Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2024-07-03 12:19:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3306.03 | 683.75 | 683.75 |
Net Site Energy | 3306.03 | 683.75 | 683.75 |
Total Source Energy | 6301.85 | 1303.35 | 1303.35 |
Net Source Energy | 6301.85 | 1303.35 | 1303.35 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2001.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 378.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 12.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1304.90 | 2001.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2001.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 378.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 12.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2001.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 19.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 378.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 12.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 85.01 | 413.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 269.88 | 413.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 85.01 | 413.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 269.88 | 413.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1304.904 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1304.904 | 100.00 |
Total On-Site and Utility Electric Sources | 1304.904 | 100.00 |
Total Electricity End Uses | 1304.904 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 89.50 |
Time Setpoint Not Met During Occupied Cooling | 3.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3103.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINE STORAGE OFFICE FRONT WALL WINDOW | FINE STORAGE OFFICE LEFT WALL WINDOW | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINE STORAGE OFFICE FRONT WALL WINDOW | FINE STORAGE OFFICE LEFT WALL WINDOW | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 149.82 | 39.41 | 0.00 | 0.00 | 110.41 |
Gross Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Above Ground Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 149.82 | 39.41 | 0.00 | 0.00 | 110.41 |
Gross Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Above Ground Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 21.81 |
Skylight-Roof Ratio [%] | 0.47 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 28.42 | 28.42 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 121.40 | 121.40 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 149.82 | 149.82 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 149.82 | 149.82 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-14:00 | 04-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 462689.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22125.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14541.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1404.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 94299.37 | 462689.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 462689.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22125.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 12236.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1404.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2169.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 62.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 423.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1199.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 39.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4132.63 | 2169.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 448.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 248.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 854.71 | 448.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 448.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 248.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 854.71 | 448.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.43 |
ZONE2 FINE STORAGE DIRECT AIR | 6.12 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 23.91 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 23.91 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 312660.28 |
PSZ-OFFICE HEATING COIL | 24918.64 |
PSZ-FINE STORAGE HEATING COIL | 102674.93 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.43 | 1.43 | 1.43 | 1.43 | 1.43 | 1.43 | 1.00 | 1.00 | 1.43 |
PSZ-FINE STORAGE | 6.12 | 6.12 | 6.12 | 6.12 | 6.12 | 6.12 | 1.00 | 1.00 | 6.12 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.43 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 6.12 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.43 | 2377.42 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 6.12 | 9859.10 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.43 | 1.43 | 1.43 | 1.43 | 23794.92 | 24918.64 | 32.21 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 6.12 | 6.12 | 6.12 | 6.12 | 104331.57 | 102674.93 | 26.67 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.43 | 0.715229 | 0.953640 | 23794.92 | 11897.46 | 0.800870 | 0.800870 |
PSZ-FINE STORAGE COOLING COIL | 6.12 | 3.06 | 4.08 | 104331.57 | 52165.79 | 0.800250 | 0.800250 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE OFFICE FRONT WALL | FINE STORAGE OFFICE FRONT WALL WINDOW | |
FINE STORAGE OFFICE LEFT WALL | FINE STORAGE OFFICE LEFT WALL WINDOW | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 68 | 44 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 117.24 | 28.42 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 605.78 | 121.40 | 11 | 8 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
2 | SEMIHEATED_ROOF | 18 | 3 | 3 | 0.167 | 1.136 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | NONRES_EXT_WALL_GRD | 19 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 200.0 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 4.938 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
3 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
5 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8212 |
6 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
7 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
16 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
17 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5000E-02 |
18 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2025 |
19 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
20 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
21 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
22 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
23 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
34 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
35 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
36 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
37 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
38 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
39 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
40 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
41 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
42 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
43 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
2 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
3 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
4 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
5 | 3 | -0.53954861E-06 | 0.47047397E-08 | -0.33276159E-05 | 0.24742089E-17 |
6 | 2 | 0.71895056 | 0.67549398E-02 | 0.98308090 | -0.63795361E-06 |
7 | 1 | -21.239987 | 0.46806363 | -6.4456230 | 0.18844773 |
8 | 0 | 21.442615 | 0.44675967 | 6.3841236 | |
9 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
10 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
11 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
12 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
13 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
14 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
15 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
16 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
17 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
18 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
19 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
20 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
21 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
22 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
23 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
24 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
25 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
26 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
27 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
28 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
29 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
30 | 0 | 200.00000 | 200.00000 | 200.00000 | |
31 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
32 | 0 | 4.9377744 | 4.9377744 | 4.9377744 | |
33 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
34 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
35 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
36 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
37 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
38 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
39 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
40 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
41 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
42 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
43 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
44 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
45 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
46 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
47 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
48 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
49 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
50 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
51 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
52 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
53 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
54 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
55 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
56 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
57 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
58 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
59 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
60 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
61 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
62 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
63 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
64 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
65 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
66 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
67 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
68 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
69 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
70 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
71 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
72 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
73 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
74 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
75 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
76 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
77 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
78 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
79 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
80 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
81 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
82 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
83 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
84 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
85 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
86 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
87 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
88 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
89 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
90 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
91 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
92 | 7 | -0.94456721E-13 | 0.24575595E-14 | -0.29735092E-12 | 0.15324278E-15 |
93 | 6 | 0.65405332E-08 | 0.22114619E-09 | 0.28546880E-07 | -0.13451374E-12 |
94 | 5 | -0.97466953E-04 | 0.18937623E-05 | -0.18947583E-03 | 0.64660656E-08 |
95 | 4 | 0.99417931E-01 | 0.92215111E-03 | 0.29140875 | -0.33466744E-04 |
96 | 3 | -2.3345767 | 0.28579858E-01 | -7.2517161 | 0.28937395E-01 |
97 | 2 | 15.247323 | 0.10163225 | 40.822959 | -0.33280368 |
98 | 1 | -29.125752 | 0.45869584E-01 | -80.508872 | 1.0778326 |
99 | 0 | 16.291614 | 0.92288667E-03 | 46.824339 | |
100 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
101 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
102 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
103 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.49 | 34 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
2 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.49 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
3 | NONRESWINDOW_U_0.57_SHGC_EAST_0.49 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
4 | NONRESWINDOW_U_0.57_SHGC_WEST_0.49 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
5 | SKYLIGHT_U_0.69_SHGC_0.68 | 38 | 1 | VerySmooth | 3.922 | 3.922 | 1.000 | 0.683 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.59264 | 0.15506 | 0.15506 | 0.68000 | 0.13462 | 0.14960 | 0.00000 | 0.84000 | 0.84000 | 2.30798E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.637 | 0.467 | 0.419 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.264 | 7.065E-004 | 4.615E-004 | 0.231 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone ZONE1 OFFICE | 1.2500 |
3 | Zone ZONE2 FINE STORAGE | 1.2500 |
4 | Zone ZONE3 BULK STORAGE | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone ZONE1 OFFICE | 1.1500 |
3 | Zone ZONE2 FINE STORAGE | 1.1500 |
4 | Zone ZONE3 BULK STORAGE | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12895.21757 | 14829.50021 | 0.98650 | 1.13448 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 15106.70517 | 18883.38147 | 1.14437 | 1.43046 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70000 | 1.83376E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 47399.84795 | 54509.82514 | 3.62637 | 4.17032 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 28.69467 | 1.27234E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 64067.03066 | 80083.78832 | 4.89944 | 6.12429 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -32.70000 | 1.83376E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 250128.22164 | 312660.27705 | 19.12926 | 23.91157 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15143.18 | 1.13448 | 1.13448 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 24918.64 | 1.43046 | 1.43046 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 54719.85 | 4.17032 | 4.17032 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 102674.93 | 6.12429 | 6.12429 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.43046 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.12429 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 23.91157 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 23.91157 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 312660.27666 |
6 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.43046 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43046 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.43046 |
9 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43046 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.43046 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.43046 |
12 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
13 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.12429 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.12429 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.12429 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 6.12429 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.12429 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 6.12429 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.43046 |
23 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 6.12429 |
24 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.43046 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
26 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.43046 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2377.41788 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.43046 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.43046 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.43046 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.43046 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.43046 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.71523 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95364 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23794.92000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11897.46000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80087 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80087 |
39 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23794.92000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24918.63597 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.21000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
43 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 24918.63597 |
44 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.12429 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
46 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.12429 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 9859.10418 |
48 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.12429 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.12429 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.12429 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 6.12429 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.12429 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.06215 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.08286 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 104331.57000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 52165.78500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80025 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80025 |
59 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 104331.57000 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 102674.92941 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 26.67000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
63 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 102674.92941 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 22684.9 | 10.68 | 10.44 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 99578.9 | 10.73 | 10.49 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.7129292835 | 0.6992728461 | Pass | Pass | 0.7645509772 | 0.6819163730 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.4525548645 | 1.3566395255 | Pass | Pass | 0.6276396289 | 0.6454989612 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.1102230246E-015 | 1.0229058312E-015 | Pass | Pass | 1.3066645920E-002 | 1.0807106214E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7320.00 | 898.75 | 0.00 | 162.22 | 665.33 | 9046.33 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 110.54 | 88.07 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 39.02 | 29.17 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 110.54 | 20.66 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 39.02 | 7.50 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.30 | 0.982 | 1.136 | 3204.84 | 3183.04 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.662 | 0.787 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.662 | 0.787 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.57_SHGC_WEST_0.49 | 9.73 | 0.00 | 0.00 | 9.73 | 9.73 | 3.241 | 0.491 | 0.541 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_WEST_0.49 | 10.79 | 0.00 | 0.00 | 10.79 | 10.79 | 3.241 | 0.491 | 0.541 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.49 | 3.95 | 0.00 | 0.00 | 3.95 | 3.95 | 3.241 | 0.491 | 0.541 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.49 | 3.95 | 0.00 | 0.00 | 3.95 | 3.95 | 3.241 | 0.491 | 0.541 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINE STORAGE OFFICE FRONT WALL WINDOW | NONRESWINDOW_U_0.57_SHGC_WEST_0.49 | 89.88 | 0.00 | 0.00 | 89.88 | 89.88 | 3.241 | 0.491 | 0.541 | No | FINE STORAGE OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
FINE STORAGE OFFICE LEFT WALL WINDOW | NONRESWINDOW_U_0.57_SHGC_NORTH_0.49 | 31.51 | 0.00 | 0.00 | 31.51 | 31.51 | 3.241 | 0.491 | 0.541 | No | FINE STORAGE OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 171.62 | 3.566 | 0.499 | 0.542 | |||||||||||||||||
North Total or Average | 39.41 | 3.241 | 0.491 | 0.541 | |||||||||||||||||
Non-North Total or Average | 132.21 | 3.663 | 0.501 | 0.543 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINE STORAGE OFFICE FRONT WALL WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
FINE STORAGE OFFICE LEFT WALL WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.52 | 83.52 | 133.76 | |
Exterior Lighting Total | 8532.22 | 133.76 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23794.92 | 19056.64 | 4738.28 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 104331.57 | 83491.34 | 20840.23 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 22684.9 | 10.68 | 10.44 | ||||
PSZ-FINE STORAGE COOLING COIL | 99578.9 | 10.73 | 10.49 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 312660.28 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 24918.64 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 102674.93 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 340.63 | 23.91 | 15195.98 | 635.51 | 1.00 | 1.18 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 966.87 | 1.43 | 2377.42 | 1662.00 | 1.00 | 1.27 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.60 | 966.87 | 6.12 | 9859.10 | 1609.84 | 1.00 | 1.17 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12895.22 | 14829.50 | 62.60 | 0.987 | 1.134 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00845 | 28.36 | 0.01272 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 47399.85 | 54509.83 | 39.12 | 3.626 | 4.170 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 26.70 | 26.70 | 0.00858 | 28.69 | 0.01272 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 0.00 | 31.36 | 0.01279 | 30.10 | 0.01273 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 15106.71 | 18883.38 | 79.72 | 1.144 | 1.430 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00798 | -32.70 | 0.00018 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 64067.03 | 80083.79 | 57.47 | 4.899 | 6.124 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00767 | -32.70 | 0.00018 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 250128.22 | 312660.28 | 97.56 | 19.129 | 23.912 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00752 | -32.70 | 0.00018 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.13 | 1.13 | 1.43 | 1.43 | 1.4305 | 1.4305 | 1.4305 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.17 | 4.17 | 6.12 | 6.12 | 6.1243 | 6.1243 | 6.1243 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3 BULK STORAGE UNIT HEATER | 312660.277 | 312660.277 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 312660.28 | 312660.28 | 23.911574 | 10.00 | 9.53 | 0.00752072 | 21.11 | 14.48 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 10.00 | 0.00752072 | 94.4631 | 312660.28 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 23794.920 | 19056.638 | 1.430460 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 11897.46 | 10372.22 | 0.953640 | 24.30 | 16.34 | 0.00883872 | 11.38 | 10.62 | 0.00800000 | 28.36 | 0.01272282 | 20.62 | 10.7257 | 23.90 | 0.00845383 | 43.8805 | 12895.22 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 24918.636 | 24918.636 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 24918.64 | 24918.64 | 1.430458 | 17.19 | 12.43 | 0.00742375 | 32.21 | 18.30 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 7.1505 | 21.10 | 0.00798134 | 49.1430 | 15106.71 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 104331.570 | 83491.339 | 6.124290 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 52165.79 | 45396.36 | 4.082860 | 26.92 | 17.37 | 0.00900490 | 14.22 | 11.80 | 0.00800000 | 28.86 | 0.01272368 | 20.77 | 10.4023 | 26.70 | 0.00858269 | 37.7085 | 47345.96 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 102674.929 | 102674.929 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 102674.93 | 102674.93 | 6.124294 | 12.21 | 10.10 | 0.00715407 | 26.67 | 16.46 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 6.9349 | 15.56 | 0.00767350 | 66.9323 | 64067.03 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3 BULK STORAGE UNIT HEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 312660.277 | 312660.277 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 23.911574 | 27.59215937 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 312660.28 | 312660.28 | 1.0000 | 27.59215937 | 23.911574 | 10.00 | 9.53 | 0.00752072 | 28995.7 | 21.11 | 14.48 | 0.00800000 | 41534.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 312660.28 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 10.00 | 0.00752072 | 10.00 | 0.00752072 | 94.4631 | 312660.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23794.920 | 19056.638 | 1.430460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2707 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.430458 | 1.65064130 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 11897.46 | 10372.22 | 1.0000 | 1.10042890 | 0.953640 | 24.30 | 16.34 | 0.00883872 | 46922.6 | 11.38 | 10.62 | 0.00800000 | 31610.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11897.46 | 28.36 | 0.01272282 | 20.62 | 0.10228463 | 10.7257 | 23.90 | 0.00845383 | 23.90 | 0.00845383 | 43.8805 | 12895.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24918.636 | 24918.636 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.430458 | 1.65064130 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 24918.64 | 24918.64 | 1.0000 | 1.65064130 | 1.430458 | 17.19 | 12.43 | 0.00742375 | 36073.4 | 32.21 | 18.30 | 0.00800000 | 52852.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24918.64 | -32.70 | 0.00018338 | -32.70 | 0.10228463 | 7.1505 | 21.03 | 0.00798134 | 21.10 | 0.00798134 | 49.1430 | 15106.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 104331.570 | 83491.339 | 6.124290 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5797 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 6.124294 | 7.06697532 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 52165.79 | 45396.36 | 1.0000 | 4.71131364 | 4.082860 | 26.92 | 17.37 | 0.00900490 | 50019.3 | 14.22 | 11.80 | 0.00800000 | 34511.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52165.79 | 28.86 | 0.01272368 | 20.77 | 0.42471127 | 10.4023 | 26.70 | 0.00858269 | 26.70 | 0.00858269 | 37.7085 | 47345.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 102674.929 | 102674.929 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 6.124294 | 7.06697532 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 102674.93 | 102674.93 | 1.0000 | 7.06697532 | 6.124294 | 12.21 | 10.10 | 0.00715407 | 30324.8 | 26.67 | 16.46 | 0.00800000 | 47203.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 102674.93 | -32.70 | 0.00018338 | -32.70 | 0.42471127 | 6.9349 | 15.56 | 0.00767350 | 15.56 | 0.00767350 | 66.9323 | 64067.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | FixedDryBulb | 0.10 | 1.43 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | FixedDryBulb | 0.42 | 6.12 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2734.50 | 2666.50 | 1990.67 |
ZONE2 FINE STORAGE | 3191.83 | 2976.17 | 2608.00 |
ZONE3 BULK STORAGE | 3262.00 | 3313.67 | 3000.50 |
Facility | 3590.83 | 3407.67 | 3103.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 356.33 | 3.67 | 76.17 | 3.50 |
ZONE2 FINE STORAGE | 587.67 | 37.33 | 29.67 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 851.33 | 41.00 | 89.50 | 3.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 1.026 | 0.315 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.42 | 30.00 | 2953.02 | 0.932 | 0.246 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.127 | 0.000 | 0.135 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.42 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.42 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.53 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 3686692.76 | 0.00 | 3686692.76 | 1827265.85 | 5513958.61 | 3225648.14 | 5645.05 | 2004.75 | 1110.20 | 0.00 |
ZONE2 FINE STORAGE | 10224536.11 | 0.00 | 10224536.11 | 6606177.37 | 16830713.48 | 13393694.68 | 5641.77 | 2291.94 | 826.28 | 45.45 |
ZONE3 BULK STORAGE | 0.00 | 27672840.06 | 27672840.06 | 32169310.86 | 59842150.92 | 30805497.77 | 8181.72 | 55.50 | 522.78 | 4777.64 |
Total Facility | 13911228.87 | 27672840.06 | 41584068.94 | 40602754.08 | 82186823.01 | 47424840.58 | 8433.08 | 2326.94 | 1638.09 | 4780.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2817 | 0.0000 | 0.2817 | 0.0872 | 0.3688 | 0.1023 | 521.05 | 2004.75 | 1110.20 |
ZONE2 FINE STORAGE | 0.7467 | 0.0000 | 0.7467 | 0.2003 | 0.9470 | 0.4247 | 561.00 | 2291.78 | 783.22 |
ZONE3 BULK STORAGE | 0.0000 | 1.2868 | 1.2868 | 1.2559 | 2.5427 | 0.9768 | 3293.58 | 27.67 | 314.75 |
Total Facility | 1.0283 | 1.2868 | 2.3151 | 1.5434 | 3.8585 | 1.5038 | 3309.08 | 2298.94 | 1387.19 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 4908988.37 | 0.00 | 4908988.37 | 3225648.14 | 5641.53 | 0.17 | 3118.31 | 0.00 |
PSZ-FINE STORAGE | 13614405.14 | 0.00 | 13614405.14 | 13393694.68 | 5634.77 | 0.17 | 3125.06 | 45.45 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.3750 | 0.0000 | 0.3750 | 0.1023 | 517.53 | 0.17 | 3118.31 |
PSZ-FINE STORAGE | 0.9942 | 0.0000 | 0.9942 | 0.4247 | 554.67 | 0.17 | 3081.16 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2476.01 | 648.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2410.45 | 730.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.3809 | 0.6490 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.7938 | 2.4354 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 16 | 16 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 382 |
Defaulted Fields | 322 |
Fields with Defaults | 1019 |
Autosized Fields | 42 |
Autosizable Fields | 96 |
Autocalculated Fields | 94 |
Autocalculatable Fields | 138 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1304.90 | 6131.39 | 04-JUL-12:40 | 94299.37 | 30-JUN-15:00 |
Electricity:Building | 760.89 | 6131.39 | 01-JAN-00:10 | 58533.65 | 27-JUN-10:50 |
Electricity:Zone:ZONE1 OFFICE | 60.03 | 926.90 | 01-JAN-00:10 | 3790.09 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 760.12 | 6131.39 | 01-JAN-00:10 | 56228.36 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 461.71 | 3104.69 | 01-JAN-00:10 | 36895.31 | 27-JUN-10:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 378.80 | 0.00 | 20-FEB-15:20 | 27432.51 | 06-JAN-08:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.77 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
Ventilation (simple):Fans:Electricity | 0.77 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.77 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUN-16:50 |
ElectricityPurchased:Facility | 1304.90 | 6131.39 | 04-JUL-12:40 | 94299.37 | 30-JUN-15:00 |
ElectricityPurchased:Plant | 1304.90 | 6131.39 | 04-JUL-12:40 | 94299.37 | 30-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1304.90 | 6131.39 | 04-JUL-12:40 | 94299.37 | 30-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1304.90 | 6131.39 | 04-JUL-12:40 | 94299.37 | 30-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1304.90 | 6131.39 | 04-JUL-12:40 | 94299.37 | 30-JUN-15:00 |
ElectricityNet:Plant | 1304.90 | 6131.39 | 04-JUL-12:40 | 94299.37 | 30-JUN-15:00 |
Cogeneration:ElectricityNet | 1304.90 | 6131.39 | 04-JUL-12:40 | 94299.37 | 30-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1304.90 | 6131.39 | 04-JUL-12:40 | 94299.37 | 30-JUN-15:00 |
Electricity:HVAC | 397.76 | 0.00 | 20-FEB-15:20 | 37339.98 | 29-JUN-16:00 |
General:Fans:Electricity | 378.04 | 0.00 | 20-FEB-15:20 | 27432.51 | 06-JAN-08:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 19.72 | 0.00 | 01-JAN-00:10 | 25103.46 | 29-JUN-16:00 |
General:Cooling:Electricity | 19.72 | 0.00 | 01-JAN-00:10 | 25103.46 | 29-JUN-16:00 |
ExteriorLights:Electricity | 133.76 | 0.00 | 01-JAN-08:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 133.76 | 0.00 | 01-JAN-08:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 12.50 | 0.00 | 02-JAN-00:10 | 1852.19 | 25-FEB-13:00 |
WaterSystems:Electricity | 12.50 | 0.00 | 02-JAN-00:10 | 1852.19 | 25-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 12.50 | 0.00 | 02-JAN-00:10 | 1852.19 | 25-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2001.12 | 4750.00 | 29-JUN-05:20 | 462689.12 | 04-JAN-06:10 |
NaturalGas:HVAC | 2001.12 | 4750.00 | 29-JUN-05:20 | 462689.12 | 04-JAN-06:10 |
Heating:NaturalGas | 2001.12 | 4750.00 | 29-JUN-05:20 | 462689.12 | 04-JAN-06:10 |
General:Heating:NaturalGas | 2001.12 | 4750.00 | 29-JUN-05:20 | 462689.12 | 04-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3261.98 | 0.00 | 20-FEB-15:20 | 746126.32 | 04-JAN-06:10 |
EnergyTransfer:Building | 1744.25 | 0.00 | 20-FEB-15:20 | 383266.64 | 04-JAN-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 90.02 | 0.00 | 01-JAN-00:40 | 27764.32 | 05-JAN-07:20 |
Heating:EnergyTransfer | 1664.10 | 0.00 | 20-FEB-15:20 | 383266.64 | 04-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 66.64 | 0.00 | 01-JAN-00:40 | 27764.32 | 05-JAN-07:20 |
General:Heating:EnergyTransfer | 1664.10 | 0.00 | 20-FEB-15:20 | 383266.64 | 04-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 66.64 | 0.00 | 01-JAN-00:40 | 27764.32 | 05-JAN-07:20 |
Cooling:EnergyTransfer | 80.16 | 0.00 | 01-JAN-00:10 | 55449.44 | 29-JUN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 23.38 | 0.00 | 01-JAN-00:10 | 12109.22 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer | 80.16 | 0.00 | 01-JAN-00:10 | 55449.44 | 29-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 23.38 | 0.00 | 01-JAN-00:10 | 12109.22 | 29-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 335.45 | 0.00 | 01-JAN-00:40 | 79258.46 | 04-JAN-06:20 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 278.68 | 0.00 | 01-JAN-00:40 | 79258.46 | 04-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 278.68 | 0.00 | 01-JAN-00:40 | 79258.46 | 04-JAN-06:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 56.77 | 0.00 | 01-JAN-00:10 | 52085.11 | 26-JUL-18:00 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 56.77 | 0.00 | 01-JAN-00:10 | 52085.11 | 26-JUL-18:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1318.78 | 0.00 | 17-JAN-13:00 | 290060.68 | 04-JAN-06:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1318.78 | 0.00 | 17-JAN-13:00 | 290060.68 | 04-JAN-06:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1318.78 | 0.00 | 17-JAN-13:00 | 290060.68 | 04-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1517.73 | 0.00 | 04-FEB-14:50 | 362859.68 | 04-JAN-06:10 |
HeatingCoils:EnergyTransfer | 1436.62 | 0.00 | 04-FEB-14:50 | 362859.68 | 04-JAN-06:10 |
CoolingCoils:EnergyTransfer | 81.11 | 0.00 | 01-JAN-00:10 | 90937.28 | 30-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 66.638 | -23.382 | 0.000 | 0.000 | 9.999 | 30.864 | 29.165 | 20.008 | 0.000 | 0.299 | 0.001 | 0.000 | -29.495 | 0.000 | -38.804 | -65.291 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 278.679 | -56.770 | 0.000 | 0.000 | 24.871 | 239.148 | 0.000 | 86.147 | 0.000 | 0.325 | 0.002 | 0.000 | -110.541 | 0.000 | -129.511 | -332.348 |
ZONE3 BULK STORAGE | 1318.777 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 66.655 | 353.598 | 107.344 | 25.844 | 0.000 | 2.520 | 0.000 | 0.000 | -25.778 | 0.000 | -706.785 | -1142.177 |
Total Facility | 1318.777 | 0.000 | 345.317 | -80.153 | 0.000 | 0.000 | 101.525 | 623.610 | 136.508 | 131.999 | 0.000 | 3.145 | 0.003 | 0.000 | -165.814 | 0.000 | -875.100 | -1539.816 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 25-AUG-05:02 | 0.00 | 0.00 | 0.00 | -31006.38 | 0.00 | 0.00 | 86.57 | 583.97 | 550.52 | 0.00 | 0.00 | 0.00 | 31602.90 | 0.00 | -1360.84 | 0.00 | -456.74 | 0.00 |
ZONE2 FINE STORAGE | 16-JUN-19:11 | 0.00 | 0.00 | 0.00 | -125594.07 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 8816.71 | 0.00 | 0.00 | 116126.73 | 0.00 | -0.00 | 0.00 | -1449.17 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-JUN-19:11 | 0.00 | 0.00 | 0.00 | -125594.07 | 0.00 | 0.00 | 0.00 | 5661.51 | 2519.91 | 10870.76 | 0.00 | 0.00 | 116531.33 | 0.00 | -520.09 | 0.00 | -9469.34 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 20-DEC-06:31 | 0.00 | 0.00 | 30017.61 | 0.00 | 0.00 | 0.00 | 149.15 | 583.97 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3220.59 | 0.00 | -3808.22 | -24272.44 |
ZONE2 FINE STORAGE | 05-JAN-06:41 | 0.00 | 0.00 | 121056.17 | 0.00 | 0.00 | 0.00 | 396.95 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12865.35 | 0.00 | -11543.80 | -99143.76 |
ZONE3 BULK STORAGE | 04-JAN-05:51 | 290060.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3339.16 | 0.00 | -139533.26 | -152342.88 |
Total Facility | 04-JAN-06:01 | 281766.59 | 0.00 | 131689.44 | 0.00 | 0.00 | 0.00 | 1464.91 | 5788.46 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18895.89 | 0.00 | -160113.49 | -244300.57 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.4305 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.4305 | 0.0902 | 1.0000 | Not calculated | 0.1023 | 0.0715 | ||
PSZ-FINE STORAGE | 6.1243 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 6.1243 | 0.1018 | 1.0000 | Not calculated | 0.4247 | 0.0693 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.4305 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.4305 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0715 | ||
PSZ-FINE STORAGE | 6.1243 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 6.1243 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0693 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4305 | 1.4305 | 1.4305 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.1243 | 6.1243 | 6.1243 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.4305 | 1.4305 | 1.4305 | 1.4305 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 6.1243 | 6.1243 | 6.1243 | 6.1243 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4305 | 1.4305 | 1.4305 | No | 0.1023 | 0.0715 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.1243 | 6.1243 | 6.1243 | No | 0.4247 | 0.0693 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.4305 | 1.4305 | 1.4305 | 1.4305 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 6.1243 | 6.1243 | 6.1243 | 6.1243 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 89.50 |
Number of hours cooling loads not met | 3.50 |
Number of hours not met | 93.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 2001.12 | 462689.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 19.72 | 25103.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 133.76 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.77 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 378.04 | 27432.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 12.50 | 1852.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 1304.90 |
Natural Gas | 0.00 | 2001.12 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 3306.03 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 4.08 |
Fans (All) | 78.34 |
Service Water Heating | 2.58 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 269.88 |
Subtotal | 269.88 |
Natural Gas [MJ/m2] | |
Space Heating | 413.87 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 413.87 |
Subtotal | 413.87 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.86 |
Space Heating | 60.53 |
Space Cooling | 0.60 |
Fans (All) | 11.46 |
Service Water Heating | 0.38 |
Receptacle Equipment | 4.13 |
Miscellaneous | 4.05 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8143.17 | 616.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7885.83 | 874.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7886.00 | 849.00 | 25.00 | 0.00 | 0.00 |
Min | 7885.83 | 616.83 | 0.00 | 0.00 | 0.00 |
Max | 8143.17 | 874.17 | 25.00 | 0.00 | 0.00 |
Average | 7971.67 | 780.00 | 8.33 | 0.00 | 0.00 |
Sum | 23915.00 | 2340.00 | 25.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 68629.00 | 14090.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 162326.00 | 27685.33 | 1181.67 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 162326.00 | 27685.33 | 1181.67 | 0.00 | 0.00 |
Average | 87994.00 | 13925.11 | 393.89 | 0.00 | 0.00 |
Sum | 263982.00 | 41775.33 | 1181.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7909.50 | 850.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7469.00 | 1291.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7517.33 | 1228.17 | 14.50 | 0.00 | 0.00 |
Min | 7469.00 | 850.50 | 0.00 | 0.00 | 0.00 |
Max | 7909.50 | 1291.00 | 14.50 | 0.00 | 0.00 |
Average | 7631.94 | 1123.22 | 4.83 | 0.00 | 0.00 |
Sum | 22895.83 | 3369.67 | 14.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32352.00 | 675.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 66661.00 | 16058.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 156716.67 | 33694.33 | 782.00 | 0.00 | 0.00 |
Min | 32352.00 | 675.00 | 0.00 | 0.00 | 0.00 |
Max | 156716.67 | 33694.33 | 782.00 | 0.00 | 0.00 |
Average | 85243.22 | 16809.11 | 260.67 | 0.00 | 0.00 |
Sum | 255729.67 | 50427.33 | 782.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:40
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.496291E+09 | 603.25 | 21-JAN-08:09 | -22.1 | -22.3 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.5 | 0.457273E+09 | 628.31 | 28-FEB-16:10 | 6.02 | 1.46 |
March | 1887963.54 | 381.72 | 17-MAR-16:00 | -1.7 | -5.6 | 0.538041E+09 | 703.54 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.143073E+09 | 3487.03 | 22-APR-16:00 | 18.90 | 8.04 | 0.536429E+09 | 768.97 | 18-APR-15:00 | 18.90 | 8.04 |
May | 0.278671E+10 | 27961.87 | 19-MAY-05:02 | 14.23 | 9.76 | 0.644736E+09 | 769.03 | 26-MAY-09:09 | 21.35 | 17.65 |
June | 0.494107E+10 | 25953.57 | 21-JUN-05:03 | 11.57 | 10.79 | 0.659384E+09 | 769.04 | 22-JUN-10:39 | 20.20 | 18.45 |
July | 0.663177E+10 | 29751.33 | 01-JUL-05:01 | 9.78 | 9.47 | 0.634807E+09 | 769.04 | 25-JUL-15:00 | 19.40 | 19.06 |
August | 0.597653E+10 | 31024.86 | 25-AUG-05:02 | 7.88 | 7.62 | 0.685444E+09 | 769.04 | 29-AUG-09:00 | 21.10 | 19.19 |
September | 0.263660E+10 | 26833.99 | 02-SEP-05:02 | 13.80 | 10.55 | 0.626824E+09 | 769.03 | 01-SEP-09:39 | 13.80 | 10.55 |
October | 0.265287E+09 | 3807.76 | 21-OCT-15:00 | 20.00 | 11.16 | 0.555667E+09 | 768.98 | 20-OCT-12:09 | 20.00 | 11.16 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 | 0.483136E+09 | 768.97 | 01-NOV-15:50 | 17.88 | 13.29 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.496839E+09 | 603.25 | 30-DEC-08:09 | -4.6 | -5.3 |
Annual Sum or Average | 0.233829E+11 | 0.681487E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.457273E+09 | 603.25 | -22.1 | -22.3 | ||
Maximum of Months | 0.663177E+10 | 31024.86 | 20.00 | 11.16 | 0.685444E+09 | 769.04 | 21.35 | 19.19 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23808426.04 | 3435.10 | 27-JAN-15:30 | -14.4 | -15.6 | 0.649779E+09 | 861.20 | 17-JAN-15:50 | -14.4 | -15.6 |
February | 54938239.93 | 2291.91 | 27-FEB-15:00 | -7.8 | -10.2 | 0.625366E+09 | 1180.71 | 08-FEB-16:10 | -7.8 | -10.2 |
March | 77640392.69 | 2883.83 | 06-MAR-16:00 | -10.0 | -12.0 | 0.780425E+09 | 1450.30 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 17674427.45 | 1053.38 | 04-APR-15:00 | -3.3 | -6.8 | 0.104616E+10 | 2182.46 | 22-APR-15:09 | 18.40 | 7.85 |
May | 0.509051E+10 | 113844.98 | 18-MAY-20:31 | 18.90 | 13.19 | 0.172085E+10 | 2246.96 | 26-MAY-12:00 | 23.50 | 18.24 |
June | 0.131132E+11 | 125585.00 | 16-JUN-19:11 | 18.33 | 11.12 | 0.189892E+10 | 2246.96 | 24-JUN-14:09 | 27.88 | 23.16 |
July | 0.211966E+11 | 118321.11 | 07-JUL-19:41 | 18.17 | 12.56 | 0.185035E+10 | 2246.97 | 15-JUL-12:30 | 27.75 | 24.03 |
August | 0.143659E+11 | 117119.05 | 04-AUG-19:51 | 16.70 | 12.83 | 0.198535E+10 | 2246.97 | 31-AUG-14:30 | 26.95 | 21.82 |
September | 0.282524E+10 | 124187.66 | 05-SEP-17:11 | 16.33 | 9.57 | 0.165765E+10 | 2246.96 | 01-SEP-12:09 | 16.33 | 9.57 |
October | 4062361.43 | 949.22 | 25-OCT-08:20 | -1.9 | -1.9 | 0.109452E+10 | 2188.70 | 21-OCT-15:09 | -1.9 | -1.9 |
November | 2524948.30 | 605.66 | 10-NOV-13:20 | -2.4 | -5.1 | 0.734743E+09 | 1574.06 | 01-NOV-15:09 | -2.4 | -5.1 |
December | 250148.66 | 87.26 | 06-DEC-14:00 | -6.5 | -6.6 | 0.650459E+09 | 870.68 | 28-DEC-15:09 | -1.8 | -3.8 |
Annual Sum or Average | 0.567724E+11 | 0.146946E+11 | ||||||||
Minimum of Months | 250148.66 | 87.26 | -14.4 | -15.6 | 0.625366E+09 | 861.20 | -14.4 | -15.6 | ||
Maximum of Months | 0.211966E+11 | 125585.00 | 18.90 | 13.19 | 0.198535E+10 | 2246.97 | 27.88 | 24.03 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.644120E+09 | 793.47 | 27-JAN-14:50 | -14.4 | -15.6 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.5 | 0.603054E+09 | 1022.26 | 08-FEB-14:39 | 5.00 | -0.5 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.3 | 0.755459E+09 | 1462.38 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.38 | 0.109530E+10 | 2650.07 | 22-APR-15:09 | 18.40 | 7.85 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.4 | 0.278927E+10 | 6072.63 | 25-MAY-15:00 | 29.10 | 19.63 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.410206E+10 | 8480.91 | 29-JUN-15:00 | 35.00 | 24.72 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 | 0.476133E+10 | 7024.54 | 15-JUL-15:09 | 30.92 | 24.34 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.448495E+10 | 6786.05 | 08-AUG-15:30 | 30.60 | 23.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.266578E+10 | 6317.17 | 01-SEP-13:50 | 25.40 | 18.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.112002E+10 | 2495.97 | 21-OCT-15:09 | 20.00 | 11.21 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 | 0.679535E+09 | 1617.93 | 01-NOV-14:00 | 18.30 | 13.44 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.644143E+09 | 793.69 | 05-DEC-15:30 | -0.5 | -0.5 |
Annual Sum or Average | 0.00 | 0.243450E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.603054E+09 | 793.47 | -14.4 | -15.6 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.476133E+10 | 8480.91 | 35.00 | 24.72 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163672E+11 | 29994.62 | 25-JAN-06:31 | -25.2 |
February | 0.119294E+11 | 29976.13 | 01-FEB-06:31 | -22.8 |
March | 0.992769E+10 | 27110.23 | 06-MAR-07:22 | -19.1 |
April | 0.383741E+10 | 26728.70 | 04-APR-05:12 | -9.1 |
May | 0.544932E+09 | 26433.58 | 01-MAY-05:12 | -3.5 |
June | 84967426.77 | 2596.92 | 21-JUN-06:07 | 14.27 |
July | 6169073.87 | 2604.63 | 10-JUL-06:07 | 11.75 |
August | 33182428.34 | 2652.35 | 02-AUG-06:07 | 10.97 |
September | 0.257699E+09 | 14814.41 | 29-SEP-05:03 | 7.20 |
October | 0.207201E+10 | 26480.41 | 30-OCT-05:12 | -9.8 |
November | 0.683752E+10 | 26843.46 | 25-NOV-06:31 | -19.4 |
December | 0.147399E+11 | 30017.50 | 20-DEC-06:31 | -29.0 |
Annual Sum or Average | 0.666380E+11 | |||
Minimum of Months | 6169073.87 | 2596.92 | -29.0 | |
Maximum of Months | 0.163672E+11 | 30017.50 | 14.27 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.733120E+11 | 121056.20 | 05-JAN-06:41 | -32.3 |
February | 0.501102E+11 | 120298.95 | 01-FEB-06:01 | -22.8 |
March | 0.339705E+11 | 108216.32 | 06-MAR-18:42 | -13.0 |
April | 0.117643E+11 | 106105.19 | 05-APR-05:01 | -13.4 |
May | 0.232862E+10 | 93115.27 | 01-MAY-05:01 | -3.4 |
June | 0.860827E+09 | 9681.94 | 03-JUN-06:25 | 8.60 |
July | 0.167056E+09 | 9473.13 | 10-JUL-06:25 | 13.05 |
August | 0.588514E+09 | 9634.15 | 17-AUG-06:25 | 15.55 |
September | 0.212444E+10 | 9663.76 | 29-SEP-06:25 | 7.50 |
October | 0.774441E+10 | 99669.95 | 30-OCT-03:32 | -9.8 |
November | 0.293572E+11 | 106262.71 | 29-NOV-06:01 | -20.3 |
December | 0.663506E+11 | 120473.02 | 20-DEC-06:01 | -28.9 |
Annual Sum or Average | 0.278679E+12 | |||
Minimum of Months | 0.167056E+09 | 9473.13 | -32.3 | |
Maximum of Months | 0.733120E+11 | 121056.20 | 15.55 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366549E+12 | 290060.72 | 04-JAN-05:51 | -28.9 |
February | 0.254081E+12 | 258224.93 | 12-FEB-22:55 | -17.2 |
March | 0.166117E+12 | 201589.94 | 15-MAR-04:54 | -22.2 |
April | 0.384207E+11 | 106449.43 | 04-APR-24:00 | -10.6 |
May | 0.690545E+09 | 33499.31 | 01-MAY-03:55 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.154797E+11 | 76177.28 | 30-OCT-06:00 | -9.4 |
November | 0.135971E+12 | 164968.01 | 25-NOV-01:51 | -15.6 |
December | 0.341470E+12 | 261232.59 | 24-DEC-08:55 | -31.1 |
Annual Sum or Average | 0.131878E+13 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.366549E+12 | 290060.72 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684659E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549212E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450955E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2059081.18 | 0.304271E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39421266.21 | 0.157706E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102648E+09 | 0.919686E+09 |
July | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101030E+09 | 0.684372E+09 |
August | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51806473.63 | 0.103901E+10 |
September | 0.138726E+10 | 0.254196E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2231248.76 | 0.176490E+10 |
October | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250494E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394840E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647461E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299196E+09 | 0.388039E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684372E+09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102648E+09 | 0.684659E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216516E+11 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181345E+11 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129845E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12660030.88 | 0.104280E+11 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16521513.66 | 0.599846E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151115E+09 | 0.399787E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114811E+09 | 0.303018E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30176380.06 | 0.427731E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649483E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732387E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132310E+11 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219593E+11 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325284E+09 | 0.129511E+12 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303018E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151115E+09 | 0.219593E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855646E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690466E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465856E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530235E+09 | 0.287012E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450228E+09 | 0.169612E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10234326.96 | 0.149185E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1518525.12 | 0.160171E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186562E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34225871.45 | 0.207041E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291320E+09 | 0.182554E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207554E+09 | 0.420246E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834914E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152532E+10 | 0.460926E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149185E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530235E+09 | 0.855646E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 17052.78 | 04-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 15715.72 | 14-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 13690.90 | 15-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.34 | 23-APR-16:00 | 9161.23 | 04-APR-17:00 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.64 | 25-MAY-16:10 | 5581.39 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3066.32 | 29-JUN-16:10 | 3696.23 | 09-JUN-07:00 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.97 | 28-JUL-16:10 | 2913.03 | 27-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.94 | 08-AUG-16:10 | 4142.83 | 17-AUG-16:10 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 468.27 | 01-SEP-16:10 | 5036.21 | 06-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 8539.59 | 30-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10918.22 | 29-NOV-07:40 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 16493.25 | 18-DEC-17:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2913.03 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3066.32 | 17052.78 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 26759.88 | 04-JAN-16:10 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 32636.16 | 12-FEB-23:00 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 19931.53 | 14-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1197.31 | 23-APR-16:00 | 17746.52 | 26-APR-15:03 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.97 | 25-MAY-15:10 | 9465.82 | 20-MAY-06:40 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4467.42 | 29-JUN-16:00 | 10008.27 | 09-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3054.49 | 15-JUL-15:10 | 6307.16 | 08-JUL-16:00 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2305.40 | 08-AUG-16:00 | 12820.38 | 17-AUG-15:05 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 9454.51 | 20-SEP-06:20 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 10834.02 | 05-OCT-08:00 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16086.11 | 22-NOV-01:55 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 32861.78 | 18-DEC-16:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6307.16 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4467.42 | 32861.78 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 142306.93 | 04-JAN-12:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 107009.82 | 12-FEB-22:55 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 64399.62 | 14-MAR-15:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18979.91 | 23-APR-16:00 | 47678.29 | 19-APR-10:00 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9663.48 | 10-MAY-15:00 | 27685.72 | 20-MAY-07:10 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1190.68 | 29-JUN-16:00 | 35595.59 | 09-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1254.09 | 15-JUL-13:55 | 41928.29 | 03-JUL-10:55 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 45030.94 | 17-AUG-14:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3122.38 | 24-SEP-15:00 | 24754.74 | 12-SEP-10:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10600.60 | 19-OCT-15:00 | 28823.26 | 31-OCT-11:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6648.13 | 01-NOV-13:00 | 54213.68 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 125334.23 | 18-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24754.74 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 18979.91 | 142306.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 4570.22 | 4698.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1571.61 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2742.13 | 2819.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2501.99 |
March | 381.72 | 17-MAR-16:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.23 |
April | 3487.03 | 22-APR-16:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.00 |
May | 27961.87 | 19-MAY-05:02 | 924.51 | 2919.87 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.42 |
June | 25953.57 | 21-JUN-05:03 | 739.61 | 2335.89 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.88 |
July | 29751.33 | 01-JUL-05:01 | 1294.31 | 4087.81 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.15 |
August | 31024.86 | 25-AUG-05:02 | 924.51 | 2919.87 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.74 |
September | 26833.99 | 02-SEP-05:02 | 924.51 | 2919.87 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.07 |
October | 3807.76 | 21-OCT-15:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.05 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 457.02 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 730.14 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1828.09 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1439.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 457.02 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.05 | |
Maximum of Months | 31024.86 | 1680.92 | 4570.22 | 4698.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2501.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3435.10 | 27-JAN-15:30 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2291.91 | 27-FEB-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4666.87 |
March | 2883.83 | 06-MAR-16:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5075.66 |
April | 1053.38 | 04-APR-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4393.65 |
May | 113844.98 | 18-MAY-20:31 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.52 |
June | 125585.00 | 16-JUN-19:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.17 |
July | 118321.11 | 07-JUL-19:41 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1195.44 |
August | 117119.05 | 04-AUG-19:51 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1384.18 |
September | 124187.66 | 05-SEP-17:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2479.01 |
October | 949.22 | 25-OCT-08:20 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 605.66 | 10-NOV-13:20 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4121.81 |
December | 87.26 | 06-DEC-14:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2734.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 87.26 | 0.00 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 125585.00 | 3955.50 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5075.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 31046.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31820.97 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 18628.16 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50712.47 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13440.37 |
April | 0.00 | 01-APR-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9400.43 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2189.32 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7561.20 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5138.04 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7439.75 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4731.92 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5031.73 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9393.42 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 12418.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26286.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2189.32 | |
Maximum of Months | 0.00 | 0.00 | 31046.94 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50712.47 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.137550E+12 | 87825.44 | 10-JAN-08:09 | 0.548078E+12 | 462689.12 | 04-JAN-06:10 |
February | 0.120933E+12 | 85323.71 | 25-FEB-15:50 | 0.372530E+12 | 406045.17 | 12-FEB-22:49 |
March | 0.129729E+12 | 85322.66 | 01-MAR-13:39 | 0.237618E+12 | 328427.83 | 15-MAR-05:10 |
April | 0.100193E+12 | 85275.81 | 03-APR-12:30 | 0.594546E+11 | 174368.27 | 04-APR-05:00 |
May | 0.897699E+11 | 83888.39 | 25-MAY-14:00 | 0.136756E+11 | 63785.37 | 01-MAY-05:10 |
June | 0.915348E+11 | 94299.37 | 30-JUN-14:00 | 0.123120E+11 | 4750.00 | 01-JUN-00:10 |
July | 0.940651E+11 | 90665.67 | 15-JUL-14:30 | 0.127224E+11 | 4750.00 | 01-JUL-00:10 |
August | 0.955504E+11 | 89831.46 | 08-AUG-14:00 | 0.127224E+11 | 4750.00 | 01-AUG-00:10 |
September | 0.868577E+11 | 83390.69 | 01-SEP-14:39 | 0.123526E+11 | 9672.74 | 28-SEP-05:10 |
October | 0.989071E+11 | 85066.14 | 30-OCT-12:09 | 0.283971E+11 | 130905.66 | 30-OCT-05:00 |
November | 0.122300E+12 | 87560.86 | 30-NOV-16:30 | 0.187705E+12 | 273959.43 | 25-NOV-06:10 |
December | 0.137514E+12 | 87823.13 | 28-DEC-08:09 | 0.503556E+12 | 409528.23 | 24-DEC-08:00 |
Annual Sum or Average | 0.130490E+13 | 0.200112E+13 | ||||
Minimum of Months | 0.868577E+11 | 83390.69 | 0.123120E+11 | 4750.00 | ||
Maximum of Months | 0.137550E+12 | 94299.37 | 0.548078E+12 | 462689.12 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.146771E+11 | 0.112984E+11 | 0.00 | 0.585610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112753E+10 | 0.00 |
February | 0.474804E+11 | 0.120560E+11 | 0.103734E+11 | 0.00 | 0.499671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105555E+10 | 0.00 |
March | 0.548234E+11 | 0.117182E+11 | 0.121089E+11 | 0.00 | 0.498554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122362E+10 | 0.00 |
April | 0.513965E+11 | 0.970113E+10 | 0.112578E+11 | 0.00 | 0.267314E+11 | 0.00 | 0.00 | 337973.86 | 0.00 | 0.00 | 0.00 | 0.110638E+10 | 0.00 |
May | 0.533545E+11 | 0.854928E+10 | 0.117000E+11 | 0.00 | 0.132811E+11 | 0.00 | 0.00 | 0.179605E+10 | 0.00 | 0.00 | 0.00 | 0.108901E+10 | 0.00 |
June | 0.528654E+11 | 0.747422E+10 | 0.116594E+11 | 0.00 | 0.135724E+11 | 0.00 | 0.00 | 0.494241E+10 | 0.00 | 0.00 | 0.00 | 0.102111E+10 | 0.00 |
July | 0.518856E+11 | 0.809878E+10 | 0.112984E+11 | 0.00 | 0.138358E+11 | 0.00 | 0.00 | 0.800446E+10 | 0.00 | 0.00 | 0.00 | 0.942054E+09 | 0.00 |
August | 0.548234E+11 | 0.936326E+10 | 0.121016E+11 | 0.00 | 0.138128E+11 | 0.00 | 0.00 | 0.446811E+10 | 0.00 | 0.00 | 0.00 | 0.981223E+09 | 0.00 |
September | 0.513965E+11 | 0.106226E+11 | 0.112504E+11 | 0.00 | 0.121654E+11 | 0.00 | 0.00 | 0.500374E+09 | 0.00 | 0.00 | 0.00 | 0.922407E+09 | 0.00 |
October | 0.518856E+11 | 0.126755E+11 | 0.113057E+11 | 0.00 | 0.220639E+11 | 0.00 | 0.00 | 8995902.00 | 0.00 | 0.00 | 0.00 | 0.967302E+09 | 0.00 |
November | 0.499276E+11 | 0.137556E+11 | 0.108562E+11 | 0.00 | 0.467776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982774E+09 | 0.00 |
December | 0.518856E+11 | 0.150713E+11 | 0.112984E+11 | 0.00 | 0.581801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107897E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.133763E+12 | 0.136508E+12 | 0.00 | 0.378804E+12 | 0.00 | 0.00 | 0.197207E+11 | 0.00 | 0.00 | 0.00 | 0.124979E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.747422E+10 | 0.103734E+11 | 0.00 | 0.121654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922407E+09 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.150713E+11 | 0.121089E+11 | 0.00 | 0.585610E+11 | 0.00 | 0.00 | 0.800446E+10 | 0.00 | 0.00 | 0.00 | 0.122362E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.548078E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.372530E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.237618E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.594546E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.136756E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.123120E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.127224E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.127224E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.123526E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.283971E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.187705E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.503556E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200112E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.123120E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.548078E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 27432.51 | 06-JAN-07:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 27432.51 | 04-FEB-10:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 27432.51 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10035.17 | 01-APR-07:10 | 0.00 | 27432.51 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 27432.51 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 14541.82 | 24-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 14541.82 | 03-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 14541.82 | 08-AUG-12:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 13004.95 | 01-SEP-13:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 27432.51 | 06-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 27432.51 | 28-NOV-14:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 27432.51 | 01-DEC-17:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10035.17 | 0.00 | 13004.95 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10035.17 | 0.00 | 27432.51 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1844.77 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 1852.19 | 25-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 1852.00 | 01-MAR-12:50 | 0.00 |
April | 121.47 | 13-APR-15:00 | 0.00 | 0.00 | 0.00 | 1838.09 | 01-APR-11:20 | 0.00 |
May | 14613.15 | 25-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1735.27 | 01-MAY-11:09 | 0.00 |
June | 25103.46 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1660.27 | 01-JUN-11:20 | 0.00 |
July | 18721.43 | 21-JUL-15:50 | 0.00 | 0.00 | 0.00 | 1591.03 | 01-JUL-11:00 | 0.00 |
August | 18876.59 | 08-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1503.79 | 01-AUG-11:30 | 0.00 |
September | 13630.72 | 01-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1508.32 | 30-SEP-11:20 | 0.00 |
October | 848.16 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1603.56 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 1706.11 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1790.02 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1503.79 | 0.00 | ||
Maximum of Months | 25103.46 | 0.00 | 0.00 | 0.00 | 1852.19 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 87825.44 | 10-JAN-08:09 | 40988.70 | 10035.17 | 8532.22 | 0.00 | 27432.51 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85323.71 | 25-FEB-15:50 | 46193.18 | 10035.17 | 0.00 | 0.00 | 27432.51 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85322.66 | 01-MAR-13:39 | 46193.18 | 10035.17 | 0.00 | 0.00 | 27432.51 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85275.81 | 03-APR-12:30 | 46193.18 | 10035.17 | 0.00 | 0.00 | 27432.51 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83888.39 | 25-MAY-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 12236.52 | 0.00 | 0.00 | 13921.74 | 0.00 |
June | 94299.37 | 30-JUN-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 14541.82 | 0.00 | 0.00 | 22125.19 | 0.00 |
July | 90665.67 | 15-JUL-14:30 | 46193.18 | 10035.17 | 0.00 | 0.00 | 14541.82 | 0.00 | 0.00 | 18567.47 | 0.00 |
August | 89831.46 | 08-AUG-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 14541.82 | 0.00 | 0.00 | 17742.71 | 0.00 |
September | 83390.69 | 01-SEP-14:39 | 46193.18 | 10035.17 | 0.00 | 0.00 | 13004.95 | 0.00 | 0.00 | 12889.66 | 0.00 |
October | 85066.14 | 30-OCT-12:09 | 46193.18 | 10035.17 | 0.00 | 0.00 | 27432.51 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87560.86 | 30-NOV-16:30 | 40988.70 | 10035.17 | 8532.22 | 0.00 | 27432.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 87823.13 | 28-DEC-08:09 | 40988.70 | 10035.17 | 8532.22 | 0.00 | 27432.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 83390.69 | 40988.70 | 10035.17 | 0.00 | 0.00 | 12236.52 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94299.37 | 46193.18 | 10035.17 | 8532.22 | 0.00 | 27432.51 | 0.00 | 0.00 | 22125.19 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 462689.12 | 04-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 406045.17 | 12-FEB-22:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 328427.83 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 174368.27 | 04-APR-05:00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 63785.37 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4750.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 4750.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 9672.74 | 28-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 130905.66 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 273959.43 | 25-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 409528.23 | 24-DEC-08:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 4750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 462689.12 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 104.67 | 15.38 | 18.67 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
February | 69.50 | 15.34 | 11.17 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
March | 42.50 | 15.89 | 11.33 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
April | 12.50 | 17.64 | 7.67 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
May | 1.00 | 19.99 | 1.00 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.59 | 1.33 | 24.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.29 | 1.17 | 24.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.55 | 1.00 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5.67 | 19.53 | 5.33 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
November | 33.00 | 16.14 | 9.50 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
December | 87.50 | 15.15 | 11.50 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
Annual Sum or Average | 356.33 | 15.60 | 76.17 | 16.20 | 3.67 | 16.28 | 3.50 | 16.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.67 | 19.99 | 18.67 | 19.99 | 1.33 | 25.29 | 1.33 | 24.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 117.67 | 13.26 | 5.83 | 13.27 | 0.00 | 13.27 | 0.00 | 13.27 |
February | 102.00 | 13.63 | 4.50 | 13.62 | 0.00 | 13.62 | 0.00 | 13.62 |
March | 94.33 | 14.09 | 4.83 | 14.08 | 0.00 | 14.08 | 0.00 | 14.08 |
April | 41.17 | 14.56 | 3.33 | 14.56 | 0.00 | 14.56 | 0.00 | 14.56 |
May | 1.33 | 14.81 | 0.17 | 14.81 | 2.67 | 22.95 | 0.00 | 22.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.65 | 0.00 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.62 | 0.00 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.46 | 0.00 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.47 | 0.00 | 27.47 |
October | 18.50 | 14.82 | 1.50 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
November | 96.67 | 14.26 | 4.50 | 14.26 | 0.00 | 14.26 | 0.00 | 14.26 |
December | 116.00 | 13.33 | 5.00 | 13.34 | 0.00 | 13.34 | 0.00 | 13.34 |
Annual Sum or Average | 587.67 | 13.78 | 29.67 | 13.78 | 37.33 | 14.57 | 0.00 | 14.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 0.00 | 13.27 |
Maximum of Months | 117.67 | 14.82 | 5.83 | 14.82 | 18.33 | 27.65 | 0.00 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.96 | 300.00 | 20.96 | 300.00 | 20.96 |
February | 276.00 | 21.00 | 276.00 | 21.00 | 276.00 | 21.00 |
March | 324.00 | 21.04 | 320.33 | 21.03 | 320.33 | 21.03 |
April | 300.00 | 21.77 | 211.17 | 21.50 | 211.17 | 21.39 |
May | 204.00 | 23.17 | 102.50 | 23.12 | 33.33 | 22.93 |
June | 114.33 | 23.74 | 172.83 | 23.84 | 43.17 | 23.85 |
July | 35.33 | 23.88 | 286.00 | 23.90 | 34.33 | 23.90 |
August | 41.50 | 23.79 | 273.67 | 23.89 | 29.83 | 23.89 |
September | 183.33 | 23.35 | 62.83 | 23.45 | 13.33 | 23.43 |
October | 300.00 | 22.12 | 154.83 | 21.78 | 154.83 | 21.62 |
November | 288.00 | 21.14 | 274.33 | 21.11 | 274.33 | 21.09 |
December | 300.00 | 21.00 | 300.00 | 21.00 | 300.00 | 21.00 |
Annual Sum or Average | 2666.50 | 21.76 | 2734.50 | 21.85 | 1990.67 | 21.67 |
Minimum of Months | 35.33 | 20.96 | 62.83 | 20.96 | 13.33 | 20.96 |
Maximum of Months | 324.00 | 23.88 | 320.33 | 23.90 | 320.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.52 | 300.00 | 15.52 | 300.00 | 15.52 |
February | 276.00 | 15.83 | 276.00 | 15.83 | 276.00 | 15.83 |
March | 324.00 | 16.29 | 324.00 | 16.29 | 324.00 | 16.29 |
April | 292.50 | 19.18 | 231.83 | 18.66 | 231.83 | 18.46 |
May | 169.83 | 23.37 | 203.50 | 24.31 | 87.00 | 24.10 |
June | 164.67 | 26.12 | 276.17 | 26.40 | 138.83 | 26.46 |
July | 219.00 | 26.67 | 296.83 | 26.63 | 217.83 | 26.65 |
August | 196.00 | 26.52 | 310.50 | 26.52 | 187.17 | 26.56 |
September | 157.50 | 23.43 | 173.83 | 24.61 | 50.33 | 24.49 |
October | 288.67 | 19.63 | 215.17 | 19.17 | 211.00 | 18.94 |
November | 288.00 | 16.69 | 284.00 | 16.65 | 284.00 | 16.64 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 2976.17 | 19.50 | 3191.83 | 19.93 | 2608.00 | 19.65 |
Minimum of Months | 157.50 | 15.52 | 173.83 | 15.52 | 50.33 | 15.52 |
Maximum of Months | 324.00 | 26.67 | 324.00 | 26.63 | 324.00 | 26.65 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
February | 276.00 | 10.07 | 276.00 | 10.07 | 276.00 | 10.07 |
March | 324.00 | 10.38 | 324.00 | 10.38 | 324.00 | 10.38 |
April | 300.00 | 12.75 | 300.00 | 12.75 | 300.00 | 12.75 |
May | 271.17 | 19.47 | 228.67 | 19.48 | 194.67 | 19.16 |
June | 232.83 | 24.95 | 201.33 | 25.68 | 140.17 | 25.95 |
July | 235.83 | 28.57 | 286.67 | 28.30 | 230.17 | 28.43 |
August | 217.67 | 26.25 | 250.00 | 26.60 | 159.33 | 26.86 |
September | 268.17 | 19.88 | 207.33 | 19.73 | 188.17 | 19.51 |
October | 300.00 | 13.00 | 300.00 | 13.00 | 300.00 | 13.00 |
November | 288.00 | 10.42 | 288.00 | 10.42 | 288.00 | 10.42 |
December | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
Annual Sum or Average | 3313.67 | 15.61 | 3262.00 | 15.70 | 3000.50 | 15.45 |
Minimum of Months | 217.67 | 10.00 | 201.33 | 10.00 | 140.17 | 10.00 |
Maximum of Months | 324.00 | 28.57 | 324.00 | 28.30 | 324.00 | 28.43 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 1288665.19 | 337973.86 | 6.33 | 1288665.19 | 0.00 | 0.00 | 0.05 | 13-APR-16:00 | 0.00 | 01-APR-00:10 | 463.92 | 13-APR-16:00 | 463.92 | 13-APR-16:00 | 0.00 | 13-APR-15:40 | 121.47 | 13-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.224534E+10 | 0.545579E+09 | 98.64 | 0.198744E+10 | 0.257902E+09 | 0.00 | 1.00 | 18-MAY-05:03 | 0.00 | 01-MAY-00:10 | 24320.17 | 26-MAY-05:02 | 18582.51 | 19-MAY-05:02 | 8199.28 | 27-MAY-05:03 | 5742.44 | 26-MAY-05:02 | 0.00 | 01-MAY-00:10 |
June | 0.553179E+10 | 0.134266E+10 | 190.04 | 0.436988E+10 | 0.116192E+10 | 0.00 | 1.00 | 19-JUN-05:03 | 0.00 | 01-JUN-00:10 | 29305.77 | 30-JUN-05:01 | 16581.15 | 30-JUN-05:01 | 13927.93 | 23-JUN-05:03 | 6750.50 | 30-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.863083E+10 | 0.204252E+10 | 249.21 | 0.643906E+10 | 0.219177E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 27015.71 | 05-JUL-05:51 | 17443.38 | 21-JUL-05:13 | 15171.07 | 05-JUL-05:51 | 6255.07 | 05-JUL-05:51 | 0.00 | 01-JUL-00:10 |
August | 0.617319E+10 | 0.145207E+10 | 209.36 | 0.449052E+10 | 0.168267E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 25707.39 | 09-AUG-05:01 | 15944.50 | 05-AUG-05:02 | 13780.50 | 30-AUG-05:45 | 6019.90 | 09-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.831521E+09 | 0.200920E+09 | 66.09 | 0.715623E+09 | 0.115898E+09 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 24783.29 | 01-SEP-05:02 | 16432.50 | 02-SEP-05:02 | 13407.39 | 01-SEP-05:03 | 5838.35 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 35233998.22 | 8995902.00 | 7.17 | 35063298.14 | 170700.08 | 0.00 | 0.31 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3368.30 | 19-OCT-15:00 | 3368.30 | 19-OCT-15:00 | 52.59 | 19-OCT-13:50 | 848.16 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.234492E+11 | 0.559307E+10 | 826.84 | 0.180389E+11 | 0.541033E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.863083E+10 | 0.204252E+10 | 249.21 | 0.643906E+10 | 0.219177E+10 | 0.00 | 1.00 | 0.00 | 29305.77 | 18582.51 | 15171.07 | 6750.50 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.497388E+10 | 0.125047E+10 | 62.10 | 0.469572E+10 | 0.278163E+09 | 0.00 | 1.00 | 17-MAY-17:08 | 0.00 | 01-MAY-00:10 | 113361.41 | 26-MAY-17:10 | 103867.56 | 24-MAY-19:50 | 37092.40 | 26-MAY-17:41 | 26516.35 | 26-MAY-17:10 | 0.00 | 01-MAY-00:10 |
June | 0.144796E+11 | 0.359975E+10 | 146.67 | 0.120850E+11 | 0.239456E+10 | 0.00 | 1.00 | 07-JUN-17:08 | 0.00 | 01-JUN-00:10 | 122175.05 | 19-JUN-17:20 | 106791.99 | 20-JUN-17:08 | 56892.81 | 27-JUN-22:01 | 29557.12 | 29-JUN-17:04 | 0.00 | 01-JUN-00:10 |
July | 0.244997E+11 | 0.596194E+10 | 209.52 | 0.200051E+11 | 0.449455E+10 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:10 | 127992.09 | 04-JUL-00:01 | 106970.11 | 26-JUL-17:06 | 74510.52 | 04-JUL-00:01 | 28897.95 | 04-JUL-00:01 | 0.00 | 01-JUL-00:10 |
August | 0.124635E+11 | 0.301605E+10 | 121.43 | 0.101922E+11 | 0.227133E+10 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:10 | 121218.88 | 07-AUG-17:10 | 107060.43 | 13-AUG-12:10 | 54136.11 | 09-AUG-21:51 | 28453.21 | 08-AUG-17:06 | 0.00 | 01-AUG-00:10 |
September | 0.123931E+10 | 0.299454E+09 | 26.81 | 0.110479E+10 | 0.134528E+09 | 0.00 | 1.00 | 01-SEP-17:06 | 0.00 | 01-SEP-00:10 | 111517.32 | 01-SEP-18:01 | 102370.59 | 03-SEP-17:20 | 44238.91 | 01-SEP-19:51 | 26165.19 | 01-SEP-18:01 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.576560E+11 | 0.141277E+11 | 566.53 | 0.480828E+11 | 0.957313E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.244997E+11 | 0.596194E+10 | 209.52 | 0.200051E+11 | 0.449455E+10 | 0.00 | 1.00 | 0.00 | 127992.09 | 107060.43 | 74510.52 | 29557.12 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.74 | 60.60 | 83.14 | 43.97 | 669.01 | 0.00 | 0.00 | 0.00 |
February | 232.40 | 106.21 | 126.19 | 130.84 | 526.55 | 0.00 | 0.00 | 0.00 |
March | 305.79 | 156.74 | 149.05 | 222.05 | 397.12 | 0.00 | 0.00 | 0.00 |
April | 389.67 | 197.33 | 192.35 | 353.11 | 235.96 | 0.00 | 0.00 | 0.00 |
May | 479.83 | 229.25 | 250.58 | 506.83 | 152.97 | 0.00 | 0.00 | 0.00 |
June | 462.30 | 200.00 | 262.30 | 514.62 | 119.93 | 0.00 | 0.00 | 0.00 |
July | 494.47 | 230.45 | 264.02 | 565.63 | 124.88 | 0.00 | 0.00 | 0.00 |
August | 404.96 | 183.38 | 221.57 | 444.41 | 142.77 | 0.00 | 0.00 | 0.00 |
September | 317.21 | 142.25 | 174.96 | 299.46 | 195.63 | 0.00 | 0.00 | 0.00 |
October | 200.71 | 80.64 | 120.07 | 146.60 | 249.54 | 0.00 | 0.00 | 0.00 |
November | 122.45 | 41.72 | 80.73 | 52.98 | 378.14 | 0.00 | 0.00 | 0.00 |
December | 108.14 | 37.62 | 70.52 | 22.01 | 648.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 305.54 | 139.05 | 166.50 | 276.07 | 319.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.14 | 37.62 | 70.52 | 22.01 | 119.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 494.47 | 230.45 | 264.02 | 565.63 | 669.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.42 | 67.22 | 92.21 | 48.77 | 741.99 | 0.00 | 0.00 | 0.00 |
February | 257.75 | 117.79 | 139.96 | 145.11 | 584.00 | 0.00 | 0.00 | 0.00 |
March | 339.15 | 173.84 | 165.31 | 246.28 | 440.45 | 0.00 | 0.00 | 0.00 |
April | 432.19 | 218.86 | 213.33 | 391.63 | 261.70 | 0.00 | 0.00 | 0.00 |
May | 532.18 | 254.26 | 277.92 | 562.12 | 169.66 | 0.00 | 0.00 | 0.00 |
June | 512.73 | 221.82 | 290.91 | 570.76 | 133.02 | 0.00 | 0.00 | 0.00 |
July | 548.42 | 255.60 | 292.82 | 627.34 | 138.51 | 0.00 | 0.00 | 0.00 |
August | 449.14 | 203.39 | 245.75 | 492.89 | 158.34 | 0.00 | 0.00 | 0.00 |
September | 351.82 | 157.77 | 194.05 | 332.13 | 216.97 | 0.00 | 0.00 | 0.00 |
October | 222.61 | 89.44 | 133.17 | 162.59 | 276.76 | 0.00 | 0.00 | 0.00 |
November | 135.81 | 46.27 | 89.54 | 58.76 | 419.40 | 0.00 | 0.00 | 0.00 |
December | 119.94 | 41.72 | 78.22 | 24.41 | 718.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 338.88 | 154.22 | 184.66 | 306.19 | 354.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.94 | 41.72 | 78.22 | 24.41 | 133.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 548.42 | 255.60 | 292.82 | 627.34 | 741.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.06 | 0.00 | 26.06 | 0.10 | 297.02 | 0.00 | 0.00 | 0.00 |
February | 40.02 | 0.00 | 40.02 | 1.79 | 234.81 | 0.00 | 0.00 | 0.00 |
March | 49.26 | 0.00 | 49.25 | 4.71 | 176.24 | 0.00 | 0.00 | 0.00 |
April | 64.70 | 0.63 | 64.06 | 24.90 | 99.89 | 0.00 | 0.00 | 0.00 |
May | 90.87 | 4.89 | 85.98 | 66.94 | 59.15 | 0.00 | 0.00 | 0.00 |
June | 101.29 | 11.08 | 90.20 | 94.83 | 45.63 | 0.00 | 0.00 | 0.00 |
July | 96.67 | 8.17 | 88.50 | 92.09 | 47.29 | 0.00 | 0.00 | 0.00 |
August | 73.78 | 1.49 | 72.28 | 60.93 | 56.50 | 0.00 | 0.00 | 0.00 |
September | 57.34 | 0.04 | 57.30 | 31.09 | 82.15 | 0.00 | 0.00 | 0.00 |
October | 39.78 | 0.00 | 39.78 | 9.28 | 106.34 | 0.00 | 0.00 | 0.00 |
November | 26.34 | 0.00 | 26.34 | 1.54 | 164.26 | 0.00 | 0.00 | 0.00 |
December | 22.08 | 0.00 | 22.08 | 0.00 | 283.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.43 | 2.20 | 55.23 | 32.54 | 137.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.08 | 0.00 | 22.08 | 0.00 | 45.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.29 | 11.08 | 90.20 | 94.83 | 297.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.06 | 0.00 | 26.06 | 0.10 | 297.02 | 0.00 | 0.00 | 0.00 |
February | 40.02 | 0.00 | 40.02 | 1.79 | 234.81 | 0.00 | 0.00 | 0.00 |
March | 49.26 | 0.00 | 49.25 | 4.71 | 176.24 | 0.00 | 0.00 | 0.00 |
April | 64.70 | 0.63 | 64.06 | 24.90 | 99.89 | 0.00 | 0.00 | 0.00 |
May | 90.87 | 4.89 | 85.98 | 66.94 | 59.15 | 0.00 | 0.00 | 0.00 |
June | 101.29 | 11.08 | 90.20 | 94.83 | 45.63 | 0.00 | 0.00 | 0.00 |
July | 96.67 | 8.17 | 88.50 | 92.09 | 47.29 | 0.00 | 0.00 | 0.00 |
August | 73.78 | 1.49 | 72.28 | 60.93 | 56.50 | 0.00 | 0.00 | 0.00 |
September | 57.34 | 0.04 | 57.30 | 31.09 | 82.15 | 0.00 | 0.00 | 0.00 |
October | 39.78 | 0.00 | 39.78 | 9.28 | 106.34 | 0.00 | 0.00 | 0.00 |
November | 26.34 | 0.00 | 26.34 | 1.54 | 164.26 | 0.00 | 0.00 | 0.00 |
December | 22.08 | 0.00 | 22.08 | 0.00 | 283.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.43 | 2.20 | 55.23 | 32.54 | 137.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.08 | 0.00 | 22.08 | 0.00 | 45.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.29 | 11.08 | 90.20 | 94.83 | 297.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINE STORAGE OFFICE FRONT WALL WINDOW
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1327.68 | 559.77 | 767.90 | 477.20 | 5388.63 | 0.00 | 0.00 | 0.00 |
February | 2146.58 | 981.00 | 1165.58 | 1311.16 | 4226.79 | 0.00 | 0.00 | 0.00 |
March | 2824.45 | 1447.75 | 1376.70 | 2156.48 | 3165.68 | 0.00 | 0.00 | 0.00 |
April | 3599.26 | 1822.64 | 1776.61 | 3304.40 | 1917.50 | 0.00 | 0.00 | 0.00 |
May | 4432.02 | 2117.51 | 2314.51 | 4554.69 | 1325.02 | 0.00 | 0.00 | 0.00 |
June | 4270.06 | 1847.31 | 2422.74 | 4553.39 | 1068.78 | 0.00 | 0.00 | 0.00 |
July | 4567.23 | 2128.60 | 2438.63 | 5026.52 | 1100.72 | 0.00 | 0.00 | 0.00 |
August | 3740.41 | 1693.84 | 2046.58 | 3944.82 | 1262.95 | 0.00 | 0.00 | 0.00 |
September | 2929.93 | 1313.88 | 1616.05 | 2704.60 | 1644.47 | 0.00 | 0.00 | 0.00 |
October | 1853.89 | 744.85 | 1109.03 | 1426.77 | 1941.76 | 0.00 | 0.00 | 0.00 |
November | 1131.03 | 385.34 | 745.69 | 560.59 | 2953.79 | 0.00 | 0.00 | 0.00 |
December | 998.87 | 347.47 | 651.40 | 249.66 | 5175.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2822.17 | 1284.32 | 1537.85 | 2529.65 | 2591.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 998.87 | 347.47 | 651.40 | 249.66 | 1068.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4567.23 | 2128.60 | 2438.63 | 5026.52 | 5388.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINE STORAGE OFFICE LEFT WALL WINDOW
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 207.93 | 0.00 | 207.93 | 1.21 | 2077.48 | 0.00 | 0.00 | 0.00 |
February | 319.40 | 0.00 | 319.40 | 24.10 | 1619.46 | 0.00 | 0.00 | 0.00 |
March | 393.07 | 0.03 | 393.04 | 56.48 | 1197.69 | 0.00 | 0.00 | 0.00 |
April | 516.29 | 5.06 | 511.22 | 217.50 | 694.51 | 0.00 | 0.00 | 0.00 |
May | 725.19 | 39.05 | 686.14 | 502.29 | 442.60 | 0.00 | 0.00 | 0.00 |
June | 808.26 | 88.44 | 719.83 | 697.04 | 351.90 | 0.00 | 0.00 | 0.00 |
July | 771.46 | 65.23 | 706.23 | 675.96 | 359.29 | 0.00 | 0.00 | 0.00 |
August | 588.74 | 11.90 | 576.84 | 439.50 | 430.95 | 0.00 | 0.00 | 0.00 |
September | 457.60 | 0.33 | 457.27 | 235.00 | 598.21 | 0.00 | 0.00 | 0.00 |
October | 317.41 | 0.00 | 317.41 | 96.58 | 710.87 | 0.00 | 0.00 | 0.00 |
November | 210.16 | 0.00 | 210.16 | 20.17 | 1097.51 | 0.00 | 0.00 | 0.00 |
December | 176.18 | 0.00 | 176.18 | 0.01 | 1965.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 458.33 | 17.58 | 440.75 | 248.49 | 959.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 176.18 | 0.00 | 176.18 | 0.01 | 351.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 808.26 | 88.44 | 719.83 | 697.04 | 2077.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 4.81 | 178.73 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 31.01 | 134.80 | 4.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 63.70 | 94.69 | 5.67 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 118.35 | 53.44 | 2.67 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 154.57 | 40.39 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 162.13 | 38.96 | 26.00 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 162.37 | 47.20 | 18.50 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 127.54 | 45.30 | 28.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 89.25 | 47.40 | 12.50 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 47.53 | 49.72 | 55.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 17.41 | 84.23 | 18.17 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 1.71 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 81.95 | 81.74 | 171.50 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 1.71 | 38.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 162.37 | 178.73 | 55.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 4.81 | 178.73 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 31.01 | 134.80 | 4.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 63.70 | 94.69 | 5.67 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 118.35 | 53.44 | 2.67 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 154.57 | 40.39 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 162.13 | 38.96 | 26.00 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 162.37 | 47.20 | 18.50 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 127.54 | 45.30 | 28.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 89.25 | 47.40 | 12.50 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 47.53 | 49.72 | 55.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 17.41 | 84.23 | 18.17 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 1.71 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 81.95 | 81.74 | 171.50 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 1.71 | 38.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 162.37 | 178.73 | 55.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 4.81 | 178.73 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 31.01 | 134.80 | 4.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 63.70 | 94.69 | 5.67 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 118.35 | 53.44 | 2.67 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 154.57 | 40.39 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 162.13 | 38.96 | 26.00 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 162.37 | 47.20 | 18.50 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 127.54 | 45.30 | 28.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 89.25 | 47.40 | 12.50 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 47.53 | 49.72 | 55.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 17.41 | 84.23 | 18.17 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 1.71 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 81.95 | 81.74 | 171.50 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 1.71 | 38.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 162.37 | 178.73 | 55.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 4.81 | 178.73 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 31.01 | 134.80 | 4.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 63.70 | 94.69 | 5.67 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 118.35 | 53.44 | 2.67 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 154.57 | 40.39 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 162.13 | 38.96 | 26.00 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 162.37 | 47.20 | 18.50 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 127.54 | 45.30 | 28.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 89.25 | 47.40 | 12.50 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 47.53 | 49.72 | 55.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 17.41 | 84.23 | 18.17 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 1.71 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 81.95 | 81.74 | 171.50 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 1.71 | 38.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 162.37 | 178.73 | 55.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 4.81 | 178.73 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 31.01 | 134.80 | 4.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 63.70 | 94.69 | 5.67 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 118.35 | 53.44 | 2.67 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 154.57 | 40.39 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 162.13 | 38.96 | 26.00 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 162.37 | 47.20 | 18.50 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 127.54 | 45.30 | 28.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 89.25 | 47.40 | 12.50 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 47.53 | 49.72 | 55.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 17.41 | 84.23 | 18.17 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 1.71 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 81.95 | 81.74 | 171.50 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 1.71 | 38.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 162.37 | 178.73 | 55.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 4.81 | 178.73 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 31.01 | 134.80 | 4.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 63.70 | 94.69 | 5.67 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 118.35 | 53.44 | 2.67 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 154.57 | 40.39 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 162.13 | 38.96 | 26.00 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 162.37 | 47.20 | 18.50 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 127.54 | 45.30 | 28.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 89.25 | 47.40 | 12.50 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 47.53 | 49.72 | 55.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 17.41 | 84.23 | 18.17 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 1.71 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 81.95 | 81.74 | 171.50 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 1.71 | 38.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 162.37 | 178.73 | 55.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 4.81 | 178.73 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 31.01 | 134.80 | 4.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 63.70 | 94.69 | 5.67 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 118.35 | 53.44 | 2.67 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 154.57 | 40.39 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 162.13 | 38.96 | 26.00 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 162.37 | 47.20 | 18.50 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 127.54 | 45.30 | 28.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 89.25 | 47.40 | 12.50 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 47.53 | 49.72 | 55.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 17.41 | 84.23 | 18.17 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 1.71 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 81.95 | 81.74 | 171.50 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 1.71 | 38.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 162.37 | 178.73 | 55.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 4.81 | 178.73 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 31.01 | 134.80 | 4.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 63.70 | 94.69 | 5.67 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 118.35 | 53.44 | 2.67 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 154.57 | 40.39 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 162.13 | 38.96 | 26.00 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 162.37 | 47.20 | 18.50 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 127.54 | 45.30 | 28.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 89.25 | 47.40 | 12.50 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 47.53 | 49.72 | 55.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 17.41 | 84.23 | 18.17 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 1.71 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 81.95 | 81.74 | 171.50 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 1.71 | 38.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 162.37 | 178.73 | 55.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 4.81 | 178.73 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 31.01 | 134.80 | 4.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 63.70 | 94.69 | 5.67 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 118.35 | 53.44 | 2.67 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 154.57 | 40.39 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 162.13 | 38.96 | 26.00 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 162.37 | 47.20 | 18.50 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 127.54 | 45.30 | 28.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 89.25 | 47.40 | 12.50 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 47.53 | 49.72 | 55.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 17.41 | 84.23 | 18.17 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 1.71 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 81.95 | 81.74 | 171.50 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 1.71 | 38.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 162.37 | 178.73 | 55.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.39 | 9.39 | 17.00 | 4.81 | 178.73 | 0.00 | 0.00 | 0.00 |
February | 46.56 | 21.57 | 24.99 | 31.01 | 134.80 | 4.00 | 0.00 | 0.00 |
March | 66.74 | 37.77 | 28.98 | 63.70 | 94.69 | 5.67 | 0.00 | 0.00 |
April | 97.05 | 61.06 | 35.99 | 118.35 | 53.44 | 2.67 | 0.00 | 0.00 |
May | 119.05 | 66.76 | 52.29 | 154.57 | 40.39 | 0.00 | 0.00 | 0.00 |
June | 125.63 | 72.28 | 53.35 | 162.13 | 38.96 | 26.00 | 0.00 | 0.00 |
July | 128.40 | 76.42 | 51.98 | 162.37 | 47.20 | 18.50 | 0.00 | 0.00 |
August | 102.29 | 57.62 | 44.68 | 127.54 | 45.30 | 28.33 | 0.00 | 0.00 |
September | 74.40 | 38.48 | 35.92 | 89.25 | 47.40 | 12.50 | 0.00 | 0.00 |
October | 42.90 | 16.46 | 26.44 | 47.53 | 49.72 | 55.67 | 0.00 | 0.00 |
November | 25.72 | 7.99 | 17.73 | 17.41 | 84.23 | 18.17 | 0.00 | 0.00 |
December | 20.47 | 5.35 | 15.12 | 1.71 | 167.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.10 | 39.34 | 33.75 | 81.95 | 81.74 | 171.50 | 0.00 | 0.00 |
Minimum of Months | 20.47 | 5.35 | 15.12 | 1.71 | 38.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.40 | 76.42 | 53.35 | 162.37 | 178.73 | 55.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.384997E+09 | 0.162322E+09 | 0.222675E+09 | 0.117777E+09 | 0.179187E+10 |
February | 0.562221E+09 | 0.256938E+09 | 0.305283E+09 | 0.316520E+09 | 0.127383E+10 |
March | 0.819026E+09 | 0.419814E+09 | 0.399212E+09 | 0.594748E+09 | 0.106365E+10 |
April | 0.101004E+10 | 0.511477E+09 | 0.498558E+09 | 0.915265E+09 | 0.611612E+09 |
May | 0.128519E+10 | 0.614032E+09 | 0.671154E+09 | 0.135748E+10 | 0.409718E+09 |
June | 0.119828E+10 | 0.518400E+09 | 0.679877E+09 | 0.133390E+10 | 0.310862E+09 |
July | 0.132439E+10 | 0.617248E+09 | 0.707146E+09 | 0.151499E+10 | 0.334486E+09 |
August | 0.108464E+10 | 0.491175E+09 | 0.593461E+09 | 0.119031E+10 | 0.382384E+09 |
September | 0.822207E+09 | 0.368707E+09 | 0.453500E+09 | 0.776198E+09 | 0.507071E+09 |
October | 0.537586E+09 | 0.215991E+09 | 0.321595E+09 | 0.392655E+09 | 0.668363E+09 |
November | 0.317395E+09 | 0.108137E+09 | 0.209258E+09 | 0.137324E+09 | 0.980152E+09 |
December | 0.289650E+09 | 0.100760E+09 | 0.188890E+09 | 58958892.75 | 0.173616E+10 |
Annual Sum or Average | 0.963561E+10 | 0.438500E+10 | 0.525061E+10 | 0.870613E+10 | 0.100702E+11 |
Minimum of Months | 0.289650E+09 | 0.100760E+09 | 0.188890E+09 | 58958892.75 | 0.310862E+09 |
Maximum of Months | 0.132439E+10 | 0.617248E+09 | 0.707146E+09 | 0.151499E+10 | 0.179187E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.426998E+09 | 0.180031E+09 | 0.246968E+09 | 0.130626E+09 | 0.198735E+10 |
February | 0.623557E+09 | 0.284969E+09 | 0.338588E+09 | 0.351052E+09 | 0.141280E+10 |
March | 0.908379E+09 | 0.465615E+09 | 0.442764E+09 | 0.659633E+09 | 0.117969E+10 |
April | 0.112023E+10 | 0.567278E+09 | 0.552949E+09 | 0.101512E+10 | 0.678336E+09 |
May | 0.142539E+10 | 0.681021E+09 | 0.744374E+09 | 0.150558E+10 | 0.454417E+09 |
June | 0.132900E+10 | 0.574956E+09 | 0.754049E+09 | 0.147942E+10 | 0.344776E+09 |
July | 0.146888E+10 | 0.684588E+09 | 0.784293E+09 | 0.168027E+10 | 0.370978E+09 |
August | 0.120297E+10 | 0.544761E+09 | 0.658205E+09 | 0.132017E+10 | 0.424100E+09 |
September | 0.911907E+09 | 0.408932E+09 | 0.502975E+09 | 0.860878E+09 | 0.562391E+09 |
October | 0.596234E+09 | 0.239555E+09 | 0.356679E+09 | 0.435492E+09 | 0.741279E+09 |
November | 0.352021E+09 | 0.119934E+09 | 0.232087E+09 | 0.152306E+09 | 0.108708E+10 |
December | 0.321250E+09 | 0.111753E+09 | 0.209497E+09 | 65391084.90 | 0.192556E+10 |
Annual Sum or Average | 0.106868E+11 | 0.486339E+10 | 0.582343E+10 | 0.965593E+10 | 0.111688E+11 |
Minimum of Months | 0.321250E+09 | 0.111753E+09 | 0.209497E+09 | 65391084.90 | 0.344776E+09 |
Maximum of Months | 0.146888E+10 | 0.684588E+09 | 0.784293E+09 | 0.168027E+10 | 0.198735E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69788952.23 | 0.00 | 69788952.23 | 260684.07 | 0.795544E+09 |
February | 96826890.10 | 0.00 | 96826890.10 | 4338045.37 | 0.568048E+09 |
March | 0.131927E+09 | 9453.70 | 0.131918E+09 | 12625769.36 | 0.472052E+09 |
April | 0.167694E+09 | 1643695.43 | 0.166051E+09 | 64548747.34 | 0.258907E+09 |
May | 0.243399E+09 | 13106449.88 | 0.230293E+09 | 0.179291E+09 | 0.158424E+09 |
June | 0.262532E+09 | 28725344.98 | 0.233806E+09 | 0.245797E+09 | 0.118271E+09 |
July | 0.258930E+09 | 21891880.14 | 0.237038E+09 | 0.246661E+09 | 0.126653E+09 |
August | 0.197602E+09 | 3993928.40 | 0.193608E+09 | 0.163197E+09 | 0.151329E+09 |
September | 0.148632E+09 | 107133.18 | 0.148525E+09 | 80597216.81 | 0.212941E+09 |
October | 0.106534E+09 | 0.00 | 0.106534E+09 | 24849391.54 | 0.284818E+09 |
November | 68263448.13 | 0.00 | 68263448.13 | 3998918.95 | 0.425769E+09 |
December | 59130781.71 | 0.00 | 59130781.71 | 0.00 | 0.758539E+09 |
Annual Sum or Average | 0.181126E+10 | 69477885.71 | 0.174178E+10 | 0.102616E+10 | 0.433130E+10 |
Minimum of Months | 59130781.71 | 0.00 | 59130781.71 | 0.00 | 0.118271E+09 |
Maximum of Months | 0.262532E+09 | 28725344.98 | 0.237038E+09 | 0.246661E+09 | 0.795544E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69788952.24 | 0.00 | 69788952.24 | 260684.07 | 0.795544E+09 |
February | 96826890.11 | 0.00 | 96826890.11 | 4338045.37 | 0.568048E+09 |
March | 0.131927E+09 | 9453.70 | 0.131918E+09 | 12625769.36 | 0.472052E+09 |
April | 0.167694E+09 | 1643695.43 | 0.166051E+09 | 64548747.34 | 0.258907E+09 |
May | 0.243399E+09 | 13106449.88 | 0.230293E+09 | 0.179291E+09 | 0.158424E+09 |
June | 0.262532E+09 | 28725344.98 | 0.233806E+09 | 0.245797E+09 | 0.118271E+09 |
July | 0.258930E+09 | 21891880.14 | 0.237038E+09 | 0.246661E+09 | 0.126653E+09 |
August | 0.197602E+09 | 3993928.40 | 0.193608E+09 | 0.163197E+09 | 0.151329E+09 |
September | 0.148632E+09 | 107133.18 | 0.148525E+09 | 80597216.81 | 0.212941E+09 |
October | 0.106534E+09 | 0.00 | 0.106534E+09 | 24849391.54 | 0.284818E+09 |
November | 68263448.13 | 0.00 | 68263448.13 | 3998918.95 | 0.425769E+09 |
December | 59130781.71 | 0.00 | 59130781.71 | 0.00 | 0.758539E+09 |
Annual Sum or Average | 0.181126E+10 | 69477885.71 | 0.174178E+10 | 0.102616E+10 | 0.433130E+10 |
Minimum of Months | 59130781.71 | 0.00 | 59130781.71 | 0.00 | 0.118271E+09 |
Maximum of Months | 0.262532E+09 | 28725344.98 | 0.237038E+09 | 0.246661E+09 | 0.795544E+09 |
Report: WindowEnergyReportMonthly
For: FINE STORAGE OFFICE FRONT WALL WINDOW
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355605E+10 | 0.149930E+10 | 0.205675E+10 | 0.127814E+10 | 0.144329E+11 |
February | 0.519300E+10 | 0.237323E+10 | 0.281977E+10 | 0.317196E+10 | 0.102254E+11 |
March | 0.756500E+10 | 0.387764E+10 | 0.368735E+10 | 0.577590E+10 | 0.847896E+10 |
April | 0.932928E+10 | 0.472429E+10 | 0.460498E+10 | 0.856501E+10 | 0.497017E+10 |
May | 0.118707E+11 | 0.567155E+10 | 0.619918E+10 | 0.121993E+11 | 0.354893E+10 |
June | 0.110680E+11 | 0.478824E+10 | 0.627975E+10 | 0.118024E+11 | 0.277029E+10 |
July | 0.122329E+11 | 0.570125E+10 | 0.653162E+10 | 0.134630E+11 | 0.294817E+10 |
August | 0.100183E+11 | 0.453677E+10 | 0.548156E+10 | 0.105658E+11 | 0.338269E+10 |
September | 0.759438E+10 | 0.340559E+10 | 0.418879E+10 | 0.701033E+10 | 0.426247E+10 |
October | 0.496545E+10 | 0.199502E+10 | 0.297044E+10 | 0.382145E+10 | 0.520080E+10 |
November | 0.293164E+10 | 0.998811E+09 | 0.193283E+10 | 0.145305E+10 | 0.765623E+10 |
December | 0.267537E+10 | 0.930677E+09 | 0.174470E+10 | 0.668698E+09 | 0.138610E+11 |
Annual Sum or Average | 0.890001E+11 | 0.405024E+11 | 0.484977E+11 | 0.797751E+11 | 0.817381E+11 |
Minimum of Months | 0.267537E+10 | 0.930677E+09 | 0.174470E+10 | 0.668698E+09 | 0.277029E+10 |
Maximum of Months | 0.122329E+11 | 0.570125E+10 | 0.653162E+10 | 0.134630E+11 | 0.144329E+11 |
Report: WindowEnergyReportMonthly
For: FINE STORAGE OFFICE LEFT WALL WINDOW
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.556921E+09 | 0.00 | 0.556921E+09 | 3227585.80 | 0.556432E+10 |
February | 0.772685E+09 | 0.00 | 0.772685E+09 | 58312359.04 | 0.391779E+10 |
March | 0.105279E+10 | 75441.16 | 0.105271E+10 | 0.151286E+09 | 0.320789E+10 |
April | 0.133821E+10 | 13116804.96 | 0.132510E+10 | 0.563769E+09 | 0.180016E+10 |
May | 0.194234E+10 | 0.104590E+09 | 0.183775E+10 | 0.134534E+10 | 0.118546E+10 |
June | 0.209502E+10 | 0.229230E+09 | 0.186579E+10 | 0.180673E+10 | 0.912125E+09 |
July | 0.206628E+10 | 0.174699E+09 | 0.189158E+10 | 0.181048E+10 | 0.962318E+09 |
August | 0.157687E+10 | 31871829.07 | 0.154500E+10 | 0.117717E+10 | 0.115425E+10 |
September | 0.118609E+10 | 854930.32 | 0.118524E+10 | 0.609122E+09 | 0.155056E+10 |
October | 0.850147E+09 | 0.00 | 0.850147E+09 | 0.258675E+09 | 0.190400E+10 |
November | 0.544747E+09 | 0.00 | 0.544747E+09 | 52285753.39 | 0.284475E+10 |
December | 0.471868E+09 | 0.00 | 0.471868E+09 | 32180.63 | 0.526324E+10 |
Annual Sum or Average | 0.144540E+11 | 0.554438E+09 | 0.138995E+11 | 0.783643E+10 | 0.302669E+11 |
Minimum of Months | 0.471868E+09 | 0.00 | 0.471868E+09 | 32180.63 | 0.912125E+09 |
Maximum of Months | 0.209502E+10 | 0.229230E+09 | 0.189158E+10 | 0.181048E+10 | 0.556432E+10 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 12893780.13 | 0.478707E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 75020099.81 | 0.326115E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.170604E+09 | 0.253623E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.306768E+09 | 0.138506E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.414004E+09 | 0.108184E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.420240E+09 | 0.100982E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.434883E+09 | 0.126412E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.341615E+09 | 0.121331E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.231327E+09 | 0.122864E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.127300E+09 | 0.133181E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 45134132.99 | 0.218319E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.449527E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.258438E+10 | 0.257775E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.100982E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.434883E+09 | 0.478707E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 12893780.13 | 0.478707E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 75020099.81 | 0.326115E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.170604E+09 | 0.253623E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.306768E+09 | 0.138506E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.414004E+09 | 0.108184E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.420240E+09 | 0.100982E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.434883E+09 | 0.126412E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.341615E+09 | 0.121331E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.231327E+09 | 0.122864E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.127300E+09 | 0.133181E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 45134132.99 | 0.218319E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.449527E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.258438E+10 | 0.257775E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.100982E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.434883E+09 | 0.478707E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 12893780.13 | 0.478707E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 75020099.81 | 0.326115E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.170604E+09 | 0.253623E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.306768E+09 | 0.138506E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.414004E+09 | 0.108184E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.420240E+09 | 0.100982E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.434883E+09 | 0.126412E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.341615E+09 | 0.121331E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.231327E+09 | 0.122864E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.127300E+09 | 0.133181E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 45134132.99 | 0.218319E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.449527E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.258438E+10 | 0.257775E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.100982E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.434883E+09 | 0.478707E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 12893780.13 | 0.478707E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 75020099.81 | 0.326115E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.170604E+09 | 0.253623E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.306768E+09 | 0.138506E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.414004E+09 | 0.108184E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.420240E+09 | 0.100982E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.434883E+09 | 0.126412E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.341615E+09 | 0.121331E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.231327E+09 | 0.122864E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.127300E+09 | 0.133181E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 45134132.99 | 0.218319E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.449527E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.258438E+10 | 0.257775E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.100982E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.434883E+09 | 0.478707E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 12893780.13 | 0.478707E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 75020099.81 | 0.326115E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.170604E+09 | 0.253623E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.306768E+09 | 0.138506E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.414004E+09 | 0.108184E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.420240E+09 | 0.100982E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.434883E+09 | 0.126412E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.341615E+09 | 0.121331E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.231327E+09 | 0.122864E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.127300E+09 | 0.133181E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 45134132.99 | 0.218319E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.449527E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.258438E+10 | 0.257775E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.100982E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.434883E+09 | 0.478707E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 12893780.13 | 0.478707E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 75020099.81 | 0.326115E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.170604E+09 | 0.253623E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.306768E+09 | 0.138506E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.414004E+09 | 0.108184E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.420240E+09 | 0.100982E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.434883E+09 | 0.126412E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.341615E+09 | 0.121331E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.231327E+09 | 0.122864E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.127300E+09 | 0.133181E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 45134132.99 | 0.218319E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.449527E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.258438E+10 | 0.257775E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.100982E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.434883E+09 | 0.478707E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 12893780.13 | 0.478707E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 75020099.81 | 0.326115E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.170604E+09 | 0.253623E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.306768E+09 | 0.138506E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.414004E+09 | 0.108184E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.420240E+09 | 0.100982E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.434883E+09 | 0.126412E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.341615E+09 | 0.121331E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.231327E+09 | 0.122864E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.127300E+09 | 0.133181E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 45134132.99 | 0.218319E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.449527E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.258438E+10 | 0.257775E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.100982E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.434883E+09 | 0.478707E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 12893780.13 | 0.478707E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 75020099.81 | 0.326115E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.170604E+09 | 0.253623E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.306768E+09 | 0.138506E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.414004E+09 | 0.108184E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.420240E+09 | 0.100982E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.434883E+09 | 0.126412E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.341615E+09 | 0.121331E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.231327E+09 | 0.122864E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.127300E+09 | 0.133181E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 45134132.99 | 0.218319E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.449527E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.258438E+10 | 0.257775E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.100982E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.434883E+09 | 0.478707E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 12893780.13 | 0.478707E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 75020099.81 | 0.326115E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.170604E+09 | 0.253623E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.306768E+09 | 0.138506E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.414004E+09 | 0.108184E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.420240E+09 | 0.100982E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.434883E+09 | 0.126412E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.341615E+09 | 0.121331E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.231327E+09 | 0.122864E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.127300E+09 | 0.133181E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 45134132.99 | 0.218319E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.449527E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.258438E+10 | 0.257775E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.100982E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.434883E+09 | 0.478707E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70674513.73 | 25141978.29 | 45532535.45 | 12893780.13 | 0.478707E+09 |
February | 0.112637E+09 | 52173245.48 | 60463899.46 | 75020099.81 | 0.326115E+09 |
March | 0.178768E+09 | 0.101158E+09 | 77610505.25 | 0.170604E+09 | 0.253623E+09 |
April | 0.251552E+09 | 0.158256E+09 | 93296235.20 | 0.306768E+09 | 0.138506E+09 |
May | 0.318856E+09 | 0.178814E+09 | 0.140042E+09 | 0.414004E+09 | 0.108184E+09 |
June | 0.325636E+09 | 0.187352E+09 | 0.138284E+09 | 0.420240E+09 | 0.100982E+09 |
July | 0.343902E+09 | 0.204680E+09 | 0.139222E+09 | 0.434883E+09 | 0.126412E+09 |
August | 0.273987E+09 | 0.154325E+09 | 0.119662E+09 | 0.341615E+09 | 0.121331E+09 |
September | 0.192851E+09 | 99748392.38 | 93102443.95 | 0.231327E+09 | 0.122864E+09 |
October | 0.114915E+09 | 44086124.57 | 70829316.40 | 0.127300E+09 | 0.133181E+09 |
November | 66663930.83 | 20719281.35 | 45944649.48 | 45134132.99 | 0.218319E+09 |
December | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.449527E+09 |
Annual Sum or Average | 0.230526E+10 | 0.124077E+10 | 0.106449E+10 | 0.258438E+10 | 0.257775E+10 |
Minimum of Months | 54815982.45 | 14316141.78 | 40499840.67 | 4590449.65 | 0.100982E+09 |
Maximum of Months | 0.343902E+09 | 0.204680E+09 | 0.140042E+09 | 0.434883E+09 | 0.478707E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 63.41 | 1975.51 | 355.28 | 127.82 | 227.46 | 0.00 | 0.00 |
February | 249.83 | 1550.46 | 570.20 | 224.00 | 346.20 | 0.00 | 0.00 |
March | 454.23 | 1166.52 | 743.45 | 330.59 | 412.86 | 0.00 | 0.00 |
April | 786.77 | 689.66 | 951.25 | 417.45 | 533.80 | 0.00 | 0.00 |
May | 1200.20 | 438.30 | 1193.76 | 493.30 | 700.46 | 0.00 | 0.00 |
June | 1266.56 | 335.73 | 1177.60 | 443.98 | 733.62 | 0.00 | 0.00 |
July | 1369.72 | 350.52 | 1236.24 | 502.40 | 733.84 | 0.00 | 0.00 |
August | 1057.89 | 412.82 | 1001.64 | 389.76 | 611.89 | 0.00 | 0.00 |
September | 688.88 | 572.01 | 783.71 | 300.10 | 483.61 | 0.00 | 0.00 |
October | 320.96 | 732.19 | 502.87 | 170.08 | 332.79 | 0.00 | 0.00 |
November | 100.69 | 1111.94 | 310.93 | 87.99 | 222.94 | 0.00 | 0.00 |
December | 27.00 | 1914.12 | 272.24 | 79.34 | 192.89 | 0.00 | 0.00 |
Annual Sum or Average | 634.46 | 935.29 | 759.29 | 297.67 | 461.62 | 0.00 | 0.00 |
Minimum of Months | 27.00 | 335.73 | 272.24 | 79.34 | 192.89 | 0.00 | 0.00 |
Maximum of Months | 1369.72 | 1975.51 | 1236.24 | 502.40 | 733.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 363.15 | 7350.85 | 1535.61 | 559.77 | 975.83 | 0.00 | 0.00 |
February | 1237.12 | 5748.11 | 2465.97 | 981.00 | 1484.98 | 0.00 | 0.00 |
March | 2143.28 | 4293.69 | 3217.51 | 1447.77 | 1769.74 | 0.00 | 0.00 |
April | 3497.43 | 2587.53 | 4115.54 | 1827.70 | 2287.84 | 0.00 | 0.00 |
May | 5044.77 | 1755.41 | 5157.21 | 2156.56 | 3000.65 | 0.00 | 0.00 |
June | 5215.63 | 1385.88 | 5078.32 | 1935.75 | 3142.57 | 0.00 | 0.00 |
July | 5670.57 | 1428.10 | 5338.69 | 2193.83 | 3144.86 | 0.00 | 0.00 |
August | 4379.17 | 1688.75 | 4329.15 | 1705.74 | 2623.42 | 0.00 | 0.00 |
September | 2919.66 | 2222.74 | 3387.53 | 1314.21 | 2073.31 | 0.00 | 0.00 |
October | 1500.48 | 2629.77 | 2171.30 | 744.85 | 1426.44 | 0.00 | 0.00 |
November | 534.12 | 4004.66 | 1341.20 | 385.34 | 955.85 | 0.00 | 0.00 |
December | 170.47 | 7060.96 | 1175.05 | 347.47 | 827.57 | 0.00 | 0.00 |
Annual Sum or Average | 2731.71 | 3505.22 | 3280.51 | 1301.90 | 1978.60 | 0.00 | 0.00 |
Minimum of Months | 170.47 | 1385.88 | 1175.05 | 347.47 | 827.57 | 0.00 | 0.00 |
Maximum of Months | 5670.57 | 7350.85 | 5338.69 | 2193.83 | 3144.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 48.14 | 1787.29 | 263.87 | 93.87 | 170.00 | 0.00 | 0.00 |
February | 310.10 | 1348.03 | 465.60 | 215.66 | 249.93 | 0.00 | 0.00 |
March | 636.96 | 946.92 | 667.44 | 377.68 | 289.76 | 0.00 | 0.00 |
April | 1183.52 | 534.36 | 970.49 | 610.55 | 359.94 | 0.00 | 0.00 |
May | 1545.71 | 403.91 | 1190.47 | 667.62 | 522.86 | 0.00 | 0.00 |
June | 1621.30 | 389.59 | 1256.31 | 722.81 | 533.50 | 0.00 | 0.00 |
July | 1623.67 | 471.97 | 1283.98 | 764.19 | 519.80 | 0.00 | 0.00 |
August | 1275.44 | 453.00 | 1022.95 | 576.18 | 446.77 | 0.00 | 0.00 |
September | 892.46 | 474.01 | 744.02 | 384.83 | 359.19 | 0.00 | 0.00 |
October | 475.28 | 497.24 | 429.05 | 164.60 | 264.45 | 0.00 | 0.00 |
November | 174.13 | 842.28 | 257.19 | 79.94 | 177.26 | 0.00 | 0.00 |
December | 17.14 | 1678.34 | 204.66 | 53.45 | 151.21 | 0.00 | 0.00 |
Annual Sum or Average | 819.50 | 817.40 | 730.99 | 393.45 | 337.55 | 0.00 | 0.00 |
Minimum of Months | 17.14 | 389.59 | 204.66 | 53.45 | 151.21 | 0.00 | 0.00 |
Maximum of Months | 1623.67 | 1787.29 | 1283.98 | 764.19 | 533.50 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.169834E+09 | 0.529122E+10 | 0.951573E+09 | 0.342353E+09 | 0.609220E+09 | 0.00 | 0.00 |
February | 0.604384E+09 | 0.375087E+10 | 0.137943E+10 | 0.541907E+09 | 0.837525E+09 | 0.00 | 0.00 |
March | 0.121660E+10 | 0.312441E+10 | 0.199126E+10 | 0.885448E+09 | 0.110581E+10 | 0.00 | 0.00 |
April | 0.203931E+10 | 0.178759E+10 | 0.246565E+10 | 0.108204E+10 | 0.138361E+10 | 0.00 | 0.00 |
May | 0.321461E+10 | 0.117394E+10 | 0.319738E+10 | 0.132127E+10 | 0.187611E+10 | 0.00 | 0.00 |
June | 0.328293E+10 | 0.870202E+09 | 0.305235E+10 | 0.115081E+10 | 0.190154E+10 | 0.00 | 0.00 |
July | 0.366865E+10 | 0.938839E+09 | 0.331113E+10 | 0.134562E+10 | 0.196552E+10 | 0.00 | 0.00 |
August | 0.283344E+10 | 0.110571E+10 | 0.268280E+10 | 0.104392E+10 | 0.163888E+10 | 0.00 | 0.00 |
September | 0.178557E+10 | 0.148265E+10 | 0.203138E+10 | 0.777853E+09 | 0.125352E+10 | 0.00 | 0.00 |
October | 0.859655E+09 | 0.196109E+10 | 0.134689E+10 | 0.455546E+09 | 0.891342E+09 | 0.00 | 0.00 |
November | 0.260999E+09 | 0.288214E+10 | 0.805943E+09 | 0.228071E+09 | 0.577872E+09 | 0.00 | 0.00 |
December | 72319606.04 | 0.512677E+10 | 0.729161E+09 | 0.212513E+09 | 0.516648E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.200083E+11 | 0.294954E+11 | 0.239449E+11 | 0.938735E+10 | 0.145576E+11 | 0.00 | 0.00 |
Minimum of Months | 72319606.04 | 0.870202E+09 | 0.729161E+09 | 0.212513E+09 | 0.516648E+09 | 0.00 | 0.00 |
Maximum of Months | 0.366865E+10 | 0.529122E+10 | 0.331113E+10 | 0.134562E+10 | 0.196552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.972658E+09 | 0.196885E+11 | 0.411297E+10 | 0.149930E+10 | 0.261367E+10 | 0.00 | 0.00 |
February | 0.299285E+10 | 0.139058E+11 | 0.596568E+10 | 0.237323E+10 | 0.359246E+10 | 0.00 | 0.00 |
March | 0.574057E+10 | 0.115002E+11 | 0.861779E+10 | 0.387772E+10 | 0.474007E+10 | 0.00 | 0.00 |
April | 0.906534E+10 | 0.670689E+10 | 0.106675E+11 | 0.473741E+10 | 0.593008E+10 | 0.00 | 0.00 |
May | 0.135119E+11 | 0.470169E+10 | 0.138131E+11 | 0.577614E+10 | 0.803693E+10 | 0.00 | 0.00 |
June | 0.135189E+11 | 0.359219E+10 | 0.131630E+11 | 0.501747E+10 | 0.814554E+10 | 0.00 | 0.00 |
July | 0.151880E+11 | 0.382502E+10 | 0.142992E+11 | 0.587595E+10 | 0.842320E+10 | 0.00 | 0.00 |
August | 0.117292E+11 | 0.452314E+10 | 0.115952E+11 | 0.456864E+10 | 0.702656E+10 | 0.00 | 0.00 |
September | 0.756776E+10 | 0.576134E+10 | 0.878047E+10 | 0.340644E+10 | 0.537403E+10 | 0.00 | 0.00 |
October | 0.401890E+10 | 0.704357E+10 | 0.581560E+10 | 0.199502E+10 | 0.382058E+10 | 0.00 | 0.00 |
November | 0.138444E+10 | 0.103801E+11 | 0.347639E+10 | 0.998811E+09 | 0.247758E+10 | 0.00 | 0.00 |
December | 0.456582E+09 | 0.189121E+11 | 0.314724E+10 | 0.930677E+09 | 0.221656E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.861471E+11 | 0.110541E+12 | 0.103454E+12 | 0.410568E+11 | 0.623973E+11 | 0.00 | 0.00 |
Minimum of Months | 0.456582E+09 | 0.359219E+10 | 0.314724E+10 | 0.930677E+09 | 0.221656E+10 | 0.00 | 0.00 |
Maximum of Months | 0.151880E+11 | 0.196885E+11 | 0.142992E+11 | 0.587595E+10 | 0.842320E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.128938E+09 | 0.478707E+10 | 0.706745E+09 | 0.251420E+09 | 0.455325E+09 | 0.00 | 0.00 |
February | 0.750201E+09 | 0.326115E+10 | 0.112637E+10 | 0.521732E+09 | 0.604639E+09 | 0.00 | 0.00 |
March | 0.170604E+10 | 0.253623E+10 | 0.178768E+10 | 0.101158E+10 | 0.776105E+09 | 0.00 | 0.00 |
April | 0.306768E+10 | 0.138506E+10 | 0.251552E+10 | 0.158256E+10 | 0.932962E+09 | 0.00 | 0.00 |
May | 0.414004E+10 | 0.108184E+10 | 0.318856E+10 | 0.178814E+10 | 0.140042E+10 | 0.00 | 0.00 |
June | 0.420240E+10 | 0.100982E+10 | 0.325636E+10 | 0.187352E+10 | 0.138284E+10 | 0.00 | 0.00 |
July | 0.434883E+10 | 0.126412E+10 | 0.343902E+10 | 0.204680E+10 | 0.139222E+10 | 0.00 | 0.00 |
August | 0.341615E+10 | 0.121331E+10 | 0.273987E+10 | 0.154325E+10 | 0.119662E+10 | 0.00 | 0.00 |
September | 0.231327E+10 | 0.122864E+10 | 0.192851E+10 | 0.997484E+09 | 0.931024E+09 | 0.00 | 0.00 |
October | 0.127300E+10 | 0.133181E+10 | 0.114915E+10 | 0.440861E+09 | 0.708293E+09 | 0.00 | 0.00 |
November | 0.451341E+09 | 0.218319E+10 | 0.666639E+09 | 0.207193E+09 | 0.459446E+09 | 0.00 | 0.00 |
December | 45904496.51 | 0.449527E+10 | 0.548160E+09 | 0.143161E+09 | 0.404998E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.258438E+11 | 0.257775E+11 | 0.230526E+11 | 0.124077E+11 | 0.106449E+11 | 0.00 | 0.00 |
Minimum of Months | 45904496.51 | 0.100982E+10 | 0.548160E+09 | 0.143161E+09 | 0.404998E+09 | 0.00 | 0.00 |
Maximum of Months | 0.434883E+10 | 0.478707E+10 | 0.343902E+10 | 0.204680E+10 | 0.140042E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.112756E+10 | -0.103720E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -90358374.4 | 59.95 | 0.00 | 0.00 |
February | 0.105553E+10 | -974108832.7 | 0.00 | 0.00 | 672.00 | 0.00 | -81419989.3 | 59.95 | 0.00 | 0.00 |
March | 0.122362E+10 | -0.113414E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -89481386.2 | 59.95 | 0.00 | 0.00 |
April | 0.110636E+10 | -0.102243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -83930308.6 | 59.95 | 0.00 | 0.00 |
May | 0.108904E+10 | -0.101101E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -78027611.8 | 59.95 | 0.00 | 0.00 |
June | 0.102111E+10 | -948346126.0 | 0.00 | 0.00 | 720.00 | 0.00 | -72761594.8 | 59.95 | 0.00 | 0.00 |
July | 0.942044E+09 | -869180311.2 | 0.00 | 0.00 | 744.00 | 0.00 | -72863879.9 | 59.95 | 0.00 | 0.00 |
August | 0.981212E+09 | -907200411.7 | 0.00 | 0.00 | 744.00 | 0.00 | -74011768.4 | 59.95 | 0.00 | 0.00 |
September | 0.922408E+09 | -847581036.0 | 0.00 | 0.00 | 720.00 | 0.00 | -74826528.2 | 59.95 | 0.00 | 0.00 |
October | 0.967308E+09 | -882041068.5 | 0.00 | 0.00 | 744.00 | 0.00 | -85266577.2 | 59.95 | 0.00 | 0.00 |
November | 0.982783E+09 | -895942110.0 | 0.00 | 0.00 | 720.00 | 0.00 | -86840571.1 | 59.95 | 0.00 | 0.00 |
December | 0.107896E+10 | -988674445.4 | 0.00 | 0.00 | 744.00 | 0.00 | -90288688.6 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.124979E+11 | -0.115179E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -980077278.5 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.922408E+09 | -0.113414E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -90358374.4 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.122362E+10 | -847581036.0 | 0.00 | 0.00 | 744.00 | 0.00 | -72761594.8 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174907E+11 | 24918.64 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124284E+11 | 24918.64 | 01-FEB-00:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100335E+11 | 24918.64 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325038E+10 | 24918.64 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265909E+09 | 24918.64 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27043663.38 | 14239.28 | 29-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153645E+10 | 24918.64 | 03-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.652317E+10 | 24918.64 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155679E+11 | 24918.64 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.671235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174907E+11 | 24918.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.736473E+11 | 102674.93 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.486510E+11 | 102674.93 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.312119E+11 | 102674.93 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.777728E+10 | 102674.93 | 03-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199029E+09 | 89295.04 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.387159E+10 | 97280.41 | 30-OCT-03:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252239E+11 | 102674.93 | 07-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.657067E+11 | 102674.93 | 01-DEC-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.736473E+11 | 102674.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.325945E+12 | 274864.74 | 04-JAN-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219463E+12 | 243028.95 | 12-FEB-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132371E+12 | 186393.96 | 15-MAR-04:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.247882E+11 | 91253.45 | 04-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216617E+09 | 18303.34 | 01-MAY-03:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.608580E+10 | 60981.30 | 30-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103511E+12 | 149772.03 | 25-NOV-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300828E+12 | 246036.60 | 24-DEC-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111321E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.325945E+12 | 274864.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1288665.19 | 1288665.19 | 463.92 | 13-APR-16:00 | 463.92 | 0.00 |
May | 0.00 | 0.00 | 0.224534E+10 | 0.198744E+10 | 24320.17 | 26-MAY-05:02 | 16497.70 | 0.00 |
June | 0.00 | 0.00 | 0.553179E+10 | 0.436988E+10 | 29305.77 | 30-JUN-05:01 | 16581.15 | 0.00 |
July | 0.00 | 0.00 | 0.863083E+10 | 0.643906E+10 | 27015.71 | 05-JUL-05:51 | 11844.63 | 0.00 |
August | 0.00 | 0.00 | 0.617319E+10 | 0.449052E+10 | 25707.39 | 09-AUG-05:01 | 12876.20 | 0.00 |
September | 0.00 | 0.00 | 0.831521E+09 | 0.715623E+09 | 24783.29 | 01-SEP-05:02 | 11394.70 | 0.00 |
October | 0.00 | 0.00 | 35233998.22 | 35063298.14 | 3368.30 | 19-OCT-15:00 | 3368.30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234492E+11 | 0.180389E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.863083E+10 | 0.643906E+10 | 29305.77 | 16581.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.497388E+10 | 0.469572E+10 | 113361.41 | 26-MAY-17:10 | 95354.93 | 0.00 |
June | 0.00 | 0.00 | 0.144796E+11 | 0.120850E+11 | 122175.05 | 19-JUN-17:20 | 79375.02 | 0.00 |
July | 0.00 | 0.00 | 0.244997E+11 | 0.200051E+11 | 127992.09 | 04-JUL-00:01 | 53481.57 | 0.00 |
August | 0.00 | 0.00 | 0.124635E+11 | 0.101922E+11 | 121218.88 | 07-AUG-17:10 | 81517.89 | 0.00 |
September | 0.00 | 0.00 | 0.123931E+10 | 0.110479E+10 | 111517.32 | 01-SEP-18:01 | 81235.69 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.576560E+11 | 0.480828E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.244997E+11 | 0.200051E+11 | 127992.09 | 95354.93 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.406097E+11 | 0.55 | 15195.98 | 01-JAN-00:01 | 0.55 |
February | 0.346233E+11 | 0.51 | 15195.98 | 01-FEB-00:02 | 0.55 |
March | 0.337837E+11 | 0.45 | 15195.98 | 01-MAR-00:10 | 0.55 |
April | 0.136879E+11 | 0.19 | 15195.98 | 01-APR-00:10 | 0.55 |
May | 0.481105E+09 | 0.01 | 15195.98 | 01-MAY-00:10 | 0.54 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.947363E+10 | 0.13 | 15195.98 | 06-OCT-02:30 | 0.55 |
November | 0.325249E+11 | 0.45 | 15195.98 | 01-NOV-00:10 | 0.55 |
December | 0.406462E+11 | 0.55 | 15195.98 | 01-DEC-00:03 | 0.55 |
Annual Sum or Average | 0.205831E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406462E+11 | 0.55 | 15195.98 | 0.55 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.301292E+10 | 1.22 | 2377.42 | 07-JAN-11:40 | 1.43 |
February | 0.262986E+10 | 1.17 | 2377.42 | 01-FEB-13:10 | 1.43 |
March | 0.287367E+10 | 1.04 | 2377.42 | 02-MAR-10:10 | 1.43 |
April | 0.247288E+10 | 0.73 | 2377.42 | 01-APR-06:10 | 1.43 |
May | 0.246901E+10 | 0.56 | 2377.42 | 03-MAY-12:00 | 1.42 |
June | 0.247914E+10 | 0.58 | 2377.42 | 01-JUN-15:20 | 1.42 |
July | 0.242105E+10 | 0.56 | 2377.42 | 05-JUL-08:20 | 1.40 |
August | 0.259303E+10 | 0.58 | 2377.42 | 05-AUG-09:10 | 1.41 |
September | 0.235947E+10 | 0.54 | 2377.42 | 02-SEP-11:50 | 1.41 |
October | 0.239938E+10 | 0.56 | 2377.42 | 05-OCT-07:00 | 1.42 |
November | 0.250363E+10 | 0.92 | 2377.42 | 04-NOV-08:20 | 1.43 |
December | 0.296258E+10 | 1.21 | 2377.42 | 01-DEC-12:00 | 1.43 |
Annual Sum or Average | 0.311766E+11 | 0.80 | |||
Minimum of Months | 0.235947E+10 | 0.54 | 2377.42 | 1.40 | |
Maximum of Months | 0.301292E+10 | 1.22 | 2377.42 | 1.43 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149384E+11 | 1.24 | 9859.10 | 06-JAN-08:00 | 1.39 |
February | 0.127140E+11 | 1.24 | 9859.10 | 04-FEB-10:20 | 1.38 |
March | 0.131980E+11 | 1.17 | 9859.10 | 01-MAR-07:10 | 1.38 |
April | 0.105706E+11 | 0.84 | 9859.10 | 03-APR-06:20 | 1.38 |
May | 0.103310E+11 | 0.56 | 9859.10 | 04-MAY-13:50 | 1.38 |
June | 0.107992E+11 | 0.63 | 9859.10 | 01-JUN-10:30 | 1.37 |
July | 0.110074E+11 | 0.65 | 9859.10 | 31-JUL-07:30 | 1.36 |
August | 0.111550E+11 | 0.61 | 9859.10 | 02-AUG-14:50 | 1.37 |
September | 0.980379E+10 | 0.53 | 9859.10 | 01-SEP-07:20 | 1.36 |
October | 0.101909E+11 | 0.74 | 9859.10 | 06-OCT-06:10 | 1.38 |
November | 0.117491E+11 | 1.17 | 9859.10 | 28-NOV-14:10 | 1.38 |
December | 0.145713E+11 | 1.24 | 9859.10 | 01-DEC-17:30 | 1.39 |
Annual Sum or Average | 0.141029E+12 | 0.88 | |||
Minimum of Months | 0.980379E+10 | 0.53 | 9859.10 | 1.36 | |
Maximum of Months | 0.149384E+11 | 1.24 | 9859.10 | 1.39 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.301292E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.262986E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.287367E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.247321E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.301458E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.382180E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.446357E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.404509E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.256039E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.240838E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.250363E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.296258E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.367697E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.240838E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.446357E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.149384E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.127140E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.131980E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.105706E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.115814E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.143990E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.169693E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.141710E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.101032E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.101909E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.117491E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145713E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.155156E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.101032E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.169693E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.301292E+10 | 0.00 | 0.174907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262986E+10 | 0.00 | 0.124284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.287367E+10 | 0.00 | 0.100335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.247288E+10 | 1288665.19 | 0.325038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.246901E+10 | 0.224534E+10 | 0.265909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.247914E+10 | 0.553179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.242105E+10 | 0.863083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.259303E+10 | 0.617319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.235947E+10 | 0.831521E+09 | 27043663.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239938E+10 | 35233998.22 | 0.153645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250363E+10 | 0.00 | 0.652317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296258E+10 | 0.00 | 0.155679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311766E+11 | 0.234492E+11 | 0.671235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.301292E+10 | 0.863083E+10 | 0.174907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149384E+11 | 0.00 | 0.736473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127140E+11 | 0.00 | 0.486510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131980E+11 | 0.00 | 0.312119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105706E+11 | 0.00 | 0.777728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103310E+11 | 0.497388E+10 | 0.199029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107992E+11 | 0.144796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110074E+11 | 0.244997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111550E+11 | 0.124635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.980379E+10 | 0.123931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101909E+11 | 0.00 | 0.387159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117491E+11 | 0.00 | 0.252239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145713E+11 | 0.00 | 0.657067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141029E+12 | 0.576560E+11 | 0.256289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.980379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149384E+11 | 0.244997E+11 | 0.736473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.301292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.287367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.247288E+10 | 0.00 | 0.00 | 0.00 | 337973.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.246901E+10 | 0.00 | 0.00 | 0.00 | 0.545579E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.247914E+10 | 0.00 | 0.00 | 0.00 | 0.134266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.242105E+10 | 0.00 | 0.00 | 0.00 | 0.204252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.259303E+10 | 0.00 | 0.00 | 0.00 | 0.145207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.235947E+10 | 0.00 | 0.00 | 0.00 | 0.200920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239938E+10 | 0.00 | 0.00 | 0.00 | 8995902.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311766E+11 | 0.00 | 0.00 | 0.00 | 0.559307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.301292E+10 | 0.00 | 0.00 | 0.00 | 0.204252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103310E+11 | 0.00 | 0.00 | 0.00 | 0.125047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107992E+11 | 0.00 | 0.00 | 0.00 | 0.359975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110074E+11 | 0.00 | 0.00 | 0.00 | 0.596194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111550E+11 | 0.00 | 0.00 | 0.00 | 0.301605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.980379E+10 | 0.00 | 0.00 | 0.00 | 0.299454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141029E+12 | 0.00 | 0.00 | 0.00 | 0.141277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.980379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149384E+11 | 0.00 | 0.00 | 0.00 | 0.596194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424606E+10 | 0.00 | 0.00 | 0.12 |
February | 35075491.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320479E+10 | 0.00 | 0.00 | 0.13 |
March | 0.111761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304091E+10 | 0.00 | 0.00 | 0.13 |
April | 0.635648E+09 | 0.00 | 0.00 | 238267.04 | 0.00 | 0.113719E+10 | 0.487588E+09 | 0.00 | 0.19 |
May | 0.307569E+09 | 74275430.31 | 0.00 | 3418025.38 | 0.00 | 53275342.25 | 0.288739E+10 | 0.00 | 0.59 |
June | 31778770.09 | 0.482646E+09 | 0.00 | 5285130.49 | 0.00 | 0.00 | 0.316655E+10 | 0.00 | 0.92 |
July | 11036047.04 | 0.884063E+09 | 0.00 | 7746958.82 | 589004.05 | 0.00 | 0.234211E+10 | 0.00 | 0.84 |
August | 46541368.97 | 0.454358E+09 | 0.00 | 7375709.38 | 66886.10 | 0.00 | 0.368296E+10 | 0.00 | 1.04 |
September | 0.253450E+09 | 17675629.40 | 0.00 | 4253424.17 | 0.00 | 0.00 | 0.419219E+10 | 0.00 | 0.67 |
October | 0.868597E+09 | 0.00 | 0.00 | 437948.48 | 0.00 | 0.706670E+09 | 0.766808E+09 | 0.00 | 0.21 |
November | 0.196207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215995E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392309E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.249766E+10 | 0.191302E+10 | 0.00 | 28755463.75 | 655890.15 | 0.184719E+11 | 0.175256E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.868597E+09 | 0.884063E+09 | 0.00 | 7746958.82 | 589004.05 | 0.424606E+10 | 0.419219E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.458476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141245E+11 | 0.00 | 0.00 | 0.17 |
February | 0.186997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892044E+10 | 0.00 | 0.00 | 0.17 |
March | 0.431854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590490E+10 | 0.00 | 0.00 | 0.19 |
April | 0.594644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585817E+09 | 0.00 | 0.00 | 0.18 |
May | 0.394954E+10 | 38054110.43 | 0.00 | 7322973.75 | 0.00 | 0.00 | 0.494476E+10 | 0.00 | 0.45 |
June | 0.176416E+10 | 0.910802E+09 | 0.00 | 13647710.32 | 0.00 | 0.00 | 0.101095E+11 | 0.00 | 0.84 |
July | 0.395314E+09 | 0.136438E+10 | 0.00 | 27831516.74 | 0.00 | 0.00 | 0.115594E+11 | 0.00 | 0.92 |
August | 0.126404E+10 | 0.544924E+09 | 0.00 | 20405527.47 | 0.00 | 0.00 | 0.138577E+11 | 0.00 | 0.98 |
September | 0.468366E+10 | 1861912.08 | 0.00 | 4903719.00 | 0.00 | 0.00 | 0.537678E+10 | 0.00 | 0.42 |
October | 0.620084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162793E+09 | 0.00 | 0.00 | 0.18 |
November | 0.389687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349153E+10 | 0.00 | 0.00 | 0.17 |
December | 0.366491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128599E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.351143E+11 | 0.286002E+10 | 0.00 | 74111447.28 | 0.00 | 0.460498E+11 | 0.458482E+11 | 0.00 | 0.40 |
Minimum of Months | 0.366491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.620084E+10 | 0.136438E+10 | 0.00 | 27831516.74 | 0.00 | 0.141245E+11 | 0.138577E+11 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:40
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.327132E+12 | 0.158179E+12 | 0.00 | 0.188290E+11 | 0.130992E+12 |
February | 0.457284E+12 | 0.128083E+12 | 0.00 | 0.140303E+11 | 0.919883E+11 |
March | 0.640994E+12 | 0.887524E+11 | 0.00 | 0.133761E+11 | 0.640014E+11 |
April | 0.790744E+12 | 0.577165E+11 | 0.00 | 0.866485E+10 | 0.236403E+11 |
May | 0.942652E+12 | 0.354656E+11 | 0.00 | 0.122821E+11 | 0.220094E+11 |
June | 0.979345E+12 | 0.329233E+11 | 0.00 | 0.139107E+11 | 0.372658E+11 |
July | 0.101170E+13 | 0.405923E+11 | 0.00 | 0.126386E+11 | 0.538574E+11 |
August | 0.849724E+12 | 0.374707E+11 | 0.00 | 0.182744E+11 | 0.358272E+11 |
September | 0.612518E+12 | 0.431412E+11 | 0.00 | 0.146114E+11 | 0.148968E+11 |
October | 0.319360E+12 | 0.392506E+11 | 0.00 | 0.870614E+10 | 0.169474E+11 |
November | 0.162210E+12 | 0.816226E+11 | 0.00 | 0.974456E+10 | 0.524469E+11 |
December | 0.226337E+12 | 0.155557E+12 | 0.00 | 0.171495E+11 | 0.121453E+12 |
Annual Sum or Average | 0.732000E+13 | 0.898754E+12 | 0.00 | 0.162218E+12 | 0.665326E+12 |
Minimum of Months | 0.162210E+12 | 0.329233E+11 | 0.00 | 0.866485E+10 | 0.148968E+11 |
Maximum of Months | 0.101170E+13 | 0.158179E+12 | 0.00 | 0.188290E+11 | 0.130992E+12 |