Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:19:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1683.77 | 348.24 | 348.24 |
Net Site Energy | 1683.77 | 348.24 | 348.24 |
Total Source Energy | 2579.16 | 533.42 | 533.42 |
Net Source Energy | 2579.16 | 533.42 | 533.42 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1321.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 110.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 11.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 361.96 | 1321.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1321.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 110.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 32.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 11.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1321.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 7.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 110.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 33.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 11.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 35.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.86 | 273.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 74.86 | 273.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 35.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.86 | 273.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 74.86 | 273.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 361.957 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 361.957 | 100.00 |
Total On-Site and Utility Electric Sources | 361.957 | 100.00 |
Total Electricity End Uses | 361.957 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 81.00 |
Time Setpoint Not Met During Occupied Cooling | 3.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3152.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:50 | 18-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 370256.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10165.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8207.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4314.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1228.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 33951.80 | 370256.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 370256.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10165.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8207.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2009.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1228.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1432.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 351.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 196.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 104.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1146.32 | 1432.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 296.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 72.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 237.08 | 296.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 296.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 72.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 237.08 | 296.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.970058 |
ZONE2 FINE STORAGE DIRECT AIR | 1.73 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 5.62 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 5.62 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 219568.75 |
PSZ-OFFICE HEATING COIL | 26793.89 |
PSZ-FINE STORAGE HEATING COIL | 69198.39 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 219568.76 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.970058 | 0.970058 | 0.970058 | 0.970058 | 0.970058 | 0.970058 | 1.00 | 1.000000 | 0.970058 |
PSZ-FINE STORAGE | 1.73 | 1.73 | 1.73 | 1.73 | 1.73 | 1.73 | 1.00 | 1.00 | 1.73 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.970058 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.73 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.970058 | 1074.01 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.73 | 1848.23 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.970058 | 0.970058 | 0.970058 | 0.970058 | 18509.65 | 26793.89 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.73 | 1.73 | 1.73 | 1.14 | 42891.48 | 69198.39 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.970060 | 0.485029 | 0.646707 | 18509.65 | 9254.83 | 0.794960 | 0.794960 |
PSZ-FINE STORAGE COOLING COIL | 1.73 | 0.863620 | 1.15 | 42891.48 | 21445.74 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3574 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3694 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.946 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1333 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5514E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.798 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.608 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3395 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.423 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.06 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
2 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
3 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
4 | 2 | 0.92894805E-09 | 0.33911764E-13 | 0.21779261E-14 | 0.0000000 |
5 | 1 | -5.2160150 | 0.41827095E-04 | -0.44821328E-04 | 0.18401191E-09 |
6 | 0 | 5.5734381 | 0.35738136 | 0.35746801 | |
7 | 4 | 0.80462617E-12 | 0.82840410E-16 | -0.20078756E-14 | 0.11271485E-15 |
8 | 3 | -0.39242815E-03 | 0.26180773E-06 | -0.56999769E-04 | 0.15438257E-12 |
9 | 2 | 1.7577325 | 0.56772723E-02 | 1.1542901 | -0.75235290E-04 |
10 | 1 | -7.1048256 | 0.14632850 | -17.186369 | 0.33689683 |
11 | 0 | 5.5924660 | 0.92974441E-01 | 16.277116 | |
12 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
13 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
14 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
15 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
16 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.9455516 | 2.9455516 | 2.9455516 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.31875017E-08 | -0.23223167E-14 | 0.11745088E-14 | -0.42051331E-16 |
55 | 6 | 0.38616340E-05 | 0.25494915E-08 | 0.31950331E-02 | -0.26802615E-04 |
56 | 5 | -0.27022284E-03 | 0.15072689E-05 | -0.22401801 | 0.19587403E-02 |
57 | 4 | 0.61670379E-02 | 0.68550054E-04 | 4.8344327 | -0.45311958E-01 |
58 | 3 | -0.54002887E-01 | 0.54467183E-03 | -38.049021 | 0.39895888 |
59 | 2 | 0.19154071 | 0.90547994E-03 | 116.53767 | -1.4186579 |
60 | 1 | -0.27632409 | 0.27557907E-03 | -143.93893 | 2.0495597 |
61 | 0 | 0.13468807 | 0.66882102E-05 | 60.838472 | |
62 | 7 | -0.77687407E-08 | 0.22327722E-15 | -0.37072247E-14 | 0.17899991E-16 |
63 | 6 | 0.20649052E-05 | 0.10720148E-08 | 0.32011002E-02 | -0.26853511E-04 |
64 | 5 | -0.12245401E-03 | 0.62775152E-06 | -0.22436262 | 0.19617821E-02 |
65 | 4 | 0.26426329E-02 | 0.28408139E-04 | 4.8401680 | -0.45367094E-01 |
66 | 3 | -0.22645990E-01 | 0.22478354E-03 | -38.081398 | 0.39931679 |
67 | 2 | 0.79613263E-01 | 0.37221057E-03 | 116.60066 | -1.4195005 |
68 | 1 | -0.11438919 | 0.11271005E-03 | -143.97600 | 2.0501690 |
69 | 0 | 0.55641142E-01 | 0.27215667E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.25659737E-14 | 0.20825084E-15 | 0.74747876E-12 | 0.12362927E-15 |
85 | 3 | -0.54038165E-04 | 0.45238042E-06 | -0.37328678E-03 | 0.14344535E-12 |
86 | 2 | 1.1198054 | 0.10013958E-01 | 1.7123825 | -0.71564441E-04 |
87 | 1 | -16.966117 | 0.26145347 | -7.1648294 | 0.32817431 |
88 | 0 | 16.285382 | 0.16754891 | 5.8918369 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | 34 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
5 | SKYLIGHT_U_0.47_SHGC_0.4 | 38 | 1 | VerySmooth | 2.672 | 2.672 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.555 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.40629E-002 | 0.31435 | 0.46917 | 0.46917 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11822 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.553 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 3.833E-002 | 1.618E-004 | 2.498E-004 | 0.137 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.195 | 1.399E-004 | 8.913E-005 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 1.834 | 5.723E-004 | 3.738E-004 | 0.187 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0426E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7455E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6964E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8300E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9108E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3918E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0880E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2172E-004 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5266E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0600E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1822E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1637E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1355E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8576E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9979E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4455E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2037E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5775E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7133E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1756E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3627E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1682E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1771E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0426E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0171E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8900E-004 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5219E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8046E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6087E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0384E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.7783E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.8899E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.1522E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.1921E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.9708E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.9477E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9807E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.2338E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.0432E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.4224E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.5042E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.3900E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.0746E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.3415E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.1742E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.0089E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.4989E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.9551E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.1362E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1153E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7899E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.3398E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.7385E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1881E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.6900E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.9620E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.2292E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1190E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.5968E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3359E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.7384E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1881E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9371.24709 | 11245.49651 | 0.80838 | 0.97006 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53623E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10973.17410 | 13167.80893 | 0.32296 | 0.38755 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 21403.93559 | 25684.72271 | 1.43937 | 1.72724 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 34862.05830 | 41834.46996 | 0.86415 | 1.03698 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 182973.96286 | 219568.75543 | 4.68652 | 5.62383 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14031.89 | 0.97006 | 0.97006 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14053.98 | 0.38755 | 0.38755 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 31485.81 | 1.72724 | 1.72724 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 49723.90 | 1.03698 | 1.03698 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97006 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.72724 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.62383 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 5.62383 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 219568.75014 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 219568.75543 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97006 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97006 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97006 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97006 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97006 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.97006 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.72724 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.72724 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.72724 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.72724 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.72724 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.72724 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.97006 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.72724 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97006 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97006 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1074.00854 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97006 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97006 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97006 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97006 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97006 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48503 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64671 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18509.65000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9254.82500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79496 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79496 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18509.65000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26793.88999 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26793.88999 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.72724 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.72724 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1848.22855 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.72724 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.72724 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.72724 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13998 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.72724 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.86362 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.15149 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42891.48000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21445.74000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42891.48000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 69198.38527 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 69198.38527 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 17756.5 | 11.79 | 11.52 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 41548.9 | 12.27 | 11.99 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2140879093 | 0.1847209793 | Pass | Pass | 0.3735964586 | 1.2458221392 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4653341873 | 0.4180418997 | Pass | Pass | 0.1474442784 | 0.3878862494 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.3060435227E-005 | 1.3480732308E-004 | Pass | Pass | 1.8658960654E-002 | 1.9606959519E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8333.70 | 820.28 | 0.00 | 88.21 | 337.82 | 9580.04 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.131 | 0.133 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.055 | 0.055 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.176 | 0.180 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.341 | 0.357 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.943 | 0.380 | 0.418 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.943 | 0.380 | 0.418 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.943 | 0.380 | 0.418 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.943 | 0.380 | 0.418 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.003 | 0.460 | 0.479 | |||||||||||||||||
North Total or Average | 6.51 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.268 | 0.480 | 0.495 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 31.46 | 0.0000 | Y | 9.75 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 25.09 | 0.0000 | Y | 48.75 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 24.55 | 0.0000 | Y | 52.47 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 110.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.12 | 11383.89 | 1320.53 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 42.24 | 42.24 | 0.98 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.63 | 62.93 | 50.87 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.63 | 49.46 | 10.13 | |
Exterior Lighting Total | 5520.82 | 61.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18509.65 | 14714.43 | 3795.22 | 0.79 | 3.82 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42891.48 | 30070.36 | 12821.12 | 0.70 | 3.81 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 17756.5 | 11.79 | 11.52 | ||||
PSZ-FINE STORAGE COOLING COIL | 41548.9 | 12.27 | 11.99 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 219568.75 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26793.89 | 0.81 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 69198.39 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.62 | 522.51 | 92.91 | 1.00 | 3.12 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1074.01 | 1107.16 | 1.00 | 1.41 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.73 | 1848.23 | 1070.05 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9371.25 | 11245.50 | 47.47 | 0.808 | 0.970 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00856 | 29.72 | 0.01536 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 21403.94 | 25684.72 | 18.43 | 1.439 | 1.727 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00939 | 31.09 | 0.01536 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 31.43 | 0.01543 | 31.09 | 0.01536 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10973.17 | 13167.81 | 55.59 | 0.323 | 0.388 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00766 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 34862.06 | 41834.47 | 30.02 | 0.864 | 1.037 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00644 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 182973.96 | 219568.76 | 68.51 | 4.687 | 5.624 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00534 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.97 | 0.97 | 0.39 | 0.39 | 0.9701 | 0.9701 | 0.9701 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.73 | 1.73 | 1.04 | 1.04 | 1.7272 | 1.7272 | 1.7272 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 219568.750 | 219568.750 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 219568.75 | 219568.75 | 5.623830 | 9.99 | 7.06 | 0.00533964 | 43.33 | 21.59 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 9.99 | 0.00533964 | 67.0073 | 219568.76 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18509.650 | 14714.431 | 0.970060 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 9254.83 | 7674.04 | 0.646707 | 25.50 | 17.07 | 0.00927852 | 12.00 | 10.84 | 0.00800000 | 30.14 | 0.01536312 | 22.84 | 15.8162 | 23.90 | 0.00855977 | 44.2158 | 9353.08 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26793.890 | 26793.890 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26793.89 | 26793.89 | 0.970058 | 16.07 | 11.41 | 0.00689057 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 10.5442 | 21.10 | 0.00766017 | 46.9740 | 10973.17 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 42891.480 | 30070.359 | 1.727240 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21445.74 | 15506.28 | 1.151493 | 28.71 | 19.33 | 0.01086314 | 12.00 | 10.84 | 0.00800000 | 31.20 | 0.01536508 | 23.13 | 36.8835 | 26.70 | 0.00939394 | 41.0291 | 21389.98 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 69198.385 | 69198.385 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 69198.39 | 69198.39 | 1.727240 | 5.29 | 4.24 | 0.00494297 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 24.5890 | 15.55 | 0.00643689 | 56.0074 | 34862.06 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 219568.750 | 219568.750 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 5.623830 | 6.45928235 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 219568.75 | 219568.75 | 1.0000 | 6.45928235 | 5.623830 | 9.99 | 7.06 | 0.00533964 | 23496.1 | 43.33 | 21.59 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 219568.75 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 9.99 | 0.00533964 | 9.99 | 0.00533964 | 67.0073 | 219568.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18509.650 | 14714.431 | 0.970060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0883 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.970058 | 1.11416613 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 9254.83 | 7674.04 | 1.0000 | 0.74277871 | 0.646707 | 25.50 | 17.07 | 0.00927852 | 49268.9 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9254.83 | 30.14 | 0.01536312 | 22.84 | 0.10228463 | 15.8162 | 23.90 | 0.00855977 | 23.90 | 0.00855977 | 44.2158 | 9353.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26793.890 | 26793.890 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.970058 | 1.11416613 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26793.89 | 26793.89 | 1.0000 | 1.11416613 | 0.970058 | 16.07 | 11.41 | 0.00689057 | 33584.4 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26793.89 | -26.20 | 0.00036134 | -26.20 | 0.10228463 | 10.5442 | 21.05 | 0.00766017 | 21.10 | 0.00766017 | 46.9740 | 10973.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42891.480 | 30070.359 | 1.727240 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0340 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.727240 | 1.98383168 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 21445.74 | 15506.28 | 1.0000 | 1.32255438 | 1.151493 | 28.71 | 19.33 | 0.01086314 | 56600.6 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21445.74 | 31.20 | 0.01536508 | 23.13 | 0.42471127 | 36.8835 | 26.70 | 0.00939394 | 26.70 | 0.00939394 | 41.0291 | 21389.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 69198.385 | 69198.385 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.727240 | 1.98383168 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 69198.39 | 69198.39 | 1.0000 | 1.98383168 | 1.727240 | 5.29 | 4.24 | 0.00494297 | 17723.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69198.39 | -26.20 | 0.00036134 | -26.20 | 0.42471127 | 24.5890 | 15.55 | 0.00643689 | 15.55 | 0.00643689 | 56.0074 | 34862.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 0.97 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.73 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2922.83 | 2893.50 | 2334.83 |
ZONE2 FINE STORAGE | 3298.67 | 3189.17 | 2899.33 |
ZONE3 BULK STORAGE | 3402.50 | 3281.50 | 3096.50 |
Facility | 3474.17 | 3331.67 | 3152.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 137.17 | 3.50 | 63.33 | 3.50 |
ZONE2 FINE STORAGE | 500.33 | 2.17 | 22.17 | 0.00 |
ZONE3 BULK STORAGE | 12.67 | 0.00 | 8.17 | 0.00 |
Facility | 602.50 | 5.67 | 81.00 | 3.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.640 | 0.270 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.470 | 0.159 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.146 | 0.000 | 0.104 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2300748.18 | 0.00 | 2300748.18 | 1451805.18 | 3752553.36 | 3225648.14 | 5670.64 | 2430.67 | 658.70 | 0.00 |
ZONE2 FINE STORAGE | 5010738.43 | 0.00 | 5010738.43 | 4405893.47 | 9416631.89 | 13393694.68 | 5725.73 | 2768.00 | 266.27 | 3.61 |
ZONE3 BULK STORAGE | 0.00 | 26589839.63 | 26589839.63 | 38108989.31 | 64698828.94 | 30805497.77 | 6721.07 | 131.33 | 1907.60 | 5100.17 |
Total Facility | 7311486.60 | 26589839.63 | 33901326.23 | 43966687.96 | 77868014.19 | 47424840.58 | 7867.04 | 3023.67 | 2669.23 | 5100.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1758 | 0.0000 | 0.1758 | 0.0748 | 0.2505 | 0.1023 | 546.64 | 2430.67 | 658.70 |
ZONE2 FINE STORAGE | 0.3819 | 0.0000 | 0.3819 | 0.1297 | 0.5116 | 0.4247 | 605.33 | 2768.00 | 262.67 |
ZONE3 BULK STORAGE | 0.0000 | 1.0096 | 1.0096 | 1.4408 | 2.4504 | 0.9768 | 2625.87 | 53.00 | 957.12 |
Total Facility | 0.5577 | 1.0096 | 1.5673 | 1.6452 | 3.2125 | 1.5038 | 2743.04 | 2945.33 | 1715.42 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3035102.10 | 0.00 | 3035102.10 | 3225648.14 | 5668.77 | 0.00 | 3091.23 | 0.00 |
PSZ-FINE STORAGE | 6610261.11 | 0.00 | 6610261.11 | 13393694.68 | 5725.23 | 0.00 | 3034.77 | 3.61 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2319 | 0.0000 | 0.2319 | 0.1023 | 544.77 | 0.00 | 3091.23 |
PSZ-FINE STORAGE | 0.5039 | 0.0000 | 0.5039 | 0.4247 | 604.83 | 0.00 | 3031.17 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2829.64 | 270.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2979.77 | 56.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2510 | 0.4923 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6000 | 0.8281 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 400 |
Defaulted Fields | 319 |
Fields with Defaults | 1041 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 361.96 | 1261.11 | 18-JUN-10:40 | 33951.80 | 04-AUG-14:50 |
Electricity:Building | 247.68 | 1261.11 | 01-JAN-10:10 | 20604.86 | 04-AUG-10:10 |
Electricity:Zone:ZONE1 OFFICE | 38.91 | 520.87 | 01-JAN-00:10 | 2846.16 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 247.47 | 1261.11 | 01-JAN-10:10 | 19071.07 | 12-DEC-16:00 |
InteriorLights:Electricity | 110.96 | 791.24 | 01-JAN-10:10 | 9035.89 | 12-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 9.75 | 51.00 | 01-JAN-00:10 | 1011.11 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 110.96 | 791.24 | 01-JAN-10:10 | 9035.89 | 12-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 110.96 | 791.24 | 01-JAN-10:10 | 9035.89 | 12-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 9.75 | 51.00 | 01-JAN-00:10 | 1011.11 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 110.96 | 791.24 | 01-JAN-10:10 | 9035.89 | 12-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 160.02 | 440.27 | 01-JAN-10:10 | 14247.78 | 28-JUN-13:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 52.47 | 440.27 | 01-JAN-10:10 | 4194.37 | 05-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 52.47 | 440.27 | 01-JAN-10:10 | 4194.37 | 05-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 33.09 | 0.00 | 24-FEB-18:10 | 4361.52 | 04-AUG-15:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.21 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-AUG-16:10 |
Ventilation (simple):Fans:Electricity | 0.21 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-AUG-16:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.21 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-AUG-16:10 |
ElectricityPurchased:Facility | 361.96 | 1261.11 | 18-JUN-10:40 | 33951.80 | 04-AUG-14:50 |
ElectricityPurchased:Plant | 361.96 | 1261.11 | 18-JUN-10:40 | 33951.80 | 04-AUG-14:50 |
Cogeneration:ElectricityPurchased | 361.96 | 1261.11 | 18-JUN-10:40 | 33951.80 | 04-AUG-14:50 |
General:Cogeneration:ElectricityPurchased | 361.96 | 1261.11 | 18-JUN-10:40 | 33951.80 | 04-AUG-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 361.96 | 1261.11 | 18-JUN-10:40 | 33951.80 | 04-AUG-14:50 |
ElectricityNet:Plant | 361.96 | 1261.11 | 18-JUN-10:40 | 33951.80 | 04-AUG-14:50 |
Cogeneration:ElectricityNet | 361.96 | 1261.11 | 18-JUN-10:40 | 33951.80 | 04-AUG-14:50 |
General:Cogeneration:ElectricityNet | 361.96 | 1261.11 | 18-JUN-10:40 | 33951.80 | 04-AUG-14:50 |
Electricity:HVAC | 40.46 | 0.00 | 24-FEB-18:10 | 12623.55 | 04-AUG-15:30 |
General:Fans:Electricity | 32.89 | 0.00 | 24-FEB-18:10 | 3256.94 | 09-DEC-09:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 7.57 | 0.00 | 01-JAN-00:10 | 10567.32 | 04-AUG-15:30 |
General:Cooling:Electricity | 7.57 | 0.00 | 01-JAN-00:10 | 10567.32 | 04-AUG-15:30 |
ExteriorLights:Electricity | 61.98 | 0.00 | 01-JAN-08:00 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.98 | 0.00 | 01-JAN-08:00 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 11.84 | 0.00 | 02-JAN-00:10 | 1795.50 | 24-FEB-12:10 |
WaterSystems:Electricity | 11.84 | 0.00 | 02-JAN-00:10 | 1795.50 | 24-FEB-12:10 |
Water Heater:WaterSystems:Electricity | 11.84 | 0.00 | 02-JAN-00:10 | 1795.50 | 24-FEB-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1321.81 | 0.00 | 24-FEB-18:10 | 370256.29 | 18-JAN-18:00 |
NaturalGas:HVAC | 1321.81 | 0.00 | 24-FEB-18:10 | 370256.29 | 18-JAN-18:00 |
Heating:NaturalGas | 1321.81 | 0.00 | 24-FEB-18:10 | 370256.29 | 18-JAN-18:00 |
General:Heating:NaturalGas | 1321.81 | 0.00 | 24-FEB-18:10 | 370256.29 | 18-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2080.39 | 0.00 | 24-FEB-18:10 | 572673.43 | 09-DEC-06:10 |
EnergyTransfer:Building | 1022.46 | 0.00 | 24-FEB-18:10 | 287078.65 | 09-DEC-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 61.91 | 0.00 | 01-JAN-00:40 | 27892.99 | 02-FEB-07:20 |
Heating:EnergyTransfer | 986.53 | 0.00 | 24-FEB-18:10 | 287078.65 | 09-DEC-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 46.63 | 0.00 | 01-JAN-00:40 | 27892.99 | 02-FEB-07:20 |
General:Heating:EnergyTransfer | 986.53 | 0.00 | 24-FEB-18:10 | 287078.65 | 09-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 46.63 | 0.00 | 01-JAN-00:40 | 27892.99 | 02-FEB-07:20 |
Cooling:EnergyTransfer | 35.94 | 0.00 | 01-JAN-00:10 | 21183.23 | 04-AUG-15:30 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 15.28 | 0.00 | 01-JAN-00:10 | 7864.58 | 30-JUN-05:10 |
General:Cooling:EnergyTransfer | 35.94 | 0.00 | 01-JAN-00:10 | 21183.23 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 15.28 | 0.00 | 01-JAN-00:10 | 7864.58 | 30-JUN-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 163.97 | 0.00 | 01-JAN-00:40 | 48631.01 | 19-JAN-02:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 143.32 | 0.00 | 01-JAN-00:40 | 48631.01 | 19-JAN-02:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 143.32 | 0.00 | 01-JAN-00:40 | 48631.01 | 19-JAN-02:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 20.66 | 0.00 | 01-JAN-00:10 | 13622.52 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 20.66 | 0.00 | 01-JAN-00:10 | 13622.52 | 04-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 796.58 | 0.00 | 12-JAN-13:10 | 221897.11 | 09-DEC-08:30 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 796.58 | 0.00 | 12-JAN-13:10 | 221897.11 | 09-DEC-08:30 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 796.58 | 0.00 | 12-JAN-13:10 | 221897.11 | 09-DEC-08:30 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1057.92 | 0.00 | 24-FEB-18:10 | 292911.80 | 18-JAN-18:00 |
HeatingCoils:EnergyTransfer | 1024.74 | 0.00 | 24-FEB-18:10 | 292911.80 | 18-JAN-18:00 |
CoolingCoils:EnergyTransfer | 33.18 | 0.00 | 01-JAN-00:10 | 43216.41 | 04-AUG-15:40 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 46.627 | -15.278 | 0.000 | 0.000 | 10.143 | 9.748 | 29.165 | 10.870 | 0.000 | 0.413 | 0.000 | 0.000 | -9.521 | 0.000 | -26.130 | -56.037 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 143.316 | -20.658 | 0.000 | 0.000 | 26.799 | 48.748 | 0.000 | 0.000 | 0.000 | 0.577 | 0.001 | 0.000 | 0.000 | 0.000 | -69.678 | -129.105 |
ZONE3 BULK STORAGE | 796.582 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 67.507 | 52.468 | 107.344 | 123.987 | 0.000 | 15.796 | 0.000 | 0.000 | -67.266 | 0.000 | -712.139 | -384.280 |
Total Facility | 796.582 | 0.000 | 189.943 | -35.936 | 0.000 | 0.000 | 104.450 | 110.965 | 136.508 | 134.857 | 0.000 | 16.786 | 0.001 | 0.000 | -76.787 | 0.000 | -807.946 | -569.422 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-JUL-05:03 | 0.00 | 0.00 | 0.00 | -19420.60 | 0.00 | 0.00 | 92.30 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 19411.59 | 0.00 | -186.33 | 0.00 | -498.47 | 0.00 |
ZONE2 FINE STORAGE | 05-JUL-17:10 | 0.00 | 0.00 | 0.00 | -32379.72 | 0.00 | 0.00 | 0.00 | 452.77 | 0.00 | 0.00 | 0.00 | 0.00 | 31932.15 | 0.00 | -0.00 | 0.00 | -5.20 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-17:10 | 0.00 | 0.00 | 0.00 | -32379.72 | 0.00 | 0.00 | 0.00 | 1054.06 | 2519.91 | 30645.90 | 0.00 | 43.45 | 602.53 | 0.00 | 0.00 | 0.00 | -2486.13 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 04-MAR-06:32 | 0.00 | 0.00 | 28182.72 | 0.00 | 0.00 | 0.00 | 137.06 | 302.02 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -733.83 | 0.00 | -840.76 | -27597.73 |
ZONE2 FINE STORAGE | 02-FEB-01:21 | 0.00 | 0.00 | 72453.96 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10097.81 | -62656.12 |
ZONE3 BULK STORAGE | 09-DEC-08:30 | 221898.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8472.37 | 3669.95 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7477.97 | 0.00 | -224134.77 | -10627.79 |
Total Facility | 09-DEC-06:11 | 220104.94 | 0.00 | 98101.68 | 0.00 | 0.00 | 0.00 | 1397.22 | 1252.83 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9562.72 | 0.00 | -210458.18 | -103436.31 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9701 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9701 | 0.1054 | 1.0000 | Not calculated | 0.1023 | 0.1054 | ||
PSZ-FINE STORAGE | 1.7272 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.7272 | 0.2459 | 1.0000 | Not calculated | 0.4247 | 0.2459 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9701 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9701 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1054 | ||
PSZ-FINE STORAGE | 1.7272 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.7272 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2459 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9701 | 0.9701 | 0.9701 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7272 | 1.7272 | 1.7272 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9701 | 0.9701 | 0.9701 | 0.9701 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.7272 | 1.7272 | 1.7272 | 1.7272 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9701 | 0.9701 | 0.9701 | No | 0.1023 | 0.2639 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7272 | 1.7272 | 1.7272 | No | 0.4247 | 0.4096 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9701 | 0.9701 | 0.9701 | 0.9701 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.7272 | 1.7272 | 1.7272 | 1.7272 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 81.00 |
Number of hours cooling loads not met | 3.50 |
Number of hours not met | 84.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1321.81 | 370256.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 7.57 | 10567.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 110.96 | 9035.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.98 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.21 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 32.89 | 3256.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 11.84 | 1795.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 361.96 |
Natural Gas | 0.00 | 1321.81 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1683.77 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 22.95 |
Space Heating | 0.00 |
Space Cooling | 1.57 |
Fans (All) | 6.84 |
Service Water Heating | 2.45 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 74.86 |
Subtotal | 74.86 |
Natural Gas [MJ/m2] | |
Space Heating | 273.38 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 273.38 |
Subtotal | 273.38 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.59 |
Space Heating | 78.50 |
Space Cooling | 0.45 |
Fans (All) | 1.97 |
Service Water Heating | 0.70 |
Receptacle Equipment | 8.11 |
Miscellaneous | 3.68 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8454.50 | 305.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8147.00 | 613.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8049.33 | 683.50 | 27.17 | 0.00 | 0.00 |
Min | 8049.33 | 305.50 | 0.00 | 0.00 | 0.00 |
Max | 8454.50 | 683.50 | 27.17 | 0.00 | 0.00 |
Average | 8216.94 | 534.00 | 9.06 | 0.00 | 0.00 |
Sum | 24650.83 | 1602.00 | 27.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 71765.50 | 10953.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 166769.67 | 23215.83 | 1207.50 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 166769.67 | 23215.83 | 1207.50 | 0.00 | 0.00 |
Average | 90520.72 | 11389.78 | 402.50 | 0.00 | 0.00 |
Sum | 271562.17 | 34169.33 | 1207.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7737.50 | 1022.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7186.00 | 1574.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7321.00 | 1428.67 | 10.33 | 0.00 | 0.00 |
Min | 7186.00 | 1022.50 | 0.00 | 0.00 | 0.00 |
Max | 7737.50 | 1574.00 | 10.33 | 0.00 | 0.00 |
Average | 7414.83 | 1341.72 | 3.44 | 0.00 | 0.00 |
Sum | 22244.50 | 4025.17 | 10.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31556.00 | 1471.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 64364.50 | 18354.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 153968.00 | 36623.33 | 601.67 | 0.00 | 0.00 |
Min | 31556.00 | 1471.00 | 0.00 | 0.00 | 0.00 |
Max | 153968.00 | 36623.33 | 601.67 | 0.00 | 0.00 |
Average | 83296.17 | 18816.28 | 200.56 | 0.00 | 0.00 |
Sum | 249888.50 | 56448.83 | 601.67 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.496961E+09 | 603.25 | 07-JAN-08:09 | -25.9 | -26.2 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.457106E+09 | 603.25 | 15-FEB-08:09 | -12.1 | -12.7 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.537376E+09 | 658.39 | 25-MAR-15:30 | 18.35 | 10.46 |
April | 0.111280E+09 | 2911.82 | 18-APR-15:10 | 27.75 | 20.46 | 0.515264E+09 | 786.84 | 15-APR-13:39 | 27.75 | 20.46 |
May | 0.305292E+09 | 4042.85 | 31-MAY-16:00 | 28.30 | 18.78 | 0.602422E+09 | 769.01 | 30-MAY-15:00 | 28.30 | 18.78 |
June | 0.302111E+10 | 16293.76 | 29-JUN-05:02 | 17.48 | 16.35 | 0.648502E+09 | 769.01 | 28-JUN-07:00 | 17.48 | 16.35 |
July | 0.457885E+10 | 19426.29 | 19-JUL-05:03 | 12.48 | 11.50 | 0.634656E+09 | 769.03 | 03-JUL-07:30 | 12.48 | 11.50 |
August | 0.473114E+10 | 18937.63 | 09-AUG-05:03 | 12.98 | 11.32 | 0.685476E+09 | 769.03 | 12-AUG-15:00 | 20.60 | 18.08 |
September | 0.250883E+10 | 18512.26 | 09-SEP-05:02 | 13.80 | 13.12 | 0.606975E+09 | 769.02 | 11-SEP-08:20 | 22.77 | 19.12 |
October | 21149175.97 | 474.86 | 23-OCT-14:50 | 8.22 | 3.63 | 0.508763E+09 | 768.97 | 20-OCT-15:39 | 8.22 | 3.63 |
November | 439722.31 | 246.28 | 04-NOV-16:50 | 8.63 | 4.11 | 0.479841E+09 | 690.66 | 03-NOV-15:20 | 8.63 | 4.11 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.497023E+09 | 603.25 | 02-DEC-08:09 | -1.0 | -2.4 |
Annual Sum or Average | 0.152781E+11 | 0.667037E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.457106E+09 | 603.25 | -25.9 | -26.2 | ||
Maximum of Months | 0.473114E+10 | 19426.29 | 28.30 | 20.46 | 0.685476E+09 | 786.84 | 28.30 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59840596.98 | 2659.78 | 13-JAN-14:40 | 3.90 | 1.72 | 0.649185E+09 | 787.42 | 19-JAN-11:00 | -25.0 | -25.2 |
February | 0.266549E+09 | 5641.93 | 07-FEB-11:35 | 2.03 | 0.53 | 0.598213E+09 | 864.23 | 24-FEB-15:39 | 8.30 | 5.79 |
March | 0.829313E+09 | 8121.97 | 10-MAR-10:25 | -3.3 | -4.7 | 0.720749E+09 | 1107.86 | 25-MAR-15:20 | 18.53 | 10.46 |
April | 0.176202E+10 | 7458.28 | 21-APR-11:00 | -1.1 | -1.4 | 0.784934E+09 | 1928.99 | 18-APR-15:20 | -1.1 | -1.4 |
May | 0.134825E+10 | 4309.18 | 02-MAY-09:20 | 5.37 | 2.77 | 0.114023E+10 | 2212.38 | 31-MAY-15:30 | 29.15 | 19.25 |
June | 0.286758E+10 | 29699.76 | 30-JUN-17:10 | 28.30 | 20.22 | 0.164108E+10 | 2246.91 | 30-JUN-13:50 | 28.30 | 20.22 |
July | 0.429331E+10 | 32385.27 | 05-JUL-17:10 | 26.70 | 20.64 | 0.179467E+10 | 2246.91 | 05-JUL-14:00 | 26.70 | 20.64 |
August | 0.349375E+10 | 27392.37 | 02-AUG-17:12 | 28.53 | 22.51 | 0.192176E+10 | 2246.91 | 04-AUG-12:00 | 31.70 | 26.64 |
September | 0.271237E+10 | 21844.52 | 10-SEP-15:25 | 27.25 | 17.99 | 0.144013E+10 | 2254.29 | 05-SEP-12:50 | 27.25 | 17.99 |
October | 0.213062E+10 | 5531.71 | 23-OCT-09:20 | 2.70 | 0.39 | 0.763536E+09 | 1332.84 | 20-OCT-15:20 | 2.70 | 0.39 |
November | 0.810609E+09 | 5548.04 | 09-NOV-15:00 | 2.80 | 0.77 | 0.662752E+09 | 1158.97 | 03-NOV-14:50 | 2.80 | 0.77 |
December | 84222260.78 | 3213.69 | 02-DEC-15:10 | 6.02 | 3.34 | 0.649289E+09 | 787.42 | 30-DEC-10:00 | -1.1 | -1.8 |
Annual Sum or Average | 0.206584E+11 | 0.127665E+11 | ||||||||
Minimum of Months | 59840596.98 | 2659.78 | -3.3 | -4.7 | 0.598213E+09 | 787.42 | -25.0 | -25.2 | ||
Maximum of Months | 0.429331E+10 | 32385.27 | 28.53 | 22.51 | 0.192176E+10 | 2254.29 | 31.70 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.643975E+09 | 785.37 | 12-JAN-13:30 | 2.20 | 0.51 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.598116E+09 | 1024.82 | 24-FEB-15:30 | 8.30 | 5.75 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.773351E+09 | 1597.95 | 25-MAR-15:30 | 18.35 | 10.46 |
April | 0.00 | 0.00 | 01-APR-00:05 | -1.2 | -2.2 | 0.111428E+10 | 3770.46 | 18-APR-15:09 | 27.75 | 20.46 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.15 | 0.208962E+10 | 4444.14 | 31-MAY-15:20 | 29.43 | 19.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 | 0.360696E+10 | 6408.42 | 29-JUN-15:00 | 30.00 | 20.53 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 | 0.440508E+10 | 6523.24 | 03-JUL-15:20 | 29.63 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 | 0.457039E+10 | 7845.09 | 04-AUG-15:50 | 33.90 | 26.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 | 0.315218E+10 | 5796.63 | 08-SEP-14:50 | 30.10 | 19.14 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 | 0.112497E+10 | 2249.09 | 02-OCT-15:39 | 17.17 | 14.05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 | -0.5 | 0.775212E+09 | 1721.09 | 03-NOV-14:50 | 16.10 | 9.74 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.639050E+09 | 851.09 | 02-DEC-15:50 | 5.68 | 3.15 |
Annual Sum or Average | 0.00 | 0.234932E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.598116E+09 | 785.37 | 2.20 | 0.51 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.457039E+10 | 7845.09 | 33.90 | 26.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110002E+11 | 28139.39 | 11-JAN-06:32 | -4.4 |
February | 0.815266E+10 | 27892.99 | 02-FEB-07:20 | -36.7 |
March | 0.662845E+10 | 28182.66 | 04-MAR-06:32 | -8.3 |
April | 0.349386E+10 | 28095.78 | 05-APR-05:32 | -2.8 |
May | 0.888647E+09 | 27181.58 | 02-MAY-05:12 | 2.20 |
June | 0.115718E+09 | 26525.24 | 05-JUN-05:02 | 9.32 |
July | 17212732.84 | 1310.62 | 19-JUL-06:10 | 14.37 |
August | 30392707.91 | 1343.81 | 07-AUG-06:10 | 8.87 |
September | 0.292014E+09 | 27057.94 | 29-SEP-05:01 | 0.92 |
October | 0.230365E+10 | 27166.44 | 16-OCT-05:12 | 0.27 |
November | 0.517571E+10 | 27432.57 | 24-NOV-06:12 | -13.5 |
December | 0.852852E+10 | 27548.47 | 11-DEC-06:11 | -22.0 |
Annual Sum or Average | 0.466270E+11 | |||
Minimum of Months | 17212732.84 | 1310.62 | -36.7 | |
Maximum of Months | 0.110002E+11 | 28182.66 | 14.37 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391641E+11 | 72452.99 | 19-JAN-02:61 | -24.1 |
February | 0.283222E+11 | 72453.84 | 02-FEB-01:21 | -34.1 |
March | 0.171718E+11 | 71037.87 | 06-MAR-00:02 | -16.3 |
April | 0.680624E+10 | 70138.67 | 03-APR-00:23 | -5.8 |
May | 0.710732E+09 | 41457.64 | 01-MAY-05:37 | 5.93 |
June | 0.103755E+09 | 2260.02 | 09-JUN-12:00 | 28.30 |
July | 52842048.11 | 714.88 | 10-JUL-06:13 | 17.40 |
August | 56730387.08 | 715.62 | 25-AUG-07:00 | 13.90 |
September | 0.122616E+09 | 16960.44 | 30-SEP-04:35 | -0.2 |
October | 0.324726E+10 | 61618.10 | 27-OCT-05:01 | 0.00 |
November | 0.165493E+11 | 71660.35 | 26-NOV-04:02 | -25.0 |
December | 0.310090E+11 | 71818.94 | 09-DEC-18:42 | -19.9 |
Annual Sum or Average | 0.143317E+12 | |||
Minimum of Months | 52842048.11 | 714.88 | -34.1 | |
Maximum of Months | 0.391641E+11 | 72453.84 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243163E+12 | 220602.07 | 18-JAN-18:00 | -18.3 |
February | 0.164436E+12 | 212667.84 | 01-FEB-20:57 | -28.9 |
March | 0.882124E+11 | 149915.88 | 06-MAR-08:70 | -11.8 |
April | 0.195268E+11 | 89728.59 | 02-APR-24:00 | -5.6 |
May | 0.276243E+09 | 13877.01 | 02-MAY-03:00 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.196184E+10 | 18104.23 | 24-OCT-06:00 | 2.20 |
November | 0.917927E+11 | 147517.05 | 26-NOV-04:00 | -25.0 |
December | 0.187215E+12 | 221897.11 | 09-DEC-08:30 | -22.8 |
Annual Sum or Average | 0.796584E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.243163E+12 | 221897.11 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.882773E+09 | 1011.11 | 02-JAN-16:40 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.777339E+09 | 984.05 | 11-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.850652E+09 | 949.80 | 01-MAR-16:00 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.790678E+09 | 954.15 | 10-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.772735E+09 | 874.02 | 25-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.754425E+09 | 930.61 | 13-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.738246E+09 | 931.94 | 20-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.796802E+09 | 909.09 | 31-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.782572E+09 | 954.85 | 21-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.813614E+09 | 978.89 | 21-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.854303E+09 | 1011.11 | 06-NOV-16:00 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.934047E+09 | 1011.11 | 01-DEC-16:30 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.974818E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.738246E+09 | 874.02 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.934047E+09 | 1011.11 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.404504E+10 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.370796E+10 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.430437E+10 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.401913E+10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.417471E+10 | 3848.58 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.414879E+10 | 3848.58 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.404504E+10 | 3848.58 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.430437E+10 | 3848.58 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.401913E+10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.404504E+10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.388946E+10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.404504E+10 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.487481E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.370796E+10 | 3848.58 | 0.00 | 0.00 | |
Maximum of Months | 0.430437E+10 | 3848.58 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.450378E+10 | 4172.41 | 02-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.407525E+10 | 4138.82 | 08-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.458781E+10 | 4093.79 | 13-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.425464E+10 | 3949.11 | 10-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.438479E+10 | 3902.87 | 04-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.433461E+10 | 3847.84 | 05-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.426053E+10 | 3890.60 | 20-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.451877E+10 | 3935.28 | 29-AUG-08:20 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.427600E+10 | 4003.72 | 21-SEP-08:30 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.440739E+10 | 4103.19 | 30-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.429363E+10 | 4172.73 | 29-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.457115E+10 | 4194.37 | 05-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.524684E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.407525E+10 | 3847.84 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.458781E+10 | 4194.37 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.882773E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513504E+10 |
February | 0.127628E+10 | 0.777339E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382221E+10 |
March | 0.149825E+10 | 0.850652E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387236.75 | 0.315940E+10 |
April | 0.138726E+10 | 0.790678E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25611570.50 | 0.182996E+10 |
May | 0.144276E+10 | 0.772735E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25304408.08 | 0.963025E+09 |
June | 0.144276E+10 | 0.754425E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103081E+09 | 0.607689E+09 |
July | 0.138726E+10 | 0.738246E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78013020.89 | 0.393975E+09 |
August | 0.149825E+10 | 0.796802E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113737E+09 | 0.558080E+09 |
September | 0.138726E+10 | 0.782572E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66445882.55 | 0.981360E+09 |
October | 0.138726E+10 | 0.813614E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165307E+10 |
November | 0.133177E+10 | 0.854303E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288506E+10 |
December | 0.138726E+10 | 0.934047E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414071E+10 |
Annual Sum or Average | 0.168137E+11 | 0.974818E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412581E+09 | 0.261296E+11 |
Minimum of Months | 0.127628E+10 | 0.738246E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393975E+09 |
Maximum of Months | 0.149825E+10 | 0.934047E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113737E+09 | 0.513504E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140130E+11 |
February | 0.300332E+10 | 0.370796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102510E+11 |
March | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7442152.09 | 0.797396E+10 |
April | 0.326447E+10 | 0.401913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180609E+09 | 0.422171E+10 |
May | 0.339505E+10 | 0.417471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70976150.81 | 0.201536E+10 |
June | 0.339505E+10 | 0.414879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168062E+09 | 0.169589E+10 |
July | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38905469.51 | 0.153168E+10 |
August | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58403116.96 | 0.209647E+10 |
September | 0.326447E+10 | 0.401913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44948782.63 | 0.263536E+10 |
October | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7893603.14 | 0.357924E+10 |
November | 0.313390E+10 | 0.388946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801407E+10 |
December | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116501E+11 |
Annual Sum or Average | 0.395654E+11 | 0.487481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577241E+09 | 0.696778E+11 |
Minimum of Months | 0.300332E+10 | 0.370796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153168E+10 |
Maximum of Months | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180609E+09 | 0.140130E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.450378E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961986E+11 |
February | 0.690763E+10 | 0.407525E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668427E+11 |
March | 0.810895E+10 | 0.458781E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878435E+09 | 0.452219E+11 |
April | 0.750829E+10 | 0.425464E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365490E+10 | 0.217931E+11 |
May | 0.780862E+10 | 0.438479E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210775E+10 | 0.100608E+11 |
June | 0.780862E+10 | 0.433461E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129356E+10 | 0.114195E+11 |
July | 0.750829E+10 | 0.426053E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80413664.80 | 0.134038E+11 |
August | 0.810895E+10 | 0.451877E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102368E+09 | 0.164308E+11 |
September | 0.750829E+10 | 0.427600E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399376E+09 | 0.184281E+11 |
October | 0.750829E+10 | 0.440739E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.831977E+09 | 0.167776E+11 |
November | 0.720796E+10 | 0.429363E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161208E+09 | 0.466807E+11 |
December | 0.750829E+10 | 0.457115E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755036E+11 |
Annual Sum or Average | 0.910005E+11 | 0.524684E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951000E+10 | 0.438761E+12 |
Minimum of Months | 0.690763E+10 | 0.407525E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100608E+11 |
Maximum of Months | 0.810895E+10 | 0.458781E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365490E+10 | 0.961986E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1011.11 | 02-JAN-16:40 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14767.81 | 19-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 984.05 | 11-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16757.78 | 02-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 949.80 | 01-MAR-16:00 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.27 | 19-MAR-14:00 | 10575.07 | 06-MAR-08:00 |
April | 1680.92 | 01-APR-07:10 | 954.15 | 10-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 899.66 | 18-APR-12:00 | 7928.69 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 874.02 | 25-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.09 | 31-MAY-17:00 | 5014.51 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 930.61 | 13-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1769.43 | 26-JUN-16:10 | 3562.45 | 02-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 931.94 | 20-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.15 | 25-JUL-16:10 | 2701.40 | 24-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 909.09 | 31-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2101.51 | 04-AUG-16:10 | 3632.26 | 07-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 954.85 | 21-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1685.12 | 06-SEP-16:10 | 5262.48 | 29-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 978.89 | 21-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6034.93 | 23-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1011.11 | 06-NOV-16:00 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 10027.97 | 28-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1011.11 | 01-DEC-16:30 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13473.22 | 08-DEC-17:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 874.02 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2701.40 | |||||
Maximum of Months | 1680.92 | 1011.11 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2101.51 | 16757.78 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 24026.18 | 18-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14959.93 | 04-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.60 | 19-MAR-16:00 | 14703.13 | 06-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3406.25 | 15-APR-17:00 | 9184.84 | 25-APR-06:10 |
May | 3955.50 | 01-MAY-07:10 | 3848.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1722.18 | 05-MAY-15:10 | 3887.54 | 02-MAY-03:00 |
June | 3955.50 | 01-JUN-07:10 | 3848.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2010.96 | 11-JUN-15:00 | 3903.41 | 02-JUN-05:00 |
July | 3955.50 | 01-JUL-07:10 | 3848.58 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.36 | 25-JUL-16:00 | 2488.35 | 10-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 3848.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.45 | 04-AUG-16:20 | 2849.18 | 06-AUG-06:00 |
September | 3955.50 | 01-SEP-07:10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.61 | 06-SEP-15:40 | 3944.92 | 18-SEP-23:00 |
October | 3955.50 | 02-OCT-07:10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.86 | 20-OCT-15:10 | 6288.69 | 24-OCT-06:10 |
November | 3955.50 | 01-NOV-07:10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 13352.32 | 25-NOV-16:10 |
December | 3955.50 | 01-DEC-08:09 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 26545.12 | 09-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2488.35 | ||||
Maximum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3406.25 | 26545.12 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4172.41 | 02-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 131540.85 | 18-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 4138.82 | 08-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 92742.49 | 28-FEB-10:00 |
March | 9097.65 | 01-MAR-08:09 | 4093.79 | 13-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15901.49 | 25-MAR-15:00 | 84545.50 | 06-MAR-08:70 |
April | 9097.65 | 01-APR-07:10 | 3949.11 | 10-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35934.69 | 15-APR-15:00 | 40179.00 | 02-APR-24:00 |
May | 9097.65 | 01-MAY-07:10 | 3902.87 | 04-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23415.23 | 04-MAY-14:00 | 23737.95 | 13-MAY-13:00 |
June | 9097.65 | 01-JUN-07:10 | 3847.84 | 05-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16440.89 | 11-JUN-15:00 | 24468.95 | 02-JUN-08:00 |
July | 9097.65 | 01-JUL-07:10 | 3890.60 | 20-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3784.32 | 25-JUL-16:00 | 24457.88 | 10-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 3935.28 | 29-AUG-08:20 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3262.61 | 21-AUG-13:00 | 20687.50 | 30-AUG-15:00 |
September | 9097.65 | 01-SEP-07:10 | 4003.72 | 21-SEP-08:30 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8121.20 | 06-SEP-14:00 | 25262.91 | 18-SEP-16:00 |
October | 9097.65 | 02-OCT-07:10 | 4103.19 | 30-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13986.44 | 20-OCT-15:00 | 23358.83 | 24-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 4172.73 | 29-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8389.90 | 20-NOV-10:00 | 91126.14 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 4194.37 | 05-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 157354.02 | 09-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3847.84 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20687.50 | |||||
Maximum of Months | 9097.65 | 4194.37 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 35934.69 | 157354.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.46 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.72 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1251.98 |
April | 2911.82 | 18-APR-15:10 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 390.67 | 0.00 |
May | 4042.85 | 31-MAY-16:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 281.01 | 0.00 |
June | 16293.76 | 29-JUN-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.89 |
July | 19426.29 | 19-JUL-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.47 |
August | 18937.63 | 09-AUG-05:03 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.76 |
September | 18512.26 | 09-SEP-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.12 |
October | 474.86 | 23-OCT-14:50 | 1680.92 | 639.59 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.73 |
November | 246.28 | 04-NOV-16:50 | 537.90 | 785.93 | 917.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.21 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 152.99 | 917.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19426.29 | 1680.92 | 785.93 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.67 | 1251.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2659.78 | 13-JAN-14:40 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.98 |
February | 5641.93 | 07-FEB-11:35 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.46 |
March | 8121.97 | 10-MAR-10:25 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.69 |
April | 7458.28 | 21-APR-11:00 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1966.06 |
May | 4309.18 | 02-MAY-09:20 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.73 |
June | 29699.76 | 30-JUN-17:10 | 0.00 | 1811.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.22 | 0.00 |
July | 32385.27 | 05-JUL-17:10 | 0.00 | 1811.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 |
August | 27392.37 | 02-AUG-17:12 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.13 | 0.00 |
September | 21844.52 | 10-SEP-15:25 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.08 | 0.00 |
October | 5531.71 | 23-OCT-09:20 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.12 |
November | 5548.04 | 09-NOV-15:00 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2910.14 |
December | 3213.69 | 02-DEC-15:10 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2659.78 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32385.27 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.13 | 2910.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1992.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16604.45 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2490.23 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40749.75 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2490.23 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42176.00 |
April | 0.00 | 01-APR-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7659.16 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4204.93 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5476.20 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5455.89 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6341.27 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7841.90 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7702.24 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5138.97 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1494.14 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17062.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4204.93 | |
Maximum of Months | 0.00 | 0.00 | 2490.23 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42176.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.332726E+11 | 27310.81 | 18-JAN-16:00 | 0.391279E+12 | 370256.29 | 18-JAN-17:00 |
February | 0.294272E+11 | 23200.15 | 02-FEB-13:39 | 0.268812E+12 | 328248.25 | 01-FEB-20:00 |
March | 0.319903E+11 | 22826.09 | 02-MAR-15:00 | 0.151602E+12 | 254840.51 | 06-MAR-08:09 |
April | 0.281705E+11 | 22911.59 | 18-APR-14:00 | 0.415280E+11 | 149728.54 | 02-APR-23:49 |
May | 0.278478E+11 | 23006.53 | 31-MAY-14:50 | 0.200769E+10 | 46299.88 | 02-MAY-05:10 |
June | 0.287022E+11 | 30675.21 | 30-JUN-14:50 | 71611463.40 | 6320.28 | 05-JUN-05:10 |
July | 0.293330E+11 | 31863.65 | 03-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.312117E+11 | 33951.80 | 04-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.287401E+11 | 26631.74 | 08-SEP-14:09 | 0.472572E+09 | 17528.04 | 30-SEP-05:30 |
October | 0.294437E+11 | 21870.84 | 27-OCT-12:30 | 0.111611E+11 | 52701.07 | 27-OCT-05:10 |
November | 0.305332E+11 | 27180.61 | 25-NOV-16:00 | 0.151879E+12 | 247726.90 | 25-NOV-17:00 |
December | 0.332847E+11 | 27351.78 | 09-DEC-16:00 | 0.302996E+12 | 368227.21 | 09-DEC-08:00 |
Annual Sum or Average | 0.361957E+12 | 0.132181E+13 | ||||
Minimum of Months | 0.278478E+11 | 21870.84 | 0.00 | 0.00 | ||
Maximum of Months | 0.332847E+11 | 33951.80 | 0.391279E+12 | 370256.29 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.943160E+10 | 0.702230E+10 | 0.112984E+11 | 0.00 | 0.443592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108441E+10 | 0.00 |
February | 0.856055E+10 | 0.570171E+10 | 0.103734E+11 | 0.00 | 0.377883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101270E+10 | 0.00 |
March | 0.974284E+10 | 0.542568E+10 | 0.121089E+11 | 0.00 | 0.354575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116710E+10 | 0.00 |
April | 0.906444E+10 | 0.434176E+10 | 0.112578E+11 | 0.00 | 0.241650E+10 | 0.00 | 0.00 | 42016823.74 | 0.00 | 0.00 | 0.00 | 0.104805E+10 | 0.00 |
May | 0.933223E+10 | 0.378915E+10 | 0.117000E+11 | 0.00 | 0.190672E+10 | 0.00 | 0.00 | 93188816.04 | 0.00 | 0.00 | 0.00 | 0.102659E+10 | 0.00 |
June | 0.923783E+10 | 0.337007E+10 | 0.116594E+11 | 0.00 | 0.194663E+10 | 0.00 | 0.00 | 0.153572E+10 | 0.00 | 0.00 | 0.00 | 0.952617E+09 | 0.00 |
July | 0.904382E+10 | 0.358354E+10 | 0.112984E+11 | 0.00 | 0.190313E+10 | 0.00 | 0.00 | 0.262823E+10 | 0.00 | 0.00 | 0.00 | 0.875893E+09 | 0.00 |
August | 0.961994E+10 | 0.414498E+10 | 0.121016E+11 | 0.00 | 0.205465E+10 | 0.00 | 0.00 | 0.237692E+10 | 0.00 | 0.00 | 0.00 | 0.913645E+09 | 0.00 |
September | 0.907770E+10 | 0.484525E+10 | 0.112504E+11 | 0.00 | 0.180637E+10 | 0.00 | 0.00 | 0.894725E+09 | 0.00 | 0.00 | 0.00 | 0.865670E+09 | 0.00 |
October | 0.926605E+10 | 0.594574E+10 | 0.113057E+11 | 0.00 | 0.200748E+10 | 0.00 | 0.00 | 169.92 | 0.00 | 0.00 | 0.00 | 0.918725E+09 | 0.00 |
November | 0.903739E+10 | 0.656444E+10 | 0.108562E+11 | 0.00 | 0.313649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938746E+09 | 0.00 |
December | 0.955024E+10 | 0.724424E+10 | 0.112984E+11 | 0.00 | 0.415549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103639E+10 | 0.00 |
Annual Sum or Average | 0.110965E+12 | 0.619789E+11 | 0.136508E+12 | 0.00 | 0.330940E+11 | 0.00 | 0.00 | 0.757080E+10 | 0.00 | 0.00 | 0.00 | 0.118405E+11 | 0.00 |
Minimum of Months | 0.856055E+10 | 0.337007E+10 | 0.103734E+11 | 0.00 | 0.180637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865670E+09 | 0.00 |
Maximum of Months | 0.974284E+10 | 0.724424E+10 | 0.121089E+11 | 0.00 | 0.443592E+10 | 0.00 | 0.00 | 0.262823E+10 | 0.00 | 0.00 | 0.00 | 0.116710E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.391279E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.268812E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.151602E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.415280E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.200769E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 71611463.40 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.472572E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.111611E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.151879E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.302996E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132181E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.391279E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8962.14 | 10-JAN-15:00 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3154.96 | 19-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8872.03 | 08-FEB-09:09 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3239.64 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8837.04 | 13-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2924.76 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8714.81 | 10-APR-08:09 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2712.88 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 8573.25 | 04-MAY-08:09 | 4975.14 | 01-MAY-19:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 2505.10 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 8583.01 | 05-JUN-08:09 | 4975.14 | 01-JUN-19:40 | 10035.17 | 01-JUN-07:10 | 0.00 | 4118.59 | 30-JUN-12:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 8638.58 | 20-JUL-08:09 | 4975.14 | 01-JUL-19:00 | 10035.17 | 01-JUL-07:10 | 0.00 | 4118.59 | 03-JUL-14:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8617.41 | 29-AUG-08:20 | 5520.82 | 08-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4361.52 | 04-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8789.58 | 21-SEP-08:30 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1923.52 | 30-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8851.35 | 30-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2521.48 | 28-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8975.76 | 27-NOV-15:00 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2990.27 | 25-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9035.89 | 12-DEC-15:00 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 3256.94 | 09-DEC-08:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 8573.25 | 4975.14 | 10035.17 | 0.00 | 1923.52 | 0.00 | 0.00 | |||||
Maximum of Months | 9035.89 | 5520.82 | 10035.17 | 0.00 | 4361.52 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1768.97 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 1795.50 | 24-FEB-12:09 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 1788.91 | 02-MAR-12:09 | 0.00 |
April | 1397.05 | 18-APR-15:09 | 0.00 | 0.00 | 0.00 | 1726.73 | 01-APR-11:20 | 0.00 |
May | 1608.12 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1643.85 | 01-MAY-11:00 | 0.00 |
June | 7019.14 | 30-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1534.29 | 01-JUN-11:00 | 0.00 |
July | 8220.06 | 03-JUL-14:00 | 0.00 | 0.00 | 0.00 | 1451.77 | 01-JUL-11:09 | 0.00 |
August | 10567.32 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 1401.46 | 02-AUG-11:20 | 0.00 |
September | 5413.83 | 06-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1412.39 | 30-SEP-11:09 | 0.00 |
October | 0.28 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1507.08 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 1610.88 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1716.12 | 30-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1401.46 | 0.00 | ||
Maximum of Months | 10567.32 | 0.00 | 0.00 | 0.00 | 1795.50 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 27310.81 | 18-JAN-16:00 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 3038.33 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23200.15 | 02-FEB-13:39 | 8690.62 | 10035.17 | 0.00 | 0.00 | 2876.13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22826.09 | 02-MAR-15:00 | 8639.57 | 10035.17 | 0.00 | 0.00 | 2553.86 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22911.59 | 18-APR-14:00 | 8207.72 | 10035.17 | 0.00 | 0.00 | 1813.30 | 0.00 | 0.00 | 1373.74 | 0.00 |
May | 23006.53 | 31-MAY-14:50 | 8207.72 | 10035.17 | 0.00 | 0.00 | 1813.30 | 0.00 | 0.00 | 1566.81 | 0.00 |
June | 30675.21 | 30-JUN-14:50 | 8207.72 | 10035.17 | 0.00 | 0.00 | 4118.59 | 0.00 | 0.00 | 7004.75 | 0.00 |
July | 31863.65 | 03-JUL-14:00 | 8207.72 | 10035.17 | 0.00 | 0.00 | 4118.59 | 0.00 | 0.00 | 8220.06 | 0.00 |
August | 33951.80 | 04-AUG-14:50 | 8207.72 | 10035.17 | 0.00 | 0.00 | 4314.58 | 0.00 | 0.00 | 10165.72 | 0.00 |
September | 26631.74 | 08-SEP-14:09 | 8207.72 | 10035.17 | 0.00 | 0.00 | 1813.30 | 0.00 | 0.00 | 5346.77 | 0.00 |
October | 21870.84 | 27-OCT-12:30 | 8702.29 | 10035.17 | 0.00 | 0.00 | 1813.30 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27180.61 | 25-NOV-16:00 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2913.32 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27351.78 | 09-DEC-16:00 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 3082.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21870.84 | 8142.10 | 10035.17 | 0.00 | 0.00 | 1813.30 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33951.80 | 8702.29 | 10035.17 | 5520.82 | 0.00 | 4314.58 | 0.00 | 0.00 | 10165.72 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 370256.29 | 18-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 328248.25 | 01-FEB-20:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 254840.51 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 149728.54 | 02-APR-23:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 46299.88 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6320.28 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 17528.04 | 30-SEP-05:30 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 52701.07 | 27-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 247726.90 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 368227.21 | 09-DEC-08:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 370256.29 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.83 | 16.05 | 9.50 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
February | 29.17 | 16.14 | 9.67 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
March | 16.83 | 17.63 | 10.17 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
April | 8.33 | 19.15 | 7.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
May | 1.67 | 20.03 | 1.67 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.33 | 24.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.55 | 1.33 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.54 | 1.50 | 24.54 |
September | 0.67 | 20.26 | 0.67 | 20.26 | 0.33 | 21.12 | 0.33 | 21.69 |
October | 7.17 | 20.09 | 7.17 | 20.09 | 0.00 | 20.09 | 0.00 | 20.09 |
November | 14.00 | 17.56 | 7.67 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
December | 25.50 | 16.49 | 9.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
Annual Sum or Average | 137.17 | 16.97 | 63.33 | 17.73 | 3.50 | 17.84 | 3.50 | 17.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 | 16.71 |
Maximum of Months | 33.83 | 20.26 | 10.17 | 20.26 | 1.50 | 24.55 | 1.50 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.17 | 14.28 | 4.17 | 14.27 | 0.00 | 14.27 | 0.00 | 14.27 |
February | 98.17 | 14.47 | 4.33 | 14.47 | 0.00 | 14.47 | 0.00 | 14.47 |
March | 73.50 | 14.67 | 4.67 | 14.67 | 0.00 | 14.67 | 0.00 | 14.67 |
April | 28.67 | 14.83 | 1.83 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
May | 0.17 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.00 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.30 | 0.00 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.00 | 27.26 |
September | 0.17 | 14.98 | 0.00 | 14.98 | 0.17 | 21.12 | 0.00 | 21.12 |
October | 6.50 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
November | 66.67 | 14.60 | 2.83 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
December | 111.33 | 14.49 | 4.33 | 14.49 | 0.00 | 14.49 | 0.00 | 14.49 |
Annual Sum or Average | 500.33 | 14.50 | 22.17 | 14.50 | 2.17 | 14.56 | 0.00 | 14.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 0.00 | 14.27 |
Maximum of Months | 115.17 | 14.99 | 4.67 | 14.99 | 1.17 | 27.30 | 0.00 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.67 | 8.67 | 8.17 | 8.58 | 0.00 | 8.58 | 0.00 | 8.58 |
Annual Sum or Average | 12.67 | 8.67 | 8.17 | 8.58 | 0.00 | 8.58 | 0.00 | 8.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.67 | 8.67 | 8.17 | 8.58 | 0.00 | 8.58 | 0.00 | 8.58 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
February | 276.00 | 21.01 | 276.00 | 21.01 | 276.00 | 21.01 |
March | 324.00 | 21.05 | 323.00 | 21.05 | 323.00 | 21.05 |
April | 299.50 | 21.39 | 249.50 | 21.29 | 249.50 | 21.25 |
May | 304.50 | 22.55 | 86.50 | 22.37 | 84.33 | 22.25 |
June | 157.83 | 23.31 | 158.67 | 23.59 | 57.50 | 23.62 |
July | 83.17 | 23.88 | 277.50 | 23.89 | 80.00 | 23.90 |
August | 102.67 | 23.89 | 285.00 | 23.90 | 96.67 | 23.90 |
September | 157.83 | 22.66 | 142.50 | 22.87 | 43.67 | 22.66 |
October | 300.00 | 21.28 | 255.00 | 21.20 | 255.00 | 21.16 |
November | 288.00 | 21.11 | 269.17 | 21.08 | 269.17 | 21.08 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 2893.50 | 21.66 | 2922.83 | 21.77 | 2334.83 | 21.66 |
Minimum of Months | 83.17 | 21.01 | 86.50 | 21.01 | 43.67 | 21.01 |
Maximum of Months | 324.00 | 23.89 | 323.00 | 23.90 | 323.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
February | 276.00 | 15.55 | 276.00 | 15.55 | 276.00 | 15.55 |
March | 324.00 | 15.73 | 324.00 | 15.73 | 324.00 | 15.73 |
April | 300.00 | 16.93 | 283.50 | 16.80 | 283.50 | 16.76 |
May | 311.17 | 20.06 | 194.67 | 19.80 | 193.83 | 19.68 |
June | 220.00 | 23.76 | 229.00 | 24.39 | 148.00 | 24.43 |
July | 218.67 | 26.29 | 289.50 | 26.24 | 214.50 | 26.27 |
August | 180.00 | 26.13 | 303.00 | 26.13 | 175.00 | 26.15 |
September | 171.33 | 21.06 | 211.00 | 22.26 | 96.50 | 21.81 |
October | 300.00 | 16.74 | 300.00 | 16.74 | 300.00 | 16.74 |
November | 288.00 | 15.98 | 288.00 | 15.98 | 288.00 | 15.98 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 3189.17 | 18.48 | 3298.67 | 18.79 | 2899.33 | 18.59 |
Minimum of Months | 171.33 | 15.54 | 194.67 | 15.54 | 96.50 | 15.54 |
Maximum of Months | 324.00 | 26.29 | 324.00 | 26.24 | 324.00 | 26.27 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
February | 276.00 | 10.04 | 276.00 | 10.04 | 276.00 | 10.04 |
March | 324.00 | 10.49 | 324.00 | 10.49 | 324.00 | 10.49 |
April | 300.00 | 12.86 | 299.33 | 12.86 | 299.33 | 12.85 |
May | 308.00 | 17.62 | 298.33 | 17.60 | 295.17 | 17.56 |
June | 240.50 | 23.04 | 227.00 | 23.55 | 164.83 | 23.54 |
July | 226.67 | 27.33 | 288.67 | 27.16 | 221.67 | 27.24 |
August | 214.83 | 26.79 | 294.67 | 26.67 | 201.00 | 26.77 |
September | 203.50 | 20.85 | 206.50 | 21.55 | 126.50 | 21.19 |
October | 300.00 | 13.13 | 300.00 | 13.13 | 300.00 | 13.13 |
November | 288.00 | 11.09 | 288.00 | 11.09 | 288.00 | 11.09 |
December | 300.00 | 9.96 | 300.00 | 9.96 | 300.00 | 9.96 |
Annual Sum or Average | 3281.50 | 15.33 | 3402.50 | 15.62 | 3096.50 | 15.40 |
Minimum of Months | 203.50 | 9.96 | 206.50 | 9.96 | 126.50 | 9.96 |
Maximum of Months | 324.00 | 27.33 | 324.00 | 27.16 | 324.00 | 27.24 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.178359E+09 | 42016823.74 | 13.17 | 0.126771E+09 | 51587704.66 | 0.00 | 0.60 | 18-APR-15:10 | 0.00 | 01-APR-00:05 | 6080.10 | 18-APR-15:10 | 4447.25 | 18-APR-15:10 | 1632.84 | 18-APR-15:10 | 1397.05 | 18-APR-15:10 | 0.00 | 01-APR-00:05 |
May | 0.399831E+09 | 93188816.04 | 34.50 | 0.308389E+09 | 91442440.77 | 0.00 | 0.70 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 | 6786.01 | 31-MAY-15:10 | 5735.42 | 31-MAY-15:10 | 1442.48 | 30-MAY-13:50 | 1608.12 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 0.382302E+10 | 0.843919E+09 | 178.66 | 0.285570E+10 | 0.967326E+09 | 0.00 | 1.00 | 14-JUN-05:03 | 0.00 | 01-JUN-00:10 | 21732.29 | 26-JUN-05:45 | 11477.15 | 30-JUN-05:01 | 11497.27 | 26-JUN-05:05 | 4559.75 | 26-JUN-05:45 | 0.00 | 01-JUN-00:10 |
July | 0.623401E+10 | 0.134316E+10 | 247.59 | 0.440692E+10 | 0.182708E+10 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 21361.47 | 27-JUL-05:02 | 12357.28 | 25-JUL-05:03 | 12010.29 | 27-JUL-05:03 | 4505.41 | 27-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.630202E+10 | 0.137341E+10 | 265.94 | 0.448262E+10 | 0.181940E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 23434.70 | 04-AUG-05:01 | 11812.50 | 09-AUG-05:03 | 14692.69 | 04-AUG-05:08 | 4779.26 | 04-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.235147E+10 | 0.532928E+09 | 123.88 | 0.206440E+10 | 0.287075E+09 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 19941.09 | 11-SEP-05:02 | 13513.54 | 18-SEP-05:03 | 9294.80 | 12-SEP-05:03 | 4275.34 | 11-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 703.57 | 169.92 | 0.17 | 703.57 | -0.0 | 0.00 | 0.00 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1.17 | 20-OCT-15:00 | 1.17 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 0.28 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.192887E+11 | 0.422862E+10 | 863.90 | 0.142448E+11 | 0.504391E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.630202E+10 | 0.137341E+10 | 265.94 | 0.448262E+10 | 0.182708E+10 | 0.00 | 1.00 | 0.00 | 23434.70 | 13513.54 | 14692.69 | 4779.26 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.284813E+10 | 0.691798E+09 | 77.51 | 0.185536E+10 | 0.992774E+09 | 0.00 | 1.00 | 25-JUN-13:40 | 0.00 | 01-JUN-00:10 | 47738.34 | 29-JUN-19:35 | 32884.95 | 28-JUN-18:45 | 16515.15 | 29-JUN-19:35 | 10495.39 | 28-JUN-18:45 | 0.00 | 01-JUN-00:10 |
July | 0.545307E+10 | 0.128507E+10 | 155.14 | 0.332841E+10 | 0.212466E+10 | 0.00 | 1.00 | 01-JUL-17:12 | 0.00 | 01-JUL-00:10 | 52835.55 | 03-JUL-19:55 | 35180.84 | 05-JUL-17:10 | 27643.92 | 03-JUL-19:55 | 11238.52 | 03-JUL-19:55 | 0.00 | 01-JUL-00:10 |
August | 0.418701E+10 | 0.100351E+10 | 129.10 | 0.254195E+10 | 0.164506E+10 | 0.00 | 1.00 | 01-AUG-17:23 | 0.00 | 01-AUG-00:10 | 52363.52 | 04-AUG-17:20 | 32940.23 | 05-AUG-17:23 | 27468.86 | 04-AUG-17:40 | 11159.17 | 04-AUG-17:20 | 0.00 | 01-AUG-00:10 |
September | 0.140383E+10 | 0.361798E+09 | 61.33 | 0.109960E+10 | 0.304232E+09 | 0.00 | 1.00 | 10-SEP-15:25 | 0.00 | 01-SEP-00:10 | 45054.34 | 10-SEP-15:25 | 36005.21 | 10-SEP-15:25 | 9049.12 | 10-SEP-15:25 | 10240.42 | 10-SEP-15:25 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.138920E+11 | 0.334218E+10 | 423.09 | 0.882531E+10 | 0.506673E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.545307E+10 | 0.128507E+10 | 155.14 | 0.332841E+10 | 0.212466E+10 | 0.00 | 1.00 | 0.00 | 52835.55 | 36005.21 | 27643.92 | 11238.52 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.15 | 26.83 | 39.31 | 32.94 | 214.23 | 0.00 | 0.00 | 0.00 |
February | 96.22 | 47.20 | 49.02 | 68.61 | 165.72 | 0.00 | 0.00 | 0.00 |
March | 115.53 | 43.04 | 72.49 | 99.87 | 99.62 | 0.00 | 0.00 | 0.00 |
April | 168.42 | 83.23 | 85.19 | 189.01 | 64.85 | 0.00 | 0.00 | 0.00 |
May | 168.88 | 67.47 | 101.41 | 208.01 | 38.58 | 0.00 | 0.00 | 0.00 |
June | 197.85 | 85.58 | 112.27 | 254.99 | 34.58 | 0.00 | 0.00 | 0.00 |
July | 212.89 | 101.17 | 111.71 | 276.84 | 36.14 | 0.00 | 0.00 | 0.00 |
August | 185.54 | 84.86 | 100.68 | 242.26 | 42.19 | 0.00 | 0.00 | 0.00 |
September | 150.56 | 71.38 | 79.18 | 182.60 | 61.99 | 0.00 | 0.00 | 0.00 |
October | 105.38 | 46.97 | 58.41 | 111.17 | 74.00 | 0.00 | 0.00 | 0.00 |
November | 63.04 | 23.41 | 39.62 | 45.24 | 123.37 | 0.00 | 0.00 | 0.00 |
December | 48.69 | 23.16 | 25.53 | 29.37 | 190.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.74 | 58.71 | 73.03 | 145.45 | 95.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.69 | 23.16 | 25.53 | 29.37 | 34.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.89 | 101.17 | 112.27 | 276.84 | 214.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.15 | 26.83 | 39.31 | 32.94 | 214.23 | 0.00 | 0.00 | 0.00 |
February | 96.22 | 47.20 | 49.02 | 68.61 | 165.72 | 0.00 | 0.00 | 0.00 |
March | 115.53 | 43.04 | 72.49 | 99.87 | 99.62 | 0.00 | 0.00 | 0.00 |
April | 168.42 | 83.23 | 85.19 | 189.01 | 64.85 | 0.00 | 0.00 | 0.00 |
May | 168.88 | 67.47 | 101.41 | 208.01 | 38.58 | 0.00 | 0.00 | 0.00 |
June | 197.85 | 85.58 | 112.27 | 254.99 | 34.58 | 0.00 | 0.00 | 0.00 |
July | 212.89 | 101.17 | 111.71 | 276.84 | 36.14 | 0.00 | 0.00 | 0.00 |
August | 185.54 | 84.86 | 100.68 | 242.26 | 42.19 | 0.00 | 0.00 | 0.00 |
September | 150.56 | 71.38 | 79.18 | 182.60 | 61.99 | 0.00 | 0.00 | 0.00 |
October | 105.38 | 46.97 | 58.41 | 111.17 | 74.00 | 0.00 | 0.00 | 0.00 |
November | 63.04 | 23.41 | 39.62 | 45.24 | 123.37 | 0.00 | 0.00 | 0.00 |
December | 48.69 | 23.16 | 25.53 | 29.37 | 190.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.74 | 58.71 | 73.03 | 145.45 | 95.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.69 | 23.16 | 25.53 | 29.37 | 34.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.89 | 101.17 | 112.27 | 276.84 | 214.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.10 | 0.00 | 18.10 | 0.18 | 136.47 | 0.00 | 0.00 | 0.00 |
February | 22.95 | 0.00 | 22.95 | 2.23 | 106.17 | 0.00 | 0.00 | 0.00 |
March | 34.40 | 0.00 | 34.40 | 15.19 | 61.83 | 0.00 | 0.00 | 0.00 |
April | 39.80 | 0.27 | 39.53 | 28.79 | 38.57 | 0.00 | 0.00 | 0.00 |
May | 51.87 | 2.01 | 49.86 | 54.95 | 21.39 | 0.00 | 0.00 | 0.00 |
June | 60.48 | 5.46 | 55.02 | 71.81 | 19.14 | 0.00 | 0.00 | 0.00 |
July | 56.74 | 3.81 | 52.93 | 66.98 | 20.15 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 0.99 | 46.70 | 55.70 | 23.72 | 0.00 | 0.00 | 0.00 |
September | 36.47 | 0.02 | 36.45 | 34.72 | 36.79 | 0.00 | 0.00 | 0.00 |
October | 27.09 | 0.00 | 27.09 | 17.58 | 44.72 | 0.00 | 0.00 | 0.00 |
November | 18.95 | 0.00 | 18.95 | 4.95 | 76.28 | 0.00 | 0.00 | 0.00 |
December | 12.29 | 0.00 | 12.29 | 0.08 | 118.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.64 | 1.05 | 34.59 | 29.59 | 58.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.29 | 0.00 | 12.29 | 0.08 | 19.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.48 | 5.46 | 55.02 | 71.81 | 136.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.10 | 0.00 | 18.10 | 0.18 | 136.47 | 0.00 | 0.00 | 0.00 |
February | 22.95 | 0.00 | 22.95 | 2.23 | 106.17 | 0.00 | 0.00 | 0.00 |
March | 34.40 | 0.00 | 34.40 | 15.19 | 61.83 | 0.00 | 0.00 | 0.00 |
April | 39.80 | 0.27 | 39.53 | 28.79 | 38.57 | 0.00 | 0.00 | 0.00 |
May | 51.86 | 2.01 | 49.86 | 54.94 | 21.39 | 0.00 | 0.00 | 0.00 |
June | 60.48 | 5.46 | 55.02 | 71.80 | 19.14 | 0.00 | 0.00 | 0.00 |
July | 56.74 | 3.81 | 52.93 | 66.98 | 20.15 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 0.99 | 46.70 | 55.70 | 23.72 | 0.00 | 0.00 | 0.00 |
September | 36.47 | 0.02 | 36.45 | 34.72 | 36.79 | 0.00 | 0.00 | 0.00 |
October | 27.09 | 0.00 | 27.09 | 17.58 | 44.72 | 0.00 | 0.00 | 0.00 |
November | 18.95 | 0.00 | 18.95 | 4.95 | 76.28 | 0.00 | 0.00 | 0.00 |
December | 12.29 | 0.00 | 12.29 | 0.08 | 118.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.64 | 1.05 | 34.58 | 29.59 | 58.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.29 | 0.00 | 12.29 | 0.08 | 19.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.48 | 5.46 | 55.02 | 71.80 | 136.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.91 | 89.24 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.69 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.89 | 25.74 | 42.33 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.64 | 18.90 | 27.67 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.35 | 21.72 | 18.67 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.45 | 27.04 | 11.33 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 152.97 | 27.87 | 15.83 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 113.93 | 37.40 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.31 | 31.42 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.02 | 48.18 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.85 | 42.41 | 130.83 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.35 | 89.24 | 42.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.91 | 89.24 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.69 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.89 | 25.74 | 42.33 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.64 | 18.90 | 27.67 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.35 | 21.72 | 18.67 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.45 | 27.04 | 11.33 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 152.97 | 27.87 | 15.83 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 113.93 | 37.40 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.31 | 31.42 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.02 | 48.18 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.85 | 42.41 | 130.83 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.35 | 89.24 | 42.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.91 | 89.24 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.69 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.89 | 25.74 | 42.33 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.64 | 18.90 | 27.67 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.35 | 21.72 | 18.67 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.45 | 27.04 | 11.33 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 152.97 | 27.87 | 15.83 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 113.93 | 37.40 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.31 | 31.42 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.02 | 48.18 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.85 | 42.41 | 130.83 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.35 | 89.24 | 42.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.91 | 89.24 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.69 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.89 | 25.74 | 42.33 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.64 | 18.90 | 27.67 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.35 | 21.72 | 18.67 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.45 | 27.04 | 11.33 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 152.97 | 27.87 | 15.83 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 113.93 | 37.40 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.31 | 31.42 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.02 | 48.18 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.85 | 42.41 | 130.83 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.35 | 89.24 | 42.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.91 | 89.24 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.69 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.89 | 25.74 | 42.33 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.64 | 18.90 | 27.67 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.35 | 21.72 | 18.67 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.45 | 27.04 | 11.33 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 152.97 | 27.87 | 15.83 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 113.93 | 37.40 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.31 | 31.42 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.02 | 48.18 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.85 | 42.41 | 130.83 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.35 | 89.24 | 42.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.91 | 89.24 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.69 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.89 | 25.74 | 42.33 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.64 | 18.90 | 27.67 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.35 | 21.72 | 18.67 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.45 | 27.04 | 11.33 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 152.97 | 27.87 | 15.83 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 113.93 | 37.40 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.31 | 31.42 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.02 | 48.18 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.85 | 42.41 | 130.83 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.35 | 89.24 | 42.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.91 | 89.24 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.69 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.89 | 25.74 | 42.33 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.64 | 18.90 | 27.67 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.35 | 21.72 | 18.67 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.45 | 27.04 | 11.33 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 152.97 | 27.87 | 15.83 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 113.93 | 37.40 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.31 | 31.42 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.02 | 48.18 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.85 | 42.41 | 130.83 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.35 | 89.24 | 42.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.91 | 89.24 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.69 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.89 | 25.74 | 42.33 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.64 | 18.90 | 27.67 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.35 | 21.72 | 18.67 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.45 | 27.04 | 11.33 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 152.97 | 27.87 | 15.83 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 113.93 | 37.40 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.31 | 31.42 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.02 | 48.18 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.85 | 42.41 | 130.83 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.35 | 89.24 | 42.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.91 | 89.24 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.69 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.89 | 25.74 | 42.33 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.64 | 18.90 | 27.67 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.35 | 21.72 | 18.67 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.45 | 27.04 | 11.33 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 152.97 | 27.87 | 15.83 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 113.93 | 37.40 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.31 | 31.42 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.02 | 48.18 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.85 | 42.41 | 130.83 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.35 | 89.24 | 42.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.91 | 89.24 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.69 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.89 | 25.74 | 42.33 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.64 | 18.90 | 27.67 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.35 | 21.72 | 18.67 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.45 | 27.04 | 11.33 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 152.97 | 27.87 | 15.83 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 113.93 | 37.40 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.31 | 31.42 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.02 | 48.18 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.85 | 42.41 | 130.83 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.35 | 89.24 | 42.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177164E+09 | 71868735.54 | 0.105295E+09 | 88230075.00 | 0.573793E+09 |
February | 0.232773E+09 | 0.114177E+09 | 0.118596E+09 | 0.165983E+09 | 0.400914E+09 |
March | 0.309440E+09 | 0.115273E+09 | 0.194167E+09 | 0.267493E+09 | 0.266833E+09 |
April | 0.436545E+09 | 0.215723E+09 | 0.220821E+09 | 0.489925E+09 | 0.168096E+09 |
May | 0.452321E+09 | 0.180716E+09 | 0.271605E+09 | 0.557124E+09 | 0.103332E+09 |
June | 0.512839E+09 | 0.221835E+09 | 0.291004E+09 | 0.660922E+09 | 89626508.59 |
July | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.741499E+09 | 96798585.67 |
August | 0.496950E+09 | 0.227280E+09 | 0.269670E+09 | 0.648860E+09 | 0.113002E+09 |
September | 0.390252E+09 | 0.185011E+09 | 0.205242E+09 | 0.473307E+09 | 0.160685E+09 |
October | 0.282254E+09 | 0.125817E+09 | 0.156437E+09 | 0.297746E+09 | 0.198198E+09 |
November | 0.163395E+09 | 60689328.10 | 0.102706E+09 | 0.117273E+09 | 0.319785E+09 |
December | 0.130405E+09 | 62020230.89 | 68384856.96 | 78657885.88 | 0.511498E+09 |
Annual Sum or Average | 0.415453E+10 | 0.185139E+10 | 0.230314E+10 | 0.458702E+10 | 0.300256E+10 |
Minimum of Months | 0.130405E+09 | 60689328.10 | 68384856.96 | 78657885.88 | 89626508.59 |
Maximum of Months | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.741499E+09 | 0.573793E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177164E+09 | 71868735.54 | 0.105295E+09 | 88230075.00 | 0.573793E+09 |
February | 0.232773E+09 | 0.114177E+09 | 0.118596E+09 | 0.165983E+09 | 0.400914E+09 |
March | 0.309440E+09 | 0.115273E+09 | 0.194167E+09 | 0.267493E+09 | 0.266833E+09 |
April | 0.436545E+09 | 0.215723E+09 | 0.220821E+09 | 0.489925E+09 | 0.168096E+09 |
May | 0.452321E+09 | 0.180716E+09 | 0.271605E+09 | 0.557124E+09 | 0.103332E+09 |
June | 0.512839E+09 | 0.221835E+09 | 0.291004E+09 | 0.660922E+09 | 89626508.59 |
July | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.741499E+09 | 96798585.67 |
August | 0.496950E+09 | 0.227280E+09 | 0.269670E+09 | 0.648860E+09 | 0.113002E+09 |
September | 0.390252E+09 | 0.185011E+09 | 0.205242E+09 | 0.473307E+09 | 0.160685E+09 |
October | 0.282254E+09 | 0.125817E+09 | 0.156437E+09 | 0.297746E+09 | 0.198198E+09 |
November | 0.163395E+09 | 60689328.10 | 0.102706E+09 | 0.117273E+09 | 0.319785E+09 |
December | 0.130405E+09 | 62020230.89 | 68384856.96 | 78657885.88 | 0.511498E+09 |
Annual Sum or Average | 0.415453E+10 | 0.185139E+10 | 0.230314E+10 | 0.458702E+10 | 0.300256E+10 |
Minimum of Months | 0.130405E+09 | 60689328.10 | 68384856.96 | 78657885.88 | 89626508.59 |
Maximum of Months | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.741499E+09 | 0.573793E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48488126.83 | 0.00 | 48488126.83 | 477086.00 | 0.365533E+09 |
February | 55524446.54 | 0.00 | 55524446.54 | 5400955.53 | 0.256837E+09 |
March | 92146307.37 | 2499.55 | 92143807.82 | 40683742.39 | 0.165618E+09 |
April | 0.103167E+09 | 702085.40 | 0.102464E+09 | 74625061.67 | 99970738.27 |
May | 0.138917E+09 | 5379542.38 | 0.133537E+09 | 0.147166E+09 | 57300317.84 |
June | 0.156769E+09 | 14161738.08 | 0.142608E+09 | 0.186120E+09 | 49603944.83 |
July | 0.151972E+09 | 10196569.90 | 0.141776E+09 | 0.179401E+09 | 53971144.11 |
August | 0.127740E+09 | 2661251.59 | 0.125078E+09 | 0.149197E+09 | 63521636.99 |
September | 94536431.71 | 63161.34 | 94473270.37 | 89999448.34 | 95347803.87 |
October | 72562893.63 | 0.00 | 72562893.63 | 47088304.09 | 0.119769E+09 |
November | 49121072.59 | 0.00 | 49121072.59 | 12827683.03 | 0.197728E+09 |
December | 32924996.33 | 0.00 | 32924996.33 | 226505.51 | 0.317769E+09 |
Annual Sum or Average | 0.112387E+10 | 33166848.24 | 0.109070E+10 | 0.933213E+09 | 0.184297E+10 |
Minimum of Months | 32924996.33 | 0.00 | 32924996.33 | 226505.51 | 49603944.83 |
Maximum of Months | 0.156769E+09 | 14161738.08 | 0.142608E+09 | 0.186120E+09 | 0.365533E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48486565.90 | 0.00 | 48486565.90 | 476963.98 | 0.365534E+09 |
February | 55522718.22 | 0.00 | 55522718.22 | 5400336.68 | 0.256837E+09 |
March | 92143381.60 | 2499.43 | 92140882.17 | 40681021.46 | 0.165618E+09 |
April | 0.103164E+09 | 702052.49 | 0.102461E+09 | 74622104.94 | 99971022.54 |
May | 0.138913E+09 | 5379290.24 | 0.133533E+09 | 0.147161E+09 | 57300010.37 |
June | 0.156765E+09 | 14161074.30 | 0.142603E+09 | 0.186114E+09 | 49603566.38 |
July | 0.151968E+09 | 10196091.97 | 0.141771E+09 | 0.179395E+09 | 53970627.33 |
August | 0.127736E+09 | 2661126.85 | 0.125075E+09 | 0.149192E+09 | 63521243.60 |
September | 94533632.71 | 63158.38 | 94470474.33 | 89996361.67 | 95347288.18 |
October | 72560611.18 | 0.00 | 72560611.18 | 47085903.89 | 0.119769E+09 |
November | 49119433.09 | 0.00 | 49119433.09 | 12826704.77 | 0.197728E+09 |
December | 32923954.99 | 0.00 | 32923954.99 | 226448.92 | 0.317769E+09 |
Annual Sum or Average | 0.112383E+10 | 33165293.66 | 0.109067E+10 | 0.933178E+09 | 0.184297E+10 |
Minimum of Months | 32923954.99 | 0.00 | 32923954.99 | 226448.92 | 49603566.38 |
Maximum of Months | 0.156765E+09 | 14161074.30 | 0.142603E+09 | 0.186114E+09 | 0.365534E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 56000372.91 | 0.239016E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99068698.64 | 0.165379E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232189E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336681E+09 | 66711732.55 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.440985E+09 | 50624445.87 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.477824E+09 | 56306484.31 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486006E+09 | 72421467.26 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409718E+09 | 74633891.66 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295315E+09 | 96933848.98 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191009E+09 | 84150665.41 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85578490.81 | 0.124892E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 0.201997E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.314900E+10 | 0.133760E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 50624445.87 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486006E+09 | 0.239016E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 56000372.91 | 0.239016E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99068698.64 | 0.165379E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232189E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336681E+09 | 66711732.55 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.440985E+09 | 50624445.87 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.477824E+09 | 56306484.31 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486006E+09 | 72421467.26 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409718E+09 | 74633891.66 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295315E+09 | 96933848.98 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191009E+09 | 84150665.41 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85578490.81 | 0.124892E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 0.201997E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.314900E+10 | 0.133760E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 50624445.87 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486006E+09 | 0.239016E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 56000372.91 | 0.239016E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99068698.64 | 0.165379E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232189E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336681E+09 | 66711732.55 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.440985E+09 | 50624445.87 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.477824E+09 | 56306484.31 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486006E+09 | 72421467.26 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409718E+09 | 74633891.66 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295315E+09 | 96933848.98 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191009E+09 | 84150665.41 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85578490.81 | 0.124892E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 0.201997E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.314900E+10 | 0.133760E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 50624445.87 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486006E+09 | 0.239016E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 56000372.91 | 0.239016E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99068698.64 | 0.165379E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232189E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336681E+09 | 66711732.55 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.440985E+09 | 50624445.87 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.477824E+09 | 56306484.31 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486006E+09 | 72421467.26 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409718E+09 | 74633891.66 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295315E+09 | 96933848.98 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191009E+09 | 84150665.41 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85578490.81 | 0.124892E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 0.201997E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.314900E+10 | 0.133760E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 50624445.87 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486006E+09 | 0.239016E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 56000372.91 | 0.239016E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99068698.64 | 0.165379E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232189E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336681E+09 | 66711732.55 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.440985E+09 | 50624445.87 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.477824E+09 | 56306484.31 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486006E+09 | 72421467.26 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409718E+09 | 74633891.66 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295315E+09 | 96933848.98 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191009E+09 | 84150665.41 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85578490.81 | 0.124892E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 0.201997E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.314900E+10 | 0.133760E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 50624445.87 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486006E+09 | 0.239016E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 56000372.91 | 0.239016E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99068698.64 | 0.165379E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232189E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336681E+09 | 66711732.55 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.440985E+09 | 50624445.87 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.477824E+09 | 56306484.31 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486006E+09 | 72421467.26 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409718E+09 | 74633891.66 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295315E+09 | 96933848.98 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191009E+09 | 84150665.41 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85578490.81 | 0.124892E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 0.201997E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.314900E+10 | 0.133760E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 50624445.87 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486006E+09 | 0.239016E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 56000372.91 | 0.239016E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99068698.64 | 0.165379E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232189E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336681E+09 | 66711732.55 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.440985E+09 | 50624445.87 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.477824E+09 | 56306484.31 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486006E+09 | 72421467.26 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409718E+09 | 74633891.66 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295315E+09 | 96933848.98 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191009E+09 | 84150665.41 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85578490.81 | 0.124892E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 0.201997E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.314900E+10 | 0.133760E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 50624445.87 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486006E+09 | 0.239016E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 56000372.91 | 0.239016E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99068698.64 | 0.165379E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232189E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336681E+09 | 66711732.55 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.440985E+09 | 50624445.87 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.477824E+09 | 56306484.31 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486006E+09 | 72421467.26 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409718E+09 | 74633891.66 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295315E+09 | 96933848.98 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191009E+09 | 84150665.41 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85578490.81 | 0.124892E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 0.201997E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.314900E+10 | 0.133760E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 50624445.87 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486006E+09 | 0.239016E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 56000372.91 | 0.239016E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99068698.64 | 0.165379E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232189E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336681E+09 | 66711732.55 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.440985E+09 | 50624445.87 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.477824E+09 | 56306484.31 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486006E+09 | 72421467.26 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409718E+09 | 74633891.66 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295315E+09 | 96933848.98 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191009E+09 | 84150665.41 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85578490.81 | 0.124892E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 0.201997E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.314900E+10 | 0.133760E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 50624445.87 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486006E+09 | 0.239016E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 56000372.91 | 0.239016E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99068698.64 | 0.165379E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232189E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336681E+09 | 66711732.55 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.440985E+09 | 50624445.87 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.477824E+09 | 56306484.31 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486006E+09 | 72421467.26 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409718E+09 | 74633891.66 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295315E+09 | 96933848.98 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191009E+09 | 84150665.41 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85578490.81 | 0.124892E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 0.201997E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.314900E+10 | 0.133760E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38623879.16 | 50624445.87 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486006E+09 | 0.239016E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 50.87 | 686.04 | 168.50 | 53.67 | 114.83 | 0.00 | 0.00 |
February | 125.73 | 527.82 | 238.34 | 94.39 | 143.95 | 0.00 | 0.00 |
March | 224.51 | 317.31 | 299.87 | 86.08 | 213.79 | 0.00 | 0.00 |
April | 433.87 | 205.11 | 416.44 | 166.99 | 249.45 | 0.00 | 0.00 |
May | 524.34 | 118.39 | 441.48 | 138.96 | 302.52 | 0.00 | 0.00 |
June | 651.37 | 105.22 | 516.67 | 182.10 | 334.57 | 0.00 | 0.00 |
July | 686.10 | 111.04 | 539.25 | 209.96 | 329.29 | 0.00 | 0.00 |
August | 595.28 | 131.17 | 466.46 | 171.70 | 294.76 | 0.00 | 0.00 |
September | 433.27 | 196.18 | 374.06 | 142.80 | 231.26 | 0.00 | 0.00 |
October | 254.90 | 234.83 | 264.95 | 93.95 | 171.00 | 0.00 | 0.00 |
November | 94.35 | 393.28 | 163.98 | 46.83 | 117.15 | 0.00 | 0.00 |
December | 48.17 | 608.49 | 121.96 | 46.31 | 75.65 | 0.00 | 0.00 |
Annual Sum or Average | 344.70 | 301.91 | 334.75 | 119.52 | 215.24 | 0.00 | 0.00 |
Minimum of Months | 48.17 | 105.22 | 121.96 | 46.31 | 75.65 | 0.00 | 0.00 |
Maximum of Months | 686.10 | 686.04 | 539.25 | 209.96 | 334.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1179.34 | 7373.33 | 350.83 | 151.47 | 199.36 | 0.00 | 0.00 |
February | 2134.47 | 5648.90 | 482.05 | 240.10 | 241.94 | 0.00 | 0.00 |
March | 3973.93 | 2677.19 | 760.85 | 364.27 | 396.58 | 0.00 | 0.00 |
April | 5285.00 | 1362.79 | 1034.01 | 622.06 | 411.94 | 0.00 | 0.00 |
May | 6473.16 | 639.42 | 1242.44 | 699.11 | 543.33 | 0.00 | 0.00 |
June | 7168.57 | 662.81 | 1412.66 | 827.20 | 585.46 | 0.00 | 0.00 |
July | 6823.06 | 853.33 | 1423.59 | 876.76 | 546.84 | 0.00 | 0.00 |
August | 5568.13 | 889.86 | 1185.29 | 675.75 | 509.54 | 0.00 | 0.00 |
September | 4298.32 | 1205.41 | 920.54 | 534.73 | 385.81 | 0.00 | 0.00 |
October | 2762.68 | 1429.48 | 583.32 | 288.68 | 294.64 | 0.00 | 0.00 |
November | 1470.08 | 3201.27 | 347.07 | 127.52 | 219.55 | 0.00 | 0.00 |
December | 746.72 | 5434.97 | 237.38 | 115.44 | 121.94 | 0.00 | 0.00 |
Annual Sum or Average | 3999.35 | 2600.99 | 833.48 | 461.33 | 372.15 | 0.00 | 0.00 |
Minimum of Months | 746.72 | 639.42 | 237.38 | 115.44 | 121.94 | 0.00 | 0.00 |
Maximum of Months | 7168.57 | 7373.33 | 1423.59 | 876.76 | 585.46 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136238E+09 | 0.183748E+10 | 0.451302E+09 | 0.143737E+09 | 0.307564E+09 | 0.00 | 0.00 |
February | 0.304154E+09 | 0.127689E+10 | 0.576593E+09 | 0.228354E+09 | 0.348239E+09 | 0.00 | 0.00 |
March | 0.601330E+09 | 0.849880E+09 | 0.803169E+09 | 0.230550E+09 | 0.572619E+09 | 0.00 | 0.00 |
April | 0.112460E+10 | 0.531641E+09 | 0.107942E+10 | 0.432851E+09 | 0.646569E+09 | 0.00 | 0.00 |
May | 0.140440E+10 | 0.317090E+09 | 0.118247E+10 | 0.372190E+09 | 0.810281E+09 | 0.00 | 0.00 |
June | 0.168834E+10 | 0.272726E+09 | 0.133921E+10 | 0.471994E+09 | 0.867218E+09 | 0.00 | 0.00 |
July | 0.183766E+10 | 0.297408E+09 | 0.144433E+10 | 0.562347E+09 | 0.881979E+09 | 0.00 | 0.00 |
August | 0.159439E+10 | 0.351331E+09 | 0.124937E+10 | 0.459882E+09 | 0.789492E+09 | 0.00 | 0.00 |
September | 0.112304E+10 | 0.508498E+09 | 0.969575E+09 | 0.370148E+09 | 0.599427E+09 | 0.00 | 0.00 |
October | 0.682712E+09 | 0.628979E+09 | 0.709632E+09 | 0.251634E+09 | 0.457997E+09 | 0.00 | 0.00 |
November | 0.244555E+09 | 0.101938E+10 | 0.425030E+09 | 0.121379E+09 | 0.303652E+09 | 0.00 | 0.00 |
December | 0.129006E+09 | 0.162977E+10 | 0.326659E+09 | 0.124040E+09 | 0.202619E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108704E+11 | 0.952107E+10 | 0.105568E+11 | 0.376911E+10 | 0.678766E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129006E+09 | 0.272726E+09 | 0.326659E+09 | 0.121379E+09 | 0.202619E+09 | 0.00 | 0.00 |
Maximum of Months | 0.183766E+10 | 0.183748E+10 | 0.144433E+10 | 0.562347E+09 | 0.881979E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.315874E+10 | 0.197487E+11 | 0.939665E+09 | 0.405708E+09 | 0.533957E+09 | 0.00 | 0.00 |
February | 0.516370E+10 | 0.136658E+11 | 0.116617E+10 | 0.580860E+09 | 0.585312E+09 | 0.00 | 0.00 |
March | 0.106438E+11 | 0.717057E+10 | 0.203786E+10 | 0.975674E+09 | 0.106219E+10 | 0.00 | 0.00 |
April | 0.136987E+11 | 0.353234E+10 | 0.268014E+10 | 0.161239E+10 | 0.106775E+10 | 0.00 | 0.00 |
May | 0.173377E+11 | 0.171262E+10 | 0.332776E+10 | 0.187250E+10 | 0.145526E+10 | 0.00 | 0.00 |
June | 0.185809E+11 | 0.171801E+10 | 0.366161E+10 | 0.214410E+10 | 0.151751E+10 | 0.00 | 0.00 |
July | 0.182749E+11 | 0.228555E+10 | 0.381296E+10 | 0.234830E+10 | 0.146465E+10 | 0.00 | 0.00 |
August | 0.149137E+11 | 0.238341E+10 | 0.317469E+10 | 0.180993E+10 | 0.136476E+10 | 0.00 | 0.00 |
September | 0.111413E+11 | 0.312444E+10 | 0.238604E+10 | 0.138603E+10 | 0.100001E+10 | 0.00 | 0.00 |
October | 0.739957E+10 | 0.382873E+10 | 0.156236E+10 | 0.773194E+09 | 0.789166E+09 | 0.00 | 0.00 |
November | 0.381045E+10 | 0.829768E+10 | 0.899606E+09 | 0.330533E+09 | 0.569073E+09 | 0.00 | 0.00 |
December | 0.200002E+10 | 0.145570E+11 | 0.635808E+09 | 0.309203E+09 | 0.326605E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126123E+12 | 0.820249E+11 | 0.262847E+11 | 0.145484E+11 | 0.117363E+11 | 0.00 | 0.00 |
Minimum of Months | 0.200002E+10 | 0.171262E+10 | 0.635808E+09 | 0.309203E+09 | 0.326605E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185809E+11 | 0.197487E+11 | 0.381296E+10 | 0.234830E+10 | 0.151751E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.108441E+10 | -994288781.1 | 0.00 | 0.00 | 744.00 | 0.00 | -90123153.5 | 59.95 | 0.00 | 0.00 |
February | 0.101271E+10 | -931396969.6 | 0.00 | 0.00 | 672.00 | 0.00 | -81310416.0 | 59.95 | 0.00 | 0.00 |
March | 0.116710E+10 | -0.107787E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -89231303.2 | 59.95 | 0.00 | 0.00 |
April | 0.104806E+10 | -963505912.1 | 0.00 | 0.00 | 720.00 | 0.00 | -84555889.1 | 59.95 | 0.00 | 0.00 |
May | 0.102658E+10 | -944010720.9 | 0.00 | 0.00 | 744.00 | 0.00 | -82566685.5 | 59.95 | 0.00 | 0.00 |
June | 0.952605E+09 | -878259154.3 | 0.00 | 0.00 | 720.00 | 0.00 | -74346316.5 | 59.95 | 0.00 | 0.00 |
July | 0.875913E+09 | -801847047.7 | 0.00 | 0.00 | 744.00 | 0.00 | -74066321.9 | 59.95 | 0.00 | 0.00 |
August | 0.913632E+09 | -838910069.2 | 0.00 | 0.00 | 744.00 | 0.00 | -74722407.7 | 59.95 | 0.00 | 0.00 |
September | 0.865673E+09 | -790319395.7 | 0.00 | 0.00 | 720.00 | 0.00 | -75353702.9 | 59.95 | 0.00 | 0.00 |
October | 0.918723E+09 | -831284960.9 | 0.00 | 0.00 | 744.00 | 0.00 | -87437841.6 | 59.95 | 0.00 | 0.00 |
November | 0.938736E+09 | -852415967.0 | 0.00 | 0.00 | 720.00 | 0.00 | -86320414.4 | 59.95 | 0.00 | 0.00 |
December | 0.103640E+10 | -946293823.4 | 0.00 | 0.00 | 744.00 | 0.00 | -90108826.5 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.118405E+11 | -0.108504E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -990143278.8 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.865673E+09 | -0.107787E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -90123153.5 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.116710E+10 | -790319395.7 | 0.00 | 0.00 | 744.00 | 0.00 | -74066321.9 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.94 | 0.88 | 01-JAN-10:09 | 122.09 | 9.12 | 0.00 | 30.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.93 | 0.88 | 03-FEB-10:30 | 131.14 | 9.24 | 0.00 | 60.17 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.91 | 0.88 | 01-MAR-08:39 | 215.13 | 11.77 | 0.00 | 164.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.90 | 0.88 | 02-APR-14:39 | 239.89 | 11.77 | 0.00 | 190.33 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.90 | 0.88 | 01-MAY-07:10 | 798.49 | 12.54 | 0.00 | 265.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.90 | 0.88 | 01-JUN-06:49 | 1989.55 | 12.88 | 0.00 | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.90 | 0.88 | 01-JUL-07:10 | 1832.96 | 13.59 | 20.00 | 278.17 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.90 | 0.88 | 01-AUG-07:49 | 1103.05 | 12.99 | 14.67 | 260.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.91 | 0.88 | 01-SEP-07:19 | 212.64 | 11.67 | 0.00 | 161.83 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.92 | 0.88 | 01-OCT-09:20 | 162.73 | 10.29 | 0.00 | 93.33 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.93 | 0.88 | 01-NOV-09:30 | 139.43 | 9.76 | 0.00 | 51.67 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.96 | 0.88 | 04-DEC-12:20 | 79.37 | 6.96 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.91 | 714.50 | 11.50 | 34.67 | 1839.17 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 186.17 | 0.90 | 0.88 | 79.37 | 6.96 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 428.67 | 0.96 | 0.88 | 1989.55 | 13.59 | 20.00 | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.78 | 0.63 | 24-JAN-14:39 | 350.33 | 24.13 | 122.83 | 34.33 | 126.38 | 21.25 | 110.50 | 0.00 |
February | 226.83 | 0.76 | 0.61 | 06-FEB-14:30 | 641.58 | 25.03 | 142.67 | 58.00 | 147.61 | 21.49 | 139.83 | 2.00 |
March | 334.33 | 0.74 | 0.61 | 03-MAR-16:10 | 401.37 | 23.69 | 205.50 | 98.50 | 293.87 | 24.05 | 224.33 | 41.00 |
April | 285.17 | 0.71 | 0.61 | 03-APR-13:30 | 473.67 | 23.12 | 171.00 | 114.83 | 463.95 | 24.00 | 229.17 | 80.17 |
May | 428.67 | 0.72 | 0.61 | 01-MAY-13:30 | 325.85 | 21.74 | 237.83 | 130.00 | 308.65 | 22.83 | 301.00 | 75.33 |
June | 400.67 | 0.69 | 0.61 | 01-JUN-16:19 | 382.08 | 22.24 | 259.67 | 187.33 | 463.71 | 23.52 | 316.17 | 100.33 |
July | 414.00 | 0.69 | 0.61 | 01-JUL-13:20 | 387.87 | 22.51 | 260.17 | 186.17 | 513.73 | 23.74 | 331.83 | 125.33 |
August | 410.83 | 0.71 | 0.61 | 01-AUG-14:20 | 387.46 | 22.32 | 247.17 | 156.33 | 402.81 | 23.31 | 295.83 | 102.67 |
September | 326.50 | 0.72 | 0.61 | 01-SEP-14:09 | 554.51 | 24.79 | 204.67 | 113.00 | 473.74 | 25.31 | 255.00 | 73.17 |
October | 325.17 | 0.76 | 0.61 | 01-OCT-14:30 | 444.95 | 24.48 | 194.83 | 74.50 | 183.85 | 23.39 | 203.00 | 20.83 |
November | 254.83 | 0.81 | 0.61 | 03-NOV-15:09 | 259.83 | 22.63 | 128.17 | 22.33 | 115.02 | 20.88 | 114.50 | 0.00 |
December | 186.17 | 0.83 | 0.65 | 02-DEC-14:30 | 217.00 | 22.25 | 71.33 | 13.83 | 92.09 | 19.59 | 38.67 | 0.00 |
Annual Sum or Average | 3807.33 | 0.73 | 403.09 | 23.12 | 2245.83 | 1189.17 | 327.86 | 23.05 | 2559.83 | 620.83 | ||
Minimum of Months | 186.17 | 0.69 | 0.61 | 217.00 | 21.74 | 71.33 | 13.83 | 92.09 | 19.59 | 38.67 | 0.00 | |
Maximum of Months | 428.67 | 0.83 | 0.65 | 641.58 | 25.03 | 260.17 | 187.33 | 513.73 | 25.31 | 331.83 | 125.33 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134105E+11 | 26793.89 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.987580E+10 | 26793.89 | 01-FEB-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.766279E+10 | 26793.89 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388655E+10 | 26793.89 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.688925E+09 | 26793.89 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48824312.54 | 26793.89 | 05-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.248412E+09 | 26793.89 | 27-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245261E+10 | 26793.89 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.606118E+10 | 26793.89 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103619E+11 | 26793.89 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.546975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134105E+11 | 26793.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.499193E+11 | 69198.39 | 02-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359811E+11 | 69198.39 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218576E+11 | 69198.39 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.816883E+10 | 69198.39 | 02-APR-19:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.461149E+09 | 41000.22 | 01-MAY-05:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71983561.72 | 16723.50 | 30-SEP-04:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.351914E+10 | 60937.80 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205819E+11 | 69198.39 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393716E+11 | 69198.39 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.499193E+11 | 69198.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241766E+12 | 219568.75 | 18-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163204E+12 | 212145.33 | 01-FEB-20:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.871647E+11 | 149392.98 | 06-MAR-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191281E+11 | 89206.19 | 02-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.259252E+09 | 13354.46 | 02-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185921E+10 | 17581.67 | 24-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.909066E+11 | 146994.54 | 26-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185824E+12 | 219568.75 | 08-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241766E+12 | 219568.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.178359E+09 | 0.126771E+09 | 6080.10 | 18-APR-15:10 | 4447.25 | 0.00 |
May | 0.00 | 0.00 | 0.399831E+09 | 0.308389E+09 | 6786.01 | 31-MAY-15:10 | 5735.42 | 0.00 |
June | 0.00 | 0.00 | 0.382302E+10 | 0.285570E+10 | 21732.29 | 26-JUN-05:45 | 10383.04 | 0.00 |
July | 0.00 | 0.00 | 0.623401E+10 | 0.440692E+10 | 21361.47 | 27-JUL-05:02 | 9351.94 | 0.00 |
August | 0.00 | 0.00 | 0.630202E+10 | 0.448262E+10 | 23434.70 | 04-AUG-05:01 | 8840.28 | 0.00 |
September | 0.00 | 0.00 | 0.235147E+10 | 0.206440E+10 | 19941.09 | 11-SEP-05:02 | 12248.77 | 0.00 |
October | 0.00 | 0.00 | 703.57 | 703.57 | 1.17 | 20-OCT-15:00 | 1.17 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192887E+11 | 0.142448E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.630202E+10 | 0.448262E+10 | 23434.70 | 12248.77 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.284813E+10 | 0.185536E+10 | 47738.34 | 29-JUN-19:35 | 31223.19 | 0.00 |
July | 0.00 | 0.00 | 0.545307E+10 | 0.332841E+10 | 52835.55 | 03-JUL-19:55 | 25191.63 | 0.00 |
August | 0.00 | 0.00 | 0.418701E+10 | 0.254195E+10 | 52363.52 | 04-AUG-17:20 | 25255.94 | 0.00 |
September | 0.00 | 0.00 | 0.140383E+10 | 0.109960E+10 | 45054.34 | 10-SEP-15:25 | 36005.21 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138920E+11 | 0.882531E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.545307E+10 | 0.332841E+10 | 52835.55 | 36005.21 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139668E+10 | 0.08 | 522.51 | 01-JAN-00:03 | 0.08 |
February | 0.123146E+10 | 0.08 | 522.51 | 01-FEB-00:02 | 0.08 |
March | 0.104644E+10 | 0.06 | 522.51 | 01-MAR-00:02 | 0.08 |
April | 0.397554E+09 | 0.02 | 522.51 | 01-APR-00:05 | 0.08 |
May | 16929406.09 | 0.00 | 522.51 | 01-MAY-22:05 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.102360E+09 | 0.01 | 522.51 | 16-OCT-22:35 | 0.08 |
November | 0.884875E+09 | 0.05 | 522.51 | 10-NOV-00:50 | 0.08 |
December | 0.139072E+10 | 0.08 | 522.51 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.646701E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139668E+10 | 0.08 | 522.51 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121794E+10 | 0.72 | 1074.01 | 02-JAN-06:01 | 0.95 |
February | 0.107862E+10 | 0.64 | 1074.01 | 01-FEB-02:62 | 0.96 |
March | 0.121686E+10 | 0.52 | 1074.01 | 18-MAR-13:30 | 0.95 |
April | 0.109661E+10 | 0.42 | 1074.01 | 14-APR-10:20 | 0.94 |
May | 0.111705E+10 | 0.38 | 1074.01 | 24-MAY-07:00 | 0.95 |
June | 0.111448E+10 | 0.38 | 1074.01 | 06-JUN-06:20 | 0.94 |
July | 0.108427E+10 | 0.36 | 1074.01 | 07-JUL-09:50 | 0.93 |
August | 0.116710E+10 | 0.39 | 1074.01 | 02-AUG-16:40 | 0.94 |
September | 0.107236E+10 | 0.37 | 1074.01 | 13-SEP-07:20 | 0.94 |
October | 0.108680E+10 | 0.38 | 1074.01 | 02-OCT-07:40 | 0.95 |
November | 0.108227E+10 | 0.49 | 1074.01 | 06-NOV-17:00 | 0.94 |
December | 0.116808E+10 | 0.61 | 1074.01 | 01-DEC-06:01 | 0.95 |
Annual Sum or Average | 0.135024E+11 | 0.47 | |||
Minimum of Months | 0.107236E+10 | 0.36 | 1074.01 | 0.93 | |
Maximum of Months | 0.121794E+10 | 0.72 | 1074.01 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182130E+10 | 0.67 | 1848.23 | 02-JAN-00:03 | 0.92 |
February | 0.146875E+10 | 0.64 | 1848.23 | 01-FEB-00:02 | 0.93 |
March | 0.128246E+10 | 0.54 | 1848.23 | 01-MAR-00:02 | 0.93 |
April | 0.922340E+09 | 0.40 | 1848.23 | 02-APR-19:42 | 0.92 |
May | 0.772736E+09 | 0.23 | 1095.08 | 01-MAY-05:37 | 0.92 |
June | 0.771287E+09 | 0.23 | 1709.13 | 30-JUN-17:10 | 0.88 |
July | 0.761352E+09 | 0.22 | 1848.23 | 03-JUL-17:10 | 0.91 |
August | 0.797183E+09 | 0.22 | 1733.74 | 02-AUG-17:12 | 0.88 |
September | 0.734010E+09 | 0.21 | 849.51 | 30-SEP-06:10 | 0.61 |
October | 0.818318E+09 | 0.33 | 1627.60 | 27-OCT-05:01 | 0.92 |
November | 0.116934E+10 | 0.51 | 1848.23 | 13-NOV-06:01 | 0.92 |
December | 0.159669E+10 | 0.64 | 1848.23 | 01-DEC-06:01 | 0.92 |
Annual Sum or Average | 0.129158E+11 | 0.40 | |||
Minimum of Months | 0.734010E+09 | 0.21 | 849.51 | 0.61 | |
Maximum of Months | 0.182130E+10 | 0.67 | 1848.23 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.121794E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.107862E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.121686E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.113862E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.121024E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.195840E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.242742E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.254051E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.160529E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.108680E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.108227E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.116808E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.177311E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107862E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.254051E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.182130E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.146875E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.128246E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.922340E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.772736E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.146308E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.204643E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.180069E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.109581E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.818318E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.116934E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.159669E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.162580E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.772736E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.204643E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.121794E+10 | 0.00 | 0.134105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107862E+10 | 0.00 | 0.987580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121686E+10 | 0.00 | 0.766279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109661E+10 | 0.178359E+09 | 0.388655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111705E+10 | 0.399831E+09 | 0.688925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111448E+10 | 0.382302E+10 | 48824312.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108427E+10 | 0.623401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116710E+10 | 0.630202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107236E+10 | 0.235147E+10 | 0.248412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108680E+10 | 703.57 | 0.245261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108227E+10 | 0.00 | 0.606118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116808E+10 | 0.00 | 0.103619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135024E+11 | 0.192887E+11 | 0.546975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121794E+10 | 0.630202E+10 | 0.134105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182130E+10 | 0.00 | 0.499193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146875E+10 | 0.00 | 0.359811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128246E+10 | 0.00 | 0.218576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922340E+09 | 0.00 | 0.816883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.772736E+09 | 0.00 | 0.461149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.771287E+09 | 0.283123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761352E+09 | 0.531337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.797183E+09 | 0.415491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.734010E+09 | 0.139923E+10 | 71983561.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.818318E+09 | 0.00 | 0.351914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116934E+10 | 0.00 | 0.205819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159669E+10 | 0.00 | 0.393716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129158E+11 | 0.136987E+11 | 0.179933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.734010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182130E+10 | 0.531337E+10 | 0.499193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.121794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109661E+10 | 0.00 | 0.00 | 0.00 | 42016823.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111705E+10 | 0.00 | 0.00 | 0.00 | 93188816.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111448E+10 | 0.00 | 0.00 | 0.00 | 0.843919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108427E+10 | 0.00 | 0.00 | 0.00 | 0.134316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116710E+10 | 0.00 | 0.00 | 0.00 | 0.137341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107236E+10 | 0.00 | 0.00 | 0.00 | 0.532928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108680E+10 | 0.00 | 0.00 | 0.00 | 169.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135024E+11 | 0.00 | 0.00 | 0.00 | 0.422862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121794E+10 | 0.00 | 0.00 | 0.00 | 0.137341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.182130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.772736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.771287E+09 | 0.00 | 0.00 | 0.00 | 0.691798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761352E+09 | 0.00 | 0.00 | 0.00 | 0.128507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.797183E+09 | 0.00 | 0.00 | 0.00 | 0.100351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.734010E+09 | 0.00 | 0.00 | 0.00 | 0.361798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.818318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129158E+11 | 0.00 | 0.00 | 0.00 | 0.334218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.734010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182130E+10 | 0.00 | 0.00 | 0.00 | 0.128507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383463E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299221E+10 | 0.00 | 0.00 | 0.13 |
March | 20878723.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243680E+10 | 0.00 | 0.00 | 0.13 |
April | 0.230587E+09 | 24799444.03 | 0.00 | 21541.50 | 10207524.38 | 0.143122E+10 | 45894873.50 | 0.00 | 0.13 |
May | 0.672796E+09 | 30465080.31 | 0.00 | 198898.14 | 173861.50 | 0.147591E+09 | 0.349795E+09 | 0.00 | 0.20 |
June | 0.209293E+09 | 0.475582E+09 | 0.00 | 2458634.76 | 0.00 | 6456844.38 | 0.124327E+10 | 0.00 | 0.49 |
July | 3594879.52 | 0.693119E+09 | 0.00 | 3957079.41 | 308887.62 | 0.00 | 0.110383E+10 | 0.00 | 0.57 |
August | 10148576.15 | 0.753300E+09 | 0.00 | 3564357.80 | 395432.06 | 0.00 | 0.129651E+10 | 0.00 | 0.64 |
September | 0.347043E+09 | 0.129311E+09 | 0.00 | 2477467.54 | 0.00 | 97895684.99 | 0.141759E+10 | 0.00 | 0.39 |
October | 0.356583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113368E+10 | 0.00 | 0.00 | 0.13 |
November | 0.122069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207186E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321060E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.197299E+10 | 0.210658E+10 | 0.00 | 12677979.14 | 11085705.56 | 0.173630E+11 | 0.545689E+10 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.672796E+09 | 0.753300E+09 | 0.00 | 3957079.41 | 10207524.38 | 0.383463E+10 | 0.141759E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126304E+11 | 0.00 | 0.00 | 0.17 |
February | 0.775201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883640E+10 | 0.00 | 0.00 | 0.18 |
March | 0.235306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468878E+10 | 0.00 | 0.00 | 0.19 |
April | 0.325044E+10 | 0.00 | 0.00 | 0.00 | 0.130581E+09 | 0.130522E+10 | 0.00 | 0.00 | 0.18 |
May | 0.245575E+10 | 0.00 | 0.00 | 0.00 | 41680805.34 | 20169035.16 | 0.00 | 0.00 | 0.18 |
June | 0.227327E+10 | 0.438979E+09 | 0.00 | 376578.08 | 9303773.01 | 0.00 | 0.275815E+09 | 0.00 | 0.21 |
July | 0.113727E+10 | 0.777520E+09 | 0.00 | 2355299.30 | 0.00 | 0.00 | 0.127929E+10 | 0.00 | 0.26 |
August | 0.134637E+10 | 0.727508E+09 | 0.00 | 2068170.07 | 1694868.36 | 0.00 | 0.125185E+10 | 0.00 | 0.26 |
September | 0.295665E+10 | 0.123038E+09 | 0.00 | 690878.06 | 28143.05 | 0.00 | 0.360134E+09 | 0.00 | 0.20 |
October | 0.344533E+10 | 0.00 | 0.00 | 0.00 | 5616392.84 | 0.211132E+09 | 0.00 | 0.00 | 0.17 |
November | 0.175756E+10 | 0.00 | 31061.48 | 0.00 | 59766.52 | 0.460676E+10 | 0.00 | 749.20 | 0.17 |
December | 0.412667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987123E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.224056E+11 | 0.206705E+10 | 31061.48 | 5490925.51 | 0.188965E+09 | 0.421701E+11 | 0.316709E+10 | 749.20 | 0.20 |
Minimum of Months | 0.242052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.344533E+10 | 0.777520E+09 | 31061.48 | 2355299.30 | 0.130581E+09 | 0.126304E+11 | 0.127929E+10 | 749.20 | 0.26 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.361508E+12 | 0.176641E+12 | 0.00 | 0.167071E+11 | 0.861807E+11 |
February | 0.432761E+12 | 0.123266E+12 | 0.00 | 0.126038E+11 | 0.597519E+11 |
March | 0.720383E+12 | 0.843987E+11 | 0.00 | 0.949952E+10 | 0.349167E+11 |
April | 0.886684E+12 | 0.368610E+11 | 0.00 | 0.609780E+10 | 0.105649E+11 |
May | 0.105879E+13 | 0.180762E+11 | 0.00 | 0.357398E+10 | 0.109139E+10 |
June | 0.112294E+13 | 0.222619E+11 | 0.00 | 0.309333E+10 | 0.822966E+10 |
July | 0.115185E+13 | 0.278546E+11 | 0.00 | 0.206802E+10 | 0.143153E+11 |
August | 0.997174E+12 | 0.333342E+11 | 0.00 | 0.244376E+10 | 0.128660E+11 |
September | 0.689345E+12 | 0.376542E+11 | 0.00 | 0.493283E+10 | 0.480220E+10 |
October | 0.478738E+12 | 0.328791E+11 | 0.00 | 0.514111E+10 | 0.333012E+10 |
November | 0.258394E+12 | 0.876807E+11 | 0.00 | 0.855815E+10 | 0.343295E+11 |
December | 0.175128E+12 | 0.139378E+12 | 0.00 | 0.134945E+11 | 0.674381E+11 |
Annual Sum or Average | 0.833370E+13 | 0.820285E+12 | 0.00 | 0.882139E+11 | 0.337816E+12 |
Minimum of Months | 0.175128E+12 | 0.180762E+11 | 0.00 | 0.206802E+10 | 0.109139E+10 |
Maximum of Months | 0.115185E+13 | 0.176641E+12 | 0.00 | 0.167071E+11 | 0.861807E+11 |