Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2024-07-03 12:19:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2421.79 | 500.87 | 500.87 |
Net Site Energy | 2421.79 | 500.87 | 500.87 |
Total Source Energy | 5231.67 | 1082.01 | 1082.01 |
Net Source Energy | 5231.67 | 1082.01 | 1082.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1170.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 322.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1251.30 | 1170.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1170.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 133.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1170.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 22.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 133.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 322.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 73.90 | 242.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 258.79 | 242.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 73.90 | 242.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 258.79 | 242.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1251.298 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1251.298 | 100.00 |
Total On-Site and Utility Electric Sources | 1251.298 | 100.00 |
Total Electricity End Uses | 1251.298 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 82.67 |
Time Setpoint Not Met During Occupied Cooling | 3.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3063.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINE STORAGE OFFICE FRONT WALL WINDOW | FINE STORAGE OFFICE LEFT WALL WINDOW | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINE STORAGE OFFICE FRONT WALL WINDOW | FINE STORAGE OFFICE LEFT WALL WINDOW | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 149.82 | 39.41 | 0.00 | 0.00 | 110.41 |
Gross Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Above Ground Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 149.82 | 39.41 | 0.00 | 0.00 | 110.41 |
Gross Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Above Ground Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 21.81 |
Skylight-Roof Ratio [%] | 0.47 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 28.42 | 28.42 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 121.40 | 121.40 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 149.82 | 149.82 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 149.82 | 149.82 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-14:00 | 10-JAN-23:10 | - | - | - | - | - | - | - | - | - | - | 29-JUL-11:50 |
Heating | 0.00 | 390122.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21036.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14933.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1233.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 93431.78 | 390122.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 390122.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 21036.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 12628.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1233.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1268.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 423.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1022.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3962.86 | 1268.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 262.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 211.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 819.60 | 262.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 262.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 211.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 819.60 | 262.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.52 |
ZONE2 FINE STORAGE DIRECT AIR | 6.28 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 23.41 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 23.41 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 279426.36 |
PSZ-OFFICE HEATING COIL | 23208.06 |
PSZ-FINE STORAGE HEATING COIL | 93232.92 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.52 | 1.52 | 1.52 | 1.52 | 1.52 | 1.52 | 1.00 | 1.00 | 1.52 |
PSZ-FINE STORAGE | 6.28 | 6.28 | 6.28 | 6.28 | 6.28 | 6.28 | 1.00 | 1.00 | 6.28 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.52 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 6.28 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.52 | 2520.33 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 6.28 | 10107.91 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.52 | 1.52 | 1.52 | 1.52 | 25102.60 | 23208.06 | 32.21 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 6.28 | 6.28 | 6.28 | 6.28 | 103937.28 | 93232.92 | 26.67 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.52 | 0.758224 | 1.01 | 25102.60 | 12551.30 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 6.28 | 3.14 | 4.19 | 103937.28 | 51968.64 | 0.800660 | 0.800660 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE OFFICE FRONT WALL | FINE STORAGE OFFICE FRONT WALL WINDOW | |
FINE STORAGE OFFICE LEFT WALL | FINE STORAGE OFFICE LEFT WALL WINDOW | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 68 | 44 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 117.24 | 28.42 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 605.78 | 121.40 | 11 | 8 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
2 | SEMIHEATED_ROOF | 18 | 3 | 3 | 0.167 | 1.136 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | NONRES_EXT_WALL_GRD | 19 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 200.0 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 4.938 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
3 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
5 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8212 |
6 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
7 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
16 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
17 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5000E-02 |
18 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2025 |
19 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
20 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
21 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
22 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
23 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
34 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
35 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
36 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
37 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
38 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
39 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
40 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
41 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
42 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
43 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
2 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
3 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
4 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
5 | 3 | -0.53954861E-06 | 0.47047397E-08 | -0.33276159E-05 | 0.24742089E-17 |
6 | 2 | 0.71895056 | 0.67549398E-02 | 0.98308090 | -0.63795361E-06 |
7 | 1 | -21.239987 | 0.46806363 | -6.4456230 | 0.18844773 |
8 | 0 | 21.442615 | 0.44675967 | 6.3841236 | |
9 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
10 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
11 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
12 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
13 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
14 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
15 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
16 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
17 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
18 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
19 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
20 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
21 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
22 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
23 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
24 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
25 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
26 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
27 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
28 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
29 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
30 | 0 | 200.00000 | 200.00000 | 200.00000 | |
31 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
32 | 0 | 4.9377744 | 4.9377744 | 4.9377744 | |
33 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
34 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
35 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
36 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
37 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
38 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
39 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
40 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
41 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
42 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
43 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
44 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
45 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
46 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
47 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
48 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
49 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
50 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
51 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
52 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
53 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
54 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
55 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
56 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
57 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
58 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
59 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
60 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
61 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
62 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
63 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
64 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
65 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
66 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
67 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
68 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
69 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
70 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
71 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
72 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
73 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
74 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
75 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
76 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
77 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
78 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
79 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
80 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
81 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
82 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
83 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
84 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
85 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
86 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
87 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
88 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
89 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
90 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
91 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
92 | 7 | -0.94456721E-13 | 0.24575595E-14 | -0.29735092E-12 | 0.15324278E-15 |
93 | 6 | 0.65405332E-08 | 0.22114619E-09 | 0.28546880E-07 | -0.13451374E-12 |
94 | 5 | -0.97466953E-04 | 0.18937623E-05 | -0.18947583E-03 | 0.64660656E-08 |
95 | 4 | 0.99417931E-01 | 0.92215111E-03 | 0.29140875 | -0.33466744E-04 |
96 | 3 | -2.3345767 | 0.28579858E-01 | -7.2517161 | 0.28937395E-01 |
97 | 2 | 15.247323 | 0.10163225 | 40.822959 | -0.33280368 |
98 | 1 | -29.125752 | 0.45869584E-01 | -80.508872 | 1.0778326 |
99 | 0 | 16.291614 | 0.92288667E-03 | 46.824339 | |
100 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
101 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
102 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
103 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39 | 34 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | NONRESWINDOW_U_0.57_SHGC_EAST_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
5 | SKYLIGHT_U_0.69_SHGC_0.49 | 38 | 1 | VerySmooth | 3.922 | 3.922 | 1.000 | 0.493 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.36905 | 0.28585 | 0.28585 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 2.30798E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.637 | 0.467 | 0.419 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone ZONE1 OFFICE | 1.2500 |
3 | Zone ZONE2 FINE STORAGE | 1.2500 |
4 | Zone ZONE3 BULK STORAGE | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone ZONE1 OFFICE | 1.1500 |
3 | Zone ZONE2 FINE STORAGE | 1.1500 |
4 | Zone ZONE3 BULK STORAGE | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12906.25435 | 14842.19250 | 1.08172 | 1.24398 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.16000 | 6.30335E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 14613.35501 | 18266.69376 | 1.21316 | 1.51645 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60000 | 3.41898E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 49171.16830 | 56546.84355 | 4.12099 | 4.73914 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.58667 | 6.30401E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 59947.36706 | 74934.20882 | 5.02308 | 6.27885 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -27.60000 | 3.41898E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 223541.08730 | 279426.35912 | 18.73183 | 23.41479 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15411.95 | 1.24398 | 1.24398 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 23208.06 | 1.51645 | 1.51645 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 57957.11 | 4.73914 | 4.73914 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 93232.92 | 6.27885 | 6.27885 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.51645 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.27885 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 23.41479 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 23.41479 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 279426.35871 |
6 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.51645 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.51645 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.51645 |
9 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.51645 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.51645 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.51645 |
12 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
13 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.27885 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.27885 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.27885 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 6.27885 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.27885 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 6.27885 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.51645 |
23 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 6.27885 |
24 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.51645 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
26 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.51645 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2520.33249 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.51645 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.51645 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.51645 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.51645 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.51645 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.75822 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.01097 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25102.60000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12551.30000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
39 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25102.60000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23208.06281 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.21000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
43 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 23208.06281 |
44 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.27885 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
46 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.27885 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 10107.91500 |
48 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.27885 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.27885 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.27885 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 6.27885 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.27885 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.13943 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.18590 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 103937.28000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 51968.64000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
59 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 103937.28000 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 93232.91636 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 26.67000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
63 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 93232.91636 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 23925.9 | 10.67 | 10.43 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 99065.1 | 10.67 | 10.43 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2122666960 | 0.2290896121 | Pass | Pass | 0.6723011813 | 1.0548861984 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5187301004 | 0.5539141249 | Pass | Pass | 0.8292403207 | 2.0895801450 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 8.3808565395E-003 | 1.9680674513E-002 | Pass | Pass | 3.4487154144E-002 | 8.9396941656E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7754.12 | 770.48 | 0.00 | 127.69 | 533.10 | 9185.42 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 110.54 | 88.07 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 39.02 | 29.17 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 110.54 | 20.66 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 39.02 | 7.50 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.30 | 0.982 | 1.136 | 3204.84 | 3183.04 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.662 | 0.787 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.662 | 0.787 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 9.73 | 0.00 | 0.00 | 9.73 | 9.73 | 3.241 | 0.391 | 0.431 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 10.79 | 0.00 | 0.00 | 10.79 | 10.79 | 3.241 | 0.391 | 0.431 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 | 3.95 | 0.00 | 0.00 | 3.95 | 3.95 | 3.241 | 0.391 | 0.431 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 | 3.95 | 0.00 | 0.00 | 3.95 | 3.95 | 3.241 | 0.391 | 0.431 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINE STORAGE OFFICE FRONT WALL WINDOW | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 89.88 | 0.00 | 0.00 | 89.88 | 89.88 | 3.241 | 0.391 | 0.431 | No | FINE STORAGE OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
FINE STORAGE OFFICE LEFT WALL WINDOW | NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 | 31.51 | 0.00 | 0.00 | 31.51 | 31.51 | 3.241 | 0.391 | 0.431 | No | FINE STORAGE OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 171.62 | 3.566 | 0.412 | 0.446 | |||||||||||||||||
North Total or Average | 39.41 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 132.21 | 3.663 | 0.418 | 0.451 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINE STORAGE OFFICE FRONT WALL WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
FINE STORAGE OFFICE LEFT WALL WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.57 | 83.57 | 133.84 | |
Exterior Lighting Total | 8532.22 | 133.84 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25102.60 | 20098.65 | 5003.95 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 103937.28 | 83218.42 | 20718.86 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 23925.9 | 10.67 | 10.43 | ||||
PSZ-FINE STORAGE COOLING COIL | 99065.1 | 10.67 | 10.43 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 279426.36 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 23208.06 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 93232.92 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 340.63 | 23.41 | 14880.27 | 635.51 | 1.00 | 1.18 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 966.87 | 1.52 | 2520.33 | 1662.00 | 1.00 | 1.26 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.60 | 966.87 | 6.28 | 10107.91 | 1609.84 | 1.00 | 1.17 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12906.25 | 14842.19 | 62.66 | 1.082 | 1.244 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00819 | 31.16 | 0.00630 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 49171.17 | 56546.84 | 40.58 | 4.121 | 4.739 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 26.70 | 26.70 | 0.00806 | 31.59 | 0.00630 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 34.18 | 0.00639 | 33.24 | 0.00631 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 14613.36 | 18266.69 | 77.11 | 1.213 | 1.516 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00798 | -27.60 | 0.00034 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 59947.37 | 74934.21 | 53.78 | 5.023 | 6.279 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00766 | -27.60 | 0.00034 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 223541.09 | 279426.36 | 87.19 | 18.732 | 23.415 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00747 | -27.60 | 0.00034 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.24 | 1.24 | 1.52 | 1.52 | 1.5164 | 1.5164 | 1.5164 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.74 | 4.74 | 6.28 | 6.28 | 6.2789 | 6.2789 | 6.2789 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3 BULK STORAGE UNIT HEATER | 279426.359 | 279426.359 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 279426.36 | 279426.36 | 23.414789 | 10.00 | 8.70 | 0.00746573 | 21.11 | 13.58 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 10.00 | 0.00746573 | 85.5903 | 279426.36 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 25102.600 | 20098.648 | 1.516450 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 12551.30 | 12489.60 | 1.010967 | 24.50 | 14.80 | 0.00803124 | 11.24 | 9.77 | 0.00800000 | 31.16 | 0.00630335 | 15.63 | 10.1175 | 23.90 | 0.00818604 | 38.7931 | 12906.25 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 23208.063 | 23208.063 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 23208.06 | 23208.06 | 1.516448 | 17.75 | 11.85 | 0.00746946 | 32.21 | 17.30 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 6.7450 | 21.10 | 0.00798499 | 44.8710 | 14613.36 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 103937.280 | 83218.423 | 6.278850 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 51968.64 | 51968.64 | 4.185900 | 27.16 | 15.59 | 0.00790093 | 14.09 | 10.83 | 0.00790093 | 31.80 | 0.00630434 | 15.84 | 10.1462 | 26.70 | 0.00805828 | 32.3345 | 49119.62 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 93232.916 | 93232.916 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 93232.92 | 93232.92 | 6.278851 | 12.64 | 9.50 | 0.00716260 | 26.67 | 15.51 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 6.7642 | 15.56 | 0.00765744 | 60.9603 | 59947.37 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3 BULK STORAGE UNIT HEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 279426.359 | 279426.359 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 23.414789 | 24.65904824 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 279426.36 | 279426.36 | 1.0000 | 24.65904824 | 23.414789 | 10.00 | 8.70 | 0.00746573 | 28857.0 | 21.11 | 13.58 | 0.00800000 | 41534.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 279426.36 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 10.00 | 0.00746573 | 10.00 | 0.00746573 | 85.5903 | 279426.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25102.600 | 20098.648 | 1.516450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7697 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.516448 | 1.59703176 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 12551.30 | 12489.60 | 1.0000 | 1.06468931 | 1.010967 | 24.50 | 14.80 | 0.00803124 | 45066.0 | 11.24 | 9.77 | 0.00800000 | 31470.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12551.30 | 31.16 | 0.00630335 | 15.63 | 0.10228463 | 10.1175 | 23.90 | 0.00818604 | 23.90 | 0.00818604 | 38.7931 | 12906.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23208.063 | 23208.063 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.516448 | 1.59703176 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 23208.06 | 23208.06 | 1.0000 | 1.59703176 | 1.516448 | 17.75 | 11.85 | 0.00746946 | 36761.3 | 32.21 | 17.30 | 0.00800000 | 52852.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23208.06 | -27.60 | 0.00034190 | -27.60 | 0.10228463 | 6.7450 | 21.03 | 0.00798499 | 21.10 | 0.00798499 | 44.8710 | 14613.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 103937.280 | 83218.423 | 6.278850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5274 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 6.278851 | 6.61250830 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 51968.64 | 51968.64 | 1.0000 | 4.40833822 | 4.185900 | 27.16 | 15.59 | 0.00790093 | 47447.3 | 14.09 | 10.83 | 0.00790093 | 34124.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51968.64 | 31.80 | 0.00630434 | 15.84 | 0.42471127 | 10.1462 | 26.70 | 0.00805828 | 26.70 | 0.00805828 | 32.3345 | 49119.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 93232.916 | 93232.916 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 6.278851 | 6.61250830 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 93232.92 | 93232.92 | 1.0000 | 6.61250830 | 6.278851 | 12.64 | 9.50 | 0.00716260 | 30781.4 | 26.67 | 15.51 | 0.00800000 | 47203.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93232.92 | -27.60 | 0.00034190 | -27.60 | 0.42471127 | 6.7642 | 15.56 | 0.00765744 | 15.56 | 0.00765744 | 60.9603 | 59947.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | FixedDryBulb | 0.10 | 1.52 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | FixedDryBulb | 0.42 | 6.28 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2327.67 | 2741.67 | 1763.33 |
ZONE2 FINE STORAGE | 3025.33 | 2876.33 | 2372.33 |
ZONE3 BULK STORAGE | 3275.67 | 3346.50 | 3040.67 |
Facility | 3551.50 | 3388.67 | 3063.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 220.33 | 5.33 | 67.83 | 3.67 |
ZONE2 FINE STORAGE | 466.67 | 55.50 | 28.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 618.50 | 60.83 | 82.67 | 3.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.969 | 0.352 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.843 | 0.327 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.172 | 0.000 | 0.263 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 3498588.87 | 0.00 | 3498588.87 | 2217108.45 | 5715697.32 | 3225648.14 | 5655.78 | 2066.17 | 1038.06 | 0.17 |
ZONE2 FINE STORAGE | 9105017.99 | 0.00 | 9105017.99 | 8997871.09 | 18102889.08 | 13393694.68 | 5672.99 | 2424.60 | 662.41 | 20.10 |
ZONE3 BULK STORAGE | 0.00 | 56778339.56 | 56778339.56 | 44616091.62 | 0.10E+09 | 30805497.77 | 6626.20 | 85.67 | 2048.14 | 5019.40 |
Total Facility | 12603606.86 | 56778339.56 | 69381946.42 | 55831071.16 | 0.13E+09 | 47424840.58 | 7681.02 | 2485.87 | 2860.27 | 5019.40 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2673 | 0.0000 | 0.2673 | 0.0976 | 0.3649 | 0.1023 | 531.94 | 2066.17 | 1037.89 |
ZONE2 FINE STORAGE | 0.6785 | 0.0000 | 0.6785 | 0.2666 | 0.9451 | 0.4247 | 567.60 | 2424.60 | 643.80 |
ZONE3 BULK STORAGE | 0.0000 | 2.5108 | 2.5108 | 1.6982 | 4.2090 | 0.9768 | 2457.75 | 39.92 | 1138.33 |
Total Facility | 0.9457 | 2.5108 | 3.4566 | 2.0624 | 5.5190 | 1.5038 | 2557.02 | 2440.12 | 1932.48 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3880297.54 | 0.00 | 3880297.54 | 3225648.14 | 5655.22 | 0.22 | 3104.56 | 0.17 |
PSZ-FINE STORAGE | 10098408.29 | 0.00 | 10098408.29 | 13393694.68 | 5671.70 | 0.19 | 3088.10 | 20.10 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2964 | 0.0000 | 0.2964 | 0.1023 | 531.39 | 0.22 | 3104.39 |
PSZ-FINE STORAGE | 0.7525 | 0.0000 | 0.7525 | 0.4247 | 566.36 | 0.19 | 3069.45 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2453.79 | 659.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2523.66 | 582.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2938 | 0.5419 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6378 | 1.9743 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 16 | 16 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 382 |
Defaulted Fields | 322 |
Fields with Defaults | 1019 |
Autosized Fields | 42 |
Autosizable Fields | 96 |
Autocalculated Fields | 94 |
Autocalculatable Fields | 138 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1251.30 | 6131.39 | 28-MAY-17:50 | 93431.78 | 17-JUL-15:00 |
Electricity:Building | 762.39 | 6131.39 | 01-JAN-00:10 | 58533.65 | 22-JUN-12:10 |
Electricity:Zone:ZONE1 OFFICE | 60.03 | 926.90 | 01-JAN-00:10 | 3790.09 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 760.12 | 6131.39 | 01-JAN-00:10 | 56228.36 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 463.22 | 3104.69 | 01-JAN-00:10 | 36895.31 | 22-JUN-12:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 322.82 | 0.00 | 01-JAN-14:00 | 27508.52 | 02-JAN-08:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 2.27 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-12:40 |
Ventilation (simple):Fans:Electricity | 2.27 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-12:40 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 2.27 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-12:40 |
ElectricityPurchased:Facility | 1251.30 | 6131.39 | 28-MAY-17:50 | 93431.78 | 17-JUL-15:00 |
ElectricityPurchased:Plant | 1251.30 | 6131.39 | 28-MAY-17:50 | 93431.78 | 17-JUL-15:00 |
Cogeneration:ElectricityPurchased | 1251.30 | 6131.39 | 28-MAY-17:50 | 93431.78 | 17-JUL-15:00 |
General:Cogeneration:ElectricityPurchased | 1251.30 | 6131.39 | 28-MAY-17:50 | 93431.78 | 17-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1251.30 | 6131.39 | 28-MAY-17:50 | 93431.78 | 17-JUL-15:00 |
ElectricityNet:Plant | 1251.30 | 6131.39 | 28-MAY-17:50 | 93431.78 | 17-JUL-15:00 |
Cogeneration:ElectricityNet | 1251.30 | 6131.39 | 28-MAY-17:50 | 93431.78 | 17-JUL-15:00 |
General:Cogeneration:ElectricityNet | 1251.30 | 6131.39 | 28-MAY-17:50 | 93431.78 | 17-JUL-15:00 |
Electricity:HVAC | 343.37 | 0.00 | 01-JAN-14:00 | 36657.29 | 17-JUL-16:00 |
General:Fans:Electricity | 320.55 | 0.00 | 01-JAN-14:00 | 27508.52 | 02-JAN-08:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 22.83 | 0.00 | 01-JAN-00:10 | 24029.04 | 17-JUL-16:00 |
General:Cooling:Electricity | 22.83 | 0.00 | 01-JAN-00:10 | 24029.04 | 17-JUL-16:00 |
ExteriorLights:Electricity | 133.84 | 0.00 | 01-JAN-08:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 133.84 | 0.00 | 01-JAN-08:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 11.69 | 0.00 | 02-JAN-00:10 | 1729.65 | 18-FEB-13:00 |
WaterSystems:Electricity | 11.69 | 0.00 | 02-JAN-00:10 | 1729.65 | 18-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 11.69 | 0.00 | 02-JAN-00:10 | 1729.65 | 18-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1170.49 | 6500.00 | 01-JUL-18:10 | 390122.94 | 10-JAN-23:10 |
NaturalGas:HVAC | 1170.49 | 6500.00 | 01-JUL-18:10 | 390122.94 | 10-JAN-23:10 |
Heating:NaturalGas | 1170.49 | 6500.00 | 01-JUL-18:10 | 390122.94 | 10-JAN-23:10 |
General:Heating:NaturalGas | 1170.49 | 6500.00 | 01-JUL-18:10 | 390122.94 | 10-JAN-23:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUL-11:50 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUL-11:50 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUL-11:50 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUL-11:50 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUL-11:50 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUL-11:50 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUL-11:50 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 29-JUL-11:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1867.36 | 0.00 | 01-JAN-14:00 | 629126.59 | 10-JAN-23:10 |
EnergyTransfer:Building | 1029.66 | 0.00 | 01-JAN-14:00 | 325775.07 | 10-JAN-23:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 68.58 | 0.00 | 01-JAN-00:10 | 26196.25 | 09-JAN-07:10 |
Heating:EnergyTransfer | 946.19 | 0.00 | 01-JAN-14:00 | 325775.07 | 10-JAN-23:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 46.02 | 0.00 | 01-JAN-00:10 | 26196.25 | 09-JAN-07:10 |
General:Heating:EnergyTransfer | 946.19 | 0.00 | 01-JAN-14:00 | 325775.07 | 10-JAN-23:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 46.02 | 0.00 | 01-JAN-00:10 | 26196.25 | 09-JAN-07:10 |
Cooling:EnergyTransfer | 83.47 | 0.00 | 01-JAN-00:10 | 59788.91 | 17-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 22.56 | 0.00 | 01-JAN-00:10 | 13250.42 | 17-JUL-16:30 |
General:Cooling:EnergyTransfer | 83.47 | 0.00 | 01-JAN-00:10 | 59788.91 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 22.56 | 0.00 | 01-JAN-00:10 | 13250.42 | 17-JUL-16:30 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 250.24 | 0.00 | 01-JAN-00:40 | 75769.06 | 10-JAN-23:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 189.32 | 0.00 | 01-JAN-00:40 | 75769.06 | 10-JAN-23:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 189.32 | 0.00 | 01-JAN-00:40 | 75769.06 | 10-JAN-23:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 60.91 | 0.00 | 01-JAN-00:10 | 48122.74 | 23-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 60.91 | 0.00 | 01-JAN-00:10 | 48122.74 | 23-JUL-17:40 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 710.85 | 0.00 | 01-JAN-11:50 | 249722.70 | 10-JAN-23:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 710.85 | 0.00 | 01-JAN-11:50 | 249722.70 | 10-JAN-23:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 710.85 | 0.00 | 01-JAN-11:50 | 249722.70 | 10-JAN-23:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 837.69 | 0.00 | 01-JAN-14:00 | 303351.52 | 10-JAN-23:10 |
HeatingCoils:EnergyTransfer | 748.95 | 0.00 | 01-JAN-14:00 | 303351.52 | 10-JAN-23:10 |
CoolingCoils:EnergyTransfer | 88.74 | 0.00 | 01-JAN-00:10 | 78626.99 | 17-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 46.021 | -22.556 | 0.000 | 0.000 | 9.931 | 30.864 | 29.165 | 18.216 | 0.000 | 0.565 | 0.000 | 0.000 | -24.397 | 0.000 | -32.977 | -54.830 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 189.324 | -60.910 | 0.000 | 0.000 | 24.372 | 239.148 | 0.000 | 77.981 | 0.000 | 1.023 | 0.001 | 0.000 | -91.219 | 0.000 | -118.989 | -260.731 |
ZONE3 BULK STORAGE | 710.848 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 65.338 | 353.598 | 107.344 | 31.708 | 0.000 | 9.858 | 0.000 | 0.000 | -20.656 | 0.000 | -596.028 | -662.010 |
Total Facility | 710.848 | 0.000 | 235.345 | -83.467 | 0.000 | 0.000 | 99.641 | 623.610 | 136.508 | 127.905 | 0.000 | 11.446 | 0.001 | 0.000 | -136.272 | 0.000 | -747.994 | -977.571 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 12-AUG-05:01 | 0.00 | 0.00 | 0.00 | -33966.97 | 0.00 | 0.00 | 82.14 | 583.97 | 550.52 | 0.00 | 0.00 | 0.00 | 34131.54 | 0.00 | -1108.02 | 0.00 | -273.17 | 0.00 |
ZONE2 FINE STORAGE | 02-AUG-19:31 | 0.00 | 0.00 | 0.00 | -130490.39 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 7496.26 | 0.00 | 0.00 | 123199.05 | 0.00 | -0.00 | 0.00 | -2304.72 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-AUG-19:31 | 0.00 | 0.00 | 0.00 | -130490.39 | 0.00 | 0.00 | 0.00 | 5661.51 | 2519.91 | 9208.38 | 0.00 | 0.00 | 132723.98 | 0.00 | -1133.05 | 0.00 | -18490.34 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-JAN-06:31 | 0.00 | 0.00 | 28321.77 | 0.00 | 0.00 | 0.00 | 149.80 | 583.97 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2991.78 | 0.00 | -2984.62 | -23629.66 |
ZONE2 FINE STORAGE | 06-JAN-06:41 | 0.00 | 0.00 | 110512.04 | 0.00 | 0.00 | 0.00 | 395.81 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11066.09 | 0.00 | -14947.72 | -86993.84 |
ZONE3 BULK STORAGE | 10-JAN-22:52 | 249722.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3599.91 | 0.00 | -84770.46 | -166506.88 |
Total Facility | 10-JAN-22:52 | 249722.52 | 0.00 | 101589.43 | 0.00 | 0.00 | 0.00 | 0.00 | 5661.51 | 2519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20832.53 | 0.00 | -102590.79 | -236070.05 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5164 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5164 | 0.0822 | 1.0000 | Not calculated | 0.1023 | 0.0675 | ||
PSZ-FINE STORAGE | 6.2789 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 6.2789 | 0.0896 | 1.0000 | Not calculated | 0.4247 | 0.0676 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5164 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5164 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0675 | ||
PSZ-FINE STORAGE | 6.2789 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 6.2789 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0676 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5164 | 1.5164 | 1.5164 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.2789 | 6.2789 | 6.2789 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5164 | 1.5164 | 1.5164 | 1.5164 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 6.2789 | 6.2789 | 6.2789 | 6.2789 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5164 | 1.5164 | 1.5164 | No | 0.1023 | 0.0675 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.2789 | 6.2789 | 6.2789 | No | 0.4247 | 0.0676 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5164 | 1.5164 | 1.5164 | 1.5164 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 6.2789 | 6.2789 | 6.2789 | 6.2789 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 82.67 |
Number of hours cooling loads not met | 3.67 |
Number of hours not met | 86.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1170.49 | 390122.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 22.83 | 24029.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 133.84 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 2.27 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 320.55 | 27508.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 11.69 | 1729.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 1251.30 |
Natural Gas | 0.00 | 1170.49 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 2421.79 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 4.72 |
Fans (All) | 66.77 |
Service Water Heating | 2.42 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 258.79 |
Subtotal | 258.79 |
Natural Gas [MJ/m2] | |
Space Heating | 242.08 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 242.08 |
Subtotal | 242.08 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 25.75 |
Space Heating | 48.33 |
Space Cooling | 0.94 |
Fans (All) | 13.33 |
Service Water Heating | 0.48 |
Receptacle Equipment | 5.64 |
Miscellaneous | 5.53 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8372.83 | 387.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8680.83 | 79.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7883.00 | 869.67 | 7.33 | 0.00 | 0.00 |
Min | 7883.00 | 79.17 | 0.00 | 0.00 | 0.00 |
Max | 8680.83 | 869.67 | 7.33 | 0.00 | 0.00 |
Average | 8312.22 | 445.33 | 2.44 | 0.00 | 0.00 |
Sum | 24936.67 | 1336.00 | 7.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 81983.00 | 736.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 162335.67 | 28532.67 | 324.67 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 162335.67 | 28532.67 | 324.67 | 0.00 | 0.00 |
Average | 92448.56 | 9756.22 | 108.22 | 0.00 | 0.00 |
Sum | 277345.67 | 29268.67 | 324.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8612.00 | 148.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8688.17 | 71.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8278.17 | 481.83 | 0.00 | 0.00 | 0.00 |
Min | 8278.17 | 71.83 | 0.00 | 0.00 | 0.00 |
Max | 8688.17 | 481.83 | 0.00 | 0.00 | 0.00 |
Average | 8526.11 | 233.89 | 0.00 | 0.00 | 0.00 |
Sum | 25578.33 | 701.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 81814.50 | 904.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 173178.67 | 18014.33 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 173178.67 | 18014.33 | 0.00 | 0.00 | 0.00 |
Average | 96006.72 | 6306.28 | 0.00 | 0.00 | 0.00 |
Sum | 288020.17 | 18918.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.3 | 0.497837E+09 | 701.33 | 14-JAN-16:10 | 9.82 | 4.49 |
February | 687830.75 | 378.26 | 27-FEB-16:00 | 18.90 | 7.06 | 0.465138E+09 | 768.97 | 27-FEB-15:30 | 18.90 | 7.06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.1 | 0.552720E+09 | 768.96 | 02-MAR-16:00 | 8.30 | 3.80 |
April | 0.196463E+09 | 3739.67 | 25-APR-16:00 | 17.80 | 7.70 | 0.554487E+09 | 768.97 | 05-APR-15:39 | 17.80 | 7.70 |
May | 0.128127E+10 | 7843.06 | 19-MAY-16:00 | 27.80 | 14.54 | 0.613964E+09 | 768.98 | 20-MAY-10:39 | 21.83 | 13.45 |
June | 0.447884E+10 | 30427.92 | 30-JUN-05:02 | 10.37 | 8.12 | 0.657761E+09 | 769.01 | 22-JUN-07:49 | 10.37 | 8.12 |
July | 0.670713E+10 | 31568.54 | 22-JUL-05:02 | 8.77 | 7.17 | 0.634672E+09 | 769.03 | 19-JUL-07:40 | 8.77 | 7.17 |
August | 0.612970E+10 | 33968.30 | 12-AUG-05:01 | 13.07 | 6.78 | 0.684640E+09 | 769.01 | 01-AUG-14:09 | 13.07 | 6.78 |
September | 0.308058E+10 | 29496.94 | 02-SEP-05:02 | 14.40 | 8.78 | 0.621388E+09 | 769.05 | 07-SEP-13:30 | 20.00 | 18.14 |
October | 0.668391E+09 | 5398.02 | 18-OCT-16:00 | 24.40 | 11.02 | 0.591430E+09 | 768.97 | 07-OCT-14:09 | 24.40 | 11.02 |
November | 13598117.72 | 1598.34 | 04-NOV-15:00 | 16.70 | 7.97 | 0.509286E+09 | 768.97 | 01-NOV-15:50 | 16.70 | 7.97 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -2.1 | -4.2 | 0.499745E+09 | 707.68 | 06-DEC-16:10 | 8.95 | 4.16 |
Annual Sum or Average | 0.225566E+11 | 0.688307E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.0 | -4.2 | 0.465138E+09 | 701.33 | 8.30 | 3.80 | ||
Maximum of Months | 0.670713E+10 | 33968.30 | 27.80 | 14.54 | 0.684640E+09 | 769.05 | 24.40 | 18.14 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.3 | 0.686119E+09 | 1317.83 | 14-JAN-16:10 | 9.82 | 4.49 |
February | 696245.87 | 149.33 | 22-FEB-14:00 | -5.0 | -6.5 | 0.719363E+09 | 1790.88 | 27-FEB-16:10 | 17.78 | 6.92 |
March | 6677395.37 | 1689.96 | 03-MAR-13:10 | -12.7 | -13.6 | 0.946022E+09 | 1656.15 | 02-MAR-16:10 | -12.7 | -13.6 |
April | 439609.98 | 439.44 | 27-APR-08:20 | -1.3 | -2.9 | 0.115084E+10 | 2222.35 | 25-APR-15:00 | -1.3 | -2.9 |
May | 0.162758E+10 | 102230.13 | 31-MAY-18:31 | 22.43 | 10.13 | 0.146197E+10 | 2246.79 | 19-MAY-15:30 | 22.43 | 10.13 |
June | 0.116731E+11 | 120015.57 | 24-JUN-20:21 | 18.65 | 9.04 | 0.186908E+10 | 2246.88 | 21-JUN-10:00 | 18.65 | 9.04 |
July | 0.231291E+11 | 121888.93 | 11-JUL-19:51 | 18.30 | 8.66 | 0.184503E+10 | 2246.93 | 19-JUL-09:30 | 25.00 | 17.58 |
August | 0.180854E+11 | 130495.97 | 02-AUG-19:31 | 15.97 | 9.26 | 0.196896E+10 | 2246.86 | 22-AUG-13:50 | 24.13 | 15.51 |
September | 0.635531E+10 | 120837.25 | 08-SEP-17:41 | 18.48 | 9.77 | 0.163376E+10 | 2246.97 | 07-SEP-15:20 | 18.48 | 9.77 |
October | 32722737.02 | 4768.56 | 18-OCT-15:00 | 25.00 | 11.61 | 0.129999E+10 | 2246.79 | 18-OCT-15:00 | 24.40 | 11.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 | 1.54 | 0.880504E+09 | 1821.94 | 04-NOV-15:09 | 16.60 | 7.90 |
December | 434666.52 | 237.51 | 13-DEC-13:30 | -5.8 | -7.0 | 0.731374E+09 | 1351.05 | 06-DEC-15:50 | -5.8 | -7.0 |
Annual Sum or Average | 0.609115E+11 | 0.151930E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.7 | -13.6 | 0.686119E+09 | 1317.83 | -12.7 | -13.6 | ||
Maximum of Months | 0.231291E+11 | 130495.97 | 25.00 | 11.61 | 0.196896E+10 | 2246.97 | 25.00 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.3 | 0.657013E+09 | 1166.58 | 14-JAN-15:50 | 10.10 | 4.67 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -12.4 | -13.9 | 0.688055E+09 | 1956.87 | 27-FEB-16:10 | 17.78 | 6.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.1 | 0.928222E+09 | 1798.83 | 22-MAR-15:09 | 11.10 | 4.06 |
April | 0.00 | 0.00 | 01-APR-00:03 | 2.68 | 0.55 | 0.131524E+10 | 3021.31 | 25-APR-15:39 | 17.53 | 7.62 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -1.1 | -3.0 | 0.203004E+10 | 5027.95 | 20-MAY-15:00 | 30.00 | 15.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.36 | 0.399037E+10 | 7461.56 | 29-JUN-15:09 | 32.02 | 14.63 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.32 | 0.498762E+10 | 9097.65 | 17-JUL-13:20 | 36.30 | 17.01 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.96 | 0.493434E+10 | 8546.64 | 05-AUG-15:00 | 35.60 | 17.65 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.59 | 0.299399E+10 | 8091.07 | 02-SEP-15:20 | 34.23 | 16.29 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.94 | 0.157648E+10 | 3411.11 | 18-OCT-15:09 | 24.90 | 11.51 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 | 1.54 | 0.876728E+09 | 2038.44 | 04-NOV-14:00 | 16.70 | 7.97 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -2.1 | -4.2 | 0.684684E+09 | 1270.38 | 06-DEC-13:00 | 11.70 | 5.59 |
Annual Sum or Average | 0.00 | 0.256628E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.9 | 0.657013E+09 | 1166.58 | 10.10 | 4.06 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.32 | 0.498762E+10 | 9097.65 | 36.30 | 17.65 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125410E+11 | 28321.64 | 27-JAN-06:31 | -27.1 |
February | 0.764763E+10 | 25388.09 | 04-FEB-06:11 | -19.6 |
March | 0.604770E+10 | 26358.07 | 06-MAR-06:01 | -16.3 |
April | 0.250530E+10 | 24914.37 | 29-APR-05:12 | -7.6 |
May | 0.163771E+10 | 25058.53 | 01-MAY-05:12 | -0.4 |
June | 0.133183E+09 | 9171.62 | 17-JUN-05:03 | 2.35 |
July | 19319860.85 | 3114.00 | 17-JUL-06:05 | 19.05 |
August | 91711699.36 | 3925.81 | 18-AUG-06:03 | 8.17 |
September | 0.439495E+09 | 24586.24 | 19-SEP-05:01 | 2.20 |
October | 0.133603E+10 | 25078.11 | 10-OCT-05:22 | -6.1 |
November | 0.461401E+10 | 25323.77 | 27-NOV-06:11 | -14.4 |
December | 0.900767E+10 | 27709.61 | 29-DEC-06:31 | -25.4 |
Annual Sum or Average | 0.460207E+11 | |||
Minimum of Months | 19319860.85 | 3114.00 | -27.1 | |
Maximum of Months | 0.125410E+11 | 28321.64 | 19.05 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.551148E+11 | 110511.97 | 06-JAN-06:41 | -25.5 |
February | 0.303772E+11 | 99400.87 | 09-FEB-18:04 | -19.0 |
March | 0.212984E+11 | 108494.18 | 06-MAR-06:01 | -16.3 |
April | 0.736872E+10 | 97230.09 | 29-APR-05:01 | -7.7 |
May | 0.517742E+10 | 97138.30 | 08-MAY-05:01 | -2.8 |
June | 0.110478E+10 | 10091.04 | 16-JUN-06:25 | 2.50 |
July | 0.320852E+09 | 9970.22 | 08-JUL-06:25 | 10.55 |
August | 0.853948E+09 | 10036.68 | 17-AUG-06:25 | 8.30 |
September | 0.252395E+10 | 10137.27 | 12-SEP-06:25 | 5.30 |
October | 0.585032E+10 | 88487.68 | 10-OCT-03:32 | -4.6 |
November | 0.190520E+11 | 98178.13 | 27-NOV-18:04 | -8.3 |
December | 0.402817E+11 | 99832.72 | 28-DEC-18:04 | -22.3 |
Annual Sum or Average | 0.189324E+12 | |||
Minimum of Months | 0.320852E+09 | 9970.22 | -25.5 | |
Maximum of Months | 0.551148E+11 | 110511.97 | 10.55 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250032E+12 | 249722.70 | 10-JAN-22:57 | -33.9 |
February | 0.128100E+12 | 173163.74 | 04-FEB-03:00 | -21.7 |
March | 0.767770E+11 | 173037.82 | 06-MAR-03:58 | -18.3 |
April | 0.667335E+10 | 72465.41 | 29-APR-04:56 | -7.8 |
May | 0.544616E+10 | 61772.71 | 09-MAY-04:53 | -2.2 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.254398E+10 | 50181.06 | 10-OCT-05:58 | -6.1 |
November | 0.676851E+11 | 151671.37 | 27-NOV-05:00 | -15.6 |
December | 0.173592E+12 | 222764.81 | 31-DEC-02:58 | -24.4 |
Annual Sum or Average | 0.710849E+12 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.250032E+12 | 249722.70 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548876E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395155E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368035E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239932E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13535183.14 | 0.242871E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96478059.74 | 0.139496E+10 |
July | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229281E+09 | 0.821153E+09 |
August | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178765E+09 | 0.108581E+10 |
September | 0.138726E+10 | 0.254196E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45574636.94 | 0.181107E+10 |
October | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1226315.46 | 0.234927E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326529E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430055E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564861E+09 | 0.329768E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821153E+09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229281E+09 | 0.548876E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188779E+11 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135733E+11 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125549E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834366E+10 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14954900.97 | 0.900986E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115758E+09 | 0.610329E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383826E+09 | 0.392270E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349625E+09 | 0.475161E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153694E+09 | 0.749836E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4980219.15 | 0.827611E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111285E+11 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149484E+11 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102284E+10 | 0.118989E+12 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392270E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383826E+09 | 0.188779E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682534E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255045E+09 | 0.404823E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4631957.62 | 0.373969E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642159E+09 | 0.213310E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477328E+09 | 0.241858E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15813277.37 | 0.234533E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41298425.32 | 0.197645E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63226444.36 | 0.219263E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384517E+09 | 0.253628E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110815E+10 | 0.197385E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863554E+09 | 0.295763E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180921E+09 | 0.469230E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403664E+10 | 0.378394E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197385E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110815E+10 | 0.682534E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14861.85 | 05-JAN-17:10 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 11260.34 | 01-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 10645.32 | 06-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 6650.88 | 28-APR-16:10 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.11 | 19-MAY-16:10 | 9097.43 | 22-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2023.17 | 29-JUN-16:10 | 4604.06 | 16-JUN-07:00 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.77 | 17-JUL-16:10 | 3632.45 | 05-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2315.18 | 09-AUG-17:00 | 4684.46 | 17-AUG-16:05 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.61 | 01-SEP-16:10 | 6186.27 | 18-SEP-16:03 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.36 | 18-OCT-15:10 | 7255.45 | 10-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 9706.60 | 27-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 12276.47 | 28-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3632.45 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.77 | 14861.85 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 34591.08 | 05-JAN-16:10 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 18426.97 | 01-FEB-17:00 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 16030.02 | 30-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 13662.09 | 14-APR-16:00 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.31 | 20-MAY-16:00 | 22015.42 | 22-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4012.15 | 29-JUN-15:10 | 11907.45 | 14-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4301.47 | 25-JUL-15:10 | 8518.03 | 08-JUL-07:00 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3702.66 | 09-AUG-17:00 | 16787.40 | 17-AUG-15:05 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3983.39 | 02-SEP-15:10 | 15136.61 | 18-SEP-15:13 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.35 | 15-OCT-14:00 | 12991.91 | 31-OCT-16:00 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 15775.38 | 28-NOV-08:00 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 18513.79 | 02-DEC-16:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8518.03 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4301.47 | 34591.08 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 125994.13 | 05-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6149.45 | 27-FEB-13:05 | 66452.48 | 01-FEB-15:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.89 | 14-MAR-12:05 | 53756.34 | 03-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11179.37 | 07-APR-12:10 | 42499.41 | 27-APR-11:00 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9617.93 | 13-MAY-14:00 | 67959.76 | 22-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.14 | 20-JUN-17:00 | 44086.61 | 26-JUN-13:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1869.31 | 30-JUL-11:55 | 32534.26 | 08-JUL-10:00 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1738.07 | 06-AUG-11:55 | 57807.83 | 17-AUG-12:05 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5680.91 | 25-SEP-12:10 | 45754.16 | 12-SEP-11:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14729.00 | 12-OCT-12:10 | 28725.76 | 03-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8548.02 | 17-NOV-17:00 | 49634.07 | 27-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11220.15 | 10-DEC-02:00 | 86493.92 | 27-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28725.76 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14729.00 | 125994.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1828.09 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.08 |
February | 378.26 | 27-FEB-16:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.77 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 457.02 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.51 |
April | 3739.67 | 25-APR-16:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.89 |
May | 7843.06 | 19-MAY-16:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 750.59 | 0.00 |
June | 30427.92 | 30-JUN-05:02 | 924.51 | 2919.87 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.09 |
July | 31568.54 | 22-JUL-05:02 | 924.51 | 2919.87 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33968.30 | 12-AUG-05:01 | 1294.31 | 4087.81 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.17 |
September | 29496.94 | 02-SEP-05:02 | 924.51 | 2919.87 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.15 |
October | 5398.02 | 18-OCT-16:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 60.53 | 0.00 |
November | 1598.34 | 04-NOV-15:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.59 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 2285.11 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1763.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 457.02 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33968.30 | 1680.92 | 4087.81 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 750.59 | 1763.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 8399.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1947.68 |
February | 149.33 | 22-FEB-14:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3042.62 |
March | 1689.96 | 03-MAR-13:10 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4388.44 |
April | 439.44 | 27-APR-08:20 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3499.72 |
May | 102230.13 | 31-MAY-18:31 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1210.73 |
June | 120015.57 | 24-JUN-20:21 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1859.75 |
July | 121888.93 | 11-JUL-19:51 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1731.56 |
August | 130495.97 | 02-AUG-19:31 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2304.72 |
September | 120837.25 | 08-SEP-17:41 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4304.27 |
October | 4768.56 | 18-OCT-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.21 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5344.35 |
December | 237.51 | 13-DEC-13:30 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1924.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.21 | |
Maximum of Months | 130495.97 | 3955.50 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5344.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 12418.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4940.62 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 15523.47 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38436.73 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7908.36 |
April | 0.00 | 01-APR-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10145.64 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10499.17 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2572.37 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8559.90 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5709.86 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7409.13 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15283.92 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10713.89 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 15523.47 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29390.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2572.37 | |
Maximum of Months | 0.00 | 0.00 | 15523.47 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38436.73 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.133338E+12 | 87836.20 | 21-JAN-08:09 | 0.371269E+12 | 390122.94 | 10-JAN-23:10 |
February | 0.112518E+12 | 85293.92 | 17-FEB-13:20 | 0.188304E+12 | 279628.31 | 04-FEB-06:10 |
March | 0.119508E+12 | 85282.56 | 03-MAR-15:50 | 0.113313E+12 | 280501.22 | 06-MAR-06:10 |
April | 0.902626E+11 | 79302.48 | 01-APR-07:10 | 0.265182E+11 | 130038.72 | 29-APR-05:10 |
May | 0.911482E+11 | 84969.11 | 08-MAY-10:09 | 0.248599E+11 | 108215.61 | 08-MAY-05:19 |
June | 0.909122E+11 | 88423.61 | 29-JUN-14:00 | 0.168544E+11 | 10606.58 | 17-JUN-05:10 |
July | 0.962450E+11 | 93431.78 | 17-JUL-14:00 | 0.174096E+11 | 6500.00 | 01-JUL-05:10 |
August | 0.992225E+11 | 91200.37 | 10-AUG-14:00 | 0.174131E+11 | 9055.87 | 18-AUG-05:30 |
September | 0.897353E+11 | 89786.80 | 02-SEP-14:00 | 0.170667E+11 | 19920.46 | 20-SEP-05:10 |
October | 0.907785E+11 | 84573.29 | 10-OCT-08:09 | 0.218272E+11 | 94393.39 | 10-OCT-05:40 |
November | 0.107759E+12 | 87633.63 | 29-NOV-16:49 | 0.102866E+12 | 244797.54 | 27-NOV-06:10 |
December | 0.129870E+12 | 87833.31 | 29-DEC-08:09 | 0.252786E+12 | 353617.94 | 31-DEC-02:00 |
Annual Sum or Average | 0.125130E+13 | 0.117049E+13 | ||||
Minimum of Months | 0.897353E+11 | 79302.48 | 0.168544E+11 | 6500.00 | ||
Maximum of Months | 0.133338E+12 | 93431.78 | 0.371269E+12 | 390122.94 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.145184E+11 | 0.112984E+11 | 0.00 | 0.545711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106463E+10 | 0.00 |
February | 0.474804E+11 | 0.119946E+11 | 0.103734E+11 | 0.00 | 0.416780E+11 | 0.00 | 0.00 | 129.77 | 0.00 | 0.00 | 0.00 | 0.991461E+09 | 0.00 |
March | 0.548234E+11 | 0.117130E+11 | 0.121089E+11 | 0.00 | 0.397208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114221E+10 | 0.00 |
April | 0.513965E+11 | 0.975233E+10 | 0.112578E+11 | 0.00 | 0.168160E+11 | 0.00 | 0.00 | 13528921.30 | 0.00 | 0.00 | 0.00 | 0.102648E+10 | 0.00 |
May | 0.533545E+11 | 0.867215E+10 | 0.117000E+11 | 0.00 | 0.157928E+11 | 0.00 | 0.00 | 0.619208E+09 | 0.00 | 0.00 | 0.00 | 0.100963E+10 | 0.00 |
June | 0.528654E+11 | 0.765852E+10 | 0.116594E+11 | 0.00 | 0.137735E+11 | 0.00 | 0.00 | 0.401345E+10 | 0.00 | 0.00 | 0.00 | 0.941990E+09 | 0.00 |
July | 0.518856E+11 | 0.825236E+10 | 0.112984E+11 | 0.00 | 0.150319E+11 | 0.00 | 0.00 | 0.890550E+10 | 0.00 | 0.00 | 0.00 | 0.871207E+09 | 0.00 |
August | 0.548234E+11 | 0.944517E+10 | 0.121016E+11 | 0.00 | 0.151804E+11 | 0.00 | 0.00 | 0.675974E+10 | 0.00 | 0.00 | 0.00 | 0.912258E+09 | 0.00 |
September | 0.513965E+11 | 0.106431E+11 | 0.112504E+11 | 0.00 | 0.131574E+11 | 0.00 | 0.00 | 0.242362E+10 | 0.00 | 0.00 | 0.00 | 0.864358E+09 | 0.00 |
October | 0.518856E+11 | 0.126243E+11 | 0.113057E+11 | 0.00 | 0.139603E+11 | 0.00 | 0.00 | 91848452.96 | 0.00 | 0.00 | 0.00 | 0.910657E+09 | 0.00 |
November | 0.499276E+11 | 0.136481E+11 | 0.108562E+11 | 0.00 | 0.323979E+11 | 0.00 | 0.00 | 175.05 | 0.00 | 0.00 | 0.00 | 0.929391E+09 | 0.00 |
December | 0.518856E+11 | 0.149229E+11 | 0.112984E+11 | 0.00 | 0.507411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102178E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.133845E+12 | 0.136508E+12 | 0.00 | 0.322821E+12 | 0.00 | 0.00 | 0.228269E+11 | 0.00 | 0.00 | 0.00 | 0.116861E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.765852E+10 | 0.103734E+11 | 0.00 | 0.131574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864358E+09 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.149229E+11 | 0.121089E+11 | 0.00 | 0.545711E+11 | 0.00 | 0.00 | 0.890550E+10 | 0.00 | 0.00 | 0.00 | 0.114221E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.371269E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.188304E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.113313E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.265182E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.248599E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.168544E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.174096E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.174131E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.170667E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.218272E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.102866E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.252786E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117049E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.168544E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.371269E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 27508.52 | 02-JAN-08:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 27508.52 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 27508.52 | 01-MAR-08:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10035.17 | 01-APR-07:10 | 0.00 | 27508.52 | 01-APR-07:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 27508.52 | 08-MAY-06:49 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 14933.54 | 22-JUN-11:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 14933.54 | 01-JUL-12:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 14933.54 | 04-AUG-10:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 14933.54 | 01-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 27508.52 | 10-OCT-06:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 27508.52 | 06-NOV-07:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 27508.52 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10035.17 | 0.00 | 14933.54 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10035.17 | 0.00 | 27508.52 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1726.15 | 31-JAN-12:39 | 0.00 |
February | 0.09 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 1729.65 | 18-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 1728.47 | 01-MAR-12:20 | 0.00 |
April | 1079.18 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 1708.89 | 05-APR-11:09 | 0.00 |
May | 10698.27 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1613.36 | 01-MAY-11:20 | 0.00 |
June | 16480.37 | 29-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1510.76 | 01-JUN-11:30 | 0.00 |
July | 24029.04 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1416.68 | 01-JUL-11:00 | 0.00 |
August | 20059.07 | 05-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1400.34 | 03-AUG-11:00 | 0.00 |
September | 17976.01 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1410.93 | 30-SEP-11:20 | 0.00 |
October | 5472.64 | 18-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1503.87 | 31-OCT-11:30 | 0.00 |
November | 0.07 | 04-NOV-13:09 | 0.00 | 0.00 | 0.00 | 1604.01 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1704.16 | 30-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1400.34 | 0.00 | ||
Maximum of Months | 24029.04 | 0.00 | 0.00 | 0.00 | 1729.65 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 87836.20 | 21-JAN-08:09 | 40988.70 | 10035.17 | 8532.22 | 0.00 | 27508.52 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85293.92 | 17-FEB-13:20 | 46193.18 | 10035.17 | 0.00 | 0.00 | 27508.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85282.56 | 03-MAR-15:50 | 46193.18 | 10035.17 | 0.00 | 0.00 | 27508.52 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79302.48 | 01-APR-07:10 | 40988.70 | 10035.17 | 0.00 | 0.00 | 27508.52 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84969.11 | 08-MAY-10:09 | 46193.18 | 10035.17 | 0.00 | 0.00 | 27508.52 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88423.61 | 29-JUN-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 14933.54 | 0.00 | 0.00 | 16020.11 | 0.00 |
July | 93431.78 | 17-JUL-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 14933.54 | 0.00 | 0.00 | 21036.69 | 0.00 |
August | 91200.37 | 10-AUG-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 14933.54 | 0.00 | 0.00 | 18852.07 | 0.00 |
September | 89786.80 | 02-SEP-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 14933.54 | 0.00 | 0.00 | 17397.33 | 0.00 |
October | 84573.29 | 10-OCT-08:09 | 46193.18 | 10035.17 | 0.00 | 0.00 | 27508.52 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87633.63 | 29-NOV-16:49 | 40988.70 | 10035.17 | 8532.22 | 0.00 | 27508.52 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 87833.31 | 29-DEC-08:09 | 40988.70 | 10035.17 | 8532.22 | 0.00 | 27508.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 79302.48 | 40988.70 | 10035.17 | 0.00 | 0.00 | 14933.54 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93431.78 | 46193.18 | 10035.17 | 8532.22 | 0.00 | 27508.52 | 0.00 | 0.00 | 21036.69 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 390122.94 | 10-JAN-23:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 279628.31 | 04-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 280501.22 | 06-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 130038.72 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 108215.61 | 08-MAY-05:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10606.58 | 17-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 6500.00 | 01-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 9055.87 | 18-AUG-05:30 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 19920.46 | 20-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 94393.39 | 10-OCT-05:40 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 244797.54 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 353617.94 | 31-DEC-02:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 6500.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 390122.94 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.83 | 15.30 | 12.50 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
February | 38.33 | 15.75 | 9.67 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
March | 26.17 | 16.49 | 10.83 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
April | 7.83 | 19.45 | 7.33 | 19.59 | 0.00 | 19.59 | 0.00 | 19.59 |
May | 4.67 | 19.36 | 4.17 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.17 | 26.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.67 | 1.67 | 25.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.96 | 1.50 | 25.38 |
September | 0.83 | 20.28 | 0.83 | 20.28 | 0.33 | 21.03 | 0.33 | 21.56 |
October | 3.50 | 19.85 | 3.50 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
November | 19.67 | 16.84 | 8.67 | 17.62 | 0.00 | 17.62 | 0.00 | 17.62 |
December | 48.50 | 15.70 | 10.33 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
Annual Sum or Average | 220.33 | 16.07 | 67.83 | 16.80 | 5.33 | 16.97 | 3.67 | 17.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | 0.00 | 15.82 |
Maximum of Months | 70.83 | 20.28 | 12.50 | 20.28 | 2.67 | 27.29 | 1.67 | 26.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 113.33 | 13.60 | 5.50 | 13.61 | 0.00 | 13.61 | 0.00 | 13.61 |
February | 86.83 | 14.06 | 5.00 | 14.06 | 0.00 | 14.06 | 0.00 | 14.06 |
March | 73.67 | 14.37 | 7.00 | 14.38 | 0.00 | 14.38 | 0.00 | 14.38 |
April | 13.33 | 14.75 | 1.33 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
May | 8.33 | 14.58 | 0.67 | 14.57 | 0.33 | 15.02 | 0.00 | 15.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.74 | 0.00 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.77 | 0.00 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.79 | 0.00 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.75 | 0.00 | 27.75 |
October | 6.00 | 14.65 | 0.50 | 14.63 | 0.00 | 14.63 | 0.00 | 14.63 |
November | 57.17 | 14.28 | 3.17 | 14.28 | 0.00 | 14.28 | 0.00 | 14.28 |
December | 108.00 | 13.95 | 4.83 | 13.96 | 0.00 | 13.96 | 0.00 | 13.96 |
Annual Sum or Average | 466.67 | 14.04 | 28.00 | 14.04 | 55.50 | 15.43 | 0.00 | 15.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 | 0.00 | 13.61 |
Maximum of Months | 113.33 | 14.75 | 7.00 | 14.75 | 26.00 | 27.79 | 0.00 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.01 | 298.17 | 21.01 | 298.17 | 21.01 |
February | 276.00 | 21.17 | 262.00 | 21.11 | 262.00 | 21.09 |
March | 324.00 | 21.29 | 291.17 | 21.20 | 291.17 | 21.16 |
April | 300.00 | 22.12 | 176.00 | 21.78 | 176.00 | 21.62 |
May | 281.33 | 22.69 | 107.83 | 22.33 | 99.00 | 22.09 |
June | 114.50 | 23.53 | 114.17 | 23.71 | 0.83 | 23.70 |
July | 17.33 | 23.62 | 218.83 | 23.88 | 0.00 | 23.88 |
August | 63.33 | 23.59 | 155.83 | 23.81 | 0.33 | 23.80 |
September | 179.33 | 23.19 | 92.33 | 23.24 | 24.50 | 23.11 |
October | 297.83 | 22.79 | 93.17 | 22.41 | 93.17 | 22.17 |
November | 288.00 | 21.64 | 220.67 | 21.43 | 220.67 | 21.35 |
December | 300.00 | 21.07 | 297.50 | 21.06 | 297.50 | 21.06 |
Annual Sum or Average | 2741.67 | 21.94 | 2327.67 | 21.87 | 1763.33 | 21.67 |
Minimum of Months | 17.33 | 21.01 | 92.33 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 324.00 | 23.62 | 298.17 | 23.88 | 298.17 | 23.88 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.89 | 300.00 | 15.89 | 300.00 | 15.89 |
February | 276.00 | 16.84 | 269.00 | 16.76 | 269.00 | 16.74 |
March | 324.00 | 17.79 | 309.50 | 17.69 | 309.50 | 17.65 |
April | 286.83 | 20.06 | 205.17 | 19.50 | 200.83 | 19.23 |
May | 223.67 | 20.95 | 198.33 | 21.35 | 126.50 | 20.84 |
June | 127.67 | 25.26 | 248.00 | 26.10 | 80.17 | 26.17 |
July | 175.83 | 26.54 | 284.17 | 26.59 | 167.33 | 26.62 |
August | 151.33 | 26.04 | 279.83 | 26.40 | 122.50 | 26.45 |
September | 162.33 | 23.09 | 201.67 | 24.16 | 85.33 | 23.96 |
October | 260.67 | 21.00 | 161.50 | 20.56 | 143.00 | 20.17 |
November | 288.00 | 18.16 | 268.17 | 18.00 | 268.17 | 17.95 |
December | 300.00 | 16.35 | 300.00 | 16.35 | 300.00 | 16.35 |
Annual Sum or Average | 2876.33 | 19.75 | 3025.33 | 20.20 | 2372.33 | 19.85 |
Minimum of Months | 127.67 | 15.89 | 161.50 | 15.89 | 80.17 | 15.89 |
Maximum of Months | 324.00 | 26.54 | 309.50 | 26.59 | 309.50 | 26.62 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.09 | 300.00 | 10.09 | 300.00 | 10.09 |
February | 276.00 | 10.66 | 276.00 | 10.66 | 276.00 | 10.66 |
March | 324.00 | 11.40 | 324.00 | 11.40 | 324.00 | 11.40 |
April | 300.00 | 14.01 | 300.00 | 14.01 | 300.00 | 14.01 |
May | 295.33 | 16.53 | 261.00 | 16.24 | 249.83 | 16.00 |
June | 224.83 | 24.27 | 192.67 | 24.95 | 123.00 | 25.09 |
July | 237.33 | 29.16 | 271.17 | 29.10 | 215.17 | 29.32 |
August | 231.33 | 27.62 | 247.17 | 28.05 | 173.67 | 28.41 |
September | 269.67 | 21.03 | 215.67 | 21.05 | 191.00 | 20.88 |
October | 300.00 | 15.51 | 300.00 | 15.51 | 300.00 | 15.51 |
November | 288.00 | 11.72 | 288.00 | 11.72 | 288.00 | 11.72 |
December | 300.00 | 10.27 | 300.00 | 10.27 | 300.00 | 10.27 |
Annual Sum or Average | 3346.50 | 16.22 | 3275.67 | 16.28 | 3040.67 | 16.07 |
Minimum of Months | 224.83 | 10.09 | 192.67 | 10.09 | 123.00 | 10.09 |
Maximum of Months | 324.00 | 29.16 | 324.00 | 29.10 | 324.00 | 29.32 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 492.26 | 129.77 | 0.67 | 492.26 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:02 | 0.32 | 27-FEB-15:30 | 0.32 | 27-FEB-15:30 | 0.00 | 27-FEB-15:40 | 0.09 | 27-FEB-15:30 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 53260265.60 | 13528921.30 | 13.75 | 53260265.60 | 0.00 | 0.00 | 0.38 | 07-APR-14:00 | 0.00 | 01-APR-00:03 | 4342.60 | 07-APR-14:00 | 4342.60 | 07-APR-14:00 | 0.00 | 06-APR-15:50 | 1079.18 | 07-APR-14:00 | 0.00 | 01-APR-00:03 |
May | 0.880393E+09 | 0.218187E+09 | 61.78 | 0.872518E+09 | 7874356.97 | 0.00 | 0.87 | 19-MAY-16:00 | 0.00 | 01-MAY-00:03 | 10788.99 | 19-MAY-16:00 | 10788.99 | 19-MAY-16:00 | 291.82 | 20-MAY-11:00 | 2673.30 | 19-MAY-16:00 | 0.00 | 01-MAY-00:03 |
June | 0.398159E+10 | 0.985419E+09 | 164.46 | 0.380511E+10 | 0.176483E+09 | 0.00 | 1.00 | 20-JUN-15:30 | 0.00 | 01-JUN-00:10 | 23544.25 | 21-JUN-05:45 | 19905.67 | 23-JUN-05:02 | 8278.75 | 24-JUN-05:02 | 5578.51 | 21-JUN-05:45 | 0.00 | 01-JUN-00:10 |
July | 0.766060E+10 | 0.193142E+10 | 247.91 | 0.736835E+10 | 0.292246E+09 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 25922.96 | 19-JUL-05:01 | 23092.00 | 25-JUL-05:03 | 9988.34 | 19-JUL-05:03 | 6113.60 | 19-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.631724E+10 | 0.159470E+10 | 227.37 | 0.624094E+10 | 76303479.66 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 23092.00 | 05-AUG-05:02 | 23092.00 | 11-AUG-05:01 | 6741.47 | 14-AUG-05:03 | 5466.43 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 0.252158E+10 | 0.624929E+09 | 119.69 | 0.233668E+10 | 0.184905E+09 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 24157.78 | 07-SEP-05:02 | 21468.54 | 05-SEP-05:01 | 9294.08 | 07-SEP-05:03 | 5725.07 | 07-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 0.220752E+09 | 55155657.68 | 33.00 | 0.220752E+09 | -0.0 | 0.00 | 0.67 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 | 7972.13 | 18-OCT-16:00 | 7972.13 | 18-OCT-16:00 | 0.00 | 18-OCT-13:10 | 1909.99 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 664.02 | 175.05 | 1.67 | 664.02 | -0.0 | 0.00 | 0.00 | 04-NOV-13:10 | 0.00 | 01-NOV-00:05 | 0.25 | 04-NOV-13:10 | 0.25 | 04-NOV-13:10 | 0.00 | 04-NOV-13:40 | 0.07 | 04-NOV-13:10 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.216354E+11 | 0.542334E+10 | 870.29 | 0.208976E+11 | 0.737812E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.766060E+10 | 0.193142E+10 | 247.91 | 0.736835E+10 | 0.292246E+09 | 0.00 | 1.00 | 0.00 | 25922.96 | 23092.00 | 9988.34 | 6113.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 |
May | 0.156269E+10 | 0.401021E+09 | 31.38 | 0.156268E+10 | 17383.07 | 0.00 | 1.00 | 19-MAY-19:11 | 0.00 | 01-MAY-00:03 | 99254.59 | 20-MAY-18:31 | 99244.73 | 20-MAY-18:31 | 15.97 | 19-MAY-11:50 | 23523.25 | 20-MAY-18:31 | 0.00 | 01-MAY-00:03 |
June | 0.119015E+11 | 0.302803E+10 | 144.89 | 0.116613E+11 | 0.240184E+09 | 0.00 | 1.00 | 02-JUN-17:11 | 0.00 | 01-JUN-00:10 | 106911.26 | 21-JUN-19:20 | 103167.17 | 25-JUN-19:30 | 26529.89 | 22-JUN-19:41 | 26027.81 | 30-JUN-17:05 | 0.00 | 01-JUN-00:10 |
July | 0.268450E+11 | 0.697408E+10 | 256.60 | 0.264961E+11 | 0.348837E+09 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:10 | 110436.77 | 18-JUL-22:11 | 103411.74 | 16-JUL-24:00 | 48487.37 | 18-JUL-22:11 | 28596.73 | 17-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.197498E+11 | 0.516505E+10 | 196.38 | 0.197260E+11 | 23762269.02 | 0.00 | 1.00 | 01-AUG-17:11 | 0.00 | 01-AUG-00:10 | 103194.03 | 01-AUG-17:34 | 103194.03 | 01-AUG-17:34 | 16690.30 | 13-AUG-16:11 | 27837.10 | 06-AUG-15:43 | 0.00 | 01-AUG-00:10 |
September | 0.690543E+10 | 0.179869E+10 | 84.40 | 0.664007E+10 | 0.265359E+09 | 0.00 | 1.00 | 01-SEP-17:06 | 0.00 | 01-SEP-00:10 | 110480.93 | 06-SEP-18:48 | 103244.14 | 05-SEP-17:10 | 33508.72 | 06-SEP-20:01 | 27362.51 | 02-SEP-17:05 | 0.00 | 01-SEP-00:10 |
October | 0.142052E+09 | 36692795.28 | 3.75 | 0.142052E+09 | 0.00 | 0.00 | 0.30 | 18-OCT-15:00 | 0.00 | 01-OCT-00:10 | 14106.19 | 18-OCT-15:00 | 14106.19 | 18-OCT-15:00 | 0.00 | 18-OCT-14:00 | 3635.11 | 18-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.671065E+11 | 0.174036E+11 | 717.39 | 0.662283E+11 | 0.878160E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.268450E+11 | 0.697408E+10 | 256.60 | 0.264961E+11 | 0.348837E+09 | 0.00 | 1.00 | 0.00 | 110480.93 | 103411.74 | 48487.37 | 28596.73 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.43 | 41.61 | 60.82 | 45.74 | 534.73 | 0.00 | 0.00 | 0.00 |
February | 173.54 | 85.41 | 88.13 | 127.77 | 371.28 | 0.00 | 0.00 | 0.00 |
March | 222.79 | 81.83 | 140.96 | 169.30 | 299.91 | 0.00 | 0.00 | 0.00 |
April | 290.32 | 128.25 | 162.08 | 280.67 | 209.95 | 0.00 | 0.00 | 0.00 |
May | 359.18 | 163.86 | 195.32 | 375.58 | 181.96 | 0.00 | 0.00 | 0.00 |
June | 390.47 | 179.30 | 211.17 | 451.67 | 149.32 | 0.00 | 0.00 | 0.00 |
July | 400.42 | 202.43 | 197.99 | 514.18 | 133.68 | 0.00 | 0.00 | 0.00 |
August | 339.28 | 166.06 | 173.22 | 420.40 | 142.90 | 0.00 | 0.00 | 0.00 |
September | 273.17 | 138.03 | 135.14 | 306.39 | 186.36 | 0.00 | 0.00 | 0.00 |
October | 195.63 | 97.24 | 98.38 | 180.43 | 236.41 | 0.00 | 0.00 | 0.00 |
November | 138.24 | 68.58 | 69.65 | 103.16 | 308.72 | 0.00 | 0.00 | 0.00 |
December | 92.73 | 39.07 | 53.66 | 43.85 | 441.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.52 | 116.09 | 132.44 | 252.24 | 266.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.73 | 39.07 | 53.66 | 43.85 | 133.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 400.42 | 202.43 | 211.17 | 514.18 | 534.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.61 | 46.15 | 67.46 | 50.73 | 593.07 | 0.00 | 0.00 | 0.00 |
February | 192.48 | 94.73 | 97.75 | 141.71 | 411.79 | 0.00 | 0.00 | 0.00 |
March | 247.09 | 90.75 | 156.34 | 187.77 | 332.62 | 0.00 | 0.00 | 0.00 |
April | 322.00 | 142.24 | 179.76 | 311.29 | 232.85 | 0.00 | 0.00 | 0.00 |
May | 398.36 | 181.73 | 216.63 | 416.56 | 201.81 | 0.00 | 0.00 | 0.00 |
June | 433.07 | 198.86 | 234.21 | 500.95 | 165.61 | 0.00 | 0.00 | 0.00 |
July | 444.10 | 224.51 | 219.59 | 570.28 | 148.26 | 0.00 | 0.00 | 0.00 |
August | 376.29 | 184.18 | 192.11 | 466.26 | 158.49 | 0.00 | 0.00 | 0.00 |
September | 302.97 | 153.08 | 149.89 | 339.82 | 206.69 | 0.00 | 0.00 | 0.00 |
October | 216.97 | 107.85 | 109.12 | 200.12 | 262.20 | 0.00 | 0.00 | 0.00 |
November | 153.32 | 76.07 | 77.25 | 114.41 | 342.40 | 0.00 | 0.00 | 0.00 |
December | 102.85 | 43.34 | 59.51 | 48.63 | 490.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.64 | 128.75 | 146.89 | 279.76 | 295.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.85 | 43.34 | 59.51 | 48.63 | 148.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 444.10 | 224.51 | 234.21 | 570.28 | 593.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.86 | 0.00 | 19.86 | 0.31 | 227.69 | 0.00 | 0.00 | 0.00 |
February | 28.04 | 0.00 | 28.04 | 3.80 | 162.95 | 0.00 | 0.00 | 0.00 |
March | 45.56 | 0.00 | 45.56 | 11.72 | 125.91 | 0.00 | 0.00 | 0.00 |
April | 52.10 | 0.39 | 51.71 | 23.84 | 86.85 | 0.00 | 0.00 | 0.00 |
May | 68.17 | 3.99 | 64.18 | 43.00 | 71.18 | 0.00 | 0.00 | 0.00 |
June | 79.34 | 9.06 | 70.28 | 68.58 | 54.20 | 0.00 | 0.00 | 0.00 |
July | 72.47 | 6.70 | 65.77 | 77.87 | 49.25 | 0.00 | 0.00 | 0.00 |
August | 58.75 | 2.12 | 56.63 | 56.42 | 55.77 | 0.00 | 0.00 | 0.00 |
September | 43.59 | 0.04 | 43.56 | 30.85 | 76.34 | 0.00 | 0.00 | 0.00 |
October | 31.77 | 0.00 | 31.77 | 10.15 | 99.21 | 0.00 | 0.00 | 0.00 |
November | 21.59 | 0.00 | 21.59 | 2.72 | 134.15 | 0.00 | 0.00 | 0.00 |
December | 16.66 | 0.00 | 16.66 | 0.15 | 189.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.92 | 1.87 | 43.05 | 27.60 | 110.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.66 | 0.00 | 16.66 | 0.15 | 49.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.34 | 9.06 | 70.28 | 77.87 | 227.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.86 | 0.00 | 19.86 | 0.31 | 227.69 | 0.00 | 0.00 | 0.00 |
February | 28.04 | 0.00 | 28.04 | 3.80 | 162.95 | 0.00 | 0.00 | 0.00 |
March | 45.56 | 0.00 | 45.56 | 11.72 | 125.91 | 0.00 | 0.00 | 0.00 |
April | 52.10 | 0.39 | 51.71 | 23.84 | 86.85 | 0.00 | 0.00 | 0.00 |
May | 68.17 | 3.99 | 64.18 | 43.00 | 71.18 | 0.00 | 0.00 | 0.00 |
June | 79.34 | 9.06 | 70.28 | 68.58 | 54.20 | 0.00 | 0.00 | 0.00 |
July | 72.47 | 6.70 | 65.77 | 77.87 | 49.25 | 0.00 | 0.00 | 0.00 |
August | 58.75 | 2.12 | 56.63 | 56.42 | 55.77 | 0.00 | 0.00 | 0.00 |
September | 43.59 | 0.04 | 43.56 | 30.85 | 76.34 | 0.00 | 0.00 | 0.00 |
October | 31.77 | 0.00 | 31.77 | 10.15 | 99.21 | 0.00 | 0.00 | 0.00 |
November | 21.59 | 0.00 | 21.59 | 2.72 | 134.15 | 0.00 | 0.00 | 0.00 |
December | 16.66 | 0.00 | 16.66 | 0.15 | 189.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.92 | 1.87 | 43.05 | 27.60 | 110.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.66 | 0.00 | 16.66 | 0.15 | 49.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.34 | 9.06 | 70.28 | 77.87 | 227.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINE STORAGE OFFICE FRONT WALL WINDOW
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 946.12 | 384.31 | 561.81 | 469.74 | 4260.85 | 0.00 | 0.00 | 0.00 |
February | 1602.94 | 788.88 | 814.06 | 1253.67 | 2945.56 | 0.00 | 0.00 | 0.00 |
March | 2057.78 | 755.79 | 1301.98 | 1638.13 | 2400.16 | 0.00 | 0.00 | 0.00 |
April | 2681.61 | 1184.57 | 1497.03 | 2610.26 | 1699.91 | 0.00 | 0.00 | 0.00 |
May | 3317.57 | 1513.49 | 1804.08 | 3418.90 | 1503.29 | 0.00 | 0.00 | 0.00 |
June | 3606.61 | 1656.09 | 1950.52 | 3977.75 | 1317.84 | 0.00 | 0.00 | 0.00 |
July | 3698.48 | 1869.73 | 1828.74 | 4536.53 | 1181.82 | 0.00 | 0.00 | 0.00 |
August | 3133.78 | 1533.85 | 1599.94 | 3692.44 | 1263.04 | 0.00 | 0.00 | 0.00 |
September | 2523.14 | 1274.88 | 1248.26 | 2742.76 | 1566.90 | 0.00 | 0.00 | 0.00 |
October | 1806.93 | 898.19 | 908.74 | 1687.55 | 1868.82 | 0.00 | 0.00 | 0.00 |
November | 1276.82 | 633.48 | 643.34 | 1016.82 | 2394.20 | 0.00 | 0.00 | 0.00 |
December | 856.55 | 360.91 | 495.64 | 461.33 | 3483.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2295.51 | 1072.23 | 1223.28 | 2297.46 | 2155.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 856.55 | 360.91 | 495.64 | 461.33 | 1181.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3698.48 | 1869.73 | 1950.52 | 4536.53 | 4260.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINE STORAGE OFFICE LEFT WALL WINDOW
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.50 | 0.00 | 158.50 | 5.46 | 1565.05 | 0.00 | 0.00 | 0.00 |
February | 223.80 | 0.00 | 223.80 | 42.78 | 1108.42 | 0.00 | 0.00 | 0.00 |
March | 363.59 | 0.02 | 363.57 | 118.82 | 866.19 | 0.00 | 0.00 | 0.00 |
April | 415.78 | 3.14 | 412.64 | 201.91 | 603.76 | 0.00 | 0.00 | 0.00 |
May | 543.98 | 31.84 | 512.14 | 339.27 | 508.32 | 0.00 | 0.00 | 0.00 |
June | 633.12 | 72.32 | 560.80 | 492.86 | 412.91 | 0.00 | 0.00 | 0.00 |
July | 578.29 | 53.45 | 524.84 | 557.91 | 374.73 | 0.00 | 0.00 | 0.00 |
August | 468.87 | 16.92 | 451.95 | 395.14 | 425.90 | 0.00 | 0.00 | 0.00 |
September | 347.88 | 0.30 | 347.57 | 226.75 | 555.96 | 0.00 | 0.00 | 0.00 |
October | 253.50 | 0.00 | 253.50 | 90.71 | 678.10 | 0.00 | 0.00 | 0.00 |
November | 172.33 | 0.00 | 172.33 | 32.86 | 894.00 | 0.00 | 0.00 | 0.00 |
December | 132.91 | 0.00 | 132.91 | 4.24 | 1284.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 358.43 | 14.91 | 343.52 | 210.10 | 772.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 132.91 | 0.00 | 132.91 | 4.24 | 374.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 633.12 | 72.32 | 560.80 | 557.91 | 1565.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 15.61 | 128.54 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 45.99 | 86.39 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 88.15 | 67.26 | 2.50 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 119.10 | 45.68 | 6.17 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 158.73 | 40.35 | 5.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 189.99 | 44.55 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 198.92 | 49.44 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 163.10 | 50.13 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 111.49 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 66.23 | 52.91 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 32.52 | 67.81 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 13.10 | 103.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 100.55 | 65.50 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 13.10 | 40.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 198.92 | 128.54 | 6.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 15.61 | 128.54 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 45.99 | 86.39 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 88.15 | 67.26 | 2.50 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 119.10 | 45.68 | 6.17 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 158.73 | 40.35 | 5.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 189.99 | 44.55 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 198.92 | 49.44 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 163.10 | 50.13 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 111.49 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 66.23 | 52.91 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 32.52 | 67.81 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 13.10 | 103.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 100.55 | 65.50 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 13.10 | 40.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 198.92 | 128.54 | 6.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 15.61 | 128.54 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 45.99 | 86.39 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 88.15 | 67.26 | 2.50 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 119.10 | 45.68 | 6.17 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 158.73 | 40.35 | 5.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 189.99 | 44.55 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 198.92 | 49.44 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 163.10 | 50.13 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 111.49 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 66.23 | 52.91 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 32.52 | 67.81 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 13.10 | 103.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 100.55 | 65.50 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 13.10 | 40.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 198.92 | 128.54 | 6.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 15.61 | 128.54 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 45.99 | 86.39 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 88.15 | 67.26 | 2.50 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 119.10 | 45.68 | 6.17 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 158.73 | 40.35 | 5.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 189.99 | 44.55 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 198.92 | 49.44 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 163.10 | 50.13 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 111.49 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 66.23 | 52.91 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 32.52 | 67.81 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 13.10 | 103.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 100.55 | 65.50 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 13.10 | 40.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 198.92 | 128.54 | 6.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 15.61 | 128.54 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 45.99 | 86.39 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 88.15 | 67.26 | 2.50 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 119.10 | 45.68 | 6.17 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 158.73 | 40.35 | 5.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 189.99 | 44.55 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 198.92 | 49.44 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 163.10 | 50.13 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 111.49 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 66.23 | 52.91 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 32.52 | 67.81 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 13.10 | 103.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 100.55 | 65.50 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 13.10 | 40.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 198.92 | 128.54 | 6.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 15.61 | 128.54 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 45.99 | 86.39 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 88.15 | 67.26 | 2.50 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 119.10 | 45.68 | 6.17 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 158.73 | 40.35 | 5.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 189.99 | 44.55 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 198.92 | 49.44 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 163.10 | 50.13 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 111.49 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 66.23 | 52.91 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 32.52 | 67.81 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 13.10 | 103.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 100.55 | 65.50 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 13.10 | 40.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 198.92 | 128.54 | 6.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 15.61 | 128.54 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 45.99 | 86.39 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 88.15 | 67.26 | 2.50 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 119.10 | 45.68 | 6.17 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 158.73 | 40.35 | 5.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 189.99 | 44.55 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 198.92 | 49.44 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 163.10 | 50.13 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 111.49 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 66.23 | 52.91 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 32.52 | 67.81 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 13.10 | 103.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 100.55 | 65.50 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 13.10 | 40.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 198.92 | 128.54 | 6.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 15.61 | 128.54 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 45.99 | 86.39 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 88.15 | 67.26 | 2.50 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 119.10 | 45.68 | 6.17 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 158.73 | 40.35 | 5.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 189.99 | 44.55 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 198.92 | 49.44 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 163.10 | 50.13 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 111.49 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 66.23 | 52.91 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 32.52 | 67.81 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 13.10 | 103.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 100.55 | 65.50 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 13.10 | 40.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 198.92 | 128.54 | 6.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 15.61 | 128.54 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 45.99 | 86.39 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 88.15 | 67.26 | 2.50 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 119.10 | 45.68 | 6.17 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 158.73 | 40.35 | 5.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 189.99 | 44.55 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 198.92 | 49.44 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 163.10 | 50.13 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 111.49 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 66.23 | 52.91 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 32.52 | 67.81 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 13.10 | 103.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 100.55 | 65.50 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 13.10 | 40.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 198.92 | 128.54 | 6.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.43 | 11.83 | 16.60 | 15.61 | 128.54 | 0.00 | 0.00 | 0.00 |
February | 46.92 | 25.81 | 21.11 | 45.99 | 86.39 | 0.00 | 0.00 | 0.00 |
March | 76.76 | 36.57 | 40.19 | 88.15 | 67.26 | 2.50 | 0.00 | 0.00 |
April | 95.17 | 53.21 | 41.97 | 119.10 | 45.68 | 6.17 | 0.00 | 0.00 |
May | 122.18 | 69.69 | 52.49 | 158.73 | 40.35 | 5.00 | 0.00 | 0.00 |
June | 147.14 | 94.46 | 52.68 | 189.99 | 44.55 | 0.00 | 0.00 | 0.00 |
July | 152.33 | 106.59 | 45.74 | 198.92 | 49.44 | 0.00 | 0.00 | 0.00 |
August | 126.82 | 86.46 | 40.36 | 163.10 | 50.13 | 0.00 | 0.00 | 0.00 |
September | 88.03 | 55.81 | 32.22 | 111.49 | 49.93 | 0.00 | 0.00 | 0.00 |
October | 54.84 | 30.49 | 24.35 | 66.23 | 52.91 | 0.00 | 0.00 | 0.00 |
November | 33.20 | 16.34 | 16.86 | 32.52 | 67.81 | 0.00 | 0.00 | 0.00 |
December | 22.30 | 8.73 | 13.56 | 13.10 | 103.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 49.80 | 33.25 | 100.55 | 65.50 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 22.30 | 8.73 | 13.56 | 13.10 | 40.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.33 | 106.59 | 52.68 | 198.92 | 128.54 | 6.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.274353E+09 | 0.111441E+09 | 0.162912E+09 | 0.122515E+09 | 0.143223E+10 |
February | 0.419834E+09 | 0.206619E+09 | 0.213216E+09 | 0.309113E+09 | 0.898206E+09 |
March | 0.596709E+09 | 0.219164E+09 | 0.377546E+09 | 0.453458E+09 | 0.803268E+09 |
April | 0.752521E+09 | 0.332419E+09 | 0.420102E+09 | 0.727503E+09 | 0.544187E+09 |
May | 0.962022E+09 | 0.438878E+09 | 0.523143E+09 | 0.100596E+10 | 0.487358E+09 |
June | 0.101210E+10 | 0.464737E+09 | 0.547361E+09 | 0.117074E+10 | 0.387031E+09 |
July | 0.107247E+10 | 0.542182E+09 | 0.530292E+09 | 0.137719E+10 | 0.358043E+09 |
August | 0.908727E+09 | 0.444782E+09 | 0.463945E+09 | 0.112599E+10 | 0.382750E+09 |
September | 0.708052E+09 | 0.357762E+09 | 0.350291E+09 | 0.794167E+09 | 0.483052E+09 |
October | 0.523969E+09 | 0.260456E+09 | 0.263513E+09 | 0.483268E+09 | 0.633195E+09 |
November | 0.358306E+09 | 0.177771E+09 | 0.180535E+09 | 0.267382E+09 | 0.800203E+09 |
December | 0.248380E+09 | 0.104655E+09 | 0.143725E+09 | 0.117436E+09 | 0.118366E+10 |
Annual Sum or Average | 0.783745E+10 | 0.366087E+10 | 0.417658E+10 | 0.795472E+10 | 0.839318E+10 |
Minimum of Months | 0.248380E+09 | 0.104655E+09 | 0.143725E+09 | 0.117436E+09 | 0.358043E+09 |
Maximum of Months | 0.107247E+10 | 0.542182E+09 | 0.547361E+09 | 0.137719E+10 | 0.143223E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.304284E+09 | 0.123599E+09 | 0.180685E+09 | 0.135881E+09 | 0.158848E+10 |
February | 0.465637E+09 | 0.229160E+09 | 0.236477E+09 | 0.342836E+09 | 0.996197E+09 |
March | 0.661808E+09 | 0.243074E+09 | 0.418734E+09 | 0.502928E+09 | 0.890901E+09 |
April | 0.834619E+09 | 0.368685E+09 | 0.465934E+09 | 0.806871E+09 | 0.603555E+09 |
May | 0.106697E+10 | 0.486758E+09 | 0.580216E+09 | 0.111571E+10 | 0.540527E+09 |
June | 0.112251E+10 | 0.515439E+09 | 0.607076E+09 | 0.129846E+10 | 0.429254E+09 |
July | 0.118948E+10 | 0.601332E+09 | 0.588145E+09 | 0.152743E+10 | 0.397105E+09 |
August | 0.100787E+10 | 0.493306E+09 | 0.514560E+09 | 0.124883E+10 | 0.424507E+09 |
September | 0.785298E+09 | 0.396792E+09 | 0.388506E+09 | 0.880808E+09 | 0.535751E+09 |
October | 0.581132E+09 | 0.288871E+09 | 0.292262E+09 | 0.535991E+09 | 0.702274E+09 |
November | 0.397396E+09 | 0.197165E+09 | 0.200231E+09 | 0.296552E+09 | 0.887502E+09 |
December | 0.275477E+09 | 0.116072E+09 | 0.159405E+09 | 0.130248E+09 | 0.131279E+10 |
Annual Sum or Average | 0.869248E+10 | 0.406025E+10 | 0.463223E+10 | 0.882255E+10 | 0.930884E+10 |
Minimum of Months | 0.275477E+09 | 0.116072E+09 | 0.159405E+09 | 0.130248E+09 | 0.397105E+09 |
Maximum of Months | 0.118948E+10 | 0.601332E+09 | 0.607076E+09 | 0.152743E+10 | 0.158848E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53199176.97 | 0.00 | 53199176.97 | 817426.53 | 0.609845E+09 |
February | 67844768.28 | 0.00 | 67844768.28 | 9189513.62 | 0.394220E+09 |
March | 0.122034E+09 | 6330.77 | 0.122027E+09 | 31379964.62 | 0.337229E+09 |
April | 0.135050E+09 | 1020446.40 | 0.134029E+09 | 61805100.21 | 0.225125E+09 |
May | 0.182578E+09 | 10686258.37 | 0.171892E+09 | 0.115174E+09 | 0.190660E+09 |
June | 0.205643E+09 | 23489286.90 | 0.182154E+09 | 0.177768E+09 | 0.140499E+09 |
July | 0.194096E+09 | 17941108.83 | 0.176155E+09 | 0.208579E+09 | 0.131911E+09 |
August | 0.157369E+09 | 5677652.20 | 0.151691E+09 | 0.151108E+09 | 0.149387E+09 |
September | 0.112993E+09 | 98630.38 | 0.112895E+09 | 79963282.98 | 0.197880E+09 |
October | 85082679.28 | 0.00 | 85082679.28 | 27193079.26 | 0.265724E+09 |
November | 55974221.39 | 0.00 | 55974221.39 | 7038242.62 | 0.347728E+09 |
December | 44610518.05 | 0.00 | 44610518.05 | 390363.24 | 0.508538E+09 |
Annual Sum or Average | 0.141647E+10 | 58919713.85 | 0.135756E+10 | 0.870405E+09 | 0.349875E+10 |
Minimum of Months | 44610518.05 | 0.00 | 44610518.05 | 390363.24 | 0.131911E+09 |
Maximum of Months | 0.205643E+09 | 23489286.90 | 0.182154E+09 | 0.208579E+09 | 0.609845E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53199176.98 | 0.00 | 53199176.98 | 817426.53 | 0.609845E+09 |
February | 67844768.28 | 0.00 | 67844768.28 | 9189513.62 | 0.394220E+09 |
March | 0.122034E+09 | 6330.77 | 0.122027E+09 | 31379964.62 | 0.337229E+09 |
April | 0.135050E+09 | 1020446.40 | 0.134029E+09 | 61805100.20 | 0.225125E+09 |
May | 0.182578E+09 | 10686258.37 | 0.171892E+09 | 0.115174E+09 | 0.190660E+09 |
June | 0.205643E+09 | 23489286.90 | 0.182154E+09 | 0.177768E+09 | 0.140499E+09 |
July | 0.194096E+09 | 17941108.83 | 0.176155E+09 | 0.208579E+09 | 0.131911E+09 |
August | 0.157369E+09 | 5677652.20 | 0.151691E+09 | 0.151108E+09 | 0.149387E+09 |
September | 0.112993E+09 | 98630.38 | 0.112895E+09 | 79963282.98 | 0.197880E+09 |
October | 85082679.28 | 0.00 | 85082679.28 | 27193079.26 | 0.265724E+09 |
November | 55974221.39 | 0.00 | 55974221.39 | 7038242.62 | 0.347728E+09 |
December | 44610518.05 | 0.00 | 44610518.05 | 390363.24 | 0.508538E+09 |
Annual Sum or Average | 0.141647E+10 | 58919713.85 | 0.135756E+10 | 0.870405E+09 | 0.349875E+10 |
Minimum of Months | 44610518.05 | 0.00 | 44610518.05 | 390363.24 | 0.131911E+09 |
Maximum of Months | 0.205643E+09 | 23489286.90 | 0.182154E+09 | 0.208579E+09 | 0.609845E+09 |
Report: WindowEnergyReportMonthly
For: FINE STORAGE OFFICE FRONT WALL WINDOW
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253408E+10 | 0.102933E+10 | 0.150475E+10 | 0.125815E+10 | 0.114123E+11 |
February | 0.387783E+10 | 0.190845E+10 | 0.196938E+10 | 0.303289E+10 | 0.712590E+10 |
March | 0.551155E+10 | 0.202432E+10 | 0.348723E+10 | 0.438758E+10 | 0.642859E+10 |
April | 0.695072E+10 | 0.307041E+10 | 0.388031E+10 | 0.676580E+10 | 0.440617E+10 |
May | 0.888579E+10 | 0.405373E+10 | 0.483206E+10 | 0.915719E+10 | 0.402641E+10 |
June | 0.934833E+10 | 0.429258E+10 | 0.505575E+10 | 0.103103E+11 | 0.341585E+10 |
July | 0.990600E+10 | 0.500790E+10 | 0.489810E+10 | 0.121506E+11 | 0.316539E+10 |
August | 0.839353E+10 | 0.410825E+10 | 0.428528E+10 | 0.988984E+10 | 0.338293E+10 |
September | 0.653998E+10 | 0.330449E+10 | 0.323549E+10 | 0.710923E+10 | 0.406139E+10 |
October | 0.483968E+10 | 0.240572E+10 | 0.243397E+10 | 0.451993E+10 | 0.500546E+10 |
November | 0.330952E+10 | 0.164199E+10 | 0.166753E+10 | 0.263561E+10 | 0.620575E+10 |
December | 0.229418E+10 | 0.966650E+09 | 0.132753E+10 | 0.123563E+10 | 0.933066E+10 |
Annual Sum or Average | 0.723912E+11 | 0.338138E+11 | 0.385774E+11 | 0.724528E+11 | 0.679668E+11 |
Minimum of Months | 0.229418E+10 | 0.966650E+09 | 0.132753E+10 | 0.123563E+10 | 0.316539E+10 |
Maximum of Months | 0.990600E+10 | 0.500790E+10 | 0.505575E+10 | 0.121506E+11 | 0.114123E+11 |
Report: WindowEnergyReportMonthly
For: FINE STORAGE OFFICE LEFT WALL WINDOW
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.424533E+09 | 0.00 | 0.424533E+09 | 14611793.96 | 0.419184E+10 |
February | 0.541406E+09 | 0.00 | 0.541406E+09 | 0.103503E+09 | 0.268148E+10 |
March | 0.973838E+09 | 50520.01 | 0.973787E+09 | 0.318248E+09 | 0.232000E+10 |
April | 0.107771E+10 | 8143233.92 | 0.106956E+10 | 0.523342E+09 | 0.156494E+10 |
May | 0.145699E+10 | 85277092.22 | 0.137171E+10 | 0.908708E+09 | 0.136148E+10 |
June | 0.164105E+10 | 0.187446E+09 | 0.145360E+10 | 0.127749E+10 | 0.107028E+10 |
July | 0.154890E+10 | 0.143171E+09 | 0.140573E+10 | 0.149430E+10 | 0.100367E+10 |
August | 0.125581E+10 | 45308063.25 | 0.121050E+10 | 0.105833E+10 | 0.114074E+10 |
September | 0.901695E+09 | 787077.35 | 0.900908E+09 | 0.587746E+09 | 0.144105E+10 |
October | 0.678966E+09 | 0.00 | 0.678966E+09 | 0.242965E+09 | 0.181623E+10 |
November | 0.446678E+09 | 0.00 | 0.446678E+09 | 85176226.68 | 0.231724E+10 |
December | 0.355995E+09 | 0.00 | 0.355995E+09 | 11365955.85 | 0.344100E+10 |
Annual Sum or Average | 0.113036E+11 | 0.470183E+09 | 0.108334E+11 | 0.662578E+10 | 0.243499E+11 |
Minimum of Months | 0.355995E+09 | 0.00 | 0.355995E+09 | 11365955.85 | 0.100367E+10 |
Maximum of Months | 0.164105E+10 | 0.187446E+09 | 0.145360E+10 | 0.149430E+10 | 0.419184E+10 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 41807721.24 | 0.344291E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.111252E+09 | 0.208994E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.236092E+09 | 0.180144E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.308714E+09 | 0.118414E+09 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.425146E+09 | 0.108063E+09 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.492457E+09 | 0.115470E+09 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.532775E+09 | 0.132408E+09 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.436837E+09 | 0.134275E+09 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.288977E+09 | 0.129415E+09 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.177387E+09 | 0.141716E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 84293963.74 | 0.175752E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.276625E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.317082E+10 | 0.206557E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.108063E+09 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.532775E+09 | 0.344291E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 41807721.24 | 0.344291E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.111252E+09 | 0.208994E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.236092E+09 | 0.180144E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.308714E+09 | 0.118414E+09 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.425146E+09 | 0.108063E+09 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.492457E+09 | 0.115470E+09 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.532775E+09 | 0.132408E+09 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.436837E+09 | 0.134275E+09 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.288977E+09 | 0.129415E+09 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.177387E+09 | 0.141716E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 84293963.74 | 0.175752E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.276625E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.317082E+10 | 0.206557E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.108063E+09 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.532775E+09 | 0.344291E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 41807721.24 | 0.344291E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.111252E+09 | 0.208994E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.236092E+09 | 0.180144E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.308714E+09 | 0.118414E+09 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.425146E+09 | 0.108063E+09 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.492457E+09 | 0.115470E+09 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.532775E+09 | 0.132408E+09 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.436837E+09 | 0.134275E+09 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.288977E+09 | 0.129415E+09 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.177387E+09 | 0.141716E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 84293963.74 | 0.175752E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.276625E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.317082E+10 | 0.206557E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.108063E+09 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.532775E+09 | 0.344291E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 41807721.24 | 0.344291E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.111252E+09 | 0.208994E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.236092E+09 | 0.180144E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.308714E+09 | 0.118414E+09 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.425146E+09 | 0.108063E+09 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.492457E+09 | 0.115470E+09 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.532775E+09 | 0.132408E+09 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.436837E+09 | 0.134275E+09 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.288977E+09 | 0.129415E+09 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.177387E+09 | 0.141716E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 84293963.74 | 0.175752E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.276625E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.317082E+10 | 0.206557E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.108063E+09 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.532775E+09 | 0.344291E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 41807721.24 | 0.344291E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.111252E+09 | 0.208994E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.236092E+09 | 0.180144E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.308714E+09 | 0.118414E+09 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.425146E+09 | 0.108063E+09 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.492457E+09 | 0.115470E+09 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.532775E+09 | 0.132408E+09 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.436837E+09 | 0.134275E+09 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.288977E+09 | 0.129415E+09 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.177387E+09 | 0.141716E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 84293963.74 | 0.175752E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.276625E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.317082E+10 | 0.206557E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.108063E+09 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.532775E+09 | 0.344291E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 41807721.24 | 0.344291E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.111252E+09 | 0.208994E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.236092E+09 | 0.180144E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.308714E+09 | 0.118414E+09 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.425146E+09 | 0.108063E+09 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.492457E+09 | 0.115470E+09 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.532775E+09 | 0.132408E+09 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.436837E+09 | 0.134275E+09 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.288977E+09 | 0.129415E+09 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.177387E+09 | 0.141716E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 84293963.74 | 0.175752E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.276625E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.317082E+10 | 0.206557E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.108063E+09 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.532775E+09 | 0.344291E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 41807721.24 | 0.344291E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.111252E+09 | 0.208994E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.236092E+09 | 0.180144E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.308714E+09 | 0.118414E+09 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.425146E+09 | 0.108063E+09 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.492457E+09 | 0.115470E+09 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.532775E+09 | 0.132408E+09 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.436837E+09 | 0.134275E+09 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.288977E+09 | 0.129415E+09 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.177387E+09 | 0.141716E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 84293963.74 | 0.175752E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.276625E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.317082E+10 | 0.206557E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.108063E+09 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.532775E+09 | 0.344291E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 41807721.24 | 0.344291E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.111252E+09 | 0.208994E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.236092E+09 | 0.180144E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.308714E+09 | 0.118414E+09 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.425146E+09 | 0.108063E+09 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.492457E+09 | 0.115470E+09 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.532775E+09 | 0.132408E+09 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.436837E+09 | 0.134275E+09 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.288977E+09 | 0.129415E+09 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.177387E+09 | 0.141716E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 84293963.74 | 0.175752E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.276625E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.317082E+10 | 0.206557E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.108063E+09 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.532775E+09 | 0.344291E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 41807721.24 | 0.344291E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.111252E+09 | 0.208994E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.236092E+09 | 0.180144E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.308714E+09 | 0.118414E+09 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.425146E+09 | 0.108063E+09 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.492457E+09 | 0.115470E+09 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.532775E+09 | 0.132408E+09 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.436837E+09 | 0.134275E+09 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.288977E+09 | 0.129415E+09 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.177387E+09 | 0.141716E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 84293963.74 | 0.175752E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.276625E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.317082E+10 | 0.206557E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.108063E+09 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.532775E+09 | 0.344291E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 76151318.78 | 31681577.61 | 44469741.16 | 41807721.24 | 0.344291E+09 |
February | 0.113506E+09 | 62437978.37 | 51068079.19 | 0.111252E+09 | 0.208994E+09 |
March | 0.205594E+09 | 97946827.94 | 0.107647E+09 | 0.236092E+09 | 0.180144E+09 |
April | 0.246686E+09 | 0.137909E+09 | 0.108777E+09 | 0.308714E+09 | 0.118414E+09 |
May | 0.327249E+09 | 0.186669E+09 | 0.140580E+09 | 0.425146E+09 | 0.108063E+09 |
June | 0.381375E+09 | 0.244831E+09 | 0.136544E+09 | 0.492457E+09 | 0.115470E+09 |
July | 0.407990E+09 | 0.285478E+09 | 0.122512E+09 | 0.532775E+09 | 0.132408E+09 |
August | 0.339667E+09 | 0.231564E+09 | 0.108103E+09 | 0.436837E+09 | 0.134275E+09 |
September | 0.228164E+09 | 0.144661E+09 | 83502934.36 | 0.288977E+09 | 0.129415E+09 |
October | 0.146882E+09 | 81675448.11 | 65206094.52 | 0.177387E+09 | 0.141716E+09 |
November | 86054524.67 | 42341627.57 | 43712897.10 | 84293963.74 | 0.175752E+09 |
December | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.276625E+09 |
Annual Sum or Average | 0.261903E+10 | 0.157058E+10 | 0.104845E+10 | 0.317082E+10 | 0.206557E+10 |
Minimum of Months | 59715011.75 | 23385958.64 | 36329053.11 | 35085437.10 | 0.108063E+09 |
Maximum of Months | 0.407990E+09 | 0.285478E+09 | 0.140580E+09 | 0.532775E+09 | 0.344291E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 79.89 | 1565.99 | 255.76 | 87.75 | 168.01 | 0.00 | 0.00 |
February | 260.32 | 1092.21 | 422.11 | 180.13 | 241.97 | 0.00 | 0.00 |
March | 372.97 | 876.81 | 561.00 | 172.58 | 388.42 | 0.00 | 0.00 |
April | 634.87 | 611.73 | 716.53 | 271.28 | 445.25 | 0.00 | 0.00 |
May | 874.72 | 522.72 | 893.87 | 353.57 | 540.30 | 0.00 | 0.00 |
June | 1080.62 | 414.17 | 982.21 | 396.28 | 585.94 | 0.00 | 0.00 |
July | 1230.96 | 371.19 | 989.45 | 440.34 | 549.11 | 0.00 | 0.00 |
August | 997.03 | 410.48 | 833.08 | 354.48 | 478.60 | 0.00 | 0.00 |
September | 704.20 | 542.04 | 663.32 | 291.18 | 372.14 | 0.00 | 0.00 |
October | 392.70 | 688.88 | 476.13 | 205.10 | 271.04 | 0.00 | 0.00 |
November | 205.61 | 902.04 | 334.74 | 144.65 | 190.09 | 0.00 | 0.00 |
December | 77.04 | 1296.07 | 228.90 | 82.41 | 146.49 | 0.00 | 0.00 |
Annual Sum or Average | 577.62 | 773.64 | 613.99 | 248.57 | 365.42 | 0.00 | 0.00 |
Minimum of Months | 77.04 | 371.19 | 228.90 | 82.41 | 146.49 | 0.00 | 0.00 |
Maximum of Months | 1230.96 | 1565.99 | 989.45 | 440.34 | 585.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 417.68 | 5768.38 | 1104.62 | 384.31 | 720.31 | 0.00 | 0.00 |
February | 1238.95 | 3996.47 | 1826.74 | 788.88 | 1037.86 | 0.00 | 0.00 |
March | 1730.89 | 3240.28 | 2421.37 | 755.81 | 1665.55 | 0.00 | 0.00 |
April | 2797.06 | 2288.56 | 3097.39 | 1187.71 | 1909.67 | 0.00 | 0.00 |
May | 3742.76 | 1996.19 | 3861.55 | 1545.33 | 2316.22 | 0.00 | 0.00 |
June | 4431.18 | 1691.33 | 4239.73 | 1728.40 | 2511.33 | 0.00 | 0.00 |
July | 5055.17 | 1517.29 | 4276.77 | 1923.19 | 2353.58 | 0.00 | 0.00 |
August | 4077.46 | 1678.83 | 3602.65 | 1550.76 | 2051.89 | 0.00 | 0.00 |
September | 2954.68 | 2108.02 | 2871.02 | 1275.18 | 1595.83 | 0.00 | 0.00 |
October | 1749.58 | 2518.24 | 2060.43 | 898.19 | 1162.24 | 0.00 | 0.00 |
November | 991.81 | 3230.32 | 1449.15 | 633.48 | 815.67 | 0.00 | 0.00 |
December | 407.78 | 4710.60 | 989.46 | 360.91 | 628.56 | 0.00 | 0.00 |
Annual Sum or Average | 2472.75 | 2892.53 | 2653.94 | 1087.14 | 1566.81 | 0.00 | 0.00 |
Minimum of Months | 407.78 | 1517.29 | 989.46 | 360.91 | 628.56 | 0.00 | 0.00 |
Maximum of Months | 5055.17 | 5768.38 | 4276.77 | 1923.19 | 2511.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 156.09 | 1285.44 | 284.32 | 118.29 | 166.03 | 0.00 | 0.00 |
February | 459.87 | 863.90 | 469.19 | 258.09 | 211.09 | 0.00 | 0.00 |
March | 881.47 | 672.58 | 767.60 | 365.69 | 401.91 | 0.00 | 0.00 |
April | 1191.03 | 456.84 | 951.72 | 532.06 | 419.66 | 0.00 | 0.00 |
May | 1587.31 | 403.46 | 1221.81 | 696.94 | 524.86 | 0.00 | 0.00 |
June | 1899.91 | 445.49 | 1471.36 | 944.56 | 526.79 | 0.00 | 0.00 |
July | 1989.15 | 494.36 | 1523.26 | 1065.85 | 457.41 | 0.00 | 0.00 |
August | 1630.96 | 501.32 | 1268.17 | 864.56 | 403.61 | 0.00 | 0.00 |
September | 1114.88 | 499.29 | 880.26 | 558.11 | 322.16 | 0.00 | 0.00 |
October | 662.29 | 529.11 | 548.39 | 304.94 | 243.45 | 0.00 | 0.00 |
November | 325.21 | 678.06 | 332.00 | 163.36 | 168.65 | 0.00 | 0.00 |
December | 130.99 | 1032.80 | 222.95 | 87.31 | 135.64 | 0.00 | 0.00 |
Annual Sum or Average | 1005.46 | 654.99 | 830.49 | 498.03 | 332.46 | 0.00 | 0.00 |
Minimum of Months | 130.99 | 403.46 | 222.95 | 87.31 | 135.64 | 0.00 | 0.00 |
Maximum of Months | 1989.15 | 1285.44 | 1523.26 | 1065.85 | 526.79 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.213968E+09 | 0.419434E+10 | 0.685035E+09 | 0.235040E+09 | 0.449995E+09 | 0.00 | 0.00 |
February | 0.629761E+09 | 0.264228E+10 | 0.102116E+10 | 0.435779E+09 | 0.585382E+09 | 0.00 | 0.00 |
March | 0.998953E+09 | 0.234843E+10 | 0.150258E+10 | 0.462250E+09 | 0.104033E+10 | 0.00 | 0.00 |
April | 0.164559E+10 | 0.158559E+10 | 0.185724E+10 | 0.703145E+09 | 0.115409E+10 | 0.00 | 0.00 |
May | 0.234286E+10 | 0.140004E+10 | 0.239415E+10 | 0.947009E+09 | 0.144714E+10 | 0.00 | 0.00 |
June | 0.280097E+10 | 0.107352E+10 | 0.254590E+10 | 0.102715E+10 | 0.151875E+10 | 0.00 | 0.00 |
July | 0.329700E+10 | 0.994190E+09 | 0.265014E+10 | 0.117940E+10 | 0.147075E+10 | 0.00 | 0.00 |
August | 0.267043E+10 | 0.109943E+10 | 0.223133E+10 | 0.949443E+09 | 0.128189E+10 | 0.00 | 0.00 |
September | 0.182530E+10 | 0.140496E+10 | 0.171934E+10 | 0.754751E+09 | 0.964586E+09 | 0.00 | 0.00 |
October | 0.105182E+10 | 0.184509E+10 | 0.127527E+10 | 0.549326E+09 | 0.725941E+09 | 0.00 | 0.00 |
November | 0.532940E+09 | 0.233809E+10 | 0.867651E+09 | 0.374936E+09 | 0.492715E+09 | 0.00 | 0.00 |
December | 0.206340E+09 | 0.347140E+10 | 0.613078E+09 | 0.220727E+09 | 0.392351E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.182159E+11 | 0.243974E+11 | 0.193629E+11 | 0.783896E+10 | 0.115239E+11 | 0.00 | 0.00 |
Minimum of Months | 0.206340E+09 | 0.994190E+09 | 0.613078E+09 | 0.220727E+09 | 0.392351E+09 | 0.00 | 0.00 |
Maximum of Months | 0.329700E+10 | 0.419434E+10 | 0.265014E+10 | 0.117940E+10 | 0.151875E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111871E+10 | 0.154500E+11 | 0.295861E+10 | 0.102933E+10 | 0.192928E+10 | 0.00 | 0.00 |
February | 0.299727E+10 | 0.966826E+10 | 0.441924E+10 | 0.190845E+10 | 0.251079E+10 | 0.00 | 0.00 |
March | 0.463601E+10 | 0.867877E+10 | 0.648539E+10 | 0.202437E+10 | 0.446102E+10 | 0.00 | 0.00 |
April | 0.724997E+10 | 0.593194E+10 | 0.802843E+10 | 0.307856E+10 | 0.494987E+10 | 0.00 | 0.00 |
May | 0.100246E+11 | 0.534659E+10 | 0.103428E+11 | 0.413901E+10 | 0.620377E+10 | 0.00 | 0.00 |
June | 0.114856E+11 | 0.438394E+10 | 0.109894E+11 | 0.448002E+10 | 0.650936E+10 | 0.00 | 0.00 |
July | 0.135398E+11 | 0.406390E+10 | 0.114549E+11 | 0.515107E+10 | 0.630383E+10 | 0.00 | 0.00 |
August | 0.109211E+11 | 0.449657E+10 | 0.964934E+10 | 0.415356E+10 | 0.549578E+10 | 0.00 | 0.00 |
September | 0.765854E+10 | 0.546400E+10 | 0.744168E+10 | 0.330528E+10 | 0.413640E+10 | 0.00 | 0.00 |
October | 0.468607E+10 | 0.674486E+10 | 0.551865E+10 | 0.240572E+10 | 0.311293E+10 | 0.00 | 0.00 |
November | 0.257076E+10 | 0.837298E+10 | 0.375620E+10 | 0.164199E+10 | 0.211421E+10 | 0.00 | 0.00 |
December | 0.109221E+10 | 0.126169E+11 | 0.265017E+10 | 0.966650E+09 | 0.168352E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.779806E+11 | 0.912187E+11 | 0.836948E+11 | 0.342840E+11 | 0.494108E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109221E+10 | 0.406390E+10 | 0.265017E+10 | 0.966650E+09 | 0.168352E+10 | 0.00 | 0.00 |
Maximum of Months | 0.135398E+11 | 0.154500E+11 | 0.114549E+11 | 0.515107E+10 | 0.650936E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.418077E+09 | 0.344291E+10 | 0.761513E+09 | 0.316816E+09 | 0.444697E+09 | 0.00 | 0.00 |
February | 0.111252E+10 | 0.208994E+10 | 0.113506E+10 | 0.624380E+09 | 0.510681E+09 | 0.00 | 0.00 |
March | 0.236092E+10 | 0.180144E+10 | 0.205594E+10 | 0.979468E+09 | 0.107647E+10 | 0.00 | 0.00 |
April | 0.308714E+10 | 0.118414E+10 | 0.246686E+10 | 0.137909E+10 | 0.108777E+10 | 0.00 | 0.00 |
May | 0.425146E+10 | 0.108063E+10 | 0.327249E+10 | 0.186669E+10 | 0.140580E+10 | 0.00 | 0.00 |
June | 0.492457E+10 | 0.115470E+10 | 0.381375E+10 | 0.244831E+10 | 0.136544E+10 | 0.00 | 0.00 |
July | 0.532775E+10 | 0.132408E+10 | 0.407990E+10 | 0.285478E+10 | 0.122512E+10 | 0.00 | 0.00 |
August | 0.436837E+10 | 0.134275E+10 | 0.339667E+10 | 0.231564E+10 | 0.108103E+10 | 0.00 | 0.00 |
September | 0.288977E+10 | 0.129415E+10 | 0.228164E+10 | 0.144661E+10 | 0.835029E+09 | 0.00 | 0.00 |
October | 0.177387E+10 | 0.141716E+10 | 0.146882E+10 | 0.816754E+09 | 0.652061E+09 | 0.00 | 0.00 |
November | 0.842940E+09 | 0.175752E+10 | 0.860545E+09 | 0.423416E+09 | 0.437129E+09 | 0.00 | 0.00 |
December | 0.350854E+09 | 0.276625E+10 | 0.597150E+09 | 0.233860E+09 | 0.363291E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.317082E+11 | 0.206557E+11 | 0.261903E+11 | 0.157058E+11 | 0.104845E+11 | 0.00 | 0.00 |
Minimum of Months | 0.350854E+09 | 0.108063E+10 | 0.597150E+09 | 0.233860E+09 | 0.363291E+09 | 0.00 | 0.00 |
Maximum of Months | 0.532775E+10 | 0.344291E+10 | 0.407990E+10 | 0.285478E+10 | 0.140580E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.106465E+10 | -974402181.5 | 0.00 | 0.00 | 744.00 | 0.00 | -90252609.2 | 59.95 | 0.00 | 0.00 |
February | 0.991456E+09 | -910485249.5 | 0.00 | 0.00 | 672.00 | 0.00 | -80970993.4 | 59.95 | 0.00 | 0.00 |
March | 0.114219E+10 | -0.105330E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88885766.2 | 59.95 | 0.00 | 0.00 |
April | 0.102647E+10 | -943459161.6 | 0.00 | 0.00 | 720.00 | 0.00 | -83013260.5 | 59.95 | 0.00 | 0.00 |
May | 0.100964E+10 | -928303765.3 | 0.00 | 0.00 | 744.00 | 0.00 | -81334608.2 | 59.95 | 0.00 | 0.00 |
June | 0.942006E+09 | -868887603.5 | 0.00 | 0.00 | 720.00 | 0.00 | -73118365.7 | 59.95 | 0.00 | 0.00 |
July | 0.871189E+09 | -798041611.4 | 0.00 | 0.00 | 744.00 | 0.00 | -73146906.7 | 59.95 | 0.00 | 0.00 |
August | 0.912265E+09 | -838086799.4 | 0.00 | 0.00 | 744.00 | 0.00 | -74178620.7 | 59.95 | 0.00 | 0.00 |
September | 0.864361E+09 | -789621227.6 | 0.00 | 0.00 | 720.00 | 0.00 | -74740065.9 | 59.95 | 0.00 | 0.00 |
October | 0.910670E+09 | -827653082.3 | 0.00 | 0.00 | 744.00 | 0.00 | -83017164.3 | 59.95 | 0.00 | 0.00 |
November | 0.929371E+09 | -844102321.6 | 0.00 | 0.00 | 720.00 | 0.00 | -85268547.3 | 59.95 | 0.00 | 0.00 |
December | 0.102177E+10 | -931781309.3 | 0.00 | 0.00 | 744.00 | 0.00 | -89986529.9 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.116860E+11 | -0.107081E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -977913437.9 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.864361E+09 | -0.105330E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -90252609.2 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.114219E+10 | -789621227.6 | 0.00 | 0.00 | 744.00 | 0.00 | -73118365.7 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123960E+11 | 23208.06 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.711268E+10 | 23208.06 | 01-FEB-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.512702E+10 | 23208.06 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161227E+10 | 23208.06 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104193E+10 | 23208.06 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4274424.56 | 8616.46 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2318219.90 | 3391.01 | 18-AUG-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149658E+09 | 23208.06 | 13-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.720126E+09 | 23208.06 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.369719E+10 | 23208.06 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.847542E+10 | 23208.06 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.403389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123960E+11 | 23208.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.510997E+11 | 93232.92 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258731E+11 | 93232.92 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159515E+11 | 93232.92 | 03-MAR-06:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.255814E+10 | 93232.92 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154289E+10 | 93232.92 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120015E+10 | 85343.38 | 10-OCT-03:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136191E+11 | 93232.92 | 13-NOV-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351310E+11 | 93232.92 | 01-DEC-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146976E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.510997E+11 | 93232.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212927E+12 | 234842.43 | 10-JAN-22:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100804E+12 | 158283.46 | 04-FEB-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.526095E+11 | 158157.55 | 06-MAR-03:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.281040E+10 | 57585.14 | 29-APR-04:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.294788E+10 | 46892.43 | 09-MAY-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126915E+10 | 35300.79 | 10-OCT-05:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.490281E+11 | 136791.09 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139242E+12 | 207884.53 | 31-DEC-02:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212927E+12 | 234842.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 492.26 | 492.26 | 0.32 | 27-FEB-15:30 | 0.32 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 53260265.60 | 53260265.60 | 4342.60 | 07-APR-14:00 | 4342.60 | 0.00 |
May | 0.00 | 0.00 | 0.880393E+09 | 0.872518E+09 | 10788.99 | 19-MAY-16:00 | 10788.99 | 0.00 |
June | 0.00 | 0.00 | 0.398159E+10 | 0.380511E+10 | 23544.25 | 21-JUN-05:45 | 17100.49 | 0.00 |
July | 0.00 | 0.00 | 0.766060E+10 | 0.736835E+10 | 25922.96 | 19-JUL-05:01 | 16036.71 | 0.00 |
August | 0.00 | 0.00 | 0.631724E+10 | 0.624094E+10 | 23092.00 | 05-AUG-05:02 | 21416.76 | 0.00 |
September | 0.00 | 0.00 | 0.252158E+10 | 0.233668E+10 | 24157.78 | 07-SEP-05:02 | 14956.55 | 0.00 |
October | 0.00 | 0.00 | 0.220752E+09 | 0.220752E+09 | 7972.13 | 18-OCT-16:00 | 7972.13 | 0.00 |
November | 0.00 | 0.00 | 664.02 | 664.02 | 0.25 | 04-NOV-13:10 | 0.25 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.216354E+11 | 0.208976E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.766060E+10 | 0.736835E+10 | 25922.96 | 21416.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.156269E+10 | 0.156268E+10 | 99254.59 | 20-MAY-18:31 | 99244.73 | 0.00 |
June | 0.00 | 0.00 | 0.119015E+11 | 0.116613E+11 | 106911.26 | 21-JUN-19:20 | 98832.73 | 0.00 |
July | 0.00 | 0.00 | 0.268450E+11 | 0.264961E+11 | 110436.77 | 18-JUL-22:11 | 61949.40 | 0.00 |
August | 0.00 | 0.00 | 0.197498E+11 | 0.197260E+11 | 103194.03 | 01-AUG-17:34 | 103194.03 | 0.00 |
September | 0.00 | 0.00 | 0.690543E+10 | 0.664007E+10 | 110480.93 | 06-SEP-18:48 | 78922.22 | 0.00 |
October | 0.00 | 0.00 | 0.142052E+09 | 0.142052E+09 | 14106.19 | 18-OCT-15:00 | 14106.19 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.671065E+11 | 0.662283E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.268450E+11 | 0.264961E+11 | 110480.93 | 103194.03 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.371360E+11 | 0.56 | 14880.27 | 01-JAN-00:03 | 0.60 |
February | 0.273403E+11 | 0.45 | 14880.27 | 01-FEB-00:02 | 0.60 |
March | 0.242330E+11 | 0.36 | 14880.27 | 01-MAR-00:10 | 0.60 |
April | 0.391619E+10 | 0.06 | 14880.27 | 01-APR-00:03 | 0.60 |
May | 0.252206E+10 | 0.04 | 14880.27 | 01-MAY-00:03 | 0.60 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.128119E+10 | 0.02 | 14880.27 | 09-OCT-21:10 | 0.60 |
November | 0.187222E+11 | 0.29 | 14880.27 | 02-NOV-02:50 | 0.60 |
December | 0.343891E+11 | 0.52 | 14880.27 | 01-DEC-00:02 | 0.60 |
Annual Sum or Average | 0.149540E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.371360E+11 | 0.56 | 14880.27 | 0.60 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.303279E+10 | 1.25 | 2520.33 | 02-JAN-11:30 | 1.56 |
February | 0.259534E+10 | 1.08 | 2520.33 | 01-FEB-07:10 | 1.57 |
March | 0.290850E+10 | 0.91 | 2520.33 | 15-MAR-13:20 | 1.56 |
April | 0.256719E+10 | 0.66 | 2520.33 | 01-APR-07:30 | 1.56 |
May | 0.264610E+10 | 0.66 | 2520.33 | 24-MAY-06:03 | 1.56 |
June | 0.261127E+10 | 0.63 | 2520.33 | 01-JUN-15:00 | 1.54 |
July | 0.257082E+10 | 0.62 | 2520.33 | 01-JUL-10:15 | 1.54 |
August | 0.275048E+10 | 0.66 | 2520.33 | 01-AUG-06:03 | 1.55 |
September | 0.252960E+10 | 0.63 | 2520.33 | 01-SEP-06:15 | 1.55 |
October | 0.252906E+10 | 0.62 | 2520.33 | 02-OCT-06:07 | 1.56 |
November | 0.256509E+10 | 0.81 | 2520.33 | 01-NOV-06:25 | 1.56 |
December | 0.288493E+10 | 1.14 | 2520.33 | 01-DEC-08:30 | 1.56 |
Annual Sum or Average | 0.321912E+11 | 0.80 | |||
Minimum of Months | 0.252906E+10 | 0.62 | 2520.33 | 1.54 | |
Maximum of Months | 0.303279E+10 | 1.25 | 2520.33 | 1.57 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144024E+11 | 1.34 | 10107.91 | 02-JAN-08:30 | 1.51 |
February | 0.117424E+11 | 1.26 | 10107.91 | 01-FEB-08:70 | 1.52 |
March | 0.125793E+11 | 1.19 | 10107.91 | 01-MAR-07:05 | 1.51 |
April | 0.103327E+11 | 0.77 | 10107.91 | 29-APR-06:20 | 1.52 |
May | 0.106246E+11 | 0.67 | 10107.91 | 06-MAY-06:03 | 1.51 |
June | 0.108853E+11 | 0.67 | 10107.91 | 02-JUN-10:40 | 1.50 |
July | 0.114415E+11 | 0.74 | 10107.91 | 01-JUL-07:10 | 1.49 |
August | 0.116685E+11 | 0.71 | 10107.91 | 08-AUG-17:11 | 1.50 |
September | 0.104111E+11 | 0.64 | 10107.91 | 01-SEP-10:40 | 1.50 |
October | 0.101500E+11 | 0.63 | 10107.91 | 10-OCT-06:30 | 1.51 |
November | 0.111106E+11 | 1.04 | 10107.91 | 03-NOV-06:05 | 1.51 |
December | 0.134671E+11 | 1.32 | 10107.91 | 01-DEC-07:10 | 1.52 |
Annual Sum or Average | 0.138816E+12 | 0.91 | |||
Minimum of Months | 0.101500E+11 | 0.63 | 10107.91 | 1.49 | |
Maximum of Months | 0.144024E+11 | 1.34 | 10107.91 | 1.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.303279E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.259534E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.290850E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.258072E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.286429E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.359669E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.450224E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.434518E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.315453E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.258422E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.256509E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.288493E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.376145E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.256509E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.450224E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.144024E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.117424E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.125793E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.103327E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110256E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.139133E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.184156E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.168336E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.122098E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.101867E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.111106E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.134671E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.156219E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.101867E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.184156E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.303279E+10 | 0.00 | 0.123960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259534E+10 | 492.26 | 0.711268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.290850E+10 | 0.00 | 0.512702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.256719E+10 | 53260265.60 | 0.161227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264610E+10 | 0.880393E+09 | 0.104193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.261127E+10 | 0.398159E+10 | 4274424.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.257082E+10 | 0.766060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.275048E+10 | 0.631724E+10 | 2318219.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252960E+10 | 0.252158E+10 | 0.149658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252906E+10 | 0.220752E+09 | 0.720126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256509E+10 | 664.02 | 0.369719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288493E+10 | 0.00 | 0.847542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321912E+11 | 0.216354E+11 | 0.403389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.252906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.303279E+10 | 0.766060E+10 | 0.123960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144024E+11 | 0.00 | 0.510997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117424E+11 | 0.00 | 0.258731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125793E+11 | 0.00 | 0.159515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103327E+11 | 0.00 | 0.255814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106246E+11 | 0.156269E+10 | 0.154289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108853E+11 | 0.119015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114415E+11 | 0.268450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116685E+11 | 0.197498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104111E+11 | 0.690543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101500E+11 | 0.142052E+09 | 0.120015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111106E+11 | 0.00 | 0.136191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134671E+11 | 0.00 | 0.351310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138816E+12 | 0.671065E+11 | 0.146976E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144024E+11 | 0.268450E+11 | 0.510997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.303279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259534E+10 | 0.00 | 0.00 | 0.00 | 129.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.290850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.256719E+10 | 0.00 | 0.00 | 0.00 | 13528921.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264610E+10 | 0.00 | 0.00 | 0.00 | 0.218187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.261127E+10 | 0.00 | 0.00 | 0.00 | 0.985419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.257082E+10 | 0.00 | 0.00 | 0.00 | 0.193142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.275048E+10 | 0.00 | 0.00 | 0.00 | 0.159470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252960E+10 | 0.00 | 0.00 | 0.00 | 0.624929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252906E+10 | 0.00 | 0.00 | 0.00 | 55155657.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256509E+10 | 0.00 | 0.00 | 0.00 | 175.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321912E+11 | 0.00 | 0.00 | 0.00 | 0.542334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.252906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.303279E+10 | 0.00 | 0.00 | 0.00 | 0.193142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106246E+11 | 0.00 | 0.00 | 0.00 | 0.401021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108853E+11 | 0.00 | 0.00 | 0.00 | 0.302803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114415E+11 | 0.00 | 0.00 | 0.00 | 0.697408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116685E+11 | 0.00 | 0.00 | 0.00 | 0.516505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104111E+11 | 0.00 | 0.00 | 0.00 | 0.179869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101500E+11 | 0.00 | 0.00 | 0.00 | 36692795.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138816E+12 | 0.00 | 0.00 | 0.00 | 0.174036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144024E+11 | 0.00 | 0.00 | 0.00 | 0.697408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33410866.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297349E+10 | 0.00 | 0.00 | 0.12 |
February | 0.157130E+09 | 0.00 | 0.00 | 1146.52 | 0.00 | 0.203599E+10 | 9792638.22 | 0.00 | 0.13 |
March | 0.410728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174004E+10 | 0.00 | 0.00 | 0.13 |
April | 0.737375E+09 | 0.00 | 0.00 | 327334.17 | 0.00 | 0.695500E+09 | 0.652796E+09 | 0.00 | 0.24 |
May | 0.619245E+09 | 1731256.82 | 0.00 | 1851486.85 | 1487172.25 | 0.317274E+09 | 0.190050E+10 | 0.00 | 0.48 |
June | 84274715.13 | 75794410.62 | 0.00 | 5594428.96 | 0.00 | 0.00 | 0.355110E+10 | 0.00 | 0.84 |
July | 23665167.93 | 0.159613E+09 | 0.00 | 8727428.56 | 0.00 | 0.00 | 0.228173E+10 | 0.00 | 0.71 |
August | 73639906.51 | 93997788.96 | 0.00 | 7462325.49 | 0.00 | 0.00 | 0.297889E+10 | 0.00 | 0.83 |
September | 0.367358E+09 | 55870459.18 | 0.00 | 4438093.57 | 0.00 | 28821407.63 | 0.291875E+10 | 0.00 | 0.70 |
October | 0.794048E+09 | 159699.53 | 0.00 | 1067763.63 | 0.00 | 0.232847E+09 | 0.167152E+10 | 0.00 | 0.38 |
November | 0.602701E+09 | 0.00 | 0.00 | 22658.14 | 0.00 | 0.114332E+10 | 93740103.85 | 0.00 | 0.13 |
December | 0.112247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238666E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.401582E+10 | 0.387167E+09 | 0.00 | 29492665.89 | 1487172.25 | 0.115539E+11 | 0.160588E+11 | 0.00 | 0.40 |
Minimum of Months | 23665167.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.794048E+09 | 0.159613E+09 | 0.00 | 8727428.56 | 1487172.25 | 0.297349E+10 | 0.355110E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.162159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822891E+10 | 0.00 | 0.00 | 0.17 |
February | 0.303687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395275E+10 | 0.00 | 0.00 | 0.18 |
March | 0.528394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167035E+10 | 0.00 | 0.00 | 0.19 |
April | 0.547147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63387563.97 | 0.00 | 0.00 | 0.19 |
May | 0.524494E+10 | 0.00 | 0.00 | 2652809.00 | 7130549.92 | 77608794.72 | 0.216107E+10 | 0.00 | 0.35 |
June | 0.193994E+10 | 78571880.93 | 0.00 | 16620870.86 | 0.00 | 0.00 | 0.918088E+10 | 0.00 | 0.70 |
July | 0.528533E+09 | 0.197684E+09 | 0.00 | 31730930.89 | 0.00 | 0.00 | 0.895741E+10 | 0.00 | 0.73 |
August | 0.121562E+10 | 0.118215E+09 | 0.00 | 22116972.54 | 0.00 | 0.00 | 0.953214E+10 | 0.00 | 0.77 |
September | 0.369040E+10 | 64691323.54 | 0.00 | 7935024.97 | 0.00 | 0.00 | 0.452083E+10 | 0.00 | 0.47 |
October | 0.536094E+10 | 0.00 | 0.00 | 53628.15 | 0.00 | 85721623.20 | 40275812.78 | 0.00 | 0.20 |
November | 0.422570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129320E+10 | 0.00 | 0.00 | 0.17 |
December | 0.282804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511169E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.404480E+11 | 0.459162E+09 | 0.00 | 81110236.40 | 7130549.92 | 0.204836E+11 | 0.343926E+11 | 0.00 | 0.36 |
Minimum of Months | 0.528533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.547147E+10 | 0.197684E+09 | 0.00 | 31730930.89 | 7130549.92 | 0.822891E+10 | 0.953214E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.269365E+12 | 0.127519E+12 | 0.00 | 0.128574E+11 | 0.948450E+11 |
February | 0.378879E+12 | 0.783966E+11 | 0.00 | 0.919253E+10 | 0.545146E+11 |
March | 0.683635E+12 | 0.738744E+11 | 0.00 | 0.910505E+10 | 0.396254E+11 |
April | 0.730382E+12 | 0.437378E+11 | 0.00 | 0.762021E+10 | 0.196042E+11 |
May | 0.100588E+13 | 0.490966E+11 | 0.00 | 0.103493E+11 | 0.223895E+11 |
June | 0.113348E+13 | 0.496789E+11 | 0.00 | 0.148342E+11 | 0.367467E+11 |
July | 0.114774E+13 | 0.548250E+11 | 0.00 | 0.120442E+11 | 0.608207E+11 |
August | 0.960063E+12 | 0.523314E+11 | 0.00 | 0.141768E+11 | 0.502376E+11 |
September | 0.690455E+12 | 0.500375E+11 | 0.00 | 0.115986E+11 | 0.287677E+11 |
October | 0.410640E+12 | 0.410727E+11 | 0.00 | 0.811797E+10 | 0.190924E+11 |
November | 0.198012E+12 | 0.590562E+11 | 0.00 | 0.735869E+10 | 0.365215E+11 |
December | 0.145591E+12 | 0.908501E+11 | 0.00 | 0.104386E+11 | 0.699374E+11 |
Annual Sum or Average | 0.775412E+13 | 0.770477E+12 | 0.00 | 0.127694E+12 | 0.533103E+12 |
Minimum of Months | 0.145591E+12 | 0.410727E+11 | 0.00 | 0.735869E+10 | 0.190924E+11 |
Maximum of Months | 0.114774E+13 | 0.127519E+12 | 0.00 | 0.148342E+11 | 0.948450E+11 |