Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:20:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2524.58 | 1207.75 | 1207.75 |
Net Site Energy | 2524.58 | 1207.75 | 1207.75 |
Total Source Energy | 7995.34 | 3824.94 | 3824.94 |
Net Source Energy | 7995.34 | 3824.94 | 3824.94 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1016.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 619.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 177.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 570.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 12.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2524.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1016.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 619.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 177.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 570.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 12.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1016.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 619.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 177.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 570.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 12.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 381.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 765.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1207.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 381.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 765.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1207.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2524.580 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2524.580 | 100.00 |
Total On-Site and Utility Electric Sources | 2524.580 | 100.00 |
Total Electricity End Uses | 2524.580 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.69 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.69 | 100.00 |
Total Water End Uses | 87.69 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 8.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 440.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL | PSZ-AC_3:3 HP COOLING COIL | PSZ-AC_4:4 HP COOLING COIL | PSZ-AC_5:5 HP COOLING COIL | PSZ-AC_6:6 HP COOLING COIL | PSZ-AC_7:7 HP COOLING COIL | PSZ-AC_8:8 HP COOLING COIL | PSZ-AC_9:9 HP COOLING COIL | PSZ-AC_10:10 HP COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1_SUPPHEATCOIL | PSZ-AC_2:2_SUPPHEATCOIL | PSZ-AC_3:3_SUPPHEATCOIL | PSZ-AC_4:4_SUPPHEATCOIL | PSZ-AC_5:5_SUPPHEATCOIL | PSZ-AC_6:6_SUPPHEATCOIL | PSZ-AC_7:7_SUPPHEATCOIL | PSZ-AC_8:8_SUPPHEATCOIL | PSZ-AC_9:9_SUPPHEATCOIL | PSZ-AC_10:10_SUPPHEATCOIL | PSZ-AC_1:1 HP COOLING COIL | PSZ-AC_2:2 HP COOLING COIL | PSZ-AC_3:3 HP COOLING COIL | PSZ-AC_4:4 HP COOLING COIL | PSZ-AC_5:5 HP COOLING COIL | PSZ-AC_6:6 HP COOLING COIL | PSZ-AC_7:7 HP COOLING COIL | PSZ-AC_8:8 HP COOLING COIL | PSZ-AC_9:9 HP COOLING COIL | PSZ-AC_10:10 HP COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 236.76 | 0.00 | 0.00 | 236.76 | 0.00 |
Gross Window-Wall Ratio [%] | 19.99 | 0.00 | 0.00 | 49.99 | 0.00 |
Above Ground Window-Wall Ratio [%] | 19.99 | 0.00 | 0.00 | 49.99 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 236.76 | 0.00 | 0.00 | 236.76 | 0.00 |
Gross Window-Wall Ratio [%] | 19.99 | 0.00 | 0.00 | 49.99 | 0.00 |
Above Ground Window-Wall Ratio [%] | 19.99 | 0.00 | 0.00 | 49.99 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 39.49 | 39.49 | 21.6022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.75 | 19.75 | 24.7401 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 23.0997 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 23.0997 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 23.0997 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 39.45 | 39.45 | 15.8794 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 16.1458 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 16.1458 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 19.72 | 19.72 | 16.1458 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 19.72 | 19.72 | 16.1458 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 236.76 | 236.76 | 19.4655 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 236.76 | 236.76 | 19.4655 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 21.6022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 24.7401 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 23.0997 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 23.0997 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 23.0997 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 15.8794 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 16.1458 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 16.1458 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 16.1458 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 16.1458 | 6.19 | 4.3000 | |
Total | 2090.32 | 19.4655 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 19.4655 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 19.4655 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-16:10 | - | - | - | - | - | - | - | - | - | - | - | 02-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 151362.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38660.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32901.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 688.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 231672.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 151362.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 38660.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 32901.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 688.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3218.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1960.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 563.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1807.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 39.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7995.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1539.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 938.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 269.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 864.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3824.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1539.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 938.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 269.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 864.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3824.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 3.33 |
SMSTORE1 DIRECT AIR | 1.71 |
SMSTORE2 DIRECT AIR | 1.70 |
SMSTORE3 DIRECT AIR | 1.71 |
SMSTORE4 DIRECT AIR | 1.71 |
LGSTORE2 DIRECT AIR | 3.09 |
SMSTORE5 DIRECT AIR | 1.63 |
SMSTORE6 DIRECT AIR | 1.62 |
SMSTORE7 DIRECT AIR | 1.63 |
SMSTORE8 DIRECT AIR | 1.83 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.33 | 3.33 | 3.33 | 3.33 | 3.33 | 3.33 | 1.00 | 1.00 | 3.33 |
PSZ-AC_2:2 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.00 | 1.00 | 1.71 |
PSZ-AC_3:3 | 1.70 | 1.70 | 1.70 | 1.70 | 1.70 | 1.70 | 1.00 | 1.00 | 1.70 |
PSZ-AC_4:4 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.00 | 1.00 | 1.71 |
PSZ-AC_5:5 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.00 | 1.00 | 1.71 |
PSZ-AC_6:6 | 3.09 | 3.09 | 3.09 | 3.09 | 3.09 | 3.09 | 1.00 | 1.00 | 3.09 |
PSZ-AC_7:7 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.00 | 1.00 | 1.63 |
PSZ-AC_8:8 | 1.62 | 1.62 | 1.62 | 1.62 | 1.62 | 1.62 | 1.00 | 1.000000 | 1.62 |
PSZ-AC_9:9 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.00 | 1.00 | 1.63 |
PSZ-AC_10:10 | 1.83 | 1.83 | 1.83 | 1.83 | 1.83 | 1.83 | 1.00 | 1.00 | 1.83 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.33 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.71 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.70 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.71 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.71 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 3.09 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.63 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.62 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.63 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.83 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 3.33 | 5398.26 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.71 | 2833.76 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.70 | 2833.22 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.71 | 2837.60 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.71 | 2835.19 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 3.09 | 5016.20 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.63 | 2701.43 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.62 | 2691.97 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.63 | 2706.53 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.83 | 3047.75 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.33 | 3.33 | 3.33 | 3.33 | 81282.56 | 54969.62 | 32.22 | 82044.22 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.71 | 1.71 | 1.71 | 1.71 | 41558.05 | 28159.40 | 32.22 | 42028.95 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.70 | 1.70 | 1.70 | 1.70 | 41553.70 | 28156.42 | 32.22 | 42024.50 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.71 | 1.71 | 1.71 | 1.71 | 41605.31 | 28191.51 | 32.22 | 42076.87 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.71 | 1.71 | 1.71 | 1.71 | 41577.17 | 28172.37 | 32.22 | 42048.31 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 3.09 | 3.09 | 3.09 | 3.09 | 76579.54 | 51449.86 | 32.22 | 76790.83 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.63 | 1.63 | 1.63 | 1.63 | 40015.68 | 27043.07 | 32.22 | 40362.79 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.62 | 1.62 | 1.62 | 1.62 | 39904.96 | 26948.36 | 32.22 | 40221.43 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.63 | 1.63 | 1.63 | 1.63 | 40076.39 | 27094.14 | 32.22 | 40439.02 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.83 | 1.83 | 1.83 | 1.83 | 43902.27 | 29753.31 | 32.22 | 44407.92 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 HP COOLING COIL | 3.33 | 1.66 | 2.22 | 81282.56 | 40641.28 | 0.706170 | 0.706170 |
PSZ-AC_2:2 HP COOLING COIL | 1.71 | 0.852517 | 1.14 | 41558.05 | 20779.03 | 0.706690 | 0.706690 |
PSZ-AC_3:3 HP COOLING COIL | 1.70 | 0.852355 | 1.14 | 41553.70 | 20776.85 | 0.706670 | 0.706670 |
PSZ-AC_4:4 HP COOLING COIL | 1.71 | 0.853672 | 1.14 | 41605.31 | 20802.65 | 0.706750 | 0.706750 |
PSZ-AC_5:5 HP COOLING COIL | 1.71 | 0.852945 | 1.14 | 41577.17 | 20788.58 | 0.706710 | 0.706710 |
PSZ-AC_6:6 HP COOLING COIL | 3.09 | 1.55 | 2.06 | 76579.54 | 38289.77 | 0.702760 | 0.702760 |
PSZ-AC_7:7 HP COOLING COIL | 1.63 | 0.812705 | 1.08 | 40015.68 | 20007.84 | 0.704210 | 0.704210 |
PSZ-AC_8:8 HP COOLING COIL | 1.62 | 0.809858 | 1.08 | 39904.96 | 19952.48 | 0.704030 | 0.704030 |
PSZ-AC_9:9 HP COOLING COIL | 1.63 | 0.814240 | 1.09 | 40076.39 | 20038.19 | 0.704300 | 0.704300 |
PSZ-AC_10:10 HP COOLING COIL | 1.83 | 0.916894 | 1.22 | 43902.27 | 21951.13 | 0.712210 | 0.712210 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | Design Size Speed 2 Gross Rated Heating Capacity [W] | Design Size Speed 1 Gross Rated Heating Capacity [W] | Design Size Resistive Defrost Heater Capacity | |
PSZ-AC_1:1 HEATING COIL | 3.33 | 1.66 | 82044.22 | 41022.11 | 0.000000 |
PSZ-AC_2:2 HEATING COIL | 1.71 | 0.852517 | 42028.95 | 21014.47 | 0.000000 |
PSZ-AC_3:3 HEATING COIL | 1.70 | 0.852355 | 42024.50 | 21012.25 | 0.000000 |
PSZ-AC_4:4 HEATING COIL | 1.71 | 0.853672 | 42076.87 | 21038.44 | 0.000000 |
PSZ-AC_5:5 HEATING COIL | 1.71 | 0.852945 | 42048.31 | 21024.16 | 0.000000 |
PSZ-AC_6:6 HEATING COIL | 3.09 | 1.55 | 76790.83 | 38395.42 | 0.000000 |
PSZ-AC_7:7 HEATING COIL | 1.63 | 0.812705 | 40362.79 | 20181.39 | 0.000000 |
PSZ-AC_8:8 HEATING COIL | 1.62 | 0.809858 | 40221.43 | 20110.71 | 0.000000 |
PSZ-AC_9:9 HEATING COIL | 1.63 | 0.814240 | 40439.02 | 20219.51 | 0.000000 |
PSZ-AC_10:10 HEATING COIL | 1.83 | 0.916894 | 44407.92 | 22203.96 | 0.000000 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_SUPPHEATCOIL | 82044.22 |
PSZ-AC_2:2_SUPPHEATCOIL | 42028.95 |
PSZ-AC_3:3_SUPPHEATCOIL | 42024.50 |
PSZ-AC_4:4_SUPPHEATCOIL | 42076.87 |
PSZ-AC_5:5_SUPPHEATCOIL | 42048.31 |
PSZ-AC_6:6_SUPPHEATCOIL | 76790.83 |
PSZ-AC_7:7_SUPPHEATCOIL | 40362.79 |
PSZ-AC_8:8_SUPPHEATCOIL | 40221.43 |
PSZ-AC_9:9_SUPPHEATCOIL | 40439.02 |
PSZ-AC_10:10_SUPPHEATCOIL | 44407.92 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 229.01 | 39.49 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.30 | 19.75 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 110.68 | 39.45 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 55.34 | 19.72 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 173.76 | 19.72 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 21.602 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.902 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 24.740 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.040 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 23.100 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.400 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 23.100 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.400 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 23.100 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.400 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 16.146 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.446 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 16.146 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.446 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 16.146 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.446 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 16.146 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.446 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 5541.183 | 15.905 | 98.509 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5541.183 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2816.997 | 16.172 | 100.162 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2816.997 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 5532.181 | 15.879 | 98.349 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5532.181 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2812.497 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2812.497 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
19 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
20 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
21 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
22 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
23 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
24 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
25 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
26 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
27 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
28 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
29 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 35 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.1892 | 11712.0 | 0.999 | 0.8953 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 0.14 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.25 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.25 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 9.99E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone LGSTORE1 | 1.2500 |
3 | Zone SMSTORE1 | 1.2500 |
4 | Zone SMSTORE2 | 1.2500 |
5 | Zone SMSTORE3 | 1.2500 |
6 | Zone SMSTORE4 | 1.2500 |
7 | Zone LGSTORE2 | 1.2500 |
8 | Zone SMSTORE5 | 1.2500 |
9 | Zone SMSTORE6 | 1.2500 |
10 | Zone SMSTORE7 | 1.2500 |
11 | Zone SMSTORE8 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone LGSTORE1 | 1.1500 |
3 | Zone SMSTORE1 | 1.1500 |
4 | Zone SMSTORE2 | 1.1500 |
5 | Zone SMSTORE3 | 1.1500 |
6 | Zone SMSTORE4 | 1.1500 |
7 | Zone LGSTORE2 | 1.1500 |
8 | Zone SMSTORE5 | 1.1500 |
9 | Zone SMSTORE6 | 1.1500 |
10 | Zone SMSTORE7 | 1.1500 |
11 | Zone SMSTORE8 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 39373.80237 | 45279.87272 | 2.89382 | 3.32789 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 10134.67257 | 12668.34071 | 0.74321 | 0.92901 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 20173.02301 | 23198.97646 | 1.48264 | 1.70503 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 5220.03537 | 6525.04422 | 0.38280 | 0.47850 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 20169.23421 | 23194.61934 | 1.48236 | 1.70471 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 5324.81029 | 6656.01286 | 0.39049 | 0.48811 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 20200.40975 | 23230.47122 | 1.48465 | 1.70734 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 5385.33919 | 6731.67399 | 0.39493 | 0.49366 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 20183.20850 | 23210.68977 | 1.48338 | 1.70589 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 5455.32851 | 6819.16064 | 0.40006 | 0.50007 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 36587.66483 | 42075.81455 | 2.68901 | 3.09237 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 10526.43727 | 13158.04658 | 0.77194 | 0.96492 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 19231.00469 | 22115.65539 | 1.41340 | 1.62541 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 5669.40689 | 7086.75862 | 0.41576 | 0.51970 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 19163.65244 | 22038.20031 | 1.40845 | 1.61972 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 5654.31464 | 7067.89330 | 0.41465 | 0.51831 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 19267.32629 | 22157.42524 | 1.41607 | 1.62848 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 5707.64539 | 7134.55674 | 0.41856 | 0.52320 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 21697.11056 | 24951.67714 | 1.59460 | 1.83379 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 42.39583 | 1.07811E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 6256.37655 | 7820.47068 | 0.45880 | 0.57350 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 54114.95 | 3.32789 | 3.32789 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 16668.11 | 0.92901 | 0.92901 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 27602.80 | 1.70503 | 1.70503 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 8522.13 | 0.47850 | 0.47850 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 27594.01 | 1.70471 | 1.70471 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 8651.18 | 0.48811 | 0.48811 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 27628.19 | 1.70734 | 1.70734 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 8725.73 | 0.49366 | 0.49366 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 27608.52 | 1.70589 | 1.70589 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 8811.94 | 0.50007 | 0.50007 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 50916.54 | 3.09237 | 3.09237 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 17150.62 | 0.96492 | 0.96492 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 26521.50 | 1.62541 | 1.62541 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 9075.61 | 0.51970 | 0.51970 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 26444.76 | 1.61972 | 1.61972 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 9057.02 | 0.51831 | 0.51831 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 26560.50 | 1.62848 | 1.62848 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 9122.71 | 0.52320 | 0.52320 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 29247.75 | 1.83379 | 1.83379 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 9798.58 | 0.57350 | 0.57350 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.32789 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.70503 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.70471 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.70734 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.70589 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.09237 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.62541 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.61972 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.62848 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.83379 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.32789 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.32789 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.32789 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.32789 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.32789 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.32789 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.70503 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.70503 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.70503 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.70503 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.70503 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.70503 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.70471 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.70471 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.70471 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.70471 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.70471 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.70471 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.70734 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.70734 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.70734 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.70734 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.70734 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.70734 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.70589 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.70589 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.70589 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.70589 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.70589 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.70589 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.09237 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.09237 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.09237 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.09237 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.09237 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 3.09237 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.62541 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.62541 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.62541 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.62541 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.62541 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.62541 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.61972 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.61972 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.61972 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.61972 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.61972 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.61972 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.62848 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.62848 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.62848 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.62848 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.62848 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.62848 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.83379 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.83379 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.83379 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.83379 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.83379 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.83379 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.32789 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.70503 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.70471 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.70734 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.70589 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 3.09237 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.62541 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.61972 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.62848 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.83379 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.32789 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.32789 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 5398.25700 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.32789 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.32789 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.32789 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.32789 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.32789 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.66395 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.21859 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 81282.56000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 40641.28000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70617 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70617 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 81282.56000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54969.62468 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 82044.21595 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 3.32789 |
122 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.66395 |
123 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 82044.21595 |
124 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 41022.10797 |
125 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
126 | Coil:Heating:Electric | PSZ-AC_1:1_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 82044.21595 |
127 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.70503 |
128 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
129 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.70503 |
130 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2833.76137 |
131 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.70503 |
132 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.70503 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.70503 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.70503 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.70503 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85252 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13669 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41558.05000 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20779.02500 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70669 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70669 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41558.05000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28159.39613 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 42028.94945 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
147 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.70503 |
148 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85252 |
149 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 42028.94945 |
150 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 21014.47472 |
151 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
152 | Coil:Heating:Electric | PSZ-AC_2:2_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 42028.94945 |
153 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.70471 |
154 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
155 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.70471 |
156 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2833.22225 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.70471 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.70471 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.70471 |
160 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.70471 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.70471 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85235 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13647 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41553.70000 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20776.85000 |
166 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70667 |
167 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70667 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41553.70000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28156.41624 |
170 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
171 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 42024.50184 |
172 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
173 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.70471 |
174 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85235 |
175 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 42024.50184 |
176 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 21012.25092 |
177 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
178 | Coil:Heating:Electric | PSZ-AC_3:3_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 42024.50184 |
179 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.70734 |
180 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
181 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.70734 |
182 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2837.60148 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.70734 |
184 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.70734 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.70734 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.70734 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.70734 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85367 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13823 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41605.31000 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20802.65500 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70675 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70675 |
194 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41605.31000 |
195 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28191.50543 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 42076.87378 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
199 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.70734 |
200 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85367 |
201 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 42076.87378 |
202 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 21038.43689 |
203 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
204 | Coil:Heating:Electric | PSZ-AC_4:4_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 42076.87378 |
205 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.70589 |
206 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
207 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.70589 |
208 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2835.18518 |
209 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.70589 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.70589 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.70589 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.70589 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.70589 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85295 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13726 |
216 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41577.17000 |
217 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20788.58500 |
218 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70671 |
219 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70671 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41577.17000 |
221 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28172.36916 |
222 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 42048.31217 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
225 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.70589 |
226 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85295 |
227 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 42048.31217 |
228 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 21024.15609 |
229 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
230 | Coil:Heating:Electric | PSZ-AC_5:5_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 42048.31217 |
231 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.09237 |
232 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
233 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.09237 |
234 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 5016.20238 |
235 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.09237 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.09237 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.09237 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.09237 |
239 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.09237 |
240 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.54618 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.06158 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 76579.54000 |
243 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 38289.77000 |
244 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70276 |
245 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70276 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 76579.54000 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51449.85765 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 76790.83231 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
251 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 3.09237 |
252 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.54618 |
253 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 76790.83231 |
254 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 38395.41615 |
255 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
256 | Coil:Heating:Electric | PSZ-AC_6:6_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 76790.83231 |
257 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.62541 |
258 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
259 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.62541 |
260 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2701.42647 |
261 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.62541 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.62541 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.62541 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.62541 |
265 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.62541 |
266 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.81270 |
267 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.08361 |
268 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40015.68000 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20007.84000 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70421 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70421 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40015.68000 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27043.06915 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 40362.78977 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
277 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.62541 |
278 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.81270 |
279 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 40362.78977 |
280 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 20181.39489 |
281 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
282 | Coil:Heating:Electric | PSZ-AC_7:7_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 40362.78977 |
283 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.61972 |
284 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
285 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.61972 |
286 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2691.96543 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.61972 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.61972 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.61972 |
290 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.61972 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.61972 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.80986 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.07981 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39904.96000 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19952.48000 |
296 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70403 |
297 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70403 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39904.96000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26948.35781 |
300 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
301 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 40221.42957 |
302 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
303 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.61972 |
304 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.80986 |
305 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 40221.42957 |
306 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 20110.71478 |
307 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
308 | Coil:Heating:Electric | PSZ-AC_8:8_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 40221.42957 |
309 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.62848 |
310 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
311 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.62848 |
312 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2706.52853 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.62848 |
314 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.62848 |
315 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.62848 |
316 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.62848 |
317 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.62848 |
318 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.81424 |
319 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.08565 |
320 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40076.39000 |
321 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20038.19500 |
322 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70430 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70430 |
324 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40076.39000 |
325 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27094.14414 |
326 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
327 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 40439.02111 |
328 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
329 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.62848 |
330 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.81424 |
331 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 40439.02111 |
332 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 20219.51056 |
333 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
334 | Coil:Heating:Electric | PSZ-AC_9:9_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 40439.02111 |
335 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.83379 |
336 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
337 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.83379 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3047.75161 |
339 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.83379 |
340 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.83379 |
341 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.83379 |
342 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.83379 |
343 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.83379 |
344 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.91689 |
345 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22253 |
346 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 43902.27000 |
347 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21951.13500 |
348 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71221 |
349 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71221 |
350 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43902.27000 |
351 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29753.30579 |
352 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.22000 |
353 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 44407.91910 |
354 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
355 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.83379 |
356 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.91689 |
357 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 44407.91910 |
358 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 22203.95955 |
359 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
360 | Coil:Heating:Electric | PSZ-AC_10:10_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 44407.91910 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 HP COOLING COIL | 78658.0 | 10.00 | 10.00 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 HP COOLING COIL | 40213.4 | 10.27 | 10.27 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 HP COOLING COIL | 40209.3 | 10.27 | 10.27 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 HP COOLING COIL | 40258.9 | 10.27 | 10.27 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 HP COOLING COIL | 40231.9 | 10.27 | 10.27 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 HP COOLING COIL | 74140.1 | 10.01 | 10.01 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 HP COOLING COIL | 38733.6 | 10.29 | 10.29 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 HP COOLING COIL | 38627.3 | 10.29 | 10.29 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 HP COOLING COIL | 38791.9 | 10.29 | 10.29 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 HP COOLING COIL | 42456.6 | 10.25 | 10.25 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:MultiSpeed | PSZ-AC_1:1 HEATING COIL | 84717.1 | 46624.5 | 7.56 | 2 |
2 | Coil:Heating:DX:MultiSpeed | PSZ-AC_2:2 HEATING COIL | 43398.4 | 23884.6 | 7.87 | 2 |
3 | Coil:Heating:DX:MultiSpeed | PSZ-AC_3:3 HEATING COIL | 43393.7 | 23882.0 | 7.87 | 2 |
4 | Coil:Heating:DX:MultiSpeed | PSZ-AC_4:4 HEATING COIL | 43448.2 | 23912.1 | 7.87 | 2 |
5 | Coil:Heating:DX:MultiSpeed | PSZ-AC_5:5 HEATING COIL | 43418.5 | 23895.7 | 7.87 | 2 |
6 | Coil:Heating:DX:MultiSpeed | PSZ-AC_6:6 HEATING COIL | 79275.3 | 43621.7 | 7.60 | 2 |
7 | Coil:Heating:DX:MultiSpeed | PSZ-AC_7:7 HEATING COIL | 41668.7 | 22928.4 | 7.90 | 2 |
8 | Coil:Heating:DX:MultiSpeed | PSZ-AC_8:8 HEATING COIL | 41522.7 | 22848.1 | 7.91 | 2 |
9 | Coil:Heating:DX:MultiSpeed | PSZ-AC_9:9 HEATING COIL | 41747.4 | 22971.7 | 7.90 | 2 |
10 | Coil:Heating:DX:MultiSpeed | PSZ-AC_10:10 HEATING COIL | 45879.8 | 25261.5 | 7.90 | 2 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 39.45 | 78.94 | 39.45 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.73 | 39.47 | 19.73 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 39.49 | 78.94 | 39.49 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 19.75 | 39.47 | 19.75 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.92 | 7.92 | 7.92 | 180.00 | 90.00 | 2.13 | 3.72 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.7920288477E-002 | 3.4212207719E-002 | Pass | Pass | 4.9738964874E-002 | 0.1163539236 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 1.5400513811E-002 | 3.3841429755E-002 | Pass | Pass | 4.4949697265E-002 | 0.1114317144 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.5558936498E-002 | 0.1110775478 | Pass | Pass | 6.6841771282E-002 | 0.2208839581 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 4.6690149569E-002 | 0.1102778942 | Pass | Pass | 5.5554465050E-002 | 0.1671423165 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.7698517244E-002 | 0.1096770516 | Pass | Pass | 7.1481711271E-002 | 0.2191999803 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.9749982149E-002 | 0.1005594424 | Pass | Pass | 7.0984004273E-002 | 0.2953164489 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.0225767081E-002 | 0.1020085971 | Pass | Pass | 0.1714488227 | 1.1875851447 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.0401872455E-002 | 0.1014731626 | Pass | Pass | 0.3571558374 | 2.7994302044 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.1466335470E-002 | 0.1020556665 | Pass | Pass | 0.2442550793 | 1.7724347461 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.0598346685E-002 | 0.1153648754 | Pass | Pass | 8.0689227522E-002 | 0.2752383699 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3505.62 | -454.6 | 0.00 | -1102.6 | 4297.05 | 6245.53 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 78.94 | 39.45 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.73 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 78.94 | 39.49 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 19.75 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 6.926 | 0.251 | 0.277 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 6.926 | 0.251 | 0.277 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 6.926 | 0.251 | 0.277 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 6.926 | 0.251 | 0.277 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 6.926 | 0.251 | 0.277 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 6.926 | 0.251 | 0.277 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 6.926 | 0.251 | 0.277 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 6.926 | 0.251 | 0.277 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 6.926 | 0.251 | 0.277 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 6.926 | 0.251 | 0.277 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 6.926 | 0.251 | 0.277 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.22_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 6.926 | 0.251 | 0.277 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_1.22_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 6.926 | 0.251 | 0.277 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 236.76 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 236.76 | 6.926 | 0.251 | 0.277 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 3.975 | 9.815 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 3.975 | 9.815 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 15.9053 | 348.39 | 5541.18 | LightsWired | LTG_SCH_BASE_LPD1 | 97.64 | 168.00 | 97.63 | 0.0000 | Y | 101.55 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 36.32 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 16.1717 | 174.19 | 2817.00 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 97.89 | 168.00 | 97.87 | 0.0000 | Y | 51.75 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 27.31 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 41.16 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 41.16 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 41.16 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 15.8794 | 348.39 | 5532.18 | LightsWired | LTG_SCH_BASE_LPD2 | 72.07 | 168.00 | 71.48 | 0.0000 | Y | 74.23 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.83 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.83 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.83 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 16.1458 | 174.19 | 2812.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.83 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 9.7327 | 4180.64 | 40689.09 | 619.14 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 11300.38 | AstronomicalClock | - | 83.85 | 83.85 | 177.87 | |
Exterior Lighting Total | 11300.38 | 177.87 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 81282.56 | 57399.31 | 23883.25 | 0.71 | 3.10 | |||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41558.05 | 29368.66 | 12189.39 | 0.71 | 3.20 | |||
PSZ-AC_3:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41553.70 | 29364.75 | 12188.95 | 0.71 | 3.20 | |||
PSZ-AC_4:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41605.31 | 29404.55 | 12200.76 | 0.71 | 3.20 | |||
PSZ-AC_5:5 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41577.17 | 29383.00 | 12194.17 | 0.71 | 3.20 | |||
PSZ-AC_6:6 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 76579.54 | 53817.04 | 22762.50 | 0.70 | 3.10 | |||
PSZ-AC_7:7 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40015.68 | 28179.44 | 11836.24 | 0.70 | 3.20 | |||
PSZ-AC_8:8 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39904.96 | 28094.29 | 11810.67 | 0.70 | 3.20 | |||
PSZ-AC_9:9 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40076.39 | 28225.80 | 11850.59 | 0.70 | 3.20 | |||
PSZ-AC_10:10 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43902.27 | 31267.64 | 12634.63 | 0.71 | 3.20 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 HP COOLING COIL | 78658.0 | 10.00 | 10.00 | ||||
PSZ-AC_2:2 HP COOLING COIL | 40213.4 | 10.27 | 10.27 | ||||
PSZ-AC_3:3 HP COOLING COIL | 40209.3 | 10.27 | 10.27 | ||||
PSZ-AC_4:4 HP COOLING COIL | 40258.9 | 10.27 | 10.27 | ||||
PSZ-AC_5:5 HP COOLING COIL | 40231.9 | 10.27 | 10.27 | ||||
PSZ-AC_6:6 HP COOLING COIL | 74140.1 | 10.01 | 10.01 | ||||
PSZ-AC_7:7 HP COOLING COIL | 38733.6 | 10.29 | 10.29 | ||||
PSZ-AC_8:8 HP COOLING COIL | 38627.3 | 10.29 | 10.29 | ||||
PSZ-AC_9:9 HP COOLING COIL | 38791.9 | 10.29 | 10.29 | ||||
PSZ-AC_10:10 HP COOLING COIL | 42456.6 | 10.25 | 10.25 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 84717.1 | 46624.5 | 7.56 | 2 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 43398.4 | 23884.6 | 7.87 | 2 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | 43393.7 | 23882.0 | 7.87 | 2 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | 43448.2 | 23912.1 | 7.87 | 2 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:DX:MultiSpeed | 43418.5 | 23895.7 | 7.87 | 2 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:DX:MultiSpeed | 79275.3 | 43621.7 | 7.60 | 2 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:DX:MultiSpeed | 41668.7 | 22928.4 | 7.90 | 2 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:DX:MultiSpeed | 41522.7 | 22848.1 | 7.91 | 2 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:DX:MultiSpeed | 41747.4 | 22971.7 | 7.90 | 2 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:DX:MultiSpeed | 45879.8 | 25261.5 | 7.90 | 2 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | 82044.22 | 3.40 | |
PSZ-AC_1:1_SUPPHEATCOIL | Coil:Heating:Electric | 82044.22 | 1.00 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | 42028.95 | 3.40 | |
PSZ-AC_2:2_SUPPHEATCOIL | Coil:Heating:Electric | 42028.95 | 1.00 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | 42024.50 | 3.40 | |
PSZ-AC_3:3_SUPPHEATCOIL | Coil:Heating:Electric | 42024.50 | 1.00 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | 42076.87 | 3.40 | |
PSZ-AC_4:4_SUPPHEATCOIL | Coil:Heating:Electric | 42076.87 | 1.00 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:DX:MultiSpeed | 42048.31 | 3.40 | |
PSZ-AC_5:5_SUPPHEATCOIL | Coil:Heating:Electric | 42048.31 | 1.00 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:DX:MultiSpeed | 76790.83 | 3.40 | |
PSZ-AC_6:6_SUPPHEATCOIL | Coil:Heating:Electric | 76790.83 | 1.00 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:DX:MultiSpeed | 40362.79 | 3.40 | |
PSZ-AC_7:7_SUPPHEATCOIL | Coil:Heating:Electric | 40362.79 | 1.00 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:DX:MultiSpeed | 40221.43 | 3.40 | |
PSZ-AC_8:8_SUPPHEATCOIL | Coil:Heating:Electric | 40221.43 | 1.00 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:DX:MultiSpeed | 40439.02 | 3.40 | |
PSZ-AC_9:9_SUPPHEATCOIL | Coil:Heating:Electric | 40439.02 | 1.00 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:DX:MultiSpeed | 44407.92 | 3.40 | |
PSZ-AC_10:10_SUPPHEATCOIL | Coil:Heating:Electric | 44407.92 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 3.33 | 5398.26 | 1622.12 | 1.00 | 1.20 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.71 | 2833.76 | 1662.00 | 1.00 | 1.24 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.70 | 2833.22 | 1662.00 | 1.00 | 1.24 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.71 | 2837.60 | 1662.00 | 1.00 | 1.24 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.71 | 2835.19 | 1662.00 | 1.00 | 1.24 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 3.09 | 5016.20 | 1622.12 | 1.00 | 1.20 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.63 | 2701.43 | 1662.00 | 1.00 | 1.25 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.62 | 2691.97 | 1662.00 | 1.00 | 1.25 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.63 | 2706.53 | 1662.00 | 1.00 | 1.25 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.83 | 3047.75 | 1662.00 | 1.00 | 1.23 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.19 | 11712.00 | 1.00 | 1.00 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 39373.80 | 45279.87 | 129.97 | 2.894 | 3.328 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 23.89 | 23.89 | 0.00774 | 42.80 | 0.01078 | 0.411 | 0.00 |
SMSTORE1 | 20173.02 | 23198.98 | 133.18 | 1.483 | 1.705 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00775 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE2 | 20169.23 | 23194.62 | 133.15 | 1.482 | 1.705 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00775 | 42.64 | 0.01078 | 0.206 | 0.00 |
SMSTORE3 | 20200.41 | 23230.47 | 133.36 | 1.485 | 1.707 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00775 | 42.64 | 0.01078 | 0.206 | 0.00 |
SMSTORE4 | 20183.21 | 23210.69 | 133.25 | 1.483 | 1.706 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00775 | 42.64 | 0.01078 | 0.206 | 0.00 |
LGSTORE2 | 36587.66 | 42075.81 | 120.77 | 2.689 | 3.092 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00777 | 42.64 | 0.01078 | 0.411 | 0.00 |
SMSTORE5 | 19231.00 | 22115.66 | 126.96 | 1.413 | 1.625 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00778 | 42.64 | 0.01078 | 0.206 | 0.00 |
SMSTORE6 | 19163.65 | 22038.20 | 126.52 | 1.408 | 1.620 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00778 | 42.64 | 0.01078 | 0.206 | 0.00 |
SMSTORE7 | 19267.33 | 22157.43 | 127.20 | 1.416 | 1.628 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00778 | 42.64 | 0.01078 | 0.206 | 0.00 |
SMSTORE8 | 21697.11 | 24951.68 | 143.24 | 1.595 | 1.834 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 23.89 | 23.89 | 0.00774 | 42.40 | 0.01078 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 10134.67 | 12668.34 | 36.36 | 0.743 | 0.929 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00837 | 12.70 | 0.00915 | 0.411 | 0.00 |
SMSTORE1 | 5220.04 | 6525.04 | 37.46 | 0.383 | 0.479 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00839 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE2 | 5324.81 | 6656.01 | 38.21 | 0.390 | 0.488 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00839 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE3 | 5385.34 | 6731.67 | 38.64 | 0.395 | 0.494 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00839 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE4 | 5455.33 | 6819.16 | 39.15 | 0.400 | 0.500 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00838 | 12.70 | 0.00915 | 0.206 | 0.00 |
LGSTORE2 | 10526.44 | 13158.05 | 37.77 | 0.772 | 0.965 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00836 | 12.70 | 0.00915 | 0.411 | 0.00 |
SMSTORE5 | 5669.41 | 7086.76 | 40.68 | 0.416 | 0.520 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00838 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE6 | 5654.31 | 7067.89 | 40.58 | 0.415 | 0.518 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00838 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE7 | 5707.65 | 7134.56 | 40.96 | 0.419 | 0.523 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00837 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE8 | 6256.38 | 7820.47 | 44.90 | 0.459 | 0.574 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00837 | 12.70 | 0.00915 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.33 | 3.33 | 0.93 | 0.93 | 3.3279 | 3.3279 | 3.3279 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.71 | 1.71 | 0.48 | 0.48 | 1.7050 | 1.7050 | 1.7050 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.70 | 1.70 | 0.49 | 0.49 | 1.7047 | 1.7047 | 1.7047 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.71 | 1.71 | 0.49 | 0.49 | 1.7073 | 1.7073 | 1.7073 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.71 | 1.71 | 0.50 | 0.50 | 1.7059 | 1.7059 | 1.7059 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 3.09 | 3.09 | 0.96 | 0.96 | 3.0924 | 3.0924 | 3.0924 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.63 | 1.63 | 0.52 | 0.52 | 1.6254 | 1.6254 | 1.6254 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.62 | 1.62 | 0.52 | 0.52 | 1.6197 | 1.6197 | 1.6197 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.63 | 1.63 | 0.52 | 0.52 | 1.6285 | 1.6285 | 1.6285 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.83 | 1.83 | 0.57 | 0.57 | 1.8338 | 1.8338 | 1.8338 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 81282.560 | 57399.305 | 3.327890 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 40641.28 | 35049.90 | 2.218593 | 26.22 | 16.84 | 0.00811438 | 11.46 | 9.96 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 18.5468 | 23.89 | 0.00773803 | 41.9736 | 39373.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 82044.216 | 82044.216 | 3.327894 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41022.11 | 24811.63 | 1.663947 | 20.07 | 14.92 | 0.00846750 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 24.7291 | 21.11 | 0.00837071 | 53.6902 | 10134.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_1:1 | 82044.216 | 82044.216 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 82044.22 | 49623.25 | 3.327894 | 20.07 | 14.92 | 0.00846750 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.3645 | 21.11 | 0.00837071 | 53.6902 | 10134.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 41558.050 | 29368.658 | 1.705030 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 20779.03 | 17907.03 | 1.136687 | 26.17 | 16.82 | 0.00811684 | 11.43 | 9.95 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 18.0999 | 23.89 | 0.00775102 | 42.0432 | 20167.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 42028.949 | 42028.949 | 1.705034 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21014.47 | 12685.91 | 0.852517 | 20.10 | 14.95 | 0.00848515 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 24.1332 | 21.11 | 0.00839344 | 53.8339 | 5220.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_2:2 | 42028.949 | 42028.949 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 42028.95 | 25371.81 | 1.705034 | 20.10 | 14.95 | 0.00848515 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.0666 | 21.11 | 0.00839344 | 53.8339 | 5220.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 41553.700 | 29364.753 | 1.704710 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 20776.85 | 17904.34 | 1.136473 | 26.17 | 16.82 | 0.00811727 | 11.43 | 9.95 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 18.1033 | 23.89 | 0.00775135 | 42.0449 | 20159.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 42024.502 | 42024.502 | 1.704709 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21012.25 | 12683.69 | 0.852355 | 20.10 | 14.94 | 0.00848148 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 24.1378 | 21.11 | 0.00838925 | 53.8074 | 5324.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_3:3 | 42024.502 | 42024.502 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 42024.50 | 25367.39 | 1.704709 | 20.10 | 14.94 | 0.00848148 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.0689 | 21.11 | 0.00838925 | 53.8074 | 5324.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 41605.310 | 29404.553 | 1.707340 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 20802.65 | 17929.20 | 1.138227 | 26.17 | 16.82 | 0.00811587 | 11.43 | 9.95 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 18.0754 | 23.89 | 0.00775038 | 42.0397 | 20189.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 42076.874 | 42076.874 | 1.707344 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21038.44 | 12701.66 | 0.853672 | 20.10 | 14.94 | 0.00847929 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 24.1005 | 21.11 | 0.00838693 | 53.7926 | 5385.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_4:4 | 42076.874 | 42076.874 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 42076.87 | 25403.31 | 1.707344 | 20.10 | 14.94 | 0.00847929 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.0503 | 21.11 | 0.00838693 | 53.7926 | 5385.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 41577.170 | 29383.002 | 1.705890 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 20788.58 | 17915.55 | 1.137260 | 26.17 | 16.82 | 0.00811668 | 11.43 | 9.95 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 18.0908 | 23.89 | 0.00775095 | 42.0428 | 20172.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 42048.312 | 42048.312 | 1.705890 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21024.16 | 12691.75 | 0.852945 | 20.10 | 14.94 | 0.00847696 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 24.1211 | 21.11 | 0.00838418 | 53.7753 | 5455.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_5:5 | 42048.312 | 42048.312 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 42048.31 | 25383.49 | 1.705890 | 20.10 | 14.94 | 0.00847696 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.0605 | 21.11 | 0.00838418 | 53.7753 | 5455.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 76579.540 | 53817.038 | 3.092370 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 38289.77 | 32843.55 | 2.061580 | 26.40 | 16.95 | 0.00817015 | 11.46 | 9.96 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 19.9594 | 23.89 | 0.00776890 | 42.1387 | 36556.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 76790.832 | 76790.832 | 3.092367 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38395.42 | 23205.95 | 1.546183 | 19.99 | 14.89 | 0.00846151 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 26.6125 | 21.11 | 0.00835531 | 53.5927 | 10526.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_6:6 | 76790.832 | 76790.832 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 76790.83 | 46411.90 | 3.092367 | 19.99 | 14.89 | 0.00846151 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.3063 | 21.11 | 0.00835531 | 53.5927 | 10526.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 40015.680 | 28179.442 | 1.625410 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 20007.84 | 17159.53 | 1.083607 | 26.28 | 16.90 | 0.00816329 | 11.43 | 9.95 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 18.9865 | 23.89 | 0.00778344 | 42.2169 | 19214.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 40362.790 | 40362.790 | 1.625410 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 20181.39 | 12143.07 | 0.812705 | 20.05 | 14.92 | 0.00847475 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 25.3154 | 21.11 | 0.00837639 | 53.7259 | 5669.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_7:7 | 40362.790 | 40362.790 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 40362.79 | 24286.13 | 1.625410 | 20.05 | 14.92 | 0.00847475 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.6577 | 21.11 | 0.00837639 | 53.7259 | 5669.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 39904.960 | 28094.289 | 1.619720 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 19952.48 | 17106.02 | 1.079813 | 26.29 | 16.90 | 0.00816672 | 11.43 | 9.95 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 19.0532 | 23.89 | 0.00778584 | 42.2297 | 19147.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 40221.430 | 40221.430 | 1.619717 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 20110.71 | 12104.26 | 0.809858 | 20.04 | 14.92 | 0.00847556 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 25.4044 | 21.11 | 0.00837693 | 53.7293 | 5654.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_8:8 | 40221.430 | 40221.430 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 40221.43 | 24208.52 | 1.619717 | 20.04 | 14.92 | 0.00847556 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.7022 | 21.11 | 0.00837693 | 53.7293 | 5654.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 40076.390 | 28225.801 | 1.628480 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 20038.19 | 17188.59 | 1.085653 | 26.28 | 16.90 | 0.00816157 | 11.43 | 9.95 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 18.9507 | 23.89 | 0.00778225 | 42.2105 | 19249.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 40439.021 | 40439.021 | 1.628479 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 20219.51 | 12164.00 | 0.814240 | 20.05 | 14.92 | 0.00847334 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 25.2677 | 21.11 | 0.00837500 | 53.7171 | 5707.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_9:9 | 40439.021 | 40439.021 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 40439.02 | 24327.99 | 1.628479 | 20.05 | 14.92 | 0.00847334 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.6338 | 21.11 | 0.00837500 | 53.7171 | 5707.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 43902.270 | 31267.636 | 1.833790 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 21951.13 | 18979.11 | 1.222527 | 25.97 | 16.72 | 0.00807835 | 11.42 | 9.95 | 0.00700000 | 42.48 | 0.01078126 | 23.77 | 16.8290 | 23.89 | 0.00773661 | 41.9664 | 21667.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 44407.919 | 44407.919 | 1.833788 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 22203.96 | 13563.64 | 0.916894 | 20.17 | 14.95 | 0.00845686 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 22.4387 | 21.11 | 0.00836883 | 53.6779 | 6256.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-AC_10:10 | 44407.919 | 44407.919 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 44407.92 | 27127.28 | 1.833788 | 20.17 | 14.95 | 0.00845686 | 32.22 | 18.76 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 11.2194 | 21.11 | 0.00836883 | 53.6779 | 6256.38 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 81282.560 | 57399.305 | 3.327890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9242 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.327894 | 4.00543676 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | Sensible | 40641.28 | 35049.90 | 1.0000 | 2.67028780 | 2.218593 | 26.22 | 16.84 | 0.00811438 | 47040.0 | 11.46 | 9.96 | 0.00700000 | 29168.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40641.28 | 42.80 | 0.01078182 | 23.86 | 0.41147883 | 18.5468 | 23.89 | 0.00773803 | 23.89 | 0.00773803 | 41.9736 | 39373.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 82044.216 | 82044.216 | 3.327894 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.327894 | 4.00543676 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 41022.11 | 24811.63 | 1.0000 | 2.00271838 | 1.663947 | 20.07 | 14.92 | 0.00846750 | 41660.3 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41022.11 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 24.7291 | 21.11 | 0.00837071 | 21.11 | 0.00837071 | 53.6902 | 10134.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 82044.216 | 82044.216 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.327894 | 4.00543676 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 82044.22 | 49623.25 | 1.0000 | 4.00543676 | 3.327894 | 20.07 | 14.92 | 0.00846750 | 41660.3 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82044.22 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 12.3645 | 21.11 | 0.00837071 | 21.11 | 0.00837071 | 53.6902 | 10134.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41558.050 | 29368.658 | 1.705030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9288 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.705034 | 2.05216983 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 20779.03 | 17907.03 | 1.0000 | 1.36811037 | 1.136687 | 26.17 | 16.82 | 0.00811684 | 46989.5 | 11.43 | 9.95 | 0.00700000 | 29135.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20779.03 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 18.0999 | 23.89 | 0.00775102 | 23.89 | 0.00775102 | 42.0432 | 20167.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 42028.949 | 42028.949 | 1.705034 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.705034 | 2.05216983 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 21014.47 | 12685.91 | 1.0000 | 1.02608492 | 0.852517 | 20.10 | 14.95 | 0.00848515 | 41730.7 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21014.47 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 24.1332 | 21.11 | 0.00839344 | 21.11 | 0.00839344 | 53.8339 | 5220.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 42028.949 | 42028.949 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.705034 | 2.05216983 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 42028.95 | 25371.81 | 1.0000 | 2.05216983 | 1.705034 | 20.10 | 14.95 | 0.00848515 | 41730.7 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42028.95 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.0666 | 21.11 | 0.00839344 | 21.11 | 0.00839344 | 53.8339 | 5220.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41553.700 | 29364.753 | 1.704710 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9296 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.704709 | 2.05177941 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 20776.85 | 17904.34 | 1.0000 | 1.36785360 | 1.136473 | 26.17 | 16.82 | 0.00811727 | 46991.5 | 11.43 | 9.95 | 0.00700000 | 29135.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20776.85 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 18.1033 | 23.89 | 0.00775135 | 23.89 | 0.00775135 | 42.0449 | 20159.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 42024.502 | 42024.502 | 1.704709 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.704709 | 2.05177941 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 21012.25 | 12683.69 | 1.0000 | 1.02588970 | 0.852355 | 20.10 | 14.94 | 0.00848148 | 41721.2 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21012.25 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 24.1378 | 21.11 | 0.00838925 | 21.11 | 0.00838925 | 53.8074 | 5324.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 42024.502 | 42024.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.704709 | 2.05177941 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 42024.50 | 25367.39 | 1.0000 | 2.05177941 | 1.704709 | 20.10 | 14.94 | 0.00848148 | 41721.2 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42024.50 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.0689 | 21.11 | 0.00838925 | 21.11 | 0.00838925 | 53.8074 | 5324.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41605.310 | 29404.553 | 1.707340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9270 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.707344 | 2.05495078 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 20802.65 | 17929.20 | 1.0000 | 1.36996390 | 1.138227 | 26.17 | 16.82 | 0.00811587 | 46984.4 | 11.43 | 9.95 | 0.00700000 | 29135.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20802.65 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 18.0754 | 23.89 | 0.00775038 | 23.89 | 0.00775038 | 42.0397 | 20189.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 42076.874 | 42076.874 | 1.707344 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.707344 | 2.05495078 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 21038.44 | 12701.66 | 1.0000 | 1.02747539 | 0.853672 | 20.10 | 14.94 | 0.00847929 | 41717.2 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21038.44 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 24.1005 | 21.11 | 0.00838693 | 21.11 | 0.00838693 | 53.7926 | 5385.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 42076.874 | 42076.874 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.707344 | 2.05495078 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 42076.87 | 25403.31 | 1.0000 | 2.05495078 | 1.707344 | 20.10 | 14.94 | 0.00847929 | 41717.2 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42076.87 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.0503 | 21.11 | 0.00838693 | 21.11 | 0.00838693 | 53.7926 | 5385.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41577.170 | 29383.002 | 1.705890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9285 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.705890 | 2.05320093 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 20788.58 | 17915.55 | 1.0000 | 1.36880043 | 1.137260 | 26.17 | 16.82 | 0.00811668 | 46988.5 | 11.43 | 9.95 | 0.00700000 | 29135.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20788.58 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 18.0908 | 23.89 | 0.00775095 | 23.89 | 0.00775095 | 42.0428 | 20172.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 42048.312 | 42048.312 | 1.705890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.705890 | 2.05320093 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 21024.16 | 12691.75 | 1.0000 | 1.02660047 | 0.852945 | 20.10 | 14.94 | 0.00847696 | 41710.4 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21024.16 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 24.1211 | 21.11 | 0.00838418 | 21.11 | 0.00838418 | 53.7753 | 5455.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 42048.312 | 42048.312 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.705890 | 2.05320093 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 42048.31 | 25383.49 | 1.0000 | 2.05320093 | 1.705890 | 20.10 | 14.94 | 0.00847696 | 41710.4 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42048.31 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.0605 | 21.11 | 0.00838418 | 21.11 | 0.00838418 | 53.7753 | 5455.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 76579.540 | 53817.038 | 3.092370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0279 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.092367 | 3.72195718 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 38289.77 | 32843.55 | 1.0000 | 2.48130734 | 2.061580 | 26.40 | 16.95 | 0.00817015 | 47366.2 | 11.46 | 9.96 | 0.00700000 | 29168.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38289.77 | 42.80 | 0.01078182 | 23.86 | 0.41147883 | 19.9594 | 23.89 | 0.00776890 | 23.89 | 0.00776890 | 42.1387 | 36556.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 76790.832 | 76790.832 | 3.092367 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.092367 | 3.72195718 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 38395.42 | 23205.95 | 1.0000 | 1.86097859 | 1.546183 | 19.99 | 14.89 | 0.00846151 | 41564.2 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38395.42 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 26.6125 | 21.11 | 0.00835531 | 21.11 | 0.00835531 | 53.5927 | 10526.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76790.832 | 76790.832 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.092367 | 3.72195718 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 76790.83 | 46411.90 | 1.0000 | 3.72195718 | 3.092367 | 19.99 | 14.89 | 0.00846151 | 41564.2 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76790.83 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 13.3063 | 21.11 | 0.00835531 | 21.11 | 0.00835531 | 53.5927 | 10526.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40015.680 | 28179.442 | 1.625410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0151 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.625410 | 1.95633477 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 20007.84 | 17159.53 | 1.0000 | 1.30422355 | 1.083607 | 26.28 | 16.90 | 0.00816329 | 47223.3 | 11.43 | 9.95 | 0.00700000 | 29135.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20007.84 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 18.9865 | 23.89 | 0.00778344 | 23.89 | 0.00778344 | 42.2169 | 19214.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 40362.790 | 40362.790 | 1.625410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.625410 | 1.95633477 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 20181.39 | 12143.07 | 1.0000 | 0.97816739 | 0.812705 | 20.05 | 14.92 | 0.00847475 | 41653.5 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20181.39 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 25.3154 | 21.11 | 0.00837639 | 21.11 | 0.00837639 | 53.7259 | 5669.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40362.790 | 40362.790 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.625410 | 1.95633477 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 40362.79 | 24286.13 | 1.0000 | 1.95633477 | 1.625410 | 20.05 | 14.92 | 0.00847475 | 41653.5 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40362.79 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.6577 | 21.11 | 0.00837639 | 21.11 | 0.00837639 | 53.7259 | 5669.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39904.960 | 28094.289 | 1.619720 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0215 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.619717 | 1.94948322 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 19952.48 | 17106.02 | 1.0000 | 1.29965791 | 1.079813 | 26.29 | 16.90 | 0.00816672 | 47240.7 | 11.43 | 9.95 | 0.00700000 | 29135.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19952.48 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 19.0532 | 23.89 | 0.00778584 | 23.89 | 0.00778584 | 42.2297 | 19147.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 40221.430 | 40221.430 | 1.619717 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.619717 | 1.94948322 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 20110.71 | 12104.26 | 1.0000 | 0.97474161 | 0.809858 | 20.04 | 14.92 | 0.00847556 | 41651.8 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20110.71 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 25.4044 | 21.11 | 0.00837693 | 21.11 | 0.00837693 | 53.7293 | 5654.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40221.430 | 40221.430 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.619717 | 1.94948322 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 40221.43 | 24208.52 | 1.0000 | 1.94948322 | 1.619717 | 20.04 | 14.92 | 0.00847556 | 41651.8 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40221.43 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.7022 | 21.11 | 0.00837693 | 21.11 | 0.00837693 | 53.7293 | 5654.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40076.390 | 28225.801 | 1.628480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0120 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.628479 | 1.96002961 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 20038.19 | 17188.59 | 1.0000 | 1.30668690 | 1.085653 | 26.28 | 16.90 | 0.00816157 | 47214.6 | 11.43 | 9.95 | 0.00700000 | 29135.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20038.19 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 18.9507 | 23.89 | 0.00778225 | 23.89 | 0.00778225 | 42.2105 | 19249.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 40439.021 | 40439.021 | 1.628479 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.628479 | 1.96002961 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 20219.51 | 12164.00 | 1.0000 | 0.98001480 | 0.814240 | 20.05 | 14.92 | 0.00847334 | 41652.0 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20219.51 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 25.2677 | 21.11 | 0.00837500 | 21.11 | 0.00837500 | 53.7171 | 5707.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40439.021 | 40439.021 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.628479 | 1.96002961 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 40439.02 | 24327.99 | 1.0000 | 1.96002961 | 1.628479 | 20.05 | 14.92 | 0.00847334 | 41652.0 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40439.02 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.6338 | 21.11 | 0.00837500 | 21.11 | 0.00837500 | 53.7171 | 5707.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43902.270 | 31267.636 | 1.833790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8572 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.833788 | 2.20713853 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | Sensible | 21951.13 | 18979.11 | 1.0000 | 1.47142696 | 1.222527 | 25.97 | 16.72 | 0.00807835 | 46691.3 | 11.42 | 9.95 | 0.00700000 | 29135.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21951.13 | 42.48 | 0.01078126 | 23.77 | 0.20573941 | 16.8290 | 23.89 | 0.00773661 | 23.89 | 0.00773661 | 41.9664 | 21667.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 44407.919 | 44407.919 | 1.833788 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.833788 | 2.20713853 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 22203.96 | 13563.64 | 1.0000 | 1.10356926 | 0.916894 | 20.17 | 14.95 | 0.00845686 | 41731.6 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22203.96 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 22.4387 | 21.11 | 0.00836883 | 21.11 | 0.00836883 | 53.6779 | 6256.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 44407.919 | 44407.919 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.833788 | 2.20713853 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 44407.92 | 27127.28 | 1.0000 | 2.20713853 | 1.833788 | 20.17 | 14.95 | 0.00845686 | 41731.6 | 32.22 | 18.76 | 0.00800000 | 52862.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44407.92 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 11.2194 | 21.11 | 0.00836883 | 21.11 | 0.00836883 | 53.6779 | 6256.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5481.50 | 211.67 | 178.17 |
SMSTORE1 | 5403.33 | 178.83 | 155.17 |
SMSTORE2 | 4227.33 | 344.50 | 333.50 |
SMSTORE3 | 4226.50 | 338.67 | 327.17 |
SMSTORE4 | 4210.33 | 339.67 | 325.33 |
LGSTORE2 | 3830.00 | 233.33 | 225.83 |
SMSTORE5 | 3758.50 | 248.67 | 236.67 |
SMSTORE6 | 3748.83 | 252.00 | 239.17 |
SMSTORE7 | 3741.00 | 246.67 | 232.50 |
SMSTORE8 | 3756.83 | 214.00 | 190.50 |
Facility | 5619.67 | 496.17 | 440.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 12.00 | 0.00 | 8.83 |
SMSTORE1 | 0.00 | 9.00 | 0.00 | 7.17 |
SMSTORE2 | 0.00 | 16.17 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 17.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 16.67 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 16.83 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 14.83 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 14.50 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 15.00 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 19.67 | 0.00 | 0.00 |
Facility | 0.00 | 37.00 | 0.00 | 8.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.847 | 0.341 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.734 | 0.378 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.848 | 0.496 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.848 | 0.496 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.848 | 0.496 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.848 | 0.465 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.848 | 0.529 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.848 | 0.529 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.848 | 0.529 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.848 | 0.548 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.048 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.827 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.827 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.827 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.826 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.82 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.13 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803507.24 | 0.00 | 8803507.24 | 3720417.12 | 12523924.36 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3825093.53 | 0.00 | 3825093.53 | 2005460.50 | 5830554.03 | 6488198.17 | 4274.75 | 4485.25 | 0.00 | 103.00 |
SMSTORE2 | 3525579.93 | 0.00 | 3525579.93 | 2030324.42 | 5555904.35 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.25 |
SMSTORE3 | 3525741.55 | 0.00 | 3525741.55 | 2030324.42 | 5556065.98 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 366.92 |
SMSTORE4 | 3525733.36 | 0.00 | 3525733.36 | 2030324.42 | 5556057.79 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 366.67 |
LGSTORE2 | 6510834.19 | 0.00 | 6510834.19 | 3601646.44 | 10112480.62 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 366.75 |
SMSTORE5 | 3255294.92 | 0.00 | 3255294.92 | 2036872.93 | 5292167.85 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.92 |
SMSTORE6 | 3255284.38 | 0.00 | 3255284.38 | 2036872.93 | 5292157.30 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.67 |
SMSTORE7 | 3255299.27 | 0.00 | 3255299.27 | 2036872.93 | 5292172.20 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.83 |
SMSTORE8 | 3256666.92 | 0.00 | 3256666.92 | 2265587.09 | 5522254.00 | 6488198.17 | 4364.98 | 4395.02 | 0.00 | 376.60 |
Total Facility | 42739035.29 | 0.00 | 42739035.29 | 23794703.20 | 66533738.49 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 742.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1654 | 0.5768 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1783 | 0.0000 | 0.1783 | 0.0918 | 0.2701 | 0.2057 | 1457.75 | 4382.25 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2254 | 0.6369 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3341 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3341 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3341 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1330 | 0.3388 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4414 | 0.0000 | 2.4414 | 1.3622 | 3.8036 | 2.4689 | 1457.75 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12753120.48 | 0.00 | 12753120.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 5541186.85 | 0.00 | 5541186.85 | 6488198.17 | 3978.21 | 23.67 | 4758.13 | 103.00 |
PSZ-AC_3:3 | 5107299.21 | 0.00 | 5107299.21 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.25 |
PSZ-AC_4:4 | 5107533.34 | 0.00 | 5107533.34 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 366.83 |
PSZ-AC_5:5 | 5107521.48 | 0.00 | 5107521.48 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 366.67 |
PSZ-AC_6:6 | 9431860.57 | 0.00 | 9431860.57 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 366.67 |
PSZ-AC_7:7 | 4715753.30 | 0.00 | 4715753.30 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.92 |
PSZ-AC_8:8 | 4715738.02 | 0.00 | 4715738.02 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.67 |
PSZ-AC_9:9 | 4715759.60 | 0.00 | 4715759.60 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.83 |
PSZ-AC_10:10 | 4717740.83 | 0.00 | 4717740.83 | 6488198.17 | 4364.98 | 0.00 | 4395.02 | 376.39 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2583 | 0.0000 | 0.2583 | 0.2057 | 1161.21 | 23.67 | 4655.13 |
PSZ-AC_3:3 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4761.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4761.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4396.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4406.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2583 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5962 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 786 |
Defaulted Fields | 863 |
Fields with Defaults | 2832 |
Autosized Fields | 222 |
Autosizable Fields | 564 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2524.58 | 2476.63 | 01-JAN-07:10 | 231672.53 | 10-AUG-16:10 |
Electricity:Building | 747.30 | 2476.63 | 01-JAN-00:10 | 46719.60 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 164.11 | 450.38 | 01-JAN-00:10 | 8500.73 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 747.30 | 2476.63 | 01-JAN-00:10 | 46719.60 | 01-JAN-11:10 |
InteriorLights:Electricity | 619.14 | 2034.80 | 01-JAN-00:10 | 38660.10 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 137.86 | 376.74 | 01-JAN-00:10 | 7157.48 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 619.14 | 2034.80 | 01-JAN-00:10 | 38660.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 619.14 | 2034.80 | 01-JAN-00:10 | 38660.10 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 137.86 | 376.74 | 01-JAN-00:10 | 7157.48 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 619.14 | 2034.80 | 01-JAN-00:10 | 38660.10 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 92.19 | 252.86 | 01-JAN-00:10 | 4776.42 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 79.06 | 216.04 | 01-JAN-00:10 | 4104.79 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 79.06 | 216.04 | 01-JAN-00:10 | 4104.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 69.31 | 238.01 | 01-JAN-00:10 | 4494.25 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 69.31 | 238.01 | 01-JAN-00:10 | 4494.25 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 69.31 | 238.01 | 01-JAN-00:10 | 4494.25 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 58.88 | 201.19 | 01-JAN-00:10 | 3822.63 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 93.40 | 349.58 | 01-JAN-00:10 | 6585.71 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 74.23 | 275.95 | 01-JAN-00:10 | 5242.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 74.23 | 275.95 | 01-JAN-00:10 | 5242.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 47.42 | 177.44 | 01-JAN-00:10 | 3343.50 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 47.42 | 177.44 | 01-JAN-00:10 | 3343.50 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 47.42 | 177.44 | 01-JAN-00:10 | 3343.50 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 47.42 | 177.44 | 01-JAN-00:10 | 3343.50 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 37.83 | 140.62 | 01-JAN-00:10 | 2671.87 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 2524.58 | 2476.63 | 01-JAN-07:10 | 231672.53 | 10-AUG-16:10 |
ElectricityPurchased:Plant | 2524.58 | 2476.63 | 01-JAN-07:10 | 231672.53 | 10-AUG-16:10 |
Cogeneration:ElectricityPurchased | 2524.58 | 2476.63 | 01-JAN-07:10 | 231672.53 | 10-AUG-16:10 |
General:Cogeneration:ElectricityPurchased | 2524.58 | 2476.63 | 01-JAN-07:10 | 231672.53 | 10-AUG-16:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2524.58 | 2476.63 | 01-JAN-07:10 | 231672.53 | 10-AUG-16:10 |
ElectricityNet:Plant | 2524.58 | 2476.63 | 01-JAN-07:10 | 231672.53 | 10-AUG-16:10 |
Cogeneration:ElectricityNet | 2524.58 | 2476.63 | 01-JAN-07:10 | 231672.53 | 10-AUG-16:10 |
General:Cogeneration:ElectricityNet | 2524.58 | 2476.63 | 01-JAN-07:10 | 231672.53 | 10-AUG-16:10 |
Electricity:HVAC | 1587.00 | 0.00 | 01-JAN-00:10 | 184264.80 | 10-AUG-16:10 |
Cooling:Electricity | 1016.41 | 0.00 | 01-JAN-00:10 | 151362.89 | 10-AUG-16:10 |
General:Cooling:Electricity | 1016.41 | 0.00 | 01-JAN-00:10 | 151362.89 | 10-AUG-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity | 570.60 | 0.00 | 01-JAN-00:10 | 32901.90 | 04-JAN-17:00 |
General:Fans:Electricity | 570.60 | 0.00 | 01-JAN-00:10 | 32901.90 | 04-JAN-17:00 |
ExteriorLights:Electricity | 177.87 | 0.00 | 01-JAN-07:10 | 11300.38 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 177.87 | 0.00 | 01-JAN-07:10 | 11300.38 | 01-JAN-00:10 |
Electricity:Plant | 12.42 | 0.00 | 01-JAN-00:10 | 1309.73 | 13-JAN-13:20 |
WaterSystems:Electricity | 12.42 | 0.00 | 01-JAN-00:10 | 1309.73 | 13-JAN-13:20 |
Water Heater:WaterSystems:Electricity | 12.42 | 0.00 | 01-JAN-00:10 | 1309.73 | 13-JAN-13:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
Water:Plant | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
WaterSystems:Water | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
MainsWater:Facility | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
MainsWater:Plant | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
WaterSystems:MainsWater | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.69 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4853.17 | 0.00 | 01-JAN-00:10 | 610788.98 | 20-JUL-13:00 |
EnergyTransfer:Building | 1572.53 | 0.00 | 01-JAN-00:10 | 200183.21 | 16-AUG-12:10 |
EnergyTransfer:Zone:LGSTORE1 | 309.49 | 0.00 | 01-JAN-00:10 | 32529.14 | 16-AUG-12:10 |
Heating:EnergyTransfer | 15.46 | 0.00 | 01-JAN-00:10 | 47356.68 | 05-AUG-17:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.42 | 0.00 | 01-JAN-00:10 | 4207.94 | 21-OCT-07:20 |
General:Heating:EnergyTransfer | 15.46 | 0.00 | 01-JAN-00:10 | 47356.68 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.42 | 0.00 | 01-JAN-00:10 | 4207.94 | 21-OCT-07:20 |
Cooling:EnergyTransfer | 1557.07 | 0.00 | 01-JAN-00:10 | 200183.21 | 16-AUG-12:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 309.07 | 0.00 | 01-JAN-00:10 | 32529.14 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer | 1557.07 | 0.00 | 01-JAN-00:10 | 200183.21 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 309.07 | 0.00 | 01-JAN-00:10 | 32529.14 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE1 | 161.47 | 0.00 | 01-JAN-00:10 | 16800.76 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.21 | 0.00 | 01-JAN-00:10 | 1925.51 | 21-NOV-08:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.21 | 0.00 | 01-JAN-00:10 | 1925.51 | 21-NOV-08:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 161.26 | 0.00 | 01-JAN-00:10 | 16800.76 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 161.26 | 0.00 | 01-JAN-00:10 | 16800.76 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE2 | 131.17 | 0.00 | 01-JAN-00:10 | 16962.44 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 2.98 | 0.00 | 01-JAN-00:10 | 5573.46 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 2.98 | 0.00 | 01-JAN-00:10 | 5573.46 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 128.19 | 0.00 | 01-JAN-00:10 | 16962.44 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 128.19 | 0.00 | 01-JAN-00:10 | 16962.44 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE3 | 132.10 | 0.00 | 01-JAN-00:10 | 17052.42 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 2.95 | 0.00 | 01-JAN-00:10 | 5571.48 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 2.95 | 0.00 | 01-JAN-00:10 | 5571.48 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 129.14 | 0.00 | 01-JAN-00:10 | 17052.42 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 129.14 | 0.00 | 01-JAN-00:10 | 17052.42 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE4 | 131.13 | 0.00 | 01-JAN-00:10 | 17010.78 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 3.00 | 0.00 | 01-JAN-00:10 | 5573.95 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 3.00 | 0.00 | 01-JAN-00:10 | 5573.95 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 128.13 | 0.00 | 01-JAN-00:10 | 17010.78 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 128.13 | 0.00 | 01-JAN-00:10 | 17010.78 | 16-AUG-12:10 |
EnergyTransfer:Zone:LGSTORE2 | 225.56 | 0.00 | 01-JAN-00:10 | 31184.90 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.86 | 0.00 | 01-JAN-00:10 | 10288.05 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.86 | 0.00 | 01-JAN-00:10 | 10288.05 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 223.70 | 0.00 | 01-JAN-00:10 | 31184.90 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 223.70 | 0.00 | 01-JAN-00:10 | 31184.90 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE5 | 117.11 | 0.00 | 01-JAN-00:10 | 16498.35 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 1.00 | 0.00 | 01-JAN-00:10 | 5295.60 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 1.00 | 0.00 | 01-JAN-00:10 | 5295.60 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 116.11 | 0.00 | 01-JAN-00:10 | 16498.35 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 116.11 | 0.00 | 01-JAN-00:10 | 16498.35 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE6 | 116.37 | 0.00 | 01-JAN-00:10 | 16443.07 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 1.01 | 0.00 | 01-JAN-00:10 | 5295.54 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 1.01 | 0.00 | 01-JAN-00:10 | 5295.54 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 115.37 | 0.00 | 01-JAN-00:10 | 16443.07 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 115.37 | 0.00 | 01-JAN-00:10 | 16443.07 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE7 | 117.21 | 0.00 | 01-JAN-00:10 | 16607.44 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.01 | 0.00 | 01-JAN-00:10 | 5291.04 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 1.01 | 0.00 | 01-JAN-00:10 | 5291.04 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 116.21 | 0.00 | 01-JAN-00:10 | 16607.44 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 116.21 | 0.00 | 01-JAN-00:10 | 16607.44 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE8 | 130.92 | 0.00 | 01-JAN-00:10 | 19093.89 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.03 | 0.00 | 01-JAN-00:10 | 5290.89 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 1.03 | 0.00 | 01-JAN-00:10 | 5290.89 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 129.90 | 0.00 | 01-JAN-00:10 | 19093.89 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 129.90 | 0.00 | 01-JAN-00:10 | 19093.89 | 16-AUG-12:10 |
EnergyTransfer:HVAC | 3280.64 | 0.00 | 01-JAN-00:10 | 445743.43 | 20-JUL-13:00 |
CoolingCoils:EnergyTransfer | 3280.64 | 0.00 | 01-JAN-00:10 | 445743.43 | 20-JUL-13:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.421 | -309.068 | 0.000 | 0.000 | 23.214 | 137.864 | 26.249 | 49.787 | 0.000 | 32.777 | 49.953 | 0.000 | -8.847 | 0.000 | -2.351 | -0.002 |
SMSTORE1 | 0.000 | 0.000 | 0.206 | -161.265 | 0.000 | 0.000 | 11.607 | 79.064 | 13.125 | 25.070 | 0.000 | 18.131 | 19.640 | 0.000 | -4.469 | 0.000 | -1.109 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 2.980 | -128.185 | 0.000 | 0.000 | 6.956 | 58.885 | 10.421 | 24.315 | 0.000 | 17.863 | 12.857 | 0.000 | -4.852 | 0.000 | -1.239 | -0.002 |
SMSTORE3 | 0.000 | 0.000 | 2.954 | -129.140 | 0.000 | 0.000 | 6.956 | 58.885 | 10.421 | 24.237 | 0.000 | 17.852 | 13.967 | 0.000 | -4.891 | 0.000 | -1.241 | -0.000 |
SMSTORE4 | 0.000 | 0.000 | 2.999 | -128.127 | 0.000 | 0.000 | 6.957 | 58.885 | 10.421 | 24.276 | 0.000 | 17.855 | 12.802 | 0.000 | -4.831 | 0.000 | -1.235 | -0.001 |
LGSTORE2 | 0.000 | 0.000 | 1.856 | -223.701 | 0.000 | 0.000 | 23.909 | 74.230 | 19.173 | 48.985 | 0.000 | 31.448 | 35.334 | 0.000 | -9.013 | 0.000 | -2.221 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.999 | -116.113 | 0.000 | 0.000 | 11.954 | 37.832 | 9.586 | 24.668 | 0.000 | 17.894 | 18.811 | 0.000 | -4.415 | 0.000 | -1.217 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 1.006 | -115.368 | 0.000 | 0.000 | 11.954 | 37.832 | 9.586 | 24.696 | 0.000 | 17.896 | 18.003 | 0.000 | -4.392 | 0.000 | -1.214 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 1.009 | -116.205 | 0.000 | 0.000 | 11.954 | 37.832 | 9.586 | 24.651 | 0.000 | 17.890 | 18.888 | 0.000 | -4.394 | 0.000 | -1.214 | -0.001 |
SMSTORE8 | 0.000 | 0.000 | 1.027 | -129.894 | 0.000 | 0.000 | 11.954 | 37.832 | 9.586 | 24.238 | 0.000 | 18.816 | 32.458 | 0.000 | -4.377 | 0.000 | -1.641 | -0.001 |
Total Facility | 0.000 | 0.000 | 15.458 | -1557.065 | 0.000 | 0.000 | 127.417 | 619.141 | 128.154 | 294.924 | 0.000 | 208.422 | 232.714 | 0.000 | -54.482 | 0.000 | -14.682 | -0.008 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 10-MAY-07:01 | 0.00 | 0.00 | 0.00 | -63068.39 | 0.00 | 0.00 | 156.99 | 376.74 | 74.62 | 933.72 | 0.00 | 363.19 | 61163.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 11-MAY-07:01 | 0.00 | 0.00 | 0.00 | -32425.79 | 0.00 | 0.00 | 77.05 | 216.04 | 37.31 | 485.55 | 0.00 | 179.16 | 31430.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 28-MAR-06:02 | 0.00 | 0.00 | 0.00 | -33350.64 | 0.00 | 0.00 | 0.00 | 201.19 | 36.82 | 0.00 | 0.00 | 0.00 | 33459.69 | 0.00 | -346.50 | 0.00 | -0.56 | 0.00 |
SMSTORE3 | 28-MAR-06:02 | 0.00 | 0.00 | 0.00 | -33478.85 | 0.00 | 0.00 | 0.00 | 201.19 | 36.82 | 0.00 | 0.00 | 0.00 | 33593.42 | 0.00 | -351.95 | 0.00 | -0.63 | 0.00 |
SMSTORE4 | 28-MAR-06:02 | 0.00 | 0.00 | 0.00 | -33376.30 | 0.00 | 0.00 | 0.00 | 201.19 | 36.82 | 0.00 | 0.00 | 0.00 | 33485.63 | 0.00 | -346.78 | 0.00 | -0.56 | 0.00 |
LGSTORE2 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -60290.95 | 0.00 | 0.00 | 0.00 | 275.95 | 73.64 | 1730.04 | 0.00 | 359.68 | 57851.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -31304.40 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 876.21 | 0.00 | 211.07 | 30039.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -31183.15 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 877.93 | 0.00 | 211.76 | 29916.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -31422.10 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 872.15 | 0.00 | 209.28 | 30163.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -34804.44 | 0.00 | 0.00 | 0.00 | 140.62 | 36.82 | 843.92 | 0.00 | 211.85 | 33571.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-MAY-07:01 | 0.00 | 0.00 | 0.00 | -295254.83 | 0.00 | 0.00 | 525.52 | 7466.95 | 1452.23 | 6149.02 | 0.00 | 2252.17 | 277408.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 11-JUL-07:05 | 0.00 | 0.00 | 11011.76 | 0.00 | 0.00 | 0.00 | 134.96 | 376.74 | 74.62 | 1244.25 | 0.00 | 741.17 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13583.52 |
SMSTORE1 | 06-AUG-07:05 | 0.00 | 0.00 | 5926.03 | 0.00 | 0.00 | 0.00 | 63.67 | 216.04 | 37.31 | 699.78 | 0.00 | 419.74 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7362.57 |
SMSTORE2 | 31-MAY-19:11 | 0.00 | 0.00 | 6358.60 | 0.00 | 0.00 | 0.00 | 67.64 | 2011.91 | 373.13 | 1031.57 | 0.00 | 47.05 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9889.90 |
SMSTORE3 | 31-MAY-19:11 | 0.00 | 0.00 | 6360.87 | 0.00 | 0.00 | 0.00 | 67.56 | 2011.91 | 373.13 | 1030.34 | 0.00 | 47.03 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9890.83 |
SMSTORE4 | 31-MAY-19:11 | 0.00 | 0.00 | 6360.61 | 0.00 | 0.00 | 0.00 | 67.63 | 2011.91 | 373.13 | 1031.42 | 0.00 | 47.05 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9891.73 |
LGSTORE2 | 05-AUG-17:01 | 0.00 | 0.00 | 11699.21 | 0.00 | 0.00 | 0.00 | 433.40 | 2759.18 | 746.25 | 3007.33 | 0.00 | 1160.96 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19806.32 |
SMSTORE5 | 05-AUG-17:11 | 0.00 | 0.00 | 6010.56 | 0.00 | 0.00 | 0.00 | 142.85 | 1406.25 | 373.13 | 1332.94 | 0.00 | 549.94 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9815.66 |
SMSTORE6 | 05-AUG-17:11 | 0.00 | 0.00 | 6004.65 | 0.00 | 0.00 | 0.00 | 143.10 | 1406.25 | 373.13 | 1334.43 | 0.00 | 550.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9811.86 |
SMSTORE7 | 05-AUG-17:11 | 0.00 | 0.00 | 6011.69 | 0.00 | 0.00 | 0.00 | 142.52 | 1406.25 | 373.13 | 1330.74 | 0.00 | 549.43 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9813.74 |
SMSTORE8 | 05-AUG-17:11 | 0.00 | 0.00 | 6239.90 | 0.00 | 0.00 | 0.00 | 134.23 | 1406.25 | 373.13 | 1284.49 | 0.00 | 620.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10058.50 |
Total Facility | 05-AUG-17:11 | -32989.44 | 32989.44 | 54212.33 | -32989.44 | 0.00 | 0.00 | 3991.77 | 25682.17 | 5373.00 | 16169.62 | 0.00 | 6839.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -79279.10 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.3279 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 3.3279 | 0.1236 | 1.0000 | Not calculated | 0.4115 | 0.1236 | ||
PSZ-AC_2:2 | 1.7050 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.7050 | 0.1207 | 1.0000 | Not calculated | 0.2057 | 0.1207 | ||
PSZ-AC_3:3 | 1.7047 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.7047 | 0.1207 | 1.0000 | Not calculated | 0.2057 | 0.1207 | ||
PSZ-AC_4:4 | 1.7073 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.7073 | 0.1205 | 1.0000 | Not calculated | 0.2057 | 0.1205 | ||
PSZ-AC_5:5 | 1.7059 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.7059 | 0.1206 | 1.0000 | Not calculated | 0.2057 | 0.1206 | ||
PSZ-AC_6:6 | 3.0924 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 3.0924 | 0.1331 | 1.0000 | Not calculated | 0.4115 | 0.1331 | ||
PSZ-AC_7:7 | 1.6254 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6254 | 0.1266 | 1.0000 | Not calculated | 0.2057 | 0.1266 | ||
PSZ-AC_8:8 | 1.6197 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6197 | 0.1270 | 1.0000 | Not calculated | 0.2057 | 0.1270 | ||
PSZ-AC_9:9 | 1.6285 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6285 | 0.1263 | 1.0000 | Not calculated | 0.2057 | 0.1263 | ||
PSZ-AC_10:10 | 1.8338 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.8338 | 0.1122 | 1.0000 | Not calculated | 0.2057 | 0.1122 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.3279 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 3.3279 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1236 | ||
PSZ-AC_2:2 | 1.7050 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.7050 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1207 | ||
PSZ-AC_3:3 | 1.7047 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.7047 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1207 | ||
PSZ-AC_4:4 | 1.7073 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.7073 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1205 | ||
PSZ-AC_5:5 | 1.7059 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.7059 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1206 | ||
PSZ-AC_6:6 | 3.0924 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 3.0924 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1331 | ||
PSZ-AC_7:7 | 1.6254 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6254 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1266 | ||
PSZ-AC_8:8 | 1.6197 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6197 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1270 | ||
PSZ-AC_9:9 | 1.6285 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6285 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1263 | ||
PSZ-AC_10:10 | 1.8338 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.8338 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1122 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3279 | 3.3279 | 3.3279 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7050 | 1.7050 | 1.7050 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7047 | 1.7047 | 1.7047 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7073 | 1.7073 | 1.7073 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7059 | 1.7059 | 1.7059 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0924 | 3.0924 | 3.0924 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6254 | 1.6254 | 1.6254 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6197 | 1.6197 | 1.6197 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6285 | 1.6285 | 1.6285 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8338 | 1.8338 | 1.8338 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.3279 | 3.3279 | 3.3279 | 3.3279 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.7050 | 1.7050 | 1.7050 | 1.7050 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.7047 | 1.7047 | 1.7047 | 1.7047 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.7073 | 1.7073 | 1.7073 | 1.7073 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.7059 | 1.7059 | 1.7059 | 1.7059 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 3.0924 | 3.0924 | 3.0924 | 3.0924 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.6254 | 1.6254 | 1.6254 | 1.6254 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.6197 | 1.6197 | 1.6197 | 1.6197 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.6285 | 1.6285 | 1.6285 | 1.6285 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.8338 | 1.8338 | 1.8338 | 1.8338 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.3279 | 3.3279 | 3.3279 | No | 0.4115 | 0.4429 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7050 | 1.7050 | 1.7050 | No | 0.2057 | 0.4300 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7047 | 1.7047 | 1.7047 | No | 0.2057 | 0.4215 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7073 | 1.7073 | 1.7073 | No | 0.2057 | 0.4168 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7059 | 1.7059 | 1.7059 | No | 0.2057 | 0.4114 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0924 | 3.0924 | 3.0924 | No | 0.4115 | 0.4264 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6254 | 1.6254 | 1.6254 | No | 0.2057 | 0.3959 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6197 | 1.6197 | 1.6197 | No | 0.2057 | 0.3969 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6285 | 1.6285 | 1.6285 | No | 0.2057 | 0.3932 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8338 | 1.8338 | 1.8338 | No | 0.2057 | 0.3587 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.3279 | 3.3279 | 3.3279 | 3.3279 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.7050 | 1.7050 | 1.7050 | 1.7050 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.7047 | 1.7047 | 1.7047 | 1.7047 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.7073 | 1.7073 | 1.7073 | 1.7073 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.7059 | 1.7059 | 1.7059 | 1.7059 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 3.0924 | 3.0924 | 3.0924 | 3.0924 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.6254 | 1.6254 | 1.6254 | 1.6254 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.6197 | 1.6197 | 1.6197 | 1.6197 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.6285 | 1.6285 | 1.6285 | 1.6285 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.8338 | 1.8338 | 1.8338 | 1.8338 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 8.83 |
Number of hours not met | 8.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1016.41 | 151362.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 619.14 | 38660.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 177.87 | 11300.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 570.60 | 32901.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 12.42 | 1309.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 2524.58 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 2524.58 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 296.19 |
Space Heating | 0.00 |
Space Cooling | 486.25 |
Fans (All) | 272.97 |
Service Water Heating | 5.94 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 1207.75 |
Subtotal | 1207.75 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.52 |
Space Heating | 0.00 |
Space Cooling | 40.26 |
Fans (All) | 22.60 |
Service Water Heating | 0.49 |
Receptacle Equipment | 5.08 |
Miscellaneous | 7.05 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3758. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3767. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 5104. | 8760. |
LTG_SCH_BASE_LPD1 | 5091. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 4096. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 7757.50 | 1002.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7885.00 | 875.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 6387.33 | 2315.67 | 57.00 | 0.00 | 0.00 |
SMSTORE3 | 6344.00 | 2337.17 | 78.83 | 0.00 | 0.00 |
SMSTORE4 | 6380.83 | 2297.67 | 81.50 | 0.00 | 0.00 |
LGSTORE2 | 6767.00 | 1917.67 | 75.33 | 0.00 | 0.00 |
SMSTORE5 | 6886.00 | 1802.50 | 71.50 | 0.00 | 0.00 |
SMSTORE6 | 6905.83 | 1783.67 | 70.50 | 0.00 | 0.00 |
SMSTORE7 | 6869.33 | 1807.67 | 83.00 | 0.00 | 0.00 |
SMSTORE8 | 6680.33 | 1831.67 | 248.00 | 0.00 | 0.00 |
Min | 6344.00 | 875.00 | 0.00 | 0.00 | 0.00 |
Max | 7885.00 | 2337.17 | 248.00 | 0.00 | 0.00 |
Average | 6886.32 | 1797.12 | 76.57 | 0.00 | 0.00 |
Sum | 68863.17 | 17971.17 | 765.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25249.00 | 224.33 | 1.67 | 0.00 | 0.00 |
SMSTORE3 | 25249.17 | 224.33 | 1.50 | 0.00 | 0.00 |
SMSTORE4 | 25250.83 | 222.67 | 1.50 | 0.00 | 0.00 |
LGSTORE2 | 92776.00 | 426.00 | 9.00 | 0.00 | 0.00 |
SMSTORE5 | 45692.00 | 214.00 | 6.00 | 0.00 | 0.00 |
SMSTORE6 | 45692.00 | 214.00 | 6.00 | 0.00 | 0.00 |
SMSTORE7 | 45692.00 | 214.50 | 5.50 | 0.00 | 0.00 |
SMSTORE8 | 45681.50 | 226.00 | 4.50 | 0.00 | 0.00 |
Min | 25249.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 92776.00 | 426.00 | 9.00 | 0.00 | 0.00 |
Average | 48410.05 | 196.58 | 3.57 | 0.00 | 0.00 |
Sum | 484100.50 | 1965.83 | 35.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 7137.67 | 1622.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7534.17 | 1225.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 5475.00 | 3258.67 | 26.33 | 0.00 | 0.00 |
SMSTORE3 | 5470.00 | 3252.83 | 37.17 | 0.00 | 0.00 |
SMSTORE4 | 5496.67 | 3224.33 | 39.00 | 0.00 | 0.00 |
LGSTORE2 | 5843.17 | 2883.33 | 33.50 | 0.00 | 0.00 |
SMSTORE5 | 5897.33 | 2823.33 | 39.33 | 0.00 | 0.00 |
SMSTORE6 | 5900.83 | 2820.17 | 39.00 | 0.00 | 0.00 |
SMSTORE7 | 5906.50 | 2811.33 | 42.17 | 0.00 | 0.00 |
SMSTORE8 | 5784.17 | 2877.33 | 98.50 | 0.00 | 0.00 |
Min | 5470.00 | 1225.83 | 0.00 | 0.00 | 0.00 |
Max | 7534.17 | 3258.67 | 98.50 | 0.00 | 0.00 |
Average | 6044.55 | 2679.95 | 35.50 | 0.00 | 0.00 |
Sum | 60445.50 | 26799.50 | 355.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 87349.00 | 1692.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 42687.17 | 1089.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24437.67 | 1037.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24471.83 | 1003.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24466.83 | 1008.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 88893.67 | 4317.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 43555.00 | 2356.50 | 0.50 | 0.00 | 0.00 |
SMSTORE6 | 43499.83 | 2411.67 | 0.50 | 0.00 | 0.00 |
SMSTORE7 | 43618.00 | 2294.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 44283.50 | 1628.50 | 0.00 | 0.00 | 0.00 |
Min | 24437.67 | 1003.17 | 0.00 | 0.00 | 0.00 |
Max | 88893.67 | 4317.33 | 0.50 | 0.00 | 0.00 |
Average | 46726.25 | 1883.85 | 0.10 | 0.00 | 0.00 |
Sum | 467262.50 | 18838.50 | 1.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143369E+11 | 21668.97 | 29-JAN-08:63 | 22.17 | 18.26 | 0.140947E+10 | 1686.03 | 14-JAN-13:00 | 22.17 | 18.26 |
February | 0.147237E+11 | 37050.08 | 09-FEB-08:62 | 22.17 | 19.26 | 0.127254E+10 | 1686.06 | 19-FEB-13:09 | 25.33 | 18.14 |
March | 0.188556E+11 | 59681.70 | 02-MAR-08:62 | 27.00 | 17.55 | 0.139758E+10 | 1686.08 | 31-MAR-12:00 | 26.00 | 20.01 |
April | 0.224199E+11 | 59793.33 | 29-APR-07:02 | 27.25 | 16.62 | 0.136176E+10 | 1686.07 | 21-APR-12:09 | 27.25 | 16.62 |
May | 0.299817E+11 | 63073.02 | 10-MAY-07:01 | 30.52 | 16.02 | 0.140200E+10 | 1686.00 | 28-MAY-17:00 | 31.00 | 25.72 |
June | 0.315941E+11 | 55587.05 | 01-JUN-07:01 | 30.17 | 21.35 | 0.135507E+10 | 1686.09 | 04-JUN-17:10 | 35.67 | 28.96 |
July | 0.358744E+11 | 61985.76 | 04-JUL-07:01 | 31.33 | 17.56 | 0.141343E+10 | 1686.09 | 16-JUL-17:10 | 35.00 | 29.36 |
August | 0.372475E+11 | 56789.45 | 06-AUG-07:01 | 35.08 | 22.69 | 0.139482E+10 | 1686.08 | 27-AUG-17:10 | 35.83 | 28.37 |
September | 0.329615E+11 | 52592.23 | 02-SEP-07:01 | 32.25 | 23.03 | 0.136571E+10 | 1686.10 | 10-SEP-17:10 | 34.00 | 30.01 |
October | 0.303069E+11 | 59269.20 | 20-OCT-07:02 | 23.25 | 15.43 | 0.141012E+10 | 1686.09 | 07-OCT-12:50 | 23.25 | 15.43 |
November | 0.234866E+11 | 58876.00 | 05-NOV-07:02 | 21.17 | 15.81 | 0.136341E+10 | 1686.06 | 24-NOV-13:09 | 28.08 | 22.45 |
December | 0.172792E+11 | 49793.95 | 12-DEC-08:62 | 23.17 | 17.37 | 0.141679E+10 | 1686.08 | 08-DEC-13:00 | 23.17 | 17.37 |
Annual Sum or Average | 0.309068E+12 | 0.165627E+11 | ||||||||
Minimum of Months | 0.143369E+11 | 21668.97 | 21.17 | 15.43 | 0.127254E+10 | 1686.00 | 22.17 | 15.43 | ||
Maximum of Months | 0.372475E+11 | 63073.02 | 35.08 | 23.03 | 0.141679E+10 | 1686.10 | 35.83 | 30.01 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.791070E+10 | 12161.91 | 29-JAN-08:63 | 22.17 | 18.26 | 0.704781E+09 | 843.00 | 07-JAN-13:00 | 22.17 | 18.26 |
February | 0.806066E+10 | 19951.18 | 09-FEB-08:62 | 22.17 | 19.26 | 0.636291E+09 | 843.00 | 17-FEB-13:00 | 25.00 | 18.54 |
March | 0.102155E+11 | 30662.19 | 02-MAR-08:62 | 27.00 | 17.55 | 0.698797E+09 | 843.01 | 31-MAR-12:00 | 26.00 | 20.01 |
April | 0.119620E+11 | 31108.52 | 29-APR-07:02 | 27.25 | 16.62 | 0.680880E+09 | 843.00 | 16-APR-16:10 | 27.25 | 16.62 |
May | 0.156077E+11 | 32427.74 | 11-MAY-07:01 | 30.33 | 16.47 | 0.700986E+09 | 842.96 | 28-MAY-12:20 | 34.90 | 24.88 |
June | 0.162768E+11 | 29803.48 | 02-JUN-07:01 | 29.67 | 18.04 | 0.677509E+09 | 843.02 | 04-JUN-17:10 | 35.67 | 28.96 |
July | 0.183398E+11 | 32050.53 | 04-JUL-07:01 | 31.33 | 17.56 | 0.706672E+09 | 843.02 | 16-JUL-17:10 | 35.00 | 29.36 |
August | 0.188680E+11 | 29541.37 | 06-AUG-07:01 | 35.08 | 22.69 | 0.697357E+09 | 843.01 | 27-AUG-17:10 | 35.83 | 28.37 |
September | 0.168259E+11 | 28303.04 | 26-SEP-07:01 | 27.00 | 17.98 | 0.682820E+09 | 843.02 | 10-SEP-17:10 | 27.00 | 17.98 |
October | 0.156074E+11 | 31455.20 | 20-OCT-07:02 | 23.25 | 15.43 | 0.705035E+09 | 843.02 | 07-OCT-12:39 | 23.25 | 15.43 |
November | 0.122677E+11 | 31178.99 | 05-NOV-07:02 | 21.17 | 15.81 | 0.681690E+09 | 843.00 | 24-NOV-13:09 | 28.08 | 22.45 |
December | 0.932231E+10 | 27503.63 | 12-DEC-08:62 | 23.17 | 17.37 | 0.708392E+09 | 843.01 | 22-DEC-13:50 | 24.00 | 18.09 |
Annual Sum or Average | 0.161264E+12 | 0.828121E+10 | ||||||||
Minimum of Months | 0.791070E+10 | 12161.91 | 21.17 | 15.43 | 0.636291E+09 | 842.96 | 22.17 | 15.43 | ||
Maximum of Months | 0.188680E+11 | 32427.74 | 35.08 | 22.69 | 0.708392E+09 | 843.02 | 35.83 | 29.36 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.568591E+10 | 11951.57 | 29-JAN-08:63 | 22.17 | 18.26 | 0.420598E+09 | 842.99 | 14-JAN-13:09 | 22.17 | 18.26 |
February | 0.599780E+10 | 21753.46 | 09-FEB-07:03 | 22.42 | 19.25 | 0.382200E+09 | 842.99 | 25-FEB-13:00 | 22.00 | 15.87 |
March | 0.789290E+10 | 33352.76 | 28-MAR-06:02 | 24.00 | 14.40 | 0.432297E+09 | 843.00 | 18-MAR-12:20 | 24.00 | 14.40 |
April | 0.932761E+10 | 31164.90 | 29-APR-06:02 | 25.25 | 16.39 | 0.412095E+09 | 842.98 | 15-APR-12:00 | 25.25 | 16.39 |
May | 0.126281E+11 | 32199.37 | 11-MAY-06:01 | 28.30 | 15.96 | 0.428027E+09 | 842.92 | 27-MAY-12:30 | 34.75 | 23.02 |
June | 0.133435E+11 | 30231.17 | 01-JUN-06:01 | 27.43 | 20.95 | 0.418981E+09 | 843.01 | 10-JUN-12:00 | 36.30 | 29.09 |
July | 0.148528E+11 | 31895.47 | 04-JUL-07:01 | 31.33 | 17.56 | 0.422312E+09 | 843.00 | 01-JUL-12:00 | 31.33 | 17.56 |
August | 0.156209E+11 | 26752.38 | 16-AUG-06:01 | 33.90 | 25.20 | 0.433942E+09 | 843.00 | 26-AUG-12:50 | 37.25 | 27.15 |
September | 0.136713E+11 | 24697.28 | 05-SEP-06:01 | 30.92 | 23.71 | 0.412893E+09 | 842.99 | 09-SEP-12:20 | 35.90 | 25.83 |
October | 0.125449E+11 | 30279.75 | 20-OCT-06:02 | 23.82 | 15.96 | 0.422340E+09 | 843.02 | 07-OCT-12:30 | 23.82 | 15.96 |
November | 0.969576E+10 | 29723.33 | 05-NOV-07:02 | 21.17 | 15.81 | 0.407386E+09 | 842.99 | 25-NOV-13:09 | 26.75 | 19.19 |
December | 0.692541E+10 | 25445.94 | 12-DEC-07:02 | 23.17 | 17.81 | 0.420395E+09 | 842.98 | 09-DEC-13:00 | 23.17 | 17.81 |
Annual Sum or Average | 0.128187E+12 | 0.501347E+10 | ||||||||
Minimum of Months | 0.568591E+10 | 11951.57 | 21.17 | 14.40 | 0.382200E+09 | 842.92 | 22.00 | 14.40 | ||
Maximum of Months | 0.156209E+11 | 33352.76 | 33.90 | 25.20 | 0.433942E+09 | 843.02 | 37.25 | 29.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.564395E+10 | 11733.73 | 29-JAN-08:63 | 22.17 | 18.26 | 0.420585E+09 | 842.99 | 14-JAN-13:09 | 22.17 | 18.26 |
February | 0.598173E+10 | 22022.84 | 09-FEB-07:03 | 22.42 | 19.25 | 0.382195E+09 | 842.97 | 25-FEB-13:00 | 22.00 | 15.87 |
March | 0.790440E+10 | 33480.91 | 28-MAR-06:02 | 24.00 | 14.40 | 0.432295E+09 | 843.00 | 18-MAR-12:20 | 24.00 | 14.40 |
April | 0.938468E+10 | 31312.91 | 29-APR-06:02 | 25.25 | 16.39 | 0.412099E+09 | 842.98 | 15-APR-12:00 | 25.25 | 16.39 |
May | 0.127558E+11 | 32351.66 | 11-MAY-06:01 | 28.30 | 15.96 | 0.428034E+09 | 842.92 | 27-MAY-12:30 | 34.75 | 23.02 |
June | 0.134806E+11 | 30426.59 | 01-JUN-06:01 | 27.43 | 20.95 | 0.418986E+09 | 843.01 | 10-JUN-12:00 | 36.30 | 29.09 |
July | 0.150316E+11 | 32138.26 | 04-JUL-07:01 | 31.33 | 17.56 | 0.422317E+09 | 843.00 | 01-JUL-12:00 | 31.33 | 17.56 |
August | 0.157957E+11 | 26966.34 | 16-AUG-06:01 | 33.90 | 25.20 | 0.433947E+09 | 843.00 | 26-AUG-12:50 | 37.25 | 27.15 |
September | 0.138214E+11 | 25126.14 | 05-SEP-06:01 | 30.92 | 23.71 | 0.412901E+09 | 842.99 | 09-SEP-12:20 | 35.90 | 25.83 |
October | 0.126705E+11 | 30430.05 | 20-OCT-06:02 | 23.82 | 15.96 | 0.422349E+09 | 843.02 | 07-OCT-12:30 | 23.82 | 15.96 |
November | 0.975173E+10 | 29871.61 | 05-NOV-07:02 | 21.17 | 15.81 | 0.407390E+09 | 842.99 | 25-NOV-13:09 | 26.75 | 19.19 |
December | 0.691967E+10 | 25502.14 | 12-DEC-07:02 | 23.17 | 17.81 | 0.420392E+09 | 842.98 | 09-DEC-13:00 | 23.17 | 17.81 |
Annual Sum or Average | 0.129142E+12 | 0.501349E+10 | ||||||||
Minimum of Months | 0.564395E+10 | 11733.73 | 21.17 | 14.40 | 0.382195E+09 | 842.92 | 22.00 | 14.40 | ||
Maximum of Months | 0.157957E+11 | 33480.91 | 33.90 | 25.20 | 0.433947E+09 | 843.02 | 37.25 | 29.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548868E+10 | 11089.60 | 29-JAN-08:63 | 22.17 | 18.26 | 0.420557E+09 | 842.99 | 14-JAN-13:00 | 22.17 | 18.26 |
February | 0.585490E+10 | 21103.52 | 09-FEB-07:03 | 22.42 | 19.25 | 0.382177E+09 | 842.96 | 11-FEB-13:00 | 23.00 | 15.32 |
March | 0.776928E+10 | 33378.42 | 28-MAR-06:02 | 24.00 | 14.40 | 0.432276E+09 | 843.00 | 18-MAR-12:20 | 24.00 | 14.40 |
April | 0.927538E+10 | 31188.29 | 29-APR-06:02 | 25.25 | 16.39 | 0.412083E+09 | 842.98 | 15-APR-12:00 | 25.25 | 16.39 |
May | 0.126901E+11 | 32235.68 | 11-MAY-06:01 | 28.30 | 15.96 | 0.428022E+09 | 842.92 | 27-MAY-12:30 | 34.75 | 23.02 |
June | 0.134281E+11 | 30327.87 | 01-JUN-06:01 | 27.43 | 20.95 | 0.418978E+09 | 843.01 | 10-JUN-12:00 | 36.30 | 29.09 |
July | 0.150126E+11 | 32065.02 | 04-JUL-07:01 | 31.33 | 17.56 | 0.422313E+09 | 843.00 | 01-JUL-12:00 | 31.33 | 17.56 |
August | 0.157744E+11 | 26871.01 | 16-AUG-06:01 | 33.90 | 25.20 | 0.433944E+09 | 843.00 | 26-AUG-12:50 | 37.25 | 27.15 |
September | 0.137805E+11 | 25180.64 | 05-SEP-06:01 | 30.92 | 23.71 | 0.412892E+09 | 842.99 | 09-SEP-12:20 | 35.90 | 25.83 |
October | 0.126098E+11 | 30320.73 | 20-OCT-06:02 | 23.82 | 15.96 | 0.422335E+09 | 843.02 | 07-OCT-12:30 | 23.82 | 15.96 |
November | 0.965793E+10 | 29803.06 | 05-NOV-07:02 | 21.17 | 15.81 | 0.407374E+09 | 842.99 | 25-NOV-13:09 | 26.75 | 19.19 |
December | 0.678692E+10 | 25391.97 | 12-DEC-07:02 | 23.17 | 17.81 | 0.420374E+09 | 842.98 | 09-DEC-13:00 | 23.17 | 17.81 |
Annual Sum or Average | 0.128129E+12 | 0.501332E+10 | ||||||||
Minimum of Months | 0.548868E+10 | 11089.60 | 21.17 | 14.40 | 0.382177E+09 | 842.92 | 22.17 | 14.40 | ||
Maximum of Months | 0.157744E+11 | 33378.42 | 33.90 | 25.20 | 0.433944E+09 | 843.02 | 37.25 | 29.09 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.910180E+10 | 23851.69 | 29-JAN-09:03 | 23.22 | 19.02 | 0.143511E+10 | 2248.04 | 28-JAN-15:00 | 23.22 | 19.02 |
February | 0.988445E+10 | 36501.02 | 06-FEB-08:62 | 21.17 | 17.80 | 0.130689E+10 | 2248.02 | 11-FEB-15:00 | 21.30 | 15.15 |
March | 0.133058E+11 | 57345.00 | 28-MAR-07:02 | 24.33 | 12.69 | 0.148054E+10 | 2248.05 | 18-MAR-14:09 | 24.33 | 12.69 |
April | 0.160375E+11 | 56297.54 | 29-APR-07:02 | 27.25 | 16.62 | 0.141210E+10 | 2248.09 | 15-APR-14:00 | 27.25 | 16.62 |
May | 0.222963E+11 | 58768.29 | 11-MAY-07:01 | 30.33 | 16.47 | 0.146038E+10 | 2247.81 | 06-MAY-14:50 | 30.33 | 16.47 |
June | 0.236725E+11 | 54865.35 | 01-JUN-07:01 | 30.17 | 21.35 | 0.143222E+10 | 2248.10 | 10-JUN-14:09 | 37.00 | 27.58 |
July | 0.265918E+11 | 60293.43 | 04-JUL-08:61 | 32.82 | 19.26 | 0.144169E+10 | 2248.08 | 01-JUL-14:09 | 32.82 | 19.26 |
August | 0.280812E+11 | 49634.97 | 16-AUG-07:01 | 33.67 | 25.11 | 0.148264E+10 | 2248.08 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.243578E+11 | 48176.49 | 26-SEP-07:01 | 27.00 | 17.98 | 0.141314E+10 | 2248.11 | 09-SEP-14:00 | 27.00 | 17.98 |
October | 0.221889E+11 | 56570.84 | 20-OCT-07:02 | 23.25 | 15.43 | 0.143822E+10 | 2248.11 | 07-OCT-14:09 | 23.25 | 15.43 |
November | 0.167359E+11 | 55760.76 | 19-NOV-09:02 | 25.40 | 16.09 | 0.138394E+10 | 2248.07 | 25-NOV-15:00 | 26.30 | 18.79 |
December | 0.114482E+11 | 48139.44 | 12-DEC-08:62 | 23.17 | 17.37 | 0.143827E+10 | 2248.10 | 02-DEC-15:50 | 23.17 | 17.37 |
Annual Sum or Average | 0.223702E+12 | 0.171251E+11 | ||||||||
Minimum of Months | 0.910180E+10 | 23851.69 | 21.17 | 12.69 | 0.130689E+10 | 2247.81 | 21.30 | 12.69 | ||
Maximum of Months | 0.280812E+11 | 60293.43 | 33.67 | 25.11 | 0.148264E+10 | 2248.11 | 37.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.459964E+10 | 10990.63 | 29-JAN-09:03 | 23.22 | 19.02 | 0.717542E+09 | 1123.99 | 28-JAN-15:00 | 23.22 | 19.02 |
February | 0.503147E+10 | 17493.42 | 06-FEB-08:62 | 21.17 | 17.80 | 0.653426E+09 | 1123.97 | 11-FEB-15:50 | 21.42 | 15.12 |
March | 0.682422E+10 | 27586.73 | 02-MAR-08:62 | 27.00 | 17.55 | 0.740243E+09 | 1123.99 | 18-MAR-14:09 | 25.17 | 17.15 |
April | 0.830864E+10 | 29139.31 | 29-APR-07:02 | 27.25 | 16.62 | 0.706019E+09 | 1124.01 | 15-APR-14:00 | 27.25 | 16.62 |
May | 0.116311E+11 | 30445.52 | 11-MAY-07:01 | 30.33 | 16.47 | 0.730165E+09 | 1123.87 | 06-MAY-14:50 | 30.33 | 16.47 |
June | 0.123609E+11 | 28465.07 | 01-JUN-07:01 | 30.17 | 21.35 | 0.716088E+09 | 1124.02 | 10-JUN-14:09 | 37.00 | 27.58 |
July | 0.139093E+11 | 31305.73 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720818E+09 | 1124.01 | 01-JUL-14:09 | 32.82 | 19.26 |
August | 0.146748E+11 | 25747.35 | 16-AUG-07:01 | 33.67 | 25.11 | 0.741292E+09 | 1124.01 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.127097E+11 | 24950.62 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706545E+09 | 1124.02 | 09-SEP-14:00 | 27.00 | 17.98 |
October | 0.115518E+11 | 29289.17 | 20-OCT-07:02 | 23.25 | 15.43 | 0.719084E+09 | 1124.02 | 07-OCT-14:09 | 23.25 | 15.43 |
November | 0.866450E+10 | 28851.45 | 19-NOV-09:02 | 25.40 | 16.09 | 0.691947E+09 | 1124.00 | 25-NOV-15:00 | 26.30 | 18.79 |
December | 0.584761E+10 | 24919.00 | 12-DEC-08:62 | 23.17 | 17.37 | 0.719119E+09 | 1124.02 | 02-DEC-15:50 | 23.17 | 17.37 |
Annual Sum or Average | 0.116114E+12 | 0.856229E+10 | ||||||||
Minimum of Months | 0.459964E+10 | 10990.63 | 21.17 | 15.43 | 0.653426E+09 | 1123.87 | 21.42 | 15.12 | ||
Maximum of Months | 0.146748E+11 | 31305.73 | 33.67 | 25.11 | 0.741292E+09 | 1124.02 | 37.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454005E+10 | 10706.51 | 29-JAN-09:03 | 23.22 | 19.02 | 0.717524E+09 | 1123.99 | 28-JAN-15:00 | 23.22 | 19.02 |
February | 0.497342E+10 | 17157.09 | 06-FEB-08:62 | 21.17 | 17.80 | 0.653418E+09 | 1123.97 | 11-FEB-15:50 | 21.42 | 15.12 |
March | 0.675649E+10 | 27469.46 | 02-MAR-08:62 | 27.00 | 17.55 | 0.740236E+09 | 1123.99 | 18-MAR-14:09 | 25.17 | 17.15 |
April | 0.824444E+10 | 29018.97 | 29-APR-07:02 | 27.25 | 16.62 | 0.706010E+09 | 1124.02 | 15-APR-14:00 | 27.25 | 16.62 |
May | 0.115650E+11 | 30324.25 | 11-MAY-07:01 | 30.33 | 16.47 | 0.730161E+09 | 1123.87 | 06-MAY-14:00 | 30.33 | 16.47 |
June | 0.122963E+11 | 28342.12 | 01-JUN-07:01 | 30.17 | 21.35 | 0.716086E+09 | 1124.02 | 10-JUN-14:09 | 37.00 | 27.58 |
July | 0.138471E+11 | 31184.50 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720816E+09 | 1124.01 | 01-JUL-14:09 | 32.82 | 19.26 |
August | 0.146091E+11 | 25636.18 | 16-AUG-07:01 | 33.67 | 25.11 | 0.741290E+09 | 1124.01 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.126496E+11 | 24843.21 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706542E+09 | 1124.02 | 09-SEP-14:00 | 27.00 | 17.98 |
October | 0.114915E+11 | 29176.44 | 20-OCT-07:02 | 23.25 | 15.43 | 0.719079E+09 | 1124.02 | 07-OCT-14:09 | 23.25 | 15.43 |
November | 0.860646E+10 | 28739.90 | 19-NOV-09:02 | 25.40 | 16.09 | 0.691940E+09 | 1124.00 | 25-NOV-15:00 | 26.30 | 18.79 |
December | 0.578879E+10 | 24818.41 | 12-DEC-08:62 | 23.17 | 17.37 | 0.719110E+09 | 1124.01 | 02-DEC-15:39 | 23.17 | 17.37 |
Annual Sum or Average | 0.115368E+12 | 0.856221E+10 | ||||||||
Minimum of Months | 0.454005E+10 | 10706.51 | 21.17 | 15.43 | 0.653418E+09 | 1123.87 | 21.42 | 15.12 | ||
Maximum of Months | 0.146091E+11 | 31184.50 | 33.67 | 25.11 | 0.741290E+09 | 1124.02 | 37.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450069E+10 | 10340.78 | 29-JAN-09:03 | 23.22 | 19.02 | 0.717512E+09 | 1123.99 | 28-JAN-15:00 | 23.22 | 19.02 |
February | 0.493799E+10 | 16783.06 | 06-FEB-08:62 | 21.17 | 17.80 | 0.653418E+09 | 1123.97 | 11-FEB-15:50 | 21.42 | 15.12 |
March | 0.672895E+10 | 27582.91 | 02-MAR-08:62 | 27.00 | 17.55 | 0.740239E+09 | 1123.99 | 18-MAR-14:09 | 25.17 | 17.15 |
April | 0.825833E+10 | 29157.04 | 29-APR-07:02 | 27.25 | 16.62 | 0.706017E+09 | 1124.02 | 15-APR-14:00 | 27.25 | 16.62 |
May | 0.116599E+11 | 30504.13 | 11-MAY-07:01 | 30.33 | 16.47 | 0.730167E+09 | 1123.87 | 06-MAY-14:50 | 30.33 | 16.47 |
June | 0.124202E+11 | 28544.64 | 01-JUN-07:01 | 30.17 | 21.35 | 0.716090E+09 | 1124.02 | 10-JUN-14:09 | 37.00 | 27.58 |
July | 0.140106E+11 | 31423.40 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720821E+09 | 1124.01 | 01-JUL-14:09 | 32.82 | 19.26 |
August | 0.148053E+11 | 25900.97 | 16-AUG-07:01 | 33.67 | 25.11 | 0.741294E+09 | 1124.01 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.128058E+11 | 25056.33 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706549E+09 | 1124.02 | 09-SEP-14:00 | 27.00 | 17.98 |
October | 0.116201E+11 | 29351.75 | 20-OCT-07:02 | 23.25 | 15.43 | 0.719089E+09 | 1124.02 | 07-OCT-14:09 | 23.25 | 15.43 |
November | 0.867391E+10 | 28875.48 | 19-NOV-09:02 | 25.40 | 16.09 | 0.691949E+09 | 1124.00 | 25-NOV-15:00 | 26.30 | 18.79 |
December | 0.578386E+10 | 24924.70 | 12-DEC-08:62 | 23.17 | 17.37 | 0.719114E+09 | 1124.02 | 02-DEC-15:50 | 23.17 | 17.37 |
Annual Sum or Average | 0.116206E+12 | 0.856226E+10 | ||||||||
Minimum of Months | 0.450069E+10 | 10340.78 | 21.17 | 15.43 | 0.653418E+09 | 1123.87 | 21.42 | 15.12 | ||
Maximum of Months | 0.148053E+11 | 31423.40 | 33.67 | 25.11 | 0.741294E+09 | 1124.02 | 37.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.467179E+10 | 9115.78 | 29-JAN-09:03 | 23.22 | 19.02 | 0.717552E+09 | 1123.99 | 28-JAN-15:00 | 23.22 | 19.02 |
February | 0.511981E+10 | 13884.99 | 06-FEB-08:62 | 21.17 | 17.80 | 0.653478E+09 | 1123.97 | 11-FEB-15:00 | 21.30 | 15.15 |
March | 0.706435E+10 | 31643.07 | 02-MAR-08:62 | 27.00 | 17.55 | 0.740306E+09 | 1124.00 | 18-MAR-14:09 | 25.17 | 17.15 |
April | 0.897226E+10 | 30436.21 | 29-APR-07:02 | 27.25 | 16.62 | 0.706151E+09 | 1124.02 | 15-APR-14:00 | 27.25 | 16.62 |
May | 0.131059E+11 | 33612.10 | 11-MAY-07:01 | 30.33 | 16.47 | 0.730233E+09 | 1123.88 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.140860E+11 | 30174.39 | 01-JUN-07:01 | 30.17 | 21.35 | 0.716137E+09 | 1124.02 | 10-JUN-14:09 | 37.00 | 27.58 |
July | 0.160175E+11 | 34805.89 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720880E+09 | 1124.01 | 01-JUL-14:00 | 32.82 | 19.26 |
August | 0.171340E+11 | 28482.82 | 06-AUG-08:61 | 36.17 | 23.08 | 0.741334E+09 | 1124.01 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.146900E+11 | 27063.08 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706629E+09 | 1124.03 | 09-SEP-14:00 | 27.00 | 17.98 |
October | 0.132013E+11 | 31377.46 | 20-OCT-07:02 | 23.25 | 15.43 | 0.719203E+09 | 1124.02 | 07-OCT-14:09 | 23.25 | 15.43 |
November | 0.968303E+10 | 30535.20 | 19-NOV-09:02 | 25.40 | 16.09 | 0.692083E+09 | 1124.00 | 25-NOV-15:00 | 26.30 | 18.79 |
December | 0.614989E+10 | 25025.02 | 12-DEC-08:62 | 23.17 | 17.37 | 0.719219E+09 | 1124.02 | 02-DEC-15:50 | 23.17 | 17.37 |
Annual Sum or Average | 0.129896E+12 | 0.856320E+10 | ||||||||
Minimum of Months | 0.467179E+10 | 9115.78 | 21.17 | 15.43 | 0.653478E+09 | 1123.88 | 21.30 | 15.15 | ||
Maximum of Months | 0.171340E+11 | 34805.89 | 36.17 | 23.08 | 0.741334E+09 | 1124.03 | 37.00 | 27.58 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21320824.64 | 5367.07 | 29-JAN-08:07 | 22.17 |
February | 27281099.56 | 6406.06 | 09-FEB-08:05 | 22.17 |
March | 38524349.83 | 8254.57 | 28-MAR-07:04 | 24.33 |
April | 66274053.26 | 9778.13 | 28-APR-07:04 | 27.25 |
May | 46346916.77 | 10514.00 | 11-MAY-07:04 | 30.33 |
June | 30676056.09 | 10744.90 | 11-JUN-07:04 | 31.92 |
July | 17515075.89 | 11013.07 | 11-JUL-07:05 | 33.42 |
August | 18531193.03 | 10743.96 | 19-AUG-07:05 | 32.75 |
September | 26204678.07 | 10932.26 | 02-SEP-07:04 | 32.25 |
October | 37654817.05 | 9046.76 | 04-OCT-07:04 | 26.75 |
November | 58637457.13 | 7536.18 | 09-NOV-08:04 | 24.50 |
December | 31819474.47 | 7223.32 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.420786E+09 | |||
Minimum of Months | 17515075.89 | 5367.07 | 22.17 | |
Maximum of Months | 66274053.26 | 11013.07 | 33.42 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8509338.03 | 2921.57 | 29-JAN-08:07 | 22.17 |
February | 12329732.34 | 3456.28 | 09-FEB-08:05 | 22.17 |
March | 19020829.83 | 4352.01 | 28-MAR-07:04 | 24.33 |
April | 34341143.01 | 5125.45 | 28-APR-07:04 | 27.25 |
May | 19717255.47 | 5312.95 | 13-MAY-07:04 | 29.17 |
June | 14579365.47 | 5518.14 | 01-JUN-07:04 | 30.17 |
July | 8241103.15 | 5547.48 | 23-JUL-07:05 | 33.00 |
August | 9875833.27 | 5926.20 | 06-AUG-07:05 | 35.08 |
September | 13386341.94 | 5328.58 | 02-SEP-07:04 | 32.25 |
October | 16603530.00 | 4773.74 | 06-OCT-07:04 | 27.43 |
November | 32144884.57 | 4258.92 | 09-NOV-08:04 | 24.50 |
December | 17226763.56 | 3949.54 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.205976E+09 | |||
Minimum of Months | 8241103.15 | 2921.57 | 22.17 | |
Maximum of Months | 34341143.01 | 5926.20 | 35.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125537E+09 | 2919.83 | 29-JAN-08:07 | 22.17 |
February | 0.136816E+09 | 3837.69 | 05-FEB-17:11 | 31.00 |
March | 0.205899E+09 | 4230.59 | 28-MAR-06:03 | 24.00 |
April | 0.284327E+09 | 4456.13 | 29-APR-17:11 | 33.33 |
May | 0.325217E+09 | 6358.66 | 31-MAY-19:11 | 41.60 |
June | 0.304268E+09 | 5575.68 | 09-JUN-19:11 | 38.00 |
July | 0.279264E+09 | 6211.37 | 21-JUL-19:11 | 41.00 |
August | 0.286155E+09 | 6182.88 | 10-AUG-19:11 | 40.73 |
September | 0.293140E+09 | 5893.43 | 04-SEP-16:01 | 40.58 |
October | 0.310789E+09 | 4946.26 | 09-OCT-16:01 | 36.67 |
November | 0.261426E+09 | 3949.88 | 19-NOV-08:04 | 22.75 |
December | 0.166939E+09 | 3781.79 | 12-DEC-07:04 | 23.17 |
Annual Sum or Average | 0.297978E+10 | |||
Minimum of Months | 0.125537E+09 | 2919.83 | 22.17 | |
Maximum of Months | 0.325217E+09 | 6358.66 | 41.60 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127197E+09 | 2908.38 | 29-JAN-08:07 | 22.17 |
February | 0.137862E+09 | 3841.85 | 05-FEB-17:11 | 31.00 |
March | 0.206081E+09 | 4221.76 | 28-MAR-06:03 | 24.00 |
April | 0.282813E+09 | 4458.97 | 29-APR-17:11 | 33.33 |
May | 0.321070E+09 | 6360.92 | 31-MAY-19:11 | 41.60 |
June | 0.298774E+09 | 5578.53 | 09-JUN-19:11 | 38.00 |
July | 0.275309E+09 | 6213.69 | 21-JUL-19:11 | 41.00 |
August | 0.280353E+09 | 6185.73 | 10-AUG-19:11 | 40.73 |
September | 0.289450E+09 | 5888.71 | 04-SEP-16:01 | 40.58 |
October | 0.307687E+09 | 4942.93 | 09-OCT-16:01 | 36.67 |
November | 0.259938E+09 | 3948.93 | 19-NOV-08:04 | 22.75 |
December | 0.167436E+09 | 3785.78 | 12-DEC-07:04 | 23.17 |
Annual Sum or Average | 0.295397E+10 | |||
Minimum of Months | 0.127197E+09 | 2908.38 | 22.17 | |
Maximum of Months | 0.321070E+09 | 6360.92 | 41.60 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130975E+09 | 2859.55 | 29-JAN-08:07 | 22.17 |
February | 0.139850E+09 | 3841.37 | 05-FEB-17:11 | 31.00 |
March | 0.207608E+09 | 4229.56 | 28-MAR-06:03 | 24.00 |
April | 0.284590E+09 | 4458.73 | 29-APR-17:11 | 33.33 |
May | 0.326230E+09 | 6360.66 | 31-MAY-19:11 | 41.60 |
June | 0.305234E+09 | 5578.68 | 09-JUN-19:11 | 38.00 |
July | 0.279857E+09 | 6213.56 | 21-JUL-19:11 | 41.00 |
August | 0.286595E+09 | 6185.63 | 10-AUG-19:11 | 40.73 |
September | 0.294229E+09 | 5886.18 | 04-SEP-16:01 | 40.58 |
October | 0.312281E+09 | 4941.40 | 09-OCT-16:01 | 36.67 |
November | 0.262237E+09 | 3945.19 | 19-NOV-08:04 | 22.75 |
December | 0.168960E+09 | 3803.38 | 12-DEC-07:04 | 23.17 |
Annual Sum or Average | 0.299864E+10 | |||
Minimum of Months | 0.130975E+09 | 2859.55 | 22.17 | |
Maximum of Months | 0.326230E+09 | 6360.66 | 41.60 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117407E+09 | 5681.21 | 29-JAN-09:07 | 23.22 |
February | 0.116150E+09 | 7199.85 | 05-FEB-17:11 | 31.00 |
March | 0.130240E+09 | 8103.96 | 27-MAR-07:05 | 26.50 |
April | 0.233477E+09 | 8968.74 | 29-APR-07:04 | 27.25 |
May | 0.178222E+09 | 10203.11 | 11-MAY-07:04 | 30.33 |
June | 0.128190E+09 | 10012.62 | 16-JUN-07:04 | 29.50 |
July | 0.156399E+09 | 11371.83 | 29-JUL-17:11 | 40.00 |
August | 0.110381E+09 | 11697.87 | 05-AUG-17:01 | 40.83 |
September | 0.158813E+09 | 11481.01 | 04-SEP-16:01 | 40.58 |
October | 0.189069E+09 | 9583.49 | 09-OCT-16:01 | 36.67 |
November | 0.190729E+09 | 7420.53 | 20-NOV-08:05 | 26.17 |
December | 0.146551E+09 | 6757.47 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.185563E+10 | |||
Minimum of Months | 0.110381E+09 | 5681.21 | 23.17 | |
Maximum of Months | 0.233477E+09 | 11697.87 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74877527.58 | 2930.41 | 29-JAN-09:07 | 23.22 |
February | 68847949.40 | 3747.58 | 05-FEB-17:11 | 31.00 |
March | 69345223.66 | 4189.88 | 27-MAR-07:05 | 26.50 |
April | 0.121336E+09 | 4800.26 | 29-APR-07:04 | 27.25 |
May | 91294124.14 | 5123.17 | 20-MAY-17:11 | 36.67 |
June | 69208690.93 | 5461.21 | 29-JUN-07:05 | 33.50 |
July | 80195727.12 | 5862.21 | 29-JUL-17:11 | 40.00 |
August | 60031973.92 | 6010.27 | 05-AUG-17:11 | 40.67 |
September | 86856198.26 | 5837.21 | 04-SEP-16:01 | 40.58 |
October | 98047628.19 | 4894.96 | 09-OCT-16:01 | 36.67 |
November | 99127048.25 | 3924.86 | 09-NOV-08:04 | 24.50 |
December | 79844304.51 | 3669.88 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.999013E+09 | |||
Minimum of Months | 60031973.92 | 2930.41 | 23.17 | |
Maximum of Months | 0.121336E+09 | 6010.27 | 40.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76234765.00 | 2900.39 | 29-JAN-09:07 | 23.22 |
February | 69276611.97 | 3741.40 | 05-FEB-17:11 | 31.00 |
March | 70016793.88 | 4160.47 | 27-MAR-07:05 | 26.50 |
April | 0.121451E+09 | 4786.75 | 29-APR-07:04 | 27.25 |
May | 91995393.22 | 5117.03 | 20-MAY-17:11 | 36.67 |
June | 69839707.69 | 5451.52 | 29-JUN-07:05 | 33.50 |
July | 81412531.22 | 5856.30 | 29-JUL-17:11 | 40.00 |
August | 60432374.06 | 6004.36 | 05-AUG-17:11 | 40.67 |
September | 87529055.23 | 5834.35 | 04-SEP-16:01 | 40.58 |
October | 98580728.04 | 4892.02 | 09-OCT-16:01 | 36.67 |
November | 99422968.56 | 3918.82 | 09-NOV-08:04 | 24.50 |
December | 79835009.25 | 3656.52 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.100603E+10 | |||
Minimum of Months | 60432374.06 | 2900.39 | 23.17 | |
Maximum of Months | 0.121451E+09 | 6004.36 | 40.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79373927.45 | 2887.09 | 29-JAN-09:07 | 23.22 |
February | 73139357.97 | 3753.26 | 05-FEB-17:11 | 31.00 |
March | 72803771.57 | 4165.54 | 27-MAR-07:05 | 26.50 |
April | 0.121138E+09 | 4819.21 | 29-APR-07:04 | 27.25 |
May | 91187472.87 | 5126.80 | 20-MAY-17:11 | 36.67 |
June | 68947852.49 | 5465.70 | 29-JUN-07:05 | 33.50 |
July | 79874304.52 | 5864.50 | 29-JUL-17:11 | 40.00 |
August | 59050929.20 | 6011.40 | 05-AUG-17:11 | 40.67 |
September | 85483215.37 | 5834.85 | 04-SEP-16:01 | 40.58 |
October | 97399785.46 | 4893.59 | 09-OCT-16:01 | 36.67 |
November | 99224480.05 | 3952.05 | 09-NOV-08:04 | 24.50 |
December | 81432996.62 | 3683.36 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.100906E+10 | |||
Minimum of Months | 59050929.20 | 2887.09 | 23.17 | |
Maximum of Months | 0.121138E+09 | 6011.40 | 40.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114810E+09 | 2683.38 | 29-JAN-17:12 | 24.67 |
February | 94812246.77 | 4018.90 | 05-FEB-17:11 | 31.00 |
March | 93916483.56 | 5138.95 | 02-MAR-08:03 | 27.00 |
April | 0.115883E+09 | 5348.17 | 29-APR-07:04 | 27.25 |
May | 81656388.08 | 5635.72 | 12-MAY-07:04 | 28.58 |
June | 59071068.49 | 5792.69 | 01-JUN-07:04 | 30.17 |
July | 69005436.13 | 6101.43 | 29-JUL-17:11 | 40.00 |
August | 48338458.73 | 6239.58 | 05-AUG-17:11 | 40.67 |
September | 69793313.79 | 5917.36 | 04-SEP-16:01 | 40.58 |
October | 85551171.06 | 5046.46 | 09-OCT-16:11 | 36.53 |
November | 99416679.51 | 4441.94 | 09-NOV-08:04 | 24.50 |
December | 94665368.98 | 4088.85 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.102692E+10 | |||
Minimum of Months | 48338458.73 | 2683.38 | 23.17 | |
Maximum of Months | 0.115883E+09 | 6239.58 | 40.67 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117009E+11 | 7157.48 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.105780E+11 | 7157.48 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.117131E+11 | 7157.48 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.113388E+11 | 7157.48 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.117009E+11 | 7157.48 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.113388E+11 | 7157.48 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.117131E+11 | 7157.48 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.117009E+11 | 7157.48 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.113510E+11 | 7157.48 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.117009E+11 | 7157.48 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.113022E+11 | 7157.48 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.117253E+11 | 7157.48 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.137864E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.105780E+11 | 7157.48 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.117253E+11 | 7157.48 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.671043E+10 | 4104.79 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.606645E+10 | 4104.79 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.671742E+10 | 4104.79 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.650277E+10 | 4104.79 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.671043E+10 | 4104.79 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.650277E+10 | 4104.79 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.671742E+10 | 4104.79 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.671043E+10 | 4104.79 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.650977E+10 | 4104.79 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.671043E+10 | 4104.79 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.648177E+10 | 4104.79 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.672442E+10 | 4104.79 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.790645E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.606645E+10 | 4104.79 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.672442E+10 | 4104.79 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497151E+10 | 3822.63 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.450217E+10 | 3822.63 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.507580E+10 | 3822.63 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.482375E+10 | 3822.63 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.502365E+10 | 3822.63 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.490197E+10 | 3822.63 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.494543E+10 | 3822.63 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.507580E+10 | 3822.63 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.482375E+10 | 3822.63 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.497151E+10 | 3822.63 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.482375E+10 | 3822.63 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.494543E+10 | 3822.63 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.588845E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.450217E+10 | 3822.63 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.507580E+10 | 3822.63 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497151E+10 | 3822.63 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.450217E+10 | 3822.63 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.507580E+10 | 3822.63 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.482375E+10 | 3822.63 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.502365E+10 | 3822.63 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.490197E+10 | 3822.63 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.494543E+10 | 3822.63 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.507580E+10 | 3822.63 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.482375E+10 | 3822.63 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.497151E+10 | 3822.63 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.482375E+10 | 3822.63 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.494543E+10 | 3822.63 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.588845E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.450217E+10 | 3822.63 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.507580E+10 | 3822.63 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.497151E+10 | 3822.63 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.450217E+10 | 3822.63 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.507580E+10 | 3822.63 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.482375E+10 | 3822.63 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.502365E+10 | 3822.63 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.490197E+10 | 3822.63 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.494543E+10 | 3822.63 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.507580E+10 | 3822.63 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.482375E+10 | 3822.63 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.497151E+10 | 3822.63 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.482375E+10 | 3822.63 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.494543E+10 | 3822.63 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.588845E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.450217E+10 | 3822.63 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.507580E+10 | 3822.63 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.626384E+10 | 5242.46 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.567381E+10 | 5242.46 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.640687E+10 | 5242.46 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.607908E+10 | 5242.46 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.633536E+10 | 5242.46 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.618636E+10 | 5242.46 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.622808E+10 | 5242.46 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.640687E+10 | 5242.46 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.607908E+10 | 5242.46 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.626384E+10 | 5242.46 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.607908E+10 | 5242.46 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.622808E+10 | 5242.46 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.742303E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.567381E+10 | 5242.46 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.640687E+10 | 5242.46 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.319241E+10 | 2671.87 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.289170E+10 | 2671.87 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.326531E+10 | 2671.87 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.309825E+10 | 2671.87 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.322886E+10 | 2671.87 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.315292E+10 | 2671.87 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.317418E+10 | 2671.87 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.326531E+10 | 2671.87 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.309825E+10 | 2671.87 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.319241E+10 | 2671.87 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.309825E+10 | 2671.87 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.317418E+10 | 2671.87 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.378320E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.289170E+10 | 2671.87 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.326531E+10 | 2671.87 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.319241E+10 | 2671.87 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.289170E+10 | 2671.87 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.326531E+10 | 2671.87 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.309825E+10 | 2671.87 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.322886E+10 | 2671.87 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.315292E+10 | 2671.87 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.317418E+10 | 2671.87 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.326531E+10 | 2671.87 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.309825E+10 | 2671.87 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.319241E+10 | 2671.87 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.309825E+10 | 2671.87 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.317418E+10 | 2671.87 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.378320E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.289170E+10 | 2671.87 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.326531E+10 | 2671.87 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.319241E+10 | 2671.87 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.289170E+10 | 2671.87 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.326531E+10 | 2671.87 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.309825E+10 | 2671.87 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.322886E+10 | 2671.87 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.315292E+10 | 2671.87 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.317418E+10 | 2671.87 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.326531E+10 | 2671.87 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.309825E+10 | 2671.87 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.319241E+10 | 2671.87 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.309825E+10 | 2671.87 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.317418E+10 | 2671.87 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.378320E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.289170E+10 | 2671.87 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.326531E+10 | 2671.87 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.319241E+10 | 2671.87 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.289170E+10 | 2671.87 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.326531E+10 | 2671.87 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.309825E+10 | 2671.87 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.322886E+10 | 2671.87 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.315292E+10 | 2671.87 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.317418E+10 | 2671.87 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.326531E+10 | 2671.87 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.309825E+10 | 2671.87 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.319241E+10 | 2671.87 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.309825E+10 | 2671.87 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.317418E+10 | 2671.87 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.378320E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.289170E+10 | 2671.87 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.326531E+10 | 2671.87 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.117009E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75434877.86 | 0.841500E+09 |
February | 0.305697E+10 | 0.105780E+11 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402007E+09 | 0.603875E+09 |
March | 0.335708E+10 | 0.117131E+11 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104609E+10 | 0.264277E+09 |
April | 0.327081E+10 | 0.113388E+11 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231204E+10 | 76671512.10 |
May | 0.336680E+10 | 0.117009E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410042E+10 | 10667952.21 |
June | 0.325380E+10 | 0.113388E+11 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450046E+10 | 2894113.90 |
July | 0.339353E+10 | 0.117131E+11 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523575E+10 | 0.00 |
August | 0.334857E+10 | 0.117009E+11 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527511E+10 | 0.00 |
September | 0.327932E+10 | 0.113510E+11 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430030E+10 | 2855362.63 |
October | 0.338624E+10 | 0.117009E+11 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335891E+10 | 20302966.27 |
November | 0.327446E+10 | 0.113022E+11 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177381E+10 | 80453285.08 |
December | 0.340325E+10 | 0.117253E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396433E+09 | 0.447576E+09 |
Annual Sum or Average | 0.397770E+11 | 0.137864E+12 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327768E+11 | 0.235107E+10 |
Minimum of Months | 0.305697E+10 | 0.105780E+11 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75434877.86 | 0.00 |
Maximum of Months | 0.340325E+10 | 0.117253E+11 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527511E+10 | 0.841500E+09 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.671043E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42454864.46 | 0.423155E+09 |
February | 0.152844E+10 | 0.606645E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225273E+09 | 0.291465E+09 |
March | 0.167849E+10 | 0.671742E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582824E+09 | 0.120438E+09 |
April | 0.163536E+10 | 0.650277E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128973E+10 | 26545317.30 |
May | 0.168335E+10 | 0.671043E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227514E+10 | 3356511.49 |
June | 0.162685E+10 | 0.650277E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248024E+10 | 893152.58 |
July | 0.169671E+10 | 0.671742E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287420E+10 | 0.00 |
August | 0.167424E+10 | 0.671043E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289455E+10 | 0.00 |
September | 0.163961E+10 | 0.650977E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237809E+10 | 744917.19 |
October | 0.169307E+10 | 0.671043E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187265E+10 | 5763246.87 |
November | 0.163718E+10 | 0.648177E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992448E+09 | 25753772.35 |
December | 0.170157E+10 | 0.672442E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223020E+09 | 0.211089E+09 |
Annual Sum or Average | 0.198880E+11 | 0.790645E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181306E+11 | 0.110920E+10 |
Minimum of Months | 0.152844E+10 | 0.606645E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42454864.46 | 0.00 |
Maximum of Months | 0.170157E+10 | 0.672442E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289455E+10 | 0.423155E+09 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41968417.26 | 0.455986E+09 |
February | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219761E+09 | 0.321359E+09 |
March | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573931E+09 | 0.140558E+09 |
April | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125873E+10 | 32297119.83 |
May | 0.102058E+10 | 0.502365E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224361E+10 | 3817083.69 |
June | 0.998711E+09 | 0.490197E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245364E+10 | 989123.27 |
July | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283916E+10 | 0.00 |
August | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287166E+10 | 0.00 |
September | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234440E+10 | 953444.61 |
October | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183260E+10 | 6677825.77 |
November | 0.973196E+09 | 0.482375E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965447E+09 | 35210779.84 |
December | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218305E+09 | 0.241499E+09 |
Annual Sum or Average | 0.119700E+11 | 0.588845E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178632E+11 | 0.123935E+10 |
Minimum of Months | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41968417.26 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287166E+10 | 0.455986E+09 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41969039.76 | 0.455485E+09 |
February | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219747E+09 | 0.321200E+09 |
March | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573861E+09 | 0.140677E+09 |
April | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125841E+10 | 32753226.65 |
May | 0.102058E+10 | 0.502365E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224235E+10 | 4102304.75 |
June | 0.998711E+09 | 0.490197E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245177E+10 | 1098120.64 |
July | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283654E+10 | 35.19 |
August | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286955E+10 | 0.00 |
September | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234260E+10 | 1083647.53 |
October | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183157E+10 | 7201630.39 |
November | 0.973196E+09 | 0.482375E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965237E+09 | 35763475.86 |
December | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218305E+09 | 0.241479E+09 |
Annual Sum or Average | 0.119700E+11 | 0.588845E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178519E+11 | 0.124084E+10 |
Minimum of Months | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41969039.76 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286955E+10 | 0.455485E+09 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41969631.12 | 0.454341E+09 |
February | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219768E+09 | 0.320134E+09 |
March | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573944E+09 | 0.139787E+09 |
April | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125858E+10 | 32178644.73 |
May | 0.102058E+10 | 0.502365E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224270E+10 | 3994745.71 |
June | 0.998711E+09 | 0.490197E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245233E+10 | 1043365.78 |
July | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283700E+10 | 75.20 |
August | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287010E+10 | 0.00 |
September | 0.984131E+09 | 0.482375E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234302E+10 | 1035363.10 |
October | 0.100722E+10 | 0.497151E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183191E+10 | 7008791.50 |
November | 0.973196E+09 | 0.482375E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965382E+09 | 35182843.85 |
December | 0.100600E+10 | 0.494543E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218311E+09 | 0.240545E+09 |
Annual Sum or Average | 0.119700E+11 | 0.588845E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178550E+11 | 0.123525E+10 |
Minimum of Months | 0.914877E+09 | 0.450217E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41969631.12 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.507580E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287010E+10 | 0.454341E+09 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.626384E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73596645.00 | 0.808006E+09 |
February | 0.313522E+10 | 0.567381E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385956E+09 | 0.573409E+09 |
March | 0.355148E+10 | 0.640687E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100967E+10 | 0.250250E+09 |
April | 0.338259E+10 | 0.607908E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221406E+10 | 60719872.32 |
May | 0.349753E+10 | 0.633536E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394600E+10 | 7740542.03 |
June | 0.343071E+10 | 0.618636E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432405E+10 | 2385133.20 |
July | 0.344942E+10 | 0.622808E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500256E+10 | 0.00 |
August | 0.355148E+10 | 0.640687E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506373E+10 | 0.00 |
September | 0.338259E+10 | 0.607908E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412544E+10 | 2156644.32 |
October | 0.344359E+10 | 0.626384E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322182E+10 | 15771744.47 |
November | 0.331698E+10 | 0.607908E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169777E+10 | 67708638.44 |
December | 0.344942E+10 | 0.622808E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382982E+09 | 0.432450E+09 |
Annual Sum or Average | 0.410346E+11 | 0.742303E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314476E+11 | 0.222060E+10 |
Minimum of Months | 0.313522E+10 | 0.567381E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73596645.00 | 0.00 |
Maximum of Months | 0.355148E+10 | 0.640687E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506373E+10 | 0.808006E+09 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41973325.47 | 0.450131E+09 |
February | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220037E+09 | 0.315981E+09 |
March | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575192E+09 | 0.135925E+09 |
April | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126161E+10 | 30596962.46 |
May | 0.174872E+10 | 0.322886E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224625E+10 | 3623301.03 |
June | 0.171530E+10 | 0.315292E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245927E+10 | 1097409.76 |
July | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284296E+10 | 0.00 |
August | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287736E+10 | 0.00 |
September | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234749E+10 | 957160.81 |
October | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183566E+10 | 7385719.51 |
November | 0.165844E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967694E+09 | 33892690.62 |
December | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218406E+09 | 0.237556E+09 |
Annual Sum or Average | 0.205167E+11 | 0.378320E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178939E+11 | 0.121715E+10 |
Minimum of Months | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41973325.47 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287736E+10 | 0.450131E+09 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41973970.92 | 0.449568E+09 |
February | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220058E+09 | 0.315437E+09 |
March | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575254E+09 | 0.135518E+09 |
April | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126176E+10 | 30340769.61 |
May | 0.174872E+10 | 0.322886E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224649E+10 | 3558799.07 |
June | 0.171530E+10 | 0.315292E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245960E+10 | 1071074.26 |
July | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284333E+10 | 0.00 |
August | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287767E+10 | 0.00 |
September | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234778E+10 | 935282.33 |
October | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183587E+10 | 7277107.23 |
November | 0.165844E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967798E+09 | 33616960.65 |
December | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218411E+09 | 0.237105E+09 |
Annual Sum or Average | 0.205167E+11 | 0.378320E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178960E+11 | 0.121443E+10 |
Minimum of Months | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41973970.92 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287767E+10 | 0.449568E+09 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41973908.20 | 0.448983E+09 |
February | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220050E+09 | 0.314901E+09 |
March | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575241E+09 | 0.135175E+09 |
April | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126163E+10 | 30279550.26 |
May | 0.174872E+10 | 0.322886E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224604E+10 | 3626527.03 |
June | 0.171530E+10 | 0.315292E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245884E+10 | 1113338.76 |
July | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284209E+10 | 0.00 |
August | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287646E+10 | 0.00 |
September | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234678E+10 | 1004363.47 |
October | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183533E+10 | 7583718.81 |
November | 0.165844E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967640E+09 | 33925720.31 |
December | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218407E+09 | 0.237019E+09 |
Annual Sum or Average | 0.205167E+11 | 0.378320E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178905E+11 | 0.121361E+10 |
Minimum of Months | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41973908.20 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287646E+10 | 0.448983E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42958131.23 | 0.552478E+09 |
February | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226281E+09 | 0.412978E+09 |
March | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597660E+09 | 0.188753E+09 |
April | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130652E+10 | 58670238.98 |
May | 0.174872E+10 | 0.322886E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235256E+10 | 8498251.75 |
June | 0.171530E+10 | 0.315292E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260208E+10 | 2480847.11 |
July | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302920E+10 | 1044.59 |
August | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306697E+10 | 0.00 |
September | 0.169125E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246764E+10 | 3055649.24 |
October | 0.172174E+10 | 0.319241E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190352E+10 | 20249689.49 |
November | 0.165844E+10 | 0.309825E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997315E+09 | 72729464.06 |
December | 0.172466E+10 | 0.317418E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223458E+09 | 0.320913E+09 |
Annual Sum or Average | 0.205167E+11 | 0.378320E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188161E+11 | 0.164081E+10 |
Minimum of Months | 0.156756E+10 | 0.289170E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42958131.23 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.326531E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306697E+10 | 0.552478E+09 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 7157.48 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.45 | 23-JAN-14:00 | 2422.95 | 18-JAN-17:00 |
February | 4050.04 | 03-FEB-13:09 | 7157.48 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4040.67 | 06-FEB-15:00 | 2980.52 | 20-FEB-16:00 |
March | 4050.04 | 03-MAR-13:09 | 7157.48 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6493.18 | 27-MAR-11:10 | 2863.31 | 05-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 7157.48 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8034.01 | 28-APR-12:00 | 462.10 | 01-APR-07:05 |
May | 4050.04 | 05-MAY-12:09 | 7157.48 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7779.74 | 09-MAY-13:00 | 250.83 | 01-MAY-07:02 |
June | 4050.04 | 02-JUN-12:09 | 7157.48 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8426.90 | 12-JUN-12:00 | 206.27 | 22-JUN-08:00 |
July | 4050.04 | 01-JUL-12:09 | 7157.48 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9608.88 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 4050.04 | 04-AUG-12:09 | 7157.48 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9880.04 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 4050.04 | 01-SEP-12:09 | 7157.48 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7773.33 | 26-SEP-13:00 | 87.41 | 25-SEP-05:00 |
October | 4050.04 | 01-OCT-12:09 | 7157.48 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6298.30 | 09-OCT-12:00 | 251.29 | 29-OCT-07:02 |
November | 4050.04 | 03-NOV-12:09 | 7157.48 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4618.23 | 05-NOV-12:00 | 439.49 | 22-NOV-08:63 |
December | 4050.04 | 01-DEC-13:09 | 7157.48 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2845.16 | 10-DEC-12:10 | 2919.28 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 7157.48 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.45 | 0.00 | |||||
Maximum of Months | 4050.04 | 7157.48 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9880.04 | 2980.52 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 4104.79 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.92 | 23-JAN-14:00 | 1358.10 | 18-JAN-17:00 |
February | 2024.96 | 03-FEB-13:09 | 4104.79 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.86 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 03-MAR-13:09 | 4104.79 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1615.40 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 4104.79 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4554.04 | 28-APR-12:00 | 258.03 | 01-APR-07:05 |
May | 2024.96 | 05-MAY-12:09 | 4104.79 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.37 | 09-MAY-13:00 | 135.32 | 01-MAY-07:02 |
June | 2024.96 | 02-JUN-12:09 | 4104.79 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.69 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 4104.79 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.58 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 04-AUG-12:09 | 4104.79 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 01-SEP-12:09 | 4104.79 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.50 | 26-SEP-13:00 | 30.79 | 25-SEP-07:01 |
October | 2024.96 | 01-OCT-12:09 | 4104.79 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.70 | 09-OCT-12:00 | 135.97 | 29-OCT-07:02 |
November | 2024.96 | 03-NOV-12:09 | 4104.79 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2622.00 | 05-NOV-12:00 | 239.12 | 22-NOV-08:63 |
December | 2024.96 | 01-DEC-13:09 | 4104.79 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.93 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 4104.79 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.92 | 0.00 | |||||
Maximum of Months | 2024.96 | 4104.79 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3822.63 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.92 | 23-JAN-14:00 | 1626.46 | 15-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3822.63 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.87 | 06-FEB-15:00 | 1970.90 | 20-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3822.63 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 2004.40 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3822.63 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4554.04 | 28-APR-12:00 | 539.69 | 09-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 3822.63 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.37 | 09-MAY-13:00 | 111.48 | 01-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 3822.63 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.69 | 12-JUN-12:00 | 114.15 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 3822.63 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.58 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 3822.63 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 3822.63 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.50 | 26-SEP-13:00 | 49.49 | 24-SEP-07:01 |
October | 2024.96 | 07-OCT-12:09 | 3822.63 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.69 | 09-OCT-12:00 | 155.16 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 3822.63 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2622.00 | 05-NOV-12:00 | 596.93 | 23-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3822.63 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.93 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.92 | 0.00 | |||||
Maximum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 2004.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3822.63 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.92 | 23-JAN-14:00 | 1622.92 | 15-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3822.63 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.87 | 06-FEB-15:00 | 1966.32 | 20-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3822.63 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 2000.95 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3822.63 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4554.04 | 28-APR-12:00 | 547.59 | 09-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 3822.63 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.37 | 09-MAY-13:00 | 111.48 | 01-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 3822.63 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.69 | 12-JUN-12:00 | 114.15 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 3822.63 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.58 | 21-JUL-12:00 | 0.06 | 03-JUL-06:00 |
August | 2024.96 | 05-AUG-12:09 | 3822.63 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 3822.63 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.50 | 26-SEP-13:00 | 53.56 | 24-SEP-07:01 |
October | 2024.96 | 07-OCT-12:09 | 3822.63 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.69 | 09-OCT-12:00 | 158.44 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 3822.63 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2622.00 | 05-NOV-12:00 | 600.50 | 23-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3822.63 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.93 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.92 | 0.00 | |||||
Maximum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 2000.95 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3822.63 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.92 | 23-JAN-14:00 | 1613.60 | 15-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3822.63 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.87 | 06-FEB-15:00 | 1956.44 | 20-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3822.63 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1991.69 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3822.63 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4554.04 | 28-APR-12:00 | 541.47 | 09-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 3822.63 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.37 | 09-MAY-13:00 | 111.48 | 01-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 3822.63 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.69 | 12-JUN-12:00 | 114.15 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 3822.63 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.58 | 21-JUL-12:00 | 0.13 | 03-JUL-06:00 |
August | 2024.96 | 05-AUG-12:09 | 3822.63 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 3822.63 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.50 | 26-SEP-13:00 | 52.75 | 24-SEP-07:01 |
October | 2024.96 | 07-OCT-12:09 | 3822.63 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.69 | 09-OCT-12:00 | 157.21 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 3822.63 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2622.00 | 05-NOV-12:00 | 592.60 | 23-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3822.63 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.92 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.92 | 0.00 | |||||
Maximum of Months | 2024.96 | 3822.63 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 1991.69 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 5242.46 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.26 | 23-JAN-14:00 | 2695.23 | 15-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 5242.46 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3973.50 | 06-FEB-15:00 | 3291.11 | 20-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 5242.46 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6361.78 | 27-MAR-11:10 | 3359.53 | 05-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 5242.46 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7976.73 | 28-APR-12:00 | 865.46 | 09-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 5242.46 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7660.50 | 09-MAY-13:00 | 300.30 | 01-MAY-07:02 |
June | 5400.05 | 03-JUN-14:09 | 5242.46 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8344.22 | 12-JUN-12:00 | 200.65 | 22-JUN-08:00 |
July | 5400.05 | 01-JUL-14:09 | 5242.46 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9514.62 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 5400.05 | 05-AUG-14:09 | 5242.46 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9690.55 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 5400.05 | 02-SEP-14:09 | 5242.46 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7686.74 | 26-SEP-13:00 | 140.80 | 24-SEP-07:10 |
October | 5400.05 | 07-OCT-14:09 | 5242.46 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6272.17 | 09-OCT-12:00 | 371.97 | 29-OCT-07:02 |
November | 5400.05 | 04-NOV-14:09 | 5242.46 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4591.55 | 05-NOV-12:00 | 925.32 | 23-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 5242.46 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2813.09 | 10-DEC-12:10 | 2850.43 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 5242.46 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.26 | 0.00 | |||||
Maximum of Months | 5400.05 | 5242.46 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9690.55 | 3359.53 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 2671.87 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.89 | 23-JAN-14:00 | 1530.33 | 15-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 2671.87 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.85 | 06-FEB-15:00 | 1866.15 | 20-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 2671.87 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1901.94 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 2671.87 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4554.04 | 28-APR-12:00 | 461.06 | 09-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 2671.87 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.37 | 09-MAY-13:00 | 167.08 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 2671.87 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.68 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 2671.87 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.58 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 2671.87 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 2671.87 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.49 | 26-SEP-13:00 | 75.65 | 24-SEP-07:10 |
October | 2699.95 | 07-OCT-14:09 | 2671.87 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.69 | 09-OCT-12:00 | 206.14 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 2671.87 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.99 | 05-NOV-12:00 | 506.80 | 23-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 2671.87 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.91 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.89 | 0.00 | |||||
Maximum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 1901.94 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 2671.87 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.89 | 23-JAN-14:00 | 1524.13 | 15-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 2671.87 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.85 | 06-FEB-15:00 | 1859.79 | 20-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 2671.87 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1895.56 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 2671.87 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4554.04 | 28-APR-12:00 | 454.96 | 09-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 2671.87 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.37 | 09-MAY-13:00 | 166.29 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 2671.87 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.68 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 2671.87 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.58 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 2671.87 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 2671.87 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.49 | 26-SEP-13:00 | 74.95 | 24-SEP-07:10 |
October | 2699.95 | 07-OCT-14:09 | 2671.87 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.69 | 09-OCT-12:00 | 205.24 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 2671.87 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.99 | 05-NOV-12:00 | 501.13 | 23-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 2671.87 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.91 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.89 | 0.00 | |||||
Maximum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 1895.56 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 2671.87 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.89 | 23-JAN-14:00 | 1524.57 | 15-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 2671.87 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.85 | 06-FEB-15:00 | 1857.75 | 20-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 2671.87 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1893.65 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 2671.87 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4554.04 | 28-APR-12:00 | 459.46 | 09-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 2671.87 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.37 | 09-MAY-13:00 | 166.21 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 2671.87 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.68 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 2671.87 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.58 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 2671.87 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 2671.87 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.49 | 26-SEP-13:00 | 77.48 | 24-SEP-07:10 |
October | 2699.95 | 07-OCT-14:09 | 2671.87 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.69 | 09-OCT-12:00 | 207.03 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 2671.87 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.99 | 05-NOV-12:00 | 506.78 | 23-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 2671.87 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.90 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.89 | 0.00 | |||||
Maximum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.05 | 1893.65 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 2671.87 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1116.04 | 23-JAN-14:00 | 1598.91 | 15-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 2671.87 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2332.01 | 06-FEB-15:00 | 1916.46 | 20-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 2671.87 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3755.26 | 27-MAR-11:10 | 1964.51 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 2671.87 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4611.32 | 28-APR-12:00 | 557.21 | 09-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 2671.87 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.61 | 09-MAY-13:00 | 169.51 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 2671.87 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4844.34 | 12-JUN-12:00 | 119.77 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 2671.87 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5523.83 | 21-JUL-12:00 | 1.49 | 03-JUL-06:00 |
August | 2699.95 | 05-AUG-14:09 | 2671.87 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5710.55 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 2671.87 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4472.05 | 26-SEP-13:00 | 91.27 | 24-SEP-07:10 |
October | 2699.95 | 07-OCT-14:09 | 2671.87 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3608.78 | 09-OCT-12:00 | 236.80 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 2671.87 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2648.68 | 05-NOV-12:00 | 604.32 | 23-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 2671.87 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.96 | 10-DEC-12:10 | 1691.59 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1116.04 | 0.00 | |||||
Maximum of Months | 2699.95 | 2671.87 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5710.55 | 1964.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21668.97 | 29-JAN-08:63 | 1012.51 | 1130.22 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.18 |
February | 37050.08 | 09-FEB-08:62 | 1350.01 | 1506.96 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.74 |
March | 59681.70 | 02-MAR-08:62 | 2025.02 | 2260.43 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 162.90 | 0.00 |
April | 59793.33 | 29-APR-07:02 | 0.00 | 1883.69 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 202.90 | 0.00 |
May | 63073.02 | 10-MAY-07:01 | 2362.52 | 2637.17 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 363.19 | 0.00 |
June | 55587.05 | 01-JUN-07:01 | 2700.03 | 3013.91 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.72 | 0.00 |
July | 61985.76 | 04-JUL-07:01 | 3037.53 | 3390.65 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 329.75 | 0.00 |
August | 56789.45 | 06-AUG-07:01 | 3375.03 | 3767.39 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 467.07 | 0.00 |
September | 52592.23 | 02-SEP-07:01 | 0.00 | 3390.65 | 662.75 | 0.00 | 0.00 | 0.00 | 0.00 | 395.77 | 0.00 |
October | 59269.20 | 20-OCT-07:02 | 0.00 | 2260.43 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.71 |
November | 58876.00 | 05-NOV-07:02 | 2025.02 | 2260.43 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.41 |
December | 49793.95 | 12-DEC-08:62 | 1687.52 | 1883.69 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 21668.97 | 0.00 | 1130.22 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 63073.02 | 3375.03 | 3767.39 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 467.07 | 212.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12161.91 | 29-JAN-08:63 | 506.24 | 648.12 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.00 |
February | 19951.18 | 09-FEB-08:62 | 674.99 | 864.17 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.90 |
March | 30662.19 | 02-MAR-08:62 | 1012.48 | 1296.25 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 87.56 | 0.00 |
April | 31108.52 | 29-APR-07:02 | 0.00 | 1080.21 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.20 | 0.00 |
May | 32427.74 | 11-MAY-07:01 | 1181.23 | 1512.29 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 179.16 | 0.00 |
June | 29803.48 | 02-JUN-07:01 | 0.00 | 1512.29 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 159.75 | 0.00 |
July | 32050.53 | 04-JUL-07:01 | 1518.72 | 1944.37 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 188.12 | 0.00 |
August | 29541.37 | 06-AUG-07:01 | 1687.47 | 2160.42 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 272.55 | 0.00 |
September | 28303.04 | 26-SEP-07:01 | 1181.23 | 1512.29 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 61.37 | 0.00 |
October | 31455.20 | 20-OCT-07:02 | 0.00 | 1296.25 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.64 |
November | 31178.99 | 05-NOV-07:02 | 1012.48 | 1296.25 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.10 |
December | 27503.63 | 12-DEC-08:62 | 843.73 | 1080.21 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12161.91 | 0.00 | 648.12 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32427.74 | 1687.47 | 2160.42 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 272.55 | 119.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11951.57 | 29-JAN-08:63 | 0.00 | 603.57 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.89 |
February | 21753.46 | 09-FEB-07:03 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 |
March | 33352.76 | 28-MAR-06:02 | 0.00 | 1207.14 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
April | 31164.90 | 29-APR-06:02 | 0.00 | 1207.14 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
May | 32199.37 | 11-MAY-06:01 | 0.00 | 1609.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 0.00 |
June | 30231.17 | 01-JUN-06:01 | 0.00 | 1609.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 0.00 |
July | 31895.47 | 04-JUL-07:01 | 0.00 | 1810.72 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 171.38 | 0.00 |
August | 26752.38 | 16-AUG-06:01 | 0.00 | 2011.91 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 0.00 |
September | 24697.28 | 05-SEP-06:01 | 0.00 | 2011.91 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 | 0.00 |
October | 30279.75 | 20-OCT-06:02 | 0.00 | 1207.14 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 |
November | 29723.33 | 05-NOV-07:02 | 0.00 | 1207.14 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.42 |
December | 25445.94 | 12-DEC-07:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11951.57 | 0.00 | 603.57 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33352.76 | 0.00 | 2011.91 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 171.38 | 134.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11733.73 | 29-JAN-08:63 | 0.00 | 603.57 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.73 |
February | 22022.84 | 09-FEB-07:03 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 |
March | 33480.91 | 28-MAR-06:02 | 0.00 | 1207.14 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
April | 31312.91 | 29-APR-06:02 | 0.00 | 1207.14 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
May | 32351.66 | 11-MAY-06:01 | 0.00 | 1609.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
June | 30426.59 | 01-JUN-06:01 | 0.00 | 1609.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
July | 32138.26 | 04-JUL-07:01 | 0.00 | 1810.72 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 165.95 | 0.00 |
August | 26966.34 | 16-AUG-06:01 | 0.00 | 2011.91 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 23.86 | 0.00 |
September | 25126.14 | 05-SEP-06:01 | 0.00 | 2011.91 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 4.92 | 0.00 |
October | 30430.05 | 20-OCT-06:02 | 0.00 | 1207.14 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
November | 29871.61 | 05-NOV-07:02 | 0.00 | 1207.14 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.59 |
December | 25502.14 | 12-DEC-07:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11733.73 | 0.00 | 603.57 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33480.91 | 0.00 | 2011.91 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 165.95 | 137.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11089.60 | 29-JAN-08:63 | 0.00 | 603.57 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.22 |
February | 21103.52 | 09-FEB-07:03 | 0.00 | 804.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 |
March | 33378.42 | 28-MAR-06:02 | 0.00 | 1207.14 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
April | 31188.29 | 29-APR-06:02 | 0.00 | 1207.14 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 0.00 |
May | 32235.68 | 11-MAY-06:01 | 0.00 | 1609.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1.66 | 0.00 |
June | 30327.87 | 01-JUN-06:01 | 0.00 | 1609.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
July | 32065.02 | 04-JUL-07:01 | 0.00 | 1810.72 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 167.31 | 0.00 |
August | 26871.01 | 16-AUG-06:01 | 0.00 | 2011.91 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | 0.00 |
September | 25180.64 | 05-SEP-06:01 | 0.00 | 2011.91 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 0.00 |
October | 30320.73 | 20-OCT-06:02 | 0.00 | 1207.14 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
November | 29803.06 | 05-NOV-07:02 | 0.00 | 1207.14 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.27 |
December | 25391.97 | 12-DEC-07:02 | 0.00 | 1005.95 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11089.60 | 0.00 | 603.57 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33378.42 | 0.00 | 2011.91 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 167.31 | 136.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23851.69 | 29-JAN-09:03 | 0.00 | 827.84 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.97 |
February | 36501.02 | 06-FEB-08:62 | 0.00 | 1103.78 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.83 |
March | 57345.00 | 28-MAR-07:02 | 0.00 | 1379.73 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 17.74 | 0.00 |
April | 56297.54 | 29-APR-07:02 | 0.00 | 1379.73 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 189.59 | 0.00 |
May | 58768.29 | 11-MAY-07:01 | 0.00 | 1931.62 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 307.10 | 0.00 |
June | 54865.35 | 01-JUN-07:01 | 0.00 | 2207.56 | 589.11 | 0.00 | 0.00 | 0.00 | 0.00 | 258.82 | 0.00 |
July | 60293.43 | 04-JUL-08:61 | 0.00 | 2759.45 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 359.68 | 0.00 |
August | 49634.97 | 16-AUG-07:01 | 0.00 | 2759.45 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 438.61 | 0.00 |
September | 48176.49 | 26-SEP-07:01 | 0.00 | 1931.62 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 0.00 |
October | 56570.84 | 20-OCT-07:02 | 0.00 | 1655.67 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.06 |
November | 55760.76 | 19-NOV-09:02 | 0.00 | 1655.67 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 34.26 | 0.00 |
December | 48139.44 | 12-DEC-08:62 | 0.00 | 1379.73 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23851.69 | 0.00 | 827.84 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60293.43 | 0.00 | 2759.45 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 438.61 | 212.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10990.63 | 29-JAN-09:03 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 |
February | 17493.42 | 06-FEB-08:62 | 0.00 | 562.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.54 |
March | 27586.73 | 02-MAR-08:62 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 96.92 | 0.00 |
April | 29139.31 | 29-APR-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.37 | 0.00 |
May | 30445.52 | 11-MAY-07:01 | 0.00 | 984.37 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 182.18 | 0.00 |
June | 28465.07 | 01-JUN-07:01 | 0.00 | 1125.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 154.42 | 0.00 |
July | 31305.73 | 04-JUL-08:61 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 211.07 | 0.00 |
August | 25747.35 | 16-AUG-07:01 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 253.87 | 0.00 |
September | 24950.62 | 26-SEP-07:01 | 0.00 | 984.37 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 53.94 | 0.00 |
October | 29289.17 | 20-OCT-07:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.50 |
November | 28851.45 | 19-NOV-09:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 | 0.00 |
December | 24919.00 | 12-DEC-08:62 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10990.63 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31305.73 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 253.87 | 120.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10706.51 | 29-JAN-09:03 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 |
February | 17157.09 | 06-FEB-08:62 | 0.00 | 562.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.37 |
March | 27469.46 | 02-MAR-08:62 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 97.99 | 0.00 |
April | 29018.97 | 29-APR-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.36 | 0.00 |
May | 30324.25 | 11-MAY-07:01 | 0.00 | 984.37 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 183.06 | 0.00 |
June | 28342.12 | 01-JUN-07:01 | 0.00 | 1125.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 155.35 | 0.00 |
July | 31184.50 | 04-JUL-08:61 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 211.76 | 0.00 |
August | 25636.18 | 16-AUG-07:01 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 254.67 | 0.00 |
September | 24843.21 | 26-SEP-07:01 | 0.00 | 984.37 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 54.59 | 0.00 |
October | 29176.44 | 20-OCT-07:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.66 |
November | 28739.90 | 19-NOV-09:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 0.00 |
December | 24818.41 | 12-DEC-08:62 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10706.51 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31184.50 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 254.67 | 120.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10340.78 | 29-JAN-09:03 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.81 |
February | 16783.06 | 06-FEB-08:62 | 0.00 | 562.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.28 |
March | 27582.91 | 02-MAR-08:62 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 98.35 | 0.00 |
April | 29157.04 | 29-APR-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.21 | 0.00 |
May | 30504.13 | 11-MAY-07:01 | 0.00 | 984.37 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 181.94 | 0.00 |
June | 28544.64 | 01-JUN-07:01 | 0.00 | 1125.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 153.57 | 0.00 |
July | 31423.40 | 04-JUL-08:61 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 209.28 | 0.00 |
August | 25900.97 | 16-AUG-07:01 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 250.72 | 0.00 |
September | 25056.33 | 26-SEP-07:01 | 0.00 | 984.37 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 | 0.00 |
October | 29351.75 | 20-OCT-07:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.98 |
November | 28875.48 | 19-NOV-09:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 | 0.00 |
December | 24924.70 | 12-DEC-08:62 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10340.78 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31423.40 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 250.72 | 120.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9115.78 | 29-JAN-09:03 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.63 |
February | 13884.99 | 06-FEB-08:62 | 0.00 | 562.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.11 |
March | 31643.07 | 02-MAR-08:62 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 123.08 | 0.00 |
April | 30436.21 | 29-APR-07:02 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.15 | 0.00 |
May | 33612.10 | 11-MAY-07:01 | 0.00 | 984.37 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 184.37 | 0.00 |
June | 30174.39 | 01-JUN-07:01 | 0.00 | 1125.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 151.81 | 0.00 |
July | 34805.89 | 04-JUL-08:61 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 211.85 | 0.00 |
August | 28482.82 | 06-AUG-08:61 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 299.31 | 0.00 |
September | 27063.08 | 26-SEP-07:01 | 0.00 | 984.37 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 47.29 | 0.00 |
October | 31377.46 | 20-OCT-07:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 |
November | 30535.20 | 19-NOV-09:02 | 0.00 | 843.75 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 28.76 | 0.00 |
December | 25025.02 | 12-DEC-08:62 | 0.00 | 703.12 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9115.78 | 0.00 | 421.87 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34805.89 | 0.00 | 1406.25 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 299.31 | 131.11 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.164988E+12 | 129045.88 | 29-JAN-15:00 | 0.00 | 0.00 |
February | 0.155655E+12 | 144890.43 | 07-FEB-13:30 | 0.00 | 0.00 |
March | 0.181757E+12 | 155420.83 | 27-MAR-12:09 | 0.00 | 0.00 |
April | 0.190036E+12 | 176723.80 | 28-APR-11:00 | 0.00 | 0.00 |
May | 0.224313E+12 | 195250.74 | 31-MAY-12:09 | 0.00 | 0.00 |
June | 0.237655E+12 | 208881.40 | 09-JUN-12:00 | 0.00 | 0.00 |
July | 0.262147E+12 | 225974.04 | 20-JUL-12:00 | 0.00 | 0.00 |
August | 0.273652E+12 | 231672.53 | 10-AUG-16:10 | 0.00 | 0.00 |
September | 0.242287E+12 | 214654.77 | 07-SEP-13:30 | 0.00 | 0.00 |
October | 0.222809E+12 | 198358.20 | 07-OCT-12:00 | 0.00 | 0.00 |
November | 0.193482E+12 | 173152.48 | 01-NOV-13:00 | 0.00 | 0.00 |
December | 0.175800E+12 | 143924.74 | 05-DEC-17:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.252458E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.155655E+12 | 129045.88 | 0.00 | 0.00 | |
Maximum of Months | 0.273652E+12 | 231672.53 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.523593E+11 | 0.168489E+11 | 0.108325E+11 | 0.00 | 0.478992E+11 | 0.00 | 0.00 | 0.358098E+11 | 0.00 | 0.00 | 0.00 | 0.123876E+10 | 0.00 |
February | 0.473916E+11 | 0.146182E+11 | 0.980803E+10 | 0.00 | 0.434003E+11 | 0.00 | 0.00 | 0.393397E+11 | 0.00 | 0.00 | 0.00 | 0.109742E+10 | 0.00 |
March | 0.531261E+11 | 0.153098E+11 | 0.110075E+11 | 0.00 | 0.487792E+11 | 0.00 | 0.00 | 0.523656E+11 | 0.00 | 0.00 | 0.00 | 0.116870E+10 | 0.00 |
April | 0.507849E+11 | 0.138859E+11 | 0.105079E+11 | 0.00 | 0.466547E+11 | 0.00 | 0.00 | 0.671888E+11 | 0.00 | 0.00 | 0.00 | 0.101368E+10 | 0.00 |
May | 0.527331E+11 | 0.136011E+11 | 0.109147E+11 | 0.00 | 0.486715E+11 | 0.00 | 0.00 | 0.974360E+11 | 0.00 | 0.00 | 0.00 | 0.956807E+09 | 0.00 |
June | 0.513456E+11 | 0.128146E+11 | 0.106386E+11 | 0.00 | 0.475809E+11 | 0.00 | 0.00 | 0.114407E+12 | 0.00 | 0.00 | 0.00 | 0.867712E+09 | 0.00 |
July | 0.521917E+11 | 0.133706E+11 | 0.107945E+11 | 0.00 | 0.484139E+11 | 0.00 | 0.00 | 0.136527E+12 | 0.00 | 0.00 | 0.00 | 0.849523E+09 | 0.00 |
August | 0.531069E+11 | 0.140147E+11 | 0.110006E+11 | 0.00 | 0.493811E+11 | 0.00 | 0.00 | 0.145242E+12 | 0.00 | 0.00 | 0.00 | 0.906409E+09 | 0.00 |
September | 0.508041E+11 | 0.144080E+11 | 0.105148E+11 | 0.00 | 0.470672E+11 | 0.00 | 0.00 | 0.118558E+12 | 0.00 | 0.00 | 0.00 | 0.934477E+09 | 0.00 |
October | 0.523593E+11 | 0.158115E+11 | 0.108325E+11 | 0.00 | 0.483050E+11 | 0.00 | 0.00 | 0.944446E+11 | 0.00 | 0.00 | 0.00 | 0.105569E+10 | 0.00 |
November | 0.507273E+11 | 0.160963E+11 | 0.104978E+11 | 0.00 | 0.466240E+11 | 0.00 | 0.00 | 0.684232E+11 | 0.00 | 0.00 | 0.00 | 0.111333E+10 | 0.00 |
December | 0.522109E+11 | 0.170862E+11 | 0.108050E+11 | 0.00 | 0.478180E+11 | 0.00 | 0.00 | 0.466657E+11 | 0.00 | 0.00 | 0.00 | 0.121385E+10 | 0.00 |
Annual Sum or Average | 0.619141E+12 | 0.177866E+12 | 0.128154E+12 | 0.00 | 0.570595E+12 | 0.00 | 0.00 | 0.101641E+13 | 0.00 | 0.00 | 0.00 | 0.124163E+11 | 0.00 |
Minimum of Months | 0.473916E+11 | 0.128146E+11 | 0.980803E+10 | 0.00 | 0.434003E+11 | 0.00 | 0.00 | 0.358098E+11 | 0.00 | 0.00 | 0.00 | 0.849523E+09 | 0.00 |
Maximum of Months | 0.531261E+11 | 0.170862E+11 | 0.110075E+11 | 0.00 | 0.493811E+11 | 0.00 | 0.00 | 0.145242E+12 | 0.00 | 0.00 | 0.00 | 0.123876E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 38660.10 | 01-JAN-11:09 | 11300.38 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 32901.90 | 04-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 38660.10 | 01-FEB-10:09 | 11300.38 | 01-FEB-00:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 32901.90 | 06-FEB-12:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 38660.10 | 01-MAR-10:09 | 11300.38 | 01-MAR-00:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 32901.90 | 04-MAR-08:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 38660.10 | 01-APR-09:09 | 11300.38 | 01-APR-00:10 | 8059.50 | 01-APR-09:09 | 0.00 | 32901.90 | 02-APR-08:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 38660.10 | 01-MAY-09:09 | 11300.38 | 01-MAY-00:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 32901.90 | 04-MAY-13:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 38660.10 | 01-JUN-09:09 | 11300.38 | 01-JUN-00:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 32901.90 | 02-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 38660.10 | 01-JUL-09:09 | 11300.38 | 01-JUL-00:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 32901.90 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 38660.10 | 01-AUG-09:09 | 11300.38 | 01-AUG-00:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 32901.90 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 38660.10 | 01-SEP-09:09 | 11300.38 | 01-SEP-00:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 32901.90 | 18-SEP-12:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38660.10 | 01-OCT-10:09 | 11300.38 | 01-OCT-00:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 32901.90 | 02-OCT-12:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 38660.10 | 01-NOV-09:09 | 11300.38 | 01-NOV-00:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 32901.90 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 38660.10 | 01-DEC-10:09 | 11300.38 | 01-DEC-00:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 32901.90 | 05-DEC-17:19 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 38660.10 | 11300.38 | 8059.50 | 0.00 | 32901.90 | 0.00 | 0.00 | |||||
Maximum of Months | 38660.10 | 11300.38 | 8059.50 | 0.00 | 32901.90 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 48731.81 | 29-JAN-15:00 | 0.00 | 0.00 | 0.00 | 1309.73 | 13-JAN-13:20 | 0.00 |
February | 63961.86 | 07-FEB-13:30 | 0.00 | 0.00 | 0.00 | 1308.15 | 01-FEB-13:30 | 0.00 |
March | 74651.87 | 27-MAR-12:09 | 0.00 | 0.00 | 0.00 | 1301.10 | 01-MAR-13:50 | 0.00 |
April | 96262.48 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 1144.84 | 01-APR-12:09 | 0.00 |
May | 114786.21 | 31-MAY-12:09 | 0.00 | 0.00 | 0.00 | 992.09 | 01-MAY-12:09 | 0.00 |
June | 128418.49 | 09-JUN-12:00 | 0.00 | 0.00 | 0.00 | 983.34 | 01-JUN-12:39 | 0.00 |
July | 145552.56 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 846.12 | 26-JUL-12:00 | 0.00 |
August | 151362.89 | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | 984.72 | 31-AUG-12:09 | 0.00 |
September | 134114.98 | 07-SEP-13:30 | 0.00 | 0.00 | 0.00 | 993.35 | 29-SEP-12:00 | 0.00 |
October | 117741.22 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 1147.80 | 31-OCT-12:30 | 0.00 |
November | 92528.47 | 01-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1302.65 | 30-NOV-13:39 | 0.00 |
December | 58696.77 | 04-DEC-13:09 | 0.00 | 0.00 | 0.00 | 1308.93 | 29-DEC-13:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 48731.81 | 0.00 | 0.00 | 0.00 | 846.12 | 0.00 | ||
Maximum of Months | 151362.89 | 0.00 | 0.00 | 0.00 | 1309.73 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 129045.88 | 29-JAN-15:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 48731.81 | 0.00 |
February | 144890.43 | 07-FEB-13:30 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 63961.86 | 0.00 |
March | 155420.83 | 27-MAR-12:09 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 74651.87 | 0.00 |
April | 176723.80 | 28-APR-11:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 96262.48 | 0.00 |
May | 195250.74 | 31-MAY-12:09 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 114786.21 | 0.00 |
June | 208881.40 | 09-JUN-12:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 128418.49 | 0.00 |
July | 225974.04 | 20-JUL-12:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 145552.56 | 0.00 |
August | 231672.53 | 10-AUG-16:10 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 151362.89 | 0.00 |
September | 214654.77 | 07-SEP-13:30 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 134114.98 | 0.00 |
October | 198358.20 | 07-OCT-12:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 117741.22 | 0.00 |
November | 173152.48 | 01-NOV-13:00 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 92528.47 | 0.00 |
December | 143924.74 | 05-DEC-17:30 | 38660.10 | 8059.50 | 11300.38 | 0.00 | 32901.90 | 0.00 | 0.00 | 52014.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 129045.88 | 38660.10 | 8059.50 | 0.00 | 0.00 | 32901.90 | 0.00 | 0.00 | 48731.81 | 0.00 | |
Maximum of Months | 231672.53 | 38660.10 | 8059.50 | 11300.38 | 0.00 | 32901.90 | 0.00 | 0.00 | 151362.89 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.61 | 0.67 | 24.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.70 | 3.00 | 24.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.72 | 3.67 | 24.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.55 | 1.50 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.00 | 24.68 | 8.83 | 24.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.72 | 3.67 | 24.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.17 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.55 | 2.67 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.56 | 3.50 | 24.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.47 | 0.83 | 24.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.00 | 24.55 | 7.17 | 24.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.56 | 3.50 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.00 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.64 | 0.00 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.81 | 0.00 | 24.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.85 | 0.00 | 24.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.70 | 0.00 | 24.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.00 | 24.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.17 | 24.77 | 0.00 | 24.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.85 | 0.00 | 24.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.00 | 24.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.67 | 0.00 | 24.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.87 | 0.00 | 24.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.91 | 0.00 | 24.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.71 | 0.00 | 24.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.65 | 0.00 | 24.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.00 | 24.80 | 0.00 | 24.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.91 | 0.00 | 24.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.00 | 24.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.66 | 0.00 | 24.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.87 | 0.00 | 24.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.90 | 0.00 | 24.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.73 | 0.00 | 24.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.65 | 0.00 | 24.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 24.80 | 0.00 | 24.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.90 | 0.00 | 24.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.56 | 0.00 | 24.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.76 | 0.00 | 24.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.91 | 0.00 | 24.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.89 | 0.00 | 24.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.00 | 0.00 | 25.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.76 | 0.00 | 24.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.83 | 24.87 | 0.00 | 24.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.00 | 0.00 | 25.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.00 | 24.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.74 | 0.00 | 24.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.83 | 0.00 | 24.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.83 | 0.00 | 24.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.80 | 0.00 | 24.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.77 | 0.00 | 24.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.83 | 24.80 | 0.00 | 24.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.83 | 0.00 | 24.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.00 | 24.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.73 | 0.00 | 24.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.83 | 0.00 | 24.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.83 | 0.00 | 24.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.86 | 0.00 | 24.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.77 | 0.00 | 24.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.50 | 24.81 | 0.00 | 24.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.86 | 0.00 | 24.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.56 | 0.00 | 24.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.75 | 0.00 | 24.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.86 | 0.00 | 24.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.85 | 0.00 | 24.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.76 | 0.00 | 24.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.73 | 0.00 | 24.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.00 | 24.81 | 0.00 | 24.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.86 | 0.00 | 24.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.59 | 0.00 | 24.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.14 | 0.00 | 25.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 25.78 | 0.00 | 25.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.48 | 0.00 | 25.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.84 | 0.00 | 24.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.89 | 0.00 | 24.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.67 | 25.36 | 0.00 | 25.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 25.78 | 0.00 | 25.78 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.33 | 23.75 | 348.00 | 23.88 | 0.00 | 23.88 |
February | 6.67 | 23.82 | 382.67 | 23.89 | 0.00 | 23.89 |
March | 6.17 | 23.89 | 426.67 | 23.89 | 0.00 | 23.89 |
April | 0.00 | 0.00 | 463.17 | 23.89 | 0.00 | 23.89 |
May | 2.17 | 23.99 | 496.00 | 23.89 | 2.17 | 23.89 |
June | 22.00 | 23.94 | 481.00 | 23.90 | 22.00 | 23.90 |
July | 61.00 | 23.93 | 495.00 | 23.90 | 61.00 | 23.90 |
August | 51.83 | 23.94 | 497.00 | 23.90 | 51.83 | 23.90 |
September | 31.17 | 23.92 | 479.00 | 23.90 | 31.17 | 23.90 |
October | 10.00 | 23.93 | 496.00 | 23.89 | 10.00 | 23.89 |
November | 0.00 | 0.00 | 477.67 | 23.89 | 0.00 | 23.89 |
December | 3.33 | 23.90 | 439.33 | 23.89 | 0.00 | 23.89 |
Annual Sum or Average | 211.67 | 23.91 | 5481.50 | 23.89 | 178.17 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 348.00 | 23.88 | 0.00 | 23.88 |
Maximum of Months | 61.00 | 23.99 | 497.00 | 23.90 | 61.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.67 | 23.84 | 329.83 | 23.89 | 0.00 | 23.89 |
February | 4.83 | 23.89 | 365.83 | 23.89 | 0.00 | 23.89 |
March | 3.17 | 23.90 | 416.17 | 23.89 | 0.00 | 23.89 |
April | 0.00 | 0.00 | 455.50 | 23.89 | 0.00 | 23.89 |
May | 1.83 | 23.89 | 496.00 | 23.89 | 1.83 | 23.89 |
June | 14.33 | 23.92 | 481.00 | 23.89 | 14.33 | 23.89 |
July | 53.50 | 23.92 | 495.00 | 23.90 | 53.50 | 23.90 |
August | 50.83 | 23.91 | 497.00 | 23.90 | 50.83 | 23.90 |
September | 30.33 | 23.90 | 479.00 | 23.89 | 30.33 | 23.89 |
October | 4.33 | 23.91 | 495.67 | 23.89 | 4.33 | 23.89 |
November | 0.00 | 0.00 | 470.33 | 23.89 | 0.00 | 23.89 |
December | 2.00 | 23.91 | 422.00 | 23.89 | 0.00 | 23.89 |
Annual Sum or Average | 178.83 | 23.91 | 5403.33 | 23.89 | 155.17 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 329.83 | 23.89 | 0.00 | 23.89 |
Maximum of Months | 53.50 | 23.92 | 497.00 | 23.90 | 53.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 23.99 | 296.17 | 24.10 | 0.33 | 24.10 |
February | 3.00 | 26.67 | 308.17 | 24.12 | 2.00 | 24.14 |
March | 7.00 | 27.43 | 344.33 | 24.20 | 6.00 | 24.26 |
April | 15.50 | 28.27 | 349.50 | 24.36 | 15.50 | 24.52 |
May | 26.00 | 28.43 | 375.00 | 24.51 | 26.00 | 24.75 |
June | 36.50 | 27.32 | 366.00 | 24.53 | 36.50 | 24.77 |
July | 74.17 | 25.77 | 369.00 | 24.53 | 74.17 | 24.71 |
August | 73.83 | 25.78 | 379.00 | 24.52 | 73.83 | 24.70 |
September | 53.67 | 26.23 | 360.00 | 24.51 | 53.67 | 24.71 |
October | 27.67 | 27.95 | 371.00 | 24.49 | 27.67 | 24.72 |
November | 14.17 | 28.08 | 359.67 | 24.31 | 14.17 | 24.45 |
December | 4.33 | 26.99 | 349.50 | 24.14 | 3.67 | 24.17 |
Annual Sum or Average | 344.50 | 26.61 | 4227.33 | 24.38 | 333.50 | 24.54 |
Minimum of Months | 3.00 | 23.99 | 296.17 | 24.10 | 0.33 | 24.10 |
Maximum of Months | 74.17 | 28.43 | 379.00 | 24.53 | 74.17 | 24.77 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.00 | 23.97 | 294.17 | 24.10 | 0.33 | 24.10 |
February | 3.17 | 26.53 | 308.17 | 24.12 | 2.00 | 24.14 |
March | 7.17 | 27.44 | 344.83 | 24.20 | 6.17 | 24.27 |
April | 15.83 | 28.26 | 350.33 | 24.36 | 15.83 | 24.52 |
May | 25.50 | 28.53 | 375.00 | 24.52 | 25.50 | 24.76 |
June | 35.33 | 27.44 | 366.00 | 24.54 | 35.33 | 24.77 |
July | 73.17 | 25.80 | 369.00 | 24.53 | 73.17 | 24.71 |
August | 71.83 | 25.84 | 379.00 | 24.52 | 71.83 | 24.70 |
September | 52.00 | 26.31 | 360.00 | 24.52 | 52.00 | 24.72 |
October | 27.17 | 28.06 | 371.00 | 24.50 | 27.17 | 24.72 |
November | 14.17 | 28.10 | 359.67 | 24.31 | 14.17 | 24.45 |
December | 4.33 | 26.99 | 349.33 | 24.14 | 3.67 | 24.17 |
Annual Sum or Average | 338.67 | 26.66 | 4226.50 | 24.38 | 327.17 | 24.54 |
Minimum of Months | 3.17 | 23.97 | 294.17 | 24.10 | 0.33 | 24.10 |
Maximum of Months | 73.17 | 28.53 | 379.00 | 24.54 | 73.17 | 24.77 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 23.93 | 287.00 | 24.10 | 0.33 | 24.10 |
February | 3.17 | 26.12 | 305.17 | 24.11 | 1.67 | 24.13 |
March | 7.00 | 27.16 | 341.17 | 24.19 | 5.50 | 24.25 |
April | 15.33 | 28.26 | 349.50 | 24.36 | 15.33 | 24.51 |
May | 25.33 | 28.52 | 375.00 | 24.51 | 25.33 | 24.75 |
June | 35.33 | 27.44 | 366.00 | 24.53 | 35.33 | 24.77 |
July | 72.83 | 25.81 | 369.00 | 24.53 | 72.83 | 24.71 |
August | 71.83 | 25.84 | 379.00 | 24.52 | 71.83 | 24.70 |
September | 52.67 | 26.28 | 360.00 | 24.52 | 52.67 | 24.71 |
October | 27.17 | 28.02 | 371.00 | 24.49 | 27.17 | 24.72 |
November | 13.83 | 28.08 | 359.67 | 24.31 | 13.83 | 24.44 |
December | 4.67 | 26.61 | 347.83 | 24.13 | 3.50 | 24.17 |
Annual Sum or Average | 339.67 | 26.62 | 4210.33 | 24.38 | 325.33 | 24.54 |
Minimum of Months | 3.17 | 23.93 | 287.00 | 24.10 | 0.33 | 24.10 |
Maximum of Months | 72.83 | 28.52 | 379.00 | 24.53 | 72.83 | 24.77 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 23.87 | 243.00 | 23.97 | 0.17 | 23.97 |
February | 1.00 | 27.13 | 274.83 | 23.97 | 0.67 | 23.98 |
March | 2.00 | 27.93 | 308.83 | 23.99 | 1.83 | 24.01 |
April | 6.83 | 28.34 | 324.17 | 24.10 | 6.83 | 24.18 |
May | 11.00 | 27.46 | 344.00 | 24.12 | 11.00 | 24.22 |
June | 23.17 | 25.50 | 336.00 | 24.10 | 23.17 | 24.19 |
July | 61.50 | 24.76 | 338.00 | 24.16 | 61.50 | 24.24 |
August | 58.17 | 24.56 | 348.00 | 24.08 | 58.17 | 24.14 |
September | 41.67 | 24.99 | 330.00 | 24.14 | 41.67 | 24.23 |
October | 14.67 | 26.70 | 340.00 | 24.13 | 14.67 | 24.23 |
November | 4.50 | 28.18 | 330.00 | 24.04 | 4.50 | 24.09 |
December | 1.67 | 27.15 | 313.17 | 23.99 | 1.67 | 24.00 |
Annual Sum or Average | 233.33 | 25.27 | 3830.00 | 24.07 | 225.83 | 24.14 |
Minimum of Months | 1.00 | 23.87 | 243.00 | 23.97 | 0.17 | 23.97 |
Maximum of Months | 61.50 | 28.34 | 348.00 | 24.16 | 61.50 | 24.24 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.00 | 23.88 | 215.67 | 23.97 | 0.17 | 23.98 |
February | 1.67 | 25.82 | 263.83 | 23.97 | 0.67 | 23.98 |
March | 2.67 | 26.89 | 295.67 | 23.99 | 1.83 | 24.02 |
April | 6.67 | 28.35 | 318.50 | 24.10 | 6.67 | 24.18 |
May | 12.00 | 27.13 | 344.00 | 24.12 | 12.00 | 24.21 |
June | 24.17 | 25.44 | 336.00 | 24.10 | 24.17 | 24.18 |
July | 62.33 | 24.74 | 338.00 | 24.16 | 62.33 | 24.24 |
August | 65.33 | 24.49 | 348.00 | 24.08 | 65.33 | 24.14 |
September | 43.00 | 24.97 | 330.00 | 24.14 | 43.00 | 24.23 |
October | 15.17 | 26.57 | 339.83 | 24.13 | 15.17 | 24.23 |
November | 3.83 | 28.27 | 329.17 | 24.03 | 3.83 | 24.08 |
December | 1.83 | 26.53 | 299.83 | 23.99 | 1.50 | 24.00 |
Annual Sum or Average | 248.67 | 25.17 | 3758.50 | 24.07 | 236.67 | 24.14 |
Minimum of Months | 1.67 | 23.88 | 215.67 | 23.97 | 0.17 | 23.98 |
Maximum of Months | 65.33 | 28.35 | 348.00 | 24.16 | 65.33 | 24.24 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.33 | 23.82 | 212.00 | 23.97 | 0.00 | 23.97 |
February | 2.00 | 25.49 | 262.33 | 23.97 | 0.67 | 23.98 |
March | 2.67 | 26.88 | 292.83 | 23.99 | 1.83 | 24.02 |
April | 6.67 | 28.33 | 317.83 | 24.10 | 6.67 | 24.18 |
May | 12.17 | 27.08 | 344.00 | 24.12 | 12.17 | 24.21 |
June | 25.33 | 25.37 | 336.00 | 24.10 | 25.33 | 24.18 |
July | 62.67 | 24.74 | 338.00 | 24.16 | 62.67 | 24.24 |
August | 66.00 | 24.48 | 348.00 | 24.08 | 66.00 | 24.13 |
September | 43.33 | 24.96 | 330.00 | 24.14 | 43.33 | 24.22 |
October | 15.50 | 26.51 | 339.67 | 24.13 | 15.50 | 24.23 |
November | 3.67 | 28.29 | 329.00 | 24.03 | 3.67 | 24.08 |
December | 1.67 | 26.43 | 299.17 | 23.99 | 1.33 | 24.00 |
Annual Sum or Average | 252.00 | 25.14 | 3748.83 | 24.07 | 239.17 | 24.14 |
Minimum of Months | 1.67 | 23.82 | 212.00 | 23.97 | 0.00 | 23.97 |
Maximum of Months | 66.00 | 28.33 | 348.00 | 24.16 | 66.00 | 24.24 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.17 | 23.81 | 209.83 | 23.97 | 0.00 | 23.97 |
February | 2.17 | 25.37 | 259.67 | 23.97 | 0.67 | 23.99 |
March | 3.00 | 26.55 | 291.00 | 23.99 | 1.83 | 24.02 |
April | 6.67 | 28.35 | 317.33 | 24.10 | 6.67 | 24.18 |
May | 12.00 | 27.13 | 344.00 | 24.12 | 12.00 | 24.21 |
June | 23.67 | 25.47 | 336.00 | 24.10 | 23.67 | 24.19 |
July | 61.17 | 24.76 | 338.00 | 24.16 | 61.17 | 24.24 |
August | 63.17 | 24.51 | 348.00 | 24.08 | 63.17 | 24.14 |
September | 43.00 | 24.97 | 330.00 | 24.14 | 43.00 | 24.23 |
October | 14.83 | 26.63 | 339.83 | 24.13 | 14.83 | 24.23 |
November | 4.00 | 28.24 | 329.17 | 24.03 | 4.00 | 24.08 |
December | 1.83 | 26.53 | 298.17 | 23.99 | 1.50 | 24.00 |
Annual Sum or Average | 246.67 | 25.18 | 3741.00 | 24.07 | 232.50 | 24.14 |
Minimum of Months | 1.83 | 23.81 | 209.83 | 23.97 | 0.00 | 23.97 |
Maximum of Months | 63.17 | 28.35 | 348.00 | 24.16 | 63.17 | 24.24 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.33 | 23.88 | 218.50 | 23.98 | 0.33 | 23.98 |
February | 3.83 | 24.75 | 259.17 | 23.98 | 0.67 | 23.99 |
March | 6.50 | 25.45 | 291.33 | 24.00 | 2.33 | 24.03 |
April | 7.50 | 28.47 | 319.50 | 24.12 | 7.50 | 24.22 |
May | 9.50 | 28.19 | 344.00 | 24.13 | 9.50 | 24.23 |
June | 19.00 | 25.95 | 336.00 | 24.11 | 19.00 | 24.20 |
July | 51.50 | 24.96 | 338.00 | 24.17 | 51.50 | 24.26 |
August | 44.83 | 24.78 | 348.00 | 24.09 | 44.83 | 24.17 |
September | 34.17 | 25.30 | 330.00 | 24.16 | 34.17 | 24.25 |
October | 13.50 | 27.22 | 340.00 | 24.15 | 13.50 | 24.26 |
November | 5.17 | 28.37 | 329.83 | 24.06 | 5.17 | 24.12 |
December | 3.17 | 26.11 | 302.50 | 24.00 | 2.00 | 24.02 |
Annual Sum or Average | 214.00 | 25.51 | 3756.83 | 24.09 | 190.50 | 24.16 |
Minimum of Months | 3.17 | 23.88 | 218.50 | 23.98 | 0.33 | 23.98 |
Maximum of Months | 51.50 | 28.47 | 348.00 | 24.17 | 51.50 | 24.26 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.88535 | 42.97149 | 0.47553 | 9.89190 |
February | 448.00000 | 23.88924 | 45.56622 | 0.51506 | 10.68803 |
March | 497.00000 | 23.89030 | 43.94064 | 0.52809 | 11.01377 |
April | 479.00000 | 23.89026 | 46.91411 | 0.58971 | 12.43294 |
May | 496.00000 | 23.89217 | 48.80178 | -0.1304 | 5.56288 |
June | 481.00000 | 23.89403 | 54.71489 | -0.0546 | 5.23667 |
July | 495.00000 | 23.89685 | 56.52801 | 0.00442 | 5.18872 |
August | 497.00000 | 23.89791 | 57.62022 | 0.03180 | 5.21207 |
September | 479.00000 | 23.89447 | 56.64309 | -0.0167 | 5.21897 |
October | 496.00000 | 23.89258 | 51.13304 | 0.69429 | 15.27520 |
November | 480.00000 | 23.89077 | 48.49434 | 0.61814 | 13.15759 |
December | 496.00000 | 23.89042 | 46.77582 | 0.53432 | 11.12766 |
Annual Sum or Average | 5840.00000 | 23.89205 | 50.02605 | 0.31450 | 9.15617 |
Minimum of Months | 448.00000 | 23.88535 | 42.97149 | -0.1304 | 5.18872 |
Maximum of Months | 497.00000 | 23.89791 | 57.62022 | 0.69429 | 15.27520 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.88913 | 41.85112 | 0.46856 | 9.72948 |
February | 448.00000 | 23.89072 | 44.03492 | 0.50216 | 10.39953 |
March | 497.00000 | 23.89065 | 42.68905 | 0.51321 | 10.66287 |
April | 479.00000 | 23.89023 | 45.36913 | 0.56582 | 11.84067 |
May | 496.00000 | 23.89195 | 47.68441 | -0.1755 | 5.81478 |
June | 481.00000 | 23.89338 | 53.61418 | -0.1076 | 5.39480 |
July | 495.00000 | 23.89540 | 55.90772 | -0.0536 | 5.21406 |
August | 497.00000 | 23.89601 | 57.12585 | -0.0319 | 5.17606 |
September | 479.00000 | 23.89360 | 55.66746 | -0.0751 | 5.30115 |
October | 496.00000 | 23.89224 | 49.88598 | 0.65614 | 14.17834 |
November | 480.00000 | 23.89050 | 47.21116 | 0.58951 | 12.42211 |
December | 496.00000 | 23.89065 | 45.25094 | 0.51751 | 10.74532 |
Annual Sum or Average | 5840.00000 | 23.89205 | 48.87908 | 0.27935 | 8.89596 |
Minimum of Months | 448.00000 | 23.88913 | 41.85112 | -0.1755 | 5.17606 |
Maximum of Months | 497.00000 | 23.89601 | 57.12585 | 0.65614 | 14.17834 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.05848 | 42.25275 | 0.50959 | 10.69049 |
February | 336.00000 | 24.07557 | 44.72120 | 0.55127 | 11.62736 |
March | 379.00000 | 24.11134 | 42.90347 | 0.56619 | 12.11295 |
April | 360.00000 | 24.17740 | 45.26728 | 0.63094 | 13.92368 |
May | 375.00000 | 24.24223 | 47.14739 | -0.0671 | 6.54503 |
June | 366.00000 | 24.25445 | 52.99027 | 0.00560 | 6.59160 |
July | 369.00000 | 24.28295 | 55.64433 | 0.07156 | 6.84374 |
August | 379.00000 | 24.27176 | 56.89364 | 0.09017 | 6.81995 |
September | 360.00000 | 24.25810 | 55.40488 | 0.04575 | 6.67490 |
October | 371.00000 | 24.23376 | 49.75061 | 0.73823 | 17.14012 |
November | 360.00000 | 24.16132 | 48.11223 | 0.66275 | 14.65465 |
December | 369.00000 | 24.09025 | 46.17954 | 0.57173 | 12.15891 |
Annual Sum or Average | 4395.00000 | 24.18556 | 48.96309 | 0.36255 | 10.46134 |
Minimum of Months | 336.00000 | 24.05848 | 42.25275 | -0.0671 | 6.54503 |
Maximum of Months | 379.00000 | 24.28295 | 56.89364 | 0.73823 | 17.14012 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.05723 | 42.27423 | 0.50801 | 10.65747 |
February | 336.00000 | 24.07506 | 44.73217 | 0.55064 | 11.61242 |
March | 379.00000 | 24.11127 | 42.89613 | 0.56646 | 12.12007 |
April | 360.00000 | 24.17797 | 45.23615 | 0.63255 | 13.96787 |
May | 375.00000 | 24.24305 | 47.08674 | -0.0625 | 6.54245 |
June | 366.00000 | 24.25514 | 52.90430 | 0.01034 | 6.60327 |
July | 369.00000 | 24.28358 | 55.53711 | 0.07720 | 6.87125 |
August | 379.00000 | 24.27228 | 56.78823 | 0.09538 | 6.84952 |
September | 360.00000 | 24.25888 | 55.30097 | 0.05068 | 6.69561 |
October | 371.00000 | 24.23474 | 49.66989 | 0.74111 | 17.23375 |
November | 360.00000 | 24.16191 | 48.07592 | 0.66419 | 14.69771 |
December | 369.00000 | 24.08995 | 46.18165 | 0.57149 | 12.15305 |
Annual Sum or Average | 4395.00000 | 24.18585 | 48.91401 | 0.36498 | 10.47989 |
Minimum of Months | 336.00000 | 24.05723 | 42.27423 | -0.0625 | 6.54245 |
Maximum of Months | 379.00000 | 24.28358 | 56.78823 | 0.74111 | 17.23375 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.05398 | 42.36609 | 0.50241 | 10.53966 |
February | 336.00000 | 24.07270 | 44.82845 | 0.54608 | 11.50477 |
March | 379.00000 | 24.10901 | 42.96874 | 0.56218 | 12.01487 |
April | 360.00000 | 24.17601 | 45.29934 | 0.62910 | 13.87073 |
May | 375.00000 | 24.24179 | 47.11275 | -0.0656 | 6.53420 |
June | 366.00000 | 24.25422 | 52.93409 | 0.00783 | 6.58477 |
July | 369.00000 | 24.28309 | 55.54610 | 0.07601 | 6.84999 |
August | 379.00000 | 24.27192 | 56.80032 | 0.09412 | 6.82646 |
September | 360.00000 | 24.25799 | 55.33068 | 0.04867 | 6.67433 |
October | 371.00000 | 24.23334 | 49.70576 | 0.73921 | 17.16801 |
November | 360.00000 | 24.15999 | 48.14045 | 0.66128 | 14.60920 |
December | 369.00000 | 24.08769 | 46.27717 | 0.56732 | 12.04972 |
Annual Sum or Average | 4395.00000 | 24.18425 | 48.96582 | 0.36191 | 10.41545 |
Minimum of Months | 336.00000 | 24.05398 | 42.36609 | -0.0656 | 6.53420 |
Maximum of Months | 379.00000 | 24.28309 | 56.80032 | 0.73921 | 17.16801 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.94402 | 43.78385 | 0.47872 | 9.97055 |
February | 308.00000 | 23.95076 | 46.15738 | 0.52347 | 10.88819 |
March | 348.00000 | 23.95237 | 44.37871 | 0.53803 | 11.28533 |
April | 330.00000 | 24.00593 | 46.64212 | 0.60680 | 13.07006 |
May | 344.00000 | 24.01120 | 48.43806 | -0.1053 | 5.95919 |
June | 336.00000 | 24.00423 | 54.21049 | -0.0346 | 5.78663 |
July | 338.00000 | 24.04899 | 56.71692 | 0.04310 | 5.96677 |
August | 348.00000 | 24.00297 | 58.04404 | 0.05427 | 5.75434 |
September | 330.00000 | 24.03209 | 56.50904 | 0.01596 | 5.86846 |
October | 340.00000 | 24.02071 | 50.69298 | 0.71546 | 16.15278 |
November | 330.00000 | 23.98262 | 49.41202 | 0.63628 | 13.71796 |
December | 338.00000 | 23.96291 | 47.69263 | 0.54456 | 11.40583 |
Annual Sum or Average | 4030.00000 | 23.99340 | 50.24700 | 0.33241 | 9.62981 |
Minimum of Months | 308.00000 | 23.94402 | 43.78385 | -0.1053 | 5.75434 |
Maximum of Months | 348.00000 | 24.04899 | 58.04404 | 0.71546 | 16.15278 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.94432 | 43.77545 | 0.46244 | 9.64396 |
February | 308.00000 | 23.95072 | 46.16694 | 0.50513 | 10.48500 |
March | 348.00000 | 23.95211 | 44.38752 | 0.51748 | 10.81873 |
April | 330.00000 | 24.00548 | 46.66381 | 0.58303 | 12.46944 |
May | 344.00000 | 24.01123 | 48.45191 | -0.1461 | 6.16500 |
June | 336.00000 | 24.00428 | 54.26072 | -0.0780 | 5.88664 |
July | 338.00000 | 24.04915 | 56.79858 | -0.0032 | 5.93012 |
August | 348.00000 | 24.00307 | 58.15239 | 0.00682 | 5.69069 |
September | 330.00000 | 24.03216 | 56.60816 | -0.0287 | 5.87741 |
October | 340.00000 | 24.02075 | 50.72012 | 0.68676 | 15.30263 |
November | 330.00000 | 23.98262 | 49.44813 | 0.61264 | 13.08902 |
December | 338.00000 | 23.96302 | 47.71635 | 0.52651 | 10.99406 |
Annual Sum or Average | 4030.00000 | 23.99341 | 50.28649 | 0.30131 | 9.34228 |
Minimum of Months | 308.00000 | 23.94432 | 43.77545 | -0.1461 | 5.69069 |
Maximum of Months | 348.00000 | 24.04915 | 58.15239 | 0.68676 | 15.30263 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.94349 | 43.81783 | 0.46015 | 9.59977 |
February | 308.00000 | 23.95021 | 46.21660 | 0.50295 | 10.43823 |
March | 348.00000 | 23.95173 | 44.42716 | 0.51531 | 10.77096 |
April | 330.00000 | 24.00504 | 46.70282 | 0.58101 | 12.41837 |
May | 344.00000 | 24.01104 | 48.48232 | -0.1488 | 6.17999 |
June | 336.00000 | 24.00415 | 54.30085 | -0.0806 | 5.89403 |
July | 338.00000 | 24.04899 | 56.83855 | -0.0057 | 5.92877 |
August | 348.00000 | 24.00297 | 58.19430 | 0.00438 | 5.68863 |
September | 330.00000 | 24.03196 | 56.65211 | -0.0311 | 5.87816 |
October | 340.00000 | 24.02047 | 50.75635 | 0.68508 | 15.25315 |
November | 330.00000 | 23.98222 | 49.48934 | 0.61090 | 13.04263 |
December | 338.00000 | 23.96251 | 47.76509 | 0.52462 | 10.95108 |
Annual Sum or Average | 4030.00000 | 23.99307 | 50.32751 | 0.29909 | 9.31676 |
Minimum of Months | 308.00000 | 23.94349 | 43.81783 | -0.1488 | 5.68863 |
Maximum of Months | 348.00000 | 24.04899 | 58.19430 | 0.68508 | 15.25315 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.94306 | 43.84179 | 0.45855 | 9.57336 |
February | 308.00000 | 23.95021 | 46.24789 | 0.50164 | 10.41341 |
March | 348.00000 | 23.95181 | 44.44629 | 0.51449 | 10.75731 |
April | 330.00000 | 24.00538 | 46.70051 | 0.58171 | 12.43913 |
May | 344.00000 | 24.01133 | 48.44074 | -0.1448 | 6.16108 |
June | 336.00000 | 24.00437 | 54.22340 | -0.0757 | 5.88179 |
July | 338.00000 | 24.04931 | 56.73331 | 0.00039 | 5.93246 |
August | 348.00000 | 24.00319 | 58.06386 | 0.01116 | 5.69464 |
September | 330.00000 | 24.03236 | 56.53639 | -0.0252 | 5.87735 |
October | 340.00000 | 24.02098 | 50.67683 | 0.68849 | 15.35448 |
November | 330.00000 | 23.98273 | 49.44314 | 0.61298 | 13.09932 |
December | 338.00000 | 23.96275 | 47.76763 | 0.52456 | 10.95268 |
Annual Sum or Average | 4030.00000 | 23.99330 | 50.28353 | 0.30162 | 9.32461 |
Minimum of Months | 308.00000 | 23.94306 | 43.84179 | -0.1448 | 5.69464 |
Maximum of Months | 348.00000 | 24.04931 | 58.06386 | 0.68849 | 15.35448 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.94620 | 43.85669 | 0.46517 | 9.74194 |
February | 308.00000 | 23.95432 | 46.35601 | 0.51014 | 10.62858 |
March | 348.00000 | 23.95550 | 44.56905 | 0.52663 | 11.07250 |
April | 330.00000 | 24.01237 | 46.75093 | 0.60750 | 13.13199 |
May | 344.00000 | 24.01506 | 48.29598 | -0.0846 | 5.93059 |
June | 336.00000 | 24.00712 | 53.80395 | -0.0091 | 5.80462 |
July | 338.00000 | 24.05295 | 56.11275 | 0.07553 | 6.10034 |
August | 348.00000 | 24.00580 | 57.23632 | 0.09286 | 5.91997 |
September | 330.00000 | 24.03711 | 55.83274 | 0.04872 | 5.98481 |
October | 340.00000 | 24.02696 | 50.27894 | 0.73316 | 16.72484 |
November | 330.00000 | 23.98990 | 49.18104 | 0.64517 | 13.99309 |
December | 338.00000 | 23.96863 | 47.70014 | 0.53860 | 11.30105 |
Annual Sum or Average | 4030.00000 | 23.99782 | 50.01863 | 0.34368 | 9.67347 |
Minimum of Months | 308.00000 | 23.94620 | 43.85669 | -0.0846 | 5.80462 |
Maximum of Months | 348.00000 | 24.05295 | 57.23632 | 0.73316 | 16.72484 |
Report: DXReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.258411E+11 | 0.769946E+10 | 494.92 | 0.212671E+11 | 0.457402E+10 | 0.00 | 0.87 | 29-JAN-08:63 | 0.00 | 01-JAN-00:10 | 38136.49 | 29-JAN-08:63 | 29661.43 | 29-JAN-08:63 | 10359.09 | 30-JAN-08:63 | 9909.55 | 29-JAN-08:63 | 0.00 |
February | 0.276676E+11 | 0.827967E+10 | 453.22 | 0.221944E+11 | 0.547324E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 73085.90 | 09-FEB-08:62 | 46048.56 | 09-FEB-08:62 | 27037.34 | 09-FEB-08:62 | 18759.35 | 09-FEB-08:62 | 0.00 |
March | 0.353445E+11 | 0.107802E+11 | 505.14 | 0.292785E+11 | 0.606598E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 81399.42 | 02-MAR-08:62 | 71235.45 | 02-MAR-08:62 | 22754.04 | 01-MAR-08:62 | 23180.62 | 02-MAR-08:62 | 0.00 |
April | 0.447580E+11 | 0.139170E+11 | 486.65 | 0.358727E+11 | 0.888526E+10 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:05 | 87521.00 | 30-APR-07:02 | 72866.70 | 29-APR-07:02 | 35721.71 | 30-APR-07:02 | 23028.47 | 29-APR-07:02 | 0.00 |
May | 0.611914E+11 | 0.197764E+11 | 503.17 | 0.485053E+11 | 0.126861E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 90169.90 | 30-MAY-07:01 | 75803.42 | 10-MAY-07:01 | 42207.65 | 30-MAY-07:03 | 24758.44 | 23-MAY-07:01 | 0.00 |
June | 0.716865E+11 | 0.230105E+11 | 489.38 | 0.508974E+11 | 0.207892E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 92224.65 | 19-JUN-07:01 | 66991.18 | 02-JUN-07:01 | 48079.53 | 19-JUN-07:03 | 26339.24 | 05-JUN-07:12 | 0.00 |
July | 0.838621E+11 | 0.274982E+11 | 503.75 | 0.575166E+11 | 0.263456E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 92743.25 | 18-JUL-07:01 | 73445.18 | 04-JUL-07:01 | 48925.03 | 18-JUL-07:05 | 26182.64 | 19-JUL-07:12 | 0.00 |
August | 0.879602E+11 | 0.287868E+11 | 504.73 | 0.590103E+11 | 0.289498E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 92911.74 | 08-AUG-07:02 | 68703.95 | 06-AUG-07:01 | 55379.04 | 08-AUG-07:05 | 26658.89 | 05-AUG-07:01 | 0.00 |
September | 0.765322E+11 | 0.240370E+11 | 488.57 | 0.516849E+11 | 0.248473E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 91619.77 | 11-SEP-07:01 | 63746.06 | 02-SEP-07:01 | 46414.16 | 11-SEP-07:11 | 25430.75 | 02-SEP-07:01 | 0.00 |
October | 0.630865E+11 | 0.193628E+11 | 503.32 | 0.468542E+11 | 0.162323E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 91644.78 | 08-OCT-07:01 | 68960.38 | 20-OCT-07:02 | 46728.55 | 08-OCT-07:04 | 24050.04 | 06-OCT-07:01 | 0.00 |
November | 0.466881E+11 | 0.140292E+11 | 485.61 | 0.359261E+11 | 0.107620E+11 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 87663.97 | 03-NOV-07:02 | 67660.82 | 05-NOV-07:02 | 33418.64 | 03-NOV-07:02 | 23366.59 | 20-NOV-08:62 | 0.00 |
December | 0.333588E+11 | 0.987492E+10 | 505.13 | 0.259187E+11 | 0.744003E+10 | 0.00 | 1.00 | 03-DEC-08:62 | 0.00 | 01-DEC-01:05 | 85541.22 | 12-DEC-08:62 | 59499.36 | 12-DEC-08:62 | 26041.85 | 12-DEC-08:62 | 22611.77 | 12-DEC-08:62 | 0.00 |
Annual Sum or Average | 0.657977E+12 | 0.207052E+12 | 5923.60 | 0.484926E+12 | 0.173051E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.258411E+11 | 0.769946E+10 | 453.22 | 0.212671E+11 | 0.457402E+10 | 0.00 | 0.87 | 0.00 | 38136.49 | 29661.43 | 10359.09 | 9909.55 | 0.00 | ||||||
Maximum of Months | 0.879602E+11 | 0.287868E+11 | 505.14 | 0.590103E+11 | 0.289498E+11 | 0.00 | 1.00 | 0.00 | 92911.74 | 75803.42 | 55379.04 | 26658.89 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.133310E+11 | 0.384086E+10 | 498.67 | 0.111125E+11 | 0.221848E+10 | 0.00 | 0.90 | 29-JAN-08:63 | 0.00 | 01-JAN-00:10 | 19971.17 | 29-JAN-08:63 | 16575.72 | 29-JAN-08:63 | 4696.40 | 30-JAN-14:40 | 5000.81 | 29-JAN-08:63 | 0.00 |
February | 0.141009E+11 | 0.408460E+10 | 455.00 | 0.114971E+11 | 0.260378E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 34855.66 | 09-FEB-08:62 | 24870.15 | 09-FEB-08:62 | 9985.51 | 09-FEB-08:62 | 8706.54 | 09-FEB-08:62 | 0.00 |
March | 0.178366E+11 | 0.527295E+10 | 505.03 | 0.149752E+11 | 0.286133E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 41452.57 | 02-MAR-08:62 | 36752.42 | 02-MAR-08:62 | 8409.33 | 01-MAR-08:62 | 11454.49 | 02-MAR-08:62 | 0.00 |
April | 0.221905E+11 | 0.671116E+10 | 486.39 | 0.180800E+11 | 0.411053E+10 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:05 | 43755.68 | 30-APR-07:02 | 38014.93 | 29-APR-07:02 | 13820.37 | 30-APR-07:02 | 11360.65 | 29-APR-07:02 | 0.00 |
May | 0.301684E+11 | 0.952031E+10 | 503.08 | 0.242261E+11 | 0.594228E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 44819.64 | 30-MAY-07:01 | 38991.86 | 10-MAY-07:01 | 16705.47 | 30-MAY-07:02 | 12195.75 | 23-MAY-07:01 | 0.00 |
June | 0.354072E+11 | 0.111169E+11 | 489.34 | 0.254796E+11 | 0.992756E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 45815.20 | 19-JUN-07:01 | 35999.33 | 02-JUN-07:01 | 20384.84 | 19-JUN-07:03 | 13019.16 | 05-JUN-07:01 | 0.00 |
July | 0.417391E+11 | 0.133564E+11 | 503.83 | 0.288446E+11 | 0.128945E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 46213.94 | 18-JUL-07:01 | 38080.56 | 04-JUL-07:01 | 21852.66 | 18-JUL-07:12 | 12946.11 | 19-JUL-07:12 | 0.00 |
August | 0.437308E+11 | 0.139573E+11 | 504.81 | 0.295206E+11 | 0.142102E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 47144.58 | 08-AUG-07:01 | 35831.52 | 06-AUG-07:01 | 24507.72 | 08-AUG-07:12 | 13158.14 | 05-AUG-07:01 | 0.00 |
September | 0.377692E+11 | 0.115966E+11 | 488.38 | 0.258235E+11 | 0.119457E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 45630.49 | 10-SEP-07:01 | 34193.29 | 02-SEP-07:01 | 20598.61 | 11-SEP-07:11 | 12534.32 | 02-SEP-07:01 | 0.00 |
October | 0.309472E+11 | 0.927365E+10 | 503.17 | 0.233096E+11 | 0.763762E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 45655.80 | 08-OCT-07:01 | 36725.22 | 20-OCT-07:02 | 19454.01 | 08-OCT-07:02 | 11884.35 | 02-OCT-07:01 | 0.00 |
November | 0.230184E+11 | 0.672615E+10 | 485.47 | 0.179355E+11 | 0.508295E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 43865.95 | 02-NOV-07:02 | 36120.92 | 12-NOV-08:62 | 13302.61 | 02-NOV-07:02 | 11476.71 | 20-NOV-08:62 | 0.00 |
December | 0.168006E+11 | 0.481991E+10 | 505.10 | 0.132757E+11 | 0.352492E+10 | 0.00 | 1.00 | 03-DEC-08:62 | 0.00 | 01-DEC-01:05 | 42910.94 | 12-DEC-08:62 | 32901.44 | 12-DEC-08:62 | 10009.50 | 12-DEC-08:62 | 11072.66 | 12-DEC-08:62 | 0.00 |
Annual Sum or Average | 0.327040E+12 | 0.100277E+12 | 5928.27 | 0.244080E+12 | 0.829599E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.133310E+11 | 0.384086E+10 | 455.00 | 0.111125E+11 | 0.221848E+10 | 0.00 | 0.90 | 0.00 | 19971.17 | 16575.72 | 4696.40 | 5000.81 | 0.00 | ||||||
Maximum of Months | 0.437308E+11 | 0.139573E+11 | 505.10 | 0.295206E+11 | 0.142102E+11 | 0.00 | 1.00 | 0.00 | 47144.58 | 38991.86 | 24507.72 | 13158.14 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.101789E+11 | 0.292597E+10 | 361.36 | 0.845813E+10 | 0.172076E+10 | 0.00 | 0.95 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 | 22603.72 | 30-JAN-07:03 | 16330.57 | 29-JAN-08:63 | 8134.36 | 30-JAN-07:03 | 5419.87 | 30-JAN-07:03 | 0.00 |
February | 0.110914E+11 | 0.320627E+10 | 333.44 | 0.901352E+10 | 0.207786E+10 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:05 | 43948.41 | 09-FEB-07:03 | 26885.92 | 09-FEB-07:03 | 17062.48 | 09-FEB-07:03 | 11035.59 | 09-FEB-07:03 | 0.00 |
March | 0.143719E+11 | 0.424496E+10 | 377.88 | 0.120827E+11 | 0.228918E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 42756.00 | 29-MAR-06:03 | 39040.16 | 28-MAR-06:02 | 17254.46 | 29-MAR-06:03 | 11676.66 | 02-MAR-07:02 | 0.00 |
April | 0.177975E+11 | 0.536895E+10 | 359.56 | 0.145661E+11 | 0.323140E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 45229.09 | 30-APR-07:02 | 36849.69 | 29-APR-06:02 | 19203.22 | 30-APR-07:02 | 11382.45 | 17-APR-06:02 | 0.00 |
May | 0.246889E+11 | 0.774003E+10 | 382.24 | 0.198820E+11 | 0.480687E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 46732.77 | 01-MAY-06:02 | 37810.19 | 11-MAY-06:01 | 25583.70 | 01-MAY-06:02 | 12269.90 | 23-MAY-06:01 | 0.00 |
June | 0.290256E+11 | 0.909937E+10 | 375.94 | 0.209722E+11 | 0.805341E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 47741.09 | 19-JUN-06:01 | 35412.65 | 01-JUN-06:01 | 28581.93 | 19-JUN-06:03 | 12772.25 | 29-JUN-06:03 | 0.00 |
July | 0.338873E+11 | 0.108319E+11 | 384.06 | 0.232593E+11 | 0.106281E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 47611.10 | 06-JUL-06:01 | 37807.73 | 04-JUL-07:01 | 29465.36 | 31-JUL-06:04 | 12843.49 | 16-JUL-07:14 | 0.00 |
August | 0.362122E+11 | 0.115590E+11 | 394.23 | 0.242806E+11 | 0.119317E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 47515.45 | 26-AUG-06:01 | 32568.39 | 16-AUG-06:01 | 28522.53 | 27-AUG-07:04 | 13121.76 | 06-AUG-07:01 | 0.00 |
September | 0.306057E+11 | 0.938138E+10 | 369.75 | 0.209366E+11 | 0.966907E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 47888.09 | 25-SEP-06:01 | 29584.05 | 05-SEP-06:01 | 31784.15 | 11-SEP-06:02 | 12579.82 | 04-SEP-07:12 | 0.00 |
October | 0.252541E+11 | 0.748730E+10 | 375.89 | 0.189174E+11 | 0.633673E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 47889.49 | 01-OCT-07:01 | 35443.87 | 20-OCT-06:02 | 29133.12 | 08-OCT-07:04 | 11875.43 | 02-OCT-06:13 | 0.00 |
November | 0.189272E+11 | 0.548021E+10 | 359.03 | 0.145649E+11 | 0.436228E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 45699.83 | 03-NOV-06:02 | 34883.31 | 19-NOV-08:62 | 19983.49 | 03-NOV-06:02 | 11463.19 | 25-NOV-07:02 | 0.00 |
December | 0.132095E+11 | 0.377770E+10 | 368.16 | 0.103584E+11 | 0.285110E+10 | 0.00 | 1.00 | 03-DEC-08:62 | 0.00 | 01-DEC-00:10 | 43652.06 | 12-DEC-07:02 | 30567.14 | 12-DEC-07:02 | 16216.99 | 11-DEC-07:03 | 11187.36 | 12-DEC-07:02 | 0.00 |
Annual Sum or Average | 0.265250E+12 | 0.811030E+11 | 4441.56 | 0.197292E+12 | 0.679584E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.101789E+11 | 0.292597E+10 | 333.44 | 0.845813E+10 | 0.172076E+10 | 0.00 | 0.95 | 0.00 | 22603.72 | 16330.57 | 8134.36 | 5419.87 | 0.00 | ||||||
Maximum of Months | 0.362122E+11 | 0.115590E+11 | 394.23 | 0.242806E+11 | 0.119317E+11 | 0.00 | 1.00 | 0.00 | 47889.49 | 39040.16 | 31784.15 | 13121.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.101365E+11 | 0.291520E+10 | 361.19 | 0.842069E+10 | 0.171583E+10 | 0.00 | 0.95 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 | 22571.33 | 30-JAN-07:03 | 16085.53 | 29-JAN-08:63 | 8124.42 | 30-JAN-07:03 | 5415.54 | 30-JAN-07:03 | 0.00 |
February | 0.110772E+11 | 0.320306E+10 | 333.28 | 0.900189E+10 | 0.207530E+10 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:05 | 44425.43 | 09-FEB-07:03 | 27196.00 | 09-FEB-07:03 | 17229.43 | 09-FEB-07:03 | 11161.57 | 09-FEB-07:03 | 0.00 |
March | 0.143909E+11 | 0.425067E+10 | 378.16 | 0.121003E+11 | 0.229062E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 43780.84 | 29-MAR-06:03 | 39171.07 | 28-MAR-06:02 | 17627.62 | 29-MAR-06:03 | 11692.06 | 02-MAR-07:02 | 0.00 |
April | 0.178687E+11 | 0.538874E+10 | 359.87 | 0.146306E+11 | 0.323805E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 45303.68 | 30-APR-07:02 | 37001.33 | 29-APR-06:02 | 19118.96 | 30-APR-07:02 | 11398.39 | 17-APR-06:02 | 0.00 |
May | 0.248421E+11 | 0.778430E+10 | 382.59 | 0.200204E+11 | 0.482163E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 46810.83 | 01-MAY-06:02 | 37967.18 | 11-MAY-06:01 | 25455.26 | 01-MAY-06:02 | 12285.95 | 23-MAY-06:01 | 0.00 |
June | 0.291970E+11 | 0.915107E+10 | 376.07 | 0.211215E+11 | 0.807544E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 47800.41 | 19-JUN-06:01 | 35607.42 | 01-JUN-06:01 | 28409.69 | 19-JUN-06:03 | 12788.17 | 29-JUN-06:03 | 0.00 |
July | 0.341074E+11 | 0.109022E+11 | 384.37 | 0.234498E+11 | 0.106577E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 47670.26 | 06-JUL-06:01 | 38038.44 | 04-JUL-07:01 | 29269.75 | 31-JUL-06:04 | 12859.28 | 16-JUL-07:14 | 0.00 |
August | 0.364341E+11 | 0.116309E+11 | 395.38 | 0.244712E+11 | 0.119629E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 47574.49 | 26-AUG-06:01 | 32772.76 | 16-AUG-06:01 | 28399.26 | 27-AUG-07:04 | 13138.11 | 06-AUG-07:01 | 0.00 |
September | 0.307933E+11 | 0.943787E+10 | 370.32 | 0.210980E+11 | 0.969535E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 47972.33 | 25-SEP-06:01 | 29980.70 | 05-SEP-06:01 | 31549.77 | 11-SEP-06:04 | 12595.36 | 04-SEP-07:12 | 0.00 |
October | 0.254083E+11 | 0.752888E+10 | 375.97 | 0.190525E+11 | 0.635581E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 47949.00 | 01-OCT-07:01 | 35596.32 | 20-OCT-06:02 | 29042.62 | 08-OCT-07:04 | 11890.14 | 02-OCT-06:13 | 0.00 |
November | 0.189982E+11 | 0.549900E+10 | 359.12 | 0.146282E+11 | 0.437001E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 45773.51 | 03-NOV-06:02 | 34979.46 | 19-NOV-08:62 | 19914.18 | 03-NOV-06:02 | 11478.44 | 25-NOV-07:02 | 0.00 |
December | 0.132086E+11 | 0.377803E+10 | 368.08 | 0.103582E+11 | 0.285030E+10 | 0.00 | 1.00 | 03-DEC-08:62 | 0.00 | 01-DEC-00:10 | 43711.66 | 12-DEC-07:02 | 30633.54 | 12-DEC-07:02 | 16397.68 | 11-DEC-07:03 | 11202.02 | 12-DEC-07:02 | 0.00 |
Annual Sum or Average | 0.266462E+12 | 0.814699E+11 | 4444.39 | 0.198353E+12 | 0.681089E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.101365E+11 | 0.291520E+10 | 333.28 | 0.842069E+10 | 0.171583E+10 | 0.00 | 0.95 | 0.00 | 22571.33 | 16085.53 | 8124.42 | 5415.54 | 0.00 | ||||||
Maximum of Months | 0.364341E+11 | 0.116309E+11 | 395.38 | 0.244712E+11 | 0.119629E+11 | 0.00 | 1.00 | 0.00 | 47972.33 | 39171.07 | 31549.77 | 13138.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.995363E+10 | 0.286663E+10 | 358.78 | 0.825845E+10 | 0.169518E+10 | 0.00 | 0.92 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 | 21612.86 | 30-JAN-07:03 | 15333.58 | 29-JAN-08:63 | 7817.38 | 30-JAN-07:03 | 5237.91 | 30-JAN-07:03 | 0.00 |
February | 0.109253E+11 | 0.316332E+10 | 332.61 | 0.886999E+10 | 0.205533E+10 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:05 | 42840.09 | 09-FEB-07:03 | 26167.63 | 09-FEB-07:03 | 16672.46 | 09-FEB-07:03 | 10739.66 | 09-FEB-07:03 | 0.00 |
March | 0.142349E+11 | 0.420997E+10 | 377.96 | 0.119607E+11 | 0.227419E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 42194.60 | 29-MAR-06:03 | 39069.43 | 28-MAR-06:02 | 17051.14 | 29-MAR-06:03 | 11681.34 | 02-MAR-07:02 | 0.00 |
April | 0.177417E+11 | 0.535556E+10 | 359.61 | 0.145170E+11 | 0.322470E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 45267.61 | 30-APR-07:02 | 36877.54 | 29-APR-06:02 | 19151.77 | 30-APR-07:02 | 11389.86 | 17-APR-06:02 | 0.00 |
May | 0.247616E+11 | 0.776078E+10 | 382.20 | 0.199464E+11 | 0.481522E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 46778.78 | 01-MAY-06:02 | 37849.38 | 11-MAY-06:01 | 25463.24 | 01-MAY-06:02 | 12277.44 | 23-MAY-06:01 | 0.00 |
June | 0.291263E+11 | 0.912844E+10 | 375.89 | 0.210591E+11 | 0.806715E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 47768.06 | 19-JUN-06:01 | 35507.29 | 01-JUN-06:01 | 28380.79 | 19-JUN-06:03 | 12779.49 | 29-JUN-06:03 | 0.00 |
July | 0.340767E+11 | 0.108902E+11 | 384.36 | 0.234226E+11 | 0.106541E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 47637.99 | 06-JUL-06:01 | 37964.98 | 04-JUL-07:01 | 29229.27 | 31-JUL-06:06 | 12850.54 | 16-JUL-07:14 | 0.00 |
August | 0.363978E+11 | 0.116163E+11 | 394.95 | 0.244398E+11 | 0.119580E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 47542.29 | 26-AUG-06:01 | 32680.17 | 16-AUG-06:01 | 28410.01 | 27-AUG-07:04 | 13129.22 | 06-AUG-07:01 | 0.00 |
September | 0.307360E+11 | 0.941962E+10 | 370.05 | 0.210489E+11 | 0.968710E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 47941.95 | 25-SEP-06:01 | 30021.98 | 05-SEP-06:01 | 31506.06 | 11-SEP-06:04 | 12586.93 | 04-SEP-07:12 | 0.00 |
October | 0.253307E+11 | 0.750742E+10 | 375.58 | 0.189840E+11 | 0.634669E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 47916.55 | 01-OCT-07:01 | 35489.44 | 20-OCT-06:02 | 29053.07 | 08-OCT-07:04 | 11882.13 | 02-OCT-06:13 | 0.00 |
November | 0.188858E+11 | 0.547073E+10 | 359.00 | 0.145298E+11 | 0.435599E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 45731.48 | 03-NOV-06:02 | 34902.60 | 19-NOV-08:62 | 19991.70 | 03-NOV-06:02 | 11469.45 | 25-NOV-07:02 | 0.00 |
December | 0.130493E+11 | 0.373706E+10 | 367.88 | 0.102207E+11 | 0.282861E+10 | 0.00 | 1.00 | 03-DEC-08:62 | 0.00 | 01-DEC-00:10 | 43668.66 | 12-DEC-07:02 | 30528.30 | 12-DEC-07:02 | 15999.52 | 11-DEC-07:03 | 11192.53 | 12-DEC-07:02 | 0.00 |
Annual Sum or Average | 0.265220E+12 | 0.811260E+11 | 4438.86 | 0.197257E+12 | 0.679623E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.995363E+10 | 0.286663E+10 | 332.61 | 0.825845E+10 | 0.169518E+10 | 0.00 | 0.92 | 0.00 | 21612.86 | 15333.58 | 7817.38 | 5237.91 | 0.00 | ||||||
Maximum of Months | 0.363978E+11 | 0.116163E+11 | 394.95 | 0.244398E+11 | 0.119580E+11 | 0.00 | 1.00 | 0.00 | 47941.95 | 39069.43 | 31506.06 | 13129.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.171742E+11 | 0.513090E+10 | 346.75 | 0.139109E+11 | 0.326324E+10 | 0.00 | 1.00 | 29-JAN-09:03 | 0.00 | 01-JAN-00:10 | 44528.64 | 29-JAN-09:03 | 32075.70 | 29-JAN-09:03 | 13831.56 | 30-JAN-08:63 | 11226.67 | 29-JAN-09:03 | 0.00 |
February | 0.191272E+11 | 0.574001E+10 | 322.11 | 0.151950E+11 | 0.393223E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 67832.51 | 09-FEB-08:62 | 44206.69 | 06-FEB-08:62 | 25590.80 | 09-FEB-08:62 | 17392.80 | 09-FEB-08:62 | 0.00 |
March | 0.253712E+11 | 0.777210E+10 | 369.50 | 0.209128E+11 | 0.445839E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 77541.39 | 02-MAR-08:62 | 67945.93 | 28-MAR-07:02 | 23321.56 | 29-MAR-07:03 | 21974.38 | 02-MAR-08:62 | 0.00 |
April | 0.319289E+11 | 0.997300E+10 | 349.33 | 0.257184E+11 | 0.621053E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 83719.07 | 30-APR-08:62 | 68073.26 | 29-APR-07:02 | 36840.39 | 30-APR-08:62 | 21902.73 | 28-APR-07:02 | 0.00 |
May | 0.451118E+11 | 0.146310E+11 | 369.09 | 0.358701E+11 | 0.924176E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 86168.27 | 01-MAY-07:02 | 70231.85 | 11-MAY-07:01 | 47502.95 | 01-MAY-07:02 | 24231.98 | 28-MAY-08:61 | 0.00 |
June | 0.531720E+11 | 0.172422E+11 | 362.21 | 0.379347E+11 | 0.152373E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 88150.35 | 25-JUN-08:61 | 65225.12 | 01-JUN-07:01 | 51739.65 | 19-JUN-07:03 | 24820.56 | 11-JUN-08:13 | 0.00 |
July | 0.620411E+11 | 0.205195E+11 | 364.73 | 0.421195E+11 | 0.199216E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 87374.31 | 05-JUL-07:01 | 71007.32 | 04-JUL-08:61 | 53006.17 | 05-JUL-07:06 | 25267.58 | 23-JUL-08:12 | 0.00 |
August | 0.666920E+11 | 0.220140E+11 | 376.72 | 0.441698E+11 | 0.225222E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 87535.81 | 08-AUG-07:01 | 60298.70 | 05-AUG-07:01 | 52275.33 | 27-AUG-08:07 | 25324.11 | 06-AUG-08:02 | 0.00 |
September | 0.561454E+11 | 0.177979E+11 | 355.35 | 0.378594E+11 | 0.182860E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 88282.69 | 25-SEP-07:01 | 57532.04 | 02-SEP-07:01 | 58278.56 | 11-SEP-07:03 | 24631.28 | 04-SEP-08:12 | 0.00 |
October | 0.459237E+11 | 0.140947E+11 | 363.60 | 0.340442E+11 | 0.118794E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 88125.10 | 02-OCT-07:02 | 65235.91 | 20-OCT-07:02 | 53474.72 | 08-OCT-08:04 | 23037.55 | 08-OCT-08:12 | 0.00 |
November | 0.339875E+11 | 0.101877E+11 | 349.97 | 0.256841E+11 | 0.830333E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 82817.70 | 03-NOV-07:02 | 65412.38 | 19-NOV-09:02 | 32806.62 | 03-NOV-07:02 | 22047.91 | 20-NOV-08:62 | 0.00 |
December | 0.228829E+11 | 0.678773E+10 | 355.85 | 0.175228E+11 | 0.536007E+10 | 0.00 | 1.00 | 03-DEC-09:02 | 0.00 | 01-DEC-00:10 | 79928.76 | 12-DEC-08:62 | 57013.86 | 12-DEC-08:62 | 27369.34 | 03-DEC-09:02 | 21203.52 | 12-DEC-08:62 | 0.00 |
Annual Sum or Average | 0.479558E+12 | 0.151891E+12 | 4285.20 | 0.350942E+12 | 0.128616E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.171742E+11 | 0.513090E+10 | 322.11 | 0.139109E+11 | 0.326324E+10 | 0.00 | 1.00 | 0.00 | 44528.64 | 32075.70 | 13831.56 | 11226.67 | 0.00 | ||||||
Maximum of Months | 0.666920E+11 | 0.220140E+11 | 376.72 | 0.441698E+11 | 0.225222E+11 | 0.00 | 1.00 | 0.00 | 88282.69 | 71007.32 | 58278.56 | 25324.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.892116E+10 | 0.258363E+10 | 345.58 | 0.724334E+10 | 0.167782E+10 | 0.00 | 0.95 | 29-JAN-09:03 | 0.00 | 01-JAN-00:10 | 21181.79 | 29-JAN-09:03 | 15244.65 | 29-JAN-09:03 | 6688.31 | 30-JAN-08:63 | 5248.39 | 29-JAN-09:03 | 0.00 |
February | 0.993184E+10 | 0.288966E+10 | 322.03 | 0.790785E+10 | 0.202400E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 32573.84 | 06-FEB-08:62 | 21571.66 | 06-FEB-08:62 | 11946.21 | 09-FEB-08:62 | 7992.12 | 06-FEB-08:62 | 0.00 |
March | 0.131808E+11 | 0.391526E+10 | 369.78 | 0.108860E+11 | 0.229479E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 40478.80 | 02-MAR-08:62 | 33160.44 | 02-MAR-08:62 | 10750.48 | 29-MAR-07:03 | 11117.80 | 02-MAR-08:62 | 0.00 |
April | 0.166099E+11 | 0.503011E+10 | 349.59 | 0.133943E+11 | 0.321561E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 43775.32 | 30-APR-08:62 | 35519.04 | 29-APR-07:02 | 19487.85 | 30-APR-08:62 | 11081.57 | 28-APR-07:02 | 0.00 |
May | 0.234717E+11 | 0.738502E+10 | 369.09 | 0.186758E+11 | 0.479590E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 45091.80 | 01-MAY-07:02 | 36609.18 | 11-MAY-07:01 | 25125.19 | 01-MAY-07:02 | 12265.92 | 28-MAY-08:61 | 0.00 |
June | 0.276479E+11 | 0.870364E+10 | 362.01 | 0.197403E+11 | 0.790767E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 46091.07 | 25-JUN-08:61 | 34051.45 | 01-JUN-07:01 | 27270.73 | 19-JUN-07:03 | 12563.87 | 11-JUN-08:13 | 0.00 |
July | 0.322736E+11 | 0.103615E+11 | 364.38 | 0.219253E+11 | 0.103483E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 45656.36 | 05-JUL-07:01 | 37043.50 | 04-JUL-08:61 | 27904.96 | 05-JUL-07:06 | 12790.42 | 23-JUL-08:12 | 0.00 |
August | 0.346683E+11 | 0.111063E+11 | 376.29 | 0.229746E+11 | 0.116938E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 45729.13 | 21-AUG-07:01 | 31374.61 | 05-AUG-07:01 | 27514.55 | 27-AUG-08:06 | 12819.18 | 06-AUG-08:02 | 0.00 |
September | 0.291892E+11 | 0.898140E+10 | 354.88 | 0.197010E+11 | 0.948815E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 46185.78 | 25-SEP-07:01 | 29985.48 | 02-SEP-07:01 | 30791.78 | 11-SEP-07:02 | 12468.38 | 04-SEP-08:12 | 0.00 |
October | 0.238829E+11 | 0.711129E+10 | 363.40 | 0.177331E+11 | 0.614988E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 46048.68 | 02-OCT-07:02 | 34065.77 | 20-OCT-07:02 | 28185.28 | 08-OCT-08:04 | 11661.75 | 08-OCT-08:12 | 0.00 |
November | 0.176828E+11 | 0.513947E+10 | 349.90 | 0.133848E+11 | 0.429795E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 43220.76 | 03-NOV-07:02 | 34112.08 | 19-NOV-09:02 | 17067.54 | 03-NOV-07:02 | 11158.73 | 20-NOV-08:62 | 0.00 |
December | 0.119020E+11 | 0.342241E+10 | 356.23 | 0.913322E+10 | 0.276879E+10 | 0.00 | 1.00 | 03-DEC-09:02 | 0.00 | 01-DEC-00:10 | 41737.37 | 12-DEC-08:62 | 29796.72 | 12-DEC-08:62 | 13313.93 | 11-DEC-08:62 | 10729.06 | 12-DEC-08:62 | 0.00 |
Annual Sum or Average | 0.249362E+12 | 0.766296E+11 | 4283.15 | 0.182700E+12 | 0.666626E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.892116E+10 | 0.258363E+10 | 322.03 | 0.724334E+10 | 0.167782E+10 | 0.00 | 0.95 | 0.00 | 21181.79 | 15244.65 | 6688.31 | 5248.39 | 0.00 | ||||||
Maximum of Months | 0.346683E+11 | 0.111063E+11 | 376.29 | 0.229746E+11 | 0.116938E+11 | 0.00 | 1.00 | 0.00 | 46185.78 | 37043.50 | 30791.78 | 12819.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.883776E+10 | 0.256083E+10 | 345.17 | 0.716979E+10 | 0.166797E+10 | 0.00 | 0.93 | 29-JAN-09:03 | 0.00 | 01-JAN-00:10 | 20733.98 | 29-JAN-09:03 | 14900.43 | 29-JAN-09:03 | 6524.73 | 30-JAN-08:63 | 5160.09 | 29-JAN-09:03 | 0.00 |
February | 0.985095E+10 | 0.286763E+10 | 320.90 | 0.783766E+10 | 0.201329E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 32001.57 | 06-FEB-08:62 | 21179.19 | 06-FEB-08:62 | 11714.43 | 09-FEB-08:62 | 7842.13 | 06-FEB-08:62 | 0.00 |
March | 0.130895E+11 | 0.389000E+10 | 369.66 | 0.108044E+11 | 0.228508E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 40361.25 | 02-MAR-08:62 | 33018.58 | 02-MAR-08:62 | 10524.70 | 29-MAR-07:03 | 11086.22 | 02-MAR-08:62 | 0.00 |
April | 0.165241E+11 | 0.500572E+10 | 349.54 | 0.133177E+11 | 0.320647E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 43650.83 | 30-APR-08:62 | 35371.14 | 29-APR-07:02 | 19476.06 | 30-APR-08:62 | 11050.04 | 28-APR-07:02 | 0.00 |
May | 0.233841E+11 | 0.735773E+10 | 369.12 | 0.185961E+11 | 0.478801E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 44965.71 | 01-MAY-07:02 | 36463.03 | 11-MAY-07:01 | 25098.35 | 01-MAY-07:02 | 12231.91 | 28-MAY-08:61 | 0.00 |
June | 0.275594E+11 | 0.867504E+10 | 361.92 | 0.196624E+11 | 0.789700E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 45963.53 | 25-JUN-08:61 | 33910.59 | 01-JUN-07:01 | 27217.45 | 19-JUN-07:03 | 12529.19 | 11-JUN-08:13 | 0.00 |
July | 0.321871E+11 | 0.103320E+11 | 364.24 | 0.218492E+11 | 0.103378E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 45530.01 | 05-JUL-07:01 | 36903.77 | 04-JUL-08:61 | 27845.41 | 05-JUL-07:06 | 12755.06 | 23-JUL-08:12 | 0.00 |
August | 0.345774E+11 | 0.110751E+11 | 376.07 | 0.228952E+11 | 0.116822E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 45602.59 | 21-AUG-07:01 | 31240.98 | 05-AUG-07:01 | 27460.25 | 27-AUG-08:06 | 12783.71 | 06-AUG-08:02 | 0.00 |
September | 0.291047E+11 | 0.895438E+10 | 354.77 | 0.196278E+11 | 0.947689E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 46057.97 | 25-SEP-07:01 | 29852.55 | 02-SEP-07:01 | 30731.54 | 11-SEP-07:02 | 12433.97 | 04-SEP-08:12 | 0.00 |
October | 0.238001E+11 | 0.708664E+10 | 363.40 | 0.176596E+11 | 0.614054E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 45921.25 | 02-OCT-07:01 | 33929.26 | 20-OCT-07:02 | 28138.22 | 08-OCT-08:04 | 11629.17 | 08-OCT-08:12 | 0.00 |
November | 0.176026E+11 | 0.511721E+10 | 349.86 | 0.133143E+11 | 0.428825E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 43101.32 | 03-NOV-07:02 | 33980.53 | 19-NOV-09:02 | 17076.11 | 03-NOV-07:02 | 11127.43 | 20-NOV-08:62 | 0.00 |
December | 0.118189E+11 | 0.339992E+10 | 356.39 | 0.906172E+10 | 0.275718E+10 | 0.00 | 1.00 | 03-DEC-09:02 | 0.00 | 01-DEC-00:10 | 41618.13 | 12-DEC-08:62 | 29671.24 | 12-DEC-08:62 | 13145.78 | 11-DEC-08:62 | 10698.79 | 12-DEC-08:62 | 0.00 |
Annual Sum or Average | 0.248337E+12 | 0.763222E+11 | 4281.04 | 0.181796E+12 | 0.665407E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.883776E+10 | 0.256083E+10 | 320.90 | 0.716979E+10 | 0.166797E+10 | 0.00 | 0.93 | 0.00 | 20733.98 | 14900.43 | 6524.73 | 5160.09 | 0.00 | ||||||
Maximum of Months | 0.345774E+11 | 0.110751E+11 | 376.07 | 0.228952E+11 | 0.116822E+11 | 0.00 | 1.00 | 0.00 | 46057.97 | 36903.77 | 30731.54 | 12783.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.880891E+10 | 0.255393E+10 | 344.50 | 0.714587E+10 | 0.166303E+10 | 0.00 | 0.91 | 29-JAN-09:03 | 0.00 | 01-JAN-00:10 | 20199.83 | 29-JAN-09:03 | 14503.55 | 29-JAN-09:03 | 6375.17 | 30-JAN-08:63 | 5062.76 | 29-JAN-09:03 | 0.00 |
February | 0.982210E+10 | 0.286111E+10 | 320.21 | 0.781488E+10 | 0.200721E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 31402.76 | 06-FEB-08:62 | 20793.47 | 06-FEB-08:62 | 11478.48 | 09-FEB-08:62 | 7680.17 | 06-FEB-08:62 | 0.00 |
March | 0.130740E+11 | 0.388782E+10 | 369.17 | 0.107929E+11 | 0.228112E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 40533.02 | 02-MAR-08:62 | 33173.12 | 02-MAR-08:62 | 10305.71 | 29-MAR-07:03 | 11133.60 | 02-MAR-08:62 | 0.00 |
April | 0.165585E+11 | 0.501813E+10 | 349.75 | 0.133503E+11 | 0.320818E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 43834.95 | 30-APR-08:62 | 35558.24 | 29-APR-07:02 | 19537.91 | 30-APR-08:62 | 11097.24 | 28-APR-07:02 | 0.00 |
May | 0.235109E+11 | 0.739802E+10 | 369.09 | 0.187116E+11 | 0.479926E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 45155.71 | 01-MAY-07:02 | 36680.23 | 11-MAY-07:01 | 25177.70 | 01-MAY-07:02 | 12284.58 | 28-MAY-08:61 | 0.00 |
June | 0.277242E+11 | 0.872829E+10 | 361.99 | 0.198066E+11 | 0.791758E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 46161.00 | 25-JUN-08:61 | 34138.47 | 01-JUN-07:01 | 27264.88 | 19-JUN-07:03 | 12582.92 | 11-JUN-08:13 | 0.00 |
July | 0.323994E+11 | 0.104033E+11 | 364.36 | 0.220339E+11 | 0.103655E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 45725.62 | 05-JUL-07:04 | 37165.31 | 04-JUL-08:61 | 27890.96 | 05-JUL-07:06 | 12809.85 | 23-JUL-08:12 | 0.00 |
August | 0.348306E+11 | 0.111605E+11 | 376.29 | 0.231134E+11 | 0.117173E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 45798.51 | 21-AUG-07:01 | 31536.59 | 05-AUG-07:01 | 27489.70 | 27-AUG-08:06 | 12838.72 | 06-AUG-08:02 | 0.00 |
September | 0.293117E+11 | 0.902001E+10 | 354.85 | 0.198052E+11 | 0.950651E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 46255.85 | 25-SEP-07:01 | 30116.60 | 02-SEP-07:01 | 30704.63 | 11-SEP-07:02 | 12487.39 | 04-SEP-08:12 | 0.00 |
October | 0.239699E+11 | 0.713644E+10 | 363.56 | 0.178089E+11 | 0.616096E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 46118.54 | 02-OCT-07:01 | 34141.28 | 20-OCT-07:02 | 28171.21 | 08-OCT-08:04 | 11679.67 | 08-OCT-08:12 | 0.00 |
November | 0.177001E+11 | 0.514499E+10 | 349.91 | 0.134006E+11 | 0.429942E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 43286.99 | 03-NOV-07:02 | 34158.74 | 19-NOV-09:02 | 17064.33 | 03-NOV-07:02 | 11176.18 | 20-NOV-08:62 | 0.00 |
December | 0.118309E+11 | 0.340444E+10 | 355.73 | 0.907364E+10 | 0.275722E+10 | 0.00 | 1.00 | 03-DEC-09:02 | 0.00 | 01-DEC-00:10 | 41796.55 | 12-DEC-08:62 | 29819.63 | 12-DEC-08:62 | 13139.48 | 11-DEC-08:62 | 10744.70 | 12-DEC-08:62 | 0.00 |
Annual Sum or Average | 0.249541E+12 | 0.767171E+11 | 4279.40 | 0.182858E+12 | 0.666833E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.880891E+10 | 0.255393E+10 | 320.21 | 0.714587E+10 | 0.166303E+10 | 0.00 | 0.91 | 0.00 | 20199.83 | 14503.55 | 6375.17 | 5062.76 | 0.00 | ||||||
Maximum of Months | 0.348306E+11 | 0.111605E+11 | 376.29 | 0.231134E+11 | 0.117173E+11 | 0.00 | 1.00 | 0.00 | 46255.85 | 37165.31 | 30704.63 | 12838.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.940134E+10 | 0.273234E+10 | 341.83 | 0.772221E+10 | 0.167914E+10 | 0.00 | 0.82 | 29-JAN-09:03 | 0.00 | 01-JAN-00:10 | 19309.99 | 29-JAN-09:03 | 13587.38 | 29-JAN-09:03 | 5722.61 | 29-JAN-09:03 | 4980.51 | 29-JAN-09:03 | 0.00 |
February | 0.104119E+11 | 0.304433E+10 | 317.61 | 0.837558E+10 | 0.203636E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 29452.95 | 06-FEB-08:62 | 18119.33 | 06-FEB-08:62 | 11641.82 | 09-FEB-08:62 | 7049.01 | 06-FEB-08:62 | 0.00 |
March | 0.138658E+11 | 0.414160E+10 | 366.53 | 0.115620E+11 | 0.230383E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 43835.73 | 02-MAR-08:62 | 38370.07 | 02-MAR-08:62 | 9757.37 | 29-MAR-07:03 | 12108.01 | 02-MAR-08:62 | 0.00 |
April | 0.178146E+11 | 0.542046E+10 | 350.56 | 0.145050E+11 | 0.330960E+10 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:05 | 48668.97 | 30-APR-08:62 | 37770.58 | 29-APR-07:02 | 24006.87 | 30-APR-08:62 | 12125.54 | 17-APR-07:02 | 0.00 |
May | 0.256397E+11 | 0.808239E+10 | 370.21 | 0.206281E+11 | 0.501163E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 50381.40 | 30-MAY-07:01 | 40723.56 | 11-MAY-07:01 | 27884.11 | 01-MAY-07:02 | 13470.87 | 28-MAY-08:61 | 0.00 |
June | 0.302933E+11 | 0.955200E+10 | 362.73 | 0.219342E+11 | 0.835913E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 50567.74 | 25-JUN-08:02 | 36442.07 | 01-JUN-07:01 | 31283.38 | 19-JUN-07:03 | 13785.92 | 11-JUN-08:13 | 0.00 |
July | 0.355088E+11 | 0.114316E+11 | 369.42 | 0.245236E+11 | 0.109852E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 50183.39 | 26-JUL-07:01 | 41276.10 | 04-JUL-08:61 | 32443.45 | 05-JUL-07:04 | 14032.44 | 23-JUL-08:13 | 0.00 |
August | 0.383679E+11 | 0.123358E+11 | 381.75 | 0.259402E+11 | 0.124277E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 50183.39 | 08-AUG-07:06 | 34941.40 | 06-AUG-08:61 | 31920.60 | 08-AUG-07:05 | 14063.04 | 06-AUG-08:61 | 0.00 |
September | 0.322033E+11 | 0.993180E+10 | 357.70 | 0.221557E+11 | 0.100476E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 50671.64 | 25-SEP-07:01 | 32574.40 | 26-SEP-07:01 | 34515.13 | 11-SEP-07:01 | 13679.61 | 04-SEP-08:12 | 0.00 |
October | 0.263611E+11 | 0.785552E+10 | 365.09 | 0.198578E+11 | 0.650326E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 50521.22 | 02-OCT-07:01 | 37030.92 | 20-OCT-07:02 | 32110.14 | 08-OCT-08:03 | 12782.47 | 08-OCT-08:14 | 0.00 |
November | 0.193320E+11 | 0.562853E+10 | 350.45 | 0.148478E+11 | 0.448423E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 48243.63 | 03-NOV-07:02 | 36627.14 | 19-NOV-09:02 | 21332.91 | 03-NOV-07:02 | 12290.26 | 20-NOV-08:62 | 0.00 |
December | 0.126927E+11 | 0.366356E+10 | 354.96 | 0.986874E+10 | 0.282393E+10 | 0.00 | 1.00 | 03-DEC-09:02 | 0.00 | 01-DEC-00:10 | 45225.07 | 12-DEC-08:62 | 30610.16 | 12-DEC-08:62 | 14614.91 | 12-DEC-08:62 | 11545.60 | 12-DEC-08:62 | 0.00 |
Annual Sum or Average | 0.271892E+12 | 0.838199E+11 | 4288.84 | 0.201921E+12 | 0.699716E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.940134E+10 | 0.273234E+10 | 317.61 | 0.772221E+10 | 0.167914E+10 | 0.00 | 0.82 | 0.00 | 19309.99 | 13587.38 | 5722.61 | 4980.51 | 0.00 | ||||||
Maximum of Months | 0.383679E+11 | 0.123358E+11 | 381.75 | 0.259402E+11 | 0.124277E+11 | 0.00 | 1.00 | 0.00 | 50671.64 | 41276.10 | 34515.13 | 14063.04 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 248.82 | 148.04 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 255.54 | 126.34 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 246.01 | 96.41 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 242.65 | 59.18 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 287.42 | 15.82 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 303.89 | 5.06 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 365.85 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 405.84 | 0.14 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 398.62 | 7.99 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 399.81 | 27.19 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 352.52 | 68.60 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 271.16 | 122.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 315.23 | 56.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 242.65 | 0.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 405.84 | 148.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 248.82 | 148.04 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 255.54 | 126.34 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 246.01 | 96.41 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 242.65 | 59.18 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 287.42 | 15.82 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 303.89 | 5.06 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 365.85 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 405.84 | 0.14 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 398.62 | 7.99 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 399.81 | 27.19 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 352.52 | 68.60 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 271.16 | 122.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 315.23 | 56.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 242.65 | 0.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 405.84 | 148.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 248.82 | 148.04 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 255.54 | 126.34 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 246.01 | 96.41 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 242.65 | 59.18 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 287.42 | 15.82 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 303.89 | 5.06 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 365.85 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 405.84 | 0.14 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 398.62 | 7.99 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 399.81 | 27.19 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 352.52 | 68.60 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 271.16 | 122.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 315.23 | 56.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 242.65 | 0.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 405.84 | 148.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 248.82 | 148.04 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 255.54 | 126.34 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 246.01 | 96.41 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 242.65 | 59.18 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 287.42 | 15.82 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 303.89 | 5.06 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 365.85 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 405.84 | 0.14 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 398.62 | 7.99 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 399.81 | 27.19 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 352.52 | 68.60 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 271.16 | 122.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 315.23 | 56.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 242.65 | 0.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 405.84 | 148.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.15 | 25.23 | 28.92 | 125.71 | 73.70 | 0.00 | 0.00 | 0.00 |
February | 51.53 | 21.24 | 30.29 | 129.21 | 62.80 | 0.00 | 0.00 | 0.00 |
March | 43.48 | 12.75 | 30.73 | 124.31 | 47.96 | 0.00 | 0.00 | 0.00 |
April | 34.41 | 4.76 | 29.65 | 122.50 | 29.47 | 0.00 | 0.00 | 0.00 |
May | 28.43 | 0.76 | 27.66 | 144.66 | 7.96 | 0.00 | 0.00 | 0.00 |
June | 26.49 | 0.07 | 26.42 | 152.80 | 2.60 | 0.00 | 0.00 | 0.00 |
July | 26.63 | 0.40 | 26.23 | 183.85 | 0.13 | 0.00 | 0.00 | 0.00 |
August | 31.62 | 3.11 | 28.51 | 204.04 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 42.17 | 10.98 | 31.19 | 200.97 | 4.06 | 0.00 | 0.00 | 0.00 |
October | 53.95 | 22.03 | 31.91 | 201.78 | 13.64 | 0.00 | 0.00 | 0.00 |
November | 58.22 | 27.96 | 30.27 | 177.96 | 34.12 | 0.00 | 0.00 | 0.00 |
December | 53.61 | 26.15 | 27.45 | 136.88 | 61.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.00 | 12.91 | 29.09 | 158.91 | 27.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 0.07 | 26.23 | 122.50 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.22 | 27.96 | 31.91 | 204.04 | 73.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.15 | 25.23 | 28.92 | 125.71 | 73.70 | 0.00 | 0.00 | 0.00 |
February | 51.53 | 21.24 | 30.29 | 129.21 | 62.80 | 0.00 | 0.00 | 0.00 |
March | 43.48 | 12.75 | 30.73 | 124.31 | 47.96 | 0.00 | 0.00 | 0.00 |
April | 34.41 | 4.76 | 29.65 | 122.50 | 29.47 | 0.00 | 0.00 | 0.00 |
May | 28.43 | 0.76 | 27.66 | 144.66 | 7.96 | 0.00 | 0.00 | 0.00 |
June | 26.49 | 0.07 | 26.42 | 152.80 | 2.60 | 0.00 | 0.00 | 0.00 |
July | 26.63 | 0.40 | 26.23 | 183.85 | 0.13 | 0.00 | 0.00 | 0.00 |
August | 31.62 | 3.11 | 28.51 | 204.04 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 42.17 | 10.98 | 31.19 | 200.97 | 4.06 | 0.00 | 0.00 | 0.00 |
October | 53.95 | 22.03 | 31.91 | 201.78 | 13.64 | 0.00 | 0.00 | 0.00 |
November | 58.22 | 27.96 | 30.27 | 177.96 | 34.12 | 0.00 | 0.00 | 0.00 |
December | 53.61 | 26.15 | 27.45 | 136.88 | 61.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.00 | 12.91 | 29.09 | 158.91 | 27.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 0.07 | 26.23 | 122.50 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.22 | 27.96 | 31.91 | 204.04 | 73.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 246.30 | 150.73 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 253.38 | 128.89 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 244.90 | 98.25 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 243.06 | 60.22 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 291.18 | 15.83 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 309.52 | 4.76 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 373.42 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 414.44 | 0.10 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 403.94 | 7.41 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 402.50 | 26.27 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 352.51 | 68.05 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 269.55 | 124.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 317.47 | 56.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 243.06 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 414.44 | 150.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 246.30 | 150.73 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 253.38 | 128.89 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 244.90 | 98.25 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 243.06 | 60.22 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 291.18 | 15.83 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 309.52 | 4.76 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 373.42 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 414.44 | 0.10 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 403.94 | 7.41 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 402.50 | 26.27 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 352.51 | 68.05 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 269.55 | 124.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 317.47 | 56.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 243.06 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 414.44 | 150.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.15 | 25.23 | 28.92 | 124.57 | 75.02 | 0.00 | 0.00 | 0.00 |
February | 51.53 | 21.24 | 30.29 | 128.24 | 64.06 | 0.00 | 0.00 | 0.00 |
March | 43.48 | 12.75 | 30.73 | 123.84 | 48.88 | 0.00 | 0.00 | 0.00 |
April | 34.41 | 4.76 | 29.65 | 122.74 | 30.00 | 0.00 | 0.00 | 0.00 |
May | 28.43 | 0.76 | 27.66 | 146.47 | 7.97 | 0.00 | 0.00 | 0.00 |
June | 26.49 | 0.07 | 26.42 | 155.50 | 2.45 | 0.00 | 0.00 | 0.00 |
July | 26.63 | 0.40 | 26.23 | 187.50 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 31.62 | 3.11 | 28.51 | 208.19 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 42.17 | 10.98 | 31.19 | 203.54 | 3.76 | 0.00 | 0.00 | 0.00 |
October | 53.95 | 22.03 | 31.91 | 203.12 | 13.19 | 0.00 | 0.00 | 0.00 |
November | 58.22 | 27.96 | 30.27 | 178.02 | 33.86 | 0.00 | 0.00 | 0.00 |
December | 53.61 | 26.15 | 27.45 | 136.17 | 61.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.00 | 12.91 | 29.09 | 160.03 | 28.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.49 | 0.07 | 26.23 | 122.74 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.22 | 27.96 | 31.91 | 208.19 | 75.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 246.24 | 154.36 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 253.04 | 133.77 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 243.92 | 104.81 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 239.73 | 68.68 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 277.83 | 20.66 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 292.20 | 7.29 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 349.70 | 0.55 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 391.78 | 0.28 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 386.26 | 10.39 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 393.73 | 34.65 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 351.36 | 77.94 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 269.42 | 130.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 308.28 | 61.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 239.73 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 393.73 | 154.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 246.24 | 154.36 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 253.04 | 133.77 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 243.92 | 104.81 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 239.73 | 68.68 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 277.83 | 20.66 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 292.20 | 7.29 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 349.70 | 0.55 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 391.78 | 0.28 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 386.26 | 10.39 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 393.73 | 34.65 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 351.36 | 77.94 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 269.42 | 130.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 308.28 | 61.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 239.73 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 393.73 | 154.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.85 | 25.09 | 28.76 | 123.86 | 76.59 | 0.00 | 0.00 | 0.00 |
February | 51.25 | 21.12 | 30.13 | 127.38 | 66.31 | 0.00 | 0.00 | 0.00 |
March | 43.24 | 12.68 | 30.57 | 122.67 | 52.03 | 0.00 | 0.00 | 0.00 |
April | 34.22 | 4.74 | 29.48 | 120.37 | 34.16 | 0.00 | 0.00 | 0.00 |
May | 28.27 | 0.76 | 27.51 | 138.83 | 10.36 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 0.07 | 26.28 | 145.82 | 3.72 | 0.00 | 0.00 | 0.00 |
July | 26.48 | 0.39 | 26.09 | 174.36 | 0.28 | 0.00 | 0.00 | 0.00 |
August | 31.45 | 3.10 | 28.36 | 195.49 | 0.15 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 10.92 | 31.02 | 193.42 | 5.25 | 0.00 | 0.00 | 0.00 |
October | 53.65 | 21.91 | 31.74 | 197.53 | 17.35 | 0.00 | 0.00 | 0.00 |
November | 57.90 | 27.80 | 30.10 | 176.49 | 38.76 | 0.00 | 0.00 | 0.00 |
December | 53.31 | 26.01 | 27.30 | 135.37 | 64.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 12.84 | 28.93 | 154.47 | 30.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 0.07 | 26.09 | 120.37 | 0.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.90 | 27.80 | 31.74 | 197.53 | 76.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 246.40 | 153.69 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 253.09 | 133.47 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 243.87 | 105.00 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 239.50 | 69.61 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 276.65 | 21.84 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 290.40 | 8.13 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 346.56 | 0.70 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 388.73 | 0.37 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 384.49 | 11.41 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 393.08 | 36.30 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 351.13 | 78.84 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 269.43 | 130.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 307.28 | 62.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 239.50 | 0.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 393.08 | 153.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 246.40 | 153.69 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 253.09 | 133.47 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 243.87 | 105.00 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 239.50 | 69.61 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 276.65 | 21.84 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 290.40 | 8.13 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 346.56 | 0.70 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 388.73 | 0.37 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 384.49 | 11.41 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 393.08 | 36.30 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 351.13 | 78.84 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 269.43 | 130.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 307.28 | 62.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 239.50 | 0.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 393.08 | 153.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.85 | 25.09 | 28.76 | 123.94 | 76.26 | 0.00 | 0.00 | 0.00 |
February | 51.25 | 21.12 | 30.13 | 127.40 | 66.16 | 0.00 | 0.00 | 0.00 |
March | 43.24 | 12.68 | 30.57 | 122.64 | 52.12 | 0.00 | 0.00 | 0.00 |
April | 34.22 | 4.74 | 29.48 | 120.26 | 34.62 | 0.00 | 0.00 | 0.00 |
May | 28.27 | 0.76 | 27.51 | 138.26 | 10.95 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 0.07 | 26.28 | 144.95 | 4.14 | 0.00 | 0.00 | 0.00 |
July | 26.48 | 0.39 | 26.09 | 172.83 | 0.37 | 0.00 | 0.00 | 0.00 |
August | 31.45 | 3.10 | 28.36 | 194.00 | 0.20 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 10.92 | 31.02 | 192.56 | 5.76 | 0.00 | 0.00 | 0.00 |
October | 53.65 | 21.91 | 31.74 | 197.21 | 18.17 | 0.00 | 0.00 | 0.00 |
November | 57.90 | 27.80 | 30.10 | 176.38 | 39.21 | 0.00 | 0.00 | 0.00 |
December | 53.31 | 26.01 | 27.30 | 135.37 | 64.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 12.84 | 28.93 | 153.98 | 30.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 0.07 | 26.09 | 120.26 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.90 | 27.80 | 31.74 | 197.21 | 76.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 246.97 | 152.16 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 253.56 | 132.12 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 244.31 | 103.75 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 239.88 | 68.57 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 277.18 | 21.33 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 291.11 | 7.86 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 347.18 | 0.69 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 389.45 | 0.35 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 385.00 | 11.09 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 393.37 | 35.63 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 351.46 | 77.86 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 269.86 | 129.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 307.78 | 61.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 239.88 | 0.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 393.37 | 152.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 246.97 | 152.16 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 253.56 | 132.12 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 244.31 | 103.75 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 239.88 | 68.57 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 277.18 | 21.33 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 291.11 | 7.86 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 347.18 | 0.69 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 389.45 | 0.35 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 385.00 | 11.09 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 393.37 | 35.63 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 351.46 | 77.86 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 269.86 | 129.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 307.78 | 61.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 239.88 | 0.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 393.37 | 152.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.85 | 25.09 | 28.76 | 124.21 | 75.50 | 0.00 | 0.00 | 0.00 |
February | 51.25 | 21.12 | 30.13 | 127.62 | 65.50 | 0.00 | 0.00 | 0.00 |
March | 43.24 | 12.68 | 30.57 | 122.85 | 51.51 | 0.00 | 0.00 | 0.00 |
April | 34.22 | 4.74 | 29.48 | 120.44 | 34.11 | 0.00 | 0.00 | 0.00 |
May | 28.27 | 0.76 | 27.51 | 138.51 | 10.69 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 0.07 | 26.28 | 145.29 | 4.00 | 0.00 | 0.00 | 0.00 |
July | 26.48 | 0.39 | 26.09 | 173.13 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 31.45 | 3.10 | 28.36 | 194.35 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 10.92 | 31.02 | 192.81 | 5.61 | 0.00 | 0.00 | 0.00 |
October | 53.65 | 21.91 | 31.74 | 197.35 | 17.84 | 0.00 | 0.00 | 0.00 |
November | 57.90 | 27.80 | 30.10 | 176.54 | 38.73 | 0.00 | 0.00 | 0.00 |
December | 53.31 | 26.01 | 27.30 | 135.58 | 64.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 12.84 | 28.93 | 154.22 | 30.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 0.07 | 26.09 | 120.44 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.90 | 27.80 | 31.74 | 197.35 | 75.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 251.51 | 144.32 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 257.47 | 124.78 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.49 | 96.91 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 242.19 | 62.93 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 279.59 | 18.84 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 293.66 | 6.40 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 348.72 | 0.54 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 391.75 | 0.24 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 387.71 | 9.59 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 395.84 | 32.17 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 353.64 | 71.94 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 273.24 | 122.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 310.57 | 57.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 242.19 | 0.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 395.84 | 144.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 251.51 | 144.32 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 257.47 | 124.78 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.49 | 96.91 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 242.19 | 62.93 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 279.59 | 18.84 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 293.66 | 6.40 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 348.72 | 0.54 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 391.75 | 0.24 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 387.71 | 9.59 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 395.84 | 32.17 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 353.64 | 71.94 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 273.24 | 122.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 310.57 | 57.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 242.19 | 0.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 395.84 | 144.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 251.51 | 144.32 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 257.47 | 124.78 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.49 | 96.91 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 242.19 | 62.93 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 279.59 | 18.84 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 293.66 | 6.40 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 348.72 | 0.54 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 391.75 | 0.24 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 387.71 | 9.59 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 395.84 | 32.17 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 353.64 | 71.94 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 273.24 | 122.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 310.57 | 57.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 242.19 | 0.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 395.84 | 144.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 251.51 | 144.32 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 257.47 | 124.78 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.49 | 96.91 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 242.19 | 62.93 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 279.59 | 18.84 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 293.66 | 6.40 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 348.72 | 0.54 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 391.75 | 0.24 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 387.71 | 9.59 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 395.84 | 32.17 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 353.64 | 71.94 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 273.24 | 122.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 310.57 | 57.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 242.19 | 0.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 395.84 | 144.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.85 | 25.09 | 28.76 | 126.29 | 71.62 | 0.00 | 0.00 | 0.00 |
February | 51.25 | 21.12 | 30.13 | 129.39 | 61.87 | 0.00 | 0.00 | 0.00 |
March | 43.24 | 12.68 | 30.57 | 124.29 | 48.11 | 0.00 | 0.00 | 0.00 |
April | 34.22 | 4.74 | 29.48 | 121.47 | 31.30 | 0.00 | 0.00 | 0.00 |
May | 28.27 | 0.76 | 27.51 | 139.68 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 0.07 | 26.28 | 146.55 | 3.27 | 0.00 | 0.00 | 0.00 |
July | 26.48 | 0.39 | 26.09 | 173.92 | 0.28 | 0.00 | 0.00 | 0.00 |
August | 31.45 | 3.10 | 28.36 | 195.51 | 0.13 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 10.92 | 31.02 | 194.09 | 4.85 | 0.00 | 0.00 | 0.00 |
October | 53.65 | 21.91 | 31.74 | 198.47 | 16.10 | 0.00 | 0.00 | 0.00 |
November | 57.90 | 27.80 | 30.10 | 177.44 | 35.76 | 0.00 | 0.00 | 0.00 |
December | 53.31 | 26.01 | 27.30 | 137.09 | 60.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 12.84 | 28.93 | 155.51 | 28.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 0.07 | 26.09 | 121.47 | 0.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.90 | 27.80 | 31.74 | 198.47 | 71.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.85 | 25.09 | 28.76 | 126.29 | 71.62 | 0.00 | 0.00 | 0.00 |
February | 51.25 | 21.12 | 30.13 | 129.39 | 61.87 | 0.00 | 0.00 | 0.00 |
March | 43.24 | 12.68 | 30.57 | 124.29 | 48.11 | 0.00 | 0.00 | 0.00 |
April | 34.22 | 4.74 | 29.48 | 121.47 | 31.30 | 0.00 | 0.00 | 0.00 |
May | 28.27 | 0.76 | 27.51 | 139.68 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 0.07 | 26.28 | 146.55 | 3.27 | 0.00 | 0.00 | 0.00 |
July | 26.48 | 0.39 | 26.09 | 173.92 | 0.28 | 0.00 | 0.00 | 0.00 |
August | 31.45 | 3.10 | 28.36 | 195.51 | 0.13 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 10.92 | 31.02 | 194.09 | 4.85 | 0.00 | 0.00 | 0.00 |
October | 53.65 | 21.91 | 31.74 | 198.47 | 16.10 | 0.00 | 0.00 | 0.00 |
November | 57.90 | 27.80 | 30.10 | 177.44 | 35.76 | 0.00 | 0.00 | 0.00 |
December | 53.31 | 26.01 | 27.30 | 137.09 | 60.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 12.84 | 28.93 | 155.51 | 28.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 0.07 | 26.09 | 121.47 | 0.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.90 | 27.80 | 31.74 | 198.47 | 71.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 250.46 | 143.52 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 256.58 | 123.70 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.41 | 95.33 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 243.19 | 61.06 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 283.43 | 17.56 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 299.00 | 5.49 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 355.37 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 398.51 | 0.15 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 391.71 | 8.54 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 397.53 | 30.19 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 353.66 | 69.93 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 272.57 | 120.89 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 312.81 | 56.07 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 243.19 | 0.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 398.51 | 143.52 | 1.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 250.46 | 143.52 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 256.58 | 123.70 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.41 | 95.33 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 243.19 | 61.06 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 283.43 | 17.56 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 299.00 | 5.49 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 355.37 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 398.51 | 0.15 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 391.71 | 8.54 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 397.53 | 30.19 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 353.66 | 69.93 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 272.57 | 120.89 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 312.81 | 56.07 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 243.19 | 0.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 398.51 | 143.52 | 1.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.85 | 25.09 | 28.76 | 125.84 | 71.21 | 0.00 | 0.00 | 0.00 |
February | 51.25 | 21.12 | 30.13 | 129.02 | 61.32 | 0.00 | 0.00 | 0.00 |
March | 43.24 | 12.68 | 30.57 | 124.29 | 47.33 | 0.00 | 0.00 | 0.00 |
April | 34.22 | 4.74 | 29.48 | 121.97 | 30.39 | 0.00 | 0.00 | 0.00 |
May | 28.27 | 0.76 | 27.51 | 141.52 | 8.81 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 0.07 | 26.28 | 149.09 | 2.81 | 0.00 | 0.00 | 0.00 |
July | 26.48 | 0.39 | 26.09 | 177.11 | 0.22 | 0.00 | 0.00 | 0.00 |
August | 31.45 | 3.10 | 28.36 | 198.76 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 10.92 | 31.02 | 196.02 | 4.33 | 0.00 | 0.00 | 0.00 |
October | 53.65 | 21.91 | 31.74 | 199.31 | 15.13 | 0.00 | 0.00 | 0.00 |
November | 57.90 | 27.80 | 30.10 | 177.51 | 34.79 | 0.00 | 0.00 | 0.00 |
December | 53.31 | 26.01 | 27.30 | 136.83 | 59.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 12.84 | 28.93 | 156.61 | 27.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 0.07 | 26.09 | 121.97 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.90 | 27.80 | 31.74 | 199.31 | 71.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 250.72 | 143.01 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 256.83 | 123.17 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.66 | 94.83 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 243.45 | 60.63 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 283.83 | 17.35 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 299.48 | 5.37 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 355.93 | 0.41 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 399.07 | 0.14 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 392.13 | 8.41 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 397.81 | 29.92 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 353.89 | 69.58 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 272.79 | 120.45 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 313.16 | 55.77 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 243.45 | 0.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 399.07 | 143.01 | 1.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 250.72 | 143.01 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 256.83 | 123.17 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.66 | 94.83 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 243.45 | 60.63 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 283.83 | 17.35 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 299.48 | 5.37 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 355.93 | 0.41 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 399.07 | 0.14 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 392.13 | 8.41 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 397.81 | 29.92 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 353.89 | 69.58 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 272.79 | 120.45 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 313.16 | 55.77 | 1.17 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 243.45 | 0.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 399.07 | 143.01 | 1.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.85 | 25.09 | 28.76 | 125.97 | 70.96 | 0.00 | 0.00 | 0.00 |
February | 51.25 | 21.12 | 30.13 | 129.14 | 61.06 | 0.00 | 0.00 | 0.00 |
March | 43.24 | 12.68 | 30.57 | 124.41 | 47.09 | 0.00 | 0.00 | 0.00 |
April | 34.22 | 4.74 | 29.48 | 122.10 | 30.18 | 0.00 | 0.00 | 0.00 |
May | 28.27 | 0.76 | 27.51 | 141.71 | 8.71 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 0.07 | 26.28 | 149.33 | 2.75 | 0.00 | 0.00 | 0.00 |
July | 26.48 | 0.39 | 26.09 | 177.39 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 31.45 | 3.10 | 28.36 | 199.03 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 10.92 | 31.02 | 196.22 | 4.26 | 0.00 | 0.00 | 0.00 |
October | 53.65 | 21.91 | 31.74 | 199.44 | 15.00 | 0.00 | 0.00 | 0.00 |
November | 57.90 | 27.80 | 30.10 | 177.62 | 34.61 | 0.00 | 0.00 | 0.00 |
December | 53.31 | 26.01 | 27.30 | 136.93 | 59.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 12.84 | 28.93 | 156.78 | 27.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 0.07 | 26.09 | 122.10 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.90 | 27.80 | 31.74 | 199.44 | 70.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 251.00 | 142.37 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 257.07 | 122.52 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.81 | 94.35 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 243.41 | 60.58 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 283.20 | 17.62 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 298.47 | 5.63 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 354.22 | 0.47 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 397.10 | 0.18 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 390.89 | 8.85 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 397.18 | 30.65 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 353.64 | 69.99 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 272.87 | 120.25 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 312.59 | 55.79 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 243.41 | 0.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 397.18 | 142.37 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 251.00 | 142.37 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 257.07 | 122.52 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.81 | 94.35 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 243.41 | 60.58 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 283.20 | 17.62 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 298.47 | 5.63 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 354.22 | 0.47 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 397.10 | 0.18 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 390.89 | 8.85 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 397.18 | 30.65 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 353.64 | 69.99 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 272.87 | 120.25 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 312.59 | 55.79 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 243.41 | 0.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 397.18 | 142.37 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.85 | 25.09 | 28.76 | 126.11 | 70.64 | 0.00 | 0.00 | 0.00 |
February | 51.25 | 21.12 | 30.13 | 129.26 | 60.74 | 0.00 | 0.00 | 0.00 |
March | 43.24 | 12.68 | 30.57 | 124.48 | 46.85 | 0.00 | 0.00 | 0.00 |
April | 34.22 | 4.74 | 29.48 | 122.08 | 30.15 | 0.00 | 0.00 | 0.00 |
May | 28.27 | 0.76 | 27.51 | 141.41 | 8.85 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 0.07 | 26.28 | 148.84 | 2.88 | 0.00 | 0.00 | 0.00 |
July | 26.48 | 0.39 | 26.09 | 176.55 | 0.25 | 0.00 | 0.00 | 0.00 |
August | 31.45 | 3.10 | 28.36 | 198.07 | 0.10 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 10.92 | 31.02 | 195.63 | 4.48 | 0.00 | 0.00 | 0.00 |
October | 53.65 | 21.91 | 31.74 | 199.14 | 15.36 | 0.00 | 0.00 | 0.00 |
November | 57.90 | 27.80 | 30.10 | 177.50 | 34.82 | 0.00 | 0.00 | 0.00 |
December | 53.31 | 26.01 | 27.30 | 136.97 | 59.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 12.84 | 28.93 | 156.51 | 27.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 0.07 | 26.09 | 122.08 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.90 | 27.80 | 31.74 | 199.14 | 70.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 251.08 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 256.98 | 118.54 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.10 | 91.18 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 241.16 | 59.54 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 277.14 | 18.48 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 290.12 | 6.70 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 342.09 | 0.79 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 383.07 | 0.42 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 381.28 | 11.13 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 391.22 | 34.27 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 350.54 | 72.12 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 272.14 | 118.82 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 307.31 | 55.58 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 241.16 | 0.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 391.22 | 138.69 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 51.28 | 58.80 | 251.08 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 104.76 | 43.18 | 61.58 | 256.98 | 118.54 | 0.00 | 0.00 | 0.00 |
March | 88.39 | 25.91 | 62.48 | 247.10 | 91.18 | 0.00 | 0.00 | 0.00 |
April | 69.95 | 9.68 | 60.27 | 241.16 | 59.54 | 0.00 | 0.00 | 0.00 |
May | 57.79 | 1.55 | 56.23 | 277.14 | 18.48 | 0.00 | 0.00 | 0.00 |
June | 53.86 | 0.14 | 53.72 | 290.12 | 6.70 | 0.00 | 0.00 | 0.00 |
July | 54.13 | 0.81 | 53.32 | 342.09 | 0.79 | 0.00 | 0.00 | 0.00 |
August | 64.29 | 6.33 | 57.96 | 383.07 | 0.42 | 0.00 | 0.00 | 0.00 |
September | 85.73 | 22.33 | 63.40 | 381.28 | 11.13 | 0.00 | 0.00 | 0.00 |
October | 109.67 | 44.79 | 64.87 | 391.22 | 34.27 | 0.00 | 0.00 | 0.00 |
November | 118.36 | 56.83 | 61.53 | 350.54 | 72.12 | 0.00 | 0.00 | 0.00 |
December | 108.97 | 53.17 | 55.80 | 272.14 | 118.82 | 1.33 | 0.00 | 0.00 |
Annual Sum or Average | 85.38 | 26.24 | 59.14 | 307.31 | 55.58 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 53.86 | 0.14 | 53.32 | 241.16 | 0.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.36 | 56.83 | 64.87 | 391.22 | 138.69 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.85 | 25.09 | 28.76 | 126.16 | 68.81 | 0.00 | 0.00 | 0.00 |
February | 51.25 | 21.12 | 30.13 | 129.23 | 58.76 | 0.00 | 0.00 | 0.00 |
March | 43.24 | 12.68 | 30.57 | 124.14 | 45.28 | 0.00 | 0.00 | 0.00 |
April | 34.22 | 4.74 | 29.48 | 121.01 | 29.64 | 0.00 | 0.00 | 0.00 |
May | 28.27 | 0.76 | 27.51 | 138.50 | 9.27 | 0.00 | 0.00 | 0.00 |
June | 26.35 | 0.07 | 26.28 | 144.82 | 3.43 | 0.00 | 0.00 | 0.00 |
July | 26.48 | 0.39 | 26.09 | 170.66 | 0.41 | 0.00 | 0.00 | 0.00 |
August | 31.45 | 3.10 | 28.36 | 191.27 | 0.22 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 10.92 | 31.02 | 191.02 | 5.64 | 0.00 | 0.00 | 0.00 |
October | 53.65 | 21.91 | 31.74 | 196.30 | 17.16 | 0.00 | 0.00 | 0.00 |
November | 57.90 | 27.80 | 30.10 | 176.03 | 35.86 | 0.00 | 0.00 | 0.00 |
December | 53.31 | 26.01 | 27.30 | 136.63 | 58.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.77 | 12.84 | 28.93 | 153.97 | 27.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.35 | 0.07 | 26.09 | 121.01 | 0.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.90 | 27.80 | 31.74 | 196.30 | 68.81 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.666430E+09 | 0.396521E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.618211E+09 | 0.305634E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.658907E+09 | 0.258223E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.628949E+09 | 0.153401E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.769830E+09 | 42376843.48 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.787686E+09 | 13116969.80 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.979884E+09 | 644526.51 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.108701E+10 | 368852.92 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.103323E+10 | 20721713.39 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.107085E+10 | 72835222.60 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.913744E+09 | 0.177822E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.726273E+09 | 0.329091E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.994101E+10 | 0.177076E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.618211E+09 | 368852.92 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.108701E+10 | 0.396521E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.666430E+09 | 0.396521E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.618211E+09 | 0.305634E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.658907E+09 | 0.258223E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.628949E+09 | 0.153401E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.769830E+09 | 42376843.48 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.787686E+09 | 13116969.80 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.979884E+09 | 644526.51 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.108701E+10 | 368852.92 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.103323E+10 | 20721713.39 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.107085E+10 | 72835222.60 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.913744E+09 | 0.177822E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.726273E+09 | 0.329091E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.994101E+10 | 0.177076E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.618211E+09 | 368852.92 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.108701E+10 | 0.396521E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.666430E+09 | 0.396521E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.618211E+09 | 0.305634E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.658907E+09 | 0.258223E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.628949E+09 | 0.153401E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.769830E+09 | 42376843.48 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.787686E+09 | 13116969.80 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.979884E+09 | 644526.51 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.108701E+10 | 368852.92 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.103323E+10 | 20721713.39 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.107085E+10 | 72835222.60 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.913744E+09 | 0.177822E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.726273E+09 | 0.329091E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.994101E+10 | 0.177076E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.618211E+09 | 368852.92 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.108701E+10 | 0.396521E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.666430E+09 | 0.396521E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.618211E+09 | 0.305634E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.658907E+09 | 0.258223E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.628949E+09 | 0.153401E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.769830E+09 | 42376843.48 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.787686E+09 | 13116969.80 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.979884E+09 | 644526.51 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.108701E+10 | 368852.92 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.103323E+10 | 20721713.39 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.107085E+10 | 72835222.60 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.913744E+09 | 0.177822E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.726273E+09 | 0.329091E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.994101E+10 | 0.177076E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.618211E+09 | 368852.92 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.108701E+10 | 0.396521E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145032E+09 | 67566337.81 | 77465288.90 | 0.336707E+09 | 0.197404E+09 |
February | 0.124667E+09 | 51386345.06 | 73280283.70 | 0.312590E+09 | 0.151935E+09 |
March | 0.116454E+09 | 34136231.47 | 82317446.45 | 0.332956E+09 | 0.128468E+09 |
April | 89189179.89 | 12345000.67 | 76844179.22 | 0.317528E+09 | 76389317.96 |
May | 76133925.41 | 2045799.49 | 74088125.92 | 0.387450E+09 | 21322819.78 |
June | 68668549.76 | 180085.03 | 68488464.74 | 0.396070E+09 | 6745201.79 |
July | 71317500.95 | 1062383.45 | 70255117.49 | 0.492434E+09 | 348170.63 |
August | 84703733.06 | 8338431.41 | 76365301.66 | 0.546494E+09 | 199291.96 |
September | 0.109308E+09 | 28471010.81 | 80836816.59 | 0.520915E+09 | 10519828.44 |
October | 0.144488E+09 | 59017208.31 | 85470686.12 | 0.540459E+09 | 36525417.03 |
November | 0.150910E+09 | 72461566.14 | 78448249.60 | 0.461260E+09 | 88432125.18 |
December | 0.143576E+09 | 70053110.44 | 73522894.55 | 0.366611E+09 | 0.163669E+09 |
Annual Sum or Average | 0.132445E+10 | 0.407064E+09 | 0.917383E+09 | 0.501147E+10 | 0.881958E+09 |
Minimum of Months | 68668549.76 | 180085.03 | 68488464.74 | 0.312590E+09 | 199291.96 |
Maximum of Months | 0.150910E+09 | 72461566.14 | 85470686.12 | 0.546494E+09 | 0.197404E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145032E+09 | 67566337.81 | 77465288.90 | 0.336707E+09 | 0.197404E+09 |
February | 0.124667E+09 | 51386345.06 | 73280283.70 | 0.312590E+09 | 0.151935E+09 |
March | 0.116454E+09 | 34136231.47 | 82317446.45 | 0.332956E+09 | 0.128468E+09 |
April | 89189179.89 | 12345000.67 | 76844179.22 | 0.317528E+09 | 76389317.96 |
May | 76133925.41 | 2045799.49 | 74088125.92 | 0.387450E+09 | 21322819.78 |
June | 68668549.76 | 180085.03 | 68488464.74 | 0.396070E+09 | 6745201.79 |
July | 71317500.95 | 1062383.45 | 70255117.49 | 0.492434E+09 | 348170.63 |
August | 84703733.06 | 8338431.41 | 76365301.66 | 0.546494E+09 | 199291.96 |
September | 0.109308E+09 | 28471010.81 | 80836816.59 | 0.520915E+09 | 10519828.44 |
October | 0.144488E+09 | 59017208.31 | 85470686.12 | 0.540459E+09 | 36525417.03 |
November | 0.150910E+09 | 72461566.14 | 78448249.60 | 0.461260E+09 | 88432125.18 |
December | 0.143576E+09 | 70053110.44 | 73522894.55 | 0.366611E+09 | 0.163669E+09 |
Annual Sum or Average | 0.132445E+10 | 0.407064E+09 | 0.917383E+09 | 0.501147E+10 | 0.881958E+09 |
Minimum of Months | 68668549.76 | 180085.03 | 68488464.74 | 0.312590E+09 | 199291.96 |
Maximum of Months | 0.150910E+09 | 72461566.14 | 85470686.12 | 0.546494E+09 | 0.197404E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.659701E+09 | 0.403723E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.612968E+09 | 0.311807E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.655947E+09 | 0.263166E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.630011E+09 | 0.156081E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.779902E+09 | 42394935.33 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.802286E+09 | 12331199.58 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.100018E+10 | 492102.53 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.111004E+10 | 258728.64 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.104701E+10 | 19196916.07 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.107806E+10 | 70363588.39 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.913708E+09 | 0.176378E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.721962E+09 | 0.332802E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.100118E+11 | 0.178899E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.612968E+09 | 258728.64 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.111004E+10 | 0.403723E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.659701E+09 | 0.403723E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.612968E+09 | 0.311807E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.655947E+09 | 0.263166E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.630011E+09 | 0.156081E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.779902E+09 | 42394935.33 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.802286E+09 | 12331199.58 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.100018E+10 | 492102.53 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.111004E+10 | 258728.64 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.104701E+10 | 19196916.07 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.107806E+10 | 70363588.39 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.913708E+09 | 0.176378E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.721962E+09 | 0.332802E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.100118E+11 | 0.178899E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.612968E+09 | 258728.64 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.111004E+10 | 0.403723E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145032E+09 | 67566337.81 | 77465288.90 | 0.333649E+09 | 0.200930E+09 |
February | 0.124667E+09 | 51386345.06 | 73280283.70 | 0.310234E+09 | 0.154968E+09 |
March | 0.116454E+09 | 34136231.47 | 82317446.45 | 0.331680E+09 | 0.130920E+09 |
April | 89189179.89 | 12345000.67 | 76844179.22 | 0.318134E+09 | 77748218.91 |
May | 76133925.41 | 2045799.49 | 74088125.92 | 0.392303E+09 | 21346779.13 |
June | 68668549.76 | 180085.03 | 68488464.74 | 0.403068E+09 | 6356083.61 |
July | 71317500.95 | 1062383.45 | 70255117.49 | 0.502207E+09 | 271162.68 |
August | 84703733.06 | 8338431.41 | 76365301.66 | 0.557614E+09 | 139712.62 |
September | 0.109308E+09 | 28471010.81 | 80836816.59 | 0.527588E+09 | 9752455.29 |
October | 0.144488E+09 | 59017208.31 | 85470686.12 | 0.544046E+09 | 35328863.66 |
November | 0.150910E+09 | 72461566.14 | 78448249.60 | 0.461421E+09 | 87764098.22 |
December | 0.143576E+09 | 70053110.44 | 73522894.55 | 0.364707E+09 | 0.165491E+09 |
Annual Sum or Average | 0.132445E+10 | 0.407064E+09 | 0.917383E+09 | 0.504665E+10 | 0.891016E+09 |
Minimum of Months | 68668549.76 | 180085.03 | 68488464.74 | 0.310234E+09 | 139712.62 |
Maximum of Months | 0.150910E+09 | 72461566.14 | 85470686.12 | 0.557614E+09 | 0.200930E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.659541E+09 | 0.413450E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.612164E+09 | 0.323611E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.653315E+09 | 0.280717E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.621390E+09 | 0.178016E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.744135E+09 | 55328219.93 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.757372E+09 | 18893896.20 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.936638E+09 | 1460356.89 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.104935E+10 | 751000.65 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.100120E+10 | 26932336.29 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.105458E+10 | 92804956.50 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.910712E+09 | 0.202013E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.721604E+09 | 0.349295E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.972200E+10 | 0.194327E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.612164E+09 | 751000.65 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.105458E+10 | 0.413450E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.659541E+09 | 0.413450E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.612164E+09 | 0.323611E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.653315E+09 | 0.280717E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.621390E+09 | 0.178016E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.744135E+09 | 55328219.93 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.757372E+09 | 18893896.20 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.936638E+09 | 1460356.89 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.104935E+10 | 751000.65 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.100120E+10 | 26932336.29 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.105458E+10 | 92804956.50 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.910712E+09 | 0.202013E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.721604E+09 | 0.349295E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.972200E+10 | 0.194327E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.612164E+09 | 751000.65 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.105458E+10 | 0.413450E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144239E+09 | 67197122.85 | 77041981.31 | 0.331748E+09 | 0.205144E+09 |
February | 0.123985E+09 | 51105545.36 | 72879845.00 | 0.308148E+09 | 0.160418E+09 |
March | 0.115817E+09 | 33949694.69 | 81867624.34 | 0.328551E+09 | 0.139353E+09 |
April | 88701807.32 | 12277541.65 | 76424265.67 | 0.311994E+09 | 88551776.88 |
May | 75717893.03 | 2034620.26 | 73683272.77 | 0.371836E+09 | 27741259.98 |
June | 68293311.79 | 179100.96 | 68114210.83 | 0.377961E+09 | 9634419.96 |
July | 70927787.83 | 1056578.08 | 69871209.75 | 0.467018E+09 | 761718.72 |
August | 84240871.13 | 8292866.21 | 75948004.93 | 0.523604E+09 | 398777.73 |
September | 0.108711E+09 | 28315431.51 | 80395085.36 | 0.501335E+09 | 13612314.98 |
October | 0.143698E+09 | 58694709.90 | 85003633.19 | 0.529052E+09 | 46475325.44 |
November | 0.150085E+09 | 72065601.30 | 78019570.64 | 0.457450E+09 | 0.100478E+09 |
December | 0.142791E+09 | 69670306.56 | 73121130.10 | 0.362572E+09 | 0.173289E+09 |
Annual Sum or Average | 0.131721E+10 | 0.404839E+09 | 0.912370E+09 | 0.487127E+10 | 0.965858E+09 |
Minimum of Months | 68293311.79 | 179100.96 | 68114210.83 | 0.308148E+09 | 398777.73 |
Maximum of Months | 0.150085E+09 | 72065601.30 | 85003633.19 | 0.529052E+09 | 0.205144E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.659961E+09 | 0.411636E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.612285E+09 | 0.322899E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.653168E+09 | 0.281233E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.620784E+09 | 0.180426E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.740992E+09 | 58491776.92 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.752719E+09 | 21085614.01 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.928228E+09 | 1880783.77 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.104118E+10 | 992838.28 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.996604E+09 | 29572360.16 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.105283E+10 | 97227486.42 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.910122E+09 | 0.204355E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.721628E+09 | 0.349096E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.969050E+10 | 0.195890E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.612285E+09 | 992838.28 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.105283E+10 | 0.411636E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.659961E+09 | 0.411636E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.612285E+09 | 0.322899E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.653168E+09 | 0.281233E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.620784E+09 | 0.180426E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.740992E+09 | 58491776.92 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.752719E+09 | 21085614.01 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.928228E+09 | 1880783.77 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.104118E+10 | 992838.28 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.996604E+09 | 29572360.16 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.105283E+10 | 97227486.42 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.910122E+09 | 0.204355E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.721628E+09 | 0.349096E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.969050E+10 | 0.195890E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.612285E+09 | 992838.28 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.105283E+10 | 0.411636E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144239E+09 | 67197122.85 | 77041981.31 | 0.331949E+09 | 0.204246E+09 |
February | 0.123985E+09 | 51105545.36 | 72879845.00 | 0.308206E+09 | 0.160066E+09 |
March | 0.115817E+09 | 33949694.69 | 81867624.34 | 0.328481E+09 | 0.139608E+09 |
April | 88701807.32 | 12277541.65 | 76424265.67 | 0.311705E+09 | 89741889.37 |
May | 75717893.03 | 2034620.26 | 73683272.77 | 0.370321E+09 | 29318215.88 |
June | 68293311.79 | 179100.96 | 68114210.83 | 0.375715E+09 | 10742201.27 |
July | 70927787.83 | 1056578.08 | 69871209.75 | 0.462896E+09 | 981439.91 |
August | 84240871.13 | 8292866.21 | 75948004.93 | 0.519600E+09 | 525360.31 |
September | 0.108711E+09 | 28315431.51 | 80395085.36 | 0.499118E+09 | 14941806.14 |
October | 0.143698E+09 | 58694709.90 | 85003633.19 | 0.528217E+09 | 48664274.33 |
November | 0.150085E+09 | 72065601.30 | 78019570.64 | 0.457170E+09 | 0.101635E+09 |
December | 0.142791E+09 | 69670306.56 | 73121130.10 | 0.362584E+09 | 0.173190E+09 |
Annual Sum or Average | 0.131721E+10 | 0.404839E+09 | 0.912370E+09 | 0.485596E+10 | 0.973662E+09 |
Minimum of Months | 68293311.79 | 179100.96 | 68114210.83 | 0.308206E+09 | 525360.31 |
Maximum of Months | 0.150085E+09 | 72065601.30 | 85003633.19 | 0.528217E+09 | 0.204246E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.661495E+09 | 0.407544E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.613412E+09 | 0.319637E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.654348E+09 | 0.277877E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.621778E+09 | 0.177725E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.742386E+09 | 57138542.77 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.754551E+09 | 20367856.43 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.929892E+09 | 1839093.36 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.104311E+10 | 944033.14 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.997914E+09 | 28756550.27 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.105361E+10 | 95432660.26 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.910989E+09 | 0.201823E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.722796E+09 | 0.345731E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.970628E+10 | 0.193482E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.613412E+09 | 944033.14 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.105361E+10 | 0.407544E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.661495E+09 | 0.407544E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.613412E+09 | 0.319637E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.654348E+09 | 0.277877E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.621778E+09 | 0.177725E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.742386E+09 | 57138542.77 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.754551E+09 | 20367856.43 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.929892E+09 | 1839093.36 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.104311E+10 | 944033.14 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.997914E+09 | 28756550.27 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.105361E+10 | 95432660.26 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.910989E+09 | 0.201823E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.722796E+09 | 0.345731E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.970628E+10 | 0.193482E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.613412E+09 | 944033.14 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.105361E+10 | 0.407544E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144239E+09 | 67197122.85 | 77041981.31 | 0.332682E+09 | 0.202224E+09 |
February | 0.123985E+09 | 51105545.36 | 72879845.00 | 0.308743E+09 | 0.158457E+09 |
March | 0.115817E+09 | 33949694.69 | 81867624.34 | 0.329043E+09 | 0.137953E+09 |
April | 88701807.32 | 12277541.65 | 76424265.67 | 0.312177E+09 | 88409793.00 |
May | 75717893.03 | 2034620.26 | 73683272.77 | 0.370990E+09 | 28641750.30 |
June | 68293311.79 | 179100.96 | 68114210.83 | 0.376600E+09 | 10378791.74 |
July | 70927787.83 | 1056578.08 | 69871209.75 | 0.463716E+09 | 959855.26 |
August | 84240871.13 | 8292866.21 | 75948004.93 | 0.520550E+09 | 500409.57 |
September | 0.108711E+09 | 28315431.51 | 80395085.36 | 0.499752E+09 | 14533211.06 |
October | 0.143698E+09 | 58694709.90 | 85003633.19 | 0.528587E+09 | 47773174.05 |
November | 0.150085E+09 | 72065601.30 | 78019570.64 | 0.457582E+09 | 0.100386E+09 |
December | 0.142791E+09 | 69670306.56 | 73121130.10 | 0.363141E+09 | 0.171528E+09 |
Annual Sum or Average | 0.131721E+10 | 0.404839E+09 | 0.912370E+09 | 0.486356E+10 | 0.961745E+09 |
Minimum of Months | 68293311.79 | 179100.96 | 68114210.83 | 0.308743E+09 | 500409.57 |
Maximum of Months | 0.150085E+09 | 72065601.30 | 85003633.19 | 0.528587E+09 | 0.202224E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.673654E+09 | 0.386541E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.622874E+09 | 0.301878E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.662879E+09 | 0.259573E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.627751E+09 | 0.163109E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.748863E+09 | 50471437.15 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.761154E+09 | 16584564.90 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.934024E+09 | 1455372.89 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.104927E+10 | 640052.76 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.100494E+10 | 24866648.02 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.106023E+10 | 86165295.40 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.916640E+09 | 0.186460E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.731837E+09 | 0.327114E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.979411E+10 | 0.180486E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.622874E+09 | 640052.76 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.106023E+10 | 0.386541E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.673654E+09 | 0.386541E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.622874E+09 | 0.301878E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.662879E+09 | 0.259573E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.627751E+09 | 0.163109E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.748863E+09 | 50471437.15 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.761154E+09 | 16584564.90 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.934024E+09 | 1455372.89 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.104927E+10 | 640052.76 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.100494E+10 | 24866648.02 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.106023E+10 | 86165295.40 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.916640E+09 | 0.186460E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.731837E+09 | 0.327114E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.979411E+10 | 0.180486E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.622874E+09 | 640052.76 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.106023E+10 | 0.386541E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.673654E+09 | 0.386541E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.622874E+09 | 0.301878E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.662879E+09 | 0.259573E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.627751E+09 | 0.163109E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.748863E+09 | 50471437.15 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.761154E+09 | 16584564.90 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.934024E+09 | 1455372.89 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.104927E+10 | 640052.76 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.100494E+10 | 24866648.02 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.106023E+10 | 86165295.40 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.916640E+09 | 0.186460E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.731837E+09 | 0.327114E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.979411E+10 | 0.180486E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.622874E+09 | 640052.76 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.106023E+10 | 0.386541E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.673654E+09 | 0.386541E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.622874E+09 | 0.301878E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.662879E+09 | 0.259573E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.627751E+09 | 0.163109E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.748863E+09 | 50471437.15 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.761154E+09 | 16584564.90 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.934024E+09 | 1455372.89 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.104927E+10 | 640052.76 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.100494E+10 | 24866648.02 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.106023E+10 | 86165295.40 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.916640E+09 | 0.186460E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.731837E+09 | 0.327114E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.979411E+10 | 0.180486E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.622874E+09 | 640052.76 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.106023E+10 | 0.386541E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144239E+09 | 67197122.85 | 77041981.31 | 0.338252E+09 | 0.191821E+09 |
February | 0.123985E+09 | 51105545.36 | 72879845.00 | 0.313027E+09 | 0.149668E+09 |
March | 0.115817E+09 | 33949694.69 | 81867624.34 | 0.332888E+09 | 0.128861E+09 |
April | 88701807.32 | 12277541.65 | 76424265.67 | 0.314855E+09 | 81132829.30 |
May | 75717893.03 | 2034620.26 | 73683272.77 | 0.374126E+09 | 25291144.93 |
June | 68293311.79 | 179100.96 | 68114210.83 | 0.379848E+09 | 8463020.76 |
July | 70927787.83 | 1056578.08 | 69871209.75 | 0.465826E+09 | 759908.92 |
August | 84240871.13 | 8292866.21 | 75948004.93 | 0.523648E+09 | 342209.97 |
September | 0.108711E+09 | 28315431.51 | 80395085.36 | 0.503077E+09 | 12573677.67 |
October | 0.143698E+09 | 58694709.90 | 85003633.19 | 0.531574E+09 | 43131449.42 |
November | 0.150085E+09 | 72065601.30 | 78019570.64 | 0.459935E+09 | 92700689.97 |
December | 0.142791E+09 | 69670306.56 | 73121130.10 | 0.367187E+09 | 0.162288E+09 |
Annual Sum or Average | 0.131721E+10 | 0.404839E+09 | 0.912370E+09 | 0.490424E+10 | 0.897033E+09 |
Minimum of Months | 68293311.79 | 179100.96 | 68114210.83 | 0.313027E+09 | 342209.97 |
Maximum of Months | 0.150085E+09 | 72065601.30 | 85003633.19 | 0.531574E+09 | 0.191821E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144239E+09 | 67197122.85 | 77041981.31 | 0.338252E+09 | 0.191821E+09 |
February | 0.123985E+09 | 51105545.36 | 72879845.00 | 0.313027E+09 | 0.149668E+09 |
March | 0.115817E+09 | 33949694.69 | 81867624.34 | 0.332888E+09 | 0.128861E+09 |
April | 88701807.32 | 12277541.65 | 76424265.67 | 0.314855E+09 | 81132829.30 |
May | 75717893.03 | 2034620.26 | 73683272.77 | 0.374126E+09 | 25291144.93 |
June | 68293311.79 | 179100.96 | 68114210.83 | 0.379848E+09 | 8463020.76 |
July | 70927787.83 | 1056578.08 | 69871209.75 | 0.465826E+09 | 759908.92 |
August | 84240871.13 | 8292866.21 | 75948004.93 | 0.523648E+09 | 342209.97 |
September | 0.108711E+09 | 28315431.51 | 80395085.36 | 0.503077E+09 | 12573677.67 |
October | 0.143698E+09 | 58694709.90 | 85003633.19 | 0.531574E+09 | 43131449.42 |
November | 0.150085E+09 | 72065601.30 | 78019570.64 | 0.459935E+09 | 92700689.97 |
December | 0.142791E+09 | 69670306.56 | 73121130.10 | 0.367187E+09 | 0.162288E+09 |
Annual Sum or Average | 0.131721E+10 | 0.404839E+09 | 0.912370E+09 | 0.490424E+10 | 0.897033E+09 |
Minimum of Months | 68293311.79 | 179100.96 | 68114210.83 | 0.313027E+09 | 342209.97 |
Maximum of Months | 0.150085E+09 | 72065601.30 | 85003633.19 | 0.531574E+09 | 0.191821E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.670821E+09 | 0.384406E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.620715E+09 | 0.299252E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.662669E+09 | 0.255339E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.630358E+09 | 0.158265E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.759136E+09 | 47033347.63 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.775008E+09 | 14222778.11 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.951826E+09 | 1122723.77 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.106737E+10 | 401296.79 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.101532E+10 | 22131294.95 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.106475E+10 | 80856372.79 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.916695E+09 | 0.181265E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.730040E+09 | 0.323799E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.986470E+10 | 0.176809E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.620715E+09 | 401296.79 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.106737E+10 | 0.384406E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.670821E+09 | 0.384406E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.620715E+09 | 0.299252E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.662669E+09 | 0.255339E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.630358E+09 | 0.158265E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.759136E+09 | 47033347.63 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.775008E+09 | 14222778.11 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.951826E+09 | 1122723.77 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.106737E+10 | 401296.79 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.101532E+10 | 22131294.95 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.106475E+10 | 80856372.79 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.916695E+09 | 0.181265E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.730040E+09 | 0.323799E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.986470E+10 | 0.176809E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.620715E+09 | 401296.79 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.106737E+10 | 0.384406E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144239E+09 | 67197122.85 | 77041981.31 | 0.337057E+09 | 0.190731E+09 |
February | 0.123985E+09 | 51105545.36 | 72879845.00 | 0.312137E+09 | 0.148351E+09 |
March | 0.115817E+09 | 33949694.69 | 81867624.34 | 0.332900E+09 | 0.126777E+09 |
April | 88701807.32 | 12277541.65 | 76424265.67 | 0.316158E+09 | 78766100.49 |
May | 75717893.03 | 2034620.26 | 73683272.77 | 0.379048E+09 | 23606267.79 |
June | 68293311.79 | 179100.96 | 68114210.83 | 0.386451E+09 | 7289549.58 |
July | 70927787.83 | 1056578.08 | 69871209.75 | 0.474374E+09 | 591762.49 |
August | 84240871.13 | 8292866.21 | 75948004.93 | 0.532361E+09 | 222628.37 |
September | 0.108711E+09 | 28315431.51 | 80395085.36 | 0.508092E+09 | 11212877.12 |
October | 0.143698E+09 | 58694709.90 | 85003633.19 | 0.533832E+09 | 40533595.78 |
November | 0.150085E+09 | 72065601.30 | 78019570.64 | 0.460108E+09 | 90170285.86 |
December | 0.142791E+09 | 69670306.56 | 73121130.10 | 0.366477E+09 | 0.160638E+09 |
Annual Sum or Average | 0.131721E+10 | 0.404839E+09 | 0.912370E+09 | 0.493899E+10 | 0.878890E+09 |
Minimum of Months | 68293311.79 | 179100.96 | 68114210.83 | 0.312137E+09 | 222628.37 |
Maximum of Months | 0.150085E+09 | 72065601.30 | 85003633.19 | 0.533832E+09 | 0.190731E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.671521E+09 | 0.383038E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.621321E+09 | 0.297976E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.663337E+09 | 0.254003E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.631026E+09 | 0.157165E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.760198E+09 | 46464372.48 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.776262E+09 | 13906080.98 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.953336E+09 | 1088494.17 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.106887E+10 | 378386.90 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.101641E+10 | 21803011.56 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.106549E+10 | 80132603.62 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.917288E+09 | 0.180339E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.730628E+09 | 0.322614E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.987569E+10 | 0.175891E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.621321E+09 | 378386.90 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.106887E+10 | 0.383038E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.671521E+09 | 0.383038E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.621321E+09 | 0.297976E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.663337E+09 | 0.254003E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.631026E+09 | 0.157165E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.760198E+09 | 46464372.48 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.776262E+09 | 13906080.98 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.953336E+09 | 1088494.17 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.106887E+10 | 378386.90 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.101641E+10 | 21803011.56 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.106549E+10 | 80132603.62 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.917288E+09 | 0.180339E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.730628E+09 | 0.322614E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.987569E+10 | 0.175891E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.621321E+09 | 378386.90 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.106887E+10 | 0.383038E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144239E+09 | 67197122.85 | 77041981.31 | 0.337394E+09 | 0.190056E+09 |
February | 0.123985E+09 | 51105545.36 | 72879845.00 | 0.312427E+09 | 0.147722E+09 |
March | 0.115817E+09 | 33949694.69 | 81867624.34 | 0.333218E+09 | 0.126118E+09 |
April | 88701807.32 | 12277541.65 | 76424265.67 | 0.316476E+09 | 78223603.62 |
May | 75717893.03 | 2034620.26 | 73683272.77 | 0.379558E+09 | 23323538.81 |
June | 68293311.79 | 179100.96 | 68114210.83 | 0.387056E+09 | 7130305.90 |
July | 70927787.83 | 1056578.08 | 69871209.75 | 0.475110E+09 | 573779.97 |
August | 84240871.13 | 8292866.21 | 75948004.93 | 0.533093E+09 | 209621.67 |
September | 0.108711E+09 | 28315431.51 | 80395085.36 | 0.508615E+09 | 11046568.83 |
October | 0.143698E+09 | 58694709.90 | 85003633.19 | 0.534185E+09 | 40174426.55 |
November | 0.150085E+09 | 72065601.30 | 78019570.64 | 0.460393E+09 | 89715382.90 |
December | 0.142791E+09 | 69670306.56 | 73121130.10 | 0.366759E+09 | 0.160053E+09 |
Annual Sum or Average | 0.131721E+10 | 0.404839E+09 | 0.912370E+09 | 0.494428E+10 | 0.874347E+09 |
Minimum of Months | 68293311.79 | 179100.96 | 68114210.83 | 0.312427E+09 | 209621.67 |
Maximum of Months | 0.150085E+09 | 72065601.30 | 85003633.19 | 0.534185E+09 | 0.190056E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.672283E+09 | 0.381321E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.621914E+09 | 0.296403E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.663734E+09 | 0.252710E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.630907E+09 | 0.157017E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.758531E+09 | 47202612.24 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.773637E+09 | 14585922.44 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.948751E+09 | 1250053.80 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.106358E+10 | 481861.10 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.101318E+10 | 22936904.23 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.106382E+10 | 82101740.31 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.916640E+09 | 0.181413E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.730852E+09 | 0.322072E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.985783E+10 | 0.175949E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.621914E+09 | 481861.10 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.106382E+10 | 0.381321E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.672283E+09 | 0.381321E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.621914E+09 | 0.296403E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.663734E+09 | 0.252710E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.630907E+09 | 0.157017E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.758531E+09 | 47202612.24 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.773637E+09 | 14585922.44 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.948751E+09 | 1250053.80 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.106358E+10 | 481861.10 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.101318E+10 | 22936904.23 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.106382E+10 | 82101740.31 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.916640E+09 | 0.181413E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.730852E+09 | 0.322072E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.985783E+10 | 0.175949E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.621914E+09 | 481861.10 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.106382E+10 | 0.381321E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144239E+09 | 67197122.85 | 77041981.31 | 0.337763E+09 | 0.189208E+09 |
February | 0.123985E+09 | 51105545.36 | 72879845.00 | 0.312712E+09 | 0.146945E+09 |
March | 0.115817E+09 | 33949694.69 | 81867624.34 | 0.333409E+09 | 0.125479E+09 |
April | 88701807.32 | 12277541.65 | 76424265.67 | 0.316420E+09 | 78151387.00 |
May | 75717893.03 | 2034620.26 | 73683272.77 | 0.378755E+09 | 23691568.90 |
June | 68293311.79 | 179100.96 | 68114210.83 | 0.385792E+09 | 7476321.52 |
July | 70927787.83 | 1056578.08 | 69871209.75 | 0.472874E+09 | 658424.03 |
August | 84240871.13 | 8292866.21 | 75948004.93 | 0.530516E+09 | 264332.23 |
September | 0.108711E+09 | 28315431.51 | 80395085.36 | 0.507063E+09 | 11619680.63 |
October | 0.143698E+09 | 58694709.90 | 85003633.19 | 0.533386E+09 | 41150078.10 |
November | 0.150085E+09 | 72065601.30 | 78019570.64 | 0.460083E+09 | 90244586.39 |
December | 0.142791E+09 | 69670306.56 | 73121130.10 | 0.366868E+09 | 0.159785E+09 |
Annual Sum or Average | 0.131721E+10 | 0.404839E+09 | 0.912370E+09 | 0.493564E+10 | 0.874674E+09 |
Minimum of Months | 68293311.79 | 179100.96 | 68114210.83 | 0.312712E+09 | 264332.23 |
Maximum of Months | 0.150085E+09 | 72065601.30 | 85003633.19 | 0.533386E+09 | 0.189208E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.672497E+09 | 0.371459E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.621698E+09 | 0.286771E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.661820E+09 | 0.244227E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.625091E+09 | 0.154338E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.742286E+09 | 49489094.56 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.751986E+09 | 17363408.94 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.916262E+09 | 2113055.78 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.102602E+10 | 1119210.32 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.988270E+09 | 28860299.72 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.104783E+10 | 91794622.33 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.908588E+09 | 0.186922E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.728908E+09 | 0.318251E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.969126E+10 | 0.175271E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.621698E+09 | 1119210.32 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.104783E+10 | 0.371459E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294834E+09 | 0.137355E+09 | 0.157479E+09 | 0.672497E+09 | 0.371459E+09 |
February | 0.253434E+09 | 0.104463E+09 | 0.148971E+09 | 0.621698E+09 | 0.286771E+09 |
March | 0.236738E+09 | 69395286.04 | 0.167343E+09 | 0.661820E+09 | 0.244227E+09 |
April | 0.181312E+09 | 25096058.23 | 0.156216E+09 | 0.625091E+09 | 0.154338E+09 |
May | 0.154772E+09 | 4158890.27 | 0.150613E+09 | 0.742286E+09 | 49489094.56 |
June | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.751986E+09 | 17363408.94 |
July | 0.144981E+09 | 2159711.27 | 0.142821E+09 | 0.916262E+09 | 2113055.78 |
August | 0.172194E+09 | 16951133.96 | 0.155242E+09 | 0.102602E+10 | 1119210.32 |
September | 0.222211E+09 | 57878501.92 | 0.164333E+09 | 0.988270E+09 | 28860299.72 |
October | 0.293728E+09 | 0.119976E+09 | 0.173753E+09 | 0.104783E+10 | 91794622.33 |
November | 0.306783E+09 | 0.147307E+09 | 0.159477E+09 | 0.908588E+09 | 0.186922E+09 |
December | 0.291875E+09 | 0.142410E+09 | 0.149464E+09 | 0.728908E+09 | 0.318251E+09 |
Annual Sum or Average | 0.269246E+10 | 0.827516E+09 | 0.186494E+10 | 0.969126E+10 | 0.175271E+10 |
Minimum of Months | 0.139596E+09 | 366093.49 | 0.139230E+09 | 0.621698E+09 | 1119210.32 |
Maximum of Months | 0.306783E+09 | 0.147307E+09 | 0.173753E+09 | 0.104783E+10 | 0.371459E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144239E+09 | 67197122.85 | 77041981.31 | 0.337895E+09 | 0.184304E+09 |
February | 0.123985E+09 | 51105545.36 | 72879845.00 | 0.312634E+09 | 0.142157E+09 |
March | 0.115817E+09 | 33949694.69 | 81867624.34 | 0.332507E+09 | 0.121266E+09 |
April | 88701807.32 | 12277541.65 | 76424265.67 | 0.313661E+09 | 76824293.47 |
May | 75717893.03 | 2034620.26 | 73683272.77 | 0.370957E+09 | 24838770.74 |
June | 68293311.79 | 179100.96 | 68114210.83 | 0.375374E+09 | 8883913.19 |
July | 70927787.83 | 1056578.08 | 69871209.75 | 0.457085E+09 | 1109001.03 |
August | 84240871.13 | 8292866.21 | 75948004.93 | 0.512296E+09 | 598453.40 |
September | 0.108711E+09 | 28315431.51 | 80395085.36 | 0.495126E+09 | 14611271.14 |
October | 0.143698E+09 | 58694709.90 | 85003633.19 | 0.525772E+09 | 45967477.44 |
November | 0.150085E+09 | 72065601.30 | 78019570.64 | 0.456257E+09 | 92954243.65 |
December | 0.142791E+09 | 69670306.56 | 73121130.10 | 0.365962E+09 | 0.157875E+09 |
Annual Sum or Average | 0.131721E+10 | 0.404839E+09 | 0.912370E+09 | 0.485552E+10 | 0.871389E+09 |
Minimum of Months | 68293311.79 | 179100.96 | 68114210.83 | 0.312634E+09 | 598453.40 |
Maximum of Months | 0.150085E+09 | 72065601.30 | 85003633.19 | 0.525772E+09 | 0.184304E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1246.69 | 739.58 | 548.61 | 255.58 | 293.03 | 0.00 | 0.00 |
February | 1280.60 | 630.95 | 522.10 | 215.21 | 306.90 | 0.00 | 0.00 |
March | 1232.65 | 481.57 | 440.51 | 129.13 | 311.38 | 0.00 | 0.00 |
April | 1215.61 | 295.67 | 348.62 | 48.25 | 300.37 | 0.00 | 0.00 |
May | 1439.00 | 79.21 | 287.99 | 7.74 | 280.25 | 0.00 | 0.00 |
June | 1521.17 | 25.45 | 268.41 | 0.70 | 267.71 | 0.00 | 0.00 |
July | 1831.09 | 1.22 | 269.77 | 4.02 | 265.75 | 0.00 | 0.00 |
August | 2031.45 | 0.70 | 320.41 | 31.54 | 288.87 | 0.00 | 0.00 |
September | 1996.43 | 40.09 | 427.26 | 111.29 | 315.97 | 0.00 | 0.00 |
October | 2002.81 | 136.05 | 546.55 | 223.24 | 323.31 | 0.00 | 0.00 |
November | 1766.01 | 342.65 | 589.87 | 283.24 | 306.64 | 0.00 | 0.00 |
December | 1358.39 | 613.69 | 543.10 | 264.99 | 278.11 | 0.00 | 0.00 |
Annual Sum or Average | 1578.73 | 280.53 | 425.50 | 130.78 | 294.73 | 0.00 | 0.00 |
Minimum of Months | 1215.61 | 0.70 | 268.41 | 0.70 | 265.75 | 0.00 | 0.00 |
Maximum of Months | 2031.45 | 739.58 | 589.87 | 283.24 | 323.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 617.18 | 376.48 | 274.31 | 127.79 | 146.51 | 0.00 | 0.00 |
February | 634.99 | 321.83 | 261.05 | 107.60 | 153.45 | 0.00 | 0.00 |
March | 613.64 | 245.39 | 220.25 | 64.56 | 155.69 | 0.00 | 0.00 |
April | 608.86 | 150.43 | 174.31 | 24.13 | 150.18 | 0.00 | 0.00 |
May | 728.83 | 39.63 | 144.00 | 3.87 | 140.13 | 0.00 | 0.00 |
June | 774.55 | 11.97 | 134.21 | 0.35 | 133.85 | 0.00 | 0.00 |
July | 934.35 | 0.47 | 134.89 | 2.01 | 132.88 | 0.00 | 0.00 |
August | 1037.07 | 0.25 | 160.20 | 15.77 | 144.43 | 0.00 | 0.00 |
September | 1011.42 | 18.57 | 213.63 | 55.64 | 157.99 | 0.00 | 0.00 |
October | 1008.13 | 65.73 | 273.28 | 111.62 | 161.65 | 0.00 | 0.00 |
November | 883.04 | 169.95 | 294.94 | 141.62 | 153.32 | 0.00 | 0.00 |
December | 675.26 | 310.29 | 271.55 | 132.49 | 139.06 | 0.00 | 0.00 |
Annual Sum or Average | 794.97 | 141.71 | 212.75 | 65.39 | 147.36 | 0.00 | 0.00 |
Minimum of Months | 608.86 | 0.25 | 134.21 | 0.35 | 132.88 | 0.00 | 0.00 |
Maximum of Months | 1037.07 | 376.48 | 294.94 | 141.62 | 161.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 616.35 | 385.32 | 274.01 | 127.65 | 146.36 | 0.00 | 0.00 |
February | 633.46 | 333.85 | 260.77 | 107.49 | 153.28 | 0.00 | 0.00 |
March | 610.51 | 261.64 | 220.02 | 64.49 | 155.52 | 0.00 | 0.00 |
April | 599.84 | 171.52 | 174.12 | 24.10 | 150.02 | 0.00 | 0.00 |
May | 694.48 | 51.67 | 143.84 | 3.87 | 139.98 | 0.00 | 0.00 |
June | 730.21 | 18.29 | 134.06 | 0.35 | 133.71 | 0.00 | 0.00 |
July | 873.77 | 1.37 | 134.74 | 2.01 | 132.73 | 0.00 | 0.00 |
August | 979.05 | 0.71 | 160.03 | 15.75 | 144.28 | 0.00 | 0.00 |
September | 965.94 | 26.03 | 213.40 | 55.58 | 157.82 | 0.00 | 0.00 |
October | 984.99 | 86.65 | 272.98 | 111.50 | 161.48 | 0.00 | 0.00 |
November | 879.20 | 194.64 | 294.62 | 141.47 | 153.15 | 0.00 | 0.00 |
December | 674.20 | 325.52 | 271.26 | 132.35 | 138.91 | 0.00 | 0.00 |
Annual Sum or Average | 771.03 | 153.87 | 212.52 | 65.32 | 147.20 | 0.00 | 0.00 |
Minimum of Months | 599.84 | 0.71 | 134.06 | 0.35 | 132.73 | 0.00 | 0.00 |
Maximum of Months | 984.99 | 385.32 | 294.62 | 141.47 | 161.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 616.74 | 383.63 | 274.01 | 127.65 | 146.36 | 0.00 | 0.00 |
February | 633.59 | 333.11 | 260.77 | 107.49 | 153.28 | 0.00 | 0.00 |
March | 610.37 | 262.12 | 220.02 | 64.49 | 155.52 | 0.00 | 0.00 |
April | 599.26 | 173.84 | 174.12 | 24.10 | 150.02 | 0.00 | 0.00 |
May | 691.57 | 54.62 | 143.84 | 3.87 | 139.98 | 0.00 | 0.00 |
June | 725.75 | 20.41 | 134.06 | 0.35 | 133.71 | 0.00 | 0.00 |
July | 865.95 | 1.77 | 134.74 | 2.01 | 132.73 | 0.00 | 0.00 |
August | 971.46 | 0.94 | 160.03 | 15.75 | 144.28 | 0.00 | 0.00 |
September | 961.54 | 28.58 | 213.40 | 55.58 | 157.82 | 0.00 | 0.00 |
October | 983.37 | 90.77 | 272.98 | 111.50 | 161.48 | 0.00 | 0.00 |
November | 878.63 | 196.89 | 294.62 | 141.47 | 153.15 | 0.00 | 0.00 |
December | 674.22 | 325.34 | 271.26 | 132.35 | 138.91 | 0.00 | 0.00 |
Annual Sum or Average | 768.55 | 155.11 | 212.52 | 65.32 | 147.20 | 0.00 | 0.00 |
Minimum of Months | 599.26 | 0.94 | 134.06 | 0.35 | 132.73 | 0.00 | 0.00 |
Maximum of Months | 983.37 | 383.63 | 294.62 | 141.47 | 161.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 618.16 | 379.82 | 274.01 | 127.65 | 146.36 | 0.00 | 0.00 |
February | 634.74 | 329.75 | 260.77 | 107.49 | 153.28 | 0.00 | 0.00 |
March | 611.46 | 259.00 | 220.02 | 64.49 | 155.52 | 0.00 | 0.00 |
April | 600.21 | 171.24 | 174.12 | 24.10 | 150.02 | 0.00 | 0.00 |
May | 692.86 | 53.36 | 143.84 | 3.87 | 139.98 | 0.00 | 0.00 |
June | 727.51 | 19.72 | 134.06 | 0.35 | 133.71 | 0.00 | 0.00 |
July | 867.49 | 1.73 | 134.74 | 2.01 | 132.73 | 0.00 | 0.00 |
August | 973.26 | 0.89 | 160.03 | 15.75 | 144.28 | 0.00 | 0.00 |
September | 962.80 | 27.79 | 213.40 | 55.58 | 157.82 | 0.00 | 0.00 |
October | 984.10 | 89.10 | 272.98 | 111.50 | 161.48 | 0.00 | 0.00 |
November | 879.46 | 194.46 | 294.62 | 141.47 | 153.15 | 0.00 | 0.00 |
December | 675.30 | 322.20 | 271.26 | 132.35 | 138.91 | 0.00 | 0.00 |
Annual Sum or Average | 769.79 | 153.20 | 212.52 | 65.32 | 147.20 | 0.00 | 0.00 |
Minimum of Months | 600.21 | 0.89 | 134.06 | 0.35 | 132.73 | 0.00 | 0.00 |
Maximum of Months | 984.10 | 379.82 | 294.62 | 141.47 | 161.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1258.63 | 720.50 | 548.02 | 255.31 | 292.71 | 0.00 | 0.00 |
February | 1288.67 | 622.87 | 521.54 | 214.97 | 306.57 | 0.00 | 0.00 |
March | 1238.53 | 483.88 | 440.03 | 128.99 | 311.05 | 0.00 | 0.00 |
April | 1211.69 | 314.31 | 348.25 | 48.20 | 300.04 | 0.00 | 0.00 |
May | 1397.74 | 94.26 | 287.68 | 7.73 | 279.95 | 0.00 | 0.00 |
June | 1467.71 | 32.12 | 268.12 | 0.70 | 267.42 | 0.00 | 0.00 |
July | 1742.74 | 2.74 | 269.48 | 4.01 | 265.47 | 0.00 | 0.00 |
August | 1958.02 | 1.21 | 320.06 | 31.51 | 288.56 | 0.00 | 0.00 |
September | 1939.01 | 48.07 | 426.80 | 111.17 | 315.63 | 0.00 | 0.00 |
October | 1980.31 | 160.89 | 545.96 | 223.00 | 322.96 | 0.00 | 0.00 |
November | 1769.46 | 359.27 | 589.24 | 282.93 | 306.31 | 0.00 | 0.00 |
December | 1367.13 | 609.70 | 542.52 | 264.70 | 277.81 | 0.00 | 0.00 |
Annual Sum or Average | 1553.30 | 285.82 | 425.05 | 130.64 | 294.41 | 0.00 | 0.00 |
Minimum of Months | 1211.69 | 1.21 | 268.12 | 0.70 | 265.47 | 0.00 | 0.00 |
Maximum of Months | 1980.31 | 720.50 | 589.24 | 282.93 | 322.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 626.75 | 358.25 | 274.01 | 127.65 | 146.36 | 0.00 | 0.00 |
February | 642.18 | 308.72 | 260.77 | 107.49 | 153.28 | 0.00 | 0.00 |
March | 619.12 | 238.00 | 220.02 | 64.49 | 155.52 | 0.00 | 0.00 |
April | 608.36 | 152.51 | 174.12 | 24.10 | 150.02 | 0.00 | 0.00 |
May | 708.38 | 43.93 | 143.84 | 3.87 | 139.98 | 0.00 | 0.00 |
June | 747.09 | 13.79 | 134.06 | 0.35 | 133.71 | 0.00 | 0.00 |
July | 887.85 | 1.06 | 134.74 | 2.01 | 132.73 | 0.00 | 0.00 |
August | 995.78 | 0.38 | 160.03 | 15.75 | 144.28 | 0.00 | 0.00 |
September | 979.45 | 21.40 | 213.40 | 55.58 | 157.82 | 0.00 | 0.00 |
October | 994.37 | 75.51 | 272.98 | 111.50 | 161.48 | 0.00 | 0.00 |
November | 884.84 | 174.65 | 294.62 | 141.47 | 153.15 | 0.00 | 0.00 |
December | 681.96 | 301.76 | 271.26 | 132.35 | 138.91 | 0.00 | 0.00 |
Annual Sum or Average | 782.23 | 140.00 | 212.52 | 65.32 | 147.20 | 0.00 | 0.00 |
Minimum of Months | 608.36 | 0.38 | 134.06 | 0.35 | 132.73 | 0.00 | 0.00 |
Maximum of Months | 995.78 | 358.25 | 294.62 | 141.47 | 161.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 627.40 | 356.98 | 274.01 | 127.65 | 146.36 | 0.00 | 0.00 |
February | 642.80 | 307.40 | 260.77 | 107.49 | 153.28 | 0.00 | 0.00 |
March | 619.73 | 236.75 | 220.02 | 64.49 | 155.52 | 0.00 | 0.00 |
April | 609.00 | 151.45 | 174.12 | 24.10 | 150.02 | 0.00 | 0.00 |
May | 709.36 | 43.40 | 143.84 | 3.87 | 139.98 | 0.00 | 0.00 |
June | 748.29 | 13.48 | 134.06 | 0.35 | 133.71 | 0.00 | 0.00 |
July | 889.25 | 1.03 | 134.74 | 2.01 | 132.73 | 0.00 | 0.00 |
August | 997.18 | 0.36 | 160.03 | 15.75 | 144.28 | 0.00 | 0.00 |
September | 980.49 | 21.08 | 213.40 | 55.58 | 157.82 | 0.00 | 0.00 |
October | 995.06 | 74.83 | 272.98 | 111.50 | 161.48 | 0.00 | 0.00 |
November | 885.40 | 173.76 | 294.62 | 141.47 | 153.15 | 0.00 | 0.00 |
December | 682.50 | 300.66 | 271.26 | 132.35 | 138.91 | 0.00 | 0.00 |
Annual Sum or Average | 783.09 | 139.27 | 212.52 | 65.32 | 147.20 | 0.00 | 0.00 |
Minimum of Months | 609.00 | 0.36 | 134.06 | 0.35 | 132.73 | 0.00 | 0.00 |
Maximum of Months | 997.18 | 356.98 | 294.62 | 141.47 | 161.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 628.11 | 355.38 | 274.01 | 127.65 | 146.36 | 0.00 | 0.00 |
February | 643.41 | 305.78 | 260.77 | 107.49 | 153.28 | 0.00 | 0.00 |
March | 620.10 | 235.55 | 220.02 | 64.49 | 155.52 | 0.00 | 0.00 |
April | 608.89 | 151.31 | 174.12 | 24.10 | 150.02 | 0.00 | 0.00 |
May | 707.82 | 44.09 | 143.84 | 3.87 | 139.98 | 0.00 | 0.00 |
June | 745.78 | 14.14 | 134.06 | 0.35 | 133.71 | 0.00 | 0.00 |
July | 885.00 | 1.18 | 134.74 | 2.01 | 132.73 | 0.00 | 0.00 |
August | 992.26 | 0.46 | 160.03 | 15.75 | 144.28 | 0.00 | 0.00 |
September | 977.40 | 22.18 | 213.40 | 55.58 | 157.82 | 0.00 | 0.00 |
October | 993.51 | 76.67 | 272.98 | 111.50 | 161.48 | 0.00 | 0.00 |
November | 884.79 | 174.80 | 294.62 | 141.47 | 153.15 | 0.00 | 0.00 |
December | 682.71 | 300.15 | 271.26 | 132.35 | 138.91 | 0.00 | 0.00 |
Annual Sum or Average | 781.69 | 139.32 | 212.52 | 65.32 | 147.20 | 0.00 | 0.00 |
Minimum of Months | 608.89 | 0.46 | 134.06 | 0.35 | 132.73 | 0.00 | 0.00 |
Maximum of Months | 993.51 | 355.38 | 294.62 | 141.47 | 161.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 628.32 | 346.18 | 274.01 | 127.65 | 146.36 | 0.00 | 0.00 |
February | 643.20 | 295.84 | 260.77 | 107.49 | 153.28 | 0.00 | 0.00 |
March | 618.33 | 227.64 | 220.02 | 64.49 | 155.52 | 0.00 | 0.00 |
April | 603.33 | 148.73 | 174.12 | 24.10 | 150.02 | 0.00 | 0.00 |
May | 692.77 | 46.23 | 143.84 | 3.87 | 139.98 | 0.00 | 0.00 |
June | 725.06 | 16.82 | 134.06 | 0.35 | 133.71 | 0.00 | 0.00 |
July | 854.84 | 1.99 | 134.74 | 2.01 | 132.73 | 0.00 | 0.00 |
August | 957.42 | 1.06 | 160.03 | 15.75 | 144.28 | 0.00 | 0.00 |
September | 953.57 | 27.90 | 213.40 | 55.58 | 157.82 | 0.00 | 0.00 |
October | 978.73 | 85.71 | 272.98 | 111.50 | 161.48 | 0.00 | 0.00 |
November | 877.10 | 180.09 | 294.62 | 141.47 | 153.15 | 0.00 | 0.00 |
December | 680.92 | 296.59 | 271.26 | 132.35 | 138.91 | 0.00 | 0.00 |
Annual Sum or Average | 768.58 | 138.79 | 212.52 | 65.32 | 147.20 | 0.00 | 0.00 |
Minimum of Months | 603.33 | 1.06 | 134.06 | 0.35 | 132.73 | 0.00 | 0.00 |
Maximum of Months | 978.73 | 346.18 | 294.62 | 141.47 | 161.48 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.333913E+10 | 0.198089E+10 | 0.146940E+10 | 0.684553E+09 | 0.784845E+09 | 0.00 | 0.00 |
February | 0.309802E+10 | 0.152641E+10 | 0.126307E+10 | 0.520624E+09 | 0.742444E+09 | 0.00 | 0.00 |
March | 0.330154E+10 | 0.128982E+10 | 0.117986E+10 | 0.345854E+09 | 0.834005E+09 | 0.00 | 0.00 |
April | 0.315085E+10 | 0.766382E+09 | 0.903626E+09 | 0.125074E+09 | 0.778552E+09 | 0.00 | 0.00 |
May | 0.385422E+10 | 0.212151E+09 | 0.771356E+09 | 20727160.05 | 0.750629E+09 | 0.00 | 0.00 |
June | 0.394288E+10 | 65953482.32 | 0.695720E+09 | 1824544.00 | 0.693896E+09 | 0.00 | 0.00 |
July | 0.490440E+10 | 3274074.34 | 0.722558E+09 | 10763611.97 | 0.711795E+09 | 0.00 | 0.00 |
August | 0.544104E+10 | 1873497.69 | 0.858182E+09 | 84481398.65 | 0.773700E+09 | 0.00 | 0.00 |
September | 0.517475E+10 | 0.103922E+09 | 0.110746E+10 | 0.288456E+09 | 0.819004E+09 | 0.00 | 0.00 |
October | 0.536433E+10 | 0.364389E+09 | 0.146389E+10 | 0.597937E+09 | 0.865952E+09 | 0.00 | 0.00 |
November | 0.457749E+10 | 0.888148E+09 | 0.152895E+10 | 0.734149E+09 | 0.794804E+09 | 0.00 | 0.00 |
December | 0.363831E+10 | 0.164370E+10 | 0.145465E+10 | 0.709748E+09 | 0.744902E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.497870E+11 | 0.884692E+10 | 0.134187E+11 | 0.412419E+10 | 0.929453E+10 | 0.00 | 0.00 |
Minimum of Months | 0.309802E+10 | 1873497.69 | 0.695720E+09 | 1824544.00 | 0.693896E+09 | 0.00 | 0.00 |
Maximum of Months | 0.544104E+10 | 0.198089E+10 | 0.152895E+10 | 0.734149E+09 | 0.865952E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165305E+10 | 0.100837E+10 | 0.734699E+09 | 0.342277E+09 | 0.392422E+09 | 0.00 | 0.00 |
February | 0.153617E+10 | 0.778580E+09 | 0.631534E+09 | 0.260312E+09 | 0.371222E+09 | 0.00 | 0.00 |
March | 0.164357E+10 | 0.657251E+09 | 0.589929E+09 | 0.172927E+09 | 0.417002E+09 | 0.00 | 0.00 |
April | 0.157815E+10 | 0.389908E+09 | 0.451813E+09 | 62537117.13 | 0.389276E+09 | 0.00 | 0.00 |
May | 0.195211E+10 | 0.106135E+09 | 0.385678E+09 | 10363580.03 | 0.375315E+09 | 0.00 | 0.00 |
June | 0.200764E+10 | 31016505.94 | 0.347860E+09 | 912272.00 | 0.346948E+09 | 0.00 | 0.00 |
July | 0.250256E+10 | 1254175.84 | 0.361279E+09 | 5381805.99 | 0.355897E+09 | 0.00 | 0.00 |
August | 0.277769E+10 | 656690.96 | 0.429091E+09 | 42240699.33 | 0.386850E+09 | 0.00 | 0.00 |
September | 0.262161E+10 | 48145108.36 | 0.553730E+09 | 0.144228E+09 | 0.409502E+09 | 0.00 | 0.00 |
October | 0.270017E+10 | 0.176055E+09 | 0.731945E+09 | 0.298968E+09 | 0.432976E+09 | 0.00 | 0.00 |
November | 0.228884E+10 | 0.440519E+09 | 0.764477E+09 | 0.367075E+09 | 0.397402E+09 | 0.00 | 0.00 |
December | 0.180863E+10 | 0.831093E+09 | 0.727325E+09 | 0.354874E+09 | 0.372451E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.250702E+11 | 0.446899E+10 | 0.670936E+10 | 0.206210E+10 | 0.464726E+10 | 0.00 | 0.00 |
Minimum of Months | 0.153617E+10 | 656690.96 | 0.347860E+09 | 912272.00 | 0.346948E+09 | 0.00 | 0.00 |
Maximum of Months | 0.277769E+10 | 0.100837E+10 | 0.764477E+09 | 0.367075E+09 | 0.432976E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165083E+10 | 0.103204E+10 | 0.733906E+09 | 0.341907E+09 | 0.391999E+09 | 0.00 | 0.00 |
February | 0.153247E+10 | 0.807639E+09 | 0.630853E+09 | 0.260031E+09 | 0.370822E+09 | 0.00 | 0.00 |
March | 0.163518E+10 | 0.700786E+09 | 0.589293E+09 | 0.172740E+09 | 0.416553E+09 | 0.00 | 0.00 |
April | 0.155477E+10 | 0.444583E+09 | 0.451326E+09 | 62469658.11 | 0.388856E+09 | 0.00 | 0.00 |
May | 0.186010E+10 | 0.138396E+09 | 0.385262E+09 | 10352400.79 | 0.374910E+09 | 0.00 | 0.00 |
June | 0.189270E+10 | 47419929.40 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
July | 0.234029E+10 | 3681122.47 | 0.360889E+09 | 5376000.61 | 0.355513E+09 | 0.00 | 0.00 |
August | 0.262230E+10 | 1900335.31 | 0.428628E+09 | 42195134.13 | 0.386433E+09 | 0.00 | 0.00 |
September | 0.250373E+10 | 67474680.77 | 0.553133E+09 | 0.144072E+09 | 0.409060E+09 | 0.00 | 0.00 |
October | 0.263821E+10 | 0.232081E+09 | 0.731155E+09 | 0.298646E+09 | 0.432509E+09 | 0.00 | 0.00 |
November | 0.227887E+10 | 0.504503E+09 | 0.763652E+09 | 0.366679E+09 | 0.396973E+09 | 0.00 | 0.00 |
December | 0.180578E+10 | 0.871876E+09 | 0.726541E+09 | 0.354491E+09 | 0.372049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.243152E+11 | 0.485238E+10 | 0.670212E+10 | 0.205987E+10 | 0.464225E+10 | 0.00 | 0.00 |
Minimum of Months | 0.153247E+10 | 1900335.31 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.263821E+10 | 0.103204E+10 | 0.763652E+09 | 0.366679E+09 | 0.432509E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165187E+10 | 0.102752E+10 | 0.733906E+09 | 0.341907E+09 | 0.391999E+09 | 0.00 | 0.00 |
February | 0.153277E+10 | 0.805863E+09 | 0.630853E+09 | 0.260031E+09 | 0.370822E+09 | 0.00 | 0.00 |
March | 0.163482E+10 | 0.702074E+09 | 0.589293E+09 | 0.172740E+09 | 0.416553E+09 | 0.00 | 0.00 |
April | 0.155327E+10 | 0.450594E+09 | 0.451326E+09 | 62469658.11 | 0.388856E+09 | 0.00 | 0.00 |
May | 0.185230E+10 | 0.146300E+09 | 0.385262E+09 | 10352400.79 | 0.374910E+09 | 0.00 | 0.00 |
June | 0.188115E+10 | 52909775.37 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
July | 0.231935E+10 | 4741956.13 | 0.360889E+09 | 5376000.61 | 0.355513E+09 | 0.00 | 0.00 |
August | 0.260196E+10 | 2509493.15 | 0.428628E+09 | 42195134.13 | 0.386433E+09 | 0.00 | 0.00 |
September | 0.249232E+10 | 74083324.57 | 0.553133E+09 | 0.144072E+09 | 0.409060E+09 | 0.00 | 0.00 |
October | 0.263387E+10 | 0.243118E+09 | 0.731155E+09 | 0.298646E+09 | 0.432509E+09 | 0.00 | 0.00 |
November | 0.227741E+10 | 0.510344E+09 | 0.763652E+09 | 0.366679E+09 | 0.396973E+09 | 0.00 | 0.00 |
December | 0.180584E+10 | 0.871381E+09 | 0.726541E+09 | 0.354491E+09 | 0.372049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.242369E+11 | 0.489144E+10 | 0.670212E+10 | 0.205987E+10 | 0.464225E+10 | 0.00 | 0.00 |
Minimum of Months | 0.153277E+10 | 2509493.15 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.263387E+10 | 0.102752E+10 | 0.763652E+09 | 0.366679E+09 | 0.432509E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165567E+10 | 0.101731E+10 | 0.733906E+09 | 0.341907E+09 | 0.391999E+09 | 0.00 | 0.00 |
February | 0.153556E+10 | 0.797728E+09 | 0.630853E+09 | 0.260031E+09 | 0.370822E+09 | 0.00 | 0.00 |
March | 0.163774E+10 | 0.693706E+09 | 0.589293E+09 | 0.172740E+09 | 0.416553E+09 | 0.00 | 0.00 |
April | 0.155573E+10 | 0.443860E+09 | 0.451326E+09 | 62469658.11 | 0.388856E+09 | 0.00 | 0.00 |
May | 0.185576E+10 | 0.142917E+09 | 0.385262E+09 | 10352400.79 | 0.374910E+09 | 0.00 | 0.00 |
June | 0.188570E+10 | 51111570.45 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
July | 0.232350E+10 | 4637188.25 | 0.360889E+09 | 5376000.61 | 0.355513E+09 | 0.00 | 0.00 |
August | 0.260677E+10 | 2387391.71 | 0.428628E+09 | 42195134.13 | 0.386433E+09 | 0.00 | 0.00 |
September | 0.249558E+10 | 72042905.78 | 0.553133E+09 | 0.144072E+09 | 0.409060E+09 | 0.00 | 0.00 |
October | 0.263580E+10 | 0.238634E+09 | 0.731155E+09 | 0.298646E+09 | 0.432509E+09 | 0.00 | 0.00 |
November | 0.227956E+10 | 0.504031E+09 | 0.763652E+09 | 0.366679E+09 | 0.396973E+09 | 0.00 | 0.00 |
December | 0.180873E+10 | 0.862989E+09 | 0.726541E+09 | 0.354491E+09 | 0.372049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.242761E+11 | 0.483135E+10 | 0.670212E+10 | 0.205987E+10 | 0.464225E+10 | 0.00 | 0.00 |
Minimum of Months | 0.153556E+10 | 2387391.71 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.263580E+10 | 0.101731E+10 | 0.763652E+09 | 0.366679E+09 | 0.432509E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.337112E+10 | 0.192980E+10 | 0.146781E+10 | 0.683815E+09 | 0.783998E+09 | 0.00 | 0.00 |
February | 0.311755E+10 | 0.150685E+10 | 0.126171E+10 | 0.520063E+09 | 0.741643E+09 | 0.00 | 0.00 |
March | 0.331729E+10 | 0.129601E+10 | 0.117859E+10 | 0.345481E+09 | 0.833105E+09 | 0.00 | 0.00 |
April | 0.314071E+10 | 0.814702E+09 | 0.902652E+09 | 0.124939E+09 | 0.777712E+09 | 0.00 | 0.00 |
May | 0.374370E+10 | 0.252466E+09 | 0.770524E+09 | 20704801.59 | 0.749819E+09 | 0.00 | 0.00 |
June | 0.380431E+10 | 83260655.43 | 0.694970E+09 | 1822575.86 | 0.693147E+09 | 0.00 | 0.00 |
July | 0.466775E+10 | 7339744.24 | 0.721779E+09 | 10752001.22 | 0.711027E+09 | 0.00 | 0.00 |
August | 0.524436E+10 | 3244014.96 | 0.857256E+09 | 84390268.25 | 0.772866E+09 | 0.00 | 0.00 |
September | 0.502590E+10 | 0.124610E+09 | 0.110627E+10 | 0.288145E+09 | 0.818120E+09 | 0.00 | 0.00 |
October | 0.530405E+10 | 0.430923E+09 | 0.146231E+10 | 0.597292E+09 | 0.865018E+09 | 0.00 | 0.00 |
November | 0.458643E+10 | 0.931240E+09 | 0.152730E+10 | 0.733357E+09 | 0.793947E+09 | 0.00 | 0.00 |
December | 0.366172E+10 | 0.163303E+10 | 0.145308E+10 | 0.708982E+09 | 0.744099E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.489849E+11 | 0.901347E+10 | 0.134042E+11 | 0.411974E+10 | 0.928450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.311755E+10 | 3244014.96 | 0.694970E+09 | 1822575.86 | 0.693147E+09 | 0.00 | 0.00 |
Maximum of Months | 0.530405E+10 | 0.192980E+10 | 0.152730E+10 | 0.733357E+09 | 0.865018E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167870E+10 | 0.959541E+09 | 0.733906E+09 | 0.341907E+09 | 0.391999E+09 | 0.00 | 0.00 |
February | 0.155357E+10 | 0.746853E+09 | 0.630853E+09 | 0.260031E+09 | 0.370822E+09 | 0.00 | 0.00 |
March | 0.165824E+10 | 0.637454E+09 | 0.589293E+09 | 0.172740E+09 | 0.416553E+09 | 0.00 | 0.00 |
April | 0.157687E+10 | 0.395296E+09 | 0.451326E+09 | 62469658.11 | 0.388856E+09 | 0.00 | 0.00 |
May | 0.189732E+10 | 0.117672E+09 | 0.385262E+09 | 10352400.79 | 0.374910E+09 | 0.00 | 0.00 |
June | 0.193646E+10 | 35732497.72 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
July | 0.237803E+10 | 2836515.82 | 0.360889E+09 | 5376000.61 | 0.355513E+09 | 0.00 | 0.00 |
August | 0.266709E+10 | 1022981.60 | 0.428628E+09 | 42195134.13 | 0.386433E+09 | 0.00 | 0.00 |
September | 0.253873E+10 | 55472604.20 | 0.553133E+09 | 0.144072E+09 | 0.409060E+09 | 0.00 | 0.00 |
October | 0.266333E+10 | 0.202245E+09 | 0.731155E+09 | 0.298646E+09 | 0.432509E+09 | 0.00 | 0.00 |
November | 0.229350E+10 | 0.452700E+09 | 0.763652E+09 | 0.366679E+09 | 0.396973E+09 | 0.00 | 0.00 |
December | 0.182656E+10 | 0.808236E+09 | 0.726541E+09 | 0.354491E+09 | 0.372049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.246684E+11 | 0.441506E+10 | 0.670212E+10 | 0.205987E+10 | 0.464225E+10 | 0.00 | 0.00 |
Minimum of Months | 0.155357E+10 | 1022981.60 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.266709E+10 | 0.959541E+09 | 0.763652E+09 | 0.366679E+09 | 0.432509E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168043E+10 | 0.956131E+09 | 0.733906E+09 | 0.341907E+09 | 0.391999E+09 | 0.00 | 0.00 |
February | 0.155507E+10 | 0.743673E+09 | 0.630853E+09 | 0.260031E+09 | 0.370822E+09 | 0.00 | 0.00 |
March | 0.165989E+10 | 0.634122E+09 | 0.589293E+09 | 0.172740E+09 | 0.416553E+09 | 0.00 | 0.00 |
April | 0.157853E+10 | 0.392553E+09 | 0.451326E+09 | 62469658.11 | 0.388856E+09 | 0.00 | 0.00 |
May | 0.189995E+10 | 0.116251E+09 | 0.385262E+09 | 10352400.79 | 0.374910E+09 | 0.00 | 0.00 |
June | 0.193958E+10 | 34940674.78 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
July | 0.238178E+10 | 2749352.82 | 0.360889E+09 | 5376000.61 | 0.355513E+09 | 0.00 | 0.00 |
August | 0.267084E+10 | 965369.99 | 0.428628E+09 | 42195134.13 | 0.386433E+09 | 0.00 | 0.00 |
September | 0.254144E+10 | 54649997.87 | 0.553133E+09 | 0.144072E+09 | 0.409060E+09 | 0.00 | 0.00 |
October | 0.266516E+10 | 0.200438E+09 | 0.731155E+09 | 0.298646E+09 | 0.432509E+09 | 0.00 | 0.00 |
November | 0.229497E+10 | 0.450393E+09 | 0.763652E+09 | 0.366679E+09 | 0.396973E+09 | 0.00 | 0.00 |
December | 0.182802E+10 | 0.805281E+09 | 0.726541E+09 | 0.354491E+09 | 0.372049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.246956E+11 | 0.439215E+10 | 0.670212E+10 | 0.205987E+10 | 0.464225E+10 | 0.00 | 0.00 |
Minimum of Months | 0.155507E+10 | 965369.99 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.267084E+10 | 0.956131E+09 | 0.763652E+09 | 0.366679E+09 | 0.432509E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168233E+10 | 0.951848E+09 | 0.733906E+09 | 0.341907E+09 | 0.391999E+09 | 0.00 | 0.00 |
February | 0.155654E+10 | 0.739750E+09 | 0.630853E+09 | 0.260031E+09 | 0.370822E+09 | 0.00 | 0.00 |
March | 0.166088E+10 | 0.630898E+09 | 0.589293E+09 | 0.172740E+09 | 0.416553E+09 | 0.00 | 0.00 |
April | 0.157823E+10 | 0.392185E+09 | 0.451326E+09 | 62469658.11 | 0.388856E+09 | 0.00 | 0.00 |
May | 0.189582E+10 | 0.118096E+09 | 0.385262E+09 | 10352400.79 | 0.374910E+09 | 0.00 | 0.00 |
June | 0.193306E+10 | 36643179.51 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
July | 0.237038E+10 | 3157541.49 | 0.360889E+09 | 5376000.61 | 0.355513E+09 | 0.00 | 0.00 |
August | 0.265768E+10 | 1228054.42 | 0.428628E+09 | 42195134.13 | 0.386433E+09 | 0.00 | 0.00 |
September | 0.253342E+10 | 57490793.93 | 0.553133E+09 | 0.144072E+09 | 0.409060E+09 | 0.00 | 0.00 |
October | 0.266102E+10 | 0.205353E+09 | 0.731155E+09 | 0.298646E+09 | 0.432509E+09 | 0.00 | 0.00 |
November | 0.229336E+10 | 0.453071E+09 | 0.763652E+09 | 0.366679E+09 | 0.396973E+09 | 0.00 | 0.00 |
December | 0.182857E+10 | 0.803928E+09 | 0.726541E+09 | 0.354491E+09 | 0.372049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.246513E+11 | 0.439365E+10 | 0.670212E+10 | 0.205987E+10 | 0.464225E+10 | 0.00 | 0.00 |
Minimum of Months | 0.155654E+10 | 1228054.42 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.266102E+10 | 0.951848E+09 | 0.763652E+09 | 0.366679E+09 | 0.432509E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168289E+10 | 0.927221E+09 | 0.733906E+09 | 0.341907E+09 | 0.391999E+09 | 0.00 | 0.00 |
February | 0.155603E+10 | 0.715697E+09 | 0.630853E+09 | 0.260031E+09 | 0.370822E+09 | 0.00 | 0.00 |
March | 0.165615E+10 | 0.609719E+09 | 0.589293E+09 | 0.172740E+09 | 0.416553E+09 | 0.00 | 0.00 |
April | 0.156384E+10 | 0.385499E+09 | 0.451326E+09 | 62469658.11 | 0.388856E+09 | 0.00 | 0.00 |
May | 0.185553E+10 | 0.123816E+09 | 0.385262E+09 | 10352400.79 | 0.374910E+09 | 0.00 | 0.00 |
June | 0.187934E+10 | 43608558.56 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
July | 0.228961E+10 | 5333372.86 | 0.360889E+09 | 5376000.61 | 0.355513E+09 | 0.00 | 0.00 |
August | 0.256434E+10 | 2835459.27 | 0.428628E+09 | 42195134.13 | 0.386433E+09 | 0.00 | 0.00 |
September | 0.247166E+10 | 72329319.03 | 0.553133E+09 | 0.144072E+09 | 0.409060E+09 | 0.00 | 0.00 |
October | 0.262144E+10 | 0.229556E+09 | 0.731155E+09 | 0.298646E+09 | 0.432509E+09 | 0.00 | 0.00 |
November | 0.227343E+10 | 0.466799E+09 | 0.763652E+09 | 0.366679E+09 | 0.396973E+09 | 0.00 | 0.00 |
December | 0.182378E+10 | 0.794377E+09 | 0.726541E+09 | 0.354491E+09 | 0.372049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.242380E+11 | 0.437679E+10 | 0.670212E+10 | 0.205987E+10 | 0.464225E+10 | 0.00 | 0.00 |
Minimum of Months | 0.155603E+10 | 2835459.27 | 0.347485E+09 | 911287.93 | 0.346574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.262144E+10 | 0.927221E+09 | 0.763652E+09 | 0.366679E+09 | 0.432509E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.123876E+10 | -0.108085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157910905.8 | 59.95 | 0.00 | 0.00 |
February | 0.109743E+10 | -955126691.3 | 0.00 | 0.00 | 672.00 | 0.00 | -142306182.1 | 59.95 | 0.00 | 0.00 |
March | 0.116874E+10 | -0.101173E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157014935.2 | 59.95 | 0.00 | 0.00 |
April | 0.101365E+10 | -862345790.8 | 0.00 | 0.00 | 720.00 | 0.00 | -151302209.4 | 59.95 | 0.00 | 0.00 |
May | 0.956814E+09 | -801939423.8 | 0.00 | 0.00 | 744.00 | 0.00 | -154874846.2 | 59.95 | 0.00 | 0.00 |
June | 0.867664E+09 | -718435612.7 | 0.00 | 0.00 | 720.00 | 0.00 | -149228700.7 | 59.95 | 0.00 | 0.00 |
July | 0.849575E+09 | -696286644.2 | 0.00 | 0.00 | 744.00 | 0.00 | -153288597.0 | 59.95 | 0.00 | 0.00 |
August | 0.906428E+09 | -753442870.0 | 0.00 | 0.00 | 744.00 | 0.00 | -152984872.5 | 59.95 | 0.00 | 0.00 |
September | 0.934452E+09 | -785491106.6 | 0.00 | 0.00 | 720.00 | 0.00 | -148961174.3 | 59.95 | 0.00 | 0.00 |
October | 0.105563E+10 | -900924775.2 | 0.00 | 0.00 | 744.00 | 0.00 | -154705951.4 | 59.95 | 0.00 | 0.00 |
November | 0.111338E+10 | -962482517.6 | 0.00 | 0.00 | 720.00 | 0.00 | -150893153.8 | 59.95 | 0.00 | 0.00 |
December | 0.121382E+10 | -0.105663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157187755.2 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.124163E+11 | -0.105857E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.183066E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.849575E+09 | -0.108085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157910905.8 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.123876E+10 | -696286644.2 | 0.00 | 0.00 | 744.00 | 0.00 | -142306182.1 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_SUPPHEATCOIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.258411E+11 | 0.212671E+11 | 38136.49 | 29-JAN-08:63 | 29661.43 | 0.00 |
February | 0.00 | 0.00 | 0.276676E+11 | 0.221944E+11 | 73085.90 | 09-FEB-08:62 | 46048.56 | 0.00 |
March | 0.00 | 0.00 | 0.353445E+11 | 0.292785E+11 | 81399.42 | 02-MAR-08:62 | 71235.45 | 0.00 |
April | 0.00 | 0.00 | 0.447580E+11 | 0.358727E+11 | 87521.00 | 30-APR-07:02 | 51799.29 | 0.00 |
May | 0.00 | 0.00 | 0.611914E+11 | 0.485053E+11 | 90169.90 | 30-MAY-07:01 | 49223.78 | 0.00 |
June | 0.00 | 0.00 | 0.716865E+11 | 0.508974E+11 | 92224.65 | 19-JUN-07:01 | 44561.96 | 0.00 |
July | 0.00 | 0.00 | 0.838621E+11 | 0.575166E+11 | 92743.25 | 18-JUL-07:01 | 45167.49 | 0.00 |
August | 0.00 | 0.00 | 0.879602E+11 | 0.590103E+11 | 92911.74 | 08-AUG-07:02 | 38759.52 | 0.00 |
September | 0.00 | 0.00 | 0.765322E+11 | 0.516849E+11 | 91619.77 | 11-SEP-07:01 | 47635.21 | 0.00 |
October | 0.00 | 0.00 | 0.630865E+11 | 0.468542E+11 | 91644.78 | 08-OCT-07:01 | 45994.49 | 0.00 |
November | 0.00 | 0.00 | 0.466881E+11 | 0.359261E+11 | 87663.97 | 03-NOV-07:02 | 54245.33 | 0.00 |
December | 0.00 | 0.00 | 0.333588E+11 | 0.259187E+11 | 85541.22 | 12-DEC-08:62 | 59499.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.657977E+12 | 0.484926E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.258411E+11 | 0.212671E+11 | 38136.49 | 29661.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.879602E+11 | 0.590103E+11 | 92911.74 | 71235.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.133310E+11 | 0.111125E+11 | 19971.17 | 29-JAN-08:63 | 16575.72 | 0.00 |
February | 0.00 | 0.00 | 0.141009E+11 | 0.114971E+11 | 34855.66 | 09-FEB-08:62 | 24870.15 | 0.00 |
March | 0.00 | 0.00 | 0.178366E+11 | 0.149752E+11 | 41452.57 | 02-MAR-08:62 | 36752.42 | 0.00 |
April | 0.00 | 0.00 | 0.221905E+11 | 0.180800E+11 | 43755.68 | 30-APR-07:02 | 29935.30 | 0.00 |
May | 0.00 | 0.00 | 0.301684E+11 | 0.242261E+11 | 44819.64 | 30-MAY-07:01 | 28616.82 | 0.00 |
June | 0.00 | 0.00 | 0.354072E+11 | 0.254796E+11 | 45815.20 | 19-JUN-07:01 | 26194.58 | 0.00 |
July | 0.00 | 0.00 | 0.417391E+11 | 0.288446E+11 | 46213.94 | 18-JUL-07:01 | 25793.84 | 0.00 |
August | 0.00 | 0.00 | 0.437308E+11 | 0.295206E+11 | 47144.58 | 08-AUG-07:01 | 23697.65 | 0.00 |
September | 0.00 | 0.00 | 0.377692E+11 | 0.258235E+11 | 45630.49 | 10-SEP-07:01 | 27131.82 | 0.00 |
October | 0.00 | 0.00 | 0.309472E+11 | 0.233096E+11 | 45655.80 | 08-OCT-07:01 | 26668.73 | 0.00 |
November | 0.00 | 0.00 | 0.230184E+11 | 0.179355E+11 | 43865.95 | 02-NOV-07:02 | 30563.33 | 0.00 |
December | 0.00 | 0.00 | 0.168006E+11 | 0.132757E+11 | 42910.94 | 12-DEC-08:62 | 32901.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.327040E+12 | 0.244080E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.133310E+11 | 0.111125E+11 | 19971.17 | 16575.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.437308E+11 | 0.295206E+11 | 47144.58 | 36752.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.101789E+11 | 0.845813E+10 | 22603.72 | 30-JAN-07:03 | 14469.36 | 0.00 |
February | 0.00 | 0.00 | 0.110914E+11 | 0.901352E+10 | 43948.41 | 09-FEB-07:03 | 26885.92 | 0.00 |
March | 0.00 | 0.00 | 0.143719E+11 | 0.120827E+11 | 42756.00 | 29-MAR-06:03 | 25501.54 | 0.00 |
April | 0.00 | 0.00 | 0.177975E+11 | 0.145661E+11 | 45229.09 | 30-APR-07:02 | 26025.86 | 0.00 |
May | 0.00 | 0.00 | 0.246889E+11 | 0.198820E+11 | 46732.77 | 01-MAY-06:02 | 21149.08 | 0.00 |
June | 0.00 | 0.00 | 0.290256E+11 | 0.209722E+11 | 47741.09 | 19-JUN-06:01 | 19413.96 | 0.00 |
July | 0.00 | 0.00 | 0.338873E+11 | 0.232593E+11 | 47611.10 | 06-JUL-06:01 | 21937.23 | 0.00 |
August | 0.00 | 0.00 | 0.362122E+11 | 0.242806E+11 | 47515.45 | 26-AUG-06:01 | 22062.75 | 0.00 |
September | 0.00 | 0.00 | 0.306057E+11 | 0.209366E+11 | 47888.09 | 25-SEP-06:01 | 19653.76 | 0.00 |
October | 0.00 | 0.00 | 0.252541E+11 | 0.189174E+11 | 47889.49 | 01-OCT-07:01 | 20534.62 | 0.00 |
November | 0.00 | 0.00 | 0.189272E+11 | 0.145649E+11 | 45699.83 | 03-NOV-06:02 | 25716.33 | 0.00 |
December | 0.00 | 0.00 | 0.132095E+11 | 0.103584E+11 | 43652.06 | 12-DEC-07:02 | 30567.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.265250E+12 | 0.197292E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.101789E+11 | 0.845813E+10 | 22603.72 | 14469.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.362122E+11 | 0.242806E+11 | 47889.49 | 30567.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.101365E+11 | 0.842069E+10 | 22571.33 | 30-JAN-07:03 | 14446.91 | 0.00 |
February | 0.00 | 0.00 | 0.110772E+11 | 0.900189E+10 | 44425.43 | 09-FEB-07:03 | 27196.00 | 0.00 |
March | 0.00 | 0.00 | 0.143909E+11 | 0.121003E+11 | 43780.84 | 29-MAR-06:03 | 26153.22 | 0.00 |
April | 0.00 | 0.00 | 0.178687E+11 | 0.146306E+11 | 45303.68 | 30-APR-07:02 | 26184.72 | 0.00 |
May | 0.00 | 0.00 | 0.248421E+11 | 0.200204E+11 | 46810.83 | 01-MAY-06:02 | 21355.57 | 0.00 |
June | 0.00 | 0.00 | 0.291970E+11 | 0.211215E+11 | 47800.41 | 19-JUN-06:01 | 19700.34 | 0.00 |
July | 0.00 | 0.00 | 0.341074E+11 | 0.234498E+11 | 47670.26 | 06-JUL-06:01 | 22181.03 | 0.00 |
August | 0.00 | 0.00 | 0.364341E+11 | 0.244712E+11 | 47574.49 | 26-AUG-06:01 | 22283.13 | 0.00 |
September | 0.00 | 0.00 | 0.307933E+11 | 0.210980E+11 | 47972.33 | 25-SEP-06:01 | 19911.62 | 0.00 |
October | 0.00 | 0.00 | 0.254083E+11 | 0.190525E+11 | 47949.00 | 01-OCT-07:01 | 20738.03 | 0.00 |
November | 0.00 | 0.00 | 0.189982E+11 | 0.146282E+11 | 45773.51 | 03-NOV-06:02 | 25859.33 | 0.00 |
December | 0.00 | 0.00 | 0.132086E+11 | 0.103582E+11 | 43711.66 | 12-DEC-07:02 | 30633.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.266462E+12 | 0.198353E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.101365E+11 | 0.842069E+10 | 22571.33 | 14446.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.364341E+11 | 0.244712E+11 | 47972.33 | 30633.54 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.995363E+10 | 0.825845E+10 | 21612.86 | 30-JAN-07:03 | 13795.48 | 0.00 |
February | 0.00 | 0.00 | 0.109253E+11 | 0.886999E+10 | 42840.09 | 09-FEB-07:03 | 26167.63 | 0.00 |
March | 0.00 | 0.00 | 0.142349E+11 | 0.119607E+11 | 42194.60 | 29-MAR-06:03 | 25143.46 | 0.00 |
April | 0.00 | 0.00 | 0.177417E+11 | 0.145170E+11 | 45267.61 | 30-APR-07:02 | 26115.84 | 0.00 |
May | 0.00 | 0.00 | 0.247616E+11 | 0.199464E+11 | 46778.78 | 01-MAY-06:02 | 21315.54 | 0.00 |
June | 0.00 | 0.00 | 0.291263E+11 | 0.210591E+11 | 47768.06 | 19-JUN-06:01 | 19702.01 | 0.00 |
July | 0.00 | 0.00 | 0.340767E+11 | 0.234226E+11 | 47637.99 | 06-JUL-06:01 | 22096.04 | 0.00 |
August | 0.00 | 0.00 | 0.363978E+11 | 0.244398E+11 | 47542.29 | 26-AUG-06:01 | 22149.16 | 0.00 |
September | 0.00 | 0.00 | 0.307360E+11 | 0.210489E+11 | 47941.95 | 25-SEP-06:01 | 19898.04 | 0.00 |
October | 0.00 | 0.00 | 0.253307E+11 | 0.189840E+11 | 47916.55 | 01-OCT-07:01 | 20682.75 | 0.00 |
November | 0.00 | 0.00 | 0.188858E+11 | 0.145298E+11 | 45731.48 | 03-NOV-06:02 | 25739.78 | 0.00 |
December | 0.00 | 0.00 | 0.130493E+11 | 0.102207E+11 | 43668.66 | 12-DEC-07:02 | 30528.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.265220E+12 | 0.197257E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.995363E+10 | 0.825845E+10 | 21612.86 | 13795.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.363978E+11 | 0.244398E+11 | 47941.95 | 30528.30 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.171742E+11 | 0.139109E+11 | 44528.64 | 29-JAN-09:03 | 32075.70 | 0.00 |
February | 0.00 | 0.00 | 0.191272E+11 | 0.151950E+11 | 67832.51 | 09-FEB-08:62 | 42241.71 | 0.00 |
March | 0.00 | 0.00 | 0.253712E+11 | 0.209128E+11 | 77541.39 | 02-MAR-08:62 | 63523.87 | 0.00 |
April | 0.00 | 0.00 | 0.319289E+11 | 0.257184E+11 | 83719.07 | 30-APR-08:62 | 46878.68 | 0.00 |
May | 0.00 | 0.00 | 0.451118E+11 | 0.358701E+11 | 86168.27 | 01-MAY-07:02 | 38665.32 | 0.00 |
June | 0.00 | 0.00 | 0.531720E+11 | 0.379347E+11 | 88150.35 | 25-JUN-08:61 | 39394.40 | 0.00 |
July | 0.00 | 0.00 | 0.620411E+11 | 0.421195E+11 | 87374.31 | 05-JUL-07:01 | 35771.46 | 0.00 |
August | 0.00 | 0.00 | 0.666920E+11 | 0.441698E+11 | 87535.81 | 08-AUG-07:01 | 43002.15 | 0.00 |
September | 0.00 | 0.00 | 0.561454E+11 | 0.378594E+11 | 88282.69 | 25-SEP-07:01 | 36662.52 | 0.00 |
October | 0.00 | 0.00 | 0.459237E+11 | 0.340442E+11 | 88125.10 | 02-OCT-07:02 | 37187.65 | 0.00 |
November | 0.00 | 0.00 | 0.339875E+11 | 0.256841E+11 | 82817.70 | 03-NOV-07:02 | 50011.08 | 0.00 |
December | 0.00 | 0.00 | 0.228829E+11 | 0.175228E+11 | 79928.76 | 12-DEC-08:62 | 57013.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.479558E+12 | 0.350942E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.171742E+11 | 0.139109E+11 | 44528.64 | 32075.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.666920E+11 | 0.441698E+11 | 88282.69 | 63523.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.892116E+10 | 0.724334E+10 | 21181.79 | 29-JAN-09:03 | 15244.65 | 0.00 |
February | 0.00 | 0.00 | 0.993184E+10 | 0.790785E+10 | 32573.84 | 06-FEB-08:62 | 21571.66 | 0.00 |
March | 0.00 | 0.00 | 0.131808E+11 | 0.108860E+11 | 40478.80 | 02-MAR-08:62 | 33160.44 | 0.00 |
April | 0.00 | 0.00 | 0.166099E+11 | 0.133943E+11 | 43775.32 | 30-APR-08:62 | 24287.47 | 0.00 |
May | 0.00 | 0.00 | 0.234717E+11 | 0.186758E+11 | 45091.80 | 01-MAY-07:02 | 19966.61 | 0.00 |
June | 0.00 | 0.00 | 0.276479E+11 | 0.197403E+11 | 46091.07 | 25-JUN-08:61 | 20312.19 | 0.00 |
July | 0.00 | 0.00 | 0.322736E+11 | 0.219253E+11 | 45656.36 | 05-JUL-07:01 | 18372.18 | 0.00 |
August | 0.00 | 0.00 | 0.346683E+11 | 0.229746E+11 | 45729.13 | 21-AUG-07:01 | 19642.90 | 0.00 |
September | 0.00 | 0.00 | 0.291892E+11 | 0.197010E+11 | 46185.78 | 25-SEP-07:01 | 18841.77 | 0.00 |
October | 0.00 | 0.00 | 0.238829E+11 | 0.177331E+11 | 46048.68 | 02-OCT-07:02 | 19139.06 | 0.00 |
November | 0.00 | 0.00 | 0.176828E+11 | 0.133848E+11 | 43220.76 | 03-NOV-07:02 | 26153.22 | 0.00 |
December | 0.00 | 0.00 | 0.119020E+11 | 0.913322E+10 | 41737.37 | 12-DEC-08:62 | 29796.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.249362E+12 | 0.182700E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.892116E+10 | 0.724334E+10 | 21181.79 | 15244.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.346683E+11 | 0.229746E+11 | 46185.78 | 33160.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.883776E+10 | 0.716979E+10 | 20733.98 | 29-JAN-09:03 | 14900.43 | 0.00 |
February | 0.00 | 0.00 | 0.985095E+10 | 0.783766E+10 | 32001.57 | 06-FEB-08:62 | 21179.19 | 0.00 |
March | 0.00 | 0.00 | 0.130895E+11 | 0.108044E+11 | 40361.25 | 02-MAR-08:62 | 33018.58 | 0.00 |
April | 0.00 | 0.00 | 0.165241E+11 | 0.133177E+11 | 43650.83 | 30-APR-08:62 | 24174.78 | 0.00 |
May | 0.00 | 0.00 | 0.233841E+11 | 0.185961E+11 | 44965.71 | 01-MAY-07:02 | 19867.36 | 0.00 |
June | 0.00 | 0.00 | 0.275594E+11 | 0.196624E+11 | 45963.53 | 25-JUN-08:61 | 20211.41 | 0.00 |
July | 0.00 | 0.00 | 0.321871E+11 | 0.218492E+11 | 45530.01 | 05-JUL-07:01 | 18292.12 | 0.00 |
August | 0.00 | 0.00 | 0.345774E+11 | 0.228952E+11 | 45602.59 | 21-AUG-07:01 | 19562.50 | 0.00 |
September | 0.00 | 0.00 | 0.291047E+11 | 0.196278E+11 | 46057.97 | 25-SEP-07:01 | 18761.63 | 0.00 |
October | 0.00 | 0.00 | 0.238001E+11 | 0.176596E+11 | 45921.25 | 02-OCT-07:01 | 19184.98 | 0.00 |
November | 0.00 | 0.00 | 0.176026E+11 | 0.133143E+11 | 43101.32 | 03-NOV-07:02 | 26025.21 | 0.00 |
December | 0.00 | 0.00 | 0.118189E+11 | 0.906172E+10 | 41618.13 | 12-DEC-08:62 | 29671.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.248337E+12 | 0.181796E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.883776E+10 | 0.716979E+10 | 20733.98 | 14900.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.345774E+11 | 0.228952E+11 | 46057.97 | 33018.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.880891E+10 | 0.714587E+10 | 20199.83 | 29-JAN-09:03 | 14503.55 | 0.00 |
February | 0.00 | 0.00 | 0.982210E+10 | 0.781488E+10 | 31402.76 | 06-FEB-08:62 | 20793.47 | 0.00 |
March | 0.00 | 0.00 | 0.130740E+11 | 0.107929E+11 | 40533.02 | 02-MAR-08:62 | 33173.12 | 0.00 |
April | 0.00 | 0.00 | 0.165585E+11 | 0.133503E+11 | 43834.95 | 30-APR-08:62 | 24297.03 | 0.00 |
May | 0.00 | 0.00 | 0.235109E+11 | 0.187116E+11 | 45155.71 | 01-MAY-07:02 | 19978.00 | 0.00 |
June | 0.00 | 0.00 | 0.277242E+11 | 0.198066E+11 | 46161.00 | 25-JUN-08:61 | 20391.81 | 0.00 |
July | 0.00 | 0.00 | 0.323994E+11 | 0.220339E+11 | 45725.62 | 05-JUL-07:04 | 17932.94 | 0.00 |
August | 0.00 | 0.00 | 0.348306E+11 | 0.231134E+11 | 45798.51 | 21-AUG-07:01 | 19803.62 | 0.00 |
September | 0.00 | 0.00 | 0.293117E+11 | 0.198052E+11 | 46255.85 | 25-SEP-07:01 | 18953.05 | 0.00 |
October | 0.00 | 0.00 | 0.239699E+11 | 0.178089E+11 | 46118.54 | 02-OCT-07:01 | 19387.34 | 0.00 |
November | 0.00 | 0.00 | 0.177001E+11 | 0.134006E+11 | 43286.99 | 03-NOV-07:02 | 26222.66 | 0.00 |
December | 0.00 | 0.00 | 0.118309E+11 | 0.907364E+10 | 41796.55 | 12-DEC-08:62 | 29819.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.249541E+12 | 0.182858E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.880891E+10 | 0.714587E+10 | 20199.83 | 14503.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.348306E+11 | 0.231134E+11 | 46255.85 | 33173.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.940134E+10 | 0.772221E+10 | 19309.99 | 29-JAN-09:03 | 13587.38 | 0.00 |
February | 0.00 | 0.00 | 0.104119E+11 | 0.837558E+10 | 29452.95 | 06-FEB-08:62 | 18119.33 | 0.00 |
March | 0.00 | 0.00 | 0.138658E+11 | 0.115620E+11 | 43835.73 | 02-MAR-08:62 | 38370.07 | 0.00 |
April | 0.00 | 0.00 | 0.178146E+11 | 0.145050E+11 | 48668.97 | 30-APR-08:62 | 24662.09 | 0.00 |
May | 0.00 | 0.00 | 0.256397E+11 | 0.206281E+11 | 50381.40 | 30-MAY-07:01 | 23842.64 | 0.00 |
June | 0.00 | 0.00 | 0.302933E+11 | 0.219342E+11 | 50567.74 | 25-JUN-08:02 | 20325.58 | 0.00 |
July | 0.00 | 0.00 | 0.355088E+11 | 0.245236E+11 | 50183.39 | 26-JUL-07:01 | 22375.97 | 0.00 |
August | 0.00 | 0.00 | 0.383679E+11 | 0.259402E+11 | 50183.39 | 08-AUG-07:06 | 18273.96 | 0.00 |
September | 0.00 | 0.00 | 0.322033E+11 | 0.221557E+11 | 50671.64 | 25-SEP-07:01 | 20137.09 | 0.00 |
October | 0.00 | 0.00 | 0.263611E+11 | 0.198578E+11 | 50521.22 | 02-OCT-07:01 | 20072.55 | 0.00 |
November | 0.00 | 0.00 | 0.193320E+11 | 0.148478E+11 | 48243.63 | 03-NOV-07:02 | 26910.71 | 0.00 |
December | 0.00 | 0.00 | 0.126927E+11 | 0.986874E+10 | 45225.07 | 12-DEC-08:62 | 30610.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.271892E+12 | 0.201921E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.940134E+10 | 0.772221E+10 | 19309.99 | 13587.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.383679E+11 | 0.259402E+11 | 50671.64 | 38370.07 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.979460E+10 | 0.90 | 5398.26 | 01-JAN-09:25 | 1.33 |
February | 0.886178E+10 | 0.90 | 5398.26 | 01-FEB-11:00 | 1.32 |
March | 0.983346E+10 | 0.90 | 5398.26 | 01-MAR-09:20 | 1.32 |
April | 0.948366E+10 | 0.89 | 5398.26 | 01-APR-07:05 | 1.32 |
May | 0.979460E+10 | 0.89 | 5398.26 | 01-MAY-07:08 | 1.31 |
June | 0.952253E+10 | 0.90 | 5398.26 | 01-JUN-07:30 | 1.32 |
July | 0.979460E+10 | 0.89 | 5398.26 | 01-JUL-07:06 | 1.31 |
August | 0.981403E+10 | 0.89 | 5398.26 | 01-AUG-08:00 | 1.32 |
September | 0.950309E+10 | 0.89 | 5398.26 | 01-SEP-07:06 | 1.31 |
October | 0.979460E+10 | 0.89 | 5398.26 | 01-OCT-07:10 | 1.31 |
November | 0.946422E+10 | 0.89 | 5398.26 | 01-NOV-07:20 | 1.31 |
December | 0.983346E+10 | 0.90 | 5398.26 | 01-DEC-08:50 | 1.32 |
Annual Sum or Average | 0.115495E+12 | 0.89 | |||
Minimum of Months | 0.886178E+10 | 0.89 | 5398.26 | 1.31 | |
Maximum of Months | 0.983346E+10 | 0.90 | 5398.26 | 1.33 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.420626E+10 | 0.97 | 2833.76 | 01-JAN-09:15 | 1.36 |
February | 0.384038E+10 | 0.97 | 2833.76 | 01-FEB-09:00 | 1.35 |
March | 0.433690E+10 | 0.97 | 2833.76 | 01-MAR-09:50 | 1.35 |
April | 0.428018E+10 | 0.96 | 2833.76 | 01-APR-07:40 | 1.35 |
May | 0.462333E+10 | 0.95 | 2833.76 | 01-MAY-07:40 | 1.35 |
June | 0.463427E+10 | 0.94 | 2833.76 | 01-JUN-07:08 | 1.35 |
July | 0.488740E+10 | 0.93 | 2833.76 | 01-JUL-07:04 | 1.35 |
August | 0.493496E+10 | 0.93 | 2833.76 | 01-AUG-07:09 | 1.35 |
September | 0.466516E+10 | 0.94 | 2833.76 | 01-SEP-07:30 | 1.35 |
October | 0.461205E+10 | 0.95 | 2833.76 | 01-OCT-07:06 | 1.35 |
November | 0.426892E+10 | 0.96 | 2833.76 | 01-NOV-07:20 | 1.35 |
December | 0.426380E+10 | 0.97 | 2833.76 | 01-DEC-09:50 | 1.36 |
Annual Sum or Average | 0.535536E+11 | 0.95 | |||
Minimum of Months | 0.384038E+10 | 0.93 | 2833.76 | 1.35 | |
Maximum of Months | 0.493496E+10 | 0.97 | 2833.76 | 1.36 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.410024E+10 | 0.73 | 2833.22 | 01-JAN-09:25 | 1.36 |
February | 0.371265E+10 | 0.73 | 2833.22 | 01-FEB-07:10 | 1.35 |
March | 0.418184E+10 | 0.75 | 2833.22 | 01-MAR-09:10 | 1.35 |
April | 0.397784E+10 | 0.73 | 2833.22 | 02-APR-08:40 | 1.36 |
May | 0.414104E+10 | 0.74 | 2833.22 | 01-MAY-08:20 | 1.35 |
June | 0.403904E+10 | 0.74 | 2833.22 | 01-JUN-07:06 | 1.35 |
July | 0.407984E+10 | 0.72 | 2833.22 | 01-JUL-11:10 | 1.35 |
August | 0.418233E+10 | 0.74 | 2833.22 | 01-AUG-09:50 | 1.35 |
September | 0.397784E+10 | 0.73 | 2833.22 | 01-SEP-10:00 | 1.35 |
October | 0.410024E+10 | 0.73 | 2833.22 | 01-OCT-08:09 | 1.35 |
November | 0.397784E+10 | 0.73 | 2833.22 | 01-NOV-06:50 | 1.35 |
December | 0.407984E+10 | 0.73 | 2833.22 | 01-DEC-07:40 | 1.35 |
Annual Sum or Average | 0.485506E+11 | 0.73 | |||
Minimum of Months | 0.371265E+10 | 0.72 | 2833.22 | 1.35 | |
Maximum of Months | 0.418233E+10 | 0.75 | 2833.22 | 1.36 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.410658E+10 | 0.73 | 2837.60 | 01-JAN-10:30 | 1.36 |
February | 0.371839E+10 | 0.73 | 2837.60 | 01-FEB-10:50 | 1.35 |
March | 0.418830E+10 | 0.75 | 2837.60 | 01-MAR-07:08 | 1.35 |
April | 0.398399E+10 | 0.73 | 2837.60 | 01-APR-10:00 | 1.36 |
May | 0.414744E+10 | 0.74 | 2837.60 | 01-MAY-07:03 | 1.35 |
June | 0.404528E+10 | 0.74 | 2837.60 | 01-JUN-07:01 | 1.35 |
July | 0.408663E+10 | 0.73 | 2837.60 | 01-JUL-08:20 | 1.35 |
August | 0.419054E+10 | 0.75 | 2837.60 | 01-AUG-06:06 | 1.34 |
September | 0.398451E+10 | 0.73 | 2837.60 | 01-SEP-12:20 | 1.35 |
October | 0.410658E+10 | 0.73 | 2837.60 | 01-OCT-07:08 | 1.34 |
November | 0.398399E+10 | 0.73 | 2837.60 | 01-NOV-10:10 | 1.35 |
December | 0.408615E+10 | 0.73 | 2837.60 | 01-DEC-08:63 | 1.36 |
Annual Sum or Average | 0.486284E+11 | 0.73 | |||
Minimum of Months | 0.371839E+10 | 0.73 | 2837.60 | 1.34 | |
Maximum of Months | 0.419054E+10 | 0.75 | 2837.60 | 1.36 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.410308E+10 | 0.73 | 2835.19 | 06-JAN-12:00 | 1.35 |
February | 0.371523E+10 | 0.73 | 2835.19 | 01-FEB-18:40 | 1.35 |
March | 0.418473E+10 | 0.75 | 2835.19 | 02-MAR-08:05 | 1.35 |
April | 0.398060E+10 | 0.73 | 2835.19 | 02-APR-08:00 | 1.36 |
May | 0.414391E+10 | 0.74 | 2835.19 | 02-MAY-08:00 | 1.35 |
June | 0.404184E+10 | 0.74 | 2835.19 | 04-JUN-15:40 | 1.35 |
July | 0.408316E+10 | 0.73 | 2835.19 | 02-JUL-11:20 | 1.35 |
August | 0.418681E+10 | 0.75 | 2835.19 | 04-AUG-17:30 | 1.35 |
September | 0.398113E+10 | 0.73 | 2835.19 | 09-SEP-16:50 | 1.35 |
October | 0.410308E+10 | 0.73 | 2835.19 | 02-OCT-06:06 | 1.34 |
November | 0.398060E+10 | 0.73 | 2835.19 | 04-NOV-06:08 | 1.35 |
December | 0.408267E+10 | 0.73 | 2835.19 | 08-DEC-19:10 | 1.35 |
Annual Sum or Average | 0.485868E+11 | 0.73 | |||
Minimum of Months | 0.371523E+10 | 0.73 | 2835.19 | 1.34 | |
Maximum of Months | 0.418681E+10 | 0.75 | 2835.19 | 1.36 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.669964E+10 | 0.66 | 5016.20 | 01-JAN-11:30 | 1.32 |
February | 0.606760E+10 | 0.66 | 5016.20 | 01-FEB-09:20 | 1.32 |
March | 0.684411E+10 | 0.67 | 5016.20 | 01-MAR-10:00 | 1.32 |
April | 0.650100E+10 | 0.66 | 5016.20 | 01-APR-08:00 | 1.32 |
May | 0.677187E+10 | 0.67 | 5016.20 | 01-MAY-07:50 | 1.31 |
June | 0.660935E+10 | 0.67 | 5016.20 | 01-JUN-10:20 | 1.32 |
July | 0.666449E+10 | 0.65 | 5016.20 | 01-JUL-10:10 | 1.32 |
August | 0.684765E+10 | 0.67 | 5016.20 | 01-AUG-09:40 | 1.32 |
September | 0.650267E+10 | 0.66 | 5016.20 | 01-SEP-08:40 | 1.32 |
October | 0.669964E+10 | 0.66 | 5016.20 | 01-OCT-08:09 | 1.31 |
November | 0.650100E+10 | 0.66 | 5016.20 | 01-NOV-07:03 | 1.32 |
December | 0.666352E+10 | 0.65 | 5016.20 | 01-DEC-08:30 | 1.32 |
Annual Sum or Average | 0.793725E+11 | 0.66 | |||
Minimum of Months | 0.606760E+10 | 0.65 | 5016.20 | 1.31 | |
Maximum of Months | 0.684765E+10 | 0.67 | 5016.20 | 1.32 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.360803E+10 | 0.68 | 2701.43 | 01-JAN-11:20 | 1.36 |
February | 0.326765E+10 | 0.68 | 2701.43 | 01-FEB-09:10 | 1.35 |
March | 0.368583E+10 | 0.69 | 2701.43 | 01-MAR-08:62 | 1.35 |
April | 0.350105E+10 | 0.68 | 2701.43 | 01-APR-07:05 | 1.35 |
May | 0.364693E+10 | 0.68 | 2701.43 | 16-MAY-13:50 | 1.35 |
June | 0.355940E+10 | 0.69 | 2701.43 | 01-JUN-07:05 | 1.35 |
July | 0.358857E+10 | 0.67 | 2701.43 | 01-JUL-07:10 | 1.34 |
August | 0.368679E+10 | 0.69 | 2701.43 | 01-AUG-07:07 | 1.35 |
September | 0.350148E+10 | 0.68 | 2701.43 | 01-SEP-07:04 | 1.34 |
October | 0.360803E+10 | 0.67 | 2701.43 | 01-OCT-08:08 | 1.34 |
November | 0.350105E+10 | 0.68 | 2701.43 | 01-NOV-07:08 | 1.35 |
December | 0.358857E+10 | 0.67 | 2701.43 | 27-DEC-20:45 | 1.35 |
Annual Sum or Average | 0.427434E+11 | 0.68 | |||
Minimum of Months | 0.326765E+10 | 0.67 | 2701.43 | 1.34 | |
Maximum of Months | 0.368679E+10 | 0.69 | 2701.43 | 1.36 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.359539E+10 | 0.68 | 2691.97 | 01-JAN-10:20 | 1.36 |
February | 0.325620E+10 | 0.68 | 2691.97 | 02-FEB-11:10 | 1.35 |
March | 0.367292E+10 | 0.69 | 2691.97 | 01-MAR-15:20 | 1.36 |
April | 0.348879E+10 | 0.68 | 2691.97 | 01-APR-08:50 | 1.35 |
May | 0.363415E+10 | 0.68 | 2691.97 | 01-MAY-13:10 | 1.35 |
June | 0.354693E+10 | 0.69 | 2691.97 | 01-JUN-07:15 | 1.35 |
July | 0.357601E+10 | 0.67 | 2691.97 | 01-JUL-10:10 | 1.35 |
August | 0.367371E+10 | 0.69 | 2691.97 | 01-AUG-10:10 | 1.35 |
September | 0.348921E+10 | 0.68 | 2691.97 | 01-SEP-18:10 | 1.35 |
October | 0.359539E+10 | 0.67 | 2691.97 | 01-OCT-08:20 | 1.34 |
November | 0.348879E+10 | 0.68 | 2691.97 | 01-NOV-07:05 | 1.35 |
December | 0.357601E+10 | 0.67 | 2691.97 | 01-DEC-14:20 | 1.35 |
Annual Sum or Average | 0.425935E+11 | 0.68 | |||
Minimum of Months | 0.325620E+10 | 0.67 | 2691.97 | 1.34 | |
Maximum of Months | 0.367371E+10 | 0.69 | 2691.97 | 1.36 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.361484E+10 | 0.68 | 2706.53 | 02-JAN-20:00 | 1.36 |
February | 0.327382E+10 | 0.68 | 2706.53 | 01-FEB-08:50 | 1.35 |
March | 0.369279E+10 | 0.69 | 2706.53 | 01-MAR-08:10 | 1.35 |
April | 0.350766E+10 | 0.68 | 2706.53 | 01-APR-07:20 | 1.35 |
May | 0.365381E+10 | 0.68 | 2706.53 | 01-MAY-07:08 | 1.34 |
June | 0.356612E+10 | 0.69 | 2706.53 | 07-JUN-15:20 | 1.35 |
July | 0.359535E+10 | 0.67 | 2706.53 | 01-JUL-07:04 | 1.35 |
August | 0.369383E+10 | 0.69 | 2706.53 | 09-AUG-17:10 | 1.35 |
September | 0.350808E+10 | 0.68 | 2706.53 | 01-SEP-07:04 | 1.34 |
October | 0.361484E+10 | 0.67 | 2706.53 | 04-OCT-13:00 | 1.35 |
November | 0.350766E+10 | 0.68 | 2706.53 | 01-NOV-07:03 | 1.35 |
December | 0.359535E+10 | 0.67 | 2706.53 | 01-DEC-08:10 | 1.35 |
Annual Sum or Average | 0.428242E+11 | 0.68 | |||
Minimum of Months | 0.327382E+10 | 0.67 | 2706.53 | 1.34 | |
Maximum of Months | 0.369383E+10 | 0.69 | 2706.53 | 1.36 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.407058E+10 | 0.68 | 3047.75 | 01-JAN-10:20 | 1.36 |
February | 0.368656E+10 | 0.68 | 3047.75 | 01-FEB-09:20 | 1.35 |
March | 0.415835E+10 | 0.69 | 3047.75 | 01-MAR-08:30 | 1.35 |
April | 0.394989E+10 | 0.68 | 3047.75 | 01-APR-07:10 | 1.35 |
May | 0.411446E+10 | 0.68 | 3047.75 | 08-MAY-16:00 | 1.35 |
June | 0.401617E+10 | 0.69 | 3047.75 | 01-JUN-07:30 | 1.35 |
July | 0.405784E+10 | 0.68 | 3047.75 | 05-JUL-09:50 | 1.35 |
August | 0.417043E+10 | 0.70 | 3047.75 | 13-AUG-09:40 | 1.35 |
September | 0.395405E+10 | 0.68 | 3047.75 | 01-SEP-07:04 | 1.35 |
October | 0.407058E+10 | 0.67 | 3047.75 | 30-OCT-13:50 | 1.35 |
November | 0.394989E+10 | 0.68 | 3047.75 | 01-NOV-07:40 | 1.35 |
December | 0.404863E+10 | 0.67 | 3047.75 | 01-DEC-08:40 | 1.36 |
Annual Sum or Average | 0.482474E+11 | 0.68 | |||
Minimum of Months | 0.368656E+10 | 0.67 | 3047.75 | 1.35 | |
Maximum of Months | 0.417043E+10 | 0.70 | 3047.75 | 1.36 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.174941E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.171414E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.206137E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.234007E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.295710E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.325330E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.372928E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.386008E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.335401E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.291574E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.234935E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.197084E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.322547E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.171414E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.386008E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.804712E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.792498E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.960985E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.109913E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.141436E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.157512E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.182438E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.188923E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.162618E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.138857E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.109951E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.908372E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.153830E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.792498E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.188923E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.702621E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.691893E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.842679E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.934680E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.118811E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.131384E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.149117E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.157413E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.133592E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115875E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.945806E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.785754E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.129654E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.691893E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.157413E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.702178E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.692145E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.843897E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.937273E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.119317E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.131964E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.149889E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.158214E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134224E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116355E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.948299E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.786418E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.130098E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.692145E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.158214E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.696971E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.687854E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.839471E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.933616E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.119047E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.131703E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.149733E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.158031E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134007E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116105E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.945133E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.781973E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.129713E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.687854E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.158031E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.118305E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.118076E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.146162E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.164740E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.214029E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.238516E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.271840E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.288616E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.243006E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.207943E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.166887E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.134512E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.231263E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.118076E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.288616E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.619166E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.615731E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.760108E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.853116E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110319E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.122630E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.139500E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.147931E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.124829E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.107193E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.864051E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.701099E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.119373E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.615731E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.147931E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.615622E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.612383E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.756291E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.849451E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.109919E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.122220E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.139080E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.147488E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.124436E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.106820E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.860600E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.697593E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.118916E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.612383E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.147488E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.616877E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.613493E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.758061E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.852579E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110518E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.122944E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.139987E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.148544E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125281E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.107513E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.865265E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.699979E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.119541E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.613493E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.148544E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.680292E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.673089E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.829996E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.937034E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.121969E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.135682E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.154894E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.165062E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.138858E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.119261E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.957841E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.771219E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.132067E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.673089E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.165062E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.979460E+10 | 0.258411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.886178E+10 | 0.276676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.983346E+10 | 0.353445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.948366E+10 | 0.447580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.979460E+10 | 0.611914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.952253E+10 | 0.716865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.979460E+10 | 0.838621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.981403E+10 | 0.879602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.950309E+10 | 0.765322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.979460E+10 | 0.630865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.946422E+10 | 0.466881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.983346E+10 | 0.333588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115495E+12 | 0.657977E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.886178E+10 | 0.258411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.983346E+10 | 0.879602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.420626E+10 | 0.133310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384038E+10 | 0.141009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433690E+10 | 0.178366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.428018E+10 | 0.221905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.462333E+10 | 0.301684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.463427E+10 | 0.354072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.488740E+10 | 0.417391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.493496E+10 | 0.437308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.466516E+10 | 0.377692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.461205E+10 | 0.309472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.426892E+10 | 0.230184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426380E+10 | 0.168006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.535536E+11 | 0.327040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.384038E+10 | 0.133310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.493496E+10 | 0.437308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.410024E+10 | 0.101789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371265E+10 | 0.110914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418184E+10 | 0.143719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397784E+10 | 0.177975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.414104E+10 | 0.246889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.403904E+10 | 0.290256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.407984E+10 | 0.338873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.418233E+10 | 0.362122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.397784E+10 | 0.306057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410024E+10 | 0.252541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397784E+10 | 0.189272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407984E+10 | 0.132095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485506E+11 | 0.265250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371265E+10 | 0.101789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.418233E+10 | 0.362122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.410658E+10 | 0.101365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371839E+10 | 0.110772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418830E+10 | 0.143909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398399E+10 | 0.178687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.414744E+10 | 0.248421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.404528E+10 | 0.291970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.408663E+10 | 0.341074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.419054E+10 | 0.364341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.398451E+10 | 0.307933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410658E+10 | 0.254083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.398399E+10 | 0.189982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408615E+10 | 0.132086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486284E+11 | 0.266462E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371839E+10 | 0.101365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.419054E+10 | 0.364341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.410308E+10 | 0.995363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371523E+10 | 0.109253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418473E+10 | 0.142349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398060E+10 | 0.177417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.414391E+10 | 0.247616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.404184E+10 | 0.291263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.408316E+10 | 0.340767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.418681E+10 | 0.363978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.398113E+10 | 0.307360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410308E+10 | 0.253307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.398060E+10 | 0.188858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408267E+10 | 0.130493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485868E+11 | 0.265220E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371523E+10 | 0.995363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.418681E+10 | 0.363978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.669964E+10 | 0.171742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.606760E+10 | 0.191272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.684411E+10 | 0.253712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.650100E+10 | 0.319289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.677187E+10 | 0.451118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.660935E+10 | 0.531720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.666449E+10 | 0.620411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.684765E+10 | 0.666920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.650267E+10 | 0.561454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.669964E+10 | 0.459237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.650100E+10 | 0.339875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.666352E+10 | 0.228829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793725E+11 | 0.479558E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.606760E+10 | 0.171742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.684765E+10 | 0.666920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.360803E+10 | 0.892116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326765E+10 | 0.993184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368583E+10 | 0.131808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350105E+10 | 0.166099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.364693E+10 | 0.234717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.355940E+10 | 0.276479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.358857E+10 | 0.322736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.368679E+10 | 0.346683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350148E+10 | 0.291892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360803E+10 | 0.238829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350105E+10 | 0.176828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358857E+10 | 0.119020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.427434E+11 | 0.249362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.326765E+10 | 0.892116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.368679E+10 | 0.346683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.359539E+10 | 0.883776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325620E+10 | 0.985095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.367292E+10 | 0.130895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348879E+10 | 0.165241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.363415E+10 | 0.233841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.354693E+10 | 0.275594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.357601E+10 | 0.321871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.367371E+10 | 0.345774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.348921E+10 | 0.291047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.359539E+10 | 0.238001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348879E+10 | 0.176026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357601E+10 | 0.118189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425935E+11 | 0.248337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325620E+10 | 0.883776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.367371E+10 | 0.345774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.361484E+10 | 0.880891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327382E+10 | 0.982210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369279E+10 | 0.130740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350766E+10 | 0.165585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.365381E+10 | 0.235109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.356612E+10 | 0.277242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.359535E+10 | 0.323994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.369383E+10 | 0.348306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350808E+10 | 0.293117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.361484E+10 | 0.239699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350766E+10 | 0.177001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359535E+10 | 0.118309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428242E+11 | 0.249541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.327382E+10 | 0.880891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.369383E+10 | 0.348306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.407058E+10 | 0.940134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.368656E+10 | 0.104119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415835E+10 | 0.138658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394989E+10 | 0.178146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.411446E+10 | 0.256397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.401617E+10 | 0.302933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.405784E+10 | 0.355088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.417043E+10 | 0.383679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.395405E+10 | 0.322033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.407058E+10 | 0.263611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.394989E+10 | 0.193320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.404863E+10 | 0.126927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482474E+11 | 0.271892E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.368656E+10 | 0.940134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.417043E+10 | 0.383679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.979460E+10 | 0.00 | 0.00 | 0.00 | 0.769946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.886178E+10 | 0.00 | 0.00 | 0.00 | 0.827967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.983346E+10 | 0.00 | 0.00 | 0.00 | 0.107802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.948366E+10 | 0.00 | 0.00 | 0.00 | 0.139170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.979460E+10 | 0.00 | 0.00 | 0.00 | 0.197764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.952253E+10 | 0.00 | 0.00 | 0.00 | 0.230105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.979460E+10 | 0.00 | 0.00 | 0.00 | 0.274982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.981403E+10 | 0.00 | 0.00 | 0.00 | 0.287868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.950309E+10 | 0.00 | 0.00 | 0.00 | 0.240370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.979460E+10 | 0.00 | 0.00 | 0.00 | 0.193628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.946422E+10 | 0.00 | 0.00 | 0.00 | 0.140292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.983346E+10 | 0.00 | 0.00 | 0.00 | 0.987492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115495E+12 | 0.00 | 0.00 | 0.00 | 0.207052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.886178E+10 | 0.00 | 0.00 | 0.00 | 0.769946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.983346E+10 | 0.00 | 0.00 | 0.00 | 0.287868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.420626E+10 | 0.00 | 0.00 | 0.00 | 0.384086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384038E+10 | 0.00 | 0.00 | 0.00 | 0.408460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433690E+10 | 0.00 | 0.00 | 0.00 | 0.527295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.428018E+10 | 0.00 | 0.00 | 0.00 | 0.671116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.462333E+10 | 0.00 | 0.00 | 0.00 | 0.952031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.463427E+10 | 0.00 | 0.00 | 0.00 | 0.111169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.488740E+10 | 0.00 | 0.00 | 0.00 | 0.133564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.493496E+10 | 0.00 | 0.00 | 0.00 | 0.139573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.466516E+10 | 0.00 | 0.00 | 0.00 | 0.115966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.461205E+10 | 0.00 | 0.00 | 0.00 | 0.927365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.426892E+10 | 0.00 | 0.00 | 0.00 | 0.672615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426380E+10 | 0.00 | 0.00 | 0.00 | 0.481991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.535536E+11 | 0.00 | 0.00 | 0.00 | 0.100277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.384038E+10 | 0.00 | 0.00 | 0.00 | 0.384086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.493496E+10 | 0.00 | 0.00 | 0.00 | 0.139573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.410024E+10 | 0.00 | 0.00 | 0.00 | 0.292597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371265E+10 | 0.00 | 0.00 | 0.00 | 0.320627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418184E+10 | 0.00 | 0.00 | 0.00 | 0.424496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397784E+10 | 0.00 | 0.00 | 0.00 | 0.536895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.414104E+10 | 0.00 | 0.00 | 0.00 | 0.774003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.403904E+10 | 0.00 | 0.00 | 0.00 | 0.909937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.407984E+10 | 0.00 | 0.00 | 0.00 | 0.108319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.418233E+10 | 0.00 | 0.00 | 0.00 | 0.115590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.397784E+10 | 0.00 | 0.00 | 0.00 | 0.938138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410024E+10 | 0.00 | 0.00 | 0.00 | 0.748730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397784E+10 | 0.00 | 0.00 | 0.00 | 0.548021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407984E+10 | 0.00 | 0.00 | 0.00 | 0.377770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485506E+11 | 0.00 | 0.00 | 0.00 | 0.811030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371265E+10 | 0.00 | 0.00 | 0.00 | 0.292597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.418233E+10 | 0.00 | 0.00 | 0.00 | 0.115590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.410658E+10 | 0.00 | 0.00 | 0.00 | 0.291520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371839E+10 | 0.00 | 0.00 | 0.00 | 0.320306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418830E+10 | 0.00 | 0.00 | 0.00 | 0.425067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398399E+10 | 0.00 | 0.00 | 0.00 | 0.538874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.414744E+10 | 0.00 | 0.00 | 0.00 | 0.778430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.404528E+10 | 0.00 | 0.00 | 0.00 | 0.915107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.408663E+10 | 0.00 | 0.00 | 0.00 | 0.109022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.419054E+10 | 0.00 | 0.00 | 0.00 | 0.116309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.398451E+10 | 0.00 | 0.00 | 0.00 | 0.943787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410658E+10 | 0.00 | 0.00 | 0.00 | 0.752888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.398399E+10 | 0.00 | 0.00 | 0.00 | 0.549900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408615E+10 | 0.00 | 0.00 | 0.00 | 0.377803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486284E+11 | 0.00 | 0.00 | 0.00 | 0.814699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371839E+10 | 0.00 | 0.00 | 0.00 | 0.291520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.419054E+10 | 0.00 | 0.00 | 0.00 | 0.116309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.410308E+10 | 0.00 | 0.00 | 0.00 | 0.286663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371523E+10 | 0.00 | 0.00 | 0.00 | 0.316332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418473E+10 | 0.00 | 0.00 | 0.00 | 0.420997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398060E+10 | 0.00 | 0.00 | 0.00 | 0.535556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.414391E+10 | 0.00 | 0.00 | 0.00 | 0.776078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.404184E+10 | 0.00 | 0.00 | 0.00 | 0.912844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.408316E+10 | 0.00 | 0.00 | 0.00 | 0.108902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.418681E+10 | 0.00 | 0.00 | 0.00 | 0.116163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.398113E+10 | 0.00 | 0.00 | 0.00 | 0.941962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410308E+10 | 0.00 | 0.00 | 0.00 | 0.750742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.398060E+10 | 0.00 | 0.00 | 0.00 | 0.547073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408267E+10 | 0.00 | 0.00 | 0.00 | 0.373706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485868E+11 | 0.00 | 0.00 | 0.00 | 0.811260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371523E+10 | 0.00 | 0.00 | 0.00 | 0.286663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.418681E+10 | 0.00 | 0.00 | 0.00 | 0.116163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.669964E+10 | 0.00 | 0.00 | 0.00 | 0.513090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.606760E+10 | 0.00 | 0.00 | 0.00 | 0.574001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.684411E+10 | 0.00 | 0.00 | 0.00 | 0.777210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.650100E+10 | 0.00 | 0.00 | 0.00 | 0.997300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.677187E+10 | 0.00 | 0.00 | 0.00 | 0.146310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.660935E+10 | 0.00 | 0.00 | 0.00 | 0.172422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.666449E+10 | 0.00 | 0.00 | 0.00 | 0.205195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.684765E+10 | 0.00 | 0.00 | 0.00 | 0.220140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.650267E+10 | 0.00 | 0.00 | 0.00 | 0.177979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.669964E+10 | 0.00 | 0.00 | 0.00 | 0.140947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.650100E+10 | 0.00 | 0.00 | 0.00 | 0.101877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.666352E+10 | 0.00 | 0.00 | 0.00 | 0.678773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793725E+11 | 0.00 | 0.00 | 0.00 | 0.151891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.606760E+10 | 0.00 | 0.00 | 0.00 | 0.513090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.684765E+10 | 0.00 | 0.00 | 0.00 | 0.220140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.360803E+10 | 0.00 | 0.00 | 0.00 | 0.258363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326765E+10 | 0.00 | 0.00 | 0.00 | 0.288966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368583E+10 | 0.00 | 0.00 | 0.00 | 0.391526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350105E+10 | 0.00 | 0.00 | 0.00 | 0.503011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.364693E+10 | 0.00 | 0.00 | 0.00 | 0.738502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.355940E+10 | 0.00 | 0.00 | 0.00 | 0.870364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.358857E+10 | 0.00 | 0.00 | 0.00 | 0.103615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.368679E+10 | 0.00 | 0.00 | 0.00 | 0.111063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350148E+10 | 0.00 | 0.00 | 0.00 | 0.898140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360803E+10 | 0.00 | 0.00 | 0.00 | 0.711129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350105E+10 | 0.00 | 0.00 | 0.00 | 0.513947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358857E+10 | 0.00 | 0.00 | 0.00 | 0.342241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.427434E+11 | 0.00 | 0.00 | 0.00 | 0.766296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.326765E+10 | 0.00 | 0.00 | 0.00 | 0.258363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.368679E+10 | 0.00 | 0.00 | 0.00 | 0.111063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.359539E+10 | 0.00 | 0.00 | 0.00 | 0.256083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325620E+10 | 0.00 | 0.00 | 0.00 | 0.286763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.367292E+10 | 0.00 | 0.00 | 0.00 | 0.389000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348879E+10 | 0.00 | 0.00 | 0.00 | 0.500572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.363415E+10 | 0.00 | 0.00 | 0.00 | 0.735773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.354693E+10 | 0.00 | 0.00 | 0.00 | 0.867504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.357601E+10 | 0.00 | 0.00 | 0.00 | 0.103320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.367371E+10 | 0.00 | 0.00 | 0.00 | 0.110751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.348921E+10 | 0.00 | 0.00 | 0.00 | 0.895438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.359539E+10 | 0.00 | 0.00 | 0.00 | 0.708664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348879E+10 | 0.00 | 0.00 | 0.00 | 0.511721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357601E+10 | 0.00 | 0.00 | 0.00 | 0.339992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425935E+11 | 0.00 | 0.00 | 0.00 | 0.763222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325620E+10 | 0.00 | 0.00 | 0.00 | 0.256083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.367371E+10 | 0.00 | 0.00 | 0.00 | 0.110751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.361484E+10 | 0.00 | 0.00 | 0.00 | 0.255393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327382E+10 | 0.00 | 0.00 | 0.00 | 0.286111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369279E+10 | 0.00 | 0.00 | 0.00 | 0.388782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350766E+10 | 0.00 | 0.00 | 0.00 | 0.501813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.365381E+10 | 0.00 | 0.00 | 0.00 | 0.739802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.356612E+10 | 0.00 | 0.00 | 0.00 | 0.872829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.359535E+10 | 0.00 | 0.00 | 0.00 | 0.104033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.369383E+10 | 0.00 | 0.00 | 0.00 | 0.111605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350808E+10 | 0.00 | 0.00 | 0.00 | 0.902001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.361484E+10 | 0.00 | 0.00 | 0.00 | 0.713644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350766E+10 | 0.00 | 0.00 | 0.00 | 0.514499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359535E+10 | 0.00 | 0.00 | 0.00 | 0.340444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428242E+11 | 0.00 | 0.00 | 0.00 | 0.767171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.327382E+10 | 0.00 | 0.00 | 0.00 | 0.255393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.369383E+10 | 0.00 | 0.00 | 0.00 | 0.111605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.407058E+10 | 0.00 | 0.00 | 0.00 | 0.273234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.368656E+10 | 0.00 | 0.00 | 0.00 | 0.304433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415835E+10 | 0.00 | 0.00 | 0.00 | 0.414160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394989E+10 | 0.00 | 0.00 | 0.00 | 0.542046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.411446E+10 | 0.00 | 0.00 | 0.00 | 0.808239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.401617E+10 | 0.00 | 0.00 | 0.00 | 0.955200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.405784E+10 | 0.00 | 0.00 | 0.00 | 0.114316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.417043E+10 | 0.00 | 0.00 | 0.00 | 0.123358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.395405E+10 | 0.00 | 0.00 | 0.00 | 0.993180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.407058E+10 | 0.00 | 0.00 | 0.00 | 0.785552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.394989E+10 | 0.00 | 0.00 | 0.00 | 0.562853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.404863E+10 | 0.00 | 0.00 | 0.00 | 0.366356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482474E+11 | 0.00 | 0.00 | 0.00 | 0.838199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.368656E+10 | 0.00 | 0.00 | 0.00 | 0.273234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.417043E+10 | 0.00 | 0.00 | 0.00 | 0.123358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230968E+09 | 0.115139E+10 | 0.00 | 12258470.81 | 2729636.68 | 0.00 | 0.151647E+10 | 0.00 | 0.57 |
February | 86678745.27 | 0.240023E+10 | 0.00 | 6534106.23 | 4812925.39 | 0.00 | 0.687415E+09 | 0.00 | 0.57 |
March | 48628190.14 | 0.444525E+10 | 0.00 | 4204479.37 | 7869542.98 | 0.00 | 0.384262E+09 | 0.00 | 0.57 |
April | 24496014.66 | 0.953068E+10 | 0.00 | 960946.71 | 30298915.88 | 0.00 | 69827516.32 | 0.00 | 0.57 |
May | 715176.37 | 0.169035E+11 | 0.00 | 856165.51 | 60897448.20 | 0.00 | 1610748.90 | 0.00 | 0.57 |
June | 431309.14 | 0.237918E+11 | 0.00 | 280337.80 | 70535328.57 | 0.00 | 571224.69 | 0.00 | 0.58 |
July | 0.00 | 0.295071E+11 | 0.00 | 223355.69 | 40880615.55 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.314674E+11 | 0.00 | 0.00 | 46466941.39 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 7304.69 | 0.261353E+11 | 0.00 | 180378.37 | 68832516.28 | 0.00 | 108211.85 | 0.00 | 0.58 |
October | 1528889.47 | 0.175922E+11 | 0.00 | 795775.03 | 0.103567E+09 | 0.00 | 6916156.95 | 0.00 | 0.57 |
November | 2824986.03 | 0.965673E+10 | 0.00 | 610340.10 | 61789197.49 | 0.00 | 5624361.79 | 0.00 | 0.57 |
December | 27018979.68 | 0.368401E+10 | 0.00 | 7150308.05 | 8743046.84 | 0.00 | 0.602920E+09 | 0.00 | 0.57 |
Annual Sum or Average | 0.423298E+09 | 0.176266E+12 | 0.00 | 34054663.69 | 0.507423E+09 | 0.00 | 0.327573E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.115139E+10 | 0.00 | 0.00 | 2729636.68 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.230968E+09 | 0.314674E+11 | 0.00 | 12258470.81 | 0.103567E+09 | 0.00 | 0.151647E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 62270635.43 | 0.576384E+09 | 0.00 | 6379507.88 | 2904346.38 | 0.00 | 0.495648E+09 | 0.00 | 0.46 |
February | 9840963.32 | 0.112446E+10 | 0.00 | 3135892.13 | 6331901.21 | 0.00 | 0.190283E+09 | 0.00 | 0.46 |
March | 7687098.67 | 0.200713E+10 | 0.00 | 1950890.77 | 8526450.31 | 0.00 | 98271491.99 | 0.00 | 0.47 |
April | 5126406.15 | 0.415953E+10 | 0.00 | 369960.92 | 26276040.05 | 0.00 | 10620508.56 | 0.00 | 0.48 |
May | 0.00 | 0.756263E+10 | 0.00 | 181644.20 | 28653265.03 | 0.00 | 53343.08 | 0.00 | 0.51 |
June | 0.00 | 0.109599E+11 | 0.00 | 84606.81 | 26705550.62 | 0.00 | 8633.10 | 0.00 | 0.53 |
July | 0.00 | 0.139798E+11 | 0.00 | 31708.00 | 32850813.67 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.150056E+11 | 0.00 | 0.00 | 34608154.03 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.121384E+11 | 0.00 | 15072.54 | 33354670.85 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 45286.01 | 0.792552E+10 | 0.00 | 150835.02 | 49094093.05 | 0.00 | 761641.51 | 0.00 | 0.50 |
November | 237947.06 | 0.433279E+10 | 0.00 | 113835.85 | 47888743.46 | 0.00 | 471681.38 | 0.00 | 0.48 |
December | 3997230.25 | 0.170496E+10 | 0.00 | 3446908.24 | 11110539.11 | 0.00 | 0.141065E+09 | 0.00 | 0.46 |
Annual Sum or Average | 89205566.90 | 0.814771E+11 | 0.00 | 15860862.36 | 0.308305E+09 | 0.00 | 0.937183E+09 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.576384E+09 | 0.00 | 0.00 | 2904346.38 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 62270635.43 | 0.150056E+11 | 0.00 | 6379507.88 | 49094093.05 | 0.00 | 0.495648E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207006E+09 | 0.489218E+09 | 0.00 | 4029231.83 | 9246993.24 | 0.00 | 0.638136E+09 | 0.00 | 0.45 |
February | 81711076.86 | 0.919701E+09 | 0.00 | 2190333.81 | 39600695.49 | 0.00 | 0.333645E+09 | 0.00 | 0.46 |
March | 60783986.71 | 0.166337E+10 | 0.00 | 1663523.20 | 81620044.34 | 0.00 | 0.228360E+09 | 0.00 | 0.47 |
April | 21090471.14 | 0.325597E+10 | 0.00 | 1057197.80 | 0.212030E+09 | 0.00 | 82338706.57 | 0.00 | 0.46 |
May | 3854985.10 | 0.586920E+10 | 0.00 | 1258360.87 | 0.373583E+09 | 0.00 | 9185572.94 | 0.00 | 0.46 |
June | 132264.80 | 0.829553E+10 | 0.00 | 732087.51 | 0.565992E+09 | 0.00 | 2274237.71 | 0.00 | 0.47 |
July | 162044.89 | 0.105711E+11 | 0.00 | 448824.72 | 0.604613E+09 | 0.00 | 1708293.95 | 0.00 | 0.46 |
August | 0.00 | 0.115456E+11 | 0.00 | 84666.00 | 0.702729E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 103277.64 | 0.898551E+10 | 0.00 | 813604.14 | 0.622666E+09 | 0.00 | 2255959.11 | 0.00 | 0.46 |
October | 1620202.56 | 0.615598E+10 | 0.00 | 633877.69 | 0.413859E+09 | 0.00 | 8219163.03 | 0.00 | 0.46 |
November | 6130727.00 | 0.361355E+10 | 0.00 | 679623.58 | 0.198981E+09 | 0.00 | 15976442.64 | 0.00 | 0.46 |
December | 53902457.38 | 0.135042E+10 | 0.00 | 2125988.60 | 67143820.73 | 0.00 | 0.287548E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.436498E+09 | 0.627152E+11 | 0.00 | 15717319.75 | 0.389206E+10 | 0.00 | 0.160965E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.489218E+09 | 0.00 | 84666.00 | 9246993.24 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.207006E+09 | 0.115456E+11 | 0.00 | 4029231.83 | 0.702729E+09 | 0.00 | 0.638136E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212380E+09 | 0.488054E+09 | 0.00 | 3995652.38 | 9209619.75 | 0.00 | 0.633802E+09 | 0.00 | 0.45 |
February | 91012536.60 | 0.919391E+09 | 0.00 | 2183260.23 | 39577686.06 | 0.00 | 0.325229E+09 | 0.00 | 0.46 |
March | 63694130.94 | 0.166478E+10 | 0.00 | 1671499.66 | 81617808.48 | 0.00 | 0.225405E+09 | 0.00 | 0.47 |
April | 20859211.93 | 0.326048E+10 | 0.00 | 1089065.17 | 0.212253E+09 | 0.00 | 81978354.25 | 0.00 | 0.46 |
May | 3927300.20 | 0.588132E+10 | 0.00 | 1318489.53 | 0.372554E+09 | 0.00 | 8883102.81 | 0.00 | 0.46 |
June | 140432.69 | 0.831577E+10 | 0.00 | 772934.73 | 0.561788E+09 | 0.00 | 2214965.91 | 0.00 | 0.47 |
July | 158882.20 | 0.105992E+11 | 0.00 | 474127.54 | 0.597538E+09 | 0.00 | 1662258.81 | 0.00 | 0.46 |
August | 0.00 | 0.115842E+11 | 0.00 | 87664.92 | 0.687111E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 101868.25 | 0.900807E+10 | 0.00 | 868606.84 | 0.619929E+09 | 0.00 | 2160828.18 | 0.00 | 0.46 |
October | 1593933.59 | 0.617664E+10 | 0.00 | 661236.82 | 0.407728E+09 | 0.00 | 7955998.38 | 0.00 | 0.46 |
November | 6150238.04 | 0.362057E+10 | 0.00 | 702661.49 | 0.198076E+09 | 0.00 | 15829108.44 | 0.00 | 0.46 |
December | 55847330.55 | 0.135074E+10 | 0.00 | 2124133.89 | 67107527.69 | 0.00 | 0.286014E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.455866E+09 | 0.628693E+11 | 0.00 | 15949333.20 | 0.385449E+10 | 0.00 | 0.159113E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.488054E+09 | 0.00 | 87664.92 | 9209619.75 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.212380E+09 | 0.115842E+11 | 0.00 | 3995652.38 | 0.687111E+09 | 0.00 | 0.633802E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239543E+09 | 0.481367E+09 | 0.00 | 3882706.28 | 9093255.02 | 0.00 | 0.612237E+09 | 0.00 | 0.45 |
February | 98687738.98 | 0.911183E+09 | 0.00 | 2131661.35 | 39347933.42 | 0.00 | 0.322356E+09 | 0.00 | 0.46 |
March | 72784510.19 | 0.165664E+10 | 0.00 | 1619834.90 | 81349476.44 | 0.00 | 0.219305E+09 | 0.00 | 0.47 |
April | 21186713.99 | 0.325220E+10 | 0.00 | 1043465.46 | 0.212116E+09 | 0.00 | 83239583.22 | 0.00 | 0.46 |
May | 3940054.68 | 0.587701E+10 | 0.00 | 1296555.78 | 0.372964E+09 | 0.00 | 8941754.51 | 0.00 | 0.46 |
June | 140405.71 | 0.830662E+10 | 0.00 | 760411.73 | 0.566175E+09 | 0.00 | 2255272.59 | 0.00 | 0.47 |
July | 159648.57 | 0.105918E+11 | 0.00 | 475293.00 | 0.603540E+09 | 0.00 | 1657482.09 | 0.00 | 0.46 |
August | 0.00 | 0.115786E+11 | 0.00 | 87479.01 | 0.690352E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 102621.05 | 0.900185E+10 | 0.00 | 869443.01 | 0.621345E+09 | 0.00 | 2195037.22 | 0.00 | 0.46 |
October | 1613520.39 | 0.616737E+10 | 0.00 | 649108.33 | 0.411428E+09 | 0.00 | 8094909.33 | 0.00 | 0.46 |
November | 6201467.20 | 0.361051E+10 | 0.00 | 681039.17 | 0.198450E+09 | 0.00 | 16092968.52 | 0.00 | 0.46 |
December | 62536250.43 | 0.134029E+10 | 0.00 | 2071574.16 | 66868462.15 | 0.00 | 0.283627E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.506896E+09 | 0.627755E+11 | 0.00 | 15568572.20 | 0.387303E+10 | 0.00 | 0.156000E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.481367E+09 | 0.00 | 87479.01 | 9093255.02 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.239543E+09 | 0.115786E+11 | 0.00 | 3882706.28 | 0.690352E+09 | 0.00 | 0.612237E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.339235E+09 | 0.768790E+09 | 0.00 | 7312972.99 | 11075548.46 | 0.00 | 0.982996E+09 | 0.00 | 0.42 |
February | 0.167419E+09 | 0.165034E+10 | 0.00 | 4059248.13 | 22761542.24 | 0.00 | 0.433073E+09 | 0.00 | 0.42 |
March | 81170493.05 | 0.317683E+10 | 0.00 | 2667631.45 | 39721944.62 | 0.00 | 0.263224E+09 | 0.00 | 0.43 |
April | 25417857.81 | 0.644084E+10 | 0.00 | 988234.76 | 0.156269E+09 | 0.00 | 63566625.94 | 0.00 | 0.42 |
May | 3397891.35 | 0.117234E+11 | 0.00 | 1441427.56 | 0.213488E+09 | 0.00 | 4940176.08 | 0.00 | 0.43 |
June | 163646.14 | 0.164750E+11 | 0.00 | 578672.32 | 0.270162E+09 | 0.00 | 445327.32 | 0.00 | 0.44 |
July | 77281.49 | 0.205951E+11 | 0.00 | 613126.59 | 0.285266E+09 | 0.00 | 419796.60 | 0.00 | 0.43 |
August | 0.00 | 0.227771E+11 | 0.00 | 0.00 | 0.235397E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 62672.78 | 0.178401E+11 | 0.00 | 1040642.84 | 0.350067E+09 | 0.00 | 195147.48 | 0.00 | 0.43 |
October | 3531701.61 | 0.120105E+11 | 0.00 | 1069025.19 | 0.298456E+09 | 0.00 | 13681649.85 | 0.00 | 0.42 |
November | 3751597.32 | 0.709944E+10 | 0.00 | 632935.38 | 0.129030E+09 | 0.00 | 5396696.36 | 0.00 | 0.42 |
December | 73705006.49 | 0.247948E+10 | 0.00 | 4082509.81 | 58251453.19 | 0.00 | 0.364596E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.697933E+09 | 0.123037E+12 | 0.00 | 24486427.03 | 0.206994E+10 | 0.00 | 0.213253E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.768790E+09 | 0.00 | 0.00 | 11075548.46 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.339235E+09 | 0.227771E+11 | 0.00 | 7312972.99 | 0.350067E+09 | 0.00 | 0.982996E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189479E+09 | 0.382132E+09 | 0.00 | 3641220.13 | 5309440.59 | 0.00 | 0.467334E+09 | 0.00 | 0.42 |
February | 90295722.98 | 0.823815E+09 | 0.00 | 2010783.99 | 11234329.44 | 0.00 | 0.208965E+09 | 0.00 | 0.42 |
March | 52581008.07 | 0.158731E+10 | 0.00 | 1307976.76 | 19422227.44 | 0.00 | 0.118822E+09 | 0.00 | 0.43 |
April | 12589525.96 | 0.321986E+10 | 0.00 | 476115.42 | 75836746.32 | 0.00 | 31492602.16 | 0.00 | 0.42 |
May | 752471.23 | 0.587730E+10 | 0.00 | 674734.10 | 90582573.51 | 0.00 | 3443592.15 | 0.00 | 0.43 |
June | 69893.91 | 0.823296E+10 | 0.00 | 273151.06 | 0.135391E+09 | 0.00 | 211459.25 | 0.00 | 0.44 |
July | 46509.19 | 0.102696E+11 | 0.00 | 289851.09 | 0.162606E+09 | 0.00 | 230356.27 | 0.00 | 0.43 |
August | 0.00 | 0.113578E+11 | 0.00 | 2961.78 | 0.136194E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 19214.07 | 0.891712E+10 | 0.00 | 520415.00 | 0.166911E+09 | 0.00 | 103896.52 | 0.00 | 0.43 |
October | 1107544.81 | 0.601337E+10 | 0.00 | 516608.59 | 0.138590E+09 | 0.00 | 7362160.86 | 0.00 | 0.42 |
November | 1611336.32 | 0.355003E+10 | 0.00 | 295960.76 | 59720483.08 | 0.00 | 2968097.65 | 0.00 | 0.42 |
December | 47455446.12 | 0.123633E+10 | 0.00 | 2017545.13 | 28173969.90 | 0.00 | 0.170490E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.396007E+09 | 0.614676E+11 | 0.00 | 12027323.82 | 0.102997E+10 | 0.00 | 0.101142E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.382132E+09 | 0.00 | 2961.78 | 5309440.59 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.189479E+09 | 0.113578E+11 | 0.00 | 3641220.13 | 0.166911E+09 | 0.00 | 0.467334E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193346E+09 | 0.378773E+09 | 0.00 | 3598474.65 | 5289946.45 | 0.00 | 0.465647E+09 | 0.00 | 0.42 |
February | 90300095.91 | 0.819324E+09 | 0.00 | 1982979.77 | 11214945.18 | 0.00 | 0.210978E+09 | 0.00 | 0.42 |
March | 56835126.35 | 0.158242E+10 | 0.00 | 1285170.18 | 19389990.88 | 0.00 | 0.115871E+09 | 0.00 | 0.43 |
April | 12673217.85 | 0.321436E+10 | 0.00 | 463939.93 | 75771655.83 | 0.00 | 31845953.30 | 0.00 | 0.42 |
May | 757005.50 | 0.587241E+10 | 0.00 | 667388.83 | 90536768.01 | 0.00 | 3460316.26 | 0.00 | 0.43 |
June | 71264.79 | 0.822411E+10 | 0.00 | 271196.69 | 0.137726E+09 | 0.00 | 218885.19 | 0.00 | 0.44 |
July | 46620.94 | 0.102610E+11 | 0.00 | 289546.48 | 0.164690E+09 | 0.00 | 231340.82 | 0.00 | 0.43 |
August | 0.00 | 0.113506E+11 | 0.00 | 2973.42 | 0.136268E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 19762.62 | 0.890998E+10 | 0.00 | 520187.33 | 0.167157E+09 | 0.00 | 105366.99 | 0.00 | 0.43 |
October | 1116579.85 | 0.600692E+10 | 0.00 | 511889.82 | 0.139323E+09 | 0.00 | 7404430.52 | 0.00 | 0.42 |
November | 1624644.06 | 0.354339E+10 | 0.00 | 289779.71 | 60178655.22 | 0.00 | 2999630.20 | 0.00 | 0.42 |
December | 51668956.20 | 0.123077E+10 | 0.00 | 1995870.97 | 28087005.75 | 0.00 | 0.167974E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.408460E+09 | 0.613941E+11 | 0.00 | 11879397.77 | 0.103563E+10 | 0.00 | 0.100674E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.378773E+09 | 0.00 | 2973.42 | 5289946.45 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.193346E+09 | 0.113506E+11 | 0.00 | 3598474.65 | 0.167157E+09 | 0.00 | 0.465647E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195230E+09 | 0.377456E+09 | 0.00 | 3553068.82 | 5286697.22 | 0.00 | 0.464889E+09 | 0.00 | 0.42 |
February | 93545984.54 | 0.817001E+09 | 0.00 | 1963535.33 | 11184392.89 | 0.00 | 0.209623E+09 | 0.00 | 0.42 |
March | 61598559.18 | 0.158059E+10 | 0.00 | 1259210.83 | 19365424.07 | 0.00 | 0.112578E+09 | 0.00 | 0.43 |
April | 12719559.37 | 0.321433E+10 | 0.00 | 453298.16 | 75731493.12 | 0.00 | 32078276.13 | 0.00 | 0.42 |
May | 753891.15 | 0.587950E+10 | 0.00 | 674282.45 | 89972353.35 | 0.00 | 3439794.60 | 0.00 | 0.43 |
June | 69227.28 | 0.823856E+10 | 0.00 | 275441.69 | 0.135905E+09 | 0.00 | 207350.75 | 0.00 | 0.44 |
July | 32222.59 | 0.102823E+11 | 0.00 | 297914.26 | 0.160818E+09 | 0.00 | 237338.55 | 0.00 | 0.43 |
August | 0.00 | 0.113766E+11 | 0.00 | 4217.68 | 0.132849E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 18556.19 | 0.893166E+10 | 0.00 | 530509.73 | 0.164209E+09 | 0.00 | 101884.72 | 0.00 | 0.43 |
October | 1061983.31 | 0.602127E+10 | 0.00 | 523093.95 | 0.137954E+09 | 0.00 | 7376107.32 | 0.00 | 0.42 |
November | 1621036.49 | 0.355071E+10 | 0.00 | 292776.62 | 59578057.67 | 0.00 | 2988925.00 | 0.00 | 0.42 |
December | 55161642.69 | 0.123071E+10 | 0.00 | 1981841.93 | 28100455.67 | 0.00 | 0.165181E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.421813E+09 | 0.615007E+11 | 0.00 | 11809191.43 | 0.102095E+10 | 0.00 | 0.998702E+09 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.377456E+09 | 0.00 | 4217.68 | 5286697.22 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.195230E+09 | 0.113766E+11 | 0.00 | 3553068.82 | 0.164209E+09 | 0.00 | 0.464889E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211696E+09 | 0.381637E+09 | 0.00 | 3611642.76 | 4497618.34 | 0.00 | 0.453408E+09 | 0.00 | 0.42 |
February | 0.108636E+09 | 0.805091E+09 | 0.00 | 2033600.30 | 9169298.03 | 0.00 | 0.207461E+09 | 0.00 | 0.42 |
March | 81420502.45 | 0.156396E+10 | 0.00 | 1241125.59 | 16840944.99 | 0.00 | 0.106505E+09 | 0.00 | 0.43 |
April | 19549405.50 | 0.319032E+10 | 0.00 | 433222.82 | 69794678.50 | 0.00 | 35858950.26 | 0.00 | 0.42 |
May | 775013.04 | 0.587699E+10 | 0.00 | 964352.83 | 78169745.96 | 0.00 | 4362677.31 | 0.00 | 0.43 |
June | 171047.06 | 0.828106E+10 | 0.00 | 464877.76 | 0.100578E+09 | 0.00 | 840703.90 | 0.00 | 0.44 |
July | 30373.54 | 0.103636E+11 | 0.00 | 502804.38 | 0.119573E+09 | 0.00 | 60768.04 | 0.00 | 0.43 |
August | 0.00 | 0.114998E+11 | 0.00 | 101322.55 | 85319165.17 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 52354.95 | 0.901549E+10 | 0.00 | 823868.22 | 0.132820E+09 | 0.00 | 241762.72 | 0.00 | 0.43 |
October | 1262419.19 | 0.606401E+10 | 0.00 | 707408.34 | 0.107364E+09 | 0.00 | 9628110.77 | 0.00 | 0.42 |
November | 2283236.15 | 0.357363E+10 | 0.00 | 375690.20 | 45051769.84 | 0.00 | 4615081.26 | 0.00 | 0.42 |
December | 68008464.10 | 0.123595E+10 | 0.00 | 2082858.30 | 27066499.28 | 0.00 | 0.159523E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.493885E+09 | 0.618516E+11 | 0.00 | 13342774.05 | 0.796245E+09 | 0.00 | 0.982505E+09 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.381637E+09 | 0.00 | 101322.55 | 4497618.34 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.211696E+09 | 0.114998E+11 | 0.00 | 3611642.76 | 0.132820E+09 | 0.00 | 0.453408E+09 | 0.00 | 0.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.206457E+12 | -273273247.1 | 0.00 | 0.282048E+11 | 0.158394E+12 |
February | 0.236674E+12 | -0.550044E+10 | 0.00 | 0.709525E+10 | 0.173346E+12 |
March | 0.308236E+12 | -0.124417E+11 | 0.00 | -0.966526E+10 | 0.227126E+12 |
April | 0.342942E+12 | -0.266549E+11 | 0.00 | -0.492319E+11 | 0.286981E+12 |
May | 0.379388E+12 | -0.447364E+11 | 0.00 | -0.111985E+12 | 0.404207E+12 |
June | 0.374617E+12 | -0.605317E+11 | 0.00 | -0.165111E+12 | 0.475247E+12 |
July | 0.374732E+12 | -0.760094E+11 | 0.00 | -0.215698E+12 | 0.558609E+12 |
August | 0.357332E+12 | -0.815643E+11 | 0.00 | -0.231020E+12 | 0.595113E+12 |
September | 0.303674E+12 | -0.661423E+11 | 0.00 | -0.178631E+12 | 0.500949E+12 |
October | 0.250032E+12 | -0.440186E+11 | 0.00 | -0.121971E+12 | 0.408409E+12 |
November | 0.191555E+12 | -0.268740E+11 | 0.00 | -0.557144E+11 | 0.301246E+12 |
December | 0.179984E+12 | -0.980370E+10 | 0.00 | 0.108972E+10 | 0.207420E+12 |
Annual Sum or Average | 0.350562E+13 | -0.454551E+12 | 0.00 | -0.110264E+13 | 0.429705E+13 |
Minimum of Months | 0.179984E+12 | -0.815643E+11 | 0.00 | -0.231020E+12 | 0.158394E+12 |
Maximum of Months | 0.379388E+12 | -273273247.1 | 0.00 | 0.282048E+11 | 0.595113E+12 |