Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:19:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 533.31 | 110.30 | 110.30 |
Net Site Energy | 533.31 | 110.30 | 110.30 |
Total Source Energy | 1688.98 | 349.31 | 349.31 |
Net Source Energy | 1688.98 | 349.31 | 349.31 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 166.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 78.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 83.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 533.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 166.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 78.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 37.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 46.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 166.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 78.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 83.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 7.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 28.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 53.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 110.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 28.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 53.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 110.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 533.306 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 533.306 | 100.00 |
Total On-Site and Utility Electric Sources | 533.306 | 100.00 |
Total Electricity End Uses | 533.306 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 65.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3005.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE HP COOLING COIL | PSZ-FINE STORAGE HP COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE_SUPPHEATCOIL | PSZ-FINE STORAGE_SUPPHEATCOIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | PSZ-OFFICE HP COOLING COIL | PSZ-FINE STORAGE HP COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 119.93 |
Skylight-Roof Ratio [%] | 2.61 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | - | - | - | - | - | - | - | - | - | - | - | 03-MAR-12:30 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28744.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4429.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7539.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 271.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 51019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28744.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4429.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5234.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 271.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 527.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 247.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 263.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1688.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 109.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 51.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 54.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 349.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 109.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 51.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 54.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 349.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.22 |
ZONE2 FINE STORAGE DIRECT AIR | 3.53 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39959.00 |
PSZ-OFFICE_SUPPHEATCOIL | 26889.86 |
PSZ-FINE STORAGE_SUPPHEATCOIL | 87605.18 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.00 | 1.000000 | 1.22 |
PSZ-FINE STORAGE | 3.53 | 3.53 | 3.53 | 3.53 | 3.53 | 3.53 | 1.00 | 1.00 | 3.53 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.22 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 3.53 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.22 | 1352.72 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.53 | 6027.70 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.22 | 1.22 | 1.22 | 0.806384 | 26231.00 | 18016.21 | 40.00 | 26889.86 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 3.53 | 3.53 | 3.53 | 2.33 | 87605.18 | 58695.47 | 40.00 | 87605.18 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE HP COOLING COIL | 1.22 | 0.610897 | 0.814527 | 26231.00 | 13115.50 | 0.749480 | 0.749480 |
PSZ-FINE STORAGE HP COOLING COIL | 3.53 | 1.76 | 2.35 | 87605.18 | 43802.59 | 0.701080 | 0.701080 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | Design Size Speed 2 Gross Rated Heating Capacity [W] | Design Size Speed 1 Gross Rated Heating Capacity [W] | Design Size Resistive Defrost Heater Capacity | |
PSZ-OFFICE HEATING COIL | 1.22 | 0.610897 | 26889.86 | 13444.93 | 0.000000 |
PSZ-FINE STORAGE HEATING COIL | 3.53 | 1.76 | 87605.17 | 43802.58 | 0.000000 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.7173 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 200.0 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.394 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5000E-02 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53311453E-11 | 0.59398160E-16 | 0.15345153E-15 | 0.0000000 |
5 | 1 | -5.2159564 | 0.46378490E-04 | -0.22332804E-04 | 0.68713370E-11 |
6 | 0 | 5.9333026 | 0.71729982 | 0.71736853 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.33466332E-12 | 0.89461943E-14 | -0.12859024E-13 | 0.20877214E-15 |
13 | 3 | -0.22871403E-03 | 0.15053116E-05 | -0.31975464E-04 | 0.68322840E-13 |
14 | 2 | 1.3386772 | 0.41030944E-01 | 0.83718830 | -0.43809927E-04 |
15 | 1 | -7.7424045 | 1.2165027 | -15.097018 | 0.25560053 |
16 | 0 | 8.5066984 | 0.84520726 | 16.362604 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 200.00000 | 200.00000 | 200.00000 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12859024E-13 | 0.89461943E-14 | 0.33466332E-12 | 0.20877214E-15 |
85 | 3 | -0.31975464E-04 | 0.15053116E-05 | -0.22871403E-03 | 0.68322840E-13 |
86 | 2 | 0.83718830 | 0.41030944E-01 | 1.3386772 | -0.43809927E-04 |
87 | 1 | -15.097018 | 1.2165027 | -7.7424045 | 0.25560053 |
88 | 0 | 16.362604 | 0.84520726 | 8.5066984 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.219 | 34 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.220 | ||
2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.219 | 35 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.220 | ||
3 | NONRESWINDOW_U_0.503_SHGC_EAST_0.219 | 36 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.220 | ||
4 | NONRESWINDOW_U_0.503_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.220 | ||
5 | SKYLIGHT_U_0.7_SHGC_0.3 | 38 | 1 | VerySmooth | 3.979 | 3.979 | 1.000 | 0.303 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93472E-002 | 0.13026 | 0.64157 | 0.64157 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93472E-002 | 0.13026 | 0.64157 | 0.64157 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93472E-002 | 0.13026 | 0.64157 | 0.64157 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93472E-002 | 0.13026 | 0.64157 | 0.64157 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.17728 | 0.47032 | 0.47032 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.40661E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.838 | 0.300 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.799 | 0.390 | 0.214 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 3.833E-002 | 1.618E-004 | 2.498E-004 | 0.137 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.195 | 1.399E-004 | 8.913E-005 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 1.834 | 5.723E-004 | 3.738E-004 | 0.187 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.8411E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9362E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0191E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1160E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6499E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0182E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0157E-004 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7234E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5858E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6259E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3567E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7562E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4258E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5968E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4476E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5357E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6348E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2401E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0770E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2865E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.1171E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1461E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0436E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1182E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.2605E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8801E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.6353E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0709E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8368E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4272E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3611E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3609E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7287E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3091E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8438E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4181E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3072E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1745E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1206E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8484E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1601E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6953E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3172E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7777E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.2210E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7245E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8883E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6707E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9891E-004 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7969E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2579E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8966E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0303E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7708E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4746E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6794E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3657E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6028E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0042E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7639E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6535E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3164E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1327E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8762E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1993E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.9114E-005 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2090E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2956E-005 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8315E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9602E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6038E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4693E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2081E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7120E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2857E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8540E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3459E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4077E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6538E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6639E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9796E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6972E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6733E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5172E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8480E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.3825E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4325E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9096E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5756E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1567E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.5957E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8073E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.2814E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1859E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1412E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0087E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7311E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6555E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4028E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.8046E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1907E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2233E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1055E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2128E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5615E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7276E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2706E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2491E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0659E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0512E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8879E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2630E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2319E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6623E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8587E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9474E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6057E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5533E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4434E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7783E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7745E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2962E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3609E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1094E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1936E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0279E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8550E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9597E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7482E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9692E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3056E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1442E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3931E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2304E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1328E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4494E-005 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2522E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6815E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2291E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8510E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1087E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3329E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9357E-005 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4958E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2853E-005 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4901E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9651E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4251E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6039E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4172E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7689E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5024E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2500E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0171E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3137E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5398E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0982E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3737E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8937E-005 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2943E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2639E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3507E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5540E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5569E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0537E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0844E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7691E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0170E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4637E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0228E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6910E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8481E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2636E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7626E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3116E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7153E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1996E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7278E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3886E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4660E-005 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6110E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2182E-005 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1948E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9944E-005 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1601E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2276E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8410E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4955E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9391E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5080E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8033E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9473E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8103E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8449E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9843E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9749E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3272E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3594E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2493E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8179E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5729E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7739E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9170E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9610E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8052E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8121E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3899E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0224E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5114E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7085E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5891E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.1255E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8450E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8133E-005 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1149E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6646E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1052E-003 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5581E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4653E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1115E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5258E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4758E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3665E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6699E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8926E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9094E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4553E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7925E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2917E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6301E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7821E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8219E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2950E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4185E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1172E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3421E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4615E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1775E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7771E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4939E-005 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0208E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7972E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9053E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.2559E-005 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1037E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9576E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2842E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6124E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6735E-004 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9116E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8980E-005 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8288E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6217E-005 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3315E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4395E-005 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9607E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3234E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4623E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9125E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2421E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3522E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5972E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4104E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6327E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7664E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4270E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4585E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3803E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2011E-005 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5224E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0177E-005 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3802E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7219E-005 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4909E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8807E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0862E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1553E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0282E-005 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0024E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1881E-005 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9195E-005 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6287E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2743E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5747E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2154E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9029E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8697E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2490E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2083E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1436E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4279E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1842E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3677E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7999E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9707E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2436E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5727E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8700E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8814E-005 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4630E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3007E-005 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1051E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6308E-005 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2148E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.8689E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5634E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4590E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1392E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2801E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 2.9957E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7285E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0610E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.5523E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3289E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1738E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.7272E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0476E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4302E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0256E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3194E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.6476E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9978E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.0188E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.6018E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.3853E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.2240E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.1699E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.8630E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.7253E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.0016E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.0439E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.6036E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.2406E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.2217E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.1699E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.8630E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12369.56433 | 14843.47720 | 1.01816 | 1.22179 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 42.21800 | 1.07808E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 4668.71772 | 5602.46127 | 0.13073 | 0.15688 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 12.70000 | 9.15345E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 45817.91860 | 54981.50232 | 2.93988 | 3.52786 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 5184.26228 | 6221.11473 | 0.12265 | 0.42471 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 12.70000 | 9.15345E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 42.80000 | 1.07818E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | 00:10:00 | 12.70000 | 9.15345E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 19855.12 | 1.22179 | 1.22179 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 4634.08 | 0.15688 | 0.15688 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 70984.97 | 3.52786 | 3.52786 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 14023.03 | 0.42471 | 0.42471 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22179 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.52786 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Electric | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39959.00499 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22179 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22179 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22179 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22179 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22179 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.22179 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.52786 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.52786 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.52786 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.52786 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.52786 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.52786 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.22179 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.52786 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22179 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22179 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1352.71979 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22179 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22179 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22179 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80638 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22179 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61090 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.81453 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26231.00000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13115.50000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74948 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74948 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26231.00000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18016.20861 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 26889.86359 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
45 | Coil:Heating:DX:MultiSpeed | PSZ-OFFICE HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 1.22179 |
46 | Coil:Heating:DX:MultiSpeed | PSZ-OFFICE HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61090 |
47 | Coil:Heating:DX:MultiSpeed | PSZ-OFFICE HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 26889.86359 |
48 | Coil:Heating:DX:MultiSpeed | PSZ-OFFICE HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 13444.93180 |
49 | Coil:Heating:DX:MultiSpeed | PSZ-OFFICE HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
50 | Coil:Heating:Electric | PSZ-OFFICE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 26889.86359 |
51 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.52786 |
52 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
53 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.52786 |
54 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 6027.69640 |
55 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.52786 |
56 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.52786 |
57 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.52786 |
58 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.32839 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.52786 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.76393 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.35191 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 87605.18000 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 43802.59000 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 87605.18000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58695.46942 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 87605.17825 |
70 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
71 | Coil:Heating:DX:MultiSpeed | PSZ-FINE STORAGE HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 3.52786 |
72 | Coil:Heating:DX:MultiSpeed | PSZ-FINE STORAGE HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.76393 |
73 | Coil:Heating:DX:MultiSpeed | PSZ-FINE STORAGE HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 87605.16514 |
74 | Coil:Heating:DX:MultiSpeed | PSZ-FINE STORAGE HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 43802.58257 |
75 | Coil:Heating:DX:MultiSpeed | PSZ-FINE STORAGE HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
76 | Coil:Heating:Electric | PSZ-FINE STORAGE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 87605.17825 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE HP COOLING COIL | 25282.0 | 11.80 | 11.53 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE HP COOLING COIL | 84863.0 | 10.89 | 10.64 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:MultiSpeed | PSZ-OFFICE HEATING COIL | 27867.3 | 15382.5 | 8.07 | 2 |
2 | Coil:Heating:DX:MultiSpeed | PSZ-FINE STORAGE HEATING COIL | 90439.5 | 49764.9 | 7.66 | 2 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.4925720477E-002 | 2.0969032857E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 4.6321429541E-002 | 3.3415226410E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.5348952911E-002 | 4.5970264089E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8497.03 | 487.73 | 0.00 | -146.1 | 733.63 | 9572.32 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.653 | 0.717 | 3204.84 | 3105.72 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.503_SHGC_WEST_0.219 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.860 | 0.220 | 0.242 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.503_SHGC_WEST_0.219 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.860 | 0.220 | 0.242 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.219 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.860 | 0.220 | 0.242 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.219 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.860 | 0.220 | 0.242 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 137.59 | 5.146 | 0.471 | 0.381 | |||||||||||||||||
North Total or Average | 6.51 | 2.860 | 0.220 | 0.242 | |||||||||||||||||
Non-North Total or Average | 131.09 | 5.260 | 0.483 | 0.388 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 31.82 | 0.0000 | Y | 9.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 16.96 | 0.0000 | Y | 32.95 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 16.55 | 0.0000 | Y | 35.37 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 78.18 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 41.85 | 41.85 | 0.97 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.85 | 62.85 | 50.80 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.85 | 48.85 | 10.01 | |
Exterior Lighting Total | 5520.82 | 61.78 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26231.00 | 19659.61 | 6571.39 | 0.75 | 3.74 | |||
PSZ-FINE STORAGE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 87605.18 | 61418.24 | 26186.94 | 0.70 | 3.32 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE HP COOLING COIL | 25282.0 | 11.80 | 11.53 | ||||
PSZ-FINE STORAGE HP COOLING COIL | 84863.0 | 10.89 | 10.64 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
PSZ-OFFICE HEATING COIL | Coil:Heating:DX:MultiSpeed | 27867.3 | 15382.5 | 8.07 | 2 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:DX:MultiSpeed | 90439.5 | 49764.9 | 7.66 | 2 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Electric | 39959.00 | 1.00 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:DX:MultiSpeed | 26889.86 | 3.55 | |
PSZ-OFFICE_SUPPHEATCOIL | Coil:Heating:Electric | 26889.86 | 1.00 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:DX:MultiSpeed | 87605.17 | 3.49 | |
PSZ-FINE STORAGE_SUPPHEATCOIL | Coil:Heating:Electric | 87605.18 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.22 | 1352.72 | 1107.16 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.53 | 6027.70 | 1708.60 | 1.00 | 1.19 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12369.56 | 14843.48 | 62.66 | 1.018 | 1.222 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 23.90 | 23.90 | 0.00830 | 42.22 | 0.01078 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 45817.92 | 54981.50 | 39.46 | 2.940 | 3.528 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00837 | 42.80 | 0.01078 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 0.00 | 42.78 | 0.01086 | 42.80 | 0.01078 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 4668.72 | 5602.46 | 23.65 | 0.131 | 0.157 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00907 | 12.70 | 0.00915 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 5184.26 | 6221.11 | 4.46 | 0.123 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00855 | 12.70 | 0.00915 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | 00:10:00 | 10.00 | 11.65 | 0.00853 | 12.70 | 0.00915 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.22 | 1.22 | 0.16 | 0.16 | 1.2218 | 1.2218 | 1.2218 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.53 | 3.53 | 0.42 | 0.42 | 3.5279 | 3.5279 | 3.5279 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:ELECTRIC | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 39959.00 | 39959.00 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 26231.000 | 19659.610 | 1.221790 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 13115.50 | 12138.98 | 0.814527 | 26.34 | 17.21 | 0.00850353 | 12.00 | 11.25 | 0.00800000 | 42.31 | 0.01078097 | 23.73 | 12.5576 | 23.90 | 0.00829538 | 44.9205 | 12365.52 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 26889.864 | 26889.864 | 1.221794 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 13444.93 | 13444.93 | 0.610897 | 20.27 | 15.54 | 0.00907587 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 16.7434 | 21.10 | 0.00906878 | 58.1354 | 4668.72 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-OFFICE | 26889.864 | 26889.864 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26889.86 | 26889.86 | 1.221794 | 20.27 | 15.54 | 0.00907587 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.3717 | 21.10 | 0.00906878 | 58.1354 | 4668.72 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 87605.180 | 61418.240 | 3.527860 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 43802.59 | 40341.54 | 2.351907 | 30.03 | 18.57 | 0.00866166 | 12.00 | 11.25 | 0.00800000 | 42.80 | 0.01078182 | 23.86 | 18.0582 | 26.70 | 0.00837149 | 38.3741 | 45817.92 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 87605.178 | 87605.178 | 3.527861 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 43802.58 | 43802.58 | 1.763930 | 15.22 | 13.52 | 0.00895827 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 24.0776 | 15.56 | 0.00893156 | 81.0841 | 5018.95 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ-FINE STORAGE | 87605.178 | 87605.178 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 87605.18 | 87605.18 | 3.527861 | 15.22 | 13.52 | 0.00895827 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.0388 | 15.56 | 0.00893156 | 81.0841 | 5018.95 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17571482 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 39959.00 | 39959.00 | 1.0000 | 1.17571482 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39959.00 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26231.000 | 19659.610 | 1.221790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6476 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.221794 | 1.47054500 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | Sensible | 13115.50 | 12138.98 | 1.0000 | 0.98036021 | 0.814527 | 26.34 | 17.21 | 0.00850353 | 48153.0 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13115.50 | 42.31 | 0.01078097 | 23.73 | 0.10228463 | 12.5576 | 23.90 | 0.00829538 | 23.90 | 0.00829538 | 44.9205 | 12365.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 26889.864 | 26889.864 | 1.221794 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.221794 | 1.47054500 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 13444.93 | 13444.93 | 1.0000 | 0.73527250 | 0.610897 | 20.27 | 15.54 | 0.00907587 | 43410.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13444.93 | 12.70 | 0.00915345 | 12.70 | 0.10228463 | 16.7434 | 20.96 | 0.00906878 | 21.10 | 0.00906878 | 58.1354 | 4668.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26889.864 | 26889.864 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.221794 | 1.47054500 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26889.86 | 26889.86 | 1.0000 | 1.47054500 | 1.221794 | 20.27 | 15.54 | 0.00907587 | 43410.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26889.86 | 12.70 | 0.00915345 | 12.70 | 0.10228463 | 8.3717 | 20.96 | 0.00906878 | 21.10 | 0.00906878 | 58.1354 | 4668.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 87605.180 | 61418.240 | 3.527860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9416 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.527861 | 4.24611523 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 43802.59 | 40341.54 | 1.0000 | 2.83074306 | 2.351907 | 30.03 | 18.57 | 0.00866166 | 52318.4 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43802.59 | 42.80 | 0.01078182 | 23.86 | 0.42471127 | 18.0582 | 26.70 | 0.00837149 | 26.70 | 0.00837149 | 38.3741 | 45817.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 87605.178 | 87605.178 | 3.527861 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.527861 | 4.24611523 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 43802.58 | 43802.58 | 1.0000 | 2.12305761 | 1.763930 | 15.22 | 13.52 | 0.00895827 | 37947.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43802.58 | 12.70 | 0.00915345 | 12.70 | 0.42471127 | 24.0776 | 15.56 | 0.00893156 | 15.56 | 0.00893156 | 81.0841 | 5018.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87605.178 | 87605.178 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.527861 | 4.24611523 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 87605.18 | 87605.18 | 1.0000 | 4.24611523 | 3.527861 | 15.22 | 13.52 | 0.00895827 | 37947.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87605.18 | 12.70 | 0.00915345 | 12.70 | 0.42471127 | 12.0388 | 15.56 | 0.00893156 | 15.56 | 0.00893156 | 81.0841 | 5018.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3177.67 | 425.33 | 261.50 |
ZONE2 FINE STORAGE | 3442.67 | 2732.50 | 2591.17 |
ZONE3 BULK STORAGE | 3396.17 | 3174.33 | 2986.00 |
Facility | 3452.17 | 3213.50 | 3005.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 71.50 | 0.00 | 65.83 |
ZONE2 FINE STORAGE | 0.00 | 464.00 | 0.00 | 8.67 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 526.83 | 0.00 | 65.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.354 | 0.348 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.498 | 0.100 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.096 | 0.000 | 2.196 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1268960.91 | 0.00 | 1268960.91 | 1497664.61 | 2766625.52 | 3225648.14 | 5388.45 | 3371.55 | 0.00 | 135.36 |
ZONE2 FINE STORAGE | 5935408.10 | 0.00 | 5935408.10 | 2375440.95 | 8310849.05 | 13393694.68 | 5398.83 | 3361.17 | 0.00 | 1837.65 |
ZONE3 BULK STORAGE | 0.00 | 0.57E+09 | 0.57E+09 | 21068267.77 | 0.59E+09 | 30805497.77 | 4229.30 | 7.92 | 4522.79 | 5105.89 |
Total Facility | 7204369.01 | 0.57E+09 | 0.57E+09 | 24941373.33 | 0.60E+09 | 47424840.58 | 6763.09 | 3402.74 | 4522.79 | 5106.31 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0963 | 0.0000 | 0.0963 | 0.0946 | 0.1909 | 0.1023 | 264.45 | 3371.55 | 0.00 |
ZONE2 FINE STORAGE | 0.3914 | 0.0000 | 0.3914 | 0.0786 | 0.4700 | 0.4247 | 301.99 | 3334.01 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 19.8732 | 19.8732 | 0.8785 | 20.7517 | 0.9768 | 1542.12 | 3.92 | 2089.96 |
Total Facility | 0.4877 | 19.8732 | 20.3609 | 1.0516 | 21.4125 | 1.5038 | 1639.09 | 3371.58 | 2089.96 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1838290.08 | 0.00 | 1838290.08 | 3225648.14 | 5366.82 | 1.85 | 3391.33 | 132.71 |
PSZ-FINE STORAGE | 8598284.75 | 0.00 | 8598284.75 | 13393694.68 | 5299.75 | 8.66 | 3451.59 | 1837.21 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1395 | 0.0000 | 0.1395 | 0.1023 | 245.45 | 1.47 | 3389.09 |
PSZ-FINE STORAGE | 0.5670 | 0.0000 | 0.5670 | 0.4247 | 299.78 | 0.43 | 3335.79 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3655.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1441 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6024 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 448 |
Defaulted Fields | 420 |
Fields with Defaults | 1220 |
Autosized Fields | 53 |
Autosizable Fields | 123 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 533.31 | 1069.86 | 01-JAN-10:00 | 51019.61 | 10-AUG-16:00 |
Electricity:Building | 251.76 | 1069.86 | 01-JAN-09:10 | 19728.63 | 13-NOV-17:00 |
Electricity:Zone:ZONE1 OFFICE | 39.03 | 520.87 | 01-JAN-00:10 | 2831.88 | 15-MAR-07:10 |
Electricity:SpaceType:GENERAL | 214.68 | 1069.86 | 01-JAN-09:10 | 18077.14 | 14-MAR-08:10 |
InteriorLights:Electricity | 78.18 | 599.99 | 01-JAN-09:10 | 8041.97 | 14-MAR-08:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 9.86 | 51.00 | 01-JAN-00:10 | 996.83 | 15-MAR-07:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 78.18 | 599.99 | 01-JAN-09:10 | 8041.97 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity | 78.18 | 599.99 | 01-JAN-09:10 | 8041.97 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 9.86 | 51.00 | 01-JAN-00:10 | 996.83 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 78.18 | 599.99 | 01-JAN-09:10 | 8041.97 | 14-MAR-08:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 32.95 | 299.97 | 01-JAN-00:10 | 3519.92 | 14-MAR-08:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 32.95 | 299.97 | 01-JAN-00:10 | 3519.92 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 32.95 | 299.97 | 01-JAN-00:10 | 3519.92 | 14-MAR-08:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 179.78 | 249.02 | 01-JAN-09:10 | 13869.11 | 18-NOV-17:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 35.37 | 249.02 | 01-JAN-09:10 | 3550.39 | 14-MAR-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 35.37 | 249.02 | 01-JAN-09:10 | 3550.39 | 14-MAR-08:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 83.09 | 0.00 | 01-JAN-00:10 | 7598.40 | 10-AUG-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 37.07 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-FEB-14:30 |
Ventilation (simple):Fans:Electricity | 37.07 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-FEB-14:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 37.07 | 0.00 | 01-JAN-00:10 | 2305.29 | 04-FEB-14:30 |
ElectricityPurchased:Facility | 533.31 | 1069.86 | 01-JAN-10:00 | 51019.61 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 533.31 | 1069.86 | 01-JAN-10:00 | 51019.61 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 533.31 | 1069.86 | 01-JAN-10:00 | 51019.61 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 533.31 | 1069.86 | 01-JAN-10:00 | 51019.61 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 533.31 | 1069.86 | 01-JAN-10:00 | 51019.61 | 10-AUG-16:00 |
ElectricityNet:Plant | 533.31 | 1069.86 | 01-JAN-10:00 | 51019.61 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 533.31 | 1069.86 | 01-JAN-10:00 | 51019.61 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 533.31 | 1069.86 | 01-JAN-10:00 | 51019.61 | 10-AUG-16:00 |
Electricity:HVAC | 212.69 | 0.00 | 01-JAN-00:10 | 34355.80 | 10-AUG-16:10 |
General:Fans:Electricity | 46.01 | 0.00 | 01-JAN-00:10 | 5293.10 | 10-AUG-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 640.22 | 02-JAN-07:20 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 640.22 | 02-JAN-07:20 |
Cooling:Electricity | 166.67 | 0.00 | 01-JAN-00:10 | 29062.70 | 10-AUG-16:10 |
General:Cooling:Electricity | 166.67 | 0.00 | 01-JAN-00:10 | 29062.70 | 10-AUG-16:10 |
ExteriorLights:Electricity | 61.78 | 0.00 | 01-JAN-07:10 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.78 | 0.00 | 01-JAN-07:10 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 7.08 | 0.00 | 01-JAN-00:10 | 1137.39 | 12-JAN-12:50 |
WaterSystems:Electricity | 7.08 | 0.00 | 01-JAN-00:10 | 1137.39 | 12-JAN-12:50 |
Water Heater:WaterSystems:Electricity | 7.08 | 0.00 | 01-JAN-00:10 | 1137.39 | 12-JAN-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-MAR-12:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-MAR-12:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-MAR-12:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-MAR-12:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-MAR-12:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-MAR-12:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-MAR-12:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 03-MAR-12:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 910.36 | 0.00 | 01-JAN-00:10 | 137363.63 | 10-AUG-16:10 |
EnergyTransfer:Building | 343.38 | 0.00 | 01-JAN-00:10 | 49707.98 | 16-AUG-12:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 91.74 | 0.00 | 01-JAN-00:10 | 16062.92 | 21-JUL-12:00 |
Heating:EnergyTransfer | 0.38 | 0.00 | 01-JAN-00:10 | 1683.84 | 02-JAN-07:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.01 | 0.00 | 01-JAN-00:10 | 1683.84 | 02-JAN-07:20 |
General:Heating:EnergyTransfer | 0.38 | 0.00 | 01-JAN-00:10 | 1683.84 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.01 | 0.00 | 01-JAN-00:10 | 1683.84 | 02-JAN-07:20 |
Cooling:EnergyTransfer | 343.00 | 0.00 | 01-JAN-00:10 | 49707.98 | 16-AUG-12:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 91.73 | 0.00 | 01-JAN-00:10 | 16062.92 | 21-JUL-12:00 |
General:Cooling:EnergyTransfer | 343.00 | 0.00 | 01-JAN-00:10 | 49707.98 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 91.73 | 0.00 | 01-JAN-00:10 | 16062.92 | 21-JUL-12:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 251.65 | 0.00 | 01-JAN-00:10 | 37959.84 | 30-JUL-14:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.37 | 0.00 | 01-JAN-00:10 | 1653.03 | 01-MAR-08:30 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.37 | 0.00 | 01-JAN-00:10 | 1653.03 | 01-MAR-08:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 251.28 | 0.00 | 01-JAN-00:10 | 37959.84 | 30-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 251.28 | 0.00 | 01-JAN-00:10 | 37959.84 | 30-JUL-14:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 566.98 | 0.00 | 01-JAN-00:10 | 90503.42 | 10-AUG-16:10 |
HeatingCoils:EnergyTransfer | 0.01 | 0.00 | 01-JAN-00:10 | 2136.54 | 02-JAN-07:20 |
CoolingCoils:EnergyTransfer | 566.96 | 0.00 | 01-JAN-00:10 | 90503.42 | 10-AUG-16:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.010 | -91.725 | 0.000 | 0.000 | 9.123 | 9.861 | 29.165 | 12.311 | 0.000 | 9.984 | 26.151 | 0.000 | -2.817 | 0.000 | -2.061 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.369 | -251.277 | 0.000 | 0.000 | 17.434 | 32.946 | 0.000 | 36.587 | 0.000 | 11.490 | 165.455 | 0.000 | -8.491 | 0.000 | -4.514 | -0.002 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20.420 | 35.368 | 107.344 | 788.116 | 0.000 | 54.828 | 0.011 | 0.000 | -187.401 | 0.000 | -535.994 | -282.681 |
Total Facility | 0.000 | 0.000 | 0.379 | -343.002 | 0.000 | 0.000 | 46.976 | 78.176 | 136.508 | 837.014 | 0.000 | 76.303 | 191.617 | 0.000 | -198.710 | 0.000 | -542.570 | -282.683 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 20-OCT-05:01 | 0.00 | 0.00 | 0.00 | -25363.18 | 0.00 | 0.00 | 71.98 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 25242.38 | 0.00 | -262.96 | 0.00 | -289.73 | 0.00 |
ZONE2 FINE STORAGE | 29-OCT-14:02 | 0.00 | 0.00 | 0.00 | -72271.44 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 2916.16 | 0.00 | 1180.91 | 67874.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-05:01 | 0.00 | 0.00 | 0.00 | -90878.51 | 0.00 | 0.00 | 368.96 | 849.01 | 2600.55 | 14.94 | 0.00 | 611.04 | 185075.85 | 0.00 | -11008.50 | 0.00 | -87633.33 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 03-JAN-07:15 | 0.00 | 0.00 | 2039.65 | 0.00 | 0.00 | 0.00 | 224.86 | 546.93 | 917.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -377.68 | 0.00 | -3049.64 | -301.64 |
ZONE2 FINE STORAGE | 29-APR-06:07 | 0.00 | 0.00 | 1944.93 | 0.00 | 0.00 | 0.00 | 340.91 | 2593.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -440.20 | 0.00 | -31.76 | -4406.97 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JAN-07:15 | -1620.25 | 1620.25 | 2039.65 | -1620.25 | 0.00 | 0.00 | 2112.28 | 6163.30 | 2967.56 | 0.00 | 0.00 | 0.00 | 13490.62 | 0.00 | -21625.93 | 0.00 | -3527.24 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2218 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2218 | 0.0837 | 1.0000 | Not calculated | 0.1023 | 0.0837 | ||
PSZ-FINE STORAGE | 3.5279 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.5279 | 0.1204 | 1.0000 | Not calculated | 0.4247 | 0.1204 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2218 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2218 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0837 | ||
PSZ-FINE STORAGE | 3.5279 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 3.5279 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1204 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2218 | 1.2218 | 1.2218 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.5279 | 3.5279 | 3.5279 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2218 | 1.2218 | 1.2218 | 1.2218 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.5279 | 3.5279 | 3.5279 | 3.5279 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2218 | 1.2218 | 1.2218 | No | 0.1023 | 0.6520 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.5279 | 3.5279 | 3.5279 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2218 | 1.2218 | 1.2218 | 1.2218 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.5279 | 3.5279 | 3.5279 | 3.5279 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 65.83 |
Number of hours not met | 65.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 640.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 166.67 | 29062.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 78.18 | 8041.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.78 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 37.07 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 46.01 | 5293.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 7.08 | 1137.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 533.31 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 533.31 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 16.17 |
Space Heating | 0.00 |
Space Cooling | 34.47 |
Fans (All) | 17.18 |
Service Water Heating | 1.46 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 110.30 |
Subtotal | 110.30 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.66 |
Space Heating | 0.00 |
Space Cooling | 31.25 |
Fans (All) | 15.58 |
Service Water Heating | 1.33 |
Receptacle Equipment | 25.60 |
Miscellaneous | 11.58 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 5289.67 | 3418.50 | 51.83 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 3623.17 | 5136.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 2112.83 | 2731.50 | 1962.67 | 1904.50 | 48.50 |
Min | 2112.83 | 2731.50 | 0.00 | 0.00 | 0.00 |
Max | 5289.67 | 5136.83 | 1962.67 | 1904.50 | 48.50 |
Average | 3675.22 | 3762.28 | 671.50 | 634.83 | 16.17 |
Sum | 11025.67 | 11286.83 | 2014.50 | 1904.50 | 48.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33025.33 | 1.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 24577.50 | 58141.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 28524.00 | 68420.33 | 46704.33 | 45118.17 | 2426.17 |
Min | 24577.50 | 1.67 | 0.00 | 0.00 | 0.00 |
Max | 33025.33 | 68420.33 | 46704.33 | 45118.17 | 2426.17 |
Average | 28708.94 | 42187.83 | 15568.11 | 15039.39 | 808.72 |
Sum | 86126.83 | 126563.50 | 46704.33 | 45118.17 | 2426.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 4584.33 | 4173.17 | 2.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2418.83 | 6341.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1528.50 | 4064.33 | 1415.83 | 1407.67 | 343.67 |
Min | 1528.50 | 4064.33 | 0.00 | 0.00 | 0.00 |
Max | 4584.33 | 6341.17 | 1415.83 | 1407.67 | 343.67 |
Average | 2843.89 | 4859.56 | 472.78 | 469.22 | 114.56 |
Sum | 8531.67 | 14578.67 | 1418.33 | 1407.67 | 343.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32024.00 | 1003.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 17847.50 | 64871.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 19144.33 | 98452.33 | 31424.67 | 30326.83 | 11844.83 |
Min | 17847.50 | 1003.00 | 0.00 | 0.00 | 0.00 |
Max | 32024.00 | 98452.33 | 31424.67 | 30326.83 | 11844.83 |
Average | 23005.28 | 54775.61 | 10474.89 | 10108.94 | 3948.28 |
Sum | 69015.83 | 164326.83 | 31424.67 | 30326.83 | 11844.83 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297048E+10 | 18713.74 | 30-JAN-06:02 | 20.03 | 17.43 | 0.630183E+09 | 769.02 | 31-JAN-16:00 | 23.00 | 17.31 |
February | 0.381115E+10 | 21157.07 | 10-FEB-06:02 | 19.82 | 12.70 | 0.582600E+09 | 769.04 | 08-FEB-16:30 | 19.82 | 12.70 |
March | 0.565770E+10 | 24591.02 | 28-MAR-05:01 | 25.67 | 14.74 | 0.685146E+09 | 769.04 | 14-MAR-14:09 | 25.67 | 14.74 |
April | 0.672991E+10 | 24899.24 | 26-APR-05:01 | 23.17 | 12.12 | 0.635037E+09 | 769.05 | 28-APR-12:09 | 41.12 | 20.13 |
May | 0.933543E+10 | 24517.87 | 11-MAY-05:01 | 28.00 | 16.07 | 0.660689E+09 | 769.09 | 31-MAY-12:09 | 39.63 | 26.77 |
June | 0.101750E+11 | 23651.98 | 16-JUN-05:01 | 28.17 | 20.46 | 0.660779E+09 | 769.10 | 26-JUN-12:09 | 38.97 | 25.98 |
July | 0.108415E+11 | 22841.39 | 22-JUL-05:01 | 31.00 | 23.08 | 0.635493E+09 | 771.66 | 17-JUL-12:09 | 31.00 | 23.08 |
August | 0.119922E+11 | 21010.34 | 07-AUG-05:01 | 32.82 | 23.16 | 0.686424E+09 | 780.19 | 10-AUG-12:09 | 42.17 | 28.04 |
September | 0.999145E+10 | 20874.07 | 05-SEP-05:01 | 30.17 | 24.66 | 0.635405E+09 | 769.09 | 06-SEP-12:09 | 37.13 | 27.40 |
October | 0.880283E+10 | 25363.19 | 20-OCT-05:01 | 23.17 | 16.23 | 0.635310E+09 | 769.08 | 02-OCT-15:00 | 23.17 | 16.23 |
November | 0.682248E+10 | 23096.67 | 18-NOV-06:01 | 20.08 | 16.00 | 0.609727E+09 | 769.07 | 01-NOV-13:50 | 20.08 | 16.00 |
December | 0.459558E+10 | 22928.61 | 13-DEC-06:02 | 15.02 | 12.69 | 0.634053E+09 | 769.04 | 05-DEC-13:50 | 15.02 | 12.69 |
Annual Sum or Average | 0.917257E+11 | 0.769085E+10 | ||||||||
Minimum of Months | 0.297048E+10 | 18713.74 | 15.02 | 12.12 | 0.582600E+09 | 769.02 | 15.02 | 12.69 | ||
Maximum of Months | 0.119922E+11 | 25363.19 | 32.82 | 24.66 | 0.686424E+09 | 780.19 | 42.17 | 28.04 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.676248E+09 | 4482.92 | 31-JAN-13:50 | 23.15 | 16.15 | 0.167379E+10 | 2250.43 | 14-JAN-16:19 | 23.15 | 16.15 |
February | 0.251543E+10 | 25071.42 | 05-FEB-14:25 | 31.80 | 19.36 | 0.163968E+10 | 2246.90 | 06-FEB-14:30 | 32.25 | 17.25 |
March | 0.711436E+10 | 59654.08 | 26-MAR-15:23 | 32.20 | 18.57 | 0.196741E+10 | 2246.91 | 21-MAR-12:50 | 32.20 | 18.57 |
April | 0.145457E+11 | 67487.08 | 30-APR-12:02 | 37.02 | 20.74 | 0.184930E+10 | 2246.94 | 07-APR-14:20 | 37.02 | 20.74 |
May | 0.300301E+11 | 71024.14 | 07-MAY-16:23 | 34.05 | 21.67 | 0.192891E+10 | 2247.00 | 31-MAY-14:30 | 38.00 | 26.49 |
June | 0.350102E+11 | 67419.22 | 15-JUN-17:06 | 37.67 | 20.98 | 0.192885E+10 | 2247.04 | 28-JUN-13:39 | 37.83 | 26.90 |
July | 0.427442E+11 | 70668.03 | 04-JUL-09:43 | 35.98 | 22.33 | 0.185485E+10 | 2247.07 | 21-JUL-12:30 | 44.15 | 25.11 |
August | 0.448647E+11 | 68027.11 | 06-AUG-08:23 | 36.50 | 23.32 | 0.200330E+10 | 2247.07 | 15-AUG-13:50 | 39.97 | 23.04 |
September | 0.339015E+11 | 64173.17 | 04-SEP-12:22 | 40.80 | 24.42 | 0.185470E+10 | 2247.05 | 14-SEP-13:20 | 38.60 | 25.42 |
October | 0.246712E+11 | 72275.93 | 29-OCT-14:02 | 33.67 | 19.63 | 0.185483E+10 | 2246.98 | 17-OCT-14:50 | 33.67 | 19.63 |
November | 0.120058E+11 | 62483.85 | 05-NOV-11:43 | 33.72 | 17.44 | 0.177713E+10 | 2246.96 | 06-NOV-15:20 | 31.80 | 21.81 |
December | 0.319973E+10 | 28679.08 | 03-DEC-13:25 | 28.40 | 19.50 | 0.179865E+10 | 2246.80 | 05-DEC-11:00 | 27.00 | 21.53 |
Annual Sum or Average | 0.251279E+12 | 0.221314E+11 | ||||||||
Minimum of Months | 0.676248E+09 | 4482.92 | 23.15 | 16.15 | 0.163968E+10 | 2246.80 | 23.15 | 16.15 | ||
Maximum of Months | 0.448647E+11 | 72275.93 | 40.80 | 24.42 | 0.200330E+10 | 2250.43 | 44.15 | 26.90 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.369336E+10 | 5701.20 | 28-JAN-14:30 | 27.00 | 16.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 0.398251E+10 | 7299.46 | 06-FEB-15:09 | 32.32 | 17.34 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 | 0.528024E+10 | 9097.65 | 27-MAR-10:00 | 38.00 | 18.84 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.560074E+10 | 9097.65 | 24-APR-12:09 | 37.07 | 17.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 | 23.56 | 0.701971E+10 | 9097.65 | 04-MAY-09:00 | 37.40 | 18.18 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 | 0.728372E+10 | 9097.65 | 01-JUN-08:00 | 37.00 | 22.08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 | 0.726003E+10 | 9097.65 | 01-JUL-09:39 | 36.80 | 26.55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.787897E+10 | 9097.65 | 01-AUG-08:50 | 36.33 | 24.56 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 | 0.690795E+10 | 9097.65 | 01-SEP-10:09 | 36.08 | 24.95 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.621922E+10 | 9097.65 | 02-OCT-12:09 | 36.12 | 19.21 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 | 0.508426E+10 | 7943.42 | 01-NOV-14:09 | 32.83 | 26.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 | 0.437021E+10 | 6354.33 | 01-DEC-14:39 | 28.00 | 18.15 |
Annual Sum or Average | 0.00 | 0.705809E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.369336E+10 | 5701.20 | 27.00 | 16.03 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.787897E+10 | 9097.65 | 38.00 | 26.55 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9242617.30 | 2039.63 | 03-JAN-07:15 | 12.73 |
February | 303261.07 | 219.93 | 24-FEB-07:10 | 19.17 |
March | 230868.22 | 298.17 | 09-MAR-07:10 | 20.17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 114968.72 | 191.61 | 27-DEC-07:10 | 20.92 |
Annual Sum or Average | 9891715.30 | |||
Minimum of Months | 0.00 | 0.00 | 12.73 | |
Maximum of Months | 9242617.30 | 2039.63 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258677E+09 | 1536.33 | 17-JAN-12:20 | 25.07 |
February | 36098435.78 | 1506.68 | 15-FEB-08:00 | 23.20 |
March | 27913794.26 | 1653.03 | 01-MAR-08:30 | 26.00 |
April | 1826441.61 | 1944.89 | 29-APR-06:07 | 25.25 |
May | 1156456.74 | 1251.87 | 16-MAY-06:04 | 23.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 508639.33 | 1425.90 | 30-SEP-06:05 | 24.10 |
October | 2459539.72 | 1201.38 | 19-OCT-06:10 | 24.08 |
November | 797493.87 | 1010.79 | 25-NOV-07:10 | 24.70 |
December | 39182948.12 | 1382.96 | 23-DEC-17:30 | 24.60 |
Annual Sum or Average | 0.368620E+09 | |||
Minimum of Months | 0.00 | 0.00 | 23.20 | |
Maximum of Months | 0.258677E+09 | 1944.89 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.863820E+09 | 970.49 | 09-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.762443E+09 | 966.11 | 09-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.877693E+09 | 996.83 | 15-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.811814E+09 | 974.75 | 18-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.823032E+09 | 897.80 | 23-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.803450E+09 | 904.50 | 08-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.787971E+09 | 957.67 | 20-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.845452E+09 | 930.20 | 29-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.796383E+09 | 941.44 | 06-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.814739E+09 | 957.92 | 31-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.803339E+09 | 959.49 | 29-NOV-08:09 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.870630E+09 | 985.89 | 15-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.986076E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.762443E+09 | 897.80 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.877693E+09 | 996.83 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.296332E+10 | 3220.61 | 30-JAN-15:00 | 0.00 | 0.00 |
February | 0.258590E+10 | 3149.87 | 09-FEB-16:00 | 0.00 | 0.00 |
March | 0.288698E+10 | 3519.92 | 14-MAR-08:09 | 0.00 | 0.00 |
April | 0.262239E+10 | 3200.09 | 18-APR-08:09 | 0.00 | 0.00 |
May | 0.268837E+10 | 2980.71 | 10-MAY-07:10 | 0.00 | 0.00 |
June | 0.264788E+10 | 2867.63 | 30-JUN-07:10 | 0.00 | 0.00 |
July | 0.260675E+10 | 3062.64 | 20-JUL-07:10 | 0.00 | 0.00 |
August | 0.275752E+10 | 2989.29 | 29-AUG-07:10 | 0.00 | 0.00 |
September | 0.263403E+10 | 3051.59 | 26-SEP-07:10 | 0.00 | 0.00 |
October | 0.276216E+10 | 3136.08 | 30-OCT-07:10 | 0.00 | 0.00 |
November | 0.277806E+10 | 3269.12 | 29-NOV-15:00 | 0.00 | 0.00 |
December | 0.301303E+10 | 3400.52 | 15-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.329464E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.258590E+10 | 2867.63 | 0.00 | 0.00 | |
Maximum of Months | 0.301303E+10 | 3519.92 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313439E+10 | 3334.06 | 03-JAN-16:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.277898E+10 | 3253.28 | 09-FEB-16:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.311683E+10 | 3550.39 | 14-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.283441E+10 | 3210.77 | 18-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.287292E+10 | 2670.15 | 01-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.282075E+10 | 2788.70 | 08-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.279791E+10 | 3009.73 | 20-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.297706E+10 | 2966.04 | 29-AUG-06:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.286063E+10 | 2988.27 | 21-SEP-06:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.298766E+10 | 3116.57 | 31-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.298750E+10 | 3424.08 | 29-NOV-16:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.319942E+10 | 3464.84 | 09-DEC-16:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353685E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.277898E+10 | 2670.15 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.319942E+10 | 3550.39 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.863820E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8107034.69 | 0.597703E+09 |
February | 0.127628E+10 | 0.762443E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87192366.43 | 0.441115E+09 |
March | 0.149825E+10 | 0.877693E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306972E+09 | 0.299459E+09 |
April | 0.138726E+10 | 0.811814E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577440E+09 | 0.127480E+09 |
May | 0.144276E+10 | 0.823032E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124639E+10 | 19598226.00 |
June | 0.144276E+10 | 0.803450E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150788E+10 | 3318288.09 |
July | 0.138726E+10 | 0.787971E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164645E+10 | 17437.56 |
August | 0.149825E+10 | 0.845452E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187874E+10 | 90.65 |
September | 0.138726E+10 | 0.796383E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130036E+10 | 3774590.10 |
October | 0.138726E+10 | 0.814739E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908793E+09 | 21413536.30 |
November | 0.133177E+10 | 0.803339E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447445E+09 | 0.147960E+09 |
December | 0.138726E+10 | 0.870630E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68503634.22 | 0.399643E+09 |
Annual Sum or Average | 0.168137E+11 | 0.986076E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998428E+10 | 0.206148E+10 |
Minimum of Months | 0.127628E+10 | 0.762443E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8107034.69 | 90.65 |
Maximum of Months | 0.149825E+10 | 0.877693E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187874E+10 | 0.597703E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.296332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744864.51 | 0.997984E+09 |
February | 0.300332E+10 | 0.258590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45788310.70 | 0.110499E+10 |
March | 0.352563E+10 | 0.288698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172310E+09 | 0.721845E+09 |
April | 0.326447E+10 | 0.262239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471684E+09 | 0.334312E+09 |
May | 0.339505E+10 | 0.268837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138428E+10 | 46866531.95 |
June | 0.339505E+10 | 0.264788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182145E+10 | 11282028.51 |
July | 0.326447E+10 | 0.260675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239085E+10 | 0.00 |
August | 0.352563E+10 | 0.275752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242118E+10 | 0.00 |
September | 0.326447E+10 | 0.263403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161986E+10 | 9312385.96 |
October | 0.326447E+10 | 0.276216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901257E+09 | 83705517.34 |
November | 0.313390E+10 | 0.277806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249395E+09 | 0.343370E+09 |
December | 0.326447E+10 | 0.301303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11497157.98 | 0.860550E+09 |
Annual Sum or Average | 0.395654E+11 | 0.329464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114903E+11 | 0.451422E+10 |
Minimum of Months | 0.300332E+10 | 0.258590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744864.51 | 0.00 |
Maximum of Months | 0.352563E+10 | 0.301303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242118E+10 | 0.110499E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.313439E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4734025.15 | 0.706081E+10 |
February | 0.690763E+10 | 0.277898E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81723343.21 | 0.932631E+10 |
March | 0.810895E+10 | 0.311683E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265637E+09 | 0.800752E+10 |
April | 0.750829E+10 | 0.283441E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77416519.66 | 0.489537E+10 |
May | 0.780862E+10 | 0.287292E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239860E+09 | 0.173881E+10 |
June | 0.780862E+10 | 0.282075E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246403E+09 | 0.157980E+10 |
July | 0.750829E+10 | 0.279791E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234122E+09 | 0.124186E+10 |
August | 0.810895E+10 | 0.297706E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191006E+09 | 0.141917E+10 |
September | 0.750829E+10 | 0.286063E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118550E+09 | 0.145379E+10 |
October | 0.750829E+10 | 0.298766E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41676225.87 | 0.237828E+10 |
November | 0.720796E+10 | 0.298750E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3025143.01 | 0.450379E+10 |
December | 0.750829E+10 | 0.319942E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8132651.64 | 0.759467E+10 |
Annual Sum or Average | 0.910005E+11 | 0.353685E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151229E+10 | 0.512002E+11 |
Minimum of Months | 0.690763E+10 | 0.277898E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3025143.01 | 0.124186E+10 |
Maximum of Months | 0.810895E+10 | 0.319942E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265637E+09 | 0.932631E+10 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 970.49 | 09-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1249.56 | 23-JAN-13:00 | 4266.73 | 19-JAN-07:03 |
February | 1680.92 | 01-FEB-08:09 | 966.11 | 09-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2504.78 | 07-FEB-13:00 | 3912.81 | 13-FEB-07:03 |
March | 1680.92 | 01-MAR-08:09 | 996.83 | 15-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4857.53 | 27-MAR-11:10 | 3315.62 | 07-MAR-07:05 |
April | 1680.92 | 01-APR-07:10 | 974.75 | 18-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5980.64 | 28-APR-12:00 | 2497.33 | 05-APR-06:40 |
May | 1680.92 | 01-MAY-07:10 | 897.80 | 23-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5715.39 | 09-MAY-12:00 | 1233.90 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 904.50 | 08-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6433.68 | 09-JUN-16:10 | 235.00 | 07-JUN-05:01 |
July | 1680.92 | 01-JUL-07:10 | 957.67 | 20-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7161.30 | 21-JUL-12:00 | 4.08 | 03-JUL-04:00 |
August | 1680.92 | 01-AUG-07:10 | 930.20 | 29-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7345.02 | 16-AUG-12:00 | 0.15 | 31-AUG-04:00 |
September | 1680.92 | 01-SEP-07:10 | 941.44 | 06-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5686.43 | 05-SEP-12:00 | 310.23 | 25-SEP-05:01 |
October | 1680.92 | 02-OCT-07:10 | 957.92 | 31-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4670.03 | 04-OCT-12:00 | 699.95 | 30-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 959.49 | 29-NOV-08:09 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3016.36 | 01-NOV-16:10 | 2565.81 | 22-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 985.89 | 15-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.18 | 01-DEC-13:00 | 3615.25 | 26-DEC-07:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 897.80 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1249.56 | 0.15 | |||||
Maximum of Months | 1680.92 | 996.83 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 7345.02 | 4266.73 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3220.61 | 30-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.32 | 23-JAN-14:00 | 1821.29 | 19-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 3149.87 | 09-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.08 | 05-FEB-15:10 | 2194.56 | 10-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 3519.92 | 14-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2367.57 | 01-MAR-16:10 | 1713.17 | 25-MAR-09:00 |
April | 3955.50 | 01-APR-07:10 | 3200.09 | 18-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3251.75 | 28-APR-15:10 | 1090.67 | 04-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 2980.71 | 10-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8833.64 | 21-MAY-12:51 | 588.77 | 01-MAY-07:10 |
June | 3955.50 | 01-JUN-07:10 | 2867.63 | 30-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4582.81 | 09-JUN-15:40 | 401.24 | 07-JUN-06:05 |
July | 3955.50 | 01-JUL-07:10 | 3062.64 | 20-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4593.41 | 14-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 3955.50 | 01-AUG-07:10 | 2989.29 | 29-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3925.29 | 10-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 3955.50 | 01-SEP-07:10 | 3051.59 | 26-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3361.56 | 02-SEP-16:00 | 275.46 | 25-SEP-05:00 |
October | 3955.50 | 02-OCT-07:10 | 3136.08 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3579.32 | 19-OCT-15:10 | 767.00 | 21-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 3269.12 | 29-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.99 | 01-NOV-15:10 | 1020.81 | 22-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 3400.52 | 15-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.36 | 10-DEC-12:50 | 1499.75 | 16-DEC-16:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 2867.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.32 | 0.00 | ||||
Maximum of Months | 3955.50 | 3519.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8833.64 | 2194.56 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3334.06 | 03-JAN-16:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1385.33 | 23-JAN-13:10 | 12510.50 | 19-JAN-09:50 |
February | 9097.65 | 01-FEB-08:09 | 3253.28 | 09-FEB-16:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3807.69 | 05-FEB-12:00 | 18917.99 | 10-FEB-15:00 |
March | 9097.65 | 01-MAR-08:09 | 3550.39 | 14-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10452.68 | 01-MAR-11:00 | 29670.90 | 25-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3210.77 | 18-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2534.30 | 25-APR-07:53 | 8569.65 | 04-APR-07:10 |
May | 9097.65 | 01-MAY-07:10 | 2670.15 | 01-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4410.12 | 22-MAY-07:53 | 6885.47 | 01-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 2788.70 | 08-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2571.96 | 09-JUN-15:00 | 4767.52 | 07-JUN-06:10 |
July | 9097.65 | 01-JUL-07:10 | 3009.73 | 20-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3041.28 | 15-JUL-09:55 | 3006.08 | 16-JUL-16:52 |
August | 9097.65 | 01-AUG-07:10 | 2966.04 | 29-AUG-06:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3998.49 | 16-AUG-10:53 | 3830.80 | 10-AUG-20:53 |
September | 9097.65 | 01-SEP-07:10 | 2988.27 | 21-SEP-06:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1694.11 | 26-SEP-11:00 | 4238.56 | 23-SEP-07:10 |
October | 9097.65 | 02-OCT-07:10 | 3116.57 | 31-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2739.53 | 19-OCT-09:53 | 7911.85 | 21-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 3424.08 | 29-NOV-16:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 662.15 | 19-NOV-19:00 | 6598.21 | 20-NOV-16:30 |
December | 9097.65 | 01-DEC-08:09 | 3464.84 | 09-DEC-16:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.29 | 10-DEC-11:55 | 20991.82 | 15-DEC-12:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2670.15 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 662.15 | 3006.08 | |||||
Maximum of Months | 9097.65 | 3550.39 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10452.68 | 29670.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18713.74 | 30-JAN-06:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.51 |
February | 21157.07 | 10-FEB-06:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.33 |
March | 24591.02 | 28-MAR-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.58 |
April | 24899.24 | 26-APR-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.81 |
May | 24517.87 | 11-MAY-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 | 0.00 |
June | 23651.98 | 16-JUN-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 21.44 | 0.00 |
July | 22841.39 | 22-JUL-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 51.59 | 0.00 |
August | 21010.34 | 07-AUG-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 235.28 | 0.00 |
September | 20874.07 | 05-SEP-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 53.03 | 0.00 |
October | 25363.19 | 20-OCT-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.73 |
November | 23096.67 | 18-NOV-06:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.26 |
December | 22928.61 | 13-DEC-06:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18713.74 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25363.19 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 235.28 | 613.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4482.92 | 31-JAN-13:50 | 3955.50 | 1924.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.24 |
February | 25071.42 | 05-FEB-14:25 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.47 | 0.00 |
March | 59654.08 | 26-MAR-15:23 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 839.38 | 0.00 |
April | 67487.08 | 30-APR-12:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.43 | 0.00 |
May | 71024.14 | 07-MAY-16:23 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.88 | 0.00 |
June | 67419.22 | 15-JUN-17:06 | 0.00 | 1783.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1608.33 | 0.00 |
July | 70668.03 | 04-JUL-09:43 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.16 | 0.00 |
August | 68027.11 | 06-AUG-08:23 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.88 | 0.00 |
September | 64173.17 | 04-SEP-12:22 | 0.00 | 1499.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1516.89 | 0.00 |
October | 72275.93 | 29-OCT-14:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.91 | 0.00 |
November | 62483.85 | 05-NOV-11:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.17 | 0.00 |
December | 28679.08 | 03-DEC-13:25 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4482.92 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72275.93 | 3955.50 | 1924.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1608.33 | 160.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.37 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2656.54 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1928.35 |
April | 0.00 | 01-APR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1837.64 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1060.50 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.32 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.61 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.76 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.74 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1350.52 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3313.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | |
Maximum of Months | 0.00 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3313.44 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.290868E+11 | 23595.08 | 30-JAN-15:00 | 0.00 | 0.00 |
February | 0.275721E+11 | 29901.34 | 07-FEB-13:30 | 0.00 | 0.00 |
March | 0.339559E+11 | 33194.76 | 27-MAR-12:09 | 0.00 | 0.00 |
April | 0.372862E+11 | 37200.15 | 28-APR-12:09 | 0.00 | 0.00 |
May | 0.501862E+11 | 40815.87 | 30-MAY-14:00 | 0.00 | 0.00 |
June | 0.554698E+11 | 44862.27 | 09-JUN-15:09 | 0.00 | 0.00 |
July | 0.623855E+11 | 47539.17 | 20-JUL-13:30 | 0.00 | 0.00 |
August | 0.665072E+11 | 51019.61 | 10-AUG-15:00 | 0.00 | 0.00 |
September | 0.555397E+11 | 44142.50 | 07-SEP-13:30 | 0.00 | 0.00 |
October | 0.473882E+11 | 38813.92 | 07-OCT-13:39 | 0.00 | 0.00 |
November | 0.366341E+11 | 35691.66 | 01-NOV-13:00 | 0.00 | 0.00 |
December | 0.312940E+11 | 28856.27 | 04-DEC-13:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.533306E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.275721E+11 | 23595.08 | 0.00 | 0.00 | |
Maximum of Months | 0.665072E+11 | 51019.61 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.696153E+10 | 0.609812E+10 | 0.112984E+11 | 0.00 | 0.292391E+10 | 0.00 | 3942515.77 | 0.109845E+10 | 0.00 | 0.00 | 0.00 | 0.702477E+09 | 0.00 |
February | 0.612732E+10 | 0.521477E+10 | 0.103734E+11 | 0.00 | 0.283012E+10 | 0.00 | 0.00 | 0.239906E+10 | 0.00 | 0.00 | 0.00 | 0.627429E+09 | 0.00 |
March | 0.688149E+10 | 0.534618E+10 | 0.121089E+11 | 0.00 | 0.385381E+10 | 0.00 | 0.00 | 0.508201E+10 | 0.00 | 0.00 | 0.00 | 0.683460E+09 | 0.00 |
April | 0.626861E+10 | 0.471938E+10 | 0.112578E+11 | 0.00 | 0.532621E+10 | 0.00 | 0.00 | 0.913342E+10 | 0.00 | 0.00 | 0.00 | 0.580796E+09 | 0.00 |
May | 0.638432E+10 | 0.451144E+10 | 0.117000E+11 | 0.00 | 0.911614E+10 | 0.00 | 0.00 | 0.179283E+11 | 0.00 | 0.00 | 0.00 | 0.546055E+09 | 0.00 |
June | 0.627208E+10 | 0.419601E+10 | 0.116594E+11 | 0.00 | 0.102417E+11 | 0.00 | 0.00 | 0.226000E+11 | 0.00 | 0.00 | 0.00 | 0.500692E+09 | 0.00 |
July | 0.619263E+10 | 0.439881E+10 | 0.112984E+11 | 0.00 | 0.115265E+11 | 0.00 | 0.00 | 0.284940E+11 | 0.00 | 0.00 | 0.00 | 0.475183E+09 | 0.00 |
August | 0.658003E+10 | 0.471350E+10 | 0.121016E+11 | 0.00 | 0.119150E+11 | 0.00 | 0.00 | 0.306727E+11 | 0.00 | 0.00 | 0.00 | 0.524402E+09 | 0.00 |
September | 0.629105E+10 | 0.497444E+10 | 0.112504E+11 | 0.00 | 0.100155E+11 | 0.00 | 0.00 | 0.224744E+11 | 0.00 | 0.00 | 0.00 | 0.534026E+09 | 0.00 |
October | 0.656456E+10 | 0.559131E+10 | 0.113057E+11 | 0.00 | 0.784567E+10 | 0.00 | 0.00 | 0.154872E+11 | 0.00 | 0.00 | 0.00 | 0.593667E+09 | 0.00 |
November | 0.656890E+10 | 0.579925E+10 | 0.108562E+11 | 0.00 | 0.450316E+10 | 0.00 | 0.00 | 0.828325E+10 | 0.00 | 0.00 | 0.00 | 0.623379E+09 | 0.00 |
December | 0.708308E+10 | 0.621406E+10 | 0.112984E+11 | 0.00 | 0.298907E+10 | 0.00 | 0.00 | 0.302081E+10 | 0.00 | 0.00 | 0.00 | 0.688618E+09 | 0.00 |
Annual Sum or Average | 0.781756E+11 | 0.617773E+11 | 0.136508E+12 | 0.00 | 0.830868E+11 | 0.00 | 3942515.77 | 0.166673E+12 | 0.00 | 0.00 | 0.00 | 0.708018E+10 | 0.00 |
Minimum of Months | 0.612732E+10 | 0.419601E+10 | 0.103734E+11 | 0.00 | 0.283012E+10 | 0.00 | 0.00 | 0.109845E+10 | 0.00 | 0.00 | 0.00 | 0.475183E+09 | 0.00 |
Maximum of Months | 0.708308E+10 | 0.621406E+10 | 0.121089E+11 | 0.00 | 0.119150E+11 | 0.00 | 3942515.77 | 0.306727E+11 | 0.00 | 0.00 | 0.00 | 0.702477E+09 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 7288.69 | 04-JAN-16:00 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2952.17 | 13-JAN-13:39 | 0.00 | 640.22 | 02-JAN-07:19 |
February | 7369.26 | 09-FEB-16:00 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 5257.46 | 04-FEB-14:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8041.97 | 14-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 5455.57 | 27-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7333.10 | 18-APR-07:10 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 5702.36 | 28-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 6420.02 | 10-MAY-07:10 | 5520.82 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 5909.78 | 31-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 6226.26 | 08-JUN-07:10 | 5520.82 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 6566.10 | 09-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7030.03 | 20-JUL-07:10 | 5520.82 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 6866.53 | 20-JUL-13:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 6664.14 | 29-AUG-07:10 | 5520.82 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 7598.40 | 10-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 6863.85 | 26-SEP-07:10 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 6359.65 | 07-SEP-11:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7209.39 | 31-OCT-07:10 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 5700.36 | 05-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7606.99 | 29-NOV-16:00 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 5567.62 | 01-NOV-11:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7698.72 | 09-DEC-16:00 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 5257.46 | 01-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6226.26 | 5520.82 | 10035.17 | 0.00 | 2952.17 | 0.00 | 0.00 | |||||
Maximum of Months | 8041.97 | 5520.82 | 10035.17 | 0.00 | 7598.40 | 0.00 | 640.22 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3842.65 | 23-JAN-13:00 | 0.00 | 0.00 | 0.00 | 1137.39 | 12-JAN-12:50 | 0.00 |
February | 8872.61 | 07-FEB-13:50 | 0.00 | 0.00 | 0.00 | 1126.51 | 02-FEB-12:09 | 0.00 |
March | 13054.56 | 27-MAR-11:00 | 0.00 | 0.00 | 0.00 | 1061.33 | 01-MAR-12:39 | 0.00 |
April | 18174.39 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 981.76 | 01-APR-11:39 | 0.00 |
May | 21014.19 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 888.11 | 01-MAY-11:20 | 0.00 |
June | 23781.46 | 09-JUN-16:10 | 0.00 | 0.00 | 0.00 | 770.76 | 01-JUN-11:30 | 0.00 |
July | 25415.73 | 21-JUL-11:00 | 0.00 | 0.00 | 0.00 | 764.52 | 27-JUL-11:50 | 0.00 |
August | 29062.70 | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | 813.79 | 31-AUG-11:09 | 0.00 |
September | 22968.64 | 07-SEP-11:00 | 0.00 | 0.00 | 0.00 | 905.57 | 29-SEP-11:20 | 0.00 |
October | 17995.67 | 07-OCT-13:39 | 0.00 | 0.00 | 0.00 | 985.23 | 31-OCT-11:00 | 0.00 |
November | 15029.23 | 01-NOV-11:00 | 0.00 | 0.00 | 0.00 | 1063.63 | 30-NOV-12:39 | 0.00 |
December | 7914.49 | 04-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1136.30 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3842.65 | 0.00 | 0.00 | 0.00 | 764.52 | 0.00 | ||
Maximum of Months | 29062.70 | 0.00 | 0.00 | 0.00 | 1137.39 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23595.08 | 30-JAN-15:00 | 7167.29 | 10035.17 | 0.00 | 0.00 | 2952.17 | 0.00 | 0.00 | 2457.86 | 0.00 |
February | 29901.34 | 07-FEB-13:30 | 4775.55 | 10035.17 | 0.00 | 0.00 | 5257.46 | 0.00 | 0.00 | 8848.95 | 0.00 |
March | 33194.76 | 27-MAR-12:09 | 4835.05 | 10035.17 | 0.00 | 0.00 | 5257.46 | 0.00 | 0.00 | 12222.64 | 0.00 |
April | 37200.15 | 28-APR-12:09 | 4843.15 | 10035.17 | 0.00 | 0.00 | 5309.46 | 0.00 | 0.00 | 16288.83 | 0.00 |
May | 40815.87 | 30-MAY-14:00 | 4657.79 | 10035.17 | 0.00 | 0.00 | 5704.28 | 0.00 | 0.00 | 19717.50 | 0.00 |
June | 44862.27 | 09-JUN-15:09 | 4360.37 | 10035.17 | 0.00 | 0.00 | 6527.76 | 0.00 | 0.00 | 23667.63 | 0.00 |
July | 47539.17 | 20-JUL-13:30 | 5036.30 | 10035.17 | 0.00 | 0.00 | 6866.53 | 0.00 | 0.00 | 25029.88 | 0.00 |
August | 51019.61 | 10-AUG-15:00 | 4429.29 | 10035.17 | 0.00 | 0.00 | 7539.50 | 0.00 | 0.00 | 28744.49 | 0.00 |
September | 44142.50 | 07-SEP-13:30 | 4697.55 | 10035.17 | 0.00 | 0.00 | 6348.51 | 0.00 | 0.00 | 22425.91 | 0.00 |
October | 38813.92 | 07-OCT-13:39 | 4697.21 | 10035.17 | 0.00 | 0.00 | 5394.83 | 0.00 | 0.00 | 17995.67 | 0.00 |
November | 35691.66 | 01-NOV-13:00 | 4696.99 | 10035.17 | 0.00 | 0.00 | 5343.24 | 0.00 | 0.00 | 14846.86 | 0.00 |
December | 28856.27 | 04-DEC-13:30 | 4783.36 | 10035.17 | 0.00 | 0.00 | 5257.46 | 0.00 | 0.00 | 7799.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 23595.08 | 4360.37 | 10035.17 | 0.00 | 0.00 | 2952.17 | 0.00 | 0.00 | 2457.86 | 0.00 | |
Maximum of Months | 51019.61 | 7167.29 | 10035.17 | 0.00 | 0.00 | 7539.50 | 0.00 | 0.00 | 28744.49 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.67 | 24.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.55 | 1.17 | 24.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.57 | 3.17 | 24.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.23 | 8.50 | 25.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.48 | 8.50 | 25.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 25.51 | 10.50 | 25.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.09 | 11.17 | 25.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.93 | 8.33 | 25.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.39 | 8.33 | 25.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.65 | 5.17 | 24.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 |
Annual Sum or Average | 0.00 | 0.00 | 71.50 | 25.49 | 65.83 | 25.30 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.09 | 11.17 | 25.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.00 | 27.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.41 | 0.00 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.46 | 0.00 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 27.58 | 0.00 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 27.57 | 0.50 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 107.67 | 27.67 | 3.17 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 107.33 | 27.67 | 4.33 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 68.17 | 27.57 | 0.67 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.53 | 0.00 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.39 | 0.00 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.00 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 464.00 | 27.60 | 8.67 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 107.67 | 27.67 | 4.33 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 108.83 | 23.43 | 88.17 | 23.64 | 0.00 | 23.64 |
February | 27.33 | 23.32 | 177.83 | 23.83 | 0.17 | 23.83 |
March | 11.50 | 23.44 | 253.00 | 23.89 | 0.17 | 23.89 |
April | 0.33 | 24.40 | 295.67 | 23.91 | 0.33 | 23.91 |
May | 10.33 | 24.19 | 312.00 | 23.94 | 10.33 | 23.94 |
June | 36.50 | 24.14 | 312.00 | 23.96 | 36.50 | 23.98 |
July | 68.00 | 24.13 | 300.00 | 23.99 | 68.00 | 24.01 |
August | 74.00 | 24.16 | 324.00 | 24.00 | 74.00 | 24.03 |
September | 47.67 | 24.17 | 300.00 | 23.98 | 47.67 | 24.00 |
October | 17.33 | 24.08 | 300.00 | 23.94 | 17.33 | 23.95 |
November | 6.00 | 24.05 | 288.00 | 23.92 | 6.00 | 23.92 |
December | 17.50 | 23.44 | 227.00 | 23.87 | 1.00 | 23.87 |
Annual Sum or Average | 425.33 | 23.86 | 3177.67 | 23.92 | 261.50 | 23.94 |
Minimum of Months | 0.33 | 23.32 | 88.17 | 23.64 | 0.00 | 23.64 |
Maximum of Months | 108.83 | 24.40 | 324.00 | 24.00 | 74.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 105.67 | 23.50 | 190.67 | 25.16 | 22.67 | 25.24 |
February | 92.00 | 25.45 | 232.83 | 26.10 | 61.33 | 26.16 |
March | 145.67 | 26.56 | 311.00 | 26.46 | 139.67 | 26.51 |
April | 229.83 | 26.68 | 300.00 | 26.65 | 229.83 | 26.66 |
May | 283.00 | 26.71 | 312.00 | 26.71 | 283.00 | 26.71 |
June | 309.17 | 26.71 | 312.00 | 26.71 | 309.17 | 26.71 |
July | 299.17 | 26.71 | 300.00 | 26.71 | 299.17 | 26.71 |
August | 324.00 | 26.71 | 324.00 | 26.71 | 324.00 | 26.71 |
September | 297.00 | 26.71 | 300.00 | 26.71 | 297.00 | 26.71 |
October | 277.83 | 26.71 | 300.00 | 26.72 | 277.83 | 26.72 |
November | 240.50 | 26.69 | 288.00 | 26.66 | 240.50 | 26.67 |
December | 128.67 | 26.00 | 272.17 | 26.22 | 107.00 | 26.28 |
Annual Sum or Average | 2732.50 | 26.50 | 3442.67 | 26.54 | 2591.17 | 26.59 |
Minimum of Months | 92.00 | 23.50 | 190.67 | 25.16 | 22.67 | 25.24 |
Maximum of Months | 324.00 | 26.71 | 324.00 | 26.72 | 324.00 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 133.67 | 22.77 | 163.00 | 24.37 | 26.00 | 24.41 |
February | 184.67 | 26.77 | 225.00 | 27.02 | 143.67 | 27.26 |
March | 244.33 | 29.09 | 311.00 | 28.71 | 236.83 | 28.88 |
April | 287.67 | 30.49 | 300.00 | 30.41 | 287.67 | 30.43 |
May | 312.00 | 33.74 | 312.00 | 33.74 | 312.00 | 33.74 |
June | 312.00 | 34.99 | 312.00 | 34.99 | 312.00 | 34.99 |
July | 300.00 | 36.59 | 300.00 | 36.59 | 300.00 | 36.59 |
August | 324.00 | 36.89 | 324.00 | 36.89 | 324.00 | 36.89 |
September | 300.00 | 34.36 | 300.00 | 34.36 | 300.00 | 34.36 |
October | 300.00 | 32.03 | 300.00 | 32.03 | 300.00 | 32.03 |
November | 278.33 | 29.60 | 288.00 | 29.54 | 278.33 | 29.56 |
December | 197.67 | 26.99 | 261.17 | 27.09 | 165.50 | 27.28 |
Annual Sum or Average | 3174.33 | 32.05 | 3396.17 | 31.94 | 2986.00 | 32.16 |
Minimum of Months | 133.67 | 22.77 | 163.00 | 24.37 | 26.00 | 24.41 |
Maximum of Months | 324.00 | 36.89 | 324.00 | 36.89 | 324.00 | 36.89 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE HP COOLING COIL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.387534E+10 | 0.948516E+09 | 243.88 | 0.313172E+10 | 0.743619E+09 | 0.00 | 1.00 | 25-JAN-06:03 | 0.00 | 01-JAN-00:10 | 29466.49 | 30-JAN-06:02 | 20759.11 | 30-JAN-06:02 | 8707.38 | 30-JAN-06:02 | 6410.64 | 30-JAN-06:02 | 0.00 |
February | 0.520107E+10 | 0.127154E+10 | 241.73 | 0.417343E+10 | 0.102764E+10 | 0.00 | 1.00 | 06-FEB-06:01 | 0.00 | 01-FEB-00:10 | 30913.15 | 09-FEB-06:01 | 23399.18 | 10-FEB-06:02 | 11115.22 | 09-FEB-06:03 | 6633.92 | 09-FEB-06:01 | 0.00 |
March | 0.763737E+10 | 0.189779E+10 | 297.27 | 0.638147E+10 | 0.125589E+10 | 0.00 | 1.00 | 01-MAR-06:02 | 0.00 | 01-MAR-00:10 | 30936.20 | 29-MAR-05:01 | 26710.59 | 28-MAR-05:01 | 11361.16 | 29-MAR-05:04 | 6637.27 | 29-MAR-05:01 | 0.00 |
April | 0.950489E+10 | 0.242885E+10 | 291.29 | 0.787443E+10 | 0.163047E+10 | 0.00 | 1.00 | 01-APR-05:02 | 0.00 | 01-APR-00:10 | 31167.50 | 10-APR-05:01 | 26863.58 | 26-APR-05:01 | 11640.22 | 20-APR-05:04 | 6670.51 | 10-APR-05:01 | 0.00 |
May | 0.137532E+11 | 0.369444E+10 | 319.46 | 0.112723E+11 | 0.248086E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:05 | 32539.94 | 24-MAY-05:01 | 26826.09 | 11-MAY-05:01 | 14485.51 | 24-MAY-05:06 | 7036.24 | 23-MAY-05:01 | 0.00 |
June | 0.166006E+11 | 0.449582E+10 | 322.99 | 0.124395E+11 | 0.416108E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 33048.34 | 08-JUN-05:01 | 25929.05 | 16-JUN-05:01 | 15616.57 | 27-JUN-05:06 | 7352.31 | 09-JUN-05:01 | 0.00 |
July | 0.190774E+11 | 0.525394E+10 | 334.36 | 0.134284E+11 | 0.564897E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 32746.96 | 06-JUL-05:01 | 25323.44 | 22-JUL-05:01 | 16675.27 | 06-JUL-05:07 | 7564.49 | 19-JUL-17:00 | 0.00 |
August | 0.213497E+11 | 0.589069E+10 | 349.97 | 0.148476E+11 | 0.650209E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 32746.96 | 31-AUG-05:02 | 23535.68 | 07-AUG-05:01 | 17594.91 | 23-AUG-05:08 | 7863.35 | 16-AUG-12:00 | 0.00 |
September | 0.170427E+11 | 0.450594E+10 | 319.39 | 0.121087E+11 | 0.493407E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 33541.28 | 23-SEP-05:01 | 23057.91 | 05-SEP-05:01 | 16318.25 | 23-SEP-05:05 | 7251.98 | 08-SEP-05:01 | 0.00 |
October | 0.137317E+11 | 0.348091E+10 | 307.11 | 0.103517E+11 | 0.338004E+10 | 0.00 | 1.00 | 01-OCT-12:22 | 0.00 | 01-OCT-00:10 | 33376.24 | 02-OCT-05:01 | 27164.28 | 20-OCT-05:01 | 15825.49 | 02-OCT-05:06 | 7129.23 | 02-OCT-05:01 | 0.00 |
November | 0.102038E+11 | 0.249752E+10 | 282.45 | 0.779666E+10 | 0.240715E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 32187.39 | 03-NOV-05:01 | 24778.97 | 20-NOV-06:01 | 13151.92 | 02-NOV-05:05 | 6809.24 | 03-NOV-05:01 | 0.00 |
December | 0.639514E+10 | 0.154322E+10 | 272.99 | 0.501269E+10 | 0.138245E+10 | 0.00 | 1.00 | 01-DEC-06:02 | 0.00 | 01-DEC-00:10 | 30844.67 | 06-DEC-06:01 | 24436.50 | 13-DEC-06:02 | 11864.74 | 06-DEC-06:03 | 6623.94 | 06-DEC-06:01 | 0.00 |
Annual Sum or Average | 0.144373E+12 | 0.379092E+11 | 3582.89 | 0.108819E+12 | 0.355543E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.387534E+10 | 0.948516E+09 | 241.73 | 0.313172E+10 | 0.743619E+09 | 0.00 | 1.00 | 0.00 | 29466.49 | 20759.11 | 8707.38 | 6410.64 | 0.00 | ||||||
Maximum of Months | 0.213497E+11 | 0.589069E+10 | 349.97 | 0.148476E+11 | 0.650209E+10 | 0.00 | 1.00 | 0.00 | 33541.28 | 27164.28 | 17594.91 | 7863.35 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE HP COOLING COIL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.518371E+09 | 0.149931E+09 | 51.67 | 0.389847E+09 | 0.128524E+09 | 0.00 | 0.19 | 28-JAN-14:00 | 0.00 | 01-JAN-00:10 | 7102.60 | 28-JAN-14:00 | 7102.60 | 28-JAN-14:00 | 2289.15 | 30-JAN-13:10 | 2191.48 | 28-JAN-14:00 | 0.00 |
February | 0.386193E+10 | 0.112752E+10 | 153.00 | 0.297878E+10 | 0.883153E+09 | 0.00 | 0.77 | 05-FEB-14:25 | 0.00 | 01-FEB-00:10 | 32138.99 | 05-FEB-14:25 | 29062.07 | 05-FEB-14:25 | 6416.33 | 07-FEB-16:00 | 9568.33 | 05-FEB-14:25 | 0.00 |
March | 0.107708E+11 | 0.318422E+10 | 252.36 | 0.882805E+10 | 0.194274E+10 | 0.00 | 1.00 | 23-MAR-17:10 | 0.00 | 01-MAR-00:10 | 70390.68 | 26-MAR-12:43 | 70276.90 | 26-MAR-12:43 | 10721.46 | 28-MAR-17:12 | 21531.10 | 26-MAR-12:43 | 0.00 |
April | 0.222935E+11 | 0.670458E+10 | 346.19 | 0.183862E+11 | 0.390728E+10 | 0.00 | 1.00 | 02-APR-10:53 | 0.00 | 01-APR-00:10 | 93031.72 | 30-APR-17:23 | 79851.12 | 30-APR-12:02 | 24097.36 | 30-APR-17:23 | 26822.28 | 30-APR-12:02 | 0.00 |
May | 0.459703E+11 | 0.142338E+11 | 548.48 | 0.379681E+11 | 0.800223E+10 | 0.00 | 1.00 | 01-MAY-17:08 | 0.00 | 01-MAY-00:05 | 97430.91 | 24-MAY-17:08 | 82701.75 | 21-MAY-12:23 | 29976.16 | 24-MAY-17:08 | 28685.82 | 31-MAY-18:23 | 0.00 |
June | 0.590029E+11 | 0.181042E+11 | 577.02 | 0.444516E+11 | 0.145513E+11 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:13 | 101091.83 | 08-JUN-05:07 | 81389.96 | 15-JUN-17:06 | 35788.97 | 08-JUN-05:07 | 28774.58 | 09-JUN-17:05 | 0.00 |
July | 0.748693E+11 | 0.232400E+11 | 600.71 | 0.546119E+11 | 0.202574E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:15 | 99782.12 | 18-JUL-05:01 | 83173.44 | 04-JUL-09:43 | 35514.30 | 04-JUL-23:03 | 29652.87 | 30-JUL-13:02 | 0.00 |
August | 0.799910E+11 | 0.247820E+11 | 606.64 | 0.574606E+11 | 0.225304E+11 | 0.00 | 1.00 | 01-AUG-00:23 | 0.00 | 01-AUG-00:13 | 102339.75 | 08-AUG-05:01 | 80473.08 | 06-AUG-08:23 | 40377.68 | 22-AUG-17:06 | 29706.55 | 10-AUG-17:42 | 0.00 |
September | 0.597140E+11 | 0.179684E+11 | 568.94 | 0.427579E+11 | 0.169561E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:13 | 102745.01 | 23-SEP-05:08 | 81344.33 | 04-SEP-11:43 | 39129.65 | 08-SEP-17:06 | 28613.47 | 04-SEP-14:22 | 0.00 |
October | 0.404674E+11 | 0.120063E+11 | 514.76 | 0.306789E+11 | 0.978853E+10 | 0.00 | 1.00 | 01-OCT-08:35 | 0.00 | 01-OCT-00:15 | 100771.94 | 07-OCT-05:06 | 83561.98 | 29-OCT-14:02 | 37010.55 | 07-OCT-17:08 | 27334.69 | 07-OCT-17:08 | 0.00 |
November | 0.199529E+11 | 0.578573E+10 | 322.11 | 0.150019E+11 | 0.495097E+10 | 0.00 | 1.00 | 01-NOV-17:08 | 0.00 | 01-NOV-00:10 | 73901.00 | 05-NOV-11:43 | 73881.07 | 05-NOV-11:43 | 22994.55 | 01-NOV-17:08 | 22093.42 | 05-NOV-11:43 | 0.00 |
December | 0.517796E+10 | 0.147759E+10 | 179.67 | 0.376581E+10 | 0.141215E+10 | 0.00 | 0.89 | 03-DEC-13:25 | 0.00 | 01-DEC-00:10 | 40301.81 | 03-DEC-13:25 | 32379.25 | 03-DEC-13:25 | 8907.96 | 03-DEC-11:30 | 10898.29 | 03-DEC-13:25 | 0.00 |
Annual Sum or Average | 0.422590E+12 | 0.128764E+12 | 4721.54 | 0.317280E+12 | 0.105311E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.518371E+09 | 0.149931E+09 | 51.67 | 0.389847E+09 | 0.128524E+09 | 0.00 | 0.19 | 0.00 | 7102.60 | 7102.60 | 2289.15 | 2191.48 | 0.00 | ||||||
Maximum of Months | 0.799910E+11 | 0.247820E+11 | 606.64 | 0.574606E+11 | 0.225304E+11 | 0.00 | 1.00 | 0.00 | 102745.01 | 83561.98 | 40377.68 | 29706.55 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.01 | 13.82 | 34.19 | 69.47 | 63.10 | 0.00 | 0.00 | 0.00 |
February | 54.75 | 15.66 | 39.08 | 85.59 | 57.04 | 0.00 | 0.00 | 0.00 |
March | 64.79 | 19.23 | 45.56 | 114.56 | 45.97 | 0.00 | 0.00 | 0.00 |
April | 70.63 | 19.79 | 50.85 | 143.37 | 32.58 | 0.00 | 0.00 | 0.00 |
May | 76.85 | 22.95 | 53.91 | 186.26 | 11.39 | 0.00 | 0.00 | 0.00 |
June | 79.55 | 25.12 | 54.43 | 202.57 | 4.72 | 0.00 | 0.00 | 0.00 |
July | 73.00 | 20.90 | 52.10 | 210.36 | 0.66 | 0.00 | 0.00 | 0.00 |
August | 74.74 | 22.66 | 52.07 | 215.25 | 0.41 | 0.00 | 0.00 | 0.00 |
September | 71.20 | 22.38 | 48.82 | 179.28 | 6.64 | 0.00 | 0.00 | 0.00 |
October | 63.29 | 20.44 | 42.84 | 140.63 | 19.42 | 0.00 | 0.00 | 0.00 |
November | 54.47 | 17.84 | 36.63 | 103.09 | 40.47 | 0.00 | 0.00 | 0.00 |
December | 45.57 | 13.80 | 31.77 | 70.50 | 59.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.77 | 19.56 | 45.21 | 143.74 | 28.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.57 | 13.80 | 31.77 | 69.47 | 0.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.55 | 25.12 | 54.43 | 215.25 | 63.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.01 | 13.82 | 34.19 | 69.47 | 63.10 | 0.00 | 0.00 | 0.00 |
February | 54.75 | 15.66 | 39.08 | 85.59 | 57.04 | 0.00 | 0.00 | 0.00 |
March | 64.79 | 19.23 | 45.56 | 114.56 | 45.97 | 0.00 | 0.00 | 0.00 |
April | 70.63 | 19.79 | 50.85 | 143.37 | 32.58 | 0.00 | 0.00 | 0.00 |
May | 76.85 | 22.95 | 53.91 | 186.26 | 11.39 | 0.00 | 0.00 | 0.00 |
June | 79.55 | 25.12 | 54.43 | 202.57 | 4.72 | 0.00 | 0.00 | 0.00 |
July | 73.00 | 20.90 | 52.10 | 210.36 | 0.66 | 0.00 | 0.00 | 0.00 |
August | 74.74 | 22.66 | 52.07 | 215.25 | 0.41 | 0.00 | 0.00 | 0.00 |
September | 71.20 | 22.38 | 48.82 | 179.28 | 6.64 | 0.00 | 0.00 | 0.00 |
October | 63.29 | 20.44 | 42.84 | 140.63 | 19.42 | 0.00 | 0.00 | 0.00 |
November | 54.47 | 17.84 | 36.63 | 103.09 | 40.47 | 0.00 | 0.00 | 0.00 |
December | 45.57 | 13.80 | 31.77 | 70.50 | 59.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.77 | 19.56 | 45.21 | 143.74 | 28.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.57 | 13.80 | 31.77 | 69.47 | 0.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.55 | 25.12 | 54.43 | 215.25 | 63.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.73 | 0.00 | 15.73 | 17.28 | 37.38 | 0.00 | 0.00 | 0.00 |
February | 18.03 | 0.00 | 18.03 | 23.23 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 20.72 | 0.00 | 20.71 | 33.72 | 26.99 | 0.00 | 0.00 | 0.00 |
April | 23.37 | 0.07 | 23.31 | 48.70 | 18.70 | 0.00 | 0.00 | 0.00 |
May | 26.33 | 0.83 | 25.50 | 72.44 | 6.26 | 0.00 | 0.00 | 0.00 |
June | 28.07 | 1.52 | 26.55 | 82.91 | 2.81 | 0.00 | 0.00 | 0.00 |
July | 25.80 | 0.73 | 25.07 | 90.35 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 24.09 | 0.26 | 23.83 | 87.79 | 0.21 | 0.00 | 0.00 | 0.00 |
September | 21.89 | 0.01 | 21.88 | 65.98 | 3.70 | 0.00 | 0.00 | 0.00 |
October | 19.40 | 0.00 | 19.40 | 47.46 | 11.08 | 0.00 | 0.00 | 0.00 |
November | 16.65 | 0.00 | 16.65 | 30.21 | 23.48 | 0.00 | 0.00 | 0.00 |
December | 14.68 | 0.00 | 14.68 | 17.96 | 35.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.24 | 0.29 | 20.96 | 51.68 | 16.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.68 | 0.00 | 14.68 | 17.28 | 0.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.07 | 1.52 | 26.55 | 90.35 | 37.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.73 | 0.00 | 15.73 | 17.28 | 37.38 | 0.00 | 0.00 | 0.00 |
February | 18.03 | 0.00 | 18.03 | 23.23 | 33.81 | 0.00 | 0.00 | 0.00 |
March | 20.72 | 0.00 | 20.71 | 33.72 | 26.99 | 0.00 | 0.00 | 0.00 |
April | 23.37 | 0.07 | 23.31 | 48.70 | 18.70 | 0.00 | 0.00 | 0.00 |
May | 26.33 | 0.83 | 25.50 | 72.43 | 6.26 | 0.00 | 0.00 | 0.00 |
June | 28.07 | 1.52 | 26.55 | 82.91 | 2.81 | 0.00 | 0.00 | 0.00 |
July | 25.80 | 0.73 | 25.07 | 90.35 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 24.09 | 0.26 | 23.83 | 87.79 | 0.21 | 0.00 | 0.00 | 0.00 |
September | 21.89 | 0.01 | 21.88 | 65.98 | 3.69 | 0.00 | 0.00 | 0.00 |
October | 19.40 | 0.00 | 19.40 | 47.46 | 11.08 | 0.00 | 0.00 | 0.00 |
November | 16.65 | 0.00 | 16.65 | 30.20 | 23.48 | 0.00 | 0.00 | 0.00 |
December | 14.68 | 0.00 | 14.68 | 17.96 | 35.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.24 | 0.29 | 20.96 | 51.67 | 16.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.68 | 0.00 | 14.68 | 17.28 | 0.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.07 | 1.52 | 26.55 | 90.35 | 37.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.12 | 11.51 | 18.61 | 43.82 | 31.90 | 2.67 | 0.00 | 0.00 |
February | 36.67 | 15.04 | 21.63 | 55.45 | 29.85 | 0.00 | 0.00 | 0.00 |
March | 44.48 | 18.81 | 25.67 | 71.39 | 27.25 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 23.47 | 29.03 | 90.55 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 59.63 | 29.23 | 30.40 | 110.64 | 12.81 | 0.00 | 0.00 | 0.00 |
June | 62.20 | 31.89 | 30.31 | 117.23 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 60.37 | 30.89 | 29.48 | 119.13 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 57.45 | 28.46 | 28.99 | 113.92 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 51.50 | 24.89 | 26.61 | 97.40 | 10.85 | 0.00 | 0.00 | 0.00 |
October | 43.21 | 20.39 | 22.82 | 76.86 | 18.11 | 0.00 | 0.00 | 0.00 |
November | 34.19 | 14.95 | 19.24 | 55.37 | 27.20 | 0.00 | 0.00 | 0.00 |
December | 27.95 | 10.82 | 17.14 | 40.94 | 31.73 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 46.73 | 21.73 | 25.01 | 82.87 | 19.23 | 6.00 | 0.00 | 0.00 |
Minimum of Months | 27.95 | 10.82 | 17.14 | 40.94 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.20 | 31.89 | 30.40 | 119.13 | 31.90 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.81 | 26.37 | 42.43 | 86.41 | 52.23 | 28.67 | 0.00 | 0.00 |
February | 83.43 | 34.09 | 49.33 | 105.70 | 51.88 | 11.00 | 0.00 | 0.00 |
March | 100.89 | 42.35 | 58.54 | 131.33 | 51.57 | 0.00 | 0.00 | 0.00 |
April | 118.94 | 52.73 | 66.21 | 160.69 | 48.09 | 7.17 | 0.00 | 0.00 |
May | 134.96 | 65.63 | 69.33 | 186.47 | 36.15 | 2.17 | 0.00 | 0.00 |
June | 140.68 | 71.54 | 69.13 | 194.18 | 34.49 | 9.17 | 0.00 | 0.00 |
July | 136.46 | 69.24 | 67.23 | 190.73 | 30.84 | 2.83 | 0.00 | 0.00 |
August | 129.99 | 63.88 | 66.11 | 180.51 | 31.66 | 4.33 | 0.00 | 0.00 |
September | 116.66 | 55.98 | 60.68 | 160.79 | 36.82 | 24.33 | 0.00 | 0.00 |
October | 98.15 | 46.10 | 52.05 | 132.04 | 45.14 | 37.17 | 0.00 | 0.00 |
November | 77.98 | 34.11 | 43.88 | 100.30 | 55.21 | 9.33 | 0.00 | 0.00 |
December | 63.93 | 24.84 | 39.09 | 78.93 | 55.37 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 106.01 | 48.98 | 57.03 | 142.51 | 44.06 | 163.50 | 0.00 | 0.00 |
Minimum of Months | 63.93 | 24.84 | 39.09 | 78.93 | 30.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.68 | 71.54 | 69.33 | 194.18 | 55.37 | 37.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128591E+09 | 37011830.31 | 91579563.20 | 0.186075E+09 | 0.168997E+09 |
February | 0.132447E+09 | 37896403.38 | 94550134.80 | 0.207056E+09 | 0.137994E+09 |
March | 0.173537E+09 | 51505547.19 | 0.122032E+09 | 0.306836E+09 | 0.123123E+09 |
April | 0.183085E+09 | 51288250.57 | 0.131796E+09 | 0.371620E+09 | 84446227.04 |
May | 0.205846E+09 | 61458477.20 | 0.144387E+09 | 0.498878E+09 | 30498721.09 |
June | 0.206201E+09 | 65118127.61 | 0.141082E+09 | 0.525049E+09 | 12234027.89 |
July | 0.195511E+09 | 55972134.66 | 0.139539E+09 | 0.563438E+09 | 1766003.16 |
August | 0.200175E+09 | 60698656.81 | 0.139476E+09 | 0.576515E+09 | 1110313.79 |
September | 0.184555E+09 | 58020004.38 | 0.126535E+09 | 0.464690E+09 | 17212828.08 |
October | 0.169507E+09 | 54757333.65 | 0.114750E+09 | 0.376653E+09 | 52018346.26 |
November | 0.141187E+09 | 46230972.89 | 94956084.29 | 0.267204E+09 | 0.104890E+09 |
December | 0.122064E+09 | 36974042.12 | 85089674.14 | 0.188840E+09 | 0.159187E+09 |
Annual Sum or Average | 0.204270E+10 | 0.616932E+09 | 0.142577E+10 | 0.453285E+10 | 0.893477E+09 |
Minimum of Months | 0.122064E+09 | 36974042.12 | 85089674.14 | 0.186075E+09 | 1110313.79 |
Maximum of Months | 0.206201E+09 | 65118127.61 | 0.144387E+09 | 0.576515E+09 | 0.168997E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128591E+09 | 37011830.31 | 91579563.20 | 0.186075E+09 | 0.168997E+09 |
February | 0.132447E+09 | 37896403.38 | 94550134.80 | 0.207056E+09 | 0.137994E+09 |
March | 0.173537E+09 | 51505547.19 | 0.122032E+09 | 0.306836E+09 | 0.123123E+09 |
April | 0.183085E+09 | 51288250.57 | 0.131796E+09 | 0.371620E+09 | 84446227.04 |
May | 0.205846E+09 | 61458477.20 | 0.144387E+09 | 0.498878E+09 | 30498721.09 |
June | 0.206201E+09 | 65118127.61 | 0.141082E+09 | 0.525049E+09 | 12234027.89 |
July | 0.195511E+09 | 55972134.66 | 0.139539E+09 | 0.563438E+09 | 1766003.16 |
August | 0.200175E+09 | 60698656.81 | 0.139476E+09 | 0.576515E+09 | 1110313.79 |
September | 0.184555E+09 | 58020004.38 | 0.126535E+09 | 0.464690E+09 | 17212828.08 |
October | 0.169507E+09 | 54757333.65 | 0.114750E+09 | 0.376653E+09 | 52018346.26 |
November | 0.141187E+09 | 46230972.89 | 94956084.29 | 0.267204E+09 | 0.104890E+09 |
December | 0.122064E+09 | 36974042.12 | 85089674.14 | 0.188840E+09 | 0.159187E+09 |
Annual Sum or Average | 0.204270E+10 | 0.616932E+09 | 0.142577E+10 | 0.453285E+10 | 0.893477E+09 |
Minimum of Months | 0.122064E+09 | 36974042.12 | 85089674.14 | 0.186075E+09 | 1110313.79 |
Maximum of Months | 0.206201E+09 | 65118127.61 | 0.144387E+09 | 0.576515E+09 | 0.168997E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42132490.08 | 0.00 | 42132490.08 | 46277128.06 | 0.100124E+09 |
February | 43622112.43 | 0.00 | 43622112.43 | 56204218.46 | 81786896.07 |
March | 55485201.87 | 2407.54 | 55482794.33 | 90318089.97 | 72295689.96 |
April | 60586178.48 | 174781.71 | 60411396.77 | 0.126237E+09 | 48460926.85 |
May | 70531102.25 | 2227361.19 | 68303741.05 | 0.194011E+09 | 16774669.37 |
June | 72761182.25 | 3940601.28 | 68820580.97 | 0.214896E+09 | 7277327.00 |
July | 69115066.20 | 1968561.74 | 67146504.46 | 0.241992E+09 | 1035831.81 |
August | 64527437.86 | 696491.63 | 63830946.24 | 0.235140E+09 | 573573.37 |
September | 56731511.03 | 14121.79 | 56717389.24 | 0.171033E+09 | 9577671.52 |
October | 51956378.17 | 0.00 | 51956378.17 | 0.127124E+09 | 29683242.88 |
November | 43164613.08 | 0.00 | 43164613.08 | 78291780.12 | 60870051.80 |
December | 39325228.12 | 0.00 | 39325228.12 | 48113805.23 | 93740265.72 |
Annual Sum or Average | 0.669939E+09 | 9024326.88 | 0.660914E+09 | 0.162964E+10 | 0.522200E+09 |
Minimum of Months | 39325228.12 | 0.00 | 39325228.12 | 46277128.06 | 573573.37 |
Maximum of Months | 72761182.25 | 3940601.28 | 68820580.97 | 0.241992E+09 | 0.100124E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42131107.34 | 0.00 | 42131107.34 | 46275343.55 | 0.100123E+09 |
February | 43620707.49 | 0.00 | 43620707.49 | 56202340.23 | 81786010.00 |
March | 55483442.45 | 2407.43 | 55481035.02 | 90315653.23 | 72294631.59 |
April | 60584295.30 | 174773.52 | 60409521.78 | 0.126234E+09 | 48459920.78 |
May | 70528905.94 | 2227256.79 | 68301649.15 | 0.194008E+09 | 16773982.32 |
June | 72758887.87 | 3940416.58 | 68818471.30 | 0.214893E+09 | 7276842.81 |
July | 69112942.26 | 1968469.47 | 67144472.80 | 0.241990E+09 | 1035704.66 |
August | 64525482.21 | 696458.98 | 63829023.23 | 0.235138E+09 | 573493.21 |
September | 56729789.00 | 14121.13 | 56715667.87 | 0.171031E+09 | 9577135.82 |
October | 51954766.85 | 0.00 | 51954766.85 | 0.127123E+09 | 29682221.83 |
November | 43163236.15 | 0.00 | 43163236.15 | 78290083.00 | 60868811.83 |
December | 39323937.11 | 0.00 | 39323937.11 | 48112139.24 | 93739124.56 |
Annual Sum or Average | 0.669917E+09 | 9023903.89 | 0.660894E+09 | 0.162961E+10 | 0.522191E+09 |
Minimum of Months | 39323937.11 | 0.00 | 39323937.11 | 46275343.55 | 573493.21 |
Maximum of Months | 72758887.87 | 3940416.58 | 68818471.30 | 0.241990E+09 | 0.100123E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80662988.31 | 30830339.36 | 49832648.95 | 0.117374E+09 | 85443891.15 |
February | 88701595.30 | 36373595.39 | 52327999.91 | 0.134145E+09 | 72210736.51 |
March | 0.119135E+09 | 50384171.55 | 68751105.11 | 0.191223E+09 | 72985294.36 |
April | 0.136083E+09 | 60831707.65 | 75250802.23 | 0.234714E+09 | 58956344.55 |
May | 0.159722E+09 | 78300520.34 | 81421339.58 | 0.296342E+09 | 34303357.26 |
June | 0.161215E+09 | 82646003.04 | 78569240.44 | 0.303871E+09 | 25600448.41 |
July | 0.161695E+09 | 82746534.34 | 78948352.19 | 0.319076E+09 | 12924492.75 |
August | 0.153870E+09 | 76231237.56 | 77639235.00 | 0.305116E+09 | 11937513.83 |
September | 0.133476E+09 | 64510216.26 | 68965293.05 | 0.252465E+09 | 28128867.56 |
October | 0.115731E+09 | 54603956.40 | 61126833.98 | 0.205866E+09 | 48516187.12 |
November | 88607765.68 | 38742263.20 | 49865502.47 | 0.143527E+09 | 70492426.73 |
December | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 84997476.98 |
Annual Sum or Average | 0.147377E+10 | 0.685172E+09 | 0.788600E+09 | 0.261336E+10 | 0.606497E+09 |
Minimum of Months | 74873006.24 | 28971562.86 | 45901443.38 | 0.109646E+09 | 11937513.83 |
Maximum of Months | 0.161695E+09 | 82746534.34 | 81421339.58 | 0.319076E+09 | 85443891.15 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184292E+09 | 70638815.15 | 0.113653E+09 | 0.231452E+09 | 0.139884E+09 |
February | 0.201827E+09 | 82482399.67 | 0.119344E+09 | 0.255715E+09 | 0.125499E+09 |
March | 0.270235E+09 | 0.113435E+09 | 0.156801E+09 | 0.351756E+09 | 0.138127E+09 |
April | 0.308293E+09 | 0.136669E+09 | 0.171624E+09 | 0.416512E+09 | 0.124655E+09 |
May | 0.361472E+09 | 0.175775E+09 | 0.185698E+09 | 0.499431E+09 | 96820255.84 |
June | 0.364634E+09 | 0.185441E+09 | 0.179193E+09 | 0.503302E+09 | 89408758.37 |
July | 0.365507E+09 | 0.185450E+09 | 0.180057E+09 | 0.510853E+09 | 82601444.43 |
August | 0.348160E+09 | 0.171088E+09 | 0.177072E+09 | 0.483486E+09 | 84785950.67 |
September | 0.302386E+09 | 0.145097E+09 | 0.157289E+09 | 0.416775E+09 | 95438175.54 |
October | 0.262876E+09 | 0.123464E+09 | 0.139412E+09 | 0.353665E+09 | 0.120913E+09 |
November | 0.202135E+09 | 88407082.04 | 0.113728E+09 | 0.259989E+09 | 0.143103E+09 |
December | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 0.148305E+09 |
Annual Sum or Average | 0.334304E+10 | 0.154448E+10 | 0.179856E+10 | 0.449435E+10 | 0.138954E+10 |
Minimum of Months | 0.171220E+09 | 66532500.54 | 0.104687E+09 | 0.211416E+09 | 82601444.43 |
Maximum of Months | 0.365507E+09 | 0.185450E+09 | 0.185698E+09 | 0.510853E+09 | 0.148305E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.89 | 199.34 | 127.48 | 27.64 | 99.84 | 0.00 | 0.00 |
February | 216.30 | 180.35 | 145.56 | 31.33 | 114.23 | 0.00 | 0.00 |
March | 295.83 | 145.19 | 171.01 | 38.46 | 132.55 | 0.00 | 0.00 |
April | 384.00 | 102.40 | 188.02 | 39.71 | 148.31 | 0.00 | 0.00 |
May | 517.10 | 35.01 | 206.37 | 47.56 | 158.82 | 0.00 | 0.00 |
June | 570.78 | 14.89 | 215.25 | 53.29 | 161.96 | 0.00 | 0.00 |
July | 601.41 | 2.07 | 197.60 | 43.27 | 154.33 | 0.00 | 0.00 |
August | 606.06 | 1.24 | 197.66 | 45.84 | 151.81 | 0.00 | 0.00 |
September | 490.51 | 20.66 | 186.18 | 44.78 | 141.40 | 0.00 | 0.00 |
October | 376.16 | 60.99 | 165.37 | 40.89 | 124.48 | 0.00 | 0.00 |
November | 266.43 | 127.75 | 142.25 | 35.67 | 106.57 | 0.00 | 0.00 |
December | 176.02 | 187.95 | 120.51 | 27.61 | 92.90 | 0.00 | 0.00 |
Annual Sum or Average | 390.37 | 89.33 | 172.03 | 39.70 | 132.34 | 0.00 | 0.00 |
Minimum of Months | 171.89 | 1.24 | 120.51 | 27.61 | 92.90 | 0.00 | 0.00 |
Maximum of Months | 606.06 | 199.34 | 215.25 | 53.29 | 161.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 613.51 | 446.62 | 421.63 | 161.15 | 260.48 | 0.00 | 0.00 |
February | 776.30 | 417.89 | 513.32 | 210.50 | 302.82 | 0.00 | 0.00 |
March | 999.52 | 381.49 | 622.72 | 263.36 | 359.36 | 0.00 | 0.00 |
April | 1267.75 | 318.44 | 735.01 | 328.57 | 406.45 | 0.00 | 0.00 |
May | 1548.98 | 179.30 | 834.87 | 409.28 | 425.59 | 0.00 | 0.00 |
June | 1641.28 | 138.27 | 870.76 | 446.39 | 424.37 | 0.00 | 0.00 |
July | 1667.81 | 67.56 | 845.18 | 432.52 | 412.66 | 0.00 | 0.00 |
August | 1594.84 | 62.40 | 804.28 | 398.46 | 405.82 | 0.00 | 0.00 |
September | 1363.62 | 151.93 | 720.93 | 348.43 | 372.50 | 0.00 | 0.00 |
October | 1076.06 | 253.59 | 604.92 | 285.41 | 319.51 | 0.00 | 0.00 |
November | 775.22 | 380.75 | 478.59 | 209.26 | 269.34 | 0.00 | 0.00 |
December | 573.12 | 444.28 | 391.36 | 151.43 | 239.93 | 0.00 | 0.00 |
Annual Sum or Average | 1160.17 | 269.25 | 654.26 | 304.17 | 350.09 | 0.00 | 0.00 |
Minimum of Months | 573.12 | 62.40 | 391.36 | 151.43 | 239.93 | 0.00 | 0.00 |
Maximum of Months | 1667.81 | 446.62 | 870.76 | 446.39 | 425.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10536.45 | 5451.17 | 2201.82 | 843.95 | 1357.87 | 0.00 | 0.00 |
February | 13132.03 | 5598.73 | 2669.67 | 1091.04 | 1578.63 | 0.00 | 0.00 |
March | 20255.67 | 5807.59 | 3228.62 | 1355.25 | 1873.36 | 0.00 | 0.00 |
April | 27859.68 | 6221.06 | 3806.09 | 1687.27 | 2118.82 | 0.00 | 0.00 |
May | 38806.24 | 7109.15 | 4318.67 | 2100.06 | 2218.61 | 0.00 | 0.00 |
June | 42157.03 | 6925.96 | 4501.65 | 2289.39 | 2212.26 | 0.00 | 0.00 |
July | 46907.70 | 6628.13 | 4366.87 | 2215.65 | 2151.22 | 0.00 | 0.00 |
August | 43054.00 | 7038.04 | 4159.62 | 2044.07 | 2115.55 | 0.00 | 0.00 |
September | 34930.46 | 7561.90 | 3733.16 | 1791.32 | 1941.84 | 0.00 | 0.00 |
October | 24424.79 | 8381.92 | 3140.69 | 1475.07 | 1665.61 | 0.00 | 0.00 |
November | 15272.30 | 7052.45 | 2495.50 | 1091.45 | 1404.05 | 0.00 | 0.00 |
December | 9620.71 | 6166.73 | 2045.64 | 794.89 | 1250.75 | 0.00 | 0.00 |
Annual Sum or Average | 27331.65 | 6667.59 | 3392.22 | 1567.20 | 1825.02 | 0.00 | 0.00 |
Minimum of Months | 9620.71 | 5451.17 | 2045.64 | 794.89 | 1250.75 | 0.00 | 0.00 |
Maximum of Months | 46907.70 | 8381.92 | 4501.65 | 2289.39 | 2218.61 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.460383E+09 | 0.533922E+09 | 0.341446E+09 | 74023660.62 | 0.267423E+09 | 0.00 | 0.00 |
February | 0.523262E+09 | 0.436306E+09 | 0.352136E+09 | 75792806.76 | 0.276343E+09 | 0.00 | 0.00 |
March | 0.792356E+09 | 0.388886E+09 | 0.458043E+09 | 0.103016E+09 | 0.355027E+09 | 0.00 | 0.00 |
April | 0.995324E+09 | 0.265426E+09 | 0.487340E+09 | 0.102926E+09 | 0.384414E+09 | 0.00 | 0.00 |
May | 0.138500E+10 | 93775389.49 | 0.552751E+09 | 0.127372E+09 | 0.425380E+09 | 0.00 | 0.00 |
June | 0.147947E+10 | 38606859.37 | 0.557921E+09 | 0.138117E+09 | 0.419804E+09 | 0.00 | 0.00 |
July | 0.161081E+10 | 5556673.61 | 0.529251E+09 | 0.115881E+09 | 0.413369E+09 | 0.00 | 0.00 |
August | 0.162327E+10 | 3328407.79 | 0.529402E+09 | 0.122790E+09 | 0.406612E+09 | 0.00 | 0.00 |
September | 0.127141E+10 | 53548016.66 | 0.482571E+09 | 0.116068E+09 | 0.366503E+09 | 0.00 | 0.00 |
October | 0.100750E+10 | 0.163349E+09 | 0.442925E+09 | 0.109515E+09 | 0.333410E+09 | 0.00 | 0.00 |
November | 0.690594E+09 | 0.331121E+09 | 0.368702E+09 | 92461945.78 | 0.276240E+09 | 0.00 | 0.00 |
December | 0.471460E+09 | 0.503407E+09 | 0.322777E+09 | 73948084.24 | 0.248829E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123108E+11 | 0.281723E+10 | 0.542527E+10 | 0.125191E+10 | 0.417335E+10 | 0.00 | 0.00 |
Minimum of Months | 0.460383E+09 | 3328407.79 | 0.322777E+09 | 73948084.24 | 0.248829E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162327E+10 | 0.533922E+09 | 0.557921E+09 | 0.138117E+09 | 0.425380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.164323E+10 | 0.119621E+10 | 0.112928E+10 | 0.431625E+09 | 0.697657E+09 | 0.00 | 0.00 |
February | 0.187803E+10 | 0.101095E+10 | 0.124182E+10 | 0.509230E+09 | 0.732592E+09 | 0.00 | 0.00 |
March | 0.267712E+10 | 0.102179E+10 | 0.166789E+10 | 0.705378E+09 | 0.962515E+09 | 0.00 | 0.00 |
April | 0.328600E+10 | 0.825389E+09 | 0.190516E+10 | 0.851644E+09 | 0.105351E+10 | 0.00 | 0.00 |
May | 0.414879E+10 | 0.480247E+09 | 0.223611E+10 | 0.109621E+10 | 0.113990E+10 | 0.00 | 0.00 |
June | 0.425420E+10 | 0.358406E+09 | 0.225701E+10 | 0.115704E+10 | 0.109997E+10 | 0.00 | 0.00 |
July | 0.446706E+10 | 0.180943E+09 | 0.226373E+10 | 0.115845E+10 | 0.110528E+10 | 0.00 | 0.00 |
August | 0.427162E+10 | 0.167125E+09 | 0.215419E+10 | 0.106724E+10 | 0.108695E+10 | 0.00 | 0.00 |
September | 0.353451E+10 | 0.393804E+09 | 0.186866E+10 | 0.903143E+09 | 0.965514E+09 | 0.00 | 0.00 |
October | 0.288213E+10 | 0.679227E+09 | 0.162023E+10 | 0.764455E+09 | 0.855776E+09 | 0.00 | 0.00 |
November | 0.200937E+10 | 0.986894E+09 | 0.124051E+10 | 0.542392E+09 | 0.698117E+09 | 0.00 | 0.00 |
December | 0.153504E+10 | 0.118996E+10 | 0.104822E+10 | 0.405602E+09 | 0.642620E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.365871E+11 | 0.849096E+10 | 0.206328E+11 | 0.959241E+10 | 0.110404E+11 | 0.00 | 0.00 |
Minimum of Months | 0.153504E+10 | 0.167125E+09 | 0.104822E+10 | 0.405602E+09 | 0.642620E+09 | 0.00 | 0.00 |
Maximum of Months | 0.446706E+10 | 0.119621E+10 | 0.226373E+10 | 0.115845E+10 | 0.113990E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.282208E+11 | 0.146004E+11 | 0.589735E+10 | 0.226044E+10 | 0.363691E+10 | 0.00 | 0.00 |
February | 0.317690E+11 | 0.135445E+11 | 0.645846E+10 | 0.263944E+10 | 0.381902E+10 | 0.00 | 0.00 |
March | 0.542528E+11 | 0.155551E+11 | 0.864752E+10 | 0.362990E+10 | 0.501762E+10 | 0.00 | 0.00 |
April | 0.722123E+11 | 0.161250E+11 | 0.986539E+10 | 0.437341E+10 | 0.549198E+10 | 0.00 | 0.00 |
May | 0.103939E+12 | 0.190411E+11 | 0.115671E+11 | 0.562479E+10 | 0.594232E+10 | 0.00 | 0.00 |
June | 0.109271E+12 | 0.179521E+11 | 0.116683E+11 | 0.593410E+10 | 0.573417E+10 | 0.00 | 0.00 |
July | 0.125638E+12 | 0.177528E+11 | 0.116962E+11 | 0.593439E+10 | 0.576184E+10 | 0.00 | 0.00 |
August | 0.115316E+12 | 0.188507E+11 | 0.111411E+11 | 0.547482E+10 | 0.566630E+10 | 0.00 | 0.00 |
September | 0.905398E+11 | 0.196004E+11 | 0.967635E+10 | 0.464310E+10 | 0.503325E+10 | 0.00 | 0.00 |
October | 0.654194E+11 | 0.224501E+11 | 0.841202E+10 | 0.395084E+10 | 0.446118E+10 | 0.00 | 0.00 |
November | 0.395858E+11 | 0.182799E+11 | 0.646833E+10 | 0.282903E+10 | 0.363930E+10 | 0.00 | 0.00 |
December | 0.257681E+11 | 0.165170E+11 | 0.547904E+10 | 0.212904E+10 | 0.335000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.861931E+12 | 0.210269E+12 | 0.106977E+12 | 0.494233E+11 | 0.575539E+11 | 0.00 | 0.00 |
Minimum of Months | 0.257681E+11 | 0.135445E+11 | 0.547904E+10 | 0.212904E+10 | 0.335000E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125638E+12 | 0.224501E+11 | 0.116962E+11 | 0.593439E+10 | 0.594232E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.702497E+09 | -626072759.8 | 0.00 | 0.00 | 744.00 | 0.00 | -76424426.0 | 59.95 | 0.00 | 0.00 |
February | 0.627427E+09 | -559569719.5 | 0.00 | 0.00 | 672.00 | 0.00 | -67856786.7 | 59.95 | 0.00 | 0.00 |
March | 0.683453E+09 | -609210339.2 | 0.00 | 0.00 | 744.00 | 0.00 | -74242658.4 | 59.95 | 0.00 | 0.00 |
April | 0.580808E+09 | -510366336.3 | 0.00 | 0.00 | 720.00 | 0.00 | -70441927.3 | 59.95 | 0.00 | 0.00 |
May | 0.546028E+09 | -474549242.9 | 0.00 | 0.00 | 744.00 | 0.00 | -71478790.0 | 59.95 | 0.00 | 0.00 |
June | 0.500694E+09 | -431766054.0 | 0.00 | 0.00 | 720.00 | 0.00 | -68927775.3 | 59.95 | 0.00 | 0.00 |
July | 0.475199E+09 | -404868893.3 | 0.00 | 0.00 | 744.00 | 0.00 | -70330526.3 | 59.95 | 0.00 | 0.00 |
August | 0.524402E+09 | -453825579.5 | 0.00 | 0.00 | 744.00 | 0.00 | -70576357.7 | 59.95 | 0.00 | 0.00 |
September | 0.534033E+09 | -465400901.8 | 0.00 | 0.00 | 720.00 | 0.00 | -68632341.4 | 59.95 | 0.00 | 0.00 |
October | 0.593648E+09 | -522324014.2 | 0.00 | 0.00 | 744.00 | 0.00 | -71324358.8 | 59.95 | 0.00 | 0.00 |
November | 0.623378E+09 | -553262274.3 | 0.00 | 0.00 | 720.00 | 0.00 | -70115228.6 | 59.95 | 0.00 | 0.00 |
December | 0.688630E+09 | -614069091.9 | 0.00 | 0.00 | 744.00 | 0.00 | -74560507.8 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.708020E+10 | -0.622529E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -854911684.3 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.475199E+09 | -626072759.8 | 0.00 | 0.00 | 672.00 | 0.00 | -76424426.0 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.702497E+09 | -404868893.3 | 0.00 | 0.00 | 744.00 | 0.00 | -67856786.7 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.70 | 0.50 | 01-JAN-11:30 | 212.61 | 0.00 | 0.00 | 78.00 | 393.76 | 0.00 | 0.00 | 23.33 |
February | 308.33 | 0.68 | 0.50 | 01-FEB-10:50 | 244.70 | 0.00 | 0.00 | 113.17 | 446.87 | 0.00 | 0.00 | 65.17 |
March | 357.50 | 0.66 | 0.50 | 01-MAR-10:30 | 284.69 | 0.00 | 0.00 | 163.00 | 227.03 | 0.00 | 0.00 | 116.00 |
April | 375.00 | 0.65 | 0.50 | 01-APR-10:20 | 314.04 | 0.00 | 0.00 | 182.33 | 600.74 | 0.00 | 0.00 | 157.17 |
May | 405.33 | 0.66 | 0.50 | 01-MAY-09:39 | 809.09 | 0.00 | 0.00 | 206.83 | 226.39 | 0.00 | 0.00 | 121.00 |
June | 403.50 | 0.66 | 0.50 | 01-JUN-09:00 | 341.26 | 0.00 | 0.00 | 205.17 | 215.31 | 0.00 | 0.00 | 112.33 |
July | 405.00 | 0.65 | 0.50 | 01-JUL-09:00 | 618.70 | 0.00 | 0.00 | 215.83 | 226.17 | 0.00 | 0.00 | 122.50 |
August | 395.83 | 0.65 | 0.50 | 01-AUG-09:00 | 914.16 | 0.00 | 0.00 | 209.33 | 252.14 | 0.00 | 0.00 | 149.67 |
September | 358.83 | 0.64 | 0.50 | 01-SEP-09:39 | 313.46 | 0.00 | 0.00 | 181.00 | 251.15 | 0.00 | 0.00 | 138.83 |
October | 351.17 | 0.66 | 0.50 | 01-OCT-09:30 | 266.24 | 0.00 | 0.00 | 147.83 | 312.04 | 0.00 | 0.00 | 106.67 |
November | 318.83 | 0.68 | 0.50 | 01-NOV-09:00 | 228.62 | 0.00 | 0.00 | 98.00 | 554.46 | 0.00 | 0.00 | 67.00 |
December | 319.00 | 0.71 | 0.50 | 01-DEC-10:50 | 201.99 | 0.00 | 0.00 | 51.83 | 165.87 | 0.00 | 0.00 | 0.83 |
Annual Sum or Average | 4323.33 | 0.66 | 412.98 | 0.00 | 0.00 | 1852.33 | 317.26 | 0.00 | 0.00 | 1180.50 | ||
Minimum of Months | 308.33 | 0.64 | 0.50 | 201.99 | 0.00 | 0.00 | 51.83 | 165.87 | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 405.33 | 0.71 | 0.50 | 914.16 | 0.00 | 0.00 | 215.83 | 600.74 | 0.00 | 0.00 | 157.17 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.60 | 0.50 | 01-JAN-09:09 | 610.24 | 14.14 | 20.17 | 197.67 | 323.63 | 18.82 | 58.50 | 184.17 |
February | 308.33 | 0.60 | 0.50 | 01-FEB-08:00 | 736.88 | 14.42 | 16.50 | 200.00 | 230.20 | 16.97 | 56.00 | 164.33 |
March | 357.50 | 0.59 | 0.50 | 01-MAR-08:39 | 767.40 | 13.92 | 0.00 | 251.67 | 651.97 | 17.27 | 75.83 | 210.17 |
April | 375.00 | 0.58 | 0.50 | 01-APR-07:00 | 743.72 | 13.96 | 0.00 | 268.00 | 646.15 | 17.30 | 90.33 | 229.17 |
May | 405.33 | 0.58 | 0.50 | 01-MAY-07:30 | 345.21 | 14.03 | 0.00 | 292.83 | 298.53 | 17.46 | 103.33 | 252.00 |
June | 403.50 | 0.58 | 0.50 | 01-JUN-07:19 | 350.95 | 13.99 | 0.00 | 292.33 | 302.99 | 17.52 | 105.83 | 250.33 |
July | 405.00 | 0.57 | 0.50 | 01-JUL-07:10 | 357.21 | 14.04 | 0.00 | 297.00 | 330.22 | 19.20 | 127.83 | 277.67 |
August | 395.83 | 0.58 | 0.50 | 01-AUG-07:30 | 462.04 | 14.23 | 0.00 | 289.00 | 408.16 | 17.64 | 106.33 | 251.50 |
September | 358.83 | 0.58 | 0.50 | 01-SEP-07:40 | 1053.35 | 14.38 | 0.00 | 263.83 | 928.92 | 17.88 | 100.67 | 224.83 |
October | 351.17 | 0.59 | 0.50 | 01-OCT-07:49 | 304.10 | 14.04 | 0.00 | 241.67 | 254.48 | 17.59 | 91.00 | 203.00 |
November | 318.83 | 0.60 | 0.50 | 01-NOV-08:09 | 263.21 | 13.84 | 0.00 | 205.17 | 568.06 | 17.35 | 56.83 | 164.33 |
December | 319.00 | 0.61 | 0.50 | 01-DEC-08:50 | 232.93 | 13.00 | 0.00 | 188.50 | 359.69 | 16.33 | 9.50 | 145.50 |
Annual Sum or Average | 4323.33 | 0.59 | 516.01 | 14.01 | 36.67 | 2987.67 | 441.48 | 17.64 | 982.00 | 2557.00 | ||
Minimum of Months | 308.33 | 0.57 | 0.50 | 232.93 | 13.00 | 0.00 | 188.50 | 230.20 | 16.33 | 9.50 | 145.50 | |
Maximum of Months | 405.33 | 0.61 | 0.50 | 1053.35 | 14.42 | 20.17 | 297.00 | 928.92 | 19.20 | 127.83 | 277.67 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.81 | 0.65 | 29-JAN-15:30 | 218.05 | 22.48 | 165.83 | 25.67 | 108.65 | 20.24 | 146.17 | 0.00 |
February | 308.33 | 0.79 | 0.61 | 10-FEB-16:10 | 258.47 | 22.74 | 155.83 | 34.33 | 166.24 | 22.15 | 155.50 | 21.17 |
March | 357.50 | 0.77 | 0.61 | 01-MAR-15:30 | 283.74 | 22.47 | 171.00 | 58.33 | 204.52 | 23.01 | 188.67 | 28.33 |
April | 375.00 | 0.78 | 0.61 | 01-APR-15:20 | 232.83 | 19.98 | 141.33 | 48.67 | 163.75 | 21.02 | 177.33 | 16.83 |
May | 405.33 | 0.76 | 0.61 | 01-MAY-14:50 | 248.42 | 19.86 | 141.50 | 64.50 | 174.23 | 21.12 | 180.17 | 22.00 |
June | 403.50 | 0.75 | 0.61 | 01-JUN-14:00 | 264.29 | 19.86 | 144.67 | 80.17 | 188.71 | 21.15 | 191.83 | 31.17 |
July | 405.00 | 0.76 | 0.61 | 01-JUL-14:39 | 260.99 | 19.77 | 148.83 | 76.67 | 175.94 | 20.94 | 196.50 | 27.33 |
August | 395.83 | 0.76 | 0.61 | 01-AUG-14:00 | 259.28 | 20.17 | 158.00 | 78.00 | 189.84 | 21.48 | 205.00 | 33.00 |
September | 358.83 | 0.76 | 0.61 | 01-SEP-14:30 | 275.97 | 21.68 | 172.00 | 79.83 | 233.52 | 23.53 | 201.83 | 41.00 |
October | 351.17 | 0.77 | 0.61 | 01-OCT-14:00 | 264.91 | 23.14 | 189.00 | 59.83 | 176.24 | 23.50 | 199.67 | 28.67 |
November | 318.83 | 0.78 | 0.61 | 01-NOV-16:10 | 276.11 | 23.74 | 174.83 | 35.00 | 134.06 | 22.30 | 169.83 | 6.83 |
December | 319.00 | 0.82 | 0.65 | 05-DEC-14:39 | 218.04 | 22.56 | 160.67 | 21.00 | 106.08 | 20.23 | 139.33 | 0.00 |
Annual Sum or Average | 4323.33 | 0.77 | 255.50 | 21.41 | 1923.50 | 662.00 | 170.36 | 21.71 | 2151.83 | 256.33 | ||
Minimum of Months | 308.33 | 0.75 | 0.61 | 218.04 | 19.77 | 141.33 | 21.00 | 106.08 | 20.23 | 139.33 | 0.00 | |
Maximum of Months | 405.33 | 0.82 | 0.65 | 283.74 | 23.74 | 189.00 | 80.17 | 233.52 | 23.53 | 205.00 | 41.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13082559.52 | 2295.67 | 03-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13082559.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13082559.52 | 2295.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HP COOLING COIL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.387534E+10 | 0.313172E+10 | 29466.49 | 30-JAN-06:02 | 20759.11 | 0.00 |
February | 0.00 | 0.00 | 0.520107E+10 | 0.417343E+10 | 30913.15 | 09-FEB-06:01 | 19982.62 | 0.00 |
March | 0.00 | 0.00 | 0.763737E+10 | 0.638147E+10 | 30936.20 | 29-MAR-05:01 | 20028.33 | 0.00 |
April | 0.00 | 0.00 | 0.950489E+10 | 0.787443E+10 | 31167.50 | 10-APR-05:01 | 20142.84 | 0.00 |
May | 0.00 | 0.00 | 0.137532E+11 | 0.112723E+11 | 32539.94 | 24-MAY-05:01 | 18670.64 | 0.00 |
June | 0.00 | 0.00 | 0.166006E+11 | 0.124395E+11 | 33048.34 | 08-JUN-05:01 | 18106.14 | 0.00 |
July | 0.00 | 0.00 | 0.190774E+11 | 0.134284E+11 | 32746.96 | 06-JUL-05:01 | 17054.62 | 0.00 |
August | 0.00 | 0.00 | 0.213497E+11 | 0.148476E+11 | 32746.96 | 31-AUG-05:02 | 17457.09 | 0.00 |
September | 0.00 | 0.00 | 0.170427E+11 | 0.121087E+11 | 33541.28 | 23-SEP-05:01 | 17446.20 | 0.00 |
October | 0.00 | 0.00 | 0.137317E+11 | 0.103517E+11 | 33376.24 | 02-OCT-05:01 | 18086.12 | 0.00 |
November | 0.00 | 0.00 | 0.102038E+11 | 0.779666E+10 | 32187.39 | 03-NOV-05:01 | 19885.38 | 0.00 |
December | 0.00 | 0.00 | 0.639514E+10 | 0.501269E+10 | 30844.67 | 06-DEC-06:01 | 19141.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144373E+12 | 0.108819E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.387534E+10 | 0.313172E+10 | 29466.49 | 17054.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213497E+11 | 0.148476E+11 | 33541.28 | 20759.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HP COOLING COIL
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.518371E+09 | 0.389847E+09 | 7102.60 | 28-JAN-14:00 | 7102.60 | 0.00 |
February | 0.00 | 0.00 | 0.386193E+10 | 0.297878E+10 | 32138.99 | 05-FEB-14:25 | 29062.07 | 0.00 |
March | 0.00 | 0.00 | 0.107708E+11 | 0.882805E+10 | 70390.68 | 26-MAR-12:43 | 70276.90 | 0.00 |
April | 0.00 | 0.00 | 0.222935E+11 | 0.183862E+11 | 93031.72 | 30-APR-17:23 | 68934.36 | 0.00 |
May | 0.00 | 0.00 | 0.459703E+11 | 0.379681E+11 | 97430.91 | 24-MAY-17:08 | 67454.74 | 0.00 |
June | 0.00 | 0.00 | 0.590029E+11 | 0.444516E+11 | 101091.83 | 08-JUN-05:07 | 65302.86 | 0.00 |
July | 0.00 | 0.00 | 0.748693E+11 | 0.546119E+11 | 99782.12 | 18-JUL-05:01 | 65648.04 | 0.00 |
August | 0.00 | 0.00 | 0.799910E+11 | 0.574606E+11 | 102339.75 | 08-AUG-05:01 | 62483.56 | 0.00 |
September | 0.00 | 0.00 | 0.597140E+11 | 0.427579E+11 | 102745.01 | 23-SEP-05:08 | 64533.36 | 0.00 |
October | 0.00 | 0.00 | 0.404674E+11 | 0.306789E+11 | 100771.94 | 07-OCT-05:06 | 67310.01 | 0.00 |
November | 0.00 | 0.00 | 0.199529E+11 | 0.150019E+11 | 73901.00 | 05-NOV-11:43 | 73881.07 | 0.00 |
December | 0.00 | 0.00 | 0.517796E+10 | 0.376581E+10 | 40301.81 | 03-DEC-13:25 | 32379.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.422590E+12 | 0.317280E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.518371E+09 | 0.389847E+09 | 7102.60 | 7102.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.799910E+11 | 0.574606E+11 | 102745.01 | 73881.07 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.536947E+09 | 0.20 | 1352.72 | 30-JAN-06:02 | 0.90 |
February | 0.497930E+09 | 0.21 | 1352.72 | 06-FEB-06:01 | 0.90 |
March | 0.592034E+09 | 0.23 | 1352.72 | 01-MAR-06:02 | 0.90 |
April | 0.560477E+09 | 0.22 | 1352.72 | 01-APR-05:02 | 0.90 |
May | 0.661547E+09 | 0.25 | 1352.72 | 01-MAY-05:01 | 0.89 |
June | 0.764369E+09 | 0.28 | 1352.72 | 01-JUN-05:01 | 0.90 |
July | 0.889869E+09 | 0.31 | 1352.72 | 01-JUL-05:01 | 0.89 |
August | 0.100382E+10 | 0.33 | 1352.72 | 01-AUG-05:01 | 0.89 |
September | 0.769246E+09 | 0.28 | 1352.72 | 01-SEP-05:01 | 0.89 |
October | 0.624262E+09 | 0.24 | 1352.72 | 02-OCT-05:01 | 0.89 |
November | 0.542289E+09 | 0.22 | 1352.72 | 01-NOV-05:01 | 0.90 |
December | 0.545438E+09 | 0.21 | 1352.72 | 01-DEC-06:02 | 0.90 |
Annual Sum or Average | 0.798823E+10 | 0.25 | |||
Minimum of Months | 0.497930E+09 | 0.20 | 1352.72 | 0.89 | |
Maximum of Months | 0.100382E+10 | 0.33 | 1352.72 | 0.90 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.238697E+10 | 0.31 | 2411.08 | 13-JAN-13:40 | 0.84 |
February | 0.220551E+10 | 0.32 | 2411.08 | 01-FEB-15:50 | 0.84 |
March | 0.263559E+10 | 0.37 | 4916.23 | 26-MAR-12:43 | 1.27 |
April | 0.267484E+10 | 0.45 | 6027.70 | 30-APR-12:02 | 1.39 |
May | 0.342074E+10 | 0.66 | 6027.70 | 07-MAY-16:23 | 1.39 |
June | 0.374147E+10 | 0.72 | 6027.70 | 01-JUN-17:06 | 1.39 |
July | 0.446218E+10 | 0.74 | 6027.70 | 01-JUL-17:06 | 1.38 |
August | 0.473669E+10 | 0.76 | 6027.70 | 01-AUG-05:01 | 1.38 |
September | 0.372431E+10 | 0.71 | 6027.70 | 01-SEP-17:06 | 1.38 |
October | 0.315209E+10 | 0.61 | 6027.70 | 01-OCT-09:53 | 1.38 |
November | 0.248237E+10 | 0.40 | 5165.38 | 05-NOV-11:43 | 1.30 |
December | 0.240340E+10 | 0.32 | 2411.08 | 09-DEC-16:10 | 0.84 |
Annual Sum or Average | 0.380262E+11 | 0.53 | |||
Minimum of Months | 0.220551E+10 | 0.31 | 2411.08 | 0.84 | |
Maximum of Months | 0.473669E+10 | 0.76 | 6027.70 | 1.39 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148940E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.176947E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.248983E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.298932E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.435599E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.526019E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.614381E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.689452E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.527518E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.410517E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.303981E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.208866E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.459013E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.148940E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.689452E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.253690E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.333303E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.581981E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.937941E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.176546E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.218456E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.277022E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.295187E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.216927E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151584E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.826810E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.388099E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.166790E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.253690E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.295187E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.536947E+09 | 0.387534E+10 | 13082559.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.497930E+09 | 0.520107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.592034E+09 | 0.763737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.560477E+09 | 0.950489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.661547E+09 | 0.137532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.764369E+09 | 0.166006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.889869E+09 | 0.190774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100382E+10 | 0.213497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.769246E+09 | 0.170427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.624262E+09 | 0.137317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.542289E+09 | 0.102038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.545438E+09 | 0.639514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.798823E+10 | 0.144373E+12 | 13082559.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.497930E+09 | 0.387534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100382E+10 | 0.213497E+11 | 13082559.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.238697E+10 | 0.518371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220551E+10 | 0.386193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263559E+10 | 0.107708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.267484E+10 | 0.222935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.342074E+10 | 0.459703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.374147E+10 | 0.590029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.446218E+10 | 0.748693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.473669E+10 | 0.799910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372431E+10 | 0.597140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.315209E+10 | 0.404674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248237E+10 | 0.199529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240340E+10 | 0.517796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380262E+11 | 0.422590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.220551E+10 | 0.518371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.473669E+10 | 0.799910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.536947E+09 | 0.00 | 0.00 | 3942515.77 | 0.948516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.497930E+09 | 0.00 | 0.00 | 0.00 | 0.127154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.592034E+09 | 0.00 | 0.00 | 0.00 | 0.189779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.560477E+09 | 0.00 | 0.00 | 0.00 | 0.242885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.661547E+09 | 0.00 | 0.00 | 0.00 | 0.369444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.764369E+09 | 0.00 | 0.00 | 0.00 | 0.449582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.889869E+09 | 0.00 | 0.00 | 0.00 | 0.525394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100382E+10 | 0.00 | 0.00 | 0.00 | 0.589069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.769246E+09 | 0.00 | 0.00 | 0.00 | 0.450594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.624262E+09 | 0.00 | 0.00 | 0.00 | 0.348091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.542289E+09 | 0.00 | 0.00 | 0.00 | 0.249752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.545438E+09 | 0.00 | 0.00 | 0.00 | 0.154322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.798823E+10 | 0.00 | 0.00 | 3942515.77 | 0.379092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.497930E+09 | 0.00 | 0.00 | 0.00 | 0.948516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100382E+10 | 0.00 | 0.00 | 3942515.77 | 0.589069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.238697E+10 | 0.00 | 0.00 | 0.00 | 0.149931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220551E+10 | 0.00 | 0.00 | 0.00 | 0.112752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263559E+10 | 0.00 | 0.00 | 0.00 | 0.318422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.267484E+10 | 0.00 | 0.00 | 0.00 | 0.670458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.342074E+10 | 0.00 | 0.00 | 0.00 | 0.142338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.374147E+10 | 0.00 | 0.00 | 0.00 | 0.181042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.446218E+10 | 0.00 | 0.00 | 0.00 | 0.232400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.473669E+10 | 0.00 | 0.00 | 0.00 | 0.247820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372431E+10 | 0.00 | 0.00 | 0.00 | 0.179684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.315209E+10 | 0.00 | 0.00 | 0.00 | 0.120063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248237E+10 | 0.00 | 0.00 | 0.00 | 0.578573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240340E+10 | 0.00 | 0.00 | 0.00 | 0.147759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380262E+11 | 0.00 | 0.00 | 0.00 | 0.128764E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.220551E+10 | 0.00 | 0.00 | 0.00 | 0.149931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.473669E+10 | 0.00 | 0.00 | 0.00 | 0.247820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117761E+09 | 0.108481E+09 | 0.00 | 2917171.36 | 0.00 | 9130305.20 | 0.294092E+09 | 0.00 | 0.14 |
February | 59367809.24 | 0.261447E+09 | 0.00 | 2925123.26 | 0.00 | 0.00 | 0.142104E+09 | 0.00 | 0.14 |
March | 39306377.63 | 0.546189E+09 | 0.00 | 3691434.41 | 0.00 | 0.00 | 0.104212E+09 | 0.00 | 0.15 |
April | 2497367.77 | 0.107079E+10 | 0.00 | 3797544.72 | 0.00 | 0.00 | 45568842.39 | 0.00 | 0.15 |
May | 0.00 | 0.205476E+10 | 0.00 | 2102333.21 | 0.00 | 0.00 | 4664256.35 | 0.00 | 0.15 |
June | 0.00 | 0.311687E+10 | 0.00 | 676489.40 | 0.00 | 0.00 | 251439.35 | 0.00 | 0.16 |
July | 0.00 | 0.411329E+10 | 0.00 | 892136.91 | 0.00 | 0.00 | 771179.59 | 0.00 | 0.15 |
August | 0.00 | 0.461945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.340007E+10 | 0.00 | 582286.81 | 0.00 | 0.00 | 561490.05 | 0.00 | 0.15 |
October | 0.00 | 0.220458E+10 | 0.00 | 1064347.74 | 0.00 | 0.00 | 5588659.85 | 0.00 | 0.14 |
November | 0.00 | 0.128376E+10 | 0.00 | 2221236.12 | 0.00 | 0.00 | 11702098.56 | 0.00 | 0.14 |
December | 43404477.75 | 0.417627E+09 | 0.00 | 3198824.23 | 0.00 | 0.00 | 0.130579E+09 | 0.00 | 0.14 |
Annual Sum or Average | 0.262337E+09 | 0.231973E+11 | 0.00 | 24068928.16 | 0.00 | 9130305.20 | 0.740094E+09 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.108481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.117761E+09 | 0.461945E+10 | 0.00 | 3797544.72 | 0.00 | 9130305.20 | 0.294092E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295358E+10 | 18615615.79 | 0.00 | 370034.58 | 402574.47 | 0.00 | 0.505394E+09 | 0.00 | 0.20 |
February | 0.140627E+10 | 0.209999E+09 | 0.00 | 2395527.29 | 0.00 | 0.00 | 0.113398E+10 | 0.00 | 0.20 |
March | 0.925347E+09 | 0.866412E+09 | 0.00 | 4671712.37 | 1510836.93 | 0.00 | 0.941375E+09 | 0.00 | 0.22 |
April | 0.316729E+09 | 0.282848E+10 | 0.00 | 3290040.05 | 175532.15 | 0.00 | 0.450266E+09 | 0.00 | 0.22 |
May | 536458.39 | 0.847821E+10 | 0.00 | 1072240.80 | 3301883.70 | 0.00 | 41073119.49 | 0.00 | 0.25 |
June | 0.00 | 0.143255E+11 | 0.00 | 114067.00 | 0.00 | 0.00 | 1484506.98 | 0.00 | 0.28 |
July | 0.00 | 0.206929E+11 | 0.00 | 202489.73 | 0.00 | 0.00 | 810742.73 | 0.00 | 0.29 |
August | 0.00 | 0.228371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.158036E+11 | 0.00 | 0.00 | 2921316.34 | 0.00 | 0.00 | 0.00 | 0.27 |
October | 503137.52 | 0.838005E+10 | 0.00 | 1379609.33 | 16167600.42 | 0.00 | 69734651.64 | 0.00 | 0.24 |
November | 0.148008E+09 | 0.301182E+10 | 0.00 | 2297443.30 | 891496.93 | 0.00 | 0.161555E+09 | 0.00 | 0.21 |
December | 0.145386E+10 | 0.351917E+09 | 0.00 | 2730018.43 | 1126920.38 | 0.00 | 0.100903E+10 | 0.00 | 0.20 |
Annual Sum or Average | 0.720483E+10 | 0.978045E+11 | 0.00 | 18523182.87 | 26498161.32 | 0.00 | 0.431471E+10 | 0.00 | 0.24 |
Minimum of Months | 0.00 | 18615615.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.295358E+10 | 0.228371E+11 | 0.00 | 4671712.37 | 16167600.42 | 0.00 | 0.113398E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.501244E+12 | 0.167094E+11 | 0.00 | 0.109129E+11 | 0.548301E+10 |
February | 0.568733E+12 | 0.195377E+11 | 0.00 | 0.749280E+10 | 0.114621E+11 |
March | 0.738043E+12 | 0.208130E+11 | 0.00 | 0.410331E+10 | 0.234902E+11 |
April | 0.811151E+12 | 0.327117E+11 | 0.00 | -0.447605E+10 | 0.409318E+11 |
May | 0.898608E+12 | 0.568542E+11 | 0.00 | -0.168178E+11 | 0.776518E+11 |
June | 0.888252E+12 | 0.630776E+11 | 0.00 | -0.266200E+11 | 0.982035E+11 |
July | 0.894282E+12 | 0.534048E+11 | 0.00 | -0.363674E+11 | 0.122441E+12 |
August | 0.864334E+12 | 0.656522E+11 | 0.00 | -0.390438E+11 | 0.132013E+12 |
September | 0.745554E+12 | 0.616548E+11 | 0.00 | -0.292561E+11 | 0.992311E+11 |
October | 0.635277E+12 | 0.496072E+11 | 0.00 | -0.183811E+11 | 0.696864E+11 |
November | 0.496746E+12 | 0.285853E+11 | 0.00 | -0.505406E+10 | 0.384399E+11 |
December | 0.454808E+12 | 0.191217E+11 | 0.00 | 0.737460E+10 | 0.145939E+11 |
Annual Sum or Average | 0.849703E+13 | 0.487730E+12 | 0.00 | -0.146133E+12 | 0.733628E+12 |
Minimum of Months | 0.454808E+12 | 0.167094E+11 | 0.00 | -0.390438E+11 | 0.548301E+10 |
Maximum of Months | 0.898608E+12 | 0.656522E+11 | 0.00 | 0.109129E+11 | 0.132013E+12 |