Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:19:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1688.13 | 349.14 | 349.14 |
Net Site Energy | 1688.13 | 349.14 | 349.14 |
Total Source Energy | 2587.17 | 535.08 | 535.08 |
Net Source Energy | 2587.17 | 535.08 | 535.08 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1324.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 11.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 363.53 | 1324.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1324.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 8.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 118.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 26.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 11.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1324.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 8.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 118.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 26.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 11.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 37.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 9.65 | 273.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 75.19 | 273.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 37.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 9.65 | 273.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 75.19 | 273.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 363.530 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 363.530 | 100.00 |
Total On-Site and Utility Electric Sources | 363.530 | 100.00 |
Total Electricity End Uses | 363.530 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 81.50 |
Time Setpoint Not Met During Occupied Cooling | 4.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3151.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 9.3385 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.7674 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 5.0950 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 9.3385 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.7674 | 46.45 | 2.5587 | |
Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 5.0950 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 5.0950 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:39 | 18-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 371049.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10264.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8644.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3911.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1228.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 34084.54 | 371049.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 371049.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10264.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8644.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1606.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1228.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1435.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 374.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 196.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1151.30 | 1435.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 296.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 77.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 238.11 | 296.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 296.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 77.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 238.11 | 296.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.03 |
ZONE2 FINE STORAGE DIRECT AIR | 1.74 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 5.63 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 5.63 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 219803.60 |
PSZ-OFFICE HEATING COIL | 28022.44 |
PSZ-FINE STORAGE HEATING COIL | 69508.13 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 219803.61 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.000000 | 1.03 |
PSZ-FINE STORAGE | 1.74 | 1.74 | 1.74 | 1.74 | 1.74 | 1.74 | 1.00 | 1.00 | 1.74 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.03 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.74 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.03 | 1136.20 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.74 | 1859.98 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.677313 | 19337.61 | 28022.44 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.74 | 1.74 | 1.74 | 1.15 | 43164.11 | 69508.13 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.03 | 0.513116 | 0.684153 | 19337.61 | 9668.81 | 0.800980 | 0.800980 |
PSZ-FINE STORAGE COOLING COIL | 1.74 | 0.869109 | 1.16 | 43164.11 | 21582.06 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 9.339 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 17.412 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.767 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.326 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2212.108 | 9.339 | 173.516 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2212.108 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 12073.795 | 3.767 | 174.983 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 12073.795 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3574 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3694 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.946 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1333 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5514E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.798 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.608 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3395 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.423 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.06 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
2 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
3 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
4 | 2 | 0.92894805E-09 | 0.33911764E-13 | 0.21779261E-14 | 0.0000000 |
5 | 1 | -5.2160150 | 0.41827095E-04 | -0.44821328E-04 | 0.18401191E-09 |
6 | 0 | 5.5734381 | 0.35738136 | 0.35746801 | |
7 | 4 | 0.80462617E-12 | 0.82840410E-16 | -0.20078756E-14 | 0.11271485E-15 |
8 | 3 | -0.39242815E-03 | 0.26180773E-06 | -0.56999769E-04 | 0.15438257E-12 |
9 | 2 | 1.7577325 | 0.56772723E-02 | 1.1542901 | -0.75235290E-04 |
10 | 1 | -7.1048256 | 0.14632850 | -17.186369 | 0.33689683 |
11 | 0 | 5.5924660 | 0.92974441E-01 | 16.277116 | |
12 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
13 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
14 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
15 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
16 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.9455516 | 2.9455516 | 2.9455516 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.31875017E-08 | -0.23223167E-14 | 0.11745088E-14 | -0.42051331E-16 |
55 | 6 | 0.38616340E-05 | 0.25494915E-08 | 0.31950331E-02 | -0.26802615E-04 |
56 | 5 | -0.27022284E-03 | 0.15072689E-05 | -0.22401801 | 0.19587403E-02 |
57 | 4 | 0.61670379E-02 | 0.68550054E-04 | 4.8344327 | -0.45311958E-01 |
58 | 3 | -0.54002887E-01 | 0.54467183E-03 | -38.049021 | 0.39895888 |
59 | 2 | 0.19154071 | 0.90547994E-03 | 116.53767 | -1.4186579 |
60 | 1 | -0.27632409 | 0.27557907E-03 | -143.93893 | 2.0495597 |
61 | 0 | 0.13468807 | 0.66882102E-05 | 60.838472 | |
62 | 7 | -0.77687407E-08 | 0.22327722E-15 | -0.37072247E-14 | 0.17899991E-16 |
63 | 6 | 0.20649052E-05 | 0.10720148E-08 | 0.32011002E-02 | -0.26853511E-04 |
64 | 5 | -0.12245401E-03 | 0.62775152E-06 | -0.22436262 | 0.19617821E-02 |
65 | 4 | 0.26426329E-02 | 0.28408139E-04 | 4.8401680 | -0.45367094E-01 |
66 | 3 | -0.22645990E-01 | 0.22478354E-03 | -38.081398 | 0.39931679 |
67 | 2 | 0.79613263E-01 | 0.37221057E-03 | 116.60066 | -1.4195005 |
68 | 1 | -0.11438919 | 0.11271005E-03 | -143.97600 | 2.0501690 |
69 | 0 | 0.55641142E-01 | 0.27215667E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.25659737E-14 | 0.20825084E-15 | 0.74747876E-12 | 0.12362927E-15 |
85 | 3 | -0.54038165E-04 | 0.45238042E-06 | -0.37328678E-03 | 0.14344535E-12 |
86 | 2 | 1.1198054 | 0.10013958E-01 | 1.7123825 | -0.71564441E-04 |
87 | 1 | -16.966117 | 0.26145347 | -7.1648294 | 0.32817431 |
88 | 0 | 16.285382 | 0.16754891 | 5.8918369 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.36_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.36_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.36_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.5_SHGC_0.4 | 38 | 1 | VerySmooth | 2.843 | 2.843 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | 39 | 1 | VerySmooth | 4.827 | 4.827 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.13907 | 0.13907 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 5.00274E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.614 | 0.549 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 3.833E-002 | 1.618E-004 | 2.498E-004 | 0.137 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.195 | 1.399E-004 | 8.913E-005 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 1.834 | 5.723E-004 | 3.738E-004 | 0.187 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0441E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7472E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6964E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8116E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8959E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3627E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0883E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2199E-004 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5268E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4692E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0407E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1662E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1317E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1369E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8592E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9978E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4468E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2051E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5771E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6841E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1484E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3578E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1686E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1774E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0429E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4692E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0136E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8563E-004 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5164E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4320E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8057E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6099E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0378E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2079E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 6.0984E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.2709E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.4376E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.5345E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.2462E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.2766E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1458E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.5232E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.4327E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.7782E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.8639E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.6886E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.4105E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.6374E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.4603E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.2309E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.8035E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.1737E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.3654E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.2875E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9445E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.4691E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9456E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.3643E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.0052E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.1811E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.4635E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.2914E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.7406E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.4649E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.9455E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3643E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9913.90984 | 11896.69181 | 0.85519 | 1.02623 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53623E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11026.57938 | 13231.89525 | 0.32454 | 0.38944 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 21539.98571 | 25847.98285 | 1.44852 | 1.73822 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 34872.90020 | 41847.48024 | 0.86442 | 1.03731 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 183169.67411 | 219803.60893 | 4.69154 | 5.62984 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14801.24 | 1.02623 | 1.02623 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14095.32 | 0.38944 | 0.38944 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 31671.57 | 1.73822 | 1.73822 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 49732.99 | 1.03731 | 1.03731 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02623 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.73822 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.62984 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 5.62984 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 219803.60365 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 219803.60893 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02623 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02623 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02623 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02623 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02623 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.02623 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.73822 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.73822 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.73822 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.73822 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.73822 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.73822 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.02623 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.73822 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02623 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02623 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1136.20089 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02623 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02623 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02623 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67731 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02623 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51312 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68415 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19337.61000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9668.80500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80098 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80098 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19337.61000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28022.43770 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28022.43770 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.73822 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.73822 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1859.97637 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.73822 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.73822 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.73822 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14722 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.73822 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.86911 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.15881 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 43164.11000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21582.05500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43164.11000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 69508.13471 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 69508.13471 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18540.9 | 11.71 | 11.45 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 41813.0 | 12.27 | 11.99 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2032482710 | 0.1802682626 | Pass | Pass | 0.6453331738 | 1.7624002561 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4653509728 | 0.4180251283 | Pass | Pass | 0.1535576027 | 0.3866895258 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.1977471184E-005 | 1.3556546701E-004 | Pass | Pass | 1.8667919779E-002 | 1.9615023408E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8337.08 | 820.82 | 0.00 | 86.13 | 341.29 | 9585.34 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.131 | 0.133 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.350 | 0.369 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.055 | 0.055 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.176 | 0.180 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.341 | 0.357 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.565 | 0.653 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.36_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.045 | 0.401 | 0.442 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.36_SHGC_WEST_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.045 | 0.401 | 0.442 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.36_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.045 | 0.401 | 0.442 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.36_SHGC_NORTH_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.045 | 0.401 | 0.442 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.85_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.827 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.614 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.316 | 0.469 | 0.492 | |||||||||||||||||
North Total or Average | 6.51 | 2.045 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.634 | 0.486 | 0.504 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 2.044 | 2.946 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 9.3385 | 236.88 | 2212.11 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 32.31 | 0.0000 | Y | 13.42 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 25.09 | 0.0000 | Y | 48.75 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.7674 | 3204.84 | 12073.79 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 24.81 | 0.0000 | Y | 56.22 |
Interior Lighting Total | 5.0950 | 4835.13 | 24634.88 | 118.38 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 12073.79 | 1400.56 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.29 | 2212.11 | 641.51 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Stepped | 0.10 | 2212.11 | 221.21 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 42.24 | 42.24 | 0.98 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.63 | 62.93 | 50.87 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.63 | 49.46 | 10.13 | |
Exterior Lighting Total | 5520.82 | 61.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19337.61 | 15489.04 | 3848.57 | 0.80 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43164.11 | 30261.49 | 12902.62 | 0.70 | 3.81 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18540.9 | 11.71 | 11.45 | ||||
PSZ-FINE STORAGE COOLING COIL | 41813.0 | 12.27 | 11.99 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 219803.60 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28022.44 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 69508.13 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 5.63 | 523.07 | 92.91 | 1.00 | 3.12 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1136.20 | 1107.16 | 1.00 | 1.40 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.74 | 1859.98 | 1070.05 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9913.91 | 11896.69 | 50.22 | 0.855 | 1.026 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00853 | 29.72 | 0.01536 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 21539.99 | 25847.98 | 18.55 | 1.449 | 1.738 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00938 | 31.09 | 0.01536 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 31.44 | 0.01543 | 31.09 | 0.01536 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11026.58 | 13231.90 | 55.86 | 0.325 | 0.389 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00766 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 34872.90 | 41847.48 | 30.03 | 0.864 | 1.037 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00644 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 183169.67 | 219803.61 | 68.58 | 4.692 | 5.630 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00534 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.03 | 1.03 | 0.39 | 0.39 | 1.0262 | 1.0262 | 1.0262 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.74 | 1.74 | 1.04 | 1.04 | 1.7382 | 1.7382 | 1.7382 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 219803.604 | 219803.604 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 219803.60 | 219803.60 | 5.629845 | 9.99 | 7.06 | 0.00534150 | 43.33 | 21.59 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 9.99 | 0.00534150 | 67.0304 | 219803.61 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19337.610 | 15489.039 | 1.026230 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 9668.81 | 8086.04 | 0.684153 | 25.45 | 17.00 | 0.00921097 | 12.00 | 10.84 | 0.00800000 | 30.00 | 0.01536286 | 22.80 | 14.9505 | 23.90 | 0.00852933 | 44.0607 | 9906.06 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28022.438 | 28022.438 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28022.44 | 28022.44 | 1.026231 | 16.34 | 11.57 | 0.00693605 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 9.9670 | 21.10 | 0.00766390 | 46.9965 | 11026.58 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 43164.110 | 30261.494 | 1.738220 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21582.06 | 15626.07 | 1.158813 | 28.71 | 19.32 | 0.01084805 | 12.00 | 10.84 | 0.00800000 | 31.20 | 0.01536508 | 23.13 | 36.6505 | 26.70 | 0.00938622 | 40.9959 | 21525.69 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 69508.135 | 69508.135 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 69508.13 | 69508.13 | 1.738219 | 5.35 | 4.28 | 0.00495270 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 24.4337 | 15.55 | 0.00643728 | 56.0107 | 34872.90 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 219803.604 | 219803.604 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 5.629845 | 6.46619094 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 219803.60 | 219803.60 | 1.0000 | 6.46619094 | 5.629845 | 9.99 | 7.06 | 0.00534150 | 23500.7 | 43.33 | 21.59 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 219803.60 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 9.99 | 0.00534150 | 9.99 | 0.00534150 | 67.0304 | 219803.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19337.610 | 15489.039 | 1.026230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9627 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.026231 | 1.17868388 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 9668.81 | 8086.04 | 1.0000 | 0.78578830 | 0.684153 | 25.45 | 17.00 | 0.00921097 | 49044.9 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9668.81 | 30.00 | 0.01536286 | 22.80 | 0.10228463 | 14.9505 | 23.90 | 0.00852933 | 23.90 | 0.00852933 | 44.0607 | 9906.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28022.438 | 28022.438 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.026231 | 1.17868388 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 28022.44 | 28022.44 | 1.0000 | 1.17868388 | 1.026231 | 16.34 | 11.57 | 0.00693605 | 33977.0 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28022.44 | -26.20 | 0.00036134 | -26.20 | 0.10228463 | 9.9670 | 21.05 | 0.00766390 | 21.10 | 0.00766390 | 46.9965 | 11026.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43164.110 | 30261.494 | 1.738220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0060 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.738219 | 1.99644143 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 21582.06 | 15626.07 | 1.0000 | 1.33096181 | 1.158813 | 28.71 | 19.32 | 0.01084805 | 56554.9 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21582.06 | 31.20 | 0.01536508 | 23.13 | 0.42471127 | 36.6505 | 26.70 | 0.00938622 | 26.70 | 0.00938622 | 40.9959 | 21525.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 69508.135 | 69508.135 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.738219 | 1.99644143 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 69508.13 | 69508.13 | 1.0000 | 1.99644143 | 1.738219 | 5.35 | 4.28 | 0.00495270 | 17813.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69508.13 | -26.20 | 0.00036134 | -26.20 | 0.42471127 | 24.4337 | 15.55 | 0.00643728 | 15.55 | 0.00643728 | 56.0107 | 34872.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 1.03 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.74 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2953.17 | 2820.33 | 2289.00 |
ZONE2 FINE STORAGE | 3301.83 | 3188.67 | 2902.00 |
ZONE3 BULK STORAGE | 3403.50 | 3282.50 | 3097.83 |
Facility | 3475.17 | 3329.50 | 3151.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 136.33 | 4.00 | 63.00 | 4.00 |
ZONE2 FINE STORAGE | 500.67 | 0.83 | 22.17 | 0.00 |
ZONE3 BULK STORAGE | 12.67 | 0.00 | 8.17 | 0.00 |
Facility | 610.67 | 4.83 | 81.50 | 4.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.517 | 0.270 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.467 | 0.159 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.146 | 0.000 | 0.104 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1860613.47 | 0.00 | 1860613.47 | 1451805.18 | 3312418.65 | 3225648.14 | 5676.57 | 2462.67 | 620.76 | 0.00 |
ZONE2 FINE STORAGE | 4976623.08 | 0.00 | 4976623.08 | 4405893.47 | 9382516.55 | 13393694.68 | 5725.70 | 2764.50 | 269.80 | 3.63 |
ZONE3 BULK STORAGE | 0.00 | 26672400.13 | 26672400.13 | 38108989.31 | 64781389.44 | 30805497.77 | 6720.47 | 131.33 | 1908.19 | 5100.25 |
Total Facility | 6837236.56 | 26672400.13 | 33509636.69 | 43966687.96 | 77476324.65 | 47424840.58 | 7866.61 | 3020.50 | 2636.75 | 5100.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1421 | 0.0000 | 0.1421 | 0.0748 | 0.2169 | 0.1023 | 552.57 | 2462.67 | 620.76 |
ZONE2 FINE STORAGE | 0.3794 | 0.0000 | 0.3794 | 0.1297 | 0.5090 | 0.4247 | 605.33 | 2764.50 | 266.17 |
ZONE3 BULK STORAGE | 0.0000 | 1.0143 | 1.0143 | 1.4408 | 2.4551 | 0.9768 | 2625.44 | 53.00 | 957.56 |
Total Facility | 0.5215 | 1.0143 | 1.5358 | 1.6452 | 3.1810 | 1.5038 | 2742.61 | 2942.17 | 1682.79 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2454453.43 | 0.00 | 2454453.43 | 3225648.14 | 5673.57 | 0.00 | 3086.43 | 0.00 |
PSZ-FINE STORAGE | 6565256.86 | 0.00 | 6565256.86 | 13393694.68 | 5725.20 | 0.17 | 3034.63 | 3.63 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1875 | 0.0000 | 0.1875 | 0.1023 | 549.57 | 0.00 | 3086.43 |
PSZ-FINE STORAGE | 0.5005 | 0.0000 | 0.5005 | 0.4247 | 604.83 | 0.17 | 3031.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2928.36 | 165.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2984.96 | 51.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2130 | 0.3520 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5967 | 0.8033 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 400 |
Defaulted Fields | 319 |
Fields with Defaults | 1041 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 363.53 | 1287.80 | 11-JUN-16:50 | 34084.54 | 04-AUG-14:40 |
Electricity:Building | 255.11 | 1287.80 | 01-JAN-10:30 | 21206.11 | 30-JUN-12:40 |
Electricity:Zone:ZONE1 OFFICE | 42.58 | 520.87 | 01-JAN-00:10 | 3190.10 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 254.89 | 1287.80 | 01-JAN-10:30 | 19728.80 | 07-JAN-09:10 |
InteriorLights:Electricity | 118.38 | 817.92 | 01-JAN-10:30 | 9693.63 | 07-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 13.42 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 118.38 | 817.92 | 01-JAN-10:30 | 9693.63 | 07-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 118.38 | 817.92 | 01-JAN-10:30 | 9693.63 | 07-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 13.42 | 51.00 | 01-JAN-00:10 | 1355.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 118.38 | 817.92 | 01-JAN-10:30 | 9693.63 | 07-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 163.78 | 466.95 | 01-JAN-10:30 | 14474.58 | 28-JUN-13:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 56.22 | 466.95 | 01-JAN-10:30 | 4490.00 | 02-JAN-10:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 56.22 | 466.95 | 01-JAN-10:30 | 4490.00 | 02-JAN-10:30 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 26.73 | 0.00 | 24-FEB-18:10 | 3999.16 | 04-AUG-15:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.21 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-JUL-17:20 |
Ventilation (simple):Fans:Electricity | 0.21 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-JUL-17:20 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.21 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-JUL-17:20 |
ElectricityPurchased:Facility | 363.53 | 1287.80 | 11-JUN-16:50 | 34084.54 | 04-AUG-14:40 |
ElectricityPurchased:Plant | 363.53 | 1287.80 | 11-JUN-16:50 | 34084.54 | 04-AUG-14:40 |
Cogeneration:ElectricityPurchased | 363.53 | 1287.80 | 11-JUN-16:50 | 34084.54 | 04-AUG-14:40 |
General:Cogeneration:ElectricityPurchased | 363.53 | 1287.80 | 11-JUN-16:50 | 34084.54 | 04-AUG-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 363.53 | 1287.80 | 11-JUN-16:50 | 34084.54 | 04-AUG-14:40 |
ElectricityNet:Plant | 363.53 | 1287.80 | 11-JUN-16:50 | 34084.54 | 04-AUG-14:40 |
Cogeneration:ElectricityNet | 363.53 | 1287.80 | 11-JUN-16:50 | 34084.54 | 04-AUG-14:40 |
General:Cogeneration:ElectricityNet | 363.53 | 1287.80 | 11-JUN-16:50 | 34084.54 | 04-AUG-14:40 |
Electricity:HVAC | 34.60 | 0.00 | 24-FEB-18:10 | 12371.83 | 04-AUG-15:30 |
General:Fans:Electricity | 26.52 | 0.00 | 24-FEB-18:10 | 3084.56 | 18-JAN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 8.09 | 0.00 | 01-JAN-00:10 | 10677.97 | 04-AUG-15:30 |
General:Cooling:Electricity | 8.09 | 0.00 | 01-JAN-00:10 | 10677.97 | 04-AUG-15:30 |
ExteriorLights:Electricity | 61.98 | 0.00 | 01-JAN-08:00 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.98 | 0.00 | 01-JAN-08:00 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 11.84 | 0.00 | 02-JAN-00:10 | 1796.52 | 22-FEB-12:30 |
WaterSystems:Electricity | 11.84 | 0.00 | 02-JAN-00:10 | 1796.52 | 22-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 11.84 | 0.00 | 02-JAN-00:10 | 1796.52 | 22-FEB-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1324.60 | 0.00 | 24-FEB-18:10 | 371049.32 | 18-JAN-18:00 |
NaturalGas:HVAC | 1324.60 | 0.00 | 24-FEB-18:10 | 371049.32 | 18-JAN-18:00 |
Heating:NaturalGas | 1324.60 | 0.00 | 24-FEB-18:10 | 371049.32 | 18-JAN-18:00 |
General:Heating:NaturalGas | 1324.60 | 0.00 | 24-FEB-18:10 | 371049.32 | 18-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2081.71 | 0.00 | 24-FEB-18:10 | 573440.67 | 09-DEC-06:10 |
EnergyTransfer:Building | 1021.70 | 0.00 | 24-FEB-18:10 | 287449.47 | 09-DEC-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 61.53 | 0.00 | 01-JAN-00:40 | 27709.96 | 02-FEB-07:20 |
Heating:EnergyTransfer | 984.14 | 0.00 | 24-FEB-18:10 | 287449.47 | 09-DEC-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 44.83 | 0.00 | 01-JAN-00:40 | 27709.96 | 02-FEB-07:20 |
General:Heating:EnergyTransfer | 984.14 | 0.00 | 24-FEB-18:10 | 287449.47 | 09-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 44.83 | 0.00 | 01-JAN-00:40 | 27709.96 | 02-FEB-07:20 |
Cooling:EnergyTransfer | 37.56 | 0.00 | 01-JAN-00:10 | 21472.52 | 04-AUG-15:30 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 16.70 | 0.00 | 01-JAN-00:10 | 7942.94 | 05-JUL-05:10 |
General:Cooling:EnergyTransfer | 37.56 | 0.00 | 01-JAN-00:10 | 21472.52 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 16.70 | 0.00 | 01-JAN-00:10 | 7942.94 | 05-JUL-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 164.22 | 0.00 | 01-JAN-00:40 | 48376.41 | 09-DEC-02:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 143.36 | 0.00 | 01-JAN-00:40 | 48376.41 | 09-DEC-02:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 143.36 | 0.00 | 01-JAN-00:40 | 48376.41 | 09-DEC-02:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 20.87 | 0.00 | 01-JAN-00:10 | 13686.57 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 20.87 | 0.00 | 01-JAN-00:10 | 13686.57 | 04-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 795.95 | 0.00 | 12-JAN-13:10 | 222131.59 | 09-DEC-08:30 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 795.95 | 0.00 | 12-JAN-13:10 | 222131.59 | 09-DEC-08:30 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 795.95 | 0.00 | 12-JAN-13:10 | 222131.59 | 09-DEC-08:30 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1060.01 | 0.00 | 24-FEB-18:10 | 293022.08 | 18-JAN-18:00 |
HeatingCoils:EnergyTransfer | 1025.70 | 0.00 | 24-FEB-18:10 | 293022.08 | 18-JAN-18:00 |
CoolingCoils:EnergyTransfer | 34.30 | 0.00 | 01-JAN-00:10 | 43231.93 | 04-AUG-15:40 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 44.832 | -16.697 | 0.000 | 0.000 | 10.164 | 13.417 | 29.165 | 11.487 | 0.000 | 0.412 | 0.000 | 0.000 | -9.939 | 0.000 | -26.104 | -56.737 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 143.357 | -20.866 | 0.000 | 0.000 | 26.792 | 48.748 | 0.000 | 0.000 | 0.000 | 0.576 | 0.001 | 0.000 | 0.000 | 0.000 | -69.702 | -128.904 |
ZONE3 BULK STORAGE | 795.944 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 67.471 | 56.220 | 107.344 | 126.623 | 0.000 | 15.677 | 0.000 | 0.000 | -74.224 | 0.000 | -712.745 | -382.309 |
Total Facility | 795.944 | 0.000 | 188.189 | -37.563 | 0.000 | 0.000 | 104.427 | 118.384 | 136.508 | 138.110 | 0.000 | 16.665 | 0.001 | 0.000 | -84.163 | 0.000 | -808.551 | -567.949 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-SEP-05:02 | 0.00 | 0.00 | 0.00 | -19252.93 | 0.00 | 0.00 | 89.58 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 19177.20 | 0.00 | -417.30 | 0.00 | -198.06 | 0.00 |
ZONE2 FINE STORAGE | 05-JUL-17:10 | 0.00 | 0.00 | 0.00 | -32589.20 | 0.00 | 0.00 | 0.00 | 452.77 | 0.00 | 0.00 | 0.00 | 0.00 | 32141.56 | 0.00 | -0.00 | 0.00 | -5.12 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-17:10 | 0.00 | 0.00 | 0.00 | -32589.20 | 0.00 | 0.00 | 0.00 | 1133.37 | 2519.91 | 31093.09 | 0.00 | 41.50 | 604.87 | 0.00 | 0.00 | 0.00 | -2803.52 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 11-JAN-06:32 | 0.00 | 0.00 | 29378.33 | 0.00 | 0.00 | 0.00 | 136.63 | 404.75 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -644.42 | 0.00 | -1115.08 | -28710.73 |
ZONE2 FINE STORAGE | 02-FEB-01:21 | 0.00 | 0.00 | 72775.81 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10098.83 | -62976.96 |
ZONE3 BULK STORAGE | 09-DEC-08:30 | 222132.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8470.89 | 3961.65 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8340.01 | 0.00 | -224218.36 | -10206.88 |
Total Facility | 09-DEC-06:11 | 220340.25 | 0.00 | 99644.76 | 0.00 | 0.00 | 0.00 | 1397.14 | 1385.75 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10502.01 | 0.00 | -210504.94 | -104361.50 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0262 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0262 | 0.0997 | 1.0000 | Not calculated | 0.1023 | 0.0997 | ||
PSZ-FINE STORAGE | 1.7382 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.7382 | 0.2443 | 1.0000 | Not calculated | 0.4247 | 0.2443 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0262 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0262 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0997 | ||
PSZ-FINE STORAGE | 1.7382 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.7382 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2443 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0262 | 1.0262 | 1.0262 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7382 | 1.7382 | 1.7382 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0262 | 1.0262 | 1.0262 | 1.0262 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.7382 | 1.7382 | 1.7382 | 1.7382 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0262 | 1.0262 | 1.0262 | No | 0.1023 | 0.2626 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7382 | 1.7382 | 1.7382 | No | 0.4247 | 0.4094 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0262 | 1.0262 | 1.0262 | 1.0262 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.7382 | 1.7382 | 1.7382 | 1.7382 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 81.50 |
Number of hours cooling loads not met | 4.00 |
Number of hours not met | 85.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1324.60 | 371049.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 8.09 | 10677.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 118.38 | 9693.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.98 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.21 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 26.52 | 3084.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 11.84 | 1796.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 363.53 |
Natural Gas | 0.00 | 1324.60 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1688.13 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 24.48 |
Space Heating | 0.00 |
Space Cooling | 1.67 |
Fans (All) | 5.53 |
Service Water Heating | 2.45 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 75.19 |
Subtotal | 75.19 |
Natural Gas [MJ/m2] | |
Space Heating | 273.95 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 273.95 |
Subtotal | 273.95 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.01 |
Space Heating | 78.47 |
Space Cooling | 0.48 |
Fans (All) | 1.58 |
Service Water Heating | 0.70 |
Receptacle Equipment | 8.09 |
Miscellaneous | 3.67 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8441.67 | 318.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8140.00 | 620.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8042.17 | 690.83 | 27.00 | 0.00 | 0.00 |
Min | 8042.17 | 318.33 | 0.00 | 0.00 | 0.00 |
Max | 8441.67 | 690.83 | 27.00 | 0.00 | 0.00 |
Average | 8207.94 | 543.06 | 9.00 | 0.00 | 0.00 |
Sum | 24623.83 | 1629.17 | 27.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 71587.00 | 11132.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 166532.50 | 23453.00 | 1207.50 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 166532.50 | 23453.00 | 1207.50 | 0.00 | 0.00 |
Average | 90382.17 | 11528.33 | 402.50 | 0.00 | 0.00 |
Sum | 271146.50 | 34585.00 | 1207.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7811.67 | 948.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7180.17 | 1579.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7316.83 | 1432.50 | 10.67 | 0.00 | 0.00 |
Min | 7180.17 | 948.33 | 0.00 | 0.00 | 0.00 |
Max | 7811.67 | 1579.83 | 10.67 | 0.00 | 0.00 |
Average | 7436.22 | 1320.22 | 3.56 | 0.00 | 0.00 |
Sum | 22308.67 | 3960.67 | 10.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32158.83 | 868.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 64327.50 | 18391.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 153826.33 | 36749.83 | 616.83 | 0.00 | 0.00 |
Min | 32158.83 | 868.17 | 0.00 | 0.00 | 0.00 |
Max | 153826.33 | 36749.83 | 616.83 | 0.00 | 0.00 |
Average | 83437.56 | 18669.83 | 205.61 | 0.00 | 0.00 |
Sum | 250312.67 | 56009.50 | 616.83 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:44
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.496962E+09 | 603.25 | 25-JAN-08:09 | -16.6 | -16.9 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.457107E+09 | 603.25 | 06-FEB-08:09 | -14.8 | -15.6 |
March | 2012395.52 | 223.84 | 24-MAR-14:40 | 12.97 | 6.49 | 0.537079E+09 | 643.10 | 25-MAR-15:20 | 18.53 | 10.46 |
April | 0.168256E+09 | 3075.66 | 18-APR-15:10 | 27.75 | 20.46 | 0.513017E+09 | 768.96 | 18-APR-10:00 | 27.75 | 20.46 |
May | 0.553880E+09 | 4228.94 | 31-MAY-16:00 | 28.30 | 18.78 | 0.593661E+09 | 769.01 | 31-MAY-13:39 | 28.30 | 18.78 |
June | 0.326831E+10 | 17041.02 | 29-JUN-05:02 | 17.48 | 16.35 | 0.646223E+09 | 769.05 | 26-JUN-15:39 | 17.48 | 16.35 |
July | 0.480606E+10 | 19238.92 | 01-JUL-05:02 | 15.78 | 13.80 | 0.634755E+09 | 769.04 | 03-JUL-12:09 | 27.48 | 23.67 |
August | 0.499543E+10 | 17976.07 | 12-AUG-05:02 | 15.50 | 14.53 | 0.685391E+09 | 769.05 | 02-AUG-15:50 | 15.50 | 14.53 |
September | 0.276157E+10 | 19257.91 | 09-SEP-05:02 | 13.80 | 13.12 | 0.603744E+09 | 769.03 | 12-SEP-13:09 | 21.38 | 16.08 |
October | 0.101763E+09 | 1070.48 | 14-OCT-15:50 | 6.80 | 3.42 | 0.505811E+09 | 765.06 | 20-OCT-15:50 | 21.63 | 12.83 |
November | 40538459.21 | 668.08 | 04-NOV-16:25 | 10.30 | 5.01 | 0.478834E+09 | 672.87 | 03-NOV-15:09 | 10.30 | 5.01 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.497003E+09 | 603.25 | 02-DEC-08:09 | -1.0 | -2.4 |
Annual Sum or Average | 0.166978E+11 | 0.664959E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.457107E+09 | 603.25 | -16.6 | -16.9 | ||
Maximum of Months | 0.499543E+10 | 19257.91 | 28.30 | 20.46 | 0.685391E+09 | 769.05 | 28.30 | 23.67 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60929029.38 | 2685.00 | 13-JAN-14:40 | 3.90 | 1.72 | 0.649185E+09 | 787.42 | 11-JAN-11:00 | 3.90 | 1.72 |
February | 0.267606E+09 | 4339.41 | 25-FEB-14:30 | 5.30 | 2.61 | 0.598234E+09 | 865.25 | 24-FEB-15:39 | 5.30 | 2.61 |
March | 0.837020E+09 | 5786.04 | 17-MAR-14:25 | 1.70 | -0.4 | 0.720921E+09 | 1108.69 | 25-MAR-15:20 | 18.53 | 10.46 |
April | 0.177523E+10 | 8078.49 | 03-APR-13:05 | -3.2 | -4.9 | 0.785403E+09 | 1931.14 | 18-APR-15:20 | 27.20 | 20.26 |
May | 0.134482E+10 | 4308.69 | 02-MAY-09:20 | 5.37 | 2.77 | 0.114011E+10 | 2215.10 | 31-MAY-15:30 | 29.15 | 19.25 |
June | 0.290534E+10 | 30450.49 | 29-JUN-17:12 | 29.23 | 20.38 | 0.164282E+10 | 2246.91 | 30-JUN-13:50 | 29.40 | 21.96 |
July | 0.435964E+10 | 32594.81 | 05-JUL-17:10 | 26.70 | 20.64 | 0.179588E+10 | 2246.91 | 05-JUL-14:00 | 26.70 | 20.64 |
August | 0.354185E+10 | 27807.33 | 02-AUG-17:12 | 28.53 | 22.51 | 0.192324E+10 | 2246.91 | 04-AUG-12:00 | 31.70 | 26.64 |
September | 0.273501E+10 | 22400.41 | 10-SEP-14:15 | 27.07 | 17.41 | 0.144185E+10 | 2246.87 | 09-SEP-13:00 | 27.07 | 17.41 |
October | 0.213330E+10 | 5548.84 | 23-OCT-09:20 | 2.70 | 0.39 | 0.763978E+09 | 1333.01 | 20-OCT-15:20 | 2.70 | 0.39 |
November | 0.819501E+09 | 6182.85 | 18-NOV-10:05 | 0.87 | -0.6 | 0.662984E+09 | 1159.63 | 03-NOV-14:50 | 0.87 | -0.6 |
December | 86024904.59 | 3247.13 | 02-DEC-15:10 | 6.02 | 3.34 | 0.649310E+09 | 787.42 | 30-DEC-11:09 | -1.0 | -1.8 |
Annual Sum or Average | 0.208663E+11 | 0.127739E+11 | ||||||||
Minimum of Months | 60929029.38 | 2685.00 | -3.2 | -4.9 | 0.598234E+09 | 787.42 | -1.0 | -1.8 | ||
Maximum of Months | 0.435964E+10 | 32594.81 | 29.23 | 22.51 | 0.192324E+10 | 2246.91 | 31.70 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.643983E+09 | 785.95 | 12-JAN-13:30 | 2.20 | 0.51 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.598218E+09 | 1027.40 | 24-FEB-15:30 | 8.30 | 5.75 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.773905E+09 | 1601.01 | 25-MAR-15:30 | 18.35 | 10.46 |
April | 0.00 | 0.00 | 01-APR-00:05 | -1.2 | -2.2 | 0.111665E+10 | 3777.62 | 18-APR-15:09 | 27.75 | 20.46 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.15 | 0.209458E+10 | 4454.17 | 31-MAY-15:20 | 29.43 | 19.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 | 0.361385E+10 | 6410.98 | 29-JUN-15:00 | 30.00 | 20.53 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 | 0.441046E+10 | 6525.57 | 03-JUL-15:20 | 29.63 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 | 0.457581E+10 | 7847.93 | 04-AUG-15:50 | 33.90 | 26.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 | 0.315771E+10 | 5806.28 | 08-SEP-14:50 | 30.10 | 19.14 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 | 0.112827E+10 | 2254.57 | 02-OCT-15:39 | 17.17 | 14.05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 | -0.5 | 0.776625E+09 | 1727.24 | 03-NOV-14:50 | 16.10 | 9.74 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.639139E+09 | 853.17 | 02-DEC-15:50 | 5.68 | 3.15 |
Annual Sum or Average | 0.00 | 0.235292E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.598218E+09 | 785.95 | 2.20 | 0.51 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.457581E+10 | 7847.93 | 33.90 | 26.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107878E+11 | 29378.32 | 11-JAN-06:32 | -4.4 |
February | 0.795276E+10 | 28974.38 | 02-FEB-07:05 | -36.7 |
March | 0.638991E+10 | 28724.32 | 06-MAR-06:12 | -13.9 |
April | 0.328455E+10 | 28650.81 | 03-APR-05:12 | -7.2 |
May | 0.739945E+09 | 28375.51 | 02-MAY-05:12 | 2.20 |
June | 82340148.98 | 27676.24 | 05-JUN-05:02 | 9.32 |
July | 8128219.29 | 686.73 | 25-JUL-06:07 | 17.98 |
August | 16097390.33 | 744.51 | 07-AUG-06:10 | 8.87 |
September | 0.259726E+09 | 28263.17 | 29-SEP-05:01 | 0.92 |
October | 0.210327E+10 | 28276.77 | 23-OCT-05:01 | -2.7 |
November | 0.497907E+10 | 28652.60 | 24-NOV-06:12 | -13.5 |
December | 0.822932E+10 | 28776.77 | 09-DEC-06:11 | -22.8 |
Annual Sum or Average | 0.448329E+11 | |||
Minimum of Months | 8128219.29 | 686.73 | -36.7 | |
Maximum of Months | 0.107878E+11 | 29378.32 | 17.98 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390838E+11 | 72158.37 | 29-JAN-12:42 | -21.7 |
February | 0.282910E+11 | 72775.70 | 02-FEB-01:21 | -34.1 |
March | 0.170602E+11 | 71347.49 | 06-MAR-00:02 | -16.3 |
April | 0.678233E+10 | 70440.80 | 03-APR-00:23 | -5.8 |
May | 0.710392E+09 | 47046.02 | 03-MAY-05:01 | 1.38 |
June | 0.103010E+09 | 2256.92 | 09-JUN-12:00 | 28.30 |
July | 52000043.13 | 709.89 | 06-JUL-07:00 | 19.40 |
August | 57295045.90 | 725.21 | 25-AUG-07:00 | 13.90 |
September | 0.121978E+09 | 16961.02 | 30-SEP-04:35 | -0.2 |
October | 0.322256E+10 | 66844.61 | 07-OCT-05:01 | 3.90 |
November | 0.165250E+11 | 71976.47 | 26-NOV-04:02 | -25.0 |
December | 0.313475E+11 | 72134.87 | 09-DEC-18:42 | -19.9 |
Annual Sum or Average | 0.143357E+12 | |||
Minimum of Months | 52000043.13 | 709.89 | -34.1 | |
Maximum of Months | 0.390838E+11 | 72775.70 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243126E+12 | 220833.05 | 18-JAN-18:00 | -18.3 |
February | 0.164336E+12 | 212800.37 | 01-FEB-20:57 | -28.9 |
March | 0.880699E+11 | 149788.23 | 06-MAR-08:70 | -11.8 |
April | 0.194486E+11 | 89729.49 | 02-APR-24:00 | -5.6 |
May | 0.271025E+09 | 13781.38 | 02-MAY-02:55 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.191642E+10 | 17875.56 | 24-OCT-06:00 | 2.20 |
November | 0.916735E+11 | 147630.01 | 26-NOV-04:00 | -25.0 |
December | 0.187104E+12 | 222131.59 | 09-DEC-08:30 | -22.8 |
Annual Sum or Average | 0.795945E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.243126E+12 | 222131.59 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.121174E+10 | 1355.05 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.106835E+10 | 1355.05 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.117859E+10 | 1355.05 | 01-MAR-16:19 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.108544E+10 | 1355.05 | 01-APR-08:30 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.107087E+10 | 1224.06 | 02-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.103866E+10 | 1355.05 | 05-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.100771E+10 | 1355.05 | 20-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.110104E+10 | 1355.05 | 31-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.107697E+10 | 1355.05 | 12-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.112252E+10 | 1355.05 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.117294E+10 | 1355.05 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.128172E+10 | 1355.05 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.134166E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.100771E+10 | 1224.06 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.128172E+10 | 1355.05 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.404504E+10 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.370796E+10 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.430437E+10 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.401913E+10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.417471E+10 | 3848.58 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.414879E+10 | 3848.58 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.404504E+10 | 3848.58 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.430437E+10 | 3848.58 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.401913E+10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.404504E+10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.388946E+10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.404504E+10 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.487481E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.370796E+10 | 3848.58 | 0.00 | 0.00 | |
Maximum of Months | 0.430437E+10 | 3848.58 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.484194E+10 | 4490.00 | 02-JAN-10:30 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.438610E+10 | 4490.00 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.491700E+10 | 4490.00 | 13-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.455660E+10 | 4316.39 | 01-APR-08:20 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.467696E+10 | 4142.78 | 04-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.461775E+10 | 4142.78 | 05-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.454274E+10 | 4142.78 | 06-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.481980E+10 | 4316.39 | 29-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.458768E+10 | 4316.39 | 21-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.473755E+10 | 4490.00 | 20-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.461618E+10 | 4490.00 | 04-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.491937E+10 | 4490.00 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.562197E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.438610E+10 | 4142.78 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.491937E+10 | 4490.00 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.121174E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513507E+10 |
February | 0.127628E+10 | 0.106835E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382257E+10 |
March | 0.149825E+10 | 0.117859E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360942.15 | 0.315979E+10 |
April | 0.138726E+10 | 0.108544E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25625657.25 | 0.182801E+10 |
May | 0.144276E+10 | 0.107087E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25377449.43 | 0.948433E+09 |
June | 0.144276E+10 | 0.103866E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102564E+09 | 0.604317E+09 |
July | 0.138726E+10 | 0.100771E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77954603.60 | 0.395880E+09 |
August | 0.149825E+10 | 0.110104E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113620E+09 | 0.558977E+09 |
September | 0.138726E+10 | 0.107697E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66405480.88 | 0.975639E+09 |
October | 0.138726E+10 | 0.112252E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164984E+10 |
November | 0.133177E+10 | 0.117294E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288459E+10 |
December | 0.138726E+10 | 0.128172E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414051E+10 |
Annual Sum or Average | 0.168137E+11 | 0.134166E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411908E+09 | 0.261036E+11 |
Minimum of Months | 0.127628E+10 | 0.100771E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395880E+09 |
Maximum of Months | 0.149825E+10 | 0.128172E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113620E+09 | 0.513507E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140133E+11 |
February | 0.300332E+10 | 0.370796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102511E+11 |
March | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7393387.00 | 0.797431E+10 |
April | 0.326447E+10 | 0.401913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180036E+09 | 0.422321E+10 |
May | 0.339505E+10 | 0.417471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70746388.14 | 0.201512E+10 |
June | 0.339505E+10 | 0.414879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167422E+09 | 0.170150E+10 |
July | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38840287.95 | 0.153561E+10 |
August | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58433071.99 | 0.210205E+10 |
September | 0.326447E+10 | 0.401913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44773069.00 | 0.264144E+10 |
October | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7906636.24 | 0.357989E+10 |
November | 0.313390E+10 | 0.388946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801449E+10 |
December | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116504E+11 |
Annual Sum or Average | 0.395654E+11 | 0.487481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575551E+09 | 0.697023E+11 |
Minimum of Months | 0.300332E+10 | 0.370796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153561E+10 |
Maximum of Months | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180036E+09 | 0.140133E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.484194E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961992E+11 |
February | 0.690763E+10 | 0.438610E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668438E+11 |
March | 0.810895E+10 | 0.491700E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875313E+09 | 0.452298E+11 |
April | 0.750829E+10 | 0.455660E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363845E+10 | 0.218218E+11 |
May | 0.780862E+10 | 0.467696E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209140E+10 | 0.101048E+11 |
June | 0.780862E+10 | 0.461775E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128230E+10 | 0.114694E+11 |
July | 0.750829E+10 | 0.454274E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78225849.15 | 0.134465E+11 |
August | 0.810895E+10 | 0.481980E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100225E+09 | 0.164648E+11 |
September | 0.750829E+10 | 0.458768E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393289E+09 | 0.184738E+11 |
October | 0.750829E+10 | 0.473755E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823578E+09 | 0.168257E+11 |
November | 0.720796E+10 | 0.461618E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157990E+09 | 0.466976E+11 |
December | 0.750829E+10 | 0.491937E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755070E+11 |
Annual Sum or Average | 0.910005E+11 | 0.562197E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944077E+10 | 0.439084E+12 |
Minimum of Months | 0.690763E+10 | 0.438610E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101048E+11 |
Maximum of Months | 0.810895E+10 | 0.491937E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363845E+10 | 0.961992E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1355.05 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14767.81 | 19-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 1355.05 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16757.80 | 02-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1355.05 | 01-MAR-16:19 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.27 | 19-MAR-14:00 | 10575.07 | 06-MAR-08:00 |
April | 1680.92 | 01-APR-07:10 | 1355.05 | 01-APR-08:30 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 899.66 | 18-APR-12:00 | 7928.69 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1224.06 | 02-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.04 | 31-MAY-17:00 | 5014.51 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1355.05 | 05-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1769.20 | 26-JUN-16:10 | 3551.23 | 02-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 1355.05 | 20-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.15 | 25-JUL-16:10 | 2697.01 | 24-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1355.05 | 31-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2101.59 | 04-AUG-16:10 | 3631.09 | 07-AUG-06:05 |
September | 1680.92 | 01-SEP-07:10 | 1355.05 | 12-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1685.10 | 06-SEP-16:10 | 5262.48 | 29-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 1355.05 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6034.93 | 23-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1355.05 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 10027.97 | 28-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1355.05 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13473.22 | 08-DEC-17:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1224.06 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2697.01 | |||||
Maximum of Months | 1680.92 | 1355.05 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2101.59 | 16757.80 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 24026.18 | 18-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14959.93 | 04-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.48 | 19-MAR-16:00 | 14703.13 | 06-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3401.37 | 15-APR-17:00 | 9184.84 | 25-APR-06:10 |
May | 3955.50 | 01-MAY-07:10 | 3848.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1719.36 | 05-MAY-15:10 | 3922.80 | 02-MAY-03:00 |
June | 3955.50 | 01-JUN-07:10 | 3848.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2003.94 | 11-JUN-15:00 | 3908.42 | 02-JUN-05:00 |
July | 3955.50 | 01-JUL-07:10 | 3848.58 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.36 | 25-JUL-16:00 | 2497.25 | 10-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 3848.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.45 | 04-AUG-16:20 | 2853.02 | 06-AUG-06:00 |
September | 3955.50 | 01-SEP-07:10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.61 | 06-SEP-15:40 | 3952.24 | 18-SEP-23:00 |
October | 3955.50 | 02-OCT-07:10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.50 | 20-OCT-15:10 | 6288.69 | 24-OCT-06:10 |
November | 3955.50 | 01-NOV-07:10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 13352.32 | 25-NOV-16:10 |
December | 3955.50 | 01-DEC-08:09 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 26545.12 | 09-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2497.25 | ||||
Maximum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3401.37 | 26545.12 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4490.00 | 02-JAN-10:30 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 131565.93 | 18-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 4490.00 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 92742.49 | 28-FEB-10:00 |
March | 9097.65 | 01-MAR-08:09 | 4490.00 | 13-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15844.38 | 25-MAR-15:00 | 84545.49 | 06-MAR-08:70 |
April | 9097.65 | 01-APR-07:10 | 4316.39 | 01-APR-08:20 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35843.59 | 15-APR-15:00 | 40179.00 | 02-APR-24:00 |
May | 9097.65 | 01-MAY-07:10 | 4142.78 | 04-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23341.12 | 04-MAY-14:00 | 23826.70 | 13-MAY-13:00 |
June | 9097.65 | 01-JUN-07:10 | 4142.78 | 05-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16394.76 | 11-JUN-15:00 | 24581.03 | 02-JUN-08:00 |
July | 9097.65 | 01-JUL-07:10 | 4142.78 | 06-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3725.37 | 25-JUL-16:00 | 24501.32 | 10-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 4316.39 | 29-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3224.71 | 21-AUG-13:00 | 20753.09 | 30-AUG-15:00 |
September | 9097.65 | 01-SEP-07:10 | 4316.39 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8082.25 | 06-SEP-14:00 | 25308.67 | 18-SEP-16:00 |
October | 9097.65 | 02-OCT-07:10 | 4490.00 | 20-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13940.79 | 20-OCT-15:00 | 23358.83 | 24-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 4490.00 | 04-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8346.08 | 20-NOV-10:00 | 91126.13 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 4490.00 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 157420.68 | 09-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 4142.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20753.09 | |||||
Maximum of Months | 9097.65 | 4490.00 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 35843.59 | 157420.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.43 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.71 |
March | 223.84 | 24-MAR-14:40 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.86 |
April | 3075.66 | 18-APR-15:10 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 390.67 | 0.00 |
May | 4228.94 | 31-MAY-16:00 | 1680.92 | 826.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 281.00 | 0.00 |
June | 17041.02 | 29-JUN-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.29 |
July | 19238.92 | 01-JUL-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.86 |
August | 17976.07 | 12-AUG-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.37 |
September | 19257.91 | 09-SEP-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.06 |
October | 1070.48 | 14-OCT-15:50 | 1680.92 | 916.92 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.41 |
November | 668.08 | 04-NOV-16:25 | 1075.79 | 1731.86 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.43 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19257.91 | 1680.92 | 1731.86 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.67 | 1111.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2685.00 | 13-JAN-14:40 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.98 |
February | 4339.41 | 25-FEB-14:30 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 933.54 |
March | 5786.04 | 17-MAR-14:25 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1586.72 |
April | 8078.49 | 03-APR-13:05 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1917.63 |
May | 4308.69 | 02-MAY-09:20 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1169.08 |
June | 30450.49 | 29-JUN-17:12 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.04 | 0.00 |
July | 32594.81 | 05-JUL-17:10 | 0.00 | 1811.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 |
August | 27807.33 | 02-AUG-17:12 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.05 | 0.00 |
September | 22400.41 | 10-SEP-14:15 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.52 | 0.00 |
October | 5548.84 | 23-OCT-09:20 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.12 |
November | 6182.85 | 18-NOV-10:05 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.26 |
December | 3247.13 | 02-DEC-15:10 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2685.00 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32594.81 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.05 | 1917.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 2112.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16604.45 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2641.14 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40749.75 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2641.14 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42176.00 |
April | 0.00 | 01-APR-00:05 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7659.16 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4220.85 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5493.31 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5465.27 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6349.25 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 528.23 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7861.26 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7712.93 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 1056.46 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5146.94 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1584.69 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17062.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 528.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4220.85 | |
Maximum of Months | 0.00 | 0.00 | 2641.14 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42176.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.335627E+11 | 27570.77 | 18-JAN-16:00 | 0.391689E+12 | 371049.32 | 18-JAN-17:00 |
February | 0.296503E+11 | 23474.98 | 02-FEB-11:20 | 0.269136E+12 | 328561.99 | 01-FEB-20:00 |
March | 0.321378E+11 | 23130.55 | 01-MAR-15:50 | 0.151817E+12 | 255124.76 | 06-MAR-08:09 |
April | 0.282330E+11 | 22775.29 | 01-APR-14:39 | 0.418041E+11 | 149848.63 | 02-APR-23:49 |
May | 0.278155E+11 | 22828.69 | 31-MAY-14:50 | 0.212579E+10 | 46533.66 | 02-MAY-05:10 |
June | 0.287291E+11 | 30624.64 | 30-JUN-14:39 | 88130512.46 | 6291.94 | 05-JUN-05:10 |
July | 0.294515E+11 | 31933.48 | 03-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.313517E+11 | 34084.54 | 04-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.288015E+11 | 26646.69 | 06-SEP-14:00 | 0.547638E+09 | 17922.23 | 30-SEP-06:10 |
October | 0.295228E+11 | 21973.11 | 27-OCT-12:30 | 0.115198E+11 | 50972.34 | 24-OCT-05:10 |
November | 0.307040E+11 | 27361.46 | 25-NOV-16:00 | 0.152162E+12 | 248166.67 | 25-NOV-17:00 |
December | 0.335701E+11 | 27584.37 | 09-DEC-16:00 | 0.303710E+12 | 368958.87 | 09-DEC-08:00 |
Annual Sum or Average | 0.363530E+12 | 0.132460E+13 | ||||
Minimum of Months | 0.278155E+11 | 21973.11 | 0.00 | 0.00 | ||
Maximum of Months | 0.335701E+11 | 34084.54 | 0.391689E+12 | 371049.32 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.100987E+11 | 0.702230E+10 | 0.112984E+11 | 0.00 | 0.405896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108439E+10 | 0.00 |
February | 0.916241E+10 | 0.570171E+10 | 0.103734E+11 | 0.00 | 0.340009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101273E+10 | 0.00 |
March | 0.104000E+11 | 0.542568E+10 | 0.121089E+11 | 0.00 | 0.303614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116709E+10 | 0.00 |
April | 0.966117E+10 | 0.434176E+10 | 0.112578E+11 | 0.00 | 0.188491E+10 | 0.00 | 0.00 | 39371141.69 | 0.00 | 0.00 | 0.00 | 0.104806E+10 | 0.00 |
May | 0.992255E+10 | 0.378915E+10 | 0.117000E+11 | 0.00 | 0.128492E+10 | 0.00 | 0.00 | 92178836.90 | 0.00 | 0.00 | 0.00 | 0.102673E+10 | 0.00 |
June | 0.980520E+10 | 0.337007E+10 | 0.116594E+11 | 0.00 | 0.131300E+10 | 0.00 | 0.00 | 0.162887E+10 | 0.00 | 0.00 | 0.00 | 0.952595E+09 | 0.00 |
July | 0.959550E+10 | 0.358354E+10 | 0.112984E+11 | 0.00 | 0.129290E+10 | 0.00 | 0.00 | 0.280533E+10 | 0.00 | 0.00 | 0.00 | 0.875846E+09 | 0.00 |
August | 0.102252E+11 | 0.414498E+10 | 0.121016E+11 | 0.00 | 0.140027E+10 | 0.00 | 0.00 | 0.256617E+10 | 0.00 | 0.00 | 0.00 | 0.913558E+09 | 0.00 |
September | 0.968378E+10 | 0.484525E+10 | 0.112504E+11 | 0.00 | 0.120017E+10 | 0.00 | 0.00 | 0.956153E+09 | 0.00 | 0.00 | 0.00 | 0.865705E+09 | 0.00 |
October | 0.990511E+10 | 0.594574E+10 | 0.113057E+11 | 0.00 | 0.144742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918761E+09 | 0.00 |
November | 0.967858E+10 | 0.656444E+10 | 0.108562E+11 | 0.00 | 0.266604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938726E+09 | 0.00 |
December | 0.102461E+11 | 0.724424E+10 | 0.112984E+11 | 0.00 | 0.374495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103641E+10 | 0.00 |
Annual Sum or Average | 0.118384E+12 | 0.619789E+11 | 0.136508E+12 | 0.00 | 0.267298E+11 | 0.00 | 0.00 | 0.808808E+10 | 0.00 | 0.00 | 0.00 | 0.118406E+11 | 0.00 |
Minimum of Months | 0.916241E+10 | 0.337007E+10 | 0.103734E+11 | 0.00 | 0.120017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865705E+09 | 0.00 |
Maximum of Months | 0.104000E+11 | 0.724424E+10 | 0.121089E+11 | 0.00 | 0.405896E+10 | 0.00 | 0.00 | 0.280533E+10 | 0.00 | 0.00 | 0.00 | 0.116709E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.391689E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.269136E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.151817E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.418041E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.212579E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 88130512.46 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.547638E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.115198E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.152162E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.303710E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132460E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.391689E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 9693.63 | 07-JAN-09:09 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3084.56 | 18-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 9693.63 | 08-FEB-09:09 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3060.00 | 02-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9562.64 | 13-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2687.74 | 06-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 9520.02 | 01-APR-08:30 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2437.75 | 03-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 9215.41 | 04-MAY-08:09 | 4975.14 | 01-MAY-19:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 2058.71 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 9215.41 | 05-JUN-08:09 | 4975.14 | 01-JUN-19:40 | 10035.17 | 01-JUN-07:10 | 0.00 | 3551.98 | 30-JUN-15:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 9215.41 | 06-JUL-08:09 | 4975.14 | 01-JUL-19:00 | 10035.17 | 01-JUL-07:10 | 0.00 | 3669.24 | 03-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 9389.03 | 29-AUG-08:09 | 5520.82 | 08-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 3999.16 | 04-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 9520.02 | 21-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1429.93 | 30-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 9562.64 | 20-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2128.64 | 19-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9693.63 | 04-NOV-08:09 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2652.92 | 25-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9693.63 | 01-DEC-09:09 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 3009.49 | 08-DEC-17:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9215.41 | 4975.14 | 10035.17 | 0.00 | 1429.93 | 0.00 | 0.00 | |||||
Maximum of Months | 9693.63 | 5520.82 | 10035.17 | 0.00 | 3999.16 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1768.94 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 1796.52 | 22-FEB-12:30 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 1790.38 | 01-MAR-12:39 | 0.00 |
April | 1395.88 | 18-APR-15:09 | 0.00 | 0.00 | 0.00 | 1726.72 | 01-APR-11:20 | 0.00 |
May | 1631.77 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1624.14 | 01-MAY-11:00 | 0.00 |
June | 7145.24 | 30-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1534.31 | 01-JUN-11:00 | 0.00 |
July | 8331.68 | 03-JUL-14:00 | 0.00 | 0.00 | 0.00 | 1456.52 | 01-JUL-11:00 | 0.00 |
August | 10677.97 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 1401.46 | 02-AUG-11:09 | 0.00 |
September | 5524.74 | 06-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1412.39 | 30-SEP-11:09 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 1507.08 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 1610.88 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1716.11 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1401.46 | 0.00 | ||
Maximum of Months | 10677.97 | 0.00 | 0.00 | 0.00 | 1796.52 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 27570.77 | 18-JAN-16:00 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 2727.97 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23474.98 | 02-FEB-11:20 | 9389.03 | 10035.17 | 0.00 | 0.00 | 2651.31 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23130.55 | 01-MAR-15:50 | 9389.03 | 10035.17 | 0.00 | 0.00 | 2106.15 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22775.29 | 01-APR-14:39 | 9215.41 | 10035.17 | 0.00 | 0.00 | 1987.64 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22828.69 | 31-MAY-14:50 | 8644.32 | 10035.17 | 0.00 | 0.00 | 1198.47 | 0.00 | 0.00 | 1585.87 | 0.00 |
June | 30624.64 | 30-JUN-14:39 | 8644.32 | 10035.17 | 0.00 | 0.00 | 3531.63 | 0.00 | 0.00 | 7126.31 | 0.00 |
July | 31933.48 | 03-JUL-14:00 | 8644.32 | 10035.17 | 0.00 | 0.00 | 3644.56 | 0.00 | 0.00 | 8331.68 | 0.00 |
August | 34084.54 | 04-AUG-14:39 | 8644.32 | 10035.17 | 0.00 | 0.00 | 3911.56 | 0.00 | 0.00 | 10264.89 | 0.00 |
September | 26646.69 | 06-SEP-14:00 | 8817.93 | 10035.17 | 0.00 | 0.00 | 1198.47 | 0.00 | 0.00 | 5366.77 | 0.00 |
October | 21973.11 | 27-OCT-12:30 | 9389.03 | 10035.17 | 0.00 | 0.00 | 1228.84 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27361.46 | 25-NOV-16:00 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 2523.86 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27584.37 | 09-DEC-16:00 | 8712.41 | 10035.17 | 5520.82 | 0.00 | 2745.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21973.11 | 8644.32 | 10035.17 | 0.00 | 0.00 | 1198.47 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34084.54 | 9389.03 | 10035.17 | 5520.82 | 0.00 | 3911.56 | 0.00 | 0.00 | 10264.89 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 371049.32 | 18-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 328561.99 | 01-FEB-20:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 255124.76 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 149848.63 | 02-APR-23:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 46533.66 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6291.94 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 17922.23 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 50972.34 | 24-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 248166.67 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 368958.87 | 09-DEC-08:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 371049.32 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.17 | 16.02 | 9.50 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
February | 29.33 | 16.15 | 9.67 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
March | 15.83 | 17.74 | 10.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
April | 8.00 | 19.27 | 7.33 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
May | 1.50 | 20.01 | 1.50 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.54 | 1.50 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.55 | 1.67 | 24.55 |
September | 1.00 | 20.32 | 1.00 | 20.32 | 0.33 | 20.93 | 0.33 | 21.39 |
October | 7.17 | 20.12 | 7.17 | 20.12 | 0.00 | 20.12 | 0.00 | 20.12 |
November | 14.00 | 17.53 | 7.50 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
December | 25.33 | 16.47 | 9.33 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
Annual Sum or Average | 136.33 | 16.97 | 63.00 | 17.73 | 4.00 | 17.87 | 4.00 | 18.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 | 0.00 | 16.68 |
Maximum of Months | 34.17 | 20.32 | 10.00 | 20.32 | 1.67 | 24.55 | 1.67 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.00 | 14.28 | 4.17 | 14.27 | 0.00 | 14.27 | 0.00 | 14.27 |
February | 98.17 | 14.47 | 4.33 | 14.47 | 0.00 | 14.47 | 0.00 | 14.47 |
March | 73.00 | 14.67 | 4.83 | 14.67 | 0.00 | 14.67 | 0.00 | 14.67 |
April | 28.67 | 14.83 | 2.00 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
May | 0.50 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.31 | 0.00 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
October | 7.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
November | 66.83 | 14.60 | 2.67 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
December | 111.17 | 14.49 | 4.17 | 14.49 | 0.00 | 14.49 | 0.00 | 14.49 |
Annual Sum or Average | 500.67 | 14.51 | 22.17 | 14.50 | 0.83 | 14.52 | 0.00 | 14.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.00 | 14.98 | 4.83 | 14.98 | 0.83 | 27.31 | 0.00 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.67 | 8.68 | 8.17 | 8.59 | 0.00 | 8.59 | 0.00 | 8.59 |
Annual Sum or Average | 12.67 | 8.68 | 8.17 | 8.59 | 0.00 | 8.59 | 0.00 | 8.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.67 | 8.68 | 8.17 | 8.59 | 0.00 | 8.59 | 0.00 | 8.59 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
February | 276.00 | 21.01 | 276.00 | 21.01 | 276.00 | 21.01 |
March | 324.00 | 21.05 | 324.00 | 21.05 | 324.00 | 21.05 |
April | 299.17 | 21.35 | 252.33 | 21.27 | 252.33 | 21.23 |
May | 304.00 | 22.39 | 95.50 | 22.26 | 93.50 | 22.17 |
June | 150.17 | 23.19 | 160.83 | 23.54 | 49.50 | 23.57 |
July | 50.00 | 23.90 | 280.50 | 23.90 | 47.67 | 23.91 |
August | 77.17 | 23.87 | 285.83 | 23.90 | 70.17 | 23.90 |
September | 151.83 | 22.49 | 147.00 | 22.77 | 44.67 | 22.56 |
October | 300.00 | 21.23 | 260.00 | 21.16 | 260.00 | 21.14 |
November | 288.00 | 21.09 | 271.17 | 21.08 | 271.17 | 21.07 |
December | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
Annual Sum or Average | 2820.33 | 21.56 | 2953.17 | 21.73 | 2289.00 | 21.60 |
Minimum of Months | 50.00 | 21.01 | 95.50 | 21.01 | 44.67 | 21.01 |
Maximum of Months | 324.00 | 23.90 | 324.00 | 23.90 | 324.00 | 23.91 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
February | 276.00 | 15.55 | 276.00 | 15.55 | 276.00 | 15.55 |
March | 324.00 | 15.74 | 324.00 | 15.74 | 324.00 | 15.74 |
April | 300.00 | 16.94 | 283.50 | 16.81 | 283.50 | 16.76 |
May | 311.17 | 20.06 | 195.83 | 19.80 | 195.00 | 19.68 |
June | 219.33 | 23.77 | 229.00 | 24.41 | 147.83 | 24.44 |
July | 219.17 | 26.30 | 290.00 | 26.25 | 215.00 | 26.28 |
August | 180.67 | 26.15 | 304.17 | 26.14 | 175.83 | 26.16 |
September | 170.33 | 21.07 | 211.33 | 22.27 | 96.83 | 21.83 |
October | 300.00 | 16.74 | 300.00 | 16.74 | 300.00 | 16.74 |
November | 288.00 | 15.98 | 288.00 | 15.98 | 288.00 | 15.98 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 3188.67 | 18.49 | 3301.83 | 18.80 | 2902.00 | 18.60 |
Minimum of Months | 170.33 | 15.54 | 195.83 | 15.54 | 96.83 | 15.54 |
Maximum of Months | 324.00 | 26.30 | 324.00 | 26.25 | 324.00 | 26.28 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
February | 276.00 | 10.04 | 276.00 | 10.04 | 276.00 | 10.04 |
March | 324.00 | 10.49 | 324.00 | 10.49 | 324.00 | 10.49 |
April | 300.00 | 12.88 | 299.33 | 12.87 | 299.33 | 12.87 |
May | 308.00 | 17.64 | 298.50 | 17.62 | 295.33 | 17.59 |
June | 240.17 | 23.06 | 226.83 | 23.58 | 164.00 | 23.57 |
July | 226.67 | 27.36 | 289.00 | 27.18 | 222.00 | 27.26 |
August | 215.83 | 26.80 | 294.83 | 26.69 | 202.17 | 26.79 |
September | 203.83 | 20.88 | 207.00 | 21.58 | 127.00 | 21.23 |
October | 300.00 | 13.15 | 300.00 | 13.15 | 300.00 | 13.15 |
November | 288.00 | 11.10 | 288.00 | 11.10 | 288.00 | 11.10 |
December | 300.00 | 9.96 | 300.00 | 9.96 | 300.00 | 9.96 |
Annual Sum or Average | 3282.50 | 15.35 | 3403.50 | 15.63 | 3097.83 | 15.41 |
Minimum of Months | 203.83 | 9.96 | 207.00 | 9.96 | 127.00 | 9.96 |
Maximum of Months | 324.00 | 27.36 | 324.00 | 27.18 | 324.00 | 27.26 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.156580E+09 | 39371141.69 | 12.83 | 0.106049E+09 | 50530497.96 | 0.00 | 0.59 | 18-APR-15:10 | 0.00 | 01-APR-00:05 | 5697.95 | 18-APR-15:10 | 3990.41 | 18-APR-15:10 | 1707.53 | 18-APR-15:10 | 1395.88 | 18-APR-15:10 | 0.00 | 01-APR-00:05 |
May | 0.370667E+09 | 92178836.90 | 34.33 | 0.275275E+09 | 95391978.19 | 0.00 | 0.70 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 | 6464.57 | 31-MAY-15:10 | 5298.07 | 31-MAY-15:10 | 1496.82 | 30-MAY-14:00 | 1631.77 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 0.393088E+10 | 0.921932E+09 | 192.12 | 0.283639E+10 | 0.109450E+10 | 0.00 | 1.00 | 12-JUN-05:05 | 0.00 | 01-JUN-00:10 | 22733.87 | 26-JUN-05:01 | 12410.45 | 30-JUN-05:01 | 12020.03 | 26-JUN-05:10 | 4793.70 | 26-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.649176E+10 | 0.148227E+10 | 263.95 | 0.442501E+10 | 0.206676E+10 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 22399.85 | 27-JUL-05:02 | 12717.19 | 01-JUL-05:02 | 12359.16 | 27-JUL-05:03 | 4744.79 | 27-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.667067E+10 | 0.153876E+10 | 282.55 | 0.456240E+10 | 0.210827E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 24458.65 | 04-AUG-05:01 | 12584.35 | 09-AUG-05:03 | 15297.83 | 04-AUG-05:08 | 5017.22 | 04-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.243401E+10 | 0.585319E+09 | 138.84 | 0.206644E+10 | 0.367574E+09 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 20867.30 | 11-SEP-05:01 | 14228.27 | 18-SEP-05:03 | 9303.12 | 12-SEP-05:02 | 4496.71 | 11-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.200546E+11 | 0.465983E+10 | 924.63 | 0.142716E+11 | 0.578302E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.667067E+10 | 0.153876E+10 | 282.55 | 0.456240E+10 | 0.210827E+10 | 0.00 | 1.00 | 0.00 | 24458.65 | 14228.27 | 15297.83 | 5017.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.291061E+10 | 0.706942E+09 | 78.63 | 0.189933E+10 | 0.101128E+10 | 0.00 | 1.00 | 25-JUN-13:30 | 0.00 | 01-JUN-00:10 | 48505.20 | 27-JUN-18:35 | 33226.11 | 28-JUN-18:45 | 16687.31 | 27-JUN-18:35 | 10767.22 | 27-JUN-18:35 | 0.00 | 01-JUN-00:10 |
July | 0.561430E+10 | 0.132307E+10 | 157.99 | 0.343691E+10 | 0.217739E+10 | 0.00 | 1.00 | 01-JUL-17:12 | 0.00 | 01-JUL-00:10 | 52781.86 | 03-JUL-19:55 | 35415.85 | 05-JUL-17:10 | 26890.05 | 03-JUL-19:55 | 11266.65 | 03-JUL-19:55 | 0.00 | 01-JUL-00:10 |
August | 0.428515E+10 | 0.102741E+10 | 133.18 | 0.260957E+10 | 0.167558E+10 | 0.00 | 1.00 | 01-AUG-17:15 | 0.00 | 01-AUG-00:10 | 52501.89 | 04-AUG-17:20 | 33208.62 | 05-AUG-17:23 | 27121.36 | 04-AUG-17:30 | 11207.69 | 04-AUG-17:20 | 0.00 | 01-AUG-00:10 |
September | 0.143973E+10 | 0.370833E+09 | 62.50 | 0.112809E+10 | 0.311642E+09 | 0.00 | 1.00 | 10-SEP-14:15 | 0.00 | 01-SEP-00:10 | 45019.43 | 10-SEP-14:15 | 36572.69 | 10-SEP-14:15 | 8446.73 | 10-SEP-14:15 | 10223.04 | 10-SEP-14:15 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.142498E+11 | 0.342825E+10 | 432.29 | 0.907390E+10 | 0.517590E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.561430E+10 | 0.132307E+10 | 157.99 | 0.343691E+10 | 0.217739E+10 | 0.00 | 1.00 | 0.00 | 52781.86 | 36572.69 | 27121.36 | 11266.65 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.04 | 28.82 | 42.22 | 34.98 | 223.54 | 0.00 | 0.00 | 0.00 |
February | 103.33 | 50.69 | 52.65 | 72.68 | 172.88 | 0.00 | 0.00 | 0.00 |
March | 124.08 | 46.22 | 77.85 | 105.69 | 103.93 | 0.00 | 0.00 | 0.00 |
April | 180.88 | 89.38 | 91.49 | 199.65 | 67.69 | 0.00 | 0.00 | 0.00 |
May | 181.37 | 72.46 | 108.90 | 219.92 | 40.18 | 0.00 | 0.00 | 0.00 |
June | 212.49 | 91.91 | 120.57 | 268.99 | 36.26 | 0.00 | 0.00 | 0.00 |
July | 228.63 | 108.65 | 119.98 | 291.93 | 37.91 | 0.00 | 0.00 | 0.00 |
August | 199.26 | 91.13 | 108.13 | 255.47 | 44.21 | 0.00 | 0.00 | 0.00 |
September | 161.69 | 76.66 | 85.04 | 192.80 | 64.81 | 0.00 | 0.00 | 0.00 |
October | 113.17 | 50.45 | 62.73 | 117.59 | 77.21 | 0.00 | 0.00 | 0.00 |
November | 67.70 | 25.15 | 42.55 | 47.97 | 128.67 | 0.00 | 0.00 | 0.00 |
December | 52.29 | 24.87 | 27.42 | 31.12 | 199.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.48 | 63.05 | 78.43 | 153.63 | 99.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.29 | 24.87 | 27.42 | 31.12 | 36.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.63 | 108.65 | 120.57 | 291.93 | 223.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.04 | 28.82 | 42.22 | 34.98 | 223.54 | 0.00 | 0.00 | 0.00 |
February | 103.33 | 50.69 | 52.65 | 72.68 | 172.88 | 0.00 | 0.00 | 0.00 |
March | 124.08 | 46.22 | 77.85 | 105.69 | 103.93 | 0.00 | 0.00 | 0.00 |
April | 180.88 | 89.38 | 91.49 | 199.65 | 67.69 | 0.00 | 0.00 | 0.00 |
May | 181.37 | 72.46 | 108.90 | 219.92 | 40.18 | 0.00 | 0.00 | 0.00 |
June | 212.49 | 91.91 | 120.57 | 268.99 | 36.26 | 0.00 | 0.00 | 0.00 |
July | 228.63 | 108.65 | 119.98 | 291.93 | 37.91 | 0.00 | 0.00 | 0.00 |
August | 199.26 | 91.13 | 108.13 | 255.47 | 44.21 | 0.00 | 0.00 | 0.00 |
September | 161.69 | 76.66 | 85.04 | 192.80 | 64.81 | 0.00 | 0.00 | 0.00 |
October | 113.17 | 50.45 | 62.73 | 117.59 | 77.21 | 0.00 | 0.00 | 0.00 |
November | 67.70 | 25.15 | 42.55 | 47.97 | 128.67 | 0.00 | 0.00 | 0.00 |
December | 52.29 | 24.87 | 27.42 | 31.12 | 199.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.48 | 63.05 | 78.43 | 153.63 | 99.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.29 | 24.87 | 27.42 | 31.12 | 36.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.63 | 108.65 | 120.57 | 291.93 | 223.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.44 | 0.00 | 19.44 | 0.20 | 142.42 | 0.00 | 0.00 | 0.00 |
February | 24.65 | 0.00 | 24.65 | 2.42 | 110.72 | 0.00 | 0.00 | 0.00 |
March | 36.95 | 0.00 | 36.95 | 16.19 | 64.50 | 0.00 | 0.00 | 0.00 |
April | 42.75 | 0.29 | 42.45 | 30.54 | 40.26 | 0.00 | 0.00 | 0.00 |
May | 55.70 | 2.16 | 53.54 | 58.27 | 22.29 | 0.00 | 0.00 | 0.00 |
June | 64.95 | 5.87 | 59.09 | 75.77 | 20.08 | 0.00 | 0.00 | 0.00 |
July | 60.94 | 4.09 | 56.85 | 70.62 | 21.14 | 0.00 | 0.00 | 0.00 |
August | 51.22 | 1.07 | 50.15 | 58.75 | 24.86 | 0.00 | 0.00 | 0.00 |
September | 39.17 | 0.03 | 39.14 | 36.74 | 38.44 | 0.00 | 0.00 | 0.00 |
October | 29.10 | 0.00 | 29.10 | 18.74 | 46.63 | 0.00 | 0.00 | 0.00 |
November | 20.35 | 0.00 | 20.35 | 5.31 | 79.54 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.10 | 123.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.27 | 1.13 | 37.14 | 31.31 | 61.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.10 | 20.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.95 | 5.87 | 59.09 | 75.77 | 142.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.44 | 0.00 | 19.44 | 0.20 | 142.42 | 0.00 | 0.00 | 0.00 |
February | 24.65 | 0.00 | 24.65 | 2.42 | 110.72 | 0.00 | 0.00 | 0.00 |
March | 36.95 | 0.00 | 36.95 | 16.19 | 64.50 | 0.00 | 0.00 | 0.00 |
April | 42.74 | 0.29 | 42.45 | 30.54 | 40.26 | 0.00 | 0.00 | 0.00 |
May | 55.70 | 2.16 | 53.54 | 58.27 | 22.29 | 0.00 | 0.00 | 0.00 |
June | 64.95 | 5.87 | 59.09 | 75.76 | 20.08 | 0.00 | 0.00 | 0.00 |
July | 60.93 | 4.09 | 56.85 | 70.62 | 21.14 | 0.00 | 0.00 | 0.00 |
August | 51.22 | 1.07 | 50.15 | 58.75 | 24.86 | 0.00 | 0.00 | 0.00 |
September | 39.17 | 0.03 | 39.14 | 36.74 | 38.44 | 0.00 | 0.00 | 0.00 |
October | 29.09 | 0.00 | 29.09 | 18.74 | 46.63 | 0.00 | 0.00 | 0.00 |
November | 20.35 | 0.00 | 20.35 | 5.31 | 79.54 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 0.00 | 13.20 | 0.10 | 123.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.27 | 1.13 | 37.14 | 31.31 | 61.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 0.00 | 13.20 | 0.10 | 20.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.95 | 5.87 | 59.09 | 75.76 | 142.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 19.83 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 39.87 | 75.35 | 0.00 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 85.85 | 42.81 | 13.00 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 129.55 | 28.21 | 49.50 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 164.98 | 20.60 | 37.17 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 184.43 | 23.92 | 29.00 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 181.12 | 29.71 | 20.17 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 152.98 | 30.53 | 25.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 113.71 | 41.02 | 1.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 71.42 | 34.17 | 11.50 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 32.64 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 14.10 | 83.38 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 99.52 | 46.69 | 187.67 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 14.10 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 184.43 | 99.04 | 49.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 19.83 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 39.87 | 75.35 | 0.00 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 85.85 | 42.81 | 13.00 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 129.55 | 28.21 | 49.50 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 164.98 | 20.60 | 37.17 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 184.43 | 23.92 | 29.00 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 181.12 | 29.71 | 20.17 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 152.98 | 30.53 | 25.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 113.71 | 41.02 | 1.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 71.42 | 34.17 | 11.50 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 32.64 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 14.10 | 83.38 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 99.52 | 46.69 | 187.67 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 14.10 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 184.43 | 99.04 | 49.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 19.83 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 39.87 | 75.35 | 0.00 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 85.85 | 42.81 | 13.00 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 129.55 | 28.21 | 49.50 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 164.98 | 20.60 | 37.17 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 184.43 | 23.92 | 29.00 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 181.12 | 29.71 | 20.17 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 152.98 | 30.53 | 25.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 113.71 | 41.02 | 1.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 71.42 | 34.17 | 11.50 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 32.64 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 14.10 | 83.38 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 99.52 | 46.69 | 187.67 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 14.10 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 184.43 | 99.04 | 49.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 19.83 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 39.87 | 75.35 | 0.00 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 85.85 | 42.81 | 13.00 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 129.55 | 28.21 | 49.50 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 164.98 | 20.60 | 37.17 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 184.43 | 23.92 | 29.00 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 181.12 | 29.71 | 20.17 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 152.98 | 30.53 | 25.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 113.71 | 41.02 | 1.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 71.42 | 34.17 | 11.50 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 32.64 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 14.10 | 83.38 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 99.52 | 46.69 | 187.67 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 14.10 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 184.43 | 99.04 | 49.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 19.83 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 39.87 | 75.35 | 0.00 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 85.85 | 42.81 | 13.00 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 129.55 | 28.21 | 49.50 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 164.98 | 20.60 | 37.17 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 184.43 | 23.92 | 29.00 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 181.12 | 29.71 | 20.17 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 152.98 | 30.53 | 25.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 113.71 | 41.02 | 1.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 71.42 | 34.17 | 11.50 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 32.64 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 14.10 | 83.38 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 99.52 | 46.69 | 187.67 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 14.10 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 184.43 | 99.04 | 49.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 19.83 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 39.87 | 75.35 | 0.00 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 85.85 | 42.81 | 13.00 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 129.55 | 28.21 | 49.50 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 164.98 | 20.60 | 37.17 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 184.43 | 23.92 | 29.00 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 181.12 | 29.71 | 20.17 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 152.98 | 30.53 | 25.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 113.71 | 41.02 | 1.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 71.42 | 34.17 | 11.50 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 32.64 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 14.10 | 83.38 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 99.52 | 46.69 | 187.67 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 14.10 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 184.43 | 99.04 | 49.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 19.83 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 39.87 | 75.35 | 0.00 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 85.85 | 42.81 | 13.00 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 129.55 | 28.21 | 49.50 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 164.98 | 20.60 | 37.17 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 184.43 | 23.92 | 29.00 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 181.12 | 29.71 | 20.17 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 152.98 | 30.53 | 25.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 113.71 | 41.02 | 1.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 71.42 | 34.17 | 11.50 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 32.64 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 14.10 | 83.38 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 99.52 | 46.69 | 187.67 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 14.10 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 184.43 | 99.04 | 49.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 19.83 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 39.87 | 75.35 | 0.00 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 85.85 | 42.81 | 13.00 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 129.55 | 28.21 | 49.50 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 164.98 | 20.60 | 37.17 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 184.43 | 23.92 | 29.00 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 181.12 | 29.71 | 20.17 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 152.98 | 30.53 | 25.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 113.71 | 41.02 | 1.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 71.42 | 34.17 | 11.50 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 32.64 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 14.10 | 83.38 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 99.52 | 46.69 | 187.67 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 14.10 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 184.43 | 99.04 | 49.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 19.83 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 39.87 | 75.35 | 0.00 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 85.85 | 42.81 | 13.00 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 129.55 | 28.21 | 49.50 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 164.98 | 20.60 | 37.17 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 184.43 | 23.92 | 29.00 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 181.12 | 29.71 | 20.17 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 152.98 | 30.53 | 25.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 113.71 | 41.02 | 1.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 71.42 | 34.17 | 11.50 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 32.64 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 14.10 | 83.38 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 99.52 | 46.69 | 187.67 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 14.10 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 184.43 | 99.04 | 49.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 19.83 | 99.04 | 0.00 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 39.87 | 75.35 | 0.00 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 85.85 | 42.81 | 13.00 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 129.55 | 28.21 | 49.50 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 164.98 | 20.60 | 37.17 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 184.43 | 23.92 | 29.00 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 181.12 | 29.71 | 20.17 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 152.98 | 30.53 | 25.33 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 113.71 | 41.02 | 1.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 71.42 | 34.17 | 11.50 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 32.64 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 14.10 | 83.38 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 99.52 | 46.69 | 187.67 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 14.10 | 20.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 184.43 | 99.04 | 49.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190265E+09 | 77183664.42 | 0.113082E+09 | 93686181.65 | 0.598725E+09 |
February | 0.249987E+09 | 0.122621E+09 | 0.127366E+09 | 0.175828E+09 | 0.418237E+09 |
March | 0.332324E+09 | 0.123798E+09 | 0.208526E+09 | 0.283082E+09 | 0.278376E+09 |
April | 0.468829E+09 | 0.231677E+09 | 0.237152E+09 | 0.517503E+09 | 0.175449E+09 |
May | 0.485771E+09 | 0.194080E+09 | 0.291691E+09 | 0.589024E+09 | 0.107616E+09 |
June | 0.550765E+09 | 0.238241E+09 | 0.312524E+09 | 0.697218E+09 | 93997136.74 |
July | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.781918E+09 | 0.101549E+09 |
August | 0.533701E+09 | 0.244088E+09 | 0.289613E+09 | 0.684257E+09 | 0.118414E+09 |
September | 0.419113E+09 | 0.198693E+09 | 0.220420E+09 | 0.499735E+09 | 0.167990E+09 |
October | 0.303128E+09 | 0.135122E+09 | 0.168006E+09 | 0.314962E+09 | 0.206793E+09 |
November | 0.175478E+09 | 65177503.11 | 0.110301E+09 | 0.124331E+09 | 0.333518E+09 |
December | 0.140049E+09 | 66606830.53 | 73442141.58 | 83345525.23 | 0.533783E+09 |
Annual Sum or Average | 0.446177E+10 | 0.198830E+10 | 0.247347E+10 | 0.484489E+10 | 0.313445E+10 |
Minimum of Months | 0.140049E+09 | 65177503.11 | 73442141.58 | 83345525.23 | 93997136.74 |
Maximum of Months | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.781918E+09 | 0.598725E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190265E+09 | 77183664.42 | 0.113082E+09 | 93686181.65 | 0.598725E+09 |
February | 0.249987E+09 | 0.122621E+09 | 0.127366E+09 | 0.175828E+09 | 0.418237E+09 |
March | 0.332324E+09 | 0.123798E+09 | 0.208526E+09 | 0.283082E+09 | 0.278376E+09 |
April | 0.468829E+09 | 0.231677E+09 | 0.237152E+09 | 0.517503E+09 | 0.175449E+09 |
May | 0.485771E+09 | 0.194080E+09 | 0.291691E+09 | 0.589024E+09 | 0.107616E+09 |
June | 0.550765E+09 | 0.238241E+09 | 0.312524E+09 | 0.697218E+09 | 93997136.74 |
July | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.781918E+09 | 0.101549E+09 |
August | 0.533701E+09 | 0.244088E+09 | 0.289613E+09 | 0.684257E+09 | 0.118414E+09 |
September | 0.419113E+09 | 0.198693E+09 | 0.220420E+09 | 0.499735E+09 | 0.167990E+09 |
October | 0.303128E+09 | 0.135122E+09 | 0.168006E+09 | 0.314962E+09 | 0.206793E+09 |
November | 0.175478E+09 | 65177503.11 | 0.110301E+09 | 0.124331E+09 | 0.333518E+09 |
December | 0.140049E+09 | 66606830.53 | 73442141.58 | 83345525.23 | 0.533783E+09 |
Annual Sum or Average | 0.446177E+10 | 0.198830E+10 | 0.247347E+10 | 0.484489E+10 | 0.313445E+10 |
Minimum of Months | 0.140049E+09 | 65177503.11 | 73442141.58 | 83345525.23 | 93997136.74 |
Maximum of Months | 0.612361E+09 | 0.291017E+09 | 0.321344E+09 | 0.781918E+09 | 0.598725E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52073982.96 | 0.00 | 52073982.96 | 542142.62 | 0.381456E+09 |
February | 59630661.61 | 0.00 | 59630661.61 | 5862068.99 | 0.267853E+09 |
March | 98960829.24 | 2684.40 | 98958144.85 | 43371570.18 | 0.172760E+09 |
April | 0.110796E+09 | 754006.91 | 0.110042E+09 | 79153295.36 | 0.104354E+09 |
May | 0.149190E+09 | 5777377.20 | 0.143413E+09 | 0.156080E+09 | 59704958.14 |
June | 0.168363E+09 | 15209045.09 | 0.153154E+09 | 0.196386E+09 | 52039428.63 |
July | 0.163211E+09 | 10950639.71 | 0.152260E+09 | 0.189145E+09 | 56633566.22 |
August | 0.137186E+09 | 2858059.88 | 0.134328E+09 | 0.157358E+09 | 66575642.84 |
September | 0.101528E+09 | 67832.33 | 0.101460E+09 | 95239000.17 | 99641650.79 |
October | 77929157.78 | 0.00 | 77929157.78 | 50186405.00 | 0.124883E+09 |
November | 52753737.13 | 0.00 | 52753737.13 | 13771840.46 | 0.206174E+09 |
December | 35359907.87 | 0.00 | 35359907.87 | 263699.69 | 0.331650E+09 |
Annual Sum or Average | 0.120698E+10 | 35619645.52 | 0.117136E+10 | 0.987358E+09 | 0.192373E+10 |
Minimum of Months | 35359907.87 | 0.00 | 35359907.87 | 263699.69 | 52039428.63 |
Maximum of Months | 0.168363E+09 | 15209045.09 | 0.153154E+09 | 0.196386E+09 | 0.381456E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52072306.59 | 0.00 | 52072306.59 | 542011.56 | 0.381457E+09 |
February | 59628805.47 | 0.00 | 59628805.47 | 5861403.18 | 0.267854E+09 |
March | 98957687.10 | 2684.27 | 98955002.83 | 43368675.32 | 0.172761E+09 |
April | 0.110793E+09 | 753971.57 | 0.110039E+09 | 79150153.19 | 0.104355E+09 |
May | 0.149186E+09 | 5777106.41 | 0.143409E+09 | 0.156074E+09 | 59704631.53 |
June | 0.168358E+09 | 15208332.23 | 0.153149E+09 | 0.196379E+09 | 52039036.01 |
July | 0.163206E+09 | 10950126.44 | 0.152256E+09 | 0.189139E+09 | 56633030.23 |
August | 0.137182E+09 | 2857925.91 | 0.134324E+09 | 0.157353E+09 | 66575229.98 |
September | 0.101525E+09 | 67829.15 | 0.101457E+09 | 95235736.97 | 99641114.45 |
October | 77926706.53 | 0.00 | 77926706.53 | 50183855.24 | 0.124883E+09 |
November | 52751976.39 | 0.00 | 52751976.39 | 13770792.33 | 0.206174E+09 |
December | 35358789.52 | 0.00 | 35358789.52 | 263633.33 | 0.331650E+09 |
Annual Sum or Average | 0.120695E+10 | 35617975.98 | 0.117133E+10 | 0.987320E+09 | 0.192373E+10 |
Minimum of Months | 35358789.52 | 0.00 | 35358789.52 | 263633.33 | 52039036.01 |
Maximum of Months | 0.168358E+09 | 15208332.23 | 0.153149E+09 | 0.196379E+09 | 0.381457E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 53103912.17 | 0.265281E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 96455428.12 | 0.182295E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.229931E+09 | 0.114657E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.335801E+09 | 73115495.69 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.441869E+09 | 55185384.36 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.478032E+09 | 62003238.78 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.485101E+09 | 79567652.70 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.409742E+09 | 81782774.96 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.294730E+09 | 0.106314E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.191284E+09 | 91511098.68 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 84598617.11 | 0.137235E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 0.223320E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.313840E+10 | 0.147227E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 55185384.36 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.485101E+09 | 0.265281E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 53103912.17 | 0.265281E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 96455428.12 | 0.182295E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.229931E+09 | 0.114657E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.335801E+09 | 73115495.69 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.441869E+09 | 55185384.36 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.478032E+09 | 62003238.78 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.485101E+09 | 79567652.70 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.409742E+09 | 81782774.96 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.294730E+09 | 0.106314E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.191284E+09 | 91511098.68 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 84598617.11 | 0.137235E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 0.223320E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.313840E+10 | 0.147227E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 55185384.36 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.485101E+09 | 0.265281E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 53103912.17 | 0.265281E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 96455428.12 | 0.182295E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.229931E+09 | 0.114657E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.335801E+09 | 73115495.69 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.441869E+09 | 55185384.36 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.478032E+09 | 62003238.78 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.485101E+09 | 79567652.70 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.409742E+09 | 81782774.96 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.294730E+09 | 0.106314E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.191284E+09 | 91511098.68 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 84598617.11 | 0.137235E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 0.223320E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.313840E+10 | 0.147227E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 55185384.36 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.485101E+09 | 0.265281E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 53103912.17 | 0.265281E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 96455428.12 | 0.182295E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.229931E+09 | 0.114657E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.335801E+09 | 73115495.69 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.441869E+09 | 55185384.36 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.478032E+09 | 62003238.78 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.485101E+09 | 79567652.70 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.409742E+09 | 81782774.96 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.294730E+09 | 0.106314E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.191284E+09 | 91511098.68 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 84598617.11 | 0.137235E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 0.223320E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.313840E+10 | 0.147227E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 55185384.36 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.485101E+09 | 0.265281E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 53103912.17 | 0.265281E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 96455428.12 | 0.182295E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.229931E+09 | 0.114657E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.335801E+09 | 73115495.69 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.441869E+09 | 55185384.36 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.478032E+09 | 62003238.78 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.485101E+09 | 79567652.70 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.409742E+09 | 81782774.96 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.294730E+09 | 0.106314E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.191284E+09 | 91511098.68 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 84598617.11 | 0.137235E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 0.223320E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.313840E+10 | 0.147227E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 55185384.36 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.485101E+09 | 0.265281E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 53103912.17 | 0.265281E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 96455428.12 | 0.182295E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.229931E+09 | 0.114657E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.335801E+09 | 73115495.69 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.441869E+09 | 55185384.36 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.478032E+09 | 62003238.78 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.485101E+09 | 79567652.70 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.409742E+09 | 81782774.96 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.294730E+09 | 0.106314E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.191284E+09 | 91511098.68 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 84598617.11 | 0.137235E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 0.223320E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.313840E+10 | 0.147227E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 55185384.36 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.485101E+09 | 0.265281E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 53103912.17 | 0.265281E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 96455428.12 | 0.182295E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.229931E+09 | 0.114657E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.335801E+09 | 73115495.69 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.441869E+09 | 55185384.36 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.478032E+09 | 62003238.78 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.485101E+09 | 79567652.70 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.409742E+09 | 81782774.96 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.294730E+09 | 0.106314E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.191284E+09 | 91511098.68 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 84598617.11 | 0.137235E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 0.223320E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.313840E+10 | 0.147227E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 55185384.36 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.485101E+09 | 0.265281E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 53103912.17 | 0.265281E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 96455428.12 | 0.182295E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.229931E+09 | 0.114657E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.335801E+09 | 73115495.69 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.441869E+09 | 55185384.36 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.478032E+09 | 62003238.78 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.485101E+09 | 79567652.70 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.409742E+09 | 81782774.96 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.294730E+09 | 0.106314E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.191284E+09 | 91511098.68 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 84598617.11 | 0.137235E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 0.223320E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.313840E+10 | 0.147227E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 55185384.36 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.485101E+09 | 0.265281E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 53103912.17 | 0.265281E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 96455428.12 | 0.182295E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.229931E+09 | 0.114657E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.335801E+09 | 73115495.69 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.441869E+09 | 55185384.36 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.478032E+09 | 62003238.78 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.485101E+09 | 79567652.70 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.409742E+09 | 81782774.96 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.294730E+09 | 0.106314E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.191284E+09 | 91511098.68 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 84598617.11 | 0.137235E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 0.223320E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.313840E+10 | 0.147227E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 55185384.36 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.485101E+09 | 0.265281E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 53103912.17 | 0.265281E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 96455428.12 | 0.182295E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.229931E+09 | 0.114657E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.335801E+09 | 73115495.69 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.441869E+09 | 55185384.36 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.478032E+09 | 62003238.78 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.485101E+09 | 79567652.70 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.409742E+09 | 81782774.96 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.294730E+09 | 0.106314E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.191284E+09 | 91511098.68 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 84598617.11 | 0.137235E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 0.223320E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.313840E+10 | 0.147227E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 37755436.01 | 55185384.36 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.485101E+09 | 0.265281E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 54.28 | 715.83 | 180.96 | 57.63 | 123.32 | 0.00 | 0.00 |
February | 133.55 | 550.55 | 255.97 | 101.37 | 154.59 | 0.00 | 0.00 |
March | 237.94 | 331.04 | 322.05 | 92.44 | 229.60 | 0.00 | 0.00 |
April | 458.58 | 214.10 | 447.24 | 179.34 | 267.90 | 0.00 | 0.00 |
May | 554.75 | 123.31 | 474.13 | 149.24 | 324.90 | 0.00 | 0.00 |
June | 687.20 | 110.37 | 554.88 | 195.56 | 359.32 | 0.00 | 0.00 |
July | 723.49 | 116.50 | 579.13 | 225.48 | 353.65 | 0.00 | 0.00 |
August | 627.77 | 137.46 | 500.96 | 184.40 | 316.56 | 0.00 | 0.00 |
September | 457.65 | 205.07 | 401.73 | 153.36 | 248.36 | 0.00 | 0.00 |
October | 269.98 | 244.98 | 284.54 | 100.90 | 183.64 | 0.00 | 0.00 |
November | 100.29 | 410.16 | 176.10 | 50.29 | 125.81 | 0.00 | 0.00 |
December | 51.22 | 635.02 | 130.98 | 49.74 | 81.24 | 0.00 | 0.00 |
Annual Sum or Average | 364.26 | 315.16 | 359.51 | 128.36 | 231.15 | 0.00 | 0.00 |
Minimum of Months | 51.22 | 110.37 | 130.98 | 49.74 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 723.49 | 715.83 | 579.13 | 225.48 | 359.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1117.33 | 8174.75 | 340.28 | 148.34 | 191.94 | 0.00 | 0.00 |
February | 2071.36 | 6195.78 | 466.12 | 233.18 | 232.94 | 0.00 | 0.00 |
March | 3961.98 | 2941.24 | 731.71 | 349.89 | 381.82 | 0.00 | 0.00 |
April | 5246.59 | 1487.49 | 993.55 | 596.93 | 396.61 | 0.00 | 0.00 |
May | 6507.64 | 696.13 | 1194.06 | 670.94 | 523.12 | 0.00 | 0.00 |
June | 7404.11 | 730.94 | 1357.84 | 794.17 | 563.68 | 0.00 | 0.00 |
July | 7368.86 | 940.79 | 1368.24 | 841.75 | 526.49 | 0.00 | 0.00 |
August | 5934.26 | 979.16 | 1139.24 | 648.65 | 490.58 | 0.00 | 0.00 |
September | 4346.44 | 1330.32 | 884.97 | 513.52 | 371.45 | 0.00 | 0.00 |
October | 2767.05 | 1550.22 | 562.48 | 278.80 | 283.68 | 0.00 | 0.00 |
November | 1449.47 | 3508.96 | 335.72 | 124.34 | 211.38 | 0.00 | 0.00 |
December | 731.04 | 6084.65 | 230.97 | 113.57 | 117.40 | 0.00 | 0.00 |
Annual Sum or Average | 4086.11 | 2870.10 | 802.16 | 443.86 | 358.31 | 0.00 | 0.00 |
Minimum of Months | 731.04 | 696.13 | 230.97 | 113.57 | 117.40 | 0.00 | 0.00 |
Maximum of Months | 7404.11 | 8174.75 | 1368.24 | 841.75 | 563.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145373E+09 | 0.191728E+10 | 0.484677E+09 | 0.154367E+09 | 0.330310E+09 | 0.00 | 0.00 |
February | 0.323095E+09 | 0.133190E+10 | 0.619234E+09 | 0.245241E+09 | 0.373992E+09 | 0.00 | 0.00 |
March | 0.637301E+09 | 0.886669E+09 | 0.862567E+09 | 0.247600E+09 | 0.614966E+09 | 0.00 | 0.00 |
April | 0.118865E+10 | 0.554945E+09 | 0.115925E+10 | 0.464862E+09 | 0.694385E+09 | 0.00 | 0.00 |
May | 0.148584E+10 | 0.330278E+09 | 0.126992E+10 | 0.399715E+09 | 0.870204E+09 | 0.00 | 0.00 |
June | 0.178121E+10 | 0.286083E+09 | 0.143825E+10 | 0.506899E+09 | 0.931352E+09 | 0.00 | 0.00 |
July | 0.193780E+10 | 0.312046E+09 | 0.155114E+10 | 0.603934E+09 | 0.947204E+09 | 0.00 | 0.00 |
August | 0.168141E+10 | 0.368165E+09 | 0.134177E+10 | 0.493892E+09 | 0.847878E+09 | 0.00 | 0.00 |
September | 0.118623E+10 | 0.531547E+09 | 0.104128E+10 | 0.397522E+09 | 0.643756E+09 | 0.00 | 0.00 |
October | 0.723104E+09 | 0.656162E+09 | 0.762111E+09 | 0.270243E+09 | 0.491868E+09 | 0.00 | 0.00 |
November | 0.259945E+09 | 0.106312E+10 | 0.456463E+09 | 0.130355E+09 | 0.326108E+09 | 0.00 | 0.00 |
December | 0.137197E+09 | 0.170084E+10 | 0.350817E+09 | 0.133214E+09 | 0.217603E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114871E+11 | 0.993904E+10 | 0.113375E+11 | 0.404784E+10 | 0.728963E+10 | 0.00 | 0.00 |
Minimum of Months | 0.137197E+09 | 0.286083E+09 | 0.350817E+09 | 0.130355E+09 | 0.217603E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193780E+10 | 0.191728E+10 | 0.155114E+10 | 0.603934E+09 | 0.947204E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.299267E+10 | 0.218952E+11 | 0.911401E+09 | 0.397312E+09 | 0.514089E+09 | 0.00 | 0.00 |
February | 0.501103E+10 | 0.149888E+11 | 0.112763E+10 | 0.564098E+09 | 0.563533E+09 | 0.00 | 0.00 |
March | 0.106118E+11 | 0.787782E+10 | 0.195982E+10 | 0.937155E+09 | 0.102266E+10 | 0.00 | 0.00 |
April | 0.135992E+11 | 0.385558E+10 | 0.257527E+10 | 0.154725E+10 | 0.102802E+10 | 0.00 | 0.00 |
May | 0.174301E+11 | 0.186453E+10 | 0.319817E+10 | 0.179706E+10 | 0.140112E+10 | 0.00 | 0.00 |
June | 0.191914E+11 | 0.189460E+10 | 0.351953E+10 | 0.205848E+10 | 0.146105E+10 | 0.00 | 0.00 |
July | 0.197367E+11 | 0.251982E+10 | 0.366470E+10 | 0.225455E+10 | 0.141015E+10 | 0.00 | 0.00 |
August | 0.158943E+11 | 0.262257E+10 | 0.305134E+10 | 0.173736E+10 | 0.131398E+10 | 0.00 | 0.00 |
September | 0.112660E+11 | 0.344820E+10 | 0.229385E+10 | 0.133104E+10 | 0.962804E+09 | 0.00 | 0.00 |
October | 0.741128E+10 | 0.415210E+10 | 0.150654E+10 | 0.746738E+09 | 0.759802E+09 | 0.00 | 0.00 |
November | 0.375702E+10 | 0.909521E+10 | 0.870186E+09 | 0.322288E+09 | 0.547898E+09 | 0.00 | 0.00 |
December | 0.195802E+10 | 0.162971E+11 | 0.618634E+09 | 0.304181E+09 | 0.314453E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128859E+12 | 0.905116E+11 | 0.252971E+11 | 0.139975E+11 | 0.112996E+11 | 0.00 | 0.00 |
Minimum of Months | 0.195802E+10 | 0.186453E+10 | 0.618634E+09 | 0.304181E+09 | 0.314453E+09 | 0.00 | 0.00 |
Maximum of Months | 0.197367E+11 | 0.218952E+11 | 0.366470E+10 | 0.225455E+10 | 0.146105E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.108441E+10 | -994288936.9 | 0.00 | 0.00 | 744.00 | 0.00 | -90125687.0 | 59.95 | 0.00 | 0.00 |
February | 0.101270E+10 | -931397085.8 | 0.00 | 0.00 | 672.00 | 0.00 | -81304415.1 | 59.95 | 0.00 | 0.00 |
March | 0.116709E+10 | -0.107787E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -89219370.9 | 59.95 | 0.00 | 0.00 |
April | 0.104806E+10 | -963505947.7 | 0.00 | 0.00 | 720.00 | 0.00 | -84558972.6 | 59.95 | 0.00 | 0.00 |
May | 0.102672E+10 | -944010770.5 | 0.00 | 0.00 | 744.00 | 0.00 | -82711698.0 | 59.95 | 0.00 | 0.00 |
June | 0.952592E+09 | -878259376.0 | 0.00 | 0.00 | 720.00 | 0.00 | -74332945.4 | 59.95 | 0.00 | 0.00 |
July | 0.875844E+09 | -801847038.7 | 0.00 | 0.00 | 744.00 | 0.00 | -73996570.6 | 59.95 | 0.00 | 0.00 |
August | 0.913577E+09 | -838910087.6 | 0.00 | 0.00 | 744.00 | 0.00 | -74666775.1 | 59.95 | 0.00 | 0.00 |
September | 0.865691E+09 | -790319418.4 | 0.00 | 0.00 | 720.00 | 0.00 | -75371976.6 | 59.95 | 0.00 | 0.00 |
October | 0.918756E+09 | -831284949.6 | 0.00 | 0.00 | 744.00 | 0.00 | -87471075.0 | 59.95 | 0.00 | 0.00 |
November | 0.938743E+09 | -852415919.7 | 0.00 | 0.00 | 720.00 | 0.00 | -86327078.7 | 59.95 | 0.00 | 0.00 |
December | 0.103641E+10 | -946293794.4 | 0.00 | 0.00 | 744.00 | 0.00 | -90115582.7 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.118406E+11 | -0.108504E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -990202147.7 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.865691E+09 | -0.107787E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -90125687.0 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.116709E+10 | -790319418.4 | 0.00 | 0.00 | 744.00 | 0.00 | -73996570.6 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.95 | 0.88 | 01-JAN-10:30 | 121.98 | 9.11 | 0.00 | 30.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.95 | 0.88 | 03-FEB-11:30 | 131.01 | 9.23 | 0.00 | 59.67 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.92 | 0.88 | 01-MAR-08:00 | 214.81 | 11.77 | 0.00 | 164.67 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.92 | 0.88 | 02-APR-14:39 | 239.53 | 11.76 | 0.00 | 189.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.91 | 0.88 | 01-MAY-07:30 | 797.94 | 12.54 | 0.00 | 264.50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.91 | 0.88 | 01-JUN-07:40 | 1988.92 | 12.87 | 0.00 | 282.33 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.91 | 0.88 | 01-JUL-07:00 | 1830.37 | 13.59 | 20.00 | 277.67 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.91 | 0.88 | 01-AUG-08:30 | 1101.34 | 12.98 | 14.67 | 260.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.92 | 0.88 | 01-SEP-07:40 | 212.33 | 11.66 | 0.00 | 161.33 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.94 | 0.88 | 02-OCT-09:20 | 162.51 | 10.28 | 0.00 | 93.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.94 | 0.88 | 01-NOV-10:09 | 139.26 | 9.75 | 0.00 | 51.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.98 | 0.88 | 18-DEC-12:30 | 79.33 | 6.95 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.93 | 713.77 | 11.49 | 34.67 | 1835.67 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 186.17 | 0.91 | 0.88 | 79.33 | 6.95 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 428.67 | 0.98 | 0.88 | 1988.92 | 13.59 | 20.00 | 282.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.83 | 0.64 | 05-JAN-15:30 | 369.74 | 24.34 | 129.17 | 44.83 | 133.38 | 21.48 | 118.17 | 0.00 |
February | 226.83 | 0.81 | 0.61 | 23-FEB-15:50 | 677.12 | 25.24 | 151.67 | 63.50 | 155.79 | 21.71 | 150.50 | 3.17 |
March | 334.33 | 0.79 | 0.61 | 03-MAR-16:10 | 423.60 | 23.90 | 212.67 | 112.50 | 310.14 | 24.26 | 233.33 | 45.00 |
April | 285.17 | 0.74 | 0.61 | 03-APR-14:39 | 499.91 | 23.33 | 182.17 | 124.17 | 489.64 | 24.20 | 240.17 | 85.33 |
May | 428.67 | 0.77 | 0.61 | 01-MAY-14:09 | 343.89 | 21.97 | 254.33 | 149.00 | 325.74 | 23.05 | 312.33 | 82.33 |
June | 400.67 | 0.73 | 0.61 | 01-JUN-16:30 | 403.24 | 22.46 | 275.50 | 206.83 | 489.40 | 23.72 | 323.67 | 106.50 |
July | 414.00 | 0.73 | 0.61 | 01-JUL-13:50 | 409.35 | 22.72 | 281.50 | 203.33 | 542.18 | 23.94 | 339.50 | 132.00 |
August | 410.83 | 0.75 | 0.61 | 01-AUG-14:39 | 408.92 | 22.53 | 258.83 | 175.67 | 425.12 | 23.52 | 306.50 | 108.17 |
September | 326.50 | 0.76 | 0.61 | 01-SEP-14:39 | 585.23 | 25.00 | 219.33 | 123.67 | 499.98 | 25.51 | 263.33 | 78.17 |
October | 325.17 | 0.81 | 0.61 | 01-OCT-14:00 | 469.59 | 24.69 | 203.50 | 81.00 | 194.03 | 23.61 | 213.00 | 24.00 |
November | 254.83 | 0.86 | 0.64 | 03-NOV-14:09 | 274.23 | 22.85 | 137.17 | 26.83 | 121.39 | 21.12 | 122.67 | 0.00 |
December | 186.17 | 0.89 | 0.68 | 01-DEC-15:09 | 229.01 | 22.48 | 76.00 | 15.17 | 97.19 | 19.84 | 47.33 | 0.00 |
Annual Sum or Average | 3807.33 | 0.78 | 425.42 | 23.34 | 2381.83 | 1326.50 | 346.02 | 23.27 | 2670.50 | 664.67 | ||
Minimum of Months | 186.17 | 0.73 | 0.61 | 229.01 | 21.97 | 76.00 | 15.17 | 97.19 | 19.84 | 47.33 | 0.00 | |
Maximum of Months | 428.67 | 0.89 | 0.68 | 677.12 | 25.24 | 281.50 | 206.83 | 542.18 | 25.51 | 339.50 | 132.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135811E+11 | 28022.44 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100611E+11 | 28022.44 | 01-FEB-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.793516E+10 | 28022.44 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.411848E+10 | 28022.44 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.762660E+09 | 28022.44 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 59072952.31 | 28022.44 | 05-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.294963E+09 | 28022.44 | 27-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272291E+10 | 28022.44 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.629732E+10 | 28022.44 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104901E+11 | 28022.44 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.563229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135811E+11 | 28022.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.498340E+11 | 69508.13 | 02-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359442E+11 | 69508.13 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217369E+11 | 69508.13 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.813045E+10 | 69508.13 | 02-APR-19:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.459789E+09 | 46350.10 | 03-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71812156.04 | 16723.63 | 30-SEP-04:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.348988E+10 | 66241.59 | 07-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205453E+11 | 69508.13 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396943E+11 | 69508.13 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.498340E+11 | 69508.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241728E+12 | 219803.60 | 18-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163103E+12 | 212277.31 | 01-FEB-20:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.870216E+11 | 149264.77 | 06-MAR-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190516E+11 | 89206.53 | 02-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.254201E+09 | 13258.59 | 02-MAY-02:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181592E+10 | 17352.44 | 24-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.907871E+11 | 147106.94 | 26-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185712E+12 | 219803.60 | 08-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.789474E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241728E+12 | 219803.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.156580E+09 | 0.106049E+09 | 5697.95 | 18-APR-15:10 | 3990.41 | 0.00 |
May | 0.00 | 0.00 | 0.370667E+09 | 0.275275E+09 | 6464.57 | 31-MAY-15:10 | 5298.07 | 0.00 |
June | 0.00 | 0.00 | 0.393088E+10 | 0.283639E+10 | 22733.87 | 26-JUN-05:01 | 11014.64 | 0.00 |
July | 0.00 | 0.00 | 0.649176E+10 | 0.442501E+10 | 22399.85 | 27-JUL-05:02 | 10047.55 | 0.00 |
August | 0.00 | 0.00 | 0.667067E+10 | 0.456240E+10 | 24458.65 | 04-AUG-05:01 | 9551.12 | 0.00 |
September | 0.00 | 0.00 | 0.243401E+10 | 0.206644E+10 | 20867.30 | 11-SEP-05:01 | 13189.40 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200546E+11 | 0.142716E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.667067E+10 | 0.456240E+10 | 24458.65 | 13189.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.291061E+10 | 0.189933E+10 | 48505.20 | 27-JUN-18:35 | 31817.88 | 0.00 |
July | 0.00 | 0.00 | 0.561430E+10 | 0.343691E+10 | 52781.86 | 03-JUL-19:55 | 25891.81 | 0.00 |
August | 0.00 | 0.00 | 0.428515E+10 | 0.260957E+10 | 52501.89 | 04-AUG-17:20 | 25684.21 | 0.00 |
September | 0.00 | 0.00 | 0.143973E+10 | 0.112809E+10 | 45019.43 | 10-SEP-14:15 | 36572.69 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142498E+11 | 0.907390E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.561430E+10 | 0.343691E+10 | 52781.86 | 36572.69 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139786E+10 | 0.08 | 523.07 | 01-JAN-00:03 | 0.08 |
February | 0.123207E+10 | 0.08 | 523.07 | 01-FEB-00:02 | 0.08 |
March | 0.104682E+10 | 0.06 | 523.07 | 01-MAR-00:02 | 0.08 |
April | 0.396096E+09 | 0.02 | 523.07 | 01-APR-00:05 | 0.08 |
May | 16790591.68 | 0.00 | 523.07 | 01-MAY-22:10 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.100168E+09 | 0.01 | 523.07 | 16-OCT-22:40 | 0.08 |
November | 0.885037E+09 | 0.05 | 523.07 | 10-NOV-00:50 | 0.08 |
December | 0.139158E+10 | 0.08 | 523.07 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.646642E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139786E+10 | 0.08 | 523.07 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.835056E+09 | 0.59 | 1136.20 | 02-JAN-06:01 | 0.95 |
February | 0.694183E+09 | 0.50 | 1136.20 | 01-FEB-02:62 | 0.96 |
March | 0.703735E+09 | 0.39 | 1136.20 | 01-MAR-06:01 | 0.96 |
April | 0.562294E+09 | 0.29 | 1136.20 | 01-APR-05:01 | 0.95 |
May | 0.490575E+09 | 0.24 | 1136.20 | 01-MAY-05:01 | 0.95 |
June | 0.475585E+09 | 0.23 | 1136.20 | 05-JUN-05:02 | 0.95 |
July | 0.465619E+09 | 0.22 | 1136.20 | 01-JUL-05:02 | 0.94 |
August | 0.505729E+09 | 0.24 | 1136.20 | 01-AUG-05:02 | 0.94 |
September | 0.461587E+09 | 0.23 | 1136.20 | 08-SEP-05:02 | 0.94 |
October | 0.524835E+09 | 0.25 | 1136.20 | 02-OCT-05:01 | 0.95 |
November | 0.607110E+09 | 0.36 | 1136.20 | 01-NOV-05:01 | 0.95 |
December | 0.741352E+09 | 0.48 | 1136.20 | 01-DEC-06:11 | 0.95 |
Annual Sum or Average | 0.706766E+10 | 0.33 | |||
Minimum of Months | 0.461587E+09 | 0.22 | 1136.20 | 0.94 | |
Maximum of Months | 0.835056E+09 | 0.59 | 1136.20 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182605E+10 | 0.67 | 1859.98 | 02-JAN-00:03 | 0.92 |
February | 0.147384E+10 | 0.63 | 1859.98 | 01-FEB-00:02 | 0.93 |
March | 0.128558E+10 | 0.54 | 1859.98 | 01-MAR-00:02 | 0.93 |
April | 0.926519E+09 | 0.40 | 1859.98 | 02-APR-19:42 | 0.92 |
May | 0.777557E+09 | 0.23 | 1240.29 | 03-MAY-05:01 | 0.92 |
June | 0.776556E+09 | 0.23 | 1739.77 | 29-JUN-17:12 | 0.88 |
July | 0.766190E+09 | 0.22 | 1859.98 | 03-JUL-17:10 | 0.91 |
August | 0.802330E+09 | 0.22 | 1760.49 | 02-AUG-17:12 | 0.88 |
September | 0.738583E+09 | 0.21 | 854.17 | 30-SEP-06:10 | 0.61 |
October | 0.822412E+09 | 0.33 | 1772.57 | 07-OCT-05:01 | 0.92 |
November | 0.117389E+10 | 0.51 | 1859.98 | 13-NOV-06:01 | 0.92 |
December | 0.161202E+10 | 0.63 | 1859.98 | 02-DEC-06:01 | 0.92 |
Annual Sum or Average | 0.129815E+11 | 0.40 | |||
Minimum of Months | 0.738583E+09 | 0.21 | 854.17 | 0.61 | |
Maximum of Months | 0.182605E+10 | 0.67 | 1859.98 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.835056E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.694183E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.703735E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.601665E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.582754E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.139752E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.194789E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.204449E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.104691E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.524835E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.607110E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.741352E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.117275E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.524835E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.204449E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.182605E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.147384E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.128558E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.926519E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.777557E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.148350E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.208926E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.182974E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.110942E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.822412E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.117389E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.161202E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164098E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.777557E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.208926E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.835056E+09 | 0.00 | 0.135811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694183E+09 | 0.00 | 0.100611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.703735E+09 | 0.00 | 0.793516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.562294E+09 | 0.156580E+09 | 0.411848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.490575E+09 | 0.370667E+09 | 0.762660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.475585E+09 | 0.391607E+10 | 59072952.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.465619E+09 | 0.645681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.505729E+09 | 0.663374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.461587E+09 | 0.242676E+10 | 0.294963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.524835E+09 | 0.00 | 0.272291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.607110E+09 | 0.00 | 0.629732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.741352E+09 | 0.00 | 0.104901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706766E+10 | 0.199606E+11 | 0.563229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.461587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.835056E+09 | 0.663374E+10 | 0.135811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182605E+10 | 0.00 | 0.498340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147384E+10 | 0.00 | 0.359442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128558E+10 | 0.00 | 0.217369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.926519E+09 | 0.00 | 0.813045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.777557E+09 | 0.00 | 0.459789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.776556E+09 | 0.288869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.766190E+09 | 0.546238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802330E+09 | 0.425357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.738583E+09 | 0.143514E+10 | 71812156.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.822412E+09 | 0.00 | 0.348988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117389E+10 | 0.00 | 0.205453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161202E+10 | 0.00 | 0.396943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129815E+11 | 0.140398E+11 | 0.179907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.738583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182605E+10 | 0.546238E+10 | 0.498340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.835056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.703735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.562294E+09 | 0.00 | 0.00 | 0.00 | 39371141.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.490575E+09 | 0.00 | 0.00 | 0.00 | 92178836.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.475585E+09 | 0.00 | 0.00 | 0.00 | 0.921932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.465619E+09 | 0.00 | 0.00 | 0.00 | 0.148227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.505729E+09 | 0.00 | 0.00 | 0.00 | 0.153876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.461587E+09 | 0.00 | 0.00 | 0.00 | 0.585319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.524835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.607110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.741352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706766E+10 | 0.00 | 0.00 | 0.00 | 0.465983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.461587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.835056E+09 | 0.00 | 0.00 | 0.00 | 0.153876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.182605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.926519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.777557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.776556E+09 | 0.00 | 0.00 | 0.00 | 0.706942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.766190E+09 | 0.00 | 0.00 | 0.00 | 0.132307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802330E+09 | 0.00 | 0.00 | 0.00 | 0.102741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.738583E+09 | 0.00 | 0.00 | 0.00 | 0.370833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.822412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129815E+11 | 0.00 | 0.00 | 0.00 | 0.342825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.738583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182605E+10 | 0.00 | 0.00 | 0.00 | 0.132307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383998E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299741E+10 | 0.00 | 0.00 | 0.13 |
March | 21127313.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244314E+10 | 0.00 | 0.00 | 0.13 |
April | 0.235178E+09 | 25653089.45 | 0.00 | 22903.41 | 7258986.26 | 0.143296E+10 | 32301081.30 | 0.00 | 0.13 |
May | 0.668848E+09 | 32963533.89 | 0.00 | 231392.73 | 163624.75 | 0.149646E+09 | 0.232504E+09 | 0.00 | 0.17 |
June | 0.204955E+09 | 0.508949E+09 | 0.00 | 2456658.35 | 0.00 | 7700972.54 | 0.880350E+09 | 0.00 | 0.35 |
July | 410750.85 | 0.809711E+09 | 0.00 | 3653600.70 | 228.05 | 0.00 | 0.693631E+09 | 0.00 | 0.41 |
August | 927066.65 | 0.858620E+09 | 0.00 | 3394731.65 | 238468.70 | 0.00 | 0.788671E+09 | 0.00 | 0.45 |
September | 0.353857E+09 | 0.152045E+09 | 0.00 | 2526235.84 | 0.00 | 97628400.62 | 0.108955E+10 | 0.00 | 0.30 |
October | 0.449913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103575E+10 | 0.00 | 0.00 | 0.12 |
November | 0.150556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204513E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321705E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.208577E+10 | 0.238794E+10 | 0.00 | 12285522.67 | 7661307.76 | 0.172664E+11 | 0.371701E+10 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.668848E+09 | 0.858620E+09 | 0.00 | 3653600.70 | 7258986.26 | 0.383998E+10 | 0.108955E+10 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126312E+11 | 0.00 | 0.00 | 0.17 |
February | 0.790986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882043E+10 | 0.00 | 0.00 | 0.18 |
March | 0.238949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465225E+10 | 0.00 | 0.00 | 0.19 |
April | 0.325780E+10 | 0.00 | 0.00 | 0.00 | 0.130103E+09 | 0.130008E+10 | 0.00 | 0.00 | 0.18 |
May | 0.245556E+10 | 0.00 | 0.00 | 0.00 | 41074988.20 | 20170670.16 | 0.00 | 0.00 | 0.18 |
June | 0.226497E+10 | 0.446146E+09 | 0.00 | 390592.87 | 9071108.26 | 0.00 | 0.285523E+09 | 0.00 | 0.21 |
July | 0.111721E+10 | 0.777162E+09 | 0.00 | 2374578.85 | 0.00 | 0.00 | 0.124910E+10 | 0.00 | 0.25 |
August | 0.132842E+10 | 0.734374E+09 | 0.00 | 2112268.22 | 1652836.26 | 0.00 | 0.123702E+10 | 0.00 | 0.25 |
September | 0.295184E+10 | 0.125074E+09 | 0.00 | 710326.43 | 38676.59 | 0.00 | 0.357384E+09 | 0.00 | 0.20 |
October | 0.344765E+10 | 0.00 | 0.00 | 0.00 | 5609638.06 | 0.211116E+09 | 0.00 | 0.00 | 0.17 |
November | 0.175663E+10 | 0.00 | 31674.93 | 0.00 | 57636.69 | 0.460771E+10 | 0.00 | 707.81 | 0.17 |
December | 0.412667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987144E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.224153E+11 | 0.208276E+10 | 31674.93 | 5587766.38 | 0.187608E+09 | 0.421144E+11 | 0.312903E+10 | 707.81 | 0.19 |
Minimum of Months | 0.242032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.344765E+10 | 0.777162E+09 | 31674.93 | 2374578.85 | 0.130103E+09 | 0.126312E+11 | 0.124910E+10 | 707.81 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:44
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.361852E+12 | 0.176676E+12 | 0.00 | 0.167132E+11 | 0.865444E+11 |
February | 0.433032E+12 | 0.123250E+12 | 0.00 | 0.126088E+11 | 0.600273E+11 |
March | 0.720650E+12 | 0.844249E+11 | 0.00 | 0.950601E+10 | 0.351235E+11 |
April | 0.886967E+12 | 0.369541E+11 | 0.00 | 0.609533E+10 | 0.106996E+11 |
May | 0.105908E+13 | 0.181782E+11 | 0.00 | 0.345276E+10 | 0.111199E+10 |
June | 0.112329E+13 | 0.223630E+11 | 0.00 | 0.268742E+10 | 0.849943E+10 |
July | 0.115220E+13 | 0.278566E+11 | 0.00 | 0.149292E+10 | 0.149114E+11 |
August | 0.997465E+12 | 0.333343E+11 | 0.00 | 0.178730E+10 | 0.135220E+11 |
September | 0.689622E+12 | 0.377056E+11 | 0.00 | 0.458658E+10 | 0.501076E+10 |
October | 0.478951E+12 | 0.329738E+11 | 0.00 | 0.513882E+10 | 0.349106E+10 |
November | 0.258597E+12 | 0.876988E+11 | 0.00 | 0.855994E+10 | 0.345324E+11 |
December | 0.175378E+12 | 0.139402E+12 | 0.00 | 0.135011E+11 | 0.678136E+11 |
Annual Sum or Average | 0.833708E+13 | 0.820817E+12 | 0.00 | 0.861303E+11 | 0.341287E+12 |
Minimum of Months | 0.175378E+12 | 0.181782E+11 | 0.00 | 0.149292E+10 | 0.111199E+10 |
Maximum of Months | 0.115220E+13 | 0.176676E+12 | 0.00 | 0.167132E+11 | 0.865444E+11 |