Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:20:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1565.77 | 323.83 | 323.83 |
Net Site Energy | 1458.96 | 301.74 | 301.74 |
Total Source Energy | 2382.42 | 492.73 | 492.73 |
Net Source Energy | 2044.16 | 422.77 | 422.77 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1236.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 99.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 11.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 328.91 | 1236.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1236.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 99.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 31.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 11.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1236.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 7.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 99.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 31.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 11.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.52 | 255.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 68.03 | 255.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.52 | 255.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 68.03 | 255.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 111.814 | 34.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -5.01 | -1.5 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 106.807 | 32.47 |
Electricity Coming From Utility | 237.945 | 72.34 |
Surplus Electricity Going To Utility | 15.840 | 4.82 |
Net Electricity From Utility | 222.105 | 67.53 |
Total On-Site and Utility Electric Sources | 328.912 | 100.00 |
Total Electricity End Uses | 328.912 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 77.67 |
Time Setpoint Not Met During Occupied Cooling | 3.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3153.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.1633 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.1633 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3473 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:00 | 18-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 346036.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9810.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7297.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4245.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1228.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32616.86 | 346036.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 346036.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 9810.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 7297.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1939.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1228.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1340.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 314.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 101.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1041.67 | 1340.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 277.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 65.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 215.44 | 277.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 277.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 65.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 215.44 | 277.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.940188 |
ZONE2 FINE STORAGE DIRECT AIR | 1.62 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 5.58 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 5.58 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 217850.80 |
PSZ-OFFICE HEATING COIL | 26140.61 |
PSZ-FINE STORAGE HEATING COIL | 66115.37 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 217850.81 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.940188 | 0.940188 | 0.940188 | 0.940188 | 0.940188 | 0.940188 | 1.00 | 1.00 | 0.940188 |
PSZ-FINE STORAGE | 1.62 | 1.62 | 1.62 | 1.62 | 1.62 | 1.62 | 1.00 | 1.00 | 1.62 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.940188 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.62 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.940188 | 1040.94 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.62 | 1731.30 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.940188 | 0.940188 | 0.940188 | 0.940188 | 18042.25 | 26140.61 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.62 | 1.62 | 1.62 | 1.07 | 40177.94 | 66115.37 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.940190 | 0.470094 | 0.626793 | 18042.25 | 9021.12 | 0.793140 | 0.793140 |
PSZ-FINE STORAGE COOLING COIL | 1.62 | 0.808983 | 1.08 | 40177.94 | 20088.97 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.163 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.237 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1459.960 | 6.163 | 114.518 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1459.960 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3574 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3330 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6144 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.946 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1333 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5514E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6144 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.798 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.904 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.528 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3395 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.423 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.06 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.528 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
2 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
3 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
4 | 2 | 0.92894805E-09 | 0.33911764E-13 | 0.21779261E-14 | 0.0000000 |
5 | 1 | -5.2160150 | 0.41827095E-04 | -0.44821328E-04 | 0.18401191E-09 |
6 | 0 | 5.5734381 | 0.35738136 | 0.35746801 | |
7 | 4 | 0.81205461E-12 | -0.60820818E-16 | 0.53959138E-14 | 0.11194769E-15 |
8 | 3 | -0.39487908E-03 | 0.23668407E-06 | -0.57379545E-04 | 0.15580508E-12 |
9 | 2 | 1.7634853 | 0.51193665E-02 | 1.1586669 | -0.75705256E-04 |
10 | 1 | -7.0973464 | 0.13173731 | -17.214220 | 0.33800211 |
11 | 0 | 5.5547270 | 0.83614094E-01 | 16.276082 | |
12 | 4 | 0.75524091E-12 | 0.18585927E-15 | -0.24619336E-14 | 0.12165746E-15 |
13 | 3 | -0.37591709E-03 | 0.42679598E-06 | -0.54444663E-04 | 0.14493025E-12 |
14 | 2 | 1.7186597 | 0.94202666E-02 | 1.1245767 | -0.72068922E-04 |
15 | 1 | -7.1564116 | 0.24550773 | -16.996678 | 0.32938266 |
16 | 0 | 5.8501984 | 0.15714209 | 16.284226 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.9455516 | 2.9455516 | 2.9455516 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.31875017E-08 | -0.23223167E-14 | 0.11745088E-14 | -0.42051331E-16 |
55 | 6 | 0.38616340E-05 | 0.25494915E-08 | 0.31950331E-02 | -0.26802615E-04 |
56 | 5 | -0.27022284E-03 | 0.15072689E-05 | -0.22401801 | 0.19587403E-02 |
57 | 4 | 0.61670379E-02 | 0.68550054E-04 | 4.8344327 | -0.45311958E-01 |
58 | 3 | -0.54002887E-01 | 0.54467183E-03 | -38.049021 | 0.39895888 |
59 | 2 | 0.19154071 | 0.90547994E-03 | 116.53767 | -1.4186579 |
60 | 1 | -0.27632409 | 0.27557907E-03 | -143.93893 | 2.0495597 |
61 | 0 | 0.13468807 | 0.66882102E-05 | 60.838472 | |
62 | 7 | -0.77687407E-08 | 0.22327722E-15 | -0.37072247E-14 | 0.17899991E-16 |
63 | 6 | 0.20649052E-05 | 0.10720148E-08 | 0.32011002E-02 | -0.26853511E-04 |
64 | 5 | -0.12245401E-03 | 0.62775152E-06 | -0.22436262 | 0.19617821E-02 |
65 | 4 | 0.26426329E-02 | 0.28408139E-04 | 4.8401680 | -0.45367094E-01 |
66 | 3 | -0.22645990E-01 | 0.22478354E-03 | -38.081398 | 0.39931679 |
67 | 2 | 0.79613263E-01 | 0.37221057E-03 | 116.60066 | -1.4195005 |
68 | 1 | -0.11438919 | 0.11271005E-03 | -143.97600 | 2.0501690 |
69 | 0 | 0.55641142E-01 | 0.27215667E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.24619336E-14 | 0.18585927E-15 | 0.75524091E-12 | 0.12165746E-15 |
85 | 3 | -0.54444663E-04 | 0.42679598E-06 | -0.37591709E-03 | 0.14493025E-12 |
86 | 2 | 1.1245767 | 0.94202666E-02 | 1.7186597 | -0.72068922E-04 |
87 | 1 | -16.996678 | 0.24550773 | -7.1564116 | 0.32938266 |
88 | 0 | 16.284226 | 0.15714209 | 5.8501984 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | 34 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
5 | SKYLIGHT_U_0.47_SHGC_0.4 | 38 | 1 | VerySmooth | 2.672 | 2.672 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.555 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.40629E-002 | 0.31435 | 0.46917 | 0.46917 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11822 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.553 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 3.833E-002 | 1.618E-004 | 2.498E-004 | 0.137 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.195 | 1.399E-004 | 8.913E-005 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 1.834 | 5.723E-004 | 3.738E-004 | 0.187 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0426E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7455E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6964E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8300E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9108E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3918E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0880E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2172E-004 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5266E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0600E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1822E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1637E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1355E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8576E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9979E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4455E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2037E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5775E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7133E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1756E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3627E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1682E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1771E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0426E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0171E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8900E-004 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5219E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8046E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6087E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0384E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.7783E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.8899E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.1522E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.1921E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.9708E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.9477E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9807E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.2338E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.0432E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.4224E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.5042E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.3900E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.0746E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.3415E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.1742E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.0089E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.4989E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.9551E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.1362E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1153E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7899E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.3398E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.7385E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1881E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.6900E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.9620E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.2292E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1190E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.5968E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3359E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.7384E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1881E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9082.68325 | 10899.21990 | 0.78349 | 0.94019 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53623E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10766.99358 | 12920.39230 | 0.31688 | 0.38025 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 20049.82313 | 24059.78776 | 1.34830 | 1.61797 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 33911.98313 | 40694.37976 | 0.84060 | 1.00872 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 181542.33810 | 217850.80573 | 4.64986 | 5.57983 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13625.26 | 0.94019 | 0.94019 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 13894.38 | 0.38025 | 0.38025 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 29640.46 | 1.61797 | 1.61797 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 48926.58 | 1.00872 | 1.00872 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94019 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.61797 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.57983 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 5.57983 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 217850.80037 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 217850.80573 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94019 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94019 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94019 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94019 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94019 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.94019 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.61797 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.61797 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.61797 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.61797 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.61797 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.61797 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.94019 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.61797 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94019 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94019 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1040.93746 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94019 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94019 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94019 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94019 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94019 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47009 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62679 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18042.25000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9021.12500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79314 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79314 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18042.25000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26140.61282 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26140.61282 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.61797 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.61797 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1731.29984 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.61797 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.61797 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.61797 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06786 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.61797 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.80898 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.07865 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40177.94000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20088.97000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40177.94000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 66115.36668 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 66115.36668 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 17312.3 | 11.80 | 11.54 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 38920.3 | 12.27 | 11.99 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2034009760 | 0.1849501644 | Pass | Pass | 0.4657775996 | 0.9847810248 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4580366536 | 0.4057640853 | Pass | Pass | 0.1973564723 | 0.5290302327 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.9765511313E-005 | 1.1002869212E-004 | Pass | Pass | 1.8805514000E-002 | 1.9760323050E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8325.30 | 818.70 | 0.00 | 87.75 | 256.76 | 9488.53 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.131 | 0.133 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.055 | 0.055 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.176 | 0.180 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.563 | 0.614 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.563 | 0.614 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.563 | 0.614 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.341 | 0.357 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.614 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.614 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.943 | 0.380 | 0.418 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.943 | 0.380 | 0.418 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.943 | 0.380 | 0.418 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.943 | 0.380 | 0.418 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.003 | 0.460 | 0.479 | |||||||||||||||||
North Total or Average | 6.51 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.268 | 0.480 | 0.495 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.1633 | 236.88 | 1459.96 | LightsWired | LTG_SCH_OFFICE | 44.65 | 168.00 | 27.68 | 0.0000 | Y | 7.59 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 25.41 | 0.0000 | Y | 44.43 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 24.55 | 0.0000 | Y | 47.22 |
Interior Lighting Total | 4.3473 | 4835.13 | 21019.54 | 99.23 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.12 | 10245.50 | 1188.48 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1459.96 | 423.39 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1459.96 | 146.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 119.03 | AstronomicalClock | - | 42.24 | 42.24 | 0.94 | |
EXTERIOR_LIGHTS_B | 2955.82 | AstronomicalClock | - | 83.63 | 62.93 | 34.92 | |
EXTERIOR_LIGHTS_C | 694.12 | AstronomicalClock | - | 83.63 | 49.46 | 6.44 | |
Exterior Lighting Total | 3768.97 | 42.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18042.25 | 14310.03 | 3732.22 | 0.79 | 3.82 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40177.94 | 28167.95 | 12009.99 | 0.70 | 3.81 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 17312.3 | 11.80 | 11.54 | ||||
PSZ-FINE STORAGE COOLING COIL | 38920.3 | 12.27 | 11.99 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 217850.80 | 0.85 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26140.61 | 0.84 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 66115.37 | 0.85 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.58 | 518.42 | 92.91 | 1.00 | 3.12 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1040.94 | 1107.16 | 1.00 | 1.42 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.62 | 1731.30 | 1070.05 | 1.00 | 1.35 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9082.68 | 10899.22 | 46.01 | 0.783 | 0.940 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00858 | 29.72 | 0.01536 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 20049.82 | 24059.79 | 17.27 | 1.348 | 1.618 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00947 | 31.09 | 0.01536 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 31.38 | 0.01543 | 31.09 | 0.01536 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10766.99 | 12920.39 | 54.54 | 0.317 | 0.380 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00765 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 33911.98 | 40694.38 | 29.20 | 0.841 | 1.009 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00640 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 181542.34 | 217850.81 | 67.98 | 4.650 | 5.580 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00533 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.94 | 0.94 | 0.38 | 0.38 | 0.9402 | 0.9402 | 0.9402 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.62 | 1.62 | 1.01 | 1.01 | 1.6180 | 1.6180 | 1.6180 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 217850.800 | 217850.800 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 217850.80 | 217850.80 | 5.579830 | 9.99 | 7.04 | 0.00532595 | 43.33 | 21.59 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 9.99 | 0.00532595 | 66.8368 | 217850.81 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18042.250 | 14310.030 | 0.940190 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 9021.12 | 7444.26 | 0.626793 | 25.52 | 17.11 | 0.00931646 | 12.00 | 10.84 | 0.00800000 | 30.14 | 0.01536312 | 22.84 | 16.3187 | 23.90 | 0.00857690 | 44.3031 | 9067.01 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26140.613 | 26140.613 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26140.61 | 26140.61 | 0.940188 | 15.91 | 11.31 | 0.00685281 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 10.8792 | 21.10 | 0.00764524 | 46.8836 | 10766.99 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 40177.940 | 28167.950 | 1.617970 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 20088.97 | 14321.75 | 1.078647 | 28.79 | 19.47 | 0.01102182 | 12.00 | 10.84 | 0.00800000 | 31.20 | 0.01536508 | 23.13 | 39.3745 | 26.70 | 0.00947511 | 41.3783 | 20041.82 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 66115.367 | 66115.367 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 66115.37 | 66115.37 | 1.617966 | 4.59 | 3.71 | 0.00481650 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 26.2497 | 15.55 | 0.00640220 | 55.7086 | 33911.98 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 217850.800 | 217850.800 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 5.579830 | 6.40874582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 217850.80 | 217850.80 | 1.0000 | 6.40874582 | 5.579830 | 9.99 | 7.04 | 0.00532595 | 23461.6 | 43.33 | 21.59 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 217850.80 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 9.99 | 0.00532595 | 9.99 | 0.00532595 | 66.8368 | 217850.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18042.250 | 14310.030 | 0.940190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1588 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.940188 | 1.07985851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 9021.12 | 7444.26 | 1.0000 | 0.71990714 | 0.626793 | 25.52 | 17.11 | 0.00931646 | 49386.8 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9021.12 | 30.14 | 0.01536312 | 22.84 | 0.10228463 | 16.3187 | 23.90 | 0.00857690 | 23.90 | 0.00857690 | 44.3031 | 9067.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26140.613 | 26140.613 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.940188 | 1.07985851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26140.61 | 26140.61 | 1.0000 | 1.07985851 | 0.940188 | 15.91 | 11.31 | 0.00685281 | 33327.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26140.61 | -26.20 | 0.00036134 | -26.20 | 0.10228463 | 10.8792 | 21.05 | 0.00764524 | 21.10 | 0.00764524 | 46.8836 | 10766.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40177.940 | 28167.950 | 1.617970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3290 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.617966 | 1.85832400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 20088.97 | 14321.75 | 1.0000 | 1.23888592 | 1.078647 | 28.79 | 19.47 | 0.01102182 | 57082.0 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20088.97 | 31.20 | 0.01536508 | 23.13 | 0.42471127 | 39.3745 | 26.70 | 0.00947511 | 26.70 | 0.00947511 | 41.3783 | 20041.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 66115.367 | 66115.367 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.617966 | 1.85832400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 66115.37 | 66115.37 | 1.0000 | 1.85832400 | 1.617966 | 4.59 | 3.71 | 0.00481650 | 16703.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66115.37 | -26.20 | 0.00036134 | -26.20 | 0.42471127 | 26.2497 | 15.55 | 0.00640220 | 15.55 | 0.00640220 | 55.7086 | 33911.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 0.94 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.62 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2934.83 | 2900.00 | 2358.33 |
ZONE2 FINE STORAGE | 3312.00 | 3192.83 | 2916.17 |
ZONE3 BULK STORAGE | 3398.17 | 3282.00 | 3096.17 |
Facility | 3471.83 | 3333.67 | 3153.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 125.50 | 3.33 | 61.33 | 3.33 |
ZONE2 FINE STORAGE | 497.00 | 1.67 | 21.83 | 0.00 |
ZONE3 BULK STORAGE | 13.33 | 0.00 | 8.50 | 0.00 |
Facility | 594.50 | 5.00 | 77.67 | 3.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.622 | 0.270 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.463 | 0.159 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.146 | 0.000 | 0.102 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2237921.62 | 0.00 | 2237921.62 | 1451805.18 | 3689726.80 | 3225648.14 | 5671.64 | 2450.25 | 638.11 | 0.00 |
ZONE2 FINE STORAGE | 4939460.72 | 0.00 | 4939460.72 | 4405893.47 | 9345354.19 | 13393694.68 | 5726.46 | 2791.06 | 242.48 | 3.04 |
ZONE3 BULK STORAGE | 0.00 | 26297883.18 | 26297883.18 | 38108989.31 | 64406872.49 | 30805497.77 | 6723.35 | 131.33 | 1905.32 | 5100.17 |
Total Facility | 7177382.34 | 26297883.18 | 33475265.53 | 43966687.96 | 77441953.49 | 47424840.58 | 7868.72 | 3038.42 | 2641.76 | 5100.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1710 | 0.0000 | 0.1710 | 0.0748 | 0.2457 | 0.1023 | 547.64 | 2450.25 | 638.11 |
ZONE2 FINE STORAGE | 0.3767 | 0.0000 | 0.3767 | 0.1297 | 0.5063 | 0.4247 | 605.50 | 2791.06 | 239.44 |
ZONE3 BULK STORAGE | 0.0000 | 0.9930 | 0.9930 | 1.4408 | 2.4338 | 0.9768 | 2627.56 | 53.00 | 955.44 |
Total Facility | 0.5476 | 0.9930 | 1.5407 | 1.6452 | 3.1859 | 1.5038 | 2744.72 | 2960.08 | 1688.96 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2952222.54 | 0.00 | 2952222.54 | 3225648.14 | 5670.35 | 0.00 | 3089.65 | 0.00 |
PSZ-FINE STORAGE | 6516251.58 | 0.00 | 6516251.58 | 13393694.68 | 5726.29 | 0.00 | 3033.71 | 3.04 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2255 | 0.0000 | 0.2255 | 0.1023 | 546.35 | 0.00 | 3089.65 |
PSZ-FINE STORAGE | 0.4969 | 0.0000 | 0.4969 | 0.4247 | 605.33 | 0.00 | 3030.67 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2845.21 | 252.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2989.54 | 46.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2453 | 0.4850 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5929 | 0.8108 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 405 |
Defaulted Fields | 323 |
Fields with Defaults | 1052 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 328.91 | 1217.09 | 11-JUN-12:40 | 32616.86 | 04-AUG-15:00 |
Electricity:Building | 235.93 | 1217.09 | 01-JAN-10:10 | 19680.87 | 04-AUG-10:20 |
Electricity:Zone:ZONE1 OFFICE | 36.75 | 520.87 | 01-JAN-00:10 | 2598.04 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 235.74 | 1217.09 | 01-JAN-10:10 | 18022.62 | 12-DEC-16:00 |
InteriorLights:Electricity | 99.24 | 747.21 | 01-JAN-10:10 | 7987.45 | 12-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.59 | 51.00 | 01-JAN-00:10 | 762.98 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 99.24 | 747.21 | 01-JAN-10:10 | 7987.45 | 12-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 99.24 | 747.21 | 01-JAN-10:10 | 7987.45 | 12-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.59 | 51.00 | 01-JAN-00:10 | 762.98 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 99.24 | 747.21 | 01-JAN-10:10 | 7987.45 | 12-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 154.75 | 396.24 | 01-JAN-10:10 | 13873.54 | 28-JUN-14:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 47.22 | 396.24 | 01-JAN-10:10 | 3774.93 | 05-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 47.22 | 396.24 | 01-JAN-10:10 | 3774.93 | 05-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 31.89 | 0.00 | 24-FEB-18:10 | 4296.16 | 04-AUG-15:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.19 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-AUG-17:10 |
Ventilation (simple):Fans:Electricity | 0.19 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-AUG-17:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.19 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-AUG-17:10 |
ElectricityProduced:Facility | 106.81 | -0.00 | 03-APR-18:30 | 21002.45 | 25-APR-12:20 |
ElectricityProduced:Plant | 106.81 | -0.00 | 03-APR-18:30 | 21002.45 | 25-APR-12:20 |
Photovoltaic:ElectricityProduced | 111.81 | 0.00 | 01-JAN-00:10 | 21870.23 | 25-APR-12:20 |
PowerConversion:ElectricityProduced | -5.01 | -867.78 | 25-APR-12:20 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 11.84 | 0.00 | 02-JAN-00:20 | 1796.07 | 23-FEB-12:40 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 237.95 | 0.00 | 01-JAN-09:50 | 24531.13 | 09-DEC-16:50 |
ElectricityPurchased:Plant | 237.95 | 0.00 | 01-JAN-09:50 | 24531.13 | 09-DEC-16:50 |
Cogeneration:ElectricityPurchased | 237.95 | 0.00 | 01-JAN-09:50 | 24531.13 | 09-DEC-16:50 |
General:Cogeneration:ElectricityPurchased | 237.95 | 0.00 | 01-JAN-09:50 | 24531.13 | 09-DEC-16:50 |
ElectricitySurplusSold:Facility | 15.84 | 0.00 | 01-JAN-00:10 | 18963.86 | 23-APR-12:10 |
ElectricitySurplusSold:Plant | 15.84 | 0.00 | 01-JAN-00:10 | 18963.86 | 23-APR-12:10 |
Cogeneration:ElectricitySurplusSold | 15.84 | 0.00 | 01-JAN-00:10 | 18963.86 | 23-APR-12:10 |
General:Cogeneration:ElectricitySurplusSold | 15.84 | 0.00 | 01-JAN-00:10 | 18963.86 | 23-APR-12:10 |
ElectricityNet:Facility | 222.11 | -18963.86 | 23-APR-12:10 | 24531.13 | 09-DEC-16:50 |
ElectricityNet:Plant | 222.11 | -18963.86 | 23-APR-12:10 | 24531.13 | 09-DEC-16:50 |
Cogeneration:ElectricityNet | 222.11 | -18963.86 | 23-APR-12:10 | 24531.13 | 09-DEC-16:50 |
General:Cogeneration:ElectricityNet | 222.11 | -18963.86 | 23-APR-12:10 | 24531.13 | 09-DEC-16:50 |
Electricity:HVAC | 38.83 | 0.00 | 24-FEB-18:10 | 12213.90 | 04-AUG-15:30 |
General:Fans:Electricity | 31.70 | 0.00 | 24-FEB-18:10 | 3147.38 | 09-DEC-09:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 7.13 | 0.00 | 01-JAN-00:10 | 10223.04 | 04-AUG-15:30 |
General:Cooling:Electricity | 7.13 | 0.00 | 01-JAN-00:10 | 10223.04 | 04-AUG-15:30 |
ExteriorLights:Electricity | 42.31 | 0.00 | 01-JAN-08:00 | 3768.97 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.31 | 0.00 | 01-JAN-08:00 | 3768.97 | 01-JAN-06:10 |
WaterSystems:Electricity | 11.84 | 0.00 | 02-JAN-00:20 | 1796.07 | 23-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 11.84 | 0.00 | 02-JAN-00:20 | 1796.07 | 23-FEB-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1236.86 | 0.00 | 24-FEB-18:10 | 346036.36 | 18-JAN-18:00 |
NaturalGas:HVAC | 1236.86 | 0.00 | 24-FEB-18:10 | 346036.36 | 18-JAN-18:00 |
Heating:NaturalGas | 1236.86 | 0.00 | 24-FEB-18:10 | 346036.36 | 18-JAN-18:00 |
General:Heating:NaturalGas | 1236.86 | 0.00 | 24-FEB-18:10 | 346036.36 | 18-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2063.54 | 0.00 | 24-FEB-18:10 | 565493.71 | 09-DEC-06:10 |
EnergyTransfer:Building | 1013.71 | 0.00 | 24-FEB-18:10 | 283465.92 | 09-DEC-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 61.40 | 0.00 | 01-JAN-00:10 | 27311.11 | 02-FEB-07:20 |
Heating:EnergyTransfer | 979.54 | 0.00 | 24-FEB-18:10 | 283465.92 | 09-DEC-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 46.77 | 0.00 | 01-JAN-00:10 | 27311.11 | 02-FEB-07:20 |
General:Heating:EnergyTransfer | 979.54 | 0.00 | 24-FEB-18:10 | 283465.92 | 09-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 46.77 | 0.00 | 01-JAN-00:10 | 27311.11 | 02-FEB-07:20 |
Cooling:EnergyTransfer | 34.18 | 0.00 | 01-JAN-00:10 | 20198.40 | 04-AUG-15:30 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 14.63 | 0.00 | 01-JAN-00:10 | 7854.36 | 05-JUL-05:10 |
General:Cooling:EnergyTransfer | 34.18 | 0.00 | 01-JAN-00:10 | 20198.40 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 14.63 | 0.00 | 01-JAN-00:10 | 7854.36 | 05-JUL-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 159.30 | 0.00 | 01-JAN-00:40 | 47996.24 | 09-DEC-02:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 139.76 | 0.00 | 01-JAN-00:40 | 47996.24 | 09-DEC-02:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 139.76 | 0.00 | 01-JAN-00:40 | 47996.24 | 09-DEC-02:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 19.54 | 0.00 | 01-JAN-00:10 | 12863.26 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 19.54 | 0.00 | 01-JAN-00:10 | 12863.26 | 04-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 793.01 | 0.00 | 12-JAN-13:10 | 220170.63 | 09-DEC-08:30 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 793.01 | 0.00 | 12-JAN-13:10 | 220170.63 | 09-DEC-08:30 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 793.01 | 0.00 | 12-JAN-13:10 | 220170.63 | 09-DEC-08:30 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1049.82 | 0.00 | 24-FEB-18:10 | 290877.99 | 18-JAN-18:00 |
HeatingCoils:EnergyTransfer | 1018.52 | 0.00 | 24-FEB-18:10 | 290877.99 | 18-JAN-18:00 |
CoolingCoils:EnergyTransfer | 31.30 | 0.00 | 01-JAN-00:10 | 41907.59 | 04-AUG-15:30 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 46.769 | -14.632 | 0.000 | 0.000 | 10.154 | 7.587 | 29.165 | 10.879 | 0.000 | 0.415 | 0.000 | 0.000 | -9.524 | 0.000 | -26.107 | -54.705 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 139.760 | -19.543 | 0.000 | 0.000 | 26.860 | 44.427 | 0.000 | 0.000 | 0.000 | 0.594 | 0.001 | 0.000 | 0.000 | 0.000 | -69.565 | -122.533 |
ZONE3 BULK STORAGE | 793.008 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 67.591 | 47.222 | 107.344 | 124.446 | 0.000 | 16.171 | 0.000 | 0.000 | -66.654 | 0.000 | -710.824 | -378.301 |
Total Facility | 793.008 | 0.000 | 186.529 | -34.175 | 0.000 | 0.000 | 104.605 | 99.235 | 136.508 | 135.325 | 0.000 | 17.180 | 0.002 | 0.000 | -76.179 | 0.000 | -806.496 | -555.540 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-JUL-05:03 | 0.00 | 0.00 | 0.00 | -18913.92 | 0.00 | 0.00 | 92.28 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 18906.34 | 0.00 | -186.16 | 0.00 | -500.05 | 0.00 |
ZONE2 FINE STORAGE | 05-JUL-17:10 | 0.00 | 0.00 | 0.00 | -30250.70 | 0.00 | 0.00 | 0.00 | 407.49 | 0.00 | 0.00 | 0.00 | 0.00 | 29848.42 | 0.00 | -0.00 | 0.00 | -5.21 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-17:10 | 0.00 | 0.00 | 0.00 | -30250.70 | 0.00 | 0.00 | 0.00 | 927.69 | 2519.91 | 30604.58 | 0.00 | 45.52 | 0.00 | 0.00 | 0.00 | 0.00 | -2612.96 | -1234.04 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 04-MAR-06:32 | 0.00 | 0.00 | 27513.64 | 0.00 | 0.00 | 0.00 | 136.94 | 227.91 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -735.12 | 0.00 | -840.59 | -26853.30 |
ZONE2 FINE STORAGE | 09-DEC-21:22 | 0.00 | 0.00 | 68686.59 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -11875.02 | -57111.53 |
ZONE3 BULK STORAGE | 09-DEC-08:30 | 220171.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8477.99 | 3302.96 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7472.63 | 0.00 | -223818.34 | -8861.67 |
Total Facility | 09-DEC-06:11 | 218383.36 | 0.00 | 94315.44 | 0.00 | 0.00 | 0.00 | 1397.69 | 1083.64 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9561.53 | 0.00 | -210259.85 | -97959.31 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9402 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9402 | 0.1088 | 1.0000 | Not calculated | 0.1023 | 0.1088 | ||
PSZ-FINE STORAGE | 1.6180 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.6180 | 0.2625 | 1.0000 | Not calculated | 0.4247 | 0.2625 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9402 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9402 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1088 | ||
PSZ-FINE STORAGE | 1.6180 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.6180 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2625 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9402 | 0.9402 | 0.9402 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6180 | 1.6180 | 1.6180 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9402 | 0.9402 | 0.9402 | 0.9402 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6180 | 1.6180 | 1.6180 | 1.6180 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9402 | 0.9402 | 0.9402 | No | 0.1023 | 0.2690 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6180 | 1.6180 | 1.6180 | No | 0.4247 | 0.4210 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9402 | 0.9402 | 0.9402 | 0.9402 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6180 | 1.6180 | 1.6180 | 1.6180 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 77.67 |
Number of hours cooling loads not met | 3.33 |
Number of hours not met | 81.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1236.86 | 346036.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 7.13 | 10223.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 99.24 | 7987.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.31 | 3768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.19 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 31.70 | 3147.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 11.84 | 1796.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 328.91 |
Natural Gas | 0.00 | 1236.86 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1565.77 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 111.81 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 20.52 |
Space Heating | 0.00 |
Space Cooling | 1.47 |
Fans (All) | 6.60 |
Service Water Heating | 2.45 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 68.03 |
Subtotal | 68.03 |
Natural Gas [MJ/m2] | |
Space Heating | 255.81 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 255.81 |
Subtotal | 255.81 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.34 |
Space Heating | 78.99 |
Space Cooling | 0.46 |
Fans (All) | 2.04 |
Service Water Heating | 0.76 |
Receptacle Equipment | 8.72 |
Miscellaneous | 2.70 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_OFFICE | 2328. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8468.67 | 291.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8171.83 | 588.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8062.83 | 670.50 | 26.67 | 0.00 | 0.00 |
Min | 8062.83 | 291.33 | 0.00 | 0.00 | 0.00 |
Max | 8468.67 | 670.50 | 26.67 | 0.00 | 0.00 |
Average | 8234.44 | 516.67 | 8.89 | 0.00 | 0.00 |
Sum | 24703.33 | 1550.00 | 26.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 72179.00 | 10540.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 167222.33 | 22786.17 | 1184.50 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 167222.33 | 22786.17 | 1184.50 | 0.00 | 0.00 |
Average | 90809.44 | 11108.72 | 394.83 | 0.00 | 0.00 |
Sum | 272428.33 | 33326.17 | 1184.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7737.17 | 1022.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7193.50 | 1566.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7329.33 | 1420.50 | 10.17 | 0.00 | 0.00 |
Min | 7193.50 | 1022.83 | 0.00 | 0.00 | 0.00 |
Max | 7737.17 | 1566.50 | 10.17 | 0.00 | 0.00 |
Average | 7420.00 | 1336.61 | 3.39 | 0.00 | 0.00 |
Sum | 22260.00 | 4009.83 | 10.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31525.17 | 1501.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 64500.50 | 18218.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 154240.33 | 36362.50 | 590.17 | 0.00 | 0.00 |
Min | 31525.17 | 1501.83 | 0.00 | 0.00 | 0.00 |
Max | 154240.33 | 36362.50 | 590.17 | 0.00 | 0.00 |
Average | 83422.00 | 18694.28 | 196.72 | 0.00 | 0.00 |
Sum | 250266.00 | 56082.83 | 590.17 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.497016E+09 | 603.25 | 28-JAN-08:09 | -18.7 | -19.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.457255E+09 | 603.25 | 06-FEB-08:09 | -14.8 | -15.6 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.537196E+09 | 650.00 | 25-MAR-15:30 | 18.35 | 10.46 |
April | 94633978.36 | 2679.05 | 18-APR-15:10 | 27.75 | 20.46 | 0.514013E+09 | 778.65 | 18-APR-09:30 | 27.75 | 20.46 |
May | 0.251209E+09 | 3792.49 | 31-MAY-16:00 | 28.30 | 18.78 | 0.597214E+09 | 769.00 | 31-MAY-12:20 | 28.30 | 18.78 |
June | 0.286579E+10 | 15842.89 | 29-JUN-05:02 | 17.48 | 16.35 | 0.647333E+09 | 769.01 | 28-JUN-07:00 | 17.48 | 16.35 |
July | 0.442341E+10 | 18919.33 | 19-JUL-05:03 | 12.48 | 11.50 | 0.634700E+09 | 769.03 | 03-JUL-07:30 | 12.48 | 11.50 |
August | 0.457150E+10 | 18468.29 | 09-AUG-05:03 | 12.98 | 11.32 | 0.685499E+09 | 769.02 | 12-AUG-15:00 | 20.60 | 18.08 |
September | 0.241137E+10 | 18019.74 | 09-SEP-05:02 | 13.80 | 13.12 | 0.605713E+09 | 769.02 | 11-SEP-08:20 | 22.77 | 19.12 |
October | 14376889.38 | 438.69 | 07-OCT-15:20 | 7.80 | 4.00 | 0.507217E+09 | 768.97 | 20-OCT-15:00 | 21.30 | 12.72 |
November | 301149.32 | 222.73 | 04-NOV-16:40 | 9.47 | 4.57 | 0.479252E+09 | 680.87 | 03-NOV-15:09 | 9.47 | 4.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.497033E+09 | 603.25 | 05-DEC-08:09 | -6.7 | -8.3 |
Annual Sum or Average | 0.146326E+11 | 0.665944E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.457255E+09 | 603.25 | -18.7 | -19.1 | ||
Maximum of Months | 0.457150E+10 | 18919.33 | 28.30 | 20.46 | 0.685499E+09 | 778.65 | 28.30 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 53531004.78 | 2470.79 | 13-JAN-14:40 | 3.90 | 1.72 | 0.649200E+09 | 787.42 | 19-JAN-11:50 | -25.1 | -25.3 |
February | 0.247276E+09 | 6596.76 | 09-FEB-10:45 | 0.13 | -0.4 | 0.598048E+09 | 854.45 | 24-FEB-15:30 | 8.30 | 5.75 |
March | 0.791958E+09 | 8051.16 | 13-MAR-12:05 | -3.0 | -5.1 | 0.719258E+09 | 1095.43 | 25-MAR-15:20 | 18.53 | 10.46 |
April | 0.170665E+10 | 7352.27 | 21-APR-10:20 | -0.8 | -1.2 | 0.779254E+09 | 1899.25 | 18-APR-15:20 | -0.8 | -1.2 |
May | 0.132732E+10 | 4289.93 | 02-MAY-09:20 | 5.37 | 2.77 | 0.112496E+10 | 2178.25 | 31-MAY-15:30 | 29.15 | 19.25 |
June | 0.266665E+10 | 26824.91 | 28-JUN-17:20 | 27.93 | 20.15 | 0.162785E+10 | 2246.90 | 30-JUN-13:39 | 29.40 | 21.96 |
July | 0.394590E+10 | 30255.65 | 05-JUL-17:10 | 26.70 | 20.64 | 0.179034E+10 | 2246.90 | 05-JUL-14:50 | 26.70 | 20.64 |
August | 0.322584E+10 | 26754.81 | 02-AUG-17:15 | 28.53 | 22.51 | 0.191614E+10 | 2246.90 | 04-AUG-12:39 | 31.50 | 26.46 |
September | 0.259552E+10 | 12226.27 | 10-SEP-14:35 | 27.43 | 17.62 | 0.143353E+10 | 2246.86 | 07-SEP-15:09 | 27.43 | 17.62 |
October | 0.211110E+10 | 5540.77 | 23-OCT-09:30 | 2.95 | 0.54 | 0.757299E+09 | 1314.90 | 20-OCT-15:20 | 2.95 | 0.54 |
November | 0.793185E+09 | 5512.42 | 09-NOV-14:40 | 2.97 | 0.92 | 0.660495E+09 | 1143.23 | 03-NOV-14:50 | 2.97 | 0.92 |
December | 78517906.32 | 4947.82 | 02-DEC-16:25 | 3.65 | 2.10 | 0.649302E+09 | 787.42 | 30-DEC-10:00 | -1.1 | -1.8 |
Annual Sum or Average | 0.195434E+11 | 0.127057E+11 | ||||||||
Minimum of Months | 53531004.78 | 2470.79 | -3.0 | -5.1 | 0.598048E+09 | 787.42 | -25.1 | -25.3 | ||
Maximum of Months | 0.394590E+10 | 30255.65 | 28.53 | 22.51 | 0.191614E+10 | 2246.90 | 31.50 | 26.46 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.643945E+09 | 784.18 | 12-JAN-13:30 | 2.20 | 0.51 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.597864E+09 | 1018.22 | 24-FEB-15:30 | 8.30 | 5.75 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.771810E+09 | 1589.10 | 25-MAR-15:30 | 18.35 | 10.46 |
April | 0.00 | 0.00 | 01-APR-00:05 | -1.2 | -2.2 | 0.110778E+10 | 3743.10 | 18-APR-15:09 | 27.75 | 20.46 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.15 | 0.207473E+10 | 4410.16 | 31-MAY-15:20 | 29.43 | 19.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 | 0.358862E+10 | 6399.45 | 29-JUN-15:00 | 30.00 | 20.53 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 | 0.439546E+10 | 6517.80 | 03-JUL-15:20 | 29.63 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 | 0.455773E+10 | 7836.13 | 04-AUG-15:50 | 33.90 | 26.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 | 0.314162E+10 | 5767.10 | 08-SEP-14:50 | 30.10 | 19.14 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 | 0.111928E+10 | 2240.92 | 02-OCT-15:39 | 17.17 | 14.05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 | -0.5 | 0.772284E+09 | 1705.50 | 03-NOV-14:50 | 16.10 | 9.74 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.638806E+09 | 847.61 | 02-DEC-15:50 | 5.68 | 3.15 |
Annual Sum or Average | 0.00 | 0.234099E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.597864E+09 | 784.18 | 2.20 | 0.51 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.455773E+10 | 7836.13 | 33.90 | 26.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108664E+11 | 26923.58 | 30-JAN-06:11 | -28.5 |
February | 0.821594E+10 | 27489.31 | 22-FEB-06:32 | -1.7 |
March | 0.666227E+10 | 27513.59 | 04-MAR-06:32 | -8.3 |
April | 0.358525E+10 | 27439.69 | 06-APR-05:32 | -5.4 |
May | 0.933555E+09 | 26543.42 | 02-MAY-05:12 | 2.20 |
June | 0.126037E+09 | 25910.17 | 05-JUN-05:02 | 9.32 |
July | 17108866.46 | 1266.86 | 19-JUL-06:10 | 14.37 |
August | 32296439.99 | 1365.63 | 15-AUG-06:07 | 14.18 |
September | 0.299004E+09 | 26418.59 | 30-SEP-05:42 | 0.50 |
October | 0.238825E+10 | 26527.04 | 16-OCT-05:12 | 0.27 |
November | 0.520181E+10 | 26776.69 | 24-NOV-06:12 | -13.5 |
December | 0.844140E+10 | 27443.16 | 14-DEC-06:32 | -1.3 |
Annual Sum or Average | 0.467694E+11 | |||
Minimum of Months | 17108866.46 | 1266.86 | -28.5 | |
Maximum of Months | 0.108664E+11 | 27513.59 | 14.37 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382536E+11 | 68639.88 | 31-JAN-05:22 | -30.6 |
February | 0.273034E+11 | 68605.21 | 04-FEB-20:02 | -19.9 |
March | 0.169002E+11 | 67958.67 | 06-MAR-04:02 | -16.0 |
April | 0.664235E+10 | 67083.59 | 03-APR-00:23 | -5.8 |
May | 0.713031E+09 | 40966.40 | 01-MAY-05:37 | 5.93 |
June | 0.106914E+09 | 2316.44 | 09-JUN-12:00 | 28.30 |
July | 50476197.60 | 671.86 | 10-JUL-06:13 | 17.40 |
August | 54712681.87 | 673.92 | 25-AUG-07:00 | 13.90 |
September | 0.118230E+09 | 27000.78 | 30-SEP-05:45 | 0.50 |
October | 0.311923E+10 | 60005.12 | 24-OCT-05:01 | 2.03 |
November | 0.160412E+11 | 67959.14 | 25-NOV-21:22 | -23.9 |
December | 0.304572E+11 | 68686.45 | 09-DEC-21:22 | -20.0 |
Annual Sum or Average | 0.139761E+12 | |||
Minimum of Months | 50476197.60 | 671.86 | -30.6 | |
Maximum of Months | 0.382536E+11 | 68686.45 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241773E+12 | 218933.83 | 18-JAN-18:00 | -18.3 |
February | 0.163680E+12 | 211433.56 | 01-FEB-20:57 | -28.9 |
March | 0.880654E+11 | 149457.82 | 06-MAR-08:70 | -11.8 |
April | 0.195566E+11 | 89415.19 | 02-APR-24:00 | -5.6 |
May | 0.289474E+09 | 14235.29 | 02-MAY-03:00 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.200513E+10 | 18446.23 | 24-OCT-06:00 | 2.20 |
November | 0.914387E+11 | 146422.67 | 26-NOV-04:00 | -25.0 |
December | 0.186201E+12 | 220170.63 | 09-DEC-08:30 | -22.8 |
Annual Sum or Average | 0.793009E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.241773E+12 | 220170.63 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.686147E+09 | 762.98 | 02-JAN-16:40 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.604424E+09 | 742.57 | 11-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.660827E+09 | 716.72 | 01-MAR-16:00 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.615570E+09 | 720.00 | 10-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.602571E+09 | 659.53 | 25-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.587673E+09 | 702.24 | 13-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.577086E+09 | 703.24 | 20-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.620192E+09 | 686.00 | 31-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.609454E+09 | 720.53 | 21-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.633959E+09 | 738.67 | 21-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.664123E+09 | 762.98 | 06-NOV-16:00 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.724838E+09 | 762.98 | 01-DEC-16:30 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.758686E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.577086E+09 | 659.53 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.724838E+09 | 762.98 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.368849E+10 | 3463.72 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.337993E+10 | 3463.72 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.391929E+10 | 3463.72 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.366257E+10 | 3463.72 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.380389E+10 | 3463.72 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.377797E+10 | 3463.72 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.368849E+10 | 3463.72 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.391929E+10 | 3463.72 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.366257E+10 | 3463.72 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.368849E+10 | 3463.72 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.354717E+10 | 3463.72 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.368849E+10 | 3463.72 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.444266E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.337993E+10 | 3463.72 | 0.00 | 0.00 | |
Maximum of Months | 0.391929E+10 | 3463.72 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.405341E+10 | 3755.17 | 02-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.366772E+10 | 3724.94 | 08-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.412903E+10 | 3684.41 | 13-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.382918E+10 | 3554.20 | 10-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.394631E+10 | 3512.58 | 04-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.390115E+10 | 3463.06 | 05-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.383448E+10 | 3501.54 | 20-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.406689E+10 | 3541.75 | 29-AUG-08:20 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.384840E+10 | 3603.35 | 21-SEP-08:30 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.396665E+10 | 3692.87 | 30-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.386426E+10 | 3755.45 | 29-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.411404E+10 | 3774.93 | 05-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.472215E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.366772E+10 | 3463.06 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.412903E+10 | 3774.93 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.686147E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513560E+10 |
February | 0.127628E+10 | 0.604424E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382367E+10 |
March | 0.149825E+10 | 0.660827E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 411557.17 | 0.315858E+10 |
April | 0.138726E+10 | 0.615570E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26214505.44 | 0.182751E+10 |
May | 0.144276E+10 | 0.602571E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25632983.45 | 0.952161E+09 |
June | 0.144276E+10 | 0.587673E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103928E+09 | 0.603395E+09 |
July | 0.138726E+10 | 0.577086E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78024656.01 | 0.393547E+09 |
August | 0.149825E+10 | 0.620192E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113825E+09 | 0.557474E+09 |
September | 0.138726E+10 | 0.609454E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66468192.57 | 0.978417E+09 |
October | 0.138726E+10 | 0.633959E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165088E+10 |
November | 0.133177E+10 | 0.664123E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288483E+10 |
December | 0.138726E+10 | 0.724838E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414060E+10 |
Annual Sum or Average | 0.168137E+11 | 0.758686E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414504E+09 | 0.261067E+11 |
Minimum of Months | 0.127628E+10 | 0.577086E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393547E+09 |
Maximum of Months | 0.149825E+10 | 0.724838E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113825E+09 | 0.513560E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140151E+11 |
February | 0.300332E+10 | 0.337993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102528E+11 |
March | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7768373.24 | 0.797060E+10 |
April | 0.326447E+10 | 0.366257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188056E+09 | 0.420970E+10 |
May | 0.339505E+10 | 0.380389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76323922.72 | 0.198169E+10 |
June | 0.339505E+10 | 0.377797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170887E+09 | 0.166958E+10 |
July | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38945222.84 | 0.152301E+10 |
August | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58488638.35 | 0.208594E+10 |
September | 0.326447E+10 | 0.366257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45197841.13 | 0.262554E+10 |
October | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8660577.90 | 0.356658E+10 |
November | 0.313390E+10 | 0.354717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801124E+10 |
December | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116528E+11 |
Annual Sum or Average | 0.395654E+11 | 0.444266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594328E+09 | 0.695646E+11 |
Minimum of Months | 0.300332E+10 | 0.337993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152301E+10 |
Maximum of Months | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188056E+09 | 0.140151E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.405341E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961950E+11 |
February | 0.690763E+10 | 0.366772E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668398E+11 |
March | 0.810895E+10 | 0.412903E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890627E+09 | 0.451946E+11 |
April | 0.750829E+10 | 0.382918E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370939E+10 | 0.217181E+11 |
May | 0.780862E+10 | 0.394631E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216636E+10 | 0.992838E+10 |
June | 0.780862E+10 | 0.390115E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133053E+10 | 0.112843E+11 |
July | 0.750829E+10 | 0.383448E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85277411.49 | 0.133433E+11 |
August | 0.810895E+10 | 0.406689E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108797E+09 | 0.163405E+11 |
September | 0.750829E+10 | 0.384840E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417342E+09 | 0.183590E+11 |
October | 0.750829E+10 | 0.396665E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854220E+09 | 0.167070E+11 |
November | 0.720796E+10 | 0.386426E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168575E+09 | 0.466443E+11 |
December | 0.750829E+10 | 0.411404E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754915E+11 |
Annual Sum or Average | 0.910005E+11 | 0.472215E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973112E+10 | 0.438046E+12 |
Minimum of Months | 0.690763E+10 | 0.366772E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992838E+10 |
Maximum of Months | 0.810895E+10 | 0.412903E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370939E+10 | 0.961950E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 762.98 | 02-JAN-16:40 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14767.81 | 19-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 742.57 | 11-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16757.76 | 02-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 716.72 | 01-MAR-16:00 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.44 | 19-MAR-14:00 | 10575.07 | 06-MAR-08:00 |
April | 1680.92 | 01-APR-07:10 | 720.00 | 10-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 899.66 | 18-APR-12:00 | 7928.69 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 659.53 | 25-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.09 | 31-MAY-17:00 | 5014.51 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 702.24 | 13-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1769.43 | 26-JUN-16:10 | 3569.78 | 02-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 703.24 | 20-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.15 | 25-JUL-16:10 | 2699.60 | 24-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 686.00 | 31-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2101.51 | 04-AUG-16:10 | 3631.85 | 07-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 720.53 | 21-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1685.12 | 06-SEP-16:10 | 5262.48 | 29-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 738.67 | 21-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6034.93 | 23-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 762.98 | 06-NOV-16:00 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 10027.98 | 28-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 762.98 | 01-DEC-16:30 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13473.22 | 08-DEC-17:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 659.53 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2699.60 | |||||
Maximum of Months | 1680.92 | 762.98 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2101.51 | 16757.76 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3463.72 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 24026.18 | 18-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 3463.72 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14959.93 | 04-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 3463.72 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.59 | 19-MAR-16:00 | 14703.13 | 06-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 3463.72 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3487.23 | 15-APR-17:00 | 9184.84 | 25-APR-06:10 |
May | 3955.50 | 01-MAY-07:10 | 3463.72 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1797.73 | 05-MAY-15:10 | 3887.53 | 02-MAY-03:00 |
June | 3955.50 | 01-JUN-07:10 | 3463.72 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2067.09 | 11-JUN-15:00 | 3881.56 | 02-JUN-05:00 |
July | 3955.50 | 01-JUL-07:10 | 3463.72 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.36 | 25-JUL-16:00 | 2459.74 | 10-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 3463.72 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.43 | 04-AUG-16:15 | 2848.78 | 06-AUG-06:00 |
September | 3955.50 | 01-SEP-07:10 | 3463.72 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.61 | 06-SEP-15:40 | 3940.91 | 18-SEP-23:00 |
October | 3955.50 | 02-OCT-07:10 | 3463.72 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.70 | 20-OCT-15:10 | 6288.69 | 24-OCT-06:10 |
November | 3955.50 | 01-NOV-07:10 | 3463.72 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 13352.32 | 25-NOV-16:10 |
December | 3955.50 | 01-DEC-08:09 | 3463.72 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 26545.12 | 09-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2459.74 | ||||
Maximum of Months | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3487.23 | 26545.12 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3755.17 | 02-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 131376.09 | 18-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 3724.94 | 08-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 92742.48 | 28-FEB-10:00 |
March | 9097.65 | 01-MAR-08:09 | 3684.41 | 13-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16055.28 | 25-MAR-15:00 | 84545.53 | 06-MAR-08:70 |
April | 9097.65 | 01-APR-07:10 | 3554.20 | 10-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36216.71 | 15-APR-15:00 | 40179.00 | 02-APR-24:00 |
May | 9097.65 | 01-MAY-07:10 | 3512.58 | 04-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23665.73 | 04-MAY-14:00 | 23474.71 | 13-MAY-13:00 |
June | 9097.65 | 01-JUN-07:10 | 3463.06 | 05-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16616.85 | 11-JUN-15:00 | 24391.80 | 02-JUN-08:00 |
July | 9097.65 | 01-JUL-07:10 | 3501.54 | 20-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3910.50 | 25-JUL-16:00 | 24444.58 | 10-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 3541.75 | 29-AUG-08:20 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3353.09 | 21-AUG-13:00 | 20558.48 | 30-AUG-15:00 |
September | 9097.65 | 01-SEP-07:10 | 3603.35 | 21-SEP-08:30 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8228.93 | 06-SEP-14:00 | 25187.34 | 18-SEP-16:00 |
October | 9097.65 | 02-OCT-07:10 | 3692.87 | 30-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14118.41 | 20-OCT-15:00 | 23358.83 | 24-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 3755.45 | 29-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8445.24 | 20-NOV-10:00 | 91126.14 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 3774.93 | 05-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 157103.50 | 09-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3463.06 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20558.48 | |||||
Maximum of Months | 9097.65 | 3774.93 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 36216.71 | 157103.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.55 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.76 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1251.98 |
April | 2679.05 | 18-APR-15:10 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 390.67 | 0.00 |
May | 3792.49 | 31-MAY-16:00 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 281.01 | 0.00 |
June | 15842.89 | 29-JUN-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.90 |
July | 18919.33 | 19-JUL-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.05 |
August | 18468.29 | 09-AUG-05:03 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.56 |
September | 18019.74 | 09-SEP-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.58 |
October | 438.69 | 07-OCT-15:20 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.58 |
November | 222.73 | 04-NOV-16:40 | 1075.79 | 1115.99 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.68 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 607.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18919.33 | 1680.92 | 1115.99 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.67 | 1251.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2470.79 | 13-JAN-14:40 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.98 |
February | 6596.76 | 09-FEB-10:45 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.26 |
March | 8051.16 | 13-MAR-12:05 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1924.50 |
April | 7352.27 | 21-APR-10:20 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1835.81 |
May | 4289.93 | 02-MAY-09:20 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167.20 |
June | 26824.91 | 28-JUN-17:20 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.54 | 0.00 |
July | 30255.65 | 05-JUL-17:10 | 0.00 | 1629.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 |
August | 26754.81 | 02-AUG-17:15 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.12 | 0.00 |
September | 12226.27 | 10-SEP-14:35 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.96 | 0.00 |
October | 5540.77 | 23-OCT-09:30 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.53 |
November | 5512.42 | 09-NOV-14:40 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.86 |
December | 4947.82 | 02-DEC-16:25 | 7911.00 | 6112.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2470.79 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30255.65 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.12 | 2900.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1344.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16604.45 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2241.20 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40749.75 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2241.20 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42176.00 |
April | 0.00 | 01-APR-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7659.16 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4166.02 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5414.36 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5435.91 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6315.82 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7813.53 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7711.26 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5126.97 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1344.72 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17062.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4166.02 | |
Maximum of Months | 0.00 | 0.00 | 2241.20 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42176.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.299014E+11 | 24514.43 | 18-JAN-16:00 | 0.365436E+12 | 346036.36 | 18-JAN-17:00 |
February | 0.265877E+11 | 22088.06 | 02-FEB-13:20 | 0.251130E+12 | 305867.60 | 01-FEB-20:00 |
March | 0.291274E+11 | 21750.90 | 02-MAR-15:00 | 0.142485E+12 | 238870.43 | 06-MAR-08:09 |
April | 0.257447E+11 | 21875.41 | 18-APR-14:00 | 0.392702E+11 | 139771.60 | 02-APR-23:49 |
May | 0.255754E+11 | 21972.71 | 31-MAY-14:00 | 0.198030E+10 | 44018.64 | 02-MAY-05:10 |
June | 0.264689E+11 | 29391.20 | 30-JUN-14:50 | 79745894.93 | 6065.61 | 05-JUN-05:10 |
July | 0.270073E+11 | 30567.08 | 03-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.286690E+11 | 32616.86 | 04-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.261095E+11 | 25377.59 | 08-SEP-14:09 | 0.463789E+09 | 20766.91 | 30-SEP-05:10 |
October | 0.264989E+11 | 20809.52 | 27-OCT-12:09 | 0.106594E+11 | 48179.42 | 24-OCT-05:10 |
November | 0.273836E+11 | 24364.86 | 25-NOV-16:49 | 0.142081E+12 | 231911.35 | 25-NOV-17:00 |
December | 0.298386E+11 | 24531.13 | 09-DEC-16:49 | 0.283271E+12 | 343741.89 | 09-DEC-08:00 |
Annual Sum or Average | 0.328912E+12 | 0.123686E+13 | ||||
Minimum of Months | 0.255754E+11 | 20809.52 | 0.00 | 0.00 | ||
Maximum of Months | 0.299014E+11 | 32616.86 | 0.365436E+12 | 346036.36 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.451076E+10 | 13530.32 | 29-JAN-12:30 | 0.00 | 0.00 |
February | 0.552877E+10 | 13916.64 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.877826E+10 | 19103.51 | 16-MAR-12:30 | 0.00 | 0.00 |
April | 0.109917E+11 | 21002.45 | 25-APR-12:20 | 0.00 | 0.00 |
May | 0.130505E+11 | 20439.47 | 18-MAY-11:30 | 0.00 | 0.00 |
June | 0.140150E+11 | 20158.17 | 22-JUN-11:00 | 0.00 | 0.00 |
July | 0.144981E+11 | 19653.41 | 15-JUL-12:30 | 0.00 | 0.00 |
August | 0.122406E+11 | 19515.22 | 07-AUG-12:30 | 0.00 | 0.00 |
September | 0.945246E+10 | 17136.07 | 04-SEP-11:00 | 0.00 | 0.00 |
October | 0.668665E+10 | 13966.29 | 01-OCT-12:39 | 0.00 | 0.00 |
November | 0.403833E+10 | 11136.64 | 04-NOV-11:50 | 0.00 | 0.00 |
December | 0.301621E+10 | 9012.93 | 01-DEC-11:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106807E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.301621E+10 | 9012.93 | 0.00 | 0.00 | |
Maximum of Months | 0.144981E+11 | 21002.45 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.842804E+10 | 0.479383E+10 | 0.112984E+11 | 0.00 | 0.429675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108439E+10 | 0.00 |
February | 0.765208E+10 | 0.389230E+10 | 0.103734E+11 | 0.00 | 0.365726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101270E+10 | 0.00 |
March | 0.870915E+10 | 0.370384E+10 | 0.121089E+11 | 0.00 | 0.343837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116710E+10 | 0.00 |
April | 0.810732E+10 | 0.296387E+10 | 0.112578E+11 | 0.00 | 0.232957E+10 | 0.00 | 0.00 | 38035747.90 | 0.00 | 0.00 | 0.00 | 0.104813E+10 | 0.00 |
May | 0.835277E+10 | 0.258625E+10 | 0.117000E+11 | 0.00 | 0.182442E+10 | 0.00 | 0.00 | 85286353.96 | 0.00 | 0.00 | 0.00 | 0.102675E+10 | 0.00 |
June | 0.826680E+10 | 0.229949E+10 | 0.116594E+11 | 0.00 | 0.185547E+10 | 0.00 | 0.00 | 0.143502E+10 | 0.00 | 0.00 | 0.00 | 0.952735E+09 | 0.00 |
July | 0.810005E+10 | 0.244499E+10 | 0.112984E+11 | 0.00 | 0.181261E+10 | 0.00 | 0.00 | 0.247539E+10 | 0.00 | 0.00 | 0.00 | 0.875930E+09 | 0.00 |
August | 0.860637E+10 | 0.282916E+10 | 0.121016E+11 | 0.00 | 0.196210E+10 | 0.00 | 0.00 | 0.225609E+10 | 0.00 | 0.00 | 0.00 | 0.913683E+09 | 0.00 |
September | 0.812042E+10 | 0.330760E+10 | 0.112504E+11 | 0.00 | 0.172665E+10 | 0.00 | 0.00 | 0.838706E+09 | 0.00 | 0.00 | 0.00 | 0.865706E+09 | 0.00 |
October | 0.828910E+10 | 0.405888E+10 | 0.113057E+11 | 0.00 | 0.192640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918736E+09 | 0.00 |
November | 0.807555E+10 | 0.448126E+10 | 0.108562E+11 | 0.00 | 0.303185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938737E+09 | 0.00 |
December | 0.852736E+10 | 0.494534E+10 | 0.112984E+11 | 0.00 | 0.403110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103642E+10 | 0.00 |
Annual Sum or Average | 0.992350E+11 | 0.423068E+11 | 0.136508E+12 | 0.00 | 0.318925E+11 | 0.00 | 0.00 | 0.712854E+10 | 0.00 | 0.00 | 0.00 | 0.118410E+11 | 0.00 |
Minimum of Months | 0.765208E+10 | 0.229949E+10 | 0.103734E+11 | 0.00 | 0.172665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865706E+09 | 0.00 |
Maximum of Months | 0.870915E+10 | 0.494534E+10 | 0.121089E+11 | 0.00 | 0.429675E+10 | 0.00 | 0.00 | 0.247539E+10 | 0.00 | 0.00 | 0.00 | 0.116710E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.365436E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.251130E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.142485E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.392702E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.198030E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 79745894.93 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.463789E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.106594E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.142081E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.283271E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123686E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.365436E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 7924.30 | 10-JAN-15:00 | 3768.97 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3045.77 | 19-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7853.22 | 08-FEB-09:09 | 3768.97 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3125.78 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7823.25 | 13-MAR-08:09 | 3768.97 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2823.36 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7709.98 | 10-APR-08:09 | 3768.97 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2618.71 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7596.44 | 04-MAY-08:09 | 3421.91 | 01-MAY-19:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 2416.30 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7595.80 | 05-JUN-08:09 | 3421.91 | 01-JUN-19:40 | 10035.17 | 01-JUN-07:10 | 0.00 | 4038.75 | 29-JUN-13:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7643.95 | 20-JUL-08:09 | 3421.91 | 01-JUL-19:00 | 10035.17 | 01-JUL-07:10 | 0.00 | 4038.75 | 03-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7634.47 | 29-AUG-08:20 | 3768.97 | 08-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4296.16 | 04-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7774.35 | 21-SEP-08:30 | 3768.97 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1828.98 | 30-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7835.42 | 30-OCT-08:09 | 3768.97 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2429.98 | 19-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7936.24 | 27-NOV-15:00 | 3768.97 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2887.44 | 25-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7987.45 | 12-DEC-15:00 | 3768.97 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 3147.38 | 09-DEC-08:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7595.80 | 3421.91 | 10035.17 | 0.00 | 1828.98 | 0.00 | 0.00 | |||||
Maximum of Months | 7987.45 | 3768.97 | 10035.17 | 0.00 | 4296.16 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1766.02 | 30-JAN-12:00 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 1796.07 | 23-FEB-12:39 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 1788.85 | 02-MAR-12:00 | 0.00 | 01-MAR-00:10 |
April | 1329.44 | 18-APR-15:09 | 0.00 | 0.00 | 0.00 | 1726.73 | 01-APR-11:30 | 0.00 | 01-APR-00:10 |
May | 1540.94 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1643.82 | 01-MAY-11:30 | 0.00 | 01-MAY-00:10 |
June | 6729.31 | 30-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1527.40 | 02-JUN-11:20 | 0.00 | 01-JUN-00:10 |
July | 7907.69 | 03-JUL-14:00 | 0.00 | 0.00 | 0.00 | 1456.51 | 01-JUL-11:00 | 0.00 | 01-JUL-00:10 |
August | 10223.04 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 1401.46 | 02-AUG-11:20 | 0.00 | 01-AUG-00:10 |
September | 5140.38 | 06-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1412.41 | 30-SEP-11:50 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 1507.08 | 31-OCT-11:20 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 1610.88 | 30-NOV-12:39 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1716.11 | 30-DEC-12:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1401.46 | 0.00 | |||
Maximum of Months | 10223.04 | 0.00 | 0.00 | 0.00 | 1796.07 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 24514.43 | 18-JAN-16:00 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 2935.62 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22088.06 | 02-FEB-13:20 | 7667.39 | 10035.17 | 0.00 | 0.00 | 2787.27 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21750.90 | 02-MAR-15:00 | 7650.15 | 10035.17 | 0.00 | 0.00 | 2465.56 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21875.41 | 18-APR-14:00 | 7297.27 | 10035.17 | 0.00 | 0.00 | 1733.46 | 0.00 | 0.00 | 1305.15 | 0.00 |
May | 21972.71 | 31-MAY-14:00 | 7297.27 | 10035.17 | 0.00 | 0.00 | 1733.46 | 0.00 | 0.00 | 1516.72 | 0.00 |
June | 29391.20 | 30-JUN-14:50 | 7297.27 | 10035.17 | 0.00 | 0.00 | 4038.75 | 0.00 | 0.00 | 6711.02 | 0.00 |
July | 30567.08 | 03-JUL-14:00 | 7297.27 | 10035.17 | 0.00 | 0.00 | 4038.75 | 0.00 | 0.00 | 7907.69 | 0.00 |
August | 32616.86 | 04-AUG-14:00 | 7297.27 | 10035.17 | 0.00 | 0.00 | 4245.16 | 0.00 | 0.00 | 9810.65 | 0.00 |
September | 25377.59 | 08-SEP-14:09 | 7297.27 | 10035.17 | 0.00 | 0.00 | 1733.46 | 0.00 | 0.00 | 5082.92 | 0.00 |
October | 20809.52 | 27-OCT-12:09 | 7720.83 | 10035.17 | 0.00 | 0.00 | 1733.46 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24364.86 | 25-NOV-16:49 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 2810.64 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24531.13 | 09-DEC-16:49 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 2975.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 20809.52 | 7180.87 | 10035.17 | 0.00 | 0.00 | 1733.46 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32616.86 | 7720.83 | 10035.17 | 3768.97 | 0.00 | 4245.16 | 0.00 | 0.00 | 9810.65 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 346036.36 | 18-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 305867.60 | 01-FEB-20:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 238870.43 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 139771.60 | 02-APR-23:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 44018.64 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6065.61 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 20766.91 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 48179.42 | 24-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 231911.35 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 343741.89 | 09-DEC-08:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 346036.36 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.17 | 16.08 | 8.83 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
February | 26.50 | 16.21 | 8.33 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
March | 14.33 | 17.99 | 10.17 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
April | 7.83 | 19.36 | 7.33 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
May | 2.17 | 20.14 | 2.17 | 20.14 | 0.00 | 20.14 | 0.00 | 20.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.53 | 1.17 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.56 | 1.67 | 24.56 |
September | 0.83 | 20.31 | 0.83 | 20.31 | 0.33 | 21.01 | 0.33 | 21.51 |
October | 7.17 | 20.09 | 7.17 | 20.09 | 0.00 | 20.09 | 0.00 | 20.09 |
November | 12.83 | 17.76 | 7.50 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
December | 23.67 | 16.52 | 9.00 | 17.25 | 0.00 | 17.25 | 0.00 | 17.25 |
Annual Sum or Average | 125.50 | 17.11 | 61.33 | 17.87 | 3.33 | 17.99 | 3.33 | 18.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.74 | 0.00 | 16.74 |
Maximum of Months | 30.17 | 20.31 | 10.17 | 20.31 | 1.67 | 24.56 | 1.67 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.17 | 14.31 | 4.17 | 14.31 | 0.00 | 14.31 | 0.00 | 14.31 |
February | 97.50 | 14.49 | 4.17 | 14.49 | 0.00 | 14.49 | 0.00 | 14.49 |
March | 72.00 | 14.68 | 4.67 | 14.68 | 0.00 | 14.68 | 0.00 | 14.68 |
April | 28.17 | 14.85 | 1.67 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
May | 0.33 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.00 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.28 | 0.00 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.00 | 27.32 |
September | 0.33 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
October | 6.33 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
November | 65.83 | 14.62 | 2.83 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
December | 111.33 | 14.52 | 4.33 | 14.52 | 0.00 | 14.52 | 0.00 | 14.52 |
Annual Sum or Average | 497.00 | 14.53 | 21.83 | 14.53 | 1.67 | 14.57 | 0.00 | 14.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 0.00 | 14.31 |
Maximum of Months | 115.17 | 14.99 | 4.67 | 14.99 | 0.83 | 27.32 | 0.00 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.33 | 8.67 | 8.50 | 8.58 | 0.00 | 8.58 | 0.00 | 8.58 |
Annual Sum or Average | 13.33 | 8.67 | 8.50 | 8.58 | 0.00 | 8.58 | 0.00 | 8.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.33 | 8.67 | 8.50 | 8.58 | 0.00 | 8.58 | 0.00 | 8.58 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
February | 276.00 | 21.03 | 276.00 | 21.03 | 276.00 | 21.03 |
March | 324.00 | 21.04 | 324.00 | 21.04 | 324.00 | 21.04 |
April | 300.00 | 21.37 | 253.17 | 21.28 | 253.17 | 21.25 |
May | 305.67 | 22.46 | 92.33 | 22.29 | 92.17 | 22.19 |
June | 159.50 | 23.28 | 155.83 | 23.56 | 58.00 | 23.60 |
July | 84.67 | 23.88 | 276.83 | 23.90 | 81.83 | 23.90 |
August | 103.50 | 23.89 | 284.83 | 23.90 | 97.83 | 23.90 |
September | 158.67 | 22.62 | 142.33 | 22.83 | 45.83 | 22.62 |
October | 300.00 | 21.26 | 258.67 | 21.18 | 258.67 | 21.15 |
November | 288.00 | 21.10 | 270.83 | 21.08 | 270.83 | 21.07 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 2900.00 | 21.64 | 2934.83 | 21.76 | 2358.33 | 21.65 |
Minimum of Months | 84.67 | 21.03 | 92.33 | 21.03 | 45.83 | 21.03 |
Maximum of Months | 324.00 | 23.89 | 324.00 | 23.90 | 324.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
February | 276.00 | 15.55 | 276.00 | 15.55 | 276.00 | 15.55 |
March | 324.00 | 15.72 | 324.00 | 15.72 | 324.00 | 15.72 |
April | 300.00 | 16.88 | 285.67 | 16.76 | 285.67 | 16.72 |
May | 311.17 | 19.93 | 208.50 | 19.69 | 207.67 | 19.58 |
June | 223.00 | 23.66 | 228.00 | 24.28 | 149.67 | 24.32 |
July | 217.67 | 26.26 | 288.83 | 26.22 | 213.33 | 26.25 |
August | 180.50 | 26.09 | 302.33 | 26.09 | 175.50 | 26.11 |
September | 172.50 | 21.02 | 210.67 | 22.21 | 96.33 | 21.76 |
October | 300.00 | 16.67 | 300.00 | 16.67 | 300.00 | 16.67 |
November | 288.00 | 15.95 | 288.00 | 15.95 | 288.00 | 15.95 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 3192.83 | 18.45 | 3312.00 | 18.75 | 2916.17 | 18.56 |
Minimum of Months | 172.50 | 15.54 | 208.50 | 15.54 | 96.33 | 15.54 |
Maximum of Months | 324.00 | 26.26 | 324.00 | 26.22 | 324.00 | 26.25 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
February | 276.00 | 10.04 | 276.00 | 10.04 | 276.00 | 10.04 |
March | 324.00 | 10.48 | 324.00 | 10.48 | 324.00 | 10.48 |
April | 300.00 | 12.83 | 299.50 | 12.82 | 299.50 | 12.82 |
May | 308.33 | 17.57 | 298.00 | 17.53 | 295.67 | 17.50 |
June | 241.50 | 22.99 | 225.67 | 23.48 | 166.00 | 23.47 |
July | 227.17 | 27.30 | 288.50 | 27.13 | 222.00 | 27.21 |
August | 214.00 | 26.74 | 294.00 | 26.64 | 199.83 | 26.74 |
September | 203.00 | 20.79 | 204.50 | 21.49 | 125.17 | 21.13 |
October | 300.00 | 13.09 | 300.00 | 13.09 | 300.00 | 13.09 |
November | 288.00 | 11.08 | 288.00 | 11.08 | 288.00 | 11.08 |
December | 300.00 | 9.96 | 300.00 | 9.96 | 300.00 | 9.96 |
Annual Sum or Average | 3282.00 | 15.31 | 3398.17 | 15.58 | 3096.17 | 15.37 |
Minimum of Months | 203.00 | 9.96 | 204.50 | 9.96 | 125.17 | 9.96 |
Maximum of Months | 324.00 | 27.30 | 324.00 | 27.13 | 324.00 | 27.21 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.161059E+09 | 38035747.90 | 13.00 | 0.113419E+09 | 47640431.58 | 0.00 | 0.59 | 18-APR-15:10 | 0.00 | 01-APR-00:05 | 5775.91 | 18-APR-15:10 | 4181.57 | 18-APR-15:10 | 1594.34 | 18-APR-15:10 | 1329.44 | 18-APR-15:10 | 0.00 | 01-APR-00:05 |
May | 0.364999E+09 | 85286353.96 | 31.50 | 0.280303E+09 | 84696281.51 | 0.00 | 0.69 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 | 6491.55 | 31-MAY-15:10 | 5459.26 | 31-MAY-15:10 | 1404.72 | 30-MAY-14:00 | 1540.94 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 0.367046E+10 | 0.810695E+09 | 177.91 | 0.273155E+10 | 0.938915E+09 | 0.00 | 1.00 | 14-JUN-05:03 | 0.00 | 01-JUN-00:10 | 21185.71 | 26-JUN-05:45 | 11167.44 | 30-JUN-05:01 | 11219.46 | 26-JUN-05:05 | 4444.92 | 26-JUN-05:45 | 0.00 | 01-JUN-00:10 |
July | 0.605389E+10 | 0.130447E+10 | 246.98 | 0.426625E+10 | 0.178764E+10 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 20824.26 | 27-JUL-05:02 | 12863.54 | 05-JUL-05:13 | 11724.64 | 27-JUL-05:02 | 4391.97 | 27-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.611975E+10 | 0.133394E+10 | 265.24 | 0.434044E+10 | 0.177930E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 22843.58 | 04-AUG-05:01 | 11504.29 | 09-AUG-05:03 | 14325.36 | 04-AUG-05:07 | 4658.65 | 04-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.227914E+10 | 0.516659E+09 | 122.99 | 0.199600E+10 | 0.283133E+09 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 19436.86 | 11-SEP-05:02 | 13150.79 | 18-SEP-05:03 | 9068.44 | 12-SEP-05:03 | 4167.26 | 11-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.186493E+11 | 0.408909E+10 | 857.62 | 0.137280E+11 | 0.492133E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.611975E+10 | 0.133394E+10 | 265.24 | 0.434044E+10 | 0.178764E+10 | 0.00 | 1.00 | 0.00 | 22843.58 | 13150.79 | 14325.36 | 4658.65 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.257574E+10 | 0.624324E+09 | 73.39 | 0.166947E+10 | 0.906268E+09 | 0.00 | 1.00 | 25-JUN-13:55 | 0.00 | 01-JUN-00:10 | 44368.64 | 30-JUN-18:42 | 30752.37 | 28-JUN-18:55 | 15211.67 | 30-JUN-19:25 | 9828.97 | 30-JUN-18:42 | 0.00 | 01-JUN-00:10 |
July | 0.497226E+10 | 0.117092E+10 | 149.14 | 0.301852E+10 | 0.195374E+10 | 0.00 | 1.00 | 01-JUL-17:20 | 0.00 | 01-JUL-00:10 | 49535.51 | 03-JUL-20:05 | 32804.51 | 05-JUL-17:10 | 26254.85 | 03-JUL-20:05 | 10492.23 | 03-JUL-20:05 | 0.00 | 01-JUL-00:10 |
August | 0.385532E+10 | 0.922153E+09 | 123.83 | 0.231927E+10 | 0.153605E+10 | 0.00 | 1.00 | 01-AUG-18:25 | 0.00 | 01-AUG-00:10 | 50304.19 | 03-AUG-18:55 | 30567.30 | 05-AUG-17:42 | 27345.07 | 03-AUG-18:55 | 10665.20 | 03-AUG-18:55 | 0.00 | 01-AUG-00:10 |
September | 0.124742E+10 | 0.322047E+09 | 59.25 | 0.974925E+09 | 0.272494E+09 | 0.00 | 0.84 | 10-SEP-14:35 | 0.00 | 01-SEP-00:10 | 17502.85 | 10-SEP-14:35 | 13278.32 | 10-SEP-14:35 | 4224.53 | 10-SEP-14:35 | 4090.23 | 10-SEP-14:35 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.126507E+11 | 0.303945E+10 | 405.61 | 0.798219E+10 | 0.466855E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.497226E+10 | 0.117092E+10 | 149.14 | 0.301852E+10 | 0.195374E+10 | 0.00 | 1.00 | 0.00 | 50304.19 | 32804.51 | 27345.07 | 10665.20 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.15 | 26.83 | 39.31 | 32.91 | 214.57 | 0.00 | 0.00 | 0.00 |
February | 96.22 | 47.20 | 49.02 | 68.56 | 166.02 | 0.00 | 0.00 | 0.00 |
March | 115.53 | 43.04 | 72.49 | 99.83 | 99.76 | 0.00 | 0.00 | 0.00 |
April | 168.42 | 83.23 | 85.19 | 189.12 | 64.81 | 0.00 | 0.00 | 0.00 |
May | 168.88 | 67.47 | 101.41 | 208.47 | 38.23 | 0.00 | 0.00 | 0.00 |
June | 197.85 | 85.58 | 112.27 | 255.30 | 34.26 | 0.00 | 0.00 | 0.00 |
July | 212.89 | 101.17 | 111.71 | 276.94 | 36.03 | 0.00 | 0.00 | 0.00 |
August | 185.54 | 84.86 | 100.68 | 242.34 | 42.10 | 0.00 | 0.00 | 0.00 |
September | 150.56 | 71.38 | 79.18 | 182.68 | 61.92 | 0.00 | 0.00 | 0.00 |
October | 105.38 | 46.97 | 58.41 | 111.22 | 73.99 | 0.00 | 0.00 | 0.00 |
November | 63.04 | 23.41 | 39.62 | 45.23 | 123.55 | 0.00 | 0.00 | 0.00 |
December | 48.69 | 23.16 | 25.53 | 29.34 | 191.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.74 | 58.71 | 73.03 | 145.54 | 95.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.69 | 23.16 | 25.53 | 29.34 | 34.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.89 | 101.17 | 112.27 | 276.94 | 214.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.15 | 26.83 | 39.31 | 32.91 | 214.57 | 0.00 | 0.00 | 0.00 |
February | 96.22 | 47.20 | 49.02 | 68.56 | 166.02 | 0.00 | 0.00 | 0.00 |
March | 115.53 | 43.04 | 72.49 | 99.83 | 99.76 | 0.00 | 0.00 | 0.00 |
April | 168.42 | 83.23 | 85.19 | 189.12 | 64.81 | 0.00 | 0.00 | 0.00 |
May | 168.88 | 67.47 | 101.41 | 208.47 | 38.23 | 0.00 | 0.00 | 0.00 |
June | 197.85 | 85.58 | 112.27 | 255.30 | 34.26 | 0.00 | 0.00 | 0.00 |
July | 212.89 | 101.17 | 111.71 | 276.94 | 36.03 | 0.00 | 0.00 | 0.00 |
August | 185.54 | 84.86 | 100.68 | 242.34 | 42.10 | 0.00 | 0.00 | 0.00 |
September | 150.56 | 71.38 | 79.18 | 182.68 | 61.92 | 0.00 | 0.00 | 0.00 |
October | 105.38 | 46.97 | 58.41 | 111.22 | 73.99 | 0.00 | 0.00 | 0.00 |
November | 63.04 | 23.41 | 39.62 | 45.23 | 123.55 | 0.00 | 0.00 | 0.00 |
December | 48.69 | 23.16 | 25.53 | 29.34 | 191.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.74 | 58.71 | 73.03 | 145.54 | 95.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.69 | 23.16 | 25.53 | 29.34 | 34.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.89 | 101.17 | 112.27 | 276.94 | 214.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.10 | 0.00 | 18.10 | 0.18 | 136.71 | 0.00 | 0.00 | 0.00 |
February | 22.95 | 0.00 | 22.95 | 2.22 | 106.38 | 0.00 | 0.00 | 0.00 |
March | 34.40 | 0.00 | 34.40 | 15.17 | 61.92 | 0.00 | 0.00 | 0.00 |
April | 39.80 | 0.27 | 39.53 | 28.85 | 38.55 | 0.00 | 0.00 | 0.00 |
May | 51.87 | 2.01 | 49.86 | 55.22 | 21.19 | 0.00 | 0.00 | 0.00 |
June | 60.48 | 5.46 | 55.02 | 72.01 | 18.97 | 0.00 | 0.00 | 0.00 |
July | 56.74 | 3.81 | 52.93 | 67.04 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 0.99 | 46.70 | 55.75 | 23.66 | 0.00 | 0.00 | 0.00 |
September | 36.47 | 0.02 | 36.45 | 34.77 | 36.74 | 0.00 | 0.00 | 0.00 |
October | 27.09 | 0.00 | 27.09 | 17.60 | 44.72 | 0.00 | 0.00 | 0.00 |
November | 18.95 | 0.00 | 18.95 | 4.95 | 76.41 | 0.00 | 0.00 | 0.00 |
December | 12.29 | 0.00 | 12.29 | 0.08 | 118.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.64 | 1.05 | 34.59 | 29.65 | 58.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.29 | 0.00 | 12.29 | 0.08 | 18.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.48 | 5.46 | 55.02 | 72.01 | 136.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.10 | 0.00 | 18.10 | 0.18 | 136.71 | 0.00 | 0.00 | 0.00 |
February | 22.95 | 0.00 | 22.95 | 2.22 | 106.38 | 0.00 | 0.00 | 0.00 |
March | 34.40 | 0.00 | 34.40 | 15.17 | 61.93 | 0.00 | 0.00 | 0.00 |
April | 39.80 | 0.27 | 39.53 | 28.85 | 38.55 | 0.00 | 0.00 | 0.00 |
May | 51.86 | 2.01 | 49.86 | 55.22 | 21.19 | 0.00 | 0.00 | 0.00 |
June | 60.48 | 5.46 | 55.02 | 72.00 | 18.97 | 0.00 | 0.00 | 0.00 |
July | 56.74 | 3.81 | 52.93 | 67.04 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 0.99 | 46.70 | 55.75 | 23.66 | 0.00 | 0.00 | 0.00 |
September | 36.47 | 0.02 | 36.45 | 34.76 | 36.74 | 0.00 | 0.00 | 0.00 |
October | 27.09 | 0.00 | 27.09 | 17.60 | 44.72 | 0.00 | 0.00 | 0.00 |
November | 18.95 | 0.00 | 18.95 | 4.94 | 76.41 | 0.00 | 0.00 | 0.00 |
December | 12.29 | 0.00 | 12.29 | 0.08 | 118.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.64 | 1.05 | 34.58 | 29.65 | 58.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.29 | 0.00 | 12.29 | 0.08 | 18.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.48 | 5.46 | 55.02 | 72.00 | 136.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.38 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.71 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.97 | 25.69 | 42.17 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.79 | 18.80 | 29.17 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.50 | 21.61 | 19.17 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.52 | 27.00 | 11.50 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.05 | 27.82 | 16.00 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.00 | 37.35 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.36 | 31.37 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.04 | 48.17 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.91 | 42.38 | 133.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.50 | 89.27 | 42.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.38 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.71 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.97 | 25.69 | 42.17 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.79 | 18.80 | 29.17 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.50 | 21.61 | 19.17 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.52 | 27.00 | 11.50 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.05 | 27.82 | 16.00 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.00 | 37.35 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.36 | 31.37 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.04 | 48.17 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.91 | 42.38 | 133.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.50 | 89.27 | 42.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.38 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.71 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.97 | 25.69 | 42.17 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.79 | 18.80 | 29.17 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.50 | 21.61 | 19.17 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.52 | 27.00 | 11.50 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.05 | 27.82 | 16.00 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.00 | 37.35 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.36 | 31.37 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.04 | 48.17 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.91 | 42.38 | 133.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.50 | 89.27 | 42.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.38 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.71 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.97 | 25.69 | 42.17 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.79 | 18.80 | 29.17 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.50 | 21.61 | 19.17 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.52 | 27.00 | 11.50 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.05 | 27.82 | 16.00 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.00 | 37.35 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.36 | 31.37 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.04 | 48.17 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.91 | 42.38 | 133.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.50 | 89.27 | 42.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.38 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.71 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.97 | 25.69 | 42.17 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.79 | 18.80 | 29.17 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.50 | 21.61 | 19.17 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.52 | 27.00 | 11.50 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.05 | 27.82 | 16.00 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.00 | 37.35 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.36 | 31.37 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.04 | 48.17 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.91 | 42.38 | 133.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.50 | 89.27 | 42.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.38 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.71 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.97 | 25.69 | 42.17 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.79 | 18.80 | 29.17 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.50 | 21.61 | 19.17 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.52 | 27.00 | 11.50 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.05 | 27.82 | 16.00 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.00 | 37.35 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.36 | 31.37 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.04 | 48.17 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.91 | 42.38 | 133.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.50 | 89.27 | 42.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.38 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.71 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.97 | 25.69 | 42.17 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.79 | 18.80 | 29.17 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.50 | 21.61 | 19.17 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.52 | 27.00 | 11.50 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.05 | 27.82 | 16.00 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.00 | 37.35 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.36 | 31.37 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.04 | 48.17 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.91 | 42.38 | 133.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.50 | 89.27 | 42.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.38 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.71 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.97 | 25.69 | 42.17 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.79 | 18.80 | 29.17 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.50 | 21.61 | 19.17 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.52 | 27.00 | 11.50 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.05 | 27.82 | 16.00 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.00 | 37.35 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.36 | 31.37 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.04 | 48.17 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.91 | 42.38 | 133.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.50 | 89.27 | 42.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.38 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.71 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.97 | 25.69 | 42.17 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.79 | 18.80 | 29.17 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.50 | 21.61 | 19.17 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.52 | 27.00 | 11.50 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.05 | 27.82 | 16.00 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.00 | 37.35 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.36 | 31.37 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.04 | 48.17 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.91 | 42.38 | 133.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.50 | 89.27 | 42.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.27 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.38 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.71 | 39.03 | 9.67 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 129.97 | 25.69 | 42.17 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 164.79 | 18.80 | 29.17 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 184.50 | 21.61 | 19.17 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 181.52 | 27.00 | 11.50 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.05 | 27.82 | 16.00 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.00 | 37.35 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.36 | 31.37 | 5.33 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.04 | 48.17 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 99.91 | 42.38 | 133.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 184.50 | 89.27 | 42.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177164E+09 | 71868735.54 | 0.105295E+09 | 88133762.31 | 0.574704E+09 |
February | 0.232773E+09 | 0.114177E+09 | 0.118596E+09 | 0.165858E+09 | 0.401642E+09 |
March | 0.309440E+09 | 0.115273E+09 | 0.194167E+09 | 0.267394E+09 | 0.267190E+09 |
April | 0.436545E+09 | 0.215723E+09 | 0.220821E+09 | 0.490202E+09 | 0.167996E+09 |
May | 0.452321E+09 | 0.180716E+09 | 0.271605E+09 | 0.558354E+09 | 0.102395E+09 |
June | 0.512839E+09 | 0.221835E+09 | 0.291004E+09 | 0.661737E+09 | 88812457.25 |
July | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.741757E+09 | 96506721.93 |
August | 0.496950E+09 | 0.227280E+09 | 0.269670E+09 | 0.649073E+09 | 0.112748E+09 |
September | 0.390252E+09 | 0.185011E+09 | 0.205242E+09 | 0.473508E+09 | 0.160503E+09 |
October | 0.282254E+09 | 0.125817E+09 | 0.156437E+09 | 0.297880E+09 | 0.198188E+09 |
November | 0.163395E+09 | 60689328.10 | 0.102706E+09 | 0.117224E+09 | 0.320253E+09 |
December | 0.130405E+09 | 62020230.89 | 68384856.96 | 78586677.75 | 0.512362E+09 |
Annual Sum or Average | 0.415453E+10 | 0.185139E+10 | 0.230314E+10 | 0.458971E+10 | 0.300330E+10 |
Minimum of Months | 0.130405E+09 | 60689328.10 | 68384856.96 | 78586677.75 | 88812457.25 |
Maximum of Months | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.741757E+09 | 0.574704E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177164E+09 | 71868735.54 | 0.105295E+09 | 88133762.31 | 0.574704E+09 |
February | 0.232773E+09 | 0.114177E+09 | 0.118596E+09 | 0.165858E+09 | 0.401642E+09 |
March | 0.309440E+09 | 0.115273E+09 | 0.194167E+09 | 0.267394E+09 | 0.267190E+09 |
April | 0.436545E+09 | 0.215723E+09 | 0.220821E+09 | 0.490202E+09 | 0.167996E+09 |
May | 0.452321E+09 | 0.180716E+09 | 0.271605E+09 | 0.558354E+09 | 0.102395E+09 |
June | 0.512839E+09 | 0.221835E+09 | 0.291004E+09 | 0.661737E+09 | 88812457.25 |
July | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.741757E+09 | 96506721.93 |
August | 0.496950E+09 | 0.227280E+09 | 0.269670E+09 | 0.649073E+09 | 0.112748E+09 |
September | 0.390252E+09 | 0.185011E+09 | 0.205242E+09 | 0.473508E+09 | 0.160503E+09 |
October | 0.282254E+09 | 0.125817E+09 | 0.156437E+09 | 0.297880E+09 | 0.198188E+09 |
November | 0.163395E+09 | 60689328.10 | 0.102706E+09 | 0.117224E+09 | 0.320253E+09 |
December | 0.130405E+09 | 62020230.89 | 68384856.96 | 78586677.75 | 0.512362E+09 |
Annual Sum or Average | 0.415453E+10 | 0.185139E+10 | 0.230314E+10 | 0.458971E+10 | 0.300330E+10 |
Minimum of Months | 0.130405E+09 | 60689328.10 | 68384856.96 | 78586677.75 | 88812457.25 |
Maximum of Months | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.741757E+09 | 0.574704E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48488126.83 | 0.00 | 48488126.83 | 470711.95 | 0.366170E+09 |
February | 55524446.54 | 0.00 | 55524446.54 | 5375703.75 | 0.257347E+09 |
March | 92146307.37 | 2499.55 | 92143807.82 | 40631994.81 | 0.165860E+09 |
April | 0.103167E+09 | 702085.40 | 0.102464E+09 | 74778609.05 | 99911559.33 |
May | 0.138917E+09 | 5379542.38 | 0.133537E+09 | 0.147911E+09 | 56763870.02 |
June | 0.156769E+09 | 14161738.08 | 0.142608E+09 | 0.186639E+09 | 49162777.87 |
July | 0.151972E+09 | 10196569.90 | 0.141776E+09 | 0.179572E+09 | 53811681.05 |
August | 0.127740E+09 | 2661251.59 | 0.125078E+09 | 0.149327E+09 | 63372195.92 |
September | 94536431.71 | 63161.34 | 94473270.37 | 90111080.90 | 95237668.53 |
October | 72562893.63 | 0.00 | 72562893.63 | 47148676.75 | 0.119768E+09 |
November | 49121072.59 | 0.00 | 49121072.59 | 12817640.93 | 0.198053E+09 |
December | 32924996.33 | 0.00 | 32924996.33 | 224818.04 | 0.318365E+09 |
Annual Sum or Average | 0.112387E+10 | 33166848.24 | 0.109070E+10 | 0.935008E+09 | 0.184382E+10 |
Minimum of Months | 32924996.33 | 0.00 | 32924996.33 | 224818.04 | 49162777.87 |
Maximum of Months | 0.156769E+09 | 14161738.08 | 0.142608E+09 | 0.186639E+09 | 0.366170E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48486565.90 | 0.00 | 48486565.90 | 470591.09 | 0.366171E+09 |
February | 55522718.22 | 0.00 | 55522718.22 | 5375086.81 | 0.257348E+09 |
March | 92143381.60 | 2499.43 | 92140882.17 | 40629275.83 | 0.165860E+09 |
April | 0.103164E+09 | 702052.49 | 0.102461E+09 | 74775656.77 | 99911847.46 |
May | 0.138913E+09 | 5379290.24 | 0.133533E+09 | 0.147906E+09 | 56763560.71 |
June | 0.156765E+09 | 14161074.30 | 0.142603E+09 | 0.186633E+09 | 49162399.77 |
July | 0.151968E+09 | 10196091.97 | 0.141771E+09 | 0.179566E+09 | 53811156.63 |
August | 0.127736E+09 | 2661126.85 | 0.125075E+09 | 0.149322E+09 | 63371799.63 |
September | 94533632.71 | 63158.38 | 94470474.33 | 90107998.16 | 95237153.73 |
October | 72560611.18 | 0.00 | 72560611.18 | 47146275.04 | 0.119767E+09 |
November | 49119433.09 | 0.00 | 49119433.09 | 12816664.58 | 0.198053E+09 |
December | 32923954.99 | 0.00 | 32923954.99 | 224761.45 | 0.318365E+09 |
Annual Sum or Average | 0.112383E+10 | 33165293.66 | 0.109067E+10 | 0.934973E+09 | 0.184382E+10 |
Minimum of Months | 32923954.99 | 0.00 | 32923954.99 | 224761.45 | 49162399.77 |
Maximum of Months | 0.156765E+09 | 14161074.30 | 0.142603E+09 | 0.186633E+09 | 0.366171E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55986697.94 | 0.239112E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99066613.58 | 0.165435E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232246E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336878E+09 | 66581428.05 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.441385E+09 | 50362161.49 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.478232E+09 | 56020950.46 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486194E+09 | 72321153.77 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409929E+09 | 74503380.01 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295489E+09 | 96805954.04 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191142E+09 | 84034332.23 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85638934.78 | 0.124844E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 0.202068E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.315081E+10 | 0.133662E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 50362161.49 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486194E+09 | 0.239112E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55986697.94 | 0.239112E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99066613.58 | 0.165435E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232246E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336878E+09 | 66581428.05 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.441385E+09 | 50362161.49 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.478232E+09 | 56020950.46 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486194E+09 | 72321153.77 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409929E+09 | 74503380.01 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295489E+09 | 96805954.04 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191142E+09 | 84034332.23 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85638934.78 | 0.124844E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 0.202068E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.315081E+10 | 0.133662E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 50362161.49 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486194E+09 | 0.239112E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55986697.94 | 0.239112E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99066613.58 | 0.165435E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232246E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336878E+09 | 66581428.05 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.441385E+09 | 50362161.49 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.478232E+09 | 56020950.46 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486194E+09 | 72321153.77 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409929E+09 | 74503380.01 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295489E+09 | 96805954.04 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191142E+09 | 84034332.23 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85638934.78 | 0.124844E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 0.202068E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.315081E+10 | 0.133662E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 50362161.49 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486194E+09 | 0.239112E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55986697.94 | 0.239112E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99066613.58 | 0.165435E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232246E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336878E+09 | 66581428.05 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.441385E+09 | 50362161.49 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.478232E+09 | 56020950.46 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486194E+09 | 72321153.77 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409929E+09 | 74503380.01 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295489E+09 | 96805954.04 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191142E+09 | 84034332.23 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85638934.78 | 0.124844E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 0.202068E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.315081E+10 | 0.133662E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 50362161.49 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486194E+09 | 0.239112E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55986697.94 | 0.239112E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99066613.58 | 0.165435E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232246E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336878E+09 | 66581428.05 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.441385E+09 | 50362161.49 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.478232E+09 | 56020950.46 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486194E+09 | 72321153.77 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409929E+09 | 74503380.01 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295489E+09 | 96805954.04 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191142E+09 | 84034332.23 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85638934.78 | 0.124844E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 0.202068E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.315081E+10 | 0.133662E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 50362161.49 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486194E+09 | 0.239112E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55986697.94 | 0.239112E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99066613.58 | 0.165435E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232246E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336878E+09 | 66581428.05 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.441385E+09 | 50362161.49 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.478232E+09 | 56020950.46 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486194E+09 | 72321153.77 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409929E+09 | 74503380.01 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295489E+09 | 96805954.04 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191142E+09 | 84034332.23 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85638934.78 | 0.124844E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 0.202068E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.315081E+10 | 0.133662E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 50362161.49 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486194E+09 | 0.239112E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55986697.94 | 0.239112E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99066613.58 | 0.165435E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232246E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336878E+09 | 66581428.05 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.441385E+09 | 50362161.49 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.478232E+09 | 56020950.46 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486194E+09 | 72321153.77 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409929E+09 | 74503380.01 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295489E+09 | 96805954.04 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191142E+09 | 84034332.23 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85638934.78 | 0.124844E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 0.202068E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.315081E+10 | 0.133662E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 50362161.49 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486194E+09 | 0.239112E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55986697.94 | 0.239112E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99066613.58 | 0.165435E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232246E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336878E+09 | 66581428.05 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.441385E+09 | 50362161.49 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.478232E+09 | 56020950.46 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486194E+09 | 72321153.77 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409929E+09 | 74503380.01 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295489E+09 | 96805954.04 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191142E+09 | 84034332.23 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85638934.78 | 0.124844E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 0.202068E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.315081E+10 | 0.133662E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 50362161.49 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486194E+09 | 0.239112E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55986697.94 | 0.239112E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99066613.58 | 0.165435E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232246E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336878E+09 | 66581428.05 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.441385E+09 | 50362161.49 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.478232E+09 | 56020950.46 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486194E+09 | 72321153.77 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409929E+09 | 74503380.01 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295489E+09 | 96805954.04 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191142E+09 | 84034332.23 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85638934.78 | 0.124844E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 0.202068E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.315081E+10 | 0.133662E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 50362161.49 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486194E+09 | 0.239112E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55986697.94 | 0.239112E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99066613.58 | 0.165435E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232246E+09 | 0.104533E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.336878E+09 | 66581428.05 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.441385E+09 | 50362161.49 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.478232E+09 | 56020950.46 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.486194E+09 | 72321153.77 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.409929E+09 | 74503380.01 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.295489E+09 | 96805954.04 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.191142E+09 | 84034332.23 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85638934.78 | 0.124844E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 0.202068E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.315081E+10 | 0.133662E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38620718.37 | 50362161.49 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.486194E+09 | 0.239112E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 50.77 | 687.18 | 168.50 | 53.67 | 114.83 | 0.00 | 0.00 |
February | 125.58 | 528.82 | 238.34 | 94.39 | 143.95 | 0.00 | 0.00 |
March | 224.40 | 317.75 | 299.87 | 86.08 | 213.79 | 0.00 | 0.00 |
April | 434.22 | 205.00 | 416.44 | 166.99 | 249.45 | 0.00 | 0.00 |
May | 525.83 | 117.30 | 441.48 | 138.96 | 302.52 | 0.00 | 0.00 |
June | 652.41 | 104.26 | 516.67 | 182.10 | 334.57 | 0.00 | 0.00 |
July | 686.43 | 110.70 | 539.25 | 209.96 | 329.29 | 0.00 | 0.00 |
August | 595.54 | 130.87 | 466.46 | 171.70 | 294.76 | 0.00 | 0.00 |
September | 433.53 | 195.97 | 374.06 | 142.80 | 231.26 | 0.00 | 0.00 |
October | 255.06 | 234.84 | 264.95 | 93.95 | 171.00 | 0.00 | 0.00 |
November | 94.30 | 393.88 | 163.98 | 46.83 | 117.15 | 0.00 | 0.00 |
December | 48.09 | 609.56 | 121.96 | 46.31 | 75.65 | 0.00 | 0.00 |
Annual Sum or Average | 344.98 | 302.01 | 334.75 | 119.52 | 215.24 | 0.00 | 0.00 |
Minimum of Months | 48.09 | 104.26 | 121.96 | 46.31 | 75.65 | 0.00 | 0.00 |
Maximum of Months | 686.43 | 687.18 | 539.25 | 209.96 | 334.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1193.04 | 7174.27 | 350.83 | 151.47 | 199.36 | 0.00 | 0.00 |
February | 2133.95 | 5417.56 | 482.05 | 240.10 | 241.94 | 0.00 | 0.00 |
March | 4021.29 | 2713.33 | 760.85 | 364.27 | 396.58 | 0.00 | 0.00 |
April | 5290.86 | 1353.24 | 1034.01 | 622.06 | 411.94 | 0.00 | 0.00 |
May | 6467.77 | 637.55 | 1242.44 | 699.11 | 543.33 | 0.00 | 0.00 |
June | 7194.09 | 658.37 | 1412.66 | 827.20 | 585.46 | 0.00 | 0.00 |
July | 6822.74 | 852.27 | 1423.59 | 876.76 | 546.84 | 0.00 | 0.00 |
August | 5611.31 | 888.23 | 1185.29 | 675.75 | 509.54 | 0.00 | 0.00 |
September | 4307.40 | 1202.69 | 920.54 | 534.73 | 385.81 | 0.00 | 0.00 |
October | 2770.12 | 1422.10 | 583.32 | 288.68 | 294.64 | 0.00 | 0.00 |
November | 1474.88 | 3169.16 | 347.07 | 127.52 | 219.55 | 0.00 | 0.00 |
December | 743.69 | 5482.11 | 237.38 | 115.44 | 121.94 | 0.00 | 0.00 |
Annual Sum or Average | 4011.77 | 2568.39 | 833.48 | 461.33 | 372.15 | 0.00 | 0.00 |
Minimum of Months | 743.69 | 637.55 | 237.38 | 115.44 | 121.94 | 0.00 | 0.00 |
Maximum of Months | 7194.09 | 7174.27 | 1423.59 | 876.76 | 585.46 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135991E+09 | 0.184053E+10 | 0.451302E+09 | 0.143737E+09 | 0.307564E+09 | 0.00 | 0.00 |
February | 0.303800E+09 | 0.127931E+10 | 0.576593E+09 | 0.228354E+09 | 0.348239E+09 | 0.00 | 0.00 |
March | 0.601023E+09 | 0.851074E+09 | 0.803169E+09 | 0.230550E+09 | 0.572619E+09 | 0.00 | 0.00 |
April | 0.112550E+10 | 0.531355E+09 | 0.107942E+10 | 0.432851E+09 | 0.646569E+09 | 0.00 | 0.00 |
May | 0.140837E+10 | 0.314165E+09 | 0.118247E+10 | 0.372190E+09 | 0.810281E+09 | 0.00 | 0.00 |
June | 0.169104E+10 | 0.270246E+09 | 0.133921E+10 | 0.471994E+09 | 0.867218E+09 | 0.00 | 0.00 |
July | 0.183852E+10 | 0.296507E+09 | 0.144433E+10 | 0.562347E+09 | 0.881979E+09 | 0.00 | 0.00 |
August | 0.159509E+10 | 0.350533E+09 | 0.124937E+10 | 0.459882E+09 | 0.789492E+09 | 0.00 | 0.00 |
September | 0.112370E+10 | 0.507946E+09 | 0.969575E+09 | 0.370148E+09 | 0.599427E+09 | 0.00 | 0.00 |
October | 0.683141E+09 | 0.628996E+09 | 0.709632E+09 | 0.251634E+09 | 0.457997E+09 | 0.00 | 0.00 |
November | 0.244419E+09 | 0.102095E+10 | 0.425030E+09 | 0.121379E+09 | 0.303652E+09 | 0.00 | 0.00 |
December | 0.128809E+09 | 0.163264E+10 | 0.326659E+09 | 0.124040E+09 | 0.202619E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108794E+11 | 0.952425E+10 | 0.105568E+11 | 0.376911E+10 | 0.678766E+10 | 0.00 | 0.00 |
Minimum of Months | 0.128809E+09 | 0.270246E+09 | 0.326659E+09 | 0.121379E+09 | 0.202619E+09 | 0.00 | 0.00 |
Maximum of Months | 0.183852E+10 | 0.184053E+10 | 0.144433E+10 | 0.562347E+09 | 0.881979E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.319543E+10 | 0.192156E+11 | 0.939665E+09 | 0.405708E+09 | 0.533957E+09 | 0.00 | 0.00 |
February | 0.516246E+10 | 0.131062E+11 | 0.116617E+10 | 0.580860E+09 | 0.585312E+09 | 0.00 | 0.00 |
March | 0.107706E+11 | 0.726737E+10 | 0.203786E+10 | 0.975674E+09 | 0.106219E+10 | 0.00 | 0.00 |
April | 0.137139E+11 | 0.350759E+10 | 0.268014E+10 | 0.161239E+10 | 0.106775E+10 | 0.00 | 0.00 |
May | 0.173233E+11 | 0.170763E+10 | 0.332776E+10 | 0.187250E+10 | 0.145526E+10 | 0.00 | 0.00 |
June | 0.186471E+11 | 0.170651E+10 | 0.366161E+10 | 0.214410E+10 | 0.151751E+10 | 0.00 | 0.00 |
July | 0.182740E+11 | 0.228273E+10 | 0.381296E+10 | 0.234830E+10 | 0.146465E+10 | 0.00 | 0.00 |
August | 0.150293E+11 | 0.237905E+10 | 0.317469E+10 | 0.180993E+10 | 0.136476E+10 | 0.00 | 0.00 |
September | 0.111648E+11 | 0.311736E+10 | 0.238604E+10 | 0.138603E+10 | 0.100001E+10 | 0.00 | 0.00 |
October | 0.741948E+10 | 0.380894E+10 | 0.156236E+10 | 0.773194E+09 | 0.789166E+09 | 0.00 | 0.00 |
November | 0.382289E+10 | 0.821446E+10 | 0.899606E+09 | 0.330533E+09 | 0.569073E+09 | 0.00 | 0.00 |
December | 0.199189E+10 | 0.146833E+11 | 0.635808E+09 | 0.309203E+09 | 0.326605E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126515E+12 | 0.809966E+11 | 0.262847E+11 | 0.145484E+11 | 0.117363E+11 | 0.00 | 0.00 |
Minimum of Months | 0.199189E+10 | 0.170651E+10 | 0.635808E+09 | 0.309203E+09 | 0.326605E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186471E+11 | 0.192156E+11 | 0.381296E+10 | 0.234830E+10 | 0.151751E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.108441E+10 | -994288741.8 | 0.00 | 0.00 | 744.00 | 0.00 | -90124436.2 | 59.95 | 0.00 | 0.00 |
February | 0.101269E+10 | -931397118.5 | 0.00 | 0.00 | 672.00 | 0.00 | -81287894.1 | 59.95 | 0.00 | 0.00 |
March | 0.116712E+10 | -0.107787E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -89242893.9 | 59.95 | 0.00 | 0.00 |
April | 0.104811E+10 | -963505973.6 | 0.00 | 0.00 | 720.00 | 0.00 | -84602463.8 | 59.95 | 0.00 | 0.00 |
May | 0.102677E+10 | -944010777.7 | 0.00 | 0.00 | 744.00 | 0.00 | -82761217.9 | 59.95 | 0.00 | 0.00 |
June | 0.952718E+09 | -878259291.0 | 0.00 | 0.00 | 720.00 | 0.00 | -74458956.5 | 59.95 | 0.00 | 0.00 |
July | 0.875944E+09 | -801847006.8 | 0.00 | 0.00 | 744.00 | 0.00 | -74096677.5 | 59.95 | 0.00 | 0.00 |
August | 0.913661E+09 | -838910035.3 | 0.00 | 0.00 | 744.00 | 0.00 | -74751024.4 | 59.95 | 0.00 | 0.00 |
September | 0.865711E+09 | -790319338.8 | 0.00 | 0.00 | 720.00 | 0.00 | -75391551.0 | 59.95 | 0.00 | 0.00 |
October | 0.918751E+09 | -831284914.5 | 0.00 | 0.00 | 744.00 | 0.00 | -87466570.8 | 59.95 | 0.00 | 0.00 |
November | 0.938739E+09 | -852415963.7 | 0.00 | 0.00 | 720.00 | 0.00 | -86322699.5 | 59.95 | 0.00 | 0.00 |
December | 0.103640E+10 | -946293767.7 | 0.00 | 0.00 | 744.00 | 0.00 | -90110495.7 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.118410E+11 | -0.108504E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -990616881.4 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.865711E+09 | -0.107787E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -90124436.2 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.116712E+10 | -790319338.8 | 0.00 | 0.00 | 744.00 | 0.00 | -74096677.5 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.94 | 0.88 | 01-JAN-10:09 | 122.09 | 9.12 | 0.00 | 30.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.93 | 0.88 | 03-FEB-10:30 | 131.14 | 9.24 | 0.00 | 60.17 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.91 | 0.88 | 01-MAR-08:39 | 215.13 | 11.77 | 0.00 | 164.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.90 | 0.88 | 02-APR-14:39 | 239.89 | 11.77 | 0.00 | 190.33 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.90 | 0.88 | 01-MAY-07:10 | 798.49 | 12.54 | 0.00 | 265.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.90 | 0.88 | 01-JUN-06:49 | 1989.55 | 12.88 | 0.00 | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.90 | 0.88 | 01-JUL-07:10 | 1832.96 | 13.59 | 20.00 | 278.17 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.90 | 0.88 | 01-AUG-07:49 | 1103.05 | 12.99 | 14.67 | 260.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.91 | 0.88 | 01-SEP-07:19 | 212.64 | 11.67 | 0.00 | 161.83 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.92 | 0.88 | 01-OCT-09:20 | 162.73 | 10.29 | 0.00 | 93.33 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.93 | 0.88 | 01-NOV-09:30 | 139.43 | 9.76 | 0.00 | 51.67 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.96 | 0.88 | 04-DEC-12:20 | 79.37 | 6.96 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.91 | 714.50 | 11.50 | 34.67 | 1839.17 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 186.17 | 0.90 | 0.88 | 79.37 | 6.96 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 428.67 | 0.96 | 0.88 | 1989.55 | 13.59 | 20.00 | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.78 | 0.63 | 24-JAN-14:39 | 350.33 | 24.13 | 122.83 | 34.33 | 126.38 | 21.25 | 110.50 | 0.00 |
February | 226.83 | 0.76 | 0.61 | 06-FEB-14:30 | 641.58 | 25.03 | 142.67 | 58.00 | 147.61 | 21.49 | 139.83 | 2.00 |
March | 334.33 | 0.74 | 0.61 | 03-MAR-16:10 | 401.37 | 23.69 | 205.50 | 98.50 | 293.87 | 24.05 | 224.33 | 41.00 |
April | 285.17 | 0.71 | 0.61 | 03-APR-13:30 | 473.67 | 23.12 | 171.00 | 114.83 | 463.95 | 24.00 | 229.17 | 80.17 |
May | 428.67 | 0.72 | 0.61 | 01-MAY-13:30 | 325.85 | 21.74 | 237.83 | 130.00 | 308.65 | 22.83 | 301.00 | 75.33 |
June | 400.67 | 0.69 | 0.61 | 01-JUN-16:19 | 382.08 | 22.24 | 259.67 | 187.33 | 463.71 | 23.52 | 316.17 | 100.33 |
July | 414.00 | 0.69 | 0.61 | 01-JUL-13:20 | 387.87 | 22.51 | 260.17 | 186.17 | 513.73 | 23.74 | 331.83 | 125.33 |
August | 410.83 | 0.71 | 0.61 | 01-AUG-14:20 | 387.46 | 22.32 | 247.17 | 156.33 | 402.81 | 23.31 | 295.83 | 102.67 |
September | 326.50 | 0.72 | 0.61 | 01-SEP-14:09 | 554.51 | 24.79 | 204.67 | 113.00 | 473.74 | 25.31 | 255.00 | 73.17 |
October | 325.17 | 0.76 | 0.61 | 01-OCT-14:30 | 444.95 | 24.48 | 194.83 | 74.50 | 183.85 | 23.39 | 203.00 | 20.83 |
November | 254.83 | 0.81 | 0.61 | 03-NOV-15:09 | 259.83 | 22.63 | 128.17 | 22.33 | 115.02 | 20.88 | 114.50 | 0.00 |
December | 186.17 | 0.83 | 0.65 | 02-DEC-14:30 | 217.00 | 22.25 | 71.33 | 13.83 | 92.09 | 19.59 | 38.67 | 0.00 |
Annual Sum or Average | 3807.33 | 0.73 | 403.09 | 23.12 | 2245.83 | 1189.17 | 327.86 | 23.05 | 2559.83 | 620.83 | ||
Minimum of Months | 186.17 | 0.69 | 0.61 | 217.00 | 21.74 | 71.33 | 13.83 | 92.09 | 19.59 | 38.67 | 0.00 | |
Maximum of Months | 428.67 | 0.83 | 0.65 | 641.58 | 25.03 | 260.17 | 187.33 | 513.73 | 25.31 | 331.83 | 125.33 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133151E+11 | 26140.61 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.996756E+10 | 26140.61 | 01-FEB-03:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.773212E+10 | 26140.61 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.400417E+10 | 26140.61 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.726661E+09 | 26140.61 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 56230943.49 | 26140.61 | 05-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.261446E+09 | 26140.61 | 27-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.257090E+10 | 26140.61 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.611847E+10 | 26140.61 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103131E+11 | 26140.61 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133151E+11 | 26140.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.490923E+11 | 66115.37 | 02-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350511E+11 | 66115.37 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216751E+11 | 66115.37 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.808081E+10 | 66115.37 | 02-APR-20:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.461516E+09 | 40516.12 | 01-MAY-05:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66590449.39 | 26703.92 | 30-SEP-05:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342461E+10 | 59340.52 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201372E+11 | 66115.37 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388950E+11 | 66115.37 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.490923E+11 | 66115.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.240386E+12 | 217850.80 | 18-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162457E+12 | 210915.14 | 01-FEB-20:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.870226E+11 | 148939.06 | 06-MAR-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191586E+11 | 88896.88 | 02-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.272474E+09 | 13716.83 | 02-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189978E+10 | 17927.75 | 24-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.905583E+11 | 145904.24 | 26-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184820E+12 | 217850.80 | 08-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.786575E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.240386E+12 | 217850.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.161059E+09 | 0.113419E+09 | 5775.91 | 18-APR-15:10 | 4181.57 | 0.00 |
May | 0.00 | 0.00 | 0.364999E+09 | 0.280303E+09 | 6491.55 | 31-MAY-15:10 | 5459.26 | 0.00 |
June | 0.00 | 0.00 | 0.367046E+10 | 0.273155E+10 | 21185.71 | 26-JUN-05:45 | 10103.29 | 0.00 |
July | 0.00 | 0.00 | 0.605389E+10 | 0.426625E+10 | 20824.26 | 27-JUL-05:02 | 9099.63 | 0.00 |
August | 0.00 | 0.00 | 0.611975E+10 | 0.434044E+10 | 22843.58 | 04-AUG-05:01 | 8602.38 | 0.00 |
September | 0.00 | 0.00 | 0.227914E+10 | 0.199600E+10 | 19436.86 | 11-SEP-05:02 | 11925.17 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186493E+11 | 0.137280E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.611975E+10 | 0.434044E+10 | 22843.58 | 11925.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.257574E+10 | 0.166947E+10 | 44368.64 | 30-JUN-18:42 | 30097.80 | 0.00 |
July | 0.00 | 0.00 | 0.497226E+10 | 0.301852E+10 | 49535.51 | 03-JUL-20:05 | 23280.66 | 0.00 |
August | 0.00 | 0.00 | 0.385532E+10 | 0.231927E+10 | 50304.19 | 03-AUG-18:55 | 22959.12 | 0.00 |
September | 0.00 | 0.00 | 0.124742E+10 | 0.974925E+09 | 17502.85 | 10-SEP-14:35 | 13278.32 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126507E+11 | 0.798219E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.497226E+10 | 0.301852E+10 | 50304.19 | 30097.80 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138637E+10 | 0.08 | 518.42 | 01-JAN-00:03 | 0.08 |
February | 0.122276E+10 | 0.08 | 518.42 | 01-FEB-00:02 | 0.08 |
March | 0.104167E+10 | 0.06 | 518.42 | 01-MAR-00:02 | 0.08 |
April | 0.396543E+09 | 0.02 | 518.42 | 01-APR-00:05 | 0.08 |
May | 16952480.11 | 0.00 | 518.42 | 01-MAY-22:00 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.104950E+09 | 0.01 | 518.42 | 16-OCT-22:30 | 0.08 |
November | 0.879507E+09 | 0.05 | 518.42 | 10-NOV-00:50 | 0.08 |
December | 0.138046E+10 | 0.08 | 518.42 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.642921E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138637E+10 | 0.08 | 518.42 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117661E+10 | 0.71 | 1040.94 | 03-JAN-15:50 | 0.96 |
February | 0.104789E+10 | 0.63 | 1040.94 | 01-FEB-13:30 | 0.96 |
March | 0.117933E+10 | 0.53 | 1040.94 | 01-MAR-09:40 | 0.96 |
April | 0.106378E+10 | 0.42 | 1040.94 | 01-APR-08:40 | 0.95 |
May | 0.108315E+10 | 0.38 | 1040.94 | 01-MAY-15:00 | 0.95 |
June | 0.108022E+10 | 0.38 | 1040.94 | 06-JUN-06:40 | 0.94 |
July | 0.105063E+10 | 0.36 | 1040.94 | 01-JUL-07:20 | 0.94 |
August | 0.113052E+10 | 0.39 | 1040.94 | 01-AUG-07:40 | 0.93 |
September | 0.103936E+10 | 0.37 | 1040.94 | 01-SEP-11:40 | 0.95 |
October | 0.105387E+10 | 0.38 | 1040.94 | 02-OCT-07:50 | 0.95 |
November | 0.104824E+10 | 0.48 | 1040.94 | 01-NOV-08:20 | 0.95 |
December | 0.112859E+10 | 0.59 | 1040.94 | 01-DEC-09:10 | 0.95 |
Annual Sum or Average | 0.130822E+11 | 0.47 | |||
Minimum of Months | 0.103936E+10 | 0.36 | 1040.94 | 0.93 | |
Maximum of Months | 0.117933E+10 | 0.71 | 1040.94 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173377E+10 | 0.67 | 1731.30 | 02-JAN-04:03 | 0.92 |
February | 0.138661E+10 | 0.64 | 1731.30 | 01-FEB-00:02 | 0.93 |
March | 0.121737E+10 | 0.55 | 1731.30 | 01-MAR-00:02 | 0.93 |
April | 0.869251E+09 | 0.40 | 1731.30 | 02-APR-20:23 | 0.92 |
May | 0.724319E+09 | 0.23 | 1060.96 | 01-MAY-05:37 | 0.92 |
June | 0.721304E+09 | 0.22 | 1554.31 | 26-JUN-17:20 | 0.87 |
July | 0.710920E+09 | 0.22 | 1731.30 | 03-JUL-17:10 | 0.91 |
August | 0.746971E+09 | 0.22 | 1731.30 | 02-AUG-17:15 | 0.91 |
September | 0.687294E+09 | 0.21 | 788.04 | 30-SEP-07:10 | 0.61 |
October | 0.767572E+09 | 0.33 | 1553.89 | 24-OCT-05:01 | 0.92 |
November | 0.110410E+10 | 0.51 | 1731.30 | 13-NOV-06:01 | 0.92 |
December | 0.152205E+10 | 0.63 | 1731.30 | 01-DEC-06:01 | 0.92 |
Annual Sum or Average | 0.121915E+11 | 0.40 | |||
Minimum of Months | 0.687294E+09 | 0.21 | 788.04 | 0.61 | |
Maximum of Months | 0.173377E+10 | 0.67 | 1731.30 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.117661E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.104789E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.117933E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.110181E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.116844E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.189091E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.235510E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.246446E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.155602E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.105387E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.104824E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.112859E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.171713E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104789E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.246446E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.173377E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.138661E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.121737E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.869251E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.724319E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.134563E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.188184E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.166912E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.100934E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.767572E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.110410E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.152205E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152310E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.724319E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.188184E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117661E+10 | 0.00 | 0.133151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104789E+10 | 0.00 | 0.996756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117933E+10 | 0.00 | 0.773212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106378E+10 | 0.161059E+09 | 0.400417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108315E+10 | 0.364999E+09 | 0.726661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108022E+10 | 0.367046E+10 | 56230943.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105063E+10 | 0.605389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113052E+10 | 0.611975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103936E+10 | 0.227914E+10 | 0.261446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105387E+10 | 0.00 | 0.257090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104824E+10 | 0.00 | 0.611847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112859E+10 | 0.00 | 0.103131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130822E+11 | 0.186493E+11 | 0.550658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117933E+10 | 0.611975E+10 | 0.133151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173377E+10 | 0.00 | 0.490923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138661E+10 | 0.00 | 0.350511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121737E+10 | 0.00 | 0.216751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.869251E+09 | 0.00 | 0.808081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.724319E+09 | 0.00 | 0.461516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.721304E+09 | 0.256446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.710920E+09 | 0.484881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746971E+09 | 0.382817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.687294E+09 | 0.124742E+10 | 66590449.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.767572E+09 | 0.00 | 0.342461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110410E+10 | 0.00 | 0.201372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152205E+10 | 0.00 | 0.388950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121915E+11 | 0.124888E+11 | 0.176884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.687294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173377E+10 | 0.484881E+10 | 0.490923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106378E+10 | 0.00 | 0.00 | 0.00 | 38035747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108315E+10 | 0.00 | 0.00 | 0.00 | 85286353.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108022E+10 | 0.00 | 0.00 | 0.00 | 0.810695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105063E+10 | 0.00 | 0.00 | 0.00 | 0.130447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113052E+10 | 0.00 | 0.00 | 0.00 | 0.133394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103936E+10 | 0.00 | 0.00 | 0.00 | 0.516659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130822E+11 | 0.00 | 0.00 | 0.00 | 0.408909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117933E+10 | 0.00 | 0.00 | 0.00 | 0.133394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.173377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.869251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.724319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.721304E+09 | 0.00 | 0.00 | 0.00 | 0.624324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.710920E+09 | 0.00 | 0.00 | 0.00 | 0.117092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746971E+09 | 0.00 | 0.00 | 0.00 | 0.922153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.687294E+09 | 0.00 | 0.00 | 0.00 | 0.322047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.767572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121915E+11 | 0.00 | 0.00 | 0.00 | 0.303945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.687294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173377E+10 | 0.00 | 0.00 | 0.00 | 0.117092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383549E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299266E+10 | 0.00 | 0.00 | 0.13 |
March | 13005931.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244577E+10 | 0.00 | 0.00 | 0.13 |
April | 0.223322E+09 | 21882991.92 | 0.00 | 15613.89 | 12127715.09 | 0.144276E+10 | 34234509.35 | 0.00 | 0.13 |
May | 0.708035E+09 | 29230474.56 | 0.00 | 126538.18 | 364391.08 | 0.158637E+09 | 0.231421E+09 | 0.00 | 0.19 |
June | 0.215662E+09 | 0.462445E+09 | 0.00 | 2326771.61 | 533282.36 | 8056261.64 | 0.117361E+10 | 0.00 | 0.47 |
July | 4175652.18 | 0.678877E+09 | 0.00 | 3857533.26 | 0.00 | 0.00 | 0.107282E+10 | 0.00 | 0.55 |
August | 7878832.66 | 0.738099E+09 | 0.00 | 3467547.93 | 0.00 | 0.00 | 0.126144E+10 | 0.00 | 0.62 |
September | 0.350518E+09 | 0.128170E+09 | 0.00 | 2371187.70 | 0.00 | 0.104372E+09 | 0.135094E+10 | 0.00 | 0.38 |
October | 0.288492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119493E+10 | 0.00 | 0.00 | 0.12 |
November | 0.100536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209249E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321127E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.191163E+10 | 0.205870E+10 | 0.00 | 12165192.58 | 13025388.53 | 0.174864E+11 | 0.512446E+10 | 0.00 | 0.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.708035E+09 | 0.738099E+09 | 0.00 | 3857533.26 | 12127715.09 | 0.383549E+10 | 0.135094E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126320E+11 | 0.00 | 0.00 | 0.17 |
February | 0.747410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886318E+10 | 0.00 | 0.00 | 0.18 |
March | 0.226447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477139E+10 | 0.00 | 0.00 | 0.19 |
April | 0.319262E+10 | 0.00 | 0.00 | 0.00 | 0.137667E+09 | 0.134152E+10 | 0.00 | 0.00 | 0.18 |
May | 0.238629E+10 | 0.00 | 0.00 | 0.00 | 45824482.23 | 20171087.25 | 0.00 | 0.00 | 0.18 |
June | 0.228831E+10 | 0.398491E+09 | 0.00 | 294515.21 | 12857899.14 | 0.00 | 0.194327E+09 | 0.00 | 0.21 |
July | 0.121416E+10 | 0.709396E+09 | 0.00 | 2070756.88 | 0.00 | 0.00 | 0.113957E+10 | 0.00 | 0.25 |
August | 0.142199E+10 | 0.684278E+09 | 0.00 | 1810177.90 | 1610293.08 | 0.00 | 0.109882E+10 | 0.00 | 0.25 |
September | 0.294245E+10 | 0.110441E+09 | 0.00 | 600832.06 | 89086.86 | 0.00 | 0.333296E+09 | 0.00 | 0.20 |
October | 0.341154E+10 | 0.00 | 0.00 | 0.00 | 7003468.13 | 0.211103E+09 | 0.00 | 0.00 | 0.17 |
November | 0.173607E+10 | 0.00 | 6184.11 | 0.00 | 49394.98 | 0.461578E+10 | 0.00 | 633.70 | 0.17 |
December | 0.405396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987908E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.222529E+11 | 0.190261E+10 | 6184.11 | 4776282.05 | 0.205102E+09 | 0.423343E+11 | 0.276601E+10 | 633.70 | 0.19 |
Minimum of Months | 0.242174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.341154E+10 | 0.709396E+09 | 6184.11 | 2070756.88 | 0.137667E+09 | 0.126320E+11 | 0.113957E+10 | 633.70 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.359359E+12 | 0.176785E+12 | 0.00 | 0.167097E+11 | 0.626401E+11 |
February | 0.431339E+12 | 0.123217E+12 | 0.00 | 0.126032E+11 | 0.436552E+11 |
March | 0.719622E+12 | 0.844726E+11 | 0.00 | 0.949464E+10 | 0.260554E+11 |
April | 0.886376E+12 | 0.366281E+11 | 0.00 | 0.606279E+10 | 0.822574E+10 |
May | 0.105873E+13 | 0.177080E+11 | 0.00 | 0.342926E+10 | 0.969937E+09 |
June | 0.112283E+13 | 0.218902E+11 | 0.00 | 0.300684E+10 | 0.770474E+10 |
July | 0.115178E+13 | 0.277451E+11 | 0.00 | 0.205892E+10 | 0.135015E+11 |
August | 0.997069E+12 | 0.331346E+11 | 0.00 | 0.239676E+10 | 0.122312E+11 |
September | 0.689010E+12 | 0.374840E+11 | 0.00 | 0.484856E+10 | 0.450101E+10 |
October | 0.478384E+12 | 0.327171E+11 | 0.00 | 0.509905E+10 | 0.276408E+10 |
November | 0.257373E+12 | 0.876139E+11 | 0.00 | 0.854482E+10 | 0.252674E+11 |
December | 0.173423E+12 | 0.139302E+12 | 0.00 | 0.134958E+11 | 0.492432E+11 |
Annual Sum or Average | 0.832530E+13 | 0.818698E+12 | 0.00 | 0.877503E+11 | 0.256759E+12 |
Minimum of Months | 0.173423E+12 | 0.177080E+11 | 0.00 | 0.205892E+10 | 0.969937E+09 |
Maximum of Months | 0.115178E+13 | 0.176785E+12 | 0.00 | 0.167097E+11 | 0.626401E+11 |