Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2024-07-03 12:20:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1610.91 | 333.17 | 333.17 |
Net Site Energy | 1538.95 | 318.29 | 318.29 |
Total Source Energy | 2415.39 | 499.55 | 499.55 |
Net Source Energy | 2187.50 | 452.42 | 452.42 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1289.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 100.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 43.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 321.25 | 1289.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1289.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 100.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 43.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 26.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1289.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 0.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 100.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 43.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 26.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 8.34 | 266.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 66.44 | 266.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 8.34 | 266.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 66.44 | 266.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 75.796 | 23.59 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -3.84 | -1.2 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 71.958 | 22.40 |
Electricity Coming From Utility | 258.296 | 80.40 |
Surplus Electricity Going To Utility | 9.006 | 2.80 |
Net Electricity From Utility | 249.291 | 77.60 |
Total On-Site and Utility Electric Sources | 321.249 | 100.00 |
Total Electricity End Uses | 321.249 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 105.50 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2908.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.1633 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.1633 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3473 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 12-JAN-15:30 | 28-FEB-17:49 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 195631.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8036.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2229.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1693.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25764.22 | 195631.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 195631.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8036.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 3768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2229.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1693.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1397.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 319.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 137.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 83.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 42.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1017.40 | 1397.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 289.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 66.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 28.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 210.42 | 289.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 289.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 66.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 28.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 210.42 | 289.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.837650 |
ZONE2 FINE STORAGE DIRECT AIR | 1.22 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.49 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.49 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 100200.39 |
PSZ-OFFICE HEATING COIL | 26576.37 |
PSZ-FINE STORAGE HEATING COIL | 64705.37 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 100200.38 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.837650 | 0.837650 | 0.837650 | 0.837650 | 0.837650 | 0.837650 | 1.00 | 1.000000 | 0.837650 |
PSZ-FINE STORAGE | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.00 | 1.000000 | 1.22 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.837650 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.22 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.837650 | 927.41 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.22 | 1355.20 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.837650 | 0.837650 | 0.837650 | 0.837650 | 13866.08 | 26576.37 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.22 | 1.22 | 1.22 | 0.807860 | 22687.49 | 64705.37 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.837650 | 0.418825 | 0.558433 | 13866.08 | 6933.04 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 1.22 | 0.612015 | 0.816020 | 22687.49 | 11343.75 | 0.800350 | 0.800350 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.163 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.237 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1459.960 | 6.163 | 114.518 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1459.960 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1507 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.2656 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.3953 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1131 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.4686E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.3953 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.636 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 3.666 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.431 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.764 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.26 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.431 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.68857323E-13 | 0.53233684E-18 | 0.39256197E-18 | 0.0000000 |
2 | 1 | -5.2161015 | 0.66198115E-04 | -0.10631122E-03 | 0.13200917E-13 |
3 | 0 | 5.3667923 | 0.15062465 | 0.15079716 | |
4 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
5 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
6 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
7 | 4 | 0.82647311E-12 | -0.58150351E-16 | 0.17257441E-13 | -0.56565897E-18 |
8 | 3 | -0.39941507E-03 | 0.18976481E-06 | -0.58082735E-04 | 0.15844951E-12 |
9 | 2 | 1.7741008 | 0.40853436E-02 | 1.1667447 | -0.76574997E-04 |
10 | 1 | -7.0836217 | 0.10481985 | -17.265563 | 0.34004097 |
11 | 0 | 5.4852248 | 0.66399090E-01 | 16.274181 | |
12 | 4 | 0.79936253E-12 | 0.91184990E-16 | -0.20402017E-14 | 0.11337666E-15 |
13 | 3 | -0.39068608E-03 | 0.27956711E-06 | -0.56729907E-04 | 0.15337474E-12 |
14 | 2 | 1.7536362 | 0.60734726E-02 | 1.1511739 | -0.74901239E-04 |
15 | 1 | -7.1101691 | 0.15671991 | -17.166525 | 0.33610966 |
16 | 0 | 5.6193701 | 0.99652939E-01 | 16.277855 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.37649694E-08 | -0.38100788E-14 | 0.10290045E-14 | -0.35615536E-16 |
55 | 6 | 0.33493986E-05 | 0.21644755E-08 | 0.31966043E-02 | -0.26815795E-04 |
56 | 5 | -0.23076027E-03 | 0.12783299E-05 | -0.22410729 | 0.19595283E-02 |
57 | 4 | 0.52416495E-02 | 0.58114224E-04 | 4.8359191 | -0.45326248E-01 |
58 | 3 | -0.45819541E-01 | 0.46156737E-03 | -38.057416 | 0.39905167 |
59 | 2 | 0.16240161 | 0.76708217E-03 | 116.55401 | -1.4188764 |
60 | 1 | -0.23421267 | 0.23331839E-03 | -143.94855 | 2.0497178 |
61 | 0 | 0.11414341 | 0.56746991E-05 | 60.838472 | |
62 | 7 | -0.91484681E-08 | 0.56263811E-15 | -0.30200569E-14 | 0.24533578E-16 |
63 | 6 | 0.19425951E-05 | 0.91955099E-09 | 0.32017440E-02 | -0.26858912E-04 |
64 | 5 | -0.10849969E-03 | 0.53618193E-06 | -0.22439914 | 0.19621045E-02 |
65 | 4 | 0.22868027E-02 | 0.24209771E-04 | 4.8407749 | -0.45372930E-01 |
66 | 3 | -0.19407984E-01 | 0.19121198E-03 | -38.084820 | 0.39935462 |
67 | 2 | 0.67952963E-01 | 0.31605674E-03 | 116.60731 | -1.4195894 |
68 | 1 | -0.97452405E-01 | 0.95496718E-04 | -143.97991 | 2.0502333 |
69 | 0 | 0.47357000E-01 | 0.22976438E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20402017E-14 | 0.91184990E-16 | 0.79936253E-12 | 0.11337666E-15 |
85 | 3 | -0.56729907E-04 | 0.27956711E-06 | -0.39068608E-03 | 0.15337474E-12 |
86 | 2 | 1.1511739 | 0.60734726E-02 | 1.7536362 | -0.74901239E-04 |
87 | 1 | -17.166525 | 0.15671991 | -7.1101691 | 0.33610966 |
88 | 0 | 16.277855 | 0.99652939E-01 | 5.6193701 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.262_SHGC_SOUTH_0.399 | 34 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
2 | NONRESWINDOW_U_0.262_SHGC_NORTH_0.399 | 35 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
3 | NONRESWINDOW_U_0.262_SHGC_EAST_0.399 | 36 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
4 | NONRESWINDOW_U_0.262_SHGC_WEST_0.399 | 37 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
5 | SKYLIGHT_U_0.41_SHGC_0.55 | 38 | 1 | VerySmooth | 2.330 | 2.330 | 1.000 | 0.551 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.555 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 3.14065E-002 | 0.47116 | 0.33556 | 0.33556 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.12199 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.553 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 3.833E-002 | 1.618E-004 | 2.498E-004 | 0.137 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.195 | 1.399E-004 | 8.913E-005 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 1.767 | 5.514E-004 | 3.602E-004 | 0.180 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4173E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0766E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8710E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9714E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9073E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0026E-003 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2553E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0764E-003 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1348E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8955E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0972E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1634E-003 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4574E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2310E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4733E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4434E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2123E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4422E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5499E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9543E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3279E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6327E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5713E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0429E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6460E-004 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4759E-004 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5512E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1556E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0753E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1965E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 6.5215E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.9469E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.9682E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.1422E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.8752E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.0861E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1311E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.4677E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 8.0903E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 7.9932E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.5308E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.8969E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.1674E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.5670E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.4069E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.2078E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 7.3845E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 5.2510E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.8844E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.2617E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.8058E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9100E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9330E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.3345E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 8.3077E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.2799E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.3977E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.2782E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1835E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8921E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.9329E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3345E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 8352.86730 | 10023.44076 | 0.69804 | 0.83765 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 25.97200 | 7.00497E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9861.35928 | 11833.63113 | 0.28114 | 0.33737 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 15658.19253 | 18789.83104 | 1.02003 | 1.22403 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 26.89000 | 7.00637E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 27471.39889 | 32965.67867 | 0.65987 | 0.79184 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 27.19600 | 7.00683E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 83500.31959 | 100200.38350 | 2.07248 | 2.48697 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 12125.61 | 0.83765 | 0.83765 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15284.76 | 0.33737 | 0.33737 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 21623.53 | 1.22403 | 1.22403 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 52122.83 | 0.79184 | 0.79184 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83765 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22403 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.48697 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.48697 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 100200.38714 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 100200.38350 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.83765 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.83765 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.83765 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.83765 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.83765 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.83765 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22403 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22403 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22403 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22403 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22403 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.22403 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.83765 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.22403 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.83765 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.83765 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 927.41113 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.83765 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.83765 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.83765 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83765 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.83765 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.41882 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.55843 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 13866.08000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6933.04000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13866.08000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26576.37027 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26576.37027 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22403 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22403 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1355.19617 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22403 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22403 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22403 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80786 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22403 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61202 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.81602 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22687.49000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11343.74500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80035 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80035 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22687.49000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 64705.37407 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 64705.37407 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 13216.1 | 11.46 | 11.20 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 21737.3 | 11.68 | 11.41 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3566559481 | 0.3044103465 | Pass | Pass | 2.4211761976 | 8.1682729662 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5976854152 | 0.5422516903 | Pass | Pass | 0.7873781197 | 0.6718238835 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.5561481497E-005 | 2.2969509463E-005 | Pass | Pass | 2.5421931276E-002 | 2.4491218158E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4975.58 | 454.53 | 0.00 | 143.14 | 235.74 | 5809.02 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.255 | 0.266 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.255 | 0.266 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.111 | 0.113 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.255 | 0.266 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.255 | 0.266 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.255 | 0.266 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.255 | 0.266 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.255 | 0.266 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.047 | 0.047 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.148 | 0.151 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.395 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.395 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.373 | 0.395 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.054 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.210 | 0.216 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.361 | 0.395 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.361 | 0.395 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.262_SHGC_WEST_0.399 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.488 | 0.400 | 0.440 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.262_SHGC_WEST_0.399 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.488 | 0.400 | 0.440 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.262_SHGC_NORTH_0.399 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.488 | 0.400 | 0.440 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.262_SHGC_NORTH_0.399 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.488 | 0.400 | 0.440 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.756 | 0.471 | 0.491 | |||||||||||||||||
North Total or Average | 6.51 | 1.488 | 0.400 | 0.440 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.073 | 0.489 | 0.504 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.1633 | 236.88 | 1459.96 | LightsWired | LTG_SCH_OFFICE | 44.65 | 168.00 | 29.72 | 0.0000 | Y | 8.15 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 25.41 | 0.0000 | Y | 44.43 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 25.11 | 0.0000 | Y | 48.30 |
Interior Lighting Total | 4.3473 | 4835.13 | 21019.54 | 100.87 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.12 | 10245.50 | 1188.48 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1459.96 | 423.39 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1459.96 | 146.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 119.03 | AstronomicalClock | - | 44.84 | 44.84 | 1.00 | |
EXTERIOR_LIGHTS_B | 2955.82 | AstronomicalClock | - | 83.06 | 63.95 | 35.48 | |
EXTERIOR_LIGHTS_C | 694.12 | AstronomicalClock | - | 83.06 | 54.03 | 7.04 | |
Exterior Lighting Total | 3768.97 | 43.53 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13866.08 | 11102.02 | 2764.06 | 0.80 | 3.82 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22687.49 | 18157.93 | 4529.56 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 13216.1 | 11.46 | 11.20 | ||||
PSZ-FINE STORAGE COOLING COIL | 21737.3 | 11.68 | 11.41 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 100200.39 | 0.86 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26576.37 | 0.85 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 64705.37 | 0.85 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.49 | 231.07 | 92.91 | 1.00 | 3.45 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.84 | 927.41 | 1107.16 | 1.00 | 1.45 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.22 | 1355.20 | 1107.16 | 1.00 | 1.36 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8352.87 | 10023.44 | 42.31 | 0.698 | 0.838 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00834 | 25.97 | 0.00700 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 15658.19 | 18789.83 | 13.48 | 1.020 | 1.224 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 26.70 | 26.70 | 0.00857 | 26.89 | 0.00701 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 0.00 | 29.43 | 0.00751 | 27.20 | 0.00701 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9861.36 | 11833.63 | 49.96 | 0.281 | 0.337 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00836 | -41.90 | 0.00006 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 27471.40 | 32965.68 | 23.66 | 0.660 | 0.792 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00785 | -41.90 | 0.00006 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 83500.32 | 100200.38 | 31.27 | 2.072 | 2.487 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00752 | -41.90 | 0.00006 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.84 | 0.84 | 0.34 | 0.34 | 0.8376 | 0.8376 | 0.8376 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.22 | 1.22 | 0.79 | 0.79 | 1.2240 | 1.2240 | 1.2240 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 100200.387 | 100200.387 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 100200.39 | 100200.39 | 2.486975 | 10.00 | 9.75 | 0.00751776 | 43.33 | 21.96 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 10.00 | 0.00751776 | 96.9994 | 100200.38 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 13866.080 | 11102.016 | 0.837650 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 6933.04 | 6727.54 | 0.558433 | 25.07 | 16.33 | 0.00817858 | 12.00 | 11.12 | 0.00800000 | 25.97 | 0.00700497 | 15.63 | 18.3164 | 23.90 | 0.00834182 | 44.4867 | 8352.87 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26576.370 | 26576.370 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26576.37 | 26576.37 | 0.837650 | 13.37 | 11.02 | 0.00734355 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 12.2109 | 21.10 | 0.00835602 | 52.8201 | 9861.36 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 22687.490 | 18157.933 | 1.224030 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 11343.75 | 11308.72 | 0.816020 | 27.79 | 17.14 | 0.00802144 | 12.00 | 11.12 | 0.00800000 | 27.20 | 0.00700683 | 16.07 | 52.0467 | 26.70 | 0.00856286 | 38.6460 | 15614.28 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 64705.374 | 64705.374 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 64705.37 | 64705.37 | 1.224031 | -4.38 | -4.38 | 0.00515014 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 34.6978 | 15.56 | 0.00785235 | 70.3359 | 27471.40 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 100200.387 | 100200.387 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.486975 | 2.94815758 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 100200.39 | 100200.39 | 1.0000 | 2.94815758 | 2.486975 | 10.00 | 9.75 | 0.00751776 | 28989.1 | 43.33 | 21.96 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100200.39 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 10.00 | 0.00751776 | 10.00 | 0.00751776 | 96.9994 | 100200.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13866.080 | 11102.016 | 0.837650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0436 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.837650 | 0.99298281 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 6933.04 | 6727.54 | 1.0000 | 0.66198882 | 0.558433 | 25.07 | 16.33 | 0.00817858 | 46024.5 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6933.04 | 25.97 | 0.00700497 | 15.63 | 0.10228463 | 18.3164 | 23.90 | 0.00834182 | 23.90 | 0.00834182 | 44.4867 | 8352.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26576.370 | 26576.370 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.837650 | 0.99298281 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26576.37 | 26576.37 | 1.0000 | 0.99298281 | 0.837650 | 13.37 | 11.02 | 0.00734355 | 31978.1 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26576.37 | -41.90 | 0.00006450 | -41.90 | 0.10228463 | 12.2109 | 21.05 | 0.00835602 | 21.10 | 0.00835602 | 52.8201 | 9861.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22687.490 | 18157.933 | 1.224030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7514 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.224031 | 1.45101396 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 11343.75 | 11308.72 | 1.0000 | 0.96734217 | 0.816020 | 27.79 | 17.14 | 0.00802144 | 48397.9 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11343.75 | 27.20 | 0.00700683 | 16.07 | 0.42471127 | 52.0467 | 26.70 | 0.00856286 | 26.70 | 0.00856286 | 38.6460 | 15614.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 64705.374 | 64705.374 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.224031 | 1.45101396 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 64705.37 | 64705.37 | 1.0000 | 1.45101396 | 1.224031 | -4.38 | -4.38 | 0.00515014 | 8439.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64705.37 | -41.90 | 0.00006450 | -41.90 | 0.42471127 | 34.6978 | 15.56 | 0.00785235 | 15.56 | 0.00785235 | 70.3359 | 27471.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 0.84 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.22 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2617.17 | 3424.50 | 2590.17 |
ZONE2 FINE STORAGE | 2993.17 | 3348.67 | 2785.33 |
ZONE3 BULK STORAGE | 2996.00 | 3471.00 | 2908.50 |
Facility | 3116.33 | 3490.50 | 2908.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 122.83 | 0.50 | 74.33 | 0.50 |
ZONE2 FINE STORAGE | 643.33 | 0.00 | 28.50 | 0.00 |
ZONE3 BULK STORAGE | 80.00 | 0.00 | 24.33 | 0.00 |
Facility | 789.50 | 0.50 | 105.50 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.500 | 0.230 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.433 | 0.066 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.057 | 0.000 | 0.033 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.28 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.04 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1801210.68 | 0.00 | 1801210.68 | 1065268.43 | 2866479.11 | 3225648.14 | 5722.06 | 2462.67 | 575.28 | 0.00 |
ZONE2 FINE STORAGE | 4634063.47 | 0.00 | 4634063.47 | 1962642.38 | 6596705.85 | 13393694.68 | 5730.00 | 3026.83 | 3.17 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 10266576.17 | 10266576.17 | 15959291.73 | 26225867.90 | 30805497.77 | 8651.17 | 10.50 | 98.33 | 4375.33 |
Total Facility | 6435274.15 | 10266576.17 | 16701850.32 | 18987202.54 | 35689052.86 | 47424840.58 | 8717.83 | 3037.00 | 668.44 | 4375.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1376 | 0.0000 | 0.1376 | 0.0636 | 0.2012 | 0.1023 | 598.06 | 2462.67 | 575.28 |
ZONE2 FINE STORAGE | 0.3540 | 0.0000 | 0.3540 | 0.0536 | 0.4077 | 0.4247 | 606.00 | 3026.83 | 3.17 |
ZONE3 BULK STORAGE | 0.0000 | 0.3240 | 0.3240 | 0.5599 | 0.8838 | 0.9768 | 3593.83 | 3.50 | 38.67 |
Total Facility | 0.4916 | 0.3240 | 0.8156 | 0.6771 | 1.4927 | 1.5038 | 3593.83 | 3030.00 | 608.78 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2531180.70 | 0.00 | 2531180.70 | 3225648.14 | 5719.89 | 0.00 | 3040.11 | 0.00 |
PSZ-FINE STORAGE | 6512798.39 | 0.00 | 6512798.39 | 13393694.68 | 5730.00 | 0.00 | 3030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1934 | 0.0000 | 0.1934 | 0.1023 | 595.89 | 0.00 | 3040.11 |
PSZ-FINE STORAGE | 0.4976 | 0.0000 | 0.4976 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2665.03 | 380.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3028.67 | 1.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1998 | 0.4489 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5971 | 1.0373 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 405 |
Defaulted Fields | 323 |
Fields with Defaults | 1052 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 321.25 | 1269.47 | 23-JUL-16:00 | 25764.22 | 12-JAN-15:30 |
Electricity:Building | 237.38 | 1217.09 | 05-MAR-10:20 | 18071.97 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 37.31 | 520.87 | 01-JAN-00:10 | 2598.04 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 237.38 | 1217.09 | 05-MAR-10:20 | 18071.97 | 02-JAN-09:10 |
InteriorLights:Electricity | 100.87 | 747.21 | 05-MAR-10:20 | 8036.80 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 8.15 | 51.00 | 01-JAN-00:10 | 762.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 100.87 | 747.21 | 05-MAR-10:20 | 8036.80 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 100.87 | 747.21 | 05-MAR-10:20 | 8036.80 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 8.15 | 51.00 | 01-JAN-00:10 | 762.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 100.87 | 747.21 | 05-MAR-10:20 | 8036.80 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 155.65 | 396.24 | 05-MAR-10:20 | 12010.22 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 48.30 | 396.24 | 05-MAR-10:20 | 3810.10 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 48.30 | 396.24 | 05-MAR-10:20 | 3810.10 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 26.33 | 0.00 | 22-MAR-17:10 | 2288.12 | 27-FEB-08:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityProduced:Facility | 71.96 | -0.00 | 01-JAN-13:50 | 15887.94 | 01-JUN-12:30 |
ElectricityProduced:Plant | 71.96 | -0.00 | 01-JAN-13:50 | 15887.94 | 01-JUN-12:30 |
Photovoltaic:ElectricityProduced | 75.80 | 0.00 | 01-JAN-00:10 | 16512.46 | 01-JUN-12:30 |
PowerConversion:ElectricityProduced | -3.84 | -624.52 | 01-JUN-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 13.43 | 0.00 | 02-JAN-00:30 | 1857.72 | 12-JAN-12:40 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 258.30 | 0.00 | 05-FEB-11:20 | 25764.22 | 12-JAN-15:30 |
ElectricityPurchased:Plant | 258.30 | 0.00 | 05-FEB-11:20 | 25764.22 | 12-JAN-15:30 |
Cogeneration:ElectricityPurchased | 258.30 | 0.00 | 05-FEB-11:20 | 25764.22 | 12-JAN-15:30 |
General:Cogeneration:ElectricityPurchased | 258.30 | 0.00 | 05-FEB-11:20 | 25764.22 | 12-JAN-15:30 |
ElectricitySurplusSold:Facility | 9.01 | 0.00 | 01-JAN-00:10 | 14562.72 | 21-MAY-13:00 |
ElectricitySurplusSold:Plant | 9.01 | 0.00 | 01-JAN-00:10 | 14562.72 | 21-MAY-13:00 |
Cogeneration:ElectricitySurplusSold | 9.01 | 0.00 | 01-JAN-00:10 | 14562.72 | 21-MAY-13:00 |
General:Cogeneration:ElectricitySurplusSold | 9.01 | 0.00 | 01-JAN-00:10 | 14562.72 | 21-MAY-13:00 |
ElectricityNet:Facility | 249.29 | -14562.72 | 21-MAY-13:00 | 25764.22 | 12-JAN-15:30 |
ElectricityNet:Plant | 249.29 | -14562.72 | 21-MAY-13:00 | 25764.22 | 12-JAN-15:30 |
Cogeneration:ElectricityNet | 249.29 | -14562.72 | 21-MAY-13:00 | 25764.22 | 12-JAN-15:30 |
General:Cogeneration:ElectricityNet | 249.29 | -14562.72 | 21-MAY-13:00 | 25764.22 | 12-JAN-15:30 |
Electricity:HVAC | 26.91 | 0.00 | 22-MAR-17:10 | 3959.76 | 29-JUL-16:00 |
General:Fans:Electricity | 26.33 | 0.00 | 22-MAR-17:10 | 2288.12 | 27-FEB-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 0.58 | 0.00 | 01-JAN-00:10 | 2490.27 | 29-JUL-16:00 |
General:Cooling:Electricity | 0.58 | 0.00 | 01-JAN-00:10 | 2490.27 | 29-JUL-16:00 |
ExteriorLights:Electricity | 43.53 | 0.00 | 01-JAN-11:20 | 3768.97 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 43.53 | 0.00 | 01-JAN-11:20 | 3768.97 | 01-JAN-06:10 |
WaterSystems:Electricity | 13.43 | 0.00 | 02-JAN-00:30 | 1857.72 | 12-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 13.43 | 0.00 | 02-JAN-00:30 | 1857.72 | 12-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1289.66 | 0.00 | 22-MAR-17:10 | 195631.86 | 28-FEB-17:50 |
NaturalGas:HVAC | 1289.66 | 0.00 | 22-MAR-17:10 | 195631.86 | 28-FEB-17:50 |
Heating:NaturalGas | 1289.66 | 0.00 | 22-MAR-17:10 | 195631.86 | 28-FEB-17:50 |
General:Heating:NaturalGas | 1289.66 | 0.00 | 22-MAR-17:10 | 195631.86 | 28-FEB-17:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2047.66 | 0.00 | 22-MAR-17:10 | 305123.11 | 24-FEB-07:10 |
EnergyTransfer:Building | 988.02 | 0.00 | 22-MAR-17:10 | 153537.63 | 24-FEB-07:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 69.00 | 0.00 | 01-JAN-00:40 | 26518.43 | 27-FEB-07:10 |
Heating:EnergyTransfer | 968.61 | 0.00 | 22-MAR-17:10 | 153537.63 | 24-FEB-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 63.43 | 0.00 | 01-JAN-00:40 | 26518.43 | 27-FEB-07:10 |
General:Heating:EnergyTransfer | 968.61 | 0.00 | 22-MAR-17:10 | 153537.63 | 24-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 63.43 | 0.00 | 01-JAN-00:40 | 26518.43 | 27-FEB-07:10 |
Cooling:EnergyTransfer | 19.41 | 0.00 | 01-JAN-00:10 | 9988.55 | 30-AUG-07:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 5.57 | 0.00 | 01-JAN-00:10 | 5572.77 | 14-JUL-05:10 |
General:Cooling:EnergyTransfer | 19.41 | 0.00 | 01-JAN-00:10 | 9988.55 | 30-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 5.57 | 0.00 | 01-JAN-00:10 | 5572.77 | 14-JUL-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 197.81 | 0.00 | 01-JAN-00:40 | 40253.97 | 28-JAN-22:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 183.97 | 0.00 | 01-JAN-00:40 | 40253.97 | 28-JAN-22:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 183.97 | 0.00 | 01-JAN-00:40 | 40253.97 | 28-JAN-22:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 13.84 | 0.00 | 01-JAN-00:10 | 8645.34 | 30-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 13.84 | 0.00 | 01-JAN-00:10 | 8645.34 | 30-AUG-07:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 721.20 | 0.00 | 09-FEB-12:00 | 101017.04 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 721.20 | 0.00 | 09-FEB-12:00 | 101017.04 | 28-JAN-15:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 721.20 | 0.00 | 09-FEB-12:00 | 101017.04 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1059.65 | 0.00 | 22-MAR-17:10 | 163178.29 | 28-FEB-17:50 |
HeatingCoils:EnergyTransfer | 1057.08 | 0.00 | 22-MAR-17:10 | 163178.29 | 28-FEB-17:50 |
CoolingCoils:EnergyTransfer | 2.57 | 0.00 | 01-JAN-00:10 | 10204.88 | 29-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 63.429 | -5.574 | 0.000 | 0.000 | 10.361 | 8.146 | 29.165 | 7.987 | 0.000 | 0.029 | 0.000 | 0.000 | -11.796 | 0.000 | -27.359 | -74.388 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 183.971 | -13.839 | 0.000 | 0.000 | 28.912 | 44.427 | 0.000 | 0.000 | 0.000 | 0.031 | 0.001 | 0.000 | 0.000 | 0.000 | -36.417 | -207.084 |
ZONE3 BULK STORAGE | 721.203 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 73.938 | 48.302 | 107.344 | 75.701 | 0.000 | 2.401 | 0.000 | 0.000 | -115.213 | 0.000 | -370.862 | -542.814 |
Total Facility | 721.203 | 0.000 | 247.400 | -19.412 | 0.000 | 0.000 | 113.211 | 100.874 | 136.508 | 83.688 | 0.000 | 2.461 | 0.001 | 0.000 | -127.010 | 0.000 | -434.638 | -824.286 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-JUL-05:03 | 0.00 | 0.00 | 0.00 | -18931.80 | 0.00 | 0.00 | 92.78 | 51.00 | 550.52 | 348.44 | 0.00 | 0.00 | 18233.63 | 0.00 | -0.00 | 0.00 | -344.56 | 0.00 |
ZONE2 FINE STORAGE | 30-AUG-07:05 | 0.00 | 0.00 | 0.00 | -8753.26 | 0.00 | 0.00 | 2727.13 | 3056.14 | 0.00 | 0.00 | 0.00 | 0.00 | 4822.78 | 0.00 | -0.00 | 0.00 | -1852.79 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-JUL-05:03 | 0.00 | 0.00 | 0.00 | -18931.80 | 0.00 | 0.00 | 911.97 | 764.33 | 2600.55 | 1554.76 | 0.00 | 0.00 | 13444.75 | 0.00 | 0.00 | 0.00 | -344.56 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 05-DEC-06:31 | 0.00 | 0.00 | 28215.55 | 0.00 | 0.00 | 0.00 | 140.10 | 227.91 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1004.24 | 0.00 | -1503.45 | -26626.38 |
ZONE2 FINE STORAGE | 28-JAN-22:42 | 0.00 | 0.00 | 66722.45 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -11708.09 | -55314.33 |
ZONE3 BULK STORAGE | 28-JAN-15:00 | 101015.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8686.76 | 3794.62 | 8200.12 | 0.00 | 0.00 | 0.00 | 22984.81 | 0.00 | -7602.57 | 0.00 | -137079.05 | 0.00 |
Total Facility | 24-FEB-05:22 | 100538.06 | 0.00 | 93564.16 | 0.00 | 0.00 | 0.00 | 0.00 | 799.21 | 2519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10244.67 | 0.00 | -83733.98 | -103442.69 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8376 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.8376 | 0.1221 | 1.0000 | Not calculated | 0.1023 | 0.1221 | ||
PSZ-FINE STORAGE | 1.2240 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.2240 | 0.3470 | 1.0000 | Not calculated | 0.4247 | 0.3470 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8376 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.8376 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1221 | ||
PSZ-FINE STORAGE | 1.2240 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.2240 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.3470 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8376 | 0.8376 | 0.8376 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2240 | 1.2240 | 1.2240 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8376 | 0.8376 | 0.8376 | 0.8376 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.2240 | 1.2240 | 1.2240 | 1.2240 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8376 | 0.8376 | 0.8376 | No | 0.1023 | 0.3032 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2240 | 1.2240 | 1.2240 | No | 0.4247 | 0.5364 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8376 | 0.8376 | 0.8376 | 0.8376 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.2240 | 1.2240 | 1.2240 | 1.2240 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 105.50 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 106.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1289.66 | 195631.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 0.58 | 2490.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 100.87 | 8036.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 43.53 | 3768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 26.33 | 2288.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 13.43 | 1857.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 321.25 |
Natural Gas | 0.00 | 1289.66 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1610.91 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 75.80 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 20.86 |
Space Heating | 0.00 |
Space Cooling | 0.12 |
Fans (All) | 5.45 |
Service Water Heating | 2.78 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 66.44 |
Subtotal | 66.44 |
Natural Gas [MJ/m2] | |
Space Heating | 266.73 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 266.73 |
Subtotal | 266.73 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.26 |
Space Heating | 80.06 |
Space Cooling | 0.04 |
Fans (All) | 1.63 |
Service Water Heating | 0.83 |
Receptacle Equipment | 8.47 |
Miscellaneous | 2.70 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_OFFICE | 2328. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8753.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 6.50 | 0.00 | 0.00 | 0.00 |
Average | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
Sum | 26273.50 | 6.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 82550.00 | 169.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 191193.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 191193.00 | 169.00 | 0.00 | 0.00 | 0.00 |
Average | 102256.67 | 56.33 | 0.00 | 0.00 | 0.00 |
Sum | 306770.00 | 169.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
Min | 8736.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 23.17 | 0.00 | 0.00 | 0.00 |
Average | 8751.22 | 8.78 | 0.00 | 0.00 | 0.00 |
Sum | 26253.67 | 26.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 82133.50 | 585.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 190998.00 | 195.00 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 190998.00 | 585.50 | 0.00 | 0.00 | 0.00 |
Average | 102052.83 | 260.17 | 0.00 | 0.00 | 0.00 |
Sum | 306158.50 | 780.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -14.9 | -15.4 | 0.496996E+09 | 603.25 | 09-JAN-08:09 | -18.9 | -19.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 | -20.7 | 0.457299E+09 | 603.25 | 21-FEB-08:09 | -22.8 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.2 | 0.536756E+09 | 603.25 | 14-MAR-07:10 | -17.1 | -18.0 |
April | 1311630.30 | 137.55 | 28-APR-15:00 | 12.20 | 4.79 | 0.497621E+09 | 651.43 | 22-APR-15:00 | 12.20 | 4.79 |
May | 45122701.44 | 595.74 | 16-MAY-10:20 | 8.53 | 6.41 | 0.542051E+09 | 768.96 | 13-MAY-15:30 | 8.53 | 6.41 |
June | 0.132164E+10 | 3722.61 | 21-JUN-16:00 | 25.60 | 14.20 | 0.643298E+09 | 768.99 | 30-JUN-10:00 | 22.80 | 17.09 |
July | 0.240602E+10 | 18933.52 | 13-JUL-05:03 | 11.52 | 8.37 | 0.631555E+09 | 768.99 | 19-JUL-12:20 | 22.40 | 16.46 |
August | 0.171317E+10 | 15240.25 | 05-AUG-05:03 | 13.98 | 12.01 | 0.666707E+09 | 768.99 | 03-AUG-15:09 | 13.98 | 12.01 |
September | 86360484.10 | 912.68 | 02-SEP-07:10 | 6.78 | 6.01 | 0.509134E+09 | 768.96 | 02-SEP-15:30 | 16.70 | 10.62 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 | 0.497192E+09 | 603.25 | 07-OCT-07:10 | 4.82 | 3.94 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 | -10.9 | 0.477110E+09 | 603.25 | 04-NOV-07:10 | -8.3 | -9.8 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.497055E+09 | 603.25 | 19-DEC-08:09 | -17.7 | -18.1 |
Annual Sum or Average | 0.557363E+10 | 0.645277E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.457299E+09 | 603.25 | -22.8 | -23.1 | ||
Maximum of Months | 0.240602E+10 | 18933.52 | 25.60 | 14.20 | 0.666707E+09 | 768.99 | 22.80 | 17.09 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -14.9 | -15.4 | 0.649309E+09 | 787.42 | 19-JAN-11:09 | -7.1 | -7.8 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 | -20.7 | 0.597369E+09 | 787.42 | 09-FEB-10:30 | -3.9 | -3.9 |
March | 0.154123E+09 | 4540.52 | 22-MAR-14:50 | 5.60 | 2.17 | 0.701306E+09 | 789.44 | 22-MAR-14:00 | 5.60 | 2.22 |
April | 0.164250E+10 | 7004.40 | 14-APR-08:35 | 0.20 | -2.7 | 0.680879E+09 | 1087.09 | 22-APR-14:30 | 15.00 | 6.61 |
May | 0.191632E+10 | 6299.37 | 16-MAY-07:05 | 3.58 | 2.20 | 0.918797E+09 | 1443.63 | 13-MAY-15:09 | 3.58 | 2.20 |
June | 0.183415E+10 | 5654.18 | 17-JUN-07:10 | 10.18 | 8.41 | 0.139064E+10 | 2154.71 | 30-JUN-15:09 | 27.38 | 17.05 |
July | 0.189098E+10 | 6218.36 | 17-JUL-07:05 | 9.78 | 9.73 | 0.155237E+10 | 2246.80 | 22-JUL-12:39 | 27.43 | 16.84 |
August | 0.295155E+10 | 8753.33 | 30-AUG-07:05 | 0.78 | -1.1 | 0.146104E+10 | 2168.80 | 04-AUG-15:09 | 0.78 | -1.1 |
September | 0.279609E+10 | 7513.65 | 16-SEP-07:05 | -0.1 | -0.4 | 0.774103E+09 | 1410.95 | 02-SEP-15:20 | -0.1 | -0.4 |
October | 0.652658E+09 | 7214.85 | 20-OCT-11:35 | -0.2 | -0.5 | 0.655019E+09 | 928.37 | 03-OCT-15:09 | -0.2 | -0.5 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 | -10.9 | 0.623386E+09 | 787.42 | 28-NOV-11:20 | -28.5 | -28.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.649304E+09 | 787.42 | 20-DEC-11:50 | -16.5 | -16.8 |
Annual Sum or Average | 0.138384E+11 | 0.106535E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.597369E+09 | 787.42 | -28.5 | -28.7 | ||
Maximum of Months | 0.295155E+10 | 8753.33 | 10.18 | 9.73 | 0.155237E+10 | 2246.80 | 27.43 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -14.9 | -15.4 | 0.632483E+09 | 780.39 | 31-JAN-14:20 | -20.0 | -20.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 | -20.7 | 0.590090E+09 | 780.43 | 27-FEB-14:20 | -28.7 | -28.9 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.2 | 0.703189E+09 | 1003.05 | 22-MAR-15:20 | 5.60 | 2.35 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 | 0.775255E+09 | 1440.64 | 22-APR-15:00 | 15.00 | 6.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 | 0.152889E+10 | 2392.70 | 13-MAY-15:30 | 20.00 | 9.32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.274004E+10 | 4375.75 | 30-JUN-15:20 | 26.47 | 16.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.337225E+10 | 5061.30 | 29-JUL-15:00 | 30.00 | 18.34 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 | 0.323318E+10 | 4881.90 | 04-AUG-15:09 | 22.70 | 14.61 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.153189E+10 | 3007.40 | 02-SEP-15:30 | 16.70 | 10.62 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 | 0.692515E+09 | 1197.46 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 | -10.9 | 0.618260E+09 | 780.43 | 25-NOV-15:20 | -20.0 | -20.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.644022E+09 | 780.38 | 27-DEC-13:09 | -23.4 | -23.6 |
Annual Sum or Average | 0.00 | 0.170621E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.590090E+09 | 780.38 | -28.7 | -28.9 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.337225E+10 | 5061.30 | 30.00 | 18.34 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109501E+11 | 27153.32 | 31-JAN-06:12 | -25.4 |
February | 0.935790E+10 | 27763.32 | 04-FEB-06:32 | -18.9 |
March | 0.912410E+10 | 27787.07 | 11-MAR-06:32 | -10.4 |
April | 0.480610E+10 | 27856.24 | 10-APR-05:32 | -6.7 |
May | 0.153083E+10 | 26819.80 | 05-MAY-05:42 | 3.80 |
June | 0.172083E+09 | 26519.89 | 02-JUN-05:01 | 5.78 |
July | 63371096.71 | 1517.58 | 05-JUL-06:30 | 8.30 |
August | 0.160559E+09 | 26188.90 | 31-AUG-05:02 | -1.2 |
September | 0.202849E+10 | 27371.75 | 25-SEP-05:42 | -1.6 |
October | 0.563394E+10 | 27744.60 | 25-OCT-05:32 | -11.1 |
November | 0.906773E+10 | 27780.78 | 01-NOV-05:32 | -10.2 |
December | 0.105355E+11 | 28215.47 | 05-DEC-06:31 | -28.1 |
Annual Sum or Average | 0.634307E+11 | |||
Minimum of Months | 63371096.71 | 1517.58 | -28.1 | |
Maximum of Months | 0.109501E+11 | 28215.47 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366346E+11 | 66722.26 | 28-JAN-22:42 | -24.2 |
February | 0.296634E+11 | 66574.72 | 24-FEB-05:22 | -25.6 |
March | 0.246272E+11 | 66210.13 | 02-MAR-04:42 | -26.6 |
April | 0.104875E+11 | 65633.88 | 10-APR-05:32 | -6.7 |
May | 0.496216E+09 | 60204.29 | 03-MAY-05:08 | 4.40 |
June | 95267770.65 | 1649.01 | 30-JUN-15:00 | 28.30 |
July | 61913124.49 | 1265.92 | 21-JUL-16:30 | 28.30 |
August | 70354007.67 | 1292.46 | 23-AUG-17:00 | 25.00 |
September | 0.151007E+10 | 65250.03 | 30-SEP-05:01 | -4.5 |
October | 0.143150E+11 | 65551.08 | 31-OCT-04:23 | -18.1 |
November | 0.297796E+11 | 65631.66 | 26-NOV-04:42 | -24.8 |
December | 0.362297E+11 | 66163.60 | 15-DEC-02:62 | -31.2 |
Annual Sum or Average | 0.183971E+12 | |||
Minimum of Months | 61913124.49 | 1265.92 | -31.2 | |
Maximum of Months | 0.366346E+11 | 66722.26 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144469E+12 | 101017.04 | 28-JAN-15:00 | -20.0 |
February | 0.119074E+12 | 100896.75 | 26-FEB-04:30 | -25.6 |
March | 0.108912E+12 | 100487.05 | 02-MAR-05:00 | -26.7 |
April | 0.461497E+11 | 98429.07 | 02-APR-20:00 | -12.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.244348E+09 | 13663.21 | 30-SEP-05:00 | -4.4 |
October | 0.587193E+11 | 81243.25 | 27-OCT-04:00 | -17.8 |
November | 0.102368E+12 | 87454.57 | 10-NOV-01:52 | -20.0 |
December | 0.141268E+12 | 100443.07 | 22-DEC-14:00 | -23.9 |
Annual Sum or Average | 0.721204E+12 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.144469E+12 | 101017.04 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.790893E+09 | 762.98 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.688004E+09 | 762.98 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.705613E+09 | 762.98 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.608194E+09 | 718.69 | 04-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.609268E+09 | 658.18 | 20-MAY-08:30 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.584412E+09 | 654.66 | 08-JUN-07:30 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.585324E+09 | 678.56 | 01-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.646403E+09 | 672.83 | 18-AUG-15:00 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.650154E+09 | 732.10 | 21-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.728280E+09 | 762.98 | 03-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.749562E+09 | 762.98 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.799684E+09 | 762.98 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.814579E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.584412E+09 | 654.66 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.799684E+09 | 762.98 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.368849E+10 | 3463.72 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.337993E+10 | 3463.72 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.391929E+10 | 3463.72 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.366257E+10 | 3463.72 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.380389E+10 | 3463.72 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.377797E+10 | 3463.72 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.368849E+10 | 3463.72 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.391929E+10 | 3463.72 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.366257E+10 | 3463.72 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.368849E+10 | 3463.72 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.354717E+10 | 3463.72 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.368849E+10 | 3463.72 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.444266E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.337993E+10 | 3463.72 | 0.00 | 0.00 | |
Maximum of Months | 0.391929E+10 | 3463.72 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.422422E+10 | 3810.10 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.379984E+10 | 3810.10 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.424375E+10 | 3751.09 | 03-MAR-15:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.388681E+10 | 3655.50 | 13-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.397465E+10 | 3636.11 | 09-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.389421E+10 | 3575.88 | 07-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.384532E+10 | 3621.98 | 29-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.411065E+10 | 3679.70 | 31-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.394005E+10 | 3710.49 | 30-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.409981E+10 | 3810.10 | 23-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.404274E+10 | 3810.10 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.423985E+10 | 3810.10 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.483019E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.379984E+10 | 3575.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.424375E+10 | 3810.10 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.790893E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394785E+10 |
February | 0.127628E+10 | 0.688004E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308875E+10 |
March | 0.149825E+10 | 0.705613E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353584E+10 |
April | 0.138726E+10 | 0.608194E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218895E+10 |
May | 0.144276E+10 | 0.609268E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21818.36 | 0.115720E+10 |
June | 0.144276E+10 | 0.584412E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9287884.32 | 0.747743E+09 |
July | 0.138726E+10 | 0.585324E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16160320.01 | 0.609898E+09 |
August | 0.149825E+10 | 0.646403E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3649841.15 | 0.991249E+09 |
September | 0.138726E+10 | 0.650154E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129421E+10 |
October | 0.138726E+10 | 0.728280E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257540E+10 |
November | 0.133177E+10 | 0.749562E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337741E+10 |
December | 0.138726E+10 | 0.799684E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384464E+10 |
Annual Sum or Average | 0.168137E+11 | 0.814579E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29119863.84 | 0.273591E+11 |
Minimum of Months | 0.127628E+10 | 0.584412E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609898E+09 |
Maximum of Months | 0.149825E+10 | 0.799684E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16160320.01 | 0.394785E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455593E+10 |
February | 0.300332E+10 | 0.337993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376942E+10 |
March | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543382E+10 |
April | 0.326447E+10 | 0.366257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477560E+10 |
May | 0.339505E+10 | 0.380389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5699727.41 | 0.217202E+10 |
June | 0.339505E+10 | 0.377797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7056357.45 | 0.153018E+10 |
July | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12049100.34 | 0.138844E+10 |
August | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5873407.50 | 0.180156E+10 |
September | 0.326447E+10 | 0.366257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160499E+10 |
October | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421173E+10 |
November | 0.313390E+10 | 0.354717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170420E+10 |
December | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346954E+10 |
Annual Sum or Average | 0.395654E+11 | 0.444266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30678592.70 | 0.364174E+11 |
Minimum of Months | 0.300332E+10 | 0.337993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138844E+10 |
Maximum of Months | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12049100.34 | 0.543382E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.422422E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301735E+11 |
February | 0.690763E+10 | 0.379984E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245948E+11 |
March | 0.810895E+10 | 0.424375E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339407E+11 |
April | 0.750829E+10 | 0.388681E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70967409.51 | 0.245210E+11 |
May | 0.780862E+10 | 0.397465E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699407E+09 | 0.104626E+11 |
June | 0.780862E+10 | 0.389421E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366739E+09 | 0.815744E+10 |
July | 0.750829E+10 | 0.384532E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187549E+09 | 0.938231E+10 |
August | 0.810895E+10 | 0.411065E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124647E+09 | 0.134175E+11 |
September | 0.750829E+10 | 0.394005E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26869.93 | 0.107571E+11 |
October | 0.750829E+10 | 0.409981E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19831744.43 | 0.241380E+11 |
November | 0.720796E+10 | 0.404274E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111774E+11 |
December | 0.750829E+10 | 0.423985E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244038E+11 |
Annual Sum or Average | 0.910005E+11 | 0.483019E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146917E+10 | 0.225126E+12 |
Minimum of Months | 0.690763E+10 | 0.379984E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815744E+10 |
Maximum of Months | 0.810895E+10 | 0.424375E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699407E+09 | 0.339407E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 762.98 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15694.77 | 12-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 762.98 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 15005.74 | 27-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 762.98 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 13190.10 | 01-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 718.69 | 04-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 11267.49 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 658.18 | 20-MAY-08:30 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 | 30-MAY-18:00 | 4754.21 | 16-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 654.66 | 08-JUN-07:30 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.75 | 29-JUN-16:10 | 3149.29 | 02-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 678.56 | 01-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.92 | 21-JUL-16:10 | 3478.47 | 17-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 672.83 | 18-AUG-15:00 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.92 | 11-AUG-16:10 | 5620.72 | 31-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 732.10 | 21-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 6529.22 | 29-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 762.98 | 03-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 10868.86 | 31-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 762.98 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 13423.11 | 29-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 762.98 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14336.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 654.66 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3149.29 | |||||
Maximum of Months | 1680.92 | 762.98 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.92 | 15694.77 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3463.72 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15719.47 | 28-JAN-17:00 |
February | 3955.50 | 01-FEB-08:09 | 3463.72 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9499.05 | 23-FEB-17:00 |
March | 3955.50 | 01-MAR-08:09 | 3463.72 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 7221.67 | 25-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 3463.72 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 8210.11 | 01-APR-19:07 |
May | 3955.50 | 01-MAY-07:10 | 3463.72 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.31 | 30-MAY-18:00 | 4174.42 | 27-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 3463.72 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.46 | 30-JUN-15:10 | 3735.92 | 24-JUN-21:00 |
July | 3955.50 | 01-JUL-07:10 | 3463.72 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1243.82 | 21-JUL-16:00 | 2300.08 | 04-JUL-17:00 |
August | 3955.50 | 01-AUG-07:10 | 3463.72 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.72 | 23-AUG-18:00 | 3617.64 | 29-AUG-20:00 |
September | 3955.50 | 01-SEP-07:10 | 3463.72 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2319.14 | 29-SEP-07:00 |
October | 3955.50 | 02-OCT-07:10 | 3463.72 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5391.32 | 27-OCT-06:10 |
November | 3955.50 | 01-NOV-07:10 | 3463.72 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5311.72 | 03-NOV-19:47 |
December | 3955.50 | 01-DEC-08:09 | 3463.72 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6129.30 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.08 | ||||
Maximum of Months | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1243.82 | 15719.47 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3810.10 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 89354.48 | 28-JAN-15:00 |
February | 9097.65 | 01-FEB-08:09 | 3810.10 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 60783.55 | 25-FEB-12:00 |
March | 9097.65 | 01-MAR-08:09 | 3751.09 | 03-MAR-15:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 44548.87 | 25-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3655.50 | 13-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2224.12 | 22-APR-14:00 | 42496.73 | 01-APR-18:53 |
May | 9097.65 | 01-MAY-07:10 | 3636.11 | 09-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7297.78 | 30-MAY-18:00 | 29361.86 | 27-MAY-11:00 |
June | 9097.65 | 01-JUN-07:10 | 3575.88 | 07-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6341.81 | 30-JUN-15:00 | 20927.23 | 24-JUN-21:00 |
July | 9097.65 | 01-JUL-07:10 | 3621.98 | 29-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10791.67 | 21-JUL-16:00 | 13015.22 | 04-JUL-17:00 |
August | 9097.65 | 01-AUG-07:10 | 3679.70 | 31-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.01 | 23-AUG-18:00 | 26827.09 | 31-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 3710.49 | 30-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 | 17-SEP-16:00 | 13323.69 | 21-SEP-14:00 |
October | 9097.65 | 02-OCT-07:10 | 3810.10 | 23-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2163.78 | 01-OCT-17:00 | 31666.78 | 31-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 3810.10 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 32156.02 | 01-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 3810.10 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 45866.97 | 22-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3575.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13015.22 | |||||
Maximum of Months | 9097.65 | 3810.10 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10791.67 | 89354.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.36 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.66 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.68 |
April | 137.55 | 28-APR-15:00 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.15 |
May | 595.74 | 16-MAY-10:20 | 1680.92 | 509.14 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.25 |
June | 3722.61 | 21-JUN-16:00 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 68.63 | 0.00 |
July | 18933.52 | 13-JUL-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.56 |
August | 15240.25 | 05-AUG-05:03 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.05 |
September | 912.68 | 02-SEP-07:10 | 1680.92 | 678.13 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.42 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.31 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.54 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18933.52 | 1680.92 | 678.13 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 68.63 | 556.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.08 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2223.09 |
March | 4540.52 | 22-MAR-14:50 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7004.40 | 14-APR-08:35 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.56 |
May | 6299.37 | 16-MAY-07:05 | 7911.00 | 6112.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3703.17 |
June | 5654.18 | 17-JUN-07:10 | 3955.50 | 3056.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6218.36 | 17-JUL-07:05 | 7911.00 | 6112.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.94 |
August | 8753.33 | 30-AUG-07:05 | 7911.00 | 6112.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.79 |
September | 7513.65 | 16-SEP-07:05 | 7911.00 | 6112.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1701.91 |
October | 7214.85 | 20-OCT-11:35 | 4192.83 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836.89 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2497.54 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8753.33 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3703.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1792.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16751.91 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 1792.96 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13167.47 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2241.20 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6565.09 |
April | 0.00 | 01-APR-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22785.65 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.82 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.36 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2928.42 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5919.23 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3947.09 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7132.77 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13388.67 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1792.96 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2241.20 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22785.65 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.308401E+11 | 25764.22 | 12-JAN-15:30 | 0.253306E+12 | 194284.40 | 30-JAN-17:00 |
February | 0.267375E+11 | 24969.51 | 04-FEB-09:20 | 0.207860E+12 | 195631.86 | 28-FEB-17:49 |
March | 0.288914E+11 | 24010.24 | 01-MAR-08:09 | 0.189042E+12 | 168023.39 | 16-MAR-07:00 |
April | 0.250309E+11 | 21074.70 | 01-APR-14:30 | 0.802650E+11 | 147150.38 | 02-APR-19:49 |
May | 0.242032E+11 | 20889.42 | 09-MAY-12:50 | 0.282140E+10 | 23494.28 | 03-MAY-05:10 |
June | 0.233523E+11 | 21595.92 | 30-JUN-14:39 | 89543421.69 | 7569.00 | 01-JUN-05:10 |
July | 0.232608E+11 | 22589.60 | 29-JUL-14:00 | 1568496.35 | 716.79 | 05-JUL-06:30 |
August | 0.255364E+11 | 21503.83 | 11-AUG-14:50 | 0.107143E+09 | 7630.39 | 31-AUG-06:10 |
September | 0.251907E+11 | 20831.64 | 20-SEP-14:50 | 0.729490E+10 | 45213.80 | 30-SEP-05:10 |
October | 0.278482E+11 | 24861.58 | 27-OCT-08:20 | 0.106695E+12 | 139057.09 | 31-OCT-05:10 |
November | 0.289515E+11 | 25560.22 | 29-NOV-15:39 | 0.192100E+12 | 156947.30 | 29-NOV-08:09 |
December | 0.314059E+11 | 25641.57 | 15-DEC-15:09 | 0.250080E+12 | 187385.82 | 15-DEC-12:09 |
Annual Sum or Average | 0.321249E+12 | 0.128966E+13 | ||||
Minimum of Months | 0.232608E+11 | 20831.64 | 1568496.35 | 716.79 | ||
Maximum of Months | 0.314059E+11 | 25764.22 | 0.253306E+12 | 195631.86 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.271683E+09 | 2404.88 | 31-JAN-11:30 | 0.00 | 0.00 |
February | 0.153173E+10 | 5685.32 | 26-FEB-13:09 | 0.00 | 0.00 |
March | 0.549191E+10 | 12815.86 | 30-MAR-12:30 | 0.00 | 0.00 |
April | 0.101335E+11 | 14852.12 | 30-APR-13:30 | 0.00 | 0.00 |
May | 0.126085E+11 | 15832.26 | 21-MAY-12:00 | 0.00 | 0.00 |
June | 0.129493E+11 | 15887.94 | 01-JUN-12:30 | 0.00 | 0.00 |
July | 0.119295E+11 | 15746.15 | 06-JUL-12:50 | 0.00 | 0.00 |
August | 0.918319E+10 | 13860.99 | 10-AUG-12:30 | 0.00 | 0.00 |
September | 0.502437E+10 | 10259.37 | 09-SEP-12:30 | 0.00 | 0.00 |
October | 0.225762E+10 | 6788.73 | 03-OCT-12:30 | 0.00 | 0.00 |
November | 0.524886E+09 | 2888.74 | 06-NOV-13:30 | 0.00 | 0.00 |
December | 52171141.85 | 766.26 | 02-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.719583E+11 | 0.00 | 0.00 | ||
Minimum of Months | 52171141.85 | 766.26 | 0.00 | 0.00 | |
Maximum of Months | 0.129493E+11 | 15887.94 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.870360E+10 | 0.665269E+10 | 0.112984E+11 | 0.00 | 0.302459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116088E+10 | 0.00 |
February | 0.786778E+10 | 0.475162E+10 | 0.103734E+11 | 0.00 | 0.267972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106502E+10 | 0.00 |
March | 0.886865E+10 | 0.383935E+10 | 0.121089E+11 | 0.00 | 0.283499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123945E+10 | 0.00 |
April | 0.815757E+10 | 0.237959E+10 | 0.112578E+11 | 0.00 | 0.208189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115409E+10 | 0.00 |
May | 0.838781E+10 | 0.138818E+10 | 0.117000E+11 | 0.00 | 0.153870E+10 | 0.00 | 0.00 | 12.95 | 0.00 | 0.00 | 0.00 | 0.118854E+10 | 0.00 |
June | 0.825660E+10 | 0.664655E+09 | 0.116594E+11 | 0.00 | 0.151408E+10 | 0.00 | 0.00 | 0.122093E+09 | 0.00 | 0.00 | 0.00 | 0.113549E+10 | 0.00 |
July | 0.811913E+10 | 0.984119E+09 | 0.112984E+11 | 0.00 | 0.145705E+10 | 0.00 | 0.00 | 0.339890E+09 | 0.00 | 0.00 | 0.00 | 0.106225E+10 | 0.00 |
August | 0.867634E+10 | 0.195440E+10 | 0.121016E+11 | 0.00 | 0.157310E+10 | 0.00 | 0.00 | 0.119523E+09 | 0.00 | 0.00 | 0.00 | 0.111151E+10 | 0.00 |
September | 0.825277E+10 | 0.312663E+10 | 0.112504E+11 | 0.00 | 0.152037E+10 | 0.00 | 0.00 | 0.39 | 0.00 | 0.00 | 0.00 | 0.104052E+10 | 0.00 |
October | 0.851658E+10 | 0.464684E+10 | 0.113057E+11 | 0.00 | 0.231166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106735E+10 | 0.00 |
November | 0.833947E+10 | 0.591045E+10 | 0.108562E+11 | 0.00 | 0.278573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105964E+10 | 0.00 |
December | 0.872802E+10 | 0.722708E+10 | 0.112984E+11 | 0.00 | 0.300897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114348E+10 | 0.00 |
Annual Sum or Average | 0.100874E+12 | 0.435256E+11 | 0.136508E+12 | 0.00 | 0.263309E+11 | 0.00 | 0.00 | 0.581506E+09 | 0.00 | 0.00 | 0.00 | 0.134282E+11 | 0.00 |
Minimum of Months | 0.786778E+10 | 0.664655E+09 | 0.103734E+11 | 0.00 | 0.145705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104052E+10 | 0.00 |
Maximum of Months | 0.886865E+10 | 0.722708E+10 | 0.121089E+11 | 0.00 | 0.302459E+10 | 0.00 | 0.00 | 0.339890E+09 | 0.00 | 0.00 | 0.00 | 0.123945E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.253306E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.207860E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.189042E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.802650E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.282140E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 89543421.69 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1568496.35 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.107143E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.729490E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.106695E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.192100E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.250080E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128966E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1568496.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.253306E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8036.80 | 02-JAN-09:09 | 3768.97 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2278.61 | 12-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8036.80 | 01-FEB-09:09 | 3768.97 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2288.12 | 27-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7872.93 | 03-MAR-09:09 | 3768.97 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2200.95 | 02-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7778.51 | 13-APR-08:09 | 3768.97 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2109.45 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7755.56 | 09-MAY-08:09 | 3421.91 | 01-MAY-21:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 1552.46 | 27-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7667.91 | 07-JUN-08:09 | 3421.91 | 01-JUN-22:49 | 10035.17 | 01-JUN-07:10 | 0.00 | 1469.49 | 10-JUN-14:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7731.16 | 29-JUL-08:09 | 3421.91 | 11-JUL-22:00 | 10035.17 | 01-JUL-07:10 | 0.00 | 1469.49 | 03-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7805.01 | 31-AUG-08:09 | 3768.97 | 24-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 1469.49 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7855.73 | 30-SEP-08:09 | 3768.97 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1792.38 | 30-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8036.80 | 23-OCT-08:09 | 3768.97 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2097.48 | 31-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8036.80 | 01-NOV-08:09 | 3768.97 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2215.36 | 29-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8036.80 | 01-DEC-09:09 | 3768.97 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2253.40 | 15-DEC-08:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7667.91 | 3421.91 | 10035.17 | 0.00 | 1469.49 | 0.00 | 0.00 | |||||
Maximum of Months | 8036.80 | 3768.97 | 10035.17 | 0.00 | 2288.12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1857.72 | 12-JAN-12:39 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 1857.65 | 13-FEB-12:09 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 1857.65 | 07-MAR-12:00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 1857.65 | 20-APR-11:50 | 0.00 | 01-APR-00:10 |
May | 0.01 | 13-MAY-14:00 | 0.00 | 0.00 | 0.00 | 1857.63 | 03-MAY-11:09 | 0.00 | 01-MAY-00:10 |
June | 1256.75 | 30-JUN-14:00 | 0.00 | 0.00 | 0.00 | 1838.09 | 01-JUN-11:39 | 0.00 | 01-JUN-00:10 |
July | 2490.27 | 29-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1735.94 | 01-JUL-11:00 | 0.00 | 01-JUL-00:10 |
August | 1162.51 | 11-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1713.98 | 02-AUG-11:00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 02-SEP-14:39 | 0.00 | 0.00 | 0.00 | 1711.08 | 29-SEP-11:09 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 1729.87 | 31-OCT-11:30 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 1828.60 | 29-NOV-12:09 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1857.64 | 29-DEC-12:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1711.08 | 0.00 | |||
Maximum of Months | 2490.27 | 0.00 | 0.00 | 0.00 | 1857.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 25764.22 | 12-JAN-15:30 | 8036.80 | 10035.17 | 3768.97 | 0.00 | 2229.85 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24969.51 | 04-FEB-09:20 | 8036.80 | 10035.17 | 3768.97 | 0.00 | 2065.21 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24010.24 | 01-MAR-08:09 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 2183.56 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21074.70 | 01-APR-14:30 | 7551.98 | 10035.17 | 0.00 | 0.00 | 1808.65 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20889.42 | 09-MAY-12:50 | 7702.70 | 10035.17 | 0.00 | 0.00 | 1469.49 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21595.92 | 30-JUN-14:39 | 7297.27 | 10035.17 | 0.00 | 0.00 | 1469.49 | 0.00 | 0.00 | 1239.94 | 0.00 |
July | 22589.60 | 29-JUL-14:00 | 7432.91 | 10035.17 | 0.00 | 0.00 | 1469.49 | 0.00 | 0.00 | 2142.42 | 0.00 |
August | 21503.83 | 11-AUG-14:50 | 7475.42 | 10035.17 | 0.00 | 0.00 | 1469.49 | 0.00 | 0.00 | 1018.62 | 0.00 |
September | 20831.64 | 20-SEP-14:50 | 7823.20 | 10035.17 | 0.00 | 0.00 | 1469.49 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24861.58 | 27-OCT-08:20 | 8036.80 | 10035.17 | 3768.97 | 0.00 | 2034.95 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25560.22 | 29-NOV-15:39 | 8036.80 | 10035.17 | 3768.97 | 0.00 | 2110.22 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25641.57 | 15-DEC-15:09 | 8036.80 | 10035.17 | 3768.97 | 0.00 | 2180.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 20831.64 | 7180.87 | 10035.17 | 0.00 | 0.00 | 1469.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25764.22 | 8036.80 | 10035.17 | 3768.97 | 0.00 | 2229.85 | 0.00 | 0.00 | 2142.42 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 194284.40 | 30-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 195631.86 | 28-FEB-17:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 168023.39 | 16-MAR-07:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 147150.38 | 02-APR-19:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 23494.28 | 03-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 7569.00 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 716.79 | 05-JUL-06:30 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 7630.39 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 45213.80 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 139057.09 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 156947.30 | 29-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 187385.82 | 15-DEC-12:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 716.79 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 195631.86 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.17 | 16.53 | 9.17 | 17.25 | 0.00 | 17.25 | 0.00 | 17.25 |
February | 22.00 | 16.47 | 7.83 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
March | 15.67 | 17.63 | 10.17 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
April | 11.50 | 18.61 | 9.50 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
May | 5.33 | 20.25 | 5.33 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.33 | 24.53 |
August | 0.33 | 20.51 | 0.33 | 20.51 | 0.17 | 21.30 | 0.17 | 21.83 |
September | 5.33 | 20.19 | 5.33 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
October | 10.33 | 18.88 | 8.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
November | 14.33 | 17.63 | 9.17 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
December | 12.83 | 18.06 | 9.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
Annual Sum or Average | 122.83 | 17.67 | 74.33 | 18.33 | 0.50 | 18.35 | 0.50 | 18.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.17 | 20.51 | 10.17 | 20.51 | 0.33 | 24.53 | 0.33 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.00 | 14.45 | 4.17 | 14.45 | 0.00 | 14.45 | 0.00 | 14.45 |
February | 101.83 | 14.49 | 3.83 | 14.49 | 0.00 | 14.49 | 0.00 | 14.49 |
March | 98.50 | 14.62 | 5.33 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
April | 46.33 | 14.78 | 3.83 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
May | 1.50 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
October | 50.83 | 14.78 | 3.00 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
November | 112.00 | 14.61 | 4.17 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
December | 115.17 | 14.49 | 4.17 | 14.49 | 0.00 | 14.49 | 0.00 | 14.49 |
Annual Sum or Average | 643.33 | 14.57 | 28.50 | 14.57 | 0.00 | 14.57 | 0.00 | 14.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.17 | 14.98 | 5.33 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.00 | 8.16 | 17.00 | 8.19 | 0.00 | 8.19 | 0.00 | 8.19 |
February | 31.00 | 8.95 | 7.33 | 8.94 | 0.00 | 8.94 | 0.00 | 8.94 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.00 | 8.47 | 24.33 | 8.46 | 0.00 | 8.46 | 0.00 | 8.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.00 | 8.95 | 17.00 | 8.94 | 0.00 | 8.94 | 0.00 | 8.94 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
February | 276.00 | 21.04 | 276.00 | 21.04 | 276.00 | 21.04 |
March | 324.00 | 21.03 | 324.00 | 21.03 | 324.00 | 21.03 |
April | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
May | 312.00 | 21.52 | 232.00 | 21.38 | 232.00 | 21.32 |
June | 298.67 | 23.40 | 12.67 | 23.31 | 12.67 | 23.23 |
July | 163.83 | 23.69 | 23.17 | 23.71 | 0.00 | 23.71 |
August | 262.00 | 23.30 | 15.17 | 23.22 | 11.33 | 23.14 |
September | 300.00 | 21.30 | 246.17 | 21.21 | 246.17 | 21.18 |
October | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
November | 288.00 | 21.03 | 288.00 | 21.03 | 288.00 | 21.03 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 3424.50 | 21.61 | 2617.17 | 21.39 | 2590.17 | 21.29 |
Minimum of Months | 163.83 | 21.03 | 12.67 | 21.03 | 0.00 | 21.03 |
Maximum of Months | 324.00 | 23.69 | 324.00 | 23.71 | 324.00 | 23.71 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 15.54 | 324.00 | 15.54 | 324.00 | 15.54 |
April | 300.00 | 15.88 | 300.00 | 15.88 | 300.00 | 15.88 |
May | 312.00 | 18.03 | 312.00 | 18.03 | 312.00 | 18.03 |
June | 273.83 | 22.03 | 72.67 | 21.94 | 47.33 | 21.66 |
July | 124.00 | 22.90 | 135.00 | 24.22 | 0.83 | 24.21 |
August | 250.83 | 21.89 | 89.50 | 22.08 | 41.17 | 21.80 |
September | 300.00 | 16.93 | 296.00 | 16.90 | 296.00 | 16.90 |
October | 300.00 | 15.60 | 300.00 | 15.60 | 300.00 | 15.60 |
November | 288.00 | 15.54 | 288.00 | 15.54 | 288.00 | 15.54 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 3348.67 | 17.21 | 2993.17 | 17.01 | 2785.33 | 16.74 |
Minimum of Months | 124.00 | 15.54 | 72.67 | 15.54 | 0.83 | 15.54 |
Maximum of Months | 324.00 | 22.90 | 324.00 | 24.22 | 324.00 | 24.21 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.90 | 300.00 | 9.90 | 300.00 | 9.90 |
February | 276.00 | 9.97 | 276.00 | 9.97 | 276.00 | 9.97 |
March | 324.00 | 10.05 | 324.00 | 10.05 | 324.00 | 10.05 |
April | 300.00 | 10.89 | 300.00 | 10.89 | 300.00 | 10.89 |
May | 312.00 | 15.12 | 312.00 | 15.12 | 312.00 | 15.12 |
June | 311.50 | 20.58 | 135.00 | 20.01 | 135.00 | 19.71 |
July | 186.67 | 22.68 | 61.33 | 23.18 | 5.50 | 23.11 |
August | 272.83 | 21.52 | 99.67 | 21.44 | 68.00 | 21.12 |
September | 300.00 | 15.46 | 300.00 | 15.46 | 300.00 | 15.46 |
October | 300.00 | 10.34 | 300.00 | 10.34 | 300.00 | 10.34 |
November | 288.00 | 10.00 | 288.00 | 10.00 | 288.00 | 10.00 |
December | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
Annual Sum or Average | 3471.00 | 13.57 | 2996.00 | 12.96 | 2908.50 | 12.62 |
Minimum of Months | 186.67 | 9.90 | 61.33 | 9.90 | 5.50 | 9.90 |
Maximum of Months | 324.00 | 22.68 | 324.00 | 23.18 | 324.00 | 23.11 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 53.67 | 12.95 | 0.50 | 53.67 | -0.0 | 0.00 | 0.00 | 13-MAY-15:00 | 0.00 | 01-MAY-00:10 | 0.06 | 13-MAY-15:00 | 0.06 | 13-MAY-15:00 | 0.00 | 01-MAY-00:10 | 0.01 | 13-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.538713E+09 | 0.122093E+09 | 72.58 | 0.517379E+09 | 21334406.97 | 0.00 | 0.75 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 5460.68 | 30-JUN-15:00 | 5039.90 | 30-JUN-15:00 | 868.95 | 30-JUN-12:10 | 1256.75 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.144949E+10 | 0.325460E+09 | 145.93 | 0.137253E+10 | 76956888.07 | 0.00 | 1.00 | 12-JUL-05:03 | 0.00 | 01-JUL-00:10 | 13630.88 | 25-JUL-05:03 | 11413.56 | 12-JUL-05:03 | 5484.37 | 25-JUL-05:03 | 2954.11 | 25-JUL-05:03 | 0.00 | 01-JUL-00:10 |
August | 0.527469E+09 | 0.119523E+09 | 70.93 | 0.503122E+09 | 24346608.59 | 0.00 | 1.00 | 03-AUG-05:03 | 0.00 | 01-AUG-00:10 | 13248.92 | 03-AUG-05:03 | 9348.93 | 03-AUG-05:03 | 3899.99 | 03-AUG-05:03 | 2873.33 | 03-AUG-05:03 | 0.00 | 01-AUG-00:10 |
September | 1.63 | 0.39 | 0.17 | 1.55 | 0.08 | 0.00 | 0.00 | 02-SEP-14:40 | 0.00 | 01-SEP-00:10 | 0.00 | 02-SEP-14:40 | 0.00 | 02-SEP-14:40 | 0.00 | 02-SEP-14:40 | 0.00 | 02-SEP-14:40 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.251567E+10 | 0.567076E+09 | 290.11 | 0.239303E+10 | 0.122638E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.144949E+10 | 0.325460E+09 | 145.93 | 0.137253E+10 | 76956888.07 | 0.00 | 1.00 | 0.00 | 13630.88 | 11413.56 | 5484.37 | 2954.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 |
July | 53888071.28 | 14429155.69 | 8.83 | 53624491.29 | 263579.99 | 0.00 | 0.34 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 | 3548.73 | 29-JUL-16:00 | 3548.73 | 29-JUL-16:00 | 51.61 | 22-JUL-12:10 | 948.64 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 53888071.28 | 14429155.69 | 8.83 | 53624491.29 | 263579.99 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 53888071.28 | 14429155.69 | 8.83 | 53624491.29 | 263579.99 | 0.00 | 0.34 | 0.00 | 3548.73 | 3548.73 | 51.61 | 948.64 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4.70 | 0.80 | 3.90 | 0.00 | 240.71 | 0.00 | 0.00 | 0.00 |
February | 28.02 | 9.76 | 18.26 | 6.63 | 200.18 | 0.00 | 0.00 | 0.00 |
March | 84.43 | 36.54 | 47.89 | 54.65 | 138.26 | 0.00 | 0.00 | 0.00 |
April | 199.45 | 103.48 | 95.97 | 213.07 | 71.08 | 0.00 | 0.00 | 0.00 |
May | 193.74 | 88.37 | 105.37 | 223.53 | 30.39 | 0.00 | 0.00 | 0.00 |
June | 212.44 | 90.81 | 121.63 | 252.13 | 18.56 | 0.00 | 0.00 | 0.00 |
July | 177.48 | 67.17 | 110.30 | 207.66 | 24.58 | 0.00 | 0.00 | 0.00 |
August | 146.28 | 62.21 | 84.07 | 163.48 | 36.67 | 0.00 | 0.00 | 0.00 |
September | 88.13 | 36.81 | 51.32 | 83.26 | 58.26 | 0.00 | 0.00 | 0.00 |
October | 34.44 | 10.27 | 24.17 | 15.84 | 120.43 | 0.00 | 0.00 | 0.00 |
November | 13.76 | 4.94 | 8.82 | 1.62 | 228.99 | 0.00 | 0.00 | 0.00 |
December | 1.24 | 0.13 | 1.11 | 0.00 | 257.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.93 | 42.70 | 56.23 | 102.21 | 118.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.24 | 0.13 | 1.11 | 0.00 | 18.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.44 | 103.48 | 121.63 | 252.13 | 257.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4.70 | 0.80 | 3.90 | 0.00 | 240.71 | 0.00 | 0.00 | 0.00 |
February | 28.02 | 9.76 | 18.26 | 6.63 | 200.18 | 0.00 | 0.00 | 0.00 |
March | 84.43 | 36.54 | 47.89 | 54.65 | 138.26 | 0.00 | 0.00 | 0.00 |
April | 199.45 | 103.48 | 95.97 | 213.07 | 71.08 | 0.00 | 0.00 | 0.00 |
May | 193.74 | 88.37 | 105.37 | 223.53 | 30.39 | 0.00 | 0.00 | 0.00 |
June | 212.44 | 90.81 | 121.63 | 252.13 | 18.56 | 0.00 | 0.00 | 0.00 |
July | 177.48 | 67.17 | 110.30 | 207.66 | 24.58 | 0.00 | 0.00 | 0.00 |
August | 146.28 | 62.21 | 84.07 | 163.48 | 36.67 | 0.00 | 0.00 | 0.00 |
September | 88.13 | 36.81 | 51.32 | 83.26 | 58.26 | 0.00 | 0.00 | 0.00 |
October | 34.44 | 10.27 | 24.17 | 15.84 | 120.43 | 0.00 | 0.00 | 0.00 |
November | 13.76 | 4.94 | 8.82 | 1.62 | 228.99 | 0.00 | 0.00 | 0.00 |
December | 1.24 | 0.13 | 1.11 | 0.00 | 257.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.93 | 42.70 | 56.23 | 102.21 | 118.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.24 | 0.13 | 1.11 | 0.00 | 18.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.44 | 103.48 | 121.63 | 252.13 | 257.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.99 | 0.00 | 1.99 | 0.00 | 142.15 | 0.00 | 0.00 | 0.00 |
February | 8.81 | 0.00 | 8.81 | 0.00 | 124.88 | 0.00 | 0.00 | 0.00 |
March | 23.62 | 0.01 | 23.62 | 3.02 | 88.46 | 0.00 | 0.00 | 0.00 |
April | 42.94 | 1.16 | 41.78 | 24.29 | 41.86 | 0.00 | 0.00 | 0.00 |
May | 65.75 | 10.51 | 55.24 | 65.35 | 15.79 | 0.00 | 0.00 | 0.00 |
June | 84.86 | 18.56 | 66.30 | 92.63 | 8.45 | 0.00 | 0.00 | 0.00 |
July | 71.60 | 11.71 | 59.89 | 76.41 | 12.29 | 0.00 | 0.00 | 0.00 |
August | 45.99 | 2.43 | 43.56 | 40.82 | 20.23 | 0.00 | 0.00 | 0.00 |
September | 25.61 | 0.07 | 25.54 | 13.82 | 35.15 | 0.00 | 0.00 | 0.00 |
October | 12.40 | 0.00 | 12.40 | 1.73 | 74.34 | 0.00 | 0.00 | 0.00 |
November | 3.85 | 0.00 | 3.85 | 0.00 | 139.40 | 0.00 | 0.00 | 0.00 |
December | 0.60 | 0.00 | 0.60 | 0.00 | 150.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.45 | 3.72 | 28.73 | 26.66 | 70.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.60 | 0.00 | 0.60 | 0.00 | 8.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.86 | 18.56 | 66.30 | 92.63 | 150.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.99 | 0.00 | 1.99 | 0.00 | 142.15 | 0.00 | 0.00 | 0.00 |
February | 8.81 | 0.00 | 8.81 | 0.00 | 124.88 | 0.00 | 0.00 | 0.00 |
March | 23.62 | 0.01 | 23.62 | 3.02 | 88.46 | 0.00 | 0.00 | 0.00 |
April | 42.93 | 1.16 | 41.78 | 24.29 | 41.86 | 0.00 | 0.00 | 0.00 |
May | 65.75 | 10.51 | 55.24 | 65.35 | 15.79 | 0.00 | 0.00 | 0.00 |
June | 84.85 | 18.56 | 66.29 | 92.63 | 8.45 | 0.00 | 0.00 | 0.00 |
July | 71.60 | 11.71 | 59.89 | 76.41 | 12.29 | 0.00 | 0.00 | 0.00 |
August | 45.99 | 2.43 | 43.56 | 40.81 | 20.22 | 0.00 | 0.00 | 0.00 |
September | 25.61 | 0.07 | 25.54 | 13.82 | 35.15 | 0.00 | 0.00 | 0.00 |
October | 12.40 | 0.00 | 12.40 | 1.73 | 74.34 | 0.00 | 0.00 | 0.00 |
November | 3.85 | 0.00 | 3.85 | 0.00 | 139.40 | 0.00 | 0.00 | 0.00 |
December | 0.60 | 0.00 | 0.60 | 0.00 | 150.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.45 | 3.72 | 28.73 | 26.66 | 70.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.60 | 0.00 | 0.60 | 0.00 | 8.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.85 | 18.56 | 66.29 | 92.63 | 150.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.79 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.92 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.22 | 39.75 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 143.61 | 19.51 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 154.81 | 13.32 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 134.78 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.00 | 27.17 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 44.94 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.37 | 60.23 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.68 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.05 | 69.02 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 154.81 | 148.88 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.79 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.92 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.22 | 39.75 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 143.61 | 19.51 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 154.81 | 13.32 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 134.78 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.00 | 27.17 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 44.94 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.37 | 60.23 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.68 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.05 | 69.02 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 154.81 | 148.88 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.79 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.92 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.22 | 39.75 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 143.61 | 19.51 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 154.81 | 13.32 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 134.78 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.00 | 27.17 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 44.94 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.37 | 60.23 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.68 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.05 | 69.02 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 154.81 | 148.88 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.79 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.92 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.22 | 39.75 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 143.61 | 19.51 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 154.81 | 13.32 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 134.78 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.00 | 27.17 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 44.94 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.37 | 60.23 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.68 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.05 | 69.02 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 154.81 | 148.88 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.79 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.92 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.22 | 39.75 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 143.61 | 19.51 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 154.81 | 13.32 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 134.78 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.00 | 27.17 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 44.94 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.37 | 60.23 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.68 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.05 | 69.02 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 154.81 | 148.88 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.79 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.92 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.22 | 39.75 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 143.61 | 19.51 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 154.81 | 13.32 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 134.78 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.00 | 27.17 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 44.94 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.37 | 60.23 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.68 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.05 | 69.02 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 154.81 | 148.88 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.79 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.92 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.22 | 39.75 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 143.61 | 19.51 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 154.81 | 13.32 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 134.78 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.00 | 27.17 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 44.94 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.37 | 60.23 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.68 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.05 | 69.02 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 154.81 | 148.88 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.79 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.92 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.22 | 39.75 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 143.61 | 19.51 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 154.81 | 13.32 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 134.78 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.00 | 27.17 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 44.94 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.37 | 60.23 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.68 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.05 | 69.02 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 154.81 | 148.88 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.79 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.92 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.22 | 39.75 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 143.61 | 19.51 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 154.81 | 13.32 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 134.78 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.00 | 27.17 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 44.94 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.37 | 60.23 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.68 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.05 | 69.02 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 154.81 | 148.88 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.22 | 2.22 | 0.00 | 138.69 | 0.00 | 0.00 | 0.00 |
February | 12.37 | 3.03 | 9.35 | 0.17 | 115.79 | 0.00 | 0.00 | 0.00 |
March | 43.44 | 18.47 | 24.97 | 31.85 | 76.92 | 0.00 | 0.00 | 0.00 |
April | 87.39 | 47.15 | 40.24 | 100.22 | 39.75 | 0.00 | 0.00 | 0.00 |
May | 113.99 | 64.86 | 49.13 | 143.61 | 19.51 | 0.00 | 0.00 | 0.00 |
June | 123.66 | 61.66 | 62.00 | 154.81 | 13.32 | 0.00 | 0.00 | 0.00 |
July | 110.94 | 53.65 | 57.29 | 134.78 | 18.70 | 0.00 | 0.00 | 0.00 |
August | 83.52 | 40.52 | 43.00 | 96.00 | 27.17 | 0.00 | 0.00 | 0.00 |
September | 45.12 | 17.86 | 27.26 | 44.94 | 36.43 | 0.00 | 0.00 | 0.00 |
October | 18.52 | 4.49 | 14.03 | 10.37 | 60.23 | 9.33 | 0.00 | 0.00 |
November | 4.64 | 0.39 | 4.26 | 0.00 | 135.68 | 0.00 | 0.00 | 0.00 |
December | 0.68 | 0.01 | 0.67 | 0.00 | 148.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.11 | 26.15 | 27.96 | 60.05 | 69.02 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.01 | 0.67 | 0.00 | 13.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.66 | 64.86 | 62.00 | 154.81 | 148.88 | 9.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 12585264.08 | 2137577.42 | 10447686.66 | 0.00 | 0.644726E+09 |
February | 67777076.39 | 23606070.59 | 44171005.80 | 16038929.85 | 0.484269E+09 |
March | 0.226135E+09 | 97857243.62 | 0.128278E+09 | 0.146382E+09 | 0.370321E+09 |
April | 0.516980E+09 | 0.268222E+09 | 0.248758E+09 | 0.552289E+09 | 0.184243E+09 |
May | 0.518912E+09 | 0.236697E+09 | 0.282215E+09 | 0.598712E+09 | 81394832.97 |
June | 0.550646E+09 | 0.235377E+09 | 0.315269E+09 | 0.653513E+09 | 48104371.80 |
July | 0.475353E+09 | 0.179913E+09 | 0.295440E+09 | 0.556187E+09 | 65826044.34 |
August | 0.391792E+09 | 0.166611E+09 | 0.225181E+09 | 0.437856E+09 | 98207681.40 |
September | 0.228433E+09 | 95403472.71 | 0.133030E+09 | 0.215799E+09 | 0.151000E+09 |
October | 92235753.62 | 27501698.32 | 64734055.30 | 42438679.82 | 0.322558E+09 |
November | 35674091.01 | 12812997.12 | 22861093.89 | 4206012.63 | 0.593542E+09 |
December | 3316086.03 | 340650.64 | 2975435.39 | 0.00 | 0.689579E+09 |
Annual Sum or Average | 0.311984E+10 | 0.134648E+10 | 0.177336E+10 | 0.322342E+10 | 0.373377E+10 |
Minimum of Months | 3316086.03 | 340650.64 | 2975435.39 | 0.00 | 48104371.80 |
Maximum of Months | 0.550646E+09 | 0.268222E+09 | 0.315269E+09 | 0.653513E+09 | 0.689579E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 12585264.08 | 2137577.42 | 10447686.66 | 0.00 | 0.644726E+09 |
February | 67777076.39 | 23606070.59 | 44171005.80 | 16038929.85 | 0.484269E+09 |
March | 0.226135E+09 | 97857243.62 | 0.128278E+09 | 0.146382E+09 | 0.370321E+09 |
April | 0.516980E+09 | 0.268222E+09 | 0.248758E+09 | 0.552289E+09 | 0.184243E+09 |
May | 0.518912E+09 | 0.236697E+09 | 0.282215E+09 | 0.598712E+09 | 81394832.97 |
June | 0.550646E+09 | 0.235377E+09 | 0.315269E+09 | 0.653513E+09 | 48104371.80 |
July | 0.475353E+09 | 0.179913E+09 | 0.295440E+09 | 0.556187E+09 | 65826044.34 |
August | 0.391792E+09 | 0.166611E+09 | 0.225181E+09 | 0.437856E+09 | 98207681.40 |
September | 0.228433E+09 | 95403472.71 | 0.133030E+09 | 0.215799E+09 | 0.151000E+09 |
October | 92235753.62 | 27501698.32 | 64734055.30 | 42438679.82 | 0.322558E+09 |
November | 35674091.01 | 12812997.12 | 22861093.89 | 4206012.63 | 0.593542E+09 |
December | 3316086.03 | 340650.64 | 2975435.39 | 0.00 | 0.689579E+09 |
Annual Sum or Average | 0.311984E+10 | 0.134648E+10 | 0.177336E+10 | 0.322342E+10 | 0.373377E+10 |
Minimum of Months | 3316086.03 | 340650.64 | 2975435.39 | 0.00 | 48104371.80 |
Maximum of Months | 0.550646E+09 | 0.268222E+09 | 0.315269E+09 | 0.653513E+09 | 0.689579E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 5336011.68 | 0.00 | 5336011.68 | 0.00 | 0.380739E+09 |
February | 21305066.83 | 0.00 | 21305066.83 | 0.00 | 0.302115E+09 |
March | 63272979.64 | 18892.60 | 63254087.04 | 8092260.38 | 0.236923E+09 |
April | 0.111289E+09 | 3001191.94 | 0.108288E+09 | 62956149.62 | 0.108503E+09 |
May | 0.176115E+09 | 28157904.89 | 0.147957E+09 | 0.175046E+09 | 42280276.80 |
June | 0.219951E+09 | 48108939.50 | 0.171842E+09 | 0.240105E+09 | 21890681.10 |
July | 0.191773E+09 | 31367267.56 | 0.160406E+09 | 0.204669E+09 | 32926690.38 |
August | 0.123179E+09 | 6500140.13 | 0.116679E+09 | 0.109321E+09 | 54170819.55 |
September | 66389520.56 | 178450.79 | 66211069.77 | 35815219.71 | 91111572.66 |
October | 33206161.12 | 0.00 | 33206161.12 | 4646583.52 | 0.199102E+09 |
November | 9972625.53 | 0.00 | 9972625.53 | 0.00 | 0.361330E+09 |
December | 1618666.00 | 0.00 | 1618666.00 | 0.00 | 0.403718E+09 |
Annual Sum or Average | 0.102341E+10 | 0.117333E+09 | 0.906075E+09 | 0.840652E+09 | 0.223481E+10 |
Minimum of Months | 1618666.00 | 0.00 | 1618666.00 | 0.00 | 21890681.10 |
Maximum of Months | 0.219951E+09 | 48108939.50 | 0.171842E+09 | 0.240105E+09 | 0.403718E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 5335818.80 | 0.00 | 5335818.80 | 0.00 | 0.380738E+09 |
February | 21304345.52 | 0.00 | 21304345.52 | 0.00 | 0.302115E+09 |
March | 63270965.05 | 18891.72 | 63252073.33 | 8091294.34 | 0.236924E+09 |
April | 0.111285E+09 | 3001051.27 | 0.108284E+09 | 62952755.80 | 0.108503E+09 |
May | 0.176109E+09 | 28156585.09 | 0.147953E+09 | 0.175039E+09 | 42280082.58 |
June | 0.219943E+09 | 48106684.57 | 0.171836E+09 | 0.240095E+09 | 21890613.35 |
July | 0.191766E+09 | 31365797.34 | 0.160400E+09 | 0.204661E+09 | 32926612.09 |
August | 0.123175E+09 | 6499835.46 | 0.116675E+09 | 0.109316E+09 | 54170599.55 |
September | 66387327.10 | 178442.42 | 66208884.68 | 35813083.21 | 91111512.88 |
October | 33205023.58 | 0.00 | 33205023.58 | 4646156.60 | 0.199102E+09 |
November | 9972265.08 | 0.00 | 9972265.08 | 0.00 | 0.361329E+09 |
December | 1618604.93 | 0.00 | 1618604.93 | 0.00 | 0.403717E+09 |
Annual Sum or Average | 0.102337E+10 | 0.117327E+09 | 0.906046E+09 | 0.840614E+09 | 0.223481E+10 |
Minimum of Months | 1618604.93 | 0.00 | 1618604.93 | 0.00 | 21890613.35 |
Maximum of Months | 0.219943E+09 | 48106684.57 | 0.171836E+09 | 0.240095E+09 | 0.403717E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.371470E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401566.14 | 0.280113E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85312817.81 | 0.206023E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259759E+09 | 0.103026E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.384646E+09 | 52266146.79 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.401265E+09 | 34536188.43 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.360983E+09 | 50076964.47 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.257136E+09 | 72781208.79 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.116474E+09 | 94427294.13 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27772359.04 | 0.161320E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351678E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398763E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.189375E+10 | 0.217648E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 34536188.43 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.401265E+09 | 0.398763E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.371470E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401566.14 | 0.280113E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85312817.81 | 0.206023E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259759E+09 | 0.103026E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.384646E+09 | 52266146.79 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.401265E+09 | 34536188.43 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.360983E+09 | 50076964.47 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.257136E+09 | 72781208.79 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.116474E+09 | 94427294.13 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27772359.04 | 0.161320E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351678E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398763E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.189375E+10 | 0.217648E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 34536188.43 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.401265E+09 | 0.398763E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.371470E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401566.14 | 0.280113E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85312817.81 | 0.206023E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259759E+09 | 0.103026E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.384646E+09 | 52266146.79 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.401265E+09 | 34536188.43 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.360983E+09 | 50076964.47 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.257136E+09 | 72781208.79 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.116474E+09 | 94427294.13 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27772359.04 | 0.161320E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351678E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398763E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.189375E+10 | 0.217648E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 34536188.43 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.401265E+09 | 0.398763E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.371470E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401566.14 | 0.280113E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85312817.81 | 0.206023E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259759E+09 | 0.103026E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.384646E+09 | 52266146.79 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.401265E+09 | 34536188.43 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.360983E+09 | 50076964.47 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.257136E+09 | 72781208.79 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.116474E+09 | 94427294.13 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27772359.04 | 0.161320E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351678E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398763E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.189375E+10 | 0.217648E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 34536188.43 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.401265E+09 | 0.398763E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.371470E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401566.14 | 0.280113E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85312817.81 | 0.206023E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259759E+09 | 0.103026E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.384646E+09 | 52266146.79 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.401265E+09 | 34536188.43 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.360983E+09 | 50076964.47 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.257136E+09 | 72781208.79 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.116474E+09 | 94427294.13 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27772359.04 | 0.161320E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351678E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398763E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.189375E+10 | 0.217648E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 34536188.43 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.401265E+09 | 0.398763E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.371470E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401566.14 | 0.280113E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85312817.81 | 0.206023E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259759E+09 | 0.103026E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.384646E+09 | 52266146.79 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.401265E+09 | 34536188.43 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.360983E+09 | 50076964.47 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.257136E+09 | 72781208.79 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.116474E+09 | 94427294.13 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27772359.04 | 0.161320E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351678E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398763E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.189375E+10 | 0.217648E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 34536188.43 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.401265E+09 | 0.398763E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.371470E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401566.14 | 0.280113E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85312817.81 | 0.206023E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259759E+09 | 0.103026E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.384646E+09 | 52266146.79 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.401265E+09 | 34536188.43 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.360983E+09 | 50076964.47 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.257136E+09 | 72781208.79 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.116474E+09 | 94427294.13 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27772359.04 | 0.161320E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351678E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398763E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.189375E+10 | 0.217648E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 34536188.43 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.401265E+09 | 0.398763E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.371470E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401566.14 | 0.280113E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85312817.81 | 0.206023E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259759E+09 | 0.103026E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.384646E+09 | 52266146.79 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.401265E+09 | 34536188.43 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.360983E+09 | 50076964.47 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.257136E+09 | 72781208.79 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.116474E+09 | 94427294.13 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27772359.04 | 0.161320E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351678E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398763E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.189375E+10 | 0.217648E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 34536188.43 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.401265E+09 | 0.398763E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.371470E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401566.14 | 0.280113E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85312817.81 | 0.206023E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259759E+09 | 0.103026E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.384646E+09 | 52266146.79 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.401265E+09 | 34536188.43 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.360983E+09 | 50076964.47 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.257136E+09 | 72781208.79 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.116474E+09 | 94427294.13 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27772359.04 | 0.161320E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351678E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398763E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.189375E+10 | 0.217648E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 34536188.43 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.401265E+09 | 0.398763E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6546105.47 | 597225.44 | 5948880.03 | 0.00 | 0.371470E+09 |
February | 29934670.29 | 7325881.42 | 22608788.87 | 401566.14 | 0.280113E+09 |
March | 0.116348E+09 | 49472675.65 | 66874972.33 | 85312817.81 | 0.206023E+09 |
April | 0.226510E+09 | 0.122207E+09 | 0.104303E+09 | 0.259759E+09 | 0.103026E+09 |
May | 0.305308E+09 | 0.173722E+09 | 0.131586E+09 | 0.384646E+09 | 52266146.79 |
June | 0.320521E+09 | 0.159811E+09 | 0.160711E+09 | 0.401265E+09 | 34536188.43 |
July | 0.297144E+09 | 0.143687E+09 | 0.153457E+09 | 0.360983E+09 | 50076964.47 |
August | 0.223692E+09 | 0.108530E+09 | 0.115162E+09 | 0.257136E+09 | 72781208.79 |
September | 0.116950E+09 | 46298188.78 | 70651973.15 | 0.116474E+09 | 94427294.13 |
October | 49603267.26 | 12029681.11 | 37573586.15 | 27772359.04 | 0.161320E+09 |
November | 12036261.84 | 999940.01 | 11036321.83 | 0.00 | 0.351678E+09 |
December | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 0.398763E+09 |
Annual Sum or Average | 0.170643E+10 | 0.824715E+09 | 0.881713E+09 | 0.189375E+10 | 0.217648E+10 |
Minimum of Months | 1834567.09 | 34967.36 | 1799599.73 | 0.00 | 34536188.43 |
Maximum of Months | 0.320521E+09 | 0.173722E+09 | 0.160711E+09 | 0.401265E+09 | 0.398763E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 765.73 | 13.38 | 1.60 | 11.79 | 0.00 | 0.00 |
February | 6.14 | 642.99 | 73.65 | 19.52 | 54.13 | 0.00 | 0.00 |
March | 104.39 | 442.48 | 216.10 | 73.09 | 143.02 | 0.00 | 0.00 |
April | 470.98 | 222.14 | 484.77 | 209.28 | 275.50 | 0.00 | 0.00 |
May | 571.23 | 85.80 | 518.98 | 197.77 | 321.21 | 0.00 | 0.00 |
June | 683.15 | 47.64 | 594.59 | 218.74 | 375.85 | 0.00 | 0.00 |
July | 562.70 | 68.31 | 498.15 | 157.77 | 340.38 | 0.00 | 0.00 |
August | 404.00 | 109.20 | 384.53 | 129.26 | 255.27 | 0.00 | 0.00 |
September | 191.75 | 184.42 | 227.49 | 73.75 | 153.73 | 0.00 | 0.00 |
October | 30.86 | 385.23 | 93.67 | 20.54 | 73.13 | 0.00 | 0.00 |
November | 1.02 | 734.56 | 35.22 | 9.89 | 25.33 | 0.00 | 0.00 |
December | 0.00 | 816.38 | 3.68 | 0.25 | 3.43 | 0.00 | 0.00 |
Annual Sum or Average | 253.28 | 374.06 | 262.76 | 92.83 | 169.93 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 47.64 | 3.68 | 0.25 | 3.43 | 0.00 | 0.00 |
Maximum of Months | 683.15 | 816.38 | 594.59 | 218.74 | 375.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 9784.50 | 24.44 | 2.23 | 22.21 | 0.00 | 0.00 |
February | 8.33 | 8226.58 | 123.74 | 30.28 | 93.46 | 0.00 | 0.00 |
March | 1605.21 | 5437.19 | 434.39 | 184.71 | 249.68 | 0.00 | 0.00 |
April | 4348.44 | 2437.94 | 873.88 | 471.48 | 402.41 | 0.00 | 0.00 |
May | 5619.51 | 647.64 | 1139.89 | 648.60 | 491.29 | 0.00 | 0.00 |
June | 6056.33 | 399.93 | 1236.58 | 616.55 | 620.03 | 0.00 | 0.00 |
July | 5219.63 | 561.43 | 1109.41 | 536.47 | 572.94 | 0.00 | 0.00 |
August | 3870.28 | 830.62 | 835.17 | 405.20 | 429.97 | 0.00 | 0.00 |
September | 1815.18 | 1465.39 | 451.20 | 178.62 | 272.58 | 0.00 | 0.00 |
October | 458.71 | 3608.28 | 185.20 | 44.91 | 140.28 | 0.00 | 0.00 |
November | 0.00 | 9110.96 | 46.44 | 3.86 | 42.58 | 0.00 | 0.00 |
December | 0.00 | 10142.66 | 6.85 | 0.13 | 6.72 | 0.00 | 0.00 |
Annual Sum or Average | 2429.60 | 4367.54 | 541.10 | 261.52 | 279.59 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 399.93 | 6.85 | 0.13 | 6.72 | 0.00 | 0.00 |
Maximum of Months | 6056.33 | 10142.66 | 1236.58 | 648.60 | 620.03 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.205093E+10 | 35842358.65 | 4275154.85 | 31567203.80 | 0.00 | 0.00 |
February | 14844055.29 | 0.155553E+10 | 0.178164E+09 | 47212141.19 | 0.130951E+09 | 0.00 | 0.00 |
March | 0.279588E+09 | 0.118513E+10 | 0.578814E+09 | 0.195752E+09 | 0.383061E+09 | 0.00 | 0.00 |
April | 0.122079E+10 | 0.575792E+09 | 0.125653E+10 | 0.542445E+09 | 0.714088E+09 | 0.00 | 0.00 |
May | 0.152997E+10 | 0.229811E+09 | 0.139005E+10 | 0.529709E+09 | 0.860339E+09 | 0.00 | 0.00 |
June | 0.177071E+10 | 0.123479E+09 | 0.154119E+10 | 0.566970E+09 | 0.974216E+09 | 0.00 | 0.00 |
July | 0.150715E+10 | 0.182950E+09 | 0.133425E+10 | 0.422559E+09 | 0.911687E+09 | 0.00 | 0.00 |
August | 0.108206E+10 | 0.292469E+09 | 0.102994E+10 | 0.346222E+09 | 0.683716E+09 | 0.00 | 0.00 |
September | 0.497013E+09 | 0.478010E+09 | 0.589644E+09 | 0.191164E+09 | 0.398480E+09 | 0.00 | 0.00 |
October | 82647471.17 | 0.103180E+10 | 0.250883E+09 | 55003396.64 | 0.195879E+09 | 0.00 | 0.00 |
November | 2653737.73 | 0.190399E+10 | 91293072.63 | 25625994.25 | 65667078.39 | 0.00 | 0.00 |
December | 0.00 | 0.218659E+10 | 9869442.99 | 681301.28 | 9188141.71 | 0.00 | 0.00 |
Annual Sum or Average | 0.798743E+10 | 0.117965E+11 | 0.828646E+10 | 0.292762E+10 | 0.535884E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.123479E+09 | 9869442.99 | 681301.28 | 9188141.71 | 0.00 | 0.00 |
Maximum of Months | 0.177071E+10 | 0.218659E+10 | 0.154119E+10 | 0.566970E+09 | 0.974216E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.262068E+11 | 65461054.70 | 5972254.40 | 59488800.30 | 0.00 | 0.00 |
February | 20144793.09 | 0.199017E+11 | 0.299347E+09 | 73258814.24 | 0.226088E+09 | 0.00 | 0.00 |
March | 0.429939E+10 | 0.145630E+11 | 0.116348E+10 | 0.494727E+09 | 0.668750E+09 | 0.00 | 0.00 |
April | 0.112712E+11 | 0.631915E+10 | 0.226510E+10 | 0.122207E+10 | 0.104303E+10 | 0.00 | 0.00 |
May | 0.150513E+11 | 0.173463E+10 | 0.305308E+10 | 0.173722E+10 | 0.131586E+10 | 0.00 | 0.00 |
June | 0.156980E+11 | 0.103663E+10 | 0.320521E+10 | 0.159811E+10 | 0.160711E+10 | 0.00 | 0.00 |
July | 0.139802E+11 | 0.150373E+10 | 0.297144E+10 | 0.143687E+10 | 0.153457E+10 | 0.00 | 0.00 |
August | 0.103662E+11 | 0.222473E+10 | 0.223692E+10 | 0.108530E+10 | 0.115162E+10 | 0.00 | 0.00 |
September | 0.470494E+10 | 0.379828E+10 | 0.116950E+10 | 0.462982E+09 | 0.706520E+09 | 0.00 | 0.00 |
October | 0.122861E+10 | 0.966442E+10 | 0.496033E+09 | 0.120297E+09 | 0.375736E+09 | 0.00 | 0.00 |
November | 0.00 | 0.236156E+11 | 0.120363E+09 | 9999400.12 | 0.110363E+09 | 0.00 | 0.00 |
December | 0.00 | 0.271661E+11 | 18345670.88 | 349673.56 | 17995997.32 | 0.00 | 0.00 |
Annual Sum or Average | 0.766199E+11 | 0.137735E+12 | 0.170643E+11 | 0.824715E+10 | 0.881713E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.103663E+10 | 18345670.88 | 349673.56 | 17995997.32 | 0.00 | 0.00 |
Maximum of Months | 0.156980E+11 | 0.271661E+11 | 0.320521E+10 | 0.173722E+10 | 0.160711E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.116089E+10 | -0.107077E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -90115060.8 | 59.95 | 0.00 | 0.00 |
February | 0.106502E+10 | -983743441.1 | 0.00 | 0.00 | 672.00 | 0.00 | -81280044.1 | 59.95 | 0.00 | 0.00 |
March | 0.123944E+10 | -0.114981E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -89629810.7 | 59.95 | 0.00 | 0.00 |
April | 0.115409E+10 | -0.106814E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -85948879.3 | 59.95 | 0.00 | 0.00 |
May | 0.118856E+10 | -0.110281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -85743742.5 | 59.95 | 0.00 | 0.00 |
June | 0.113549E+10 | -0.105913E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -76359563.2 | 59.95 | 0.00 | 0.00 |
July | 0.106223E+10 | -985661091.6 | 0.00 | 0.00 | 744.00 | 0.00 | -76564784.4 | 59.95 | 0.00 | 0.00 |
August | 0.111153E+10 | -0.103339E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -78136367.8 | 59.95 | 0.00 | 0.00 |
September | 0.104050E+10 | -957154100.1 | 0.00 | 0.00 | 720.00 | 0.00 | -83348650.2 | 59.95 | 0.00 | 0.00 |
October | 0.106734E+10 | -977972874.7 | 0.00 | 0.00 | 744.00 | 0.00 | -89368434.8 | 59.95 | 0.00 | 0.00 |
November | 0.105964E+10 | -972404998.8 | 0.00 | 0.00 | 720.00 | 0.00 | -87235746.9 | 59.95 | 0.00 | 0.00 |
December | 0.114350E+10 | -0.105339E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -90111321.6 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.134282E+11 | -0.124144E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.101384E+10 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.104050E+10 | -0.114981E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -90115060.8 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.123944E+10 | -957154100.1 | 0.00 | 0.00 | 744.00 | 0.00 | -76359563.2 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.98 | 0.94 | 31-JAN-11:30 | 27.87 | 2.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.96 | 0.88 | 23-FEB-11:09 | 64.78 | 6.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.94 | 0.88 | 05-MAR-10:20 | 121.25 | 9.31 | 0.00 | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.93 | 0.88 | 01-APR-09:39 | 149.93 | 10.18 | 0.00 | 92.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.92 | 0.88 | 01-MAY-06:00 | 169.43 | 10.47 | 0.00 | 181.17 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.92 | 0.88 | 01-JUN-06:19 | 518.28 | 10.76 | 0.00 | 282.17 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.92 | 0.88 | 01-JUL-05:30 | 195.34 | 10.93 | 0.00 | 244.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.92 | 0.88 | 01-AUG-06:40 | 168.42 | 10.61 | 0.00 | 155.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.93 | 0.88 | 01-SEP-07:49 | 126.00 | 9.51 | 0.00 | 42.50 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.95 | 0.88 | 01-OCT-09:20 | 89.65 | 7.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.98 | 0.92 | 06-NOV-13:30 | 38.36 | 2.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 1.00 | 0.98 | 04-DEC-11:30 | 8.80 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.93 | 191.82 | 9.31 | 0.00 | 1052.83 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 71.17 | 0.92 | 0.88 | 8.80 | 0.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 0.98 | 518.28 | 10.93 | 0.00 | 282.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.95 | 0.89 | 31-JAN-11:30 | 51.00 | 13.25 | 0.00 | 0.00 | 24.91 | 12.93 | 0.00 | 0.00 |
February | 205.83 | 0.89 | 0.74 | 28-FEB-15:20 | 120.24 | 18.36 | 22.50 | 0.00 | 62.17 | 18.09 | 9.83 | 0.00 |
March | 329.50 | 0.79 | 0.61 | 12-MAR-17:10 | 347.72 | 23.69 | 172.33 | 39.67 | 145.64 | 22.57 | 163.00 | 9.17 |
April | 421.83 | 0.74 | 0.61 | 01-APR-15:20 | 604.68 | 24.05 | 245.50 | 148.83 | 470.20 | 24.18 | 280.50 | 95.83 |
May | 545.00 | 0.74 | 0.61 | 01-MAY-16:00 | 294.00 | 20.83 | 259.17 | 123.83 | 295.74 | 21.88 | 330.67 | 94.17 |
June | 583.50 | 0.73 | 0.61 | 01-JUN-14:30 | 315.99 | 20.65 | 285.50 | 176.50 | 226.35 | 21.58 | 352.33 | 85.83 |
July | 562.83 | 0.74 | 0.61 | 02-JUL-14:39 | 305.42 | 20.64 | 257.00 | 150.67 | 280.35 | 21.59 | 315.17 | 84.00 |
August | 467.17 | 0.75 | 0.61 | 01-AUG-14:30 | 419.95 | 22.49 | 232.50 | 110.00 | 346.99 | 23.07 | 262.83 | 66.00 |
September | 356.33 | 0.79 | 0.61 | 01-SEP-15:20 | 426.36 | 24.36 | 184.00 | 58.00 | 155.81 | 22.74 | 187.50 | 12.83 |
October | 265.50 | 0.87 | 0.66 | 01-OCT-15:30 | 167.24 | 21.08 | 55.50 | 10.50 | 69.95 | 18.89 | 22.33 | 0.00 |
November | 135.83 | 0.94 | 0.83 | 06-NOV-13:30 | 71.04 | 15.42 | 0.67 | 0.00 | 36.56 | 15.05 | 0.17 | 0.00 |
December | 71.17 | 0.98 | 0.95 | 05-DEC-11:30 | 18.01 | 7.02 | 0.00 | 0.00 | 8.48 | 6.67 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.78 | 325.64 | 21.11 | 1714.67 | 818.00 | 235.53 | 21.18 | 1924.33 | 447.83 | ||
Minimum of Months | 71.17 | 0.73 | 0.61 | 18.01 | 7.02 | 0.00 | 0.00 | 8.48 | 6.67 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.98 | 0.95 | 604.68 | 24.36 | 285.50 | 176.50 | 470.20 | 24.18 | 352.33 | 95.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142375E+11 | 26576.37 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118797E+11 | 26576.37 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115494E+11 | 26576.37 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.579873E+10 | 26576.37 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151120E+10 | 26576.37 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 64236974.87 | 26576.37 | 01-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1068548.21 | 488.51 | 05-JUL-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75516555.32 | 26576.37 | 31-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.253496E+10 | 26576.37 | 05-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.728175E+10 | 26576.37 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121885E+11 | 26576.37 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140744E+11 | 26576.37 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.811971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1068548.21 | 488.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142375E+11 | 26576.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.506497E+11 | 64705.37 | 01-JAN-00:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.405532E+11 | 64705.37 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350899E+11 | 64705.37 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138041E+11 | 64705.37 | 01-APR-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.508100E+09 | 59641.21 | 03-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.245889E+10 | 64705.37 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210849E+11 | 64705.37 | 22-OCT-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.430796E+11 | 64705.37 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.512375E+11 | 64705.37 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.512375E+11 | 64705.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143848E+12 | 100200.39 | 12-JAN-00:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118517E+12 | 100200.39 | 23-FEB-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108323E+12 | 100200.39 | 02-MAR-04:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.458095E+11 | 98198.16 | 02-APR-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.236992E+09 | 13432.14 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.582601E+11 | 81012.18 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101769E+12 | 87223.51 | 10-NOV-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140649E+12 | 100200.39 | 22-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.717414E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143848E+12 | 100200.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 53.67 | 53.67 | 0.06 | 13-MAY-15:00 | 0.06 | 0.00 |
June | 0.00 | 0.00 | 0.538713E+09 | 0.517379E+09 | 5460.68 | 30-JUN-15:00 | 5039.90 | 0.00 |
July | 0.00 | 0.00 | 0.144949E+10 | 0.137253E+10 | 13630.88 | 25-JUL-05:03 | 8146.51 | 0.00 |
August | 0.00 | 0.00 | 0.527469E+09 | 0.503122E+09 | 13248.92 | 03-AUG-05:03 | 9348.93 | 0.00 |
September | 0.00 | 0.00 | 1.63 | 1.55 | 0.00 | 02-SEP-14:40 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.251567E+10 | 0.239303E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144949E+10 | 0.137253E+10 | 13630.88 | 9348.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 53888071.28 | 53624491.29 | 3548.73 | 29-JUL-16:00 | 3548.73 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 53888071.28 | 53624491.29 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 53888071.28 | 53624491.29 | 3548.73 | 3548.73 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.618887E+09 | 0.08 | 231.07 | 01-JAN-00:03 | 0.08 |
February | 0.558856E+09 | 0.08 | 231.07 | 01-FEB-00:03 | 0.08 |
March | 0.588040E+09 | 0.07 | 231.07 | 01-MAR-00:02 | 0.08 |
April | 0.338932E+09 | 0.04 | 231.07 | 01-APR-00:10 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 7278576.99 | 0.00 | 231.07 | 30-SEP-01:40 | 0.08 |
October | 0.458365E+09 | 0.06 | 231.07 | 01-OCT-00:10 | 0.08 |
November | 0.598923E+09 | 0.08 | 231.07 | 01-NOV-00:05 | 0.08 |
December | 0.618887E+09 | 0.08 | 231.07 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.378817E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.618887E+09 | 0.08 | 231.07 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.103048E+10 | 0.64 | 927.41 | 02-JAN-14:20 | 0.93 |
February | 0.945265E+09 | 0.64 | 927.41 | 01-FEB-10:20 | 0.93 |
March | 0.107436E+10 | 0.58 | 927.41 | 01-MAR-15:50 | 0.93 |
April | 0.959980E+09 | 0.44 | 927.41 | 01-APR-06:10 | 0.93 |
May | 0.970737E+09 | 0.38 | 927.41 | 01-MAY-12:40 | 0.92 |
June | 0.955959E+09 | 0.37 | 927.41 | 03-JUN-06:05 | 0.92 |
July | 0.920397E+09 | 0.34 | 927.41 | 03-JUL-12:00 | 0.92 |
August | 0.993507E+09 | 0.37 | 927.41 | 01-AUG-06:10 | 0.92 |
September | 0.934655E+09 | 0.38 | 927.41 | 05-SEP-17:00 | 0.92 |
October | 0.958413E+09 | 0.42 | 927.41 | 02-OCT-15:20 | 0.92 |
November | 0.959824E+09 | 0.59 | 927.41 | 01-NOV-06:50 | 0.93 |
December | 0.101562E+10 | 0.63 | 927.41 | 01-DEC-09:30 | 0.93 |
Annual Sum or Average | 0.117192E+11 | 0.48 | |||
Minimum of Months | 0.920397E+09 | 0.34 | 927.41 | 0.92 | |
Maximum of Months | 0.107436E+10 | 0.64 | 927.41 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137523E+10 | 0.69 | 1355.20 | 01-JAN-00:08 | 0.93 |
February | 0.117560E+10 | 0.66 | 1355.20 | 01-FEB-00:03 | 0.93 |
March | 0.117259E+10 | 0.63 | 1355.20 | 01-MAR-00:02 | 0.93 |
April | 0.782974E+09 | 0.48 | 1355.20 | 01-APR-00:23 | 0.93 |
May | 0.567964E+09 | 0.24 | 1249.13 | 03-MAY-05:08 | 0.92 |
June | 0.558124E+09 | 0.22 | 542.08 | 01-JUN-06:10 | 0.56 |
July | 0.536658E+09 | 0.21 | 542.08 | 01-JUL-06:10 | 0.55 |
August | 0.579590E+09 | 0.22 | 542.08 | 01-AUG-06:10 | 0.56 |
September | 0.578436E+09 | 0.28 | 1355.20 | 30-SEP-05:01 | 0.92 |
October | 0.894886E+09 | 0.55 | 1355.20 | 22-OCT-03:03 | 0.93 |
November | 0.122698E+10 | 0.66 | 1355.20 | 01-NOV-05:01 | 0.93 |
December | 0.137446E+10 | 0.69 | 1355.20 | 01-DEC-00:03 | 0.93 |
Annual Sum or Average | 0.108235E+11 | 0.46 | |||
Minimum of Months | 0.536658E+09 | 0.21 | 542.08 | 0.55 | |
Maximum of Months | 0.137523E+10 | 0.69 | 1355.20 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.103048E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.945265E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.107436E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.959980E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.970737E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.107805E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.124586E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.111303E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.934655E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.958413E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.959824E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.101562E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.122863E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.934655E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.124586E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.137523E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.117560E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.117259E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.782974E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.567964E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.558124E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.551087E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.579590E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.578436E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.894886E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.122698E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.137446E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.108379E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.551087E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.137523E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.103048E+10 | 0.00 | 0.142375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.945265E+09 | 0.00 | 0.118797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107436E+10 | 0.00 | 0.115494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.959980E+09 | 0.00 | 0.579873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.970737E+09 | 53.67 | 0.151120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.955959E+09 | 0.538713E+09 | 64236974.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.920397E+09 | 0.144949E+10 | 1068548.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.993507E+09 | 0.527469E+09 | 75516555.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.934655E+09 | 1.63 | 0.253496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.958413E+09 | 0.00 | 0.728175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.959824E+09 | 0.00 | 0.121885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101562E+10 | 0.00 | 0.140744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117192E+11 | 0.251567E+10 | 0.811971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.920397E+09 | 0.00 | 1068548.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107436E+10 | 0.144949E+10 | 0.142375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137523E+10 | 0.00 | 0.506497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117560E+10 | 0.00 | 0.405532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117259E+10 | 0.00 | 0.350899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.782974E+09 | 0.00 | 0.138041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.567964E+09 | 0.00 | 0.508100E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.558124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.536658E+09 | 53888071.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.579590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.578436E+09 | 0.00 | 0.245889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.894886E+09 | 0.00 | 0.210849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122698E+10 | 0.00 | 0.430796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137446E+10 | 0.00 | 0.512375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108235E+11 | 53888071.28 | 0.258466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.536658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137523E+10 | 53888071.28 | 0.512375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.103048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.945265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.959980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.970737E+09 | 0.00 | 0.00 | 0.00 | 12.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.955959E+09 | 0.00 | 0.00 | 0.00 | 0.122093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.920397E+09 | 0.00 | 0.00 | 0.00 | 0.325460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.993507E+09 | 0.00 | 0.00 | 0.00 | 0.119523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.934655E+09 | 0.00 | 0.00 | 0.00 | 0.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.958413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.959824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117192E+11 | 0.00 | 0.00 | 0.00 | 0.567076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.920397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107436E+10 | 0.00 | 0.00 | 0.00 | 0.325460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.782974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.567964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.558124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.536658E+09 | 0.00 | 0.00 | 0.00 | 14429155.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.579590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.578436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.894886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108235E+11 | 0.00 | 0.00 | 0.00 | 14429155.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.536658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137523E+10 | 0.00 | 0.00 | 0.00 | 14429155.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457359E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370023E+10 | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375792E+10 | 0.00 | 0.00 | 0.13 |
April | 60661373.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213591E+10 | 0.00 | 0.00 | 0.13 |
May | 0.644328E+09 | 0.00 | 0.00 | 820.94 | 0.00 | 0.608986E+09 | 8557757.81 | 0.00 | 0.13 |
June | 0.297660E+09 | 1512423.51 | 0.00 | 2072487.69 | 0.00 | 0.00 | 0.185771E+10 | 0.00 | 0.40 |
July | 87127562.81 | 12705355.32 | 0.00 | 3837886.56 | 0.00 | 0.00 | 0.226330E+10 | 0.00 | 0.53 |
August | 0.439378E+09 | 2730.17 | 0.00 | 2655975.58 | 0.00 | 13072033.43 | 0.215767E+10 | 0.00 | 0.41 |
September | 0.529561E+09 | 0.00 | 0.00 | 4524.49 | 0.00 | 0.125978E+10 | 13648623.71 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286158E+10 | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433681E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481450E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.205872E+10 | 14220509.01 | 0.00 | 8571695.25 | 0.00 | 0.280624E+11 | 0.630088E+10 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.644328E+09 | 12705355.32 | 0.00 | 3837886.56 | 0.00 | 0.481450E+10 | 0.226330E+10 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158353E+11 | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124462E+11 | 0.00 | 0.00 | 0.18 |
March | 0.786534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114111E+11 | 0.00 | 0.00 | 0.19 |
April | 0.343413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271307E+10 | 0.00 | 0.00 | 0.18 |
May | 0.309597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.342677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
July | 0.345267E+10 | 560016.92 | 0.00 | 34532.68 | 5900790.32 | 0.00 | 62426725.40 | 0.00 | 0.18 |
August | 0.457748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
September | 0.456106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343076E+09 | 0.00 | 0.00 | 0.18 |
October | 0.212644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661582E+10 | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149990E+11 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168265E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.254610E+11 | 560016.92 | 0.00 | 34532.68 | 5900790.32 | 0.811901E+11 | 62426725.40 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.457748E+10 | 560016.92 | 0.00 | 34532.68 | 5900790.32 | 0.168265E+11 | 62426725.40 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.140916E+12 | 0.591763E+11 | 0.00 | 0.204089E+11 | 0.445687E+11 |
February | 0.617726E+10 | 0.484352E+11 | 0.00 | 0.161465E+11 | 0.369100E+11 |
March | 0.403669E+12 | 0.661660E+11 | 0.00 | 0.159556E+11 | 0.340797E+11 |
April | 0.781413E+12 | 0.485315E+11 | 0.00 | 0.834383E+10 | 0.148526E+11 |
May | 0.101482E+13 | 0.213882E+11 | 0.00 | 0.435785E+10 | 0.802095E+09 |
June | 0.106987E+13 | 0.176868E+11 | 0.00 | 0.558270E+10 | 0.686112E+09 |
July | 0.980811E+12 | 0.212338E+11 | 0.00 | 0.586342E+10 | 0.184377E+10 |
August | 0.726824E+12 | 0.287550E+11 | 0.00 | 0.719430E+10 | 0.678619E+09 |
September | 0.323739E+12 | 0.225407E+11 | 0.00 | 0.670717E+10 | 0.206406E+10 |
October | 0.722795E+11 | 0.479647E+11 | 0.00 | 0.116039E+11 | 0.200684E+11 |
November | -0.959613E+11 | 0.243512E+11 | 0.00 | 0.193358E+11 | 0.350632E+11 |
December | -0.167144E+12 | 0.483020E+11 | 0.00 | 0.216410E+11 | 0.441185E+11 |
Annual Sum or Average | 0.497558E+13 | 0.454531E+12 | 0.00 | 0.143141E+12 | 0.235736E+12 |
Minimum of Months | -0.167144E+12 | 0.176868E+11 | 0.00 | 0.435785E+10 | 0.678619E+09 |
Maximum of Months | 0.106987E+13 | 0.661660E+11 | 0.00 | 0.216410E+11 | 0.445687E+11 |