Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2024-07-03 12:20:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 987.23 | 472.29 | 472.29 |
Net Site Energy | 987.23 | 472.29 | 472.29 |
Total Source Energy | 2870.97 | 1373.46 | 1373.46 |
Net Source Energy | 2870.97 | 1373.46 | 1373.46 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 122.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 125.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 116.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 864.53 | 122.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 122.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 125.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 116.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 122.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 125.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 116.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 128.20 | 58.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 413.59 | 58.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 128.20 | 58.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 413.59 | 58.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 864.531 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 864.531 | 100.00 |
Total On-Site and Utility Electric Sources | 864.531 | 100.00 |
Total Electricity End Uses | 864.531 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 996.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 16.9392 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.9075 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 11.2173 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 16.9392 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.9075 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 18.2679 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 11.2173 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 11.3140 | 6.19 | 4.3000 | |
Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 14.6900 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-16:10 | 06-FEB-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 125973.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 44198.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10288.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1477.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 90284.33 | 125973.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 125973.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 44198.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 10288.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1477.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 133.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 399.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1293.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 368.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 80.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2737.97 | 133.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 63.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 190.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 176.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1309.83 | 63.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 63.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 190.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 176.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1309.83 | 63.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.43 |
SMSTORE1 DIRECT AIR | 1.30 |
SMSTORE2 DIRECT AIR | 1.37 |
SMSTORE3 DIRECT AIR | 1.36 |
SMSTORE4 DIRECT AIR | 1.36 |
LGSTORE2 DIRECT AIR | 2.29 |
SMSTORE5 DIRECT AIR | 1.16 |
SMSTORE6 DIRECT AIR | 1.16 |
SMSTORE7 DIRECT AIR | 1.15 |
SMSTORE8 DIRECT AIR | 1.29 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.43 | 2.43 | 2.43 | 2.43 | 2.43 | 2.43 | 1.00 | 1.00 | 2.43 |
PSZ-AC_2:2 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.000000 | 1.30 |
PSZ-AC_3:3 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.000000 | 1.37 |
PSZ-AC_4:4 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.00 | 1.36 |
PSZ-AC_5:5 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.00 | 1.36 |
PSZ-AC_6:6 | 2.29 | 2.29 | 2.29 | 2.29 | 2.29 | 2.29 | 1.00 | 1.00 | 2.29 |
PSZ-AC_7:7 | 1.16 | 1.16 | 1.16 | 1.16 | 1.19 | 1.19 | 1.00 | 0.980739 | 1.19 |
PSZ-AC_8:8 | 1.16 | 1.16 | 1.16 | 1.16 | 1.18 | 1.18 | 1.00 | 0.981041 | 1.18 |
PSZ-AC_9:9 | 1.15 | 1.15 | 1.15 | 1.15 | 1.18 | 1.18 | 1.00 | 0.977923 | 1.18 |
PSZ-AC_10:10 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.00 | 1.00 | 1.29 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.43 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.30 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.37 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.36 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.36 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.29 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.19 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.18 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.18 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.29 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.43 | 2599.88 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1438.11 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1516.92 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.36 | 1508.39 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.36 | 1508.08 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.29 | 2449.30 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.19 | 1313.95 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.18 | 1306.87 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.18 | 1305.61 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.29 | 1430.04 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.43 | 2.43 | 2.43 | 1.60 | 40219.98 | 57562.48 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.857288 | 21501.75 | 30362.08 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 0.904265 | 22679.99 | 31700.38 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 0.899185 | 22552.58 | 31555.66 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 0.898995 | 22547.82 | 31550.25 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.29 | 2.29 | 2.29 | 1.51 | 37983.00 | 54916.24 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.19 | 1.19 | 1.19 | 0.783270 | 19645.30 | 27823.65 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.18 | 1.18 | 1.18 | 0.779054 | 19539.56 | 27712.57 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.18 | 1.18 | 1.18 | 0.778298 | 19520.60 | 27622.30 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.29 | 1.29 | 1.29 | 0.852476 | 21381.07 | 30225.33 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.43 | 1.21 | 1.62 | 40219.98 | 20109.99 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 1.30 | 0.649460 | 0.865947 | 21501.75 | 10750.88 | 0.800660 | 0.800660 |
PSZ-AC_3:3 COOLING COIL | 1.37 | 0.685049 | 0.913400 | 22679.99 | 11340.00 | 0.800660 | 0.800660 |
PSZ-AC_4:4 COOLING COIL | 1.36 | 0.681201 | 0.908267 | 22552.58 | 11276.29 | 0.800660 | 0.800660 |
PSZ-AC_5:5 COOLING COIL | 1.36 | 0.681057 | 0.908073 | 22547.82 | 11273.91 | 0.800660 | 0.800660 |
PSZ-AC_6:6 COOLING COIL | 2.29 | 1.14 | 1.53 | 37983.00 | 18991.50 | 0.800760 | 0.800760 |
PSZ-AC_7:7 COOLING COIL | 1.19 | 0.593386 | 0.791180 | 19645.30 | 9822.65 | 0.800660 | 0.800660 |
PSZ-AC_8:8 COOLING COIL | 1.18 | 0.590193 | 0.786927 | 19539.56 | 9769.78 | 0.800660 | 0.800660 |
PSZ-AC_9:9 COOLING COIL | 1.18 | 0.589620 | 0.786160 | 19520.60 | 9760.30 | 0.800660 | 0.800660 |
PSZ-AC_10:10 COOLING COIL | 1.29 | 0.645815 | 0.861087 | 21381.07 | 10690.53 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 57562.48 |
PSZ-AC_2:2 HEATING COIL | 30362.08 |
PSZ-AC_3:3 HEATING COIL | 31700.38 |
PSZ-AC_4:4 HEATING COIL | 31555.66 |
PSZ-AC_5:5 HEATING COIL | 31550.25 |
PSZ-AC_6:6 HEATING COIL | 54916.24 |
PSZ-AC_7:7 HEATING COIL | 27823.65 |
PSZ-AC_8:8 HEATING COIL | 27712.57 |
PSZ-AC_9:9 HEATING COIL | 27622.30 |
PSZ-AC_10:10 HEATING COIL | 30225.33 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 16.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.239 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.907 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.207 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3916.664 | 11.242 | 69.629 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3916.664 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1975.182 | 11.339 | 70.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1975.182 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3907.965 | 11.217 | 69.474 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.965 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.433 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34128934E-12 | 0.10473450E-14 | -0.10397207E-12 | 0.10371484E-15 |
23 | 6 | 0.30755064E-07 | 0.17217129E-09 | 0.70279215E-08 | -0.14642558E-12 |
24 | 5 | -0.20062951E-03 | 0.14545406E-05 | -0.10304618E-03 | 0.69406843E-08 |
25 | 4 | 0.30437449 | 0.69977658E-03 | 0.10408506 | -0.35305012E-04 |
26 | 3 | -7.5082928 | 0.21456968E-01 | -2.4107259 | 0.30195353E-01 |
27 | 2 | 41.668927 | 0.75582488E-01 | 15.559173 | -0.34222686 |
28 | 1 | -81.156896 | 0.33830739E-01 | -29.405205 | 1.0916426 |
29 | 0 | 46.824335 | 0.67514285E-03 | 16.285023 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 35 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.46913E-002 | 0.27318 | 0.51792 | 0.51792 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 7.082E-002 | 2.033E-004 | 1.120E-004 | 0.141 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.872E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 4.047E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 5.058E-002 | 2.904E-004 | 1.347E-004 | 0.202 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22632.85066 | 27159.42080 | 2.02474 | 2.42969 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 18752.60191 | 22503.12229 | 0.98283 | 1.17940 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90000 | 2.34317E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12099.69636 | 14519.63564 | 1.08243 | 1.29892 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8856.49992 | 10627.79990 | 0.46417 | 0.55701 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90000 | 2.34317E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 13043.18549 | 15651.82259 | 1.14175 | 1.37010 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.68796E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8969.11268 | 10762.93522 | 0.47008 | 0.56409 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90000 | 2.34317E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12971.67398 | 15566.00878 | 1.13533 | 1.36240 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.68796E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 9070.10228 | 10884.12274 | 0.47537 | 0.57044 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90000 | 2.34317E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12968.21142 | 15561.85370 | 1.13509 | 1.36211 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.68796E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9248.81471 | 11098.57766 | 0.48473 | 0.58168 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90000 | 2.34317E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21321.70341 | 25586.04410 | 1.90747 | 2.28896 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 17981.57294 | 21577.88753 | 0.94243 | 1.13092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90000 | 2.34317E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11123.47048 | 13348.16457 | 0.96993 | 1.16391 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.97000 | 5.69146E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9563.44519 | 11476.13423 | 0.50122 | 0.60147 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90000 | 2.34317E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11067.93196 | 13281.51835 | 0.96501 | 1.15801 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.97000 | 5.69146E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9562.73290 | 11475.27948 | 0.50119 | 0.60143 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90000 | 2.34317E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11022.58646 | 13227.10375 | 0.96100 | 1.15321 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.97000 | 5.69146E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 9844.15737 | 11812.98884 | 0.51594 | 0.61912 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90000 | 2.34317E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12031.37026 | 14437.64431 | 1.07636 | 1.29163 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 34.42500 | 5.69833E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 11834.18118 | 14201.01742 | 0.62022 | 0.74427 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90000 | 2.34317E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 31403.97 | 2.42969 | 2.42969 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 34054.27 | 1.17940 | 1.17940 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16620.97 | 1.29892 | 1.29892 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 16412.46 | 0.55701 | 0.55701 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16663.43 | 1.37010 | 1.37010 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16545.62 | 0.56409 | 0.56409 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16707.91 | 1.36240 | 1.36240 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16665.05 | 0.57044 | 0.57044 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16586.14 | 1.36211 | 1.36211 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16876.38 | 0.58168 | 0.58168 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 29814.89 | 2.28896 | 2.28896 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 33142.58 | 1.13092 | 1.13092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15369.77 | 1.18677 | 1.18677 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 17248.44 | 0.60147 | 0.60147 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15299.18 | 1.18039 | 1.18039 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 17247.60 | 0.60143 | 0.60143 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15284.07 | 1.17924 | 1.17924 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17580.39 | 0.61912 | 0.61912 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 16410.82 | 1.29163 | 1.29163 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 19933.57 | 0.74427 | 0.74427 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.42969 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29892 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37010 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36240 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36211 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.28896 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16391 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15801 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15321 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29163 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.42969 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.42969 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.42969 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.42969 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.42969 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.42969 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29892 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29892 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29892 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29892 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29892 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.29892 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37010 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37010 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37010 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37010 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37010 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37010 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36240 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36240 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36240 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36240 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36240 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36240 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36211 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36211 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36211 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36211 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36211 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36211 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.28896 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28896 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.28896 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28896 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.28896 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.28896 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16391 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16391 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16391 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16391 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.18677 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.18677 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98074 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15801 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15801 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15801 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15801 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.18039 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.18039 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98104 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15321 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15321 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15321 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15321 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.17924 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.17924 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.97792 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29163 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29163 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29163 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29163 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29163 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.29163 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.42969 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.29892 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.37010 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.36240 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.36211 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.28896 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.18677 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.18039 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.17924 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.29163 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.42969 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.42969 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2599.88219 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.42969 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.42969 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.42969 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.60359 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.42969 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.21484 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.61979 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40219.98000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20109.99000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40219.98000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57562.48349 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 57562.48349 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29892 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29892 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1438.11145 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29892 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29892 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29892 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85729 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29892 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64946 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86595 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21501.75000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10750.87500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21501.75000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30362.07826 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 30362.07826 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37010 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37010 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1516.91612 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37010 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37010 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37010 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90426 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37010 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68505 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91340 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22679.99000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11339.99500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22679.99000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31700.37873 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 31700.37873 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36240 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36240 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1508.39455 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36240 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36240 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36240 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89918 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36240 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68120 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.90827 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22552.58000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11276.29000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22552.58000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31555.66289 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 31555.66289 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36211 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36211 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1508.07592 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36211 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36211 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36211 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89899 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36211 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68106 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.90807 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22547.82000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11273.91000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22547.82000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31550.24965 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 31550.24965 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.28896 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.28896 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2449.30044 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.28896 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.28896 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.28896 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.51072 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.28896 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.14448 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.52597 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37983.00000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18991.50000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80076 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80076 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37983.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54916.24242 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 54916.24242 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.18677 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.18677 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1313.94536 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.18677 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.18677 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.18677 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78327 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.18677 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59339 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.79118 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19645.30000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9822.65000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19645.30000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27823.64698 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 27823.64698 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.18039 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.18039 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1306.87369 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.18039 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.18039 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.18039 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77905 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.18039 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59019 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.78693 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19539.56000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9769.78000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19539.56000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27712.57335 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 27712.57335 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.17924 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.17924 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1305.60553 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.17924 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.17924 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.17924 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77830 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.17924 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58962 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.78616 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19520.60000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9760.30000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19520.60000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27622.30302 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 27622.30302 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29163 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29163 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1430.03962 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29163 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29163 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29163 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85248 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29163 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64582 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86109 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21381.07000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10690.53500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21381.07000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30225.33490 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 30225.33490 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 38315.8 | 11.13 | 11.13 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 20483.8 | 11.12 | 11.12 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 21606.2 | 11.12 | 11.12 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 21484.9 | 11.12 | 11.12 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 21480.3 | 11.12 | 11.12 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 36189.1 | 11.12 | 11.12 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 18715.2 | 11.12 | 11.12 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 18614.5 | 11.12 | 11.12 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 18596.4 | 11.12 | 11.12 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 20368.8 | 11.12 | 11.12 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 6.9903904125E-002 | 7.6299760435E-002 | Pass | Pass | 3.3892887195E-002 | 8.8664575534E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 6.6414517131E-002 | 0.1147012597 | Pass | Pass | 5.7512655201E-002 | 0.1737020903 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 7.0393218920E-002 | 9.6797955511E-002 | Pass | Pass | 2.7690079288E-002 | 9.5234359923E-002 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 6.8367173608E-002 | 8.6200542853E-002 | Pass | Pass | 2.8114252263E-002 | 9.9842337306E-002 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 6.4127586082E-002 | 8.7470695990E-002 | Pass | Pass | 4.9737223655E-002 | 0.1695651313 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 6.4352225776E-002 | 0.1318923599 | Pass | Pass | 9.2906332071E-002 | 0.3418169762 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 6.3356298517E-002 | 0.1410288626 | Pass | Pass | 0.1789047198 | 1.2402906774 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.8215035872E-002 | 0.1395401909 | Pass | Pass | 0.3728931672 | 3.3453524936 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.4806471651E-002 | 0.1511408323 | Pass | Pass | 0.2276155784 | 1.1732517740 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.7698087911E-002 | 0.2610999731 | Pass | Pass | 9.3567800222E-002 | 0.2298971709 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5288.18 | 96.13 | 0.00 | 330.22 | 632.48 | 6347.04 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.361 | 0.397 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.153 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.153 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.101 | 3.065 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.101 | 3.065 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 11.2423 | 348.39 | 3916.66 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.43 | 0.0000 | Y | 60.61 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 11.3390 | 174.19 | 1975.18 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 83.87 | 0.0000 | Y | 31.10 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 11.2173 | 348.39 | 3907.97 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 58.99 | 0.0000 | Y | 43.28 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3450 | 4180.64 | 30706.87 | 408.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.81 | 41.81 | 3.58 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.71 | 62.76 | 32.33 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.71 | 55.76 | 24.15 | |
Exterior Lighting Total | 5507.06 | 60.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40219.98 | 32202.53 | 8017.45 | 0.80 | 3.81 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21501.75 | 17215.59 | 4286.16 | 0.80 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22679.99 | 18158.96 | 4521.03 | 0.80 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22552.58 | 18056.95 | 4495.63 | 0.80 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22547.82 | 18053.14 | 4494.68 | 0.80 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37983.00 | 30415.27 | 7567.73 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19645.30 | 15729.21 | 3916.09 | 0.80 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19539.56 | 15644.54 | 3895.02 | 0.80 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19520.60 | 15629.36 | 3891.24 | 0.80 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21381.07 | 17118.97 | 4262.10 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 38315.8 | 11.13 | 11.13 | ||||
PSZ-AC_2:2 COOLING COIL | 20483.8 | 11.12 | 11.12 | ||||
PSZ-AC_3:3 COOLING COIL | 21606.2 | 11.12 | 11.12 | ||||
PSZ-AC_4:4 COOLING COIL | 21484.9 | 11.12 | 11.12 | ||||
PSZ-AC_5:5 COOLING COIL | 21480.3 | 11.12 | 11.12 | ||||
PSZ-AC_6:6 COOLING COIL | 36189.1 | 11.12 | 11.12 | ||||
PSZ-AC_7:7 COOLING COIL | 18715.2 | 11.12 | 11.12 | ||||
PSZ-AC_8:8 COOLING COIL | 18614.5 | 11.12 | 11.12 | ||||
PSZ-AC_9:9 COOLING COIL | 18596.4 | 11.12 | 11.12 | ||||
PSZ-AC_10:10 COOLING COIL | 20368.8 | 11.12 | 11.12 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 57562.48 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 30362.08 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 31700.38 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 31555.66 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 31550.25 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 54916.24 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 27823.65 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 27712.57 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 27622.30 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 30225.33 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.43 | 2599.88 | 1070.05 | 1.00 | 1.29 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1438.11 | 1107.16 | 1.00 | 1.34 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1516.92 | 1107.16 | 1.00 | 1.33 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.36 | 1508.39 | 1107.16 | 1.00 | 1.33 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.36 | 1508.08 | 1107.16 | 1.00 | 1.33 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.29 | 2449.30 | 1070.05 | 1.00 | 1.30 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.19 | 1313.95 | 1107.16 | 1.00 | 1.36 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.18 | 1306.87 | 1107.16 | 1.00 | 1.36 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.18 | 1305.61 | 1107.16 | 1.00 | 1.36 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.29 | 1430.04 | 1107.16 | 1.00 | 1.34 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22632.85 | 27159.42 | 77.96 | 2.025 | 2.430 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 23.89 | 23.89 | 0.00735 | 35.10 | 0.00570 | 0.411 | 0.00 |
SMSTORE1 | 12099.70 | 14519.64 | 83.35 | 1.082 | 1.299 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00732 | 34.88 | 0.00570 | 0.206 | 0.00 |
SMSTORE2 | 13043.19 | 15651.82 | 89.85 | 1.142 | 1.370 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00761 | 27.68 | 0.00569 | 0.206 | 0.00 |
SMSTORE3 | 12971.67 | 15566.01 | 89.36 | 1.135 | 1.362 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00761 | 27.68 | 0.00569 | 0.206 | 0.00 |
SMSTORE4 | 12968.21 | 15561.85 | 89.34 | 1.135 | 1.362 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00762 | 27.68 | 0.00569 | 0.206 | 0.00 |
LGSTORE2 | 21321.70 | 25586.04 | 73.44 | 1.907 | 2.289 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00738 | 34.76 | 0.00570 | 0.411 | 0.00 |
SMSTORE5 | 11123.47 | 13348.16 | 76.63 | 0.970 | 1.164 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00768 | 29.97 | 0.00569 | 0.206 | 0.00 |
SMSTORE6 | 11067.93 | 13281.52 | 76.25 | 0.965 | 1.158 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00769 | 29.97 | 0.00569 | 0.206 | 0.00 |
SMSTORE7 | 11022.59 | 13227.10 | 75.93 | 0.961 | 1.153 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00770 | 29.97 | 0.00569 | 0.206 | 0.00 |
SMSTORE8 | 12031.37 | 14437.64 | 82.88 | 1.076 | 1.292 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00731 | 34.43 | 0.00570 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18752.60 | 22503.12 | 64.59 | 0.983 | 1.179 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00686 | -7.90 | 0.00234 | 0.411 | 0.00 |
SMSTORE1 | 8856.50 | 10627.80 | 61.01 | 0.464 | 0.557 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00674 | -7.90 | 0.00234 | 0.206 | 0.00 |
SMSTORE2 | 8969.11 | 10762.94 | 61.79 | 0.470 | 0.564 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -7.90 | 0.00234 | 0.206 | 0.00 |
SMSTORE3 | 9070.10 | 10884.12 | 62.48 | 0.475 | 0.570 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -7.90 | 0.00234 | 0.206 | 0.00 |
SMSTORE4 | 9248.81 | 11098.58 | 63.71 | 0.485 | 0.582 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00677 | -7.90 | 0.00234 | 0.206 | 0.00 |
LGSTORE2 | 17981.57 | 21577.89 | 61.94 | 0.942 | 1.131 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00686 | -7.90 | 0.00234 | 0.411 | 0.00 |
SMSTORE5 | 9563.45 | 11476.13 | 65.88 | 0.501 | 0.601 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00680 | -7.90 | 0.00234 | 0.206 | 0.00 |
SMSTORE6 | 9562.73 | 11475.28 | 65.88 | 0.501 | 0.601 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00680 | -7.90 | 0.00234 | 0.206 | 0.00 |
SMSTORE7 | 9844.16 | 11812.99 | 67.82 | 0.516 | 0.619 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00682 | -7.90 | 0.00234 | 0.206 | 0.00 |
SMSTORE8 | 11834.18 | 14201.02 | 81.52 | 0.620 | 0.744 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00690 | -7.90 | 0.00234 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.43 | 2.43 | 1.18 | 1.18 | 2.4297 | 2.4297 | 2.4297 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.30 | 1.30 | 0.56 | 0.56 | 1.2989 | 1.2989 | 1.2989 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.37 | 1.37 | 0.56 | 0.56 | 1.3701 | 1.3701 | 1.3701 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.36 | 1.36 | 0.57 | 0.57 | 1.3624 | 1.3624 | 1.3624 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.36 | 1.36 | 0.58 | 0.58 | 1.3621 | 1.3621 | 1.3621 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.29 | 2.29 | 1.13 | 1.13 | 2.2890 | 2.2890 | 2.2890 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.19 | 1.19 | 0.60 | 0.60 | 1.1868 | 1.1639 | 1.1868 | 0.9807 | 1.0000 |
PSZ-AC_8:8 | 1.18 | 1.18 | 0.60 | 0.60 | 1.1804 | 1.1580 | 1.1804 | 0.9810 | 1.0000 |
PSZ-AC_9:9 | 1.18 | 1.18 | 0.62 | 0.62 | 1.1792 | 1.1532 | 1.1792 | 0.9779 | 1.0000 |
PSZ-AC_10:10 | 1.29 | 1.29 | 0.74 | 0.74 | 1.2916 | 1.2916 | 1.2916 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 40219.980 | 32202.529 | 2.429690 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 20109.99 | 19942.76 | 1.619793 | 26.85 | 14.17 | 0.00707017 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 25.4032 | 23.89 | 0.00734965 | 32.8194 | 22632.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 57562.483 | 57562.483 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 57562.48 | 57562.48 | 2.429689 | 16.19 | 9.35 | 0.00609128 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 16.9355 | 21.11 | 0.00685545 | 36.2804 | 18752.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 21501.750 | 17215.591 | 1.298920 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10750.88 | 10672.92 | 0.865947 | 26.76 | 14.14 | 0.00706087 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 23.7589 | 23.89 | 0.00731730 | 32.6764 | 12092.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 30362.078 | 30362.078 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30362.08 | 30362.08 | 1.298921 | 16.51 | 9.43 | 0.00604050 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 15.8393 | 21.11 | 0.00673635 | 35.6570 | 8856.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 22679.990 | 18158.961 | 1.370100 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11340.00 | 11257.65 | 0.913400 | 26.76 | 14.13 | 0.00706094 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 22.5246 | 23.89 | 0.00731648 | 32.6728 | 13043.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31700.379 | 31700.379 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31700.38 | 31700.38 | 1.370098 | 16.75 | 9.57 | 0.00608478 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 15.0164 | 21.11 | 0.00674592 | 35.7071 | 8969.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 22552.580 | 18056.949 | 1.362400 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11276.29 | 11194.31 | 0.908267 | 26.75 | 14.13 | 0.00706100 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 22.6519 | 23.89 | 0.00731562 | 32.6689 | 12971.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 31555.663 | 31555.663 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31555.66 | 31555.66 | 1.362401 | 16.73 | 9.56 | 0.00608837 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 15.1012 | 21.11 | 0.00675454 | 35.7523 | 9070.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 22547.820 | 18053.138 | 1.362110 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11273.91 | 11192.21 | 0.908073 | 26.77 | 14.14 | 0.00706085 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 22.6567 | 23.89 | 0.00731801 | 32.6795 | 12968.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 31550.250 | 31550.250 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31550.25 | 31550.25 | 1.362114 | 16.73 | 9.57 | 0.00610118 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 15.1044 | 21.11 | 0.00676979 | 35.8322 | 9248.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 37983.000 | 30415.267 | 2.288960 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 18991.50 | 18826.40 | 1.525973 | 26.97 | 14.21 | 0.00707380 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 26.9650 | 23.89 | 0.00737554 | 32.9337 | 21291.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 54916.242 | 54916.242 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 54916.24 | 54916.24 | 2.288965 | 15.89 | 9.18 | 0.00604416 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 17.9766 | 21.11 | 0.00685529 | 36.2791 | 17981.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 19645.300 | 15729.206 | 1.186770 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 9822.65 | 9754.70 | 0.791180 | 26.93 | 14.19 | 0.00705852 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 26.0041 | 23.89 | 0.00734415 | 32.7949 | 11036.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 27823.647 | 27823.647 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 27823.65 | 27823.65 | 1.186772 | 16.08 | 9.24 | 0.00602371 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 17.3360 | 21.11 | 0.00679558 | 35.9673 | 9563.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 19539.560 | 15644.544 | 1.180390 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 9769.78 | 9702.44 | 0.786927 | 26.94 | 14.19 | 0.00705834 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 26.1447 | 23.89 | 0.00734580 | 32.8022 | 10976.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 27712.573 | 27712.573 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 27712.57 | 27712.57 | 1.180385 | 16.05 | 9.22 | 0.00601951 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 17.4299 | 21.11 | 0.00679556 | 35.9671 | 9562.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 19520.600 | 15629.364 | 1.179240 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 9760.30 | 9693.08 | 0.786160 | 26.95 | 14.19 | 0.00705830 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 26.1702 | 23.89 | 0.00734616 | 32.8038 | 10963.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 27622.303 | 27622.303 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 27622.30 | 27622.30 | 1.179240 | 16.05 | 9.24 | 0.00603673 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 17.4468 | 21.11 | 0.00681733 | 36.0812 | 9844.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 21381.070 | 17118.968 | 1.291630 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 10690.53 | 10623.47 | 0.861087 | 26.66 | 14.09 | 0.00705237 | 12.80 | 8.87 | 0.00700000 | 34.43 | 0.00569833 | 15.56 | 23.8930 | 23.89 | 0.00730891 | 32.6393 | 12031.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 30225.335 | 30225.335 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30225.33 | 30225.33 | 1.291630 | 16.49 | 9.55 | 0.00617832 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 15.9287 | 21.11 | 0.00690495 | 36.5407 | 11834.18 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40219.980 | 32202.529 | 2.429690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9831 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.429689 | 2.40638569 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 20109.99 | 19942.76 | 1.0000 | 1.60425772 | 1.619793 | 26.85 | 14.17 | 0.00707017 | 45013.4 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20109.99 | 35.10 | 0.00569938 | 15.77 | 0.41147883 | 25.4032 | 23.89 | 0.00734965 | 23.89 | 0.00734965 | 32.8194 | 22632.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57562.483 | 57562.483 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.429689 | 2.40638569 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 57562.48 | 57562.48 | 1.0000 | 2.40638569 | 2.429689 | 16.19 | 9.35 | 0.00609128 | 31690.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57562.48 | -7.90 | 0.00234317 | -7.90 | 0.41147883 | 16.9355 | 21.11 | 0.00685545 | 21.11 | 0.00685545 | 36.2804 | 18752.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21501.750 | 17215.591 | 1.298920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9658 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.298921 | 1.28646266 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10750.88 | 10672.92 | 1.0000 | 0.85764128 | 0.865947 | 26.76 | 14.14 | 0.00706087 | 44903.3 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10750.88 | 35.10 | 0.00569938 | 15.77 | 0.20573941 | 23.7589 | 23.89 | 0.00731730 | 23.89 | 0.00731730 | 32.6764 | 12092.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30362.078 | 30362.078 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.298921 | 1.28646266 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30362.08 | 30362.08 | 1.0000 | 1.28646266 | 1.298921 | 16.51 | 9.43 | 0.00604050 | 31885.2 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30362.08 | -7.90 | 0.00234317 | -7.90 | 0.20573941 | 15.8393 | 21.11 | 0.00673635 | 21.11 | 0.00673635 | 35.6570 | 8856.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22679.990 | 18158.961 | 1.370100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9659 | 1004.8586 | 0.9904 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.370098 | 1.35695738 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11340.00 | 11257.65 | 1.0000 | 0.90463948 | 0.913400 | 26.76 | 14.13 | 0.00706094 | 44898.1 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11340.00 | 35.10 | 0.00569938 | 15.77 | 0.20573941 | 22.5246 | 23.89 | 0.00731648 | 23.89 | 0.00731648 | 32.6728 | 13043.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31700.379 | 31700.379 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.370098 | 1.35695738 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31700.38 | 31700.38 | 1.0000 | 1.35695738 | 1.370098 | 16.75 | 9.57 | 0.00608478 | 32239.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31700.38 | -7.90 | 0.00234317 | -7.90 | 0.20573941 | 15.0164 | 21.11 | 0.00674592 | 21.11 | 0.00674592 | 35.7071 | 8969.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22552.580 | 18056.949 | 1.362400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9660 | 1004.8586 | 0.9904 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.362401 | 1.34933441 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11276.29 | 11194.31 | 1.0000 | 0.89955538 | 0.908267 | 26.75 | 14.13 | 0.00706100 | 44892.7 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11276.29 | 35.10 | 0.00569938 | 15.77 | 0.20573941 | 22.6519 | 23.89 | 0.00731562 | 23.89 | 0.00731562 | 32.6689 | 12971.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31555.663 | 31555.663 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.362401 | 1.34933441 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31555.66 | 31555.66 | 1.0000 | 1.34933441 | 1.362401 | 16.73 | 9.56 | 0.00608837 | 32223.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31555.66 | -7.90 | 0.00234317 | -7.90 | 0.20573941 | 15.1012 | 21.11 | 0.00675454 | 21.11 | 0.00675454 | 35.7523 | 9070.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22547.820 | 18053.138 | 1.362110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9658 | 1004.8586 | 0.9904 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.362114 | 1.34904938 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11273.91 | 11192.21 | 1.0000 | 0.89936391 | 0.908073 | 26.77 | 14.14 | 0.00706085 | 44907.6 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11273.91 | 35.10 | 0.00569938 | 15.77 | 0.20573941 | 22.6567 | 23.89 | 0.00731801 | 23.89 | 0.00731801 | 32.6795 | 12968.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31550.250 | 31550.250 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.362114 | 1.34904938 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31550.25 | 31550.25 | 1.0000 | 1.34904938 | 1.362114 | 16.73 | 9.57 | 0.00610118 | 32255.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31550.25 | -7.90 | 0.00234317 | -7.90 | 0.20573941 | 15.1044 | 21.11 | 0.00676979 | 21.11 | 0.00676979 | 35.8322 | 9248.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37983.000 | 30415.267 | 2.288960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9898 | 1004.8586 | 0.9904 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.288965 | 2.26701101 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 18991.50 | 18826.40 | 1.0000 | 1.51133756 | 1.525973 | 26.97 | 14.21 | 0.00707380 | 45144.4 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18991.50 | 35.10 | 0.00569938 | 15.77 | 0.41147883 | 26.9650 | 23.89 | 0.00737554 | 23.89 | 0.00737554 | 32.9337 | 21291.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54916.242 | 54916.242 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.288965 | 2.26701101 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 54916.24 | 54916.24 | 1.0000 | 2.26701101 | 2.288965 | 15.89 | 9.18 | 0.00604416 | 31264.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54916.24 | -7.90 | 0.00234317 | -7.90 | 0.41147883 | 17.9766 | 21.11 | 0.00685529 | 21.11 | 0.00685529 | 36.2791 | 17981.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19645.300 | 15729.206 | 1.186770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9614 | 1004.8586 | 0.9904 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.186772 | 1.17538988 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 9822.65 | 9754.70 | 1.0000 | 0.78359171 | 0.791180 | 26.93 | 14.19 | 0.00705852 | 45070.4 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9822.65 | 35.10 | 0.00569938 | 15.77 | 0.20573941 | 26.0041 | 23.89 | 0.00734415 | 23.89 | 0.00734415 | 32.7949 | 11036.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27823.647 | 27823.647 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.186772 | 1.17538988 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 27823.65 | 27823.65 | 1.0000 | 1.17538988 | 1.186772 | 16.08 | 9.24 | 0.00602371 | 31401.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27823.65 | -7.90 | 0.00234317 | -7.90 | 0.20573941 | 17.3360 | 21.11 | 0.00679558 | 21.11 | 0.00679558 | 35.9673 | 9563.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19539.560 | 15644.544 | 1.180390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9611 | 1004.8586 | 0.9904 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.180385 | 1.16906391 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 9769.78 | 9702.44 | 1.0000 | 0.77937917 | 0.786927 | 26.94 | 14.19 | 0.00705834 | 45080.7 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9769.78 | 35.10 | 0.00569938 | 15.77 | 0.20573941 | 26.1447 | 23.89 | 0.00734580 | 23.89 | 0.00734580 | 32.8022 | 10976.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27712.573 | 27712.573 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.180385 | 1.16906391 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 27712.57 | 27712.57 | 1.0000 | 1.16906391 | 1.180385 | 16.05 | 9.22 | 0.00601951 | 31363.3 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27712.57 | -7.90 | 0.00234317 | -7.90 | 0.20573941 | 17.4299 | 21.11 | 0.00679556 | 21.11 | 0.00679556 | 35.9671 | 9562.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19520.600 | 15629.364 | 1.179240 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9610 | 1004.8586 | 0.9904 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.179240 | 1.16792948 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 9760.30 | 9693.08 | 1.0000 | 0.77861986 | 0.786160 | 26.95 | 14.19 | 0.00705830 | 45082.9 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9760.30 | 35.10 | 0.00569938 | 15.77 | 0.20573941 | 26.1702 | 23.89 | 0.00734616 | 23.89 | 0.00734616 | 32.8038 | 10963.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27622.303 | 27622.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.179240 | 1.16792948 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 27622.30 | 27622.30 | 1.0000 | 1.16792948 | 1.179240 | 16.05 | 9.24 | 0.00603673 | 31401.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27622.30 | -7.90 | 0.00234317 | -7.90 | 0.20573941 | 17.4468 | 21.11 | 0.00681733 | 21.11 | 0.00681733 | 36.0812 | 9844.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21381.070 | 17118.968 | 1.291630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9500 | 1004.8586 | 0.9904 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.291630 | 1.27924201 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 10690.53 | 10623.47 | 1.0000 | 0.85282789 | 0.861087 | 26.66 | 14.09 | 0.00705237 | 44780.9 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10690.53 | 34.43 | 0.00569833 | 15.56 | 0.20573941 | 23.8930 | 23.89 | 0.00730891 | 23.89 | 0.00730891 | 32.6393 | 12031.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30225.335 | 30225.335 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.291630 | 1.27924201 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30225.33 | 30225.33 | 1.0000 | 1.27924201 | 1.291630 | 16.49 | 9.55 | 0.00617832 | 32207.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30225.33 | -7.90 | 0.00234317 | -7.90 | 0.20573941 | 15.9287 | 21.11 | 0.00690495 | 21.11 | 0.00690495 | 36.5407 | 11834.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.43 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.30 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.37 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.36 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.36 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.29 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.19 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.18 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.18 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.29 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2048.17 | 3228.67 | 367.17 |
SMSTORE1 | 1698.00 | 3072.17 | 56.00 |
SMSTORE2 | 1497.17 | 2257.67 | 135.00 |
SMSTORE3 | 1517.67 | 2289.17 | 154.00 |
SMSTORE4 | 1528.50 | 2353.67 | 190.33 |
LGSTORE2 | 1417.00 | 2266.67 | 252.83 |
SMSTORE5 | 1375.67 | 2309.83 | 276.00 |
SMSTORE6 | 1394.33 | 2328.00 | 305.00 |
SMSTORE7 | 1473.67 | 2360.33 | 394.17 |
SMSTORE8 | 1875.00 | 2393.17 | 753.00 |
Facility | 2786.67 | 3647.33 | 996.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 1.50 | 0.00 | 0.00 | 0.00 |
Facility | 2.17 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.111 | 0.216 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.990 | 0.236 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.157 | 0.309 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.148 | 0.309 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.133 | 0.309 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 1.054 | 0.297 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 1.063 | 0.330 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 1.056 | 0.330 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 1.045 | 0.330 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 1.062 | 0.339 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.805 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.78 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.98 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 11633988.86 | 0.00 | 11633988.86 | 2421470.17 | 14055459.03 | 12976396.34 | 3119.06 | 4037.50 | 1603.44 | 31.44 |
SMSTORE1 | 5191912.41 | 0.00 | 5191912.41 | 1279713.12 | 6471625.54 | 6488198.17 | 4231.09 | 2916.23 | 1612.68 | 38.19 |
SMSTORE2 | 4700576.44 | 0.00 | 4700576.44 | 1297779.15 | 5998355.60 | 6488198.17 | 4282.07 | 3292.33 | 1185.60 | 142.48 |
SMSTORE3 | 4666876.74 | 0.00 | 4666876.74 | 1297779.15 | 5964655.89 | 6488198.17 | 4281.82 | 3328.67 | 1149.51 | 140.67 |
SMSTORE4 | 4601059.70 | 0.00 | 4601059.70 | 1297779.15 | 5898838.86 | 6488198.17 | 4285.66 | 3387.25 | 1087.09 | 137.11 |
LGSTORE2 | 7808303.79 | 0.00 | 7808303.79 | 2354243.74 | 10162547.53 | 12976396.34 | 4667.94 | 3175.42 | 916.64 | 111.79 |
SMSTORE5 | 3940146.58 | 0.00 | 3940146.58 | 1301884.48 | 5242031.06 | 6488198.17 | 4667.01 | 3191.75 | 901.24 | 110.74 |
SMSTORE6 | 3913252.20 | 0.00 | 3913252.20 | 1301884.48 | 5215136.68 | 6488198.17 | 4669.29 | 3209.00 | 881.71 | 106.74 |
SMSTORE7 | 3864955.23 | 0.00 | 3864955.23 | 1301884.48 | 5166839.71 | 6488198.17 | 4671.09 | 3256.17 | 832.74 | 101.04 |
SMSTORE8 | 3926818.98 | 0.00 | 3926818.98 | 1446710.67 | 5373529.65 | 6488198.17 | 4676.41 | 3312.67 | 770.92 | 90.69 |
Total Facility | 54247890.94 | 0.00 | 54247890.94 | 15301128.62 | 69549019.55 | 77858378.04 | 4680.14 | 4574.89 | 1987.35 | 276.60 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5501 | 0.0000 | 0.5501 | 0.1071 | 0.6571 | 0.4115 | 217.46 | 4037.50 | 1585.04 |
SMSTORE1 | 0.2449 | 0.0000 | 0.2449 | 0.0584 | 0.3033 | 0.2057 | 1331.69 | 2916.23 | 1592.08 |
SMSTORE2 | 0.2864 | 0.0000 | 0.2864 | 0.0766 | 0.3630 | 0.2057 | 0.00 | 3291.33 | 1103.67 |
SMSTORE3 | 0.2843 | 0.0000 | 0.2843 | 0.0766 | 0.3609 | 0.2057 | 0.00 | 3328.00 | 1067.00 |
SMSTORE4 | 0.2806 | 0.0000 | 0.2806 | 0.0766 | 0.3572 | 0.2057 | 0.00 | 3386.92 | 1008.08 |
LGSTORE2 | 0.5221 | 0.0000 | 0.5221 | 0.1469 | 0.6690 | 0.4115 | 0.00 | 3174.58 | 855.42 |
SMSTORE5 | 0.2632 | 0.0000 | 0.2632 | 0.0818 | 0.3450 | 0.2057 | 0.00 | 3191.08 | 838.92 |
SMSTORE6 | 0.2616 | 0.0000 | 0.2616 | 0.0818 | 0.3434 | 0.2057 | 0.00 | 3208.67 | 821.33 |
SMSTORE7 | 0.2588 | 0.0000 | 0.2588 | 0.0818 | 0.3406 | 0.2057 | 0.00 | 3255.00 | 775.00 |
SMSTORE8 | 0.2632 | 0.0000 | 0.2632 | 0.0839 | 0.3471 | 0.2057 | 0.00 | 3312.33 | 717.67 |
Total Facility | 3.2153 | 0.0000 | 3.2153 | 0.8715 | 4.0868 | 2.4689 | 1429.74 | 4570.39 | 1917.83 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 11412035.93 | 0.00 | 11412035.93 | 12976396.34 | 7156.06 | 11.00 | 1592.94 | 31.40 |
PSZ-AC_2:2 | 5092826.03 | 0.00 | 5092826.03 | 6488198.17 | 7146.98 | 14.69 | 1598.33 | 38.19 |
PSZ-AC_3:3 | 4610875.11 | 0.00 | 4610875.11 | 6488198.17 | 7573.90 | 6.50 | 1179.60 | 142.48 |
PSZ-AC_4:4 | 4577820.75 | 0.00 | 4577820.75 | 6488198.17 | 7610.32 | 6.50 | 1143.18 | 140.51 |
PSZ-AC_5:5 | 4513261.43 | 0.00 | 4513261.43 | 6488198.17 | 7672.74 | 4.50 | 1082.76 | 136.80 |
PSZ-AC_6:6 | 7659341.59 | 0.00 | 7659341.59 | 12976396.34 | 7842.86 | 4.33 | 912.81 | 111.79 |
PSZ-AC_7:7 | 3864973.05 | 0.00 | 3864973.05 | 6488198.17 | 7858.59 | 3.33 | 898.07 | 110.49 |
PSZ-AC_8:8 | 3838590.06 | 0.00 | 3838590.06 | 6488198.17 | 7877.79 | 3.67 | 878.54 | 106.57 |
PSZ-AC_9:9 | 3791200.57 | 0.00 | 3791200.57 | 6488198.17 | 7926.92 | 3.50 | 829.58 | 101.04 |
PSZ-AC_10:10 | 3851838.58 | 0.00 | 3851838.58 | 6488198.17 | 7989.08 | 2.00 | 768.92 | 90.52 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5396 | 0.0000 | 0.5396 | 0.4115 | 4254.46 | 10.83 | 1574.71 |
PSZ-AC_2:2 | 0.2402 | 0.0000 | 0.2402 | 0.2057 | 4247.59 | 14.52 | 1577.89 |
PSZ-AC_3:3 | 0.2810 | 0.0000 | 0.2810 | 0.2057 | 3290.83 | 6.00 | 1098.17 |
PSZ-AC_4:4 | 0.2789 | 0.0000 | 0.2789 | 0.2057 | 3327.83 | 5.33 | 1061.83 |
PSZ-AC_5:5 | 0.2753 | 0.0000 | 0.2753 | 0.2057 | 3386.75 | 4.00 | 1004.25 |
PSZ-AC_6:6 | 0.5121 | 0.0000 | 0.5121 | 0.4115 | 3174.25 | 3.67 | 852.08 |
PSZ-AC_7:7 | 0.2582 | 0.0000 | 0.2582 | 0.2057 | 3190.92 | 2.50 | 836.58 |
PSZ-AC_8:8 | 0.2566 | 0.0000 | 0.2566 | 0.2057 | 3208.17 | 3.50 | 818.33 |
PSZ-AC_9:9 | 0.2539 | 0.0000 | 0.2539 | 0.2057 | 3254.83 | 3.00 | 772.17 |
PSZ-AC_10:10 | 0.2582 | 0.0000 | 0.2582 | 0.2057 | 3312.33 | 1.67 | 716.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5036.45 | 659.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4107.82 | 1139.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3963.60 | 573.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3995.95 | 539.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4032.42 | 499.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3765.38 | 376.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3772.43 | 368.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3783.40 | 353.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3806.52 | 324.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3836.95 | 283.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5418 | 0.6708 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2690 | 0.2707 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2695 | 0.3765 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2678 | 0.3787 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2648 | 0.3790 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.4985 | 0.6824 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2511 | 0.3493 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2500 | 0.3464 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2477 | 0.3459 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2516 | 0.3700 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 828 |
Defaulted Fields | 823 |
Fields with Defaults | 2679 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 864.53 | 891.83 | 20-FEB-07:50 | 90284.33 | 28-JUN-16:10 |
Electricity:Building | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 122.08 | 148.64 | 01-JAN-00:20 | 6431.20 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 70.71 | 74.32 | 01-JAN-00:20 | 3733.31 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 62.45 | 148.64 | 01-JAN-00:10 | 4534.89 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 864.53 | 891.83 | 20-FEB-07:50 | 90284.33 | 28-JUN-16:10 |
ElectricityPurchased:Plant | 864.53 | 891.83 | 20-FEB-07:50 | 90284.33 | 28-JUN-16:10 |
Cogeneration:ElectricityPurchased | 864.53 | 891.83 | 20-FEB-07:50 | 90284.33 | 28-JUN-16:10 |
General:Cogeneration:ElectricityPurchased | 864.53 | 891.83 | 20-FEB-07:50 | 90284.33 | 28-JUN-16:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 864.53 | 891.83 | 20-FEB-07:50 | 90284.33 | 28-JUN-16:10 |
ElectricityNet:Plant | 864.53 | 891.83 | 20-FEB-07:50 | 90284.33 | 28-JUN-16:10 |
Cogeneration:ElectricityNet | 864.53 | 891.83 | 20-FEB-07:50 | 90284.33 | 28-JUN-16:10 |
General:Cogeneration:ElectricityNet | 864.53 | 891.83 | 20-FEB-07:50 | 90284.33 | 28-JUN-16:10 |
Electricity:HVAC | 242.46 | 0.00 | 01-JAN-00:10 | 54486.45 | 28-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 125.99 | 0.00 | 01-JAN-00:10 | 44198.24 | 28-JUN-16:10 |
General:Cooling:Electricity | 125.99 | 0.00 | 01-JAN-00:10 | 44198.24 | 28-JUN-16:10 |
Fans:Electricity | 116.47 | 0.00 | 01-JAN-00:10 | 10288.21 | 28-JUN-16:10 |
General:Fans:Electricity | 116.47 | 0.00 | 01-JAN-00:10 | 10288.21 | 28-JUN-16:10 |
ExteriorLights:Electricity | 60.06 | 0.00 | 01-JAN-07:20 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.06 | 0.00 | 01-JAN-07:20 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 25.52 | 0.00 | 01-JAN-00:10 | 2235.74 | 17-FEB-13:50 |
WaterSystems:Electricity | 25.52 | 0.00 | 01-JAN-00:10 | 2235.74 | 17-FEB-13:50 |
Water Heater:WaterSystems:Electricity | 25.52 | 0.00 | 01-JAN-00:10 | 2235.74 | 17-FEB-13:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 122.70 | 0.00 | 01-JAN-00:10 | 125973.60 | 06-FEB-08:10 |
NaturalGas:HVAC | 122.70 | 0.00 | 01-JAN-00:10 | 125973.60 | 06-FEB-08:10 |
Heating:NaturalGas | 122.70 | 0.00 | 01-JAN-00:10 | 125973.60 | 06-FEB-08:10 |
General:Heating:NaturalGas | 122.70 | 0.00 | 01-JAN-00:10 | 125973.60 | 06-FEB-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1151.29 | 0.00 | 01-JAN-00:10 | 236609.16 | 22-JUL-15:00 |
EnergyTransfer:Building | 571.18 | 0.00 | 01-JAN-00:10 | 96006.80 | 22-JUL-14:00 |
EnergyTransfer:Zone:LGSTORE1 | 120.36 | 0.00 | 01-JAN-00:10 | 16173.99 | 28-JUN-16:30 |
Heating:EnergyTransfer | 24.44 | 0.00 | 01-JAN-00:10 | 91025.61 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 3.09 | 0.00 | 01-JAN-00:10 | 15826.64 | 06-FEB-08:10 |
General:Heating:EnergyTransfer | 24.44 | 0.00 | 01-JAN-00:10 | 91025.61 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 3.09 | 0.00 | 01-JAN-00:10 | 15826.64 | 06-FEB-08:10 |
Cooling:EnergyTransfer | 546.74 | 0.00 | 01-JAN-00:10 | 96006.80 | 22-JUL-14:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 117.28 | 0.00 | 01-JAN-00:10 | 16173.99 | 28-JUN-16:30 |
General:Cooling:EnergyTransfer | 546.74 | 0.00 | 01-JAN-00:10 | 96006.80 | 22-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 117.28 | 0.00 | 01-JAN-00:10 | 16173.99 | 28-JUN-16:30 |
EnergyTransfer:Zone:SMSTORE1 | 65.84 | 0.00 | 01-JAN-00:10 | 8911.44 | 08-OCT-18:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.69 | 0.00 | 01-JAN-00:10 | 4694.34 | 20-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.69 | 0.00 | 01-JAN-00:10 | 4694.34 | 20-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 65.15 | 0.00 | 01-JAN-00:10 | 8911.44 | 08-OCT-18:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 65.15 | 0.00 | 01-JAN-00:10 | 8911.44 | 08-OCT-18:10 |
EnergyTransfer:Zone:SMSTORE2 | 50.34 | 0.00 | 01-JAN-00:10 | 8358.21 | 22-JUL-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.25 | 0.00 | 01-JAN-00:10 | 6286.66 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.25 | 0.00 | 01-JAN-00:10 | 6286.66 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 49.10 | 0.00 | 01-JAN-00:10 | 8358.21 | 22-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 49.10 | 0.00 | 01-JAN-00:10 | 8358.21 | 22-JUL-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 49.74 | 0.00 | 01-JAN-00:10 | 8387.17 | 22-JUL-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.42 | 0.00 | 01-JAN-00:10 | 7130.15 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.42 | 0.00 | 01-JAN-00:10 | 7130.15 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 48.32 | 0.00 | 01-JAN-00:10 | 8387.17 | 22-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 48.32 | 0.00 | 01-JAN-00:10 | 8387.17 | 22-JUL-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 47.56 | 0.00 | 01-JAN-00:10 | 8242.84 | 22-JUL-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.70 | 0.00 | 01-JAN-00:10 | 7851.82 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.70 | 0.00 | 01-JAN-00:10 | 7851.82 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 45.86 | 0.00 | 01-JAN-00:10 | 8242.84 | 22-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 45.86 | 0.00 | 01-JAN-00:10 | 8242.84 | 22-JUL-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 78.61 | 0.00 | 01-JAN-00:10 | 17123.29 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 3.36 | 0.00 | 01-JAN-00:10 | 17123.29 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 3.36 | 0.00 | 01-JAN-00:10 | 17123.29 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 75.25 | 0.00 | 01-JAN-00:10 | 15186.75 | 22-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 75.25 | 0.00 | 01-JAN-00:10 | 15186.75 | 22-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE5 | 39.91 | 0.00 | 01-JAN-00:10 | 8912.27 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 1.99 | 0.00 | 01-JAN-00:10 | 8912.27 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 1.99 | 0.00 | 01-JAN-00:10 | 8912.27 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 37.92 | 0.00 | 01-JAN-00:10 | 7914.96 | 22-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 37.92 | 0.00 | 01-JAN-00:10 | 7914.96 | 22-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE6 | 39.26 | 0.00 | 01-JAN-00:10 | 9104.56 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 2.16 | 0.00 | 01-JAN-00:10 | 9104.56 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 2.16 | 0.00 | 01-JAN-00:10 | 9104.56 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 37.10 | 0.00 | 01-JAN-00:10 | 7869.09 | 22-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 37.10 | 0.00 | 01-JAN-00:10 | 7869.09 | 22-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE7 | 38.09 | 0.00 | 01-JAN-00:10 | 10768.22 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 2.82 | 0.00 | 01-JAN-00:10 | 10768.22 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 2.82 | 0.00 | 01-JAN-00:10 | 10768.22 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 35.27 | 0.00 | 01-JAN-00:10 | 7869.76 | 22-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 35.27 | 0.00 | 01-JAN-00:10 | 7869.76 | 22-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE8 | 41.46 | 0.00 | 01-JAN-00:10 | 15812.83 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 5.97 | 0.00 | 01-JAN-00:10 | 15812.83 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 5.97 | 0.00 | 01-JAN-00:10 | 15812.83 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 35.49 | 0.00 | 01-JAN-00:10 | 8786.54 | 22-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 35.49 | 0.00 | 01-JAN-00:10 | 8786.54 | 22-JUL-14:10 |
EnergyTransfer:HVAC | 580.11 | 0.00 | 01-JAN-00:10 | 140902.80 | 22-JUL-15:00 |
HeatingCoils:EnergyTransfer | 98.16 | 0.00 | 01-JAN-00:10 | 100778.88 | 06-FEB-08:10 |
CoolingCoils:EnergyTransfer | 481.95 | 0.00 | 01-JAN-00:10 | 140902.80 | 22-JUL-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 3.088 | -117.274 | 0.000 | 0.000 | 24.530 | 95.826 | 26.249 | 30.898 | 0.000 | 4.002 | 0.000 | 0.000 | -9.102 | 0.000 | -16.931 | -41.286 |
SMSTORE1 | 0.000 | 0.000 | 0.686 | -65.151 | 0.000 | 0.000 | 12.038 | 57.583 | 13.125 | 15.349 | 0.000 | 2.200 | 0.000 | 0.000 | -4.758 | 0.000 | -8.944 | -22.129 |
SMSTORE2 | 0.000 | 0.000 | 1.247 | -49.096 | 0.000 | 0.000 | 7.315 | 40.956 | 10.421 | 15.320 | 0.000 | 2.160 | 0.001 | 0.000 | -4.768 | 0.000 | -9.038 | -14.518 |
SMSTORE3 | 0.000 | 0.000 | 1.415 | -48.323 | 0.000 | 0.000 | 7.331 | 40.956 | 10.421 | 15.335 | 0.000 | 2.160 | 0.002 | 0.000 | -4.729 | 0.000 | -8.982 | -15.584 |
SMSTORE4 | 0.000 | 0.000 | 1.699 | -45.863 | 0.000 | 0.000 | 7.355 | 40.956 | 10.421 | 15.361 | 0.000 | 2.161 | 0.001 | 0.000 | -4.673 | 0.000 | -8.899 | -18.517 |
LGSTORE2 | 0.000 | 0.000 | 3.364 | -75.248 | 0.000 | 0.000 | 25.349 | 43.277 | 19.173 | 30.817 | 0.000 | 3.888 | 0.001 | 0.000 | -9.079 | 0.000 | -16.002 | -25.539 |
SMSTORE5 | 0.000 | 0.000 | 1.995 | -37.918 | 0.000 | 0.000 | 12.685 | 22.197 | 9.586 | 15.402 | 0.000 | 2.165 | 0.002 | 0.000 | -4.522 | 0.000 | -8.778 | -12.813 |
SMSTORE6 | 0.000 | 0.000 | 2.156 | -37.100 | 0.000 | 0.000 | 12.701 | 22.197 | 9.586 | 15.415 | 0.000 | 2.166 | 0.002 | 0.000 | -4.498 | 0.000 | -8.745 | -13.879 |
SMSTORE7 | 0.000 | 0.000 | 2.824 | -35.268 | 0.000 | 0.000 | 12.737 | 22.197 | 9.586 | 15.444 | 0.000 | 2.166 | 0.000 | 0.000 | -4.434 | 0.000 | -8.664 | -16.588 |
SMSTORE8 | 0.000 | 0.000 | 5.970 | -35.488 | 0.000 | 0.000 | 12.785 | 22.197 | 9.586 | 15.498 | 0.000 | 2.216 | 0.001 | 0.000 | -4.216 | 0.000 | -9.956 | -18.593 |
Total Facility | 0.000 | 0.000 | 24.443 | -546.729 | 0.000 | 0.000 | 134.827 | 408.342 | 128.154 | 184.840 | 0.000 | 25.284 | 0.010 | 0.000 | -54.779 | 0.000 | -104.937 | -199.446 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 19-AUG-07:02 | 0.00 | 0.00 | 0.00 | -36226.23 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 366.98 | 0.00 | 0.00 | 35785.34 | 0.00 | -0.00 | 0.00 | -74.73 | 0.00 |
SMSTORE1 | 19-AUG-07:02 | 0.00 | 0.00 | 0.00 | -19722.31 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 181.34 | 0.00 | 0.00 | 19509.31 | 0.00 | -0.00 | 0.00 | -42.66 | 0.00 |
SMSTORE2 | 19-AUG-06:02 | 0.00 | 0.00 | 0.00 | -22183.49 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22189.98 | 0.00 | -77.75 | 0.00 | -3.07 | 0.00 |
SMSTORE3 | 26-JUN-06:02 | 0.00 | 0.00 | 0.00 | -22181.12 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 14.25 | 0.00 | 0.00 | 22097.28 | 0.00 | -0.00 | 0.00 | -4.74 | 0.00 |
SMSTORE4 | 19-AUG-06:02 | 0.00 | 0.00 | 0.00 | -21457.25 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 21462.65 | 0.00 | -76.67 | 0.00 | -3.05 | 0.00 |
LGSTORE2 | 26-JUN-07:02 | 0.00 | 0.00 | 0.00 | -34927.76 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 303.36 | 0.00 | 0.00 | 34520.52 | 0.00 | -0.00 | 0.00 | -44.76 | 0.00 |
SMSTORE5 | 26-JUN-07:02 | 0.00 | 0.00 | 0.00 | -17940.48 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 153.07 | 0.00 | 0.00 | 17736.43 | 0.00 | -0.00 | 0.00 | -23.34 | 0.00 |
SMSTORE6 | 26-JUN-07:02 | 0.00 | 0.00 | 0.00 | -17824.74 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 153.76 | 0.00 | 0.00 | 17619.53 | 0.00 | -0.00 | 0.00 | -22.87 | 0.00 |
SMSTORE7 | 26-JUN-07:02 | 0.00 | 0.00 | 0.00 | -17714.84 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 155.33 | 0.00 | 0.00 | 17505.98 | 0.00 | -0.00 | 0.00 | -20.79 | 0.00 |
SMSTORE8 | 07-AUG-07:02 | 0.00 | 0.00 | 0.00 | -19093.48 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 69.34 | 0.00 | 0.00 | 19015.57 | 0.00 | -0.00 | 0.00 | -65.75 | 0.00 |
Total Facility | 07-AUG-07:02 | 0.00 | 0.00 | 0.00 | -170491.11 | 0.00 | 0.00 | 561.05 | 450.00 | 1452.23 | 849.69 | 0.00 | 0.00 | 167907.96 | 0.00 | 0.00 | 0.00 | -729.82 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 15-DEC-08:61 | 0.00 | 0.00 | 57783.57 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 1771.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -960.03 | -58743.47 |
SMSTORE1 | 15-DEC-08:61 | 0.00 | 0.00 | 30452.96 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 862.76 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -555.98 | -30834.05 |
SMSTORE2 | 05-FEB-08:61 | 0.00 | 0.00 | 31398.20 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -237.81 | 0.00 | -576.70 | -30658.51 |
SMSTORE3 | 05-FEB-08:61 | 0.00 | 0.00 | 31263.55 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -233.44 | 0.00 | -571.80 | -30533.12 |
SMSTORE4 | 05-FEB-08:61 | 0.00 | 0.00 | 31259.87 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -229.64 | 0.00 | -567.20 | -30537.85 |
LGSTORE2 | 15-DEC-08:61 | 0.00 | 0.00 | 55216.43 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 1757.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -961.12 | -56161.25 |
SMSTORE5 | 15-DEC-08:61 | 0.00 | 0.00 | 28012.10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 878.64 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -535.01 | -28430.05 |
SMSTORE6 | 15-DEC-08:61 | 0.00 | 0.00 | 27903.59 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 880.25 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -533.31 | -28324.85 |
SMSTORE7 | 15-DEC-08:61 | 0.00 | 0.00 | 27821.03 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 887.07 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -525.65 | -28256.77 |
SMSTORE8 | 15-DEC-08:61 | 0.00 | 0.00 | 30344.38 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 915.62 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -502.59 | -30831.73 |
Total Facility | 06-FEB-08:61 | 0.00 | 0.00 | 266223.91 | 0.00 | 0.00 | 0.00 | 734.92 | 450.00 | 1452.23 | 2496.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5749.64 | -265608.33 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4297 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.4297 | 0.1694 | 1.0000 | Not calculated | 0.4115 | 0.1694 | ||
PSZ-AC_2:2 | 1.2989 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2989 | 0.1584 | 1.0000 | Not calculated | 0.2057 | 0.1584 | ||
PSZ-AC_3:3 | 1.3701 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3701 | 0.1502 | 1.0000 | Not calculated | 0.2057 | 0.1502 | ||
PSZ-AC_4:4 | 1.3624 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3624 | 0.1510 | 1.0000 | Not calculated | 0.2057 | 0.1510 | ||
PSZ-AC_5:5 | 1.3621 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3621 | 0.1510 | 1.0000 | Not calculated | 0.2057 | 0.1510 | ||
PSZ-AC_6:6 | 2.2890 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2890 | 0.1798 | 1.0000 | Not calculated | 0.4115 | 0.1798 | ||
PSZ-AC_7:7 | 1.1639 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1868 | 0.1734 | 1.0000 | Not calculated | 0.2057 | 0.1734 | ||
PSZ-AC_8:8 | 1.1580 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1804 | 0.1743 | 1.0000 | Not calculated | 0.2057 | 0.1743 | ||
PSZ-AC_9:9 | 1.1532 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1792 | 0.1745 | 1.0000 | Not calculated | 0.2057 | 0.1745 | ||
PSZ-AC_10:10 | 1.2916 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2916 | 0.1593 | 1.0000 | Not calculated | 0.2057 | 0.1593 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4297 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.4297 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1694 | ||
PSZ-AC_2:2 | 1.2989 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2989 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1584 | ||
PSZ-AC_3:3 | 1.3701 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3701 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1502 | ||
PSZ-AC_4:4 | 1.3624 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3624 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1510 | ||
PSZ-AC_5:5 | 1.3621 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3621 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1510 | ||
PSZ-AC_6:6 | 2.2890 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2890 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1798 | ||
PSZ-AC_7:7 | 1.1639 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1639 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1768 | ||
PSZ-AC_8:8 | 1.1580 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1580 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1777 | ||
PSZ-AC_9:9 | 1.1532 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1532 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1784 | ||
PSZ-AC_10:10 | 1.2916 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2916 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1593 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4297 | 2.4297 | 2.4297 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2989 | 1.2989 | 1.2989 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3701 | 1.3701 | 1.3701 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3624 | 1.3624 | 1.3624 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3621 | 1.3621 | 1.3621 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2890 | 2.2890 | 2.2890 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1639 | 1.1639 | 1.1639 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1580 | 1.1580 | 1.1580 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1532 | 1.1532 | 1.1532 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2916 | 1.2916 | 1.2916 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4297 | 2.4297 | 2.4297 | 2.4297 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2989 | 1.2989 | 1.2989 | 1.2989 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3701 | 1.3701 | 1.3701 | 1.3701 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3624 | 1.3624 | 1.3624 | 1.3624 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3621 | 1.3621 | 1.3621 | 1.3621 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.2890 | 2.2890 | 2.2890 | 2.2890 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1639 | 1.1868 | 1.1639 | 1.1639 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1580 | 1.1804 | 1.1580 | 1.1580 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1532 | 1.1792 | 1.1532 | 1.1532 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2916 | 1.2916 | 1.2916 | 1.2916 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4297 | 2.4297 | 2.4297 | No | 0.4115 | 0.3489 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2989 | 1.2989 | 1.2989 | No | 0.2057 | 0.3694 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3701 | 1.3701 | 1.3701 | No | 0.2057 | 0.3647 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3624 | 1.3624 | 1.3624 | No | 0.2057 | 0.3607 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3621 | 1.3621 | 1.3621 | No | 0.2057 | 0.3537 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2890 | 2.2890 | 2.2890 | No | 0.4115 | 0.3638 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1639 | 1.1639 | 1.1639 | No | 0.2057 | 0.3421 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1580 | 1.1580 | 1.1580 | No | 0.2057 | 0.3421 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1532 | 1.1532 | 1.1532 | No | 0.2057 | 0.3323 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2916 | 1.2916 | 1.2916 | No | 0.2057 | 0.2764 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4297 | 2.4297 | 2.4297 | 2.4297 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2989 | 1.2989 | 1.2989 | 1.2989 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3701 | 1.3701 | 1.3701 | 1.3701 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3624 | 1.3624 | 1.3624 | 1.3624 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3621 | 1.3621 | 1.3621 | 1.3621 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.2890 | 2.2890 | 2.2890 | 2.2890 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1639 | 1.1639 | 1.1639 | 1.1639 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1580 | 1.1580 | 1.1580 | 1.1580 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1532 | 1.1532 | 1.1532 | 1.1532 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2916 | 1.2916 | 1.2916 | 1.2916 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 122.70 | 125973.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 125.99 | 44198.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 408.34 | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.06 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 116.47 | 10288.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.52 | 2235.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 864.53 |
Natural Gas | 0.00 | 122.70 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 987.23 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 195.35 |
Space Heating | 0.00 |
Space Cooling | 60.27 |
Fans (All) | 55.72 |
Service Water Heating | 12.21 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 413.59 |
Subtotal | 413.59 |
Natural Gas [MJ/m2] | |
Space Heating | 58.70 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 58.70 |
Subtotal | 58.70 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 41.36 |
Space Heating | 12.43 |
Space Cooling | 12.76 |
Fans (All) | 11.80 |
Service Water Heating | 2.59 |
Receptacle Equipment | 12.98 |
Miscellaneous | 6.08 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8741.67 | 18.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
Min | 8741.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 18.33 | 0.00 | 0.00 | 0.00 |
Average | 8750.03 | 9.97 | 0.00 | 0.00 | 0.00 |
Sum | 87500.33 | 99.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25465.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25465.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25466.67 | 8.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93174.00 | 37.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45896.50 | 15.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45897.00 | 15.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45898.00 | 14.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45891.50 | 20.50 | 0.00 | 0.00 | 0.00 |
Min | 25465.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93174.00 | 37.00 | 0.00 | 0.00 | 0.00 |
Average | 48597.27 | 12.93 | 0.00 | 0.00 | 0.00 |
Sum | 485972.67 | 129.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8724.33 | 35.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8722.00 | 38.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8727.17 | 32.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8727.00 | 33.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8729.17 | 30.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8730.50 | 29.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
Min | 8722.00 | 6.83 | 0.00 | 0.00 | 0.00 |
Max | 8753.17 | 38.00 | 0.00 | 0.00 | 0.00 |
Average | 8732.27 | 27.73 | 0.00 | 0.00 | 0.00 |
Sum | 87322.67 | 277.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25470.83 | 4.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25470.83 | 4.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25471.17 | 3.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93195.00 | 16.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45904.50 | 7.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45904.50 | 7.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45905.00 | 7.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45903.00 | 9.00 | 0.00 | 0.00 | 0.00 |
Min | 25470.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93195.00 | 16.00 | 0.00 | 0.00 | 0.00 |
Average | 48604.28 | 5.92 | 0.00 | 0.00 | 0.00 |
Sum | 486042.83 | 59.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.428356E+10 | 9855.40 | 20-JAN-00:02 | -6.9 | -7.0 | 0.110114E+10 | 1599.05 | 01-JAN-13:00 | -6.9 | -7.0 |
February | 0.421241E+10 | 8630.73 | 04-FEB-00:03 | -3.9 | -5.7 | 0.102860E+10 | 1685.84 | 12-FEB-17:30 | 15.25 | 4.88 |
March | 0.563563E+10 | 6970.76 | 11-MAR-00:05 | 0.68 | -3.1 | 0.124411E+10 | 1685.85 | 12-MAR-17:40 | 19.07 | 5.65 |
April | 0.771302E+10 | 9800.54 | 13-APR-16:30 | 25.85 | 10.20 | 0.132034E+10 | 1685.85 | 02-APR-16:30 | 25.85 | 10.20 |
May | 0.100678E+11 | 11718.73 | 19-MAY-16:50 | 30.00 | 12.24 | 0.139022E+10 | 1685.92 | 28-MAY-12:09 | 23.07 | 13.79 |
June | 0.142030E+11 | 34014.61 | 28-JUN-07:02 | 24.68 | 13.99 | 0.135431E+10 | 1685.95 | 25-JUN-16:10 | 24.68 | 13.99 |
July | 0.172688E+11 | 34670.28 | 20-JUL-07:02 | 22.15 | 14.28 | 0.141280E+10 | 1686.04 | 07-JUL-12:00 | 22.15 | 14.28 |
August | 0.170902E+11 | 36222.50 | 19-AUG-07:02 | 21.65 | 13.20 | 0.139408E+10 | 1685.99 | 26-AUG-12:09 | 25.47 | 18.91 |
September | 0.146133E+11 | 34316.34 | 03-SEP-07:02 | 21.05 | 13.47 | 0.136512E+10 | 1686.00 | 23-SEP-12:00 | 23.30 | 16.04 |
October | 0.109448E+11 | 24502.43 | 02-OCT-07:03 | 16.65 | 12.53 | 0.137011E+10 | 1685.89 | 07-OCT-12:09 | 23.90 | 13.90 |
November | 0.688766E+10 | 7650.58 | 02-NOV-17:10 | 15.92 | 9.45 | 0.118411E+10 | 1685.78 | 24-NOV-13:00 | 15.00 | 5.08 |
December | 0.435523E+10 | 9040.28 | 15-DEC-00:03 | -5.0 | -9.0 | 0.108229E+10 | 1417.84 | 02-DEC-13:00 | -5.0 | -9.0 |
Annual Sum or Average | 0.117275E+12 | 0.152472E+11 | ||||||||
Minimum of Months | 0.421241E+10 | 6970.76 | -6.9 | -9.0 | 0.102860E+10 | 1417.84 | -6.9 | -9.0 | ||
Maximum of Months | 0.172688E+11 | 36222.50 | 30.00 | 14.28 | 0.141280E+10 | 1686.04 | 25.85 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221833E+10 | 3603.72 | 25-JAN-21:00 | 0.60 | -4.7 | 0.600028E+09 | 843.08 | 15-JAN-18:00 | 0.60 | -4.7 |
February | 0.228535E+10 | 3977.83 | 14-FEB-15:00 | 21.70 | 7.37 | 0.553772E+09 | 842.90 | 26-FEB-18:00 | 10.60 | 3.65 |
March | 0.307098E+10 | 15250.64 | 12-MAR-17:35 | 19.07 | 5.65 | 0.663575E+09 | 842.90 | 26-MAR-16:10 | 20.50 | 7.71 |
April | 0.468864E+10 | 15996.68 | 30-APR-20:25 | 17.75 | 5.13 | 0.670029E+09 | 842.90 | 02-APR-12:30 | 17.75 | 5.13 |
May | 0.609294E+10 | 15960.79 | 12-MAY-21:55 | 17.80 | 7.72 | 0.695047E+09 | 843.18 | 29-MAY-17:40 | 23.50 | 13.67 |
June | 0.798087E+10 | 19226.92 | 26-JUN-07:02 | 22.98 | 13.46 | 0.674705E+09 | 843.13 | 11-JUN-17:40 | 22.98 | 13.46 |
July | 0.940746E+10 | 18625.48 | 20-JUL-07:02 | 22.15 | 14.28 | 0.705459E+09 | 843.00 | 07-JUL-12:00 | 22.15 | 14.28 |
August | 0.929736E+10 | 19722.16 | 19-AUG-07:02 | 21.65 | 13.20 | 0.695579E+09 | 842.99 | 06-AUG-17:49 | 21.65 | 13.20 |
September | 0.813525E+10 | 19175.71 | 03-SEP-07:02 | 21.05 | 13.47 | 0.678308E+09 | 843.25 | 24-SEP-17:40 | 23.87 | 15.05 |
October | 0.621939E+10 | 16748.84 | 11-OCT-20:35 | 15.33 | 7.60 | 0.690738E+09 | 843.44 | 01-OCT-17:40 | 15.33 | 7.60 |
November | 0.339977E+10 | 11513.51 | 02-NOV-22:51 | 10.00 | 7.26 | 0.640292E+09 | 842.90 | 05-NOV-17:00 | 10.60 | 2.64 |
December | 0.235528E+10 | 4289.96 | 22-DEC-09:32 | -4.1 | -6.2 | 0.582201E+09 | 842.90 | 31-DEC-18:00 | 6.10 | -0.9 |
Annual Sum or Average | 0.651516E+11 | 0.784973E+10 | ||||||||
Minimum of Months | 0.221833E+10 | 3603.72 | -4.1 | -6.2 | 0.553772E+09 | 842.90 | 0.60 | -4.7 | ||
Maximum of Months | 0.940746E+10 | 19722.16 | 22.98 | 14.28 | 0.705459E+09 | 843.44 | 23.87 | 15.05 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184191E+10 | 4341.03 | 04-JAN-08:61 | -3.1 | -4.3 | 0.338227E+09 | 719.20 | 14-JAN-13:00 | 11.10 | 2.60 |
February | 0.186395E+10 | 3904.66 | 11-FEB-08:61 | -1.1 | -2.6 | 0.315218E+09 | 766.23 | 11-FEB-13:00 | 13.90 | 4.65 |
March | 0.244185E+10 | 3586.40 | 25-MAR-07:01 | 1.12 | -2.2 | 0.396999E+09 | 842.89 | 25-MAR-12:20 | 17.40 | 6.23 |
April | 0.330417E+10 | 5211.04 | 29-APR-13:00 | 22.80 | 9.09 | 0.401165E+09 | 842.90 | 29-APR-12:20 | 22.80 | 9.09 |
May | 0.427141E+10 | 6869.99 | 22-MAY-06:03 | 17.57 | 12.19 | 0.423548E+09 | 842.90 | 27-MAY-12:09 | 23.98 | 12.77 |
June | 0.595927E+10 | 21464.87 | 26-JUN-06:02 | 19.97 | 12.34 | 0.417146E+09 | 842.93 | 24-JUN-12:09 | 19.97 | 12.34 |
July | 0.707352E+10 | 21592.61 | 22-JUL-06:02 | 22.15 | 12.93 | 0.420543E+09 | 842.98 | 22-JUL-12:00 | 36.10 | 17.61 |
August | 0.710270E+10 | 22185.50 | 19-AUG-06:02 | 18.77 | 12.01 | 0.431968E+09 | 842.97 | 26-AUG-12:09 | 25.47 | 18.91 |
September | 0.598641E+10 | 20657.25 | 03-SEP-07:02 | 21.05 | 13.47 | 0.410811E+09 | 842.98 | 23-SEP-12:00 | 23.30 | 16.04 |
October | 0.455231E+10 | 20808.76 | 02-OCT-06:02 | 16.60 | 12.55 | 0.408782E+09 | 842.92 | 07-OCT-12:09 | 23.90 | 13.90 |
November | 0.280900E+10 | 4268.44 | 27-NOV-08:61 | -3.0 | -5.9 | 0.366161E+09 | 819.37 | 18-NOV-13:00 | -3.0 | -5.9 |
December | 0.189011E+10 | 3777.53 | 30-DEC-08:61 | -0.8 | -3.8 | 0.324195E+09 | 764.39 | 02-DEC-13:00 | -0.8 | -3.8 |
Annual Sum or Average | 0.490966E+11 | 0.465476E+10 | ||||||||
Minimum of Months | 0.184191E+10 | 3586.40 | -3.1 | -5.9 | 0.315218E+09 | 719.20 | -3.0 | -5.9 | ||
Maximum of Months | 0.710270E+10 | 22185.50 | 22.80 | 13.47 | 0.431968E+09 | 842.98 | 36.10 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169760E+10 | 4283.65 | 04-JAN-08:61 | -3.1 | -4.3 | 0.335013E+09 | 712.96 | 14-JAN-13:00 | 11.10 | 2.60 |
February | 0.173108E+10 | 3872.51 | 11-FEB-08:61 | -1.1 | -2.6 | 0.313044E+09 | 757.29 | 11-FEB-13:00 | 13.90 | 4.65 |
March | 0.230769E+10 | 3550.58 | 25-MAR-07:01 | 1.12 | -2.2 | 0.393991E+09 | 842.89 | 25-MAR-12:20 | 17.40 | 6.23 |
April | 0.320237E+10 | 5199.91 | 29-APR-13:00 | 22.80 | 9.09 | 0.400117E+09 | 842.90 | 22-APR-12:50 | 22.80 | 9.09 |
May | 0.423693E+10 | 7126.82 | 22-MAY-06:03 | 17.57 | 12.19 | 0.423265E+09 | 842.90 | 27-MAY-12:09 | 23.98 | 12.77 |
June | 0.597813E+10 | 22177.25 | 26-JUN-06:02 | 19.97 | 12.34 | 0.417141E+09 | 842.93 | 24-JUN-12:09 | 19.97 | 12.34 |
July | 0.711686E+10 | 21529.51 | 22-JUL-06:02 | 22.15 | 12.93 | 0.420544E+09 | 842.98 | 22-JUL-12:00 | 36.10 | 17.61 |
August | 0.714201E+10 | 22118.12 | 19-AUG-06:02 | 18.77 | 12.01 | 0.431969E+09 | 842.97 | 26-AUG-12:09 | 25.47 | 18.91 |
September | 0.600881E+10 | 20733.54 | 01-SEP-06:02 | 18.40 | 12.94 | 0.410808E+09 | 842.98 | 23-SEP-12:00 | 23.30 | 16.04 |
October | 0.449454E+10 | 21627.80 | 02-OCT-06:02 | 16.60 | 12.55 | 0.408186E+09 | 842.92 | 07-OCT-12:09 | 23.90 | 13.90 |
November | 0.267605E+10 | 3928.64 | 02-NOV-17:10 | 15.92 | 9.45 | 0.361821E+09 | 805.41 | 18-NOV-13:00 | 12.80 | 3.25 |
December | 0.173211E+10 | 3428.04 | 02-DEC-08:61 | 1.28 | -3.3 | 0.322795E+09 | 752.22 | 02-DEC-13:00 | 10.60 | 3.19 |
Annual Sum or Average | 0.483242E+11 | 0.463869E+10 | ||||||||
Minimum of Months | 0.169760E+10 | 3428.04 | -3.1 | -4.3 | 0.313044E+09 | 712.96 | 10.60 | 2.60 | ||
Maximum of Months | 0.714201E+10 | 22177.25 | 22.80 | 12.94 | 0.431969E+09 | 842.98 | 36.10 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149865E+10 | 3835.37 | 20-JAN-11:13 | -1.8 | -1.9 | 0.331214E+09 | 701.84 | 14-JAN-13:00 | -1.8 | -1.9 |
February | 0.152776E+10 | 3551.04 | 06-FEB-10:03 | -0.8 | -4.5 | 0.310230E+09 | 742.19 | 11-FEB-13:00 | 13.90 | 4.65 |
March | 0.208633E+10 | 3487.58 | 25-MAR-07:01 | 1.12 | -2.2 | 0.388925E+09 | 842.88 | 25-MAR-12:39 | 17.60 | 6.30 |
April | 0.296650E+10 | 5015.24 | 29-APR-13:00 | 22.80 | 9.09 | 0.397930E+09 | 842.90 | 29-APR-12:30 | 22.80 | 9.09 |
May | 0.401415E+10 | 6128.54 | 22-MAY-06:03 | 17.57 | 12.19 | 0.422474E+09 | 842.90 | 27-MAY-12:09 | 23.98 | 12.77 |
June | 0.577543E+10 | 21200.48 | 26-JUN-06:02 | 19.97 | 12.34 | 0.417086E+09 | 842.93 | 24-JUN-12:09 | 19.97 | 12.34 |
July | 0.693607E+10 | 21392.47 | 22-JUL-06:02 | 22.15 | 12.93 | 0.420507E+09 | 842.98 | 22-JUL-12:00 | 36.10 | 17.61 |
August | 0.695671E+10 | 21459.16 | 19-AUG-06:02 | 18.77 | 12.01 | 0.431932E+09 | 842.97 | 26-AUG-12:09 | 25.47 | 18.91 |
September | 0.582143E+10 | 20493.20 | 03-SEP-07:02 | 21.05 | 13.47 | 0.410765E+09 | 842.98 | 23-SEP-12:00 | 23.30 | 16.04 |
October | 0.429233E+10 | 20459.11 | 02-OCT-06:02 | 16.60 | 12.55 | 0.407040E+09 | 842.92 | 07-OCT-12:09 | 23.90 | 13.90 |
November | 0.248440E+10 | 3714.51 | 04-NOV-07:03 | 0.78 | 0.12 | 0.355609E+09 | 785.64 | 18-NOV-13:00 | 12.80 | 3.25 |
December | 0.150371E+10 | 3357.08 | 02-DEC-08:61 | 1.28 | -3.3 | 0.321283E+09 | 733.90 | 02-DEC-13:00 | 10.60 | 3.19 |
Annual Sum or Average | 0.458635E+11 | 0.461499E+10 | ||||||||
Minimum of Months | 0.149865E+10 | 3357.08 | -1.8 | -4.5 | 0.310230E+09 | 701.84 | -1.8 | -1.9 | ||
Maximum of Months | 0.695671E+10 | 21459.16 | 22.80 | 13.47 | 0.431932E+09 | 842.98 | 36.10 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213237E+10 | 5982.61 | 13-JAN-17:43 | 3.03 | -0.9 | 0.111947E+10 | 1889.02 | 14-JAN-15:00 | 12.20 | 3.09 |
February | 0.223372E+10 | 7123.81 | 16-FEB-09:03 | 0.60 | -0.3 | 0.105082E+10 | 2036.63 | 11-FEB-15:00 | 0.60 | -0.3 |
March | 0.325377E+10 | 5659.98 | 17-MAR-19:30 | 4.70 | 3.03 | 0.130708E+10 | 2247.80 | 25-MAR-14:00 | 18.90 | 6.69 |
April | 0.467237E+10 | 8812.84 | 28-APR-14:30 | 24.70 | 10.35 | 0.135348E+10 | 2247.80 | 01-APR-14:50 | 24.70 | 10.35 |
May | 0.651741E+10 | 10370.39 | 19-MAY-15:00 | 30.00 | 12.81 | 0.144102E+10 | 2247.80 | 27-MAY-14:09 | 25.00 | 12.86 |
June | 0.972917E+10 | 34921.95 | 26-JUN-07:02 | 22.98 | 13.46 | 0.142965E+10 | 2247.95 | 24-JUN-14:39 | 22.98 | 13.46 |
July | 0.118534E+11 | 33529.22 | 05-JUL-07:02 | 24.60 | 15.17 | 0.143884E+10 | 2248.07 | 08-JUL-14:00 | 32.80 | 18.95 |
August | 0.119347E+11 | 34860.72 | 19-AUG-07:02 | 21.65 | 13.20 | 0.148045E+10 | 2247.97 | 26-AUG-14:00 | 23.30 | 17.03 |
September | 0.984086E+10 | 33404.87 | 03-SEP-08:62 | 23.68 | 14.11 | 0.141000E+10 | 2247.99 | 23-SEP-14:09 | 22.80 | 15.77 |
October | 0.704945E+10 | 30271.31 | 02-OCT-07:03 | 16.65 | 12.53 | 0.138328E+10 | 2247.88 | 07-OCT-14:39 | 24.23 | 14.18 |
November | 0.402667E+10 | 7101.22 | 04-NOV-08:62 | 1.70 | 0.61 | 0.117625E+10 | 2079.33 | 18-NOV-15:50 | 13.30 | 3.02 |
December | 0.200488E+10 | 6467.06 | 14-DEC-12:23 | 1.70 | -5.0 | 0.109563E+10 | 1952.63 | 02-DEC-15:30 | 1.70 | -5.0 |
Annual Sum or Average | 0.752488E+11 | 0.156860E+11 | ||||||||
Minimum of Months | 0.200488E+10 | 5659.98 | 0.60 | -5.0 | 0.105082E+10 | 1889.02 | 0.60 | -5.0 | ||
Maximum of Months | 0.119347E+11 | 34921.95 | 30.00 | 15.17 | 0.148045E+10 | 2248.07 | 32.80 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100583E+10 | 3428.63 | 21-JAN-18:43 | 0.47 | -2.9 | 0.558665E+09 | 943.30 | 14-JAN-15:00 | 0.47 | -2.9 |
February | 0.105070E+10 | 3497.75 | 16-FEB-09:03 | 0.60 | -0.3 | 0.524223E+09 | 1008.81 | 11-FEB-15:00 | 0.60 | -0.3 |
March | 0.153600E+10 | 2810.46 | 17-MAR-19:30 | 4.70 | 3.03 | 0.650276E+09 | 1123.87 | 25-MAR-14:50 | 19.08 | 6.80 |
April | 0.228863E+10 | 4511.82 | 28-APR-14:30 | 24.70 | 10.35 | 0.674935E+09 | 1123.87 | 22-APR-14:00 | 24.70 | 10.35 |
May | 0.328422E+10 | 5371.98 | 19-MAY-15:00 | 30.00 | 12.81 | 0.719925E+09 | 1123.87 | 27-MAY-14:09 | 25.00 | 12.86 |
June | 0.499859E+10 | 17937.32 | 26-JUN-07:02 | 22.98 | 13.46 | 0.714791E+09 | 1123.94 | 24-JUN-14:39 | 22.98 | 13.46 |
July | 0.611971E+10 | 17244.49 | 05-JUL-07:02 | 24.60 | 15.17 | 0.719367E+09 | 1124.01 | 08-JUL-14:00 | 32.80 | 18.95 |
August | 0.614758E+10 | 17914.10 | 07-AUG-07:02 | 20.87 | 13.47 | 0.740183E+09 | 1123.95 | 26-AUG-14:00 | 23.30 | 17.03 |
September | 0.505035E+10 | 17146.47 | 03-SEP-08:62 | 23.68 | 14.11 | 0.704959E+09 | 1123.96 | 23-SEP-14:09 | 22.80 | 15.77 |
October | 0.355890E+10 | 14694.39 | 02-OCT-07:03 | 16.65 | 12.53 | 0.691203E+09 | 1123.91 | 07-OCT-14:39 | 24.23 | 14.18 |
November | 0.194110E+10 | 3490.25 | 04-NOV-08:62 | 1.70 | 0.61 | 0.585309E+09 | 1033.67 | 18-NOV-15:50 | 13.30 | 3.02 |
December | 0.937377E+09 | 4074.99 | 22-DEC-10:13 | -2.6 | -5.3 | 0.547539E+09 | 971.44 | 02-DEC-15:30 | -2.6 | -5.3 |
Annual Sum or Average | 0.379190E+11 | 0.783137E+10 | ||||||||
Minimum of Months | 0.937377E+09 | 2810.46 | -2.6 | -5.3 | 0.524223E+09 | 943.30 | -2.6 | -5.3 | ||
Maximum of Months | 0.614758E+10 | 17937.32 | 30.00 | 15.17 | 0.740183E+09 | 1124.01 | 32.80 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.942822E+09 | 2649.34 | 31-JAN-14:43 | 4.60 | -1.9 | 0.556894E+09 | 937.07 | 14-JAN-15:00 | 4.60 | -1.9 |
February | 0.987839E+09 | 3100.69 | 07-FEB-20:53 | 2.20 | -1.0 | 0.522568E+09 | 1000.67 | 11-FEB-15:00 | 15.00 | 4.95 |
March | 0.145962E+10 | 2715.78 | 17-MAR-19:20 | 5.17 | 3.27 | 0.646466E+09 | 1123.87 | 25-MAR-14:39 | 19.27 | 6.91 |
April | 0.220355E+10 | 4435.31 | 28-APR-14:30 | 24.70 | 10.35 | 0.672772E+09 | 1123.87 | 22-APR-14:09 | 24.70 | 10.35 |
May | 0.320450E+10 | 5316.19 | 19-MAY-15:00 | 30.00 | 12.81 | 0.719131E+09 | 1123.87 | 27-MAY-14:09 | 25.00 | 12.86 |
June | 0.493352E+10 | 17821.62 | 26-JUN-07:02 | 22.98 | 13.46 | 0.714766E+09 | 1123.94 | 24-JUN-14:39 | 22.98 | 13.46 |
July | 0.606112E+10 | 17128.77 | 05-JUL-07:02 | 24.60 | 15.17 | 0.719358E+09 | 1124.01 | 08-JUL-14:00 | 32.80 | 18.95 |
August | 0.608611E+10 | 17797.20 | 07-AUG-07:02 | 20.87 | 13.47 | 0.740177E+09 | 1123.95 | 26-AUG-14:00 | 23.30 | 17.03 |
September | 0.498788E+10 | 17026.30 | 03-SEP-08:62 | 23.68 | 14.11 | 0.704947E+09 | 1123.96 | 23-SEP-14:09 | 22.80 | 15.77 |
October | 0.348728E+10 | 14268.55 | 02-OCT-07:03 | 16.65 | 12.53 | 0.690330E+09 | 1123.91 | 07-OCT-14:39 | 24.23 | 14.18 |
November | 0.186747E+10 | 3470.12 | 04-NOV-08:62 | 1.70 | 0.61 | 0.581257E+09 | 1025.74 | 18-NOV-15:50 | 13.30 | 3.02 |
December | 0.878596E+09 | 4113.77 | 21-DEC-10:13 | -2.8 | -4.8 | 0.546942E+09 | 963.69 | 02-DEC-15:30 | -2.8 | -4.8 |
Annual Sum or Average | 0.371003E+11 | 0.781561E+10 | ||||||||
Minimum of Months | 0.878596E+09 | 2649.34 | -2.8 | -4.8 | 0.522568E+09 | 937.07 | -2.8 | -4.8 | ||
Maximum of Months | 0.608611E+10 | 17821.62 | 30.00 | 15.17 | 0.740177E+09 | 1124.01 | 32.80 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.767331E+09 | 3310.10 | 13-JAN-20:53 | 1.10 | -2.1 | 0.552900E+09 | 919.08 | 14-JAN-15:00 | 12.20 | 3.09 |
February | 0.796888E+09 | 3354.85 | 02-FEB-20:23 | 0.85 | -2.5 | 0.518593E+09 | 997.43 | 14-FEB-17:10 | 20.37 | 6.95 |
March | 0.125687E+10 | 2578.87 | 17-MAR-19:00 | 6.10 | 3.71 | 0.637289E+09 | 1123.84 | 11-MAR-15:09 | 6.10 | 3.71 |
April | 0.201017E+10 | 4277.12 | 28-APR-14:30 | 24.70 | 10.35 | 0.667591E+09 | 1123.87 | 22-APR-14:20 | 24.70 | 10.35 |
May | 0.301082E+10 | 5209.70 | 19-MAY-15:00 | 30.00 | 12.81 | 0.716987E+09 | 1123.87 | 27-MAY-14:09 | 25.00 | 12.86 |
June | 0.482052E+10 | 17711.74 | 26-JUN-07:02 | 22.98 | 13.46 | 0.714681E+09 | 1123.93 | 24-JUN-14:39 | 22.98 | 13.46 |
July | 0.600593E+10 | 17025.22 | 05-JUL-07:02 | 24.60 | 15.17 | 0.719348E+09 | 1124.00 | 08-JUL-14:00 | 32.80 | 18.95 |
August | 0.602379E+10 | 17710.61 | 07-AUG-07:02 | 20.87 | 13.47 | 0.740170E+09 | 1123.95 | 26-AUG-14:00 | 23.30 | 17.03 |
September | 0.488330E+10 | 16927.31 | 03-SEP-08:62 | 23.68 | 14.11 | 0.704918E+09 | 1123.96 | 23-SEP-14:09 | 22.80 | 15.77 |
October | 0.332829E+10 | 13123.53 | 02-OCT-07:03 | 16.65 | 12.53 | 0.688083E+09 | 1123.91 | 07-OCT-14:50 | 24.32 | 14.18 |
November | 0.168418E+10 | 3397.58 | 04-NOV-08:62 | 1.70 | 0.61 | 0.573164E+09 | 1009.59 | 18-NOV-15:50 | 13.30 | 3.02 |
December | 0.681059E+09 | 3901.52 | 14-DEC-20:42 | -1.7 | -6.9 | 0.545633E+09 | 945.97 | 02-DEC-15:30 | -1.7 | -6.9 |
Annual Sum or Average | 0.352691E+11 | 0.777936E+10 | ||||||||
Minimum of Months | 0.681059E+09 | 2578.87 | -1.7 | -6.9 | 0.518593E+09 | 919.08 | -1.7 | -6.9 | ||
Maximum of Months | 0.602379E+10 | 17711.74 | 30.00 | 15.17 | 0.740170E+09 | 1124.00 | 32.80 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.398232E+09 | 3340.39 | 13-JAN-18:53 | 0.60 | -2.2 | 0.547945E+09 | 880.49 | 14-JAN-15:00 | 12.20 | 3.09 |
February | 0.433366E+09 | 3147.67 | 16-FEB-11:53 | 1.70 | 1.16 | 0.512411E+09 | 997.43 | 13-FEB-17:10 | 1.70 | 1.16 |
March | 0.859864E+09 | 2250.31 | 03-MAR-18:45 | 5.97 | 0.85 | 0.624298E+09 | 1123.84 | 25-MAR-14:09 | 19.82 | 7.25 |
April | 0.184858E+10 | 4434.87 | 28-APR-13:00 | 24.40 | 9.84 | 0.661471E+09 | 1123.87 | 22-APR-14:09 | 24.40 | 9.84 |
May | 0.296641E+10 | 5470.76 | 19-MAY-13:00 | 28.90 | 12.73 | 0.713708E+09 | 1123.87 | 27-MAY-14:09 | 25.00 | 12.86 |
June | 0.529737E+10 | 17678.84 | 29-JUN-07:02 | 27.57 | 17.14 | 0.714415E+09 | 1123.89 | 03-JUN-14:00 | 27.57 | 17.14 |
July | 0.678739E+10 | 18089.83 | 05-JUL-07:02 | 24.60 | 15.17 | 0.719448E+09 | 1124.02 | 29-JUL-14:09 | 32.15 | 18.57 |
August | 0.676061E+10 | 19096.60 | 07-AUG-07:02 | 20.87 | 13.47 | 0.740246E+09 | 1123.96 | 26-AUG-14:00 | 23.30 | 17.03 |
September | 0.526777E+10 | 18455.10 | 03-SEP-08:62 | 23.68 | 14.11 | 0.704921E+09 | 1123.97 | 23-SEP-14:00 | 22.80 | 15.63 |
October | 0.328059E+10 | 9777.17 | 02-OCT-07:03 | 16.65 | 12.53 | 0.685205E+09 | 1123.91 | 07-OCT-14:50 | 24.32 | 14.18 |
November | 0.127831E+10 | 2699.19 | 04-NOV-13:03 | 4.08 | 1.89 | 0.563344E+09 | 997.42 | 02-NOV-16:19 | 4.08 | 1.89 |
December | 0.310456E+09 | 2996.69 | 28-DEC-10:33 | 2.43 | -1.1 | 0.543951E+09 | 912.95 | 02-DEC-15:30 | 2.43 | -1.1 |
Annual Sum or Average | 0.354890E+11 | 0.773136E+10 | ||||||||
Minimum of Months | 0.310456E+09 | 2250.31 | 0.60 | -2.2 | 0.512411E+09 | 880.49 | 1.70 | -1.1 | ||
Maximum of Months | 0.678739E+10 | 19096.60 | 28.90 | 17.14 | 0.740246E+09 | 1124.02 | 32.15 | 18.57 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.964868E+09 | 57770.39 | 21-JAN-08:61 | -4.5 |
February | 0.627231E+09 | 57769.05 | 25-FEB-08:61 | -0.3 |
March | 0.235876E+09 | 57738.52 | 06-MAR-08:61 | 1.75 |
April | 94851388.98 | 23373.22 | 08-APR-07:01 | 2.57 |
May | 45596255.65 | 1011.58 | 06-MAY-07:13 | 7.23 |
June | 28360548.37 | 2008.59 | 28-JUN-07:04 | 24.68 |
July | 33150969.23 | 2014.10 | 22-JUL-07:04 | 24.87 |
August | 34982678.57 | 2059.60 | 19-AUG-07:04 | 21.65 |
September | 27661063.85 | 1982.74 | 03-SEP-07:04 | 21.05 |
October | 74822091.95 | 43395.28 | 26-OCT-07:01 | -2.1 |
November | 0.120327E+09 | 57749.67 | 27-NOV-08:61 | -3.0 |
December | 0.800037E+09 | 57783.59 | 15-DEC-08:61 | -7.2 |
Annual Sum or Average | 0.308776E+10 | |||
Minimum of Months | 27661063.85 | 1011.58 | -7.2 | |
Maximum of Months | 0.964868E+09 | 57783.59 | 24.87 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176973E+09 | 30446.07 | 21-JAN-08:61 | -4.5 |
February | 0.106730E+09 | 30440.13 | 04-FEB-08:61 | -5.7 |
March | 62529132.68 | 22858.99 | 04-MAR-08:61 | 0.78 |
April | 37823769.54 | 570.48 | 18-APR-07:25 | 7.50 |
May | 14128469.01 | 738.67 | 21-MAY-07:07 | 17.07 |
June | 14384817.11 | 1157.99 | 26-JUN-07:04 | 22.98 |
July | 16365673.56 | 1154.86 | 22-JUL-07:04 | 24.87 |
August | 17683927.65 | 1171.81 | 19-AUG-07:04 | 21.65 |
September | 16590561.54 | 1143.89 | 03-SEP-07:04 | 21.05 |
October | 24215952.46 | 1470.95 | 26-OCT-07:01 | -2.1 |
November | 48961315.55 | 583.01 | 04-NOV-07:50 | 1.52 |
December | 0.149363E+09 | 30453.03 | 15-DEC-08:61 | -7.2 |
Annual Sum or Average | 0.685750E+09 | |||
Minimum of Months | 14128469.01 | 570.48 | -7.2 | |
Maximum of Months | 0.176973E+09 | 30453.03 | 24.87 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283445E+09 | 31172.37 | 22-JAN-08:61 | -2.6 |
February | 0.174234E+09 | 31398.21 | 05-FEB-08:61 | -6.5 |
March | 74213613.34 | 18141.86 | 04-MAR-07:02 | -1.3 |
April | 41284577.48 | 823.61 | 08-APR-07:08 | 2.57 |
May | 34472731.46 | 1197.65 | 14-MAY-16:12 | 28.30 |
June | 85224136.45 | 2509.86 | 25-JUN-16:02 | 35.22 |
July | 0.103542E+09 | 2583.53 | 04-JUL-16:02 | 35.68 |
August | 73790315.89 | 2426.38 | 20-AUG-16:02 | 34.90 |
September | 32219122.11 | 1675.63 | 02-SEP-17:02 | 30.92 |
October | 30620443.20 | 5938.85 | 27-OCT-07:10 | -1.9 |
November | 51647487.04 | 5219.04 | 28-NOV-07:03 | -1.9 |
December | 0.262455E+09 | 28258.65 | 22-DEC-07:02 | -6.1 |
Annual Sum or Average | 0.124715E+10 | |||
Minimum of Months | 30620443.20 | 823.61 | -6.5 | |
Maximum of Months | 0.283445E+09 | 31398.21 | 35.68 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345973E+09 | 31040.22 | 22-JAN-08:61 | -2.6 |
February | 0.208156E+09 | 31263.56 | 05-FEB-08:61 | -6.5 |
March | 83410810.66 | 21852.42 | 05-MAR-08:62 | 0.37 |
April | 42990811.21 | 1267.98 | 08-APR-07:06 | 2.57 |
May | 35295132.15 | 1195.99 | 14-MAY-16:12 | 28.30 |
June | 84916253.07 | 2508.39 | 25-JUN-16:02 | 35.22 |
July | 0.102303E+09 | 2582.52 | 04-JUL-16:02 | 35.68 |
August | 72768160.96 | 2424.86 | 20-AUG-16:02 | 34.90 |
September | 31984890.91 | 1674.06 | 02-SEP-17:02 | 30.92 |
October | 30762997.99 | 2673.26 | 26-OCT-06:05 | -1.4 |
November | 55921678.48 | 7278.38 | 28-NOV-07:03 | -1.9 |
December | 0.320648E+09 | 30708.71 | 22-DEC-07:02 | -6.1 |
Annual Sum or Average | 0.141513E+10 | |||
Minimum of Months | 30762997.99 | 1195.99 | -6.5 | |
Maximum of Months | 0.345973E+09 | 31263.56 | 35.68 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.446775E+09 | 31037.58 | 22-JAN-08:61 | -2.6 |
February | 0.263326E+09 | 31259.87 | 05-FEB-08:61 | -6.5 |
March | 0.103288E+09 | 26232.07 | 05-MAR-08:62 | 0.37 |
April | 46802456.69 | 1377.19 | 08-APR-07:05 | 2.57 |
May | 38554115.20 | 1202.73 | 14-MAY-16:12 | 28.30 |
June | 86384250.48 | 2513.99 | 25-JUN-16:02 | 35.22 |
July | 0.105022E+09 | 2588.37 | 04-JUL-16:02 | 35.68 |
August | 74840060.20 | 2430.15 | 20-AUG-16:02 | 34.90 |
September | 32020248.30 | 1680.89 | 02-SEP-17:02 | 30.92 |
October | 34746504.45 | 3751.82 | 26-OCT-06:05 | -1.4 |
November | 66872137.78 | 9354.86 | 27-NOV-07:03 | -4.2 |
December | 0.400074E+09 | 30709.97 | 26-DEC-07:02 | -1.8 |
Annual Sum or Average | 0.169871E+10 | |||
Minimum of Months | 32020248.30 | 1202.73 | -6.5 | |
Maximum of Months | 0.446775E+09 | 31259.87 | 35.68 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101238E+10 | 55212.73 | 17-JAN-08:61 | -3.7 |
February | 0.595047E+09 | 55207.13 | 25-FEB-08:61 | -0.3 |
March | 0.221092E+09 | 55192.03 | 06-MAR-08:61 | 1.75 |
April | 91213178.89 | 20633.39 | 08-APR-07:01 | 2.57 |
May | 70368081.31 | 2251.56 | 14-MAY-16:12 | 28.30 |
June | 74859155.52 | 5007.17 | 25-JUN-16:02 | 35.22 |
July | 0.106065E+09 | 5163.06 | 04-JUL-16:02 | 35.68 |
August | 75923243.47 | 4846.22 | 20-AUG-16:02 | 34.90 |
September | 49958738.85 | 3331.58 | 02-SEP-17:02 | 30.92 |
October | 72481400.82 | 38159.65 | 26-OCT-07:01 | -2.1 |
November | 0.138971E+09 | 55197.27 | 27-NOV-08:61 | -3.0 |
December | 0.856002E+09 | 55216.46 | 15-DEC-08:61 | -7.2 |
Annual Sum or Average | 0.336436E+10 | |||
Minimum of Months | 49958738.85 | 2251.56 | -7.2 | |
Maximum of Months | 0.101238E+10 | 55216.46 | 35.68 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.609778E+09 | 28010.32 | 17-JAN-08:61 | -3.7 |
February | 0.362612E+09 | 28006.43 | 25-FEB-08:61 | -0.3 |
March | 0.133149E+09 | 27998.25 | 06-MAR-08:61 | 1.75 |
April | 51644297.01 | 12688.61 | 08-APR-07:01 | 2.57 |
May | 39699607.92 | 1152.32 | 14-MAY-16:12 | 28.30 |
June | 39307644.48 | 2517.33 | 25-JUN-16:02 | 35.22 |
July | 55128635.87 | 2595.27 | 04-JUL-16:02 | 35.68 |
August | 39509195.12 | 2435.76 | 20-AUG-16:02 | 34.90 |
September | 26160086.32 | 1685.71 | 02-SEP-17:02 | 30.92 |
October | 41570500.78 | 19657.39 | 26-OCT-07:01 | -2.1 |
November | 82231748.08 | 28001.77 | 27-NOV-08:61 | -3.0 |
December | 0.513921E+09 | 28012.11 | 15-DEC-08:61 | -7.2 |
Annual Sum or Average | 0.199471E+10 | |||
Minimum of Months | 26160086.32 | 1152.32 | -7.2 | |
Maximum of Months | 0.609778E+09 | 28012.11 | 35.68 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.658636E+09 | 27902.35 | 17-JAN-08:61 | -3.7 |
February | 0.397205E+09 | 27897.70 | 25-FEB-08:61 | -0.3 |
March | 0.149376E+09 | 27890.50 | 06-MAR-08:61 | 1.75 |
April | 54911086.95 | 16087.41 | 08-APR-07:01 | 2.57 |
May | 41146406.77 | 1151.28 | 14-MAY-16:12 | 28.30 |
June | 39600525.52 | 2518.28 | 25-JUN-16:02 | 35.22 |
July | 55296142.43 | 2596.19 | 04-JUL-16:02 | 35.68 |
August | 39561979.38 | 2436.67 | 20-AUG-16:02 | 34.90 |
September | 26058495.16 | 1686.65 | 02-SEP-17:02 | 30.92 |
October | 44196110.97 | 21069.69 | 26-OCT-07:01 | -2.1 |
November | 87886684.48 | 27893.27 | 27-NOV-08:61 | -3.0 |
December | 0.562207E+09 | 27903.61 | 15-DEC-08:61 | -7.2 |
Annual Sum or Average | 0.215608E+10 | |||
Minimum of Months | 26058495.16 | 1151.28 | -7.2 | |
Maximum of Months | 0.658636E+09 | 27903.61 | 35.68 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.867650E+09 | 27819.13 | 17-JAN-08:61 | -3.7 |
February | 0.544426E+09 | 27815.91 | 25-FEB-08:61 | -0.3 |
March | 0.226635E+09 | 27808.55 | 06-MAR-08:61 | 1.75 |
April | 67889133.49 | 26431.99 | 08-APR-07:01 | 2.57 |
May | 46443788.08 | 1544.61 | 06-MAY-07:03 | 6.97 |
June | 41259910.73 | 2520.21 | 25-JUN-16:02 | 35.22 |
July | 55519798.88 | 2597.06 | 04-JUL-16:02 | 35.68 |
August | 39473912.95 | 2437.02 | 20-AUG-16:02 | 34.90 |
September | 25580683.36 | 1688.29 | 02-SEP-17:02 | 30.92 |
October | 56117348.14 | 27260.99 | 26-OCT-07:01 | -2.1 |
November | 0.120537E+09 | 27811.03 | 27-NOV-08:61 | -3.0 |
December | 0.732091E+09 | 27821.04 | 15-DEC-08:61 | -7.2 |
Annual Sum or Average | 0.282362E+10 | |||
Minimum of Months | 25580683.36 | 1544.61 | -7.2 | |
Maximum of Months | 0.867650E+09 | 27821.04 | 35.68 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177185E+10 | 30335.45 | 18-JAN-08:61 | -3.2 |
February | 0.126058E+10 | 30334.49 | 09-FEB-08:61 | -1.2 |
March | 0.613024E+09 | 30320.39 | 06-MAR-08:61 | 1.75 |
April | 0.147781E+09 | 30025.02 | 08-APR-07:01 | 2.57 |
May | 69053356.40 | 16058.13 | 06-MAY-07:03 | 6.97 |
June | 44129456.96 | 2517.78 | 25-JUN-16:02 | 35.22 |
July | 54972052.16 | 2583.78 | 04-JUL-16:02 | 35.68 |
August | 36937302.52 | 2420.08 | 20-AUG-16:02 | 34.90 |
September | 26003021.78 | 1684.90 | 02-SEP-17:02 | 30.92 |
October | 0.115219E+09 | 29824.16 | 26-OCT-07:01 | -2.1 |
November | 0.291672E+09 | 30328.55 | 27-NOV-08:61 | -3.0 |
December | 0.153855E+10 | 30344.39 | 15-DEC-08:61 | -7.2 |
Annual Sum or Average | 0.596977E+10 | |||
Minimum of Months | 26003021.78 | 1684.90 | -7.2 | |
Maximum of Months | 0.177185E+10 | 30344.39 | 35.68 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.813398E+10 | 5087.95 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.735242E+10 | 5087.95 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.814191E+10 | 5087.95 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.788011E+10 | 5087.95 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.813398E+10 | 5087.95 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.788127E+10 | 5087.95 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.814063E+10 | 5087.95 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.813456E+10 | 5087.95 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.788734E+10 | 5087.95 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.813398E+10 | 5087.95 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.785744E+10 | 5087.95 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.814844E+10 | 5087.95 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.958261E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.735242E+10 | 5087.95 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.814844E+10 | 5087.95 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488783E+10 | 3061.69 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.441818E+10 | 3061.69 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.489263E+10 | 3061.69 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.473526E+10 | 3061.69 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.488783E+10 | 3061.69 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.473600E+10 | 3061.69 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.489181E+10 | 3061.69 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.488820E+10 | 3061.69 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.473961E+10 | 3061.69 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.488783E+10 | 3061.69 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.472164E+10 | 3061.69 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.489653E+10 | 3061.69 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.575834E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.441818E+10 | 3061.69 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.489653E+10 | 3061.69 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365008E+10 | 3191.64 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.330698E+10 | 3191.64 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.373984E+10 | 3191.64 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.354319E+10 | 3191.64 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.369496E+10 | 3191.64 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.361051E+10 | 3191.64 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.362764E+10 | 3191.64 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.373984E+10 | 3191.64 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.354319E+10 | 3191.64 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.365008E+10 | 3191.64 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.354319E+10 | 3191.64 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.362764E+10 | 3191.64 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.432771E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.330698E+10 | 3191.64 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.373984E+10 | 3191.64 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294350E+10 |
February | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242332E+10 |
March | 0.335708E+10 | 0.814191E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193402E+10 |
April | 0.327081E+10 | 0.788011E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25451921.97 | 0.119379E+10 |
May | 0.336680E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213529E+09 | 0.716294E+09 |
June | 0.325380E+10 | 0.788127E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996211E+09 | 0.255504E+09 |
July | 0.339353E+10 | 0.814063E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130639E+10 | 78644318.13 |
August | 0.334857E+10 | 0.813456E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946181E+09 | 0.120984E+09 |
September | 0.327932E+10 | 0.788734E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431750E+09 | 0.252710E+09 |
October | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82309550.30 | 0.127943E+10 |
November | 0.327446E+10 | 0.785744E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245044E+10 |
December | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328204E+10 |
Annual Sum or Average | 0.397770E+11 | 0.958261E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400182E+10 | 0.169307E+11 |
Minimum of Months | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78644318.13 |
Maximum of Months | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130639E+10 | 0.328204E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158431E+10 |
February | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128906E+10 |
March | 0.167849E+10 | 0.489263E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102986E+10 |
April | 0.163536E+10 | 0.473526E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13929085.37 | 0.623067E+09 |
May | 0.168335E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117066E+09 | 0.353975E+09 |
June | 0.162685E+10 | 0.473600E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546742E+09 | 0.113274E+09 |
July | 0.169671E+10 | 0.489181E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717371E+09 | 28592327.95 |
August | 0.167424E+10 | 0.488820E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520956E+09 | 45106051.21 |
September | 0.163961E+10 | 0.473961E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238425E+09 | 0.109272E+09 |
October | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45302471.61 | 0.663940E+09 |
November | 0.163718E+10 | 0.472164E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133692E+10 |
December | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176641E+10 |
Annual Sum or Average | 0.198880E+11 | 0.575834E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219979E+10 | 0.894379E+10 |
Minimum of Months | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28592327.95 |
Maximum of Months | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717371E+09 | 0.176641E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158425E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129466E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103771E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13878938.36 | 0.640754E+09 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112085E+09 | 0.365716E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539869E+09 | 0.121231E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705329E+09 | 35264887.97 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512419E+09 | 53256473.83 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232702E+09 | 0.123062E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44109951.23 | 0.677208E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133283E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177195E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216039E+10 | 0.903788E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35264887.97 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705329E+09 | 0.177195E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157243E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128636E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102770E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13879063.02 | 0.636942E+09 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112090E+09 | 0.364695E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539791E+09 | 0.121337E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705190E+09 | 35579730.42 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512340E+09 | 53561401.76 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232698E+09 | 0.123244E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44109794.63 | 0.675366E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131876E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176573E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216010E+10 | 0.898170E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35579730.42 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705190E+09 | 0.176573E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155874E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127635E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101199E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13879373.29 | 0.629289E+09 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112180E+09 | 0.361569E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540004E+09 | 0.120489E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705471E+09 | 34823245.74 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512481E+09 | 52736240.99 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232746E+09 | 0.122450E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44118978.60 | 0.671482E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129925E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175959E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216088E+10 | 0.889875E+10 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34823245.74 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705471E+09 | 0.175959E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280062E+10 |
February | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229593E+10 |
March | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180592E+10 |
April | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24945820.96 | 0.112644E+10 |
May | 0.349753E+10 | 0.369496E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202152E+09 | 0.658940E+09 |
June | 0.343071E+10 | 0.361051E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972291E+09 | 0.225260E+09 |
July | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126939E+10 | 66989215.01 |
August | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921653E+09 | 0.101607E+09 |
September | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418172E+09 | 0.230234E+09 |
October | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79298843.98 | 0.121331E+10 |
November | 0.331698E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230208E+10 |
December | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317433E+10 |
Annual Sum or Average | 0.410346E+11 | 0.432771E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388790E+10 | 0.160017E+11 |
Minimum of Months | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66989215.01 |
Maximum of Months | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126939E+10 | 0.317433E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154300E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126226E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985015E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13880899.56 | 0.614016E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112600E+09 | 0.357883E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541402E+09 | 0.120686E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706953E+09 | 34336135.31 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513439E+09 | 52500889.43 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233016E+09 | 0.122736E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44159595.17 | 0.666148E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126439E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175485E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216545E+10 | 0.877781E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34336135.31 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706953E+09 | 0.175485E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153895E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125851E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977907E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13881056.72 | 0.609646E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112645E+09 | 0.356148E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541470E+09 | 0.120419E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707045E+09 | 34142073.20 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513491E+09 | 52290121.99 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233039E+09 | 0.122493E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44162903.21 | 0.664314E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125670E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175321E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216573E+10 | 0.874472E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34142073.20 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707045E+09 | 0.175321E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152889E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124886E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960150E+09 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13881486.65 | 0.598866E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112766E+09 | 0.351180E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541587E+09 | 0.119529E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707145E+09 | 33670963.65 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513535E+09 | 51794985.51 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233076E+09 | 0.121849E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44168100.41 | 0.659438E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124081E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174895E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216616E+10 | 0.866399E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33670963.65 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707145E+09 | 0.174895E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170984E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141568E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111406E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14299825.78 | 0.703552E+09 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115911E+09 | 0.436210E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556133E+09 | 0.170734E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724873E+09 | 63401391.79 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523503E+09 | 95032152.13 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236457E+09 | 0.183678E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45061828.48 | 0.763605E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138080E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191929E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221624E+10 | 0.995588E+10 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63401391.79 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724873E+09 | 0.191929E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5087.95 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6366.17 | 16-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5087.95 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5467.88 | 03-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5087.95 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4390.32 | 21-MAR-11:05 |
April | 4050.04 | 01-APR-12:09 | 5087.95 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 532.16 | 13-APR-17:00 | 3925.69 | 23-APR-17:00 |
May | 4050.04 | 05-MAY-12:09 | 5087.95 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.53 | 19-MAY-15:00 | 3331.46 | 01-MAY-14:00 |
June | 4050.04 | 02-JUN-12:09 | 5087.95 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3461.48 | 28-JUN-16:00 | 2267.32 | 08-JUN-17:00 |
July | 4050.04 | 01-JUL-12:09 | 5087.95 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3352.80 | 22-JUL-15:00 | 1241.32 | 01-JUL-13:00 |
August | 4050.04 | 04-AUG-12:09 | 5087.95 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2605.78 | 01-AUG-16:00 | 1059.26 | 23-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 5087.95 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2095.35 | 03-SEP-14:00 | 1924.16 | 08-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 5087.95 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.99 | 01-OCT-16:00 | 4977.34 | 24-OCT-15:00 |
November | 4050.04 | 03-NOV-12:09 | 5087.95 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4909.81 | 26-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5087.95 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 5989.84 | 21-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.26 | |||||
Maximum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3461.48 | 6366.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3061.69 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3447.56 | 16-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3061.69 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3007.30 | 03-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3061.69 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2496.01 | 21-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 3061.69 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.33 | 13-APR-17:00 | 2235.95 | 23-APR-17:00 |
May | 2024.96 | 05-MAY-12:09 | 3061.69 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 815.41 | 22-MAY-13:00 | 1867.94 | 01-MAY-14:00 |
June | 2024.96 | 02-JUN-12:09 | 3061.69 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.99 | 28-JUN-16:00 | 1242.91 | 08-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 3061.69 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.10 | 22-JUL-15:00 | 685.91 | 01-JUL-13:00 |
August | 2024.96 | 04-AUG-12:09 | 3061.69 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1439.88 | 01-AUG-16:00 | 587.73 | 23-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 3061.69 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.16 | 03-SEP-14:00 | 1056.92 | 08-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 3061.69 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 662.52 | 01-OCT-16:00 | 2787.49 | 24-OCT-15:00 |
November | 2024.96 | 03-NOV-12:09 | 3061.69 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2688.57 | 26-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3061.69 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3324.71 | 21-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.73 | |||||
Maximum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.99 | 3447.56 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3447.56 | 16-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3007.30 | 03-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2468.88 | 21-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.33 | 13-APR-17:00 | 2136.06 | 23-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 815.41 | 22-MAY-13:00 | 1866.56 | 01-MAY-14:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.99 | 28-JUN-16:00 | 1242.92 | 08-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.11 | 22-JUL-15:00 | 685.91 | 01-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1439.91 | 01-AUG-16:00 | 587.73 | 23-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.18 | 03-SEP-14:00 | 1056.92 | 08-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 662.52 | 01-OCT-16:00 | 2767.06 | 24-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2688.57 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3324.71 | 21-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.73 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.99 | 3447.56 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3447.56 | 16-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3007.28 | 03-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2438.09 | 21-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.33 | 13-APR-17:00 | 2123.70 | 23-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 815.41 | 22-MAY-13:00 | 1865.79 | 01-MAY-14:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.99 | 28-JUN-16:00 | 1242.92 | 08-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.11 | 22-JUL-15:00 | 685.91 | 01-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1439.92 | 01-AUG-16:00 | 587.73 | 23-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.18 | 03-SEP-14:00 | 1056.92 | 08-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 662.52 | 01-OCT-16:00 | 2757.64 | 24-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2688.57 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3324.71 | 21-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.73 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.99 | 3447.56 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3447.56 | 16-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3007.30 | 03-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2401.56 | 21-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.33 | 13-APR-17:00 | 2098.46 | 23-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 815.41 | 22-MAY-13:00 | 1856.55 | 01-MAY-14:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1917.00 | 28-JUN-16:00 | 1242.92 | 08-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.12 | 22-JUL-15:00 | 685.91 | 01-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1439.92 | 01-AUG-16:00 | 587.73 | 23-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.18 | 03-SEP-14:00 | 1056.92 | 08-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 662.52 | 01-OCT-16:00 | 2738.34 | 24-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2688.57 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3324.71 | 21-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.73 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1917.00 | 3447.56 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3191.64 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6203.82 | 16-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3191.64 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5401.23 | 03-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3191.64 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4310.66 | 21-MAR-11:05 |
April | 5400.05 | 01-APR-14:09 | 3191.64 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 526.69 | 13-APR-17:00 | 3709.87 | 23-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 3191.64 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.90 | 22-MAY-13:00 | 3252.45 | 01-MAY-14:00 |
June | 5400.05 | 03-JUN-14:09 | 3191.64 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3440.10 | 28-JUN-16:00 | 2233.21 | 08-JUN-17:00 |
July | 5400.05 | 01-JUL-14:09 | 3191.64 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3318.41 | 22-JUL-15:00 | 1231.22 | 01-JUL-13:00 |
August | 5400.05 | 05-AUG-14:09 | 3191.64 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2584.60 | 01-AUG-16:00 | 1054.45 | 23-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 3191.64 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2080.38 | 03-SEP-14:00 | 1898.53 | 08-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 3191.64 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1189.24 | 01-OCT-16:00 | 4858.98 | 24-OCT-15:00 |
November | 5400.05 | 04-NOV-14:09 | 3191.64 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4831.38 | 26-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3191.64 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 5964.63 | 21-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1054.45 | |||||
Maximum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3440.10 | 6203.82 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3447.56 | 16-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3007.30 | 03-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2398.04 | 21-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.33 | 13-APR-17:00 | 2063.86 | 23-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 815.41 | 22-MAY-13:00 | 1806.59 | 01-MAY-14:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.99 | 28-JUN-16:00 | 1242.91 | 08-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.12 | 22-JUL-15:00 | 685.91 | 01-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1439.87 | 01-AUG-16:00 | 587.73 | 23-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.11 | 03-SEP-14:00 | 1056.90 | 08-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 662.52 | 01-OCT-16:00 | 2706.59 | 24-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2688.57 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3324.71 | 21-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.73 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.99 | 3447.56 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3447.56 | 16-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3007.30 | 03-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2398.03 | 21-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.33 | 13-APR-17:00 | 2063.86 | 23-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 815.41 | 22-MAY-13:00 | 1799.05 | 01-MAY-14:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.99 | 28-JUN-16:00 | 1242.91 | 08-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.12 | 22-JUL-15:00 | 685.91 | 01-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1439.87 | 01-AUG-16:00 | 587.73 | 23-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.11 | 03-SEP-14:00 | 1056.90 | 08-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 662.52 | 01-OCT-16:00 | 2697.16 | 24-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2688.57 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3324.71 | 21-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.73 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.99 | 3447.56 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3447.56 | 16-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3007.30 | 03-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2398.02 | 21-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.33 | 13-APR-17:00 | 2063.86 | 23-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 815.41 | 22-MAY-13:00 | 1780.18 | 01-MAY-14:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1917.00 | 28-JUN-16:00 | 1242.91 | 08-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.12 | 22-JUL-15:00 | 685.91 | 01-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1439.88 | 01-AUG-16:00 | 587.73 | 23-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.13 | 03-SEP-14:00 | 1056.90 | 08-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 662.52 | 01-OCT-16:00 | 2672.50 | 24-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2688.57 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3324.71 | 21-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.73 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1917.00 | 3447.56 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3609.91 | 16-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3073.95 | 03-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2477.56 | 21-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 298.80 | 13-APR-17:00 | 2131.97 | 23-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 840.00 | 19-MAY-15:00 | 1792.29 | 01-MAY-14:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.39 | 28-JUN-16:00 | 1253.79 | 08-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1882.55 | 22-JUL-15:00 | 696.01 | 01-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.10 | 01-AUG-16:00 | 592.54 | 23-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.18 | 03-SEP-14:00 | 1082.50 | 08-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 672.28 | 01-OCT-16:00 | 2767.64 | 24-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2767.00 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3349.92 | 21-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.54 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.39 | 3609.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9855.40 | 20-JAN-00:02 | 1687.52 | 1338.85 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8630.73 | 04-FEB-00:03 | 1350.01 | 10711.44 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.93 |
March | 6970.76 | 11-MAR-00:05 | 675.01 | 5355.72 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9800.54 | 13-APR-16:30 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 473.85 | 0.00 |
May | 11718.73 | 19-MAY-16:50 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1473.96 | 0.00 |
June | 34014.61 | 28-JUN-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 | 0.00 |
July | 34670.28 | 20-JUL-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.75 |
August | 36222.50 | 19-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.73 |
September | 34316.34 | 03-SEP-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.96 |
October | 24502.43 | 02-OCT-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.09 |
November | 7650.58 | 02-NOV-17:10 | 3375.03 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.58 |
December | 9040.28 | 15-DEC-00:03 | 1350.01 | 1071.08 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6970.76 | 0.00 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36222.50 | 3375.03 | 10711.44 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1473.96 | 283.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3603.72 | 25-JAN-21:00 | 1012.48 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3977.83 | 14-FEB-15:00 | 1349.97 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.29 |
March | 15250.64 | 12-MAR-17:35 | 12149.77 | 18370.11 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.82 |
April | 15996.68 | 30-APR-20:25 | 6074.88 | 18370.11 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 |
May | 15960.79 | 12-MAY-21:55 | 6074.88 | 18370.11 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 |
June | 19226.92 | 26-JUN-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.68 |
July | 18625.48 | 20-JUL-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.57 |
August | 19722.16 | 19-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.66 |
September | 19175.71 | 03-SEP-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.59 |
October | 16748.84 | 11-OCT-20:35 | 2024.96 | 6123.37 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 |
November | 11513.51 | 02-NOV-22:51 | 1181.23 | 11279.89 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 |
December | 4289.96 | 22-DEC-09:32 | 674.99 | 6445.65 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3603.72 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19722.16 | 12149.77 | 18370.11 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4341.03 | 04-JAN-08:61 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.49 |
February | 3904.66 | 11-FEB-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.08 |
March | 3586.40 | 25-MAR-07:01 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.71 |
April | 5211.04 | 29-APR-13:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.97 |
May | 6869.99 | 22-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 |
June | 21464.87 | 26-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 |
July | 21592.61 | 22-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 |
August | 22185.50 | 19-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 |
September | 20657.25 | 03-SEP-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.22 |
October | 20808.76 | 02-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
November | 4268.44 | 27-NOV-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.08 |
December | 3777.53 | 30-DEC-08:61 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3586.40 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 | |
Maximum of Months | 22185.50 | 2024.96 | 2789.01 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4283.65 | 04-JAN-08:61 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.20 |
February | 3872.51 | 11-FEB-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.51 |
March | 3550.58 | 25-MAR-07:01 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.68 |
April | 5199.91 | 29-APR-13:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.97 |
May | 7126.82 | 22-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 |
June | 22177.25 | 26-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
July | 21529.51 | 22-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 |
August | 22118.12 | 19-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 |
September | 20733.54 | 01-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
October | 21627.80 | 02-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
November | 3928.64 | 02-NOV-17:10 | 1687.47 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.60 |
December | 3428.04 | 02-DEC-08:61 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3428.04 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | |
Maximum of Months | 22177.25 | 2024.96 | 2789.01 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3835.37 | 20-JAN-11:13 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.86 |
February | 3551.04 | 06-FEB-10:03 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.85 |
March | 3487.58 | 25-MAR-07:01 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.39 |
April | 5015.24 | 29-APR-13:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.97 |
May | 6128.54 | 22-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 |
June | 21200.48 | 26-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 |
July | 21392.47 | 22-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 |
August | 21459.16 | 19-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
September | 20493.20 | 03-SEP-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.52 |
October | 20459.11 | 02-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
November | 3714.51 | 04-NOV-07:03 | 674.99 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.07 |
December | 3357.08 | 02-DEC-08:61 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3357.08 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | |
Maximum of Months | 21459.16 | 2024.96 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5982.61 | 13-JAN-17:43 | 14377.64 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4597.45 |
February | 7123.81 | 16-FEB-09:03 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.70 |
March | 5659.98 | 17-MAR-19:30 | 742.51 | 1679.80 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.87 |
April | 8812.84 | 28-APR-14:30 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 194.47 | 0.00 |
May | 10370.39 | 19-MAY-15:00 | 4657.54 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.69 | 0.00 |
June | 34921.95 | 26-JUN-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 |
July | 33529.22 | 05-JUL-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 |
August | 34860.72 | 19-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.61 |
September | 33404.87 | 03-SEP-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 |
October | 30271.31 | 02-OCT-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.63 |
November | 7101.22 | 04-NOV-08:62 | 2970.03 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.76 |
December | 6467.06 | 14-DEC-12:23 | 9315.09 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5043.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5659.98 | 0.00 | 225.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34921.95 | 14377.64 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.69 | 5043.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3428.63 | 21-JAN-18:43 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.13 |
February | 3497.75 | 16-FEB-09:03 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.43 |
March | 2810.46 | 17-MAR-19:30 | 371.24 | 862.24 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 |
April | 4511.82 | 28-APR-14:30 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 108.27 | 0.00 |
May | 5371.98 | 19-MAY-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 813.17 | 0.00 |
June | 17937.32 | 26-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 |
July | 17244.49 | 05-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 |
August | 17914.10 | 07-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.56 |
September | 17146.47 | 03-SEP-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 |
October | 14694.39 | 02-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.88 |
November | 3490.25 | 04-NOV-08:62 | 1484.97 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.37 |
December | 4074.99 | 22-DEC-10:13 | 1484.97 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2810.46 | 0.00 | 112.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17937.32 | 2328.71 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 813.17 | 476.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2649.34 | 31-JAN-14:43 | 5062.40 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2339.37 |
February | 3100.69 | 07-FEB-20:53 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.46 |
March | 2715.78 | 17-MAR-19:20 | 371.24 | 862.24 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 |
April | 4435.31 | 28-APR-14:30 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 108.27 | 0.00 |
May | 5316.19 | 19-MAY-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 813.17 | 0.00 |
June | 17821.62 | 26-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.87 |
July | 17128.77 | 05-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
August | 17797.20 | 07-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 |
September | 17026.30 | 03-SEP-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.35 |
October | 14268.55 | 02-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.79 |
November | 3470.12 | 04-NOV-08:62 | 1484.97 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.88 |
December | 4113.77 | 21-DEC-10:13 | 1484.97 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2649.34 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17821.62 | 5062.40 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 813.17 | 2339.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3310.10 | 13-JAN-20:53 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3354.85 | 02-FEB-20:23 | 1113.73 | 2586.72 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 |
March | 2578.87 | 17-MAR-19:00 | 877.48 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.83 |
April | 4277.12 | 28-APR-14:30 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 108.27 | 0.00 |
May | 5209.70 | 19-MAY-15:00 | 2328.71 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 813.17 | 0.00 |
June | 17711.74 | 26-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 |
July | 17025.22 | 05-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.16 |
August | 17710.61 | 07-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.87 |
September | 16927.31 | 03-SEP-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 |
October | 13123.53 | 02-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.53 |
November | 3397.58 | 04-NOV-08:62 | 1484.97 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.39 |
December | 3901.52 | 14-DEC-20:42 | 1484.97 | 3448.95 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2578.87 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17711.74 | 2328.71 | 3448.95 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 813.17 | 391.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3340.39 | 13-JAN-18:53 | 3442.43 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.09 |
February | 3147.67 | 16-FEB-11:53 | 4353.67 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.48 |
March | 2250.31 | 03-MAR-18:45 | 2294.96 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.14 |
April | 4434.87 | 28-APR-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 69.22 | 0.00 |
May | 5470.76 | 19-MAY-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 684.48 | 0.00 |
June | 17678.84 | 29-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 63.90 | 0.00 |
July | 18089.83 | 05-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
August | 19096.60 | 07-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 |
September | 18455.10 | 03-SEP-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
October | 9777.17 | 02-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.54 |
November | 2699.19 | 04-NOV-13:03 | 7796.10 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2384.38 |
December | 2996.69 | 28-DEC-10:33 | 1113.73 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2250.31 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19096.60 | 7796.10 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 684.48 | 2384.38 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.644258E+11 | 49935.48 | 17-JAN-17:00 | 0.380718E+11 | 114997.34 | 17-JAN-08:09 |
February | 0.578133E+11 | 49849.85 | 14-FEB-15:50 | 0.260975E+11 | 125973.60 | 06-FEB-08:09 |
March | 0.637640E+11 | 50455.22 | 08-MAR-13:00 | 0.717291E+10 | 78013.61 | 04-MAR-08:09 |
April | 0.642623E+11 | 59418.43 | 28-APR-18:49 | 0.790352E+09 | 35705.68 | 08-APR-08:09 |
May | 0.719435E+11 | 65858.58 | 19-MAY-16:30 | 56678519.55 | 10055.29 | 06-MAY-08:20 |
June | 0.833138E+11 | 90284.33 | 28-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.928264E+11 | 88026.45 | 22-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.910524E+11 | 79238.91 | 20-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.792481E+11 | 74180.58 | 03-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.699506E+11 | 66878.98 | 01-OCT-14:20 | 0.217463E+10 | 52415.57 | 26-OCT-07:10 |
November | 0.614806E+11 | 48704.25 | 27-NOV-17:00 | 0.610386E+10 | 61239.36 | 27-NOV-09:09 |
December | 0.644499E+11 | 49900.27 | 21-DEC-17:30 | 0.422301E+11 | 104101.15 | 22-DEC-08:09 |
Annual Sum or Average | 0.864531E+12 | 0.122698E+12 | ||||
Minimum of Months | 0.578133E+11 | 48704.25 | 0.00 | 0.00 | ||
Maximum of Months | 0.928264E+11 | 90284.33 | 0.422301E+11 | 125973.60 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.345281E+11 | 0.637027E+10 | 0.108325E+11 | 0.00 | 0.103189E+11 | 0.00 | 0.00 | 1059765.13 | 0.00 | 0.00 | 0.00 | 0.237499E+10 | 0.00 |
February | 0.312534E+11 | 0.530964E+10 | 0.980803E+10 | 0.00 | 0.918176E+10 | 0.00 | 0.00 | 0.101927E+09 | 0.00 | 0.00 | 0.00 | 0.215854E+10 | 0.00 |
March | 0.350527E+11 | 0.523692E+10 | 0.110075E+11 | 0.00 | 0.987894E+10 | 0.00 | 0.00 | 0.216676E+09 | 0.00 | 0.00 | 0.00 | 0.237124E+10 | 0.00 |
April | 0.334898E+11 | 0.441087E+10 | 0.105079E+11 | 0.00 | 0.936180E+10 | 0.00 | 0.00 | 0.433042E+10 | 0.00 | 0.00 | 0.00 | 0.216147E+10 | 0.00 |
May | 0.347840E+11 | 0.400499E+10 | 0.109147E+11 | 0.00 | 0.969567E+10 | 0.00 | 0.00 | 0.104120E+11 | 0.00 | 0.00 | 0.00 | 0.213211E+10 | 0.00 |
June | 0.338757E+11 | 0.362526E+10 | 0.106386E+11 | 0.00 | 0.960225E+10 | 0.00 | 0.00 | 0.235921E+11 | 0.00 | 0.00 | 0.00 | 0.197996E+10 | 0.00 |
July | 0.344108E+11 | 0.384584E+10 | 0.107945E+11 | 0.00 | 0.980518E+10 | 0.00 | 0.00 | 0.320305E+11 | 0.00 | 0.00 | 0.00 | 0.193962E+10 | 0.00 |
August | 0.350409E+11 | 0.430513E+10 | 0.110006E+11 | 0.00 | 0.984566E+10 | 0.00 | 0.00 | 0.288905E+11 | 0.00 | 0.00 | 0.00 | 0.196955E+10 | 0.00 |
September | 0.335014E+11 | 0.479086E+10 | 0.105148E+11 | 0.00 | 0.932704E+10 | 0.00 | 0.00 | 0.191923E+11 | 0.00 | 0.00 | 0.00 | 0.192182E+10 | 0.00 |
October | 0.345281E+11 | 0.561691E+10 | 0.108325E+11 | 0.00 | 0.968748E+10 | 0.00 | 0.00 | 0.721656E+10 | 0.00 | 0.00 | 0.00 | 0.206915E+10 | 0.00 |
November | 0.334535E+11 | 0.601012E+10 | 0.104978E+11 | 0.00 | 0.938682E+10 | 0.00 | 0.00 | 4254129.01 | 0.00 | 0.00 | 0.00 | 0.212801E+10 | 0.00 |
December | 0.344233E+11 | 0.652888E+10 | 0.108050E+11 | 0.00 | 0.103788E+11 | 0.00 | 0.00 | 427142.65 | 0.00 | 0.00 | 0.00 | 0.231355E+10 | 0.00 |
Annual Sum or Average | 0.408342E+12 | 0.600557E+11 | 0.128154E+12 | 0.00 | 0.116470E+12 | 0.00 | 0.00 | 0.125989E+12 | 0.00 | 0.00 | 0.00 | 0.255200E+11 | 0.00 |
Minimum of Months | 0.312534E+11 | 0.362526E+10 | 0.980803E+10 | 0.00 | 0.918176E+10 | 0.00 | 0.00 | 427142.65 | 0.00 | 0.00 | 0.00 | 0.192182E+10 | 0.00 |
Maximum of Months | 0.350527E+11 | 0.652888E+10 | 0.110075E+11 | 0.00 | 0.103788E+11 | 0.00 | 0.00 | 0.320305E+11 | 0.00 | 0.00 | 0.00 | 0.237499E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.380718E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.260975E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.717291E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.790352E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 56678519.55 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.217463E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.610386E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.422301E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.122698E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.422301E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26261.30 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9126.07 | 17-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26261.30 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9370.80 | 06-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26261.30 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8297.16 | 04-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26261.30 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7345.53 | 08-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26261.30 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 6774.95 | 06-MAY-08:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26261.30 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 10288.21 | 28-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26261.30 | 01-JUL-09:09 | 5507.06 | 01-JUL-19:19 | 8059.50 | 01-JUL-09:09 | 0.00 | 9530.43 | 22-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26261.30 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8003.90 | 20-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26261.30 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 7487.55 | 03-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26261.30 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 7727.86 | 26-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26261.30 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7918.33 | 27-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26261.30 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8881.70 | 22-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 6774.95 | 0.00 | 0.00 | |||||
Maximum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 10288.21 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 323.39 | 01-JAN-18:19 | 0.00 | 0.00 | 0.00 | 2235.73 | 27-JAN-13:00 | 0.00 |
February | 7225.30 | 14-FEB-15:00 | 0.00 | 0.00 | 0.00 | 2235.74 | 17-FEB-13:50 | 0.00 |
March | 7586.46 | 08-MAR-13:00 | 0.00 | 0.00 | 0.00 | 2234.78 | 01-MAR-13:20 | 0.00 |
April | 16763.61 | 13-APR-16:30 | 0.00 | 0.00 | 0.00 | 2231.33 | 07-APR-13:30 | 0.00 |
May | 23601.05 | 19-MAY-16:10 | 0.00 | 0.00 | 0.00 | 2149.99 | 03-MAY-13:20 | 0.00 |
June | 44198.24 | 28-JUN-16:10 | 0.00 | 0.00 | 0.00 | 2014.45 | 01-JUN-12:50 | 0.00 |
July | 42908.46 | 22-JUL-14:00 | 0.00 | 0.00 | 0.00 | 1906.29 | 03-JUL-12:39 | 0.00 |
August | 35967.97 | 20-AUG-14:00 | 0.00 | 0.00 | 0.00 | 1903.69 | 21-AUG-12:00 | 0.00 |
September | 31789.42 | 03-SEP-13:00 | 0.00 | 0.00 | 0.00 | 2008.66 | 23-SEP-12:39 | 0.00 |
October | 24735.18 | 01-OCT-14:20 | 0.00 | 0.00 | 0.00 | 2016.47 | 27-OCT-12:20 | 0.00 |
November | 457.20 | 19-NOV-18:10 | 0.00 | 0.00 | 0.00 | 2124.59 | 17-NOV-13:09 | 0.00 |
December | 246.09 | 24-DEC-18:49 | 0.00 | 0.00 | 0.00 | 2234.14 | 22-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 246.09 | 0.00 | 0.00 | 0.00 | 1903.69 | 0.00 | ||
Maximum of Months | 44198.24 | 0.00 | 0.00 | 0.00 | 2235.74 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 49935.48 | 17-JAN-17:00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 8519.07 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49849.85 | 14-FEB-15:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6550.86 | 0.00 | 0.00 | 7069.48 | 0.00 |
March | 50455.22 | 08-MAR-13:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6550.86 | 0.00 | 0.00 | 7586.46 | 0.00 |
April | 59418.43 | 28-APR-18:49 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 6550.86 | 0.00 | 0.00 | 11667.05 | 0.00 |
May | 65858.58 | 19-MAY-16:30 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6550.86 | 0.00 | 0.00 | 23572.61 | 0.00 |
June | 90284.33 | 28-JUN-16:10 | 26261.30 | 8059.50 | 0.00 | 0.00 | 10288.21 | 0.00 | 0.00 | 44198.24 | 0.00 |
July | 88026.45 | 22-JUL-14:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 9530.43 | 0.00 | 0.00 | 42908.46 | 0.00 |
August | 79238.91 | 20-AUG-14:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8003.90 | 0.00 | 0.00 | 35967.97 | 0.00 |
September | 74180.58 | 03-SEP-13:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7018.76 | 0.00 | 0.00 | 31789.42 | 0.00 |
October | 66878.98 | 01-OCT-14:20 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6550.86 | 0.00 | 0.00 | 24735.18 | 0.00 |
November | 48704.25 | 27-NOV-17:00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 7362.34 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49900.27 | 21-DEC-17:30 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 8378.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 48704.25 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6550.86 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 90284.33 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 10288.21 | 0.00 | 0.00 | 44198.24 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 114997.34 | 17-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 125973.60 | 06-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 78013.61 | 04-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 35705.68 | 08-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 10055.29 | 06-MAY-08:20 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 52415.57 | 26-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 61239.36 | 27-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 104101.15 | 22-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 125973.60 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 0.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 0.67 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.31 | 97.50 | 21.25 | 97.50 | 21.21 |
February | 445.67 | 21.53 | 71.17 | 21.44 | 71.17 | 21.38 |
March | 497.00 | 22.31 | 22.00 | 22.25 | 22.00 | 22.20 |
April | 370.83 | 23.21 | 0.67 | 23.20 | 0.67 | 23.20 |
May | 181.33 | 23.49 | 60.83 | 23.59 | 0.00 | 23.59 |
June | 20.67 | 23.69 | 236.83 | 23.87 | 0.00 | 23.87 |
July | 40.50 | 23.89 | 475.67 | 23.89 | 40.50 | 23.89 |
August | 17.00 | 23.89 | 482.50 | 23.89 | 17.00 | 23.89 |
September | 11.50 | 23.89 | 378.67 | 23.89 | 5.33 | 23.89 |
October | 197.67 | 22.84 | 111.67 | 23.19 | 2.83 | 23.17 |
November | 454.50 | 22.14 | 6.33 | 22.13 | 5.83 | 22.11 |
December | 496.00 | 21.14 | 104.33 | 21.11 | 104.33 | 21.09 |
Annual Sum or Average | 3228.67 | 22.09 | 2048.17 | 22.62 | 367.17 | 22.54 |
Minimum of Months | 11.50 | 21.14 | 0.67 | 21.11 | 0.00 | 21.09 |
Maximum of Months | 497.00 | 23.89 | 482.50 | 23.89 | 104.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 22.15 | 6.17 | 22.14 | 6.17 | 22.13 |
February | 439.83 | 22.30 | 7.33 | 22.28 | 7.33 | 22.27 |
March | 476.33 | 23.13 | 0.00 | 23.13 | 0.00 | 23.13 |
April | 327.00 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
May | 167.33 | 23.61 | 68.33 | 23.69 | 0.00 | 23.69 |
June | 28.00 | 23.35 | 223.17 | 23.83 | 0.00 | 23.83 |
July | 17.67 | 23.86 | 454.83 | 23.87 | 17.33 | 23.87 |
August | 15.50 | 23.79 | 471.33 | 23.87 | 14.33 | 23.87 |
September | 16.17 | 23.32 | 349.67 | 23.85 | 1.67 | 23.85 |
October | 178.67 | 23.21 | 104.17 | 23.46 | 0.00 | 23.46 |
November | 413.67 | 23.03 | 3.83 | 23.04 | 0.00 | 23.04 |
December | 496.00 | 21.87 | 9.17 | 21.86 | 9.17 | 21.84 |
Annual Sum or Average | 3072.17 | 22.72 | 1698.00 | 23.12 | 56.00 | 23.11 |
Minimum of Months | 15.50 | 21.87 | 0.00 | 21.86 | 0.00 | 21.84 |
Maximum of Months | 496.00 | 23.86 | 471.33 | 23.87 | 17.33 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.59 | 33.67 | 21.55 | 33.67 | 21.51 |
February | 331.83 | 21.77 | 20.50 | 21.73 | 20.50 | 21.69 |
March | 365.33 | 22.71 | 3.17 | 22.69 | 3.17 | 22.68 |
April | 216.83 | 23.26 | 3.00 | 23.29 | 0.00 | 23.29 |
May | 102.33 | 23.54 | 65.17 | 23.84 | 0.00 | 23.84 |
June | 7.83 | 24.02 | 199.33 | 24.21 | 0.50 | 24.22 |
July | 21.67 | 24.61 | 356.33 | 24.14 | 21.67 | 24.17 |
August | 17.17 | 24.50 | 376.67 | 24.10 | 17.17 | 24.12 |
September | 5.17 | 24.24 | 307.17 | 24.07 | 2.83 | 24.07 |
October | 128.33 | 22.79 | 95.33 | 23.33 | 0.17 | 23.33 |
November | 321.17 | 22.48 | 2.50 | 22.48 | 1.00 | 22.48 |
December | 369.00 | 21.27 | 34.33 | 21.26 | 34.33 | 21.25 |
Annual Sum or Average | 2257.67 | 22.25 | 1497.17 | 22.92 | 135.00 | 22.90 |
Minimum of Months | 5.17 | 21.27 | 2.50 | 21.26 | 0.00 | 21.25 |
Maximum of Months | 371.00 | 24.61 | 376.67 | 24.21 | 34.33 | 24.22 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.51 | 40.67 | 21.47 | 40.67 | 21.44 |
February | 332.33 | 21.71 | 24.83 | 21.67 | 24.83 | 21.63 |
March | 372.17 | 22.64 | 5.00 | 22.62 | 5.00 | 22.60 |
April | 228.17 | 23.23 | 2.83 | 23.25 | 0.00 | 23.25 |
May | 103.50 | 23.51 | 64.67 | 23.82 | 0.00 | 23.82 |
June | 8.17 | 24.00 | 200.00 | 24.21 | 0.50 | 24.22 |
July | 21.33 | 24.63 | 356.67 | 24.14 | 21.33 | 24.17 |
August | 17.17 | 24.51 | 377.00 | 24.10 | 17.17 | 24.12 |
September | 4.83 | 24.26 | 308.00 | 24.07 | 2.33 | 24.07 |
October | 133.17 | 22.77 | 95.33 | 23.31 | 0.67 | 23.30 |
November | 328.33 | 22.37 | 2.83 | 22.37 | 1.67 | 22.37 |
December | 369.00 | 21.24 | 39.83 | 21.23 | 39.83 | 21.22 |
Annual Sum or Average | 2289.17 | 22.20 | 1517.67 | 22.88 | 154.00 | 22.85 |
Minimum of Months | 4.83 | 21.24 | 2.83 | 21.23 | 0.00 | 21.22 |
Maximum of Months | 372.17 | 24.63 | 377.00 | 24.21 | 40.67 | 24.22 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.42 | 53.00 | 21.38 | 53.00 | 21.35 |
February | 333.67 | 21.64 | 31.00 | 21.60 | 31.00 | 21.56 |
March | 376.83 | 22.52 | 9.33 | 22.48 | 9.33 | 22.45 |
April | 253.50 | 23.18 | 1.83 | 23.20 | 0.00 | 23.20 |
May | 112.83 | 23.46 | 58.83 | 23.76 | 0.00 | 23.76 |
June | 9.50 | 23.94 | 192.83 | 24.20 | 0.50 | 24.21 |
July | 21.50 | 24.52 | 356.00 | 24.13 | 21.50 | 24.15 |
August | 18.33 | 24.46 | 376.17 | 24.09 | 18.33 | 24.11 |
September | 6.67 | 24.13 | 304.17 | 24.06 | 3.17 | 24.07 |
October | 143.33 | 22.76 | 93.00 | 23.25 | 1.17 | 23.24 |
November | 337.50 | 22.23 | 3.17 | 22.22 | 3.17 | 22.21 |
December | 369.00 | 21.21 | 49.17 | 21.19 | 49.17 | 21.19 |
Annual Sum or Average | 2353.67 | 22.15 | 1528.50 | 22.81 | 190.33 | 22.77 |
Minimum of Months | 6.67 | 21.21 | 1.83 | 21.19 | 0.00 | 21.19 |
Maximum of Months | 376.83 | 24.52 | 376.17 | 24.20 | 53.00 | 24.21 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.31 | 76.83 | 21.28 | 76.83 | 21.25 |
February | 308.00 | 21.55 | 44.00 | 21.50 | 44.00 | 21.45 |
March | 348.00 | 22.32 | 11.17 | 22.29 | 11.17 | 22.25 |
April | 280.33 | 23.20 | 1.00 | 23.21 | 0.33 | 23.20 |
May | 136.00 | 23.47 | 40.50 | 23.63 | 2.50 | 23.64 |
June | 10.83 | 23.87 | 155.00 | 24.00 | 0.33 | 24.01 |
July | 17.67 | 24.42 | 323.00 | 24.01 | 17.67 | 24.03 |
August | 16.00 | 24.28 | 340.00 | 23.97 | 16.00 | 23.98 |
September | 4.67 | 23.89 | 265.50 | 23.97 | 3.17 | 23.97 |
October | 150.33 | 22.78 | 80.00 | 23.18 | 0.83 | 23.17 |
November | 316.83 | 21.96 | 2.33 | 21.95 | 2.33 | 21.94 |
December | 338.00 | 21.16 | 77.67 | 21.15 | 77.67 | 21.14 |
Annual Sum or Average | 2266.67 | 22.09 | 1417.00 | 22.65 | 252.83 | 22.58 |
Minimum of Months | 4.67 | 21.16 | 1.00 | 21.15 | 0.33 | 21.14 |
Maximum of Months | 348.00 | 24.42 | 340.00 | 24.01 | 77.67 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.30 | 81.83 | 21.26 | 81.83 | 21.24 |
February | 308.00 | 21.54 | 47.50 | 21.48 | 47.50 | 21.44 |
March | 348.00 | 22.29 | 15.50 | 22.24 | 15.50 | 22.19 |
April | 289.33 | 23.20 | 1.33 | 23.19 | 0.83 | 23.19 |
May | 155.67 | 23.50 | 31.00 | 23.63 | 2.33 | 23.63 |
June | 15.83 | 23.82 | 135.00 | 24.00 | 0.17 | 24.01 |
July | 17.50 | 24.34 | 318.83 | 24.00 | 17.50 | 24.02 |
August | 16.00 | 24.24 | 334.17 | 23.97 | 16.00 | 23.98 |
September | 6.17 | 23.89 | 246.33 | 23.97 | 3.17 | 23.97 |
October | 157.83 | 22.83 | 74.00 | 23.18 | 1.00 | 23.17 |
November | 317.50 | 21.93 | 3.50 | 21.92 | 3.50 | 21.91 |
December | 338.00 | 21.16 | 86.67 | 21.15 | 86.67 | 21.14 |
Annual Sum or Average | 2309.83 | 22.10 | 1375.67 | 22.62 | 276.00 | 22.55 |
Minimum of Months | 6.17 | 21.16 | 1.33 | 21.15 | 0.17 | 21.14 |
Maximum of Months | 348.00 | 24.34 | 334.17 | 24.00 | 86.67 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.28 | 89.50 | 21.25 | 89.50 | 21.22 |
February | 308.00 | 21.51 | 51.50 | 21.45 | 51.50 | 21.41 |
March | 348.00 | 22.23 | 18.50 | 22.17 | 18.50 | 22.12 |
April | 292.67 | 23.16 | 2.17 | 23.15 | 1.83 | 23.14 |
May | 162.50 | 23.49 | 30.00 | 23.61 | 2.33 | 23.61 |
June | 17.33 | 23.81 | 131.50 | 24.00 | 0.17 | 24.00 |
July | 17.67 | 24.33 | 318.00 | 24.00 | 17.67 | 24.02 |
August | 16.00 | 24.19 | 333.67 | 23.96 | 16.00 | 23.97 |
September | 6.83 | 23.89 | 243.33 | 23.97 | 3.33 | 23.97 |
October | 163.17 | 22.83 | 73.33 | 23.16 | 1.33 | 23.15 |
November | 317.83 | 21.86 | 4.67 | 21.85 | 4.67 | 21.84 |
December | 338.00 | 21.15 | 98.17 | 21.14 | 98.17 | 21.14 |
Annual Sum or Average | 2328.00 | 22.08 | 1394.33 | 22.59 | 305.00 | 22.51 |
Minimum of Months | 6.83 | 21.15 | 2.17 | 21.14 | 0.17 | 21.14 |
Maximum of Months | 348.00 | 24.33 | 333.67 | 24.00 | 98.17 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.23 | 114.17 | 21.20 | 114.17 | 21.18 |
February | 308.00 | 21.45 | 66.17 | 21.39 | 66.17 | 21.35 |
March | 348.00 | 22.10 | 27.67 | 22.03 | 27.67 | 21.96 |
April | 300.00 | 23.07 | 6.00 | 23.03 | 5.83 | 23.00 |
May | 173.50 | 23.43 | 27.50 | 23.55 | 2.83 | 23.55 |
June | 20.17 | 23.78 | 128.83 | 23.99 | 0.17 | 24.00 |
July | 18.33 | 24.32 | 318.17 | 24.00 | 18.33 | 24.02 |
August | 16.17 | 24.19 | 333.17 | 23.96 | 16.17 | 23.97 |
September | 8.33 | 23.87 | 241.50 | 23.97 | 3.50 | 23.97 |
October | 171.17 | 22.79 | 73.17 | 23.12 | 2.00 | 23.10 |
November | 318.67 | 21.74 | 8.50 | 21.73 | 8.50 | 21.71 |
December | 338.00 | 21.14 | 128.83 | 21.13 | 128.83 | 21.12 |
Annual Sum or Average | 2360.33 | 22.03 | 1473.67 | 22.51 | 394.17 | 22.41 |
Minimum of Months | 8.33 | 21.14 | 6.00 | 21.13 | 0.17 | 21.12 |
Maximum of Months | 348.00 | 24.32 | 333.17 | 24.00 | 128.83 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.18 | 211.00 | 21.15 | 211.00 | 21.14 |
February | 308.00 | 21.36 | 148.00 | 21.28 | 148.00 | 21.24 |
March | 348.00 | 21.92 | 73.83 | 21.78 | 73.83 | 21.68 |
April | 307.33 | 22.96 | 13.00 | 22.89 | 13.00 | 22.82 |
May | 185.17 | 23.33 | 26.83 | 23.44 | 3.83 | 23.43 |
June | 21.33 | 23.66 | 142.33 | 23.97 | 0.33 | 23.98 |
July | 19.17 | 24.49 | 324.67 | 24.01 | 19.17 | 24.04 |
August | 16.50 | 24.36 | 338.83 | 23.97 | 16.50 | 23.99 |
September | 10.50 | 23.77 | 259.17 | 23.96 | 3.50 | 23.96 |
October | 177.67 | 22.71 | 81.33 | 23.01 | 7.83 | 22.96 |
November | 321.50 | 21.61 | 32.67 | 21.56 | 32.67 | 21.52 |
December | 338.00 | 21.12 | 223.33 | 21.11 | 223.33 | 21.11 |
Annual Sum or Average | 2393.17 | 21.95 | 1875.00 | 22.36 | 753.00 | 22.20 |
Minimum of Months | 10.50 | 21.12 | 13.00 | 21.11 | 0.33 | 21.11 |
Maximum of Months | 348.00 | 24.49 | 338.83 | 24.01 | 223.33 | 24.04 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.30782 | 17.05376 | -0.4561 | 9.90494 |
February | 448.00000 | 21.54286 | 18.46129 | -0.3842 | 9.09070 |
March | 497.00000 | 22.31415 | 17.96660 | -0.1919 | 7.07188 |
April | 479.00000 | 23.36101 | 14.86172 | 0.07224 | 6.00872 |
May | 496.00000 | 23.74142 | 22.38448 | -0.6635 | 15.10373 |
June | 481.00000 | 23.87990 | 30.28403 | -0.4871 | 10.15629 |
July | 495.00000 | 23.88848 | 42.08568 | -0.3559 | 7.73827 |
August | 497.00000 | 23.88826 | 41.57306 | -0.3572 | 7.77576 |
September | 479.00000 | 23.88821 | 36.94121 | -0.4198 | 8.87847 |
October | 496.00000 | 23.46651 | 23.66213 | 0.20297 | 7.24893 |
November | 480.00000 | 22.23078 | 18.20650 | -0.1702 | 6.84321 |
December | 496.00000 | 21.14386 | 15.21724 | -0.4940 | 10.36843 |
Annual Sum or Average | 5840.00000 | 22.89369 | 24.94164 | -0.3088 | 8.85715 |
Minimum of Months | 448.00000 | 21.14386 | 14.86172 | -0.6635 | 6.00872 |
Maximum of Months | 497.00000 | 23.88848 | 42.08568 | 0.20297 | 15.10373 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.15266 | 19.28527 | -0.2371 | 7.08229 |
February | 448.00000 | 22.33148 | 19.72131 | -0.1837 | 6.83984 |
March | 497.00000 | 23.15755 | 18.02031 | 0.01159 | 5.84111 |
April | 479.00000 | 23.64818 | 14.83352 | 0.15303 | 5.85497 |
May | 496.00000 | 23.78173 | 22.53991 | -0.6300 | 13.76451 |
June | 481.00000 | 23.83314 | 30.42240 | -0.5000 | 10.43284 |
July | 495.00000 | 23.86092 | 41.22506 | -0.3805 | 8.12992 |
August | 497.00000 | 23.85211 | 41.01236 | -0.3833 | 8.20038 |
September | 479.00000 | 23.80982 | 36.70674 | -0.4483 | 9.45545 |
October | 496.00000 | 23.62575 | 23.57752 | 0.24359 | 7.02139 |
November | 480.00000 | 23.14730 | 18.60273 | 0.03586 | 5.76226 |
December | 496.00000 | 21.86882 | 17.57325 | -0.3042 | 7.62040 |
Annual Sum or Average | 5840.00000 | 23.25943 | 25.34026 | -0.2192 | 8.01152 |
Minimum of Months | 448.00000 | 21.86882 | 14.83352 | -0.6300 | 5.76226 |
Maximum of Months | 497.00000 | 23.86092 | 41.22506 | 0.24359 | 13.76451 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.58552 | 16.20025 | -0.3601 | 8.41958 |
February | 336.00000 | 21.79321 | 17.33894 | -0.2971 | 7.92891 |
March | 379.00000 | 22.75613 | 16.75105 | -0.0716 | 6.31189 |
April | 360.00000 | 23.56160 | 14.29877 | 0.13269 | 6.08959 |
May | 375.00000 | 23.90305 | 21.66372 | -0.6033 | 13.38647 |
June | 366.00000 | 24.06742 | 29.41852 | -0.4417 | 9.56133 |
July | 369.00000 | 24.10630 | 41.21520 | -0.3089 | 7.46833 |
August | 379.00000 | 24.07912 | 40.96100 | -0.3162 | 7.47763 |
September | 360.00000 | 24.04026 | 36.41065 | -0.3808 | 8.36768 |
October | 371.00000 | 23.57596 | 22.70600 | 0.23245 | 7.43283 |
November | 360.00000 | 22.63067 | 16.96114 | -0.0660 | 6.21218 |
December | 369.00000 | 21.27241 | 14.28229 | -0.4324 | 9.20113 |
Annual Sum or Average | 4395.00000 | 23.12372 | 24.08738 | -0.2432 | 8.16450 |
Minimum of Months | 336.00000 | 21.27241 | 14.28229 | -0.6033 | 6.08959 |
Maximum of Months | 379.00000 | 24.10630 | 41.21520 | 0.23245 | 13.38647 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.51065 | 16.25658 | -0.3861 | 8.73046 |
February | 336.00000 | 21.73386 | 17.40156 | -0.3183 | 8.15328 |
March | 379.00000 | 22.66851 | 16.85372 | -0.0979 | 6.44293 |
April | 360.00000 | 23.51984 | 14.34391 | 0.11877 | 6.09501 |
May | 375.00000 | 23.89241 | 21.67755 | -0.6086 | 13.57322 |
June | 366.00000 | 24.06699 | 29.42067 | -0.4410 | 9.54997 |
July | 369.00000 | 24.10659 | 41.19684 | -0.3070 | 7.44559 |
August | 379.00000 | 24.07926 | 40.94259 | -0.3146 | 7.45770 |
September | 360.00000 | 24.03995 | 36.40226 | -0.3800 | 8.35366 |
October | 371.00000 | 23.55540 | 22.73098 | 0.22558 | 7.43380 |
November | 360.00000 | 22.50599 | 17.07624 | -0.1002 | 6.39212 |
December | 369.00000 | 21.23987 | 14.30509 | -0.4482 | 9.45226 |
Annual Sum or Average | 4395.00000 | 23.08628 | 24.12046 | -0.2551 | 8.26576 |
Minimum of Months | 336.00000 | 21.23987 | 14.30509 | -0.6086 | 6.09501 |
Maximum of Months | 379.00000 | 24.10659 | 41.19684 | 0.22558 | 13.57322 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.42339 | 16.31996 | -0.4162 | 9.12974 |
February | 336.00000 | 21.65788 | 17.48061 | -0.3451 | 8.45099 |
March | 379.00000 | 22.52515 | 17.02338 | -0.1387 | 6.66916 |
April | 360.00000 | 23.43680 | 14.43299 | 0.09218 | 6.09938 |
May | 375.00000 | 23.86064 | 21.71470 | -0.6273 | 14.16853 |
June | 366.00000 | 24.06076 | 29.43816 | -0.4497 | 9.70130 |
July | 369.00000 | 24.10208 | 41.27177 | -0.3134 | 7.50845 |
August | 379.00000 | 24.07481 | 41.01514 | -0.3209 | 7.52544 |
September | 360.00000 | 24.03458 | 36.44786 | -0.3873 | 8.46532 |
October | 371.00000 | 23.51392 | 22.79246 | 0.21112 | 7.39124 |
November | 360.00000 | 22.33376 | 17.23952 | -0.1458 | 6.64540 |
December | 369.00000 | 21.20544 | 14.32966 | -0.4659 | 9.74899 |
Annual Sum or Average | 4395.00000 | 23.02900 | 24.19532 | -0.2759 | 8.46782 |
Minimum of Months | 336.00000 | 21.20544 | 14.32966 | -0.6273 | 6.09938 |
Maximum of Months | 379.00000 | 24.10208 | 41.27177 | 0.21112 | 14.16853 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.31429 | 17.88763 | -0.4648 | 9.89351 |
February | 308.00000 | 21.55055 | 18.93366 | -0.3908 | 9.00710 |
March | 348.00000 | 22.32312 | 18.59207 | -0.2016 | 7.05604 |
April | 330.00000 | 23.31685 | 15.73135 | 0.05151 | 6.01396 |
May | 344.00000 | 23.76052 | 22.92445 | -0.6740 | 15.50441 |
June | 336.00000 | 23.93855 | 30.58470 | -0.4914 | 10.32990 |
July | 338.00000 | 23.97824 | 42.33916 | -0.3490 | 7.82429 |
August | 348.00000 | 23.95103 | 42.19147 | -0.3551 | 7.86144 |
September | 330.00000 | 23.95249 | 37.67466 | -0.4135 | 8.84760 |
October | 340.00000 | 23.42175 | 23.95850 | 0.18455 | 7.25555 |
November | 330.00000 | 22.03298 | 18.93304 | -0.2228 | 7.13685 |
December | 338.00000 | 21.16040 | 15.84425 | -0.5000 | 10.37420 |
Annual Sum or Average | 4030.00000 | 22.90194 | 25.53655 | -0.3192 | 8.93575 |
Minimum of Months | 308.00000 | 21.16040 | 15.73135 | -0.6740 | 6.01396 |
Maximum of Months | 348.00000 | 23.97824 | 42.33916 | 0.18455 | 15.50441 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.30220 | 17.79308 | -0.4747 | 10.05792 |
February | 308.00000 | 21.53603 | 18.84501 | -0.4027 | 9.17132 |
March | 348.00000 | 22.28684 | 18.54727 | -0.2207 | 7.20077 |
April | 330.00000 | 23.29158 | 15.67188 | 0.03229 | 6.00864 |
May | 344.00000 | 23.75270 | 22.83415 | -0.6959 | 16.15809 |
June | 336.00000 | 23.93764 | 30.48099 | -0.5151 | 10.81644 |
July | 338.00000 | 23.97631 | 42.23710 | -0.3763 | 8.22399 |
August | 348.00000 | 23.94979 | 42.11076 | -0.3820 | 8.26177 |
September | 330.00000 | 23.95128 | 37.59726 | -0.4379 | 9.26773 |
October | 340.00000 | 23.41943 | 23.87660 | 0.17002 | 7.12557 |
November | 330.00000 | 21.99884 | 18.85632 | -0.2425 | 7.30050 |
December | 338.00000 | 21.15778 | 15.74319 | -0.5074 | 10.52048 |
Annual Sum or Average | 4030.00000 | 22.89029 | 25.45316 | -0.3380 | 9.18780 |
Minimum of Months | 308.00000 | 21.15778 | 15.67188 | -0.6959 | 6.00864 |
Maximum of Months | 348.00000 | 23.97631 | 42.23710 | 0.17002 | 16.15809 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.28089 | 17.80665 | -0.4851 | 10.23836 |
February | 308.00000 | 21.51067 | 18.87131 | -0.4140 | 9.33172 |
March | 348.00000 | 22.23134 | 18.62046 | -0.2384 | 7.35617 |
April | 330.00000 | 23.25109 | 15.72649 | 0.01819 | 6.04963 |
May | 344.00000 | 23.73709 | 22.85833 | -0.7061 | 16.52925 |
June | 336.00000 | 23.93638 | 30.48817 | -0.5190 | 10.90370 |
July | 338.00000 | 23.97580 | 42.26503 | -0.3792 | 8.26771 |
August | 348.00000 | 23.94943 | 42.13439 | -0.3849 | 8.30738 |
September | 330.00000 | 23.95056 | 37.61271 | -0.4413 | 9.32992 |
October | 340.00000 | 23.40234 | 23.90815 | 0.16309 | 7.11513 |
November | 330.00000 | 21.93824 | 18.91021 | -0.2605 | 7.45467 |
December | 338.00000 | 21.15030 | 15.74807 | -0.5142 | 10.65947 |
Annual Sum or Average | 4030.00000 | 22.86984 | 25.48290 | -0.3471 | 9.30711 |
Minimum of Months | 308.00000 | 21.15030 | 15.72649 | -0.7061 | 6.04963 |
Maximum of Months | 348.00000 | 23.97580 | 42.26503 | 0.16309 | 16.52925 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.23343 | 17.83651 | -0.5113 | 10.73526 |
February | 308.00000 | 21.45169 | 18.92889 | -0.4429 | 9.78827 |
March | 348.00000 | 22.10102 | 18.78838 | -0.2794 | 7.77290 |
April | 330.00000 | 23.15168 | 15.84857 | -0.0132 | 6.18528 |
May | 344.00000 | 23.69282 | 22.91802 | -0.7296 | 17.42691 |
June | 336.00000 | 23.93225 | 30.49643 | -0.5234 | 11.01332 |
July | 338.00000 | 23.97524 | 42.30384 | -0.3786 | 8.25761 |
August | 348.00000 | 23.94905 | 42.16585 | -0.3847 | 8.30485 |
September | 330.00000 | 23.94878 | 37.63732 | -0.4439 | 9.38244 |
October | 340.00000 | 23.35703 | 23.97842 | 0.14800 | 7.13185 |
November | 330.00000 | 21.81653 | 19.02033 | -0.2963 | 7.80936 |
December | 338.00000 | 21.13537 | 15.75715 | -0.5325 | 11.05083 |
Annual Sum or Average | 4030.00000 | 22.82254 | 25.54380 | -0.3659 | 9.58329 |
Minimum of Months | 308.00000 | 21.13537 | 15.75715 | -0.7296 | 6.18528 |
Maximum of Months | 348.00000 | 23.97524 | 42.30384 | 0.14800 | 17.42691 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.17622 | 17.76918 | -0.5810 | 12.31328 |
February | 308.00000 | 21.36173 | 18.93744 | -0.5182 | 11.27203 |
March | 348.00000 | 21.91911 | 18.96498 | -0.3588 | 8.82165 |
April | 330.00000 | 23.03143 | 15.88414 | -0.0577 | 6.48800 |
May | 344.00000 | 23.62343 | 22.96502 | -0.7640 | 18.85613 |
June | 336.00000 | 23.92302 | 30.49363 | -0.5049 | 10.70183 |
July | 338.00000 | 23.98078 | 42.05604 | -0.3397 | 7.70366 |
August | 348.00000 | 23.95320 | 41.90177 | -0.3489 | 7.80252 |
September | 330.00000 | 23.94927 | 37.53508 | -0.4229 | 9.05739 |
October | 340.00000 | 23.29182 | 23.97503 | 0.12751 | 7.34993 |
November | 330.00000 | 21.66393 | 19.08880 | -0.3583 | 8.61418 |
December | 338.00000 | 21.11742 | 15.66889 | -0.5902 | 12.43325 |
Annual Sum or Average | 4030.00000 | 22.75995 | 25.50667 | -0.3930 | 10.12500 |
Minimum of Months | 308.00000 | 21.11742 | 15.66889 | -0.7640 | 6.48800 |
Maximum of Months | 348.00000 | 23.98078 | 42.05604 | 0.12751 | 18.85613 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 69081974.13 | 18587108.85 | 7.67 | 69081974.13 | 0.00 | 0.00 | 0.31 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 4661.10 | 14-FEB-16:00 | 4661.10 | 14-FEB-16:00 | 0.00 | 14-FEB-16:20 | 1237.71 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.158556E+09 | 43011382.15 | 24.33 | 0.158556E+09 | -0.0 | 0.00 | 0.31 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 4734.72 | 08-MAR-16:00 | 4734.72 | 08-MAR-16:00 | 0.00 | 08-MAR-16:00 | 1269.57 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.317927E+10 | 0.826544E+09 | 172.03 | 0.317927E+10 | 1046.45 | 0.00 | 0.70 | 13-APR-17:00 | 0.00 | 01-APR-00:05 | 11693.23 | 13-APR-17:00 | 11693.23 | 13-APR-17:00 | 1.04 | 14-APR-21:15 | 2996.75 | 13-APR-17:00 | 0.00 | 01-APR-00:05 |
May | 0.782756E+10 | 0.204266E+10 | 310.92 | 0.778012E+10 | 47441862.22 | 0.00 | 0.88 | 19-MAY-17:00 | 0.00 | 01-MAY-00:10 | 15271.73 | 19-MAY-16:50 | 15271.73 | 19-MAY-16:50 | 977.29 | 28-MAY-15:30 | 4032.71 | 19-MAY-16:50 | 0.00 | 01-MAY-00:10 |
June | 0.168233E+11 | 0.455858E+10 | 426.74 | 0.165573E+11 | 0.265974E+09 | 0.00 | 1.00 | 13-JUN-16:10 | 0.00 | 01-JUN-00:10 | 38768.54 | 29-JUN-07:02 | 38458.49 | 29-JUN-07:02 | 7127.54 | 24-JUN-07:03 | 9196.31 | 29-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.241400E+11 | 0.634437E+10 | 493.83 | 0.217201E+11 | 0.241996E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:03 | 41162.25 | 26-JUL-07:02 | 38573.67 | 22-JUL-07:02 | 13987.29 | 16-JUL-07:03 | 8979.01 | 11-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.219966E+11 | 0.564783E+10 | 488.93 | 0.198493E+11 | 0.214726E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 41528.65 | 14-AUG-07:02 | 35737.29 | 19-AUG-07:02 | 16636.00 | 13-AUG-07:02 | 8943.63 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.144025E+11 | 0.363744E+10 | 434.50 | 0.133392E+11 | 0.106325E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 36895.31 | 03-SEP-07:02 | 32706.15 | 03-SEP-07:02 | 11186.86 | 05-SEP-07:03 | 7827.61 | 03-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.536352E+10 | 0.135177E+10 | 223.61 | 0.513676E+10 | 0.226762E+09 | 0.00 | 1.00 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 | 22703.44 | 02-OCT-07:03 | 17276.52 | 02-OCT-07:03 | 5426.92 | 02-OCT-07:03 | 4809.01 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 24538.67 | 6914.66 | 2.17 | 23730.15 | 808.51 | 0.00 | 0.00 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 34.86 | 02-NOV-15:00 | 33.52 | 02-NOV-15:00 | 1.34 | 02-NOV-15:00 | 9.82 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.939604E+11 | 0.244708E+11 | 2584.72 | 0.877898E+11 | 0.617065E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.241400E+11 | 0.634437E+10 | 493.83 | 0.217201E+11 | 0.241996E+10 | 0.00 | 1.00 | 0.00 | 41528.65 | 38573.67 | 16636.00 | 9196.31 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 3887964.96 | 1059765.13 | 3.64 | 3887964.96 | 0.00 | 0.00 | 0.30 | 01-JAN-18:20 | 0.00 | 01-JAN-00:05 | 2478.86 | 01-JAN-18:20 | 2478.86 | 01-JAN-18:20 | 0.00 | 01-JAN-18:10 | 646.77 | 01-JAN-18:20 | 0.00 | 01-JAN-00:05 |
February | 72196291.89 | 19068650.18 | 12.89 | 72196291.89 | 0.00 | 0.00 | 0.40 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 3347.53 | 14-FEB-16:00 | 3347.53 | 14-FEB-16:00 | 0.00 | 13-FEB-15:30 | 867.22 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.214615E+09 | 55240097.94 | 39.17 | 0.214592E+09 | 23477.31 | 0.00 | 1.00 | 12-MAR-17:01 | 0.00 | 01-MAR-00:10 | 20234.50 | 12-MAR-17:01 | 20234.50 | 26-MAR-17:40 | 36.09 | 28-MAR-22:20 | 4277.90 | 12-MAR-17:01 | 0.00 | 01-MAR-00:10 |
April | 0.247672E+10 | 0.612731E+09 | 182.73 | 0.247644E+10 | 282462.30 | 0.00 | 1.00 | 01-APR-18:01 | 0.00 | 01-APR-00:05 | 20234.50 | 13-APR-20:08 | 20234.50 | 13-APR-21:30 | 550.55 | 14-APR-22:10 | 4421.90 | 29-APR-18:02 | 0.00 | 01-APR-00:05 |
May | 0.530968E+10 | 0.132724E+10 | 305.40 | 0.525896E+10 | 50719839.16 | 0.00 | 1.00 | 02-MAY-20:01 | 0.00 | 01-MAY-00:10 | 20863.50 | 21-MAY-22:58 | 20250.04 | 27-MAY-19:08 | 6661.49 | 27-MAY-20:45 | 4565.69 | 21-MAY-19:28 | 0.00 | 01-MAY-00:10 |
June | 0.962680E+10 | 0.256175E+10 | 407.42 | 0.943796E+10 | 0.188831E+09 | 0.00 | 1.00 | 02-JUN-20:01 | 0.00 | 01-JUN-00:10 | 21018.79 | 30-JUN-22:10 | 20729.64 | 29-JUN-07:02 | 6649.68 | 04-JUN-17:30 | 4922.83 | 29-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.133784E+11 | 0.347912E+10 | 478.04 | 0.119221E+11 | 0.145630E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:03 | 22484.68 | 31-JUL-20:03 | 20622.32 | 22-JUL-07:02 | 9863.72 | 15-JUL-19:17 | 4812.96 | 21-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.123821E+11 | 0.313992E+10 | 468.60 | 0.110711E+11 | 0.131099E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 22081.72 | 14-AUG-07:02 | 20334.68 | 16-AUG-22:08 | 9646.75 | 25-AUG-20:10 | 4793.93 | 12-AUG-18:03 | 0.00 | 01-AUG-00:10 |
September | 0.903294E+10 | 0.221333E+10 | 397.13 | 0.830786E+10 | 0.725076E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 21467.83 | 04-SEP-20:58 | 20263.83 | 13-SEP-20:02 | 8880.92 | 05-SEP-20:10 | 4696.49 | 04-SEP-19:08 | 0.00 | 01-SEP-00:05 |
October | 0.354553E+10 | 0.866254E+09 | 223.34 | 0.337586E+10 | 0.169666E+09 | 0.00 | 1.00 | 01-OCT-18:02 | 0.00 | 01-OCT-00:10 | 21349.01 | 02-OCT-20:02 | 20279.93 | 01-OCT-18:02 | 7302.90 | 02-OCT-20:02 | 4539.87 | 02-OCT-20:02 | 0.00 | 01-OCT-00:10 |
November | 14707197.78 | 3906540.13 | 10.13 | 14571741.29 | 135456.49 | 0.00 | 1.00 | 02-NOV-22:51 | 0.00 | 01-NOV-00:10 | 10096.36 | 02-NOV-22:51 | 10096.36 | 02-NOV-22:51 | 77.55 | 09-NOV-23:10 | 2137.41 | 02-NOV-22:51 | 0.00 | 01-NOV-00:10 |
December | 1550454.97 | 427142.65 | 1.14 | 1550454.97 | -0.0 | 0.00 | 0.16 | 02-DEC-19:17 | 0.00 | 01-DEC-00:05 | 1263.22 | 02-DEC-19:17 | 1263.22 | 02-DEC-19:17 | 0.00 | 24-DEC-18:50 | 342.29 | 02-DEC-19:17 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.560590E+11 | 0.142801E+11 | 2529.63 | 0.521570E+11 | 0.390203E+10 | 0.00 | ||||||||||||||
Minimum of Months | 1550454.97 | 427142.65 | 1.14 | 1550454.97 | -0.0 | 0.00 | 0.16 | 0.00 | 1263.22 | 1263.22 | 0.00 | 342.29 | 0.00 | |||||||
Maximum of Months | 0.133784E+11 | 0.347912E+10 | 478.04 | 0.119221E+11 | 0.145630E+10 | 0.00 | 1.00 | 0.00 | 22484.68 | 20729.64 | 9863.72 | 4922.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 48288683.37 | 12924631.89 | 8.50 | 48288683.37 | 0.00 | 0.00 | 0.33 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 2877.69 | 14-FEB-16:00 | 2877.69 | 14-FEB-16:00 | 0.00 | 14-FEB-15:30 | 759.55 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 97217884.49 | 26298963.45 | 26.00 | 97217884.49 | 0.00 | 0.00 | 0.37 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3241.01 | 08-MAR-14:00 | 3241.01 | 08-MAR-14:00 | 0.00 | 08-MAR-13:50 | 855.86 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.156414E+10 | 0.407496E+09 | 142.42 | 0.156414E+10 | 0.53 | 0.00 | 0.65 | 13-APR-16:10 | 0.00 | 01-APR-00:05 | 6056.71 | 13-APR-16:10 | 6056.71 | 13-APR-16:10 | 0.00 | 15-APR-08:15 | 1565.81 | 13-APR-16:30 | 0.00 | 01-APR-00:05 |
May | 0.341669E+10 | 0.897113E+09 | 248.03 | 0.339510E+10 | 21587767.09 | 0.00 | 0.82 | 19-MAY-16:10 | 0.00 | 01-MAY-00:10 | 7865.17 | 19-MAY-16:10 | 7865.17 | 19-MAY-16:10 | 735.56 | 22-MAY-06:03 | 2119.63 | 19-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.721177E+10 | 0.198222E+10 | 331.49 | 0.708335E+10 | 0.128422E+09 | 0.00 | 1.00 | 15-JUN-06:03 | 0.00 | 01-JUN-00:10 | 22501.53 | 29-JUN-06:02 | 21453.63 | 28-JUN-06:02 | 4001.81 | 24-JUN-06:02 | 5065.00 | 29-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.996737E+10 | 0.265179E+10 | 360.63 | 0.899709E+10 | 0.970281E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:03 | 23001.04 | 01-JUL-06:02 | 21554.43 | 21-JUL-06:02 | 9042.61 | 01-JUL-06:02 | 4976.10 | 04-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.921664E+10 | 0.239248E+10 | 367.57 | 0.831171E+10 | 0.904927E+09 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23259.33 | 14-AUG-06:02 | 20023.70 | 02-AUG-06:02 | 9358.15 | 14-AUG-06:02 | 4930.61 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.634389E+10 | 0.161961E+10 | 328.38 | 0.589289E+10 | 0.451001E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 22418.89 | 05-SEP-06:02 | 19761.40 | 03-SEP-07:02 | 9323.31 | 05-SEP-06:02 | 4767.46 | 05-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.248345E+10 | 0.630762E+09 | 184.52 | 0.238132E+10 | 0.102128E+09 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 20079.52 | 02-OCT-06:02 | 15927.99 | 02-OCT-06:02 | 4528.29 | 03-OCT-06:03 | 4253.29 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 863336.66 | 238721.44 | 3.00 | 861997.70 | 1338.96 | 0.00 | 0.10 | 01-NOV-06:10 | 0.00 | 01-NOV-00:10 | 821.50 | 01-NOV-06:10 | 821.50 | 01-NOV-06:10 | 2.22 | 02-NOV-15:00 | 226.07 | 01-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.403503E+11 | 0.106209E+11 | 2000.55 | 0.377720E+11 | 0.257835E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.996737E+10 | 0.265179E+10 | 367.57 | 0.899709E+10 | 0.970281E+09 | 0.00 | 1.00 | 0.00 | 23259.33 | 21554.43 | 9358.15 | 5065.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 41898115.60 | 11266178.29 | 8.00 | 41898115.60 | 0.00 | 0.00 | 0.31 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 2673.15 | 14-FEB-16:00 | 2673.15 | 14-FEB-16:00 | 0.00 | 14-FEB-15:00 | 709.44 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 81649732.16 | 22160582.72 | 23.00 | 81649732.16 | 0.00 | 0.00 | 0.35 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3026.07 | 08-MAR-14:00 | 3026.07 | 08-MAR-14:00 | 0.00 | 08-MAR-13:50 | 803.65 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.151560E+10 | 0.395357E+09 | 139.33 | 0.151560E+10 | 0.55 | 0.00 | 0.65 | 13-APR-16:10 | 0.00 | 01-APR-00:05 | 5971.18 | 13-APR-16:10 | 5971.18 | 13-APR-16:10 | 0.00 | 15-APR-08:15 | 1546.12 | 13-APR-16:30 | 0.00 | 01-APR-00:05 |
May | 0.339652E+10 | 0.891728E+09 | 247.86 | 0.337508E+10 | 21438604.99 | 0.00 | 0.83 | 19-MAY-16:10 | 0.00 | 01-MAY-00:10 | 7856.94 | 19-MAY-16:10 | 7856.94 | 19-MAY-16:10 | 791.61 | 22-MAY-06:03 | 2115.45 | 19-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.723029E+10 | 0.198484E+10 | 331.78 | 0.710131E+10 | 0.128977E+09 | 0.00 | 1.00 | 15-JUN-06:03 | 0.00 | 01-JUN-00:10 | 22377.29 | 29-JUN-06:02 | 21335.81 | 28-JUN-06:02 | 3972.92 | 24-JUN-06:02 | 5036.90 | 29-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.100125E+11 | 0.265930E+10 | 360.64 | 0.903734E+10 | 0.975123E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:03 | 23260.64 | 16-JUL-07:03 | 21436.81 | 21-JUL-06:02 | 8982.48 | 01-JUL-06:02 | 4948.45 | 04-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.925802E+10 | 0.239925E+10 | 368.00 | 0.834773E+10 | 0.910293E+09 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23131.41 | 14-AUG-06:02 | 19917.86 | 02-AUG-06:02 | 9292.25 | 14-AUG-06:02 | 4903.39 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.636617E+10 | 0.162322E+10 | 329.05 | 0.591155E+10 | 0.454622E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 22295.83 | 05-SEP-06:02 | 19663.92 | 03-SEP-07:02 | 9257.41 | 05-SEP-06:02 | 4741.29 | 05-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.246987E+10 | 0.626780E+09 | 183.77 | 0.236693E+10 | 0.102937E+09 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 20969.72 | 02-OCT-06:02 | 16667.04 | 02-OCT-06:02 | 4659.02 | 03-OCT-06:03 | 4441.85 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 364239.54 | 101681.14 | 2.17 | 364232.99 | 6.55 | 0.00 | 0.05 | 01-NOV-06:10 | 0.00 | 01-NOV-00:10 | 429.17 | 01-NOV-06:10 | 429.17 | 01-NOV-06:10 | 0.00 | 02-NOV-16:10 | 119.53 | 01-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.403729E+11 | 0.106140E+11 | 1993.60 | 0.377795E+11 | 0.259339E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.100125E+11 | 0.265930E+10 | 368.00 | 0.903734E+10 | 0.975123E+09 | 0.00 | 1.00 | 0.00 | 23260.64 | 21436.81 | 9292.25 | 5036.90 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 33107247.23 | 8968383.35 | 7.50 | 33107247.23 | -0.0 | 0.00 | 0.28 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 2364.53 | 14-FEB-16:00 | 2364.53 | 14-FEB-16:00 | 0.00 | 14-FEB-15:50 | 633.22 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 58530920.79 | 15968137.56 | 18.83 | 58530920.79 | 0.00 | 0.00 | 0.31 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2682.04 | 08-MAR-14:00 | 2682.04 | 08-MAR-14:00 | 0.00 | 08-MAR-15:10 | 719.43 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.139971E+10 | 0.367012E+09 | 130.83 | 0.139971E+10 | 0.39 | 0.00 | 0.63 | 13-APR-16:20 | 0.00 | 01-APR-00:05 | 5762.73 | 13-APR-16:10 | 5762.73 | 13-APR-16:10 | 0.00 | 15-APR-08:30 | 1500.86 | 13-APR-16:30 | 0.00 | 01-APR-00:05 |
May | 0.324816E+10 | 0.856663E+09 | 241.86 | 0.322900E+10 | 19164479.11 | 0.00 | 0.81 | 19-MAY-16:10 | 0.00 | 01-MAY-00:10 | 7709.39 | 19-MAY-16:10 | 7709.39 | 19-MAY-16:10 | 587.94 | 22-MAY-06:03 | 2083.71 | 19-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.704697E+10 | 0.194202E+10 | 330.16 | 0.692415E+10 | 0.122824E+09 | 0.00 | 1.00 | 15-JUN-06:03 | 0.00 | 01-JUN-00:10 | 22365.36 | 29-JUN-06:02 | 21322.54 | 28-JUN-06:02 | 3939.53 | 24-JUN-06:02 | 5034.64 | 29-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.981158E+10 | 0.261454E+10 | 360.76 | 0.885842E+10 | 0.953157E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:03 | 22863.26 | 01-JUL-06:02 | 21422.72 | 21-JUL-06:02 | 9007.50 | 01-JUL-06:02 | 4946.31 | 04-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.905886E+10 | 0.235587E+10 | 367.41 | 0.817290E+10 | 0.885957E+09 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23122.96 | 14-AUG-06:02 | 19688.64 | 20-AUG-07:02 | 9311.38 | 14-AUG-06:02 | 4901.73 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.619281E+10 | 0.158491E+10 | 326.33 | 0.575553E+10 | 0.437280E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 22287.68 | 05-SEP-06:02 | 19634.39 | 03-SEP-07:02 | 9274.07 | 05-SEP-06:02 | 4739.55 | 05-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.236629E+10 | 0.602337E+09 | 178.30 | 0.226729E+10 | 99001319.97 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 19717.12 | 02-OCT-06:02 | 15630.07 | 02-OCT-06:02 | 4258.02 | 03-OCT-06:03 | 4176.51 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 962.38 | 271.65 | 1.67 | 960.66 | 1.73 | 0.00 | 0.00 | 03-NOV-17:20 | 0.00 | 01-NOV-00:10 | 0.25 | 03-NOV-17:20 | 0.25 | 03-NOV-17:20 | 0.00 | 02-NOV-16:10 | 0.07 | 03-NOV-17:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.392160E+11 | 0.103483E+11 | 1963.65 | 0.366986E+11 | 0.251738E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.981158E+10 | 0.261454E+10 | 367.41 | 0.885842E+10 | 0.953157E+09 | 0.00 | 1.00 | 0.00 | 23122.96 | 21422.72 | 9311.38 | 5034.64 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 49537528.16 | 13429988.23 | 6.83 | 49537528.16 | 0.00 | 0.00 | 0.29 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 4191.79 | 14-FEB-16:00 | 4191.79 | 14-FEB-16:00 | 0.00 | 14-FEB-15:50 | 1118.48 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 88874001.26 | 24278707.34 | 15.00 | 88874001.26 | -0.0 | 0.00 | 0.30 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 4234.22 | 08-MAR-14:00 | 4234.22 | 08-MAR-14:00 | 0.00 | 08-MAR-15:30 | 1141.42 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.228069E+10 | 0.598586E+09 | 128.00 | 0.228069E+10 | -0.0 | 0.00 | 0.65 | 28-APR-15:00 | 0.00 | 01-APR-00:05 | 10149.94 | 28-APR-14:50 | 10149.94 | 28-APR-14:50 | 0.00 | 28-APR-16:20 | 2603.56 | 29-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.558574E+10 | 0.147108E+10 | 233.42 | 0.555324E+10 | 32493720.24 | 0.00 | 0.85 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 | 13863.97 | 19-MAY-15:00 | 13863.97 | 19-MAY-15:00 | 868.74 | 23-MAY-14:10 | 3706.11 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.125228E+11 | 0.343661E+10 | 319.81 | 0.123173E+11 | 0.205527E+09 | 0.00 | 1.00 | 14-JUN-13:50 | 0.00 | 01-JUN-00:10 | 37342.08 | 25-JUN-08:62 | 36329.09 | 27-JUN-07:02 | 5565.42 | 24-JUN-07:03 | 8652.09 | 29-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.174466E+11 | 0.461387E+10 | 349.95 | 0.157786E+11 | 0.166801E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:03 | 39497.30 | 16-JUL-08:62 | 36481.36 | 23-JUL-08:61 | 14051.42 | 17-JUL-07:03 | 8618.63 | 04-JUL-08:62 | 0.00 | 01-JUL-00:03 |
August | 0.162554E+11 | 0.418895E+10 | 359.83 | 0.146463E+11 | 0.160905E+10 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 39319.44 | 13-AUG-08:62 | 35612.58 | 20-AUG-08:62 | 15635.59 | 13-AUG-08:62 | 8431.78 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.109383E+11 | 0.277408E+10 | 319.90 | 0.101255E+11 | 0.812804E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 37530.53 | 04-SEP-08:62 | 35439.09 | 03-SEP-08:62 | 13995.94 | 05-SEP-07:03 | 8144.18 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.412439E+10 | 0.104212E+10 | 171.24 | 0.393502E+10 | 0.189365E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 28811.00 | 02-OCT-07:03 | 22650.06 | 02-OCT-07:03 | 6160.94 | 02-OCT-07:03 | 6103.90 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.692924E+11 | 0.181630E+11 | 1903.98 | 0.647751E+11 | 0.451725E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.174466E+11 | 0.461387E+10 | 359.83 | 0.157786E+11 | 0.166801E+10 | 0.00 | 1.00 | 0.00 | 39497.30 | 36481.36 | 15635.59 | 8652.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 23376154.18 | 6346477.27 | 6.33 | 23376154.18 | 0.00 | 0.00 | 0.29 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 2127.60 | 14-FEB-16:00 | 2127.60 | 14-FEB-16:00 | 0.00 | 14-FEB-15:40 | 568.47 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 38965237.73 | 10671647.42 | 13.50 | 38965237.73 | 0.00 | 0.00 | 0.28 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2033.12 | 08-MAR-14:00 | 2033.12 | 08-MAR-14:00 | 0.00 | 08-MAR-14:00 | 550.98 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.114689E+10 | 0.301386E+09 | 124.83 | 0.114689E+10 | -0.0 | 0.00 | 0.65 | 28-APR-15:00 | 0.00 | 01-APR-00:05 | 5222.62 | 28-APR-15:00 | 5222.62 | 28-APR-15:00 | 0.00 | 28-APR-13:30 | 1341.17 | 29-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.285632E+10 | 0.752839E+09 | 230.00 | 0.284033E+10 | 15989439.07 | 0.00 | 0.85 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 | 7154.62 | 19-MAY-15:00 | 7154.62 | 19-MAY-15:00 | 436.03 | 23-MAY-14:10 | 1913.18 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.643492E+10 | 0.176775E+10 | 318.54 | 0.633051E+10 | 0.104409E+09 | 0.00 | 1.00 | 14-JUN-13:50 | 0.00 | 01-JUN-00:10 | 19313.84 | 25-JUN-08:62 | 18792.22 | 27-JUN-07:02 | 2651.93 | 24-JUN-07:03 | 4472.65 | 29-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.898056E+10 | 0.237749E+10 | 350.12 | 0.812469E+10 | 0.855872E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:03 | 20430.73 | 16-JUL-08:62 | 18859.97 | 23-JUL-08:61 | 7113.56 | 16-JUL-08:62 | 4458.19 | 04-JUL-08:62 | 0.00 | 01-JUL-00:03 |
August | 0.836368E+10 | 0.215737E+10 | 359.53 | 0.753969E+10 | 0.823993E+09 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 20338.91 | 13-AUG-08:62 | 18432.14 | 20-AUG-08:62 | 8084.54 | 13-AUG-08:62 | 4361.13 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.562471E+10 | 0.142730E+10 | 319.35 | 0.521175E+10 | 0.412958E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 19414.19 | 04-SEP-08:62 | 18343.54 | 03-SEP-08:62 | 6793.16 | 05-SEP-07:03 | 4212.07 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.211896E+10 | 0.535419E+09 | 169.43 | 0.202271E+10 | 96248410.89 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 13876.27 | 02-OCT-07:03 | 10893.22 | 02-OCT-07:03 | 2983.05 | 02-OCT-07:03 | 2940.07 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.355884E+11 | 0.933656E+10 | 1891.64 | 0.332789E+11 | 0.230947E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.898056E+10 | 0.237749E+10 | 359.53 | 0.812469E+10 | 0.855872E+09 | 0.00 | 1.00 | 0.00 | 20430.73 | 18859.97 | 8084.54 | 4472.65 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 20630234.50 | 5618079.30 | 6.17 | 20630234.50 | 0.00 | 0.00 | 0.27 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 2005.34 | 14-FEB-16:00 | 2005.34 | 14-FEB-16:00 | 0.00 | 14-FEB-15:30 | 537.83 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 33610808.32 | 9229404.01 | 12.00 | 33610808.32 | -0.0 | 0.00 | 0.26 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 1911.78 | 08-MAR-16:00 | 1911.78 | 08-MAR-16:00 | 0.00 | 08-MAR-15:50 | 520.06 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.110467E+10 | 0.290839E+09 | 122.25 | 0.110467E+10 | -0.0 | 0.00 | 0.64 | 29-APR-15:00 | 0.00 | 01-APR-00:05 | 5144.84 | 28-APR-15:00 | 5144.84 | 28-APR-15:00 | 0.00 | 26-APR-14:10 | 1325.10 | 29-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.279991E+10 | 0.738942E+09 | 228.33 | 0.278452E+10 | 15387963.32 | 0.00 | 0.85 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 | 7096.02 | 19-MAY-15:00 | 7096.02 | 19-MAY-15:00 | 426.21 | 23-MAY-14:10 | 1898.68 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.637314E+10 | 0.175182E+10 | 317.63 | 0.627056E+10 | 0.102584E+09 | 0.00 | 1.00 | 14-JUN-13:50 | 0.00 | 01-JUN-00:10 | 19208.23 | 25-JUN-08:62 | 18688.81 | 27-JUN-07:02 | 2587.40 | 24-JUN-07:03 | 4447.22 | 29-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.891111E+10 | 0.235992E+10 | 349.97 | 0.806339E+10 | 0.847722E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:03 | 20319.74 | 16-JUL-08:62 | 18752.33 | 23-JUL-08:61 | 7083.48 | 16-JUL-08:62 | 4434.01 | 04-JUL-08:62 | 0.00 | 01-JUL-00:03 |
August | 0.829368E+10 | 0.214013E+10 | 359.33 | 0.747847E+10 | 0.815206E+09 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 20228.47 | 13-AUG-08:62 | 18326.12 | 20-AUG-08:62 | 8049.28 | 13-AUG-08:62 | 4337.44 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.556470E+10 | 0.141288E+10 | 319.26 | 0.515744E+10 | 0.407261E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 19308.38 | 04-SEP-08:62 | 18237.60 | 03-SEP-08:62 | 6601.15 | 05-SEP-07:03 | 4189.10 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.208215E+10 | 0.526490E+09 | 167.60 | 0.198738E+10 | 94765756.17 | 0.00 | 1.00 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 | 13426.50 | 02-OCT-07:03 | 10527.06 | 02-OCT-07:03 | 2899.45 | 02-OCT-07:03 | 2844.81 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.351836E+11 | 0.923587E+10 | 1882.54 | 0.329007E+11 | 0.228293E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.891111E+10 | 0.235992E+10 | 359.33 | 0.806339E+10 | 0.847722E+09 | 0.00 | 1.00 | 0.00 | 20319.74 | 18752.33 | 8049.28 | 4447.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 14511540.31 | 3982505.60 | 5.17 | 14511540.31 | 0.00 | 0.00 | 0.23 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 1702.42 | 14-FEB-16:00 | 1702.42 | 14-FEB-16:00 | 0.00 | 14-FEB-16:00 | 461.31 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 22695421.23 | 6273199.80 | 8.67 | 22695421.23 | 0.00 | 0.00 | 0.23 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 1647.47 | 08-MAR-16:00 | 1647.47 | 08-MAR-16:00 | 0.00 | 08-MAR-15:40 | 452.22 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.101493E+10 | 0.268575E+09 | 116.42 | 0.101493E+10 | -0.0 | 0.00 | 0.63 | 29-APR-15:00 | 0.00 | 01-APR-00:05 | 4987.34 | 28-APR-15:00 | 4987.34 | 28-APR-15:00 | 0.00 | 29-APR-15:50 | 1293.57 | 29-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.267147E+10 | 0.708104E+09 | 218.25 | 0.265756E+10 | 13909727.90 | 0.00 | 0.84 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 | 6989.09 | 19-MAY-15:00 | 6989.09 | 19-MAY-15:00 | 400.20 | 23-MAY-14:10 | 1875.67 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.627587E+10 | 0.172841E+10 | 314.90 | 0.617752E+10 | 98351873.18 | 0.00 | 1.00 | 14-JUN-13:50 | 0.00 | 01-JUN-00:10 | 19184.34 | 25-JUN-08:62 | 18614.77 | 28-JUN-07:02 | 2408.36 | 24-JUN-07:03 | 4436.04 | 29-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.884686E+10 | 0.234515E+10 | 349.61 | 0.800843E+10 | 0.838434E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:03 | 19959.72 | 25-JUL-07:02 | 18717.47 | 23-JUL-08:61 | 6722.93 | 16-JUL-08:62 | 4429.14 | 04-JUL-08:62 | 0.00 | 01-JUL-00:03 |
August | 0.822614E+10 | 0.212467E+10 | 359.27 | 0.742214E+10 | 0.803994E+09 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 20205.59 | 13-AUG-08:62 | 18292.18 | 20-AUG-08:62 | 8060.38 | 13-AUG-08:62 | 4332.63 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.547392E+10 | 0.139222E+10 | 318.03 | 0.507723E+10 | 0.396689E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 19285.89 | 04-SEP-08:62 | 18200.74 | 03-SEP-08:62 | 6045.01 | 05-SEP-07:03 | 4184.23 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.201053E+10 | 0.509428E+09 | 162.76 | 0.191861E+10 | 91916245.35 | 0.00 | 1.00 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 | 12188.72 | 02-OCT-07:03 | 9517.24 | 02-OCT-07:03 | 2671.48 | 02-OCT-07:03 | 2582.68 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.345569E+11 | 0.908682E+10 | 1853.08 | 0.323136E+11 | 0.224330E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.884686E+10 | 0.234515E+10 | 359.27 | 0.800843E+10 | 0.838434E+09 | 0.00 | 1.00 | 0.00 | 20205.59 | 18717.47 | 8060.38 | 4436.04 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 6232963.03 | 1734635.21 | 3.00 | 6232963.03 | -0.0 | 0.00 | 0.15 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 | 1199.88 | 14-FEB-16:00 | 1199.88 | 14-FEB-16:00 | 0.00 | 14-FEB-15:40 | 332.07 | 14-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 12628539.88 | 3544226.11 | 5.17 | 12628539.88 | 0.00 | 0.00 | 0.16 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1285.10 | 08-MAR-14:00 | 1285.10 | 08-MAR-14:00 | 0.00 | 08-MAR-15:40 | 358.63 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.981184E+09 | 0.261895E+09 | 110.75 | 0.981184E+09 | 0.00 | 0.00 | 0.59 | 28-APR-13:00 | 0.00 | 01-APR-00:05 | 5110.79 | 28-APR-13:00 | 5110.79 | 28-APR-13:00 | 0.00 | 28-APR-15:40 | 1316.51 | 29-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.271474E+10 | 0.725585E+09 | 213.83 | 0.270045E+10 | 14286690.53 | 0.00 | 0.80 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 | 7214.47 | 19-MAY-15:00 | 7214.47 | 19-MAY-15:00 | 387.64 | 28-MAY-11:30 | 1959.19 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.681604E+10 | 0.187807E+10 | 312.66 | 0.671370E+10 | 0.102341E+09 | 0.00 | 1.00 | 14-JUN-14:10 | 0.00 | 01-JUN-00:10 | 21022.12 | 25-JUN-08:62 | 20463.61 | 29-JUN-07:02 | 2186.67 | 24-JUN-07:03 | 4878.29 | 29-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.976391E+10 | 0.258493E+10 | 349.36 | 0.884662E+10 | 0.917287E+09 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:03 | 21895.90 | 04-JUL-08:62 | 20593.64 | 23-JUL-08:61 | 6911.55 | 16-JUL-08:62 | 4871.61 | 04-JUL-08:62 | 0.00 | 01-JUL-00:03 |
August | 0.909209E+10 | 0.234403E+10 | 358.06 | 0.821276E+10 | 0.879333E+09 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 22152.99 | 13-AUG-08:62 | 20114.75 | 20-AUG-08:62 | 8924.07 | 13-AUG-08:62 | 4691.80 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.592005E+10 | 0.150725E+10 | 308.92 | 0.550320E+10 | 0.416855E+09 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 | 20668.12 | 03-SEP-08:62 | 19952.03 | 03-SEP-08:62 | 4155.56 | 04-SEP-08:62 | 4582.53 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.206525E+10 | 0.525197E+09 | 155.35 | 0.196912E+10 | 96130486.04 | 0.00 | 0.88 | 01-OCT-14:20 | 0.00 | 01-OCT-00:10 | 8592.86 | 02-OCT-14:30 | 8432.51 | 01-OCT-14:10 | 1905.99 | 02-OCT-07:03 | 2135.70 | 01-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.373721E+11 | 0.983224E+10 | 1817.11 | 0.349459E+11 | 0.242623E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.976391E+10 | 0.258493E+10 | 358.06 | 0.884662E+10 | 0.917287E+09 | 0.00 | 1.00 | 0.00 | 22152.99 | 20593.64 | 8924.07 | 4878.29 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.60 | 76.56 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.91 | 69.98 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.30 | 57.41 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.90 | 42.39 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.99 | 31.43 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.50 | 20.74 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.83 | 13.32 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.55 | 15.85 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.88 | 27.78 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.58 | 46.74 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 206.99 | 63.53 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.63 | 78.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.96 | 45.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.50 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.63 | 78.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.60 | 76.56 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.91 | 69.98 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.30 | 57.41 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.90 | 42.39 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.99 | 31.43 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.50 | 20.74 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.83 | 13.32 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.55 | 15.85 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.88 | 27.78 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.58 | 46.74 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 206.99 | 63.53 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.63 | 78.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.96 | 45.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.50 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.63 | 78.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.60 | 76.56 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.91 | 69.98 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.30 | 57.41 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.90 | 42.39 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.99 | 31.43 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.50 | 20.74 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.83 | 13.32 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.55 | 15.85 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.88 | 27.78 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.58 | 46.74 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 206.99 | 63.53 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.63 | 78.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.96 | 45.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.50 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.63 | 78.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.60 | 76.56 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.91 | 69.98 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.30 | 57.41 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.90 | 42.39 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.99 | 31.43 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.50 | 20.74 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.83 | 13.32 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.55 | 15.85 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.88 | 27.78 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.58 | 46.74 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 206.99 | 63.53 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.63 | 78.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.96 | 45.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.50 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.63 | 78.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 199.21 | 155.01 | 44.20 | 239.11 | 91.12 | 0.00 | 0.00 | 0.00 |
February | 194.95 | 142.41 | 52.55 | 239.45 | 83.29 | 0.00 | 0.00 | 0.00 |
March | 143.66 | 86.85 | 56.81 | 180.99 | 68.36 | 0.00 | 0.00 | 0.00 |
April | 112.04 | 45.99 | 66.05 | 145.53 | 50.59 | 0.00 | 0.00 | 0.00 |
May | 74.72 | 16.44 | 58.28 | 97.41 | 37.57 | 0.00 | 0.00 | 0.00 |
June | 63.21 | 7.79 | 55.42 | 96.47 | 24.87 | 0.00 | 0.00 | 0.00 |
July | 69.94 | 11.17 | 58.77 | 116.06 | 16.01 | 0.00 | 0.00 | 0.00 |
August | 96.17 | 31.26 | 64.91 | 151.89 | 19.01 | 0.00 | 0.00 | 0.00 |
September | 132.99 | 74.16 | 58.83 | 194.54 | 33.24 | 0.00 | 0.00 | 0.00 |
October | 181.94 | 134.00 | 47.94 | 239.99 | 55.78 | 0.00 | 0.00 | 0.00 |
November | 202.65 | 155.53 | 47.12 | 249.07 | 75.71 | 0.00 | 0.00 | 0.00 |
December | 216.14 | 178.29 | 37.85 | 260.68 | 93.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.33 | 86.29 | 54.04 | 183.95 | 53.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.21 | 7.79 | 37.85 | 96.47 | 16.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.14 | 178.29 | 66.05 | 260.68 | 93.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 199.21 | 155.01 | 44.20 | 239.11 | 91.12 | 0.00 | 0.00 | 0.00 |
February | 194.95 | 142.41 | 52.55 | 239.45 | 83.29 | 0.00 | 0.00 | 0.00 |
March | 143.66 | 86.85 | 56.81 | 180.99 | 68.36 | 0.00 | 0.00 | 0.00 |
April | 112.04 | 45.99 | 66.05 | 145.53 | 50.59 | 0.00 | 0.00 | 0.00 |
May | 74.72 | 16.44 | 58.28 | 97.41 | 37.57 | 0.00 | 0.00 | 0.00 |
June | 63.21 | 7.79 | 55.42 | 96.47 | 24.87 | 0.00 | 0.00 | 0.00 |
July | 69.94 | 11.17 | 58.77 | 116.06 | 16.01 | 0.00 | 0.00 | 0.00 |
August | 96.17 | 31.26 | 64.91 | 151.89 | 19.01 | 0.00 | 0.00 | 0.00 |
September | 132.99 | 74.16 | 58.83 | 194.54 | 33.24 | 0.00 | 0.00 | 0.00 |
October | 181.94 | 134.00 | 47.94 | 239.99 | 55.78 | 0.00 | 0.00 | 0.00 |
November | 202.65 | 155.53 | 47.12 | 249.07 | 75.71 | 0.00 | 0.00 | 0.00 |
December | 216.14 | 178.29 | 37.85 | 260.68 | 93.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.33 | 86.29 | 54.04 | 183.95 | 53.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.21 | 7.79 | 37.85 | 96.47 | 16.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.14 | 178.29 | 66.05 | 260.68 | 93.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 196.65 | 81.14 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 197.04 | 74.29 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 148.13 | 61.54 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 119.58 | 44.24 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.34 | 32.25 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.51 | 20.94 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 97.00 | 13.41 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.64 | 15.88 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.77 | 27.78 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 198.84 | 47.83 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 205.01 | 67.25 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 215.15 | 82.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 151.97 | 47.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.34 | 13.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 215.15 | 82.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 196.65 | 81.14 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 197.04 | 74.29 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 148.13 | 61.54 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 119.58 | 44.24 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.34 | 32.25 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.51 | 20.94 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 97.00 | 13.41 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.64 | 15.88 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.77 | 27.78 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 198.84 | 47.83 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 205.01 | 67.25 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 215.15 | 82.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 151.97 | 47.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.34 | 13.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 215.15 | 82.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 199.21 | 155.01 | 44.20 | 236.82 | 96.50 | 0.00 | 0.00 | 0.00 |
February | 194.95 | 142.41 | 52.55 | 237.25 | 88.35 | 0.00 | 0.00 | 0.00 |
March | 143.66 | 86.85 | 56.81 | 178.44 | 73.22 | 0.00 | 0.00 | 0.00 |
April | 112.04 | 45.99 | 66.05 | 143.98 | 52.78 | 0.00 | 0.00 | 0.00 |
May | 74.72 | 16.44 | 58.28 | 96.64 | 38.54 | 0.00 | 0.00 | 0.00 |
June | 63.21 | 7.79 | 55.42 | 96.48 | 25.11 | 0.00 | 0.00 | 0.00 |
July | 69.94 | 11.17 | 58.77 | 116.26 | 16.12 | 0.00 | 0.00 | 0.00 |
August | 96.17 | 31.26 | 64.91 | 152.02 | 19.05 | 0.00 | 0.00 | 0.00 |
September | 132.99 | 74.16 | 58.83 | 194.44 | 33.23 | 0.00 | 0.00 | 0.00 |
October | 181.94 | 134.00 | 47.94 | 239.14 | 57.06 | 0.00 | 0.00 | 0.00 |
November | 202.65 | 155.53 | 47.12 | 246.74 | 80.10 | 0.00 | 0.00 | 0.00 |
December | 216.14 | 178.29 | 37.85 | 258.94 | 97.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.33 | 86.29 | 54.04 | 182.79 | 56.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.21 | 7.79 | 37.85 | 96.48 | 16.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.14 | 178.29 | 66.05 | 258.94 | 97.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 197.12 | 79.26 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 197.42 | 72.73 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 148.47 | 60.68 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 119.72 | 44.57 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.17 | 33.36 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.03 | 22.58 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.27 | 15.20 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.20 | 17.74 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.52 | 29.67 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 198.90 | 48.64 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 205.60 | 66.19 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 215.52 | 80.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 151.99 | 47.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.03 | 15.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 215.52 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 197.12 | 79.26 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 197.42 | 72.73 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 148.47 | 60.68 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 119.72 | 44.57 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.17 | 33.36 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.03 | 22.58 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.27 | 15.20 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.20 | 17.74 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.52 | 29.67 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 198.90 | 48.64 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 205.60 | 66.19 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 215.52 | 80.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 151.99 | 47.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.03 | 15.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 215.52 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.12 | 154.16 | 43.96 | 236.09 | 93.78 | 0.00 | 0.00 | 0.00 |
February | 193.89 | 141.63 | 52.26 | 236.41 | 86.04 | 0.00 | 0.00 | 0.00 |
March | 142.88 | 86.38 | 56.50 | 177.87 | 71.82 | 0.00 | 0.00 | 0.00 |
April | 111.42 | 45.74 | 65.69 | 143.37 | 52.87 | 0.00 | 0.00 | 0.00 |
May | 74.31 | 16.35 | 57.96 | 95.92 | 39.63 | 0.00 | 0.00 | 0.00 |
June | 62.86 | 7.75 | 55.11 | 95.40 | 26.88 | 0.00 | 0.00 | 0.00 |
July | 69.56 | 11.11 | 58.45 | 114.77 | 18.13 | 0.00 | 0.00 | 0.00 |
August | 95.65 | 31.09 | 64.56 | 150.68 | 21.12 | 0.00 | 0.00 | 0.00 |
September | 132.26 | 73.75 | 58.51 | 193.08 | 35.27 | 0.00 | 0.00 | 0.00 |
October | 180.95 | 133.27 | 47.68 | 237.90 | 57.68 | 0.00 | 0.00 | 0.00 |
November | 201.54 | 154.68 | 46.86 | 246.09 | 78.41 | 0.00 | 0.00 | 0.00 |
December | 214.95 | 177.32 | 37.64 | 257.97 | 95.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.56 | 85.82 | 53.75 | 181.82 | 56.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.86 | 7.75 | 37.64 | 95.40 | 18.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.95 | 177.32 | 65.69 | 257.97 | 95.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 197.44 | 78.29 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 197.70 | 71.88 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 148.80 | 59.88 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 119.91 | 44.14 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.22 | 33.24 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.01 | 22.64 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.22 | 15.34 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.17 | 17.86 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.51 | 29.75 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 198.99 | 48.41 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 206.01 | 65.30 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 215.72 | 79.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.13 | 47.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.01 | 15.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 215.72 | 79.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 197.44 | 78.29 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 197.70 | 71.88 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 148.80 | 59.88 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 119.91 | 44.14 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.22 | 33.24 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.01 | 22.64 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.22 | 15.34 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.17 | 17.86 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.51 | 29.75 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 198.99 | 48.41 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 206.01 | 65.30 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 215.72 | 79.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.13 | 47.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.01 | 15.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 215.72 | 79.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.12 | 154.16 | 43.96 | 236.48 | 92.62 | 0.00 | 0.00 | 0.00 |
February | 193.89 | 141.63 | 52.26 | 236.74 | 85.04 | 0.00 | 0.00 | 0.00 |
March | 142.88 | 86.38 | 56.50 | 178.26 | 70.87 | 0.00 | 0.00 | 0.00 |
April | 111.42 | 45.74 | 65.69 | 143.60 | 52.36 | 0.00 | 0.00 | 0.00 |
May | 74.31 | 16.35 | 57.96 | 95.98 | 39.49 | 0.00 | 0.00 | 0.00 |
June | 62.86 | 7.75 | 55.11 | 95.37 | 26.96 | 0.00 | 0.00 | 0.00 |
July | 69.56 | 11.11 | 58.45 | 114.72 | 18.30 | 0.00 | 0.00 | 0.00 |
August | 95.65 | 31.09 | 64.56 | 150.63 | 21.27 | 0.00 | 0.00 | 0.00 |
September | 132.26 | 73.75 | 58.51 | 193.06 | 35.36 | 0.00 | 0.00 | 0.00 |
October | 180.95 | 133.27 | 47.68 | 238.01 | 57.42 | 0.00 | 0.00 | 0.00 |
November | 201.54 | 154.68 | 46.86 | 246.58 | 77.35 | 0.00 | 0.00 | 0.00 |
December | 214.95 | 177.32 | 37.64 | 258.22 | 94.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.56 | 85.82 | 53.75 | 182.00 | 55.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.86 | 7.75 | 37.64 | 95.37 | 18.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.95 | 177.32 | 65.69 | 258.22 | 94.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 197.81 | 77.46 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.04 | 71.12 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 149.28 | 58.94 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.28 | 43.47 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.43 | 32.83 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.14 | 22.35 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.33 | 15.09 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.26 | 17.61 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.60 | 29.48 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.18 | 47.99 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 206.52 | 64.33 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 215.96 | 79.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.39 | 46.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.14 | 15.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 215.96 | 79.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 197.81 | 77.46 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.04 | 71.12 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 149.28 | 58.94 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.28 | 43.47 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.43 | 32.83 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.14 | 22.35 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.33 | 15.09 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.26 | 17.61 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.60 | 29.48 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.18 | 47.99 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 206.52 | 64.33 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 215.96 | 79.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.39 | 46.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.14 | 15.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 215.96 | 79.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.12 | 154.16 | 43.96 | 236.91 | 91.64 | 0.00 | 0.00 | 0.00 |
February | 193.89 | 141.63 | 52.26 | 237.15 | 84.14 | 0.00 | 0.00 | 0.00 |
March | 142.88 | 86.38 | 56.50 | 178.83 | 69.76 | 0.00 | 0.00 | 0.00 |
April | 111.42 | 45.74 | 65.69 | 144.03 | 51.57 | 0.00 | 0.00 | 0.00 |
May | 74.31 | 16.35 | 57.96 | 96.24 | 39.00 | 0.00 | 0.00 | 0.00 |
June | 62.86 | 7.75 | 55.11 | 95.53 | 26.62 | 0.00 | 0.00 | 0.00 |
July | 69.56 | 11.11 | 58.45 | 114.85 | 18.01 | 0.00 | 0.00 | 0.00 |
August | 95.65 | 31.09 | 64.56 | 150.75 | 20.97 | 0.00 | 0.00 | 0.00 |
September | 132.26 | 73.75 | 58.51 | 193.17 | 35.04 | 0.00 | 0.00 | 0.00 |
October | 180.95 | 133.27 | 47.68 | 238.24 | 56.91 | 0.00 | 0.00 | 0.00 |
November | 201.54 | 154.68 | 46.86 | 247.19 | 76.21 | 0.00 | 0.00 | 0.00 |
December | 214.95 | 177.32 | 37.64 | 258.50 | 93.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.56 | 85.82 | 53.75 | 182.30 | 55.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.86 | 7.75 | 37.64 | 95.53 | 18.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.95 | 177.32 | 65.69 | 258.50 | 93.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.80 | 75.64 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.98 | 69.35 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.30 | 56.93 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.98 | 41.96 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.76 | 31.72 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.12 | 21.43 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.19 | 14.32 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.13 | 16.76 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.64 | 28.65 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.53 | 46.93 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 207.48 | 62.48 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.71 | 77.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.87 | 45.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.12 | 14.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.71 | 77.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.80 | 75.64 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.98 | 69.35 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.30 | 56.93 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.98 | 41.96 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.76 | 31.72 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.12 | 21.43 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.19 | 14.32 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.13 | 16.76 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.64 | 28.65 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.53 | 46.93 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 207.48 | 62.48 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.71 | 77.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.87 | 45.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.12 | 14.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.71 | 77.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.80 | 75.64 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.98 | 69.35 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.30 | 56.93 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.98 | 41.96 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.76 | 31.72 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.12 | 21.43 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.19 | 14.32 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.13 | 16.76 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.64 | 28.65 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.53 | 46.93 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 207.48 | 62.48 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.71 | 77.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.87 | 45.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.12 | 14.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.71 | 77.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.80 | 75.64 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.98 | 69.35 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.30 | 56.93 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.98 | 41.96 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.76 | 31.72 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.12 | 21.43 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.19 | 14.32 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.13 | 16.76 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.64 | 28.65 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.53 | 46.93 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 207.48 | 62.48 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.71 | 77.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.87 | 45.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.12 | 14.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.71 | 77.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.12 | 154.16 | 43.96 | 238.05 | 89.52 | 0.00 | 0.00 | 0.00 |
February | 193.89 | 141.63 | 52.26 | 238.22 | 82.08 | 0.00 | 0.00 | 0.00 |
March | 142.88 | 86.38 | 56.50 | 180.01 | 67.41 | 0.00 | 0.00 | 0.00 |
April | 111.42 | 45.74 | 65.69 | 144.84 | 49.80 | 0.00 | 0.00 | 0.00 |
May | 74.31 | 16.35 | 57.96 | 96.62 | 37.69 | 0.00 | 0.00 | 0.00 |
June | 62.86 | 7.75 | 55.11 | 95.52 | 25.53 | 0.00 | 0.00 | 0.00 |
July | 69.56 | 11.11 | 58.45 | 114.69 | 17.09 | 0.00 | 0.00 | 0.00 |
August | 95.65 | 31.09 | 64.56 | 150.59 | 19.97 | 0.00 | 0.00 | 0.00 |
September | 132.26 | 73.75 | 58.51 | 193.20 | 34.07 | 0.00 | 0.00 | 0.00 |
October | 180.95 | 133.27 | 47.68 | 238.62 | 55.68 | 0.00 | 0.00 | 0.00 |
November | 201.54 | 154.68 | 46.86 | 248.29 | 74.04 | 0.00 | 0.00 | 0.00 |
December | 214.95 | 177.32 | 37.64 | 259.35 | 91.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.56 | 85.82 | 53.75 | 182.85 | 53.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.86 | 7.75 | 37.64 | 95.52 | 17.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.95 | 177.32 | 65.69 | 259.35 | 91.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.12 | 154.16 | 43.96 | 238.05 | 89.52 | 0.00 | 0.00 | 0.00 |
February | 193.89 | 141.63 | 52.26 | 238.22 | 82.08 | 0.00 | 0.00 | 0.00 |
March | 142.88 | 86.38 | 56.50 | 180.01 | 67.41 | 0.00 | 0.00 | 0.00 |
April | 111.42 | 45.74 | 65.69 | 144.84 | 49.80 | 0.00 | 0.00 | 0.00 |
May | 74.31 | 16.35 | 57.96 | 96.62 | 37.69 | 0.00 | 0.00 | 0.00 |
June | 62.86 | 7.75 | 55.11 | 95.52 | 25.53 | 0.00 | 0.00 | 0.00 |
July | 69.56 | 11.11 | 58.45 | 114.69 | 17.09 | 0.00 | 0.00 | 0.00 |
August | 95.65 | 31.09 | 64.56 | 150.59 | 19.97 | 0.00 | 0.00 | 0.00 |
September | 132.26 | 73.75 | 58.51 | 193.20 | 34.07 | 0.00 | 0.00 | 0.00 |
October | 180.95 | 133.27 | 47.68 | 238.62 | 55.68 | 0.00 | 0.00 | 0.00 |
November | 201.54 | 154.68 | 46.86 | 248.29 | 74.04 | 0.00 | 0.00 | 0.00 |
December | 214.95 | 177.32 | 37.64 | 259.35 | 91.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.56 | 85.82 | 53.75 | 182.85 | 53.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.86 | 7.75 | 37.64 | 95.52 | 17.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.95 | 177.32 | 65.69 | 259.35 | 91.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.51 | 75.67 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.72 | 69.35 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.17 | 56.78 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.92 | 41.72 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.77 | 31.51 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.31 | 21.17 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.39 | 14.02 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.22 | 16.45 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.58 | 28.38 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.38 | 46.75 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 207.36 | 62.26 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.42 | 77.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.80 | 45.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.31 | 14.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.42 | 77.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.51 | 75.67 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.72 | 69.35 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.17 | 56.78 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 120.92 | 41.72 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.77 | 31.51 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.31 | 21.17 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.39 | 14.02 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.22 | 16.45 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.58 | 28.38 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.38 | 46.75 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 207.36 | 62.26 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.42 | 77.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.80 | 45.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.31 | 14.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.42 | 77.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.12 | 154.16 | 43.96 | 237.76 | 89.52 | 0.00 | 0.00 | 0.00 |
February | 193.89 | 141.63 | 52.26 | 237.97 | 82.04 | 0.00 | 0.00 | 0.00 |
March | 142.88 | 86.38 | 56.50 | 179.90 | 67.21 | 0.00 | 0.00 | 0.00 |
April | 111.42 | 45.74 | 65.69 | 144.80 | 49.50 | 0.00 | 0.00 | 0.00 |
May | 74.31 | 16.35 | 57.96 | 96.65 | 37.44 | 0.00 | 0.00 | 0.00 |
June | 62.86 | 7.75 | 55.11 | 95.74 | 25.23 | 0.00 | 0.00 | 0.00 |
July | 69.56 | 11.11 | 58.45 | 114.93 | 16.74 | 0.00 | 0.00 | 0.00 |
August | 95.65 | 31.09 | 64.56 | 150.71 | 19.61 | 0.00 | 0.00 | 0.00 |
September | 132.26 | 73.75 | 58.51 | 193.16 | 33.75 | 0.00 | 0.00 | 0.00 |
October | 180.95 | 133.27 | 47.68 | 238.49 | 55.45 | 0.00 | 0.00 | 0.00 |
November | 201.54 | 154.68 | 46.86 | 248.19 | 73.76 | 0.00 | 0.00 | 0.00 |
December | 214.95 | 177.32 | 37.64 | 259.06 | 91.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.56 | 85.82 | 53.75 | 182.80 | 53.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.86 | 7.75 | 37.64 | 95.74 | 16.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.95 | 177.32 | 65.69 | 259.06 | 91.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.67 | 75.34 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.88 | 68.99 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.40 | 56.36 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 121.13 | 41.38 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.90 | 31.32 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.38 | 21.07 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.45 | 13.95 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.27 | 16.37 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.63 | 28.28 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.48 | 46.56 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 207.58 | 61.86 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.53 | 77.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.93 | 44.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.38 | 13.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.53 | 77.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 198.67 | 75.34 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 198.88 | 68.99 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.40 | 56.36 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 121.13 | 41.38 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 80.90 | 31.32 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.38 | 21.07 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.45 | 13.95 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.27 | 16.37 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.63 | 28.28 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.48 | 46.56 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 207.58 | 61.86 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.53 | 77.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 152.93 | 44.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.38 | 13.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.53 | 77.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.12 | 154.16 | 43.96 | 237.95 | 89.13 | 0.00 | 0.00 | 0.00 |
February | 193.89 | 141.63 | 52.26 | 238.17 | 81.63 | 0.00 | 0.00 | 0.00 |
March | 142.88 | 86.38 | 56.50 | 180.17 | 66.71 | 0.00 | 0.00 | 0.00 |
April | 111.42 | 45.74 | 65.69 | 145.06 | 49.11 | 0.00 | 0.00 | 0.00 |
May | 74.31 | 16.35 | 57.96 | 96.80 | 37.22 | 0.00 | 0.00 | 0.00 |
June | 62.86 | 7.75 | 55.11 | 95.82 | 25.11 | 0.00 | 0.00 | 0.00 |
July | 69.56 | 11.11 | 58.45 | 115.00 | 16.65 | 0.00 | 0.00 | 0.00 |
August | 95.65 | 31.09 | 64.56 | 150.77 | 19.51 | 0.00 | 0.00 | 0.00 |
September | 132.26 | 73.75 | 58.51 | 193.22 | 33.63 | 0.00 | 0.00 | 0.00 |
October | 180.95 | 133.27 | 47.68 | 238.61 | 55.23 | 0.00 | 0.00 | 0.00 |
November | 201.54 | 154.68 | 46.86 | 248.45 | 73.29 | 0.00 | 0.00 | 0.00 |
December | 214.95 | 177.32 | 37.64 | 259.19 | 91.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.56 | 85.82 | 53.75 | 182.95 | 53.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.86 | 7.75 | 37.64 | 95.82 | 16.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.95 | 177.32 | 65.69 | 259.19 | 91.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 199.10 | 74.28 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 199.35 | 67.88 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.95 | 55.20 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 121.61 | 40.51 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 81.22 | 30.78 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.48 | 20.85 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.47 | 13.85 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.29 | 16.27 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.69 | 28.09 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.72 | 46.08 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 208.05 | 60.94 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.85 | 76.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 153.22 | 44.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.48 | 13.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.85 | 76.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 199.10 | 74.28 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 199.35 | 67.88 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 150.95 | 55.20 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 121.61 | 40.51 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 81.22 | 30.78 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.48 | 20.85 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.47 | 13.85 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 126.29 | 16.27 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.69 | 28.09 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 199.72 | 46.08 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 208.05 | 60.94 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 216.85 | 76.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 153.22 | 44.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.48 | 13.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 216.85 | 76.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.12 | 154.16 | 43.96 | 238.47 | 87.88 | 0.00 | 0.00 | 0.00 |
February | 193.89 | 141.63 | 52.26 | 238.72 | 80.30 | 0.00 | 0.00 | 0.00 |
March | 142.88 | 86.38 | 56.50 | 180.83 | 65.34 | 0.00 | 0.00 | 0.00 |
April | 111.42 | 45.74 | 65.69 | 145.62 | 48.08 | 0.00 | 0.00 | 0.00 |
May | 74.31 | 16.35 | 57.96 | 97.18 | 36.59 | 0.00 | 0.00 | 0.00 |
June | 62.86 | 7.75 | 55.11 | 95.94 | 24.85 | 0.00 | 0.00 | 0.00 |
July | 69.56 | 11.11 | 58.45 | 115.03 | 16.54 | 0.00 | 0.00 | 0.00 |
August | 95.65 | 31.09 | 64.56 | 150.80 | 19.39 | 0.00 | 0.00 | 0.00 |
September | 132.26 | 73.75 | 58.51 | 193.29 | 33.41 | 0.00 | 0.00 | 0.00 |
October | 180.95 | 133.27 | 47.68 | 238.90 | 54.67 | 0.00 | 0.00 | 0.00 |
November | 201.54 | 154.68 | 46.86 | 249.02 | 72.20 | 0.00 | 0.00 | 0.00 |
December | 214.95 | 177.32 | 37.64 | 259.57 | 90.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.56 | 85.82 | 53.75 | 183.30 | 52.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.86 | 7.75 | 37.64 | 95.94 | 16.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.95 | 177.32 | 65.69 | 259.57 | 90.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 200.41 | 70.38 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 200.67 | 63.80 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 152.19 | 51.46 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 122.38 | 37.78 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 81.78 | 28.90 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.33 | 20.02 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.01 | 13.63 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 125.87 | 16.03 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.53 | 27.48 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 200.13 | 44.45 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 209.06 | 58.15 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 217.87 | 72.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 153.75 | 41.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.33 | 13.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 217.87 | 72.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.71 | 128.95 | 36.76 | 200.41 | 70.38 | 0.00 | 0.00 | 0.00 |
February | 162.17 | 118.46 | 43.71 | 200.67 | 63.80 | 0.00 | 0.00 | 0.00 |
March | 119.50 | 72.25 | 47.26 | 152.19 | 51.46 | 0.00 | 0.00 | 0.00 |
April | 93.20 | 38.26 | 54.94 | 122.38 | 37.78 | 0.00 | 0.00 | 0.00 |
May | 62.15 | 13.67 | 48.48 | 81.78 | 28.90 | 0.00 | 0.00 | 0.00 |
June | 52.58 | 6.48 | 46.10 | 80.33 | 20.02 | 0.00 | 0.00 | 0.00 |
July | 58.18 | 9.29 | 48.89 | 96.01 | 13.63 | 0.00 | 0.00 | 0.00 |
August | 80.00 | 26.00 | 54.00 | 125.87 | 16.03 | 0.00 | 0.00 | 0.00 |
September | 110.62 | 61.69 | 48.94 | 161.53 | 27.48 | 0.00 | 0.00 | 0.00 |
October | 151.35 | 111.47 | 39.88 | 200.13 | 44.45 | 0.00 | 0.00 | 0.00 |
November | 168.57 | 129.38 | 39.19 | 209.06 | 58.15 | 0.00 | 0.00 | 0.00 |
December | 179.79 | 148.31 | 31.48 | 217.87 | 72.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 116.73 | 71.78 | 44.95 | 153.75 | 41.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.58 | 6.48 | 31.48 | 80.33 | 13.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 179.79 | 148.31 | 54.94 | 217.87 | 72.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.12 | 154.16 | 43.96 | 240.03 | 83.26 | 0.00 | 0.00 | 0.00 |
February | 193.89 | 141.63 | 52.26 | 240.31 | 75.48 | 0.00 | 0.00 | 0.00 |
March | 142.88 | 86.38 | 56.50 | 182.32 | 60.93 | 0.00 | 0.00 | 0.00 |
April | 111.42 | 45.74 | 65.69 | 146.54 | 44.87 | 0.00 | 0.00 | 0.00 |
May | 74.31 | 16.35 | 57.96 | 97.86 | 34.37 | 0.00 | 0.00 | 0.00 |
June | 62.86 | 7.75 | 55.11 | 95.77 | 23.87 | 0.00 | 0.00 | 0.00 |
July | 69.56 | 11.11 | 58.45 | 114.47 | 16.28 | 0.00 | 0.00 | 0.00 |
August | 95.65 | 31.09 | 64.56 | 150.29 | 19.11 | 0.00 | 0.00 | 0.00 |
September | 132.26 | 73.75 | 58.51 | 193.10 | 32.68 | 0.00 | 0.00 | 0.00 |
October | 180.95 | 133.27 | 47.68 | 239.38 | 52.74 | 0.00 | 0.00 | 0.00 |
November | 201.54 | 154.68 | 46.86 | 250.22 | 68.90 | 0.00 | 0.00 | 0.00 |
December | 214.95 | 177.32 | 37.64 | 260.80 | 86.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.56 | 85.82 | 53.75 | 183.94 | 49.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.86 | 7.75 | 37.64 | 95.77 | 16.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.95 | 177.32 | 65.69 | 260.80 | 86.18 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.531928E+09 | 0.205070E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.481213E+09 | 0.169297E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402553E+09 | 0.153761E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313361E+09 | 0.109880E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216923E+09 | 84179672.64 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208650E+09 | 53766859.96 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.259359E+09 | 35685242.14 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338942E+09 | 42444085.10 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.419601E+09 | 72002360.17 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534550E+09 | 0.125201E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.536528E+09 | 0.164660E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.580218E+09 | 0.209483E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.482383E+10 | 0.142543E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208650E+09 | 35685242.14 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.580218E+09 | 0.209483E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.531928E+09 | 0.205070E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.481213E+09 | 0.169297E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402553E+09 | 0.153761E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313361E+09 | 0.109880E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216923E+09 | 84179672.64 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208650E+09 | 53766859.96 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.259359E+09 | 35685242.14 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338942E+09 | 42444085.10 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.419601E+09 | 72002360.17 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534550E+09 | 0.125201E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.536528E+09 | 0.164660E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.580218E+09 | 0.209483E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.482383E+10 | 0.142543E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208650E+09 | 35685242.14 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.580218E+09 | 0.209483E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.531928E+09 | 0.205070E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.481213E+09 | 0.169297E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402553E+09 | 0.153761E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313361E+09 | 0.109880E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216923E+09 | 84179672.64 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208650E+09 | 53766859.96 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.259359E+09 | 35685242.14 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338942E+09 | 42444085.10 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.419601E+09 | 72002360.17 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534550E+09 | 0.125201E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.536528E+09 | 0.164660E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.580218E+09 | 0.209483E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.482383E+10 | 0.142543E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208650E+09 | 35685242.14 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.580218E+09 | 0.209483E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.531928E+09 | 0.205070E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.481213E+09 | 0.169297E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402553E+09 | 0.153761E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313361E+09 | 0.109880E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216923E+09 | 84179672.64 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208650E+09 | 53766859.96 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.259359E+09 | 35685242.14 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338942E+09 | 42444085.10 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.419601E+09 | 72002360.17 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534550E+09 | 0.125201E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.536528E+09 | 0.164660E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.580218E+09 | 0.209483E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.482383E+10 | 0.142543E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208650E+09 | 35685242.14 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.580218E+09 | 0.209483E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.533561E+09 | 0.415184E+09 | 0.118377E+09 | 0.640437E+09 | 0.244052E+09 |
February | 0.471630E+09 | 0.344510E+09 | 0.127120E+09 | 0.579280E+09 | 0.201486E+09 |
March | 0.384780E+09 | 0.232623E+09 | 0.152157E+09 | 0.484761E+09 | 0.183094E+09 |
April | 0.290399E+09 | 0.119204E+09 | 0.171196E+09 | 0.377213E+09 | 0.131142E+09 |
May | 0.200128E+09 | 44024492.68 | 0.156104E+09 | 0.260909E+09 | 0.100627E+09 |
June | 0.163830E+09 | 20190330.50 | 0.143640E+09 | 0.250055E+09 | 64459385.60 |
July | 0.187329E+09 | 29914782.28 | 0.157415E+09 | 0.310855E+09 | 42890614.18 |
August | 0.257592E+09 | 83730544.59 | 0.173861E+09 | 0.406820E+09 | 50916859.11 |
September | 0.344704E+09 | 0.192217E+09 | 0.152487E+09 | 0.504253E+09 | 86156783.13 |
October | 0.487317E+09 | 0.358906E+09 | 0.128410E+09 | 0.642784E+09 | 0.149413E+09 |
November | 0.525269E+09 | 0.403143E+09 | 0.122127E+09 | 0.645583E+09 | 0.196241E+09 |
December | 0.578898E+09 | 0.477530E+09 | 0.101368E+09 | 0.698193E+09 | 0.249432E+09 |
Annual Sum or Average | 0.442544E+10 | 0.272118E+10 | 0.170426E+10 | 0.580114E+10 | 0.169991E+10 |
Minimum of Months | 0.163830E+09 | 20190330.50 | 0.101368E+09 | 0.250055E+09 | 42890614.18 |
Maximum of Months | 0.578898E+09 | 0.477530E+09 | 0.173861E+09 | 0.698193E+09 | 0.249432E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.533561E+09 | 0.415184E+09 | 0.118377E+09 | 0.640437E+09 | 0.244052E+09 |
February | 0.471630E+09 | 0.344510E+09 | 0.127120E+09 | 0.579280E+09 | 0.201486E+09 |
March | 0.384780E+09 | 0.232623E+09 | 0.152157E+09 | 0.484761E+09 | 0.183094E+09 |
April | 0.290399E+09 | 0.119204E+09 | 0.171196E+09 | 0.377213E+09 | 0.131142E+09 |
May | 0.200128E+09 | 44024492.68 | 0.156104E+09 | 0.260909E+09 | 0.100627E+09 |
June | 0.163830E+09 | 20190330.50 | 0.143640E+09 | 0.250055E+09 | 64459385.60 |
July | 0.187329E+09 | 29914782.28 | 0.157415E+09 | 0.310855E+09 | 42890614.18 |
August | 0.257592E+09 | 83730544.59 | 0.173861E+09 | 0.406820E+09 | 50916859.11 |
September | 0.344704E+09 | 0.192217E+09 | 0.152487E+09 | 0.504253E+09 | 86156783.13 |
October | 0.487317E+09 | 0.358906E+09 | 0.128410E+09 | 0.642784E+09 | 0.149413E+09 |
November | 0.525269E+09 | 0.403143E+09 | 0.122127E+09 | 0.645583E+09 | 0.196241E+09 |
December | 0.578898E+09 | 0.477530E+09 | 0.101368E+09 | 0.698193E+09 | 0.249432E+09 |
Annual Sum or Average | 0.442544E+10 | 0.272118E+10 | 0.170426E+10 | 0.580114E+10 | 0.169991E+10 |
Minimum of Months | 0.163830E+09 | 20190330.50 | 0.101368E+09 | 0.250055E+09 | 42890614.18 |
Maximum of Months | 0.578898E+09 | 0.477530E+09 | 0.173861E+09 | 0.698193E+09 | 0.249432E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.526706E+09 | 0.217318E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.476678E+09 | 0.179719E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.396753E+09 | 0.164830E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.309941E+09 | 0.114681E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.215171E+09 | 86367588.68 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208676E+09 | 54284610.22 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.259816E+09 | 35918765.86 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.339200E+09 | 42522667.63 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.419308E+09 | 71993626.17 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.532575E+09 | 0.128116E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.531378E+09 | 0.174316E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.576247E+09 | 0.220504E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.479245E+10 | 0.149057E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208676E+09 | 35918765.86 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.576247E+09 | 0.220504E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.526706E+09 | 0.217318E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.476678E+09 | 0.179719E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.396753E+09 | 0.164830E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.309941E+09 | 0.114681E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.215171E+09 | 86367588.68 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208676E+09 | 54284610.22 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.259816E+09 | 35918765.86 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.339200E+09 | 42522667.63 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.419308E+09 | 71993626.17 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.532575E+09 | 0.128116E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.531378E+09 | 0.174316E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.576247E+09 | 0.220504E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.479245E+10 | 0.149057E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208676E+09 | 35918765.86 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.576247E+09 | 0.220504E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.533561E+09 | 0.415184E+09 | 0.118377E+09 | 0.634309E+09 | 0.258460E+09 |
February | 0.471630E+09 | 0.344510E+09 | 0.127120E+09 | 0.573957E+09 | 0.213745E+09 |
March | 0.384780E+09 | 0.232623E+09 | 0.152157E+09 | 0.477941E+09 | 0.196124E+09 |
April | 0.290399E+09 | 0.119204E+09 | 0.171196E+09 | 0.373201E+09 | 0.136805E+09 |
May | 0.200128E+09 | 44024492.68 | 0.156104E+09 | 0.258849E+09 | 0.103218E+09 |
June | 0.163830E+09 | 20190330.50 | 0.143640E+09 | 0.250076E+09 | 65084039.81 |
July | 0.187329E+09 | 29914782.28 | 0.157415E+09 | 0.311403E+09 | 43179202.31 |
August | 0.257592E+09 | 83730544.59 | 0.173861E+09 | 0.407164E+09 | 51011806.28 |
September | 0.344704E+09 | 0.192217E+09 | 0.152487E+09 | 0.503977E+09 | 86144482.63 |
October | 0.487317E+09 | 0.358906E+09 | 0.128410E+09 | 0.640519E+09 | 0.152836E+09 |
November | 0.525269E+09 | 0.403143E+09 | 0.122127E+09 | 0.639556E+09 | 0.207612E+09 |
December | 0.578898E+09 | 0.477530E+09 | 0.101368E+09 | 0.693542E+09 | 0.262396E+09 |
Annual Sum or Average | 0.442544E+10 | 0.272118E+10 | 0.170426E+10 | 0.576449E+10 | 0.177661E+10 |
Minimum of Months | 0.163830E+09 | 20190330.50 | 0.101368E+09 | 0.250076E+09 | 43179202.31 |
Maximum of Months | 0.578898E+09 | 0.477530E+09 | 0.173861E+09 | 0.693542E+09 | 0.262396E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.527955E+09 | 0.212302E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.477603E+09 | 0.175942E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.397659E+09 | 0.162523E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.310315E+09 | 0.115527E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.214723E+09 | 89355571.06 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.207433E+09 | 58514989.59 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.257837E+09 | 40709790.23 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338016E+09 | 47507003.80 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418671E+09 | 76905452.10 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.532729E+09 | 0.130271E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.532908E+09 | 0.171576E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.577237E+09 | 0.215799E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.479309E+10 | 0.149693E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.207433E+09 | 40709790.23 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.577237E+09 | 0.215799E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.527955E+09 | 0.212302E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.477603E+09 | 0.175942E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.397659E+09 | 0.162523E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.310315E+09 | 0.115527E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.214723E+09 | 89355571.06 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.207433E+09 | 58514989.59 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.257837E+09 | 40709790.23 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338016E+09 | 47507003.80 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418671E+09 | 76905452.10 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.532729E+09 | 0.130271E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.532908E+09 | 0.171576E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.577237E+09 | 0.215799E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.479309E+10 | 0.149693E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.207433E+09 | 40709790.23 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.577237E+09 | 0.215799E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530645E+09 | 0.412915E+09 | 0.117730E+09 | 0.632334E+09 | 0.251170E+09 |
February | 0.469053E+09 | 0.342627E+09 | 0.126426E+09 | 0.571929E+09 | 0.208154E+09 |
March | 0.382677E+09 | 0.231352E+09 | 0.151325E+09 | 0.476404E+09 | 0.192350E+09 |
April | 0.288812E+09 | 0.118552E+09 | 0.170260E+09 | 0.371607E+09 | 0.137034E+09 |
May | 0.199034E+09 | 43783921.68 | 0.155250E+09 | 0.256910E+09 | 0.106135E+09 |
June | 0.162935E+09 | 20080000.82 | 0.142855E+09 | 0.247269E+09 | 69680604.33 |
July | 0.186306E+09 | 29751313.53 | 0.156554E+09 | 0.307408E+09 | 48566926.48 |
August | 0.256184E+09 | 83273000.63 | 0.172911E+09 | 0.403569E+09 | 56576715.50 |
September | 0.342821E+09 | 0.191167E+09 | 0.151654E+09 | 0.500470E+09 | 91407671.56 |
October | 0.484654E+09 | 0.356945E+09 | 0.127709E+09 | 0.637203E+09 | 0.154500E+09 |
November | 0.522399E+09 | 0.400940E+09 | 0.121459E+09 | 0.637871E+09 | 0.203249E+09 |
December | 0.575735E+09 | 0.474921E+09 | 0.100814E+09 | 0.690938E+09 | 0.255445E+09 |
Annual Sum or Average | 0.440126E+10 | 0.270631E+10 | 0.169495E+10 | 0.573391E+10 | 0.177427E+10 |
Minimum of Months | 0.162935E+09 | 20080000.82 | 0.100814E+09 | 0.247269E+09 | 48566926.48 |
Maximum of Months | 0.575735E+09 | 0.474921E+09 | 0.172911E+09 | 0.690938E+09 | 0.255445E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.528827E+09 | 0.209689E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.478272E+09 | 0.173894E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.398534E+09 | 0.160382E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.310819E+09 | 0.114401E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.214868E+09 | 89037325.14 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.207379E+09 | 58690021.65 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.257713E+09 | 41080037.80 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.337923E+09 | 47848581.62 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418626E+09 | 77108477.22 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.532967E+09 | 0.129673E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.533975E+09 | 0.169251E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.577795E+09 | 0.213623E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.479770E+10 | 0.148468E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.207379E+09 | 41080037.80 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.577795E+09 | 0.213623E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.528827E+09 | 0.209689E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.478272E+09 | 0.173894E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.398534E+09 | 0.160382E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.310819E+09 | 0.114401E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.214868E+09 | 89037325.14 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.207379E+09 | 58690021.65 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.257713E+09 | 41080037.80 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.337923E+09 | 47848581.62 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418626E+09 | 77108477.22 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.532967E+09 | 0.129673E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.533975E+09 | 0.169251E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.577795E+09 | 0.213623E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.479770E+10 | 0.148468E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.207379E+09 | 41080037.80 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.577795E+09 | 0.213623E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530645E+09 | 0.412915E+09 | 0.117730E+09 | 0.633376E+09 | 0.248077E+09 |
February | 0.469053E+09 | 0.342627E+09 | 0.126426E+09 | 0.572729E+09 | 0.205732E+09 |
March | 0.382677E+09 | 0.231352E+09 | 0.151325E+09 | 0.477446E+09 | 0.189820E+09 |
April | 0.288812E+09 | 0.118552E+09 | 0.170260E+09 | 0.372208E+09 | 0.135705E+09 |
May | 0.199034E+09 | 43783921.68 | 0.155250E+09 | 0.257085E+09 | 0.105759E+09 |
June | 0.162935E+09 | 20080000.82 | 0.142855E+09 | 0.247205E+09 | 69888572.14 |
July | 0.186306E+09 | 29751313.53 | 0.156554E+09 | 0.307260E+09 | 49005042.59 |
August | 0.256184E+09 | 83273000.63 | 0.172911E+09 | 0.403456E+09 | 56980689.90 |
September | 0.342821E+09 | 0.191167E+09 | 0.151654E+09 | 0.500415E+09 | 91647627.35 |
October | 0.484654E+09 | 0.356945E+09 | 0.127709E+09 | 0.637486E+09 | 0.153792E+09 |
November | 0.522399E+09 | 0.400940E+09 | 0.121459E+09 | 0.639140E+09 | 0.200499E+09 |
December | 0.575735E+09 | 0.474921E+09 | 0.100814E+09 | 0.691610E+09 | 0.252868E+09 |
Annual Sum or Average | 0.440126E+10 | 0.270631E+10 | 0.169495E+10 | 0.573942E+10 | 0.175977E+10 |
Minimum of Months | 0.162935E+09 | 20080000.82 | 0.100814E+09 | 0.247205E+09 | 49005042.59 |
Maximum of Months | 0.575735E+09 | 0.474921E+09 | 0.172911E+09 | 0.691610E+09 | 0.252868E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.529802E+09 | 0.207458E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.479088E+09 | 0.172046E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.399832E+09 | 0.157868E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.311761E+09 | 0.112671E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.215430E+09 | 87941482.00 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.207712E+09 | 57933259.89 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.258004E+09 | 40417072.00 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338173E+09 | 47164285.75 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418858E+09 | 76407430.89 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.533480E+09 | 0.128526E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.535293E+09 | 0.166735E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.578415E+09 | 0.211885E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.480585E+10 | 0.146705E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.207712E+09 | 40417072.00 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.578415E+09 | 0.211885E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.529802E+09 | 0.207458E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.479088E+09 | 0.172046E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.399832E+09 | 0.157868E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.311761E+09 | 0.112671E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.215430E+09 | 87941482.00 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.207712E+09 | 57933259.89 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.258004E+09 | 40417072.00 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338173E+09 | 47164285.75 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418858E+09 | 76407430.89 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.533480E+09 | 0.128526E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.535293E+09 | 0.166735E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.578415E+09 | 0.211885E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.480585E+10 | 0.146705E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.207712E+09 | 40417072.00 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.578415E+09 | 0.211885E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530645E+09 | 0.412915E+09 | 0.117730E+09 | 0.634541E+09 | 0.245439E+09 |
February | 0.469053E+09 | 0.342627E+09 | 0.126426E+09 | 0.573704E+09 | 0.203547E+09 |
March | 0.382677E+09 | 0.231352E+09 | 0.151325E+09 | 0.478991E+09 | 0.186855E+09 |
April | 0.288812E+09 | 0.118552E+09 | 0.170260E+09 | 0.373332E+09 | 0.133668E+09 |
May | 0.199034E+09 | 43783921.68 | 0.155250E+09 | 0.257757E+09 | 0.104469E+09 |
June | 0.162935E+09 | 20080000.82 | 0.142855E+09 | 0.247604E+09 | 68999104.89 |
July | 0.186306E+09 | 29751313.53 | 0.156554E+09 | 0.307609E+09 | 48226484.11 |
August | 0.256184E+09 | 83273000.63 | 0.172911E+09 | 0.403757E+09 | 56177201.97 |
September | 0.342821E+09 | 0.191167E+09 | 0.151654E+09 | 0.500696E+09 | 90824223.07 |
October | 0.484654E+09 | 0.356945E+09 | 0.127709E+09 | 0.638100E+09 | 0.152441E+09 |
November | 0.522399E+09 | 0.400940E+09 | 0.121459E+09 | 0.640708E+09 | 0.197527E+09 |
December | 0.575735E+09 | 0.474921E+09 | 0.100814E+09 | 0.692355E+09 | 0.250812E+09 |
Annual Sum or Average | 0.440126E+10 | 0.270631E+10 | 0.169495E+10 | 0.574915E+10 | 0.173898E+10 |
Minimum of Months | 0.162935E+09 | 20080000.82 | 0.100814E+09 | 0.247604E+09 | 48226484.11 |
Maximum of Months | 0.575735E+09 | 0.474921E+09 | 0.172911E+09 | 0.692355E+09 | 0.250812E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.532465E+09 | 0.202587E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.481368E+09 | 0.167781E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402573E+09 | 0.152487E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313567E+09 | 0.108767E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216305E+09 | 84953096.68 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.207680E+09 | 55556551.35 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.257630E+09 | 38357384.55 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.337828E+09 | 44895551.43 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418973E+09 | 74273002.74 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534408E+09 | 0.125700E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.537783E+09 | 0.161951E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.580423E+09 | 0.207662E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.482100E+10 | 0.142497E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.207680E+09 | 38357384.55 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.580423E+09 | 0.207662E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.532465E+09 | 0.202587E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.481368E+09 | 0.167781E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402573E+09 | 0.152487E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313567E+09 | 0.108767E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216305E+09 | 84953096.68 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.207680E+09 | 55556551.35 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.257630E+09 | 38357384.55 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.337828E+09 | 44895551.43 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418973E+09 | 74273002.74 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534408E+09 | 0.125700E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.537783E+09 | 0.161951E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.580423E+09 | 0.207662E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.482100E+10 | 0.142497E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.207680E+09 | 38357384.55 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.580423E+09 | 0.207662E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.532465E+09 | 0.202587E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.481368E+09 | 0.167781E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402573E+09 | 0.152487E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313567E+09 | 0.108767E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216305E+09 | 84953096.68 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.207680E+09 | 55556551.35 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.257630E+09 | 38357384.55 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.337828E+09 | 44895551.43 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418973E+09 | 74273002.74 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534408E+09 | 0.125700E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.537783E+09 | 0.161951E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.580423E+09 | 0.207662E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.482100E+10 | 0.142497E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.207680E+09 | 38357384.55 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.580423E+09 | 0.207662E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.532465E+09 | 0.202587E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.481368E+09 | 0.167781E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402573E+09 | 0.152487E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313567E+09 | 0.108767E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216305E+09 | 84953096.68 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.207680E+09 | 55556551.35 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.257630E+09 | 38357384.55 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.337828E+09 | 44895551.43 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418973E+09 | 74273002.74 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534408E+09 | 0.125700E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.537783E+09 | 0.161951E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.580423E+09 | 0.207662E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.482100E+10 | 0.142497E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.207680E+09 | 38357384.55 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.580423E+09 | 0.207662E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530645E+09 | 0.412915E+09 | 0.117730E+09 | 0.637589E+09 | 0.239757E+09 |
February | 0.469053E+09 | 0.342627E+09 | 0.126426E+09 | 0.576309E+09 | 0.198573E+09 |
March | 0.382677E+09 | 0.231352E+09 | 0.151325E+09 | 0.482150E+09 | 0.180562E+09 |
April | 0.288812E+09 | 0.118552E+09 | 0.170260E+09 | 0.375414E+09 | 0.129083E+09 |
May | 0.199034E+09 | 43783921.68 | 0.155250E+09 | 0.258774E+09 | 0.100950E+09 |
June | 0.162935E+09 | 20080000.82 | 0.142855E+09 | 0.247584E+09 | 66181601.92 |
July | 0.186306E+09 | 29751313.53 | 0.156554E+09 | 0.307178E+09 | 45776326.02 |
August | 0.256184E+09 | 83273000.63 | 0.172911E+09 | 0.403331E+09 | 53492210.63 |
September | 0.342821E+09 | 0.191167E+09 | 0.151654E+09 | 0.500781E+09 | 88306766.14 |
October | 0.484654E+09 | 0.356945E+09 | 0.127709E+09 | 0.639125E+09 | 0.149130E+09 |
November | 0.522399E+09 | 0.400940E+09 | 0.121459E+09 | 0.643558E+09 | 0.191917E+09 |
December | 0.575735E+09 | 0.474921E+09 | 0.100814E+09 | 0.694638E+09 | 0.245881E+09 |
Annual Sum or Average | 0.440126E+10 | 0.270631E+10 | 0.169495E+10 | 0.576643E+10 | 0.168961E+10 |
Minimum of Months | 0.162935E+09 | 20080000.82 | 0.100814E+09 | 0.247584E+09 | 45776326.02 |
Maximum of Months | 0.575735E+09 | 0.474921E+09 | 0.172911E+09 | 0.694638E+09 | 0.245881E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530645E+09 | 0.412915E+09 | 0.117730E+09 | 0.637589E+09 | 0.239757E+09 |
February | 0.469053E+09 | 0.342627E+09 | 0.126426E+09 | 0.576309E+09 | 0.198573E+09 |
March | 0.382677E+09 | 0.231352E+09 | 0.151325E+09 | 0.482150E+09 | 0.180562E+09 |
April | 0.288812E+09 | 0.118552E+09 | 0.170260E+09 | 0.375414E+09 | 0.129083E+09 |
May | 0.199034E+09 | 43783921.68 | 0.155250E+09 | 0.258774E+09 | 0.100950E+09 |
June | 0.162935E+09 | 20080000.82 | 0.142855E+09 | 0.247584E+09 | 66181601.92 |
July | 0.186306E+09 | 29751313.53 | 0.156554E+09 | 0.307178E+09 | 45776326.02 |
August | 0.256184E+09 | 83273000.63 | 0.172911E+09 | 0.403331E+09 | 53492210.63 |
September | 0.342821E+09 | 0.191167E+09 | 0.151654E+09 | 0.500781E+09 | 88306766.14 |
October | 0.484654E+09 | 0.356945E+09 | 0.127709E+09 | 0.639125E+09 | 0.149130E+09 |
November | 0.522399E+09 | 0.400940E+09 | 0.121459E+09 | 0.643558E+09 | 0.191917E+09 |
December | 0.575735E+09 | 0.474921E+09 | 0.100814E+09 | 0.694638E+09 | 0.245881E+09 |
Annual Sum or Average | 0.440126E+10 | 0.270631E+10 | 0.169495E+10 | 0.576643E+10 | 0.168961E+10 |
Minimum of Months | 0.162935E+09 | 20080000.82 | 0.100814E+09 | 0.247584E+09 | 45776326.02 |
Maximum of Months | 0.575735E+09 | 0.474921E+09 | 0.172911E+09 | 0.694638E+09 | 0.245881E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.531691E+09 | 0.202664E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.480741E+09 | 0.167761E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402207E+09 | 0.152083E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313415E+09 | 0.108128E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216330E+09 | 84396224.95 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208154E+09 | 54884083.76 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.258171E+09 | 37557568.58 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338067E+09 | 44063817.12 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418805E+09 | 73566208.23 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534007E+09 | 0.125218E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.537473E+09 | 0.161376E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.579671E+09 | 0.207822E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.481873E+10 | 0.141952E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208154E+09 | 37557568.58 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.579671E+09 | 0.207822E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.531691E+09 | 0.202664E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.480741E+09 | 0.167761E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402207E+09 | 0.152083E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313415E+09 | 0.108128E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216330E+09 | 84396224.95 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208154E+09 | 54884083.76 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.258171E+09 | 37557568.58 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338067E+09 | 44063817.12 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418805E+09 | 73566208.23 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534007E+09 | 0.125218E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.537473E+09 | 0.161376E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.579671E+09 | 0.207822E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.481873E+10 | 0.141952E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208154E+09 | 37557568.58 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.579671E+09 | 0.207822E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530645E+09 | 0.412915E+09 | 0.117730E+09 | 0.636814E+09 | 0.239760E+09 |
February | 0.469053E+09 | 0.342627E+09 | 0.126426E+09 | 0.575695E+09 | 0.198476E+09 |
March | 0.382677E+09 | 0.231352E+09 | 0.151325E+09 | 0.481835E+09 | 0.180025E+09 |
April | 0.288812E+09 | 0.118552E+09 | 0.170260E+09 | 0.375323E+09 | 0.128309E+09 |
May | 0.199034E+09 | 43783921.68 | 0.155250E+09 | 0.258855E+09 | 0.100287E+09 |
June | 0.162935E+09 | 20080000.82 | 0.142855E+09 | 0.248146E+09 | 65393041.85 |
July | 0.186306E+09 | 29751313.53 | 0.156554E+09 | 0.307828E+09 | 44842199.30 |
August | 0.256184E+09 | 83273000.63 | 0.172911E+09 | 0.403663E+09 | 52514966.96 |
September | 0.342821E+09 | 0.191167E+09 | 0.151654E+09 | 0.500665E+09 | 87468535.46 |
October | 0.484654E+09 | 0.356945E+09 | 0.127709E+09 | 0.638760E+09 | 0.148528E+09 |
November | 0.522399E+09 | 0.400940E+09 | 0.121459E+09 | 0.643315E+09 | 0.191183E+09 |
December | 0.575735E+09 | 0.474921E+09 | 0.100814E+09 | 0.693877E+09 | 0.245991E+09 |
Annual Sum or Average | 0.440126E+10 | 0.270631E+10 | 0.169495E+10 | 0.576478E+10 | 0.168278E+10 |
Minimum of Months | 0.162935E+09 | 20080000.82 | 0.100814E+09 | 0.248146E+09 | 44842199.30 |
Maximum of Months | 0.575735E+09 | 0.474921E+09 | 0.172911E+09 | 0.693877E+09 | 0.245991E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.532108E+09 | 0.201781E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.481138E+09 | 0.166912E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402824E+09 | 0.150948E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313969E+09 | 0.107257E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216683E+09 | 83884043.70 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208336E+09 | 54625354.87 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.258326E+09 | 37351082.94 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338209E+09 | 43846239.55 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418937E+09 | 73305903.06 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534291E+09 | 0.124715E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.538042E+09 | 0.160353E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.579952E+09 | 0.207100E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.482281E+10 | 0.141208E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208336E+09 | 37351082.94 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.579952E+09 | 0.207100E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.532108E+09 | 0.201781E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.481138E+09 | 0.166912E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.402824E+09 | 0.150948E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.313969E+09 | 0.107257E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.216683E+09 | 83884043.70 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208336E+09 | 54625354.87 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.258326E+09 | 37351082.94 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338209E+09 | 43846239.55 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418937E+09 | 73305903.06 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534291E+09 | 0.124715E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.538042E+09 | 0.160353E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.579952E+09 | 0.207100E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.482281E+10 | 0.141208E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208336E+09 | 37351082.94 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.579952E+09 | 0.207100E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530645E+09 | 0.412915E+09 | 0.117730E+09 | 0.637314E+09 | 0.238714E+09 |
February | 0.469053E+09 | 0.342627E+09 | 0.126426E+09 | 0.576170E+09 | 0.197470E+09 |
March | 0.382677E+09 | 0.231352E+09 | 0.151325E+09 | 0.482571E+09 | 0.178684E+09 |
April | 0.288812E+09 | 0.118552E+09 | 0.170260E+09 | 0.375983E+09 | 0.127281E+09 |
May | 0.199034E+09 | 43783921.68 | 0.155250E+09 | 0.259278E+09 | 99681560.41 |
June | 0.162935E+09 | 20080000.82 | 0.142855E+09 | 0.248363E+09 | 65087321.12 |
July | 0.186306E+09 | 29751313.53 | 0.156554E+09 | 0.308014E+09 | 44597623.75 |
August | 0.256184E+09 | 83273000.63 | 0.172911E+09 | 0.403833E+09 | 52257246.70 |
September | 0.342821E+09 | 0.191167E+09 | 0.151654E+09 | 0.500824E+09 | 87160745.87 |
October | 0.484654E+09 | 0.356945E+09 | 0.127709E+09 | 0.639099E+09 | 0.147934E+09 |
November | 0.522399E+09 | 0.400940E+09 | 0.121459E+09 | 0.643993E+09 | 0.189972E+09 |
December | 0.575735E+09 | 0.474921E+09 | 0.100814E+09 | 0.694216E+09 | 0.245133E+09 |
Annual Sum or Average | 0.440126E+10 | 0.270631E+10 | 0.169495E+10 | 0.576966E+10 | 0.167397E+10 |
Minimum of Months | 0.162935E+09 | 20080000.82 | 0.100814E+09 | 0.248363E+09 | 44597623.75 |
Maximum of Months | 0.575735E+09 | 0.474921E+09 | 0.172911E+09 | 0.694216E+09 | 0.245133E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.533282E+09 | 0.198963E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.482259E+09 | 0.164210E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.404308E+09 | 0.147839E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.315208E+09 | 0.105002E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.217527E+09 | 82450085.46 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208594E+09 | 54042047.31 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.258387E+09 | 37100333.05 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338268E+09 | 43577846.06 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.419089E+09 | 72820168.00 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534933E+09 | 0.123426E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.539274E+09 | 0.157956E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.580802E+09 | 0.204624E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.483193E+10 | 0.139201E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208594E+09 | 37100333.05 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.580802E+09 | 0.204624E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.533282E+09 | 0.198963E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.482259E+09 | 0.164210E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.404308E+09 | 0.147839E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.315208E+09 | 0.105002E+09 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.217527E+09 | 82450085.46 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208594E+09 | 54042047.31 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.258387E+09 | 37100333.05 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.338268E+09 | 43577846.06 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.419089E+09 | 72820168.00 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.534933E+09 | 0.123426E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.539274E+09 | 0.157956E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.580802E+09 | 0.204624E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.483193E+10 | 0.139201E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208594E+09 | 37100333.05 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.580802E+09 | 0.204624E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530645E+09 | 0.412915E+09 | 0.117730E+09 | 0.638721E+09 | 0.235382E+09 |
February | 0.469053E+09 | 0.342627E+09 | 0.126426E+09 | 0.577513E+09 | 0.194273E+09 |
March | 0.382677E+09 | 0.231352E+09 | 0.151325E+09 | 0.484340E+09 | 0.175016E+09 |
April | 0.288812E+09 | 0.118552E+09 | 0.170260E+09 | 0.377459E+09 | 0.124624E+09 |
May | 0.199034E+09 | 43783921.68 | 0.155250E+09 | 0.260284E+09 | 97991788.46 |
June | 0.162935E+09 | 20080000.82 | 0.142855E+09 | 0.248671E+09 | 64402675.24 |
July | 0.186306E+09 | 29751313.53 | 0.156554E+09 | 0.308086E+09 | 44307185.22 |
August | 0.256184E+09 | 83273000.63 | 0.172911E+09 | 0.403903E+09 | 51945813.33 |
September | 0.342821E+09 | 0.191167E+09 | 0.151654E+09 | 0.501007E+09 | 86592002.58 |
October | 0.484654E+09 | 0.356945E+09 | 0.127709E+09 | 0.639867E+09 | 0.146415E+09 |
November | 0.522399E+09 | 0.400940E+09 | 0.121459E+09 | 0.645461E+09 | 0.187139E+09 |
December | 0.575735E+09 | 0.474921E+09 | 0.100814E+09 | 0.695239E+09 | 0.242202E+09 |
Annual Sum or Average | 0.440126E+10 | 0.270631E+10 | 0.169495E+10 | 0.578055E+10 | 0.165029E+10 |
Minimum of Months | 0.162935E+09 | 20080000.82 | 0.100814E+09 | 0.248671E+09 | 44307185.22 |
Maximum of Months | 0.575735E+09 | 0.474921E+09 | 0.172911E+09 | 0.695239E+09 | 0.242202E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.536765E+09 | 0.188504E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.485462E+09 | 0.154336E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.407623E+09 | 0.137822E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.317198E+09 | 97931229.58 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.219053E+09 | 77403222.65 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208226E+09 | 51899373.34 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.257141E+09 | 36513323.25 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.337129E+09 | 42925242.48 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418678E+09 | 71222844.80 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.536023E+09 | 0.119060E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.541875E+09 | 0.150718E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.583541E+09 | 0.195016E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.484871E+10 | 0.132335E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208226E+09 | 36513323.25 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.583541E+09 | 0.195016E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443837E+09 | 0.345367E+09 | 98470699.41 | 0.536765E+09 | 0.188504E+09 |
February | 0.392321E+09 | 0.286577E+09 | 0.105744E+09 | 0.485462E+09 | 0.154336E+09 |
March | 0.320075E+09 | 0.193505E+09 | 0.126570E+09 | 0.407623E+09 | 0.137822E+09 |
April | 0.241566E+09 | 99158320.88 | 0.142407E+09 | 0.317198E+09 | 97931229.58 |
May | 0.166475E+09 | 36621343.42 | 0.129853E+09 | 0.219053E+09 | 77403222.65 |
June | 0.136281E+09 | 16795128.85 | 0.119486E+09 | 0.208226E+09 | 51899373.34 |
July | 0.155828E+09 | 24884318.90 | 0.130944E+09 | 0.257141E+09 | 36513323.25 |
August | 0.214275E+09 | 69650434.15 | 0.144625E+09 | 0.337129E+09 | 42925242.48 |
September | 0.286739E+09 | 0.159894E+09 | 0.126845E+09 | 0.418678E+09 | 71222844.80 |
October | 0.405370E+09 | 0.298553E+09 | 0.106817E+09 | 0.536023E+09 | 0.119060E+09 |
November | 0.436940E+09 | 0.335350E+09 | 0.101590E+09 | 0.541875E+09 | 0.150718E+09 |
December | 0.481551E+09 | 0.397229E+09 | 84321687.75 | 0.583541E+09 | 0.195016E+09 |
Annual Sum or Average | 0.368126E+10 | 0.226358E+10 | 0.141767E+10 | 0.484871E+10 | 0.132335E+10 |
Minimum of Months | 0.136281E+09 | 16795128.85 | 84321687.75 | 0.208226E+09 | 36513323.25 |
Maximum of Months | 0.481551E+09 | 0.397229E+09 | 0.144625E+09 | 0.583541E+09 | 0.195016E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530645E+09 | 0.412915E+09 | 0.117730E+09 | 0.642908E+09 | 0.223005E+09 |
February | 0.469053E+09 | 0.342627E+09 | 0.126426E+09 | 0.581361E+09 | 0.182593E+09 |
March | 0.382677E+09 | 0.231352E+09 | 0.151325E+09 | 0.488317E+09 | 0.163201E+09 |
April | 0.288812E+09 | 0.118552E+09 | 0.170260E+09 | 0.379836E+09 | 0.116292E+09 |
May | 0.199034E+09 | 43783921.68 | 0.155250E+09 | 0.262103E+09 | 92044086.68 |
June | 0.162935E+09 | 20080000.82 | 0.142855E+09 | 0.248223E+09 | 61879065.75 |
July | 0.186306E+09 | 29751313.53 | 0.156554E+09 | 0.306585E+09 | 43617394.35 |
August | 0.256184E+09 | 83273000.63 | 0.172911E+09 | 0.402531E+09 | 51182884.98 |
September | 0.342821E+09 | 0.191167E+09 | 0.151654E+09 | 0.500507E+09 | 84711896.20 |
October | 0.484654E+09 | 0.356945E+09 | 0.127709E+09 | 0.641168E+09 | 0.141261E+09 |
November | 0.522399E+09 | 0.400940E+09 | 0.121459E+09 | 0.648569E+09 | 0.178580E+09 |
December | 0.575735E+09 | 0.474921E+09 | 0.100814E+09 | 0.698539E+09 | 0.230822E+09 |
Annual Sum or Average | 0.440126E+10 | 0.270631E+10 | 0.169495E+10 | 0.580065E+10 | 0.156919E+10 |
Minimum of Months | 0.162935E+09 | 20080000.82 | 0.100814E+09 | 0.248223E+09 | 43617394.35 |
Maximum of Months | 0.575735E+09 | 0.474921E+09 | 0.172911E+09 | 0.698539E+09 | 0.230822E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1272.62 | 488.49 | 1061.26 | 825.80 | 235.45 | 0.00 | 0.00 |
February | 1274.56 | 446.49 | 1038.58 | 758.65 | 279.93 | 0.00 | 0.00 |
March | 963.16 | 366.35 | 765.33 | 462.69 | 302.64 | 0.00 | 0.00 |
April | 774.64 | 270.76 | 596.86 | 245.00 | 351.86 | 0.00 | 0.00 |
May | 518.78 | 200.86 | 398.06 | 87.57 | 310.49 | 0.00 | 0.00 |
June | 514.93 | 132.71 | 336.72 | 41.50 | 295.22 | 0.00 | 0.00 |
July | 619.45 | 85.32 | 372.60 | 59.50 | 313.10 | 0.00 | 0.00 |
August | 809.96 | 101.41 | 512.35 | 166.54 | 345.81 | 0.00 | 0.00 |
September | 1036.62 | 177.59 | 708.47 | 395.07 | 313.41 | 0.00 | 0.00 |
October | 1278.29 | 298.55 | 969.28 | 713.87 | 255.41 | 0.00 | 0.00 |
November | 1326.11 | 405.53 | 1079.59 | 828.58 | 251.01 | 0.00 | 0.00 |
December | 1387.86 | 499.10 | 1151.43 | 949.81 | 201.62 | 0.00 | 0.00 |
Annual Sum or Average | 979.76 | 288.61 | 747.59 | 459.69 | 287.90 | 0.00 | 0.00 |
Minimum of Months | 514.93 | 85.32 | 336.72 | 41.50 | 201.62 | 0.00 | 0.00 |
Maximum of Months | 1387.86 | 499.10 | 1151.43 | 949.81 | 351.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 630.12 | 258.77 | 530.63 | 412.90 | 117.73 | 0.00 | 0.00 |
February | 631.33 | 236.93 | 519.29 | 379.33 | 139.97 | 0.00 | 0.00 |
March | 474.70 | 196.30 | 382.67 | 231.34 | 151.32 | 0.00 | 0.00 |
April | 383.13 | 141.27 | 298.43 | 122.50 | 175.93 | 0.00 | 0.00 |
May | 257.31 | 103.03 | 199.03 | 43.78 | 155.25 | 0.00 | 0.00 |
June | 257.50 | 67.00 | 168.36 | 20.75 | 147.61 | 0.00 | 0.00 |
July | 310.27 | 42.94 | 186.30 | 29.75 | 156.55 | 0.00 | 0.00 |
August | 405.30 | 50.80 | 256.18 | 83.27 | 172.91 | 0.00 | 0.00 |
September | 517.98 | 88.79 | 354.24 | 197.53 | 156.70 | 0.00 | 0.00 |
October | 636.82 | 152.73 | 484.64 | 356.93 | 127.70 | 0.00 | 0.00 |
November | 656.76 | 214.60 | 539.80 | 414.29 | 125.50 | 0.00 | 0.00 |
December | 689.23 | 262.62 | 575.72 | 474.91 | 100.81 | 0.00 | 0.00 |
Annual Sum or Average | 486.73 | 150.87 | 373.79 | 229.84 | 143.95 | 0.00 | 0.00 |
Minimum of Months | 257.31 | 42.94 | 168.36 | 20.75 | 100.81 | 0.00 | 0.00 |
Maximum of Months | 689.23 | 262.62 | 575.72 | 474.91 | 175.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 630.32 | 252.30 | 529.54 | 412.06 | 117.48 | 0.00 | 0.00 |
February | 631.26 | 231.50 | 518.23 | 378.55 | 139.68 | 0.00 | 0.00 |
March | 474.81 | 193.17 | 381.88 | 230.87 | 151.01 | 0.00 | 0.00 |
April | 382.81 | 142.01 | 297.82 | 122.25 | 175.57 | 0.00 | 0.00 |
May | 256.26 | 106.35 | 198.62 | 43.69 | 154.93 | 0.00 | 0.00 |
June | 255.45 | 72.03 | 168.02 | 20.71 | 147.31 | 0.00 | 0.00 |
July | 307.30 | 48.53 | 185.92 | 29.69 | 156.23 | 0.00 | 0.00 |
August | 403.08 | 56.60 | 255.65 | 83.10 | 172.55 | 0.00 | 0.00 |
September | 516.13 | 94.61 | 353.51 | 197.13 | 156.38 | 0.00 | 0.00 |
October | 635.70 | 154.96 | 483.64 | 356.20 | 127.44 | 0.00 | 0.00 |
November | 657.29 | 210.80 | 538.69 | 413.44 | 125.25 | 0.00 | 0.00 |
December | 689.00 | 256.51 | 574.54 | 473.93 | 100.60 | 0.00 | 0.00 |
Annual Sum or Average | 485.80 | 151.20 | 373.03 | 229.37 | 143.65 | 0.00 | 0.00 |
Minimum of Months | 255.45 | 48.53 | 168.02 | 20.71 | 100.60 | 0.00 | 0.00 |
Maximum of Months | 689.00 | 256.51 | 574.54 | 473.93 | 175.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 631.36 | 249.20 | 529.54 | 412.06 | 117.48 | 0.00 | 0.00 |
February | 632.14 | 228.80 | 518.23 | 378.55 | 139.68 | 0.00 | 0.00 |
March | 475.85 | 190.63 | 381.88 | 230.87 | 151.01 | 0.00 | 0.00 |
April | 383.43 | 140.63 | 297.82 | 122.25 | 175.57 | 0.00 | 0.00 |
May | 256.43 | 105.97 | 198.62 | 43.69 | 154.93 | 0.00 | 0.00 |
June | 255.39 | 72.25 | 168.02 | 20.71 | 147.31 | 0.00 | 0.00 |
July | 307.16 | 48.97 | 185.92 | 29.69 | 156.23 | 0.00 | 0.00 |
August | 402.97 | 57.00 | 255.65 | 83.10 | 172.55 | 0.00 | 0.00 |
September | 516.08 | 94.86 | 353.51 | 197.13 | 156.38 | 0.00 | 0.00 |
October | 635.98 | 154.25 | 483.64 | 356.20 | 127.44 | 0.00 | 0.00 |
November | 658.60 | 207.95 | 538.69 | 413.44 | 125.25 | 0.00 | 0.00 |
December | 689.67 | 253.93 | 574.54 | 473.93 | 100.60 | 0.00 | 0.00 |
Annual Sum or Average | 486.26 | 149.96 | 373.03 | 229.37 | 143.65 | 0.00 | 0.00 |
Minimum of Months | 255.39 | 48.97 | 168.02 | 20.71 | 100.60 | 0.00 | 0.00 |
Maximum of Months | 689.67 | 253.93 | 574.54 | 473.93 | 175.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 632.52 | 246.55 | 529.54 | 412.06 | 117.48 | 0.00 | 0.00 |
February | 633.22 | 226.37 | 518.23 | 378.55 | 139.68 | 0.00 | 0.00 |
March | 477.39 | 187.65 | 381.88 | 230.87 | 151.01 | 0.00 | 0.00 |
April | 384.59 | 138.51 | 297.82 | 122.25 | 175.57 | 0.00 | 0.00 |
May | 257.10 | 104.67 | 198.62 | 43.69 | 154.93 | 0.00 | 0.00 |
June | 255.80 | 71.32 | 168.02 | 20.71 | 147.31 | 0.00 | 0.00 |
July | 307.50 | 48.19 | 185.92 | 29.69 | 156.23 | 0.00 | 0.00 |
August | 403.26 | 56.19 | 255.65 | 83.10 | 172.55 | 0.00 | 0.00 |
September | 516.36 | 94.00 | 353.51 | 197.13 | 156.38 | 0.00 | 0.00 |
October | 636.60 | 152.89 | 483.64 | 356.20 | 127.44 | 0.00 | 0.00 |
November | 660.22 | 204.86 | 538.69 | 413.44 | 125.25 | 0.00 | 0.00 |
December | 690.41 | 251.86 | 574.54 | 473.93 | 100.60 | 0.00 | 0.00 |
Annual Sum or Average | 487.09 | 148.18 | 373.03 | 229.37 | 143.65 | 0.00 | 0.00 |
Minimum of Months | 255.80 | 48.19 | 168.02 | 20.71 | 100.60 | 0.00 | 0.00 |
Maximum of Months | 690.41 | 251.86 | 574.54 | 473.93 | 175.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1271.30 | 481.58 | 1059.08 | 824.11 | 234.97 | 0.00 | 0.00 |
February | 1272.36 | 441.58 | 1036.45 | 757.09 | 279.36 | 0.00 | 0.00 |
March | 961.24 | 362.56 | 763.76 | 461.74 | 302.02 | 0.00 | 0.00 |
April | 773.57 | 267.45 | 595.64 | 244.50 | 351.14 | 0.00 | 0.00 |
May | 516.27 | 202.25 | 397.24 | 87.39 | 309.85 | 0.00 | 0.00 |
June | 511.53 | 136.80 | 336.03 | 41.41 | 294.62 | 0.00 | 0.00 |
July | 614.13 | 91.47 | 371.84 | 59.38 | 312.46 | 0.00 | 0.00 |
August | 805.69 | 106.99 | 511.30 | 166.20 | 345.10 | 0.00 | 0.00 |
September | 1032.97 | 182.76 | 707.02 | 394.26 | 312.76 | 0.00 | 0.00 |
October | 1275.34 | 299.08 | 967.29 | 712.40 | 254.89 | 0.00 | 0.00 |
November | 1326.48 | 398.01 | 1077.38 | 826.88 | 250.49 | 0.00 | 0.00 |
December | 1385.52 | 493.73 | 1149.07 | 947.86 | 201.21 | 0.00 | 0.00 |
Annual Sum or Average | 977.20 | 287.90 | 746.05 | 458.74 | 287.31 | 0.00 | 0.00 |
Minimum of Months | 511.53 | 91.47 | 336.03 | 41.41 | 201.21 | 0.00 | 0.00 |
Maximum of Months | 1385.52 | 493.73 | 1149.07 | 947.86 | 351.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 634.78 | 240.85 | 529.54 | 412.06 | 117.48 | 0.00 | 0.00 |
February | 635.41 | 220.73 | 518.23 | 378.55 | 139.68 | 0.00 | 0.00 |
March | 480.23 | 180.78 | 381.88 | 230.87 | 151.01 | 0.00 | 0.00 |
April | 386.63 | 132.93 | 297.82 | 122.25 | 175.57 | 0.00 | 0.00 |
May | 258.18 | 100.46 | 198.62 | 43.69 | 154.93 | 0.00 | 0.00 |
June | 256.35 | 67.58 | 168.02 | 20.71 | 147.31 | 0.00 | 0.00 |
July | 307.71 | 44.79 | 185.92 | 29.69 | 156.23 | 0.00 | 0.00 |
August | 403.15 | 52.51 | 255.65 | 83.10 | 172.55 | 0.00 | 0.00 |
September | 516.31 | 90.51 | 353.51 | 197.13 | 156.38 | 0.00 | 0.00 |
October | 637.24 | 148.96 | 483.64 | 356.20 | 127.44 | 0.00 | 0.00 |
November | 662.91 | 198.28 | 538.69 | 413.44 | 125.25 | 0.00 | 0.00 |
December | 691.91 | 247.03 | 574.54 | 473.93 | 100.60 | 0.00 | 0.00 |
Annual Sum or Average | 488.40 | 143.39 | 373.03 | 229.37 | 143.65 | 0.00 | 0.00 |
Minimum of Months | 256.35 | 44.79 | 168.02 | 20.71 | 100.60 | 0.00 | 0.00 |
Maximum of Months | 691.91 | 247.03 | 574.54 | 473.93 | 175.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 635.28 | 239.80 | 529.54 | 412.06 | 117.48 | 0.00 | 0.00 |
February | 635.93 | 219.62 | 518.23 | 378.55 | 139.68 | 0.00 | 0.00 |
March | 480.97 | 179.43 | 381.88 | 230.87 | 151.01 | 0.00 | 0.00 |
April | 387.31 | 131.87 | 297.82 | 122.25 | 175.57 | 0.00 | 0.00 |
May | 258.60 | 99.85 | 198.62 | 43.69 | 154.93 | 0.00 | 0.00 |
June | 256.57 | 67.26 | 168.02 | 20.71 | 147.31 | 0.00 | 0.00 |
July | 307.89 | 44.54 | 185.92 | 29.69 | 156.23 | 0.00 | 0.00 |
August | 403.32 | 52.25 | 255.65 | 83.10 | 172.55 | 0.00 | 0.00 |
September | 516.47 | 90.19 | 353.51 | 197.13 | 156.38 | 0.00 | 0.00 |
October | 637.57 | 148.36 | 483.64 | 356.20 | 127.44 | 0.00 | 0.00 |
November | 663.61 | 197.02 | 538.69 | 413.44 | 125.25 | 0.00 | 0.00 |
December | 692.25 | 246.17 | 574.54 | 473.93 | 100.60 | 0.00 | 0.00 |
Annual Sum or Average | 488.82 | 142.63 | 373.03 | 229.37 | 143.65 | 0.00 | 0.00 |
Minimum of Months | 256.57 | 44.54 | 168.02 | 20.71 | 100.60 | 0.00 | 0.00 |
Maximum of Months | 692.25 | 246.17 | 574.54 | 473.93 | 175.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 636.68 | 236.45 | 529.54 | 412.06 | 117.48 | 0.00 | 0.00 |
February | 637.41 | 216.06 | 518.23 | 378.55 | 139.68 | 0.00 | 0.00 |
March | 482.73 | 175.74 | 381.88 | 230.87 | 151.01 | 0.00 | 0.00 |
April | 388.84 | 129.10 | 297.82 | 122.25 | 175.57 | 0.00 | 0.00 |
May | 259.61 | 98.15 | 198.62 | 43.69 | 154.93 | 0.00 | 0.00 |
June | 256.89 | 66.55 | 168.02 | 20.71 | 147.31 | 0.00 | 0.00 |
July | 307.97 | 44.25 | 185.92 | 29.69 | 156.23 | 0.00 | 0.00 |
August | 403.39 | 51.93 | 255.65 | 83.10 | 172.55 | 0.00 | 0.00 |
September | 516.66 | 89.60 | 353.51 | 197.13 | 156.38 | 0.00 | 0.00 |
October | 638.34 | 146.83 | 483.64 | 356.20 | 127.44 | 0.00 | 0.00 |
November | 665.13 | 194.08 | 538.69 | 413.44 | 125.25 | 0.00 | 0.00 |
December | 693.26 | 243.22 | 574.54 | 473.93 | 100.60 | 0.00 | 0.00 |
Annual Sum or Average | 489.74 | 140.61 | 373.03 | 229.37 | 143.65 | 0.00 | 0.00 |
Minimum of Months | 256.89 | 44.25 | 168.02 | 20.71 | 100.60 | 0.00 | 0.00 |
Maximum of Months | 693.26 | 243.22 | 574.54 | 473.93 | 175.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 640.84 | 224.02 | 529.54 | 412.06 | 117.48 | 0.00 | 0.00 |
February | 641.65 | 203.07 | 518.23 | 378.55 | 139.68 | 0.00 | 0.00 |
March | 486.69 | 163.85 | 381.88 | 230.87 | 151.01 | 0.00 | 0.00 |
April | 391.29 | 120.43 | 297.82 | 122.25 | 175.57 | 0.00 | 0.00 |
May | 261.43 | 92.16 | 198.62 | 43.69 | 154.93 | 0.00 | 0.00 |
June | 256.43 | 63.92 | 168.02 | 20.71 | 147.31 | 0.00 | 0.00 |
July | 306.48 | 43.55 | 185.92 | 29.69 | 156.23 | 0.00 | 0.00 |
August | 402.03 | 51.16 | 255.65 | 83.10 | 172.55 | 0.00 | 0.00 |
September | 516.15 | 87.64 | 353.51 | 197.13 | 156.38 | 0.00 | 0.00 |
October | 639.64 | 141.64 | 483.64 | 356.20 | 127.44 | 0.00 | 0.00 |
November | 668.33 | 185.19 | 538.69 | 413.44 | 125.25 | 0.00 | 0.00 |
December | 696.54 | 231.80 | 574.54 | 473.93 | 100.60 | 0.00 | 0.00 |
Annual Sum or Average | 491.44 | 133.68 | 373.03 | 229.37 | 143.65 | 0.00 | 0.00 |
Minimum of Months | 256.43 | 43.55 | 168.02 | 20.71 | 100.60 | 0.00 | 0.00 |
Maximum of Months | 696.54 | 231.80 | 574.54 | 473.93 | 175.57 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.340858E+10 | 0.130838E+10 | 0.284247E+10 | 0.221183E+10 | 0.630637E+09 | 0.00 | 0.00 |
February | 0.308341E+10 | 0.108016E+10 | 0.251254E+10 | 0.183533E+10 | 0.677216E+09 | 0.00 | 0.00 |
March | 0.257973E+10 | 0.981229E+09 | 0.204986E+10 | 0.123927E+10 | 0.810594E+09 | 0.00 | 0.00 |
April | 0.200787E+10 | 0.701803E+09 | 0.154706E+10 | 0.635040E+09 | 0.912021E+09 | 0.00 | 0.00 |
May | 0.138951E+10 | 0.537972E+09 | 0.106615E+10 | 0.234534E+09 | 0.831620E+09 | 0.00 | 0.00 |
June | 0.133471E+10 | 0.343984E+09 | 0.872784E+09 | 0.107561E+09 | 0.765223E+09 | 0.00 | 0.00 |
July | 0.165915E+10 | 0.228520E+09 | 0.997972E+09 | 0.159367E+09 | 0.838605E+09 | 0.00 | 0.00 |
August | 0.216941E+10 | 0.271607E+09 | 0.137229E+10 | 0.446063E+09 | 0.926223E+09 | 0.00 | 0.00 |
September | 0.268691E+10 | 0.460323E+09 | 0.183636E+10 | 0.102401E+10 | 0.812353E+09 | 0.00 | 0.00 |
October | 0.342377E+10 | 0.799627E+09 | 0.259611E+10 | 0.191202E+10 | 0.684089E+09 | 0.00 | 0.00 |
November | 0.343728E+10 | 0.105112E+10 | 0.279830E+10 | 0.214769E+10 | 0.650613E+09 | 0.00 | 0.00 |
December | 0.371726E+10 | 0.133680E+10 | 0.308400E+10 | 0.254398E+10 | 0.540022E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.308976E+11 | 0.910153E+10 | 0.235759E+11 | 0.144967E+11 | 0.907921E+10 | 0.00 | 0.00 |
Minimum of Months | 0.133471E+10 | 0.228520E+09 | 0.872784E+09 | 0.107561E+09 | 0.540022E+09 | 0.00 | 0.00 |
Maximum of Months | 0.371726E+10 | 0.133680E+10 | 0.308400E+10 | 0.254398E+10 | 0.926223E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168772E+10 | 0.693095E+09 | 0.142124E+10 | 0.110592E+10 | 0.315318E+09 | 0.00 | 0.00 |
February | 0.152731E+10 | 0.573182E+09 | 0.125627E+10 | 0.917664E+09 | 0.338608E+09 | 0.00 | 0.00 |
March | 0.127144E+10 | 0.525783E+09 | 0.102493E+10 | 0.619633E+09 | 0.405297E+09 | 0.00 | 0.00 |
April | 0.993083E+09 | 0.366167E+09 | 0.773531E+09 | 0.317520E+09 | 0.456010E+09 | 0.00 | 0.00 |
May | 0.689190E+09 | 0.275952E+09 | 0.533077E+09 | 0.117267E+09 | 0.415810E+09 | 0.00 | 0.00 |
June | 0.667428E+09 | 0.173653E+09 | 0.436392E+09 | 53780588.19 | 0.382611E+09 | 0.00 | 0.00 |
July | 0.831034E+09 | 0.115016E+09 | 0.498986E+09 | 79683420.09 | 0.419302E+09 | 0.00 | 0.00 |
August | 0.108556E+10 | 0.136056E+09 | 0.686143E+09 | 0.223031E+09 | 0.463111E+09 | 0.00 | 0.00 |
September | 0.134259E+10 | 0.230132E+09 | 0.918182E+09 | 0.512005E+09 | 0.406176E+09 | 0.00 | 0.00 |
October | 0.170567E+10 | 0.409066E+09 | 0.129806E+10 | 0.956012E+09 | 0.342044E+09 | 0.00 | 0.00 |
November | 0.170231E+10 | 0.556243E+09 | 0.139915E+10 | 0.107384E+10 | 0.325306E+09 | 0.00 | 0.00 |
December | 0.184604E+10 | 0.703403E+09 | 0.154200E+10 | 0.127199E+10 | 0.270011E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153494E+11 | 0.475775E+10 | 0.117880E+11 | 0.724835E+10 | 0.453961E+10 | 0.00 | 0.00 |
Minimum of Months | 0.667428E+09 | 0.115016E+09 | 0.436392E+09 | 53780588.19 | 0.270011E+09 | 0.00 | 0.00 |
Maximum of Months | 0.184604E+10 | 0.703403E+09 | 0.154200E+10 | 0.127199E+10 | 0.463111E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168824E+10 | 0.675772E+09 | 0.141832E+10 | 0.110365E+10 | 0.314671E+09 | 0.00 | 0.00 |
February | 0.152713E+10 | 0.560037E+09 | 0.125369E+10 | 0.915781E+09 | 0.337913E+09 | 0.00 | 0.00 |
March | 0.127172E+10 | 0.517395E+09 | 0.102283E+10 | 0.618362E+09 | 0.404466E+09 | 0.00 | 0.00 |
April | 0.992237E+09 | 0.368088E+09 | 0.771944E+09 | 0.316869E+09 | 0.455075E+09 | 0.00 | 0.00 |
May | 0.686355E+09 | 0.284845E+09 | 0.531983E+09 | 0.117027E+09 | 0.414957E+09 | 0.00 | 0.00 |
June | 0.662135E+09 | 0.186710E+09 | 0.435497E+09 | 53670258.52 | 0.381826E+09 | 0.00 | 0.00 |
July | 0.823083E+09 | 0.129986E+09 | 0.497962E+09 | 79519951.33 | 0.418442E+09 | 0.00 | 0.00 |
August | 0.107960E+10 | 0.151590E+09 | 0.684735E+09 | 0.222574E+09 | 0.462161E+09 | 0.00 | 0.00 |
September | 0.133781E+10 | 0.245219E+09 | 0.916298E+09 | 0.510955E+09 | 0.405343E+09 | 0.00 | 0.00 |
October | 0.170266E+10 | 0.415042E+09 | 0.129539E+10 | 0.954050E+09 | 0.341343E+09 | 0.00 | 0.00 |
November | 0.170369E+10 | 0.546402E+09 | 0.139628E+10 | 0.107164E+10 | 0.324639E+09 | 0.00 | 0.00 |
December | 0.184541E+10 | 0.687041E+09 | 0.153884E+10 | 0.126938E+10 | 0.269457E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153201E+11 | 0.476813E+10 | 0.117638E+11 | 0.723348E+10 | 0.453029E+10 | 0.00 | 0.00 |
Minimum of Months | 0.662135E+09 | 0.129986E+09 | 0.435497E+09 | 53670258.52 | 0.269457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.184541E+10 | 0.687041E+09 | 0.153884E+10 | 0.126938E+10 | 0.462161E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.169103E+10 | 0.667454E+09 | 0.141832E+10 | 0.110365E+10 | 0.314671E+09 | 0.00 | 0.00 |
February | 0.152927E+10 | 0.553520E+09 | 0.125369E+10 | 0.915781E+09 | 0.337913E+09 | 0.00 | 0.00 |
March | 0.127451E+10 | 0.510584E+09 | 0.102283E+10 | 0.618362E+09 | 0.404466E+09 | 0.00 | 0.00 |
April | 0.993844E+09 | 0.364505E+09 | 0.771944E+09 | 0.316869E+09 | 0.455075E+09 | 0.00 | 0.00 |
May | 0.686821E+09 | 0.283833E+09 | 0.531983E+09 | 0.117027E+09 | 0.414957E+09 | 0.00 | 0.00 |
June | 0.661962E+09 | 0.187268E+09 | 0.435497E+09 | 53670258.52 | 0.381826E+09 | 0.00 | 0.00 |
July | 0.822685E+09 | 0.131165E+09 | 0.497962E+09 | 79519951.33 | 0.418442E+09 | 0.00 | 0.00 |
August | 0.107930E+10 | 0.152678E+09 | 0.684735E+09 | 0.222574E+09 | 0.462161E+09 | 0.00 | 0.00 |
September | 0.133767E+10 | 0.245865E+09 | 0.916298E+09 | 0.510955E+09 | 0.405343E+09 | 0.00 | 0.00 |
October | 0.170342E+10 | 0.413138E+09 | 0.129539E+10 | 0.954050E+09 | 0.341343E+09 | 0.00 | 0.00 |
November | 0.170709E+10 | 0.539001E+09 | 0.139628E+10 | 0.107164E+10 | 0.324639E+09 | 0.00 | 0.00 |
December | 0.184720E+10 | 0.680113E+09 | 0.153884E+10 | 0.126938E+10 | 0.269457E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153348E+11 | 0.472912E+10 | 0.117638E+11 | 0.723348E+10 | 0.453029E+10 | 0.00 | 0.00 |
Minimum of Months | 0.661962E+09 | 0.131165E+09 | 0.435497E+09 | 53670258.52 | 0.269457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.184720E+10 | 0.680113E+09 | 0.153884E+10 | 0.126938E+10 | 0.462161E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.169415E+10 | 0.660355E+09 | 0.141832E+10 | 0.110365E+10 | 0.314671E+09 | 0.00 | 0.00 |
February | 0.153188E+10 | 0.547637E+09 | 0.125369E+10 | 0.915781E+09 | 0.337913E+09 | 0.00 | 0.00 |
March | 0.127865E+10 | 0.502591E+09 | 0.102283E+10 | 0.618362E+09 | 0.404466E+09 | 0.00 | 0.00 |
April | 0.996854E+09 | 0.359009E+09 | 0.771944E+09 | 0.316869E+09 | 0.455075E+09 | 0.00 | 0.00 |
May | 0.688617E+09 | 0.280352E+09 | 0.531983E+09 | 0.117027E+09 | 0.414957E+09 | 0.00 | 0.00 |
June | 0.663027E+09 | 0.184865E+09 | 0.435497E+09 | 53670258.52 | 0.381826E+09 | 0.00 | 0.00 |
July | 0.823617E+09 | 0.129060E+09 | 0.497962E+09 | 79519951.33 | 0.418442E+09 | 0.00 | 0.00 |
August | 0.108010E+10 | 0.150505E+09 | 0.684735E+09 | 0.222574E+09 | 0.462161E+09 | 0.00 | 0.00 |
September | 0.133841E+10 | 0.243639E+09 | 0.916298E+09 | 0.510955E+09 | 0.405343E+09 | 0.00 | 0.00 |
October | 0.170506E+10 | 0.409491E+09 | 0.129539E+10 | 0.954050E+09 | 0.341343E+09 | 0.00 | 0.00 |
November | 0.171129E+10 | 0.530996E+09 | 0.139628E+10 | 0.107164E+10 | 0.324639E+09 | 0.00 | 0.00 |
December | 0.184918E+10 | 0.674581E+09 | 0.153884E+10 | 0.126938E+10 | 0.269457E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153608E+11 | 0.467308E+10 | 0.117638E+11 | 0.723348E+10 | 0.453029E+10 | 0.00 | 0.00 |
Minimum of Months | 0.663027E+09 | 0.129060E+09 | 0.435497E+09 | 53670258.52 | 0.269457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.184918E+10 | 0.674581E+09 | 0.153884E+10 | 0.126938E+10 | 0.462161E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.340504E+10 | 0.128986E+10 | 0.283664E+10 | 0.220730E+10 | 0.629343E+09 | 0.00 | 0.00 |
February | 0.307809E+10 | 0.106827E+10 | 0.250739E+10 | 0.183156E+10 | 0.675827E+09 | 0.00 | 0.00 |
March | 0.257459E+10 | 0.971071E+09 | 0.204566E+10 | 0.123672E+10 | 0.808931E+09 | 0.00 | 0.00 |
April | 0.200510E+10 | 0.693233E+09 | 0.154389E+10 | 0.633738E+09 | 0.910150E+09 | 0.00 | 0.00 |
May | 0.138277E+10 | 0.541711E+09 | 0.106397E+10 | 0.234053E+09 | 0.829914E+09 | 0.00 | 0.00 |
June | 0.132589E+10 | 0.354589E+09 | 0.870993E+09 | 0.107341E+09 | 0.763653E+09 | 0.00 | 0.00 |
July | 0.164488E+10 | 0.244981E+09 | 0.995924E+09 | 0.159040E+09 | 0.836884E+09 | 0.00 | 0.00 |
August | 0.215797E+10 | 0.286566E+09 | 0.136947E+10 | 0.445148E+09 | 0.924323E+09 | 0.00 | 0.00 |
September | 0.267745E+10 | 0.473705E+09 | 0.183260E+10 | 0.102191E+10 | 0.810686E+09 | 0.00 | 0.00 |
October | 0.341588E+10 | 0.801056E+09 | 0.259079E+10 | 0.190810E+10 | 0.682686E+09 | 0.00 | 0.00 |
November | 0.343825E+10 | 0.103164E+10 | 0.279256E+10 | 0.214328E+10 | 0.649278E+09 | 0.00 | 0.00 |
December | 0.371097E+10 | 0.132241E+10 | 0.307767E+10 | 0.253876E+10 | 0.538914E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.308169E+11 | 0.907909E+10 | 0.235275E+11 | 0.144670E+11 | 0.906059E+10 | 0.00 | 0.00 |
Minimum of Months | 0.132589E+10 | 0.244981E+09 | 0.870993E+09 | 0.107341E+09 | 0.538914E+09 | 0.00 | 0.00 |
Maximum of Months | 0.371097E+10 | 0.132241E+10 | 0.307767E+10 | 0.253876E+10 | 0.924323E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170019E+10 | 0.645085E+09 | 0.141832E+10 | 0.110365E+10 | 0.314671E+09 | 0.00 | 0.00 |
February | 0.153718E+10 | 0.533997E+09 | 0.125369E+10 | 0.915781E+09 | 0.337913E+09 | 0.00 | 0.00 |
March | 0.128625E+10 | 0.484190E+09 | 0.102283E+10 | 0.618362E+09 | 0.404466E+09 | 0.00 | 0.00 |
April | 0.100215E+10 | 0.344564E+09 | 0.771944E+09 | 0.316869E+09 | 0.455075E+09 | 0.00 | 0.00 |
May | 0.691514E+09 | 0.269079E+09 | 0.531983E+09 | 0.117027E+09 | 0.414957E+09 | 0.00 | 0.00 |
June | 0.664454E+09 | 0.175161E+09 | 0.435497E+09 | 53670258.52 | 0.381826E+09 | 0.00 | 0.00 |
July | 0.824169E+09 | 0.119957E+09 | 0.497962E+09 | 79519951.33 | 0.418442E+09 | 0.00 | 0.00 |
August | 0.107980E+10 | 0.140642E+09 | 0.684735E+09 | 0.222574E+09 | 0.462161E+09 | 0.00 | 0.00 |
September | 0.133827E+10 | 0.234601E+09 | 0.916298E+09 | 0.510955E+09 | 0.405343E+09 | 0.00 | 0.00 |
October | 0.170677E+10 | 0.398963E+09 | 0.129539E+10 | 0.954050E+09 | 0.341343E+09 | 0.00 | 0.00 |
November | 0.171826E+10 | 0.513935E+09 | 0.139628E+10 | 0.107164E+10 | 0.324639E+09 | 0.00 | 0.00 |
December | 0.185322E+10 | 0.661635E+09 | 0.153884E+10 | 0.126938E+10 | 0.269457E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.154022E+11 | 0.452181E+10 | 0.117638E+11 | 0.723348E+10 | 0.453029E+10 | 0.00 | 0.00 |
Minimum of Months | 0.664454E+09 | 0.119957E+09 | 0.435497E+09 | 53670258.52 | 0.269457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185322E+10 | 0.661635E+09 | 0.153884E+10 | 0.126938E+10 | 0.462161E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170153E+10 | 0.642274E+09 | 0.141832E+10 | 0.110365E+10 | 0.314671E+09 | 0.00 | 0.00 |
February | 0.153845E+10 | 0.531294E+09 | 0.125369E+10 | 0.915781E+09 | 0.337913E+09 | 0.00 | 0.00 |
March | 0.128822E+10 | 0.480580E+09 | 0.102283E+10 | 0.618362E+09 | 0.404466E+09 | 0.00 | 0.00 |
April | 0.100392E+10 | 0.341796E+09 | 0.771944E+09 | 0.316869E+09 | 0.455075E+09 | 0.00 | 0.00 |
May | 0.692645E+09 | 0.267449E+09 | 0.531983E+09 | 0.117027E+09 | 0.414957E+09 | 0.00 | 0.00 |
June | 0.665035E+09 | 0.174338E+09 | 0.435497E+09 | 53670258.52 | 0.381826E+09 | 0.00 | 0.00 |
July | 0.824666E+09 | 0.119299E+09 | 0.497962E+09 | 79519951.33 | 0.418442E+09 | 0.00 | 0.00 |
August | 0.108025E+10 | 0.139949E+09 | 0.684735E+09 | 0.222574E+09 | 0.462161E+09 | 0.00 | 0.00 |
September | 0.133870E+10 | 0.233772E+09 | 0.916298E+09 | 0.510955E+09 | 0.405343E+09 | 0.00 | 0.00 |
October | 0.170768E+10 | 0.397364E+09 | 0.129539E+10 | 0.954050E+09 | 0.341343E+09 | 0.00 | 0.00 |
November | 0.172008E+10 | 0.510678E+09 | 0.139628E+10 | 0.107164E+10 | 0.324639E+09 | 0.00 | 0.00 |
December | 0.185412E+10 | 0.659333E+09 | 0.153884E+10 | 0.126938E+10 | 0.269457E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.154153E+11 | 0.449812E+10 | 0.117638E+11 | 0.723348E+10 | 0.453029E+10 | 0.00 | 0.00 |
Minimum of Months | 0.665035E+09 | 0.119299E+09 | 0.435497E+09 | 53670258.52 | 0.269457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185412E+10 | 0.659333E+09 | 0.153884E+10 | 0.126938E+10 | 0.462161E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170528E+10 | 0.633308E+09 | 0.141832E+10 | 0.110365E+10 | 0.314671E+09 | 0.00 | 0.00 |
February | 0.154203E+10 | 0.522694E+09 | 0.125369E+10 | 0.915781E+09 | 0.337913E+09 | 0.00 | 0.00 |
March | 0.129296E+10 | 0.470694E+09 | 0.102283E+10 | 0.618362E+09 | 0.404466E+09 | 0.00 | 0.00 |
April | 0.100788E+10 | 0.334627E+09 | 0.771944E+09 | 0.316869E+09 | 0.455075E+09 | 0.00 | 0.00 |
May | 0.695337E+09 | 0.262892E+09 | 0.531983E+09 | 0.117027E+09 | 0.414957E+09 | 0.00 | 0.00 |
June | 0.665858E+09 | 0.172486E+09 | 0.435497E+09 | 53670258.52 | 0.381826E+09 | 0.00 | 0.00 |
July | 0.824859E+09 | 0.118508E+09 | 0.497962E+09 | 79519951.33 | 0.418442E+09 | 0.00 | 0.00 |
August | 0.108044E+10 | 0.139101E+09 | 0.684735E+09 | 0.222574E+09 | 0.462161E+09 | 0.00 | 0.00 |
September | 0.133918E+10 | 0.232232E+09 | 0.916298E+09 | 0.510955E+09 | 0.405343E+09 | 0.00 | 0.00 |
October | 0.170973E+10 | 0.393265E+09 | 0.129539E+10 | 0.954050E+09 | 0.341343E+09 | 0.00 | 0.00 |
November | 0.172401E+10 | 0.503050E+09 | 0.139628E+10 | 0.107164E+10 | 0.324639E+09 | 0.00 | 0.00 |
December | 0.185684E+10 | 0.651450E+09 | 0.153884E+10 | 0.126938E+10 | 0.269457E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.154444E+11 | 0.443431E+10 | 0.117638E+11 | 0.723348E+10 | 0.453029E+10 | 0.00 | 0.00 |
Minimum of Months | 0.665858E+09 | 0.118508E+09 | 0.435497E+09 | 53670258.52 | 0.269457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185684E+10 | 0.651450E+09 | 0.153884E+10 | 0.126938E+10 | 0.462161E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.171644E+10 | 0.600012E+09 | 0.141832E+10 | 0.110365E+10 | 0.314671E+09 | 0.00 | 0.00 |
February | 0.155229E+10 | 0.491265E+09 | 0.125369E+10 | 0.915781E+09 | 0.337913E+09 | 0.00 | 0.00 |
March | 0.130356E+10 | 0.438843E+09 | 0.102283E+10 | 0.618362E+09 | 0.404466E+09 | 0.00 | 0.00 |
April | 0.101423E+10 | 0.312153E+09 | 0.771944E+09 | 0.316869E+09 | 0.455075E+09 | 0.00 | 0.00 |
May | 0.700207E+09 | 0.246850E+09 | 0.531983E+09 | 0.117027E+09 | 0.414957E+09 | 0.00 | 0.00 |
June | 0.664675E+09 | 0.165677E+09 | 0.435497E+09 | 53670258.52 | 0.381826E+09 | 0.00 | 0.00 |
July | 0.820865E+09 | 0.116643E+09 | 0.497962E+09 | 79519951.33 | 0.418442E+09 | 0.00 | 0.00 |
August | 0.107679E+10 | 0.137033E+09 | 0.684735E+09 | 0.222574E+09 | 0.462161E+09 | 0.00 | 0.00 |
September | 0.133786E+10 | 0.227158E+09 | 0.916298E+09 | 0.510955E+09 | 0.405343E+09 | 0.00 | 0.00 |
October | 0.171321E+10 | 0.379380E+09 | 0.129539E+10 | 0.954050E+09 | 0.341343E+09 | 0.00 | 0.00 |
November | 0.173232E+10 | 0.480016E+09 | 0.139628E+10 | 0.107164E+10 | 0.324639E+09 | 0.00 | 0.00 |
December | 0.186562E+10 | 0.620853E+09 | 0.153884E+10 | 0.126938E+10 | 0.269457E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.154981E+11 | 0.421588E+10 | 0.117638E+11 | 0.723348E+10 | 0.453029E+10 | 0.00 | 0.00 |
Minimum of Months | 0.664675E+09 | 0.116643E+09 | 0.435497E+09 | 53670258.52 | 0.269457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186562E+10 | 0.620853E+09 | 0.153884E+10 | 0.126938E+10 | 0.462161E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.365175E+09 | -238991349.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126183915.4 | 59.95 | 0.00 | 0.00 |
February | 0.331973E+09 | -218653124.1 | 0.00 | 0.00 | 672.00 | 0.00 | -113320020.7 | 59.95 | 0.00 | 0.00 |
March | 0.362836E+09 | -240101912.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122734223.5 | 59.95 | 0.00 | 0.00 |
April | 0.332294E+09 | -217418186.8 | 0.00 | 0.00 | 720.00 | 0.00 | -114876008.8 | 59.95 | 0.00 | 0.00 |
May | 0.326468E+09 | -209530198.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116937756.2 | 59.95 | 0.00 | 0.00 |
June | 0.302555E+09 | -190555343.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111999602.5 | 59.95 | 0.00 | 0.00 |
July | 0.298520E+09 | -183378594.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115141045.6 | 59.95 | 0.00 | 0.00 |
August | 0.300351E+09 | -185215317.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115136180.7 | 59.95 | 0.00 | 0.00 |
September | 0.294938E+09 | -183145550.5 | 0.00 | 0.00 | 720.00 | 0.00 | -111792696.4 | 59.95 | 0.00 | 0.00 |
October | 0.317460E+09 | -199891360.8 | 0.00 | 0.00 | 744.00 | 0.00 | -117568338.6 | 59.95 | 0.00 | 0.00 |
November | 0.326094E+09 | -207755131.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118338727.9 | 59.95 | 0.00 | 0.00 |
December | 0.356354E+09 | -229843349.2 | 0.00 | 0.00 | 744.00 | 0.00 | -126510170.3 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.391502E+10 | -0.250448E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141054E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.294938E+09 | -240101912.6 | 0.00 | 0.00 | 672.00 | 0.00 | -126510170.3 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.365175E+09 | -183145550.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111792696.4 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.361960E+09 | -238991359.7 | 0.00 | 0.00 | 744.00 | 0.00 | -122968670.4 | 59.95 | 0.00 | 0.00 |
February | 0.329213E+09 | -218653201.8 | 0.00 | 0.00 | 672.00 | 0.00 | -110559548.8 | 59.95 | 0.00 | 0.00 |
March | 0.359634E+09 | -240101884.3 | 0.00 | 0.00 | 744.00 | 0.00 | -119531933.9 | 59.95 | 0.00 | 0.00 |
April | 0.330884E+09 | -217418140.6 | 0.00 | 0.00 | 720.00 | 0.00 | -113465421.9 | 59.95 | 0.00 | 0.00 |
May | 0.325866E+09 | -209530250.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116335673.4 | 59.95 | 0.00 | 0.00 |
June | 0.302410E+09 | -190555294.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111854509.0 | 59.95 | 0.00 | 0.00 |
July | 0.298438E+09 | -183378530.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115059182.2 | 59.95 | 0.00 | 0.00 |
August | 0.300300E+09 | -185215282.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115084461.3 | 59.95 | 0.00 | 0.00 |
September | 0.294954E+09 | -183145630.7 | 0.00 | 0.00 | 720.00 | 0.00 | -111807936.1 | 59.95 | 0.00 | 0.00 |
October | 0.316618E+09 | -199891328.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116726186.0 | 59.95 | 0.00 | 0.00 |
November | 0.323020E+09 | -207755100.1 | 0.00 | 0.00 | 720.00 | 0.00 | -115264473.3 | 59.95 | 0.00 | 0.00 |
December | 0.353554E+09 | -229843303.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123710263.0 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.389685E+10 | -0.250448E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139237E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.294954E+09 | -240101884.3 | 0.00 | 0.00 | 672.00 | 0.00 | -123710263.0 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.361960E+09 | -183145630.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110559548.8 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.334991E+09 | -210164404.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124826850.2 | 59.95 | 0.00 | 0.00 |
February | 0.304446E+09 | -192434359.6 | 0.00 | 0.00 | 672.00 | 0.00 | -112011343.4 | 59.95 | 0.00 | 0.00 |
March | 0.334878E+09 | -214282471.8 | 0.00 | 0.00 | 744.00 | 0.00 | -120595630.1 | 59.95 | 0.00 | 0.00 |
April | 0.304598E+09 | -191221744.8 | 0.00 | 0.00 | 720.00 | 0.00 | -113376447.6 | 59.95 | 0.00 | 0.00 |
May | 0.301241E+09 | -185861837.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115379253.2 | 59.95 | 0.00 | 0.00 |
June | 0.279948E+09 | -169700515.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110247232.9 | 59.95 | 0.00 | 0.00 |
July | 0.273325E+09 | -160307227.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113017286.3 | 59.95 | 0.00 | 0.00 |
August | 0.278672E+09 | -165435361.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113236225.1 | 59.95 | 0.00 | 0.00 |
September | 0.271191E+09 | -160984785.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110205777.4 | 59.95 | 0.00 | 0.00 |
October | 0.292049E+09 | -175809518.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116239862.1 | 59.95 | 0.00 | 0.00 |
November | 0.300021E+09 | -183431010.9 | 0.00 | 0.00 | 720.00 | 0.00 | -116590080.5 | 59.95 | 0.00 | 0.00 |
December | 0.326080E+09 | -200621234.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125458452.3 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.360144E+10 | -0.221025E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139118E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.271191E+09 | -214282471.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125458452.3 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.334991E+09 | -160307227.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110205777.4 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.335563E+09 | -210164377.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125398945.3 | 59.95 | 0.00 | 0.00 |
February | 0.304894E+09 | -192434361.0 | 0.00 | 0.00 | 672.00 | 0.00 | -112459821.4 | 59.95 | 0.00 | 0.00 |
March | 0.335401E+09 | -214282523.0 | 0.00 | 0.00 | 744.00 | 0.00 | -121118723.0 | 59.95 | 0.00 | 0.00 |
April | 0.304876E+09 | -191221724.4 | 0.00 | 0.00 | 720.00 | 0.00 | -113654125.4 | 59.95 | 0.00 | 0.00 |
May | 0.301319E+09 | -185861818.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115457057.1 | 59.95 | 0.00 | 0.00 |
June | 0.279909E+09 | -169700488.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110208310.2 | 59.95 | 0.00 | 0.00 |
July | 0.273240E+09 | -160307226.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112933031.2 | 59.95 | 0.00 | 0.00 |
August | 0.278599E+09 | -165435313.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113163258.3 | 59.95 | 0.00 | 0.00 |
September | 0.271151E+09 | -160984780.3 | 0.00 | 0.00 | 720.00 | 0.00 | -110166353.7 | 59.95 | 0.00 | 0.00 |
October | 0.292192E+09 | -175809471.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116382794.6 | 59.95 | 0.00 | 0.00 |
November | 0.300638E+09 | -183431031.2 | 0.00 | 0.00 | 720.00 | 0.00 | -117206812.7 | 59.95 | 0.00 | 0.00 |
December | 0.326513E+09 | -200621247.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125891702.1 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.360430E+10 | -0.221025E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139404E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.271151E+09 | -214282523.0 | 0.00 | 0.00 | 672.00 | 0.00 | -125891702.1 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.335563E+09 | -160307226.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110166353.7 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.325702E+09 | -198635378.2 | 0.00 | 0.00 | 744.00 | 0.00 | -127066289.0 | 59.95 | 0.00 | 0.00 |
February | 0.295902E+09 | -181976565.9 | 0.00 | 0.00 | 672.00 | 0.00 | -113925071.1 | 59.95 | 0.00 | 0.00 |
March | 0.325946E+09 | -202757838.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123188352.5 | 59.95 | 0.00 | 0.00 |
April | 0.296105E+09 | -180954692.4 | 0.00 | 0.00 | 720.00 | 0.00 | -115150645.6 | 59.95 | 0.00 | 0.00 |
May | 0.292292E+09 | -175770922.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116521496.2 | 59.95 | 0.00 | 0.00 |
June | 0.271614E+09 | -160575632.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111037941.7 | 59.95 | 0.00 | 0.00 |
July | 0.265252E+09 | -151609620.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113642839.1 | 59.95 | 0.00 | 0.00 |
August | 0.270411E+09 | -156537027.3 | 0.00 | 0.00 | 744.00 | 0.00 | -113874235.2 | 59.95 | 0.00 | 0.00 |
September | 0.263149E+09 | -152343776.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110804820.6 | 59.95 | 0.00 | 0.00 |
October | 0.283508E+09 | -166168305.0 | 0.00 | 0.00 | 744.00 | 0.00 | -117339766.8 | 59.95 | 0.00 | 0.00 |
November | 0.292490E+09 | -173245953.4 | 0.00 | 0.00 | 720.00 | 0.00 | -119244482.1 | 59.95 | 0.00 | 0.00 |
December | 0.316910E+09 | -189734565.7 | 0.00 | 0.00 | 744.00 | 0.00 | -127175792.2 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.349928E+10 | -0.209031E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140897E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.263149E+09 | -202757838.6 | 0.00 | 0.00 | 672.00 | 0.00 | -127175792.2 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.325946E+09 | -151609620.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110804820.6 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.325785E+09 | -198635324.7 | 0.00 | 0.00 | 744.00 | 0.00 | -127149249.5 | 59.95 | 0.00 | 0.00 |
February | 0.295986E+09 | -181976503.6 | 0.00 | 0.00 | 672.00 | 0.00 | -114009994.9 | 59.95 | 0.00 | 0.00 |
March | 0.326115E+09 | -202757853.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123357423.2 | 59.95 | 0.00 | 0.00 |
April | 0.296258E+09 | -180954643.3 | 0.00 | 0.00 | 720.00 | 0.00 | -115303362.8 | 59.95 | 0.00 | 0.00 |
May | 0.292392E+09 | -175770918.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116621413.8 | 59.95 | 0.00 | 0.00 |
June | 0.271716E+09 | -160575708.7 | 0.00 | 0.00 | 720.00 | 0.00 | -111140553.1 | 59.95 | 0.00 | 0.00 |
July | 0.265387E+09 | -151609598.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113777608.0 | 59.95 | 0.00 | 0.00 |
August | 0.270543E+09 | -156537019.8 | 0.00 | 0.00 | 744.00 | 0.00 | -114005548.5 | 59.95 | 0.00 | 0.00 |
September | 0.263257E+09 | -152343675.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110913569.2 | 59.95 | 0.00 | 0.00 |
October | 0.283610E+09 | -166168244.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117441893.5 | 59.95 | 0.00 | 0.00 |
November | 0.292694E+09 | -173245994.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119448104.2 | 59.95 | 0.00 | 0.00 |
December | 0.316960E+09 | -189734526.6 | 0.00 | 0.00 | 744.00 | 0.00 | -127225564.1 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.350070E+10 | -0.209031E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141039E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.263257E+09 | -202757853.5 | 0.00 | 0.00 | 672.00 | 0.00 | -127225564.1 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.326115E+09 | -151609598.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110913569.2 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.325972E+09 | -198635318.9 | 0.00 | 0.00 | 744.00 | 0.00 | -127336929.3 | 59.95 | 0.00 | 0.00 |
February | 0.296172E+09 | -181976563.1 | 0.00 | 0.00 | 672.00 | 0.00 | -114195107.9 | 59.95 | 0.00 | 0.00 |
March | 0.326399E+09 | -202757808.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123640705.9 | 59.95 | 0.00 | 0.00 |
April | 0.296489E+09 | -180954664.5 | 0.00 | 0.00 | 720.00 | 0.00 | -115534149.5 | 59.95 | 0.00 | 0.00 |
May | 0.292523E+09 | -175770871.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116751984.3 | 59.95 | 0.00 | 0.00 |
June | 0.271774E+09 | -160575684.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111198623.6 | 59.95 | 0.00 | 0.00 |
July | 0.265436E+09 | -151609625.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113826405.2 | 59.95 | 0.00 | 0.00 |
August | 0.270590E+09 | -156537007.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114052765.5 | 59.95 | 0.00 | 0.00 |
September | 0.263309E+09 | -152343711.5 | 0.00 | 0.00 | 720.00 | 0.00 | -110965269.6 | 59.95 | 0.00 | 0.00 |
October | 0.283732E+09 | -166168214.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117564104.0 | 59.95 | 0.00 | 0.00 |
November | 0.292966E+09 | -173245999.6 | 0.00 | 0.00 | 720.00 | 0.00 | -119719788.4 | 59.95 | 0.00 | 0.00 |
December | 0.317096E+09 | -189734560.2 | 0.00 | 0.00 | 744.00 | 0.00 | -127361523.7 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.350246E+10 | -0.209031E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141215E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.263309E+09 | -202757808.9 | 0.00 | 0.00 | 672.00 | 0.00 | -127361523.7 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.326399E+09 | -151609625.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110965269.6 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.604458E+10 | 57562.48 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.415165E+10 | 57562.48 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101742E+10 | 57562.48 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77727490.97 | 22663.46 | 08-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4243548.47 | 2072.47 | 06-MAY-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304791E+09 | 43504.12 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.697948E+09 | 57562.48 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.643331E+10 | 57562.48 | 04-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.643331E+10 | 57562.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115111E+10 | 30362.08 | 17-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705991E+09 | 30362.08 | 03-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68038519.08 | 22581.25 | 04-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1325350.57 | 770.33 | 08-APR-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47760565.02 | 3667.32 | 26-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28749410.86 | 4372.09 | 27-NOV-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126277E+10 | 30362.08 | 08-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126277E+10 | 30362.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179772E+10 | 31700.38 | 17-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116574E+10 | 31700.38 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196421E+09 | 18440.93 | 04-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7938807.05 | 3905.18 | 08-APR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90358340.34 | 9928.32 | 27-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136667E+09 | 6440.25 | 27-NOV-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206051E+10 | 28937.10 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206051E+10 | 31700.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198017E+10 | 31555.66 | 17-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129638E+10 | 31555.66 | 04-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252444E+09 | 22103.33 | 05-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12388329.63 | 4339.01 | 08-APR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101056E+09 | 5832.93 | 26-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193282E+09 | 7265.24 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.226779E+10 | 31555.66 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.610351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226779E+10 | 31555.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.224886E+10 | 31550.25 | 17-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150131E+10 | 31550.25 | 04-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.349010E+09 | 26748.85 | 05-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26727680.82 | 4460.13 | 08-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121793E+09 | 6580.20 | 27-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.281752E+09 | 9518.05 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255899E+10 | 31550.25 | 09-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.708845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255899E+10 | 31550.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.486399E+10 | 54916.24 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330861E+10 | 54916.24 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.852123E+09 | 54916.24 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82984274.96 | 19896.87 | 08-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2991892.12 | 1763.16 | 06-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285417E+09 | 38043.99 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.821193E+09 | 54916.24 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.556831E+10 | 54916.24 | 04-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.556831E+10 | 54916.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.253880E+10 | 27823.65 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173162E+10 | 27823.65 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.461430E+09 | 27823.65 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46274873.08 | 12325.82 | 08-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1730320.36 | 1210.04 | 06-MAY-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146232E+09 | 19581.82 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.437543E+09 | 27823.65 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288036E+10 | 27823.65 | 04-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288036E+10 | 27823.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.264630E+10 | 27712.57 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181736E+10 | 27712.57 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.517467E+09 | 27712.57 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 58294601.32 | 15800.47 | 08-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2901507.50 | 1711.31 | 06-MAY-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155573E+09 | 21048.80 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.497433E+09 | 27712.57 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298665E+10 | 27712.57 | 04-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.868197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298665E+10 | 27712.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.301003E+10 | 27622.30 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.211978E+10 | 27622.30 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.709789E+09 | 27622.30 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98673462.78 | 26456.94 | 08-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8301456.04 | 2822.40 | 05-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189541E+09 | 27498.36 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.667868E+09 | 27622.30 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334185E+10 | 27622.30 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.334185E+10 | 27622.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.417584E+10 | 30225.33 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307955E+10 | 30225.33 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131418E+10 | 30225.33 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219947E+09 | 30225.33 | 01-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25174091.15 | 16466.52 | 06-MAY-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.297182E+09 | 30225.33 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112066E+10 | 30225.33 | 05-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.442353E+10 | 30225.33 | 01-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.442353E+10 | 30225.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 69081974.13 | 69081974.13 | 4661.10 | 14-FEB-16:00 | 4661.10 | 0.00 |
March | 0.00 | 0.00 | 0.158556E+09 | 0.158556E+09 | 4734.72 | 08-MAR-16:00 | 4734.72 | 0.00 |
April | 0.00 | 0.00 | 0.317927E+10 | 0.317927E+10 | 11693.23 | 13-APR-17:00 | 11693.23 | 0.00 |
May | 0.00 | 0.00 | 0.782756E+10 | 0.778012E+10 | 15271.73 | 19-MAY-16:50 | 15271.73 | 0.00 |
June | 0.00 | 0.00 | 0.168233E+11 | 0.165573E+11 | 38768.54 | 29-JUN-07:02 | 38458.49 | 0.00 |
July | 0.00 | 0.00 | 0.241400E+11 | 0.217201E+11 | 41162.25 | 26-JUL-07:02 | 28713.19 | 0.00 |
August | 0.00 | 0.00 | 0.219966E+11 | 0.198493E+11 | 41528.65 | 14-AUG-07:02 | 25354.53 | 0.00 |
September | 0.00 | 0.00 | 0.144025E+11 | 0.133392E+11 | 36895.31 | 03-SEP-07:02 | 32706.15 | 0.00 |
October | 0.00 | 0.00 | 0.536352E+10 | 0.513676E+10 | 22703.44 | 02-OCT-07:03 | 17276.52 | 0.00 |
November | 0.00 | 0.00 | 24538.67 | 23730.15 | 34.86 | 02-NOV-15:00 | 33.52 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.939604E+11 | 0.877898E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241400E+11 | 0.217201E+11 | 41528.65 | 38458.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3887964.96 | 3887964.96 | 2478.86 | 01-JAN-18:20 | 2478.86 | 0.00 |
February | 0.00 | 0.00 | 72196291.89 | 72196291.89 | 3347.53 | 14-FEB-16:00 | 3347.53 | 0.00 |
March | 0.00 | 0.00 | 0.214615E+09 | 0.214592E+09 | 20234.50 | 12-MAR-17:01 | 20234.50 | 0.00 |
April | 0.00 | 0.00 | 0.247672E+10 | 0.247644E+10 | 20234.50 | 13-APR-20:08 | 20234.50 | 0.00 |
May | 0.00 | 0.00 | 0.530968E+10 | 0.525896E+10 | 20863.50 | 21-MAY-22:58 | 17757.60 | 0.00 |
June | 0.00 | 0.00 | 0.962680E+10 | 0.943796E+10 | 21018.79 | 30-JUN-22:10 | 18439.65 | 0.00 |
July | 0.00 | 0.00 | 0.133784E+11 | 0.119221E+11 | 22484.68 | 31-JUL-20:03 | 13008.84 | 0.00 |
August | 0.00 | 0.00 | 0.123821E+11 | 0.110711E+11 | 22081.72 | 14-AUG-07:02 | 14057.40 | 0.00 |
September | 0.00 | 0.00 | 0.903294E+10 | 0.830786E+10 | 21467.83 | 04-SEP-20:58 | 15914.60 | 0.00 |
October | 0.00 | 0.00 | 0.354553E+10 | 0.337586E+10 | 21349.01 | 02-OCT-20:02 | 14046.11 | 0.00 |
November | 0.00 | 0.00 | 14707197.78 | 14571741.29 | 10096.36 | 02-NOV-22:51 | 10096.36 | 0.00 |
December | 0.00 | 0.00 | 1550454.97 | 1550454.97 | 1263.22 | 02-DEC-19:17 | 1263.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.560590E+11 | 0.521570E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1550454.97 | 1550454.97 | 1263.22 | 1263.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.133784E+11 | 0.119221E+11 | 22484.68 | 20234.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 48288683.37 | 48288683.37 | 2877.69 | 14-FEB-16:00 | 2877.69 | 0.00 |
March | 0.00 | 0.00 | 97217884.49 | 97217884.49 | 3241.01 | 08-MAR-14:00 | 3241.01 | 0.00 |
April | 0.00 | 0.00 | 0.156414E+10 | 0.156414E+10 | 6056.71 | 13-APR-16:10 | 6056.71 | 0.00 |
May | 0.00 | 0.00 | 0.341669E+10 | 0.339510E+10 | 7865.17 | 19-MAY-16:10 | 7865.17 | 0.00 |
June | 0.00 | 0.00 | 0.721177E+10 | 0.708335E+10 | 22501.53 | 29-JUN-06:02 | 20325.29 | 0.00 |
July | 0.00 | 0.00 | 0.996737E+10 | 0.899709E+10 | 23001.04 | 01-JUL-06:02 | 13958.43 | 0.00 |
August | 0.00 | 0.00 | 0.921664E+10 | 0.831171E+10 | 23259.33 | 14-AUG-06:02 | 13901.18 | 0.00 |
September | 0.00 | 0.00 | 0.634389E+10 | 0.589289E+10 | 22418.89 | 05-SEP-06:02 | 13095.58 | 0.00 |
October | 0.00 | 0.00 | 0.248345E+10 | 0.238132E+10 | 20079.52 | 02-OCT-06:02 | 15927.99 | 0.00 |
November | 0.00 | 0.00 | 863336.66 | 861997.70 | 821.50 | 01-NOV-06:10 | 821.50 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.403503E+11 | 0.377720E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.996737E+10 | 0.899709E+10 | 23259.33 | 20325.29 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 41898115.60 | 41898115.60 | 2673.15 | 14-FEB-16:00 | 2673.15 | 0.00 |
March | 0.00 | 0.00 | 81649732.16 | 81649732.16 | 3026.07 | 08-MAR-14:00 | 3026.07 | 0.00 |
April | 0.00 | 0.00 | 0.151560E+10 | 0.151560E+10 | 5971.18 | 13-APR-16:10 | 5971.18 | 0.00 |
May | 0.00 | 0.00 | 0.339652E+10 | 0.337508E+10 | 7856.94 | 19-MAY-16:10 | 7856.94 | 0.00 |
June | 0.00 | 0.00 | 0.723029E+10 | 0.710131E+10 | 22377.29 | 29-JUN-06:02 | 20219.95 | 0.00 |
July | 0.00 | 0.00 | 0.100125E+11 | 0.903734E+10 | 23260.64 | 16-JUL-07:03 | 14499.50 | 0.00 |
August | 0.00 | 0.00 | 0.925802E+10 | 0.834773E+10 | 23131.41 | 14-AUG-06:02 | 13839.16 | 0.00 |
September | 0.00 | 0.00 | 0.636617E+10 | 0.591155E+10 | 22295.83 | 05-SEP-06:02 | 13038.42 | 0.00 |
October | 0.00 | 0.00 | 0.246987E+10 | 0.236693E+10 | 20969.72 | 02-OCT-06:02 | 16667.04 | 0.00 |
November | 0.00 | 0.00 | 364239.54 | 364232.99 | 429.17 | 01-NOV-06:10 | 429.17 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.403729E+11 | 0.377795E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100125E+11 | 0.903734E+10 | 23260.64 | 20219.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 33107247.23 | 33107247.23 | 2364.53 | 14-FEB-16:00 | 2364.53 | 0.00 |
March | 0.00 | 0.00 | 58530920.79 | 58530920.79 | 2682.04 | 08-MAR-14:00 | 2682.04 | 0.00 |
April | 0.00 | 0.00 | 0.139971E+10 | 0.139971E+10 | 5762.73 | 13-APR-16:10 | 5762.73 | 0.00 |
May | 0.00 | 0.00 | 0.324816E+10 | 0.322900E+10 | 7709.39 | 19-MAY-16:10 | 7709.39 | 0.00 |
June | 0.00 | 0.00 | 0.704697E+10 | 0.692415E+10 | 22365.36 | 29-JUN-06:02 | 20178.61 | 0.00 |
July | 0.00 | 0.00 | 0.981158E+10 | 0.885842E+10 | 22863.26 | 01-JUL-06:02 | 13855.76 | 0.00 |
August | 0.00 | 0.00 | 0.905886E+10 | 0.817290E+10 | 23122.96 | 14-AUG-06:02 | 13811.59 | 0.00 |
September | 0.00 | 0.00 | 0.619281E+10 | 0.575553E+10 | 22287.68 | 05-SEP-06:02 | 13013.62 | 0.00 |
October | 0.00 | 0.00 | 0.236629E+10 | 0.226729E+10 | 19717.12 | 02-OCT-06:02 | 15630.07 | 0.00 |
November | 0.00 | 0.00 | 962.38 | 960.66 | 0.25 | 03-NOV-17:20 | 0.25 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.392160E+11 | 0.366986E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.981158E+10 | 0.885842E+10 | 23122.96 | 20178.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 49537528.16 | 49537528.16 | 4191.79 | 14-FEB-16:00 | 4191.79 | 0.00 |
March | 0.00 | 0.00 | 88874001.26 | 88874001.26 | 4234.22 | 08-MAR-14:00 | 4234.22 | 0.00 |
April | 0.00 | 0.00 | 0.228069E+10 | 0.228069E+10 | 10149.94 | 28-APR-14:50 | 10149.94 | 0.00 |
May | 0.00 | 0.00 | 0.558574E+10 | 0.555324E+10 | 13863.97 | 19-MAY-15:00 | 13863.97 | 0.00 |
June | 0.00 | 0.00 | 0.125228E+11 | 0.123173E+11 | 37342.08 | 25-JUN-08:62 | 34232.25 | 0.00 |
July | 0.00 | 0.00 | 0.174466E+11 | 0.157786E+11 | 39497.30 | 16-JUL-08:62 | 25739.07 | 0.00 |
August | 0.00 | 0.00 | 0.162554E+11 | 0.146463E+11 | 39319.44 | 13-AUG-08:62 | 23683.85 | 0.00 |
September | 0.00 | 0.00 | 0.109383E+11 | 0.101255E+11 | 37530.53 | 04-SEP-08:62 | 28170.36 | 0.00 |
October | 0.00 | 0.00 | 0.412439E+10 | 0.393502E+10 | 28811.00 | 02-OCT-07:03 | 22650.06 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.692924E+11 | 0.647751E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.174466E+11 | 0.157786E+11 | 39497.30 | 34232.25 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 23376154.18 | 23376154.18 | 2127.60 | 14-FEB-16:00 | 2127.60 | 0.00 |
March | 0.00 | 0.00 | 38965237.73 | 38965237.73 | 2033.12 | 08-MAR-14:00 | 2033.12 | 0.00 |
April | 0.00 | 0.00 | 0.114689E+10 | 0.114689E+10 | 5222.62 | 28-APR-15:00 | 5222.62 | 0.00 |
May | 0.00 | 0.00 | 0.285632E+10 | 0.284033E+10 | 7154.62 | 19-MAY-15:00 | 7154.62 | 0.00 |
June | 0.00 | 0.00 | 0.643492E+10 | 0.633051E+10 | 19313.84 | 25-JUN-08:62 | 17716.46 | 0.00 |
July | 0.00 | 0.00 | 0.898056E+10 | 0.812469E+10 | 20430.73 | 16-JUL-08:62 | 13317.16 | 0.00 |
August | 0.00 | 0.00 | 0.836368E+10 | 0.753969E+10 | 20338.91 | 13-AUG-08:62 | 12254.37 | 0.00 |
September | 0.00 | 0.00 | 0.562471E+10 | 0.521175E+10 | 19414.19 | 04-SEP-08:62 | 14579.01 | 0.00 |
October | 0.00 | 0.00 | 0.211896E+10 | 0.202271E+10 | 13876.27 | 02-OCT-07:03 | 10893.22 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.355884E+11 | 0.332789E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.898056E+10 | 0.812469E+10 | 20430.73 | 17716.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 20630234.50 | 20630234.50 | 2005.34 | 14-FEB-16:00 | 2005.34 | 0.00 |
March | 0.00 | 0.00 | 33610808.32 | 33610808.32 | 1911.78 | 08-MAR-16:00 | 1911.78 | 0.00 |
April | 0.00 | 0.00 | 0.110467E+10 | 0.110467E+10 | 5144.84 | 28-APR-15:00 | 5144.84 | 0.00 |
May | 0.00 | 0.00 | 0.279991E+10 | 0.278452E+10 | 7096.02 | 19-MAY-15:00 | 7096.02 | 0.00 |
June | 0.00 | 0.00 | 0.637314E+10 | 0.627056E+10 | 19208.23 | 25-JUN-08:62 | 17612.86 | 0.00 |
July | 0.00 | 0.00 | 0.891111E+10 | 0.806339E+10 | 20319.74 | 16-JUL-08:62 | 13236.26 | 0.00 |
August | 0.00 | 0.00 | 0.829368E+10 | 0.747847E+10 | 20228.47 | 13-AUG-08:62 | 12179.19 | 0.00 |
September | 0.00 | 0.00 | 0.556470E+10 | 0.515744E+10 | 19308.38 | 04-SEP-08:62 | 14493.10 | 0.00 |
October | 0.00 | 0.00 | 0.208215E+10 | 0.198738E+10 | 13426.50 | 02-OCT-07:03 | 10527.06 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.351836E+11 | 0.329007E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.891111E+10 | 0.806339E+10 | 20319.74 | 17612.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 14511540.31 | 14511540.31 | 1702.42 | 14-FEB-16:00 | 1702.42 | 0.00 |
March | 0.00 | 0.00 | 22695421.23 | 22695421.23 | 1647.47 | 08-MAR-16:00 | 1647.47 | 0.00 |
April | 0.00 | 0.00 | 0.101493E+10 | 0.101493E+10 | 4987.34 | 28-APR-15:00 | 4987.34 | 0.00 |
May | 0.00 | 0.00 | 0.267147E+10 | 0.265756E+10 | 6989.09 | 19-MAY-15:00 | 6989.09 | 0.00 |
June | 0.00 | 0.00 | 0.627587E+10 | 0.617752E+10 | 19184.34 | 25-JUN-08:62 | 17569.17 | 0.00 |
July | 0.00 | 0.00 | 0.884686E+10 | 0.800843E+10 | 19959.72 | 25-JUL-07:02 | 13907.42 | 0.00 |
August | 0.00 | 0.00 | 0.822614E+10 | 0.742214E+10 | 20205.59 | 13-AUG-08:62 | 12145.22 | 0.00 |
September | 0.00 | 0.00 | 0.547392E+10 | 0.507723E+10 | 19285.89 | 04-SEP-08:62 | 14458.95 | 0.00 |
October | 0.00 | 0.00 | 0.201053E+10 | 0.191861E+10 | 12188.72 | 02-OCT-07:03 | 9517.24 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.345569E+11 | 0.323136E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.884686E+10 | 0.800843E+10 | 20205.59 | 17569.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 6232963.03 | 6232963.03 | 1199.88 | 14-FEB-16:00 | 1199.88 | 0.00 |
March | 0.00 | 0.00 | 12628539.88 | 12628539.88 | 1285.10 | 08-MAR-14:00 | 1285.10 | 0.00 |
April | 0.00 | 0.00 | 0.981184E+09 | 0.981184E+09 | 5110.79 | 28-APR-13:00 | 5110.79 | 0.00 |
May | 0.00 | 0.00 | 0.271474E+10 | 0.270045E+10 | 7214.47 | 19-MAY-15:00 | 7214.47 | 0.00 |
June | 0.00 | 0.00 | 0.681604E+10 | 0.671370E+10 | 21022.12 | 25-JUN-08:62 | 19225.41 | 0.00 |
July | 0.00 | 0.00 | 0.976391E+10 | 0.884662E+10 | 21895.90 | 04-JUL-08:62 | 17092.28 | 0.00 |
August | 0.00 | 0.00 | 0.909209E+10 | 0.821276E+10 | 22152.99 | 13-AUG-08:62 | 13228.91 | 0.00 |
September | 0.00 | 0.00 | 0.592005E+10 | 0.550320E+10 | 20668.12 | 03-SEP-08:62 | 19952.03 | 0.00 |
October | 0.00 | 0.00 | 0.206525E+10 | 0.196912E+10 | 8592.86 | 02-OCT-14:30 | 7977.25 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.373721E+11 | 0.349459E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.976391E+10 | 0.884662E+10 | 22152.99 | 19952.03 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205111E+10 | 0.46 | 2599.88 | 05-JAN-08:61 | 1.07 |
February | 0.182014E+10 | 0.46 | 2599.88 | 01-FEB-08:61 | 1.07 |
March | 0.192195E+10 | 0.44 | 2599.88 | 01-MAR-08:61 | 1.07 |
April | 0.182910E+10 | 0.44 | 1654.13 | 08-APR-07:01 | 0.86 |
May | 0.188701E+10 | 0.44 | 1096.12 | 06-MAY-08:15 | 0.67 |
June | 0.186711E+10 | 0.44 | 2599.88 | 27-JUN-07:02 | 1.06 |
July | 0.193311E+10 | 0.44 | 2599.88 | 04-JUL-07:02 | 1.05 |
August | 0.190929E+10 | 0.44 | 2599.88 | 06-AUG-07:02 | 1.06 |
September | 0.183179E+10 | 0.44 | 2438.45 | 03-SEP-07:02 | 1.03 |
October | 0.189521E+10 | 0.44 | 2218.90 | 26-OCT-07:01 | 0.99 |
November | 0.184216E+10 | 0.44 | 2599.88 | 27-NOV-08:61 | 1.07 |
December | 0.206880E+10 | 0.47 | 2599.88 | 04-DEC-08:61 | 1.07 |
Annual Sum or Average | 0.228568E+11 | 0.45 | |||
Minimum of Months | 0.182014E+10 | 0.44 | 1096.12 | 0.67 | |
Maximum of Months | 0.206880E+10 | 0.47 | 2599.88 | 1.07 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.819599E+09 | 0.38 | 1438.11 | 17-JAN-08:61 | 1.10 |
February | 0.758369E+09 | 0.40 | 1438.11 | 03-FEB-08:61 | 1.10 |
March | 0.889564E+09 | 0.44 | 1216.99 | 04-MAR-08:61 | 1.02 |
April | 0.924670E+09 | 0.44 | 597.14 | 08-APR-08:40 | 0.69 |
May | 0.941996E+09 | 0.43 | 575.24 | 02-MAY-14:10 | 0.67 |
June | 0.923043E+09 | 0.44 | 1438.11 | 26-JUN-07:02 | 1.10 |
July | 0.945911E+09 | 0.45 | 1438.11 | 04-JUL-07:02 | 1.09 |
August | 0.938882E+09 | 0.44 | 1438.11 | 02-AUG-07:02 | 1.10 |
September | 0.897690E+09 | 0.42 | 1425.37 | 03-SEP-07:02 | 1.09 |
October | 0.958072E+09 | 0.44 | 802.36 | 02-OCT-07:03 | 0.82 |
November | 0.835451E+09 | 0.44 | 699.50 | 27-NOV-09:10 | 0.76 |
December | 0.817984E+09 | 0.37 | 1438.11 | 08-DEC-08:61 | 1.10 |
Annual Sum or Average | 0.106512E+11 | 0.42 | |||
Minimum of Months | 0.758369E+09 | 0.37 | 575.24 | 0.67 | |
Maximum of Months | 0.958072E+09 | 0.45 | 1438.11 | 1.10 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.929727E+09 | 0.38 | 1516.92 | 17-JAN-07:01 | 1.11 |
February | 0.828576E+09 | 0.37 | 1516.92 | 05-FEB-08:61 | 1.11 |
March | 0.901227E+09 | 0.37 | 1136.22 | 04-MAR-07:02 | 0.97 |
April | 0.852128E+09 | 0.36 | 718.89 | 08-APR-07:08 | 0.75 |
May | 0.886850E+09 | 0.36 | 606.77 | 02-MAY-12:40 | 0.67 |
June | 0.873679E+09 | 0.37 | 1516.92 | 24-JUN-06:02 | 1.09 |
July | 0.885389E+09 | 0.36 | 1516.92 | 01-JUL-06:02 | 1.09 |
August | 0.898702E+09 | 0.37 | 1516.92 | 01-AUG-06:02 | 1.09 |
September | 0.852539E+09 | 0.36 | 1516.92 | 03-SEP-07:02 | 1.10 |
October | 0.880857E+09 | 0.36 | 1394.32 | 02-OCT-06:02 | 1.06 |
November | 0.855824E+09 | 0.36 | 791.67 | 27-NOV-08:03 | 0.79 |
December | 0.932903E+09 | 0.38 | 1437.58 | 22-DEC-07:02 | 1.08 |
Annual Sum or Average | 0.105784E+11 | 0.37 | |||
Minimum of Months | 0.828576E+09 | 0.36 | 606.77 | 0.67 | |
Maximum of Months | 0.932903E+09 | 0.38 | 1516.92 | 1.11 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.929972E+09 | 0.38 | 1508.39 | 17-JAN-07:01 | 1.11 |
February | 0.827821E+09 | 0.37 | 1508.39 | 04-FEB-07:02 | 1.11 |
March | 0.897796E+09 | 0.37 | 1237.30 | 05-MAR-08:62 | 1.01 |
April | 0.847470E+09 | 0.36 | 727.80 | 08-APR-07:06 | 0.76 |
May | 0.881868E+09 | 0.36 | 603.36 | 08-MAY-10:00 | 0.67 |
June | 0.869432E+09 | 0.37 | 1508.39 | 24-JUN-06:02 | 1.09 |
July | 0.881281E+09 | 0.36 | 1508.39 | 01-JUL-06:02 | 1.09 |
August | 0.893981E+09 | 0.37 | 1508.39 | 01-AUG-06:02 | 1.09 |
September | 0.847799E+09 | 0.36 | 1508.39 | 03-SEP-07:02 | 1.10 |
October | 0.876253E+09 | 0.36 | 1470.48 | 02-OCT-06:02 | 1.08 |
November | 0.852658E+09 | 0.36 | 811.73 | 28-NOV-07:03 | 0.81 |
December | 0.933877E+09 | 0.38 | 1508.39 | 22-DEC-07:02 | 1.11 |
Annual Sum or Average | 0.105402E+11 | 0.37 | |||
Minimum of Months | 0.827821E+09 | 0.36 | 603.36 | 0.67 | |
Maximum of Months | 0.933877E+09 | 0.38 | 1508.39 | 1.11 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.937491E+09 | 0.38 | 1508.08 | 17-JAN-07:01 | 1.11 |
February | 0.833530E+09 | 0.38 | 1508.08 | 04-FEB-07:02 | 1.11 |
March | 0.900377E+09 | 0.37 | 1370.37 | 05-MAR-08:62 | 1.06 |
April | 0.847702E+09 | 0.36 | 731.14 | 08-APR-07:05 | 0.76 |
May | 0.881682E+09 | 0.36 | 603.23 | 20-MAY-06:05 | 0.67 |
June | 0.868083E+09 | 0.37 | 1508.08 | 28-JUN-06:02 | 1.10 |
July | 0.879548E+09 | 0.36 | 1508.08 | 01-JUL-06:02 | 1.09 |
August | 0.893272E+09 | 0.37 | 1508.08 | 01-AUG-06:02 | 1.09 |
September | 0.847491E+09 | 0.36 | 1508.08 | 03-SEP-07:02 | 1.10 |
October | 0.876614E+09 | 0.36 | 1365.70 | 02-OCT-06:02 | 1.05 |
November | 0.855016E+09 | 0.37 | 876.20 | 27-NOV-07:03 | 0.84 |
December | 0.942042E+09 | 0.38 | 1508.08 | 09-DEC-07:02 | 1.10 |
Annual Sum or Average | 0.105628E+11 | 0.37 | |||
Minimum of Months | 0.833530E+09 | 0.36 | 603.23 | 0.67 | |
Maximum of Months | 0.942042E+09 | 0.38 | 1508.08 | 1.11 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143868E+10 | 0.34 | 2449.30 | 02-JAN-08:61 | 1.07 |
February | 0.127361E+10 | 0.34 | 2449.30 | 01-FEB-08:61 | 1.07 |
March | 0.135953E+10 | 0.33 | 2449.30 | 01-MAR-08:61 | 1.07 |
April | 0.127194E+10 | 0.32 | 1512.17 | 08-APR-07:01 | 0.84 |
May | 0.132270E+10 | 0.33 | 1026.90 | 06-MAY-08:30 | 0.67 |
June | 0.131916E+10 | 0.33 | 2449.30 | 25-JUN-08:62 | 1.06 |
July | 0.134369E+10 | 0.32 | 2449.30 | 04-JUL-08:62 | 1.05 |
August | 0.135331E+10 | 0.33 | 2449.30 | 02-AUG-07:02 | 1.06 |
September | 0.127092E+10 | 0.32 | 2449.30 | 03-SEP-08:62 | 1.06 |
October | 0.131633E+10 | 0.32 | 1997.79 | 26-OCT-07:01 | 0.97 |
November | 0.129169E+10 | 0.33 | 2449.30 | 27-NOV-08:61 | 1.07 |
December | 0.145047E+10 | 0.34 | 2449.30 | 04-DEC-08:61 | 1.07 |
Annual Sum or Average | 0.160120E+11 | 0.33 | |||
Minimum of Months | 0.127092E+10 | 0.32 | 1026.90 | 0.67 | |
Maximum of Months | 0.145047E+10 | 0.34 | 2449.30 | 1.07 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.773898E+09 | 0.36 | 1313.95 | 02-JAN-08:61 | 1.11 |
February | 0.684804E+09 | 0.35 | 1313.95 | 01-FEB-08:61 | 1.11 |
March | 0.730173E+09 | 0.35 | 1313.95 | 01-MAR-08:61 | 1.11 |
April | 0.682460E+09 | 0.34 | 874.82 | 08-APR-07:01 | 0.91 |
May | 0.709580E+09 | 0.34 | 559.86 | 06-MAY-08:15 | 0.70 |
June | 0.707729E+09 | 0.34 | 1313.95 | 25-JUN-08:62 | 1.09 |
July | 0.720824E+09 | 0.33 | 1313.95 | 04-JUL-08:62 | 1.09 |
August | 0.725938E+09 | 0.34 | 1313.95 | 06-AUG-08:62 | 1.09 |
September | 0.681732E+09 | 0.33 | 1313.95 | 03-SEP-08:62 | 1.10 |
October | 0.706164E+09 | 0.33 | 1080.42 | 26-OCT-07:01 | 1.01 |
November | 0.693547E+09 | 0.34 | 1313.95 | 27-NOV-08:61 | 1.11 |
December | 0.779791E+09 | 0.36 | 1313.95 | 04-DEC-08:61 | 1.10 |
Annual Sum or Average | 0.859664E+10 | 0.34 | |||
Minimum of Months | 0.681732E+09 | 0.33 | 559.86 | 0.70 | |
Maximum of Months | 0.779791E+09 | 0.36 | 1313.95 | 1.11 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.773061E+09 | 0.36 | 1306.87 | 01-JAN-09:01 | 1.11 |
February | 0.683740E+09 | 0.35 | 1306.87 | 01-FEB-08:61 | 1.11 |
March | 0.727881E+09 | 0.35 | 1306.87 | 01-MAR-08:61 | 1.11 |
April | 0.679133E+09 | 0.34 | 969.82 | 08-APR-07:01 | 0.96 |
May | 0.705794E+09 | 0.34 | 571.17 | 06-MAY-08:15 | 0.71 |
June | 0.703889E+09 | 0.34 | 1306.87 | 25-JUN-08:62 | 1.09 |
July | 0.716896E+09 | 0.33 | 1306.87 | 04-JUL-08:62 | 1.09 |
August | 0.721970E+09 | 0.34 | 1306.87 | 06-AUG-08:62 | 1.09 |
September | 0.678034E+09 | 0.33 | 1306.87 | 03-SEP-08:62 | 1.10 |
October | 0.702639E+09 | 0.33 | 1118.32 | 26-OCT-07:01 | 1.03 |
November | 0.691558E+09 | 0.34 | 1306.87 | 27-NOV-08:61 | 1.11 |
December | 0.778927E+09 | 0.36 | 1306.87 | 04-DEC-08:61 | 1.10 |
Annual Sum or Average | 0.856352E+10 | 0.34 | |||
Minimum of Months | 0.678034E+09 | 0.33 | 571.17 | 0.71 | |
Maximum of Months | 0.778927E+09 | 0.36 | 1306.87 | 1.11 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.782870E+09 | 0.36 | 1305.61 | 01-JAN-09:01 | 1.11 |
February | 0.691821E+09 | 0.35 | 1305.61 | 01-FEB-08:61 | 1.11 |
March | 0.732677E+09 | 0.35 | 1305.61 | 01-MAR-08:61 | 1.11 |
April | 0.679624E+09 | 0.34 | 1272.56 | 08-APR-07:01 | 1.09 |
May | 0.705262E+09 | 0.34 | 602.28 | 05-MAY-08:10 | 0.73 |
June | 0.702726E+09 | 0.34 | 1305.61 | 25-JUN-08:62 | 1.09 |
July | 0.715724E+09 | 0.33 | 1305.61 | 04-JUL-08:62 | 1.09 |
August | 0.721041E+09 | 0.34 | 1305.61 | 06-AUG-08:62 | 1.09 |
September | 0.677292E+09 | 0.33 | 1305.61 | 03-SEP-08:62 | 1.10 |
October | 0.702919E+09 | 0.33 | 1302.09 | 26-OCT-07:01 | 1.10 |
November | 0.695767E+09 | 0.34 | 1305.61 | 13-NOV-08:61 | 1.11 |
December | 0.788521E+09 | 0.36 | 1305.61 | 03-DEC-09:01 | 1.11 |
Annual Sum or Average | 0.859624E+10 | 0.34 | |||
Minimum of Months | 0.677292E+09 | 0.33 | 602.28 | 0.73 | |
Maximum of Months | 0.788521E+09 | 0.36 | 1305.61 | 1.11 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.882526E+09 | 0.37 | 1430.04 | 01-JAN-09:01 | 1.11 |
February | 0.779358E+09 | 0.36 | 1430.04 | 01-FEB-08:61 | 1.11 |
March | 0.817765E+09 | 0.35 | 1430.04 | 01-MAR-08:61 | 1.11 |
April | 0.747576E+09 | 0.34 | 1430.04 | 01-APR-07:02 | 1.11 |
May | 0.772936E+09 | 0.34 | 1039.46 | 06-MAY-07:03 | 0.95 |
June | 0.767401E+09 | 0.34 | 1430.04 | 25-JUN-08:62 | 1.09 |
July | 0.782815E+09 | 0.33 | 1430.04 | 04-JUL-08:62 | 1.09 |
August | 0.789284E+09 | 0.34 | 1430.04 | 06-AUG-08:62 | 1.09 |
September | 0.741751E+09 | 0.33 | 1430.04 | 03-SEP-08:62 | 1.10 |
October | 0.772421E+09 | 0.34 | 1430.04 | 26-OCT-07:01 | 1.11 |
November | 0.773145E+09 | 0.34 | 1430.04 | 05-NOV-08:62 | 1.10 |
December | 0.885439E+09 | 0.37 | 1430.04 | 01-DEC-08:62 | 1.10 |
Annual Sum or Average | 0.951242E+10 | 0.35 | |||
Minimum of Months | 0.741751E+09 | 0.33 | 1039.46 | 0.95 | |
Maximum of Months | 0.885439E+09 | 0.37 | 1430.04 | 1.11 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.205111E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.183872E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.196496E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.265564E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.392967E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.642570E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.827748E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.755712E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.546923E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.324698E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.184217E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.206880E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.473276E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.183872E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.827748E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.820659E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.777438E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.944804E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153740E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.226923E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.348479E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.442503E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.407881E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.311102E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.182433E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.839357E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.818411E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.249313E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.777438E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.442503E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.929727E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.841501E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.927526E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.178396E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.285590E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.353718E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.329118E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.247215E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151162E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.856063E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.932903E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.211993E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.841501E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.353718E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.929972E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.839087E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.919957E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.124283E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.177360E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.285427E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.354058E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.329323E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.247102E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.150303E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.852760E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.933877E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.211542E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.839087E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.354058E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.937491E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.842498E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.916346E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.121471E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.173834E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.281010E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.349409E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.324914E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.243241E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.147895E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.855016E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.942042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209111E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.842498E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.349409E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.143868E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128704E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.138381E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.187052E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.279378E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.475577E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.595755E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.554226E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.404500E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.235845E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.129169E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145047E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.341750E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.128704E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.595755E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.773898E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.691150E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.740845E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.983847E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.146242E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.247548E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.309831E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.288330E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.210903E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.124158E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.693547E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.779791E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179332E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.691150E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.309831E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.773061E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.689358E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.737110E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.969972E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.144474E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.245571E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.307681E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.286210E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.209092E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.122913E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.691558E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.778927E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.177994E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.689358E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.307681E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.782870E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.695803E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.738950E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.948199E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.141337E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.243114E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.306087E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.284571E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.206952E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.121235E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.695767E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.788521E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176831E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.695767E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.306087E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.882526E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.781092E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.821309E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.100947E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.149852E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.264547E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.336775E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.313332E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.224900E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.129762E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.773145E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.885439E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.193447E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.773145E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.336775E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.205111E+10 | 0.00 | 0.604458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182014E+10 | 69081974.13 | 0.415165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192195E+10 | 0.158556E+09 | 0.101742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182910E+10 | 0.317927E+10 | 77727490.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188701E+10 | 0.782756E+10 | 4243548.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186711E+10 | 0.168233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193311E+10 | 0.241400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190929E+10 | 0.219966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183179E+10 | 0.144025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189521E+10 | 0.536352E+10 | 0.304791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184216E+10 | 24538.67 | 0.697948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206880E+10 | 0.00 | 0.643331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228568E+11 | 0.939604E+11 | 0.187317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.182014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206880E+10 | 0.241400E+11 | 0.643331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.819599E+09 | 3887964.96 | 0.115111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.758369E+09 | 72196291.89 | 0.705991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.889564E+09 | 0.203608E+09 | 68038519.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.924670E+09 | 0.230143E+10 | 1325350.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.941996E+09 | 0.494158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.923043E+09 | 0.931048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.945911E+09 | 0.130264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.938882E+09 | 0.119941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.897690E+09 | 0.849668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.958072E+09 | 0.334675E+10 | 47760565.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.835451E+09 | 14707197.78 | 28749410.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.817984E+09 | 1550454.97 | 0.126277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106512E+11 | 0.537134E+11 | 0.326575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.758369E+09 | 1550454.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.958072E+09 | 0.130264E+11 | 0.126277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.929727E+09 | 0.00 | 0.179772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.828576E+09 | 48288683.37 | 0.116574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.901227E+09 | 97217884.49 | 0.196421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.852128E+09 | 0.156414E+10 | 7938807.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.886850E+09 | 0.341669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.873679E+09 | 0.721177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.885389E+09 | 0.996737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.898702E+09 | 0.921664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.852539E+09 | 0.634389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.880857E+09 | 0.248345E+10 | 90358340.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.855824E+09 | 863336.66 | 0.136667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.932903E+09 | 0.00 | 0.206051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105784E+11 | 0.403503E+11 | 0.545536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.828576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.932903E+09 | 0.996737E+10 | 0.206051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.929972E+09 | 0.00 | 0.198017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827821E+09 | 41898115.60 | 0.129638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.897796E+09 | 81649732.16 | 0.252444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.847470E+09 | 0.151560E+10 | 12388329.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.881868E+09 | 0.339652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.869432E+09 | 0.723029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.881281E+09 | 0.100125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.893981E+09 | 0.925802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.847799E+09 | 0.636617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876253E+09 | 0.246987E+10 | 0.101056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.852658E+09 | 364239.54 | 0.193282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.933877E+09 | 0.00 | 0.226779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105402E+11 | 0.403729E+11 | 0.610351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.827821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.933877E+09 | 0.100125E+11 | 0.226779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.937491E+09 | 0.00 | 0.224886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.833530E+09 | 33107247.23 | 0.150131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.900377E+09 | 58530920.79 | 0.349010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.847702E+09 | 0.139971E+10 | 26727680.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.881682E+09 | 0.324816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.868083E+09 | 0.704697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.879548E+09 | 0.981158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.893272E+09 | 0.905886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.847491E+09 | 0.619281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876614E+09 | 0.236629E+10 | 0.121793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.855016E+09 | 962.38 | 0.281752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.942042E+09 | 0.00 | 0.255899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105628E+11 | 0.392160E+11 | 0.708845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.833530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.942042E+09 | 0.981158E+10 | 0.255899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143868E+10 | 0.00 | 0.486399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127361E+10 | 49537528.16 | 0.330861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135953E+10 | 88874001.26 | 0.852123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127194E+10 | 0.228069E+10 | 82984274.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132270E+10 | 0.558574E+10 | 2991892.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131916E+10 | 0.125228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134369E+10 | 0.174466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135331E+10 | 0.162554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127092E+10 | 0.109383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131633E+10 | 0.412439E+10 | 0.285417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129169E+10 | 0.00 | 0.821193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145047E+10 | 0.00 | 0.556831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160120E+11 | 0.692924E+11 | 0.157856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145047E+10 | 0.174466E+11 | 0.556831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.773898E+09 | 0.00 | 0.253880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.684804E+09 | 23376154.18 | 0.173162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.730173E+09 | 38965237.73 | 0.461430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.682460E+09 | 0.114689E+10 | 46274873.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.709580E+09 | 0.285632E+10 | 1730320.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.707729E+09 | 0.643492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.720824E+09 | 0.898056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.725938E+09 | 0.836368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.681732E+09 | 0.562471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.706164E+09 | 0.211896E+10 | 0.146232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.693547E+09 | 0.00 | 0.437543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.779791E+09 | 0.00 | 0.288036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.859664E+10 | 0.355884E+11 | 0.824399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.681732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.779791E+09 | 0.898056E+10 | 0.288036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.773061E+09 | 0.00 | 0.264630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.683740E+09 | 20630234.50 | 0.181736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.727881E+09 | 33610808.32 | 0.517467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679133E+09 | 0.110467E+10 | 58294601.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.705794E+09 | 0.279991E+10 | 2901507.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.703889E+09 | 0.637314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.716896E+09 | 0.891111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.721970E+09 | 0.829368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.678034E+09 | 0.556470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.702639E+09 | 0.208215E+10 | 0.155573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.691558E+09 | 0.00 | 0.497433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.778927E+09 | 0.00 | 0.298665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.856352E+10 | 0.351836E+11 | 0.868197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.678034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.778927E+09 | 0.891111E+10 | 0.298665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.782870E+09 | 0.00 | 0.301003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.691821E+09 | 14511540.31 | 0.211978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.732677E+09 | 22695421.23 | 0.709789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679624E+09 | 0.101493E+10 | 98673462.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.705262E+09 | 0.267147E+10 | 8301456.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.702726E+09 | 0.627587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.715724E+09 | 0.884686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.721041E+09 | 0.822614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.677292E+09 | 0.547392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.702919E+09 | 0.201053E+10 | 0.189541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695767E+09 | 0.00 | 0.667868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.788521E+09 | 0.00 | 0.334185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.859624E+10 | 0.345569E+11 | 0.101458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.677292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.788521E+09 | 0.884686E+10 | 0.334185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.882526E+09 | 0.00 | 0.417584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.779358E+09 | 6232963.03 | 0.307955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.817765E+09 | 12628539.88 | 0.131418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.747576E+09 | 0.981184E+09 | 0.219947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.772936E+09 | 0.271474E+10 | 25174091.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.767401E+09 | 0.681604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.782815E+09 | 0.976391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789284E+09 | 0.909209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.741751E+09 | 0.592005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.772421E+09 | 0.206525E+10 | 0.297182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.773145E+09 | 0.00 | 0.112066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.885439E+09 | 0.00 | 0.442353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.951242E+10 | 0.373721E+11 | 0.146561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.741751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.885439E+09 | 0.976391E+10 | 0.442353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.205111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182014E+10 | 0.00 | 0.00 | 0.00 | 18587108.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192195E+10 | 0.00 | 0.00 | 0.00 | 43011382.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182910E+10 | 0.00 | 0.00 | 0.00 | 0.826544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188701E+10 | 0.00 | 0.00 | 0.00 | 0.204266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186711E+10 | 0.00 | 0.00 | 0.00 | 0.455858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193311E+10 | 0.00 | 0.00 | 0.00 | 0.634437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190929E+10 | 0.00 | 0.00 | 0.00 | 0.564783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183179E+10 | 0.00 | 0.00 | 0.00 | 0.363744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189521E+10 | 0.00 | 0.00 | 0.00 | 0.135177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184216E+10 | 0.00 | 0.00 | 0.00 | 6914.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228568E+11 | 0.00 | 0.00 | 0.00 | 0.244708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.182014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206880E+10 | 0.00 | 0.00 | 0.00 | 0.634437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.819599E+09 | 0.00 | 0.00 | 0.00 | 1059765.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.758369E+09 | 0.00 | 0.00 | 0.00 | 19068650.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.889564E+09 | 0.00 | 0.00 | 0.00 | 55240097.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.924670E+09 | 0.00 | 0.00 | 0.00 | 0.612731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.941996E+09 | 0.00 | 0.00 | 0.00 | 0.132724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.923043E+09 | 0.00 | 0.00 | 0.00 | 0.256175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.945911E+09 | 0.00 | 0.00 | 0.00 | 0.347912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.938882E+09 | 0.00 | 0.00 | 0.00 | 0.313992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.897690E+09 | 0.00 | 0.00 | 0.00 | 0.221333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.958072E+09 | 0.00 | 0.00 | 0.00 | 0.866254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.835451E+09 | 0.00 | 0.00 | 0.00 | 3906540.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.817984E+09 | 0.00 | 0.00 | 0.00 | 427142.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106512E+11 | 0.00 | 0.00 | 0.00 | 0.142801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.758369E+09 | 0.00 | 0.00 | 0.00 | 427142.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.958072E+09 | 0.00 | 0.00 | 0.00 | 0.347912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.929727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.828576E+09 | 0.00 | 0.00 | 0.00 | 12924631.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.901227E+09 | 0.00 | 0.00 | 0.00 | 26298963.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.852128E+09 | 0.00 | 0.00 | 0.00 | 0.407496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.886850E+09 | 0.00 | 0.00 | 0.00 | 0.897113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.873679E+09 | 0.00 | 0.00 | 0.00 | 0.198222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.885389E+09 | 0.00 | 0.00 | 0.00 | 0.265179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.898702E+09 | 0.00 | 0.00 | 0.00 | 0.239248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.852539E+09 | 0.00 | 0.00 | 0.00 | 0.161961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.880857E+09 | 0.00 | 0.00 | 0.00 | 0.630762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.855824E+09 | 0.00 | 0.00 | 0.00 | 238721.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.932903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105784E+11 | 0.00 | 0.00 | 0.00 | 0.106209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.828576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.932903E+09 | 0.00 | 0.00 | 0.00 | 0.265179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.929972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827821E+09 | 0.00 | 0.00 | 0.00 | 11266178.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.897796E+09 | 0.00 | 0.00 | 0.00 | 22160582.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.847470E+09 | 0.00 | 0.00 | 0.00 | 0.395357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.881868E+09 | 0.00 | 0.00 | 0.00 | 0.891728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.869432E+09 | 0.00 | 0.00 | 0.00 | 0.198484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.881281E+09 | 0.00 | 0.00 | 0.00 | 0.265930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.893981E+09 | 0.00 | 0.00 | 0.00 | 0.239925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.847799E+09 | 0.00 | 0.00 | 0.00 | 0.162322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876253E+09 | 0.00 | 0.00 | 0.00 | 0.626780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.852658E+09 | 0.00 | 0.00 | 0.00 | 101681.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.933877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105402E+11 | 0.00 | 0.00 | 0.00 | 0.106140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.827821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.933877E+09 | 0.00 | 0.00 | 0.00 | 0.265930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.937491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.833530E+09 | 0.00 | 0.00 | 0.00 | 8968383.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.900377E+09 | 0.00 | 0.00 | 0.00 | 15968137.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.847702E+09 | 0.00 | 0.00 | 0.00 | 0.367012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.881682E+09 | 0.00 | 0.00 | 0.00 | 0.856663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.868083E+09 | 0.00 | 0.00 | 0.00 | 0.194202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.879548E+09 | 0.00 | 0.00 | 0.00 | 0.261454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.893272E+09 | 0.00 | 0.00 | 0.00 | 0.235587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.847491E+09 | 0.00 | 0.00 | 0.00 | 0.158491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876614E+09 | 0.00 | 0.00 | 0.00 | 0.602337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.855016E+09 | 0.00 | 0.00 | 0.00 | 271.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.942042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105628E+11 | 0.00 | 0.00 | 0.00 | 0.103483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.833530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.942042E+09 | 0.00 | 0.00 | 0.00 | 0.261454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127361E+10 | 0.00 | 0.00 | 0.00 | 13429988.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135953E+10 | 0.00 | 0.00 | 0.00 | 24278707.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127194E+10 | 0.00 | 0.00 | 0.00 | 0.598586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132270E+10 | 0.00 | 0.00 | 0.00 | 0.147108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131916E+10 | 0.00 | 0.00 | 0.00 | 0.343661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134369E+10 | 0.00 | 0.00 | 0.00 | 0.461387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135331E+10 | 0.00 | 0.00 | 0.00 | 0.418895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127092E+10 | 0.00 | 0.00 | 0.00 | 0.277408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131633E+10 | 0.00 | 0.00 | 0.00 | 0.104212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160120E+11 | 0.00 | 0.00 | 0.00 | 0.181630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145047E+10 | 0.00 | 0.00 | 0.00 | 0.461387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.773898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.684804E+09 | 0.00 | 0.00 | 0.00 | 6346477.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.730173E+09 | 0.00 | 0.00 | 0.00 | 10671647.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.682460E+09 | 0.00 | 0.00 | 0.00 | 0.301386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.709580E+09 | 0.00 | 0.00 | 0.00 | 0.752839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.707729E+09 | 0.00 | 0.00 | 0.00 | 0.176775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.720824E+09 | 0.00 | 0.00 | 0.00 | 0.237749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.725938E+09 | 0.00 | 0.00 | 0.00 | 0.215737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.681732E+09 | 0.00 | 0.00 | 0.00 | 0.142730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.706164E+09 | 0.00 | 0.00 | 0.00 | 0.535419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.693547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.779791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.859664E+10 | 0.00 | 0.00 | 0.00 | 0.933656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.681732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.779791E+09 | 0.00 | 0.00 | 0.00 | 0.237749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.773061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.683740E+09 | 0.00 | 0.00 | 0.00 | 5618079.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.727881E+09 | 0.00 | 0.00 | 0.00 | 9229404.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679133E+09 | 0.00 | 0.00 | 0.00 | 0.290839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.705794E+09 | 0.00 | 0.00 | 0.00 | 0.738942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.703889E+09 | 0.00 | 0.00 | 0.00 | 0.175182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.716896E+09 | 0.00 | 0.00 | 0.00 | 0.235992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.721970E+09 | 0.00 | 0.00 | 0.00 | 0.214013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.678034E+09 | 0.00 | 0.00 | 0.00 | 0.141288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.702639E+09 | 0.00 | 0.00 | 0.00 | 0.526490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.691558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.778927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.856352E+10 | 0.00 | 0.00 | 0.00 | 0.923587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.678034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.778927E+09 | 0.00 | 0.00 | 0.00 | 0.235992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.782870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.691821E+09 | 0.00 | 0.00 | 0.00 | 3982505.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.732677E+09 | 0.00 | 0.00 | 0.00 | 6273199.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679624E+09 | 0.00 | 0.00 | 0.00 | 0.268575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.705262E+09 | 0.00 | 0.00 | 0.00 | 0.708104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.702726E+09 | 0.00 | 0.00 | 0.00 | 0.172841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.715724E+09 | 0.00 | 0.00 | 0.00 | 0.234515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.721041E+09 | 0.00 | 0.00 | 0.00 | 0.212467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.677292E+09 | 0.00 | 0.00 | 0.00 | 0.139222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.702919E+09 | 0.00 | 0.00 | 0.00 | 0.509428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.788521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.859624E+10 | 0.00 | 0.00 | 0.00 | 0.908682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.677292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.788521E+09 | 0.00 | 0.00 | 0.00 | 0.234515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.882526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.779358E+09 | 0.00 | 0.00 | 0.00 | 1734635.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.817765E+09 | 0.00 | 0.00 | 0.00 | 3544226.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.747576E+09 | 0.00 | 0.00 | 0.00 | 0.261895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.772936E+09 | 0.00 | 0.00 | 0.00 | 0.725585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.767401E+09 | 0.00 | 0.00 | 0.00 | 0.187807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.782815E+09 | 0.00 | 0.00 | 0.00 | 0.258493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789284E+09 | 0.00 | 0.00 | 0.00 | 0.234403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.741751E+09 | 0.00 | 0.00 | 0.00 | 0.150725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.772421E+09 | 0.00 | 0.00 | 0.00 | 0.525197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.773145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.885439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.951242E+10 | 0.00 | 0.00 | 0.00 | 0.983224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.741751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.885439E+09 | 0.00 | 0.00 | 0.00 | 0.258493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100687E+11 | 0.00 | 0.00 | 19747.68 | 0.00 | 0.218852E+10 | 29400436.88 | 0.00 | 0.52 |
February | 0.850588E+10 | 0.00 | 0.00 | 603636.28 | 0.00 | 0.123499E+10 | 0.543301E+09 | 0.00 | 0.55 |
March | 0.687350E+10 | 0.00 | 0.00 | 2415574.14 | 0.00 | 0.192419E+09 | 0.209722E+10 | 0.00 | 0.62 |
April | 0.270608E+10 | 6094211.46 | 0.00 | 13088824.68 | 0.00 | 9337511.54 | 0.475094E+10 | 0.00 | 0.87 |
May | 0.937827E+09 | 0.186225E+09 | 0.00 | 18321925.78 | 0.00 | 0.00 | 0.450614E+10 | 0.00 | 0.92 |
June | 94696389.40 | 0.205421E+10 | 0.00 | 11799563.53 | 124059.02 | 0.00 | 0.222894E+10 | 0.00 | 0.81 |
July | 15219.51 | 0.391313E+10 | 0.00 | 4716402.23 | 6998469.51 | 0.00 | 0.358154E+09 | 0.00 | 0.74 |
August | 126389.63 | 0.262814E+10 | 0.00 | 10499278.30 | 1111779.19 | 0.00 | 0.100491E+10 | 0.00 | 0.84 |
September | 4635684.42 | 0.653408E+09 | 0.00 | 24238369.58 | 0.00 | 0.00 | 0.392482E+10 | 0.00 | 1.04 |
October | 0.240737E+10 | 69665438.36 | 0.00 | 18260429.82 | 0.00 | 27859767.24 | 0.647326E+10 | 0.00 | 0.94 |
November | 0.836191E+10 | 0.00 | 0.00 | 1698758.15 | 0.00 | 26490980.19 | 0.184043E+10 | 0.00 | 0.54 |
December | 0.109486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197282E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.509093E+11 | 0.951087E+10 | 0.00 | 0.105663E+09 | 8234307.73 | 0.565245E+10 | 0.277575E+11 | 0.00 | 0.74 |
Minimum of Months | 15219.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.109486E+11 | 0.391313E+10 | 0.00 | 24238369.58 | 6998469.51 | 0.218852E+10 | 0.647326E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.380631E+10 | 0.00 | 0.00 | 257427.99 | 0.00 | 0.421594E+09 | 0.250037E+09 | 0.00 | 0.39 |
February | 0.318189E+10 | 0.00 | 0.00 | 910534.61 | 0.00 | 0.112803E+09 | 0.692361E+09 | 0.00 | 0.45 |
March | 0.192708E+10 | 0.00 | 0.00 | 2881467.56 | 0.00 | 3299331.60 | 0.234097E+10 | 0.00 | 0.61 |
April | 0.715819E+09 | 3390637.10 | 0.00 | 7373132.28 | 0.00 | 0.00 | 0.313781E+10 | 0.00 | 0.89 |
May | 0.224591E+09 | 93620557.24 | 0.00 | 8592101.85 | 0.00 | 0.00 | 0.256226E+10 | 0.00 | 0.88 |
June | 13187857.27 | 0.983660E+09 | 0.00 | 4983965.54 | 0.00 | 0.00 | 0.110820E+10 | 0.00 | 0.71 |
July | 0.00 | 0.196703E+10 | 0.00 | 578025.33 | 4830720.41 | 0.00 | 47354905.60 | 0.00 | 0.59 |
August | 108295.57 | 0.131672E+10 | 0.00 | 3460040.75 | 1253858.05 | 0.00 | 0.290967E+09 | 0.00 | 0.71 |
September | 1228245.90 | 0.341889E+09 | 0.00 | 9293217.05 | 0.00 | 0.00 | 0.153960E+10 | 0.00 | 0.91 |
October | 0.778955E+09 | 37413117.02 | 0.00 | 9316744.51 | 0.00 | 2388092.82 | 0.370576E+10 | 0.00 | 0.94 |
November | 0.242481E+10 | 0.00 | 0.00 | 2651036.27 | 0.00 | 2250045.38 | 0.225178E+10 | 0.00 | 0.50 |
December | 0.442484E+10 | 0.00 | 0.00 | 96028.08 | 0.00 | 0.244577E+09 | 74883719.22 | 0.00 | 0.38 |
Annual Sum or Average | 0.174988E+11 | 0.474373E+10 | 0.00 | 50393721.85 | 6084578.46 | 0.786912E+09 | 0.180020E+11 | 0.00 | 0.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 96028.08 | 0.00 | 0.00 | 47354905.60 | 0.00 | 0.38 |
Maximum of Months | 0.442484E+10 | 0.196703E+10 | 0.00 | 9316744.51 | 4830720.41 | 0.421594E+09 | 0.370576E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.370010E+10 | 0.00 | 0.00 | 56678.04 | 0.00 | 0.739465E+09 | 76842029.67 | 0.00 | 0.41 |
February | 0.314748E+10 | 0.00 | 0.00 | 419580.54 | 0.00 | 0.365597E+09 | 0.325255E+09 | 0.00 | 0.45 |
March | 0.231926E+10 | 0.00 | 0.00 | 1401380.99 | 0.00 | 47834316.55 | 0.127550E+10 | 0.00 | 0.55 |
April | 0.108550E+10 | 5086436.24 | 0.00 | 3686297.15 | 0.00 | 265151.21 | 0.177201E+10 | 0.00 | 0.72 |
May | 0.441608E+09 | 92598537.38 | 0.00 | 4418193.72 | 3956144.49 | 0.00 | 0.168045E+10 | 0.00 | 0.75 |
June | 58223308.04 | 0.946561E+09 | 0.00 | 2229478.10 | 41703257.10 | 0.00 | 0.748333E+09 | 0.00 | 0.67 |
July | 8465194.08 | 0.171102E+10 | 0.00 | 867090.03 | 63956954.76 | 0.00 | 84852703.26 | 0.00 | 0.58 |
August | 23372478.29 | 0.118209E+10 | 0.00 | 1946315.18 | 31722146.10 | 0.00 | 0.356490E+09 | 0.00 | 0.68 |
September | 87663041.03 | 0.334339E+09 | 0.00 | 4127607.85 | 3890792.84 | 0.00 | 0.107407E+10 | 0.00 | 0.76 |
October | 0.107591E+10 | 38154394.36 | 0.00 | 5027515.53 | 1685246.83 | 10249453.20 | 0.228317E+10 | 0.00 | 0.77 |
November | 0.285669E+10 | 0.00 | 0.00 | 1155034.36 | 0.00 | 13150960.39 | 0.112427E+10 | 0.00 | 0.45 |
December | 0.408364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764729E+09 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.188879E+11 | 0.430985E+10 | 0.00 | 25335171.50 | 0.146915E+09 | 0.194129E+10 | 0.108012E+11 | 0.00 | 0.60 |
Minimum of Months | 8465194.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.408364E+10 | 0.171102E+10 | 0.00 | 5027515.53 | 63956954.76 | 0.764729E+09 | 0.228317E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.356501E+10 | 0.00 | 0.00 | 23538.34 | 0.00 | 0.880090E+09 | 44720865.92 | 0.00 | 0.41 |
February | 0.309531E+10 | 0.00 | 0.00 | 365844.47 | 0.00 | 0.411446E+09 | 0.299244E+09 | 0.00 | 0.45 |
March | 0.236595E+10 | 0.00 | 0.00 | 1213131.61 | 0.00 | 69501335.76 | 0.112868E+10 | 0.00 | 0.54 |
April | 0.110867E+10 | 5072628.23 | 0.00 | 3506973.58 | 0.00 | 1302088.12 | 0.169014E+10 | 0.00 | 0.71 |
May | 0.452861E+09 | 92616941.40 | 0.00 | 4363096.70 | 3973862.64 | 0.00 | 0.164831E+10 | 0.00 | 0.75 |
June | 59429235.36 | 0.946950E+09 | 0.00 | 2233524.98 | 41640882.28 | 0.00 | 0.743946E+09 | 0.00 | 0.66 |
July | 8474898.89 | 0.171381E+10 | 0.00 | 889747.15 | 64385416.82 | 0.00 | 83926902.78 | 0.00 | 0.58 |
August | 23063021.12 | 0.118459E+10 | 0.00 | 1968650.90 | 31706545.32 | 0.00 | 0.353726E+09 | 0.00 | 0.68 |
September | 87524824.66 | 0.335224E+09 | 0.00 | 4156972.64 | 3886915.96 | 0.00 | 0.107079E+10 | 0.00 | 0.76 |
October | 0.110132E+10 | 38237165.93 | 0.00 | 4929336.68 | 1685072.07 | 12954329.69 | 0.221561E+10 | 0.00 | 0.77 |
November | 0.291224E+10 | 0.00 | 0.00 | 943065.35 | 0.00 | 31473440.44 | 0.962754E+09 | 0.00 | 0.44 |
December | 0.402193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816622E+09 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.188018E+11 | 0.431650E+10 | 0.00 | 24593882.40 | 0.147279E+09 | 0.222339E+10 | 0.102419E+11 | 0.00 | 0.60 |
Minimum of Months | 8474898.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.402193E+10 | 0.171381E+10 | 0.00 | 4929336.68 | 64385416.82 | 0.880090E+09 | 0.221561E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.335503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110823E+10 | 0.00 | 0.00 | 0.41 |
February | 0.297493E+10 | 0.00 | 0.00 | 284383.75 | 0.00 | 0.536222E+09 | 0.253341E+09 | 0.00 | 0.44 |
March | 0.243119E+10 | 0.00 | 0.00 | 926073.53 | 0.00 | 0.113072E+09 | 0.895517E+09 | 0.00 | 0.52 |
April | 0.119575E+10 | 5072039.43 | 0.00 | 3095482.82 | 0.00 | 2027389.26 | 0.148850E+10 | 0.00 | 0.69 |
May | 0.487059E+09 | 92492824.90 | 0.00 | 4027304.89 | 4096668.16 | 0.00 | 0.153395E+10 | 0.00 | 0.73 |
June | 67693670.23 | 0.945596E+09 | 0.00 | 2090181.36 | 42212227.78 | 0.00 | 0.711898E+09 | 0.00 | 0.66 |
July | 8393503.13 | 0.170214E+10 | 0.00 | 832146.41 | 63277553.91 | 0.00 | 84641316.06 | 0.00 | 0.58 |
August | 23000587.35 | 0.117411E+10 | 0.00 | 1869715.98 | 31856707.55 | 0.00 | 0.352884E+09 | 0.00 | 0.68 |
September | 89670339.36 | 0.331962E+09 | 0.00 | 3976191.29 | 3954402.56 | 0.00 | 0.105063E+10 | 0.00 | 0.76 |
October | 0.114792E+10 | 37526509.69 | 0.00 | 4606949.40 | 1717728.07 | 22770758.69 | 0.207462E+10 | 0.00 | 0.75 |
November | 0.303347E+10 | 0.00 | 0.00 | 655653.04 | 0.00 | 58057290.88 | 0.697471E+09 | 0.00 | 0.43 |
December | 0.388437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943795E+09 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.186985E+11 | 0.428890E+10 | 0.00 | 22364082.46 | 0.147115E+09 | 0.278417E+10 | 0.914345E+10 | 0.00 | 0.59 |
Minimum of Months | 8393503.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.388437E+10 | 0.170214E+10 | 0.00 | 4606949.40 | 63277553.91 | 0.110823E+10 | 0.207462E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.569127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249040E+10 | 0.00 | 0.00 | 0.38 |
February | 0.542426E+10 | 0.00 | 0.00 | 336452.71 | 0.00 | 0.112918E+10 | 0.325049E+09 | 0.00 | 0.40 |
March | 0.463242E+10 | 0.00 | 0.00 | 1133831.50 | 0.00 | 0.169951E+09 | 0.127805E+10 | 0.00 | 0.45 |
April | 0.212911E+10 | 298342.22 | 0.00 | 5395728.39 | 0.00 | 3908152.81 | 0.252837E+10 | 0.00 | 0.58 |
May | 0.823873E+09 | 75493004.86 | 0.00 | 7532011.08 | 4900956.68 | 0.00 | 0.254186E+10 | 0.00 | 0.61 |
June | 72827649.36 | 0.170576E+10 | 0.00 | 3340901.19 | 12309763.46 | 0.00 | 0.114115E+10 | 0.00 | 0.53 |
July | 3624413.53 | 0.305128E+10 | 0.00 | 590848.22 | 53735043.59 | 0.00 | 82454269.62 | 0.00 | 0.46 |
August | 3858559.31 | 0.204226E+10 | 0.00 | 2636083.31 | 24453619.74 | 0.00 | 0.410504E+09 | 0.00 | 0.56 |
September | 35144915.20 | 0.425191E+09 | 0.00 | 8471195.25 | 4299584.53 | 0.00 | 0.170939E+10 | 0.00 | 0.65 |
October | 0.200670E+10 | 30680944.18 | 0.00 | 8571267.71 | 2252291.19 | 16764819.87 | 0.353531E+10 | 0.00 | 0.63 |
November | 0.601206E+10 | 0.00 | 0.00 | 541540.76 | 0.00 | 89175137.74 | 0.695114E+09 | 0.00 | 0.39 |
December | 0.682826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209156E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.336634E+11 | 0.733096E+10 | 0.00 | 38549860.12 | 0.101951E+09 | 0.599094E+10 | 0.142473E+11 | 0.00 | 0.50 |
Minimum of Months | 3624413.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.682826E+10 | 0.305128E+10 | 0.00 | 8571267.71 | 53735043.59 | 0.249040E+10 | 0.353531E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.271858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135610E+10 | 0.00 | 0.00 | 0.38 |
February | 0.258579E+10 | 0.00 | 0.00 | 153946.99 | 0.00 | 0.684612E+09 | 0.150925E+09 | 0.00 | 0.40 |
March | 0.230690E+10 | 0.00 | 0.00 | 493617.91 | 0.00 | 0.118093E+09 | 0.575289E+09 | 0.00 | 0.44 |
April | 0.108436E+10 | 163064.02 | 0.00 | 2632559.92 | 0.00 | 3202646.34 | 0.121962E+10 | 0.00 | 0.58 |
May | 0.415196E+09 | 41339248.87 | 0.00 | 3716135.13 | 2584751.04 | 0.00 | 0.126309E+10 | 0.00 | 0.62 |
June | 39955298.40 | 0.865095E+09 | 0.00 | 1645495.07 | 6774835.66 | 0.00 | 0.572615E+09 | 0.00 | 0.54 |
July | 1793173.36 | 0.154228E+10 | 0.00 | 295226.14 | 28843906.75 | 0.00 | 43893258.50 | 0.00 | 0.47 |
August | 1904157.88 | 0.103517E+10 | 0.00 | 1316800.43 | 14135945.43 | 0.00 | 0.213581E+09 | 0.00 | 0.56 |
September | 17394819.29 | 0.219654E+09 | 0.00 | 4183431.36 | 2355195.93 | 0.00 | 0.875168E+09 | 0.00 | 0.66 |
October | 0.101250E+10 | 16504274.03 | 0.00 | 4277481.80 | 1216462.67 | 11497559.29 | 0.176861E+10 | 0.00 | 0.64 |
November | 0.302054E+10 | 0.00 | 0.00 | 238275.48 | 0.00 | 55491211.64 | 0.296222E+09 | 0.00 | 0.39 |
December | 0.323788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120903E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.164428E+11 | 0.372021E+10 | 0.00 | 18952970.23 | 55911097.48 | 0.343802E+10 | 0.697902E+10 | 0.00 | 0.50 |
Minimum of Months | 1793173.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.323788E+10 | 0.154228E+10 | 0.00 | 4277481.80 | 28843906.75 | 0.135610E+10 | 0.176861E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142989E+10 | 0.00 | 0.00 | 0.38 |
February | 0.252368E+10 | 0.00 | 0.00 | 136161.10 | 0.00 | 0.748661E+09 | 0.137271E+09 | 0.00 | 0.40 |
March | 0.230263E+10 | 0.00 | 0.00 | 428514.34 | 0.00 | 0.133148E+09 | 0.526753E+09 | 0.00 | 0.44 |
April | 0.111158E+10 | 161802.86 | 0.00 | 2483730.18 | 0.00 | 7251532.16 | 0.114755E+10 | 0.00 | 0.58 |
May | 0.422416E+09 | 41357906.80 | 0.00 | 3592181.02 | 2551309.93 | 0.00 | 0.122641E+10 | 0.00 | 0.61 |
June | 42600187.35 | 0.864681E+09 | 0.00 | 1604000.26 | 6830998.38 | 0.00 | 0.561487E+09 | 0.00 | 0.53 |
July | 1794969.01 | 0.153732E+10 | 0.00 | 289008.94 | 28702005.35 | 0.00 | 43958795.81 | 0.00 | 0.47 |
August | 1856289.23 | 0.103054E+10 | 0.00 | 1298756.38 | 14405595.45 | 0.00 | 0.212638E+09 | 0.00 | 0.56 |
September | 17466244.98 | 0.218494E+09 | 0.00 | 4117310.60 | 2366056.30 | 0.00 | 0.867027E+09 | 0.00 | 0.66 |
October | 0.101864E+10 | 16276406.76 | 0.00 | 4154368.24 | 1230150.32 | 18547192.01 | 0.172152E+10 | 0.00 | 0.64 |
November | 0.302564E+10 | 0.00 | 0.00 | 200214.59 | 0.00 | 69333521.92 | 0.252979E+09 | 0.00 | 0.38 |
December | 0.313797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130666E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.162445E+11 | 0.370883E+10 | 0.00 | 18304245.67 | 56086115.73 | 0.371350E+10 | 0.669759E+10 | 0.00 | 0.50 |
Minimum of Months | 1794969.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.313797E+10 | 0.153732E+10 | 0.00 | 4154368.24 | 28702005.35 | 0.142989E+10 | 0.172152E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172511E+10 | 0.00 | 0.00 | 0.38 |
February | 0.225262E+10 | 0.00 | 0.00 | 99940.16 | 0.00 | 0.101987E+10 | 0.111460E+09 | 0.00 | 0.39 |
March | 0.225158E+10 | 0.00 | 0.00 | 291564.09 | 0.00 | 0.239391E+09 | 0.389639E+09 | 0.00 | 0.42 |
April | 0.117222E+10 | 161499.21 | 0.00 | 2179878.40 | 0.00 | 19019742.09 | 0.991422E+09 | 0.00 | 0.56 |
May | 0.455797E+09 | 41319314.81 | 0.00 | 3275760.51 | 2608870.69 | 1491810.14 | 0.111992E+10 | 0.00 | 0.59 |
June | 51609505.41 | 0.864561E+09 | 0.00 | 1489710.25 | 6998669.48 | 0.00 | 0.532090E+09 | 0.00 | 0.53 |
July | 1797873.60 | 0.153165E+10 | 0.00 | 280682.86 | 28579851.63 | 0.00 | 44425134.05 | 0.00 | 0.47 |
August | 1954239.13 | 0.102706E+10 | 0.00 | 1256128.67 | 13382869.04 | 0.00 | 0.211576E+09 | 0.00 | 0.56 |
September | 26513371.03 | 0.217022E+09 | 0.00 | 3985383.47 | 2334438.37 | 0.00 | 0.841096E+09 | 0.00 | 0.65 |
October | 0.105759E+10 | 15931798.56 | 0.00 | 3901841.98 | 1248635.50 | 45774835.18 | 0.158505E+10 | 0.00 | 0.63 |
November | 0.301927E+10 | 0.00 | 0.00 | 146650.71 | 0.00 | 0.110694E+09 | 0.170288E+09 | 0.00 | 0.38 |
December | 0.275431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168574E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.153737E+11 | 0.369771E+10 | 0.00 | 16907541.09 | 55153334.71 | 0.484708E+10 | 0.599697E+10 | 0.00 | 0.49 |
Minimum of Months | 1797873.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.301927E+10 | 0.153165E+10 | 0.00 | 3985383.47 | 28579851.63 | 0.172511E+10 | 0.158505E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261992E+10 | 0.00 | 0.00 | 0.38 |
February | 0.124990E+10 | 0.00 | 0.00 | 50003.65 | 0.00 | 0.201979E+10 | 71014125.61 | 0.00 | 0.39 |
March | 0.190079E+10 | 0.00 | 0.00 | 121071.66 | 0.00 | 0.657597E+09 | 0.214045E+09 | 0.00 | 0.41 |
April | 0.116824E+10 | 182850.79 | 0.00 | 2019709.57 | 16305.28 | 71407808.20 | 0.905672E+09 | 0.00 | 0.57 |
May | 0.535745E+09 | 41674980.64 | 0.00 | 3138233.38 | 2588854.21 | 5066559.45 | 0.100426E+10 | 0.00 | 0.61 |
June | 76085799.23 | 0.859449E+09 | 0.00 | 1418301.17 | 7866586.27 | 0.00 | 0.511382E+09 | 0.00 | 0.54 |
July | 2452400.27 | 0.155533E+10 | 0.00 | 298060.54 | 28582052.72 | 0.00 | 52369887.23 | 0.00 | 0.48 |
August | 4382371.70 | 0.106061E+10 | 0.00 | 1246180.65 | 12582856.98 | 0.00 | 0.223898E+09 | 0.00 | 0.58 |
September | 36777045.32 | 0.228459E+09 | 0.00 | 4006198.52 | 2322673.34 | 0.00 | 0.854000E+09 | 0.00 | 0.68 |
October | 0.977073E+09 | 17777387.57 | 0.00 | 3841401.13 | 1134799.06 | 0.156142E+09 | 0.156683E+10 | 0.00 | 0.65 |
November | 0.273340E+10 | 0.00 | 0.00 | 99744.10 | 0.00 | 0.383335E+09 | 0.116233E+09 | 0.00 | 0.38 |
December | 0.142002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300178E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.115076E+11 | 0.376348E+10 | 0.00 | 16238904.38 | 55094127.87 | 0.891503E+10 | 0.551970E+10 | 0.00 | 0.50 |
Minimum of Months | 2452400.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.273340E+10 | 0.155533E+10 | 0.00 | 4006198.52 | 28582052.72 | 0.300178E+10 | 0.156683E+10 | 0.00 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.252110E+12 | 0.201619E+11 | 0.00 | 0.566007E+11 | 0.761930E+10 |
February | 0.327140E+12 | 0.167333E+11 | 0.00 | 0.473469E+11 | 0.570028E+10 |
March | 0.438776E+12 | 0.136830E+11 | 0.00 | 0.421881E+11 | 0.245860E+10 |
April | 0.560080E+12 | 0.877898E+10 | 0.00 | 0.333375E+11 | 0.211523E+11 |
May | 0.609100E+12 | 0.465575E+10 | 0.00 | 0.236135E+11 | 0.502501E+11 |
June | 0.582219E+12 | -0.295900E+10 | 0.00 | -0.168930E+10 | 0.109954E+12 |
July | 0.599643E+12 | -0.784454E+10 | 0.00 | -0.196620E+11 | 0.153289E+12 |
August | 0.578647E+12 | -0.517267E+10 | 0.00 | -0.101216E+11 | 0.141034E+12 |
September | 0.465370E+12 | -270796400.3 | 0.00 | 0.110351E+11 | 0.950522E+11 |
October | 0.363824E+12 | 0.891543E+10 | 0.00 | 0.397288E+11 | 0.362814E+11 |
November | 0.276723E+12 | 0.169921E+11 | 0.00 | 0.469657E+11 | 0.124099E+10 |
December | 0.234551E+12 | 0.224600E+11 | 0.00 | 0.608788E+11 | 0.844799E+10 |
Annual Sum or Average | 0.528818E+13 | 0.961334E+11 | 0.00 | 0.330222E+12 | 0.632480E+12 |
Minimum of Months | 0.234551E+12 | -0.784454E+10 | 0.00 | -0.196620E+11 | 0.124099E+10 |
Maximum of Months | 0.609100E+12 | 0.224600E+11 | 0.00 | 0.608788E+11 | 0.153289E+12 |