Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2024-07-03 12:19:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1083.54 | 224.10 | 224.10 |
Net Site Energy | 973.40 | 201.32 | 201.32 |
Total Source Energy | 1856.02 | 383.86 | 383.86 |
Net Source Energy | 1507.18 | 311.72 | 311.72 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 756.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 99.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 11.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 327.15 | 756.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 756.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 99.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 1.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 11.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 756.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 99.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 31.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 11.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.09 | 156.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 67.66 | 156.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.09 | 156.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 67.66 | 156.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 115.245 | 35.23 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -5.10 | -1.6 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 110.146 | 33.67 |
Electricity Coming From Utility | 232.222 | 70.98 |
Surplus Electricity Going To Utility | 15.216 | 4.65 |
Net Electricity From Utility | 217.006 | 66.33 |
Total On-Site and Utility Electric Sources | 327.152 | 100.00 |
Total Electricity End Uses | 327.152 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 72.00 |
Time Setpoint Not Met During Occupied Cooling | 2.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2979.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.1633 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.1633 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3473 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-14:00 | 05-JAN-17:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 255472.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7689.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7297.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4326.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1233.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30581.30 | 255472.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 255472.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7689.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 7297.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2020.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1233.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 819.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 101.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1036.09 | 819.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 169.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 65.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 214.28 | 169.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 169.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 65.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 214.28 | 169.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.03 |
ZONE2 FINE STORAGE DIRECT AIR | 1.81 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 4.29 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 4.29 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 153387.81 |
PSZ-OFFICE HEATING COIL | 25920.51 |
PSZ-FINE STORAGE HEATING COIL | 66298.55 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 153387.82 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-FINE STORAGE | 1.81 | 1.81 | 1.81 | 1.81 | 1.81 | 1.81 | 1.00 | 1.00 | 1.81 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.03 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.81 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.03 | 1140.38 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.81 | 1940.20 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 17050.20 | 25920.51 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.81 | 1.81 | 1.81 | 1.20 | 35879.74 | 66298.55 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.03 | 0.515001 | 0.686667 | 17050.20 | 8525.10 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 1.81 | 0.906595 | 1.21 | 35879.74 | 17939.87 | 0.780560 | 0.780560 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.163 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.237 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1459.960 | 6.163 | 114.518 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1459.960 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3574 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3330 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6144 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.946 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1333 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5514E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6144 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.798 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.904 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.528 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3395 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.423 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.06 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.528 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
2 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
3 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
4 | 2 | 0.92894805E-09 | 0.33911764E-13 | 0.21779261E-14 | 0.0000000 |
5 | 1 | -5.2160150 | 0.41827095E-04 | -0.44821328E-04 | 0.18401191E-09 |
6 | 0 | 5.5734381 | 0.35738136 | 0.35746801 | |
7 | 4 | 0.81205461E-12 | -0.60820818E-16 | 0.53959138E-14 | 0.11194769E-15 |
8 | 3 | -0.39487908E-03 | 0.23668407E-06 | -0.57379545E-04 | 0.15580508E-12 |
9 | 2 | 1.7634853 | 0.51193665E-02 | 1.1586669 | -0.75705256E-04 |
10 | 1 | -7.0973464 | 0.13173731 | -17.214220 | 0.33800211 |
11 | 0 | 5.5547270 | 0.83614094E-01 | 16.276082 | |
12 | 4 | 0.75524091E-12 | 0.18585927E-15 | -0.24619336E-14 | 0.12165746E-15 |
13 | 3 | -0.37591709E-03 | 0.42679598E-06 | -0.54444663E-04 | 0.14493025E-12 |
14 | 2 | 1.7186597 | 0.94202666E-02 | 1.1245767 | -0.72068922E-04 |
15 | 1 | -7.1564116 | 0.24550773 | -16.996678 | 0.32938266 |
16 | 0 | 5.8501984 | 0.15714209 | 16.284226 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.9455516 | 2.9455516 | 2.9455516 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.31875017E-08 | -0.23223167E-14 | 0.11745088E-14 | -0.42051331E-16 |
55 | 6 | 0.38616340E-05 | 0.25494915E-08 | 0.31950331E-02 | -0.26802615E-04 |
56 | 5 | -0.27022284E-03 | 0.15072689E-05 | -0.22401801 | 0.19587403E-02 |
57 | 4 | 0.61670379E-02 | 0.68550054E-04 | 4.8344327 | -0.45311958E-01 |
58 | 3 | -0.54002887E-01 | 0.54467183E-03 | -38.049021 | 0.39895888 |
59 | 2 | 0.19154071 | 0.90547994E-03 | 116.53767 | -1.4186579 |
60 | 1 | -0.27632409 | 0.27557907E-03 | -143.93893 | 2.0495597 |
61 | 0 | 0.13468807 | 0.66882102E-05 | 60.838472 | |
62 | 7 | -0.77687407E-08 | 0.22327722E-15 | -0.37072247E-14 | 0.17899991E-16 |
63 | 6 | 0.20649052E-05 | 0.10720148E-08 | 0.32011002E-02 | -0.26853511E-04 |
64 | 5 | -0.12245401E-03 | 0.62775152E-06 | -0.22436262 | 0.19617821E-02 |
65 | 4 | 0.26426329E-02 | 0.28408139E-04 | 4.8401680 | -0.45367094E-01 |
66 | 3 | -0.22645990E-01 | 0.22478354E-03 | -38.081398 | 0.39931679 |
67 | 2 | 0.79613263E-01 | 0.37221057E-03 | 116.60066 | -1.4195005 |
68 | 1 | -0.11438919 | 0.11271005E-03 | -143.97600 | 2.0501690 |
69 | 0 | 0.55641142E-01 | 0.27215667E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.24619336E-14 | 0.18585927E-15 | 0.75524091E-12 | 0.12165746E-15 |
85 | 3 | -0.54444663E-04 | 0.42679598E-06 | -0.37591709E-03 | 0.14493025E-12 |
86 | 2 | 1.1245767 | 0.94202666E-02 | 1.7186597 | -0.72068922E-04 |
87 | 1 | -16.996678 | 0.24550773 | -7.1564116 | 0.32938266 |
88 | 0 | 16.284226 | 0.15714209 | 5.8501984 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | 34 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
5 | SKYLIGHT_U_0.47_SHGC_0.4 | 38 | 1 | VerySmooth | 2.672 | 2.672 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.555 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.40629E-002 | 0.31435 | 0.46917 | 0.46917 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11822 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.553 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 3.833E-002 | 1.618E-004 | 2.498E-004 | 0.137 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.195 | 1.399E-004 | 8.913E-005 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 1.834 | 5.723E-004 | 3.738E-004 | 0.187 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0708E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7629E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6840E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8860E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9378E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4468E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0965E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2813E-004 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5875E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2030E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3375E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7152E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2084E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9389E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1831E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3692E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1207E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4959E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1332E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5222E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3182E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0130E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9940E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9673E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0365E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0146E-003 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5626E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9583E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7907E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2363E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.6814E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.8754E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.0398E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.1236E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.8681E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.8556E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9807E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.2338E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.0205E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.5117E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.4400E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.4446E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.9779E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.2748E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.1742E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.0089E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.7029E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.1163E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.3283E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.2490E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9960E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.4242E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.7385E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1881E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.0655E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.1290E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.5097E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.2558E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.6544E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4169E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.7384E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1881E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9124.53778 | 10949.44534 | 0.85834 | 1.03000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.16000 | 6.30335E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9909.57247 | 11891.48696 | 0.31808 | 0.38170 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60000 | 3.41898E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 20606.37089 | 24727.64507 | 1.51099 | 1.81319 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 28791.57133 | 34549.88560 | 0.77840 | 0.93408 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -27.60000 | 3.41898E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 127823.18364 | 153387.82037 | 3.57084 | 4.28501 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13770.29 | 1.03000 | 1.03000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 12920.29 | 0.38170 | 0.38170 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 31129.92 | 1.81319 | 1.81319 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 43558.81 | 0.93408 | 0.93408 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03000 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.81319 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.28501 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 4.28501 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 153387.81307 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 153387.82037 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03000 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03000 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03000 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03000 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03000 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.03000 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.81319 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.81319 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.81319 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.81319 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.81319 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.81319 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.03000 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.81319 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03000 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03000 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1140.37669 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03000 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03000 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03000 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51500 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68667 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17050.20000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8525.10000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17050.20000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25920.50789 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25920.50789 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.81319 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.81319 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1940.19937 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.81319 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.81319 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.81319 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.19671 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.81319 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90660 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.20879 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35879.74000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17939.87000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78056 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78056 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35879.74000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 66298.55383 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 66298.55383 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 16251.0 | 11.46 | 11.20 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 34471.8 | 11.82 | 11.55 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1714895827 | 0.1661434706 | Pass | Pass | 0.3466446683 | 1.4137026683 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.3423805581 | 0.3234257309 | Pass | Pass | 1.5489704175 | 10.1369875012 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.8940644930E-003 | 8.6512444466E-003 | Pass | Pass | 7.2529886990E-002 | 0.2284512251 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8308.29 | 523.33 | 0.00 | 78.20 | 165.57 | 9075.45 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.131 | 0.133 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.055 | 0.055 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.176 | 0.180 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.563 | 0.614 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.563 | 0.614 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.563 | 0.614 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.341 | 0.357 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.614 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.614 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.943 | 0.380 | 0.418 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.943 | 0.380 | 0.418 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.943 | 0.380 | 0.418 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.943 | 0.380 | 0.418 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.003 | 0.460 | 0.479 | |||||||||||||||||
North Total or Average | 6.51 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.268 | 0.480 | 0.495 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.1633 | 236.88 | 1459.96 | LightsWired | LTG_SCH_OFFICE | 44.65 | 168.00 | 27.99 | 0.0000 | Y | 7.67 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 25.41 | 0.0000 | Y | 44.43 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 24.68 | 0.0000 | Y | 47.47 |
Interior Lighting Total | 4.3473 | 4835.13 | 21019.54 | 99.57 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.12 | 10245.50 | 1188.48 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1459.96 | 423.39 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1459.96 | 146.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 119.03 | AstronomicalClock | - | 42.11 | 42.11 | 0.94 | |
EXTERIOR_LIGHTS_B | 2955.82 | AstronomicalClock | - | 83.57 | 62.84 | 34.87 | |
EXTERIOR_LIGHTS_C | 694.12 | AstronomicalClock | - | 83.57 | 49.89 | 6.50 | |
Exterior Lighting Total | 3768.97 | 42.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17050.20 | 13651.41 | 3398.79 | 0.80 | 3.82 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35879.74 | 28006.29 | 7873.45 | 0.78 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 16251.0 | 11.46 | 11.20 | ||||
PSZ-FINE STORAGE COOLING COIL | 34471.8 | 11.82 | 11.55 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 153387.81 | 0.85 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25920.51 | 0.84 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 66298.55 | 0.85 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 4.29 | 398.12 | 92.91 | 1.00 | 3.21 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1140.38 | 1107.16 | 1.00 | 1.39 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.81 | 1940.20 | 1070.05 | 1.00 | 1.33 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9124.54 | 10949.45 | 46.22 | 0.858 | 1.030 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00829 | 31.16 | 0.00630 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 20606.37 | 24727.65 | 17.75 | 1.511 | 1.813 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 26.70 | 26.70 | 0.00835 | 33.08 | 0.00631 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 33.12 | 0.00639 | 33.24 | 0.00631 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9909.57 | 11891.49 | 50.20 | 0.318 | 0.382 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00804 | -27.60 | 0.00034 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 28791.57 | 34549.89 | 24.80 | 0.778 | 0.934 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00708 | -27.60 | 0.00034 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 127823.18 | 153387.82 | 47.86 | 3.571 | 4.285 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00608 | -27.60 | 0.00034 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.03 | 1.03 | 0.38 | 0.38 | 1.0300 | 1.0300 | 1.0300 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.81 | 1.81 | 0.93 | 0.93 | 1.8132 | 1.8132 | 1.8132 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 153387.813 | 153387.813 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 153387.81 | 153387.81 | 4.285010 | 10.00 | 7.21 | 0.00607822 | 43.33 | 20.56 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 10.00 | 0.00607822 | 69.8448 | 153387.82 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 17050.200 | 13651.413 | 1.030000 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 8525.10 | 8413.12 | 0.686667 | 25.70 | 15.26 | 0.00809050 | 12.00 | 10.08 | 0.00800000 | 31.59 | 0.00630401 | 15.77 | 14.8958 | 23.90 | 0.00828800 | 39.2702 | 9102.15 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25920.508 | 25920.508 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25920.51 | 25920.51 | 1.030003 | 16.22 | 11.07 | 0.00727826 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 9.9305 | 21.10 | 0.00804302 | 45.1929 | 9909.57 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 35879.740 | 28006.290 | 1.813190 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 17939.87 | 17939.87 | 1.208793 | 29.27 | 16.26 | 0.00786623 | 12.00 | 9.95 | 0.00786623 | 33.40 | 0.00630683 | 16.37 | 35.1351 | 26.70 | 0.00834515 | 33.4713 | 20542.90 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 66298.554 | 66298.554 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 66298.55 | 66298.55 | 1.813190 | 5.45 | 4.40 | 0.00550361 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 23.4234 | 15.56 | 0.00708249 | 56.4376 | 28791.57 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 153387.813 | 153387.813 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 4.285010 | 4.51271533 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 153387.81 | 153387.81 | 1.0000 | 4.51271533 | 4.285010 | 10.00 | 7.21 | 0.00607822 | 25359.5 | 43.33 | 20.56 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 153387.81 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 10.00 | 0.00607822 | 10.00 | 0.00607822 | 69.8448 | 153387.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17050.200 | 13651.413 | 1.030000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8798 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.030003 | 1.08473711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 8525.10 | 8413.12 | 1.0000 | 0.72315605 | 0.686667 | 25.70 | 15.26 | 0.00809050 | 46439.7 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8525.10 | 31.59 | 0.00630401 | 15.77 | 0.10228463 | 14.8958 | 23.90 | 0.00828800 | 23.90 | 0.00828800 | 39.2702 | 9102.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25920.508 | 25920.508 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.030003 | 1.08473711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 25920.51 | 25920.51 | 1.0000 | 1.08473711 | 1.030003 | 16.22 | 11.07 | 0.00727826 | 34720.3 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25920.51 | -27.60 | 0.00034190 | -27.60 | 0.10228463 | 9.9305 | 21.05 | 0.00804302 | 21.10 | 0.00804302 | 45.1929 | 9909.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35879.740 | 28006.290 | 1.813190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4629 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.813190 | 1.90954305 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 17939.87 | 17939.87 | 1.0000 | 1.27302847 | 1.208793 | 29.27 | 16.26 | 0.00786623 | 49512.9 | 12.00 | 9.95 | 0.00786623 | 31906.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17939.87 | 33.40 | 0.00630683 | 16.37 | 0.42471127 | 35.1351 | 26.70 | 0.00834515 | 26.70 | 0.00834515 | 33.4713 | 20542.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 66298.554 | 66298.554 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.813190 | 1.90954305 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 66298.55 | 66298.55 | 1.0000 | 1.90954305 | 1.813190 | 5.45 | 4.40 | 0.00550361 | 19294.6 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66298.55 | -27.60 | 0.00034190 | -27.60 | 0.42471127 | 23.4234 | 15.56 | 0.00708249 | 15.56 | 0.00708249 | 56.4376 | 28791.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.03 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.81 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2511.50 | 3031.33 | 2223.50 |
ZONE2 FINE STORAGE | 3128.33 | 3000.83 | 2573.33 |
ZONE3 BULK STORAGE | 3274.00 | 3278.33 | 2974.17 |
Facility | 3335.67 | 3334.50 | 2979.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 98.50 | 2.17 | 62.83 | 2.17 |
ZONE2 FINE STORAGE | 417.83 | 2.33 | 23.83 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 482.33 | 4.50 | 72.00 | 2.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.584 | 0.264 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.453 | 0.146 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.135 | 0.000 | 0.164 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.04 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2112321.98 | 0.00 | 2112321.98 | 1392189.88 | 3504511.86 | 3225648.14 | 5689.86 | 2493.42 | 576.72 | 0.00 |
ZONE2 FINE STORAGE | 4850585.13 | 0.00 | 4850585.13 | 4049041.99 | 8899627.12 | 13393694.68 | 5727.79 | 2889.56 | 142.65 | 2.04 |
ZONE3 BULK STORAGE | 0.00 | 37371430.37 | 37371430.37 | 35103114.49 | 72474544.86 | 30805497.77 | 6758.43 | 86.67 | 1914.90 | 5019.00 |
Total Facility | 6962907.11 | 37371430.37 | 44334337.49 | 40544346.36 | 84878683.85 | 47424840.58 | 7761.94 | 3034.50 | 2458.93 | 5019.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1614 | 0.0000 | 0.1614 | 0.0731 | 0.2345 | 0.1023 | 565.86 | 2493.42 | 576.72 |
ZONE2 FINE STORAGE | 0.3701 | 0.0000 | 0.3701 | 0.1200 | 0.4900 | 0.4247 | 605.83 | 2889.56 | 140.61 |
ZONE3 BULK STORAGE | 0.0000 | 1.5774 | 1.5774 | 1.3361 | 2.9135 | 0.9768 | 2538.28 | 40.33 | 1057.39 |
Total Facility | 0.5314 | 1.5774 | 2.1088 | 1.5292 | 3.6381 | 1.5038 | 2637.94 | 2988.17 | 1599.53 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2342783.93 | 0.00 | 2342783.93 | 3225648.14 | 5688.86 | 0.00 | 3071.14 | 0.00 |
PSZ-FINE STORAGE | 5379844.33 | 0.00 | 5379844.33 | 13393694.68 | 5727.79 | 0.00 | 3032.21 | 2.04 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1790 | 0.0000 | 0.1790 | 0.1023 | 564.86 | 0.00 | 3071.14 |
PSZ-FINE STORAGE | 0.4104 | 0.0000 | 0.4104 | 0.4247 | 605.83 | 0.00 | 3030.17 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2764.08 | 315.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2997.04 | 35.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1861 | 0.4329 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.4897 | 0.7510 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 405 |
Defaulted Fields | 323 |
Fields with Defaults | 1052 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 327.15 | 1217.09 | 25-JUN-13:50 | 30581.30 | 17-JUL-15:00 |
Electricity:Building | 237.10 | 1217.09 | 08-JAN-10:20 | 19941.19 | 07-AUG-09:20 |
Electricity:Zone:ZONE1 OFFICE | 36.84 | 520.87 | 01-JAN-00:10 | 2598.04 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 236.07 | 1217.09 | 08-JAN-10:20 | 18031.58 | 19-JAN-09:10 |
InteriorLights:Electricity | 99.57 | 747.21 | 08-JAN-10:20 | 7996.41 | 19-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.67 | 51.00 | 01-JAN-00:10 | 762.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 99.57 | 747.21 | 08-JAN-10:20 | 7996.41 | 19-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 99.57 | 747.21 | 08-JAN-10:20 | 7996.41 | 19-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.67 | 51.00 | 01-JAN-00:10 | 762.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 99.57 | 747.21 | 08-JAN-10:20 | 7996.41 | 19-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 155.83 | 396.24 | 08-JAN-10:20 | 14017.69 | 04-AUG-15:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 47.47 | 396.24 | 08-JAN-10:20 | 3788.71 | 19-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 47.47 | 396.24 | 08-JAN-10:20 | 3788.71 | 19-JAN-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 31.98 | 0.00 | 01-JAN-12:40 | 4457.31 | 17-JUL-16:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 1.02 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUL-13:20 |
Ventilation (simple):Fans:Electricity | 1.02 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUL-13:20 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 1.02 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-JUL-13:20 |
ElectricityProduced:Facility | 110.15 | -0.00 | 03-JAN-16:30 | 20682.61 | 14-MAY-12:30 |
ElectricityProduced:Plant | 110.15 | -0.00 | 03-JAN-16:30 | 20682.61 | 14-MAY-12:30 |
Photovoltaic:ElectricityProduced | 115.24 | 0.00 | 01-JAN-00:10 | 21533.91 | 14-MAY-12:30 |
PowerConversion:ElectricityProduced | -5.10 | -851.31 | 14-MAY-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 11.70 | 0.00 | 02-JAN-00:10 | 1729.65 | 18-FEB-12:40 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 232.22 | 0.00 | 01-JAN-09:40 | 24759.80 | 06-JAN-08:10 |
ElectricityPurchased:Plant | 232.22 | 0.00 | 01-JAN-09:40 | 24759.80 | 06-JAN-08:10 |
Cogeneration:ElectricityPurchased | 232.22 | 0.00 | 01-JAN-09:40 | 24759.80 | 06-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 232.22 | 0.00 | 01-JAN-09:40 | 24759.80 | 06-JAN-08:10 |
ElectricitySurplusSold:Facility | 15.22 | 0.00 | 01-JAN-00:10 | 19413.11 | 14-MAY-12:30 |
ElectricitySurplusSold:Plant | 15.22 | 0.00 | 01-JAN-00:10 | 19413.11 | 14-MAY-12:30 |
Cogeneration:ElectricitySurplusSold | 15.22 | 0.00 | 01-JAN-00:10 | 19413.11 | 14-MAY-12:30 |
General:Cogeneration:ElectricitySurplusSold | 15.22 | 0.00 | 01-JAN-00:10 | 19413.11 | 14-MAY-12:30 |
ElectricityNet:Facility | 217.01 | -19413.11 | 14-MAY-12:30 | 24759.80 | 06-JAN-08:10 |
ElectricityNet:Plant | 217.01 | -19413.11 | 14-MAY-12:30 | 24759.80 | 06-JAN-08:10 |
Cogeneration:ElectricityNet | 217.01 | -19413.11 | 14-MAY-12:30 | 24759.80 | 06-JAN-08:10 |
General:Cogeneration:ElectricityNet | 217.01 | -19413.11 | 14-MAY-12:30 | 24759.80 | 06-JAN-08:10 |
Electricity:HVAC | 36.05 | 0.00 | 01-JAN-12:40 | 10783.20 | 17-JUL-16:00 |
General:Fans:Electricity | 30.96 | 0.00 | 01-JAN-12:40 | 3057.80 | 10-JAN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5.09 | 0.00 | 01-JAN-00:10 | 8631.18 | 17-JUL-16:00 |
General:Cooling:Electricity | 5.09 | 0.00 | 01-JAN-00:10 | 8631.18 | 17-JUL-16:00 |
ExteriorLights:Electricity | 42.31 | 0.00 | 01-JAN-08:20 | 3768.97 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.31 | 0.00 | 01-JAN-08:20 | 3768.97 | 01-JAN-06:10 |
WaterSystems:Electricity | 11.70 | 0.00 | 02-JAN-00:10 | 1729.65 | 18-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 11.70 | 0.00 | 02-JAN-00:10 | 1729.65 | 18-FEB-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 756.39 | 0.00 | 01-JAN-12:40 | 255472.97 | 05-JAN-17:30 |
NaturalGas:HVAC | 756.39 | 0.00 | 01-JAN-12:40 | 255472.97 | 05-JAN-17:30 |
Heating:NaturalGas | 756.39 | 0.00 | 01-JAN-12:40 | 255472.97 | 05-JAN-17:30 |
General:Heating:NaturalGas | 756.39 | 0.00 | 01-JAN-12:40 | 255472.97 | 05-JAN-17:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1263.93 | 0.00 | 01-JAN-12:40 | 407026.94 | 05-JAN-17:30 |
EnergyTransfer:Building | 626.62 | 0.00 | 01-JAN-12:40 | 194459.80 | 05-JAN-17:30 |
EnergyTransfer:Zone:ZONE1 OFFICE | 50.24 | 0.00 | 01-JAN-00:10 | 22775.44 | 09-JAN-07:10 |
Heating:EnergyTransfer | 593.66 | 0.00 | 01-JAN-12:40 | 194459.80 | 05-JAN-17:30 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 38.24 | 0.00 | 01-JAN-00:10 | 22775.44 | 09-JAN-07:10 |
General:Heating:EnergyTransfer | 593.66 | 0.00 | 01-JAN-12:40 | 194459.80 | 05-JAN-17:30 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 38.24 | 0.00 | 01-JAN-00:10 | 22775.44 | 09-JAN-07:10 |
Cooling:EnergyTransfer | 32.95 | 0.00 | 01-JAN-00:10 | 21955.07 | 17-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 12.00 | 0.00 | 01-JAN-00:10 | 10276.43 | 12-AUG-05:50 |
General:Cooling:EnergyTransfer | 32.95 | 0.00 | 01-JAN-00:10 | 21955.07 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 12.00 | 0.00 | 01-JAN-00:10 | 10276.43 | 12-AUG-05:50 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 123.23 | 0.00 | 01-JAN-00:40 | 38899.39 | 29-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 102.27 | 0.00 | 01-JAN-00:40 | 38899.39 | 29-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 102.27 | 0.00 | 01-JAN-00:40 | 38899.39 | 29-JAN-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 20.96 | 0.00 | 01-JAN-00:10 | 13906.92 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 20.96 | 0.00 | 01-JAN-00:10 | 13906.92 | 17-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 453.15 | 0.00 | 01-JAN-12:20 | 154388.45 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 453.15 | 0.00 | 01-JAN-12:20 | 154388.45 | 05-JAN-16:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 453.15 | 0.00 | 01-JAN-12:20 | 154388.45 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 637.31 | 0.00 | 01-JAN-12:40 | 212567.14 | 05-JAN-17:30 |
HeatingCoils:EnergyTransfer | 616.61 | 0.00 | 01-JAN-12:40 | 212567.14 | 05-JAN-17:30 |
CoolingCoils:EnergyTransfer | 20.70 | 0.00 | 01-JAN-00:10 | 30313.14 | 17-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 38.244 | -11.996 | 0.000 | 0.000 | 10.188 | 7.672 | 29.165 | 11.550 | 0.000 | 0.445 | 0.000 | 0.000 | -9.087 | 0.000 | -20.358 | -55.822 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 102.267 | -20.958 | 0.000 | 0.000 | 27.311 | 44.427 | 0.000 | 0.000 | 0.000 | 0.637 | 0.000 | 0.000 | 0.000 | 0.000 | -47.886 | -105.798 |
ZONE3 BULK STORAGE | 453.149 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68.558 | 47.467 | 107.344 | 132.648 | 0.000 | 24.406 | 0.000 | 0.000 | -61.432 | 0.000 | -451.270 | -320.870 |
Total Facility | 453.149 | 0.000 | 140.511 | -32.954 | 0.000 | 0.000 | 106.057 | 99.566 | 136.508 | 144.198 | 0.000 | 25.488 | 0.000 | 0.000 | -70.519 | 0.000 | -519.515 | -482.490 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 12-AUG-05:02 | 0.00 | 0.00 | 0.00 | -23978.14 | 0.00 | 0.00 | 84.48 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 23854.38 | 0.00 | -439.84 | 0.00 | -122.40 | 0.00 |
ZONE2 FINE STORAGE | 08-AUG-17:10 | 0.00 | 0.00 | 0.00 | -31649.08 | 0.00 | 0.00 | 0.00 | 407.49 | 0.00 | 0.00 | 0.00 | 219.20 | 31022.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-AUG-17:10 | 0.00 | 0.00 | 0.00 | -31649.08 | 0.00 | 0.00 | 0.00 | 930.76 | 2519.91 | 32323.38 | 0.00 | 381.18 | 0.00 | 0.00 | 0.00 | 0.00 | -3679.50 | -826.64 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-JAN-06:12 | 0.00 | 0.00 | 26693.85 | 0.00 | 0.00 | 0.00 | 118.54 | 227.91 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1254.40 | 0.00 | -2071.05 | -24265.37 |
ZONE2 FINE STORAGE | 28-JAN-04:02 | 0.00 | 0.00 | 68785.47 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4989.87 | -64095.57 |
ZONE3 BULK STORAGE | 05-JAN-16:00 | 154380.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8329.32 | 3677.75 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5675.53 | 0.00 | -149049.92 | -19861.84 |
Total Facility | 05-JAN-22:02 | 153801.19 | 0.00 | 92204.31 | 0.00 | 0.00 | 0.00 | 0.00 | 799.21 | 2519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9601.61 | 0.00 | -110093.20 | -129629.81 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0300 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0300 | 0.0993 | 1.0000 | Not calculated | 0.1023 | 0.0993 | ||
PSZ-FINE STORAGE | 1.8132 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.8132 | 0.2342 | 1.0000 | Not calculated | 0.4247 | 0.2342 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0300 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0300 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0993 | ||
PSZ-FINE STORAGE | 1.8132 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.8132 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2342 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0300 | 1.0300 | 1.0300 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8132 | 1.8132 | 1.8132 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0300 | 1.0300 | 1.0300 | 1.0300 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.8132 | 1.8132 | 1.8132 | 1.8132 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0300 | 1.0300 | 1.0300 | No | 0.1023 | 0.2680 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8132 | 1.8132 | 1.8132 | No | 0.4247 | 0.4547 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0300 | 1.0300 | 1.0300 | 1.0300 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.8132 | 1.8132 | 1.8132 | 1.8132 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 72.00 |
Number of hours cooling loads not met | 2.17 |
Number of hours not met | 74.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 756.39 | 255472.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5.09 | 8631.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 99.57 | 7996.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.31 | 3768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 1.02 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 30.96 | 3057.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 11.70 | 1729.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 327.15 |
Natural Gas | 0.00 | 756.39 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1083.54 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 115.24 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 20.59 |
Space Heating | 0.00 |
Space Cooling | 1.05 |
Fans (All) | 6.61 |
Service Water Heating | 2.42 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 67.66 |
Subtotal | 67.66 |
Natural Gas [MJ/m2] | |
Space Heating | 156.44 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 156.44 |
Subtotal | 156.44 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.19 |
Space Heating | 69.81 |
Space Cooling | 0.47 |
Fans (All) | 2.95 |
Service Water Heating | 1.08 |
Receptacle Equipment | 12.60 |
Miscellaneous | 3.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_OFFICE | 2328. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8668.00 | 92.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8722.00 | 38.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8286.17 | 472.83 | 1.00 | 0.00 | 0.00 |
Min | 8286.17 | 38.00 | 0.00 | 0.00 | 0.00 |
Max | 8722.00 | 472.83 | 1.00 | 0.00 | 0.00 |
Average | 8558.72 | 200.94 | 0.33 | 0.00 | 0.00 |
Sum | 25676.17 | 602.83 | 1.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 81951.50 | 767.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 175285.00 | 15862.50 | 45.50 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 175285.00 | 15862.50 | 45.50 | 0.00 | 0.00 |
Average | 96754.50 | 5543.33 | 15.17 | 0.00 | 0.00 |
Sum | 290263.50 | 16630.00 | 45.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8723.33 | 36.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8683.83 | 76.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8524.67 | 235.33 | 0.00 | 0.00 | 0.00 |
Min | 8524.67 | 36.67 | 0.00 | 0.00 | 0.00 |
Max | 8723.33 | 235.33 | 0.00 | 0.00 | 0.00 |
Average | 8643.94 | 116.06 | 0.00 | 0.00 | 0.00 |
Sum | 25931.83 | 348.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 81424.00 | 1295.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 181646.33 | 9546.67 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 181646.33 | 9546.67 | 0.00 | 0.00 | 0.00 |
Average | 98699.11 | 3613.89 | 0.00 | 0.00 | 0.00 |
Sum | 296097.33 | 10841.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:48
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.3 | 0.497072E+09 | 603.25 | 07-JAN-08:09 | -20.3 | -20.9 |
February | 7816.99 | 13.03 | 28-FEB-16:40 | 10.37 | 4.49 | 0.457818E+09 | 654.56 | 27-FEB-16:10 | 10.37 | 4.49 |
March | 9786.97 | 13.10 | 02-MAR-16:00 | 10.60 | 4.73 | 0.536857E+09 | 606.89 | 18-MAR-15:09 | 12.12 | 4.19 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.55 | 0.504864E+09 | 735.63 | 06-APR-15:00 | 22.20 | 11.02 |
May | 0.142029E+09 | 2636.04 | 19-MAY-16:00 | 27.80 | 14.54 | 0.558733E+09 | 768.97 | 31-MAY-12:09 | 21.28 | 9.59 |
June | 0.196619E+10 | 20538.77 | 26-JUN-05:03 | 9.87 | 8.82 | 0.645946E+09 | 768.99 | 22-JUN-09:09 | 9.87 | 8.82 |
July | 0.437001E+10 | 22590.94 | 22-JUL-05:03 | 8.77 | 7.17 | 0.634419E+09 | 769.01 | 19-JUL-07:30 | 8.77 | 7.17 |
August | 0.390529E+10 | 23978.98 | 12-AUG-05:02 | 13.07 | 6.78 | 0.683384E+09 | 768.99 | 01-AUG-13:00 | 13.07 | 6.78 |
September | 0.155379E+10 | 20499.80 | 02-SEP-05:03 | 14.40 | 8.78 | 0.599078E+09 | 769.03 | 07-SEP-13:50 | 20.73 | 18.37 |
October | 57100203.51 | 1250.66 | 18-OCT-16:00 | 24.40 | 11.02 | 0.531436E+09 | 768.97 | 16-OCT-15:09 | 24.40 | 11.02 |
November | 1398504.21 | 214.54 | 09-NOV-15:30 | 8.85 | 3.70 | 0.479078E+09 | 684.52 | 04-NOV-15:09 | 8.85 | 3.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -2.1 | -4.2 | 0.497104E+09 | 603.25 | 09-DEC-08:09 | -4.9 | -5.5 |
Annual Sum or Average | 0.119958E+11 | 0.662579E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.457818E+09 | 603.25 | -20.3 | -20.9 | ||
Maximum of Months | 0.437001E+10 | 23978.98 | 27.80 | 14.54 | 0.683384E+09 | 769.03 | 24.40 | 18.37 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151094E+09 | 2894.48 | 23-JAN-13:40 | 6.87 | 2.58 | 0.650282E+09 | 855.71 | 14-JAN-15:50 | 6.87 | 2.58 |
February | 0.498684E+09 | 4517.55 | 28-FEB-11:00 | 3.90 | 1.11 | 0.612413E+09 | 1106.51 | 27-FEB-15:00 | 3.90 | 1.11 |
March | 0.132651E+10 | 4776.46 | 15-MAR-13:10 | 3.07 | -1.2 | 0.727268E+09 | 1016.86 | 14-MAR-14:09 | 3.07 | -1.2 |
April | 0.138358E+10 | 4866.80 | 29-APR-12:30 | 3.05 | -2.3 | 0.749460E+09 | 1293.56 | 07-APR-14:39 | 3.05 | -2.3 |
May | 0.162274E+10 | 6977.77 | 22-MAY-08:15 | -0.4 | -0.7 | 0.941468E+09 | 1892.67 | 20-MAY-15:00 | -0.4 | -0.7 |
June | 0.175500E+10 | 11889.42 | 30-JUN-17:45 | 29.50 | 14.59 | 0.150993E+10 | 2261.79 | 23-JUN-10:09 | 29.50 | 14.59 |
July | 0.448467E+10 | 31393.39 | 19-JUL-17:10 | 30.77 | 16.46 | 0.177045E+10 | 2246.88 | 17-JUL-15:20 | 30.77 | 16.46 |
August | 0.386920E+10 | 31649.29 | 08-AUG-17:10 | 30.50 | 16.33 | 0.182430E+10 | 2246.84 | 08-AUG-12:09 | 30.50 | 16.33 |
September | 0.241351E+10 | 19485.25 | 04-SEP-15:05 | 32.30 | 16.64 | 0.129358E+10 | 2246.85 | 06-SEP-12:39 | 23.17 | 17.43 |
October | 0.191495E+10 | 7027.55 | 21-OCT-07:05 | -1.1 | -2.0 | 0.857683E+09 | 1544.69 | 18-OCT-15:30 | -1.1 | -2.0 |
November | 0.112682E+10 | 4910.28 | 10-NOV-11:10 | 2.98 | -0.7 | 0.664748E+09 | 1119.04 | 04-NOV-14:50 | 2.98 | -0.7 |
December | 0.410966E+09 | 8441.36 | 13-DEC-13:25 | -5.8 | -7.0 | 0.652797E+09 | 893.08 | 06-DEC-13:50 | -5.8 | -7.0 |
Annual Sum or Average | 0.209577E+11 | 0.122544E+11 | ||||||||
Minimum of Months | 0.151094E+09 | 2894.48 | -5.8 | -7.0 | 0.612413E+09 | 855.71 | -5.8 | -7.0 | ||
Maximum of Months | 0.448467E+10 | 31649.29 | 32.30 | 16.64 | 0.182430E+10 | 2261.79 | 30.77 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.3 | 0.649461E+09 | 991.43 | 14-JAN-15:50 | 10.10 | 4.67 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -12.4 | -13.9 | 0.644402E+09 | 1501.28 | 27-FEB-15:00 | 18.90 | 7.06 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 | -4.1 | 0.808334E+09 | 1365.90 | 14-MAR-14:20 | 14.07 | 6.61 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.55 | 0.101568E+10 | 2077.65 | 07-APR-14:00 | 21.70 | 8.90 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -1.1 | -3.0 | 0.148883E+10 | 3375.97 | 31-MAY-15:00 | 25.00 | 10.32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.36 | 0.311166E+10 | 5778.16 | 29-JUN-15:20 | 31.83 | 14.57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.32 | 0.454134E+10 | 8701.05 | 17-JUL-15:00 | 37.20 | 17.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.96 | 0.457932E+10 | 8064.78 | 05-AUG-15:00 | 35.60 | 17.65 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.59 | 0.268002E+10 | 5976.44 | 02-SEP-15:20 | 34.23 | 16.29 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.94 | 0.143316E+10 | 2670.07 | 02-OCT-15:00 | 15.60 | 7.74 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 | 1.54 | 0.823277E+09 | 1762.09 | 04-NOV-14:39 | 16.87 | 8.04 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -2.1 | -4.2 | 0.667063E+09 | 1118.67 | 06-DEC-13:00 | 11.70 | 5.59 |
Annual Sum or Average | 0.00 | 0.224425E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.9 | 0.644402E+09 | 991.43 | 10.10 | 4.67 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.32 | 0.457932E+10 | 8701.05 | 37.20 | 17.65 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.871270E+10 | 26693.84 | 09-JAN-06:12 | -27.2 |
February | 0.590007E+10 | 26516.00 | 10-FEB-06:12 | -19.8 |
March | 0.550901E+10 | 26656.90 | 06-MAR-06:12 | -17.1 |
April | 0.318296E+10 | 26384.21 | 29-APR-05:12 | -7.6 |
May | 0.211865E+10 | 26397.86 | 01-MAY-05:12 | -0.4 |
June | 0.146780E+09 | 25691.17 | 17-JUN-05:02 | 2.35 |
July | 29747091.15 | 1327.00 | 05-JUL-06:20 | 9.40 |
August | 65678100.29 | 1394.14 | 03-AUG-06:20 | 8.50 |
September | 0.437320E+09 | 26229.65 | 19-SEP-05:01 | 2.20 |
October | 0.164999E+10 | 26407.68 | 10-OCT-05:12 | -6.1 |
November | 0.401057E+10 | 26506.98 | 27-NOV-06:12 | -14.4 |
December | 0.648086E+10 | 26511.64 | 29-DEC-06:12 | -25.2 |
Annual Sum or Average | 0.382443E+11 | |||
Minimum of Months | 29747091.15 | 1327.00 | -27.2 | |
Maximum of Months | 0.871270E+10 | 26693.84 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296430E+11 | 68785.39 | 28-JAN-04:02 | -29.6 |
February | 0.175079E+11 | 68109.38 | 04-FEB-02:42 | -21.7 |
March | 0.136538E+11 | 68087.79 | 05-MAR-00:42 | -22.4 |
April | 0.489373E+10 | 67038.33 | 29-APR-05:01 | -7.7 |
May | 0.238732E+10 | 66904.00 | 08-MAY-05:21 | -2.8 |
June | 0.178429E+09 | 2440.28 | 20-JUN-16:20 | 29.40 |
July | 69724050.08 | 1175.02 | 10-JUL-15:10 | 27.52 |
August | 0.105957E+09 | 2057.45 | 24-AUG-17:00 | 29.40 |
September | 0.207602E+09 | 3402.97 | 20-SEP-06:10 | 3.48 |
October | 0.143283E+10 | 49493.11 | 12-OCT-05:01 | 8.40 |
November | 0.104164E+11 | 67940.96 | 27-NOV-04:42 | -15.6 |
December | 0.217708E+11 | 68711.52 | 31-DEC-08:62 | -27.6 |
Annual Sum or Average | 0.102268E+12 | |||
Minimum of Months | 69724050.08 | 1175.02 | -29.6 | |
Maximum of Months | 0.296430E+11 | 68785.39 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157611E+12 | 154388.45 | 05-JAN-16:00 | -19.4 |
February | 0.835346E+11 | 104017.37 | 04-FEB-03:00 | -21.7 |
March | 0.547610E+11 | 108220.15 | 06-MAR-03:52 | -18.3 |
April | 0.609251E+10 | 48474.61 | 29-APR-04:53 | -7.8 |
May | 0.482163E+10 | 40440.18 | 09-MAY-04:53 | -2.2 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.282621E+09 | 13854.44 | 11-OCT-05:53 | 0.00 |
November | 0.395544E+11 | 92814.53 | 27-NOV-05:00 | -15.6 |
December | 0.106492E+12 | 147062.20 | 31-DEC-03:00 | -24.4 |
Annual Sum or Average | 0.453150E+12 | |||
Minimum of Months | 0.00 | 0.00 | -24.4 | |
Maximum of Months | 0.157611E+12 | 154388.45 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.708567E+09 | 762.98 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.607735E+09 | 742.82 | 02-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.657610E+09 | 757.30 | 17-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.612614E+09 | 738.75 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.609026E+09 | 719.44 | 03-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.594614E+09 | 672.35 | 16-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.594821E+09 | 703.17 | 07-JUL-07:30 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.646057E+09 | 712.76 | 17-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.619100E+09 | 733.64 | 11-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.647467E+09 | 762.98 | 30-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.660562E+09 | 762.98 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.713599E+09 | 762.98 | 01-DEC-16:40 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.767177E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.594614E+09 | 672.35 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.713599E+09 | 762.98 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.368849E+10 | 3463.72 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.337993E+10 | 3463.72 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.391929E+10 | 3463.72 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.366257E+10 | 3463.72 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.380389E+10 | 3463.72 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.377797E+10 | 3463.72 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.368849E+10 | 3463.72 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.391929E+10 | 3463.72 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.366257E+10 | 3463.72 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.368849E+10 | 3463.72 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.354717E+10 | 3463.72 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.368849E+10 | 3463.72 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.444266E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.337993E+10 | 3463.72 | 0.00 | 0.00 | |
Maximum of Months | 0.391929E+10 | 3463.72 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.406762E+10 | 3788.71 | 19-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.368486E+10 | 3748.73 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.413637E+10 | 3743.95 | 16-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.385029E+10 | 3635.68 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.395779E+10 | 3534.49 | 11-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.391219E+10 | 3593.20 | 30-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.385181E+10 | 3540.49 | 03-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.409843E+10 | 3638.72 | 04-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.389536E+10 | 3669.63 | 21-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.400495E+10 | 3757.99 | 28-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.390800E+10 | 3763.03 | 13-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.409975E+10 | 3767.68 | 26-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.474674E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.368486E+10 | 3534.49 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.413637E+10 | 3788.71 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.708567E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357988E+10 |
February | 0.127628E+10 | 0.607735E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255011E+10 |
March | 0.149825E+10 | 0.657610E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236912E+10 |
April | 0.138726E+10 | 0.612614E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 549546.33 | 0.144379E+10 |
May | 0.144276E+10 | 0.609026E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10694997.70 | 0.137771E+10 |
June | 0.144276E+10 | 0.594614E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77169892.62 | 0.768132E+09 |
July | 0.138726E+10 | 0.594821E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183633E+09 | 0.435987E+09 |
August | 0.149825E+10 | 0.646057E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138001E+09 | 0.636195E+09 |
September | 0.138726E+10 | 0.619100E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32448345.02 | 0.102820E+10 |
October | 0.138726E+10 | 0.647467E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2478045.21 | 0.135693E+10 |
November | 0.133177E+10 | 0.660562E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203490E+10 |
December | 0.138726E+10 | 0.713599E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277740E+10 |
Annual Sum or Average | 0.168137E+11 | 0.767177E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444974E+09 | 0.203583E+11 |
Minimum of Months | 0.127628E+10 | 0.594614E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435987E+09 |
Maximum of Months | 0.149825E+10 | 0.713599E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183633E+09 | 0.357988E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849271E+10 |
February | 0.300332E+10 | 0.337993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168172.83 | 0.593057E+10 |
March | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527829E+10 |
April | 0.326447E+10 | 0.366257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20758214.59 | 0.299530E+10 |
May | 0.339505E+10 | 0.380389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75814591.43 | 0.295275E+10 |
June | 0.339505E+10 | 0.377797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71165207.34 | 0.201942E+10 |
July | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181367E+09 | 0.158512E+10 |
August | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162599E+09 | 0.187165E+10 |
September | 0.326447E+10 | 0.366257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91083139.19 | 0.267247E+10 |
October | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34351900.28 | 0.282919E+10 |
November | 0.313390E+10 | 0.354717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462377E+10 |
December | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663497E+10 |
Annual Sum or Average | 0.395654E+11 | 0.444266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637307E+09 | 0.478862E+11 |
Minimum of Months | 0.300332E+10 | 0.337993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158512E+10 |
Maximum of Months | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181367E+09 | 0.849271E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.406762E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535801E+11 |
February | 0.690763E+10 | 0.368486E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457524E+09 | 0.313489E+11 |
March | 0.810895E+10 | 0.413637E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55734167.63 | 0.277729E+11 |
April | 0.750829E+10 | 0.385029E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154359E+10 | 0.139078E+11 |
May | 0.780862E+10 | 0.395779E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219185E+10 | 0.145526E+11 |
June | 0.780862E+10 | 0.391219E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949106E+09 | 0.126226E+11 |
July | 0.750829E+10 | 0.385181E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551522E+09 | 0.131380E+11 |
August | 0.810895E+10 | 0.409843E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326858E+09 | 0.159318E+11 |
September | 0.750829E+10 | 0.389536E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120788E+10 | 0.184816E+11 |
October | 0.750829E+10 | 0.400495E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167740E+10 | 0.150548E+11 |
November | 0.720796E+10 | 0.390800E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100913E+10 | 0.229807E+11 |
December | 0.750829E+10 | 0.409975E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190151E+09 | 0.366596E+11 |
Annual Sum or Average | 0.910005E+11 | 0.474674E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101607E+11 | 0.276032E+12 |
Minimum of Months | 0.690763E+10 | 0.368486E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126226E+11 |
Maximum of Months | 0.810895E+10 | 0.413637E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219185E+10 | 0.535801E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 762.98 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 12218.16 | 27-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 742.82 | 02-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10679.82 | 01-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 757.30 | 17-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 9614.27 | 06-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 738.75 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.78 | 16-APR-14:00 | 5401.04 | 28-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 719.44 | 03-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 936.49 | 19-MAY-16:10 | 6467.67 | 22-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 672.35 | 16-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1576.75 | 29-JUN-16:10 | 4158.12 | 16-JUN-07:00 |
July | 1680.92 | 01-JUL-07:10 | 703.17 | 07-JUL-07:30 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2663.16 | 17-JUL-16:10 | 3155.45 | 05-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 712.76 | 17-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1813.35 | 10-AUG-17:00 | 3631.09 | 17-AUG-16:03 |
September | 1680.92 | 01-SEP-07:10 | 733.64 | 11-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 978.09 | 01-SEP-16:10 | 4408.23 | 19-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 762.98 | 30-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.13 | 15-OCT-14:00 | 6375.97 | 10-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 762.98 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 8438.80 | 27-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 762.98 | 01-DEC-16:40 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 10926.84 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 672.35 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3155.45 | |||||
Maximum of Months | 1680.92 | 762.98 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2663.16 | 12218.16 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3463.72 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15565.98 | 05-JAN-16:10 |
February | 3955.50 | 01-FEB-08:09 | 3463.72 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.47 | 27-FEB-15:00 | 8292.13 | 01-FEB-17:00 |
March | 3955.50 | 01-MAR-08:09 | 3463.72 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 7213.50 | 30-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 3463.72 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.68 | 07-APR-15:10 | 5230.15 | 28-APR-16:00 |
May | 3955.50 | 01-MAY-07:10 | 3463.72 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1739.60 | 19-MAY-16:00 | 9953.76 | 22-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 3463.72 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1805.47 | 29-JUN-15:10 | 4132.13 | 14-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 3463.72 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1935.66 | 25-JUL-15:10 | 3215.13 | 08-JUL-07:00 |
August | 3955.50 | 01-AUG-07:10 | 3463.72 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.19 | 09-AUG-17:00 | 6084.09 | 17-AUG-15:10 |
September | 3955.50 | 01-SEP-07:10 | 3463.72 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1792.53 | 02-SEP-15:10 | 5596.97 | 12-SEP-03:00 |
October | 3955.50 | 02-OCT-07:10 | 3463.72 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1141.97 | 15-OCT-14:00 | 4282.80 | 31-OCT-16:00 |
November | 3955.50 | 01-NOV-07:10 | 3463.72 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 7098.92 | 28-NOV-08:00 |
December | 3955.50 | 01-DEC-08:09 | 3463.72 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8107.28 | 31-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3215.13 | ||||
Maximum of Months | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1935.66 | 15565.98 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3788.71 | 19-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 98405.86 | 05-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 3748.73 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8253.38 | 27-FEB-13:10 | 52284.84 | 01-FEB-15:00 |
March | 9097.65 | 01-MAR-08:09 | 3743.95 | 16-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4475.48 | 14-MAR-12:10 | 42293.74 | 03-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3635.68 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16672.90 | 07-APR-12:10 | 30599.96 | 27-APR-11:00 |
May | 9097.65 | 01-MAY-07:10 | 3534.49 | 11-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21399.14 | 19-MAY-16:00 | 50120.48 | 22-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 3593.20 | 30-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10297.08 | 29-JUN-13:00 | 25940.57 | 14-JUN-08:00 |
July | 9097.65 | 01-JUL-07:10 | 3540.49 | 03-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6760.84 | 13-JUL-16:00 | 21656.30 | 08-JUL-10:00 |
August | 9097.65 | 01-AUG-07:10 | 3638.72 | 04-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6273.54 | 25-AUG-16:00 | 47508.93 | 17-AUG-12:05 |
September | 9097.65 | 01-SEP-07:10 | 3669.63 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10981.10 | 02-SEP-14:00 | 37414.98 | 12-SEP-11:00 |
October | 9097.65 | 02-OCT-07:10 | 3757.99 | 28-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16177.68 | 12-OCT-12:10 | 22716.75 | 03-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 3763.03 | 13-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11146.75 | 17-NOV-14:00 | 39050.74 | 27-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 3767.68 | 26-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8815.96 | 10-DEC-02:00 | 68051.19 | 27-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3534.49 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21656.30 | |||||
Maximum of Months | 9097.65 | 3788.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 21399.14 | 98405.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.74 |
February | 13.03 | 28-FEB-16:40 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.96 |
March | 13.10 | 02-MAR-16:00 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.40 |
April | 0.00 | 01-APR-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.71 |
May | 2636.04 | 19-MAY-16:00 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 389.03 | 0.00 |
June | 20538.77 | 26-JUN-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.10 |
July | 22590.94 | 22-JUL-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23978.98 | 12-AUG-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.40 |
September | 20499.80 | 02-SEP-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.25 |
October | 1250.66 | 18-OCT-16:00 | 1680.92 | 489.01 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 | 0.00 |
November | 214.54 | 09-NOV-15:30 | 1680.92 | 495.59 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.86 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23978.98 | 1680.92 | 495.59 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.03 | 781.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2894.48 | 23-JAN-13:40 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1690.06 |
February | 4517.55 | 28-FEB-11:00 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.52 |
March | 4776.46 | 15-MAR-13:10 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1783.42 |
April | 4866.80 | 29-APR-12:30 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 765.49 |
May | 6977.77 | 22-MAY-08:15 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3334.04 |
June | 11889.42 | 30-JUN-17:45 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.60 | 0.00 |
July | 31393.39 | 19-JUL-17:10 | 0.00 | 1629.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.96 | 0.00 |
August | 31649.29 | 08-AUG-17:10 | 0.00 | 1629.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.20 | 0.00 |
September | 19485.25 | 04-SEP-15:05 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.00 | 0.00 |
October | 7027.55 | 21-OCT-07:05 | 7911.00 | 6112.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2624.24 |
November | 4910.28 | 10-NOV-11:10 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.85 |
December | 8441.36 | 13-DEC-13:25 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2894.48 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31649.29 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.96 | 3334.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1344.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3887.18 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 1792.96 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30241.31 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6222.16 |
April | 0.00 | 01-APR-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7982.45 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 1344.72 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8260.56 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.54 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.03 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4354.00 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4654.23 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10589.68 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9780.76 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1344.72 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23123.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.54 | |
Maximum of Months | 0.00 | 0.00 | 1792.96 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30241.31 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.297282E+11 | 24759.80 | 06-JAN-08:09 | 0.248048E+12 | 255472.97 | 05-JAN-17:30 |
February | 0.261685E+11 | 21957.83 | 09-FEB-15:00 | 0.136490E+12 | 166081.24 | 04-FEB-06:10 |
March | 0.289644E+11 | 21586.71 | 03-MAR-15:00 | 0.949911E+11 | 167498.01 | 06-MAR-03:49 |
April | 0.255853E+11 | 21202.41 | 28-APR-12:50 | 0.194606E+11 | 95337.68 | 29-APR-05:10 |
May | 0.257447E+11 | 21607.05 | 20-MAY-14:50 | 0.117826E+11 | 82261.21 | 08-MAY-05:10 |
June | 0.256182E+11 | 25048.88 | 29-JUN-14:00 | 66232623.20 | 6165.87 | 17-JUN-05:10 |
July | 0.271997E+11 | 30581.30 | 17-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.287752E+11 | 29602.44 | 10-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.259918E+11 | 25978.43 | 02-SEP-14:00 | 0.451401E+09 | 14460.94 | 20-SEP-06:10 |
October | 0.266540E+11 | 23742.63 | 31-OCT-07:10 | 0.456625E+10 | 43153.61 | 11-OCT-05:19 |
November | 0.271757E+11 | 24236.19 | 27-NOV-16:00 | 0.691090E+11 | 149862.26 | 27-NOV-06:10 |
December | 0.295459E+11 | 24691.01 | 29-DEC-08:09 | 0.171425E+12 | 208829.94 | 31-DEC-03:09 |
Annual Sum or Average | 0.327152E+12 | 0.756390E+12 | ||||
Minimum of Months | 0.255853E+11 | 21202.41 | 0.00 | 0.00 | ||
Maximum of Months | 0.297282E+11 | 30581.30 | 0.248048E+12 | 255472.97 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.376268E+10 | 11657.09 | 27-JAN-12:30 | 0.00 | 0.00 |
February | 0.548954E+10 | 12852.55 | 28-FEB-12:30 | 0.00 | 0.00 |
March | 0.920882E+10 | 18466.21 | 16-MAR-12:39 | 0.00 | 0.00 |
April | 0.106352E+11 | 19449.15 | 25-APR-12:30 | 0.00 | 0.00 |
May | 0.135436E+11 | 20682.61 | 14-MAY-12:30 | 0.00 | 0.00 |
June | 0.152233E+11 | 20267.73 | 19-JUN-12:50 | 0.00 | 0.00 |
July | 0.159095E+11 | 19745.87 | 11-JUL-12:30 | 0.00 | 0.00 |
August | 0.134016E+11 | 18973.13 | 03-AUG-12:39 | 0.00 | 0.00 |
September | 0.950239E+10 | 17092.10 | 01-SEP-12:30 | 0.00 | 0.00 |
October | 0.653792E+10 | 14134.23 | 10-OCT-12:09 | 0.00 | 0.00 |
November | 0.399837E+10 | 10067.00 | 03-NOV-12:09 | 0.00 | 0.00 |
December | 0.293305E+10 | 7518.42 | 01-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.110146E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.293305E+10 | 7518.42 | 0.00 | 0.00 | |
Maximum of Months | 0.159095E+11 | 20682.61 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.846467E+10 | 0.495665E+10 | 0.112984E+11 | 0.00 | 0.394405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106443E+10 | 0.00 |
February | 0.767252E+10 | 0.398275E+10 | 0.103734E+11 | 0.00 | 0.314828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991544E+09 | 0.00 |
March | 0.871327E+10 | 0.371741E+10 | 0.121089E+11 | 0.00 | 0.328233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114250E+10 | 0.00 |
April | 0.812548E+10 | 0.290266E+10 | 0.112578E+11 | 0.00 | 0.227076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102867E+10 | 0.00 |
May | 0.837071E+10 | 0.244117E+10 | 0.117000E+11 | 0.00 | 0.217306E+10 | 0.00 | 0.00 | 46538017.60 | 0.00 | 0.00 | 0.00 | 0.101326E+10 | 0.00 |
June | 0.828477E+10 | 0.212292E+10 | 0.116594E+11 | 0.00 | 0.197544E+10 | 0.00 | 0.00 | 0.631092E+09 | 0.00 | 0.00 | 0.00 | 0.944628E+09 | 0.00 |
July | 0.813512E+10 | 0.228348E+10 | 0.112984E+11 | 0.00 | 0.239020E+10 | 0.00 | 0.00 | 0.222006E+10 | 0.00 | 0.00 | 0.00 | 0.872474E+09 | 0.00 |
August | 0.866378E+10 | 0.273311E+10 | 0.121016E+11 | 0.00 | 0.266815E+10 | 0.00 | 0.00 | 0.169510E+10 | 0.00 | 0.00 | 0.00 | 0.913540E+09 | 0.00 |
September | 0.817703E+10 | 0.329177E+10 | 0.112504E+11 | 0.00 | 0.191588E+10 | 0.00 | 0.00 | 0.490518E+09 | 0.00 | 0.00 | 0.00 | 0.866225E+09 | 0.00 |
October | 0.834091E+10 | 0.411994E+10 | 0.113057E+11 | 0.00 | 0.196826E+10 | 0.00 | 0.00 | 5764161.04 | 0.00 | 0.00 | 0.00 | 0.913369E+09 | 0.00 |
November | 0.811572E+10 | 0.461920E+10 | 0.108562E+11 | 0.00 | 0.265445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930168E+09 | 0.00 |
December | 0.850184E+10 | 0.513530E+10 | 0.112984E+11 | 0.00 | 0.358883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102162E+10 | 0.00 |
Annual Sum or Average | 0.995658E+11 | 0.423064E+11 | 0.136508E+12 | 0.00 | 0.319797E+11 | 0.00 | 0.00 | 0.508908E+10 | 0.00 | 0.00 | 0.00 | 0.117024E+11 | 0.00 |
Minimum of Months | 0.767252E+10 | 0.212292E+10 | 0.103734E+11 | 0.00 | 0.191588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866225E+09 | 0.00 |
Maximum of Months | 0.871327E+10 | 0.513530E+10 | 0.121089E+11 | 0.00 | 0.394405E+10 | 0.00 | 0.00 | 0.222006E+10 | 0.00 | 0.00 | 0.00 | 0.114250E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.248048E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.136490E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.949911E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.194606E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.117826E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 66232623.20 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.451401E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.456625E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.691090E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.171425E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.756390E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.248048E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 7996.41 | 19-JAN-09:09 | 3768.97 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3057.80 | 10-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7924.56 | 01-FEB-09:09 | 3768.97 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2904.10 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7920.91 | 16-MAR-08:09 | 3768.97 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2837.60 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7814.64 | 01-APR-08:09 | 3768.97 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2570.99 | 29-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7645.75 | 08-MAY-08:09 | 3768.97 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 2565.05 | 08-MAY-07:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7710.07 | 30-JUN-08:09 | 3421.91 | 01-JUN-20:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 1916.46 | 16-JUN-16:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7684.65 | 07-JUL-08:09 | 3421.91 | 01-JUL-20:30 | 10035.17 | 01-JUL-07:10 | 0.00 | 4457.31 | 17-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7775.83 | 04-AUG-08:09 | 3768.97 | 03-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4261.74 | 10-AUG-15:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7807.76 | 16-SEP-08:09 | 3768.97 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1967.76 | 20-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7940.26 | 28-OCT-08:09 | 3768.97 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2510.86 | 11-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7926.06 | 03-NOV-08:09 | 3768.97 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2767.56 | 27-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7956.94 | 26-DEC-09:09 | 3768.97 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2979.49 | 29-DEC-08:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7645.75 | 3421.91 | 10035.17 | 0.00 | 1916.46 | 0.00 | 0.00 | |||||
Maximum of Months | 7996.41 | 3768.97 | 10035.17 | 0.00 | 4457.31 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1726.15 | 31-JAN-12:09 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 1729.65 | 18-FEB-12:39 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 1728.46 | 01-MAR-12:09 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 1712.36 | 01-APR-11:09 | 0.00 | 01-APR-00:10 |
May | 1074.84 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1613.36 | 01-MAY-11:50 | 0.00 | 01-MAY-00:10 |
June | 4720.67 | 29-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1510.96 | 01-JUN-11:50 | 0.00 | 01-JUN-00:10 |
July | 8631.18 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1416.71 | 01-JUL-11:00 | 0.00 | 01-JUL-00:10 |
August | 6924.68 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1400.89 | 01-AUG-11:20 | 0.00 | 01-AUG-00:10 |
September | 5646.68 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1410.93 | 30-SEP-11:30 | 0.00 | 01-SEP-00:10 |
October | 567.89 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 | 1503.89 | 31-OCT-11:30 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 1604.01 | 30-NOV-12:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1704.93 | 30-DEC-12:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1400.89 | 0.00 | |||
Maximum of Months | 8631.18 | 0.00 | 0.00 | 0.00 | 1729.65 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 24759.80 | 06-JAN-08:09 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 3004.92 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21957.83 | 09-FEB-15:00 | 7700.34 | 10035.17 | 0.00 | 0.00 | 2692.30 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21586.71 | 03-MAR-15:00 | 7422.25 | 10035.17 | 0.00 | 0.00 | 2610.67 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21202.41 | 28-APR-12:50 | 7332.60 | 10035.17 | 0.00 | 0.00 | 2414.57 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21607.05 | 20-MAY-14:50 | 7297.27 | 10035.17 | 0.00 | 0.00 | 1916.46 | 0.00 | 0.00 | 956.36 | 0.00 |
June | 25048.88 | 29-JUN-14:00 | 7297.27 | 10035.17 | 0.00 | 0.00 | 1916.46 | 0.00 | 0.00 | 4505.21 | 0.00 |
July | 30581.30 | 17-JUL-14:00 | 7297.27 | 10035.17 | 0.00 | 0.00 | 4326.15 | 0.00 | 0.00 | 7689.52 | 0.00 |
August | 29602.44 | 10-AUG-14:00 | 7297.27 | 10035.17 | 0.00 | 0.00 | 4233.76 | 0.00 | 0.00 | 6818.99 | 0.00 |
September | 25978.43 | 02-SEP-14:00 | 7420.81 | 10035.17 | 0.00 | 0.00 | 1916.46 | 0.00 | 0.00 | 5378.42 | 0.00 |
October | 23742.63 | 31-OCT-07:10 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 2058.01 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24236.19 | 27-NOV-16:00 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 2682.36 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24691.01 | 29-DEC-08:09 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 2951.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21202.41 | 7180.87 | 10035.17 | 0.00 | 0.00 | 1916.46 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30581.30 | 7700.34 | 10035.17 | 3768.97 | 0.00 | 4326.15 | 0.00 | 0.00 | 7689.52 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 255472.97 | 05-JAN-17:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 166081.24 | 04-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 167498.01 | 06-MAR-03:49 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 95337.68 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 82261.21 | 08-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6165.87 | 17-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 14460.94 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 43153.61 | 11-OCT-05:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 149862.26 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 208829.94 | 31-DEC-03:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 255472.97 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.50 | 16.13 | 8.50 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
February | 10.67 | 18.40 | 8.33 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
March | 13.33 | 18.16 | 9.67 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
April | 8.00 | 19.73 | 7.83 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
May | 6.17 | 19.67 | 5.83 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
June | 0.17 | 20.46 | 0.17 | 20.46 | 0.50 | 22.90 | 0.50 | 23.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.50 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.50 | 24.53 |
September | 1.17 | 20.34 | 1.17 | 20.34 | 0.67 | 21.27 | 0.67 | 21.87 |
October | 4.50 | 20.17 | 4.50 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
November | 9.00 | 19.35 | 8.17 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
December | 15.00 | 17.60 | 8.67 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
Annual Sum or Average | 98.50 | 17.92 | 62.83 | 18.58 | 2.17 | 18.66 | 2.17 | 18.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 0.00 | 16.81 |
Maximum of Months | 30.50 | 20.46 | 9.67 | 20.46 | 0.67 | 24.53 | 0.67 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.17 | 14.41 | 4.17 | 14.41 | 0.00 | 14.41 | 0.00 | 14.41 |
February | 79.83 | 14.64 | 4.00 | 14.64 | 0.00 | 14.64 | 0.00 | 14.64 |
March | 60.83 | 14.74 | 5.83 | 14.74 | 0.00 | 14.74 | 0.00 | 14.74 |
April | 14.83 | 14.92 | 1.17 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
May | 8.00 | 14.85 | 0.67 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.28 | 0.00 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.27 | 0.00 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
October | 6.50 | 14.95 | 0.83 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
November | 48.33 | 14.75 | 2.50 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
December | 98.33 | 14.62 | 4.67 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
Annual Sum or Average | 417.83 | 14.63 | 23.83 | 14.63 | 2.33 | 14.70 | 0.00 | 14.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.17 | 14.95 | 5.83 | 14.94 | 1.50 | 27.28 | 0.00 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
February | 276.00 | 21.05 | 276.00 | 21.05 | 276.00 | 21.05 |
March | 324.00 | 21.05 | 324.00 | 21.05 | 324.00 | 21.05 |
April | 300.00 | 21.21 | 279.33 | 21.17 | 279.33 | 21.15 |
May | 312.00 | 21.82 | 203.83 | 21.54 | 203.83 | 21.42 |
June | 224.50 | 23.28 | 35.67 | 23.27 | 8.33 | 23.20 |
July | 49.17 | 23.75 | 137.83 | 23.86 | 0.00 | 23.86 |
August | 126.50 | 23.64 | 80.33 | 23.74 | 0.00 | 23.74 |
September | 231.17 | 22.78 | 96.50 | 22.70 | 54.00 | 22.52 |
October | 300.00 | 21.71 | 194.50 | 21.49 | 194.50 | 21.39 |
November | 288.00 | 21.10 | 283.50 | 21.09 | 283.50 | 21.08 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 3031.33 | 21.66 | 2511.50 | 21.55 | 2223.50 | 21.41 |
Minimum of Months | 49.17 | 21.04 | 35.67 | 21.04 | 0.00 | 21.04 |
Maximum of Months | 324.00 | 23.75 | 324.00 | 23.86 | 324.00 | 23.86 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.55 | 300.00 | 15.55 | 300.00 | 15.55 |
February | 276.00 | 15.71 | 276.00 | 15.71 | 276.00 | 15.71 |
March | 324.00 | 15.79 | 324.00 | 15.79 | 324.00 | 15.79 |
April | 300.00 | 16.60 | 300.00 | 16.60 | 300.00 | 16.60 |
May | 312.00 | 18.15 | 265.17 | 17.80 | 265.17 | 17.68 |
June | 207.83 | 21.90 | 137.33 | 22.72 | 49.33 | 22.37 |
July | 62.17 | 25.08 | 248.83 | 26.10 | 33.00 | 26.16 |
August | 96.17 | 23.60 | 208.67 | 25.44 | 18.17 | 25.51 |
September | 234.67 | 20.70 | 188.83 | 21.11 | 128.17 | 20.73 |
October | 300.00 | 17.74 | 291.50 | 17.69 | 291.50 | 17.67 |
November | 288.00 | 15.99 | 288.00 | 15.99 | 288.00 | 15.99 |
December | 300.00 | 15.58 | 300.00 | 15.58 | 300.00 | 15.58 |
Annual Sum or Average | 3000.83 | 17.53 | 3128.33 | 17.97 | 2573.33 | 17.60 |
Minimum of Months | 62.17 | 15.55 | 137.33 | 15.55 | 18.17 | 15.55 |
Maximum of Months | 324.00 | 25.08 | 324.00 | 26.10 | 324.00 | 26.16 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.04 | 300.00 | 10.04 | 300.00 | 10.04 |
February | 276.00 | 10.37 | 276.00 | 10.37 | 276.00 | 10.37 |
March | 324.00 | 10.71 | 324.00 | 10.71 | 324.00 | 10.71 |
April | 300.00 | 12.40 | 300.00 | 12.40 | 300.00 | 12.40 |
May | 312.00 | 14.68 | 305.33 | 14.61 | 305.33 | 14.59 |
June | 242.17 | 20.69 | 177.00 | 21.01 | 121.50 | 20.62 |
July | 190.67 | 27.91 | 244.83 | 28.01 | 147.17 | 28.36 |
August | 201.67 | 26.52 | 211.17 | 27.23 | 114.00 | 27.73 |
September | 243.83 | 19.29 | 247.67 | 19.72 | 198.17 | 19.42 |
October | 300.00 | 14.92 | 300.00 | 14.92 | 300.00 | 14.92 |
November | 288.00 | 11.41 | 288.00 | 11.41 | 288.00 | 11.41 |
December | 300.00 | 10.15 | 300.00 | 10.15 | 300.00 | 10.15 |
Annual Sum or Average | 3278.33 | 14.90 | 3274.00 | 15.06 | 2974.17 | 14.78 |
Minimum of Months | 190.67 | 10.04 | 177.00 | 10.04 | 114.00 | 10.04 |
Maximum of Months | 324.00 | 27.91 | 324.00 | 28.01 | 324.00 | 28.36 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.194879E+09 | 46538017.60 | 27.67 | 0.194308E+09 | 570928.42 | 0.00 | 0.54 | 20-MAY-16:00 | 0.00 | 01-MAY-00:03 | 4301.47 | 20-MAY-16:00 | 4301.47 | 20-MAY-16:00 | 58.75 | 19-MAY-14:00 | 1074.84 | 20-MAY-16:00 | 0.00 | 01-MAY-00:03 |
June | 0.187954E+10 | 0.436485E+09 | 127.54 | 0.180571E+10 | 73831144.59 | 0.00 | 1.00 | 26-JUN-05:03 | 0.00 | 01-JUN-00:10 | 15684.57 | 26-JUN-05:03 | 10871.55 | 26-JUN-05:03 | 4813.03 | 26-JUN-05:03 | 3397.61 | 26-JUN-05:03 | 0.00 | 01-JUN-00:10 |
July | 0.460151E+10 | 0.106575E+10 | 227.66 | 0.444797E+10 | 0.153544E+09 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 17710.01 | 19-JUL-05:01 | 15910.51 | 25-JUL-05:45 | 6274.92 | 19-JUL-05:04 | 3819.16 | 19-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.367590E+10 | 0.854922E+09 | 206.96 | 0.364682E+10 | 29077521.50 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 15684.82 | 08-AUG-05:01 | 15684.57 | 11-AUG-05:03 | 3998.41 | 14-AUG-05:03 | 3397.67 | 08-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.123389E+10 | 0.281470E+09 | 86.88 | 0.113679E+10 | 97099345.86 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 16590.02 | 07-SEP-05:02 | 15038.89 | 05-SEP-05:01 | 5950.95 | 07-SEP-05:02 | 3596.86 | 07-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 24413181.17 | 5764161.04 | 4.83 | 24413181.17 | -0.0 | 0.00 | 0.31 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 | 2445.22 | 18-OCT-16:00 | 2445.22 | 18-OCT-16:00 | 0.00 | 18-OCT-14:20 | 567.89 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.116101E+11 | 0.269093E+10 | 681.54 | 0.112560E+11 | 0.354123E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.460151E+10 | 0.106575E+10 | 227.66 | 0.444797E+10 | 0.153544E+09 | 0.00 | 1.00 | 0.00 | 17710.01 | 15910.51 | 6274.92 | 3819.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 |
June | 0.719636E+09 | 0.194607E+09 | 40.83 | 0.712699E+09 | 6936813.29 | 0.00 | 0.80 | 30-JUN-17:45 | 0.00 | 01-JUN-00:10 | 12970.79 | 30-JUN-17:45 | 12970.79 | 30-JUN-17:45 | 378.26 | 22-JUN-15:00 | 3278.52 | 30-JUN-17:45 | 0.00 | 01-JUN-00:10 |
July | 0.440744E+10 | 0.115432E+10 | 158.60 | 0.432201E+10 | 85426855.19 | 0.00 | 1.00 | 02-JUL-12:55 | 0.00 | 01-JUL-00:10 | 37037.70 | 16-JUL-10:45 | 35140.34 | 19-JUL-17:45 | 5579.22 | 16-JUL-10:45 | 8987.79 | 17-JUL-17:08 | 0.00 | 01-JUL-00:10 |
August | 0.317669E+10 | 0.840180E+09 | 111.71 | 0.316728E+10 | 9412767.32 | 0.00 | 1.00 | 04-AUG-17:17 | 0.00 | 01-AUG-00:10 | 34853.54 | 08-AUG-20:05 | 34853.54 | 08-AUG-20:05 | 790.94 | 08-AUG-12:00 | 8562.67 | 07-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 0.789132E+09 | 0.209048E+09 | 37.50 | 0.731355E+09 | 57776581.95 | 0.00 | 1.00 | 03-SEP-12:30 | 0.00 | 01-SEP-00:10 | 21488.07 | 04-SEP-14:30 | 21488.07 | 04-SEP-14:30 | 3044.06 | 07-SEP-15:40 | 5509.70 | 04-SEP-15:05 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.909290E+10 | 0.239815E+10 | 348.64 | 0.893334E+10 | 0.159553E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.440744E+10 | 0.115432E+10 | 158.60 | 0.432201E+10 | 85426855.19 | 0.00 | 1.00 | 0.00 | 37037.70 | 35140.34 | 5579.22 | 8987.79 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.52 | 22.96 | 33.56 | 33.22 | 193.88 | 0.00 | 0.00 | 0.00 |
February | 95.76 | 47.13 | 48.63 | 84.77 | 133.55 | 0.00 | 0.00 | 0.00 |
March | 122.93 | 45.15 | 77.78 | 114.36 | 106.08 | 0.00 | 0.00 | 0.00 |
April | 160.19 | 70.76 | 89.43 | 178.59 | 68.91 | 0.00 | 0.00 | 0.00 |
May | 198.19 | 90.41 | 107.77 | 235.75 | 54.81 | 0.00 | 0.00 | 0.00 |
June | 215.45 | 98.93 | 116.52 | 271.99 | 44.62 | 0.00 | 0.00 | 0.00 |
July | 220.94 | 111.69 | 109.25 | 293.65 | 44.42 | 0.00 | 0.00 | 0.00 |
August | 187.21 | 91.63 | 95.58 | 243.00 | 47.36 | 0.00 | 0.00 | 0.00 |
September | 150.73 | 76.16 | 74.57 | 184.53 | 59.86 | 0.00 | 0.00 | 0.00 |
October | 107.94 | 53.66 | 54.29 | 118.45 | 76.50 | 0.00 | 0.00 | 0.00 |
November | 76.28 | 37.84 | 38.43 | 69.61 | 108.20 | 0.00 | 0.00 | 0.00 |
December | 51.17 | 21.56 | 29.61 | 32.59 | 160.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.13 | 64.05 | 73.08 | 155.39 | 91.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.17 | 21.56 | 29.61 | 32.59 | 44.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.94 | 111.69 | 116.52 | 293.65 | 193.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.52 | 22.96 | 33.56 | 33.22 | 193.88 | 0.00 | 0.00 | 0.00 |
February | 95.76 | 47.13 | 48.63 | 84.77 | 133.55 | 0.00 | 0.00 | 0.00 |
March | 122.93 | 45.15 | 77.78 | 114.36 | 106.08 | 0.00 | 0.00 | 0.00 |
April | 160.19 | 70.76 | 89.43 | 178.59 | 68.91 | 0.00 | 0.00 | 0.00 |
May | 198.19 | 90.41 | 107.77 | 235.75 | 54.81 | 0.00 | 0.00 | 0.00 |
June | 215.45 | 98.93 | 116.52 | 271.99 | 44.62 | 0.00 | 0.00 | 0.00 |
July | 220.94 | 111.69 | 109.25 | 293.65 | 44.42 | 0.00 | 0.00 | 0.00 |
August | 187.21 | 91.63 | 95.58 | 243.00 | 47.36 | 0.00 | 0.00 | 0.00 |
September | 150.73 | 76.16 | 74.57 | 184.53 | 59.86 | 0.00 | 0.00 | 0.00 |
October | 107.94 | 53.66 | 54.29 | 118.45 | 76.50 | 0.00 | 0.00 | 0.00 |
November | 76.28 | 37.84 | 38.43 | 69.61 | 108.20 | 0.00 | 0.00 | 0.00 |
December | 51.17 | 21.56 | 29.61 | 32.59 | 160.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.13 | 64.05 | 73.08 | 155.39 | 91.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.17 | 21.56 | 29.61 | 32.59 | 44.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.94 | 111.69 | 116.52 | 293.65 | 193.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.75 | 0.00 | 15.75 | 1.11 | 119.36 | 0.00 | 0.00 | 0.00 |
February | 22.24 | 0.00 | 22.24 | 6.60 | 83.48 | 0.00 | 0.00 | 0.00 |
March | 36.14 | 0.00 | 36.14 | 18.52 | 63.58 | 0.00 | 0.00 | 0.00 |
April | 41.33 | 0.31 | 41.01 | 31.11 | 39.94 | 0.00 | 0.00 | 0.00 |
May | 54.07 | 3.16 | 50.90 | 51.38 | 30.56 | 0.00 | 0.00 | 0.00 |
June | 62.93 | 7.19 | 55.74 | 70.22 | 23.52 | 0.00 | 0.00 | 0.00 |
July | 57.48 | 5.31 | 52.16 | 70.50 | 23.92 | 0.00 | 0.00 | 0.00 |
August | 46.60 | 1.68 | 44.92 | 52.43 | 26.30 | 0.00 | 0.00 | 0.00 |
September | 34.58 | 0.03 | 34.55 | 32.61 | 35.17 | 0.00 | 0.00 | 0.00 |
October | 25.20 | 0.00 | 25.20 | 16.45 | 45.69 | 0.00 | 0.00 | 0.00 |
November | 17.13 | 0.00 | 17.13 | 5.06 | 66.86 | 0.00 | 0.00 | 0.00 |
December | 13.21 | 0.00 | 13.21 | 0.74 | 99.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.63 | 1.48 | 34.14 | 29.86 | 54.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.21 | 0.00 | 13.21 | 0.74 | 23.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.93 | 7.19 | 55.74 | 70.50 | 119.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.75 | 0.00 | 15.75 | 1.11 | 119.36 | 0.00 | 0.00 | 0.00 |
February | 22.24 | 0.00 | 22.24 | 6.60 | 83.48 | 0.00 | 0.00 | 0.00 |
March | 36.14 | 0.00 | 36.13 | 18.52 | 63.58 | 0.00 | 0.00 | 0.00 |
April | 41.32 | 0.31 | 41.01 | 31.11 | 39.94 | 0.00 | 0.00 | 0.00 |
May | 54.06 | 3.16 | 50.90 | 51.38 | 30.56 | 0.00 | 0.00 | 0.00 |
June | 62.92 | 7.19 | 55.74 | 70.22 | 23.52 | 0.00 | 0.00 | 0.00 |
July | 57.48 | 5.31 | 52.16 | 70.50 | 23.92 | 0.00 | 0.00 | 0.00 |
August | 46.60 | 1.68 | 44.92 | 52.43 | 26.30 | 0.00 | 0.00 | 0.00 |
September | 34.57 | 0.03 | 34.54 | 32.61 | 35.17 | 0.00 | 0.00 | 0.00 |
October | 25.19 | 0.00 | 25.19 | 16.45 | 45.69 | 0.00 | 0.00 | 0.00 |
November | 17.13 | 0.00 | 17.13 | 5.06 | 66.86 | 0.00 | 0.00 | 0.00 |
December | 13.21 | 0.00 | 13.21 | 0.74 | 99.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.62 | 1.48 | 34.14 | 29.86 | 54.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.21 | 0.00 | 13.21 | 0.74 | 23.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.92 | 7.19 | 55.74 | 70.50 | 119.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.24 | 11.99 | 17.24 | 19.84 | 80.57 | 0.00 | 0.00 | 0.00 |
February | 48.44 | 26.52 | 21.93 | 49.91 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 79.75 | 38.01 | 41.74 | 92.93 | 43.84 | 0.00 | 0.00 | 0.00 |
April | 99.00 | 55.42 | 43.59 | 124.64 | 28.74 | 0.00 | 0.00 | 0.00 |
May | 127.11 | 72.60 | 54.51 | 165.85 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 153.11 | 98.39 | 54.72 | 199.61 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 158.55 | 111.04 | 47.51 | 205.39 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 90.11 | 41.92 | 167.76 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 91.55 | 58.09 | 33.46 | 115.63 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 56.76 | 31.48 | 25.29 | 68.39 | 36.20 | 0.00 | 0.00 | 0.00 |
November | 34.18 | 16.66 | 17.52 | 34.95 | 45.22 | 0.00 | 0.00 | 0.00 |
December | 22.87 | 8.78 | 14.09 | 15.78 | 66.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.27 | 51.74 | 34.53 | 105.36 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.87 | 8.78 | 14.09 | 15.78 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.55 | 111.04 | 54.72 | 205.39 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.24 | 11.99 | 17.24 | 19.84 | 80.57 | 0.00 | 0.00 | 0.00 |
February | 48.44 | 26.52 | 21.93 | 49.91 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 79.75 | 38.01 | 41.74 | 92.93 | 43.84 | 0.00 | 0.00 | 0.00 |
April | 99.00 | 55.42 | 43.59 | 124.64 | 28.74 | 0.00 | 0.00 | 0.00 |
May | 127.11 | 72.60 | 54.51 | 165.85 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 153.11 | 98.39 | 54.72 | 199.61 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 158.55 | 111.04 | 47.51 | 205.39 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 90.11 | 41.92 | 167.76 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 91.55 | 58.09 | 33.46 | 115.63 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 56.76 | 31.48 | 25.29 | 68.39 | 36.20 | 0.00 | 0.00 | 0.00 |
November | 34.18 | 16.66 | 17.52 | 34.95 | 45.22 | 0.00 | 0.00 | 0.00 |
December | 22.87 | 8.78 | 14.09 | 15.78 | 66.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.27 | 51.74 | 34.53 | 105.36 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.87 | 8.78 | 14.09 | 15.78 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.55 | 111.04 | 54.72 | 205.39 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.24 | 11.99 | 17.24 | 19.84 | 80.57 | 0.00 | 0.00 | 0.00 |
February | 48.44 | 26.52 | 21.93 | 49.91 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 79.75 | 38.01 | 41.74 | 92.93 | 43.84 | 0.00 | 0.00 | 0.00 |
April | 99.00 | 55.42 | 43.59 | 124.64 | 28.74 | 0.00 | 0.00 | 0.00 |
May | 127.11 | 72.60 | 54.51 | 165.85 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 153.11 | 98.39 | 54.72 | 199.61 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 158.55 | 111.04 | 47.51 | 205.39 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 90.11 | 41.92 | 167.76 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 91.55 | 58.09 | 33.46 | 115.63 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 56.76 | 31.48 | 25.29 | 68.39 | 36.20 | 0.00 | 0.00 | 0.00 |
November | 34.18 | 16.66 | 17.52 | 34.95 | 45.22 | 0.00 | 0.00 | 0.00 |
December | 22.87 | 8.78 | 14.09 | 15.78 | 66.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.27 | 51.74 | 34.53 | 105.36 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.87 | 8.78 | 14.09 | 15.78 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.55 | 111.04 | 54.72 | 205.39 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.24 | 11.99 | 17.24 | 19.84 | 80.57 | 0.00 | 0.00 | 0.00 |
February | 48.44 | 26.52 | 21.93 | 49.91 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 79.75 | 38.01 | 41.74 | 92.93 | 43.84 | 0.00 | 0.00 | 0.00 |
April | 99.00 | 55.42 | 43.59 | 124.64 | 28.74 | 0.00 | 0.00 | 0.00 |
May | 127.11 | 72.60 | 54.51 | 165.85 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 153.11 | 98.39 | 54.72 | 199.61 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 158.55 | 111.04 | 47.51 | 205.39 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 90.11 | 41.92 | 167.76 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 91.55 | 58.09 | 33.46 | 115.63 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 56.76 | 31.48 | 25.29 | 68.39 | 36.20 | 0.00 | 0.00 | 0.00 |
November | 34.18 | 16.66 | 17.52 | 34.95 | 45.22 | 0.00 | 0.00 | 0.00 |
December | 22.87 | 8.78 | 14.09 | 15.78 | 66.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.27 | 51.74 | 34.53 | 105.36 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.87 | 8.78 | 14.09 | 15.78 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.55 | 111.04 | 54.72 | 205.39 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.24 | 11.99 | 17.24 | 19.84 | 80.57 | 0.00 | 0.00 | 0.00 |
February | 48.44 | 26.52 | 21.93 | 49.91 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 79.75 | 38.01 | 41.74 | 92.93 | 43.84 | 0.00 | 0.00 | 0.00 |
April | 99.00 | 55.42 | 43.59 | 124.64 | 28.74 | 0.00 | 0.00 | 0.00 |
May | 127.11 | 72.60 | 54.51 | 165.85 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 153.11 | 98.39 | 54.72 | 199.61 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 158.55 | 111.04 | 47.51 | 205.39 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 90.11 | 41.92 | 167.76 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 91.55 | 58.09 | 33.46 | 115.63 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 56.76 | 31.48 | 25.29 | 68.39 | 36.20 | 0.00 | 0.00 | 0.00 |
November | 34.18 | 16.66 | 17.52 | 34.95 | 45.22 | 0.00 | 0.00 | 0.00 |
December | 22.87 | 8.78 | 14.09 | 15.78 | 66.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.27 | 51.74 | 34.53 | 105.36 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.87 | 8.78 | 14.09 | 15.78 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.55 | 111.04 | 54.72 | 205.39 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.24 | 11.99 | 17.24 | 19.84 | 80.57 | 0.00 | 0.00 | 0.00 |
February | 48.44 | 26.52 | 21.93 | 49.91 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 79.75 | 38.01 | 41.74 | 92.93 | 43.84 | 0.00 | 0.00 | 0.00 |
April | 99.00 | 55.42 | 43.59 | 124.64 | 28.74 | 0.00 | 0.00 | 0.00 |
May | 127.11 | 72.60 | 54.51 | 165.85 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 153.11 | 98.39 | 54.72 | 199.61 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 158.55 | 111.04 | 47.51 | 205.39 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 90.11 | 41.92 | 167.76 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 91.55 | 58.09 | 33.46 | 115.63 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 56.76 | 31.48 | 25.29 | 68.39 | 36.20 | 0.00 | 0.00 | 0.00 |
November | 34.18 | 16.66 | 17.52 | 34.95 | 45.22 | 0.00 | 0.00 | 0.00 |
December | 22.87 | 8.78 | 14.09 | 15.78 | 66.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.27 | 51.74 | 34.53 | 105.36 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.87 | 8.78 | 14.09 | 15.78 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.55 | 111.04 | 54.72 | 205.39 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.24 | 11.99 | 17.24 | 19.84 | 80.57 | 0.00 | 0.00 | 0.00 |
February | 48.44 | 26.52 | 21.93 | 49.91 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 79.75 | 38.01 | 41.74 | 92.93 | 43.84 | 0.00 | 0.00 | 0.00 |
April | 99.00 | 55.42 | 43.59 | 124.64 | 28.74 | 0.00 | 0.00 | 0.00 |
May | 127.11 | 72.60 | 54.51 | 165.85 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 153.11 | 98.39 | 54.72 | 199.61 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 158.55 | 111.04 | 47.51 | 205.39 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 90.11 | 41.92 | 167.76 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 91.55 | 58.09 | 33.46 | 115.63 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 56.76 | 31.48 | 25.29 | 68.39 | 36.20 | 0.00 | 0.00 | 0.00 |
November | 34.18 | 16.66 | 17.52 | 34.95 | 45.22 | 0.00 | 0.00 | 0.00 |
December | 22.87 | 8.78 | 14.09 | 15.78 | 66.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.27 | 51.74 | 34.53 | 105.36 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.87 | 8.78 | 14.09 | 15.78 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.55 | 111.04 | 54.72 | 205.39 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.24 | 11.99 | 17.24 | 19.84 | 80.57 | 0.00 | 0.00 | 0.00 |
February | 48.44 | 26.52 | 21.93 | 49.91 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 79.75 | 38.01 | 41.74 | 92.93 | 43.84 | 0.00 | 0.00 | 0.00 |
April | 99.00 | 55.42 | 43.59 | 124.64 | 28.74 | 0.00 | 0.00 | 0.00 |
May | 127.11 | 72.60 | 54.51 | 165.85 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 153.11 | 98.39 | 54.72 | 199.61 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 158.55 | 111.04 | 47.51 | 205.39 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 90.11 | 41.92 | 167.76 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 91.55 | 58.09 | 33.46 | 115.63 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 56.76 | 31.48 | 25.29 | 68.39 | 36.20 | 0.00 | 0.00 | 0.00 |
November | 34.18 | 16.66 | 17.52 | 34.95 | 45.22 | 0.00 | 0.00 | 0.00 |
December | 22.87 | 8.78 | 14.09 | 15.78 | 66.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.27 | 51.74 | 34.53 | 105.36 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.87 | 8.78 | 14.09 | 15.78 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.55 | 111.04 | 54.72 | 205.39 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.24 | 11.99 | 17.24 | 19.84 | 80.57 | 0.00 | 0.00 | 0.00 |
February | 48.44 | 26.52 | 21.93 | 49.91 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 79.75 | 38.01 | 41.74 | 92.93 | 43.84 | 0.00 | 0.00 | 0.00 |
April | 99.00 | 55.42 | 43.59 | 124.64 | 28.74 | 0.00 | 0.00 | 0.00 |
May | 127.11 | 72.60 | 54.51 | 165.85 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 153.11 | 98.39 | 54.72 | 199.61 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 158.55 | 111.04 | 47.51 | 205.39 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 90.11 | 41.92 | 167.76 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 91.55 | 58.09 | 33.46 | 115.63 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 56.76 | 31.48 | 25.29 | 68.39 | 36.20 | 0.00 | 0.00 | 0.00 |
November | 34.18 | 16.66 | 17.52 | 34.95 | 45.22 | 0.00 | 0.00 | 0.00 |
December | 22.87 | 8.78 | 14.09 | 15.78 | 66.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.27 | 51.74 | 34.53 | 105.36 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.87 | 8.78 | 14.09 | 15.78 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.55 | 111.04 | 54.72 | 205.39 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.24 | 11.99 | 17.24 | 19.84 | 80.57 | 0.00 | 0.00 | 0.00 |
February | 48.44 | 26.52 | 21.93 | 49.91 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 79.75 | 38.01 | 41.74 | 92.93 | 43.84 | 0.00 | 0.00 | 0.00 |
April | 99.00 | 55.42 | 43.59 | 124.64 | 28.74 | 0.00 | 0.00 | 0.00 |
May | 127.11 | 72.60 | 54.51 | 165.85 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 153.11 | 98.39 | 54.72 | 199.61 | 24.70 | 0.00 | 0.00 | 0.00 |
July | 158.55 | 111.04 | 47.51 | 205.39 | 31.35 | 0.00 | 0.00 | 0.00 |
August | 132.03 | 90.11 | 41.92 | 167.76 | 33.30 | 0.00 | 0.00 | 0.00 |
September | 91.55 | 58.09 | 33.46 | 115.63 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 56.76 | 31.48 | 25.29 | 68.39 | 36.20 | 0.00 | 0.00 | 0.00 |
November | 34.18 | 16.66 | 17.52 | 34.95 | 45.22 | 0.00 | 0.00 | 0.00 |
December | 22.87 | 8.78 | 14.09 | 15.78 | 66.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.27 | 51.74 | 34.53 | 105.36 | 41.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.87 | 8.78 | 14.09 | 15.78 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.55 | 111.04 | 54.72 | 205.39 | 80.57 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151382E+09 | 61490482.08 | 89891596.51 | 88980707.03 | 0.519294E+09 |
February | 0.231656E+09 | 0.114007E+09 | 0.117648E+09 | 0.205083E+09 | 0.323073E+09 |
March | 0.329252E+09 | 0.120929E+09 | 0.208322E+09 | 0.306290E+09 | 0.284135E+09 |
April | 0.415225E+09 | 0.183421E+09 | 0.231804E+09 | 0.462907E+09 | 0.178615E+09 |
May | 0.530823E+09 | 0.242163E+09 | 0.288660E+09 | 0.631438E+09 | 0.146816E+09 |
June | 0.558455E+09 | 0.256431E+09 | 0.302024E+09 | 0.704990E+09 | 0.115645E+09 |
July | 0.591769E+09 | 0.299163E+09 | 0.292606E+09 | 0.786516E+09 | 0.118986E+09 |
August | 0.501416E+09 | 0.245420E+09 | 0.255997E+09 | 0.650854E+09 | 0.126844E+09 |
September | 0.390688E+09 | 0.197404E+09 | 0.193284E+09 | 0.478299E+09 | 0.155159E+09 |
October | 0.289115E+09 | 0.143713E+09 | 0.145402E+09 | 0.317254E+09 | 0.204890E+09 |
November | 0.197706E+09 | 98089762.87 | 99615938.84 | 0.180437E+09 | 0.280464E+09 |
December | 0.137051E+09 | 57745949.93 | 79304592.36 | 87277214.95 | 0.430884E+09 |
Annual Sum or Average | 0.432454E+10 | 0.201998E+10 | 0.230456E+10 | 0.490032E+10 | 0.288481E+10 |
Minimum of Months | 0.137051E+09 | 57745949.93 | 79304592.36 | 87277214.95 | 0.115645E+09 |
Maximum of Months | 0.591769E+09 | 0.299163E+09 | 0.302024E+09 | 0.786516E+09 | 0.519294E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151382E+09 | 61490482.08 | 89891596.51 | 88980707.03 | 0.519294E+09 |
February | 0.231656E+09 | 0.114007E+09 | 0.117648E+09 | 0.205083E+09 | 0.323073E+09 |
March | 0.329252E+09 | 0.120929E+09 | 0.208322E+09 | 0.306290E+09 | 0.284135E+09 |
April | 0.415225E+09 | 0.183421E+09 | 0.231804E+09 | 0.462907E+09 | 0.178615E+09 |
May | 0.530823E+09 | 0.242163E+09 | 0.288660E+09 | 0.631438E+09 | 0.146816E+09 |
June | 0.558455E+09 | 0.256431E+09 | 0.302024E+09 | 0.704990E+09 | 0.115645E+09 |
July | 0.591769E+09 | 0.299163E+09 | 0.292606E+09 | 0.786516E+09 | 0.118986E+09 |
August | 0.501416E+09 | 0.245420E+09 | 0.255997E+09 | 0.650854E+09 | 0.126844E+09 |
September | 0.390688E+09 | 0.197404E+09 | 0.193284E+09 | 0.478299E+09 | 0.155159E+09 |
October | 0.289115E+09 | 0.143713E+09 | 0.145402E+09 | 0.317254E+09 | 0.204890E+09 |
November | 0.197706E+09 | 98089762.87 | 99615938.84 | 0.180437E+09 | 0.280464E+09 |
December | 0.137051E+09 | 57745949.93 | 79304592.36 | 87277214.95 | 0.430884E+09 |
Annual Sum or Average | 0.432454E+10 | 0.201998E+10 | 0.230456E+10 | 0.490032E+10 | 0.288481E+10 |
Minimum of Months | 0.137051E+09 | 57745949.93 | 79304592.36 | 87277214.95 | 0.115645E+09 |
Maximum of Months | 0.591769E+09 | 0.299163E+09 | 0.302024E+09 | 0.786516E+09 | 0.519294E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42194899.85 | 0.00 | 42194899.85 | 2976117.43 | 0.319703E+09 |
February | 53811102.08 | 0.00 | 53811102.08 | 15977375.10 | 0.201958E+09 |
March | 96791042.01 | 5021.21 | 96786020.80 | 49610835.61 | 0.170282E+09 |
April | 0.107115E+09 | 809360.45 | 0.106305E+09 | 80628702.43 | 0.103524E+09 |
May | 0.144812E+09 | 8475736.56 | 0.136336E+09 | 0.137623E+09 | 81864208.12 |
June | 0.163106E+09 | 18630375.65 | 0.144476E+09 | 0.182008E+09 | 60962149.86 |
July | 0.153948E+09 | 14229874.18 | 0.139718E+09 | 0.188837E+09 | 64063411.86 |
August | 0.124817E+09 | 4503193.04 | 0.120314E+09 | 0.140429E+09 | 70446249.63 |
September | 89620820.25 | 78228.05 | 89542592.20 | 84520915.35 | 91160849.24 |
October | 67483351.44 | 0.00 | 67483351.44 | 44070014.34 | 0.122384E+09 |
November | 44395945.17 | 0.00 | 44395945.17 | 13116249.35 | 0.173308E+09 |
December | 35382801.46 | 0.00 | 35382801.46 | 1987279.13 | 0.266387E+09 |
Annual Sum or Average | 0.112348E+10 | 46731789.13 | 0.107675E+10 | 0.941784E+09 | 0.172604E+10 |
Minimum of Months | 35382801.46 | 0.00 | 35382801.46 | 1987279.13 | 60962149.86 |
Maximum of Months | 0.163106E+09 | 18630375.65 | 0.144476E+09 | 0.188837E+09 | 0.319703E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42193539.19 | 0.00 | 42193539.19 | 2975784.87 | 0.319703E+09 |
February | 53809481.58 | 0.00 | 53809481.58 | 15976411.21 | 0.201959E+09 |
March | 96787984.98 | 5020.98 | 96782964.00 | 49607800.94 | 0.170282E+09 |
April | 0.107111E+09 | 809322.51 | 0.106302E+09 | 80625299.33 | 0.103524E+09 |
May | 0.144807E+09 | 8475339.29 | 0.136332E+09 | 0.137617E+09 | 81863948.14 |
June | 0.163101E+09 | 18629502.42 | 0.144471E+09 | 0.182001E+09 | 60961842.41 |
July | 0.153943E+09 | 14229207.21 | 0.139714E+09 | 0.188832E+09 | 64062863.55 |
August | 0.124814E+09 | 4502981.97 | 0.120311E+09 | 0.140425E+09 | 70445754.53 |
September | 89618256.29 | 78224.38 | 89540031.91 | 84518180.40 | 91160429.49 |
October | 67481307.79 | 0.00 | 67481307.79 | 44068015.42 | 0.122384E+09 |
November | 44394552.95 | 0.00 | 44394552.95 | 13115462.07 | 0.173308E+09 |
December | 35381644.98 | 0.00 | 35381644.98 | 1987041.47 | 0.266387E+09 |
Annual Sum or Average | 0.112344E+10 | 46729598.75 | 0.107671E+10 | 0.941749E+09 | 0.172604E+10 |
Minimum of Months | 35381644.98 | 0.00 | 35381644.98 | 1987041.47 | 60961842.41 |
Maximum of Months | 0.163101E+09 | 18629502.42 | 0.144471E+09 | 0.188832E+09 | 0.319703E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78313383.53 | 32125021.58 | 46188361.95 | 53143722.36 | 0.215811E+09 |
February | 0.117191E+09 | 64148953.19 | 53041705.76 | 0.120734E+09 | 0.134034E+09 |
March | 0.213608E+09 | 0.101801E+09 | 0.111807E+09 | 0.248891E+09 | 0.117424E+09 |
April | 0.256619E+09 | 0.143638E+09 | 0.112981E+09 | 0.323068E+09 | 74501085.27 |
May | 0.340462E+09 | 0.194450E+09 | 0.146013E+09 | 0.444212E+09 | 63400644.13 |
June | 0.396860E+09 | 0.255039E+09 | 0.141821E+09 | 0.517400E+09 | 64029211.10 |
July | 0.424653E+09 | 0.297407E+09 | 0.127247E+09 | 0.550123E+09 | 83976713.73 |
August | 0.353621E+09 | 0.241340E+09 | 0.112281E+09 | 0.449339E+09 | 89196338.68 |
September | 0.237308E+09 | 0.150578E+09 | 86730069.83 | 0.299712E+09 | 85275364.29 |
October | 0.152038E+09 | 84312132.28 | 67726112.56 | 0.183188E+09 | 96966868.38 |
November | 88582024.33 | 43179756.17 | 45402268.16 | 90582949.53 | 0.117214E+09 |
December | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 0.177018E+09 |
Annual Sum or Average | 0.272052E+10 | 0.163155E+10 | 0.108897E+10 | 0.332267E+10 | 0.131885E+10 |
Minimum of Months | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 63400644.13 |
Maximum of Months | 0.424653E+09 | 0.297407E+09 | 0.146013E+09 | 0.550123E+09 | 0.215811E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78313383.53 | 32125021.58 | 46188361.95 | 53143722.36 | 0.215811E+09 |
February | 0.117191E+09 | 64148953.19 | 53041705.76 | 0.120734E+09 | 0.134034E+09 |
March | 0.213608E+09 | 0.101801E+09 | 0.111807E+09 | 0.248891E+09 | 0.117424E+09 |
April | 0.256619E+09 | 0.143638E+09 | 0.112981E+09 | 0.323068E+09 | 74501085.27 |
May | 0.340462E+09 | 0.194450E+09 | 0.146013E+09 | 0.444212E+09 | 63400644.13 |
June | 0.396860E+09 | 0.255039E+09 | 0.141821E+09 | 0.517400E+09 | 64029211.10 |
July | 0.424653E+09 | 0.297407E+09 | 0.127247E+09 | 0.550123E+09 | 83976713.73 |
August | 0.353621E+09 | 0.241340E+09 | 0.112281E+09 | 0.449339E+09 | 89196338.68 |
September | 0.237308E+09 | 0.150578E+09 | 86730069.83 | 0.299712E+09 | 85275364.29 |
October | 0.152038E+09 | 84312132.28 | 67726112.56 | 0.183188E+09 | 96966868.38 |
November | 88582024.33 | 43179756.17 | 45402268.16 | 90582949.53 | 0.117214E+09 |
December | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 0.177018E+09 |
Annual Sum or Average | 0.272052E+10 | 0.163155E+10 | 0.108897E+10 | 0.332267E+10 | 0.131885E+10 |
Minimum of Months | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 63400644.13 |
Maximum of Months | 0.424653E+09 | 0.297407E+09 | 0.146013E+09 | 0.550123E+09 | 0.215811E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78313383.53 | 32125021.58 | 46188361.95 | 53143722.36 | 0.215811E+09 |
February | 0.117191E+09 | 64148953.19 | 53041705.76 | 0.120734E+09 | 0.134034E+09 |
March | 0.213608E+09 | 0.101801E+09 | 0.111807E+09 | 0.248891E+09 | 0.117424E+09 |
April | 0.256619E+09 | 0.143638E+09 | 0.112981E+09 | 0.323068E+09 | 74501085.27 |
May | 0.340462E+09 | 0.194450E+09 | 0.146013E+09 | 0.444212E+09 | 63400644.13 |
June | 0.396860E+09 | 0.255039E+09 | 0.141821E+09 | 0.517400E+09 | 64029211.10 |
July | 0.424653E+09 | 0.297407E+09 | 0.127247E+09 | 0.550123E+09 | 83976713.73 |
August | 0.353621E+09 | 0.241340E+09 | 0.112281E+09 | 0.449339E+09 | 89196338.68 |
September | 0.237308E+09 | 0.150578E+09 | 86730069.83 | 0.299712E+09 | 85275364.29 |
October | 0.152038E+09 | 84312132.28 | 67726112.56 | 0.183188E+09 | 96966868.38 |
November | 88582024.33 | 43179756.17 | 45402268.16 | 90582949.53 | 0.117214E+09 |
December | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 0.177018E+09 |
Annual Sum or Average | 0.272052E+10 | 0.163155E+10 | 0.108897E+10 | 0.332267E+10 | 0.131885E+10 |
Minimum of Months | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 63400644.13 |
Maximum of Months | 0.424653E+09 | 0.297407E+09 | 0.146013E+09 | 0.550123E+09 | 0.215811E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78313383.53 | 32125021.58 | 46188361.95 | 53143722.36 | 0.215811E+09 |
February | 0.117191E+09 | 64148953.19 | 53041705.76 | 0.120734E+09 | 0.134034E+09 |
March | 0.213608E+09 | 0.101801E+09 | 0.111807E+09 | 0.248891E+09 | 0.117424E+09 |
April | 0.256619E+09 | 0.143638E+09 | 0.112981E+09 | 0.323068E+09 | 74501085.27 |
May | 0.340462E+09 | 0.194450E+09 | 0.146013E+09 | 0.444212E+09 | 63400644.13 |
June | 0.396860E+09 | 0.255039E+09 | 0.141821E+09 | 0.517400E+09 | 64029211.10 |
July | 0.424653E+09 | 0.297407E+09 | 0.127247E+09 | 0.550123E+09 | 83976713.73 |
August | 0.353621E+09 | 0.241340E+09 | 0.112281E+09 | 0.449339E+09 | 89196338.68 |
September | 0.237308E+09 | 0.150578E+09 | 86730069.83 | 0.299712E+09 | 85275364.29 |
October | 0.152038E+09 | 84312132.28 | 67726112.56 | 0.183188E+09 | 96966868.38 |
November | 88582024.33 | 43179756.17 | 45402268.16 | 90582949.53 | 0.117214E+09 |
December | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 0.177018E+09 |
Annual Sum or Average | 0.272052E+10 | 0.163155E+10 | 0.108897E+10 | 0.332267E+10 | 0.131885E+10 |
Minimum of Months | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 63400644.13 |
Maximum of Months | 0.424653E+09 | 0.297407E+09 | 0.146013E+09 | 0.550123E+09 | 0.215811E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78313383.53 | 32125021.58 | 46188361.95 | 53143722.36 | 0.215811E+09 |
February | 0.117191E+09 | 64148953.19 | 53041705.76 | 0.120734E+09 | 0.134034E+09 |
March | 0.213608E+09 | 0.101801E+09 | 0.111807E+09 | 0.248891E+09 | 0.117424E+09 |
April | 0.256619E+09 | 0.143638E+09 | 0.112981E+09 | 0.323068E+09 | 74501085.27 |
May | 0.340462E+09 | 0.194450E+09 | 0.146013E+09 | 0.444212E+09 | 63400644.13 |
June | 0.396860E+09 | 0.255039E+09 | 0.141821E+09 | 0.517400E+09 | 64029211.10 |
July | 0.424653E+09 | 0.297407E+09 | 0.127247E+09 | 0.550123E+09 | 83976713.73 |
August | 0.353621E+09 | 0.241340E+09 | 0.112281E+09 | 0.449339E+09 | 89196338.68 |
September | 0.237308E+09 | 0.150578E+09 | 86730069.83 | 0.299712E+09 | 85275364.29 |
October | 0.152038E+09 | 84312132.28 | 67726112.56 | 0.183188E+09 | 96966868.38 |
November | 88582024.33 | 43179756.17 | 45402268.16 | 90582949.53 | 0.117214E+09 |
December | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 0.177018E+09 |
Annual Sum or Average | 0.272052E+10 | 0.163155E+10 | 0.108897E+10 | 0.332267E+10 | 0.131885E+10 |
Minimum of Months | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 63400644.13 |
Maximum of Months | 0.424653E+09 | 0.297407E+09 | 0.146013E+09 | 0.550123E+09 | 0.215811E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78313383.53 | 32125021.58 | 46188361.95 | 53143722.36 | 0.215811E+09 |
February | 0.117191E+09 | 64148953.19 | 53041705.76 | 0.120734E+09 | 0.134034E+09 |
March | 0.213608E+09 | 0.101801E+09 | 0.111807E+09 | 0.248891E+09 | 0.117424E+09 |
April | 0.256619E+09 | 0.143638E+09 | 0.112981E+09 | 0.323068E+09 | 74501085.27 |
May | 0.340462E+09 | 0.194450E+09 | 0.146013E+09 | 0.444212E+09 | 63400644.13 |
June | 0.396860E+09 | 0.255039E+09 | 0.141821E+09 | 0.517400E+09 | 64029211.10 |
July | 0.424653E+09 | 0.297407E+09 | 0.127247E+09 | 0.550123E+09 | 83976713.73 |
August | 0.353621E+09 | 0.241340E+09 | 0.112281E+09 | 0.449339E+09 | 89196338.68 |
September | 0.237308E+09 | 0.150578E+09 | 86730069.83 | 0.299712E+09 | 85275364.29 |
October | 0.152038E+09 | 84312132.28 | 67726112.56 | 0.183188E+09 | 96966868.38 |
November | 88582024.33 | 43179756.17 | 45402268.16 | 90582949.53 | 0.117214E+09 |
December | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 0.177018E+09 |
Annual Sum or Average | 0.272052E+10 | 0.163155E+10 | 0.108897E+10 | 0.332267E+10 | 0.131885E+10 |
Minimum of Months | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 63400644.13 |
Maximum of Months | 0.424653E+09 | 0.297407E+09 | 0.146013E+09 | 0.550123E+09 | 0.215811E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78313383.53 | 32125021.58 | 46188361.95 | 53143722.36 | 0.215811E+09 |
February | 0.117191E+09 | 64148953.19 | 53041705.76 | 0.120734E+09 | 0.134034E+09 |
March | 0.213608E+09 | 0.101801E+09 | 0.111807E+09 | 0.248891E+09 | 0.117424E+09 |
April | 0.256619E+09 | 0.143638E+09 | 0.112981E+09 | 0.323068E+09 | 74501085.27 |
May | 0.340462E+09 | 0.194450E+09 | 0.146013E+09 | 0.444212E+09 | 63400644.13 |
June | 0.396860E+09 | 0.255039E+09 | 0.141821E+09 | 0.517400E+09 | 64029211.10 |
July | 0.424653E+09 | 0.297407E+09 | 0.127247E+09 | 0.550123E+09 | 83976713.73 |
August | 0.353621E+09 | 0.241340E+09 | 0.112281E+09 | 0.449339E+09 | 89196338.68 |
September | 0.237308E+09 | 0.150578E+09 | 86730069.83 | 0.299712E+09 | 85275364.29 |
October | 0.152038E+09 | 84312132.28 | 67726112.56 | 0.183188E+09 | 96966868.38 |
November | 88582024.33 | 43179756.17 | 45402268.16 | 90582949.53 | 0.117214E+09 |
December | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 0.177018E+09 |
Annual Sum or Average | 0.272052E+10 | 0.163155E+10 | 0.108897E+10 | 0.332267E+10 | 0.131885E+10 |
Minimum of Months | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 63400644.13 |
Maximum of Months | 0.424653E+09 | 0.297407E+09 | 0.146013E+09 | 0.550123E+09 | 0.215811E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78313383.53 | 32125021.58 | 46188361.95 | 53143722.36 | 0.215811E+09 |
February | 0.117191E+09 | 64148953.19 | 53041705.76 | 0.120734E+09 | 0.134034E+09 |
March | 0.213608E+09 | 0.101801E+09 | 0.111807E+09 | 0.248891E+09 | 0.117424E+09 |
April | 0.256619E+09 | 0.143638E+09 | 0.112981E+09 | 0.323068E+09 | 74501085.27 |
May | 0.340462E+09 | 0.194450E+09 | 0.146013E+09 | 0.444212E+09 | 63400644.13 |
June | 0.396860E+09 | 0.255039E+09 | 0.141821E+09 | 0.517400E+09 | 64029211.10 |
July | 0.424653E+09 | 0.297407E+09 | 0.127247E+09 | 0.550123E+09 | 83976713.73 |
August | 0.353621E+09 | 0.241340E+09 | 0.112281E+09 | 0.449339E+09 | 89196338.68 |
September | 0.237308E+09 | 0.150578E+09 | 86730069.83 | 0.299712E+09 | 85275364.29 |
October | 0.152038E+09 | 84312132.28 | 67726112.56 | 0.183188E+09 | 96966868.38 |
November | 88582024.33 | 43179756.17 | 45402268.16 | 90582949.53 | 0.117214E+09 |
December | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 0.177018E+09 |
Annual Sum or Average | 0.272052E+10 | 0.163155E+10 | 0.108897E+10 | 0.332267E+10 | 0.131885E+10 |
Minimum of Months | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 63400644.13 |
Maximum of Months | 0.424653E+09 | 0.297407E+09 | 0.146013E+09 | 0.550123E+09 | 0.215811E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78313383.53 | 32125021.58 | 46188361.95 | 53143722.36 | 0.215811E+09 |
February | 0.117191E+09 | 64148953.19 | 53041705.76 | 0.120734E+09 | 0.134034E+09 |
March | 0.213608E+09 | 0.101801E+09 | 0.111807E+09 | 0.248891E+09 | 0.117424E+09 |
April | 0.256619E+09 | 0.143638E+09 | 0.112981E+09 | 0.323068E+09 | 74501085.27 |
May | 0.340462E+09 | 0.194450E+09 | 0.146013E+09 | 0.444212E+09 | 63400644.13 |
June | 0.396860E+09 | 0.255039E+09 | 0.141821E+09 | 0.517400E+09 | 64029211.10 |
July | 0.424653E+09 | 0.297407E+09 | 0.127247E+09 | 0.550123E+09 | 83976713.73 |
August | 0.353621E+09 | 0.241340E+09 | 0.112281E+09 | 0.449339E+09 | 89196338.68 |
September | 0.237308E+09 | 0.150578E+09 | 86730069.83 | 0.299712E+09 | 85275364.29 |
October | 0.152038E+09 | 84312132.28 | 67726112.56 | 0.183188E+09 | 96966868.38 |
November | 88582024.33 | 43179756.17 | 45402268.16 | 90582949.53 | 0.117214E+09 |
December | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 0.177018E+09 |
Annual Sum or Average | 0.272052E+10 | 0.163155E+10 | 0.108897E+10 | 0.332267E+10 | 0.131885E+10 |
Minimum of Months | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 63400644.13 |
Maximum of Months | 0.424653E+09 | 0.297407E+09 | 0.146013E+09 | 0.550123E+09 | 0.215811E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78313383.53 | 32125021.58 | 46188361.95 | 53143722.36 | 0.215811E+09 |
February | 0.117191E+09 | 64148953.19 | 53041705.76 | 0.120734E+09 | 0.134034E+09 |
March | 0.213608E+09 | 0.101801E+09 | 0.111807E+09 | 0.248891E+09 | 0.117424E+09 |
April | 0.256619E+09 | 0.143638E+09 | 0.112981E+09 | 0.323068E+09 | 74501085.27 |
May | 0.340462E+09 | 0.194450E+09 | 0.146013E+09 | 0.444212E+09 | 63400644.13 |
June | 0.396860E+09 | 0.255039E+09 | 0.141821E+09 | 0.517400E+09 | 64029211.10 |
July | 0.424653E+09 | 0.297407E+09 | 0.127247E+09 | 0.550123E+09 | 83976713.73 |
August | 0.353621E+09 | 0.241340E+09 | 0.112281E+09 | 0.449339E+09 | 89196338.68 |
September | 0.237308E+09 | 0.150578E+09 | 86730069.83 | 0.299712E+09 | 85275364.29 |
October | 0.152038E+09 | 84312132.28 | 67726112.56 | 0.183188E+09 | 96966868.38 |
November | 88582024.33 | 43179756.17 | 45402268.16 | 90582949.53 | 0.117214E+09 |
December | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 0.177018E+09 |
Annual Sum or Average | 0.272052E+10 | 0.163155E+10 | 0.108897E+10 | 0.332267E+10 | 0.131885E+10 |
Minimum of Months | 61259758.35 | 23526697.39 | 37733060.96 | 42271247.72 | 63400644.13 |
Maximum of Months | 0.424653E+09 | 0.297407E+09 | 0.146013E+09 | 0.550123E+09 | 0.215811E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 60.01 | 617.83 | 144.55 | 45.92 | 98.63 | 0.00 | 0.00 |
February | 175.00 | 426.30 | 236.00 | 94.25 | 141.75 | 0.00 | 0.00 |
March | 263.13 | 336.70 | 318.13 | 90.30 | 227.83 | 0.00 | 0.00 |
April | 418.64 | 216.94 | 403.04 | 142.15 | 260.89 | 0.00 | 0.00 |
May | 571.93 | 168.42 | 504.50 | 187.16 | 317.35 | 0.00 | 0.00 |
June | 679.81 | 131.68 | 556.76 | 212.24 | 344.52 | 0.00 | 0.00 |
July | 723.83 | 132.21 | 556.84 | 234.01 | 322.82 | 0.00 | 0.00 |
August | 589.20 | 145.66 | 467.62 | 186.62 | 281.00 | 0.00 | 0.00 |
September | 433.44 | 189.23 | 370.61 | 152.38 | 218.23 | 0.00 | 0.00 |
October | 267.71 | 242.28 | 266.28 | 107.31 | 158.96 | 0.00 | 0.00 |
November | 142.44 | 343.23 | 186.81 | 75.69 | 111.12 | 0.00 | 0.00 |
December | 57.91 | 511.92 | 128.76 | 43.12 | 85.64 | 0.00 | 0.00 |
Annual Sum or Average | 366.23 | 288.15 | 345.51 | 131.07 | 214.44 | 0.00 | 0.00 |
Minimum of Months | 57.91 | 131.68 | 128.76 | 43.12 | 85.64 | 0.00 | 0.00 |
Maximum of Months | 723.83 | 617.83 | 556.84 | 234.01 | 344.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 993.80 | 6178.55 | 292.39 | 119.94 | 172.45 | 0.00 | 0.00 |
February | 2185.17 | 3888.14 | 484.42 | 265.17 | 219.25 | 0.00 | 0.00 |
March | 4072.87 | 2820.46 | 797.52 | 380.08 | 417.44 | 0.00 | 0.00 |
April | 5033.64 | 1442.91 | 990.04 | 554.16 | 435.88 | 0.00 | 0.00 |
May | 6637.82 | 988.08 | 1271.14 | 725.99 | 545.15 | 0.00 | 0.00 |
June | 7815.43 | 756.67 | 1531.10 | 983.95 | 547.15 | 0.00 | 0.00 |
July | 8272.90 | 1005.47 | 1585.47 | 1110.39 | 475.08 | 0.00 | 0.00 |
August | 6746.78 | 1068.39 | 1320.27 | 901.06 | 419.21 | 0.00 | 0.00 |
September | 4537.28 | 1060.69 | 915.54 | 580.93 | 334.61 | 0.00 | 0.00 |
October | 2729.38 | 1389.57 | 567.65 | 314.79 | 252.86 | 0.00 | 0.00 |
November | 1468.86 | 2646.16 | 341.75 | 166.59 | 175.16 | 0.00 | 0.00 |
December | 746.64 | 4499.42 | 228.72 | 87.84 | 140.88 | 0.00 | 0.00 |
Annual Sum or Average | 4282.32 | 2308.24 | 862.67 | 517.36 | 345.31 | 0.00 | 0.00 |
Minimum of Months | 746.64 | 756.67 | 228.72 | 87.84 | 140.88 | 0.00 | 0.00 |
Maximum of Months | 8272.90 | 6178.55 | 1585.47 | 1110.39 | 547.15 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160721E+09 | 0.165480E+10 | 0.387153E+09 | 0.122981E+09 | 0.264172E+09 | 0.00 | 0.00 |
February | 0.423354E+09 | 0.103130E+10 | 0.570932E+09 | 0.228015E+09 | 0.342917E+09 | 0.00 | 0.00 |
March | 0.704779E+09 | 0.901814E+09 | 0.852082E+09 | 0.241868E+09 | 0.610214E+09 | 0.00 | 0.00 |
April | 0.108511E+10 | 0.562319E+09 | 0.104468E+10 | 0.368461E+09 | 0.676216E+09 | 0.00 | 0.00 |
May | 0.153186E+10 | 0.451107E+09 | 0.135127E+10 | 0.501276E+09 | 0.849989E+09 | 0.00 | 0.00 |
June | 0.176208E+10 | 0.341304E+09 | 0.144312E+10 | 0.550122E+09 | 0.892995E+09 | 0.00 | 0.00 |
July | 0.193870E+10 | 0.354102E+09 | 0.149143E+10 | 0.626785E+09 | 0.864644E+09 | 0.00 | 0.00 |
August | 0.157812E+10 | 0.390139E+09 | 0.125246E+10 | 0.499846E+09 | 0.752618E+09 | 0.00 | 0.00 |
September | 0.112348E+10 | 0.490485E+09 | 0.960616E+09 | 0.394965E+09 | 0.565651E+09 | 0.00 | 0.00 |
October | 0.717027E+09 | 0.648929E+09 | 0.713195E+09 | 0.287427E+09 | 0.425768E+09 | 0.00 | 0.00 |
November | 0.369214E+09 | 0.889653E+09 | 0.484202E+09 | 0.196180E+09 | 0.288022E+09 | 0.00 | 0.00 |
December | 0.155119E+09 | 0.137113E+10 | 0.344866E+09 | 0.115492E+09 | 0.229374E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115496E+11 | 0.908708E+10 | 0.108960E+11 | 0.413342E+10 | 0.676258E+10 | 0.00 | 0.00 |
Minimum of Months | 0.155119E+09 | 0.341304E+09 | 0.344866E+09 | 0.115492E+09 | 0.229374E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193870E+10 | 0.165480E+10 | 0.149143E+10 | 0.626785E+09 | 0.892995E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.266178E+10 | 0.165486E+11 | 0.783134E+09 | 0.321250E+09 | 0.461884E+09 | 0.00 | 0.00 |
February | 0.528636E+10 | 0.940618E+10 | 0.117191E+10 | 0.641490E+09 | 0.530417E+09 | 0.00 | 0.00 |
March | 0.109088E+11 | 0.755432E+10 | 0.213608E+10 | 0.101801E+10 | 0.111807E+10 | 0.00 | 0.00 |
April | 0.130472E+11 | 0.374001E+10 | 0.256619E+10 | 0.143638E+10 | 0.112981E+10 | 0.00 | 0.00 |
May | 0.177787E+11 | 0.264648E+10 | 0.340462E+10 | 0.194450E+10 | 0.146013E+10 | 0.00 | 0.00 |
June | 0.202576E+11 | 0.196128E+10 | 0.396860E+10 | 0.255039E+10 | 0.141821E+10 | 0.00 | 0.00 |
July | 0.221581E+11 | 0.269305E+10 | 0.424653E+10 | 0.297407E+10 | 0.127247E+10 | 0.00 | 0.00 |
August | 0.180706E+11 | 0.286157E+10 | 0.353621E+10 | 0.241340E+10 | 0.112281E+10 | 0.00 | 0.00 |
September | 0.117606E+11 | 0.274930E+10 | 0.237308E+10 | 0.150578E+10 | 0.867301E+09 | 0.00 | 0.00 |
October | 0.731037E+10 | 0.372184E+10 | 0.152038E+10 | 0.843121E+09 | 0.677261E+09 | 0.00 | 0.00 |
November | 0.380728E+10 | 0.685884E+10 | 0.885820E+09 | 0.431798E+09 | 0.454023E+09 | 0.00 | 0.00 |
December | 0.199979E+10 | 0.120512E+11 | 0.612598E+09 | 0.235267E+09 | 0.377331E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135047E+12 | 0.727927E+11 | 0.272052E+11 | 0.163155E+11 | 0.108897E+11 | 0.00 | 0.00 |
Minimum of Months | 0.199979E+10 | 0.196128E+10 | 0.612598E+09 | 0.235267E+09 | 0.377331E+09 | 0.00 | 0.00 |
Maximum of Months | 0.221581E+11 | 0.165486E+11 | 0.424653E+10 | 0.297407E+10 | 0.146013E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.106444E+10 | -974402309.5 | 0.00 | 0.00 | 744.00 | 0.00 | -90039331.9 | 59.95 | 0.00 | 0.00 |
February | 0.991552E+09 | -910485195.3 | 0.00 | 0.00 | 672.00 | 0.00 | -81066728.9 | 59.95 | 0.00 | 0.00 |
March | 0.114249E+10 | -0.105330E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -89189322.7 | 59.95 | 0.00 | 0.00 |
April | 0.102868E+10 | -943459134.6 | 0.00 | 0.00 | 720.00 | 0.00 | -85221972.4 | 59.95 | 0.00 | 0.00 |
May | 0.101324E+10 | -928303635.6 | 0.00 | 0.00 | 744.00 | 0.00 | -84936099.8 | 59.95 | 0.00 | 0.00 |
June | 0.944641E+09 | -868887581.9 | 0.00 | 0.00 | 720.00 | 0.00 | -75753596.7 | 59.95 | 0.00 | 0.00 |
July | 0.872481E+09 | -798041437.0 | 0.00 | 0.00 | 744.00 | 0.00 | -74439186.5 | 59.95 | 0.00 | 0.00 |
August | 0.913523E+09 | -838086847.1 | 0.00 | 0.00 | 744.00 | 0.00 | -75436436.4 | 59.95 | 0.00 | 0.00 |
September | 0.866238E+09 | -789621325.5 | 0.00 | 0.00 | 720.00 | 0.00 | -76616966.0 | 59.95 | 0.00 | 0.00 |
October | 0.913367E+09 | -827653079.5 | 0.00 | 0.00 | 744.00 | 0.00 | -85713627.7 | 59.95 | 0.00 | 0.00 |
November | 0.930147E+09 | -844102296.5 | 0.00 | 0.00 | 720.00 | 0.00 | -86044740.2 | 59.95 | 0.00 | 0.00 |
December | 0.102163E+10 | -931781465.9 | 0.00 | 0.00 | 744.00 | 0.00 | -89852447.3 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.117024E+11 | -0.107081E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -994310456.6 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.866238E+09 | -0.105330E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -90039331.9 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.114249E+10 | -789621325.5 | 0.00 | 0.00 | 744.00 | 0.00 | -74439186.5 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.94 | 0.88 | 03-JAN-11:30 | 114.96 | 8.44 | 0.00 | 31.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.94 | 0.88 | 02-FEB-10:20 | 121.19 | 8.91 | 0.00 | 35.83 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.91 | 0.88 | 02-MAR-08:50 | 224.98 | 11.96 | 0.00 | 161.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.91 | 0.88 | 01-APR-08:00 | 234.79 | 11.91 | 0.00 | 180.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.90 | 0.88 | 01-MAY-07:49 | 1046.17 | 13.12 | 18.67 | 251.33 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.91 | 0.88 | 01-JUN-13:39 | 3258.63 | 14.24 | 51.33 | 268.17 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.90 | 0.88 | 01-JUL-06:00 | 2569.11 | 13.85 | 33.83 | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.91 | 0.88 | 01-AUG-08:50 | 215.97 | 11.35 | 0.00 | 177.50 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.92 | 0.88 | 02-SEP-13:20 | 174.83 | 10.60 | 0.00 | 113.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.93 | 0.88 | 01-OCT-09:20 | 137.54 | 9.33 | 0.00 | 65.33 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.94 | 0.88 | 01-NOV-09:00 | 104.73 | 8.04 | 0.00 | 17.33 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.95 | 0.88 | 04-DEC-10:30 | 87.27 | 7.21 | 0.00 | 8.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.92 | 842.17 | 11.16 | 103.83 | 1564.50 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 226.83 | 0.90 | 0.88 | 87.27 | 7.21 | 0.00 | 8.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 434.17 | 0.95 | 0.88 | 3258.63 | 14.24 | 51.33 | 268.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.82 | 0.61 | 30-JAN-15:20 | 191.95 | 20.25 | 97.00 | 5.67 | 106.77 | 20.25 | 88.50 | 0.00 |
February | 275.00 | 0.79 | 0.61 | 07-FEB-15:30 | 304.43 | 22.92 | 141.17 | 43.00 | 131.34 | 21.11 | 125.83 | 0.33 |
March | 304.00 | 0.72 | 0.61 | 01-MAR-14:50 | 488.73 | 24.64 | 216.67 | 115.33 | 367.02 | 25.17 | 241.67 | 57.00 |
April | 325.17 | 0.72 | 0.61 | 01-APR-14:50 | 448.11 | 22.92 | 195.67 | 114.67 | 474.48 | 24.03 | 232.50 | 78.00 |
May | 385.83 | 0.71 | 0.61 | 01-MAY-14:39 | 362.26 | 22.14 | 236.83 | 145.83 | 594.96 | 23.28 | 281.00 | 103.17 |
June | 434.17 | 0.71 | 0.61 | 01-JUN-14:09 | 351.70 | 21.85 | 248.33 | 162.67 | 329.35 | 23.08 | 315.00 | 106.83 |
July | 417.33 | 0.71 | 0.61 | 01-JUL-14:30 | 360.66 | 22.19 | 237.00 | 158.50 | 498.25 | 23.30 | 297.50 | 114.83 |
August | 421.33 | 0.74 | 0.61 | 01-AUG-14:09 | 351.87 | 21.82 | 215.67 | 125.83 | 467.57 | 22.95 | 265.17 | 95.33 |
September | 352.17 | 0.75 | 0.61 | 01-SEP-14:00 | 532.31 | 23.83 | 193.00 | 103.83 | 468.80 | 24.93 | 223.33 | 63.33 |
October | 317.67 | 0.77 | 0.61 | 02-OCT-14:20 | 520.15 | 24.54 | 180.67 | 70.83 | 205.54 | 23.28 | 180.33 | 23.00 |
November | 269.50 | 0.81 | 0.61 | 01-NOV-15:09 | 292.51 | 23.41 | 135.17 | 31.50 | 108.88 | 20.33 | 106.50 | 0.00 |
December | 236.83 | 0.84 | 0.65 | 04-DEC-14:30 | 201.47 | 22.24 | 101.67 | 13.83 | 89.34 | 19.63 | 65.50 | 0.00 |
Annual Sum or Average | 3965.83 | 0.75 | 376.22 | 22.72 | 2198.83 | 1091.50 | 349.13 | 22.84 | 2422.83 | 641.83 | ||
Minimum of Months | 226.83 | 0.71 | 0.61 | 191.95 | 20.25 | 97.00 | 5.67 | 89.34 | 19.63 | 65.50 | 0.00 | |
Maximum of Months | 434.17 | 0.84 | 0.65 | 532.31 | 24.64 | 248.33 | 162.67 | 594.96 | 25.17 | 315.00 | 114.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102930E+11 | 25920.51 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.677731E+10 | 25920.51 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.614441E+10 | 25920.51 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.322074E+10 | 25920.51 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203455E+10 | 25920.51 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46221278.34 | 25920.51 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.316168E+09 | 25920.51 | 18-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154991E+10 | 25920.51 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.437037E+10 | 25920.51 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.757881E+10 | 25920.51 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.423315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102930E+11 | 25920.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.373435E+11 | 66298.55 | 03-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220129E+11 | 66298.55 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167105E+11 | 66298.55 | 03-MAR-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571920E+10 | 66298.55 | 15-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244644E+10 | 66298.55 | 08-MAY-05:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3228852.87 | 2922.03 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147639E+10 | 48742.60 | 12-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124482E+11 | 66298.55 | 13-NOV-01:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272785E+11 | 66298.55 | 01-DEC-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125439E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.373435E+11 | 66298.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156581E+12 | 153387.81 | 05-JAN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827404E+11 | 103619.40 | 04-FEB-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.540085E+11 | 107822.18 | 06-MAR-03:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.589931E+10 | 48076.49 | 29-APR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.471085E+10 | 40042.28 | 09-MAY-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268962E+09 | 13456.32 | 11-OCT-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.390823E+11 | 92416.36 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105548E+12 | 146664.56 | 31-DEC-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448839E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156581E+12 | 153387.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.194879E+09 | 0.194308E+09 | 4301.47 | 20-MAY-16:00 | 4301.47 | 0.00 |
June | 0.00 | 0.00 | 0.187954E+10 | 0.180571E+10 | 15684.57 | 26-JUN-05:03 | 10871.55 | 0.00 |
July | 0.00 | 0.00 | 0.460151E+10 | 0.444797E+10 | 17710.01 | 19-JUL-05:01 | 11590.82 | 0.00 |
August | 0.00 | 0.00 | 0.367590E+10 | 0.364682E+10 | 15684.82 | 08-AUG-05:01 | 14734.26 | 0.00 |
September | 0.00 | 0.00 | 0.123389E+10 | 0.113679E+10 | 16590.02 | 07-SEP-05:02 | 10639.07 | 0.00 |
October | 0.00 | 0.00 | 24413181.17 | 24413181.17 | 2445.22 | 18-OCT-16:00 | 2445.22 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116101E+11 | 0.112560E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.460151E+10 | 0.444797E+10 | 17710.01 | 14734.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.719636E+09 | 0.712699E+09 | 12970.79 | 30-JUN-17:45 | 12970.79 | 0.00 |
July | 0.00 | 0.00 | 0.440744E+10 | 0.432201E+10 | 37037.70 | 16-JUL-10:45 | 31458.48 | 0.00 |
August | 0.00 | 0.00 | 0.317669E+10 | 0.316728E+10 | 34853.54 | 08-AUG-20:05 | 34853.54 | 0.00 |
September | 0.00 | 0.00 | 0.789132E+09 | 0.731355E+09 | 21488.07 | 04-SEP-14:30 | 21488.07 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.909290E+10 | 0.893334E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.440744E+10 | 0.432201E+10 | 37037.70 | 34853.54 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102915E+10 | 0.08 | 398.12 | 01-JAN-00:03 | 0.09 |
February | 0.792582E+09 | 0.07 | 398.12 | 01-FEB-00:03 | 0.09 |
March | 0.750142E+09 | 0.06 | 398.12 | 01-MAR-00:05 | 0.09 |
April | 0.192564E+09 | 0.02 | 398.12 | 01-APR-00:10 | 0.09 |
May | 0.110598E+09 | 0.01 | 398.12 | 01-MAY-00:03 | 0.09 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 13615780.42 | 0.00 | 398.12 | 10-OCT-04:50 | 0.09 |
November | 0.470999E+09 | 0.04 | 398.12 | 10-NOV-02:40 | 0.09 |
December | 0.942487E+09 | 0.08 | 398.12 | 01-DEC-00:03 | 0.09 |
Annual Sum or Average | 0.430213E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102915E+10 | 0.08 | 398.12 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.124615E+10 | 0.69 | 1140.38 | 02-JAN-07:20 | 1.04 |
February | 0.110611E+10 | 0.57 | 1140.38 | 24-FEB-16:00 | 1.04 |
March | 0.127737E+10 | 0.52 | 1140.38 | 01-MAR-09:40 | 1.04 |
April | 0.116014E+10 | 0.43 | 1140.38 | 05-APR-12:10 | 1.04 |
May | 0.119837E+10 | 0.43 | 1140.38 | 01-MAY-07:10 | 1.04 |
June | 0.117602E+10 | 0.41 | 1140.38 | 03-JUN-10:50 | 1.03 |
July | 0.114682E+10 | 0.39 | 1140.38 | 27-JUL-06:03 | 1.03 |
August | 0.123218E+10 | 0.42 | 1140.38 | 01-AUG-08:30 | 1.03 |
September | 0.113858E+10 | 0.41 | 1140.38 | 01-SEP-07:40 | 1.03 |
October | 0.114777E+10 | 0.41 | 1140.38 | 06-OCT-16:40 | 1.03 |
November | 0.112729E+10 | 0.47 | 1140.38 | 17-NOV-10:00 | 1.04 |
December | 0.120523E+10 | 0.57 | 1140.38 | 01-DEC-08:20 | 1.04 |
Annual Sum or Average | 0.141620E+11 | 0.48 | |||
Minimum of Months | 0.110611E+10 | 0.39 | 1140.38 | 1.03 | |
Maximum of Months | 0.127737E+10 | 0.69 | 1140.38 | 1.04 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166876E+10 | 0.69 | 1940.20 | 03-JAN-06:01 | 1.01 |
February | 0.124959E+10 | 0.63 | 1940.20 | 01-FEB-00:03 | 1.01 |
March | 0.125481E+10 | 0.61 | 1940.20 | 03-MAR-04:33 | 1.01 |
April | 0.918064E+09 | 0.44 | 1940.20 | 15-APR-05:01 | 1.01 |
May | 0.864095E+09 | 0.31 | 1940.20 | 08-MAY-05:21 | 1.00 |
June | 0.799412E+09 | 0.24 | 776.08 | 22-JUN-15:00 | 0.60 |
July | 0.800920E+09 | 0.24 | 1940.20 | 17-JUL-17:08 | 1.00 |
August | 0.854758E+09 | 0.26 | 1940.20 | 07-AUG-17:10 | 1.00 |
September | 0.777295E+09 | 0.24 | 1126.00 | 04-SEP-15:05 | 0.76 |
October | 0.806881E+09 | 0.28 | 1426.43 | 12-OCT-05:01 | 1.00 |
November | 0.105616E+10 | 0.52 | 1940.20 | 13-NOV-01:42 | 1.01 |
December | 0.144111E+10 | 0.66 | 1940.20 | 01-DEC-04:42 | 1.01 |
Annual Sum or Average | 0.124919E+11 | 0.43 | |||
Minimum of Months | 0.777295E+09 | 0.24 | 776.08 | 0.60 | |
Maximum of Months | 0.166876E+10 | 0.69 | 1940.20 | 1.01 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124615E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.110611E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.127737E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.116014E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.124491E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.161251E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.221257E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.208710E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.142005E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115353E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.112729E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.120523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.168530E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110611E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.221257E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.166876E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.124959E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.125481E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.918064E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.864095E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.994020E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.195524E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.169494E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.986344E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.806881E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.105616E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.144111E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.148900E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.806881E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.195524E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.124615E+10 | 0.00 | 0.102930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110611E+10 | 0.00 | 0.677731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127737E+10 | 0.00 | 0.614441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116014E+10 | 0.00 | 0.322074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119837E+10 | 0.194879E+09 | 0.203455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117602E+10 | 0.187954E+10 | 46221278.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114682E+10 | 0.460151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123218E+10 | 0.367590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113858E+10 | 0.123389E+10 | 0.316168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114777E+10 | 24413181.17 | 0.154991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112729E+10 | 0.00 | 0.437037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120523E+10 | 0.00 | 0.757881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141620E+11 | 0.116101E+11 | 0.423315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127737E+10 | 0.460151E+10 | 0.102930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166876E+10 | 0.00 | 0.373435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124959E+10 | 0.00 | 0.220129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125481E+10 | 0.00 | 0.167105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.918064E+09 | 0.00 | 0.571920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.864095E+09 | 0.00 | 0.244644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.799412E+09 | 0.719636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.800920E+09 | 0.433376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.854758E+09 | 0.316393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.777295E+09 | 0.789132E+09 | 3228852.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.806881E+09 | 0.00 | 0.147639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105616E+10 | 0.00 | 0.124482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144111E+10 | 0.00 | 0.272785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124919E+11 | 0.900646E+10 | 0.125439E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.777295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166876E+10 | 0.433376E+10 | 0.373435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.124615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119837E+10 | 0.00 | 0.00 | 0.00 | 46538017.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117602E+10 | 0.00 | 0.00 | 0.00 | 0.436485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114682E+10 | 0.00 | 0.00 | 0.00 | 0.106575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123218E+10 | 0.00 | 0.00 | 0.00 | 0.854922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113858E+10 | 0.00 | 0.00 | 0.00 | 0.281470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114777E+10 | 0.00 | 0.00 | 0.00 | 5764161.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141620E+11 | 0.00 | 0.00 | 0.00 | 0.269093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127737E+10 | 0.00 | 0.00 | 0.00 | 0.106575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.918064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.864095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.799412E+09 | 0.00 | 0.00 | 0.00 | 0.194607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.800920E+09 | 0.00 | 0.00 | 0.00 | 0.115432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.854758E+09 | 0.00 | 0.00 | 0.00 | 0.840180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.777295E+09 | 0.00 | 0.00 | 0.00 | 0.209048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.806881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124919E+11 | 0.00 | 0.00 | 0.00 | 0.239815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.777295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166876E+10 | 0.00 | 0.00 | 0.00 | 0.115432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304415E+10 | 0.00 | 0.00 | 0.12 |
February | 25002646.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216749E+10 | 0.00 | 0.00 | 0.13 |
March | 6828981.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214685E+10 | 0.00 | 0.00 | 0.13 |
April | 0.181956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126919E+10 | 0.00 | 0.00 | 0.13 |
May | 0.400893E+09 | 48155.32 | 826717.30 | 210904.72 | 1298536.48 | 0.808575E+09 | 0.156535E+09 | 4898.64 | 0.18 |
June | 0.285151E+09 | 51486418.05 | 0.00 | 2072824.23 | 0.00 | 10252741.12 | 0.142331E+10 | 0.00 | 0.43 |
July | 7264944.09 | 0.120823E+09 | 0.00 | 5118545.54 | 0.00 | 0.00 | 0.151219E+10 | 0.00 | 0.48 |
August | 45265480.36 | 77034151.32 | 0.00 | 4416966.61 | 0.00 | 0.00 | 0.192443E+10 | 0.00 | 0.55 |
September | 0.482036E+09 | 36498042.27 | 0.00 | 2053717.59 | 0.00 | 0.102451E+09 | 0.119604E+10 | 0.00 | 0.36 |
October | 0.683713E+09 | 0.00 | 0.00 | 23829.00 | 0.00 | 0.615158E+09 | 43695985.03 | 0.00 | 0.14 |
November | 88956654.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162314E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253077E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.220707E+10 | 0.285890E+09 | 826717.30 | 13896787.69 | 1298536.48 | 0.143180E+11 | 0.625621E+10 | 4898.64 | 0.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.683713E+09 | 0.120823E+09 | 826717.30 | 5118545.54 | 1298536.48 | 0.304415E+10 | 0.192443E+10 | 4898.64 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.428508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937302E+10 | 0.00 | 0.00 | 0.17 |
February | 0.150396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506017E+10 | 0.00 | 0.00 | 0.17 |
March | 0.304668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296041E+10 | 0.00 | 0.00 | 0.19 |
April | 0.305670E+10 | 0.00 | 0.00 | 0.00 | 7104310.87 | 0.564339E+09 | 0.00 | 0.00 | 0.18 |
May | 0.298922E+10 | 0.00 | 0.00 | 0.00 | 32841638.01 | 0.204230E+09 | 0.00 | 0.00 | 0.18 |
June | 0.253392E+10 | 11389059.25 | 0.00 | 573919.41 | 32285579.01 | 0.00 | 0.251670E+09 | 0.00 | 0.20 |
July | 0.125195E+10 | 0.137805E+09 | 0.00 | 3759848.12 | 0.00 | 0.00 | 0.127449E+10 | 0.00 | 0.23 |
August | 0.210579E+10 | 80781653.11 | 0.00 | 1989449.37 | 0.00 | 0.00 | 0.768112E+09 | 0.00 | 0.22 |
September | 0.278158E+10 | 23205033.11 | 0.00 | 662154.71 | 4184755.32 | 0.00 | 0.281559E+09 | 0.00 | 0.20 |
October | 0.317762E+10 | 0.00 | 0.00 | 0.00 | 11791618.46 | 0.135583E+09 | 0.00 | 0.00 | 0.17 |
November | 0.250987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207605E+10 | 0.00 | 0.00 | 0.17 |
December | 0.127066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640038E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.266565E+11 | 0.253180E+09 | 0.00 | 6985371.62 | 88207901.67 | 0.267742E+11 | 0.257583E+10 | 0.00 | 0.19 |
Minimum of Months | 0.428508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.317762E+10 | 0.137805E+09 | 0.00 | 3759848.12 | 32841638.01 | 0.937302E+10 | 0.127449E+10 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:48
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.236301E+12 | 0.100167E+12 | 0.00 | 0.128457E+11 | 0.438302E+11 |
February | 0.389878E+12 | 0.594469E+11 | 0.00 | 0.875663E+10 | 0.249591E+11 |
March | 0.724451E+12 | 0.541516E+11 | 0.00 | 0.816077E+10 | 0.181277E+11 |
April | 0.793440E+12 | 0.261972E+11 | 0.00 | 0.506509E+10 | 0.462135E+10 |
May | 0.109201E+13 | 0.262068E+11 | 0.00 | 0.452465E+10 | 0.283214E+10 |
June | 0.122768E+13 | 0.250961E+11 | 0.00 | 0.441201E+10 | 0.325028E+10 |
July | 0.125755E+13 | 0.241891E+11 | 0.00 | 0.380737E+10 | 0.112290E+11 |
August | 0.105194E+13 | 0.306022E+11 | 0.00 | 0.470151E+10 | 0.854769E+10 |
September | 0.749107E+12 | 0.350272E+11 | 0.00 | 0.478608E+10 | 0.264554E+10 |
October | 0.449733E+12 | 0.282541E+11 | 0.00 | 0.464401E+10 | 0.130116E+10 |
November | 0.211636E+12 | 0.438087E+11 | 0.00 | 0.629801E+10 | 0.132082E+11 |
December | 0.124564E+12 | 0.701877E+11 | 0.00 | 0.102018E+11 | 0.310194E+11 |
Annual Sum or Average | 0.830829E+13 | 0.523335E+12 | 0.00 | 0.782036E+11 | 0.165572E+12 |
Minimum of Months | 0.124564E+12 | 0.241891E+11 | 0.00 | 0.380737E+10 | 0.130116E+10 |
Maximum of Months | 0.125755E+13 | 0.100167E+12 | 0.00 | 0.128457E+11 | 0.438302E+11 |