Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2024-07-03 12:21:33
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1271.62 | 608.34 | 608.34 |
Net Site Energy | 1271.62 | 608.34 | 608.34 |
Total Source Energy | 3136.92 | 1500.69 | 1500.69 |
Net Source Energy | 3136.92 | 1500.69 | 1500.69 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 427.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 121.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 99.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 844.21 | 427.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 427.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 121.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 99.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 427.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 121.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 408.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 99.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.33 | 204.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 403.87 | 204.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 224.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.33 | 204.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 403.87 | 204.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 844.208 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 844.208 | 100.00 |
Total On-Site and Utility Electric Sources | 844.208 | 100.00 |
Total Electricity End Uses | 844.208 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2238.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 16.9392 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 19.9075 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 18.2679 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 11.2173 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 11.3140 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 14.6900 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 16.9392 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 19.9075 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 18.2679 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 18.2679 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 11.2173 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 11.3140 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 11.3140 | 6.19 | 4.3000 | |
Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 14.6900 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 14.6900 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-12:20 | 02-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 221334.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 49020.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8581.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1800.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 93722.92 | 221334.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 221334.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 49020.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8581.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1800.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 463.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 384.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1293.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 191.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 316.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 82.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2673.61 | 463.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 221.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 183.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 39.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1279.04 | 221.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 221.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 183.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 39.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1279.04 | 221.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.98 |
SMSTORE1 DIRECT AIR | 1.06 |
SMSTORE2 DIRECT AIR | 1.08 |
SMSTORE3 DIRECT AIR | 1.07 |
SMSTORE4 DIRECT AIR | 1.07 |
LGSTORE2 DIRECT AIR | 1.82 |
SMSTORE5 DIRECT AIR | 0.981150 |
SMSTORE6 DIRECT AIR | 0.976162 |
SMSTORE7 DIRECT AIR | 0.972687 |
SMSTORE8 DIRECT AIR | 1.06 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.98 | 1.98 | 1.98 | 1.98 | 1.98 | 1.98 | 1.00 | 1.00 | 1.98 |
PSZ-AC_2:2 | 1.06 | 1.06 | 1.06 | 1.06 | 1.07 | 1.07 | 1.00 | 0.991005 | 1.07 |
PSZ-AC_3:3 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-AC_4:4 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 0.996756 | 1.07 |
PSZ-AC_5:5 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.00 | 1.07 |
PSZ-AC_6:6 | 1.82 | 1.82 | 1.82 | 1.82 | 1.88 | 1.88 | 1.00 | 0.968715 | 1.88 |
PSZ-AC_7:7 | 0.981150 | 0.981150 | 0.981150 | 0.981150 | 0.981150 | 0.981150 | 1.00 | 1.00 | 0.981150 |
PSZ-AC_8:8 | 0.976162 | 0.976162 | 0.976162 | 0.976162 | 0.976162 | 0.976162 | 1.00 | 1.00 | 0.976162 |
PSZ-AC_9:9 | 0.972687 | 0.972687 | 0.972687 | 0.972687 | 0.972890 | 0.972890 | 1.00 | 0.999791 | 0.972890 |
PSZ-AC_10:10 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 0.994744 | 1.06 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.98 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.08 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.88 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.981150 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.976162 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.972890 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.06 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.98 | 2118.13 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1180.70 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1193.23 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1189.74 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1185.69 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.88 | 2013.39 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.981150 | 1086.29 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.976162 | 1080.77 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.972890 | 1077.14 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1174.80 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.98 | 1.98 | 1.98 | 1.31 | 44848.50 | 61061.39 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.703837 | 23711.91 | 32063.60 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.711310 | 23941.36 | 32541.51 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.709227 | 23851.41 | 32389.75 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.706812 | 23821.69 | 32385.78 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.88 | 1.88 | 1.88 | 1.24 | 43005.08 | 57478.80 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.981150 | 0.981150 | 0.981150 | 0.647559 | 22303.56 | 30334.31 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.976162 | 0.976162 | 0.976162 | 0.644267 | 22222.42 | 30220.32 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.972890 | 0.972890 | 0.972890 | 0.642108 | 22156.12 | 30140.90 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.700325 | 23696.66 | 32034.52 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.98 | 0.989736 | 1.32 | 44848.50 | 22424.25 | 0.730620 | 0.730620 |
PSZ-AC_2:2 COOLING COIL | 1.07 | 0.533210 | 0.710947 | 23711.91 | 11855.95 | 0.736710 | 0.736710 |
PSZ-AC_3:3 COOLING COIL | 1.08 | 0.538871 | 0.718493 | 23941.36 | 11970.68 | 0.736970 | 0.736970 |
PSZ-AC_4:4 COOLING COIL | 1.07 | 0.537293 | 0.716393 | 23851.41 | 11925.70 | 0.737190 | 0.737190 |
PSZ-AC_5:5 COOLING COIL | 1.07 | 0.535463 | 0.713953 | 23821.69 | 11910.84 | 0.736600 | 0.736600 |
PSZ-AC_6:6 COOLING COIL | 1.88 | 0.940795 | 1.25 | 43005.08 | 21502.54 | 0.727280 | 0.727280 |
PSZ-AC_7:7 COOLING COIL | 0.981150 | 0.490575 | 0.654100 | 22303.56 | 11151.78 | 0.729730 | 0.729730 |
PSZ-AC_8:8 COOLING COIL | 0.976160 | 0.488081 | 0.650773 | 22222.42 | 11111.21 | 0.729340 | 0.729340 |
PSZ-AC_9:9 COOLING COIL | 0.972890 | 0.486445 | 0.648593 | 22156.12 | 11078.06 | 0.729240 | 0.729240 |
PSZ-AC_10:10 COOLING COIL | 1.06 | 0.530549 | 0.707400 | 23696.66 | 11848.33 | 0.735520 | 0.735520 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 61061.39 |
PSZ-AC_2:2 HEATING COIL | 32063.60 |
PSZ-AC_3:3 HEATING COIL | 32541.51 |
PSZ-AC_4:4 HEATING COIL | 32389.75 |
PSZ-AC_5:5 HEATING COIL | 32385.78 |
PSZ-AC_6:6 HEATING COIL | 57478.80 |
PSZ-AC_7:7 HEATING COIL | 30334.31 |
PSZ-AC_8:8 HEATING COIL | 30220.32 |
PSZ-AC_9:9 HEATING COIL | 30140.90 |
PSZ-AC_10:10 HEATING COIL | 32034.52 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 16.939 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.239 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 19.907 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.207 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 18.268 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.568 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 11.217 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.517 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 11.314 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 15.614 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3916.664 | 11.242 | 69.629 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3916.664 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1975.182 | 11.339 | 70.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1975.182 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3907.965 | 11.217 | 69.474 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3907.965 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1970.831 | 11.314 | 70.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1970.831 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.433 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34128934E-12 | 0.10473450E-14 | -0.10397207E-12 | 0.10371484E-15 |
23 | 6 | 0.30755064E-07 | 0.17217129E-09 | 0.70279215E-08 | -0.14642558E-12 |
24 | 5 | -0.20062951E-03 | 0.14545406E-05 | -0.10304618E-03 | 0.69406843E-08 |
25 | 4 | 0.30437449 | 0.69977658E-03 | 0.10408506 | -0.35305012E-04 |
26 | 3 | -7.5082928 | 0.21456968E-01 | -2.4107259 | 0.30195353E-01 |
27 | 2 | 41.668927 | 0.75582488E-01 | 15.559173 | -0.34222686 |
28 | 1 | -81.156896 | 0.33830739E-01 | -29.405205 | 1.0916426 |
29 | 0 | 46.824335 | 0.67514285E-03 | 16.285023 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 35 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.46913E-002 | 0.27318 | 0.51792 | 0.51792 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.001 | 0.9234 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 7.082E-002 | 2.033E-004 | 1.120E-004 | 0.141 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.872E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 4.047E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 2.023E-002 | 1.162E-004 | 7.873E-005 | 8.070E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 5.058E-002 | 2.904E-004 | 1.347E-004 | 0.202 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22463.05418 | 26955.66501 | 1.64956 | 1.97947 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 32.03833 | 1.41195E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 23695.48108 | 28434.57730 | 1.02186 | 1.22623 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12335.38181 | 14802.45817 | 0.88069 | 1.05683 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 11176.68290 | 13412.01948 | 0.48199 | 0.57839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12575.67538 | 15090.81046 | 0.89812 | 1.07774 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 11334.49380 | 13601.39256 | 0.48880 | 0.58656 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12500.44779 | 15000.53735 | 0.89258 | 1.07110 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 11445.14331 | 13734.17197 | 0.49357 | 0.59229 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12497.93233 | 14997.51879 | 0.89244 | 1.07093 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 11612.91162 | 13935.49394 | 0.50081 | 0.60097 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21357.81186 | 25629.37424 | 1.51894 | 1.82272 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 22329.78406 | 26795.74088 | 0.96298 | 1.15558 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11471.90088 | 13766.28105 | 0.81763 | 0.98115 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 11936.00509 | 14323.20611 | 0.51474 | 0.61769 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11415.01697 | 13698.02036 | 0.81347 | 0.97616 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 11927.17426 | 14312.60912 | 0.51436 | 0.61723 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11375.23317 | 13650.27980 | 0.81057 | 0.97269 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 12159.65927 | 14591.59112 | 0.52439 | 0.62926 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12317.09764 | 14780.51717 | 0.87960 | 1.05552 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 14729.76548 | 17675.71858 | 0.63520 | 0.76223 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30625.63 | 1.97947 | 1.97947 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 43849.12 | 1.22623 | 1.22623 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16274.47 | 1.06642 | 1.06642 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 21131.07 | 0.57839 | 0.57839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16327.12 | 1.07774 | 1.07774 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 21317.68 | 0.58656 | 0.58656 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16374.31 | 1.07459 | 1.07459 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 21448.53 | 0.59229 | 0.59229 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16252.04 | 1.07093 | 1.07093 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 21646.92 | 0.60097 | 0.60097 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 29163.16 | 1.88159 | 1.88159 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 42234.37 | 1.15558 | 1.15558 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15028.54 | 0.98115 | 0.98115 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 22028.99 | 0.61769 | 0.61769 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14956.19 | 0.97616 | 0.97616 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 22018.55 | 0.61723 | 0.61723 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14937.89 | 0.97289 | 0.97289 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 22293.47 | 0.62926 | 0.62926 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 16018.67 | 1.06110 | 1.06110 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 25332.48 | 0.76223 | 0.76223 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.97947 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05683 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07774 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07110 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07093 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.82272 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98115 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97616 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97269 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05552 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.97947 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.97947 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.97947 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.97947 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.97947 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.97947 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05683 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05683 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05683 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05683 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06642 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06642 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.99100 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07774 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07774 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07774 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07774 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07774 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07774 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07110 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07110 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07110 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07110 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07459 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07459 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.99676 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07093 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07093 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07093 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07093 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07093 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07093 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.82272 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.82272 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.82272 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.82272 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.88159 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.88159 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.96871 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98115 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98115 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98115 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98115 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98115 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98115 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97616 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97616 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97616 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97616 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97616 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97616 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97269 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97269 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97269 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97269 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97289 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97289 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99979 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05552 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05552 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05552 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05552 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06110 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06110 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.99474 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.97947 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.06642 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.07774 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.07459 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.07093 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.88159 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.98115 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.97616 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.97289 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.06110 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.97947 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.97947 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2118.12759 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.97947 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.97947 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.97947 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30645 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.97947 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98974 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31965 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 44848.50000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22424.25000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73062 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73062 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44848.50000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61061.38533 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 61061.38533 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06642 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06642 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1180.69597 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06642 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06642 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06642 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70384 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06642 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53321 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71095 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23711.91000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11855.95500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73671 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73671 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23711.91000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32063.59791 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 32063.59791 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07774 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07774 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1193.23116 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07774 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07774 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07774 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71131 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07774 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53887 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71849 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23941.36000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11970.68000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73697 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73697 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23941.36000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32541.51145 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 32541.51145 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07459 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07459 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1189.73807 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07459 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07459 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07459 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70923 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07459 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53729 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71639 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23851.41000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11925.70500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73719 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73719 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23851.41000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32389.74931 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 32389.74931 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07093 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07093 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1185.68617 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07093 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07093 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07093 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70681 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07093 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53546 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71395 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23821.69000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11910.84500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73660 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73660 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23821.69000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32385.78008 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 32385.78008 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.88159 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.88159 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2013.38928 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.88159 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.88159 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.88159 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24185 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.88159 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94079 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.25439 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 43005.08000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21502.54000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72728 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72728 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43005.08000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57478.80380 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 57478.80380 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98115 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98115 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1086.28930 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98115 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98115 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98115 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.64756 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98115 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49058 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65410 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22303.56000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11151.78000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72973 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72973 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22303.56000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30334.31187 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 30334.31187 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97616 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97616 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1080.76639 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97616 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97616 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97616 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.64427 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97616 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48808 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65077 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22222.42000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11111.21000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72934 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72934 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22222.42000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30220.32395 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 30220.32395 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97289 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97289 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1077.14396 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97289 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97289 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97289 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.64211 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97289 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48645 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64859 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22156.12000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11078.06000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72924 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72924 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22156.12000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30140.90279 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 30140.90279 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06110 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06110 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1174.80365 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06110 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06110 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06110 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70032 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06110 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53055 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70740 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23696.66000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11848.33000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73552 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73552 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23696.66000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32034.52494 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 32034.52494 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 43289.6 | 11.81 | 11.81 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 22872.3 | 11.76 | 11.76 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 23092.9 | 11.76 | 11.76 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 23005.4 | 11.75 | 11.75 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 22978.6 | 11.76 | 11.76 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 41523.0 | 11.82 | 11.82 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 21530.8 | 11.80 | 11.80 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 21453.6 | 11.80 | 11.80 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 21389.9 | 11.80 | 11.80 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 22861.2 | 11.77 | 11.77 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_0.36 | N/A | 2.153 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 5.5566295163E-002 | 0.3088273687 | Pass | Pass | 0.1535450881 | 1.0095591642 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.2817778312E-002 | 0.2281695256 | Pass | Pass | 0.1069254455 | 0.3221559323 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.7620434341E-002 | 0.3103279626 | Pass | Pass | 4.2123186612E-002 | 0.1159785581 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 6.4205485237E-002 | 0.3343467235 | Pass | Pass | 3.6707876053E-002 | 0.1041473376 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 6.8723835584E-002 | 0.3571276308 | Pass | Pass | 3.3636892611E-002 | 9.7497409049E-002 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 7.8247224321E-002 | 0.3896808823 | Pass | Pass | 3.2517072797E-002 | 0.1230412368 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 7.7261795003E-002 | 0.3926272108 | Pass | Pass | 2.9286545328E-002 | 0.1006314604 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 7.8098052860E-002 | 0.3950241884 | Pass | Pass | 2.9323389580E-002 | 0.1021483867 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 8.1423158190E-002 | 0.4117718275 | Pass | Pass | 2.7118787772E-002 | 9.0720843213E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.1820405246 | 0.4330447512 | Pass | Pass | 3.1189724732 | 12.2305806832 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4105.42 | 142.78 | 0.00 | 385.37 | 707.68 | 5341.29 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.361 | 0.397 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.153 | 0.361 | 0.397 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.153 | 0.361 | 0.397 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.379_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.153 | 0.361 | 0.397 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.153 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.153 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.101 | 3.065 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.101 | 3.065 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 11.2423 | 348.39 | 3916.66 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.43 | 0.0000 | Y | 60.61 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 11.3390 | 174.19 | 1975.18 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 83.87 | 0.0000 | Y | 31.10 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.69 | 0.0000 | Y | 24.30 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 11.2173 | 348.39 | 3907.97 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 58.99 | 0.0000 | Y | 43.28 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 11.3140 | 174.19 | 1970.83 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.00 | 0.0000 | Y | 22.20 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.3450 | 4180.64 | 30706.87 | 408.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 42.43 | 42.43 | 3.63 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.64 | 63.04 | 32.47 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.64 | 56.04 | 24.27 | |
Exterior Lighting Total | 5507.06 | 60.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 44848.50 | 32767.21 | 12081.29 | 0.73 | 3.81 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23711.91 | 17468.80 | 6243.11 | 0.74 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23941.36 | 17644.06 | 6297.30 | 0.74 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23851.41 | 17583.02 | 6268.39 | 0.74 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23821.69 | 17547.06 | 6274.63 | 0.74 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43005.08 | 31276.73 | 11728.35 | 0.73 | 3.81 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22303.56 | 16275.58 | 6027.98 | 0.73 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22222.42 | 16207.70 | 6014.72 | 0.73 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22156.12 | 16157.13 | 5998.99 | 0.73 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23696.66 | 17429.37 | 6267.29 | 0.74 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 43289.6 | 11.81 | 11.81 | ||||
PSZ-AC_2:2 COOLING COIL | 22872.3 | 11.76 | 11.76 | ||||
PSZ-AC_3:3 COOLING COIL | 23092.9 | 11.76 | 11.76 | ||||
PSZ-AC_4:4 COOLING COIL | 23005.4 | 11.75 | 11.75 | ||||
PSZ-AC_5:5 COOLING COIL | 22978.6 | 11.76 | 11.76 | ||||
PSZ-AC_6:6 COOLING COIL | 41523.0 | 11.82 | 11.82 | ||||
PSZ-AC_7:7 COOLING COIL | 21530.8 | 11.80 | 11.80 | ||||
PSZ-AC_8:8 COOLING COIL | 21453.6 | 11.80 | 11.80 | ||||
PSZ-AC_9:9 COOLING COIL | 21389.9 | 11.80 | 11.80 | ||||
PSZ-AC_10:10 COOLING COIL | 22861.2 | 11.77 | 11.77 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 61061.39 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 32063.60 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 32541.51 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 32389.75 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 32385.78 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 57478.80 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 30334.31 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 30220.32 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 30140.90 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 32034.52 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.98 | 2118.13 | 1070.05 | 1.00 | 1.32 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1180.70 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1193.23 | 1107.16 | 1.00 | 1.38 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1189.74 | 1107.16 | 1.00 | 1.38 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1185.69 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.88 | 2013.39 | 1070.05 | 1.00 | 1.32 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1086.29 | 1107.16 | 1.00 | 1.41 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1080.77 | 1107.16 | 1.00 | 1.41 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1077.14 | 1107.16 | 1.00 | 1.41 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1174.80 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.00 | 0.92 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22463.05 | 26955.67 | 77.37 | 1.650 | 1.979 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00972 | 32.04 | 0.01412 | 0.411 | 0.00 |
SMSTORE1 | 12335.38 | 14802.46 | 84.98 | 0.881 | 1.057 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00928 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE2 | 12575.68 | 15090.81 | 86.63 | 0.898 | 1.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00950 | 28.03 | 0.01411 | 0.206 | 0.00 |
SMSTORE3 | 12500.45 | 15000.54 | 86.11 | 0.893 | 1.071 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00949 | 28.03 | 0.01411 | 0.206 | 0.00 |
SMSTORE4 | 12497.93 | 14997.52 | 86.10 | 0.892 | 1.071 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00952 | 28.03 | 0.01411 | 0.206 | 0.00 |
LGSTORE2 | 21357.81 | 25629.37 | 73.57 | 1.519 | 1.823 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00954 | 29.29 | 0.01411 | 0.411 | 0.00 |
SMSTORE5 | 11471.90 | 13766.28 | 79.03 | 0.818 | 0.981 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00946 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE6 | 11415.02 | 13698.02 | 78.64 | 0.813 | 0.976 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00947 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE7 | 11375.23 | 13650.28 | 78.36 | 0.811 | 0.973 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00949 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE8 | 12317.10 | 14780.52 | 84.85 | 0.880 | 1.056 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00943 | 29.29 | 0.01411 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23695.48 | 28434.58 | 81.62 | 1.022 | 1.226 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00660 | -10.70 | 0.00150 | 0.411 | 0.00 |
SMSTORE1 | 11176.68 | 13412.02 | 77.00 | 0.482 | 0.578 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE2 | 11334.49 | 13601.39 | 78.08 | 0.489 | 0.587 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00652 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE3 | 11445.14 | 13734.17 | 78.84 | 0.494 | 0.592 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE4 | 11612.91 | 13935.49 | 80.00 | 0.501 | 0.601 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00654 | -10.70 | 0.00150 | 0.206 | 0.00 |
LGSTORE2 | 22329.78 | 26795.74 | 76.91 | 0.963 | 1.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00662 | -10.70 | 0.00150 | 0.411 | 0.00 |
SMSTORE5 | 11936.01 | 14323.21 | 82.23 | 0.515 | 0.618 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00657 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE6 | 11927.17 | 14312.61 | 82.17 | 0.514 | 0.617 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00657 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE7 | 12159.66 | 14591.59 | 83.77 | 0.524 | 0.629 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00658 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE8 | 14729.77 | 17675.72 | 101.47 | 0.635 | 0.762 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -10.70 | 0.00150 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.98 | 1.98 | 1.23 | 1.23 | 1.9795 | 1.9795 | 1.9795 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.07 | 1.07 | 0.58 | 0.58 | 1.0664 | 1.0568 | 1.0664 | 0.9910 | 1.0000 |
PSZ-AC_3:3 | 1.08 | 1.08 | 0.59 | 0.59 | 1.0777 | 1.0777 | 1.0777 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.07 | 1.07 | 0.59 | 0.59 | 1.0746 | 1.0711 | 1.0746 | 0.9968 | 1.0000 |
PSZ-AC_5:5 | 1.07 | 1.07 | 0.60 | 0.60 | 1.0709 | 1.0709 | 1.0709 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.88 | 1.88 | 1.16 | 1.16 | 1.8816 | 1.8227 | 1.8816 | 0.9687 | 1.0000 |
PSZ-AC_7:7 | 0.98 | 0.98 | 0.62 | 0.62 | 0.9812 | 0.9812 | 0.9812 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.98 | 0.98 | 0.62 | 0.62 | 0.9762 | 0.9762 | 0.9762 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.97 | 0.97 | 0.63 | 0.63 | 0.9729 | 0.9727 | 0.9729 | 0.9998 | 1.0000 |
PSZ-AC_10:10 | 1.06 | 1.06 | 0.76 | 0.76 | 1.0611 | 1.0555 | 1.0611 | 0.9947 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 44848.500 | 32767.211 | 1.979470 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 22424.25 | 16500.08 | 1.319647 | 26.46 | 18.96 | 0.01063671 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 31.1810 | 23.89 | 0.00972265 | 52.5731 | 22461.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 61061.385 | 61061.385 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61061.39 | 61061.39 | 1.979471 | 14.49 | 9.73 | 0.00554244 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 20.7873 | 21.10 | 0.00660225 | 42.4822 | 23695.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 23711.910 | 17468.801 | 1.066420 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11855.95 | 8813.87 | 0.710947 | 26.33 | 18.85 | 0.01053685 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 28.9388 | 23.89 | 0.00967891 | 52.3400 | 12070.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 32063.598 | 32063.598 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32063.60 | 32063.60 | 1.066420 | 14.97 | 9.94 | 0.00553843 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.2925 | 21.10 | 0.00650285 | 41.8491 | 11176.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 23941.360 | 17644.064 | 1.077740 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11970.68 | 8905.19 | 0.718493 | 26.33 | 18.84 | 0.01053070 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 28.6348 | 23.89 | 0.00967519 | 52.3202 | 12128.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 32541.511 | 32541.511 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32541.51 | 32541.51 | 1.077742 | 15.03 | 9.99 | 0.00555972 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.0899 | 21.10 | 0.00651665 | 41.9370 | 11334.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 23851.410 | 17583.021 | 1.074590 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11925.70 | 8877.11 | 0.716393 | 26.32 | 18.83 | 0.01052521 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 28.7188 | 23.89 | 0.00967187 | 52.3025 | 12168.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 32389.749 | 32389.749 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32389.75 | 32389.75 | 1.074587 | 15.02 | 9.99 | 0.00556448 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.1459 | 21.10 | 0.00652600 | 41.9966 | 11445.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 23821.690 | 17547.057 | 1.070930 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11910.84 | 8852.08 | 0.713953 | 26.34 | 18.85 | 0.01053951 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 28.8169 | 23.89 | 0.00968053 | 52.3486 | 12064.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 32385.780 | 32385.780 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32385.78 | 32385.78 | 1.070927 | 15.00 | 9.99 | 0.00557272 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.2113 | 21.10 | 0.00654028 | 42.0875 | 11612.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 43005.080 | 31276.735 | 1.881590 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 21502.54 | 15697.68 | 1.254393 | 26.51 | 19.04 | 0.01070840 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 32.8030 | 23.89 | 0.00975078 | 52.7224 | 21302.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 57478.804 | 57478.804 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 57478.80 | 57478.80 | 1.881589 | 14.15 | 9.53 | 0.00550427 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 21.8687 | 21.10 | 0.00662396 | 42.6193 | 22329.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 22303.560 | 16275.577 | 0.981150 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 11151.78 | 8152.66 | 0.654100 | 26.47 | 19.01 | 0.01069036 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 31.4538 | 23.89 | 0.00977095 | 52.8299 | 11027.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 30334.312 | 30334.312 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30334.31 | 30334.31 | 0.981150 | 14.44 | 9.66 | 0.00550498 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 20.9692 | 21.10 | 0.00656658 | 42.2551 | 11936.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 22222.420 | 16207.700 | 0.976160 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 11111.21 | 8114.58 | 0.650773 | 26.48 | 19.02 | 0.01070018 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 31.6146 | 23.89 | 0.00977692 | 52.8617 | 10966.62 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 30220.324 | 30220.324 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30220.32 | 30220.32 | 0.976162 | 14.40 | 9.64 | 0.00549904 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 21.0764 | 21.10 | 0.00656593 | 42.2509 | 11927.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 22156.120 | 16157.129 | 0.972890 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 11078.06 | 8088.24 | 0.648593 | 26.48 | 19.02 | 0.01070268 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 31.7209 | 23.89 | 0.00977844 | 52.8697 | 10950.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 30140.903 | 30140.903 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30140.90 | 30140.90 | 0.972890 | 14.38 | 9.64 | 0.00550978 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 21.1472 | 21.10 | 0.00658410 | 42.3667 | 12159.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 23696.660 | 17429.367 | 1.061100 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 11848.33 | 8746.15 | 0.707400 | 26.32 | 18.88 | 0.01059140 | 12.80 | 12.09 | 0.00850000 | 31.73 | 0.01411898 | 23.03 | 29.0839 | 23.89 | 0.00973087 | 52.6167 | 11906.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 32034.525 | 32034.525 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32034.52 | 32034.52 | 1.061098 | 14.94 | 10.04 | 0.00564326 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.3893 | 21.10 | 0.00663890 | 42.7177 | 14729.77 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 44848.500 | 32767.211 | 1.979470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6131 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.979471 | 2.38248141 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 22424.25 | 16500.08 | 1.0000 | 1.58832011 | 1.319647 | 26.46 | 18.96 | 0.01063671 | 53713.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22424.25 | 32.10 | 0.01411964 | 23.13 | 0.41147883 | 31.1810 | 23.89 | 0.00972265 | 23.89 | 0.00972265 | 52.5731 | 22461.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61061.385 | 61061.385 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.979471 | 2.38248141 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 61061.39 | 61061.39 | 1.0000 | 2.38248141 | 1.979471 | 14.49 | 9.73 | 0.00554244 | 28575.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61061.39 | -10.70 | 0.00150390 | -10.70 | 0.41147883 | 20.7873 | 21.11 | 0.00660225 | 21.10 | 0.00660225 | 42.4822 | 23695.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23711.910 | 17468.801 | 1.066420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4275 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.066420 | 1.28353748 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 11855.95 | 8813.87 | 1.0000 | 0.85569184 | 0.710947 | 26.33 | 18.85 | 0.01053685 | 53330.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11855.95 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 28.9388 | 23.89 | 0.00967891 | 23.89 | 0.00967891 | 52.3400 | 12070.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32063.598 | 32063.598 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.066420 | 1.28353748 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32063.60 | 32063.60 | 1.0000 | 1.28353748 | 1.066420 | 14.97 | 9.94 | 0.00553843 | 29048.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32063.60 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.2925 | 21.11 | 0.00650285 | 21.10 | 0.00650285 | 41.8491 | 11176.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23941.360 | 17644.064 | 1.077740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4160 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.077742 | 1.29716452 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11970.68 | 8905.19 | 1.0000 | 0.86477497 | 0.718493 | 26.33 | 18.84 | 0.01053070 | 53308.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11970.68 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 28.6348 | 23.89 | 0.00967519 | 23.89 | 0.00967519 | 52.3202 | 12128.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32541.511 | 32541.511 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.077742 | 1.29716452 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32541.51 | 32541.51 | 1.0000 | 1.29716452 | 1.077742 | 15.03 | 9.99 | 0.00555972 | 29167.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32541.51 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.0899 | 21.11 | 0.00651665 | 21.10 | 0.00651665 | 41.9370 | 11334.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23851.410 | 17583.021 | 1.074590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4058 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.074587 | 1.29336718 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 11925.70 | 8877.11 | 1.0000 | 0.86224742 | 0.716393 | 26.32 | 18.83 | 0.01052521 | 53289.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11925.70 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 28.7188 | 23.89 | 0.00967187 | 23.89 | 0.00967187 | 52.3025 | 12168.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32389.749 | 32389.749 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.074587 | 1.29336718 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32389.75 | 32389.75 | 1.0000 | 1.29336718 | 1.074587 | 15.02 | 9.99 | 0.00556448 | 29161.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32389.75 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.1459 | 21.11 | 0.00652600 | 21.10 | 0.00652600 | 41.9966 | 11445.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23821.690 | 17547.057 | 1.070930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4324 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.070927 | 1.28896235 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11910.84 | 8852.08 | 1.0000 | 0.85931065 | 0.713953 | 26.34 | 18.85 | 0.01053951 | 53339.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11910.84 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 28.8169 | 23.89 | 0.00968053 | 23.89 | 0.00968053 | 52.3486 | 12064.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32385.780 | 32385.780 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.070927 | 1.28896235 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32385.78 | 32385.78 | 1.0000 | 1.28896235 | 1.070927 | 15.00 | 9.99 | 0.00557272 | 29161.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32385.78 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.2113 | 21.11 | 0.00654028 | 21.10 | 0.00654028 | 42.0875 | 11612.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43005.080 | 31276.735 | 1.881590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7464 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.881589 | 2.26467120 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 21502.54 | 15697.68 | 1.0000 | 1.50978152 | 1.254393 | 26.51 | 19.04 | 0.01070840 | 53950.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21502.54 | 31.92 | 0.01411931 | 23.08 | 0.41147883 | 32.8030 | 23.89 | 0.00975078 | 23.89 | 0.00975078 | 52.7224 | 21302.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57478.804 | 57478.804 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.881589 | 2.26467120 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 57478.80 | 57478.80 | 1.0000 | 2.26467120 | 1.881589 | 14.15 | 9.53 | 0.00550427 | 28130.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57478.80 | -10.70 | 0.00150390 | -10.70 | 0.41147883 | 21.8687 | 21.11 | 0.00662396 | 21.10 | 0.00662396 | 42.6193 | 22329.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22303.560 | 16275.577 | 0.981150 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7128 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.981150 | 1.18090777 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | Sensible | 11151.78 | 8152.66 | 1.0000 | 0.78727148 | 0.654100 | 26.47 | 19.01 | 0.01069036 | 53858.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11151.78 | 31.85 | 0.01411920 | 23.06 | 0.20573941 | 31.4538 | 23.89 | 0.00977095 | 23.89 | 0.00977095 | 52.8299 | 11027.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30334.312 | 30334.312 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.981150 | 1.18090777 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30334.31 | 30334.31 | 1.0000 | 1.18090777 | 0.981150 | 14.44 | 9.66 | 0.00550498 | 28422.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30334.31 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 20.9692 | 21.11 | 0.00656658 | 21.10 | 0.00656658 | 42.2551 | 11936.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22222.420 | 16207.700 | 0.976160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7311 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976162 | 1.17490379 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | Sensible | 11111.21 | 8114.58 | 1.0000 | 0.78326752 | 0.650773 | 26.48 | 19.02 | 0.01070018 | 53892.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11111.21 | 31.85 | 0.01411920 | 23.06 | 0.20573941 | 31.6146 | 23.89 | 0.00977692 | 23.89 | 0.00977692 | 52.8617 | 10966.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30220.324 | 30220.324 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976162 | 1.17490379 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30220.32 | 30220.32 | 1.0000 | 1.17490379 | 0.976162 | 14.40 | 9.64 | 0.00549904 | 28372.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30220.32 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 21.0764 | 21.11 | 0.00656593 | 21.10 | 0.00656593 | 42.2509 | 11927.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22156.120 | 16157.129 | 0.972890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7358 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.972890 | 1.17096585 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 11078.06 | 8088.24 | 1.0000 | 0.78064368 | 0.648593 | 26.48 | 19.02 | 0.01070268 | 53901.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11078.06 | 31.85 | 0.01411920 | 23.06 | 0.20573941 | 31.7209 | 23.89 | 0.00977844 | 23.89 | 0.00977844 | 52.8697 | 10950.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30140.903 | 30140.903 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.972890 | 1.17096585 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30140.90 | 30140.90 | 1.0000 | 1.17096585 | 0.972890 | 14.38 | 9.64 | 0.00550978 | 28376.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30140.90 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 21.1472 | 21.11 | 0.00658410 | 21.10 | 0.00658410 | 42.3667 | 12159.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23696.660 | 17429.367 | 1.061100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5289 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.061098 | 1.27713193 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 11848.33 | 8746.15 | 1.0000 | 0.85142309 | 0.707400 | 26.32 | 18.88 | 0.01059140 | 53456.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11848.33 | 31.73 | 0.01411898 | 23.03 | 0.20573941 | 29.0839 | 23.89 | 0.00973087 | 23.89 | 0.00973087 | 52.6167 | 11906.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32034.525 | 32034.525 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.061098 | 1.27713193 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32034.52 | 32034.52 | 1.0000 | 1.27713193 | 1.061098 | 14.94 | 10.04 | 0.00564326 | 29281.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32034.52 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.3893 | 21.11 | 0.00663890 | 21.10 | 0.00663890 | 42.7177 | 14729.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.98 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.07 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.08 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.07 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.07 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.88 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.98 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.98 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.97 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.06 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3037.67 | 3498.83 | 1204.83 |
SMSTORE1 | 2385.17 | 3153.33 | 425.17 |
SMSTORE2 | 2050.50 | 2557.33 | 621.33 |
SMSTORE3 | 2093.50 | 2585.00 | 678.17 |
SMSTORE4 | 2141.67 | 2649.67 | 782.67 |
LGSTORE2 | 2177.33 | 2610.33 | 1098.33 |
SMSTORE5 | 2146.33 | 2654.67 | 1122.50 |
SMSTORE6 | 2174.50 | 2684.33 | 1173.17 |
SMSTORE7 | 2263.67 | 2755.33 | 1311.00 |
SMSTORE8 | 2628.50 | 2842.17 | 1704.33 |
Facility | 3941.00 | 4104.67 | 2238.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 4.33 | 0.00 | 0.50 | 0.00 |
SMSTORE1 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 2.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 12.17 | 0.00 | 0.00 | 0.00 |
Facility | 16.83 | 0.00 | 0.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.931 | 0.221 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.799 | 0.240 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.988 | 0.314 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.984 | 0.314 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.975 | 0.314 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.949 | 0.301 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.955 | 0.335 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.952 | 0.335 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.945 | 0.335 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.956 | 0.346 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.78 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.98 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9669872.91 | 0.00 | 9669872.91 | 2503277.68 | 12173150.59 | 12976396.34 | 3164.21 | 4620.00 | 975.79 | 14.71 |
SMSTORE1 | 4145267.18 | 0.00 | 4145267.18 | 1306686.68 | 5451953.86 | 6488198.17 | 4433.61 | 3301.92 | 1024.47 | 19.12 |
SMSTORE2 | 3901536.45 | 0.00 | 3901536.45 | 1327277.24 | 5228813.70 | 6488198.17 | 4343.02 | 3662.00 | 754.98 | 66.99 |
SMSTORE3 | 3884920.72 | 0.00 | 3884920.72 | 1327277.24 | 5212197.96 | 6488198.17 | 4344.11 | 3685.83 | 730.06 | 64.86 |
SMSTORE4 | 3847495.73 | 0.00 | 3847495.73 | 1327277.24 | 5174772.98 | 6488198.17 | 4346.41 | 3723.75 | 689.84 | 60.95 |
LGSTORE2 | 6854337.85 | 0.00 | 6854337.85 | 2414841.65 | 9269179.49 | 12976396.34 | 4713.56 | 3423.33 | 623.11 | 53.61 |
SMSTORE5 | 3451909.30 | 0.00 | 3451909.30 | 1332947.46 | 4784856.75 | 6488198.17 | 4713.56 | 3432.67 | 613.77 | 53.13 |
SMSTORE6 | 3437928.84 | 0.00 | 3437928.84 | 1332947.46 | 4770876.30 | 6488198.17 | 4713.84 | 3447.50 | 598.66 | 49.77 |
SMSTORE7 | 3410706.66 | 0.00 | 3410706.66 | 1332947.46 | 4743654.12 | 6488198.17 | 4714.84 | 3480.75 | 564.41 | 42.55 |
SMSTORE8 | 3448316.83 | 0.00 | 3448316.83 | 1513296.22 | 4961613.05 | 6488198.17 | 4716.19 | 3514.04 | 529.77 | 31.38 |
Total Facility | 46052292.48 | 0.00 | 46052292.48 | 15718776.32 | 61771068.80 | 77858378.04 | 4723.35 | 5177.08 | 1274.18 | 142.26 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4592 | 0.0000 | 0.4592 | 0.1090 | 0.5681 | 0.4115 | 248.26 | 4620.00 | 971.74 |
SMSTORE1 | 0.1967 | 0.0000 | 0.1967 | 0.0591 | 0.2558 | 0.2057 | 1516.84 | 3301.92 | 1021.24 |
SMSTORE2 | 0.2436 | 0.0000 | 0.2436 | 0.0775 | 0.3211 | 0.2057 | 0.00 | 3661.50 | 733.50 |
SMSTORE3 | 0.2427 | 0.0000 | 0.2427 | 0.0775 | 0.3202 | 0.2057 | 0.00 | 3685.17 | 709.83 |
SMSTORE4 | 0.2405 | 0.0000 | 0.2405 | 0.0775 | 0.3180 | 0.2057 | 0.00 | 3723.50 | 671.50 |
LGSTORE2 | 0.4677 | 0.0000 | 0.4677 | 0.1487 | 0.6164 | 0.4115 | 0.00 | 3423.33 | 606.67 |
SMSTORE5 | 0.2355 | 0.0000 | 0.2355 | 0.0827 | 0.3182 | 0.2057 | 0.00 | 3432.67 | 597.33 |
SMSTORE6 | 0.2347 | 0.0000 | 0.2347 | 0.0827 | 0.3174 | 0.2057 | 0.00 | 3447.50 | 582.50 |
SMSTORE7 | 0.2330 | 0.0000 | 0.2330 | 0.0827 | 0.3157 | 0.2057 | 0.00 | 3480.58 | 549.42 |
SMSTORE8 | 0.2357 | 0.0000 | 0.2357 | 0.0855 | 0.3212 | 0.2057 | 0.00 | 3513.83 | 516.17 |
Total Facility | 2.7894 | 0.0000 | 2.7894 | 0.8829 | 3.6723 | 2.4689 | 1622.61 | 5175.50 | 1251.86 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14008611.74 | 0.00 | 14008611.74 | 12976396.34 | 3156.54 | 0.33 | 5603.13 | 14.71 |
PSZ-AC_2:2 | 6005136.79 | 0.00 | 6005136.79 | 6488198.17 | 4359.96 | 2.42 | 4397.62 | 19.12 |
PSZ-AC_3:3 | 5652071.83 | 0.00 | 5652071.83 | 6488198.17 | 4334.74 | 0.37 | 4424.89 | 66.66 |
PSZ-AC_4:4 | 5628002.14 | 0.00 | 5628002.14 | 6488198.17 | 4335.52 | 0.67 | 4423.81 | 64.69 |
PSZ-AC_5:5 | 5573784.80 | 0.00 | 5573784.80 | 6488198.17 | 4338.55 | 0.08 | 4421.37 | 60.79 |
PSZ-AC_6:6 | 9929797.86 | 0.00 | 9929797.86 | 12976396.34 | 4707.22 | 0.50 | 4052.28 | 53.53 |
PSZ-AC_7:7 | 5000723.55 | 0.00 | 5000723.55 | 6488198.17 | 4706.81 | 0.50 | 4052.69 | 52.96 |
PSZ-AC_8:8 | 4980467.91 | 0.00 | 4980467.91 | 6488198.17 | 4708.42 | 0.33 | 4051.25 | 49.77 |
PSZ-AC_9:9 | 4941016.74 | 0.00 | 4941016.74 | 6488198.17 | 4711.37 | 0.00 | 4048.63 | 42.13 |
PSZ-AC_10:10 | 4995439.72 | 0.00 | 4995439.72 | 6488198.17 | 4711.42 | 0.00 | 4048.58 | 31.38 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6652 | 0.0000 | 0.6652 | 0.4115 | 241.76 | 0.33 | 5597.91 |
PSZ-AC_2:2 | 0.2850 | 0.0000 | 0.2850 | 0.2057 | 1444.86 | 2.42 | 4392.72 |
PSZ-AC_3:3 | 0.3529 | 0.0000 | 0.3529 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3516 | 0.0000 | 0.3516 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3485 | 0.0000 | 0.3485 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6776 | 0.0000 | 0.6776 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3412 | 0.0000 | 0.3412 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3399 | 0.0000 | 0.3399 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3376 | 0.0000 | 0.3376 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3415 | 0.0000 | 0.3415 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5176.38 | 458.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4266.87 | 731.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4105.01 | 356.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4123.23 | 336.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4141.12 | 314.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3834.86 | 248.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3832.21 | 250.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3839.91 | 239.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3854.13 | 218.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3864.19 | 197.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6748 | 0.8851 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3259 | 0.3848 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3432 | 0.4873 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3420 | 0.4928 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3396 | 0.4881 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6658 | 0.8986 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3347 | 0.4620 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3337 | 0.4619 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3317 | 0.4620 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3346 | 0.4960 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 828 |
Defaulted Fields | 823 |
Fields with Defaults | 2679 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 844.21 | 891.83 | 14-FEB-07:00 | 93722.92 | 08-JUL-12:20 |
Electricity:Building | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 122.08 | 148.64 | 01-JAN-00:20 | 6431.20 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 536.50 | 891.83 | 01-JAN-00:20 | 34320.80 | 01-JAN-11:10 |
InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 95.83 | 75.00 | 01-JAN-00:20 | 5087.95 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 408.34 | 450.00 | 01-JAN-00:20 | 26261.30 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 70.71 | 74.32 | 01-JAN-00:20 | 3733.31 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 57.58 | 37.50 | 01-JAN-00:20 | 3061.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 51.38 | 74.32 | 01-JAN-00:10 | 3460.63 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 40.96 | 37.50 | 01-JAN-00:10 | 2789.01 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 62.45 | 148.64 | 01-JAN-00:10 | 4534.89 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 43.28 | 75.00 | 01-JAN-00:10 | 3191.64 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 31.78 | 74.32 | 01-JAN-00:10 | 2309.88 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 22.20 | 37.50 | 01-JAN-00:10 | 1638.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 844.21 | 891.83 | 14-FEB-07:00 | 93722.92 | 08-JUL-12:20 |
ElectricityPurchased:Plant | 844.21 | 891.83 | 14-FEB-07:00 | 93722.92 | 08-JUL-12:20 |
Cogeneration:ElectricityPurchased | 844.21 | 891.83 | 14-FEB-07:00 | 93722.92 | 08-JUL-12:20 |
General:Cogeneration:ElectricityPurchased | 844.21 | 891.83 | 14-FEB-07:00 | 93722.92 | 08-JUL-12:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 844.21 | 891.83 | 14-FEB-07:00 | 93722.92 | 08-JUL-12:20 |
ElectricityNet:Plant | 844.21 | 891.83 | 14-FEB-07:00 | 93722.92 | 08-JUL-12:20 |
Cogeneration:ElectricityNet | 844.21 | 891.83 | 14-FEB-07:00 | 93722.92 | 08-JUL-12:20 |
General:Cogeneration:ElectricityNet | 844.21 | 891.83 | 14-FEB-07:00 | 93722.92 | 08-JUL-12:20 |
Electricity:HVAC | 221.26 | 0.00 | 01-JAN-00:10 | 57678.19 | 08-JUL-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 121.41 | 0.00 | 01-JAN-00:10 | 49104.13 | 08-JUL-12:10 |
General:Cooling:Electricity | 121.41 | 0.00 | 01-JAN-00:10 | 49104.13 | 08-JUL-12:10 |
Fans:Electricity | 99.85 | 0.00 | 01-JAN-00:10 | 9127.36 | 02-JAN-08:10 |
General:Fans:Electricity | 99.85 | 0.00 | 01-JAN-00:10 | 9127.36 | 02-JAN-08:10 |
ExteriorLights:Electricity | 60.37 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.37 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 26.08 | 0.00 | 01-JAN-00:10 | 2237.28 | 10-FEB-13:30 |
WaterSystems:Electricity | 26.08 | 0.00 | 01-JAN-00:10 | 2237.28 | 10-FEB-13:30 |
Water Heater:WaterSystems:Electricity | 26.08 | 0.00 | 01-JAN-00:10 | 2237.28 | 10-FEB-13:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 427.41 | 0.00 | 01-JAN-00:10 | 221334.85 | 02-JAN-08:10 |
NaturalGas:HVAC | 427.41 | 0.00 | 01-JAN-00:10 | 221334.85 | 02-JAN-08:10 |
Heating:NaturalGas | 427.41 | 0.00 | 01-JAN-00:10 | 221334.85 | 02-JAN-08:10 |
General:Heating:NaturalGas | 427.41 | 0.00 | 01-JAN-00:10 | 221334.85 | 02-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1358.76 | 0.00 | 01-JAN-00:10 | 333899.67 | 02-JAN-08:10 |
EnergyTransfer:Building | 516.04 | 0.00 | 01-JAN-00:10 | 156831.79 | 02-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 106.11 | 0.00 | 01-JAN-00:10 | 27488.01 | 06-FEB-08:10 |
Heating:EnergyTransfer | 92.53 | 0.00 | 01-JAN-00:10 | 156831.79 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 13.14 | 0.00 | 01-JAN-00:10 | 27488.01 | 06-FEB-08:10 |
General:Heating:EnergyTransfer | 92.53 | 0.00 | 01-JAN-00:10 | 156831.79 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 13.14 | 0.00 | 01-JAN-00:10 | 27488.01 | 06-FEB-08:10 |
Cooling:EnergyTransfer | 423.51 | 0.00 | 01-JAN-00:10 | 94798.90 | 18-AUG-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 92.97 | 0.00 | 01-JAN-00:10 | 15831.82 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer | 423.51 | 0.00 | 01-JAN-00:10 | 94798.90 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 92.97 | 0.00 | 01-JAN-00:10 | 15831.82 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 55.43 | 0.00 | 01-JAN-00:10 | 9736.19 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 3.50 | 0.00 | 01-JAN-00:10 | 9736.19 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 3.50 | 0.00 | 01-JAN-00:10 | 9736.19 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 51.94 | 0.00 | 01-JAN-00:10 | 9370.90 | 25-OCT-20:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 51.94 | 0.00 | 01-JAN-00:10 | 9370.90 | 25-OCT-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 43.49 | 0.00 | 01-JAN-00:10 | 12610.61 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 5.06 | 0.00 | 01-JAN-00:10 | 12610.30 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 5.06 | 0.00 | 01-JAN-00:10 | 12610.30 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 38.43 | 0.00 | 01-JAN-00:10 | 8210.18 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 38.43 | 0.00 | 01-JAN-00:10 | 8210.18 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 43.27 | 0.00 | 01-JAN-00:10 | 14005.83 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 5.71 | 0.00 | 01-JAN-00:10 | 14005.83 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 5.71 | 0.00 | 01-JAN-00:10 | 14005.83 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 37.56 | 0.00 | 01-JAN-00:10 | 8232.19 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 37.56 | 0.00 | 01-JAN-00:10 | 8232.19 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 42.17 | 0.00 | 01-JAN-00:10 | 14984.80 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 6.72 | 0.00 | 01-JAN-00:10 | 14984.80 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 6.72 | 0.00 | 01-JAN-00:10 | 14984.80 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 35.45 | 0.00 | 01-JAN-00:10 | 8097.80 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 35.45 | 0.00 | 01-JAN-00:10 | 8097.80 | 18-AUG-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 71.07 | 0.00 | 01-JAN-00:10 | 32536.58 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 13.91 | 0.00 | 01-JAN-00:10 | 32536.58 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 13.91 | 0.00 | 01-JAN-00:10 | 32536.58 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 57.15 | 0.00 | 01-JAN-00:10 | 14694.56 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 57.15 | 0.00 | 01-JAN-00:10 | 14694.56 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE5 | 37.02 | 0.00 | 01-JAN-00:10 | 16679.96 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 8.21 | 0.00 | 01-JAN-00:10 | 16679.96 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 8.21 | 0.00 | 01-JAN-00:10 | 16679.96 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 28.81 | 0.00 | 01-JAN-00:10 | 7637.43 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 28.81 | 0.00 | 01-JAN-00:10 | 7637.43 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE6 | 36.76 | 0.00 | 01-JAN-00:10 | 16791.40 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 8.56 | 0.00 | 01-JAN-00:10 | 16791.40 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 8.56 | 0.00 | 01-JAN-00:10 | 16791.40 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 28.20 | 0.00 | 01-JAN-00:10 | 7587.86 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 28.20 | 0.00 | 01-JAN-00:10 | 7587.86 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE7 | 36.91 | 0.00 | 01-JAN-00:10 | 17512.29 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 10.14 | 0.00 | 01-JAN-00:10 | 17512.29 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 10.14 | 0.00 | 01-JAN-00:10 | 17512.29 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 26.77 | 0.00 | 01-JAN-00:10 | 7576.10 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 26.77 | 0.00 | 01-JAN-00:10 | 7576.10 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE8 | 43.81 | 0.00 | 01-JAN-00:10 | 19475.72 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 17.58 | 0.00 | 01-JAN-00:10 | 19475.72 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 17.58 | 0.00 | 01-JAN-00:10 | 19475.72 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 26.23 | 0.00 | 01-JAN-00:10 | 8455.87 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 26.23 | 0.00 | 01-JAN-00:10 | 8455.87 | 18-AUG-13:00 |
EnergyTransfer:HVAC | 842.73 | 0.00 | 01-JAN-00:10 | 208018.20 | 08-JUL-12:30 |
HeatingCoils:EnergyTransfer | 341.93 | 0.00 | 01-JAN-00:10 | 177067.88 | 02-JAN-08:10 |
CoolingCoils:EnergyTransfer | 500.79 | 0.00 | 01-JAN-00:10 | 208018.20 | 08-JUL-12:30 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 13.138 | -92.973 | 0.000 | 0.000 | 25.114 | 95.826 | 26.249 | 22.380 | 0.000 | 2.245 | 0.002 | 0.000 | -8.938 | 0.000 | -28.533 | -54.508 |
SMSTORE1 | 0.000 | 0.000 | 3.498 | -51.936 | 0.000 | 0.000 | 12.374 | 57.583 | 13.125 | 11.106 | 0.000 | 1.229 | 0.001 | 0.000 | -4.706 | 0.000 | -14.802 | -27.471 |
SMSTORE2 | 0.000 | 0.000 | 5.063 | -38.425 | 0.000 | 0.000 | 7.529 | 40.956 | 10.421 | 11.091 | 0.000 | 1.213 | 0.001 | 0.000 | -4.658 | 0.000 | -15.040 | -18.150 |
SMSTORE3 | 0.000 | 0.000 | 5.709 | -37.563 | 0.000 | 0.000 | 7.537 | 40.956 | 10.421 | 11.104 | 0.000 | 1.213 | 0.003 | 0.000 | -4.609 | 0.000 | -14.994 | -19.773 |
SMSTORE4 | 0.000 | 0.000 | 6.720 | -35.445 | 0.000 | 0.000 | 7.549 | 40.956 | 10.421 | 11.125 | 0.000 | 1.213 | 0.002 | 0.000 | -4.552 | 0.000 | -14.930 | -23.056 |
LGSTORE2 | 0.000 | 0.000 | 13.914 | -57.151 | 0.000 | 0.000 | 25.959 | 43.277 | 19.173 | 22.345 | 0.000 | 2.183 | 0.002 | 0.000 | -8.813 | 0.000 | -27.059 | -33.828 |
SMSTORE5 | 0.000 | 0.000 | 8.208 | -28.811 | 0.000 | 0.000 | 12.985 | 22.197 | 9.586 | 11.160 | 0.000 | 1.215 | 0.000 | 0.000 | -4.402 | 0.000 | -14.872 | -17.267 |
SMSTORE6 | 0.000 | 0.000 | 8.557 | -28.202 | 0.000 | 0.000 | 12.994 | 22.197 | 9.586 | 11.170 | 0.000 | 1.215 | 0.001 | 0.000 | -4.380 | 0.000 | -14.846 | -18.291 |
SMSTORE7 | 0.000 | 0.000 | 10.144 | -26.766 | 0.000 | 0.000 | 13.014 | 22.197 | 9.586 | 11.196 | 0.000 | 1.215 | 0.000 | 0.000 | -4.311 | 0.000 | -14.776 | -21.501 |
SMSTORE8 | 0.000 | 0.000 | 17.577 | -26.233 | 0.000 | 0.000 | 13.044 | 22.197 | 9.586 | 11.261 | 0.000 | 1.252 | 0.000 | 0.000 | -4.058 | 0.000 | -17.006 | -27.621 |
Total Facility | 0.000 | 0.000 | 92.530 | -423.506 | 0.000 | 0.000 | 138.099 | 408.342 | 128.154 | 133.938 | 0.000 | 14.192 | 0.011 | 0.000 | -53.428 | 0.000 | -176.856 | -261.465 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -37597.78 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 402.80 | 0.00 | 0.00 | 37183.45 | 0.00 | -0.00 | 0.00 | -137.10 | 0.00 |
SMSTORE1 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -20326.48 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 199.44 | 0.00 | 0.00 | 20124.83 | 0.00 | -0.00 | 0.00 | -72.11 | 0.00 |
SMSTORE2 | 25-AUG-06:02 | 0.00 | 0.00 | 0.00 | -23046.16 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 23059.39 | 0.00 | -77.22 | 0.00 | -10.33 | 0.00 |
SMSTORE3 | 25-AUG-06:02 | 0.00 | 0.00 | 0.00 | -23025.64 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 23039.91 | 0.00 | -78.18 | 0.00 | -10.41 | 0.00 |
SMSTORE4 | 25-AUG-06:02 | 0.00 | 0.00 | 0.00 | -22840.79 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22852.97 | 0.00 | -76.28 | 0.00 | -10.22 | 0.00 |
LGSTORE2 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -35949.23 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 402.30 | 0.00 | 0.00 | 35528.40 | 0.00 | -0.00 | 0.00 | -130.10 | 0.00 |
SMSTORE5 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -18572.64 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 202.56 | 0.00 | 0.00 | 18365.01 | 0.00 | -0.00 | 0.00 | -69.25 | 0.00 |
SMSTORE6 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -18461.59 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 203.26 | 0.00 | 0.00 | 18252.52 | 0.00 | -0.00 | 0.00 | -68.51 | 0.00 |
SMSTORE7 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -18313.53 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 204.21 | 0.00 | 0.00 | 18101.52 | 0.00 | -0.00 | 0.00 | -66.51 | 0.00 |
SMSTORE8 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -19449.71 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 205.79 | 0.00 | 0.00 | 19240.02 | 0.00 | -0.00 | 0.00 | -70.42 | 0.00 |
Total Facility | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -176683.80 | 0.00 | 0.00 | 295.52 | 450.00 | 1450.75 | 2457.29 | 0.00 | 0.00 | 172797.65 | 0.00 | 0.00 | 0.00 | -767.40 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 61148.69 | 0.00 | 0.00 | 0.00 | 274.66 | 75.00 | 74.62 | 567.95 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1400.83 | -60740.10 |
SMSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 32091.58 | 0.00 | 0.00 | 0.00 | 132.11 | 37.50 | 37.31 | 261.74 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -772.34 | -31787.90 |
SMSTORE2 | 02-JAN-07:01 | 0.00 | 0.00 | 32544.74 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -546.52 | 0.00 | -30.03 | -32042.51 |
SMSTORE3 | 02-JAN-07:01 | 0.00 | 0.00 | 32400.27 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -536.60 | 0.00 | -29.49 | -31908.50 |
SMSTORE4 | 02-JAN-07:01 | 0.00 | 0.00 | 32397.66 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -530.20 | 0.00 | -29.14 | -31912.64 |
LGSTORE2 | 02-JAN-08:12 | 0.00 | 0.00 | 57890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 853.61 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1474.67 | -57418.35 |
SMSTORE5 | 02-JAN-08:12 | 0.00 | 0.00 | 30576.73 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 425.15 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -818.51 | -30257.68 |
SMSTORE6 | 02-JAN-08:12 | 0.00 | 0.00 | 30477.73 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 425.93 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -817.55 | -30160.42 |
SMSTORE7 | 02-JAN-08:12 | 0.00 | 0.00 | 30449.11 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 429.59 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -813.55 | -30139.47 |
SMSTORE8 | 02-JAN-08:12 | 0.00 | 0.00 | 32382.16 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 439.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -886.72 | -32009.05 |
Total Facility | 02-JAN-08:61 | 0.00 | 0.00 | 292429.90 | 0.00 | 0.00 | 0.00 | 753.59 | 450.00 | 1452.23 | 3441.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8807.82 | -289719.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9795 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9795 | 0.2079 | 1.0000 | Not calculated | 0.4115 | 0.2079 | ||
PSZ-AC_2:2 | 1.0568 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0664 | 0.1929 | 1.0000 | Not calculated | 0.2057 | 0.1929 | ||
PSZ-AC_3:3 | 1.0777 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0777 | 0.1909 | 1.0000 | Not calculated | 0.2057 | 0.1909 | ||
PSZ-AC_4:4 | 1.0711 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0746 | 0.1915 | 1.0000 | Not calculated | 0.2057 | 0.1915 | ||
PSZ-AC_5:5 | 1.0709 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0709 | 0.1921 | 1.0000 | Not calculated | 0.2057 | 0.1921 | ||
PSZ-AC_6:6 | 1.8227 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8816 | 0.2187 | 1.0000 | Not calculated | 0.4115 | 0.2187 | ||
PSZ-AC_7:7 | 0.9812 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9812 | 0.2097 | 1.0000 | Not calculated | 0.2057 | 0.2097 | ||
PSZ-AC_8:8 | 0.9762 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9762 | 0.2108 | 1.0000 | Not calculated | 0.2057 | 0.2108 | ||
PSZ-AC_9:9 | 0.9727 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9729 | 0.2115 | 1.0000 | Not calculated | 0.2057 | 0.2115 | ||
PSZ-AC_10:10 | 1.0555 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0611 | 0.1939 | 1.0000 | Not calculated | 0.2057 | 0.1939 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9795 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9795 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2079 | ||
PSZ-AC_2:2 | 1.0568 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0568 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1947 | ||
PSZ-AC_3:3 | 1.0777 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0777 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1909 | ||
PSZ-AC_4:4 | 1.0711 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0711 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1921 | ||
PSZ-AC_5:5 | 1.0709 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0709 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1921 | ||
PSZ-AC_6:6 | 1.8227 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8227 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2257 | ||
PSZ-AC_7:7 | 0.9812 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9812 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2097 | ||
PSZ-AC_8:8 | 0.9762 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9762 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2108 | ||
PSZ-AC_9:9 | 0.9727 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9727 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2115 | ||
PSZ-AC_10:10 | 1.0555 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0555 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1949 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9795 | 1.9795 | 1.9795 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0568 | 1.0568 | 1.0568 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0777 | 1.0777 | 1.0777 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0711 | 1.0711 | 1.0711 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0709 | 1.0709 | 1.0709 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8227 | 1.8227 | 1.8227 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9812 | 0.9812 | 0.9812 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9762 | 0.9762 | 0.9762 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9727 | 0.9727 | 0.9727 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0555 | 1.0555 | 1.0555 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9795 | 1.9795 | 1.9795 | 1.9795 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0568 | 1.0664 | 1.0568 | 1.0568 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0777 | 1.0777 | 1.0777 | 1.0777 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0711 | 1.0746 | 1.0711 | 1.0711 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0709 | 1.0709 | 1.0709 | 1.0709 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8227 | 1.8816 | 1.8227 | 1.8227 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9812 | 0.9812 | 0.9812 | 0.9812 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9762 | 0.9762 | 0.9762 | 0.9762 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9727 | 0.9729 | 0.9727 | 0.9727 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0555 | 1.0611 | 1.0555 | 1.0555 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9795 | 1.9795 | 1.9795 | No | 0.4115 | 0.3356 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0568 | 1.0568 | 1.0568 | No | 0.2057 | 0.3557 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0777 | 1.0777 | 1.0777 | No | 0.2057 | 0.3508 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0711 | 1.0711 | 1.0711 | No | 0.2057 | 0.3474 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0709 | 1.0709 | 1.0709 | No | 0.2057 | 0.3423 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8227 | 1.8227 | 1.8227 | No | 0.4115 | 0.3561 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9812 | 0.9812 | 0.9812 | No | 0.2057 | 0.3331 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9762 | 0.9762 | 0.9762 | No | 0.2057 | 0.3333 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9727 | 0.9727 | 0.9727 | No | 0.2057 | 0.3270 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0555 | 1.0555 | 1.0555 | No | 0.2057 | 0.2699 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9795 | 1.9795 | 1.9795 | 1.9795 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0568 | 1.0568 | 1.0568 | 1.0568 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0777 | 1.0777 | 1.0777 | 1.0777 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0711 | 1.0711 | 1.0711 | 1.0711 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0709 | 1.0709 | 1.0709 | 1.0709 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8227 | 1.8227 | 1.8227 | 1.8227 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9812 | 0.9812 | 0.9812 | 0.9812 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9762 | 0.9762 | 0.9762 | 0.9762 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9727 | 0.9727 | 0.9727 | 0.9727 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0555 | 1.0555 | 1.0555 | 1.0555 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 427.41 | 221334.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 121.41 | 49104.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 408.34 | 26261.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.37 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 99.85 | 9127.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.08 | 2237.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 844.21 |
Natural Gas | 0.00 | 427.41 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1271.62 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 195.35 |
Space Heating | 0.00 |
Space Cooling | 58.08 |
Fans (All) | 47.77 |
Service Water Heating | 12.48 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 403.87 |
Subtotal | 403.87 |
Natural Gas [MJ/m2] | |
Space Heating | 204.47 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 204.47 |
Subtotal | 204.47 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 32.11 |
Space Heating | 33.61 |
Space Cooling | 9.55 |
Fans (All) | 7.85 |
Service Water Heating | 2.05 |
Receptacle Equipment | 10.08 |
Miscellaneous | 4.75 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8660.33 | 99.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8651.17 | 108.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8687.83 | 72.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8726.17 | 33.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8741.67 | 18.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8736.50 | 23.50 | 0.00 | 0.00 | 0.00 |
Min | 8651.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 108.83 | 0.00 | 0.00 | 0.00 |
Average | 8719.47 | 40.53 | 0.00 | 0.00 | 0.00 |
Sum | 87194.67 | 405.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25463.33 | 11.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25463.50 | 11.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25464.00 | 11.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93191.00 | 20.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45902.00 | 10.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45902.00 | 10.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45902.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45901.50 | 10.50 | 0.00 | 0.00 | 0.00 |
Min | 25463.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93191.00 | 20.00 | 0.00 | 0.00 | 0.00 |
Average | 48600.78 | 9.42 | 0.00 | 0.00 | 0.00 |
Sum | 486007.83 | 94.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 7850.33 | 909.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8458.17 | 301.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7400.17 | 1359.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7400.67 | 1359.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7399.00 | 1361.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 7325.17 | 1434.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 7325.33 | 1434.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 7315.83 | 1444.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 7320.00 | 1440.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 7351.33 | 1408.67 | 0.00 | 0.00 | 0.00 |
Min | 7315.83 | 301.83 | 0.00 | 0.00 | 0.00 |
Max | 8458.17 | 1444.17 | 0.00 | 0.00 | 0.00 |
Average | 7514.60 | 1245.40 | 0.00 | 0.00 | 0.00 |
Sum | 75146.00 | 12454.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 84372.50 | 4668.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 42107.33 | 1669.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24000.83 | 1474.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 23989.83 | 1485.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 23863.17 | 1611.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 84315.17 | 8895.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 41371.33 | 4540.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 41235.67 | 4676.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 41021.00 | 4891.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 41017.00 | 4895.00 | 0.00 | 0.00 | 0.00 |
Min | 23863.17 | 1474.17 | 0.00 | 0.00 | 0.00 |
Max | 84372.50 | 8895.83 | 0.00 | 0.00 | 0.00 |
Average | 44729.38 | 3880.82 | 0.00 | 0.00 | 0.00 |
Sum | 447293.83 | 38808.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:33
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121193E+10 | 12130.90 | 11-JAN-19:02 | -6.0 | -8.8 | 0.106534E+10 | 1275.40 | 01-JAN-18:00 | -6.0 | -8.8 |
February | 0.112162E+10 | 11597.87 | 08-FEB-19:42 | -4.9 | -7.7 | 0.961623E+09 | 1275.40 | 05-FEB-18:00 | -4.9 | -7.7 |
March | 0.327475E+10 | 9971.73 | 17-MAR-23:03 | -1.7 | -1.9 | 0.107609E+10 | 1470.47 | 03-MAR-13:00 | -1.7 | -1.9 |
April | 0.505529E+10 | 7990.26 | 08-APR-13:00 | 22.80 | 16.08 | 0.115730E+10 | 1685.98 | 08-APR-12:39 | 22.80 | 16.08 |
May | 0.797338E+10 | 13538.43 | 30-MAY-07:03 | 23.17 | 16.07 | 0.135952E+10 | 1685.98 | 28-MAY-16:00 | 23.17 | 16.07 |
June | 0.124478E+11 | 34146.63 | 22-JUN-07:02 | 23.98 | 15.88 | 0.135450E+10 | 1686.01 | 18-JUN-17:40 | 23.98 | 15.88 |
July | 0.159824E+11 | 36344.89 | 11-JUL-07:02 | 22.30 | 16.06 | 0.141285E+10 | 1686.03 | 30-JUL-12:50 | 27.02 | 23.90 |
August | 0.170133E+11 | 35598.57 | 19-AUG-07:02 | 21.28 | 16.54 | 0.139409E+10 | 1686.06 | 11-AUG-12:00 | 21.28 | 16.54 |
September | 0.125007E+11 | 37601.25 | 02-SEP-07:02 | 21.70 | 16.23 | 0.136461E+10 | 1686.02 | 04-SEP-17:00 | 23.90 | 19.12 |
October | 0.988972E+10 | 24125.50 | 06-OCT-07:03 | 20.00 | 18.15 | 0.135583E+10 | 1685.96 | 22-OCT-17:00 | 17.80 | 16.73 |
November | 0.439831E+10 | 10800.16 | 24-NOV-00:02 | -3.3 | -5.8 | 0.109048E+10 | 1685.85 | 04-NOV-12:20 | -3.3 | -5.8 |
December | 0.210380E+10 | 10715.22 | 22-DEC-00:03 | -3.3 | -6.0 | 0.107100E+10 | 1314.99 | 17-DEC-13:00 | -3.3 | -6.0 |
Annual Sum or Average | 0.929731E+11 | 0.146632E+11 | ||||||||
Minimum of Months | 0.112162E+10 | 7990.26 | -6.0 | -8.8 | 0.961623E+09 | 1275.40 | -6.0 | -8.8 | ||
Maximum of Months | 0.170133E+11 | 37601.25 | 23.98 | 18.15 | 0.141285E+10 | 1686.06 | 27.02 | 23.90 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720605E+09 | 5342.85 | 08-JAN-11:23 | -3.5 | -4.6 | 0.550256E+09 | 767.97 | 22-JAN-18:00 | 6.10 | 5.30 |
February | 0.693533E+09 | 5435.06 | 08-FEB-10:23 | -3.9 | -6.7 | 0.497628E+09 | 778.09 | 20-FEB-18:00 | 3.90 | 2.68 |
March | 0.176208E+10 | 3809.59 | 29-MAR-19:00 | 3.90 | 3.17 | 0.569400E+09 | 842.88 | 26-MAR-17:00 | 3.90 | 3.17 |
April | 0.284083E+10 | 14696.86 | 16-APR-17:01 | 21.93 | 13.37 | 0.607722E+09 | 842.97 | 08-APR-12:00 | 21.93 | 13.37 |
May | 0.477943E+10 | 16971.69 | 27-MAY-22:43 | 18.40 | 10.63 | 0.692806E+09 | 842.97 | 29-MAY-16:49 | 23.17 | 17.15 |
June | 0.712565E+10 | 19157.28 | 22-JUN-07:02 | 23.98 | 15.88 | 0.676454E+09 | 842.98 | 17-JUN-12:39 | 23.98 | 15.88 |
July | 0.880713E+10 | 19836.80 | 11-JUL-07:02 | 22.30 | 16.06 | 0.706429E+09 | 843.00 | 16-JUL-12:30 | 31.70 | 22.52 |
August | 0.923373E+10 | 19589.99 | 19-AUG-07:02 | 21.28 | 16.54 | 0.696653E+09 | 843.00 | 11-AUG-12:50 | 21.28 | 16.54 |
September | 0.707961E+10 | 20327.27 | 02-SEP-07:02 | 21.70 | 16.23 | 0.681208E+09 | 842.98 | 08-SEP-12:09 | 24.90 | 19.74 |
October | 0.544933E+10 | 17600.38 | 25-OCT-20:07 | 17.70 | 8.13 | 0.693756E+09 | 842.96 | 20-OCT-12:00 | 17.70 | 8.13 |
November | 0.228131E+10 | 4659.65 | 22-NOV-09:23 | -0.6 | -2.9 | 0.580872E+09 | 842.92 | 04-NOV-12:00 | -0.6 | -2.9 |
December | 0.116320E+10 | 3866.30 | 21-DEC-12:33 | 2.60 | -1.8 | 0.560513E+09 | 829.29 | 17-DEC-18:00 | 2.60 | -1.8 |
Annual Sum or Average | 0.519364E+11 | 0.751370E+10 | ||||||||
Minimum of Months | 0.693533E+09 | 3809.59 | -3.9 | -6.7 | 0.497628E+09 | 767.97 | -0.6 | -2.9 | ||
Maximum of Months | 0.923373E+10 | 20327.27 | 23.98 | 16.54 | 0.706429E+09 | 843.00 | 31.70 | 22.52 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420542E+09 | 3509.11 | 25-JAN-09:13 | 4.07 | 0.90 | 0.317180E+09 | 637.68 | 28-JAN-13:09 | 5.60 | 4.34 |
February | 0.414671E+09 | 5855.78 | 26-FEB-11:32 | -5.4 | -6.4 | 0.288104E+09 | 637.68 | 11-FEB-13:50 | -5.4 | -6.4 |
March | 0.135860E+10 | 4162.67 | 30-MAR-07:01 | 2.30 | 1.13 | 0.334246E+09 | 702.43 | 27-MAR-16:49 | 2.30 | 1.13 |
April | 0.214694E+10 | 4666.95 | 08-APR-12:30 | 23.60 | 16.18 | 0.350963E+09 | 842.97 | 08-APR-12:00 | 22.80 | 16.08 |
May | 0.337951E+10 | 9336.15 | 30-MAY-06:03 | 20.47 | 15.45 | 0.416968E+09 | 842.93 | 27-MAY-12:30 | 20.47 | 15.45 |
June | 0.529592E+10 | 19616.42 | 23-JUN-06:02 | 21.38 | 17.00 | 0.416565E+09 | 842.96 | 24-JUN-12:00 | 27.80 | 23.34 |
July | 0.655647E+10 | 20267.91 | 11-JUL-06:02 | 20.87 | 15.63 | 0.420004E+09 | 842.98 | 01-JUL-12:09 | 20.87 | 15.63 |
August | 0.710370E+10 | 23049.48 | 25-AUG-06:02 | 17.88 | 13.11 | 0.431711E+09 | 842.98 | 05-AUG-12:00 | 17.88 | 13.11 |
September | 0.515616E+10 | 20421.31 | 02-SEP-06:02 | 21.70 | 16.19 | 0.410240E+09 | 842.97 | 02-SEP-12:09 | 24.50 | 17.34 |
October | 0.405855E+10 | 15830.47 | 06-OCT-06:03 | 19.50 | 17.97 | 0.408209E+09 | 842.96 | 14-OCT-12:20 | 18.67 | 16.24 |
November | 0.176316E+10 | 3457.14 | 04-NOV-13:00 | 17.80 | 12.74 | 0.329742E+09 | 842.91 | 04-NOV-12:00 | 17.80 | 12.74 |
December | 0.771438E+09 | 4060.36 | 11-DEC-10:33 | 1.70 | 0.81 | 0.317017E+09 | 637.68 | 23-DEC-13:09 | 3.30 | 2.12 |
Annual Sum or Average | 0.384257E+11 | 0.444095E+10 | ||||||||
Minimum of Months | 0.414671E+09 | 3457.14 | -5.4 | -6.4 | 0.288104E+09 | 637.68 | -5.4 | -6.4 | ||
Maximum of Months | 0.710370E+10 | 23049.48 | 23.60 | 17.97 | 0.431711E+09 | 842.98 | 27.80 | 23.34 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354359E+09 | 5521.00 | 05-JAN-10:32 | -4.3 | -6.9 | 0.317179E+09 | 637.68 | 14-JAN-13:00 | -6.7 | -7.4 |
February | 0.353377E+09 | 5436.89 | 13-FEB-19:33 | -3.9 | -6.6 | 0.288102E+09 | 637.68 | 04-FEB-13:20 | -3.9 | -6.6 |
March | 0.122535E+10 | 4008.22 | 29-MAR-07:01 | 3.07 | 1.14 | 0.333277E+09 | 702.43 | 27-MAR-16:40 | 3.07 | 1.14 |
April | 0.200204E+10 | 4529.89 | 08-APR-12:30 | 23.60 | 16.18 | 0.349529E+09 | 842.97 | 08-APR-12:00 | 22.80 | 16.08 |
May | 0.327672E+10 | 9100.43 | 30-MAY-06:03 | 20.47 | 15.45 | 0.415252E+09 | 842.93 | 27-MAY-12:30 | 20.47 | 15.45 |
June | 0.527310E+10 | 19560.82 | 23-JUN-06:02 | 21.38 | 17.00 | 0.416557E+09 | 842.96 | 24-JUN-12:00 | 27.80 | 23.34 |
July | 0.656127E+10 | 20246.21 | 11-JUL-06:02 | 20.87 | 15.63 | 0.420001E+09 | 842.98 | 01-JUL-12:09 | 20.87 | 15.63 |
August | 0.712144E+10 | 23028.94 | 25-AUG-06:02 | 17.88 | 13.11 | 0.431709E+09 | 842.99 | 05-AUG-12:00 | 17.88 | 13.11 |
September | 0.513381E+10 | 20392.22 | 02-SEP-06:02 | 21.70 | 16.19 | 0.410215E+09 | 842.97 | 02-SEP-12:09 | 24.50 | 17.34 |
October | 0.397203E+10 | 15678.89 | 06-OCT-06:03 | 19.50 | 17.97 | 0.407026E+09 | 842.96 | 14-OCT-12:20 | 18.67 | 16.24 |
November | 0.162145E+10 | 4795.74 | 24-NOV-09:23 | -1.1 | -3.5 | 0.327443E+09 | 842.89 | 04-NOV-12:20 | -1.1 | -3.5 |
December | 0.668875E+09 | 4773.66 | 31-DEC-10:43 | -1.1 | -4.5 | 0.316931E+09 | 637.68 | 02-DEC-13:39 | -1.1 | -4.5 |
Annual Sum or Average | 0.375638E+11 | 0.443322E+10 | ||||||||
Minimum of Months | 0.353377E+09 | 4008.22 | -4.3 | -6.9 | 0.288102E+09 | 637.68 | -6.7 | -7.4 | ||
Maximum of Months | 0.712144E+10 | 23028.94 | 23.60 | 17.97 | 0.431709E+09 | 842.99 | 27.80 | 23.34 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256475E+09 | 5177.26 | 04-JAN-11:43 | -2.8 | -5.7 | 0.317182E+09 | 637.68 | 07-JAN-13:30 | 0.60 | -4.2 |
February | 0.249970E+09 | 3377.92 | 01-FEB-09:33 | 4.63 | 1.45 | 0.288103E+09 | 637.68 | 04-FEB-13:00 | 2.20 | 1.69 |
March | 0.103652E+10 | 3496.78 | 29-MAR-07:01 | 3.07 | 1.14 | 0.332009E+09 | 702.43 | 27-MAR-16:30 | 3.07 | 1.14 |
April | 0.178654E+10 | 4238.98 | 08-APR-12:50 | 23.07 | 16.12 | 0.347329E+09 | 842.97 | 08-APR-12:50 | 23.07 | 16.12 |
May | 0.304796E+10 | 7696.65 | 30-MAY-06:03 | 20.47 | 15.45 | 0.412151E+09 | 842.92 | 27-MAY-12:30 | 20.47 | 15.45 |
June | 0.507351E+10 | 19421.12 | 23-JUN-06:02 | 21.38 | 17.00 | 0.416514E+09 | 842.95 | 24-JUN-12:00 | 27.80 | 23.34 |
July | 0.638286E+10 | 20074.78 | 11-JUL-06:02 | 20.87 | 15.63 | 0.419968E+09 | 842.98 | 22-JUL-12:00 | 26.70 | 23.40 |
August | 0.693643E+10 | 22844.10 | 25-AUG-06:02 | 17.88 | 13.11 | 0.431675E+09 | 842.97 | 26-AUG-12:09 | 25.10 | 18.26 |
September | 0.494134E+10 | 20205.46 | 02-SEP-06:02 | 21.70 | 16.19 | 0.410120E+09 | 842.97 | 02-SEP-12:09 | 24.50 | 17.34 |
October | 0.377734E+10 | 14128.06 | 06-OCT-06:03 | 19.50 | 17.97 | 0.404953E+09 | 842.95 | 21-OCT-12:20 | 19.07 | 15.73 |
November | 0.143234E+10 | 4074.05 | 25-NOV-10:23 | 1.65 | -0.6 | 0.324264E+09 | 842.90 | 04-NOV-12:20 | 1.65 | -0.6 |
December | 0.524334E+09 | 3775.73 | 21-DEC-13:13 | 2.97 | -1.7 | 0.316849E+09 | 637.68 | 16-DEC-13:39 | 2.97 | -1.7 |
Annual Sum or Average | 0.354456E+11 | 0.442112E+10 | ||||||||
Minimum of Months | 0.249970E+09 | 3377.92 | -2.8 | -5.7 | 0.288103E+09 | 637.68 | 0.60 | -4.2 | ||
Maximum of Months | 0.693643E+10 | 22844.10 | 23.07 | 17.97 | 0.431675E+09 | 842.98 | 27.80 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184139E+09 | 10466.28 | 10-JAN-11:32 | -2.6 | -5.3 | 0.108441E+10 | 1700.53 | 07-JAN-15:09 | -2.6 | -5.3 |
February | 0.175750E+09 | 7830.05 | 04-FEB-11:33 | 2.80 | 2.22 | 0.987306E+09 | 1700.53 | 18-FEB-15:09 | 6.70 | 3.12 |
March | 0.134719E+10 | 9786.22 | 17-MAR-10:13 | -1.1 | -2.4 | 0.113287E+10 | 1994.92 | 27-MAR-16:30 | 21.65 | 15.87 |
April | 0.266546E+10 | 6842.81 | 12-APR-08:63 | 5.78 | 0.39 | 0.117962E+10 | 2247.80 | 08-APR-14:09 | 5.78 | 0.39 |
May | 0.483405E+10 | 15163.93 | 30-MAY-07:03 | 23.17 | 16.07 | 0.139078E+10 | 2247.83 | 20-MAY-14:09 | 23.17 | 16.07 |
June | 0.841591E+10 | 32351.37 | 22-JUN-07:02 | 23.98 | 15.88 | 0.142886E+10 | 2247.93 | 03-JUN-14:00 | 23.98 | 15.88 |
July | 0.108374E+11 | 35051.10 | 11-JUL-07:02 | 22.30 | 16.06 | 0.143780E+10 | 2248.00 | 01-JUL-14:00 | 22.30 | 16.06 |
August | 0.118827E+11 | 33863.00 | 19-AUG-07:02 | 21.28 | 16.54 | 0.147980E+10 | 2247.99 | 26-AUG-14:00 | 25.60 | 19.37 |
September | 0.816314E+10 | 35952.78 | 02-SEP-07:02 | 21.70 | 16.23 | 0.140788E+10 | 2248.00 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.615292E+10 | 23144.65 | 06-OCT-07:03 | 20.00 | 18.15 | 0.137161E+10 | 2247.93 | 14-OCT-14:09 | 18.30 | 16.20 |
November | 0.203487E+10 | 6796.55 | 30-NOV-10:13 | 5.00 | 3.51 | 0.108873E+10 | 2247.76 | 04-NOV-14:20 | 5.00 | 3.51 |
December | 0.457560E+09 | 8721.12 | 01-DEC-20:53 | 1.10 | -2.2 | 0.108625E+10 | 1700.53 | 02-DEC-15:20 | 6.50 | 1.30 |
Annual Sum or Average | 0.571512E+11 | 0.150759E+11 | ||||||||
Minimum of Months | 0.175750E+09 | 6796.55 | -2.6 | -5.3 | 0.987306E+09 | 1700.53 | -2.6 | -5.3 | ||
Maximum of Months | 0.118827E+11 | 35952.78 | 23.98 | 18.15 | 0.147980E+10 | 2248.00 | 25.60 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83276815.36 | 5193.89 | 31-JAN-18:33 | -2.6 | -6.5 | 0.542192E+09 | 850.24 | 07-JAN-15:09 | -2.6 | -6.5 |
February | 74112746.76 | 5243.16 | 03-FEB-18:53 | -2.8 | -5.0 | 0.493639E+09 | 850.24 | 18-FEB-15:09 | 6.70 | 3.12 |
March | 0.629174E+09 | 4339.77 | 08-MAR-20:23 | 1.10 | 1.10 | 0.566020E+09 | 997.42 | 27-MAR-16:00 | 21.10 | 15.41 |
April | 0.125784E+10 | 3359.47 | 12-APR-08:63 | 5.78 | 0.39 | 0.588287E+09 | 1123.87 | 08-APR-14:09 | 5.78 | 0.39 |
May | 0.236727E+10 | 7064.50 | 30-MAY-07:03 | 23.17 | 16.07 | 0.692839E+09 | 1123.88 | 20-MAY-14:09 | 23.17 | 16.07 |
June | 0.429406E+10 | 16739.64 | 22-JUN-07:02 | 23.98 | 15.88 | 0.714403E+09 | 1123.93 | 03-JUN-14:00 | 23.98 | 15.88 |
July | 0.558449E+10 | 18110.02 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718864E+09 | 1123.97 | 22-JUL-14:00 | 26.70 | 23.40 |
August | 0.611957E+10 | 17485.17 | 19-AUG-07:02 | 21.28 | 16.54 | 0.739866E+09 | 1123.97 | 05-AUG-14:00 | 21.28 | 16.54 |
September | 0.416310E+10 | 18574.50 | 02-SEP-07:02 | 21.70 | 16.23 | 0.703911E+09 | 1123.97 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.306478E+10 | 10814.45 | 06-OCT-07:03 | 20.00 | 18.15 | 0.684948E+09 | 1123.94 | 14-OCT-14:39 | 18.30 | 16.20 |
November | 0.963453E+09 | 4544.44 | 21-NOV-20:42 | 0.18 | -1.7 | 0.543153E+09 | 1123.85 | 04-NOV-14:20 | 0.18 | -1.7 |
December | 0.210160E+09 | 4321.36 | 01-DEC-20:53 | 1.10 | -2.2 | 0.543107E+09 | 850.24 | 09-DEC-15:50 | 5.40 | 2.25 |
Annual Sum or Average | 0.288113E+11 | 0.753123E+10 | ||||||||
Minimum of Months | 74112746.76 | 3359.47 | -2.8 | -6.5 | 0.493639E+09 | 850.24 | -2.6 | -6.5 | ||
Maximum of Months | 0.611957E+10 | 18574.50 | 23.98 | 18.15 | 0.739866E+09 | 1123.97 | 26.70 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72700338.02 | 4768.55 | 30-JAN-18:42 | -0.7 | -2.7 | 0.542193E+09 | 850.24 | 07-JAN-15:09 | -0.7 | -2.7 |
February | 63613778.15 | 4235.62 | 24-FEB-20:33 | 1.47 | -2.5 | 0.493633E+09 | 850.24 | 04-FEB-15:09 | 1.47 | -2.5 |
March | 0.589958E+09 | 4855.78 | 17-MAR-18:33 | -1.1 | -2.0 | 0.565517E+09 | 997.43 | 27-MAR-16:00 | 21.10 | 15.41 |
April | 0.120094E+10 | 3333.03 | 12-APR-08:63 | 5.78 | 0.39 | 0.586552E+09 | 1123.87 | 08-APR-14:09 | 5.78 | 0.39 |
May | 0.227595E+10 | 6317.49 | 30-MAY-07:03 | 23.17 | 16.07 | 0.689762E+09 | 1123.88 | 20-MAY-14:09 | 23.17 | 16.07 |
June | 0.422170E+10 | 16622.60 | 22-JUN-07:02 | 23.98 | 15.88 | 0.714389E+09 | 1123.93 | 03-JUN-14:00 | 23.98 | 15.88 |
July | 0.551956E+10 | 18001.90 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718856E+09 | 1123.97 | 22-JUL-14:00 | 26.70 | 23.40 |
August | 0.605507E+10 | 17379.06 | 19-AUG-07:02 | 21.28 | 16.54 | 0.739860E+09 | 1123.97 | 05-AUG-14:00 | 21.28 | 16.54 |
September | 0.410024E+10 | 18463.44 | 02-SEP-07:02 | 21.70 | 16.23 | 0.703830E+09 | 1123.97 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.299186E+10 | 10259.86 | 06-OCT-07:03 | 20.00 | 18.15 | 0.683258E+09 | 1123.94 | 14-OCT-14:50 | 18.30 | 16.20 |
November | 0.921659E+09 | 4680.91 | 22-NOV-19:33 | -0.4 | -3.1 | 0.541653E+09 | 1123.85 | 04-NOV-14:20 | -0.4 | -3.1 |
December | 0.189076E+09 | 4316.21 | 21-DEC-10:23 | 1.15 | -2.3 | 0.543096E+09 | 850.24 | 02-DEC-15:50 | 1.15 | -2.3 |
Annual Sum or Average | 0.282023E+11 | 0.752260E+10 | ||||||||
Minimum of Months | 63613778.15 | 3333.03 | -1.1 | -3.1 | 0.493633E+09 | 850.24 | -0.7 | -3.1 | ||
Maximum of Months | 0.605507E+10 | 18463.44 | 23.98 | 18.15 | 0.739860E+09 | 1123.97 | 26.70 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38390259.70 | 2634.29 | 19-JAN-10:25 | 7.80 | 4.48 | 0.542192E+09 | 850.24 | 14-JAN-15:30 | 7.80 | 4.48 |
February | 32055757.75 | 3371.94 | 23-FEB-19:13 | 5.00 | 4.42 | 0.493640E+09 | 850.24 | 04-FEB-15:30 | 5.00 | 4.42 |
March | 0.460920E+09 | 4604.55 | 22-MAR-19:03 | -0.1 | -4.8 | 0.564193E+09 | 997.42 | 27-MAR-16:49 | 21.28 | 15.57 |
April | 0.102178E+10 | 3082.79 | 08-APR-13:10 | 22.43 | 15.95 | 0.582517E+09 | 1123.87 | 08-APR-14:09 | 20.78 | 15.22 |
May | 0.206350E+10 | 5817.17 | 30-MAY-13:00 | 30.00 | 18.00 | 0.682639E+09 | 1123.88 | 20-MAY-14:09 | 30.00 | 18.00 |
June | 0.404611E+10 | 14851.60 | 20-JUN-07:02 | 23.17 | 19.56 | 0.714340E+09 | 1123.93 | 03-JUN-14:00 | 23.17 | 19.56 |
July | 0.541170E+10 | 17845.82 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718840E+09 | 1123.97 | 01-JUL-14:00 | 22.30 | 16.06 |
August | 0.597007E+10 | 17238.86 | 19-AUG-07:02 | 21.28 | 16.54 | 0.739851E+09 | 1123.97 | 26-AUG-14:00 | 25.60 | 19.37 |
September | 0.397009E+10 | 18315.39 | 02-SEP-07:02 | 21.70 | 16.23 | 0.703527E+09 | 1123.97 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.282803E+10 | 8525.14 | 06-OCT-07:03 | 20.00 | 18.15 | 0.679045E+09 | 1123.93 | 14-OCT-14:50 | 18.30 | 16.20 |
November | 0.806504E+09 | 4589.59 | 22-NOV-18:42 | 0.00 | -2.8 | 0.538811E+09 | 1118.89 | 04-NOV-14:09 | 0.00 | -2.8 |
December | 0.116677E+09 | 4118.86 | 28-DEC-19:23 | 1.70 | -2.1 | 0.543110E+09 | 850.24 | 02-DEC-15:09 | 1.70 | -2.1 |
Annual Sum or Average | 0.267658E+11 | 0.750271E+10 | ||||||||
Minimum of Months | 32055757.75 | 2634.29 | -0.1 | -4.8 | 0.493640E+09 | 850.24 | 0.00 | -2.8 | ||
Maximum of Months | 0.597007E+10 | 18315.39 | 30.00 | 19.56 | 0.739851E+09 | 1123.97 | 30.00 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2650165.07 | 618.66 | 19-JAN-12:00 | 7.20 | 3.79 | 0.542193E+09 | 850.24 | 07-JAN-15:09 | 7.20 | 3.79 |
February | 4753168.01 | 3248.44 | 11-FEB-11:23 | 5.25 | 1.70 | 0.493639E+09 | 850.24 | 25-FEB-15:30 | 3.60 | -1.1 |
March | 0.222876E+09 | 3734.58 | 23-MAR-10:43 | 3.12 | -2.0 | 0.562429E+09 | 965.95 | 27-MAR-16:40 | 21.47 | 15.72 |
April | 0.712656E+09 | 3216.81 | 08-APR-12:20 | 23.87 | 16.21 | 0.577602E+09 | 1123.87 | 08-APR-14:20 | 20.97 | 15.19 |
May | 0.180559E+10 | 6157.62 | 30-MAY-13:00 | 30.00 | 18.00 | 0.670356E+09 | 1123.87 | 20-MAY-14:09 | 30.00 | 18.00 |
June | 0.395376E+10 | 15637.64 | 26-JUN-07:02 | 23.40 | 18.26 | 0.714180E+09 | 1123.95 | 24-JUN-14:00 | 23.40 | 18.26 |
July | 0.573045E+10 | 18517.10 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718870E+09 | 1123.98 | 01-JUL-14:39 | 22.30 | 16.06 |
August | 0.649111E+10 | 16241.40 | 22-AUG-07:02 | 26.20 | 18.45 | 0.739890E+09 | 1123.98 | 05-AUG-14:50 | 26.20 | 18.45 |
September | 0.405923E+10 | 19452.11 | 02-SEP-07:02 | 21.70 | 16.23 | 0.702365E+09 | 1123.97 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.264890E+10 | 5589.26 | 04-OCT-13:00 | 25.00 | 18.54 | 0.672333E+09 | 1123.93 | 21-OCT-14:30 | 19.40 | 17.42 |
November | 0.578396E+09 | 2718.21 | 18-NOV-13:15 | 7.20 | 3.66 | 0.535849E+09 | 1110.17 | 04-NOV-14:09 | 7.20 | 3.66 |
December | 23279176.81 | 3144.10 | 14-DEC-11:03 | 5.68 | 1.27 | 0.543108E+09 | 850.24 | 02-DEC-15:09 | 5.68 | 1.27 |
Annual Sum or Average | 0.262336E+11 | 0.747281E+10 | ||||||||
Minimum of Months | 2650165.07 | 618.66 | 3.12 | -2.0 | 0.493639E+09 | 850.24 | 3.60 | -1.1 | ||
Maximum of Months | 0.649111E+10 | 19452.11 | 30.00 | 18.54 | 0.739890E+09 | 1123.98 | 30.00 | 18.81 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412838E+10 | 61148.66 | 02-JAN-08:61 | -11.0 |
February | 0.390128E+10 | 61118.66 | 13-FEB-08:61 | -8.7 |
March | 0.144717E+10 | 61117.89 | 23-MAR-07:01 | -2.9 |
April | 0.460082E+09 | 61096.07 | 03-APR-07:01 | 3.68 |
May | 61080266.56 | 1269.27 | 30-MAY-07:07 | 23.17 |
June | 25874323.17 | 1726.62 | 23-JUN-07:05 | 23.45 |
July | 25236069.43 | 1725.24 | 11-JUL-07:04 | 22.30 |
August | 28263825.98 | 1752.29 | 23-AUG-07:05 | 20.87 |
September | 22883974.03 | 1644.04 | 04-SEP-07:04 | 20.97 |
October | 51818476.19 | 1845.94 | 29-OCT-08:06 | 6.88 |
November | 0.753543E+09 | 61121.54 | 24-NOV-08:61 | -3.5 |
December | 0.223239E+10 | 61120.92 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.131380E+11 | |||
Minimum of Months | 22883974.03 | 1269.27 | -11.0 | |
Maximum of Months | 0.412838E+10 | 61148.66 | 23.45 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122438E+10 | 32091.63 | 02-JAN-08:61 | -11.0 |
February | 0.113399E+10 | 32075.94 | 15-FEB-08:61 | -4.0 |
March | 0.270028E+09 | 32075.94 | 23-MAR-07:01 | -2.9 |
April | 76754422.96 | 23759.21 | 03-APR-07:01 | 3.68 |
May | 20701892.07 | 861.17 | 30-MAY-07:07 | 23.17 |
June | 15585720.52 | 1065.24 | 23-JUN-07:05 | 23.45 |
July | 14275242.34 | 1031.50 | 24-JUL-07:05 | 22.12 |
August | 15421676.60 | 1039.80 | 21-AUG-07:05 | 22.38 |
September | 13634398.82 | 1012.05 | 22-SEP-07:05 | 21.70 |
October | 23318766.41 | 943.26 | 06-OCT-07:05 | 20.00 |
November | 0.159483E+09 | 32075.02 | 25-NOV-08:61 | -1.5 |
December | 0.530148E+09 | 32076.55 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.349772E+10 | |||
Minimum of Months | 13634398.82 | 861.17 | -11.0 | |
Maximum of Months | 0.122438E+10 | 32091.63 | 23.45 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169429E+10 | 32544.74 | 02-JAN-07:01 | -11.6 |
February | 0.148123E+10 | 32530.73 | 12-FEB-08:61 | -10.5 |
March | 0.449549E+09 | 32048.63 | 20-MAR-06:01 | -0.6 |
April | 0.121070E+09 | 32037.26 | 02-APR-07:01 | 4.18 |
May | 22098259.89 | 818.86 | 30-MAY-06:07 | 20.47 |
June | 27103802.41 | 2029.87 | 19-JUN-19:03 | 31.42 |
July | 36462800.73 | 1609.48 | 16-JUL-16:03 | 29.90 |
August | 51563567.47 | 2502.00 | 04-AUG-19:02 | 33.12 |
September | 18209821.69 | 1038.91 | 03-SEP-07:05 | 19.27 |
October | 23898369.53 | 962.58 | 06-OCT-06:05 | 19.50 |
November | 0.289816E+09 | 32062.27 | 23-NOV-08:61 | -2.6 |
December | 0.848093E+09 | 32380.60 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.506338E+10 | |||
Minimum of Months | 18209821.69 | 818.86 | -11.6 | |
Maximum of Months | 0.169429E+10 | 32544.74 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189159E+10 | 32400.27 | 02-JAN-07:01 | -11.6 |
February | 0.162824E+10 | 32385.04 | 12-FEB-08:61 | -10.5 |
March | 0.535492E+09 | 31907.12 | 20-MAR-06:01 | -0.6 |
April | 0.145946E+09 | 31895.04 | 02-APR-07:01 | 4.18 |
May | 24163401.03 | 803.44 | 30-MAY-06:07 | 20.47 |
June | 27072260.47 | 2030.87 | 19-JUN-19:03 | 31.42 |
July | 36133819.60 | 1610.10 | 16-JUL-16:03 | 29.90 |
August | 51393145.35 | 2501.84 | 04-AUG-19:02 | 33.12 |
September | 18151615.15 | 1040.86 | 03-SEP-07:05 | 19.27 |
October | 24992547.13 | 955.41 | 06-OCT-06:05 | 19.50 |
November | 0.348555E+09 | 31919.70 | 23-NOV-08:61 | -2.6 |
December | 0.977452E+09 | 32236.09 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.570918E+10 | |||
Minimum of Months | 18151615.15 | 803.44 | -11.6 | |
Maximum of Months | 0.189159E+10 | 32400.27 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218158E+10 | 32397.66 | 02-JAN-07:01 | -11.6 |
February | 0.186233E+10 | 32382.10 | 12-FEB-08:61 | -10.5 |
March | 0.676979E+09 | 31906.40 | 20-MAR-06:01 | -0.6 |
April | 0.190981E+09 | 31893.99 | 02-APR-07:01 | 4.18 |
May | 28110487.81 | 741.45 | 30-MAY-06:07 | 20.47 |
June | 26768608.24 | 2037.08 | 19-JUN-19:03 | 31.42 |
July | 37684203.93 | 1616.34 | 16-JUL-16:03 | 29.90 |
August | 52225788.40 | 2506.84 | 04-AUG-19:02 | 33.12 |
September | 18146601.61 | 1003.78 | 01-SEP-19:03 | 27.12 |
October | 26134301.91 | 898.69 | 06-OCT-06:05 | 19.50 |
November | 0.441256E+09 | 31918.50 | 23-NOV-08:61 | -2.6 |
December | 0.117823E+10 | 32233.86 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.672044E+10 | |||
Minimum of Months | 18146601.61 | 741.45 | -11.6 | |
Maximum of Months | 0.218158E+10 | 32397.66 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453293E+10 | 57890.78 | 02-JAN-08:12 | -10.9 |
February | 0.384176E+10 | 57654.09 | 13-FEB-08:61 | -8.7 |
March | 0.145807E+10 | 57647.30 | 23-MAR-07:01 | -2.9 |
April | 0.428770E+09 | 57630.74 | 03-APR-07:01 | 3.68 |
May | 61884255.75 | 14515.87 | 01-MAY-07:01 | 10.37 |
June | 30224725.66 | 1714.88 | 23-JUN-07:05 | 23.45 |
July | 46386397.52 | 3253.40 | 16-JUL-16:03 | 29.90 |
August | 43001427.84 | 3283.93 | 13-AUG-16:02 | 29.90 |
September | 26817876.36 | 1704.20 | 03-SEP-08:05 | 21.38 |
October | 51869931.26 | 1944.83 | 31-OCT-08:10 | 7.38 |
November | 0.939172E+09 | 57644.55 | 24-NOV-08:61 | -3.5 |
December | 0.245324E+10 | 57643.91 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.139141E+11 | |||
Minimum of Months | 26817876.36 | 1704.20 | -10.9 | |
Maximum of Months | 0.453293E+10 | 57890.78 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260541E+10 | 30576.73 | 02-JAN-08:12 | -10.9 |
February | 0.223658E+10 | 30413.45 | 13-FEB-08:61 | -8.7 |
March | 0.911137E+09 | 30409.00 | 23-MAR-07:01 | -2.9 |
April | 0.261149E+09 | 30399.24 | 03-APR-07:01 | 3.68 |
May | 35600293.90 | 10060.42 | 01-MAY-07:01 | 10.37 |
June | 15427370.72 | 877.09 | 23-JUN-07:05 | 23.45 |
July | 24748875.48 | 1636.84 | 16-JUL-16:03 | 29.90 |
August | 22542339.36 | 1653.15 | 13-AUG-16:02 | 29.90 |
September | 14534626.59 | 869.37 | 03-SEP-08:05 | 21.38 |
October | 29652591.94 | 1927.01 | 29-OCT-08:62 | 6.88 |
November | 0.582101E+09 | 30407.07 | 24-NOV-08:61 | -3.5 |
December | 0.146943E+10 | 30407.33 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.820831E+10 | |||
Minimum of Months | 14534626.59 | 869.37 | -10.9 | |
Maximum of Months | 0.260541E+10 | 30576.73 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267987E+10 | 30477.73 | 02-JAN-08:12 | -10.9 |
February | 0.231703E+10 | 30302.52 | 13-FEB-08:61 | -8.7 |
March | 0.970276E+09 | 30297.68 | 23-MAR-07:01 | -2.9 |
April | 0.288091E+09 | 30288.43 | 03-APR-07:01 | 3.68 |
May | 38797599.59 | 13915.84 | 01-MAY-07:01 | 10.37 |
June | 15107245.78 | 857.72 | 23-JUN-07:05 | 23.45 |
July | 25054197.83 | 1638.53 | 16-JUL-16:03 | 29.90 |
August | 22574751.54 | 1654.34 | 13-AUG-16:02 | 29.90 |
September | 15277836.96 | 851.66 | 03-SEP-08:05 | 21.38 |
October | 31012576.88 | 3973.81 | 29-OCT-08:62 | 6.88 |
November | 0.618182E+09 | 30296.55 | 24-NOV-08:61 | -3.5 |
December | 0.153572E+10 | 30296.39 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.855699E+10 | |||
Minimum of Months | 15107245.78 | 851.66 | -10.9 | |
Maximum of Months | 0.267987E+10 | 30477.73 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306132E+10 | 30449.11 | 02-JAN-08:12 | -10.9 |
February | 0.269767E+10 | 30228.09 | 13-FEB-08:61 | -8.7 |
March | 0.122863E+10 | 30224.58 | 23-MAR-07:01 | -2.9 |
April | 0.389355E+09 | 30215.26 | 03-APR-07:01 | 3.68 |
May | 51312802.78 | 24678.88 | 01-MAY-07:01 | 10.37 |
June | 14069660.72 | 792.69 | 20-JUN-07:04 | 23.17 |
July | 25710503.72 | 1641.52 | 16-JUL-16:03 | 29.90 |
August | 22964827.98 | 1655.24 | 13-AUG-16:02 | 29.90 |
September | 18176482.40 | 823.10 | 04-SEP-08:04 | 22.98 |
October | 35745897.97 | 9920.64 | 29-OCT-08:62 | 6.88 |
November | 0.766292E+09 | 30222.96 | 24-NOV-08:61 | -3.5 |
December | 0.183298E+10 | 30222.15 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.101442E+11 | |||
Minimum of Months | 14069660.72 | 792.69 | -10.9 | |
Maximum of Months | 0.306132E+10 | 30449.11 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491566E+10 | 32382.16 | 02-JAN-08:12 | -10.9 |
February | 0.453227E+10 | 32173.97 | 06-FEB-08:13 | -12.6 |
March | 0.237893E+10 | 32065.15 | 14-MAR-07:01 | -1.4 |
April | 0.924201E+09 | 32051.26 | 03-APR-07:01 | 3.68 |
May | 0.122837E+09 | 31548.53 | 01-MAY-07:01 | 10.37 |
June | 20475243.53 | 856.33 | 26-JUN-07:04 | 23.40 |
July | 26491163.78 | 1635.39 | 16-JUL-16:03 | 29.90 |
August | 22187542.76 | 1642.94 | 13-AUG-16:02 | 29.90 |
September | 25455486.50 | 908.43 | 02-SEP-07:03 | 21.70 |
October | 69226467.48 | 27508.79 | 29-OCT-08:62 | 6.88 |
November | 0.137350E+10 | 32064.98 | 24-NOV-08:61 | -3.5 |
December | 0.316573E+10 | 32062.68 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.175770E+11 | |||
Minimum of Months | 20475243.53 | 856.33 | -12.6 | |
Maximum of Months | 0.491566E+10 | 32382.16 | 29.90 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.813398E+10 | 5087.95 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.735242E+10 | 5087.95 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.814191E+10 | 5087.95 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.788011E+10 | 5087.95 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.813398E+10 | 5087.95 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.788127E+10 | 5087.95 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.814063E+10 | 5087.95 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.813456E+10 | 5087.95 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.788734E+10 | 5087.95 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.813398E+10 | 5087.95 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.785744E+10 | 5087.95 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.814844E+10 | 5087.95 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.958261E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.735242E+10 | 5087.95 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.814844E+10 | 5087.95 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488783E+10 | 3061.69 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.441818E+10 | 3061.69 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.489263E+10 | 3061.69 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.473526E+10 | 3061.69 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.488783E+10 | 3061.69 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.473600E+10 | 3061.69 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.489181E+10 | 3061.69 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.488820E+10 | 3061.69 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.473961E+10 | 3061.69 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.488783E+10 | 3061.69 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.472164E+10 | 3061.69 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.489653E+10 | 3061.69 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.575834E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.441818E+10 | 3061.69 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.489653E+10 | 3061.69 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345591E+10 | 2789.01 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.313041E+10 | 2789.01 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.353515E+10 | 2789.01 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.335401E+10 | 2789.01 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.349553E+10 | 2789.01 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.341344E+10 | 2789.01 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.343610E+10 | 2789.01 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.353515E+10 | 2789.01 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.335401E+10 | 2789.01 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.345591E+10 | 2789.01 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.335401E+10 | 2789.01 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.343610E+10 | 2789.01 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.409557E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.313041E+10 | 2789.01 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.353515E+10 | 2789.01 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365008E+10 | 3191.64 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.330698E+10 | 3191.64 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.373984E+10 | 3191.64 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.354319E+10 | 3191.64 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.369496E+10 | 3191.64 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.361051E+10 | 3191.64 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.362764E+10 | 3191.64 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.373984E+10 | 3191.64 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.354319E+10 | 3191.64 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.365008E+10 | 3191.64 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.354319E+10 | 3191.64 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.362764E+10 | 3191.64 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.432771E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.330698E+10 | 3191.64 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.373984E+10 | 3191.64 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187212E+10 | 1638.25 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.169615E+10 | 1638.25 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.191822E+10 | 1638.25 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.181731E+10 | 1638.25 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.189517E+10 | 1638.25 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.185188E+10 | 1638.25 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.186060E+10 | 1638.25 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.191822E+10 | 1638.25 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.181731E+10 | 1638.25 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.187212E+10 | 1638.25 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.181731E+10 | 1638.25 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.186060E+10 | 1638.25 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.221970E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.169615E+10 | 1638.25 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.191822E+10 | 1638.25 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520702E+10 |
February | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489751E+10 |
March | 0.335708E+10 | 0.814191E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382610E+10 |
April | 0.327081E+10 | 0.788011E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12338773.85 | 0.237020E+10 |
May | 0.336680E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67530381.32 | 0.137041E+10 |
June | 0.325380E+10 | 0.788127E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333628E+09 | 0.377543E+09 |
July | 0.339353E+10 | 0.814063E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795972E+09 | 46263377.70 |
August | 0.334857E+10 | 0.813456E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875275E+09 | 80509284.04 |
September | 0.327932E+10 | 0.788734E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157198E+09 | 0.629198E+09 |
October | 0.338624E+10 | 0.813398E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2877838.10 | 0.183208E+10 |
November | 0.327446E+10 | 0.785744E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334716E+10 |
December | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454868E+10 |
Annual Sum or Average | 0.397770E+11 | 0.958261E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224482E+10 | 0.285326E+11 |
Minimum of Months | 0.305697E+10 | 0.735242E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46263377.70 |
Maximum of Months | 0.340325E+10 | 0.814844E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875275E+09 | 0.520702E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268266E+10 |
February | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253828E+10 |
March | 0.167849E+10 | 0.489263E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199802E+10 |
April | 0.163536E+10 | 0.473526E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6770418.40 | 0.124721E+10 |
May | 0.168335E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37146083.84 | 0.729364E+09 |
June | 0.162685E+10 | 0.473600E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182414E+09 | 0.179027E+09 |
July | 0.169671E+10 | 0.489181E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435925E+09 | 16867302.90 |
August | 0.167424E+10 | 0.488820E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478818E+09 | 30240246.62 |
September | 0.163961E+10 | 0.473961E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86311192.15 | 0.315058E+09 |
October | 0.169307E+10 | 0.488783E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1580477.08 | 0.960474E+09 |
November | 0.163718E+10 | 0.472164E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175036E+10 |
December | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235443E+10 |
Annual Sum or Average | 0.198880E+11 | 0.575834E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122896E+10 | 0.148020E+11 |
Minimum of Months | 0.152844E+10 | 0.441818E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16867302.90 |
Maximum of Months | 0.170157E+10 | 0.489653E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478818E+09 | 0.268266E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272765E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257517E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201937E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6770434.28 | 0.125254E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36971964.51 | 0.736384E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180329E+09 | 0.194400E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427908E+09 | 27195101.36 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473889E+09 | 39044467.30 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85262840.42 | 0.330592E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580439.50 | 0.973979E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176801E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239539E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121271E+10 | 0.150397E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27195101.36 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473889E+09 | 0.272765E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272404E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257263E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201345E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6770436.70 | 0.124547E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36972103.76 | 0.729380E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180325E+09 | 0.194246E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427871E+09 | 27324895.00 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473840E+09 | 39237193.56 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85262880.95 | 0.330417E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580623.99 | 0.968544E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175715E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239216E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121262E+10 | 0.149941E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27324895.00 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473840E+09 | 0.272404E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272107E+10 |
February | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257051E+10 |
March | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200681E+10 |
April | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6770428.75 | 0.123597E+10 |
May | 0.102058E+10 | 0.349553E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36972424.19 | 0.716842E+09 |
June | 0.998711E+09 | 0.341344E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180368E+09 | 0.193001E+09 |
July | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428050E+09 | 26284981.94 |
August | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474000E+09 | 38322616.97 |
September | 0.984131E+09 | 0.335401E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85268183.96 | 0.329173E+09 |
October | 0.100722E+10 | 0.345591E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580766.28 | 0.959513E+09 |
November | 0.973196E+09 | 0.335401E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174345E+10 |
December | 0.100600E+10 | 0.343610E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238935E+10 |
Annual Sum or Average | 0.119700E+11 | 0.409557E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121301E+10 | 0.149303E+11 |
Minimum of Months | 0.914877E+09 | 0.313041E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26284981.94 |
Maximum of Months | 0.103395E+10 | 0.353515E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474000E+09 | 0.272107E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494907E+10 |
February | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467596E+10 |
March | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364225E+10 |
April | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12163272.54 | 0.222604E+10 |
May | 0.349753E+10 | 0.369496E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66414001.69 | 0.126971E+10 |
June | 0.343071E+10 | 0.361051E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324692E+09 | 0.355498E+09 |
July | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769967E+09 | 48819065.08 |
August | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853168E+09 | 72700473.77 |
September | 0.338259E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153294E+09 | 0.601827E+09 |
October | 0.344359E+10 | 0.365008E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2840267.16 | 0.172401E+10 |
November | 0.331698E+10 | 0.354319E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314617E+10 |
December | 0.344942E+10 | 0.362764E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434647E+10 |
Annual Sum or Average | 0.410346E+11 | 0.432771E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218254E+10 | 0.270585E+11 |
Minimum of Months | 0.313522E+10 | 0.330698E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48819065.08 |
Maximum of Months | 0.355148E+10 | 0.373984E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853168E+09 | 0.494907E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272589E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257755E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200519E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6770337.77 | 0.122134E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36977362.84 | 0.692233E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180662E+09 | 0.192258E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428654E+09 | 24774871.22 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474832E+09 | 37477519.70 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85336616.22 | 0.329232E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1581226.59 | 0.944662E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172718E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239389E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121481E+10 | 0.148717E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24774871.22 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474832E+09 | 0.272589E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272508E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257670E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200332E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6770393.68 | 0.121687E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36977787.04 | 0.685190E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180679E+09 | 0.191842E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428728E+09 | 24482398.12 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474887E+09 | 37230771.56 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85339269.59 | 0.328766E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1581513.31 | 0.940342E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172313E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239305E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121496E+10 | 0.148460E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24482398.12 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474887E+09 | 0.272508E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272079E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257303E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199706E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6771043.24 | 0.120561E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36979026.77 | 0.668676E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180722E+09 | 0.190386E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428908E+09 | 23587794.90 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475006E+09 | 36582369.75 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85343756.11 | 0.327230E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582000.01 | 0.929276E+09 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171411E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238921E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121531E+10 | 0.147756E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23587794.90 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475006E+09 | 0.272079E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312604E+10 |
February | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292860E+10 |
March | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227797E+10 |
April | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6947075.24 | 0.137550E+10 |
May | 0.174872E+10 | 0.189517E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37792917.13 | 0.746158E+09 |
June | 0.171530E+10 | 0.185188E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186829E+09 | 0.247458E+09 |
July | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441331E+09 | 41487114.22 |
August | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490317E+09 | 64256502.68 |
September | 0.169125E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87457217.16 | 0.393083E+09 |
October | 0.172174E+10 | 0.187212E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1620416.60 | 0.107716E+10 |
November | 0.165844E+10 | 0.181731E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198847E+10 |
December | 0.172466E+10 | 0.186060E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273940E+10 |
Annual Sum or Average | 0.205167E+11 | 0.221970E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125229E+10 | 0.170056E+11 |
Minimum of Months | 0.156756E+10 | 0.169615E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41487114.22 |
Maximum of Months | 0.177569E+10 | 0.191822E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490317E+09 | 0.312604E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5087.95 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9557.02 | 14-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 5087.95 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 10141.06 | 06-FEB-12:10 |
March | 4050.04 | 03-MAR-13:09 | 5087.95 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7203.28 | 17-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 5087.95 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.50 | 07-APR-13:00 | 5259.18 | 01-APR-12:00 |
May | 4050.04 | 05-MAY-12:09 | 5087.95 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1781.47 | 30-MAY-13:00 | 3208.86 | 14-MAY-16:40 |
June | 4050.04 | 02-JUN-12:09 | 5087.95 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3633.07 | 19-JUN-12:00 | 1707.25 | 03-JUN-17:00 |
July | 4050.04 | 01-JUL-12:09 | 5087.95 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2848.65 | 07-JUL-12:00 | 504.52 | 23-JUL-17:00 |
August | 4050.04 | 04-AUG-12:09 | 5087.95 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2897.02 | 24-AUG-15:00 | 834.93 | 06-AUG-12:00 |
September | 4050.04 | 01-SEP-12:09 | 5087.95 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2060.06 | 01-SEP-14:00 | 2635.73 | 23-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 5087.95 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 325.39 | 04-OCT-13:00 | 4055.27 | 08-OCT-11:10 |
November | 4050.04 | 03-NOV-12:09 | 5087.95 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6911.17 | 22-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5087.95 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8706.82 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.52 | |||||
Maximum of Months | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3633.07 | 10141.06 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3061.69 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5210.60 | 14-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 3061.69 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5553.15 | 06-FEB-12:10 |
March | 2024.96 | 03-MAR-13:09 | 3061.69 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3963.21 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3061.69 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.93 | 07-APR-13:00 | 2912.56 | 01-APR-12:00 |
May | 2024.96 | 05-MAY-12:09 | 3061.69 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 981.97 | 30-MAY-13:00 | 1804.40 | 14-MAY-16:50 |
June | 2024.96 | 02-JUN-12:09 | 3061.69 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 19-JUN-12:00 | 935.89 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 3061.69 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1575.83 | 07-JUL-12:00 | 278.47 | 23-JUL-17:00 |
August | 2024.96 | 04-AUG-12:09 | 3061.69 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.35 | 24-AUG-15:00 | 460.22 | 06-AUG-12:00 |
September | 2024.96 | 01-SEP-12:09 | 3061.69 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1137.04 | 01-SEP-14:00 | 1479.27 | 23-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 3061.69 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.37 | 04-OCT-13:00 | 2351.12 | 08-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 3061.69 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3793.15 | 23-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3061.69 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4767.77 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.47 | |||||
Maximum of Months | 2024.96 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 5553.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5210.60 | 14-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5553.15 | 06-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3963.21 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.93 | 07-APR-13:00 | 2912.56 | 01-APR-12:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 981.97 | 30-MAY-13:00 | 1741.66 | 14-MAY-16:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 19-JUN-12:00 | 935.86 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1575.83 | 07-JUL-12:00 | 531.92 | 23-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.41 | 24-AUG-15:00 | 710.71 | 06-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1137.04 | 01-SEP-14:00 | 1484.62 | 23-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.36 | 04-OCT-13:00 | 2337.58 | 28-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3793.15 | 23-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4767.77 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.92 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 5553.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5210.60 | 14-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5553.15 | 06-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3963.21 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.93 | 07-APR-13:00 | 2912.56 | 01-APR-12:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 981.97 | 30-MAY-13:00 | 1728.30 | 14-MAY-16:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 19-JUN-12:00 | 935.86 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1575.83 | 07-JUL-12:00 | 531.77 | 23-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.40 | 24-AUG-15:00 | 711.17 | 06-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1137.04 | 01-SEP-14:00 | 1484.62 | 23-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.36 | 04-OCT-13:00 | 2320.32 | 28-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3793.15 | 23-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4767.77 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.77 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 5553.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2789.01 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5210.60 | 14-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2789.01 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5553.15 | 06-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2789.01 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3963.21 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2789.01 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.93 | 07-APR-13:00 | 2912.56 | 01-APR-12:00 |
May | 2024.96 | 06-MAY-12:09 | 2789.01 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 981.97 | 30-MAY-13:00 | 1702.46 | 14-MAY-16:00 |
June | 2024.96 | 03-JUN-12:09 | 2789.01 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 19-JUN-12:00 | 935.85 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2789.01 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1575.83 | 07-JUL-12:00 | 522.19 | 23-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2789.01 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.43 | 24-AUG-15:00 | 701.42 | 06-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2789.01 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1137.04 | 01-SEP-14:00 | 1481.06 | 23-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2789.01 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.35 | 04-OCT-13:00 | 2287.15 | 28-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2789.01 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3793.15 | 23-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2789.01 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4767.77 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.19 | |||||
Maximum of Months | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 5553.15 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3191.64 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9368.53 | 14-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 3191.64 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9979.07 | 06-FEB-12:10 |
March | 5400.05 | 04-MAR-15:09 | 3191.64 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7117.77 | 17-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 3191.64 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 813.44 | 07-APR-13:00 | 5226.66 | 01-APR-12:00 |
May | 5400.05 | 06-MAY-14:09 | 3191.64 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1763.16 | 30-MAY-13:00 | 2933.61 | 14-MAY-16:00 |
June | 5400.05 | 03-JUN-14:09 | 3191.64 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3595.76 | 19-JUN-12:00 | 1681.39 | 03-JUN-17:00 |
July | 5400.05 | 01-JUL-14:09 | 3191.64 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2828.25 | 07-JUL-12:00 | 878.90 | 23-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 3191.64 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2847.44 | 24-AUG-15:00 | 1201.78 | 06-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3191.64 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2041.28 | 01-SEP-14:00 | 2634.28 | 23-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 3191.64 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 322.04 | 04-OCT-13:00 | 4014.95 | 28-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 3191.64 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6812.65 | 23-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3191.64 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8567.73 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.90 | |||||
Maximum of Months | 5400.05 | 3191.64 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3595.76 | 9979.07 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5210.60 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5553.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3963.21 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.91 | 07-APR-13:00 | 2912.56 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 981.96 | 30-MAY-13:00 | 1623.82 | 14-MAY-16:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 19-JUN-12:00 | 935.79 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1575.83 | 07-JUL-12:00 | 483.09 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.29 | 24-AUG-15:00 | 659.25 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1137.04 | 01-SEP-14:00 | 1464.33 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.35 | 04-OCT-13:00 | 2228.25 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3793.15 | 23-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4767.77 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.09 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 5553.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5210.60 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5553.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3963.21 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.91 | 07-APR-13:00 | 2912.56 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 981.96 | 30-MAY-13:00 | 1608.50 | 13-MAY-16:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 19-JUN-12:00 | 935.79 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1575.83 | 07-JUL-12:00 | 479.75 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.29 | 24-AUG-15:00 | 655.84 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1137.04 | 01-SEP-14:00 | 1461.99 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.35 | 04-OCT-13:00 | 2216.27 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3793.15 | 23-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4767.77 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.75 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 5553.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5210.60 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5553.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3963.21 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.91 | 07-APR-13:00 | 2912.56 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 981.96 | 30-MAY-13:00 | 1571.87 | 13-MAY-16:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 19-JUN-12:00 | 935.79 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1575.83 | 07-JUL-12:00 | 471.49 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.30 | 24-AUG-15:00 | 649.92 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1137.04 | 01-SEP-14:00 | 1455.05 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.35 | 04-OCT-13:00 | 2185.01 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3793.15 | 23-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4767.77 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.49 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.59 | 5553.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1638.25 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5399.09 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1638.25 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5715.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1638.25 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4048.72 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1638.25 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 462.95 | 07-APR-13:00 | 2945.08 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1638.25 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.25 | 30-MAY-13:00 | 1539.50 | 11-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1638.25 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2039.90 | 19-JUN-12:00 | 961.46 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1638.25 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1596.23 | 07-JUL-12:00 | 458.75 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1638.25 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1633.83 | 24-AUG-15:00 | 661.82 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1638.25 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.81 | 01-SEP-14:00 | 1420.69 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1638.25 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.68 | 04-OCT-13:00 | 2194.23 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1638.25 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3897.73 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1638.25 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4906.86 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.75 | |||||
Maximum of Months | 2699.95 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2039.90 | 5715.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12130.90 | 11-JAN-19:02 | 16875.16 | 25439.75 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.34 |
February | 11597.87 | 08-FEB-19:42 | 16875.16 | 25439.75 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.47 |
March | 9971.73 | 17-MAR-23:03 | 1350.01 | 10711.44 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.78 |
April | 7990.26 | 08-APR-13:00 | 4050.04 | 5087.95 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.97 |
May | 13538.43 | 30-MAY-07:03 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.37 |
June | 34146.63 | 22-JUN-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 |
July | 36344.89 | 11-JUL-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.67 |
August | 35598.57 | 19-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.21 |
September | 37601.25 | 02-SEP-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.10 |
October | 24125.50 | 06-OCT-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.99 |
November | 10800.16 | 24-NOV-00:02 | 1687.52 | 1338.85 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.46 |
December | 10715.22 | 22-DEC-00:03 | 1350.01 | 1071.08 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7990.26 | 0.00 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 | |
Maximum of Months | 37601.25 | 16875.16 | 25439.75 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5342.85 | 08-JAN-11:23 | 2699.95 | 12246.74 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.09 |
February | 5435.06 | 08-FEB-10:23 | 1349.97 | 12246.74 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.34 |
March | 3809.59 | 29-MAR-19:00 | 1687.47 | 3061.69 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.69 |
April | 14696.86 | 16-APR-17:01 | 16199.69 | 24493.48 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.10 |
May | 16971.69 | 27-MAY-22:43 | 4724.91 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 |
June | 19157.28 | 22-JUN-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 |
July | 19836.80 | 11-JUL-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.76 |
August | 19589.99 | 19-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.92 |
September | 20327.27 | 02-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 |
October | 17600.38 | 25-OCT-20:07 | 7087.36 | 21431.80 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
November | 4659.65 | 22-NOV-09:23 | 674.99 | 6445.65 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.73 |
December | 3866.30 | 21-DEC-12:33 | 2024.96 | 9185.06 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3227.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3809.59 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 | |
Maximum of Months | 20327.27 | 16199.69 | 24493.48 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3227.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3509.11 | 25-JAN-09:13 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.17 |
February | 5855.78 | 26-FEB-11:32 | 3374.94 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.62 |
March | 4162.67 | 30-MAR-07:01 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.70 |
April | 4666.95 | 08-APR-12:30 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.59 |
May | 9336.15 | 30-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 |
June | 19616.42 | 23-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 |
July | 20267.91 | 11-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 |
August | 23049.48 | 25-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 |
September | 20421.31 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 |
October | 15830.47 | 06-OCT-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 |
November | 3457.14 | 04-NOV-13:00 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.57 |
December | 4060.36 | 11-DEC-10:33 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3457.14 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | |
Maximum of Months | 23049.48 | 3374.94 | 13945.03 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5521.00 | 05-JAN-10:32 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.78 |
February | 5436.89 | 13-FEB-19:33 | 2699.95 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.37 |
March | 4008.22 | 29-MAR-07:01 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.27 |
April | 4529.89 | 08-APR-12:30 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.59 |
May | 9100.43 | 30-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 |
June | 19560.82 | 23-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 |
July | 20246.21 | 11-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 |
August | 23028.94 | 25-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 |
September | 20392.22 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 |
October | 15678.89 | 06-OCT-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 |
November | 4795.74 | 24-NOV-09:23 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.47 |
December | 4773.66 | 31-DEC-10:43 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4008.22 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | |
Maximum of Months | 23028.94 | 2699.95 | 11156.02 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5177.26 | 04-JAN-11:43 | 1349.97 | 11156.02 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.10 |
February | 3377.92 | 01-FEB-09:33 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.68 |
March | 3496.78 | 29-MAR-07:01 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.86 |
April | 4238.98 | 08-APR-12:50 | 2024.96 | 2789.01 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.74 |
May | 7696.65 | 30-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
June | 19421.12 | 23-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 |
July | 20074.78 | 11-JUL-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
August | 22844.10 | 25-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 |
September | 20205.46 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 |
October | 14128.06 | 06-OCT-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 |
November | 4074.05 | 25-NOV-10:23 | 1012.48 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.89 |
December | 3775.73 | 21-DEC-13:13 | 4049.92 | 8367.02 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3157.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3377.92 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 | |
Maximum of Months | 22844.10 | 4049.92 | 11156.02 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3157.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10466.28 | 10-JAN-11:32 | 11610.11 | 12766.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.89 |
February | 7830.05 | 04-FEB-11:33 | 11745.11 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.71 |
March | 9786.22 | 17-MAR-10:13 | 11610.11 | 12766.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 992.61 |
April | 6842.81 | 12-APR-08:63 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.48 |
May | 15163.93 | 30-MAY-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.04 |
June | 32351.37 | 22-JUN-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
July | 35051.10 | 11-JUL-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.25 |
August | 33863.00 | 19-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.15 |
September | 35952.78 | 02-SEP-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.10 |
October | 23144.65 | 06-OCT-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.21 |
November | 6796.55 | 30-NOV-10:13 | 2227.52 | 9574.91 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.62 |
December | 8721.12 | 01-DEC-20:53 | 2970.03 | 6719.20 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6796.55 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | |
Maximum of Months | 35952.78 | 11745.11 | 12766.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5193.89 | 31-JAN-18:33 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.75 |
February | 5243.16 | 03-FEB-18:53 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.53 |
March | 4339.77 | 08-MAR-20:23 | 1484.97 | 3448.95 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.88 |
April | 3359.47 | 12-APR-08:63 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.75 |
May | 7064.50 | 30-MAY-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
June | 16739.64 | 22-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
July | 18110.02 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.44 |
August | 17485.17 | 19-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.71 |
September | 18574.50 | 02-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.25 |
October | 10814.45 | 06-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.13 |
November | 4544.44 | 21-NOV-20:42 | 1484.97 | 3448.95 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.07 |
December | 4321.36 | 01-DEC-20:53 | 1484.97 | 3448.95 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3359.47 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | |
Maximum of Months | 18574.50 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4768.55 | 30-JAN-18:42 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.15 |
February | 4235.62 | 24-FEB-20:33 | 1484.97 | 3448.95 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.12 |
March | 4855.78 | 17-MAR-18:33 | 3509.93 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.02 |
April | 3333.03 | 12-APR-08:63 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.48 |
May | 6317.49 | 30-MAY-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 |
June | 16622.60 | 22-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
July | 18001.90 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.73 |
August | 17379.06 | 19-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.99 |
September | 18463.44 | 02-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.51 |
October | 10259.86 | 06-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.01 |
November | 4680.91 | 22-NOV-19:33 | 3509.93 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.28 |
December | 4316.21 | 21-DEC-10:23 | 1484.97 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3333.03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | |
Maximum of Months | 18463.44 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2634.29 | 19-JAN-10:25 | 742.49 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.84 |
February | 3371.94 | 23-FEB-19:13 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.18 |
March | 4604.55 | 22-MAR-19:03 | 1484.97 | 3448.95 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.39 |
April | 3082.79 | 08-APR-13:10 | 2598.70 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.81 |
May | 5817.17 | 30-MAY-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 981.96 | 0.00 |
June | 14851.60 | 20-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.41 |
July | 17845.82 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 |
August | 17238.86 | 19-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.08 |
September | 18315.39 | 02-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.51 |
October | 8525.14 | 06-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.69 |
November | 4589.59 | 22-NOV-18:42 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.06 |
December | 4118.86 | 28-DEC-19:23 | 2632.45 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2634.29 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18315.39 | 4589.91 | 6553.01 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 981.96 | 559.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 618.66 | 19-JAN-12:00 | 1451.22 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.03 |
February | 3248.44 | 11-FEB-11:23 | 5872.39 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.81 |
March | 3734.58 | 23-MAR-10:43 | 4353.67 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.22 |
April | 3216.81 | 08-APR-12:20 | 2497.45 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
May | 6157.62 | 30-MAY-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.25 | 0.00 |
June | 15637.64 | 26-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 |
July | 18517.10 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 |
August | 16241.40 | 22-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 41.43 | 0.00 |
September | 19452.11 | 02-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.42 |
October | 5589.26 | 04-OCT-13:00 | 2396.20 | 1638.25 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 182.68 | 0.00 |
November | 2718.21 | 18-NOV-13:15 | 4994.90 | 3276.51 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.15 |
December | 3144.10 | 14-DEC-11:03 | 4353.67 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 618.66 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19452.11 | 5872.39 | 4914.76 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.25 | 2400.15 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.641229E+11 | 49868.26 | 14-JAN-16:00 | 0.113720E+12 | 221334.85 | 02-JAN-08:09 |
February | 0.575443E+11 | 49845.02 | 06-FEB-17:40 | 0.107113E+12 | 210521.70 | 06-FEB-08:09 |
March | 0.626310E+11 | 48363.81 | 08-MAR-17:00 | 0.604905E+11 | 123408.24 | 17-MAR-11:09 |
April | 0.592549E+11 | 57641.97 | 07-APR-12:00 | 0.203807E+11 | 96775.97 | 03-APR-07:10 |
May | 0.641276E+11 | 69096.34 | 30-MAY-12:00 | 0.488641E+09 | 20201.97 | 01-MAY-07:10 |
June | 0.797621E+11 | 92088.47 | 19-JUN-12:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.954290E+11 | 93722.92 | 08-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.962753E+11 | 93190.70 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.750192E+11 | 78172.41 | 14-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.659181E+11 | 65847.11 | 04-OCT-12:50 | 0.452549E+09 | 18789.98 | 31-OCT-08:20 |
November | 0.605545E+11 | 48469.02 | 24-NOV-17:40 | 0.396212E+11 | 119786.36 | 24-NOV-08:09 |
December | 0.635691E+11 | 49009.91 | 31-DEC-16:00 | 0.851475E+11 | 158853.71 | 31-DEC-17:00 |
Annual Sum or Average | 0.844208E+12 | 0.427415E+12 | ||||
Minimum of Months | 0.575443E+11 | 48363.81 | 0.00 | 0.00 | ||
Maximum of Months | 0.962753E+11 | 93722.92 | 0.113720E+12 | 221334.85 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.345281E+11 | 0.669409E+10 | 0.108325E+11 | 0.00 | 0.963936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242890E+10 | 0.00 |
February | 0.312534E+11 | 0.546825E+10 | 0.980803E+10 | 0.00 | 0.879896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221558E+10 | 0.00 |
March | 0.350527E+11 | 0.526005E+10 | 0.110075E+11 | 0.00 | 0.885785E+10 | 0.00 | 0.00 | 6808058.23 | 0.00 | 0.00 | 0.00 | 0.244608E+10 | 0.00 |
April | 0.334898E+11 | 0.429522E+10 | 0.105079E+11 | 0.00 | 0.786238E+10 | 0.00 | 0.00 | 0.863012E+09 | 0.00 | 0.00 | 0.00 | 0.223653E+10 | 0.00 |
May | 0.347840E+11 | 0.384977E+10 | 0.109147E+11 | 0.00 | 0.790416E+10 | 0.00 | 0.00 | 0.448916E+10 | 0.00 | 0.00 | 0.00 | 0.218573E+10 | 0.00 |
June | 0.338757E+11 | 0.343615E+10 | 0.106386E+11 | 0.00 | 0.772089E+10 | 0.00 | 0.00 | 0.220718E+11 | 0.00 | 0.00 | 0.00 | 0.201900E+10 | 0.00 |
July | 0.344108E+11 | 0.363884E+10 | 0.107945E+11 | 0.00 | 0.804956E+10 | 0.00 | 0.00 | 0.365616E+11 | 0.00 | 0.00 | 0.00 | 0.197372E+10 | 0.00 |
August | 0.350409E+11 | 0.412573E+10 | 0.110006E+11 | 0.00 | 0.829641E+10 | 0.00 | 0.00 | 0.358116E+11 | 0.00 | 0.00 | 0.00 | 0.199994E+10 | 0.00 |
September | 0.335014E+11 | 0.474129E+10 | 0.105148E+11 | 0.00 | 0.760594E+10 | 0.00 | 0.00 | 0.167054E+11 | 0.00 | 0.00 | 0.00 | 0.195038E+10 | 0.00 |
October | 0.345281E+11 | 0.572595E+10 | 0.108325E+11 | 0.00 | 0.783797E+10 | 0.00 | 0.00 | 0.489459E+10 | 0.00 | 0.00 | 0.00 | 0.209910E+10 | 0.00 |
November | 0.334535E+11 | 0.626785E+10 | 0.104978E+11 | 0.00 | 0.815866E+10 | 0.00 | 0.00 | 2073690.29 | 0.00 | 0.00 | 0.00 | 0.217459E+10 | 0.00 |
December | 0.344233E+11 | 0.686921E+10 | 0.108050E+11 | 0.00 | 0.911842E+10 | 0.00 | 0.00 | 59939.20 | 0.00 | 0.00 | 0.00 | 0.235306E+10 | 0.00 |
Annual Sum or Average | 0.408342E+12 | 0.603724E+11 | 0.128154E+12 | 0.00 | 0.998506E+11 | 0.00 | 0.00 | 0.121406E+12 | 0.00 | 0.00 | 0.00 | 0.260826E+11 | 0.00 |
Minimum of Months | 0.312534E+11 | 0.343615E+10 | 0.980803E+10 | 0.00 | 0.760594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195038E+10 | 0.00 |
Maximum of Months | 0.350527E+11 | 0.686921E+10 | 0.110075E+11 | 0.00 | 0.963936E+10 | 0.00 | 0.00 | 0.365616E+11 | 0.00 | 0.00 | 0.00 | 0.244608E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.113720E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.107113E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.604905E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.203807E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.488641E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.452549E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.396212E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.851475E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.427415E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.113720E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26261.30 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9127.36 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26261.30 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 8941.03 | 06-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26261.30 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7443.99 | 17-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26261.30 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6985.93 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26261.30 | 01-MAY-09:09 | 5507.06 | 01-MAY-18:49 | 8059.50 | 01-MAY-09:09 | 0.00 | 5669.78 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26261.30 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:19 | 8059.50 | 01-JUN-09:09 | 0.00 | 7794.45 | 19-JUN-12:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26261.30 | 01-JUL-09:09 | 5507.06 | 01-JUL-19:30 | 8059.50 | 01-JUL-09:09 | 0.00 | 8581.13 | 08-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26261.30 | 01-AUG-09:09 | 5507.06 | 01-AUG-19:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8498.45 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26261.30 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 6487.69 | 07-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26261.30 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 6008.19 | 06-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26261.30 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7383.50 | 24-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26261.30 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8055.55 | 31-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 5669.78 | 0.00 | 0.00 | |||||
Maximum of Months | 26261.30 | 5507.06 | 8059.50 | 0.00 | 9127.36 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2236.94 | 20-JAN-13:39 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2237.28 | 10-FEB-13:30 | 0.00 |
March | 2051.98 | 27-MAR-16:10 | 0.00 | 0.00 | 0.00 | 2236.52 | 10-MAR-13:09 | 0.00 |
April | 16086.52 | 07-APR-12:00 | 0.00 | 0.00 | 0.00 | 2234.13 | 04-APR-12:09 | 0.00 |
May | 27439.85 | 30-MAY-12:00 | 0.00 | 0.00 | 0.00 | 2123.05 | 09-MAY-13:30 | 0.00 |
June | 48277.14 | 19-JUN-12:09 | 0.00 | 0.00 | 0.00 | 2121.11 | 07-JUN-12:20 | 0.00 |
July | 49104.13 | 08-JUL-12:09 | 0.00 | 0.00 | 0.00 | 2012.72 | 12-JUL-12:20 | 0.00 |
August | 48888.89 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | 1907.67 | 17-AUG-12:50 | 0.00 |
September | 36350.68 | 14-SEP-12:00 | 0.00 | 0.00 | 0.00 | 2005.03 | 14-SEP-12:39 | 0.00 |
October | 24598.62 | 04-OCT-12:00 | 0.00 | 0.00 | 0.00 | 2122.29 | 20-OCT-12:20 | 0.00 |
November | 319.55 | 02-NOV-22:10 | 0.00 | 0.00 | 0.00 | 2230.93 | 13-NOV-13:39 | 0.00 |
December | 99.90 | 17-DEC-20:19 | 0.00 | 0.00 | 0.00 | 2235.25 | 22-DEC-13:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1907.67 | 0.00 | ||
Maximum of Months | 49104.13 | 0.00 | 0.00 | 0.00 | 2237.28 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 49868.26 | 14-JAN-16:00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 8154.86 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49845.02 | 06-FEB-17:40 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 8185.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 48363.81 | 08-MAR-17:00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 6840.98 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57641.97 | 07-APR-12:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5319.95 | 0.00 | 0.00 | 16086.52 | 0.00 |
May | 69096.34 | 30-MAY-12:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5319.95 | 0.00 | 0.00 | 27439.85 | 0.00 |
June | 92088.47 | 19-JUN-12:09 | 26261.30 | 8059.50 | 0.00 | 0.00 | 7794.45 | 0.00 | 0.00 | 48277.14 | 0.00 |
July | 93722.92 | 08-JUL-12:20 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8581.13 | 0.00 | 0.00 | 49020.14 | 0.00 |
August | 93190.70 | 16-AUG-12:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 8498.45 | 0.00 | 0.00 | 48888.89 | 0.00 |
September | 78172.41 | 14-SEP-12:00 | 26261.30 | 8059.50 | 0.00 | 0.00 | 6017.69 | 0.00 | 0.00 | 36350.68 | 0.00 |
October | 65847.11 | 04-OCT-12:50 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5319.95 | 0.00 | 0.00 | 24404.09 | 0.00 |
November | 48469.02 | 24-NOV-17:40 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 6978.53 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49009.91 | 31-DEC-16:00 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 7810.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 48363.81 | 26261.30 | 8059.50 | 0.00 | 0.00 | 5319.95 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93722.92 | 26261.30 | 8059.50 | 5507.06 | 0.00 | 8581.13 | 0.00 | 0.00 | 49020.14 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 221334.85 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 210521.70 | 06-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 123408.24 | 17-MAR-11:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 96775.97 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 20201.97 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 18789.98 | 31-OCT-08:20 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 119786.36 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 158853.71 | 31-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 221334.85 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.47 | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 1.33 | 20.45 | 0.33 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
March | 1.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
April | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
December | 0.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 4.33 | 20.47 | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.54 | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
February | 0.17 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
February | 0.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
February | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
February | 0.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
February | 1.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 |
February | 5.50 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
March | 1.33 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
April | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
December | 0.83 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 12.17 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.07 | 274.33 | 21.06 | 274.33 | 21.05 |
February | 448.00 | 21.06 | 299.00 | 21.05 | 299.00 | 21.05 |
March | 492.67 | 21.18 | 87.50 | 21.14 | 87.50 | 21.11 |
April | 404.00 | 21.72 | 42.50 | 21.79 | 19.67 | 21.75 |
May | 216.83 | 22.91 | 116.00 | 23.24 | 26.33 | 23.29 |
June | 81.33 | 23.88 | 422.00 | 23.89 | 75.17 | 23.89 |
July | 97.67 | 23.89 | 495.00 | 23.89 | 97.67 | 23.89 |
August | 42.83 | 23.89 | 471.33 | 23.89 | 42.83 | 23.89 |
September | 38.33 | 23.74 | 369.17 | 23.88 | 21.17 | 23.88 |
October | 218.33 | 22.77 | 225.50 | 23.34 | 25.83 | 23.37 |
November | 466.83 | 21.49 | 53.00 | 21.43 | 53.00 | 21.39 |
December | 496.00 | 21.07 | 182.33 | 21.05 | 182.33 | 21.04 |
Annual Sum or Average | 3498.83 | 21.64 | 3037.67 | 22.28 | 1204.83 | 22.19 |
Minimum of Months | 38.33 | 21.06 | 42.50 | 21.05 | 19.67 | 21.04 |
Maximum of Months | 496.00 | 23.89 | 495.00 | 23.89 | 299.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.43 | 126.67 | 21.37 | 126.67 | 21.33 |
February | 448.00 | 21.44 | 112.33 | 21.38 | 112.33 | 21.33 |
March | 489.50 | 21.77 | 11.50 | 21.76 | 11.50 | 21.75 |
April | 353.17 | 22.22 | 34.50 | 22.37 | 0.00 | 22.37 |
May | 139.50 | 23.42 | 145.50 | 23.65 | 24.67 | 23.67 |
June | 26.83 | 23.85 | 402.33 | 23.88 | 23.33 | 23.89 |
July | 50.17 | 23.89 | 490.67 | 23.89 | 50.17 | 23.89 |
August | 27.00 | 23.85 | 453.00 | 23.89 | 26.00 | 23.89 |
September | 22.83 | 23.72 | 349.83 | 23.88 | 12.50 | 23.88 |
October | 166.67 | 23.33 | 233.67 | 23.65 | 15.67 | 23.66 |
November | 437.67 | 22.09 | 8.67 | 22.10 | 5.83 | 22.09 |
December | 496.00 | 21.56 | 16.50 | 21.55 | 16.50 | 21.53 |
Annual Sum or Average | 3153.33 | 21.97 | 2385.17 | 22.66 | 425.17 | 22.62 |
Minimum of Months | 22.83 | 21.43 | 8.67 | 21.37 | 0.00 | 21.33 |
Maximum of Months | 496.00 | 23.89 | 490.67 | 23.89 | 126.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 147.83 | 21.11 | 147.83 | 21.11 |
February | 336.00 | 21.11 | 145.33 | 21.11 | 145.33 | 21.11 |
March | 373.67 | 21.26 | 28.17 | 21.25 | 28.17 | 21.24 |
April | 289.17 | 21.77 | 25.67 | 21.91 | 3.83 | 21.90 |
May | 133.67 | 23.13 | 104.83 | 23.50 | 23.67 | 23.53 |
June | 47.83 | 24.15 | 327.83 | 24.03 | 45.33 | 24.05 |
July | 84.17 | 24.28 | 369.00 | 24.09 | 84.17 | 24.12 |
August | 42.33 | 24.52 | 364.33 | 24.11 | 42.33 | 24.14 |
September | 29.00 | 23.93 | 288.17 | 24.00 | 19.33 | 24.01 |
October | 139.33 | 22.91 | 181.67 | 23.50 | 16.00 | 23.52 |
November | 342.17 | 21.61 | 17.00 | 21.60 | 14.67 | 21.58 |
December | 369.00 | 21.11 | 50.67 | 21.11 | 50.67 | 21.11 |
Annual Sum or Average | 2557.33 | 21.73 | 2050.50 | 22.50 | 621.33 | 22.47 |
Minimum of Months | 29.00 | 21.11 | 17.00 | 21.11 | 3.83 | 21.11 |
Maximum of Months | 373.67 | 24.52 | 369.00 | 24.11 | 147.83 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 158.83 | 21.11 | 158.83 | 21.11 |
February | 336.00 | 21.11 | 161.83 | 21.11 | 161.83 | 21.11 |
March | 375.67 | 21.25 | 35.17 | 21.24 | 35.17 | 21.23 |
April | 293.67 | 21.75 | 24.83 | 21.88 | 4.67 | 21.87 |
May | 144.67 | 23.04 | 97.67 | 23.41 | 23.67 | 23.46 |
June | 48.17 | 24.15 | 327.50 | 24.03 | 45.50 | 24.04 |
July | 84.17 | 24.28 | 369.00 | 24.09 | 84.17 | 24.12 |
August | 42.17 | 24.52 | 364.50 | 24.11 | 42.17 | 24.14 |
September | 29.67 | 23.92 | 287.50 | 24.00 | 19.50 | 24.01 |
October | 143.50 | 22.84 | 180.00 | 23.45 | 16.17 | 23.48 |
November | 347.33 | 21.57 | 18.33 | 21.55 | 18.17 | 21.53 |
December | 369.00 | 21.11 | 68.33 | 21.11 | 68.33 | 21.11 |
Annual Sum or Average | 2585.00 | 21.72 | 2093.50 | 22.47 | 678.17 | 22.43 |
Minimum of Months | 29.67 | 21.11 | 18.33 | 21.11 | 4.67 | 21.11 |
Maximum of Months | 375.67 | 24.52 | 369.00 | 24.11 | 161.83 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 177.00 | 21.11 | 177.00 | 21.11 |
February | 336.00 | 21.11 | 179.83 | 21.11 | 179.83 | 21.11 |
March | 378.00 | 21.24 | 44.67 | 21.23 | 44.67 | 21.21 |
April | 303.00 | 21.73 | 23.83 | 21.84 | 6.17 | 21.82 |
May | 157.67 | 22.88 | 83.33 | 23.26 | 23.67 | 23.31 |
June | 56.50 | 24.11 | 324.67 | 24.02 | 53.33 | 24.04 |
July | 94.33 | 24.23 | 369.00 | 24.08 | 94.33 | 24.11 |
August | 46.67 | 24.45 | 363.50 | 24.10 | 46.67 | 24.13 |
September | 33.83 | 23.86 | 283.17 | 23.99 | 21.33 | 24.00 |
October | 153.67 | 22.76 | 174.17 | 23.38 | 17.17 | 23.41 |
November | 350.00 | 21.49 | 25.83 | 21.46 | 25.83 | 21.44 |
December | 369.00 | 21.11 | 92.67 | 21.11 | 92.67 | 21.11 |
Annual Sum or Average | 2649.67 | 21.72 | 2141.67 | 22.43 | 782.67 | 22.38 |
Minimum of Months | 33.83 | 21.11 | 23.83 | 21.11 | 6.17 | 21.11 |
Maximum of Months | 378.00 | 24.45 | 369.00 | 24.10 | 179.83 | 24.13 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 226.00 | 21.11 | 226.00 | 21.11 |
February | 308.00 | 21.11 | 222.50 | 21.11 | 222.50 | 21.11 |
March | 348.00 | 21.20 | 69.33 | 21.19 | 69.33 | 21.18 |
April | 293.33 | 21.72 | 18.67 | 21.76 | 10.00 | 21.74 |
May | 186.17 | 22.78 | 64.00 | 23.06 | 25.83 | 23.12 |
June | 90.17 | 23.95 | 291.00 | 23.93 | 87.33 | 23.93 |
July | 122.67 | 24.00 | 338.00 | 23.96 | 122.67 | 23.97 |
August | 58.17 | 24.04 | 327.00 | 23.95 | 58.17 | 23.96 |
September | 46.67 | 23.77 | 249.00 | 23.90 | 32.00 | 23.91 |
October | 154.33 | 22.62 | 146.83 | 23.24 | 19.50 | 23.28 |
November | 324.83 | 21.37 | 44.83 | 21.34 | 44.83 | 21.31 |
December | 338.00 | 21.11 | 180.17 | 21.11 | 180.17 | 21.11 |
Annual Sum or Average | 2610.33 | 21.78 | 2177.33 | 22.31 | 1098.33 | 22.26 |
Minimum of Months | 46.67 | 21.11 | 18.67 | 21.11 | 10.00 | 21.11 |
Maximum of Months | 348.00 | 24.04 | 338.00 | 23.96 | 226.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 225.83 | 21.11 | 225.83 | 21.11 |
February | 308.00 | 21.11 | 225.00 | 21.11 | 225.00 | 21.11 |
March | 348.00 | 21.20 | 74.83 | 21.18 | 74.83 | 21.17 |
April | 301.00 | 21.75 | 18.67 | 21.77 | 12.33 | 21.75 |
May | 203.50 | 22.81 | 61.00 | 23.05 | 25.67 | 23.12 |
June | 95.17 | 23.95 | 282.33 | 23.93 | 90.50 | 23.93 |
July | 124.17 | 24.00 | 336.50 | 23.96 | 124.17 | 23.97 |
August | 60.83 | 24.03 | 318.00 | 23.95 | 60.83 | 23.96 |
September | 49.67 | 23.78 | 234.00 | 23.90 | 32.33 | 23.91 |
October | 160.67 | 22.65 | 138.83 | 23.23 | 19.67 | 23.27 |
November | 325.67 | 21.36 | 48.50 | 21.33 | 48.50 | 21.30 |
December | 338.00 | 21.11 | 182.83 | 21.11 | 182.83 | 21.11 |
Annual Sum or Average | 2654.67 | 21.80 | 2146.33 | 22.30 | 1122.50 | 22.25 |
Minimum of Months | 49.67 | 21.11 | 18.67 | 21.11 | 12.33 | 21.11 |
Maximum of Months | 348.00 | 24.03 | 336.50 | 23.96 | 225.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 232.00 | 21.11 | 232.00 | 21.11 |
February | 308.00 | 21.11 | 234.83 | 21.11 | 234.83 | 21.11 |
March | 348.00 | 21.19 | 83.17 | 21.18 | 83.17 | 21.17 |
April | 303.00 | 21.74 | 21.00 | 21.75 | 15.00 | 21.72 |
May | 214.00 | 22.78 | 58.17 | 23.01 | 25.83 | 23.07 |
June | 98.67 | 23.95 | 280.33 | 23.93 | 93.67 | 23.93 |
July | 128.33 | 23.99 | 336.50 | 23.96 | 128.33 | 23.97 |
August | 62.67 | 24.01 | 316.83 | 23.95 | 62.67 | 23.96 |
September | 52.17 | 23.76 | 231.50 | 23.90 | 32.83 | 23.90 |
October | 165.50 | 22.62 | 135.33 | 23.19 | 20.00 | 23.24 |
November | 326.00 | 21.34 | 53.00 | 21.31 | 53.00 | 21.28 |
December | 338.00 | 21.11 | 191.83 | 21.11 | 191.83 | 21.11 |
Annual Sum or Average | 2684.33 | 21.81 | 2174.50 | 22.29 | 1173.17 | 22.23 |
Minimum of Months | 52.17 | 21.11 | 21.00 | 21.11 | 15.00 | 21.11 |
Maximum of Months | 348.00 | 24.01 | 336.50 | 23.96 | 234.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 250.50 | 21.11 | 250.50 | 21.11 |
February | 308.00 | 21.11 | 255.00 | 21.11 | 255.00 | 21.11 |
March | 348.00 | 21.17 | 106.00 | 21.16 | 106.00 | 21.15 |
April | 309.67 | 21.71 | 27.83 | 21.69 | 23.67 | 21.66 |
May | 233.00 | 22.69 | 53.17 | 22.90 | 25.67 | 22.95 |
June | 113.17 | 23.93 | 276.17 | 23.92 | 107.00 | 23.93 |
July | 136.83 | 23.98 | 336.33 | 23.96 | 136.83 | 23.96 |
August | 66.83 | 24.00 | 316.17 | 23.95 | 66.83 | 23.96 |
September | 57.83 | 23.72 | 226.50 | 23.89 | 34.17 | 23.89 |
October | 177.17 | 22.55 | 132.33 | 23.12 | 21.67 | 23.17 |
November | 326.83 | 21.30 | 64.33 | 21.27 | 64.33 | 21.25 |
December | 338.00 | 21.11 | 219.33 | 21.11 | 219.33 | 21.11 |
Annual Sum or Average | 2755.33 | 21.82 | 2263.67 | 22.25 | 1311.00 | 22.19 |
Minimum of Months | 57.83 | 21.11 | 27.83 | 21.11 | 21.67 | 21.11 |
Maximum of Months | 348.00 | 24.00 | 336.33 | 23.96 | 255.00 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 299.83 | 21.11 | 299.83 | 21.11 |
February | 308.00 | 21.11 | 305.17 | 21.11 | 305.17 | 21.11 |
March | 348.00 | 21.15 | 200.67 | 21.14 | 200.67 | 21.13 |
April | 314.00 | 21.65 | 66.33 | 21.55 | 66.33 | 21.49 |
May | 267.00 | 22.56 | 53.67 | 22.72 | 26.17 | 22.75 |
June | 135.00 | 23.91 | 269.67 | 23.91 | 127.50 | 23.92 |
July | 140.50 | 23.99 | 337.17 | 23.96 | 140.50 | 23.97 |
August | 59.17 | 24.04 | 324.50 | 23.95 | 59.17 | 23.96 |
September | 69.50 | 23.63 | 226.00 | 23.86 | 38.17 | 23.86 |
October | 194.17 | 22.43 | 130.50 | 23.00 | 25.83 | 23.05 |
November | 328.83 | 21.27 | 111.33 | 21.23 | 111.33 | 21.20 |
December | 338.00 | 21.11 | 303.67 | 21.11 | 303.67 | 21.11 |
Annual Sum or Average | 2842.17 | 21.82 | 2628.50 | 22.16 | 1704.33 | 22.08 |
Minimum of Months | 59.17 | 21.11 | 53.67 | 21.11 | 25.83 | 21.11 |
Maximum of Months | 348.00 | 24.04 | 337.17 | 23.96 | 305.17 | 23.97 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.07068 | 23.13338 | -0.5623 | 11.96580 |
February | 448.00000 | 21.06338 | 17.83634 | -0.5925 | 12.62692 |
March | 497.00000 | 21.20207 | 29.51653 | -0.4207 | 9.27992 |
April | 479.00000 | 22.05613 | 36.82114 | -0.1381 | 7.58574 |
May | 496.00000 | 23.44327 | 43.71015 | -0.6544 | 15.42026 |
June | 481.00000 | 23.88668 | 54.48663 | -0.3397 | 7.62034 |
July | 495.00000 | 23.88987 | 59.96944 | -0.2499 | 6.39844 |
August | 497.00000 | 23.88782 | 53.31044 | -0.2786 | 6.82164 |
September | 479.00000 | 23.87332 | 48.54119 | -0.3786 | 8.29181 |
October | 496.00000 | 23.38545 | 41.79270 | 0.30029 | 8.53256 |
November | 480.00000 | 21.55347 | 32.08888 | -0.2906 | 8.02651 |
December | 496.00000 | 21.07002 | 22.90085 | -0.5192 | 10.81408 |
Annual Sum or Average | 5840.00000 | 22.54037 | 38.79833 | -0.3423 | 9.43997 |
Minimum of Months | 448.00000 | 21.06338 | 17.83634 | -0.6544 | 6.39844 |
Maximum of Months | 497.00000 | 23.88987 | 59.96944 | 0.30029 | 15.42026 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.42829 | 25.67565 | -0.4217 | 9.24460 |
February | 448.00000 | 21.43845 | 20.30716 | -0.4447 | 9.57059 |
March | 497.00000 | 21.80655 | 31.01457 | -0.2513 | 7.27034 |
April | 479.00000 | 22.65360 | 37.08129 | 0.01579 | 6.83068 |
May | 496.00000 | 23.73712 | 42.64954 | -0.5440 | 11.74117 |
June | 481.00000 | 23.87549 | 51.43520 | -0.3575 | 7.88507 |
July | 495.00000 | 23.89011 | 56.55038 | -0.2794 | 6.76295 |
August | 497.00000 | 23.87771 | 51.03108 | -0.3090 | 7.21903 |
September | 479.00000 | 23.86718 | 46.67555 | -0.3899 | 8.42299 |
October | 496.00000 | 23.69158 | 40.79746 | 0.36602 | 8.61560 |
November | 480.00000 | 22.24807 | 32.94642 | -0.1151 | 6.88911 |
December | 496.00000 | 21.56138 | 25.22565 | -0.3643 | 8.25932 |
Annual Sum or Average | 5840.00000 | 22.84748 | 38.55781 | -0.2570 | 8.22284 |
Minimum of Months | 448.00000 | 21.42829 | 20.30716 | -0.5440 | 6.76295 |
Maximum of Months | 497.00000 | 23.89011 | 56.55038 | 0.36602 | 11.74117 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10955 | 22.74117 | -0.5114 | 10.72170 |
February | 336.00000 | 21.10980 | 17.16496 | -0.5326 | 11.09458 |
March | 379.00000 | 21.29928 | 28.42606 | -0.3667 | 8.36444 |
April | 360.00000 | 22.18941 | 35.19622 | -0.0892 | 7.26580 |
May | 375.00000 | 23.63267 | 42.49380 | -0.5784 | 13.04070 |
June | 366.00000 | 23.99963 | 53.54408 | -0.3068 | 7.28999 |
July | 369.00000 | 24.04773 | 59.58561 | -0.2105 | 6.26071 |
August | 379.00000 | 24.05172 | 52.57296 | -0.2436 | 6.69754 |
September | 360.00000 | 23.97422 | 47.73197 | -0.3501 | 7.95336 |
October | 371.00000 | 23.54064 | 40.99132 | 0.34209 | 8.74114 |
November | 360.00000 | 21.71663 | 31.09290 | -0.2326 | 7.57422 |
December | 369.00000 | 21.11411 | 22.04240 | -0.4745 | 9.78909 |
Annual Sum or Average | 4395.00000 | 22.66072 | 37.95482 | -0.2951 | 8.72432 |
Minimum of Months | 336.00000 | 21.10955 | 17.16496 | -0.5784 | 6.26071 |
Maximum of Months | 379.00000 | 24.05172 | 59.58561 | 0.34209 | 13.04070 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10957 | 22.74087 | -0.5230 | 10.97883 |
February | 336.00000 | 21.10955 | 17.16535 | -0.5429 | 11.33055 |
March | 379.00000 | 21.27624 | 28.47434 | -0.3808 | 8.54709 |
April | 360.00000 | 22.14241 | 35.31640 | -0.1073 | 7.32452 |
May | 375.00000 | 23.57629 | 42.67030 | -0.6026 | 13.86289 |
June | 366.00000 | 23.99860 | 53.60585 | -0.3078 | 7.30174 |
July | 369.00000 | 24.04740 | 59.58487 | -0.2105 | 6.25900 |
August | 379.00000 | 24.05156 | 52.55912 | -0.2431 | 6.69104 |
September | 360.00000 | 23.97183 | 47.75379 | -0.3518 | 7.98699 |
October | 371.00000 | 23.50133 | 41.11320 | 0.33028 | 8.68429 |
November | 360.00000 | 21.64916 | 31.23654 | -0.2565 | 7.69341 |
December | 369.00000 | 21.11233 | 22.04419 | -0.4849 | 9.99778 |
Annual Sum or Average | 4395.00000 | 22.64074 | 38.01177 | -0.3056 | 8.88029 |
Minimum of Months | 336.00000 | 21.10955 | 17.16535 | -0.6026 | 6.25900 |
Maximum of Months | 379.00000 | 24.05156 | 59.58487 | 0.33028 | 13.86289 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10977 | 22.74037 | -0.5375 | 11.30799 |
February | 336.00000 | 21.10981 | 17.16515 | -0.5568 | 11.65868 |
March | 379.00000 | 21.24598 | 28.53326 | -0.3988 | 8.79853 |
April | 360.00000 | 22.07171 | 35.49754 | -0.1323 | 7.39224 |
May | 375.00000 | 23.47390 | 43.00546 | -0.6454 | 15.32696 |
June | 366.00000 | 23.99323 | 53.87136 | -0.3144 | 7.38410 |
July | 369.00000 | 24.04324 | 59.88105 | -0.2152 | 6.28518 |
August | 379.00000 | 24.04740 | 52.75538 | -0.2484 | 6.73243 |
September | 360.00000 | 23.96266 | 47.94656 | -0.3600 | 8.12164 |
October | 371.00000 | 23.43409 | 41.36488 | 0.31091 | 8.57960 |
November | 360.00000 | 21.55703 | 31.43477 | -0.2873 | 7.85647 |
December | 369.00000 | 21.11065 | 22.04560 | -0.4979 | 10.26783 |
Annual Sum or Average | 4395.00000 | 22.60837 | 38.17752 | -0.3225 | 9.13616 |
Minimum of Months | 336.00000 | 21.10977 | 17.16515 | -0.6454 | 6.28518 |
Maximum of Months | 379.00000 | 24.04740 | 59.88105 | 0.31091 | 15.32696 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10982 | 24.22779 | -0.5786 | 12.26532 |
February | 308.00000 | 21.10971 | 18.62090 | -0.5961 | 12.60428 |
March | 348.00000 | 21.20274 | 30.08672 | -0.4369 | 9.40945 |
April | 330.00000 | 21.95769 | 37.23125 | -0.1778 | 7.54864 |
May | 344.00000 | 23.28940 | 44.89381 | -0.7253 | 18.05619 |
June | 336.00000 | 23.91569 | 55.54305 | -0.3448 | 7.71637 |
July | 338.00000 | 23.95045 | 61.33472 | -0.2443 | 6.44098 |
August | 348.00000 | 23.93369 | 54.00526 | -0.2814 | 6.92650 |
September | 330.00000 | 23.89534 | 49.42299 | -0.3883 | 8.49217 |
October | 340.00000 | 23.30297 | 43.07116 | 0.27764 | 8.36570 |
November | 330.00000 | 21.40848 | 33.14781 | -0.3452 | 8.38164 |
December | 338.00000 | 21.10972 | 23.40906 | -0.5358 | 11.08802 |
Annual Sum or Average | 4030.00000 | 22.52692 | 39.74315 | -0.3637 | 9.76919 |
Minimum of Months | 308.00000 | 21.10971 | 18.62090 | -0.7253 | 6.44098 |
Maximum of Months | 348.00000 | 23.95045 | 61.33472 | 0.27764 | 18.05619 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10969 | 24.12672 | -0.5775 | 12.22837 |
February | 308.00000 | 21.10962 | 18.52047 | -0.5969 | 12.61726 |
March | 348.00000 | 21.19839 | 30.00336 | -0.4444 | 9.53083 |
April | 330.00000 | 21.93836 | 37.19064 | -0.1914 | 7.59584 |
May | 344.00000 | 23.25416 | 44.92524 | -0.7548 | 19.05647 |
June | 336.00000 | 23.91523 | 55.61685 | -0.3654 | 8.01775 |
July | 338.00000 | 23.94955 | 61.44118 | -0.2680 | 6.68774 |
August | 348.00000 | 23.93289 | 54.08184 | -0.3066 | 7.22816 |
September | 330.00000 | 23.89581 | 49.43954 | -0.4083 | 8.81090 |
October | 340.00000 | 23.29497 | 43.06326 | 0.26260 | 8.21252 |
November | 330.00000 | 21.39220 | 33.08508 | -0.3565 | 8.48489 |
December | 338.00000 | 21.10927 | 23.31001 | -0.5382 | 11.13772 |
Annual Sum or Average | 4030.00000 | 22.51974 | 39.72805 | -0.3778 | 9.96446 |
Minimum of Months | 308.00000 | 21.10927 | 18.52047 | -0.7548 | 6.68774 |
Maximum of Months | 348.00000 | 23.94955 | 61.44118 | 0.26260 | 19.05647 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10975 | 24.12673 | -0.5816 | 12.32626 |
February | 308.00000 | 21.10953 | 18.52079 | -0.6017 | 12.73670 |
March | 348.00000 | 21.19189 | 30.01727 | -0.4510 | 9.64523 |
April | 330.00000 | 21.90921 | 37.26036 | -0.2027 | 7.65212 |
May | 344.00000 | 23.20171 | 45.09168 | -0.7787 | 19.94527 |
June | 336.00000 | 23.91440 | 55.71369 | -0.3689 | 8.07412 |
July | 338.00000 | 23.94905 | 61.54347 | -0.2707 | 6.71676 |
August | 348.00000 | 23.93255 | 54.13853 | -0.3095 | 7.26434 |
September | 330.00000 | 23.89292 | 49.50399 | -0.4124 | 8.88988 |
October | 340.00000 | 23.26405 | 43.18686 | 0.25270 | 8.17449 |
November | 330.00000 | 21.36838 | 33.13576 | -0.3662 | 8.58788 |
December | 338.00000 | 21.10936 | 23.30974 | -0.5429 | 11.24499 |
Annual Sum or Average | 4030.00000 | 22.50739 | 39.79057 | -0.3852 | 10.10315 |
Minimum of Months | 308.00000 | 21.10936 | 18.52079 | -0.7787 | 6.71676 |
Maximum of Months | 348.00000 | 23.94905 | 61.54347 | 0.25270 | 19.94527 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10983 | 24.12644 | -0.5969 | 12.70824 |
February | 308.00000 | 21.10994 | 18.52016 | -0.6187 | 13.18024 |
March | 348.00000 | 21.17495 | 30.05498 | -0.4707 | 10.00627 |
April | 330.00000 | 21.84184 | 37.42160 | -0.2302 | 7.84501 |
May | 344.00000 | 23.07810 | 45.49812 | -0.8315 | 21.93620 |
June | 336.00000 | 23.91146 | 56.03601 | -0.3739 | 8.16146 |
July | 338.00000 | 23.94808 | 61.77375 | -0.2716 | 6.72405 |
August | 348.00000 | 23.93202 | 54.24278 | -0.3097 | 7.27050 |
September | 330.00000 | 23.88299 | 49.68010 | -0.4188 | 9.04407 |
October | 340.00000 | 23.18489 | 43.46374 | 0.23023 | 8.12787 |
November | 330.00000 | 21.32426 | 33.22723 | -0.3873 | 8.85989 |
December | 338.00000 | 21.10960 | 23.30941 | -0.5582 | 11.60132 |
Annual Sum or Average | 4030.00000 | 22.47844 | 39.94209 | -0.4022 | 10.45547 |
Minimum of Months | 308.00000 | 21.10960 | 18.52016 | -0.8315 | 6.72405 |
Maximum of Months | 348.00000 | 23.94808 | 61.77375 | 0.23023 | 21.93620 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 23.98535 | -0.6613 | 14.45523 |
February | 308.00000 | 21.10984 | 18.40214 | -0.6894 | 15.16635 |
March | 348.00000 | 21.15244 | 29.94166 | -0.5354 | 11.37412 |
April | 330.00000 | 21.75625 | 37.47705 | -0.2927 | 8.64630 |
May | 344.00000 | 22.86691 | 46.05484 | -0.9329 | 26.02543 |
June | 336.00000 | 23.90416 | 56.72919 | -0.3798 | 8.29542 |
July | 338.00000 | 23.94972 | 61.90224 | -0.2540 | 6.54222 |
August | 348.00000 | 23.93415 | 54.08885 | -0.2841 | 6.98313 |
September | 330.00000 | 23.85391 | 49.93867 | -0.4232 | 9.32694 |
October | 340.00000 | 23.05012 | 43.70719 | 0.19077 | 8.19910 |
November | 330.00000 | 21.27764 | 33.15997 | -0.4366 | 9.74488 |
December | 338.00000 | 21.10975 | 23.20380 | -0.6170 | 13.07896 |
Annual Sum or Average | 4030.00000 | 22.43362 | 40.04606 | -0.4419 | 11.48411 |
Minimum of Months | 308.00000 | 21.10975 | 18.40214 | -0.9329 | 6.54222 |
Maximum of Months | 348.00000 | 23.94972 | 61.90224 | 0.19077 | 26.02543 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 6706604.22 | 1874378.20 | 1.67 | 4930335.93 | 1776268.28 | 0.00 | 0.12 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 2101.61 | 27-MAR-16:10 | 1537.02 | 27-MAR-16:10 | 564.59 | 27-MAR-16:10 | 584.00 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.620092E+09 | 0.165937E+09 | 39.17 | 0.539910E+09 | 80182376.59 | 0.00 | 0.55 | 07-APR-13:00 | 0.00 | 01-APR-00:05 | 10476.13 | 07-APR-13:00 | 9683.88 | 07-APR-13:00 | 1882.61 | 08-APR-13:00 | 2806.44 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.346507E+10 | 0.895810E+09 | 168.91 | 0.296035E+10 | 0.504729E+09 | 0.00 | 0.86 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 19042.64 | 31-MAY-14:00 | 15894.03 | 30-MAY-13:00 | 5694.96 | 31-MAY-13:30 | 4553.66 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 0.177722E+11 | 0.434634E+10 | 441.54 | 0.118714E+11 | 0.590072E+10 | 0.00 | 1.00 | 08-JUN-07:03 | 0.00 | 01-JUN-00:10 | 48864.33 | 25-JUN-07:02 | 37437.70 | 26-JUN-07:02 | 26373.94 | 16-JUN-07:03 | 10806.36 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.314999E+11 | 0.744867E+10 | 496.79 | 0.194703E+11 | 0.120295E+11 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 49876.07 | 22-JUL-07:02 | 37038.24 | 12-JUL-07:02 | 22708.91 | 22-JUL-07:03 | 10712.18 | 10-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.296976E+11 | 0.714739E+10 | 494.33 | 0.204312E+11 | 0.926640E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 49417.45 | 17-AUG-07:02 | 36207.65 | 22-AUG-07:02 | 20762.96 | 17-AUG-07:03 | 10741.55 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.136661E+11 | 0.334609E+10 | 384.01 | 0.976232E+10 | 0.390379E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 48857.68 | 14-SEP-07:02 | 37899.92 | 04-SEP-07:02 | 18516.58 | 14-SEP-07:02 | 10445.50 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.379316E+10 | 0.943171E+09 | 172.05 | 0.254974E+10 | 0.124342E+10 | 0.00 | 1.00 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 38962.94 | 06-OCT-07:03 | 20253.92 | 06-OCT-07:03 | 18709.02 | 06-OCT-07:03 | 8175.81 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.100521E+12 | 0.242953E+11 | 2198.45 | 0.675903E+11 | 0.329305E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.314999E+11 | 0.744867E+10 | 496.79 | 0.204312E+11 | 0.120295E+11 | 0.00 | 1.00 | 0.00 | 49876.07 | 37899.92 | 26373.94 | 10806.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 10301863.41 | 2838061.00 | 3.83 | 7896035.90 | 2405827.51 | 0.00 | 0.20 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1908.42 | 27-MAR-16:10 | 1413.61 | 27-MAR-16:10 | 494.81 | 27-MAR-16:10 | 519.85 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.482618E+09 | 0.124783E+09 | 48.31 | 0.420888E+09 | 61730050.50 | 0.00 | 1.00 | 07-APR-20:01 | 0.00 | 01-APR-00:05 | 23368.01 | 07-APR-20:01 | 21736.82 | 16-APR-17:01 | 4556.05 | 07-APR-21:16 | 4984.20 | 07-APR-20:01 | 0.00 | 01-APR-00:05 |
May | 0.242857E+10 | 0.609517E+09 | 189.03 | 0.211529E+10 | 0.313279E+09 | 0.00 | 1.00 | 09-MAY-20:01 | 0.00 | 01-MAY-00:10 | 23803.28 | 30-MAY-20:02 | 22314.40 | 27-MAY-18:56 | 6858.52 | 30-MAY-20:57 | 5059.45 | 30-MAY-20:02 | 0.00 | 01-MAY-00:10 |
June | 0.102601E+11 | 0.250209E+10 | 446.30 | 0.714680E+10 | 0.311331E+10 | 0.00 | 1.00 | 01-JUN-20:22 | 0.00 | 01-JUN-00:10 | 25028.95 | 30-JUN-20:02 | 21418.86 | 26-JUN-07:02 | 13062.19 | 06-JUN-20:10 | 5638.21 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.162170E+11 | 0.386758E+10 | 497.67 | 0.105414E+11 | 0.567560E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25238.47 | 22-JUL-07:02 | 21870.41 | 12-JUL-07:02 | 7412.35 | 08-JUL-12:50 | 5615.75 | 10-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.154597E+11 | 0.374594E+10 | 490.47 | 0.110753E+11 | 0.438433E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25109.45 | 17-AUG-07:02 | 22913.10 | 24-AUG-21:48 | 7785.97 | 07-AUG-21:32 | 5636.09 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.792585E+10 | 0.192949E+10 | 382.60 | 0.588710E+10 | 0.203875E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 24976.12 | 14-SEP-07:02 | 22819.86 | 02-SEP-07:02 | 12170.09 | 22-SEP-20:22 | 5440.46 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.253719E+10 | 0.622406E+09 | 190.24 | 0.173177E+10 | 0.805413E+09 | 0.00 | 1.00 | 03-OCT-20:02 | 0.00 | 01-OCT-00:10 | 24945.40 | 23-OCT-20:10 | 22314.40 | 25-OCT-20:07 | 13771.74 | 23-OCT-20:10 | 5253.61 | 23-OCT-20:10 | 0.00 | 01-OCT-00:10 |
November | 6918638.78 | 1906437.43 | 3.72 | 5997754.98 | 920883.79 | 0.00 | 0.26 | 05-NOV-17:30 | 0.00 | 01-NOV-00:10 | 2283.04 | 05-NOV-17:30 | 2283.04 | 05-NOV-17:30 | 410.65 | 10-NOV-21:10 | 603.20 | 05-NOV-17:30 | 0.00 | 01-NOV-00:10 |
December | 214622.78 | 59939.20 | 0.17 | 214622.78 | 0.00 | 0.00 | 0.04 | 17-DEC-20:20 | 0.00 | 01-DEC-00:03 | 357.70 | 17-DEC-20:20 | 357.70 | 17-DEC-20:20 | 0.00 | 17-DEC-20:20 | 99.90 | 17-DEC-20:20 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.553285E+11 | 0.134066E+11 | 2252.34 | 0.389327E+11 | 0.163957E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.162170E+11 | 0.386758E+10 | 497.67 | 0.110753E+11 | 0.567560E+10 | 0.00 | 1.00 | 0.00 | 25238.47 | 22913.10 | 13771.74 | 5638.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 3611750.14 | 1009607.25 | 1.67 | 2679265.44 | 932484.70 | 0.00 | 0.13 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1223.68 | 27-MAR-16:10 | 904.58 | 27-MAR-16:10 | 319.10 | 27-MAR-16:10 | 339.54 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.338959E+09 | 90176498.70 | 37.83 | 0.295561E+09 | 43398022.83 | 0.00 | 0.58 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 6074.34 | 08-APR-12:10 | 5276.82 | 07-APR-13:00 | 1119.48 | 09-APR-11:00 | 1540.57 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.161369E+10 | 0.419053E+09 | 153.17 | 0.141652E+10 | 0.197169E+09 | 0.00 | 0.92 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 10743.79 | 30-MAY-06:03 | 8638.00 | 30-MAY-13:00 | 3775.18 | 31-MAY-06:03 | 2400.35 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.780126E+10 | 0.191097E+10 | 346.53 | 0.534218E+10 | 0.245908E+10 | 0.00 | 1.00 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 | 26894.47 | 25-JUN-07:02 | 22308.93 | 23-JUN-06:02 | 14422.15 | 16-JUN-06:03 | 5655.71 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.128354E+11 | 0.304359E+10 | 362.78 | 0.811425E+10 | 0.472111E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 26906.20 | 21-JUL-06:02 | 21086.36 | 12-JUL-06:02 | 14965.33 | 24-JUL-06:02 | 5741.03 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.122506E+11 | 0.296063E+10 | 368.12 | 0.863061E+10 | 0.362002E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27171.47 | 06-AUG-07:02 | 23720.92 | 31-AUG-06:02 | 13569.81 | 06-AUG-07:03 | 5731.86 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.581644E+10 | 0.142513E+10 | 294.32 | 0.424305E+10 | 0.157339E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 26491.30 | 14-SEP-06:02 | 21726.18 | 04-SEP-07:02 | 11796.84 | 06-SEP-06:02 | 5610.02 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.187173E+10 | 0.465682E+09 | 157.12 | 0.127947E+10 | 0.592266E+09 | 0.00 | 1.00 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 | 24903.95 | 06-OCT-06:03 | 13218.99 | 06-OCT-06:03 | 11684.96 | 06-OCT-06:03 | 5238.40 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 588419.76 | 165583.32 | 0.83 | 473987.76 | 114432.00 | 0.00 | 0.03 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 272.39 | 04-NOV-13:00 | 217.87 | 04-NOV-13:00 | 54.52 | 04-NOV-13:00 | 76.56 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.425323E+11 | 0.103164E+11 | 1722.36 | 0.293248E+11 | 0.132075E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.128354E+11 | 0.304359E+10 | 368.12 | 0.863061E+10 | 0.472111E+10 | 0.00 | 1.00 | 0.00 | 27171.47 | 23720.92 | 14965.33 | 5741.03 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 2094720.97 | 588840.31 | 1.33 | 1552652.89 | 542068.08 | 0.00 | 0.10 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 932.19 | 27-MAR-16:10 | 688.31 | 27-MAR-16:10 | 243.88 | 27-MAR-16:10 | 260.64 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.316942E+09 | 84582336.81 | 35.33 | 0.276539E+09 | 40403181.47 | 0.00 | 0.57 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 5916.53 | 08-APR-12:10 | 5097.46 | 07-APR-13:00 | 1030.94 | 09-APR-11:00 | 1505.39 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.157057E+10 | 0.408000E+09 | 148.25 | 0.137803E+10 | 0.192543E+09 | 0.00 | 0.90 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 10424.71 | 30-MAY-06:03 | 8604.57 | 30-MAY-13:00 | 3715.13 | 31-MAY-06:03 | 2390.68 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.776487E+10 | 0.190172E+10 | 346.06 | 0.531505E+10 | 0.244982E+10 | 0.00 | 1.00 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 | 26793.84 | 25-JUN-07:02 | 22243.36 | 23-JUN-06:02 | 14370.51 | 16-JUN-06:03 | 5634.49 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.128390E+11 | 0.304260E+10 | 362.94 | 0.811816E+10 | 0.472088E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 26811.27 | 21-JUL-06:02 | 21030.39 | 12-JUL-06:02 | 14907.56 | 24-JUL-06:02 | 5719.45 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.122703E+11 | 0.296330E+10 | 367.97 | 0.864785E+10 | 0.362243E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27073.42 | 06-AUG-07:02 | 23645.08 | 31-AUG-06:02 | 13484.19 | 06-AUG-07:03 | 5710.54 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.580166E+10 | 0.142078E+10 | 292.77 | 0.423233E+10 | 0.156932E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 26393.75 | 14-SEP-06:02 | 21671.91 | 04-SEP-07:02 | 11745.23 | 06-SEP-06:02 | 5589.23 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.181773E+10 | 0.452619E+09 | 152.71 | 0.124136E+10 | 0.576374E+09 | 0.00 | 1.00 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 | 24653.48 | 06-OCT-06:03 | 13079.98 | 06-OCT-06:03 | 11573.49 | 06-OCT-06:03 | 5185.78 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 5894.95 | 1669.54 | 0.17 | 4713.83 | 1181.12 | 0.00 | 0.00 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 9.82 | 04-NOV-13:00 | 7.86 | 04-NOV-13:00 | 1.97 | 04-NOV-13:00 | 2.78 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.423832E+11 | 0.102742E+11 | 1707.54 | 0.292109E+11 | 0.131723E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.128390E+11 | 0.304260E+10 | 367.97 | 0.864785E+10 | 0.472088E+10 | 0.00 | 1.00 | 0.00 | 27073.42 | 23645.08 | 14907.56 | 5719.45 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 946158.44 | 267693.52 | 1.00 | 699117.50 | 247040.94 | 0.00 | 0.07 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 618.94 | 27-MAR-16:10 | 456.10 | 27-MAR-16:10 | 162.85 | 27-MAR-16:10 | 174.52 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.279184E+09 | 75009904.68 | 32.83 | 0.243978E+09 | 35206206.23 | 0.00 | 0.54 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 5583.81 | 08-APR-12:10 | 4798.88 | 07-APR-13:00 | 1025.59 | 08-APR-13:00 | 1431.88 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.146139E+10 | 0.380828E+09 | 137.00 | 0.127926E+10 | 0.182132E+09 | 0.00 | 0.83 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 9740.72 | 31-MAY-14:00 | 8451.36 | 30-MAY-13:00 | 2909.37 | 31-MAY-13:00 | 2357.61 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.752147E+10 | 0.184788E+10 | 342.93 | 0.513256E+10 | 0.238892E+10 | 0.00 | 1.00 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 | 26747.36 | 25-JUN-07:02 | 22075.88 | 23-JUN-06:02 | 14405.12 | 16-JUN-06:03 | 5627.12 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.125985E+11 | 0.299215E+10 | 363.27 | 0.793538E+10 | 0.466310E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 26767.79 | 21-JUL-06:02 | 20866.84 | 12-JUL-06:02 | 14929.51 | 24-JUL-06:02 | 5712.33 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.120439E+11 | 0.291410E+10 | 367.29 | 0.846157E+10 | 0.358234E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27028.82 | 06-AUG-07:02 | 23489.29 | 31-AUG-06:02 | 13613.79 | 06-AUG-07:03 | 5703.07 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.561470E+10 | 0.137884E+10 | 290.03 | 0.408451E+10 | 0.153019E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 26354.10 | 14-SEP-06:02 | 21530.32 | 04-SEP-07:02 | 11774.44 | 06-SEP-06:02 | 5581.69 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.168780E+10 | 0.421615E+09 | 144.24 | 0.115231E+10 | 0.535486E+09 | 0.00 | 1.00 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 | 22078.49 | 06-OCT-06:03 | 11632.54 | 06-OCT-06:03 | 10445.95 | 06-OCT-06:03 | 4645.58 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.412079E+11 | 0.100107E+11 | 1678.59 | 0.282903E+11 | 0.129176E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.125985E+11 | 0.299215E+10 | 367.29 | 0.846157E+10 | 0.466310E+10 | 0.00 | 1.00 | 0.00 | 27028.82 | 23489.29 | 14929.51 | 5712.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 712944.66 | 202880.63 | 0.50 | 511862.38 | 201082.28 | 0.00 | 0.03 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 488.54 | 27-MAR-16:00 | 349.18 | 27-MAR-16:00 | 139.37 | 27-MAR-16:00 | 139.10 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.436725E+09 | 0.117903E+09 | 30.17 | 0.376423E+09 | 60302093.12 | 0.00 | 0.51 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 9446.29 | 08-APR-12:00 | 8255.49 | 07-APR-13:00 | 1752.69 | 08-APR-13:00 | 2459.67 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.239700E+10 | 0.623498E+09 | 116.36 | 0.205285E+10 | 0.344158E+09 | 0.00 | 0.92 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 19640.08 | 31-MAY-07:03 | 15899.88 | 31-MAY-07:03 | 5863.33 | 31-MAY-13:00 | 4384.23 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.130577E+11 | 0.319988E+10 | 329.08 | 0.868033E+10 | 0.437739E+10 | 0.00 | 1.00 | 08-JUN-07:03 | 0.00 | 01-JUN-00:10 | 48431.37 | 25-JUN-08:62 | 35453.41 | 23-JUN-07:03 | 24567.47 | 25-JUN-08:04 | 10387.68 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.223924E+11 | 0.528887E+10 | 350.69 | 0.137177E+11 | 0.867468E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 48509.00 | 09-JUL-08:62 | 37539.81 | 12-JUL-07:02 | 27604.13 | 24-JUL-07:03 | 10364.36 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.217254E+11 | 0.523919E+10 | 361.63 | 0.149148E+11 | 0.681063E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 48042.71 | 06-AUG-08:62 | 35695.58 | 21-AUG-07:03 | 27964.11 | 06-AUG-08:03 | 10302.64 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.974259E+10 | 0.238629E+10 | 277.62 | 0.690328E+10 | 0.283931E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 47010.09 | 14-SEP-07:02 | 37705.97 | 04-SEP-08:62 | 18839.70 | 14-SEP-07:02 | 10048.86 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.277078E+10 | 0.691353E+09 | 127.01 | 0.184028E+10 | 0.930495E+09 | 0.00 | 1.00 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 37134.73 | 06-OCT-07:03 | 19470.69 | 06-OCT-07:03 | 17664.04 | 06-OCT-07:03 | 7797.17 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.725233E+11 | 0.175472E+11 | 1593.06 | 0.484862E+11 | 0.240372E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.223924E+11 | 0.528887E+10 | 361.63 | 0.149148E+11 | 0.867468E+10 | 0.00 | 1.00 | 0.00 | 48509.00 | 37705.97 | 27964.11 | 10387.68 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 50584.06 | 14463.66 | 0.33 | 36499.44 | 14084.62 | 0.00 | 0.01 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 84.10 | 27-MAR-16:10 | 60.68 | 27-MAR-16:10 | 23.42 | 27-MAR-16:10 | 24.05 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.211480E+09 | 57319941.44 | 28.33 | 0.183194E+09 | 28286560.46 | 0.00 | 0.50 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4769.08 | 08-APR-12:00 | 4143.22 | 07-APR-13:00 | 867.27 | 08-APR-13:00 | 1242.08 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.119731E+10 | 0.312234E+09 | 112.69 | 0.102821E+10 | 0.169102E+09 | 0.00 | 0.85 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 9326.36 | 31-MAY-14:10 | 8021.28 | 30-MAY-13:00 | 2984.34 | 31-MAY-13:00 | 2264.90 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.666089E+10 | 0.163773E+10 | 326.56 | 0.444611E+10 | 0.221478E+10 | 0.00 | 1.00 | 08-JUN-07:03 | 0.00 | 01-JUN-00:10 | 25126.28 | 25-JUN-08:62 | 18010.47 | 22-JUN-07:02 | 12708.29 | 25-JUN-08:62 | 5393.75 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.114840E+11 | 0.272155E+10 | 351.13 | 0.706650E+10 | 0.441753E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25170.90 | 09-JUL-08:62 | 19520.49 | 12-JUL-07:02 | 14303.38 | 24-JUL-07:03 | 5381.46 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.111373E+11 | 0.269449E+10 | 361.71 | 0.767608E+10 | 0.346120E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24921.49 | 06-AUG-08:62 | 18519.41 | 21-AUG-07:03 | 14498.07 | 06-AUG-08:03 | 5349.37 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.497607E+10 | 0.122226E+10 | 276.31 | 0.354115E+10 | 0.143493E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 24370.03 | 14-SEP-07:02 | 19578.18 | 04-SEP-08:62 | 9713.71 | 14-SEP-07:02 | 5217.12 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.138969E+10 | 0.347426E+09 | 123.13 | 0.927546E+09 | 0.462141E+09 | 0.00 | 1.00 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 17179.79 | 06-OCT-07:03 | 8992.61 | 06-OCT-07:03 | 8187.19 | 06-OCT-07:03 | 3612.59 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.370568E+11 | 0.899302E+10 | 1580.20 | 0.248688E+11 | 0.121880E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.114840E+11 | 0.272155E+10 | 361.71 | 0.767608E+10 | 0.441753E+10 | 0.00 | 1.00 | 0.00 | 25170.90 | 19578.18 | 14498.07 | 5393.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 42414.51 | 12131.93 | 0.33 | 30542.34 | 11872.17 | 0.00 | 0.01 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 70.53 | 27-MAR-16:10 | 50.79 | 27-MAR-16:10 | 19.74 | 27-MAR-16:10 | 20.18 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.201326E+09 | 54672018.47 | 27.17 | 0.174251E+09 | 27075149.29 | 0.00 | 0.49 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4661.99 | 08-APR-12:00 | 4041.87 | 07-APR-13:00 | 848.77 | 08-APR-13:00 | 1217.04 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.115340E+10 | 0.301113E+09 | 108.36 | 0.988220E+09 | 0.165182E+09 | 0.00 | 0.84 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 9248.12 | 31-MAY-14:10 | 7938.51 | 30-MAY-13:00 | 2968.49 | 31-MAY-13:00 | 2246.21 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.657395E+10 | 0.161748E+10 | 325.60 | 0.438037E+10 | 0.219358E+10 | 0.00 | 1.00 | 08-JUN-07:03 | 0.00 | 01-JUN-00:10 | 25031.45 | 25-JUN-08:62 | 17915.13 | 22-JUN-07:02 | 12711.38 | 25-JUN-08:62 | 5374.10 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.113960E+11 | 0.270152E+10 | 351.02 | 0.699806E+10 | 0.439796E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25076.82 | 09-JUL-08:62 | 19404.18 | 12-JUL-07:02 | 14266.29 | 24-JUL-07:03 | 5361.91 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.110587E+11 | 0.267604E+10 | 361.75 | 0.760900E+10 | 0.344971E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24830.25 | 06-AUG-08:62 | 18410.01 | 21-AUG-07:03 | 14457.41 | 06-AUG-08:03 | 5329.95 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.491661E+10 | 0.120826E+10 | 273.94 | 0.349301E+10 | 0.142361E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 24283.53 | 14-SEP-07:02 | 19464.90 | 04-SEP-08:62 | 9740.16 | 14-SEP-07:02 | 5198.15 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.133981E+10 | 0.335356E+09 | 119.99 | 0.892623E+09 | 0.447192E+09 | 0.00 | 1.00 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 16234.42 | 06-OCT-07:03 | 8471.86 | 06-OCT-07:03 | 7762.56 | 06-OCT-07:03 | 3414.41 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.366399E+11 | 0.889445E+10 | 1568.16 | 0.245356E+11 | 0.121043E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.113960E+11 | 0.270152E+10 | 361.75 | 0.760900E+10 | 0.439796E+10 | 0.00 | 1.00 | 0.00 | 25076.82 | 19464.90 | 14457.41 | 5374.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 6.04 | 1.73 | 0.17 | 4.33 | 1.72 | 0.00 | 0.00 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 | 0.01 | 27-MAR-16:20 | 0.01 | 27-MAR-16:20 | 0.00 | 27-MAR-16:20 | 0.00 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 |
April | 0.177081E+09 | 48318042.37 | 25.00 | 0.153331E+09 | 23749500.07 | 0.00 | 0.47 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4426.29 | 08-APR-12:00 | 3833.63 | 07-APR-13:00 | 801.00 | 08-APR-13:00 | 1162.29 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.105517E+10 | 0.276310E+09 | 99.61 | 0.900114E+09 | 0.155058E+09 | 0.00 | 0.83 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 9089.62 | 31-MAY-14:10 | 7785.18 | 30-MAY-13:00 | 2928.01 | 31-MAY-13:00 | 2211.11 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.635053E+10 | 0.156586E+10 | 318.97 | 0.422153E+10 | 0.212900E+10 | 0.00 | 1.00 | 15-JUN-07:03 | 0.00 | 01-JUN-00:10 | 24938.24 | 25-JUN-08:62 | 16905.37 | 20-JUN-07:02 | 12823.40 | 25-JUN-08:62 | 5357.91 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.112413E+11 | 0.266742E+10 | 350.97 | 0.688661E+10 | 0.435473E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 24987.36 | 09-JUL-08:62 | 19224.53 | 12-JUL-07:02 | 14269.61 | 24-JUL-07:03 | 5346.11 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.109506E+11 | 0.265107E+10 | 361.24 | 0.752346E+10 | 0.342717E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24752.50 | 06-AUG-08:62 | 17768.89 | 22-AUG-07:02 | 14437.66 | 06-AUG-08:03 | 5313.81 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.479706E+10 | 0.118013E+10 | 271.65 | 0.340292E+10 | 0.139413E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 24209.08 | 14-SEP-07:02 | 19313.49 | 04-SEP-08:62 | 9862.96 | 14-SEP-07:02 | 5182.01 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.124050E+10 | 0.311067E+09 | 112.93 | 0.826371E+09 | 0.414128E+09 | 0.00 | 1.00 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 13229.35 | 06-OCT-07:03 | 6828.30 | 06-OCT-07:03 | 6401.05 | 06-OCT-07:03 | 2784.31 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.358123E+11 | 0.870018E+10 | 1540.54 | 0.239143E+11 | 0.118980E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.112413E+11 | 0.266742E+10 | 361.24 | 0.752346E+10 | 0.435473E+10 | 0.00 | 1.00 | 0.00 | 24987.36 | 19313.49 | 14437.66 | 5357.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.161700E+09 | 44309523.71 | 21.00 | 0.140715E+09 | 20985379.99 | 0.00 | 0.46 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4645.66 | 08-APR-12:00 | 3974.94 | 07-APR-13:00 | 791.19 | 08-APR-12:50 | 1222.59 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.999726E+09 | 0.262796E+09 | 90.69 | 0.855694E+09 | 0.144032E+09 | 0.00 | 0.81 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 | 9178.33 | 31-MAY-14:10 | 8164.97 | 30-MAY-13:00 | 2942.05 | 31-MAY-13:00 | 2319.78 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.620223E+10 | 0.154189E+10 | 304.00 | 0.416702E+10 | 0.203521E+10 | 0.00 | 1.00 | 15-JUN-11:40 | 0.00 | 01-JUN-00:10 | 26750.60 | 25-JUN-08:62 | 17424.96 | 20-JUN-07:02 | 14333.28 | 25-JUN-08:62 | 5730.86 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.116890E+11 | 0.278762E+10 | 351.31 | 0.724412E+10 | 0.444490E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 26802.79 | 09-JUL-08:62 | 18504.27 | 11-JUL-07:02 | 13930.30 | 09-JUL-08:03 | 5716.79 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.116206E+11 | 0.281945E+10 | 360.93 | 0.807984E+10 | 0.354074E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 26496.17 | 06-AUG-08:62 | 19042.19 | 22-AUG-07:02 | 15578.30 | 06-AUG-08:62 | 5688.27 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.490383E+10 | 0.120811E+10 | 258.59 | 0.352604E+10 | 0.137780E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 26150.00 | 14-SEP-07:02 | 20318.79 | 04-SEP-08:62 | 11839.10 | 14-SEP-07:02 | 5557.69 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.121171E+10 | 0.303892E+09 | 101.42 | 0.818426E+09 | 0.393287E+09 | 0.00 | 0.76 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 | 8596.35 | 04-OCT-13:00 | 6331.36 | 04-OCT-13:00 | 2792.31 | 24-OCT-12:40 | 2068.25 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.367888E+11 | 0.896807E+10 | 1487.93 | 0.248318E+11 | 0.119570E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.116890E+11 | 0.281945E+10 | 360.93 | 0.807984E+10 | 0.444490E+10 | 0.00 | 1.00 | 0.00 | 26802.79 | 20318.79 | 15578.30 | 5730.86 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.64 | 83.42 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.10 | 81.87 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.68 | 58.70 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.57 | 43.92 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.40 | 29.06 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.42 | 15.62 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.13 | 7.75 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.05 | 11.56 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.60 | 24.03 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.98 | 43.34 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.91 | 60.68 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.21 | 75.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.74 | 44.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.40 | 7.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.98 | 83.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.64 | 83.42 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.10 | 81.87 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.68 | 58.70 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.57 | 43.92 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.40 | 29.06 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.42 | 15.62 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.13 | 7.75 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.05 | 11.56 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.60 | 24.03 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.98 | 43.34 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.91 | 60.68 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.21 | 75.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.74 | 44.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.40 | 7.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.98 | 83.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.64 | 83.42 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.10 | 81.87 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.68 | 58.70 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.57 | 43.92 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.40 | 29.06 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.42 | 15.62 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.13 | 7.75 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.05 | 11.56 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.60 | 24.03 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.98 | 43.34 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.91 | 60.68 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.21 | 75.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.74 | 44.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.40 | 7.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.98 | 83.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.64 | 83.42 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.10 | 81.87 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.68 | 58.70 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.57 | 43.92 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.40 | 29.06 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.42 | 15.62 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.13 | 7.75 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.05 | 11.56 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.60 | 24.03 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.98 | 43.34 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.91 | 60.68 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.21 | 75.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.74 | 44.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.40 | 7.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.98 | 83.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.64 | 66.55 | 35.08 | 104.58 | 98.99 | 0.00 | 0.00 | 0.00 |
February | 134.06 | 88.73 | 45.32 | 141.28 | 97.17 | 0.00 | 0.00 | 0.00 |
March | 120.94 | 67.13 | 53.82 | 135.91 | 69.67 | 0.00 | 0.00 | 0.00 |
April | 93.85 | 37.11 | 56.74 | 109.22 | 52.21 | 0.00 | 0.00 | 0.00 |
May | 82.24 | 17.15 | 65.09 | 100.51 | 34.62 | 0.00 | 0.00 | 0.00 |
June | 77.18 | 11.80 | 65.39 | 107.52 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 80.90 | 14.05 | 66.85 | 125.03 | 9.34 | 0.00 | 0.00 | 0.00 |
August | 108.04 | 40.07 | 67.97 | 166.96 | 13.91 | 0.00 | 0.00 | 0.00 |
September | 117.22 | 60.63 | 56.59 | 160.64 | 28.74 | 0.00 | 0.00 | 0.00 |
October | 160.59 | 100.70 | 59.89 | 205.82 | 51.69 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 66.87 | 44.48 | 124.06 | 72.16 | 0.00 | 0.00 | 0.00 |
December | 110.16 | 78.21 | 31.95 | 118.43 | 90.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.06 | 53.91 | 54.15 | 133.35 | 52.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.18 | 11.80 | 31.95 | 100.51 | 9.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.59 | 100.70 | 67.97 | 205.82 | 98.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.64 | 66.55 | 35.08 | 104.58 | 98.99 | 0.00 | 0.00 | 0.00 |
February | 134.06 | 88.73 | 45.32 | 141.28 | 97.17 | 0.00 | 0.00 | 0.00 |
March | 120.94 | 67.13 | 53.82 | 135.91 | 69.67 | 0.00 | 0.00 | 0.00 |
April | 93.85 | 37.11 | 56.74 | 109.22 | 52.21 | 0.00 | 0.00 | 0.00 |
May | 82.24 | 17.15 | 65.09 | 100.51 | 34.62 | 0.00 | 0.00 | 0.00 |
June | 77.18 | 11.80 | 65.39 | 107.52 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 80.90 | 14.05 | 66.85 | 125.03 | 9.34 | 0.00 | 0.00 | 0.00 |
August | 108.04 | 40.07 | 67.97 | 166.96 | 13.91 | 0.00 | 0.00 | 0.00 |
September | 117.22 | 60.63 | 56.59 | 160.64 | 28.74 | 0.00 | 0.00 | 0.00 |
October | 160.59 | 100.70 | 59.89 | 205.82 | 51.69 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 66.87 | 44.48 | 124.06 | 72.16 | 0.00 | 0.00 | 0.00 |
December | 110.16 | 78.21 | 31.95 | 118.43 | 90.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.06 | 53.91 | 54.15 | 133.35 | 52.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.18 | 11.80 | 31.95 | 100.51 | 9.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.59 | 100.70 | 67.97 | 205.82 | 98.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 85.67 | 87.59 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 115.80 | 86.15 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.36 | 62.92 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.16 | 47.45 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.09 | 30.79 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.10 | 16.03 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.08 | 7.93 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.09 | 11.62 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.34 | 24.38 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.00 | 44.89 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 101.56 | 64.50 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.23 | 79.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 109.90 | 46.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.09 | 7.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.00 | 87.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 85.67 | 87.59 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 115.80 | 86.15 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.36 | 62.92 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.16 | 47.45 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.09 | 30.79 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.10 | 16.03 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 104.08 | 7.93 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 139.09 | 11.62 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.34 | 24.38 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.00 | 44.89 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 101.56 | 64.50 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.23 | 79.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 109.90 | 46.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.09 | 7.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.00 | 87.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.64 | 66.55 | 35.08 | 103.44 | 103.90 | 0.00 | 0.00 | 0.00 |
February | 134.06 | 88.73 | 45.32 | 139.75 | 102.22 | 0.00 | 0.00 | 0.00 |
March | 120.94 | 67.13 | 53.82 | 134.35 | 74.62 | 0.00 | 0.00 | 0.00 |
April | 93.85 | 37.11 | 56.74 | 107.55 | 56.35 | 0.00 | 0.00 | 0.00 |
May | 82.24 | 17.15 | 65.09 | 98.96 | 36.66 | 0.00 | 0.00 | 0.00 |
June | 77.18 | 11.80 | 65.39 | 107.16 | 19.16 | 0.00 | 0.00 | 0.00 |
July | 80.90 | 14.05 | 66.85 | 124.98 | 9.55 | 0.00 | 0.00 | 0.00 |
August | 108.04 | 40.07 | 67.97 | 167.02 | 13.99 | 0.00 | 0.00 | 0.00 |
September | 117.22 | 60.63 | 56.59 | 160.36 | 29.14 | 0.00 | 0.00 | 0.00 |
October | 160.59 | 100.70 | 59.89 | 204.70 | 53.51 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 66.87 | 44.48 | 122.47 | 76.65 | 0.00 | 0.00 | 0.00 |
December | 110.16 | 78.21 | 31.95 | 117.28 | 94.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.06 | 53.91 | 54.15 | 132.36 | 55.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.18 | 11.80 | 31.95 | 98.96 | 9.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.59 | 100.70 | 67.97 | 204.70 | 103.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 85.86 | 85.35 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 115.95 | 84.20 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.64 | 61.13 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.52 | 46.22 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.26 | 31.04 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 88.93 | 17.25 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.68 | 9.44 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.71 | 13.23 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.28 | 25.74 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.24 | 45.20 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 101.99 | 62.86 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.44 | 77.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 109.98 | 46.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.26 | 9.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.24 | 85.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 85.86 | 85.35 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 115.95 | 84.20 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.64 | 61.13 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.52 | 46.22 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.26 | 31.04 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 88.93 | 17.25 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.68 | 9.44 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.71 | 13.23 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.28 | 25.74 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.24 | 45.20 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 101.99 | 62.86 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.44 | 77.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 109.98 | 46.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.26 | 9.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.24 | 85.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 103.11 | 100.71 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 139.17 | 99.37 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 133.96 | 72.12 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 107.39 | 54.61 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 98.62 | 36.74 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.38 | 20.48 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.83 | 11.26 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.67 | 15.81 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.41 | 30.58 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 203.86 | 53.57 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 122.31 | 74.31 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 116.89 | 92.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 131.74 | 54.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 98.62 | 11.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 203.86 | 100.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 85.99 | 84.39 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.09 | 83.35 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.82 | 60.32 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.76 | 45.48 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.50 | 30.58 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 88.95 | 17.21 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.66 | 9.48 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.69 | 13.31 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.29 | 25.70 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.39 | 44.81 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.26 | 61.93 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.56 | 77.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.10 | 45.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.50 | 9.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.39 | 84.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 85.99 | 84.39 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.09 | 83.35 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 111.82 | 60.32 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 89.76 | 45.48 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.50 | 30.58 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 88.95 | 17.21 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.66 | 9.48 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.69 | 13.31 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.29 | 25.70 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.39 | 44.81 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.26 | 61.93 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.56 | 77.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.10 | 45.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.50 | 9.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.39 | 84.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 103.27 | 99.57 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 139.34 | 98.37 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 134.18 | 71.16 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 107.69 | 53.73 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 98.91 | 36.19 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.40 | 20.43 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.82 | 11.32 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.64 | 15.90 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.43 | 30.52 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 204.04 | 53.11 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 122.65 | 73.21 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 117.04 | 91.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 131.89 | 54.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 98.91 | 11.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 204.04 | 99.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.15 | 83.57 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.28 | 82.62 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.04 | 59.61 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.09 | 44.76 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.93 | 29.91 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.09 | 16.94 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.78 | 9.25 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.79 | 13.07 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.40 | 25.39 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.63 | 44.28 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.61 | 61.05 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.71 | 76.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.31 | 45.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.93 | 9.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.63 | 83.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.15 | 83.57 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.28 | 82.62 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.04 | 59.61 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.09 | 44.76 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 82.93 | 29.91 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.09 | 16.94 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.78 | 9.25 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.79 | 13.07 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.40 | 25.39 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.63 | 44.28 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 102.61 | 61.05 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 97.71 | 76.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.31 | 45.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 82.93 | 9.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.63 | 83.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 103.46 | 98.60 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 139.57 | 97.50 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 134.44 | 70.33 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 108.07 | 52.89 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 99.43 | 35.41 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.56 | 20.12 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.96 | 11.05 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.77 | 15.61 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.55 | 30.17 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 204.33 | 52.49 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 123.06 | 72.18 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 117.22 | 90.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 132.14 | 53.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 99.43 | 11.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 204.33 | 98.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.88 | 81.15 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.18 | 80.43 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.79 | 57.76 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.86 | 43.10 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.72 | 28.52 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.17 | 16.16 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.66 | 8.58 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.70 | 12.35 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.48 | 24.60 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.13 | 43.14 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.38 | 59.15 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.36 | 74.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.79 | 43.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.72 | 8.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.13 | 81.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.88 | 81.15 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.18 | 80.43 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.79 | 57.76 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.86 | 43.10 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.72 | 28.52 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.17 | 16.16 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.66 | 8.58 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.70 | 12.35 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.48 | 24.60 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.13 | 43.14 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.38 | 59.15 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.36 | 74.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.79 | 43.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.72 | 8.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.13 | 81.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.88 | 81.15 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.18 | 80.43 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.79 | 57.76 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.86 | 43.10 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.72 | 28.52 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.17 | 16.16 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.66 | 8.58 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.70 | 12.35 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.48 | 24.60 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.13 | 43.14 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.38 | 59.15 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.36 | 74.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.79 | 43.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.72 | 8.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.13 | 81.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.88 | 81.15 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.18 | 80.43 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.79 | 57.76 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.86 | 43.10 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.72 | 28.52 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.17 | 16.16 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.66 | 8.58 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.70 | 12.35 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.48 | 24.60 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.13 | 43.14 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.38 | 59.15 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.36 | 74.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.79 | 43.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.72 | 8.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.13 | 81.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 104.30 | 95.78 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 140.60 | 94.95 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 135.30 | 68.17 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 108.96 | 50.96 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 100.35 | 33.77 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.66 | 19.20 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.80 | 10.25 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.65 | 14.76 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.64 | 29.23 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 204.88 | 51.16 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 123.95 | 69.95 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 117.96 | 87.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 132.69 | 51.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 100.35 | 10.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 204.88 | 95.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 104.30 | 95.78 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 140.60 | 94.95 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 135.30 | 68.17 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 108.96 | 50.96 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 100.35 | 33.77 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.66 | 19.20 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.80 | 10.25 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.65 | 14.76 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.64 | 29.23 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 204.88 | 51.16 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 123.95 | 69.95 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 117.96 | 87.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 132.69 | 51.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 100.35 | 10.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 204.88 | 95.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.57 | 81.59 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.83 | 80.78 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.49 | 57.87 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.69 | 43.03 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.73 | 28.26 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.18 | 15.95 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.75 | 8.30 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.76 | 12.04 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.39 | 24.36 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.91 | 42.93 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.22 | 59.15 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.10 | 74.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.66 | 43.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.73 | 8.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.91 | 81.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.57 | 81.59 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.83 | 80.78 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.49 | 57.87 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.69 | 43.03 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 83.73 | 28.26 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.18 | 15.95 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.75 | 8.30 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.76 | 12.04 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.39 | 24.36 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 170.91 | 42.93 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.22 | 59.15 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.10 | 74.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.66 | 43.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 83.73 | 8.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 170.91 | 81.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 103.97 | 96.25 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 140.23 | 95.32 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 134.98 | 68.27 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 108.81 | 50.84 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 100.39 | 33.46 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.68 | 18.95 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 123.93 | 9.92 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.74 | 14.40 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.56 | 28.95 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 204.67 | 50.90 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 123.79 | 69.92 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 117.69 | 88.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 132.56 | 51.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 100.39 | 9.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 204.67 | 96.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.62 | 81.36 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.90 | 80.52 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.58 | 57.59 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.85 | 42.71 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 84.01 | 27.90 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.26 | 15.84 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.82 | 8.22 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.82 | 11.96 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.45 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.05 | 42.68 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.34 | 58.86 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.16 | 74.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.76 | 43.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 84.01 | 8.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.05 | 81.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.62 | 81.36 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 116.90 | 80.52 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.58 | 57.59 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 90.85 | 42.71 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 84.01 | 27.90 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.26 | 15.84 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.82 | 8.22 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.82 | 11.96 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.45 | 24.25 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.05 | 42.68 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.34 | 58.86 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.16 | 74.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 110.76 | 43.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 84.01 | 8.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.05 | 81.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 104.03 | 95.98 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 140.32 | 95.01 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 135.10 | 67.94 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 108.99 | 50.47 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 100.72 | 33.04 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.78 | 18.82 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 124.02 | 9.83 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.82 | 14.30 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.63 | 28.81 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 204.84 | 50.60 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 123.94 | 69.58 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 117.77 | 87.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 132.69 | 51.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 100.72 | 9.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 204.84 | 95.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.83 | 80.30 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.19 | 79.41 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.88 | 56.55 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 91.26 | 41.73 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 84.64 | 27.03 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.44 | 15.57 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.91 | 8.07 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.87 | 11.83 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.56 | 23.98 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.38 | 42.05 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.65 | 58.03 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.39 | 73.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 111.02 | 42.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 84.64 | 8.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.38 | 80.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 86.83 | 80.30 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 117.19 | 79.41 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 112.88 | 56.55 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 91.26 | 41.73 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 84.64 | 27.03 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.44 | 15.57 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.91 | 8.07 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.87 | 11.83 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.56 | 23.98 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 171.38 | 42.05 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 103.65 | 58.03 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 98.39 | 73.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 111.02 | 42.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 84.64 | 8.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 171.38 | 80.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 104.28 | 94.73 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 140.67 | 93.69 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 135.46 | 66.71 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 109.48 | 49.31 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 101.47 | 32.01 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 106.99 | 18.50 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 124.13 | 9.65 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.87 | 14.16 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.76 | 28.49 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 205.23 | 49.86 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 124.31 | 68.59 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 118.04 | 86.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 133.00 | 50.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 101.47 | 9.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 205.23 | 94.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 87.60 | 75.92 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 118.27 | 74.72 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 113.86 | 52.48 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 92.26 | 38.31 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 86.00 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.87 | 14.49 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.88 | 7.63 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.62 | 11.50 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.68 | 23.08 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 172.00 | 40.15 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 104.44 | 55.21 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 99.18 | 69.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 111.66 | 40.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 86.00 | 7.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 172.00 | 75.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.55 | 55.36 | 29.18 | 87.60 | 75.92 | 0.00 | 0.00 | 0.00 |
February | 111.51 | 73.81 | 37.70 | 118.27 | 74.72 | 0.00 | 0.00 | 0.00 |
March | 100.61 | 55.84 | 44.77 | 113.86 | 52.48 | 0.00 | 0.00 | 0.00 |
April | 78.07 | 30.87 | 47.20 | 92.26 | 38.31 | 0.00 | 0.00 | 0.00 |
May | 68.41 | 14.27 | 54.14 | 86.00 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 64.20 | 9.81 | 54.39 | 89.87 | 14.49 | 0.00 | 0.00 | 0.00 |
July | 67.30 | 11.69 | 55.61 | 103.88 | 7.63 | 0.00 | 0.00 | 0.00 |
August | 89.87 | 33.33 | 56.54 | 138.62 | 11.50 | 0.00 | 0.00 | 0.00 |
September | 97.51 | 50.44 | 47.07 | 133.68 | 23.08 | 0.00 | 0.00 | 0.00 |
October | 133.58 | 83.77 | 49.82 | 172.00 | 40.15 | 0.00 | 0.00 | 0.00 |
November | 92.63 | 55.63 | 37.00 | 104.44 | 55.21 | 0.00 | 0.00 | 0.00 |
December | 91.64 | 65.06 | 26.58 | 99.18 | 69.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.89 | 44.84 | 45.04 | 111.66 | 40.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.20 | 9.81 | 26.58 | 86.00 | 7.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.58 | 83.77 | 56.54 | 172.00 | 75.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.08 | 66.19 | 34.89 | 105.22 | 89.54 | 0.00 | 0.00 | 0.00 |
February | 133.32 | 88.25 | 45.07 | 141.98 | 88.15 | 0.00 | 0.00 | 0.00 |
March | 120.28 | 66.76 | 53.52 | 136.64 | 61.91 | 0.00 | 0.00 | 0.00 |
April | 93.34 | 36.91 | 56.43 | 110.69 | 45.29 | 0.00 | 0.00 | 0.00 |
May | 81.79 | 17.06 | 64.73 | 103.10 | 29.04 | 0.00 | 0.00 | 0.00 |
June | 76.76 | 11.73 | 65.03 | 107.50 | 17.23 | 0.00 | 0.00 | 0.00 |
July | 80.46 | 13.98 | 66.49 | 124.08 | 9.13 | 0.00 | 0.00 | 0.00 |
August | 107.45 | 39.85 | 67.59 | 165.57 | 13.76 | 0.00 | 0.00 | 0.00 |
September | 116.58 | 60.30 | 56.28 | 159.91 | 27.43 | 0.00 | 0.00 | 0.00 |
October | 159.71 | 100.15 | 59.56 | 205.97 | 47.61 | 0.00 | 0.00 | 0.00 |
November | 110.74 | 66.51 | 44.24 | 125.26 | 65.27 | 0.00 | 0.00 | 0.00 |
December | 109.56 | 77.78 | 31.78 | 119.00 | 82.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.47 | 53.61 | 53.85 | 133.76 | 47.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.76 | 11.73 | 31.78 | 103.10 | 9.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.71 | 100.15 | 67.59 | 205.97 | 89.54 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232054E+09 | 0.223431E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283288E+09 | 0.198052E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301812E+09 | 0.157213E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.234770E+09 | 0.113835E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.223388E+09 | 77832421.63 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231768E+09 | 40497268.13 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278910E+09 | 20765621.96 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372440E+09 | 30953833.70 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346279E+09 | 62295801.02 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.457940E+09 | 0.116082E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.266751E+09 | 0.157278E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263041E+09 | 0.203007E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349244E+10 | 0.140124E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.223388E+09 | 20765621.96 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.457940E+09 | 0.223431E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232054E+09 | 0.223431E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283288E+09 | 0.198052E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301812E+09 | 0.157213E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.234770E+09 | 0.113835E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.223388E+09 | 77832421.63 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231768E+09 | 40497268.13 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278910E+09 | 20765621.96 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372440E+09 | 30953833.70 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346279E+09 | 62295801.02 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.457940E+09 | 0.116082E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.266751E+09 | 0.157278E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263041E+09 | 0.203007E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349244E+10 | 0.140124E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.223388E+09 | 20765621.96 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.457940E+09 | 0.223431E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232054E+09 | 0.223431E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283288E+09 | 0.198052E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301812E+09 | 0.157213E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.234770E+09 | 0.113835E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.223388E+09 | 77832421.63 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231768E+09 | 40497268.13 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278910E+09 | 20765621.96 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372440E+09 | 30953833.70 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346279E+09 | 62295801.02 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.457940E+09 | 0.116082E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.266751E+09 | 0.157278E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263041E+09 | 0.203007E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349244E+10 | 0.140124E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.223388E+09 | 20765621.96 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.457940E+09 | 0.223431E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232054E+09 | 0.223431E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283288E+09 | 0.198052E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301812E+09 | 0.157213E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.234770E+09 | 0.113835E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.223388E+09 | 77832421.63 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231768E+09 | 40497268.13 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278910E+09 | 20765621.96 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372440E+09 | 30953833.70 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346279E+09 | 62295801.02 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.457940E+09 | 0.116082E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.266751E+09 | 0.157278E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263041E+09 | 0.203007E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349244E+10 | 0.140124E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.223388E+09 | 20765621.96 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.457940E+09 | 0.223431E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272227E+09 | 0.178256E+09 | 93970800.61 | 0.280102E+09 | 0.265142E+09 |
February | 0.324310E+09 | 0.214667E+09 | 0.109643E+09 | 0.341777E+09 | 0.235079E+09 |
March | 0.323938E+09 | 0.179791E+09 | 0.144147E+09 | 0.364022E+09 | 0.186600E+09 |
April | 0.243256E+09 | 96190572.35 | 0.147065E+09 | 0.283101E+09 | 0.135330E+09 |
May | 0.220283E+09 | 45947642.04 | 0.174336E+09 | 0.269201E+09 | 92721440.98 |
June | 0.200061E+09 | 30581343.47 | 0.169479E+09 | 0.278694E+09 | 48425552.54 |
July | 0.216694E+09 | 37639662.46 | 0.179054E+09 | 0.334888E+09 | 25015575.75 |
August | 0.289371E+09 | 0.107332E+09 | 0.182038E+09 | 0.447184E+09 | 37268165.90 |
September | 0.303845E+09 | 0.157161E+09 | 0.146684E+09 | 0.416371E+09 | 74488403.30 |
October | 0.430117E+09 | 0.269714E+09 | 0.160403E+09 | 0.551260E+09 | 0.138451E+09 |
November | 0.288628E+09 | 0.173335E+09 | 0.115293E+09 | 0.321566E+09 | 0.187043E+09 |
December | 0.295053E+09 | 0.209468E+09 | 85585004.99 | 0.317192E+09 | 0.241131E+09 |
Annual Sum or Average | 0.340778E+10 | 0.170008E+10 | 0.170770E+10 | 0.420536E+10 | 0.166670E+10 |
Minimum of Months | 0.200061E+09 | 30581343.47 | 85585004.99 | 0.269201E+09 | 25015575.75 |
Maximum of Months | 0.430117E+09 | 0.269714E+09 | 0.182038E+09 | 0.551260E+09 | 0.265142E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272227E+09 | 0.178256E+09 | 93970800.61 | 0.280102E+09 | 0.265142E+09 |
February | 0.324310E+09 | 0.214667E+09 | 0.109643E+09 | 0.341777E+09 | 0.235079E+09 |
March | 0.323938E+09 | 0.179791E+09 | 0.144147E+09 | 0.364022E+09 | 0.186600E+09 |
April | 0.243256E+09 | 96190572.35 | 0.147065E+09 | 0.283101E+09 | 0.135330E+09 |
May | 0.220283E+09 | 45947642.04 | 0.174336E+09 | 0.269201E+09 | 92721440.98 |
June | 0.200061E+09 | 30581343.47 | 0.169479E+09 | 0.278694E+09 | 48425552.54 |
July | 0.216694E+09 | 37639662.46 | 0.179054E+09 | 0.334888E+09 | 25015575.75 |
August | 0.289371E+09 | 0.107332E+09 | 0.182038E+09 | 0.447184E+09 | 37268165.90 |
September | 0.303845E+09 | 0.157161E+09 | 0.146684E+09 | 0.416371E+09 | 74488403.30 |
October | 0.430117E+09 | 0.269714E+09 | 0.160403E+09 | 0.551260E+09 | 0.138451E+09 |
November | 0.288628E+09 | 0.173335E+09 | 0.115293E+09 | 0.321566E+09 | 0.187043E+09 |
December | 0.295053E+09 | 0.209468E+09 | 85585004.99 | 0.317192E+09 | 0.241131E+09 |
Annual Sum or Average | 0.340778E+10 | 0.170008E+10 | 0.170770E+10 | 0.420536E+10 | 0.166670E+10 |
Minimum of Months | 0.200061E+09 | 30581343.47 | 85585004.99 | 0.269201E+09 | 25015575.75 |
Maximum of Months | 0.430117E+09 | 0.269714E+09 | 0.182038E+09 | 0.551260E+09 | 0.265142E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.229461E+09 | 0.234588E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.280145E+09 | 0.208419E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.298262E+09 | 0.168525E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.231100E+09 | 0.122983E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.219862E+09 | 82465673.39 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230959E+09 | 41551106.90 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278759E+09 | 21242118.58 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372530E+09 | 31121620.30 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345629E+09 | 63187790.24 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.455320E+09 | 0.120231E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.263237E+09 | 0.167194E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.260430E+09 | 0.214153E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.346570E+10 | 0.147566E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.219862E+09 | 21242118.58 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.455320E+09 | 0.234588E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.229461E+09 | 0.234588E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.280145E+09 | 0.208419E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.298262E+09 | 0.168525E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.231100E+09 | 0.122983E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.219862E+09 | 82465673.39 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230959E+09 | 41551106.90 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278759E+09 | 21242118.58 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.372530E+09 | 31121620.30 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345629E+09 | 63187790.24 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.455320E+09 | 0.120231E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.263237E+09 | 0.167194E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.260430E+09 | 0.214153E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.346570E+10 | 0.147566E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.219862E+09 | 21242118.58 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.455320E+09 | 0.234588E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272227E+09 | 0.178256E+09 | 93970800.61 | 0.277061E+09 | 0.278281E+09 |
February | 0.324310E+09 | 0.214667E+09 | 0.109643E+09 | 0.338089E+09 | 0.247291E+09 |
March | 0.323938E+09 | 0.179791E+09 | 0.144147E+09 | 0.359850E+09 | 0.199875E+09 |
April | 0.243256E+09 | 96190572.35 | 0.147065E+09 | 0.278773E+09 | 0.146070E+09 |
May | 0.220283E+09 | 45947642.04 | 0.174336E+09 | 0.265058E+09 | 98181428.23 |
June | 0.200061E+09 | 30581343.47 | 0.169479E+09 | 0.277770E+09 | 49669473.11 |
July | 0.216694E+09 | 37639662.46 | 0.179054E+09 | 0.334741E+09 | 25586388.90 |
August | 0.289371E+09 | 0.107332E+09 | 0.182038E+09 | 0.447342E+09 | 37477181.89 |
September | 0.303845E+09 | 0.157161E+09 | 0.146684E+09 | 0.415666E+09 | 75543630.87 |
October | 0.430117E+09 | 0.269714E+09 | 0.160403E+09 | 0.548255E+09 | 0.143327E+09 |
November | 0.288628E+09 | 0.173335E+09 | 0.115293E+09 | 0.317439E+09 | 0.198684E+09 |
December | 0.295053E+09 | 0.209468E+09 | 85585004.99 | 0.314130E+09 | 0.254239E+09 |
Annual Sum or Average | 0.340778E+10 | 0.170008E+10 | 0.170770E+10 | 0.417417E+10 | 0.175423E+10 |
Minimum of Months | 0.200061E+09 | 30581343.47 | 85585004.99 | 0.265058E+09 | 25586388.90 |
Maximum of Months | 0.430117E+09 | 0.269714E+09 | 0.182038E+09 | 0.548255E+09 | 0.278281E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.229975E+09 | 0.228614E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.280511E+09 | 0.203698E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.299020E+09 | 0.163721E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.232035E+09 | 0.119790E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.220313E+09 | 83126079.69 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230516E+09 | 44708997.42 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277686E+09 | 25279057.41 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371512E+09 | 35447334.57 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345452E+09 | 66729937.84 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.455976E+09 | 0.121052E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.264350E+09 | 0.162923E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.260983E+09 | 0.208722E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.346833E+10 | 0.146381E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.220313E+09 | 25279057.41 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.455976E+09 | 0.228614E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.229975E+09 | 0.228614E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.280511E+09 | 0.203698E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.299020E+09 | 0.163721E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.232035E+09 | 0.119790E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.220313E+09 | 83126079.69 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230516E+09 | 44708997.42 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277686E+09 | 25279057.41 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371512E+09 | 35447334.57 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345452E+09 | 66729937.84 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.455976E+09 | 0.121052E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.264350E+09 | 0.162923E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.260983E+09 | 0.208722E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.346833E+10 | 0.146381E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.220313E+09 | 25279057.41 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.455976E+09 | 0.228614E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.276174E+09 | 0.269755E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.336690E+09 | 0.240404E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.358796E+09 | 0.193169E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.278366E+09 | 0.141539E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.264148E+09 | 98396166.10 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.275729E+09 | 53074895.93 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.331665E+09 | 30169676.68 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443720E+09 | 42341522.15 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413186E+09 | 79255766.76 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.546031E+09 | 0.143477E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.317036E+09 | 0.192600E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.313085E+09 | 0.246493E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.415463E+10 | 0.173067E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.264148E+09 | 30169676.68 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.546031E+09 | 0.269755E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.230326E+09 | 0.226024E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.280848E+09 | 0.201649E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.299501E+09 | 0.161552E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.232666E+09 | 0.117872E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.220966E+09 | 81895037.87 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230567E+09 | 44610303.68 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277655E+09 | 25402815.79 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371457E+09 | 35645203.25 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345493E+09 | 66602343.22 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.456375E+09 | 0.120010E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.265068E+09 | 0.160521E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.261313E+09 | 0.206458E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.347224E+10 | 0.144824E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.220966E+09 | 25402815.79 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.456375E+09 | 0.226024E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.230326E+09 | 0.226024E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.280848E+09 | 0.201649E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.299501E+09 | 0.161552E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.232666E+09 | 0.117872E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.220966E+09 | 81895037.87 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230567E+09 | 44610303.68 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277655E+09 | 25402815.79 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371457E+09 | 35645203.25 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345493E+09 | 66602343.22 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.456375E+09 | 0.120010E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.265068E+09 | 0.160521E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.261313E+09 | 0.206458E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.347224E+10 | 0.144824E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.220966E+09 | 25402815.79 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.456375E+09 | 0.226024E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.276598E+09 | 0.266684E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.337099E+09 | 0.237976E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.359376E+09 | 0.190603E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.279122E+09 | 0.139276E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.264929E+09 | 96941639.53 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.275790E+09 | 52958960.77 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.331628E+09 | 30315841.43 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443654E+09 | 42576528.61 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413236E+09 | 79105115.61 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.546508E+09 | 0.142245E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.317896E+09 | 0.189761E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.313485E+09 | 0.243810E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.415932E+10 | 0.171225E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.264929E+09 | 30315841.43 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.546508E+09 | 0.266684E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.230757E+09 | 0.223832E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.281306E+09 | 0.199866E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.300091E+09 | 0.159671E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.233501E+09 | 0.116025E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.222117E+09 | 80120955.49 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230912E+09 | 43917908.27 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277971E+09 | 24782861.93 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371733E+09 | 34999044.74 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345761E+09 | 65823653.89 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.457020E+09 | 0.118604E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.265960E+09 | 0.158252E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.261712E+09 | 0.204568E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.347884E+10 | 0.143046E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.222117E+09 | 24782861.93 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.457020E+09 | 0.223832E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.230757E+09 | 0.223832E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.281306E+09 | 0.199866E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.300091E+09 | 0.159671E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.233501E+09 | 0.116025E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.222117E+09 | 80120955.49 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.230912E+09 | 43917908.27 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277971E+09 | 24782861.93 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371733E+09 | 34999044.74 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345761E+09 | 65823653.89 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.457020E+09 | 0.118604E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.265960E+09 | 0.158252E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.261712E+09 | 0.204568E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.347884E+10 | 0.143046E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.222117E+09 | 24782861.93 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.457020E+09 | 0.223832E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.277120E+09 | 0.264087E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.337655E+09 | 0.235865E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.360087E+09 | 0.188380E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.280121E+09 | 0.137100E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.266301E+09 | 94852880.64 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.276206E+09 | 52148501.72 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.332006E+09 | 29589675.24 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443986E+09 | 41817788.71 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413559E+09 | 78189047.20 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.547278E+09 | 0.140589E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.318964E+09 | 0.187084E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.313967E+09 | 0.241573E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.416725E+10 | 0.169128E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.266301E+09 | 29589675.24 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.547278E+09 | 0.264087E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232693E+09 | 0.217361E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283474E+09 | 0.194569E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302094E+09 | 0.154697E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235501E+09 | 0.111728E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224241E+09 | 76377351.08 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231141E+09 | 41897958.74 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277630E+09 | 22968677.82 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371485E+09 | 33079230.60 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345988E+09 | 63771817.85 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458342E+09 | 0.115552E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267972E+09 | 0.153321E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263448E+09 | 0.199223E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349401E+10 | 0.138454E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224241E+09 | 22968677.82 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458342E+09 | 0.217361E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232693E+09 | 0.217361E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283474E+09 | 0.194569E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302094E+09 | 0.154697E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235501E+09 | 0.111728E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224241E+09 | 76377351.08 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231141E+09 | 41897958.74 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277630E+09 | 22968677.82 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371485E+09 | 33079230.60 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345988E+09 | 63771817.85 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458342E+09 | 0.115552E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267972E+09 | 0.153321E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263448E+09 | 0.199223E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349401E+10 | 0.138454E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224241E+09 | 22968677.82 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458342E+09 | 0.217361E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232693E+09 | 0.217361E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283474E+09 | 0.194569E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302094E+09 | 0.154697E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235501E+09 | 0.111728E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224241E+09 | 76377351.08 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231141E+09 | 41897958.74 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277630E+09 | 22968677.82 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371485E+09 | 33079230.60 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345988E+09 | 63771817.85 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458342E+09 | 0.115552E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267972E+09 | 0.153321E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263448E+09 | 0.199223E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349401E+10 | 0.138454E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224241E+09 | 22968677.82 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458342E+09 | 0.217361E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232693E+09 | 0.217361E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283474E+09 | 0.194569E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302094E+09 | 0.154697E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235501E+09 | 0.111728E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224241E+09 | 76377351.08 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231141E+09 | 41897958.74 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277630E+09 | 22968677.82 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371485E+09 | 33079230.60 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345988E+09 | 63771817.85 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458342E+09 | 0.115552E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267972E+09 | 0.153321E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263448E+09 | 0.199223E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349401E+10 | 0.138454E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224241E+09 | 22968677.82 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458342E+09 | 0.217361E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.279350E+09 | 0.256537E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.340142E+09 | 0.229696E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.362384E+09 | 0.182589E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.282435E+09 | 0.132083E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.268764E+09 | 90461268.71 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.276455E+09 | 49772467.18 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.331597E+09 | 27440208.69 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443664E+09 | 39529048.13 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413776E+09 | 75766904.96 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.548741E+09 | 0.137014E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.321276E+09 | 0.181313E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.315957E+09 | 0.235327E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.418454E+10 | 0.163753E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.268764E+09 | 27440208.69 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.548741E+09 | 0.256537E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.279350E+09 | 0.256537E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.340142E+09 | 0.229696E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.362384E+09 | 0.182589E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.282435E+09 | 0.132083E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.268764E+09 | 90461268.71 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.276455E+09 | 49772467.18 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.331597E+09 | 27440208.69 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443664E+09 | 39529048.13 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413776E+09 | 75766904.96 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.548741E+09 | 0.137014E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.321276E+09 | 0.181313E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.315957E+09 | 0.235327E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.418454E+10 | 0.163753E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.268764E+09 | 27440208.69 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.548741E+09 | 0.256537E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.231877E+09 | 0.218534E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.282625E+09 | 0.195418E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301283E+09 | 0.155002E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235077E+09 | 0.111523E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224272E+09 | 75689349.22 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231153E+09 | 41336054.84 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277876E+09 | 22230876.44 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371661E+09 | 32247492.79 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345750E+09 | 63150859.25 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.457772E+09 | 0.114996E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267543E+09 | 0.153323E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.262752E+09 | 0.199951E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.348964E+10 | 0.138340E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224272E+09 | 22230876.44 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.457772E+09 | 0.218534E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.231877E+09 | 0.218534E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.282625E+09 | 0.195418E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301283E+09 | 0.155002E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235077E+09 | 0.111523E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.224272E+09 | 75689349.22 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231153E+09 | 41336054.84 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.277876E+09 | 22230876.44 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371661E+09 | 32247492.79 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345750E+09 | 63150859.25 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.457772E+09 | 0.114996E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267543E+09 | 0.153323E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.262752E+09 | 0.199951E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.348964E+10 | 0.138340E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.224272E+09 | 22230876.44 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.457772E+09 | 0.218534E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.278476E+09 | 0.257804E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.339248E+09 | 0.230590E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.361543E+09 | 0.182857E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.282024E+09 | 0.131789E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.268887E+09 | 89621376.17 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.276527E+09 | 49106623.07 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.331934E+09 | 26578254.00 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443930E+09 | 38558565.36 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413577E+09 | 75025811.29 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.548195E+09 | 0.136326E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.320863E+09 | 0.181245E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.315223E+09 | 0.236085E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.418043E+10 | 0.163559E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.268887E+09 | 26578254.00 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.548195E+09 | 0.257804E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232014E+09 | 0.217914E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.282806E+09 | 0.194795E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301536E+09 | 0.154242E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235485E+09 | 0.110695E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.225004E+09 | 74739584.69 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231366E+09 | 41065901.88 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278071E+09 | 22010858.38 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371824E+09 | 32031038.31 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345903E+09 | 62850705.45 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458147E+09 | 0.114323E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267869E+09 | 0.152560E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.262924E+09 | 0.199277E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349295E+10 | 0.137650E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.225004E+09 | 22010858.38 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458147E+09 | 0.217914E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232014E+09 | 0.217914E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.282806E+09 | 0.194795E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.301536E+09 | 0.154242E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.235485E+09 | 0.110695E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.225004E+09 | 74739584.69 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231366E+09 | 41065901.88 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278071E+09 | 22010858.38 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371824E+09 | 32031038.31 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.345903E+09 | 62850705.45 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.458147E+09 | 0.114323E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.267869E+09 | 0.152560E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.262924E+09 | 0.199277E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.349295E+10 | 0.137650E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.225004E+09 | 22010858.38 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.458147E+09 | 0.217914E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.278641E+09 | 0.257068E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.339467E+09 | 0.229851E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.361848E+09 | 0.181958E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.282514E+09 | 0.130813E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.269761E+09 | 88501026.23 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.276782E+09 | 48787803.80 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.332168E+09 | 26318092.73 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.444125E+09 | 38301838.10 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.413762E+09 | 74670547.69 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.548642E+09 | 0.135530E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.321254E+09 | 0.180342E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.315432E+09 | 0.235285E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.418440E+10 | 0.162743E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.269761E+09 | 26318092.73 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.548642E+09 | 0.257068E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232561E+09 | 0.215086E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283503E+09 | 0.192097E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302339E+09 | 0.151464E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.236542E+09 | 0.108154E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.226693E+09 | 72399490.46 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231820E+09 | 40345269.73 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278322E+09 | 21601662.27 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371952E+09 | 31698862.57 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346177E+09 | 62145102.53 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.459018E+09 | 0.112632E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.268664E+09 | 0.150403E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263526E+09 | 0.196639E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.350112E+10 | 0.135466E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.226693E+09 | 21601662.27 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.459018E+09 | 0.215086E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.232561E+09 | 0.215086E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.283503E+09 | 0.192097E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.302339E+09 | 0.151464E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.236542E+09 | 0.108154E+09 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.226693E+09 | 72399490.46 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.231820E+09 | 40345269.73 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278322E+09 | 21601662.27 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371952E+09 | 31698862.57 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346177E+09 | 62145102.53 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.459018E+09 | 0.112632E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.268664E+09 | 0.150403E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.263526E+09 | 0.196639E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.350112E+10 | 0.135466E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.226693E+09 | 21601662.27 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.459018E+09 | 0.215086E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.279303E+09 | 0.253721E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.340308E+09 | 0.226657E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.362821E+09 | 0.178675E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.283782E+09 | 0.127823E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.271774E+09 | 85746119.96 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.277324E+09 | 47942770.79 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.332466E+09 | 25840427.54 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.444277E+09 | 37915691.22 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.414090E+09 | 73841769.38 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.549680E+09 | 0.133538E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.322204E+09 | 0.177795E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.316159E+09 | 0.232164E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.419419E+10 | 0.160166E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.271774E+09 | 25840427.54 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.549680E+09 | 0.253721E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.234633E+09 | 0.203337E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.286121E+09 | 0.180767E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.304951E+09 | 0.140572E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.239141E+09 | 99304230.98 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.230346E+09 | 65647138.50 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.232932E+09 | 37548190.48 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278219E+09 | 20430049.80 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371278E+09 | 30805279.92 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346507E+09 | 59817552.12 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.460693E+09 | 0.107530E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.270711E+09 | 0.143105E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.265646E+09 | 0.186188E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.352118E+10 | 0.127505E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.230346E+09 | 20430049.80 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.460693E+09 | 0.203337E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226449E+09 | 0.148280E+09 | 78168690.91 | 0.234633E+09 | 0.203337E+09 |
February | 0.269774E+09 | 0.178569E+09 | 91205556.37 | 0.286121E+09 | 0.180767E+09 |
March | 0.269464E+09 | 0.149557E+09 | 0.119907E+09 | 0.304951E+09 | 0.140572E+09 |
April | 0.202350E+09 | 80015186.31 | 0.122335E+09 | 0.239141E+09 | 99304230.98 |
May | 0.183241E+09 | 38221096.40 | 0.145020E+09 | 0.230346E+09 | 65647138.50 |
June | 0.166419E+09 | 25438791.30 | 0.140980E+09 | 0.232932E+09 | 37548190.48 |
July | 0.180255E+09 | 31310184.88 | 0.148944E+09 | 0.278219E+09 | 20430049.80 |
August | 0.240710E+09 | 89283405.56 | 0.151427E+09 | 0.371278E+09 | 30805279.92 |
September | 0.252750E+09 | 0.130733E+09 | 0.122018E+09 | 0.346507E+09 | 59817552.12 |
October | 0.357788E+09 | 0.224359E+09 | 0.133429E+09 | 0.460693E+09 | 0.107530E+09 |
November | 0.240092E+09 | 0.144187E+09 | 95905446.71 | 0.270711E+09 | 0.143105E+09 |
December | 0.245437E+09 | 0.174244E+09 | 71193048.88 | 0.265646E+09 | 0.186188E+09 |
Annual Sum or Average | 0.283473E+10 | 0.141420E+10 | 0.142053E+10 | 0.352118E+10 | 0.127505E+10 |
Minimum of Months | 0.166419E+09 | 25438791.30 | 71193048.88 | 0.230346E+09 | 20430049.80 |
Maximum of Months | 0.357788E+09 | 0.224359E+09 | 0.151427E+09 | 0.460693E+09 | 0.203337E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270739E+09 | 0.177282E+09 | 93457298.97 | 0.281811E+09 | 0.239820E+09 |
February | 0.322538E+09 | 0.213494E+09 | 0.109044E+09 | 0.343473E+09 | 0.213247E+09 |
March | 0.322167E+09 | 0.178809E+09 | 0.143359E+09 | 0.365987E+09 | 0.165811E+09 |
April | 0.241926E+09 | 95664940.81 | 0.146261E+09 | 0.286919E+09 | 0.117397E+09 |
May | 0.219080E+09 | 45696562.03 | 0.173383E+09 | 0.276133E+09 | 77784831.29 |
June | 0.198967E+09 | 30414232.30 | 0.168553E+09 | 0.278647E+09 | 44648398.95 |
July | 0.215510E+09 | 37433981.25 | 0.178076E+09 | 0.332334E+09 | 24459107.47 |
August | 0.287789E+09 | 0.106746E+09 | 0.181044E+09 | 0.443459E+09 | 36860180.81 |
September | 0.302185E+09 | 0.156302E+09 | 0.145882E+09 | 0.414479E+09 | 71095750.73 |
October | 0.427766E+09 | 0.268240E+09 | 0.159526E+09 | 0.551676E+09 | 0.127525E+09 |
November | 0.287051E+09 | 0.172388E+09 | 0.114663E+09 | 0.324663E+09 | 0.169175E+09 |
December | 0.293440E+09 | 0.208323E+09 | 85117327.37 | 0.318717E+09 | 0.219802E+09 |
Annual Sum or Average | 0.338916E+10 | 0.169079E+10 | 0.169837E+10 | 0.421830E+10 | 0.150762E+10 |
Minimum of Months | 0.198967E+09 | 30414232.30 | 85117327.37 | 0.276133E+09 | 24459107.47 |
Maximum of Months | 0.427766E+09 | 0.268240E+09 | 0.181044E+09 | 0.551676E+09 | 0.239820E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 555.71 | 531.66 | 541.46 | 354.55 | 186.91 | 0.00 | 0.00 |
February | 750.95 | 521.81 | 714.17 | 472.72 | 241.45 | 0.00 | 0.00 |
March | 722.55 | 374.12 | 644.31 | 357.61 | 286.71 | 0.00 | 0.00 |
April | 580.74 | 280.09 | 499.97 | 197.70 | 302.26 | 0.00 | 0.00 |
May | 534.63 | 185.47 | 438.15 | 91.39 | 346.76 | 0.00 | 0.00 |
June | 572.71 | 99.86 | 411.19 | 62.85 | 348.33 | 0.00 | 0.00 |
July | 666.60 | 49.69 | 431.01 | 74.87 | 356.14 | 0.00 | 0.00 |
August | 890.13 | 74.06 | 575.56 | 213.49 | 362.08 | 0.00 | 0.00 |
September | 855.66 | 153.61 | 624.50 | 323.01 | 301.48 | 0.00 | 0.00 |
October | 1095.53 | 276.74 | 855.51 | 536.46 | 319.04 | 0.00 | 0.00 |
November | 659.77 | 387.04 | 593.22 | 356.26 | 236.96 | 0.00 | 0.00 |
December | 629.68 | 483.23 | 586.86 | 416.63 | 170.23 | 0.00 | 0.00 |
Annual Sum or Average | 709.68 | 283.43 | 575.67 | 287.19 | 288.48 | 0.00 | 0.00 |
Minimum of Months | 534.63 | 49.69 | 411.19 | 62.85 | 170.23 | 0.00 | 0.00 |
Maximum of Months | 1095.53 | 531.66 | 855.51 | 536.46 | 362.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 274.78 | 279.07 | 270.73 | 177.28 | 93.45 | 0.00 | 0.00 |
February | 371.35 | 274.52 | 357.08 | 236.36 | 120.72 | 0.00 | 0.00 |
March | 357.07 | 200.46 | 322.16 | 178.80 | 143.35 | 0.00 | 0.00 |
April | 285.87 | 151.25 | 249.98 | 98.85 | 151.13 | 0.00 | 0.00 |
May | 263.13 | 98.23 | 219.07 | 45.70 | 173.38 | 0.00 | 0.00 |
June | 285.37 | 51.22 | 205.59 | 31.43 | 174.17 | 0.00 | 0.00 |
July | 333.13 | 25.41 | 215.50 | 37.43 | 178.07 | 0.00 | 0.00 |
August | 445.19 | 37.23 | 287.78 | 106.74 | 181.04 | 0.00 | 0.00 |
September | 427.05 | 77.90 | 312.25 | 161.51 | 150.74 | 0.00 | 0.00 |
October | 544.69 | 143.29 | 427.75 | 268.23 | 159.52 | 0.00 | 0.00 |
November | 325.58 | 205.66 | 296.61 | 178.13 | 118.48 | 0.00 | 0.00 |
December | 311.75 | 254.83 | 293.43 | 208.32 | 85.11 | 0.00 | 0.00 |
Annual Sum or Average | 352.15 | 149.21 | 287.84 | 143.60 | 144.24 | 0.00 | 0.00 |
Minimum of Months | 263.13 | 25.41 | 205.59 | 31.43 | 85.11 | 0.00 | 0.00 |
Maximum of Months | 544.69 | 279.07 | 427.75 | 268.23 | 181.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 274.84 | 271.42 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 371.08 | 267.77 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 357.24 | 194.37 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 286.43 | 147.04 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 263.13 | 98.81 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 284.24 | 54.97 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.18 | 30.14 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.08 | 42.28 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 425.96 | 82.07 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 544.35 | 143.96 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 326.29 | 200.02 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 311.77 | 247.89 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 351.70 | 147.71 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 263.13 | 30.14 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 544.35 | 271.42 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 275.26 | 268.34 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 371.52 | 265.08 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 357.82 | 191.80 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 287.21 | 144.68 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 263.91 | 97.35 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 284.31 | 54.85 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.14 | 30.29 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.01 | 42.51 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 426.01 | 81.91 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 544.82 | 142.72 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 327.17 | 197.07 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 312.17 | 245.19 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 352.10 | 146.14 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 263.91 | 30.29 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 544.82 | 268.34 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 275.77 | 265.74 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 372.13 | 262.73 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 358.52 | 189.56 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 288.24 | 142.42 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 265.28 | 95.24 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 284.73 | 54.01 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.52 | 29.55 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.34 | 41.75 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 426.34 | 80.96 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 545.59 | 141.05 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 328.27 | 194.28 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 312.65 | 242.95 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 352.77 | 144.35 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 265.28 | 29.55 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 545.59 | 265.74 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 556.10 | 516.17 | 540.35 | 353.82 | 186.53 | 0.00 | 0.00 |
February | 749.91 | 511.60 | 712.70 | 471.75 | 240.95 | 0.00 | 0.00 |
March | 721.75 | 367.37 | 642.99 | 356.87 | 286.12 | 0.00 | 0.00 |
April | 581.35 | 274.33 | 498.94 | 197.30 | 301.64 | 0.00 | 0.00 |
May | 535.58 | 181.61 | 437.25 | 91.20 | 346.04 | 0.00 | 0.00 |
June | 570.01 | 103.06 | 410.34 | 62.73 | 347.62 | 0.00 | 0.00 |
July | 662.23 | 54.79 | 430.12 | 74.71 | 355.41 | 0.00 | 0.00 |
August | 886.08 | 78.92 | 574.38 | 213.05 | 361.33 | 0.00 | 0.00 |
September | 853.20 | 156.88 | 623.21 | 322.35 | 300.86 | 0.00 | 0.00 |
October | 1094.25 | 274.88 | 853.75 | 535.36 | 318.39 | 0.00 | 0.00 |
November | 661.44 | 376.51 | 592.00 | 355.53 | 236.48 | 0.00 | 0.00 |
December | 629.37 | 473.25 | 585.66 | 415.78 | 169.88 | 0.00 | 0.00 |
Annual Sum or Average | 708.56 | 279.47 | 574.49 | 286.60 | 287.89 | 0.00 | 0.00 |
Minimum of Months | 535.58 | 54.79 | 410.34 | 62.73 | 169.88 | 0.00 | 0.00 |
Maximum of Months | 1094.25 | 516.17 | 853.75 | 535.36 | 361.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.12 | 259.44 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 373.88 | 256.87 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 359.96 | 184.01 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 290.19 | 136.90 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 267.86 | 89.98 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 285.04 | 50.84 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.42 | 26.52 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.27 | 38.48 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 426.34 | 77.67 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 546.50 | 136.77 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 330.23 | 188.23 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 313.89 | 237.45 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 353.87 | 139.60 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 267.86 | 26.52 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 546.50 | 259.44 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.28 | 258.70 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 374.12 | 256.05 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 360.26 | 183.11 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 290.70 | 135.88 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 268.73 | 88.85 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 285.31 | 50.51 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.66 | 26.26 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.46 | 38.22 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 426.53 | 77.30 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 546.94 | 135.97 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 330.63 | 187.29 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 314.10 | 236.65 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 354.21 | 138.90 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 268.73 | 26.26 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 546.94 | 258.70 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.94 | 255.34 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 375.05 | 252.50 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 361.22 | 179.81 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 292.00 | 132.77 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 270.74 | 86.08 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 285.87 | 49.63 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.96 | 25.78 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 443.62 | 37.83 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 426.87 | 76.44 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 547.98 | 133.96 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 331.61 | 184.65 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 314.82 | 233.51 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 355.04 | 136.70 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 270.74 | 25.78 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 547.98 | 255.34 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 280.42 | 241.37 | 270.18 | 176.91 | 93.26 | 0.00 | 0.00 |
February | 378.52 | 237.59 | 356.35 | 235.88 | 120.48 | 0.00 | 0.00 |
March | 364.35 | 166.87 | 321.50 | 178.44 | 143.06 | 0.00 | 0.00 |
April | 295.22 | 121.92 | 249.47 | 98.65 | 150.82 | 0.00 | 0.00 |
May | 275.10 | 78.06 | 218.62 | 45.60 | 173.02 | 0.00 | 0.00 |
June | 287.23 | 46.20 | 205.17 | 31.36 | 173.81 | 0.00 | 0.00 |
July | 331.83 | 24.39 | 215.06 | 37.36 | 177.70 | 0.00 | 0.00 |
August | 442.81 | 36.76 | 287.19 | 106.52 | 180.67 | 0.00 | 0.00 |
September | 427.27 | 73.58 | 311.61 | 161.18 | 150.43 | 0.00 | 0.00 |
October | 549.98 | 127.91 | 426.88 | 267.68 | 159.19 | 0.00 | 0.00 |
November | 334.14 | 175.69 | 296.00 | 177.76 | 118.24 | 0.00 | 0.00 |
December | 317.36 | 221.09 | 292.83 | 207.89 | 84.94 | 0.00 | 0.00 |
Annual Sum or Average | 357.07 | 128.67 | 287.25 | 143.30 | 143.94 | 0.00 | 0.00 |
Minimum of Months | 275.10 | 24.39 | 205.17 | 31.36 | 84.94 | 0.00 | 0.00 |
Maximum of Months | 549.98 | 241.37 | 426.88 | 267.68 | 180.67 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148842E+10 | 0.142401E+10 | 0.145025E+10 | 0.949633E+09 | 0.500616E+09 | 0.00 | 0.00 |
February | 0.181670E+10 | 0.126237E+10 | 0.172772E+10 | 0.114361E+10 | 0.584108E+09 | 0.00 | 0.00 |
March | 0.193528E+10 | 0.100204E+10 | 0.172573E+10 | 0.957812E+09 | 0.767921E+09 | 0.00 | 0.00 |
April | 0.150528E+10 | 0.725995E+09 | 0.129591E+10 | 0.512442E+09 | 0.783469E+09 | 0.00 | 0.00 |
May | 0.143195E+10 | 0.496771E+09 | 0.117353E+10 | 0.244780E+09 | 0.928750E+09 | 0.00 | 0.00 |
June | 0.148446E+10 | 0.258840E+09 | 0.106580E+10 | 0.162918E+09 | 0.902878E+09 | 0.00 | 0.00 |
July | 0.178541E+10 | 0.133092E+09 | 0.115441E+10 | 0.200520E+09 | 0.953886E+09 | 0.00 | 0.00 |
August | 0.238413E+10 | 0.198351E+09 | 0.154158E+10 | 0.571798E+09 | 0.969784E+09 | 0.00 | 0.00 |
September | 0.221786E+10 | 0.398160E+09 | 0.161869E+10 | 0.837253E+09 | 0.781438E+09 | 0.00 | 0.00 |
October | 0.293428E+10 | 0.741231E+09 | 0.229139E+10 | 0.143686E+10 | 0.854522E+09 | 0.00 | 0.00 |
November | 0.171014E+10 | 0.100320E+10 | 0.153763E+10 | 0.923418E+09 | 0.614208E+09 | 0.00 | 0.00 |
December | 0.168655E+10 | 0.129429E+10 | 0.157185E+10 | 0.111591E+10 | 0.455942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223805E+11 | 0.893834E+10 | 0.181545E+11 | 0.905696E+10 | 0.909752E+10 | 0.00 | 0.00 |
Minimum of Months | 0.143195E+10 | 0.133092E+09 | 0.106580E+10 | 0.162918E+09 | 0.455942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.293428E+10 | 0.142401E+10 | 0.229139E+10 | 0.143686E+10 | 0.969784E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.735981E+09 | 0.747456E+09 | 0.725124E+09 | 0.474816E+09 | 0.250308E+09 | 0.00 | 0.00 |
February | 0.898378E+09 | 0.664128E+09 | 0.863858E+09 | 0.571804E+09 | 0.292054E+09 | 0.00 | 0.00 |
March | 0.956373E+09 | 0.536923E+09 | 0.862866E+09 | 0.478906E+09 | 0.383961E+09 | 0.00 | 0.00 |
April | 0.740973E+09 | 0.392035E+09 | 0.647955E+09 | 0.256221E+09 | 0.391734E+09 | 0.00 | 0.00 |
May | 0.704781E+09 | 0.263112E+09 | 0.586765E+09 | 0.122390E+09 | 0.464375E+09 | 0.00 | 0.00 |
June | 0.739687E+09 | 0.132771E+09 | 0.532898E+09 | 81458926.08 | 0.451439E+09 | 0.00 | 0.00 |
July | 0.892258E+09 | 68069307.29 | 0.577203E+09 | 0.100260E+09 | 0.476943E+09 | 0.00 | 0.00 |
August | 0.119240E+10 | 99719160.24 | 0.770791E+09 | 0.285899E+09 | 0.484892E+09 | 0.00 | 0.00 |
September | 0.110692E+10 | 0.201919E+09 | 0.809346E+09 | 0.418627E+09 | 0.390719E+09 | 0.00 | 0.00 |
October | 0.145890E+10 | 0.383790E+09 | 0.114569E+10 | 0.718432E+09 | 0.427261E+09 | 0.00 | 0.00 |
November | 0.843912E+09 | 0.533071E+09 | 0.768813E+09 | 0.461709E+09 | 0.307104E+09 | 0.00 | 0.00 |
December | 0.834988E+09 | 0.682543E+09 | 0.785926E+09 | 0.557955E+09 | 0.227971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111056E+11 | 0.470554E+10 | 0.907724E+10 | 0.452848E+10 | 0.454876E+10 | 0.00 | 0.00 |
Minimum of Months | 0.704781E+09 | 68069307.29 | 0.532898E+09 | 81458926.08 | 0.227971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145890E+10 | 0.747456E+09 | 0.114569E+10 | 0.718432E+09 | 0.484892E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.736122E+09 | 0.726982E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.897710E+09 | 0.647797E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.956835E+09 | 0.520610E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.742435E+09 | 0.381118E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.704773E+09 | 0.264648E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.736760E+09 | 0.142492E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.887036E+09 | 80727584.72 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118674E+10 | 0.113236E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110409E+10 | 0.212715E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.145798E+10 | 0.385580E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.845735E+09 | 0.518444E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.835048E+09 | 0.663937E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110913E+11 | 0.465829E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.704773E+09 | 80727584.72 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145798E+10 | 0.726982E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.737250E+09 | 0.718731E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.898793E+09 | 0.641272E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.958375E+09 | 0.513704E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.744451E+09 | 0.375018E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.706861E+09 | 0.260731E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.736924E+09 | 0.142179E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.886938E+09 | 81121326.06 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118657E+10 | 0.113867E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110422E+10 | 0.212309E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.145926E+10 | 0.382265E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.848031E+09 | 0.510800E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.836110E+09 | 0.656725E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111038E+11 | 0.460872E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.706861E+09 | 81121326.06 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145926E+10 | 0.718731E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.738633E+09 | 0.711749E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.900266E+09 | 0.635595E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.960267E+09 | 0.507721E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.747121E+09 | 0.369148E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.710535E+09 | 0.255095E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.738029E+09 | 0.139984E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.887949E+09 | 79155389.06 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118745E+10 | 0.111816E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110508E+10 | 0.209836E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.146132E+10 | 0.377795E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.850883E+09 | 0.503586E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.837390E+09 | 0.650708E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111249E+11 | 0.455219E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.710535E+09 | 79155389.06 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146132E+10 | 0.711749E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148947E+10 | 0.138251E+10 | 0.144727E+10 | 0.947684E+09 | 0.499589E+09 | 0.00 | 0.00 |
February | 0.181418E+10 | 0.123767E+10 | 0.172417E+10 | 0.114126E+10 | 0.582910E+09 | 0.00 | 0.00 |
March | 0.193314E+10 | 0.983961E+09 | 0.172219E+10 | 0.955847E+09 | 0.766346E+09 | 0.00 | 0.00 |
April | 0.150687E+10 | 0.711074E+09 | 0.129325E+10 | 0.511391E+09 | 0.781861E+09 | 0.00 | 0.00 |
May | 0.143449E+10 | 0.486430E+09 | 0.117112E+10 | 0.244278E+09 | 0.926844E+09 | 0.00 | 0.00 |
June | 0.147747E+10 | 0.267136E+09 | 0.106361E+10 | 0.162584E+09 | 0.901026E+09 | 0.00 | 0.00 |
July | 0.177371E+10 | 0.146755E+09 | 0.115204E+10 | 0.200109E+09 | 0.951929E+09 | 0.00 | 0.00 |
August | 0.237327E+10 | 0.211375E+09 | 0.153842E+10 | 0.570625E+09 | 0.967794E+09 | 0.00 | 0.00 |
September | 0.221150E+10 | 0.406621E+09 | 0.161537E+10 | 0.835536E+09 | 0.779835E+09 | 0.00 | 0.00 |
October | 0.293085E+10 | 0.736237E+09 | 0.228669E+10 | 0.143392E+10 | 0.852769E+09 | 0.00 | 0.00 |
November | 0.171444E+10 | 0.975908E+09 | 0.153447E+10 | 0.921523E+09 | 0.612948E+09 | 0.00 | 0.00 |
December | 0.168571E+10 | 0.126754E+10 | 0.156863E+10 | 0.111362E+10 | 0.455007E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223451E+11 | 0.881322E+10 | 0.181172E+11 | 0.903837E+10 | 0.907886E+10 | 0.00 | 0.00 |
Minimum of Months | 0.143449E+10 | 0.146755E+09 | 0.106361E+10 | 0.162584E+09 | 0.455007E+09 | 0.00 | 0.00 |
Maximum of Months | 0.293085E+10 | 0.138251E+10 | 0.228669E+10 | 0.143392E+10 | 0.967794E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.742228E+09 | 0.694871E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.904495E+09 | 0.621423E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.964106E+09 | 0.492859E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.752176E+09 | 0.354833E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.717430E+09 | 0.240999E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.738832E+09 | 0.131779E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.887687E+09 | 71039920.57 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118725E+10 | 0.103053E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110508E+10 | 0.201327E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.146374E+10 | 0.366318E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.855948E+09 | 0.487891E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.840725E+09 | 0.635985E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111597E+11 | 0.440238E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.717430E+09 | 71039920.57 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146374E+10 | 0.694871E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.742667E+09 | 0.692893E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.905078E+09 | 0.619439E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.964918E+09 | 0.490440E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.753483E+09 | 0.352202E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.719769E+09 | 0.237979E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.739514E+09 | 0.130919E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.888310E+09 | 70339696.31 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118777E+10 | 0.102364E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110557E+10 | 0.200372E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.146493E+10 | 0.364175E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.856991E+09 | 0.485462E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.841278E+09 | 0.633837E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111703E+11 | 0.438042E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.719769E+09 | 70339696.31 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146493E+10 | 0.692893E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.744424E+09 | 0.683891E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.907313E+09 | 0.610849E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.967494E+09 | 0.481598E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.756864E+09 | 0.344130E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.725159E+09 | 0.230545E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.740963E+09 | 0.128633E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.889109E+09 | 69043604.09 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118818E+10 | 0.101313E+09 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110644E+10 | 0.198132E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.146772E+10 | 0.358802E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.859531E+09 | 0.478601E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.843210E+09 | 0.625441E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111964E+11 | 0.431098E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.725159E+09 | 69043604.09 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146772E+10 | 0.683891E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.751077E+09 | 0.646494E+09 | 0.723637E+09 | 0.473842E+09 | 0.249795E+09 | 0.00 | 0.00 |
February | 0.915715E+09 | 0.574781E+09 | 0.862086E+09 | 0.570631E+09 | 0.291455E+09 | 0.00 | 0.00 |
March | 0.975885E+09 | 0.446951E+09 | 0.861096E+09 | 0.477923E+09 | 0.383173E+09 | 0.00 | 0.00 |
April | 0.765199E+09 | 0.316004E+09 | 0.646626E+09 | 0.255695E+09 | 0.390931E+09 | 0.00 | 0.00 |
May | 0.736825E+09 | 0.209079E+09 | 0.585561E+09 | 0.122139E+09 | 0.463422E+09 | 0.00 | 0.00 |
June | 0.744510E+09 | 0.119745E+09 | 0.531805E+09 | 81291814.91 | 0.450513E+09 | 0.00 | 0.00 |
July | 0.888771E+09 | 65318918.67 | 0.576019E+09 | 0.100054E+09 | 0.475965E+09 | 0.00 | 0.00 |
August | 0.118602E+10 | 98470639.28 | 0.769210E+09 | 0.285313E+09 | 0.483897E+09 | 0.00 | 0.00 |
September | 0.110749E+10 | 0.190730E+09 | 0.807685E+09 | 0.417768E+09 | 0.389917E+09 | 0.00 | 0.00 |
October | 0.147306E+10 | 0.342585E+09 | 0.114334E+10 | 0.716958E+09 | 0.426385E+09 | 0.00 | 0.00 |
November | 0.866085E+09 | 0.455384E+09 | 0.767236E+09 | 0.460762E+09 | 0.306474E+09 | 0.00 | 0.00 |
December | 0.850007E+09 | 0.592175E+09 | 0.784314E+09 | 0.556811E+09 | 0.227503E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112606E+11 | 0.405772E+10 | 0.905862E+10 | 0.451919E+10 | 0.453943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.736825E+09 | 65318918.67 | 0.531805E+09 | 81291814.91 | 0.227503E+09 | 0.00 | 0.00 |
Maximum of Months | 0.147306E+10 | 0.646494E+09 | 0.114334E+10 | 0.716958E+09 | 0.483897E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.372720E+09 | -245123490.8 | 0.00 | 0.00 | 744.00 | 0.00 | -127596622.6 | 59.95 | 0.00 | 0.00 |
February | 0.340152E+09 | -224770782.2 | 0.00 | 0.00 | 672.00 | 0.00 | -115381322.5 | 59.95 | 0.00 | 0.00 |
March | 0.373706E+09 | -247345270.7 | 0.00 | 0.00 | 744.00 | 0.00 | -126360577.4 | 59.95 | 0.00 | 0.00 |
April | 0.343567E+09 | -224340968.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119226184.2 | 59.95 | 0.00 | 0.00 |
May | 0.334448E+09 | -216328537.3 | 0.00 | 0.00 | 744.00 | 0.00 | -118119739.9 | 59.95 | 0.00 | 0.00 |
June | 0.308488E+09 | -196573985.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111914178.5 | 59.95 | 0.00 | 0.00 |
July | 0.303788E+09 | -188737487.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115050429.5 | 59.95 | 0.00 | 0.00 |
August | 0.305064E+09 | -190036605.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115026969.9 | 59.95 | 0.00 | 0.00 |
September | 0.299258E+09 | -187405358.5 | 0.00 | 0.00 | 720.00 | 0.00 | -111852242.5 | 59.95 | 0.00 | 0.00 |
October | 0.322029E+09 | -204264099.8 | 0.00 | 0.00 | 744.00 | 0.00 | -117764704.5 | 59.95 | 0.00 | 0.00 |
November | 0.332950E+09 | -212335449.7 | 0.00 | 0.00 | 720.00 | 0.00 | -120614239.0 | 59.95 | 0.00 | 0.00 |
December | 0.362169E+09 | -235233436.9 | 0.00 | 0.00 | 744.00 | 0.00 | -126935910.1 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.399834E+10 | -0.257250E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142584E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.299258E+09 | -247345270.7 | 0.00 | 0.00 | 672.00 | 0.00 | -127596622.6 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.373706E+09 | -187405358.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111852242.5 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.370834E+09 | -245123487.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125710500.9 | 59.95 | 0.00 | 0.00 |
February | 0.338318E+09 | -224770809.9 | 0.00 | 0.00 | 672.00 | 0.00 | -113547650.1 | 59.95 | 0.00 | 0.00 |
March | 0.371171E+09 | -247345264.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123825290.9 | 59.95 | 0.00 | 0.00 |
April | 0.341225E+09 | -224341009.1 | 0.00 | 0.00 | 720.00 | 0.00 | -116884328.8 | 59.95 | 0.00 | 0.00 |
May | 0.333043E+09 | -216328569.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116714073.4 | 59.95 | 0.00 | 0.00 |
June | 0.308216E+09 | -196573978.3 | 0.00 | 0.00 | 720.00 | 0.00 | -111641753.5 | 59.95 | 0.00 | 0.00 |
July | 0.303584E+09 | -188737448.8 | 0.00 | 0.00 | 744.00 | 0.00 | -114846972.0 | 59.95 | 0.00 | 0.00 |
August | 0.304931E+09 | -190036623.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114894009.0 | 59.95 | 0.00 | 0.00 |
September | 0.299037E+09 | -187405323.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111632091.1 | 59.95 | 0.00 | 0.00 |
October | 0.320782E+09 | -204264185.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116518294.4 | 59.95 | 0.00 | 0.00 |
November | 0.330408E+09 | -212335397.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118072983.0 | 59.95 | 0.00 | 0.00 |
December | 0.359975E+09 | -235233458.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124741068.7 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.398152E+10 | -0.257250E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140903E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.299037E+09 | -247345264.3 | 0.00 | 0.00 | 672.00 | 0.00 | -125710500.9 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.371171E+09 | -187405323.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111632091.1 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.343002E+09 | -215556955.9 | 0.00 | 0.00 | 744.00 | 0.00 | -127445307.4 | 59.95 | 0.00 | 0.00 |
February | 0.312811E+09 | -197817134.4 | 0.00 | 0.00 | 672.00 | 0.00 | -114993460.5 | 59.95 | 0.00 | 0.00 |
March | 0.346211E+09 | -220747462.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125463531.6 | 59.95 | 0.00 | 0.00 |
April | 0.315423E+09 | -197310534.1 | 0.00 | 0.00 | 720.00 | 0.00 | -118112834.3 | 59.95 | 0.00 | 0.00 |
May | 0.308566E+09 | -191892216.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116674203.0 | 59.95 | 0.00 | 0.00 |
June | 0.285652E+09 | -175059671.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110592608.0 | 59.95 | 0.00 | 0.00 |
July | 0.278289E+09 | -164990081.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113299405.4 | 59.95 | 0.00 | 0.00 |
August | 0.283050E+09 | -169741868.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113308149.6 | 59.95 | 0.00 | 0.00 |
September | 0.275308E+09 | -164727232.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110581247.9 | 59.95 | 0.00 | 0.00 |
October | 0.296194E+09 | -179655220.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116539193.2 | 59.95 | 0.00 | 0.00 |
November | 0.307090E+09 | -187475107.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119614678.7 | 59.95 | 0.00 | 0.00 |
December | 0.331769E+09 | -205324477.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126444285.2 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.368337E+10 | -0.227030E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141307E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.275308E+09 | -220747462.2 | 0.00 | 0.00 | 672.00 | 0.00 | -127445307.4 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.346211E+09 | -164727232.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110581247.9 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.343416E+09 | -215556810.5 | 0.00 | 0.00 | 744.00 | 0.00 | -127859040.1 | 59.95 | 0.00 | 0.00 |
February | 0.313150E+09 | -197817162.1 | 0.00 | 0.00 | 672.00 | 0.00 | -115332436.6 | 59.95 | 0.00 | 0.00 |
March | 0.346609E+09 | -220747497.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125861886.3 | 59.95 | 0.00 | 0.00 |
April | 0.315836E+09 | -197310514.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118525181.2 | 59.95 | 0.00 | 0.00 |
May | 0.308891E+09 | -191892257.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116998971.5 | 59.95 | 0.00 | 0.00 |
June | 0.285672E+09 | -175059794.3 | 0.00 | 0.00 | 720.00 | 0.00 | -110611753.4 | 59.95 | 0.00 | 0.00 |
July | 0.278258E+09 | -164990085.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113268354.1 | 59.95 | 0.00 | 0.00 |
August | 0.283004E+09 | -169741784.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113262312.6 | 59.95 | 0.00 | 0.00 |
September | 0.275331E+09 | -164727236.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110604103.1 | 59.95 | 0.00 | 0.00 |
October | 0.296444E+09 | -179655171.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116788764.1 | 59.95 | 0.00 | 0.00 |
November | 0.307598E+09 | -187475065.8 | 0.00 | 0.00 | 720.00 | 0.00 | -120123373.6 | 59.95 | 0.00 | 0.00 |
December | 0.332138E+09 | -205324463.2 | 0.00 | 0.00 | 744.00 | 0.00 | -126813256.6 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.368635E+10 | -0.227030E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141605E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.275331E+09 | -220747497.0 | 0.00 | 0.00 | 672.00 | 0.00 | -127859040.1 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.346609E+09 | -164727236.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110604103.1 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333076E+09 | -203732094.1 | 0.00 | 0.00 | 744.00 | 0.00 | -129343477.7 | 59.95 | 0.00 | 0.00 |
February | 0.303700E+09 | -187066742.6 | 0.00 | 0.00 | 672.00 | 0.00 | -116633642.6 | 59.95 | 0.00 | 0.00 |
March | 0.336047E+09 | -208875048.8 | 0.00 | 0.00 | 744.00 | 0.00 | -127171564.6 | 59.95 | 0.00 | 0.00 |
April | 0.306677E+09 | -186716535.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119960491.7 | 59.95 | 0.00 | 0.00 |
May | 0.300038E+09 | -181473967.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118563609.3 | 59.95 | 0.00 | 0.00 |
June | 0.276881E+09 | -165646697.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111234165.6 | 59.95 | 0.00 | 0.00 |
July | 0.269860E+09 | -156038384.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113821336.5 | 59.95 | 0.00 | 0.00 |
August | 0.274504E+09 | -160612020.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113891896.4 | 59.95 | 0.00 | 0.00 |
September | 0.267080E+09 | -155885244.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111195238.3 | 59.95 | 0.00 | 0.00 |
October | 0.287695E+09 | -169803028.3 | 0.00 | 0.00 | 744.00 | 0.00 | -117892128.5 | 59.95 | 0.00 | 0.00 |
November | 0.298793E+09 | -177065504.5 | 0.00 | 0.00 | 720.00 | 0.00 | -121727991.7 | 59.95 | 0.00 | 0.00 |
December | 0.322241E+09 | -194182454.1 | 0.00 | 0.00 | 744.00 | 0.00 | -128058467.6 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.357659E+10 | -0.214710E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142949E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.267080E+09 | -208875048.8 | 0.00 | 0.00 | 672.00 | 0.00 | -129343477.7 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.336047E+09 | -155885244.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111195238.3 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333019E+09 | -203732128.4 | 0.00 | 0.00 | 744.00 | 0.00 | -129286565.9 | 59.95 | 0.00 | 0.00 |
February | 0.303672E+09 | -187066718.0 | 0.00 | 0.00 | 672.00 | 0.00 | -116605161.5 | 59.95 | 0.00 | 0.00 |
March | 0.336080E+09 | -208875025.7 | 0.00 | 0.00 | 744.00 | 0.00 | -127204668.1 | 59.95 | 0.00 | 0.00 |
April | 0.306776E+09 | -186716522.8 | 0.00 | 0.00 | 720.00 | 0.00 | -120059715.2 | 59.95 | 0.00 | 0.00 |
May | 0.300239E+09 | -181473916.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118765307.1 | 59.95 | 0.00 | 0.00 |
June | 0.276973E+09 | -165646752.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111325891.7 | 59.95 | 0.00 | 0.00 |
July | 0.269979E+09 | -156038377.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113940971.8 | 59.95 | 0.00 | 0.00 |
August | 0.274633E+09 | -160611998.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114021170.3 | 59.95 | 0.00 | 0.00 |
September | 0.267173E+09 | -155885184.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111288043.7 | 59.95 | 0.00 | 0.00 |
October | 0.287820E+09 | -169803086.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118017325.3 | 59.95 | 0.00 | 0.00 |
November | 0.298889E+09 | -177065515.9 | 0.00 | 0.00 | 720.00 | 0.00 | -121823120.4 | 59.95 | 0.00 | 0.00 |
December | 0.322233E+09 | -194182457.6 | 0.00 | 0.00 | 744.00 | 0.00 | -128050258.2 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.357749E+10 | -0.214710E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.143039E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.267173E+09 | -208875025.7 | 0.00 | 0.00 | 672.00 | 0.00 | -129286565.9 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.336080E+09 | -155885184.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111288043.7 | 59.95 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333113E+09 | -203732102.3 | 0.00 | 0.00 | 744.00 | 0.00 | -129381126.4 | 59.95 | 0.00 | 0.00 |
February | 0.303773E+09 | -187066691.8 | 0.00 | 0.00 | 672.00 | 0.00 | -116706489.4 | 59.95 | 0.00 | 0.00 |
March | 0.336211E+09 | -208875084.6 | 0.00 | 0.00 | 744.00 | 0.00 | -127335566.3 | 59.95 | 0.00 | 0.00 |
April | 0.306965E+09 | -186716549.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120248577.5 | 59.95 | 0.00 | 0.00 |
May | 0.300516E+09 | -181473953.1 | 0.00 | 0.00 | 744.00 | 0.00 | -119042153.4 | 59.95 | 0.00 | 0.00 |
June | 0.277035E+09 | -165646749.6 | 0.00 | 0.00 | 720.00 | 0.00 | -111387948.9 | 59.95 | 0.00 | 0.00 |
July | 0.270036E+09 | -156038364.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113997401.9 | 59.95 | 0.00 | 0.00 |
August | 0.274684E+09 | -160611943.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114071560.9 | 59.95 | 0.00 | 0.00 |
September | 0.267234E+09 | -155885181.3 | 0.00 | 0.00 | 720.00 | 0.00 | -111349055.7 | 59.95 | 0.00 | 0.00 |
October | 0.287992E+09 | -169803040.9 | 0.00 | 0.00 | 744.00 | 0.00 | -118188826.6 | 59.95 | 0.00 | 0.00 |
November | 0.299051E+09 | -177065510.6 | 0.00 | 0.00 | 720.00 | 0.00 | -121985819.5 | 59.95 | 0.00 | 0.00 |
December | 0.322338E+09 | -194182497.3 | 0.00 | 0.00 | 744.00 | 0.00 | -128155275.7 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.357895E+10 | -0.214710E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.143185E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.267234E+09 | -208875084.6 | 0.00 | 0.00 | 672.00 | 0.00 | -129381126.4 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.336211E+09 | -155885181.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111349055.7 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172880E+11 | 61061.39 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165848E+11 | 61061.39 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.900074E+10 | 61061.39 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.293627E+10 | 61061.39 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6877726.35 | 2587.70 | 04-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39218786.20 | 7952.54 | 29-OCT-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.574511E+10 | 61061.39 | 16-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129782E+11 | 61061.39 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.645791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172880E+11 | 61061.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.554215E+10 | 32063.60 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.531270E+10 | 32063.60 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243937E+10 | 32063.60 | 13-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.580143E+09 | 23563.19 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149426E+10 | 32063.60 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.382988E+10 | 32063.60 | 06-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.554215E+10 | 32063.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.669998E+10 | 32541.51 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.633433E+10 | 32541.51 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328897E+10 | 32541.51 | 13-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.924516E+09 | 32541.51 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1849938.66 | 833.10 | 29-OCT-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209859E+10 | 32541.51 | 23-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.488722E+10 | 32541.51 | 07-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.669998E+10 | 32541.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.696065E+10 | 32389.75 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.654066E+10 | 32389.75 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.349474E+10 | 32389.75 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103277E+10 | 32389.75 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 884901.29 | 734.24 | 01-MAY-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4863885.13 | 3296.30 | 29-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226438E+10 | 32389.75 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.511630E+10 | 32389.75 | 07-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.696065E+10 | 32389.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.734430E+10 | 32385.78 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.687454E+10 | 32385.78 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380844E+10 | 32385.78 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119813E+10 | 32385.78 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4042392.44 | 2478.12 | 01-MAY-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12515299.98 | 3707.74 | 29-OCT-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.249922E+10 | 32385.78 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.545747E+10 | 32385.78 | 07-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.734430E+10 | 32385.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143592E+11 | 57478.80 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133496E+11 | 57478.80 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.777010E+10 | 57478.80 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265960E+10 | 57478.80 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29542962.15 | 13920.92 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45418403.43 | 7816.45 | 31-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.522625E+10 | 57478.80 | 15-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108851E+11 | 57478.80 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.543248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143592E+11 | 57478.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.747530E+10 | 30334.31 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.695676E+10 | 30334.31 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.406091E+10 | 30334.31 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139760E+10 | 30334.31 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19823529.64 | 9792.64 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24704042.56 | 3392.28 | 31-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272784E+10 | 30334.31 | 15-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.565485E+10 | 30334.31 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.747530E+10 | 30334.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.756191E+10 | 30220.32 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.704889E+10 | 30220.32 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415803E+10 | 30220.32 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146083E+10 | 30220.32 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31461884.49 | 13739.79 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31593019.75 | 3649.83 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279819E+10 | 30220.32 | 15-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.574375E+10 | 30220.32 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.756191E+10 | 30220.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.797241E+10 | 30140.90 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.745570E+10 | 30140.90 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.453403E+10 | 30140.90 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168882E+10 | 30140.90 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73879918.88 | 24838.74 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 53523945.40 | 9784.12 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304362E+10 | 30140.90 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.610895E+10 | 30140.90 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.797241E+10 | 30140.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.977235E+10 | 32034.52 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.923279E+10 | 32034.52 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.583707E+10 | 32034.52 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.242588E+10 | 32034.52 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.224400E+09 | 32034.52 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148352E+09 | 28289.63 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.379949E+10 | 32034.52 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.745627E+10 | 32034.52 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.977235E+10 | 32034.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 6706604.22 | 4930335.93 | 2101.61 | 27-MAR-16:10 | 1537.02 | 0.00 |
April | 0.00 | 0.00 | 0.620092E+09 | 0.539910E+09 | 10476.13 | 07-APR-13:00 | 9683.88 | 0.00 |
May | 0.00 | 0.00 | 0.346507E+10 | 0.296035E+10 | 19042.64 | 31-MAY-14:00 | 13448.67 | 0.00 |
June | 0.00 | 0.00 | 0.177722E+11 | 0.118714E+11 | 48864.33 | 25-JUN-07:02 | 29622.04 | 0.00 |
July | 0.00 | 0.00 | 0.314999E+11 | 0.194703E+11 | 49876.07 | 22-JUL-07:02 | 27430.21 | 0.00 |
August | 0.00 | 0.00 | 0.296976E+11 | 0.204312E+11 | 49417.45 | 17-AUG-07:02 | 29004.15 | 0.00 |
September | 0.00 | 0.00 | 0.136661E+11 | 0.976232E+10 | 48857.68 | 14-SEP-07:02 | 30341.11 | 0.00 |
October | 0.00 | 0.00 | 0.379316E+10 | 0.254974E+10 | 38962.94 | 06-OCT-07:03 | 20253.92 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.100521E+12 | 0.675903E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.314999E+11 | 0.204312E+11 | 49876.07 | 30341.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 10301863.41 | 7896035.90 | 1908.42 | 27-MAR-16:10 | 1413.61 | 0.00 |
April | 0.00 | 0.00 | 0.482618E+09 | 0.420888E+09 | 23368.01 | 07-APR-20:01 | 19613.92 | 0.00 |
May | 0.00 | 0.00 | 0.242857E+10 | 0.211529E+10 | 23803.28 | 30-MAY-20:02 | 17075.40 | 0.00 |
June | 0.00 | 0.00 | 0.102601E+11 | 0.714680E+10 | 25028.95 | 30-JUN-20:02 | 13416.18 | 0.00 |
July | 0.00 | 0.00 | 0.162170E+11 | 0.105414E+11 | 25238.47 | 22-JUL-07:02 | 18201.91 | 0.00 |
August | 0.00 | 0.00 | 0.154597E+11 | 0.110753E+11 | 25109.45 | 17-AUG-07:02 | 18562.88 | 0.00 |
September | 0.00 | 0.00 | 0.792585E+10 | 0.588710E+10 | 24976.12 | 14-SEP-07:02 | 19176.78 | 0.00 |
October | 0.00 | 0.00 | 0.253719E+10 | 0.173177E+10 | 24945.40 | 23-OCT-20:10 | 11173.66 | 0.00 |
November | 0.00 | 0.00 | 6918638.78 | 5997754.98 | 2283.04 | 05-NOV-17:30 | 2283.04 | 0.00 |
December | 0.00 | 0.00 | 214622.78 | 214622.78 | 357.70 | 17-DEC-20:20 | 357.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.553285E+11 | 0.389327E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.162170E+11 | 0.110753E+11 | 25238.47 | 19613.92 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 3611750.14 | 2679265.44 | 1223.68 | 27-MAR-16:10 | 904.58 | 0.00 |
April | 0.00 | 0.00 | 0.338959E+09 | 0.295561E+09 | 6074.34 | 08-APR-12:10 | 5182.45 | 0.00 |
May | 0.00 | 0.00 | 0.161369E+10 | 0.141652E+10 | 10743.79 | 30-MAY-06:03 | 7881.16 | 0.00 |
June | 0.00 | 0.00 | 0.780126E+10 | 0.534218E+10 | 26894.47 | 25-JUN-07:02 | 13860.31 | 0.00 |
July | 0.00 | 0.00 | 0.128354E+11 | 0.811425E+10 | 26906.20 | 21-JUL-06:02 | 14207.39 | 0.00 |
August | 0.00 | 0.00 | 0.122506E+11 | 0.863061E+10 | 27171.47 | 06-AUG-07:02 | 13717.64 | 0.00 |
September | 0.00 | 0.00 | 0.581644E+10 | 0.424305E+10 | 26491.30 | 14-SEP-06:02 | 15315.99 | 0.00 |
October | 0.00 | 0.00 | 0.187173E+10 | 0.127947E+10 | 24903.95 | 06-OCT-06:03 | 13218.99 | 0.00 |
November | 0.00 | 0.00 | 588419.76 | 473987.76 | 272.39 | 04-NOV-13:00 | 217.87 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.425323E+11 | 0.293248E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.128354E+11 | 0.863061E+10 | 27171.47 | 15315.99 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2094720.97 | 1552652.89 | 932.19 | 27-MAR-16:10 | 688.31 | 0.00 |
April | 0.00 | 0.00 | 0.316942E+09 | 0.276539E+09 | 5916.53 | 08-APR-12:10 | 5043.33 | 0.00 |
May | 0.00 | 0.00 | 0.157057E+10 | 0.137803E+10 | 10424.71 | 30-MAY-06:03 | 7645.80 | 0.00 |
June | 0.00 | 0.00 | 0.776487E+10 | 0.531505E+10 | 26793.84 | 25-JUN-07:02 | 13807.40 | 0.00 |
July | 0.00 | 0.00 | 0.128390E+11 | 0.811816E+10 | 26811.27 | 21-JUL-06:02 | 14180.07 | 0.00 |
August | 0.00 | 0.00 | 0.122703E+11 | 0.864785E+10 | 27073.42 | 06-AUG-07:02 | 13707.25 | 0.00 |
September | 0.00 | 0.00 | 0.580166E+10 | 0.423233E+10 | 26393.75 | 14-SEP-06:02 | 15252.57 | 0.00 |
October | 0.00 | 0.00 | 0.181773E+10 | 0.124136E+10 | 24653.48 | 06-OCT-06:03 | 13079.98 | 0.00 |
November | 0.00 | 0.00 | 5894.95 | 4713.83 | 9.82 | 04-NOV-13:00 | 7.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.423832E+11 | 0.292109E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.128390E+11 | 0.864785E+10 | 27073.42 | 15252.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 946158.44 | 699117.50 | 618.94 | 27-MAR-16:10 | 456.10 | 0.00 |
April | 0.00 | 0.00 | 0.279184E+09 | 0.243978E+09 | 5583.81 | 08-APR-12:10 | 4745.77 | 0.00 |
May | 0.00 | 0.00 | 0.146139E+10 | 0.127926E+10 | 9740.72 | 31-MAY-14:00 | 6961.92 | 0.00 |
June | 0.00 | 0.00 | 0.752147E+10 | 0.513256E+10 | 26747.36 | 25-JUN-07:02 | 13615.26 | 0.00 |
July | 0.00 | 0.00 | 0.125985E+11 | 0.793538E+10 | 26767.79 | 21-JUL-06:02 | 13978.16 | 0.00 |
August | 0.00 | 0.00 | 0.120439E+11 | 0.846157E+10 | 27028.82 | 06-AUG-07:02 | 13522.78 | 0.00 |
September | 0.00 | 0.00 | 0.561470E+10 | 0.408451E+10 | 26354.10 | 14-SEP-06:02 | 15050.07 | 0.00 |
October | 0.00 | 0.00 | 0.168780E+10 | 0.115231E+10 | 22078.49 | 06-OCT-06:03 | 11632.54 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.412079E+11 | 0.282903E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125985E+11 | 0.846157E+10 | 27028.82 | 15050.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 712944.66 | 511862.38 | 488.54 | 27-MAR-16:00 | 349.18 | 0.00 |
April | 0.00 | 0.00 | 0.436725E+09 | 0.376423E+09 | 9446.29 | 08-APR-12:00 | 7902.36 | 0.00 |
May | 0.00 | 0.00 | 0.239700E+10 | 0.205285E+10 | 19640.08 | 31-MAY-07:03 | 15899.88 | 0.00 |
June | 0.00 | 0.00 | 0.130577E+11 | 0.868033E+10 | 48431.37 | 25-JUN-08:62 | 24015.33 | 0.00 |
July | 0.00 | 0.00 | 0.223924E+11 | 0.137177E+11 | 48509.00 | 09-JUL-08:62 | 24147.65 | 0.00 |
August | 0.00 | 0.00 | 0.217254E+11 | 0.149148E+11 | 48042.71 | 06-AUG-08:62 | 20091.29 | 0.00 |
September | 0.00 | 0.00 | 0.974259E+10 | 0.690328E+10 | 47010.09 | 14-SEP-07:02 | 28170.39 | 0.00 |
October | 0.00 | 0.00 | 0.277078E+10 | 0.184028E+10 | 37134.73 | 06-OCT-07:03 | 19470.69 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.725233E+11 | 0.484862E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.223924E+11 | 0.149148E+11 | 48509.00 | 28170.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 50584.06 | 36499.44 | 84.10 | 27-MAR-16:10 | 60.68 | 0.00 |
April | 0.00 | 0.00 | 0.211480E+09 | 0.183194E+09 | 4769.08 | 08-APR-12:00 | 4007.20 | 0.00 |
May | 0.00 | 0.00 | 0.119731E+10 | 0.102821E+10 | 9326.36 | 31-MAY-14:10 | 6509.79 | 0.00 |
June | 0.00 | 0.00 | 0.666089E+10 | 0.444611E+10 | 25126.28 | 25-JUN-08:62 | 12417.99 | 0.00 |
July | 0.00 | 0.00 | 0.114840E+11 | 0.706650E+10 | 25170.90 | 09-JUL-08:62 | 12470.04 | 0.00 |
August | 0.00 | 0.00 | 0.111373E+11 | 0.767608E+10 | 24921.49 | 06-AUG-08:62 | 10429.78 | 0.00 |
September | 0.00 | 0.00 | 0.497607E+10 | 0.354115E+10 | 24370.03 | 14-SEP-07:02 | 14656.33 | 0.00 |
October | 0.00 | 0.00 | 0.138969E+10 | 0.927546E+09 | 17179.79 | 06-OCT-07:03 | 8992.61 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.370568E+11 | 0.248688E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114840E+11 | 0.767608E+10 | 25170.90 | 14656.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 42414.51 | 30542.34 | 70.53 | 27-MAR-16:10 | 50.79 | 0.00 |
April | 0.00 | 0.00 | 0.201326E+09 | 0.174251E+09 | 4661.99 | 08-APR-12:00 | 3912.29 | 0.00 |
May | 0.00 | 0.00 | 0.115340E+10 | 0.988220E+09 | 9248.12 | 31-MAY-14:10 | 6444.06 | 0.00 |
June | 0.00 | 0.00 | 0.657395E+10 | 0.438037E+10 | 25031.45 | 25-JUN-08:62 | 12320.07 | 0.00 |
July | 0.00 | 0.00 | 0.113960E+11 | 0.699806E+10 | 25076.82 | 09-JUL-08:62 | 12374.68 | 0.00 |
August | 0.00 | 0.00 | 0.110587E+11 | 0.760900E+10 | 24830.25 | 06-AUG-08:62 | 10378.46 | 0.00 |
September | 0.00 | 0.00 | 0.491661E+10 | 0.349301E+10 | 24283.53 | 14-SEP-07:02 | 14543.38 | 0.00 |
October | 0.00 | 0.00 | 0.133981E+10 | 0.892623E+09 | 16234.42 | 06-OCT-07:03 | 8471.86 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.366399E+11 | 0.245356E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113960E+11 | 0.760900E+10 | 25076.82 | 14543.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 6.04 | 4.33 | 0.01 | 27-MAR-16:20 | 0.01 | 0.00 |
April | 0.00 | 0.00 | 0.177081E+09 | 0.153331E+09 | 4426.29 | 08-APR-12:00 | 3711.79 | 0.00 |
May | 0.00 | 0.00 | 0.105517E+10 | 0.900114E+09 | 9089.62 | 31-MAY-14:10 | 6320.21 | 0.00 |
June | 0.00 | 0.00 | 0.635053E+10 | 0.422153E+10 | 24938.24 | 25-JUN-08:62 | 12114.83 | 0.00 |
July | 0.00 | 0.00 | 0.112413E+11 | 0.688661E+10 | 24987.36 | 09-JUL-08:62 | 12211.86 | 0.00 |
August | 0.00 | 0.00 | 0.109506E+11 | 0.752346E+10 | 24752.50 | 06-AUG-08:62 | 10318.06 | 0.00 |
September | 0.00 | 0.00 | 0.479706E+10 | 0.340292E+10 | 24209.08 | 14-SEP-07:02 | 14346.12 | 0.00 |
October | 0.00 | 0.00 | 0.124050E+10 | 0.826371E+09 | 13229.35 | 06-OCT-07:03 | 6828.30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.358123E+11 | 0.239143E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112413E+11 | 0.752346E+10 | 24987.36 | 14346.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.161700E+09 | 0.140715E+09 | 4645.66 | 08-APR-12:00 | 3930.89 | 0.00 |
May | 0.00 | 0.00 | 0.999726E+09 | 0.855694E+09 | 9178.33 | 31-MAY-14:10 | 6433.66 | 0.00 |
June | 0.00 | 0.00 | 0.620223E+10 | 0.416702E+10 | 26750.60 | 25-JUN-08:62 | 12417.32 | 0.00 |
July | 0.00 | 0.00 | 0.116890E+11 | 0.724412E+10 | 26802.79 | 09-JUL-08:62 | 12926.05 | 0.00 |
August | 0.00 | 0.00 | 0.116206E+11 | 0.807984E+10 | 26496.17 | 06-AUG-08:62 | 10917.87 | 0.00 |
September | 0.00 | 0.00 | 0.490383E+10 | 0.352604E+10 | 26150.00 | 14-SEP-07:02 | 14310.89 | 0.00 |
October | 0.00 | 0.00 | 0.121171E+10 | 0.818426E+09 | 8596.35 | 04-OCT-13:00 | 6331.36 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.367888E+11 | 0.248318E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.116890E+11 | 0.807984E+10 | 26802.79 | 14310.89 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.189900E+10 | 0.42 | 2118.13 | 01-JAN-08:61 | 0.88 |
February | 0.173802E+10 | 0.42 | 2118.13 | 01-FEB-08:61 | 0.88 |
March | 0.173110E+10 | 0.39 | 2118.13 | 01-MAR-08:61 | 0.88 |
April | 0.154960E+10 | 0.37 | 2118.13 | 01-APR-07:01 | 0.88 |
May | 0.153740E+10 | 0.36 | 901.11 | 04-MAY-08:30 | 0.55 |
June | 0.150418E+10 | 0.36 | 2118.13 | 16-JUN-07:03 | 0.86 |
July | 0.158509E+10 | 0.36 | 2118.13 | 03-JUL-07:02 | 0.87 |
August | 0.160579E+10 | 0.37 | 2118.13 | 01-AUG-07:02 | 0.87 |
September | 0.149530E+10 | 0.36 | 2118.13 | 01-SEP-07:02 | 0.87 |
October | 0.153819E+10 | 0.36 | 1660.07 | 06-OCT-07:03 | 0.77 |
November | 0.160510E+10 | 0.38 | 2118.13 | 16-NOV-08:61 | 0.88 |
December | 0.181392E+10 | 0.40 | 2118.13 | 01-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.196027E+11 | 0.38 | |||
Minimum of Months | 0.149530E+10 | 0.36 | 901.11 | 0.55 | |
Maximum of Months | 0.189900E+10 | 0.42 | 2118.13 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.763761E+09 | 0.32 | 1180.70 | 01-JAN-08:61 | 0.91 |
February | 0.697522E+09 | 0.32 | 1180.70 | 01-FEB-08:61 | 0.91 |
March | 0.710795E+09 | 0.31 | 1180.70 | 13-MAR-07:01 | 0.91 |
April | 0.697789E+09 | 0.33 | 992.89 | 03-APR-07:01 | 0.84 |
May | 0.798543E+09 | 0.37 | 540.90 | 30-MAY-07:03 | 0.60 |
June | 0.749585E+09 | 0.38 | 1180.70 | 19-JUN-07:02 | 0.90 |
July | 0.792786E+09 | 0.39 | 1180.70 | 03-JUL-07:02 | 0.90 |
August | 0.801590E+09 | 0.39 | 1180.70 | 01-AUG-07:02 | 0.90 |
September | 0.755860E+09 | 0.37 | 1180.70 | 01-SEP-07:02 | 0.90 |
October | 0.790008E+09 | 0.37 | 1017.75 | 06-OCT-07:03 | 0.84 |
November | 0.686511E+09 | 0.33 | 1180.70 | 22-NOV-08:61 | 0.91 |
December | 0.722294E+09 | 0.30 | 1180.70 | 06-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.896704E+10 | 0.35 | |||
Minimum of Months | 0.686511E+09 | 0.30 | 540.90 | 0.60 | |
Maximum of Months | 0.801590E+09 | 0.39 | 1180.70 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.838143E+09 | 0.34 | 1193.23 | 01-JAN-08:61 | 0.91 |
February | 0.764804E+09 | 0.34 | 1193.23 | 01-FEB-07:02 | 0.91 |
March | 0.776844E+09 | 0.32 | 1193.23 | 13-MAR-06:01 | 0.91 |
April | 0.690459E+09 | 0.30 | 1193.23 | 02-APR-07:01 | 0.91 |
May | 0.697611E+09 | 0.30 | 477.29 | 11-MAY-15:00 | 0.55 |
June | 0.685501E+09 | 0.30 | 1193.23 | 15-JUN-06:03 | 0.89 |
July | 0.708463E+09 | 0.30 | 1193.23 | 02-JUL-07:03 | 0.90 |
August | 0.733171E+09 | 0.31 | 1193.23 | 01-AUG-06:02 | 0.90 |
September | 0.672078E+09 | 0.30 | 1193.23 | 01-SEP-06:02 | 0.89 |
October | 0.690890E+09 | 0.30 | 1172.03 | 06-OCT-06:03 | 0.89 |
November | 0.716289E+09 | 0.31 | 1193.23 | 23-NOV-08:61 | 0.91 |
December | 0.794824E+09 | 0.32 | 1193.23 | 07-DEC-07:02 | 0.91 |
Annual Sum or Average | 0.876908E+10 | 0.31 | |||
Minimum of Months | 0.672078E+09 | 0.30 | 477.29 | 0.55 | |
Maximum of Months | 0.838143E+09 | 0.34 | 1193.23 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.842122E+09 | 0.34 | 1189.74 | 01-JAN-08:61 | 0.91 |
February | 0.767764E+09 | 0.34 | 1189.74 | 01-FEB-07:02 | 0.91 |
March | 0.779442E+09 | 0.32 | 1189.74 | 01-MAR-07:02 | 0.91 |
April | 0.690918E+09 | 0.30 | 1189.74 | 02-APR-07:01 | 0.91 |
May | 0.695588E+09 | 0.30 | 492.08 | 01-MAY-07:40 | 0.56 |
June | 0.683545E+09 | 0.30 | 1189.74 | 15-JUN-06:03 | 0.89 |
July | 0.707033E+09 | 0.30 | 1189.74 | 02-JUL-07:03 | 0.90 |
August | 0.732040E+09 | 0.31 | 1189.74 | 01-AUG-06:02 | 0.90 |
September | 0.670164E+09 | 0.30 | 1189.74 | 01-SEP-06:02 | 0.89 |
October | 0.688926E+09 | 0.30 | 1159.74 | 06-OCT-06:03 | 0.89 |
November | 0.718062E+09 | 0.31 | 1189.74 | 20-NOV-07:02 | 0.91 |
December | 0.798048E+09 | 0.33 | 1189.74 | 07-DEC-07:02 | 0.91 |
Annual Sum or Average | 0.877365E+10 | 0.31 | |||
Minimum of Months | 0.670164E+09 | 0.30 | 492.08 | 0.56 | |
Maximum of Months | 0.842122E+09 | 0.34 | 1189.74 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.847701E+09 | 0.34 | 1185.69 | 01-JAN-08:61 | 0.91 |
February | 0.772501E+09 | 0.34 | 1185.69 | 01-FEB-07:02 | 0.91 |
March | 0.783688E+09 | 0.33 | 1185.69 | 01-MAR-07:02 | 0.91 |
April | 0.692200E+09 | 0.30 | 1185.69 | 02-APR-07:01 | 0.91 |
May | 0.693288E+09 | 0.30 | 528.71 | 01-MAY-07:07 | 0.59 |
June | 0.680704E+09 | 0.30 | 1185.69 | 16-JUN-06:03 | 0.89 |
July | 0.702433E+09 | 0.30 | 1185.69 | 02-JUL-07:03 | 0.90 |
August | 0.726909E+09 | 0.31 | 1185.69 | 01-AUG-06:02 | 0.90 |
September | 0.667561E+09 | 0.30 | 1185.69 | 01-SEP-06:02 | 0.89 |
October | 0.686726E+09 | 0.30 | 1012.69 | 06-OCT-06:03 | 0.83 |
November | 0.720781E+09 | 0.31 | 1185.69 | 20-NOV-07:02 | 0.91 |
December | 0.802838E+09 | 0.33 | 1185.69 | 07-DEC-07:02 | 0.91 |
Annual Sum or Average | 0.877733E+10 | 0.31 | |||
Minimum of Months | 0.667561E+09 | 0.30 | 528.71 | 0.59 | |
Maximum of Months | 0.847701E+09 | 0.34 | 1185.69 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137742E+10 | 0.31 | 2013.39 | 01-JAN-09:01 | 0.88 |
February | 0.125473E+10 | 0.31 | 2013.39 | 01-FEB-08:61 | 0.88 |
March | 0.126213E+10 | 0.30 | 2013.39 | 01-MAR-08:61 | 0.88 |
April | 0.109964E+10 | 0.27 | 2013.39 | 01-APR-07:01 | 0.87 |
May | 0.108785E+10 | 0.27 | 1097.93 | 01-MAY-07:01 | 0.64 |
June | 0.107075E+10 | 0.27 | 2013.39 | 16-JUN-07:03 | 0.86 |
July | 0.111571E+10 | 0.27 | 2013.39 | 02-JUL-08:62 | 0.86 |
August | 0.116009E+10 | 0.28 | 2013.39 | 01-AUG-07:02 | 0.87 |
September | 0.104753E+10 | 0.26 | 2013.39 | 01-SEP-07:02 | 0.87 |
October | 0.107670E+10 | 0.26 | 1569.30 | 06-OCT-07:03 | 0.77 |
November | 0.115358E+10 | 0.28 | 2013.39 | 15-NOV-08:61 | 0.88 |
December | 0.129861E+10 | 0.30 | 2013.39 | 01-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.140047E+11 | 0.28 | |||
Minimum of Months | 0.104753E+10 | 0.26 | 1097.93 | 0.64 | |
Maximum of Months | 0.137742E+10 | 0.31 | 2013.39 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.740956E+09 | 0.32 | 1086.29 | 01-JAN-09:01 | 0.91 |
February | 0.675066E+09 | 0.32 | 1086.29 | 01-FEB-08:61 | 0.91 |
March | 0.680107E+09 | 0.31 | 1086.29 | 01-MAR-08:61 | 0.91 |
April | 0.593162E+09 | 0.28 | 1086.29 | 01-APR-07:01 | 0.90 |
May | 0.587022E+09 | 0.28 | 644.92 | 01-MAY-07:01 | 0.69 |
June | 0.577402E+09 | 0.28 | 1086.29 | 19-JUN-07:02 | 0.89 |
July | 0.600595E+09 | 0.28 | 1086.29 | 02-JUL-08:62 | 0.89 |
August | 0.624254E+09 | 0.29 | 1086.29 | 01-AUG-07:02 | 0.90 |
September | 0.564980E+09 | 0.27 | 1086.29 | 01-SEP-07:02 | 0.90 |
October | 0.580915E+09 | 0.27 | 732.38 | 06-OCT-07:03 | 0.74 |
November | 0.621744E+09 | 0.29 | 1086.29 | 15-NOV-08:61 | 0.91 |
December | 0.698713E+09 | 0.31 | 1086.29 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.754492E+10 | 0.29 | |||
Minimum of Months | 0.564980E+09 | 0.27 | 644.92 | 0.69 | |
Maximum of Months | 0.740956E+09 | 0.32 | 1086.29 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.739650E+09 | 0.32 | 1080.77 | 01-JAN-09:01 | 0.91 |
February | 0.674171E+09 | 0.32 | 1080.77 | 01-FEB-08:61 | 0.91 |
March | 0.679061E+09 | 0.31 | 1080.77 | 01-MAR-08:61 | 0.91 |
April | 0.591615E+09 | 0.28 | 1080.77 | 01-APR-07:01 | 0.90 |
May | 0.584289E+09 | 0.28 | 727.13 | 01-MAY-07:01 | 0.74 |
June | 0.574324E+09 | 0.28 | 1080.77 | 19-JUN-07:02 | 0.89 |
July | 0.597195E+09 | 0.28 | 1080.77 | 02-JUL-08:62 | 0.89 |
August | 0.620776E+09 | 0.29 | 1080.77 | 01-AUG-07:02 | 0.90 |
September | 0.562050E+09 | 0.27 | 1080.77 | 01-SEP-07:02 | 0.90 |
October | 0.578104E+09 | 0.27 | 680.26 | 06-OCT-07:03 | 0.71 |
November | 0.620312E+09 | 0.29 | 1080.77 | 15-NOV-08:61 | 0.91 |
December | 0.697524E+09 | 0.31 | 1080.77 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.751907E+10 | 0.29 | |||
Minimum of Months | 0.562050E+09 | 0.27 | 680.26 | 0.71 | |
Maximum of Months | 0.739650E+09 | 0.32 | 1080.77 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.746399E+09 | 0.32 | 1077.14 | 01-JAN-09:01 | 0.91 |
February | 0.681032E+09 | 0.33 | 1077.14 | 01-FEB-08:61 | 0.91 |
March | 0.685082E+09 | 0.31 | 1077.14 | 01-MAR-08:61 | 0.91 |
April | 0.594603E+09 | 0.29 | 1077.14 | 01-APR-07:01 | 0.90 |
May | 0.583242E+09 | 0.28 | 963.45 | 01-MAY-07:01 | 0.86 |
June | 0.571880E+09 | 0.28 | 1077.14 | 19-JUN-07:02 | 0.89 |
July | 0.594373E+09 | 0.27 | 1077.14 | 03-JUL-07:02 | 0.89 |
August | 0.618309E+09 | 0.29 | 1077.14 | 01-AUG-07:02 | 0.90 |
September | 0.560034E+09 | 0.27 | 1077.14 | 01-SEP-07:02 | 0.90 |
October | 0.576614E+09 | 0.27 | 640.65 | 29-OCT-08:62 | 0.70 |
November | 0.623653E+09 | 0.29 | 1077.14 | 13-NOV-08:61 | 0.91 |
December | 0.703340E+09 | 0.31 | 1077.14 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.753856E+10 | 0.29 | |||
Minimum of Months | 0.560034E+09 | 0.27 | 640.65 | 0.70 | |
Maximum of Months | 0.746399E+09 | 0.33 | 1077.14 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.844210E+09 | 0.34 | 1174.80 | 01-JAN-09:01 | 0.91 |
February | 0.773352E+09 | 0.35 | 1174.80 | 01-FEB-08:61 | 0.91 |
March | 0.769599E+09 | 0.31 | 1174.80 | 01-MAR-08:61 | 0.91 |
April | 0.662397E+09 | 0.29 | 1174.80 | 01-APR-07:01 | 0.91 |
May | 0.639332E+09 | 0.28 | 1174.80 | 01-MAY-07:01 | 0.90 |
June | 0.623026E+09 | 0.28 | 1174.80 | 19-JUN-07:02 | 0.89 |
July | 0.645881E+09 | 0.27 | 1174.80 | 03-JUL-07:02 | 0.89 |
August | 0.673481E+09 | 0.29 | 1174.80 | 01-AUG-07:02 | 0.90 |
September | 0.610386E+09 | 0.27 | 1174.80 | 01-SEP-07:02 | 0.89 |
October | 0.630891E+09 | 0.27 | 1092.40 | 29-OCT-08:62 | 0.88 |
November | 0.692622E+09 | 0.30 | 1174.80 | 13-NOV-08:61 | 0.91 |
December | 0.788310E+09 | 0.32 | 1174.80 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.835349E+10 | 0.30 | |||
Minimum of Months | 0.610386E+09 | 0.27 | 1092.40 | 0.88 | |
Maximum of Months | 0.844210E+09 | 0.35 | 1174.80 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.189900E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.173802E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.173297E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.171554E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.243321E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.585052E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.903376E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.875318E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.484139E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.248136E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.160510E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.181392E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.438980E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160510E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.903376E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.763761E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.697522E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.713633E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.822572E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.140806E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.325168E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.466037E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.454753E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.268535E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.141241E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.688417E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.722354E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.223737E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.688417E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.466037E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.838143E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.764804E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.777853E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.780635E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.111666E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.259647E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.375205E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.369380E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.209721E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115657E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.716455E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.794824E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.190855E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.716455E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.375205E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.842122E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.767764E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.780031E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.775501E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110359E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.258527E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.374963E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.369534E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.209095E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114154E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.718064E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.798048E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.190479E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.718064E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.374963E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.847701E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.772501E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.783956E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.767210E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107412E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.252858E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.369458E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.364101E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.204640E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.110834E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.720781E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.802838E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.187880E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.720781E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.369458E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.137742E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.125473E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.126233E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.121754E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.171135E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.427063E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.640458E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.639929E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.343382E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.176806E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.115358E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.129861E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.315519E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115358E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.640458E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.740956E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.675066E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.680122E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.650482E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.899256E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.221513E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.332214E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.331874E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.178724E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.928340E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.621744E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.698713E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.165379E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.621744E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.332214E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.739650E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.674171E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.679073E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.646287E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.885402E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.219181E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.329872E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.329682E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.177031E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.913460E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.620312E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.697524E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164135E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.620312E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.329872E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.746399E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.681032E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.685082E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.642922E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.859552E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.213774E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.326180E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.326938E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.174016E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.887681E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.623653E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.703340E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.162387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.623653E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.326938E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.844210E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.773352E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.769599E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.706706E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.902127E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.216491E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.343350E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.349293E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.181850E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.934784E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.692622E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.788310E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.173216E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.692622E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.349293E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.189900E+10 | 0.00 | 0.172880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173802E+10 | 0.00 | 0.165848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173110E+10 | 6706604.22 | 0.900074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154960E+10 | 0.620092E+09 | 0.293627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153740E+10 | 0.346507E+10 | 6877726.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150418E+10 | 0.177722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158509E+10 | 0.314999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160579E+10 | 0.296976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149530E+10 | 0.136661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153819E+10 | 0.379316E+10 | 39218786.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160510E+10 | 0.00 | 0.574511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181392E+10 | 0.00 | 0.129782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196027E+11 | 0.100521E+12 | 0.645791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189900E+10 | 0.314999E+11 | 0.172880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.763761E+09 | 0.00 | 0.554215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.697522E+09 | 0.00 | 0.531270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.710795E+09 | 10301863.41 | 0.243937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.697789E+09 | 0.465907E+09 | 0.580143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.798543E+09 | 0.232513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.749585E+09 | 0.101786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.792786E+09 | 0.162170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.801590E+09 | 0.153749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.755860E+09 | 0.780354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.790008E+09 | 0.250524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.686511E+09 | 6918638.78 | 0.149426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.722294E+09 | 214622.78 | 0.382988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.896704E+10 | 0.548878E+11 | 0.191985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.801590E+09 | 0.162170E+11 | 0.554215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.838143E+09 | 0.00 | 0.669998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764804E+09 | 0.00 | 0.633433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.776844E+09 | 3611750.14 | 0.328897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690459E+09 | 0.338959E+09 | 0.924516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.697611E+09 | 0.161369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.685501E+09 | 0.780126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.708463E+09 | 0.128354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.733171E+09 | 0.122506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672078E+09 | 0.581644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.690890E+09 | 0.187173E+10 | 1849938.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.716289E+09 | 588419.76 | 0.209859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.794824E+09 | 0.00 | 0.488722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876908E+10 | 0.425323E+11 | 0.242355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.672078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.838143E+09 | 0.128354E+11 | 0.669998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.842122E+09 | 0.00 | 0.696065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767764E+09 | 0.00 | 0.654066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779442E+09 | 2094720.97 | 0.349474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690918E+09 | 0.316942E+09 | 0.103277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.695588E+09 | 0.157057E+10 | 884901.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.683545E+09 | 0.776487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.707033E+09 | 0.128390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.732040E+09 | 0.122703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.670164E+09 | 0.580166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.688926E+09 | 0.181773E+10 | 4863885.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.718062E+09 | 5894.95 | 0.226438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798048E+09 | 0.00 | 0.511630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.877365E+10 | 0.423832E+11 | 0.254153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.670164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.842122E+09 | 0.128390E+11 | 0.696065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.847701E+09 | 0.00 | 0.734430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772501E+09 | 0.00 | 0.687454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.783688E+09 | 946158.44 | 0.380844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.692200E+09 | 0.279184E+09 | 0.119813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.693288E+09 | 0.146139E+10 | 4042392.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.680704E+09 | 0.752147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.702433E+09 | 0.125985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.726909E+09 | 0.120439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.667561E+09 | 0.561470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.686726E+09 | 0.168780E+10 | 12515299.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720781E+09 | 0.00 | 0.249922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.802838E+09 | 0.00 | 0.545747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.877733E+10 | 0.412079E+11 | 0.271987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.667561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.847701E+09 | 0.125985E+11 | 0.734430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137742E+10 | 0.00 | 0.143592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125473E+10 | 0.00 | 0.133496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126213E+10 | 712944.66 | 0.777010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109964E+10 | 0.436725E+09 | 0.265960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108785E+10 | 0.239700E+10 | 29542962.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107075E+10 | 0.130577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111571E+10 | 0.223924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116009E+10 | 0.217254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104753E+10 | 0.974259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107670E+10 | 0.277078E+10 | 45418403.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115358E+10 | 0.00 | 0.522625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129861E+10 | 0.00 | 0.108851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140047E+11 | 0.725233E+11 | 0.543248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137742E+10 | 0.223924E+11 | 0.143592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.740956E+09 | 0.00 | 0.747530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675066E+09 | 0.00 | 0.695676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.680107E+09 | 50584.06 | 0.406091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.593162E+09 | 0.211480E+09 | 0.139760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587022E+09 | 0.119731E+10 | 19823529.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.577402E+09 | 0.666089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.600595E+09 | 0.114840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.624254E+09 | 0.111373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.564980E+09 | 0.497607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.580915E+09 | 0.138969E+10 | 24704042.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.621744E+09 | 0.00 | 0.272784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.698713E+09 | 0.00 | 0.565485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.754492E+10 | 0.370568E+11 | 0.283178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.564980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.740956E+09 | 0.114840E+11 | 0.747530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.739650E+09 | 0.00 | 0.756191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.674171E+09 | 0.00 | 0.704889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.679061E+09 | 42414.51 | 0.415803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591615E+09 | 0.201326E+09 | 0.146083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.584289E+09 | 0.115340E+10 | 31461884.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.574324E+09 | 0.657395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.597195E+09 | 0.113960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.620776E+09 | 0.110587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.562050E+09 | 0.491661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.578104E+09 | 0.133981E+10 | 31593019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.620312E+09 | 0.00 | 0.279819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.697524E+09 | 0.00 | 0.574375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.751907E+10 | 0.366399E+11 | 0.288347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.562050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.739650E+09 | 0.113960E+11 | 0.756191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.746399E+09 | 0.00 | 0.797241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681032E+09 | 0.00 | 0.745570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685082E+09 | 6.04 | 0.453403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594603E+09 | 0.177081E+09 | 0.168882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.583242E+09 | 0.105517E+10 | 73879918.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.571880E+09 | 0.635053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.594373E+09 | 0.112413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.618309E+09 | 0.109506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.560034E+09 | 0.479706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.576614E+09 | 0.124050E+10 | 53523945.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.623653E+09 | 0.00 | 0.304362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.703340E+09 | 0.00 | 0.610895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.753856E+10 | 0.358123E+11 | 0.309309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.560034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746399E+09 | 0.112413E+11 | 0.797241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.844210E+09 | 0.00 | 0.977235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.773352E+09 | 0.00 | 0.923279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.769599E+09 | 0.00 | 0.583707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662397E+09 | 0.161700E+09 | 0.242588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.639332E+09 | 0.999726E+09 | 0.224400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623026E+09 | 0.620223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.645881E+09 | 0.116890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.673481E+09 | 0.116206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.610386E+09 | 0.490383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.630891E+09 | 0.121171E+10 | 0.148352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692622E+09 | 0.00 | 0.379949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.788310E+09 | 0.00 | 0.745627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835349E+10 | 0.367888E+11 | 0.388966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.610386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.844210E+09 | 0.116890E+11 | 0.977235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.189900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173110E+10 | 0.00 | 0.00 | 0.00 | 1874378.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154960E+10 | 0.00 | 0.00 | 0.00 | 0.165937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153740E+10 | 0.00 | 0.00 | 0.00 | 0.895810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150418E+10 | 0.00 | 0.00 | 0.00 | 0.434634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158509E+10 | 0.00 | 0.00 | 0.00 | 0.744867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160579E+10 | 0.00 | 0.00 | 0.00 | 0.714739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149530E+10 | 0.00 | 0.00 | 0.00 | 0.334609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153819E+10 | 0.00 | 0.00 | 0.00 | 0.943171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196027E+11 | 0.00 | 0.00 | 0.00 | 0.242953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189900E+10 | 0.00 | 0.00 | 0.00 | 0.744867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.763761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.697522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.710795E+09 | 0.00 | 0.00 | 0.00 | 2838061.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.697789E+09 | 0.00 | 0.00 | 0.00 | 0.124783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.798543E+09 | 0.00 | 0.00 | 0.00 | 0.609517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.749585E+09 | 0.00 | 0.00 | 0.00 | 0.250209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.792786E+09 | 0.00 | 0.00 | 0.00 | 0.386758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.801590E+09 | 0.00 | 0.00 | 0.00 | 0.374594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.755860E+09 | 0.00 | 0.00 | 0.00 | 0.192949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.790008E+09 | 0.00 | 0.00 | 0.00 | 0.622406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.686511E+09 | 0.00 | 0.00 | 0.00 | 1906437.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.722294E+09 | 0.00 | 0.00 | 0.00 | 59939.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.896704E+10 | 0.00 | 0.00 | 0.00 | 0.134066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.801590E+09 | 0.00 | 0.00 | 0.00 | 0.386758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.838143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.776844E+09 | 0.00 | 0.00 | 0.00 | 1009607.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690459E+09 | 0.00 | 0.00 | 0.00 | 90176498.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.697611E+09 | 0.00 | 0.00 | 0.00 | 0.419053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.685501E+09 | 0.00 | 0.00 | 0.00 | 0.191097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.708463E+09 | 0.00 | 0.00 | 0.00 | 0.304359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.733171E+09 | 0.00 | 0.00 | 0.00 | 0.296063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672078E+09 | 0.00 | 0.00 | 0.00 | 0.142513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.690890E+09 | 0.00 | 0.00 | 0.00 | 0.465682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.716289E+09 | 0.00 | 0.00 | 0.00 | 165583.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.794824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876908E+10 | 0.00 | 0.00 | 0.00 | 0.103164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.672078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.838143E+09 | 0.00 | 0.00 | 0.00 | 0.304359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.842122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779442E+09 | 0.00 | 0.00 | 0.00 | 588840.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690918E+09 | 0.00 | 0.00 | 0.00 | 84582336.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.695588E+09 | 0.00 | 0.00 | 0.00 | 0.408000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.683545E+09 | 0.00 | 0.00 | 0.00 | 0.190172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.707033E+09 | 0.00 | 0.00 | 0.00 | 0.304260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.732040E+09 | 0.00 | 0.00 | 0.00 | 0.296330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.670164E+09 | 0.00 | 0.00 | 0.00 | 0.142078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.688926E+09 | 0.00 | 0.00 | 0.00 | 0.452619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.718062E+09 | 0.00 | 0.00 | 0.00 | 1669.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.877365E+10 | 0.00 | 0.00 | 0.00 | 0.102742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.670164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.842122E+09 | 0.00 | 0.00 | 0.00 | 0.304260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.847701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.783688E+09 | 0.00 | 0.00 | 0.00 | 267693.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.692200E+09 | 0.00 | 0.00 | 0.00 | 75009904.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.693288E+09 | 0.00 | 0.00 | 0.00 | 0.380828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.680704E+09 | 0.00 | 0.00 | 0.00 | 0.184788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.702433E+09 | 0.00 | 0.00 | 0.00 | 0.299215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.726909E+09 | 0.00 | 0.00 | 0.00 | 0.291410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.667561E+09 | 0.00 | 0.00 | 0.00 | 0.137884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.686726E+09 | 0.00 | 0.00 | 0.00 | 0.421615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.802838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.877733E+10 | 0.00 | 0.00 | 0.00 | 0.100107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.667561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.847701E+09 | 0.00 | 0.00 | 0.00 | 0.299215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126213E+10 | 0.00 | 0.00 | 0.00 | 202880.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109964E+10 | 0.00 | 0.00 | 0.00 | 0.117903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108785E+10 | 0.00 | 0.00 | 0.00 | 0.623498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107075E+10 | 0.00 | 0.00 | 0.00 | 0.319988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111571E+10 | 0.00 | 0.00 | 0.00 | 0.528887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116009E+10 | 0.00 | 0.00 | 0.00 | 0.523919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104753E+10 | 0.00 | 0.00 | 0.00 | 0.238629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107670E+10 | 0.00 | 0.00 | 0.00 | 0.691353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140047E+11 | 0.00 | 0.00 | 0.00 | 0.175472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137742E+10 | 0.00 | 0.00 | 0.00 | 0.528887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.740956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.680107E+09 | 0.00 | 0.00 | 0.00 | 14463.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.593162E+09 | 0.00 | 0.00 | 0.00 | 57319941.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587022E+09 | 0.00 | 0.00 | 0.00 | 0.312234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.577402E+09 | 0.00 | 0.00 | 0.00 | 0.163773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.600595E+09 | 0.00 | 0.00 | 0.00 | 0.272155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.624254E+09 | 0.00 | 0.00 | 0.00 | 0.269449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.564980E+09 | 0.00 | 0.00 | 0.00 | 0.122226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.580915E+09 | 0.00 | 0.00 | 0.00 | 0.347426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.621744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.698713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.754492E+10 | 0.00 | 0.00 | 0.00 | 0.899302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.564980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.740956E+09 | 0.00 | 0.00 | 0.00 | 0.272155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.739650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.674171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.679061E+09 | 0.00 | 0.00 | 0.00 | 12131.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591615E+09 | 0.00 | 0.00 | 0.00 | 54672018.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.584289E+09 | 0.00 | 0.00 | 0.00 | 0.301113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.574324E+09 | 0.00 | 0.00 | 0.00 | 0.161748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.597195E+09 | 0.00 | 0.00 | 0.00 | 0.270152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.620776E+09 | 0.00 | 0.00 | 0.00 | 0.267604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.562050E+09 | 0.00 | 0.00 | 0.00 | 0.120826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.578104E+09 | 0.00 | 0.00 | 0.00 | 0.335356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.620312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.697524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.751907E+10 | 0.00 | 0.00 | 0.00 | 0.889445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.562050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.739650E+09 | 0.00 | 0.00 | 0.00 | 0.270152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.746399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685082E+09 | 0.00 | 0.00 | 0.00 | 1.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594603E+09 | 0.00 | 0.00 | 0.00 | 48318042.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.583242E+09 | 0.00 | 0.00 | 0.00 | 0.276310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.571880E+09 | 0.00 | 0.00 | 0.00 | 0.156586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.594373E+09 | 0.00 | 0.00 | 0.00 | 0.266742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.618309E+09 | 0.00 | 0.00 | 0.00 | 0.265107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.560034E+09 | 0.00 | 0.00 | 0.00 | 0.118013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.576614E+09 | 0.00 | 0.00 | 0.00 | 0.311067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.623653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.703340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.753856E+10 | 0.00 | 0.00 | 0.00 | 0.870018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.560034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746399E+09 | 0.00 | 0.00 | 0.00 | 0.266742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.844210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.773352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.769599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662397E+09 | 0.00 | 0.00 | 0.00 | 44309523.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.639332E+09 | 0.00 | 0.00 | 0.00 | 0.262796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623026E+09 | 0.00 | 0.00 | 0.00 | 0.154189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.645881E+09 | 0.00 | 0.00 | 0.00 | 0.278762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.673481E+09 | 0.00 | 0.00 | 0.00 | 0.281945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.610386E+09 | 0.00 | 0.00 | 0.00 | 0.120811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.630891E+09 | 0.00 | 0.00 | 0.00 | 0.303892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.788310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835349E+10 | 0.00 | 0.00 | 0.00 | 0.896807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.610386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.844210E+09 | 0.00 | 0.00 | 0.00 | 0.281945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.686700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102336E+11 | 0.00 | 0.00 | 0.52 |
February | 0.663960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962607E+10 | 0.00 | 0.00 | 0.53 |
March | 0.905718E+10 | 0.00 | 0.00 | 77770.29 | 0.00 | 0.424236E+10 | 0.100095E+09 | 0.00 | 0.53 |
April | 0.659231E+10 | 27476049.63 | 0.00 | 2361342.84 | 0.00 | 0.107032E+10 | 0.174846E+10 | 0.00 | 0.59 |
May | 0.265860E+10 | 0.309454E+09 | 0.00 | 9866024.73 | 0.00 | 0.00 | 0.482375E+10 | 0.00 | 0.75 |
June | 9509191.86 | 0.386706E+10 | 0.00 | 7966041.48 | 0.00 | 0.00 | 0.231903E+10 | 0.00 | 0.74 |
July | 0.00 | 0.103477E+11 | 0.00 | 104988.83 | 0.00 | 0.00 | 6765654.01 | 0.00 | 0.54 |
August | 820511.84 | 0.843326E+10 | 0.00 | 3107955.81 | 0.00 | 0.00 | 0.329513E+09 | 0.00 | 0.59 |
September | 0.166769E+09 | 0.222174E+10 | 0.00 | 13212870.12 | 0.00 | 0.00 | 0.427600E+10 | 0.00 | 0.83 |
October | 0.330940E+10 | 0.199024E+09 | 0.00 | 11107838.41 | 0.00 | 785061.97 | 0.586390E+10 | 0.00 | 0.77 |
November | 0.890393E+10 | 0.00 | 0.00 | 372589.08 | 0.00 | 0.251873E+10 | 0.449761E+09 | 0.00 | 0.53 |
December | 0.896187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655674E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.531670E+11 | 0.254057E+11 | 0.00 | 48177421.59 | 0.00 | 0.342486E+11 | 0.199173E+11 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.905718E+10 | 0.103477E+11 | 0.00 | 13212870.12 | 0.00 | 0.102336E+11 | 0.586390E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.289879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330964E+10 | 0.00 | 0.00 | 0.38 |
February | 0.285073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307480E+10 | 0.00 | 0.00 | 0.38 |
March | 0.398663E+10 | 0.00 | 0.00 | 134272.79 | 0.00 | 0.951616E+09 | 0.120807E+09 | 0.00 | 0.40 |
April | 0.243058E+10 | 14888822.68 | 0.00 | 2090413.21 | 0.00 | 0.199251E+09 | 0.144411E+10 | 0.00 | 0.53 |
May | 0.534245E+09 | 0.156283E+09 | 0.00 | 6418666.52 | 0.00 | 0.00 | 0.348738E+10 | 0.00 | 0.78 |
June | 0.00 | 0.194500E+10 | 0.00 | 3439119.21 | 0.00 | 0.00 | 0.891964E+09 | 0.00 | 0.63 |
July | 681.80 | 0.470680E+10 | 0.00 | 44694.55 | 0.00 | 0.00 | 426523.94 | 0.00 | 0.44 |
August | 36430.60 | 0.384729E+10 | 0.00 | 963555.41 | 0.00 | 0.00 | 81849951.04 | 0.00 | 0.48 |
September | 26636725.39 | 0.108264E+10 | 0.00 | 6243633.37 | 0.00 | 0.00 | 0.208433E+10 | 0.00 | 0.77 |
October | 0.823553E+09 | 0.120787E+09 | 0.00 | 6954432.68 | 0.00 | 0.00 | 0.371729E+10 | 0.00 | 0.78 |
November | 0.347747E+10 | 0.00 | 0.00 | 823944.34 | 0.00 | 0.571916E+09 | 0.693123E+09 | 0.00 | 0.43 |
December | 0.353230E+10 | 0.00 | 0.00 | 2523.62 | 0.00 | 0.207908E+10 | 1911780.43 | 0.00 | 0.38 |
Annual Sum or Average | 0.205610E+11 | 0.118737E+11 | 0.00 | 27115255.69 | 0.00 | 0.101863E+11 | 0.125232E+11 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.398663E+10 | 0.470680E+10 | 0.00 | 6954432.68 | 0.00 | 0.330964E+10 | 0.371729E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416539E+10 | 0.00 | 0.00 | 0.41 |
February | 0.238346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382390E+10 | 0.00 | 0.00 | 0.41 |
March | 0.361889E+10 | 0.00 | 0.00 | 34640.27 | 0.00 | 0.153485E+10 | 42887370.88 | 0.00 | 0.42 |
April | 0.257400E+10 | 14681545.05 | 0.00 | 959679.82 | 0.00 | 0.309554E+09 | 0.683797E+09 | 0.00 | 0.48 |
May | 0.986412E+09 | 0.149981E+09 | 0.00 | 3366656.44 | 1455775.69 | 0.00 | 0.196424E+10 | 0.00 | 0.64 |
June | 55183133.88 | 0.160391E+10 | 0.00 | 2303407.39 | 67311165.19 | 0.00 | 0.690906E+09 | 0.00 | 0.59 |
July | 233894.96 | 0.388663E+10 | 0.00 | 341120.23 | 0.208496E+09 | 0.00 | 10469188.78 | 0.00 | 0.42 |
August | 6923861.21 | 0.323729E+10 | 0.00 | 1129518.00 | 0.177577E+09 | 0.00 | 0.170426E+09 | 0.00 | 0.49 |
September | 0.169854E+09 | 0.895206E+09 | 0.00 | 4127517.20 | 39670872.39 | 0.00 | 0.147397E+10 | 0.00 | 0.67 |
October | 0.124826E+10 | 0.102308E+09 | 0.00 | 3883412.05 | 436201.57 | 0.00 | 0.213823E+10 | 0.00 | 0.64 |
November | 0.332861E+10 | 0.00 | 0.00 | 254879.62 | 0.00 | 0.957551E+09 | 0.241387E+09 | 0.00 | 0.43 |
December | 0.313938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268933E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.198139E+11 | 0.989001E+10 | 0.00 | 16400831.03 | 0.494947E+09 | 0.134806E+11 | 0.741632E+10 | 0.00 | 0.50 |
Minimum of Months | 233894.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.361889E+10 | 0.388663E+10 | 0.00 | 4127517.20 | 0.208496E+09 | 0.416539E+10 | 0.213823E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441251E+10 | 0.00 | 0.00 | 0.41 |
February | 0.216207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404523E+10 | 0.00 | 0.00 | 0.41 |
March | 0.342980E+10 | 0.00 | 0.00 | 26632.39 | 0.00 | 0.172123E+10 | 34765831.36 | 0.00 | 0.42 |
April | 0.255095E+10 | 14381693.73 | 0.00 | 856248.97 | 0.00 | 0.340515E+09 | 0.634156E+09 | 0.00 | 0.48 |
May | 0.103689E+10 | 0.149582E+09 | 0.00 | 3166564.09 | 1450032.55 | 0.00 | 0.184681E+10 | 0.00 | 0.63 |
June | 59039100.21 | 0.159925E+10 | 0.00 | 2307954.89 | 67099462.30 | 0.00 | 0.691104E+09 | 0.00 | 0.59 |
July | 225295.54 | 0.388724E+10 | 0.00 | 357280.04 | 0.208316E+09 | 0.00 | 10388193.99 | 0.00 | 0.42 |
August | 6804046.94 | 0.323967E+10 | 0.00 | 1137483.50 | 0.177505E+09 | 0.00 | 0.170104E+09 | 0.00 | 0.49 |
September | 0.171405E+09 | 0.894380E+09 | 0.00 | 4091832.28 | 39604484.06 | 0.00 | 0.146095E+10 | 0.00 | 0.67 |
October | 0.129220E+10 | 0.100174E+09 | 0.00 | 3730100.07 | 412484.25 | 338278.49 | 0.205477E+10 | 0.00 | 0.63 |
November | 0.314029E+10 | 0.00 | 0.00 | 197113.28 | 0.00 | 0.114890E+10 | 0.203122E+09 | 0.00 | 0.42 |
December | 0.292467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290340E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.188299E+11 | 0.988468E+10 | 0.00 | 15871209.52 | 0.494387E+09 | 0.145721E+11 | 0.710616E+10 | 0.00 | 0.50 |
Minimum of Months | 225295.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.342980E+10 | 0.388724E+10 | 0.00 | 4091832.28 | 0.208316E+09 | 0.441251E+10 | 0.205477E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476683E+10 | 0.00 | 0.00 | 0.41 |
February | 0.180316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440422E+10 | 0.00 | 0.00 | 0.41 |
March | 0.318433E+10 | 0.00 | 0.00 | 18021.54 | 0.00 | 0.195954E+10 | 28948146.47 | 0.00 | 0.42 |
April | 0.247538E+10 | 13859586.56 | 0.00 | 682302.58 | 0.00 | 0.451156E+09 | 0.538458E+09 | 0.00 | 0.47 |
May | 0.110668E+10 | 0.147623E+09 | 0.00 | 2742408.65 | 1432660.22 | 2195747.31 | 0.164351E+10 | 0.00 | 0.61 |
June | 62193434.99 | 0.156784E+10 | 0.00 | 2176155.87 | 66165553.29 | 0.00 | 0.686230E+09 | 0.00 | 0.59 |
July | 267088.93 | 0.384493E+10 | 0.00 | 309786.46 | 0.206611E+09 | 0.00 | 10590732.93 | 0.00 | 0.42 |
August | 5151047.95 | 0.321248E+10 | 0.00 | 1083852.05 | 0.176636E+09 | 0.00 | 0.171393E+09 | 0.00 | 0.48 |
September | 0.182888E+09 | 0.877786E+09 | 0.00 | 3863790.17 | 39132738.71 | 0.00 | 0.141717E+10 | 0.00 | 0.66 |
October | 0.136750E+10 | 95311944.48 | 0.00 | 3363494.09 | 343546.85 | 335260.34 | 0.190579E+10 | 0.00 | 0.62 |
November | 0.291981E+10 | 0.00 | 0.00 | 116443.13 | 0.00 | 0.139362E+10 | 0.130984E+09 | 0.00 | 0.42 |
December | 0.257573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325173E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.173844E+11 | 0.975983E+10 | 0.00 | 14356254.53 | 0.490321E+09 | 0.162296E+11 | 0.653307E+10 | 0.00 | 0.49 |
Minimum of Months | 267088.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.318433E+10 | 0.384493E+10 | 0.00 | 3863790.17 | 0.206611E+09 | 0.476683E+10 | 0.190579E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103783E+11 | 0.00 | 0.00 | 0.38 |
February | 0.183711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971863E+10 | 0.00 | 0.00 | 0.38 |
March | 0.500973E+10 | 0.00 | 0.00 | 13437.64 | 0.00 | 0.463498E+10 | 29307156.61 | 0.00 | 0.39 |
April | 0.459863E+10 | 16775882.75 | 0.00 | 852013.24 | 44764.27 | 0.109089E+10 | 0.707574E+09 | 0.00 | 0.41 |
May | 0.232542E+10 | 0.252876E+09 | 0.00 | 3725679.16 | 1581991.23 | 3300847.58 | 0.252224E+10 | 0.00 | 0.52 |
June | 33642347.24 | 0.276660E+10 | 0.00 | 3685201.15 | 36897140.23 | 0.00 | 0.133582E+10 | 0.00 | 0.53 |
July | 648291.78 | 0.707732E+10 | 0.00 | 374254.47 | 0.110487E+09 | 0.00 | 9617618.19 | 0.00 | 0.39 |
August | 3811060.34 | 0.605452E+10 | 0.00 | 1548849.78 | 77602824.96 | 0.00 | 0.208653E+09 | 0.00 | 0.43 |
September | 0.236662E+09 | 0.157324E+10 | 0.00 | 6639354.39 | 8383290.79 | 0.00 | 0.258213E+10 | 0.00 | 0.58 |
October | 0.259417E+10 | 0.130788E+09 | 0.00 | 5356903.37 | 0.00 | 1478328.05 | 0.320503E+10 | 0.00 | 0.53 |
November | 0.504503E+10 | 0.00 | 0.00 | 133193.40 | 0.00 | 0.303884E+10 | 0.149584E+09 | 0.00 | 0.38 |
December | 0.361120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731977E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.270060E+11 | 0.178721E+11 | 0.00 | 22328886.61 | 0.234997E+09 | 0.361862E+11 | 0.107499E+11 | 0.00 | 0.44 |
Minimum of Months | 648291.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.504503E+10 | 0.707732E+10 | 0.00 | 6639354.39 | 0.110487E+09 | 0.103783E+11 | 0.320503E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.774366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525770E+10 | 0.00 | 0.00 | 0.38 |
February | 0.784609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498236E+10 | 0.00 | 0.00 | 0.38 |
March | 0.225779E+10 | 0.00 | 0.00 | 4980.27 | 0.00 | 0.255332E+10 | 12170707.45 | 0.00 | 0.39 |
April | 0.223334E+10 | 8362428.19 | 0.00 | 379078.98 | 33602.97 | 0.623541E+09 | 0.324386E+09 | 0.00 | 0.42 |
May | 0.120231E+10 | 0.125618E+09 | 0.00 | 1769302.13 | 777522.10 | 2000060.15 | 0.120274E+10 | 0.00 | 0.52 |
June | 19616792.05 | 0.137478E+10 | 0.00 | 1854769.49 | 18030276.63 | 0.00 | 0.689919E+09 | 0.00 | 0.54 |
July | 343489.33 | 0.352496E+10 | 0.00 | 179276.55 | 54347262.75 | 0.00 | 4924693.43 | 0.00 | 0.39 |
August | 1040138.83 | 0.301687E+10 | 0.00 | 764027.99 | 38344303.17 | 0.00 | 0.109194E+09 | 0.00 | 0.44 |
September | 0.118670E+09 | 0.782348E+09 | 0.00 | 3351618.02 | 4056810.38 | 0.00 | 0.132325E+10 | 0.00 | 0.59 |
October | 0.132129E+10 | 64025696.03 | 0.00 | 2656373.60 | 0.00 | 738132.74 | 0.159661E+10 | 0.00 | 0.54 |
November | 0.237697E+10 | 0.00 | 0.00 | 53851.10 | 0.00 | 0.165308E+10 | 66528524.00 | 0.00 | 0.38 |
December | 0.160883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384464E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.126992E+11 | 0.889697E+10 | 0.00 | 11013278.13 | 0.115590E+09 | 0.189174E+11 | 0.532973E+10 | 0.00 | 0.44 |
Minimum of Months | 343489.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.237697E+10 | 0.352496E+10 | 0.00 | 3351618.02 | 54347262.75 | 0.525770E+10 | 0.159661E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.718686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531341E+10 | 0.00 | 0.00 | 0.38 |
February | 0.647796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511915E+10 | 0.00 | 0.00 | 0.38 |
March | 0.218314E+10 | 0.00 | 0.00 | 3753.76 | 0.00 | 0.262674E+10 | 10394441.46 | 0.00 | 0.39 |
April | 0.220403E+10 | 8252943.84 | 0.00 | 338155.10 | 44907.67 | 0.690224E+09 | 0.272555E+09 | 0.00 | 0.41 |
May | 0.126217E+10 | 0.124867E+09 | 0.00 | 1618908.62 | 783029.48 | 2649725.77 | 0.109496E+10 | 0.00 | 0.51 |
June | 20893476.30 | 0.136374E+10 | 0.00 | 1805776.73 | 17929497.33 | 0.00 | 0.685247E+09 | 0.00 | 0.53 |
July | 350964.83 | 0.351048E+10 | 0.00 | 174373.21 | 54189496.80 | 0.00 | 4929322.00 | 0.00 | 0.39 |
August | 2942283.18 | 0.300892E+10 | 0.00 | 747131.06 | 38294174.06 | 0.00 | 0.107290E+09 | 0.00 | 0.43 |
September | 0.127295E+09 | 0.777344E+09 | 0.00 | 3273680.15 | 4036328.79 | 0.00 | 0.129972E+10 | 0.00 | 0.59 |
October | 0.135733E+10 | 62325991.04 | 0.00 | 2549179.79 | 0.00 | 0.00 | 0.153383E+10 | 0.00 | 0.54 |
November | 0.231669E+10 | 0.00 | 0.00 | 43165.18 | 0.00 | 0.170901E+10 | 60485494.75 | 0.00 | 0.38 |
December | 0.149310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396036E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.123344E+11 | 0.885593E+10 | 0.00 | 10554123.61 | 0.115277E+09 | 0.194216E+11 | 0.506941E+10 | 0.00 | 0.44 |
Minimum of Months | 350964.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.231669E+10 | 0.351048E+10 | 0.00 | 3273680.15 | 54189496.80 | 0.531341E+10 | 0.153383E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.464093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556800E+10 | 0.00 | 0.00 | 0.38 |
February | 0.400182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536689E+10 | 0.00 | 0.00 | 0.38 |
March | 0.181623E+10 | 0.00 | 0.00 | 1046.09 | 0.00 | 0.299140E+10 | 4790460.65 | 0.00 | 0.39 |
April | 0.202632E+10 | 7817102.52 | 0.00 | 280910.94 | 233047.20 | 0.901980E+09 | 0.207458E+09 | 0.00 | 0.41 |
May | 0.135643E+10 | 0.122528E+09 | 0.00 | 1302309.77 | 840340.45 | 10003614.28 | 0.894293E+09 | 0.00 | 0.50 |
June | 33692353.31 | 0.132690E+10 | 0.00 | 1681007.38 | 17767007.84 | 0.00 | 0.668836E+09 | 0.00 | 0.53 |
July | 385655.91 | 0.347741E+10 | 0.00 | 157444.44 | 53893217.70 | 0.00 | 4944008.40 | 0.00 | 0.39 |
August | 2760982.17 | 0.299440E+10 | 0.00 | 711342.89 | 38228209.97 | 0.00 | 0.108049E+09 | 0.00 | 0.44 |
September | 0.140795E+09 | 0.765396E+09 | 0.00 | 3068401.20 | 3989902.41 | 0.00 | 0.125137E+10 | 0.00 | 0.58 |
October | 0.141622E+10 | 58869010.77 | 0.00 | 2294037.20 | 0.00 | 2364524.03 | 0.140801E+10 | 0.00 | 0.53 |
November | 0.204911E+10 | 0.00 | 0.00 | 24921.26 | 0.00 | 0.198245E+10 | 36876871.42 | 0.00 | 0.38 |
December | 0.105059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440298E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.107568E+11 | 0.875331E+10 | 0.00 | 9521421.17 | 0.114952E+09 | 0.212261E+11 | 0.458463E+10 | 0.00 | 0.44 |
Minimum of Months | 385655.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.204911E+10 | 0.347741E+10 | 0.00 | 3068401.20 | 53893217.70 | 0.556800E+10 | 0.140801E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 42614845.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597169E+10 | 0.00 | 0.00 | 0.38 |
February | 52189348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570107E+10 | 0.00 | 0.00 | 0.38 |
March | 0.877733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390469E+10 | 0.00 | 0.00 | 0.39 |
April | 0.136599E+10 | 7602018.03 | 0.00 | 232200.19 | 694412.33 | 0.153932E+10 | 0.180862E+09 | 0.00 | 0.41 |
May | 0.136439E+10 | 0.121977E+09 | 0.00 | 994660.87 | 1348997.25 | 89413925.05 | 0.708318E+09 | 0.00 | 0.50 |
June | 47795833.75 | 0.125032E+10 | 0.00 | 1587612.34 | 18759392.18 | 0.00 | 0.683784E+09 | 0.00 | 0.55 |
July | 328589.23 | 0.345581E+10 | 0.00 | 177389.74 | 53302192.44 | 0.00 | 14662873.71 | 0.00 | 0.39 |
August | 1246894.45 | 0.301540E+10 | 0.00 | 767376.22 | 38220470.61 | 0.00 | 0.122448E+09 | 0.00 | 0.45 |
September | 0.202113E+09 | 0.746362E+09 | 0.00 | 2965105.29 | 3933302.73 | 0.00 | 0.120184E+10 | 0.00 | 0.60 |
October | 0.143168E+10 | 60218918.22 | 0.00 | 2055943.69 | 0.00 | 32295628.43 | 0.129786E+10 | 0.00 | 0.53 |
November | 0.140971E+10 | 0.00 | 0.00 | 13835.29 | 0.00 | 0.259692E+10 | 24464512.33 | 0.00 | 0.38 |
December | 0.236121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520407E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.703191E+10 | 0.865769E+10 | 0.00 | 8794123.65 | 0.116259E+09 | 0.250395E+11 | 0.423424E+10 | 0.00 | 0.44 |
Minimum of Months | 328589.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.143168E+10 | 0.345581E+10 | 0.00 | 2965105.29 | 53302192.44 | 0.597169E+10 | 0.129786E+10 | 0.00 | 0.60 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:33
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.111447E+12 | 0.341282E+11 | 0.00 | 0.818190E+11 | 0.227440E+11 |
February | 0.200327E+12 | 0.320901E+11 | 0.00 | 0.781134E+11 | 0.214227E+11 |
March | 0.365798E+12 | 0.255256E+11 | 0.00 | 0.649983E+11 | 0.121294E+11 |
April | 0.410854E+12 | 0.160957E+11 | 0.00 | 0.438619E+11 | 0.816526E+10 |
May | 0.543700E+12 | 0.898752E+10 | 0.00 | 0.325318E+11 | 0.219288E+11 |
June | 0.541017E+12 | -0.550784E+10 | 0.00 | -0.879451E+10 | 0.112037E+12 |
July | 0.533040E+12 | -0.178876E+11 | 0.00 | -0.479368E+11 | 0.190754E+12 |
August | 0.512368E+12 | -0.146316E+11 | 0.00 | -0.386867E+11 | 0.184026E+12 |
September | 0.346624E+12 | -170307604.7 | 0.00 | 0.923876E+10 | 0.848663E+11 |
October | 0.319283E+12 | 0.115070E+11 | 0.00 | 0.399997E+11 | 0.246452E+11 |
November | 0.139004E+12 | 0.225019E+11 | 0.00 | 0.560946E+11 | 0.793383E+10 |
December | 0.819630E+11 | 0.301384E+11 | 0.00 | 0.741302E+11 | 0.170298E+11 |
Annual Sum or Average | 0.410542E+13 | 0.142777E+12 | 0.00 | 0.385370E+12 | 0.707683E+12 |
Minimum of Months | 0.819630E+11 | -0.178876E+11 | 0.00 | -0.479368E+11 | 0.793383E+10 |
Maximum of Months | 0.543700E+12 | 0.341282E+11 | 0.00 | 0.818190E+11 | 0.190754E+12 |