | 01-DEC-15:09 | 11815.78 | 01-DEC-17:40 | 4639.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.55 | 13-DEC-14:00 | 949.64 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24809.68 | 10395.87 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 59.94 | |||||
Maximum of Months | 24809.68 | 11815.78 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 322.69 | 1042.51 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1113.38 | 02-JAN-09:09 | 2912.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 19-JAN-12:10 | 409.39 | 26-JAN-03:00 |
February | 2337.76 | 01-FEB-15:09 | 1113.38 | 01-FEB-09:09 | 2912.71 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 02-FEB-13:00 | 579.73 | 16-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 1113.38 | 01-MAR-09:09 | 2912.71 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 | 28-MAR-14:00 | 479.96 | 20-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 1113.38 | 01-APR-09:09 | 2912.71 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.57 | 29-APR-16:00 | 258.59 | 01-APR-21:10 |
May | 2337.76 | 01-MAY-14:09 | 1113.38 | 01-MAY-08:09 | 2912.71 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.86 | 07-MAY-18:10 | 19.79 | 13-MAY-04:40 |
June | 2337.76 | 01-JUN-14:09 | 1113.38 | 01-JUN-08:09 | 2912.71 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.20 | 09-JUN-20:10 | 59.15 | 06-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 1113.38 | 01-JUL-09:09 | 2912.71 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.43 | 02-JUL-21:30 | 18.03 | 11-JUL-20:10 |
August | 2337.76 | 01-AUG-14:09 | 1113.38 | 01-AUG-08:09 | 2912.71 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 22-AUG-20:10 | 92.95 | 25-AUG-24:00 |
September | 2337.76 | 01-SEP-14:09 | 1113.38 | 01-SEP-08:09 | 2912.71 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 204.23 | 09-SEP-22:53 | 56.23 | 12-SEP-24:00 |
October | 2337.76 | 02-OCT-14:09 | 1113.38 | 02-OCT-08:09 | 2912.71 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.90 | 08-OCT-18:10 | 236.63 | 29-OCT-01:40 |
November | 2337.76 | 01-NOV-14:09 | 1113.38 | 01-NOV-08:09 | 2912.71 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 07-NOV-21:47 | 333.82 | 12-NOV-07:20 |
December | 2337.76 | 01-DEC-15:09 | 1113.38 | 01-DEC-09:09 | 2912.71 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 | 13-DEC-14:00 | 505.68 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 1113.38 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 18.03 | |||||
Maximum of Months | 2337.76 | 1113.38 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 204.23 | 579.73 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1113.38 | 02-JAN-09:09 | 437.18 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 19-JAN-12:07 | 388.41 | 26-JAN-03:00 |
February | 2337.76 | 01-FEB-15:09 | 1113.38 | 01-FEB-09:09 | 437.18 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 02-FEB-13:00 | 555.94 | 05-FEB-08:00 |
March | 2337.76 | 01-MAR-15:09 | 1113.38 | 01-MAR-09:09 | 437.18 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 | 28-MAR-14:00 | 456.32 | 20-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 1113.38 | 01-APR-09:09 | 437.18 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.57 | 29-APR-16:00 | 253.41 | 01-APR-21:10 |
May | 2337.76 | 01-MAY-14:09 | 1113.38 | 01-MAY-08:09 | 437.18 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.07 | 07-MAY-18:10 | 22.19 | 13-MAY-04:45 |
June | 2337.76 | 01-JUN-14:09 | 1113.38 | 01-JUN-08:09 | 437.18 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.76 | 09-JUN-20:10 | 59.94 | 06-JUN-20:55 |
July | 2337.76 | 01-JUL-10:09 | 1113.38 | 01-JUL-09:09 | 437.18 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.25 | 02-JUL-21:30 | 16.24 | 11-JUL-20:10 |
August | 2337.76 | 01-AUG-14:09 | 1113.38 | 01-AUG-08:09 | 437.18 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.99 | 22-AUG-20:10 | 89.28 | 25-AUG-24:00 |
September | 2337.76 | 01-SEP-14:09 | 1113.38 | 01-SEP-08:09 | 437.18 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 205.39 | 09-SEP-22:53 | 51.25 | 05-SEP-03:20 |
October | 2337.76 | 02-OCT-14:09 | 1113.38 | 02-OCT-08:09 | 437.18 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.13 | 08-OCT-18:10 | 238.29 | 29-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 1113.38 | 01-NOV-08:09 | 437.18 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.51 | 07-NOV-21:47 | 332.04 | 12-NOV-08:00 |
December | 2337.76 | 01-DEC-15:09 | 1113.38 | 01-DEC-09:09 | 437.18 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 13-DEC-14:00 | 471.34 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 1113.38 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 16.24 | |||||
Maximum of Months | 2337.76 | 1113.38 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 205.39 | 555.94 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 186.05 | 02-JAN-15:09 | 38.29 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 | 02-JAN-15:00 | 18215.21 | 04-JAN-18:00 |
February | 186.05 | 01-FEB-15:09 | 38.29 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.28 | 24-FEB-12:55 | 20294.28 | 04-FEB-18:00 |
March | 186.05 | 01-MAR-15:09 | 38.29 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.34 | 30-MAR-13:00 | 17677.43 | 11-MAR-12:10 |
April | 186.05 | 01-APR-10:09 | 38.29 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1045.51 | 28-APR-11:02 | 2708.16 | 02-APR-11:02 |
May | 186.05 | 01-MAY-14:09 | 38.29 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.56 | 27-MAY-11:02 | 1244.98 | 13-MAY-11:53 |
June | 186.05 | 01-JUN-14:09 | 38.29 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1876.33 | 14-JUN-11:02 | 1454.33 | 18-JUN-13:53 |
July | 186.05 | 01-JUL-10:09 | 38.29 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2549.55 | 18-JUL-11:02 | 1454.67 | 31-JUL-11:02 |
August | 186.05 | 01-AUG-14:09 | 38.29 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1823.88 | 01-AUG-11:02 | 1623.68 | 06-AUG-15:53 |
September | 186.05 | 01-SEP-14:09 | 38.29 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1876.14 | 10-SEP-11:02 | 2602.85 | 02-SEP-15:52 |
October | 186.05 | 02-OCT-14:09 | 38.29 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 757.68 | 06-OCT-11:03 | 4092.65 | 27-OCT-11:01 |
November | 186.05 | 01-NOV-14:09 | 38.29 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.10 | 01-NOV-14:00 | 6815.29 | 12-NOV-12:01 |
December | 186.05 | 01-DEC-15:09 | 38.29 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.33 | 13-DEC-12:05 | 22019.19 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 186.05 | 38.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 | 1244.98 | ||||
Maximum of Months | 186.05 | 38.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2549.55 | 22019.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8661.21 | 19-JAN-23:05 | 0.00 | 163.56 | 1210.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.49 |
February | 8671.63 | 28-FEB-22:40 | 0.00 | 163.56 | 1210.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.65 |
March | 13686.67 | 30-MAR-21:25 | 0.00 | 163.56 | 1210.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.36 |
April | 20077.03 | 23-APR-07:02 | 0.00 | 212.24 | 2269.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 |
May | 22281.93 | 07-MAY-18:53 | 0.00 | 127.34 | 1361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 77.30 | 0.00 |
June | 23253.44 | 13-JUN-20:10 | 0.00 | 509.33 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 56.25 | 0.00 |
July | 22683.66 | 07-JUL-21:23 | 0.00 | 245.35 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 91.86 | 0.00 |
August | 24463.45 | 03-AUG-21:23 | 0.00 | 245.35 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 0.00 |
September | 24875.72 | 11-SEP-02:63 | 0.00 | 127.34 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 35.85 | 0.00 |
October | 27437.68 | 26-OCT-20:19 | 0.00 | 654.26 | 4840.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 |
November | 17975.00 | 02-NOV-22:03 | 0.00 | 245.35 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24976.80 | 17-DEC-08:61 | 0.00 | 339.59 | 3630.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8661.21 | 0.00 | 127.34 | 1210.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27437.68 | 0.00 | 654.26 | 4840.70 | 0.00 | 0.00 | 0.00 | 0.00 | 91.86 | 94.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 130110.88 | 02-JAN-07:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.03 |
February | 128951.79 | 25-FEB-07:03 | 12404.84 | 1378.20 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 134404.44 | 01-MAR-07:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.45 |
April | 127478.26 | 19-APR-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.92 |
May | 113443.77 | 12-MAY-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 |
June | 116346.41 | 12-JUN-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 |
July | 102457.49 | 08-JUL-06:02 | 15506.05 | 1722.75 | 7732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 110574.89 | 04-AUG-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 0.00 |
September | 112613.99 | 23-SEP-06:02 | 15506.05 | 1722.75 | 7732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 |
October | 193115.66 | 27-OCT-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.59 |
November | 128869.07 | 05-NOV-08:62 | 12404.84 | 1378.20 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 |
December | 137292.26 | 17-DEC-09:02 | 15506.05 | 1722.75 | 7732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 102457.49 | 12404.84 | 1378.20 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 193115.66 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 94.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14851.15 | 02-JAN-21:15 | 0.00 | 64.93 | 1281.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.31 |
February | 18994.55 | 26-FEB-08:61 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15243.30 | 19-MAR-07:01 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 |
April | 15046.63 | 16-APR-19:02 | 0.00 | 162.33 | 2402.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.60 |
May | 13377.04 | 07-MAY-18:43 | 0.00 | 97.40 | 1441.26 | 0.00 | 0.00 | 0.00 | 0.00 | 50.52 | 0.00 |
June | 13541.10 | 28-JUN-20:10 | 0.00 | 742.25 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 77.12 | 0.00 |
July | 16577.71 | 07-JUL-20:43 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 62.16 | 0.00 |
August | 18058.52 | 30-AUG-21:23 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18452.50 | 10-SEP-21:23 | 0.00 | 97.40 | 1441.26 | 0.00 | 0.00 | 0.00 | 0.00 | 31.42 | 0.00 |
October | 18616.02 | 05-OCT-22:43 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 | 0.00 |
November | 17479.53 | 22-NOV-21:15 | 0.00 | 64.93 | 1281.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.47 |
December | 16679.77 | 25-DEC-20:01 | 0.00 | 227.26 | 3362.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13377.04 | 0.00 | 64.93 | 1281.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18994.55 | 0.00 | 742.25 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 77.12 | 73.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10573.25 | 29-JAN-19:22 | 0.00 | 162.33 | 360.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.94 |
February | 10554.91 | 09-FEB-21:33 | 0.00 | 97.40 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.01 |
March | 11733.36 | 26-MAR-07:01 | 0.00 | 292.19 | 648.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 |
April | 11814.74 | 07-APR-20:33 | 0.00 | 97.40 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.39 |
May | 11457.65 | 07-MAY-18:43 | 0.00 | 97.40 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 50.76 | 0.00 |
June | 10617.92 | 28-JUN-20:10 | 0.00 | 742.25 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 77.52 | 0.00 |
July | 13435.84 | 19-JUL-20:43 | 0.00 | 97.40 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 45.38 | 0.00 |
August | 14864.08 | 30-AUG-21:23 | 0.00 | 97.40 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15527.10 | 10-SEP-22:03 | 0.00 | 97.40 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 | 0.00 |
October | 15329.19 | 09-OCT-19:23 | 0.00 | 97.40 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 41.87 | 0.00 |
November | 16019.26 | 12-NOV-20:01 | 0.00 | 259.73 | 576.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.76 |
December | 17659.97 | 17-DEC-20:07 | 0.00 | 292.19 | 648.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10554.91 | 0.00 | 97.40 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17659.97 | 0.00 | 742.25 | 648.97 | 0.00 | 0.00 | 0.00 | 0.00 | 77.52 | 175.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 4.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 4.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 4.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | |
Maximum of Months | 0.00 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.520508E+11 | 55137.76 | 19-JAN-15:30 | 0.00 | 0.00 |
February | 0.493532E+11 | 53914.06 | 24-FEB-15:00 | 0.00 | 0.00 |
March | 0.567275E+11 | 54772.53 | 06-MAR-15:00 | 0.00 | 0.00 |
April | 0.626562E+11 | 65761.64 | 28-APR-15:00 | 0.00 | 0.00 |
May | 0.834296E+11 | 66906.39 | 27-MAY-15:20 | 0.00 | 0.00 |
June | 0.850540E+11 | 73029.35 | 28-JUN-14:09 | 0.00 | 0.00 |
July | 0.888652E+11 | 77797.91 | 22-JUL-15:00 | 0.00 | 0.00 |
August | 0.896938E+11 | 71427.82 | 03-AUG-14:50 | 0.00 | 0.00 |
September | 0.820371E+11 | 75174.10 | 09-SEP-15:00 | 0.00 | 0.00 |
October | 0.784744E+11 | 74981.85 | 07-OCT-12:00 | 0.00 | 0.00 |
November | 0.590564E+11 | 63543.12 | 02-NOV-14:50 | 0.00 | 0.00 |
December | 0.564378E+11 | 58945.95 | 15-DEC-15:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.843836E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.493532E+11 | 53914.06 | 0.00 | 0.00 | |
Maximum of Months | 0.896938E+11 | 77797.91 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.481446E+10 | 8663.61 | 23-JAN-12:50 | 0.00 | 0.00 |
February | 0.536823E+10 | 10029.99 | 13-FEB-12:30 | 0.00 | 0.00 |
March | 0.632909E+10 | 11639.83 | 22-MAR-12:30 | 0.00 | 0.00 |
April | 0.754717E+10 | 11909.46 | 10-APR-12:30 | 0.00 | 0.00 |
May | 0.731448E+10 | 11576.49 | 15-MAY-12:30 | 0.00 | 0.00 |
June | 0.775459E+10 | 11672.73 | 09-JUN-12:30 | 0.00 | 0.00 |
July | 0.754175E+10 | 11031.51 | 06-JUL-12:39 | 0.00 | 0.00 |
August | 0.711991E+10 | 11055.27 | 03-AUG-12:30 | 0.00 | 0.00 |
September | 0.597518E+10 | 10323.94 | 03-SEP-12:30 | 0.00 | 0.00 |
October | 0.593007E+10 | 9916.90 | 01-OCT-12:30 | 0.00 | 0.00 |
November | 0.480385E+10 | 8943.72 | 15-NOV-12:20 | 0.00 | 0.00 |
December | 0.436865E+10 | 7974.10 | 26-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.748674E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.436865E+10 | 7974.10 | 0.00 | 0.00 | |
Maximum of Months | 0.775459E+10 | 11909.46 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.153482E+11 | 0.297478E+10 | 0.163682E+11 | 0.00 | 0.952757E+10 | 0.00 | 0.980781E+09 | 0.486582E+10 | 0.00 | 0.00 | 0.00 | 0.198542E+10 | 0.00 |
February | 0.135038E+11 | 0.252982E+10 | 0.148500E+11 | 0.00 | 0.866140E+10 | 0.00 | 0.953231E+09 | 0.706271E+10 | 0.00 | 0.00 | 0.00 | 0.179226E+10 | 0.00 |
March | 0.147298E+11 | 0.256439E+10 | 0.167807E+11 | 0.00 | 0.970461E+10 | 0.00 | 0.474061E+09 | 0.105159E+11 | 0.00 | 0.00 | 0.00 | 0.195797E+10 | 0.00 |
April | 0.133981E+11 | 0.225244E+10 | 0.159483E+11 | 0.00 | 0.940390E+10 | 0.00 | 0.00 | 0.198979E+11 | 0.00 | 0.00 | 0.00 | 0.175556E+10 | 0.00 |
May | 0.137494E+11 | 0.212085E+10 | 0.165744E+11 | 0.00 | 0.100363E+11 | 0.00 | 0.00 | 0.392498E+11 | 0.00 | 0.00 | 0.00 | 0.169890E+10 | 0.00 |
June | 0.133390E+11 | 0.193991E+10 | 0.162038E+11 | 0.00 | 0.100433E+11 | 0.00 | 0.00 | 0.419567E+11 | 0.00 | 0.00 | 0.00 | 0.157134E+10 | 0.00 |
July | 0.129894E+11 | 0.206403E+10 | 0.163169E+11 | 0.00 | 0.105722E+11 | 0.00 | 0.00 | 0.453891E+11 | 0.00 | 0.00 | 0.00 | 0.153357E+10 | 0.00 |
August | 0.135029E+11 | 0.223134E+10 | 0.167807E+11 | 0.00 | 0.105690E+11 | 0.00 | 0.00 | 0.450150E+11 | 0.00 | 0.00 | 0.00 | 0.159486E+10 | 0.00 |
September | 0.129878E+11 | 0.238502E+10 | 0.159441E+11 | 0.00 | 0.995653E+10 | 0.00 | 0.00 | 0.391745E+11 | 0.00 | 0.00 | 0.00 | 0.158907E+10 | 0.00 |
October | 0.139989E+11 | 0.270487E+10 | 0.163703E+11 | 0.00 | 0.101404E+11 | 0.00 | 0.00 | 0.335327E+11 | 0.00 | 0.00 | 0.00 | 0.172717E+10 | 0.00 |
November | 0.147141E+11 | 0.281751E+10 | 0.158468E+11 | 0.00 | 0.930789E+10 | 0.00 | 1824161.96 | 0.145918E+11 | 0.00 | 0.00 | 0.00 | 0.177656E+10 | 0.00 |
December | 0.154426E+11 | 0.302687E+10 | 0.163148E+11 | 0.00 | 0.960249E+10 | 0.00 | 0.771005E+09 | 0.933946E+10 | 0.00 | 0.00 | 0.00 | 0.194071E+10 | 0.00 |
Annual Sum or Average | 0.167704E+12 | 0.296118E+11 | 0.194299E+12 | 0.00 | 0.117526E+12 | 0.00 | 0.318090E+10 | 0.310591E+12 | 0.00 | 0.00 | 0.00 | 0.209234E+11 | 0.00 |
Minimum of Months | 0.129878E+11 | 0.193991E+10 | 0.148500E+11 | 0.00 | 0.866140E+10 | 0.00 | 0.00 | 0.486582E+10 | 0.00 | 0.00 | 0.00 | 0.153357E+10 | 0.00 |
Maximum of Months | 0.154426E+11 | 0.302687E+10 | 0.167807E+11 | 0.00 | 0.105722E+11 | 0.00 | 0.980781E+09 | 0.453891E+11 | 0.00 | 0.00 | 0.00 | 0.198542E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 14844.83 | 02-JAN-17:49 | 2630.71 | 01-JAN-06:10 | 10740.89 | 02-JAN-09:09 | 0.00 | 7811.14 | 19-JAN-07:10 | 0.00 | 18092.50 | 04-JAN-17:00 |
February | 14662.35 | 04-FEB-17:00 | 2630.71 | 01-FEB-06:10 | 10740.89 | 01-FEB-09:09 | 0.00 | 7603.44 | 27-FEB-07:10 | 0.00 | 19657.33 | 04-FEB-17:00 |
March | 14625.18 | 02-MAR-17:00 | 2630.71 | 01-MAR-06:10 | 10740.89 | 01-MAR-09:09 | 0.00 | 8459.90 | 07-MAR-07:10 | 0.00 | 20112.35 | 11-MAR-12:09 |
April | 13778.88 | 14-APR-08:09 | 2630.71 | 01-APR-05:10 | 10740.89 | 01-APR-09:09 | 0.00 | 8572.74 | 23-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 13570.21 | 11-MAY-16:00 | 2630.71 | 01-MAY-05:10 | 10740.89 | 01-MAY-08:09 | 0.00 | 8572.74 | 23-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 13580.52 | 20-JUN-16:30 | 2630.71 | 01-JUN-05:10 | 10740.89 | 01-JUN-08:09 | 0.00 | 8572.74 | 04-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 13424.92 | 27-JUL-16:00 | 2630.71 | 01-JUL-05:10 | 10740.89 | 01-JUL-09:09 | 0.00 | 9073.06 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 13676.53 | 30-AUG-16:00 | 2630.71 | 01-AUG-05:10 | 10740.89 | 01-AUG-08:09 | 0.00 | 8572.74 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 14179.56 | 30-SEP-16:00 | 2630.71 | 01-SEP-05:10 | 10740.89 | 01-SEP-08:09 | 0.00 | 8966.73 | 10-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 14462.36 | 21-OCT-16:00 | 2630.71 | 01-OCT-05:10 | 10740.89 | 02-OCT-08:09 | 0.00 | 8926.06 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 14844.83 | 06-NOV-17:40 | 2630.71 | 01-NOV-05:10 | 10740.89 | 01-NOV-08:09 | 0.00 | 8572.74 | 01-NOV-06:10 | 0.00 | 611.92 | 16-NOV-07:19 |
December | 14844.83 | 01-DEC-17:40 | 2630.71 | 01-DEC-06:10 | 10740.89 | 01-DEC-09:09 | 0.00 | 8572.74 | 12-DEC-07:10 | 0.00 | 22917.29 | 20-DEC-17:00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 13424.92 | 2630.71 | 10740.89 | 0.00 | 7603.44 | 0.00 | 0.00 | |||||
Maximum of Months | 14844.83 | 2630.71 | 10740.89 | 0.00 | 9073.06 | 0.00 | 22917.29 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 23363.77 | 19-JAN-15:09 | 0.00 | 0.00 | 0.00 | 2000.02 | 23-JAN-12:00 | 0.00 | 01-JAN-00:10 |
February | 23487.04 | 24-FEB-13:39 | 0.00 | 0.00 | 0.00 | 1998.74 | 01-FEB-12:20 | 0.00 | 01-FEB-00:10 |
March | 25142.85 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 1989.84 | 01-MAR-12:00 | 0.00 | 01-MAR-00:10 |
April | 34465.82 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 1845.47 | 03-APR-11:00 | 0.00 | 01-APR-00:10 |
May | 35796.24 | 30-MAY-12:00 | 0.00 | 0.00 | 0.00 | 1794.55 | 01-MAY-11:09 | 0.00 | 01-MAY-00:10 |
June | 41625.73 | 28-JUN-14:09 | 0.00 | 0.00 | 0.00 | 1683.81 | 01-JUN-11:00 | 0.00 | 01-JUN-00:10 |
July | 45404.50 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1551.77 | 03-JUL-11:00 | 0.00 | 01-JUL-00:10 |
August | 41033.86 | 03-AUG-14:00 | 0.00 | 0.00 | 0.00 | 1560.40 | 31-AUG-11:09 | 0.00 | 01-AUG-00:10 |
September | 42608.24 | 09-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1691.68 | 29-SEP-11:30 | 0.00 | 01-SEP-00:10 |
October | 43251.46 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 1835.66 | 31-OCT-11:20 | 0.00 | 01-OCT-00:10 |
November | 32250.22 | 02-NOV-14:09 | 0.00 | 0.00 | 0.00 | 1979.58 | 29-NOV-12:39 | 0.00 | 01-NOV-00:10 |
December | 27841.85 | 16-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1995.56 | 29-DEC-12:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 23363.77 | 0.00 | 0.00 | 0.00 | 1551.77 | 0.00 | |||
Maximum of Months | 45404.50 | 0.00 | 0.00 | 0.00 | 2000.02 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55137.76 | 19-JAN-15:30 | 13706.48 | 10740.89 | 0.00 | 0.00 | 6029.59 | 0.00 | 0.00 | 23197.08 | 0.00 |
February | 53914.06 | 24-FEB-15:00 | 13111.04 | 10740.89 | 0.00 | 0.00 | 5910.18 | 0.00 | 0.00 | 22733.66 | 0.00 |
March | 54772.53 | 06-MAR-15:00 | 13290.44 | 10740.89 | 0.00 | 0.00 | 5909.74 | 0.00 | 0.00 | 23415.62 | 0.00 |
April | 65761.64 | 28-APR-15:00 | 12573.62 | 10740.89 | 0.00 | 0.00 | 6697.46 | 0.00 | 0.00 | 34465.82 | 0.00 |
May | 66906.39 | 27-MAY-15:20 | 12399.16 | 10740.89 | 0.00 | 0.00 | 6974.03 | 0.00 | 0.00 | 35515.40 | 0.00 |
June | 73029.35 | 28-JUN-14:09 | 11174.68 | 10740.89 | 0.00 | 0.00 | 8419.12 | 0.00 | 0.00 | 41625.73 | 0.00 |
July | 77797.91 | 22-JUL-15:00 | 11427.68 | 10740.89 | 0.00 | 0.00 | 9073.06 | 0.00 | 0.00 | 45404.50 | 0.00 |
August | 71427.82 | 03-AUG-14:50 | 10422.06 | 10740.89 | 0.00 | 0.00 | 8087.02 | 0.00 | 0.00 | 41030.95 | 0.00 |
September | 75174.10 | 09-SEP-15:00 | 12188.13 | 10740.89 | 0.00 | 0.00 | 8378.15 | 0.00 | 0.00 | 42608.24 | 0.00 |
October | 74981.85 | 07-OCT-12:00 | 10396.20 | 10740.89 | 0.00 | 0.00 | 8926.06 | 0.00 | 0.00 | 43251.46 | 0.00 |
November | 63543.12 | 02-NOV-14:50 | 12971.50 | 10740.89 | 0.00 | 0.00 | 6351.87 | 0.00 | 0.00 | 32095.16 | 0.00 |
December | 58945.95 | 15-DEC-15:09 | 13566.65 | 10740.89 | 0.00 | 0.00 | 6061.49 | 0.00 | 0.00 | 27160.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 53914.06 | 10396.20 | 10740.89 | 0.00 | 0.00 | 5909.74 | 0.00 | 0.00 | 22733.66 | 0.00 | |
Maximum of Months | 77797.91 | 13706.48 | 10740.89 | 0.00 | 0.00 | 9073.06 | 0.00 | 0.00 | 45404.50 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.33 | 20.50 | 0.00 | 20.50 | 0.17 | 21.82 | 0.00 | 21.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.47 | 0.00 | 24.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.48 | 0.00 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.00 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.48 | 0.00 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.47 | 0.00 | 24.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.48 | 0.00 | 24.48 |
December | 0.50 | 20.51 | 0.00 | 20.51 | 0.83 | 22.99 | 0.00 | 22.99 |
Annual Sum or Average | 1.50 | 20.49 | 0.00 | 20.49 | 10.33 | 23.97 | 0.00 | 23.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.47 | 0.00 | 20.47 |
Maximum of Months | 0.50 | 20.51 | 0.00 | 20.51 | 2.33 | 24.48 | 0.00 | 24.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.49 | 0.00 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.48 | 0.00 | 24.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.48 | 0.00 | 24.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.48 | 0.00 | 24.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.49 | 0.00 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 24.50 | 0.00 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 24.52 | 0.00 | 24.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 24.54 | 0.00 | 24.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 24.56 | 0.00 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 24.59 | 0.00 | 24.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 24.52 | 0.00 | 24.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 24.50 | 0.00 | 24.50 |
Annual Sum or Average | 0.00 | 0.00 | 215.33 | 24.54 | 0.00 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.48 | 0.00 | 24.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 24.59 | 0.00 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.46 | 0.00 | 24.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.48 | 0.00 | 24.48 |
March | 0.17 | 20.50 | 0.00 | 20.50 | 1.17 | 23.99 | 0.00 | 23.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.47 | 0.00 | 24.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 0.00 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.00 | 24.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.48 | 0.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 24.49 | 0.00 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 24.52 | 0.00 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 24.52 | 0.00 | 24.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.48 | 0.00 | 24.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.48 | 0.00 | 24.48 |
Annual Sum or Average | 0.17 | 20.50 | 0.00 | 20.50 | 62.67 | 24.49 | 0.00 | 24.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 23.99 | 0.00 | 23.99 |
Maximum of Months | 0.17 | 20.50 | 0.00 | 20.50 | 21.17 | 24.52 | 0.00 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.50 | 13.79 | 80.67 | 13.78 | 0.00 | 13.78 | 0.00 | 13.78 |
February | 46.33 | 13.27 | 45.83 | 13.27 | 0.00 | 13.27 | 0.00 | 13.27 |
March | 41.17 | 13.78 | 40.33 | 13.79 | 0.00 | 13.79 | 0.00 | 13.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.17 | 14.58 | 6.17 | 14.58 | 0.00 | 14.58 | 0.00 | 14.58 |
December | 46.83 | 12.96 | 46.83 | 12.96 | 0.00 | 12.96 | 0.00 | 12.96 |
Annual Sum or Average | 223.00 | 13.53 | 219.83 | 13.52 | 0.00 | 13.52 | 0.00 | 13.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.50 | 14.58 | 80.67 | 14.58 | 0.00 | 14.58 | 0.00 | 14.58 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 362.00 | 21.89 | 119.83 | 22.03 | 101.50 | 22.05 |
February | 282.33 | 22.20 | 148.83 | 22.40 | 97.33 | 22.35 |
March | 301.50 | 22.66 | 132.50 | 22.84 | 55.33 | 22.78 |
April | 130.50 | 23.61 | 204.83 | 23.78 | 22.50 | 23.79 |
May | 24.67 | 23.89 | 395.50 | 23.89 | 24.67 | 23.89 |
June | 1.17 | 23.89 | 384.83 | 23.89 | 1.17 | 23.89 |
July | 15.83 | 23.89 | 402.83 | 23.89 | 15.83 | 23.89 |
August | 0.00 | 0.00 | 410.17 | 23.89 | 0.00 | 23.89 |
September | 7.00 | 23.89 | 387.67 | 23.89 | 7.00 | 23.89 |
October | 68.67 | 23.72 | 293.67 | 23.86 | 17.83 | 23.86 |
November | 231.00 | 23.36 | 118.33 | 23.54 | 14.83 | 23.55 |
December | 312.00 | 22.24 | 141.00 | 22.45 | 74.00 | 22.40 |
Annual Sum or Average | 1736.67 | 22.59 | 3140.00 | 23.31 | 432.00 | 23.25 |
Minimum of Months | 0.00 | 0.00 | 118.33 | 22.03 | 0.00 | 22.05 |
Maximum of Months | 362.00 | 23.89 | 410.17 | 23.89 | 101.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 330.50 | 22.83 | 98.83 | 23.06 | 46.83 | 23.13 |
February | 231.67 | 23.04 | 176.50 | 23.39 | 57.17 | 23.43 |
March | 188.50 | 23.06 | 170.17 | 23.45 | 16.67 | 23.47 |
April | 54.17 | 23.77 | 290.00 | 23.87 | 22.83 | 23.87 |
May | 56.83 | 23.89 | 418.00 | 23.89 | 56.83 | 23.89 |
June | 22.33 | 23.89 | 408.00 | 23.89 | 22.33 | 23.89 |
July | 87.00 | 23.89 | 415.00 | 23.89 | 87.00 | 23.89 |
August | 67.50 | 23.89 | 422.00 | 23.89 | 67.50 | 23.89 |
September | 92.50 | 23.89 | 405.00 | 23.89 | 92.50 | 23.89 |
October | 100.33 | 23.86 | 345.50 | 23.89 | 85.83 | 23.89 |
November | 120.33 | 23.67 | 183.00 | 23.80 | 36.00 | 23.81 |
December | 256.50 | 22.97 | 141.17 | 23.30 | 38.00 | 23.35 |
Annual Sum or Average | 1608.17 | 23.28 | 3473.17 | 23.70 | 629.50 | 23.72 |
Minimum of Months | 22.33 | 22.83 | 98.83 | 23.06 | 16.67 | 23.13 |
Maximum of Months | 330.50 | 23.89 | 422.00 | 23.89 | 92.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 128.67 | 23.40 | 143.67 | 23.66 | 7.83 | 23.66 |
February | 117.67 | 23.42 | 190.83 | 23.69 | 15.33 | 23.69 |
March | 132.50 | 23.27 | 185.50 | 23.62 | 2.17 | 23.62 |
April | 28.67 | 23.79 | 270.17 | 23.88 | 0.00 | 23.88 |
May | 0.00 | 0.00 | 390.17 | 23.89 | 0.00 | 23.89 |
June | 0.00 | 0.00 | 381.33 | 23.89 | 0.00 | 23.89 |
July | 0.00 | 0.00 | 398.17 | 23.89 | 0.00 | 23.89 |
August | 0.00 | 0.00 | 406.83 | 23.89 | 0.00 | 23.89 |
September | 0.00 | 0.00 | 384.50 | 23.89 | 0.00 | 23.89 |
October | 6.67 | 23.80 | 356.83 | 23.89 | 0.00 | 23.89 |
November | 19.83 | 23.84 | 272.17 | 23.89 | 0.00 | 23.89 |
December | 111.17 | 23.44 | 202.50 | 23.73 | 9.50 | 23.74 |
Annual Sum or Average | 545.17 | 23.42 | 3582.67 | 23.83 | 34.83 | 23.83 |
Minimum of Months | 0.00 | 0.00 | 143.67 | 23.62 | 0.00 | 23.62 |
Maximum of Months | 132.50 | 23.84 | 406.83 | 23.89 | 15.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 192.33 | 22.90 | 121.33 | 23.27 | 10.50 | 23.27 |
February | 155.50 | 22.92 | 173.33 | 23.40 | 23.33 | 23.40 |
March | 174.17 | 22.74 | 162.33 | 23.26 | 8.83 | 23.24 |
April | 69.17 | 23.61 | 250.00 | 23.83 | 16.50 | 23.83 |
May | 25.67 | 23.89 | 390.50 | 23.89 | 25.67 | 23.89 |
June | 3.33 | 23.89 | 378.17 | 23.89 | 3.33 | 23.89 |
July | 16.17 | 23.89 | 395.50 | 23.89 | 16.17 | 23.89 |
August | 0.00 | 0.00 | 402.67 | 23.89 | 0.00 | 23.89 |
September | 0.00 | 0.00 | 382.00 | 23.89 | 0.00 | 23.89 |
October | 13.83 | 23.69 | 345.50 | 23.88 | 0.00 | 23.88 |
November | 35.33 | 23.61 | 248.33 | 23.86 | 1.83 | 23.86 |
December | 148.00 | 22.80 | 182.33 | 23.38 | 14.17 | 23.39 |
Annual Sum or Average | 833.50 | 23.01 | 3432.00 | 23.71 | 120.33 | 23.71 |
Minimum of Months | 0.00 | 0.00 | 121.33 | 23.26 | 0.00 | 23.24 |
Maximum of Months | 192.33 | 23.89 | 402.67 | 23.89 | 25.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 382.67 | 18.60 | 318.50 | 18.54 | 296.17 | 18.38 |
February | 353.83 | 20.20 | 260.33 | 20.19 | 248.83 | 20.13 |
March | 377.83 | 20.77 | 313.50 | 20.88 | 281.83 | 20.79 |
April | 350.33 | 24.21 | 281.17 | 24.80 | 239.00 | 25.00 |
May | 418.00 | 28.40 | 418.00 | 28.40 | 418.00 | 28.40 |
June | 408.00 | 29.05 | 408.00 | 29.05 | 408.00 | 29.05 |
July | 415.00 | 28.96 | 415.00 | 28.96 | 415.00 | 28.96 |
August | 422.00 | 28.92 | 422.00 | 28.92 | 422.00 | 28.92 |
September | 405.00 | 27.66 | 405.00 | 27.66 | 405.00 | 27.66 |
October | 363.17 | 27.19 | 360.67 | 27.42 | 323.50 | 27.59 |
November | 329.83 | 22.76 | 227.33 | 23.35 | 177.33 | 23.54 |
December | 378.83 | 20.20 | 286.33 | 20.29 | 258.83 | 20.21 |
Annual Sum or Average | 4604.50 | 24.93 | 4115.83 | 25.25 | 3893.50 | 25.37 |
Minimum of Months | 329.83 | 18.60 | 227.33 | 18.54 | 177.33 | 18.38 |
Maximum of Months | 422.00 | 29.05 | 422.00 | 29.05 | 422.00 | 29.05 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.14065 | 44.48550 | -0.1661 | 8.48109 |
February | 376.00000 | 22.61869 | 49.01876 | -0.0092 | 8.29215 |
March | 422.00000 | 23.01155 | 46.12603 | 0.07952 | 7.77795 |
April | 405.00000 | 23.79954 | 52.06929 | 0.36660 | 8.25155 |
May | 418.00000 | 23.89013 | 57.79607 | -0.3928 | 8.25535 |
June | 408.00000 | 23.89017 | 56.84182 | -0.3706 | 7.92258 |
July | 415.00000 | 23.89015 | 59.33914 | -0.3457 | 7.54302 |
August | 422.00000 | 23.89017 | 58.45582 | -0.3537 | 7.65246 |
September | 405.00000 | 23.89012 | 59.43432 | -0.3756 | 7.99455 |
October | 414.00000 | 23.86179 | 53.74060 | 0.45143 | 9.57412 |
November | 399.00000 | 23.58325 | 47.96679 | 0.26194 | 7.44795 |
December | 415.00000 | 22.64600 | 46.58278 | -0.0036 | 7.98518 |
Annual Sum or Average | 4913.00000 | 23.43008 | 52.68385 | -0.0734 | 8.09752 |
Minimum of Months | 376.00000 | 22.14065 | 44.48550 | -0.3928 | 7.44795 |
Maximum of Months | 422.00000 | 23.89017 | 59.43432 | 0.45143 | 9.57412 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.03933 | 46.30937 | 0.12948 | 7.06478 |
February | 376.00000 | 23.36449 | 50.02761 | 0.24952 | 8.15262 |
March | 422.00000 | 23.51683 | 47.40343 | 0.28706 | 8.08195 |
April | 405.00000 | 23.87336 | 53.08184 | 0.46477 | 9.72920 |
May | 418.00000 | 23.89260 | 60.09946 | -0.3118 | 7.05931 |
June | 408.00000 | 23.89286 | 60.02497 | -0.2927 | 6.82965 |
July | 415.00000 | 23.89362 | 62.95606 | -0.2719 | 6.57584 |
August | 422.00000 | 23.89340 | 62.10582 | -0.2812 | 6.68103 |
September | 405.00000 | 23.89306 | 62.72649 | -0.3000 | 6.91403 |
October | 414.00000 | 23.88433 | 56.33635 | 0.52008 | 10.87599 |
November | 399.00000 | 23.82266 | 49.82015 | 0.39996 | 8.72795 |
December | 415.00000 | 23.32255 | 48.51497 | 0.23690 | 7.81957 |
Annual Sum or Average | 4913.00000 | 23.69210 | 54.99114 | 0.06661 | 7.86835 |
Minimum of Months | 376.00000 | 23.03933 | 46.30937 | -0.3118 | 6.57584 |
Maximum of Months | 422.00000 | 23.89362 | 62.95606 | 0.52008 | 10.87599 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.73683 | 39.23611 | 0.33579 | 8.12108 |
February | 376.00000 | 23.74300 | 42.49468 | 0.36570 | 8.83378 |
March | 422.00000 | 23.69553 | 42.37820 | 0.33193 | 8.41019 |
April | 405.00000 | 23.88339 | 47.75711 | 0.45505 | 9.55180 |
May | 418.00000 | 23.89029 | 53.83392 | -0.3235 | 7.29926 |
June | 408.00000 | 23.89031 | 53.73102 | -0.3057 | 7.07901 |
July | 415.00000 | 23.89028 | 55.68475 | -0.2806 | 6.76785 |
August | 422.00000 | 23.89029 | 54.25381 | -0.2680 | 6.63641 |
September | 405.00000 | 23.89030 | 53.78240 | -0.2785 | 6.78461 |
October | 414.00000 | 23.88878 | 48.24818 | 0.55350 | 11.66608 |
November | 399.00000 | 23.88758 | 42.74424 | 0.47153 | 9.89854 |
December | 415.00000 | 23.77051 | 41.75080 | 0.38783 | 8.99003 |
Annual Sum or Average | 4913.00000 | 23.83832 | 48.03872 | 0.11741 | 8.32641 |
Minimum of Months | 376.00000 | 23.69553 | 39.23611 | -0.3235 | 6.63641 |
Maximum of Months | 422.00000 | 23.89031 | 55.68475 | 0.55350 | 11.66608 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.43079 | 41.90580 | 0.25180 | 7.72640 |
February | 376.00000 | 23.48653 | 45.46593 | 0.29567 | 8.60365 |
March | 422.00000 | 23.41476 | 45.31662 | 0.25703 | 8.27720 |
April | 405.00000 | 23.84202 | 51.22631 | 0.43591 | 9.31074 |
May | 418.00000 | 23.89015 | 57.13819 | -0.3438 | 7.56669 |
June | 408.00000 | 23.89018 | 56.64000 | -0.3288 | 7.37679 |
July | 415.00000 | 23.89014 | 58.77695 | -0.3008 | 7.00243 |
August | 422.00000 | 23.89016 | 56.99576 | -0.2929 | 6.91769 |
September | 405.00000 | 23.89015 | 56.75263 | -0.3020 | 7.05535 |
October | 414.00000 | 23.88356 | 49.97993 | 0.53335 | 11.22705 |
November | 399.00000 | 23.86496 | 44.53411 | 0.44745 | 9.48672 |
December | 415.00000 | 23.50203 | 44.09760 | 0.31184 | 8.58327 |
Annual Sum or Average | 4913.00000 | 23.74037 | 50.78325 | 0.07746 | 8.25322 |
Minimum of Months | 376.00000 | 23.41476 | 41.90580 | -0.3438 | 6.91769 |
Maximum of Months | 422.00000 | 23.89018 | 58.77695 | 0.53335 | 11.22705 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 19.04433 | 53.17396 | -0.5160 | 24.58122 |
February | 376.00000 | 20.40344 | 56.33055 | -0.2186 | 21.58038 |
March | 422.00000 | 21.19436 | 54.06868 | -0.1149 | 21.76743 |
April | 405.00000 | 24.34174 | 58.78786 | 0.57334 | 20.24951 |
May | 418.00000 | 28.40471 | 65.60306 | 0.92449 | 28.58502 |
June | 408.00000 | 29.05320 | 65.35864 | 1.12277 | 35.62342 |
July | 415.00000 | 28.95862 | 73.02890 | 1.19030 | 38.90676 |
August | 422.00000 | 28.91930 | 70.29386 | 1.18213 | 38.60408 |
September | 405.00000 | 27.66115 | 74.08140 | 0.86757 | 26.99654 |
October | 414.00000 | 26.86637 | 62.38978 | 1.24511 | 44.31344 |
November | 399.00000 | 23.00054 | 54.86289 | 0.37224 | 19.32326 |
December | 415.00000 | 20.53577 | 55.75250 | -0.1722 | 24.59915 |
Annual Sum or Average | 4913.00000 | 24.89968 | 62.02721 | 0.54328 | 28.86136 |
Minimum of Months | 376.00000 | 19.04433 | 53.17396 | -0.5160 | 19.32326 |
Maximum of Months | 422.00000 | 29.05320 | 74.08140 | 1.24511 | 44.31344 |
Report: DXReportMonthly
For: PSZ-AC:1 HP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.102365E+10 | 0.259183E+09 | 73.25 | 0.667507E+09 | 0.356144E+09 | 0.00 | 0.96 | 19-JAN-23:05 | 0.00 | 01-JAN-00:05 | 15199.09 | 19-JAN-23:05 | 9781.17 | 19-JAN-23:05 | 5417.92 | 19-JAN-23:05 | 3130.21 | 19-JAN-23:05 | 0.00 |
February | 0.160888E+10 | 0.406550E+09 | 111.86 | 0.106287E+10 | 0.546007E+09 | 0.00 | 0.95 | 28-FEB-22:40 | 0.00 | 01-FEB-00:05 | 14966.65 | 28-FEB-22:40 | 9782.30 | 28-FEB-22:40 | 5184.35 | 28-FEB-22:40 | 3094.95 | 28-FEB-22:40 | 0.00 |
March | 0.296146E+10 | 0.745081E+09 | 176.08 | 0.200605E+10 | 0.955416E+09 | 0.00 | 1.00 | 30-MAR-20:30 | 0.00 | 01-MAR-00:05 | 31770.14 | 30-MAR-21:25 | 15209.98 | 30-MAR-21:25 | 16560.17 | 30-MAR-21:25 | 6484.79 | 30-MAR-21:25 | 0.00 |
April | 0.759647E+10 | 0.188137E+10 | 371.19 | 0.552981E+10 | 0.206665E+10 | 0.00 | 1.00 | 14-APR-20:25 | 0.00 | 01-APR-00:10 | 32100.67 | 30-APR-18:35 | 22077.87 | 23-APR-07:02 | 14472.67 | 30-APR-18:35 | 6549.00 | 30-APR-18:35 | 0.00 |
May | 0.210670E+11 | 0.506110E+10 | 586.19 | 0.150511E+11 | 0.601592E+10 | 0.00 | 1.00 | 01-MAY-20:20 | 0.00 | 01-MAY-00:05 | 30383.48 | 07-MAY-18:53 | 24487.64 | 07-MAY-18:53 | 8520.03 | 24-MAY-20:20 | 7203.77 | 07-MAY-18:13 | 0.00 |
June | 0.235575E+11 | 0.561309E+10 | 593.08 | 0.169512E+11 | 0.660632E+10 | 0.00 | 1.00 | 01-JUN-00:20 | 0.00 | 01-JUN-00:05 | 31202.53 | 16-JUN-20:10 | 25740.13 | 13-JUN-20:10 | 8264.60 | 18-JUN-18:20 | 7156.38 | 11-JUN-18:10 | 0.00 |
July | 0.263826E+11 | 0.621365E+10 | 620.44 | 0.180527E+11 | 0.832995E+10 | 0.00 | 1.00 | 01-JUL-00:15 | 0.00 | 01-JUL-00:05 | 31289.04 | 20-JUL-20:10 | 24686.83 | 07-JUL-21:23 | 9254.27 | 04-JUL-18:10 | 7348.02 | 23-JUL-18:10 | 0.00 |
August | 0.260282E+11 | 0.612816E+10 | 630.46 | 0.180751E+11 | 0.795305E+10 | 0.00 | 1.00 | 01-AUG-00:20 | 0.00 | 01-AUG-00:05 | 31869.86 | 10-AUG-20:10 | 26741.69 | 03-AUG-21:23 | 9778.09 | 10-AUG-20:10 | 7328.87 | 24-AUG-20:10 | 0.00 |
September | 0.220197E+11 | 0.517070E+10 | 585.26 | 0.148498E+11 | 0.716987E+10 | 0.00 | 1.00 | 01-SEP-00:15 | 0.00 | 01-SEP-00:05 | 30984.62 | 10-SEP-18:10 | 27207.91 | 11-SEP-02:63 | 9089.78 | 09-SEP-21:10 | 7651.75 | 09-SEP-21:10 | 0.00 |
October | 0.175112E+11 | 0.414810E+10 | 525.83 | 0.122728E+11 | 0.523839E+10 | 0.00 | 1.00 | 01-OCT-00:40 | 0.00 | 01-OCT-00:05 | 31732.67 | 06-OCT-20:10 | 29683.69 | 26-OCT-21:09 | 10741.56 | 01-OCT-01:23 | 6983.35 | 13-OCT-20:10 | 0.00 |
November | 0.502208E+10 | 0.122354E+10 | 264.09 | 0.341363E+10 | 0.160845E+10 | 0.00 | 1.00 | 01-NOV-20:25 | 0.00 | 01-NOV-00:05 | 31803.23 | 04-NOV-21:45 | 20073.54 | 08-NOV-00:13 | 14932.53 | 11-NOV-20:03 | 6489.17 | 04-NOV-21:45 | 0.00 |
December | 0.305469E+10 | 0.747317E+09 | 145.44 | 0.201269E+10 | 0.104200E+10 | 0.00 | 1.00 | 10-DEC-20:12 | 0.00 | 01-DEC-00:10 | 30782.86 | 17-DEC-08:61 | 20941.19 | 17-DEC-08:61 | 9841.66 | 17-DEC-08:61 | 6333.74 | 17-DEC-08:61 | 0.00 |
Annual Sum or Average | 0.157833E+12 | 0.375978E+11 | 4683.19 | 0.109945E+12 | 0.478882E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.102365E+10 | 0.259183E+09 | 73.25 | 0.667507E+09 | 0.356144E+09 | 0.00 | 0.95 | 0.00 | 14966.65 | 9781.17 | 5184.35 | 3094.95 | 0.00 | ||||||
Maximum of Months | 0.263826E+11 | 0.621365E+10 | 630.46 | 0.180751E+11 | 0.832995E+10 | 0.00 | 1.00 | 0.00 | 32100.67 | 29683.69 | 16560.17 | 7651.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2 HP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.110299E+11 | 0.302146E+10 | 112.86 | 0.676827E+10 | 0.426163E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 170861.08 | 20-JAN-07:03 | 107057.23 | 01-JAN-09:02 | 88035.19 | 19-JAN-07:03 | 39373.56 | 20-JAN-07:03 | 0.00 |
February | 0.170996E+11 | 0.463337E+10 | 147.79 | 0.105264E+11 | 0.657326E+10 | 0.00 | 1.00 | 01-FEB-07:03 | 0.00 | 01-FEB-00:05 | 173131.31 | 03-FEB-07:03 | 88936.58 | 28-FEB-07:02 | 86501.55 | 03-FEB-07:03 | 39723.28 | 03-FEB-07:03 | 0.00 |
March | 0.272752E+11 | 0.740873E+10 | 226.09 | 0.177684E+11 | 0.950679E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 176581.25 | 07-MAR-07:02 | 121342.46 | 27-MAR-06:02 | 85719.75 | 31-MAR-06:03 | 40167.74 | 07-MAR-07:02 | 0.00 |
April | 0.526150E+11 | 0.141828E+11 | 358.83 | 0.350583E+11 | 0.175568E+11 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:10 | 177895.69 | 01-APR-06:03 | 124007.62 | 23-APR-08:62 | 93115.25 | 01-APR-06:03 | 40884.08 | 29-APR-06:02 | 0.00 |
May | 0.102657E+12 | 0.270640E+11 | 437.57 | 0.638082E+11 | 0.388488E+11 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:05 | 180182.17 | 23-MAY-06:02 | 126191.40 | 12-MAY-06:02 | 76963.90 | 23-MAY-06:04 | 43068.31 | 28-MAY-08:62 | 0.00 |
June | 0.109989E+12 | 0.288286E+11 | 430.22 | 0.679330E+11 | 0.420559E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:05 | 178802.86 | 19-JUN-06:02 | 129548.72 | 12-JUN-06:02 | 71125.73 | 19-JUN-06:04 | 43400.11 | 18-JUN-08:62 | 0.00 |
July | 0.119811E+12 | 0.309154E+11 | 439.09 | 0.690188E+11 | 0.507925E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 179598.56 | 15-JUL-06:02 | 119037.63 | 19-JUL-06:02 | 74970.46 | 15-JUL-06:04 | 44123.83 | 09-JUL-08:62 | 0.00 |
August | 0.117291E+12 | 0.302992E+11 | 447.94 | 0.689056E+11 | 0.483850E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:05 | 179580.69 | 10-AUG-06:02 | 126256.85 | 04-AUG-06:02 | 73765.93 | 10-AUG-06:04 | 43464.19 | 06-AUG-08:62 | 0.00 |
September | 0.102066E+12 | 0.262100E+11 | 424.37 | 0.581244E+11 | 0.439418E+11 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 179288.60 | 27-SEP-06:02 | 123877.83 | 23-SEP-06:02 | 73655.05 | 27-SEP-06:04 | 45789.07 | 10-SEP-08:62 | 0.00 |
October | 0.845144E+11 | 0.220305E+11 | 400.06 | 0.515105E+11 | 0.330039E+11 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:05 | 180291.83 | 22-OCT-08:62 | 149067.69 | 27-OCT-06:02 | 77436.59 | 22-OCT-08:04 | 42726.81 | 07-OCT-06:02 | 0.00 |
November | 0.355217E+11 | 0.951453E+10 | 276.53 | 0.224691E+11 | 0.130526E+11 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:05 | 178248.03 | 02-NOV-06:02 | 124380.76 | 06-NOV-07:03 | 91813.81 | 04-NOV-06:04 | 41315.68 | 11-NOV-09:02 | 0.00 |
December | 0.223879E+11 | 0.599046E+10 | 176.90 | 0.137927E+11 | 0.859521E+10 | 0.00 | 1.00 | 09-DEC-07:03 | 0.00 | 01-DEC-00:10 | 177614.47 | 12-DEC-07:02 | 117226.04 | 11-DEC-07:02 | 70815.04 | 12-DEC-07:04 | 40290.37 | 15-DEC-07:02 | 0.00 |
Annual Sum or Average | 0.802258E+12 | 0.210099E+12 | 3878.24 | 0.485683E+12 | 0.316574E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.110299E+11 | 0.302146E+10 | 112.86 | 0.676827E+10 | 0.426163E+10 | 0.00 | 1.00 | 0.00 | 170861.08 | 88936.58 | 70815.04 | 39373.56 | 0.00 | ||||||
Maximum of Months | 0.119811E+12 | 0.309154E+11 | 447.94 | 0.690188E+11 | 0.507925E+11 | 0.00 | 1.00 | 0.00 | 180291.83 | 149067.69 | 93115.25 | 45789.07 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3 HP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.411890E+10 | 0.963923E+09 | 247.39 | 0.313909E+10 | 0.979810E+09 | 0.00 | 1.00 | 01-JAN-00:55 | 0.00 | 01-JAN-00:05 | 23471.42 | 29-JAN-20:42 | 16833.03 | 02-JAN-21:15 | 8326.19 | 01-JAN-00:55 | 4838.51 | 29-JAN-20:42 | 0.00 |
February | 0.530653E+10 | 0.122640E+10 | 289.75 | 0.397556E+10 | 0.133097E+10 | 0.00 | 1.00 | 01-FEB-21:15 | 0.00 | 01-FEB-00:05 | 24139.47 | 01-FEB-21:15 | 13272.23 | 27-FEB-21:10 | 12006.72 | 01-FEB-21:15 | 4954.53 | 01-FEB-21:15 | 0.00 |
March | 0.603226E+10 | 0.142244E+10 | 330.51 | 0.458465E+10 | 0.144761E+10 | 0.00 | 1.00 | 01-MAR-01:05 | 0.00 | 01-MAR-00:15 | 24345.27 | 28-MAR-20:15 | 16969.20 | 07-MAR-21:33 | 12316.64 | 28-MAR-20:15 | 4985.83 | 28-MAR-20:15 | 0.00 |
April | 0.956918E+10 | 0.229238E+10 | 483.81 | 0.725066E+10 | 0.231852E+10 | 0.00 | 1.00 | 02-APR-18:33 | 0.00 | 01-APR-00:10 | 23865.03 | 30-APR-21:45 | 21041.43 | 17-APR-20:15 | 9288.92 | 12-APR-21:45 | 4909.48 | 30-APR-21:45 | 0.00 |
May | 0.166314E+11 | 0.402872E+10 | 627.72 | 0.120292E+11 | 0.460213E+10 | 0.00 | 1.00 | 01-MAY-14:50 | 0.00 | 01-MAY-00:10 | 18491.10 | 25-MAY-20:10 | 14792.18 | 07-MAY-18:43 | 5031.85 | 24-MAY-15:00 | 4320.01 | 25-MAY-20:10 | 0.00 |
June | 0.173814E+11 | 0.421479E+10 | 616.57 | 0.125525E+11 | 0.482888E+10 | 0.00 | 1.00 | 01-JUN-20:15 | 0.00 | 01-JUN-00:05 | 19622.86 | 28-JUN-20:10 | 15255.12 | 28-JUN-20:10 | 5855.32 | 29-JUN-15:00 | 4542.12 | 28-JUN-20:10 | 0.00 |
July | 0.190863E+11 | 0.458897E+10 | 640.42 | 0.132316E+11 | 0.585468E+10 | 0.00 | 1.00 | 01-JUL-11:10 | 0.00 | 01-JUL-00:10 | 23162.13 | 07-JUL-20:43 | 18573.14 | 07-JUL-20:43 | 5639.50 | 22-JUL-11:00 | 5393.96 | 07-JUL-20:43 | 0.00 |
August | 0.199122E+11 | 0.475631E+10 | 647.87 | 0.141508E+11 | 0.576140E+10 | 0.00 | 1.00 | 01-AUG-11:02 | 0.00 | 01-AUG-00:05 | 23389.48 | 24-AUG-20:43 | 20145.32 | 30-AUG-21:23 | 5996.60 | 10-AUG-20:10 | 5509.39 | 24-AUG-20:43 | 0.00 |
September | 0.184223E+11 | 0.433711E+10 | 620.91 | 0.130004E+11 | 0.542192E+10 | 0.00 | 1.00 | 01-SEP-10:00 | 0.00 | 01-SEP-00:33 | 23430.07 | 10-SEP-18:08 | 20576.91 | 10-SEP-21:23 | 5772.40 | 18-SEP-14:10 | 5866.57 | 09-SEP-21:43 | 0.00 |
October | 0.174051E+11 | 0.408499E+10 | 600.51 | 0.130733E+11 | 0.433185E+10 | 0.00 | 1.00 | 01-OCT-03:22 | 0.00 | 01-OCT-00:25 | 24073.27 | 06-OCT-20:08 | 21251.63 | 26-OCT-04:51 | 7923.57 | 17-OCT-21:25 | 5359.05 | 13-OCT-20:08 | 0.00 |
November | 0.961640E+10 | 0.223220E+10 | 468.99 | 0.743688E+10 | 0.217952E+10 | 0.00 | 1.00 | 01-NOV-12:50 | 0.00 | 01-NOV-00:10 | 24046.26 | 20-NOV-21:15 | 21221.60 | 22-NOV-21:15 | 10496.26 | 20-NOV-21:15 | 5022.47 | 07-NOV-21:43 | 0.00 |
December | 0.661804E+10 | 0.153104E+10 | 340.06 | 0.506377E+10 | 0.155427E+10 | 0.00 | 1.00 | 01-DEC-21:15 | 0.00 | 01-DEC-00:10 | 23594.01 | 31-DEC-20:03 | 17585.03 | 07-DEC-21:15 | 10002.92 | 28-DEC-00:35 | 4861.39 | 31-DEC-20:03 | 0.00 |
Annual Sum or Average | 0.150100E+12 | 0.356793E+11 | 5914.52 | 0.109488E+12 | 0.406116E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.411890E+10 | 0.963923E+09 | 247.39 | 0.313909E+10 | 0.979810E+09 | 0.00 | 1.00 | 0.00 | 18491.10 | 13272.23 | 5031.85 | 4320.01 | 0.00 | ||||||
Maximum of Months | 0.199122E+11 | 0.475631E+10 | 647.87 | 0.141508E+11 | 0.585468E+10 | 0.00 | 1.00 | 0.00 | 24345.27 | 21251.63 | 12316.64 | 5866.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4 HP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.263053E+10 | 0.621247E+09 | 200.62 | 0.186528E+10 | 0.765251E+09 | 0.00 | 1.00 | 01-JAN-06:45 | 0.00 | 01-JAN-00:05 | 20409.60 | 17-JAN-22:45 | 13067.66 | 29-JAN-19:22 | 10709.32 | 17-JAN-22:45 | 4178.39 | 17-JAN-22:45 | 0.00 |
February | 0.342742E+10 | 0.796391E+09 | 222.64 | 0.237577E+10 | 0.105165E+10 | 0.00 | 1.00 | 01-FEB-01:25 | 0.00 | 01-FEB-00:05 | 20318.45 | 21-FEB-23:05 | 11002.30 | 09-FEB-21:33 | 10721.65 | 21-FEB-23:05 | 4164.89 | 21-FEB-23:05 | 0.00 |
March | 0.393634E+10 | 0.939689E+09 | 262.63 | 0.275911E+10 | 0.117722E+10 | 0.00 | 1.00 | 01-MAR-01:23 | 0.00 | 01-MAR-00:05 | 20541.81 | 27-MAR-21:35 | 13749.79 | 24-MAR-21:01 | 10757.71 | 27-MAR-21:35 | 4197.05 | 27-MAR-21:35 | 0.00 |
April | 0.635570E+10 | 0.154129E+10 | 413.66 | 0.447831E+10 | 0.187739E+10 | 0.00 | 1.00 | 03-APR-20:45 | 0.00 | 01-APR-00:10 | 20484.62 | 15-APR-23:15 | 16831.67 | 17-APR-20:25 | 10597.85 | 15-APR-23:15 | 4189.11 | 15-APR-23:15 | 0.00 |
May | 0.127669E+11 | 0.309590E+10 | 603.00 | 0.858263E+10 | 0.418425E+10 | 0.00 | 1.00 | 01-MAY-20:15 | 0.00 | 01-MAY-00:05 | 15791.42 | 07-MAY-18:43 | 12553.08 | 07-MAY-18:43 | 4730.58 | 23-MAY-20:20 | 3557.19 | 07-MAY-18:43 | 0.00 |
June | 0.136382E+11 | 0.330020E+10 | 600.61 | 0.916197E+10 | 0.447619E+10 | 0.00 | 1.00 | 02-JUN-20:55 | 0.00 | 01-JUN-00:05 | 16439.27 | 29-JUN-20:10 | 11802.78 | 28-JUN-20:10 | 5565.51 | 29-JUN-20:10 | 3774.93 | 28-JUN-20:10 | 0.00 |
July | 0.153419E+11 | 0.367108E+10 | 631.03 | 0.987073E+10 | 0.547119E+10 | 0.00 | 1.00 | 01-JUL-11:40 | 0.00 | 01-JUL-00:10 | 19847.13 | 07-JUL-20:43 | 14866.99 | 19-JUL-20:43 | 5528.30 | 10-JUL-20:10 | 4602.26 | 07-JUL-20:43 | 0.00 |
August | 0.160916E+11 | 0.383135E+10 | 643.51 | 0.106645E+11 | 0.542712E+10 | 0.00 | 1.00 | 01-AUG-11:40 | 0.00 | 01-AUG-00:05 | 20079.30 | 31-AUG-20:43 | 16388.55 | 30-AUG-21:23 | 6358.70 | 10-AUG-20:10 | 4624.93 | 24-AUG-20:43 | 0.00 |
September | 0.146936E+11 | 0.345672E+10 | 612.91 | 0.963142E+10 | 0.506214E+10 | 0.00 | 1.00 | 01-SEP-10:10 | 0.00 | 01-SEP-00:33 | 19656.97 | 01-SEP-20:43 | 17075.60 | 10-SEP-22:03 | 5586.14 | 18-SEP-14:10 | 4919.52 | 09-SEP-21:43 | 0.00 |
October | 0.139417E+11 | 0.326911E+10 | 584.22 | 0.984139E+10 | 0.410030E+10 | 0.00 | 1.00 | 01-OCT-02:41 | 0.00 | 01-OCT-00:05 | 20348.36 | 24-OCT-20:43 | 17232.94 | 26-OCT-04:51 | 7142.15 | 29-OCT-22:25 | 4498.31 | 13-OCT-20:08 | 0.00 |
November | 0.695571E+10 | 0.162150E+10 | 404.11 | 0.505460E+10 | 0.190111E+10 | 0.00 | 1.00 | 01-NOV-20:55 | 0.00 | 01-NOV-00:05 | 20320.70 | 20-NOV-21:25 | 15406.04 | 12-NOV-20:01 | 9738.58 | 20-NOV-21:25 | 4360.81 | 07-NOV-21:43 | 0.00 |
December | 0.461306E+10 | 0.107064E+10 | 283.84 | 0.332052E+10 | 0.129254E+10 | 0.00 | 1.00 | 01-DEC-21:15 | 0.00 | 01-DEC-00:10 | 20209.74 | 08-DEC-21:40 | 19086.91 | 17-DEC-20:07 | 9505.50 | 08-DEC-21:15 | 4148.12 | 08-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.114393E+12 | 0.272151E+11 | 5462.78 | 0.776063E+11 | 0.367864E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.263053E+10 | 0.621247E+09 | 200.62 | 0.186528E+10 | 0.765251E+09 | 0.00 | 1.00 | 0.00 | 15791.42 | 11002.30 | 4730.58 | 3557.19 | 0.00 | ||||||
Maximum of Months | 0.160916E+11 | 0.383135E+10 | 643.51 | 0.106645E+11 | 0.547119E+10 | 0.00 | 1.00 | 0.00 | 20541.81 | 19086.91 | 10757.71 | 4919.52 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.64 | 22.98 | 11.66 | 45.95 | 43.48 | 10.50 | 0.00 | 0.00 |
February | 45.11 | 31.09 | 14.01 | 61.92 | 38.95 | 2.17 | 0.00 | 0.00 |
March | 49.18 | 30.69 | 18.49 | 69.99 | 33.23 | 1.00 | 0.00 | 0.00 |
April | 63.29 | 41.50 | 21.79 | 97.29 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 60.49 | 34.88 | 25.61 | 103.07 | 10.08 | 0.00 | 0.00 | 0.00 |
June | 66.85 | 39.00 | 27.85 | 115.22 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 62.17 | 32.37 | 29.81 | 107.26 | 7.94 | 0.00 | 0.00 | 0.00 |
August | 57.85 | 29.25 | 28.60 | 100.49 | 9.45 | 0.00 | 0.00 | 0.00 |
September | 49.58 | 25.02 | 24.55 | 83.93 | 11.40 | 0.00 | 0.00 | 0.00 |
October | 46.37 | 27.49 | 18.88 | 77.10 | 17.07 | 0.00 | 0.00 | 0.00 |
November | 37.82 | 25.86 | 11.96 | 54.34 | 33.48 | 2.17 | 0.00 | 0.00 |
December | 31.62 | 20.74 | 10.88 | 43.08 | 38.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.41 | 30.03 | 20.38 | 80.03 | 23.10 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 31.62 | 20.74 | 10.88 | 43.08 | 7.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.85 | 41.50 | 29.81 | 115.22 | 43.48 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 739.55 | 528.28 | 211.27 | 1329.49 | 378.04 | 0.00 | 0.00 | 0.00 |
February | 655.68 | 420.05 | 235.63 | 1227.09 | 319.54 | 0.00 | 0.00 | 0.00 |
March | 404.88 | 170.86 | 234.01 | 808.10 | 271.17 | 0.00 | 0.00 | 0.00 |
April | 298.06 | 56.02 | 242.04 | 655.75 | 174.17 | 0.00 | 0.00 | 0.00 |
May | 236.92 | 5.66 | 231.26 | 592.29 | 36.04 | 0.00 | 0.00 | 0.00 |
June | 237.21 | 0.85 | 236.37 | 594.02 | 30.35 | 0.00 | 0.00 | 0.00 |
July | 247.46 | 2.29 | 245.17 | 623.55 | 16.70 | 0.00 | 0.00 | 0.00 |
August | 284.54 | 25.97 | 258.57 | 727.17 | 31.81 | 0.00 | 0.00 | 0.00 |
September | 337.61 | 77.97 | 259.64 | 818.23 | 49.46 | 0.00 | 0.00 | 0.00 |
October | 530.85 | 268.79 | 262.06 | 1169.87 | 106.77 | 0.00 | 0.00 | 0.00 |
November | 693.62 | 476.80 | 216.82 | 1328.81 | 248.93 | 0.00 | 0.00 | 0.00 |
December | 727.88 | 525.03 | 202.86 | 1332.07 | 330.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 448.46 | 212.18 | 236.29 | 932.39 | 165.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 236.92 | 0.85 | 202.86 | 592.29 | 16.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 739.55 | 528.28 | 262.06 | 1332.07 | 378.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 739.55 | 528.28 | 211.27 | 1325.32 | 370.47 | 0.00 | 0.00 | 0.00 |
February | 655.68 | 420.05 | 235.63 | 1221.94 | 313.51 | 0.00 | 0.00 | 0.00 |
March | 404.88 | 170.86 | 234.01 | 802.49 | 265.51 | 0.00 | 0.00 | 0.00 |
April | 298.06 | 56.02 | 242.04 | 646.04 | 173.50 | 0.00 | 0.00 | 0.00 |
May | 236.92 | 5.66 | 231.26 | 580.25 | 36.22 | 0.00 | 0.00 | 0.00 |
June | 237.21 | 0.85 | 236.37 | 581.51 | 30.26 | 0.00 | 0.00 | 0.00 |
July | 247.46 | 2.29 | 245.17 | 611.33 | 16.78 | 0.00 | 0.00 | 0.00 |
August | 284.54 | 25.97 | 258.57 | 714.87 | 31.84 | 0.00 | 0.00 | 0.00 |
September | 337.61 | 77.97 | 259.64 | 806.89 | 49.98 | 0.00 | 0.00 | 0.00 |
October | 530.85 | 268.79 | 262.06 | 1158.64 | 107.49 | 0.00 | 0.00 | 0.00 |
November | 693.62 | 476.80 | 216.82 | 1319.46 | 250.99 | 0.00 | 0.00 | 0.00 |
December | 727.88 | 525.03 | 202.86 | 1326.99 | 325.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 448.46 | 212.18 | 236.29 | 923.15 | 163.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 236.92 | 0.85 | 202.86 | 580.25 | 16.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 739.55 | 528.28 | 262.06 | 1326.99 | 370.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.15 | 108.69 | 43.47 | 279.66 | 67.53 | 0.00 | 0.00 | 0.00 |
February | 134.90 | 86.42 | 48.48 | 255.59 | 58.68 | 0.00 | 0.00 | 0.00 |
March | 83.30 | 35.15 | 48.15 | 167.52 | 50.20 | 0.00 | 0.00 | 0.00 |
April | 61.32 | 11.53 | 49.80 | 129.05 | 35.49 | 0.00 | 0.00 | 0.00 |
May | 48.74 | 1.16 | 47.58 | 103.50 | 12.22 | 0.00 | 0.00 | 0.00 |
June | 48.80 | 0.17 | 48.63 | 101.76 | 11.64 | 0.00 | 0.00 | 0.00 |
July | 50.91 | 0.47 | 50.44 | 106.67 | 8.25 | 4.50 | 0.00 | 0.00 |
August | 58.54 | 5.34 | 53.20 | 128.18 | 12.73 | 10.50 | 0.00 | 0.00 |
September | 69.46 | 16.04 | 53.42 | 151.33 | 16.37 | 0.00 | 0.00 | 0.00 |
October | 109.22 | 55.30 | 53.92 | 225.96 | 28.39 | 3.67 | 0.00 | 0.00 |
November | 142.70 | 98.09 | 44.61 | 269.39 | 50.08 | 0.00 | 0.00 | 0.00 |
December | 149.75 | 108.02 | 41.74 | 275.71 | 60.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.27 | 43.65 | 48.61 | 182.48 | 34.22 | 18.67 | 0.00 | 0.00 |
Minimum of Months | 48.74 | 0.17 | 41.74 | 101.76 | 8.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.15 | 108.69 | 53.92 | 279.66 | 67.53 | 10.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92770509.16 | 61539878.07 | 31230631.09 | 0.123070E+09 | 0.116467E+09 |
February | 0.109119E+09 | 75218720.96 | 33900484.32 | 0.149798E+09 | 94226703.77 |
March | 0.131726E+09 | 82207281.02 | 49518951.41 | 0.187461E+09 | 89003098.53 |
April | 0.164053E+09 | 0.107578E+09 | 56474850.22 | 0.252184E+09 | 63128833.12 |
May | 0.162025E+09 | 93435019.46 | 68589970.86 | 0.276070E+09 | 26987381.33 |
June | 0.173279E+09 | 0.101079E+09 | 72199626.63 | 0.298640E+09 | 25745891.61 |
July | 0.166521E+09 | 86686837.35 | 79834098.41 | 0.287283E+09 | 21276527.43 |
August | 0.154933E+09 | 78330362.24 | 76602424.71 | 0.269144E+09 | 25314058.22 |
September | 0.128504E+09 | 64862021.49 | 63642361.50 | 0.217542E+09 | 29557894.03 |
October | 0.124200E+09 | 73623273.23 | 50576974.20 | 0.206493E+09 | 45709470.17 |
November | 98030315.95 | 67027400.21 | 31002915.74 | 0.140853E+09 | 86780157.53 |
December | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 0.104285E+09 |
Annual Sum or Average | 0.158986E+10 | 0.947148E+09 | 0.642716E+09 | 0.252393E+10 | 0.728482E+09 |
Minimum of Months | 84702905.56 | 55559913.11 | 29142992.46 | 0.115398E+09 | 21276527.43 |
Maximum of Months | 0.173279E+09 | 0.107578E+09 | 79834098.41 | 0.298640E+09 | 0.116467E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198080E+10 | 0.141494E+10 | 0.565865E+09 | 0.356090E+10 | 0.101253E+10 |
February | 0.158622E+10 | 0.101619E+10 | 0.570029E+09 | 0.296857E+10 | 0.773022E+09 |
March | 0.108442E+10 | 0.457642E+09 | 0.626781E+09 | 0.216443E+10 | 0.726309E+09 |
April | 0.772570E+09 | 0.145214E+09 | 0.627357E+09 | 0.169971E+10 | 0.451448E+09 |
May | 0.634579E+09 | 15160357.97 | 0.619419E+09 | 0.158638E+10 | 96520454.67 |
June | 0.614858E+09 | 2198858.57 | 0.612660E+09 | 0.153971E+10 | 78662337.19 |
July | 0.662804E+09 | 6130424.75 | 0.656673E+09 | 0.167011E+10 | 44722477.40 |
August | 0.762109E+09 | 69567760.52 | 0.692542E+09 | 0.194765E+10 | 85187278.83 |
September | 0.875082E+09 | 0.202096E+09 | 0.672986E+09 | 0.212085E+10 | 0.128188E+09 |
October | 0.142183E+10 | 0.719935E+09 | 0.701898E+09 | 0.313339E+10 | 0.285986E+09 |
November | 0.179785E+10 | 0.123586E+10 | 0.561999E+09 | 0.344427E+10 | 0.645234E+09 |
December | 0.194956E+10 | 0.140623E+10 | 0.543333E+09 | 0.356781E+10 | 0.885267E+09 |
Annual Sum or Average | 0.141427E+11 | 0.669116E+10 | 0.745154E+10 | 0.294038E+11 | 0.521308E+10 |
Minimum of Months | 0.614858E+09 | 2198858.57 | 0.543333E+09 | 0.153971E+10 | 44722477.40 |
Maximum of Months | 0.198080E+10 | 0.141494E+10 | 0.701898E+09 | 0.356781E+10 | 0.101253E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198080E+10 | 0.141494E+10 | 0.565865E+09 | 0.354973E+10 | 0.992260E+09 |
February | 0.158622E+10 | 0.101619E+10 | 0.570029E+09 | 0.295612E+10 | 0.758436E+09 |
March | 0.108442E+10 | 0.457642E+09 | 0.626781E+09 | 0.214938E+10 | 0.711148E+09 |
April | 0.772570E+09 | 0.145214E+09 | 0.627357E+09 | 0.167454E+10 | 0.449707E+09 |
May | 0.634579E+09 | 15160357.97 | 0.619419E+09 | 0.155415E+10 | 96999049.83 |
June | 0.614858E+09 | 2198858.57 | 0.612660E+09 | 0.150727E+10 | 78440396.46 |
July | 0.662804E+09 | 6130424.75 | 0.656673E+09 | 0.163739E+10 | 44952160.76 |
August | 0.762109E+09 | 69567760.52 | 0.692542E+09 | 0.191470E+10 | 85281405.79 |
September | 0.875082E+09 | 0.202096E+09 | 0.672986E+09 | 0.209145E+10 | 0.129546E+09 |
October | 0.142183E+10 | 0.719935E+09 | 0.701898E+09 | 0.310331E+10 | 0.287909E+09 |
November | 0.179785E+10 | 0.123586E+10 | 0.561999E+09 | 0.342005E+10 | 0.650568E+09 |
December | 0.194956E+10 | 0.140623E+10 | 0.543333E+09 | 0.355421E+10 | 0.872455E+09 |
Annual Sum or Average | 0.141427E+11 | 0.669116E+10 | 0.745154E+10 | 0.291123E+11 | 0.515770E+10 |
Minimum of Months | 0.614858E+09 | 2198858.57 | 0.543333E+09 | 0.150727E+10 | 44952160.76 |
Maximum of Months | 0.198080E+10 | 0.141494E+10 | 0.701898E+09 | 0.355421E+10 | 0.992260E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407525E+09 | 0.291106E+09 | 0.116419E+09 | 0.749038E+09 | 0.180883E+09 |
February | 0.326344E+09 | 0.209068E+09 | 0.117276E+09 | 0.618318E+09 | 0.141953E+09 |
March | 0.223106E+09 | 94154079.26 | 0.128952E+09 | 0.448692E+09 | 0.134445E+09 |
April | 0.158946E+09 | 29875888.83 | 0.129070E+09 | 0.334507E+09 | 91985674.17 |
May | 0.130556E+09 | 3119054.00 | 0.127437E+09 | 0.277205E+09 | 32735302.25 |
June | 0.126499E+09 | 452387.64 | 0.126046E+09 | 0.263764E+09 | 30176908.14 |
July | 0.136363E+09 | 1261258.20 | 0.135102E+09 | 0.285716E+09 | 22108938.13 |
August | 0.156794E+09 | 14312696.47 | 0.142481E+09 | 0.343308E+09 | 34099848.47 |
September | 0.180037E+09 | 41578792.23 | 0.138458E+09 | 0.392242E+09 | 42430697.06 |
October | 0.292524E+09 | 0.148118E+09 | 0.144406E+09 | 0.605202E+09 | 76052809.73 |
November | 0.369886E+09 | 0.254262E+09 | 0.115624E+09 | 0.698252E+09 | 0.129808E+09 |
December | 0.401097E+09 | 0.289314E+09 | 0.111784E+09 | 0.738471E+09 | 0.162602E+09 |
Annual Sum or Average | 0.290968E+10 | 0.137662E+10 | 0.153305E+10 | 0.575471E+10 | 0.107928E+10 |
Minimum of Months | 0.126499E+09 | 452387.64 | 0.111784E+09 | 0.263764E+09 | 22108938.13 |
Maximum of Months | 0.407525E+09 | 0.291106E+09 | 0.144406E+09 | 0.749038E+09 | 0.180883E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 735.18 | 695.74 | 554.18 | 367.62 | 186.56 | 0.00 | 0.00 |
February | 990.72 | 623.19 | 721.69 | 497.48 | 224.21 | 0.00 | 0.00 |
March | 1119.84 | 531.68 | 786.90 | 491.08 | 295.81 | 0.00 | 0.00 |
April | 1556.69 | 389.68 | 1012.67 | 664.06 | 348.61 | 0.00 | 0.00 |
May | 1649.17 | 161.21 | 967.89 | 558.15 | 409.74 | 0.00 | 0.00 |
June | 1843.45 | 158.93 | 1069.62 | 623.95 | 445.68 | 0.00 | 0.00 |
July | 1716.15 | 127.10 | 994.75 | 517.84 | 476.91 | 0.00 | 0.00 |
August | 1607.79 | 151.22 | 925.52 | 467.92 | 457.60 | 0.00 | 0.00 |
September | 1342.85 | 182.46 | 793.24 | 400.38 | 392.85 | 0.00 | 0.00 |
October | 1233.53 | 273.06 | 741.94 | 439.80 | 302.13 | 0.00 | 0.00 |
November | 869.46 | 535.68 | 605.13 | 413.75 | 191.38 | 0.00 | 0.00 |
December | 689.35 | 622.97 | 505.99 | 331.90 | 174.09 | 0.00 | 0.00 |
Annual Sum or Average | 1280.53 | 369.60 | 806.63 | 480.54 | 326.09 | 0.00 | 0.00 |
Minimum of Months | 689.35 | 127.10 | 505.99 | 331.90 | 174.09 | 0.00 | 0.00 |
Maximum of Months | 1843.45 | 695.74 | 1069.62 | 664.06 | 476.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1329.49 | 378.04 | 739.55 | 528.28 | 211.27 | 0.00 | 0.00 |
February | 1227.09 | 319.54 | 655.68 | 420.05 | 235.63 | 0.00 | 0.00 |
March | 808.10 | 271.17 | 404.88 | 170.86 | 234.01 | 0.00 | 0.00 |
April | 655.75 | 174.17 | 298.06 | 56.02 | 242.04 | 0.00 | 0.00 |
May | 592.29 | 36.04 | 236.92 | 5.66 | 231.26 | 0.00 | 0.00 |
June | 594.02 | 30.35 | 237.21 | 0.85 | 236.37 | 0.00 | 0.00 |
July | 623.55 | 16.70 | 247.46 | 2.29 | 245.17 | 0.00 | 0.00 |
August | 727.17 | 31.81 | 284.54 | 25.97 | 258.57 | 0.00 | 0.00 |
September | 818.23 | 49.46 | 337.61 | 77.97 | 259.64 | 0.00 | 0.00 |
October | 1169.87 | 106.77 | 530.85 | 268.79 | 262.06 | 0.00 | 0.00 |
November | 1328.81 | 248.93 | 693.62 | 476.80 | 216.82 | 0.00 | 0.00 |
December | 1332.07 | 330.52 | 727.88 | 525.03 | 202.86 | 0.00 | 0.00 |
Annual Sum or Average | 932.39 | 165.31 | 448.46 | 212.18 | 236.29 | 0.00 | 0.00 |
Minimum of Months | 592.29 | 16.70 | 236.92 | 0.85 | 202.86 | 0.00 | 0.00 |
Maximum of Months | 1332.07 | 378.04 | 739.55 | 528.28 | 262.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1325.32 | 370.47 | 739.55 | 528.28 | 211.27 | 0.00 | 0.00 |
February | 1221.94 | 313.51 | 655.68 | 420.05 | 235.63 | 0.00 | 0.00 |
March | 802.49 | 265.51 | 404.88 | 170.86 | 234.01 | 0.00 | 0.00 |
April | 646.04 | 173.50 | 298.06 | 56.02 | 242.04 | 0.00 | 0.00 |
May | 580.25 | 36.22 | 236.92 | 5.66 | 231.26 | 0.00 | 0.00 |
June | 581.51 | 30.26 | 237.21 | 0.85 | 236.37 | 0.00 | 0.00 |
July | 611.33 | 16.78 | 247.46 | 2.29 | 245.17 | 0.00 | 0.00 |
August | 714.87 | 31.84 | 284.54 | 25.97 | 258.57 | 0.00 | 0.00 |
September | 806.89 | 49.98 | 337.61 | 77.97 | 259.64 | 0.00 | 0.00 |
October | 1158.64 | 107.49 | 530.85 | 268.79 | 262.06 | 0.00 | 0.00 |
November | 1319.46 | 250.99 | 693.62 | 476.80 | 216.82 | 0.00 | 0.00 |
December | 1326.99 | 325.74 | 727.88 | 525.03 | 202.86 | 0.00 | 0.00 |
Annual Sum or Average | 923.15 | 163.55 | 448.46 | 212.18 | 236.29 | 0.00 | 0.00 |
Minimum of Months | 580.25 | 16.78 | 236.92 | 0.85 | 202.86 | 0.00 | 0.00 |
Maximum of Months | 1326.99 | 370.47 | 739.55 | 528.28 | 262.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 279.66 | 67.53 | 152.15 | 108.69 | 43.47 | 0.00 | 0.00 |
February | 255.59 | 58.68 | 134.90 | 86.42 | 48.48 | 0.00 | 0.00 |
March | 167.52 | 50.20 | 83.30 | 35.15 | 48.15 | 0.00 | 0.00 |
April | 129.05 | 35.49 | 61.32 | 11.53 | 49.80 | 0.00 | 0.00 |
May | 103.50 | 12.22 | 48.74 | 1.16 | 47.58 | 0.00 | 0.00 |
June | 101.76 | 11.64 | 48.80 | 0.17 | 48.63 | 0.00 | 0.00 |
July | 106.67 | 8.25 | 50.91 | 0.47 | 50.44 | 0.00 | 0.00 |
August | 128.18 | 12.73 | 58.54 | 5.34 | 53.20 | 0.00 | 0.00 |
September | 151.33 | 16.37 | 69.46 | 16.04 | 53.42 | 0.00 | 0.00 |
October | 225.96 | 28.39 | 109.22 | 55.30 | 53.92 | 0.00 | 0.00 |
November | 269.39 | 50.08 | 142.70 | 98.09 | 44.61 | 0.00 | 0.00 |
December | 275.71 | 60.71 | 149.75 | 108.02 | 41.74 | 0.00 | 0.00 |
Annual Sum or Average | 182.48 | 34.22 | 92.27 | 43.65 | 48.61 | 0.00 | 0.00 |
Minimum of Months | 101.76 | 8.25 | 48.74 | 0.17 | 41.74 | 0.00 | 0.00 |
Maximum of Months | 279.66 | 67.53 | 152.15 | 108.69 | 53.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196911E+10 | 0.186347E+10 | 0.148433E+10 | 0.984638E+09 | 0.499690E+09 | 0.00 | 0.00 |
February | 0.239676E+10 | 0.150763E+10 | 0.174591E+10 | 0.120350E+10 | 0.542408E+09 | 0.00 | 0.00 |
March | 0.299937E+10 | 0.142405E+10 | 0.210762E+10 | 0.131532E+10 | 0.792303E+09 | 0.00 | 0.00 |
April | 0.403495E+10 | 0.101006E+10 | 0.262484E+10 | 0.172125E+10 | 0.903598E+09 | 0.00 | 0.00 |
May | 0.441712E+10 | 0.431798E+09 | 0.259240E+10 | 0.149496E+10 | 0.109744E+10 | 0.00 | 0.00 |
June | 0.477824E+10 | 0.411934E+09 | 0.277246E+10 | 0.161727E+10 | 0.115519E+10 | 0.00 | 0.00 |
July | 0.459652E+10 | 0.340424E+09 | 0.266433E+10 | 0.138699E+10 | 0.127735E+10 | 0.00 | 0.00 |
August | 0.430630E+10 | 0.405025E+09 | 0.247892E+10 | 0.125329E+10 | 0.122564E+10 | 0.00 | 0.00 |
September | 0.348068E+10 | 0.472926E+09 | 0.205607E+10 | 0.103779E+10 | 0.101828E+10 | 0.00 | 0.00 |
October | 0.330389E+10 | 0.731352E+09 | 0.198720E+10 | 0.117797E+10 | 0.809232E+09 | 0.00 | 0.00 |
November | 0.225364E+10 | 0.138848E+10 | 0.156849E+10 | 0.107244E+10 | 0.496047E+09 | 0.00 | 0.00 |
December | 0.184636E+10 | 0.166856E+10 | 0.135525E+10 | 0.888959E+09 | 0.466288E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.403829E+11 | 0.116557E+11 | 0.254378E+11 | 0.151544E+11 | 0.102835E+11 | 0.00 | 0.00 |
Minimum of Months | 0.184636E+10 | 0.340424E+09 | 0.135525E+10 | 0.888959E+09 | 0.466288E+09 | 0.00 | 0.00 |
Maximum of Months | 0.477824E+10 | 0.186347E+10 | 0.277246E+10 | 0.172125E+10 | 0.127735E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.356090E+10 | 0.101253E+10 | 0.198080E+10 | 0.141494E+10 | 0.565865E+09 | 0.00 | 0.00 |
February | 0.296857E+10 | 0.773022E+09 | 0.158622E+10 | 0.101619E+10 | 0.570029E+09 | 0.00 | 0.00 |
March | 0.216443E+10 | 0.726309E+09 | 0.108442E+10 | 0.457642E+09 | 0.626781E+09 | 0.00 | 0.00 |
April | 0.169971E+10 | 0.451448E+09 | 0.772570E+09 | 0.145214E+09 | 0.627357E+09 | 0.00 | 0.00 |
May | 0.158638E+10 | 96520454.67 | 0.634579E+09 | 15160357.97 | 0.619419E+09 | 0.00 | 0.00 |
June | 0.153971E+10 | 78662337.19 | 0.614858E+09 | 2198858.57 | 0.612660E+09 | 0.00 | 0.00 |
July | 0.167011E+10 | 44722477.40 | 0.662804E+09 | 6130424.75 | 0.656673E+09 | 0.00 | 0.00 |
August | 0.194765E+10 | 85187278.83 | 0.762109E+09 | 69567760.52 | 0.692542E+09 | 0.00 | 0.00 |
September | 0.212085E+10 | 0.128188E+09 | 0.875082E+09 | 0.202096E+09 | 0.672986E+09 | 0.00 | 0.00 |
October | 0.313339E+10 | 0.285986E+09 | 0.142183E+10 | 0.719935E+09 | 0.701898E+09 | 0.00 | 0.00 |
November | 0.344427E+10 | 0.645234E+09 | 0.179785E+10 | 0.123586E+10 | 0.561999E+09 | 0.00 | 0.00 |
December | 0.356781E+10 | 0.885267E+09 | 0.194956E+10 | 0.140623E+10 | 0.543333E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.294038E+11 | 0.521308E+10 | 0.141427E+11 | 0.669116E+10 | 0.745154E+10 | 0.00 | 0.00 |
Minimum of Months | 0.153971E+10 | 44722477.40 | 0.614858E+09 | 2198858.57 | 0.543333E+09 | 0.00 | 0.00 |
Maximum of Months | 0.356781E+10 | 0.101253E+10 | 0.198080E+10 | 0.141494E+10 | 0.701898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.354973E+10 | 0.992260E+09 | 0.198080E+10 | 0.141494E+10 | 0.565865E+09 | 0.00 | 0.00 |
February | 0.295612E+10 | 0.758436E+09 | 0.158622E+10 | 0.101619E+10 | 0.570029E+09 | 0.00 | 0.00 |
March | 0.214938E+10 | 0.711148E+09 | 0.108442E+10 | 0.457642E+09 | 0.626781E+09 | 0.00 | 0.00 |
April | 0.167454E+10 | 0.449707E+09 | 0.772570E+09 | 0.145214E+09 | 0.627357E+09 | 0.00 | 0.00 |
May | 0.155415E+10 | 96999049.83 | 0.634579E+09 | 15160357.97 | 0.619419E+09 | 0.00 | 0.00 |
June | 0.150727E+10 | 78440396.46 | 0.614858E+09 | 2198858.57 | 0.612660E+09 | 0.00 | 0.00 |
July | 0.163739E+10 | 44952160.76 | 0.662804E+09 | 6130424.75 | 0.656673E+09 | 0.00 | 0.00 |
August | 0.191470E+10 | 85281405.79 | 0.762109E+09 | 69567760.52 | 0.692542E+09 | 0.00 | 0.00 |
September | 0.209145E+10 | 0.129546E+09 | 0.875082E+09 | 0.202096E+09 | 0.672986E+09 | 0.00 | 0.00 |
October | 0.310331E+10 | 0.287909E+09 | 0.142183E+10 | 0.719935E+09 | 0.701898E+09 | 0.00 | 0.00 |
November | 0.342005E+10 | 0.650568E+09 | 0.179785E+10 | 0.123586E+10 | 0.561999E+09 | 0.00 | 0.00 |
December | 0.355421E+10 | 0.872455E+09 | 0.194956E+10 | 0.140623E+10 | 0.543333E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.291123E+11 | 0.515770E+10 | 0.141427E+11 | 0.669116E+10 | 0.745154E+10 | 0.00 | 0.00 |
Minimum of Months | 0.150727E+10 | 44952160.76 | 0.614858E+09 | 2198858.57 | 0.543333E+09 | 0.00 | 0.00 |
Maximum of Months | 0.355421E+10 | 0.992260E+09 | 0.198080E+10 | 0.141494E+10 | 0.701898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.749038E+09 | 0.180883E+09 | 0.407525E+09 | 0.291106E+09 | 0.116419E+09 | 0.00 | 0.00 |
February | 0.618318E+09 | 0.141953E+09 | 0.326344E+09 | 0.209068E+09 | 0.117276E+09 | 0.00 | 0.00 |
March | 0.448692E+09 | 0.134445E+09 | 0.223106E+09 | 94154079.26 | 0.128952E+09 | 0.00 | 0.00 |
April | 0.334507E+09 | 91985674.17 | 0.158946E+09 | 29875888.83 | 0.129070E+09 | 0.00 | 0.00 |
May | 0.277205E+09 | 32735302.25 | 0.130556E+09 | 3119054.00 | 0.127437E+09 | 0.00 | 0.00 |
June | 0.263764E+09 | 30176908.14 | 0.126499E+09 | 452387.64 | 0.126046E+09 | 0.00 | 0.00 |
July | 0.285716E+09 | 22108938.13 | 0.136363E+09 | 1261258.20 | 0.135102E+09 | 0.00 | 0.00 |
August | 0.343308E+09 | 34099848.47 | 0.156794E+09 | 14312696.47 | 0.142481E+09 | 0.00 | 0.00 |
September | 0.392242E+09 | 42430697.06 | 0.180037E+09 | 41578792.23 | 0.138458E+09 | 0.00 | 0.00 |
October | 0.605202E+09 | 76052809.73 | 0.292524E+09 | 0.148118E+09 | 0.144406E+09 | 0.00 | 0.00 |
November | 0.698252E+09 | 0.129808E+09 | 0.369886E+09 | 0.254262E+09 | 0.115624E+09 | 0.00 | 0.00 |
December | 0.738471E+09 | 0.162602E+09 | 0.401097E+09 | 0.289314E+09 | 0.111784E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.575471E+10 | 0.107928E+10 | 0.290968E+10 | 0.137662E+10 | 0.153305E+10 | 0.00 | 0.00 |
Minimum of Months | 0.263764E+09 | 22108938.13 | 0.126499E+09 | 452387.64 | 0.111784E+09 | 0.00 | 0.00 |
Maximum of Months | 0.749038E+09 | 0.180883E+09 | 0.407525E+09 | 0.291106E+09 | 0.144406E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.198548E+10 | -0.187131E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -114166402.0 | 59.95 | 0.00 | 0.00 |
February | 0.179222E+10 | -0.169040E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -101820255.7 | 59.95 | 0.00 | 0.00 |
March | 0.195795E+10 | -0.184675E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -111198984.2 | 59.95 | 0.00 | 0.00 |
April | 0.175556E+10 | -0.165072E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -104844118.2 | 59.95 | 0.00 | 0.00 |
May | 0.169889E+10 | -0.159099E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -107902130.5 | 59.95 | 0.00 | 0.00 |
June | 0.157136E+10 | -0.146690E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -104459257.4 | 59.95 | 0.00 | 0.00 |
July | 0.153358E+10 | -0.142561E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -107963086.6 | 59.95 | 0.00 | 0.00 |
August | 0.159486E+10 | -0.148690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -107963532.8 | 59.95 | 0.00 | 0.00 |
September | 0.158905E+10 | -0.148461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -104442942.3 | 59.95 | 0.00 | 0.00 |
October | 0.172716E+10 | -0.161910E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -108060309.5 | 59.95 | 0.00 | 0.00 |
November | 0.177660E+10 | -0.167083E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -105763126.5 | 59.95 | 0.00 | 0.00 |
December | 0.194069E+10 | -0.182833E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -112358672.0 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.209234E+11 | -0.196325E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129094E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.153358E+10 | -0.187131E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -114166402.0 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.198548E+10 | -0.142561E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -101820255.7 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.85 | 0.50 | 31-JAN-12:20 | 175.16 | 4.01 | 0.00 | 0.00 | 146.17 | 2.72 | 0.00 | 0.00 |
February | 295.50 | 0.82 | 0.50 | 01-FEB-12:30 | 213.55 | 4.84 | 0.00 | 0.83 | 177.70 | 3.40 | 0.00 | 0.17 |
March | 296.00 | 0.77 | 0.50 | 02-MAR-13:09 | 264.31 | 6.04 | 0.00 | 11.83 | 222.39 | 4.55 | 0.00 | 10.83 |
April | 347.33 | 0.76 | 0.50 | 01-APR-09:30 | 277.82 | 7.49 | 0.00 | 12.00 | 231.87 | 5.82 | 0.00 | 11.17 |
May | 353.67 | 0.75 | 0.50 | 01-MAY-09:09 | 292.64 | 9.29 | 0.00 | 12.67 | 243.71 | 7.62 | 0.00 | 9.50 |
June | 394.00 | 0.74 | 0.50 | 01-JUN-10:39 | 300.09 | 9.90 | 0.00 | 25.33 | 252.86 | 8.22 | 0.00 | 16.33 |
July | 390.00 | 0.72 | 0.50 | 01-JUL-09:00 | 326.31 | 10.25 | 0.00 | 45.50 | 274.13 | 8.61 | 0.00 | 24.67 |
August | 380.83 | 0.71 | 0.50 | 01-AUG-10:09 | 509.18 | 9.47 | 0.00 | 55.83 | 477.26 | 7.79 | 0.00 | 42.00 |
September | 342.17 | 0.72 | 0.50 | 01-SEP-11:09 | 1208.51 | 8.12 | 0.00 | 74.00 | 1286.51 | 6.53 | 0.00 | 59.67 |
October | 330.00 | 0.75 | 0.50 | 04-OCT-11:30 | 283.26 | 6.71 | 0.00 | 12.33 | 236.35 | 5.18 | 0.00 | 11.00 |
November | 308.00 | 0.84 | 0.50 | 01-NOV-12:20 | 185.88 | 4.10 | 0.00 | 0.00 | 155.58 | 2.77 | 0.00 | 0.00 |
December | 282.83 | 0.85 | 0.63 | 11-DEC-12:30 | 172.77 | 4.05 | 0.00 | 0.00 | 143.45 | 2.74 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.77 | 359.43 | 7.26 | 0.00 | 250.33 | 328.97 | 5.72 | 0.00 | 185.33 | ||
Minimum of Months | 282.83 | 0.71 | 0.50 | 172.77 | 4.01 | 0.00 | 0.00 | 143.45 | 2.72 | 0.00 | 0.00 | |
Maximum of Months | 394.00 | 0.85 | 0.63 | 1208.51 | 10.25 | 0.00 | 74.00 | 1286.51 | 8.61 | 0.00 | 59.67 |
Report: CoilReportMonthly
For: PSZ-AC:1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8066216.95 | 17993.59 | 05-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9985455.36 | 20103.87 | 05-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4815430.28 | 19085.92 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22867102.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9985455.36 | 20103.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 645094.31 | 7526.10 | 05-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 645094.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 645094.31 | 7526.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1162116.68 | 8655.01 | 05-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 609198.52 | 7107.32 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1771315.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1162116.68 | 8655.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164369E+09 | 24811.90 | 04-JAN-17:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.379120E+09 | 24811.90 | 04-FEB-14:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102982E+09 | 16918.58 | 11-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239926E+09 | 24811.90 | 20-DEC-16:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.886397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379120E+09 | 24811.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175886E+10 | 34473.26 | 08-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112240E+10 | 31676.73 | 19-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.740272E+09 | 30073.20 | 14-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6028750.42 | 2918.72 | 16-NOV-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.975327E+09 | 32647.49 | 31-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.460289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175886E+10 | 34473.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.560520E+09 | 27098.41 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.436504E+09 | 25201.32 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255320E+09 | 19196.04 | 13-MAR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.429103E+09 | 48586.70 | 21-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.560520E+09 | 48586.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 875383.54 | 819.98 | 10-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14561751.39 | 13228.92 | 05-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22229488.12 | 22263.41 | 12-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7540381.60 | 1620.60 | 21-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45207004.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22229488.12 | 22263.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39576421.27 | 3441.45 | 10-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77353368.20 | 16344.49 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151689E+09 | 18661.13 | 12-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71742300.74 | 11791.56 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151689E+09 | 18661.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 HP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.102365E+10 | 0.667507E+09 | 15199.09 | 19-JAN-23:05 | 9781.17 | 0.00 |
February | 0.00 | 0.00 | 0.160888E+10 | 0.106287E+10 | 14966.65 | 28-FEB-22:40 | 9782.30 | 0.00 |
March | 0.00 | 0.00 | 0.296146E+10 | 0.200605E+10 | 31770.14 | 30-MAR-21:25 | 15209.98 | 0.00 |
April | 0.00 | 0.00 | 0.759647E+10 | 0.552981E+10 | 32100.67 | 30-APR-18:35 | 17628.00 | 0.00 |
May | 0.00 | 0.00 | 0.210670E+11 | 0.150511E+11 | 30383.48 | 07-MAY-18:53 | 24487.64 | 0.00 |
June | 0.00 | 0.00 | 0.235575E+11 | 0.169512E+11 | 31202.53 | 16-JUN-20:10 | 23417.42 | 0.00 |
July | 0.00 | 0.00 | 0.263826E+11 | 0.180527E+11 | 31289.04 | 20-JUL-20:10 | 23613.17 | 0.00 |
August | 0.00 | 0.00 | 0.260282E+11 | 0.180751E+11 | 31869.86 | 10-AUG-20:10 | 22091.76 | 0.00 |
September | 0.00 | 0.00 | 0.220197E+11 | 0.148498E+11 | 30984.62 | 10-SEP-18:10 | 22999.45 | 0.00 |
October | 0.00 | 0.00 | 0.175112E+11 | 0.122728E+11 | 31732.67 | 06-OCT-20:10 | 22294.94 | 0.00 |
November | 0.00 | 0.00 | 0.502208E+10 | 0.341363E+10 | 31803.23 | 04-NOV-21:45 | 17003.39 | 0.00 |
December | 0.00 | 0.00 | 0.305469E+10 | 0.201269E+10 | 30782.86 | 17-DEC-08:61 | 20941.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157833E+12 | 0.109945E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.102365E+10 | 0.667507E+09 | 14966.65 | 9781.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.263826E+11 | 0.180751E+11 | 32100.67 | 24487.64 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 HP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.110299E+11 | 0.676827E+10 | 170861.08 | 20-JAN-07:03 | 82855.41 | 0.00 |
February | 0.00 | 0.00 | 0.170996E+11 | 0.105264E+11 | 173131.31 | 03-FEB-07:03 | 86629.76 | 0.00 |
March | 0.00 | 0.00 | 0.272752E+11 | 0.177684E+11 | 176581.25 | 07-MAR-07:02 | 110395.13 | 0.00 |
April | 0.00 | 0.00 | 0.526150E+11 | 0.350583E+11 | 177895.69 | 01-APR-06:03 | 84780.44 | 0.00 |
May | 0.00 | 0.00 | 0.102657E+12 | 0.638082E+11 | 180182.17 | 23-MAY-06:02 | 104119.79 | 0.00 |
June | 0.00 | 0.00 | 0.109989E+12 | 0.679330E+11 | 178802.86 | 19-JUN-06:02 | 108774.26 | 0.00 |
July | 0.00 | 0.00 | 0.119811E+12 | 0.690188E+11 | 179598.56 | 15-JUL-06:02 | 105572.44 | 0.00 |
August | 0.00 | 0.00 | 0.117291E+12 | 0.689056E+11 | 179580.69 | 10-AUG-06:02 | 106790.84 | 0.00 |
September | 0.00 | 0.00 | 0.102066E+12 | 0.581244E+11 | 179288.60 | 27-SEP-06:02 | 106610.65 | 0.00 |
October | 0.00 | 0.00 | 0.845144E+11 | 0.515105E+11 | 180291.83 | 22-OCT-08:62 | 103744.94 | 0.00 |
November | 0.00 | 0.00 | 0.355217E+11 | 0.224691E+11 | 178248.03 | 02-NOV-06:02 | 109889.04 | 0.00 |
December | 0.00 | 0.00 | 0.223879E+11 | 0.137927E+11 | 177614.47 | 12-DEC-07:02 | 107779.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.802258E+12 | 0.485683E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.110299E+11 | 0.676827E+10 | 170861.08 | 82855.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119811E+12 | 0.690188E+11 | 180291.83 | 110395.13 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 HP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.411890E+10 | 0.313909E+10 | 23471.42 | 29-JAN-20:42 | 15578.18 | 0.00 |
February | 0.00 | 0.00 | 0.530653E+10 | 0.397556E+10 | 24139.47 | 01-FEB-21:15 | 12132.75 | 0.00 |
March | 0.00 | 0.00 | 0.603226E+10 | 0.458465E+10 | 24345.27 | 28-MAR-20:15 | 12028.63 | 0.00 |
April | 0.00 | 0.00 | 0.956918E+10 | 0.725066E+10 | 23865.03 | 30-APR-21:45 | 15500.42 | 0.00 |
May | 0.00 | 0.00 | 0.166314E+11 | 0.120292E+11 | 18491.10 | 25-MAY-20:10 | 14412.48 | 0.00 |
June | 0.00 | 0.00 | 0.173814E+11 | 0.125525E+11 | 19622.86 | 28-JUN-20:10 | 15255.12 | 0.00 |
July | 0.00 | 0.00 | 0.190863E+11 | 0.132316E+11 | 23162.13 | 07-JUL-20:43 | 18573.14 | 0.00 |
August | 0.00 | 0.00 | 0.199122E+11 | 0.141508E+11 | 23389.48 | 24-AUG-20:43 | 19059.58 | 0.00 |
September | 0.00 | 0.00 | 0.184223E+11 | 0.130004E+11 | 23430.07 | 10-SEP-18:08 | 18597.86 | 0.00 |
October | 0.00 | 0.00 | 0.174051E+11 | 0.130733E+11 | 24073.27 | 06-OCT-20:08 | 18211.10 | 0.00 |
November | 0.00 | 0.00 | 0.961640E+10 | 0.743688E+10 | 24046.26 | 20-NOV-21:15 | 13550.00 | 0.00 |
December | 0.00 | 0.00 | 0.661804E+10 | 0.506377E+10 | 23594.01 | 31-DEC-20:03 | 13898.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150100E+12 | 0.109488E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.411890E+10 | 0.313909E+10 | 18491.10 | 12028.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199122E+11 | 0.141508E+11 | 24345.27 | 19059.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 HP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.263053E+10 | 0.186528E+10 | 20409.60 | 17-JAN-22:45 | 9700.28 | 0.00 |
February | 0.00 | 0.00 | 0.342742E+10 | 0.237577E+10 | 20318.45 | 21-FEB-23:05 | 9596.81 | 0.00 |
March | 0.00 | 0.00 | 0.393634E+10 | 0.275911E+10 | 20541.81 | 27-MAR-21:35 | 9784.10 | 0.00 |
April | 0.00 | 0.00 | 0.635570E+10 | 0.447831E+10 | 20484.62 | 15-APR-23:15 | 9886.77 | 0.00 |
May | 0.00 | 0.00 | 0.127669E+11 | 0.858263E+10 | 15791.42 | 07-MAY-18:43 | 12553.08 | 0.00 |
June | 0.00 | 0.00 | 0.136382E+11 | 0.916197E+10 | 16439.27 | 29-JUN-20:10 | 10873.77 | 0.00 |
July | 0.00 | 0.00 | 0.153419E+11 | 0.987073E+10 | 19847.13 | 07-JUL-20:43 | 14820.95 | 0.00 |
August | 0.00 | 0.00 | 0.160916E+11 | 0.106645E+11 | 20079.30 | 31-AUG-20:43 | 15240.04 | 0.00 |
September | 0.00 | 0.00 | 0.146936E+11 | 0.963142E+10 | 19656.97 | 01-SEP-20:43 | 14755.18 | 0.00 |
October | 0.00 | 0.00 | 0.139417E+11 | 0.984139E+10 | 20348.36 | 24-OCT-20:43 | 14252.38 | 0.00 |
November | 0.00 | 0.00 | 0.695571E+10 | 0.505460E+10 | 20320.70 | 20-NOV-21:25 | 10582.12 | 0.00 |
December | 0.00 | 0.00 | 0.461306E+10 | 0.332052E+10 | 20209.74 | 08-DEC-21:40 | 10719.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114393E+12 | 0.776063E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.263053E+10 | 0.186528E+10 | 15791.42 | 9596.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.160916E+11 | 0.106645E+11 | 20541.81 | 15240.04 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATER FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 5413761.15 | 0.00 | 78.19 | 03-JAN-08:04 | 0.08 |
February | 5995060.28 | 0.00 | 78.19 | 04-FEB-08:04 | 0.08 |
March | 2140819.03 | 0.00 | 78.19 | 09-MAR-08:03 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 4479065.67 | 0.00 | 78.19 | 04-DEC-08:05 | 0.08 |
Annual Sum or Average | 18028706.13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5995060.28 | 0.00 | 78.19 | 0.08 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.103814E+10 | 0.32 | 1603.30 | 05-JAN-05:02 | 0.88 |
February | 0.940993E+09 | 0.32 | 1603.30 | 05-FEB-07:01 | 0.88 |
March | 0.105265E+10 | 0.33 | 1603.30 | 10-MAR-05:03 | 0.88 |
April | 0.104112E+10 | 0.35 | 1294.43 | 23-APR-07:02 | 0.79 |
May | 0.120919E+10 | 0.44 | 1603.30 | 07-MAY-18:13 | 0.87 |
June | 0.122353E+10 | 0.46 | 1603.30 | 13-JUN-20:10 | 0.87 |
July | 0.130250E+10 | 0.47 | 1603.30 | 04-JUL-18:10 | 0.87 |
August | 0.129796E+10 | 0.47 | 1603.30 | 02-AUG-20:10 | 0.87 |
September | 0.121300E+10 | 0.45 | 1603.30 | 09-SEP-21:10 | 0.87 |
October | 0.118749E+10 | 0.42 | 1603.30 | 04-OCT-20:10 | 0.87 |
November | 0.101571E+10 | 0.33 | 1482.46 | 11-NOV-20:03 | 0.83 |
December | 0.104705E+10 | 0.33 | 1603.30 | 17-DEC-08:61 | 0.87 |
Annual Sum or Average | 0.135693E+11 | 0.39 | |||
Minimum of Months | 0.940993E+09 | 0.32 | 1294.43 | 0.79 | |
Maximum of Months | 0.130250E+10 | 0.47 | 1603.30 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.711510E+10 | 0.50 | 11095.82 | 01-JAN-09:02 | 1.37 |
February | 0.646222E+10 | 0.50 | 11095.82 | 01-FEB-07:03 | 1.36 |
March | 0.724929E+10 | 0.51 | 11095.82 | 01-MAR-07:03 | 1.37 |
April | 0.698484E+10 | 0.50 | 11095.82 | 01-APR-06:03 | 1.36 |
May | 0.729381E+10 | 0.50 | 11095.82 | 01-MAY-06:02 | 1.36 |
June | 0.729100E+10 | 0.51 | 11095.82 | 01-JUN-06:02 | 1.36 |
July | 0.764730E+10 | 0.51 | 11095.82 | 01-JUL-06:02 | 1.36 |
August | 0.759241E+10 | 0.52 | 11095.82 | 01-AUG-06:02 | 1.36 |
September | 0.714509E+10 | 0.51 | 11095.82 | 01-SEP-06:02 | 1.36 |
October | 0.728624E+10 | 0.50 | 11095.82 | 01-OCT-08:62 | 1.37 |
November | 0.687174E+10 | 0.50 | 11095.82 | 01-NOV-06:02 | 1.36 |
December | 0.713725E+10 | 0.50 | 11095.82 | 10-DEC-09:02 | 1.37 |
Annual Sum or Average | 0.860763E+11 | 0.50 | |||
Minimum of Months | 0.646222E+10 | 0.50 | 11095.82 | 1.36 | |
Maximum of Months | 0.764730E+10 | 0.52 | 11095.82 | 1.37 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.770496E+09 | 0.36 | 803.28 | 19-JAN-21:10 | 0.75 |
February | 0.705184E+09 | 0.38 | 1162.73 | 05-FEB-07:01 | 0.91 |
March | 0.790391E+09 | 0.38 | 1162.73 | 12-MAR-06:01 | 0.91 |
April | 0.778829E+09 | 0.41 | 746.28 | 28-APR-20:10 | 0.72 |
May | 0.864210E+09 | 0.47 | 863.16 | 25-MAY-20:10 | 0.78 |
June | 0.861006E+09 | 0.48 | 924.48 | 28-JUN-20:10 | 0.81 |
July | 0.910997E+09 | 0.49 | 1141.00 | 07-JUL-20:43 | 0.89 |
August | 0.941084E+09 | 0.50 | 1162.73 | 24-AUG-20:43 | 0.90 |
September | 0.895632E+09 | 0.49 | 1162.73 | 03-SEP-18:43 | 0.90 |
October | 0.933147E+09 | 0.48 | 1162.73 | 04-OCT-20:08 | 0.90 |
November | 0.801717E+09 | 0.42 | 1122.07 | 02-NOV-20:43 | 0.89 |
December | 0.797950E+09 | 0.39 | 942.54 | 10-DEC-19:43 | 0.82 |
Annual Sum or Average | 0.100506E+11 | 0.44 | |||
Minimum of Months | 0.705184E+09 | 0.36 | 746.28 | 0.72 | |
Maximum of Months | 0.941084E+09 | 0.50 | 1162.73 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.598420E+09 | 0.35 | 613.90 | 19-JAN-21:10 | 0.74 |
February | 0.547006E+09 | 0.36 | 912.49 | 05-FEB-07:01 | 0.91 |
March | 0.610126E+09 | 0.36 | 912.49 | 12-MAR-06:01 | 0.91 |
April | 0.599117E+09 | 0.39 | 489.43 | 23-APR-07:02 | 0.66 |
May | 0.669049E+09 | 0.47 | 695.88 | 07-MAY-18:43 | 0.79 |
June | 0.667818E+09 | 0.48 | 715.96 | 28-JUN-20:10 | 0.80 |
July | 0.711442E+09 | 0.50 | 912.49 | 07-JUL-20:43 | 0.90 |
August | 0.737552E+09 | 0.51 | 912.49 | 24-AUG-20:43 | 0.90 |
September | 0.702806E+09 | 0.50 | 912.49 | 03-SEP-18:43 | 0.90 |
October | 0.733523E+09 | 0.49 | 912.49 | 04-OCT-20:08 | 0.90 |
November | 0.618723E+09 | 0.40 | 912.49 | 02-NOV-20:43 | 0.90 |
December | 0.615766E+09 | 0.38 | 912.49 | 17-DEC-20:07 | 0.91 |
Annual Sum or Average | 0.781135E+10 | 0.43 | |||
Minimum of Months | 0.547006E+09 | 0.35 | 489.43 | 0.66 | |
Maximum of Months | 0.737552E+09 | 0.51 | 912.49 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.186279E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.171153E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.202352E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.292248E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.627029E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.683662E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.751614E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.742612E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.638371E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.533559E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.224108E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.211720E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.526471E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.171153E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.751614E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.103469E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.112532E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.147442E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.211677E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.343579E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.361196E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.385627E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.378916E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.333551E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.293168E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163863E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.132936E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.296795E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103469E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.385627E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.173751E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.194007E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.222042E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.307121E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.489293E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.507579E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.549996E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.569739E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.523274E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.501814E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.303391E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.233448E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.457546E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.173751E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.569739E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.123735E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.137440E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159782E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.214040E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.376495E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.396802E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.438252E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.456891E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.415952E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.400263E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.224022E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.171672E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.351535E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.123735E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.456891E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.103814E+10 | 0.102365E+10 | 0.176692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.940993E+09 | 0.160888E+10 | 0.113239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105265E+10 | 0.295822E+10 | 0.740272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104112E+10 | 0.758995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120919E+10 | 0.210670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122353E+10 | 0.235575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130250E+10 | 0.263826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129796E+10 | 0.260282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121300E+10 | 0.220197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118749E+10 | 0.174460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101571E+10 | 0.500929E+10 | 6028750.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104705E+10 | 0.305469E+10 | 0.980142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135693E+11 | 0.157746E+12 | 0.462576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.940993E+09 | 0.102365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130250E+10 | 0.263826E+11 | 0.176692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.711510E+10 | 0.110299E+11 | 0.560520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.646222E+10 | 0.170996E+11 | 0.436504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.724929E+10 | 0.272752E+11 | 0.255320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.698484E+10 | 0.526150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.729381E+10 | 0.102657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.729100E+10 | 0.109989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.764730E+10 | 0.119811E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.759241E+10 | 0.117291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.714509E+10 | 0.102066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.728624E+10 | 0.845144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687174E+10 | 0.355217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.713725E+10 | 0.223879E+11 | 0.429103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.860763E+11 | 0.802258E+12 | 0.168145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.646222E+10 | 0.110299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.764730E+10 | 0.119811E+12 | 0.560520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.770496E+09 | 0.410152E+10 | 875383.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705184E+09 | 0.529193E+10 | 15206845.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.790391E+09 | 0.600573E+10 | 22229488.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.778829E+09 | 0.954763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.864210E+09 | 0.166314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.861006E+09 | 0.173814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.910997E+09 | 0.190863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.941084E+09 | 0.199122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.895632E+09 | 0.184223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.933147E+09 | 0.173730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.801717E+09 | 0.956963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797950E+09 | 0.660514E+10 | 7540381.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100506E+11 | 0.149928E+12 | 45852098.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.705184E+09 | 0.410152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.941084E+09 | 0.199122E+11 | 22229488.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.598420E+09 | 0.261959E+10 | 39576421.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.547006E+09 | 0.341784E+10 | 78515484.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.610126E+09 | 0.391321E+10 | 0.151689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599117E+09 | 0.634435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.669049E+09 | 0.127669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.667818E+09 | 0.136382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.711442E+09 | 0.153419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.737552E+09 | 0.160916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.702806E+09 | 0.146936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.733523E+09 | 0.139202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.618723E+09 | 0.691917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.615766E+09 | 0.460963E+10 | 72351499.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781135E+10 | 0.114276E+12 | 0.342133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.547006E+09 | 0.261959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.737552E+09 | 0.160916E+11 | 0.151689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.103814E+10 | 0.00 | 0.00 | 0.557394E+09 | 0.259183E+09 | 8066216.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.940993E+09 | 0.00 | 0.00 | 0.354003E+09 | 0.406550E+09 | 9985455.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105265E+10 | 0.00 | 0.00 | 0.225790E+09 | 0.745081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104112E+10 | 0.00 | 0.00 | 0.00 | 0.188137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120919E+10 | 0.00 | 0.00 | 0.00 | 0.506110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122353E+10 | 0.00 | 0.00 | 0.00 | 0.561309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130250E+10 | 0.00 | 0.00 | 0.00 | 0.621365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129796E+10 | 0.00 | 0.00 | 0.00 | 0.612816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121300E+10 | 0.00 | 0.00 | 0.00 | 0.517070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118749E+10 | 0.00 | 0.00 | 0.00 | 0.414810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101571E+10 | 0.00 | 0.00 | 1824161.96 | 0.122354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104705E+10 | 0.00 | 0.00 | 0.318017E+09 | 0.747317E+09 | 4815430.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135693E+11 | 0.00 | 0.00 | 0.145703E+10 | 0.375978E+11 | 22867102.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.940993E+09 | 0.00 | 0.00 | 0.00 | 0.259183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130250E+10 | 0.00 | 0.00 | 0.557394E+09 | 0.621365E+10 | 9985455.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.711510E+10 | 0.00 | 0.00 | 0.210330E+09 | 0.302146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.646222E+10 | 0.00 | 0.00 | 0.157560E+09 | 0.463337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.724929E+10 | 0.00 | 0.00 | 86215144.02 | 0.740873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.698484E+10 | 0.00 | 0.00 | 0.00 | 0.141828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.729381E+10 | 0.00 | 0.00 | 0.00 | 0.270640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.729100E+10 | 0.00 | 0.00 | 0.00 | 0.288286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.764730E+10 | 0.00 | 0.00 | 0.00 | 0.309154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.759241E+10 | 0.00 | 0.00 | 0.00 | 0.302992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.714509E+10 | 0.00 | 0.00 | 0.00 | 0.262100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.728624E+10 | 0.00 | 0.00 | 0.00 | 0.220305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687174E+10 | 0.00 | 0.00 | 0.00 | 0.951453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.713725E+10 | 0.00 | 0.00 | 0.165874E+09 | 0.599046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.860763E+11 | 0.00 | 0.00 | 0.619979E+09 | 0.210099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.646222E+10 | 0.00 | 0.00 | 0.00 | 0.302146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.764730E+10 | 0.00 | 0.00 | 0.210330E+09 | 0.309154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.770496E+09 | 0.00 | 0.00 | 3089562.42 | 0.963923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705184E+09 | 0.00 | 0.00 | 7843064.24 | 0.122640E+10 | 645094.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.790391E+09 | 0.00 | 0.00 | 7590673.53 | 0.142244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.778829E+09 | 0.00 | 0.00 | 0.00 | 0.229238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.864210E+09 | 0.00 | 0.00 | 0.00 | 0.402872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.861006E+09 | 0.00 | 0.00 | 0.00 | 0.421479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.910997E+09 | 0.00 | 0.00 | 0.00 | 0.458897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.941084E+09 | 0.00 | 0.00 | 0.00 | 0.475631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.895632E+09 | 0.00 | 0.00 | 0.00 | 0.433711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.933147E+09 | 0.00 | 0.00 | 0.00 | 0.408499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.801717E+09 | 0.00 | 0.00 | 0.00 | 0.223220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797950E+09 | 0.00 | 0.00 | 5488406.81 | 0.153104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100506E+11 | 0.00 | 0.00 | 24011706.99 | 0.356793E+11 | 645094.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.705184E+09 | 0.00 | 0.00 | 0.00 | 0.963923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.941084E+09 | 0.00 | 0.00 | 7843064.24 | 0.475631E+10 | 645094.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.598420E+09 | 0.00 | 0.00 | 17680479.96 | 0.621247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.547006E+09 | 0.00 | 0.00 | 29845944.49 | 0.796391E+09 | 1162116.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.610126E+09 | 0.00 | 0.00 | 48003156.36 | 0.939689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599117E+09 | 0.00 | 0.00 | 0.00 | 0.154129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.669049E+09 | 0.00 | 0.00 | 0.00 | 0.309590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.667818E+09 | 0.00 | 0.00 | 0.00 | 0.330020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.711442E+09 | 0.00 | 0.00 | 0.00 | 0.367108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.737552E+09 | 0.00 | 0.00 | 0.00 | 0.383135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.702806E+09 | 0.00 | 0.00 | 0.00 | 0.345672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.733523E+09 | 0.00 | 0.00 | 0.00 | 0.326911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.618723E+09 | 0.00 | 0.00 | 0.00 | 0.162150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.615766E+09 | 0.00 | 0.00 | 29705013.72 | 0.107064E+10 | 609198.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781135E+10 | 0.00 | 0.00 | 0.125235E+09 | 0.272151E+11 | 1771315.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.547006E+09 | 0.00 | 0.00 | 0.00 | 0.621247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.737552E+09 | 0.00 | 0.00 | 48003156.36 | 0.383135E+10 | 1162116.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197677E+10 | 0.218101E+09 | 7506662.70 | 319001.42 | 50943779.21 | 0.815763E+09 | 0.237592E+09 | 7278.57 | 0.22 |
February | 0.143341E+10 | 0.350712E+09 | 453370.43 | 566832.62 | 34102195.07 | 0.502873E+09 | 0.268951E+09 | 143.97 | 0.23 |
March | 0.142516E+10 | 0.871402E+09 | 0.00 | 434947.01 | 28973350.27 | 0.384481E+09 | 0.325469E+09 | 0.00 | 0.23 |
April | 0.316661E+09 | 0.214244E+10 | 0.00 | 1601120.49 | 14156975.10 | 0.00 | 0.851414E+09 | 0.00 | 0.28 |
May | 0.00 | 0.730390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
June | 0.00 | 0.833885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.991980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.927711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.779388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
October | 0.130241E+09 | 0.570465E+10 | 0.00 | 1792414.93 | 0.00 | 0.00 | 0.552443E+09 | 0.00 | 0.25 |
November | 0.955191E+09 | 0.161521E+10 | 0.00 | 1788000.65 | 21202510.56 | 833119.58 | 0.890654E+09 | 0.00 | 0.27 |
December | 0.178481E+10 | 0.960290E+09 | 11355855.33 | 498457.89 | 53539058.07 | 0.508315E+09 | 0.250269E+09 | 50195.37 | 0.22 |
Annual Sum or Average | 0.802225E+10 | 0.544964E+11 | 19315888.47 | 7000775.01 | 0.202918E+09 | 0.221227E+10 | 0.337679E+10 | 57617.91 | 0.23 |
Minimum of Months | 0.00 | 0.218101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Maximum of Months | 0.197677E+10 | 0.991980E+10 | 11355855.33 | 1792414.93 | 53539058.07 | 0.815763E+09 | 0.890654E+09 | 50195.37 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184145E+11 | 0.168877E+10 | 0.00 | 10995904.04 | 34323422.99 | 47040255.09 | 0.817138E+10 | 0.00 | 0.35 |
February | 0.101290E+11 | 0.258072E+10 | 0.00 | 16808613.44 | 12894513.28 | 0.113871E+09 | 0.974927E+10 | 0.00 | 0.38 |
March | 0.828700E+10 | 0.583416E+10 | 0.00 | 20495548.24 | 21110069.34 | 40422853.88 | 0.119571E+11 | 0.00 | 0.40 |
April | 0.678304E+09 | 0.127465E+11 | 0.00 | 22655754.86 | 57662483.76 | 0.00 | 0.826156E+10 | 0.00 | 0.42 |
May | 0.00 | 0.416131E+11 | 0.00 | 0.00 | 0.367879E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.470739E+11 | 0.00 | 0.00 | 0.362179E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.556140E+11 | 0.00 | 0.00 | 0.352944E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.522177E+11 | 0.00 | 0.00 | 0.364097E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.434782E+11 | 0.00 | 0.00 | 0.297321E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 0.392930E+09 | 0.325001E+11 | 0.00 | 15019395.43 | 0.231439E+09 | 0.00 | 0.465875E+10 | 0.00 | 0.35 |
November | 0.268338E+10 | 0.927442E+10 | 0.00 | 30329344.58 | 61649695.05 | 0.00 | 0.136637E+11 | 0.00 | 0.44 |
December | 0.135656E+11 | 0.583005E+10 | 0.00 | 15575909.76 | 86078194.95 | 48829983.72 | 0.937229E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.541506E+11 | 0.310452E+12 | 0.00 | 0.131880E+09 | 0.224958E+10 | 0.250164E+09 | 0.658341E+11 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.168877E+10 | 0.00 | 0.00 | 12894513.28 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.184145E+11 | 0.556140E+11 | 0.00 | 30329344.58 | 0.367879E+09 | 0.113871E+09 | 0.136637E+11 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.405669E+09 | 0.439951E+09 | 0.00 | 9565442.82 | 0.00 | 0.00 | 0.388406E+10 | 0.00 | 0.62 |
February | 0.311366E+09 | 0.630936E+09 | 0.00 | 6045172.02 | 0.00 | 851044.21 | 0.249465E+10 | 0.00 | 0.59 |
March | 0.395005E+09 | 0.889754E+09 | 0.00 | 5939126.86 | 0.00 | 7075220.85 | 0.233620E+10 | 0.00 | 0.60 |
April | 39516665.72 | 0.167612E+10 | 0.00 | 3068623.67 | 0.00 | 0.00 | 0.101046E+10 | 0.00 | 0.52 |
May | 0.00 | 0.467349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.517293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.609740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.586724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.512153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 9379840.51 | 0.393569E+10 | 0.00 | 2880582.80 | 0.00 | 0.00 | 0.713065E+09 | 0.00 | 0.42 |
November | 21783592.77 | 0.137067E+10 | 0.00 | 9158223.96 | 0.00 | 0.00 | 0.257246E+10 | 0.00 | 0.70 |
December | 0.326105E+09 | 0.940891E+09 | 0.00 | 9188281.01 | 795357.72 | 0.00 | 0.328740E+10 | 0.00 | 0.62 |
Annual Sum or Average | 0.150882E+10 | 0.368166E+11 | 0.00 | 45845453.15 | 795357.72 | 7926265.07 | 0.162983E+11 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.439951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.405669E+09 | 0.609740E+10 | 0.00 | 9565442.82 | 795357.72 | 7075220.85 | 0.388406E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100881E+10 | 0.344242E+09 | 0.00 | 3763809.59 | 1066436.65 | 11833140.67 | 0.193221E+10 | 0.00 | 0.43 |
February | 0.710248E+09 | 0.497851E+09 | 0.00 | 2662293.62 | 82155.22 | 25220905.29 | 0.128099E+10 | 0.00 | 0.44 |
March | 0.735799E+09 | 0.719771E+09 | 0.00 | 2487994.95 | 61464.60 | 71915068.77 | 0.109832E+10 | 0.00 | 0.45 |
April | 0.101505E+09 | 0.139144E+10 | 0.00 | 1833165.01 | 1151887.93 | 0.00 | 0.760035E+09 | 0.00 | 0.45 |
May | 0.00 | 0.429068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.484122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.573963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.554319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.478515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
October | 22846974.08 | 0.374918E+10 | 0.00 | 1919233.06 | 0.00 | 0.00 | 0.500895E+09 | 0.00 | 0.38 |
November | 98408945.59 | 0.125134E+10 | 0.00 | 5775854.50 | 63997.98 | 0.00 | 0.184093E+10 | 0.00 | 0.56 |
December | 0.870293E+09 | 0.835910E+09 | 0.00 | 4483478.39 | 2560603.12 | 47680185.68 | 0.168290E+10 | 0.00 | 0.47 |
Annual Sum or Average | 0.354791E+10 | 0.339896E+11 | 0.00 | 22925829.12 | 4986545.50 | 0.156649E+09 | 0.909628E+10 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.344242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.100881E+10 | 0.573963E+10 | 0.00 | 5775854.50 | 2560603.12 | 71915068.77 | 0.193221E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.212569E+12 | 0.291661E+10 | 0.00 | 0.343085E+11 | 0.654000E+18 |
February | 0.241217E+12 | 0.239855E+10 | 0.00 | 0.230621E+11 | 0.572200E+18 |
March | 0.286395E+12 | 0.183930E+10 | 0.00 | 0.188339E+11 | 0.623900E+18 |
April | 0.335894E+12 | 0.361030E+09 | 0.00 | -0.588450E+10 | 0.592500E+18 |
May | 0.344814E+12 | -0.178623E+10 | 0.00 | -0.582490E+11 | 0.662700E+18 |
June | 0.346265E+12 | -0.148460E+10 | 0.00 | -0.657890E+11 | 0.635000E+18 |
July | 0.356499E+12 | -0.201726E+10 | 0.00 | -0.777238E+11 | 0.652500E+18 |
August | 0.325535E+12 | -0.214070E+10 | 0.00 | -0.732693E+11 | 0.661000E+18 |
September | 0.275219E+12 | -0.183451E+10 | 0.00 | -0.614761E+11 | 0.660100E+18 |
October | 0.266686E+12 | -931357596.1 | 0.00 | -0.390457E+11 | 0.694600E+18 |
November | 0.193059E+12 | 0.141906E+10 | 0.00 | 0.962674E+10 | 0.648200E+18 |
December | 0.190588E+12 | 0.250747E+10 | 0.00 | 0.233977E+11 | 0.669100E+18 |
Annual Sum or Average | 0.337474E+13 | 0.124736E+10 | 0.00 | -0.272209E+12 | 0.772580E+19 |
Minimum of Months | 0.190588E+12 | -0.214070E+10 | 0.00 | -0.777238E+11 | 0.572200E+18 |
Maximum of Months | 0.356499E+12 | 0.291661E+10 | 0.00 | 0.343085E+11 | 0.694600E+18 |