Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2024-07-03 12:20:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1750.15 | 837.27 | 837.27 |
Net Site Energy | 1750.15 | 837.27 | 837.27 |
Total Source Energy | 5542.74 | 2651.62 | 2651.62 |
Net Source Energy | 5542.74 | 2651.62 | 2651.62 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 43.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 339.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 619.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 177.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 425.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1750.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 43.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 339.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 619.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 177.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 425.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 16.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 43.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 339.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 619.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 177.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 425.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 16.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 381.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 837.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 381.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 837.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1750.155 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1750.155 | 100.00 |
Total On-Site and Utility Electric Sources | 1750.155 | 100.00 |
Total Electricity End Uses | 1750.155 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.69 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.69 | 100.00 |
Total Water End Uses | 87.69 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 904.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL | PSZ-AC_3:3 HP COOLING COIL | PSZ-AC_4:4 HP COOLING COIL | PSZ-AC_5:5 HP COOLING COIL | PSZ-AC_6:6 HP COOLING COIL | PSZ-AC_7:7 HP COOLING COIL | PSZ-AC_8:8 HP COOLING COIL | PSZ-AC_9:9 HP COOLING COIL | PSZ-AC_10:10 HP COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1_SUPPHEATCOIL | PSZ-AC_2:2_SUPPHEATCOIL | PSZ-AC_3:3_SUPPHEATCOIL | PSZ-AC_4:4_SUPPHEATCOIL | PSZ-AC_5:5_SUPPHEATCOIL | PSZ-AC_6:6_SUPPHEATCOIL | PSZ-AC_7:7_SUPPHEATCOIL | PSZ-AC_8:8_SUPPHEATCOIL | PSZ-AC_9:9_SUPPHEATCOIL | PSZ-AC_10:10_SUPPHEATCOIL | PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL | PSZ-AC_3:3 HP COOLING COIL | PSZ-AC_4:4 HP COOLING COIL | PSZ-AC_5:5 HP COOLING COIL | PSZ-AC_6:6 HP COOLING COIL | PSZ-AC_7:7 HP COOLING COIL | PSZ-AC_8:8 HP COOLING COIL | PSZ-AC_9:9 HP COOLING COIL | PSZ-AC_10:10 HP COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 236.76 | 0.00 | 0.00 | 236.76 | 0.00 |
Gross Window-Wall Ratio [%] | 19.99 | 0.00 | 0.00 | 49.99 | 0.00 |
Above Ground Window-Wall Ratio [%] | 19.99 | 0.00 | 0.00 | 49.99 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 236.76 | 0.00 | 0.00 | 236.76 | 0.00 |
Gross Window-Wall Ratio [%] | 19.99 | 0.00 | 0.00 | 49.99 | 0.00 |
Above Ground Window-Wall Ratio [%] | 19.99 | 0.00 | 0.00 | 49.99 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 39.49 | 39.49 | 21.6022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.75 | 19.75 | 24.7401 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 23.0997 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 23.0997 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 23.0997 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 39.45 | 39.45 | 15.8794 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 16.1458 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 16.1458 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 16.1458 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 19.72 | 19.72 | 16.1458 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 236.76 | 236.76 | 19.4655 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 236.76 | 236.76 | 19.4655 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 21.6022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 24.7401 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 23.0997 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 23.0997 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 23.0997 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 15.8794 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 16.1458 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 16.1458 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 16.1458 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 16.1458 | 6.19 | 4.3000 | |
Total | 2090.32 | 19.4655 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 19.4655 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 19.4655 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 12-FEB-09:09 | - | - | - | - | - | - | - | - | - | - | - | 02-JAN-13:09 |
Heating | 133426.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12801.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2459.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24636.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 265.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 173590.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 133426.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 12801.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 2459.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 24636.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 265.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 138.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1076.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1960.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1346.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 52.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5542.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 66.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 514.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 938.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 269.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 643.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2651.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 66.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 514.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 938.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 269.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 643.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2651.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.42 |
SMSTORE1 DIRECT AIR | 1.26 |
SMSTORE2 DIRECT AIR | 1.25 |
SMSTORE3 DIRECT AIR | 1.24 |
SMSTORE4 DIRECT AIR | 1.25 |
LGSTORE2 DIRECT AIR | 2.28 |
SMSTORE5 DIRECT AIR | 1.21 |
SMSTORE6 DIRECT AIR | 1.21 |
SMSTORE7 DIRECT AIR | 1.22 |
SMSTORE8 DIRECT AIR | 1.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.42 | 2.42 | 2.42 | 2.42 | 2.42 | 2.42 | 1.00 | 1.00 | 2.42 |
PSZ-AC_2:2 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
PSZ-AC_3:3 | 1.25 | 1.25 | 1.25 | 1.25 | 1.26 | 1.26 | 1.00 | 0.985816 | 1.26 |
PSZ-AC_4:4 | 1.24 | 1.24 | 1.24 | 1.24 | 1.27 | 1.27 | 1.00 | 0.977587 | 1.27 |
PSZ-AC_5:5 | 1.25 | 1.25 | 1.25 | 1.25 | 1.26 | 1.26 | 1.00 | 0.985704 | 1.26 |
PSZ-AC_6:6 | 2.28 | 2.28 | 2.28 | 2.28 | 2.28 | 2.28 | 1.00 | 1.00 | 2.28 |
PSZ-AC_7:7 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.00 | 1.00 | 1.21 |
PSZ-AC_8:8 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.00 | 1.00 | 1.21 |
PSZ-AC_9:9 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.00 | 1.00 | 1.22 |
PSZ-AC_10:10 | 1.48 | 1.48 | 1.48 | 1.48 | 1.48 | 1.48 | 1.00 | 1.00 | 1.48 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.42 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.26 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.26 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.27 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.26 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.28 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.21 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.21 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.22 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.48 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.42 | 3925.37 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 2094.58 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 2101.22 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.27 | 2107.31 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 2101.51 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.28 | 3793.75 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.21 | 2013.69 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.21 | 2010.54 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.22 | 2030.67 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.48 | 2457.83 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.42 | 2.42 | 2.42 | 2.42 | 53902.44 | 36437.53 | 32.22 | 54384.37 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 1.26 | 27775.10 | 18812.53 | 32.22 | 28078.40 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 1.26 | 27841.39 | 18857.62 | 32.22 | 28145.70 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.27 | 1.27 | 1.27 | 1.27 | 27902.07 | 18898.89 | 32.22 | 28207.31 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 1.26 | 27844.31 | 18859.60 | 32.22 | 28148.66 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.28 | 2.28 | 2.28 | 2.28 | 51434.98 | 34827.96 | 32.22 | 51982.03 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.21 | 1.21 | 1.21 | 1.21 | 27189.53 | 18411.69 | 32.22 | 27480.13 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.21 | 1.21 | 1.21 | 1.21 | 27181.19 | 18405.75 | 32.22 | 27471.27 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.22 | 1.22 | 1.22 | 1.22 | 27426.22 | 18571.90 | 32.22 | 27719.26 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.48 | 1.48 | 1.48 | 1.48 | 32341.21 | 21906.66 | 32.22 | 32696.51 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 HP COOLING COIL | 2.42 | 1.21 | 1.61 | 53902.44 | 26951.22 | 0.736220 | 0.736220 |
PSZ-AC_2:2 HP COOLING COIL | 1.26 | 0.630138 | 0.840187 | 27775.10 | 13887.55 | 0.740150 | 0.740150 |
PSZ-AC_3:3 HP COOLING COIL | 1.26 | 0.632136 | 0.842847 | 27841.39 | 13920.69 | 0.740360 | 0.740360 |
PSZ-AC_4:4 HP COOLING COIL | 1.27 | 0.633968 | 0.845293 | 27902.07 | 13951.03 | 0.740560 | 0.740560 |
PSZ-AC_5:5 HP COOLING COIL | 1.26 | 0.632223 | 0.842967 | 27844.31 | 13922.16 | 0.740370 | 0.740370 |
PSZ-AC_6:6 HP COOLING COIL | 2.28 | 1.14 | 1.52 | 51434.98 | 25717.49 | 0.732090 | 0.732090 |
PSZ-AC_7:7 HP COOLING COIL | 1.21 | 0.605804 | 0.807740 | 27189.53 | 13594.76 | 0.734200 | 0.734200 |
PSZ-AC_8:8 HP COOLING COIL | 1.21 | 0.604856 | 0.806473 | 27181.19 | 13590.59 | 0.733860 | 0.733860 |
PSZ-AC_9:9 HP COOLING COIL | 1.22 | 0.610914 | 0.814553 | 27426.22 | 13713.11 | 0.734130 | 0.734130 |
PSZ-AC_10:10 HP COOLING COIL | 1.48 | 0.739420 | 0.985893 | 32341.21 | 16170.60 | 0.742290 | 0.742290 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | Design Size Speed 2 Gross Rated Heating Capacity [W] | Design Size Speed 1 Gross Rated Heating Capacity [W] | Design Size Resistive Defrost Heater Capacity | |
PSZ-AC_1:1 HEATING COIL | 2.42 | 1.21 | 54384.37 | 27192.19 | 0.000000 |
PSZ-AC_2:2 HEATING COIL | 1.26 | 0.630138 | 28078.40 | 14039.20 | 0.000000 |
PSZ-AC_3:3 HEATING COIL | 1.26 | 0.632136 | 28145.70 | 14072.85 | 0.000000 |
PSZ-AC_4:4 HEATING COIL | 1.27 | 0.633968 | 28207.31 | 14103.65 | 0.000000 |
PSZ-AC_5:5 HEATING COIL | 1.26 | 0.632223 | 28148.66 | 14074.33 | 0.000000 |
PSZ-AC_6:6 HEATING COIL | 2.28 | 1.14 | 51982.03 | 25991.01 | 0.000000 |
PSZ-AC_7:7 HEATING COIL | 1.21 | 0.605804 | 27480.13 | 13740.06 | 0.000000 |
PSZ-AC_8:8 HEATING COIL | 1.21 | 0.604856 | 27471.27 | 13735.63 | 0.000000 |
PSZ-AC_9:9 HEATING COIL | 1.22 | 0.610914 | 27719.26 | 13859.63 | 0.000000 |
PSZ-AC_10:10 HEATING COIL | 1.48 | 0.739420 | 32696.51 | 16348.25 | 0.000000 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_SUPPHEATCOIL | 54384.37 |
PSZ-AC_2:2_SUPPHEATCOIL | 28078.40 |
PSZ-AC_3:3_SUPPHEATCOIL | 28145.70 |
PSZ-AC_4:4_SUPPHEATCOIL | 28207.31 |
PSZ-AC_5:5_SUPPHEATCOIL | 28148.66 |
PSZ-AC_6:6_SUPPHEATCOIL | 51982.03 |
PSZ-AC_7:7_SUPPHEATCOIL | 27480.13 |
PSZ-AC_8:8_SUPPHEATCOIL | 27471.27 |
PSZ-AC_9:9_SUPPHEATCOIL | 27719.26 |
PSZ-AC_10:10_SUPPHEATCOIL | 32696.51 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 229.01 | 39.49 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.30 | 19.75 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 110.68 | 39.45 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 173.76 | 19.72 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 21.602 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.902 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 24.740 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.040 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 23.100 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.400 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 23.100 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.400 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 23.100 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.400 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 16.146 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.446 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 16.146 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.446 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 16.146 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.446 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 16.146 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.446 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 5541.183 | 15.905 | 98.509 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5541.183 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2816.997 | 16.172 | 100.162 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2816.997 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 5532.181 | 15.879 | 98.349 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5532.181 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
19 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
20 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
21 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
22 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
23 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
24 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
25 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
26 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
27 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
28 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
29 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.1892 | 11712.0 | 0.999 | 0.8953 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone LGSTORE1 | 1.2500 |
3 | Zone SMSTORE1 | 1.2500 |
4 | Zone SMSTORE2 | 1.2500 |
5 | Zone SMSTORE3 | 1.2500 |
6 | Zone SMSTORE4 | 1.2500 |
7 | Zone LGSTORE2 | 1.2500 |
8 | Zone SMSTORE5 | 1.2500 |
9 | Zone SMSTORE6 | 1.2500 |
10 | Zone SMSTORE7 | 1.2500 |
11 | Zone SMSTORE8 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone LGSTORE1 | 1.1500 |
3 | Zone SMSTORE1 | 1.1500 |
4 | Zone SMSTORE2 | 1.1500 |
5 | Zone SMSTORE3 | 1.1500 |
6 | Zone SMSTORE4 | 1.1500 |
7 | Zone LGSTORE2 | 1.1500 |
8 | Zone SMSTORE5 | 1.1500 |
9 | Zone SMSTORE6 | 1.1500 |
10 | Zone SMSTORE7 | 1.1500 |
11 | Zone SMSTORE8 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 27448.00865 | 31565.20994 | 2.08573 | 2.39859 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 34.40000 | 1.44733E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 25470.48756 | 31838.10945 | 1.93592 | 2.41990 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 14421.99639 | 16585.29585 | 1.09589 | 1.26028 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 12078.24810 | 15097.81012 | 0.91804 | 1.14755 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 14603.76406 | 16794.32867 | 1.08377 | 1.24634 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 29.17500 | 1.44637E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 12238.88801 | 15298.61001 | 0.93025 | 1.16281 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 14525.72391 | 16704.58250 | 1.07784 | 1.23952 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 29.17500 | 1.44637E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 12298.72844 | 15373.41054 | 0.93480 | 1.16850 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 14604.15482 | 16794.77805 | 1.08380 | 1.24637 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 29.17500 | 1.44637E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 12383.73375 | 15479.66718 | 0.94126 | 1.17657 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 25930.65141 | 29820.24912 | 1.97039 | 2.26595 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 24025.12523 | 30031.40653 | 1.82611 | 2.28264 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 13430.13259 | 15444.65248 | 1.02052 | 1.17360 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 12752.47012 | 15940.58765 | 0.96929 | 1.21161 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 13364.62782 | 15369.32199 | 1.01554 | 1.16787 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 12732.50577 | 15915.63222 | 0.96777 | 1.20971 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 13417.15239 | 15429.72525 | 1.01953 | 1.17246 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 12860.03359 | 16075.04198 | 0.97746 | 1.22183 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 14952.73414 | 17195.64427 | 1.13614 | 1.30656 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 33.92500 | 1.44724E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 15565.99362 | 19457.49203 | 1.18307 | 1.47884 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 36124.77 | 2.39859 | 2.39859 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 44527.97 | 2.41990 | 2.41990 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 18852.64 | 1.26028 | 1.26028 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 21454.83 | 1.14755 | 1.14755 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 18904.41 | 1.26427 | 1.26427 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 21652.69 | 1.16281 | 1.16281 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 18951.80 | 1.26794 | 1.26794 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 21726.39 | 1.16850 | 1.16850 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 18906.67 | 1.26445 | 1.26445 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 21831.09 | 1.17657 | 1.17657 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 34406.71 | 2.26595 | 2.26595 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 42747.92 | 2.28264 | 2.28264 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 17728.24 | 1.17360 | 1.17360 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 22285.26 | 1.21161 | 1.21161 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 17653.97 | 1.16787 | 1.16787 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 22260.67 | 1.20971 | 1.20971 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 17712.46 | 1.17246 | 1.17246 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 22417.74 | 1.22183 | 1.22183 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 19354.88 | 1.30656 | 1.30656 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 25750.45 | 1.47884 | 1.47884 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.41990 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.26028 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24634 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23952 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24637 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.28264 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.21161 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.20971 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22183 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.47884 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.41990 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.41990 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.41990 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.41990 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.41990 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.41990 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.26028 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.26028 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.26028 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.26028 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26028 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.26028 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24634 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24634 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24634 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24634 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26427 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.26427 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.98582 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23952 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23952 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23952 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23952 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26794 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.26794 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.97759 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24637 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24637 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24637 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24637 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26445 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.26445 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.98570 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.28264 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28264 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.28264 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28264 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.28264 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.28264 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.21161 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.21161 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.21161 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.21161 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.21161 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.21161 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.20971 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.20971 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.20971 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20971 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.20971 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.20971 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22183 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22183 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22183 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22183 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22183 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22183 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.47884 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.47884 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.47884 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.47884 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.47884 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.47884 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.41990 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.26028 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.26427 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.26794 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.26445 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.28264 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.21161 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.20971 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.22183 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.47884 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.41990 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.41990 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3925.37032 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.41990 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.41990 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.41990 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.41990 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.41990 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.20995 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.61327 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 53902.44000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 26951.22000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73622 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73622 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 53902.44000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36437.52798 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 54384.37012 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 2.41990 |
122 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.20995 |
123 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 54384.37012 |
124 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 27192.18506 |
125 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
126 | Coil:Heating:Electric | PSZ-AC_1:1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 54384.37012 |
127 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26028 |
128 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
129 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26028 |
130 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2094.57564 |
131 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26028 |
132 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26028 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26028 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26028 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26028 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63014 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84019 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27775.10000 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13887.55000 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74015 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74015 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27775.10000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18812.53044 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 28078.40364 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
147 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.26028 |
148 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63014 |
149 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 28078.40364 |
150 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 14039.20182 |
151 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
152 | Coil:Heating:Electric | PSZ-AC_2:2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 28078.40364 |
153 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26427 |
154 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
155 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26427 |
156 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2101.21642 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26427 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26427 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26427 |
160 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26427 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26427 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63214 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84285 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27841.39000 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13920.69500 |
166 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74036 |
167 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74036 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27841.39000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18857.61839 |
170 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
171 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 28145.69909 |
172 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
173 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.26427 |
174 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63214 |
175 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 28145.69909 |
176 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 14072.84954 |
177 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
178 | Coil:Heating:Electric | PSZ-AC_3:3_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 28145.69909 |
179 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26794 |
180 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
181 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26794 |
182 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2107.30736 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26794 |
184 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26794 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26794 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26794 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26794 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63397 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84529 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27902.07000 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13951.03500 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74056 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74056 |
194 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27902.07000 |
195 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18898.89438 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 28207.30504 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
199 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.26794 |
200 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63397 |
201 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 28207.30504 |
202 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 14103.65252 |
203 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
204 | Coil:Heating:Electric | PSZ-AC_4:4_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 28207.30504 |
205 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26445 |
206 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
207 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26445 |
208 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2101.50633 |
209 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26445 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26445 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26445 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26445 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26445 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63222 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84297 |
216 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27844.31000 |
217 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13922.15500 |
218 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74037 |
219 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74037 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27844.31000 |
221 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18859.60058 |
222 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 28148.65758 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
225 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.26445 |
226 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63222 |
227 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 28148.65758 |
228 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 14074.32879 |
229 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
230 | Coil:Heating:Electric | PSZ-AC_5:5_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 28148.65758 |
231 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.28264 |
232 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
233 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.28264 |
234 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3793.74694 |
235 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.28264 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.28264 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.28264 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.28264 |
239 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.28264 |
240 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.14132 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.52176 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 51434.98000 |
243 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25717.49000 |
244 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73209 |
245 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73209 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 51434.98000 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34827.95853 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 51982.02766 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
251 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 2.28264 |
252 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.14132 |
253 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 51982.02766 |
254 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 25991.01383 |
255 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
256 | Coil:Heating:Electric | PSZ-AC_6:6_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 51982.02766 |
257 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.21161 |
258 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
259 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.21161 |
260 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2013.68923 |
261 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.21161 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.21161 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.21161 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.21161 |
265 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.21161 |
266 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60580 |
267 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.80774 |
268 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27189.53000 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13594.76500 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73420 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73420 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27189.53000 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18411.68627 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 27480.12877 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
277 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.21161 |
278 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60580 |
279 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 27480.12877 |
280 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 13740.06438 |
281 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
282 | Coil:Heating:Electric | PSZ-AC_7:7_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 27480.12877 |
283 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.20971 |
284 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
285 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.20971 |
286 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2010.53677 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.20971 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.20971 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.20971 |
290 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.20971 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.20971 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60486 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.80647 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27181.19000 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13590.59500 |
296 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73386 |
297 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73386 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27181.19000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18405.74888 |
300 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
301 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 27471.26699 |
302 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
303 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.20971 |
304 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60486 |
305 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 27471.26699 |
306 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 13735.63349 |
307 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
308 | Coil:Heating:Electric | PSZ-AC_8:8_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 27471.26699 |
309 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22183 |
310 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
311 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22183 |
312 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2030.67422 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22183 |
314 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22183 |
315 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22183 |
316 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22183 |
317 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22183 |
318 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61091 |
319 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.81455 |
320 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27426.22000 |
321 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13713.11000 |
322 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73413 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73413 |
324 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27426.22000 |
325 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18571.90219 |
326 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
327 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 27719.25699 |
328 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
329 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.22183 |
330 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61091 |
331 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 27719.25699 |
332 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 13859.62850 |
333 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
334 | Coil:Heating:Electric | PSZ-AC_9:9_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 27719.25699 |
335 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.47884 |
336 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
337 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.47884 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2457.82738 |
339 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.47884 |
340 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.47884 |
341 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.47884 |
342 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.47884 |
343 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.47884 |
344 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73942 |
345 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98589 |
346 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32341.21000 |
347 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16170.60500 |
348 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74229 |
349 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74229 |
350 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32341.21000 |
351 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21906.66026 |
352 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
353 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 32696.50786 |
354 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
355 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.47884 |
356 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73942 |
357 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 32696.50786 |
358 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 16348.25393 |
359 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
360 | Coil:Heating:Electric | PSZ-AC_10:10_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 32696.50786 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | 51997.2 | 10.15 | 10.15 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | 26783.1 | 10.67 | 10.67 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | 26846.2 | 10.67 | 10.67 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | 26904.0 | 10.67 | 10.67 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | 26849.0 | 10.67 | 10.67 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | 49637.5 | 10.17 | 10.17 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | 26235.5 | 10.70 | 10.70 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | 26228.6 | 10.71 | 10.71 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | 26464.1 | 10.70 | 10.70 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | 31177.3 | 10.66 | 10.66 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | 56321.6 | 31071.3 | 7.89 | 2 |
2 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | 29087.0 | 16050.4 | 7.81 | 2 |
3 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | 29157.5 | 16089.6 | 7.81 | 2 |
4 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | 29222.0 | 16125.5 | 7.81 | 2 |
5 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | 29160.6 | 16091.3 | 7.81 | 2 |
6 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | 53810.2 | 29675.3 | 7.82 | 2 |
7 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | 28450.4 | 15691.5 | 7.83 | 2 |
8 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | 28440.0 | 15685.3 | 7.84 | 2 |
9 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | 28697.7 | 15827.8 | 7.83 | 2 |
10 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | 33879.7 | 18698.9 | 7.81 | 2 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 39.45 | 78.94 | 39.45 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.73 | 39.47 | 19.73 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 39.49 | 78.94 | 39.49 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.8643290154E-002 | 0.1127931641 | Pass | Pass | 0.2247250340 | 0.8414519952 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 7.2340931365E-002 | 0.1118033089 | Pass | Pass | 1.2866962784 | 13.9749057151 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.7491993506E-002 | 0.1346600184 | Pass | Pass | 0.2224252747 | 0.7517534182 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 4.9185585882E-002 | 0.1618723994 | Pass | Pass | 0.2021243347 | 0.5565937171 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.8482048800E-002 | 0.1782737797 | Pass | Pass | 1.1668140612 | 7.6404233669 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.6405285694E-002 | 0.2280072317 | Pass | Pass | 0.2578235171 | 0.7650843103 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.6225235982E-002 | 0.2347071897 | Pass | Pass | 0.1533926950 | 0.7799798016 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.6901812585E-002 | 0.2403879746 | Pass | Pass | 0.1601181379 | 0.8012143714 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.9499516845E-002 | 0.2582043592 | Pass | Pass | 0.1503427708 | 0.9513914172 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.4165532170E-002 | 0.3358185016 | Pass | Pass | 0.2168959923 | 2.0285043554 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4109.05 | 26.73 | 0.00 | 338.96 | -0.608450E+10 | -0.608449E+10 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 78.94 | 39.45 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.73 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 78.94 | 39.49 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.241 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.57_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.241 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 236.76 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 236.76 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 3.975 | 9.815 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 3.975 | 9.815 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 15.9053 | 348.39 | 5541.18 | LightsWired | LTG_SCH_BASE_LPD1 | 97.64 | 168.00 | 97.63 | 0.0000 | Y | 101.55 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 36.32 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 16.1717 | 174.19 | 2817.00 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 97.89 | 168.00 | 97.87 | 0.0000 | Y | 51.75 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 27.31 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 41.16 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 41.16 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 41.16 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 15.8794 | 348.39 | 5532.18 | LightsWired | LTG_SCH_BASE_LPD2 | 72.07 | 168.00 | 71.48 | 0.0000 | Y | 74.23 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.83 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.83 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.83 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.83 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 9.7327 | 4180.64 | 40689.09 | 619.14 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 11300.38 | AstronomicalClock | - | 83.77 | 83.77 | 177.70 | |
Exterior Lighting Total | 11300.38 | 177.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 53902.44 | 39684.05 | 14218.39 | 0.74 | 3.20 | |||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27775.10 | 20557.74 | 7217.36 | 0.74 | 3.40 | |||
PSZ-AC_3:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27841.39 | 20612.65 | 7228.74 | 0.74 | 3.40 | |||
PSZ-AC_4:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27902.07 | 20663.16 | 7238.91 | 0.74 | 3.40 | |||
PSZ-AC_5:5 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27844.31 | 20615.09 | 7229.22 | 0.74 | 3.40 | |||
PSZ-AC_6:6 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 51434.98 | 37655.03 | 13779.95 | 0.73 | 3.20 | |||
PSZ-AC_7:7 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27189.53 | 19962.55 | 7226.98 | 0.73 | 3.40 | |||
PSZ-AC_8:8 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27181.19 | 19947.19 | 7234.00 | 0.73 | 3.40 | |||
PSZ-AC_9:9 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27426.22 | 20134.41 | 7291.81 | 0.73 | 3.40 | |||
PSZ-AC_10:10 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32341.21 | 24006.56 | 8334.65 | 0.74 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 HP COOLING COIL | 51997.2 | 10.15 | 10.15 | ||||
PSZ-AC_2:2 HP COOLING COIL | 26783.1 | 10.67 | 10.67 | ||||
PSZ-AC_3:3 HP COOLING COIL | 26846.2 | 10.67 | 10.67 | ||||
PSZ-AC_4:4 HP COOLING COIL | 26904.0 | 10.67 | 10.67 | ||||
PSZ-AC_5:5 HP COOLING COIL | 26849.0 | 10.67 | 10.67 | ||||
PSZ-AC_6:6 HP COOLING COIL | 49637.5 | 10.17 | 10.17 | ||||
PSZ-AC_7:7 HP COOLING COIL | 26235.5 | 10.70 | 10.70 | ||||
PSZ-AC_8:8 HP COOLING COIL | 26228.6 | 10.71 | 10.71 | ||||
PSZ-AC_9:9 HP COOLING COIL | 26464.1 | 10.70 | 10.70 | ||||
PSZ-AC_10:10 HP COOLING COIL | 31177.3 | 10.66 | 10.66 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 56321.6 | 31071.3 | 7.89 | 2 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 29087.0 | 16050.4 | 7.81 | 2 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | 29157.5 | 16089.6 | 7.81 | 2 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | 29222.0 | 16125.5 | 7.81 | 2 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:DX:MultiSpeed | 29160.6 | 16091.3 | 7.81 | 2 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:DX:MultiSpeed | 53810.2 | 29675.3 | 7.82 | 2 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:DX:MultiSpeed | 28450.4 | 15691.5 | 7.83 | 2 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:DX:MultiSpeed | 28440.0 | 15685.3 | 7.84 | 2 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:DX:MultiSpeed | 28697.7 | 15827.8 | 7.83 | 2 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:DX:MultiSpeed | 33879.7 | 18698.9 | 7.81 | 2 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 54384.37 | 3.40 | |
PSZ-AC_1:1_SUPPHEATCOIL | Coil:Heating:Electric | 54384.37 | 1.00 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 28078.40 | 3.40 | |
PSZ-AC_2:2_SUPPHEATCOIL | Coil:Heating:Electric | 28078.40 | 1.00 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | 28145.70 | 3.40 | |
PSZ-AC_3:3_SUPPHEATCOIL | Coil:Heating:Electric | 28145.70 | 1.00 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | 28207.31 | 3.40 | |
PSZ-AC_4:4_SUPPHEATCOIL | Coil:Heating:Electric | 28207.31 | 1.00 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:DX:MultiSpeed | 28148.66 | 3.40 | |
PSZ-AC_5:5_SUPPHEATCOIL | Coil:Heating:Electric | 28148.66 | 1.00 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:DX:MultiSpeed | 51982.03 | 3.40 | |
PSZ-AC_6:6_SUPPHEATCOIL | Coil:Heating:Electric | 51982.03 | 1.00 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:DX:MultiSpeed | 27480.13 | 3.40 | |
PSZ-AC_7:7_SUPPHEATCOIL | Coil:Heating:Electric | 27480.13 | 1.00 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:DX:MultiSpeed | 27471.27 | 3.40 | |
PSZ-AC_8:8_SUPPHEATCOIL | Coil:Heating:Electric | 27471.27 | 1.00 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:DX:MultiSpeed | 27719.26 | 3.40 | |
PSZ-AC_9:9_SUPPHEATCOIL | Coil:Heating:Electric | 27719.26 | 1.00 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:DX:MultiSpeed | 32696.51 | 3.40 | |
PSZ-AC_10:10_SUPPHEATCOIL | Coil:Heating:Electric | 32696.51 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 2.42 | 3925.37 | 1622.12 | 1.00 | 1.23 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.26 | 2094.58 | 1662.00 | 1.00 | 1.29 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.26 | 2101.22 | 1662.00 | 1.00 | 1.29 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.27 | 2107.31 | 1662.00 | 1.00 | 1.29 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.26 | 2101.51 | 1662.00 | 1.00 | 1.29 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 2.28 | 3793.75 | 1662.00 | 1.00 | 1.21 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.21 | 2013.69 | 1662.00 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.21 | 2010.54 | 1662.00 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.22 | 2030.67 | 1662.00 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.48 | 2457.83 | 1662.00 | 1.00 | 1.26 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.19 | 11712.00 | 1.00 | 1.00 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 27448.01 | 31565.21 | 90.60 | 2.086 | 2.399 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 23.89 | 23.88 | 0.00957 | 34.40 | 0.01447 | 0.411 | 0.00 |
SMSTORE1 | 14422.00 | 16585.30 | 95.21 | 1.096 | 1.260 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.88 | 0.00955 | 34.40 | 0.01447 | 0.206 | 0.00 |
SMSTORE2 | 14603.76 | 16794.33 | 96.41 | 1.084 | 1.246 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00922 | 29.17 | 0.01446 | 0.206 | 0.00 |
SMSTORE3 | 14525.72 | 16704.58 | 95.90 | 1.078 | 1.240 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00922 | 29.17 | 0.01446 | 0.206 | 0.00 |
SMSTORE4 | 14604.15 | 16794.78 | 96.41 | 1.084 | 1.246 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00922 | 29.17 | 0.01446 | 0.206 | 0.00 |
LGSTORE2 | 25930.65 | 29820.25 | 85.60 | 1.970 | 2.266 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.89 | 0.00959 | 34.40 | 0.01447 | 0.411 | 0.00 |
SMSTORE5 | 13430.13 | 15444.65 | 88.66 | 1.021 | 1.174 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.00961 | 34.32 | 0.01447 | 0.206 | 0.00 |
SMSTORE6 | 13364.63 | 15369.32 | 88.23 | 1.016 | 1.168 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.00962 | 34.32 | 0.01447 | 0.206 | 0.00 |
SMSTORE7 | 13417.15 | 15429.73 | 88.58 | 1.020 | 1.172 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.00961 | 34.32 | 0.01447 | 0.206 | 0.00 |
SMSTORE8 | 14952.73 | 17195.64 | 98.72 | 1.136 | 1.307 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.88 | 0.00957 | 33.92 | 0.01447 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 25470.49 | 31838.11 | 91.39 | 1.936 | 2.420 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00719 | -6.30 | 0.00230 | 0.411 | 0.00 |
SMSTORE1 | 12078.25 | 15097.81 | 86.67 | 0.918 | 1.148 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00715 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE2 | 12238.89 | 15298.61 | 87.83 | 0.930 | 1.163 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00716 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE3 | 12298.73 | 15373.41 | 88.25 | 0.935 | 1.168 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00716 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE4 | 12383.73 | 15479.67 | 88.86 | 0.941 | 1.177 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00716 | -6.30 | 0.00230 | 0.206 | 0.00 |
LGSTORE2 | 24025.13 | 30031.41 | 86.20 | 1.826 | 2.283 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00721 | -6.30 | 0.00230 | 0.411 | 0.00 |
SMSTORE5 | 12752.47 | 15940.59 | 91.51 | 0.969 | 1.212 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00718 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE6 | 12732.51 | 15915.63 | 91.37 | 0.968 | 1.210 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00718 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE7 | 12860.03 | 16075.04 | 92.28 | 0.977 | 1.222 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00719 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE8 | 15565.99 | 19457.49 | 111.70 | 1.183 | 1.479 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00721 | -6.30 | 0.00230 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.40 | 2.40 | 2.42 | 2.42 | 2.4199 | 2.4199 | 2.4199 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.26 | 1.26 | 1.15 | 1.15 | 1.2603 | 1.2603 | 1.2603 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.26 | 1.26 | 1.16 | 1.16 | 1.2643 | 1.2463 | 1.2643 | 0.9858 | 1.0000 |
PSZ-AC_4:4 | 1.27 | 1.27 | 1.17 | 1.17 | 1.2679 | 1.2395 | 1.2679 | 0.9776 | 1.0000 |
PSZ-AC_5:5 | 1.26 | 1.26 | 1.18 | 1.18 | 1.2644 | 1.2464 | 1.2644 | 0.9857 | 1.0000 |
PSZ-AC_6:6 | 2.27 | 2.27 | 2.28 | 2.28 | 2.2826 | 2.2826 | 2.2826 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.17 | 1.17 | 1.21 | 1.21 | 1.2116 | 1.2116 | 1.2116 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.17 | 1.17 | 1.21 | 1.21 | 1.2097 | 1.2097 | 1.2097 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.17 | 1.17 | 1.22 | 1.22 | 1.2218 | 1.2218 | 1.2218 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.31 | 1.31 | 1.48 | 1.48 | 1.4788 | 1.4788 | 1.4788 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 53902.440 | 39684.054 | 2.419900 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 26951.22 | 20322.14 | 1.613267 | 25.69 | 18.15 | 0.01041257 | 11.41 | 11.20 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 25.5059 | 23.88 | 0.00957170 | 49.9372 | 27448.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 54384.370 | 54384.370 | 2.419895 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27192.19 | 22593.07 | 1.209948 | 16.45 | 11.13 | 0.00636029 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 34.0080 | 21.11 | 0.00719260 | 44.5948 | 25470.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_1:1 | 54384.370 | 54384.370 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 54384.37 | 45186.15 | 2.419895 | 16.45 | 11.13 | 0.00636029 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 17.0040 | 21.11 | 0.00719260 | 44.5948 | 25470.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 27775.100 | 20557.740 | 1.260280 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 13887.55 | 10542.21 | 0.840187 | 25.60 | 18.07 | 0.01034959 | 11.38 | 11.19 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 24.4873 | 23.88 | 0.00954506 | 49.8000 | 14422.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28078.404 | 28078.404 | 1.260276 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 14039.20 | 11627.46 | 0.630138 | 16.63 | 11.20 | 0.00635553 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 32.6499 | 21.11 | 0.00714719 | 44.3162 | 12078.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_2:2 | 28078.404 | 28078.404 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28078.40 | 23254.91 | 1.260276 | 16.63 | 11.20 | 0.00635553 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.3249 | 21.11 | 0.00714719 | 44.3162 | 12078.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 27841.390 | 20612.652 | 1.264270 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 13920.69 | 10573.23 | 0.842847 | 25.60 | 18.07 | 0.01034465 | 11.38 | 11.19 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 24.4101 | 23.88 | 0.00954220 | 49.7853 | 14467.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 28145.699 | 28145.699 | 1.264272 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 14072.85 | 11653.74 | 0.632136 | 16.65 | 11.22 | 0.00636540 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 32.5467 | 21.11 | 0.00715599 | 44.3702 | 12238.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_3:3 | 28145.699 | 28145.699 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28145.70 | 23307.48 | 1.264272 | 16.65 | 11.22 | 0.00636540 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.2734 | 21.11 | 0.00715599 | 44.3702 | 12238.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 27902.070 | 20663.157 | 1.267940 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 13951.03 | 10601.70 | 0.845293 | 25.59 | 18.06 | 0.01034011 | 11.38 | 11.19 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 24.3394 | 23.88 | 0.00953954 | 49.7716 | 14509.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 28207.305 | 28207.305 | 1.267937 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 14103.65 | 11677.84 | 0.633968 | 16.66 | 11.23 | 0.00637040 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 32.4526 | 21.11 | 0.00715923 | 44.3900 | 12298.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_4:4 | 28207.305 | 28207.305 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28207.31 | 23355.69 | 1.267937 | 16.66 | 11.23 | 0.00637040 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.2263 | 21.11 | 0.00715923 | 44.3900 | 12298.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 27844.310 | 20615.092 | 1.264450 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 13922.16 | 10574.59 | 0.842967 | 25.60 | 18.06 | 0.01034444 | 11.38 | 11.19 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 24.4066 | 23.88 | 0.00954208 | 49.7847 | 14469.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 28148.658 | 28148.658 | 1.264446 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 14074.33 | 11654.88 | 0.632223 | 16.65 | 11.23 | 0.00637202 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 32.5422 | 21.11 | 0.00716377 | 44.4178 | 12383.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_5:5 | 28148.658 | 28148.658 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28148.66 | 23309.77 | 1.264446 | 16.65 | 11.23 | 0.00637202 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.2711 | 21.11 | 0.00716377 | 44.4178 | 12383.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 51434.980 | 37655.035 | 2.282640 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 25717.49 | 19263.99 | 1.521760 | 25.79 | 18.23 | 0.01047821 | 11.38 | 11.19 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 27.0397 | 23.89 | 0.00959178 | 50.0398 | 25930.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 51982.028 | 51982.028 | 2.282643 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25991.01 | 21689.89 | 1.141322 | 16.17 | 10.98 | 0.00632692 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 36.0528 | 21.11 | 0.00721295 | 44.7187 | 24025.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_6:6 | 51982.028 | 51982.028 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 51982.03 | 43379.79 | 2.282643 | 16.17 | 10.98 | 0.00632692 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 18.0264 | 21.11 | 0.00721295 | 44.7187 | 24025.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 27189.530 | 19962.553 | 1.211610 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 13594.76 | 10188.65 | 0.807740 | 25.73 | 18.20 | 0.01046535 | 11.38 | 11.19 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 25.4710 | 23.88 | 0.00961329 | 50.1506 | 13428.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 27480.129 | 27480.129 | 1.211608 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 13740.06 | 11307.33 | 0.605804 | 16.45 | 11.13 | 0.00635333 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 33.9614 | 21.11 | 0.00718285 | 44.5348 | 12752.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_7:7 | 27480.129 | 27480.129 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27480.13 | 22614.66 | 1.211608 | 16.45 | 11.13 | 0.00635333 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.9807 | 21.11 | 0.00718285 | 44.5348 | 12752.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 27181.190 | 19947.188 | 1.209710 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 13590.59 | 10176.51 | 0.806473 | 25.74 | 18.21 | 0.01047350 | 11.38 | 11.19 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 25.5110 | 23.88 | 0.00961811 | 50.1753 | 13363.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 27471.267 | 27471.267 | 1.209711 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 13735.63 | 11294.85 | 0.604856 | 16.45 | 11.12 | 0.00635118 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 34.0146 | 21.11 | 0.00718182 | 44.5285 | 12732.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_8:8 | 27471.267 | 27471.267 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27471.27 | 22589.71 | 1.209711 | 16.45 | 11.12 | 0.00635118 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 17.0073 | 21.11 | 0.00718182 | 44.5285 | 12732.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 27426.220 | 20134.411 | 1.221830 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 13713.11 | 10275.40 | 0.814553 | 25.73 | 18.20 | 0.01046709 | 11.38 | 11.19 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 25.2579 | 23.88 | 0.00961433 | 50.1559 | 13414.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 27719.257 | 27719.257 | 1.221828 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 13859.63 | 11374.55 | 0.610914 | 16.49 | 11.15 | 0.00636480 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 33.6773 | 21.11 | 0.00718829 | 44.5682 | 12860.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_9:9 | 27719.257 | 27719.257 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27719.26 | 22749.10 | 1.221828 | 16.49 | 11.15 | 0.00636480 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.8387 | 21.11 | 0.00718829 | 44.5682 | 12860.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 32341.210 | 24006.557 | 1.478840 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 16170.60 | 12259.50 | 0.985893 | 25.49 | 18.03 | 0.01034577 | 11.38 | 11.19 | 0.00850000 | 34.08 | 0.01447268 | 23.46 | 20.8683 | 23.88 | 0.00957330 | 49.9459 | 14932.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 32696.508 | 32696.508 | 1.478839 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 16348.25 | 13065.53 | 0.739420 | 17.29 | 11.65 | 0.00652979 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 27.8244 | 21.11 | 0.00721370 | 44.7254 | 15565.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_10:10 | 32696.508 | 32696.508 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32696.51 | 26131.07 | 1.478839 | 17.29 | 11.65 | 0.00652979 | 32.22 | 18.37 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 13.9122 | 21.11 | 0.00721370 | 44.7254 | 15565.99 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 53902.440 | 39684.054 | 2.419900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1964 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.419895 | 2.80944176 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 26951.22 | 20322.14 | 1.0000 | 1.87296475 | 1.613267 | 25.69 | 18.15 | 0.01041257 | 52351.5 | 11.41 | 11.20 | 0.00850000 | 32908.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26951.22 | 34.40 | 0.01447326 | 23.54 | 0.41147883 | 25.5059 | 23.88 | 0.00957170 | 23.88 | 0.00957170 | 49.9372 | 27448.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 54384.370 | 54384.370 | 2.419895 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.419895 | 2.80944176 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27192.19 | 22593.07 | 1.0000 | 1.40472088 | 1.209948 | 16.45 | 11.13 | 0.00636029 | 32628.0 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27192.19 | -6.30 | 0.00229779 | -6.30 | 0.41147883 | 34.0080 | 21.11 | 0.00719260 | 21.11 | 0.00719260 | 44.5948 | 25470.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54384.370 | 54384.370 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.419895 | 2.80944176 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 54384.37 | 45186.15 | 1.0000 | 2.80944176 | 2.419895 | 16.45 | 11.13 | 0.00636029 | 32628.0 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54384.37 | -6.30 | 0.00229779 | -6.30 | 0.41147883 | 17.0040 | 21.11 | 0.00719260 | 21.11 | 0.00719260 | 44.5948 | 25470.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27775.100 | 20557.740 | 1.260280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0794 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.260276 | 1.46315099 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 13887.55 | 10542.21 | 1.0000 | 0.97543701 | 0.840187 | 25.60 | 18.07 | 0.01034959 | 52101.7 | 11.38 | 11.19 | 0.00850000 | 32873.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13887.55 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 24.4873 | 23.88 | 0.00954506 | 23.88 | 0.00954506 | 49.8000 | 14422.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 28078.404 | 28078.404 | 1.260276 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.260276 | 1.46315099 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 14039.20 | 11627.46 | 1.0000 | 0.73157550 | 0.630138 | 16.63 | 11.20 | 0.00635553 | 32805.3 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14039.20 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 32.6499 | 21.11 | 0.00714719 | 21.11 | 0.00714719 | 44.3162 | 12078.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28078.404 | 28078.404 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.260276 | 1.46315099 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28078.40 | 23254.91 | 1.0000 | 1.46315099 | 1.260276 | 16.63 | 11.20 | 0.00635553 | 32805.3 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28078.40 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 16.3249 | 21.11 | 0.00714719 | 21.11 | 0.00714719 | 44.3162 | 12078.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27841.390 | 20612.652 | 1.264270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0702 | 1004.8586 | 1.1610 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.264272 | 1.46778986 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 13920.69 | 10573.23 | 1.0000 | 0.97852521 | 0.842847 | 25.60 | 18.07 | 0.01034465 | 52083.6 | 11.38 | 11.19 | 0.00850000 | 32873.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13920.69 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 24.4101 | 23.88 | 0.00954220 | 23.88 | 0.00954220 | 49.7853 | 14467.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 28145.699 | 28145.699 | 1.264272 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.264272 | 1.46778986 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 14072.85 | 11653.74 | 1.0000 | 0.73389493 | 0.632136 | 16.65 | 11.22 | 0.00636540 | 32844.7 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14072.85 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 32.5467 | 21.11 | 0.00715599 | 21.11 | 0.00715599 | 44.3702 | 12238.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28145.699 | 28145.699 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.264272 | 1.46778986 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28145.70 | 23307.48 | 1.0000 | 1.46778986 | 1.264272 | 16.65 | 11.22 | 0.00636540 | 32844.7 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28145.70 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 16.2734 | 21.11 | 0.00715599 | 21.11 | 0.00715599 | 44.3702 | 12238.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27902.070 | 20663.157 | 1.267940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0617 | 1004.8586 | 1.1610 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.267937 | 1.47204465 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 13951.03 | 10601.70 | 1.0000 | 0.98136573 | 0.845293 | 25.59 | 18.06 | 0.01034011 | 52067.0 | 11.38 | 11.19 | 0.00850000 | 32873.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13951.03 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 24.3394 | 23.88 | 0.00953954 | 23.88 | 0.00953954 | 49.7716 | 14509.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 28207.305 | 28207.305 | 1.267937 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.267937 | 1.47204465 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 14103.65 | 11677.84 | 1.0000 | 0.73602232 | 0.633968 | 16.66 | 11.23 | 0.00637040 | 32870.5 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14103.65 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 32.4526 | 21.11 | 0.00715923 | 21.11 | 0.00715923 | 44.3900 | 12298.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28207.305 | 28207.305 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.267937 | 1.47204465 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28207.31 | 23355.69 | 1.0000 | 1.47204465 | 1.267937 | 16.66 | 11.23 | 0.00637040 | 32870.5 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28207.31 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 16.2263 | 21.11 | 0.00715923 | 21.11 | 0.00715923 | 44.3900 | 12298.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27844.310 | 20615.092 | 1.264450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0698 | 1004.8586 | 1.1610 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.264446 | 1.46799238 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 13922.16 | 10574.59 | 1.0000 | 0.97866452 | 0.842967 | 25.60 | 18.06 | 0.01034444 | 52082.8 | 11.38 | 11.19 | 0.00850000 | 32873.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13922.16 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 24.4066 | 23.88 | 0.00954208 | 23.88 | 0.00954208 | 49.7847 | 14469.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 28148.658 | 28148.658 | 1.264446 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.264446 | 1.46799238 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 14074.33 | 11654.88 | 1.0000 | 0.73399619 | 0.632223 | 16.65 | 11.23 | 0.00637202 | 32862.1 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14074.33 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 32.5422 | 21.11 | 0.00716377 | 21.11 | 0.00716377 | 44.4178 | 12383.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28148.658 | 28148.658 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.264446 | 1.46799238 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28148.66 | 23309.77 | 1.0000 | 1.46799238 | 1.264446 | 16.65 | 11.23 | 0.00637202 | 32862.1 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28148.66 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 16.2711 | 21.11 | 0.00716377 | 21.11 | 0.00716377 | 44.4178 | 12383.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 51434.980 | 37655.035 | 2.282640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3185 | 1004.8586 | 1.1610 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.282643 | 2.65009509 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 25717.49 | 19263.99 | 1.0000 | 1.76672766 | 1.521760 | 25.79 | 18.23 | 0.01047821 | 52627.1 | 11.38 | 11.19 | 0.00850000 | 32874.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25717.49 | 34.40 | 0.01447326 | 23.54 | 0.41147883 | 27.0397 | 23.89 | 0.00959178 | 23.89 | 0.00959178 | 50.0398 | 25930.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 51982.028 | 51982.028 | 2.282643 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.282643 | 2.65009509 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 25991.01 | 21689.89 | 1.0000 | 1.32504754 | 1.141322 | 16.17 | 10.98 | 0.00632692 | 32258.9 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25991.01 | -6.30 | 0.00229779 | -6.30 | 0.41147883 | 36.0528 | 21.11 | 0.00721295 | 21.11 | 0.00721295 | 44.7187 | 24025.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51982.028 | 51982.028 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.282643 | 2.65009509 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 51982.03 | 43379.79 | 1.0000 | 2.65009509 | 2.282643 | 16.17 | 10.98 | 0.00632692 | 32258.9 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51982.03 | -6.30 | 0.00229779 | -6.30 | 0.41147883 | 18.0264 | 21.11 | 0.00721295 | 21.11 | 0.00721295 | 44.7187 | 24025.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27189.530 | 19962.553 | 1.211610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2946 | 1004.8586 | 1.1610 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.211608 | 1.40664836 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 13594.76 | 10188.65 | 1.0000 | 0.93776719 | 0.807740 | 25.73 | 18.20 | 0.01046535 | 52526.8 | 11.38 | 11.19 | 0.00850000 | 32874.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13594.76 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 25.4710 | 23.88 | 0.00961329 | 23.88 | 0.00961329 | 50.1506 | 13428.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 27480.129 | 27480.129 | 1.211608 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.211608 | 1.40664836 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 13740.06 | 11307.33 | 1.0000 | 0.70332418 | 0.605804 | 16.45 | 11.13 | 0.00635333 | 32617.1 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13740.06 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 33.9614 | 21.11 | 0.00718285 | 21.11 | 0.00718285 | 44.5348 | 12752.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27480.129 | 27480.129 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.211608 | 1.40664836 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27480.13 | 22614.66 | 1.0000 | 1.40664836 | 1.211608 | 16.45 | 11.13 | 0.00635333 | 32617.1 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27480.13 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 16.9807 | 21.11 | 0.00718285 | 21.11 | 0.00718285 | 44.5348 | 12752.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27181.190 | 19947.188 | 1.209710 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3097 | 1004.8586 | 1.1610 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.209711 | 1.40444623 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 13590.59 | 10176.51 | 1.0000 | 0.93629662 | 0.806473 | 25.74 | 18.21 | 0.01047350 | 52556.8 | 11.38 | 11.19 | 0.00850000 | 32874.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13590.59 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 25.5110 | 23.88 | 0.00961811 | 23.88 | 0.00961811 | 50.1753 | 13363.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 27471.267 | 27471.267 | 1.209711 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.209711 | 1.40444623 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 13735.63 | 11294.85 | 1.0000 | 0.70222312 | 0.604856 | 16.45 | 11.12 | 0.00635118 | 32604.2 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13735.63 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 34.0146 | 21.11 | 0.00718182 | 21.11 | 0.00718182 | 44.5285 | 12732.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27471.267 | 27471.267 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.209711 | 1.40444623 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27471.27 | 22589.71 | 1.0000 | 1.40444623 | 1.209711 | 16.45 | 11.12 | 0.00635118 | 32604.2 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27471.27 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 17.0073 | 21.11 | 0.00718182 | 21.11 | 0.00718182 | 44.5285 | 12732.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27426.220 | 20134.411 | 1.221830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2978 | 1004.8586 | 1.1610 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.221828 | 1.41851311 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 13713.11 | 10275.40 | 1.0000 | 0.94567731 | 0.814553 | 25.73 | 18.20 | 0.01046709 | 52533.2 | 11.38 | 11.19 | 0.00850000 | 32874.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13713.11 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 25.2579 | 23.88 | 0.00961433 | 23.88 | 0.00961433 | 50.1559 | 13414.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 27719.257 | 27719.257 | 1.221828 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.221828 | 1.41851311 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 13859.63 | 11374.55 | 1.0000 | 0.70925656 | 0.610914 | 16.49 | 11.15 | 0.00636480 | 32685.7 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13859.63 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 33.6773 | 21.11 | 0.00718829 | 21.11 | 0.00718829 | 44.5682 | 12860.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27719.257 | 27719.257 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.221828 | 1.41851311 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27719.26 | 22749.10 | 1.0000 | 1.41851311 | 1.221828 | 16.49 | 11.15 | 0.00636480 | 32685.7 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27719.26 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 16.8387 | 21.11 | 0.00718829 | 21.11 | 0.00718829 | 44.5682 | 12860.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32341.210 | 24006.557 | 1.478840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0723 | 1004.8586 | 1.1610 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.478839 | 1.71689792 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 16170.60 | 12259.50 | 1.0000 | 1.14459903 | 0.985893 | 25.49 | 18.03 | 0.01034577 | 51980.9 | 11.38 | 11.19 | 0.00850000 | 32873.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16170.60 | 34.08 | 0.01447268 | 23.46 | 0.20573941 | 20.8683 | 23.89 | 0.00957330 | 23.88 | 0.00957330 | 49.9459 | 14932.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 32696.508 | 32696.508 | 1.478839 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.478839 | 1.71689792 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 16348.25 | 13065.53 | 1.0000 | 0.85844896 | 0.739420 | 17.29 | 11.65 | 0.00652979 | 33918.5 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16348.25 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 27.8244 | 21.11 | 0.00721370 | 21.11 | 0.00721370 | 44.7254 | 15565.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32696.508 | 32696.508 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.478839 | 1.71689792 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32696.51 | 26131.07 | 1.0000 | 1.71689792 | 1.478839 | 17.29 | 11.65 | 0.00652979 | 33918.5 | 32.22 | 18.37 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32696.51 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 13.9122 | 21.11 | 0.00721370 | 21.11 | 0.00721370 | 44.7254 | 15565.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3448.17 | 2052.83 | 448.83 |
SMSTORE1 | 3271.83 | 1757.50 | 180.33 |
SMSTORE2 | 2644.50 | 1427.83 | 291.83 |
SMSTORE3 | 2653.50 | 1458.83 | 312.00 |
SMSTORE4 | 2648.33 | 1512.67 | 337.67 |
LGSTORE2 | 2430.00 | 1489.83 | 374.67 |
SMSTORE5 | 2376.00 | 1550.33 | 385.50 |
SMSTORE6 | 2374.83 | 1575.17 | 402.33 |
SMSTORE7 | 2392.83 | 1620.17 | 444.33 |
SMSTORE8 | 2492.67 | 1756.50 | 620.67 |
Facility | 3945.83 | 2622.50 | 904.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 6.83 | 0.00 | 3.17 | 0.00 |
SMSTORE1 | 2.17 | 0.00 | 1.17 | 0.00 |
SMSTORE2 | 3.00 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 3.83 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 4.33 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 5.83 | 0.17 | 0.00 | 0.00 |
SMSTORE5 | 5.67 | 0.17 | 0.00 | 0.00 |
SMSTORE6 | 5.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 7.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 16.33 | 0.00 | 0.00 | 0.00 |
Facility | 23.50 | 0.33 | 3.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.836 | 0.227 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.693 | 0.241 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.836 | 0.314 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.836 | 0.314 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.836 | 0.314 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.836 | 0.302 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.836 | 0.335 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.836 | 0.335 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.836 | 0.335 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.836 | 0.355 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.788 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8812287.46 | 0.00 | 8812287.46 | 2731052.24 | 11543339.70 | 12976396.34 | 2814.44 | 5945.56 | 0.00 | 115.53 |
SMSTORE1 | 3662792.37 | 0.00 | 3662792.37 | 1359523.50 | 5022315.87 | 6488198.17 | 4285.33 | 4474.67 | 0.00 | 107.83 |
SMSTORE2 | 3525550.60 | 0.00 | 3525550.60 | 1395493.01 | 4921043.61 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525550.60 | 0.00 | 3525550.60 | 1395493.01 | 4921043.61 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525550.60 | 0.00 | 3525550.60 | 1395493.01 | 4921043.61 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6513791.58 | 0.00 | 6513791.58 | 2566144.11 | 9079935.70 | 12976396.34 | 4363.24 | 4396.76 | 0.00 | 368.30 |
SMSTORE5 | 3256835.93 | 0.00 | 3256835.93 | 1406000.65 | 4662836.58 | 6488198.17 | 4363.14 | 4396.86 | 0.00 | 368.03 |
SMSTORE6 | 3256938.03 | 0.00 | 3256938.03 | 1406000.65 | 4662938.68 | 6488198.17 | 4363.14 | 4396.86 | 0.00 | 368.44 |
SMSTORE7 | 3257989.75 | 0.00 | 3257989.75 | 1406000.65 | 4663990.40 | 6488198.17 | 4362.31 | 4397.69 | 0.00 | 370.59 |
SMSTORE8 | 3273905.01 | 0.00 | 3273905.01 | 1733578.79 | 5007483.80 | 6488198.17 | 4357.03 | 4402.97 | 0.00 | 429.93 |
Total Facility | 42611191.94 | 0.00 | 42611191.94 | 16794779.62 | 59405971.56 | 77858378.04 | 4364.98 | 6254.88 | 0.00 | 792.19 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1116 | 0.5231 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1705 | 0.0000 | 0.1705 | 0.0593 | 0.2298 | 0.2057 | 1468.67 | 4371.33 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.0773 | 0.2831 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.0773 | 0.2831 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.0773 | 0.2831 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.1485 | 0.5600 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.0824 | 0.2882 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.0824 | 0.2882 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.0824 | 0.2882 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.0873 | 0.2931 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4337 | 0.0000 | 2.4337 | 0.8860 | 3.3197 | 2.4689 | 1468.67 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 11877787.30 | 0.00 | 11877787.30 | 12976396.34 | 2813.64 | 0.00 | 5946.36 | 115.53 |
PSZ-AC_2:2 | 4936955.24 | 0.00 | 4936955.24 | 6488198.17 | 4177.08 | 13.28 | 4569.64 | 107.67 |
PSZ-AC_3:3 | 4751971.65 | 0.00 | 4751971.65 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 4751971.65 | 0.00 | 4751971.65 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 4751971.65 | 0.00 | 4751971.65 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 8779721.64 | 0.00 | 8779721.64 | 12976396.34 | 4362.96 | 0.06 | 4396.99 | 368.30 |
PSZ-AC_7:7 | 4389780.13 | 0.00 | 4389780.13 | 6488198.17 | 4362.97 | 0.00 | 4397.03 | 368.03 |
PSZ-AC_8:8 | 4389917.75 | 0.00 | 4389917.75 | 6488198.17 | 4363.05 | 0.00 | 4396.95 | 368.44 |
PSZ-AC_9:9 | 4391335.32 | 0.00 | 4391335.32 | 6488198.17 | 4361.72 | 0.00 | 4398.28 | 370.59 |
PSZ-AC_10:10 | 4412786.98 | 0.00 | 4412786.98 | 6488198.17 | 4353.16 | 0.47 | 4406.37 | 429.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5546 | 0.0000 | 0.5546 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2299 | 0.0000 | 0.2299 | 0.2057 | 1360.75 | 13.28 | 4465.97 |
PSZ-AC_3:3 | 0.2773 | 0.0000 | 0.2773 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2773 | 0.0000 | 0.2773 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2773 | 0.0000 | 0.2773 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5546 | 0.0000 | 0.5546 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2773 | 0.0000 | 0.2773 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2773 | 0.0000 | 0.2773 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2773 | 0.0000 | 0.2773 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2773 | 0.0000 | 0.2773 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5955.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5716.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4398.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4398.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4398.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4400.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4459.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5546 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2394 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2774 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2774 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2774 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5548 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2774 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2774 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2774 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2774 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 786 |
Defaulted Fields | 863 |
Fields with Defaults | 2832 |
Autosized Fields | 222 |
Autosizable Fields | 564 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1750.15 | 2476.63 | 01-JAN-08:00 | 173590.15 | 12-FEB-09:10 |
Electricity:Building | 747.30 | 2476.63 | 01-JAN-00:10 | 46719.60 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 164.11 | 450.38 | 01-JAN-00:10 | 8500.73 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 747.30 | 2476.63 | 01-JAN-00:10 | 46719.60 | 01-JAN-11:10 |
InteriorLights:Electricity | 619.14 | 2034.80 | 01-JAN-00:10 | 38660.10 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 137.86 | 376.74 | 01-JAN-00:10 | 7157.48 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 619.14 | 2034.80 | 01-JAN-00:10 | 38660.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 619.14 | 2034.80 | 01-JAN-00:10 | 38660.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 137.86 | 376.74 | 01-JAN-00:10 | 7157.48 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 619.14 | 2034.80 | 01-JAN-00:10 | 38660.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 92.19 | 252.86 | 01-JAN-00:10 | 4776.42 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 79.06 | 216.04 | 01-JAN-00:10 | 4104.79 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 79.06 | 216.04 | 01-JAN-00:10 | 4104.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 69.31 | 238.01 | 01-JAN-00:10 | 4494.25 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 69.31 | 238.01 | 01-JAN-00:10 | 4494.25 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 69.31 | 238.01 | 01-JAN-00:10 | 4494.25 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 93.40 | 349.58 | 01-JAN-00:10 | 6585.71 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 74.23 | 275.95 | 01-JAN-00:10 | 5242.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 74.23 | 275.95 | 01-JAN-00:10 | 5242.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 47.42 | 177.44 | 01-JAN-00:10 | 3343.50 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 47.42 | 177.44 | 01-JAN-00:10 | 3343.50 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 47.42 | 177.44 | 01-JAN-00:10 | 3343.50 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 47.42 | 177.44 | 01-JAN-00:10 | 3343.50 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1750.15 | 2476.63 | 01-JAN-08:00 | 173590.15 | 12-FEB-09:10 |
ElectricityPurchased:Plant | 1750.15 | 2476.63 | 01-JAN-08:00 | 173590.15 | 12-FEB-09:10 |
Cogeneration:ElectricityPurchased | 1750.15 | 2476.63 | 01-JAN-08:00 | 173590.15 | 12-FEB-09:10 |
General:Cogeneration:ElectricityPurchased | 1750.15 | 2476.63 | 01-JAN-08:00 | 173590.15 | 12-FEB-09:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1750.15 | 2476.63 | 01-JAN-08:00 | 173590.15 | 12-FEB-09:10 |
ElectricityNet:Plant | 1750.15 | 2476.63 | 01-JAN-08:00 | 173590.15 | 12-FEB-09:10 |
Cogeneration:ElectricityNet | 1750.15 | 2476.63 | 01-JAN-08:00 | 173590.15 | 12-FEB-09:10 |
General:Cogeneration:ElectricityNet | 1750.15 | 2476.63 | 01-JAN-08:00 | 173590.15 | 12-FEB-09:10 |
Electricity:HVAC | 808.59 | 0.00 | 01-JAN-00:10 | 161606.31 | 10-JAN-08:10 |
Cooling:Electricity | 339.82 | 0.00 | 01-JAN-00:10 | 76908.47 | 08-JUL-14:00 |
General:Cooling:Electricity | 339.82 | 0.00 | 01-JAN-00:10 | 76908.47 | 08-JUL-14:00 |
Heating:Electricity | 43.74 | 0.00 | 01-JAN-00:10 | 136969.86 | 10-JAN-08:10 |
General:Heating:Electricity | 43.74 | 0.00 | 01-JAN-00:10 | 136969.86 | 10-JAN-08:10 |
Fans:Electricity | 425.03 | 0.00 | 01-JAN-00:10 | 24636.45 | 01-JAN-17:00 |
General:Fans:Electricity | 425.03 | 0.00 | 01-JAN-00:10 | 24636.45 | 01-JAN-17:00 |
ExteriorLights:Electricity | 177.70 | 0.00 | 01-JAN-07:50 | 11300.38 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 177.70 | 0.00 | 01-JAN-07:50 | 11300.38 | 01-JAN-00:10 |
Electricity:Plant | 16.58 | 0.00 | 01-JAN-00:10 | 1663.73 | 03-FEB-13:40 |
WaterSystems:Electricity | 16.58 | 0.00 | 01-JAN-00:10 | 1663.73 | 03-FEB-13:40 |
Water Heater:WaterSystems:Electricity | 16.58 | 0.00 | 01-JAN-00:10 | 1663.73 | 03-FEB-13:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
Water:Plant | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
WaterSystems:Water | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
MainsWater:Facility | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
MainsWater:Plant | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
WaterSystems:MainsWater | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2118.41 | 0.00 | 01-JAN-00:10 | 381266.51 | 08-JUL-14:00 |
EnergyTransfer:Building | 752.03 | 0.00 | 01-JAN-00:10 | 160855.63 | 13-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 154.17 | 0.00 | 01-JAN-00:10 | 33331.70 | 12-FEB-08:10 |
Heating:EnergyTransfer | 49.53 | 0.00 | 01-JAN-00:10 | 160855.63 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 5.99 | 0.00 | 01-JAN-00:10 | 33331.70 | 12-FEB-08:10 |
General:Heating:EnergyTransfer | 49.53 | 0.00 | 01-JAN-00:10 | 160855.63 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 5.99 | 0.00 | 01-JAN-00:10 | 33331.70 | 12-FEB-08:10 |
Cooling:EnergyTransfer | 702.50 | 0.00 | 01-JAN-00:10 | 127879.22 | 08-JUL-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 148.18 | 0.00 | 01-JAN-00:10 | 21411.11 | 08-JUL-16:10 |
General:Cooling:EnergyTransfer | 702.50 | 0.00 | 01-JAN-00:10 | 127879.22 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 148.18 | 0.00 | 01-JAN-00:10 | 21411.11 | 08-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 83.81 | 0.00 | 01-JAN-00:10 | 14104.79 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.65 | 0.00 | 01-JAN-00:10 | 14104.79 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 1.65 | 0.00 | 01-JAN-00:10 | 14104.79 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 82.16 | 0.00 | 01-JAN-00:10 | 10932.16 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 82.16 | 0.00 | 01-JAN-00:10 | 10932.16 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 63.87 | 0.00 | 01-JAN-00:10 | 16132.35 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 3.34 | 0.00 | 01-JAN-00:10 | 16132.35 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 3.34 | 0.00 | 01-JAN-00:10 | 16132.35 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 60.53 | 0.00 | 01-JAN-00:10 | 11098.38 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 60.53 | 0.00 | 01-JAN-00:10 | 11098.38 | 08-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 63.81 | 0.00 | 01-JAN-00:10 | 16815.66 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 3.63 | 0.00 | 01-JAN-00:10 | 16815.66 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 3.63 | 0.00 | 01-JAN-00:10 | 16815.66 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 60.18 | 0.00 | 01-JAN-00:10 | 11168.46 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 60.18 | 0.00 | 01-JAN-00:10 | 11168.46 | 08-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 62.58 | 0.00 | 01-JAN-00:10 | 17245.66 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 4.03 | 0.00 | 01-JAN-00:10 | 17245.66 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 4.03 | 0.00 | 01-JAN-00:10 | 17245.66 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 58.55 | 0.00 | 01-JAN-00:10 | 11087.56 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 58.55 | 0.00 | 01-JAN-00:10 | 11087.56 | 08-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 105.55 | 0.00 | 01-JAN-00:10 | 31754.26 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 7.48 | 0.00 | 01-JAN-00:10 | 31754.26 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 7.48 | 0.00 | 01-JAN-00:10 | 31754.26 | 13-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 98.07 | 0.00 | 01-JAN-00:10 | 20356.20 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 98.07 | 0.00 | 01-JAN-00:10 | 20356.20 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 53.83 | 0.00 | 01-JAN-00:10 | 16249.44 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 4.37 | 0.00 | 01-JAN-00:10 | 16249.44 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 4.37 | 0.00 | 01-JAN-00:10 | 16249.44 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 49.47 | 0.00 | 01-JAN-00:10 | 10566.52 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 49.47 | 0.00 | 01-JAN-00:10 | 10566.52 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 53.24 | 0.00 | 01-JAN-00:10 | 16632.28 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 4.52 | 0.00 | 01-JAN-00:10 | 16632.28 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 4.52 | 0.00 | 01-JAN-00:10 | 16632.28 | 13-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 48.72 | 0.00 | 01-JAN-00:10 | 10508.57 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 48.72 | 0.00 | 01-JAN-00:10 | 10508.57 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 52.96 | 0.00 | 01-JAN-00:10 | 16427.88 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 5.08 | 0.00 | 01-JAN-00:10 | 16427.88 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 5.08 | 0.00 | 01-JAN-00:10 | 16427.88 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 47.88 | 0.00 | 01-JAN-00:10 | 10582.11 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 47.88 | 0.00 | 01-JAN-00:10 | 10582.11 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 58.21 | 0.00 | 01-JAN-00:10 | 19676.05 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 9.45 | 0.00 | 01-JAN-00:10 | 19676.05 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 9.45 | 0.00 | 01-JAN-00:10 | 19676.05 | 13-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 48.76 | 0.00 | 01-JAN-00:10 | 11876.31 | 08-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 48.76 | 0.00 | 01-JAN-00:10 | 11876.31 | 08-JUL-13:10 |
EnergyTransfer:HVAC | 1366.38 | 0.00 | 01-JAN-00:10 | 253467.42 | 08-JUL-14:00 |
CoolingCoils:EnergyTransfer | 1266.68 | 0.00 | 01-JAN-00:10 | 253467.42 | 08-JUL-14:00 |
HeatingCoils:EnergyTransfer | 99.70 | 0.00 | 01-JAN-00:10 | 214674.79 | 13-FEB-08:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 5.988 | -148.183 | 0.000 | 0.000 | 23.925 | 137.864 | 26.249 | 31.043 | 0.000 | 5.320 | 0.003 | 0.000 | -18.826 | 0.000 | -19.889 | -43.492 |
SMSTORE1 | 0.000 | 0.000 | 1.650 | -82.154 | 0.000 | 0.000 | 11.871 | 79.064 | 13.125 | 15.379 | 0.000 | 2.882 | 0.001 | 0.000 | -9.832 | 0.000 | -9.442 | -22.542 |
SMSTORE2 | 0.000 | 0.000 | 3.338 | -60.531 | 0.000 | 0.000 | 7.171 | 58.885 | 10.421 | 15.306 | 0.000 | 2.805 | 0.001 | 0.000 | -9.862 | 0.000 | -9.788 | -17.745 |
SMSTORE3 | 0.000 | 0.000 | 3.634 | -60.175 | 0.000 | 0.000 | 7.177 | 58.885 | 10.421 | 15.320 | 0.000 | 2.805 | 0.000 | 0.000 | -9.786 | 0.000 | -9.747 | -18.533 |
SMSTORE4 | 0.000 | 0.000 | 4.027 | -58.551 | 0.000 | 0.000 | 7.187 | 58.885 | 10.421 | 15.359 | 0.000 | 2.805 | 0.000 | 0.000 | -9.672 | 0.000 | -9.692 | -20.767 |
LGSTORE2 | 0.000 | 0.000 | 7.480 | -98.067 | 0.000 | 0.000 | 24.739 | 74.230 | 19.173 | 31.032 | 0.000 | 5.061 | 0.004 | 0.000 | -18.452 | 0.000 | -17.761 | -27.434 |
SMSTORE5 | 0.000 | 0.000 | 4.366 | -49.468 | 0.000 | 0.000 | 12.375 | 37.832 | 9.586 | 15.512 | 0.000 | 2.814 | 0.001 | 0.000 | -9.190 | 0.000 | -9.606 | -14.221 |
SMSTORE6 | 0.000 | 0.000 | 4.519 | -48.722 | 0.000 | 0.000 | 12.381 | 37.832 | 9.586 | 15.532 | 0.000 | 2.815 | 0.001 | 0.000 | -9.144 | 0.000 | -9.584 | -15.214 |
SMSTORE7 | 0.000 | 0.000 | 5.081 | -47.876 | 0.000 | 0.000 | 12.392 | 37.832 | 9.586 | 15.567 | 0.000 | 2.814 | 0.003 | 0.000 | -9.034 | 0.000 | -9.533 | -16.830 |
SMSTORE8 | 0.000 | 0.000 | 9.446 | -48.762 | 0.000 | 0.000 | 12.407 | 37.832 | 9.586 | 15.634 | 0.000 | 2.940 | 0.002 | 0.000 | -8.494 | 0.000 | -12.611 | -17.978 |
Total Facility | 0.000 | 0.000 | 49.527 | -702.489 | 0.000 | 0.000 | 131.625 | 619.141 | 128.154 | 185.683 | 0.000 | 33.061 | 0.016 | 0.000 | -112.292 | 0.000 | -117.654 | -214.756 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 05-JUN-07:02 | 0.00 | 0.00 | 0.00 | -35686.88 | 0.00 | 0.00 | 181.41 | 376.74 | 74.62 | 0.00 | 0.00 | 0.00 | 35187.73 | 0.00 | -4.13 | 0.00 | -129.49 | 0.00 |
SMSTORE1 | 05-JUN-07:02 | 0.00 | 0.00 | 0.00 | -19658.27 | 0.00 | 0.00 | 88.66 | 216.04 | 37.31 | 0.00 | 0.00 | 0.00 | 19402.38 | 0.00 | -15.43 | 0.00 | -70.70 | 0.00 |
SMSTORE2 | 26-AUG-06:02 | 0.00 | 0.00 | 0.00 | -19278.55 | 0.00 | 0.00 | 0.00 | 201.19 | 36.82 | 0.00 | 0.00 | 0.00 | 19358.05 | 0.00 | -309.50 | 0.00 | -8.01 | 0.00 |
SMSTORE3 | 26-AUG-06:02 | 0.00 | 0.00 | 0.00 | -19366.12 | 0.00 | 0.00 | 0.00 | 201.19 | 36.82 | 0.00 | 0.00 | 0.00 | 19448.45 | 0.00 | -312.19 | 0.00 | -8.15 | 0.00 |
SMSTORE4 | 26-AUG-06:02 | 0.00 | 0.00 | 0.00 | -19251.20 | 0.00 | 0.00 | 0.00 | 201.19 | 36.82 | 0.00 | 0.00 | 0.00 | 19329.22 | 0.00 | -308.09 | 0.00 | -7.94 | 0.00 |
LGSTORE2 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 | -35266.05 | 0.00 | 0.00 | 0.00 | 275.95 | 73.64 | 306.63 | 0.00 | 0.00 | 34672.03 | 0.00 | -0.00 | 0.00 | -62.20 | 0.00 |
SMSTORE5 | 05-JUN-07:02 | 0.00 | 0.00 | 0.00 | -18107.44 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 0.00 | 0.00 | 0.00 | 18028.99 | 0.00 | -23.35 | 0.00 | -75.65 | 0.00 |
SMSTORE6 | 05-JUN-07:02 | 0.00 | 0.00 | 0.00 | -18067.02 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 0.00 | 0.00 | 0.00 | 17986.19 | 0.00 | -21.68 | 0.00 | -74.94 | 0.00 |
SMSTORE7 | 05-JUN-07:02 | 0.00 | 0.00 | 0.00 | -18181.54 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 0.00 | 0.00 | 0.00 | 18097.17 | 0.00 | -19.27 | 0.00 | -73.81 | 0.00 |
SMSTORE8 | 15-JUN-07:02 | 0.00 | 0.00 | 0.00 | -19005.54 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 175.48 | 0.00 | 0.00 | 18701.03 | 0.00 | -0.00 | 0.00 | -48.42 | 0.00 |
Total Facility | 05-JUN-07:02 | 0.00 | 0.00 | 0.00 | -169651.41 | 0.00 | 0.00 | 565.58 | 7466.95 | 1452.23 | 39.81 | 0.00 | 0.00 | 161102.21 | 0.00 | -139.84 | 0.00 | -835.53 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 19-JAN-08:61 | 0.00 | 0.00 | 59856.83 | 0.00 | 0.00 | 0.00 | 245.63 | 376.74 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -258.15 | 0.00 | -465.12 | -59830.54 |
SMSTORE1 | 08-FEB-08:61 | 0.00 | 0.00 | 27083.16 | 0.00 | 0.00 | 0.00 | 126.29 | 216.04 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -491.83 | 0.00 | -284.21 | -26686.77 |
SMSTORE2 | 08-FEB-07:01 | 0.00 | 0.00 | 26444.79 | 0.00 | 0.00 | 0.00 | 0.00 | 201.19 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -530.89 | 0.00 | -51.36 | -26100.55 |
SMSTORE3 | 01-JAN-08:62 | 0.00 | 0.00 | 28929.71 | 0.00 | 0.00 | 0.00 | 0.00 | 201.19 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -322.07 | 0.00 | -232.74 | -28613.41 |
SMSTORE4 | 01-JAN-08:62 | 0.00 | 0.00 | 28952.52 | 0.00 | 0.00 | 0.00 | 0.00 | 201.19 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -303.99 | 0.00 | -223.93 | -28663.10 |
LGSTORE2 | 24-DEC-09:01 | 0.00 | 0.00 | 60150.21 | 0.00 | 0.00 | 0.00 | 0.00 | 275.95 | 73.64 | 79.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -292.38 | -60287.06 |
SMSTORE5 | 24-DEC-09:01 | 0.00 | 0.00 | 32072.57 | 0.00 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 42.14 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -158.38 | -32133.76 |
SMSTORE6 | 24-DEC-09:01 | 0.00 | 0.00 | 32772.14 | 0.00 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 46.24 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -157.01 | -32838.82 |
SMSTORE7 | 24-DEC-09:01 | 0.00 | 0.00 | 33111.79 | 0.00 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 57.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -151.36 | -33195.55 |
SMSTORE8 | 24-DEC-09:01 | 0.00 | 0.00 | 39017.98 | 0.00 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 95.54 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -183.47 | -39107.49 |
Total Facility | 11-FEB-08:61 | 0.00 | 0.00 | 261857.67 | 0.00 | 0.00 | 0.00 | 346.82 | 7466.95 | 1450.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4294.24 | 0.00 | -2745.15 | -264082.80 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4199 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.4199 | 0.1716 | 1.0000 | Not calculated | 0.4115 | 0.1700 | ||
PSZ-AC_2:2 | 1.2603 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2603 | 0.1632 | 1.0000 | Not calculated | 0.2057 | 0.1632 | ||
PSZ-AC_3:3 | 1.2463 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2643 | 0.1627 | 1.0000 | Not calculated | 0.2057 | 0.1627 | ||
PSZ-AC_4:4 | 1.2395 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2679 | 0.1623 | 1.0000 | Not calculated | 0.2057 | 0.1623 | ||
PSZ-AC_5:5 | 1.2464 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2644 | 0.1627 | 1.0000 | Not calculated | 0.2057 | 0.1627 | ||
PSZ-AC_6:6 | 2.2826 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2826 | 0.1816 | 1.0000 | Not calculated | 0.4115 | 0.1803 | ||
PSZ-AC_7:7 | 1.2116 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2116 | 0.1753 | 1.0000 | Not calculated | 0.2057 | 0.1698 | ||
PSZ-AC_8:8 | 1.2097 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2097 | 0.1762 | 1.0000 | Not calculated | 0.2057 | 0.1701 | ||
PSZ-AC_9:9 | 1.2218 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2218 | 0.1755 | 1.0000 | Not calculated | 0.2057 | 0.1684 | ||
PSZ-AC_10:10 | 1.4788 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4788 | 0.1575 | 1.0000 | Not calculated | 0.2057 | 0.1391 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4199 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.4199 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1700 | ||
PSZ-AC_2:2 | 1.2603 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2603 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1632 | ||
PSZ-AC_3:3 | 1.2463 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2463 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1651 | ||
PSZ-AC_4:4 | 1.2395 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2395 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1660 | ||
PSZ-AC_5:5 | 1.2464 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2464 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1651 | ||
PSZ-AC_6:6 | 2.2826 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2826 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1803 | ||
PSZ-AC_7:7 | 1.2116 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2116 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1698 | ||
PSZ-AC_8:8 | 1.2097 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2097 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1701 | ||
PSZ-AC_9:9 | 1.2218 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2218 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1684 | ||
PSZ-AC_10:10 | 1.4788 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4788 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1391 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4199 | 2.4199 | 2.4199 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2603 | 1.2603 | 1.2603 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2463 | 1.2463 | 1.2463 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2395 | 1.2395 | 1.2395 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2464 | 1.2464 | 1.2464 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2826 | 2.2826 | 2.2826 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2116 | 1.2116 | 1.2116 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2097 | 1.2097 | 1.2097 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2218 | 1.2218 | 1.2218 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4788 | 1.4788 | 1.4788 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4199 | 2.4199 | 2.4199 | 2.4199 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2603 | 1.2603 | 1.2603 | 1.2603 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2463 | 1.2643 | 1.2463 | 1.2463 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2395 | 1.2679 | 1.2395 | 1.2395 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2464 | 1.2644 | 1.2464 | 1.2464 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.2826 | 2.2826 | 2.2826 | 2.2826 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2116 | 1.2116 | 1.2116 | 1.2116 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2097 | 1.2097 | 1.2097 | 1.2097 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2218 | 1.2218 | 1.2218 | 1.2218 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.4788 | 1.4788 | 1.4788 | 1.4788 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4199 | 2.4199 | 2.4199 | No | 0.4115 | 0.1700 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2603 | 1.2603 | 1.2603 | No | 0.2057 | 0.1793 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2463 | 1.2463 | 1.2463 | No | 0.2057 | 0.1769 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2395 | 1.2395 | 1.2395 | No | 0.2057 | 0.1761 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2464 | 1.2464 | 1.2464 | No | 0.2057 | 0.1749 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2826 | 2.2826 | 2.2826 | No | 0.4115 | 0.1803 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2116 | 1.2116 | 1.2116 | No | 0.2057 | 0.1698 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2097 | 1.2097 | 1.2097 | No | 0.2057 | 0.1701 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2218 | 1.2218 | 1.2218 | No | 0.2057 | 0.1684 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4788 | 1.4788 | 1.4788 | No | 0.2057 | 0.1391 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4199 | 2.4199 | 2.4199 | 2.4199 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2603 | 1.2603 | 1.2603 | 1.2603 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2463 | 1.2463 | 1.2463 | 1.2463 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2395 | 1.2395 | 1.2395 | 1.2395 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2464 | 1.2464 | 1.2464 | 1.2464 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.2826 | 2.2826 | 2.2826 | 2.2826 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2116 | 1.2116 | 1.2116 | 1.2116 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2097 | 1.2097 | 1.2097 | 1.2097 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2218 | 1.2218 | 1.2218 | 1.2218 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.4788 | 1.4788 | 1.4788 | 1.4788 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 3.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 3.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 43.74 | 136969.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 339.82 | 76908.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 619.14 | 38660.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 177.70 | 11300.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 425.03 | 24636.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 16.58 | 1663.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1750.15 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1750.15 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 296.19 |
Space Heating | 20.92 |
Space Cooling | 162.57 |
Fans (All) | 203.33 |
Service Water Heating | 7.93 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 837.27 |
Subtotal | 837.27 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 35.38 |
Space Heating | 2.50 |
Space Cooling | 19.42 |
Fans (All) | 24.29 |
Service Water Heating | 0.95 |
Receptacle Equipment | 7.32 |
Miscellaneous | 10.15 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3758. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3767. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 5104. | 8760. |
LTG_SCH_BASE_LPD1 | 5091. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 4096. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8134.17 | 625.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8072.33 | 687.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8124.67 | 635.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8486.17 | 273.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8515.33 | 244.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8521.83 | 238.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8520.00 | 240.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8508.50 | 251.50 | 0.00 | 0.00 | 0.00 |
Min | 8072.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 687.67 | 0.00 | 0.00 | 0.00 |
Average | 8440.30 | 319.70 | 0.00 | 0.00 | 0.00 |
Sum | 84403.00 | 3197.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25382.83 | 92.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25382.83 | 92.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25384.33 | 90.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93008.00 | 203.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45812.00 | 100.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45813.50 | 98.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45813.00 | 99.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45808.00 | 104.00 | 0.00 | 0.00 | 0.00 |
Min | 25382.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93008.00 | 203.00 | 0.00 | 0.00 | 0.00 |
Average | 48522.25 | 87.95 | 0.00 | 0.00 | 0.00 |
Sum | 485222.50 | 879.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8057.50 | 702.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8446.00 | 314.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7219.83 | 1540.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7220.17 | 1539.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7235.83 | 1524.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 7426.17 | 1333.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 7457.33 | 1302.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 7466.67 | 1293.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 7473.00 | 1287.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 7406.00 | 1354.00 | 0.00 | 0.00 | 0.00 |
Min | 7219.83 | 314.00 | 0.00 | 0.00 | 0.00 |
Max | 8446.00 | 1540.17 | 0.00 | 0.00 | 0.00 |
Average | 7540.85 | 1219.15 | 0.00 | 0.00 | 0.00 |
Sum | 75408.50 | 12191.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 88861.33 | 179.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43740.17 | 36.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25312.67 | 162.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25312.83 | 162.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25308.67 | 166.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 92407.50 | 803.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45483.67 | 428.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45471.00 | 441.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45441.00 | 471.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45388.17 | 523.83 | 0.00 | 0.00 | 0.00 |
Min | 25308.67 | 36.83 | 0.00 | 0.00 | 0.00 |
Max | 92407.50 | 803.50 | 0.00 | 0.00 | 0.00 |
Average | 48272.70 | 337.50 | 0.00 | 0.00 | 0.00 |
Sum | 482727.00 | 3375.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200751E+10 | 7150.02 | 14-JAN-00:12 | -3.5 | -5.3 | 0.113204E+10 | 1685.85 | 29-JAN-17:49 | 14.60 | 5.92 |
February | 0.351162E+10 | 10866.13 | 26-FEB-15:30 | 24.70 | 12.55 | 0.111779E+10 | 1685.85 | 19-FEB-18:40 | 24.70 | 12.55 |
March | 0.772853E+10 | 15041.04 | 30-MAR-16:10 | 27.62 | 17.53 | 0.136549E+10 | 1685.91 | 11-MAR-13:00 | 27.62 | 17.53 |
April | 0.108880E+11 | 14887.00 | 17-APR-16:10 | 28.80 | 16.45 | 0.135546E+10 | 1686.00 | 23-APR-17:00 | 23.90 | 18.45 |
May | 0.156160E+11 | 16495.34 | 19-MAY-16:10 | 30.60 | 19.33 | 0.140098E+10 | 1686.03 | 07-MAY-17:00 | 30.60 | 19.33 |
June | 0.202653E+11 | 35695.89 | 05-JUN-07:02 | 21.05 | 17.87 | 0.135464E+10 | 1685.98 | 23-JUN-12:00 | 32.20 | 24.15 |
July | 0.227012E+11 | 34852.24 | 25-JUL-07:02 | 21.20 | 18.27 | 0.141291E+10 | 1685.99 | 07-JUL-12:39 | 21.20 | 18.27 |
August | 0.238047E+11 | 33670.21 | 27-AUG-07:02 | 21.38 | 19.77 | 0.139428E+10 | 1685.98 | 04-AUG-12:00 | 21.38 | 19.77 |
September | 0.178088E+11 | 34757.40 | 16-SEP-07:02 | 22.20 | 20.70 | 0.136521E+10 | 1686.01 | 01-SEP-12:09 | 22.20 | 20.70 |
October | 0.122835E+11 | 28366.15 | 18-OCT-07:03 | 19.50 | 19.50 | 0.140140E+10 | 1686.03 | 01-OCT-17:19 | 19.50 | 19.50 |
November | 0.763173E+10 | 12776.76 | 05-NOV-16:03 | 24.03 | 17.90 | 0.131399E+10 | 1686.01 | 05-NOV-17:40 | 20.00 | 17.57 |
December | 0.393806E+10 | 9349.30 | 12-DEC-14:30 | 22.80 | 16.62 | 0.123740E+10 | 1685.85 | 10-DEC-17:10 | 22.80 | 16.62 |
Annual Sum or Average | 0.148185E+12 | 0.158516E+11 | ||||||||
Minimum of Months | 0.200751E+10 | 7150.02 | -3.5 | -5.3 | 0.111779E+10 | 1685.85 | 14.60 | 5.92 | ||
Maximum of Months | 0.238047E+11 | 35695.89 | 30.60 | 20.70 | 0.141291E+10 | 1686.03 | 32.20 | 24.15 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120043E+10 | 4054.62 | 15-JAN-08:05 | -4.2 | -5.9 | 0.589406E+09 | 842.90 | 29-JAN-18:49 | 13.48 | 5.52 |
February | 0.227703E+10 | 6340.42 | 26-FEB-15:00 | 25.00 | 12.75 | 0.570367E+09 | 842.96 | 26-FEB-18:00 | 20.00 | 10.72 |
March | 0.482044E+10 | 8166.78 | 30-MAR-14:00 | 27.80 | 17.87 | 0.689886E+09 | 842.96 | 19-MAR-17:30 | 27.80 | 17.87 |
April | 0.648270E+10 | 8083.23 | 16-APR-14:00 | 28.90 | 16.19 | 0.679538E+09 | 842.98 | 23-APR-12:50 | 22.52 | 18.70 |
May | 0.881969E+10 | 10556.49 | 31-MAY-07:03 | 19.50 | 18.65 | 0.700659E+09 | 842.98 | 28-MAY-17:10 | 19.50 | 18.65 |
June | 0.108835E+11 | 19661.39 | 05-JUN-07:02 | 21.05 | 17.87 | 0.677336E+09 | 842.97 | 23-JUN-12:00 | 32.20 | 24.15 |
July | 0.120253E+11 | 19072.80 | 25-JUL-07:02 | 21.20 | 18.27 | 0.706455E+09 | 842.97 | 07-JUL-12:39 | 21.20 | 18.27 |
August | 0.124713E+11 | 18553.72 | 27-AUG-07:02 | 21.38 | 19.77 | 0.697130E+09 | 843.00 | 27-AUG-17:00 | 30.00 | 21.92 |
September | 0.961382E+10 | 19037.03 | 16-SEP-07:02 | 22.20 | 20.70 | 0.682618E+09 | 842.97 | 01-SEP-12:09 | 22.20 | 20.70 |
October | 0.697218E+10 | 16406.13 | 18-OCT-07:03 | 19.50 | 19.50 | 0.702868E+09 | 842.98 | 15-OCT-12:09 | 19.50 | 19.50 |
November | 0.447092E+10 | 6719.30 | 05-NOV-16:03 | 24.03 | 17.90 | 0.667031E+09 | 842.98 | 05-NOV-12:50 | 24.03 | 17.90 |
December | 0.211825E+10 | 5463.45 | 12-DEC-14:10 | 22.80 | 16.93 | 0.654139E+09 | 842.90 | 24-DEC-18:00 | 11.10 | 9.01 |
Annual Sum or Average | 0.821556E+11 | 0.801743E+10 | ||||||||
Minimum of Months | 0.120043E+10 | 4054.62 | -4.2 | -5.9 | 0.570367E+09 | 842.90 | 11.10 | 5.52 | ||
Maximum of Months | 0.124713E+11 | 19661.39 | 28.90 | 20.70 | 0.706455E+09 | 843.00 | 32.20 | 24.15 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.731738E+09 | 3926.41 | 28-JAN-07:05 | -3.5 | -5.4 | 0.338496E+09 | 714.13 | 28-JAN-13:00 | 10.60 | 4.06 |
February | 0.145234E+10 | 5710.16 | 26-FEB-15:00 | 25.00 | 12.75 | 0.334936E+09 | 842.90 | 18-FEB-13:00 | 25.00 | 12.75 |
March | 0.331375E+10 | 7938.59 | 30-MAR-14:00 | 27.80 | 17.87 | 0.421528E+09 | 842.93 | 11-MAR-13:00 | 27.80 | 17.87 |
April | 0.454943E+10 | 7897.93 | 17-APR-14:00 | 28.90 | 16.63 | 0.409388E+09 | 842.92 | 08-APR-12:09 | 28.90 | 16.63 |
May | 0.649067E+10 | 16187.28 | 19-MAY-06:03 | 16.57 | 15.54 | 0.426424E+09 | 842.98 | 27-MAY-12:50 | 22.93 | 19.37 |
June | 0.838659E+10 | 19114.84 | 05-JUN-06:02 | 19.60 | 16.99 | 0.417996E+09 | 842.96 | 24-JUN-12:00 | 32.20 | 23.35 |
July | 0.915562E+10 | 18144.87 | 25-JUL-06:02 | 21.10 | 18.18 | 0.421309E+09 | 842.97 | 15-JUL-12:50 | 21.10 | 18.18 |
August | 0.980838E+10 | 19283.07 | 26-AUG-06:02 | 21.78 | 17.46 | 0.432903E+09 | 842.96 | 19-AUG-12:30 | 21.78 | 17.46 |
September | 0.717152E+10 | 18132.14 | 16-SEP-06:02 | 22.70 | 20.23 | 0.411453E+09 | 842.96 | 09-SEP-12:50 | 22.70 | 20.23 |
October | 0.491563E+10 | 14493.21 | 18-OCT-06:03 | 19.90 | 19.90 | 0.417755E+09 | 842.92 | 14-OCT-12:39 | 19.90 | 19.90 |
November | 0.306447E+10 | 6248.60 | 05-NOV-14:00 | 23.30 | 18.52 | 0.391561E+09 | 842.90 | 04-NOV-12:00 | 23.30 | 18.52 |
December | 0.149282E+10 | 5117.78 | 12-DEC-14:00 | 22.80 | 17.07 | 0.374793E+09 | 842.76 | 09-DEC-13:00 | 22.80 | 17.07 |
Annual Sum or Average | 0.605330E+11 | 0.479854E+10 | ||||||||
Minimum of Months | 0.731738E+09 | 3926.41 | -3.5 | -5.4 | 0.334936E+09 | 714.13 | 10.60 | 4.06 | ||
Maximum of Months | 0.980838E+10 | 19283.07 | 28.90 | 20.23 | 0.432903E+09 | 842.98 | 32.20 | 23.35 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.625648E+09 | 3426.17 | 22-JAN-08:04 | -0.3 | -1.9 | 0.337311E+09 | 709.61 | 28-JAN-13:00 | 10.60 | 4.06 |
February | 0.135639E+10 | 5553.14 | 26-FEB-15:00 | 25.00 | 12.75 | 0.334260E+09 | 842.90 | 18-FEB-13:00 | 25.00 | 12.75 |
March | 0.321654E+10 | 7906.34 | 30-MAR-14:00 | 27.80 | 17.87 | 0.421022E+09 | 842.93 | 11-MAR-13:00 | 27.80 | 17.87 |
April | 0.450553E+10 | 7896.42 | 17-APR-14:00 | 28.90 | 16.63 | 0.409341E+09 | 842.92 | 08-APR-12:09 | 28.90 | 16.63 |
May | 0.649062E+10 | 16677.72 | 19-MAY-06:03 | 16.57 | 15.54 | 0.426419E+09 | 842.98 | 27-MAY-12:50 | 22.93 | 19.37 |
June | 0.844627E+10 | 19247.37 | 05-JUN-06:02 | 19.60 | 16.99 | 0.418000E+09 | 842.96 | 24-JUN-12:00 | 32.20 | 23.35 |
July | 0.924622E+10 | 18254.52 | 25-JUL-06:02 | 21.10 | 18.18 | 0.421317E+09 | 842.97 | 15-JUL-12:50 | 21.10 | 18.18 |
August | 0.989591E+10 | 19370.65 | 26-AUG-06:02 | 21.78 | 17.46 | 0.432911E+09 | 842.96 | 19-AUG-12:30 | 21.78 | 17.46 |
September | 0.720354E+10 | 18194.10 | 16-SEP-06:02 | 22.70 | 20.23 | 0.411455E+09 | 842.96 | 09-SEP-12:39 | 22.70 | 20.23 |
October | 0.486762E+10 | 14517.14 | 18-OCT-06:03 | 19.90 | 19.90 | 0.417503E+09 | 842.92 | 14-OCT-12:39 | 19.90 | 19.90 |
November | 0.295466E+10 | 6169.51 | 05-NOV-14:00 | 23.30 | 18.52 | 0.390657E+09 | 842.90 | 04-NOV-12:00 | 23.30 | 18.52 |
December | 0.136778E+10 | 4954.44 | 12-DEC-14:00 | 22.80 | 17.07 | 0.372294E+09 | 842.50 | 09-DEC-13:00 | 22.80 | 17.07 |
Annual Sum or Average | 0.601767E+11 | 0.479249E+10 | ||||||||
Minimum of Months | 0.625648E+09 | 3426.17 | -0.3 | -1.9 | 0.334260E+09 | 709.61 | 10.60 | 4.06 | ||
Maximum of Months | 0.989591E+10 | 19370.65 | 28.90 | 20.23 | 0.432911E+09 | 842.98 | 32.20 | 23.35 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516388E+09 | 3168.99 | 24-JAN-07:05 | 0.18 | -1.8 | 0.336031E+09 | 702.45 | 31-JAN-18:00 | 17.80 | 12.69 |
February | 0.122750E+10 | 5378.16 | 26-FEB-15:00 | 25.00 | 12.75 | 0.333221E+09 | 842.90 | 25-FEB-13:00 | 25.00 | 12.75 |
March | 0.303197E+10 | 7776.22 | 30-MAR-14:00 | 27.80 | 17.87 | 0.419868E+09 | 842.93 | 11-MAR-13:00 | 27.80 | 17.87 |
April | 0.434152E+10 | 7798.27 | 17-APR-14:00 | 28.90 | 16.63 | 0.409156E+09 | 842.92 | 08-APR-12:09 | 28.90 | 16.63 |
May | 0.634222E+10 | 15555.02 | 19-MAY-06:03 | 16.57 | 15.54 | 0.426380E+09 | 842.98 | 27-MAY-12:50 | 22.93 | 19.37 |
June | 0.833277E+10 | 19172.46 | 05-JUN-06:02 | 19.60 | 16.99 | 0.417982E+09 | 842.96 | 24-JUN-12:00 | 32.20 | 23.35 |
July | 0.915292E+10 | 18158.72 | 25-JUL-06:02 | 21.10 | 18.18 | 0.421300E+09 | 842.97 | 15-JUL-12:50 | 21.10 | 18.18 |
August | 0.980095E+10 | 19255.74 | 26-AUG-06:02 | 21.78 | 17.46 | 0.432893E+09 | 842.96 | 19-AUG-12:30 | 21.78 | 17.46 |
September | 0.708879E+10 | 18079.28 | 16-SEP-06:02 | 22.70 | 20.23 | 0.411434E+09 | 842.96 | 09-SEP-12:50 | 22.70 | 20.23 |
October | 0.471162E+10 | 14395.49 | 18-OCT-06:03 | 19.90 | 19.90 | 0.417019E+09 | 842.92 | 14-OCT-12:39 | 19.90 | 19.90 |
November | 0.278373E+10 | 6030.16 | 05-NOV-14:00 | 23.30 | 18.52 | 0.389268E+09 | 842.90 | 04-NOV-12:00 | 23.30 | 18.52 |
December | 0.122211E+10 | 4728.48 | 12-DEC-14:00 | 22.80 | 17.07 | 0.368893E+09 | 840.44 | 09-DEC-13:00 | 22.80 | 17.07 |
Annual Sum or Average | 0.585525E+11 | 0.478345E+10 | ||||||||
Minimum of Months | 0.516388E+09 | 3168.99 | 0.18 | -1.8 | 0.333221E+09 | 702.45 | 17.80 | 12.69 | ||
Maximum of Months | 0.980095E+10 | 19255.74 | 28.90 | 20.23 | 0.432893E+09 | 842.98 | 32.20 | 23.35 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573353E+09 | 5926.09 | 22-JAN-09:05 | 1.38 | -0.9 | 0.113959E+10 | 2020.62 | 28-JAN-15:00 | 12.20 | 4.56 |
February | 0.175542E+10 | 9435.04 | 28-FEB-15:30 | 24.15 | 13.12 | 0.113070E+10 | 2247.80 | 18-FEB-15:00 | 24.15 | 13.12 |
March | 0.475412E+10 | 13983.65 | 30-MAR-14:20 | 27.80 | 17.60 | 0.143037E+10 | 2247.91 | 11-MAR-15:09 | 27.80 | 17.60 |
April | 0.709972E+10 | 14302.03 | 17-APR-14:30 | 28.90 | 16.52 | 0.140324E+10 | 2247.85 | 01-APR-14:00 | 28.90 | 16.52 |
May | 0.106954E+11 | 20112.01 | 30-MAY-07:03 | 22.07 | 19.14 | 0.145794E+10 | 2248.00 | 27-MAY-14:09 | 22.07 | 19.14 |
June | 0.144304E+11 | 35274.79 | 04-JUN-08:62 | 22.57 | 17.09 | 0.143118E+10 | 2247.93 | 24-JUN-14:09 | 32.30 | 22.07 |
July | 0.158589E+11 | 33892.14 | 25-JUL-07:02 | 21.20 | 18.27 | 0.144023E+10 | 2247.98 | 15-JUL-14:09 | 21.20 | 18.27 |
August | 0.170471E+11 | 33498.96 | 26-AUG-07:03 | 22.30 | 17.92 | 0.148163E+10 | 2247.97 | 19-AUG-14:00 | 22.30 | 17.92 |
September | 0.120551E+11 | 32839.40 | 16-SEP-07:02 | 22.20 | 20.70 | 0.141088E+10 | 2247.95 | 16-SEP-14:00 | 25.00 | 22.90 |
October | 0.774178E+10 | 24691.27 | 19-OCT-07:03 | 19.40 | 19.12 | 0.141861E+10 | 2247.88 | 21-OCT-14:09 | 21.28 | 13.29 |
November | 0.423421E+10 | 10736.77 | 05-NOV-15:00 | 23.90 | 18.46 | 0.131567E+10 | 2247.80 | 04-NOV-14:09 | 23.90 | 18.46 |
December | 0.182391E+10 | 7817.70 | 12-DEC-14:00 | 22.80 | 17.07 | 0.123544E+10 | 2247.80 | 09-DEC-15:00 | 22.80 | 17.07 |
Annual Sum or Average | 0.980693E+11 | 0.162955E+11 | ||||||||
Minimum of Months | 0.573353E+09 | 5926.09 | 1.38 | -0.9 | 0.113070E+10 | 2020.62 | 12.20 | 4.56 | ||
Maximum of Months | 0.170471E+11 | 35274.79 | 28.90 | 20.70 | 0.148163E+10 | 2248.00 | 32.30 | 22.90 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231868E+09 | 2787.50 | 22-JAN-09:05 | 1.38 | -0.9 | 0.569150E+09 | 1003.76 | 28-JAN-15:00 | 12.20 | 4.56 |
February | 0.816256E+09 | 4827.63 | 26-FEB-15:10 | 24.90 | 12.68 | 0.564666E+09 | 1123.87 | 25-FEB-15:20 | 24.90 | 12.68 |
March | 0.228576E+10 | 7194.31 | 30-MAR-14:20 | 27.80 | 17.60 | 0.714032E+09 | 1123.92 | 11-MAR-15:30 | 27.80 | 17.60 |
April | 0.354263E+10 | 7409.86 | 17-APR-14:40 | 28.90 | 16.48 | 0.701335E+09 | 1123.89 | 01-APR-14:00 | 28.90 | 16.48 |
May | 0.542650E+10 | 9385.85 | 30-MAY-07:03 | 22.07 | 19.14 | 0.728922E+09 | 1123.97 | 27-MAY-14:09 | 22.07 | 19.14 |
June | 0.739072E+10 | 18112.24 | 05-JUN-07:02 | 21.05 | 17.87 | 0.715541E+09 | 1123.93 | 24-JUN-14:09 | 32.30 | 22.07 |
July | 0.814582E+10 | 17805.01 | 25-JUL-07:02 | 21.20 | 18.27 | 0.720064E+09 | 1123.96 | 15-JUL-14:09 | 21.20 | 18.27 |
August | 0.875992E+10 | 15962.94 | 03-AUG-07:02 | 24.18 | 22.24 | 0.740768E+09 | 1123.95 | 19-AUG-14:00 | 33.30 | 24.02 |
September | 0.616543E+10 | 17280.28 | 16-SEP-07:02 | 22.20 | 20.70 | 0.705403E+09 | 1123.95 | 16-SEP-14:00 | 25.00 | 22.90 |
October | 0.387123E+10 | 12908.78 | 19-OCT-07:03 | 19.40 | 19.12 | 0.708973E+09 | 1123.91 | 21-OCT-14:09 | 21.28 | 13.29 |
November | 0.203675E+10 | 5558.84 | 05-NOV-15:00 | 23.90 | 18.46 | 0.657172E+09 | 1123.87 | 04-NOV-14:20 | 23.90 | 18.46 |
December | 0.796155E+09 | 3935.94 | 12-DEC-14:00 | 22.80 | 17.07 | 0.616142E+09 | 1123.87 | 09-DEC-15:00 | 22.80 | 17.07 |
Annual Sum or Average | 0.494690E+11 | 0.814217E+10 | ||||||||
Minimum of Months | 0.231868E+09 | 2787.50 | 1.38 | -0.9 | 0.564666E+09 | 1003.76 | 12.20 | 4.56 | ||
Maximum of Months | 0.875992E+10 | 18112.24 | 28.90 | 22.24 | 0.740768E+09 | 1123.97 | 33.30 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215722E+09 | 2842.72 | 22-JAN-09:05 | 1.38 | -0.9 | 0.568545E+09 | 998.85 | 28-JAN-15:00 | 12.20 | 4.56 |
February | 0.778942E+09 | 4733.22 | 26-FEB-15:10 | 24.90 | 12.68 | 0.564063E+09 | 1123.87 | 25-FEB-15:39 | 24.90 | 12.68 |
March | 0.220754E+10 | 7112.21 | 30-MAR-14:20 | 27.80 | 17.60 | 0.712879E+09 | 1123.92 | 11-MAR-15:30 | 27.80 | 17.60 |
April | 0.346078E+10 | 7333.14 | 17-APR-14:40 | 28.90 | 16.48 | 0.701010E+09 | 1123.89 | 01-APR-14:00 | 28.90 | 16.48 |
May | 0.534180E+10 | 8916.87 | 30-MAY-07:03 | 22.07 | 19.14 | 0.728897E+09 | 1123.97 | 27-MAY-14:09 | 22.07 | 19.14 |
June | 0.731815E+10 | 18071.83 | 05-JUN-07:02 | 21.05 | 17.87 | 0.715533E+09 | 1123.93 | 24-JUN-14:09 | 32.30 | 22.07 |
July | 0.807586E+10 | 17762.94 | 25-JUL-07:02 | 21.20 | 18.27 | 0.720055E+09 | 1123.96 | 15-JUL-14:09 | 21.20 | 18.27 |
August | 0.868842E+10 | 15916.37 | 03-AUG-07:02 | 24.18 | 22.24 | 0.740761E+09 | 1123.95 | 19-AUG-14:00 | 33.30 | 24.02 |
September | 0.610177E+10 | 17233.25 | 16-SEP-07:02 | 22.20 | 20.70 | 0.705393E+09 | 1123.95 | 16-SEP-14:00 | 25.00 | 22.90 |
October | 0.380491E+10 | 12593.00 | 19-OCT-07:03 | 19.40 | 19.12 | 0.708470E+09 | 1123.91 | 21-OCT-14:09 | 21.28 | 13.29 |
November | 0.197326E+10 | 5493.52 | 05-NOV-15:00 | 23.90 | 18.46 | 0.656324E+09 | 1123.87 | 04-NOV-14:20 | 23.90 | 18.46 |
December | 0.756116E+09 | 3837.85 | 12-DEC-14:00 | 22.80 | 17.07 | 0.614233E+09 | 1123.87 | 09-DEC-15:00 | 22.80 | 17.07 |
Annual Sum or Average | 0.487233E+11 | 0.813616E+10 | ||||||||
Minimum of Months | 0.215722E+09 | 2842.72 | 1.38 | -0.9 | 0.564063E+09 | 998.85 | 12.20 | 4.56 | ||
Maximum of Months | 0.868842E+10 | 18071.83 | 28.90 | 22.24 | 0.740761E+09 | 1123.97 | 33.30 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169505E+09 | 2893.75 | 22-JAN-09:05 | 1.38 | -0.9 | 0.567362E+09 | 997.43 | 31-JAN-13:00 | 20.60 | 13.34 |
February | 0.698995E+09 | 4554.44 | 28-FEB-15:30 | 24.15 | 13.12 | 0.562740E+09 | 1128.90 | 18-FEB-15:50 | 24.15 | 13.12 |
March | 0.203475E+10 | 7002.80 | 30-MAR-14:20 | 27.80 | 17.60 | 0.710408E+09 | 1123.93 | 11-MAR-15:30 | 27.80 | 17.60 |
April | 0.329805E+10 | 7236.85 | 17-APR-14:40 | 28.90 | 16.48 | 0.700260E+09 | 1123.89 | 01-APR-14:00 | 28.90 | 16.48 |
May | 0.522292E+10 | 8130.70 | 30-MAY-14:50 | 30.60 | 21.37 | 0.728843E+09 | 1123.98 | 27-MAY-14:09 | 30.60 | 21.37 |
June | 0.730399E+10 | 18186.44 | 05-JUN-07:02 | 21.05 | 17.87 | 0.715535E+09 | 1123.92 | 24-JUN-14:09 | 32.30 | 22.07 |
July | 0.809868E+10 | 17887.18 | 25-JUL-07:02 | 21.20 | 18.27 | 0.720062E+09 | 1123.96 | 15-JUL-14:09 | 21.20 | 18.27 |
August | 0.872870E+10 | 16068.72 | 03-AUG-07:02 | 24.18 | 22.24 | 0.740769E+09 | 1123.95 | 19-AUG-14:00 | 33.30 | 24.02 |
September | 0.609239E+10 | 17360.51 | 16-SEP-07:02 | 22.20 | 20.70 | 0.705391E+09 | 1123.96 | 16-SEP-14:00 | 25.00 | 22.90 |
October | 0.371490E+10 | 12139.70 | 19-OCT-07:03 | 19.40 | 19.12 | 0.707467E+09 | 1123.91 | 21-OCT-14:09 | 21.28 | 13.29 |
November | 0.184728E+10 | 5414.97 | 05-NOV-15:00 | 23.90 | 18.46 | 0.654896E+09 | 1123.87 | 04-NOV-14:20 | 23.90 | 18.46 |
December | 0.666719E+09 | 3828.97 | 01-DEC-08:05 | -2.9 | -4.1 | 0.610787E+09 | 1123.85 | 09-DEC-15:00 | 14.40 | 6.35 |
Annual Sum or Average | 0.478769E+11 | 0.812452E+10 | ||||||||
Minimum of Months | 0.169505E+09 | 2893.75 | -2.9 | -4.1 | 0.562740E+09 | 997.43 | 14.40 | 6.35 | ||
Maximum of Months | 0.872870E+10 | 18186.44 | 30.60 | 22.24 | 0.740769E+09 | 1128.90 | 33.30 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39180564.88 | 2428.98 | 22-JAN-09:06 | 1.38 | -0.9 | 0.566152E+09 | 997.74 | 20-JAN-17:10 | 1.38 | -0.9 |
February | 0.509059E+09 | 4398.13 | 28-FEB-15:30 | 24.15 | 13.12 | 0.560286E+09 | 1123.87 | 25-FEB-15:39 | 24.15 | 13.12 |
March | 0.151964E+10 | 7038.76 | 30-MAR-14:20 | 27.80 | 17.60 | 0.706597E+09 | 1123.94 | 11-MAR-15:39 | 27.80 | 17.60 |
April | 0.299767E+10 | 7333.44 | 17-APR-14:20 | 28.90 | 16.56 | 0.698750E+09 | 1123.89 | 01-APR-14:00 | 28.90 | 16.56 |
May | 0.524407E+10 | 8683.56 | 30-MAY-14:30 | 30.60 | 21.24 | 0.728759E+09 | 1123.94 | 06-MAY-14:09 | 30.60 | 21.24 |
June | 0.792492E+10 | 19013.88 | 15-JUN-07:02 | 22.20 | 18.87 | 0.715638E+09 | 1123.94 | 17-JUN-14:00 | 26.10 | 20.69 |
July | 0.894396E+10 | 18716.97 | 18-JUL-07:02 | 21.97 | 20.23 | 0.720204E+09 | 1123.95 | 08-JUL-14:09 | 21.97 | 20.23 |
August | 0.967159E+10 | 17656.92 | 10-AUG-07:02 | 25.37 | 23.14 | 0.740900E+09 | 1123.95 | 19-AUG-14:50 | 33.40 | 24.00 |
September | 0.655565E+10 | 17824.39 | 16-SEP-07:02 | 22.20 | 20.70 | 0.705478E+09 | 1123.98 | 16-SEP-14:30 | 25.85 | 23.36 |
October | 0.360752E+10 | 9096.05 | 10-OCT-14:10 | 29.32 | 20.98 | 0.705660E+09 | 1123.91 | 21-OCT-14:09 | 21.28 | 13.29 |
November | 0.143293E+10 | 5403.25 | 05-NOV-15:00 | 23.90 | 18.46 | 0.654063E+09 | 1123.87 | 04-NOV-14:30 | 23.90 | 18.46 |
December | 0.317032E+09 | 3457.04 | 12-DEC-14:00 | 22.80 | 17.07 | 0.607407E+09 | 1123.51 | 09-DEC-15:00 | 22.80 | 17.07 |
Annual Sum or Average | 0.487632E+11 | 0.810989E+10 | ||||||||
Minimum of Months | 39180564.88 | 2428.98 | 1.38 | -0.9 | 0.560286E+09 | 997.74 | 1.38 | -0.9 | ||
Maximum of Months | 0.967159E+10 | 19013.88 | 30.60 | 23.14 | 0.740900E+09 | 1123.98 | 33.40 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308139E+10 | 59856.12 | 19-JAN-08:61 | 12.88 |
February | 0.173858E+10 | 57927.49 | 11-FEB-08:61 | 11.73 |
March | 0.103843E+09 | 46621.23 | 23-MAR-07:01 | 6.20 |
April | 61963201.86 | 40716.30 | 07-APR-07:01 | 3.53 |
May | 13711060.57 | 3418.18 | 30-MAY-07:07 | 22.07 |
June | 36153938.80 | 4789.79 | 22-JUN-07:05 | 23.35 |
July | 33218074.32 | 5596.12 | 07-JUL-07:05 | 25.28 |
August | 30161515.11 | 5673.53 | 10-AUG-07:05 | 25.37 |
September | 33140003.10 | 4510.71 | 09-SEP-07:05 | 22.67 |
October | 9435638.22 | 16981.53 | 26-OCT-07:02 | 2.57 |
November | 0.113670E+09 | 38460.71 | 22-NOV-08:61 | -2.2 |
December | 0.732218E+09 | 49579.90 | 23-DEC-08:61 | 7.80 |
Annual Sum or Average | 0.598748E+10 | |||
Minimum of Months | 9435638.22 | 3418.18 | -2.2 | |
Maximum of Months | 0.308139E+10 | 59856.12 | 25.37 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.929019E+09 | 23654.42 | 18-JAN-08:61 | 5.68 |
February | 0.464077E+09 | 27083.18 | 08-FEB-08:61 | 8.90 |
March | 7878747.13 | 19300.87 | 23-MAR-07:01 | 6.20 |
April | 5911455.68 | 2022.78 | 06-APR-07:01 | 2.25 |
May | 9871556.82 | 2039.45 | 30-MAY-07:07 | 22.07 |
June | 19700892.58 | 2636.33 | 22-JUN-07:05 | 23.35 |
July | 14522130.17 | 3011.03 | 07-JUL-07:05 | 25.28 |
August | 14103869.63 | 3103.85 | 19-AUG-07:05 | 25.87 |
September | 17908765.55 | 2527.15 | 09-SEP-07:05 | 22.67 |
October | 3718223.40 | 1753.02 | 18-OCT-07:05 | 19.50 |
November | 20940779.59 | 18095.08 | 22-NOV-08:61 | -2.2 |
December | 0.142753E+09 | 22865.01 | 22-DEC-08:61 | 5.00 |
Annual Sum or Average | 0.165040E+10 | |||
Minimum of Months | 3718223.40 | 1753.02 | -2.2 | |
Maximum of Months | 0.929019E+09 | 27083.18 | 25.87 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128219E+10 | 24983.07 | 01-JAN-08:62 | 11.20 |
February | 0.678149E+09 | 26444.56 | 08-FEB-07:01 | 8.40 |
March | 42367565.17 | 8286.36 | 19-MAR-07:03 | 1.57 |
April | 71511047.45 | 2291.46 | 16-APR-16:12 | 26.70 |
May | 0.121601E+09 | 2986.11 | 29-MAY-16:11 | 30.00 |
June | 0.197440E+09 | 3646.04 | 25-JUN-16:01 | 33.22 |
July | 0.209285E+09 | 3986.56 | 08-JUL-17:11 | 34.40 |
August | 0.216208E+09 | 3608.56 | 18-AUG-19:11 | 32.43 |
September | 0.132009E+09 | 2994.36 | 03-SEP-16:11 | 30.00 |
October | 49531294.13 | 2447.93 | 09-OCT-16:12 | 27.43 |
November | 54665133.62 | 19156.35 | 23-NOV-08:62 | 2.67 |
December | 0.283173E+09 | 22105.64 | 22-DEC-07:02 | 5.00 |
Annual Sum or Average | 0.333813E+10 | |||
Minimum of Months | 42367565.17 | 2291.46 | 1.57 | |
Maximum of Months | 0.128219E+10 | 26444.56 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142546E+10 | 28928.97 | 01-JAN-08:62 | 11.20 |
February | 0.748487E+09 | 26556.50 | 08-FEB-07:01 | 8.40 |
March | 48720433.85 | 10893.44 | 19-MAR-07:03 | 1.57 |
April | 73504334.50 | 2301.29 | 16-APR-16:12 | 26.70 |
May | 0.122215E+09 | 2991.94 | 29-MAY-16:11 | 30.00 |
June | 0.196588E+09 | 3647.76 | 25-JUN-16:01 | 33.22 |
July | 0.209121E+09 | 3990.69 | 08-JUL-17:11 | 34.40 |
August | 0.213683E+09 | 3613.44 | 18-AUG-19:11 | 32.43 |
September | 0.131789E+09 | 2999.85 | 03-SEP-16:11 | 30.00 |
October | 49916305.96 | 2455.62 | 09-OCT-16:12 | 27.43 |
November | 65942358.46 | 19896.11 | 23-NOV-08:62 | 2.67 |
December | 0.348069E+09 | 22684.71 | 25-DEC-08:62 | 5.50 |
Annual Sum or Average | 0.363349E+10 | |||
Minimum of Months | 48720433.85 | 2301.29 | 1.57 | |
Maximum of Months | 0.142546E+10 | 28928.97 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161143E+10 | 28951.78 | 01-JAN-08:62 | 11.20 |
February | 0.846718E+09 | 26541.45 | 08-FEB-07:01 | 8.40 |
March | 57325845.94 | 13405.76 | 19-MAR-07:03 | 1.57 |
April | 76953220.45 | 2298.59 | 16-APR-16:12 | 26.70 |
May | 0.122761E+09 | 2989.03 | 29-MAY-16:11 | 30.00 |
June | 0.198047E+09 | 3646.86 | 25-JUN-16:01 | 33.22 |
July | 0.210980E+09 | 3987.53 | 08-JUL-17:11 | 34.40 |
August | 0.215408E+09 | 3610.20 | 18-AUG-19:11 | 32.43 |
September | 0.133848E+09 | 2996.62 | 03-SEP-16:11 | 30.00 |
October | 50476984.07 | 2446.72 | 09-OCT-16:12 | 27.43 |
November | 76905091.17 | 19895.18 | 23-NOV-08:62 | 2.67 |
December | 0.426057E+09 | 22702.58 | 25-DEC-08:62 | 5.50 |
Annual Sum or Average | 0.402691E+10 | |||
Minimum of Months | 50476984.07 | 2298.59 | 1.57 | |
Maximum of Months | 0.161143E+10 | 28951.78 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342457E+10 | 57644.15 | 19-JAN-08:61 | 12.88 |
February | 0.183332E+10 | 55603.53 | 11-FEB-08:61 | 11.73 |
March | 0.137144E+09 | 44476.37 | 23-MAR-07:01 | 6.20 |
April | 0.111219E+09 | 38593.67 | 07-APR-07:01 | 3.53 |
May | 0.108380E+09 | 5678.06 | 29-MAY-16:11 | 30.00 |
June | 0.153293E+09 | 7137.49 | 25-JUN-16:01 | 33.22 |
July | 0.172501E+09 | 7780.49 | 08-JUL-17:01 | 34.40 |
August | 0.142911E+09 | 6900.66 | 06-AUG-16:01 | 32.70 |
September | 0.128681E+09 | 5691.31 | 03-SEP-16:11 | 30.00 |
October | 72051789.08 | 18825.16 | 26-OCT-07:02 | 2.57 |
November | 0.156594E+09 | 48216.17 | 24-NOV-08:61 | 8.58 |
December | 0.103881E+10 | 60148.77 | 24-DEC-09:01 | 15.28 |
Annual Sum or Average | 0.747947E+10 | |||
Minimum of Months | 72051789.08 | 5678.06 | 2.57 | |
Maximum of Months | 0.342457E+10 | 60148.77 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199808E+10 | 30489.63 | 19-JAN-08:61 | 12.88 |
February | 0.107858E+10 | 29435.26 | 11-FEB-08:61 | 11.73 |
March | 86686673.83 | 23659.93 | 23-MAR-07:01 | 6.20 |
April | 68702780.83 | 20586.91 | 07-APR-07:01 | 3.53 |
May | 58070268.42 | 2937.12 | 29-MAY-16:11 | 30.00 |
June | 80727310.05 | 3630.41 | 25-JUN-16:01 | 33.22 |
July | 91429008.64 | 3959.82 | 08-JUL-17:01 | 34.40 |
August | 73618988.77 | 3512.33 | 06-AUG-16:01 | 32.70 |
September | 68529123.61 | 2943.09 | 03-SEP-16:11 | 30.00 |
October | 41173202.65 | 10131.69 | 26-OCT-07:02 | 2.57 |
November | 94666650.79 | 25589.24 | 24-NOV-08:61 | 8.58 |
December | 0.625286E+09 | 32071.81 | 24-DEC-09:01 | 15.28 |
Annual Sum or Average | 0.436554E+10 | |||
Minimum of Months | 41173202.65 | 2937.12 | 2.57 | |
Maximum of Months | 0.199808E+10 | 32071.81 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205958E+10 | 30492.67 | 19-JAN-08:61 | 12.88 |
February | 0.111382E+10 | 29439.24 | 11-FEB-08:61 | 11.73 |
March | 97560755.98 | 23672.37 | 23-MAR-07:01 | 6.20 |
April | 72651574.02 | 20600.32 | 07-APR-07:01 | 3.53 |
May | 58953627.49 | 2936.54 | 29-MAY-16:11 | 30.00 |
June | 82203576.19 | 3631.53 | 25-JUN-16:01 | 33.22 |
July | 92817099.65 | 3960.74 | 08-JUL-17:01 | 34.40 |
August | 74640367.28 | 3513.34 | 06-AUG-16:01 | 32.70 |
September | 68867679.15 | 2941.97 | 03-SEP-16:11 | 30.00 |
October | 42799974.08 | 11620.68 | 26-OCT-07:02 | 2.57 |
November | 99435396.13 | 25600.28 | 24-NOV-08:61 | 8.58 |
December | 0.655355E+09 | 32771.36 | 24-DEC-09:01 | 15.28 |
Annual Sum or Average | 0.451868E+10 | |||
Minimum of Months | 42799974.08 | 2936.54 | 2.57 | |
Maximum of Months | 0.205958E+10 | 32771.36 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227690E+10 | 30816.75 | 19-JAN-08:61 | 12.88 |
February | 0.125803E+10 | 29766.42 | 11-FEB-08:61 | 11.73 |
March | 0.137245E+09 | 23983.94 | 23-MAR-07:01 | 6.20 |
April | 91665795.87 | 20892.04 | 07-APR-07:01 | 3.53 |
May | 61963468.31 | 2956.53 | 29-MAY-16:11 | 30.00 |
June | 82632340.35 | 3642.92 | 25-JUN-16:01 | 33.22 |
July | 93623823.26 | 3970.31 | 08-JUL-17:01 | 34.40 |
August | 74527750.26 | 3523.34 | 06-AUG-16:01 | 32.70 |
September | 70441812.76 | 2959.75 | 03-SEP-16:11 | 30.00 |
October | 48515811.66 | 16450.16 | 26-OCT-07:02 | 2.57 |
November | 0.119130E+09 | 25891.83 | 24-NOV-08:61 | 8.58 |
December | 0.765908E+09 | 33111.00 | 24-DEC-09:01 | 15.28 |
Annual Sum or Average | 0.508058E+10 | |||
Minimum of Months | 48515811.66 | 2956.53 | 2.57 | |
Maximum of Months | 0.227690E+10 | 33111.00 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394025E+10 | 36490.93 | 19-JAN-08:61 | 12.88 |
February | 0.241722E+10 | 35386.34 | 11-FEB-08:61 | 11.73 |
March | 0.451914E+09 | 31725.79 | 24-MAR-07:02 | 10.10 |
April | 0.255624E+09 | 28423.28 | 27-APR-07:02 | 6.75 |
May | 0.115074E+09 | 3313.67 | 29-MAY-16:11 | 30.00 |
June | 89546390.21 | 3943.97 | 25-JUN-16:11 | 33.13 |
July | 96722987.64 | 4278.53 | 08-JUL-17:11 | 34.40 |
August | 74386269.65 | 3817.67 | 06-AUG-16:11 | 32.60 |
September | 93305598.96 | 3308.14 | 03-SEP-16:11 | 30.00 |
October | 0.114384E+09 | 27482.98 | 31-OCT-07:02 | 7.80 |
November | 0.314095E+09 | 30897.96 | 24-NOV-08:61 | 8.58 |
December | 0.148329E+10 | 39017.38 | 24-DEC-09:01 | 15.28 |
Annual Sum or Average | 0.944582E+10 | |||
Minimum of Months | 74386269.65 | 3308.14 | 6.75 | |
Maximum of Months | 0.394025E+10 | 39017.38 | 34.40 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117009E+11 | 7157.48 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.105780E+11 | 7157.48 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.117131E+11 | 7157.48 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.113388E+11 | 7157.48 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.117009E+11 | 7157.48 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.113388E+11 | 7157.48 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.117131E+11 | 7157.48 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.117009E+11 | 7157.48 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.113510E+11 | 7157.48 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.117009E+11 | 7157.48 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.113022E+11 | 7157.48 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.117253E+11 | 7157.48 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.137864E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.105780E+11 | 7157.48 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.117253E+11 | 7157.48 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.671043E+10 | 4104.79 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.606645E+10 | 4104.79 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.671742E+10 | 4104.79 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.650277E+10 | 4104.79 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.671043E+10 | 4104.79 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.650277E+10 | 4104.79 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.671742E+10 | 4104.79 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.671043E+10 | 4104.79 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.650977E+10 | 4104.79 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.671043E+10 | 4104.79 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.648177E+10 | 4104.79 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.672442E+10 | 4104.79 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.790645E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.606645E+10 | 4104.79 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.672442E+10 | 4104.79 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497151E+10 | 3822.63 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.450217E+10 | 3822.63 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.507580E+10 | 3822.63 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.482375E+10 | 3822.63 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.502365E+10 | 3822.63 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.490197E+10 | 3822.63 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.494543E+10 | 3822.63 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.507580E+10 | 3822.63 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.482375E+10 | 3822.63 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.497151E+10 | 3822.63 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.482375E+10 | 3822.63 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.494543E+10 | 3822.63 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.588845E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.450217E+10 | 3822.63 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.507580E+10 | 3822.63 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497151E+10 | 3822.63 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.450217E+10 | 3822.63 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.507580E+10 | 3822.63 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.482375E+10 | 3822.63 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.502365E+10 | 3822.63 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.490197E+10 | 3822.63 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.494543E+10 | 3822.63 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.507580E+10 | 3822.63 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.482375E+10 | 3822.63 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.497151E+10 | 3822.63 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.482375E+10 | 3822.63 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.494543E+10 | 3822.63 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.588845E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.450217E+10 | 3822.63 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.507580E+10 | 3822.63 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497151E+10 | 3822.63 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.450217E+10 | 3822.63 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.507580E+10 | 3822.63 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.482375E+10 | 3822.63 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.502365E+10 | 3822.63 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.490197E+10 | 3822.63 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.494543E+10 | 3822.63 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.507580E+10 | 3822.63 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.482375E+10 | 3822.63 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.497151E+10 | 3822.63 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.482375E+10 | 3822.63 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.494543E+10 | 3822.63 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.588845E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.450217E+10 | 3822.63 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.507580E+10 | 3822.63 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.626384E+10 | 5242.46 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.567381E+10 | 5242.46 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.640687E+10 | 5242.46 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.607908E+10 | 5242.46 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.633536E+10 | 5242.46 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.618636E+10 | 5242.46 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.622808E+10 | 5242.46 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.640687E+10 | 5242.46 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.607908E+10 | 5242.46 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.626384E+10 | 5242.46 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.607908E+10 | 5242.46 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.622808E+10 | 5242.46 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.742303E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.567381E+10 | 5242.46 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.640687E+10 | 5242.46 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.319241E+10 | 2671.87 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.289170E+10 | 2671.87 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.326531E+10 | 2671.87 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.309825E+10 | 2671.87 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.322886E+10 | 2671.87 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.315292E+10 | 2671.87 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.317418E+10 | 2671.87 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.326531E+10 | 2671.87 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.309825E+10 | 2671.87 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.319241E+10 | 2671.87 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.309825E+10 | 2671.87 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.317418E+10 | 2671.87 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.378320E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.289170E+10 | 2671.87 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.326531E+10 | 2671.87 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.319241E+10 | 2671.87 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.289170E+10 | 2671.87 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.326531E+10 | 2671.87 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.309825E+10 | 2671.87 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.322886E+10 | 2671.87 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.315292E+10 | 2671.87 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.317418E+10 | 2671.87 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.326531E+10 | 2671.87 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.309825E+10 | 2671.87 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.319241E+10 | 2671.87 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.309825E+10 | 2671.87 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.317418E+10 | 2671.87 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.378320E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.289170E+10 | 2671.87 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.326531E+10 | 2671.87 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.319241E+10 | 2671.87 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.289170E+10 | 2671.87 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.326531E+10 | 2671.87 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.309825E+10 | 2671.87 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.322886E+10 | 2671.87 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.315292E+10 | 2671.87 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.317418E+10 | 2671.87 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.326531E+10 | 2671.87 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.309825E+10 | 2671.87 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.319241E+10 | 2671.87 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.309825E+10 | 2671.87 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.317418E+10 | 2671.87 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.378320E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.289170E+10 | 2671.87 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.326531E+10 | 2671.87 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.319241E+10 | 2671.87 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.289170E+10 | 2671.87 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.326531E+10 | 2671.87 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.309825E+10 | 2671.87 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.322886E+10 | 2671.87 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.315292E+10 | 2671.87 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.317418E+10 | 2671.87 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.326531E+10 | 2671.87 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.309825E+10 | 2671.87 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.319241E+10 | 2671.87 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.309825E+10 | 2671.87 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.317418E+10 | 2671.87 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.378320E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.289170E+10 | 2671.87 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.326531E+10 | 2671.87 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.117009E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464026E+10 |
February | 0.305697E+10 | 0.105780E+11 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4234202.28 | 0.334737E+10 |
March | 0.335708E+10 | 0.117131E+11 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36072587.51 | 0.220393E+10 |
April | 0.327081E+10 | 0.113388E+11 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198145E+09 | 0.106141E+10 |
May | 0.336680E+10 | 0.117009E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469901E+09 | 0.492153E+09 |
June | 0.325380E+10 | 0.113388E+11 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119466E+10 | 0.181766E+09 |
July | 0.339353E+10 | 0.117131E+11 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139063E+10 | 0.162807E+09 |
August | 0.334857E+10 | 0.117009E+11 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136632E+10 | 81570591.67 |
September | 0.327932E+10 | 0.113510E+11 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551625E+09 | 0.312202E+09 |
October | 0.338624E+10 | 0.117009E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107557E+09 | 0.147443E+10 |
November | 0.327446E+10 | 0.113022E+11 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 653744.80 | 0.230020E+10 |
December | 0.340325E+10 | 0.117253E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363052E+10 |
Annual Sum or Average | 0.397770E+11 | 0.137864E+12 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531980E+10 | 0.198886E+11 |
Minimum of Months | 0.305697E+10 | 0.105780E+11 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81570591.67 |
Maximum of Months | 0.340325E+10 | 0.117253E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139063E+10 | 0.464026E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.671043E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228359E+10 |
February | 0.152844E+10 | 0.606645E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.159316E+10 |
March | 0.167849E+10 | 0.671742E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19332497.57 | 0.105308E+10 |
April | 0.163536E+10 | 0.650277E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108488E+09 | 0.478784E+09 |
May | 0.168335E+10 | 0.671043E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256113E+09 | 0.198253E+09 |
June | 0.162685E+10 | 0.650277E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643938E+09 | 60435022.69 |
July | 0.169671E+10 | 0.671742E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753538E+09 | 63558883.46 |
August | 0.167424E+10 | 0.671043E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738843E+09 | 25924982.84 |
September | 0.163961E+10 | 0.650977E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300521E+09 | 0.130455E+09 |
October | 0.169307E+10 | 0.671043E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58604230.49 | 0.683990E+09 |
November | 0.163718E+10 | 0.648177E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 355795.67 | 0.109569E+10 |
December | 0.170157E+10 | 0.672442E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177556E+10 |
Annual Sum or Average | 0.198880E+11 | 0.790645E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288202E+10 | 0.944249E+10 |
Minimum of Months | 0.152844E+10 | 0.606645E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25924982.84 |
Maximum of Months | 0.170157E+10 | 0.672442E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753538E+09 | 0.228359E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232716E+10 |
February | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.164134E+10 |
March | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19302749.22 | 0.109407E+10 |
April | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105659E+09 | 0.511414E+09 |
May | 0.102058E+10 | 0.502365E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249055E+09 | 0.223351E+09 |
June | 0.998711E+09 | 0.490197E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629247E+09 | 72211627.54 |
July | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732286E+09 | 73437779.50 |
August | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723025E+09 | 35298266.22 |
September | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288934E+09 | 0.147411E+09 |
October | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55240017.65 | 0.720057E+09 |
November | 0.973196E+09 | 0.482375E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 342907.17 | 0.113084E+10 |
December | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181181E+10 |
Annual Sum or Average | 0.119700E+11 | 0.588845E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280537E+10 | 0.978840E+10 |
Minimum of Months | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35298266.22 |
Maximum of Months | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732286E+09 | 0.232716E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231689E+10 |
February | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.163427E+10 |
March | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19302734.75 | 0.108998E+10 |
April | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105661E+09 | 0.510410E+09 |
May | 0.102058E+10 | 0.502365E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249036E+09 | 0.223369E+09 |
June | 0.998711E+09 | 0.490197E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629109E+09 | 72986172.67 |
July | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731924E+09 | 74277019.64 |
August | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722773E+09 | 36287804.84 |
September | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288920E+09 | 0.147735E+09 |
October | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55241795.58 | 0.718337E+09 |
November | 0.973196E+09 | 0.482375E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 342897.32 | 0.112493E+10 |
December | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179740E+10 |
Annual Sum or Average | 0.119700E+11 | 0.588845E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280459E+10 | 0.974687E+10 |
Minimum of Months | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36287804.84 |
Maximum of Months | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731924E+09 | 0.231689E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230847E+10 |
February | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.162704E+10 |
March | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19302669.74 | 0.108340E+10 |
April | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105665E+09 | 0.508229E+09 |
May | 0.102058E+10 | 0.502365E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249066E+09 | 0.222107E+09 |
June | 0.998711E+09 | 0.490197E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629193E+09 | 72068227.17 |
July | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732093E+09 | 73652717.61 |
August | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722904E+09 | 35567296.33 |
September | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288953E+09 | 0.146969E+09 |
October | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55248578.23 | 0.715131E+09 |
November | 0.973196E+09 | 0.482375E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 342886.58 | 0.111761E+10 |
December | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178177E+10 |
Annual Sum or Average | 0.119700E+11 | 0.588845E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280505E+10 | 0.969202E+10 |
Minimum of Months | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35567296.33 |
Maximum of Months | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732093E+09 | 0.230847E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.626384E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422024E+10 |
February | 0.313522E+10 | 0.567381E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4108877.91 | 0.298574E+10 |
March | 0.355148E+10 | 0.640687E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34816677.64 | 0.197612E+10 |
April | 0.338259E+10 | 0.607908E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189958E+09 | 0.938909E+09 |
May | 0.349753E+10 | 0.633536E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448399E+09 | 0.420075E+09 |
June | 0.343071E+10 | 0.618636E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113574E+10 | 0.141122E+09 |
July | 0.344942E+10 | 0.622808E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132150E+10 | 0.140993E+09 |
August | 0.355148E+10 | 0.640687E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130531E+10 | 67721697.08 |
September | 0.338259E+10 | 0.607908E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520691E+09 | 0.276444E+09 |
October | 0.344359E+10 | 0.626384E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99499788.35 | 0.131420E+10 |
November | 0.331698E+10 | 0.607908E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617244.44 | 0.204181E+10 |
December | 0.344942E+10 | 0.622808E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323801E+10 |
Annual Sum or Average | 0.410346E+11 | 0.742303E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506065E+10 | 0.177614E+11 |
Minimum of Months | 0.313522E+10 | 0.567381E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67721697.08 |
Maximum of Months | 0.355148E+10 | 0.640687E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132150E+10 | 0.422024E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230272E+10 |
February | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.161992E+10 |
March | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19323584.58 | 0.106852E+10 |
April | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105711E+09 | 0.503358E+09 |
May | 0.174872E+10 | 0.322886E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249476E+09 | 0.220236E+09 |
June | 0.171530E+10 | 0.315292E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631171E+09 | 70376348.21 |
July | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735122E+09 | 72655761.76 |
August | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725805E+09 | 32727666.17 |
September | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289664E+09 | 0.145717E+09 |
October | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55321716.07 | 0.708751E+09 |
November | 0.165844E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343281.65 | 0.110563E+10 |
December | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175575E+10 |
Annual Sum or Average | 0.205167E+11 | 0.378320E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281422E+10 | 0.960636E+10 |
Minimum of Months | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32727666.17 |
Maximum of Months | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735122E+09 | 0.230272E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230025E+10 |
February | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.161741E+10 |
March | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19323727.92 | 0.106482E+10 |
April | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105714E+09 | 0.501705E+09 |
May | 0.174872E+10 | 0.322886E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249503E+09 | 0.219438E+09 |
June | 0.171530E+10 | 0.315292E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631258E+09 | 69913806.78 |
July | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735264E+09 | 72303103.15 |
August | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725904E+09 | 32372132.58 |
September | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289698E+09 | 0.145314E+09 |
October | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55328254.52 | 0.706897E+09 |
November | 0.165844E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343352.05 | 0.110289E+10 |
December | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175036E+10 |
Annual Sum or Average | 0.205167E+11 | 0.378320E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281462E+10 | 0.958367E+10 |
Minimum of Months | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32372132.58 |
Maximum of Months | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735264E+09 | 0.230025E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229315E+10 |
February | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.161036E+10 |
March | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19323859.28 | 0.105587E+10 |
April | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105718E+09 | 0.497494E+09 |
May | 0.174872E+10 | 0.322886E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249522E+09 | 0.217798E+09 |
June | 0.171530E+10 | 0.315292E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631225E+09 | 69556430.34 |
July | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735137E+09 | 72219478.87 |
August | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725791E+09 | 32475444.67 |
September | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289680E+09 | 0.145025E+09 |
October | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55329985.81 | 0.703227E+09 |
November | 0.165844E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343348.37 | 0.109741E+10 |
December | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173869E+10 |
Annual Sum or Average | 0.205167E+11 | 0.378320E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281435E+10 | 0.953328E+10 |
Minimum of Months | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32475444.67 |
Maximum of Months | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735137E+09 | 0.229315E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286871E+10 |
February | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2407321.98 | 0.210449E+10 |
March | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20556984.64 | 0.137047E+10 |
April | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108703E+09 | 0.690960E+09 |
May | 0.174872E+10 | 0.322886E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258206E+09 | 0.350003E+09 |
June | 0.171530E+10 | 0.315292E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664914E+09 | 0.143800E+09 |
July | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767753E+09 | 0.124786E+09 |
August | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759954E+09 | 71935611.61 |
September | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299818E+09 | 0.228522E+09 |
October | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57330016.47 | 0.957358E+09 |
November | 0.165844E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 357226.08 | 0.145128E+10 |
December | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224864E+10 |
Annual Sum or Average | 0.205167E+11 | 0.378320E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294000E+10 | 0.126110E+11 |
Minimum of Months | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71935611.61 |
Maximum of Months | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767753E+09 | 0.286871E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 7157.48 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8886.97 | 07-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 7157.48 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 340.89 | 28-FEB-15:00 | 9043.12 | 11-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 7157.48 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.99 | 30-MAR-16:00 | 5360.18 | 22-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 7157.48 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.89 | 12-APR-14:00 | 4809.90 | 05-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 7157.48 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.15 | 19-MAY-16:00 | 1978.22 | 10-MAY-11:10 |
June | 4050.04 | 02-JUN-12:09 | 7157.48 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3040.59 | 06-JUN-15:00 | 781.58 | 07-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 7157.48 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3502.38 | 08-JUL-15:00 | 1533.81 | 28-JUL-17:00 |
August | 4050.04 | 04-AUG-12:09 | 7157.48 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3186.00 | 01-AUG-17:00 | 328.14 | 31-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 7157.48 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.33 | 07-SEP-15:00 | 2035.91 | 28-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 7157.48 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1728.37 | 10-OCT-16:00 | 4384.10 | 25-OCT-11:10 |
November | 4050.04 | 03-NOV-12:09 | 7157.48 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.55 | 19-NOV-15:00 | 5793.51 | 20-NOV-12:05 |
December | 4050.04 | 01-DEC-13:09 | 7157.48 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6421.86 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 7157.48 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.14 | |||||
Maximum of Months | 4050.04 | 7157.48 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3502.38 | 9043.12 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 4104.79 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 4104.79 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 4104.79 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 621.03 | 30-MAR-16:00 | 2894.38 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 4104.79 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.37 | 12-APR-14:00 | 2672.66 | 05-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 4104.79 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.43 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 02-JUN-12:09 | 4104.79 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.31 | 06-JUN-15:00 | 422.26 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 4104.79 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.85 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 04-AUG-12:09 | 4104.79 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.00 | 01-AUG-17:00 | 177.55 | 31-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 4104.79 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.24 | 07-SEP-15:00 | 1101.66 | 28-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 4104.79 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.85 | 10-OCT-16:00 | 2467.47 | 25-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 4104.79 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 3221.00 | 20-NOV-12:05 |
December | 2024.96 | 01-DEC-13:09 | 4104.79 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3499.39 | 17-DEC-17:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 4104.79 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.55 | |||||
Maximum of Months | 2024.96 | 4104.79 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.85 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3822.63 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3822.63 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3822.63 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 621.03 | 30-MAR-16:00 | 2889.11 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3822.63 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.37 | 12-APR-14:00 | 2676.34 | 05-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 3822.63 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.43 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 3822.63 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.31 | 06-JUN-15:00 | 422.26 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3822.63 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.85 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3822.63 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.00 | 01-AUG-17:00 | 216.06 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 3822.63 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.24 | 07-SEP-15:00 | 1101.66 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3822.63 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.85 | 10-OCT-16:00 | 2461.00 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 3822.63 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 3196.80 | 20-NOV-12:05 |
December | 2024.96 | 02-DEC-13:09 | 3822.63 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3499.39 | 17-DEC-17:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.06 | |||||
Maximum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.85 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3822.63 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3822.63 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3822.63 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 621.03 | 30-MAR-16:00 | 2885.59 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3822.63 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.37 | 12-APR-14:00 | 2675.80 | 05-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 3822.63 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.43 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 3822.63 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.31 | 06-JUN-15:00 | 422.26 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3822.63 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.85 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3822.63 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.00 | 01-AUG-17:00 | 223.50 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 3822.63 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.24 | 07-SEP-15:00 | 1101.66 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3822.63 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.85 | 10-OCT-16:00 | 2452.68 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 3822.63 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 3180.55 | 20-NOV-12:05 |
December | 2024.96 | 02-DEC-13:09 | 3822.63 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3499.39 | 17-DEC-17:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.50 | |||||
Maximum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.85 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3822.63 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3822.63 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3822.63 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 621.03 | 30-MAR-16:00 | 2880.57 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3822.63 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.37 | 12-APR-14:00 | 2668.90 | 05-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 3822.63 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.42 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 3822.63 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.31 | 06-JUN-15:00 | 422.26 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3822.63 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.85 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3822.63 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.00 | 01-AUG-17:00 | 221.05 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 3822.63 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.24 | 07-SEP-15:00 | 1101.66 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3822.63 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.84 | 10-OCT-16:00 | 2426.20 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 3822.63 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 3152.71 | 20-NOV-12:05 |
December | 2024.96 | 02-DEC-13:09 | 3822.63 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3499.39 | 17-DEC-17:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.05 | |||||
Maximum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.85 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 5242.46 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8548.36 | 07-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 5242.46 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 326.02 | 28-FEB-15:00 | 8665.12 | 11-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 5242.46 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1118.26 | 30-MAR-16:00 | 5188.45 | 22-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 5242.46 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.40 | 12-APR-14:00 | 4654.59 | 05-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 5242.46 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.30 | 19-MAY-16:00 | 1935.82 | 10-MAY-11:10 |
June | 5400.05 | 03-JUN-14:09 | 5242.46 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2937.33 | 06-JUN-15:00 | 760.12 | 07-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 5242.46 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.02 | 08-JUL-15:00 | 1487.64 | 28-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 5242.46 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3102.60 | 01-AUG-17:00 | 365.73 | 20-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 5242.46 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2166.33 | 07-SEP-15:00 | 1982.61 | 28-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 5242.46 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1701.41 | 10-OCT-16:00 | 4219.98 | 25-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 5242.46 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.40 | 19-NOV-15:00 | 5522.28 | 20-NOV-12:05 |
December | 5400.05 | 02-DEC-15:09 | 5242.46 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6294.04 | 17-DEC-17:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 5242.46 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.73 | |||||
Maximum of Months | 5400.05 | 5242.46 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.02 | 8665.12 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 2671.87 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 2671.87 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 2671.87 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 621.01 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 2671.87 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.35 | 12-APR-14:00 | 2569.12 | 05-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 2671.87 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.41 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 2671.87 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.30 | 06-JUN-15:00 | 422.29 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 2671.87 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.84 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 2671.87 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.00 | 01-AUG-17:00 | 178.61 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 2671.87 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.23 | 07-SEP-15:00 | 1101.66 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 2671.87 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.84 | 10-OCT-16:00 | 2330.70 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 2671.87 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 3065.62 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 2671.87 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3499.39 | 17-DEC-17:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.61 | |||||
Maximum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.84 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 2671.87 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 2671.87 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 2671.87 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 621.01 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 2671.87 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.35 | 12-APR-14:00 | 2557.10 | 05-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 2671.87 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.41 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 2671.87 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.30 | 06-JUN-15:00 | 422.29 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 2671.87 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.84 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 2671.87 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.00 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 2671.87 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.23 | 07-SEP-15:00 | 1101.66 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 2671.87 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.84 | 10-OCT-16:00 | 2320.37 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 2671.87 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 3056.30 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 2671.87 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3499.39 | 17-DEC-17:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.84 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 2671.87 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 2671.87 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 2671.87 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 621.01 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 2671.87 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.35 | 12-APR-14:00 | 2530.81 | 05-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 2671.87 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.41 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 2671.87 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.30 | 06-JUN-15:00 | 422.29 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 2671.87 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.84 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 2671.87 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.00 | 01-AUG-17:00 | 179.69 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 2671.87 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.24 | 07-SEP-15:00 | 1101.66 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 2671.87 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.84 | 10-OCT-16:00 | 2298.47 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 2671.87 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 3038.17 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 2671.87 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3499.39 | 17-DEC-17:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.69 | |||||
Maximum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.84 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 2671.87 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5080.22 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 2671.87 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.56 | 28-FEB-15:00 | 5181.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 2671.87 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 655.70 | 30-MAR-16:00 | 3052.26 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 2671.87 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.82 | 12-APR-14:00 | 2695.54 | 05-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 2671.87 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.23 | 19-MAY-16:00 | 1118.80 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 2671.87 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1733.57 | 06-JUN-15:00 | 482.00 | 07-JUN-07:00 |
July | 2699.95 | 01-JUL-14:09 | 2671.87 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.20 | 08-JUL-15:00 | 872.32 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 2671.87 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.42 | 01-AUG-17:00 | 251.46 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 2671.87 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.24 | 07-SEP-15:00 | 1154.96 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 2671.87 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 973.75 | 10-OCT-16:00 | 2391.25 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 2671.87 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.40 | 19-NOV-15:00 | 3176.51 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 2671.87 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3642.11 | 17-DEC-17:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.46 | |||||
Maximum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.20 | 5181.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7150.02 | 14-JAN-00:12 | 1350.01 | 15068.44 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.97 |
February | 10866.13 | 26-FEB-15:30 | 2700.03 | 7157.48 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 235.02 | 0.00 |
March | 15041.04 | 30-MAR-16:10 | 3375.03 | 7157.48 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.45 | 0.00 |
April | 14887.00 | 17-APR-16:10 | 3375.03 | 7157.48 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.12 | 0.00 |
May | 16495.34 | 19-MAY-16:10 | 3375.03 | 7157.48 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1925.08 | 0.00 |
June | 35695.89 | 05-JUN-07:02 | 1687.52 | 1883.69 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.49 |
July | 34852.24 | 25-JUL-07:02 | 1687.52 | 1883.69 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.36 |
August | 33670.21 | 27-AUG-07:02 | 2025.02 | 2260.43 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.96 |
September | 34757.40 | 16-SEP-07:02 | 0.00 | 1883.69 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.47 |
October | 28366.15 | 18-OCT-07:03 | 1350.01 | 1506.96 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.59 |
November | 12776.76 | 05-NOV-16:03 | 16200.15 | 28629.93 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 0.00 |
December | 9349.30 | 12-DEC-14:30 | 2700.03 | 7157.48 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7150.02 | 0.00 | 1506.96 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35695.89 | 16200.15 | 28629.93 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1925.08 | 449.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4054.62 | 15-JAN-08:05 | 1687.47 | 2160.42 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.23 |
February | 6340.42 | 26-FEB-15:00 | 1349.97 | 4104.79 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 174.85 | 0.00 |
March | 8166.78 | 30-MAR-14:00 | 1349.97 | 4104.79 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 616.28 | 0.00 |
April | 8083.23 | 16-APR-14:00 | 1349.97 | 4104.79 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 777.13 | 0.00 |
May | 10556.49 | 31-MAY-07:03 | 506.24 | 648.12 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.89 |
June | 19661.39 | 05-JUN-07:02 | 843.73 | 1080.21 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.70 |
July | 19072.80 | 25-JUL-07:02 | 843.73 | 1080.21 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.32 |
August | 18553.72 | 27-AUG-07:02 | 1012.48 | 1296.25 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.87 |
September | 19037.03 | 16-SEP-07:02 | 0.00 | 1080.21 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.77 |
October | 16406.13 | 18-OCT-07:03 | 674.99 | 864.17 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.91 |
November | 6719.30 | 05-NOV-16:03 | 8099.84 | 16419.16 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 21.38 | 0.00 |
December | 5463.45 | 12-DEC-14:10 | 1349.97 | 4104.79 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4054.62 | 0.00 | 648.12 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19661.39 | 8099.84 | 16419.16 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 777.13 | 654.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3926.41 | 28-JAN-07:05 | 0.00 | 2011.91 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.38 |
February | 5710.16 | 26-FEB-15:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 174.85 | 0.00 |
March | 7938.59 | 30-MAR-14:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 616.27 | 0.00 |
April | 7897.93 | 17-APR-14:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 772.68 | 0.00 |
May | 16187.28 | 19-MAY-06:03 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
June | 19114.84 | 05-JUN-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 |
July | 18144.87 | 25-JUL-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 |
August | 19283.07 | 26-AUG-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 |
September | 18132.14 | 16-SEP-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 |
October | 14493.21 | 18-OCT-06:03 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.31 |
November | 6248.60 | 05-NOV-14:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.32 |
December | 5117.78 | 12-DEC-14:00 | 1349.97 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3926.41 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19283.07 | 1349.97 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 772.68 | 177.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3426.17 | 22-JAN-08:04 | 0.00 | 1408.34 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.86 |
February | 5553.14 | 26-FEB-15:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 174.85 | 0.00 |
March | 7906.34 | 30-MAR-14:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 616.27 | 0.00 |
April | 7896.42 | 17-APR-14:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 772.68 | 0.00 |
May | 16677.72 | 19-MAY-06:03 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
June | 19247.37 | 05-JUN-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 |
July | 18254.52 | 25-JUL-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 |
August | 19370.65 | 26-AUG-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 |
September | 18194.10 | 16-SEP-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 |
October | 14517.14 | 18-OCT-06:03 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 |
November | 6169.51 | 05-NOV-14:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.32 |
December | 4954.44 | 12-DEC-14:00 | 1349.97 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3426.17 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19370.65 | 1349.97 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 772.68 | 572.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3168.99 | 24-JAN-07:05 | 0.00 | 1609.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.82 |
February | 5378.16 | 26-FEB-15:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 174.85 | 0.00 |
March | 7776.22 | 30-MAR-14:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 616.27 | 0.00 |
April | 7798.27 | 17-APR-14:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 772.68 | 0.00 |
May | 15555.02 | 19-MAY-06:03 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
June | 19172.46 | 05-JUN-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 |
July | 18158.72 | 25-JUL-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 |
August | 19255.74 | 26-AUG-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
September | 18079.28 | 16-SEP-06:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 |
October | 14395.49 | 18-OCT-06:03 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 |
November | 6030.16 | 05-NOV-14:00 | 1012.48 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.32 |
December | 4728.48 | 12-DEC-14:00 | 1349.97 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3168.99 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19255.74 | 1349.97 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 772.68 | 177.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5926.09 | 22-JAN-09:05 | 0.00 | 2759.45 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.31 |
February | 9435.04 | 28-FEB-15:30 | 4657.54 | 5242.46 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 0.00 |
March | 13983.65 | 30-MAR-14:20 | 4657.54 | 5242.46 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1110.80 | 0.00 |
April | 14302.03 | 17-APR-14:30 | 4657.54 | 5242.46 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1393.21 | 0.00 |
May | 20112.01 | 30-MAY-07:03 | 0.00 | 827.84 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.66 |
June | 35274.79 | 04-JUN-08:62 | 0.00 | 1103.78 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.20 |
July | 33892.14 | 25-JUL-07:02 | 0.00 | 1379.73 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.31 |
August | 33498.96 | 26-AUG-07:03 | 0.00 | 1103.78 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 |
September | 32839.40 | 16-SEP-07:02 | 0.00 | 1379.73 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.11 |
October | 24691.27 | 19-OCT-07:03 | 0.00 | 1103.78 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.31 |
November | 10736.77 | 05-NOV-15:00 | 4657.54 | 5242.46 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 0.00 |
December | 7817.70 | 12-DEC-14:00 | 4792.55 | 5242.46 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5926.09 | 0.00 | 827.84 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35274.79 | 4792.55 | 5242.46 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1393.21 | 1038.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2787.50 | 22-JAN-09:05 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.05 |
February | 4827.63 | 26-FEB-15:10 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 159.27 | 0.00 |
March | 7194.31 | 30-MAR-14:20 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 617.28 | 0.00 |
April | 7409.86 | 17-APR-14:40 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 777.03 | 0.00 |
May | 9385.85 | 30-MAY-07:03 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.93 |
June | 18112.24 | 05-JUN-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.65 |
July | 17805.01 | 25-JUL-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.95 |
August | 15962.94 | 03-AUG-07:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 |
September | 17280.28 | 16-SEP-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.93 |
October | 12908.78 | 19-OCT-07:03 | 0.00 | 562.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.57 |
November | 5558.84 | 05-NOV-15:00 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 0.00 |
December | 3935.94 | 12-DEC-14:00 | 2396.20 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2787.50 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18112.24 | 2396.20 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 777.03 | 563.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2842.72 | 22-JAN-09:05 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.03 |
February | 4733.22 | 26-FEB-15:10 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 159.27 | 0.00 |
March | 7112.21 | 30-MAR-14:20 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 617.28 | 0.00 |
April | 7333.14 | 17-APR-14:40 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 777.03 | 0.00 |
May | 8916.87 | 30-MAY-07:03 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.80 |
June | 18071.83 | 05-JUN-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.94 |
July | 17762.94 | 25-JUL-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.17 |
August | 15916.37 | 03-AUG-07:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.09 |
September | 17233.25 | 16-SEP-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.14 |
October | 12593.00 | 19-OCT-07:03 | 0.00 | 562.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.25 |
November | 5493.52 | 05-NOV-15:00 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 0.00 |
December | 3837.85 | 12-DEC-14:00 | 2396.20 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2842.72 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18071.83 | 2396.20 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 777.03 | 564.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2893.75 | 22-JAN-09:05 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.80 |
February | 4554.44 | 28-FEB-15:30 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 41.15 | 0.00 |
March | 7002.80 | 30-MAR-14:20 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 617.28 | 0.00 |
April | 7236.85 | 17-APR-14:40 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 777.03 | 0.00 |
May | 8130.70 | 30-MAY-14:50 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.61 | 0.00 |
June | 18186.44 | 05-JUN-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.81 |
July | 17887.18 | 25-JUL-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.27 |
August | 16068.72 | 03-AUG-07:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.98 |
September | 17360.51 | 16-SEP-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.36 |
October | 12139.70 | 19-OCT-07:03 | 0.00 | 562.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.20 |
November | 5414.97 | 05-NOV-15:00 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 0.00 |
December | 3828.97 | 01-DEC-08:05 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2893.75 | 0.00 | 562.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18186.44 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.61 | 620.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2428.98 | 22-JAN-09:06 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.36 |
February | 4398.13 | 28-FEB-15:30 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 0.00 |
March | 7038.76 | 30-MAR-14:20 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 646.33 | 0.00 |
April | 7333.44 | 17-APR-14:20 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 787.41 | 0.00 |
May | 8683.56 | 30-MAY-14:30 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.08 | 0.00 |
June | 19013.88 | 15-JUN-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 |
July | 18716.97 | 18-JUL-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 |
August | 17656.92 | 10-AUG-07:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 0.00 |
September | 17824.39 | 16-SEP-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.88 |
October | 9096.05 | 10-OCT-14:10 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 866.68 | 0.00 |
November | 5403.25 | 05-NOV-15:00 | 2328.71 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3457.04 | 12-DEC-14:00 | 2396.20 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2428.98 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19013.88 | 2396.20 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.08 | 755.36 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.141276E+12 | 170657.56 | 10-JAN-08:09 | 0.00 | 0.00 |
February | 0.122673E+12 | 173590.15 | 12-FEB-09:09 | 0.00 | 0.00 |
March | 0.130468E+12 | 111464.78 | 30-MAR-13:00 | 0.00 | 0.00 |
April | 0.133219E+12 | 109959.44 | 17-APR-13:00 | 0.00 | 0.00 |
May | 0.151137E+12 | 121652.34 | 30-MAY-14:00 | 0.00 | 0.00 |
June | 0.164725E+12 | 136581.52 | 27-JUN-12:00 | 0.00 | 0.00 |
July | 0.176551E+12 | 149565.22 | 08-JUL-13:00 | 0.00 | 0.00 |
August | 0.183541E+12 | 143810.66 | 19-AUG-13:00 | 0.00 | 0.00 |
September | 0.155801E+12 | 136093.64 | 06-SEP-12:00 | 0.00 | 0.00 |
October | 0.139058E+12 | 121560.00 | 10-OCT-13:00 | 0.00 | 0.00 |
November | 0.125267E+12 | 109790.21 | 22-NOV-08:09 | 0.00 | 0.00 |
December | 0.126439E+12 | 130104.66 | 18-DEC-08:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.175015E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.122673E+12 | 109790.21 | 0.00 | 0.00 | |
Maximum of Months | 0.183541E+12 | 173590.15 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.523593E+11 | 0.175879E+11 | 0.108325E+11 | 0.00 | 0.357281E+11 | 0.00 | 0.225205E+11 | 0.650857E+09 | 0.00 | 0.00 | 0.00 | 0.159713E+10 | 0.00 |
February | 0.473916E+11 | 0.150114E+11 | 0.980803E+10 | 0.00 | 0.325109E+11 | 0.00 | 0.123425E+11 | 0.415961E+10 | 0.00 | 0.00 | 0.00 | 0.144905E+10 | 0.00 |
March | 0.531261E+11 | 0.153504E+11 | 0.110075E+11 | 0.00 | 0.363555E+11 | 0.00 | 0.959728E+09 | 0.120808E+11 | 0.00 | 0.00 | 0.00 | 0.158800E+10 | 0.00 |
April | 0.507849E+11 | 0.135876E+11 | 0.105079E+11 | 0.00 | 0.347754E+11 | 0.00 | 0.244260E+09 | 0.219002E+11 | 0.00 | 0.00 | 0.00 | 0.141862E+10 | 0.00 |
May | 0.527331E+11 | 0.129367E+11 | 0.109147E+11 | 0.00 | 0.362612E+11 | 0.00 | 467401.99 | 0.369212E+11 | 0.00 | 0.00 | 0.00 | 0.136976E+10 | 0.00 |
June | 0.513456E+11 | 0.120349E+11 | 0.106386E+11 | 0.00 | 0.354759E+11 | 0.00 | 0.00 | 0.539820E+11 | 0.00 | 0.00 | 0.00 | 0.124782E+10 | 0.00 |
July | 0.521917E+11 | 0.126180E+11 | 0.107945E+11 | 0.00 | 0.360854E+11 | 0.00 | 0.00 | 0.636654E+11 | 0.00 | 0.00 | 0.00 | 0.119630E+10 | 0.00 |
August | 0.531069E+11 | 0.135401E+11 | 0.110006E+11 | 0.00 | 0.368150E+11 | 0.00 | 0.00 | 0.678476E+11 | 0.00 | 0.00 | 0.00 | 0.123034E+10 | 0.00 |
September | 0.508041E+11 | 0.143063E+11 | 0.105148E+11 | 0.00 | 0.349978E+11 | 0.00 | 0.00 | 0.439616E+11 | 0.00 | 0.00 | 0.00 | 0.121624E+10 | 0.00 |
October | 0.523593E+11 | 0.160963E+11 | 0.108325E+11 | 0.00 | 0.358813E+11 | 0.00 | 0.126545E+09 | 0.224258E+11 | 0.00 | 0.00 | 0.00 | 0.133656E+10 | 0.00 |
November | 0.507273E+11 | 0.167268E+11 | 0.104978E+11 | 0.00 | 0.346528E+11 | 0.00 | 0.130268E+10 | 0.996423E+10 | 0.00 | 0.00 | 0.00 | 0.139540E+10 | 0.00 |
December | 0.522109E+11 | 0.178998E+11 | 0.108050E+11 | 0.00 | 0.354904E+11 | 0.00 | 0.624289E+10 | 0.225710E+10 | 0.00 | 0.00 | 0.00 | 0.153279E+10 | 0.00 |
Annual Sum or Average | 0.619141E+12 | 0.177696E+12 | 0.128154E+12 | 0.00 | 0.425030E+12 | 0.00 | 0.437396E+11 | 0.339816E+12 | 0.00 | 0.00 | 0.00 | 0.165780E+11 | 0.00 |
Minimum of Months | 0.473916E+11 | 0.120349E+11 | 0.980803E+10 | 0.00 | 0.325109E+11 | 0.00 | 0.00 | 0.650857E+09 | 0.00 | 0.00 | 0.00 | 0.119630E+10 | 0.00 |
Maximum of Months | 0.531261E+11 | 0.178998E+11 | 0.110075E+11 | 0.00 | 0.368150E+11 | 0.00 | 0.225205E+11 | 0.678476E+11 | 0.00 | 0.00 | 0.00 | 0.159713E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38660.10 | 01-JAN-11:09 | 11300.38 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 24636.45 | 01-JAN-16:00 | 0.00 | 136969.86 | 10-JAN-08:09 |
February | 38660.10 | 01-FEB-10:09 | 11300.38 | 01-FEB-00:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 24636.45 | 01-FEB-12:20 | 0.00 | 135667.22 | 03-FEB-08:09 |
March | 38660.10 | 01-MAR-10:09 | 11300.38 | 01-MAR-00:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 24636.45 | 02-MAR-13:20 | 0.00 | 24963.82 | 18-MAR-07:10 |
April | 38660.10 | 01-APR-09:09 | 11300.38 | 01-APR-00:10 | 8059.50 | 01-APR-09:09 | 0.00 | 24636.45 | 01-APR-14:09 | 0.00 | 23811.31 | 06-APR-07:10 |
May | 38660.10 | 01-MAY-09:09 | 11300.38 | 01-MAY-00:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 24636.45 | 01-MAY-15:39 | 0.00 | 550.19 | 11-MAY-07:10 |
June | 38660.10 | 01-JUN-09:09 | 11300.38 | 01-JUN-00:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 24636.45 | 01-JUN-07:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38660.10 | 01-JUL-09:09 | 11300.38 | 01-JUL-00:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 24636.45 | 01-JUL-07:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38660.10 | 01-AUG-09:09 | 11300.38 | 01-AUG-00:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 24636.45 | 01-AUG-07:49 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38660.10 | 01-SEP-09:09 | 11300.38 | 01-SEP-00:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 24636.45 | 01-SEP-09:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38660.10 | 01-OCT-10:09 | 11300.38 | 01-OCT-00:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 24636.45 | 01-OCT-09:50 | 0.00 | 16927.48 | 26-OCT-07:10 |
November | 38660.10 | 01-NOV-09:09 | 11300.38 | 01-NOV-00:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 24636.45 | 01-NOV-12:00 | 0.00 | 75970.67 | 22-NOV-08:09 |
December | 38660.10 | 01-DEC-10:09 | 11300.38 | 01-DEC-00:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 24636.45 | 01-DEC-08:00 | 0.00 | 96416.99 | 18-DEC-08:09 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38660.10 | 11300.38 | 8059.50 | 0.00 | 24636.45 | 0.00 | 0.00 | |||||
Maximum of Months | 38660.10 | 11300.38 | 8059.50 | 0.00 | 24636.45 | 0.00 | 136969.86 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 11708.80 | 31-JAN-14:50 | 0.00 | 0.00 | 0.00 | 1663.52 | 26-JAN-13:09 | 0.00 |
February | 24715.75 | 26-FEB-15:09 | 0.00 | 0.00 | 0.00 | 1663.73 | 03-FEB-13:39 | 0.00 |
March | 38466.99 | 30-MAR-13:00 | 0.00 | 0.00 | 0.00 | 1659.21 | 01-MAR-13:09 | 0.00 |
April | 37238.20 | 17-APR-14:09 | 0.00 | 0.00 | 0.00 | 1644.70 | 03-APR-12:20 | 0.00 |
May | 49173.79 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 1480.27 | 01-MAY-12:50 | 0.00 |
June | 63952.55 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 1330.53 | 01-JUN-12:00 | 0.00 |
July | 76908.47 | 08-JUL-13:00 | 0.00 | 0.00 | 0.00 | 1306.50 | 03-JUL-12:00 | 0.00 |
August | 71215.33 | 19-AUG-13:00 | 0.00 | 0.00 | 0.00 | 1305.94 | 31-AUG-12:00 | 0.00 |
September | 63575.46 | 06-SEP-12:00 | 0.00 | 0.00 | 0.00 | 1315.25 | 29-SEP-12:09 | 0.00 |
October | 48869.41 | 10-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1477.86 | 31-OCT-12:39 | 0.00 |
November | 32602.23 | 05-NOV-14:00 | 0.00 | 0.00 | 0.00 | 1644.15 | 30-NOV-13:09 | 0.00 |
December | 25291.86 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 1657.15 | 29-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11708.80 | 0.00 | 0.00 | 0.00 | 1305.94 | 0.00 | ||
Maximum of Months | 76908.47 | 0.00 | 0.00 | 0.00 | 1663.73 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 170657.56 | 10-JAN-08:09 | 7466.95 | 1452.23 | 0.00 | 0.00 | 24636.45 | 0.00 | 136969.86 | 0.00 | 0.00 |
February | 173590.15 | 12-FEB-09:09 | 12801.70 | 2459.67 | 0.00 | 0.00 | 24636.45 | 0.00 | 133426.98 | 0.00 | 0.00 |
March | 111464.78 | 30-MAR-13:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 24636.45 | 0.00 | 0.00 | 38466.99 | 0.00 |
April | 109959.44 | 17-APR-13:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 24636.45 | 0.00 | 0.00 | 37119.84 | 0.00 |
May | 121652.34 | 30-MAY-14:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 24636.45 | 0.00 | 0.00 | 49173.79 | 0.00 |
June | 136581.52 | 27-JUN-12:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 24636.45 | 0.00 | 0.00 | 63952.55 | 0.00 |
July | 149565.22 | 08-JUL-13:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 24636.45 | 0.00 | 0.00 | 76908.47 | 0.00 |
August | 143810.66 | 19-AUG-13:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 24636.45 | 0.00 | 0.00 | 71215.33 | 0.00 |
September | 136093.64 | 06-SEP-12:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 24636.45 | 0.00 | 0.00 | 63575.46 | 0.00 |
October | 121560.00 | 10-OCT-13:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 24636.45 | 0.00 | 0.00 | 48869.41 | 0.00 |
November | 109790.21 | 22-NOV-08:09 | 7466.95 | 1452.23 | 0.00 | 0.00 | 24636.45 | 0.00 | 75970.67 | 0.00 | 0.00 |
December | 130104.66 | 18-DEC-08:09 | 7466.95 | 1452.23 | 0.00 | 0.00 | 24636.45 | 0.00 | 96416.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 109790.21 | 7466.95 | 1452.23 | 0.00 | 0.00 | 24636.45 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 173590.15 | 38660.10 | 8059.50 | 0.00 | 0.00 | 24636.45 | 0.00 | 136969.86 | 76908.47 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 20.22 | 1.67 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
February | 1.67 | 20.02 | 1.00 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
December | 1.00 | 20.47 | 0.50 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 6.83 | 20.21 | 3.17 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 20.53 | 1.67 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.42 | 0.67 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
February | 1.17 | 20.38 | 0.50 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 20.39 | 1.17 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.42 | 0.67 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
February | 1.17 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.00 | 20.29 | 0.00 | 20.29 | 0.17 | 20.51 | 0.00 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.33 | 0.00 | 20.33 | 0.17 | 24.48 | 0.00 | 24.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
February | 1.33 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.00 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Annual Sum or Average | 3.83 | 20.26 | 0.00 | 20.26 | 0.17 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.47 | 0.00 | 20.47 | 0.17 | 24.52 | 0.00 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
February | 1.33 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.51 | 0.00 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 4.33 | 20.22 | 0.00 | 20.22 | 0.17 | 20.38 | 0.00 | 20.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 20.48 | 0.00 | 20.48 | 0.17 | 24.51 | 0.00 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 |
February | 1.50 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.51 | 0.00 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Annual Sum or Average | 5.83 | 20.01 | 0.00 | 20.01 | 0.17 | 20.14 | 0.00 | 20.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.34 | 0.00 | 20.34 | 0.17 | 24.51 | 0.00 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.04 | 0.00 | 20.04 | 0.00 | 20.04 | 0.00 | 20.04 |
February | 1.50 | 19.92 | 0.00 | 19.92 | 0.00 | 19.92 | 0.00 | 19.92 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 5.67 | 20.05 | 0.00 | 20.05 | 0.17 | 20.18 | 0.00 | 20.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.32 | 0.00 | 20.32 | 0.17 | 24.45 | 0.00 | 24.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
February | 1.50 | 19.87 | 0.00 | 19.87 | 0.00 | 19.87 | 0.00 | 19.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 5.83 | 20.02 | 0.00 | 20.02 | 0.00 | 20.02 | 0.00 | 20.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
February | 1.83 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
December | 1.33 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Annual Sum or Average | 7.17 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
February | 6.17 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
March | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
December | 3.00 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
Annual Sum or Average | 16.33 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.33 | 21.40 | 195.67 | 21.30 | 195.67 | 21.24 |
February | 339.67 | 21.84 | 122.17 | 21.68 | 114.83 | 21.55 |
March | 261.00 | 22.97 | 103.67 | 23.18 | 6.50 | 23.15 |
April | 107.33 | 23.15 | 246.33 | 23.65 | 1.67 | 23.64 |
May | 18.83 | 23.37 | 421.17 | 23.87 | 0.17 | 23.87 |
June | 8.83 | 23.87 | 452.50 | 23.89 | 5.17 | 23.89 |
July | 19.17 | 23.89 | 495.00 | 23.89 | 19.17 | 23.89 |
August | 22.33 | 23.91 | 497.00 | 23.89 | 22.33 | 23.89 |
September | 18.83 | 23.86 | 457.50 | 23.89 | 15.50 | 23.89 |
October | 98.67 | 23.06 | 264.50 | 23.66 | 9.00 | 23.67 |
November | 246.33 | 22.71 | 110.83 | 23.02 | 6.50 | 22.99 |
December | 442.50 | 22.06 | 81.83 | 22.06 | 52.33 | 21.97 |
Annual Sum or Average | 2052.83 | 22.25 | 3448.17 | 23.08 | 448.83 | 22.96 |
Minimum of Months | 8.83 | 21.40 | 81.83 | 21.30 | 0.17 | 21.24 |
Maximum of Months | 469.33 | 23.91 | 497.00 | 23.89 | 195.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.33 | 21.79 | 96.50 | 21.67 | 96.50 | 21.58 |
February | 304.33 | 22.00 | 70.00 | 22.02 | 44.00 | 21.92 |
March | 195.33 | 23.14 | 107.83 | 23.40 | 1.00 | 23.39 |
April | 70.83 | 23.33 | 252.50 | 23.77 | 0.00 | 23.77 |
May | 10.67 | 23.47 | 421.33 | 23.88 | 0.00 | 23.88 |
June | 1.67 | 23.89 | 452.00 | 23.89 | 0.00 | 23.89 |
July | 7.83 | 23.89 | 494.50 | 23.89 | 7.83 | 23.89 |
August | 3.17 | 23.92 | 497.00 | 23.89 | 3.17 | 23.89 |
September | 10.17 | 23.89 | 452.17 | 23.89 | 9.00 | 23.89 |
October | 65.33 | 23.19 | 273.00 | 23.75 | 2.17 | 23.76 |
November | 207.83 | 23.04 | 109.00 | 23.30 | 3.00 | 23.28 |
December | 421.00 | 22.69 | 46.00 | 22.73 | 13.67 | 22.68 |
Annual Sum or Average | 1757.50 | 22.49 | 3271.83 | 23.31 | 180.33 | 23.25 |
Minimum of Months | 1.67 | 21.79 | 46.00 | 21.67 | 0.00 | 21.58 |
Maximum of Months | 459.33 | 23.92 | 497.00 | 23.89 | 96.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 345.67 | 21.46 | 108.33 | 21.38 | 107.00 | 21.33 |
February | 235.00 | 21.77 | 73.00 | 21.81 | 54.00 | 21.70 |
March | 145.67 | 22.86 | 101.00 | 23.36 | 1.67 | 23.34 |
April | 54.00 | 23.25 | 213.33 | 23.95 | 0.83 | 23.97 |
May | 14.00 | 25.08 | 342.00 | 24.15 | 5.33 | 24.20 |
June | 17.67 | 27.48 | 353.33 | 24.32 | 16.00 | 24.47 |
July | 30.67 | 26.76 | 369.00 | 24.38 | 30.67 | 24.55 |
August | 27.17 | 27.07 | 379.00 | 24.37 | 27.17 | 24.54 |
September | 20.50 | 25.97 | 349.17 | 24.22 | 20.00 | 24.31 |
October | 61.83 | 23.24 | 225.33 | 23.92 | 6.83 | 23.95 |
November | 161.67 | 22.74 | 82.83 | 23.16 | 2.50 | 23.14 |
December | 314.00 | 22.23 | 48.17 | 22.31 | 19.83 | 22.25 |
Annual Sum or Average | 1427.83 | 22.51 | 2644.50 | 23.43 | 291.83 | 23.42 |
Minimum of Months | 14.00 | 21.46 | 48.17 | 21.38 | 0.83 | 21.33 |
Maximum of Months | 345.67 | 27.48 | 379.00 | 24.38 | 107.00 | 24.55 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 346.83 | 21.43 | 117.17 | 21.36 | 116.33 | 21.31 |
February | 240.67 | 21.78 | 75.83 | 21.79 | 59.33 | 21.68 |
March | 154.17 | 22.88 | 100.83 | 23.34 | 2.67 | 23.31 |
April | 55.83 | 23.26 | 211.83 | 23.95 | 0.83 | 23.96 |
May | 14.00 | 25.07 | 341.67 | 24.15 | 5.33 | 24.21 |
June | 17.17 | 27.60 | 353.33 | 24.33 | 15.67 | 24.47 |
July | 30.67 | 26.77 | 369.00 | 24.38 | 30.67 | 24.55 |
August | 26.33 | 27.19 | 379.00 | 24.37 | 26.33 | 24.54 |
September | 20.50 | 25.98 | 349.50 | 24.22 | 20.00 | 24.31 |
October | 65.83 | 23.23 | 222.50 | 23.91 | 7.50 | 23.94 |
November | 167.00 | 22.71 | 81.17 | 23.12 | 3.00 | 23.10 |
December | 319.83 | 22.19 | 51.67 | 22.25 | 24.33 | 22.18 |
Annual Sum or Average | 1458.83 | 22.50 | 2653.50 | 23.41 | 312.00 | 23.38 |
Minimum of Months | 14.00 | 21.43 | 51.67 | 21.36 | 0.83 | 21.31 |
Maximum of Months | 346.83 | 27.60 | 379.00 | 24.38 | 116.33 | 24.55 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 349.67 | 21.42 | 128.17 | 21.33 | 128.17 | 21.29 |
February | 250.00 | 21.82 | 77.17 | 21.77 | 65.33 | 21.66 |
March | 171.17 | 22.89 | 98.33 | 23.30 | 3.33 | 23.27 |
April | 61.17 | 23.24 | 205.33 | 23.92 | 0.67 | 23.93 |
May | 14.33 | 24.84 | 339.17 | 24.14 | 4.67 | 24.19 |
June | 17.83 | 27.43 | 352.67 | 24.32 | 15.83 | 24.47 |
July | 30.67 | 26.75 | 369.00 | 24.38 | 30.67 | 24.55 |
August | 26.83 | 27.10 | 379.00 | 24.36 | 26.83 | 24.53 |
September | 21.83 | 25.83 | 348.00 | 24.22 | 20.83 | 24.31 |
October | 71.00 | 23.16 | 217.33 | 23.87 | 7.83 | 23.91 |
November | 173.67 | 22.66 | 78.33 | 23.05 | 4.00 | 23.02 |
December | 324.50 | 22.12 | 55.83 | 22.17 | 29.50 | 22.09 |
Annual Sum or Average | 1512.67 | 22.48 | 2648.33 | 23.37 | 337.67 | 23.33 |
Minimum of Months | 14.33 | 21.42 | 55.83 | 21.33 | 0.67 | 21.29 |
Maximum of Months | 349.67 | 27.43 | 379.00 | 24.38 | 128.17 | 24.55 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 338.33 | 21.48 | 160.83 | 21.37 | 160.83 | 21.32 |
February | 249.83 | 21.91 | 86.50 | 21.72 | 85.67 | 21.59 |
March | 184.33 | 22.92 | 77.33 | 23.19 | 3.17 | 23.16 |
April | 66.17 | 23.31 | 171.83 | 23.81 | 0.50 | 23.81 |
May | 11.83 | 24.48 | 304.50 | 23.99 | 3.50 | 24.02 |
June | 8.83 | 26.66 | 322.67 | 24.05 | 7.83 | 24.12 |
July | 23.17 | 25.54 | 338.00 | 24.11 | 23.17 | 24.20 |
August | 15.33 | 25.74 | 348.00 | 24.05 | 15.33 | 24.12 |
September | 19.17 | 25.03 | 318.17 | 24.04 | 18.33 | 24.09 |
October | 88.00 | 23.15 | 186.50 | 23.72 | 15.50 | 23.76 |
November | 182.17 | 22.65 | 60.67 | 22.94 | 3.50 | 22.92 |
December | 302.67 | 21.93 | 55.00 | 21.94 | 37.33 | 21.86 |
Annual Sum or Average | 1489.83 | 22.35 | 2430.00 | 23.15 | 374.67 | 23.06 |
Minimum of Months | 8.83 | 21.48 | 55.00 | 21.37 | 0.50 | 21.32 |
Maximum of Months | 338.33 | 26.66 | 348.00 | 24.11 | 160.83 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 339.50 | 21.49 | 163.50 | 21.37 | 163.50 | 21.32 |
February | 259.00 | 21.97 | 88.17 | 21.76 | 87.33 | 21.63 |
March | 199.83 | 22.97 | 69.00 | 23.18 | 3.67 | 23.16 |
April | 77.33 | 23.36 | 159.33 | 23.79 | 0.33 | 23.79 |
May | 13.00 | 24.31 | 294.33 | 23.99 | 3.17 | 24.02 |
June | 9.17 | 26.31 | 318.00 | 24.05 | 7.33 | 24.11 |
July | 25.33 | 25.38 | 338.00 | 24.11 | 25.33 | 24.19 |
August | 16.17 | 25.62 | 348.00 | 24.05 | 16.17 | 24.12 |
September | 19.33 | 25.02 | 313.00 | 24.04 | 18.17 | 24.10 |
October | 94.17 | 23.17 | 172.33 | 23.71 | 15.33 | 23.74 |
November | 192.17 | 22.70 | 56.33 | 22.95 | 4.00 | 22.92 |
December | 305.33 | 21.93 | 56.00 | 21.91 | 41.17 | 21.83 |
Annual Sum or Average | 1550.33 | 22.40 | 2376.00 | 23.14 | 385.50 | 23.04 |
Minimum of Months | 9.17 | 21.49 | 56.00 | 21.37 | 0.33 | 21.32 |
Maximum of Months | 339.50 | 26.31 | 348.00 | 24.11 | 163.50 | 24.19 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.48 | 169.17 | 21.37 | 169.17 | 21.31 |
February | 264.33 | 22.00 | 91.50 | 21.78 | 90.67 | 21.64 |
March | 203.83 | 22.96 | 67.33 | 23.16 | 4.17 | 23.13 |
April | 81.17 | 23.35 | 156.50 | 23.78 | 0.50 | 23.77 |
May | 13.67 | 24.27 | 291.67 | 23.99 | 3.17 | 24.01 |
June | 9.67 | 26.17 | 316.67 | 24.05 | 7.67 | 24.11 |
July | 25.83 | 25.35 | 338.00 | 24.11 | 25.83 | 24.19 |
August | 18.00 | 25.43 | 348.00 | 24.05 | 18.00 | 24.11 |
September | 20.33 | 24.96 | 312.83 | 24.04 | 18.83 | 24.09 |
October | 97.00 | 23.16 | 169.50 | 23.70 | 15.67 | 23.73 |
November | 195.00 | 22.69 | 55.33 | 22.93 | 4.67 | 22.89 |
December | 306.33 | 21.90 | 58.33 | 21.89 | 44.00 | 21.80 |
Annual Sum or Average | 1575.17 | 22.40 | 2374.83 | 23.13 | 402.33 | 23.03 |
Minimum of Months | 9.67 | 21.48 | 55.33 | 21.37 | 0.50 | 21.31 |
Maximum of Months | 340.00 | 26.17 | 348.00 | 24.11 | 169.17 | 24.19 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.46 | 185.67 | 21.35 | 185.67 | 21.30 |
February | 271.83 | 22.02 | 101.17 | 21.78 | 100.33 | 21.64 |
March | 212.67 | 22.93 | 64.67 | 23.11 | 5.33 | 23.07 |
April | 87.50 | 23.31 | 151.83 | 23.74 | 1.33 | 23.73 |
May | 15.33 | 24.19 | 287.83 | 23.98 | 3.50 | 24.01 |
June | 10.17 | 26.06 | 316.33 | 24.05 | 7.67 | 24.11 |
July | 27.17 | 25.28 | 338.00 | 24.11 | 27.17 | 24.19 |
August | 18.33 | 25.41 | 348.00 | 24.05 | 18.33 | 24.11 |
September | 20.83 | 24.93 | 312.00 | 24.04 | 19.33 | 24.09 |
October | 105.83 | 23.15 | 167.50 | 23.67 | 18.00 | 23.71 |
November | 202.67 | 22.69 | 54.50 | 22.90 | 5.83 | 22.86 |
December | 307.83 | 21.86 | 65.33 | 21.83 | 51.83 | 21.74 |
Annual Sum or Average | 1620.17 | 22.40 | 2392.83 | 23.10 | 444.33 | 22.99 |
Minimum of Months | 10.17 | 21.46 | 54.50 | 21.35 | 1.33 | 21.30 |
Maximum of Months | 340.00 | 26.06 | 348.00 | 24.11 | 185.67 | 24.19 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.45 | 232.33 | 21.33 | 232.33 | 21.27 |
February | 291.00 | 22.09 | 137.33 | 21.79 | 136.50 | 21.62 |
March | 241.17 | 22.93 | 63.50 | 22.99 | 17.33 | 22.89 |
April | 109.17 | 23.29 | 135.67 | 23.66 | 4.00 | 23.62 |
May | 24.00 | 24.01 | 279.17 | 23.98 | 6.67 | 24.01 |
June | 15.83 | 25.52 | 320.50 | 24.06 | 13.00 | 24.13 |
July | 33.83 | 25.09 | 338.00 | 24.12 | 33.83 | 24.20 |
August | 24.00 | 25.15 | 348.00 | 24.06 | 24.00 | 24.13 |
September | 24.50 | 24.85 | 310.33 | 24.05 | 20.33 | 24.11 |
October | 121.17 | 23.13 | 167.50 | 23.64 | 22.17 | 23.67 |
November | 218.33 | 22.73 | 51.50 | 22.84 | 13.33 | 22.76 |
December | 313.50 | 21.84 | 108.83 | 21.73 | 97.17 | 21.61 |
Annual Sum or Average | 1756.50 | 22.46 | 2492.67 | 23.02 | 620.67 | 22.88 |
Minimum of Months | 15.83 | 21.45 | 51.50 | 21.33 | 4.00 | 21.27 |
Maximum of Months | 340.00 | 25.52 | 348.00 | 24.12 | 232.33 | 24.20 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.53804 | 24.15485 | -0.4203 | 10.68484 |
February | 448.00000 | 22.33870 | 26.62110 | -0.1754 | 9.32925 |
March | 497.00000 | 23.40703 | 31.91558 | 0.19492 | 7.39189 |
April | 479.00000 | 23.72314 | 39.77894 | 0.36766 | 8.73804 |
May | 496.00000 | 23.87019 | 47.20880 | -0.3473 | 8.03758 |
June | 481.00000 | 23.89003 | 50.18098 | -0.2318 | 6.45932 |
July | 495.00000 | 23.89117 | 55.23629 | -0.1655 | 5.78020 |
August | 497.00000 | 23.89190 | 55.82753 | -0.1426 | 5.61634 |
September | 479.00000 | 23.88901 | 51.55774 | -0.2615 | 6.76025 |
October | 496.00000 | 23.72179 | 43.03695 | 0.40875 | 9.29270 |
November | 480.00000 | 23.28136 | 32.34125 | 0.17140 | 7.54115 |
December | 496.00000 | 22.26104 | 28.31123 | -0.1631 | 7.72181 |
Annual Sum or Average | 5840.00000 | 23.31229 | 40.59465 | -0.0637 | 7.77083 |
Minimum of Months | 448.00000 | 21.53804 | 24.15485 | -0.4203 | 5.61634 |
Maximum of Months | 497.00000 | 23.89190 | 55.82753 | 0.40875 | 10.68484 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.94177 | 25.81446 | -0.2841 | 8.66081 |
February | 448.00000 | 22.60429 | 27.49466 | -0.0751 | 8.18311 |
March | 497.00000 | 23.59448 | 32.31186 | 0.26286 | 7.50817 |
April | 479.00000 | 23.80698 | 39.05074 | 0.39883 | 8.88284 |
May | 496.00000 | 23.88143 | 45.83994 | -0.3467 | 7.87415 |
June | 481.00000 | 23.89087 | 49.12873 | -0.2529 | 6.60565 |
July | 495.00000 | 23.89129 | 53.95613 | -0.1955 | 5.97271 |
August | 497.00000 | 23.89175 | 54.71098 | -0.1772 | 5.81930 |
September | 479.00000 | 23.89018 | 50.12889 | -0.2809 | 6.91899 |
October | 496.00000 | 23.79690 | 42.03138 | 0.42627 | 9.31776 |
November | 480.00000 | 23.52078 | 32.50032 | 0.24029 | 7.39363 |
December | 496.00000 | 22.87454 | 29.30822 | -0.0019 | 6.69985 |
Annual Sum or Average | 5840.00000 | 23.46906 | 40.26531 | -0.0240 | 7.48077 |
Minimum of Months | 448.00000 | 21.94177 | 25.81446 | -0.3467 | 5.81930 |
Maximum of Months | 497.00000 | 23.89175 | 54.71098 | 0.42627 | 9.31776 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.62652 | 23.80333 | -0.3657 | 9.65640 |
February | 336.00000 | 22.44032 | 25.76163 | -0.1259 | 8.73332 |
March | 379.00000 | 23.57337 | 31.58023 | 0.25072 | 7.85391 |
April | 360.00000 | 23.93222 | 38.42526 | 0.41990 | 9.57791 |
May | 375.00000 | 24.08575 | 46.48276 | -0.2800 | 7.43976 |
June | 366.00000 | 24.15620 | 49.64033 | -0.1656 | 6.57258 |
July | 369.00000 | 24.18397 | 54.80207 | -0.0971 | 6.28488 |
August | 379.00000 | 24.17162 | 55.18444 | -0.0835 | 6.13013 |
September | 360.00000 | 24.11105 | 50.94569 | -0.2067 | 6.69844 |
October | 371.00000 | 23.88362 | 42.04525 | 0.44415 | 10.01485 |
November | 360.00000 | 23.43105 | 31.23772 | 0.21177 | 7.62075 |
December | 369.00000 | 22.48983 | 27.29302 | -0.0914 | 7.27378 |
Annual Sum or Average | 4395.00000 | 23.51451 | 39.88195 | -0.0073 | 7.81205 |
Minimum of Months | 336.00000 | 21.62652 | 23.80333 | -0.3657 | 6.13013 |
Maximum of Months | 379.00000 | 24.18397 | 55.18444 | 0.44415 | 10.01485 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.59589 | 23.86526 | -0.3831 | 9.88230 |
February | 336.00000 | 22.41640 | 25.82119 | -0.1389 | 8.80617 |
March | 379.00000 | 23.55423 | 31.62882 | 0.24259 | 7.81658 |
April | 360.00000 | 23.92830 | 38.45736 | 0.41746 | 9.54775 |
May | 375.00000 | 24.08535 | 46.50569 | -0.2800 | 7.44271 |
June | 366.00000 | 24.15685 | 49.62098 | -0.1631 | 6.56027 |
July | 369.00000 | 24.18489 | 54.76043 | -0.0936 | 6.27911 |
August | 379.00000 | 24.17260 | 55.14191 | -0.0802 | 6.12685 |
September | 360.00000 | 24.11132 | 50.94723 | -0.2053 | 6.68957 |
October | 371.00000 | 23.87314 | 42.10443 | 0.44025 | 9.97971 |
November | 360.00000 | 23.39882 | 31.31966 | 0.19985 | 7.59654 |
December | 369.00000 | 22.42676 | 27.40545 | -0.1134 | 7.39194 |
Annual Sum or Average | 4395.00000 | 23.49951 | 39.91300 | -0.0129 | 7.83370 |
Minimum of Months | 336.00000 | 21.59589 | 23.86526 | -0.3831 | 6.12685 |
Maximum of Months | 379.00000 | 24.18489 | 55.14191 | 0.44025 | 9.97971 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.56209 | 23.94706 | -0.4031 | 10.16397 |
February | 336.00000 | 22.37912 | 25.93072 | -0.1579 | 8.90831 |
March | 379.00000 | 23.51253 | 31.74649 | 0.22580 | 7.72954 |
April | 360.00000 | 23.91501 | 38.55045 | 0.40823 | 9.42339 |
May | 375.00000 | 24.08136 | 46.60172 | -0.2877 | 7.54086 |
June | 366.00000 | 24.15463 | 49.67466 | -0.1685 | 6.58677 |
July | 369.00000 | 24.18293 | 54.81644 | -0.0979 | 6.27979 |
August | 379.00000 | 24.17056 | 55.18985 | -0.0845 | 6.12360 |
September | 360.00000 | 24.10882 | 51.02852 | -0.2109 | 6.73232 |
October | 371.00000 | 23.85091 | 42.23365 | 0.42995 | 9.85225 |
November | 360.00000 | 23.34918 | 31.45596 | 0.18133 | 7.55220 |
December | 369.00000 | 22.34074 | 27.56447 | -0.1425 | 7.55541 |
Annual Sum or Average | 4395.00000 | 23.47489 | 40.00963 | -0.0254 | 7.86079 |
Minimum of Months | 336.00000 | 21.56209 | 23.94706 | -0.4031 | 6.12360 |
Maximum of Months | 379.00000 | 24.18293 | 55.18985 | 0.42995 | 10.16397 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.49637 | 25.58893 | -0.4505 | 10.88449 |
February | 308.00000 | 22.29605 | 27.66122 | -0.2015 | 9.17117 |
March | 348.00000 | 23.39677 | 33.45726 | 0.19057 | 7.34046 |
April | 330.00000 | 23.82920 | 40.07412 | 0.38646 | 8.92821 |
May | 344.00000 | 23.95243 | 48.02051 | -0.3237 | 7.75882 |
June | 336.00000 | 23.97757 | 50.99783 | -0.2074 | 6.47537 |
July | 338.00000 | 24.01234 | 56.09110 | -0.1320 | 6.00983 |
August | 348.00000 | 23.97876 | 56.40537 | -0.1229 | 5.81534 |
September | 330.00000 | 23.97525 | 52.45313 | -0.2439 | 6.81312 |
October | 340.00000 | 23.73331 | 43.82033 | 0.40266 | 9.40093 |
November | 330.00000 | 23.22692 | 33.15682 | 0.14172 | 7.40348 |
December | 338.00000 | 22.13095 | 29.46516 | -0.2089 | 7.92917 |
Annual Sum or Average | 4030.00000 | 23.34115 | 41.54816 | -0.0638 | 7.81486 |
Minimum of Months | 308.00000 | 21.49637 | 25.58893 | -0.4505 | 5.81534 |
Maximum of Months | 348.00000 | 24.01234 | 56.40537 | 0.40266 | 10.88449 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.48965 | 25.50684 | -0.4539 | 10.89778 |
February | 308.00000 | 22.28745 | 27.59410 | -0.2096 | 9.14817 |
March | 348.00000 | 23.38315 | 33.41631 | 0.17400 | 7.21909 |
April | 330.00000 | 23.82464 | 40.07472 | 0.36904 | 8.64906 |
May | 344.00000 | 23.95094 | 48.06741 | -0.3513 | 8.12897 |
June | 336.00000 | 23.97639 | 51.07325 | -0.2407 | 6.76375 |
July | 338.00000 | 24.01101 | 56.20626 | -0.1667 | 6.20001 |
August | 348.00000 | 23.97755 | 56.52792 | -0.1586 | 6.00062 |
September | 330.00000 | 23.97437 | 52.51784 | -0.2722 | 7.08808 |
October | 340.00000 | 23.73029 | 43.82221 | 0.38632 | 9.10862 |
November | 330.00000 | 23.22008 | 33.10166 | 0.12864 | 7.32128 |
December | 338.00000 | 22.11719 | 29.39521 | -0.2196 | 7.99270 |
Annual Sum or Average | 4030.00000 | 23.33590 | 41.55822 | -0.0844 | 7.86493 |
Minimum of Months | 308.00000 | 21.48965 | 25.50684 | -0.4539 | 6.00062 |
Maximum of Months | 348.00000 | 24.01101 | 56.52792 | 0.38632 | 10.89778 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.48113 | 25.52520 | -0.4593 | 10.98001 |
February | 308.00000 | 22.27511 | 27.62722 | -0.2162 | 9.18083 |
March | 348.00000 | 23.36336 | 33.46724 | 0.16542 | 7.19248 |
April | 330.00000 | 23.81639 | 40.12071 | 0.36335 | 8.58324 |
May | 344.00000 | 23.94969 | 48.12041 | -0.3559 | 8.20229 |
June | 336.00000 | 23.97600 | 51.10623 | -0.2441 | 6.79664 |
July | 338.00000 | 24.01054 | 56.25746 | -0.1698 | 6.21723 |
August | 348.00000 | 23.97722 | 56.57610 | -0.1615 | 6.01702 |
September | 330.00000 | 23.97381 | 52.56107 | -0.2754 | 7.12218 |
October | 340.00000 | 23.71982 | 43.87524 | 0.38128 | 9.05372 |
November | 330.00000 | 23.20319 | 33.14911 | 0.12161 | 7.31043 |
December | 338.00000 | 22.09012 | 29.44517 | -0.2293 | 8.07621 |
Annual Sum or Average | 4030.00000 | 23.32706 | 41.60229 | -0.0898 | 7.88281 |
Minimum of Months | 308.00000 | 21.48113 | 25.52520 | -0.4593 | 6.01702 |
Maximum of Months | 348.00000 | 24.01054 | 56.57610 | 0.38128 | 10.98001 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.46489 | 25.55909 | -0.4742 | 11.24754 |
February | 308.00000 | 22.24703 | 27.69703 | -0.2336 | 9.32676 |
March | 348.00000 | 23.31912 | 33.59422 | 0.14558 | 7.16656 |
April | 330.00000 | 23.79585 | 40.27077 | 0.35067 | 8.46423 |
May | 344.00000 | 23.94716 | 48.25938 | -0.3625 | 8.33281 |
June | 336.00000 | 23.97615 | 51.14346 | -0.2443 | 6.80725 |
July | 338.00000 | 24.01091 | 56.27223 | -0.1683 | 6.21521 |
August | 348.00000 | 23.97763 | 56.56561 | -0.1595 | 6.01036 |
September | 330.00000 | 23.97379 | 52.59696 | -0.2757 | 7.13886 |
October | 340.00000 | 23.69883 | 43.98529 | 0.37266 | 8.99480 |
November | 330.00000 | 23.17249 | 33.23799 | 0.10793 | 7.31324 |
December | 338.00000 | 22.04002 | 29.53606 | -0.2503 | 8.29773 |
Annual Sum or Average | 4030.00000 | 23.30942 | 41.67616 | -0.0991 | 7.93104 |
Minimum of Months | 308.00000 | 21.46489 | 25.55909 | -0.4742 | 6.01036 |
Maximum of Months | 348.00000 | 24.01091 | 56.56561 | 0.37266 | 11.24754 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.44800 | 25.40255 | -0.5324 | 12.57400 |
February | 308.00000 | 22.19475 | 27.59740 | -0.2940 | 10.16099 |
March | 348.00000 | 23.24308 | 33.75478 | 0.08954 | 7.21103 |
April | 330.00000 | 23.74972 | 40.56778 | 0.31527 | 8.20622 |
May | 344.00000 | 23.94409 | 48.48854 | -0.3689 | 8.61046 |
June | 336.00000 | 23.98174 | 51.04141 | -0.2143 | 6.60871 |
July | 338.00000 | 24.01849 | 55.95717 | -0.1295 | 6.09298 |
August | 348.00000 | 23.98444 | 56.23006 | -0.1177 | 5.86901 |
September | 330.00000 | 23.97894 | 52.43389 | -0.2537 | 7.05248 |
October | 340.00000 | 23.65967 | 44.08195 | 0.35608 | 9.07616 |
November | 330.00000 | 23.14556 | 33.20407 | 0.07549 | 7.41704 |
December | 338.00000 | 21.98542 | 29.42377 | -0.3065 | 9.09859 |
Annual Sum or Average | 4030.00000 | 23.28541 | 41.63178 | -0.1145 | 8.14957 |
Minimum of Months | 308.00000 | 21.44800 | 25.40255 | -0.5324 | 5.86901 |
Maximum of Months | 348.00000 | 24.01849 | 56.23006 | 0.35608 | 12.57400 |
Report: DXReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.550661E+09 | 0.167114E+09 | 49.17 | 0.464908E+09 | 85753045.13 | 0.00 | 0.33 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 | 7712.61 | 31-JAN-14:50 | 7215.65 | 31-JAN-15:00 | 1812.70 | 19-JAN-20:00 | 2257.13 | 31-JAN-14:50 | 0.00 |
February | 0.317676E+10 | 0.929700E+09 | 149.50 | 0.302769E+10 | 0.149063E+09 | 0.00 | 0.62 | 26-FEB-15:00 | 0.00 | 01-FEB-00:10 | 15231.05 | 26-FEB-15:00 | 15231.05 | 26-FEB-15:00 | 2026.03 | 19-FEB-14:50 | 4394.21 | 26-FEB-15:00 | 0.00 |
March | 0.895589E+10 | 0.258492E+10 | 328.42 | 0.800915E+10 | 0.946739E+09 | 0.00 | 0.86 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 23852.85 | 30-MAR-14:00 | 20779.42 | 30-MAR-16:10 | 4343.82 | 30-MAR-12:10 | 6643.53 | 30-MAR-14:00 | 0.00 |
April | 0.163367E+11 | 0.466563E+10 | 408.17 | 0.140570E+11 | 0.227969E+10 | 0.00 | 0.82 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 21599.08 | 23-APR-17:00 | 21197.48 | 17-APR-16:10 | 6484.30 | 04-APR-14:00 | 6274.31 | 17-APR-14:00 | 0.00 |
May | 0.276848E+11 | 0.771726E+10 | 489.39 | 0.218016E+11 | 0.588321E+10 | 0.00 | 1.00 | 30-MAY-14:40 | 0.00 | 01-MAY-00:10 | 30011.55 | 31-MAY-07:03 | 23692.69 | 19-MAY-16:10 | 12080.01 | 31-MAY-07:03 | 8207.51 | 30-MAY-15:00 | 0.00 |
June | 0.397082E+11 | 0.110852E+11 | 485.95 | 0.297684E+11 | 0.993985E+10 | 0.00 | 1.00 | 04-JUN-07:03 | 0.00 | 01-JUN-00:10 | 58408.73 | 23-JUN-07:03 | 40594.86 | 05-JUN-07:02 | 26134.13 | 23-JUN-07:03 | 14769.14 | 26-JUN-07:01 | 0.00 |
July | 0.477447E+11 | 0.133028E+11 | 502.40 | 0.333464E+11 | 0.143984E+11 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 59283.04 | 27-JUL-07:02 | 39591.07 | 25-JUL-07:02 | 29125.82 | 27-JUL-07:02 | 15040.93 | 07-JUL-07:02 | 0.00 |
August | 0.507316E+11 | 0.139623E+11 | 503.72 | 0.346388E+11 | 0.160927E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 59887.29 | 20-AUG-07:01 | 38919.90 | 26-AUG-07:03 | 29667.48 | 20-AUG-07:03 | 15168.21 | 19-AUG-07:02 | 0.00 |
September | 0.341458E+11 | 0.929661E+10 | 483.03 | 0.247215E+11 | 0.942435E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 59069.00 | 17-SEP-07:02 | 39946.04 | 16-SEP-07:02 | 27844.69 | 17-SEP-07:02 | 14735.88 | 17-SEP-07:02 | 0.00 |
October | 0.175246E+11 | 0.483490E+10 | 407.60 | 0.139944E+11 | 0.353018E+10 | 0.00 | 1.00 | 10-OCT-13:30 | 0.00 | 01-OCT-00:10 | 58908.80 | 19-OCT-07:03 | 32386.80 | 18-OCT-07:03 | 29455.83 | 19-OCT-07:03 | 14494.25 | 19-OCT-07:03 | 0.00 |
November | 0.780479E+10 | 0.223259E+10 | 299.17 | 0.666000E+10 | 0.114479E+10 | 0.00 | 0.78 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 21668.26 | 05-NOV-15:00 | 16764.21 | 05-NOV-16:03 | 6099.64 | 05-NOV-12:50 | 5765.28 | 05-NOV-15:00 | 0.00 |
December | 0.161554E+10 | 0.469939E+09 | 86.25 | 0.129444E+10 | 0.321105E+09 | 0.00 | 0.61 | 12-DEC-14:10 | 0.00 | 01-DEC-00:05 | 16122.54 | 12-DEC-14:00 | 12735.74 | 12-DEC-14:30 | 3735.54 | 13-DEC-18:10 | 4449.66 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.255980E+12 | 0.712490E+11 | 4192.75 | 0.191784E+12 | 0.641959E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.550661E+09 | 0.167114E+09 | 49.17 | 0.464908E+09 | 85753045.13 | 0.00 | 0.33 | 0.00 | 7712.61 | 7215.65 | 1812.70 | 2257.13 | 0.00 | ||||||
Maximum of Months | 0.507316E+11 | 0.139623E+11 | 503.72 | 0.346388E+11 | 0.160927E+11 | 0.00 | 1.00 | 0.00 | 59887.29 | 40594.86 | 29667.48 | 15168.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.479553E+09 | 0.135644E+09 | 68.75 | 0.417893E+09 | 61659643.78 | 0.00 | 0.39 | 31-JAN-14:50 | 0.00 | 01-JAN-00:10 | 4763.11 | 31-JAN-14:50 | 4488.69 | 31-JAN-15:00 | 1215.04 | 19-JAN-20:00 | 1290.76 | 31-JAN-14:50 | 0.00 |
February | 0.224866E+10 | 0.614877E+09 | 183.75 | 0.212150E+10 | 0.127164E+09 | 0.00 | 0.68 | 26-FEB-15:00 | 0.00 | 01-FEB-00:10 | 8702.30 | 26-FEB-15:00 | 8702.30 | 26-FEB-15:00 | 1354.47 | 18-FEB-18:10 | 2323.98 | 26-FEB-15:00 | 0.00 |
March | 0.570859E+10 | 0.154350E+10 | 386.00 | 0.518591E+10 | 0.522675E+09 | 0.00 | 0.90 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 12897.96 | 30-MAR-14:00 | 11209.66 | 30-MAR-14:00 | 2254.58 | 30-MAR-12:10 | 3346.08 | 30-MAR-14:00 | 0.00 |
April | 0.939739E+10 | 0.250907E+10 | 443.92 | 0.821161E+10 | 0.118578E+10 | 0.00 | 0.86 | 17-APR-14:00 | 0.00 | 01-APR-00:10 | 11829.13 | 17-APR-14:00 | 11393.48 | 16-APR-14:00 | 3443.87 | 04-APR-13:50 | 3200.57 | 17-APR-14:00 | 0.00 |
May | 0.148397E+11 | 0.387772E+10 | 493.89 | 0.119023E+11 | 0.293742E+10 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 18723.40 | 31-MAY-07:03 | 13006.18 | 30-MAY-07:03 | 5936.16 | 31-MAY-07:03 | 4262.70 | 31-MAY-07:03 | 0.00 |
June | 0.204041E+11 | 0.537296E+10 | 487.72 | 0.155492E+11 | 0.485493E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 29566.71 | 26-JUN-07:01 | 22419.03 | 05-JUN-07:02 | 10305.86 | 27-JUN-07:02 | 7111.33 | 26-JUN-07:01 | 0.00 |
July | 0.243557E+11 | 0.640435E+10 | 502.37 | 0.172944E+11 | 0.706131E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 29963.74 | 27-JUL-07:02 | 21753.94 | 25-JUL-07:02 | 12147.72 | 27-JUL-07:02 | 7247.50 | 07-JUL-07:02 | 0.00 |
August | 0.257073E+11 | 0.668287E+10 | 503.48 | 0.178505E+11 | 0.785678E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 30303.45 | 20-AUG-07:01 | 21779.20 | 26-AUG-07:03 | 12881.28 | 20-AUG-07:03 | 7320.33 | 19-AUG-07:02 | 0.00 |
September | 0.176514E+11 | 0.452831E+10 | 484.13 | 0.130401E+11 | 0.461136E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 29915.45 | 17-SEP-07:02 | 21976.08 | 16-SEP-07:02 | 11892.98 | 17-SEP-07:02 | 7102.17 | 17-SEP-07:02 | 0.00 |
October | 0.990706E+10 | 0.257389E+10 | 444.89 | 0.810027E+10 | 0.180679E+10 | 0.00 | 1.00 | 10-OCT-12:50 | 0.00 | 01-OCT-00:10 | 29764.67 | 19-OCT-07:03 | 18831.32 | 18-OCT-07:03 | 12302.52 | 19-OCT-07:03 | 6963.40 | 19-OCT-07:03 | 0.00 |
November | 0.498904E+10 | 0.133967E+10 | 353.50 | 0.438561E+10 | 0.603434E+09 | 0.00 | 0.80 | 05-NOV-14:10 | 0.00 | 01-NOV-00:10 | 11613.98 | 05-NOV-14:10 | 8844.75 | 05-NOV-16:03 | 3200.37 | 05-NOV-12:50 | 2874.83 | 05-NOV-15:00 | 0.00 |
December | 0.136006E+10 | 0.374574E+09 | 171.00 | 0.115234E+10 | 0.207713E+09 | 0.00 | 0.66 | 12-DEC-14:00 | 0.00 | 01-DEC-00:05 | 9136.00 | 12-DEC-14:00 | 7288.40 | 12-DEC-14:10 | 2190.76 | 13-DEC-18:10 | 2337.71 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.137049E+12 | 0.359574E+11 | 4523.39 | 0.105212E+12 | 0.318370E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.479553E+09 | 0.135644E+09 | 68.75 | 0.417893E+09 | 61659643.78 | 0.00 | 0.39 | 0.00 | 4763.11 | 4488.69 | 1215.04 | 1290.76 | 0.00 | ||||||
Maximum of Months | 0.257073E+11 | 0.668287E+10 | 503.48 | 0.178505E+11 | 0.785678E+10 | 0.00 | 1.00 | 0.00 | 30303.45 | 22419.03 | 12881.28 | 7320.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.251766E+09 | 71502502.47 | 36.33 | 0.218691E+09 | 33075226.52 | 0.00 | 0.34 | 31-JAN-14:50 | 0.00 | 01-JAN-00:10 | 4183.42 | 31-JAN-14:50 | 3949.11 | 31-JAN-15:00 | 1012.17 | 19-JAN-18:20 | 1147.38 | 31-JAN-14:50 | 0.00 |
February | 0.138556E+10 | 0.378601E+09 | 106.83 | 0.133421E+10 | 51355610.86 | 0.00 | 0.63 | 26-FEB-15:00 | 0.00 | 01-FEB-00:10 | 8079.11 | 26-FEB-15:00 | 8079.11 | 26-FEB-15:00 | 1032.59 | 19-FEB-14:40 | 2184.50 | 26-FEB-15:00 | 0.00 |
March | 0.389636E+10 | 0.104936E+10 | 239.92 | 0.348934E+10 | 0.407016E+09 | 0.00 | 0.88 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 12612.31 | 30-MAR-14:00 | 10988.62 | 30-MAR-14:00 | 2252.36 | 30-MAR-12:10 | 3290.31 | 30-MAR-14:00 | 0.00 |
April | 0.674530E+10 | 0.180494E+10 | 302.92 | 0.593605E+10 | 0.809248E+09 | 0.00 | 0.84 | 17-APR-14:00 | 0.00 | 01-APR-00:10 | 11642.80 | 17-APR-14:00 | 11214.70 | 17-APR-14:00 | 3326.80 | 04-APR-13:50 | 3162.77 | 17-APR-14:00 | 0.00 |
May | 0.113851E+11 | 0.297198E+10 | 361.01 | 0.905673E+10 | 0.232833E+10 | 0.00 | 1.00 | 19-MAY-06:03 | 0.00 | 01-MAY-00:10 | 29831.43 | 31-MAY-06:03 | 17920.45 | 19-MAY-06:03 | 12499.93 | 31-MAY-06:03 | 6979.46 | 31-MAY-06:03 | 0.00 |
June | 0.162866E+11 | 0.427496E+10 | 363.12 | 0.122486E+11 | 0.403803E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 30623.80 | 19-JUN-06:02 | 21386.16 | 05-JUN-06:02 | 15077.70 | 19-JUN-06:02 | 7184.22 | 26-JUN-06:01 | 0.00 |
July | 0.191033E+11 | 0.500723E+10 | 369.87 | 0.133303E+11 | 0.577303E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 30843.50 | 27-JUL-06:02 | 20645.04 | 25-JUL-06:02 | 16023.22 | 30-JUL-07:03 | 7236.12 | 07-JUL-06:01 | 0.00 |
August | 0.206854E+11 | 0.536326E+10 | 379.04 | 0.141569E+11 | 0.652859E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 31454.40 | 20-AUG-07:01 | 22115.57 | 26-AUG-06:02 | 17023.47 | 21-AUG-06:04 | 7277.28 | 19-AUG-06:01 | 0.00 |
September | 0.136533E+11 | 0.348994E+10 | 354.81 | 0.997668E+10 | 0.367658E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 31126.47 | 17-SEP-07:02 | 21055.13 | 16-SEP-06:02 | 16566.57 | 17-SEP-07:02 | 7196.01 | 17-SEP-07:02 | 0.00 |
October | 0.706376E+10 | 0.182516E+10 | 294.84 | 0.572724E+10 | 0.133651E+10 | 0.00 | 1.00 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 30804.74 | 19-OCT-06:02 | 16757.21 | 18-OCT-06:03 | 16119.09 | 19-OCT-06:02 | 7077.68 | 19-OCT-06:02 | 0.00 |
November | 0.324267E+10 | 0.868902E+09 | 216.00 | 0.285072E+10 | 0.391946E+09 | 0.00 | 0.77 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 11034.70 | 05-NOV-14:00 | 8200.42 | 05-NOV-14:00 | 2994.70 | 05-NOV-12:40 | 2747.00 | 05-NOV-14:00 | 0.00 |
December | 0.800725E+09 | 0.218454E+09 | 81.33 | 0.657786E+09 | 0.142938E+09 | 0.00 | 0.64 | 12-DEC-14:00 | 0.00 | 01-DEC-00:05 | 8761.25 | 12-DEC-14:00 | 6949.68 | 12-DEC-14:00 | 2121.20 | 13-DEC-18:10 | 2257.93 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.104500E+12 | 0.273243E+11 | 3106.03 | 0.789831E+11 | 0.255166E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.251766E+09 | 71502502.47 | 36.33 | 0.218691E+09 | 33075226.52 | 0.00 | 0.34 | 0.00 | 4183.42 | 3949.11 | 1012.17 | 1147.38 | 0.00 | ||||||
Maximum of Months | 0.206854E+11 | 0.536326E+10 | 379.04 | 0.141569E+11 | 0.652859E+10 | 0.00 | 1.00 | 0.00 | 31454.40 | 22115.57 | 17023.47 | 7277.28 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.224240E+09 | 63850824.11 | 35.42 | 0.194508E+09 | 29732778.67 | 0.00 | 0.33 | 31-JAN-14:50 | 0.00 | 01-JAN-00:10 | 3998.27 | 31-JAN-14:50 | 3774.37 | 31-JAN-15:00 | 946.41 | 19-JAN-18:20 | 1101.02 | 31-JAN-14:50 | 0.00 |
February | 0.132822E+10 | 0.363712E+09 | 104.25 | 0.128161E+10 | 46610998.08 | 0.00 | 0.62 | 26-FEB-15:00 | 0.00 | 01-FEB-00:10 | 7928.20 | 26-FEB-15:00 | 7928.20 | 26-FEB-15:00 | 986.88 | 19-FEB-14:50 | 2150.80 | 26-FEB-15:00 | 0.00 |
March | 0.382307E+10 | 0.103083E+10 | 237.58 | 0.341955E+10 | 0.403522E+09 | 0.00 | 0.88 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 12585.95 | 30-MAR-14:00 | 10962.48 | 30-MAR-14:00 | 2251.68 | 30-MAR-12:10 | 3286.47 | 30-MAR-14:00 | 0.00 |
April | 0.670903E+10 | 0.179674E+10 | 302.33 | 0.590261E+10 | 0.806426E+09 | 0.00 | 0.84 | 17-APR-14:00 | 0.00 | 01-APR-00:10 | 11647.50 | 17-APR-14:00 | 11219.28 | 17-APR-14:00 | 3316.74 | 04-APR-13:50 | 3165.23 | 17-APR-14:00 | 0.00 |
May | 0.113976E+11 | 0.297586E+10 | 360.68 | 0.906480E+10 | 0.233276E+10 | 0.00 | 1.00 | 19-MAY-06:03 | 0.00 | 01-MAY-00:10 | 29904.14 | 31-MAY-06:03 | 18463.07 | 19-MAY-06:03 | 12511.14 | 31-MAY-06:03 | 6995.66 | 31-MAY-06:03 | 0.00 |
June | 0.163744E+11 | 0.429646E+10 | 363.08 | 0.123174E+11 | 0.405700E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 30702.08 | 19-JUN-06:02 | 21514.69 | 05-JUN-06:02 | 15060.79 | 19-JUN-06:02 | 7201.13 | 26-JUN-06:01 | 0.00 |
July | 0.192328E+11 | 0.503894E+10 | 369.86 | 0.134294E+11 | 0.580339E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 30920.35 | 27-JUL-06:02 | 20755.37 | 25-JUL-06:02 | 16063.84 | 30-JUL-07:03 | 7252.88 | 07-JUL-06:01 | 0.00 |
August | 0.208177E+11 | 0.539557E+10 | 379.49 | 0.142553E+11 | 0.656236E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 31537.11 | 20-AUG-07:01 | 22208.26 | 26-AUG-06:02 | 16989.82 | 21-AUG-06:04 | 7293.91 | 19-AUG-06:01 | 0.00 |
September | 0.137076E+11 | 0.350316E+10 | 354.86 | 0.100172E+11 | 0.369040E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 31199.00 | 17-SEP-07:02 | 21125.07 | 16-SEP-06:02 | 16598.16 | 17-SEP-07:02 | 7211.85 | 17-SEP-07:02 | 0.00 |
October | 0.702656E+10 | 0.181637E+10 | 293.51 | 0.569303E+10 | 0.133354E+10 | 0.00 | 1.00 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 30876.02 | 19-OCT-06:02 | 16793.66 | 18-OCT-06:03 | 16153.27 | 19-OCT-06:02 | 7093.40 | 19-OCT-06:02 | 0.00 |
November | 0.315457E+10 | 0.846582E+09 | 212.17 | 0.276930E+10 | 0.385267E+09 | 0.00 | 0.76 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 10952.10 | 05-NOV-14:00 | 8127.48 | 05-NOV-14:00 | 2982.37 | 05-NOV-12:50 | 2731.38 | 05-NOV-14:00 | 0.00 |
December | 0.751448E+09 | 0.205189E+09 | 76.00 | 0.612304E+09 | 0.139144E+09 | 0.00 | 0.63 | 12-DEC-14:00 | 0.00 | 01-DEC-00:05 | 8581.89 | 12-DEC-14:00 | 6792.33 | 12-DEC-14:00 | 2097.37 | 13-DEC-18:10 | 2219.66 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.104547E+12 | 0.273333E+11 | 3089.23 | 0.789570E+11 | 0.255901E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.224240E+09 | 63850824.11 | 35.42 | 0.194508E+09 | 29732778.67 | 0.00 | 0.33 | 0.00 | 3998.27 | 3774.37 | 946.41 | 1101.02 | 0.00 | ||||||
Maximum of Months | 0.208177E+11 | 0.539557E+10 | 379.49 | 0.142553E+11 | 0.656236E+10 | 0.00 | 1.00 | 0.00 | 31537.11 | 22208.26 | 16989.82 | 7293.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.190112E+09 | 54290639.75 | 33.08 | 0.164702E+09 | 25409689.42 | 0.00 | 0.31 | 31-JAN-14:50 | 0.00 | 01-JAN-00:10 | 3755.78 | 31-JAN-14:50 | 3543.12 | 31-JAN-15:00 | 858.59 | 19-JAN-18:20 | 1039.31 | 31-JAN-14:50 | 0.00 |
February | 0.123750E+10 | 0.339676E+09 | 100.42 | 0.119880E+10 | 38698509.20 | 0.00 | 0.61 | 26-FEB-15:00 | 0.00 | 01-FEB-00:10 | 7747.45 | 26-FEB-15:00 | 7747.45 | 26-FEB-15:00 | 920.19 | 19-FEB-14:50 | 2108.59 | 26-FEB-15:00 | 0.00 |
March | 0.365192E+10 | 0.986784E+09 | 231.08 | 0.326060E+10 | 0.391317E+09 | 0.00 | 0.87 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 12441.45 | 30-MAR-14:00 | 10826.63 | 30-MAR-14:00 | 2236.06 | 30-MAR-12:10 | 3255.35 | 30-MAR-14:00 | 0.00 |
April | 0.652628E+10 | 0.175137E+10 | 297.75 | 0.573734E+10 | 0.788946E+09 | 0.00 | 0.84 | 17-APR-14:00 | 0.00 | 01-APR-00:10 | 11542.43 | 17-APR-14:00 | 11115.36 | 17-APR-14:00 | 3281.19 | 04-APR-13:50 | 3141.26 | 17-APR-14:00 | 0.00 |
May | 0.112130E+11 | 0.293264E+10 | 359.76 | 0.890889E+10 | 0.230409E+10 | 0.00 | 1.00 | 19-MAY-06:03 | 0.00 | 01-MAY-00:10 | 29831.23 | 31-MAY-06:03 | 17539.02 | 30-MAY-06:03 | 12538.31 | 31-MAY-06:03 | 6979.77 | 31-MAY-06:03 | 0.00 |
June | 0.162265E+11 | 0.426058E+10 | 362.79 | 0.121953E+11 | 0.403127E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 30632.88 | 19-JUN-06:02 | 21433.26 | 05-JUN-06:02 | 15056.77 | 19-JUN-06:02 | 7186.11 | 26-JUN-06:01 | 0.00 |
July | 0.190971E+11 | 0.500516E+10 | 369.66 | 0.133269E+11 | 0.577016E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 30845.42 | 27-JUL-06:02 | 20658.43 | 25-JUL-06:02 | 16092.50 | 30-JUL-07:03 | 7237.17 | 07-JUL-06:01 | 0.00 |
August | 0.206798E+11 | 0.536134E+10 | 379.31 | 0.141512E+11 | 0.652852E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 31467.09 | 20-AUG-07:01 | 22094.17 | 26-AUG-06:02 | 16961.13 | 21-AUG-06:04 | 7278.23 | 19-AUG-06:01 | 0.00 |
September | 0.135530E+11 | 0.346708E+10 | 354.49 | 0.989335E+10 | 0.365962E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 31127.40 | 17-SEP-07:02 | 21006.85 | 16-SEP-06:02 | 16614.45 | 17-SEP-07:02 | 7196.68 | 17-SEP-07:02 | 0.00 |
October | 0.685186E+10 | 0.177333E+10 | 288.67 | 0.554030E+10 | 0.131156E+10 | 0.00 | 1.00 | 10-OCT-13:00 | 0.00 | 01-OCT-00:10 | 30802.73 | 19-OCT-06:02 | 16674.50 | 18-OCT-06:03 | 16192.79 | 19-OCT-06:02 | 7078.04 | 19-OCT-06:02 | 0.00 |
November | 0.299546E+10 | 0.805674E+09 | 203.25 | 0.262410E+10 | 0.371359E+09 | 0.00 | 0.75 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 10781.58 | 05-NOV-14:00 | 7994.22 | 05-NOV-15:00 | 2949.25 | 05-NOV-12:50 | 2695.65 | 05-NOV-14:00 | 0.00 |
December | 0.681325E+09 | 0.186248E+09 | 66.50 | 0.548869E+09 | 0.132456E+09 | 0.00 | 0.61 | 12-DEC-14:00 | 0.00 | 01-DEC-00:05 | 8316.85 | 12-DEC-14:00 | 6561.11 | 12-DEC-14:00 | 2037.99 | 13-DEC-18:10 | 2160.80 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.102904E+12 | 0.269242E+11 | 3046.78 | 0.775504E+11 | 0.253534E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.190112E+09 | 54290639.75 | 33.08 | 0.164702E+09 | 25409689.42 | 0.00 | 0.31 | 0.00 | 3755.78 | 3543.12 | 858.59 | 1039.31 | 0.00 | ||||||
Maximum of Months | 0.206798E+11 | 0.536134E+10 | 379.31 | 0.141512E+11 | 0.652852E+10 | 0.00 | 1.00 | 0.00 | 31467.09 | 22094.17 | 16961.13 | 7278.23 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.200716E+09 | 61266699.08 | 25.50 | 0.170161E+09 | 30554546.41 | 0.00 | 0.28 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 6164.36 | 31-JAN-15:10 | 5642.31 | 31-JAN-15:10 | 781.34 | 31-JAN-13:50 | 1828.75 | 31-JAN-15:10 | 0.00 |
February | 0.184285E+10 | 0.541499E+09 | 89.67 | 0.180088E+10 | 41971820.34 | 0.00 | 0.59 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 | 13677.81 | 26-FEB-15:10 | 13677.81 | 26-FEB-15:10 | 1610.26 | 19-FEB-15:10 | 3974.23 | 26-FEB-15:10 | 0.00 |
March | 0.592612E+10 | 0.171285E+10 | 219.08 | 0.516426E+10 | 0.761857E+09 | 0.00 | 0.87 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 22993.51 | 30-MAR-14:10 | 19672.17 | 30-MAR-14:20 | 4672.09 | 30-MAR-12:10 | 6388.96 | 30-MAR-14:10 | 0.00 |
April | 0.112518E+11 | 0.322495E+10 | 284.42 | 0.967052E+10 | 0.158126E+10 | 0.00 | 0.84 | 17-APR-14:30 | 0.00 | 01-APR-00:10 | 21691.65 | 19-APR-14:40 | 20524.32 | 17-APR-14:30 | 6501.67 | 04-APR-14:10 | 6224.74 | 17-APR-14:20 | 0.00 |
May | 0.199519E+11 | 0.556500E+10 | 350.61 | 0.154849E+11 | 0.446702E+10 | 0.00 | 1.00 | 22-MAY-07:03 | 0.00 | 01-MAY-00:10 | 38384.33 | 30-MAY-07:03 | 25064.70 | 30-MAY-07:03 | 13319.63 | 30-MAY-07:03 | 9441.54 | 30-MAY-07:03 | 0.00 |
June | 0.296140E+11 | 0.828797E+10 | 354.93 | 0.217771E+11 | 0.783693E+10 | 0.00 | 1.00 | 04-JUN-08:62 | 0.00 | 01-JUN-00:10 | 56599.02 | 19-JUN-07:03 | 41150.35 | 04-JUN-08:62 | 28303.54 | 19-JUN-07:03 | 14134.09 | 26-JUN-07:01 | 0.00 |
July | 0.346991E+11 | 0.969560E+10 | 358.05 | 0.237211E+11 | 0.109781E+11 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 56982.20 | 31-JUL-07:03 | 38200.33 | 25-JUL-07:02 | 30043.16 | 31-JUL-07:03 | 14507.20 | 16-JUL-08:61 | 0.00 |
August | 0.376954E+11 | 0.104180E+11 | 370.13 | 0.252571E+11 | 0.124383E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 58278.99 | 20-AUG-08:61 | 39131.41 | 26-AUG-07:03 | 31849.91 | 20-AUG-08:04 | 14449.36 | 19-AUG-07:02 | 0.00 |
September | 0.241729E+11 | 0.658683E+10 | 343.06 | 0.172029E+11 | 0.696997E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 57647.13 | 17-SEP-08:62 | 37666.00 | 16-SEP-07:02 | 31843.68 | 17-SEP-08:62 | 14214.73 | 17-SEP-08:62 | 0.00 |
October | 0.117683E+11 | 0.324372E+10 | 270.26 | 0.921812E+10 | 0.255021E+10 | 0.00 | 1.00 | 10-OCT-12:40 | 0.00 | 01-OCT-00:10 | 56054.00 | 19-OCT-07:03 | 28122.86 | 18-OCT-07:03 | 28024.95 | 19-OCT-07:03 | 13814.40 | 19-OCT-07:03 | 0.00 |
November | 0.464096E+10 | 0.133423E+10 | 184.25 | 0.395635E+10 | 0.684605E+09 | 0.00 | 0.75 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 19898.32 | 05-NOV-15:00 | 14524.98 | 05-NOV-15:00 | 5579.39 | 05-NOV-14:10 | 5329.43 | 05-NOV-15:00 | 0.00 |
December | 0.979183E+09 | 0.286051E+09 | 53.17 | 0.745823E+09 | 0.233361E+09 | 0.00 | 0.58 | 12-DEC-14:00 | 0.00 | 01-DEC-00:05 | 14623.20 | 12-DEC-14:00 | 11073.06 | 12-DEC-14:00 | 3550.13 | 12-DEC-14:00 | 4064.55 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.182743E+12 | 0.509579E+11 | 2903.12 | 0.134169E+12 | 0.485741E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.200716E+09 | 61266699.08 | 25.50 | 0.170161E+09 | 30554546.41 | 0.00 | 0.28 | 0.00 | 6164.36 | 5642.31 | 781.34 | 1828.75 | 0.00 | ||||||
Maximum of Months | 0.376954E+11 | 0.104180E+11 | 370.13 | 0.252571E+11 | 0.124383E+11 | 0.00 | 1.00 | 0.00 | 58278.99 | 41150.35 | 31849.91 | 14507.20 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 95197361.25 | 27383688.53 | 22.00 | 81397180.38 | 13800180.87 | 0.00 | 0.27 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3092.18 | 31-JAN-15:10 | 2842.74 | 31-JAN-15:10 | 377.53 | 31-JAN-13:50 | 866.49 | 31-JAN-15:10 | 0.00 |
February | 0.937802E+09 | 0.259880E+09 | 88.42 | 0.918213E+09 | 19588524.22 | 0.00 | 0.58 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 | 7084.66 | 26-FEB-15:10 | 7084.66 | 26-FEB-15:10 | 779.91 | 19-FEB-15:10 | 1943.25 | 26-FEB-15:10 | 0.00 |
March | 0.302109E+10 | 0.824362E+09 | 217.75 | 0.264010E+10 | 0.380996E+09 | 0.00 | 0.85 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 11841.38 | 30-MAR-14:10 | 10155.46 | 30-MAR-14:20 | 2377.21 | 30-MAR-12:10 | 3114.26 | 30-MAR-14:10 | 0.00 |
April | 0.575910E+10 | 0.155957E+10 | 282.33 | 0.496565E+10 | 0.793454E+09 | 0.00 | 0.83 | 17-APR-14:30 | 0.00 | 01-APR-00:10 | 11160.92 | 17-APR-14:20 | 10637.89 | 17-APR-14:40 | 3325.70 | 04-APR-14:10 | 3043.06 | 17-APR-14:20 | 0.00 |
May | 0.102412E+11 | 0.270157E+10 | 350.94 | 0.797421E+10 | 0.226699E+10 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 18220.47 | 30-MAY-07:03 | 11983.30 | 30-MAY-07:03 | 6237.17 | 30-MAY-07:03 | 4173.61 | 30-MAY-07:03 | 0.00 |
June | 0.152014E+11 | 0.401582E+10 | 354.54 | 0.112137E+11 | 0.398770E+10 | 0.00 | 1.00 | 04-JUN-08:62 | 0.00 | 01-JUN-00:10 | 29930.62 | 19-JUN-07:03 | 20540.59 | 05-JUN-07:02 | 15017.24 | 19-JUN-07:03 | 7031.99 | 26-JUN-07:01 | 0.00 |
July | 0.178218E+11 | 0.469542E+10 | 358.04 | 0.122267E+11 | 0.559512E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 30132.22 | 31-JUL-07:03 | 20252.06 | 25-JUL-07:02 | 15920.40 | 31-JUL-07:03 | 7217.38 | 16-JUL-08:61 | 0.00 |
August | 0.193601E+11 | 0.504497E+10 | 370.07 | 0.130223E+11 | 0.633784E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 30798.37 | 20-AUG-08:61 | 18643.19 | 03-AUG-07:02 | 16891.73 | 21-AUG-07:03 | 7185.95 | 19-AUG-07:02 | 0.00 |
September | 0.124367E+11 | 0.320113E+10 | 343.74 | 0.888607E+10 | 0.355066E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 30467.99 | 17-SEP-08:62 | 19989.52 | 16-SEP-07:02 | 16872.59 | 17-SEP-08:62 | 7072.04 | 17-SEP-08:62 | 0.00 |
October | 0.604988E+10 | 0.157527E+10 | 269.06 | 0.475836E+10 | 0.129152E+10 | 0.00 | 1.00 | 10-OCT-13:30 | 0.00 | 01-OCT-00:10 | 29621.23 | 19-OCT-07:03 | 14844.33 | 19-OCT-07:03 | 14776.90 | 19-OCT-07:03 | 6872.00 | 19-OCT-07:03 | 0.00 |
November | 0.238175E+10 | 0.646005E+09 | 183.83 | 0.203721E+10 | 0.344539E+09 | 0.00 | 0.74 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 10330.46 | 05-NOV-15:00 | 7569.65 | 05-NOV-15:00 | 2862.09 | 05-NOV-14:10 | 2612.91 | 05-NOV-15:00 | 0.00 |
December | 0.493600E+09 | 0.135997E+09 | 50.67 | 0.375983E+09 | 0.117617E+09 | 0.00 | 0.57 | 12-DEC-14:00 | 0.00 | 01-DEC-00:05 | 7482.45 | 12-DEC-14:00 | 5680.50 | 12-DEC-14:00 | 1801.95 | 12-DEC-14:00 | 1966.56 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.937998E+11 | 0.246874E+11 | 2891.39 | 0.690999E+11 | 0.246998E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 95197361.25 | 27383688.53 | 22.00 | 81397180.38 | 13800180.87 | 0.00 | 0.27 | 0.00 | 3092.18 | 2842.74 | 377.53 | 866.49 | 0.00 | ||||||
Maximum of Months | 0.193601E+11 | 0.504497E+10 | 370.07 | 0.130223E+11 | 0.633784E+10 | 0.00 | 1.00 | 0.00 | 30798.37 | 20540.59 | 16891.73 | 7217.38 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 88167939.61 | 25376719.18 | 20.50 | 75579592.16 | 12588347.45 | 0.00 | 0.26 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3005.46 | 31-JAN-15:10 | 2758.58 | 31-JAN-15:10 | 371.16 | 31-JAN-13:50 | 843.75 | 31-JAN-15:10 | 0.00 |
February | 0.907293E+09 | 0.251756E+09 | 87.25 | 0.889347E+09 | 17945746.73 | 0.00 | 0.57 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 | 6987.12 | 26-FEB-15:10 | 6987.12 | 26-FEB-15:10 | 752.14 | 19-FEB-15:10 | 1920.21 | 26-FEB-15:10 | 0.00 |
March | 0.294758E+10 | 0.805320E+09 | 215.08 | 0.257086E+10 | 0.376722E+09 | 0.00 | 0.85 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 11757.75 | 30-MAR-14:10 | 10070.25 | 30-MAR-14:20 | 2373.63 | 30-MAR-12:10 | 3096.68 | 30-MAR-14:10 | 0.00 |
April | 0.566846E+10 | 0.153711E+10 | 280.33 | 0.488157E+10 | 0.786893E+09 | 0.00 | 0.83 | 17-APR-14:30 | 0.00 | 01-APR-00:10 | 11086.93 | 17-APR-14:20 | 10558.02 | 17-APR-14:40 | 3308.52 | 04-APR-14:10 | 3026.88 | 17-APR-14:20 | 0.00 |
May | 0.101412E+11 | 0.267843E+10 | 349.94 | 0.788462E+10 | 0.225659E+10 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 17433.74 | 30-MAY-07:03 | 11811.79 | 30-MAY-14:50 | 5972.64 | 30-MAY-07:03 | 4027.47 | 30-MAY-15:00 | 0.00 |
June | 0.151163E+11 | 0.399492E+10 | 354.35 | 0.111356E+11 | 0.398073E+10 | 0.00 | 1.00 | 04-JUN-08:62 | 0.00 | 01-JUN-00:10 | 29917.15 | 19-JUN-07:03 | 20499.50 | 05-JUN-07:02 | 15047.92 | 19-JUN-07:03 | 7029.60 | 26-JUN-07:01 | 0.00 |
July | 0.177354E+11 | 0.467334E+10 | 357.89 | 0.121512E+11 | 0.558416E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 30119.12 | 31-JUL-07:03 | 20209.40 | 25-JUL-07:02 | 15950.49 | 31-JUL-07:03 | 7215.04 | 16-JUL-08:61 | 0.00 |
August | 0.192727E+11 | 0.502279E+10 | 369.99 | 0.129456E+11 | 0.632713E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 30785.95 | 20-AUG-08:61 | 18597.11 | 03-AUG-07:02 | 16916.14 | 21-AUG-07:03 | 7183.49 | 19-AUG-07:02 | 0.00 |
September | 0.123602E+11 | 0.318340E+10 | 343.23 | 0.881810E+10 | 0.354210E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 30455.97 | 17-SEP-08:62 | 19942.23 | 16-SEP-07:02 | 16902.46 | 17-SEP-08:62 | 7069.81 | 17-SEP-08:62 | 0.00 |
October | 0.597806E+10 | 0.155787E+10 | 267.64 | 0.469258E+10 | 0.128548E+10 | 0.00 | 1.00 | 10-OCT-13:40 | 0.00 | 01-OCT-00:10 | 29008.93 | 19-OCT-07:03 | 14502.69 | 19-OCT-07:03 | 14506.23 | 19-OCT-07:03 | 6721.17 | 19-OCT-07:03 | 0.00 |
November | 0.232686E+10 | 0.631828E+09 | 181.75 | 0.198700E+10 | 0.339863E+09 | 0.00 | 0.73 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 10255.35 | 05-NOV-15:00 | 7501.23 | 05-NOV-15:00 | 2854.82 | 05-NOV-14:10 | 2597.20 | 05-NOV-15:00 | 0.00 |
December | 0.475207E+09 | 0.131075E+09 | 49.83 | 0.360107E+09 | 0.115099E+09 | 0.00 | 0.56 | 12-DEC-14:00 | 0.00 | 01-DEC-00:05 | 7367.06 | 12-DEC-14:00 | 5579.32 | 12-DEC-14:00 | 1787.74 | 12-DEC-14:00 | 1940.33 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.930174E+11 | 0.244932E+11 | 2877.79 | 0.683921E+11 | 0.246253E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 88167939.61 | 25376719.18 | 20.50 | 75579592.16 | 12588347.45 | 0.00 | 0.26 | 0.00 | 3005.46 | 2758.58 | 371.16 | 843.75 | 0.00 | ||||||
Maximum of Months | 0.192727E+11 | 0.502279E+10 | 369.99 | 0.129456E+11 | 0.632713E+10 | 0.00 | 1.00 | 0.00 | 30785.95 | 20499.50 | 16916.14 | 7215.04 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 77383150.27 | 22303148.65 | 16.50 | 66964189.81 | 10418960.46 | 0.00 | 0.24 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 2863.52 | 31-JAN-15:10 | 2627.93 | 31-JAN-15:10 | 351.99 | 31-JAN-14:00 | 806.83 | 31-JAN-15:10 | 0.00 |
February | 0.855054E+09 | 0.237926E+09 | 84.50 | 0.840540E+09 | 14514206.95 | 0.00 | 0.56 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 | 6827.98 | 26-FEB-15:10 | 6827.98 | 26-FEB-15:10 | 696.97 | 19-FEB-15:10 | 1885.01 | 26-FEB-15:10 | 0.00 |
March | 0.281505E+10 | 0.771485E+09 | 210.67 | 0.245085E+10 | 0.364207E+09 | 0.00 | 0.83 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 11657.50 | 30-MAR-14:10 | 9981.11 | 30-MAR-14:20 | 2355.97 | 30-MAR-12:10 | 3081.46 | 30-MAR-14:10 | 0.00 |
April | 0.550674E+10 | 0.149833E+10 | 274.92 | 0.474344E+10 | 0.763301E+09 | 0.00 | 0.82 | 17-APR-14:30 | 0.00 | 01-APR-00:10 | 11004.67 | 17-APR-14:20 | 10481.96 | 17-APR-14:40 | 3257.94 | 04-APR-14:10 | 3014.51 | 17-APR-14:20 | 0.00 |
May | 0.100195E+11 | 0.265335E+10 | 348.03 | 0.778997E+10 | 0.222955E+10 | 0.00 | 1.00 | 30-MAY-14:10 | 0.00 | 01-MAY-00:10 | 15708.20 | 30-MAY-07:03 | 11799.40 | 30-MAY-14:50 | 5350.82 | 30-MAY-07:03 | 4014.50 | 30-MAY-15:00 | 0.00 |
June | 0.151214E+11 | 0.399946E+10 | 354.37 | 0.111472E+11 | 0.397425E+10 | 0.00 | 1.00 | 04-JUN-08:62 | 0.00 | 01-JUN-00:10 | 30179.52 | 19-JUN-07:03 | 20668.92 | 05-JUN-07:02 | 15220.81 | 19-JUN-07:03 | 7092.65 | 26-JUN-07:01 | 0.00 |
July | 0.177820E+11 | 0.468784E+10 | 357.86 | 0.121997E+11 | 0.558226E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 30384.46 | 31-JUL-07:03 | 20387.94 | 25-JUL-07:02 | 16125.70 | 31-JUL-07:03 | 7279.96 | 16-JUL-08:61 | 0.00 |
August | 0.193441E+11 | 0.504344E+10 | 370.37 | 0.130132E+11 | 0.633085E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 31062.19 | 20-AUG-08:61 | 18792.06 | 03-AUG-07:02 | 17063.92 | 21-AUG-07:03 | 7248.04 | 19-AUG-07:02 | 0.00 |
September | 0.123685E+11 | 0.318863E+10 | 342.89 | 0.883292E+10 | 0.353558E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 30725.78 | 17-SEP-08:62 | 20124.05 | 16-SEP-07:02 | 17075.27 | 17-SEP-08:62 | 7133.43 | 17-SEP-08:62 | 0.00 |
October | 0.591123E+10 | 0.154285E+10 | 264.64 | 0.463832E+10 | 0.127292E+10 | 0.00 | 1.00 | 10-OCT-13:50 | 0.00 | 01-OCT-00:10 | 28109.34 | 19-OCT-07:03 | 14050.87 | 19-OCT-07:03 | 14058.47 | 19-OCT-07:03 | 6495.30 | 19-OCT-07:03 | 0.00 |
November | 0.224989E+10 | 0.612302E+09 | 179.75 | 0.191902E+10 | 0.330871E+09 | 0.00 | 0.73 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 10180.37 | 05-NOV-15:00 | 7442.93 | 05-NOV-15:00 | 2839.32 | 05-NOV-14:10 | 2585.78 | 05-NOV-15:00 | 0.00 |
December | 0.447162E+09 | 0.123616E+09 | 47.00 | 0.336684E+09 | 0.110478E+09 | 0.00 | 0.54 | 12-DEC-14:00 | 0.00 | 01-DEC-00:05 | 7193.26 | 12-DEC-14:00 | 5438.21 | 12-DEC-14:00 | 1755.05 | 12-DEC-14:00 | 1903.03 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.924980E+11 | 0.243815E+11 | 2851.49 | 0.679788E+11 | 0.245192E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 77383150.27 | 22303148.65 | 16.50 | 66964189.81 | 10418960.46 | 0.00 | 0.24 | 0.00 | 2863.52 | 2627.93 | 351.99 | 806.83 | 0.00 | ||||||
Maximum of Months | 0.193441E+11 | 0.504344E+10 | 370.37 | 0.130132E+11 | 0.633085E+10 | 0.00 | 1.00 | 0.00 | 31062.19 | 20668.92 | 17075.27 | 7279.96 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 76453963.99 | 22124672.33 | 14.50 | 67227997.70 | 9225966.30 | 0.00 | 0.22 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 2980.03 | 31-JAN-15:10 | 2758.76 | 31-JAN-15:10 | 333.91 | 31-JAN-14:00 | 845.88 | 31-JAN-15:10 | 0.00 |
February | 0.861550E+09 | 0.241984E+09 | 79.42 | 0.851945E+09 | 9605424.72 | 0.00 | 0.50 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 | 7064.72 | 26-FEB-15:10 | 7064.72 | 26-FEB-15:10 | 594.59 | 19-FEB-16:00 | 1984.48 | 26-FEB-15:10 | 0.00 |
March | 0.277484E+10 | 0.771380E+09 | 204.33 | 0.243048E+10 | 0.344361E+09 | 0.00 | 0.76 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 12149.96 | 30-MAR-14:10 | 10445.12 | 30-MAR-14:20 | 2426.75 | 30-MAR-12:10 | 3291.67 | 30-MAR-14:10 | 0.00 |
April | 0.561327E+10 | 0.155248E+10 | 266.58 | 0.489299E+10 | 0.720276E+09 | 0.00 | 0.74 | 17-APR-14:10 | 0.00 | 01-APR-00:10 | 11553.75 | 17-APR-14:10 | 11006.46 | 17-APR-14:20 | 3248.09 | 04-APR-14:10 | 3237.21 | 17-APR-14:10 | 0.00 |
May | 0.105711E+11 | 0.284739E+10 | 342.50 | 0.832274E+10 | 0.224841E+10 | 0.00 | 0.95 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 16376.55 | 30-MAY-15:00 | 12780.35 | 30-MAY-14:30 | 4872.14 | 31-MAY-13:00 | 4341.66 | 30-MAY-15:00 | 0.00 |
June | 0.164625E+11 | 0.439368E+10 | 354.80 | 0.123176E+11 | 0.414491E+10 | 0.00 | 1.00 | 04-JUN-08:62 | 0.00 | 01-JUN-00:10 | 35787.44 | 26-JUN-07:01 | 22641.19 | 15-JUN-07:02 | 17179.75 | 26-JUN-07:03 | 8388.48 | 26-JUN-07:01 | 0.00 |
July | 0.194455E+11 | 0.515465E+10 | 359.30 | 0.136048E+11 | 0.584077E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 35957.63 | 27-JUL-07:02 | 22200.04 | 18-JUL-07:02 | 19608.33 | 27-JUL-07:02 | 8593.76 | 16-JUL-08:61 | 0.00 |
August | 0.211840E+11 | 0.555310E+10 | 371.59 | 0.145360E+11 | 0.664797E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 37020.43 | 20-AUG-08:61 | 21530.82 | 10-AUG-07:02 | 21554.81 | 20-AUG-08:61 | 8584.55 | 19-AUG-07:02 | 0.00 |
September | 0.134815E+11 | 0.351649E+10 | 341.82 | 0.981895E+10 | 0.366255E+10 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 | 36310.87 | 17-SEP-08:62 | 21400.83 | 16-SEP-07:02 | 20644.29 | 17-SEP-08:62 | 8413.50 | 17-SEP-08:62 | 0.00 |
October | 0.636387E+10 | 0.168241E+10 | 261.83 | 0.506690E+10 | 0.129697E+10 | 0.00 | 1.00 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 | 24899.82 | 19-OCT-07:03 | 12877.25 | 10-OCT-14:10 | 13782.85 | 19-OCT-07:03 | 5564.16 | 19-OCT-07:03 | 0.00 |
November | 0.235125E+10 | 0.646441E+09 | 177.50 | 0.202345E+10 | 0.327801E+09 | 0.00 | 0.66 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 10622.74 | 05-NOV-15:00 | 7859.39 | 05-NOV-15:00 | 2864.41 | 05-NOV-14:10 | 2755.88 | 05-NOV-15:00 | 0.00 |
December | 0.451248E+09 | 0.125951E+09 | 45.83 | 0.343526E+09 | 0.107722E+09 | 0.00 | 0.48 | 12-DEC-14:00 | 0.00 | 01-DEC-00:05 | 7397.75 | 12-DEC-14:00 | 5646.48 | 12-DEC-14:00 | 1751.28 | 12-DEC-14:00 | 1991.62 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.996372E+11 | 0.265081E+11 | 2820.01 | 0.742766E+11 | 0.253606E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 76453963.99 | 22124672.33 | 14.50 | 67227997.70 | 9225966.30 | 0.00 | 0.22 | 0.00 | 2980.03 | 2758.76 | 333.91 | 845.88 | 0.00 | ||||||
Maximum of Months | 0.211840E+11 | 0.555310E+10 | 371.59 | 0.145360E+11 | 0.664797E+10 | 0.00 | 1.00 | 0.00 | 37020.43 | 22641.19 | 21554.81 | 8593.76 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 204.07 | 227.46 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 208.31 | 198.18 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 202.66 | 140.02 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 170.02 | 114.85 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.55 | 76.17 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 163.15 | 48.78 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 175.35 | 34.94 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 212.47 | 30.05 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.75 | 65.86 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.01 | 133.30 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 231.97 | 169.96 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 214.33 | 200.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.12 | 119.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.55 | 30.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.01 | 227.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 204.07 | 227.46 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 208.31 | 198.18 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 202.66 | 140.02 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 170.02 | 114.85 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.55 | 76.17 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 163.15 | 48.78 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 175.35 | 34.94 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 212.47 | 30.05 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.75 | 65.86 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.01 | 133.30 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 231.97 | 169.96 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 214.33 | 200.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.12 | 119.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.55 | 30.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.01 | 227.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 204.07 | 227.46 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 208.31 | 198.18 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 202.66 | 140.02 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 170.02 | 114.85 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.55 | 76.17 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 163.15 | 48.78 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 175.35 | 34.94 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 212.47 | 30.05 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.75 | 65.86 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.01 | 133.30 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 231.97 | 169.96 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 214.33 | 200.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.12 | 119.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.55 | 30.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.01 | 227.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 204.07 | 227.46 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 208.31 | 198.18 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 202.66 | 140.02 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 170.02 | 114.85 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.55 | 76.17 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 163.15 | 48.78 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 175.35 | 34.94 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 212.47 | 30.05 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.75 | 65.86 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.01 | 133.30 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 231.97 | 169.96 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 214.33 | 200.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.12 | 119.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.55 | 30.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.01 | 227.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 101.17 | 112.91 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 103.35 | 98.27 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 100.71 | 69.37 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 84.55 | 56.88 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 72.42 | 37.69 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 81.18 | 24.15 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 87.29 | 17.28 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 105.75 | 14.87 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.33 | 32.57 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 120.19 | 65.99 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 115.08 | 84.24 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 106.32 | 99.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 97.94 | 59.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 72.42 | 14.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 120.19 | 112.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 101.17 | 112.91 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 103.35 | 98.27 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 100.71 | 69.37 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 84.55 | 56.88 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 72.42 | 37.69 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 81.18 | 24.15 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 87.29 | 17.28 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 105.75 | 14.87 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.33 | 32.57 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 120.19 | 65.99 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 115.08 | 84.24 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 106.32 | 99.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 97.94 | 59.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 72.42 | 14.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 120.19 | 112.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 199.99 | 240.41 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 204.66 | 208.99 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 198.98 | 146.88 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 167.56 | 119.96 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 144.54 | 78.86 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 163.47 | 49.88 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 176.18 | 35.61 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 213.51 | 30.23 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.64 | 66.73 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 240.37 | 136.90 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 228.93 | 176.42 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 209.87 | 213.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 195.30 | 124.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 144.54 | 30.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 240.37 | 240.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 199.99 | 240.41 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 204.66 | 208.99 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 198.98 | 146.88 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 167.56 | 119.96 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 144.54 | 78.86 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 163.47 | 49.88 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 176.18 | 35.61 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 213.51 | 30.23 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.64 | 66.73 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 240.37 | 136.90 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 228.93 | 176.42 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 209.87 | 213.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 195.30 | 124.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 144.54 | 30.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 240.37 | 240.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 99.23 | 119.28 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 101.61 | 103.57 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 98.95 | 72.74 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 83.39 | 59.40 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 71.95 | 39.01 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 81.34 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 87.69 | 17.62 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 106.26 | 14.96 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.29 | 33.00 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 119.42 | 67.76 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 113.63 | 87.43 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 104.18 | 105.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 97.08 | 61.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 71.95 | 14.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 119.42 | 119.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 201.03 | 231.10 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 205.29 | 203.31 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 199.03 | 145.86 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 166.95 | 121.89 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 143.45 | 82.96 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.34 | 55.91 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.59 | 41.83 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 210.76 | 36.74 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 194.52 | 72.10 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 239.89 | 138.51 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 229.49 | 174.06 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 210.94 | 205.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 194.59 | 125.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 143.45 | 36.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 239.89 | 231.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 201.03 | 231.10 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 205.29 | 203.31 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 199.03 | 145.86 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 166.95 | 121.89 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 143.45 | 82.96 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.34 | 55.91 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.59 | 41.83 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 210.76 | 36.74 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 194.52 | 72.10 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 239.89 | 138.51 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 229.49 | 174.06 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 210.94 | 205.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 194.59 | 125.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 143.45 | 36.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 239.89 | 231.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 99.19 | 114.06 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 101.36 | 100.24 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 98.43 | 71.90 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 82.62 | 60.10 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 71.00 | 40.91 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.81 | 27.61 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.39 | 20.65 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.29 | 18.16 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.20 | 35.56 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 118.52 | 68.26 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 113.27 | 85.84 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 104.13 | 101.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 96.18 | 61.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 71.00 | 18.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 118.52 | 114.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 201.68 | 227.54 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 205.77 | 200.64 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 199.38 | 144.46 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 167.07 | 121.29 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 143.44 | 82.97 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.17 | 56.48 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.33 | 42.62 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 210.54 | 37.55 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 194.44 | 72.41 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 239.99 | 137.80 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 229.96 | 172.24 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 211.65 | 202.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 194.77 | 124.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 143.44 | 37.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 239.99 | 227.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 201.68 | 227.54 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 205.77 | 200.64 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 199.38 | 144.46 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 167.07 | 121.29 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 143.44 | 82.97 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.17 | 56.48 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.33 | 42.62 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 210.54 | 37.55 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 194.44 | 72.41 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 239.99 | 137.80 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 229.96 | 172.24 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 211.65 | 202.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 194.77 | 124.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 143.44 | 37.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 239.99 | 227.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 99.50 | 112.31 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 101.59 | 98.93 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 98.60 | 71.22 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 82.67 | 59.80 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 71.00 | 40.91 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.73 | 27.89 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.27 | 21.04 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.18 | 18.56 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.16 | 35.71 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 118.57 | 67.91 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 113.50 | 84.95 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 104.47 | 99.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 96.26 | 61.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 71.00 | 18.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 118.57 | 112.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 202.44 | 224.93 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 206.43 | 198.24 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 200.10 | 142.73 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 167.55 | 120.07 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 143.79 | 82.10 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.44 | 55.79 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.55 | 42.04 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 210.75 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 194.68 | 71.70 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 240.39 | 136.54 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 230.69 | 170.37 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 212.56 | 199.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 195.26 | 123.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 143.79 | 36.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 240.39 | 224.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 202.44 | 224.93 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 206.43 | 198.24 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 200.10 | 142.73 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 167.55 | 120.07 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 143.79 | 82.10 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.44 | 55.79 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.55 | 42.04 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 210.75 | 36.96 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 194.68 | 71.70 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 240.39 | 136.54 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 230.69 | 170.37 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 212.56 | 199.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 195.26 | 123.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 143.79 | 36.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 240.39 | 224.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 99.87 | 111.04 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 101.91 | 97.76 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 98.94 | 70.37 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 82.90 | 59.21 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 71.16 | 40.48 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.86 | 27.55 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.38 | 20.76 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.28 | 18.27 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.27 | 35.36 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 118.76 | 67.29 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 113.85 | 84.03 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 104.92 | 98.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 96.50 | 60.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 71.16 | 18.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 118.76 | 111.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 206.11 | 215.40 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 209.66 | 189.36 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 203.37 | 136.45 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 169.80 | 114.91 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.01 | 77.89 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.85 | 52.02 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.87 | 38.94 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 211.04 | 33.80 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.43 | 68.13 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.41 | 131.47 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 233.78 | 164.07 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 216.38 | 190.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.28 | 117.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.01 | 33.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.41 | 215.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 206.11 | 215.40 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 209.66 | 189.36 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 203.37 | 136.45 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 169.80 | 114.91 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.01 | 77.89 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.85 | 52.02 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.87 | 38.94 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 211.04 | 33.80 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.43 | 68.13 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.41 | 131.47 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 233.78 | 164.07 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 216.38 | 190.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.28 | 117.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.01 | 33.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.41 | 215.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 206.11 | 215.40 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 209.66 | 189.36 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 203.37 | 136.45 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 169.80 | 114.91 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.01 | 77.89 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.85 | 52.02 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.87 | 38.94 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 211.04 | 33.80 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.43 | 68.13 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.41 | 131.47 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 233.78 | 164.07 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 216.38 | 190.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.28 | 117.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.01 | 33.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.41 | 215.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 206.11 | 215.40 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 209.66 | 189.36 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 203.37 | 136.45 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 169.80 | 114.91 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.01 | 77.89 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.85 | 52.02 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.87 | 38.94 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 211.04 | 33.80 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.43 | 68.13 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.41 | 131.47 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 233.78 | 164.07 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 216.38 | 190.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.28 | 117.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.01 | 33.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.41 | 215.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 101.59 | 106.39 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 103.42 | 93.44 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 100.48 | 67.30 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 83.94 | 56.68 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 71.71 | 38.41 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.03 | 25.69 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.50 | 19.22 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.39 | 16.70 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.59 | 33.60 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 119.69 | 64.82 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 115.30 | 80.96 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 106.72 | 93.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 97.44 | 57.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 71.71 | 16.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 119.69 | 106.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 101.59 | 106.39 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 103.42 | 93.44 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 100.48 | 67.30 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 83.94 | 56.68 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 71.71 | 38.41 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.03 | 25.69 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.50 | 19.22 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.39 | 16.70 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.59 | 33.60 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 119.69 | 64.82 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 115.30 | 80.96 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 106.72 | 93.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 97.44 | 57.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 71.71 | 16.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 119.69 | 106.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 205.08 | 216.48 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 208.83 | 190.01 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 202.90 | 136.10 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 169.69 | 114.35 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.32 | 77.00 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 162.72 | 50.84 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 173.84 | 37.69 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 211.95 | 32.40 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.72 | 67.00 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.08 | 130.96 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 233.29 | 163.95 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 215.59 | 190.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.23 | 116.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.32 | 32.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.08 | 216.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 205.08 | 216.48 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 208.83 | 190.01 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 202.90 | 136.10 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 169.69 | 114.35 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.32 | 77.00 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 162.72 | 50.84 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 173.84 | 37.69 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 211.95 | 32.40 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.72 | 67.00 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.08 | 130.96 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 233.29 | 163.95 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 215.59 | 190.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.23 | 116.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.32 | 32.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.08 | 216.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 101.12 | 106.89 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 103.05 | 93.74 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 100.27 | 67.12 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 83.90 | 56.39 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 71.86 | 37.97 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.44 | 25.11 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.96 | 18.61 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.82 | 16.02 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.74 | 33.05 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 119.55 | 64.56 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 115.09 | 80.88 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 106.37 | 93.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 97.42 | 57.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 71.86 | 16.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 119.55 | 106.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 205.30 | 215.76 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 209.09 | 189.20 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 203.29 | 135.23 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 170.01 | 113.67 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.57 | 76.55 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 162.93 | 50.53 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 174.04 | 37.41 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 212.13 | 32.13 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.87 | 66.67 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.30 | 130.40 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 233.59 | 163.25 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 215.93 | 189.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.48 | 116.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.57 | 32.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.30 | 215.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 205.30 | 215.76 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 209.09 | 189.20 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 203.29 | 135.23 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 170.01 | 113.67 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.57 | 76.55 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 162.93 | 50.53 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 174.04 | 37.41 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 212.13 | 32.13 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.87 | 66.67 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.30 | 130.40 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 233.59 | 163.25 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 215.93 | 189.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.48 | 116.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.57 | 32.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.30 | 215.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 101.23 | 106.54 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 103.17 | 93.33 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 100.47 | 66.70 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 84.05 | 56.06 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 71.98 | 37.75 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.53 | 24.96 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 86.05 | 18.47 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.91 | 15.89 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.81 | 32.89 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 119.65 | 64.28 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 115.24 | 80.54 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 106.53 | 93.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 97.54 | 57.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 71.98 | 15.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 119.65 | 106.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 206.00 | 213.06 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 209.82 | 186.44 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 204.25 | 132.73 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 170.75 | 111.75 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.98 | 75.57 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 163.00 | 50.29 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 173.98 | 37.38 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 212.03 | 32.21 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.91 | 66.45 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.65 | 129.19 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 234.27 | 161.51 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 216.77 | 186.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.93 | 114.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.98 | 32.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.65 | 213.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 206.00 | 213.06 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 209.82 | 186.44 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 204.25 | 132.73 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 170.75 | 111.75 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 145.98 | 75.57 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 163.00 | 50.29 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 173.98 | 37.38 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 212.03 | 32.21 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.91 | 66.45 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 242.65 | 129.19 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 234.27 | 161.51 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 216.77 | 186.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 197.93 | 114.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 145.98 | 32.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 242.65 | 213.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 101.56 | 105.22 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 103.52 | 91.99 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 100.93 | 65.47 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 84.41 | 55.12 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 72.17 | 37.26 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.57 | 24.84 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 86.03 | 18.46 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.86 | 15.93 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.83 | 32.78 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 119.83 | 63.69 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 115.57 | 79.68 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 106.94 | 92.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 97.76 | 56.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 72.17 | 15.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 119.83 | 105.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 208.61 | 199.92 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 212.27 | 173.47 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 207.12 | 121.30 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 172.90 | 102.16 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 146.75 | 70.06 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.91 | 48.37 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.24 | 36.61 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 210.06 | 32.16 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.05 | 64.83 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 243.27 | 123.31 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 236.16 | 153.45 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 219.44 | 174.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 198.78 | 108.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 146.75 | 32.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 243.27 | 199.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.93 | 126.14 | 54.79 | 208.61 | 199.92 | 0.00 | 0.00 | 0.00 |
February | 168.87 | 113.20 | 55.67 | 212.27 | 173.47 | 0.00 | 0.00 | 0.00 |
March | 151.87 | 79.15 | 72.72 | 207.12 | 121.30 | 0.00 | 0.00 | 0.00 |
April | 113.74 | 37.02 | 76.72 | 172.90 | 102.16 | 0.00 | 0.00 | 0.00 |
May | 91.90 | 10.68 | 81.22 | 146.75 | 70.06 | 0.00 | 0.00 | 0.00 |
June | 84.97 | 4.73 | 80.24 | 161.91 | 48.37 | 0.00 | 0.00 | 0.00 |
July | 85.90 | 6.41 | 79.50 | 172.24 | 36.61 | 0.00 | 0.00 | 0.00 |
August | 102.56 | 19.16 | 83.40 | 210.06 | 32.16 | 0.00 | 0.00 | 0.00 |
September | 112.79 | 41.95 | 70.84 | 195.05 | 64.83 | 0.00 | 0.00 | 0.00 |
October | 163.52 | 105.93 | 57.59 | 243.27 | 123.31 | 0.00 | 0.00 | 0.00 |
November | 175.91 | 116.73 | 59.18 | 236.16 | 153.45 | 0.00 | 0.00 | 0.00 |
December | 178.35 | 125.47 | 52.88 | 219.44 | 174.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.13 | 65.32 | 68.80 | 198.78 | 108.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 84.97 | 4.73 | 52.88 | 146.75 | 32.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.93 | 126.14 | 83.40 | 243.27 | 199.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 102.81 | 98.78 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 104.69 | 85.63 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 102.30 | 59.85 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 85.44 | 50.40 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 72.55 | 34.55 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.05 | 23.89 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.20 | 18.08 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 103.92 | 15.90 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.42 | 31.98 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 120.13 | 60.80 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 116.47 | 75.72 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 108.22 | 86.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 98.17 | 53.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 72.55 | 15.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 120.13 | 98.78 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.546585E+09 | 0.609221E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.503942E+09 | 0.479440E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.542811E+09 | 0.375022E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.440700E+09 | 0.297699E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.389843E+09 | 0.204002E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.422897E+09 | 0.126435E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.469656E+09 | 93573936.71 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.569074E+09 | 80492619.76 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507372E+09 | 0.170716E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.648192E+09 | 0.357025E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.601278E+09 | 0.440536E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.574073E+09 | 0.537794E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.621642E+10 | 0.377196E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.389843E+09 | 80492619.76 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.648192E+09 | 0.609221E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.546585E+09 | 0.609221E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.503942E+09 | 0.479440E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.542811E+09 | 0.375022E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.440700E+09 | 0.297699E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.389843E+09 | 0.204002E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.422897E+09 | 0.126435E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.469656E+09 | 93573936.71 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.569074E+09 | 80492619.76 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507372E+09 | 0.170716E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.648192E+09 | 0.357025E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.601278E+09 | 0.440536E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.574073E+09 | 0.537794E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.621642E+10 | 0.377196E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.389843E+09 | 80492619.76 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.648192E+09 | 0.609221E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.546585E+09 | 0.609221E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.503942E+09 | 0.479440E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.542811E+09 | 0.375022E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.440700E+09 | 0.297699E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.389843E+09 | 0.204002E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.422897E+09 | 0.126435E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.469656E+09 | 93573936.71 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.569074E+09 | 80492619.76 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507372E+09 | 0.170716E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.648192E+09 | 0.357025E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.601278E+09 | 0.440536E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.574073E+09 | 0.537794E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.621642E+10 | 0.377196E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.389843E+09 | 80492619.76 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.648192E+09 | 0.609221E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.546585E+09 | 0.609221E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.503942E+09 | 0.479440E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.542811E+09 | 0.375022E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.440700E+09 | 0.297699E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.389843E+09 | 0.204002E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.422897E+09 | 0.126435E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.469656E+09 | 93573936.71 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.569074E+09 | 80492619.76 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507372E+09 | 0.170716E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.648192E+09 | 0.357025E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.601278E+09 | 0.440536E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.574073E+09 | 0.537794E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.621642E+10 | 0.377196E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.389843E+09 | 80492619.76 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.648192E+09 | 0.609221E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.270978E+09 | 0.302422E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.250020E+09 | 0.237735E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.269755E+09 | 0.185806E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.219162E+09 | 0.147438E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.193968E+09 | 0.100938E+09 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.210418E+09 | 62590821.45 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.233805E+09 | 46280424.70 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.283247E+09 | 39826347.50 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.252276E+09 | 84432173.89 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.321911E+09 | 0.176755E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.298285E+09 | 0.218355E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.284774E+09 | 0.266600E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.308860E+10 | 0.186918E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.193968E+09 | 39826347.50 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.321911E+09 | 0.302422E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.270978E+09 | 0.302422E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.250020E+09 | 0.237735E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.269755E+09 | 0.185806E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.219162E+09 | 0.147438E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.193968E+09 | 0.100938E+09 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.210418E+09 | 62590821.45 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.233805E+09 | 46280424.70 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.283247E+09 | 39826347.50 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.252276E+09 | 84432173.89 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.321911E+09 | 0.176755E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.298285E+09 | 0.218355E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.284774E+09 | 0.266600E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.308860E+10 | 0.186918E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.193968E+09 | 39826347.50 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.321911E+09 | 0.302422E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.535666E+09 | 0.643920E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.495118E+09 | 0.505579E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.532937E+09 | 0.393391E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.434327E+09 | 0.310948E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.387147E+09 | 0.211205E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.423718E+09 | 0.129293E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.471868E+09 | 95377478.77 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.571871E+09 | 80961527.04 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507108E+09 | 0.172953E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.643795E+09 | 0.366672E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.593398E+09 | 0.457270E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.562120E+09 | 0.572525E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.615907E+10 | 0.394010E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.387147E+09 | 80961527.04 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.643795E+09 | 0.643920E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.535666E+09 | 0.643920E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.495118E+09 | 0.505579E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.532937E+09 | 0.393391E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.434327E+09 | 0.310948E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.387147E+09 | 0.211205E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.423718E+09 | 0.129293E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.471868E+09 | 95377478.77 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.571871E+09 | 80961527.04 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507108E+09 | 0.172953E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.643795E+09 | 0.366672E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.593398E+09 | 0.457270E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.562120E+09 | 0.572525E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.615907E+10 | 0.394010E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.387147E+09 | 80961527.04 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.643795E+09 | 0.643920E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.265777E+09 | 0.319484E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.245823E+09 | 0.250553E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.265032E+09 | 0.194831E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.216135E+09 | 0.153953E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.192704E+09 | 0.104491E+09 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.210822E+09 | 64015767.43 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.234877E+09 | 47183127.04 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.284608E+09 | 40080622.50 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.252185E+09 | 85544098.51 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.319845E+09 | 0.181486E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.294520E+09 | 0.226607E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.279032E+09 | 0.283775E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.306136E+10 | 0.195200E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.192704E+09 | 40080622.50 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.319845E+09 | 0.319484E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.538444E+09 | 0.618981E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.496649E+09 | 0.491838E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.533079E+09 | 0.390662E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.432738E+09 | 0.315936E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.384208E+09 | 0.222211E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.418185E+09 | 0.144922E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.462255E+09 | 0.112026E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.564492E+09 | 98401605.42 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.504202E+09 | 0.186895E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.642510E+09 | 0.370994E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.594837E+09 | 0.451168E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.564987E+09 | 0.551376E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.613659E+10 | 0.395541E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.384208E+09 | 98401605.42 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.642510E+09 | 0.618981E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.538444E+09 | 0.618981E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.496649E+09 | 0.491838E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.533079E+09 | 0.390662E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.432738E+09 | 0.315936E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.384208E+09 | 0.222211E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.418185E+09 | 0.144922E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.462255E+09 | 0.112026E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.564492E+09 | 98401605.42 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.504202E+09 | 0.186895E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.642510E+09 | 0.370994E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.594837E+09 | 0.451168E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.564987E+09 | 0.551376E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.613659E+10 | 0.395541E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.384208E+09 | 98401605.42 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.642510E+09 | 0.618981E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.265667E+09 | 0.305486E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.245207E+09 | 0.242499E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.263627E+09 | 0.192581E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.214142E+09 | 0.155772E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.190168E+09 | 0.109566E+09 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.206880E+09 | 71569489.31 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.228722E+09 | 55305957.19 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.279323E+09 | 48637914.94 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.249346E+09 | 92172893.02 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.317436E+09 | 0.182830E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.293596E+09 | 0.222502E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.278899E+09 | 0.271842E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.303301E+10 | 0.195076E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.190168E+09 | 48637914.94 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.317436E+09 | 0.305486E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.540181E+09 | 0.609443E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.497791E+09 | 0.485392E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.534018E+09 | 0.386919E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.433045E+09 | 0.314388E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.384177E+09 | 0.222217E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.417750E+09 | 0.146385E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.461557E+09 | 0.114157E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.563898E+09 | 0.100575E+09 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.503989E+09 | 0.187690E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.642795E+09 | 0.369095E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.596052E+09 | 0.446445E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.566874E+09 | 0.542372E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.614213E+10 | 0.392508E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.384177E+09 | 0.100575E+09 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.642795E+09 | 0.609443E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.540181E+09 | 0.609443E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.497791E+09 | 0.485392E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.534018E+09 | 0.386919E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.433045E+09 | 0.314388E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.384177E+09 | 0.222217E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.417750E+09 | 0.146385E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.461557E+09 | 0.114157E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.563898E+09 | 0.100575E+09 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.503989E+09 | 0.187690E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.642795E+09 | 0.369095E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.596052E+09 | 0.446445E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.566874E+09 | 0.542372E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.614213E+10 | 0.392508E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.384177E+09 | 0.100575E+09 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.642795E+09 | 0.609443E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.266503E+09 | 0.300814E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.245757E+09 | 0.239341E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.264079E+09 | 0.190745E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.214288E+09 | 0.155012E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.190153E+09 | 0.109568E+09 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.206672E+09 | 72287882.96 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.228388E+09 | 56352200.47 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.279040E+09 | 49705212.83 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.249244E+09 | 92562935.71 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.317573E+09 | 0.181898E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.294184E+09 | 0.220183E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.279814E+09 | 0.267428E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.303570E+10 | 0.193590E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.190153E+09 | 49705212.83 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.317573E+09 | 0.300814E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.542215E+09 | 0.602448E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.499394E+09 | 0.479586E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.535946E+09 | 0.382282E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.434285E+09 | 0.311227E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.385120E+09 | 0.219894E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.418449E+09 | 0.144599E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.462149E+09 | 0.112612E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.564468E+09 | 98987782.20 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.504613E+09 | 0.185838E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.643859E+09 | 0.365712E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.597945E+09 | 0.441603E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.569328E+09 | 0.534539E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.615777E+10 | 0.387933E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.385120E+09 | 98987782.20 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.643859E+09 | 0.602448E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.542215E+09 | 0.602448E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.499394E+09 | 0.479586E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.535946E+09 | 0.382282E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.434285E+09 | 0.311227E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.385120E+09 | 0.219894E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.418449E+09 | 0.144599E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.462149E+09 | 0.112612E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.564468E+09 | 98987782.20 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.504613E+09 | 0.185838E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.643859E+09 | 0.365712E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.597945E+09 | 0.441603E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.569328E+09 | 0.534539E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.615777E+10 | 0.387933E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.385120E+09 | 98987782.20 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.643859E+09 | 0.602448E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.267482E+09 | 0.297397E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.246529E+09 | 0.236505E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.265011E+09 | 0.188475E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.214881E+09 | 0.153463E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.190603E+09 | 0.108429E+09 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207004E+09 | 71411160.34 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.228672E+09 | 55595271.10 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.279310E+09 | 48925819.95 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.249542E+09 | 91655520.26 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.318084E+09 | 0.180239E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.295099E+09 | 0.217808E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.281005E+09 | 0.263591E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.304322E+10 | 0.191350E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.190603E+09 | 48925819.95 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.318084E+09 | 0.297397E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.552038E+09 | 0.576933E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.507218E+09 | 0.458099E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.544716E+09 | 0.365461E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.440120E+09 | 0.297858E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.388384E+09 | 0.208629E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.419515E+09 | 0.134844E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.463002E+09 | 0.104288E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.565254E+09 | 90525420.36 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.506554E+09 | 0.176594E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.649280E+09 | 0.352132E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.605947E+09 | 0.425271E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.579543E+09 | 0.509439E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.622157E+10 | 0.370007E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.388384E+09 | 90525420.36 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.649280E+09 | 0.576933E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.552038E+09 | 0.576933E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.507218E+09 | 0.458099E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.544716E+09 | 0.365461E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.440120E+09 | 0.297858E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.388384E+09 | 0.208629E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.419515E+09 | 0.134844E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.463002E+09 | 0.104288E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.565254E+09 | 90525420.36 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.506554E+09 | 0.176594E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.649280E+09 | 0.352132E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.605947E+09 | 0.425271E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.579543E+09 | 0.509439E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.622157E+10 | 0.370007E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.388384E+09 | 90525420.36 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.649280E+09 | 0.576933E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.552038E+09 | 0.576933E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.507218E+09 | 0.458099E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.544716E+09 | 0.365461E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.440120E+09 | 0.297858E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.388384E+09 | 0.208629E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.419515E+09 | 0.134844E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.463002E+09 | 0.104288E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.565254E+09 | 90525420.36 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.506554E+09 | 0.176594E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.649280E+09 | 0.352132E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.605947E+09 | 0.425271E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.579543E+09 | 0.509439E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.622157E+10 | 0.370007E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.388384E+09 | 90525420.36 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.649280E+09 | 0.576933E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.552038E+09 | 0.576933E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.507218E+09 | 0.458099E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.544716E+09 | 0.365461E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.440120E+09 | 0.297858E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.388384E+09 | 0.208629E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.419515E+09 | 0.134844E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.463002E+09 | 0.104288E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.565254E+09 | 90525420.36 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.506554E+09 | 0.176594E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.649280E+09 | 0.352132E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.605947E+09 | 0.425271E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.579543E+09 | 0.509439E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.622157E+10 | 0.370007E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.388384E+09 | 90525420.36 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.649280E+09 | 0.576933E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.272094E+09 | 0.284965E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.250196E+09 | 0.226041E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.269130E+09 | 0.180259E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.217585E+09 | 0.146911E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.192064E+09 | 0.102873E+09 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207426E+09 | 66582482.24 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.229002E+09 | 51483176.27 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.279600E+09 | 44737252.02 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.250371E+09 | 87099461.74 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.320585E+09 | 0.173612E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.298865E+09 | 0.209837E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.285829E+09 | 0.251336E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.307275E+10 | 0.182574E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.192064E+09 | 44737252.02 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.320585E+09 | 0.284965E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.272094E+09 | 0.284965E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.250196E+09 | 0.226041E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.269130E+09 | 0.180259E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.217585E+09 | 0.146911E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.192064E+09 | 0.102873E+09 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207426E+09 | 66582482.24 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.229002E+09 | 51483176.27 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.279600E+09 | 44737252.02 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.250371E+09 | 87099461.74 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.320585E+09 | 0.173612E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.298865E+09 | 0.209837E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.285829E+09 | 0.251336E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.307275E+10 | 0.182574E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.192064E+09 | 44737252.02 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.320585E+09 | 0.284965E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.549273E+09 | 0.579812E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.505199E+09 | 0.459684E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.543440E+09 | 0.364524E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.439839E+09 | 0.296384E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.389237E+09 | 0.206247E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.421780E+09 | 0.131773E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.465618E+09 | 0.100955E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.567686E+09 | 86792913.52 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507312E+09 | 0.173654E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.648396E+09 | 0.350766E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.604680E+09 | 0.424949E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.577436E+09 | 0.510107E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.621990E+10 | 0.368565E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.389237E+09 | 86792913.52 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.648396E+09 | 0.579812E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.549273E+09 | 0.579812E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.505199E+09 | 0.459684E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.543440E+09 | 0.364524E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.439839E+09 | 0.296384E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.389237E+09 | 0.206247E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.421780E+09 | 0.131773E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.465618E+09 | 0.100955E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.567686E+09 | 86792913.52 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507312E+09 | 0.173654E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.648396E+09 | 0.350766E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.604680E+09 | 0.424949E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.577436E+09 | 0.510107E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.621990E+10 | 0.368565E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.389237E+09 | 86792913.52 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.648396E+09 | 0.579812E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.270841E+09 | 0.286299E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.249287E+09 | 0.226764E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.268574E+09 | 0.179776E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.217473E+09 | 0.146171E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.192473E+09 | 0.101699E+09 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.208488E+09 | 65082016.84 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.230233E+09 | 49852026.30 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.280748E+09 | 42919549.43 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.250740E+09 | 85660974.94 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.320207E+09 | 0.172918E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.298312E+09 | 0.209646E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.284892E+09 | 0.251607E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.307227E+10 | 0.181839E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.192473E+09 | 42919549.43 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.320207E+09 | 0.286299E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.549889E+09 | 0.577888E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.505832E+09 | 0.457701E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.544500E+09 | 0.362198E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.440659E+09 | 0.294632E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.389892E+09 | 0.205029E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.422310E+09 | 0.130966E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.466137E+09 | 0.100192E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.568173E+09 | 86055043.26 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507707E+09 | 0.172818E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.648964E+09 | 0.349256E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.605475E+09 | 0.423153E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.578344E+09 | 0.507480E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.622788E+10 | 0.366737E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.389892E+09 | 86055043.26 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.648964E+09 | 0.577888E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.549889E+09 | 0.577888E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.505832E+09 | 0.457701E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.544500E+09 | 0.362198E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.440659E+09 | 0.294632E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.389892E+09 | 0.205029E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.422310E+09 | 0.130966E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.466137E+09 | 0.100192E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.568173E+09 | 86055043.26 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507707E+09 | 0.172818E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.648964E+09 | 0.349256E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.605475E+09 | 0.423153E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.578344E+09 | 0.507480E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.622788E+10 | 0.366737E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.389892E+09 | 86055043.26 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.648964E+09 | 0.577888E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.271137E+09 | 0.285359E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.249591E+09 | 0.225795E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.269086E+09 | 0.178637E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.217868E+09 | 0.145313E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.192786E+09 | 0.101101E+09 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.208740E+09 | 64686010.41 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.230480E+09 | 49477951.23 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.280980E+09 | 42557629.77 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.250929E+09 | 85250900.56 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.320480E+09 | 0.172177E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.298697E+09 | 0.208765E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.285332E+09 | 0.250321E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.307611E+10 | 0.180944E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.192786E+09 | 42557629.77 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.320480E+09 | 0.285359E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.551744E+09 | 0.570650E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.507596E+09 | 0.451040E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.547071E+09 | 0.355495E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.442579E+09 | 0.289662E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.390989E+09 | 0.202399E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.422491E+09 | 0.130353E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.465996E+09 | 0.100116E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.567904E+09 | 86282001.11 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507808E+09 | 0.172250E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.649926E+09 | 0.346017E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.607231E+09 | 0.418622E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.580599E+09 | 0.500116E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.624193E+10 | 0.362300E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.390989E+09 | 86282001.11 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.649926E+09 | 0.570650E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.551744E+09 | 0.570650E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.507596E+09 | 0.451040E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.547071E+09 | 0.355495E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.442579E+09 | 0.289662E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.390989E+09 | 0.202399E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.422491E+09 | 0.130353E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.465996E+09 | 0.100116E+09 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.567904E+09 | 86282001.11 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.507808E+09 | 0.172250E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.649926E+09 | 0.346017E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.607231E+09 | 0.418622E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.580599E+09 | 0.500116E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.624193E+10 | 0.362300E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.390989E+09 | 86282001.11 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.649926E+09 | 0.570650E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.272029E+09 | 0.281821E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.250441E+09 | 0.222541E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.270327E+09 | 0.175356E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.218789E+09 | 0.142877E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.193311E+09 | 99810398.78 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.208827E+09 | 64385127.36 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.230413E+09 | 49442111.25 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.280852E+09 | 42669035.10 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.250977E+09 | 84972599.65 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.320945E+09 | 0.170590E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.299545E+09 | 0.206542E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.286423E+09 | 0.246714E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.308288E+10 | 0.178772E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.193311E+09 | 42669035.10 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.320945E+09 | 0.281821E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.558747E+09 | 0.535458E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.513514E+09 | 0.419666E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.554747E+09 | 0.324887E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.448152E+09 | 0.264804E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.393068E+09 | 0.187643E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.419665E+09 | 0.125372E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.461321E+09 | 98066294.55 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.562622E+09 | 86138365.87 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.505571E+09 | 0.168038E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.651575E+09 | 0.330282E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.612115E+09 | 0.397750E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.587751E+09 | 0.468312E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.626885E+10 | 0.340642E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.393068E+09 | 86138365.87 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.651575E+09 | 0.535458E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484604E+09 | 0.337864E+09 | 0.146740E+09 | 0.558747E+09 | 0.535458E+09 |
February | 0.408527E+09 | 0.273847E+09 | 0.134680E+09 | 0.513514E+09 | 0.419666E+09 |
March | 0.406769E+09 | 0.211984E+09 | 0.194785E+09 | 0.554747E+09 | 0.324887E+09 |
April | 0.294815E+09 | 95968666.58 | 0.198847E+09 | 0.448152E+09 | 0.264804E+09 |
May | 0.246139E+09 | 28607980.69 | 0.217531E+09 | 0.393068E+09 | 0.187643E+09 |
June | 0.220240E+09 | 12255474.73 | 0.207984E+09 | 0.419665E+09 | 0.125372E+09 |
July | 0.230080E+09 | 17156079.94 | 0.212924E+09 | 0.461321E+09 | 98066294.55 |
August | 0.274699E+09 | 51314777.07 | 0.223384E+09 | 0.562622E+09 | 86138365.87 |
September | 0.292356E+09 | 0.108741E+09 | 0.183615E+09 | 0.505571E+09 | 0.168038E+09 |
October | 0.437961E+09 | 0.283712E+09 | 0.154249E+09 | 0.651575E+09 | 0.330282E+09 |
November | 0.455968E+09 | 0.302573E+09 | 0.153395E+09 | 0.612115E+09 | 0.397750E+09 |
December | 0.477685E+09 | 0.336055E+09 | 0.141630E+09 | 0.587751E+09 | 0.468312E+09 |
Annual Sum or Average | 0.422984E+10 | 0.206008E+10 | 0.216976E+10 | 0.626885E+10 | 0.340642E+10 |
Minimum of Months | 0.220240E+09 | 12255474.73 | 0.134680E+09 | 0.393068E+09 | 86138365.87 |
Maximum of Months | 0.484604E+09 | 0.337864E+09 | 0.223384E+09 | 0.651575E+09 | 0.535458E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.275373E+09 | 0.264570E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.253275E+09 | 0.207166E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.274012E+09 | 0.160312E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.221466E+09 | 0.130649E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.194315E+09 | 92536671.01 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207490E+09 | 61927629.90 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.228193E+09 | 48430270.03 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.278342E+09 | 42593574.24 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.249917E+09 | 82889995.67 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.321749E+09 | 0.162835E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.301900E+09 | 0.196263E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.289853E+09 | 0.231064E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.309588E+10 | 0.168124E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.194315E+09 | 42593574.24 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.321749E+09 | 0.264570E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1018.63 | 1135.65 | 901.72 | 628.68 | 273.05 | 0.00 | 0.00 |
February | 1039.93 | 989.26 | 841.61 | 564.15 | 277.46 | 0.00 | 0.00 |
March | 1012.08 | 698.81 | 756.89 | 394.45 | 362.44 | 0.00 | 0.00 |
April | 849.20 | 573.18 | 566.86 | 184.53 | 382.34 | 0.00 | 0.00 |
May | 727.04 | 380.03 | 458.00 | 53.23 | 404.77 | 0.00 | 0.00 |
June | 814.98 | 243.41 | 423.47 | 23.56 | 399.91 | 0.00 | 0.00 |
July | 875.98 | 174.30 | 428.12 | 31.92 | 396.20 | 0.00 | 0.00 |
August | 1061.38 | 149.95 | 511.15 | 95.48 | 415.66 | 0.00 | 0.00 |
September | 977.64 | 328.60 | 562.13 | 209.08 | 353.05 | 0.00 | 0.00 |
October | 1208.40 | 665.18 | 814.93 | 527.92 | 287.02 | 0.00 | 0.00 |
November | 1158.06 | 848.32 | 876.72 | 581.78 | 294.94 | 0.00 | 0.00 |
December | 1069.98 | 1002.23 | 888.85 | 625.31 | 263.54 | 0.00 | 0.00 |
Annual Sum or Average | 984.36 | 596.97 | 668.47 | 325.57 | 342.90 | 0.00 | 0.00 |
Minimum of Months | 727.04 | 149.95 | 423.47 | 23.56 | 263.54 | 0.00 | 0.00 |
Maximum of Months | 1208.40 | 1135.65 | 901.72 | 628.68 | 415.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 499.22 | 600.11 | 450.86 | 314.34 | 136.52 | 0.00 | 0.00 |
February | 510.94 | 521.54 | 420.81 | 282.08 | 138.73 | 0.00 | 0.00 |
March | 496.90 | 366.49 | 378.45 | 197.22 | 181.22 | 0.00 | 0.00 |
April | 418.51 | 299.32 | 283.43 | 92.26 | 191.17 | 0.00 | 0.00 |
May | 361.04 | 196.72 | 229.00 | 26.62 | 202.38 | 0.00 | 0.00 |
June | 408.28 | 124.46 | 211.74 | 11.78 | 199.95 | 0.00 | 0.00 |
July | 440.04 | 88.84 | 214.06 | 15.96 | 198.10 | 0.00 | 0.00 |
August | 533.28 | 75.42 | 255.57 | 47.74 | 207.83 | 0.00 | 0.00 |
September | 488.58 | 166.45 | 281.07 | 104.54 | 176.52 | 0.00 | 0.00 |
October | 600.15 | 341.56 | 407.47 | 263.96 | 143.51 | 0.00 | 0.00 |
November | 571.50 | 440.26 | 438.36 | 290.89 | 147.47 | 0.00 | 0.00 |
December | 523.92 | 533.46 | 444.43 | 312.66 | 131.77 | 0.00 | 0.00 |
Annual Sum or Average | 487.68 | 311.78 | 334.23 | 162.78 | 171.45 | 0.00 | 0.00 |
Minimum of Months | 361.04 | 75.42 | 211.74 | 11.78 | 131.77 | 0.00 | 0.00 |
Maximum of Months | 600.15 | 600.11 | 450.86 | 314.34 | 207.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 501.25 | 576.26 | 450.38 | 314.00 | 136.38 | 0.00 | 0.00 |
February | 511.95 | 506.85 | 420.35 | 281.77 | 138.58 | 0.00 | 0.00 |
March | 496.48 | 363.61 | 378.04 | 197.01 | 181.03 | 0.00 | 0.00 |
April | 416.52 | 303.88 | 283.13 | 92.16 | 190.96 | 0.00 | 0.00 |
May | 357.89 | 206.84 | 228.75 | 26.59 | 202.17 | 0.00 | 0.00 |
June | 402.49 | 139.43 | 211.51 | 11.77 | 199.74 | 0.00 | 0.00 |
July | 430.57 | 104.30 | 213.83 | 15.94 | 197.88 | 0.00 | 0.00 |
August | 525.80 | 91.64 | 255.30 | 47.69 | 207.61 | 0.00 | 0.00 |
September | 485.24 | 179.77 | 280.76 | 104.43 | 176.33 | 0.00 | 0.00 |
October | 598.29 | 345.29 | 407.03 | 263.67 | 143.35 | 0.00 | 0.00 |
November | 572.25 | 433.96 | 437.89 | 290.58 | 147.31 | 0.00 | 0.00 |
December | 526.01 | 513.21 | 443.95 | 312.32 | 131.63 | 0.00 | 0.00 |
Annual Sum or Average | 485.36 | 312.71 | 333.87 | 162.61 | 171.27 | 0.00 | 0.00 |
Minimum of Months | 357.89 | 91.64 | 211.51 | 11.77 | 131.63 | 0.00 | 0.00 |
Maximum of Months | 598.29 | 576.26 | 450.38 | 314.00 | 207.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 502.86 | 567.39 | 450.38 | 314.00 | 136.38 | 0.00 | 0.00 |
February | 513.12 | 500.22 | 420.35 | 281.77 | 138.58 | 0.00 | 0.00 |
March | 497.35 | 360.13 | 378.04 | 197.01 | 181.03 | 0.00 | 0.00 |
April | 416.81 | 302.39 | 283.13 | 92.16 | 190.96 | 0.00 | 0.00 |
May | 357.87 | 206.84 | 228.75 | 26.59 | 202.17 | 0.00 | 0.00 |
June | 402.07 | 140.84 | 211.51 | 11.77 | 199.74 | 0.00 | 0.00 |
July | 429.92 | 106.28 | 213.83 | 15.94 | 197.88 | 0.00 | 0.00 |
August | 525.25 | 93.66 | 255.30 | 47.69 | 207.61 | 0.00 | 0.00 |
September | 485.04 | 180.53 | 280.76 | 104.43 | 176.33 | 0.00 | 0.00 |
October | 598.55 | 343.52 | 407.03 | 263.67 | 143.35 | 0.00 | 0.00 |
November | 573.41 | 429.43 | 437.89 | 290.58 | 147.31 | 0.00 | 0.00 |
December | 527.76 | 504.84 | 443.95 | 312.32 | 131.63 | 0.00 | 0.00 |
Annual Sum or Average | 485.79 | 310.31 | 333.87 | 162.61 | 171.27 | 0.00 | 0.00 |
Minimum of Months | 357.87 | 93.66 | 211.51 | 11.77 | 131.63 | 0.00 | 0.00 |
Maximum of Months | 598.55 | 567.39 | 450.38 | 314.00 | 207.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 504.75 | 560.89 | 450.38 | 314.00 | 136.38 | 0.00 | 0.00 |
February | 514.76 | 494.24 | 420.35 | 281.77 | 138.58 | 0.00 | 0.00 |
March | 499.14 | 355.82 | 378.04 | 197.01 | 181.03 | 0.00 | 0.00 |
April | 418.00 | 299.35 | 283.13 | 92.16 | 190.96 | 0.00 | 0.00 |
May | 358.74 | 204.68 | 228.75 | 26.59 | 202.17 | 0.00 | 0.00 |
June | 402.74 | 139.12 | 211.51 | 11.77 | 199.74 | 0.00 | 0.00 |
July | 430.47 | 104.85 | 213.83 | 15.94 | 197.88 | 0.00 | 0.00 |
August | 525.78 | 92.18 | 255.30 | 47.69 | 207.61 | 0.00 | 0.00 |
September | 485.64 | 178.75 | 280.76 | 104.43 | 176.33 | 0.00 | 0.00 |
October | 599.54 | 340.38 | 407.03 | 263.67 | 143.35 | 0.00 | 0.00 |
November | 575.23 | 424.77 | 437.89 | 290.58 | 147.31 | 0.00 | 0.00 |
December | 530.04 | 497.56 | 443.95 | 312.32 | 131.63 | 0.00 | 0.00 |
Annual Sum or Average | 487.02 | 306.70 | 333.87 | 162.61 | 171.27 | 0.00 | 0.00 |
Minimum of Months | 358.74 | 92.18 | 211.51 | 11.77 | 131.63 | 0.00 | 0.00 |
Maximum of Months | 599.54 | 560.89 | 450.38 | 314.00 | 207.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1027.61 | 1074.40 | 900.75 | 628.00 | 272.75 | 0.00 | 0.00 |
February | 1045.50 | 944.31 | 840.70 | 563.55 | 277.16 | 0.00 | 0.00 |
March | 1014.46 | 680.39 | 756.08 | 394.02 | 362.05 | 0.00 | 0.00 |
April | 847.09 | 573.01 | 566.25 | 184.33 | 381.92 | 0.00 | 0.00 |
May | 723.44 | 388.39 | 457.51 | 53.17 | 404.33 | 0.00 | 0.00 |
June | 807.45 | 259.47 | 423.01 | 23.54 | 399.47 | 0.00 | 0.00 |
July | 862.46 | 194.19 | 427.66 | 31.89 | 395.77 | 0.00 | 0.00 |
August | 1052.95 | 168.60 | 510.59 | 95.38 | 415.21 | 0.00 | 0.00 |
September | 974.91 | 339.73 | 561.53 | 208.86 | 352.67 | 0.00 | 0.00 |
October | 1209.04 | 655.52 | 814.06 | 527.35 | 286.71 | 0.00 | 0.00 |
November | 1165.71 | 818.19 | 875.78 | 581.15 | 294.63 | 0.00 | 0.00 |
December | 1078.94 | 948.49 | 887.89 | 624.64 | 263.25 | 0.00 | 0.00 |
Annual Sum or Average | 984.01 | 585.10 | 667.75 | 325.22 | 342.53 | 0.00 | 0.00 |
Minimum of Months | 723.44 | 168.60 | 423.01 | 23.54 | 263.25 | 0.00 | 0.00 |
Maximum of Months | 1209.04 | 1074.40 | 900.75 | 628.00 | 415.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 511.27 | 539.85 | 450.38 | 314.00 | 136.38 | 0.00 | 0.00 |
February | 520.70 | 473.76 | 420.35 | 281.77 | 138.58 | 0.00 | 0.00 |
March | 506.07 | 339.32 | 378.04 | 197.01 | 181.03 | 0.00 | 0.00 |
April | 423.28 | 285.08 | 283.13 | 92.16 | 190.96 | 0.00 | 0.00 |
May | 362.51 | 191.98 | 228.75 | 26.59 | 202.17 | 0.00 | 0.00 |
June | 405.88 | 126.79 | 211.51 | 11.77 | 199.74 | 0.00 | 0.00 |
July | 433.64 | 94.00 | 213.83 | 15.94 | 197.88 | 0.00 | 0.00 |
August | 528.72 | 80.83 | 255.30 | 47.69 | 207.61 | 0.00 | 0.00 |
September | 488.18 | 167.04 | 280.76 | 104.43 | 176.33 | 0.00 | 0.00 |
October | 603.72 | 326.48 | 407.03 | 263.67 | 143.35 | 0.00 | 0.00 |
November | 581.66 | 408.77 | 437.89 | 290.58 | 147.31 | 0.00 | 0.00 |
December | 537.55 | 474.84 | 443.95 | 312.32 | 131.63 | 0.00 | 0.00 |
Annual Sum or Average | 491.88 | 291.40 | 333.87 | 162.61 | 171.27 | 0.00 | 0.00 |
Minimum of Months | 362.51 | 80.83 | 211.51 | 11.77 | 131.63 | 0.00 | 0.00 |
Maximum of Months | 603.72 | 539.85 | 450.38 | 314.00 | 207.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 511.84 | 538.06 | 450.38 | 314.00 | 136.38 | 0.00 | 0.00 |
February | 521.35 | 471.73 | 420.35 | 281.77 | 138.58 | 0.00 | 0.00 |
March | 507.05 | 337.15 | 378.04 | 197.01 | 181.03 | 0.00 | 0.00 |
April | 424.07 | 283.40 | 283.13 | 92.16 | 190.96 | 0.00 | 0.00 |
May | 363.12 | 190.85 | 228.75 | 26.59 | 202.17 | 0.00 | 0.00 |
June | 406.39 | 126.01 | 211.51 | 11.77 | 199.74 | 0.00 | 0.00 |
July | 434.12 | 93.29 | 213.83 | 15.94 | 197.88 | 0.00 | 0.00 |
August | 529.17 | 80.15 | 255.30 | 47.69 | 207.61 | 0.00 | 0.00 |
September | 488.56 | 166.24 | 280.76 | 104.43 | 176.33 | 0.00 | 0.00 |
October | 604.24 | 325.08 | 407.03 | 263.67 | 143.35 | 0.00 | 0.00 |
November | 582.43 | 407.05 | 437.89 | 290.58 | 147.31 | 0.00 | 0.00 |
December | 538.39 | 472.40 | 443.95 | 312.32 | 131.63 | 0.00 | 0.00 |
Annual Sum or Average | 492.51 | 289.96 | 333.87 | 162.61 | 171.27 | 0.00 | 0.00 |
Minimum of Months | 363.12 | 80.15 | 211.51 | 11.77 | 131.63 | 0.00 | 0.00 |
Maximum of Months | 604.24 | 538.06 | 450.38 | 314.00 | 207.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 513.56 | 531.33 | 450.38 | 314.00 | 136.38 | 0.00 | 0.00 |
February | 523.16 | 464.87 | 420.35 | 281.77 | 138.58 | 0.00 | 0.00 |
March | 509.43 | 330.92 | 378.04 | 197.01 | 181.03 | 0.00 | 0.00 |
April | 425.91 | 278.63 | 283.13 | 92.16 | 190.96 | 0.00 | 0.00 |
May | 364.13 | 188.40 | 228.75 | 26.59 | 202.17 | 0.00 | 0.00 |
June | 406.56 | 125.42 | 211.51 | 11.77 | 199.74 | 0.00 | 0.00 |
July | 433.99 | 93.22 | 213.83 | 15.94 | 197.88 | 0.00 | 0.00 |
August | 528.92 | 80.36 | 255.30 | 47.69 | 207.61 | 0.00 | 0.00 |
September | 488.65 | 165.69 | 280.76 | 104.43 | 176.33 | 0.00 | 0.00 |
October | 605.14 | 322.07 | 407.03 | 263.67 | 143.35 | 0.00 | 0.00 |
November | 584.11 | 402.70 | 437.89 | 290.58 | 147.31 | 0.00 | 0.00 |
December | 540.48 | 465.56 | 443.95 | 312.32 | 131.63 | 0.00 | 0.00 |
Annual Sum or Average | 493.62 | 286.46 | 333.87 | 162.61 | 171.27 | 0.00 | 0.00 |
Minimum of Months | 364.13 | 80.36 | 211.51 | 11.77 | 131.63 | 0.00 | 0.00 |
Maximum of Months | 605.14 | 531.33 | 450.38 | 314.00 | 207.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 520.04 | 498.61 | 450.38 | 314.00 | 136.38 | 0.00 | 0.00 |
February | 529.23 | 432.58 | 420.35 | 281.77 | 138.58 | 0.00 | 0.00 |
March | 516.54 | 302.45 | 378.04 | 197.01 | 181.03 | 0.00 | 0.00 |
April | 431.24 | 254.73 | 283.13 | 92.16 | 190.96 | 0.00 | 0.00 |
May | 366.06 | 174.66 | 228.75 | 26.59 | 202.17 | 0.00 | 0.00 |
June | 403.87 | 120.63 | 211.51 | 11.77 | 199.74 | 0.00 | 0.00 |
July | 429.67 | 91.31 | 213.83 | 15.94 | 197.88 | 0.00 | 0.00 |
August | 524.04 | 80.22 | 255.30 | 47.69 | 207.61 | 0.00 | 0.00 |
September | 486.52 | 161.64 | 280.76 | 104.43 | 176.33 | 0.00 | 0.00 |
October | 606.67 | 307.42 | 407.03 | 263.67 | 143.35 | 0.00 | 0.00 |
November | 588.78 | 382.62 | 437.89 | 290.58 | 147.31 | 0.00 | 0.00 |
December | 547.10 | 435.96 | 443.95 | 312.32 | 131.63 | 0.00 | 0.00 |
Annual Sum or Average | 495.74 | 269.35 | 333.87 | 162.61 | 171.27 | 0.00 | 0.00 |
Minimum of Months | 366.06 | 80.22 | 211.51 | 11.77 | 131.63 | 0.00 | 0.00 |
Maximum of Months | 606.67 | 498.61 | 450.38 | 314.00 | 207.61 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.272830E+10 | 0.304173E+10 | 0.241518E+10 | 0.168385E+10 | 0.731324E+09 | 0.00 | 0.00 |
February | 0.251581E+10 | 0.239323E+10 | 0.203602E+10 | 0.136480E+10 | 0.671221E+09 | 0.00 | 0.00 |
March | 0.271075E+10 | 0.187170E+10 | 0.202726E+10 | 0.105649E+10 | 0.970772E+09 | 0.00 | 0.00 |
April | 0.220112E+10 | 0.148567E+10 | 0.146931E+10 | 0.478291E+09 | 0.991015E+09 | 0.00 | 0.00 |
May | 0.194731E+10 | 0.101788E+10 | 0.122671E+10 | 0.142577E+09 | 0.108413E+10 | 0.00 | 0.00 |
June | 0.211242E+10 | 0.630920E+09 | 0.109764E+10 | 61079078.75 | 0.103656E+10 | 0.00 | 0.00 |
July | 0.234623E+10 | 0.466855E+09 | 0.114668E+10 | 85502812.50 | 0.106117E+10 | 0.00 | 0.00 |
August | 0.284279E+10 | 0.401622E+09 | 0.136905E+10 | 0.255744E+09 | 0.111331E+10 | 0.00 | 0.00 |
September | 0.253404E+10 | 0.851730E+09 | 0.145705E+10 | 0.541947E+09 | 0.915104E+09 | 0.00 | 0.00 |
October | 0.323659E+10 | 0.178161E+10 | 0.218272E+10 | 0.141397E+10 | 0.768751E+09 | 0.00 | 0.00 |
November | 0.300168E+10 | 0.219885E+10 | 0.227246E+10 | 0.150797E+10 | 0.764494E+09 | 0.00 | 0.00 |
December | 0.286584E+10 | 0.268438E+10 | 0.238070E+10 | 0.167484E+10 | 0.705859E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.310429E+11 | 0.188262E+11 | 0.210808E+11 | 0.102671E+11 | 0.108137E+11 | 0.00 | 0.00 |
Minimum of Months | 0.194731E+10 | 0.401622E+09 | 0.109764E+10 | 61079078.75 | 0.671221E+09 | 0.00 | 0.00 |
Maximum of Months | 0.323659E+10 | 0.304173E+10 | 0.241518E+10 | 0.168385E+10 | 0.111331E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133711E+10 | 0.160732E+10 | 0.120759E+10 | 0.841927E+09 | 0.365662E+09 | 0.00 | 0.00 |
February | 0.123606E+10 | 0.126171E+10 | 0.101801E+10 | 0.682402E+09 | 0.335611E+09 | 0.00 | 0.00 |
March | 0.133091E+10 | 0.981612E+09 | 0.101363E+10 | 0.528244E+09 | 0.485386E+09 | 0.00 | 0.00 |
April | 0.108479E+10 | 0.775849E+09 | 0.734653E+09 | 0.239145E+09 | 0.495508E+09 | 0.00 | 0.00 |
May | 0.966997E+09 | 0.526901E+09 | 0.613355E+09 | 71288511.64 | 0.542067E+09 | 0.00 | 0.00 |
June | 0.105826E+10 | 0.322601E+09 | 0.548818E+09 | 30539539.38 | 0.518278E+09 | 0.00 | 0.00 |
July | 0.117861E+10 | 0.237937E+09 | 0.573339E+09 | 42751406.25 | 0.530587E+09 | 0.00 | 0.00 |
August | 0.142835E+10 | 0.202002E+09 | 0.684526E+09 | 0.127872E+09 | 0.556654E+09 | 0.00 | 0.00 |
September | 0.126640E+10 | 0.431451E+09 | 0.728526E+09 | 0.270974E+09 | 0.457552E+09 | 0.00 | 0.00 |
October | 0.160744E+10 | 0.914830E+09 | 0.109136E+10 | 0.706984E+09 | 0.384376E+09 | 0.00 | 0.00 |
November | 0.148132E+10 | 0.114115E+10 | 0.113623E+10 | 0.753984E+09 | 0.382247E+09 | 0.00 | 0.00 |
December | 0.140327E+10 | 0.142882E+10 | 0.119035E+10 | 0.837419E+09 | 0.352929E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153795E+11 | 0.983219E+10 | 0.105404E+11 | 0.513353E+10 | 0.540686E+10 | 0.00 | 0.00 |
Minimum of Months | 0.966997E+09 | 0.202002E+09 | 0.548818E+09 | 30539539.38 | 0.335611E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160744E+10 | 0.160732E+10 | 0.120759E+10 | 0.841927E+09 | 0.556654E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.134255E+10 | 0.154345E+10 | 0.120629E+10 | 0.841019E+09 | 0.365268E+09 | 0.00 | 0.00 |
February | 0.123850E+10 | 0.122617E+10 | 0.101691E+10 | 0.681665E+09 | 0.335249E+09 | 0.00 | 0.00 |
March | 0.132978E+10 | 0.973904E+09 | 0.101254E+10 | 0.527675E+09 | 0.484862E+09 | 0.00 | 0.00 |
April | 0.107962E+10 | 0.787644E+09 | 0.733860E+09 | 0.238887E+09 | 0.494973E+09 | 0.00 | 0.00 |
May | 0.958585E+09 | 0.553989E+09 | 0.612694E+09 | 71211612.46 | 0.541482E+09 | 0.00 | 0.00 |
June | 0.104325E+10 | 0.361413E+09 | 0.548226E+09 | 30506596.26 | 0.517719E+09 | 0.00 | 0.00 |
July | 0.115323E+10 | 0.279358E+09 | 0.572720E+09 | 42705290.15 | 0.530015E+09 | 0.00 | 0.00 |
August | 0.140831E+10 | 0.245441E+09 | 0.683787E+09 | 0.127734E+09 | 0.556053E+09 | 0.00 | 0.00 |
September | 0.125775E+10 | 0.465964E+09 | 0.727740E+09 | 0.270681E+09 | 0.457058E+09 | 0.00 | 0.00 |
October | 0.160246E+10 | 0.924818E+09 | 0.109018E+10 | 0.706221E+09 | 0.383961E+09 | 0.00 | 0.00 |
November | 0.148327E+10 | 0.112484E+10 | 0.113501E+10 | 0.753171E+09 | 0.381835E+09 | 0.00 | 0.00 |
December | 0.140887E+10 | 0.137459E+10 | 0.118906E+10 | 0.836516E+09 | 0.352549E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153062E+11 | 0.986158E+10 | 0.105290E+11 | 0.512799E+10 | 0.540102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.958585E+09 | 0.245441E+09 | 0.548226E+09 | 30506596.26 | 0.335249E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160246E+10 | 0.154345E+10 | 0.120629E+10 | 0.841019E+09 | 0.556053E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.134687E+10 | 0.151970E+10 | 0.120629E+10 | 0.841019E+09 | 0.365268E+09 | 0.00 | 0.00 |
February | 0.124134E+10 | 0.121013E+10 | 0.101691E+10 | 0.681665E+09 | 0.335249E+09 | 0.00 | 0.00 |
March | 0.133211E+10 | 0.964584E+09 | 0.101254E+10 | 0.527675E+09 | 0.484862E+09 | 0.00 | 0.00 |
April | 0.108038E+10 | 0.783788E+09 | 0.733860E+09 | 0.238887E+09 | 0.494973E+09 | 0.00 | 0.00 |
May | 0.958506E+09 | 0.554001E+09 | 0.612694E+09 | 71211612.46 | 0.541482E+09 | 0.00 | 0.00 |
June | 0.104217E+10 | 0.365058E+09 | 0.548226E+09 | 30506596.26 | 0.517719E+09 | 0.00 | 0.00 |
July | 0.115150E+10 | 0.284666E+09 | 0.572720E+09 | 42705290.15 | 0.530015E+09 | 0.00 | 0.00 |
August | 0.140684E+10 | 0.250855E+09 | 0.683787E+09 | 0.127734E+09 | 0.556053E+09 | 0.00 | 0.00 |
September | 0.125722E+10 | 0.467942E+09 | 0.727740E+09 | 0.270681E+09 | 0.457058E+09 | 0.00 | 0.00 |
October | 0.160316E+10 | 0.920088E+09 | 0.109018E+10 | 0.706221E+09 | 0.383961E+09 | 0.00 | 0.00 |
November | 0.148629E+10 | 0.111307E+10 | 0.113501E+10 | 0.753171E+09 | 0.381835E+09 | 0.00 | 0.00 |
December | 0.141356E+10 | 0.135217E+10 | 0.118906E+10 | 0.836516E+09 | 0.352549E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153199E+11 | 0.978605E+10 | 0.105290E+11 | 0.512799E+10 | 0.540102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.958506E+09 | 0.250855E+09 | 0.548226E+09 | 30506596.26 | 0.335249E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160316E+10 | 0.151970E+10 | 0.120629E+10 | 0.841019E+09 | 0.556053E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135191E+10 | 0.150229E+10 | 0.120629E+10 | 0.841019E+09 | 0.365268E+09 | 0.00 | 0.00 |
February | 0.124532E+10 | 0.119568E+10 | 0.101691E+10 | 0.681665E+09 | 0.335249E+09 | 0.00 | 0.00 |
March | 0.133690E+10 | 0.953039E+09 | 0.101254E+10 | 0.527675E+09 | 0.484862E+09 | 0.00 | 0.00 |
April | 0.108345E+10 | 0.775917E+09 | 0.733860E+09 | 0.238887E+09 | 0.494973E+09 | 0.00 | 0.00 |
May | 0.960844E+09 | 0.548217E+09 | 0.612694E+09 | 71211612.46 | 0.541482E+09 | 0.00 | 0.00 |
June | 0.104390E+10 | 0.360609E+09 | 0.548226E+09 | 30506596.26 | 0.517719E+09 | 0.00 | 0.00 |
July | 0.115297E+10 | 0.280819E+09 | 0.572720E+09 | 42705290.15 | 0.530015E+09 | 0.00 | 0.00 |
August | 0.140824E+10 | 0.246901E+09 | 0.683787E+09 | 0.127734E+09 | 0.556053E+09 | 0.00 | 0.00 |
September | 0.125877E+10 | 0.463332E+09 | 0.727740E+09 | 0.270681E+09 | 0.457058E+09 | 0.00 | 0.00 |
October | 0.160580E+10 | 0.911663E+09 | 0.109018E+10 | 0.706221E+09 | 0.383961E+09 | 0.00 | 0.00 |
November | 0.149099E+10 | 0.110101E+10 | 0.113501E+10 | 0.753171E+09 | 0.381835E+09 | 0.00 | 0.00 |
December | 0.141966E+10 | 0.133267E+10 | 0.118906E+10 | 0.836516E+09 | 0.352549E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153588E+11 | 0.967215E+10 | 0.105290E+11 | 0.512799E+10 | 0.540102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.960844E+09 | 0.246901E+09 | 0.548226E+09 | 30506596.26 | 0.335249E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160580E+10 | 0.150229E+10 | 0.120629E+10 | 0.841019E+09 | 0.556053E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.275234E+10 | 0.287766E+10 | 0.241257E+10 | 0.168204E+10 | 0.730535E+09 | 0.00 | 0.00 |
February | 0.252926E+10 | 0.228448E+10 | 0.203383E+10 | 0.136333E+10 | 0.670497E+09 | 0.00 | 0.00 |
March | 0.271712E+10 | 0.182236E+10 | 0.202507E+10 | 0.105535E+10 | 0.969725E+09 | 0.00 | 0.00 |
April | 0.219565E+10 | 0.148525E+10 | 0.146772E+10 | 0.477775E+09 | 0.989946E+09 | 0.00 | 0.00 |
May | 0.193766E+10 | 0.104026E+10 | 0.122539E+10 | 0.142423E+09 | 0.108296E+10 | 0.00 | 0.00 |
June | 0.209291E+10 | 0.672541E+09 | 0.109645E+10 | 61013192.52 | 0.103544E+10 | 0.00 | 0.00 |
July | 0.231001E+10 | 0.520116E+09 | 0.114544E+10 | 85410580.30 | 0.106003E+10 | 0.00 | 0.00 |
August | 0.282022E+10 | 0.451576E+09 | 0.136757E+10 | 0.255468E+09 | 0.111211E+10 | 0.00 | 0.00 |
September | 0.252696E+10 | 0.880576E+09 | 0.145548E+10 | 0.541363E+09 | 0.914117E+09 | 0.00 | 0.00 |
October | 0.323829E+10 | 0.175575E+10 | 0.218037E+10 | 0.141244E+10 | 0.767922E+09 | 0.00 | 0.00 |
November | 0.302152E+10 | 0.212076E+10 | 0.227001E+10 | 0.150634E+10 | 0.763670E+09 | 0.00 | 0.00 |
December | 0.288983E+10 | 0.254043E+10 | 0.237813E+10 | 0.167303E+10 | 0.705097E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.310318E+11 | 0.184518E+11 | 0.210580E+11 | 0.102560E+11 | 0.108020E+11 | 0.00 | 0.00 |
Minimum of Months | 0.193766E+10 | 0.451576E+09 | 0.109645E+10 | 61013192.52 | 0.670497E+09 | 0.00 | 0.00 |
Maximum of Months | 0.323829E+10 | 0.287766E+10 | 0.241257E+10 | 0.168204E+10 | 0.111211E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136939E+10 | 0.144592E+10 | 0.120629E+10 | 0.841019E+09 | 0.365268E+09 | 0.00 | 0.00 |
February | 0.125969E+10 | 0.114613E+10 | 0.101691E+10 | 0.681665E+09 | 0.335249E+09 | 0.00 | 0.00 |
March | 0.135545E+10 | 0.908823E+09 | 0.101254E+10 | 0.527675E+09 | 0.484862E+09 | 0.00 | 0.00 |
April | 0.109715E+10 | 0.738939E+09 | 0.733860E+09 | 0.238887E+09 | 0.494973E+09 | 0.00 | 0.00 |
May | 0.970948E+09 | 0.514193E+09 | 0.612694E+09 | 71211612.46 | 0.541482E+09 | 0.00 | 0.00 |
June | 0.105205E+10 | 0.328629E+09 | 0.548226E+09 | 30506596.26 | 0.517719E+09 | 0.00 | 0.00 |
July | 0.116147E+10 | 0.251761E+09 | 0.572720E+09 | 42705290.15 | 0.530015E+09 | 0.00 | 0.00 |
August | 0.141612E+10 | 0.216505E+09 | 0.683787E+09 | 0.127734E+09 | 0.556053E+09 | 0.00 | 0.00 |
September | 0.126536E+10 | 0.432969E+09 | 0.727740E+09 | 0.270681E+09 | 0.457058E+09 | 0.00 | 0.00 |
October | 0.161700E+10 | 0.874449E+09 | 0.109018E+10 | 0.706221E+09 | 0.383961E+09 | 0.00 | 0.00 |
November | 0.150767E+10 | 0.105954E+10 | 0.113501E+10 | 0.753171E+09 | 0.381835E+09 | 0.00 | 0.00 |
December | 0.143976E+10 | 0.127182E+10 | 0.118906E+10 | 0.836516E+09 | 0.352549E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.155121E+11 | 0.918969E+10 | 0.105290E+11 | 0.512799E+10 | 0.540102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.970948E+09 | 0.216505E+09 | 0.548226E+09 | 30506596.26 | 0.335249E+09 | 0.00 | 0.00 |
Maximum of Months | 0.161700E+10 | 0.144592E+10 | 0.120629E+10 | 0.841019E+09 | 0.556053E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137091E+10 | 0.144113E+10 | 0.120629E+10 | 0.841019E+09 | 0.365268E+09 | 0.00 | 0.00 |
February | 0.126125E+10 | 0.114120E+10 | 0.101691E+10 | 0.681665E+09 | 0.335249E+09 | 0.00 | 0.00 |
March | 0.135809E+10 | 0.903031E+09 | 0.101254E+10 | 0.527675E+09 | 0.484862E+09 | 0.00 | 0.00 |
April | 0.109919E+10 | 0.734577E+09 | 0.733860E+09 | 0.238887E+09 | 0.494973E+09 | 0.00 | 0.00 |
May | 0.972570E+09 | 0.511159E+09 | 0.612694E+09 | 71211612.46 | 0.541482E+09 | 0.00 | 0.00 |
June | 0.105336E+10 | 0.326618E+09 | 0.548226E+09 | 30506596.26 | 0.517719E+09 | 0.00 | 0.00 |
July | 0.116275E+10 | 0.249862E+09 | 0.572720E+09 | 42705290.15 | 0.530015E+09 | 0.00 | 0.00 |
August | 0.141733E+10 | 0.214667E+09 | 0.683787E+09 | 0.127734E+09 | 0.556053E+09 | 0.00 | 0.00 |
September | 0.126634E+10 | 0.430887E+09 | 0.727740E+09 | 0.270681E+09 | 0.457058E+09 | 0.00 | 0.00 |
October | 0.161841E+10 | 0.870688E+09 | 0.109018E+10 | 0.706221E+09 | 0.383961E+09 | 0.00 | 0.00 |
November | 0.150965E+10 | 0.105507E+10 | 0.113501E+10 | 0.753171E+09 | 0.381835E+09 | 0.00 | 0.00 |
December | 0.144202E+10 | 0.126528E+10 | 0.118906E+10 | 0.836516E+09 | 0.352549E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.155319E+11 | 0.914417E+10 | 0.105290E+11 | 0.512799E+10 | 0.540102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.972570E+09 | 0.214667E+09 | 0.548226E+09 | 30506596.26 | 0.335249E+09 | 0.00 | 0.00 |
Maximum of Months | 0.161841E+10 | 0.144113E+10 | 0.120629E+10 | 0.841019E+09 | 0.556053E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137552E+10 | 0.142312E+10 | 0.120629E+10 | 0.841019E+09 | 0.365268E+09 | 0.00 | 0.00 |
February | 0.126563E+10 | 0.112462E+10 | 0.101691E+10 | 0.681665E+09 | 0.335249E+09 | 0.00 | 0.00 |
March | 0.136447E+10 | 0.886347E+09 | 0.101254E+10 | 0.527675E+09 | 0.484862E+09 | 0.00 | 0.00 |
April | 0.110395E+10 | 0.722200E+09 | 0.733860E+09 | 0.238887E+09 | 0.494973E+09 | 0.00 | 0.00 |
May | 0.975289E+09 | 0.504608E+09 | 0.612694E+09 | 71211612.46 | 0.541482E+09 | 0.00 | 0.00 |
June | 0.105381E+10 | 0.325090E+09 | 0.548226E+09 | 30506596.26 | 0.517719E+09 | 0.00 | 0.00 |
July | 0.116240E+10 | 0.249674E+09 | 0.572720E+09 | 42705290.15 | 0.530015E+09 | 0.00 | 0.00 |
August | 0.141666E+10 | 0.215233E+09 | 0.683787E+09 | 0.127734E+09 | 0.556053E+09 | 0.00 | 0.00 |
September | 0.126659E+10 | 0.429472E+09 | 0.727740E+09 | 0.270681E+09 | 0.457058E+09 | 0.00 | 0.00 |
October | 0.162080E+10 | 0.862624E+09 | 0.109018E+10 | 0.706221E+09 | 0.383961E+09 | 0.00 | 0.00 |
November | 0.151401E+10 | 0.104379E+10 | 0.113501E+10 | 0.753171E+09 | 0.381835E+09 | 0.00 | 0.00 |
December | 0.144762E+10 | 0.124695E+10 | 0.118906E+10 | 0.836516E+09 | 0.352549E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.155667E+11 | 0.903372E+10 | 0.105290E+11 | 0.512799E+10 | 0.540102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.975289E+09 | 0.215233E+09 | 0.548226E+09 | 30506596.26 | 0.335249E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162080E+10 | 0.142312E+10 | 0.120629E+10 | 0.841019E+09 | 0.556053E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.139287E+10 | 0.133549E+10 | 0.120629E+10 | 0.841019E+09 | 0.365268E+09 | 0.00 | 0.00 |
February | 0.128030E+10 | 0.104650E+10 | 0.101691E+10 | 0.681665E+09 | 0.335249E+09 | 0.00 | 0.00 |
March | 0.138351E+10 | 0.810085E+09 | 0.101254E+10 | 0.527675E+09 | 0.484862E+09 | 0.00 | 0.00 |
April | 0.111777E+10 | 0.660257E+09 | 0.733860E+09 | 0.238887E+09 | 0.494973E+09 | 0.00 | 0.00 |
May | 0.980451E+09 | 0.467822E+09 | 0.612694E+09 | 71211612.46 | 0.541482E+09 | 0.00 | 0.00 |
June | 0.104682E+10 | 0.312672E+09 | 0.548226E+09 | 30506596.26 | 0.517719E+09 | 0.00 | 0.00 |
July | 0.115083E+10 | 0.244562E+09 | 0.572720E+09 | 42705290.15 | 0.530015E+09 | 0.00 | 0.00 |
August | 0.140359E+10 | 0.214870E+09 | 0.683787E+09 | 0.127734E+09 | 0.556053E+09 | 0.00 | 0.00 |
September | 0.126106E+10 | 0.418965E+09 | 0.727740E+09 | 0.270681E+09 | 0.457058E+09 | 0.00 | 0.00 |
October | 0.162490E+10 | 0.823398E+09 | 0.109018E+10 | 0.706221E+09 | 0.383961E+09 | 0.00 | 0.00 |
November | 0.152613E+10 | 0.991764E+09 | 0.113501E+10 | 0.753171E+09 | 0.381835E+09 | 0.00 | 0.00 |
December | 0.146535E+10 | 0.116769E+10 | 0.118906E+10 | 0.836516E+09 | 0.352549E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.156336E+11 | 0.849407E+10 | 0.105290E+11 | 0.512799E+10 | 0.540102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.980451E+09 | 0.214870E+09 | 0.548226E+09 | 30506596.26 | 0.335249E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162490E+10 | 0.133549E+10 | 0.120629E+10 | 0.841019E+09 | 0.556053E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.159713E+10 | -0.142480E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172334304.6 | 59.95 | 0.00 | 0.00 |
February | 0.144912E+10 | -0.129723E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -151893030.1 | 59.95 | 0.00 | 0.00 |
March | 0.158794E+10 | -0.142600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161940545.7 | 59.95 | 0.00 | 0.00 |
April | 0.141863E+10 | -0.126389E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154744042.0 | 59.95 | 0.00 | 0.00 |
May | 0.136974E+10 | -0.121175E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157991577.3 | 59.95 | 0.00 | 0.00 |
June | 0.124787E+10 | -0.109627E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151593692.5 | 59.95 | 0.00 | 0.00 |
July | 0.119624E+10 | -0.104024E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156000428.6 | 59.95 | 0.00 | 0.00 |
August | 0.123037E+10 | -0.107473E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155640895.8 | 59.95 | 0.00 | 0.00 |
September | 0.121626E+10 | -0.106463E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151636544.0 | 59.95 | 0.00 | 0.00 |
October | 0.133652E+10 | -0.117741E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159117051.6 | 59.95 | 0.00 | 0.00 |
November | 0.139540E+10 | -0.123834E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157065879.9 | 59.95 | 0.00 | 0.00 |
December | 0.153280E+10 | -0.136478E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168020017.9 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.165780E+11 | -0.146800E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.189798E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.119624E+10 | -0.142600E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -172334304.6 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.159713E+10 | -0.104024E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151593692.5 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 407.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 411.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 293.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.878010E+10 | 62549.00 | 19-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498411E+10 | 60486.80 | 11-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415543E+09 | 51081.79 | 23-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100668E+09 | 46816.21 | 07-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32178483.61 | 22990.32 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.425697E+09 | 45461.97 | 23-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.248064E+10 | 53719.36 | 23-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.878010E+10 | 62549.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.260243E+10 | 25940.26 | 18-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142260E+10 | 28690.41 | 08-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70569185.99 | 21525.47 | 23-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16399734.68 | 4560.27 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5407370.03 | 3139.82 | 26-OCT-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80045819.92 | 16149.01 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.534519E+09 | 25372.34 | 22-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.473198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.260243E+10 | 28690.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.340617E+10 | 26791.69 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184014E+10 | 28321.88 | 08-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112835E+09 | 11565.67 | 19-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34793363.78 | 2737.65 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10250289.81 | 2027.50 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149865E+09 | 22830.33 | 23-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.932910E+09 | 25433.15 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.648697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.340617E+10 | 28321.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.360754E+10 | 30883.34 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193458E+10 | 28383.87 | 08-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131385E+09 | 14392.00 | 19-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37580292.62 | 3088.03 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12009439.64 | 2574.61 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170086E+09 | 23579.56 | 23-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104581E+10 | 25905.74 | 25-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.693899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.360754E+10 | 30883.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.386708E+10 | 30819.13 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207032E+10 | 28324.86 | 08-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159574E+09 | 17122.46 | 19-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42774893.87 | 3697.55 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15868770.22 | 2631.42 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197219E+09 | 23530.54 | 23-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118402E+10 | 25851.88 | 25-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.753686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.386708E+10 | 30819.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.806366E+10 | 59786.00 | 19-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.436238E+10 | 57814.89 | 11-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446615E+09 | 48825.33 | 23-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83787072.84 | 44748.17 | 07-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 61767983.89 | 24977.67 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.490889E+09 | 52602.82 | 24-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267719E+10 | 62065.41 | 24-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.806366E+10 | 62065.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.421316E+10 | 31605.67 | 19-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227877E+10 | 30563.65 | 11-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230766E+09 | 25811.35 | 23-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42776534.57 | 23655.98 | 07-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30927137.90 | 13163.08 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251143E+09 | 27808.31 | 24-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140643E+10 | 33113.59 | 24-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.845397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.421316E+10 | 33113.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.428388E+10 | 31595.48 | 19-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232397E+10 | 30553.80 | 11-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248535E+09 | 25803.03 | 23-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45812265.83 | 23648.35 | 07-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33811026.65 | 14737.70 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.267622E+09 | 27799.34 | 24-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145607E+10 | 33837.10 | 24-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.865970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.428388E+10 | 33837.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.450573E+10 | 31880.70 | 19-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.247050E+10 | 30829.61 | 11-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300259E+09 | 26035.96 | 23-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57290358.53 | 23861.83 | 07-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42161235.13 | 19828.61 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.310100E+09 | 28050.29 | 24-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158862E+10 | 34142.56 | 24-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.927467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.450573E+10 | 34142.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.581849E+10 | 37605.18 | 19-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339010E+10 | 36365.36 | 11-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.521988E+09 | 34644.74 | 24-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122003E+09 | 31251.86 | 27-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1426142.67 | 3390.46 | 11-MAY-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76948400.16 | 30567.64 | 31-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.475879E+09 | 33086.99 | 24-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208421E+10 | 40273.17 | 24-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.581849E+10 | 40273.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115465E+09 | 24993.10 | 14-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149751E+09 | 36088.72 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 389619.42 | 2597.46 | 19-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5855702.75 | 14684.38 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25447277.06 | 18965.63 | 18-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149751E+09 | 36088.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 34978897.89 | 11090.21 | 14-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28693920.32 | 17282.15 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 986230.05 | 5868.70 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5360175.36 | 8186.61 | 18-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70019223.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34978897.89 | 17282.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 44642419.40 | 11917.04 | 08-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39866904.54 | 18148.80 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1904010.22 | 7292.33 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7873834.82 | 9116.55 | 18-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94287168.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44642419.40 | 18148.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 50050543.19 | 12297.27 | 08-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44059324.50 | 18543.83 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1978590.91 | 7561.78 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10124744.93 | 9546.56 | 18-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50050543.19 | 18543.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 53263899.24 | 12515.99 | 08-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48299743.08 | 18733.69 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2518627.50 | 7784.69 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11879298.91 | 9776.51 | 18-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53263899.24 | 18733.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133234E+09 | 24066.65 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146489E+09 | 30793.53 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6398061.04 | 13733.05 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25882294.05 | 19213.59 | 18-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146489E+09 | 30793.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 66102274.24 | 12504.61 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73349701.86 | 16013.56 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3038097.05 | 7107.73 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12822563.24 | 9995.79 | 18-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73349701.86 | 16013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 68626257.34 | 12617.97 | 08-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74270542.91 | 15982.72 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3386522.33 | 7167.40 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13125847.24 | 10088.51 | 18-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74270542.91 | 15982.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 73883166.45 | 12852.12 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 88067552.79 | 16461.77 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3738567.43 | 7522.82 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15364885.75 | 10577.17 | 18-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88067552.79 | 16461.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 82997619.60 | 15902.19 | 27-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118313E+09 | 19789.53 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6917965.18 | 11088.36 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23638671.07 | 14103.29 | 18-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118313E+09 | 19789.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.550661E+09 | 0.464908E+09 | 7712.61 | 31-JAN-14:50 | 7171.39 | 0.00 |
February | 0.00 | 0.00 | 0.317676E+10 | 0.302769E+10 | 15231.05 | 26-FEB-15:00 | 15231.05 | 0.00 |
March | 0.00 | 0.00 | 0.895589E+10 | 0.800915E+10 | 23852.85 | 30-MAR-14:00 | 20549.94 | 0.00 |
April | 0.00 | 0.00 | 0.163367E+11 | 0.140570E+11 | 21599.08 | 23-APR-17:00 | 16422.46 | 0.00 |
May | 0.00 | 0.00 | 0.276848E+11 | 0.218016E+11 | 30011.55 | 31-MAY-07:03 | 17931.54 | 0.00 |
June | 0.00 | 0.00 | 0.397082E+11 | 0.297684E+11 | 58408.73 | 23-JUN-07:03 | 32274.61 | 0.00 |
July | 0.00 | 0.00 | 0.477447E+11 | 0.333464E+11 | 59283.04 | 27-JUL-07:02 | 30157.22 | 0.00 |
August | 0.00 | 0.00 | 0.507316E+11 | 0.346388E+11 | 59887.29 | 20-AUG-07:01 | 30490.73 | 0.00 |
September | 0.00 | 0.00 | 0.341458E+11 | 0.247215E+11 | 59069.00 | 17-SEP-07:02 | 31224.32 | 0.00 |
October | 0.00 | 0.00 | 0.175246E+11 | 0.139944E+11 | 58908.80 | 19-OCT-07:03 | 29452.98 | 0.00 |
November | 0.00 | 0.00 | 0.780479E+10 | 0.666000E+10 | 21668.26 | 05-NOV-15:00 | 16309.60 | 0.00 |
December | 0.00 | 0.00 | 0.161554E+10 | 0.129444E+10 | 16122.54 | 12-DEC-14:00 | 12646.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.255980E+12 | 0.191784E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.550661E+09 | 0.464908E+09 | 7712.61 | 7171.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.507316E+11 | 0.346388E+11 | 59887.29 | 32274.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.479553E+09 | 0.417893E+09 | 4763.11 | 31-JAN-14:50 | 4473.78 | 0.00 |
February | 0.00 | 0.00 | 0.224866E+10 | 0.212150E+10 | 8702.30 | 26-FEB-15:00 | 8702.30 | 0.00 |
March | 0.00 | 0.00 | 0.570859E+10 | 0.518591E+10 | 12897.96 | 30-MAR-14:00 | 11209.66 | 0.00 |
April | 0.00 | 0.00 | 0.939739E+10 | 0.821161E+10 | 11829.13 | 17-APR-14:00 | 11353.59 | 0.00 |
May | 0.00 | 0.00 | 0.148397E+11 | 0.119023E+11 | 18723.40 | 31-MAY-07:03 | 12787.25 | 0.00 |
June | 0.00 | 0.00 | 0.204041E+11 | 0.155492E+11 | 29566.71 | 26-JUN-07:01 | 19707.52 | 0.00 |
July | 0.00 | 0.00 | 0.243557E+11 | 0.172944E+11 | 29963.74 | 27-JUL-07:02 | 17816.02 | 0.00 |
August | 0.00 | 0.00 | 0.257073E+11 | 0.178505E+11 | 30303.45 | 20-AUG-07:01 | 17689.03 | 0.00 |
September | 0.00 | 0.00 | 0.176514E+11 | 0.130401E+11 | 29915.45 | 17-SEP-07:02 | 18022.46 | 0.00 |
October | 0.00 | 0.00 | 0.990706E+10 | 0.810027E+10 | 29764.67 | 19-OCT-07:03 | 17462.15 | 0.00 |
November | 0.00 | 0.00 | 0.498904E+10 | 0.438561E+10 | 11613.98 | 05-NOV-14:10 | 8674.56 | 0.00 |
December | 0.00 | 0.00 | 0.136006E+10 | 0.115234E+10 | 9136.00 | 12-DEC-14:00 | 7279.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137049E+12 | 0.105212E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.479553E+09 | 0.417893E+09 | 4763.11 | 4473.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.257073E+11 | 0.178505E+11 | 30303.45 | 19707.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.251766E+09 | 0.218691E+09 | 4183.42 | 31-JAN-14:50 | 3936.57 | 0.00 |
February | 0.00 | 0.00 | 0.138556E+10 | 0.133421E+10 | 8079.11 | 26-FEB-15:00 | 8079.11 | 0.00 |
March | 0.00 | 0.00 | 0.389636E+10 | 0.348934E+10 | 12612.31 | 30-MAR-14:00 | 10988.62 | 0.00 |
April | 0.00 | 0.00 | 0.674530E+10 | 0.593605E+10 | 11642.80 | 17-APR-14:00 | 11214.70 | 0.00 |
May | 0.00 | 0.00 | 0.113851E+11 | 0.905673E+10 | 29831.43 | 31-MAY-06:03 | 17331.50 | 0.00 |
June | 0.00 | 0.00 | 0.162866E+11 | 0.122486E+11 | 30623.80 | 19-JUN-06:02 | 15546.10 | 0.00 |
July | 0.00 | 0.00 | 0.191033E+11 | 0.133303E+11 | 30843.50 | 27-JUL-06:02 | 15481.04 | 0.00 |
August | 0.00 | 0.00 | 0.206854E+11 | 0.141569E+11 | 31454.40 | 20-AUG-07:01 | 14847.98 | 0.00 |
September | 0.00 | 0.00 | 0.136533E+11 | 0.997668E+10 | 31126.47 | 17-SEP-07:02 | 14559.90 | 0.00 |
October | 0.00 | 0.00 | 0.706376E+10 | 0.572724E+10 | 30804.74 | 19-OCT-06:02 | 14685.65 | 0.00 |
November | 0.00 | 0.00 | 0.324267E+10 | 0.285072E+10 | 11034.70 | 05-NOV-14:00 | 8200.42 | 0.00 |
December | 0.00 | 0.00 | 0.800725E+09 | 0.657786E+09 | 8761.25 | 12-DEC-14:00 | 6949.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104500E+12 | 0.789831E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.251766E+09 | 0.218691E+09 | 4183.42 | 3936.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206854E+11 | 0.141569E+11 | 31454.40 | 17331.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.224240E+09 | 0.194508E+09 | 3998.27 | 31-JAN-14:50 | 3759.32 | 0.00 |
February | 0.00 | 0.00 | 0.132822E+10 | 0.128161E+10 | 7928.20 | 26-FEB-15:00 | 7928.20 | 0.00 |
March | 0.00 | 0.00 | 0.382307E+10 | 0.341955E+10 | 12585.95 | 30-MAR-14:00 | 10962.48 | 0.00 |
April | 0.00 | 0.00 | 0.670903E+10 | 0.590261E+10 | 11647.50 | 17-APR-14:00 | 11219.28 | 0.00 |
May | 0.00 | 0.00 | 0.113976E+11 | 0.906480E+10 | 29904.14 | 31-MAY-06:03 | 17393.00 | 0.00 |
June | 0.00 | 0.00 | 0.163744E+11 | 0.123174E+11 | 30702.08 | 19-JUN-06:02 | 15641.30 | 0.00 |
July | 0.00 | 0.00 | 0.192328E+11 | 0.134294E+11 | 30920.35 | 27-JUL-06:02 | 15546.62 | 0.00 |
August | 0.00 | 0.00 | 0.208177E+11 | 0.142553E+11 | 31537.11 | 20-AUG-07:01 | 14970.09 | 0.00 |
September | 0.00 | 0.00 | 0.137076E+11 | 0.100172E+11 | 31199.00 | 17-SEP-07:02 | 14600.84 | 0.00 |
October | 0.00 | 0.00 | 0.702656E+10 | 0.569303E+10 | 30876.02 | 19-OCT-06:02 | 14722.75 | 0.00 |
November | 0.00 | 0.00 | 0.315457E+10 | 0.276930E+10 | 10952.10 | 05-NOV-14:00 | 8127.48 | 0.00 |
December | 0.00 | 0.00 | 0.751448E+09 | 0.612304E+09 | 8581.89 | 12-DEC-14:00 | 6792.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104547E+12 | 0.789570E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.224240E+09 | 0.194508E+09 | 3998.27 | 3759.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208177E+11 | 0.142553E+11 | 31537.11 | 17393.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.190112E+09 | 0.164702E+09 | 3755.78 | 31-JAN-14:50 | 3525.56 | 0.00 |
February | 0.00 | 0.00 | 0.123750E+10 | 0.119880E+10 | 7747.45 | 26-FEB-15:00 | 7747.45 | 0.00 |
March | 0.00 | 0.00 | 0.365192E+10 | 0.326060E+10 | 12441.45 | 30-MAR-14:00 | 10826.63 | 0.00 |
April | 0.00 | 0.00 | 0.652628E+10 | 0.573734E+10 | 11542.43 | 17-APR-14:00 | 11115.36 | 0.00 |
May | 0.00 | 0.00 | 0.112130E+11 | 0.890889E+10 | 29831.23 | 31-MAY-06:03 | 17292.93 | 0.00 |
June | 0.00 | 0.00 | 0.162265E+11 | 0.121953E+11 | 30632.88 | 19-JUN-06:02 | 15576.11 | 0.00 |
July | 0.00 | 0.00 | 0.190971E+11 | 0.133269E+11 | 30845.42 | 27-JUL-06:02 | 15450.52 | 0.00 |
August | 0.00 | 0.00 | 0.206798E+11 | 0.141512E+11 | 31467.09 | 20-AUG-07:01 | 14908.35 | 0.00 |
September | 0.00 | 0.00 | 0.135530E+11 | 0.989335E+10 | 31127.40 | 17-SEP-07:02 | 14512.95 | 0.00 |
October | 0.00 | 0.00 | 0.685186E+10 | 0.554030E+10 | 30802.73 | 19-OCT-06:02 | 14609.95 | 0.00 |
November | 0.00 | 0.00 | 0.299546E+10 | 0.262410E+10 | 10781.58 | 05-NOV-14:00 | 7982.44 | 0.00 |
December | 0.00 | 0.00 | 0.681325E+09 | 0.548869E+09 | 8316.85 | 12-DEC-14:00 | 6561.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.102904E+12 | 0.775504E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.190112E+09 | 0.164702E+09 | 3755.78 | 3525.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206798E+11 | 0.141512E+11 | 31467.09 | 17292.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.200716E+09 | 0.170161E+09 | 6164.36 | 31-JAN-15:10 | 5642.31 | 0.00 |
February | 0.00 | 0.00 | 0.184285E+10 | 0.180088E+10 | 13677.81 | 26-FEB-15:10 | 13677.81 | 0.00 |
March | 0.00 | 0.00 | 0.592612E+10 | 0.516426E+10 | 22993.51 | 30-MAR-14:10 | 19660.29 | 0.00 |
April | 0.00 | 0.00 | 0.112518E+11 | 0.967052E+10 | 21691.65 | 19-APR-14:40 | 18159.48 | 0.00 |
May | 0.00 | 0.00 | 0.199519E+11 | 0.154849E+11 | 38384.33 | 30-MAY-07:03 | 25064.70 | 0.00 |
June | 0.00 | 0.00 | 0.296140E+11 | 0.217771E+11 | 56599.02 | 19-JUN-07:03 | 28295.47 | 0.00 |
July | 0.00 | 0.00 | 0.346991E+11 | 0.237211E+11 | 56982.20 | 31-JUL-07:03 | 26939.04 | 0.00 |
August | 0.00 | 0.00 | 0.376954E+11 | 0.252571E+11 | 58278.99 | 20-AUG-08:61 | 26644.93 | 0.00 |
September | 0.00 | 0.00 | 0.241729E+11 | 0.172029E+11 | 57647.13 | 17-SEP-08:62 | 25803.45 | 0.00 |
October | 0.00 | 0.00 | 0.117683E+11 | 0.921812E+10 | 56054.00 | 19-OCT-07:03 | 28029.06 | 0.00 |
November | 0.00 | 0.00 | 0.464096E+10 | 0.395635E+10 | 19898.32 | 05-NOV-15:00 | 14524.98 | 0.00 |
December | 0.00 | 0.00 | 0.979183E+09 | 0.745823E+09 | 14623.20 | 12-DEC-14:00 | 11073.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182743E+12 | 0.134169E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.200716E+09 | 0.170161E+09 | 6164.36 | 5642.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.376954E+11 | 0.252571E+11 | 58278.99 | 28295.47 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 95197361.25 | 81397180.38 | 3092.18 | 31-JAN-15:10 | 2842.74 | 0.00 |
February | 0.00 | 0.00 | 0.937802E+09 | 0.918213E+09 | 7084.66 | 26-FEB-15:10 | 7084.66 | 0.00 |
March | 0.00 | 0.00 | 0.302109E+10 | 0.264010E+10 | 11841.38 | 30-MAR-14:10 | 10143.59 | 0.00 |
April | 0.00 | 0.00 | 0.575910E+10 | 0.496565E+10 | 11160.92 | 17-APR-14:20 | 10618.99 | 0.00 |
May | 0.00 | 0.00 | 0.102412E+11 | 0.797421E+10 | 18220.47 | 30-MAY-07:03 | 11983.30 | 0.00 |
June | 0.00 | 0.00 | 0.152014E+11 | 0.112137E+11 | 29930.62 | 19-JUN-07:03 | 14913.38 | 0.00 |
July | 0.00 | 0.00 | 0.178218E+11 | 0.122267E+11 | 30132.22 | 31-JUL-07:03 | 14211.82 | 0.00 |
August | 0.00 | 0.00 | 0.193601E+11 | 0.130223E+11 | 30798.37 | 20-AUG-08:61 | 14030.20 | 0.00 |
September | 0.00 | 0.00 | 0.124367E+11 | 0.888607E+10 | 30467.99 | 17-SEP-08:62 | 13595.41 | 0.00 |
October | 0.00 | 0.00 | 0.604988E+10 | 0.475836E+10 | 29621.23 | 19-OCT-07:03 | 14844.33 | 0.00 |
November | 0.00 | 0.00 | 0.238175E+10 | 0.203721E+10 | 10330.46 | 05-NOV-15:00 | 7569.65 | 0.00 |
December | 0.00 | 0.00 | 0.493600E+09 | 0.375983E+09 | 7482.45 | 12-DEC-14:00 | 5680.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.937998E+11 | 0.690999E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 95197361.25 | 81397180.38 | 3092.18 | 2842.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.193601E+11 | 0.130223E+11 | 30798.37 | 14913.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 88167939.61 | 75579592.16 | 3005.46 | 31-JAN-15:10 | 2758.58 | 0.00 |
February | 0.00 | 0.00 | 0.907293E+09 | 0.889347E+09 | 6987.12 | 26-FEB-15:10 | 6987.12 | 0.00 |
March | 0.00 | 0.00 | 0.294758E+10 | 0.257086E+10 | 11757.75 | 30-MAR-14:10 | 10058.06 | 0.00 |
April | 0.00 | 0.00 | 0.566846E+10 | 0.488157E+10 | 11086.93 | 17-APR-14:20 | 10538.62 | 0.00 |
May | 0.00 | 0.00 | 0.101412E+11 | 0.788462E+10 | 17433.74 | 30-MAY-07:03 | 11461.11 | 0.00 |
June | 0.00 | 0.00 | 0.151163E+11 | 0.111356E+11 | 29917.15 | 19-JUN-07:03 | 14869.22 | 0.00 |
July | 0.00 | 0.00 | 0.177354E+11 | 0.121512E+11 | 30119.12 | 31-JUL-07:03 | 14168.63 | 0.00 |
August | 0.00 | 0.00 | 0.192727E+11 | 0.129456E+11 | 30785.95 | 20-AUG-08:61 | 13993.03 | 0.00 |
September | 0.00 | 0.00 | 0.123602E+11 | 0.881810E+10 | 30455.97 | 17-SEP-08:62 | 13553.50 | 0.00 |
October | 0.00 | 0.00 | 0.597806E+10 | 0.469258E+10 | 29008.93 | 19-OCT-07:03 | 14502.69 | 0.00 |
November | 0.00 | 0.00 | 0.232686E+10 | 0.198700E+10 | 10255.35 | 05-NOV-15:00 | 7501.23 | 0.00 |
December | 0.00 | 0.00 | 0.475207E+09 | 0.360107E+09 | 7367.06 | 12-DEC-14:00 | 5579.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.930174E+11 | 0.683921E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 88167939.61 | 75579592.16 | 3005.46 | 2758.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.192727E+11 | 0.129456E+11 | 30785.95 | 14869.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 77383150.27 | 66964189.81 | 2863.52 | 31-JAN-15:10 | 2627.93 | 0.00 |
February | 0.00 | 0.00 | 0.855054E+09 | 0.840540E+09 | 6827.98 | 26-FEB-15:10 | 6827.98 | 0.00 |
March | 0.00 | 0.00 | 0.281505E+10 | 0.245085E+10 | 11657.50 | 30-MAR-14:10 | 9967.70 | 0.00 |
April | 0.00 | 0.00 | 0.550674E+10 | 0.474344E+10 | 11004.67 | 17-APR-14:20 | 10462.51 | 0.00 |
May | 0.00 | 0.00 | 0.100195E+11 | 0.778997E+10 | 15708.20 | 30-MAY-07:03 | 10357.37 | 0.00 |
June | 0.00 | 0.00 | 0.151214E+11 | 0.111472E+11 | 30179.52 | 19-JUN-07:03 | 14958.71 | 0.00 |
July | 0.00 | 0.00 | 0.177820E+11 | 0.121997E+11 | 30384.46 | 31-JUL-07:03 | 14258.76 | 0.00 |
August | 0.00 | 0.00 | 0.193441E+11 | 0.130132E+11 | 31062.19 | 20-AUG-08:61 | 14140.81 | 0.00 |
September | 0.00 | 0.00 | 0.123685E+11 | 0.883292E+10 | 30725.78 | 17-SEP-08:62 | 13650.50 | 0.00 |
October | 0.00 | 0.00 | 0.591123E+10 | 0.463832E+10 | 28109.34 | 19-OCT-07:03 | 14050.87 | 0.00 |
November | 0.00 | 0.00 | 0.224989E+10 | 0.191902E+10 | 10180.37 | 05-NOV-15:00 | 7442.93 | 0.00 |
December | 0.00 | 0.00 | 0.447162E+09 | 0.336684E+09 | 7193.26 | 12-DEC-14:00 | 5438.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.924980E+11 | 0.679788E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 77383150.27 | 66964189.81 | 2863.52 | 2627.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.193441E+11 | 0.130132E+11 | 31062.19 | 14958.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 76453963.99 | 67227997.70 | 2980.03 | 31-JAN-15:10 | 2758.76 | 0.00 |
February | 0.00 | 0.00 | 0.861550E+09 | 0.851945E+09 | 7064.72 | 26-FEB-15:10 | 7064.72 | 0.00 |
March | 0.00 | 0.00 | 0.277484E+10 | 0.243048E+10 | 12149.96 | 30-MAR-14:10 | 10442.06 | 0.00 |
April | 0.00 | 0.00 | 0.561327E+10 | 0.489299E+10 | 11553.75 | 17-APR-14:10 | 11003.64 | 0.00 |
May | 0.00 | 0.00 | 0.105711E+11 | 0.832274E+10 | 16376.55 | 30-MAY-15:00 | 12732.90 | 0.00 |
June | 0.00 | 0.00 | 0.164625E+11 | 0.123176E+11 | 35787.44 | 26-JUN-07:01 | 18775.89 | 0.00 |
July | 0.00 | 0.00 | 0.194455E+11 | 0.136048E+11 | 35957.63 | 27-JUL-07:02 | 16349.30 | 0.00 |
August | 0.00 | 0.00 | 0.211840E+11 | 0.145360E+11 | 37020.43 | 20-AUG-08:61 | 15465.62 | 0.00 |
September | 0.00 | 0.00 | 0.134815E+11 | 0.981895E+10 | 36310.87 | 17-SEP-08:62 | 15666.58 | 0.00 |
October | 0.00 | 0.00 | 0.636387E+10 | 0.506690E+10 | 24899.82 | 19-OCT-07:03 | 11116.98 | 0.00 |
November | 0.00 | 0.00 | 0.235125E+10 | 0.202345E+10 | 10622.74 | 05-NOV-15:00 | 7859.39 | 0.00 |
December | 0.00 | 0.00 | 0.451248E+09 | 0.343526E+09 | 7397.75 | 12-DEC-14:00 | 5646.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.996372E+11 | 0.742766E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 76453963.99 | 67227997.70 | 2980.03 | 2758.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211840E+11 | 0.145360E+11 | 37020.43 | 18775.89 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.716283E+10 | 0.95 | 3925.37 | 22-JAN-19:10 | 1.38 |
February | 0.647961E+10 | 0.95 | 3925.37 | 11-FEB-09:00 | 1.37 |
March | 0.715045E+10 | 0.94 | 3925.37 | 03-MAR-19:20 | 1.37 |
April | 0.689609E+10 | 0.93 | 3925.37 | 01-APR-14:30 | 1.37 |
May | 0.712219E+10 | 0.93 | 3925.37 | 01-MAY-08:20 | 1.36 |
June | 0.692435E+10 | 0.93 | 3925.37 | 01-JUN-07:10 | 1.36 |
July | 0.712219E+10 | 0.92 | 3925.37 | 02-JUL-07:08 | 1.36 |
August | 0.713632E+10 | 0.93 | 3925.37 | 01-AUG-13:40 | 1.37 |
September | 0.691022E+10 | 0.93 | 3925.37 | 01-SEP-12:40 | 1.37 |
October | 0.712219E+10 | 0.93 | 3925.37 | 01-OCT-11:30 | 1.36 |
November | 0.688424E+10 | 0.93 | 3925.37 | 01-NOV-11:10 | 1.37 |
December | 0.715922E+10 | 0.94 | 3925.37 | 02-DEC-11:00 | 1.39 |
Annual Sum or Average | 0.840699E+11 | 0.93 | |||
Minimum of Months | 0.647961E+10 | 0.92 | 3925.37 | 1.36 | |
Maximum of Months | 0.716283E+10 | 0.95 | 3925.37 | 1.39 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.287757E+10 | 0.80 | 2094.58 | 01-JAN-08:08 | 1.40 |
February | 0.267169E+10 | 0.88 | 2094.58 | 01-FEB-08:03 | 1.41 |
March | 0.310047E+10 | 1.01 | 2094.58 | 01-MAR-18:40 | 1.40 |
April | 0.307087E+10 | 1.00 | 2094.58 | 01-APR-09:30 | 1.41 |
May | 0.330256E+10 | 0.99 | 2094.58 | 02-MAY-07:50 | 1.40 |
June | 0.334097E+10 | 0.98 | 2094.58 | 01-JUN-12:00 | 1.40 |
July | 0.352883E+10 | 0.97 | 2094.58 | 01-JUL-11:20 | 1.40 |
August | 0.357407E+10 | 0.97 | 2094.58 | 01-AUG-09:30 | 1.40 |
September | 0.327911E+10 | 0.99 | 2094.58 | 01-SEP-07:10 | 1.40 |
October | 0.319070E+10 | 1.00 | 2094.58 | 01-OCT-07:40 | 1.40 |
November | 0.296009E+10 | 0.99 | 2094.58 | 01-NOV-10:10 | 1.41 |
December | 0.289130E+10 | 0.88 | 2094.58 | 01-DEC-08:13 | 1.41 |
Annual Sum or Average | 0.377882E+11 | 0.96 | |||
Minimum of Months | 0.267169E+10 | 0.80 | 2094.58 | 1.40 | |
Maximum of Months | 0.357407E+10 | 1.01 | 2094.58 | 1.41 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.304088E+10 | 0.76 | 2101.22 | 01-JAN-08:30 | 1.41 |
February | 0.275343E+10 | 0.77 | 2101.22 | 01-FEB-07:05 | 1.41 |
March | 0.310140E+10 | 0.78 | 2101.22 | 01-MAR-18:40 | 1.40 |
April | 0.295011E+10 | 0.76 | 2101.22 | 01-APR-09:10 | 1.41 |
May | 0.307114E+10 | 0.76 | 2101.22 | 01-MAY-06:10 | 1.39 |
June | 0.299549E+10 | 0.77 | 2101.22 | 01-JUN-06:10 | 1.40 |
July | 0.302575E+10 | 0.75 | 2101.22 | 01-JUL-06:30 | 1.39 |
August | 0.310140E+10 | 0.77 | 2101.22 | 01-AUG-06:08 | 1.39 |
September | 0.295011E+10 | 0.76 | 2101.22 | 01-SEP-06:08 | 1.39 |
October | 0.304088E+10 | 0.76 | 2101.22 | 01-OCT-07:05 | 1.40 |
November | 0.295011E+10 | 0.76 | 2101.22 | 01-NOV-10:25 | 1.41 |
December | 0.302575E+10 | 0.76 | 2101.22 | 01-DEC-07:03 | 1.41 |
Annual Sum or Average | 0.360064E+11 | 0.76 | |||
Minimum of Months | 0.275343E+10 | 0.75 | 2101.22 | 1.39 | |
Maximum of Months | 0.310140E+10 | 0.78 | 2101.22 | 1.41 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.304970E+10 | 0.76 | 2107.31 | 01-JAN-08:08 | 1.41 |
February | 0.276142E+10 | 0.77 | 2107.31 | 01-FEB-07:30 | 1.41 |
March | 0.311039E+10 | 0.78 | 2107.31 | 01-MAR-18:20 | 1.41 |
April | 0.295866E+10 | 0.76 | 2107.31 | 01-APR-10:20 | 1.41 |
May | 0.308004E+10 | 0.76 | 2107.31 | 01-MAY-06:20 | 1.39 |
June | 0.300418E+10 | 0.77 | 2107.31 | 01-JUN-06:20 | 1.40 |
July | 0.303452E+10 | 0.75 | 2107.31 | 01-JUL-07:05 | 1.39 |
August | 0.311039E+10 | 0.77 | 2107.31 | 01-AUG-06:07 | 1.39 |
September | 0.295866E+10 | 0.76 | 2107.31 | 01-SEP-06:10 | 1.40 |
October | 0.304970E+10 | 0.76 | 2107.31 | 01-OCT-07:10 | 1.40 |
November | 0.295866E+10 | 0.76 | 2107.31 | 01-NOV-11:00 | 1.41 |
December | 0.303452E+10 | 0.76 | 2107.31 | 01-DEC-07:50 | 1.41 |
Annual Sum or Average | 0.361108E+11 | 0.76 | |||
Minimum of Months | 0.276142E+10 | 0.75 | 2107.31 | 1.39 | |
Maximum of Months | 0.311039E+10 | 0.78 | 2107.31 | 1.41 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.304130E+10 | 0.76 | 2101.51 | 07-JAN-15:10 | 1.42 |
February | 0.275381E+10 | 0.77 | 2101.51 | 01-FEB-07:05 | 1.41 |
March | 0.310182E+10 | 0.78 | 2101.51 | 01-MAR-18:30 | 1.41 |
April | 0.295051E+10 | 0.76 | 2101.51 | 01-APR-09:10 | 1.41 |
May | 0.307156E+10 | 0.76 | 2101.51 | 30-MAY-14:00 | 1.40 |
June | 0.299591E+10 | 0.77 | 2101.51 | 20-JUN-11:20 | 1.40 |
July | 0.302617E+10 | 0.75 | 2101.51 | 16-JUL-11:40 | 1.40 |
August | 0.310182E+10 | 0.77 | 2101.51 | 02-AUG-06:20 | 1.39 |
September | 0.295051E+10 | 0.76 | 2101.51 | 17-SEP-14:30 | 1.40 |
October | 0.304130E+10 | 0.76 | 2101.51 | 24-OCT-11:20 | 1.41 |
November | 0.295051E+10 | 0.76 | 2101.51 | 13-NOV-15:00 | 1.42 |
December | 0.302617E+10 | 0.76 | 2101.51 | 05-DEC-13:20 | 1.42 |
Annual Sum or Average | 0.360114E+11 | 0.76 | |||
Minimum of Months | 0.275381E+10 | 0.75 | 2101.51 | 1.39 | |
Maximum of Months | 0.310182E+10 | 0.78 | 2101.51 | 1.42 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.506923E+10 | 0.71 | 3793.75 | 01-JAN-10:40 | 1.40 |
February | 0.461828E+10 | 0.71 | 3793.75 | 01-FEB-14:20 | 1.41 |
March | 0.517619E+10 | 0.72 | 3793.75 | 02-MAR-13:40 | 1.41 |
April | 0.491670E+10 | 0.70 | 3793.75 | 02-APR-10:20 | 1.40 |
May | 0.512156E+10 | 0.71 | 3793.75 | 06-MAY-07:50 | 1.40 |
June | 0.499864E+10 | 0.71 | 3793.75 | 05-JUN-11:00 | 1.40 |
July | 0.503961E+10 | 0.69 | 3793.75 | 05-JUL-09:10 | 1.40 |
August | 0.517619E+10 | 0.71 | 3793.75 | 01-AUG-17:40 | 1.40 |
September | 0.491670E+10 | 0.70 | 3793.75 | 01-SEP-12:30 | 1.40 |
October | 0.506693E+10 | 0.70 | 3793.75 | 02-OCT-14:20 | 1.40 |
November | 0.491670E+10 | 0.70 | 3793.75 | 01-NOV-19:30 | 1.40 |
December | 0.503961E+10 | 0.70 | 3793.75 | 22-DEC-08:09 | 1.41 |
Annual Sum or Average | 0.600563E+11 | 0.71 | |||
Minimum of Months | 0.461828E+10 | 0.69 | 3793.75 | 1.40 | |
Maximum of Months | 0.517619E+10 | 0.72 | 3793.75 | 1.41 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.269079E+10 | 0.71 | 2013.69 | 16-JAN-17:30 | 1.42 |
February | 0.245058E+10 | 0.71 | 2013.69 | 01-FEB-14:20 | 1.41 |
March | 0.274748E+10 | 0.72 | 2013.69 | 02-MAR-08:07 | 1.41 |
April | 0.260974E+10 | 0.70 | 2013.69 | 11-APR-19:30 | 1.41 |
May | 0.271848E+10 | 0.71 | 2013.69 | 04-MAY-14:10 | 1.40 |
June | 0.265324E+10 | 0.71 | 2013.69 | 01-JUN-15:40 | 1.40 |
July | 0.267498E+10 | 0.69 | 2013.69 | 20-JUL-14:00 | 1.40 |
August | 0.274748E+10 | 0.71 | 2013.69 | 01-AUG-09:30 | 1.40 |
September | 0.260974E+10 | 0.70 | 2013.69 | 30-SEP-12:30 | 1.40 |
October | 0.268948E+10 | 0.70 | 2013.69 | 01-OCT-08:40 | 1.39 |
November | 0.260974E+10 | 0.70 | 2013.69 | 01-NOV-11:10 | 1.41 |
December | 0.267498E+10 | 0.70 | 2013.69 | 27-DEC-09:50 | 1.41 |
Annual Sum or Average | 0.318767E+11 | 0.71 | |||
Minimum of Months | 0.245058E+10 | 0.69 | 2013.69 | 1.39 | |
Maximum of Months | 0.274748E+10 | 0.72 | 2013.69 | 1.42 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.268643E+10 | 0.71 | 2010.54 | 05-JAN-10:50 | 1.42 |
February | 0.244801E+10 | 0.71 | 2010.54 | 02-FEB-08:15 | 1.41 |
March | 0.274318E+10 | 0.72 | 2010.54 | 06-MAR-18:40 | 1.41 |
April | 0.260566E+10 | 0.70 | 2010.54 | 17-APR-10:20 | 1.40 |
May | 0.271422E+10 | 0.71 | 2010.54 | 01-MAY-11:00 | 1.40 |
June | 0.264908E+10 | 0.71 | 2010.54 | 09-JUN-19:40 | 1.40 |
July | 0.267080E+10 | 0.69 | 2010.54 | 01-JUL-11:40 | 1.40 |
August | 0.274318E+10 | 0.71 | 2010.54 | 10-AUG-19:30 | 1.40 |
September | 0.260566E+10 | 0.70 | 2010.54 | 05-SEP-16:50 | 1.40 |
October | 0.268527E+10 | 0.70 | 2010.54 | 06-OCT-14:20 | 1.41 |
November | 0.260566E+10 | 0.70 | 2010.54 | 03-NOV-14:40 | 1.40 |
December | 0.267080E+10 | 0.70 | 2010.54 | 05-DEC-08:40 | 1.42 |
Annual Sum or Average | 0.318279E+11 | 0.71 | |||
Minimum of Months | 0.244801E+10 | 0.69 | 2010.54 | 1.40 | |
Maximum of Months | 0.274318E+10 | 0.72 | 2010.54 | 1.42 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271584E+10 | 0.71 | 2030.67 | 02-JAN-20:40 | 1.41 |
February | 0.248060E+10 | 0.72 | 2030.67 | 02-FEB-15:30 | 1.42 |
March | 0.277065E+10 | 0.72 | 2030.67 | 02-MAR-14:40 | 1.41 |
April | 0.263175E+10 | 0.70 | 2030.67 | 07-APR-14:00 | 1.41 |
May | 0.274141E+10 | 0.71 | 2030.67 | 11-MAY-19:20 | 1.41 |
June | 0.267562E+10 | 0.71 | 2030.67 | 05-JUN-13:00 | 1.40 |
July | 0.269755E+10 | 0.69 | 2030.67 | 01-JUL-11:50 | 1.40 |
August | 0.277065E+10 | 0.71 | 2030.67 | 05-AUG-16:50 | 1.40 |
September | 0.263175E+10 | 0.70 | 2030.67 | 06-SEP-15:00 | 1.40 |
October | 0.271217E+10 | 0.70 | 2030.67 | 05-OCT-18:20 | 1.40 |
November | 0.263175E+10 | 0.70 | 2030.67 | 01-NOV-17:50 | 1.40 |
December | 0.269755E+10 | 0.70 | 2030.67 | 21-DEC-08:17 | 1.42 |
Annual Sum or Average | 0.321573E+11 | 0.71 | |||
Minimum of Months | 0.248060E+10 | 0.69 | 2030.67 | 1.40 | |
Maximum of Months | 0.277065E+10 | 0.72 | 2030.67 | 1.42 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.339351E+10 | 0.78 | 2457.83 | 01-JAN-09:08 | 1.41 |
February | 0.309343E+10 | 0.77 | 2457.83 | 01-FEB-16:00 | 1.41 |
March | 0.335346E+10 | 0.72 | 2457.83 | 01-MAR-08:40 | 1.41 |
April | 0.318534E+10 | 0.70 | 2457.83 | 01-APR-12:20 | 1.41 |
May | 0.331807E+10 | 0.71 | 2457.83 | 01-MAY-10:20 | 1.40 |
June | 0.323843E+10 | 0.71 | 2457.83 | 01-JUN-09:10 | 1.40 |
July | 0.326498E+10 | 0.69 | 2457.83 | 01-JUL-12:10 | 1.40 |
August | 0.335346E+10 | 0.71 | 2457.83 | 01-AUG-10:20 | 1.40 |
September | 0.318534E+10 | 0.70 | 2457.83 | 01-SEP-09:10 | 1.40 |
October | 0.328267E+10 | 0.70 | 2457.83 | 01-OCT-11:30 | 1.39 |
November | 0.318534E+10 | 0.70 | 2457.83 | 01-NOV-13:50 | 1.40 |
December | 0.327047E+10 | 0.71 | 2457.83 | 01-DEC-08:08 | 1.42 |
Annual Sum or Average | 0.391245E+11 | 0.72 | |||
Minimum of Months | 0.309343E+10 | 0.69 | 2457.83 | 1.39 | |
Maximum of Months | 0.339351E+10 | 0.78 | 2457.83 | 1.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.113551E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.966128E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.988391E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.115973E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.148394E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.180095E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.204250E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.210986E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.162068E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.119687E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.930321E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.861666E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.162966E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.861666E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.210986E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.425464E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.393612E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.467048E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.558643E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.718028E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.871393E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.993318E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.102569E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.780742E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.576673E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.433985E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.349026E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.759363E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.349026E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.102569E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.469597E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.396811E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.419291E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.476968E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.604312E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.727046E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.803298E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.846465E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.644005E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.487021E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.389397E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.363071E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.662728E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.363071E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.846465E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.477893E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.400172E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.418995E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.477109E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.605590E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.730063E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.807347E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.850596E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.646182E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.487087E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.388813E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.366910E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.665676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.366910E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.850596E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.486369E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.402626E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.414735E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.471951E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.600420E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.725649E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.803133E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.846317E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.641760E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.482080E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.385000E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.369307E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.662935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.369307E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.846317E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.867669E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.708859E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.704599E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.817116E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.106866E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.132866E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.147352E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.155942E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.115035E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.833236E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.645134E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.634152E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.117914E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.634152E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.155942E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.457515E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.371784E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.365317E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.418445E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.542005E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.666905E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.737040E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.779245E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.581087E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.427569E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.335916E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.334565E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.601739E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.334565E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.779245E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.459704E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.372558E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.363583E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.415893E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.539265E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.664400E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.734413E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.776597E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.578905E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.425504E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.334708E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.335402E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.600093E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.334708E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.776597E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.471395E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.381429E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.364679E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.415004E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.539476E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.667508E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.738538E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.781409E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.582039E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.426971E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.336923E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.342143E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.604751E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.336923E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.781409E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.599108E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.486026E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.430260E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.477856E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.616592E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.763212E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.841963E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.890656E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.670183E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.499138E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.401960E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.418439E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.709539E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.401960E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.890656E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.716283E+10 | 0.550661E+09 | 0.889556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.647961E+10 | 0.317676E+10 | 0.513386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.715045E+10 | 0.895589E+10 | 0.415933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.689609E+10 | 0.163367E+11 | 0.100668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.712219E+10 | 0.276848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.692435E+10 | 0.397082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.712219E+10 | 0.477447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.713632E+10 | 0.507316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.691022E+10 | 0.341458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.712219E+10 | 0.175246E+11 | 32178483.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.688424E+10 | 0.780479E+10 | 0.431552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715922E+10 | 0.161554E+10 | 0.250609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840699E+11 | 0.255980E+12 | 0.175158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.647961E+10 | 0.550661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.716283E+10 | 0.507316E+11 | 0.889556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.287757E+10 | 0.479553E+09 | 0.263741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267169E+10 | 0.224866E+10 | 0.145129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310047E+10 | 0.570859E+10 | 70569185.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307087E+10 | 0.939739E+10 | 16399734.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.330256E+10 | 0.148397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.334097E+10 | 0.204041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.352883E+10 | 0.243557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.357407E+10 | 0.257073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327911E+10 | 0.176514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.319070E+10 | 0.990706E+10 | 5407370.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296009E+10 | 0.498904E+10 | 81032049.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289130E+10 | 0.136006E+10 | 0.539879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377882E+11 | 0.137049E+12 | 0.480200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.267169E+10 | 0.479553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.357407E+10 | 0.257073E+11 | 0.263741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.304088E+10 | 0.251766E+09 | 0.345081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275343E+10 | 0.138556E+10 | 0.188001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310140E+10 | 0.389636E+10 | 0.112835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295011E+10 | 0.674530E+10 | 34793363.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307114E+10 | 0.113851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.299549E+10 | 0.162866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.302575E+10 | 0.191033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310140E+10 | 0.206854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295011E+10 | 0.136533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304088E+10 | 0.706376E+10 | 10250289.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295011E+10 | 0.324267E+10 | 0.151769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302575E+10 | 0.800725E+09 | 0.940784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360064E+11 | 0.104500E+12 | 0.658126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.275343E+10 | 0.251766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.310140E+10 | 0.206854E+11 | 0.345081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.304970E+10 | 0.224240E+09 | 0.365759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276142E+10 | 0.132822E+10 | 0.197864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311039E+10 | 0.382307E+10 | 0.131385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295866E+10 | 0.670903E+10 | 37580292.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.308004E+10 | 0.113976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.300418E+10 | 0.163744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.303452E+10 | 0.192328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.311039E+10 | 0.208177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295866E+10 | 0.137076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304970E+10 | 0.702656E+10 | 12009439.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295866E+10 | 0.315457E+10 | 0.172065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303452E+10 | 0.751448E+09 | 0.105594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361108E+11 | 0.104547E+12 | 0.704521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276142E+10 | 0.224240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.311039E+10 | 0.208177E+11 | 0.365759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.304130E+10 | 0.190112E+09 | 0.392034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275381E+10 | 0.123750E+10 | 0.211862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310182E+10 | 0.365192E+10 | 0.159574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295051E+10 | 0.652628E+10 | 42774893.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307156E+10 | 0.112130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.299591E+10 | 0.162265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.302617E+10 | 0.190971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310182E+10 | 0.206798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295051E+10 | 0.135530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304130E+10 | 0.685186E+10 | 15868770.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295051E+10 | 0.299546E+10 | 0.199737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302617E+10 | 0.681325E+09 | 0.119590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360114E+11 | 0.102904E+12 | 0.765282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.275381E+10 | 0.190112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.310182E+10 | 0.206798E+11 | 0.392034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.506923E+10 | 0.200716E+09 | 0.819690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.461828E+10 | 0.184285E+10 | 0.450887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.517619E+10 | 0.592612E+10 | 0.446615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.491670E+10 | 0.112518E+11 | 83787072.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.512156E+10 | 0.199519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.499864E+10 | 0.296140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.503961E+10 | 0.346991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.517619E+10 | 0.376954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.491670E+10 | 0.241729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.506693E+10 | 0.117683E+11 | 61767983.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.491670E+10 | 0.464096E+10 | 0.497287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.503961E+10 | 0.979183E+09 | 0.270307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.600563E+11 | 0.182743E+12 | 0.164983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.461828E+10 | 0.200716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.517619E+10 | 0.376954E+11 | 0.819690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.269079E+10 | 95197361.25 | 0.427926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245058E+10 | 0.937802E+09 | 0.235212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274748E+10 | 0.302109E+10 | 0.230766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260974E+10 | 0.575910E+10 | 42776534.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271848E+10 | 0.102412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.265324E+10 | 0.152014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.267498E+10 | 0.178218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.274748E+10 | 0.193601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.260974E+10 | 0.124367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268948E+10 | 0.604988E+10 | 30927137.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260974E+10 | 0.238175E+10 | 0.254181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267498E+10 | 0.493600E+09 | 0.141926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318767E+11 | 0.937998E+11 | 0.860929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.245058E+10 | 95197361.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274748E+10 | 0.193601E+11 | 0.427926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.268643E+10 | 88167939.61 | 0.435251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244801E+10 | 0.907293E+09 | 0.239824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274318E+10 | 0.294758E+10 | 0.248535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260566E+10 | 0.566846E+10 | 45812265.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271422E+10 | 0.101412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264908E+10 | 0.151163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.267080E+10 | 0.177354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.274318E+10 | 0.192727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.260566E+10 | 0.123602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268527E+10 | 0.597806E+10 | 33811026.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260566E+10 | 0.232686E+10 | 0.271008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267080E+10 | 0.475207E+09 | 0.146920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318279E+11 | 0.930174E+11 | 0.881911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244801E+10 | 88167939.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274318E+10 | 0.192727E+11 | 0.435251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271584E+10 | 77383150.27 | 0.457961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248060E+10 | 0.855054E+09 | 0.255857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277065E+10 | 0.281505E+10 | 0.300259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263175E+10 | 0.550674E+10 | 57290358.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274141E+10 | 0.100195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267562E+10 | 0.151214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.269755E+10 | 0.177820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.277065E+10 | 0.193441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.263175E+10 | 0.123685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271217E+10 | 0.591123E+10 | 42161235.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263175E+10 | 0.224989E+10 | 0.313839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269755E+10 | 0.447162E+09 | 0.160399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321573E+11 | 0.924980E+11 | 0.945572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.248060E+10 | 77383150.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.277065E+10 | 0.193441E+11 | 0.457961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.339351E+10 | 76453963.99 | 0.590149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309343E+10 | 0.861550E+09 | 0.350841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335346E+10 | 0.277484E+10 | 0.521988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.318534E+10 | 0.561327E+10 | 0.122003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331807E+10 | 0.105711E+11 | 1426142.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.323843E+10 | 0.164625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.326498E+10 | 0.194455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.335346E+10 | 0.211840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318534E+10 | 0.134815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.328267E+10 | 0.636387E+10 | 76948400.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318534E+10 | 0.235125E+10 | 0.482797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327047E+10 | 0.451248E+09 | 0.210785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391245E+11 | 0.996372E+11 | 0.127229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.309343E+10 | 76453963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.339351E+10 | 0.211840E+11 | 0.590149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.716283E+10 | 0.00 | 0.00 | 0.390967E+10 | 0.167114E+09 | 0.115465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.647961E+10 | 0.00 | 0.00 | 0.210223E+10 | 0.929700E+09 | 0.149751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.715045E+10 | 0.00 | 0.00 | 0.148155E+09 | 0.258492E+10 | 389619.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.689609E+10 | 0.00 | 0.00 | 35588305.37 | 0.466563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.712219E+10 | 0.00 | 0.00 | 0.00 | 0.771726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.692435E+10 | 0.00 | 0.00 | 0.00 | 0.110852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.712219E+10 | 0.00 | 0.00 | 0.00 | 0.133028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.713632E+10 | 0.00 | 0.00 | 0.00 | 0.139623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.691022E+10 | 0.00 | 0.00 | 0.00 | 0.929661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.712219E+10 | 0.00 | 0.00 | 11646509.80 | 0.483490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.688424E+10 | 0.00 | 0.00 | 0.180524E+09 | 0.223259E+10 | 5855702.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715922E+10 | 0.00 | 0.00 | 0.962054E+09 | 0.469939E+09 | 25447277.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840699E+11 | 0.00 | 0.00 | 0.734987E+10 | 0.712490E+11 | 0.296908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.647961E+10 | 0.00 | 0.00 | 0.00 | 0.167114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.716283E+10 | 0.00 | 0.00 | 0.390967E+10 | 0.139623E+11 | 0.149751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.287757E+10 | 0.00 | 0.00 | 0.120645E+10 | 0.135644E+09 | 34978897.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267169E+10 | 0.00 | 0.00 | 0.620860E+09 | 0.614877E+09 | 28693920.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310047E+10 | 0.00 | 0.00 | 26507625.89 | 0.154350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307087E+10 | 0.00 | 0.00 | 6489120.41 | 0.250907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.330256E+10 | 0.00 | 0.00 | 0.00 | 0.387772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.334097E+10 | 0.00 | 0.00 | 0.00 | 0.537296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.352883E+10 | 0.00 | 0.00 | 0.00 | 0.640435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.357407E+10 | 0.00 | 0.00 | 0.00 | 0.668287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327911E+10 | 0.00 | 0.00 | 0.00 | 0.452831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.319070E+10 | 0.00 | 0.00 | 2142387.58 | 0.257389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296009E+10 | 0.00 | 0.00 | 39104737.08 | 0.133967E+10 | 986230.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289130E+10 | 0.00 | 0.00 | 0.219033E+09 | 0.374574E+09 | 5360175.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377882E+11 | 0.00 | 0.00 | 0.212059E+10 | 0.359574E+11 | 70019223.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.267169E+10 | 0.00 | 0.00 | 0.00 | 0.135644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.357407E+10 | 0.00 | 0.00 | 0.120645E+10 | 0.668287E+10 | 34978897.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.304088E+10 | 0.00 | 0.00 | 0.153894E+10 | 71502502.47 | 44642419.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275343E+10 | 0.00 | 0.00 | 0.796207E+09 | 0.378601E+09 | 39866904.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310140E+10 | 0.00 | 0.00 | 42161330.73 | 0.104936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295011E+10 | 0.00 | 0.00 | 14629486.31 | 0.180494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307114E+10 | 0.00 | 0.00 | 0.00 | 0.297198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.299549E+10 | 0.00 | 0.00 | 0.00 | 0.427496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.302575E+10 | 0.00 | 0.00 | 0.00 | 0.500723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310140E+10 | 0.00 | 0.00 | 0.00 | 0.536326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295011E+10 | 0.00 | 0.00 | 0.00 | 0.348994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304088E+10 | 0.00 | 0.00 | 4170612.15 | 0.182516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295011E+10 | 0.00 | 0.00 | 73056803.48 | 0.868902E+09 | 1904010.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302575E+10 | 0.00 | 0.00 | 0.378626E+09 | 0.218454E+09 | 7873834.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360064E+11 | 0.00 | 0.00 | 0.284779E+10 | 0.273243E+11 | 94287168.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.275343E+10 | 0.00 | 0.00 | 0.00 | 71502502.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.310140E+10 | 0.00 | 0.00 | 0.153894E+10 | 0.536326E+10 | 44642419.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.304970E+10 | 0.00 | 0.00 | 0.161533E+10 | 63850824.11 | 50050543.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276142E+10 | 0.00 | 0.00 | 0.832529E+09 | 0.363712E+09 | 44059324.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311039E+10 | 0.00 | 0.00 | 48741927.98 | 0.103083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295866E+10 | 0.00 | 0.00 | 15681585.03 | 0.179674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.308004E+10 | 0.00 | 0.00 | 0.00 | 0.297586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.300418E+10 | 0.00 | 0.00 | 0.00 | 0.429646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.303452E+10 | 0.00 | 0.00 | 0.00 | 0.503894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.311039E+10 | 0.00 | 0.00 | 0.00 | 0.539557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295866E+10 | 0.00 | 0.00 | 0.00 | 0.350316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304970E+10 | 0.00 | 0.00 | 4804015.35 | 0.181637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295866E+10 | 0.00 | 0.00 | 80907199.36 | 0.846582E+09 | 1978590.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303452E+10 | 0.00 | 0.00 | 0.419264E+09 | 0.205189E+09 | 10124744.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361108E+11 | 0.00 | 0.00 | 0.301726E+10 | 0.273333E+11 | 0.106213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276142E+10 | 0.00 | 0.00 | 0.00 | 63850824.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.311039E+10 | 0.00 | 0.00 | 0.161533E+10 | 0.539557E+10 | 50050543.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.304130E+10 | 0.00 | 0.00 | 0.171483E+10 | 54290639.75 | 53263899.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275381E+10 | 0.00 | 0.00 | 0.884472E+09 | 0.339676E+09 | 48299743.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310182E+10 | 0.00 | 0.00 | 58742708.66 | 0.986784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295051E+10 | 0.00 | 0.00 | 17622795.25 | 0.175137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307156E+10 | 0.00 | 0.00 | 0.00 | 0.293264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.299591E+10 | 0.00 | 0.00 | 0.00 | 0.426058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.302617E+10 | 0.00 | 0.00 | 0.00 | 0.500516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310182E+10 | 0.00 | 0.00 | 0.00 | 0.536134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295051E+10 | 0.00 | 0.00 | 0.00 | 0.346708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304130E+10 | 0.00 | 0.00 | 6176301.89 | 0.177333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295051E+10 | 0.00 | 0.00 | 91295561.77 | 0.805674E+09 | 2518627.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302617E+10 | 0.00 | 0.00 | 0.468775E+09 | 0.186248E+09 | 11879298.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360114E+11 | 0.00 | 0.00 | 0.324192E+10 | 0.269242E+11 | 0.115962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.275381E+10 | 0.00 | 0.00 | 0.00 | 54290639.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.310182E+10 | 0.00 | 0.00 | 0.171483E+10 | 0.536134E+10 | 53263899.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.506923E+10 | 0.00 | 0.00 | 0.341296E+10 | 61266699.08 | 0.133234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.461828E+10 | 0.00 | 0.00 | 0.178232E+10 | 0.541499E+09 | 0.146489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.517619E+10 | 0.00 | 0.00 | 0.156961E+09 | 0.171285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.491670E+10 | 0.00 | 0.00 | 29512931.57 | 0.322495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.512156E+10 | 0.00 | 0.00 | 0.00 | 0.556500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.499864E+10 | 0.00 | 0.00 | 0.00 | 0.828797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.503961E+10 | 0.00 | 0.00 | 0.00 | 0.969560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.517619E+10 | 0.00 | 0.00 | 0.00 | 0.104180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.491670E+10 | 0.00 | 0.00 | 0.00 | 0.658683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.506693E+10 | 0.00 | 0.00 | 21712566.47 | 0.324372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.491670E+10 | 0.00 | 0.00 | 0.194019E+09 | 0.133423E+10 | 6398061.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.503961E+10 | 0.00 | 0.00 | 0.989971E+09 | 0.286051E+09 | 25882294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.600563E+11 | 0.00 | 0.00 | 0.658746E+10 | 0.509579E+11 | 0.312003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.461828E+10 | 0.00 | 0.00 | 0.00 | 61266699.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.517619E+10 | 0.00 | 0.00 | 0.341296E+10 | 0.104180E+11 | 0.146489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.269079E+10 | 0.00 | 0.00 | 0.179088E+10 | 27383688.53 | 66102274.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245058E+10 | 0.00 | 0.00 | 0.934028E+09 | 0.259880E+09 | 73349701.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274748E+10 | 0.00 | 0.00 | 81326905.55 | 0.824362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260974E+10 | 0.00 | 0.00 | 15141193.96 | 0.155957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271848E+10 | 0.00 | 0.00 | 0.00 | 0.270157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.265324E+10 | 0.00 | 0.00 | 0.00 | 0.401582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.267498E+10 | 0.00 | 0.00 | 0.00 | 0.469542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.274748E+10 | 0.00 | 0.00 | 0.00 | 0.504497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.260974E+10 | 0.00 | 0.00 | 0.00 | 0.320113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268948E+10 | 0.00 | 0.00 | 10930472.66 | 0.157527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260974E+10 | 0.00 | 0.00 | 0.100380E+09 | 0.646005E+09 | 3038097.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267498E+10 | 0.00 | 0.00 | 0.521850E+09 | 0.135997E+09 | 12822563.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318767E+11 | 0.00 | 0.00 | 0.345454E+10 | 0.246874E+11 | 0.155313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.245058E+10 | 0.00 | 0.00 | 0.00 | 27383688.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274748E+10 | 0.00 | 0.00 | 0.179088E+10 | 0.504497E+10 | 73349701.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.268643E+10 | 0.00 | 0.00 | 0.181660E+10 | 25376719.18 | 68626257.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244801E+10 | 0.00 | 0.00 | 0.951549E+09 | 0.251756E+09 | 74270542.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274318E+10 | 0.00 | 0.00 | 87332330.90 | 0.805320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260566E+10 | 0.00 | 0.00 | 16166349.00 | 0.153711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271422E+10 | 0.00 | 0.00 | 0.00 | 0.267843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264908E+10 | 0.00 | 0.00 | 0.00 | 0.399492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.267080E+10 | 0.00 | 0.00 | 0.00 | 0.467334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.274318E+10 | 0.00 | 0.00 | 0.00 | 0.502279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.260566E+10 | 0.00 | 0.00 | 0.00 | 0.318340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268527E+10 | 0.00 | 0.00 | 11899865.52 | 0.155787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260566E+10 | 0.00 | 0.00 | 0.106209E+09 | 0.631828E+09 | 3386522.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267080E+10 | 0.00 | 0.00 | 0.539019E+09 | 0.131075E+09 | 13125847.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318279E+11 | 0.00 | 0.00 | 0.352878E+10 | 0.244932E+11 | 0.159409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244801E+10 | 0.00 | 0.00 | 0.00 | 25376719.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274318E+10 | 0.00 | 0.00 | 0.181660E+10 | 0.502279E+10 | 74270542.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271584E+10 | 0.00 | 0.00 | 0.190192E+10 | 22303148.65 | 73883166.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248060E+10 | 0.00 | 0.00 | 0.100770E+10 | 0.237926E+09 | 88067552.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277065E+10 | 0.00 | 0.00 | 0.104654E+09 | 0.771485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263175E+10 | 0.00 | 0.00 | 19957744.73 | 0.149833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274141E+10 | 0.00 | 0.00 | 0.00 | 0.265335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267562E+10 | 0.00 | 0.00 | 0.00 | 0.399946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.269755E+10 | 0.00 | 0.00 | 0.00 | 0.468784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.277065E+10 | 0.00 | 0.00 | 0.00 | 0.504344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.263175E+10 | 0.00 | 0.00 | 0.00 | 0.318863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271217E+10 | 0.00 | 0.00 | 14699249.90 | 0.154285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263175E+10 | 0.00 | 0.00 | 0.121435E+09 | 0.612302E+09 | 3738567.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269755E+10 | 0.00 | 0.00 | 0.584899E+09 | 0.123616E+09 | 15364885.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321573E+11 | 0.00 | 0.00 | 0.375526E+10 | 0.243815E+11 | 0.181054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.248060E+10 | 0.00 | 0.00 | 0.00 | 22303148.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.277065E+10 | 0.00 | 0.00 | 0.190192E+10 | 0.504344E+10 | 88067552.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.339351E+10 | 0.00 | 0.00 | 0.249245E+10 | 22124672.33 | 82997619.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309343E+10 | 0.00 | 0.00 | 0.140653E+10 | 0.241984E+09 | 0.118313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335346E+10 | 0.00 | 0.00 | 0.177757E+09 | 0.771380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.318534E+10 | 0.00 | 0.00 | 40740045.12 | 0.155248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331807E+10 | 0.00 | 0.00 | 467401.99 | 0.284739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.323843E+10 | 0.00 | 0.00 | 0.00 | 0.439368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.326498E+10 | 0.00 | 0.00 | 0.00 | 0.515465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.335346E+10 | 0.00 | 0.00 | 0.00 | 0.555310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318534E+10 | 0.00 | 0.00 | 0.00 | 0.351649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.328267E+10 | 0.00 | 0.00 | 26302954.02 | 0.168241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318534E+10 | 0.00 | 0.00 | 0.180895E+09 | 0.646441E+09 | 6917965.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327047E+10 | 0.00 | 0.00 | 0.764339E+09 | 0.125951E+09 | 23638671.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391245E+11 | 0.00 | 0.00 | 0.508948E+10 | 0.265081E+11 | 0.231867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.309343E+10 | 0.00 | 0.00 | 0.00 | 22124672.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.339351E+10 | 0.00 | 0.00 | 0.249245E+10 | 0.555310E+10 | 0.118313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.721486E+10 | 0.00 | 0.00 | 731539.44 | 0.00 | 0.727078E+10 | 0.770605E+09 | 0.00 | 0.56 |
February | 0.441924E+10 | 1471808.86 | 0.00 | 4641926.92 | 0.00 | 0.444447E+10 | 0.215784E+10 | 0.00 | 0.56 |
March | 0.309078E+10 | 0.246916E+09 | 0.00 | 8817463.74 | 0.00 | 0.384110E+09 | 0.419200E+10 | 0.00 | 0.57 |
April | 0.121925E+10 | 0.821430E+09 | 0.00 | 8427413.67 | 0.00 | 0.105267E+09 | 0.243014E+10 | 0.00 | 0.57 |
May | 0.208107E+09 | 0.355599E+10 | 0.00 | 4672467.22 | 2927259.69 | 0.00 | 0.819470E+09 | 0.00 | 0.57 |
June | 36384133.51 | 0.951919E+10 | 0.00 | 2459855.05 | 50209913.80 | 0.00 | 0.265739E+09 | 0.00 | 0.57 |
July | 591630.85 | 0.135883E+11 | 0.00 | 165988.71 | 85215364.64 | 0.00 | 13056010.90 | 0.00 | 0.57 |
August | 1640726.78 | 0.151148E+11 | 0.00 | 52697.64 | 97104989.44 | 0.00 | 3269898.62 | 0.00 | 0.57 |
September | 51384440.31 | 0.686641E+10 | 0.00 | 3661058.74 | 42140465.64 | 0.00 | 0.535017E+09 | 0.00 | 0.57 |
October | 0.167517E+10 | 0.168821E+10 | 0.00 | 11697406.76 | 848518.97 | 24184446.77 | 0.378801E+10 | 0.00 | 0.57 |
November | 0.400214E+10 | 0.149880E+09 | 0.00 | 8551154.34 | 1730298.67 | 0.230470E+09 | 0.411794E+10 | 0.00 | 0.56 |
December | 0.883009E+10 | 3423066.04 | 0.00 | 2017809.62 | 0.00 | 0.186531E+10 | 0.151911E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.307496E+11 | 0.515560E+11 | 0.00 | 55896781.84 | 0.280177E+09 | 0.143246E+11 | 0.206122E+11 | 0.00 | 0.57 |
Minimum of Months | 591630.85 | 0.00 | 0.00 | 52697.64 | 0.00 | 0.00 | 3269898.62 | 0.00 | 0.56 |
Maximum of Months | 0.883009E+10 | 0.151148E+11 | 0.00 | 11697406.76 | 97104989.44 | 0.727078E+10 | 0.419200E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.315707E+10 | 0.00 | 0.00 | 634818.55 | 0.00 | 0.224976E+10 | 0.319192E+09 | 0.00 | 0.42 |
February | 0.192619E+10 | 705828.53 | 0.00 | 3229589.78 | 0.00 | 0.132711E+10 | 0.843109E+09 | 0.00 | 0.43 |
March | 0.119368E+10 | 0.128806E+09 | 0.00 | 5866929.68 | 214025.98 | 53380115.94 | 0.175019E+10 | 0.00 | 0.45 |
April | 0.383642E+09 | 0.433009E+09 | 0.00 | 5080798.35 | 886277.75 | 21466018.82 | 0.968632E+09 | 0.00 | 0.46 |
May | 71903155.96 | 0.178377E+10 | 0.00 | 2442178.64 | 7914173.56 | 0.00 | 0.253691E+09 | 0.00 | 0.49 |
June | 3926489.37 | 0.457635E+10 | 0.00 | 1342670.83 | 36842000.43 | 0.00 | 0.106353E+09 | 0.00 | 0.51 |
July | 0.00 | 0.656001E+10 | 0.00 | 8377.45 | 47057111.36 | 0.00 | 48543.01 | 0.00 | 0.52 |
August | 21414.82 | 0.726370E+10 | 0.00 | 16804.47 | 47812923.11 | 0.00 | 59085.62 | 0.00 | 0.53 |
September | 12031875.60 | 0.328285E+10 | 0.00 | 1920181.94 | 33200291.52 | 0.00 | 0.153559E+09 | 0.00 | 0.50 |
October | 0.604535E+09 | 0.827660E+09 | 0.00 | 6890178.67 | 2004939.75 | 512857.14 | 0.146088E+10 | 0.00 | 0.47 |
November | 0.142258E+10 | 80874965.24 | 0.00 | 5365483.34 | 1005338.85 | 73895201.30 | 0.168968E+10 | 0.00 | 0.45 |
December | 0.305598E+10 | 4606700.22 | 0.00 | 1815268.75 | 0.00 | 0.479744E+09 | 0.981787E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.118316E+11 | 0.249424E+11 | 0.00 | 34613280.44 | 0.176937E+09 | 0.420587E+10 | 0.852718E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8377.45 | 0.00 | 0.00 | 48543.01 | 0.00 | 0.42 |
Maximum of Months | 0.315707E+10 | 0.726370E+10 | 0.00 | 6890178.67 | 47812923.11 | 0.224976E+10 | 0.175019E+10 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277366E+10 | 0.00 | 0.00 | 269917.68 | 0.00 | 0.287190E+10 | 0.236357E+09 | 0.00 | 0.44 |
February | 0.188249E+10 | 842886.94 | 0.00 | 1774926.44 | 0.00 | 0.172798E+10 | 0.610308E+09 | 0.00 | 0.45 |
March | 0.167596E+10 | 0.110032E+09 | 0.00 | 3213808.83 | 3441335.18 | 62826439.53 | 0.129628E+10 | 0.00 | 0.46 |
April | 0.635705E+09 | 0.359574E+09 | 0.00 | 2789163.84 | 11489667.34 | 27197752.06 | 0.881289E+09 | 0.00 | 0.45 |
May | 0.155986E+09 | 0.143696E+10 | 0.00 | 2061264.33 | 50938322.89 | 0.00 | 0.313761E+09 | 0.00 | 0.46 |
June | 24523872.34 | 0.372126E+10 | 0.00 | 1087948.22 | 0.206777E+09 | 0.00 | 0.121081E+09 | 0.00 | 0.46 |
July | 2606177.52 | 0.504195E+10 | 0.00 | 409479.86 | 0.306515E+09 | 0.00 | 6319678.43 | 0.00 | 0.45 |
August | 1130019.94 | 0.565178E+10 | 0.00 | 256718.90 | 0.358574E+09 | 0.00 | 3991678.30 | 0.00 | 0.46 |
September | 59724123.68 | 0.253559E+10 | 0.00 | 1482504.20 | 0.141963E+09 | 0.00 | 0.204735E+09 | 0.00 | 0.46 |
October | 0.970162E+09 | 0.648613E+09 | 0.00 | 4378262.34 | 33212222.01 | 0.00 | 0.123635E+10 | 0.00 | 0.45 |
November | 0.187942E+10 | 54400797.37 | 0.00 | 3318785.38 | 5644724.24 | 0.116657E+09 | 0.126334E+10 | 0.00 | 0.45 |
December | 0.317027E+10 | 3670298.73 | 0.00 | 857853.41 | 0.00 | 0.801493E+09 | 0.642045E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.132316E+11 | 0.195647E+11 | 0.00 | 21900633.43 | 0.111855E+10 | 0.560805E+10 | 0.681586E+10 | 0.00 | 0.45 |
Minimum of Months | 1130019.94 | 0.00 | 0.00 | 256718.90 | 0.00 | 0.00 | 3991678.30 | 0.00 | 0.44 |
Maximum of Months | 0.317027E+10 | 0.565178E+10 | 0.00 | 4378262.34 | 0.358574E+09 | 0.287190E+10 | 0.129628E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254409E+10 | 0.00 | 0.00 | 227528.92 | 0.00 | 0.310341E+10 | 0.224314E+09 | 0.00 | 0.44 |
February | 0.182057E+10 | 844470.44 | 0.00 | 1676256.84 | 0.00 | 0.180670E+10 | 0.587123E+09 | 0.00 | 0.45 |
March | 0.169082E+10 | 0.108852E+09 | 0.00 | 3105616.95 | 3399814.97 | 78767688.52 | 0.125896E+10 | 0.00 | 0.46 |
April | 0.642479E+09 | 0.357425E+09 | 0.00 | 2746993.54 | 11367158.77 | 30036049.17 | 0.871205E+09 | 0.00 | 0.45 |
May | 0.164293E+09 | 0.143471E+10 | 0.00 | 2065512.27 | 50654927.77 | 0.00 | 0.306362E+09 | 0.00 | 0.46 |
June | 22438003.01 | 0.372756E+10 | 0.00 | 1113043.89 | 0.203718E+09 | 0.00 | 0.122904E+09 | 0.00 | 0.46 |
July | 2607631.03 | 0.505551E+10 | 0.00 | 446090.60 | 0.300312E+09 | 0.00 | 6301401.27 | 0.00 | 0.45 |
August | 1133056.93 | 0.566470E+10 | 0.00 | 269567.67 | 0.353715E+09 | 0.00 | 3945326.66 | 0.00 | 0.46 |
September | 59761890.62 | 0.253754E+10 | 0.00 | 1498575.37 | 0.140161E+09 | 0.00 | 0.204921E+09 | 0.00 | 0.46 |
October | 0.983151E+09 | 0.645936E+09 | 0.00 | 4315187.22 | 32980211.15 | 1422306.57 | 0.121987E+10 | 0.00 | 0.45 |
November | 0.189638E+10 | 51827603.37 | 0.00 | 3184514.81 | 5895989.42 | 0.136695E+09 | 0.121663E+10 | 0.00 | 0.45 |
December | 0.310494E+10 | 3135083.58 | 0.00 | 782958.45 | 0.00 | 0.925775E+09 | 0.563093E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.129327E+11 | 0.195880E+11 | 0.00 | 21431846.54 | 0.110220E+10 | 0.608280E+10 | 0.658563E+10 | 0.00 | 0.45 |
Minimum of Months | 1133056.93 | 0.00 | 0.00 | 227528.92 | 0.00 | 0.00 | 3945326.66 | 0.00 | 0.44 |
Maximum of Months | 0.310494E+10 | 0.566470E+10 | 0.00 | 4315187.22 | 0.353715E+09 | 0.310341E+10 | 0.125896E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231404E+10 | 0.00 | 0.00 | 180992.41 | 0.00 | 0.335023E+10 | 0.198505E+09 | 0.00 | 0.44 |
February | 0.176046E+10 | 843255.68 | 0.00 | 1531389.88 | 0.00 | 0.189658E+10 | 0.550054E+09 | 0.00 | 0.45 |
March | 0.171859E+10 | 0.106587E+09 | 0.00 | 2883141.66 | 3388874.41 | 0.129065E+09 | 0.117049E+10 | 0.00 | 0.46 |
April | 0.677110E+09 | 0.352789E+09 | 0.00 | 2587903.58 | 11323460.24 | 39265105.88 | 0.827247E+09 | 0.00 | 0.45 |
May | 0.167900E+09 | 0.142528E+10 | 0.00 | 1979450.01 | 50719010.46 | 0.00 | 0.306822E+09 | 0.00 | 0.46 |
June | 32280438.62 | 0.371749E+10 | 0.00 | 1069492.00 | 0.206176E+09 | 0.00 | 0.113488E+09 | 0.00 | 0.46 |
July | 2643211.76 | 0.504151E+10 | 0.00 | 439737.76 | 0.305939E+09 | 0.00 | 6621959.96 | 0.00 | 0.45 |
August | 1134354.27 | 0.565431E+10 | 0.00 | 258223.82 | 0.356755E+09 | 0.00 | 4046140.64 | 0.00 | 0.46 |
September | 64333671.62 | 0.252586E+10 | 0.00 | 1461146.54 | 0.142734E+09 | 0.00 | 0.203453E+09 | 0.00 | 0.46 |
October | 0.103279E+10 | 0.640280E+09 | 0.00 | 4103250.50 | 33071861.96 | 1419223.82 | 0.116816E+10 | 0.00 | 0.45 |
November | 0.195016E+10 | 48751382.12 | 0.00 | 2959503.82 | 6108013.73 | 0.146536E+09 | 0.114104E+10 | 0.00 | 0.45 |
December | 0.303704E+10 | 2415980.97 | 0.00 | 681640.72 | 0.00 | 0.107774E+10 | 0.452839E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.127585E+11 | 0.195161E+11 | 0.00 | 20135872.70 | 0.111621E+10 | 0.664084E+10 | 0.614277E+10 | 0.00 | 0.45 |
Minimum of Months | 1134354.27 | 0.00 | 0.00 | 180992.41 | 0.00 | 0.00 | 4046140.64 | 0.00 | 0.44 |
Maximum of Months | 0.303704E+10 | 0.565431E+10 | 0.00 | 4103250.50 | 0.356755E+09 | 0.335023E+10 | 0.117049E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308672E+10 | 0.00 | 0.00 | 178406.88 | 0.00 | 0.752343E+10 | 0.288499E+09 | 0.00 | 0.41 |
February | 0.254975E+10 | 0.00 | 0.00 | 2335496.82 | 0.00 | 0.425990E+10 | 0.108001E+10 | 0.00 | 0.42 |
March | 0.289758E+10 | 0.171763E+09 | 0.00 | 4902889.18 | 0.00 | 0.359481E+09 | 0.229983E+10 | 0.00 | 0.42 |
April | 0.996504E+09 | 0.555480E+09 | 0.00 | 4514162.84 | 11797852.12 | 70187390.94 | 0.154786E+10 | 0.00 | 0.42 |
May | 0.203167E+09 | 0.265401E+10 | 0.00 | 3161362.10 | 47549180.07 | 0.00 | 0.516510E+09 | 0.00 | 0.42 |
June | 43665065.20 | 0.731001E+10 | 0.00 | 1828783.01 | 0.155277E+09 | 0.00 | 0.159919E+09 | 0.00 | 0.43 |
July | 997498.84 | 0.980097E+10 | 0.00 | 441506.56 | 0.281467E+09 | 0.00 | 10386811.53 | 0.00 | 0.42 |
August | 1384622.19 | 0.110511E+11 | 0.00 | 112930.70 | 0.250386E+09 | 0.00 | 1765127.56 | 0.00 | 0.43 |
September | 82258649.93 | 0.477601E+10 | 0.00 | 2233343.97 | 0.148257E+09 | 0.00 | 0.338261E+09 | 0.00 | 0.42 |
October | 0.178448E+10 | 0.120099E+10 | 0.00 | 6513169.48 | 21321028.14 | 57132602.07 | 0.210963E+10 | 0.00 | 0.42 |
November | 0.347855E+10 | 50953827.19 | 0.00 | 4695607.06 | 10140558.53 | 0.268336E+09 | 0.216666E+10 | 0.00 | 0.42 |
December | 0.526752E+10 | 263765.26 | 0.00 | 1015743.69 | 0.00 | 0.240538E+10 | 0.678698E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.203926E+11 | 0.375716E+11 | 0.00 | 31933402.30 | 0.926194E+09 | 0.149438E+11 | 0.111980E+11 | 0.00 | 0.42 |
Minimum of Months | 997498.84 | 0.00 | 0.00 | 112930.70 | 0.00 | 0.00 | 1765127.56 | 0.00 | 0.41 |
Maximum of Months | 0.526752E+10 | 0.110511E+11 | 0.00 | 6513169.48 | 0.281467E+09 | 0.752343E+10 | 0.229983E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137013E+10 | 0.00 | 0.00 | 74538.46 | 0.00 | 0.394690E+10 | 0.118773E+09 | 0.00 | 0.41 |
February | 0.123341E+10 | 0.00 | 0.00 | 1130781.96 | 0.00 | 0.218917E+10 | 0.507175E+09 | 0.00 | 0.42 |
March | 0.142032E+10 | 85743495.49 | 0.00 | 2365610.86 | 0.00 | 0.236851E+09 | 0.110739E+10 | 0.00 | 0.42 |
April | 0.530623E+09 | 0.276003E+09 | 0.00 | 2189134.46 | 5776495.07 | 42680540.59 | 0.729361E+09 | 0.00 | 0.42 |
May | 0.109171E+09 | 0.132139E+10 | 0.00 | 1551727.35 | 23303058.48 | 0.00 | 0.250666E+09 | 0.00 | 0.42 |
June | 23459896.12 | 0.364517E+10 | 0.00 | 896431.80 | 77652394.73 | 0.00 | 78308813.31 | 0.00 | 0.43 |
July | 586828.08 | 0.489485E+10 | 0.00 | 217268.26 | 0.130885E+09 | 0.00 | 5272738.40 | 0.00 | 0.42 |
August | 609880.28 | 0.551657E+10 | 0.00 | 53566.32 | 0.117683E+09 | 0.00 | 1040199.81 | 0.00 | 0.43 |
September | 41990842.25 | 0.238162E+10 | 0.00 | 1110858.12 | 72495419.61 | 0.00 | 0.168936E+09 | 0.00 | 0.42 |
October | 0.915803E+09 | 0.597762E+09 | 0.00 | 3235866.72 | 10480441.15 | 34215493.76 | 0.102122E+10 | 0.00 | 0.42 |
November | 0.172627E+10 | 24827916.38 | 0.00 | 2317025.09 | 5234288.91 | 0.158934E+09 | 0.105971E+10 | 0.00 | 0.42 |
December | 0.253684E+10 | 104254.45 | 0.00 | 473179.97 | 0.00 | 0.132403E+10 | 0.297932E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.990922E+10 | 0.187440E+11 | 0.00 | 15615989.39 | 0.443510E+09 | 0.793279E+10 | 0.534579E+10 | 0.00 | 0.42 |
Minimum of Months | 586828.08 | 0.00 | 0.00 | 53566.32 | 0.00 | 0.00 | 1040199.81 | 0.00 | 0.41 |
Maximum of Months | 0.253684E+10 | 0.551657E+10 | 0.00 | 3235866.72 | 0.130885E+09 | 0.394690E+10 | 0.110739E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131972E+10 | 0.00 | 0.00 | 67738.85 | 0.00 | 0.400148E+10 | 0.111967E+09 | 0.00 | 0.41 |
February | 0.121654E+10 | 0.00 | 0.00 | 1082480.33 | 0.00 | 0.222215E+10 | 0.491673E+09 | 0.00 | 0.42 |
March | 0.142311E+10 | 85109900.10 | 0.00 | 2268252.64 | 0.00 | 0.253293E+09 | 0.108307E+10 | 0.00 | 0.42 |
April | 0.548431E+09 | 0.273989E+09 | 0.00 | 2115769.74 | 5744152.82 | 46114720.24 | 0.706747E+09 | 0.00 | 0.42 |
May | 0.116415E+09 | 0.131510E+10 | 0.00 | 1515129.30 | 23693962.09 | 0.00 | 0.244762E+09 | 0.00 | 0.42 |
June | 23224489.39 | 0.363911E+10 | 0.00 | 881521.88 | 78280549.36 | 0.00 | 78432524.05 | 0.00 | 0.43 |
July | 602194.85 | 0.488370E+10 | 0.00 | 211200.31 | 0.133900E+09 | 0.00 | 5504246.29 | 0.00 | 0.42 |
August | 619152.34 | 0.550834E+10 | 0.00 | 51542.82 | 0.117807E+09 | 0.00 | 1081844.80 | 0.00 | 0.43 |
September | 42495368.96 | 0.237667E+10 | 0.00 | 1097344.00 | 72265333.22 | 0.00 | 0.169730E+09 | 0.00 | 0.42 |
October | 0.934767E+09 | 0.594851E+09 | 0.00 | 3158293.21 | 10478160.51 | 41073855.68 | 0.992678E+09 | 0.00 | 0.42 |
November | 0.173729E+10 | 23987869.86 | 0.00 | 2243262.05 | 5367900.62 | 0.160723E+09 | 0.104318E+10 | 0.00 | 0.42 |
December | 0.250740E+10 | 83091.65 | 0.00 | 443163.26 | 0.00 | 0.136607E+10 | 0.277731E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.987062E+10 | 0.187009E+11 | 0.00 | 15135698.39 | 0.447537E+09 | 0.809091E+10 | 0.520655E+10 | 0.00 | 0.42 |
Minimum of Months | 602194.85 | 0.00 | 0.00 | 51542.82 | 0.00 | 0.00 | 1081844.80 | 0.00 | 0.41 |
Maximum of Months | 0.250740E+10 | 0.550834E+10 | 0.00 | 3158293.21 | 0.133900E+09 | 0.400148E+10 | 0.108307E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117227E+10 | 0.00 | 0.00 | 54936.56 | 0.00 | 0.415666E+10 | 0.104732E+09 | 0.00 | 0.41 |
February | 0.111220E+10 | 0.00 | 0.00 | 989446.70 | 0.00 | 0.236283E+10 | 0.472614E+09 | 0.00 | 0.42 |
March | 0.137973E+10 | 83050429.21 | 0.00 | 2078017.83 | 0.00 | 0.321458E+09 | 0.104763E+10 | 0.00 | 0.42 |
April | 0.570876E+09 | 0.265697E+09 | 0.00 | 1970239.95 | 5705383.87 | 69289402.02 | 0.658602E+09 | 0.00 | 0.42 |
May | 0.121081E+09 | 0.130011E+10 | 0.00 | 1448395.20 | 23240126.87 | 0.00 | 0.243596E+09 | 0.00 | 0.42 |
June | 24720169.75 | 0.363355E+10 | 0.00 | 869024.39 | 77939858.54 | 0.00 | 77246042.55 | 0.00 | 0.43 |
July | 622838.25 | 0.488029E+10 | 0.00 | 202572.45 | 0.134371E+09 | 0.00 | 5872643.26 | 0.00 | 0.42 |
August | 627402.89 | 0.551025E+10 | 0.00 | 49174.94 | 0.116927E+09 | 0.00 | 1126709.90 | 0.00 | 0.43 |
September | 50391802.74 | 0.237329E+10 | 0.00 | 1077802.28 | 72237924.77 | 0.00 | 0.164016E+09 | 0.00 | 0.42 |
October | 0.951364E+09 | 0.590674E+09 | 0.00 | 3052605.18 | 10321523.92 | 49807359.49 | 0.963299E+09 | 0.00 | 0.42 |
November | 0.170589E+10 | 22517123.79 | 0.00 | 2125072.22 | 5682314.19 | 0.213691E+09 | 0.101459E+10 | 0.00 | 0.42 |
December | 0.241096E+10 | 51448.17 | 0.00 | 398997.51 | 0.00 | 0.148154E+10 | 0.244081E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.950073E+10 | 0.186595E+11 | 0.00 | 14316285.22 | 0.446425E+09 | 0.865528E+10 | 0.499740E+10 | 0.00 | 0.42 |
Minimum of Months | 622838.25 | 0.00 | 0.00 | 49174.94 | 0.00 | 0.00 | 1126709.90 | 0.00 | 0.41 |
Maximum of Months | 0.241096E+10 | 0.551025E+10 | 0.00 | 3052605.18 | 0.134371E+09 | 0.415666E+10 | 0.104763E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.600549E+09 | 0.00 | 0.00 | 27527.22 | 0.00 | 0.492537E+10 | 58034013.95 | 0.00 | 0.42 |
February | 0.729884E+09 | 20353.24 | 0.00 | 804729.25 | 0.00 | 0.296838E+10 | 0.386611E+09 | 0.00 | 0.43 |
March | 0.122801E+10 | 79543351.73 | 0.00 | 1599552.94 | 0.00 | 0.550605E+09 | 0.936427E+09 | 0.00 | 0.42 |
April | 0.586156E+09 | 0.249372E+09 | 0.00 | 1640712.47 | 5787026.19 | 0.125289E+09 | 0.568909E+09 | 0.00 | 0.42 |
May | 0.148496E+09 | 0.127899E+10 | 0.00 | 1378361.35 | 21707390.70 | 3672986.64 | 0.235568E+09 | 0.00 | 0.42 |
June | 26819824.00 | 0.361362E+10 | 0.00 | 921275.34 | 65638171.97 | 0.00 | 73880281.92 | 0.00 | 0.43 |
July | 3918999.02 | 0.489149E+10 | 0.00 | 269406.14 | 0.118028E+09 | 0.00 | 7976975.39 | 0.00 | 0.42 |
August | 994381.46 | 0.551217E+10 | 0.00 | 164378.31 | 99216964.00 | 0.00 | 2931286.19 | 0.00 | 0.43 |
September | 71960720.84 | 0.238504E+10 | 0.00 | 1052466.07 | 68275137.10 | 0.00 | 0.152317E+09 | 0.00 | 0.42 |
October | 0.919945E+09 | 0.591914E+09 | 0.00 | 2937498.50 | 9509734.47 | 0.109159E+09 | 0.919863E+09 | 0.00 | 0.42 |
November | 0.140401E+10 | 22663978.61 | 861370.47 | 1840780.68 | 2752723.34 | 0.547303E+09 | 0.950468E+09 | 2906.96 | 0.42 |
December | 0.184774E+10 | 30595.92 | 0.00 | 297331.58 | 0.00 | 0.205842E+10 | 0.182410E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.756848E+10 | 0.186249E+11 | 861370.47 | 12934019.84 | 0.390915E+09 | 0.112882E+11 | 0.447540E+10 | 2906.96 | 0.42 |
Minimum of Months | 994381.46 | 0.00 | 0.00 | 27527.22 | 0.00 | 0.00 | 2931286.19 | 0.00 | 0.41 |
Maximum of Months | 0.184774E+10 | 0.551217E+10 | 861370.47 | 2937498.50 | 0.118028E+09 | 0.492537E+10 | 0.950468E+09 | 2906.96 | 0.43 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.212883E+12 | 0.298137E+11 | 0.00 | 0.133135E+12 | -0.570000E+18 |
February | 0.229543E+12 | 0.215348E+11 | 0.00 | 0.101267E+12 | -0.489400E+18 |
March | 0.364201E+12 | 0.138571E+11 | 0.00 | 0.737951E+11 | -0.478400E+18 |
April | 0.433135E+12 | 0.419221E+10 | 0.00 | 0.447294E+11 | -0.469000E+18 |
May | 0.491347E+12 | -0.574255E+10 | 0.00 | 0.221795E+10 | -0.498400E+18 |
June | 0.493309E+12 | -0.175926E+11 | 0.00 | -0.504549E+11 | -0.519200E+18 |
July | 0.472634E+12 | -0.242964E+11 | 0.00 | -0.834597E+11 | -0.551900E+18 |
August | 0.432527E+12 | -0.266748E+11 | 0.00 | -0.101057E+12 | -0.560200E+18 |
September | 0.322939E+12 | -0.116053E+11 | 0.00 | -0.281407E+11 | -0.502900E+18 |
October | 0.288378E+12 | 0.561793E+10 | 0.00 | 0.505727E+11 | -0.479600E+18 |
November | 0.195541E+12 | 0.143468E+11 | 0.00 | 0.836993E+11 | -0.462100E+18 |
December | 0.172612E+12 | 0.232831E+11 | 0.00 | 0.112630E+12 | -0.503300E+18 |
Annual Sum or Average | 0.410905E+13 | 0.267340E+11 | 0.00 | 0.338935E+12 | -0.608440E+19 |
Minimum of Months | 0.172612E+12 | -0.266748E+11 | 0.00 | -0.101057E+12 | -0.570000E+18 |
Maximum of Months | 0.493309E+12 | 0.298137E+11 | 0.00 | 0.133135E+12 | -0.462100E+18 |